Valve terminal/valve sensor terminal with field bus connection VIFB1-/IIFB1-02-1/..-n Manual o D d tore 18474 GB > Res < t n e cum > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < VIFB1 – 02 Authors: Christine Lehner, Eberhard Klotz Editors: Michael Holder, H.-J. Drung Translation: D. Smith Layout: FESTO KG, Dept. PV-IDM Type setting: DUCOM < t n e cum o D d re printed on 100% receycling paper o t s e >R 9604 9604 1996 Festo KG, 73734 Esslingen, Federal Republic of Germany. All rights reserved, including translation rights. No part of this publication may be reproduced or transmitted in any form or by any means, electronic, mechanical, photocopying or otherwise, without the prior written permission of Festo > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < I VIFB1 – 02 > Res < t n e cum o D d tore KG. II > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 Contents Order no.: 18474 Title: MANUAL Designation: C.BE-VIFB-02-GB Contents Chapter 1 USER INSTRUCTIONS Chapter 2 SYSTEM STRUCTURE Chapter 3 TECHNICAL DESCRIPTION Chapter 4 INSTALLATION 4.1 Fitting the valve terminal/ valve sensor terminal . . . . . . . . . . . . . . . 4-1 < t n e cum 4.2 Installing the pneumatic components . . 4-5 4.3 Installing the electronic components . . 4-19 Chapter 5 > Res Chapter 6 o D d tore COMMISSIONING DIAGNOSIS AND ERROR TREATMENT Appendix A GLOSSARY Appendix B INDEX 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < III VIFB1 – 02 > Res IV < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 1. User instructions 1. USER INSTRUCTIONS > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 1-1 VIFB1 – 02 1. User instructions Contents USER INSTRUCTIONS. . . . . . . . . . . . . . . . . 1-3 > Res 1-2 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 1. User instructions IMPORTANT USER INSTRUCTIONS Danger categories This manual contains instructions on the hazards which may arise from improper or negligent use of the valve terminal. A distinction is made between the following instructions: WARNING This means that injury to human beings as well as material damage can occur if these instructions are not observed. CAUTION This means that material damage can occur if these instructions are not observed. > Res 9604 < t n e cum o D d tore PLEASE NOTE This means that this instruction must also be observed. > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 1-3 VIFB1 – 02 1. User instructions • This documentation describes the following products: Product Design Field bus connection for PLC from Valve terminal type 02 • VIFB-02-... Valve sensor terminal type 02 • IIFB-02-... Valve size No. of valve locations 1⁄8" Festo, Klöckner-Moeller, Siemens or 1⁄4" 4 6 8 10 12 14 16 or or or or or or Fig. 1/1: Designs of valve terminal/valve sensor terminal • Specifications on the valve terminal/valve sensor terminals of the 1/8" design are given in round brackets in this documentation. > Res 1-4 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 2. System structure 2. SYSTEM STRUCTURE > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 2-1 VIFB1 – 02 2. System structure Contents SYSTEM STRUCTURE. . . . . . . . . . . . . . . . . 2-3 Valve terminal . . . . . . . . . . . . . . . . . . . . . . . 2-3 Valve sensor terminal . . . . . . . . . . . . . . . . . 2-4 Valve terminal/valve sensor terminal in the control system . . . . . . . . . . . . . . . . . 2-5 > Res 2-2 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 2. System structure SYSTEM STRUCTURE Valve terminal Festo offers a solution to automation problems at the machine level in the form of the valve terminal. Solenoid valves, solenoid pulse valves etc. are ready fitted onto a connection block and have already been tested. Valve terminals with from 4...6 valve locations are available for the automation process. Valve terminal Circuitry Field bus connection via twocore cable (twisted, screened) < t n e cum Type 02 o D d tore Fig. 2/1: Valve terminal type 02 > Res 9604 The valve terminal with field bus connection 545 offers the following advantages: • it can be connected to various control systems • decentralized preprocessing relieves the controller (PLC) • less wiring due to two-core cables • clarity in system structure due to separation of controller and machine • valves already fitted • wired valve solenoid coils • central air supply • central exhaust • device already tested > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 2-3 VIFB1 – 02 2. System structure A field bus system also offers the following advantages: • a reduction in the number of output modules in the controller • economic data transfer over long distances • high baud rate • a large number of slaves can be linked into the network • error diagnosis is made easier Valve sensor terminal Complex automation tasks require the use of sensors for which Festo offers the valve sensor terminal. Solenoid valves, solenoid pulse valves etc. are fitted onto a connection block and have already been tested; two sensors per valve can be connected on site. Valve sensor terminals with from 4...14 valves are available for the automation process. Valve sensor terminal o D d e < t n e cum r o t s > Re Circuitry Field bus connection via two-core cable (twisted, screened) Type 02 Fig. 2/2: Valve sensor terminal type 02 The valve sensor terminal includes all the advantages of the valve terminal. It also offers: • two inputs per valve location, e.g. for sensors • two additional inputs • two additional outputs, e.g. for electric actuators, displays etc. 2-4 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 2. System structure Valve terminal/valve sensor terminal in the control system The valve terminal/valve sensor terminals are slaves in a field bus system. They can be connected to field bus modules of the following automation systems: Controller Controller (PLC) manufacturer Field bus module Field bus Festo • FPC 400 • SF-202 Type 02...05 • E.CFA • (integrated) Festo field bus KlöcknerMoeller SUCOS PS 30 series e.g. • PS 316 • PS 306 • PS 3 series • PS 4-100 series • PS 416 • PS 4-201 Serial bus interface e.g. • EBE295.1 SUCONET K1 (KL1) Siemens SIMATIC S5 series e.g. • S5-115U . . . • S5-155U PC 16/20 Teleperm/M MMC-216 Module e.g. • IM308 ET100 > Res < t n e cum o D d tore Fig. 2/3: Automation system Fig. 2/4 shows a valve terminal/valve sensor terminal with field bus connection as part of the FPC 405 control system from Festo. The system structure shown in the example of the FPC 405 controller can be used with the above-mentioned automation systems from Klöckner-Moeller and Siemens. 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 2-5 VIFB1 – 02 2. System structure PC FST Programming software Field bus module E.CFA FPC 405 Line 1 (Field bus address 1...31) Line 2 (Field bus address 32...62) Line 3 (Field bus address 63...93) < t n e cum Field bus VIFB-01-. > Res Power unit 220V ~ 24 V = o D d tore Actuator VIFB-02-. . Actuator IIFB-02-... Sensor Sensor Actuator Fig. 2/4: System structure FPC 405 with valve terminal/ valve sensor terminal 2-6 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 2. System structure Explanation of the system structure The FPC 405 controller is programmed by means of the Festo programming software FST 405. This software package enables user programs to be written in the programming languages STL (Statement List), LDR (Ladder Diagram) and BASIC. The software must be installed on a personal computer (PC) which is connected via the diagnostic interface of a processor module of the FPC 405. The field bus module E.CFA controls the complete exchange of information between the field bus slaves (decentralized I/O modules) e.g. valve terminal/valve sensor terminals, and the processor modules of the controller. > Res 9604 < t n e cum The field bus slaves are connected via the field bus interface on the field bus module. Three physical lines (field bus cables) with up to 31 field bus slaves can be connected to the field bus interface. With the Siemens module AS3083U two lines each with 32 decentralized I/O modules can be connected. With Klöckner-Moeller control systems, the number of lines and the number of field bus slaves per line depends on the type of controller used. With the PS3 controller, for example, up to three field bus slaves can be controlled. o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 2-7 VIFB1 – 02 2. System structure The field bus creates data communication between the controller and the field bus slaves (e.g. valve terminal/valve sensor terminal) distributed throughout the system. Data transmission is made in accordance with standard RS 485. Baud rates up to 375 kBaud can be set. The valve terminal as a decentralized output module processes the signals transmitted and controls the actuators which are connected. The valve terminal is supplied with current via an external power unit (AC 220V/DC 24V). The valve sensor terminal as a decentralized input/output module functions like a valve terminal. It also processes up to 22 inputs. The sensors register information (measured variables) from the control process and pass this on to the valve sensor terminal (further processing unit). > Res 2-8 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 3. Technical description 3. TECHNICAL DESCRIPTION > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 3-1 VIFB1 – 02 3. Technical description Contents TECHNICAL DESCRIPTION . . . . . . . . . . . . 3-3 Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 Valve terminal . . . . . . . . . . . . . . . . . . . . . . . . 3-3 Valve sensor terminal . . . . . . . . . . . . . . . . . . 3-5 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 Explanation on function summary . . . . . . . . . 3-9 Technical specifications . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electronic components . . . . . . . . . . . . . . . . Field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . Pneumatic components . . . . . . . . . . . . . . . . Connection block . . . . . . . . . . . . . . . . . . . . . Technical specifications of valves . . . 3-16 - > Res 3-2 3-10 3-10 3-11 3-13 3-14 3-14 3-17 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 3. Technical description TECHNICAL DESCRIPTION Structure Valve terminal The valve terminal consists of the following components: POWER BUS 1 2 BUS > Res 4 Figure < t n e cum o D d tore 3 Components 1 Field bus terminal 2 Valve terminal base unit consisting of: • Valve coupling unit (upper part) • Connection block (lower part) 3 Valve locations for • Solenoid pulse valves or • Solenoid mid-position valves or • Solenoid valves or • Relay boards or • Cover plates 4 Earth connection (M4-screw thread) Fig. 3/1: Components of the valve terminal 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 3-3 VIFB1 – 02 3. Technical description The following operation and display elements are to be found on the components of the valve terminal: 7 1 8 POWER 2 3 4 BUS 5 BUS 9 9 11 < t n e cum 6 10 8 r o t s > Re o D d e Figure 1 2 3 4 5 6 7 8 9 10 11 Components 7 Valve terminal inscription field Green LED Red LED Operating voltage connection Field bus interface Type plate Valve location inscription field (pervalve solenoid coil) Yellow LED (per valve solenoid coil) Common cable connections Work line connections (per valve) Earth connection (M4-screw thread) Fig. 3/2: Operation and display elements of the valve terminal The composition of the type plate is shown in Fig. 3/5 using the valve sensor terminal as an example: 3-4 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 3. Technical description Valve sensor terminal The valve sensor terminal consists of the following components: POWER BUS BUS 1 2 o D d tore 4 > Res Figure < t n e cum 3 Components 1 Field bus terminal 2 Valve sensor terminal base unit consisting of: • Valve sensor coupling unit (upper part) • Connection block (lower part) 3 Valve locations for • Solenoid pulse valves or • Solenoid mid-position valves or • Solenoid valves or • Relay boards or • Cover plates 4 Earth connection (M4-screw thread) Fig. 3/3: Components of the valve terminal 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 3-5 VIFB1 – 02 3. Technical description The following operation and display elements are to be found on the components of the valve sensor terminal: 9 1 10 11 2 3 4 5 6 7 12 POWER 13 BUS BUS 14 14 16 > o D d e r o t s Re Figure 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 < t n e cum 8 15 12 13 Components Connections for additional outputs Fuse for inputs Valve sensor terminal inscription field Green LED Red LED Operating voltage connection Field bus interface Type plate Connections for inputs (e.g. sensors) Inscription field inputs/outputs (per connection) Yellow or green LED (per additional input/output) Yellow LED (per valve solenoid coil) Valve location inscription field (per valve solenoid coil) Common cable connections Work line connections (per valve) Earth connection (M4-screw thread) Fig. 3/4: Operation and display elements of the valve sensor terminal 3-6 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 3. Technical description The composition of the type plate is shown in Fig. 3/5 using the valve sensor terminal as an example. The type plate is situated below the field bus node and contains the following specifications: IIFG-02-1⁄4-4 18504 Max. bar 10 max. PSI 145 24 V DC Type designation of base unit (here installation terminal) Part number Max. operating pressure in bar and psi Permitted operating voltage Fig. 3/5: Example – type plate of valve sensor terminal > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 3-7 VIFB1 – 02 3. Technical description Function The valve terminal or valve sensor terminal as a system with decentralized outputs or decentralized inputs/outputs should be placed in the immediate vicinity of the processing unit. Connection to the control level is made via the field bus which operates on the master-slave principle. The field bus module of the control system functions here as master, and the valve terminal/valve sensor terminal (field bus participants) as slave. The field bus module transmits cyclic telegrams to the valve terminal/valve sensor terminal. This receives and processes the data transmitted and sends a reply telegram to the field bus module. Field bus module of controller (PLC) Field bus > Res Operating voltage connection < t n e cum Valve coupling unit or Valve-sensor coupling unit o D d tore Field bus node Field bus interface Valve Pneumatic interface (see also opposite) Actuator Connection block Field bus participant Fig. 3/6: Function summary of valve terminal/valve sensor terminal 3-8 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 3. Technical description Explanation of the function summary The field bus node controls the following functions: • The connection of the valve terminal/valve sensor terminal to the field bus module of the control system and to further field bus slaves via the field bus interface. • The commissioning function by setting the field bus baud rate and protocol. • The control of data transfer to/from the field bus module of the control system. • The internal control of the valve terminal/valve sensor terminal. > Res 9604 The valve coupling unit of the valve terminal contains the operating voltage connection and a decoder. This decodes the signals from the field bus node and transmits the pulses to the valves. The valve-sensor coupling unit of the valve sensor terminal contains the operating voltage connection and a decoder. This decodes the signals from the field bus node and transmits the pulses to the valves. The electrical inputs for e.g. sensors, as well as two additional outputs are also situated here. The valves control the flow of air to the actuators. The valves are supplied with compressed air via the common channels of the connection block. The exhaust and pilot exhaust from the valves are also ventilated via these channels. The connection block is connected to the common cables of the pneumatic system via the pneumatic interfaces. < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 3-9 VIFB1 – 02 3. Technical description Technical specifications General Protection class (as per DIN 40050) IP 65 Temperature at • operation • storage/transport - 5 oC . . . +50 oC -20 oC . . . +60 oC Chemical resistance s. Festo Pneumatic Catalogue Chapter 2.6, Reference part (resistance table) Dimensions (LxWxH) when base unit is fully fitted • Valve terminal – VIFB-02-1⁄4 (1⁄8)-4 o D d tore – VIFB-02-1⁄4 (1⁄8)-10 > Res – VIFB-02-1⁄4 (1⁄8)-12 – VIFB-02-1⁄4 (1⁄8)-14 – VIFB-02-1⁄4 (1⁄8)-16 • Valve sensor terminal – IIFB-02-1⁄4(1⁄8)-4 – IIFB-02-1⁄4(1⁄8)-6 – IIFB-02-1⁄4(1⁄8)-8 – IIFB-02-1⁄4(1⁄8)-10 – IIFB-02-1⁄4(1⁄8)-12 – IIFB-02-1⁄4(1⁄8)-14 3-10 288 275.4 288 275.4 288 275.4 288 275.4 288 275,4 288 275.4 288 275.4 x x x x x x x x x x x x x x 141 mm 139.5 mm) 141 mm 139.5 mm) 141 mm 139.5 mm) 141 mm 139.5 mm) 141 mm) 139.5 mm) 141 mm 139.5 mm 141 mm 139.5 mm 259.5x (235.5x 325.5x (289.5x 391.5x (343.5x 457.5x (397.5x 501 x (429 x 567 x (483 x 353.4 340.8 353.4 340.8 353.4 340.8 353.4 340.8 353.4 340.8 353.4 340.8 x x x x x x x x x x x x 141 mm 139.5 mm) 141 mm 139.5 mm) 141 mm 139.5 mm) 141 mm 139.5 mm) 141 mm 139.5 mm) 141 mm 139.5 mm < t n e cum – VIFB-02-1⁄4 (1⁄8)-6 – VIFB-02-1⁄4 (1⁄8)-8 259.5x (235.5x 325.5x (289.5x 391.5x (343.5x 457.5x (397.5x 501 x (429 x 567 x (483 x 655.5x (559.5x > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 3. Technical description Electronic components Operating voltage Electronic components and inputs (Pin 1 – Operating voltage connection) • Rated value (protection against incorrect polarity) • Tolerance DC 24 V ± 25 % (DC18 V . . . 30 V) ± 4 Vpp • Residual ripple • Current capacity (at 24 V) Valve terminal 200 mA Valve sensor terminal 15 200 mA + sum of current capacity of inputs Output (P) • Calculation P[W] = (0.2 A + ∑ I Inputs) ⋅ 24 V Power failure bridging time > Res Operating voltage outputs (Pin 2 – Operating voltage connection) • Rated value (protected against incorrect polarity) • Tolerance < t n e cum o D d tore DC 24 V ± 10 % (DC 21.6 V . . . 26.4 V) • Residual ripple ± 4 Vpp • Current capacity (at 24 V) 10 mA + sum current capacity additional outputs + sum current capacity of switched valve solenoid coils (per valve solenoid coil 120 mA) Output (P) • Calculation 9604 min. 20 ms P[W] = (0.01 A + ∑ IAdditional outputs + ∑ ISolenoid coil) ⋅ 24 V > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 3-11 VIFB1 – 02 3. Technical description Electromagnetic compatibility (EMC): Resistance to interference *) ● tested as per EN 50082-2 Limit value class A Spark supression tested as per EN 55011 ● *) The valve terminal with FB1-02 can also be used in a residential environment with individual authorization (residential, business, commercial environment, small firms.) Additional outputs / valve sensor terminal Loading per • additional output Electronic fusing (short circuit, overload) • Trigger current • Response time (short circuit) max. 0.5 A (Bulbs max. 20 W because of PTC resistor characteristics Inputs / valve sensor terminal Logic level • ON • OFF > 3-12 max. 1 A max. 1 s < t n e cum o D d e r o t s Re 12 V 7.5 V Voltage range 0 V ... 30 V Current capacity (at 24V) (current from sensor to input) max. 9 mA Response delay (at 24 V) typ. 5 ms > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 3. Technical description Field bus Design RS 485, floating Transmission type serial Transmission process asynchronous, half duplex Protocol • can be set on switch Baud rate • can be set on switch (dependent on protocol) Cable length (dependent on baud rate) Cable type (dependent on cable length and field bus baud rate set) > Res 9604 Festo Field bus or Siemens ET100 or Klöckner-Moeller SUCONET 31.25 62.5 187.5 375 kBaud kBaud kBaud kBaud up to 4000 m See manual for controller (e.g. Festo FPC405, Chapter 7, Field bus module) < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 3-13 VIFB1 – 02 3. Technical description Pneumatic components • filtered or filtered and dried compressed air • lubricated or unlubricated compressed air Air quality Filter fineness (standard) • Poppet valve • Spool valve 40 µm 40 µm Pressure • Operating pressure range • Rated pressure • Highest pressure at 1 2 bar ... 10 bar; 29 psi ... 145 psi 6 bar 10 bar Fastening • Type • Mounting < t n e cum Size of connection with • 1 (compressed air) 3 and 5 (exhaust) > Res 3-14 o D d tore • 82 and 84 (pilot exhaust) 4 through holes From the front with 4 hexagon head bolts (M6x60) G1⁄2 (G3⁄8) G1⁄8 (G1⁄8) > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 3. Technical description d e r o t s e R > < t n e m u c o D Please unfold for page 3-16 9604 Please unfold for page 3-16 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 3-15 VIFB1 - 02 3. Technical description Technical specifications of valves Designation Size Switching symbol Construction Type MVH-5-1/4 B-VI Pilot air Form Manual override Basic setting (as at factory) Lubrication Option (conversion necessary) Fastening with 2 slotted head screws M4x55 1/4" without MVH-5-1/8 B-VI 1/8" MVH-5-1/4-S B-VI 1/4" MVH-5-1/8-S B-VI 1/8" MVH-5-1/4-L B-VI 1/4" MVH-5-1/8-L B-VI 1/8" MVH-5-1/4-L-S B-VI 1/4" Poppet valve unilaterallyoperated 5/2 way Single spindle with cyl. compression spring for basic position. M4x50 M4x55 with With automatic return Spool valve bilaterallyoperated 5/2 way Soft piston in sleeve with pressure relief slots. Outlet slots are overrun. With lock or safety lock 1/8" IMVH-5-1/4 B-VI 1/4" IMVH-5-1/8 B-VI IMVH-5-1/4-S B-VI IMVH-5-1/8-S B-VI MVH-5/3G-1/4 B-VI MVH-5/3G-1/8 B-VI MVH-5/3E-1/4 B-VI d e tor 1/8" s e >R 1/4" 1/8" 1/4" Spool valve bilaterallyoperated 5/2 way without With automatic return With lock or safety lock with M4x55 M4x50 M4x65 Service life lubrication (silicon-free from factory) MVH-5/3E-1/8 B-VI 1/8" MVH-5/3B-1/4 B-VI 1/4" M4x60 M4x65 M4x60 M4x65 without 1/8" 1/4" M4x55 M4x50 m u c o D Soft piston in sleeve with pressure relief slots. Outlet slots are overrun. M4x50 < t en without with MVH-5-1/8-L-S B-VI Service life lubrication (silicon-free from factory) M4x60 Spool valve bilaterallyoperated 5/3 way Soft piston in sleeve with pressure relief slots. Outlet slots are overrun. without With automatic return With lock or safety lock Service life lubrication (silicon-free from factory) M4x65 M4x60 M4x65 without MVH-5/3B-1/8 B-VI 3-16 1/8" M4x60 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 Size 3. Technical description Pressure Operating pressure Flow Pilot pressure Auxiliary pilot air (Pneumatic spring) – – 1/4" 2 ... 10 bar 1/8" 1/4" 1.5 ... 10 bar 0 ... 10 bar 1/8" Size of connection Nominal with size 2 and 4 12 and 14 (work air) (Auxiliary pilot air) G 1/4 7 mm G 1/8 5 mm G1/4 7 mm – 2 ... 10 bar G1/8 1/4" – G 1/8 10 mm 1/8" G1/8 8 mm 1/4" G1/4 -0.9 ... 10 bar 3 ... 10 bar 3 ... 10 bar G1/4 1/8" – G1/8 G1/8 1/8" 1/4" e R > 3 ... 10 bar 1/8" 2 ... 10 bar – G1/4 – – 1/4" 1/8" – 10 mm 8 mm G1/4 10 mm G1/8 8 mm – 1/8" 3 ... 10 bar 8 mm G1/8 G1/4 3 ... 10 bar 10 mm – 1/4" G1/8 OFF at 6 bar 41 ms 750 0.76 17 ms 36 ms Q = 1100 CV = 1.12 19 ms 41 ms 17 ms 36 ms 750 0.76 1600 1.63 1000 1.02 1600 1.63 1000 1.02 1600 1.63 1000 1.02 1600 1.63 1000 1.02 1600 1.63 1000 1.02 1600 1.63 1000 1.02 1600 1.63 1000 1.02 < t en m u c o D 8 mm d e r o t s 2 ... 10 bar -0.9 ... 0 bar Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = Q = CV = 10 mm G1/8 – 1/4" Q = 1300 CV = 1.32 10 mm G1/8 8 mm G1/4 10 mm G1/8 8 mm – > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 33 ms 40 ms 30 ms 100 ms 33 ms 40 ms 30 ms 100 ms 18 ms Switchover time 22 ms 18 ms Reaction time calculation Depends on program, approx. 4 ms per 1 kBit instruction + valve switching times 22 ms 27 ms 36 ms 30 ms 30 ms 1 ) 33 ms 45 ms 2 ) 40 ms 50 ms 1 ) 32 ms 38 ms 2 ) 40 ms 50 ms Notes: 1) Mid-position Q=1000, CV=1.02 9604 Valve switching times ON at 6 bar 19 ms Q = 1100 CV = 1.12 Q = CV = – 1/8" 1/4" Q = 1300 CV = 1.32 5 mm G1/4 3 ... 10 bar 1 Times Rated flow Switch position 2 or 1 4 2 3 or 4 5 [l/min] [l/min] 2 ) Mid-position Q= 400, CV=0.41 3-17 VIFB1 - 02 3. Technical description d e r o t s e R > < t n e m u c o D Please unfold for page 3-17 3-18 Please unfold for page 3-17 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation 4.1 FITTING THE VALVE TERMINAL / VALVE SENSOR TERMINAL > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-1 VIFB1 – 02 4. Installation Contents FITTING THE VALVE TERMINAL/ VALVE SENSOR TERMINAL . . . . . . . . . . . 4-3 > Res 4-2 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation FITTING THE VALVE TERMINAL/VALVE SENSOR TERMINAL Before fitting the valve terminal/valve sensor terminal please see that there is sufficient space to the left and/or right of the connection block for fitting the hoses and, if necessary, the silencers. There are 4 through holes on the right and lefthand edges of the connection block for fastening the valve terminal/valve sensor terminal (see following diagram). POWER BUS BUS < t n e cum 1 > Res o D d tore 1 1 Mounting holes for M6 hexagon head bolts Fig. 4/1: Through holes for mounting 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-3 VIFB1 – 02 4. Installation The following procedure should be adopted: 1. Bore four holes in the mounting surface. The distance between the holes depends on the type of valve terminal/valve sensor terminal used (see following diagram). POWER BUS BUS 6.8 mm L1 > Res < t n e cum o D d tore Valve terminal/ valve sensor terminal VIFB-/IIFB-02-1⁄4(1⁄8)-4 VIFB-/IIFB-02-1⁄4(1⁄8)-6 VIFB-/IIFB-02-1⁄4(1⁄8)-8 VIFB-/IIFB-02-1⁄4(1⁄8)-10 VIFB-/IIFB-02-1⁄4(1⁄8)-12 VIFB-/IIFB-02-1⁄4(1⁄8)-14 VIFB-02-1⁄4(1⁄8)-16 L2 Distance between holes [mm] L2 L1 32 (27.5) 222 (198) 32 (27.5) 288 (252) 32 (27.5) 354 (306) 32 (27.5) 420 (360) 32 (27.5) 486 (429) 32 (27.5) 522 (483) 32 (27.5) 618 (522) Fig. 4/2: Fitting the valve terminal/ valve sensor terminal 2. Fasten the valve terminal onto the mounting surface with 4 hexagon head bolts (M6x60). The bolts should be tightened in diagonally opposite sequence. 4-4 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation 4.2 INSTALLING THE PNEUMATIC COMPONENTS > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-5 VIFB1 – 02 4. Installation Contents INSTALLING THE PNEUMATIC COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . 4-7 Laying the hoses . . . . . . . . . . . . . . . . . . . . . 4-7 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7 Preparing the connection block. . . . . . . . . . . 4-8 Connecting the connection block . . . . . . . . . 4-9 Connecting the valves . . . . . . . . . . . . . . . . . 4-10 Solenoid valve (5/2-way) . . . . . . . . . . . . 4-11 Solenoid pulse valve (5/2-way) and Solenoid mid-position valve (5/3-way) . . 