Uploaded by kahwooi

349188495-Sullair-Deluxe-Microprocessor-Controller1-Operation-Manual

advertisement
DELUXE MICROPROCESSOR
CONTROLLER I
OPERATION
MANUAL
SHENZHEN SULLAIR ASIA INDUSTRIAL CO., LTD.
Part No.: 88290010-484
Rev. 00,
Jan, 2008
CATALOGUE
1. Functions of the Controller …………………………………………1
2. Key Pad………………………………………………………………1
3. Status Display ………………………………………………………3
4. Indicator ……………………………………………………………8
5. Setting of Running Parameters ……………………………………8
6. Running Mode of the Compressor …………………………………14
7. Main Functions ……………………………………………………15
Deluxe Microprocessor Controller I –Operation Manual
1.Functions of Deluxe Microprocessor Controller I
To ensure the normal operation of the controller, operators shall understand the meanings of
the marks on the control panel and have correct discretion on parameters and signals displayed at
the control panel.
Deluxe microprocessor controller I is powerful and reliable. The controller displays the
current, temperature, pressure, operation hours and run status on a LCD. With the keyboard at the
control panel, operators can control the compressor, set control parameters and display the preset
parameters. Indicators at the diagram show the position of each parameter (Figure 1). When the
light is on, there is an alarm.
2. Key Pad
STOP — Manually shut down the machine and eliminate the alarming. Press the key
when the machine is running, the machine will immediately shift to the unloading mode and
shut down the machine after 10 seconds.
MANUAL — Start up the machine at the operation mode and select manual operation
mode. When the machine is not in the alarming-at-stop status under
operation mode, pressing the key will eliminate the alarming and run the
machine in manual mode.
AUTO – Start up the machine in operation mode and select automatic operation mode.
When the machine is in the alarming-at-stop status under operation mode,
pressing the key will eliminate the alarming and run the machine in AUTO
mode.
DISPLAY – Display the pressure, temperature and other operation parameters.
PROGRAM – Press the key in operation mode to enter into the site parameter setup
screen, press the Sullair mark key to go to the password verification screen.
UP ARROW key – Used to change the displayed parameters in Status Display Mode.
Used to increase the value of parameters in parameter setup mode.
DOWN ARROW, Indicator Test - Used to change the displayed parameters in Status
Display Mode. Used to decrease the value of parameters in parameter
setup mode. Used to test indicators in default mode. When pressing the
key, all normal indicators will be lit for 3 seconds
Sullair Mark key – to complete specific operations in combination with other keys. Press
this key to check back in parameter setup mode.
Functions of keys combination:
then
1. History Records: Press
Records screen appears, press
next record. Press
and then
or
. When History
to display the previous record or
to display other parameters of a record. Parameters
Page 1 of 16
Deluxe Microprocessor Controller I –Operation Manual
recorded in monitor include P1, P2, P3, T1, T2, T3, Dp2, voltage deviation, current
time and total running time.
2. Alarm Records: Press
or
then
, alarm record screen displays. Press
to display the previous record or next record.
then
3. To set up and display operation parameters that need a password: Press
, password verification screen displays, use the keys
alter the parameters (press and hold
to enter parameters setup screen.
then
, clock screen will display.
to move the cursor to next setting and press
Press
to
, the parameter changes quickly. After the
parameters are set according to rules, press
4. The check and modify Clock: Press
and
or
to
and then
to
modify.
5. To check communication status: Press
then
enter communication status screen. Your can check current machine ID, other
machines’ working condition, current machine working mode and current machine
P1 and P2 value displayed in units selected in run status screen.
Meaning of communication status codes: R-Sequencing stop condition;
U-Unloading condition; T-Trimming loading condition;
F-Force loading condition; L-Loading condition.
The first line displays “communication status”. This is the machine’s
communication status screen.
The second line displays the communication ID of current machine on the left.
The two rows on the right (including the third row under corresponding
machine ID) display the communication ID and current working status of all
machines online.
The third line displays working condition of current machine on the left, “D”
for Disabled mode, “R” for remote control mode, “T” for time sequencing,
“C” for ID sequencing and “M” for Modbus mode.
The fourth line displays the current value of P1 and P2 of the current
machine for the convenience of online tuning and observation.
6. Three filters and dew point status records: Press
, use
and
then
and then
to select items to be displayed.
