Learning Outline Symmetrical Components Theory Sequence Impedance: Load, Line, Generator, T Transformer f Fault Analysis: Line‐Ground, Line‐Line, Line‐ Line‐Ground. Examples p and Class Exercises 1 Fault Analysis y ____________________ • Fault types: – balanced faults (<5%) • three‐phase to ground • Three‐phase – unbalanced faults • single‐line to ground (60%‐75%) • double‐line d bl li to t ground d (15%‐25%) (15% 25%) • line line‐to‐line to line faults (5% (5%‐15%) 15%) 2 Example impact of fault The second largest blackout in the history of TEPCO (The Tokyo Electric Power Company, Company Inc.) Inc ) hit central Tokyo area at about 7:38 a.m. on August 14, 2006. It was caused by a floating crane on a barge going upstream on a river on the eastern edge of the city. The workers on the boat did not realize that the 33 meter crane was raised too high, so it hit TEPCO's 275 kV double circuit transmission lines that run across the river. river As a result of the accident the transmission lines were short‐circuited and the wires damaged. The relay protection operated and tripped both lines 3 Symmetrical y Components p __________ • Three phase voltage or current is in a balance condition if it has the following characteristic: – Magnitude of phase a,b, and c is all the same – The system has sequence of a,b,c – The angle between phase is displace by 120 degree • If one of the above is character is not satisfied, unbalanced occur. Example: 4 Symmetrical y Components p __________ • For unbalanced system, power system analysis cannot be analyzed using per phase as in Load Flow analysis or Symmetrical fault ‐>Symmetrical components need to be used. • Symmetrical component allow unbalanced phase quantities such as current and voltages to be replaced by three separate balanced symmetrical components. components 5 Symmetrical y Components p __________ 6 Symmetrical y Components p __________ By convention, the direction of rotation of the phasors is taken to be counterclock‐wise. counterclock wise Positive sequence: I a1 = I a1∠0° = I a1 I b1 = I a1∠240° = a 2 I a1 (10.1) I c1 = I a1∠120° = aII a1 Where we defined an operator a that causes a counterclockwise rotation of 120 degree such that: degree, a = 1∠120 ° = cos 120 ° + j sin 120 ° = −0.5 + j 0.866 (10.2) 1 + a + a2 = 0 a 2 = (1∠120°) × (1∠120°) = 1∠240° = −0.5 − j 0.866 a 3 = 1∠360° = 1 + j 0 (10.3) 7 Symmetrical y Components p __________ Negative sequence: I a2 = I a2∠0° I b2 = I a2∠120° = aI a2 (10.4) I c2 = I a2∠ 240 ° = a 2 I a2 Zero sequence: I a0 = I b0 = I c0 (10.5) 8 Symmetrical y Components p __________ Consider the three‐phase unbalanced current of I a , I b , I c I a = I a0 + I a1 + I a2 Ib = I + I + I 0 b 1 b 2 b (10.6) I c = I c0 + I c1 + I c2 Based on (10.1), (10.4) and (10.5), (10.6) can be rewrite all in terms of phase a components I a = I a0 + I a1 + I a2 I b = I a0 + a 2 I a1 + aI a2 I c = I a0 + aI a1 + a 2 I a2 (10.7) ⎡ I a ⎤ ⎡1 1 ⎢ I ⎥ = ⎢1 a 2 ⎢ b⎥ ⎢ ⎣⎢ I c ⎥⎦ ⎢⎣1 a 1 ⎤ ⎡ I a0 ⎤ ⎢ ⎥ a ⎥⎥ ⎢ I a1 ⎥ a 2 ⎥⎦ ⎢⎣ I a2 ⎥⎦ (10.8) 9 Symmetrical y Components p __________ Equation 10.8 can be written as: I abc = AI 012 a (10.9) Where A is known as symmetrical components transformation matrix, which transforms phasor currents I abc