4-12 Checking the valve functions . . . . . . . . . Manual overrride . . . . . . . . . . . . . . . . . . . . . Designs of manual override . . . . . . . . . . Testing . . . . . . . . . . . . . . . . . . . . . . . . . . Locking the manual override . . . . . . . . . > Res 4-6 4-13 4-13 4-14 4-15 4-17 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation INSTALLING THE PNEUMATIC COMPONENTS WARNING Before installation or maintenance work is carried out the following must be switched off: • the operating voltage for electronic components and/or inputs. • The operating voltage for outputs. Laying the hoses PLEASE NOTE A suitable seal should be placed under each screw connection or each silencer. If elbow connectors or multiple distributors are used the air flow will usually be reduced. < t n e cum General • Connecting > Res o D d tore 1. Push the hose as far as it will go into or over the screw connection. 2. Pull the locking ring over the hose connection or tighten the locking screw. 3. For reasons of clarity the hoses should be grouped together with: – hose straps or – multiple hose holders. • Disconnecting 1. Loosen the locking screw or locking ring on the connection. 2. Remove the hose. 3. If necessary, replace the screw connection by blind plugs. 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-7 VIFB1 – 02 4. Installation Preparing the connection block Connections for common lines are provided on both sides of the connection block. The common lines can therefore be fitted either on the right or the left, depending on individual requirements. To increase the air flow we recommend that the lines for compressed air supply and ventilation be connected on both sides in the following cases: • When the valve terminal/valve sensor terminal has more than 10 valves (rated supply pressure 6 bar) • With large-volume actuators The connections should be made in accordance with the table below: < t n e cum o D d tore 5/3 > Res Connections for common hoses (adhesive foil) 1 3/5 Connections for common hoses (blind plugs) Connection for common hoses Procedure Unilateral Remove all adhesive foil as late as possible Fit blind plugs unilaterally Bilateral Remove all adhesive foil and blind plugs Fig. 4/3: Connections on the sub-base 4-8 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Connecting the connection block The screw connectors or silencers should be fitted with the appropriate seals as indicated in the table below. The hoses should then be fitted into place. Pilot exhaust Exhaust > o D d re o t s e R Common lines Compressed air < t n e cum 82 84 5 or 3 Compressed air 3 or 5 Pilot exhaust Exhaust 1 Connection code (ISO 5599) Size of connection (ISO 228) 1 G 1⁄2 (G3⁄8) 1⁄2 (G3⁄8) Exhaust 5/3 3/5 G Pilot exhaust 82 G 1⁄8 (G1⁄8) 84 Connection Screw connector Screw connector (with common exhaust) or silencer Fig. 4/1: Pin assignment of connection block 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-9 VIFB1 – 02 4. Installation Connecting the valves PLEASE NOTE The non-reserved or free valve locations should be protected with a cover plate. If one of the fitted valves is not used, connections 2 and 4 as well as 14 and, if necessary, 12 must be covered with blind plugs. The seals used on connections 2 and 4 should be of aluminium. Remove the lupolen plugs and fit the screw connectors with the appropriate seals as indicated in the following tables: Fig. 4/5: Pin assignment of solenoid valve Fig. 4/6: Pin assignment of solenoid pulse valve and solenoid mid-position valve The hoses should then be fitted into place. > Res 4-10 < t n e cum o D d tore PLEASE NOTE The work connections 2 and 4 are situated in different positions on the various types of valves (see also next page). > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Solenoid valve (5/2-way) MVH-5-1/4-L-B-VI MVH-5-1/8-L-B-VI MVH-5-1/4-L-S-B-VI MVH-5-1/8-L-S-B-VI MVH-5-1/4-B-VI MVH-5-1/8-B-VI MVH-5-1/4-S-B-VI MVH-5-1/8-S-B-VI 14 14 < t n e cum 2 4 2 > Res Line o D d tore 4 12 12 Connection code (ISO 5599) Size (ISO 228) Connection Work air 2 4 G 1⁄4 (G1⁄8) Screw connector or multiple distributor Auxiliary pilot air 14 G 1⁄8 (G1⁄8) Only with "S valves" Pneumatic spring 12 G 1⁄8 (G1⁄8) Only with "L valves" Fig. 4/5: Pin assignment of solenoid valve 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-11 VIFB1 – 02 4. Installation Solenoid pulse valve (5/2-way) and Solenoid mid-position valve (5/3-way) 14 Auxiliary pilot air - only "S valve" - 14 2 Work air 2 , 4 4 < t n e cum Auxiliary pilot air - only "S valve"- 12 > Res 12 o D d tore Line Connection Size of Connection code connection (ISO 5599) (ISO 228) Work air 2 4 G 1⁄4 (G1⁄8) Screw connector or multiple distributor Auxiliary pilot air 12 14 G 1⁄8 (G1⁄8) Only "S valve" Fig. 4/6: Assignment of solenoid pulse valve and solenoid mid-position valve 4-12 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Checking the valve functions Manual override The manual override (see Fig. 4/7) is used principally when the pneumatic system is commissioned, as a means of checking the function and effect of the valve or of the valve-cylinder combination. By operating the manual override, the user can switch the valve without an electric signal. Only the compresssed air supply needs to be switched on. Pilot valve Manual override < t n e cum 14 o D d tore 4 > Res 2 Base valve 12 Manual override Pilot valve Fig. 4/7: Position of the manual override 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-13 VIFB1 – 02 4. Installation Designs of manual override The manual override has been designed so that it can be used as follows: Manual override design Method of operation Manual operation with automatic reset. Basic setting as at factory After operation the manual override is reset by spring force Manual override with stop. Conversion of manual override necessary Two versions: a) see above. b) manual override can be in fixed state when operated. Manual override with safety lock. Conversion of manual override necessary Operation of manual override not possible. Fig. 4/8: Manual override designs > Res 4-14 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Testing 1. Switch on the compressed air supply. 2. Check the function and effect of each individual valve as follows. If the valve does not function correctly see Fig. 4/11. • Manual override with automatic reset: Operating the manual override Reaction of valve or of processor The valve or the processor • switches Press the plunger of manual override as far as it will go. o D d re < t n e cum o t s e >R Hold plunger of manual override pressed down. Remove the screwdriver. A spring returns the plunger of manual override to start position. • remains switched • returns to basic setting Fig. 4/9: Manual override with automatic reset 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-15 VIFB1 – 02 4. Installation • Manual override with stop: Operating the manual override Reaction of valve or of processor The valve or processor > Res Insert screwdriver in groove of plunger. Press plunger as far as it will go and turn it to the right. • returns to switch position Remove screwdriver • remains in switch position Insert screwdriver in the groove of the plunger. Press and turn plunger to the left and remove the screwdriver. < t n e cum • returns to basic setting o D d tore Fig. 4/10: Manual override with stop 3. Switch off the compressed air supply when the valves have been tested. 4-16 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Incorrect functioning: When the compressed air supply is switched on or during the subsequent test of the valves, the following is known about the operating status of the pneumatic system: Operating status of pneumatic system Air comes out . . . • of common line connections • of work line connections Valve or pneumatic system . . . • does not react as expected • does not react Valve position Error treatment after switching off compressed air supply • Basic setting • Switch position Checking the seal or hose fitting • Switch position • Check the hose lines • Switch position • Check operating pressure • Service case Fig. 4/11: Operating status of the pneumatic system < t n e cum Locking the manual override > Res o D d tore WARNING The manual override must be protected against unauthorised use in systems where security is of great importance. A conversion must be made to the manual override before it can be locked. 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-17 VIFB1 – 02 4. Installation > Res 4-18 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation 4.3 INSTALLING THE ELECTRONIC COMPONENTS > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-19 VIFB1 – 02 4. Installation Contents INSTALLING THE ELECTRONIC COMPONENTS . . . . . . . . . . . . . . . . . . . . . . 4-21 Opening and closing the field bus node . . . . . . . . . . . . . . . . . . . . . . 4-22 Configuring the valve terminal/ valve sensor terminal . . . . . . . . . . . . . . . . Address selector switch. . . . . . . . . . . . . . . . Setting the field bus address . . . . . . . . . Dual in-line switch (DIL switch) . . . . . . . . . . Setting the field bus baud rate . . . . . . . . Setting the field bus protocol . . . . . . . . . > Res 4-20 Connecting the valve terminal/ valve sensor terminal . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting sockets . . . . . . . . . . . . . . . . 24 V operating voltage connection . . . . . . . Applying the 24 V operating voltage . . . Field bus interface . . . . . . . . . . . . . . . . . . . . Field bus cable . . . . . . . . . . . . . . . . . . . . Connecting the field bus interface . . . . . Fitting the terminating resistor . . . . . . . . Outputs and valve locations . . . . . . . . . . . . Additional outputs . . . . . . . . . . . . . . . . . . . . Connection assignment of additional outputs . . . . . . . . . . . . . . . . . . Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connection assignment of inputs . . . . . . Circuitry. . . . . . . . . . . . . . . . . . . . . . . . . . 4-23 4-24 4-24 4-26 4-27 4-27 4-28 4-28 4-28 4-30 4-31 4-34 4-35 4-35 4-38 4-40 4-41 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-40 4-43 4-44 4-45 9604 VIFB1 – 02 4. Installation INSTALLING THE ELECTRONIC COMPONENTS WARNING Before installation or maintenance work is carried out the following must be switched off: • The operating voltage for electronic components and/or inputs. • The operationg voltage for outputs. The necessary pre-settings and the connections to the electronic components are described in this chapter. The following table summarizes the procedure. Switching off operating voltage and compressed air supply Opening the field bus node < t n e cum Configuring the valve terminal/valve sensor terminal • Address selector switch (Setting the field bus address) • DIL switch (Setting the field bus baud rate and field bus protocol) > Res o D d tore Closing the field bus node Connecting the valve terminal/valve sensor terminal • General (connecting sockets) • 24V operating voltage connection • Field bus interface (Connecting the interfaces and if necessary installing a terminating resistor) • Outputs (Pin assignment) • Inputs (Pin assignment and circuitry) Checking the pre-settings and connections Switching on operating voltage and compressed air supply (see Chapter 5) 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-21 VIFB1 – 02 4. Installation Opening and closing the field bus node WARNING Before the field bus node is opened, the operating voltage of the following must be switched off: – electronic components and or inputs – outputs The following connection and display elements are situated on the cover of the field bus node: Green LED POWER BUS Plug for field bus cable < t n e cum BUS > Res Red LED o D d tore Philips screw Fig. 4/12: Cover of the field bus node • Opening Unscrew the 4 Philips screws in the cover and remove the cover. • Closing Replace the cover on the field bus node and tighten the Philips screws in diagonally opposite sequence. 4-22 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Configuring the valve terminal/valve sensor terminal There are two PC boards in the field bus node. Board 1 contains an LED and a plug for the field bus cables; board 2 contains an LED and a switch for setting the configuration. Green LED Red LED Plug for field bus cables Address selector switch Screening > Res Board 2 < t n e cum 12 34 Board 1 DIL switch o D d tore Fig. 4/13: Connections, operation and display elements of field bus node 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-23 VIFB1 – 02 4. Installation Address selector switch The field bus address of the valve terminal/valve sensor terminal can be set with the two address selector switches on board 2. The switches are numbered from 0...9. The arrow on the address selector switches indicates the tens and units figure of the field bus address which has been set. UNITS 7 8 9 6 0 5 4 1 3 2 7 8 9 6 5 4 3 2 TENS Address selector switch UNITS figure Address selector switch TENS figure 0 1 Fig. 4/14: Function of the address selector switch < t n e cum Setting the field bus address > Res o D d tore PLEASE NOTE Field bus addresses may only be assigned once per field bus module. Recommendation: We recommend that the field bus addresses be assigned in ascending order. Field bus addresses should be assigned in accordance with the machine structure of the system. The field bus addresses set should be noted in the grey inscription field above the field bus node. 4-24 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Possible field bus addresses: PLC Address designation Addresses Festo Klöckner-Moeller • PS 3/PS 4 as master • other master Siemens Field bus address 1; 2; 3; ...; 99 2; 3; 4; 2; 3; 4; ...; 31 1; 2; 3; ...; 63 ET100 no. Fig. 4/15: Field bus addresses The following procedure should be adopted: 1. Switch off the operating voltage. 2. Assign a non reserved field bus address to the valve terminal/valve sensor terminal. 