FAS – EL INTEGRATION
HONEYWELL MORLEY PANEL/DXC PANEL
 Model no : MI-DCMOE
 STEPS
 1. CONNECT LOOP CABLES TO
 (3) L - IN --> NEGATIVE
 (4) L+ IN --> POSITIVE
 (5) AND (6) connect jumper .
 (8) – common
 (11)- NO
 2. Put available address using rotary
switch .
 3. Auto learn Loop of Panel in which it
I connected.
EDWARDS EST3
 Model No : SIGA-CR
 Connect
 (1) LOOP NEGATIVE
 (2) LOOP POSITIVE
 (3) LOOP NEGATIVE
 (4) LOOP POSITIVE
 (7) NO
 (8) common
 Panel software Programming is required to
add in panel .
RAVEL AVANI

MODEL RE717MR

Connect loop cables

connect to Relay 1 NO and c point .

Put address of module by dip switches by
checking available address from panel.
HONEYWELL NOTIFIER

MODEL FRM-1

Connect loop cable to + and –

Connect to normally open1 and relay
common 1.
 Put available address using rotary switch

Auto learn Loop of Panel in which it is
connected.
.
SIMPLEX FIRE PANEL

MODEL 4090-9002

CONNECT LOOP CABLES TO 3 AND 4 .

CONNECT

NO TO 7

COMMON TO 6

Panel software programming
required for adding module in FAS
PANEL.
ANY QUESTIONS