into components currents I 012 a and ⎡1 1 1 ⎤ (10 10) (10.10) A = ⎢⎢1 a 2 a ⎥⎥ 2 ⎣⎢1 a a ⎥⎦ Solving (10.9) for the symmetrical components of currents: I 012 = A − I abc a The inverse of A is given by: (10.11) ⎡1 1 1 A − = ⎢⎢1 a 3 ⎢⎣1 a 2 1⎤ a 2 ⎥⎥ a ⎥⎦ (10 12) (10.12) 10 Symmetrical y Components p __________ From (10.10) and (10.12), we conclude that 1 A − = A* 3 (10.13) Substituting for A‐1 in (10.11), we have: ⎡ I a0 ⎤ ⎡1 1 ⎢ 1⎥ 1⎢ ⎢ I a ⎥ = 3 ⎢1 a 2 ⎢ I a2 ⎥ ⎢ 1 a ⎣ ⎣ ⎦ 1 ⎤ ⎡I a ⎤ ⎢ ⎥ a 2 ⎥⎥ ⎢ I b ⎥ a ⎥⎦ ⎢⎣ I c ⎥⎦ (10.14) or in component form, the symmetrical components are: 1 I a0 = ( I a + I b + I c ) 3 1 I a1 = ( I a + aI b + a 2 I c ) 3 1 I a2 = ( I a + a 2 I b + aI c ) 3 (10.15) 11 Symmetrical y Components p __________ Similar expressions exists for voltage: Va = Va0 + Va1 + Va2 Vb = Va0 + a 2Va1 + aVa2 (10.16) V abc = AVa012 (10.17) Vc = Va0 + aVa1 + a 2Va2 The symmetrical components in terms of unbalanced voltages are: 1 Va0 = (Va + Vb + Vc ) 3 1 Va1 = (Va + aVb + a 2Vc ) 3 1 Va2 = (Va + a 2Vb + aVc ) 3 (10.18) Va012 = A − V abc (10.19) 12 Symmetrical y Components p __________ The apparent power may also be expressed in terms of the symmetrical components. components S ( 3φ ) = V abc T I abc * (10.20) Substituting (10.9) and (10.17) in (10.20), we obtain: * S ( 3φ ) = ( AVa012 )T ( AI 012 a ) =V 012T a Since T (10.21) * 012* a A AI A T = A, A T A * = 3 complex power becomes S ( 3φ ) = 3( V 012 I 012 ) T * = 3Va0 I 0a + 3Va1I1a + 3Va2 I 2a * * * (10.22) Total power for unbalance 3 3‐phase phase system can be obtained from the sum of symmetrical components powers. 13 Example p 1_______________________ One conductor of a three‐phase line is open. The current flowing to delta‐ connected load through line a is 10 A. A With the current in line a as reference and assuming that line c is open, find the symmetrical components of the line currents. a b c 1 I a0 = ( I a + I b + I c ) 3 1 I a1 = ( I a + aI b + a 2 I c ) 3 1 I a2 = ( I a + a 2 I b + aI c ) 3 I a = 10∠0° A I b = 10∠180° A Ic = 0 A 14 Solution________________________ The line current are: I a = 10∠0° I b = 10∠180° Ic = 0 From (10.15): 0 Sequence 1 I a( 0 ) = (10∠0° + 10∠180° + 0) = 0 3 + Sequence 1 I a(1) = (10∠0° + 10∠(180° + 120°) + 0) 3 = 5 − j 2.89 = 5.78∠ − 30° A ‐ Sequence 1 I a( 2 ) = (10∠0° + 10∠(180° + 240°) + 0) 3 = 5 + j 2.89 = 5.78∠30° A From (10.4) (0) b I =0 I b(1) = 5.78∠ − 150 ° A I ( 2) b = 5.78∠150° A 1 I a0 = ( I a + I b + I c ) 3 1 I a1 = ( I a + aI b + a 2 I c ) 3 1 I a2 = ( I a + a 2 I b + aI c ) 3 I c( 0 ) = 0 I c(1) = 5.78∠90 ° A I c( 2 ) = 5.78∠ − 90° A 15 Example p 2_______________________ 16 Exercise 1_______________________ Show that : (1 + a) (a) = 1∠120° 2 (1 + a ) (1 − a)) 2 (b) = 3∠ − 180° 2 (1 + a) 17 Exercise 2_______________________ Obtain the symmetrical components for the set of unbalanced voltages V a = 300 ∠ − 120 °, Vb = 200 ∠ 90 °, Vc = 100 ∠ − 30 ° V 012 = 42 .2650 ∠ − 120 ° 193 .1852 ∠ − 135 ° 86 .9473 ∠ − 84 .8961 ° 1 Va0 = (Va + Vb + Vc ) 3 1 Va1 = (Va + aVb + a 2Vc ) 3 1 Va2 = (Va + a 2Vb + aVc ) 3 The symmetrical components of a set of unbalanced three three‐phase phase currents are I a0 = 3∠ − 30 °, I a1 = 5∠90 °, I a2 = 4∠30 ° Obtain the original unbalanced phasors. I a = I