SECTION 2 SECTION 2 SYSTEM HYDRAULICS PAGE 1 SYSTEM HYDRAULICS OR SYSTEM HEAD CURVE A system head curve shows the parameters that a particular system will allow a specific pump to perform within. SECTION 2 PAGE 2 TERMS STATIC SUCTION HEAD: Is the vertical distance in feet from the centerline of the pump suction to the liquid level when the source of liquid supply is above the centerline of pump suction. STATIC SUCTION LIFT: Is the vertical distance in feet from the centerline of the pump suction to the liquid level when the source of liquid supply is below the centerline of pump suction. STATIC DISCHARGE HEAD: Is the vertical distance in feet from the centerline of pump suction to the point of free discharge level at the highest point in the piping system. SECTION 2 PAGE 3-A TERMS (continued) SYSTEM FRICTION LOSS: Is the equivalent pressure expressed in feet of liquid required to overcome the resistance to flow through the piping system (pipe, valves, fittings, etc.). TOTAL EQUIVALENT LENGTH OF PIPE: Is the equivalent length of pipe for valves & fittings. GALLONS PER MINUTE (G.P.M.): Quantity of flow. TOTAL DYNAMIC HEAD (T.D.H.): Is the vertical distance between source of supply and point of discharge plus friction losses, when pumping at required capacity. SECTION 2 PAGE 3-B HOW IS A SYSTEM HEAD CURVE CALCULATED ? Follow the same procedures as used for calculating T.D.H. in Section 1. Do it for several flow rates, plot results on pump curve. Static suction lift. (Unchanged) Static discharge head. (Unchanged) System friction loss. (varies with flow) Total Dynamic Head At Flow Rate. SECTION 2 PAGE 4 90 Deg. Elbow S.R. 341.5' 15.0' 20.0 Ft. Discharge Gate Valve 90 Deg. Elbow S.R. 3.0' Swing Check Valve 12.0 Ft. Suction 15.0' Design Condition 400 G.P.M All Pipe & Pipe Fittings Are 4 Inch, Ductile Iron. Pump Off SECTION 2 PAGE 5 2 - 90 Deg. Elbows (10.2 x 2) . . . . . . 20.4 Ft. 1 - Gate Valve . . . . . . . . . . . . . . . . . . 2.1 Ft. 1 - Swing Check Valve . . . . . . . . . . . 26.0 Ft. Total Equivalent Length of Pipe . . . 48.5 Ft. Actual Length of Straight Pipe . . . . 374.5 Ft. Total Length (Actual and Equivalent) of Pipe . . . . . . . . . . . . . . . . . . . . . . . . 423.0 Ft. SECTION 2 PAGE 6 16 423 x = 67.68 Ft. x .71(C=120) = 48 Ft. 100 F.L. Static Suction Lift Static Discharge Head 12.0 Ft. 20.0 Ft. Total Static Head F.L. at 400 G.P.M. 32.0 Ft. 48.0 Ft. T.D.H. AT 400 G.P.M. SECTION 2 PAGE 7 80.0 Ft. G.P.M. TOTAL PIPE ACTUAL & EQUIVALENT FRICTION LOSS PER/100 PIPE FRICTION HEAD C=120 x .71 TOTAL STATIC HEAD T.D.H. 100 423 1.22' 5' 4' 32' 36' 200 423 4.40' 18' 13' 32' 45' 300 423 9.30' 39' 28' 32' 60' 400 423 16.00' 67' 48' 32' 80' 500 423 24.00' 101' 72' 32' 104' 600 423 33.70' 142' 101' 32' 133' SECTION 2 PAGE 8-A G.P.M. TOTAL PIPE ACTUAL & EQUIVALENT FRICTION LOSS PER/100 PIPE FRICTION HEAD C=120 x .71 TOTAL STATIC HEAD T.D.H. 100 423 1.22' 5' 4' 32' 36' 200 423 4.40' 18' 13' 32' 45' 300 423 9.30' 39' 28' 32' 60' 400 423 16.00' 67' 48' 32' 80' 500 423 24.00' 101' 72' 32' 104' 600 423 33.70' 142' 101' 32' 133' 423 x 1.22 = 5' x .71 = 4' + 32' = 36' 100 SECTION 2 PAGE 8-B G.P.M. TOTAL PIPE ACTUAL & EQUIVALENT FRICTION LOSS PER/100 PIPE FRICTION HEAD C=120 x .71 TOTAL STATIC HEAD T.D.H. 100 423 1.22' 5' 4' 32' 36' 200 423 4.40' 18' 13' 32' 45' 300 423 9.30' 39' 28' 32' 60' 400 423 16.00' 67' 48' 32' 80' 500 423 24.00' 101' 72' 32' 104' 600 423 33.70' 142' 101' 32' 133' SECTION 2 PAGE 8-C G.P.M. TOTAL PIPE ACTUAL & EQUIVALENT FRICTION LOSS PER/100 PIPE FRICTION HEAD C=120 x .71 TOTAL STATIC HEAD T.D.H. 100 423 1.22' 5' 4' 32' 36' 200 423 4.40' 18' 13' 32' 45' 300 423 9.30' 39' 28' 32' 60' 400 423 16.00' 67' 48' 32' 80' 500 423 24.00' 101' 72' 32' 104' 600 423 33.70' 142' 101' 32' 133' 423 x 9.30 = 39' x .71 = 28' + 32' = 60' 100 SECTION 2 PAGE 8-D G.P.M. TOTAL PIPE ACTUAL & EQUIVALENT FRICTION LOSS PER/100 PIPE FRICTION HEAD C=120 x .71 TOTAL STATIC HEAD T.D.H. 100 423 1.22' 5' 4' 32' 36' 200 423 4.40' 18' 13' 32' 45' 300 423 9.30' 39' 28' 32' 60' 400 423 16.00' 67' 48' 32' 80' 500 423 24.00' 101' 72' 32' 104' 600 423 33.70' 142' 101' 32' 133' SECTION 2 PAGE 8-E G.P.M. TOTAL PIPE ACTUAL & EQUIVALENT FRICTION LOSS PER/100 PIPE