Communications Cable Fire Performance Hierarchy Fred Dawson The Chemours Canada Company Mississauga, Ontario, Canada 905-281-4577 · Fred.C.Dawson@Chemours.com Gerald Lee Dorna Belden Inc. Richmond, Indiana 765-994-9963 · Gerald.Dorna@Belden.com Stanley Kaufman, Ph.D. CableSafe, Inc. Dunwoody, Georgia 770-394-4152 · CableSafe@Bellsouth.net The Code has a similar hierarchy for optical fiber cables. It only has three levels since there are no limited use optical fiber cables. Abstract NFPA 70, National Electrical Code® (NEC) permits communications and optical fiber cable substitutions based on a fire performance hierarchy. The principle is that cable types higher in the hierarchy are permitted to substitute for cable types that are lower in the hierarchy. The Canadian Electrical Code (CEC) and the National Building Code of Canada (NBCC) which together specify communications cabling requirements in buildings in Canada also have a similar hierarchy. Figure 1. Communications Cable Fire Performance Hierarchy This paper reviews the fire tests used for listing communications cables and optical fiber cables, and the rationale for the cable substitution hierarchies. New test data are presented which show that FT6 rated cables have superior results as compared to the requirements of the FT4 test, thereby supporting the current hierarchy in the Canadian codes. Keywords: Wire; cable; symposium; fire, smoke; fire test; hierarchy; NFPA; NFPA 70; National Electrical Code; NEC; Canadian Electrical Code; CEC; National Building Code of Canada; NBCC; plenum ; riser; general-purpose; FT6; FT4; 2. NEC Requirements 1. Introduction Fire performance requirements for cables have been in the National Electrical Code since the first edition in 1897; it had a requirement that riser cables not spread fire from floor to floor. However, without a requirement for listing, it is difficult to enforce such a requirement. Listed products are certified by a recognized testing laboratory as meeting a standard. Enforcing authorities, typically electrical inspectors, rely on listings to assure that a product meets code requirements. Figure 1 illustrates the communications cable fire performance hierarchy in the 2017 NEC. Plenum cables are on top of the hierarchy; they are permitted to substitute for riser, general-purpose and limited-use cables. Next down in the hierarchy are riser cables, which are permitted to substitute for general-purpose and limited-use cables. Next down are general-purpose cables, which are permitted to substitute for limited-use cables. Limited-use cables are on the bottom of the hierarchy. The principle is that cable types higher in the hierarchy are permitted to substitute for cable types that are lower in the hierarchy. International Wire & Cable Symposium Plenum cables were the first communications cables to be listed as meeting fire performance requirements. 555 Proceedings of the 66th IWCS Conference cable, not in conduit, outperformed the conventional cable, in conduit, the candidate plenum cable earned a listing as a plenum cable. 2.1 Plenum Cable Listing In an office building, the space between a hung ceiling and the floor above is a very convenient place for installing communications cables. Since this space is commonly used as a return air plenum, there are fire protection concerns that must be addressed. Moving air can drive fire spread and circulate smoke through the building. The first listings of plenum cables were in 1978. Since these listings only addressed the fire properties of communications cables, Underwriters Labs referred to them as “classifications”. UL uses the term “Listed” to indicate a comprehensive safety certification. Figure 2. Cables Installed in a Plenum The fire protection requirements for listing plenum cables are in NFPA 90A-2015, Standard for the Installation of AirConditioning and Ventilating Systems6. It requires that cables shall be listed as having a maximum peak optical density of 0.50 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 1.5 m (5 ft) or less when tested in accordance with NFPA 262, Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces. UL 910 has been withdrawn and replaced by NFPA 262. Figure 3. NFPA 262 Test The National Electrical Code has a long-standing requirement that power cables installed in plenums must be in metal conduit or metallic-sheathed cables be used1. However, there were no requirements for communications cables installed in plenums until the 1975 NEC edition. The 1975 NEC added a new requirement that communications cables installed in plenums be installed just like power cables, but also provided an exception for cables with “inherent fire-resistant and low-smoke producing characteristics2”. The 1975 Code did not provide any guidance as to what a cable with “inherent fire-resistant and low-smoke producing characteristics” was. In order to establish requirements for these yet-to-be named plenum cables, a