3. With a screwdriver set the arrow of the appropriate address selector switch to the tens and/or units figure of the desired field bus address. < t n e cum Example: > o D d re o t s e R Example 1 UNITS 7 8 6 9 5 4 6 5 4 3 2 7 8 9 3 2 TENS Example 2 0 1 0 1 UNITS 7 8 9 6 0 5 1 4 3 2 7 8 9 6 5 4 3 2 TENS Field bus address set: 05 Field bus address set: 38 0 1 Fig. 4/16: Example of field bus addresses set 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-25 VIFB1 – 02 4. Installation Dual in-line switch (DIL switch) The following functions must be set on the DIL switch: • Field bus baud rate • Field bus protocol The DIL switch consists of four switch elements. These are numbered from 1...4. The position ’ON’ is marked. 3 < t n e cum 4 Field bus protocol 1 o D d tore 2 > Res Field bus baud rate Field bus baud rate Field bus protocol ON Fig. 4/17: Position and function of the DIL switch 4-26 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Setting the field bus baud rate PLEASE NOTE The field bus baud rate should be set on the valve terminal/valve sensor terminal so that it agrees with the setting on the field bus module (master) of the control system. Klöckner-Moeller systems: Please note that with Klöckner-Moeller control systems only the field bus baud rate 187.5 kBaud is permitted. Field bus baud rate [kBaud] 31.25 DIL switch 62.5 187.5 375 1 1 1 1 1 2 2 2 2 2 < t n e cum 3 4 ON o D d tore Fig. 4/19: Setting the field bus baud rate > Res Setting the field bus protocol The setting depends on the control system used. Control system DIL switch Festo Klöckner-Moeller Siemens 1 2 3 3 3 4 4 4 4 ON ON ON ON 3 Fig. 4/18: Setting the field bus protocol 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-27 VIFB1 – 02 4. Installation Connecting the valve terminal/valve sensor terminal General PLEASE NOTE If one of the plugs is not used, it should be sealed with a protective cap (protection class IP65). Connecting the cables to the plugs/sockets > Res 1. Open the plugs/sockets as follows (see following diagram): • Power supply socket: Insert the power supply socket into the operating voltage plug on the valve terminal/valve sensor terminal. Unscrew the housing part of the socket. Now remove the connection part of the socket from the plug. • Sensor socket (for field bus connection and electrical inputs/outputs): Unscrew the centre knurled nut. • Bus cable socket (for field bus connection): Unscrew the centre knurled nut. < t n e cum o D d tore 2. Unscrew the stain relief part at the rear of the housing. Insert the cables as follows (see diagram): Cable diameter: • power supply socket PG 7: 4.0 mm ... 6.0 mm • sensor socket PG 9: 6.0 mm ... 8.0 mm PG 13:10.0 mm ...12.0 mm Plugs/sockets (straight or angled): • • • 4-28 power supply sensor socket bus cable socket PG 7, 9 or 13.5 PG 7 PG 7, 9 or 13.5 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Cable Strain relief Housing Connecting part Socket Plug Fig. 4/20: Plug/socket parts and cable routing 3. Remove the insulation from 5 mm of the end of the cables. < t n e cum 4. If necessary, fit the strands with cable end sleeves. o D d tore 5. Connect the ends of the conductors. > Res 6. Replace the connection part onto the housing of the plug/socket. Pull the cable back so that it is not looped around inside the socket. 7. Close the plug/socket as follows: • Power supply socket: Press with the thumb from the front onto the socket and tighten the housing. • Sensor socket, bus cable socket: Tighten the knurled nut. 8. Tighten the stain relief of the plug/socket to prevent the cable connection from becoming loose. 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-29 VIFB1 – 02 4. Installation 24 V operating voltage connection WARNING An electrically isolating transformer as per EN 60742/IEC 742 with at least 4 kV isolation resistance is requiered in order that the operating voltages can be reliably separated. The connection for the operating voltage is on the left-hand edge of the base unit of the valve terminal/valve sensor terminal. Operating voltage connection > Res POWER BUS < t n e cum BUS o D d tore Fig. 4/21: Position of operation voltage connection 4-30 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation The following components of the valve terminal/valve sensor terminal are supplied separately with +24 V DC via this connection: • electronic components and/or inputs (tolerance: ± 25 %) • outputs (tolerance: ± 10 %) PLEASE NOTE The electronic components and inputs show a greater tolerance range of the 24 V operating voltage than the outputs. Under certain circumstances this can cause the electronic components to indicate the switching status of the outputs, although the latter are not in the switched position (operating voltage of the outputs outside tolerance range). > Res < t n e cum The 24 V operating voltage of the outputs should be tested whilst the system is operating. Please see that the operating voltage of the outputs is within the permitted tolerances even during full operation. o D d tore Applying the 24 V operating voltage PLEASE NOTE Please observe the polarity when the operating voltage is applied. The following diagram shows the pin assignment of the operating voltage connection. A suitable 24 V supply should be connected via the mains connection socket (see Chapter 3, Technical specifications). 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-31 VIFB1 – 02 4. Installation Please see also the example of connection in Fig. 4/23. 24 V supply (electronic components and/or inputs) 24 V supply (outputs) 2 0V 3 1 PE (Protective earth) 4 Fig. 4/22: Pin assignement of operation voltage connection • Example of connection The following diagram shows the connection of the 24 V supply. The outputs are supplied by an EMERGENCY OFF circuit. Pins 24 V ± 10% 0V EMERGENCY OFF > Res < t n e cum 1 24 V supply of electronic components and/or inputs o D d tore 2 24 V supply outputs 3 0V 4 PE (Protective earth) Fig. 4/23: Example – connection of the 24V supply 4-32 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Current consumption of electronics (field bus node and inputs) (pin 1, 24 V ± 25 %) VIFB-/IIFB-02-1/x-4 VIFB-/IIFB-02-1/x-6 VIFB-/IIFB-02-1/x-8 VIFB-/IIFB-02-1/x-10 0.200 A VIFB-/IIFB-02-1/x-12 VIFB-/IIFB-02-1/x-14 Number of sensor inputs assigned simultaneously: + ∑ A Sensor supply: _____x____ A (see manufacturer specifications) + ∑ A Current consumption of electronics: field bus node and inputs (sensors) max. 4 A < t n e cum _____ x0.010 A = ∑ A + ∑ A Number of relay boards (simultaneously supplied with current): ___ x0.020 A + A Additional output 0 (max. 0.5 A): + A Additional output 1 (max. 0.5 A): + A Current consumption of outputs = ∑ A Current consumption of outputs (pin 2, 24 V ± 10 %) o D d tore Number of valve coils (simultaneously supplied with current): ___ x0.120 A > Res Total current consumption of valve terminal/valve sensor terminal A + ∑ A = ∑ A Fig. 4/24: Calculating the current consumption 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-33 VIFB1 – 02 4. Installation Field bus interface There are two plugs on the field bus node for connecting the valve terminal/valve sensor terminal to the field bus. One of these plugs is intended for the supply line, the other is for the continuing field bus cable. The signal cables of the two plugs are connected together. This enables the field bus to be connected to further field bus slaves. Recommendation: On all valve terminal/valve sensor terminals the top connection should be used for the supply cable. POWER < t n e cum BUS o D d tore Arriving field bus > Res BUS Continuing field bus Fig. 4/25: Connection of the field bus interface 4-34 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Field bus cable A twisted, screened two-core cable should be used as field bus cable. The user should consult the PLC manual of his control system for the type of cable to be used. The distance and the field bus baud rate set should be taken into account. Connecting the field bus interface CAUTION Please observe the polarity when the field bus cables are connected. The following diagram shows the pin assignment of the field bus interface. The field bus cables should be connected to the sensor cable socket or to the bus cable socket. Please note the connection instructions in Fig. 4/27 and Fig. 4/28. > Res < t n e cum o D d tore 3 2 S– free Screening S+ 4 1 BUS 3 2 S– free Screening S+ 4 1 Fig. 4/26: Pin assignment of field bus interface 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-35 VIFB1 – 02 4. Installation • Connection instructions PLEASE NOTE The connection assignments on the field bus modules should always be checked in the PLC manual of the control system. Connect the field bus cable of the control system to the field bus interface of the valve terminal/valve sensor terminal as follows: Manufacturer Field bus module: Plug/terminal assignment Field bus cable Festo Field bus module E.CFA Festo field bus Valve terminal/ valve sensor terminal Pin assignment Field bus interface 1+ Line 1 1– < t n e cum 2+ Line 2 2– 3+ o D d re o t s e >R Line 3 KlöcknerMoeller 3– Serial bus interface Pins 1 (S+) 3 (S –) 4 (screening) Suconet With 5-pin DIN plug (DIN 41512) Pins Pins 4 (TA/RA) 1 (S+) 1 (TB/RB) 3 (S –) Housing 4 (screening) Check assignment in PLC manual Fig. 4/27: Connection instructions 4-36 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Manufacturer Field bus module: Plug/terminal assignment Field bus cable KlöcknerMoeller Serial bus interface Suconet Valve terminal/ valve sensor terminal Pin assignment With 9-pin sub-miniature D-plug (DIN 41652/ ISO 4902) Pins Pins 3 (TA/RA) 1 (S+) 7 (TB/RB) 3 (S –) 4 4 (screening) Check assignment in PLC manual Siemens Module 308-3U Line 1 S SS S- < t n e cum o D d tore Line 2 > Res ET100 Pins 1 (S+) 3 (S –) Check assignment in PLC manual Fig. 4/28: Connection instructions (cont.) 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-37 VIFB1 – 02 4. Installation Fitting the terminating resistor CAUTION If a terminating resistor is used, one of the field bus plugs on the last valve terminal/valve sensor terminal of a field bus line is not assigned. Protection in accordance with protection class IP65 as per DIN 40050 is therefore no longer guaranteed. For this reason a protective cap must be fitted to the nonused field bus plug. If the valve terminal/valve sensor terminal to be connected is at the end of a field bus line, a terminating resistor (120 Ω/0.25 W) must be fitted into the socket of the incoming field bus line (adaption). The non-assigned field bus plug must then be covered with a protective cap. > Res 4-38 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Proceed as follows: 1. Connect the wires of the resistor together with those of the incoming field bus cable between the cores S+ (pin 1) and S- (pin 3) of the sensor/bus cable socket (see following diagram). To guarantee more reliable contact, we recommend that the wires of the resistor and those of the incoming field bus cable be crimped together in common cable end sleeves. 3 2 12 0Ω < t n e cum 4 1 o D d tore Fig. 4/29: Installing the terminating resistor, when valve terminal/ valve sensor terminal is at end of line > Res 2. Fit the sensor/bus cable socket onto one of the field bus plugs on the field bus node. 3. Cover the non-used field bus plug with a protective cap. 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-39 VIFB1 – 02 4. Installation Outputs and valve locations The outputs of the valves correspond to the valve solenoid coils. They can only be used in the form intended. In general, the following applies: • not short-circuit protected • two outputs per valve location • with unilaterally-operated valves the output with the even bit number is used. The other output cannot be used for other purposes. > Res 4-40 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Additional outputs There are two additional outputs (O0.00 and O0.01) on the valve-sensor coupling unit of the valve sensor terminal. These additional outputs are transistor outputs with positive logic (PNP outputs). PNP outputs (0.5 A/24 V) O0.00 O0.01 POWER BUS > Res < t n e cum o D d tore Fig. 4/30: Additional outputs on valve sensor terminal 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-41 VIFB1 – 02 4. Installation Connection assignment of additional outputs free free 1 2 4 3 O0.00 0V O0.00 O0.01 free free 1 2 4 3 < t n e cum O0.01 > Res 4-42 0V o D d tore Fig. 4/31: Connection assignments for additional outputs > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Inputs There are two inputs for each valve location on the valve-sensor coupling unit of the valve sensor terminal. There are two further inputs above the field bus node. The inputs have positive logic (PNP inputs). PNP inputs Common fuse for operating voltage supply to sensors (4 A, slow blowing) > Res I0.00 I0.02 I0.04 I0.06 I0.08 I0.01 I0.03 I0.05 I0.07 I0.09 < t n e cum o D d tore Fig. 4/32: Inputs on the valve sensor terminal 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-43 VIFB1 – 02 4. Installation Connection assignment of inputs The following diagram shows the connection assignment of all the inputs in socket form, using inputs I0.00 and I0.01 as examples. Input sockets Connect. assignment of sockets Explanation Bridge between pin 2 and 4 24 V (fused) Upper row Internal connection of pins I 0.00 1 2 4 3 I 0.00 1 2 4 3 0V I 0.00 < t n e cum I 0.01 24 V (fused) 1 > Res Lower row 4 o D d tore I 0.01 I 0.00 2 3 1 2 4 3 0V Bridge between pin 4, 2 (socket upper row) and pin 2 (socket lower row) Advantage: Two inputs on lower socket (here I0.00 and I0.01), Thereby - fewer cables, - connection to changeover switch or converter possible. Please note: If the lower socket is used for two input cables, the upper plug must remain unused (see example 2). Fig. 4/33: Connection assignment of inputs 4-44 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 4. Installation Circuitry Recommendation: If sensors are required in a valve-cylinder combination, e.g. for interrogating limit switches, the inputs above the relevant valve should be used (clearer overview of the system). Examples: Valve-cylinder combination with interrogation of limit switches by means of sensors. • Example 1 Connecting two sensors with two plugs/ sockets. Sensor 1 (I0.08) < t n e cum Sensor 2 (I0.09) > Res o D d tore S 2 S 1 Fig. 4/34: Example 1 – connecting sensors, two plugs/sockets 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 4-45 VIFB1 – 02 4. Installation • Example 2 Connecting two sensors with one plugs/socket (plug/socket on lower row). Sensor 1 Pin 1 24 V Pin 3 0V Pin 4 I0.08 Sensor 2 Pin 1 24 V Pin 3 0V Pin 4 I0.09 Pin 12 43 Input plug I0.09 Pin 1 24 V Pin 2 I0.08 Pin 3 0V Pin 4 I0.09 Pin 1 4 3 Sensor 1 I0.08 Pin 1 4 3 Sensor 2 I0.09 Must remain unused < t n e cum 2-fold distributor* Sensor 1 and 2 > Res * o D d tore Sensor 2 S 2 S Sensor 1 1 Reference source: e.g. Karl Lumberg GmbH & Co, Postfach 1360, 5885 Schalksmühle Fig. 4/35: Example 2 – connecting sensors, one plug/socket 4-46 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 5. Commissioning 5. COMMISSIONING > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-1 VIFB1 - 02 5. Commissioning Contents COMMISSIONING. . . . . . . . . . . . . . . . . . . . . 