FRICTION HEAD C=120 x .71 TOTAL STATIC HEAD T.D.H. 100 423 1.22' 5' 4' 32' 36' 200 423 4.40' 18' 13' 32' 45' 300 423 9.30' 39' 28' 32' 60' 400 423 16.00' 67' 48' 32' 80' 500 423 24.00' 101' 72' 32' 104' 600 423 33.70' 142' 101' 32' 133' 423 x 24.0 = 101' x .71 = 72' + 32' = 104' 100 SECTION 2 PAGE 8-F SYSTEM HEAD CURVES For a specified impeller diameter and speed, a centrifugal pump has a fixed and predicable performance curve. The point where the pump will operates on its curve is dependent upon the characteristics of the system in which it is operating, commonly called the System Head Curve.... the relationship between flow and friction losses in a system. The two things that make up a system head curve are static head and friction losses. Static head, is the difference between the liquid level on the suction side of the pump and to the point of free discharge. If levels vary appreciably the extremes should be checked. Friction losses, are determined by; 1. Rate of flow. 2. Size of pipe, valves and fittings on the suction and discharge. 3. Type of pipe, valves and fittings on the suction and discharge. 4. Length of actual pipe and equivalent length of valves and fittings on the suction and discharge, SECTION 2 PAGE 10-A SYSTEM HEAD CURVES (continued) By plotting the system head curve and pump performance curve together, it can be determined: 1. Where the pump will operate on its curve. 2. What the pump efficiency will be. 3. What the horsepower required will be. 4. What changes will occur if the system head curve or the pump performance curve changes. SECTION 2 PAGE 10-B SYSTEM HEAD CURVES (continued) The pump performance curve can change by changing the pump r.p.m. or by trimming the impeller. The system head curve can change by: 1. Adding other pumps to the existing force main. 2. Changing or adding piping to the existing force main. 3. Changing the static head. 4. Changing size of pipe, valves and fittings on the suction and discharge. 5. Changing type of pipe, valves and fittings on the suction and discharge. 6. Changing length of actual pipe and equivalent length of valves and fittings on the suction and discharge. SECTION 2 PAGE 10-C SYSTEM HEAD CURVES (continued) See figure 1, there are four different system head curves. Curve "A" is 4" suction piping and 4" discharge piping, using a C factor of C=120. Curve "B" is 4" suction piping and 4" discharge piping, using a C factor of C=140. Curve "C" is 4" suction piping and 6" discharge piping, using a C factor of C=120. Curve "D" is 4" suction piping and 6" discharge piping, using a C factor of C=140. The table illustrates the different requirements to get 400 g.p.m. with the four system curves. SECTION 2 PAGE 10-D SYSTEM HEAD CURVES (continued) The table illustrates the different requirements to get 400 g.p.m. with the four system curves. REQUIRED SPEED REQUIRED HORSEPOWER EFFICIENCY A (C = 120) 1735 20 49% B (C = 140) 1610 15 51% C (C = 120) 1300 10 54% D (C = 140) 1250 10 55% CURVE SECTION 2 PAGE 10-E SYSTEM HEAD CURVES See figure 2, if curve "C" was selected, based upon C=120 the required pump speed would be 1300 r.p.m. If the actual condition was C=140, at 1300 r.p.m. the pump performance would move to the right and where the pump performance curve intersect curve "D" the flow would increase by approximately 50 g.p.m. NOTE: Check the N.P.S.H. to make sure if you get the 50 g.p.m. increase that your N.P.S.H.A. is a positive number. 60 1300 C C=120 D C=140 50 30 FIGURE 2 40 50 GPM 20 SECTION 2 PAGE 12-A 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 0 10 SYSTEM HEAD CURVES (continued) See figure 3, if curve "D" was selected, based upon C=140 the required pump speed would be 1250 r.p.m. If the actual condition was C=120, at 1250 r.p.m. the pump performance would move to the left and where the pump performance curve intersect curve "C" the flow would decrease by approximately 50 g.p.m. 60 1 250 50 C C=120 D C=140 30 FIGURE 3 40 50 GPM 20 SECTION 2 PAGE 12-B 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 5 0 0 10 SYSTEM HEAD CURVES When upgrading an existing system and you're not sure of the condition of the pipe, you would want to use several C factors