VRV Product catalogue 2020 for professionals INNOVATION CIRCULAR ECONOMY SMART USE Includes NEW VRV 5! Designed for the future What’s new? RXYSA-AV1 / AY1 p. 35 Designed for the future › Maximum flexibility allowing installation in rooms down to 10 m² › Top sustainability over the entire lifecycle thanks to low GWP R-32 refrigerant and market-leading real life seasonal efficiency › Ergonomic serviceability and handling, thanks to wide access area to easily reach components within low-profile single fan casing › Best-in-class design versatility with five sound pressure levels down to 39 dB(A) and automatic ESP setting up to 45 Pa allowing ductwork › No leak check needed as in most applications total refrigerant charge is below 7.4 kgs ErP 2021 COMPLIANT Already fully compliant to LOT 21 – Tier 2 L∞P by Daikin Reuse refrigerant to avoid more than 150,000 kg of virgin gas being produced each year › Support the circular economy of refrigerants › Make a sustainable choice by promoting units with Certified Reclaimed Refrigerant Allocation › Has zero impact on F-gas quota, as reclaimed and reused within Europe › Is administratively allocated to VRV units produced and sold in Europe Wired remote controller BRC1H52W/S/K p. 170 With new functionalities › New symbollic view display option › Save field settings and schedules on your phone and upload them to multiple controllers Silver RAL 9006 (metallic) BRC1H519S7 Black RAL 9005 (matte) BRC1H519K7 White RAL9003 (glossy) BRC1H519W7 Online controller for VRV BRP069C51 p. 166 2 Intuitive online and voice control › Control your system by voice, via Amazon Alexa or Google Assistant › Interfaces with home control systems › Available on all new R-32 VRV indoor units VRV Best Partner GREEN BUILDING SUPPORT ErP 2021 COMPLIANT Visit our BIM application suite o www.daikin.eu/BIM Maximum flexibility, minimum concern; As it should be. VRV 3 Introduction 4 Creating a sustainable future together VRV, unique in the market Which VRV offers me the best solution VRV total solution 4 8 10 12 VRV core technologies 15 VRV benefits 23 VRV 5 33 VRV 5 Outdoor units 37 VRV 5 Indoor units 39 VRV IV 47 Outdoor units Indoor units Hot water Ventilation and air handling Biddle air curtains Control systems 47 107 135 141 159 163 Options & accessories 195 Tools 209 Technical Drawings 219 3 Creating a sustainable future together Determined to reduce our environmental footprint, we aim to be CO₂-neutral by 2050. A circular economy, innovation and smart use – these are the stepping stones on our path. The time to act is now. Join us in creating a sustainable future for HVAC-R. INNOVATION CIRCULAR ECONOMY www.daikin.eu/building-a-circular-economy 4 SMART USE Towards a circular economy of refrigerants Reusing refrigerant, avoiding more than 150,000 kg of virgin gas being produced each year. F IE D RE CL ME CE TI AI R F-GAS N D REF T IO CA Make a positive choice to reduce the environmental impact of your air conditioning systems. Exclusive to Daikin, a substantial amount of reclaimed refrigerant is now used in our units and: RI › Is independently certified as the same quality as virgin refrigerant › Has zero impact on F-gas quota, as reclaimed and reused within Europe › Is administratively allocated to VRV units produced and sold in Europe › Supports the development of a circular economy in our industry Reuse refrigerant and turn waste into an asset › Create your own circular economy and reduce costs › Portable unit for easy transport › Optimum purification 5 GE RA NT AL LO Through innovation Striving to become the lowest CO² equivalent manufacturer 100% R-410A R-32 -71% potential global warming impact Introducing the lower GWP refrigerant R-32 on VRV 5 › Offer high real-world seasonal efficiencies › Variable Refrigerant Temperature for high seasonal efficiency Maximise efficiency 24/7 by deploying unique auto cleaning filters › Available on the Round flow cassette and concealed ceiling units › Automatic filter cleaning ensures high efficiencies and low maintenance costs because the filter is always clean FOTO FXDA-A 6 10 class unit for well insulated and smaller rooms › Minimised energy use and maximum comfort as the indoor is adjusted to the needsys clean Through smart use Control, monitor and optimize 24/7 Rigorously follow up on energy consumption via the Daikin Cloud Service › Direct control over your energy use › Compare with different sites to track abnormalities 24/7 Factor in experts’ advice to continuously optimise system efficiency › Enable predictive maintenance to ensure optimum operation and uptime Stay in control no matter where you are › Prevent unneccessary energy use by remote control of your system › Intuitve voice control 7 9 1 reasons why VRV is unique in the market 2 Leader in sustainability NEW › VRV 5: Completely new and dedicated R-32 mini VRV design • Less refrigerant charge • Higher efficiency • Lower CO2 equivalent › L∞P by Daikin: the creation of a circular economy of refrigerants • Saves over 150,000 kgs of virgin refrigerant being produced every year Efficiency › Variable Refrigerant Temperature for high seasonal efficiency › Round flow cassette and concealed ceiling units with auto cleaning filter › The best partner for your BREEAM, LEED or Well project ErP 2021 COMPLIANT 3 4 Comfort › Variable Refrigerant Temperature preventing cold draughts in cooling thanks to high outblow temperatures › True continuous heating during defrost › Presence and floor sensors direct the air flow away from persons, while ensuring an even temperature distribution › Auto cleaning filters to ensure optimum air quality PRESENCE SENSOR 8 FLOOR SENSOR Reliability › Refrigerant cooled PCB › Most extensive testing before new units leave the factory › Widest sales network with all spare parts available in Europe › Preventive maintenance via Daikin Cloud Service › Auto cleaning filters to further enhance reliability thanks to clean air-filters › True technical cooling 5 7 Design 6 › Widest ever range of cassette panels • Available in white and black • Sleek designer panel range › Daikin Emura, unique iconic design › Fully flat cassette, fully integrated in the ceiling NEW › Voice control via Amazon Alexa and Google Assistant through BRP069C51 online controller › Madoka: a sleek wired remote controller with intuitive touch button control › Intelligent Touch manager: A cost-effective mini BMS integrating all Daikin products › Easy integration in third party BMS via BACnet, LonWorks, Modbus, KNX › Dedicated control solutions for applications such as technical cooling, shops, hotels, ... › Daikin Cloud Service for online control, energy monitoring, comparison of multiple sites and predictive maintenance Installation 8 › › › › Automatic refrigerant charge and refrigerant containment check Unique 4-way blow ceiling suspended cassette (FXUQ) Plug & play Daikin Air Handling Unit VRV configurator software for the fastest commissioning, configuration and customisation › Outdoor unit display for quick on-site settings and detailed error readouts for improved customer support Controls Inventor › › › › Market leader of VRV systems since 1982 Over 90 years of expertise in heat pump technology Designed for and produced in Europe Innovator setting the market standard with technologies such as Variable Refrigerant Temperature, continuous heating, ... 7-segment display 9 For every application a solution ›H eat recovery for simultaneous cooling and heating › Maximum flexibility for geothermal applications with water-cooled systems › Hot and cold climate solutions offering efficient cooling up to 52°C and heating down to -25°C › Space saving mini VRV solutions, offering the most compact VRV › The invisible VRV, a unique solution when the outdoor unit must be compact and completely invisible › Replacement solutions to replace existing systems in the most cost-effective way The VRV air conditioning system is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982. VRV is the trademark of Dakin Industries Ltd, which is derived from the technology we call “variable refrigerant volume”. BREEAM is a registered trademark of BRE (the Building Research Establishment Ltd. Community Trade Mark E5778551). The BREEAM marks, logos and symbols are the Copyright of BRE and are reproduced by permission 9 Which VRV system offers me the best solution? Heat recovery or heat pump? VRV Heat recovery Additional credits for green building certificate Extracted heat is used to deliver free hot water and heating Cooling + Hot water North Heating › Simultaneous heating AND cooling from one system › "Free" heating and hot water production by transferring heat from areas requiring cooling › Maximum individual comfort in all areas › Technical cooling down to -20°C › Running costs of VRV IV heat recovery system can be 30 to 40% lower compared to water fan coil system* Components: South Outdoor unit Indoor unit 3-pipe refrigerant piping VRV Heat pump › For either heating OR cooling operation from one system Components: Outdoor unit Indoor unit * According to the Franklin + Andrews construction economics 10 2-pipe refrigerant piping Single and multi BS boxes: allows the individual switching of indoor units between heating and cooling Air cooled or water cooled? Air Cooled › Fast and easy to install; no need for additional components › Low maintenance costs › Operation range from - 25°C~52°C › Can be installed both outdoors and indoors › Up to 54HP capacity for one system Components: Outdoor unit Indoor unit Refrigerant piping Water Cooled › Suitable for high rise and large buildings because of the nearly unlimited possibilities of water piping › Not affected by outdoor temperature/climate conditions › Reduce CO2 emmisions thanks to the use of geothermal energy as a renewable energy source › Allows heat recovery in the entire building thanks to the storage of energy in the water circuit › Lower refrigerant levels thanks to the limited distance between outdoor and indoor units Additional credits for green building certificate Components: Outdoor unit Indoor unit Refrigerant piping (Geothermal) water loop Geothermal application 11 VRV total solution Typically, many buildings today rely on several separate systems for heating, cooling, air curtain heating and hot water. As a result energy is wasted. To provide a much more efficient alternative, VRV technology has been developed into a total solution managing up to 70% of a buildings energy consumption giving large potential to cost saving. 22 › Heating and cooling for year round comfort › Hot water for efficient production of hot water › Underfloor heating /cooling for efficient space heating/cooling › Fresh air ventilation for high quality environments › Air curtains for optimum air separation › Controls for maximum operating efficiency › Cooling for server rooms, telecom shelters, ... via VRV heat recovery or Sky Air units › Refrigeration via our VRV based refrigeration units Average hotel energy consumption Average office energy consumption Refrigeration 3% Lighting Ventilation 4% Integrate third party equipment Space cooling 15% Kitchen Office Other 70% Hot water 9% Other Space heating 25% Office equipment 48% Hot water 17% Lighting Space cooling 9% Space heating 31% 12 Ventilation 5% Integrate third party equipment Offices Efficiency in the workplace "Leading edge design in harmony with the construction and interior design.