Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 ac Enhancement of the Grounding System of 132/33 kV Subtransmission Station via an ETAP-Based Approach Hachimenum Amadi, Peter Nwauju, Dikio Idoniboyeobu Department of Electrical Engineering, Rivers State University, Port-Harcourt, Nigeria *Corresponding Author E-Mail Id: hachimenum.amadi@ust.edu.ng ABSTRACT Using the IEEE approach for grounding design and ETAP software for system modelling, this study seeks to enhance the grounding system at the 132/33kV Afam 1 Sub-transmission station. To get the desired effects, the touch voltage, step voltage, and mesh voltage are chosen. The findings indicate that the current grounding system of the station is in terrible shape. Three of the six grounding pits of the station have been undermined, two have been vandalised, and the one pit that is still in place is insufficient to support the station. Based on the results of the violations, the earth resistance values for Pits 1, 2, and 3 are 2.63, 1.25, and 1.16, respectively. The study used 1.5 bags of salt, six bags of ashes and some water to reduce soil resistance in pits 1, 2, and 3. Soil resistance in pits 1, 2, and 3 was reduced to 0.67, 0.59, and 0.5, respectively, after treatment, resulting in a 70% reduction in resistivity. Pits 4 and 5 require the installation of new grounding systems in place of existing ones. The grid structure of the sub-transmission station comprises squares that are 100 m by 90 m in size, making a total mesh area of 9000 m. The X-axis has 18 conductors, and the Y-axis has 19 conductors. The grid conductor was buried at depth of 0.6 metres, its diameter is 16 millimetres, its total length is 5972 metres, the crushed rock thickness is 1 metre, there are 280 ground rods, and each earth rod is 3 metres long. The station's ground rod spacing is 8 metres. The investigation also discovered that for a 70-kilogramme person with a 0.5-second fault length and a 0.6 current division factor, a fault current of 13785A and a touch voltage of 557.3 Volts were calculated. The temperature at which the thermal coefficient of resistance is zero degrees Celsius, the ambient temperature and the maximum temperature are all fixed at 40 degrees Celsius. The allowable touch voltage and the permitted step voltage at the fault location must be 529.29 and 450.87 volts, respectively, based on the 3-kA ground shortcircuit current and the 15 ratio. The ground potential rise (GPR) was 2098.7 Volts, the permitted step voltage was 2823.6 Volts, and the actual step voltage was 205.4 Volts. The grid works safely because the GPR is within allowable bounds. From the findings, treating the soil resistivity in pits 1, 2, and 3 and replacing the grounding systems in pits 4 and 5 outrightly are the best ways to stop electrical failures and fatalities. The study recommends that the station earth resistance be checked annually using an earth resistance tester. Keywords: Earthing, earthing system, grounding system, optimization, sub-transmission station, transmission INTRODUCTION When working near earthed equipment and facilities, people must be protected from electrical shock by having the electrical system earthed [1]. The configuration, chemical makeup, wetness, temperature, season, depth, diameter, and other characteristics of the ground, which serves as an electrical conductor, can all affect the conductivity of the ground [2]. A homogeneous electrical potential on the HBRP Publication Page 27-37 2023. All Rights Reserved Page 27 ac ground that is close to absolute zero is what an earthing structure is meant to achieve [3]. Its reference system, however, may experience voltage changes due to the earth's natural variations [4]. The resistance of the earth resistance and the intensity of the fault current both affect this variation, which is known as the Earth Potential Rise (EPR). For an earthing system to be functional, the ground resistance must be as low as possible to reduce the EPR. The allowable resistance levels for distribution substations might range from 1 to 5 Ohm, depending on the local circumstances [5].In the past, earthing power transformer substations involved a labour-intensive process of digging a large pit, inserting grounding rods, and connecting them to the power transformers and substation hardware. The resistance of grounding electrode systems can greatly vary due to various factors such as electrode resistance, rod surface area, rod size, and electrode material composition [6]. Adherence to proper grounding