Service Manual for product: KEA 201 SPL: Power Control Unit for Emergency and Peak Load Gensets with overlapping Synchronisation File: SA_KEA 201 SPL_EN_Ver 2016-07-01 (replaces Version 2014-12-19) _____________________________________________________________________________________ 1. Design The control unit is incorporate into the front door of the switchboard. When installed, the front meets the protection class IP 44. The two rows of LEDs are marked with interchangeable labels. The relay units are mounted on the mounting plate and linked to the control unit in the door with the supplied cable. The control unit has an optical fibre and a USB interface for the connection of a PC. Only one of them can be used at a time 1.1. Parameterisation With the parameterisation software PARAWIN, the following settings (password-protected) and analogue readouts are possible. 1. Additional Interface CAN 2. Additional Parameters 3. Alarm Remote Erasure 4. Alarms 5. Analogue Inputs 6. Analogue Outputs 7. Battery Monitor 8. CAN 0 9. Frequency Controller at isolated Operation 10. Generator Current Monitor 11. Generator Voltage Monitor 12. Hardware 13. Internal Synchroniser 14. J1939 engine management 15. J1939 Hide analogue values 16. Load Controller 17. Mains Voltage Monitor 18. Modem 19. Power Factor Controller 20. ProMerk. programmable Flags 21. Reference Load Regulation 22. Relay and Indicator Functions 23. Speed Monitoring and Control 24. Sprinkler Operation 25. Starting and Stopping 26. Transfer Mains – Generator 27. VDE-AR-N 4105 Protection for Parallel Operation 28. Voltage Controller Parameterisation can also be performed at the display. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 2 / 26 1.2. Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 2 / 26 Analogue Readouts Actual values: - Mains: Voltages and frequencies - Generator: voltages, frequencies, current, active and apparent power, PF (for L2) - Engine speed - Battery voltage - Values of the four analogue channels - Actual status of relays - Counter, e.g. for Hours of operation until maintenance - Actual values via CAN, e.g. temperatures and other data from motor, fuel, oil, coolant, battery and environment Present alarms, in total 64 alarms – for generator, oil, engine, mains, etc. Voltage monitor: - L1, L2 and L3 for mains and generator - Voltage, phase vector, phase angle, frequency Signals on the input terminals Outputs: Status of relays Other Values Commands Telealarm 2. Amendments Created Amendments Version 2014-12-15 Translation from German Version 2014-10-21 2014-10-21 2014-12-19 “Enabling Mains Parallel Operation”: section “Setpoint for Power” added 2014-12-18 - Technical Data: Corrected: Optical fibre or USB interface – with automatic switching – for parameterisation 2. Removed: Option in preparation: GSM modem 2015-02-10 - Last page: Added: Drilling Template, Scale 1:1 (was down-scaled before) 2016-07-05 _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 3 / 26 3. Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 3 / 26 Contents 1. Design ........................................................................................................................................................1 1.1. Parameterisation ................................................................................................................................1 1.2. Analogue Readouts ............................................................................................................................2 2. Amendments .............................................................................................................................................2 3. Contents ....................................................................................................................................................3 4. Safety Instructions ...................................................................................................................................5 4.1. Regulations and Instructions ..............................................................................................................5 4.2. Installation and Commissioning ..........................................................................................................5 4.3. Connections ........................................................................................................................................5 4.4. Battery and Supply voltage .................................................................................................................5 4.5. Inductors .............................................................................................................................................5 5. Connection ................................................................................................................................................5 5.1. Operating the Display .........................................................................................................................6 5.2. Setting the Display Contrast ...............................................................................................................6 6. PIN Number, Ident-Number......................................................................................................................7 7. Parameterisation Menu Structure ...........................................................................................................7 8. Alarm Monitoring ......................................................................................................................................8 8.1. Description ..........................................................................................................................................8 8.2. Alarm Announcing and Acknowledgement .........................................................................................9 8.3. Explanation of Alarms.........................................................................................................................9 8.3.1. Engine keeps running ................................................................................................................................ 9 8.3.2. Engine fails to start ................................................................................................................................... 9 8.3.3. Engine fault ............................................................................................................................................... 9 8.3.4. Overspeed ................................................................................................................................................. 9 8.3.5. Alarms 13 and 14 ...................................................................................................................................... 9 8.3.6. Battery voltage Monitor ......................................................................................................................... 10 8.3.7. Analogue Input Alarms ........................................................................................................................... 10 8.3.8. Mains CB tripped .................................................................................................................................... 10 8.3.9. Mains CB does not cut off ....................................................................................................................... 10 8.3.10. Generator CB tripped .............................................................................................................................. 10 8.3.11. Generator CB does not cut off ................................................................................................................ 10 8.3.12. Alarms of the voltage monitors .............................................................................................................. 10 8.3.13. Monitoring of the currents ..................................................................................................................... 10 8.3.14. Synchronisation failure ........................................................................................................................... 10 8.3.15. Load controller failure ............................................................................................................................ 10 8.3.16. PF controller failure ................................................................................................................................ 11 8.3.17. Reverse power ........................................................................................................................................ 11 8.3.18. Running hours till Maintenance elapsed ................................................................................................ 11 8.3.19. Maintenance period exceeded ............................................................................................................... 11 9. Mains Failure Protection in Parallel Operation ....................................................................................11 9.1. Monitoring Deviations in Voltage and Frequency .............................................................................11 9.2. Vector Shift .......................................................................................................................................11 9.3. Sealing the Setpoints ........................................................................................................................12 9.4. Mains Failure Protection according to E VDE-AR-N 4120 ...............................................................12 10. Mains Reference Load Control Operation ...........................................................................................12 11. Peak Load Operation Mode ...................................................................................................................13 12. Mains Operator’s Load Levels ..............................................................................................................13 _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 4 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 4 / 26 13. Enabling Mains Parallel Operation .......................................................................................................13 13.1. Description ........................................................................................................................................13 13.2. Setpoint for Power ............................................................................................................................14 14. Mains Recovery in Peak Load Operation .............................................................................................14 15. Power Control .........................................................................................................................................14 15.1. Frequency Range 50.2 - 51.5 Hz .....................................................................................................14 16. Controlling Reactive Power ...................................................................................................................15 17. Sprinkler Operation ................................................................................................................................15 18. Connection of Relay Unit RZ 071-D ......................................................................................................15 Terminals 1–14: Input for alarms signals. ................................................................................................................ 15 Terminal 15: Feedback signal: MAINS CB IS OFF. ......................................................................................................... 15 Terminal 16: Feedback signal: GENERATOR CB IS OFF. .................................................................................................. 16 Terminal 17: Operation mode selection is locked. ................................................................................................... 16 Terminal 18: Remote start with Load Transfer. ....................................................................................................... 16 Terminal 19: IMMEDIATE STOP. .................................................................................................................................... 16 Terminal 20: Overlapping synchronisation active. ................................................................................................... 16 Terminal 21: Peak Load Command........................................................................................................................... 16 Terminal 22: Disabled regulation of mains reference load ...................................................................................... 16 Terminal 23: Sprinkler mode. ................................................................................................................................... 16 Terminal 24: Start enable input. .............................................................................................................................. 16 Terminal 25: Remote start without Load Transfer. .................................................................................................. 16 Terminal 26: External command :GENERATOR OFF ...................................................................................................... 16 Terminal 27: Power Control in Peak Load Operation. .............................................................................................. 17 Terminal 28: Power Control in Peak Load Operation. .............................................................................................. 17 Terminal 29: Charging Dynamo, terminal D+. .......................................................................................................... 17 19. Flags for Alarm Inputs and Relays .......................................................................................................17 20. Technical Data ........................................................................................................................................20 20.1. KEA Controller ..................................................................................................................................20 20.2. Analogue Inputs and Outputs ...........................................................................................................20 20.3. Relay Unit RZ 071-D ........................................................................................................................20 20.4. Relay unit RZ 071-E (optional) .........................................................................................................20 20.5. Serial interfaces ................................................................................................................................20 20.6. Connection to other Systems (optional) ...........................................................................................20 21. Diagrams .................................................................................................................................................21 21.1. Response Diagram for Thermal Overload ........................................................................................21 21.2. Connection Diagram, RZ-071-D .......................................................................................................22 21.3. Connection Diagram, RZ-071-E (optional) .......................................................................................23 21.4. Connection Diagram, KEA 201 SPL .................................................................................................23 21.5. Connections, analogue Inputs ..........................................................................................................24 21.6. Door Cross Section of KEA, Frontview ............................................................................................24 21.7. Controller PCB with Jumper for Sealing Setpoints ...........................................................................25 22. Drilling Template, Scale 1:1 – print without scaling! ..........................................................................26 _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 5 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 4. Safety Instructions 4.1. Regulations and Instructions 5 / 26 1. The relevant regulations, especially the VDE regulations, must be observed. 2. The device must be parameterised in such a way that any risk to persons or property is prevented. 4.2. Installation and Commissioning Only adequately qualified personnel should undertake the installation and commissioning. 4.3. Connections 1. Care must be taken when connecting the device, as it may be destroyed if incorrectly connected. All details of the connection specifications must be fulfilled. 2. For safety reasons, the PE(N) must be connected to terminal 5 on the X403. 3. The shielding of the analogue wiring must only be connected the earth screws beside the terminal strip X401 on the KEA cover and may have no connection to any other metal parts. 4. The transformer connections k are to be connected to the protective conductor. 4.4. Battery and Supply voltage 1. Before the battery is disconnected, the charging device must be switched off. 2. The negative pole of the battery must be grounded at the input terminal of the switchboard. The minimum conductor diameter is 10 mm2. 3. The supply voltage is to be set to 12 or 24 V DC with a switch on the RZ 071-D. 4. When the supply voltage of the control unit has been switched off, you must wait at least 20 seconds before applying it again. 5. The leakage current of the noise filters is 22 mA in case of a 2-phase voltage lost. 4.5. Inductors All coils must be fitted with reverse diodes to prevent high voltage peaks. All other coils or inductive loads must also be fitted with suppressor elements. The same applies for all relays and inductors that are used in the switchboard or controlled externally. 5. Connection 1. 2. 3. 4. 5. 6. 7. 8. Only trained experts may make the connections of the KEA. For safety reasons, the PE(N) must be connected to terminal 5 on the X403. Before the battery is disconnected. The charging device must be switched off. When the supply voltage of the control unit has been switched off, you must wait at least 20 seconds before applying it again. The negative pole of the battery must be grounded at the input terminal of the switchboard. The minimum conductor diameter is 10 mm2. The supply voltage is to be set to 12 or 24 V DC with a switch on the RZ 071-D. The shielding of the analogue wiring must only be connected the earth screws beside the terminal strip X401 on the KEA cover and may have no connection to any other metal parts. All coils must be fitted with reverse diodes to prevent high voltage peaks. All other coils or inductive loads must also be fitted with suppressor elements. The same applies for all relays and inductors that are used in the switchboard or controlled externally. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 6 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 6 / 26 The following signals (if needed) are directly applied to the control unit: Voltage of mains and generator Current of generator Four analogue sensors Pick-up Two analogue output signals Optical fibre or USB for parameterisation Two CAN bus systems. Although the control system is protected against reverse polarity, the correct polarity when connecting the battery voltage must be strictly observed, as reverse diodes or other electronic parts of the switchboard may possibly be damaged. The fuse on the RZ 071-D will be blown if the control system is connected with the wrong polarity! Due to the fact that most of the control relays may be configured for various functions, only the status print out of the supplied control unit is to be considered as a binding document. It must be observed, that in case of a possible replacement of a unit, any modifications made after commissioning cannot be taken into account by the manufacturer. 5.1. Operating the Display Values or parameters are selected, as you would read a book. The groups listed further down are arranged as 'pages'. You can scroll forwards and backwards through these groups by pressing the [→] and [←] keys. The entries of each group can be read from top to bottom like lines of a text. Select a line by pressing the keys [↓] (down) and [↑] (up). The selection starts again with the other end of the 'page', when the top or bottom of the 'page' is reached. To select directly the ACTUAL VALUES group: hold down the LED TEST button, and press [←]. To display the group CURRENT ALARMS hold down LED TEST and press [→]. To modify a parameter: first enter the relevant IDENT-NUMBER. Note: Parameters of group 0, -GENERAL PARAMETERS-, can be modified without entering this number. Parameters are modified as follows: 1. Select the required parameter group with the [←] and [→] buttons. 2. Select the required parameter line with the [↓] and [↑] buttons. 3. Press OFF and LED TEST (function: PARA ON or PARA OFF) together. This opens parameterisation mode as can be seen by the specific cursor [ █ ]. The selection of the group cannot be changed now. 4. Press [↓] / [↑] to select the desired parameter. 5. Press OFF and ALARM OFF (ENTER function) together to select the parameter line. The shape of the cursor confirms the selection, as it underscores (e.g. 196) now the part of the parameter that is to be modified. The chosen parameter cannot be deselected now. 6. Select the figure or letter of the parameter that you want to modify with the [←] and [→] cursor keys. Numerical parameters can be increased or decreased by increments of 1 with the [↑] and [↓] buttons. Press the same buttons to negate parameters that are displayed with a letter (+/- signs, alarm coding etc.). 7. Press OFF and ALARM OFF together to store the displayed parameter. Press OFF and LED TEST to abort parameterisation. 5.2. Setting the Display Contrast Hold down LED TEST and press key [↑] to increase the display contrast (makes the display darker) Hold down LED TEST and key [↓] to lower it (makes the display lighter). _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 7 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 7 / 26 6. PIN Number, Ident-Number To modify a parameter, you first have to enter the relevant IDENT-NUMBER. This number is compared with the PIN NUMBER, and if they are identical, the user is authorised to parameterise the device. The user can chose any PIN NUMBER between 00000 and 50000. The PIN NUMBER and IDENT-NUMBER are factory-set to 00000. A special IDENT-NUMBER can be enquired from the factory if you forget your PIN NUMBER, so that a new PIN NUMBER can be entered. Modify the PIN NUMBER as follows: 1.Enter the currently valid Ident-Number. The pin number is now also shown. 2.Enter a new PIN Number. The Ident-number previously entered is now no longer valid. The IDENT-NUMBER is deleted 15 minutes after the last input, if the user has not previously set it to an invalid value. The automatic deletion of the IDENT-NUMBER is, however, not carried out while 00000 is set as the PIN. 7. Parameterisation Menu Structure Group 0 KEA 201 SPL KUHSE GmbH Group 1 ACTUAL VALUES Group 2 ENCODING OF ALARMS COUNTERS Group 3 Group 4 MAINS VOLTAGE MONITOR GENERATOR PROTECT: PARALLEL OPERATION GENERATOR MONITOR CURRENT MONITOR MONITOR Group 5 ANALOGUE INPUTS Group 6 SPEED MONITORING SPEED GOVERNOR ANALOGUE OUTPUTS Group 7 Group 8 START-STOP ADD. FUNCTIONS CHANGE OVER OF MAINS-GENERATOR Group 9 RELAY- /LED FUNCTIONS BATTERY VOLTAGE MONITOR ADDITIONAL PARAMETERS Group 10 LOAD CONTROLLER PF CONTROLLER PF CONTROLLER Group 11 SYN. FUNCTION f/U CONTROL Group 12 *) ENGINE CONTROL ACTUAL VALUES Group 13 NO ALARMS PRESENT Group 14*) ENG. CONTROLLER CURRENT ALARMS FREQUENCY CONTR. VOLTAGE CONTROL MAINS REFERENCE LOAD *) Group 12 and 14 only displayed if there is a CAN connection to the genset. The functions and parameterisation are described in FUNCTIONS AND PARAMETERISATION OF KEA 101-112 – please refer to our Website under http://www.kuhse.de/en/download/operatinginstructions/diesel-genset-controls.html. This document contains all possible functions featured in the KEA Series 101-112 and is also valid for the new KEA series 201-252. Please note however, that only those functions, listed in the service manual, are actually implemented. The PARAW IN parameterisation software also shows only the parameters that are possible for the particular control unit. Additional processes for the peak load operation according to VDE-AR-N 4105 mains failure detection according to E VDE-AR-N 4120 (as of Version 9) sprinkler operation according to VdS 2100-22:2008-11 are described further below. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 8 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 8 / 26 Group 2 3 3 4 4 5 5 6 7 7 7 8 9 10 10 10 11 11 11 Function Encoding of alarms Mains voltage monitor Mains failure protection Generator voltage monitor Generator current monitor Analogue inputs Analogue outputs Speed monitoring, Switching points Start-stop functions Additional parameters Battery voltage monitor Parameter for mains-generator switchover Settings for relays and indicators Power controller PF controller Reference load controller Synchronizer Frequency controlling in stand-alone operation Voltage controlling in stand-alone operation User manual 8. Alarm Monitoring 8.1. Description Section in FUNCTIONS AND PARAMETERISATION Alarm Monitoring Voltage Monitor Mains failure monitoring in parallel operation Voltage monitor Current monitor Analogue interface Analogue interface Speed monitoring Start and Stop Additional parameters Additional parameters Mains-Generator switchover Setting of relays Power und PF controller Power und PF controller See further below Synchronisation Synchronisation Synchronisation See BA_KEA 201_SPL The control unit can control up to 64 alarms. The texts and trigger inputs for alarms 1 to 19 and 49 to 64 are variable, i.e. their texts and actuation are determined by the parameterisation software PARAWIN. The alarms are actuated by terminals 1 to 14 or free terminals on the relay unit RZ 071-D or by internal flags (e.g. controller failures, limit value on an analogue channel too high, etc.). The parameterisation is described above. Alarms can be divided into three groups: Alarms that are monitored only after a delay when the engine is running (e.g. LOW LUB OIL PRESSURE), called DELAYED. The green MONITORING ON indicator shows that they are monitored. Alarms, which are monitored even when the engine is at a standstill, except in operation mode OFF, (e.g. BATTERY UNDERVOLTAGE), called UNDELAYED. Alarm signals 13 and 14 are always monitored, even in operation mode OFF. They are used for alarms such as LEAKAGE. In operation mode OFF the audible signal is not switched on, but the alarms are collected together in common alarms. They act just like normal alarms when any other operation mode than OFF is selected. The alarms are configured as follows: Alarm is active or inactive Contact is normally open or normally closed Delayed or undelayed monitoring Warning or shutdown In addition for warning alarms: With or without generator cut off and stop after the re-cooling period in AUTO mode. The genset is stopped after the re-cooling period and the automatic control is locked if the generator is cut off after a warning alarm in the AUTO mode. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 9 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 9 / 26 At terminal inputs, an alarm is triggered when the corresponding signalling switch closes (normally open, make contact) or opens (normally closed, break contact). In case of analogue signals an alarm is triggered, when the actual value is higher than the UPPER LIMIT (alarm pre-set for make contacts) or the actual value is lower than the LOWER LIMIT (alarm pre-set for break contacts). Alarms 11 to 14 can additionally be parameterised as break signals of output relays, i.e., the corresponding relay is activated when the alarm is inactive. 8.2. Alarm Announcing and Acknowledgement As long as no new alarm is waiting for acknowledgement, the ACTUAL ALARMS group can be selected with the [←] and [→] buttons, or by pressing LED TEST and the [→] button at the same time. The indicator COMMON ALARM (yellow one in the left row of the panel) is flashing when an unacknowledged alarm is present. The acoustic signal is switched on at the same time. Press the ALARM OFF button to turn off the acoustic signal and bring up the page of the ACTUAL ALARMS on the display. The alarm text is preceded either by <NEW> if the alarm has not been acknowledged or <ACKN> if it has been acknowledged. NEW GENERATOR OVERLOAD ACKN GENERATOR OVERLOAD Unacknowledged alarm Acknowledged alarm NO ALARMS PRESENT Display when no alarms are activated Press the ALARM OFF button to acknowledge the indicated alarm or to delete a previously acknowledged alarm if the cause of the malfunction has been removed. When all alarms have been acknowledged, the COMMON ALARM indicator stops flashing and lights up steadily. It starts to flash again when a new alarm is notified. The COMMON ALARM switches off when all alarms have been deleted. Move through the activated alarms with the [↑] and [↓] buttons to acknowledge or delete them with the ALARM OFF button. If no alarms are pending, the announcement -NO ALARMS PRESENT is displayed. If the generator is switched off by a warning alarm whilst in AUTO mode, the motor is stopped after the re-cooling time, and the automatic mode is locked. 8.3. Explanation of Alarms 8.3.1. Engine keeps running This alarm is announced when the engine is still running after the stop procedure. It means that the stopping equipment of the engine (stopping solenoid, gas valve, etc.) is defective. 8.3.2. Engine fails to start This alarm comes up (and the automatic operation is locked) when the engine is not running after the start sequence. 8.3.3. Engine fault This alarm is activated if the engine stops without having a stop command from the control unit. The control system is locked at the same time. 8.3.4. Overspeed The generator frequency or a pick-up signal is used for monitoring overspeed. The alarm GENERATOR UNDERVOLTAGE must be enabled as a shutdown alarm when the generator frequency is used. This also protects the engine if the generator voltage fails. 8.3.5. Alarms 13 and 14 The input signals for these two alarms can be delayed for 0 to 240 seconds. That means that the alarm contact must be activated for the programmed time before the alarm comes up. Furthermore these two alarms are also enabled in the operation mode OFF, however without the audible signal. Fault signals, which have to be always signalled, can be monitored by this (e.g. tank filling level, leakage). _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 10 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 10 / 26 8.3.6. Battery voltage Monitor A relay (with a break function) can be programmed for the direct output of the battery voltage monitor. It is energised if the voltage is good. A remote signal is possible by this even in the operation mode OFF. 8.3.7. Analogue Input Alarms The analogue inputs can be fitted with modules for various sensors (PT100, PT1000, current loops, thermal elements, VDO sensors, MotoMeter for engine temperature and oil pressure etc.). For each analogue input, two threshold levels can be set to trigger an alarm. 8.3.8. Mains CB tripped The mains circuit breaker can be monitored for automatic tripping (e.g. by an installed over-current tripping device). The alarm is internally triggered if no feedback signal M AINS CB IS ON is detected after running out of the mains CB closing pulse. Furthermore it can be selected whether the engine should start and take the load or not (according to VDE standard 0107) in the operation modes AUTO or TEST. The alarm must in this case be cancelled for switching back to mains supply after the switch-back delay. 8.3.9. Mains CB does not cut off The alarm occurs when the mains CB is not off two seconds later after the Off-command. This alarm can control a relay by which an additional mains coupling breaker can be switched off to allow the generator to supply the consumers. 8.3.10. Generator CB tripped The generator circuit breaker can be monitored for automatic tripping (e.g. by an installed over-current tripping device). Additionally the mode WARNING/SHUTDOWN must be programmed for this alarm. The alarm is internally triggered in case no feedback signal G ENERATOR CB IS ON is detected after running out of the generator closing pulse. 8.3.11. Generator CB does not cut off The alarm occurs when the generator CB is not off two seconds later after the Off-command. The genset gets an internal start command and by this keeps the engine running and the generator CB remains on. The engine stops when in this case a shutdown alarm occurs. An additional generator coupling breaker can be switched off by a programmed relay to prevent that the engine is operated with reverse power. 