PROJECT DRAWING M6.02G, HOT WATER LAYOUT
Floor
Elevation
Loads / Expansion Joint Travel / Operating Deflection
PROJECT NAME & RISER MATERIALS:
Presentation Manor
Size
Details / Branch / Equipment
RISER TITLE:
FCU
LEVEL Ground Floor TO LEVEL 4
CUSTOMER P.O. #
TBA
DATE:
RISER CALCULATION No.
May 01, 2017
SHEET
0467 - HW2
1
OF
REV.
3
0
Using RISERCALC version 15.05.05.01
PROJECT DRAWING M6.02G, HOT WATER LOADS
Operating Loads
Design Loads
Test Loads
Anchor 1
Description
[kg]
[lbs]
[kg]
[lbs]
[kg]
Staged Loads
[kg]
[lbs]
[lbs]
Mass of Water
Mass of Pipe
Mass of Insulation
Mass of Cladding
Mass of Joint
Mass of Guides
Expansion Load
Static Pressure Load
TOTAL
Mass of Water
Mass of Pipe
Mass of Insulation
Mass of Cladding
Mass of Joint
Mass of Guides
Expansion Load
Static Pressure Load
TOTAL
Mass of Water
Mass of Pipe
Mass of Insulation
Mass of Cladding
Mass of Joint
Mass of Guides
Expansion Load
Static Pressure Load
TOTAL
Mass of Water
Mass of Pipe
Mass of Insulation
Mass of Cladding
Mass of Joint
Mass of Guides
Expansion Load
Static Pressure Load
TOTAL
NOTES
Note 1
Note 2
Note 3
Note 4
Note 5
Note 6
Note 7
THIS DOCUMENT IS THE PROPERTY OF FLEX-PRESSION LTD. & FLEX-PRESSION (ONTARIO) LTD. AND THE DATA HERE IN IS NOT TO BE DISCLOSED IN ANY
FORM TO ANYONE WITHOUT THE WRITTEN PERMISSION OF FLEX-PRESSION LTD. OR FLEX-PRESSION (ONTARIO) LTD.
CUSTOMER:
VR Mechanical Solutions Inc
464 Kingston Road West
Ajax, ONT L1T 3A3
Phone: 905 426.7551; Fax: 905 426.7164
PROJECT:
Presentation Manor
61 Fairfax Crescent
Scarborough, ONT M1L 1Z7
CUSTOMER P.O. #
TBA
DATE:
May 01, 2017
Leonine International Inc
10 Queen Street West, Unit 205
Cambridge, Ontario N3C 1G1
Tel: +1 519 260 0052
RISER TITLE:
FCU
LEVEL Ground Floor TO LEVEL 4
RISER CALCULATION No.
0467 - HW2
SHEET
2
OF
REV.
3
0
Using RISERCALC version 15.05.05.01
PROJECT DRAWING M6.02G, HOT WATER LOADS
Operating Loads
Design Loads
Test Loads
Description
[kg]
[lbs]
[kg]
[lbs]
[kg]
Staged Loads
[kg]
[lbs]
[lbs]
Mass of Water
Mass of Pipe
Mass of Insulation
Mass of Cladding
Mass of Joint
Mass of Guides
Expansion Load
Static Pressure Load
TOTAL
Mass of Water
Mass of Pipe
Mass of Insulation
Mass of Cladding
Mass of Joint
Mass of Guides
Expansion Load
Static Pressure Load
TOTAL
Mass of Water
Mass of Pipe
Mass of Insulation
Mass of Cladding
Mass of Joint
Mass of Guides
Expansion Load
Static Pressure Load
TOTAL
Mass of Water
Mass of Pipe
Mass of Insulation
Mass of Cladding
Mass of Joint
Mass of Guides
Expansion Load
Static Pressure Load
TOTAL
NOTES
Note 1
Note 2
Note 3
Note 4
Note 5
Note 6
Note 7
THIS DOCUMENT IS THE PROPERTY OF FLEX-PRESSION LTD. & FLEX-PRESSION (ONTARIO) LTD. AND THE DATA HERE IN IS NOT TO BE DISCLOSED IN ANY FORM
TO ANYONE WITHOUT THE WRITTEN PERMISSION OF FLEX-PRESSION LTD. OR FLEX-PRESSION (ONTARIO) LTD.