5-3 Configuring the PLC . . . . . . . . . . . . . . . . . . Festo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Klöckner-Moeller . . . . . . . . . . . . . . . . . . . . . . Siemens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3 5-4 5-5 5-5 Switching on the operating voltage . . . . . 5-8 Addressing the inputs and outputs. . . . . . 5-9 Valve terminal . . . . . . . . . . . . . . . . . . . . . . . . 5-9 Valve locations . . . . . . . . . . . . . . . . . . . . . 5-9 Valve sensor terminal . . . . . . . . . . . . . . . . . 5-11 Valve locations, inputs and additional outputs . . . . . . . . . . . . . . . . . . 5-11 Status bits . . . . . . . . . . . . . . . . . . . . . . . . 5-14 Manufacturer-specific features . . . . . . . . . . 5-15 Festo . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15 Klöckner-Moeller . . . . . . . . . . . . . . . . . . . 5-16 Siemens . . . . . . . . . . . . . . . . . . . . . . . . . 5-20 > Res 5-2 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 5. Commissioning COMMISSIONING Configuring the PLC Before commissioning or programming, the user should compile a configuration list for the connected field bus slaves. On the basis of this list: • a comparison can be made between ACTUAL and NOMINAL configurations in order that incorrect connections can be avoided; • access can be made to specifications during a syntax check of a program in order that addressing errors can be avoided. > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-3 VIFB1 - 02 5. Commissioning Festo The field bus configurator in the FST software offers support in compiling the NOMINAL configuration. Menu control and operation of the software are described in the corresponding FST manual for the control system. The system should be configured as follows: • Enter the field bus address of the field bus slave (valve terminal/valve sensor terminal). • Enter the line number. • Select and enter the type of valve terminal/valve sensor terminal from the field bus type file. When the type is selected, the number of necessary input/output words (IW/OW) to be addressed is automatically assigned. Menu: FST 405 field bus configuration < t n e cum [ Insert [Esc] PA. > Res Line Type o D d tore Field bus address Number of field bus of valve terminal/ line to which valve sensor terminal terminal is connected. Valve * Valve Valve Valve IW OW Type of field bus slave (Type must be selected from field bus type file). (Type–selection) terminal 01 up to terminal 01 over terminal 02 up to terminal 02 over * Valve sensor terminal up to Valve sensor terminal over Decentralized I/Os I/O extension 405 Servodriver HPM3000 8 8 8 8 valves valves valves valves 6 valves 6 valves Fig. 5/1: Example – Configuring with the FST 405 5-4 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 5. Commissioning Klöckner-Moeller If the valve terminal/valve sensor terminal is used in the SUCONET, the following must be observed: • Configuration The valve terminal/valve sensor terminal reacts just like the PS3 controller when used with the SUCONET and must be configured accordingly. • The valve terminal only evaluates the output information. • The valve sensor terminal evaluates both output and input information. • A field bus slave is first initialized when it is accessed by the program. Then the BUS-LED goes out. • Use only the following ID words: - valve terminal without inputs: 80D4 - valve terminal with inputs: 80D8 < t n e cum Further details on the configuration are to be found in the PLC manual of the PLC control system. > Res o D d tore Siemens If the valve terminal/valve sensor terminal is used in the ET100 bus, the following must be observed: PLEASE NOTE Valve terminal/valve sensor terminals have no periphery bus. the periphery bus transmission time is therefore zero (( Tc + ∆tc) =0). • Calculating the total transmission time Please see the PLC manual of the control system for the calculation of the total transmission time (tt max). 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-5 VIFB1 - 02 5. Commissioning • Recommendation: Select a field bus address for the valve terminal/valve sensor terminal in the P-area (in spite of the oppposite recommendation in the Siemens manual). In this way, the inputs/outputs can be addressed bit by bit. • Configure the valve terminal/valve sensor terminals as analogue units. • Use only even-number start addresses (AQ/AI addresses). The configuration specifications depend on the size of the valve terminal/valve sensor terminal used and are shown in the diagram below. Field bus participant Configuration Meaning Valve terminal • up to 8 valve locations 1AA • more than 8 valve locations 2AA o t s e >R (2 bytes) < t n e um Module with 2 channels "Analogue outputs" c o D red Valve sensor terminal • up to 6 valve locations • more than 6 valve locations Module with 1 channel "Analogue outputs" (4 bytes) 1AX Module each with 1 channel "Analogue outputs" (2 bytes) and "Analogue inputs" (2 bytes) 2AX Module each with 2 channels "Analogue outputs" (4 bytes) and "Analogue inputs" (4 bytes) Fig. 5/2: Configuration of ET100U With the ET100U, addresses are assigned and entered with the communication software COM ET100. The following specifications must be made in the mask "ET100 ADDRESS CODING" when the valve terminal/valve sensor terminal is used: 5-6 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 5. Commissioning Example: Configuring a valve sensor terminal with 10 valve locations. Field bus address (ET100 no.): Range: AQ address: AI address: Configuration: 23 P 30 20 2AX **************************************************************************************** * SIMATIC S5 / ET100-AS * * ET100-ADDRESS CODING PROGRAM NAME: $$$$$$$$ * * * * ET100-No.: number selected on AS 318-8M End * 23 * Area: (P, Q, IM3, IM4) address: * P * DQ-address: ### Start address for digital outputs $$$ * * DI-address: ### Start address for digital inputs $$$ * * AQ-address: 30 Start address for analogue outputs $$$ * * AI-address: Start address for analogue inputs $$$ * 20 * Configuring: * * 0. 1. 2. 3. 4. 5. 6. 7. * * 2AX ### ### ### ### ### ### ### * * * * 8. 9. 10. 11. 12. 13. 14. 15. * * ### ### ### ### ### ### ### ### * * * * 16. 17. 18. 19. 20. 21. 22. 23. * * ### ### ### ### ### ### ### ### * * * * 24. 25. 26. 27. 28. 29. 30. 31. * * ### ### ### ### ### ### ## ### * * * F2 F3 F4 F5 F6 F7 F8 * * F1 * SELECION * PRESCROLL SCROLL FURTHER SAVE ALLOCATE UP DOWN FUNCTION HELP EXIT * * ET100 NO. *************************************************************************************** * Menu line 1 > Res < t n e cum o D d tore *************************************************************************************** * Fig. 5/3: Example – Configuring with mask ET100 ADDRESS CODING 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-7 VIFB1 – 02 5. Commissioning > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-8 VIFB1 – 02 5. Commissioning Switching on the operating voltage PLEASE NOTE Please observe also the switching-on instructions in the PLC manual of the control system. When the controller is switched on, a comparison is automatically made between the ACTUAL and NOMINAL configurations. For this configuration run it is important that the current supply to the PLC and that to the connected field bus participants must be switched on either simultaneously or in the correct sequence. • Common supply: If the control system and the valve terminal/valve sensor terminal are supplied with a common current, they should be switched on with a common central switch. > Res 5-8 < t n e cum • Separate supply: If the control system and the valve terminal/valve sensor terminal are supplied separately with current, the following sequence should be adhered to when the system is switched on: o D d tore 1. Switch on the operating voltage of the valve terminal/valve sensor terminal. 2. Switch on the operating voltage of the control system. > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 5. Commissioning Addressing the inputs/outputs Valve terminal The outputs (valve locations) are addressed with one or two output words depending on the size of the valve terminal. Valve terminal type 02 Output words to be addressed up to 8 valve locations 1 more than 8 valve locations 2 more than 8 valve locations 2 Fig. 5/4: Number of output words to be addressed Valve locations < t n e cum Each valve location has two outputs. The designation of these outputs is noted on the valve terminal and is composed as follows: > Res o D d tore Designation for Output O 1 . 05 Bit no. in output word Output word no. Output Fig. 5/5: Composition of designation for output word 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-9 VIFB1 – 02 5. Commissioning The assignment of the outputs to the relevant valve location is shown in the following diagram: Outputs of valve locations 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 1.00 1.02 BUS Valve locations 1 ... 10 0.01 0.03 0.05 0.07 0.09 0.11 < t n e um 0.13 c o D red o t s e >R Outputs of valve locations 0.15 1.01 1.03 Fig. 5/6: Outputs of the valve locations Example: Addressing and activating valves Valve Valve type location 3 Unilaterally operated 10 Bilaterally operated Output O0.04 O0.05 Bit contents 1 X O1.02 O1.03 0 1 Remarks Valve solenoid coil active Output is not evaluated, Bit contents without meaning Upper valve solenoid coil not active Lower valve solenoid coil active Fig. 5/7: Example - Addressing and activating valves 5-10 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 5. Commissioning Valve sensor terminal The outputs (valve locations and additional outputs) are addressed with one or two output words according to the size of the valve sensor terminal. The inputs are addressed correspondingly with one or two input words. Valve sensor terminal type 02 Output words to be addressed Input words to be addressed Up to 6 valve locations 1 1 More than 6 valve locations 2 2 Fig. 5/8: Number of input/output words to be addressed Valve locations, inputs and additional outputs > Res < t n e cum Each valve location has one or two outputs. Two additional inputs/outputs are arranged above the field bus node. The designation of the inputs/outputs is noted on the valve sensor terminal and is composed as follows: o D d tore Designation for Input or Output O 0 . 03 I 1 . 05 Bit no. in input/output word Input/output word no. Input/output Fig. 5/9: Composition of designation for inputs/outputs 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-11 VIFB1 – 02 5. Commissioning The assignment of the inputs/outputs to the relevant valve location or additional input/output is shown in the following diagram: Additional outputs above the field bus node (O0.00 and O0.01) Inputs above the valve locations (I0.02...I1.05) Additional inputs above the field bus node (I0.00 and I0.01) 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 1.00 1.02 1.04 0.01 0.01 0.03 0.05 0.07 0.09 0.11 0.13 0.15 1.01 1.03 1.05 0.02 0.04 0.06 0.08 0.10 0.12 0.14 1.00 1.02 1.04 BUS < t n e cum o D d tore Valve locations 1 ... 