TROUBLESHOOTING OF TRANSFORMER TROUBLE SHOOTING OF TRANSFORMER NO. 01. TROUBLE Stop of transformer (Except OLTC) CAUSE Internal fault of main tank ACTION Check on relay operation. Electrical tests Measurement of insulation resistance 1-1 1–2 1–3 Operation of differntial relay and buchholz relay or pressure relief device operate simultaneously Operation of buchholz relay and pressure relief device (1) Internal fault Operation of buchholz relay and pressure relief device Measurement of winding resistance Measurement of voltage ratio. Measurement of exciting current Gas analysis of transformer Action shall be same as internal fault procedures. (2) Internal fault (1) Internal fault Action shall be same as internal fault procedures. (2 Internal fault Action shall be same as internal fault procedures. (1) Internal fault Action shall be same as internal fault procedures. (2) Inrush current at time of energyization (1) Action shall be same as internal fault procedures. (2)-1 Setting values of relays. (2)-2 Value of inrush current. 1–4 Operation of buchholz relay (trip) only (1) Internal fault (2) Faulty operation (1) Action shall be same as internal fault procedures. (2)-1 Check wiring. (2)-2 Check contacts. 1-5 Operation of pressure device Only (1) Internal fault (2) Faulty Operation ) Action shall be same as internal fault procedures. (2)-1 Check wiring. (2)-2 Check contacts. 1–6 Winding temp. indicator or oil temp. indicator (1) Internal fault (2) Faulty operation (3) Stop of cooling fan. (1) Action shall be same as internal fault procedures. (2)-1 Check wiring (2)-2 Sudden variation of oil temperature. (3) Check cooling fan. TROUBLE SHOOTING OF TRANSFORMER NO. 02. TROUBLE Operation of buchholz: relay (alarm) only CAUSE ACTION (1) Internal fault (2) Trapped air or evaluation of dissolved gases (1) Action shall be same as internal fault procedures. (2) -1 Analysis of gas Accumulated in Buchholz Relay. (2)-2 Sudden variation of oil temperature. 03. (1) Action shall be same as internal fault procedures. 04. Operation of relays such as over current relay, ground relay, arrestor etc. (1) Internal fault (2) External faults such as short- circuit In the system Abnormality is found in recording devices - ditto - High temperature rise Burned coil (2) -1 Check any sign of Heavy current circulation in the windings. (2) -2 Check any sign of on-load tap changer interrupting heavy short-circuit current. Short-circuit current value, its duration time. - ditto - Period required to If the oil temperature is about 80`C over, Reach the maximum the transformer must not be operated temperature and continuously. ambient temperature, Load factor or type of load. Connection diagram of bank and internal connection tap voltage. Date and time of burning. Installation site. Period of use (immediately after operation period). Cause of failure: Overload Lighting Short circuiting (internal or external) Others Existence or absence of copper powder. Operation of protective devices (primary and secondary) Local heating Heated point. Load factor or type of load. Smoke. Discoloration. Insulation resistance: Insulation resistance failure Noise High voltage winding to low voltage winding and tank. Low voltage winding to high voltage winding and tank. High voltage winding to low voltage winding. Temperature and humidity at which mea surement is made. Installation site (indoors or outdoors). History of the transformer. Dielectric strength of the insulation oil. Operating conditions (overload, normal)