16IPP1624-L0001 1 GENERAL This specification covers the site conditions and the mill services. It also describes most relevant auxiliary equipment, materials, specifications and standards to be used in the project. Outdoor design temperature, DB: 2(7) 24-38 ºC Maximum temperature, DB 47 ºC Minimum temperature, DB 15 ºC Average relative humidity 25-72 % Maximum humidity 95 % Wind SI-units shall be used. Pressure unit is gauge pressure, MPa (overpressure) if not otherwise stated. - maximum 45 m/s Prevailing direction: from For more detail instructions see the project document ”Units to be Used” 16IPP1624-L0002. The equipment shall fulfil the requirements presented in the codes, regulations and standards for this project. In all cases the requirements of United Arab Emirates laws shall to be met. Note should be taken that the site is in a tropical location and therefore all equipment must be suitable protected from humidity, temperature, vermin, dust etc. The project language is English. Operation maintenance documents shall be also be in English. and Possible exceptions to the specifications below shall be listed in the Purchase documents. All Supplier's drawings shall be prepared according to the following scales: Site plans 1 : 500, 1 : 1000, 1 : 2000 General arrangement drawings 1 : 20, 1 : 50, 1 : 100, 1 : 200 Service piping, cable trays, instrument location, structural framing 1 : 50, 1 : 100 Details 1 : 50, 1 : 20, 1 : 10, 1 : 5, 1:1. Suppliers shall preferably use size A1 (A0) for drawings and A4 for documents according to ISO 5457-1999. Size A3 can also be used for electrical and instrument drawings. The document folders shall be preferably size A4 loose leaf books with filing holes according to ISO 838-1974 (80-80-80). Each folder must have a table of contents, section dividers and appropriate folder title on the spine. All drawings and documents shall be provided in electronic PDF format. 2 SITE CONDITIONS AND MILL UTILITIES 2.1 Mill Location North-West (shamal) with occasional sand storms Rainfall - Annual, maximum 350 mm - Annual, minimum 30 mm - Max. 24 hours 11 mm 2.3 Mill Utilities 2.3.1 Voltages See Section 6, Electrical Equipment. 2.3.2 Compressed air Mill and instrument air pressure 0.5 – 0.7 MPa Instrument air quality: According to ISO 8573-1:2001 Solid particles: Class 5 1 µm filtration is recommended Humidity: Class 1 Dewpoint: - 20 °C, (dew point 10 °C/ below minimum temperature is recommended) Oil class: 3 (or < 1 ppm) Mill air quality: According to ISO 8573-1:2001 Solid particles: 15 µm filtration Dewpoint: water separation Oil class: 3 (or < 1 ppm) 2.3.3 Mill water Mill water characteristics: - Temperature - Turbidity, SiO2 - Water Colour - pH - Chlorides - Total Dissolved Solids Total hardness, as CaCO3 - Silica (soluble) as SiO2 – Iron - Manganese , Mn - Residual Chlorine as CL2 Pressure on ground level The mill site is located in United Arab Emirates. Sealing water filtration The mill site is in ICAD II Industrial Zone, which is located close to Abu Dhabi City. ICAD II will provide the necessary infrastructure and services required to support industrial and business. 2.3.4 2.2 24-33 °C 3 NTU 5 PCU 7-8.5 50 mg/l 200mg/l 70 mg/l 5 mg/l 0.1 mg/l 0.05 mg/l 0.5 mg/l 0.45 MPa < 50 µm Steam Operation Design Low-pressure steam pressure, MPa (gauge) 0.35 0.5 temperature, ºC 155 200 Flange connections PN 10, EN 1092-1 Type 11. Local conditions Operation Medium pressure steam pressure, MPa (gauge) 1.1 Design 1.5