Installation & Maintenance TMC470 Marking System Controller This document contains installation and maintenance information for the Telesis® TMC470 Marking System Controller. Document No. 34701F Telesis Technologies, Inc. 28181 River Drive P.O. Box 1000 Circleville, Ohio 43113 TMC470 Installation & Maintenance Foreword Telesis Technologies, Inc. (hereinafter referred to as Telesis) reserves the right to change the information and specifications contained in this document without prior notice. The reader should consult Telesis to determine whether such changes have been made. In no event shall Telesis be liable for any incidental, indirect, special, or consequential damages whatsoever, including but not limited to lost profits, arising out of, or relating to this document or the information it contains, even if Telesis has been advised, has knowledge, or should have knowledge of the possibility of such damages. Telesis expressly warrants the equipment it manufactures as set forth in the Standard Terms and Conditions of Sale. Telesis makes no other warranties, expressed or implied, including and without limitation, warranties as to merchantability or fitness for a particular purpose. The information contained in this document is confidential and is proprietary to Telesis or its licensors. Trademarks Telesis and Merlin are registered trademarks of Telesis Technologies, Inc. in the United States and/or other countries. NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association. © 2008 – 2011 Telesis Technologies, Incorporated – All Rights Reserved 34701F i TMC470 Installation & Maintenance License Agreement for Telesis Software IMPORTANT: THE SUBJECT PROGRAMS ARE LICENSED BY TELESIS TECHNOLOGIES, INC. TO END-USERS FOR THEIR USE ONLY ON THE TERMS BELOW. ACCEPTING AND USING THESE PROGRAMS INDICATES YOUR ACCEPTANCE OF THESE TERMS. THIS IS A LEGAL AGREEMENT BETWEEN YOU, THE END USER, AND TELESIS TECHNOLOGIES, INC. 1) GRANT OF LICENSE. Telesis Technologies, Inc. (Telesis) agrees to grant to you a non-exclusive license to use the Telesis software/firmware program (the program) subject to the terms and conditions of this license agreement. 2) DEFINITION OF TERMS. The term software refers to a computer program stored on electronic media that must be loaded into computer memory to be executed. The term firmware refers to a computer program stored in semiconductor memory (ROM, PROM, EPROM, EEPROM, NVRAM, etc.) that is an integral part of the computer memory. Together, these forms of computer programs are referred to as the program. 3) COPYRIGHT. The program(s) and documentation is owned by Telesis and is protected by United States copyright laws and international treaty provisions. The program(s) contain trade secrets and proprietary property of Telesis. You may make one copy of the program(s) solely for backup or archival purposes provided that the copy clearly displays the Telesis copyright notice. Additional copies may be made when authorized to do so in writing by Telesis. In addition to any other right of Telesis, Telesis has the right to terminate this license if the terms of the license are violated. 4) RESTRICTION ON USE AND TRANSFER. The single-processor version(s) of the program(s) and documentation are to be used on one computer or embedded system at any one time. The multi-processor version(s) of the program(s) and documentation may be used over a network provided that the number of computers accessing the network simultaneously shall not exceed the number authorized by Telesis or for which you paid the corresponding multi-processor fee. You may not distribute the programs or documentation to a third party. You may transfer the license and complete package (retaining nothing) if the transferee agrees to the terms of this License Agreement. Neither the program(s) nor the documentation may be changed or translated without express written permission of Telesis. You may not reverse engineer, decompile or disassemble the program(s). 5) WARRANTY for the subject program(s) is covered under the Telesis Standard Terms and Conditions of Sale. 6) TERM. The license is effective until terminated. It will be terminated if you fail to comply with any term or condition of this License Agreement. You may terminate this License Agreement at any time. In the event of termination, you agree to destroy the program(s) and documentation together with all copies and related material. 7) YOUR USE OF THIS PROGRAM(S) acknowledges that you have read this License Agreement and agree to its terms. This agreement is complete and supersedes any other agreement that may have related to the subject matter of this agreement. ii 34701F TMC470 Installation & Maintenance Safety Summary The following safety precautions should be observed at all times. ¡ The controller uses high voltage power supplies. Accordingly, there is some danger when working with, and near, marking machines. ¡ Never use the equipment in any manner or for any purpose other than that for which it was designed. Warnings, Cautions, and Notes may be placed throughout this document to alert you to important information. These messages have the following significance. Warnings contain information that is essential to the personal safety of the user. Cautions contain information that is essential to avoid damage to the equipment. Notes call attention to information of special importance at specific points within the text. The following Warnings and Cautions are contained in this document. WARNING Turn all power OFF when performing maintenance on the controller. Ensure that all equipment energy sources are turned off or disconnected and that the switches are either locked or tagged while equipment is cleaned or serviced. The controller contains a lithium battery. Improper disposal of lithium batteries may cause an explosion. Always dispose of the lithium battery in a proper manner. CAUTION Do not block vents on the bottom of the controller. The TMC470 is not a sealed unit. Protect it from potentially damaging conditions and contaminants. Ensure the marking system is electrically isolated from any devices that may generate extreme electromagnetic interference (EMI). If your equipment arrives during cold weather, allow the components to warm up for several hours before opening the containers. Exposing the equipment to room temperatures may cause condensation in the units. The controller is shipped with electrostatic covers installed on the back panel connectors. Leave the covers installed on those connectors that will not be used. This will help to prevent electrostatic discharge (ESD) problems. Never connect or disconnect the Marker cable or the Auxiliary Axis cable while controller power is ON. Damage to the equipment will occur. Do not press on the LCD display nor apply heavy pressure to the keyboard. Be extremely careful not to scratch the LCD display or the membrane keyboard. Do not apply liquids directly to the controller. Apply liquid to cleaning cloth instead. Application of excessive liquid may enter the case and damage internal components. Mounting brackets incorrectly on the underside of the controller will block air flow and may damage the controller or cause the unit to shutdown abnormally. When installing the controller into a TMC470N enclosure, be careful to not damage the rubber grommets when removing them from the cabinet seal module. 34701F iii TMC470 Installation & Maintenance Table of Contents TOPIC PAGE Foreword ..................................................................................................................................................... i Trademarks ................................................................................................................................................. i License Agreement for Telesis Software........................................................................................................... ii Safety Summary .......................................................................................................................................... iii List of Illustrations ........................................................................................................................................ vi List of Tables ............................................................................................................................................... vi Section 1 – Installation 1.1 Overview....................................................................................................................................... 1-1 1.2 Description ................................................................................................................................... 1-1 1.3 Specifications................................................................................................................................ 1-2 1.4 Unpacking the Equipment ............................................................................................................. 1-3 1.5 Installation Requirements ............................................................................................................ 1-4 Installation Procedures ................................................................................................................. 1-6 1.6.1 1-6 1.6 1.7 1.8 iv Site Preparation .................................................................................................................. 1.6.2 Standard Table-top Installation ............................................................................................. 1-7 1.6.3 Optional Wall-mounted Installation ........................................................................................ 1-7 1.6.4 Optional Panel-mounted Installation ...................................................................................... Attaching the Mounting Brackets ........................................................................................ Installing the Bezel Gaskets ............................................................................................... Attaching the Mounting Bezel ............................................................................................. Attaching the Controller .................................................................................................... 1-8 1-8 1-9 1-10 1-12 1.6.5 Optional TMC470N NEMA Enclosure Installation ....................................................................... 1-13 Data and Electrical Connections .................................................................................................... 1-16 1.7.1 Marker Connection............................................................................................................... 1-17 1.7.2 Power Connection ................................................................................................................ 1-17 1.7.3 Auxiliary Axis Connection ..................................................................................................... 1-18 1.7.4 TTL Connection ................................................................................................................... 1-19 1.7.5 Comm 1 / Comm 2 Connections ............................................................................................ RS232 Interface ............................................................................................................... RS485 Interface ............................................................................................................... Programmable Protocol ..................................................................................................... Extended Protocol ............................................................................................................ 