standards is crucial for transmission lines and substations. A welldesigned regularly maintained earthing system with ample room for future growth is essential for its reliable and efficient functioning. It's important to ensure the earthing system is both reliable and futureproof. For the safety of an electrical station or substation and its users, an appropriate earthing system must be designed and installed [7]. To safeguard against electrical outages and lightning strikes as well as to guarantee the proper operation of control and protection systems, an efficient earthing system is required. Strong currents, such as those caused by lightning strikes, can be safely redirected to the ground with the use of the earthing system [8]. The substation and its users are at risk of damage or even death without a properly constructed edging system [5]. Given that electricity forms the basis for Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 numerous scientific and social advancements, its significance in contemporary society cannot be emphasised [9]. The preservation of human life is paramount and an earthing system is necessary to ensure safety within and around the substation. If the grid design does not fulfil these standards, it is advised to minimise the available ground fault current to enhance the power quality of a system and adhere to regulatory limits for tolerable touch voltage [10]. When a system is connected to a metal object that is buried in the ground and allows electricity to pass through the earth, the system is said to be grounded [5]. According to Reference, [11], power quality is the degree to which the parameters of the power supply, including voltage, frequency, and others, adhere to legal restrictions. The electrical station system’s neutral and the earth create a low-impedance electrical connection for the grounding system [12]. To ensure that people and other living things can safely touch metal objects connected to the system's neutral, the earth's potential in a three-phase system must be of the same value as the neutral's potential. To ensure low resistivity, it is crucial to take into account changes in soil resistivity when designing a grounding system. Soil resistivity is a critical element in the performance of a grounding system [13]. Modern substation system design now places a significant emphasis on the value of reliable grounding systems. To ensure the dependability of electric power generation, transmission and distribution, grounding is essential [14]. Protect people, equipment, and power users from lightning strikes or electrical fault currents and helps to avoid high voltage spikes during disturbances. In order to ensure the safe and dependable operation of the electrical power system, grounding is crucial. HBRP Publication Page 27-37 2023. All Rights Reserved Page 28 ac To lessen the voltage spike that occurs after a malfunction, high-voltage substations need to have extraordinarily low ground resistance. The most common method for accomplishing this is the deployment of interconnected ground networks [15]. In corrosive soils with high dampness, salt substance, and temperature, ground poles and their associations are susceptible to corrosion over the long run. Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 Even if the resistance of the grounding system was initially modest, it may increase if the ground rods begin to corrode [16]. The earthing solution for sub-transmission stations presented in this study is useful and efficient, and it can stop dangerous voltage spikes in both normal and abnormal circumstances. A comprehensive assessment of the soil resistivity in your area is provided in Table 1 below. Table 1: Guide to Soil Resistivity (Ω·M). Type of soil Climatic Condition Normal and high rainfall Range of values Alluvium and lighter clays Depends on water level of locality Clays 5 to 20 Marls 10 to 30 Porous Limestone 30 to 100 Porous Sandstone 30 to 300 Quartzites, compact and 100 to 1000 crystalline limestone Clay slates and slatey shales 300 to 3000 Granite 1000 Fissile states, schist, gneiss and 1000 upwards igneous rocks Source: [17] On-site measurement is required to establish the soil resistivity precisely. This is essential because the soil is important in the distribution of the fault current. To adequately protect against earth faults, field data such as soil surface layers and underlying geological structures should be gathered. In order to determine the viability of the protection system based on