2021 IEEE Applied Power Electronics Conference and Exposition (APEC) | 978-1-7281-8949-9/21/$31.00 ©2021 IEEE | DOI: 10.1109/APEC42165.2021.9487101 Design and Analysis of a High-frequency CLLC Resonant Converter with Medium Voltage insulation for Solid-State-Transformer Chunyang Zhao Center for Power Electronics Systems Virginia Polytechnic Institute and State University Blacksburg, USA chunyangz@vt.edu Yi-Hsun Hsieh Center for Power Electronics Systems Virginia Polytechnic Institute and State University Blacksburg, USA yhhsieh@vt.edu Abstract— The isolated DC/DC converter is the key component in high-frequency medium-voltage solid-state transformer. This paper presents a comprehensive design of a CLLC converter, including the design of transformer and resonant tank. The transformer insulation is designed to pass the partial discharge and applied voltage test. And its impact on transformer leakage inductance, as well as the resonant converter characteristic is discussed. Also, the transformer is optimized based on loss and volume trade-off. Then the relation of zero voltage switching (ZVS) condition and circuit parameters and load condition is derived from equivalent circuit. The impact of magnetizing inductance, leakage inductance, MOSFETs junction cap, and characteristic factor Q on ZVS condition is revealed. Finally, this paper provides a guidance to select deadtime appropriately and demonstrates the design on a 200kHz converter with 1.6kV input and 1.1kV output, and achieves a peak efficiency of 98.9%. Keywords—medium voltage insulation, resonant converter, ZVS commutation, I. INTRODUCTION Solid-State Transformer (SST) is gaining more and more interest in unconventional electrical applications, where loads and sources are directly connected to medium voltage utility grid. As shown in Fig. 1, High-power fast chargers for Electrical Vehicles (EV) and large data centers are examples that may benefit from direct isolated power conversion between medium voltage AC and low voltage DC [1]. Compared to a line-frequency transformer-based solution, the SST-based solution, especially the modularized SST system, is more suitable for these applications considering its size and weight advantage, flexible control and configuration, as well as easy installation and expansion [2]. Because of the high efficiency, simple structure achieved by magnetic integration, soft switching on both primary and secondary switches, the CLLC resonant converter topology has been widely employed as an isolated DC/DC converter [1]. In the DC/DC converter, Fred C. Lee Center for Power Electronics Systems Virginia Polytechnic Institute and State University Blacksburg, USA fclee@vt.edu Qiang Li Center for Power Electronics Systems Virginia Polytechnic Institute and State University Blacksburg, USA lqvt@vt.edu since the core of the transformer is grounded for safety consideration, there will be high voltage potential between the primary-side winding and the core, as well as the secondaryside winding, which is connected to the low voltage output. Thus, the insulation of the primary-side needs to be carefully designed. In paper [3][4], the insulation design of high frequency, medium voltage transformer is introduced. However, the impact of the insulation on transformer leakage inductance is not analyzed. To achieve Zero Voltage Switching (ZVS) in LLC or CLLC converters, the magnetizing inductance and dead-time selection usually follows a simplified equation [5][6][7]. However, this equation is based on some assumptions, which is not valid in every application, and cannot explain why the converter has a risk to lose ZVS when selecting a large magnetizing inductance and large dead-time. In this paper, the first section introduces an insulation design and analyzes its impact on transformer leakage inductance, as well as the impact on resonant converter characteristics. In the second section, the equivalent circuit model during the commutation is analyzed. The solution reveals the relationship between ZVS condition and many other circuit parameters, and provides a guide to select deadtime appropriately. At last, the design is demonstrated on a 200-kHz CLLC converter with 98.9% efficiency. Fig. 1. Examples of SST application This research is supported by the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, under the project of HighEfficiency, Medium-Voltage-Input, Solid-State-Transformer-Based 400kW/1000V/400A Extreme Fast Charger for Electric Vehicles, under contract number DE-EE0008361. 