1-20 1-21 1-22 1-24 1-24 1.7.6 Remote I/O Connection ........................................................................................................ VDC Input Connections ..................................................................................................... VDC Output Connections ................................................................................................... Remote I/O Signal Timing ................................................................................................. Remote Pattern Selection .................................................................................................. 1-25 1-26 1-27 1-28 1-29 1.7.7 Ethernet/Merlin Connection................................................................................................... 1-30 1.7.8 TMC420N NEMA Enclosure – Cabinet Seal ............................................................................... 1-32 Controller Checkout ...................................................................................................................... 1-32 34701F TMC470 Installation & Maintenance Table of Contents TOPIC PAGE Section 2 – Maintenance 2.1 Overview ...................................................................................................................................... 2-1 2.2 Maintenance Precautions .............................................................................................................. 2-1 2.3 Cleaning Procedures ..................................................................................................................... 2-1 2.4 Troubleshooting............................................................................................................................ 2-2 2.5 Testing Procedures ....................................................................................................................... 2-3 2.5.1 Comm 1 and Comm 2 Port Testing ........................................................................................ 2-3 2.5.2 I/O Port Testing .................................................................................................................. 2-4 2.5.3 TTL Port Testing .................................................................................................................. 2-5 2.5.4 Marker Port Testing ............................................................................................................. 2-6 2.5.5 Auxiliary Axis Port Testing .................................................................................................... 2-7 2.6 Replacement Procedures .............................................................................................................. 2-8 2.7 Reference Data ............................................................................................................................. 2-10 2.7.1 Replacement Parts .............................................................................................................. 2-10 2.7.2 Ordering Parts .................................................................................................................... 2-11 Appendix A ASCII Character Cross Reference Standard ASCII Characters ....................................................................................................................... A-1 Extended ASCII Characters ....................................................................................................................... A-2 34701F v TMC470 Installation & Maintenance List of Illustrations FIGURE PAGE 1-1 TMC470 Controller Back Panel ............................................................................................................. 1-2 TMC470 Table-top or Wall-Mounted Installation Drawing ........................................................................ 1-1 1-5 1-3 Power Entry Module – Fuse Configurations ............................................................................................ 1-6 1-4 Proper Wall-mount Bracket Orientation ................................................................................................ 1-7 1-5 Mounting Bracket Orientation .............................................................................................................. 1-8 1-6 Gasket Orientation............................................................................................................................. 1-9 1-7 Mounting Bracket Orientation .............................................................................................................. 1-10 1-8 Panel (or Enclosure) Mounting Surface ................................................................................................. 1-10 1-9 TMC470 Panel-mounted Installation Drawing ........................................................................................ 1-11 1-10 Controller Orientation and Hardware Locations ...................................................................................... 1-12 1-11 TMC470N NEMA Enclosure .................................................................................................................. 1-13 1-12 TMC470N NEMA Enclosure Installation Drawing ..................................................................................... 1-15 1-13 TTL Connections ................................................................................................................................ 1-19 1-14 RS232 Cable Diagrams ....................................................................................................................... 1-21 1-15 RS485 Connections for Networked Markers ........................................................................................... 1-23 1-16 VDC Input Connections ...................................................................................................................... 1-26 1-17 VDC Output Connections .................................................................................................................... 1-27 1-18 Input/Output Signals – Timing Diagram ............................................................................................... 1-28 2-1 Power Entry Module / Fuse Holder Assembly ......................................................................................... 2-8 List of Tables TABLE PAGE 1-1 Optional TMC470 Panel Mount Kit (63150) ............................................................................................ 1-8 1-2 Comm 1 Port – Pin Assignments .......................................................................................................... 1-20 1-3 Comm 2 Port – Pin Assignments .......................................................................................................... 1-20 1-4 I/O Port – Pin Assignments ................................................................................................................ 1-25 1-5 Reserved Pattern Names for Remote Pattern Selection ........................................................................... 1-29 1-6 Ethernet Port – Pin Assignments .......................................................................................................... 1-30 2-1 Troubleshooting ................................................................................................................................ 2-2 2-2 Comm Port Connectors....................................................................................................................... 2-3 2-3 I/O Port Connector ............................................................................................................................ 2-4 2-4 TTL Port Connector ............................................................................................................................ 2-5 2-5 Marker Port Connector ....................................................................................................................... 2-6 2-6 Optional Auxiliary Axis Port Connector .................................................................................................. 2-7 2-7 Controller Power Inlet Fuses ............................................................................................................... 2-9 2-8 Spare Parts ....................................................................................................................................... 2-10 vi 34701F TMC470 Installation & Maintenance Section 1 Installation 1.1 OVERVIEW This section documents the installation of the TMC470 controller. The controller may be used with a variety of Telesis marking heads. Installation of the controller is almost identical for all systems. Where variations do exist, they will be clearly identified within the text to inform you of the differences. 1.2 DESCRIPTION The TMC470 controller contains an integrated keyboard and display. It runs the marking system software and generates commands that control the marker. The marking system software is an easy-to-use program that is pre-installed in the controller. Refer to the TMC470 Controller Operation Manual for details on using the software. The TMC470 may be installed in any of the following configurations: • • • • Standard controller placed on a table top Standard controller with optional kit, mounted on a wall or exterior panel Standard controller with optional kit, mounted in a customer-supplied panel or enclosure Standard controller mounted in an optional Telesis TMC470N NEMA® enclosure. The back panel provides various ports for connections to facility power, the marking head, and optional, remote input/output devices. See Figure 1-1. Figure 1-1. TMC470 Controller Back Panel 34701F 1-1 TMC470 Installation & Maintenance 1.3 SPECIFICATIONS The controller design and specifications are subject to change without prior notice. Integrated Keyboard.............. Standard keyboard plus special function keys Integrated Display ................. Eight-line liquid crystal display (LCD) Rating .................................. NEMA 1 (I.P. 30) – table-top and wall-mounted configuration NEMA 12 (I.P. 65) – panel-mounted configuration (customer-supplied panel or enclosure) NEMA 12 (I.P. 65) – enclosure-mounted configuration (Telesis TMC470N enclosure) Dimensions (H x W x D) ......... Table-top Configuration: 2.95 x 13.71 x 7.71 in. (74.9 x 348.2 x 195.8 mm) controller only 4.25 x 14.62 x 12.00 in. (108.0 x 371.4 x 304.8 mm) surrounding envelope Wall-mounted Configuration: 7.71 x 14.62 x 3.29 in. (195.8 x 371.4 x 83.5 mm) controller & brackets 12.00 x 14.62 x 4.25 in. (304.8 x 371.4 x 108.0 mm) surrounding envelope Panel-mounted Configuration: 8.53 x 14.53 x 3.17 in. (216.53 x 368.9 x 80.6 mm) controller, bezel & brackets 12.43 x 15.51 x 4.00 in. (315.6 x 394.0 x 101.5 mm) surrounding envelope Enclosure-mounted Configuration: 11.82 x 19.00 x 16.00 in. (300.32 x 482.45 x 406.28 mm) TMC470N NEMA enclosure 14.00 x 23.00 x 22.00 in. (355.60 x 584.20 x 558.80 mm) surrounding envelope Weight ................................. 3.69 3.90 5.52 28.1 lb. lb. lb. lb. (1.68 kg) controller only (1.77 kg) controller and wall-mounting hardware (2.51 kg) controller and panel-mounting hardware (12.77 kg) controller, enclosure, and mounting hardware Power Requirements .............. 95 to 250 VAC, 2 amps, 50-60 Hz, single phase Communications ................... TTL, Discrete I/O, RS232, RS485 (multi-drop network), TCP/IP, USB (data backup/transfer) Input Signals ........................ Twelve (12) total, optically isolated; 8 dedicated, 1 programmable, 3 available (customer-supplied) 10 VDC (minimum voltage) 30 VDC (maximum voltage) 12 to 24 VDC (nominal voltage) 2.3 mA @ 12VDC; 4.9 mA @ 24VDC (nominal current) Output Signals ...................... Six (6) total; 4 dedicated, 2 available 0.25 amps (maximum current) 0.50 ohms (maximum On resistance) 40 VDC (maximum line voltage) 12 to 24 VDC (nominal line voltage) Operating Temperature .......... 32° to 122°F (0° to 50°C), non-condensing Cooling ................................ Internal, thermostatically-controlled fan Humidity .............................. 10% to 80% Shock .................................. 30G/4ms half sine-wave (operating) 75G/11ms half sine-wave (non-operating) Vibration .............................. 0.67G (5-500 Hz) random RMS (operating) 1.04G (2-200 Hz) random RMS (non-operating) Storage and Handling Requirements ¡ Do not drop the containers. Shock .................................. 75G/11ms half sine-wave Vibration .............................. 1.04G (2-200 Hz) random RMS ¡ Store all containers in a dry, heated, non-condensing environment. Temperature......................... -4° to 158°F (-20° to 70°C) Humidity .............................. 5% to 95% ¡ 1-2 Store all containers away from splashing or sprayed moisture. 34701F TMC470 Installation & Maintenance 1.4 UNPACKING THE EQUIPMENT This section provides guidelines for receiving and unpacking the controller equipment. CAUTION If your equipment arrives during cold weather, allow the components to warm up for several hours before opening the containers. Exposing the equipment to room temperatures may cause condensation in the units. When your controller arrives, check the shipping cartons for damaged corners, holes through the cardboard, or any other signs of damage. Ask the delivery service to note any damage to the containers on the delivery receipt. Save all packing materials in case you need to return any components. Accounting for Equipment Check the materials against the packing list. Note any discrepancies to your delivery service and request that they note the discrepancies on the delivery receipt. The controller equipment consists of: • • • • • • • Controller Controller Power Cable * Connector Kit (spare fuses, mating I/O connectors & connector pins) Optional Wall Mounting Kit, Part No. 42477 (brackets and attaching hardware) Optional Panel Mounting Kit, Part No. 63150 (bezel, brackets, and attaching hardware) Optional TMC470N NEMA Enclosure, Part No. 66738 (enclosure, bezel, brackets, and attaching hardware) Additional components may be included with the controller. Specific information for optional equipment may be provided in a separate installation manual. Specific information for custom equipment may be provided in a custom addendum. * A power cable is provided with the TMC470 controller for connection to a 115 VAC 60 Hz power source. Inspecting for Damage Place the components on a table and inspect each one for damage. Report any damage to your delivery service immediately. ¡ Ensure the controller case is not cracked or otherwise damaged. ¡ Ensure the integrated display is not cracked, scratched, or damaged. ¡ Ensure the connectors and connector pins (on the back of the controller) are not bent or broken. ¡ Optional TMC470N NEMA enclosure: Ensure the toggle switch on side of enclosure is not damaged. Ensure the rubber cabinets seals in the cable access window on the back panel are intact and are not torn, damaged or missing. 34701F 1-3 TMC470 Installation & Maintenance 1.5 INSTALLATION REQUIREMENTS The following items are required for proper installation of the controller. NOTICE It is the responsibility of the installing agency to ensure the installation requirements are correctly implemented. • A dedicated, 10-amp, clean, conditioned-power, branch circuit must be provided for the marking system. • The controller should be visible from the marking head. Most standard marker cables are approximately 4m (13 ft.). • An electrical lockout switch must be installed if the controller is not visible from the marking head. • An emergency stop (E-STOP) switch must be installed if the controller cannot be easily reached from the marking head. The switch must interrupt inlet power to the controller. • Systems that will use 230 VAC require a controller power cable that matches the source power outlet. The cable must be supplied by the customer. • Power for remote I/O signals be supplied by the customer and must comply with I/O signal limitations. Refer to Specifications for details. • Data cables to connect the controller with a remote I/O device or host computer must be supplied by the customer and must comply with cable requirements. Refer to Data and Electrical Connections for details. • The controller should not be exposed to sprays, solvents, chemicals, or other contaminants. • Do not place the controller in an area where flammable mists or fumes are present. • Allow enough space around the controller to permit adequate ventilation and to facilitate access to the interface panel for electrical connections. See Figure 1-2 for unit dimensions and surrounding clear space envelope. • Do not block the vents on the sides of the controller. • Contaminants. The vented TMC470 is rated NEMA 1 (IP30) and contains a thermostatically-controlled, variable speed fan. Accordingly, in environments where solid and/or liquid contaminants are present, the possibility exists that these contaminants can be drawn into the TMC470 controller and possibly result in failure of a number of electronic components. For that reason, in these types of environments, the controller must be located in a sealed industrial enclosure. To facilitate such installations, Telesis offers optional kits for panel-mounting and enclosure-mounting. • EMI Susceptibility. Although the system has been found to be in compliance with pertinent susceptibility standards, care should be taken when installing near welders and other extreme generators of electromagnetic interference (EMI). Particular care should be taken to ensure welder currents are not injected through the marking head chassis. The marking head chassis is connected to the electrical service earth ground through the marking head cable. The marking head should be electrically isolated from all surfaces which could become part of a welder current path. 1-4 34701F TMC470 Installation & Maintenance Figure 1-2. TMC470 Table-top or Wall-Mounted Installation Drawing 34701F 1-5 TMC470 Installation & Maintenance 1.6 INSTALLATION PROCEDURES The TMC470 controller may be installed as a table-top unit, a wall-mounted unit, a panel-mounted unit, or an enclosuremounted unit. Refer to the appropriate procedures below for details. 1.6.1 Site Preparation ¡ Before beginning installation, refer to Installation Requirements and ensure all conditions for installation are satisfied. ¡ Ensure the marking head is installed before proceeding. Refer to the marking head Installation/Maintenance Manual for guidelines and procedures. CAUTION The TMC470 is not a sealed unit. Protect it from potentially damaging conditions and contaminants. Ensure the marking system is electrically isolated from any devices that may generate extreme electromagnetic interference (EMI). ¡ Select an appropriate location for the controller. Keep these points in mind when choosing a location. Ensure the controller will not be exposed to sprays, solvents, chemicals, moisture, dust, or other contaminants. The marking head should be visible from the controller. Ensure the distance between the controller and the marking head does not exceed the available cable length. Allow enough space around the controller to permit adequate ventilation and to facilitate access to the back panel for electrical connections. See Figure 1-2 for details. Do not block the vents on the bottom of the controller. ¡ Position the controller power switch (power entry module on back panel of controller) to OFF (O). ¡ Verify the controller fuse arrangement is correctly configured for the facility power (115 or 230 VAC). Remove the power supply cord from the power entry module on the controller back panel. Insert a very small, flat-tip screwdriver into the slot on the top of the power entry module cover. See Figure 1-3. Gently pry the cover open. Figure 1-3. Power Entry Module – Fuse Configurations 1-6 34701F TMC470 Installation & Maintenance 1.6.1 Site Preparation (continued) Pull the fuse holder out of the power entry module. Verify the fuse arrangement is c0rrectly configured for the facility power (115 or 230 VAC). 115 VAC systems • • • Ensure the metal clip is installed on one side of the fuse holder. See Figure 1-3. Ensure one fuse is installed in the fuse holder on the side opposite the clip Ensure the metal clip is oriented toward the top. 230 VAC systems • • • Ensure the metal clip has been removed from the fuse holder. See Figure 1-3. Ensure two fuses are installed in the fuse holder, one on each side. Ensure the fuses are installed in the inward-most position in the fuse holder (at the end where the clip would normally be installed). The fuses must be positioned away from the exposed end of the fuse holder. Slide the fuse holder into the power entry module. Close the power entry module cover. ¡ Proceed to Standard Table-top Installation, Optional Wall-mounted Installation, Optional Panel-mounted Installation, or Optional TMC470N NEMA Enclosure Installation, as applicable. 1.6.2 Standard Table-top Installation ¡ Ensure Site Preparation is complete. ¡ Place the controller on a solid, sufficiently sturdy base. ¡ Proceed to Data and Electrical Connections. 1.6.3 Optional Wall-mounted Installation ¡ Ensure Site Preparation is complete. ¡ Locate the optional wall mounting kit # 42477. ¡ Carefully, lay the controller face down on a surface that will not damage the display screen. ¡ Remove the foam cushions from the controller’s four corner footpads to expose the mounting holes. ¡ Orient each bracket over its set of mounting holes with the larger flange down (closer to the controller) and the smaller flange outward (toward the edge of the controller). See Figure 1-4. ¡ Attach each bracket with two #6 self-tapping screws (provided). Tighten securely. ¡ Drill the mounting surface for attaching the brackets. See Figure 1-2 for hole locations and dimensions. ¡ Attach the controller/bracket assembly to mounting surface with four M4 pan head screws (provided) or with suitable, customer-supplied hardware. Tighten securely. ¡ Proceed to Data and Electrical Connections. Figure 1-4. Proper Wall-mount Bracket Orientation 34701F 1-7 TMC470 Installation & Maintenance 1.6.4 Optional Panel-mounted Installation The optional panel-mount kit (63150) is designed to mount the TMC470 Controller to a customer-supplied panel or a customer-supplied enclosure. Additionally, the kit is used to mount the controller into a Telesis TMC470N NEMA enclosure. The panel-mount kit contains the following components. Please locate and identify these parts before installing the equipment. Table 1-1. Optional TMC470 Panel Mount Kit (63150) Part No. Description Qty. 63151 Bezel, TMC470 1 63149 Gasket, TMC470, Face to Bezel, Inner 1 63148 Gasket, TMC470, Bezel to Mounting Surface 1 63866 Bar Clamping, Middle, TMC470 Enclosure 1 63867 Rod, Threaded, M3x3" 6 24153 Nut, Hex Kepsnut, M3 (Tooth Washer) 12 62933 Bracket, Mounting, TMC470 2 14634 Screw, Pan Head, Phillips, M3-0.50 x 8mm 10 17637 Screw, Pan Head, Phillips, B Self Tap, #6 X 3/8" 4 Attaching the Mounting Brackets ¡ Carefully, lay the controller face down on a surface that will not damage the display screen. ¡ Remove the foam cushions from the controller’s four corner footpads to expose the mounting holes. See Figure 1-5. CAUTION Mounting the brackets incorrectly will block air flow and may damage the controller or cause the unit to shutdown abnormally. ¡ Orient each bracket over its set of mounting holes with the larger flange facing inward (over the footpads) and the smaller flange outward (toward the edge of the controller). See Figure 1-5. ¡ Attach each bracket using two #6 x 3/8" selftapping screws. Tighten securely. ¡ Proceed to Installing the Bezel Gaskets. Figure 1-5. Mounting Bracket Orientation 1-8 34701F TMC470 Installation & Maintenance Installing the Bezel Gaskets ¡ Locate two gaskets provided with the mounting kit. ¡ The Bezel-to-Mounting Surface gasket (63148) has pre-punched holes. It is to be applied to the back side of the