Uploaded by Ritik Panwar

EEN-112 Unit-6

advertisement
INDIAN INSTITUTE OF TECHNOLOGY ROORKEE
EEN-112
Electrical Science
Unit-VI: Single Phase Transformer
Dr. Dheeraj K Khatod
Department of Electrical Engineering
Contents
• Concept of magnetic circuit
• Transformer
–
–
–
–
–
Basic constructional features
Operating principle
Equivalent circuit and phasor diagram
Tests: Open circuit and short circuit tests
Losses: Iron losses (Eddy current and Hysteresis) and Cu
losses
– Efficiency and voltage regulation
2
Concept of Magnetic Circuit
3
Magnetic Circuit
• The path of a magnetic flux is known as magnetic
circuit.
• The flow of magnetic flux in a magnetic circuit is
almost analogues to the flow of electric current in an
electric circuit.
• To carry electric current in an electric circuit, usually
aluminum or copper wires are used because the
resistance of these materials is comparatively much
lower than other materials. Similarly, to carry
magnetic flux, iron or soft steel circuits are used as
“opposition” of these materials to flux is low in
comparison with other materials.
4
Magnetic Circuit (cont.)
• Consider a toroidal ring of
ferromagnetic material of
mean radius, 𝑅𝑅 and circular
cross-section of diameter, 𝑑𝑑
as shown in Fig.
• The ring termed as core is
excited by a coil wound
round it with 𝑁𝑁 turns
carrying a current, 𝑖𝑖.
• By virtue of symmetry, flux
established in the magnetic
core is circular in shape
having the length of the
mean flux path, 𝑙𝑙.
• The cross sectional area of
the magnetic core is 𝐴𝐴.
5
Magnetic Circuit Definitions
• Magnetic Flux
– Represents the magnetic field
– Magnetic flux lines do not have origins or terminating points
but exist in continuous loops
– Symbol: πœ™πœ™
– Unit: Weber, (Wb)
• Magnetomotive Force (MMF)
–
–
–
–
“Driving force” that causes a magnetic field
Symbol: β„±
Unit: Ampere-Turns, (AT)
Definition: β„± = 𝑁𝑁 × πΌπΌ
6
Magnetic Circuit Definitions
(cont.)
• Magnetic Field Intensity or Magnetizing Force
–
–
–
–
MMF gradient, or MMF per unit length
Symbol: β„‹
Unit: Ampere-Turns per meter (AT/m)
Definition:
β„‹ = ℱ�𝑙𝑙 = 𝑁𝑁 × πΌπΌοΏ½π‘™π‘™
• Magnetic Field Density
–
–
–
–
Concentration of the lines of force in a magnetic circuit
Symbol: 𝐡𝐡
Unit: Weber per square meter (Wb/m2) or T (Tesla)
Definition:
πœ™πœ™
𝐡𝐡 = �𝐴𝐴
7
Magnetic Circuit Definitions
(cont.)
• Permeability
–
–
–
–
Relates flux density and field intensity
Symbol: πœ‡πœ‡
Unit: Weber per Ampere-Turns-meter (Wb/AT-m)
Definition: πœ‡πœ‡ = 𝐡𝐡�
β„‹
• Permeability of free space (air)
– Symbol: πœ‡πœ‡0 = 4πœ‹πœ‹ × 10−7 Wb/AT-m
• Relative Permeability
– Compares permeability of material with the permeability of
free space (air)
– Symbol: πœ‡πœ‡π‘Ÿπ‘Ÿ
– Dimensionless
– Definition: πœ‡πœ‡π‘Ÿπ‘Ÿ = πœ‡πœ‡οΏ½πœ‡πœ‡
0
8
Magnetic Circuit Definitions
(cont.)
• Reluctance
– Measure of “opposition” that the magnetic circuit offers to
the flux
– Analogous to resistance in an electrical circuit
– Symbol: β„›
– Unit: Ampere-Turns per Weber (AT/Wb)
– Definition:
β„› = β„±οΏ½πœ™πœ™ = 𝑁𝑁 × πΌπΌοΏ½πœ™πœ™ = π‘™π‘™οΏ½πœ‡πœ‡π΄π΄
• Permeance
– Reciprocal of reluctance
– Symbol: ℘
– Unit: Weber per Ampere-Turns (Wb/ AT)
– Definition:
℘ = 1οΏ½β„›
9
Magnetic Circuit Definitions
(cont.)
• Leakage Flux
– Flux that leaks through the core
– Flux that lies in air
• Fringing
– The flux passing from the core to the air-gap cannot remain
confined to the air-gap but would somewhat spread out.
This effect is called fringing.
– Average flux density in the air-gap is slightly less than the
flux density in the core
10
DC Circuit Analog of Magnetic
System
• The concept of reluctance
lumps the magnetic system
into a circuit analogically
expressed as a dc electric
circuit as shown in Fig.
• In this analog
– β„± ~ dc voltage (potential)
– β„› ~ resistance
– πœ™πœ™ ~ current
11
Magnetization Curve and
Hysteresis Loop
12
Magnetic Hysteresis Loss
• Hysteresis produces heat due to re-alignment of
magnetic domains
• Hysteresis loss varies directly with
– Frequency of the flux density
– 𝑛𝑛𝑑𝑑𝑑 power of the flux density
𝑛𝑛
• Hysteresis loss, π‘ƒπ‘ƒβ„Ž = π‘˜π‘˜β„Ž οΏ½ 𝑓𝑓 οΏ½ π΅π΅π‘šπ‘šπ‘šπ‘šπ‘šπ‘š
οΏ½ 𝑉𝑉
where
π‘˜π‘˜β„Ž is the characteristic constant of core material
𝑓𝑓 is the frequency of the flux (Hz)
π΅π΅π‘šπ‘šπ‘šπ‘šπ‘šπ‘š is the maximum value of the flux density
𝑛𝑛 is Steinmetz exponent; ranges between 1.5–2.0; typical
value is 1.6
𝑉𝑉 is the volume of core material.
