ANSI/IEEE C37.010-1979 (Includes Supplement ANSI/IEEE C37.010d-1984) (Revision of ANSI/IEEE C37.010-1972) An American National Standard IEEE Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Bass Sponsor Switchgear Committee of the IEEE Power Engineering Society Approved May 29,1975 Reaffirmed October 20, 1988 Secretariat Institute of Electrical and Electronics Engineers National Electrical Manufacturers Association Approved December 12,1975 Reaffirmed February 2, 1989 American National standardsInstitute ANSlllEEE C37.010d-1984 approved March 11, 1982 by the IEEE Standards Board Approved April 29, 1983 by the American National Standards Institute Published by The Institute of Electrical and Electronics Engineers, Inc 345 East 47th Street, New York, NY 10017 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. American National Standard An American National Standard implies a consensus of those substantially concerned wi National Standard is in e manufacturer, the consumer, and the of an American National Standard does he has approved the standard purchasing, or using products, ing to the standard. eriodic review and users CAUTION NOTICE: This American National Standard may be revised or withdrawn at any time. The procedures of the American National Standards Institute require that action be taken to reaffirm, revise, or withdraw this standard no later than five years from * National Standards the date of publication. may receive current info s by calling or writing the American National S @Copyright 1979 by The Institute of Electrical and Electronics Engineers, Inc N o part of this publication may in an electronic retrieval without the prior written permission o Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. Foreword I (This Foreword is not a part of ANSI/IEEE C37.010-1979, American National Standard Application Guide for AC High-Voltage Circuit Breakers Rated o n a Symmetrical Current Basis.) This standard is a guide to aid in the selection and application of AC high-voltage circuit breakers on electrical power systems. Described in the guide are the general application conditions, application considerations, and short-circuit considerations necessary to apply alternating current circuit breakers. This standard is a revision of ANSI/IEEE C37.010-1972. This revision contains substantive revisions due to the efforts of a working group on revisions to C37.010-1972, and editorial changes as a result of general power circuit breaker consolidation efforts. Three substantive ns are included. The first involves deletion of a Procedure Chart, from Section 5.3,page 26, e previous standard. This simplified procedure for calculating short-circuit current was useful in only a few cases, and was somewhat confusing for anyone attempting t o use it. The second substantive revision is an expansion of the statements in 5.3.2 involving the general terms “one transformation” and “two or more transformations” to recognize large external impedances such as long lines or station service transformers. Previously, “one transformation” in the form of a station service transformer dictate the use of factors from Figs 7 and 8. However, because this relatively large impedance limits the ac component decay, the wording on page 34 specifies the use of factors from Fig 9 for both three-phase and line-to-ground faults. The third substantive revision involves the rotating machine reactance table of multipliers on page 40. The multipliers under the heading “Closing and Latching Duty” were previously specified in a section of Note 4 which is deleted. The substantive change involves the placing of all motors above 1000 hp with speeds 1800r/min and below into the 1.5 multiplier category. See chart below. 3600 M = 3.0 t ,, M = 1.5 A Y II MULTIPLIER 50 250 - 3.0 500 M - 1.5 750 IOC Y o 0 RATING - HP Based on the ac short-circuit time constants of these larger, slower-speed machines and the fact that circuit breakers are available with rated interrupting times of 5 cycles or less, the 1.5 multiplier will give conservative results, whereas the previously shown 3.0 multiplier would not. The remainder of the changes are editorial. They involve updating the examples and clarification of the material in the guide. In addition, a number of changes were made as part of the general consolidation of power circuit breaker standards. Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. The development of standards for the rating, testing, and manuf breakers began almost simultaneously with the application of the power supply systems. A number of engineering and manufacturers trade organizations were int -voltage circuit breakers as well as other types of electrical equipment ard requirements for capabilities, sizes, and testing procedures. AIEE’, the National Electric Light Association (NELA), the Electric NEMA - the National Electrical Manufacturers Association), the As ing Companies (AEIC), and the Edison Electric Institute (EEI). s up to 1940, these organizations adopted and pub1 cerning rating, testing, and other requirements for hi In 1941 a unified series of standards for circuit breakers, based NEMA, w blished for trial use by the American Standards Associa the first American Standard for high-voltage circuit breakers. In 19 approved American Standard with the familiar C37 number iden g, preferred sizes, testing, and application of circuit dards was revised and supplemented by additional se basic group of American Standards for high-voltage circuit breakers. At group of standards included: NSI C37.4-1953 AC Power Circuit Breakers (included definitions, ra test requirements) ANSI C37.5-1953 Methods for Determining the RMS Value of a Sinusoidal Current Wave and Normal-Frequency Recovery Voltage, and for Simplified Calculation of Fault Currents ANSI C37.6-1953 Schedules of Preferred Ratings for Power Circuit Breakers ANSI C37.7-1952 Interrupting Rating Factors for Reclosing Service ANSI C37.8-1952 Rated Control Voltages and their Ranges ANSI C37.9-1953 Test Code for Power Circuit Breakers ANSI C37.12-1952 Guide Specifications for Alternating Current Power Circuit Breakers Under these original standards, the basis of the interrupting rating was established by 6.11 of ANSI C37.4-1953 as the highest current t o be interrupted at the specified operating voltage and was the “. . . rms value including the dc component at the instant of contact separation as determined from the envelope of the current wave.” Since this standard based the interrupting rating on the total current including dc component at the instant of contact separation, it has as the “Total Current Basis of Rating.” For circuit breaker application, a simplified method was avail iplying factors for use with the system symmetrical fa tal rms current which could be present at contact separation. This c choose the required circuit breaker rating from those listed in revisions. The factors recognized typical system characteristics an ‘AIEE (American Institute of Electrical Engineers) merged with IRE (Institute of Radio Engineers) January 1, 1963 to form the joint organization IEEE (Institute of Electrical and Electronics Engineers). Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. In 1951, the AIEE Switchgear Committee began to give consideration to the development of a circuit breaker rating method based on symmetrical interrupting currents. This work was initiated with the goal of: (1) Simplifying application where high-speed relaying and fast clearing circuit breakers are used (2) Bringing American standards into closer agreement with accepted international standards (IEC-International Electrotechnical Commission) t o avoid confusion on rating differences (3) Requiring that circuit breakers are proven to demonstrate a definite relationship between asymmetrical interrupting capability and symmetrical ratings During the course of this work, principally in a working group of the AIEE Power Circuit Breaker Subcommittee, numerous reports of the proposals on the new rating, testing, and application methods were made to the industry as a whole through committee sponsored papers a t AIEE meetings in 1954, 1959, and 1960. Suggestions made in discussions were considered by the working group and incorporated where practicable. The principal change from the 1953 “Total Current” standard was in the basis of rating. 4.5.1 of ANSI C37.04 established the Rated Short Circuit Current as “the highest value of the symmetrical component of the.. . short-circuit current in rms amperes, measured from the envelope of the current wave at contact separation, which the circuit breaker is required t o interrupt at rated maximum voltage. . .”. Certain related capabilities were also required, including operation under specified conditions of asymmetry based on typical circuit characteristics and circuit breaker timing. This rating structure became known as the Symmetrical Current Basis of Rating as compared to the previous Total Current Basis of Rating. However, as the new ratings were developed, it became apparent that changes from the older t o the newer standard could not occur overnight due to requirements for rerating and retesting of many PCBs. It was, therefore, decided to retain both rating structures, with the understanding that all new circuit breaker developments would be directed toward the symmetrical siandards. The circuit breakers based on the total current standards would be transferred t o the new standards as work progressed in rerating programs. This transfer is being carried out and ANSI C37.6 and ANSI C37.06 have been revised accordingly a number of times. The symmetrical current group of standard sections was published in 1964 and was given ANSI C37.04, C37.05, C37.06, etc, designations. These sections and the corresponding 1953 sections were : Total Current Standard Symmetrical Current Standard Subject ANSI C37.4 ANSI C37.03 ANSI C37.04 ANSI C37.04a Definitions Rating Structure ANSI C37.5 ANSI C37.05 Measurement of Voltage and Current Waves ANSI C37.6 ANSI C37.06 ANSI C37.06a Preferred Ratings ANSI C37.7 ANSI C37.07 Reclosing Factors ANSI C37.8 (included in ANSI C37.06) Control Voltages ANSI C37.9 ANSI C37.09 ANSI C37.09a Test Code ANSI C37.5 (Section 3) ANSI C37.010 Application Guide (expansion of material previously in C37.5) Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. Sections .04a, .06a, and .09a, also issued in 1964, were addenda concerned with supplemental dielectric capability requirements. In ANSI C37.06-1964 and subsequent revisions prior to 1971, circuit breaker symmetrical current i n t e r r u p w ratings were derived from ratings in ANSI C37.6-1961 by a relationship following a middle ground position between the total (asymmetrical) current of the former rating method and the full range of related requirements of the new rating method. For a given breaker this derivation was expressed by the formula: rated short circuit current where = 1,961 nominal voltage rated maximum voltage 11961 = interrupting rating in amperes appearing in ANSI C37.6-1961 F = 0.933 for 3 cycle breakers 0.955 for 5 cycle breakers 1.0 for 8 cycle breakers Rated short circuit current was tabulated for rated maximum voltage rather than for nominal voltage as had been the case under the total current basis of rating. It was stressed that this derivation was for the numerical conversion only and that a breaker, designed and tested under the total current basis of rating, could not be assu these capabilities under the symmetrical current basis of rating without approval of the manufacturer. In the revision of ANSI C37.06 published in 1971, several simplifications were introduced, including the use of a new method for selection of intempting current ratings for outdoor circuit breakers 121 kV and above. Values for rated short circuit current were chosen fr the R-10 preferred discontinued. Also number series, and the use of a reference nominal 3-phase MVA identificatio the rated voltage range factor K was changed to unity, 1.O,to simplify rating and testing procedures. In the intervening years since the official publication of the primary sections of the symmetrical basis of rating standard for high-voltage circuit breakers, a number of revisions, additions, and improvements have been developed and published. Many of these additions were in subject areas of major importance in the rating, testing, and application of circuit breakers and were published as complete standards containing appropriate definitions, rating performance criteria, rating numbers, test procedures, and application considerations. This was done to avoid delay in publication and the necessity of reprinting other existing standards as each of these was completed. The result has been the publication of a substantial number of individual supplementary standards. The basic subject areas considered in these supplementary standards, and their initial publication dates, are shown below: ANSI 637.071-1969 Requirements for Line Closing Switching Surge Control ANSI C37.072-1971 Requirements for Transient Recovery Voltage ANSI C37.0721-1971 Application Guide for Transient Recovery Voltage ANSI C37.0722-1971 Transient Recovery Voltage Ratings ANSI C37.073-1972 Requirements for Capacitance Current Switching ANSI C37.0731-1973 Application Guide for Capacitance Current Switching ANSI C37.0732-1972 Preferred Ratings for Capacitance Current Switching ANSI C37.074-1972 Eequirements for Switching Impulse Voltage Insulation Strength ANSI C37.076-1972 Requirements for Pressurized Components ANSI C37.078-1972 Requirements for External Insulating Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI C37.0781-1972 Test Values for External Insulation ANSI C37.079-1973 Method of Testing Circuit Breakers When Rated for Out-of-Phase Switching A goal of work recently completed, and reprehented by the 1979 publication of these standards, has been the editorial incorpo the supplementary standards listed above into the proper primary standards documents. breakers rated on a metrical current basis, the consolidated standards sections are: ANSI/IEEE C37.04-1979 Rating Structure ANSI C37.06-1979 Preferred Ratings and Related Required Capabilities ANSI/IEEE C37.09-1979 Test Procedure ANSI/IEEE C37.010-1979 Application Guide - General ANSI/IEEE C37.011-1979 Application Guide - Transient Recovery Voltage ANSI/IEEE C37.012-1979 Application Guide - Capacitance Current Switching The present ANSI C37.05, Measurement of Current and Voltage Waves, is incorporated into ANSI/IEEE C37.09; ANSI C37.07, Interrupting Capability Factors for Reclosing Service, is incorporated into ANSI/IEEE C37.04, ANSI C37.06, and ANSI/IEEE C37.09. Definitions which have been in C37.03-1964 are now in ANSI C37.100-1972. Standards are presently being developed in a number of additional subject areas, which will be initially published as supplementary standards and incorporated into the primary subject document at some future date. Included among these subjects are requirements for current transformers, a guide for synthetic testing, sound level measurements, and seismic capability requirements. For circuit breakers still rated on a total current basis, as listed in ANSI C37.6, the existing standards ANSI C37.4, ANSI C37.6, ANSI C37.7, and ANSI C37.9 will continue to be applicable. Documents pertaining to guide specification and control schemes, which apply to both groups of ratings, are included in the ANSI C37 series as shown below: ANSI C37.11-1972 Requirements for Electrical Control on AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis and a Total Current Basis ANSI C37.12-1969 Guide Specifications for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis and a Total Current Basis Periodic review of all these standards takes place through the normal ANSI procedure that standards are reaffirmed, revised, or withdrawn within no more than five year intervals from the original publication date. Suggestions for improvement gained in the use of this standard will be welcome. They should be sent to the American National Standards Institute 1430 Broadway New York, NY 10018 The basic data included in this consolidated document is the result of contributions made by many individuals over many years. At the time of approval, however, the American National Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. Standards Committee on Power Switchgear, 637, which reviewed and approved this standard, had the following personnel: J. P. Lucas, Secretary C. L. Wagner, Chairman J. E. Beehler, Executive Vice-chairmanof High- Voltage Switchgear Standards W. E. Laubach, Executive Vice-chairmanof Low-Voltage Switchgear Sthndards Wilson, Executive Vice- irman of IEC Activities Organization Represented Name of Representative Association of Iron and Steel Engineers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electric Light & Power Group . . . . . . . . . . . . . . . . . . . . . . ,................. . Institute of Electrical and Electronies Engineers trical Manufacturers Association. Testing Laboratory Group. H. G. Frus K. D. Hendrix F. R. Solis ............................ ...................... ................................. .... ...... Tennessee Valley Authority. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . U.S. Department of the Army . . . . . . . . . . . . . . . . . . . . . . . . . ....... ....... U.S. Department of the Interior, Bureau of Reclamation. . . . . . . . U.S. Department of the Navy, Naval Facilities Engineering Command . . . . . . . . . . . . . . The personnel of the C37 Subcommittee on High Voltage Circuit Bre approved this document were as follows: H. F. White M. J. Beachy (Alt) C. A. Mathews (Alt) R. A, McMaster (Alt) D. C. Musgrave (Alt) A. P. Colaiaco R. W. Dunham D. G. Portman G. A. Wilson W. R. Wilson E. J. Huber R. A. Naysmith R. W. Seelbach (Alt) R. C. St. Clair R. H. Bruc E.M.Tom D. M. Hannemann hich reviewed and F. G. Schaufelberger, Chairman J. J. Fayed, Secretary J. E. Beehler D. 0. Craghead M. A. Durso C. J. Dvorak R. E. Friedrich R. D. Hambrick D. R. Kanitz W. E. Laubach G. N. Lester F. W. Smith D. L. Swindler W. R. Wilson Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. The basic documents used for the consolidation sections of this standard were prepared by various working groups of the Power Circuit Breaker Subcommittee of the IEEE Switchgear Committee. The personnel of the subcommittee at the time of consolidation were: G. N. Lester, Chairman H. W. Anderl J. E. Beehler D. M. Benenson L. E. Brothers R. G. Colclaser J. C. Coon C. F. Cromer C. R. Cusick A. Dupont C. J. Dvorak J. D. Finley R. E. Friedrich T. F. Garrity W. F. Giles K. I. Gray G. P. Guaglione R. D. Hambrick G. R. Hanks W. C. Huening, Jr P. L. Kolarik S.R. Lambert D. M. Larson W. E. Laubach M. J. Maier J. A. Maneatis R. A. McMaster G. J. Meinders G. L. Nuss, Jr I. E. Olivier G. 0. Perkins J. G. Reckleff H. K. Reid A. B. Rishworth W. N. Rothenbuhler F. G. Schaufelberger H. N. Schneider E. F. Solorzano C. J. Truax E. F. Veverka C. L. Wagner D. R. Webster A. C. Wert G. A. Wilson, Jr W. R. Wilson B. F. Wirtz C. E. Zanzie The Working Group members of the IEEE Power Circuit Breaker Subcommittee who developed the substantive revision were: P. L. Kolarik, Chairman H. W. Anderl W. C. Huening, Jr G. L Nus,J r H. 0. Simmons, Jr C. J. Truax C. L. Wagner The Working Group of this subcommittee responsible for the editorial consolidation work on this standard consisted of: N. E. Reed W. N. Rothenbuhler F. G. Schaufelberger When the IEEE Standards Board approved this standard on September 4,1975, it had the following membership : Warren H. Cook, Vice Chairman Joseph L. Koepfinger, Chairman Sava I. Sherr, Secretary Jean Jacques Archambault Robert D. Briskman Dale R. Cochran Louis Costrell Frank Davidoff Jay Forster Irvin N. Howell, Jr Stuart P. Jackson Irving Kolodny William R. Kruesi Benjamin J. Leon Anthony C. Lordi John P. Markey Donald T. Michael Voss A. Moore William S. Morgan William J. Neiswender Gustave Shapiro Ralph M. Showers Robert A. Soderman Leonard Thomas Charles L. Wagner William T. Wintringham Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. Contents SECTION 1. ................................................................ Relatedstandards ................................................ 15 15 .............................................................. General Application Conditions ............................................ 3.1 Usual Service Conditions ........................................... Unusual Service Conditions ......................................... 3.2 Application Consideration ................................................ Maximum Voltage for Application .................................... 4.1 4.2 Voltage Range Factor .............................................. 4.3 Frequency ...................................................... Continuous Current ............................................... 4.4 Rated Dielectric Strength ........................................... 4.5 Standard Operating Duty ........................................... 4.6 4.7 Interrupting Time ................................................. 4.8 Permissible Tripping Delay .......................................... 4.9 ReclosingTime ................................................... 4.10 Short-circuit Rating ............................................... 4.11 Transient Recovery Voltage Rate ..................................... 4.12 Load Current Switching Capability and Life ............................ 15 Scope 1.1 2. 3. 4. Purpose 4.13 4.14 4.15 4.16 4.17 4.18 4.19 4.20 5. 6. PAGE Capacitance Current Switching ....................................... Lineclosing ..................................................... Conditions of Use with Respect to the Out-of-Phase Switching Current Rating Shunt Reactor Current Switching ..................................... Excitation Current Switching ........................................ Mechanical Life .................................................. Rated Control Voltage ............................................. Fluid Operating Pressure ............................................ .... 15 15 15 16 17 17 17 17 23 23 24 24 25 26 27 27 27 27 29 29 29 29 29 30 Short-circuit Considerations .............................................. 5.1 System Short-circuit Currents ....................................... 5.2 Selection of Applicable Circuit Breaker Ratings 5.3 Methods for Calculating System Short-circuit Currents .................... 5.4 Electrical Quantities Used 30 30 32 32 39 References 43 .......................... .......................................... ............................................................ FIGURES Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 Fig 6 Current . Time Relationship to Determine Short-Time Load-Current Capability of High-Voltage Circuit Breakers OperatingTime .................................................. Examples of Reclosing Capability for Some Usual Reclosing Duty Cycles Shown Graphically Power Circuit Breaker Design Requirements System Illustrating Use of Simplified Method of Short-circuit Calculation ..... Positive-Sequence Reactances for System Shown in Fig 5 ..................................... 22 24 ...................................................... 26 31 33 33 ............................ .................. Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. FIGURES Fig 7 Fig 8 Fig 9 Fig 10 Fig 11 Fig 1 2 Fig 13 Fig 1 4 Fig 15 Fig 1 6 Fig 1 7 Fig 18 Fig 19 PAGE Zero-Sequence Reactance for System Shown in Fig 5 . . . . . . . . . . . . . . . . . . . . . Three-phase Fault Multiplying Factors Which Include Effects of AC and DC Decrement ...................................................... Line-to-Ground Fault Multiplying Factors Which Include Effects of AC and DC Decrement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Three-phase and Line-to-Ground Fault Multiplying Factors Which Include Effects of DC Decrement Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Illustrating Use of the E / X Method With Adjustment for AC and DC ........ . Decrements . . . . . . . . , . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Positive-Sequence Impedance for System Shown in Fig 11(Br Zero-Sequence Impedance for System Shown in Fig 11(Brea Positive-Sequence Impedance for System Shown in Fig 11(B Zero-Sequence Impedance for System Shown in Fig 11 (Breaker B) . . . . . . . . . . System Illustrating large Short-circuit Contribution from Motors . . . . . . . . . . . . ........... X / R Range for Power Transformers . , . . . . . . . . . . . . . . . . . ............ X / R Range for Three-phase Induction Motors . . . . . . . . . . . X / R Range for Small Solid Rotor and Salient Pole Generators and Synchronous Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 34 35 36 37 37 37 38 38 40 42 42 42 TABLES Table 1 Table 2 Table 3 Table 4 Table 5 Summary of Temperature Limitations for Circuit Breaker for Various Ambient Temperatures . . , . Ratios of (la/lr) Typical Thermal Time Constants . . . . . . . . . . . . . . . . . . . Range and Typical Values of X / R Ratios of System Compo Equivalent System X / R Ratio at Typical Locations , . . . . . ...... . 19 ............ . . .. . . . ... . . 41 ents 21 APPENDIX Appendix A Basis for E / X Method Corrected for AC and DC D of Short-circuit Currents . . . . . . . . . . . . . . . . . . . . . . . Al. A2. A3. A4. A5. A6. A7. . . . . . . . . . 45 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Application Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . 45 The Effects of AC Component Decrement . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Derivation of E / X Multipliers . . . . . . . . . . . . . . . . . . . . . . . . . . . . * . . . . . . . . 49 Longer Contact Parting Time . . . . . . . . . . . . . . . . . . . . . . . . . Accuracy of Proposed E / X Multipliers . . . . . . . . . . . . . . . . . . . . . . . . . . References to the Appendix . . . . . . . . . . . . . . . . . . . . . APPENDIX FIGURES Fig A Fig A2 Fig A3 Fig A4 Symmetrical and Total Current Decrement; Three-phase Short Circuit; 107 .. . . . . . . . . . 46 MVA 3600 r/min Conductor-Cooled Turbine Generator . . Symmetrical and Total Current Decrement Three-phase Circuit with Generator and System Contribution . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Symmetrical and Total Current Decrement Three-phase S it; Repreenerators ; sentative 95 t o 200 MVA Conductor-Cooled 3600 r/min ults at High Side Terminals of Gener ... . . . . . mmetrical and Total Current Decr sentative 35 to 65 MVA 3600 r/min Turbine Generators . . . . . . . . . . . . . . . . . . . . . e . . Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. PAGE APPENDIX FIGURES Fig A5 Relationship of ( I w m /Isym)mcd to X / R for Several Breaker Contact Parting Times .......................................................... Illustration of Accuracy of Fault Determination Hydro Generation; ThreePhase Fault at High Side Terminals of Station Step-up Transformers ......... Relationship Between X / R Ratio and AC Decrement from Accurate Fault Calculation ...................................................... E / X Multiplier for Equivalent Symmetrical Amperes for Actual X / R (Breaker Capability Curve Corresponds to X / R of Approximately 15) . . . . . . . . . . . . . . . . Relationship of Iwm/Isyrn to X / R for Several Breaker Contact Parting Times (AC Decrement Included) .......................................... Three-phase Fault Multiplying Factors Which Include Effects of AC and DC Decrement ...................................................... Line-to-Ground Fault Multiplying Factors Which Include Effects of AC and DCDecrement ................................................... Three-phase and Line-to-Ground Fault Multiplying Factors Which Include Effects of DC Decrement Only. ...................................... Breaker Asymmetrical Capability ..................................... Illustration of Accuracy of Fault Determination ......................... Illustration of Accuracy of Fault Determination, Single Line-to-Ground Fault [Conventional Cooled Generator (3600-rlmin) Range 95-200 MVA] . . . . . . . . . Illustration of Accuracy of Fault Determination (107 MVA Turbine Generator) ......................................................... Fig A6 Fig A7 Fig A8 Fig A9 Fig A10 Fig A l l Fig A12 Fig A13 Fig A14 Fig A15 Fig A16 48 48 48 50 50 50 51 52 52 52 53 53 APPENDIX TABLES Table A 1 Calculated Symmetrical Amperes ..................................... 46 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. A n American National Standard IEEE Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis Supplement C37.01Od-1984 is indicated by a revision bar in the margin. I 1. Scope 2. Purpose This application guide applies to the ac highvoltage circuit breakers rated in accordance with the methods given in ANSI/IEEE C37.04 1979, Schedules of Rating Structure for AC High-Voltage Circuit Breakers, and listed in ANSI C37.06-1979, Preferred Ratings and Related Required Capabilities for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis. Circuit breakers rated and manufactured to meet other standards, or used in' switchgear assemblies, should be applied in accordance with application procedures adapted to their specific ratings or applications. This guide is intended for general use in the application of circuit breakers. Familiarity with other American National Standards applying to circuit breakers is assumed, and provisions of those standards are indicated herein only when necessary for clarity in describing application requirements. 3. General Application Conditions 3.1 Usual Service Conditions. Service conditions for circuit breakers are defined in ANSI/ IEEE C37.04-1979 (see 4.1). These conditions specify limits in altitude and in ambient temperature. 3.1.1 Provision for System Growth. Power system facilities must be increased from time to time to serve larger loads. This usually results in higher values of short-circuit current. Therefore, liberal allowance for expected future increase in short-circuit current is advisable. 3.1.2 System Design. Methods of limiting the magnitude of short-circuit currents or reducing the probability of highcurrent faults by system design are outside the scope of this guide. Such methods should be considered where short-circuit currents approach the maximum capability of the circuit breakers. Many station design features may depend on available circuit breaker ratings. System design should take into account the necessity for circuit breaker inspection and maintenance. 1.1 Related Standards When the following American National Standards referred to in this document are superseded by a revision approved by the American National Standards Institute, Incorporated, the revision shall apply. ANSI/IEEE C37.04-1979, Ra for AC High-Voltage Circuit Bre ANSI C37.06-1979, Schedules of Preferred Ratings and Related Required Capabilities for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis. ANSI/IEEE C37.09-1979, Test Procedure for AC High-Voltage Circuit Breakers. ANSI/IEEE C37.5-1979, Guide for Calculation of Fault Currents for Application of AC High-Voltage Circuit Breakers Rated on a Total Current Basis. ANSI/IEEE C37.24-1971, Guide for Evaluating the Effect of Solar Radiation on Outdoor Metal-Clad Switchgear. ANSI/IEEE Std 21-1977,Requirements and Test Code for Outdoor Apparatus Bushings. ANSI C37.100-1972, American National Standard Definitions for Power Switchgear. 3.2 Unusual Service Conditions. Unusual service conditions are listed in 4.2 of ANSI/IEEE C37.04-1979 and include those conditions listed below. Special installation, operation, and 15 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSIlIEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE maintenance provisions should be considered where these conditions are encountered. 3.2.1 Applications at Altitudes Above 3300 f t (IO00 m). Rating corrections for altitudes above 3300 ft (1000 m) are listed in Table 1 of ANSI/IEEE C37.04-1979. not designed for use in explosive atmospheres. For this type of service, special consideration should be given in conjunction with applicable regulatory bodies so that acceptable equipment is selected. 3.2.5 Exposure Abnormal Vibration, Shock, or Tilting. S ard circuit breakers are designed for mounting on substantially level structures free from excessive vibration, shock, or tilting. Where any of these abnormal conditions exist, recommendations for the particular application should be obtained from the manufacturer. 