CUSTOMER:
VR Mechanical Solutions Inc
464 Kingston Road West
Ajax, ONT L1T 3A3
Phone: 905 426.7551; Fax: 905 426.7164
PROJECT:
Presentation Manor
61 Fairfax Crescent
Scarborough, ONT M1L 1Z7
CUSTOMER P.O. #
TBA
DATE:
May 01, 2017
Leonine International Inc.
10 Queen Street West, Unit 205
Cambridge, Ontario N3C 1G1
Tel: +1 519 260 0052
RISER TITLE:
FCU
LEVEL Ground Floor TO LEVEL 4
RISER CALCULATION No.
0467 - HW2
SHEET
2
OF
REV.
2
0
Using RISERCALC version 15.05.05.01
Level
PROJECT DRAWING M6.02G, HOT WATER LOADS
Support Description
Pipe Size
DN
Span
NPS
[m]
Lateral (side) Load
[ft]
[N]
Lateral Moment
[Nm]
[lbs]
[lb-in]
NOTES
Note 1
Note 2
Note 3
Note 4
Note 5
Note 6
Note 7
THIS DOCUMENT IS THE PROPERTY OF FLEX-PRESSION LTD. & FLEX-PRESSION (ONTARIO) LTD. AND THE DATA HERE IN IS NOT TO BE DISCLOSED IN ANY FORM
TO ANYONE WITHOUT THE WRITTEN PERMISSION OF FLEX-PRESSION LTD. OR FLEX-PRESSION (ONTARIO) LTD.
CUSTOMER:
VR Mechanical Solutions Inc
464 Kingston Road West
Ajax, ONT L1T 3A3
Phone: 905 426.7551; Fax: 905 426.7164
PROJECT:
Presentation Manor
61 Fairfax Crescent
Scarborough, ONT M1L 1Z7
CUSTOMER P.O. #
TBA
DATE:
May 01, 2017
Leonine International Inc.
10 Queen Street West, Unit 205
Cambridge, Ontario N3C 1G1
Tel: +1 519 260 0052
RISER TITLE:
FCU
LEVEL Ground Floor TO LEVEL 4
RISER CALCULATION No.
0467 - HW2
SHEET
2
OF
REV.
2
0
Using RISERCALC version 15.05.05.01
Deflection Results
PROJECT DRAWING M6.02G, HOT WATER DEFLECTIONS
Operating
Design
Vertical Rise
NOTES
Minus values of differential deflections indicate contraction (cold) movements, and positive values represent expansion (hot) movements.
Calculated pipe expansion for sizing the expansion joint, is based on 82.2 to -17.8 °C (180.0 to 0.0 °F) plus 25.0 % safety factor.
Calculated operating pipe expansion, is based on 60.0 to 4.4 °C (140.0 to 40.0 °F)
Calculated operating pipe expansion, is based on 60.0 to 4.4 °C (140.0 to 40.0 °F)
Branch to be located so that the insulation clears the underneath of the slab sufficiently to allow for the upward expansion of the pipe.
THIS DOCUMENT IS THE PROPERTY OF FLEX-PRESSION LTD. & FLEX-PRESSION (ONTARIO) LTD. AND THE DATA HERE IN IS NOT TO BE DISCLOSED IN
ANY FORM TO ANYONE WITHOUT THE WRITTEN PERMISSION OF FLEX-PRESSION LTD. OR FLEX-PRESSION (ONTARIO) LTD.
CUSTOMER:
VR Mechanical Solutions Inc
464 Kingston Road West
Ajax, ONT L1T 3A3
Phone: 905 426.7551; Fax: 905 426.7164
PROJECT:
Presentation Manor
61 Fairfax Crescent
Scarborough, ONT M1L 1Z7
CUSTOMER P.O. #
TBA
Leonine International Inc.
10 Queen Street West, Unit 205
Cambridge, Ontario N3C 1G1
Tel: +1 519 260 0052
RISER TITLE:
FCU
LEVEL Ground Floor TO LEVEL 4
DATE:
May 01, 2017
RISER CALCULATION No.
0467 - HW2
SHEET
3
OF
REV.
3
0
Using RISERCALC version 15.05.05.01
Download