13
Eddy-Current Loss
• The voltage induced in core (made of conducting
material) by alternating flux produces circulating
currents in it. These are called eddy-currents. The
flow of eddy current also causes loss (𝐼𝐼 2 𝑅𝑅) known as
eddy-current loss.
2
• Eddy-current loss, 𝑃𝑃𝑒𝑒 = π‘˜π‘˜π‘’π‘’ οΏ½ 𝑓𝑓 2 οΏ½ π΅π΅π‘šπ‘šπ‘šπ‘šπ‘šπ‘š
οΏ½ 𝑉𝑉
where
π‘˜π‘˜π‘’π‘’ is the characteristic constant of core material
𝑓𝑓 is the frequency of the flux (Hz)
π΅π΅π‘šπ‘šπ‘šπ‘šπ‘šπ‘š is the maximum value of the flux density
𝑉𝑉 is the volume of core material.
14
Core Loss
• Core loss, also referred to as iron loss, consists of
hysteresis loss and eddy-current loss.
• Ways to reduce hysteresis loss
– By using core material (Cold Rolled Grain Oriented (CRGO)
Silicon Steel) having less area of hysteresis loop
• Ways to reduce eddy-current loss
– By using high resistive core material by adding Si
– By using a laminated core
15
Electromagnetic Induction
• Flux Linkage
– If flux πœ™πœ™ passes through all the N turns of a coil, the flux is
said to be linked with the coil
– The flux linkage of the coil, πœ†πœ† = 𝑁𝑁 × πœ™πœ™ Weber-Turns (Wb-T)
16
Electromagnetic Induction (cont.)
• Faraday’s first law states that whenever magnetic flux
linked with a close coil changes, an induced emf is set
up in the coil and the induced emf lasts as long as the
change in magnetic flux continues.
• Faraday’s second law states that the magnitude of the
induced emf is directly proportional to the time rate
of change of the magnetic flux linked with a close coil.
• Lenz’s law states that the induced emf would tend to
cause a current flow in the coil which would oppose
the change in flux (the original cause of emf
induction).
17
Electromagnetic Induction (cont.)
π‘‘π‘‘πœ†πœ†
π‘‘π‘‘πœ™πœ™
• Induced emf, 𝑒𝑒 = − 𝑑𝑑𝑑𝑑 = −𝑁𝑁 𝑑𝑑𝑑𝑑
• A current flows through the loop when a magnet is
moved near it, without any batteries!
Moving the magnet inwards the coil
No movement of the magnet
Moving the magnet outwards the coil
18
Inductance
• Self-Inductance
– The property of a current carrying coil by which it opposes
the change in flux linkage through it due to the production of
self induced emf is called self-inductance.
– The role of self-inductance in an electrical circuit is the same
as that of the inertia in mechanical motion. Thus the selfinductance of a coil is a measure of its ability to oppose the
change in current through it and hence is also called
electrical inertia.
– Symbol, 𝐿𝐿
– Unit, Henry (H) π‘‘π‘‘πœ†πœ†
π‘‘π‘‘πœ™πœ™
π‘‘π‘‘πœ™πœ™ 𝑑𝑑𝑑𝑑
𝑑𝑑𝑑𝑑
Induced emf, 𝑒𝑒 = − 𝑑𝑑𝑑𝑑 = −𝑁𝑁 𝑑𝑑𝑑𝑑 = −𝑁𝑁 𝑑𝑑𝑑𝑑 οΏ½ 𝑑𝑑𝑑𝑑 = −𝐿𝐿 𝑑𝑑𝑑𝑑
Self-inductance, 𝐿𝐿 = 𝑁𝑁 π‘‘π‘‘πœ™πœ™
𝑑𝑑𝑑𝑑
19
Inductance (cont.)
• Self-Inductance
– For a linear B-H curve (material operated in the region of
constant permeability or when the magnetic circuit has a
dominant air-gap),
Self-inductance, 𝐿𝐿 = 𝑁𝑁
πœ™πœ™
𝑖𝑖
=
πœ†πœ†
𝑖𝑖
Flux linkage of the coil, πœ†πœ† = 𝐿𝐿 × π‘–π‘–
As already derived, Reluctance, β„› = β„±οΏ½πœ™πœ™ = 𝑁𝑁×π‘–π‘–οΏ½πœ™πœ™ = π‘™π‘™οΏ½πœ‡πœ‡π΄π΄
Again self-inductance, 𝐿𝐿
πœ™πœ™
= 𝑁𝑁
𝑖𝑖
=
𝑁𝑁2
β„›
= 𝑁𝑁 2 πœ‡πœ‡
𝐴𝐴
𝑙𝑙
– Self-inductance of a coil is independent of excitation current
and depends upon the core geometry, permeability of the
core’s magnetic material and number of coil turns.
20
Inductance (cont.)
• Mutual-Inductance
– If two coils are wound on a common core or placed close to
each other, a part of the flux produced by one coil also links
the other coil. Whenever a change in current occurs in a coil,
an induced emf is set up in the other coil. This process is
called mutual induction.
– If a current 𝐼𝐼1 flows in Coil 1 (having 𝑁𝑁1 turns), the magnetic
flux linked with Coil 2 (having 𝑁𝑁2 turns) is
πœ†πœ†2 = 𝑁𝑁2 × πœ™πœ™21 = 𝐿𝐿21 × πΌπΌ1
where,
πœ™πœ™21 is the flux of Coil 1 linking with Coil 2
𝐿𝐿21 is the mutual inductance of Coil 2 with
respect to Coil 1.