978-1-7281-8949-9/21/$31.00 ©2021 IEEE 1638 Authorized licensed use limited to: Infineon Technologies AG. Downloaded on March 06,2023 at 08:58:09 UTC from IEEE Xplore. Restrictions apply. frequency and core loss density, calculated transformer core loss, winding loss, and volume are plotted in Fig. 5. Since the litz wire is capsuled by the insulation material and it’s more difficult to dissipate the heat from the winding loss compared to core loss, a smaller winding loss is preferred, as the blue zone indicates in Fig. 5. Fig. 6 shows the trade-off between transformer volume and loss, as well as the preference of smaller winding loss for given fs and Pv. Fig. 7 shows the same trade-off with swept Pv. Finally, fs is swept from 100kHz to 300kHz and a design point is selected based on loss-volume tradeoff. Fig. 2. System structure of a fast EV charger II. MEDIUM VOLTAGE HIGH FREQUENCY TRANSFORMER DESIGN AND OPTIMIZATION A. Insulation Design Referring to previous study on high-frequency transformer design with high voltage insulation for SST, UI core is selected and both primary and secondary windings on the two legs are connected in series, as shown in Fig. 3 [8]. To avoid Partial discharge (PD) between the high voltage primary-side winding and the grounded core, as well as the secondary side winding which is connected to the low voltage output, the primary-side winding is encapsulated by silicon, and then coated by a grounded shielding layer. In this way, all the electric field around the high voltage winding will be constrained within the shielding layer and the high dielectric constant silicon will handle the E-field. Besides partial discharge, the applied voltage test is another requirement according to the standard [9]. And the thickness of the silicon capsule is determined by the highest voltage required by the applied voltage test. For given silicon material, the thickness can be calculated using (1): E/Eref = (Dref /d)0.4 Fig. 3. Medium voltage transformer structure Fig. 4. Simulation of E-field (1) Where E is the E-field strength in the insulation material, Eref is the dielectric strength at given thickness Dref, and d is the design parameter, the thickness of the insulation. Considering the viscosity, thermal conductivity, and dielectric strength, silicone material Wacker SilGel 612 is selected [8]. Fig. 4 shows the simulation result of the E-field. The peak E-field inside the insulation material of the primary side winding is less than 9 kilo volts per millimeter, which is below the dielectric strength of the selected material with enough margin. B. Optimization of Transformer Design According to previous analysis [8], and considering the frequency range of interest, 100kHz to 300kHz, ML27D is selected as the transformer core material. The litz wire strand AWG is selected according to the switching frequency and manufacture recommendation as well. After the insulation dimensions are determined, the transformer core loss, winding loss, and volume can be calculated for selected core material and litz wire [10]. By sweeping the primary side turns number N1, core loss density Pv, and switching frequency fs, an optimized design region is determined and design point is selected considering the tradeoff between loss and volume, as well as winding loss and core loss. For given switching Fig. 5. Transformer loss and volume with swept N1 Fig. 6. Transformer loss and volume tradeoff 1639 Authorized licensed use limited to: Infineon Technologies AG. Downloaded on March 06,2023 at 08:58:09 UTC from IEEE Xplore. Restrictions apply. such applications where bi-directional operation is required, whereas only forward operation mode needs regulation. According to the preference of the forward gain curve while still leaving margin for the resonant cap voltage stress, the transformer and resonant tank design is finalized. The design parameters are summarized and shown in TABLE I. Fig. 7. Transformer loss and volume tradeoff with swept N1 and Pv Fig. 9. Schematic of a CLLC resonant converter for the dc-dc module Fig. 8. Switching frequency impact on loss and volume trade-off C. Impact of Insulation on Leakage Inductance Fig. 9 illustrates the schematic of the CLLC resonant converter for the dc/dc stage. Serial half bridge topology is adopted on the primary side to handle high input voltage, and thus reducing the number of modules in the Solid-state transformer. The input is 1.6kV