a0 + I a1 + I a2 Iabc = 8 .1854 ∠ 42 .2163 ° I b = I a0 + a 2 I a1 + aI a2 4 ∠ − 30 ° 8 .1854 ∠ − 102 .2163 ° I c = I a0 + aI a1 + a 2 I a2 18 Exercise 3_______________________ The line‐to‐line voltages in an unbalanced three‐phase supply are Vab = 1000 ∠ 0 °, Vbc = 866 .0254 ∠ − 150 °, Vca = 500 ∠120 ° Determine the symmetrical components for line and phase voltages, then find the phase voltages Van, Vbn, and Vcn. VL 012 = Va 012 = 0 .0 ∠ 30 ° 0 .0 ∠ 0 ° 763 .7626 ∠ − 10 .8934 ° 440 .9586 ∠ − 40 .8934 ° 288 .6751 ∠ 30 ° 166 .6667 ∠ 60 ° Vabc = 440 .9586 ∠ − 19 .1066 ° 600 .9252 ∠ − 166 .1021 ° 333 .3333 ∠ 60 ° 19 Sequence q Impedance p ______________ • The impedance of an equipment or component to the current of different sequences. • positive‐sequence iti i impedance d (Z1): ) Impedance I d th t that causes a positive‐sequence current to flow • negative‐sequence impedance (Z2): Impedance that causes a negative‐sequence current to flow • zero‐sequence impedance (Z0): Impedance that causes a zero‐sequence current to flow 20 Sequence q Impedance p of Y‐Connected Load Line to ground voltages are: Va = Z s I a + Z m I b + Z m I c + Z n I n Vb = Z m I a + Z s I b + Z m I c + Z n I n (10.23) Vc = Z m I a + Z m I b + + Z s I c + Z n I n Kirchhoff’ current law: In = Ia + Ib + Ic (10.24) Substituting In into (10.23): Zm + Zn ⎤ ⎡I a ⎤ ⎡Va ⎤ ⎡( Z s + Z n ) Z m + Z n ⎢V ⎥ = ⎢ Z + Z ⎥ ⎢I ⎥ Z + Z Z + Z ( ) b m n s n m n ⎥⎢ b⎥ ⎢ ⎥ ⎢ Z m + Z n ( Z s + Z n )⎥⎦ ⎣⎢ I c ⎥⎦ ⎣⎢Vc ⎦⎥ ⎣⎢ Z m + Z n (10 25) (10.25) V abc = Z abc I abc (10.26) 21 Sequence q Impedance p of Y‐Connected Load Zm + Zn ⎤ ⎡( Z s + Z n ) Z m + Z n Z abc = ⎢⎢ Z m + Z n ( Z s + Z n ) Z m + Z n ⎥⎥ ⎢⎣ Z m + Z n Z m + Z n ( Z s + Z n )⎥⎦ (10 27) (10.27) Writing Vabc and Iabc in terms of their symmetrical components: AVa012 = Z abc AI 012 a (10.28) Multiplying (10.28) by A‐1 : Va012 = ( A − Z abc A )I 012 a =Z I 012 012 a where Z 012 = A − Z abc A (10.29) (10.30) Substituting for Zabc, A and A‐1 from (10.27), (10.10) and (10.12): ⎡1 1 1 Z 012 = ⎢⎢1 a 3 ⎢⎣1 a 2 1 ⎤ ⎡( Z s + Z n ) Z m + Z n Z m + Z n ⎤ ⎡1 1 a 2 ⎥⎥ ⎢⎢ Z m + Z n ( Z s + Z n ) Z m + Z n ⎥⎥ ⎢⎢1 a 2 a ⎥⎦ ⎣⎢ Z m + Z n Z m + Z n ( Z s + Z n )⎦⎥ ⎢⎣1 a 1⎤ a ⎥⎥ a 2 ⎥⎦ (10.31) 22 Sequence q Impedance p of Y‐Connected Load Performing the multiplication in (10.31): Z 012 0 0 ⎡( Z s + 3Z n + 2 Z m ) ⎤ ⎢ ⎥ =⎢ 0 (Z s − Z m ) 0 ⎥ ⎢⎣ 0 0 ( Z s − Z m )⎥⎦ (10.32) When there is no mutual coupling, Zm = 0, and the impedance matrix becomes 0 0 ⎤ ⎡ ( Z s + 3Z n ) Z 012 = ⎢⎢ 0 (Z s ) 0 ⎥⎥ 0 0 ( Z s )⎥⎦ ⎣⎢ (10.33) 23 Sequence q Impedance p of Transmission Lines For sequence impedance transmission line, Z1 = Z2, whereas Z0 is different and larger approximately 3 times than positive and negative sequence. S Sequence IImpedance d off SSynchronous h M Machine hi The positive-sequence generator impedance is the value found when positivesequence q current flows from the action of an imposed p positive-sequence p q set of voltages. The negative-sequence reactance is close substransient reactance, reactance i.e ie: X2 ≈ X" to the positive-sequence d Zero-sequence reactance is approximated to the leakage reactance, i.e : X 0 ≈ Xl 24 Sequence q Impedances p of Transformer • Series Leakage Impedance. – tthee