INTERVIEW QUESTIONS: - 1. Question 1 The power system industry is concerned with the generation, transmission, and distribution of electrical energy. 1 / 1 point TRUE FALSE Correct Power system deals with the business of generation, transmission, and distribution of electrical energy. 2. Question 2 Generation, transmission, and distribution of electrical power are all part of a traditional electric power system. 1 / 1 point TRUE FALSE Correct traditional electric power systems have three separate components: generation, transmission, and distribution. 3. Question 3 The purpose of an electric power system is to link the power plant to the load of the consumers. 1 / 1 point TRUE FALSE Correct The function of an electrical power system is to connect the power station to the consumers' load. 4. Question 4 ______________ is the process of converting energy found in various forms across nature into electrical energy. 1 / 1 point Electric power generation Mechanical Power Generation Electrical and Mechanical Power Generation none of these Correct The conversion of energy available in different forms in nature into electrical energy is known as power generation of electrical energy. 5. Question 5 _______________ uses steam generated by the combustion of oil, liquid natural gas (LNG), coal, and other materials to turn generators and generate electricity. 1 / 1 point Thermal power generation Wind power Generation Synchronous generator Asynchronous Generator Correct When oil and coal are burnt in boilers, thermal energy is released. This thermal energy is used to make steams to run steam turbines. Similarly, natural gas is burned in gas turbine to produce electrical energy. 6. Question 6 Pressure is generated in the working fluid cycle in thermal power plants by ________ 1 / 1 point condenser superheater feedwater pump turbine Correct The heated flue gases from burner converts water in water tubes into steam. 7. Question 7 _____ is the bulk transfer of electrical energy from a generating facility, such as a power station or power plant, to an electrical substation, where voltage is altered and delivered to consumers or other substations. 1 / 1 point Electrical power transmission distribution system Electrical Power Generation none of these Correct The transmission system is made up of transmission lines that transports power from the generation system through power transformers 8. Question 8 The traditional electric power business was run as a vertically integrated regulated monopoly, with generating, transmission, and distribution facilities all owned by the same company. 1 / 1 point TRUE FALSE Correct The main objective of electric power restructuring is to significantly reduce the cost of power charge to small businesses and consumers. 9. Question 9 The major goal of electric power restructuring is to raise the cost of electricity charged to small enterprises and consumers dramatically. 1 / 1 point TRUE FALSE Correct Generation utilities will no longer have a monopoly, small businesses will be free to sign contract for buying power from cheaper sources. 10. Question 10 The primary objective of all power system is 1 / 1 point to provide Reliable power to provide Quality power to Increase Cost of power to provide Reliable and Quality Power Correct to maintain continuity of quality power supply to customers Whenever abnormal electrical fault conditions occur the protective equipment should function so as to reduce damage and minimize outage time to customers 11. Question 11 ______ is the abnormal condition of the electrical system which damages the electrical equipment and disturbs the normal flow of the electric current 1 / 1 point Electrical fault mechanical fault Both 1 and 2 none of these Correct An electrical fault is an abnormal condition caused by equipment failures such as transformers and rotating machines, human errors, and environmental conditions. 12. Question 12 The following are examples of transmission line faults that could occur: 1. 3-phase fault 2. L-L-G fault 3. L-L fault 4. L-G fault The increasing order of severity of the fault from the stability point of view is 1 / 1 point 4-3-2-1 2-3-4-1 1-3-2-4 3-1-4-2 Correct Among the faults, 3-phase faults is most severe and line to ground is least severe. LG<LL<LLG<LLL 13. Question 13 That fault on the power system which gives rise to equal fault currents in the lines with 120degree displacement is called a 1 / 1 point unsymmetrical fault open conductor fault symmetrical fault none of these Correct symmetrical or balance fault, during a short circuit gives the equal currents in all the phases. 14. Question 14 If all of the sequence voltages at a power system's fault location are equal, the fault is a 1 / 1 point Three-phase fault Line to ground fault Line to line fault Double line to ground fault Correct In this fault, two lines come in contact with each other along with ground. Hence Va0=Va1=Va2 15. Question 15 The power system is subjected to a fault which makes the zero-sequence component of current equal to zero. The nature of fault is 1 / 1 point Line to ground fault Double line fault Double Line to ground fault Three phase to ground fault Correct In this fault, there is no ground. Hence the zero sequence current is zero 16. Question 16 ___________ is a series type unbalanced fault that occurs in a power system. 