bezel along the perimeter. See Figure 1-6. Apply as follows: • • • • ¡ Remove the paper cover to expose the adhesive. Orient the adhesive side of gasket toward the bezel. Align the gasket holes with the holes along the perimeter of the bezel. Press gasket evenly around the bezel perimeter. The Face-to-Bezel gasket (63149) has no holes. It is to be applied to the recessed area on the back side of the bezel. See Figure 1-6. Apply as follows: • • ¡ Center the gasket over the bezel opening with the wider edge of the gasket toward the top of the bezel. The gasket should extend approximately 1/8 inch beyond the entire inside edge of the bezel opening. Proceed to Attaching the Mounting Bezel. Figure 1-6. Gasket Orientation 34701F 1-9 TMC470 Installation & Maintenance Attaching the Mounting Bezel NOTICE The following step is not necessary if using the Telesis-supplied TMC470N Enclosure. The cutout and mounting holes are already provided in the TMC470N Enclosure. ¡ Prepare the customer-supplied panel or customer-supplied enclosure for controller installation. • • • ¡ See Figure 1-9 for dimensions and locations. Cut out an area in the panel (or enclosure) for controller insertion. Drill mounting holes around the perimeter of the cutout. Access the backside of the mounting panel (or the inside of the enclosure). Note: If using the Telesis TMC470N enclosure, you may need to loosen the two quick-lock screws on the front side of the lid to open it. ¡ Orient the bezel on the front side of the panel (or enclosure) with the wider edge toward the top. See Figure 1-7. Figure 1-7. Mounting Bracket Orientation ¡ From the back side of the panel (or enclosure), attach the bezel using ten M3 pan head screws. See Figure 1-8 for screws locations. Torque to 10 in-lb (1.12 N-m) max. ¡ Locate the six remaining mounting holes drilled in the panel (or enclosure). ¡ From the back side of the panel (or enclosure), install one threaded rod in each remaining mounting hole until it bottoms out in the bezel. ¡ Secure each threaded rod with a locking hex nut. Torque to 10 in-lb (1.12 N-m) max. ¡ Proceed to Attaching the Controller. Figure 1-8. Panel (or Enclosure) Mounting Surface 1-10 34701F TMC470 Installation & Maintenance Figure 1-9. TMC470 Panel-mounted Installation Drawing 34701F 1-11 TMC470 Installation & Maintenance Attaching the Controller ¡ Access the backside of the mounting panel (or the inside of the enclosure). Note: If using the Telesis TMC470N enclosure, you may need to loosen the two quick-lock screws on the front side of the lid to open it. ¡ Orient the controller on the backside of the panel (or inside if the enclosure) as follows. See Figure 1-10. • • controller display/keyboard facing outward controller connectors toward the top of panel or enclosure. Note: If using the Telesis TMC470N enclosure, orient the controllers toward the hinged edge of the enclosure lid. ¡ Align the holes in the mounting flanges with the four threaded rods near the corners of the mounting bezel. ¡ Secure the controller using one M3 locking hex nut on each threaded rod. Torque to 10 in-lb (1.12 N-m) max. ¡ Position the clamping bar across the back of the controller and align the mounting holes with the two remaining threaded rods. See Figure 1-10. ¡ Secure the clamping bar using one M3 locking hex nut on each threaded rod. Torque to 10 in-lb (1.12 N-m) max. ¡ Complete the TMC470 installation as follows: If the controller is installed in a customer-supplied panel or a customer-supplied enclosure, proceed to Data and Electrical Connections. If the controller is installed in a Telesis TMC470N enclosure, proceed to Optional TMC470N NEMA Enclosure Installation. Figure 1-10. Controller Orientation and Hardware Locations 1-12 34701F TMC470 Installation & Maintenance 1.6.5 Optional TMC470N NEMA Enclosure Installation The optional TMC470N NEMA Enclosure (66738) is designed to protect the TMC470 Controller in environments where solid and/or liquid contaminants are present. This sealed, industrial enclosure inhibits these contaminants from being drawn into the controller. The controller is attached to a mounting bezel, which in turn is mounted to the enclosure. Two quick-lock screws allow the enclosure lid to be opened to access the controller for maintenance and service. A cabinet seal module on the back side of the enclosure allows cables to be routed to and from the controller without compromising the integrity of the enclosure. Figure 1-11. TMC470N NEMA Enclosure NOTICE Typically, new marking systems that use a TMC470N NEMA enclosure are shipped to the customer with the controller already installed in the enclosure. However, if a TMC470N enclosure is being added to a customer’s existing system, you must install the controller into the enclosure before proceeding. ¡ If the controller is already installed in the TMC470N enclosure, skip the next step. ¡ If the controller is not yet installed in the TMC470N enclosure, proceed as follows: Refer to Panel-mounted Installation for instructions on mounting the controller in the enclosure. After the controller is mounted, proceed with the following steps to install the enclosure. ¡ Ensure Site Preparation is complete. ¡ Position the toggle switch on the side of the enclosure to OFF (O). ¡ Loosen two hold-down screws that secure the enclosure lid. Open the lid to access the controller. ¡ Position the controller power switch (power entry module on back panel of controller) to OFF (O). continued on next page… 34701F 1-13 TMC470 Installation & Maintenance Optional TMC470N NEMA Enclosure Installation (continued) ¡ Confirm the controller fuse arrangement is correctly configured for the facility power (115 or 230 VAC). NOTICE The power entry module may be configured for a line voltage of either 115 VAC or 230 VAC. Systems using 115 VAC power require one fuse. Systems using 230 VAC require two fuses since both sides of the incoming voltage are not at ground potential. Refer to Replacement Procedures for information on controller fuses and configuring the power module. ¡ Inside the enclosure, locate the cabinet seal module near the bottom, center of the back panel. Note: The cabinet seal module is where the interface cables will enter the enclosure. The module consists of several rubber grommet blocks and an expansion plug that holds the grommets in place. ¡ In the cabinet seal module, loosen (but do not remove) the single hex nut in the expansion plug. CAUTION Be careful to not damage the rubber grommets when removing them from the cabinet seal module. ¡ Working from the outside of the cabinet, press the rubber grommet blocks inward (into the enclosure) to remove them from the cabinet seal module. Note: Retain the rubber grommet blocks. They will be re-installed after all interface connections are made. ¡ Continue with procedures for Free-standing Configuration or Base-mount Configuration, as applicable. Free-standing Configuration ¡ If the controller is to be used in a free-standing, table-top configuration, place the controller on a solid, sufficiently sturdy base. ¡ Loosen two hold-down screws that secure the enclosure lid. Open the lid to access the controller. ¡ Proceed to Electrical and Data Connections. 1-14 34701F TMC470 Installation & Maintenance Optional TMC470N NEMA Enclosure Installation (continued) Enclosure Base-mount Configuration As shipped, the enclosure is configured with footpads installed on the bottom of the unit. Optionally, you can re-configure the enclosure so that the unit may be secured to the mounting surface. ¡ Carefully, turn the enclosure over to access the footpads on the bottom of the unit. ¡ Remove the four footpads from the enclosure. ¡ Locate the optional mounting kit (P/N 41192) supplied with the enclosure. ¡ Position one bracket at each footpad mounting location. Attach brackets with four screws (provided). ¡ Drill the mounting surface for attaching the brackets. See Figure 1-12 for hole dimensions. ¡ Attach the enclosure/controller assembly to the surface with suitable (customer-supplied) hardware. ¡ Loosen two hold-down screws that secure the enclosure lid. Open the lid to access the controller. ¡ Proceed to Electrical and Data Connections. Figure 1-12. TMC470N NEMA Enclosure Installation Drawing 34701F 1-15 TMC470 Installation & Maintenance 1.7 DATA AND ELECTRICAL CONNECTIONS CAUTION The controller is shipped with electrostatic covers installed on the back panel connectors. Leave the covers installed on those connectors that will not be used. This will help to prevent electrostatic discharge (ESD) problems. Never connect or disconnect the Marker cable or the Auxiliary Axis cable while controller power is ON. Damage to the equipment will occur. The back panel of the TMC470 controller provides the following ports for connections to facility power, the marking head, and optional, remote input/output devices. Required Connections: • Power Entry Module • Marker Port Optional Connections: • Auxiliary Axis Port • TTL Port • Comm 1 Port • Comm 2 Port • USB Port • Ethernet Port • I/O Port Power Entry Module provides a standard power plug, with ground, to connect to facility power. TMC470 controllers configured for 115 VAC 60 Hz power use a standard power cable (supplied with the controller). Systems configured for 230 VAC require a power cable that matches the source power outlet and must be must be supplied by the customer. Refer to Power Connection for details. Marker Port provides a DB37S connector for connecting the marking head using the marker cable (provided). Refer to Marker Connection for details. (optional) Auxiliary Axis Port is available only if the controller has the optional Auxiliary Axis board installed. This port provides a DB37S connector for connecting optional auxiliary axis equipment. Optional axis components include the Z-axis electromechanical tool post and the Theta-axis rotary drive unit. Refer to Auxiliary Axis Connection for details. TTL Port provides a DB9S connector for connecting a remote push button device to start/stop print operations. Unless the device is supplied by Telesis, the customer/installer must supply the mating connector, cabling, and switches. Refer to TTL Connection for details. Comm 1 Port provides a DB9P connector for connecting an RS232 device such as a host computer, remote terminal, or bar code scanner. This port is used to transmit data, select patterns for printing, and control marker operation. Optionally, the Comm 1 Port may be configured to support RS485 communications for networking multiple controllers to a single host. Refer to Comm1 / Comm 2 Connections for details. Comm 2 Port provides a DB9P connector for connecting an RS232 device such as a host computer, remote terminal, or bar code scanner. This port is used to transmit data, select patterns for printing, and control marker operation. Refer to Comm1 / Comm 2 Connections for details. USB Port is provided for connecting a USB flash drive to backup or transfer data. Ethernet Port provides a standard RJ45 connector for connecting a CAT5 cable from a TCP/IP network. This port may be used to connect to a TCP/IP network. Refer to Ethernet Connection for details. I/O Port provides a DB26P connector for connecting a remote I/O device such as a programmable logic controller (PLC). The I/O device can remotely start or stop the marking cycle and may remotely select and load patterns. Output signals from the marker may be transmitted to the I/O device to report system status. Refer to Remote I/O Connection for details. 1-16 34701F TMC470 Installation & Maintenance NOTICE For TMC470N NEMA enclosure installations, route the electrical and data cables through the cabinet seal module (on the back panel of the enclosure). The rubber grommets will be installed in the cabinet seal module later in this procedure after all electrical and data connections have been made. 1.7.1 Marker Connection This is a required connection. ¡ Ensure the controller power switch (power entry module on back panel of controller) is OFF (O). ¡ Connect the marker cable from the marking head to the Marker Port [ ] on the controller. ¡ Proceed with Power Connection. 