magnetization ag et at o cu current e t aand d co coree losses osses represented ep ese ted by tthee sshunt u tb branch a c are neglected (they represent only 1% of the total load current) – the transformer is modeled with the equivalent series leakage impedance • Since transformer is a static device, the leakage impedance will not change if the phase sequence is changed. changed • Therefore, the positive and negative sequence impedance are the same; Z 0 = Z1 = Z2 = Zl • Wiring connection always cause a phase shift. In Y‐Delta or Delta‐Y transformer: – Positive Sequence rotates by a +30 degrees from HV to LV side – Negative Sequence rotates by a ‐30 degrees from HV to LV side – Zero Sequence does not rotate • The equivalent circuit for zero‐sequence impedance depends on the winding connections and also upon whether or not the neutrals are grounded. 25 Sequence q Impedances p of Transformer Connection diagram Zero‐sequence circuit Figure (a) Figure g (b) ( ) Figure (c) Figure (d) Figure (e) 26 Sequence q Impedances p of Transformer Description of Zero sequence Equivalent Circuit (a) Y‐Y connections with both neutrals grounded – We know that the zero sequence current equals the sum of phase currents. Since both neutrals are grounded, there is a path for the zero sequence current to flow in the primary and secondary, and the transformer exhibits the equivalent leakage impedance per phase as shown in Fig. (a). ( ) Y‐Y connections with p (b) primaryy the neutral ggrounded – The p primaryy neutral is ggrounded,, but since the secondary neutral is isolated, the secondary phase current must sum up to zero. This means that the zero‐sequence current in the secondary is zero. Consequently, the zero sequence current in the primary is zero, reflecting infinite impedance or an open circuit as shown in Fig. g ((b). ) 27 Sequence q Impedances p of Transformer c) Y‐Δ with grounded neutral – in this configuration, the primary currents can flow because the zero‐sequence circulating current in the Δ‐connected secondaryy and a gground return p path for the Y‐connected p primary. y Note that no zero‐sequence current can leave the Δ terminals, thus there is an isolation between the primary and secondary sides as shown in figure (c) d) Y‐Δ Y Δ connection ti with ith isolated i l t d neutral t l – in i this thi configuration, fi ti b because th the neutral is isolated, zero sequence current cannot flow and the equivalent circuit reflects an infinite impedance or an open as shown in figure (d) e) Δ‐Δ connection – in this configuration, zero‐sequence currents circulate in the Δ‐connected windings, but no currents can leave the Δ terminals, and the equivalent circuit is as shown in figure (e) Notice that the neutral impedance plays an important part in the equivalent circuit. When the neutral is grounded through an impedance Zn, because In=3Io, in the equivalent circuit, the neutral impedance appears as 3Zn in the path of Io. 28 Sequence q Impedances p of a Loaded Generator A synchronous machine generates balanced three‐phase internal voltages and is represented as a positive‐sequence set of phasors ⎡1⎤ E abc = ⎢⎢a 2 ⎥⎥ Ea ⎢⎣ a ⎥⎦ (10.44) 29 Sequence q Impedances p of a Loaded Generator The machine is supplying