“ Architect Hotel Hospitality with economy “With Daikin we could perfectly combine the authenticity of the hotel with the latest technology and comfort.” Owner of a 5-star hotel Shops reducing retail costs "Together with Daikin’s technical team we have optimised the design of our HVAC system, reducing investment levels and operational costs. Daikin has offered us access to the most up to date technology." Retail shop representative Residential there is no place like home “A cost effective, low energy consumption heat pump system for home owners, offering maximum comfort” 13 VRV standards & technologies Our VRV systems set pioneering standards in all-round climate comfort performance. Total design simplicity, offering rapid installation, full flexibility as well as absolute efficiency and comfort. Find out about all these revolutionary changes at www.daikin.eu/VRV 14 VRV core technologies VRV core technologies 15 Variable Refrigerant Temperature Continuous comfort during defrost VRV configurator 16 7 segment display 19 Newly developed inverter compressor 20 Refrigerant-cooled PCB 20 4-side heat exchanger 20 Predictive control 21 Outer rotor DC fan motor 21 E-Pass heat exchanger 21 I-demand function 21 18 19 15 Unique UNIQUE Capacity & Load in cooling mode Cooling requirement System capacity Design point Refrigerant temperature building Adjust capacity by Te control to meet the load (avoid over capacity and ON/OFF operation) Variable Te Fixed Te Seasonal efficiency the cooling need of the temperature can be UNIQUE Daikin VRV IV+ Variable Refrigerant Temperature control for energy saving in partial load condition. The capacity is controlled by the inverter compressor and variation of the evaporating (Te) and condensing (Tc) temperature of the refrigerant in order to achieve the highest seasonal efficiency. Evaporating temperature can vary between 3 and 16° which is the widest on the market. the higher the efficiency VRF standard Capacity is controlled only with the variation of the inverter compressor the higher the refrigerant How does it work? The lower the capacity need, › Seasonal efficiency increased by 28% › The first weather accommodating control on the market › Customer comfort is assured thanks to higher outblow temperatures (preventing cold draughts) temperature, Thanks to its revolutionary variable refrigerant temperature technology (VRT), VRV IV+ continuously adjusts both the inverter compressor speed and the refrigerant temperature in cooling AND heating, providing the necessary capacity to meet the building load with the highest efficiency at all times! The higher the refrigerant The biggest leap since the inverter compressor The colder it gets the lower variable refrigerant temperature Efficiency with Variable Refrigerant Temperature Efficiency up 20° 25° 30° 35° Outdoor temperature Calculate the benefit of variable refrigerant temperature for your project in our seasonal solutions calculator: http://extranet.daikineurope.com/en/software/ downloads/solutions-seasonal-simulator/default.jsp Success story Real test: up to 46% less energy consumed How effective is the VRV IV+ heat pump technology? A field trial was carried out in a shop of a fashion chain in Germany and showed that the innovative Daikin VRV IV delivers dramatically better energy efficiency compared with previous models. The trial demonstrated that by using air, an infinitely renewable and free energy source, the VRV IV+ system provides a complete and environmentally sustainable solution for heating, cooling and ventilation in commercial applications. The trial also showed that only by monitoring climate control systems carefully and intelligently businesses can identify and control energy waste. The trial results showed that the new VRV IV system consumed up to 60% less energy than the VRV III system, particularly during cooling. Overall energy savings during heating averaged 20%. 16 Contact Daikin for more infomation about monitoring services. Check on 8 Different modes to maximise efficiency and comfort https://www.youtube.com/ DaikinEurope For maximum energy efficiency and customer satisfaction, the outdoor unit needs to adapt the evaporating/condensing temperature at the optimum point for the application. How to set the different modes? 6 Set up the main operation mode of the system Define how the system reacts to changing loads Step 1 Step 2 Automatic* Evaporating AND condensing temperature automatically selected according to ambient temperature Quick reaction speed Powerful patents Where a quick increase of load is expected such as conference rooms. Quick reaction speed to changing load has priority, with temporarily colder outblow as a result. Top efficiency The perfect balance: Achieves top efficiency throughout the year, reacts quickly on the hottest days High sensible Target Te can be selected between 7°Cto 11°C Quick reaction speed Top efficiency Year round top efficiency Basic Quick Same as above but slower response than the powerful mode. Mild * This mode would be suitable for most office applications and it is the factory set mode. The perfect balance: Slower reaction speed with top efficiency Powerful Quick Same as above but slower response. Mild The air off temperature remains fairly constant. Suitable for low ceiling rooms. Eco Coil temperature would not change due to fluctuating load. Suitable for computer or low ceiling rooms. No submodes Current VRF standard Gives customer choice for fixing coil temperature which avoids cold draughts. A quick reaction speed to changing load has priority, with temporarily colder outblow as a result. This is how most other VRF systems work and can be used for all general type of applications. * Factory setting VRV III 20HP (2 modules) VRV IV 18HP (1 module) March 2012 - February 2013 March 2013 - February 2014 Avg (kWh/Month) 2.797 1.502 Total (KWh) 33.562 18.023 Total (€) 6.041 3.244 9,9 5,3 Period Yearly (operation cost/m² (€/m²) 46% savings = € 2.797 Measured data Fashion store Unterhaching (Germany) › Floor space: 607m² › Energy cost: 0,18 €/kWh › System taken into account for consumption: - VRV IV heat pump with continuous heating - Round flow cassettes (without auto cleaning panel) - VAM for ventilation (2x VAM2000) - Biddle Air curtain. 17 Real continuous heating during defrost mode Check on VRV IV+ continues to provide heating even when in defrost mode, providing an answer to any perceived disadvantages of specifying a heat pump as a monovalent heating system. https://www.youtube.com/ DaikinEurope › Continuous indoor comfort ensured by the heat accumulating element and alternate defrost › An innovative alternative to traditional heating systems Heat pumps are known for their high energy efficiency in heating, but frost is accumulated on their heat exchanger during heating operation and this must be melted periodically using a defrost function that reverses the refrigeration cycle. This causes a temporary temperature drop and reduced comfort levels inside the building. Defrosting can take over 10 minutes (depending on the size of the system) and occurs mostly between -7 and +7°C when humidity levels in the air are high. Humidity freezes on the coil, resulting firstly in poor performance and eventually low comfort levels. The VRV IV+ has changed the heating paradigm by providing heat even during defrost operation thus diminishing the temperature drop indoors and providing comfort at all times. Room temperature VRV IV+ VRF benchmark ΔT Time How does it work? UNIQUE Heat accumulating element Alternate defrost For the VRV IV+ heat pump single unit systems a unique heat-accumulating element is used. This element, based upon phase change material, provides the energy to defrost the outdoor unit. On all our multi unit systems only 1 outdoor coil is defrosted at a time, ensuring continuous comfort during the whole process. The outdoor unit coil is defrosted … Kan niet aders dan met gradient, want vloeistof warmt op en koelt af... … with the energy stored in the heat accumulating element … … so a comfortable temperature is maintained the outdoor unit coil is defrosted … indoors. … one at the time … … so a comfortable temperature is maintained indoors Available on: Available on: Heat pump Heat pump Heat recovery even checken in de infographics map: ik denk dat er een tekening van eenVRV VRV bestaat Replacement RYYQ8-20U RYYQ16-54U REYQ10-54U RXYQQ16-42U RQCEQ280-848P3 Water cooled VRV has no defrost cycles 18 VRV Configurator Check on Software for simplified commissioning, configuration and customisation › Graphical interface › Manage systems over multiple sites in exactly the same way › Retrieve initial settings https://www.youtube.com/ DaikinEurope Configurator software for simplified commissioning The VRV configurator is an advanced software solution that allows for easy system configuration and commissioning: › less time is required on the roof configuring the outdoor unit › multiple systems at different sites can be managed in exactly the same way, thus offering simplified commissioning for key accounts › initial settings on the outdoor unit can be easily retrieved. Simplified commissioning Retrieve initial system settings User friendly interface instead of push buttons 7-segment display for quick and accurate error diagnosis Outdoor unit display for quick on-site settings and easy read out of errors together with the indication of service parameters for checking basic functions. › easy-to-read error report › clear menu indicating quick and easy on-site settings › indication of basic service parameters to quickly check basic functions: high pressure, low pressure, frequency and operation time history of compressors, temperature of discharge/suction pipe. › No need to unmount the big front panel of the unit thanks to the service access 3 digit 7-segment display Available on: Heat recovery Heat pump Replacement VRV REYQ-U RYYQ-U RXYQQ-U RXYQ-U RXYSCQ-TV1 (only configurator, no 7 segment display) RXYSQ-T8V/T8Y/TY1 (only configurator, no 7 segment display) SB.RKXYQ-T(8) (only configurator, no 7 segment display) 19 VRV core technologies 37 patents UNIQUE Scroll compressor Check on Back pressure control › Pressure port increases pressure below the scroll in low load operation, preventing refrigerant leak from the high to low pressure side › Increased partial load efficiency The back pressure control port sends high pressure refrigerant https://www.youtube.com/ DaikinEurope Refrigerant leak at low load with conventional compressor to the back of the scroll, preventing refrigerant leakage Refrigerant-cooled PCB › Reliable cooling because it is not influenced by ambient air temperature › Smaller switchbox for smoother air flow through the heat exchanger increasing heat exchange efficiency with 5% 6 patents UNIQUE UNIQUE 4-sided, 3-row heat exchanger › Heat exchange surface up to 50% larger › (up to 235m2), leading to 30% more efficiency 10 patents 20 UNIQUE Target Predictive Control Function (PCF) General VRF: Double time against VRV IV › Reaching targets faster › Reaching targets without overshooting, so there is no waste, resulting in improved efficiency The large number of Daikin systems already in operation and which are monitored by our i-Net software put us in the unique position of being able to analyse this data and develop the predictive control function. t 2t (VRV IV) (general VRF) VRV IV with PCF General VRF with PI control Target capacity/refrigerant temperature VRV IV: PCF Compressor works with predictive data for the control › result: quick convergence to the target temperature and reduction of waste operation of the compressor Half time against general VRF General VRF: Pi control Compressor works with feedback only for the control › UNIQUE result: waste operation and longer time before reaching target set point DC fan motor Outer rotor DC motor for higher efficiency › Larger rotor diameter results in greater force for the same magnetic field, leading to better efficiency › Better control, resulting in more fan steps to match the actual capacity Conventional motor with inner rotor Daikin outer rotor Sine wave DC inverter Optimizing the sine wave curve results in smoother motor rotation and improved motor efficiency. F F DC fan motor The use of a DC fan motor offers substantial improvements in operating efficiency compared to conventional AC motors, especially during low speed rotation. E-Pass heat exchanger Optimising the heat exchanger’s path layout prevents heat being transferred from the overheated gas section to the sub-cooled liquid section which is a more efficient way to use the heat exchanger. I-demand function Limit maximum power consumption. The newly introduced current sensor minimizes the difference between the actual power consumption and the predefined power consumption. Rotor Stator Stator Standard heat exchanger e-Pass heat exchanger In 85 °C In 85 °C 43 °C 55 °C 27 °C Rotor 55 °C 27 °C 60 °C 50 °C 55 °C Out 45 °C Out 45 °C Power consumption Predefined limit Time 21 The VRV benefits See how you can benefit from Daikin's highly flexible and efficiency product range 22 VRV benefits VRV benefits 23 Drastically reducing your running costs 24 Comfort guaranteed at all times 26 Great design flexibility 28 Fast installation and commissioning Easy servicing 30 30 23 Drastically reducing running costs + Top reliability + Up to 6 times greater resistance against corrosion -71% Introducing R-32 refrigerant on VRV › Lower Global Warming Potential (GWP): only 1/3rd of R-410A › Lower refrigerant charge: 10% less compared to R-410A › Higher energy efficiency › Single component refrigerant, easy to handle and recycle 100% 71% R-410A R-32 potential global warming impact Potential global warming impact Precise zone control VRV systems have low running costs because it permits each zone to be controlled individually. That is, only those rooms that require air conditioning will be heated or cooled, while the system can be shut down completely in rooms where no air conditioning is required. All inverter compressors All inverter control compressors allow to control the refrigerant volume almost stepless. In this way the capacity perfectly matches the different loads in every room avoiding unnecessary energy use. Additionally all inverter compressors also allow precise refrigerant temperature control, automatically adapting your VRV to your building and climate requirements, reducing running costs with 28%. Even more, having no ON/OFF compressors, means total absence of high starting currents, which are being more and more limited by the grid operators and power suppliers. 