i.e. C=100, C=120 etc. when laying out the system head curve. By using several C factors, you will see the worst condition and the best. The motors and controls should be sized to handle the worst system. Size the pumps for the worst condition. If the system is actually better, make sure the pumps will operate satisfactory hydraulically, if need be make adjustments by slowing the pumps down. FORCE MAIN VELOCITIES: Velocity criteria for force mains are derived from observations that solids do not settle out at a velocity of 2.0 ft/s or greater. Solids do settle at lower velocity or when the pump is stopped, and a velocity of 3.5 ft/s or greater is required to resuspend the deposited solids. If the solids don't resuspend it will effect the I.D. of the pipe which will change your system head curve. SECTION 2 PAGE 13 PARALLEL PUMPING SYSTEM SECTION 2 PAGE 14 PARALLEL PUMPING When operating two identical pumps in parallel, that are the same size, same speed and impeller diameter, people tend to assume that if one pump is pumping 400 gallons per minute, if they turn on the second pump they will get 800 gpm. The first exercise will show us how to figure the total capacity of two identical pumps pumping into the same header in parallel. The second exercise will show us how to figure the total capacity of two different size pumps pumping into the same header in parallel. SECTION 2 PAGE 16-A PARALLEL PUMPING (continued) Figure 1 represents a duplex pumping station with two 4" pumps operating at 1750 rpm with a full diameter impeller of 9 3/4 in. First you must have the station or system head curve for your particular station. "A" is the system head curve and "B" is the pump performance curve at 1750 rpm. With one pump operating alone the capacity will be 400 gpm at 80.0 ft. total dynamic head. Since we must find what capacity the pumps will deliver with both pumps operating, it becomes necessary to draw the head capacity curve for parallel operation of the second pump. The combine delivery for a given head is equal to the sum of the individual capacities of the two pumps at the same head. Example: At 102.0 ft. T.D.H. pump #1 will deliver 50 G.P.M., so the combine deliver for pumps #1 and #2 will be 100 G.P.M. at 102.0 ft. T.D.H.. See figure 2, the table illustrates the requirements to plot two pumps in parallel. SECTION 2 PAGE 16-B PARALLEL PUMPING (continued) T.D.H. Ft. 1 PUMP G.P.M. 1 PUMP T.D.H. Ft. 2 PUMPS COMBINE G.P.M. 2 PUMPS 102.0 ft. 50 102.0 ft. 100 98.0 ft. 100 98.0 ft. 200 95.0 ft. 150 95.0 ft. 300 92.0 ft. 200 92.0 ft. 400 88.5 ft. 250 88.5 ft. 500 To avoid over heating, pumps should never run at a flow of less than 5% of the BEP capacity. For instance, if best BEP is 100 G.P.M. flow should not be less than 5 G.P.M. SECTION 2 PAGE 16-C PARALLEL PUMPING (continued) Figure 2 shows the plot of the performance of two pumps in parallel. The operating condition is at the head where the combine curve intersects the system curve or 450 g.p.m. Note the addition of the second pump only increases the capacity by 50 g.p.m. See figure 3, our total capacity is 450 gpm. At the point where pump #2 intersects your system head curve, draw a line straight back to pump #1 performance curve then straight down. That will be the capacity of each pump, approx. 225 and the total dynamic head will be 90.0 ft. SECTION 2 PAGE16-D PARALLEL PUMPING (continued) When two or more pumps are operating in parallel, you must verify that the pumps are not operating outside of the pump operating range. As you can see from this example, we are inside of the pump operating range indicated by the solid pump performance line. The dotted line indicates an unacceptable pump operating area. If you are in the field and want to determine the capacity of two pumps in parallel (see Fig. 3a) it can be done as follows: Figure 3 indicated the T.D.H. should be 90.0 ft. with both pumps running. To check pumps in the field, compute the T.D.H. from measured gauges readings of the pump. Follow the pressure over to the pump H/Q curve and then down to the actual G.P.M. (Figure 3a) It should be noted this method of determining capacity is only good for pumps that match the curve. Worn or poorly