a three‐phase balanced load. Applying kirchhoff’s voltage law to each phase we obtain: Va = Ea − Z s I a − Z n I n (10.45) Vb = Eb − Z s I b − Z n I n Vc = Ec − Z s I c − Z n I n Substituting for In = Ia + Ib + Ic into (10.45): Zn Z n ⎤ ⎡I a ⎤ ⎡Va ⎤ ⎡ E a ⎤ ⎡( Z s + Z n ) ⎢V ⎥ = ⎢ E ⎥ − ⎢ Z ⎥ ⎢I ⎥ ( Z + Z ) Z b b n s n n ⎢ ⎥ ⎢ ⎥ ⎢ ⎥⎢ b⎥ ⎢⎣Vc ⎥⎦ ⎢⎣ Ec ⎥⎦ ⎢⎣ Z n Zn ( Z s + Z n ) ⎥⎦ ⎢⎣ I c ⎥⎦ In compact form: V abc = E abc − Z abc I abc (10.46) (10.47) 30 Sequence q Impedances p of a Loaded Generator Transforming the terminal voltages and currents phasors into their symmetrical components: abc AVa012 = AE 012 AI 012 a −Z a (10.48) Multiplying (10.48) by A‐1: − abc Va012 = E 012 A)I 012 a − (A Z a (10.49) 012 012 = E 012 Ia a −Z Where: h ⎡1 1 1 Z 012 = ⎢⎢1 a 3 ⎢⎣1 a 2 1 ⎤ ⎡( Z s + Z n ) Zn Z n ⎤ ⎡1 1 a 2 ⎥⎥ ⎢⎢ Z n (Z s + Z n ) Z n ⎥⎥ ⎢⎢1 a 2 a ⎥⎦ ⎢⎣ Z n ( Z s + Z n )⎥⎦ ⎢⎣1 a Zn 1⎤ a ⎥⎥ a 2 ⎥⎦ (10.50) Performing the above multiplication: ⎡( Z s + 3Z n ) 0 Z 012 = ⎢⎢ 0 Zs ⎢⎣ 0 0 0 ⎤ ⎡Z 0 ⎢ 0 ⎥⎥ = ⎢ 0 Z s ⎦⎥ ⎣⎢ 0 0 Z1 0 0⎤ ⎥ 0⎥ Z 2 ⎥⎦ (10.51) 31 Sequence q Impedances p of a Loaded Generator Since the generated emf is balanced, there is only positive‐sequence voltage, i.e: ⎡0⎤ = ⎢⎢ Ea ⎥⎥ E 012 a ⎢⎣ 0 ⎥⎦ (10 52) (10.52) 012 Substituting for E a and Z 012 in (10.49): ⎡V ⎤ ⎡ 0 ⎤ ⎡ Z ⎢ ⎥ ⎢ ⎥ ⎢ ⎢V ⎥ = ⎢ E a ⎥ − ⎢ 0 ⎢V ⎥ ⎢⎣ 0 ⎦⎥ ⎢ 0 ⎣ ⎦ ⎣ 0 a 1 a 2 a 0 0 Z1 0 0 ⎤ ⎡I ⎤ ⎥⎢ ⎥ 0 ⎥ ⎢I ⎥ Z 2 ⎥⎦ ⎣⎢ I ⎥⎦ 0 a 1 a 2 a Va0 = 0 − Z 0 I a0 (10.53) or Va1 = Ea − Z 1 I a1 ( (10.54) ) Va2 = 0 − Z 2 I a2 32 Sequence q Impedances p of a Loaded Generator The three equations in (10.54) can be represented by the three equivalent sequence networks: • Important observations: – The three sequences are independent. – The Th positive‐sequence ii networkk is i the h same as the h one‐line li diagram di used d iin studying balance three‐phase currents and voltages. – Only the positive‐sequence network has a source and no voltage source for other sequences. – The h neutrall off the h system is the h reference f for f positive‐ and d negative‐sequence networks, but ground is the reference for zero‐sequence networks. Thus, zero sequence current can only flow if the circuit from the system neutrals to ground is complete. – The grounding impedance is reflected in the zero sequence network as 3Zn – The three‐sequence systems can be solved separately on a per phase basis. The phase currents and voltages can then be determined by superposing their 33 symmetrical components of current and voltage respectively. Single g Line‐To‐Ground Fault Three‐phase generator with neutral grounded through impedance Zn and SLGF occurs at phase a through impedance Zf . Assuming the generator is initially on no‐load, the boundary conditions at the fault point are: (10.55) Va = Z f I a Ib = Ic = 0 (10.56) 34 Single g Line‐To‐Ground Fault Substituting for Ib = Ic = 0, the symmetrical components of currents from (10.14) are: ⎡ I a0 ⎤ ⎡1 1 ⎢ 1⎥ 1⎢ ⎢ I a ⎥ = 3 ⎢1 a ⎢ I a2 ⎥ ⎢⎣1 a 2 ⎣ ⎦ 1 ⎤ ⎡I a ⎤ a 2 ⎥⎥ ⎢⎢ 0 ⎥⎥ a ⎥⎦ ⎢⎣ 0 ⎥⎦ (10.57) From the above equation, we find that: I a0 = I a1 = I a2 = 1 Ia 3 Va0 = 0 − Z 0 I a0 (10 58) V 1 = E − Z 1 I 1 (10.58) a a a Phase a voltage in terms of symmetrical components is : V a = V a0 + V a1 + V a2 Va2 = 0 − Z 2 I a2 (10.59) Substituti ng Va0 , Va1and Va2 from (10.54) and noting I a0 = I a1 = I a2 : V a = E a − ( Z 0 + Z 1 + Z 2 ) I a0 (10. 