πœ†πœ†2
𝐿𝐿21 =
𝐼𝐼1
21
Inductance (cont.)
• Mutual-Inductance
– When both coils are carrying current, the total flux linkages
are given by
πœ†πœ†1 = 𝐿𝐿11 × πΌπΌ1 ± 𝐿𝐿12 × πΌπΌ2
πœ†πœ†2 = ±πΏπΏ21 × πΌπΌ1 + 𝐿𝐿22 × πΌπΌ2
where, 𝐿𝐿11 and 𝐿𝐿22 are self-inductance of the coils and 𝐿𝐿12 and
𝐿𝐿21 are mutual inductance of the coils (equal in a bilateral
circuit)
– The induced emf in each coil is given by
𝑑𝑑𝐼𝐼1
𝑑𝑑𝐼𝐼2
𝑒𝑒1 = 𝐿𝐿11 ×
± 𝐿𝐿12 ×
𝑑𝑑𝑑𝑑
𝑑𝑑𝑑𝑑
𝑑𝑑𝐼𝐼1
𝑑𝑑𝐼𝐼2
𝑒𝑒2 = ±πΏπΏ21 ×
+ 𝐿𝐿22 ×
𝑑𝑑𝑑𝑑
𝑑𝑑𝑑𝑑
22
Inductance (cont.)
• Mutual-Inductance
– The voltage induced by mutual flux may be negative or positive,
therefore, the dot convention is used to indicate the polarity of
voltage induced by mutual flux.
– Dot convention
• A dot is placed in the circuit at one end of each of the two magnetically
coupled coils to indicate the direction of the magnetic flux if current enters
that dotted terminal of the coil.
• If a current enters the dotted terminal of one coil, the reference polarity of
the mutual voltage in the second coil is positive at the dotted terminal of the
second coil.
• Alternatively, if a current leaves the dotted terminal of one coil, the reference
polarity of the mutual voltage in the second coil is negative at the dotted
terminal of the second coil.
23
Inductance (cont.)
24
Numerical Problem on Magnetic
Circuit
• A rectangular iron core has an air-gap. Find the
exciting current needed to establish a flux density of
1.2 T in the air-gap. Given 𝑁𝑁 = 400 turns and πœ‡πœ‡π‘Ÿπ‘Ÿ (iron)
= 4000.
25
Numerical Problem on Magnetic
Circuit (cont.)
• Solution:
– Given
Flux density, 𝐡𝐡 = 1.2 T
No. of turns, 𝑁𝑁 = 400
Relative permeability of iron, πœ‡πœ‡π‘Ÿπ‘Ÿ = 4000
Core length, 𝑙𝑙𝑐𝑐 = 2 [(20 – 4) + (16 – 4)] – 0.2 = 55.8 cm
Cross-sectional area of core, 𝐴𝐴𝑐𝑐 = 16 cm2
Core reluctance, 𝑅𝑅𝑐𝑐 =
55.8 × 10–2
4πœ‹πœ‹×10−7 ×4000×16×10–4
= 0.694 × 105 AT/Wb
Air-gap length, 𝑙𝑙𝑔𝑔 = 0.2 cm
Cross-sectional area of air-gap, 𝐴𝐴𝑔𝑔 = 𝐴𝐴𝑐𝑐 = 16 cm2
Air-gap reluctance, 𝑅𝑅𝑔𝑔 =
0.2 × 10–2
4πœ‹πœ‹×10−7 ×16×10–4
= 9.95 × 105 AT/Wb
Total reluctance, 𝑅𝑅𝑇𝑇 = 𝑅𝑅𝑐𝑐 + 𝑅𝑅𝑔𝑔 = 10.64 × 105 AT/Wb
Flux in the magnetic circuit, πœ™πœ™ = 𝐡𝐡 × π΄π΄π‘π‘ = 1.2 × 16 × 10–4 = 1.92 mWb
Now, πœ™πœ™ × π‘…π‘…π‘‡π‘‡ = β„± = 𝑁𝑁 × π‘–π‘– ⇒ 𝑖𝑖 =
πœ™πœ™ × π‘…π‘…π‘‡π‘‡
𝑁𝑁
=
1.92× 10–3 ×10.64×105
4000
= 5.11 A
26
Question on Magnetic Circuit
• How does the inductor used in Lab Class of EEN-112
(study of RLC circuit) behave as a variable inductor?
27
Single Phase Transformer
28
Definition and Applications
• A static electromagnetic devices (or electrical machine), which
transfers electrical power from one circuit to another circuit
using the principle of mutual induction without change in the
frequency.
• Transformer are used for a wide range of purposes, such as
– Transmission and distribution of electricity for changing the voltage
levels
– Telecommunication circuits
– Instrumentation circuits
– Measurement of voltage, current, power, energy
– Control circuits
– DC supply such as chargers and adaptors
29
Application of Power Transformers
in Power System
30
Operating Principle
• The primary winding is
connected to the single–phase
ac supply, an ac current starts
flowing through it, which
produces an alternating flux in
the core.
• Most of this changing flux gets
linked with the secondary
winding through the core.
• The varying flux will induce
voltage into the secondary
winding according to the
faraday’s
laws
of
electromagnetic induction.
• Voltage level changes but
frequency remains same.
• There is no electrical contact
between the two winding, an
electrical
energy
gets
transferred from primary to
the secondary
31
Constructional Details
• Windings
– The primary and secondary windings are made of
copper/aluminum conductors.
• Core
– The transformer core is made of highly permeable iron so
that excitation current required to establish core flux is a
small percentage (2 - 4) of the primary current, the rest
being the useful component which corresponds to the load
current.
– High permeable core reduces the leakage flux.