3.2.6 Seasonal or Infrequent Use. Equipment stored or deenergized for long periods should be protected against accelerated deterioration. Before energizing for service, operating performance and insu on security should be checked. EXAMPLE: Consider an outdoor oil circuit breaker having a rated maximum voltage of 38 kV, a continuous current rating of 1200 A, a rated short-circuit current of 2 2 000 A at 38 kV, a maximum symmetrical interrupting capability of 36 000 A, and a rated interrupting time of 5 cycles. Assume that this breaker is to be operated at an altitude of 7000 ft (2100 m). The operating voltage and the normal-frequency recovery voltage should be [interpolating between the values given for 5000 and 10 000 ft (1500 and 3000 m ) ] : 38 kV [ 0.95 - (0.95 - 0.80)::701( 1E)] = 33.8 kV. Rated withstand voltages should be multiplied by the same factor. The continuous current must be similarly interpolated: 0.99 plication Consi~e~ation - (0.99 - 0.96) In the application of circuit breakers to electrical systems, attention must be given to many items hnical importance to assure that a misapplication does not occur. In the usual application, the principal function of the circuit breaker is to provide a means for the circuit current. However, it may be used for frequent load, exciting current, or capacitivecurrent switching. In some cases, switching requirements may be the determining factor in selection rather than the requirements of short-circuit current i ption. Special attention must also be to applications where frequent operations are essential. In the selection of a tion must be given t the present needs for for current-carrying capability. These considerations include the possibility of connected circuit changes, such as additions of supplemental cooling means for transformers nection of multiple cable or overhead ossible future transfer of the m its initial postion to some = 1174 A. The rated short-circuit current, related required capabilities, and the rated interrupting time are not affected by altitude. 3.2.2 Exposure to Damaging Fumes, Vapor, Steam, Oil Vapors, Salt Air, Hot and Humid Climate (1) Provison may be necessary to avoid condensation on all electrical insulation and current-carrying parts (2) Bushings with extra creep distance may be required (3) In cases where particular exposure represents a hazard to insulation security, special maintenance including insulator washing may be necessary (4) Materials resistant to fungus growth may be required. 3.2.3 Exposure to Excessive Dust or Abrasive, Magnetic, or Metallic Dust (1) Totally enclosed nonventilated equipment or compartments may be necessary (2) Where current-carrying equipment designed for ventilated operation is enclosed in a nonventilated compartment, derating may be necessary. 3.2.4 Exposure to Explosive Mixtures of Dust or Gases. Standard circuit breakers are In the United States, two types of circuit breakers are available for use at most voltage ratings. These types come under the general classification of oil and oilless power circuit 16 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS ANSIIIEEE C37.010-1979 without derating so that none of their temperature limits is exceeded (3) As far as temperature limits are concerned, any high-voltage circuit breaker may be used with cables having an 85OC or lower temperature limit, provided that the temperature limit of the cable insulation is not exceeded. Among the methods of accomplishing this are: (a) Operate the breaker at a continuous current sufficiently below its rating (b) Use a section of oversize conductors or a special terminal connector ahead of the cable to reduce the temperature at the cable terminal (See IEEE Std 55-1953, Guide forTemperature Correlation in the Connection of Insulated Wire and Cables to Electric Equipment.) (4)The possible adverse effect on or by closely associated equipment operating at a higher or a lower temperature than the breaker should be examined (5) It is recognized that when a circuit breaker is properly selected for continuous current operation, it may also be used for starting such equipment as motors, synchronous condensers, and cold loads on an infrequent basis; under this condition, the continuous current rating may be exceeded without causing damage to the circuit breaker. 4.4.2 Rated Continuous Current for Capacitor Banks. When a high-voltage circuit breaker is used in a circuit supplying static capacitors, the continuous current rating should be selected to include the effects of: (1) Operation at voltages below and up to 1 0 percent above the capacitor rated voltage (2) The positive tolerance in capacitance of static capacitors (- 0+15 percent) (3) The additional heating caused by harmonic currents (4) The effect of grounded or nongrounded neutral connection of the capacitor. In the absence of specific information, it will usually be conservative to use 1.25 times the nominal capacitor current at rated capacitor voltage for nongrounded neutral operation or 1.35 times the nominal current for grounded neutral operation. 4.4.3 Load Current Carrying Capability Under Various Conditions of Ambient Temperature and Load 4.4.3.1 General. Circuit breakers are designed for normal application in accordance breakers, and the preferred ratings available are listed in ANSI C37.06-1979. The choice of breaker type may be influenced by such considerations as attended versus nonattended operation, contaminated atmosphere, location, maintenance, ease of handling the interrupting medium, and cost of the installation. 4.1 Maximum Voltage for Application. The operating voltage and the normal-frequency recovery voltage should not exceed the rated maximum voltage, since this is the upper limit for operation. 4.2 Voltage Range Factor. The voltage range factor, K, is published in ANSI C37.06-1979. In most cases, the voltage range is within the range commonly used. (See 4.10.) 4.3 Frequency. Rated frequency for circuit breakers is 60 Hz. At slightly lower frequencies, such as 50 Hz, the main current-carrying parts will be adequate, but ac control devices may not be suitable for the application. At 25 Hz, the continuous current ratings in amperes are higher and are listed in ANSI C37.06-1979. Interruption of fault currents on systems operating at frequencies other than rated frequency may require modification of mechanisms to change speed of opening or may require a change in interrupting ratings of the circuit breakers. In any case, special consideration should be given to applications at frequencies differing from 60 Hz. 4.4 Continuous Current. Circuit breakers are designed for normal application where the sustained load current does not exceed the rated continuous current, the altitude above sea level is 3300 f t (1000 m) or less, and the ambient temperature does not exceed 4OOC. Rated continuous current of a circuit breaker should not be exceeded except for short periods such as in starting of motors or synchronous condensers or energizing cold loads or for conditions covered by 4.4.3. 4.4.1 Normal Operation. The conditions to be followed when making an application are: (1) Breakers designed for installation in enclosures may be so used without any further derating (2) Breakers designed for use in open rooms and outdoors cannot be used in enclosures 17 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE F ~ AC R HIGH-VOLTAGE a should be provi with 4.1 and 5.4 of ANSIPEEE C37.04-1979, where the sustained load current does not exontinuous current, the altitude less, and above sea level is 3300 f the ambient temperature ed 4OoC. The rated continuous current is based on the maximum permissible total temperature limitations of the various parts of the circuit breaker when it is carrying rated current at an ambient temperature of 4OOC. Th otal temperature of these parts under service conditions depends both on the actual load current and the actual ambient temperature. It is, therefore, possible to operate at a current higher than rated continuous current when the ambient temperature is less than 4OoC, provided that the allowable total temperature limit is not exceeded. Similarly, when the ambien than 4OoC, the current than rated continuous c temperatures within all0wable limits. on at a current higher than rated C us current will usually cause the allowable temperature limitations to be exceeded and should be avoided except in these instances: peribds, such as in the starting (1) For of motors nchronous condensers, or when energizing cold loads. Generally, the time duration of this type of current increase is short enough that it does not raise temperatures significantly. (2) When operating at an ambient temperature below 4OoC, as covered in 4.4.3.2. (3) For short periods following operation at a current less than that permitted by the existing ambient temperature, as covered in 4.4.3.3. The method of calculating allowable current at an ambient temperature above 4OoC is given in 4.4.3.2. For some high ambient temperature conditions, it may not be practical to reduce current sufficiently to keep the total temperatures within their allowable limits. Forced ventilation will help in many cases. Temperature limits of associated equipment such as cables and current transformers must be considered. Effect of solar radiation must also be considered. (See ANSI/IEEE C37.241971, Guide for Evaluating the Effect of Solar Radiation on Outdoor Metal-Clad Switchgear.) Where ambient temperature is be minimum limit of -30°C, special may be required, and additional heater capacity bility Based on The continuous where Omax = allowable h NOTE: The temperature rise of a current-carrying part is proportional to ah exponential value of the current flowing through it. although the exponent may have depending on breaker design and componen of 1/1.6 to 1/2,0. that is suitable for this application guide. follows : Circuit Breaker Component joints, etc Bushings Curkent transfor Number C37.04-1979 C76.1-1976 18 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. Section ANSI/IEEE C37.010-1979 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS The values of temperature limitations specified in these various standards are summarized in Table 1.In order that none of these limitations be exceeded when the load current is adjusted t o the value permitted by the actual ambient temperature, the values for Om= and 8, should be determined as follows: (1) If the actual ambient is less than 4OoC, the component with the highest specified valyes of allowable temperature limitations should be used for determining Omax and 8,. (2) If the actual ambient is greater than 4OoC, the component with the lowest specified values of allowable temperature limitations should be used for determining Om, and Or. The use of these values in the calculation will result in an allowable continuous current which will not cause the temperature of any part of the circuit breaker to exceed the permissible limits. NOTE: Although circuit breakers are designed to carry rated current continuously while exposed t o an ambient temperature of 4OoC, most circuit breakers in service are subjected t o a much less severe ambient temperature condition which varies with time of day and season of year. The average outdoor air temperature during any 24 h period is usually 5 to 10°C lower than the maximum, and the maximum is usually less than 4OoC. This is one important reason for the long life which circuit breakers historically have demonstrated. Continuous operation at rated current and at an ambient temperature of 4OoC likely would result in a life somewhat shorter than that usually experienced. The user is cautioned that this guide is intended to cover situations where the circuit breaker is used at its total temperature limitations infrequently (a few occasions in the expected lifetime), for relatively short periods of time (perhaps a few days). The manufacturer should be consulted if operation at maximum allowable temperature is required at frequent intervals or over extended periods of time. ay not be necessary to include the extreme values of highest and lowest allowable temperature limitations, as listed in Table 1,in Table 1 Summary of Temperature Limitations for Circuit Breaker Components Component Description Temperature Rise, OC Limit of Total Temperature, OC 0, 0max 10 50 40 80 onnected to 85OC 45 85 Hottest spot temperature of parts where they contact oil; silver (or equal) contacts in oil; silver (or equal) conducting joints in oil 50 90 Silver (or "equal) contacts in air; silver (or equal) conducting joints in air; hottest spot of bushing conductor o r of bushing metal parts in contact with Class A insulation or with oil; hottest spot winding t rature 5 5 ' ~rise of current transformers. 65 105 7 External surfaces not accessible t o an operator in the normal course of his duties 70 110 8 Hottest spot winding temperature of 80°C dry-type current transformers 110 150 1 Circuit breaker parts handled by the operator in the normal course of his duties 2 Copper contacts, copper-to-copper conducting joints, external surfaces accessible to the operator in the normal course of his duties, external terminal connected t o bushing 3 4 insulated cable 5 19 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE Table 2 *For limiting current, use lowest 0, and Omax. ?For limiting current, use highest Or and Omax. estimated from Table 2 or may be calculated directly from the lormula. this determination. The lowest value is for circuit breaker parts handled by the operator in the normal course of his duties, and the highest value generally is for external surfaces of a circuit breaker, not accessible to an operator in the normal course of his duties. In many cases, overheating of these parts beyond the specified allowable limitations will not impair circuit breaker performance or expected life. If these parts are neglected, a higher value of permissible continuous load current can be obtained from the calculation. In most cases, this higher value of current may safely be used. However, in some circuit breaker designs there may be gaskets or other components located near such inaccessible external surfaces which would be damaged if overheated. The use of 80°C rise dry-type current transformers would place a further limit on the allowable current for operation at an ambient of less than 40°C. Evaluation of the breaker design should be made to determine whether or not these extreme values of temperature limitation should be included. In case of doubt, the manufacturer should be consulted. Table 2 lists the calculated values of l a / I r for each specified temperature limit for the various componen e circuit breaker over a range of ent temperatures. The allowable current in any given situation can be EXAMPLE 1: Consider an oil circuit breaker with copper-to-copper contacts, American National Standard bushings, and 55OC rise current transformers. When operating at an ambient temperature of 2 current could be increased by a factor correspo with the highest temperature e components according to Table 2, the factor of increase is 1.12 times rated curre the current must be reduced by a factor which corresponds t o the component with the lowest temperature 20 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS current can be increased by a factor of 1.12, corresponding to the temperature rise limitations of 65OC of the silver-to-silver contacts and the current transformers. If the ambient temperature were 5OoC, the reduction factor would be 0.87 corresponding to the temperature rise limitation of 45OC of the connected cable. 4.4.3.3.I De termination of Allowable Time for I, by Use of Fig 1 . One method for determining the allowable duration of current Is is shown in Fig 1. The values of time obtained from the figure are given in “time constant units.” The actual time is determined by multiplying the time constant units by the proper thermal time constant listed in Table 3. Current transformers that form part of a circuit breaker assembly or that are normally considered a part of the breaker installation will usually have heating characteristics similar to those of the circuit breaker. The continuous current permitted by the formula will not cause overheating of a current transformer connected to a ratio tap corresponding to rated current of the circuit breaker. However, if a lower ratio tap is used, the expected secondary current must be evaluated in terms of the continuous thermal rating factor of the current transformer. The effect of the secondary current on apparatus connected to the current transformer terminals should also be considered. 