24 ON OFF ALL ON ON OFF Technical benefits VRV Duty Cycling extends operation life The cyclical start-up sequence of multiple outdoor units systems equalises compressor duty and extends operating life. Sequential Start Up to 3 outdoor units can be connected to 1 power supply and can be turned on sequentially. This allows the number of breakers and their capacities to remain small and simplifies wiring (for models of 10HP or less). Only one power supply 1 v/d 2 k Top quality Only brazed connections Flare or flange All flange and flare connections inside the unit have been replaced by brazing connections to ensure improved refrigerant containment. Also the connection of the outdoor in the main pipe is brazed. Brazing Anti Corrosion Treatment An anti-corrosion heat exchanger cutaway view Special anti corrosion treatment of the heat exchanger provides 5 to 6 times greater resistance against acid rain and salt corrosion. The provision of rust proof steel sheet on the underside of the unit gives additional protection. Hydrophilic film Aluminium Heat exchanger foto in crkeltje zou ik behouden Degree Performed tests: VDA Wechseltest Contents of 1 cycle (7 days): 24 hours salt spray test SS DIN 50021 96 hours humidity cycle test KFW DIN 50017 › 48 hours room temperature & room humidity testing period: 5 cycles › › › › Corrosion-resistant Acrylic resin of corrosion 8 7 6 5 4 3 2 1 0 Push button on the PCB 1 2 3 4 Bare aluminium 5 Cycle DAIKIN P.E. Degree of corrosion 10 9 Kesternich test (SO2) 8 › contents of 1 cycle (48 hours) 6 according to DIN50018 (0.21) › testing period : 40 cycles R410-A 7 5 4 3 2 1 0 1 2 3 4 5 6 10 20 30 40 50 60 70 Cycle naam op gasfles eventueel vervangen door echt logo even checken 25 infographics m dat er een tek Comfort guaranteed Smart Control brings comfort Stable room temperature Suction air temp. An electronic expansion valve, using PID (Proportional Integral Derivative) control, continuously adjusts the refrigerant volume in respond to load variations of the indoor units. The VRV system thus maintains comfortable room temperatures at a virtually constant level, without the temperature variations typical of conventional ON/ OFF control systems. Cooling Stable room temperature Time VRV SERIES (DAIKIN indoor unit (PID controlled)) Note: The graph shows the data, measured in a test room assuming actual heating load. The thermostat can control stable room ON/OFF controlled indoor unit (2.5HP) temperature at ± 0.5°C from set point. No more cold draught Automatic or manual adjustment of refrigerant temperature leads to higher outblow temperatures which avoid the cold draught coming from the indoor unit. 16° Constant and high Available on all VRV IV units air discharge temperature Room temperature Continuous heating During defrost › Indoor comfort not effected via the unique heat accumulating element or alternate defrost › The best alternative to traditional heating systems VRV IV VRF benchmark Available on REYQ-U, RYYQ-U, RXYQ-U and RXYQQ-U ΔT Time Back-up function In the event of a compressor malfunction another compressor or outdoor unit will take over in order to maintain 8 hour interim capacity, allowing time for maintenance or repair while comfort remains guaranteed. Single outdoor unit with multiple compressors 26 Multi outdoor unit system Technical benefits VRV Prevent energy losses from over-ventilation with CO2 sensor Enough fresh air is needed to create an enjoyable environment, but ventilating constantly is leading to energy waste. Therefore an optional CO2 sensor can be installed which switches off the ventilation system when there is enough fresh air in the room, thus saving energy. Low indoor unit operation sound level Daikin indoor units have very low sound operation levels, down to 19dB(A), making them ideal for sound sensitive area’s as hotel bedrooms, etc… Example of CO2 sensor operation in a meeting room: 9 AM 12 PM CO2 level Fixed ventilation rate Ventilation amount 5 PM Decrease in air volume and more energy saving compared to fixed ventilation rate Increase in air volume and better comfort compared to fixed ventilation rate 7 8 9 10 When many people are in the room, more fresh air is brought in to maintain comfortable CO2 levels. When fewer people are in the room, energy is saved by bringing in less fresh air. 11 12 Morning meeting 13 14 15 Lunch time 16 17 18 19 hour Meeting db(A) Perceived loudness 0 Treshold of hearing Sound - 20 Extremely soft Rustling leaves 40 Very soft Quiet room 60 Moderately loud Normal conversation 80 Very loud City traffic noise 100 Extremely loud Symphonic orchestra 120 Threshold of feeling Jet taking off Daikin indoor units: FXZQ-A emura 19dB(A) 25.5dB(A) Connectable to all VRV heat pumps Connectable to VRV IV+, VRV IV C+series and VRV IV W+series Night quiet mode For areas where there are stringent limitations to sound levels, the outdoor unit sound level can be automatically reduced to meet the requirement. Peak in the outdoor temperature 100% 8 hrs 10 hrs 50% Capacity* % Load % Operation Sound dBA Night mode Step 1 To manually set set the time for low noise operation you can use the external control adaptor DTA104A61/62/53. Step 2 Night mode STARTS Night mode ENDS Example for VRV IV heat pump, factory setting. < 00000 27 Great design flexibility Wide operation range Air cooled Water cooled The VRV system can be installed practically anywhere. VRV air cooled outdoor units can cool between -20°C BD and +52°C DB outdoor ambient and can be used as monovalent heating system between -25°C WB and +15.5°C WB. Standard water cooled outdoor units operation between 10°C & 45°C for both heating and cooling. In geothermal mode, the operation range is extended to -10°C* during heating and 6°C during cooling. These units are not influenced by external conditions and function well in extreme climates. -20C° DB 52°C DB -25C° WB 15.5°C WB Heating mode 45°C Heating mode water temperature 6°C 45°C Cooling mode water temperature * Ethylene glycol should be added to the water when Cooling mode -10°C the water inlet temperature is below 5°C With the technical cooling function, the operation range in cooling of the heat recovery system is extended from -5°C to -20°C 1, making it perfect for integrating server rooms. 1 VRV-W Contact your local dealer for more information and restrictions VRV-W 90m piping length after first branch The long piping lengths, high level differences and small refrigerant piping allows for a design with little limitations and leaving maximum space for lettable space. VRV-W 30m Level difference between indoor units Flexible piping design 40m (90m1) Level difference between indoor and outdoor units even checken in de infographics map: ik denk dat er een tekening van een VRV bestaat 165m Actual piping length even checken in de infographics map: ik denk dat er een tekening van een VRV bestaat Indoor installation Unlimited water piping length VRV IV example Air cooled Total piping length Water cooled 1000m 500m 165m (190m) 165m (190m) Longest length after first branch 90m1 40m (90m1) Level difference between indoor and outdoor units 90m 50m (40m²) Level difference between indoor units 30m 30m Longest length actual (Equivalent) 1 1 Contact your local dealer or consult technical literature for more information and restrictions 2 In case outdoor unit is located below indoor units Phased installation Installation of the VRV system can be implemented floor by floor, so that sections of the building can be put into use very quickly, or enabling the air conditioning system to be commissioned and operated in stages, rather than on final completion of the project. 28 Under construction VRV system Installation floor by floor Technical benefits VRV Indoor installation Water cooled Air cooled Standard outdoor unit installed indoors The VRV optimised fan blade shape increases output and reduces pressure loss. Together with the high ESP setting (up to 78.4 Pa), it makes VRV outdoor units ideal for indoor installation using ducts. › Seamless integration in the surrounding architecture as you cannot see the unit › Highly suited for sound sensitive areas as there is no external operation sound › Superior efficiency, even in the most extreme outside conditions, especially in geothermal operation ESP up to 78.4 Pa VRV IV i-series heat pump for indoor installation The ultimate and unique solution from Daikin is to use the VRV IV i-series. This unit is optimised for indoor installation and is the most flexible solution, without the need for a large technical room to put the outdoor unit and it is complete invisible! More details on page 62 Multiple tenants, one outdoor unit The multi tenant function ensures that the entire VRV system does not shut down when the main power supply of an indoor is switched off. This means that the indoor unit’s main power supply can be turned off when a part of the building is closed or is being serviced without affecting the rest of the building. operation in holiday in service operation 2 solutions according to the needs: › Service setting, without additional hardware: for service execution within 24 hours › PCB option: when tenants leave for a longer period (holiday) and the main power supply is shut down multi tenant No structural reinforcement necessary Thanks to the vibration-free and sufficient light construction of the outdoor units, floors do not need to be reinforced, reducing the overall cost of the building when compared to a chiller. max. 398kg for a 20HP unit 29 Fast installation and commissioning 1 v/d 2 kiezen + Easy servicing Automatic charging & testing Efficient use of time foto in 4crkeltje zou ik behouden 1 2 3 Calculate extra refrigerant volume Connect first bottle on VRV & start filling process Check on regular times weight scale to check weight of refrigerant Manual 1 2 Connect bottle to VRV & activate automatic charging function Filling procedure stops automatically: close valves Automatic Stop manually the VRV filling procedure & close valves Push button on the PCB R410-A If the temperature drops below 20°C* manual charging is necessary. * 10°C for heat pump for cold regions even checken in de Available on REYQ-U, RYYQ-U, RXYQ-U, RQYQ-P, RXYQQ-U, RQCEQ-P3 infographics map: ik denk naam *op gasfles eventueel After charging, pushing the test operation button initiates a check on the wiring, shut off valves, sensors and refrigerant volume. dat er een tekening van een VRV bestaat vervangen door echt logo Did you know? 10% undercharged up to 25% capacity loss 33% more energy use OPTIMAL CHARGE = OPTIMAL EFFICIENCY Planned installation 64 m refrigerant piping Real installation 76 m refrigerant piping › › 0.5 kg calculation: 2.2 kg extra refrigerant required 2.7 kg extra refrigerant required in reality Compliance to F-gas regulation When activating the refrigerant containment check, the unit switches into cooling mode and duplicates certain reference conditions based on memory data. The result indicates whether or not refrigerant leakage has occurred. Remote refrigerant containment check › › › › › Perform the refrigerant containment check remotely via intelligent Touch Manager. Remotely set the time and start the refrigerant containment check when it is most convenient for you. The refrigerant volume of the complete system is calculated for the following data: Outdoor temperature Reference system temperatures Reference pressure temperatures Refrigerant density Types and number of indoor units Connect to customer site via internet or 3G increasing customer satisfaction as there is no disruption to the air conditioning during business hours. Check the report once the check has been done. Available on REYQ-U, RYYQ-U, RXYQ-U. Next to remote checking, the function can also be activated on-site via a push button on the PCB. 30 Technical benefits VRV VRV configurator software even checken in de even checken in de infographics map: ik denk infographics map: ik denk dat er een tekening van dat er een tekening van een VRV bestaat een VRV bestaat For simplified commissioning, configuration and customisation Available on REYQ-U, RYYQ-U, RXYQ-U, RXYSCQ-TV1, RXYSQ-TY8V/T8Y/TY1, SB.RKXYQ-T(8) and RXYQQ-U User friendly interface instead of 1 v/d 2 kiezen 1 v/d 2 kiezen 3 digit 7-segment display push buttons Compact design The compact design of the outdoor units is sufficient to allow them to be taken up to the top of a building in a commercial elevator, overcoming site transportation problem, particularly when outdoor units need to be installed on each floor. foto in crkeltje zou ik behouden foto in crkeltje zou ik behouden Push button on the PCB Daikin unified REFNET piping R410-A Push button on the PCB R410-A The unified Daikin REFNET piping system is designed even checken in de even checken in de for simple installation. infographics map: ik denk naam op gasfles eventueel infographics map: ik denk naam op gasfles eventueel dat er een tekening van dat er een tekening van vervangen door echt logo vervangen door echt logo Compared to regular T-joints, where refrigerant een VRV bestaat een VRV bestaat distribution is far