– To minimize the eddy current loss, the core is constructed
with silicon steel laminations in form of rectangular strips
(0.35 mm thickness for 50 Hz) insulated from one another
by thin layers of varnish.
32
Constructional Details (cont.)
• Core
– Two types of geometrical core shapes and winding
arrangements are used practically
• Core Type
– Two limbs or legs with half-LV and half-HV placed on each limb
– Has a longer mean flux path but a shorter mean length of coil turn.
– LV coils are placed inside (adjoining the core) and HV coils are placed
outside.
• Shell type
– Three limbs with both windings placed on the central limb which forms a
shell around the windings.
– Half of the flux of the central limb is returned though each outer limb.
– LV and HV coil packets are sandwiched.
33
Constructional Details (cont.)
Core-type
Shell-type
34
Constructional Details (cont.)
35
Constructional Details (cont.)
• Some other parts such as suitable tank, conservator,
bushings, breather, explosion vent etc. are also used
along with the core and windings.
36
Ideal Transformer
• A transformer is said to be ideal, if it has the following
properties:
– The transformer core material has infinite permeability so
that it requires zero MMF to create flux in the core.
– The transformer core losses are negligible.
– Both coils are lossless i.e. ohmic power losses and resistance
voltage drops in the actual transformer are neglected
– The leakage flux is negligible, i.e. no reactive voltage drops in
windings
37
Voltages and EMFs in an Ideal
Transformer
• When a sinusoidal voltage is applied to the primary winding,
flux, πœ™πœ™ is established in the core linking both primary and
secondary windings
πœ™πœ™ = πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š sin πœ”πœ”πœ”πœ”
where, πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š is the maximum value of flux; πœ”πœ” = 2πœ‹πœ‹πœ‹πœ‹ is the angular
frequency of supply in rad/s; 𝑓𝑓 is the supply frequency; 𝑑𝑑 denotes the
instant of time; and 𝑁𝑁1 and 𝑁𝑁2 are the number of turns in primary and
secondary windings, respectively.
38
Voltages and EMFs in an Ideal
Transformer (cont.)
• Induced emf in primary winding balances the applied voltage as per KVL
𝑑𝑑𝑑𝑑
= πœ”πœ”πœ”πœ”1 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š = πœ”πœ”πœ”πœ”1 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š sin πœ”πœ”πœ”πœ” + 90°
𝑣𝑣1 = 𝑒𝑒1 = 𝑁𝑁1
𝑑𝑑𝑑𝑑
• Similarly, the induced emf in secondary winding becomes
𝑣𝑣2 = 𝑒𝑒2 = πœ”πœ”πœ”πœ”2 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š cos πœ”πœ”πœ”πœ” = πœ”πœ”πœ”πœ”2 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š sin πœ”πœ”πœ”πœ” + 90°
• In terms of rms values,
𝑉𝑉1 = 𝐸𝐸1 =
πœ”πœ”πœ”πœ”1 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š
= 2πœ‹πœ‹πœ‹πœ‹πœ‹πœ‹1 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š
2
𝑉𝑉2 = 𝐸𝐸2 = 2πœ‹πœ‹πœ‹πœ‹πœ‹πœ‹2 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š
• The core flux is dependent on the supply voltage and maximum flux is
proportional to rms value of supply voltage.
39
Transformation Ratio and Phasor
Diagram for an Ideal Transformer
• The transformation ratio of rms values of voltages is
𝑉𝑉�1 𝐸𝐸�1 𝑉𝑉1
𝐸𝐸1 𝑁𝑁1
=
=
=
=
= π‘Žπ‘Ž
𝐸𝐸2 𝑁𝑁2
𝑉𝑉�2 𝐸𝐸�2 𝑉𝑉2
where, π‘Žπ‘Ž is the turn ratio.
• Also, the voltage per turn for both the windings are same
𝑉𝑉1
𝐸𝐸1 𝑉𝑉2 𝐸𝐸2
=
=
=
𝑁𝑁1
𝑁𝑁1 𝑁𝑁2 𝑁𝑁2
• In an ideal transformer, the voltages are in direct ratio of turns with no
change in phase angle
40
Current in an Ideal Transformer
• The current drawn by the secondary load is
𝑖𝑖2 = 𝐼𝐼2 2 cos πœ”πœ”πœ”πœ” − πœƒπœƒ2
where, πœƒπœƒ2 = phase angle of load assumed lagging
• By Lenz’s law, this current causes MMF to oppose the core flux πœ™πœ™. In phasor
terms, secondary MMF is
𝐹𝐹�2 = 𝑁𝑁2 𝐼𝐼2Μ… where, 𝐼𝐼2Μ… = 𝐼𝐼2 ∠πœƒπœƒ2
• As the core flux cannot change being governed by primary applied voltage
and frequency, a current is drawn from the source to cause MMF, 𝐹𝐹�1 equal
and opposite to MMF, 𝐹𝐹�2
𝐹𝐹�1 = 𝐹𝐹�2 ⇒ 𝑁𝑁1 𝐼𝐼1Μ… = 𝑁𝑁2 𝐼𝐼2Μ…
41
Current in an Ideal Transformer
(cont.)
• The transformation ratio of rms values of currents is
𝐼𝐼1Μ…
𝐼𝐼1 𝑁𝑁2 1
= =
=
𝐼𝐼2 𝑁𝑁1 π‘Žπ‘Ž
𝐼𝐼2Μ…
• An ideal transformer transforms the current in the inverse ratio of turns
and the phase is preserved
42
Volt-Amperes in an Ideal
Transformer
• As derived
• Therefore,
𝑉𝑉�1 𝑁𝑁1
=
οΏ½
𝑉𝑉2 𝑁𝑁2
𝐼𝐼1Μ…
𝑁𝑁2
and
=
̅𝐼𝐼2 𝑁𝑁1
𝑉𝑉�1 οΏ½ 𝐼𝐼1∗Μ… = 𝑉𝑉�2 οΏ½ 𝐼𝐼2∗Μ… ⇒ 𝑃𝑃1 + 𝑗𝑗𝑄𝑄1 = 𝑃𝑃2 + 𝑗𝑗𝑗𝑗2
• Input VA equals output VA, that is, there is change in VA in the
ideal transformer.