fire test had to be specified for measuring the flame spread and smoke producing characteristics of cables and then pass/fail requirements had to be established. The development of a test was reported at the 1976 IWCS in a joint paper3 by Bell Labs and Underwriters Labs. The test became UL 910, UL Standard for Safety Test for Flame-Propagation and Smoke-Density Values for electrical and Optical-Fiber Cables Used in Spaces Transporting Environment Air. Use of this test for measuring the flame spread and smoke production of cables installed in a plenum was validated by a series of large-scale fire tests4. Since the National Electrical Code permits cables installed in metal conduit to be a suitable installation method for installations in plenums, risers and general-purpose spaces, and the listing requirements for plenum cables are based upon their equivalency to cables installed in metal conduit, it should be clear that plenum cables should be permitted to be installed wherever cables in metal conduit are permitted to be installed. That clearly puts plenum cables on top of the cable substitution hierarchy. 2.2 Riser Cable Listing In 1980, a joint project between Bell Laboratories and Underwriters Laboratories developed a fire test for listing riser cables7, 8. The riser cable fire test, UL 1666, Standard for Test for Flame Propagation Height of Electrical and Optical-Fiber Cables Installed Vertically in Shafts, simulates a cable installation in a building riser shaft. The cables are ignited by a very large (495,000 Btu/hr) burner. To pass, cables must not propagate flame to the top of the 12-foot-high compartment during a 30-minute test. Establishing a test was the first step in establishing a listing process for plenum cables. The next step was choosing the pass/fail criteria. Since it had been established that cables installed in metal conduit are an acceptable and code-compliant way of installing cables in a plenum, the listing concept was that plenum cable had to perform as well as conventional (non-plenum) cable in metal conduit. Extensive testing of cables in conduits was reported by Underwriters Labs, Bell Labs and E.I. du Pont de Nemours5. Prior to the establishment of pass/fail criteria, a manufacturer seeking the listing of a “plenum” cable had to submit the cable in two versions, a conventional cable and a candidate plenum cable. The flame spread and smoke production of the conventional cable, in conduit, was compared to the flame spread and smoke production of the candidate plenum cable, not in conduit, in the UL 910 test. If the candidate plenum International Wire & Cable Symposium The 1984 NEC required that riser communications cables be listed. It stated, “Communications wires and cables, both metallic conductor and optical fiber types, in a vertical run in a shaft be listed as having fire-resistance characteristics capable of preventing the carrying of fire from floor to floor.” 556 Proceedings of the 66th IWCS Conference The 1984 NEC did not have a provision explicitly permitting plenum cables to substitute for riser cables. Fire performance requirements for top two cables in the hierarchy were established, but there was no hierarchy yet. The Fine Print Note, now called an Informational Note, for plenum cables in the NEC correlates with the mandatory requirements for plenum cable testing in NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems6. The 1987 code referred to the Vertical Tray Fire Test in UL 1581 testing Type CM cables, and the VW-1 requirements in UL 1581 for testing Type CMX cables. The vertical tray test is often referred to as the IEEE 383 fire test. Figure 5. Vertical Tray Flame Test Figure 4. UL 1666 Test Figure 6. VW-1 Flame Test 2.3 Listing of all Communications Cables The 1987 NEC required that “Communications wires and cables in a building shall be listed as being suitable for the purpose9”, thereby expanding the listing requirements beyond “classification, to a complete safety listing. Listing plenum cables “as having adequate fire-resistant and low-smoke producing characteristics” and riser cables “as having fire-resistant characteristics capable as preventing the carrying of fire from floor to floor” was no longer sufficient; the cables now had to also “be listed as being suitable for the purpose”. The 1987 Code also required that plenum and riser cables be marked CMP and CMR respectively. It introduced two new cable types10, Type CM general-purpose communications cables and Type CMX limited-use communications cables. With four different types of communications cables, each with a different level or fire resistance, it was necessary to clarify what fire performance was required of each cable type, and to do so without violating the NEC prohibition on mandatory references to other standards. The cable fire performance fire hierarchy has its origin in the 1987 NEC which explicitly permitted certain cable substitutions. In the