4.4.3.3 Short-Time Load Current Capability. When a circuit breaker has been operating at a current level below its allowable continuous load current I,, it is possible to increase the load current for a short time to a value greater than the allowable current without exceeding the permissible temperature limitations. The length of time that the short-time load current Is can be carried depends on these factors: (1) The magnitude of current Is to be carried (2) The magnitude of initial current I i carried prior to application of Is (3) The thermal-time characteristics of the circuit breaker The time duration of the short-time current may be calculated directly or may be obtained by simple use of Fig 1as described below. The time duration of the current Is determined in this manner will not cause the total temperature limits of the circuit breaker to be exceeded, provided that these requirements are fulfilled : (1) The circuit breaker, and in particular the main contacts, shall have been well maintained and in essentially new condition (2) The value used for the current Ii is the maximum current carried by the breaker during the 4 h period immediately preceding the application of current Is (3) At the end of the time period, the EXAMPLE: A 1200 A oil circuit breaker with silverto-silver contacts and American National Standard bushings is operating at 1000 A (Zi = 1000 A). It is desired to increase the current to 1600 A ( I , = 1600 A) for a short time. The maximum ambient temperature expected is 25’C. For how long a time can the circuit breaker carry this current? The allowable continuous current is determined according to 4.4.3.2. Since the ambient is less than 4OoC, the highest temperature rise limitation of 65’C is used, the temperature rise limit of the bushing. From Table 2, the ratio of 1.12 is determined for the ambient temperature of 25’C. Therefore, Z, = 1.12 x 1200 = 1344 A. The ratio (Ii/Is)is (1000/1600) = 0.625. The corresponding value ti from Fig 1 is 0.58 time constant units. The ratio (Za/Zs) is (1344/1600) = 0.84. The corresponding value ta from Fig 1is 1.31 time constant units. The period of time for which the excess current can be carried is t, ti = 1.31 0.58 = 0.73 time constant units. The actual time is obtained by multiplying this value by the thermal time constant of 0.5 h taken from Table 3 (0.73 x 0.5 h ) = 0.365 h or about 22 min. After this time, the current must be reduced to no more than 1344 A in order to prevent overheating of the bushings. - - 4.4.3.3.2 Determination of Allowable Time for Is by Direct Calculation. The allowable duration of current Is may be calculated directly. While the chart method is quicker and simpler than hand calculation of these equations, the increasing availability of digital computers makes it desirable to provide the details of these calculations. These equations may be easily written in a computer language such as Fortran so that many sets of conditions may be analyzed quickly. The program also should then be immediately available for use at a Table 3 Typical Thermal Time Constants Circuit Breaker Listed in ANSI C37.06-1979 Typical Time Constant r, hours Table 1 current Is is reduced to a value which is no Table 2 Table 3 Table 4 Table 5 greater than the cunent l a (4) The value of current I, is limited to a maximum value of two times rated current I,. 21 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE APPLICATION GUIDE FOR AC HIGH-VOLTAGE C37.010-1979 9 - 8 x x 9 ? 0 a9 0 h .*E .f= Y E ga 3 ? k 0 .-E 0 ?f 0 '9 0 '9 z s- 0 0 L c c - 0 0 0 22 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS future time. These are the equations used to calculate the time duration ts for a short-time load current Is : Y = (emax 4.5 Rated Dielectric Strength 4.5.1 Low-Frequency Withstand Voltage. Circuit breakers are tested to withstand, for 1 min at normal frequency, a voltage that exceeds the rated maximum voltage. This test provides a margin of safety for normal deterioration, for minor contamination, and for normal voltage surges encountered in service. Test values are listed in rating tables in ANSI C37.06-1979. These apply to new circuit breakers tested at the factory. See 1.3 of ANSI/IEEE C37.09-1979 for tests after delivery. In some types of circuit breakers, dielectric withstand voltage may be reduced below a safe value by loss of air or gas pressure caused by a stuck valve or other malfunctioning device. Automatic isolation of the breaker should be considered in such cases. 4.5.2 Impulse Withstand Voltage. The basic impulse insulation levels (BIL) of circuit breakers are specified in rating tables in ANSI C37.06-1979 for various breaker ratings. In applying circuit breakers it is necessary to make certain that the insulation levels of all facilities at a terminal are properly coordinated. Since this is a matter of system insulation coordination, it is outside the scope of an application guide for circuit breakers. The purpose of impulse voltage withstand tests is to demonstrate that the insulation level of the circuit breaker, when coordinated with suitable protective devices, will protect against dielectric failure or flashover under lightning surge or equivalent conditions. When surge arresters are installed on the bus or on transformers and not on each circuit breaker, the surge voltage at the breaker can exceed that at the arresters, the amount of the excess depending upon the steepness of the wave front and the distance from the circuit breaker to the surge arresters. When the circuit breaker is in the open position, an incoming surge voltage may be doubled by reflection at the open terminals. Selection of too low an insulation level for circuit breakers, if not individually protected by arresters, may result in an excessive number of operations of local or remote breakers in clearing faults caused by external flashovers. - 40°C) (Ii/Ir)1.8 allowable hottest spot total temperature from Table 1, in degrees Celsius actual ambient expected (between -30°C and 6OoC), in degrees Celsius initial current carried prior to application of I s , in amperes (the maximum current carried by the breaker during the 4 h period immediately preceding the application of current I s ) short-time load current, in amperes rated current, in amperes thermal time constant of the circuit breaker from Table 3, in hours permissible time for carrying current Is at ambient 19, after initial current Ii time is in same units of hours as r. NOTE: These equations are derived in the following manner : Let O s = total temperature, in degrees Celsius, that would be reached if current I, were applied continuously at ambient ea O i = total temperature, in degrees Celsius, due to continuous current Ii at ambient ea total temperature, in degrees Celsius, at some time t after current is raised from Zi to I, et= Then et = (es - ei) (1 - E - ~ / T ) + ei Let et = Omax ;solve for t . Then where ei = (ema - 4OoC) ( I ~ / I +, ea ~ and e, = (e,,, - ANSI/IEEE C37.010-1979 4OoC) ( Z , / Z ~ ) ~ . + ~ ea. For the special case where the initial current is zero, the equations in this form are useful. By substitution and further manipulation, the equations given above in terms of Y are obtained; these are convenient to use in the more usual case where the initial current is not zero. 4.6 Standard Operating Duty. Power circuit breakers are rated for current interrupting ability on the basis of a standard operating duty. (See 5.6 of ANSIIIEEE C37.041979.) 23 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE APPLICATION GUIDE C37.010-1979 If the actual duty cycle application is different from the standard operating duty, refer to 5.10.2.6 of ANSI/IEEE C37.04-1979, and to Fig 1 of ANSI C37.06-1979,for rating factors for reclosing service and for examples illustrating the use of the rating factors. FOR AC HIGH-VOLTAGE instability. For low values of current, these considerations are less important. The rated interrupting times of specific circuit breaker ratings are given in the tables of ANSI C37.06-1979. Fast interrupting speeds may be significant where system stability is critical or where line conductor damage is an important consideration. Fig 2 shows the sequence of events in the course of a circuit interruption and reclosure. 4.7 Intempting Time. The rated interrupting time of a circuit breaker is the time between trip circuit energization and power arc interruption on an opening operation, and is used to classify breakers of different speeds. The rated interrupting time adjusted by factors included in 5.7 of ANSI/IEEE C37.041979 indicates the length of time to circuit interruption of power current after trip initiation. Note that the rated interrupting time may be exceeded at low values of current and for close-open operations; also, the time for interruption of resistor current for interrupters equipped with resistors may exceed the rated interrupting time. The increase in interrupting time on close-open operation may be important from the standpoint of line damage or possible 4.8 Permissible Tripping Delay. The rated per- missible tripping delay Y constitutes a thermal limit which should not be exceeded for a close, carry, and interrupt sequence at K times rated short-circuit current. The permissible tripping delay T , in seconds, may be determined for currents lower than K times rated short-circuit current by use of the formulas given in 5.8 of ANSI/IEEE C37.04-1979. The rigorous method is generally not required for application unless the approximate method of the section produces a result close to the tripping delayaproposed for use. Fig 2 Operating Time EXTINCTION OF ARC ON PRIMARY CONTACTS INlTlATION OF SHORT -CIRCUIT RESISTOR CIRCUIT COMPLETED ON RECLOSURE I I I I PARTING OF SECONDARY ARCING CONTACTS ENERGIZATION OF TRIP CIRCUIT EXTINCTION OF ARC SHUNTING RESISTOR CURRENT PARTING OF PRIMARY ARCING CONTACTS t I f f f PRIMARY ARCING CONTACTS M A K E T I _ + (*I RECLOSING TIME IS T H E TIME INTERVAL BETWEEN ENERGIZATION OF THE TRIP CIRCUIT AND MAKING OF THE PRIMARY ARCING CONTACTS. WHERE LOW OHMIC RESISTORS ARE USED, MAKING OF T H E RESISTOR CONTACT ON RECLOSURE MAY BE MORE SIGNIFICANT. 24 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS 1 K (Rated Short-circuit Current) T =Y L opened. Synchronous motors and static capacitors included in the load will tend to prolong the period of arcing. On tie lines, dead time on the circuit is the time interval between interruption of current by the last breaker t o clear and making of the contacts on the first breaker to reclose. A dead time on the circuit of at least 8 cycles is normally required at 115-138 kV for breakers without resistors across the interrupters. The required dead time is greater for higher voltages. Where resistors of low ohmic value are used across the interTpters, the necessary dead time may be affected by the current flowing through the resistors. Investigations in this area are being made. Fig 2 illustrates the reclosing time whieh is defined in ANSI C37.100-1972. Figure 1 of ANSI C37.06-1979 gives factors to be applied to the interrupting capabilities of circuit breakers for reclosing duty cycles other than the standard operating duty. Examples of the use of these factors are given below. 1 -1 1, where Y I,, = = aconstant the quotient E / X , in amperes. For the values of Y , see ANSI C37.06-1979 (1.1.3). EXAMPLE : Consider an outdoor circuit breaker having a rated short-circuit current of 22 000 A and a voltage range factor K of 1.65. Assume that I s is 20 000 A and Y is 2. Then the permissible tripping delay is: T = 2( 1.65x 22000 20 000 ) ANSI/IEEE C37.010-1979 = 6.6s. This limit applies to short-circuit current and does not apply to load current, motor starting current, or similar service. The aggregate tripping delay on all operations within any 30 min period must not exceed the time obtained from the above formula. 4.9 Reclosing Time. High-speed reclosing may be applied on radial lines to minimize the effect of line outages. In most cases, reclosing within l/2 s from incidence of a fault will prevent any adverse effect of the circuit outage on residential and commercial customers. In many cases, industrial customers can modify their equipment to eliminate most of the adverse effects of momentary outages if highspeed reclosing is employed. High-speed reclosing has been used successfully on tie lines where opening a circuit separates a portion of the system from the remainder. In this case, it is necessary to reclose before the rate of change or magnitude of the phase angle of voltages across the open circuit has reached a value beyond the capability of the circuit to restore synchronism following reclosure. In many applications on loop and grid systems, high-speed reclosing is used to avoid instability, to improve voltage conditions, and to minimize the effects of line outages. Several definitions of dead time for a circuit breaker are given in ANSI C37.100-1972.Before a circuit can be successfully reenergized, there must be sufficient dead time in the circuit Example 1. Determine the symmetrical interrupting capability of a circuit breaker when used on a duty cycle of 0 + Os + CO + 15s + CO + 60s + CO on a system operating at 23 kV. The breaker rated short-circuit current is 15 000 A at a rated maximum voltage of 38 kV on a standard duty cycle of CO + 15s + CO. (1) The symmetrical interrupting capability at 23 kV is 15 000 AX (38/23) = 24 800 A. (2) (From Fig 1 of ANSI C37.06-1979.) The calculating factor d, from Fig 1 for reducing the symmetrical interrupting capability is 4.0 at 24 800 A. (3) (From 5.10.2.6 of ANSI/IEEE C37.041979.) Total reduction factor D is 3 X 4.0 = 12.0 D = 4(4 + o = 12 - 2) + 4 ( 1 515- 0 ) + 4 (15-15) 15 The reclosing capability factor is thus R = 100 - 12.00 = 88.0 percent. (4) The symmetrical interrupting capability for this duty cycle at 23 kV is 24 800 A X 0.88 = 21 800 A. (5) This circuit breaker may be used on this duty cycle at 23 kV on any circuit where the calculated system short-circuit current does not exceed 21 800 A after correction for X / R , if necessary. breaker for the arc path at the fault to become deionized. On a radial line where the load includes a large motor component, arcing may be sustained after the breaker at the source is 25 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE APPLICATION GUIDE FOR AC HIGH-VOLTAGE C37.010-1979 0 I- 00 o z [r 0 & z 90 Duty Cycles Shown Graphically Example 2. Determine the symmetrical interrupting capability of a circuit breaker when used on a duty cycle 0 + 0 s + CO + 5 s + C O on a system operating at 28 kV. The breaker rated short circuit is 22 000 A at a rated maximum voltage of 38 kV on a standard duty cycle of C O + 15 s + CO. (1) The symmetrical interrupting capability at 28 kV is 22 000 A X (38/28)= 29 900 A. (2) (From Fig 1 of ANSI C37.06-1979.)The calculating factor dl from the reclosing capability curve is 4.9 at 29 900. (3) (From 5.10.2.6 of ANSI/IEEE C37.041979.) The total reduction factor using the formula for this duty cycle where (5) This breaker may be used on this duty cycle at 28 kV on any circuit where the calculated system short-circuit current does not exceed 26000 A, after corr necessary. Examples of other reclo some reclosing duty cyc ically in Fig 3. 4.10 Short-Circuit Rating. In the application of circuit breakers, it is necessary that none of the short-circuit current capabilities of a circuit breaker be exceeded. These capabilities are derived from rated short-circuit current and are described in 5.10 of ANSI/IEEE C37.04-1979. dl = 4.9 n = 3 tl = 0 tz = 5 +4.9 0 5 - 5 1 D = 4.9 (3 - 2)+ 4.9 (15-0) 15 15 times the rated max metrical interrupting c . = 13.1 U " (4) The symmetrical interrupting capability = 29 900 A X 0.869 X 26 000 A at 28 kV and 1 OpeEating Voltage 1 except that, f required symmetrical interrupting capability is the above duty cycle. 