the buried depth and substance of the earth electrodes being utilized, the stratification of the soil should also be analysed. The ideal location for the substation should be determined using a feasibility analysis, taking into account the soil resistivity, even though it may not be feasible to change the underlying soil qualities. The following is the recommended list of locations for substations: Underground waters Range of values 1 to 5 2 to 5 30 to 100 (i) Wet sand, peat, and marshy soils; (ii) Clay, clayey soil, arable and loamy land, or mixed and composite of small sands; (iii) Loamy clay and composite of small stones, sands, and gravels. The following specifications should be taken into account when choosing a conductor material for underground use: Ability to withstand all weather conditions. Adequate current carrying capacity for all currents and durations in both normal and fault operation settings. Capability to discharge highfrequency currents to lower surge impedance. HBRP Publication Page 27-37 2023. All Rights Reserved Page 29 Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 ac Capability to carry current at all temperatures in both normal and fault states. MATERIALS AND METHOD The grounding system of the 132/33kV Afam 1 Sub transmission station was enhanced by utilising data gathered from the Transmission Company of Nigeria maintenance unit. This information included data on the earthing conductor, the earth mat, the earth connectivity, the earth electrode, the grid design, the soil resistivity, and the surface layer using step and touch potentials. An earthing mat that satisfied the specifications of the earthing system and was within the permitted ranges for the step potential, touch potential, and transfer potential was produced using the simulation software known as the Transient Analyser Programme (ETAP). The study deployed the electrical transient analyser programme (ETAP) simulation software and the Institute of Electrical and Electronic Engineers (IEEE) technique in the design of the station earthing system. The earthing system dimension is 100 x 90 meters and the average soil resistivity is assumed to be 57.4 meters. It is important to take the surface layer of high resistivity area into account when building the earthing grid to ensure safety and protection against the current in the station with high resistivity top/lower soil. Touch Potential According to reference [10], there is a risk of dangerous voltage gradients in the earth near a power generation site, when there are no alternative channels for earth faults, but the earth itself, which can cause electrical shock hazards. These hazards include touch voltages, which are the potential difference between the earth and a metallic object that a person is touching, and step voltages, which are the voltage gradient between two feet that are planted firmly on the ground. The earthing grid helps to mitigate these hazards by lowering voltage gradients and distributing fault currents to remote earth [18]. Engineers use calculations of touch and step potentials to determine if the earthing grid is capable of dissipating fault currents and preventing dangerous touch and step voltages. Fig. 1: The 132/33KV Afam I Sub-transmission Station [18]. The mesh voltage, , was subsequently determined [18]: HBRP Publication Page 27-37 2023. All Rights Reserved Page 30 Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 ac (1.1) V Given height h= 0.472m and spacing between conductors D= 5 m and n= 7.363. Spacing Factor for Step Voltage In finding the step factor, we have: [ ( )] Step Potential Whenever compared to the touch potential, the step potential is frequently of a lesser magnitude as the ground is touched sequentially by the feet. The human body can endure a greater current when subjected to an electrical shock due to the current flow transpiring between the feet (1.2) as opposed to through vital organs such as the heart. The step potential must be less than the step voltage criteria to create a secure earthing system. The step potential E s is represented in [19] and found as follows: (1.3) RESULTS AND DISCUSSION By modifying the voltages based on variables such the soil resistivity, soil layer, and shock current duration, ETAP simulation software allows for the achievement of the target soil resistivity level of 2500 ohm-meters. Any unwanted circuit's maximum voltage must not be higher than the step voltage and touch voltage restrictions. This design features a 100-meter by 90-meter square