1.7.2 Power Connection This is a required connection. The TMC470 may be configured for use with 115 VAC or 230 VAC power. Refer to the appropriate section below. 115 VAC Systems For Table-top, Wall-mount, or Panel-mount Installations: Ensure the controller power switch (power entry module on back panel of controller) is OFF (O). Connect the controller power cable only to the receptacle in the power entry module. Do not connect the power cable to facility power at this time. Proceed with optional connections, as applicable. If finished with all data and electrical connections, proceed to Controller Checkout. For All TMC470N NEMA Enclosure Installations: Obtain a power cable that has a compatible connector for the facility power outlet. The controller-end of the power cable need not be terminated with a connector. DO NOT CONNECT the power cable to facility power. Connect the power cable ONLY to the terminal strip inside the enclosure, as follows: Connect the HOT wire from the power cable to terminal strip connection L. Connect the NEUTRAL wire from the power cable to terminal strip connection N. Connect the GND wire from the power cable to terminal strip connection G. Proceed with optional connections, as applicable. If finished with all data and electrical connections, proceed to TMC470N NEMA Enclosure – Cabinet Seal. 34701F 1-17 TMC470 Installation & Maintenance 230 VAC Systems For Table-top, Wall-mount, or Panel-mount Installations: Ensure the controller power switch (power entry module on back panel of controller) is OFF (O). Obtain or fabricate a power cable that has compatible connectors for both the facility power outlet and the receptacle in the controller power entry module. Connect the power cable only to the receptacle in the controller power entry module. Do not connect the power cable to facility power at this time. Proceed with optional connections, as applicable. If finished with all data and electrical connections, proceed to Controller Checkout. For All TMC470N NEMA Enclosure Installations: Obtain a power cable that has a compatible connector for the facility power outlet. The controller-end of the power cable need not be terminated with a connector. DO NOT CONNECT the power cable to facility power. Connect the power cable ONLY to the terminal strip inside the enclosure, as follows: Connect the L1 wire from the power cable to terminal strip connection L. Connect the L2 wire from the power cable to terminal strip connection N. Connect the GND wire from the power cable to terminal strip connection G. Proceed with optional connections, as applicable. If finished with all data and electrical connections, proceed to TMC470N NEMA Enclosure – Cabinet Seal. 1.7.3 Auxiliary Axis Connection This is an optional connection. Auxiliary axis components include the vertical (Z-axis) tool post and the rotational (Theta-axis) drive unit. ¡ Ensure the controller power switch (power entry module on back panel of controller) is OFF (O). ¡ Refer to the Auxiliary Axis Installation Supplement (supplied with the optional equipment) to install the auxiliary axis components. ¡ Connect cable #25209 from the auxiliary axis equipment to the Auxiliary Axis Port [ on the controller. ] ¡ Proceed with other optional connections, as applicable. ¡ If finished with all data and electrical connections: For table-top, wall-mount, or panel-mount installations, proceed to Controller Checkout. For all TMC470N NEMA enclosure installations, proceed to TMC470N NEMA Enclosure – Cabinet Seal. 1-18 34701F TMC470 Installation & Maintenance 1.7.4 TTL Connection This is an optional connection. The TTL Port allows you to start and/or stop printing operations using a simple contact closure. Figure 1-13 shows a simple contact closure circuit for remote START PRINT and STOP input signals. ¡ Obtain a Telesis-supplied TTL device. or ¡ Fabricate an appropriate contact closure circuit for the TTL interface. The customer/installer must supply the mating connector, switches, and cabling. See Figure 1-13 for cable specifications, construction, and connections. ¡ Ensure the remote TTL device is OFF. ¡ Connect the data cable from the remote device to the TTL Port [ ] on the controller. ¡ Proceed with other optional connections, as applicable. ¡ If finished with all data and electrical connections: For table-top, wall-mount, or panel-mount installations, proceed to Controller Checkout. For all TMC470N NEMA enclosure installations, proceed to TMC470N NEMA Enclosure – Cabinet Seal. Figure 1-13. TTL Connections 34701F 1-19 TMC470 Installation & Maintenance 1.7.5 Comm 1 / Comm 2 Connections This is an optional connection. The Comm 1 Port may be configured for use with an RS232 or RS485 device using Programmable or Extended Protocol. The Comm 2 Port may be used only with an RS232 device using only Programmable Protocol. ¡ Obtain or fabricate the appropriate data cable. For connections to DTE devices (see Figure 1-14), use Telesis cable Part No. 20799 or obtain a standard PC-to-PC cable with one DB9S connector and one suitable connector to mate with the host. For connections to DCE devices or to RS485 devices, the customer/installer must supply the mating connectors and cabling and must fabricate an appropriate data cable for the host interface. See Figure 1-14 for RS232 cable specifications, construction, and connections. See Figure 1-15 for RS485 cable specifications, construction, and connections. ¡ Ensure the host device is OFF. ¡ Connect the data cable from the host to the ] or Comm 2 Port [ ], Comm 1 [ as applicable. ¡ Proceed with other optional connections, as applicable. ¡ If finished with all data and electrical connections: For table-top, wall-mount, or panel-mount installations, proceed to Controller Checkout. For all TMC470N NEMA enclosure installations, proceed to TMC470N NEMA Enclosure – Cabinet Seal. Table 1-2. Comm 1 Port – Pin Assignments Table 1-3. Comm 2 Port – Pin Assignments PIN SIGNAL 1 X– RS485 bi-directional data – 1 2 RXD Receive Data (to controller) 2 RXD Receive Data (to controller) 3 TXD Transmit Data (from controller) 3 TXD Transmit Data (from controller) RS485 bi-directional data + 4 +5VDC Signal Ground 5 GND 4 X+ 5 GND 6* T+ 7 8 9* X– DESCRIPTION PIN SIGNAL DESCRIPTION not used power for optional bar code scanner Signal Ground RS485 Terminator + 6 not used ( internal jumper to pin 8 ) ** 7 ( internal jumper to pin 8 ) ** ( internal jumper to pin 7 ) ** 8 ( internal jumper to pin 7 ) ** RS485 bi-directional data – 9 not used ** Refer to RS485 Interface for important information on jumper installation and proper network termination. ** The TMC470 Controller does not use hardware handshaking. It does, however, provide an internal jumper between pin 7 and pin 8 for RTS – CTS signals. The marking system software allows you set parameters for the controller to communicate with the host interface. The hardware type (RS232 or RS485) and the protocol for the marking system must match the serial device with which it is communicating. To provide maximum flexibility, the system software offers Extended Protocol and Programmable Protocol. Each interface option (RS232 and RS485) and each protocol are described later in this section. 1-20 34701F TMC470 Installation & Maintenance RS232 Interface The RS232 interface is most often used with remote devices such as host computers, terminals, or bar code scanners. • • Using the Comm 1 Port, the RS232 interface may use Extended Protocol or Programmable Protocol. Using the Comm 2 Port, the RS232 interface may us only Programmable Protocol. The Telesis protocols are briefly described later in this section and fully detailed in the TMC470 Controller Operation Manual. The system supports XON/XOFF handshaking. When the system is unable to accept serial transmissions, it transmits the XOFF character. When the serial port is available, XON is transmitted. Similarly, if the serial port receives an XOFF signal while transmitting, the transmission is suspended until an XON is received. Figure 1-14 shows connections to both DTE (data terminal equipment) and DCE (data circuit-terminating) devices. Figure 1-14. RS232 Cable Diagrams 34701F 1-21 TMC470 Installation & Maintenance RS485 Interface The TMC470 Controller provides a half Duplex RS485 interface. This interface is normally used when communicating over long transmission distances or when several markers are networked. The RS485 interface is required in multi-drop network applications. NOTICE Since RS485 communications transmit and receive signals on the same line, a delay is required to manage the signal traffic. A delay allows time for the port to switch from receive-mode to transmit-mode, and vice versa. The TMC470 software provides a parameter to define the time delay. Refer to the TMC470 Controller Operation Manual (see Host Communication Properties) for details on setting the 485 RxÆTx Delay parameter. Set the parameter, as required, to match the customer-supplied RS485 device. When using an RS485 interface, you must use the Comm 1 Port and Telesis Extended Protocol. Some communications devices use RS422 and connect the transmit and receive signals together. If these devices are used, the installer must ensure the transmitter is turned OFF when the device is not transmitting. When multiple markers are used in a multi-drop network, each one must be assigned a unique Station ID number. The Station ID is used by the communications protocol to direct messages to a specific marker. Refer to the TMC470 Controller Operation Manual for details on configuring the Station ID software parameter. Figure 1-15 shows sample connections where several controllers are networked to a single host. • The Comm 1 Port mating connector must use a jumper across pins 6 and 9 on the Comm 1 Port mating connector. The jumper places a 220 ohm resistance across the X+ and X– signals to ensure proper network termination. • If more than one controller is used, install only one jumper for the entire network of controllers. See Figure 1-15. Specifically, jumper pins 6 and 9 on the Comm 1 Port mating connector on the last controller of the network. 1-22 34701F TMC470 Installation & Maintenance Figure 1-15. RS485 Connections for Networked Markers 34701F 1-23 TMC470 Installation & Maintenance Programmable Protocol Programmable Protocol is used to communicate with devices where one-way communication is required, such as with bar code scanners. It provides no error checking or acknowledgment of the transmitted data. The Programmable Protocol parameters define which characters to extract from the data transmission and how to employ them during the marking operation. Refer to the TMC470 Controller Operation Manual for details on using Programmable Protocol. NOTICE The host message may contain ASCII characters that define the Start, Terminating, and Ignore characters within the transmitted data. To identify these ASCII characters, you must specify their decimal equivalents when setting up the following parameters. Refer to the ASCII Cross Reference table in Appendix A to view decimal and hexadecimal equivalents of ASCII characters. Extended Protocol Extended Protocol provides two-way communication with error checking. It is designed to provide secure communications with an intelligent host device using pre-defined message formats, response formats, and message types. It also provides hand-shaking to detect faults in the transmitted messages, effectively verifying that the data is properly received. You must use Extended Protocol to communicate with an RS485 device. Extended Protocol also allows for multidrop communications so that the multiple markers may be networked through a host computer. All communications are carried out in a master/slave relationship. Only the host has the ability to initiate communications. The marker communicates only in response. Refer to the TMC470 Controller Operation Manual for details on using Extended Protocol and for information on message format, response format, and block check codes (message verification). 