Basic Mechanical Engineering [MECE2011] B.Sc Civil Engineering Credit hours – 1+0 Lecture – 5 Heating and Cooling Load Calculations Department of Mechanical Engineering Capital University of Science and Technology Islamabad, Pakistan Introduction Buildings are built to provide a safe and comfortable internal environment despite variations in external conditions. The extent to which the desired interior conditions can be economically maintained is one important measure of the success of a building design. Although control of inside conditions is usually attribute to the active heating and cooing system, the design of HVAC must start with the examination of the thermal characteristics of the envelope. They influence both the equipment capacity and the energy required for its operation. The primary objective of this paper is to examine procedures for evaluating the impact of the thermal characteristics of the building envelope on the design of HVAC systems used to maintain comfort. Health and Comfort Criteria The human body is an amazingly adaptable organism. With long-term conditioning, the body can function under quite extreme thermal conditions. Variations in outdoor temperature and humidity, however, often go beyond the normal limits of adaptability. Therefore, It becomes necessary to provide modified conditions indoors in order to maintain a healthy, comfortable environment. Thermal Comfort The figure illustrates the factors that influence thermal comfort. First, body heat is generated b metabolic processes to maintain body temperature. Metabolic processes are influenced by such factors as age, health and level of activity. For example, a given range of environmental conditions might be quite acceptable in a space occupied by a healthy person but unacceptable for one who is ill. When people are willing to adjust their dress habits with the changing seasons, they find that they are comfortable over a broader range of environment conditions than they would expect. Thermal Comfort The body is continuously generating heat, which must be dissipated to maintain a constant body temperature. Temperature control can be accomplished by various mechanisms. For a person at rest of doing light word in a conditioned space, the body dissipates heat primarily by convection (carried away by the surrounding air) and radiation ( to surrounding surfaces that are at lower temperature than the body surface. Thermal Comfort Each of these components faces of heat dissipation accounts for approximately 30 percent of the heat loss. Evaporation, from both respiration and perspiration, accounts for the remaining 40 percent. As environmental conditions or levels of activity change, these percentages will vary. For example, if a person is doing strenuous work, the primary heat dissipation mechanism will be evaporation. Thermal Comfort Four environmental factors influence the body’s ability to dissipate heat Air temperature, The temperature of the surrounding surfaces, Humidity, Air velocity. The amount and type of clothing and the activity levels of the occupants interact with these factors. In designing an air conditioning system we turn our attention to the control of these four factors. Thermal Comfort If a person is wearing appropriate clothing, the following ranges should usually be acceptable. Operative temperature : 20 to 26 oC. Humidity. A dew-point temperature of 2 to 17 oC . Average air velocity: Up to 0.25 m/s. Air Quality Air quality must also be maintained to provide a healthy, comfortable indoor environment. Sources of pollution exist in both the internal and external environment. Indoor air quality is controlled by removal of the contaminant or by dilution. Ventilation plays an important role in both processes. Ventilation is defined as supplying air by natural or mechanical means to a space. Normally, ventilation air is made up of outdoor air and recirculated air. The outdoor air is provided for dilution. In most cases odor and irritation of the upper respiratory tract or eyes are the reason for ventilation rather than the presence of health threatening contaminants. Air Quality If the level of contaminants in outdoor air exceeds that for minimum air quality standards, extraordinary measures must be used. For the present discussion, it will be presumed that outdoor air quality is satisfactory for dilution purposes. Following table presents outdoor air requirements for ventilation for three occupancy types listed in standard. As noted in table, much larger quantities of air are required for dilution in areas where smoking is permitted. Air Quality Ventilation imposes a significant load on heating and cooling equipment and thus is a major contribution to energy use. Space occupancies and the choice of ventilation rates should be considered carefully. For example, if smoking is permitted in part of a building but restricted in another part of the building, ventilation rates for smoking should not be assumed uniformly. Also, the prospect of filtering and cleaning air for recirculation must be examined carefully. The use of recirculated air will conserve energy whenever the outdoor-air temperature is extremely high or low. Air Quality The ASHRAE standard provided the following procedure for determining the allowable rate for recirculation 𝑽. = 𝑽.𝒓 + 𝑽.𝒎 Where, 𝑉 . = rate of supply air for ventilation purposes, L/s 𝑉𝑟. = recirculation air rate, L/s 𝑉𝑚. = minimum outdoor air rate for specified occupancy, for example the non-smoking value from Table 4-1, but never less that 2.5 L/s per person Also, . − 𝑽. 𝑽 𝒐 𝒎 𝑽.