• Input active and reactive power equal output active and
reactive power, that is, there is no loss in the ideal transformer.
43
Equivalent Circuit of an Ideal
Transformer
• Secondary voltage and current referred to the primary side
𝑁𝑁
𝑁𝑁
𝑉𝑉�2′ = 1 𝑉𝑉�2 = 𝑉𝑉�1 and 𝐼𝐼2′Μ… = 2 𝐼𝐼2Μ… = 𝐼𝐼1Μ…
𝑁𝑁2
𝑁𝑁1
𝑁𝑁1
𝑁𝑁2
• Primary voltage and current referred to the secondary side
𝑁𝑁
𝑁𝑁
𝑉𝑉�1′ = 2 𝑉𝑉�1 = 𝑉𝑉�2 and 𝐼𝐼1′Μ… = 1 𝐼𝐼1Μ… = 𝐼𝐼2Μ…
44
Impedance Transformation in an
Ideal Transformer
• An impedance 𝑍𝑍2Μ… connected across the secondary side of the
ideal transformer as seen from the primary side becomes
𝑁𝑁2 οΏ½
2
2
𝑁𝑁2 𝑉𝑉�1 𝑉𝑉�1
𝑁𝑁1
𝑉𝑉�2 𝑁𝑁1 𝑉𝑉1
𝑍𝑍2Μ… =
=
=
⇒ =
𝑍𝑍2Μ… = 𝑍𝑍2Μ… ′
Μ…
Μ…
𝑁𝑁1 Μ…
𝑁𝑁
𝑁𝑁2
𝐼𝐼2Μ…
𝐼𝐼
𝐼𝐼
1
1
1
𝐼𝐼1
𝑁𝑁2
• 𝑍𝑍2Μ… ′ is called ‘the secondary impedance referred to the primary
side”.
45
Accounting for Finite Permeability
and Core Loss
• In a real transformer, the core has finite permeability and to
establish flux in the core, the primary winding would draw a
current component called magnetizing current from the source
over and above the load current.
• Assuming the core to be linear, the magnetizing current is then
given by
π‘–π‘–π‘šπ‘š
β„›
β„›
β„›
=
πœ™πœ™ =
πœ™πœ™
sin πœ”πœ”πœ”πœ” = 2
𝑁𝑁1
𝑁𝑁1 π‘šπ‘šπ‘šπ‘šπ‘šπ‘š
πœ”πœ” 𝑁𝑁1
𝑉𝑉 sin πœ”πœ”πœ”πœ”
2 1
where, β„› is the core reluctance and πΌπΌπ‘šπ‘š is the rms value of magnetizing current.
• Recalling
πœ™πœ™ = πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š sin πœ”πœ”πœ”πœ”
𝑣𝑣1 = πœ”πœ”πœ”πœ”1 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š cos πœ”πœ”πœ”πœ” = πœ”πœ”πœ”πœ”1 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š sin πœ”πœ”πœ”πœ” + 90°
πœ”πœ”πœ”πœ”1 πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š
2𝑉𝑉1
⇒ πœ™πœ™π‘šπ‘šπ‘šπ‘šπ‘šπ‘š =
𝑉𝑉1 =
πœ”πœ”πœ”πœ”1
2
46
Accounting for Finite Permeability
and Core Loss (cont.)
• Magnetizing current is in phase with the core flux and
lags the induced emf by 90°. It also depends on the
supply voltage. Therefore, the effect of magnetizing
current is modelled by a magnetizing reactance π‘‹π‘‹π‘šπ‘š
across the supply.
• A real core will also have power losses (hysteresis and
eddy-current losses) because it carries alternating
flux. Since both hysteresis and eddy-current losses
depend on maximum flux density (maximum flux per
unit area) and maximum flux is proportional to rms
value of supply voltage, the core losses can be
modelled as a resistance 𝑅𝑅𝑖𝑖 across the supply.
47
Accounting for Finite Permeability
and Core Loss (cont.)
• The rms values of net exciting current drawn by the primary to create core
flux is
Μ… + 𝐼𝐼𝑖𝑖̅
𝐼𝐼0Μ… = πΌπΌπ‘šπ‘š
Μ… =
where, magnetizing current, πΌπΌπ‘šπ‘š
οΏ½1
𝑉𝑉
π‘—π‘—π‘—π‘—π‘šπ‘š
οΏ½
𝑉𝑉
= and core (iron) loss current, 𝐼𝐼𝑖𝑖̅ = 1
𝑅𝑅𝑖𝑖
• The magnetizing current in a transformer is in the range 2–5% of the rated
current.
• On no-load (𝐼𝐼2Μ… = 0), the transformer primary would draw only the exciting
current from the source. Therefore, the exciting current is also termed as
no-load current (hence, the symbol 𝐼𝐼0Μ… ).
1
𝑅𝑅𝑖𝑖
1
Susceptance, π΅π΅π‘šπ‘š =
π‘‹π‘‹π‘šπ‘š
Conductance, 𝐺𝐺𝑖𝑖 =
48
Accounting for Winding Resistance
and Leakage Flux
• Both primary and secondary windings of a transformer have
resistances.
• Apart from this the two windings have leakage flux (flux
linking only one winding). These leakage fluxes do not
contribute in the process of energy transfer, but these cause the
primary and secondary windings to possess leakage
inductances and, therefore, leakage reactances at steady
sinusoidal operation.