This record screen stores the time of last clogging/alarm and the time that
clogging/alarm is cleared. If repair time is later than alarm/clogging time, it means
that alarm/clogging has been cleared. Duration is calculated as repair time minus
clogging/alarm time, and actual running interval in the screen as running interval. If
repair time is prior to alarm/clogging time, it means that corresponding parts are in
fault condition and need to be serviced.
Page 2 of 16
Deluxe Microprocessor Controller I –Operation Manual
3. Status Display
In default conditions, the screen displays 4 lines of data. The first line is the status of the
machine, the second and third lines are discharge pressure P1, side discharge pressure P2,
discharge temperature T1 and side discharge pressure T2. The last line displays corresponding
pressure and temperature unit.
The followings are various statuses that may be displayed on the screen. Temperature unit is
℃ and pressure unit is bar. (You may also select the English unit such as oF and PSI, please refer
to the UNIT SETUP in PARAMETER SETUP for details.)
※ STOP - Shut down the machine.
※ STANDBY – Shut down the machine on a temporary basis. When the power fails or
when unloading relay is in action, the machine goes to STANDBY mode. Please note
that the machine in STANDBY mode may resume at any time.
※ STARTING – The compressor is being started.
※ OFF LOAD – The compressor is running but does not supply compressed air.
※ ON LOAD – The compressor is running and supplies compressed air.
※ FULL LOAD – The compressor is running and has full load. It is displayed only when
the machine is in online control mode and there is a full load valve.
※ RTM STOP – Remote Stop. When the remote starting contactors are closed, the machine
restarts. Please note that the machine in RTM STOP mode may resume at any time.
※ SEQ STOP – Sequence control Stop. When the requirements set by the preset sequence
for starting the machine are met, the machine restarts. Please note that the machine in
this mode may resume at any time.
Page 3 of 16
Deluxe Microprocessor Controller I –Operation Manual
Figure 1. Control Panel of the Monitor (Deluxe Microprocessor Controller I)
※ Boot-up Screen (illustrated in the following sample): SULLAIR is the mark of the
Company, ES-11DRY is the mode of the machine, CO3-CXXXXX is the serial number,
XXXXX is the only number determined when the machine was delivered from the
factory and is the same as that of the supporting machines. REV: XX.XX is version of
the software, 2004/01 means the date on which the controller was delivered from the
factory. - refers to a space.
SULLAIRˇES-11DRY
ˇˇˇCO3-CXXXXXˇˇˇ
ˇRUNˇˇˇXXXXXHRSˇ
REV:XX.XXˇ2004/01
Page 4 of 16
Deluxe Microprocessor Controller I –Operation Manual
*IMPORTANT!
In no cases shall the users attempt to modify the serial number of the machine,
otherwise the serial number shall be reset to zero. In such case Sullair takes no
responsibility for the replacement and repair of the Deluxe Microprocessor
Controller I. If you need to change the serial number please contact the Service
Department of Sullair.
※ Operation Screen: There are 4 screens as shown below. ˇ refers to a space; TD refers
to dew point, T0 refers to the chip temperature of controller main-board (approximately
the ambient temperature), U refers to voltage deviation and I refers to main motor (or
machine)’s current.
The accumulated run time and loading time are only displayed as RUN and LOAD.
Operation mode:
STOP
P1:xx.xx T1:xxx
P2:xx.xx T2:xxx
P:BARˇˇˇˇT:
STOP
P3:xx.xx T3:xxx
P4:xx.xx T4:xxx
P:BARˇˇˇˇT:
STOP
T5:xxx TD:xxx
T6:xxx T0:xxx
T:℃ ΔP1:xxx
STOP
RUN ˇ ˇ ˇ ˇ ˇ
XXXXXHRS
LOAD ˇ ˇ ˇ ˇ
In Chinese or English
Currently
selected unit
! Caution
For unused analog input channel, no value will be shown after corresponding code
on operation screen. For instance, in case T5 and T6 are not selected, values for T5
and T6 are blank as shown below. For selected analog input channels, “- - -” after
corresponding codes indicates that open circuit or short circuit fault may present.
Meanwhile alarm shall occur. See the following figure of disconnected T1, “T1: - - -” is
shown on the screen.
Press START button in operation screen. The machine may not respond due to
minimum stop time is not met. In such case a countdown timer (in second) will appear
on the upper left corner of the display showing the time before machine start allowed.
Once the timer counts down to zero and disappears, the machine is allowed to start.
※ STOP – The Machine is in STOP mode.