from optimal, the Daikin REFNET joints have specifically been designed to optimise refrigerant flow. Daikin Europe N.V. advises only to use Daikin REFNET piping system. REFNET joint T-joint REFNET joint REFNET header Easy wiring “Super Wiring” System Simplified wiring Shared use of wiring between indoor units, outdoor units and centralised remote control › Easy retrofit of centralised remote control › Impossible to make incorrect connections thanks to non polarity wiring › Sheated wire can be used › Unique total wiring length up to 2,000 m Cross wiring check The cross wiring check function warns operatives of connection errors in inter unit wiring and piping. Auto Address Setting Function Allows wiring between indoor and outdoor units, as well as group control wiring of multiple indoor units, to be performed without the bothersome task of manually setting each address. * auto adress setting fuction is not available for centralized operation 31 VRV 5 Designed for the future 32 VRV 5 VRV 5 33 Product overview 34 Outdoor units 37 Indoor units 38 Ceiling mounted cassette units FXFA-A - Round flow cassette FXZA-A - Fully flat cassette 38 39 41 Concealed ceiling units Auto cleaning filter for concealed ceiling units FXDA-A - Slim concealed ceiling unit FXSA-A - Concealed ceiling unit with medium ESP 42 42 43 44 Wall mounted units FXAA-A - Wall mounted unit 45 45 33 6 O Capacity class (kW) Remarks O * * Air curtains 5 AHU connection VRV 5 S-series Lower CO2 equivalent and market-leading flexibility › Compact single fan design saves space and is easy to install › Market-leading serviceability and handling › Reduced CO2 equivalent thanks to the use of lower GWP R-32 refrigerant and lower refrigerant charge › Offering like-for-like R-410A flexibility 4 Hydrobox UNIQUE Product name Residential indoor units Air – cooled heat pump Model VRV indoor units VRV 5 outdoor unit overview HRV units VAM Product overview 1~ RXYSA-AV1 / AY1 3~ › Standard total system connection ratio limit: 50 ~ 130% * For sales availability refer to your local sales representative With new Madoka BRC1H52W/S/K ! VRV 5 indoor unit overview Capacity class (kW) Wall mounted Concealed ceiling Ceiling mounted cassette Type Model UNIQUE Round flow cassette UNIQUE Fully flat cassette Slim concealed ceiling unit Product name › › › › › 360° air discharge for optimum efficiency and comfort Auto cleaning function ensures high efficiency Intelligent sensors save energy and maximize comfort Flexibility to suit every room layout Lowest installation height in the market! Widest choice ever in decoration panel designs and colors FXFA-A › › › › › Unique design that integrates fully flat into the ceiling Perfect integration in standard architectural ceiling tiles Blend of iconic design and engineering excellence Intelligent sensors save energy and maximize comfort Small capacity unit developed for small or well-insulated rooms Flexibility to suit every room layout FXZA-A Slim design for flexible installation Compact dimensions enable installation in narrow ceiling voids Medium external static pressure up to 44Pa Only grilles are visible Small capacity unit developted for small of well-insulated rooms Reduced energy consumption thanks to DC fan motor FXDA-A › › › › › 10 15 20 25 32 40 50 63 71 80 100 125 140 UNIQUE FOR R-32 Auto cleaning filter option Slimmest yet most powerfull medium static pressure unit on the market! Concealed ceiling unit with medium ESP › S limmest unit in class, only 245mm › Low operating sound level › Medium external static pressure up to 150Pa facilitates using flexible ducts of Wall mounted unit › › › › › FXSA-A FXAA-A varying lengths Automatic air flow adjustment function measures the air volume and static pressure and adjusts it towards the nominal air flow, guaranteeing comfort For rooms with no false ceilings nor free floor space Flat, stylish front panel is more easy to clean Small capacity unit developted for small of well-insulated rooms Reduced energy consumption thanks to DC fan motor The air is comfortably spread up- and downwards thanks to 5 different discharge angles Cooling capacity (kW)1 1.1 1.7 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 Heating capacity (kW)2 1.3 1.9 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 (1) Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m (2) Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m 34 Black and designer panels Ceiling mounted cassette units Concealed ceiling units Wall mounted unit FXZA-A FXDA-A FXSA-A FXAA-A During absence, indoor comfort levels can be maintained Fan only The air conditioner can be used as fan, blowing air without cooling or heating Auto cleaning filter The filter automatically cleans itself. Simplicity of upkeep means optimum energy efficiency and maximum comfort without the need for expensive or time-consuming maintenance Floor and presence sensor The presence sensor directs the air away from any person detected in the room. The floor sensor detects the average floor temperature and ensures an even temperature distribution between ceiling and floor Draught prevention When starting to warm up or when the thermostat is off, the air discharge direction is set horizontally and the fan to low speed, to prevent draught. After warming up, air discharge and fan speed are set as desired Whisper quiet Daikin indoor units are whisper quiet. Also the outdoor units are guaranteed not to disturb the quiet of the neightbourhood Auto cooling-heating changeover Automatically selects cooling or heating mode to achieve the set temperature Air filter Removes airborne dust particles to ensure a steady supply of clean air (G3 (2) in case of auto cleaning panel) G1(2) G1 (2) Dry programme Allows humidity levels to be reduced without variations in room temperature Ceiling soiling prevention The air discharge of the indoor unit is specially designed to prevent air being blown against the ceiling to prevent ceiling stains Vertical auto swing Possibility to select automatic vertical moving of the air discharge louvre, for uniform air flow and temperature distribution Fan speed steps Multiple fan speeds to select,to optimize comfort levels 5 + auto 3 + auto Individual louver control Individual louver control via the wired remote controller makes it simple to fix the position of each louver individually, to suit any new room configuration. Optional closure kits are available as well Online Controller (BRP069C51) Can control and monitor the status of your Daikin heating or air conditioning system (1) (1) Other funtcions Remote control & timer Air flow Comfort We care Home leave operation Air treatment FXFA-A Humidity control VRV 5 indoor unit benefit overview (optional) (optional) G1(2) 3 3 + auto 2 (1) (1) Weekly timer Timer can be set to start and stop operation anytime on a daily or weekly basis Infrared remote control Infrared remote control with LCD to remotely control your indoor unit Wired remote control Wired remote control to remotely control your indoor unit Only connectable to new BRC1H52W/S/K Centralised control Centralised control to to control several indoor units from one single point (1) Auto-restart The unit restarts automatically at the original settings after power failure Self-diagnosis Simplifies maintenance by indicating system faults or operating anomalies Drain pump kit Facilitates condensation draining from the indoor unit Standard Standard Standard Standard Optional Multi tenant The indoor unit’s main power supply can be turned off when leaving the building or for servicing purposes NEW (1) Must be combined with Madoka wired remote controller (2) Filter grade category are an indication, filters are not certified. 35 Best-in-class design versatility Indoor unit installation in rooms down to 10m²! When using R-32 refrigerant in VRV systems additional measures need to be taken according to the product standard IEC60335-2-40 (Ed.6), in order to use the VRV system to it’s full potential. ʯ The product standard IEC60335-2-40 (Ed.6) specifies all information regarding the total refrigerant amount and minimum room surface, depending on the additional measures taken. ʯ Area 1: Application area without any measures • Typically split and Sky Air systems fall in this area thanks to very low refrigerant charges. • A typical mini VRV installation, with 6.5kgs of refrigerant would require a minimum room surface of 39m² (1) ʯ Area 2 :Extended application area of VRV 5 including 2 factory-mounted measures. • The Daikin way, enabling to use the VRV system to it‘s full potential, with a minimum room surface down to 10.0m² (1) THIRD PART Y APPROV ED (1) for indoor units installed at minimum 1.8m height and above the lowest underground floor. Overview of application surface in function of applied measures under IEC60335-2-40 (Ed.6) , considering units are installed at minimum 1.8m height and above the lowest underground floor. Daikin solution 16.0 Total Refrigerant Charge (kg) 14.0 DAIKIN SOLUTION : 2 MEASURES FACTORY-MOUNTED 12.0 Area 3 10.0 Reaction time of Daikin VRV 5 system Area 2 Application area without any measures 8.0 6.5 6.0 Extended application area of VRV 5 Highly increased flexibility thanks to factory-mounted measures 4.0 2.0 0.0 Area 1: no additional measures required under IEC60335-2-40 Ed.6 39 10.0 60 80 UNIQUE IN THE MARKET Refrigerant charge for a typical mini VRV installation with 90~110m pipe length 100 Minium room surface (m2) The representation above is Daikin’s interpretation of IEC60335-2-40 (Ed.6) and has no intention to replace in anyway existing legislation. Possible measures towards flammability ʯ Manufacturers have the choice to implement zero, one or two measures ʯ 3 types of measures are allowed: • Ventilation (natural or mechanical) • Shut-off valves DAIKIN SOLUTION, UNIQUE IN THE MARKET • Alarm (local and maybe central) The most flexible solution by Daikin ʯ The most flexible solution: two measures, system integrated • No additional costs or calculations needed to implement measures in the field • No hassle or additional time needed when installing • No risk in errors thanks to Xpress selection software ʯ Third party tested and approved THIRD PART Y APPROV ED 36 NEW RXYSA-AV1/AY1 VRV 5 S-series 460 mm 1.100 mm Lower CO2 equivalent and market-leading flexibility 869mm RXYSA-AV/AY1 level difference between indoor units 869mm high! 300 m total piping length Access all technical information on RXYSA-AV1 at my.daikin.eu or click here ErP 2021 CO COMPLIANT Already fully compliant to LOT 21 - Tier 2 Reduced CO2 equivalent Like-for-like R-410A installation flexibility Access all technical information on RXYSA-AY1 at my.daikin.eu or click here Outdoor unit Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. Recommended combination Only 120 m longest pipe length 40 m longest length after first branch 15 m 50 m level difference between indoor and outdoor units ʯ Reduced CO2 equivalent thanks to the use of lower GWP R-32 refrigerant and lower refrigerant charge ʯ Top sustainability over the entire lifecycle, thanks to market leading real-life seasonal efficiency ʯ Low-height single fan range ʯ Easy to transport thanks to lightweight and compact design ʯ Wide access area to easily reach all key components ʯ Offering like-for-like R-410A flexibility ʯ Specially designed indoor units for R-32, ensuring low sound and maximum efficiency HP kW kW kW 6°CWB RXYSA4AV1 4 12.1 8.4 14.2 RXYSA5AV1 5 14.0 9.7 16.0 RXYSA6AV1 6 15.5 10.7 18.0 RXYSA4AY1 4 12.1 8.4 14.2 3xFXSA25A2VEB + 4xFXSA32A2VEB 2xFXSA32A2VEB 3xFXSA25A2VEB 1xFXSA32A2VEB + 2xFXSA40A2VEB + 1xFXSA32A2VEB % 324.5 306.1 301.0 312.5 % 200.5 185.7 183.6 193.1 ηs,c ηs,h Published data with real-life indoor units RXYSA5AY1 5 14.0 9.7 16.0 RXYSA6AY1 6 15.5 10.7 18.0 4xFXSA32A2VEB 2xFXSA32A2VEB + 2xFXSA40A2VEB 294.8 178.8 289.9 176.8 7.3 SEER 8.2 7.7 7.6 7.9 7.4 SCOP 5.1 4.7 4.7 4.9 4.5 4.5 13 (1) 16 (1) 18 (1) 13 (1) 16 (1) 18 (1) Min. 50 62.5 70 50 62.5 70 Nom. 100 125 140 100 125 140 130 162.5 182 130 162.5 182 Maximum number of connectable indoor units Indoor index connection Dimensions Weight Max. Unit Unit HeightxWidthxDepth mm kg Sound power level Cooling Nom. dBA 67 68.1 69 67 68.1 69 Heating Nom. dBA 68 69.2 70 68 69.2 70 Heating According to ENER LOT21 57 59 60 57 59 60 Cooling Nom. dBA 49 51 51 49 51 51 Heating Nom. dBA 50 52 52 50 52 52 Cooling Heating Type/GWP Charge Liquid Gas Total piping length Min.~Max. Min.