60) 35 Single g Line‐To‐Ground Fault Where Z 0 = Z s + 3Z n . Substituti ng for Va from (10.55), and noting I a = 3I a0 , we get : 3Z f I a0 = E a − ( Z 0 + Z 1 + Z 2 ) I a0 (10 61) (10.61) or Ea I = 0 Z + Z 1 + Z 2 + 3Z f 0 a (10.62) The h ffault l current is I a = 3I a0 = 3E a Z 0 + Z 1 + Z 2 + 3Z f (10.63) In order to obtain symmetrical voltage at the point of fault Equation, (10.63) is substituted into Eq. (10.54) 36 Single g Line‐To‐Ground Fault Eq. (10.58) and (10.62) can be represented by connecting the sequence networks in series as shown in the following figure. I a0 = I a1 = I a2 = 1 Ia 3 (10.58) I a0 = Ea Z 0 + Z 1 + Z 2 + 3Z f (10.62) 37 Line‐To‐Line Fault Three‐phase generator with a fault through an impedance Zf between phase b and c. Ia=0 0 Zs Zs Eb N Ea Va Zs Ec Ib Zf Ic Vb Vc Assuming the generator is initially on no‐load, the boundary conditions at the fault point are: Vb − Vc = Z f I b (10.64) Ib + Ic = 0 (10.65) Ia = 0 (10.66) 38 Line‐To‐Line Fault Substituting for Ia = 0, and Ic = ‐Ib, the symmetrical components of the currents from (10.14) are: ⎡ I a0 ⎤ ⎡1 1 ⎢ 1⎥ 1⎢ ⎢ I a ⎥ = 3 ⎢1 a 2 ⎢ 2⎥ ⎣⎢1 a ⎣I a ⎦ 1 ⎤⎡ 0 ⎤ a 2 ⎥⎥ ⎢⎢ I b ⎥⎥ a ⎥⎦ ⎢⎣− I b ⎥⎦ (10.67) From the above equation equation, we find that: I a0 = 0 (10.68) 1 I a1 = (a − a 2 ) I b 3 (10 69) (10.69) 1 I a2 = (a 2 − a) I b 3 (10.70) 39 Line‐To‐Line Fault Also, from (10.69) and (10.70), we note that: I a1 = − I a2 (10 71) (10.71) Va = Va0 + Va1 + Va2 From (10.16), we have: Vb = Va0 + a 2Va1 + aVa2 (10.16) Vb − Vc = (Va0 + a 2Va1 + aV Va2 ) − (Va0 + aV Va1 + a 2Va2 ) = ( a 2 − a )(Va1 − Va2 ) = Z f Ib Vc = Va0 + aVa1 + a 2Va2 (10.72) Substituti ng for Va1 and Va2 from (10.54) and noting I a2 = − I a1 , we get : (a 2 − a)[ E a − ( Z 1 + Z 2 ) I a1 ] = Z f I b Va0 = 0 − Z 0 I a0 Va1 = Ea − Z 1 I a1 (10.73) Va2 = 0 − Z 2 I a2 (10.74) 1 I a1 = (a − a 2 ) I b 3 (10.54) Substituti ng for I b from (10.69), we get : 3I a1 1 2 1 Ea − (Z + Z ) I a = Z f ( a − a 2 )( a 2 − a) (10.69) 40 Line‐To‐Line Fault Since (a − a 2 )(a 2 − a) = 3, solving for I a1 results in : I a1 = Ea (Z 1 + Z 2 + Z f ) (10.75) The phase currents are ⎡ I a ⎤ ⎡1 1 ⎢ I ⎥ = ⎢1 a 2 ⎢ b⎥ ⎢ ⎢⎣ I c ⎦⎥ ⎢⎣1 a 1 ⎤⎡ 0 ⎤ a ⎥⎥ ⎢⎢ I a1 ⎥⎥ a 2 ⎥⎦ ⎢⎣− I a1 ⎥⎦ (10 76) (10.76) The fault current is I b = − I c = ( a 2 − a ) I a1 (10.77) or I b = − j 3I a1 (10.78) 41 Line‐To‐Line Fault Eq. (10.71) and (10.75) can be represented by connecting the positive and negative – sequence networks as shown in the following figure. I a1 = − I a2 I a1 = Ea (Z 1 + Z 2 + Z f ) 42 Double Line‐To‐Ground Fault Figure 10.14 shows a three‐phase generator with a fault on phases b and c through an impedance Zf to ground. Assuming the generator is initially on no‐ load the boundary conditions at the fault point are load, Vb = Vc = Z f ( I b + I c ) I a = I a0 + I a1 + I a2 = 0 (10.79) (10.80) From (10.16), the phase voltages Vb and Vc are Figure 10.14 10 14 Double line‐to‐ground fault 43 Double Line‐To‐Ground Fault Vb = Va0 + a 2Va1 + aVa2 (10.81) Vc = Va0 + aVa1 + a 2Va2 (10 82) (10.82) SinceVb = Vc , from above we note that Va1 = Va2 ( (10.83) ) Substituting