Special Test on HT Cables For MV cable testing following special tests are done : 1. Partial Discharge Test 2. Tan delta Test 3. Lightening Impulse Test 4. 4-hour test Purpose of PD: 1. This test is performed to assess electrical insulation health. 1. To find the discharge before it leads to flashover and catastrophic failure 2. PD is best described as a failure of part of an insulation system to withstand the electrical field applied to it. Technical parameter of PD Rated Input 100 KVA, 50 Hz Rated output for 33KV 2000KVA, 120KV, 16.7A Rated output for 33KV 2000 KVA, 50 KV, 40A Lightning Impulse Test System Technical parameter of PD Purpose of Lightening Impulse: 1. to assess the ability of Electrical Insulation Systems to withstand such highvoltage impulses. Nominal Voltage Rated Impulse capacity Rated energy Charging voltage range Working Voltage Series 400 KV 0.111 micro Farad 20 KJ 0-100 KV 20- 100 KV 4 Thermal Cycle Test System Purpose of Thermal cycle Test: 1. Thermal cycling tests determine the ability of a cable under test (or a part of it) to resist extremely high temperatures and extremely low temperatures. Technical parameters of Thermal Cycle Test Input power 380V, 200 KVA, 50Hz Temperature sample loop current System working time 35-120 1000-6000 A Not less than 2 hours