10 > Res 0.03 0.05 0.07 0.09 0.11 0.13 0.15 1.01 1.03 1.05 Outputs of valve locations (O0.02...O1.05) Fig. 5/10: Inputs/outputs of valve locations and additional inputs/outputs of a valve sensor terminal 5-12 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 5. Commissioning Example 1: Addressing and activating valves and additional outputs (SA0 and SA1). Valve location Valve type Designation 3 Unilaterlally operated O0.06 1 Valve solenoid active O0.07 X Output is not evaluated, Bit contents without meaning Bilaterally operated O1.04 0 Upper valve solenoid not active O1.05 1 Lower valve solenoid coil active SA0 O0.00 0 Additional output not active SA1 O0.01 1 Additional output active (DC 24V) 10 Bit contents Remarks Additional outputs Fig. 5/11: Example 1 – Addressing and activating valves and additional < t n e cum Example 2: Addressing and reading inputs. Input o D d e Designation Loaded bit contents Inputs Valve location 3 I0.06 1 Signal present I0.07 0 Signal not present Inputs Valve location 10 I1.04 0 Signal not present I1.05 1 Signal present > r o t s Re Remarks Fig. 5/12: Example 2 - Addressing and reading inputs 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-13 VIFB1 – 02 5. Commissioning Status bits The valve sensor terminal makes available two status bits and a diagnostic byte for error diagnosis. The two status bits can be read with the first or second input word depending on the size of the valve sensor terminal. Accordingly the status bits have the following designations: Valve sensor terminal type 02 Designation Up to 6 valve locations I0.14 I0.15 More than 6 valve locations I1.14 I1.15 Fig. 5/13: Designation of status bits Example: Addressing and reading status bits. Status bits Up to 6 valve locations > Res More than 6 valve locations < t n e cum o D d tore Designation I0.14 I0.15 I1.14 I1.15 Loaded bit contents 0 or 1 Remarks Meaning see Chapter 6 Fig. 5/14: Example – Addressing and reading status bits 5-14 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 5. Commissioning Manufacturer-specific features Festo Example: Addressing the inputs/outputs of a valve sensor terminal with more than 6 valve locations. Processor system address E.CFA: Field bus address of the terminal: 4 16 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 1.00 1.02 1.04 0.01 0.01 0.03 0.05 0.07 0.09 0.11 0.13 0.15 1.01 1.03 1.05 0.02 0.04 0.06 0.08 0.10 0.12 1.00 1.02 1.04 0.14 BUS > Res < t n e cum o D d tore 0.03 0.05 0.07 0.09 0.11 0.13 0.15 1.01 1.03 1.05 Program: IF THEN SET I416.0.3 O416.0.4 "Input "Output I0.03 O0.04 (2nd. valve, upper coil) IF THEN I416.1.1 O416.1.5 "Input "Output I1.01 O1.05 (10th. valve, lower coil) SET Fig. 5/15: Example – Addressing a valve sensor terminal with more than 6 valve locations Further details on addressing and programming are to be found in the PLC manual of the control system (e.g. Festo system manual FPC 405, Chapter 7). 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-15 VIFB1 - 02 5. Commissioning Klöckner-Moeller When the inputs/outputs of a valve terminal/valve sensor terminal are addressed, the following must be observed: Field bus participant Addressing on the SUCONET Valve terminal • Up to 8 valve locations 1 word outputs (standard 16 bits) • More than 8 valve locations Long protocol: 1 word outputs (standard 16 bits) + additional functions Valve sensor terminal • Up to 6 valve locations 1 word outputs (standard 16 bits) 1 word inputs (standard 16 bits) • More than 6 valve locations Long protocol: 1 word outputs (standard 16 bits) + additional functions 1 word inputs (standard 16 bits) + additional functions Fig. 5/16: Addressing possibilities on the SUCONET > Res < t n e cum The valve terminal/valve sensor terminal simulates the additional functions ("Analogue output/input" and "Fast counter") of a PS3. The following bytes can therefore also be addressed: o D d tore Additional functions of PS3, simulated by valve terminal/ valve sensor terminal Byte size • • • • 8 8 8 8 Analogue output Fast counter (low byte) Fast counter (high byte) 4 analogue inputs bits bits bits bits each Fig. 5/17: Simulated additional functions Depending on the master used, the following special features must also be observed: 5-16 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 5. Commissioning • PS3 as master If a PS3 is the master, up to three valve terminal/valve sensor terminals can be connected. The following unit numbers must be assigned to the possible field bus addresses 2, 3 and 4 of the valve terminal/valve sensor terminals: Field bus address set on valve terminal/valve sensor terminal Number of unit 2 3 4 1 2 3 Fig. 5/18: Assignment of units When configuration is complete, the valve terminal/valve sensor terminals should be addressed as follows: Outputs of valve terminal/ valve sensor terminal PS3 operand O O O O QB x.0 (low byte) QB x.8 (high byte) QA x.0 C nominal (low byte) 0.00 0.08 1.00 1.08 ... ... ... ... O O O O 0.07 0.15 1.07 1.15 > Res x = Number of unit Function o D d tore < t n e cum 1st. output byte 2nd. output byte Analogue output System module "Fast counter" Fig. 5/19: Addressing outputs Inputs of valve sensor terminal PS3 operand Function I 0.00 ... I 0.07 I 0.08 ... I 0.15 I 1.00 ... I 1.07 I 1.08 ... I 1.15 Valve sensor terminal diagnostic byte IB IB IA IA IA 1st. 2nd. 1st. 2nd. 3rd. (see x.0 (low byte) x.8 (high byte) x.0 x.1 x.2 Input byte Input byte Analogue input Analogue input Analogue input also Chapter 6) x = Number of unit Fig. 5/20: Addressing inputs and valve sensor terminal diagnostic bytes 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-17 VIFB1 - 02 5. Commissioning Examples: • Example 1: Addressing the outputs O1.00 ... O1.05 of a valve terminal with the additional function "Analogue output". The outputs also addressed O1.06 and O1.07 are without meaning. Addressing the outputs: O1.00...O1.07 Field bus address: 2 Program: L IB0.0 = QA1.0 "Info from 1st. input byte of PS3 "Transfer to outputs O1.00...O1.07. • Example 2: Addressing the inputs I1.00 ... 1.05 as well as status bits I1.14 and I1.15 of a valve sensor terminal with the additional functions "1st. and 2nd. analogue input". The inputs also addressed I1.06 ... I1.13 are without meaning. > Res 5-18 < t n e cum o D d tore Addressing the inputs: Field bus address: Program: L IA3.0 = QB0.0 L IA3.1 = QB0.8 I1.00...I1.15 4 "Info from inputs I1.00...I1.07 "Transfer to output byte of PS3. "Info from inputs I1.08...I1.15 "Transfer to 2nd. output byte of PS3. > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 5. Commissioning • Other masters (e.g. PS316, PS32, EPC334) The valve terminal/valve sensor terminal should be addressed as with a PS3. Example Addressing the inputs/outputs of a valve sensor terminal and loading the valve sensor terminal diagnostic bytes. Master: Physical SBI address: Logical SBI address: Field bus address: PS316 192 SBI0 2 Program: 1 "Inputs of PS 316 to outputs of terminal: 2 " 3 L IB 0.0 4 = PP 192 B8.0 "Outputs O 0.00...O 0.07 5 L IB 0.8 6 = PP 192 B8.8 "Outputs O 0.08...O 0.15 7 L IB 1.0 8 = PP 192 B9.0 "Outputs O 1.00...O 1.07 9 L IB 1.8 10 = PP 192 B11.0 "Outputs O 1.08...O 1.15 11 " 12 "If available, inputs of terminal to outputs of PS 316: 13 " 14 L PP 192 B0.0 "Inputs I 0.00...I 0.07 15 = QB 0.0 16 L PP 192 B0.8 "Inputs I 0.08...I 0.15 17 = QB 0.8 18 L PP 192 B1.0 "Inputs I 1.00...I 1.07 19 = QB 1.0 20 L PP 192 B2.0 "Inputs I 1.08...I 1.15 21 = QB 1.8 22 " 23 "Load valve sensor terminal diagnostic byte into a flag byte. 24 " 25 L PP 192 B3.0 "Valve sensor terminal diagnostic byte 26 = MB 10.0 27 " > Res < t n e cum o D d tore Further details on addressing and programming are to be found in the PLC manual of the control system. 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-19 VIFB1 - 02 5. Commissioning Siemens Further details on addressing and programming are to be found in the PLC manual of the control system. • Example 1: Addressing the outputs of a valve terminal with up to 8 valve locations. ET100 no.: 20 AQ address: 40 Configuration: 1AA 0.00 0.02 0.04 0.06 0.08 0.01 0.03 0.05 0.07 0.09 0.10 0.12 0.14 BUS < t n e cum 0.11 0.13 0.15 **************************************************************************************** * SIMATIC S5 / ET100-AS * * ET100-ADDRESS CODING PROGRAM NAME: $$$$$$$$ * * * 20 * ET100-No.: number selected on AS 318-8M End * P * Area: (P, O, IM3, IM4) address: * * DQ-address: ### Start address for digital outputs $$$ * * DI-address: ### Start address for digital inputs $$$ * * AO-address: 40 Start address for analogue outputs $$$ * * AI-address: ### Start address for analogue inputs $$$ * * Configuring: * * 0. 1. 2. 3. 4. 5. 6 7. * * 1AA ### ### ### ### ### ### ### * *************************************************************************************** * > Res o D d tore Program: : :U I3.4 := O40.4 "Output O0.04 (3rd. valve, upper coil) := O41.7 "Output O0.15 (8th. valve, lower coil) := Fig. 5/21: Example 1 – Addressing a valve terminal with up to 8 valve locations 5-20 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 5. Commissioning • Example 2: Addressing the outputs of a valve terminal with more than 8 valve locations. ET100 no.: 21 AQ address: 50 Configuration: 2AA 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 1.00 1.02 0.01 0.03 0.05 0.07 0.09 0.11 0.13 0.15 1.01 1.03 BUS **************************************************************************************** * SIMATIC S5 / ET100-AS * * ET100-ADDRESS CODING PROGRAM NAME: $$$$$$$$ * * * 21 * ET100-No.: number selected on AS 318-8M End * P * Area: (P, O, IM3, IM4) address: * * DQ-address: ### Start address for digital outputs $$$ * * DI-address: ### Start address for digital inputs $$$ * * AO-address: 50 Start address for analogue outputs $$$ * * AI-address: ### Start address for analogue inputs $$$ * * Configuring: * * 0. 1. 2. 3. 4. 5. 6 7. * * 2AA ### ### ### ### ### ### ### * *************************************************************************************** * > Res < t n e cum o D d tore Program: : :U I3.4 := O50.4 "OutputO0.04 ( 3rd. valve, upper coil) := O51.7 "OutputO0.15 ( 8th. valve, lower coil) := O52.2 "OutputO1.02 (10th. valve, upper coil) Fig. 5/22: Example 2 – Addressing a valve terminal with more than 8 valve locations 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-21 VIFB1 - 02 5. Commissioning • Example 3: Addressing the inputs/outputs of a valve sensor terminal with up to 6 valve locations. ET100 no.: 22 AQ address: 60 AI address: 70 Configuration: 1AX 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.01 0.01 1.03 0.05 0.07 0.09 0.11 0.13 0.02 0.04 0.06 0.08 0.10 0.12 0.03 0.05 0.07 BUS < t n e cum 0.09 0.11 0.13 **************************************************************************************** * SIMATIC S5 / ET100-AS * * ET100-ADDRESS CODING PROGRAM NAME: $$$$$$$$ * * * 22 * ET100-No.: number selected on AS 318-8M End * P * Area: (P, O, IM3, IM4) address: * * DQ-address: ### Start address for digital outputs $$$ * * DI-address: ### Start address for digital inputs $$$ * * AO-address: 60 Start address for analogue outputs $$$ * 70 * AI-address: Start address for analogue inputs $$$ * * Configuring: * * 0. 1. 2. 3. 4. 5. 6 7. * * 1AX ### ### ### ### ### ### ### * *************************************************************************************** * > Res Program: : :U I70.4 := O60.0 := O60.6 := O61.5 o D d tore "Input I0.04 "Additional output O0.00 "Output O0.06 "Output O0.13 (3rd. valve, upper coil) (6th. valve, lower coil) Fig. 5/23: Example 3 – Addressing a valve sensor terminal with up to 6 valve locations 5-22 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 5. Commissioning • Example 4: Addressing the inputs/outputs of a valve sensor terminal with more than 6 valve locations. ET100 no.: 23 AQ address: 80 AI address: 90 Configuration: 2AX 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 1.00 1.02 1.04 0.01 0.01 0.03 0.05 0.07 0.09 0.11 0.13 0.15 1.01 1.03 1.05 0.02 0.04 0.06 0.08 0.10 0.12 0.14 1.00 1.02 1.04 0.03 0.05 0.07 0.09 0.11 0.13 BUS < t n e cum 0.15 1.01 1.03 1.05 **************************************************************************************** * SIMATIC S5 / ET100-AS * * ET100-ADDRESS CODING PROGRAM NAME: $$$$$$$$ * * * 23 * * ET100-No.: number selected on AS 318-8M End P * Area: (P, O, IM3, IM4) address: * * DQ-address: ### Start address for digital outputs $$$ * * DI-address: ### Start address for digital inputs $$$ * * AO-address: 80 Start address for analogue outputs $$$ * 90 * AI-address: Start address for analogue inputs $$$ * * Configuring: * * 0. 1. 2. 3. 4. 5. 6 7. * * 2AX ### ### ### ### ### ### ### * ***************************************************************************************** > Res Program: : :U I92.3 := O80.1 := O80.6 := O85.5 o D d tore "Input I1.03 "Additional output O0.01 "Output O0.06 "Output O1.05 ( 3rd. valve, upper coil) (10th. valve, lower coil) Fig. 5/24: Example 4 – Addressing a valve sensor terminal with more than 6 valve locations 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 5-23 VIFB1 - 02 5. Commissioning Commissioning tips 1. Insert module IM 308-B into the correct location on your automation device. 2. Please observe any limits in the number of digital inputs/outputs, e.g. CPU 941, max. 512. 3. Please note that the station number set does not correspond to the configured I/O address. 4. For the configuration (e.g. 1AA, 2AA, 1AX, 2AX) the number of valve locations is decisive, not the number of valves on the terminal. 5. Please make sure with the configuration that the I/O addresses of automation device components do not have the same addresses as the configured I/Os of the field bus. < t n e cum 6. Also make sure that the field bus I/O addresses are not the same as the diagnostic addresses. > Res 5-24 o D d tore 7. Connect the terminating resistor to both ends of the field bus (to the field bus connecting plug of the IM 308-B and to the last field bus slave). > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 6. Diagnostic/error treatment 6. DIAGNOSTIC AND ERROR TREATMENT > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 6-1 VIFB1 - 02 6. Diagnostic/error treatment Contents DIAGNOSTIC AND ERROR TREATMENT LED displays . . . . . . . . . . . . . . . . . . . . . . . . Field bus node. . . . . . . . . . . . . . . . . . . . . . . . Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inputs and additional outputs . . . . . . . . . . . . 6-3 6-4 6-5 6-6 Diagnostic byte . . . . . . . . . . . . . . . . . . . . . . 6-7 Festo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7 Klöckner-Moeller . . . . . . . . . . . . . . . . . . . . . 6-10 Siemens. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11 Testing the valves and additional outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15 Reaction during faults . . . . . . . . . . . . . . . 6-17 Control system. . . . . . . . . . . . . . . . . . . . . . . 6-17 Short circuit/overload at the additional output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18 > Res 6-2 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 6. Diagnostic/error treatment LED displays Field bus node The LEDs on the cover of the field bus node indicate the operating status of the valve terminal/valve sensor terminal. Green LED (operating status display) POWER Red LED (error display) BUS BUS < t n e cum o D d tore Fig. 6/1: LEDs of the field bus node > Res 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 6-3 VIFB1 - 02 6. Diagnostic/error treatment Possible LED displays indicating the operating status of the valve terminal/valve sensor terminal are listed below. LEDs Green Red alight out Operating status Error treatment Operating status normal or, operating status normal but valves do not switch. Possible causes: • Operating voltage of outputs not in tolerance range or not present None Check the... • operating voltage connection of outputs (tolerance range 21.6 V...26.4 V DC) • compressed air supply • Compressed air supply not correct • Pilot exhaust blocked • pilot exhaust channels Green Red out out Operating voltage for electronic components not present. Check operating voltage connection for electronic components. Green Red alight blinking (very quickly) Address and/or baud rate setting not permitted with field bus protocol used. Check address/baud rate setting (see Chapter 4.3) Green Red alight blinking (in 1 sec. pulse) Field bus connection not correct. Possible causes: • Address setting not correct (e.g. address assigned twice) • Baud rate on terminal and field bus module not the same • Field bus protocol setting not correct • Field bus module switched off or defective • Interrupted short-circuited or faulty field bus connection Check the... Hardware error Service case > Res Green Red alight alight o D d tore < t n e cum • address selector switch setting • baud rate setting on terminal and field bus module • field bus protocol setting (see Chapter 4.3) • field bus module • field bus connection Fig. 6/2: LED display – operating status 6-4 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 6. Diagnostic/error treatment Valves There is a yellow LED above or below each valve solenoid coil. This LED indicates the switching status of the valve solenoid coil. POWER BUS Yellow LEDs (switching status display of valve solenoid coil) LED > Res BUS < t n e cum o D d tore Switch position Valve solenoid coil Meaning Yellow out Basic setting Logic 0 (signal not present) Yellow alight • Switch position or • Basic position Logic 1 (signal present) Logic 1 but: • Operating voltage of outputs is outside permitted tolerance range (DC 21.6V...26.4V) or • Compressed air supply not correct or • Pilot exhaust blocked or • Service case Fig. 6/3: LED display – Switching status of valve solenoid coil 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 6-5 VIFB1 - 02 6. Diagnostic/error treatment Inputs and additional outputs There are green or yellow LEDs below or above the input/output connections on the valve-sensor coupling unit of the valve sensor terminal. These LEDs show the signal which is currently at the input or output. Yellow LEDs (Switching status display of additional outputs) < t n e cum POWER BUS > Res Green LEDs (switching status display of inputs) o D d tore LED Status Yellow or green out Yellow or green alight Logic 0 (signal not present) out Logic 1 (signal present) alight Fig. 6/4: LED display – Switching status of the inputs and additional outputs 6-6 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 6. Diagnostic/error treatment Diagnostic byte The diagnostic information on a valve terminal/valve sensor terminal is gathered together in the form of a diagnostic byte (status byte). With this diagnostic byte the following error states can be recognized and the PLC informed accordingly. Diagnostic information (Vval) Vvalve Voutput (Vout) Vinput (Vinp) SA0 SA1 > Res Meaning Cause Monitors the operating voltage of valves and additional outputs Monitors the operating voltage of the valves and additional outputs (no voltage), e.g. EMERGENCY OFF). Monitors the operating voltage of the inputs with valve sensor terminals Monitors additional output O0.00 of valve sensor terminal Monitors additional output O0.01 of valve sensor terminal Operating voltage at pin 2 of operating voltage connection< 21.6 V Operating voltage at pin 2 of operating voltage connection < 10 V E.g. fuse triggered < t n e cum o D d tore Short circuit or overload Short circuit or overload Fig. 6/5: Error status of valve terminal/valve sensor terminal The diagnostic byte is transmitted to the PLC, in accordance with the relevant field bus protocol. Depending on the manufacturer, the following information must be observed. Festo All diagnostic information on the valve terminal/valve sensor terminal can be evaluated with the FPC 405. An error list is then compiled in the field bus module E.CFA. All status bytes are included in this list and continually updated. 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 6-7 VIFB1 - 02 6. Diagnostic/error treatment Protocol form for status byte Bit no. 7 1 0 Diagnostic information None None None, Signal status 0 or 1 Meaning Signal status 0: Signal status 1: 1* * No error Error Cyclic field bus participant * Bit no. L always H: Indicates a cyclic field bus participant Fig. 6/6: Protocol form of status byte The status byte is interrogated with function module 44. The following diagram shows an example using the field bus module E.CFA of the FPC 405: Test system Processor Input format/interrogation or program system address Test system (on-line operation) > Program LDR 2 c o D red 4 FC4.44, <Field bus address> or F54.44, <Field bus address> 2 Define box CFM 52 WITH V44 WITH V <Field bus address> 4 Program STL 2 4 Program BASIC < t n e um FC2.44, <Field bus address> or F52.44, <Field bus address> o t s e R Return parameter Contents are shown directly FU32 CFM 54 WITH V44 WITH V <Field bus address> IF ... THEN IF ... THEN CFM 52 WITH V44 WITH V <Field bus address> FU32 CFM 54 WITH V44 WITH V <Field bus address> 2 CALL FN 52, (44, <Field bus address>) 4 CALL FN 54, (44, <Field bus address>) @Q0 Return parameters are stored in @Q0, see also appropriate FST manual. Fig. 6/7: Example E.CFA – Status interrogation of field bus slave 6-8 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 6. Diagnostic/error treatment Example Interrogation and evaluation of the status byte of a field bus slave (valve terminal/valve sensor terminal). Field bus address: 23 Processor system address: 4 Interrogation: If there is an error in Vinputs (Bit no.4) a branch must be made in the program. Note on solution: By bit-by-bit masking of the return parameter the contents will be evaluated (HEX10 = 0001.0000). Program STL: STEP (1) "Read status byte installation terminal 23 IF THEN CFM 54 WITH V44 WITH V23 STEP IF < t n e cum NOP > Res THEN OTHRW "Function module – call in CZE 4 "CFM 44 in CFA "Address of field bus slave o D d tore (2) ( FU32 AND V$10 ) = V$10 JUMP TO U_error (3) NOP "Bit no. 4 in status byte set? "CFM return parameter "Condition: Bit no. 4 =1 "Jump in subprogram "Error" Program BASIC: CALL FN54 (44, 23) :! IF :! 9604 @Q0 AND $10 THEN . . . Read status byte valve sensor terminal 23 with CFM 44 Condition: Bit no. 4 = 1 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 6-9 VIFB1 - 02 6. Diagnostic/error treatment Klöckner-Moeller The valve terminal/valve sensor terminals react on the SUCONET like a PS3 in slave configuration. The valve terminal/valve sensor terminal therefore transfers its diagnostic byte to the master via the PS3 operand "Analogue output" (3rd. analogue channel). The master receives this diagnostic byte from the SUCONET via the PS3 operand "3rd. analogue input" (5th. input channel). For further information see the following example and the PLC manual of the control system. Example: Load diagnostic byte. Master: Field bus address of terminal: PS3 2 (= unit no. 1) < t n e cum Program: LIA1.2 "Load diagnostic byte of terminal via 5th. input channel to 1st. output byte of PS3 > Res o D d tore Diagnostic information can only be received via this diagnostic byte, not via the remote user status bytes. Protocol form for diagnostic byte: Bit no. 7 1 0 Diagnostic information None None None Signal status L or H Meaning * Signal status L: Signal status H: No error Error H* * Cyclic field bus slave Bit no. 0 always ’1’: Indicates a cyclic field bus participant. Fig. 6/8: Protocol from of diagnostic byte 6-10 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 6. Diagnostic/error treatment Protocol form for remote user status byte: The remote user status bytes (RU_STBs) are set at a fixed value by the valve terminal/valve sensor terminal. The following status messages are always fixed. The meaning and states of the bits, the signal status of which is not listed here, are to be found in the PLC manual. Remote user status byte Bit signal status RU_STB0 Meaning 7 6 5 4 3 2 1 Remote user ERROR: 0 • No hardware error • No output short circuit L L RU_STB1 o D d tore L H H L > Res RU_STB2 < t n e cum 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 H H L H L H L L H H L H H L L L Remote user status: • Passive user • Job executed • Remote user is in RUN status Remote user type: • External device connected Remote user version: • Output (valve terminal) Remote user type: • External device connected Remote user version: • Output/input (valve sensor terminal) Fig. 6/9: RU_STBs Status messages 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 6-11 VIFB1 - 02 6. Diagnostic/error treatment Siemens A diagnostic byte is stored in the field bus module (AS308-3U) for every field bus slave (ET100U). The number of the diagnostic byte thereby corresponds to the field bus address (ET100 no.) of the appropriate field bus slave (valve terminal/valve sensor terminal). Example: Reading the diagnostic byte. Program: L KB n T PY m ’n = ’m = Field bus address (ET100 no.) Address in range 128 ... 255, Recommendation: 254 ’Transfer diagnostic byte to ’Address xx L PY m T MB xx Protocol form for diagnostic byte: Bit no. Bit designation 7 6 5 BASP 0 0 d e r o Rest 4 Doc < t n e um F4 3 2 1 0 F3 F2 F1 F0 Fig. 6/10: Protocol structure of diagnostic byte > 6-12 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 6. Diagnostic/error treatment If the bits marked with BASP, F1 and F0 have signal status 1, the following error messages from the field bus slave (valve terminal/valve sensor terminal) are shown: Bit designation Signal status Meaning F0 1 The valve terminal/valve sensor terminal can no longer be addressed. Possible causes: • No operating voltage • Data cable interrupted • Frequent interference in transmission cable. (Telegrams are repeated 3 times. if no valid data are received, the valve terminal/valve sensor terminal is regarded as no longer addressable). F1 1 Diagnostic information of valve terminal/valve sensor terminal as common display = 1 or Vval = 1 or Vout = 1 or Vinp SA0 = 1 or SA1 = 1 F2 ... F4, 0 BASP < t n e cum No significance with valve terminal/valve sensor terminal 1 0 > Res o D d tore ’Block command output’ ’Block command output’ activated not activated Fig. 6/11: Diagnostic byte status messages 9604 The diagnostic information from the valve terminal/valve sensor terminal is shown as a common display in bit F1. With the valve sensor terminal this common display can be further subdivided amongst the status bits. > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 6-13 VIFB1 - 02 6. Diagnostic/error treatment Status bits of the valve sensor terminal: The status bits of the valve sensor terminal are interrogated by the PLC like "normal inputs". The designation of the status bits and their meaning is shown in the following diagram: Valve sensor terminal type 02 – up to 6 valve locations – Status bit name Bit sequence Valve sensor terminal type 02 – more than 6 valve locations – I0.14 I0.15 I1.14 I.15, 0 0 0 0 No error 1 0 1 0 Vval < 21.6V 0 1 0 1 Vinp < 10V 1 1 1 1 Vout < 10V or SA0: Short circuit at additional output O0.00 or SA1: Short circuit at additional output O0.01 > Res < t n e cum o D d tore Fig. 6/12: Status bits – status messages 6-14 Meaning > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 6. Diagnostic/error treatment Testing the valves and additional outputs WARNING Before the test is started: • Switch off the compressed air supply of the valve terminal/valve sensor terminal. • Disconnect the additional outputs of the valve sensor terminal. • Switch off the operating voltage for the relay boards. The valve terminal/valve sensor terminal offers the following test routines with which all outputs are switched on and off cyclically: Test routine Meaning Parallel All outputs are switched on/off simultaneously in one-second pulses. Serial All outputs are switched on/off one after the other in one-second pulses. < t n e cum o D d tore Fig. 6/13: Test routine > Res 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 6-15 VIFB1 - 02 6. Diagnostic/error treatment Starting the test routine: If errors occur when the test routine is started, the red LED on the field bus node will blink quickly. The process must then be repeated. 