1 / 1 point Line to line fault Double line to ground fault single line to ground fault open circuit fault Correct open circuit fault also known as series faults, which are unsymmetrical or unbalanced types of faults except three phase open fault. These faults occur due to the failure of one or more conductors 17. Question 17 A ____ is a logical element which process the inputs (mostly voltages and currents) from the system and issues a trip decision if the pickup level of actuating signal is reached. 1 / 1 point Switch Fuse Protective relay Isolator Correct A relay is designed to trip circuit breaker when a fault is detected. 18. Question 18 An ability of Relay system to operate under predetermined condition is 0 / 1 point Sensitivity Selectivity Stability Reliability Incorrect Refer Desirable Features of Protective Relaying systems to know about desirable features of protective relay systems. 19. Question 19 A distance relay measure 1 / 1 point difference in voltage difference in current difference in impedance difference in phase Correct the relay operates depending upon the impedance between the point of fault and the point where relay is installed. 20. Question 20 The ____ faults are due to short circuits in conductors 1 / 1 point series shunt open fixed Correct Shunt faults involves a short circuit between conductor and ground (or) two or more conductors. 1 Current Transformer is an 'instrumentation' transformer which convert ____ values of currents to _____ values 1 / 1 point low, low low, high high, high high, low Correct The objective of CT is to step down higher values of current to lower value. 2. Question 2 Instrument transformers does not electrically isolate the relaying system from the equipment 1 / 1 point TRUE FALSE Correct Instrument transformers electrically isolates the relaying system from the equipment. 3. Question 3 A magnetic core of CT made up of silicon steel laminations links both the windings for providing 0 / 1 point a low reluctance path a high reluctance path a low resistance path a high resistance path Incorrect Refer Basics of Current Transformers (CT) to know about constructional details of CT 4. Question 4 When a current transformer's secondary winding is opened while the primary winding is carrying current, the following happens: 1 / 1 point Transformer will burn immediately High induced EMF is produced in the secondary winding Flux density in the core gets weakened High current is produced in the secondary winding Correct There is no counter mmf in the secondary winding if the secondary is opened. The entire primary current operates as a magnetizing current, causing high secondary voltages. This results in high core losses and heat, which in turn causing CT to be burned. 5. Question 5 Voltage transformers are designed to have _____________ 1 / 1 point high leakage reactance high magnetizing current high magnetizing reactance low magnetizing reactance Correct Voltage transformers are designed with low leakage reactance, low loss and high magnetizing reactance. 6. Question 6 _____________ is the value of the CT's secondary voltage over which the output current no longer follows the input current linearly within the claimed accuracy limitations. 1 / 1 point Cut-in voltage breakdown voltage flashover voltage knee-point voltage Correct The saturation last until the principal transient current falls below the saturation level. 7. Question 7 Saturation in the current transformer core is caused by the presence of _____ in fault current. 1 / 1 point primary current DC offset secondary current magnetizing current Correct DC offset in fault current is the causes of saturation in current transformer core. 8. Question 8 The acronym OTDR stands for 1 / 1 point Optical Time Data Register Optical Transfer Data Rate Optical Time Domain Reflectometer Optimal Transfer Domain Rate Correct It is an optoelectronic instrument used to characterize an optical fiber. 9. Question 9 The VT circle diagram is a quick and easy way to determine accuracy at any load and power factor 1 / 1 point TRUE FALSE Correct A simple technique to assess accuracy at any load and power factor is to use the PT or VT circle diagram. 10. Question 10 The maximum load in VA that the transformer can carry at the rated secondary voltage without exceeding the temperature rise is known as 1 / 1 point PT thermal rating mismatch of CT saturation difference in connection of CT Correct IEEE standards identify five rating parameters for voltage transformers, basic impulse insulation level in terms of full-wave test voltage, rated primary voltage and ratio, rated frequency, accuracy ratings, thermal burden rating. 