26 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS be taken to protect breakers against opening where normal current zeros are not obtained. The precaution includes: 15 percent higher but in no case greater than K times the rated short-circuit current. EXAMPLE: Consider an indoor oilless circuit breaker having a rated short-circuit current of 37 000 A at the rated maximum voltage of 15 kV and K=1.30. The symmetrical interrupting capability at an operating voltage of 13.2 kV is 37000 X ANSI/IEEE C37.010-1979 (1) Extended relay times (2) Special X/R ratios (3) Circuit breaker location to avoid this objectionable degree of asymmetry (:::;) - =42050A. For examples of calculations of system short-circuit currents for both 3-phase and line-to-ground faults, see 5.3 and 5.4. 4.10.3 Service Capability. Refer to 5.19.3.3 of ANSI/IEEE C37.04-1979 for the service capability of the breaker and for the specified breaker condition following certain performances. The required capabilities of the circuit breaker should not be exceeded, even though only one interrupting operation may be imposed. 4.11 Transient Recovery Voltage Rate. See ANSI/IEEE C37.011-1979, American National Standard, Application Guide for Transient Recovery Voltage for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis. 4.12 Load Current Switching Capability and Life (Repetitive Operation). Careful attention must be given to ANSI C37.06-1979. Motor starting duty may require closing the circuit against inrush currents many times greater than the running current. This will not be limiting on a circuit breaker having a continuous current rating at least equal to the maximum running current of the motor. [See 5.12(3) of ANSI/IEEE C37.04-1979.1 Special circuit breakers may be required for applications involving highly repetitive operations such as arc furnace switching and plugging, jogging, or reversing of motors. 4.13 Capacitance Current Switching. See ANSI/IEEE C37.012-1979, American National Standard Application Guide for Capacitance Current Switching for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis. At an operating voltage of 11.5 kV which is less than 1/K times rated maximum voltage, the symmetrical interrupting capability is limited to 37 000 K = 37 000 x (1.30) = 48 000 A. 4.10.2 Asymmetrical Requirements. A circuit breaker having adequate symmetrical intermpting capability will have adequate capability to meet all of the related short-circuit requirements unless there is a significant contribution from motor load or unless the XIR ratio is greater than approximately 15. This will result in a slower decrement rate for the asymmetrical current than that incorporated in the rating structure. (See Fig 2 of ANSI/IEEE C37.04 1979.) If the actual opening time of the circuit breaker is less than the assumed value (1.0 cycles for a 2cycle breaker, 1.5 cycles for a 3-cycle breaker, 2.5 cycles for a 5cycle breaker, and 3.5 cycles for an 8-cycle breaker), the breaker is required to have a symmetrical interrupting capability corresponding to the actual minimum contact parting time in accordance with Fig 2 of ANSI/IEEE C37.04-1979. Therefore, it is not necessary to allow a margin in application for the possibility of breaker opening faster than normally expected. Note that any combination of symmetrical and directcurrent components is permissible within the limitations covered in 5.10.2.2 of ANSI/IEEE C37.04-1979. If the actual relay time is less than 0.5 cycle, this fact should be taken into consideration when calculating required asymmetrical capability. Refer to Note 4 of 5.4.1 for the treatment of the motor contribution where it affects the initial asymmetrical current. Methods of allowing for slow decrement of the asymmetrical current are discussed in 5.3 and the sections that follow it. In some applications, particularly on generator buses, a condition may occw where over 100 percent asymmetry is obtained [ 8 ] . Where this condition exists, precautions should 4.14 Line Closing (Line Closing SwitchingSurge Factor). When a circuit breaker is closed to energize an overhead transmission line, it produces on the power system a transient overvoltage, the crest of which is called the line closing switching surge maximum voltage. Circuit breakers which have been specifically designed to control such voltage to be less than a specified limit are assigned a rating called the rated 27 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE line closing switching surge factor, This rating designates that the circuit breaker is capable of controling line closing switching surge voltages, so that there is a probability of at least 98 percent of not exceeding the rated line closing switching surge factor, when switching the standard reference transmission line from the standard reference power source. Establishment of the rated line closing switching surge factor is based on closing of the circuit breaker governed by random time energization of the device which initiates closing of all three phases. Random closing of the circuit breaker will produce line closing switching surge maximum voltages which vary in, magnitude according to the instantaneoug value of the source voltage, the parameters of the connected system, and t o the time differences between completion of the circuit path in each phase. These variations will be governed by the laws of probability so that the highest and the lowest possible overvoltages will occur very infrequently. In recognition of this and of the economy associated with not designing for the worst case, the rated line closching surge factor is based o at the circuit breaker wil ing switching surge factor equal to, or less than, the rated factor 98 percent or more of the times it is closed, and never more than 1.2 times the rated factor. 4.14.1 Statis lysis o f the Number of Allowable Occ in Excess of the Rated Value. Any device with which there is a mathematically constant probability of 2 percent of the occurrence of an event will usually different test results th a series of 50 tests. In resent case, if the event is defined as the line closin'g switching surge factor exceeding the rated factor, and a large number of test series consisting of 50 tests each were conducted, in 36.4 percent of the repeated test series, of 50 tests each, the rated factor would not be exceeded; in 37.1 factor of a circuit breaker design will be based on a great number of tests made by the manufacturer on a simulated syst by a user to perfor will be done in acco ANSI/IEEE C31.09-1979, cent of the tests to have a li surge factor in excess of the rated factor. The probability of obtainin no more than one exce bility (26.5 perc tests each will simulated tests made with a m bility of the circuit within known statis Alpha = of exceeding rated factor for unacceptable circuit breaker 5 percent = ceptance the series the rated value would be once; in 18.6 percent, twice; in 6.1 times; in 1.5 percent, 4 times; and in 0.3 percent, 5 times (from the binomial formula). Thus a circuit breaker with a perned and constant 2 percent probeeding the rated switching surge factor would do so four or more times in about 2 percent of repeated 'te eries of 50 tests each. It is expected that the rated switching surge 28 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS 4.14.2 Type of Power System to Which the ANSI/IEEE C37.010-1979 the duties specified in 4.15.9 of ANSI/IEEE C37.091979. (2) The requirements of this standard cover the great majority of applications of circuit breakers intended for switching during out-of-phase conditions. Several circumstances would have to be combined to produce a severity in excess of those covered by the tests of this standard and, as switching during out-of-phase conditions is rare, it would be uneconomic to design circuit breakers for the most extreme conditions. Where frequent out-of-phaseswitching operations are anticipated, or where for other reasons out-of-phase switching is a matter of importance, the user should consider actual system recovery voltages. A special circuit breaker, or one rated at a higher voltage, may sometimes be required. As an alternative solution, the severity of out-of-phase switching duty is reduced in several systems by using relays with coordinated impedance-sensitive elements to control the tripping instant, so that interruption will occur either substantially after or substantially before the instant the phase angle is 180'. Rated Line Closivg Switching Surge Factor Applies. The rated line closing switching surge factor applies to a power system where the circuit breaker connects an overhead transmission line directly to a power source. The factor applies specifically to a power system with characteristics of the standard reference power system as described in 4.14.1 of ANSI/IEEE C37.09-1979 and also to those actual power systems whose characteristics are not greatly different from those of the standard reference power system. The transmission line is open at the receiving end and is not konnected to such terminal apparatus as a power transformer although it may be connected to an open circuit breaker or disconnect switch. The system does not include shunt reactors, potential transformers, series capacitors, shunt capacitors, lightning arresters, or any similar apparatus unless specified in Table 8 of ANSI C37.06-1979. Applications where a circuit breaker is used on the low-voltage side of a transformer to energize a line on the high-voltage side of the transformer are being studied for possible future inclusion in this standard. It is anticipated that any actual power system which deviates too greatly from the standard reference power system may require that a simulated study be made of it in order to determine the actual line closing switching surge factor to be expected. 4.16 Shunt Reactor Current Switching. Circuit breakers may be applied to switch shunt reactors. Because of the high transient recovery voltage rate produced by switching shunt reactors, the arcing time of some circuit breakers, under that condition, may be significantly longer than it would be for other types of switching duty. This longer arcing time may require more frequent maintenance. (See 5.16 of ANSI/IEEE C37.04-1979.) 4.17 Excitation Current Switching. Circuit breakers used for switching exciting current including energizing and deenergizing of feeder regulators and transformers may require special consideration because of switching frequency or severity. 4.18 Mechanical Life. Circuit breakers are d e signed to operate satisfactorily for the number of operations specified in Table 6 of ANSI C37.06-1979. 4.15 Conditions of Use with Respect to the Out-of-Phase Switching Current Rating. The conditions of use with respect to the out-ofphase switching current rating are : (1) Opening and closing operations carried out in conformity with the instructions given by the manufacturer for the operation and proper use of the circuit breaker and its auxiliary equipment; closing operations should be limited to a maximum out-of-phase ingle of 90' whenever possible [see Note (2) below] (2) Grounding condition of the neutral of the power system corresponding to that for which the circuit breaker has been tested (3) Frequency within f 2 0 percent of the rated frequency of the circuit breaker (4) Absence of a fault on either side of the circuit breaker 4.19 Rated Control Voltage. The successful performance of circuit breakers depends upon maintenance of control voltage within the standard limits as shown in Table 8 of ANSI C37.06-1979. The voltage at the control terminals of the circuit breaker should approximate the rated control voltage under loaded conditions and must not be less than the minimum specified in Table 8 of ANSI C37.06-1979, even under minimum expected battery voltage conditions. Batteries, battery chargers, control transformers, etc, should be selected considering this limit and taking into account the line drop encountered in the control buses, leads, relay series coils, the condition and charge of the NOTES: (1) All circuit breakers having an assigned outof-phase switching current rating are able to perform 29 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATLON GUIDE FOR AC HIGH-VOL battery, and the volt-ampere burden on the control transformers. The possibility of simultaneous closing and tripping of two or more power circuit breakers should be considered in selecting the control power supply. Control current free operation may be quite high. The are especially critical where lower control voltages V - (24-48 . subjected b t h e following types of faults: Where emergency service, communication loads, indicating lights, r similar power requirements must be supplied from a control battery, these represent a sustained load requirement for the battery and charger and should be include fixing the size of ment, 4.20 Fluid Operating Pressure. Circuit breakers operated by fluid pressure are designed to operate over a pressure range prescribed by the manufacturer. Limit switches to control compressor operation, to indicate low pressure, and to prevent circuit breaker operation below minimum pressure are normally provided. A suitable power sou r compressor operation is required. euit Considerations circuit breakers h*ave 1 urrents. One of the ts of circuit breaker application is the ' determination of the maximum short-circuit duty imposed on the breaker. Different methods of determining system short-circuit currents have been published. In general, more complex calculations give improved accuracy. The application engineer should select the method in acco accuracy. Ordinarily, the meth 5.3.2will be conservative. 5.1.1 Sh-ort-circuit Tests. The most accurate ation of short-circuit current may be trolled and instrus. Sometimes such ade to test new equipment or system arrangements, but are not a means of determining circuit breakers on a p most cases, selection precedes completion of new facil 5.1.2 Types and Circuits. 30 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS 1 z z! kiii Va f BREAKER WITH I-CYCLE CONTACT PARTINGTIME I :‘IC 2 \ BREAKER WITH 1-1/2 CYCLE CONTACT PARTING TIME )t PARTING TIME Y CI W > ?!!! r I v)c * I I 1.1 :* IME QlL :k 1.0 0 0 2wcc5 a w CL I /2 I 2 3 4 CIRCUIT BREAKER CONTACT PARTING TIME-CYCLES ( SUM OF 1/2 CYCLE TRIPPING DELAY P U S THE OPENING TIME OF T H E CIRCUIT BREAKER ) (*The circuit breaker required asymmetrical interrupting capability for any time up to the permissible tripping delay. See 4.7.) Fig 4 Power Circuit Breaker Design Requirements Circuit breakers are designed to interrupt satisfactorily with the asymmetrical and symmetrical current relationships shown in Fig 4. When a breaker interrupts a short-circuit current, the critical current value is that existing at the time of primary arcing contact parting. The curve of Fig 4 is designed t o specify the required asymmetrical capability of any circuit breaker based on %-cycleminimum relay time plus the circuit breaker opening time. Once this asymmetrical capability is so established (see 5.10.2.2 of ANSI/IEEE C37.04-1979),it remains fixed for any contact parting time within the permissible tripping delay period. (See 5.8 of ANSI/IEEE C37.04-1979.For example, if a circuit breaker has an opening time of 1/2 cycle, the minimum contact parting time is 2 cycles. From Fig 4, the circuit breaker has an asymmetrical current capability of 1.2 at 2 cycles, where the required symmetrical capability is 1.0. The more exact type of calculation (see 5.3.2) evaluates the decay in the ac and the dc components of the short-circuit current. When the fault is close, electrically, to a major element of generation, the ac decay will be appreciable during the first few cycles. The ac decay may not be significant in system locations that are electrically remote from generation. This may be so even in auxiliary systems fed directly from the generator terminals, but through a relatively high impedance reactor or transformer. In cases where high X/R ratios are encountered and some tripping delay in excess of l/2 cycle is used, advantage may be taken of the system decay in either or both of the dc and ac components of short-circuit current. In locations where such advantage is taken of the decay in the ac and dc components and where the circuit breaker is applied at about 1/K times the rated maximum voltage, special care must be exercised to assure that the circuit breaker capability at l/2 cycle (closing and latching capability) is not exceeded. This is 1.6 times K times the rated short-circuit current. Also, in the presence of motor load, closing on a short-circuit may be critical, in 31 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE which case the critical current may be that of the first major current crest. Proper provision for this condition is assured by making a closing and latching duty calculation using the rotating machine reactances indicated in 5.4.1. In any case, neither the required symmetrical nor the required asymmetrical interrupting current capability of a circuit breaker should be exceeded at the time of primary arcing contact separation. be substituted for E / X in the descriptions which follow. 