The default display is as below:
STOP
P1:xx.xx T1:xxx
P2:xx.xx T2:xxx
P:BARˇˇˇˇT:
Page 5 of 16
Deluxe Microprocessor Controller I –Operation Manual
If there is a fault signal, in default situation, the fault signal is displayed alternatively, each
screen is displayed for two seconds. The default is displayed as below (for example: machine
overload):
M1 Overload
P1:xx.xx T1:xxx
P2:xx.xx T2:xxx
P:BARˇˇˇˇT:
When the machine is running, the default operation screen displays 5 messages i.e. operation
mode, discharge pressure P1, side discharge pressure P2, discharge temperature T1 and side
discharge temperature T2.
STOP
P1:xx.xx T1:xxx
P2:xx.xx T2:xxx
P:BARˇˇˇˇT:
Press the Emergency Stop button, the machine stops immediately and gives an alarm.
Press the STOP button at the controller, the machine enter into unloading condition
immediately and stops after 10 seconds. In this case the following screen is displayed:
Unloading
P1:xx.xx T1:xxx
P2:xx.xx T2:xxx
P:BARˇˇˇˇT:
! Caution
* In the process of Unloading, press the MANUAL RUN button or AUTO RUN button
the machine will enter into operation mode immediately.
* It is recommended that always use the STOP button at the panel for normal
shutdown.
Press
button to display other parameters. You can check temperature, pressure,
accumulated time, voltage deviation and current, etc. in this mode. Press
parameters to display. Press the button
to select
to return to the original screen of operation mode.
※ P3 and P4 are the pressures before and after oil filter; T3 is oil injection temperature and
T4 is inter-level temperature (if these measures are not used by the machine, 0 and –80
will be displayed for pressure and temperature respectively):
STOP
P3:xx.xx T3:xxx
P4:xx.xx T4:xxx
P:BARˇˇˇˇT:
Page 6 of 16
Deluxe Microprocessor Controller I –Operation Manual
※ Compressor discharge temperature alarming set point and alarming and stop set point;
NO:77
T1 WARN
107 ℃
NO:78
T1 MAX
113 ℃
When the discharge temperature reaches the alarming set point, the T1 alarming indicator is lit and
shows the T1 is high. At this time the machine does not stop. When the discharge temperature
exceeds the alarming and stop set point, the T1 alarming indicator is lit and shows the T1 is too
high. At this time the machine will stop immediately.
※ Compressor dry side discharge temperature alarming set point and alarming stop set
point;
NO:79
T1 WARN
107 ℃
NO:80
T2 MAX
113 ℃
When the dry side discharge temperature exceeds the alarming set point, T2 alarming indicator is
lit and shows T2 is slightly high. At this time, the machine is not stopped. If the dry side discharge
temperature exceeds the alarming and stop set point, T2 alarming indicator is lit and shows T2 is
too high. At this time, the machine will stop immediately.
※ Accumulated running time (hour) of the compressor, accumulated loading time (hour) of
the compressor.
Accumulated running time (hour) of the compressor, accumulated loading time (hour) of
the compressor can be displayed in operation screen.
STOP
RUNˇ XXXXXHRS
LOADˇXXXXXHRS
U:-20%ˇI:XXXXA
※ Stop fault information – Last 40 stop triggering fault signals are recorded along with
time. See Sullair’s Air Compressor Button Operation Manual.
Warn Notes
0 03-11-19
10:27
M1 Over load
Page 7 of 16
Deluxe Microprocessor Controller I –Operation Manual
4. Indicator
11 indicators are located on the controller panel. On the operation screen, press
key,
and all the indicators will be lit for about 3 seconds; otherwise the indicator is faulted.
The function of each indicator:
P1 – Pressure inside the separator. If the indicator is lit, it means the controller has given
alarm.
P2 – Pipeline pressure. If the indicator is lit, it means the controller has given alarm.
T1 – Main unit discharge temperature. If the indicator is lit, it means the controller has given
alarm.
T2 – Dry side discharge temperature. If the indicator is lit, it means the controller has given
alarm.
△P1 – Pressure difference before and after the separator. If the indicator is lit, it means the
filtering element must be replaced.
△P2 – Pressure difference before and after the oil filter. If the indicator is lit, it means the oil
filtering element must be replaced.
MOTOR ------ Motor overload indicator. If the indicator flashes, it means the motor overload
contact has been disconnected.
POWER ------ Power indicator. If the monitor is connected with 110V AC power, this
indicator will be always time.
ON ------ Running indicator. If the light is stable, it indicates the machine is running; if it
flashes, it indicates the machine is under Standby mode and can be started at
any time.
