G2 Estimation of connected load and diversity factors Estimation of Connected Load and Diversified Load for domestic premises Type of load G2 196 Assumed connected load Typical diversity factor [see notes 3 and 7] Lighting • sum of wattage of all luminaries or assume 100 W for each lighting point (except chandelier points) • chandelier lighting points – 500W • 1.8 x lamp wattage for fluorescent lighting 13A socketoutlets • 1,000 W for first socket-outlet plus 200 W for remainder socket-outlets (including kitchen ring circuits), [see note 2] 50% Kitchen power points • kitchen appliance connection points - assume 1,500 W each or actual rating of appliance (e.g. washing machine, dryer, dish washer etc) • cooker – assume 3,000 W or actual rating of oven plus the largest ring • fridge – assume 300 W or actual rating 50% Other power points • water heater – 1,500 W or actual rating • motors (e.g. lifts) – actual rating 50% Air conditioning • split air conditioning units – full rating • window air conditioning units – full rating • central a/c units, (see note 2) 90% 75% Note 1: the Connected Load values shown above are based on typical Appliances and connection points. Specific site information should be used where available. Note 2: the Connected Load (and cable rating) for Circuits supplying socket-outlets should be based on 1,000 W for the first socket-outlet, plus 200 W for the remainder, where a double socket outlet is counted as 2 (e.g. circuit rating for 5 x double socket-outlets = 1kW + 9 x 0.2kW = 2.8kW). The Electricity Wiring Regulations (Revision 1)