1-24 34701F TMC470 Installation & Maintenance 1.7.6 Remote I/O Connection This is an optional connection. The I/O port is optically isolated. The I/O Port allows you to transmit I/O signals between the controller and a remote I/O device such as a programmable logic controller (PLC). The I/O device can remotely start or stop the marking cycle and may remotely select and load patterns. Output signals from the marker may be transmitted to the I/O device to report system status. Refer to VDC Input Connections, VDC Output Connections, Remote I/O Signal Timing, and Remote Pattern Selection (later in this section) for more information on using the I/O interface. ¡ Fabricate the appropriate data cable. The customer/installer must supply the mating connector, switches, cabling, and DC power source. See Figure 1-16 for VDC input cable specifications, construction, connections. See Figure 1-17 for VDC output cable specifications, construction, connections. ¡ Ensure the remote I/O device is OFF. ¡ Connect the data cable from the remote I/O source to ] on the controller. the I/O Port [ ¡ Proceed with other optional connections, as applicable. ¡ If finished with all data and electrical connections: For table-top, wall-mount, or panel-mount installations, proceed to Controller Checkout. For all TMC470N NEMA enclosure installations, proceed to TMC470N NEMA Enclosure – Cabinet Seal. Table 1-4. I/O Port – Pin Assignments PIN 1 SIGNAL DESCRIPTION INPUT COMM Common for all inputs (+ or – supply) 2 START PRINT Input: Begins a print cycle 3 STOP Input: Stops the print cycle 4 SELECT_0 Input – see Remote Pattern Selection for details 5 SELECT_1 Input – see Remote Pattern Selection for details 6 SELECT_2 Input – see Remote Pattern Selection for details 7 SELECT_3 8 SELECT_6 9 SELECT_4 10 SELECT_5 Input – see Remote Pattern Selection for details 11 SPARE_IN_1 Input – spare input signal for use with custom applications 12 SPARE_IN_2 Input – spare input signal for use with custom applications 13 SPARE_IN_3 Input – spare input signal for use with custom applications Input – see Remote Pattern Selection for details (1) 14-18 19 Input – see Remote Pattern Selection for details Input – see Remote Pattern Selection for details not used OUTPUT COMM Common for all outputs (+ or – supply) 20 DONE Output: Indicates print cycle is complete 21 READY Output: Indicates system is ready for Start Print signal 22 PAUSED Output: Indicates system is paused. 23 NO_FAULT (2) Output – ON indicates normal; OFF indicates fault condition 24 SPARE_OUT_1 Output – spare output signal for use with custom applications 25 SPARE_OUT_2 Output – spare output signal for use with custom applications 26 2 not used (1) The SEL_6 input may be configured to remotely select and load patterns or to remotely place the marker online. Refer to the TMC470 Controller Operation Manual (Startup, I/O Options) for details. (2) The NO_FAULT output is normal ON to indicate system is operational. It will remain ON during the print cycle. The signal will turn OFF if an over-temperature condition occurs in the controller. A print cycle cannot be initiated when this signal is OFF. 34701F 1-25 TMC470 Installation & Maintenance VDC Input Connections Figure 1-16 shows a simple contact closure circuit for remote VDC input signals. Figure 1-16. VDC Input Connections 1-26 34701F TMC470 Installation & Maintenance VDC Output Connections Figure 1-17 shows connections for the TMC470 output signals. To demonstrate differences in polarity, the graphic illustrates both sourcing outputs and sinking outputs. Figure 1-17. VDC Output Connections 34701F 1-27 TMC470 Installation & Maintenance Remote I/O Signal Timing The controller is configured at the factory to operate with 12-to-24 VDC I/O signals (nominal voltage). The I/O Port provides access to the marking cycle control circuit. Figure 1-18 illustrates the timing relationship of the three marking control signals (START PRINT, READY, and DONE). Figure 1-18. Input/Output Signals – Timing Diagram READY and DONE are used to determine when the marker is available. • The marker will acknowledge a START PRINT command only when READY and DONE are both high (ON). • When the marker receives a START PRINT command, both READY and DONE go low (OFF). • DONE will go high (ON) after printing is complete. DONE must be high (on) in order to select a pattern. • If READY is high (ON) during pattern selection, it will temporarily go low (OFF) until the pattern is loaded and the system ensures all conditions are okay to proceed. If possible, READY will then go high (ON). • READY will go high (ON) after the marker returns to the Park position, provided all parameters to continue printing are within limits (e.g., serial number limit is not exceeded and variable text fields* contain data). Note: If the Clear option is enabled for the variable text field(s) in a pattern, the system will clear the field(s) of data after printing. The READY signal will remain low (OFF) until all variable text fields contain data. • If the print cycle is stopped, DONE will go high (ON), but READY will remain low (OFF). 1-28 34701F TMC470 Installation & Maintenance Remote Pattern Selection The Remote Pattern Selection feature allows the system to monitor up to seven dedicated input signals transmitted from a remote, customer-supplied I/O device. These signals (SEL_6 through SEL_0) are received at the TMC470 I/O Port. The ON/OFF combinations of the seven input signals generate binary codes ranging from 0000000 (0) through 1111111 (127). Each code corresponds to specific reserved pattern name. As the seven input signals are received, the system interprets their codes, then loads the pattern with reserved pattern name associated with that code. Note that if all seven input signals are OFF, the resulting code is 0000000. This effectively disables the Remote Pattern Selection feature so the pattern may be loaded manually by the operator. Note that the SEL_6 input signal may be configured either to remotely select patterns stored in the controller or to remotely place the marker online. If configured for online usage, its ON/OFF state will be ignored during remote pattern selection. This will reduce the number of patterns available for remote selection from 127 to 63. If this feature is used, all patterns that will remotely selected and loaded must be stored in the controller using the following specific pattern names as listed below. Table 1-5. Reserved Pattern Names for Remote Pattern Selection Signal State Sel_ (n) 6543210 Reserved Pattern Name Signal State Sel_ (n) 6543210 Reserved Pattern Name Signal State Sel_ (n) 6543210 Reserved Pattern Name Signal State Sel_ (n) 6543210 Reserved Pattern Name 0000000 (disabled) 0I00000 PAT032 I000000 PAT064 II00000 PAT096 000000I PAT001 0I0000I PAT033 I00000I PAT065 II0000I PAT097 00000I0 PAT002 0I000I0 PAT034 I0000I0 PAT066 II000I0 PAT098 00000II PAT003 0I000II PAT035 I0000II PAT067 II000II PAT099 0000I00 PAT004 0I00I00 PAT036 I000I00 PAT068 II00I00 PAT100 0000I0I PAT005 0I00I0I PAT037 I000I0I PAT069 II00I0I PAT101 0000II0 PAT006 0I00II0 PAT038 I000II0 PAT070 II00II0 PAT102 0000III PAT007 0I00III PAT039 I000III PAT071 II00III PAT103 000I000 PAT008 0I0I000 PAT040 I00I000 PAT072 II0I000 PAT104 000I00I PAT009 0I0I00I PAT041 I00I00I PAT073 II0I00I PAT105 000I0I0 PAT010 0I0I0I0 PAT042 I00I0I0 PAT074 II0I0I0 PAT106 000I0II PAT011 0I0I0II PAT043 I00I0II PAT075 II0I0II PAT107 000II00 PAT012 0I0II00 PAT044 I00II00 PAT076 II0II00 PAT108 000II0I PAT013 0I0II0I PAT045 I00II0I PAT077 II0II0I PAT109 000III0 PAT014 0I0III0 PAT046 I00III0 PAT078 II0III0 PAT110 000IIII PAT015 0I0IIII PAT047 I00IIII PAT079 II0IIII PAT111 00I0000 PAT016 0II0000 PAT048 I0I0000 PAT080 III0000 PAT112 00I000I PAT017 0II000I PAT049 I0I000I PAT081 III000I PAT113 00I00I0 PAT018 0II00I0 PAT050 I0I00I0 PAT082 III00I0 PAT114 00I00II PAT019 0II00II PAT051 I0I00II PAT083 III00II PAT115 00I0I00 PAT020 0II0I00 PAT052 I0I0I00 PAT084 III0I00 PAT116 00I0I0I PAT021 0II0I0I PAT053 I0I0I0I PAT085 III0I0I PAT117 00I0II0 PAT022 0II0II0 PAT054 I0I0II0 PAT086 III0II0 PAT118 00I0III PAT023 0II0III PAT055 I0I0III PAT087 III0III PAT119 00II000 PAT024 0III000 PAT056 I0II000 PAT088 IIII000 PAT120 00II00I PAT025 0III00I PAT057 I0II00I PAT089 IIII00I PAT121 00II0I0 PAT026 0III0I0 PAT058 I0II0I0 PAT090 IIII0I0 PAT122 00II0II PAT027 0III0II PAT059 I0II0II PAT091 IIII0II PAT123 00III00 PAT028 0IIII00 PAT060 I0III00 PAT092 IIIII00 PAT124 00III0I PAT029 0IIII0I PAT061 I0III0I PAT093 IIIII0I PAT125 00IIII0 PAT030 0IIIII0 PAT062 I0IIII0 PAT094 IIIIII0 PAT126 00IIIII PAT031 0IIIIII PAT063 I0IIIII PAT095 IIIIIII PAT127 Note: Pattern names shaded in gray may be remotely selected only if the SEL_6 input is configured for pattern selection. Refer to the TMC470 Controller Operation Manual (Startup, I/O Options) for details. 34701F 1-29 TMC470 Installation & Maintenance 1.7.7 Ethernet/Merlin Connection This is an optional connection. This port may be used to connect the TMC470 Controller to a remote device or application over a TCP/IP network. Optionally, this may include connecting to the Telesis Merlin®III Visual Design Software, either over the network or directly to the computer running the Merlin III software. Table 1-6. Ethernet Port – Pin Assignments PIN SIGNAL 1 TXP DESCRIPTION Transmit Data + (bi-directional pair +A) 2 TXN Transmit Data – (bi-directional pair –A) 3 RXP Receive Data + (bi-directional pair +B) 4 TP45 (bi-directional pair +C) 5 TP45 (bi-directional pair –C) 6 RXN 7 TP78 Receive Data – (bi-directional pair +D) (bi-directional pair –B) 8 TP78 (bi-directional pair –D) There are several options when connecting the TMC470 to a computer running the Merlin III software. Option 1 Direct Connection Neither the computer nor the TMC470 are on a network. The TMC470 connects directly to the computer. Option 2 Direct Connection The computer is on a network, but the TMC470 is not. The TMC470 connects directly to the computer or to the computer through a switch. This requires the computer to have two (2) Ethernet ports – one for the network and one for the TMC470. Option 3 Network Connection Both the computer and the TMC470 are on the network. The TMC470 connects indirectly to the computer through a network hub or switch. While connected to the Merlin III software: ¡ The Merlin III interface (via the computer) provides complete operational control of the marking system. ¡ The TMC470 I/O Port remains functional for remote input/output signals. Refer to Remote I/O Connection for details. ¡ The PRINT key and the STOP (ABORT) key on the TMC470 keyboard remain functional. ¡ All other keys on the TMC470 keyboard are disabled. 