5.3.1 EfXSimplified Method. In many cases of short-circuit current calculations a simple E/X computation (E/X,) for 3-phase faults or 3E/(2X1 + X,) for single line-to-ground faults) will provide adequate accuracy for circuit breaker application. NOTE: See 5.4 for definitions of electrical quantities. The results of the E / X simplified procedure may be compared with 100 percent of the circuit breaker symmetrical interrupting capability where it is kno tem X/R ratio (Xl,lRl f or (2X1 +X0)/(2R1+R,) f ground faults is 15 or less. 5.2 §election of Applicable Circuit Breaker Ratings. With the short-circuit current duties at the circuit breaker location available (see 5.3), the most severe of these should be used in selecting the desired breaker rating from the tables of preferred ratings in ANSI (337.06-1979. The proper table for indoor or outdoor, oil or oilless breaker types should be chosen. One or more interrupting and continuous ampere ratings are available in most voltage classes. NOTE : For simplification, negative-sequence reactance X z is assumed equal to positive-sequence reactance X I . A similar assumption is made for resistance values Rz and R I . The E/X simplified procedure may be used without determining the system R if E/Xdoes not exceed 80 percent of the symmetrical interrupting capability of the breaker. If it is desired to use a breaker where the current determined in this case exceeds 80 percent of the breaker’s symmetrical interrupting capability, a more exact method of calculation such as that described in 5.3.2 should be used to check the adequacy of the circuit breaker. 5.3 Methods for Calculating System ShortCircuit Currents. Various methods and devices are in use for the calculation of short-circuit current. Rather rigorous methods involving step-by-step application of ac and dc decrements have been devised and used for faults at generating stations. These same methods are sometimes used for faults at other locations, but the application of the methods is more difficult and less satisfactory as the impedance networks became more complex. A simplified method is described in 5.3.1. This method requires only an E/X calculation up to certain limits which represent the degree of accuracy of the method. A more accurate method is described in 5.3.2. This method gives results approximating those obtained by more rigorous methods. In using it, it is necessary first to make an E/X current calculation. Then it is necessary to adjust the E/X current value for both the ac and the dc decay which depend upon the circuit conditions. This method also provides for the possibility of including both ac and dc decays where relay time delay in excess of the l/2 cycle minimum is utilized. This method should provide results having an accuracy commensurate with the usually available short-circuit characteristics of electrical equipment and systems. In those instances where it is desired to use impedances instead of reactances for determining short-circuit current magnitudes, E/Z may NOTE: In many cases, calculation will show the X/R ratio to be less that 15. In such cases, no further calculation is required since EIX can be used up to 100 percent of breaker rati The more exact procedure should also be used if a single line-to-ground fault supplied predominantly by generators, at generator voltage, exceeds 70 percent of the circuit breaker symmetrical interrupting capability for single line-to-ground fa EXAMPLE OF E / X SIMP (1) General: Consider the system shown in Fig 5. Faults on both sides of breaker A in Fig 5 and of all other circuit breakers should be considered, assuming in each case that the breaker in question is the last breaker to clear the fault. However, upon careful observation of the system involved it may be apparent that a fault on one side of the breaker gives a higher fault current than does a fault on the other side. This is the case for breaker A in the system shown in Fig 5. Therefore, currents have been calculated for a fault on only one side at positi ver, in case of doubt, fault currents for fau sides of the breaker should be calculated. line-to-ground faults on tie lines, the con the remote breaker 32 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS I 132 K V . (0.400 + 0.200 ) 26 KV (0.050+ 0.020) -y- a \ Total X I = / (0.050 + 0.020) + - 0.070 x 0.50 = o.06, 0.070 + 0.50 SYSTEM EQUIVALENT OPEN Base voltage = 132 kV Base current = 437 A The value of operating voltage corresponding to the highest typical operating voltage at the fault point is 134 kV or 1.015 per unit. Fig 5 System Illustrating Use of Simplified Method of Short-circuit Calculation X, 1.015 Isc = -X 437 0.061 = 7270 A. (3) Single Line-to-Ground Fault Calculations. Consider the system shown in Fig 7. :0050 TotalXo = x,:0020 (0.030 + 0.20) (0.20) = o.107 (0.030 + 0.20) + (0.20) Since Xo is greater than X I , the single line-to-ground fault need not be considered. (4) Selection of Breaker. A circuit breaker is t o be selected from the preferred rating schedules in ANSI C37.06-1979. The load current requirement is 600 A and the standard duty cycle is used. Consider a breaker which has a rated maximum voltage of 145 kV, a continuous current rating of 1200 A, a rated short-circuit current of 20 000 A at 145 kV, a maximum symmetrical interrupting capability of 20 000 A, and a voltage range factor K of 1.0. For a three-phase fault the symmetrical interrupting capability of the breaker is 20 000 A at the 134 kV operating voltage. Since the three-phase short-circuit current (7270 A) is less than 80 percent of the symmetrical interrupting capability (16 000 A), this breaker is adequate for the service required. There is a large margin for growth which may be important in selecting the breaker for a new application. SYSTEM OPEN Fig 6 Positive-Sequence Reactances for System Shown in Fig 5 x, =o033 8-- 5.3.2 E / X Method With Adjustment for AC and DC Decrements. For greater accuracy than that given by the E/X simplified method described in 5.3.1, the following procedure should be used. The technical basis for this procedure is presented in the Appendix. The procedure involves steps for applying factors to the E / X calculation. These factors depend upon the point on the system at which the short circuit occurs,and upon the system X / R ratio as seen from that point. For determination of the system X / R ratio it should be noted that there is no completely accurate way of combining two parallel circuits with different values of X / R into a single circuit with one value of X / R . The current from the several circuits will be the sum of several exponentially decaying terms, usually with different exponents, while that from a Fig 7 Zero-Sequence Reactance for System Shown in Fig 5 closed may sometimes produce a fault current through the breaker higher than that occurring when the remote breaker is open. In such a case, the single line-toground fault current will not exceed the 3-phase fault current except for a very unusual combination of impedances. (2) Three-phase Fault Calculations. In the system shown in Fig 6, per-unit reactances are indicated adjacent to generators, transformers, and lines. Base apparent power = 100 MVA. Nominal voltage is used as base a t all levels. 33 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE BREAKER ' 0 TIME I io I 1 I I/-- ' 1.2 13 14 13 14 I O I I 12 13 IO I I I2 13 FACTORS FOR E / X A M P E R E S NOTE: Consideration has been given to extending Che curves o 1.0, but since there are possibilities of nonconservative application in both symmetrical and asymmetrical current determinations in this area, the curves have not been extended. Further studies within these zones are recommended for future revisions of this application guide. Fig 8 Three-phase Fault Multiplying Factors Which Include Effects of AC and DC Decrement [See 5.3.2(1)] single circuit contains just one such term. Investigation has shown [2] that for practical proportions, the procedure of reducing the reactance to a single value with complete disregard for the resistances and reducing the resistance to a single value with complete disregard for the reactmces gives, in general, more accurate results than any other reasonably simple procedure (including the phasor representation used at system frequency). In addition, the error for practical cases is on the conservative side. For these reasons, this is the recommended procedure. In cases where an E/Z calculation is made it is acceptable to substitute Z/R for X I R provided that the R is obtained from a separate resistance disregarding The factors taken from Figs 8, 9, or 10 should be applied to the E / X calculation so that the ac and dc decrements are properly included in the final result. The following procedure is usually conservative : . The E / X current should be multiplied by a factor from times the generator per-unit sub- 34 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS 1.0 1.1 1.2 1.3 1.4 IO 1.1 1.2 1.3 1.0 1.1 1.2 1.3 MULTIPLYING FACTORS FOR E/X AMPERES Fig 9 Line-to-Ground Fault Multiplying Factors Which Include Effects of AC and DC Decrement [See 5.3.2(1)] transient reactance on a common system megavolt-ampere base It will be noted that the maximum correction factor obtained from Figs 8, 9, and 1 0 in most practical applications is approximately 1.25. This 1.25 factor forms the basis for establishing 80 percent of circuit breaker capability as a limit for application of the simplified method in 5.3.1 where XIR is unknown. In breaker applications, relays slower than one-half cycle are frequently used. In some cases, consideration could be given to utilize this relay time to reduce the fault current at contact parting time to avoid or postpone replacement of circuit breakers. Figs 8, 9, and 10 include curves for breakers of typical speeds for longer contact parting t i e s to aid in checking the adequacy of circuit breakers with contact parting times longer than the'normal minimum. The breakers must still meet the closing and latching duty. (2) The factors of Fig 1 0 include only the effects of dc decay. The E / X current should be multiplied by a factor from Fig 10 for a threephase or a line-to-ground fault if the shortcircuit current it fed predominantly from generators through: (a) Two or more transformations or external to the (b) A per-unit generator that is equal to or exceeds 1.5 times the generator per-unit subtransient reactance on a common system megavolt-ampere base The resulting product must not exceed the symmetrical interrupting capability of the circuit breaker being considered. 35 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE I30 I20 I IO IOC 9c 8C U \ x 7c 0 5 6C U 5c 4( 3c 2c IC C ~ 3 1.1 1.2 1.3 1.4 1.5 1 1.1 1.2 1.3 1.4 1.0 1.2 1.1 1.3 1.0 1.1 1.2 1.3 MULTIPLYING FACTORS FQR E / X AMPERES Fig 10 Three-phase and Line-to-Ground Fault Multiplying Factors Which Include Effects of DC Decrement Only [See 5.3.2( the highest t is 46.8 kV EXAMPLE OF E / X METHOD WITH ADJUSTMENT FOR AC AND DC DECREMENTS: (1) Gen nsider the system shown in Fig 11. Since it arent that faults on the line side of oduce higher fault current through breakers A an the breaker than does a fault on the bus side, currents been calculated on only one side of each breaker. se of doubt, fault currents for faults on both sides of the breaker should be calcualted. ulation of Breaker A wn in Fig 12, per-unit nt t o generators, transformers, and lines. Base apparent power = 100 MVA. Nominal voltage is used as base at all levels. (0.150 + 0 . 0 7 0 ) - (0.150 + 0.070 TotalR, = (0.020 + 0.120) + 0.020 + 0.120) 25 (3) Single Line-toBreaker A (Case 1). Fig 13. Total X o = (0.070) 10.070 + (0.030 + 0.300) = o.0578 0.030 + 0.300) 0143 = 0.0856 55 = 16 720. (0.0017 i0.0015) (0.0005 + 0.0120) = o.oo255 (0.0017 + 0.0015 + 0.0005 + 0.0120) Accurate Calculation (C Base voltage = 46 kV Base current = 1255 A 36 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. for More ase fault: ANSI/IEEE C37.010-1979 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS SYSTEM EQUIVALENT A GENERATOR 46 K V +4 345KV Fig 11 System Illustrating Use of the E / X Method with Adjustment for AC and DC Decrements X i = 0.070 R , = O 0005 Fig 12 Positive-Sequence Impedance for System Shown in Fig 11 (Breaker A) R o = 0 03 Fig 13 Zero-Sequence Impedance for System Shown in Fig 11 (Breaker A) From Fig 9, the single line-to-ground short-circuit current should be multiplied by 1.13 t o assure conservative breaker application. The current to be compared with the breaker symmetrical interrupting capability for single line-to-ground faults is 1 6 720 1.13 = 1 8 890 A. (5) Selection of Breaker (Case 1). A circuit breaker is t o be selected from the preferred rating schedules of ANSI C37.06-1979. The load current requirement is 700A and the standard duty cycle is used. Consider an outdoor oil circuit breaker with a rated maximum voltage of 48.3 kV, a continuous current rating of 1200 A, a rated short-circuit current of 17 000 A at 48.3 kV, a voltage range factor K of 1.21, Consider a 5-cycle breaker with a contact parting time of 3 cycles and a normal duty cycle. Since the breaker is on the bulk system, is only one transformation away from generation, and the X/R ratio is greater than 15, the breaker duty should be multiplied by a factor from Fig 8 t o assure conservative breaker application. This factor is 1.05. The current t o be compared with the breaker symmetrical interrupting capability is 1 4 910 x 1.05 = 15 660 A. For a single line-to-ground fault: 2x1 + X , - 2 X 0.0856 + 0.0518 = 35.1 2 X 0.00255 + 0.00143 2R1 + Ro 37 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR XC HIGH-VOLTAGE I X , = O 070 R,(,,)=O 0015 X I = 0 020 __ R I (ac) = O O l L O x , = 0 I20 R, = 0 0005 , x,=0.200 IR(oc) = O . O O y 1 Fig 14 Positive-Sequence Impedance for System Shown in Fig 11 (Breaker B) Xo = O 030 = 0 300 Ro : O 0 3 0 X, X, R, = 0070 =00015 II oj D R, = O 0 3 0 !--i Fig 15 Zero-Sequence Impedance for System Shown in Fig 11 (Breaker B) NOTE: X may be either X I or 2X1 + X o and R may be either R I o r 2R1 + Ro as shown in 5.4. (6) Three-phase Fault Calculation of Breaker B (Case 2). Consider the system shown in Fig 14. (b.150 + 0.010 + = (0.160 - )' (0.020) + 0.200 = 0.219 + 0.070 + E)+ 2 (0.020) (0.0017 + 0.0015+ o.0120) (0.0005) 2 At Rated Fault The value of voltage corresponding t o the highest typical operating voltage at the fault point is 34 kV or 0.986 per unit. At X/R Adjusted Maximum Operating Voltage Voltage E/X Factor E/X 3-phase 1 4 9 1 0 1.05 single line-toground 1 6 7 2 0 1.13 15660 18890 I 17 000 17540 19550 20 170 = 0.0047 Base voltage = 34.5 kV Base current = 1670 A Symmetrical Interrupting Capability Calculated Short-Circuit Current i 0.0040 Is, = 0'986 -X 1670 = 7520 0.219 A (7) Single Line-to-Ground Fault Calculation of Breaker B (Case ~ 2 ) .Consider the system shown in Fig 15. 1 38 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS (0.070 + x, = (0.070 '9)+ X I is the positivesequence reactance. (Equivalent to X as used in this standard.) X , is the negative-sequence reactance. (In the simplified method of fault calculation, X2 is assumed equal to X , .) X , is the zero-sequence reactance which may be obtained from design data, by calculation, or by test. X,!J' is the subtransient direct-axis reactance of a synchronous machine or locked-rotor reactance of an induction machine. This is always a positive-sequence reactance. Xi is the transient direct-axis reactance of a synchronous machine. This is always a positivesequence reactance. R is the corresponding lowest value of system resistance as viewed from the fault point (determined with X assumed 0) with the resistances of the system components determined as specified in 5.4.2.Instead of calculating R , an estimate of the system X / R ratio may be determined as shown in Table 5.R may be either R I or 2R, + R o depending on whether three-phase or single line-to-ground currents are being calculated. R is the positive-sequence resistance. R 2 is the negative-sequence resistance. Ro is the zero-sequence resistance which may be obtained from design data, by calculation, or by test. L is inductance in henrys. L = X / 2 n f (where f is system frequency). C is capacitance. 