TITLE: BI – METAL LINE TAP Doc. No Issue No. 1 Revision No. 1 Date of Issue Page No: KE/300-043 SCOPE BI – METAL LINE TAP This specification covers technical requirements of design, manufacture, testing of bi – metal line taps and accessories for trouble free and efficient operation per IEC standards & Nigerian specification of local statutory authorities. The bi-metal line tap shall be designed to provide an effective corrosion barrier between the dissimilar metals Reference to NESIS: Chapter 3 Section 3.2.3 Chapter 7 section 7.2.3.15.3 The equipment provided shall conform with the following standards: IEC 61284 Overhead Lines – Requirement and Test for STANDARDS fittings And IEC 60889 Hard-drawn aluminium wire for overhead line REFERENCES conductors IEC 60888 Zinc-coated steel wires for stranded conductors SYSTEM DETAILS The following system parameters are applicable: Nominal System Voltage 11kV Highest System Voltage 12kV Relative humidity 10-100% Number of phases 3 Safety Factor ≥2.5 Frequency 50Hz Max. Ambient air temperature 50°C Creeping distance 320mm Colour Silver Minimum failing Load 6kN Grounding Ground through earthing transformer Issued by: HOG Engineering Standards Signed: Date: Authorized by: Head of Engineering Services Signed: Date: TITLE: BI – METAL LINE TAP Doc. No Issue No. 1 Revision No. 1 Date of Issue Page No: Issued by: HOG Engineering Standards Signed: Date: Authorized by: Head of Engineering Services Signed: Date: