Uploaded by valentinl

kea 201 spl

advertisement
Service Manual
for product: KEA 201 SPL:
Power Control Unit for Emergency and
Peak Load Gensets with overlapping Synchronisation
File: SA_KEA 201 SPL_EN_Ver 2016-07-01 (replaces Version 2014-12-19)
_____________________________________________________________________________________
1.
Design
The control unit is incorporate into the front door of the switchboard. When installed, the front meets the
protection class IP 44. The two rows of LEDs are marked with interchangeable labels. The relay units
are mounted on the mounting plate and linked to the control unit in the door with the supplied cable.
The control unit has an optical fibre and a USB interface for the connection of a PC. Only one of them can
be used at a time
1.1.
Parameterisation
With the parameterisation software PARAWIN, the following settings (password-protected) and analogue
readouts are possible.
1. Additional Interface CAN
2. Additional Parameters
3. Alarm Remote Erasure
4. Alarms
5. Analogue Inputs
6. Analogue Outputs
7. Battery Monitor
8. CAN 0
9. Frequency Controller at isolated Operation
10. Generator Current Monitor
11. Generator Voltage Monitor
12. Hardware
13. Internal Synchroniser
14. J1939 engine management
15. J1939 Hide analogue values
16. Load Controller
17. Mains Voltage Monitor
18. Modem
19. Power Factor Controller
20. ProMerk. programmable Flags
21. Reference Load Regulation
22. Relay and Indicator Functions
23. Speed Monitoring and Control
24. Sprinkler Operation
25. Starting and Stopping
26. Transfer Mains – Generator
27. VDE-AR-N 4105 Protection for Parallel Operation
28. Voltage Controller
Parameterisation can also be performed at the display.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
2 / 26
1.2.
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
2 / 26
Analogue Readouts
 Actual values:
- Mains: Voltages and frequencies
- Generator: voltages, frequencies, current, active and apparent power, PF (for L2)
- Engine speed
- Battery voltage
- Values of the four analogue channels
- Actual status of relays
- Counter, e.g. for Hours of operation until maintenance
- Actual values via CAN, e.g. temperatures and other data from motor, fuel, oil, coolant, battery
and environment
 Present alarms, in total 64 alarms – for generator, oil, engine, mains, etc.
 Voltage monitor:
- L1, L2 and L3 for mains and generator
- Voltage, phase vector, phase angle, frequency
 Signals on the input terminals
 Outputs: Status of relays
 Other Values
 Commands Telealarm
2.
Amendments
Created
Amendments
Version
2014-12-15
Translation from German Version 2014-10-21
2014-10-21
2014-12-19
“Enabling Mains Parallel Operation”: section “Setpoint for Power” added
2014-12-18
- Technical Data: Corrected: Optical fibre or USB interface – with automatic switching
– for parameterisation 2. Removed: Option in preparation: GSM modem
2015-02-10
- Last page: Added: Drilling Template, Scale 1:1 (was down-scaled before)
2016-07-05
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
3 / 26
3.
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
3 / 26
Contents
1.
Design ........................................................................................................................................................1
1.1.
Parameterisation ................................................................................................................................1
1.2.
Analogue Readouts ............................................................................................................................2
2.
Amendments .............................................................................................................................................2
3.
Contents ....................................................................................................................................................3
4.
Safety Instructions ...................................................................................................................................5
4.1.
Regulations and Instructions ..............................................................................................................5
4.2.
Installation and Commissioning ..........................................................................................................5
4.3.
Connections ........................................................................................................................................5
4.4.
Battery and Supply voltage .................................................................................................................5
4.5.
Inductors .............................................................................................................................................5
5.
Connection ................................................................................................................................................5
5.1.
Operating the Display .........................................................................................................................6
5.2.
Setting the Display Contrast ...............................................................................................................6
6.
PIN Number, Ident-Number......................................................................................................................7
7.
Parameterisation Menu Structure ...........................................................................................................7
8.
Alarm Monitoring ......................................................................................................................................8
8.1.
Description ..........................................................................................................................................8
8.2.
Alarm Announcing and Acknowledgement .........................................................................................9
8.3.
Explanation of Alarms.........................................................................................................................9
8.3.1.
Engine keeps running ................................................................................................................................ 9
8.3.2.
Engine fails to start ................................................................................................................................... 9
8.3.3.
Engine fault ............................................................................................................................................... 9
8.3.4.
Overspeed ................................................................................................................................................. 9
8.3.5.
Alarms 13 and 14 ...................................................................................................................................... 9
8.3.6.
Battery voltage Monitor ......................................................................................................................... 10
8.3.7.
Analogue Input Alarms ........................................................................................................................... 10
8.3.8.
Mains CB tripped .................................................................................................................................... 10
8.3.9.
Mains CB does not cut off ....................................................................................................................... 10
8.3.10.
Generator CB tripped .............................................................................................................................. 10
8.3.11.
Generator CB does not cut off ................................................................................................................ 10
8.3.12.
Alarms of the voltage monitors .............................................................................................................. 10
8.3.13.
Monitoring of the currents ..................................................................................................................... 10
8.3.14.
Synchronisation failure ........................................................................................................................... 10
8.3.15.
Load controller failure ............................................................................................................................ 10
8.3.16.
PF controller failure ................................................................................................................................ 11
8.3.17.
Reverse power ........................................................................................................................................ 11
8.3.18.
Running hours till Maintenance elapsed ................................................................................................ 11
8.3.19.
Maintenance period exceeded ............................................................................................................... 11
9.
Mains Failure Protection in Parallel Operation ....................................................................................11
9.1.
Monitoring Deviations in Voltage and Frequency .............................................................................11
9.2.
Vector Shift .......................................................................................................................................11
9.3.
Sealing the Setpoints ........................................................................................................................12
9.4.
Mains Failure Protection according to E VDE-AR-N 4120 ...............................................................12
10. Mains Reference Load Control Operation ...........................................................................................12
11. Peak Load Operation Mode ...................................................................................................................13
12. Mains Operator’s Load Levels ..............................................................................................................13
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
4 / 26
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
4 / 26
13. Enabling Mains Parallel Operation .......................................................................................................13
13.1. Description ........................................................................................................................................13
13.2. Setpoint for Power ............................................................................................................................14
14. Mains Recovery in Peak Load Operation .............................................................................................14
15. Power Control .........................................................................................................................................14
15.1. Frequency Range 50.2 - 51.5 Hz .....................................................................................................14
16. Controlling Reactive Power ...................................................................................................................15
17. Sprinkler Operation ................................................................................................................................15
18. Connection of Relay Unit RZ 071-D ......................................................................................................15
Terminals 1–14: Input for alarms signals. ................................................................................................................ 15
Terminal 15: Feedback signal: MAINS CB IS OFF. ......................................................................................................... 15
Terminal 16: Feedback signal: GENERATOR CB IS OFF. .................................................................................................. 16
Terminal 17: Operation mode selection is locked. ................................................................................................... 16
Terminal 18: Remote start with Load Transfer. ....................................................................................................... 16
Terminal 19: IMMEDIATE STOP. .................................................................................................................................... 16
Terminal 20: Overlapping synchronisation active. ................................................................................................... 16
Terminal 21: Peak Load Command........................................................................................................................... 16
Terminal 22: Disabled regulation of mains reference load ...................................................................................... 16
Terminal 23: Sprinkler mode. ................................................................................................................................... 16
Terminal 24: Start enable input. .............................................................................................................................. 16
Terminal 25: Remote start without Load Transfer. .................................................................................................. 16
Terminal 26: External command :GENERATOR OFF ...................................................................................................... 16
Terminal 27: Power Control in Peak Load Operation. .............................................................................................. 17
Terminal 28: Power Control in Peak Load Operation. .............................................................................................. 17
Terminal 29: Charging Dynamo, terminal D+. .......................................................................................................... 17
19. Flags for Alarm Inputs and Relays .......................................................................................................17
20. Technical Data ........................................................................................................................................20
20.1. KEA Controller ..................................................................................................................................20
20.2. Analogue Inputs and Outputs ...........................................................................................................20
20.3. Relay Unit RZ 071-D ........................................................................................................................20
20.4. Relay unit RZ 071-E (optional) .........................................................................................................20
20.5. Serial interfaces ................................................................................................................................20
20.6. Connection to other Systems (optional) ...........................................................................................20
21. Diagrams .................................................................................................................................................21
21.1. Response Diagram for Thermal Overload ........................................................................................21
21.2. Connection Diagram, RZ-071-D .......................................................................................................22
21.3. Connection Diagram, RZ-071-E (optional) .......................................................................................23
21.4. Connection Diagram, KEA 201 SPL .................................................................................................23
21.5. Connections, analogue Inputs ..........................................................................................................24
21.6. Door Cross Section of KEA, Frontview ............................................................................................24
21.7. Controller PCB with Jumper for Sealing Setpoints ...........................................................................25
22. Drilling Template, Scale 1:1 – print without scaling! ..........................................................................26
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
5 / 26
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
4.
Safety Instructions
4.1.
Regulations and Instructions
5 / 26
1. The relevant regulations, especially the VDE regulations, must be observed.
2. The device must be parameterised in such a way that any risk to persons or property is prevented.
4.2.
Installation and Commissioning
Only adequately qualified personnel should undertake the installation and commissioning.
4.3.
Connections
1. Care must be taken when connecting the device, as it may be destroyed if incorrectly connected.
All details of the connection specifications must be fulfilled.
2. For safety reasons, the PE(N) must be connected to terminal 5 on the X403.
3. The shielding of the analogue wiring must only be connected the earth screws beside the terminal
strip X401 on the KEA cover and may have no connection to any other metal parts.
4. The transformer connections k are to be connected to the protective conductor.
4.4.
Battery and Supply voltage
1. Before the battery is disconnected, the charging device must be switched off.
2. The negative pole of the battery must be grounded at the input terminal of the switchboard. The
minimum conductor diameter is 10 mm2.
3. The supply voltage is to be set to 12 or 24 V DC with a switch on the RZ 071-D.
4. When the supply voltage of the control unit has been switched off, you must wait at least 20 seconds before applying it again.
5. The leakage current of the noise filters is 22 mA in case of a 2-phase voltage lost.
4.5.
Inductors
All coils must be fitted with reverse diodes to prevent high voltage peaks. All other coils or inductive loads
must also be fitted with suppressor elements. The same applies for all relays and inductors that are used in
the switchboard or controlled externally.
5.
Connection
1.
2.
3.
4.
5.
6.
7.
8.
Only trained experts may make the connections of the KEA.
For safety reasons, the PE(N) must be connected to terminal 5 on the X403.
Before the battery is disconnected. The charging device must be switched off.
When the supply voltage of the control unit has been switched off, you must wait at least 20 seconds before applying it again.
The negative pole of the battery must be grounded at the input terminal of the switchboard. The
minimum conductor diameter is 10 mm2.
The supply voltage is to be set to 12 or 24 V DC with a switch on the RZ 071-D.
The shielding of the analogue wiring must only be connected the earth screws beside the terminal
strip X401 on the KEA cover and may have no connection to any other metal parts.
All coils must be fitted with reverse diodes to prevent high voltage peaks. All other coils or inductive loads must also be fitted with suppressor elements. The same applies for all relays and inductors that are used in the switchboard or controlled externally.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
6 / 26
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
6 / 26
The following signals (if needed) are directly applied to the control unit:







Voltage of mains and generator
Current of generator
Four analogue sensors
Pick-up
Two analogue output signals
Optical fibre or USB for parameterisation
Two CAN bus systems.
Although the control system is protected against reverse polarity, the correct polarity when connecting the battery voltage must be strictly observed, as reverse diodes or other electronic parts of the
switchboard may possibly be damaged.
The fuse on the RZ 071-D will be blown if the control system is connected with the wrong polarity!
Due to the fact that most of the control relays may be configured for various functions, only the
status print out of the supplied control unit is to be considered as a binding document. It must be
observed, that in case of a possible replacement of a unit, any modifications made after commissioning cannot be taken into account by the manufacturer.
5.1.
Operating the Display
Values or parameters are selected, as you would read a book. The groups listed further down are
arranged as 'pages'. You can scroll forwards and backwards through these groups by pressing the
[→] and [←] keys. The entries of each group can be read from top to bottom like lines of a text.
Select a line by pressing the keys [↓] (down) and [↑] (up). The selection starts again with the other
end of the 'page', when the top or bottom of the 'page' is reached.
To select directly the ACTUAL VALUES group: hold down the LED TEST button, and press [←].
To display the group CURRENT ALARMS hold down LED TEST and press [→].
To modify a parameter: first enter the relevant IDENT-NUMBER.
Note: Parameters of group 0, -GENERAL PARAMETERS-, can be modified without entering this number.
Parameters are modified as follows:
1. Select the required parameter group with the [←] and [→] buttons.
2. Select the required parameter line with the [↓] and [↑] buttons.
3. Press OFF and LED TEST (function: PARA ON or PARA OFF) together. This opens parameterisation
mode as can be seen by the specific cursor [ █ ]. The selection of the group cannot be changed
now.
4. Press [↓] / [↑] to select the desired parameter.
5. Press OFF and ALARM OFF (ENTER function) together to select the parameter line. The shape of
the cursor confirms the selection, as it underscores (e.g. 196) now the part of the parameter that is
to be modified. The chosen parameter cannot be deselected now.
6. Select the figure or letter of the parameter that you want to modify with the [←] and [→] cursor
keys. Numerical parameters can be increased or decreased by increments of 1 with the [↑] and [↓]
buttons. Press the same buttons to negate parameters that are displayed with a letter (+/- signs,
alarm coding etc.).
7. Press OFF and ALARM OFF together to store the displayed parameter.
Press OFF and LED TEST to abort parameterisation.
5.2.
Setting the Display Contrast
 Hold down LED TEST and press key [↑] to increase the display contrast (makes the display darker)
 Hold down LED TEST and key [↓] to lower it (makes the display lighter).
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
7 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 7 / 26
6.
PIN Number, Ident-Number
To modify a parameter, you first have to enter the relevant IDENT-NUMBER. This number is compared
with the PIN NUMBER, and if they are identical, the user is authorised to parameterise the device. The
user can chose any PIN NUMBER between 00000 and 50000. The PIN NUMBER and IDENT-NUMBER are
factory-set to 00000.
A special IDENT-NUMBER can be enquired from the factory if you forget your PIN NUMBER, so that a
new PIN NUMBER can be entered. Modify the PIN NUMBER as follows:
1.Enter the currently valid Ident-Number. The pin number is now also shown.
2.Enter a new PIN Number.
The Ident-number previously entered is now no longer valid.
The IDENT-NUMBER is deleted 15 minutes after the last input, if the user has not previously set it to an
invalid value.
The automatic deletion of the IDENT-NUMBER is, however, not carried out while 00000 is set as
the PIN.
7.
Parameterisation Menu Structure
Group 0
KEA 201 SPL
KUHSE GmbH
Group 1
ACTUAL VALUES
Group 2
ENCODING OF
ALARMS
COUNTERS
Group 3
Group 4
MAINS VOLTAGE
MONITOR
GENERATOR
PROTECT: PARALLEL
OPERATION
GENERATOR
MONITOR
CURRENT MONITOR
MONITOR
Group 5
ANALOGUE
INPUTS
Group 6
SPEED MONITORING
SPEED GOVERNOR
ANALOGUE
OUTPUTS
Group 7
Group 8
START-STOP
ADD. FUNCTIONS
CHANGE OVER OF
MAINS-GENERATOR
Group 9
RELAY- /LED
FUNCTIONS
BATTERY VOLTAGE
MONITOR
ADDITIONAL
PARAMETERS
Group 10
LOAD CONTROLLER
PF CONTROLLER
PF CONTROLLER
Group 11
SYN. FUNCTION
f/U CONTROL
Group 12 *)
ENGINE CONTROL
ACTUAL VALUES
Group 13
NO ALARMS
PRESENT
Group 14*)
ENG. CONTROLLER
CURRENT ALARMS
FREQUENCY CONTR.
VOLTAGE CONTROL
MAINS REFERENCE
LOAD
*) Group 12 and 14 only displayed if there is a CAN connection to the genset.
The functions and parameterisation are described in FUNCTIONS AND PARAMETERISATION OF KEA
101-112 – please refer to our Website under http://www.kuhse.de/en/download/operatinginstructions/diesel-genset-controls.html.
This document contains all possible functions featured in the KEA Series 101-112 and is also valid for
the new KEA series 201-252. Please note however, that only those functions, listed in the service
manual, are actually implemented. The PARAW IN parameterisation software also shows only the
parameters that are possible for the particular control unit.
Additional processes for the
 peak load operation according to VDE-AR-N 4105
 mains failure detection according to E VDE-AR-N 4120 (as of Version 9)
 sprinkler operation according to VdS 2100-22:2008-11
are described further below.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
8 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 8 / 26
Group
2
3
3
4
4
5
5
6
7
7
7
8
9
10
10
10
11
11
11
Function
Encoding of alarms
Mains voltage monitor
Mains failure protection
Generator voltage monitor
Generator current monitor
Analogue inputs
Analogue outputs
Speed monitoring, Switching points
Start-stop functions
Additional parameters
Battery voltage monitor
Parameter for mains-generator switchover
Settings for relays and indicators
Power controller
PF controller
Reference load controller
Synchronizer
Frequency controlling in stand-alone operation
Voltage controlling in stand-alone operation
User manual
8.
Alarm Monitoring
8.1.
Description
Section in FUNCTIONS AND PARAMETERISATION
Alarm Monitoring
Voltage Monitor
Mains failure monitoring in parallel operation
Voltage monitor
Current monitor
Analogue interface
Analogue interface
Speed monitoring
Start and Stop
Additional parameters
Additional parameters
Mains-Generator switchover
Setting of relays
Power und PF controller
Power und PF controller
See further below
Synchronisation
Synchronisation
Synchronisation
See BA_KEA 201_SPL
The control unit can control up to 64 alarms. The texts and trigger inputs for alarms 1 to 19 and 49 to
64 are variable, i.e. their texts and actuation are determined by the parameterisation software
PARAWIN. The alarms are actuated by terminals 1 to 14 or free terminals on the relay unit RZ 071-D or
by internal flags (e.g. controller failures, limit value on an analogue channel too high, etc.). The
parameterisation is described above.
Alarms can be divided into three groups:
 Alarms that are monitored only after a delay when the engine is running (e.g. LOW LUB OIL
PRESSURE), called DELAYED. The green MONITORING ON indicator shows that they are monitored.
 Alarms, which are monitored even when the engine is at a standstill, except in operation mode
OFF, (e.g. BATTERY UNDERVOLTAGE), called UNDELAYED.
 Alarm signals 13 and 14 are always monitored, even in operation mode OFF. They are used for
alarms such as LEAKAGE. In operation mode OFF the audible signal is not switched on, but the
alarms are collected together in common alarms. They act just like normal alarms when any other
operation mode than OFF is selected.
The alarms are configured as follows:
 Alarm is active or inactive
 Contact is normally open or normally closed
 Delayed or undelayed monitoring
 Warning or shutdown
 In addition for warning alarms: With or without generator cut off and stop after the re-cooling period
in AUTO mode.
The genset is stopped after the re-cooling period and the automatic control is locked if the
generator is cut off after a warning alarm in the AUTO mode.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
9 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 9 / 26
At terminal inputs, an alarm is triggered when the corresponding signalling switch closes (normally
open, make contact) or opens (normally closed, break contact). In case of analogue signals an alarm
is triggered, when the actual value is higher than the UPPER LIMIT (alarm pre-set for make contacts) or
the actual value is lower than the LOWER LIMIT (alarm pre-set for break contacts). Alarms 11 to 14 can
additionally be parameterised as break signals of output relays, i.e., the corresponding relay is
activated when the alarm is inactive.
8.2.
Alarm Announcing and Acknowledgement
As long as no new alarm is waiting for acknowledgement, the ACTUAL ALARMS group can be selected
with the [←] and [→] buttons, or by pressing LED TEST and the [→] button at the same time.
The indicator COMMON ALARM (yellow one in the left row of the panel) is flashing when an unacknowledged alarm is present. The acoustic signal is switched on at the same time. Press the ALARM OFF
button to turn off the acoustic signal and bring up the page of the ACTUAL ALARMS on the display.
The alarm text is preceded either by <NEW> if the alarm has not been acknowledged or <ACKN> if it
has been acknowledged.
NEW
GENERATOR
OVERLOAD
ACKN
GENERATOR
OVERLOAD
Unacknowledged alarm
Acknowledged alarm
NO ALARMS
PRESENT
Display when no alarms
are activated
Press the ALARM OFF button to acknowledge the indicated alarm or to delete a previously acknowledged alarm if the cause of the malfunction has been removed.
When all alarms have been acknowledged, the COMMON ALARM indicator stops flashing and lights
up steadily. It starts to flash again when a new alarm is notified.
The COMMON ALARM switches off when all alarms have been deleted. Move through the activated
alarms with the [↑] and [↓] buttons to acknowledge or delete them with the ALARM OFF button.
If no alarms are pending, the announcement -NO ALARMS PRESENT is displayed.
If the generator is switched off by a warning alarm whilst in AUTO mode, the motor is stopped
after the re-cooling time, and the automatic mode is locked.
8.3.
Explanation of Alarms
8.3.1.
Engine keeps running
This alarm is announced when the engine is still running after the stop procedure. It means that the
stopping equipment of the engine (stopping solenoid, gas valve, etc.) is defective.
8.3.2.
Engine fails to start
This alarm comes up (and the automatic operation is locked) when the engine is not running after the
start sequence.
8.3.3.
Engine fault
This alarm is activated if the engine stops without having a stop command from the control unit. The
control system is locked at the same time.
8.3.4.
Overspeed
The generator frequency or a pick-up signal is used for monitoring overspeed. The alarm GENERATOR
UNDERVOLTAGE must be enabled as a shutdown alarm when the generator frequency is used. This
also protects the engine if the generator voltage fails.
8.3.5.
Alarms 13 and 14
The input signals for these two alarms can be delayed for 0 to 240 seconds. That means that the
alarm contact must be activated for the programmed time before the alarm comes up. Furthermore
these two alarms are also enabled in the operation mode OFF, however without the audible signal.
Fault signals, which have to be always signalled, can be monitored by this (e.g. tank filling level,
leakage).
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
10 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 10 / 26
8.3.6.
Battery voltage Monitor
A relay (with a break function) can be programmed for the direct output of the battery voltage monitor.
It is energised if the voltage is good. A remote signal is possible by this even in the operation mode
OFF.
8.3.7.
Analogue Input Alarms
The analogue inputs can be fitted with modules for various sensors (PT100, PT1000, current loops,
thermal elements, VDO sensors, MotoMeter for engine temperature and oil pressure etc.). For each
analogue input, two threshold levels can be set to trigger an alarm.
8.3.8.
Mains CB tripped
The mains circuit breaker can be monitored for automatic tripping (e.g. by an installed over-current
tripping device). The alarm is internally triggered if no feedback signal M AINS CB IS ON is detected after
running out of the mains CB closing pulse.
Furthermore it can be selected whether the engine should start and take the load or not (according to
VDE standard 0107) in the operation modes AUTO or TEST. The alarm must in this case be cancelled
for switching back to mains supply after the switch-back delay.
8.3.9.
Mains CB does not cut off
The alarm occurs when the mains CB is not off two seconds later after the Off-command. This alarm
can control a relay by which an additional mains coupling breaker can be switched off to allow the
generator to supply the consumers.
8.3.10. Generator CB tripped
The generator circuit breaker can be monitored for automatic tripping (e.g. by an installed over-current
tripping device). Additionally the mode WARNING/SHUTDOWN must be programmed for this alarm. The
alarm is internally triggered in case no feedback signal G ENERATOR CB IS ON is detected after running
out of the generator closing pulse.
8.3.11. Generator CB does not cut off
The alarm occurs when the generator CB is not off two seconds later after the Off-command. The
genset gets an internal start command and by this keeps the engine running and the generator CB
remains on.
The engine stops when in this case a shutdown alarm occurs. An additional generator coupling
breaker can be switched off by a programmed relay to prevent that the engine is operated with reverse
power.
8.3.12. Alarms of the voltage monitors
An alarm is announced if a monitored voltage or frequency of mains or generator is out of its range.
The alarm itself has no influence of the actual voltage or frequency monitoring. That means, if the
monitor has stated a failure and triggered the alarm and later on the monitored function is again within
its limit, the alarm is still present until it is cancelled. For the internal controlling however, the actual
state is used which means, that the monitored function is effective as NORMAL.
8.3.13. Monitoring of the currents
The generator currents can be monitored for
 overcurrent (e.g. 110 %)
 short-circuit (e.g. 300 %)
 unbalanced currents and
 thermal overload.
The Response Diagram for Thermal Overload, is shown further below.
8.3.14. Synchronisation failure
A timer is started when the synchronisation begins. An alarm is triggered if no synchronisation has
happened when this delay time is up. It is programmable if in this case a changeover with a break is
done or if the synchronisation remains on.
8.3.15. Load controller failure
An alarm is indicated when after a pre-set time the actual load has not matched the pre-set load value
(the actual load has to be at least once inside the dead zone). The genset can be stopped or a peak
load command can be removed in this case.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
11 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 11 / 26
8.3.16. PF controller failure
An alarm is indicated when after a pre-set time the actual PF has not matched the pre-set PF (the
actual PF has to be at least once inside the dead zone). The genset can be stopped or a peak load
command can be removed in this case.
8.3.17. Reverse power
The generator CB must be switched off if the engine fails in parallel operation.
8.3.18. Running hours till Maintenance elapsed
The remaining running hours till the maintenance of the engine is shown in S ETPOINTS. A warning
alarm (if programmed) is given if the time period has elapsed. The counter for the time period till the
next maintenance must be set after the first one is done. This is only possible with ParaWin by
authorized persons. In case the goodwill period is set to 0 hours, this counter will stop at zero hours
and not show negative hours when the period is exceeded.
8.3.19. Maintenance period exceeded
An additional alarm (if programmed) occurs if the normal period and the additional goodwill period are
over. The reset is only possible for authorized persons. No alarm will occur in case the goodwill period
is set to 0 hours. This alarm can only be reset by the supplier!
9.
Mains Failure Protection in Parallel Operation
The mains voltage is monitored according to the limits of the VDE-AR-N 4105 or E VDE-AR-N 4105.
In addition, the voltage controller can be enabled for standard emergency power operation. This
applies to VDE-AR-N 4105 only. Due to the reduced tolerances of this standard, sensitive consumers
are safeguarded against too large deviations.
After parallel operation is established, the parameterised time elapses before the monitoring is
activated. This allows voltage, current and frequency to settle after the synchronisation. Should
subsequently a mains failure be detected, the mains switch is instantly set to OFF, and the standard
mains voltage monitor to Undervoltage. In this case, the parameterised delay for the mains voltage
monitor is disabled. Depending on the actual operating mode, the genset switches to idle emergency
mode or shuts down.
Even a brief interruption of the mains triggers the voltage monitor’s delay to run after the mains
voltage has recovered. According to the genset’s operation mode, it synchronises to the mains, or – in
case of genset standstill – the mains is switched on again. All below-listed additional functions can be
enabled or disabled for mains failure detection. This applies to the VDE-AR-N 4105 only.
9.1.
Monitoring Deviations in Voltage and Frequency
This monitoring can be enabled as a supplement to the requirements according to the VDE-AR-N
4105. After each measurement, voltage and frequencies values of the mains are stored and compared
to the previous values, even if the systems are not running in parallel. If in parallel operation, the
difference between the previous and current value (du/dt, df/dt) exceeds the parameterised value, this
is indicated as a mains failure. These measurements allow large deviations in voltage or frequency to
be treated as mains failures.
9.2.
Vector Shift
This monitoring can be enabled as a supplement to the VDE-AR-N 4105. The time duration of the
present voltage period is compared to the previous one. A deviation is converted to degrees. This is a
measurement of a vector shift. If the deviation exceeds the parameterised reference value, it is most
likely that a mains failure has occurred.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
12 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 12 / 26
9.3.
Sealing the Setpoints
Inside the KEA, on the middle PCB – see Controller_PCB further below – you will find a jumper. If you
remove this, you will no longer be able to modify the following parameters:
 Mains failure if du/dt > … Hz
 du/dt enabled
 Mains failure if df/dt > … Hz
 df/dt enabled
 Mains failure if vector shift > … degrees
 Vector shift enabled?
If the jumper is removed and the KEA cover sealed, the setpoints you have entered cannot be
changed. Setting the mains voltage monitoring to 110 % according to VDE-AR-N 4105 is only
modifiable with ParaWin and password. All other limits are fixed.
9.4.
Mains Failure Protection according to E VDE-AR-N 4120
On the low-voltage side of a medium-voltage system, the monitoring proposes deviating functions for
switching off the generator. These requirement are met by KEA 201 SPL03 as of version 9.
Implemented setting ranges:
Function
U>>
U>
U<
U<<
f>
f<
10.
Setting range
1.00 – 1.30 UNS
0.3 – 1.00 UNS
0.3 – 1.00 UNS
0.3 – 1.00 UNS
47.00 – 50.00 Hz
50.00 – 52.00 Hz
max. 100 msec
0.0 – 300 sec
0.0 – 300 sec.
max. 300 msec.
< 100 msec.
< 100 msec.
Settings, e.g. EON Mitte (German electricity provider)
1.15 UNS, no delay (< 100 msec.)
1.1 UNS, delay: 60 sec.
0.8 UNS, delay: 1 sec.
0.45, UNS, no delay (< 100 msec) (required: 0 sec).
51.50 Hz, no delay, (< 100 msec)
47.50 Hz, no delay (< 100 msec)
Mains Reference Load Control Operation
When the specified mains reference load is exceeded, the genset starts, but not until after a time
delay (max. 240 sec.) to suppress unnecessary starts. Upon parallel connection of mains and
generator, the controlling is based on a parameterised reference load.
The mains reference load must be larger than or equal to the difference between the genset’s stop
loading and the starting point.
As soon as the consumer load falls, the generator output is reduced in order to maintain the parameterised load level at its reference. If the generator output falls below the generator power setpoint, the
start command to the genset will be cancelled – after a delay. The genset unloads to the minimum that
is set and then shuts down.
Now the mains reference load rises by the amount of the aborted genset power. Hence, select the
parameter values so as to ensure the starting point is not immediately exceeded once again.
In order to protect against return feed into the mains, a limit is provided. If this is fallen short of, the
genset is immediately turned off. Always select the parameters so that the aborted power does not
cause the starting point to be exceeded. This signal can be parameterised as an error message.
High and Low-Tariff (HT and LT)
The starting point of the maximum mains load and the succeeding control can be set differently for
high and low-tariff periods. Likewise, the starting and ending times of the low-tariff period can be
entered. This also allows the load control to be switched off during the LT periods.
Furthermore, for both periods, the power control can be switched off via a switch on the relay unit.
The power limitation according to VDE-AR-N 4105 is valid for parallel operation, provided the monitoring is enabled in ParaWin.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
13 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 13 / 26
11.
Peak Load Operation Mode
1. The genset is started by a peak load command. If the genset is already running in TEST mode,
the system switches to parallel operation.
2. After parallel operation is accomplished, the internal power and PF controller is enabled and the
generator loaded. During the parallel operation, the internal power and PF (cos φ) control unit
is enabled and the generator loaded. The internal power and PF control is described further
below.
3. After the peak load command is disabled in AUTO mode, the genset is unloaded – and at a load
of 10 % of the generator switched off.
If the peak load command is given TEST or M ANUAL mode, you should switch back to the AUTO
mode to allow all following automatic processes to run.
The KEA 201 can detect a power failure during peak load operation. The KEA will then directly switch
off the mains, thus immediately shifting to emergency power operation.
After mains recovery and elapsed switch-back delay, the genset will synchronise with the mains. A
pending peak load command will cause the system to return to mains parallel operation – or switches
off if there is no start command.
12.
Mains Operator’s Load Levels
The mains operator is to specify the maximally allowed load in the following steps: 0%, (stop) 30%,
60%, and 100% (full load). For this, two terminal inputs are provided:
Terminal on RZ-071-D
Terminal 27
Terminal 28
Enabled power
(percentage of nominal load)
*) Not connected
Open*
Open*
0% (stop)
Input signal
L[-] **
Open*
Open*
L[-] **
30%
60%
L[-] **
L[-] **
100%
**) Connected
13.
Enabling Mains Parallel Operation
13.1.
Description
The start is enabled if for at least 60 sec. the following is met:
 Frequency in the range 47.5 Hz - 50.05 Hz
 Voltage in the range 85 % - 110 % of UNOM
In addition, a percentage load of 30, 60 or 100 % must be specified.
If the genset operates in parallel with the mains, the mains failure monitoring, power and PF controlling operate according to the VDE-AR-N 4105. This can be supplemented with the internal vector
shift relay.
The line-to-line voltages are to be calculated from the phase-to-neutral voltages. For this, clockwise rotation fields at the measurement inputs are mandatory, the mains and generator monitoring for the isolated operation thereby switched off.
The switching points of the VDE monitoring system can be changed via a special password and
can also be sealed.
After a power failure, the protection against overvoltage (>U, averaged over 10 min.) is continuously determined until measurements of most-recent 10 min. are available. Consequently, if for
instance the value averaged over the first 3 min. already exceeds 110 % of the nominal voltage, the
mains failure is instantly detected – rather than not until after 10 min.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
14 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 14 / 26
In M ANUAL parallel operation (i.e. no peak load command) the generator voltage monitor will also
switch over to the VDE-specified thresholds. For the VDE-AR-N 4105, these are:
Voltage drop protection
Voltage increase protection
Voltage increase protection
Frequency drop protection
Frequency increase protection
Absolute value
Averaged over 10 min.
Absolute value
Absolute value
Absolute value
U<
U>
U>>
f<
f>
0,85 UNom
1.10 UNom
1.15 UNom
47.5 Hz
51.5 Hz
The settings according to VDE-AR-N 4120 are listed forth above.
For frequencies in the range 47.5 Hz – 50.00 Hz, a separation in consequence of a frequency
deviation is not permitted.
For the 5 most-recent events, date and time are stored, readable via the USB connection. Apart
from the average U>, all switching points are fixed.
By setting different thresholds for the mains and the generator monitor in parallel and emergency
operation (incl. sprinkler operation) according to VDE-AR-N 4105, you will be able to narrow the
limits.for emergency operation Please note that after a mains failure and switching to emergency
operation, the frequency and voltage control must under certain circumstances quickly bring the
system back into the specified limits.
13.2.
Setpoint for Power
The setpoint for mains parallel operation can be predefined:
 as an analogue signal, channel 4
 via a ZLT
 or as a parameterised fixed value.
An external setpoint value is stated as per mill of the nominal value, and the fixed value is stated in
kW. If the analogue channel is used, the minimum and maximum reference value are to be parameterised accordingly.
14.
Mains Recovery in Peak Load Operation
The start is enabled if the following is met:
 Frequency in the range 47.5 Hz - 50.05 Hz
 Voltage in the range 85 % - 110 % of UNOM
The delay after a power failure that lasts longer than 3 sec. is at least 60 sec. For power failures
lasting less than 3 sec. (short-time interruption), the synchronisation process can start after just 5 sec.
15.
Power Control
Via two inputs, the mains operator is to set a power limitation, the respective percentage restriction configurable. The reduction of the enabled amount of power takes place within a minute. For
the frequency range 47.5 Hz – 50.2 Hz, there is no further limitation of the power emitted.
Terminal on RZ-071-D
Terminal 27
Terminal 28
Enabled power
(percentage of nominal load)
*) Not connected
15.1.
Open*
Open*
0% (stop)
Input signal
L[-] **
Open*
Open*
L[-] **
30%
60%
L[-] **
L[-] **
100%
**) Connected
Frequency Range 50.2 - 51.5 Hz
If the frequency is equal to or higher than 50.2 Hz, it is not permitted to increase the power.
Instead, the present power level (at 50.2 Hz) is held.
Should the frequency still increase, the setpoint value of the power controller transforms into a
linear function with a slope of 40 % pro Hertz of the value at 50.2 Hz until it is switched off at 51.5
Hz, i.e. maximally reduced by 52 %.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
15 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 15 / 26
If the frequency decreases, the power is increased according to the specified gradient until it
reaches the level at 51.5 Hz.
If the frequency still decreases, the genset can be operated with the enabled power level. In this
case, an increase in power will occur in steps of 10 % of the enabled power per minute. This is
followed by standard controlling.
Upon mains recovery, the power is increased in steps of 10 % per minute until it reaches the
required level. This is followed by standard controlling.
16.
Controlling Reactive Power
The VDE-AR-N-4105 specifies a characteristic curve or a fixed factor for the PF (cos φ). After a
start, the amount of reactive power is reached within 10 minutes. Values for the characteristic curve
are reached within 10 sec.
A standard curve specifies: Load in the range:
 0 % - 20 %: setpoint for cos φ = -/+ 0,9
 20 % - 50 %: setpoint for cos φ = -/+ 1.0
 50 % - 100 5: setpoint for cos φ linear in the range
Tables oft the standard setpoints
Power
cos φ underexited
cos φ overexited
0 - 20%
0.9
0.9
20-50%
1.0
1.0
50-100% linear decrease from 1.0 to 0.90 underexited
17.
Sprinkler Operation
The following functions are provided for operation of an electric sprinkler pump:
 Set all alarms as warning ones
 Start sequence with 10 (can be set by customer) start attempts,
 For the run-up of the sprinkler pump: pause or no pause for the emergency consumers,
 You can select when the sprinkler is no longer required, if the Sprinkler operation is cancelled after
the COOLING DOWN PERIOD AFTER SPRINKLER or is manually switched off.
The time stage for the COOLING DOWN PERIOD AFTER SPRINKLER CAN be set from 10 to 2400 seconds.
The sprinkler operation is not terminated automatically but must be ended manually if this stage is set
to 0 seconds.
In this is the case, the OFF mode indicator flashes.
The genset can now only be stopped via IMMEDIATE STOP or the mode OFF.
The pause duration of the emergency supply for the run-up of the sprinkler pump can be set from 0 to
24 seconds. The emergency consumers are not switched off if it is set to 0 sec.
The consumers are switched to generator supply if during the sprinkler operation a mains failure or a
remote start with load transfer occurs. The emergency consumers are switched back after expiry of
mains recovery delay when the mains voltage is restored or the remote start command is cancelled.
The sprinkler mode prevents that the genset is switched off or shut down due to an alarm. If a
shutdown alarm is triggered, however, the common alarm SHUTDOWN is issued.
18.
Connection of Relay Unit RZ 071-D
Terminals 1–14: Input for alarms signals.
Terminal 15: Feedback signal: MAINS CB IS OFF.
An auxiliary contact (NC) of the mains CB (or contactor) is connected to this terminal. It shows the
position of the breaker. The control unit is fitted with an interlocking circuit which prevents the generator from switching on (without synchronising) as long as the mains supply is on.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
16 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 16 / 26
Terminal 16: Feedback signal: GENERATOR CB IS OFF.
An auxiliary contact (NC) of the generator CB (or contactor) is connected to this terminal. It shows
the position of the breaker. The control unit is fitted with an interlocking circuit that prevents the
mains from switching on (without synchronising) as long as the generator supply is on.
Terminal 17: Operation mode selection is locked.
The selection of the operation modes by the push-buttons will be locked if a signal is applied at this
terminal. A key-operated switch, to prevent the selected mode from being changed by unauthorised
persons or by mistake, could perform this.
Terminal 18: Remote start with Load Transfer.
If an L[-] signal is connected, and the system is running in operation mode AUTO, the genset starts
with switchover to generator operation.
If the system is in TEST mode or has been started in AUTO mode via the command START WITHOUT
LOAD TRANSFER, the generator is automatically switched on.
If an L[-] potential is not applied – command START WITHOUT LOAD TRANSFER must not be displayed,
the generator will – upon the switch-back delay – be switched off, and the genset turned off – after
the delay.
Terminal 19: IMMEDIATE STOP.
The signal can be parameterised as normally-closed or normally-open – KEA display, Group 6,
PARAWIN, under ADDITIONAL PARAMETERS . The genset will be immediately shut down if a signal is
applied to this terminal. The control unit will be locked for any further starting attempts. To reset the
control unit, the operation mode has to be set to OFF. Resetting is only possible if the signal is no
longer connected, otherwise the indicator AUTOMATIC LOCKED would remain on.
Terminal 20: Overlapping synchronisation active.
If an L[-] signal is connected here, the load transfer between mains and generator supply (in operation mode TEST) and the re-connection to mains supply (in operation mode AUTO) will take place
without interruption by means of synchronized change-over.
If an L[-] potential is not applied, the change-over between mains and generator supply will take
place with configured breaks.
Terminal 21: Peak Load Command.
If an L[-] signal is connected here and you have selected the operation mode AUTO, the genset
starts and synchronises to the mains. It is gradually loaded according to a drive-up ramp. After the
peak load command is cancelled, the genset is unloaded, and – if the power falls below the load
relief value – the generator is turned off.
Terminal 22: Disabled regulation of mains reference load
Terminal 23: Sprinkler mode.
When an [L-] signal is connected to this terminal, the genset starts without changing over to generator supply, and all alarms serve only as warning ones – except for overspeed (only applicable if an
electronic speed controller is in use). The generator switch stays on, it can, however, be parameterised to switch off in the events of generator short-circuit or overload.
Terminal 24: Start enable input.
Any starting attempt emitted manually or automatically will be interlocked as long as there is no [L-]
potential connected to this terminal. It is therefore possible to incorporate relevant pre-start conditions before a signal is given to the starter motor for cranking. If this function is not used, a wire
jumper from [L-] to terminal no. 24 must be connected.
This function does not meet the requirements of the German Standards DIN VDE 0107, as a running genset will not be shut down; this function only protects the engine before start-up.
Terminal 25: Remote start without Load Transfer.
When a command is issued to this terminal, the genset starts in the AUTO mode without the generator being switched on. Only if a command is also issued to terminal 18 (Remote start with Load
Transfer), the generator breaker will be switched on. To switch off the generator breaker again,
both signals (terminals 18 and 25) must be cut!
Terminal 26: External command :GENERATOR OFF
If a command is applied here, the generator CB is immediately switched off and remains off as long
as the signal is applied.
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
17 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 17 / 26
Terminal 27: Power Control in Peak Load Operation.
A signal on minus enables 30 % (parameterisable) of the peak load. In combination with terminal
28, 100 % is enabled. If terminals 27 and 28 are not wired, mains parallel operation is disabled.
Terminal 28: Power Control in Peak Load Operation.
A signal on minus enables 60 % (parameterisable) of the peak load. In combination with terminal
27, 100 % is enabled. If terminal 27 and 28 are not wired, Mains Parallel operation is disabled.
Terminal 29: Charging Dynamo, terminal D+.
Terminal D+ of the charging dynamo, if present, has to be connected here. An AC-dynamo receives the pre-excitation via this connection, and the [+] signal of the dynamo will cause the starter
motor to be switched off.
19.
Flags for Alarm Inputs and Relays
Genset
Genset is running during mains operation
Genset available
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Alarm 7
Alarm 8
Alarm 9
Alarm 10
Alarm 11, closed current
Alarm 12
Alarm 12 in, closed current
Alarm 13
Alarm 13 in, closed current
Alarm 14
Alarm 14 in, closed current
Alarm 13 or 14, closed current
Alarm 15
Alarm 16
Alarm 17
Alarm 18
Alarm 19
Alarm Battery undervoltage
Alarm Engine keeps runningl
Alarm cranking failure
Alarm Overspeed
Alarm Load controller failure
Alarm Reverse power
Alarm Synchronisation failure
Alarm Mains CB does not cut off
Alarm Generator does not cut off
Alarm Mains CB tripped
Alarm Generator CB tripped
Alarm Phase sequence, mains
Alarm Phase sequence, generator
Alarm 33
0D10
4140
3304
2101
2102
2104
2108
2110
2120
2140
2180
2201
2202
5A01
2208
5A02
2210
5A04
2220
5A08
5580
2240
2280
2301
2302
2304
2308
2310
2320
2340
2380
2401
2402
2404
2408
2410
2420
2440
2480
2501
Alarm 34
Alarm 35
Alarm 36
Alarm Generator overcurrent I
Alarm Generator overcurrent II
Alarm Generator unbalanced currents
Alarm Generator thermal overload
Alarm Mains undervoltage
Alarm Mains overvoltage
Alarm Mains underfrequency
Alarm Mains overfrequency
Alarm Generator underfrequency
Alarm Generator overvoltage
Alarm Generator underfrequency
Alarm Generator overfrequency
Cranking speed exceeded
Starter motor on
Battery undervoltage, closed current
Command 1 from remote control panel
Command 2 from remote control panel
Command 3 from remote control panel
Command 4 from remote control panel
Command 5 from remote control panel
Command 6 from remote control panel
Command 7 from remote control panel
Command 8 from remote control panel
Operation mode OFF is selected
2502
2504
2508
2510
2520
2540
2580
2601
2602
2604
2608
2610
2620
2640
2680
3C01
3E02
4001
6810
6808
6804
6802
6801
6880
6840
6820
0010
Operation mode MANUAL is selected
0020
Operation mode AUTO is selected
0040
Operation mode TEST is selected
Operation solenoid on
Operation solenoid
CANopen failure
CAN J1939 failure
Speed governor lower
Speed governor higher
Supply for printer on
EMS on
Unload the genset
Remote control
0080
0F80
4E40
7120
4F08
4B08
4B10
5C20
5E10
4B20
4C80
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
18 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 18 / 26
Speed of frequency controller lower
Speed of frequency controller higher
Sensor failure channel 1
Sensor failure channel 2
Sensor failure channel 3
Sensor failure channel 4
Open gas valve
Generator overload
Relay generator on
Generator On pulses
Timers time is up, reverse power generator
Generator voltage within its limits
Pre-gloving on
Limit A exceeded channel 1
Limit B exceeded channel 1
Limit A exceeded channel 2
Limit B exceeded channel 2
Limit A exceeded channel 3
Limit B exceeded channel 3
Limit A exceeded channel 4
Limit B exceeded channel 4
Auxiliary drive I
Auxiliary drive II
Horn on
Isolated operation
KRV on
Coupling breaker off
Speed of load controller lower
Speed of load controller higher
Rated speed exceeded
Relay Mains off
Mains on pulse
Mains operation is on
Mains parallel operation
Mains voltage within its limits
ProMerk, output of NOT-1
ProMerk, output of NOT-2
ProMerk, output of NOT-3
3702
3704
4610
4620
4640
4680
3E08
25F0
3F02
3F08
1480
0E80
3E01
4901
4902
4904
4908
4910
4920
4940
4980
5320
5340
0e02
3708
4C10
4C20
4604
4608
3C04
3F01
3F04
3710
3720
0E04
6201
6202
6204
ProMerk, output of NOT-4
6208
ProMerk, output of NOT-5
ProMerk, output of NOT-6
ProMerk, output of NOT-7
ProMerk, output of NOT-8
ProMerk, output of OR-1
ProMerk, output of OR-2
ProMerk, output of OR-3
ProMerk, output of OR-4
ProMerk, output of OR-5
ProMerk, output of OR-6
ProMerk, output of OR-7
ProMerk, output of OR-8
ProMerk, output of AND-1
ProMerk, output of AND-2
ProMerk, output of AND-3
6210
6220
6240
6280
6701
6702
6704
6708
6710
6720
6740
6780
6101
6102
6104
ProMerk, output of AND-4
ProMerk, output of AND-5
ProMerk, output of AND-6
ProMerk, output of AND-7
ProMerk, output of AND-8
ProMerk, output of Timer 1
ProMerk, output of Timer 2
ProMerk, output of Timer 3
ProMerk, output of Timer 4
ProMerk, output of Timer 5
ProMerk, output of Timer 6
ProMerk, output of Timer 7
ProMerk, output of Timer 8
RZ-071-D, Terminal 1
RZ-071-D, Terminal 2
RZ-071-D, Terminal 3
RZ-071-D, Terminal 4
RZ-071-D, Terminal 5
RZ-071-D, Terminal 6
RZ-071-D, Terminal 7
RZ-071-D, Terminal 8
RZ-071-D, Terminal 9
RZ-071-D, Terminal 10
RZ-071-D, Terminal 11
RZ-071-D, Terminal 12
RZ-071-D, Terminal 13
RZ-071-D, Terminal 14
RZ-071-D, Terminal 15
RZ-071-D, Terminal 16
RZ-071-D, Terminal 17
RZ-071-D, Terminal 18
RZ-071-D, Terminal 19
RZ-071-D, Terminal 20
RZ-071-D, Terminal 21
RZ-071-D, Terminal 22
RZ-071-D, Terminal 23
RZ-071-D, Terminal 24
RZ-071-D, Terminal 25