2 is impedance. I is current. I, is the calculated symmetrical short-circuit current. K is the voltage range factor (see 5.2 of ANSI/ IEEE C37.04-1979and ANSI C37.06-1979. Tdc is the direct-current time constant for the' circuit involved in the short circuit being calculated (see 5.1.3). S is the ratio as shown in Fig 4 and 5.10.2.2 of ANSI/lEEE C37.04-1979. (0.030) 0 300 + -)+2 0.200 = 0.226 (0.030) (0.0015+0 0,300) (0.0010) + 0.0040 = 0.0049 Ro = (0.0015+O o r ) + (0.0010) 0*986 = (0.219x 2) + 0.226 x 1670 = 7440 A ( 8 ) Factors Applicable to E/X Calculation for More Accurate Calculation (Case 2). For a three-phase fault: Xi - 0.219 R1 0.0047 = 49.0 Consider a 38 kV 5-cycle breaker with a minimum relay time of 1.5 cycles resulting in contact parting time of 4 cycles and standard duty cycle. Since the breaker is on the subtransmission system, is remote from generation by more than one transformation, and the X/R ratio is greater than 15, the breaker duty should be multiplied by a factor from Fig 1 0 for a conservative breaker application. This factor is 1.20. The current t o be compared with the breaker symmetrical interrupting capability is 1.20 X 7510 = 9012 A for a 3-phase fault. For a single line-to-ground fault: 2x1 + X o 2R1 + Ro -- (2X 0.219)+ 0.226 (2 X 0.00447)+ 0.0044 C37.010-1979 , = 47.8 From Fig 10, the single line-to-ground short-circuit current should also be multiplied by 1.19.The current t o be compared with the breaker symmetrical interrupting capability for single line-to-ground faults is 1.19 X 7440 = 8850 A. A breaker would be selected as described in (5). Selection of Breaker (Case 1). 5.4 Electrical Quantities Used. E is the lineto-neutral value corresponding to the highest typical operating voltage which occurs^at the circuit breaker location. X is the corresponding lowest value of system reactance (determined with R assumed 0) as viewed from the fault point with all rotating machines represented by the appropriate reactances as specified in 5.4.1. It may be either X , or 2 X , + X o according to whether three-phase of single line-to-ground currents are being calculated. 5.4.1 Rotating Machine Reactances. Basically, initial short-circuit current of rotating machines is determined by the machine subtransient reactances. For the simplified and more accurate methods of short-circuit current calculation, the following reactances are NOTE: Load reactances are neglected in this guide pince they are usually large with respect t o the series reactance and have little effect on the magnitude of deed : short-circuitcurrent. 39 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE Using Z = (,!?/Xi) E-tIT': as the expression for the exponential decay of induction motor symmetrical current t o a terminal short circuit, the reactance multiplying factor is E + ~ / T, where t is thz proper time after initiation of the short circuit and T is the motor short-circuit time constant. (Both should be in the same time units.) For example, using manufacturer's motor data for T ', the reactance multiplying factor for determining the interrupting duty may d using t equal to the circuit breaker minimum parting time. For a circuit breaker with a five-cycle rated interrupting time, t = 3 cycles (0.05 s). For determining the closing and latching duty, t = 0.5 cycles (0.00833 s) in the reactance multiplying factor calculations. Positive Sequence Reactances for Calculating 5 P e of Rotating Machine Interrupting Closing and Duty Latching Duty (Per Unit) (Per Unit) All turbogenerators, all hydro-generators with amortisseur windings, and all condensers (See Note 2) 1.0 Hydrclgenerators without amortisseur windings (See Note 2) 0.75Xd 0.75Xd All synchronous motors (See Notes 1, 4, and 5) 1.5 Xi 1.0 xi 1.5 X t 1.0 x: xl; 1.0 x: POWER SYSTEM EQUIVALENT Induction Motors (See Notes 3, 4, and 5) Above 1000 hp at 1800 r/min or less Above 250 hp at 3600 r/min From 50 t o lo00 hp at 3.0 X: 1800 r/min or less From 50 to 250 hp at 3600 r/min Neglect all 3-phase induction motors below 50 hp and all single-phase T"" 1.2 x; lo I I 3 INDUCTION WTOR LOAD INDIVIDUAL SIZES 50 TO 250 HP 2000 HP NOTES : (1) Xl of synchronous rotating machines is the rated-voltage (saturated) direct-axis subtransient reactance. (2) Xd of synchronous rotating machines is the rated-voltage (saturated) direct-axis transient reactance. (3) X g of induction motors equals 1.00 divided by per-unit locked-rotor current at rated voltage. (4) The current contributed t o a short circuit by induction motors and small synchronous motors may usually be ignored on utility systems except station service supply systems and at substations supplying large industrial loads. At these locations, as well as in industrial distribution systems or locations close t o large motors, or both, the current at l / 2 cycle will be increased by the motor contribution t o a greater degree, proportionately, than the symmetrical current will be increased at minimum contact parting time. In these calculation of '12 cycle current g the methods of 5.3.1 or 5.3.2 and the appropriate reactance values given above under the heading "Closing and Latching Duty." A 1.6 multiplying factor should be used for asymmetry and this result must not exceed the closing and latching ' x,= 7.7 -r I HP 2000 HP Fig 16 System Illustrating Large Short-circuit Contribution from Motors f EXAMPLE: In the syste shown in Fig 16, impedances are per unit on a 100 MVA base. at 4.15 kV = 1 3 Per-unit react re indicated adjace tors and transformers. Nominal voltage is used as base at all positions. The value of voltage corresponding to the highest typical operating voltage at the fault point is 4.16 kV or 1.0 per unit. T be 1.0 (see 5.3.1). rated maximum voltage of 15.0 factor K of 2.27, a continuou 1200 A, a rated short-circuit current of 9300 A, and a maximum symmetrical interrupting capability of 21 000 A at 6.6 kV and below. The symmetrical interrupting capability of this breaker at 4.16 kV is 21 000 A. The current to be compared with the symmetrical interrupting capability is, for a 3-phase fault near breaker A: capability of the circuit breaker being used. (5) These rotating machine reactance multipliers and the E/X amperes multipliers of Figs 8 and 9 include the effects of ac decay. However, the methods for calculation of system short-circuit current described in 5.3.1 and 5.3.2 incorporate sufficient conservatism t o permit the simultaneous use of a rotating machine reactance and a E/X amperes multiplier from Fig 8 or 9. (6) When the contribution of large individual induction motors is an appreciable portion of the short-circuit current, substitution for the tabulated multiplying factors of more accurate multipliers based on manufacturer's time constant data is appropriate. l + 1 l39000 1.87 + 0.10 (3.45) (1.5) + (1.10) [ 1 + (16.8) (i.0) + 7.7 + 1 (1.5);4.75)] 1 = 11 400 A 40 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS The system R could be calculated and a correction factor based on X/R determined. However, since this factor will be 1.00 and since the current determined is already less than the symmetrical interrupting capability, it is not necessary t o make this refinement. The symmetrical component of current at l/2 cycle is: l3 ing temperature. In setting up the R network for the calculation of the equivalent X/R ratio of any system, rotating machine resistance values obtained from the manufacturer or through use of the following table should be adjusted by the applicable rotating machine reactance multipliers from the table in 5.4.1. The ranges and typical values of the X/R ratios of system components may be obtained from Table 4. An estimate of the total system equivalent X/R ratio to the point of fault may be obtained from Table 5. l + 1 1.87 + 0.10 3.45 + 1.10 -'1 + (16.8)(1.2) 1 + + 7.7 4.75 C37.010-1979 = 13 5 0 0 A The symmetrical interrupting capability is adequate. Since 1.6 times the symmetrical component of the ' / z cycle current (21 600 A) does not exceed the circuit breaker closing and latching capability (34 000 A), the breaker is satisfactory for service at position A in Fig 16. Approximate Resistance System Components 5.4.2 Resistance of System and Typical X/R Ratio. For the purpose of determining the equivalent X/R ratio, it is recommended that the manufacturer's advice be obtained concerning the resistance value to be used for important electrical devices. For machines, the X/R ratio required is a measure of the time constant of the exponential decay of the dc component of machine current for a fault at its terminals. In the absence of manufacturer's recommendations, the approximate values of resistance from the table listed are suggested. In both cases, measured values on rotating machine should be converted to normal operat- Turbine generators and condensers effective resistance' Salient pole generators and motors effective resistance' Induction motors 1.2 times the dc armature resistance Power transformers ac load loss resistance (not including no-load losses or auxiliary losses) Reactors ac resistance Lines and cables ac resistance X2" 'Effective resistance = 2TfTa3 where X p V is the rated voltage negative-sequence reactance and T,3 is the rated voltage generator armature time constant in seconds. It is usually about 1.2 times the dc resistance. Table 4 Range and Typical Values of X / R Ratios of System Components System Component Large generators and hydrogen cooled synchronous condensers Range Typical Values 40-120 80 Power transformers see Fig 1 7 Induction motors Small generators and synchronous motors see Fig 18 see Fig 19 - 40-120 80 Reactors Open wire lines 2-16 5 Underground cables 1-3 2 NOTE: Actual values should be obtained if practical. 41 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-19 79 APPLICATION GUIDE FOR AC HIGH-VOLTAGE Equivalent System (For Quick Approxi Type of Circuit Range (1) Synchronous machines connected directly t o the bus or through reactors 40-1 20 (2) Synchronous machines connected through transformers rated 100 MVA and larger 40-60 Synchronous machines connected through transformers rated 25 t o 100 MVA for ( 4 ) Remote synchronous mach larger for each three-phase bank, the total equivalent impedance t o rmers rated 100 M e 90 percent or m 30-50 (5) Remote synchronous machines connected through transformers rated 100 MVA for each three-phase bank, where the transformers provide 90 percent or of the total equivalent impedance t o the fault point (6) Rqmote synchronous machines connected through other types of circuits, such as: transformers rated 10 MVA or smaller for each three-phase bank, transmission lines, distribution feeders, etc Based on class of transformer, obtain the proper factor from the table below. Multiply the transformer megavolt-ampere rating by this factor before using Fig 17 t o obtain the typical X / R value. Class Rating in MVA 1 5 or less 6? 50 Factor 1 2 5 IO 500 1000 100 50 3-PHASE,FOA-POWER TRANSFORMER MVA (STANDARD IMP LIMITS) Fig 18 X / R Range for Three-phase Induction Motors 50 40 and Synchronous Motors z 5 X 30 70 60 _I U U 0 z > 50 20 [r 2 t- 40 J a 30 U a IO >- 20 I- IO 0 50 100 250 500 2500 5000 1000 NAMEPLATE H 0 1000 10,000 P 2500 5000 1 25000 20000 10000 15000 NAMEPLATE KVA 42 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS 6. References 6.1 References to the Text [l] SKUDERNA, J. E. The X l R Method of Applying Power Circuit Breakers. AIEE Transactions (Power Apparatus and Systems), vol80, June 1959, pp 328-338. [2] AIEE Committee Report. Calculation of Electric Power System Short Circuits During the First Few Cycles. AIEE Transactions (Power Apparatus and Systems), vol 75, April 1956, Pp120-127. [12] [13] [3] HAHN, W. M., and WAGNER, C. F. Standard Decrement Curves. AIEE Transactions, vol 51, 1932, pp 352361. [14] [4] WAGNER, C. F., and EVANS, R. D. Symmetrical Components. New York: McGraw-Hill Book Company, 1933. [15] [ 51 Electrical Transmission and Distribution Reference Book. East Pittsburgh: Central Station Engineers of Westinghouse Electric Corporation, 1950. [6] WAGNER, C. F. Decrement of Short Circuit Currents. Electrical Journal, March, April, May, 1953. [7] KIMBARK, E. W. Power System Stability. New York: Wiley, vol I, 1948; vol 11, 1950;~01111,1956. [8] OWEN, R. E., and LEWIS, W. A. Asymmetry Characteristics of Progressive Short Circuits on Large Synchronous Generators. IEEE Transactions on Power Apparatus and Systems, vol PAS-90, March/April1971, pp 587-596. [ 91 AIEE Committee Report. Calculated Symmetrical and Asymmetrical ShortCircuit Current Decrement Rates on Typical Power Systems. AIEE Transactions (Power Apparatus and Systems), vol75, June 1956, pp 274-285. ANSI/IEEE C37.010-1979 Determining the Transient Recovery Voltages on Power Systems. AIEE Transactions (Power Apparatus and Systems), vol 77, Aug 1958, pp 592604. HANNA, W. M., TRAVERS, H. A., WAGNER, C. F., WOODROW, C. A., and SKEATS, W. F. System Short Circuit Currents. AIEE Transactions, V O 60,1941, ~ pp 877-881. HUENING, W. C., Jr. Time Variation of Industrial System Short-circuit Currents and Induction Motor Contributions. A IEE Transactions (Industry and General Applications), vol 74, May 1955, pp 90101. KNABLE, A. H. Proposed New Breaker Ratings and Their Effect on Application for Industrial Systems. AIEE Transactions (Power Apparatus and Systems), vol 80, Feb 1962, pp 957-963. AIEE Committee Report. A New Basis for Rating Power Circuit Breakers. AIEE Transactions (Power Apparatus and Systems), vol 73, April 1954, pp 353-367. [ 161 AIEE Committee Report. Proposed Revision of American Standard Alternating-Current Power Circuit Breakers, C37.4-1953; AIEE Conference Paper NO CP-59-186,1959. [ 171 AIEE Committee Report. Simplified Calculation of Fault Currents. Electrical Engineering, vol 67, 1948, pp 14331435. [18] SKEATS, W. F., TITUS, C. H., and WILSON, W. R. Severe Rates of Rise of Recovery Voltage Associated with Transmission Line Short Circuits. AIEE Transactions (Power Apparatus and Systems), vol 76, Feb 1958, pp 12561266. 6.3 References Concerning Line-Closing Switching Surge Voltage Control Switch [19] JOHNSON, I. B., SILVA, R. F., and WILSON, D. D. Switching surges due to energization or reclosing. Proceedings American Power Conference, vol XXIII, 1961, pp 729-736. [20] ARISMUNANDAR, A., PRICE, W. S., and McELROY, A. J. A digital computer iterative method for simulating switching 6.2 General References Concerning ShortCircuit Current Interruption [lo] DANDENO, P. L., WATSON, W., and DILLARD, J. K. Transient Recovery Voltage on Power Systems. AIEE Transactions (Power Apparatus and Systems), V O ~77, Aug 1958, pp 581-592. [ll] GRISCOM, S. B., SAUTER, D. M., and ELLIS, H. M. Practical Method of 43 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. in high vol uit breakers. IEEE Paper, No 31CP66-112. ~ 2 4 1 SONNENBERG, C. F. Methods of switching surge testing based on statistical sampling theory. IEEE Paper, No 31C43-C. surge responses of power transmission networks. IEEE Transactions, Paper No 63-1031. [211 LAUBER, T. S. Resistive energization of ission lines: part I single-phase part I1 three-phase lines. IEEE Papers, Nos 31CP65-171 and 31CP65174. [22] Sampling Procedures and Tables for Inn b y Attributes. MILStd-105D. r231 ER, C . L. and BANKOSKE, J. W. Evaluation of surge suppression resistors [251 WALD, A. Sequential Ana York: John Wiley & Sons, 19 1261 CALABRO, S. and Practices. 1962. New liability Principles ork: McGraw-Hill, [271 and Y of Reclosing Transients on a 765 kV Shunt Compensated Transmission Line, IEEE Transactions on Power Apparatus and Systems, vol 97, July/ Aug, 1978, pp 1447-1457. 