~Max. Sound pressure level Operation range Refrigerant Piping connections OD OD system Height Difference OU-IU Power supply Current - 50Hz Phase/Frequency/Voltage Maximum fuse amps (MFA) 869x1,100x460 102 °CDB °CWB Actual -5.0 ~ 46.0 -20.0 ~ 16 R-32/675 3.40 / 2.30 9.52 15.9 300 kg/TCO2Eq mm mm m Outdoor unit in highest position m 50 Indoor unit in highest position m 40 Hz/V A 1~/50/220-240 32 3~/50/380-415 16 (1) Actual number of units depends on the indoor unit type and the connection ratio restriction for the system (being 50% <= 130%) 37 The most comfortable cassette just got better New round flow cassette › Bigger louvers and new sensor logic further improves equal air distribution in the room › Widest ever choice in panels for cassette units, with up to 8 different panels Black auto cleaning panel Black designer panel Full white standard panel White designer panel › Comes with the known benefits: 360° air flow discharge and intelligent sensors presence sensor floor sensor › Auto cleaning panels available in black and white Auto cleaning filter Dust can simply be removed using a vacuum cleaner without opening the unit. * Available as an option 38 NEW FXFA-A Round flow cassette 360° air discharge for optimum efficiency and comfort ʯ Optimised design for R-32 refrigerant ʯ Optional automatic filter cleaning results in higher efficiency & comfort and lower maintenance costs. ʯ Two optional intelligent sensors improve energy efficiency and comfort ʯ Widest choice ever in decoration panels: Designer, standard and autocleaning panels in white (RAL9010) and black (RAL9005) ʯ Bigger louvers and unique swing pattern improve equal air distribution ʯ Individual louver control: flexibility to suit every room layout without changing the location of the unit! ʯ Lowest installation height in the market: 214mm for class 20-63 ʯ Optional fresh air intake ʯ Branch duct discharge allows to optimize air distribution in irregular shaped rooms or to supply air to small adjacent rooms FXFA-A NEW BRC1H52W BRP069C51 Main unit Branch discharge Main discharge ʯ Standard drain pump with 675mm lift increases flexibility and installation speed White panel White auto cleaning panel Black panel Black design panel Access all technical information on FXFA-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Dimensions Weight Casing Decoration panel Fan Total capacity Total capacity Cooling Heating Unit Unit Material Model at high fan speed at high fan speed at high fan speed at high fan speed HeightxWidthxDepth Dimensions Weight Air flow rate 50Hz HeightxWidthxDepth Air filter Type Sound power level Cooling Sound pressure level Cooling Heating Refrigerant Type/GWP Piping connections Power supply Current - 50Hz Control systems Cooling At high fan speed Heating At high fan speed At high fan speed L/ML/M/MH/H L/ML/M/MH/H Liquid OD Gas OD Drain Phase/Frequency/Voltage Maximum fuse amps (MFA) (1) Infrared remote control Wired remote control FXFA kW kW kW kW mm kg mm kg m³/min m³/min dBA dBA dBA mm mm Hz/V A 20A 2.20 2.50 25A 2.80 3.20 32A 3.60 4.00 0.04 0.04 40A 4.50 5.00 50A 5.60 6.30 0.05 0.05 204x840x840 19 63A 7.10 8.00 0.06 0.06 80A 100A 125A 9.00 11.20 14.00 10.00 12.50 16.00 0.09 0.12 0.19 0.09 0.12 0.19 288x840x840 246x840x840 18 21 24 26 Galvanised steel plate Standard panels: BYCQ140E - white with grey louvers / BYCQ140EW - full white / BYCQ140EB - black Auto cleaning panels BYCQ140EGF - white / BYCQ140EGFB - black Designer panels: BYCQ140EP - white / BYCQ140EPB - black Standard panels: 65x950x950 / Auto cleaning panels: 148x950x950 / Designer panels: 106x950x950 Standard panels: 5.5 / Auto cleaning panels: 10.3 / Designer panels: 6.5 12.8 14.8 15.1 16.6 23.3 28.8 33.0 12.8 14.8 15.1 16.6 23.3 28.8 33.0 Resin net 49 (4) 51 (4) 53 (4) 55 (4) 60 (4) 61 (4) 31/30/29/29.5/28 (4) 33 / 32 / 31 /30 / 29 (4) 35 / 34 / 33/32/30 (4) 38/ 36 /34 /32/30 (4) 43/41/37/34 /30 (4) 45/43/41/39 /36 (4) 31/30/29/29.5/28 (4) 33 / 32/31 /30 /29 (4) 35 / 34 / 33 / 32/30 (4) 38/ 36 /34 /32 /30 (4) 43/41/37/34 /30 (4) 45/43/41/39 /36 (4) R-32 / 675 6.35 9.52 12.7 VP25 (O.D. 32 / I.D. 25) 1~/50/60/220-240/220 6 BRC7FA532F (2) BRC1H52W/S/K 9.52 15.9 (1) MFA iswith used to select the remote circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing (2) Must be combined Madoka wired controller. (3) are panel: the different (4) L/ML/M/MH/H Sound of designer +3dB fan speeds availble. L= low; ML= medium low; M= medium; MH= medium high; H= high 39 40 NEW FXZA-A Fully flat cassette Unique design in the market that integrates fully flat into the ceiling ʯ Optimised design for R-32 refrigerant ʯ Fully flat integration in standard architectural ceiling tiles, leaving only 8mm ʯ Remarkable blend of iconic design and engineering excellence with an elegant finish in white or a combination of silver and white ʯ Two optional intelligent sensors improve energy efficiency and comfort ʯ 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc. ʯ Individual louver control: flexibility to suit every room layout without changing the location of the unit! FXZA-A NEW BRC1H52W BRP069C51 ʯ Optional fresh air intake ʯ Standard drain pump with 630mm lift increases flexibility and installation speed Access all technical information on FXZA-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Dimensions Weight Casing Decoration panel Decoration panel 2 Decoration panel 3 Decoration panel 4 Fan Total capacity Total capacity Cooling Heating Unit Unit Material Model Colour Dimensions Weight Model Colour Dimensions Weight Model Colour Dimensions Weight Model Colour Dimensions Weight Air flow rate 50Hz Air filter Type Sound power level Cooling Sound pressure level Cooling Heating Refrigerant Type/GWP Piping connections Liquid Power supply Current - 50Hz Control systems Dimensions At high fan speed At high fan speed At high fan speed At high fan speed HeightxWidthxDepth FXZA kW kW kW kW mm kg HeightxWidthxDepth mm kg HeightxWidthxDepth mm kg HeightxWidthxDepth mm kg HeightxWidthxDepth mm kg Cooling At high fan speed Heating At high fan speed m³/min m³/min At high fan speed Low/medium/high fan speed Low/medium/high fan speed dBA dBA dBA OD mm Gas OD Drain Phase/Frequency/Voltage Maximum fuse amps (MFA) Infrared remote control Wired remote controldo mm Hz/V A not 15A 1.70 1.90 20A 2.20 2.50 0.043 0.043 25A 2.80 3.20 32A 3.60 4.00 0.045 0.045 40A 4.50 5.00 0.059 0.059 50A 5.60 6.30 0.092 0.092 260x575x575 15.5 16.5 18.5 Galvanised steel plate BYFQ60C2W1W White (N9.5) 46x620x620 2.8 BYFQ60C2W1S SILVER 46x620x620 2.8 BYFQ60B2W1 White (RAL9010) 55x700x700 2.7 BYFQ60B3W1 WHITE (RAL9010) 55x700x700 2.7 8.5 8.5 8.7 8.7 9.0 9.0 Resin net 50 51 25.5/30.0/33.0 26.0/30.0/33.5 25.5/30.0/33.0 26.0/30.0/33.5 R-32 / 675 6.35 49 25.5/28.0/31.5 25.5/28.0/31.5 10.0 10.0 25.5/29.5/32.0 25.5/29.5/32.0 11.5 11.5 14.0 14.0 54 28.0/32.0/37.0 28.0/32.0/37.0 60 33.0/40.0/43.0 33.0/40.0/43.0 9.52 12.7 VP20 (I.D. 20/O.D. 26) 1~/50/60/220-240/220 6 BRC7EB530W (standard panel) / BRC7F530W (white panel) / BRC7F530S (grey panel) (1) BRC1H52W/S/K include control box (1) Must be combined with Madoka wired remote controller. 41 Auto cleaning filter for concealed ceiling units The unique automatic cleaning filter achieves higher efficiency and comfort with lower maintenance costs airflow direction Reduce running costs › Automatic filter cleaning ensures low maintenance costs because the filter is always clean UNIQUE Patents pending Efficiency profile change for duct indoor unit during operation Up to 20% 100% Energy saved Gradual loss of thanks to efficiency due automatic filter to dirty filter cleaning 0% start 6 months 12 months Minimal time required for filter cleaning › The dust box can be emptied with a vacuum cleaner for fast and easy cleaning › No more dirty ceilings Improved indoor air quality › Optimum airflow eliminates draft and insulates sound How does it work? › Prevents clogged filters for seamless operation 1 Scheduled automatic filter cleaning › Unique and innovative filter technology inspired by the Daikin auto cleaning cassette 2 Dust collects in a dust box that’s integrated into the unit Superb reliability Unique technology 3 The dust can easily be removed with a vacuum cleaner Combination table BAE20A62 www.youtube.com/DaikinEurope Split / Sky Air VRV FDXM-F9 FXDA-A/FXDQ-A3 25 35 50 60 BAE20A82 BAE20A102 42 15 20 25 32 Specifications 40 50 BAE20A62 63 Heigth (mm) Width (mm) Depth (mm) BAE20A82 BAE20A102 210 830 1,030 188 1,230 NEW FXDA-A Slim concealed ceiling unit rear suction Slim design for flexible installation ʯ Optimised design for R-32 refrigerant ʯ 10 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc. ʯ Compact dimensions, can easily be mounted in a ceiling void of only 240mm outblow bottom suction SERIE A (15, 20, 25, 32) FXDA-A 200 mm NEW 700 mm 50 mm ʯ Medium external static pressure up to 44Pa facilitates unit use with flexible ducts of varying lengths ʯ Discretely concealed in the wall: only the suction and discharge grilles are visible ʯ Optional auto cleaning filter option ensures maximum efficiency, comfort and reliability by regular filter cleaning ʯ Flexible installation, as the air suction direction can be altered from rear to bottom suction BRC1H52W BRP069C51 ʯ Standard drain pump with 600mm lift increases flexibility and installation speed Access all technical information on FXDA-A at my.daikin.eu or click here Access all technical information on BAE20A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Total capacity Total capacity Cooling Heating At high fan speed At high fan speed At high fan speed At high fan speed Required ceiling void > Dimensions Unit HeightxWidthxDepth Weight Unit Casing Material Air flow rate - 50Hz Cooling At high fan speed Fan External static Factory set/High pressure - 50Hz Air filter Type Sound power level Cooling At high fan speed Low/Medium/High fan speed Sound pressure level Cooling Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control NEW FXDA kW kW kW kW mm mm kg m³/min Pa dBA dBA mm mm Hz/V A 10A 1.10 1.30 0.042 0.042 Auto cleaning filter option 15A 1.70 1.90 0.057 0.057 20A 2.20 2.50 25A 2.80 3.20 0.068 0.068 32A 3.60 4.00 40A 4.50 5.00 0.075 0.075 50A 5.60 6.30 0.096 0.096 63A 7.10 8.00 0.107 0.107 240 200x750x620 22.0 5.2 200x950x620 26.0 Galvanised steel 8.0 6.5 10.5 12.5 15/44.0 16.5 52 28.0/32.0/34.0 53 29.0/33.0/35.0 54 30.0/34.0/36.0 10/30.0 48 26 / 28 / 29 Removable / washable 51 27.0/31.0/33.0 R-32 / 675 6.35 50 27.0/31.0/32.0 9.52 200x1,150x620 29.0 12.7 VP20 (I.D. 20/O.D. 26) 1~/50/60/220-240/220 6 BRC4C65 / BRC4C66 (1) BRC1H52W/S/K (1) Must be combined with Madoka wired remote controller. 43 NEW FXSA-A Concealed ceiling unit with medium ESP Slimmest yet most powerful medium static pressure unit on the market outblow rear suction ʯ Optimised design for R-32 refrigerant ʯ Slimmest unit in class, only 245mm (300mm built-in height) and therefore narrow ceiling voids are no longer a challenge bottom suction FXSA-A NEW 245 mm ʯ Quiet operation: down to 25dBA sound pressure level ʯ Medium external static pressure up to 150Pa facilitates using flexible ducts of varying lengths ʯ Possibility to change ESP via wired remote control allows optimisation of the supply air volume ʯ Discretely concealed in the wall: only the suction and discharge grilles are visible ʯ 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc. ʯ Optional fresh air intake ʯ Flexible installation: air suction direction can be altered from rear to bottom suction and choice between free use or connection to optional suction grilles ////////////////////////////////////////// For free use into a false ceiling ////////////////////////////////////////// BRC1H52W BRP069C51 ʯ Standard built-in drain pump with 625mm lift increases flexibility and installation speed ////////////////////////////////////////// For connecting onto a suction canvas (not supplied by Daikin) For direct connection to Daikin panel (via EKBYBSD kit) External static pressure (Pa) Automatic Airflow Adjustment function Automatically selects the most appropriate fan curve to achieve the units’ nominal air flow within ±10% Fan characteristic curves Air flow (rated) Why? Air flow (actual) After installation the real ducting will frequently differ from the initially calculated air flow resistance the real air flow may be much lower or higher than nominal , leading to a lack of capacity or uncomfortable air temperature Automatic Airflow Adjustment function will adapt the unit’s fan speed to any ducting automatically (10 or more fan curves are a­ vailable on every model), making installation much faster Air flow (with automatic adjustment) Duct resistance curves ± Air flow (m3/min) Access all technical information on FXSA-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Total capacity Total capacity At high fan speed At high fan speed Power input - 50Hz Cooling At high fan speed Heating At high fan speed Dimensions Unit HeightxWidthxDepth Weight Unit Casing Material Fan Air flow rate Cooling At high fan speed 50Hz Heating At high fan speed External static Factory set/High pressure - 50Hz Air filter Type Sound power level Cooling At high fan speed Sound pressure level Cooling Low/Medium./High Heating Low/Medium/High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control (1) Must be combined with Madoka wired remote controller. 