for the symmetrical components of current in (10.79), we get V( b ) = Z f ( I a0 + a 2 I a1 + aI a2 + I a0 + aI a1 + a 2 I a2 ) = Z f ( 2 I a0 − I a1 − I a2 ) = 3 Z f I a0 (10.84) 44 Substituti ngg for Vb from ((10.84)) and for Va2 from ((10.83)) into ((10.81), ), we have : 3Z f I a0 = Va0 + (a 2 + a )Va1 = Va0 − Va1 (10.85) Substituti ng for the symmetrica l components of voltage from (10.54) into (10.85) and solving for I a0 , we get : E a − Z 1 I a1 I =− 0 ( Z + 3Z f ) 0 a (10 86) (10.86) Also, substituting for the symmetrical components of voltage in (10.83), we obtain E a − Z 1 I a1 I =− Z2 2 a (10 87) (10.87) Substituti ng for I a0 and I 2a into (10.80) and solving for I a1 , we get : I a1 = Ea Z ( Z 0 + 3Z f ) 2 Z + 1 (10.88) Z 2 + Z 0 + 3Z f 45 Equation (10.86) - (10.88) can be represente d by connecting the positive - sequence impedance in series with the paralel combinatio n of the negative - sequence and zero - sequence networks as shown in the equivalent circuit of figure 10.15. The value of I1a found from (10.86) is substitute d in (10.86) and (10.87), and I a0 and I a2 are found. found The phase current are then found from (10.8). (10 8) Finally, the fault current is obtained from I f = I b + I c = 3I a0 ((10.89)) Figure 10.15 Sequence network connection for double line‐to‐ground fault 46 EXAMPLE The one-line diagram of a simple power system is show in Figure 10.16. 10 16 The neutral of each generator is grounded through a current-limiting reactor of 0.25/3 per unit on a 100-MVA base. The system data expressed in per unit on a common 100-mva base tabulated below. The generators are running on no-load at their rated voltage and rated frequency with their emfs in phase. phase Determine the fault current for the following faults a. A balaced three-phase fault at bus 3 through a fault impedance Z f = j 0.1 per unit b. A single line-to-ground fault at bus 3 through a fault impedance Z f = j 0.1 per unit c A line-to-line fault at bus 3 through a fault impedance Z f = j 0.1 c. 0 1 per unit d. A double line-to-ground fault at bus 3 through a fault impedance Z f = j 0.1 per unit Item G1 G2 T1 T2 L12 L13 L23 Base MVA 100 100 100 100 100 100 100 Rated X1 Voltage 20-kV 0.15 20 kV 0.15 20/220 kV 0.10 20/220 kV 0.10 220 kV 0.125 220 kV 0.15 220 kV 0 25 0.25 X2 X0 0.15 0.15 0.10 0.10 0.125 0,15 0 25 0.25 0.05 0.05 0.10 0.10 0.30 0.35 0 7125 0.7125 47 Figure 10.16 10 16 Fault Item G1 G2 T1 T2 L12 L13 L23 Base MVA 100 100 100 100 100 100 100 Rated X1 Voltage 20-kV 0.15 20 kV 0 15 0.15 20/220 kV 0.10 20/220 kV 0.10 220 kV 0.125 220 kV 0.15 220 kV 0.25 X2 X0 0.15 0 15 0.15 0.10 0.10 0.125 0,15 0.25 0.05 0 05 0.05 0.10 0.10 0.30 0.35 0.7125 48 To find Thevenin impedance viewed from the faulted bus (bus 3), we convert the delta formed by buses 123 to an equivalent Y as shown below Fig. 10.17Positive-sequence impedance Z 1S = ( j 0.125)( j 0.15) = j 0.0357143 j 0.525 Z 3S = Z 2S = ( j 0.125)( j 0.25) = j 0.0595238 j 0.525 ( j 0.15)( j 0.25) = j 0.0714286 j 0.525 49 ( j 0 .2857143 )( j 0.3095238 ) + j 0 .0714286 j 0.5952381 = j 0.22 1 Z 33 = 50 To find thevenin impedance viewed from the faulted bus (bus 3), we convert the delta formed by buses 123 to an equivalent Y as shown in figure 10.19(b) ( j 