44 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. d Appendix (This Appendix is not a part of ANSI/IEEE C37.010-1979, American National Standard IEEE Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis.) Appendix A Basis for E / X Method Corrected for AC and DC Decrements in the Calculation of Short-circuitCurrents A l . Introduction A2. Application Methods The methods used in developing the application guide for the more accurate procedure described in the main body of this standard (see 5.3.2) are covered in this Appendix. This Appendix shows the derivations that permit the use of a semi-rigorous procedure for short-circuit current calculations. It avoids the intricate procedure required in the rigorous procedure while providing a degree of accuracy which is within the practical limits of shortcircuit calculation considering the accuracy of constants which are usually available for such computations. Of primary importance to any application procedure is the method for determining the value of short-circuit current which a circuit breaker must interrupt. A method of calculation [ A l l which employs correction factors for application to E / X short-circuit calculations has been suggested. The correction factors proposed to be applied to the E / X values are based on the system X / R values at the point of fault. That method does not account for any decay in the symmetrical component of the short-circuit current. It, therefore, often gives overly conservative results, particularly for faults that are near generation. The application procedures developed in this Appendix employ the basic principles proposed by an earlier paper [ A l l and, in addition, include the adjustments considered necessary for the ac decrement effects on the total short-circuit current value which is to be used in selecting a circuit breaker. Two methods of short-circuit calculation are described in 5.3.1 and 5.3.2 of this standard. The E / X simplified method and its limitations are described in 5.3 .l.The method as described in 5.3.2 is the more accurate method which, though semi-rigorous so far as accuracy of results are concerned, is relatively simple to use. It is recommended for accuracy purposes that this method be used when the following conditions occur: (1) Three-phase and line-to-ground short circuits exceed 80 percent of the circuit breaker symmetrical interrupting capability. (2) Line-to-ground short circuits supplied predominantly by generators at generator voltage exceed 70 percent of the circuit breaker symmetrical interrupting capability for single line-to-ground faults. This Appendix gives the supporting technical data for the procedure decribed in 5.3.2. A3. The Effects of AC Component Decrement The need for proper recognition of the decay in the symmetrical component of short-circuit current is clearly evident from the decrement curve calculations which have been made for short-circuit applications at or near a source of generation. Evidence of this nature, including calculated and test results, is presented in an AIEE Committee report [A2]. Further evidence is included in the sample figures in this Appendix. The data are based upon calculated decrement in both the ac component and in the total short-circuit current for machines of various manufacture. In determin- 1Numbers in brackets refer to References t o the Appendix, Section AT. 45 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE 637.010-1979 A2 A3 A4 APPLICATION GUIDE FOR AC HIGH-VOLTAGE 107 MVA, 3600 r/min, conductor cooled 95-200 MVA, 3600 r/min, conventional cooled, composite characteristics 35-65 MVA, 3600 rlmin, composite characteristics Remote 87 HV LV HV 78 68 77 = Fault on generator bus, low voltage. Dower transformers. Remote = 'see Fig A 2 for fault location. ing short-circuit current decrements for these be taken into a cases, a three-phase short circuit was assumed. The single line-to-ground fault condition is discussed later in this Appendix. The calculated data obtained by a rigorous calculation procedure are shown in Table A l . From the cases presented in Table A l , it is seen that the symmetrical component of shortcircuit current at 4 cycles after short-circuit as low as 62 percent of the e remote fault (see Fig A2) or for the close to generating station short circuit, where there is substantial fault cu contribution from a remote system, the. ac decrement may be much less. However, the assumption that regardless of fault location there will be no ac decrement will result in overly conservative results. constants for A4. ~ e ~ v a tofi oE /~X Multipliers Fig A5 shows the relationship of fault current ( I a y m /Isym)nacd (the subscript nacd indicates that there is assumed to be no ac decrement) 85 a function of X/R for various contact parting times. This family of curves whiph considers only the decay of the dc component of fault current forms the basis of a recent application proposal [ A l l . They also form the starting point for the derivation of E/X multipliers for this proposal. Fig A7 illustrates the method used to modify the curves of Fig A5 so that the decay of the symmetrical component of fault current will 46 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS 8 ? I-5 $ 6 K Z L55 CO Z w 4 wv) Ka zz gl= * iz- I n m 3 -AS I ^ [ “ tI - CONSTANTS SAME FOR ABOVE TRANSFORMERS 0 I3 BKV 1 2 3 4 5 6 1 8 CONTACT PARTING TIME-CYCLES Fig A2 Symmetrical and Total Current Decrement Three-phase Short Circuit with Generator and System Contribution 1 1 1 1 1 1 1 1 1 1 1 1 Fig A3 Symmetrical and Total Current Decrement Three-phase Short-circuit Representative 95 to 200 MVA Conductor-Cooled 3600 r/min Turbine Generators Fig A4 Symmetrical and Total Current Decrement Three-Phase Short Circuits Representative 35 to 65 MVA 3600 r / h h Turbine Generators 47 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE 5 I TOTAL~URRENT ’ I 2 I I xla 0 c a a 0 3 4 CONTACT PARTING TIME-CYCLES 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Fig A6 Illustration of Accuracy of Fault Determination Hydro Generation Three-Phase Fault at High Side Terminals of Station Step-up Transformers Fig A5 Relationship Of (Iasym/Isym)nacd to x / R for Several Breaker Contact Parting Times ATIONSHIP BETWEEN $RATIO AC DECREMENT FROM URATE FAULT C A L C U L b T l O N I I 1 ADJUSTMENT FACTORS FOR AC DECREMENT FROM S A N D FAULT LOCATION (b) A D J U S T M E N T FACTOR FOR SYMMETRICAL D E C R E M E N l FAULT LOCATION Fig A7 Relationship Between X / R Ratio and A Decrement from Accurate Fault Calculation 48 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. 5 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS very small to very large apparent power ratings of various manufacture. If considered alone, 1800 r/min machines would fall above this band, but when considered in combination with 3600 r/min units they fall within the band, and even with 1800 r/min machines alone, the error in calculated current is negligible at contact parting times up to 4 cycles. As will be demonstrated later, the upper curve of this band is used to determine the E / X multipliers, since this gives the more conservative answers in terms of circuit breaker application. Water wheel generator characteristics generally fall somewhat above the band indicated. Although separate E / X multipliers could be developed for hydro-generator circuit breaker application, the typical example shown in Fig A6 indicates that the multipliers developed in Fig A8 give adequately accurate results. Fig A7(b) shows the decay of the symmetrical component of fault current at various time intervals after fault initiation. Again, because of variations in machine and system consthts, individual points plotted on this figure result in erratic patterns. In order to remain on the conservative side, points showing the least ac decrements were favored to establish the curves shown in this plot. As far as E / X multipliers for breaker application are concerned, a reduction from the initial symmetrical E / X current with time has the same effect as a reduction in X / R if only dc decrement was considered. Fig A7( c) establishes reduction factors that can be applied to (Imym / Isym)nacd ratios of Fig A5 to obtain this effect. For a given X / R ratio, the reduction factors b be applied b the (I,,, /Iwm )nacd ratios of Fig A5 are obtained from the following relationship : Reduction Factors = ANSI/IEEE C37.010-1979 Step 1: Assume a three-phase fault, an X / R ratio of 80, and time after fault initiation of 3 cycles. From Fig A5 the ratio Step 2: Referring to Fig A7 (a) and (b) an X / R ratio of 80 is related to an ac decrement of 0.70 per unit at a time of 3 cycles after fault initiation. (For this particular system the symmetrical component of fault current has decayed to 70 percent of the initial E / X value.) Step 3: Following across to Fig A7 (c) and the curve labeled 1.5 [the ratio (Iwrn /Isym)nacd obtained from step 13, a reduction factor of 0.885 per unit is obtained. Step 4 : The modifier ( I w m / E / X ) ratio for an X / R of 80 is 0.885 X 1.5 = 1.33. This establishes one point on the three-phase modified X / R decrement curves of Fig A9. Following the above step-by-step procedure, the family of curves shown in Fig A9 was determined. The final step in this derivation was to obtain E / X multipliers for breaker application. This was accomplished through the use of the modified X / R decrement curves of Fig A9 and the breaker capability curve (see Fig 4,in 5.1.3) which shows asymmetrical to symmetrical breaker capability ratios of 1.4, 1.2, 1.1,and 1.0 for minimum breaker contact parting times of 1, 2, 3, and 4 cycles, respectively. This knowledge, in conjunction with the system decrements of Fig A9 form the basis for E / X multipliers of Fig AS. For example, assume an X / R of 80 as in the earlier step-bystep analysis which gave a modified system (Iwm/E/X) ratio of 1,33 for a time corresponding to a minimum breaker contact parting time of 3 cycles. If the E/X (Isym) fault current calculation is now taken as 1.O per unit the E / X application multiplier required to ensure sufficient breaker capability is the ratio 1.33/1.1 or 1.21 (where 1.1 is the breaker capability factor for B three-cycle contact parting time). This establishes one point for Fig A 8 which gives E / X multipliers as a function of X / R for minimum breaker contact parting times of from 1 to 4 cycles. E/X A step-by-step analysis will aid in understanding the manner in which Fig A7 was used to modify Fig A5 to account for symmetrical current decrement. ZRatios of Fig A5. 49 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE > I 1 I l l 1 I 1 I I I I ' 0 1 0 20 30 40 50 60 70 80 90100 110 I20 130 140 150 RATIO Curve Corresponds to X I R of roximately 1 5 ) Fig A8 /A' Multiplier for Equivalent Symmetrical Amperes for Actual X / R Fig AIO Multiplying Factors DC Decrement [See 5.3.2 (l)] 50 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-197 9 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS A5. Longer Contact Parting Time of the accuracy of the proposed E/X multipliers for three-phase short circuits. Curve 1 of Fig A13 shows the necessary breaker asymmetrical capability as a function of contact parting time as calculated by the E / X simplified method (see 5.3.1). The E/X calculation of symmetrical fault current yields a value of 10 per unit (ac component). For the fault indicated, the 80 percent limit applies and, therefore, the breaker symmetrical capability should be at least 1.25 E / X . Breaker asymmetrical capabilities indicated in curve 1 of Fig A13 develop from the fact that the rating structure proposes asymmetrical to symmetrical current ratios of 1.0, 1.1,1.2, and 1.4 for contact parting times of 4 , 3 , 2 , and 1cycle, respectively. Curve 2 of Fig A13 shows the necessary breaker asymmetrical capability as a function of contact parting time as calculated by the more accurate method (see 5.3.2). In this case it is necessary to consider both X and R networks for breaker selection. The following sample calculation will aid in the understanding of this method as used for the determination of In certain breaker applications, breaker contact parting time in excess of the contact parting time curves of Fig A8 can be considered. This may be true whenever relay operating time exceeds the minimum l/2 cycle tripping delay assumed in arriving at the basic rating structure. For example, if a breaker with a minimum contact parting of 2 cycles is relayed such that it actually parts contacts 4 cycles after fault initiation, the E/X multiplier for breaker selection can be reduced to account for the fault current decay during that 2-cycle period. Figs A10, A l l , and ‘A12 have been so arranged as to show the multiplier to be used in the selection of breakers relayed for both minimum and longer contact parting times. A6. Accuracy of Proposed E / X Multipliers Figs A6, A13, and A14 give an illustration Fig A l l Line-to-Ground Fault Multiplying Factors Which Include Effects of AC and DC Decrement [See 5.3.2 (l)] I30 120 110 100 90 BO a 2 70 0 4 60 a 50 40 30 BREAKER 20 IO 90 II I2 I3 14 IO I I 1.2 I 3 1.4 IO I1 I2 MULTIPLYING FACTORS FOR E/X AMPERES IS 1.3 1.0 I I 1.2 I3 51 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 APPLICATION GUIDE FOR AC HIGH-VOLTAGE 1 1.1 1.2 I.3 I.4 TORS FOR E / X AMPERE S Fig A12 Three-phaseand Line-To-GroundFault Multiplyi Which Include Effects of DC Decrement Only [ S 14 13 12 c II IO CATION FACTOR) 9 c 8 7 TRA EN 6 5 4 3 (I) E K R ASYMMETRICAL CAPABILITY U S I N G 3 SIMPLIFIED APPLICATION PROCEDURE . 2 (80% APPLICATION FACTOQ) I 0 I 2 3 0 4 TIME-CYCLES CONTACT PARTING TIME-CYCLES Fig A14 Illustration of Accuracy of Fault Determination Fig A13 Breaker Asymmetrical Capability 52 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 CIRCUIT BREAKERS RATED ON A SYMMETRICAL CURRENT BASIS 17 16 15 14 I3 -12 k z" =IC a w n 9 d 5 !i 3 4 23 2 I 0 I 2 3 4 CONTACT PARTING TIME- CYCLES O 1 2 3 4 5 6 7 8 9 CONTACT PARTING TIME-CYCLES (Conventional Cooled Generator (3600 rlmin) Range 95-200 MVA) (107 MVA Turbine-Generator) Fig A15 Illustration of Accuracy of Fault Determination, Single Line-to-Ground Fault Fig A16 Illustration of Accuracy of Fault Determination, Line-to-Ground Fault at Terminals the required symmetrical capability of a breaker which parts contacts 2 cycles after fault initiation: 1.2 X 10.2 = 12.2 per unit. This establishes one point of curve 2 of Fig A13. Figs A6 and A14 are constructed similarly. Figs A15 and A16 give an illustration of the accuracy of the proposed E/X multipliers for single line-to-groundshort circuits. These figures show the short-circuit current versus time characteristics for short circuits on a highvoltage bus and on a generator bus, respectively. It will be noted that line-to-groundshort-circuit currents have less symmetrical decrement than the three-phase short-circuit currents. The E/X simplified method should not be used for single line-to-ground faults in excess of 70 percent of breaker symmetrical single line-to-ground interrupting capability if supplied predominantly from generators at generator voltage (see 5.1.2). Should the calculated line-toground fault at these locations exceed 70 percent of the circuit X to point of fault = R to point of fault = = (0.10 + 0.10) (0.20) = o.lo (0.10 + 0.10 + 0.20) (0.00104 + 0.005) (0.017) (0.00104 + 0.005 + 0.017) 0.00447 Equivalent X/R to point of fault = 22.5 Total symmetrical fault current ( E / X ) = 10 per unit. E/X multiplier from Fig A8 = 1.02. Breaker required symmetrical capability (10 X 1.02) = 10.2 per unit. breaker capability which the application engineer desires to use, then it becomes necessary to refer to the hultipliers in Fig A l l to check the adequacy of the breaker. Since a three-cycle breaker has an asymmetrical to symmetrical ratio of 1.2, the breaker required asymmetrical capability is 53 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply. ANSI/IEEE C37.010-1979 A7. References to the Appendix Circuit Current Decrement Rates on Typical Power Systems. AIEE Transactions (Power Apparatus and Systems), vol75, June 1956, pp 274-285. [A31 AIEE Committee A New Basis uit Breakers. s (Power Apparatus and Systems), vol 73, April 1954, pp 353-36*7. [ A l l SKUDERNA, J. E. The X / R Method of Applying Power Circuit Breakers. A IEE Transactions (Power Apparatus and Systems), vol 80, June 1959, pp 328-338. [A21 AIEE Committee Report. Calculated Symmetrical and Asymmetrical Short- 54 Authorized licensed use limited to: MINCYT. Downloaded on December 23,2014 at 15:15:43 UTC from IEEE Xplore. Restrictions apply.