FAS – EL INTEGRATION HONEYWELL MORLEY PANEL/DXC PANEL Model no : MI-DCMOE STEPS 1. CONNECT LOOP CABLES TO (3) L - IN --> NEGATIVE (4) L+ IN --> POSITIVE (5) AND (6) connect jumper . (8) – common (11)- NO 2. Put available address using rotary switch . 3. Auto learn Loop of Panel in which it I connected. EDWARDS EST3 Model No : SIGA-CR Connect (1) LOOP NEGATIVE (2) LOOP POSITIVE (3) LOOP NEGATIVE (4) LOOP POSITIVE (7) NO (8) common Panel software Programming is required to add in panel . RAVEL AVANI MODEL RE717MR Connect loop cables connect to Relay 1 NO and c point . Put address of module by dip switches by checking available address from panel. HONEYWELL NOTIFIER MODEL FRM-1 Connect loop cable to + and – Connect to normally open1 and relay common 1. Put available address using rotary switch Auto learn Loop of Panel in which it is connected. . SIMPLEX FIRE PANEL MODEL 4090-9002 CONNECT LOOP CABLES TO 3 AND 4 . CONNECT NO TO 7 COMMON TO 6 Panel software programming required for adding module in FAS PANEL. ANY QUESTIONS