0.30)( j 0.35) Z 1S = = j 0.0770642 j1.3625 Z 2S = ( j 0.30)( j 0.7125) = j 0.1568807 j1.3625 Z 3S = ( j 0.35)( j 0.7125) = j 0.1830257 j1.3625 Fig. 10.19Zero-sequence impedance j0.077064 51 Combiningg the p parallel branches, the zero‐sequence q thevenin impedance p is ( j 0.4770642 )( j 0.2568807 ) + j 0.1830275 j 0.7339449 = j 0.35 Z 330 = j0.077064 So, the zero‐sequence impedance diagram is show in fig. 10.20 Fig. 10.20 Zero‐sequence network 52 (a) Balanced three‐phase fault at bus 3 Assuming the no‐load generated emfs are equal to 1.0 per unit, the fault current is I 3 (F) = V3a( 0) Z133 + Z f = 1.0 = -j3.125 j3 125 pu = 820.1 820 1∠ - 90° A j0.22 + j 0.1 (b) Single line‐to ground fault at bus 3 F From (10 (10.62), 62) the th sequence componentt off the th fault f lt currentt are I 30 = I13 = I 32 = V3a( 0) 2 0 Z133 + Z 33 + Z 33 + 3Z f = 1.0 = -j0.9174 pu j0.22 + j0.22 + j 0.35 + 3(j0.1) The fault current is : ⎡ I 3a ⎤ ⎡1 1 ⎢ b⎥ ⎢ 2 = I 1 a ⎢ 3⎥ ⎢ ⎢ I 3c ⎥ ⎢⎣1 a ⎣ ⎦ 1 ⎤ ⎡ I 30 ⎤ ⎡3I 30 ⎤ ⎡− j 2.7523⎤ ⎢ ⎥ ⎢ ⎥ ⎥ pu a ⎥⎥ ⎢ I 30 ⎥ = ⎢ 0 ⎥ = ⎢⎢ 0 ⎥ 2 0 ⎥⎦ a ⎥⎦ ⎢⎣ I 3 ⎥⎦ ⎢⎣ 0 ⎥⎦ ⎢⎣ 0 53 (c) Line‐to Line fault at bus 3 The zero‐sequence component of current is zero, i.e., I 30 = 0 The positive‐and negative‐sequence components of the fault current are I13 = −I 32 = V3a( 0) 2 0 Z133 + Z 33 + Z 33 + Zf = 1.0 = -j1.8519 pu j0.22 + j0.22 + j0.1 The fault current is ⎡ I 3a ⎤ ⎡1 1 ⎢ b⎥ ⎢ 2 1 I a = 3 ⎢ ⎥ ⎢ ⎢ c⎥ ⎣ I 3 ⎦ ⎢⎣1 a 1⎤⎡ 0 ⎤ ⎡ 0 ⎤ a ⎥⎥ ⎢⎢− j1.8519⎥⎥ = ⎢⎢− 3.2075⎥⎥ pu a 2 ⎥⎦ ⎢⎣− j1.8519⎥⎦ ⎢⎣− 3.2075⎥⎦ (d) Double Line‐to Line‐fault at bus 3 The positive‐sequence component of the fault current is I = 1 3 V3a( 0) 2 0 Z 33 ( Z 33 + 3Z f ) Z + 2 0 Z 33 + Z 33 + 3Z f ) 1 33 = 1.0 = -j2.6017 pu j0.22 (j0.35 + j0.3) j0.22 + j0.22 + j0.35 + j0.3 54 The negative‐sequence component of current is : I 32 = − V3a( 0) − Z133 I133 2 Z 33 =− 1.0 − ( j 0.22)(− j 2.6017) = j1.9438 pu j0.22 Th zero‐sequence componentt off currentt is: The i I 30 = − V3a( 0 ) − Z133 I133 0 Z 33 + 3Z f =− 1.0 − ( j 0.22)(− j 2.6017) = j0.6579 pu j0 35 + j0.3 j0.35 j0 3 And the phase currents are : ⎡ I 3a ⎤ ⎡1 1 ⎢ b⎥ ⎢ 2 = I 1 a 3 ⎢ ⎥ ⎢ ⎢ I 3c ⎥ ⎢⎣1 a ⎣ ⎦ 1 ⎤ ⎡ j 0.6579 ⎤ ⎡ 0 ⎤ a ⎥⎥ ⎢⎢− j 2.6017 ⎥⎥ = ⎢⎢4.058∠165.93°⎥⎥ pu a 2 ⎥⎦ ⎢⎣ j1.9438 ⎥⎦ ⎢⎣ 4.058∠14.07° ⎥⎦ And the fault currents is: I 3 ( F ) = I 3b + I 3c = 1.9732∠90° 55 UNBALANCED FAULT ANALYSIS USING BUS IMPEDANCE MATRIX Single Line‐to‐Ground Fault Using Zbus Vk (0) I =I =I = 1 Z kk + Z kk2 + Z kk0 + 3Z f 0 k 1 k 2 k (10.90) Where Z1kk , Z 2kk and Z okk are the diagonal elements in the k axis of the correspond ing bus impedance matrix and Vk (0)is the prefault voltage at bus k. The fault phase current is : (10.91) I kabc = A I k 012 Line‐to‐Line Fault Using Zbus I k0 = 0 I k1 = − I k2 = (10.92) Vk (0) Z kk1 + Z kk2 + Z f (10.93) 56 Double Line‐to‐Ground Fault Using Zbus I k1 = Z kk1 + Vk (0) Z kk2 ( Z kk0 + 3Z f ) (10.94) Z kk2 + Z kk0 + 3Z f Vk (0) − Z kk1 I k1 I =− Z kk2 (10.95) Vk (0) − Z kk1 I k1 I =− Z kk0 + 3Z f (10.96) 2 k 0 k Where Z1kk , and Z 2kk , and Z okk are the diagonal elements in the k axis of the correspond ing bus impedance p matrix. The pphase currents are obtained from ((10.91), ), and the result current is I k ( F ) = I kb + I kC (10.97) 57