RZ-071-D, Terminal 26
RZ-071-D, Terminal 27
RZ-071-D, Terminal 28
RZ-071-D, Terminal 29
Common of all warning alarms, operating
current
Common of all shut-down alarms, operating
current
Common of all alarms, operating current
Common of all warning alarms, closed
current
Common of all shut-down alarms, closed
current
Common of all alarms, closed current
Check synchroniser on
Voltage of voltage controller lower
Voltage of voltage controller higher
6108
6110
6120
6140
6180
6301
6302
6304
6308
6310
6320
6330
6340
0410
0408
0404
0402
0401
0580
0540
0520
0510
0508
0504
0502
0501
0680
0640
0620
0610
0608
0604
0602
0601
0780
0740
0720
0710
0708
0704
0702
0701
3804
3810
3840
3808
3820
3880
4C08
3740
3780
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
19 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 19 / 26
Voltage of cos phi / PF controller lower
Voltage of cos phi / PF controller higher
Voltage controller lower
Voltage controller
Sprinkler operation is on
Start pre-conditions on
Stopping solenoid
Synchronisation generator is on
Synchronisation mains is on
Button Alarm Off
Button LED Test
TeleAlarm Command 1
TeleAlarm Command 2
TeleAlarm Command 3
TeleAlarm Command 4
TeleAlarm Command 5
TeleAlarm Command 6
TeleAlarm Command 7
TeleAlarm Command 8
Overspeed limit exceeded
Alarm monitoring is on
VDE-AR-N 4105 Main protection is on
ZLT-Command 1
ZLT-Command 2
ZLT-Command 3
ZLT-Command 4
ZLT-Command 5
ZLT-Command 6
ZLT-Command 7
ZLT-Command 8
ZLT-Command 9
ZLT-Command 10
ZLT-Command 11
ZLT-Command 12
ZLT-Command 13
ZLT-Command 14
ZLT-Command 15
ZLT-Command 16
Ignition speed exceeded
Ignition on
Optional module CANOpen, Input 1,
Optional module CANOpen, Input 2,
Optional module CANOpen, Input 3,
Optional module CANOpen, Input 4,
Optional module CANOpen, Input 5
Optional module CANOpen, Input 6
Optional module CANOpen, Input 7
Optional module CANOpen, Input 8
Optional module CANOpen, Input 9
Optional module CANOpen, Input 10
Optional module CANOpen, Input 11
Optional module CANOpen, Input 12
Optional module CANOpen, Input 13
Optional module CANOpen, Input 14
4740
4720
4D02
4D04
2020
3410
3E04
3C40
3C80
0240
0220
6D01
6D02
6D04
6D08
6D10
6D20
6D40
6D80
3C08
0D20
7001
5001
5002
5004
5008
5010
5020
5040
5080
5101
5102
5104
5108
5110
5120
5140
5180
3C02
3E10
0801
0802
0804
0808
0810
0820
0840
0880
0901
0902
0904
0908
0910
0920
Optional module CANOpen, Input 15
Optional module CANOpen, Input 16
Output idle
0940
0980
0000
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
20.
Technical Data
20.1.
KEA Controller







Device for frontal installation, dimensions: (,, depth) 260 x 170 x 100 mm
Weight approx. 2.2 kg, can be installed wherever required
Protection class (installed) IP 44
Ambient temperature: Storage -20°C ... +70°C, Operation 0°C … +55°C
Supply voltage convertible 9-12-15V or 14-24-35V DC
3 customer-defined relays, 35 V DC, 1 A. (e.g. for acoustic signallers)
Standards/regulations VDE 100, Part 710
20.2.
Analogue Inputs and Outputs
 3-phase mains and generator voltage monitor, set in increments of 1 Volt;
if the rotary field is incorrect, the display shows <U.
 UNom 230/400 volts. They can be set from 50 to 300 volts. Accuracy class 1
 Mains and generator frequency monitor 50 or 60 Hz; they can be set to any value between 40 and 70 Hz;
accuracy class 1
 3-phase generator current monitor; accuracy class 1
 INom 5 Amp: measuring range 0.1 – 15 A; it can be set in increments of 20 mA
 Battery voltage monitor
 Input for pick-up
 Option: four analogue inputs, which can be fitted with interface cards for
- PT 100 / PT1000
- Current loops
- 0 - 10 V DC
- Thermocouple NiCr-Ni
- Temperature and pressure: VDO sensor
 Option: two analogue outputs 0 – 20 mA or 0 – 10 V
20.3.




Relay Unit RZ 071-D
Device for attachment on a mounting rail, dimensions: (,, depth) 300 x 100 x 90 mm
Weight approx. 0.7 kg, can be installed wherever required
Protection class IP 00
Fitted with:
- Input for charging dynamo D+ with pre-excitation for AC alternators
- 14 ports for alarm contacts
- 14 general control inputs
- 12 relays, of which 8 can be configured;
contact load: 2 relays max. 35 V, 20 A DC; 10 relays 250 V AC, 6 A.
20.4.
Relay unit RZ 071-E (optional)
 Device for attachment on a mounting rail, dimensions: (,, depth) 210 x 100 x 50 mm,
 Weight approx. 0.5 kg, can be installed wherever required, protection class IP 00,
 Fitted with 15 relays, of which 14 can be configured, contact load max. 250 V AC, 6 A
20.5.
Serial interfaces
 Optical fibre or USB interface – with automatic switching – for parameterisation.
 CAN bus interface to a Digital Control System (DCS)
 CAN bus interface to Engine Control Unit (ECU); the protocol must be known and implemented
20.6.
Connection to other Systems (optional)
Device for attachment on a mounting rail: KNG (Kuhse Network Gateway) to connect to other systems via
Profibus DP or Modbus RTU
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
21 / 26
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
21.
Diagrams
21.1.
Response Diagram for Thermal Overload
21 / 26
______________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice
22 / 26
21.2.
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
22 / 26
Connection Diagram, RZ-071-D
______________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice
23 / 26
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
21.3.
Connection Diagram, RZ-071-E (optional)
21.4.
Connection Diagram, KEA 201 SPL
23 / 26
______________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice
24 / 26
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
21.5.
Connections, analogue Inputs
21.6.
Door Cross Section of KEA, Frontview
24 / 26
______________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice
25 / 26
21.7.
Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc
25 / 26
Controller PCB with Jumper for Sealing Setpoints
______________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice
26 / 26 Service Manual for KEA 201 SPL – File: SA_KEA 201 SPL_EN_Ver 2016-07-01.doc 26 / 26
22.
Drilling Template, Scale 1:1 – print without scaling!
_________________________________________________________________________________
Alfred Kuhse GmbH
An der Kleinbahn 39, D-21423
Winsen (lu(
Phone: +49 4171-798-0
Fax +49 4171-798-117
kuhse@kuhse.de
www.kuhse.de
Changes without further notice reserved.
Download