section on vertical runs it required riser cable (Type CMR) and states “Type CMP wires and cables listed for use in ducts, plenums, or other air-handling spaces in accordance with Section 800-3(b)(3) shall be permitted to be used to meet the requirements of this section13”. In the section on (general) wiring in buildings it states “Type CMR wires and cables listed for use in vertical runs in accordance with Section 800-3(b)(2) and Type CMP wires and cables listed for use in ducts, plenums, or other air-handling spaces in accordance with Section 800-3(b)(3) shall be permitted to be used to meet the requirements of this section14.” The 1984 Code referred users to the test requirements for plenum cables with a Fine Print Note that stated “One method of defining low-smoke producing materials is by establishing an acceptable value of the smoke produced per the UL 910 test to a maximum peak optical density of 0.5 and a maximum average optical density of 0.15. Similarly, fire-resistant cables may be defined as having a maximum allowable flame travel distance of 5 feet (1.53 m) in the UL 910 test11.” An exception to the use of Type CM for general wiring in buildings covered the use of Type CMX cables14. “Exception No. 3: Listed Type CMX communication wires and cables that are less than 0.25 inch (6.35 mm) in diameter and installed in one- and two-family or multifamily dwellings.” The Fine Print Note in the 1987 Code stated: “One method of defining low-smoke producing wires and cables is by establishing an acceptable value of the smoke produced per the NFPA 262-1985 test to a maximum peak optical density of 0.5 and a maximum average optical density of 0.15. Similarly, fire-resistant wires and cables may be defined as having a maximum allowable flame travel distance of 5 feet (1.53 m) in the NFPA 262-1985 test12.” International Wire & Cable Symposium Until the development of the 1987 NEC, only the two fire scenarios of greatest concern, cables in air handling spaces and in risers, were addressed. There were no requirements for cables run in other building spaces. Proposal 16-15515 for the 1987 NEC 557 Proceedings of the 66th IWCS Conference Figure 7. Vertical Tray Flame Tests stated, “It is permissible under the present code to use polyethylene-jacketed outside plant cable anywhere except the plenum or riser shaft, for example in hung ceilings not used for air handling.” NEC Panel 16 agreed to require that communications cables used in buildings be listed, but not without first debating which test should be used for general-purpose cable, the IEEE383 test or the VW-1 test. The Panel choice of the IEEE 383 test was opposed by comments16 that stated the IEEE 383 test was for “extremely high risk application involving nuclear power generating plant” and recommended VW-1 which was already in use for “low voltage computer cables”. The Panel rejected the comment with the statement “The Panel believes that the requirements of UL VW-1 are not severe enough to meet the Panel’s intent.” An explicit cable substitution table and a cable substitution figure were introduced in the 1990 NEC. 2.4 Optical Fiber Cables As per NBCC requirements, buildings required to be of noncombustible construction must have communications cables rated to FT6 in plenum spaces and FT4 elsewhere in the building. Buildings permitted to be of combustible construction require communications cables with an FT4 rating in the plenum and FT1 elsewhere in the building. Note that the Province of Ontario requires that FT6 rated communications cables must be used in plenums of all buildings regardless of construction type (combustible or noncombustible construction). Article 770, Optical Fiber Cables, was introduced into the 1984 edition of the NEC. The fire performance requirements for optical fiber cables installed in plenums and risers were identical to the requirements for communications cables. The 1987 edition has three levels of fire performance, plenum, riser and general-purpose. Since there are nonconductive (all dielectric) optical fiber cables and conductive optical fiber cables which have a non-current-carrying metallic member, and three levels of fire performance, there are three types of nonconductive optical fiber cables, Types OFNP, OFNR and OFN, and three types of conductive optical fiber cables, Types OFCP, OFCR and OFC. The fire performance hierarchy is the same as the hierarchy for communications cables. The CEC allows the following substitutions to be used as per footnote 21 in Table 19: a) Communications cables, under-carpet communications (CMUC) cables, and cross-connect wires (cables) marked CMP, CMR, CMG, CM, CMX, CMH, FT6, FT4, and FT4/IEEE 1202 have been found to meet the standard criteria for FT1. 