AUTO ------ Auto run indicator. If the light is stable, it indicates the machine is auto
running; if it flashes, it indicates the machine is under Standby mode and can
be started at any time.
AIR FILTER ------ Air filter alarming indicator. If the light is lit, it indicates the air filter
needs maintenance.
5. Setting of Running Parameters
Before the compressor is started, the running parameters must be set first.
(1) Press “PROG” key, and the monitor enters the program control mode. At this time, all
user parameters can be checked but are not editable (press Up Arrow and Down Arrow
keys may change value display but controller will not confirm). Press “Sullair Mark Key”
and then “PRG” key, password verification screen will appear. Modify the value according
to user class password setting principles and all user parameters will appear. User may
modify all user parameters using this method. Press Up Arrow key to increase the
parameter value; press Down Arrow key to decrease the parameter value. The lowest line at
the parameter setting screen indicates the allowable range of the parameter setting.
Page 8 of 16
Deluxe Microprocessor Controller I –Operation Manual
The parameters are displayed based on the following sequence:
※ Display language – Choose 0 to display in Chinese; choose 1 to display in English.
NO:1
LANGUAGE
Chinese
Chinese/English
※ Temperature unit – Choose ℃ to display temperature in ℃; choose OF to display
temperature in OF.
NO:3
T.UNIT
℃
℃/oF
※ Pressure unit - Choose bar to display pressure in Bar; choose PSI to display pressure in
PSI.
NO:4
P.UNIT
Bar
Bar/PSI
※ Unloading pressure ------ When the parameter setting is 7.6bar, the machine will unload
when P2 reaches 7.6bar.
NO:5
UNLOAD
7.6Bar
2.0~15.1Bar
※ Loading pressure difference ------ Difference between loading pressure and unloading
pressure. If the unloading pressure is set at 7.5bar and the loading pressure difference is set at
0.6bar, then when the pipeline pressure is the below 6.9bar, the machine will load.
NO: 6
LOAD
0.7Bar
0.4~4.8Bar
※ Y-△ conversion time (second) – If a full voltage starter is used, set this value to 0.
NO:7
WYE-DELTA TIME
6sec
0--15sec
Page 9 of 16
Deluxe Microprocessor Controller I –Operation Manual
※ Start load delay time ------ If 5 is selected, it indicates after the machine has Y-△
conversion, 5sec later, the machine will enter the loading status.
NO:8
LOAD DELAY TIME
5sec
0--30sec
※ K5 output selection – when drain valve is selected, K5 relay acts according to drain
interval and drain time parameters. When remote output is selected in REMOTE
operation mode, K5 will close during allowed remote operation (for instance, select
Remote operation mode after the machine is stopped and press ON key, or change to
Remote mode from other operation modes during operation, etc.).
NO:9
K5 select
Remote
Drain /Remote
※ Drain interval – The interval between two draining operations.
NO:10
Drain interval
10 min
0—30 min
※ Drain time – Duration of drain valve action.
NO:11
Drain time
5 sec
0—10 sec
※ Backlight selection – Select the background color for LCD display.
NO:15
Backlight color
White
White/blue/yellow/ green
※ Unloading shutdown time – Under the auto mode, decide the allowable unload delay
time for the machine from unloading status to auto stop.
NO:17
UNLD TIME
15 min
15—120 min
Page 10 of 16
Deluxe Microprocessor Controller I –Operation Manual
※ Minimum shutdown time – Interval between last shutdown and restart, during which the
controller does not respond to Start instruction.
NO:18
STOP TIME
10 sec
0—30 sec
※ Power recovery start delay time – If main power fails during normal machine operation
and recovers, the controller will not respond to Start instruction until “Power recovery
start delay time” expires.
NO:19
DELAY TIME
10 sec
0—30 sec
※ Control mode – Set working mode of the machine. For how to set the machine in which
mode, please refer to the section of “Compressor running mode”.
NO:31
Control mode
Disabled
※ Capacity – Please refer to Sullair Sequence control and communication protocol manual
of deluxe microprocessor controller I.
NO:36
Capacity
21
0—10000m2/min
※ Rotation time – Please refer to Sullair Sequence control and communication protocol
manual of deluxe microprocessor controller I.
NO:37
Shift time
50 hours
10—250 hours
※ Communication ID – Please refer to Sullair Sequence control and communication
protocol manual of monitor deluxe microprocessor controller I.