44 FXSA kW kW 15A 1.70 1.90 kW kW mm kg m³/min m³/min Pa Hz/V A 25A 2.80 3.20 0.086 0.086 245x550x800 23.5 8.7 8.7 dBA dBA 25.0/28.0/29.5 dBA 26.0/29.0/31.5 mm mm 20A 2.20 2.50 32A 3.60 4.00 24.0 9.0 9.0 9.5 9.5 30/150 54 25.0/28.0/30.0 26.0/29.0/32.0 55 26.0/29.0/31.0 27.0/30.0/33.0 9.52 40A 4.50 5.00 50A 5.60 6.30 63A 7.10 8.00 80A 9.00 10.0 100A 11.20 12.5 125A 14.00 16.0 140A 16.00 18.0 0.147 0.150 0.183 0.209 0.285 0.326 0.382 0.147 0.150 0.183 0.209 0.285 0.326 0.382 245x1,550x800 245x700x800 245x1,000x800 245x1,400x800 28.5 29.0 35.5 36.5 46.0 47.0 51.0 Galvanised steel plate 36.0 39.0 15.0 15.2 21.0 23.0 32.0 15.0 15.2 21.0 23.0 32.0 36.0 39.0 40/150 50/150 Resin net 60 59 61 64 29.0/32.0/35.0 27.0/30.0/33.0 29.0/32.0/35.0 31.0/34.0/36.0 33.0/36.0/39.0 34.0/38.0/41.5 29.0/34.0/37.0 28.0/32.0/35.0 30.0/34.0/37.0 31.0/34.0/37.0 33.0/37.0/40.0 34.0/38.5/42.0 R-32 / 675 6.35 9.52 12.7 15.9 VP20 (I.D. 20/O.D. 26), drain height 625 mm 1~/50/60/220-240/220 6 BRC4C65 (1) BRC1H52W/S/K NEW FXAA-A Wall mounted unit For rooms with no false ceilings nor free floor space ʯ Optimised design for R-32 refrigerant ʯ Flat, stylish front panel blends easily within any interior décor and is easier to clean ʯ Can easily be installed in both new and refurbishment projects ʯ The air is comfortably spread up- and downwards thanks to 5 different discharge angles that can be programmed via the remote control ʯ Maintenance operations can be performed easily from the front of the unit FXAA-A NEW BRC1H52W BRP069C51 Access all technical information on FXAA-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Total capacity Total capacity Cooling Heating Dimensions Unit Weight Unit Fan Air flow rate 50Hz Air filter Type Sound power level Cooling Sound pressure level Cooling Heating Refrigerant Type/GWP Piping connections Power supply Current - 50Hz Control systems At high fan speed At high fan speed At high fan speed At high fan speed HeightxWidthxDepth Cooling Low/High fan speed At high fan speed Low/High fan speed Low/High fan speed Liquid OD Gas OD Drain Phase/Frequency/Voltage Maximum fuse amps (MFA) Infrared remote control Wired remote control FXAQ kW 15A 1.7 kW kW kW mm kg m³/min 1.9 dBA dBA dBA mm mm Hz/V A 20A 2.2 25A 2.8 2.5 3.2 0.02 7.0/8.4 51.0 28.5/32.0 28.5/33.0 32A 3.6 40A 4.5 50A 5.6 63A 7.1 4.0 0.04 5.0 0.02 0.02 8.0 0.05 0.06 7.0/9.8 9.7/12.2 6.3 0.03 0.04 290x1,050x269 15 11.5/14.4 13.5/18.3 58.0 35.5/41.0 35.5/42.0 63.0 38.5/46.5 38.5/47.0 0.03 0.03 290x795x266 12 7.0/9.1 7.0/9.4 52.0 28.5/33.0 28.5/34.0 53.0 28.5/35.0 28.5/36.0 Washable resin net 55.0 28.5/37.5 33.5/37.0 28.5/38.5 33.5/38.0 R-32 / 675 6.35 9.52 12.7 VP13 (I.D. 15/O.D. 18) 1~/50/220-240 6 BRC7EA628 / BRC7EA629 (1) BRC1H52W/S/K (1) Must be combined with Madoka wired remote controller. *Note: blue cells contain preliminary data 45 VRV IV Outdoor Systems For every application a solution 46 VRV Outdoor units Widest range of BS boxes VRV IV S-series (compact) VRV IV i-series VRV IV C+series RXYSA-AV1 RXYSA-AY1 REYQ-U RYYQ-U RXYQ-U RXYSCQ-TV1 RXYSQ-TV9 RXYSQ-TY9 RXYSQ-TY1 SB.RKXYQ-T (8) RXYLQ-T RQCEQ-P3 RQYQ-P RXYQQ-U RWEYQ-T9 37 56 64 72 82 86 92 93 104 RXYQQ-U only Continuous heating alternate defrost RYYQ-U (unique heat accumulating element) Connectable to stylish indoor units (Daikin Emura, Nexura) Connectable to LT hydrobox for hot water Connectable to HT hydrobox for hot water Gas cooled PCB 7 segment display Automatic refrigerant charge Refrigerant containment check Night quiet mode Low noise function Reluctance brushless DC compressor Sine wave DC inverter DC fan motor E-pass heat exchanger I demand function Manual demand function / power limitation Increased capacity! Unique product VRV IV+ heat pump (with continuous heating) Variable Refrigerant Temperature VRV configurator Widest range VRV IV+ Heat recovery VRV 5 Page Unique continuous heating Inculding shut off valves in case a leak is detected during operation (1) Either connect VRV or stylish indoor units RXYSQ-TV9/ TY9 only Replacement Replacement VRV III VRV IV+ Heat heat pump recovery VRV IV W+series - alternate defrost alternate defrost alternate defrost - (1) not available on RXYSQ4,5,6,8TY1 - - 47 Outdoor units Products overview VRVIV-S series Compact UNIQUE VRVIV-S series Air cooled - heat pump NEW Daikin’s optimum solution with top comfort Continuous heating during defrost Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, hot water, air handling units and Biddle air curtains › Connectable to stylish indoor units (Daikin Emura, Nexura) › Incorporates VRV IV standards & technologies such as Variable Refrigerant temperature and continuous heating › › Daikin’s solution for comfort & low energy consumption Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, hot water, air handling units and Biddle air curtains › Connectable to stylish indoor units (Daikin Emura, Nexura) › Incorporates VRV IV standards & technologies such as Variable Refrigerant temperature 5 6 The most compact VRV › Compact and lightweight single fan design saves space and is easy to install › Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, air handling units and Biddle air curtains › Either connect VRV of stylish indoor units (Daikin Emura, Nexura) › Incorporates VRV IV standards & technologies such as Variable Refrigerant temperature Space saving solution without compromising on efficiency Space saving trunk design for flexible installation Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, air handling units and Biddle air curtains › Either connect VRV of stylish indoor units (Daikin Emura, Nexura) › Incorporates VRV IV standards & technologies such as Variable Refrigerant temperature › › VRV IV heat pump, optimised for cold climates heat recovery › › › › heat pump The invisible VRV › Unique VRV heat pump for indoor installation › Total flexibility for any shop location and building type as the outdoor unit is invisible and split up in 2 parts › Incorporates VRV IV standards & technologies such as Variable Refrigerant temperature › Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation and Biddle air curtains › › › › › Where heating is priority without compromising on efficiency Suitable for single source heating Extended operation range down to -25°C in heating Stable heating capacity without any capacity loss down to -15°C Very economical solution as a smaller outdoor unit model can be used compared to the standard series Quick & quality replacement for R-22 and R-407C systems Cost-effective and fast replacement through re-use of exisiting piping Drastically improve your comfort, efficiency and reliability No interuption of daily business while replacing your system Replace Daikin and other manufacturers systems safely Quick & quality replacement for R-22 and R-407C systems Cost-effective and fast replacement through re-use of exisiting piping Drastically improve your comfort, efficiency and reliability No interuption of daily business while replacing your system Replace Daikin and other manufacturers systems safely Incorporates VRV IV standards & technologies such as Variable Refrigerant temperature Ideal for high rise buildings, using water as heat source › Reduced CO2 emissions thanks to the use of geothermal energy as a renewable energy source › No need for an external heating or cooling source when used in geothermal mode › Compact & lightweight design can be stacked for maximum space saving › Incorporates VRV IV standards & technologies such as Variable Refrigerant temperature › Variable Water Flow control option increases flexibility and control › Mixed connection of HT hydroboxes and VRV indoor units › Either connect VRV of stylish indoor units (Daikin Emura, Nexura › 2 analogue input signals allowing external control 8 10 12 13 14 16 18 20 22 24 26 28 30 REYQ-U RYYQ-U RXYQ-U RXYSCQ-TV1 Compact RXYSQT8V/ T8Y/TY1 T8V T8Y/ TY1 SB.RKXYQ-T(8) RXYLQ-T RQCEQ-P3 RXYQQ-U RWEYQ-T9* Ranges marked with '*' are not Eurovent certified. Multi combinations are not in scope of the Eurovent certification programme 48 4 › › › › › Water cooled VRV IV Water cooled Replacement VRV IVheat pump for indoor installation UNIQUE Product name Best efficiency & comfort solution › Fully integrated solution with heat recovery for maximum efficiency › Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, hot water, air handling units and Biddle air curtains › “Free” heating and hot water through heat recovery › The perfect personal comfort for guests/tenants via simultaneous cooling and heating › Incorporates VRV IV standards & technologies such as Variable Refrigerant temperature and continuous heating › Allows technical cooling › Widest range of BS boxes on the market NEW VRV IV heat recovery UNIQUE VRV IV heat pump VRV IV heat pump without continuous with continuous heating heating Air cooled - heat recovery Model Single unit Multi combination with LT Hydroboxes AHU connection EKEXV + EKEQMCBA Biddle air curtain CYV-DKVRV IV Heat Pump RYYQ-T(8) / RXYQ-T(9) + HRV units VAM-, VKMAHU connection EKEXV + EKEQMCBA Air curtains CYV-DK- › › › › › › › › › › Biddle air curtain CYV-DK- VRV IV-S RXYSQ-/RXYSCQ- O O O › with VRV indoor units only VRV IV i series SB.RKXYQ-T(8) › O O O O › VRV III-Q+ series Replacement H/R RQCEQ-P3 O O O O O O › VRV IV-Q Replacement H/P RXYQQ-T O O O O VRV IV-W+ series Water-cooled VRV RWEYQ-T9 O › ›› ›› › › with residential indoor units only with LT hydroboxes AHU connection EKEXV + EKEQMCBA with VRV indoor units with split indoor units with HT hydrobox AHU connection Max 32 indoor units, even on 16HP and larger systems Total system connection ratio with HT hydroboxes up to 200% possible Dedicated systems (with only ventilation units) not allowed – a mix with standard VRV indoor units is allways neccessary Total system connection ratio with AHU is 50 ~ 110% Standard total system connection ratio limit: 50 ~ 130% 200% total system connection ratio possible under special circumstances Only single-module systems (RYYQ 8~20 T / RXYQ 8~20 T) Max 32 indoor units, even on 16HP, 18HP and 20HP systems Connection ratio: 80 ~ 130% Max 32 indoor units, even on 16HP and larger systems Contact Daikin in case of multi-module systems (>20HP) Total system connection ratio with AHU is 50 ~ 110% Standard total system connection ratio limit: 50 ~ 130% AHU connection EKEXV + EKEQFCBA with VRV indoor units only Standard total system connection ratio limit: 50 ~ 130% O › › › › › VRV IV-C+ series RXYLQ-T › › Remarks › AHU connection EKEXV + EKEQFCBA with residential indoor units only AHU connection EKEXV- + EKEQMCBA AHU connection EKEXV- + EKEQFCBA HRV units VAM-, VKM- HRV units VAM-, VKM- with LT/HT Hydroboxes HT Hydrobox HXHD-A with residential indoor units with only VRV indoor units Residential indoor units with only VRV indoor units O O O VRV IV+ Heat Recovery REYQ-T LT Hydrobox HXY-A Capacity (HP) 32 34 36 38 40 42 44 46 48 50 52 54 Description / Combination VRV indoor units Outdoor units › With residential indoor: connection ratio limit: 80 ~ 130% Standard total system connection ratio limit: 50 ~ 130% Standard total system connection ratio limit: 70 ~ 130% With residential indoor: connection ratio limit: 80 ~ 130% Max. 32 indoor units, contact Daikin in case of multi-module systems (> 14HP) Total system connection ratio is 70~110% With AHU only connection ration is 90~110% Standard total system connection ratio limit: 50 ~ 130% Standard total system connection ratio limit: 50 ~ 130% Standard total system connection ratio limit: 50 ~ 130% Only single-module systems (RWEYQ8-14T9) Max 32 indoor units Connection ratio: 80 ~ 130% only in heat pump version Total system connection ratio with AHU + X indoor is 50 ~ 110% Total system connection ration with AHU only is 90~ 110% ... connection of indoor unit possible, but not neccessarily simultaneously with other allowed indoor units ... connection of indoor unit possible even simultaneously with other checked units in the same row O ... connection of indoor not possible on this outdoor unit system 49 VRV Outdoor L∞P BY DAIKIN VRV IV+ HEAT RECOVERY PARK PHI BREEAM EXCELLENT OFFICE BUILDING WATERCOOLED VRV VRV IV i-SERIES VRV IV HEAT PUMP FOR INDOOR INSTALLATION 50 VRV Outdoor HOTEL LE PIGONNET, 8 REPLACEMENT VRV L∞P BY DAIKIN VRV IV S-SERIES BASTIDE ROUGE, OFFICE BUILDING, VRV IV WITH CONTINUOUS HEATING 51 VRV IV heat recovery + Best efficiency and comfort solution Efficient 3-pipe Air curtain 22 Biddle Air curtain for VRV (CYV) system Indoor units VRV type indoor units Hot water Low temperature hydrobox High temperature hydrobox Control systems Ventilation Heat Reclaim ventilation (ALB/VAM/VKM) AHU connection kit Widest range of BS boxes for the fastest installation › 7 segment display › Automatic refrigerant charge › Refrigerant containment check › Night quiet mode › Low noise function › Connectable to LT hydrobox for hot water VRV IV standards: Variable refrigerant temperature Customize your VRV for best seasonal efficiency & comfort Continuous heating The new standard in heating comfort VRV configurator Software for simplified commissioning, configuration and customisation 52 › Connectable to HT hydrobox for hot water › Full inverter compressors › Gas cooled PCB › 4 side heat exchanger › Reluctance brushless DC compressor › Sine wave DC inverter › DC fan motor › E-pass heat exchanger › I demand function › Manual demand