8.3.12. Alarms of the voltage monitors An alarm is announced if a monitored voltage or frequency of mains or generator is out of its range. The alarm itself has no influence of the actual voltage or frequency monitoring. That means, if the monitor has stated a failure and triggered the alarm and later on the monitored function is again within its limit, the alarm is still present until it is cancelled. For the internal controlling however, the actual state is used which means, that the monitored function is effective as NORMAL. 8.3.13. Monitoring of the currents The generator currents can be monitored for overcurrent (e.g. 110 %) short-circuit (e.g. 300 %) unbalanced currents and thermal overload. The Response Diagram for Thermal Overload, is shown further below. 8.3.14. Synchronisation failure A timer is started when the synchronisation begins. An alarm is triggered if no synchronisation has happened when this delay time is up. It is programmable if in this case a changeover with a break is done or if the synchronisation remains on. 8.3.15. Load controller failure An alarm is indicated when after a pre-set time the actual load has not matched the pre-set load value (the actual load has to be at least once inside the dead zone). The genset can be stopped or a peak load command can be removed in this case. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 11 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 11 / 26 8.3.16. PF controller failure An alarm is indicated when after a pre-set time the actual PF has not matched the pre-set PF (the actual PF has to be at least once inside the dead zone). The genset can be stopped or a peak load command can be removed in this case. 8.3.17. Reverse power The generator CB must be switched off if the engine fails in parallel operation. 8.3.18. Running hours till Maintenance elapsed The remaining running hours till the maintenance of the engine is shown in S ETPOINTS. A warning alarm (if programmed) is given if the time period has elapsed. The counter for the time period till the next maintenance must be set after the first one is done. This is only possible with ParaWin by authorized persons. In case the goodwill period is set to 0 hours, this counter will stop at zero hours and not show negative hours when the period is exceeded. 8.3.19. Maintenance period exceeded An additional alarm (if programmed) occurs if the normal period and the additional goodwill period are over. The reset is only possible for authorized persons. No alarm will occur in case the goodwill period is set to 0 hours. This alarm can only be reset by the supplier! 9. Mains Failure Protection in Parallel Operation The mains voltage is monitored according to the limits of the VDE-AR-N 4105 or E VDE-AR-N 4105. In addition, the voltage controller can be enabled for standard emergency power operation. This applies to VDE-AR-N 4105 only. Due to the reduced tolerances of this standard, sensitive consumers are safeguarded against too large deviations. After parallel operation is established, the parameterised time elapses before the monitoring is activated. This allows voltage, current and frequency to settle after the synchronisation. Should subsequently a mains failure be detected, the mains switch is instantly set to OFF, and the standard mains voltage monitor to Undervoltage. In this case, the parameterised delay for the mains voltage monitor is disabled. Depending on the actual operating mode, the genset switches to idle emergency mode or shuts down. Even a brief interruption of the mains triggers the voltage monitor’s delay to run after the mains voltage has recovered. According to the genset’s operation mode, it synchronises to the mains, or – in case of genset standstill – the mains is switched on again. All below-listed additional functions can be enabled or disabled for mains failure detection. This applies to the VDE-AR-N 4105 only. 9.1. Monitoring Deviations in Voltage and Frequency This monitoring can be enabled as a supplement to the requirements according to the VDE-AR-N 4105. After each measurement, voltage and frequencies values of the mains are stored and compared to the previous values, even if the systems are not running in parallel. If in parallel operation, the difference between the previous and current value (du/dt, df/dt) exceeds the parameterised value, this is indicated as a mains failure. These measurements allow large deviations in voltage or frequency to be treated as mains failures. 9.2. Vector Shift This monitoring can be enabled as a supplement to the VDE-AR-N 4105. The time duration of the present voltage period is compared to the previous one. A deviation is converted to degrees. This is a measurement of a vector shift. If the deviation exceeds the parameterised reference value, it is most likely that a mains failure has occurred. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 12 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 12 / 26 9.3. Sealing the Setpoints Inside the KEA, on the middle PCB – see Controller_PCB further below – you will find a jumper. If you remove this, you will no longer be able to modify the following parameters: Mains failure if du/dt > … Hz du/dt enabled Mains failure if df/dt > … Hz df/dt enabled Mains failure if vector shift > … degrees Vector shift enabled? If the jumper is removed and the KEA cover sealed, the setpoints you have entered cannot be changed. Setting the mains voltage monitoring to 110 % according to VDE-AR-N 4105 is only modifiable with ParaWin and password. All other limits are fixed. 9.4. Mains Failure Protection according to E VDE-AR-N 4120 On the low-voltage side of a medium-voltage system, the monitoring proposes deviating functions for switching off the generator. These requirement are met by KEA 201 SPL03 as of version 9. Implemented setting ranges: Function U>> U> U< U<< f> f< 10. Setting range 1.00 – 1.30 UNS 0.3 – 1.00 UNS 0.3 – 1.00 UNS 0.3 – 1.00 UNS 47.00 – 50.00 Hz 50.00 – 52.00 Hz max. 100 msec 0.0 – 300 sec 0.0 – 300 sec. max. 300 msec. < 100 msec. < 100 msec. Settings, e.g. EON Mitte (German electricity provider) 1.15 UNS, no delay (< 100 msec.) 1.1 UNS, delay: 60 sec. 0.8 UNS, delay: 1 sec. 0.45, UNS, no delay (< 100 msec) (required: 0 sec). 51.50 Hz, no delay, (< 100 msec) 47.50 Hz, no delay (< 100 msec) Mains Reference Load Control Operation When the specified mains reference load is exceeded, the genset starts, but not until after a time delay (max. 240 sec.) to suppress unnecessary starts. Upon parallel connection of mains and generator, the controlling is based on a parameterised reference load. The mains reference load must be larger than or equal to the difference between the genset’s stop loading and the starting point. As soon as the consumer load falls, the generator output is reduced in order to maintain the parameterised load level at its reference. If the generator output falls below the generator power setpoint, the start command to the genset will be cancelled – after a delay. The genset unloads to the minimum that is set and then shuts down. Now the mains reference load rises by the amount of the aborted genset power. Hence, select the parameter values so as to ensure the starting point is not immediately exceeded once again. In order to protect against return feed into the mains, a limit is provided. If this is fallen short of, the genset is immediately turned off. Always select the parameters so that the aborted power does not cause the starting point to be exceeded. This signal can be parameterised as an error message. High and Low-Tariff (HT and LT) The starting point of the maximum mains load and the succeeding control can be set differently for high and low-tariff periods. Likewise, the starting and ending times of the low-tariff period can be entered. This also allows the load control to be switched off during the LT periods. Furthermore, for both periods, the power control can be switched off via a switch on the relay unit. The power limitation according to VDE-AR-N 4105 is valid for parallel operation, provided the monitoring is enabled in ParaWin. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 13 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 13 / 26 11. Peak Load Operation Mode 1. The genset is started by a peak load command. If the genset is already running in TEST mode, the system switches to parallel operation. 2. After parallel operation is accomplished, the internal power and PF controller is enabled and the generator loaded. During the parallel operation, the internal power and PF (cos φ) control unit is enabled and the generator loaded. The internal power and PF control is described further below. 3. After the peak load command is disabled in AUTO mode, the genset is unloaded – and at a load of 10 % of the generator switched off. If the peak load command is given TEST or M ANUAL mode, you should switch back to the AUTO mode to allow all following automatic processes to run. The KEA 201 can detect a power failure during peak load operation. The KEA will then directly switch off the mains, thus immediately shifting to emergency power operation. After mains recovery and elapsed switch-back delay, the genset will synchronise with the mains. A pending peak load command will cause the system to return to mains parallel operation – or switches off if there is no start command. 12. Mains Operator’s Load Levels The mains operator is to specify the maximally allowed load in the following steps: 0%, (stop) 30%, 60%, and 100% (full load). For this, two terminal inputs are provided: Terminal on RZ-071-D Terminal 27 Terminal 28 Enabled power (percentage of nominal load) *) Not connected Open* Open* 0% (stop) Input signal L[-] ** Open* Open* L[-] ** 30% 60% L[-] ** L[-] ** 100% **) Connected 13. Enabling Mains Parallel Operation 13.1. Description The start is enabled if for at least 60 sec. the following is met: Frequency in the range 47.5 Hz - 50.05 Hz Voltage in the range 85 % - 110 % of UNOM In addition, a percentage load of 30, 60 or 100 % must be specified. If the genset operates in parallel with the mains, the mains failure monitoring, power and PF controlling operate according to the VDE-AR-N 4105. This can be supplemented with the internal vector shift relay. The line-to-line voltages are to be calculated from the phase-to-neutral voltages. For this, clockwise rotation fields at the measurement inputs are mandatory, the mains and generator monitoring for the isolated operation thereby switched off. The switching points of the VDE monitoring system can be changed via a special password and can also be sealed. After a power failure, the protection against overvoltage (>U, averaged over 10 min.) is continuously determined until measurements of most-recent 10 min. are available. Consequently, if for instance the value averaged over the first 3 min. already exceeds 110 % of the nominal voltage, the mains failure is instantly detected – rather than not until after 10 min. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 14 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 14 / 26 In M ANUAL parallel operation (i.e. no peak load command) the generator voltage monitor will also switch over to the VDE-specified thresholds. For the VDE-AR-N 4105, these are: Voltage drop protection Voltage increase protection Voltage increase protection Frequency drop protection Frequency increase protection Absolute value Averaged over 10 min. Absolute value Absolute value Absolute value U< U> U>> f< f> 0,85 UNom 1.10 UNom 1.15 UNom 47.5 Hz 51.5 Hz The settings according to VDE-AR-N 4120 are listed forth above. For frequencies in the range 47.5 Hz – 50.00 Hz, a separation in consequence of a frequency deviation is not permitted. For the 5 most-recent events, date and time are stored, readable via the USB connection. Apart from the average U>, all switching points are fixed. By setting different thresholds for the mains and the generator monitor in parallel and emergency operation (incl. sprinkler operation) according to VDE-AR-N 4105, you will be able to narrow the limits.for emergency operation Please note that after a mains failure and switching to emergency operation, the frequency and voltage control must under certain circumstances quickly bring the system back into the specified limits. 13.2. Setpoint for Power The setpoint for mains parallel operation can be predefined: as an analogue signal, channel 4 via a ZLT or as a parameterised fixed value. An external setpoint value is stated as per mill of the nominal value, and the fixed value is stated in kW. If the analogue channel is used, the minimum and maximum reference value are to be parameterised accordingly. 14. Mains Recovery in Peak Load Operation The start is enabled if the following is met: Frequency in the range 47.5 Hz - 50.05 Hz Voltage in the range 85 % - 110 % of UNOM The delay after a power failure that lasts longer than 3 sec. is at least 60 sec. For power failures lasting less than 3 sec. (short-time interruption), the synchronisation process can start after just 5 sec. 15. Power Control Via two inputs, the mains operator is to set a power limitation, the respective percentage restriction configurable. The reduction of the enabled amount of power takes place within a minute. For the frequency range 47.5 Hz – 50.2 Hz, there is no further limitation of the power emitted. Terminal on RZ-071-D Terminal 27 Terminal 28 Enabled power (percentage of nominal load) *) Not connected 15.1. Open* Open* 0% (stop) Input signal L[-] ** Open* Open* L[-] ** 30% 60% L[-] ** L[-] ** 100% **) Connected Frequency Range 50.2 - 51.5 Hz If the frequency is equal to or higher than 50.2 Hz, it is not permitted to increase the power. Instead, the present power level (at 50.2 Hz) is held. Should the frequency still increase, the setpoint value of the power controller transforms into a linear function with a slope of 40 % pro Hertz of the value at 50.2 Hz until it is switched off at 51.5 Hz, i.e. maximally reduced by 52 %. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 15 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 15 / 26 If the frequency decreases, the power is increased according to the specified gradient until it reaches the level at 51.5 Hz. If the frequency still decreases, the genset can be operated with the enabled power level. In this case, an increase in power will occur in steps of 10 % of the enabled power per minute. This is followed by standard controlling. Upon mains recovery, the power is increased in steps of 10 % per minute until it reaches the required level. This is followed by standard controlling. 16. Controlling Reactive Power The VDE-AR-N-4105 specifies a characteristic curve or a fixed factor for the PF (cos φ). After a start, the amount of reactive power is reached within 10 minutes. Values for the characteristic curve are reached within 10 sec. A standard curve specifies: Load in the range: 0 % - 20 %: setpoint for cos φ = -/+ 0,9 20 % - 50 %: setpoint for cos φ = -/+ 1.0 50 % - 100 5: setpoint for cos φ linear in the range Tables oft the standard setpoints Power cos φ underexited cos φ overexited 0 - 20% 0.9 0.9 20-50% 1.0 1.0 50-100% linear decrease from 1.0 to 0.90 underexited 17. Sprinkler Operation The following functions are provided for operation of an electric sprinkler pump: Set all alarms as warning ones Start sequence with 10 (can be set by customer) start attempts, For the run-up of the sprinkler pump: pause or no pause for the emergency consumers, You can select when the sprinkler is no longer required, if the Sprinkler operation is cancelled after the COOLING DOWN PERIOD AFTER SPRINKLER or is manually switched off. The time stage for the COOLING DOWN PERIOD AFTER SPRINKLER CAN be set from 10 to 2400 seconds. The sprinkler operation is not terminated automatically but must be ended manually if this stage is set to 0 seconds. In this is the case, the OFF mode indicator flashes. The genset can now only be stopped via IMMEDIATE STOP or the mode OFF. The pause duration of the emergency supply for the run-up of the sprinkler pump can be set from 0 to 24 seconds. The emergency consumers are not switched off if it is set to 0 sec. The consumers are switched to generator supply if during the sprinkler operation a mains failure or a remote start with load transfer occurs. The emergency consumers are switched back after expiry of mains recovery delay when the mains voltage is restored or the remote start command is cancelled. The sprinkler mode prevents that the genset is switched off or shut down due to an alarm. If a shutdown alarm is triggered, however, the common alarm SHUTDOWN is issued. 