NO:38
COM ID#
1
1--16
Page 11 of 16
Deluxe Microprocessor Controller I –Operation Manual
※ Communication baud rate – Please refer to Sullair Sequence control and communication
protocol manual of monitor deluxe microprocessor controller I.
NO:40
BAUDRATE
9600
※
Recover time – Please refer to Sullair Sequence control and communication protocol
manual of monitor deluxe microprocessor controller I.
NO:41
Recover time
5 sec
2-30 sec
※ A1 OUT SELECT – When this parameter is designated to T1, A1 analog output port
outputs 0 to 10V analog value corresponding to T1 variation; when this parameter is
designated to P2 LOAD, A1 analog output port outputs 0 to 10V analog value
corresponding to P2 LOAD for connection with transducer.
NO:48
A1 SELECT
T1
T1/P2 LOAD
※ High-voltage pulse time – This parameter determines action duration of K7 and K8 (this
function is not available).
NO:49
H-volt pulse time
1.5 sec
0.7—3.0 sec
※ T1 calibration – Used for correcting the measuring error.
NO:50
T1 CAL
0℃
-7--+7℃
※ T2 calibration – Used for correcting the measuring error.
NO:51
T2 CAL
0℃
-7--+7℃
Page 12 of 16
Deluxe Microprocessor Controller I –Operation Manual
※ T3 calibration – Used for correcting the measuring error.
NO:52
T3 CAL
0℃
-7--+7℃
※ T4 calibration – Used for correcting the measuring error.
NO:53
T4 CAL
0℃
-7--+7℃
※ T5 calibration – Used for correcting the measuring error.
NO:54
T5 CAL
0℃
-7--+7℃
※ T6 calibration – Used for correcting the measuring error.
NO:55
T6 CAL
0℃
-7--+7℃
※ TD calibration – Used for correcting the measuring error.
NO:56
T7 CAL
0 Bar
-2.0--+2.0Bar
※ P1 calibration – Used for correcting the measuring error.
NO:57
P1 CAL
0 Bar
-2.0--+2.0Bar
※ P2 calibration – Used for correcting the measuring error.
NO:58
P2 CAL
0 Bar
-2.0--+2.0Bar
Page 13 of 16
Deluxe Microprocessor Controller I –Operation Manual
※ P3 calibration – Used for correcting the measuring error.
NO:59
P3 CAL
0 Bar
-2.0--+2.0Bar
※ P4 calibration – Used for correcting the measuring error.
NO:60
P4 CAL
0 Bar
-2.0--+2.0Bar
※ dP1 calibration – Used for correcting the measuring error.
NO:61
ΔP1 CAL
0 Bar
-1.0--+1.0Bar
※ dp2 calibration – Used for correcting the measuring error.
NO:62
ΔP2 CAL
0 Bar
-1.0--+1.0Bar
6. Running Mode of the Compressor
The compressor have the following running modes.
(1) Manual run mode (select “Disabled” control mode correspondingly)
Press
key to start the compressor. At this time, the compressor will be put at
manual run mode.
If the compressor is running and under auto run mode, when pressing
key, the auto
mode can be changed into manual mode. If the compressor is running under manual run
mode, when pressing
key, the alarming signal can be cleared and the indicator is
extinguished.
To turn off the unit, press
key.
If the unit is stopped already, press
key again to clear the alarming signal and
extinguish the alarming indicator.
(2) Auto run mode (select “Disabled” control mode correspondingly)
Page 14 of 16
Deluxe Microprocessor Controller I –Operation Manual
Press
key to start the compressor. At this time, the compressor is under the auto run
mode.
key, the manual mode
If the compressor is under manual run mode, when pressing
can be changed into auto mode.
If the compressor is under auto run mode, when pressing
key, the alarming signal
can be cleared and the indicator is extinguished.
Under auto run mode, press
key to stop the compressor. At this time, the monitor
will be under manual stop mode.
(3) Sequencing control mode
The following will describe briefly the sequencing control mode. For details, please refer to
“Sequencing control and communication protocol manual of monitor deluxe microprocessor
controller I”.
※
Disabled – Respond to the inquiry command and can send back the machine status and
parameter message; but doesn’t respond to the start, stop, load and unload command of the main
unit (computer).
※
Remote control – Respond to the inquiry command and can send back the machine
status and parameter message; but doesn’t respond to the start, stop, load and unload command of
the main unit (computer). This mode allows remote input of “start/stop” signal.