𝒓 = 𝑬 𝑉𝑜. = outdoor air rate from Table 4-1 for specified occupancy (smoking or non-smoking, as appropriate). L/s E = Efficiency of contaminant removal by air cleaning device. Air Quality E = Efficiency of contaminant removal by air cleaning device. The efficiency must be determined relative to the contaminant to be removed. Table 4-2 provides values appropriate for removal of 1 μm particles. Example 4-1 Determine the ventilation rate, outdoor-air rate, and recirculated-air rate for an office building meeting room if smoking is permitted. Air air-cleaning device with E = 60 percent for removal of tobacco smoke is available? Solution: . . 𝑽 − 𝑽 𝒐 𝒎 𝑽.𝒓 = 𝑬 𝑽.𝒐 = outdoor air rate from Table 4-1 for specified occupancy (smoking or non-smoking, as appropriate). L/s; From Table 4-1, outdoor air requirements rate per person for meeting and waiting spaces with smoking permitted = 17.5 L/s = 𝑽.𝒐 𝑽.𝒎 = minimum outdoor air rate for specified occupancy; From Table 4-1; required outdoor-air rate for non-smoking spaces = 3.5 L/s = 𝑽.𝒎 . 𝑉𝑜. −𝑉𝑚 17.5−3.5 Ventilation rate; = = = 23.3 L/s = 𝑽.𝒓 𝐸 60/100 Recirculated air rate = 𝑽. = 𝑉𝑟. + 𝑉𝑚. = 23.3 + 3.5 = 26.8 𝑽.𝒓 L/s per person Estimating Heat Loss and Heat Gain Heat transfer through a building envelope is influenced by the materials used; by geometric factors such as size, shape and orientation; by the existence of internal heat sources; and by climate factors. System design requires each of these factors to be examined and the impact of their interactions to be carefully evaluated. The primary function of heat loss and heat gain calculations is to estimate the capacity that will be required for the various heating and air conditioning components necessary to maintain comfort within a space. These calculations are therefore based on peak-load conditions for hearing and cooling and correspond to environmental conditions which are neat the extremes normally encountered. Standard outside design values of temperature, humidity and solar intensities are usually available from handbooks. Estimating Heat Loss and Heat Gain 1. 2. 3. 4. Loads are generally divided into the following four categories. Transmission Solar Infiltration Internal 1. Transmission: Heat loss or heat gain due to a temperature difference across a building element. 2. Solar: Heat gain due to transmission of solar energy through a transparent building component or absorption by an opaque building component. Estimating Heat Loss and Heat Gain 1. 2. 3. 4. Loads are generally divided into the following four categories. Transmission Solar Infiltration Internal 3. Infiltration: Heat loss or heat gain due to the infiltration of outside air into a conditioned space. 4. Internal: Heat gain due to the release of energy within a space (lights, people, equipment, etc) In response to these loads, the temperature in the space will change or the heating or cooling equipment will operate to maintain a desired temperature. Design Conditions The design conditions usually specified for estimating heating loads are the inside and outside dry bulb temperatures. For heating operation, an indoor temperature of 20 to 22 oC is generally assumed and for cooling operation, 24 to 26 oC is typical. A minimum relative humidity of 30 % in the winter and a maximum of 60 % in the summer is also assumed. For heating operation, the 97.5 percent value of the outside temperature is usually chosen. This means that on a long-term basis of the outside dry bulb temperature equals or exceeds this value for 97.5 percent of the hours during the coldest months of the year. At the 97.5 percent outdoor temperature, the air is assumed to be saturated. Design Conditions The set of conditions specified for the cooling load estimates is more complex and includes dry-bulb temperature, humidity and solar intensity. Peak-load conditions during the cooling season usually correspond to the maximum solar conditions rather than to the peak outdoor-air temperature. Thus, it is often necessary to make several calculations at different times of the day or times of the year to fix the appropriate maximum cooling capacity requirements. When the cooling load calculation is made, will depend on the geographic location and on the orientation of the space being considered. For example, peak solar loading on an east facing room may occur at 8 AM, while for a west room the maximum load may occur at 4 PM. Design Conditions Peak solar loads for south-facing rooms will occur during the winter rather than the summer. Of course, when a cooling system serves spaces with different orientations, the peak system load may occur at a time other than the peak for any of the several spaces. Fortunately, after making a number of such calculations, one begins to recognize likely choices for times when the peak load may occur. Table 4-3 provides outdoor design temperature data for a number of locations. The table provides the 97.5 percent dry-bulb temperature for winter and the 2.5 percent dry bulb and coincident wet bulb temperature for summer. The 2.5 percent dry bulb temperature is the temperature exceeded by 2.5 percent of the hours during June to September. The mean coincident wet-bulb temperature is the mean wet-bulb temperature occurring at that 2.5 percent dry bulb temperature. Design Conditions Example 4-2 Select outside and inside design temperatures for a building to be constructed in Denver, Colarado. Solution: From Table 4-3, the summer design conditions are given as: Summer design dry bulb temperature = 33 oC Coincident wet-bulb temperature = 15oC Assuming that no special requirements exist, an inside design temperature of 25oC and 60 % relative humidity is chosen. The winter design outside temperature is -17oC from Table 4-3, and if no special requirement exist, an inside design temperature of 20oC and 30% relative humidity is chosen. It should be noted that the inside design temperature only limits the conditions that can be maintained in extreme weather. During heating operation, when the outside temperature is above the outside design value, an inside temperature greater than 20oC can be maintained if desired.