3. Canadian Electrical Code Requirements The Canadian Electrical Code (CEC) works in tandem with the National Building Code of Canada (NBCC) to define what fire rating is required for communications cables in different spaces in a building and in fact, the requirements differ depending on whether the building is of combustible or non-combustible construction. The CEC also uses different designations than the NEC for fire test ratings. (b) Communications cables, under-carpet communications (CMUC) cables, and cross-connect wires (cables) marked CMP, CMR, CMG, and FT6 have been found to meet the standard criteria for FT4 and FT4/IEEE 1202. (c) Communications cables, under-carpet communications (CMUC) cables, and cross-connect wires (cables) marked CMP have been found to meet the standard criteria for FT6. The CEC and NBCC use three different fire test (FT) ratings to classify communications cables. The FT6 test is the NFPA 262 test which is a horizontal test. The FT4 or FT4/IEEE 1202 test is a vertical test17, and the FT1 test is also a vertical test, but less severe than the FT4 test. The FT1 test is similar to the VW-1 test. Figure 7 shows the significant differences between the US vertical flame test (on the left of Figure 7) and Canadian FT4 (on the right of Figure 7) vertical flame tests. The FT4 test is more severe because the burner is tilted up 20o, and the maximum char length is less, only 150 cm in the FT4 test versus 244 cm in the US test. 4. Fire Tests Recent research has been done to support the substitution of FT6 rated cables (Types CMP, OFNP & OFCP) where FT4 rated cables (Types CMG, OFNG & OFCG) are required. Three different FT6 (Plenum) rated cable types were tested, 1) Cat 6A UTP, 2) RG-11 Coax, and 3) a Composite Communications/ Optical Fiber. All were subjected to the FT4 test at UL Laboratories18. Figures 8, 9 and 10, show that all three cables passed with a very wide margin. The char on the Cat 6A UTP cable was 53 cm, on the RG-11 Coax char was 51 cm and the char on the Composite Optical Fiber Optic cable was 65 cm. The maximum char length allowed for FT4 is 150 cm. International Wire & Cable Symposium 558 Proceedings of the 66th IWCS Conference Figure 8. CSA FT 4 Vertical Tray Flame Test Results, CAT 6A, Type CMP Cable samples provided by Belden. We thank UL for carrying out the fire tests professionally and quickly. Dr. Kaufman, who is a consultant to CCCA, thanks CCCA for their support. 7. References [1] NFPA 70-2017, National Electrical Code, Section 300.22(C). [2] NFPA 70-1975, National Electrical Code, Section 800-3(d). [3] J. R. Beyreis, J. W. Skjordahl, S. Kaufman, M. M. Yocum, "A Test Method for Measuring and Classifying the Flame Spreading and Smoke Generating Characteristics of Communications Cable," Proceedings of the 25th International Wire and Cable Symposium, 1976, pp. 291-295. [4] S. Kaufman, M. M. Yocum, “The Behaviour of Fire-Resistant Communications Cables in Large-Scale Fire Tests,” Plastics in Telecommunications 11, p. 8-1. Also published in Plastics and Rubber: Materials and Applications, 4, No. 4, Nov. 1979, pp. 149-155. Figure 9. CSA FT 4 Vertical Tray Flame Test Results, RG11 Coaxial Cable, Type CMP Cable [5] S. Kaufman, L. J. Przybyla, E. J. Coffey, M. M. Yocum, J. C. Reed, D. B. Allen, “Low Smoke and Flame Spread Cables,” Proceedings of 28th International Wire and Cable Symposium, 1979, pp. 281-291. Also published in Journal of Fire and Flammability, 12, 1981, pp. 177-199. [6] NFPA 90A-2015, Standard for the Installation of AirConditioning and Ventilating Systems, section 4.3.4.4. [7] S. Kaufman, J. L. Williams, E. E. Smith, L. J. Przybyla, "Large Scale Fire Tests of Building Riser Cables," Proceedings of the Thirty-First International Wire and Cable Symposium, pp. 411-416 and Proceedings of the International Conference on Fire Safety, pp. 105-117, Journal of Fire Sciences, I, January/February 1983, pp. 54-65. Figure 10. CSA FT 4 Vertical Tray Flame Test Results, Composite Communications/ Optical Fiber Cable, Type CMP/OFCP [8] L. J. Przybyla, T. J. Guida, J. L. Williams, S. Kaufman, "Fire Testing of Riser Cables," Proceedings of the 33rd International Wire and Cable Symposium, 1984, pp. 5-13, Proceedings of the International Conference on Fire Safety, 10, 1985, pp. 120-133, Journal of Fire Sciences, 3, 1985, pp. 9-25. [9] NFPA 70-1987, National Electrical Code, Section 800-4. [10] NFPA 70-1987, National Electrical Code, Section 800-3(b). [11] NFPA 70-1984, National Electrical Code, Section 8003(b)(3). [12] NFPA 70-1987, National Electrical Code, Section 8003(b)(3). [13] NFPA 70-1987, National Electrical Code, Section 8003(b)(2). 