and output is 1.1kV. The transformer turns ration, n is 8:11. Lp and Ls represent the primary side and secondary side leakage inductance respectively. Due to the insulation on the primary side, the transformer has an asymmetrical structure of the primary and secondary side winding. As a result, the leakage inductance is not evenly distributed. The resonant caps of the CLLC converter are designed to match the primary side leakage and secondary side leakage inductance individually, as shown in (2). Fig. 10. Bidirectional gain curve of the CLLC resonant converter TABLE I. Parameter (2) The asymmetrical distribution of the leakage inductance has two significant impacts on the CLLC resonant converter. One is the voltage stress on the resonant caps and the other is the bidirectional gain curve. The voltage stress on each of the resonant caps is proportional to the capacitance, which means there will be huge difference of voltage stress between primary and secondary side resonant caps when the leakage inductances differ significantly. Also, due to the characteristic impedance on both sides are not equal, it will lead to different gain curves when the resonant converter is operating bi-directionally, as shown in Fig. 10. Such a characteristic could be beneficial in TRANSFORMER DESIGN RESULT Design Values Turns number 16:22 Core material ML27D Core loss density 300W/m3 Strands AWG 42 Equvialent AWG 15 Switching frequency 200kHz Core loss 39W Winding Loss 36W Transformer Volume 1.4L Primary side leakage inductance 16.8µH Secondary side leakage inductance 6.1µH III. ANALYSIS OF COMMUTATION For simplification, the analysis begins with a simple case of ZVS commutation, where primary-side and secondary-side MOSFETs Q1, Q4, SR1, and SR4 turn off simultaneously when the secondary side current reaches zero, as shown in Fig. 11. In this case, the equivalent circuit during the commutation period is shown in Fig. 12. CjQ is the junction cap of the primary side switch and CjSR’ is the junction cap of the secondary side switch reflected to the primary side. 1640 Authorized licensed use limited to: Infineon Technologies AG. Downloaded on March 06,2023 at 08:58:09 UTC from IEEE Xplore. Restrictions apply. the primary-side to achieve ZVS, and the easier for the secondary-side to achieve ZVS. Besides these dc components mentioned above, there is also a high frequency oscillation, which is determined by the two junction caps and two leakage inductances on each side. This oscillation will further reduce the primary side current after t1. From mathematics point of view, once the primary side current is reduced to zero, the primary side junction cap voltage reaches its valley point. This valley point has to be negative to guarantee ZVS of the primary side. Vice versa, primary side will lose ZVS. Equations (5) and (6) show the solution of the drain-source voltage of Q2 and SR2 respectively. Fig. 11. Gate signals and current waveform (5) Fig. 12. Equivalent circuit during commutation Ls’ is the secondary side leakage inductance reflected to the primary side. nVo is the output voltage reflected to the primary side. During the commutation period, since the resonant caps are much larger than the junction caps, they can be regarded as constant voltage sources, VCp and nVCs, and can be estimated by (3). (6) where ω is the resonant frequency of junction caps and leakage inductances defined by (7). (7) (3) Besides, since the magnetizing current im is almost constant during the commutation period, Lm can be replaced with a constant current source Ioff, which equals to the magnetizing current at t1, as shown in (4). (4) If consider the current source and voltage sources separately with superposition, the current source tends to discharge both primary and secondary side junction caps. And the equilibrium state would be the Ioff distributed on two sides proportional to the impedance of each branch. So the primary side current will begin to drop from t1. While the polarity of the voltage over the resonant cap, as shown in the equivalent circuit, indicates that it is against the primary-side ZVS commutation, and in favor of the secondary-side ZVS. Besides, this voltage is proportional to Q, which represents the load condition. Thus, the heavier the load is, the more difficult for The equivalent circuit and its solution also show that the commutation process is a combination of a linear term and two sinusoidal terms. The linear term is driven by the magnetizing