1 1 GENERAL SPECIFICATIONS

advertisement
16IPP1624-L0001
1 GENERAL
This specification covers the site conditions and the mill
services. It also describes most relevant auxiliary
equipment, materials, specifications and standards to be
used in the project.
Outdoor design temperature, DB:
2(7)
24-38 ºC
Maximum temperature, DB
47 ºC
Minimum temperature, DB
15 ºC
Average relative humidity
25-72 %
Maximum humidity
95 %
Wind
SI-units shall be used. Pressure unit is gauge pressure, MPa
(overpressure) if not otherwise stated.
- maximum
45 m/s
Prevailing direction: from
For more detail instructions see the project document
”Units to be Used” 16IPP1624-L0002. The equipment
shall fulfil the requirements presented in the codes,
regulations and standards for this project. In all cases the
requirements of United Arab Emirates laws shall to be
met.
Note should be taken that the site is in a tropical location
and therefore all equipment must be suitable protected
from humidity, temperature, vermin, dust etc.
The project language is English. Operation
maintenance documents shall be also be in English.
and
Possible exceptions to the specifications below shall be
listed in the Purchase documents.
All Supplier's drawings shall be prepared according to the
following scales:
Site plans 1 : 500, 1 : 1000, 1 : 2000
General arrangement drawings 1 : 20, 1 : 50, 1 : 100,
1 : 200
Service piping, cable trays, instrument location,
structural framing 1 : 50, 1 : 100
Details 1 : 50, 1 : 20, 1 : 10, 1 : 5, 1:1.
Suppliers shall preferably use size A1 (A0) for drawings
and A4 for documents according to ISO 5457-1999. Size
A3 can also be used for electrical and instrument
drawings.
The document folders shall be preferably size A4 loose
leaf books with filing holes according to ISO 838-1974
(80-80-80).
Each folder must have a table of contents, section dividers
and appropriate folder title on the spine.
All drawings and documents shall be provided in
electronic PDF format.
2
SITE CONDITIONS AND MILL UTILITIES
2.1
Mill Location
North-West (shamal) with occasional sand storms
Rainfall
- Annual, maximum
350 mm
- Annual, minimum
30 mm
- Max. 24 hours
11 mm
2.3
Mill Utilities
2.3.1
Voltages
See Section 6, Electrical Equipment.
2.3.2
Compressed air
Mill and instrument air pressure 0.5 – 0.7 MPa
Instrument air quality: According to ISO 8573-1:2001
Solid particles: Class 5
1 µm filtration is recommended
Humidity: Class 1
Dewpoint: - 20 °C, (dew point 10 °C/ below minimum
temperature is recommended)
Oil class: 3 (or < 1 ppm)
Mill air quality: According to ISO 8573-1:2001
Solid particles: 15 µm filtration
Dewpoint: water separation
Oil class: 3 (or < 1 ppm)
2.3.3
Mill water
Mill water characteristics:
- Temperature
- Turbidity, SiO2
- Water Colour
- pH
- Chlorides
- Total Dissolved Solids
Total hardness, as CaCO3
- Silica (soluble) as SiO2
– Iron
- Manganese , Mn
- Residual Chlorine as CL2
Pressure on ground level
The mill site is located in United Arab Emirates.
Sealing water filtration
The mill site is in ICAD II Industrial Zone, which is
located close to Abu Dhabi City. ICAD II will provide the
necessary infrastructure and services required to support
industrial and business.
2.3.4
2.2
24-33 °C
3 NTU
5 PCU
7-8.5
50 mg/l
200mg/l
70 mg/l
5 mg/l
0.1 mg/l
0.05 mg/l
0.5 mg/l
0.45 MPa
< 50 µm
Steam
Operation
Design
Low-pressure steam
pressure, MPa (gauge)
0.35
0.5
temperature, ºC
155
200
Flange connections PN 10, EN 1092-1 Type 11.
Local conditions
Operation
Medium pressure steam
pressure, MPa (gauge)
1.1
Design
1.5