18. Connection of Relay Unit RZ 071-D Terminals 1–14: Input for alarms signals. Terminal 15: Feedback signal: MAINS CB IS OFF. An auxiliary contact (NC) of the mains CB (or contactor) is connected to this terminal. It shows the position of the breaker. The control unit is fitted with an interlocking circuit which prevents the generator from switching on (without synchronising) as long as the mains supply is on. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 16 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 16 / 26 Terminal 16: Feedback signal: GENERATOR CB IS OFF. An auxiliary contact (NC) of the generator CB (or contactor) is connected to this terminal. It shows the position of the breaker. The control unit is fitted with an interlocking circuit that prevents the mains from switching on (without synchronising) as long as the generator supply is on. Terminal 17: Operation mode selection is locked. The selection of the operation modes by the push-buttons will be locked if a signal is applied at this terminal. A key-operated switch, to prevent the selected mode from being changed by unauthorised persons or by mistake, could perform this. Terminal 18: Remote start with Load Transfer. If an L[-] signal is connected, and the system is running in operation mode AUTO, the genset starts with switchover to generator operation. If the system is in TEST mode or has been started in AUTO mode via the command START WITHOUT LOAD TRANSFER, the generator is automatically switched on. If an L[-] potential is not applied – command START WITHOUT LOAD TRANSFER must not be displayed, the generator will – upon the switch-back delay – be switched off, and the genset turned off – after the delay. Terminal 19: IMMEDIATE STOP. The signal can be parameterised as normally-closed or normally-open – KEA display, Group 6, PARAWIN, under ADDITIONAL PARAMETERS . The genset will be immediately shut down if a signal is applied to this terminal. The control unit will be locked for any further starting attempts. To reset the control unit, the operation mode has to be set to OFF. Resetting is only possible if the signal is no longer connected, otherwise the indicator AUTOMATIC LOCKED would remain on. Terminal 20: Overlapping synchronisation active. If an L[-] signal is connected here, the load transfer between mains and generator supply (in operation mode TEST) and the re-connection to mains supply (in operation mode AUTO) will take place without interruption by means of synchronized change-over. If an L[-] potential is not applied, the change-over between mains and generator supply will take place with configured breaks. Terminal 21: Peak Load Command. If an L[-] signal is connected here and you have selected the operation mode AUTO, the genset starts and synchronises to the mains. It is gradually loaded according to a drive-up ramp. After the peak load command is cancelled, the genset is unloaded, and – if the power falls below the load relief value – the generator is turned off. Terminal 22: Disabled regulation of mains reference load Terminal 23: Sprinkler mode. When an [L-] signal is connected to this terminal, the genset starts without changing over to generator supply, and all alarms serve only as warning ones – except for overspeed (only applicable if an electronic speed controller is in use). The generator switch stays on, it can, however, be parameterised to switch off in the events of generator short-circuit or overload. Terminal 24: Start enable input. Any starting attempt emitted manually or automatically will be interlocked as long as there is no [L-] potential connected to this terminal. It is therefore possible to incorporate relevant pre-start conditions before a signal is given to the starter motor for cranking. If this function is not used, a wire jumper from [L-] to terminal no. 24 must be connected. This function does not meet the requirements of the German Standards DIN VDE 0107, as a running genset will not be shut down; this function only protects the engine before start-up. Terminal 25: Remote start without Load Transfer. When a command is issued to this terminal, the genset starts in the AUTO mode without the generator being switched on. Only if a command is also issued to terminal 18 (Remote start with Load Transfer), the generator breaker will be switched on. To switch off the generator breaker again, both signals (terminals 18 and 25) must be cut! Terminal 26: External command :GENERATOR OFF If a command is applied here, the generator CB is immediately switched off and remains off as long as the signal is applied. _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 17 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 17 / 26 Terminal 27: Power Control in Peak Load Operation. A signal on minus enables 30 % (parameterisable) of the peak load. In combination with terminal 28, 100 % is enabled. If terminals 27 and 28 are not wired, mains parallel operation is disabled. Terminal 28: Power Control in Peak Load Operation. A signal on minus enables 60 % (parameterisable) of the peak load. In combination with terminal 27, 100 % is enabled. If terminal 27 and 28 are not wired, Mains Parallel operation is disabled. Terminal 29: Charging Dynamo, terminal D+. Terminal D+ of the charging dynamo, if present, has to be connected here. An AC-dynamo receives the pre-excitation via this connection, and the [+] signal of the dynamo will cause the starter motor to be switched off. 19. Flags for Alarm Inputs and Relays Genset Genset is running during mains operation Genset available Alarm 1 Alarm 2 Alarm 3 Alarm 4 Alarm 5 Alarm 6 Alarm 7 Alarm 8 Alarm 9 Alarm 10 Alarm 11, closed current Alarm 12 Alarm 12 in, closed current Alarm 13 Alarm 13 in, closed current Alarm 14 Alarm 14 in, closed current Alarm 13 or 14, closed current Alarm 15 Alarm 16 Alarm 17 Alarm 18 Alarm 19 Alarm Battery undervoltage Alarm Engine keeps runningl Alarm cranking failure Alarm Overspeed Alarm Load controller failure Alarm Reverse power Alarm Synchronisation failure Alarm Mains CB does not cut off Alarm Generator does not cut off Alarm Mains CB tripped Alarm Generator CB tripped Alarm Phase sequence, mains Alarm Phase sequence, generator Alarm 33 0D10 4140 3304 2101 2102 2104 2108 2110 2120 2140 2180 2201 2202 5A01 2208 5A02 2210 5A04 2220 5A08 5580 2240 2280 2301 2302 2304 2308 2310 2320 2340 2380 2401 2402 2404 2408 2410 2420 2440 2480 2501 Alarm 34 Alarm 35 Alarm 36 Alarm Generator overcurrent I Alarm Generator overcurrent II Alarm Generator unbalanced currents Alarm Generator thermal overload Alarm Mains undervoltage Alarm Mains overvoltage Alarm Mains underfrequency Alarm Mains overfrequency Alarm Generator underfrequency Alarm Generator overvoltage Alarm Generator underfrequency Alarm Generator overfrequency Cranking speed exceeded Starter motor on Battery undervoltage, closed current Command 1 from remote control panel Command 2 from remote control panel Command 3 from remote control panel Command 4 from remote control panel Command 5 from remote control panel Command 6 from remote control panel Command 7 from remote control panel Command 8 from remote control panel Operation mode OFF is selected 2502 2504 2508 2510 2520 2540 2580 2601 2602 2604 2608 2610 2620 2640 2680 3C01 3E02 4001 6810 6808 6804 6802 6801 6880 6840 6820 0010 Operation mode MANUAL is selected 0020 Operation mode AUTO is selected 0040 Operation mode TEST is selected Operation solenoid on Operation solenoid CANopen failure CAN J1939 failure Speed governor lower Speed governor higher Supply for printer on EMS on Unload the genset Remote control 0080 0F80 4E40 7120 4F08 4B08 4B10 5C20 5E10 4B20 4C80 _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 18 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 18 / 26 Speed of frequency controller lower Speed of frequency controller higher Sensor failure channel 1 Sensor failure channel 2 Sensor failure channel 3 Sensor failure channel 4 Open gas valve Generator overload Relay generator on Generator On pulses Timers time is up, reverse power generator Generator voltage within its limits Pre-gloving on Limit A exceeded channel 1 Limit B exceeded channel 1 