• The winding resistances and leakage reactances can be lumped
in series with the windings along with the core in a circuit
model. Let windings resistances be π‘Ÿπ‘Ÿ1 , π‘Ÿπ‘Ÿ2 and winding
reactances (inductive) be π‘₯π‘₯1 and π‘₯π‘₯2 .
49
Equivalent Circuit of a Real
Transformer
𝐼𝐼2′Μ…
𝑁𝑁2
=
𝐼𝐼2Μ…
𝑁𝑁1
𝐼𝐼1Μ… = 𝐼𝐼0Μ… + 𝐼𝐼2′Μ…
𝐸𝐸�1 𝑁𝑁1
=
𝐸𝐸�2 𝑁𝑁2
𝑉𝑉�1 = 𝐸𝐸�1 + 𝐼𝐼2′Μ… × (π‘Ÿπ‘Ÿ1 + 𝑗𝑗π‘₯π‘₯1 )
𝑉𝑉�2 = 𝐸𝐸�2 − 𝐼𝐼2Μ… × (π‘Ÿπ‘Ÿ2 + 𝑗𝑗π‘₯π‘₯2 )
50
Equivalent Circuit of a Real
Transformer (cont.)
• By the technique of impedance transformation, the resistance and leakage
reactance of one side can be transferred to other side of the transformer.
• Then equivalent series resistance and reactance of the transformer referred
to the primary side are
Equivalent resistance, 𝑅𝑅 = π‘Ÿπ‘Ÿ1 +
π‘Ÿπ‘Ÿ2′
= π‘Ÿπ‘Ÿ1 +
Equivalent resistance, 𝑋𝑋 = π‘₯π‘₯1 + π‘₯π‘₯2′ = π‘₯π‘₯1 +
𝑁𝑁1 2
π‘Ÿπ‘Ÿ2
𝑁𝑁2
𝑁𝑁 2
1
𝑁𝑁2
π‘₯π‘₯2
⇒
51
Equivalent Circuit of a Real
Transformer (cont.)
𝑁𝑁1
𝑉𝑉�1 = 𝑉𝑉�2′ + 𝐼𝐼2′Μ… × π‘…π‘… + 𝑗𝑗𝑗𝑗 =
𝑉𝑉�2 + 𝐼𝐼2′Μ… ×
𝑁𝑁2
=
=
=
=
𝑁𝑁1
𝑉𝑉�
𝑁𝑁2 2
+
𝐼𝐼2′Μ…
× π‘Ÿπ‘Ÿ1 + 𝑗𝑗π‘₯π‘₯1 +
𝐼𝐼2′Μ…
×
𝑁𝑁1
π‘Ÿπ‘Ÿ1 +
𝑁𝑁2
𝑁𝑁1 2
𝑁𝑁2
π‘Ÿπ‘Ÿ2 + 𝑗𝑗π‘₯π‘₯2
𝑁𝑁1
𝑁𝑁2
𝑁𝑁1 2
′Μ…
οΏ½
Μ…
𝑉𝑉 + 𝐼𝐼2 × π‘Ÿπ‘Ÿ1 + 𝑗𝑗π‘₯π‘₯1 + 𝐼𝐼2 ×
π‘Ÿπ‘Ÿ2
𝑁𝑁2 2
𝑁𝑁1
𝑁𝑁2
𝑁𝑁1
𝑉𝑉�2 + 𝐼𝐼2Μ… × π‘Ÿπ‘Ÿ2 + 𝑗𝑗π‘₯π‘₯2 + 𝐼𝐼2′Μ… × π‘Ÿπ‘Ÿ1 + 𝑗𝑗π‘₯π‘₯1
𝑁𝑁2
𝐸𝐸�1 + 𝐼𝐼2′Μ… × π‘Ÿπ‘Ÿ1 + 𝑗𝑗π‘₯π‘₯1 = 𝑉𝑉�1
2
π‘Ÿπ‘Ÿ2
+ 𝑗𝑗π‘₯π‘₯2
=
𝑁𝑁1
𝐸𝐸�
𝑁𝑁2 2
𝑁𝑁1
+ 𝑗𝑗 π‘₯π‘₯1 +
𝑁𝑁2
2
π‘₯π‘₯2
+ 𝐼𝐼2′Μ… × π‘Ÿπ‘Ÿ1 + 𝑗𝑗π‘₯π‘₯1
52
Approximate Equivalent Circuit of
a Real Transformer
• The magnetizing shunt branches in the circuit model
do not affect voltage computation and may therefore
be ignored.
53
Tests on Transformer
• Transformer parameter determination necessitates
two following two tests
– Open-Circuit (OC) or No-load test
• Performed to determine core loss and parameters of the shunt
branch of the transformer circuit model.
– Short-Circuit (SC) test
• Performed to determine Cu-loss and series parameters of the
transformer circuit model.
54
Open-Circuit (OC) or No-Load Test
• The transformer is excited at rated voltage (and frequency) at
LV side while HV side is kept open-circuited.
• The magnetizing current in a transformer is in the range 2–5%
of the rated current.
55
Open-Circuit (OC) or No-Load Test
(cont.)
• Let the meter readings be
– Voltage (V) = 𝑉𝑉1
– Current (A) = 𝐼𝐼0
– Power (W) = 𝑃𝑃0 = core loss (𝑃𝑃𝑖𝑖 )
• The shunt branch parameters become
π‘Œπ‘Œ0 =
𝐺𝐺𝑖𝑖 =
𝐼𝐼0
𝑉𝑉1
π΅π΅π‘šπ‘š =
=
𝑃𝑃0
𝑉𝑉1
2
π‘Œπ‘Œ0
𝐺𝐺𝑖𝑖
2
2
+ π΅π΅π‘šπ‘š
− 𝐺𝐺𝑖𝑖
2
2
56
Short-Circuit Test
• The transformer is shorted on LV side and is excited from a
reduced voltage (rated frequency) source from HV side with
full-load current on HV side.