function Innovation in detail L∞P by Daikin Make a positive choice and reuse refrigerant to avoid more than 150,000 kg of virgin gas being produced each year. Insprired to help? Find out more about Daikin’s initiatives to build a circular economy of refrigerants: www.daikin.eu/building-a-circular-economy “Free” heat and hot water production Cooling An integrated heat recovery system reuses heat from offices, server rooms, to warm other areas or create hot water. North Extracted heat delivers free hot water and heating Maximum comfort A VRV heat-recovery system allows simultaneous cooling and heating. › For hotel owners, this means a perfect environment for guests as they can freely choose between cooling or heating. › For offices, it means a perfect working indoor climate for both north and south-facing offices. Hot water + Heating South 53 Advantages of 3-pipe technology Efficient 3-pipe system More “free” heat 5 to 15% more efficient in heat recovery mode compared to 2-pipe Pressure system Daikin 3-pipe technology needs less energy to recover heat, meaning significantly higher efficiency during heat recovery mode. Our system can recover heat at a low condensing temperature because it has dedicated gas, liquid and discharge pipes. Condensing 55 °C Condensing 45 °C In a 2-pipe system, gas and liquid travel as a mixture so the condensing temperature needs to be higher in order to separate the mixed gas and liquid refrigerant. The higher condensing temperature means more energy is used to recover heat resulting in lower efficiency. Power input Daikin Power input 2-pipe system Enthalpy Up to 5% more cooling capacity Lower pressure drop means more efficiency available at longer piping lengths compared to 2-pipe system Pressure › Smooth refrigerant flow in 3-pipe system thanks to 2 smaller gas pipes results in higher energy efficiency › Disturbed refrigerant flow in large gas pipe on 2-pipe system results in bigger pressure drop 3-pipe VRV H/R 2-pipe system Pipe length Maximum design flexibility and installation speed › Quickly and flexibly design your system with a Single port Multi port: 4 – 6 – 8 – 10 – 12 – 16 unique range of single and multi BS boxes. › A wide variety of compact and lightweight multi BS boxes greatly reduces installation time. › Free combination of single and multi BS boxes BS1Q 10,16,25A BS 4 Q14 A BS 10, 12 Q14 A 54 BS 6, 8 Q14 A BS 16 Q14 A Fully redesigned BS boxes Maximum design flexibility and installation speed › Quickly and flexibly design your system with a unique range of single and multi BS boxes. › A wide variety of compact and lightweight multi BS boxes greatly reduces installation time. › Free combination of single and multi BS boxes Single port › › › › › › › Unique to the market Compact and light to install No drain piping needed Ideal for remote rooms Technical cooling function Connect up to 250 class unit (28 kW) Allows multi-tenant applications BS1Q 10, 16, 25 A Multi port: 4 – 6 – 8 – 10 – 12 – 16 › Up to 55% smaller and 41% lighter than › › › › › › › previous range Faster installation thanks to a reduced number of brazing points and wiring All indoor units connectable to one BS box Fewer inspection ports needed Up to 16 kW capacity available per port Connect up to 250 class unit (28kW) by combining 2 ports No limit on unused ports, permitting phased installation Allows multi-tenant applications BS 4 Q14 AV1 BS 6, 8 Q14 AV1 BS 10, 12 Q14 AV1 BS 16 Q14 AV1 Faster installation thanks to open connection › No need to cut the pipe before brazing – for indoor units smaller or equal to 5.6 kW (50 class) › Cut and braze the pipe – for indoor units bigger or equal to 7.1 kW (63 class) Maximum comfort at all times With the VRV BS box, any indoor unit not being used to switch between heating and cooling maintains the constant desired temperature. This is because our heat recovery system does not need to equalise pressure over the entire system after a change-over. Off BS box 55 REYQ-U VRV IV+ heat recovery Best efficiency & comfort solution ʯ Fully integrated solution with heat recovery for maximum efficiency with COPs of up to 8 ! ʯ Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, hot water, air handling units and Biddle air curtains ʯ „Free“ heating and hot water production provided by transferring heat from areas requiring cooling to areas requiring heating or hot water ʯ The perfect personal comfort for guests/tenants via simultaneous cooling and heating ʯ Incorporates VRV IV standards & technologies: Variable Refrigerant Temperature, continuous heating, VRV configurator, 7 segment display and full inverter compressors, 4-side heat exchanger, refrigerant cooled PCB, new DC fan motor ʯ Outdoor unit display for quick on-site settings and easy read out of errors together with the indication of service parameters for checking basic functions. ʯ Free combination of outdoor units to meet installation space or efficiency requirements ʯ Wide piping flexibility: 30m indoor height difference, maximum piping length: 190m, total piping length: 1,000m ʯ Possibility to extend the operation range in cooling down to -20°C for technical cooling operation such as server rooms ʯ Contains all standard VRV features ErP 2021 COMPLIANT Already fully compliant to LOT 21 - Tier 2 Published data with real-life indoor units Access all technical information on REYQ-U at my.daikin.eu or click here Outdoor unit Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. 6°CWB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Dimensions Unit HeightxWidthxDepth Weight Unit Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type/GWP Charge Piping connections Liquid OD Gas OD HP/LP gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Outdoor unit System + Module System Outdoor unit module 1 Outdoor unit module 2 Capacity range Cooling capacity Prated,c Heating capacity Prated,h Max. 6°CWB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Piping connections Liquid OD Gas OD HP/LP gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) 56 REYQ HP kW kW kW % % 8U 8 22.4 13.7 25.0 286.1 165.1 7.2 4.2 10U 10 28.0 16.0 31.5 264.8 169.7 6.7 4.3 100.0 260.0 mm kg dBA dBA °CDB °CWB kg/TCO2Eq mm mm mm m Hz/V A REYQ HP kW kW kW % % mm mm mm m Hz/V A 78.0 12U 12 33.5 18.4 37.5 257.0 183.8 6.5 4.7 125.0 390.0 314 80.9 60.0 -5.0~43.0 -20.0~15.5 R-410A/2,087.5 83.4 61.0 9.8/20.5 18U 18 50.4 27.9 56.5 250.6 172.5 6.3 4.4 20U 20 52.0 31.0 63.0 246.7 162.7 6.2 4.1 200.0 225.0 250.0 520.0 585.0 1,685x1,240x765 650.0 317 85.6 63.0 9.9/20.7 83.8 62.0 87.9 65.0 11.8/24.6 9.52 19.1 15.9 16U 16 45.0 23.2 50.0 243.1 167.5 6.2 4.3 64 175.0 455.0 150.0 325.0 1,685x930x765 230 79.1 57.0 9.7/20.2 14U 14 40.0 20.6 45.0 255.8 168.3 12.7 22.2 15.9 28.6 22.2 19.1 28.6 1,000 20 3N~/50/380-415 32 25 10U 13U 16U 18U REMQ5U REYQ8U REMQ5U REYQ8U REYQ10U 10 13 16 18 28.0 36.4 44.8 50.4 16.0 21.7 23.2 27.9 32.0 41.0 50.0 56.5 275.1 301.3 288.6 272.9 158.8 160.6 168.2 167.9 7.0 7.6 7.3 6.9 4.0 4.1 4.3 125.0 163.0 200.0 225.0 325.0 9.52 22.2 423.0 520.0 585.0 12.7 28.6 19.1 22.2 500 40 50 20U 22U 24U 26U 28U 30U 32U REYQ10U REYQ8U REYQ12U REYQ16U REYQ12U REYQ16U REYQ14U REYQ16U REYQ18U REYQ16U 20 22 24 26 28 30 32 55.9 61.5 67.4 73.5 78.5 83.9 90.0 31.0 34.4 36.9 37.1 39.7 44.4 46.4 62.5 69.0 75.0 82.5 87.5 94.0 100.0 266.0 260.4 257.7 257.5 251.9 266.8 243.1 175.7 178.5 167.6 175.5 174.8 179.4 169.1 6.7 6.6 6.5 6.4 6.7 6.2 4.5 4.3 4.5 4.4 4.6 4.3 64 250.0 275.0 300.0 325.0 350.0 375.0 400.0 650.0 715.0 780.0 845.0 910.0 975.0 1,040.0 15.9 19.1 34.9 28.6 1,000 3N~/50/380-415 40 50 63 80 REYQ10,13,16,18,20,22U Liquid pipe Gas pipe Discharge gas pipe Hot water VRV indoor units 45°C - 75°C Daikin solar panel Domestic hot water 25°C - 75°C BS-Box Air handling unit Domestic hot water tank 45°C - 75°C BS-Box Low temp. radiator Heating only hydrobox for VRV VRV heat recovery Under floor heating 25°C - 35°C Outdoor unit System + Module System Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Capacity range Cooling capacity Prated,c Heating capacity Prated,h Max. 6°CWB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Piping connections Liquid OD Gas OD HP/LP gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) REYQ Outdoor unit module Dimensions Unit HeightxWidthxDepth Weight Unit Fan External static Max. pressure Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type/GWP Charge Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) REMQ mm kg Pa 5U 1,685x930x765 230 78 dBA dBA °CDB °CWB 78.0 57.0 -5.0~43.0 -20.0~15.5 R-410A/2,087.5 9.7/20.2 3N~/50/380-415 20 HP kW kW kW % % mm mm mm m Hz/V A kg/TCO2Eq Hz/V A 34U 36U 38U 40U 42U 44U 46U 48U REYQ16U REYQ8U REYQ10U REYQ12U REYQ14U REYQ18U REYQ20U REYQ12U REYQ16U REYQ18U REYQ16U 34 36 38 40 42 44 46 48 95.4 97.0 106.3 111.9 118.0 123.5 130.0 135.0 51.1 54.2 58.1 58.9 60.9 62.9 67.0 69.6 106.5 113.0 119.0 125.5 131.5 137.5 145.0 150.0 259.2 255.3 269.2 259.6 250.2 249.3 246.8 243.1 172.0 166.3 176.0 176.1 167.8 171.9 168.8 168.5 6.6 6.5 6.8 6.6 6.3 6.2 4.4 4.2 4.5 4.3 4.4 4.3 64 425.0 450.0 475.0 500.0 525.0 550.0 575.0 600.0 1,105.0 1,170.0 1,235.0 1,300.0 1,365.0 1,430.0 1,495.0 1,560.0 19.1 34.9 41.3 28.6 34.9 1,000 50U REYQ16U 50 140.4 74.3 156.5 254.4 170.3 6.4 52U 54U REYQ18U REYQ18U REYQ18U 52 54 145.8 151.2 79.0 83.7 163.0 169.5 265.7 275.2 171.7 173.3 6.7 7.0 4.4 625.0 650.0 675.0 1,625.0 1,690.0 1,755.0 3N~/50/380-415 80 Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system (50% ≤ CR ≤ 120%) 100 125 57 BS1Q-A Individual branch selector for VRV IV heat recovery ʯ Unique range of single and multi BS boxes for flexible and fast design ʯ Compact & light to install ʯ Ideal for remote rooms as no drain piping is needed ʯ Allows integration of server rooms into the heat recovery solution thanks to technical cooling function ʯ Connect up to 250 class unit (28kW) ʯ UNIQUE Faster installation thanks to open port connection ʯ Allows multi tenant applications ʯ Connectable to REYQ-T, RQCEQ-P3 and RWEYQ-T9 heat recovery units BS1Q-A Access all technical information on BS1Q-A at my.daikin.eu or click here Indoor unit Power input Cooling Nom. BS kW Heating Nom. kW Maximum number of connectable indoor units Unit Weight Unit Casing Material Piping connections Outdoor unit Indoor unit HeightxWidthxDepth 8 100<x≤160 160<x≤250 207x388x326 12 15 Galvanised steel plate Liquid OD mm Gas OD mm 15.9 Discharge gas OD mm 12.7 Liquid OD mm Gas OD mm 9.5 22.2 19.1 9.5 15.9 22.2 Foamed polyurethane Flame-resistant needle felt Phase Frequency 58 0.005 mm kg 1Q25A 0.005 15 < x ≤ 100 Sound absorbing thermal insulation Power supply 1Q16A 6 Maximum capacity index of connectable indoor units Dimensions 1Q10A 1~ Hz 50 Voltage V 220-240 Maximum fuse amps (MFA) A 15 BS-Q14AV1B Multi branch selector for VRV IV heat recovery ʯ Unique range of single and multi BS boxes for flexible and fast design ʯ Major reduction in installation time thanks to wide range, compact size and light weight multi BS boxes ʯ Up to 70% smaller and 66% lighter than previous series ʯ Faster installation thanks to a reduced number of brazing points and wiring ʯ All indoor units connectable to one BS box ʯ Less inspection ports needed compared to installing single BS boxes ʯ Up to 16kW capacity available per port ʯ Connect up to 250 class unit (28kW) by combining 2 ports ʯ No limit on unused ports allowing phased installation ʯ UNIQUE Faster installation thanks to open port connection ʯ UNIQUE Refrigerant filters for high reliability ʯ Allows multi tenant applications ʯ Connectable to REYQ-T, RQCEQ-P3 and RWEYQ-T9 heat recovery units BS6,8Q14AV1B Access all technical information on BS-Q14AV1B at my.daikin.eu or click here Indoor unit Power input Cooling Nom. Heating Nom. Maximum number of connectable indoor units Maximum number of connectable indoor units per branch Number of branches Maximum capacity index of connectable indoor units Maximum capacity index of connectable indoor units per branch Dimensions Unit HeightxWidthxDepth Weight Unit Casing Material Piping connections Outdoor unit Liquid OD Gas OD Discharge gas OD Indoor unit Liquid OD Gas OD Drain Sound absorbing thermal insulation Power supply Phase Frequency Voltage Maximum fuse amps (MFA) BS kW kW 4Q14AV1B 0.043 0.043 20 6Q14AV1B 0.064 0.064 30 8Q14AV1B 0.086 0.086 40 4 400 6 600 8 10Q14AV1B 0.107 0.107 50 12Q14AV1B 0.129 0.129 60 16Q14AV1B 0.172 0.172 64 12 16 5 10 750 140 mm kg 298x370x430 17 24 mm mm mm mm mm 9.5 22.2 / 19.1 19.1 / 15.9 12.7 28.6 / 22.2 19.1 / 22.2 Hz V A 298x580x430 298x820x430 26 35 38 Galvanised steel plate 12.7 / 15.9 15.9 15.9 / 19.1 28.6 28.6 / 34.9 19.1 / 22.2 / 28.6 28.6 9.5 / 6.4 15.9 / 12.7 VP20 (I.D. 20/O.D. 26) Urethane foam, polyethylene foam 1~ 50 220-440 15 298x1,060x430 50 19.1 34.9 59 VRV IV heat pump + Daikin’s optimum solution with top comfort Air curtain Biddle Air curtain for VRV (CYV) 22 Indoor units VRV type indoor units Residential type indoor units (such as Daikin Emura) Hot water Low temperature hydrobox (1) Control systems Ventilation Heat Reclaim ventilation (ALB/VAM/ VKM) AHU