1-30 34701F TMC470 Installation & Maintenance Perform the following steps to connect and configure the TMC470 Ethernet port. NOTICE If the TMC470 Controller will connect directly to the PC running the Merlin III software, you must use an Ethernet crossover adapter (or crossover cable) to connect the devices. If the TMC470 Controller will connect to the PC running the Merlin III software across a LAN (through a network hub or a network switch), you must contact your LAN administrator to obtain a Local IP Address for the controller. ¡ Obtain Connection Hardware You will need the following items to connect the TMC470 to the Merlin III software. • PC with Merlin III software installed • Standard CAT 5 Ethernet cable • Ethernet crossover adapter (if connecting directly to the PC) Note: Merlin III Kit P/N 66666 contains the following components. Merlin III Software CD P/N 64832, Qty. 1 CAT 5 Ethernet Cable (3m) P/N 66685, Qty. 1 Ethernet Crossover Adapter P/N 66689, Qty. 1 ¡ Connect the TMC470 Direct Connection Use these procedures if the TMC470 will connect directly to the PC running the Merlin III software. Turn the PC and TMC470 OFF. Connect the Ethernet crossover adapter to the Ethernet port [ Controller. ] on the back panel of the TMC470 Connect the CAT 5 Ethernet cable to the Ethernet crossover adapter. Connect the CAT 5 Ethernet cable to an available Ethernet port on the PC. Network Connection Use these procedures if the TMC470 will indirectly connect to the PC running the Merlin III software via a network hub or network switch. Turn the TMC470 OFF. Connect the CAT 5 Ethernet cable to the Ethernet port [ ] on the back panel of the TMC470 Controller. Connect the CAT 5 Ethernet cable to an available Ethernet port on the network hub or network switch. Contact your LAN administrator to obtain a Local IP Address for the TMC470 Controller. You will need this information to properly configure the TMC470 network parameters. ¡ Configure the TMC470 Ethernet parameters. Refer to the TMC470 Controller Operation Manual for details. See Ethernet/Merlin Communication Properties. ¡ Proceed with other optional connections, as applicable. ¡ If finished with all data and electrical connections: For table-top, wall-mount, or panel-mount installations, proceed to Controller Checkout. For all TMC470N NEMA enclosure installations, proceed to TMC470N NEMA Enclosure – Cabinet Seal. 34701F 1-31 TMC470 Installation & Maintenance 1.7.8 TMC420N NEMA Enclosure – Cabinet Seal This is a required procedure for installations that use the TMC420N NEMA enclosure. ¡ Ensure all electrical and data connections are complete before proceeding. ¡ Locate and examine the rubber grommet blocks that were removed from the cabinet seal module. Each block is made up of two halves. The blocks contain pre-cut, concentric rings that provide multiple layers of rubber sheeting. Each layer may be peeled off and removed to provide a custom fit around each cable that passes through the cabinet seal module. ¡ Separate the blocks and, for each cable, peel off the MINIMUM NUMBER OF LAYERS necessary to fit the cable in the block when the halves are reassembled. Do not remove any more layers of the rubber sheeting than necessary to provide a tight fit around the cable. ¡ Working from the inside of the enclosure, place the block halves around the cables and insert the rubber grommet blocks into the cabinet seal module. ¡ From the inside of the enclosure, press the blocks outward until the back edge of the blocks are flush against the outside edge of the cabinet seal module. ¡ Tighten the single hex nut in the expansion plug to seal the rubber grommets around the cables. ¡ Locate the power switch on the back panel of the controller (mounted in the lid of the enclosure). Position the power switch to ON ( I ). ¡ Carefully close the enclosure lid. Ensure the interior cables do not interfere with the rubber seal around the perimeter of the lid. ¡ Secure the enclosure lid by tightening the two hold-down screws. ¡ Proceed to Controller Checkout. 1.8 CONTROLLER CHECKOUT ¡ Once all data and electrical connections have been made, connect the controller power cable to facility power. ¡ Turn the controller on. Position the controller power switch (on power entry module) to ON ( I ). ¡ Confirm the marking system software starts and is displayed on the controller LCD screen. ¡ Auxiliary Axis Configuration. If the marking system will use the Z-axis or Theta-axis, you must setup parameters in the marking system software to enable and configure the axis. Refer to the TMC470 Controller Operation Manual. ¡ Host Interface Configuration. If the marking system uses a host interface (RS232, RS485, TCP/IP), you must setup parameters in the marking system software for the controller to communicate with the host. Refer to the TMC470 Controller Operation Manual for details on using and configuring the marking system software. ¡ TTL and Remote I/O Configuration. If the marking system uses a remote I/O device or remote TTL device, you should test the interface for proper operation. Refer to the TMC470 Controller Operation Manual for details on using and testing the marking system. ¡ Turn the controller off. Position the controller power switch (on power entry module) to OFF ( O ). ¡ Perform all other adjustments that may be required for the marking system. For details, refer to Installation Adjustments located in the marking head Installation/Maintenance Manual. 1-32 34701F TMC470 Installation & Maintenance Section 2 Maintenance 2.1 OVERVIEW This section provides troubleshooting, testing, repair, and replacement procedures for the TMC470 Controller. Any servicing, maintenance, or repair of the controller that is not explicitly contained in this document must be performed only by repair agencies authorized by Telesis Technologies, Inc. 2.2 MAINTENANCE PRECAUTIONS WARNING Turn all power OFF when performing maintenance on the controller. Ensure that all equipment energy sources are turned off or disconnected and that the switches are either locked or tagged while equipment is cleaned or serviced. The controller contains a lithium battery. Improper disposal of lithium batteries may cause an explosion. Always dispose of the lithium battery in a proper manner. 2.3 CLEANING PROCEDURES Perform the following steps to clean the controller. CAUTION Do not press on the LCD display nor apply heavy pressure to the keyboard. Be extremely careful not to scratch the LCD display or the membrane keyboard. Do not apply liquids directly to the controller. Apply liquid to cleaning cloth instead. Application of excessive liquid may enter the case and damage internal components. ¡ Remove electrical power from the marking system. ¡ Brush loose dust and debris from the controller. ¡ Ensure the fan inlet and vent outlet louvers (on the bottom of the controller) are not obstructed. Remove dust and debris as required. ¡ Apply isopropyl alcohol or mild, water-based solvent to a soft, clean, lint-free cloth. Wipe the case, keyboard, and LCD. 34701F 2-1 TMC470 Installation & Maintenance 2.4 TROUBLESHOOTING This section provides troubleshooting information for the controller. Refer to Table 2-1 to identify problems, their probable causes, and corrective action. If a defective component has been identified, refer to appropriate maintenance instructions to repair or replace the component. If these procedures fail to correct the problem, contact Telesis Customer Support. Table 2-1. Troubleshooting PROBLEM Controller not energized (no display) CORRECTIVE ACTION 1. Check power to the controller. 2. Ensure switch on controller power entry module is positioned ON. 3. Check the controller inlet fuse. Refer to Replacement Procedures. 4. verify proper fuse configuration. Refer to Replacement Procedures. 5. If no problem is found, contact Telesis Customer Support for assistance or contact a Telesis-authorized maintenance agency for repair. Serial communication fault 1. Ensure host is connected to proper controller port. 2. Check the communication cable. 3. Using the marking system software, display the Host Setup parameters and verify the parameters are properly configured. 4. Connect an RS232 diagnostic light box between the communication cable and the controller. Verify signals to and from the host computer are operating properly. Discrete I/O fault If the problem is an input fault, disconnect the I/O cable and verify the input voltages. Refer to Testing Procedures. If the problem is an output fault, disconnect the I/O cable and verify the output resistance. Refer to Testing Procedures. TTL Input fault Disconnect the I/O cable from the TTL Port and verify the resistance at the connector. Refer to Testing Procedures. Note: Resistance values are based on closed switches. Loss of system parameters or data after power is down 2-2 Contact Telesis Customer Support for assistance. 34701F TMC470 Installation & Maintenance 2.5 TESTING PROCEDURES This section provides reference tables for the connectors on the controller back panel. These tables include pin assignments, signal names, signal descriptions, and acceptable test values. 2.5.1 Comm 1 and Comm 2 Port Testing The following information is provided to check the Comm 1 and Comm 2 Ports. ¡ Remove electrical power from the marking system. ¡ Disconnect the interface cable from the Comm 1 or Comm 2 Port, as applicable. NOTICE Voltage measurements are to be taken with power ON. ¡ Apply electrical power to the marking system. ¡ Check for the appropriate signals at the Comm 1 or Comm 2 Port connector, as applicable. Refer to Table 2-2. Table 2-2. Comm Port Connectors COMM 1 PIN COMM 1 SIGNAL 1 X– 2 RXD Receive Data (to controller) 3 TXD Transmit Data (from controller) 4 X+ RS485 bi-directional data + (internal jumper to pin 6 through a 220 ohm resistor 6 T+ RS-485 Terminator + (internal jumper to pin 4 through a 220 ohm resistor DESCRIPTION RS485 bi-directional data (internal jumper to pin 9) 7 (internal jumper to pin 8) 8 (internal jumper to pin 7) 9 X– RS485 bi-directional data – (internal jumper to pin 1) COMM 2 PIN COMM 2 SIGNAL 2 RXD Receive Data (to controller) 3 TXD Transmit Data (from controller) 4 +5VDC DESCRIPTION Power for optional bar code scanner 7 (internal jumper to pin 8) 8 (internal jumper to pin 7) Note: Pin 5 is RS232 Signal Return (ground) on both Comm 1 and Comm 2. 34701F 2-3 TMC470 Installation & Maintenance 2.5.2 I/O Port Testing The I/O port is optically isolated. The following information is provided to check the discrete input and output signals at the I/O Port on the controller back panel. ¡ Remove electrical power from the marking system. ¡ Disconnect the interface cable from the I/O Port on the controller back panel. NOTICE All discrete I/O signals are to be checked in their ON state. For testing input signals, 12-24 VDC must be supplied from an external source. ¡ Apply electrical power to the marking system. ¡ Apply electrical power to the remote I/O source. ¡ Measure the resistance at the I/O Port connector. Refer to Table 2-3 for acceptable values. Table 2-3. I/O Port Connector PIN-to-PIN SIGNAL DESCRIPTION 1 to 2 START PRINT Input: Begins a print cycle 12 to 24 VDC 1 to 3 STOP Input: Stops the print cycle 12 to 24 VDC 1 to 4 SELECT_0 Input – see Remote Pattern Selection for details 12 to 24 VDC 1 to 5 SELECT_1 Input – see Remote Pattern Selection for details 12 to 24 VDC 1 to 6 SELECT_2 Input – see Remote Pattern Selection for details 12 to 24 VDC 1 to 7 SELECT_3 Input – see Remote Pattern Selection for details 12 to 24 VDC 1 to 8 SELECT_6 Input – see Remote Pattern Selection for details 12 to 24 VDC 1 to 9 SELECT_4 Input – see Remote Pattern Selection for details 12 to 24 VDC 1 to 10 SELECT_5 Input – see Remote Pattern Selection for details 12 to 24 VDC 1 to 11 SPARE_IN_1 Input – spare signal for use with custom applications 12 to 24 VDC 1 to 12 SPARE_IN_2 Input – spare signal for use with custom applications 12 to 24 VDC 1 to 13 SPARE_IN_3 Input – spare signal for use with custom applications 12 to 24 VDC 19 to 20 DONE Output: Indicates print cycle is complete 2 ohms (maximum) 19 to 21 READY Output: Indicates system ready for Start Print 2 ohms (maximum) 19 to 22 PAUSED Output: Indicates system is paused. 