adjusted pumps will produce a reduced curve so capacities will actually be less then the curve shows at the same head. SECTION 2 PAGE 20 PARALLEL PUMPING (continued) The second example of pumps operating in parallel, would be two different pumps pumping into the same header. It could be two identical 4 in. pumps operating at the same speed with different size impellers, with the same impeller diameter but at different speeds, or it could be a 3 in. and 4 in. pump or a 4 in. & 6 in. pump. It could be any type of combination. When you are plotting a performance of two unlike pumps, it is done a little differently. Figure 4 represents individual curves of a 3 in. and 4 in. pump performance at 1750 rpm. The system head curve is the same system head curve that was used in the first example. As you can see the capacity of the 3 in. pump would be 295 gpm at 61.0 ft. total dynamic head when operating alone and the capacity of the 4 in. pump would be 400 gpm at 80.0 ft. total dynamic head when operating alone. SECTION 2 PAGE 22-A PARALLEL PUMPING (continued) There is a duplex pumping station with a 4 in. pump with a 9 3/4 in. diameter impeller and a 3 in. pump is added with a 8 3/4 in. diameter impeller. We must find what will happen if a 4 in. pump would come on line while the 3 in. pump is operating, or if a 4 in. pump is operating and a 3 in. pump turns on. It is necessary to draw the head capacity curve for parallel operation of the two pumps. See figure 5, the 3 in. pump will not start to deliver until the discharge pressure of the 4 in. pump falls below that of the shut-off head of the 3 in. pump (88.0 ft.) The combined delivery for a given head is equal to the sum of the individual capacities of the two pumps at the same head. Example: At 88.0 ft. T.D.H. the 3 in. pump will not deliver, the 4 in. pump will deliver 255 G.P.M. so the combine capacity for the 3 in. and 4 in. pump will be 255 G.P.M. at 88.0 ft. T.D.H. See figure 5, the table illustrates the requirements to plot two different pumps operating in parallel: SECTION 2 PAGE 22-B PARALLEL PUMPING (continued) T.D.H. Ft. 3 in. PUMP G.P.M. 3 in. PUMP D.H. Ft. 4 in. PUMP G.P.M. 4 in. PUMP COMBINE G.P.M. 3 in. & 4 in.PUMPS 88.0' 0 88.0' 255 255 84.0' 35 84.0' 330 365 80.0' 70 80.0' 410 480 See figure 6, what we have just plotted is the performance of the 3 in. pump operating in parallel with the 4 in. pump. The new combined curve intersects the system head curve at the combine capacity of the 3 in. and 4 in. pump operating in parallel, approx. 415 gpm, at 82.5 ft. total dynamic head. Follow that point at the head where the combine curve crosses the system head curve (82.5 ft.), back to the 4 in. pump curve (point A) and that will be the capacity of the 4 in. pump approx. 365 gpm. Continue the line back to the 3 in. pump curve (point B) and that will be the capacity of the 3 in. pump approx. 50 gpm. SECTION 2 PAGE 22-C PARALLEL PUMPING (continued) As you can see from this example, we are outside of the pump operating range. If the pump was allowed to operate at that condition point, discharge cavitation, broken shafts and premature bearing & seal failure could occur. SECTION 2 PAGE 22-D PARALLEL PUMPING (continued) This description of mechanics of pumps operating in parallel is only intended to show the basic calculations. It also shows foregoing would not be a good selection of pump capacities or pumps for parallel operation. This example shows it is possible to get undesirable results so all applications should be checked. If you are in the field & want to determine the capacity of a 4 in. pump in parallel (see Fig. 6a) WITH a 3 in. pump it can be done as follows: Figure 6 indicated the T.D.H. should be 82.0 ft. with both pumps running. To check pumps in the field compute the T.D.H. from measured gauge readings of the pump. Follow the pressure over to the pump curve and then down to the actual G.P.M. Starting at 82.5 ft. T.D.H. on your pump performance curve, follow that point across the curve to your 3 in. pump curve, where it intersects your pump performance curve (1750 R.P.M.) read down. SECTION 2 PAGE 26-A PARALLEL PUMPING (continued) That should be your capacity for the 3 in. pump approx. 