1. Question 1 In the first few cycles, any motor, such as an induction or synchronous motor, must be considered as a source for computing fault current. 1 / 1 point TRUE FALSE Correct Due to moment of inertia the motor will contribute to the fault current. 2. Question 2 The Electrical Fault Occurrence Statistics Descending order A. Single-phase-to-ground B. Phase-to-phase-to-ground C. Phase-to-phase D. Three-phase 1 / 1 point A,B,C,D B,A,D,C B,A,C,D A,B,D,C Correct the electrical fault occurrence for LG-(70-80)% LLG-(10-17)% LL-( 8-10)% , LLL-( 2-3)% percent. 3. Question 3 If an IDMT relay has a plug setting of 50% and a CT ratio of 400/5, and the fault current is 3000 A, the plug setting multiplier is, 1 / 1 point 7.5 15 17.5 37.5 Correct The plug setting multiplier is the ratio of fault current to the product of plug setting and CT ratio Plug setting= 0.5*5=2.5A CT Ratio=400/5=80 PSM=3000/(2.5*80)=15 4. Question 4 Calculate the relay's operating current for a 5 A load, a 2.2-second IDMT rating, and a 125 percent relay setting. 1 / 1 point 2.5 5 12.5 6.25 Correct The operating current of relay is calculated as the product of rated current in CT and current setting= 1.25*5=6.25A 5. Question 5 An earth fault relay has a setting of 150 percent and a current rating of 5 amps. It's connected to a 200:5 ratio current transformer. The primary current detected by the relay is 1 / 1 point 7.5 A 20 A 300 A 1500 A Correct The primary of the CT is given by product of CT turns ratio and pick up current = (1.5*5*(200/5))= 300A 6. Question 6 In a earth fault relay ______ helps in the detection of a fault. 1 / 1 point positive sequence current zero sequence current negative sequence current positive sequence voltage Correct earth fault relays employ zero sequence current, internal phase present for, fault detection to offer sensitive protection. 7. Question 7 The time between the initiation of the fault and the moment when the fuse is blown off is known as________ time in fuses. 0 / 1 point Pre-arching time Arching time Post-arching time Operating time Incorrect Refer Fuses and Miniature Circuit Breaker for protection to know about basics of operation of fuses. 8. Question 8 ________ are rewireable fuses that interrupt low current faults. 1 / 1 point Kit-kat fuses Knife blade type fuse bolted type fuse switch type fuse Correct The rewire fuse also called as kit-kat type is used for interruption of low value of fault current. 9. Question 9 Which among the following is not a type of inverse definite minimum time (IDMT) relays 1 / 1 point Standard Inverse Very Inverse Extremely inverse Most Inverse Correct classified as, standard inverse, very inverse, and extremely inverse relays. 10. Question 10 ANSI Device Number for Time-overcurrent relay is 1 / 1 point 52 51 50 53 Correct According to IEEE C37.2 device number 51 represents time over current relay 1. Question 1 In a grounded system with low grounding resistance, the ground fault current will be 1 / 1 point large small very small negligibly small Correct If the grounding resistance is low, the ground fault current will be large, and the system will resemble the effectively solidly grounded system. 2. Question 2 The current transformer protects the star-star power transformer by having 1 / 1 point Star/star connections Delta/delta connections Star/delta connections Delta/star connections Correct In order to nullify the phase shift of the Power transformer (PT), The Current transformers (CT) connected in a reverse configuration. The star-star power transformer is protected by the current transformer having delta/delta connections. 3. Question 3 To protect against stator insulation failure, what form of protection is offered on a generator? 1 / 1 point Differential protection Overcurrent relay Thermocouple actuated alarm Reverse power relay Correct Generally, differential relays are used to protect the equipment against internal faults. Merz price protection scheme is one form of the differential relay which is used to protect the stator winding of Alternator from the internal faults. 4. Question 4 For power transformers to have differential protection (delta-delta), the current transformers will need to have 1 / 1 point Delta-delta connection Star-delta connection Star-star connection Delta-star connection Correct In order to nullify the phase shift of the Power transformer (PT), The Current transformers (CT) connected in a reverse configuration. The delta-delta power transformer is protected by the current transformer having star-star connections. 5. Question 5 Merz price differential relay is used to protect transformers against 1 / 1 point internal shorts circuits and ground faults oil failure core failure transmission line fault Correct Merz-Price differential protection is used to safeguard the transformer against internal short circuits, internal ground faults, and interturn shorts. 6. Question 6 For electrical equipment protection, differential relays are employed to detect 1 / 1 point internal faults overcurrent reverse current reverse power Correct Generally, differential relays are used to protect the equipment against internal faults. Merz price protection scheme is one form of the differential relay which is used to protect the stator winding of Alternator from the internal faults. 