2 ohms (maximum) 2 19 to 23 NO_FAULT Output – ON indicates normal; OFF indicates fault condition 19 to 24 SPARE_OUT_1 Output – spare signal for use with custom applications 2 ohms (maximum) 19 to 25 SPARE_OUT_2 Output – spare signal for use with custom applications 2 ohms (maximum) Note: Pin 1 is Input Common for all input signals (+ or –) Pin 19 is Output Common for all output signals (+ or –) 2-4 ACCEPTABLE VALUE 34701F 2 ohms (maximum) TMC470 Installation & Maintenance 2.5.3 TTL Port Testing The following information is provided to check the input signals at the TTL Port on the controller back panel. ¡ Remove electrical power from the marking system. ¡ Disconnect the interface cable from the TTL Port on the controller back panel. NOTICE All TTL input signals are to be checked in their ON state. ¡ Apply electrical power to the remote I/O source. ¡ Measure the resistance at the TTL connector. Refer to Table 2-4 for acceptable values. Table 2-4. TTL Port Connector PIN-to-PIN SIGNAL DESCRIPTION ACCEPTABLE VALUE 2 to 3 START PRINT Input signal: Begins a print cycle 10 ohms (maximum) 2 to 4 STOP Input signal: Stops the print cycle 10 ohms (maximum) Note: Pin 2 is System Digital Ground (common) 34701F 2-5 TMC470 Installation & Maintenance 2.5.4 Marker Port Testing The following information is provided to check the signals at the Marker Port on the controller back panel. ¡ Remove electrical power from the marking system. ¡ Disconnect the marker cable from the Marker Port on the controller back panel. ¡ Take measurements at Marker Port connector. Refer to Table 2-5 for acceptable values. ¡ If any motor phase readings are higher than listed as acceptable, the controller internal fuses must be checked. If any motor phase readings are lower than listed as acceptable, contact Telesis Customer Support for service. Table 2-5. Marker Port Connector PIN-to-PIN SIGNAL DESCRIPTION 1 to 2 PHS 1A X-axis Motor Phase A 21.4K ohms ± 5% 3 to 4 PHS 1/B X-axis Motor Phase B 21.4K ohms ± 5% 5 to 6 PHS 2/A Y-axis Motor Phase A 21.4K ohms ± 5% 7 to 8 PHS 2/B Y-axis Motor Phase B 12 to 31 SOL DRV 1 Solenoid #1 Driver Diode Check place + lead on pin 12 0.55 volts DC 13 to 31 SOL DRV 2 Solenoid #2 Driver Diode Check place + lead on pin 13 0.55 volts DC 14 to 31 SOL DRV 3 Solenoid #3 Driver Diode Check place + lead on pin 14 0.55 volts DC 15 to 31 SOL DRV 4 Solenoid #4 Driver Diode Check place + lead on pin 15 0.55 volts DC 16 to 31 SOL DRV 5 Solenoid #5 Driver Diode Check place + lead on pin 16 0.55 volts DC 17 to 31 SOL DRV 6 Solenoid #6 Driver Diode Check place + lead on pin 17 0.55 volts DC 18 to 31 SOL DRV 7 Solenoid #7 Driver Diode Check place + lead on pin 18 0.55 volts DC 19 to 31 SOL DRV 8 Solenoid #8 Driver Diode Check place + lead on pin 19 0.55 volts DC 20 to 22 HOME MTR1 X-axis Motor Home place + lead on pin 22 9.4K ohms ±5% 20 to 25 HOME MTR2 Y-axis Motor Home place + lead on pin 25 9.4K ohms ±5% 20 to 26 TAG SENSE (unused signal) place + lead on pin 26 9.4K ohms ±5% 20 to 27 INTERLOCK (unused signal) place + lead on pin 27 9.4K ohms ±5% 20 to 29 /START Start Print place + lead on pin 29 9.4K ohms ±5% 20 to 33 X DIR Optional signal for custom use place + lead on pin 33 > 800K ohms 20 to 34 X STEP Optional signal for custom use place + lead on pin 34 > 800K ohms 20 to 35 Y DIR Optional signal for custom use place + lead on pin 35 > 800K ohms 20 to 36 Y STEP Optional signal for custom use place + lead on pin 36 > 800K ohms Note: Pins 21 and 24 are +5 VDC Pins 31 and 32 are +48 VDC Pins 9, 10, and 11 are Solenoid Common Pins 20, 23, 28, and 30 are +5 VDC Return Pin 37 is Chassis Ground 2-6 ACCEPTABLE VALUE 34701F 21.4K ohms ± 5% TMC470 Installation & Maintenance 2.5.5 Auxiliary Axis Port Testing The following information is provided to check the signals at the Auxiliary Axis Port on the controller back panel. NOTE: This connector is available only if the controller has the optional Auxiliary Axis board installed. ¡ Remove electrical power from the marking system. ¡ Disconnect the auxiliary axis cable from the Auxiliary Axis Port on the controller back panel. ¡ Take measurements at the Auxiliary Axis Port connector. Refer to Table 2-6 for acceptable values. ¡ If any motor phase readings are higher than listed as acceptable, the controller internal fuses must be checked. If any motor phase readings are lower than listed as acceptable, contact Telesis Customer Support for service. Table 2-6. Optional Auxiliary Axis Port Connector PIN-to-PIN SIGNAL DESCRIPTION ACCEPTABLE VALUE 1 to 2 PHS 1A Aux-axis 1 Motor Phase A typically Z-axis 21.4K ohms ± 5% 3 to 4 PHS 1/B Aux-axis 1 Motor Phase B typically Z-axis 21.4K ohms ± 5% 5 to 6 PHS 2/A Aux-axis 2 Motor Phase A typically Theta-axis 21.4K ohms ± 5% typically Theta-axis 21.4K ohms ± 5% PHS 2/B Aux-axis 2 Motor Phase B 22 to 20 7 to 8 HOME MTR1 Aux-axis 1 Motor Home place + lead on pin 22 9.4K ohms ±5% 25 to 20 HOME MTR2 Aux-axis 2 Motor Home place + lead on pin 25 9.4K ohms ±5% 33 to 20 X DIR Optional signal for custom use place + lead on pin 33 > 800K ohms 34 to 20 X STEP Optional signal for custom use place + lead on pin 34 > 800K ohms 35 to 20 Y DIR Optional signal for custom use place + lead on pin 35 > 800K ohms 36 to 20 Y STEP Optional signal for custom use place + lead on pin 36 > 800K ohms Note: Pins 21 and 24 are +5 VDC; Pins 31 and 32 are +48 VDC Pins 20, 23, 28, and 30 are +5 VDC Return Pin 37 is Chassis Ground 34701F 2-7 TMC470 Installation & Maintenance 2.6 REPLACEMENT PROCEDURES Replacement of controller components is limited to the power module inlet fuses. Any other component must be replaced by repair agencies authorized by Telesis Technologies, Inc. The power inlet fuses are located in the power entry module on the controller back panel. Systems using 115 VAC power require one fuse. Systems using 230 VAC require two fuses since both sides of the incoming line voltage are not at ground potential. Perform the following steps to remove and replace the controller fuses. ¡ Position the controller power on/off switch to OFF (O). ¡ Remove the power supply cord from the power entry module on the controller back panel. ¡ Insert a very small, flat-tip screwdriver into the slot on the top of the power entry module cover. See Figure 2-1. Gently pry the cover open. Figure 2-1. Power Entry Module / Fuse Holder Assembly 2-8 34701F TMC470 Installation & Maintenance ¡ Pull the fuse holder out of the power entry module. ¡ Remove and discard old fuse(s). Obtain replacement fuse(s). Refer to Table 2-7. Table 2-7. Controller Power Inlet Fuses ¡ POWER IN FUSE QUANTITY 115 VAC MDL-2 1 230 VAC GDC2A 2 Configure the fuse holder per facility-supplied power (115 or 230 VAC). 115 VAC systems Ensure the metal clip is installed on one side of the fuse holder. See Figure 2-1. Install one fuse in the fuse holder, on the side opposite of the clip. When installing the fuse holder, orient the metal clip toward the top. 230 VAC systems Remove the small metal clip from the fuse holder. See Figure 2-1. Install two fuses in the fuse holder, one on each side. Note that the fuses for 230 VAC systems are smaller in diameter and shorter in length. Ensure the fuses are installed in the inward-most position in the fuse holder (at the end where the clip would normally be installed). Fuses must be positioned away from the exposed end of the fuse holder. ¡ Slide the fuse holder into the power entry module. ¡ Close the cover. ¡ Connect the power supply cord to the power entry module the back panel of the controller. ¡ Position the controller power on/off switch to ON ( I ). 34701F 2-9 TMC470 Installation & Maintenance 2.7 REFERENCE DATA The following information will assist you in obtaining components to maintain the controller. 2.7.1 Replacement Parts To minimize down-time, you should keep an appropriate number of spare parts on-hand for quick replacement or substitution. Table 2-8. Spare Parts PART NO. 2-10 DESCRIPTION 42453 Controller Assembly, TMC470 20122 Fuse (115 VAC systems), Glass, MDL-2 ( one required ) 19443 Fuse (230 VAC systems), Glass, Time Delay, GDC2A ( two required ) 42477 Kit for Wall-mount Configuration 63150 Kit for Panel-mount Configuration 66738 Kit for Enclosure-mount Configuration (brackets and attaching hardware) (bezel, brackets, and attaching hardware) (enclosure, bezel, brackets, and attaching hardware) 34701F TMC470 Installation & Maintenance 2.7.2 Ordering Parts If you need parts for the marking system, be sure to specify the marking head model number and serial number when ordering. Telesis Customer Support also offers the following assistance. Phone Support Telesis Customer Support offers free phone support to answer questions during normal business hours. On-Site Service Telesis can send Customer Support professionals to your facility to perform equipment start-up, repair, maintenance, and training. Service Contracts As part of your Service Contract, you receive periodic maintenance and quick on-site customer support if a problem should occur. Factory Service Telesis Customer Support can repair defective parts in our factory to save you money. Contact Telesis at one of the following locations for more information on any of these services. If you need parts or service for your marking system, be sure to specify the equipment model number and serial number. Telesis Technologies, Inc. Corporate Headquarters 28181 River Drive P.O. Box 1000 Circleville, Ohio, USA 43113 +1 (740) 477 5000 +1 (800) 654 5696 (U.S. and Canada) +1 (800) 867 8670 (after hours) +1 (740) 477 5001 (fax) email: sales@telesistech.com email: technical_services@telesistech.com Telesis Worldwide Locations For contact information, please visit our website at: www.telesis.com 34701F 2-11 TMC470 Installation & Maintenance This page intentionally left blank. 2-12 34701F TMC470 Installation & Maintenance Appendix A ASCII Character Cross Reference Standard ASCII Characters This table may be convenient when devising communications between the controller and a host device. ASCII DEC HEX ASCII DEC HEX ASCII DEC HEX ASCII DEC HEX NULL 0 00 SPACE 32 20 @ 64 40 ' 96 60 ctrl A SOH 1 01 ! 33 21 A 65 41 a 97 61 ctrl B STX 2 02 " 34 22 B 66 42 b 98 62 ctrl C ETX 3 03 # 35 23 C 67 43 c 99 63 ctrl D EOT 4 04 $ 36 24 D 68 44 d 100 64 ctrl E ENQ 5 05 % 37 25 E 69 45 e 101 65 ctrl F ACK 6 06 & 38 26 F 70 46 f 102 66 ctrl G BEL 7 07 ' 39 27 G 71 47 g 103 67 ctrl H BS 8 08 ( 40 28 H 72 48 h 104 68 ctrl I HT 9 09 ) 41 29 I 73 49 i 105 69 ctrl J LF 10 0A * 42 2A J 74 4A j 106 6A ctrl K VT 11 0B + 43 2B K 75 4B k 107 6B Ctrl L FF 12 0C , 44 2C L 76 4C l 108 6C Ctrl M CR 13 0D - 45 2D M 77 4D m 109 6D ctrl N SO 14 0E . 46 2E N 78 4E n 110 6E ctrl O SI 15 0F / 47 2F O 79 4F o 111 6F ctrl P DLE 16 10 0 48 30 P 80 50 p 112 70 ctrl Q DC1 17 11 1 49 31 Q 81 51 q 113 71 ctrl R DC2 18 12 2 50 32 R 82 52 r 114 72 ctrl S DC3 19 13 3 51 33 S 83 53 s 115 73 ctrl T DC4 20 14 4 52 34 T 84 54 t 116 74 ctrl U NAK 21 15 5 53 35 U 85 55 u 117 75 ctrl V SYN 22 16 6 54 36 V 86 56 v 118 76 ctrl W ETB 23 17 7 55 37 W 87 57 w 119 77 ctrl X CAN 24 18 8 56 38 X 88 58 x 120 78 ctrl Y EM 25 19 9 57 39 Y 89 59 y 121 79 ctrl Z SUB 26 1A : 58 3A Z 90 5A z 122 7A ctrl [ ESC 27 1B ; 59 3B [ 91 5B { 123 7B ctrl \ FS 28 1C < 60 3C \ 92 5C | 124 7C ctrl ] GS 29 1D = 61 3D ] 93 5D } 125 7D ctrl ^ RS 30 1E > 62 3E ^ 94 5E ~ 126 7E ctrl _ US 31 1F ? 63 3F _ 95 5F DEL 127 7F 34701F A-1 TMC470 Installation & Maintenance Extended ASCII Characters Extended ASCII characters may be created using the Telesis Logo/Font Generator software. ASCII DEC HEX ASCII DEC HEX ASCII DEC HEX ASCII DEC HEX € 128 80 none 160 A0 À 192 C0 à 224 E0 none 129 81 ¡ 161 A1 Á 193 C1 á 225 E1 ‚ 130 82 ¢ 162 A2  194 C2 â 226 E2 ƒ 131 83 £ 163 A3 à 195 C3 ã 227 E3 „ 132 84 ¤ 164 A4 Ä 196 C4 ä 228 E4 … 133 85 ¥ 165 A5 Å 197 C5 å 229 E5 † 134 86 ¦ 166 A6 Æ 198 C6 æ 230 E6 ‡ 135 87 § 167 A7 Ç 199 C7 ç 231 E7 ˆ 136 88 ¨ 168 A8 È 200 C8 è 232 E8 ‰ 137 89 © 169 A9 É 201 C9 é 233 E9 Š 138 8A ª 170 AA Ê 202 CA ê 234 EA ‹ 139 8B « 171 AB Ë 203 CB ë 235 EB Œ 140 8C ¬ 172 AC Ì 204 CC ì 236 EC none 141 8D - 173 AD Í 205 CD í 237 ED none 142 8E ® 174 AE Î 206 CE î 238 EE none 143 8F ¯ 175 AF Ï 207 CF ï 239 EF none 144 90 ° 176 B0 Ð 208 D0 ð 240 F0 ‘ 145 91 ± 177 B1 Ñ 209 D1 ñ 241 F1 ’ 146 92 ² 178 B2 Ò 210 D2 ò 242 F2 “ 147 93 ³ 179 B3 Ó 211 D3 ó 243 F3 ” 148 94 ´ 180 B4 Ô 212 D4 ô 244 F4 • 149 95 µ 181 B5 Õ 213 D5 õ 245 F5 – 150 96 ¶ 182 B6 Ö 214 D6 ö 246 F6 — 151 97 · 183 B7 × 215 D7 ÷ 247 F7 ˜ 152 98 ¸ 184 B8 Ø 216 D8 ø 248 F8 ™ 153 99 ¹ 185 B9 Ù 217 D9 ù 249 F9 š 154 9A º 186 BA Ú 218 DA ú 250 FA › 155 9B » 187 BB Û 219 DB û 251 FB œ 156 9C ¼ 188 BC Ü 220 DC ü 252 FC none 157 9D ½ 189 BD Ý 221 DD ý 253 FD none 158 9E ¾ 190 BE Þ 222 DE þ 254 FE Ÿ 159 9F ¿ 191 BF ß 223 DF ÿ 255 FF A-2 34701F