grid configuration with a total mesh area of 9000 square meters, ground rod spacing of 8 meters, grid conductor burial depth of 0.6 meters, grid conductor diameter of 16 millimetres, 18 conductors in the x-axis, 19 conductors in the y-axis, total conductor length of 5972 meters, 1 meter of crushed rock thickness, and 280 ground rods with a length of 3 meters each, as illustrated in Figure 2. HBRP Publication Page 27-37 2023. All Rights Reserved Page 31 ac Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 Fig. 2: The Earthing Pit Position in the 132/33KV Afam 1 Sub-transmission Station [18]. Fig. 3: The Distance and the Violated Earth Pit 1 Resistance Rating. The result shown in Figure 4 indicates that the actual earth resistance value for Pit 2 that has been violated is 1.25Ω. HBRP Publication Page 27-37 2023. All Rights Reserved Page 32 Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 ac Fig. 4: The Distance and the Violated Earth Pit 2, Resistance Rating. The 132/33kV Afam 1 sub-transmission station's earthing system is in disrepair, with three of the substation's six earthing pits broken, two vandalised, and the remaining pit unable to provide appropriate service. For pits 1, 2, and 3, the soil resistivity was treated with six bags of ashes and 1.5 bags of salt and water, resulting in a 70% reduction in soil resistivity. New earthing systems need to be installed in pits 4 and 5. The treated earth resistance values for Pits 1 and 2 are 0.67 and 0.59, respectively, according to the data illustrated in Figures 5 and 6 and Tables 2 and 3 [18]. Fig. 5: The Distance and the Treated Earth Pit 1 Resistance Values. The result shown in Figure 6 indicates that the actual earth resistance value for Pit 2 that has been treated is 0.59Ω. HBRP Publication Page 27-37 2023. All Rights Reserved Page 33 Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 ac Fig. 6: The Distance and the Treated Earth Pit 2. Resistance Values. Table 2: The Distance and the Treated Earth Resistance Values of Pit 1 [18]. Distance Resistance S/No. (M) (Ω) 1 4 0.75 2 8 0.67 3 12 0.84 Actual Earth Resistance for 0.67 Pit 1 Table 3: The Distance and the Treated Earth Resistance Values of Pit 2 [18]. The result shown in Figure 7 shows the difference between the violated earth pit and the treated earth pit 1, indicating that the resistance of pit 1 is 100% normal. HBRP Publication Page 27-37 2023. All Rights Reserved Page 34 ac Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 Fig. 7: The difference between the violated and treated earth pit 1 resistance (Ω). The result shown in Figure 8 illustrates the difference between the violated soil pit and the treated soil pit 2, indicating that the resistance to pit 2 is 100% normal. Fig. 8: The difference between the violated and treated earth pit 2 resistance (Ω). Table 4: The difference between the violated and treated earth pit 1 resistance (Ω). DISTANCE (M) Violated RESISTANCE (Ω) Treated RESISTANCE (Ω) I4 4.39 0.75 8 3.21 0.67 12 2.63 0.84 Table 5: The difference between the violated and treated earth Pit 2 resistance (Ω). DISTANCE (M) Violated RESISTANCE (Ω) Treated RESISTANCE (Ω) 4 1.27 0.59 8 1.25 0.75 12 1.39 0.64 HBRP Publication Page 27-37 2023. All Rights Reserved Page 35 ac CONCLUSION AND RECOMMENDATIONS The IEEE approach was used to model and simulate the 132/33KV sub-transmission substation with the aid of the Electrical Transient Analyser Programme (ETAP) software. The simulation revealed issues with the substation's earthing system, including broken and vandalized pits and insufficient support. Measures were taken to reduce the soil resistivity of the affected pits, but further maintenance and rebuilding of the earthing system are recommended to ensure optimal performance and reliability of the substation. Additionally, the simulation results showed that the touch voltage, step voltage, and mesh voltage of the substation met the desired values. The earth resistance of Pits 1, 2, and 3, however, were discovered to have exceeded the permissible values having read 2.63, 1.25, and 1.16 respectively. As a result, each of the pits was treated with ashes, salt, and water, which resulted in a reduction in soil resistivity of 70%. Additionally, it was discovered that the substation has a fault duration of 0.5 seconds, a fault current of 13785 amps, a rated ambient temperature of 40 volts, a current division factor of 0.6, and more, a grid short circuit current of 3 kA, a maximum permissible temperature of 1084 volts, and a temperature of the thermal coefficient of resistivity at zero volts. The substation is safe and within the permissible safe limits because the ground potential rise (GPR) was measured at 2098.7 volts, which is lower than the allowable limits. It is important to continue monitoring and maintaining the earthing system and the soil resistivity of the substation to ensure optimal performance and reliability of the substation over time. Also, the earthing systems of pits 4 and 5 need to be urgently rebuilt. Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 2. 3. 4. 5. 6. 7. 8. 9. REFERENCES 1. Patil, A. (2017). Substation Earthing Design. IOSR Journal of Electrical HBRP Publication Page 27-37 2023. All Rights Reserved and Electronics Engineering (IOSRJEEE), 12(1), 12-17. Tabatabaei, N. M., & Mortezaeei, S. R. (2010). Design of grounding systems in substations by ETAP intelligent software. International Journal on «Technical and Physical Problems of Engineering, 2, 45-49. Baby, A., James, J., Vinod, S., Sobhan, V., George, T. (2018). Earth Mat Design for a 66kV Substation. International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering,7(4), 1649-1654. Abouzeid, O., & Syakur, A. (2018). Design of grounding system at 150 kV krapyak substation by grounding system software. Int J Eng Sci Comput, 8(4). Anderson, P. M., & Fouad, A. A. (2003). Institute of Electrical and Electronics Engineers. Power system control and stability. Institute of Electrical and Electronic Engineers STD. (2005). Powering and Grounding Electronics Equipment. Kamal, A. S. A., Arief, Y. Z., & Sidik, M. A. B. (2016). A systematic approach to safe and effective earthing system design for high voltage substation. Applied Mechanics and Materials, 818, 146150. Beltz, R., Peacock, I., & Vilcheck, W. (2001). High-resistance ground retrofits in pulp and paper mills. IEEE Industry Applications Magazine, 7(2), 19-27. Uwho, K. O., Idoniboyeobu, D. C., & Amadi, H. N. (2022). Design and Simulation of 500kW Grid Connected PV System for Faculty of Engineering, Rivers State University Using Pvsyst software. Iconic Research and Engineering Journals, 5(8), 2456-8880. Page 36 Journal of Recent Trends in Electrical Power System Volume 6 Issue 3 DOI: https://doi.org/10.5281/zenodo.10043497 ac 10. 11. 12. 13. 14. Amadi, H. N. (2017). Design of grounding system for AC substations with critical consideration of the mesh, touch and step potentials. European Journal of Engineering and Technology Vol, 5(4). Chikezie, O., Dikio Clifford Idoniboyeobu, D. R., BRAIDE, U., & OKPARA, K. (2022). Enhancement of 11kV Distribution Network for Power Quality Improvement Using Artificial Neural Network Based DVR. Iconic Research and Engineering Journals, 5(10), 102-111. Prasad, D., & Sharma, H. C. (2011). Significance of Step and Touch voltages. International Journal of Soft Computing and Engineering (IJSCE), 1(5), 193-197. Amadi, H. N. (2017). Soil Resistivity Investigations for Substation Grounding Systems In Wetland Regions–A Case Study Of Lagos State, Nigeria. Asian Journal of Natural & Applied Sciences, 6(4), 94-95. Idoniboyeobu, D. C., Bala, T. K., & Okekem, E. (2018). Assessment and Evaluation of Soil Effect on Electrical Earth Resistance: A Case Study of Woji Area, Port-Harcourt, Nigeria. International Journal of Engineering and Technical Research, 8(6), 264795. 15. 16. 17. 18. 19. Shah, S. G., & Bhasme, N. R. (2014). Design of Earthing system for HV/EHV AC Substation. International Journal of Advances in Engineering & Technology, 6(6), 2597-2605. Santoso, S., & Beaty, H. W. (2018). Standard handbook for electrical engineers. McGraw-Hill Education. Loo, K. H., & Ukil, A. (2017, October). Design of safety critical substation earthing system based on soil characteristics. In 2017 IEEE industry applications society annual meeting (pp. 1-8). IEEE. Nwauju, P.I., Idoniboyeobu, D.C., Amadi, H.N. (2022). Improvement of the Earthing System for 132/33kV Afam1 Sub-transmission station. International Journal of Engineering Inventions (IJEI), 11(10), 186-196. Prasad, D., & Sharma, H. C. (2011). Significance of Step and Touch voltages. International Journal of Soft Computing and Engineering (IJSCE), 1(5), 193-197. Cite as : Hachimenum Amadi, Peter Nwauju, & Dikio Idoniboyeobu. (2023). Enhancement of the Grounding System of 132/33 kV Sub-transmission Station via an ETAP-Based Approach. Journal of Recent Trends in Electrical Power System, 6(3), 27–37. https://doi.org/10.5281/zenodo.10043497 HBRP Publication Page 27-37 2023. All Rights Reserved Page 37