50 G.P.M. Continue across the curve until you intersect the pump curve for the 4 in. pump. Read down. Your capacity for the 4 in. pump would be approx. 365 G.P.M. Your total capacity with the 3 in. & 4 in. pump operating in parallel would be approx. 415 G.P.M. (Figure 6a) It should be noted this method of determining capacity is only good for pumps that match the curve. Worn or poorly adjusted pumps will produce a reduced curve so capacities will actually be less than the curve shows at the same head. SECTION 2 PAGE 26-B SERIES PUMPING Station S/N: 91 - 357 - AXH Location: Genessee Water & Sanitation District Golden, Co. Job Name: Pine Drop Lift Station Engineer: Genessee Water & Sanitation District Golden, Co. STAGED DUPLEX / SIMPLEX AUTO-START Owner: Genessee Water & Sanitation District Golden, Co. Design: 250 G.P.M. @ 160' T.D.H. SECTION 2 PAGE 28 SERIES PUMPING Double the head at the same flow condition point. Series pumping is nothing more than a pump station with a booster pump station at the same location. Series pumping is usually used to overcome a high static discharge head or an extremely long force main with high friction losses. In some applications a project engineer will place a station at the bottom of a hill. Then half way up the hill another station will be placed with the wet well. The same is true on extremely long force mains. The engineer uses this "leap frogging" to over come high discharge heads. We, at Gorman-Rupp, feel that series pumping is a more cost effective and practical method to overcome high discharge heads. Also, the installation costs are lower due to the fact that there is only one station installation with one wet well. SECTION 2 PAGE 29-A SERIES PUMPING (continued) ADVANTAGES of SERIES PUMPING: 1) Utilization of the highly reliable and easy to maintain "T" Series pumps. 2) One pump station installation with one wet well. 3) The "T" series pumps usually require less combined horsepower than one pump to meet the same condition point. 4) More times than not, the condition point is at the highest efficiency point on the pump curve. 5) Series pumping provides for a soft hydraulic start/stop. The first stage pump starts, then after a slight delay, .2 to 60 seconds, the second stage pump starts. Conversely, on stopping the second stage pump stops first then after the delay the first stage pump stops.This helps in relieving water hammer on starting and stopping. SECTION 2 PAGE 29-B SERIES PUMPING (continued) 6) The start/stop delay between staged pumps, also provides for electrical soft start/stops. Only half the required horsepower starts at a time. 7) Pumps will reprime in about half the time. 8) Series pumping allows the pumps to operate at lower speeds thereby reducing wear. 9) Equipment is usually smaller, easier to maintain and more manageable - vs - one large submersible or centrifugal pump. SECTION 2 PAGE 29-C SERIES PUMPING DISADVANTAGES of SERIES PUMPING: 1) Total equipment is doubled a) (4) Pumps b) (4) Motors c) (4) Motor starters and circuit breakers d) (4) Drives 2) Size or area the pump station takes up. SECTION 2 PAGE 30-A SERIES PUMPING (continued) DESIGN FACTORS OF SERIES PUMPING STATION: 1) The suction flap valve is removed from all four pumps. 2) Dual discharge check valves for each pump discharge. The primary check valve is an M & H or Gorman-Rupp - depending on the type of station. This check valve maintains the water column in the force main. The secondary check valve, Gorman-Rupp, functions as a suction check valve and maintains a full pump case and suction leg. 3) The automatic air release valve is installed between the two check valves. 4) Electrically: a) One elapsed time meter is provided for each set of pumps. b) One high temperature shutdown indicator is provided for each set of pumps. d) One hand-off automatic switch for each set of pumps. SECTION 2 PAGE 30-B SERIES PUMPING (continued) LIMITING FACTORS OF SERIES PUMPS: 1) Maximum operating pressure the second stage pump will handle. 2) Area the station is to be placed. SECTION 2 PAGE 30-C STAGED DUPLEX / SIMPLEX AUTO-START "T" SERIES SECTION 2 PAGE 32 SERIES PUMPING SYSTEM SECTION 2 PAGE 33 To Section 3