• The voltage needed to circulate full-load current is only of the
order of 5–8% of the rated voltage.
57
Short-Circuit Test (cont.)
• At the reduced primary voltage, the exciting 𝐼𝐼0 gets reduced to 0.1% to 0.4%
of the rated current. The magnetizing shunt branch of the circuit model can
therefore be conveniently dropped.
• Let the meter readings be
– Voltage (V) = 𝑉𝑉𝑆𝑆𝑆𝑆
– Current (A) = 𝐼𝐼𝑆𝑆𝑆𝑆
– Power (W) = 𝑃𝑃𝑆𝑆𝑆𝑆 = full load copper loss (𝑃𝑃𝑐𝑐 )
58
Short-Circuit Test (cont.)
• The winding parameters become
𝑉𝑉𝑆𝑆𝑆𝑆
𝑍𝑍 =
= 𝑅𝑅 2 + 𝑋𝑋
𝐼𝐼𝑆𝑆𝑆𝑆
𝑃𝑃𝑆𝑆𝑆𝑆
𝑅𝑅 =
𝐼𝐼𝑆𝑆𝑆𝑆 2
𝑋𝑋 = 𝑍𝑍 2 − 𝑅𝑅 2
2
59
Losses in Transformer
• The transformer has two major losses:
– Core (iron) loss, 𝑃𝑃𝑖𝑖 is a constant loss (for constant voltage
and frequency operation)
– Copper (𝐼𝐼 2 𝑅𝑅) loss of both windings, 𝑃𝑃𝑐𝑐 is a variable loss.
• Other transformer losses, which are insignificant for
efficiency computation, are
– Load (stray) loss which results from leakage fields inducing
eddy currents in tank walls and conductors
– Dielectric loss caused by leakage current in the insulating
materials
60
Efficiency of Transformer
• The efficiency of transformer, πœ‚πœ‚
Output power
Output power
=
πœ‚πœ‚ =
Input power
Output power + Losses
Output power, 𝑃𝑃2 = 𝑉𝑉2 οΏ½ 𝐼𝐼2 οΏ½ cos πœƒπœƒ2
where, πœƒπœƒ2 is the phase angle of load
𝑉𝑉2 οΏ½ 𝐼𝐼2 οΏ½ cos πœƒπœƒ2
𝑉𝑉2 οΏ½ 𝐼𝐼2 οΏ½ cos πœƒπœƒ2
=
πœ‚πœ‚ =
𝑉𝑉2 οΏ½ 𝐼𝐼2 οΏ½ cos πœƒπœƒ2 + 𝑃𝑃𝑖𝑖 + 𝑃𝑃𝑐𝑐 𝑉𝑉2 οΏ½ 𝐼𝐼2 οΏ½ cos πœƒπœƒ2 + 𝑃𝑃𝑖𝑖 + 𝐼𝐼2 2 𝑅𝑅2
where, 𝑅𝑅2 is the equivalent transformer resistance referred to secondary
side.
πœ‚πœ‚ =
𝑉𝑉2 οΏ½ cos πœƒπœƒ2
𝑃𝑃
𝑉𝑉2 οΏ½ cos πœƒπœƒ2 + 𝑖𝑖 + 𝐼𝐼2 οΏ½ 𝑅𝑅2
𝐼𝐼2
61
Efficiency of Transformer (cont.)
• For maximum efficiency of transformer, πœ‚πœ‚π‘šπ‘šπ‘šπ‘šπ‘šπ‘š
π‘‘π‘‘πœ‚πœ‚
= 0 ⇒ 𝑃𝑃𝑖𝑖 = 𝐼𝐼2 2 𝑅𝑅2
𝑑𝑑𝐼𝐼2
• Thus, for maximum efficiency of transformer, copper loss
should be equal to iron loss or variable loss should be equal to
constant loss.
• The load corresponding to maximum efficiency
Load current, 𝐼𝐼2 =
𝑃𝑃𝑖𝑖
𝑅𝑅2
= 𝐼𝐼2,𝐹𝐹𝐹𝐹
𝑃𝑃𝑖𝑖
𝑃𝑃𝑐𝑐,𝐹𝐹𝐹𝐹
Output power, 𝑃𝑃2 = 𝑉𝑉2 οΏ½ 𝐼𝐼2 οΏ½ cos πœƒπœƒ2
where, 𝐼𝐼2,𝐹𝐹𝐹𝐹 is the full load secondary current, and 𝑃𝑃𝑐𝑐,𝐹𝐹𝐹𝐹 is the
Cu loss at full load.
62
Voltage Regulation
• Various loads require a nearly constant voltage
supply. It is, therefore, essential that the output
voltage of a transformer stays within narrow limits as
load and its power factor vary.
• The leakage reactance is the major cause of voltage
drop in a transformer and must be kept as low as
possible by design and manufacturing techniques.
• Voltage regulation is an indication of change in output
voltage of transformer with change in load. It is
expressed in percentage of rated output voltage.
63
Voltage Regulation (cont.)
• The voltage regulation of a transformer at a given power factor
is defined as
VR (in %) =
𝑉𝑉2,0 − 𝑉𝑉2,𝐹𝐹𝐹𝐹
× 100%
𝑉𝑉2,𝐹𝐹𝐹𝐹
where, 𝑉𝑉2,0 is the no-load secondary voltage, and 𝑉𝑉2,𝐹𝐹𝐹𝐹 is the full load
secondary voltage.