1. Switch off the operating voltage supply of the valve terminal/valve sensor terminal. 2. Open the field bus node. 3. Note the positions of the address selector switch and of the DIL switch elements. 4. Set address 99 and set DIL switch elements 1 ... 4 at OFF. 5. Switch on the operating voltage. 6. Set the desired test routine on the address selector switches as follows: Test routine Address to be set < t n e cum Parallel Serial > Res 0, 1 or 2 3 o D d tore 7. Start: set DIL switch elements 1 and 2 at ON. Stopping the test routine: 1. Switch off the operating voltage supply of the valve terminal/valve sensor terminal. 2. Set the address selector switch and the DIL switch elements to their original positions. 6-16 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 6. Diagnostic/error treatment Reaction during faults Control system PLC manufacturer in the field bus Festo or Siemens Reaction of PLC during faults in the control system During faults in the Festo field bus or ET100 bus (e.g. by failure of field bus signal or interruption in field bus cable) all outputs (valves and additional outputs) are switched off after a specified time delay. The time delay depends on the field bus baud rate set. Baud rate [kBaud] 31.25 62.5 187.5 375 Time delay [ms] Please note: The solenoid valves return in this case to the basic position. 2000 1000 500 250 < t n e cum Check details in PLC manual During faults in the SUCONET (e.g. by failure of field bus signal or interruption in field bus cable) all outputs (valves and additional outputs) are switched off after a time delay. The time delay depends on the type of the connected SUCONET master. > Res KlöcknerMoeller If the control system switches to STOP, all outputs (valves and additional outputs) on the valve terminal/valve sensor terminal will be switched off. o D d tore SUCONET master time delay [ms] PS3 network: Master PS3 with up to 3 slaves SUCONET network: with up to 30 slaves 80 300 Check details in PLC manual Fig. 6/14: Reaction of control system during faults 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 6-17 VIFB1 - 02 6. Diagnostic/error treatment Overload short circuit/ overload at the additional output If there is a short circuit or overload: • the additional output will be switched off, • SA0 or SA1 of the diagnostic byte will be set at logic 1. In order to activate the output again, the following procedure should be adopted: Step Explanation Eliminate short circuit or overload Set additional output at 0 (RESET) • Manual (on-line operation, test system) • Automatic in PLC program Set additional output at 1 The error bit in the diagnostic byte of the valve sensor terminal is reset at logic 0. Fig. 6/15: Eliminating short circuit/overload < t n e cum If the short circuit has still not been eliminated, the additional output must be switched off again. > Res 6-18 o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 Appendix A INDEX > Res 9604 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < A-1 VIFB1 - 02 Appendix A > Res A-2 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 Appendix A A Additional outputs . . . . . . . . . . . . . . . . . . . . . 4-41 short circuit. . . . . . . . . . . . . . . . . . . . . . . . 6-18 testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15 Address selector switch. . . . . . . . . . . . . . . . . 4-24 Addressing inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . 5-9 manufacturer-specific features. . . . . . . . . 5-15 valve locations . . . . . . . . . . . . . . . . . . . . . . 5-9 valve locations, inputs, additional outputs . . . . . . . . . . . . . . . . . . . 5-11 Auxiliary pilot air . . . . . . . . . . . . . . . . . 3-15, 4-12 B Blind plug. . . . . . . . . . . . . . . . . . . . . . . . 4-7, 4-10 Blind plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8 < t n e cum C > Res 9604 Cable type . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-35 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . 5-1 Common cable connection . . . . . . . . . . . 3-4, 3-6 Compressed air . . . . . . . . . . . . . . . . . . . . . . . . 4-9 Configuration ET100U . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6 FST 405 . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3 valve terminal/valve sensor terminal . . . . 4-23 Connection block . . . . . . . . . . . . . . . 2-4, 3-3, 3-8 connecting . . . . . . . . . . . . . . . . . . . . . . . . . 4-9 preparing . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8 Connection instructions . . . . . . . . . . . . . . . . . 4-36 Connections for additional outputs . . . . . . . . . . . . . . . . . 3-6 for inputs . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 Cover plates . . . . . . . . . . . . . . . . . 3-3, 3-5, 4-10 Current consumption . . . . . . . . . . . . . . . . . . . 4-33 o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < A-3 VIFB1 - 02 Appendix A D Diagnostic and error treatment . . . . . . . . . . . . 6-1 Diagnostic byte . . . . . . . . . . . . . . . . . . . . . . . . 6-7 Diagnostic byte status message . . . . . . . . . . 6-13 Diagnostic interface . . . . . . . . . . . . . . . . . . . . . 2-7 Distance between holes . . . . . . . . . . . . . . . . . 4-4 Dual in-line switch (DIL switch) . . . . . . . . . . . 4-26 E Electronic components installing . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19 Error states . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7 ET100 . . . . . . . . . . . . . . . . . . . . . 4-37, 5-5, 6-12 ET100 no. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25 F > Res A-4 < t n e cum Field bus . . . . . . . . . . . . . . . . . . . . . . . . . 2-8, 3-8 Field bus address setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24 Field bus baud rate . . . . . . . . . . . . . . 4-26 - 4-27 Field bus cable . . . . . . . . . . . . . . . . . . . . . . . 4-35 Field bus configurator . . . . . . . . . . . . . . . . . . . 5-4 Field bus connection . . . . . . . . . . . . . . . . . . . . 2-3 Field bus interface . . . . . . 2-7, 3-4, 3-6, 3-8, 4-34 connecting . . . . . . . . . . . . . . . . . . . . . . . . 4-35 Field bus module . . . . . . . . . . . . . . . . . . . 2-5, 2-7 cyclic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 Field bus node. . . . . . . . . . . . . . . . . . . . . . . . . 3-8 Field bus protocol . . . . . . . . . . . . . . . 4-26 - 4-27 Field bus slave . . . . . . . . . . . . . . . . . . . . . . . . 2-7 Field bus terminal . . . . . . . . . . . . . . . . . . . . . . 3-8 opening and closing . . . . . . . . . . . . . . . . . 4-22 Fitting valve terminal/valve sensor terminal . 4-1, 4-3 o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 Appendix A Flow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 FST manual . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 FST405 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7 Fuse for inputs. . . . . . . . . . . . . . . . . . . . . . . . . 3-6 H Hoses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7 I Input/output words . . . . . . . . . . . . . . . . . . . . . 5-11 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43 Inscription field inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . 3-6 valve location . . . . . . . . . . . . . . . . . . . 3-4, 3-6 valve sensor terminal . . . . . . . . . . . . . . . . . 3-6 valve terminal . . . . . . . . . . . . . . . . . . . . . . . 3-4 Installing electronic components . . . . . . . . . . . . . . . 4-19 pneumatic components . . . . . . . . . . . . . . . 4-5 > Res < t n e cum o D d tore L LED display . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3 Lupolen plug . . . . . . . . . . . . . . . . . . . . . . . . . 4-10 M Machine level. . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Manual override. . . . . . . . . . . . . . . . . . . . . . . 4-13 locking . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17 operating . . . . . . . . . . . . . . . . . . . 4-14 - 4-15 Module AS308-3U . . . . . . . . . . . . 2-5, 4-37, 6-12 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < A-5 VIFB1 - 02 Appendix A O Operating pressure . . . . . . . . . . . . . . . . . . . . . 3-7 Operating status . . . . . . . . . . . . . . . . . . . . . . . 6-3 Operating voltage . . . . . . . . . . . . . . . . . . . . . . 3-7 applying . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31 switching on . . . . . . . . . . . . . . . . . . . . . . . . 5-8 Operating voltage connection . . . . 3-4, 3-6, 4-30 Operation and display elements . . . . . . . 3-4, 3-6 Output word . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9 P > Res A-6 Part number. . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 Pilot exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9 Pneumatic components installing . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 pneumatic spring . . . . . . . . . . . . . . . . . . . 3-17 Pneumatic spring. . . . . . . . . . . . . . . . . . . . . . 3-17 Protection class IP65. . . . . . . . . . . . . . . . . . . 4-38 Protective cap . . . . . . . . . . . . . . . . . . . . . . . . 4-38 Protocol form diagnostic byte . . . . . . . . . . . . . . . . 6-10, 6-12 status byte . . . . . . . . . . . . . . . . . . . . . . . . . 6-8 < t n e cum o D d tore R Rated pressure . . . . . . . . . . . . . . . . . . . . . . . 3-15 Rated width . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15 Reaction during faults . . . . . . . . . . . . . . . . . . 6-17 Relay boards . . . . . . . . . . . . . . . . . . . . . . 3-3, 3-5 Remote user error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11 status . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11 status byte . . . . . . . . . . . . . . . . . . . . . . . . 6-10 type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11 version . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11 Reply telegram . . . . . . . . . . . . . . . . . . . . . . . . 3-8 RS 485. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 - 02 Appendix A S Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8 Serial bus interface . . . . . . . . . . . . . . . . 2-5, 4-37 Solenoid mid-position valve. . 3-3, 3-5, 3-14, 4-12 Solenoid pulse valve . . . . . . . . . . . 3-3, 3-5, 4-11 Solenoid valve . . . . . . . . . . . . . . . . 3-3, 3-5, 4-11 Status bits . . . . . . . . . . . . . . . . . . . . . . 5-14, 6-14 Status byte. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7 evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9 Status interrogation field bus slave . . . . . . . . . . . . . . . . . . . . . . 6-8 Suconet . . . . . . . . . . . . . . . . . . . . 4-36 - 4-37, 5-5 Switching status inputs/additional outputs . . . . . . . . . . . . . . 6-6 valve solenoid coil . . . . . . . . . . . . . . . . . . . 6-5 System structure . . . . . . . . . . . . . . . . . . . 2-1, 2-7 T > Res < t n e cum Technical description. . . . . . . . . . . . . . . . . . . . 3-1 Technical specifications. . . . . . . . . . . . 3-10, 3-15 Terminating resistor fitting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-38 Test routine . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16 Through hole . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3 Tolerance range . . . . . . . . . . . . . . . . . . . . . . 4-31 Total transmission time . . . . . . . . . . . . . . . . . . 5-5 Two-core cable . . . . . . . . . . . . . . . 2-3 - 2-4, 4-35 Type designation . . . . . . . . . . . . . . . . . . . . . . . 3-7 Type of field bus slave . . . . . . . . . . . . . . . . . . 5-4 Type plate . . . . . . . . . . . . . . . . . . . . 3-4, 3-6 - 3-7 o D d tore U User instructions . . . . . . . . . . . . . . . . . . . . . . . 1-1 9604 > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < A-7 VIFB1 - 02 Appendix A V Valve coupling unit . . . . . . . . . . . . . . . . . 3-3, 3-8 Valve locations outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10 Valve terminal/valve sensor terminal configuring . . . . . . . . . . . . . . . . . . . . . . . . 4-23 connecting . . . . . . . . . . . . . . . . . . . . . . . . 4-28 fitting. . . . . . . . . . . . . . . . . . . . . . . . . . 4-1, 4-3 Valve-sensor coupling unit . . . . . . . . . . . . . . . 3-8 Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8 checking the functions . . . . . . . . . . . . . . . 4-13 connecting . . . . . . . . . . . . . . . . . . . . . . . . . 4-9 testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15 W Work air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12 Work line connection . . . . . . . . . . . . . . . . 3-4, 3-6 > Res A-8 < t n e cum o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 < 9604 VIFB1 – 02 • Example 3: Addressing the outputs: O1.08...O1.13 Field bus address: 2 Programming: With the system module "Fast counter". (programmer PRG3 as from 1.6) First the system module "Fast counter". In the following example the contents of MB0.0 are output through the outputs O1.08...O1.13 of the valve/installation terminal. Autoren: Christine Lehner, Eberhard Klotz Program: xxx C_ C0.0 * S:_ C0.0 * IW:_ C0.0 * QW:_ LD M 2.0 = NM 2.0 > Res 1.0 "Set/Reset input M 2.0 "Nominal value input MB 0.0 "Nominal value output MW 1 < t n e cum "Toggle set/reset input "to transfer nominal value o D d tore > IFB1-02_BES_V_018474g1_1996-04N - Restored Document - 2011-12-15 <