7. Question 7 To protect transmission lines utilizing the Translay protection system, the following number of pilot wires is required: 1 / 1 point 1 2 3 4 Correct The translay relay is another type of differential relay. The arrangement is similar to overcurrent relay but the secondary winding is not closed on itself. The number of pilot wires required to protect transmission lines using translay protection system is two. 8. Question 8 Which of these is a type of unit protection in a feeder? 0 / 1 point Directional time graded protection Distance protection Balanced voltage system Unbalanced voltage system Incorrect Refer Merz Price Differential Relay to know about unit protection 9. Question 9 The relay used to protect the feeder is 1 / 1 point Undervoltage relay Translay relay Thermal relay Buchholz relay Correct The translay relay is a differential relay. The arrangement is similar to overcurrent relay, but the secondary winding is not closed on itself. These types of relays are used in the feeder protection 10. Question 10 Connecting the neutral to the ground through a reactor is called 1 / 1 point resistance grounding capacitive grounding short grounding reactance grounding Correct In a reactance grounding, reactance is connected between neutral and ground to limit the fault current. reactance grounding. The selection of the reactance is important for effective grounding. 1. Question 1 The condition for maximum torque angle is obtained when the current is __________ ahead of the polarizing voltage. 0 / 1 point 30 degrees 90 degrees 45 degrees 60 degrees Incorrect Refer Earth Fault Protection of AC Motors to know about voltage polarizing source. 2. Question 2 An induction motor is the same as 1 / 1 point D.C. compound motor D.C. series motor Asynchronous motor Correct An induction motor is called asynchronous motor because the actual speed of the motor is not equal to the synchronous speed of the motor. The synchronous speed of the motor is always more than the actual speed of the motor. 3. Question 3 The semiconductor device used in ac motor soft starter to control voltage is 0 / 1 point MOSFET IGBT Thyristor TRIAC Incorrect Refer Start / Stall Protection of AC Motors to know about soft starter. 4. Question 4 Slip is 4% for a three-phase 440 V, 50 Hz induction motor. The rotor current frequency will be 1 / 1 point 2 Hz 5Hz 25Hz 50Hz Correct In an induction motor, the rotor current frequency relate to slip is given by fr=s*f. Therefore fr=0.04*50=2Hz 5. Question 5 _______ is used to protect the induction motor from running in the reverse direction. 1 / 1 point Over voltage protection over current protection phase reversal protection under voltage protection Correct Phase reversal protection is used to protect the induction motor, from running in reverse direction. Normally running a motor in reverse direction does not affect the system when the motor is empty. But Running a induction motor in reverse direction with mechanical loads causes heavy load current flow on the motor’s stator winding 6. Question 6 ____ is the minimal torque produced by an electric motor from zero to maximum load speed. 1 / 1 point Break down Torque Pull-up Torque Pull out Torque Locked Rotor Torque Correct The Pull-up Torque is the minimum torque developed by an electrical motor when it runs from zero to full-load speed 7. Question 7 ______ is employed to protect the motor against Stalling 1 / 1 point Instantaneous over-current relay Thermal overload relay Buchholz relay mho relay Correct Stalling protection can also be provided by a separate definite time overcurrent relay which is operated only after a certain predefined time if overcurrent persists beyond that period. 8. Question 8 _____ are provided for the protection of motor against single phasing. 1 / 1 point Instantaneous over-current relay Thermal overload relay Buchholz relay mho relay Correct It provides the most accurate tripping of the motor during overload & single phasing. 9. Question 9 When the motor is supplied with an imbalanced supply voltage, _________flow into the motor 1 / 1 point Positive sequence currents Zero Sequence currents Negative sequence currents only positive and zero sequence currents flows Correct During the unbalanced conditions, negative sequence currents. These currents are undesirable which will generate high and possibly dangerous temperatures in a very short time. 10. Question 10 Which of the following relays is utilized for overload protection of motors? 1 / 1 point Buchholz relay Thermal relay Impedance relay mho relay Correct A thermal relay in which when a bimetallic strip is heated up by a heating coil carry over current. It is generally used where overload is allowed to flow for predetermined amount of time before it trips. An application of thermal relay is overload protection of electric motor