5. Conclusions [14] NFPA 70-1987, National Electrical Code, Section 8003(b)(1). The fire test data support the long-established fire performance hierarchy in the NEC and the CEC. [15] NEC-TCRA-1986, Proposal 16-155 6. Acknowledgments [16] NEC-TCDA-1986, Comment 16-20 The fire tests were conducted by Underwriters Laboratories for the Communications Cable & Connectivity Association (CCCA) on test [17] Provisional Specification- Tests to Determine Fire Retardancy and Acid Gas Evolution of Insulated Power and International Wire & Cable Symposium 559 Proceedings of the 66th IWCS Conference Control Cables (No. L-891SM-77). Ontario Hydro, Canada (1977). focus on wire and cable products and their fire safety and performance since 2001. [18] UL 1685 FT4.IEEE 1202,Vertical-Tray and FlamePropagation and Smoke-Release Tet for Electrical and Opticalfiber Cables,2015 Fred is a member of several fire safety related ASTM Subcommittees, and was a member of the Canadian National Research Council’s Task Group on Plenum Cables. Fred is the Chair of the Wire and Cable Section of the Plastics Industry Association (previously the Society of the Plastics Industry-SPI) Fluoropolymer Division as well as a US TAG member on IEC TC 89 and a member of the Canadian IEC TC 111 Mirror Committee. He is also a member of the IEEE (Institute of Electrical and Electronic Engineers) 802.3bt Task Force which is developing the most current PoE (Power over Ethernet) standard as well as the TIA (Telecommunications Industry Association) 42.7 Copper Communications Committee. Additionally, he is a member of IEEE 45.8, practice for selection, application and installation of electrical power, signal, control, data and specialty marine cable systems, shipboard. 8. Authors Fred is also the American Chemistry Council (ACC) Principal Representative on the NFPA National Electrical Code (NEC) Code Making Panel 16 (CMP 16). Fred holds a Bachelor of Mechanical Engineering degree from Concordia University (Montréal) as well as a Graduate Diploma in Business Management from McGill University (Montréal). *Effective July 1, 2015 the chemical businesses including the Fluorine businesses of DuPont were spun off to become the Chemours Company. At that time Fred became employed by Chemours. Fred Dawson The Chemours Canada Company 2233 Argentia Road, Suite 402 Mississauga, Ontario L5N 2X7 Since 1992 Fred has had responsibility for Regulatory Affairs within DuPont Canada’s Fluorine Products business (now operating as Chemours*), and expanded his role to include Regulatory Affairs for DuPont’s Fluoropolymer Solutions Business in the U.S. in 2005. Fred has over 40 years’ experience in sales and marketing in DuPont Canada’s Electronics and Fluoroproducts businesses. He is currently the Regulatory Affairs Manager for the Fluoropolymer business and has had a primary International Wire & Cable Symposium Gerald Lee Dorna Belden 5200 U. S. Highway 27 South Richmond, IN., 47374 Gerald Lee Dorna received is BSEE degree from Memphis State University in 1973. He has been employed by Belden for over 44 years and is currently the Technical Relations Manager. He has 560 Proceedings of the 66th IWCS Conference most of his professional career at Bell Labs/AT&T/Lucent Technologies in Norcross, GA. been involved with the National Electrical Code (NEC) since 1989 and became a member of Code Making Panel 16 (CMP-16) in 1995. Gerald currently is a member on UL’s Standard Technical Panel (STP) 13, 62, 83, 758 and 814. He is a member of CSA Technical Sub-Committee on Control, Instrument, Communication, and Marine Cables C231 (ICWC05). He is also a member of ASTM, CANENA, ICEA, IEEE, and NEMA and serves on different committees within these organizations. He was a frequent contributor to the IWCS since he presented his first paper at the 21st IWCS in1972 and won the best speaker award. His involvement with the National Electrical Code started when the 1975 NEC introduced rigorous installation requirements for cable installed in plenums. That change required a test for certifying the fire performance of plenum cables “as having adequate fire-resistant and low smoke-producing characteristics”. Stan and his coworkers at Bell Labs and Underwriters Labs presented a paper on the development of the plenum cable fire test, initially UL 910 an now NFPA 262, at the 25th IWCS in 1976. At the 35th IWCS in 1982, Stan and his coworkers at Bell Labs, Underwriters Labs and from Ohio State University presented a paper on the development of the riser cable fire test, UL 1666. UL 1666 is the test used for listing of riser cables as “having fireresistant characteristics capable of preventing the carrying of fire from floor to floor”. Stan remained active in the codes work after retiring from Lucent Technologies. He currently serves on four National Fire Protection Association Technical committees: NEC Panel 16: alternate representative to Gerald Dorna representing ICEA NEC Panel 12: representing the PLASTICS Industry Association, (formerly SPI) Dr. Stanley Kaufman Technical Committee on Electronic Computer Systems (NFPA 75): representing PLASTICS CableSafe, Inc. P.O. Box 50082 Technical Committee on Telecommunications (NFPA 76): representing PLASTICS Atlanta, Georgia 311150-0082 Stan Kaufman has a B.S. in Physics from City College of New York and a Ph.D. in Chemistry from Brown University. He spent International Wire & Cable Symposium 561 Proceedings of the 66th IWCS Conference