• As in a transformer, 𝐼𝐼𝐼𝐼 and 𝐼𝐼𝐼𝐼 voltage drops are much smaller
in magnitude compared to 𝑉𝑉1 and 𝑉𝑉2 , the angle between 𝑉𝑉�1 and
𝑉𝑉�2 is only a few degrees such that 𝑉𝑉1 ≈ 𝑂𝑂𝑂𝑂
64
Voltage Regulation (cont.)
𝑉𝑉1 − 𝑉𝑉2 ≈ 𝐡𝐡𝐷𝐷 = I 𝑅𝑅 cos πœƒπœƒ + 𝑋𝑋 sin πœƒπœƒ , for lagging power factor
= I 𝑅𝑅 cos πœƒπœƒ − 𝑋𝑋 sin πœƒπœƒ , for leading power factor
• When the load is thrown off, 𝑉𝑉2,0 = 𝑉𝑉1 , therefore
𝑉𝑉2,0 − 𝑉𝑉2 = 𝑉𝑉1 − 𝑉𝑉2 = I 𝑅𝑅 cos πœƒπœƒ ± 𝑋𝑋 sin πœƒπœƒ
𝐼𝐼 𝑅𝑅 cos πœƒπœƒ ± 𝑋𝑋 sin πœƒπœƒ
VR (in %) =
× 100%
𝑉𝑉2
65
Voltage Regulation (cont.)
• For minimum voltage regulation in transformer
𝑅𝑅 cos πœƒπœƒ − 𝑋𝑋 sin πœƒπœƒ = 0 (leading power factor)
𝑅𝑅
tan πœƒπœƒ =
𝑋𝑋
𝑋𝑋
cos πœƒπœƒ =
𝑅𝑅 2 + 𝑋𝑋 2
• For maximum voltage regulation in transformer
𝑑𝑑𝑉𝑉𝑉𝑉
= 0 ⇒ −𝑅𝑅 sin πœƒπœƒ + 𝑋𝑋 cos πœƒπœƒ = 0 (lagging power factor)
𝑑𝑑𝑑𝑑
𝑋𝑋
tan πœƒπœƒ =
𝑅𝑅
𝑅𝑅
cos πœƒπœƒ =
𝑅𝑅 2 + 𝑋𝑋 2
66
Numerical Problems on
Transformer
1. An ideal transformer has a turn-ratio of 100/300. The LV
winding is connected to a source of 3.3 kV, 50 Hz. An
impedance of (100 + j 35) Ω is connected across the
secondary terminals. Calculate
a) Value of maximum core flux,
b) Primary and secondary currents,
c) Real and reactive powers supplied by the source to the
transformer primary, and
d) Value of impedance which connected directly across the
source would draw the same real and reactive power as in
(c).
67
Numerical Problems on
Transformer (cont.)
2. A 150 kVA, 2400/240 V single-phase transformer has the following
parameters of the equivalent circuit (supplied from 2400 V side)
π‘Ÿπ‘Ÿ1 = 0.2 Ω; π‘Ÿπ‘Ÿ2 = 2 × 10−3 Ω; π‘₯π‘₯1 = 0.6 Ω; π‘₯π‘₯2 = 6 × 10−3 Ω;
𝑅𝑅𝑖𝑖 = 10 × 103 Ω; and π‘‹π‘‹π‘šπ‘š = 1.6 × 103 Ω
a) Calculate the equivalent resistance and leakage reactance as
seen of the HV side.
b) Convert the resistance and reactance values referred to LV
side.
c) At rated current, calculate the impedance voltage drop on the
HV side. Also calculate the voltage drop as percentage of the
rated voltage.
d) With the secondary open (no load), what current will be drawn
from HV side (2400 V source). What is its pf?
68
Numerical Problems on
Transformer (cont.)
3. The resistances and leakage reactances of a 10 kVA, 50 Hz,
2300/230 V distribution transformer are (subscript 1 refers
to HV and 2 to LV winding)
π‘Ÿπ‘Ÿ1 = 3.96 Ω; π‘Ÿπ‘Ÿ2 = 3.96 × 10−2 Ω; π‘₯π‘₯1 = 15.8 Ω; and π‘₯π‘₯2 =
1.58 × 10−3 Ω;
a) The transformer delivers rated kVA at 0.8 pf lagging to a
load on the LV side. Find the HV-side voltage necessary to
maintain 230 V across load terminals. Also find the
percentage voltage regulation.
b) If a capacitor bank is connected across the load, what
should be the kVA capacity of the bank to reduce the
voltage regulation to zero? What should be the HV-side
voltage under these circumstances?
69
Numerical Problems on
Transformer (cont.)
4. The test data obtained on a 15 kVA, 3000/250 V, 50 Hz
distribution transformer are:
OC test (LV side) 250 V 0.62 A 105 W
SC test (HV side) 157 V 5.2 A 360 W
a) Determine the equivalent circuit parameters referred to the
HV side.
b) If the transformer is carrying full-load at 250 V, 0.8 pf
leading, calculate the transformer (i) voltage regulation, and
(ii) efficiency.
c) Find the pf of full-load for zero voltage regulation.
d) Find the percentage load at 0.8 pf for maximum efficiency of
transformer and its value.
70
Suggested Readings
• Kothari D.P. , Nagrath I.J., “Basic Electrical
Engineering”, Tata McGraw Hill Education (India)
Private Limited, 4th Edition, 2022.
• Vincent Del Toro, “Electrical Engineering
Fundamentals”, Prentice Hall of India, 2002.
• Alexander C.K., Sadiku M.N.O., “Fundamentals of
Electric Circuits”, McGraw Hill, 5th Edition, 2012.
• Chapman, Stephen, J., “Electric Machinery
Fundamentals”, McGraw Hill Book Company, 1985.
71
Thanks
72
Download