※
Master/Slave – Respond to all the commands. Note under this status, if the slave unit
doesn’t receive the command sent from the main unit, it can’t be started or loaded. The slave unit
is controlled from the main unit (computer).
※
Sequence time – Send the status message about once a second. Control the machine
based on the sequence time (start, load or unload).
※ Communication ID – Send the status message about once a second. Control the machine
(start, load or unload) based on the machine number (COM ID#).
※ MODBUS – Adopt MODBUS communication. This method is used when using upper
unit for the control.
7. Main Functions
(1) The system features 2 RS485 ports. 1# RS485 port uses sequencing communication protocol
and 2# RS485 port uses Modbus communication protocol. In sequencing mode, no upper unit
or other devices are needed. Simply connect 1# RS485 port of each controller and set all
controllers into sequencing mode. All machines will work in networked control mode.
(2) The system features dew point and main unit current real-time display and alarming functions.
(3) 4 channels of external switch input are provided to monitor post treatment devices and alarm.
(4) 40 entries of alarm records and 60 entries of rolling history operation records in 2 hours (1
entry in every 2 minutes) are provided for the convenience of maintenance and analysis.
Page 15 of 16
Deluxe Microprocessor Controller I –Operation Manual
(5) Fault and fault clearance records for the three filters (oil/air separator filter element, air filter
and oil filter) and dew point temperature.
(6) Clock in Year/Month/Date/Hour/Minute. It records the time of history event and fault
accurately for the convenience of maintenance and analysis.
(7) 2 channels of analog output ports to output 3 types of analog DC0 ~10V value of T1 and P2
value in real-time and loading pressure for user to collect analog value and connection of
transducer.
* Note: Either T1 or loading pressure set point can be output, but not both.
(8) 4 LCD backlight colors (White, Yellow, Blue and Green) are available for different ambient
conditions.
(9) The system features ambient temperature detecting function. The system alarms when
temperature of control IC exceeds 63℃, and machine will be shutdown automatically if
temperature exceeds 68℃.
(10) The system features main unit current protection function. Together with main unit heat relay,
this function protect main unit from being damaged by high current. If current exceeds the
safety current of main unit for over 135 seconds, controller will give “Main Unit Over
Current” alarm and shutdown the machine.
Page 16 of 16
Global Sale and Service
US Headquarter:SULLAIR CORPORATION
Subsidiary of Hamilton-Sundstrand Corporation
3700 East Michigan Boulevard
Michigan City, Indiana 46360 U.S.A.
Telephone: 001-219-879-5451 or
1-800-Sullair (U.S.A. only)
Fax: 001-219-874-1273
Fax: 001-219-874-1835 (Parts)
Fax: 001-219-874-1805 (Service)
European Headquarter; SULLAIR EUROPE, S.A.
Zone Des Granges BP 82
42602 Montbrison Cedex, France
Telephone: 0033-4-77968470
Fax: 0033-4-77968499
Asia Headquarter:SULLAIR ASIA LIMITED
518068 Zuo Paotai Road, Shekou Chiwan, Shenzhen, China
Telephone: 0755-26851686
Fax: 0755-26853473, 26853475
Service hotline: 800-830-3977
Website:
http://www.sullair-asia.com
Shanghai Branch Company: 1504 room, GangLu Square, No.18 Tibet Middle
Road,Shanghai City
Post Code: 200001
Telephone: 021-53852036, 53852038 Fax: 021-53852035
Beijing Branch Company: 1506 room, B unit in Xingfu Mansion, No.3 Dong SanhuanNorth
Road, Beijing City
Post Code: 100027
Telephone: 010-64629770, 64629768 Fax: 010-64629773
Chengdu Branch Company: H unit, 28th floor, Guancheng Square, No. 308 Shuncheng
Street, Chengdu City. Post Code: 610017
Telephone: 028-86764845, 86528048 Fax: 028-86527505
Shenyang Branch Company: 1601 room, gaoDeng International Mansion,
No.355Zhongshan Road, Shenhe District, Shenyang City
Post Code: 110014
Telephone: 024-22818550, 22818650, 22818450 Fax: 024-22818590
Xi’an Branch Company: 701A, 7th floor, Jinxin International Mansion, No.99 Heping Road,
Xi’an City Post Code: 710000
Telephone: 029-87206201/87206202
Fax: 029-87206204
Wuhan Branch Company: 2909 room, B unit Zhongshang Square, No.7 Zhongnan Road,
Wuchang, Wuhan City
Post Code:430071
Telephone: 027-87322745
Fax: 027-873225
Download