current, and the sinusoidal terms represent the resonance between junction caps and leakage inductances, driven by both the voltage and current excitations. And the minimum value of the solved drain-source voltage will predict whether ZVS can be achieved or not. To be specific, the minimum value needs to be negative to guarantee ZVS. According to numerical study, the minimum value exists approximately at a quarter of the resonant period. Thus, it’s appropriate to select deadtime smaller than π/4ω, and the maximum Lm to realize ZVS while minimizing the circulating energy in resonant tank. IV. EXPERIMENTAL RESULT Fig. 13 shows the insulation test of the transformer prototype. It passed both the Applied Voltage test and the Applied Potential Partial Discharge test, for both primary side and secondary side. The transformer achieves an isolation level of 13.2kV. Then A 15 kW/200 kHz converter prototype is developed based on the high frequency isolated transformer, as shown in Fig. 14. The converter is tested from 30% to full load. In the whole range, ZVS can be achieved with a peak efficiency of 98.9%, as shown in Fig. 15 and Fig. 16. 1641 Authorized licensed use limited to: Infineon Technologies AG. Downloaded on March 06,2023 at 08:58:09 UTC from IEEE Xplore. Restrictions apply. V. CONCLUSION Fig. 13. Transformer insulation test CLLC resonant converter works as the most crucial element in the SST applications. The insulation design and transformer optimization are introduced. The impact on leakage inductance and resonant converter characteristics is discussed based on the transformer design. Then the ZVS commutation is analyzed with equivalent circuit. The derived equation shows the impact of magnetizing inductance, leakage inductance, junction cap and load condition, and also helps to select appropriate deadtime to achieve ZVS. Finally, a 15-kW 200-kHz CLLC resonant converter prototype is realized. A peak efficiency of 98.9% is achieved. REFERENCES [1] Fig. 14. CLLC resonant converter prototype Fig. 15. Key waveforms at full load operation Fig. 16. Measured efficiency at different load conditions Y. Jiao and M. M. Jovanović, "Topology Evaluation and Comparison for Isolated Multilevel DC/DC Converter for Power Cell in Solid State Transformer," 2019 IEEE Applied Power Electronics Conference and Exposition (APEC), 2019, pp. 802-809. [2] X. She, A. Q. Huang, R. Burgos, “Review of Solid-State Transformer Technologies and Their Application in Power Distribution Systems,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 1, no. 3, pp. 186-198, Sept. 2013. [3] Q. Chen, R. Raju, D. Dong and M. Agamy, "High Frequency Transformer Insulation in Medium Voltage SiC enabled Air-cooled Solid-State Transformers," 2018 IEEE Energy Conversion Congress and Exposition (ECCE), 2018, pp. 2436-2443. [4] T. Guillod, F. Krismer and J. W. Kolar, "Electrical shielding of MV/MF transformers subjected to high dv/dt PWM voltages," 2017 IEEE Applied Power Electronics Conference and Exposition (APEC), 2017, pp. 2502-2510. [5] Q. Zhu, L. Wang, L. Zhang and A. Q. Huang, "A 10 kV DC transformer (DCX) based on current fed SRC and 15 kV SiC MOSFETs," 2018 IEEE Applied Power Electronics Conference and Exposition (APEC), 2018, pp. 149-155. [6] S. Zhao, Q. Li, F. C. Lee and B. Li, "High-Frequency Transformer Design for Modular Power Conversion from Medium-Voltage AC to 400 VDC," in IEEE Transactions on Power Electronics, vol. 33, no. 9, pp. 7545-7557, Sept. 2018. [7] Z. U. Zahid, Z. M. Dalala, R. Chen, B. Chen and J. Lai, "Design of Bidirectional DC–DC Resonant Converter for Vehicle-to-Grid (V2G) Applications," in IEEE Transactions on Transportation Electrification, vol. 1, no. 3, pp. 232-244, Oct. 2015. [8] Z. Li, Y. Hsieh, Q. Li, F. Lee and M. Ahmed, "High-Frequency Transformer Design with High- Voltage Insulation for Modular Power Conversion from Medium-Voltage AC to 400-V DC," 2020 IEEE Energy Conversion Congress and Exposition (ECCE), 2020, to be published. [9] IEEE Standard for General Requirements for Dry-Type Distribution and Power Transformers, IEEE Standard C57.12.01-2015 (Revision of IEEE Standard C57.12.01-2005), 2015. [10] C. R. Sullivan, "Optimal choice for number of strands in a litz-wire transformer winding," IEEE Transactions on Power Electronics, vol. 14, no. 2, pp. 283-291, 1999. 1642 Authorized licensed use limited to: Infineon Technologies AG. Downloaded on March 06,2023 at 08:58:09 UTC from IEEE Xplore. Restrictions apply.