Limit A exceeded channel 2 Limit B exceeded channel 2 Limit A exceeded channel 3 Limit B exceeded channel 3 Limit A exceeded channel 4 Limit B exceeded channel 4 Auxiliary drive I Auxiliary drive II Horn on Isolated operation KRV on Coupling breaker off Speed of load controller lower Speed of load controller higher Rated speed exceeded Relay Mains off Mains on pulse Mains operation is on Mains parallel operation Mains voltage within its limits ProMerk, output of NOT-1 ProMerk, output of NOT-2 ProMerk, output of NOT-3 3702 3704 4610 4620 4640 4680 3E08 25F0 3F02 3F08 1480 0E80 3E01 4901 4902 4904 4908 4910 4920 4940 4980 5320 5340 0e02 3708 4C10 4C20 4604 4608 3C04 3F01 3F04 3710 3720 0E04 6201 6202 6204 ProMerk, output of NOT-4 6208 ProMerk, output of NOT-5 ProMerk, output of NOT-6 ProMerk, output of NOT-7 ProMerk, output of NOT-8 ProMerk, output of OR-1 ProMerk, output of OR-2 ProMerk, output of OR-3 ProMerk, output of OR-4 ProMerk, output of OR-5 ProMerk, output of OR-6 ProMerk, output of OR-7 ProMerk, output of OR-8 ProMerk, output of AND-1 ProMerk, output of AND-2 ProMerk, output of AND-3 6210 6220 6240 6280 6701 6702 6704 6708 6710 6720 6740 6780 6101 6102 6104 ProMerk, output of AND-4 ProMerk, output of AND-5 ProMerk, output of AND-6 ProMerk, output of AND-7 ProMerk, output of AND-8 ProMerk, output of Timer 1 ProMerk, output of Timer 2 ProMerk, output of Timer 3 ProMerk, output of Timer 4 ProMerk, output of Timer 5 ProMerk, output of Timer 6 ProMerk, output of Timer 7 ProMerk, output of Timer 8 RZ-071-D, Terminal 1 RZ-071-D, Terminal 2 RZ-071-D, Terminal 3 RZ-071-D, Terminal 4 RZ-071-D, Terminal 5 RZ-071-D, Terminal 6 RZ-071-D, Terminal 7 RZ-071-D, Terminal 8 RZ-071-D, Terminal 9 RZ-071-D, Terminal 10 RZ-071-D, Terminal 11 RZ-071-D, Terminal 12 RZ-071-D, Terminal 13 RZ-071-D, Terminal 14 RZ-071-D, Terminal 15 RZ-071-D, Terminal 16 RZ-071-D, Terminal 17 RZ-071-D, Terminal 18 RZ-071-D, Terminal 19 RZ-071-D, Terminal 20 RZ-071-D, Terminal 21 RZ-071-D, Terminal 22 RZ-071-D, Terminal 23 RZ-071-D, Terminal 24 RZ-071-D, Terminal 25 RZ-071-D, Terminal 26 RZ-071-D, Terminal 27 RZ-071-D, Terminal 28 RZ-071-D, Terminal 29 Common of all warning alarms, operating current Common of all shut-down alarms, operating current Common of all alarms, operating current Common of all warning alarms, closed current Common of all shut-down alarms, closed current Common of all alarms, closed current Check synchroniser on Voltage of voltage controller lower Voltage of voltage controller higher 6108 6110 6120 6140 6180 6301 6302 6304 6308 6310 6320 6330 6340 0410 0408 0404 0402 0401 0580 0540 0520 0510 0508 0504 0502 0501 0680 0640 0620 0610 0608 0604 0602 0601 0780 0740 0720 0710 0708 0704 0702 0701 3804 3810 3840 3808 3820 3880 4C08 3740 3780 _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 19 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 19 / 26 Voltage of cos phi / PF controller lower Voltage of cos phi / PF controller higher Voltage controller lower Voltage controller Sprinkler operation is on Start pre-conditions on Stopping solenoid Synchronisation generator is on Synchronisation mains is on Button Alarm Off Button LED Test TeleAlarm Command 1 TeleAlarm Command 2 TeleAlarm Command 3 TeleAlarm Command 4 TeleAlarm Command 5 TeleAlarm Command 6 TeleAlarm Command 7 TeleAlarm Command 8 Overspeed limit exceeded Alarm monitoring is on VDE-AR-N 4105 Main protection is on ZLT-Command 1 ZLT-Command 2 ZLT-Command 3 ZLT-Command 4 ZLT-Command 5 ZLT-Command 6 ZLT-Command 7 ZLT-Command 8 ZLT-Command 9 ZLT-Command 10 ZLT-Command 11 ZLT-Command 12 ZLT-Command 13 ZLT-Command 14 ZLT-Command 15 ZLT-Command 16 Ignition speed exceeded Ignition on Optional module CANOpen, Input 1, Optional module CANOpen, Input 2, Optional module CANOpen, Input 3, Optional module CANOpen, Input 4, Optional module CANOpen, Input 5 Optional module CANOpen, Input 6 Optional module CANOpen, Input 7 Optional module CANOpen, Input 8 Optional module CANOpen, Input 9 Optional module CANOpen, Input 10 Optional module CANOpen, Input 11 Optional module CANOpen, Input 12 Optional module CANOpen, Input 13 Optional module CANOpen, Input 14 4740 4720 4D02 4D04 2020 3410 3E04 3C40 3C80 0240 0220 6D01 6D02 6D04 6D08 6D10 6D20 6D40 6D80 3C08 0D20 7001 5001 5002 5004 5008 5010 5020 5040 5080 5101 5102 5104 5108 5110 5120 5140 5180 3C02 3E10 0801 0802 0804 0808 0810 0820 0840 0880 0901 0902 0904 0908 0910 0920 Optional module CANOpen, Input 15 Optional module CANOpen, Input 16 Output idle 0940 0980 0000 _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 20. Technical Data 20.1. KEA Controller Device for frontal installation, dimensions: (,, depth) 260 x 170 x 100 mm Weight approx. 2.2 kg, can be installed wherever required Protection class (installed) IP 44 Ambient temperature: Storage -20°C ... +70°C, Operation 0°C … +55°C Supply voltage convertible 9-12-15V or 14-24-35V DC 3 customer-defined relays, 35 V DC, 1 A. (e.g. for acoustic signallers) Standards/regulations VDE 100, Part 710 20.2. Analogue Inputs and Outputs 3-phase mains and generator voltage monitor, set in increments of 1 Volt; if the rotary field is incorrect, the display shows <U. UNom 230/400 volts. They can be set from 50 to 300 volts. Accuracy class 1 Mains and generator frequency monitor 50 or 60 Hz; they can be set to any value between 40 and 70 Hz; accuracy class 1 3-phase generator current monitor; accuracy class 1 INom 5 Amp: measuring range 0.1 – 15 A; it can be set in increments of 20 mA Battery voltage monitor Input for pick-up Option: four analogue inputs, which can be fitted with interface cards for - PT 100 / PT1000 - Current loops - 0 - 10 V DC - Thermocouple NiCr-Ni - Temperature and pressure: VDO sensor Option: two analogue outputs 0 – 20 mA or 0 – 10 V 20.3. Relay Unit RZ 071-D Device for attachment on a mounting rail, dimensions: (,, depth) 300 x 100 x 90 mm Weight approx. 0.7 kg, can be installed wherever required Protection class IP 00 Fitted with: - Input for charging dynamo D+ with pre-excitation for AC alternators - 14 ports for alarm contacts - 14 general control inputs - 12 relays, of which 8 can be configured; contact load: 2 relays max. 35 V, 20 A DC; 10 relays 250 V AC, 6 A. 20.4. Relay unit RZ 071-E (optional) Device for attachment on a mounting rail, dimensions: (,, depth) 210 x 100 x 50 mm, Weight approx. 0.5 kg, can be installed wherever required, protection class IP 00, Fitted with 15 relays, of which 14 can be configured, contact load max. 250 V AC, 6 A 20.5. Serial interfaces Optical fibre or USB interface – with automatic switching – for parameterisation. CAN bus interface to a Digital Control System (DCS) CAN bus interface to Engine Control Unit (ECU); the protocol must be known and implemented 20.6. Connection to other Systems (optional) Device for attachment on a mounting rail: KNG (Kuhse Network Gateway) to connect to other systems via Profibus DP or Modbus RTU _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved. 21 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 21. Diagrams 21.1. Response Diagram for Thermal Overload 21 / 26 ______________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice 22 / 26 21.2. Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 22 / 26 Connection Diagram, RZ-071-D ______________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice 23 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 21.3. Connection Diagram, RZ-071-E (optional) 21.4. Connection Diagram, KEA 201 SPL 23 / 26 ______________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice 24 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 21.5. Connections, analogue Inputs 21.6. Door Cross Section of KEA, Frontview 24 / 26 ______________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice 25 / 26 21.7. Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 25 / 26 Controller PCB with Jumper for Sealing Setpoints ______________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice 26 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 26 / 26 22. Drilling Template, Scale 1:1 – print without scaling! _________________________________________________________________________________ Alfred Kuhse GmbH An der Kleinbahn 39, D-21423 Winsen (lu( Phone: +49 4171-798-0 Fax +49 4171-798-117 kuhse@kuhse.de www.kuhse.de Changes without further notice reserved.