connection kit › 7 segment display › Automatic refrigerant charge › Refrigerant containment check › Night quiet mode › Low noise function › Connectable to stylish indoor units (Only for single modules) › Connectable to LT hydrobox (1) VRV IV standards: Variable refrigerant temperature Customize your VRV for best seasonal efficiency & comfort Continuous heating The new standard in heating comfort VRV configurator Software for simplified commissioning, configuration and customisation 60 › Full inverter compressors › Gas cooled PCB › 4 side heat exchanger › Reluctance brushless DC compressor › Sine wave DC inverter › DC fan motor › E-pass heat exchanger › I demand function › Manual demand function (1) Special order unit needed to connect LT hydroboxes with multi outdoor unit systems For detailed explanation of these functions refer to vrv iv technologies tab Wide range of indoor units Freely combine VRV indoor units with stylish indoor units (Daikin Emura, Nexura, …) Mix of RA units & VRV units FXSQ-A VRV indoor unit FXFQ-B VRV indoor unit FVXG-K Nexura Available for single outdoor unit systems only BPMKS967A2 FTXJ-MW/MS Daikin Emura Connectable stylish indoor units 20 CLASS Daikin Emura - Wall mounted unit Stylish - Wall mounted unit Nexura - Floor standing unit Floor standing unit 25 CLASS 35 CLASS 42 CLASS 50 CLASS FTXJ-MW/MS FTXA-AW/BS/BB/BT FVXG-K FVXM-F BPMKS box needed to connect RA indoors to VRV IV 61 VRV IV proven in practice: 40% more efficient A field trial at a German fashion chain store demonstrated how the innovative features of VRV IV have improved energy efficiency dramatically over previous models. Results: up to 60% less energy consumed The Unterhaching trial demonstrates how VRV IV heat pump technology uses a renewable energy source – air - to provide a complete and environmentally sustainable solution for heating, cooling, and ventilation in commercial environments. The trial also shows that businesses can only identify and control energy wastage through careful and intelligent monitoring of climate control systems, a service which Daikin can offer. The results of the trial showed that the new VRV IV system consumed much less energy, particularly when cooling, compared with the VRV III system – in some cases up to 60% less. When heating, savings were an average of 20%. Average daily consumption during working hours in kWh 220 210 200 190 180 170 160 150 140 130 120 110 100 90 80 Energy use VRV III in 2012 in kWh 70 60 Energy use VRV IV in 2013 in kWh 50 40 30 Trendline energy use VRV III 20 10 0 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Trendline energy use VRV IV Difference between average daily room temperature and outdoor temperature during opening hours VRV III 20HP (2 modules) VRV IV 18HP (1 module) March 2012 - February 2013 March 2013 - February 2014 Avg (kWh/Month) 2.797 1.502 Total (KWh) 33.562 18.023 Total (€) 6.041 3.244 9,9 5,3 Period Yearly (operation cost/m² (€/m²) 46% savings = € 2.797 62 Measured data Fashion store Unterhaching (Germany) › Floor space: 607m² › Energy cost: 0,18 €/kWh › System taken into account for consumption: - VRV IV heat pump with continuous heating - Round flow cassettes (without auto cleaning panel) - VAM for ventilation (2x VAM2000) - Biddle Air curtain. Free combination of outdoor units Freely combine outdoor units to optimise for small footprint, continuous heating, highest efficiency or any other combination Flexible piping design Total piping length 1000m Longest length actual (Equivalent) 165m (190m) Longest length after first branch 90m1 Level difference between indoor and outdoor units 90m1 Level difference between indoor units 30m 90m maximum 30m Level difference between indoor units 40m (90m1) Level difference between indoor and outdoor units 165m Actual piping length 1 Contact your local dealer for more information and restrictions 2 in case outdoor unit is located below indoor units 63 RYYQ-U / RXYQ-U VRV IV+ heat pump Daikin‘s optimum solution with top comfort ʯ Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, hot water, air handling units and Biddle air curtains ʯ Wide range of indoor units: possibility to combine VRV with stylish indoor units (Daikin Emura, Nexura, ...) ʯ Incorporates VRV IV standards & technologies: Variable Refrigerant Temperature, continuous heating, VRV configurator, 7 segment display and full inverter compressors, 4-side heat exchanger, refrigerant cooled PCB, new DC fan motor ʯ Outdoor unit display for quick on-site settings and easy read out of errors together with the indication of service parameters for checking basic functions. ʯ Free combination of outdoor units to meet installation space or efficiency requirements ʯ Available as heating only by irreversible field setting ʯ Contains all standard VRV features Up to 30m indoor unit height difference ErP 2021 COMPLIANT Already fully compliant Access all technical information on RYYQ-U at my.daikin.eu or click here to LOT 21 - Tier 2 Published data with real-life indoor units Access all technical information on RXYQ-U at my.daikin.eu or click here Outdoor unit Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. Recommended combination RYYQ/RXYQ HP kW kW kW 6°CWB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Dimensions Unit HeightxWidthxDepth Weight Unit Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type/GWP Charge Piping connections Liquid OD Gas OD Total piping length System Actual Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) % % 8U 8 22.4 13.7 25.0 4 x FXFQ50AVEB 10U 10 28.0 16.0 31.5 4 x FXFQ63AVEB 12U 12 33.5 18.4 37.5 6 x FXFQ50AVEB 302.4 167.9 7.6 267.6 168.2 6.8 247.8 161.4 4.3 100.0 260.0 mm kg dBA dBA °CDB °CWB kg/TCO2Eq mm mm m Hz/V A 78.0 125.0 150.0 325.0 390.0 1,685x930x765 252 (RYYQ) / 198 (RXYQ) 79.1 83.4 57.0 61.0 5.9/12.3 6.0/12.5 6.3/13.2 9.52 19.1 22.2 20 25 Outdoor unit System System Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Capacity range Cooling capacity Prated,c Heating capacity Prated,h Max. 6°CWB Recommended combination RYYQ/RXYQ HP kW kW kW 22 61.5 34.4 69.0 6 x FXFQ50AVEB + 4 x FXFQ63AVEB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Piping connections Liquid OD Gas OD Total piping length System Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) % % 64 4.1 22U 10 12 24U 8 16 26U 14U 16U 18U 20U 14 16 18 20 40.0 45.0 50.4 52.0 20.6 23.2 27.9 31.0 45.0 50.0 56.5 63.0 1 x FXFQ50AVEB 4 x FXFQ63AVEB 3 x FXFQ50AVEB 2 x FXFQ50AVEB + 5 x FXFQ63AVEB + 2 x FXFQ80AVEB + 5 x FXFQ63AVEB + 6 x FXFQ63AVEB 250.7 236.5 238.3 233.7 155.4 157.8 163.1 156.6 6.3 6.0 5.9 4.0 4.2 4.0 64 (1) 175.0 200.0 225.0 250.0 455.0 520.0 585.0 650.0 1,685x1,240x765 319 (RYYQ) / 275 (RXYQ) 378 (RYYQ) / 308 (RXYQ) 80.9 85.6 83.8 87.9 60.0 63.0 62.0 65.0 -5.0~43.0 -20.0~15.5 R-410A/2,087.5 10.3/21.5 10.4/21.7 11.7/24.4 11.8/24.6 12.7 15.9 28.6 1,000 3N~/50/380-415 32 40 50 28U 12 16 14 30U 18 - 26 73.5 39.0 82.5 7 x FXFQ50AVEB + 5 x FXFQ63AVEB 274.5 171.2 6.9 4.4 24 67.4 36.9 75.0 4 x FXFQ50AVEB + 4 x FXFQ63AVEB + 2 x FXFQ80AVEB 269.9 167.0 6.8 4.3 275.0 300.0 325.0 780.0 845.0 715.0 Actual mm mm m Hz/V A 264.2 164.6 6.7 28 30 78.5 83.9 41.6 46.3 87.5 94.0 6 x FXFQ50AVEB 9 x FXFQ50AVEB + 4 x FXFQ63AVEB + 5 x FXFQ63AVEB + 2 x FXFQ80AVEB 257.8 256.8 166.0 169.8 6.5 4.2 4.3 64 (1) 350.0 375.0 910.0 975.0 38U 8 16 20 10 20 32 34 36 38 90.0 95.4 97.0 102.4 46.4 51.1 54.2 60.7 100.0 106.5 113.0 119.5 8 x FXFQ63AVEB 3 x FXFQ50AVEB 2 x FXFQ50AVEB 6 x FXFQ50AVEB + 4 x FXFQ80AVEB + 9 x FXFQ63AVEB + 10 x FXFQ63AVEB + 10 x FXFQ63AVEB + 2 x FXFQ80AVEB + 2 x FXFQ80AVEB 251.7 253.3 250.8 272.4 163.1 166.2 162.4 167.5 6.4 6.3 6.9 4.2 4.1 4.3 15.9 28.6 32U 34U 16 18 36U 400.0 425.0 450.0 475.0 1,040.0 19.1 1,105.0 1,170.0 1,235.0 34.9 41.3 1,000 3N~/50/380-415 63 80 100 FXSQ-A VRV indoor unit FXFQ-B VRV indoor unit FVXG-K Nexura FTXJ-MW Daikin Emura BPMKS967A2 RYYQ8-12U/RXYQ8-12U Connectable stylish indoor units 20 CLASS Daikin Emura - Wall mounted unit Stylish - Wall mounted unit Nexura - Floor standing unit Floor standing unit 25 CLASS 35 CLASS 42 CLASS 50 CLASS FTXJ-MW/MS FTXA-AW/BS/BB/BT FVXG-K FVXM-F BPMKS box needed to connect RA indoors to VRV IV Outdoor unit System System RYYQ/RXYQ Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. Recommended combination 6°CWB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connection Min. Nom. Max. Piping connections Liquid OD Gas OD Total piping length System Actual Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Outdoor unit module for continuous heating combinations Dimensions Weight Fan Sound power level Sound pressure level Operation range Refrigerant Power supply Current - 50Hz Unit HeightxWidthxDepth Unit External static pressure Max. Cooling Nom. Cooling Nom. Cooling Min.~Max. Heating Min.~Max. Type/GWP Charge Phase/Frequency/Voltage Maximum fuse amps (MFA) 40U 42U 10 HP kW kW kW % % mm mm m Hz/V A RYMQ mm kg Pa dBA dBA °CDB °CWB kg/TCO2Eq Hz/V A 44U 12 46U 14 16 48U 50U 16 52U 54U 18 12 18 18 16 18 40 42 44 46 48 50 52 54 111.9 118.0 123.5 130.0 135.0 140.4 145.8 151.2 62.3 62.4 64.8 67.0 69.6 74.3 79.0 83.7 125.5 131.5 137.5 145.0 150.0 156.5 163.0 169.5 9 x FXFQ50AVEB 12 x FXFQ63AVEB 6 x FXFQ50AVEB 1 x FXFQ50AVEB 12 x FXFQ63AVEB 3 x FXFQ50AVEB 6 x FXFQ50AVEB 9 x FXFQ50AVEB + 9 x FXFQ63AVEB + 4 x FXFQ80AVEB + 8 x FXFQ63AVEB + 13 x FXFQ63AVEB + 6 x FXFQ80AVEB + 13 x FXFQ63AVEB + 14 x FXFQ63AVEB + 15 x FXFQ63AVEB + 4 x FXFQ80AVEB + 4 x FXFQ80AVEB + 4 x FXFQ80AVEB + 2 x FXFQ80AVEB 263.5 261.2 255.9 254.9 251.7 252.8 253.7 254.1 170.0 165.5 164.5 162.0 162.8 165.2 167.2 169.4 6.7 6.6 6.5 6.4 4.3 4.2 4.1 4.2 4.3 64 (1) 500.0 525.0 550.0 575.0 600.0 625.0 650.0 675.0 1,300.0 1,365.0 1,430.0 1,495.0 1,560.0 1,625.0 1,690.0 1,755.0 19.1 41.3 1,000 3N~/50/380-415 100 125 8U 10U 12U 1,685x930x765 198 78.0 16U 18U 20U 1,685x1,240x765 275 79.1 83.4 61.0 5.9/12.3 6.0/12.5 6.3/13.2 20 25 57.0 14U 78 80.9 60.0 -5.0~43.0 -20.0~15.5 R-410A/2,087.5 10.3/21.5 3N~/50/380-415 32 308 85.6 63.0 83.8 62.0 87.9 65.0 11.3/23.6 11.7/24.4 11.8/24.6 40 50 (1) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) 65 VRV IV S-series heat pump Most compact unit on the market 823mm high & 94kg The most compact VRV 22 Control systems Indoor units VRV type indoor units Residential type indoor units (such as Daikin Emura) RXYSCQ4,5,6TV1 Air curtain Biddle Air curtain for VRV (CYV) RXYSQ4,5,6TV9/TY9 Ventilation Heat Reclaim ventilation ALB/VAM/VKM AHU connection kit RXYSQ8, 10, 12TY1 NEW 6HP model › Refrigerant containment check › Night quiet mode › Low noise function › Connectable to stylish indoor units (Daikin Emura, Nexura) › Full inverter compressors VRV IV standards: › Gas cooled PCB (not available on RXYSQ4,5,6,8 T8Y/TY1) › Reluctance brushless DC compressor › Sine wave DC inverter Variable refrigerant temperature › DC fan motor Customize your VRV for best seasonal efficiency & comfort › E-pass heat exchanger VRV configurator › I demand function Software for simplified commissioning, configuration and customisation 66 › Manual demand function For detailed explanation of these functions refer to vrv iv technologies tab 823mm 1615mm Widest range of front blow units on the market 10/12 HP 8 HP 4/5/6 HP Compact: Easy for a two person crew to move and install. 4/5 HP Lowest height on the market Ideal for roof installations Ideal to install below a window on a Balcony › The low height mini VRV can be hidden in many › Daikin VRV IV S-series compact can be installed Unnoticeable for parapet installation Space saving design discretely on a balcony thanks to it’s compact dimensions, offering you air conditioning while being almost unnoticeable. Low height make the unit invisible from inside and unnoticeable from the outside 1,685 mm places where a twin fan unit cannot due to its low height. 823mm The VRV S-series is slimmer and more compact, resulting in significant savings in installation space. 765mm 320mm 460mm 900mm 940mm 930mm 67 Wide range of indoor units Connect VRV units… FXFQ-B FXZQ-A FXSQ-A FXAQ-A … or stylish indoor units (RA and Sky Air) FCAG-B BPMKS967A2 FTXJ-MW/MS - Daikin Emura FBA-A (9) FVXG-K - Nexura BPMKS967A2 Connectable stylish indoor units 15 CLASS Round flow cassette Fully flat cassette Slim concealed ceiling unit Concealed ceiling unit with inverter driven fan Daikin Emura - Wall mounted unit Stylish - Wall mounted unit Perfera - Wall mounted unit Ceiling suspended unit Nexura - Floor standing unit Floor standing unit Concealed floorstanding unit 20 CLASS 25 CLASS FCAG-B FFA-A9 FDXM-F9 FBA-A(9) FTXJ-MW/MS FTXA-AW/BS/BB/BT CTXM-N / FTXM-N FHA-A(9) FVXG-K FVXM-F FNA-A9 For more info about Daikins stylish indoor units, please check our indoor unit-portfolio * VRV indoor units and stylish indoor units cannot be combined. * To connect stylish indoor units a BPMKS unit is needed 68 35 CLASS 42 CLASS 50 CLASS 60 CLASS 71 CLASS High COP values A major feature of VRV IV S-series is its exceptional energy efficiency. The system achieves high COPs during both cooling and heating operation by the use of refined components and functions. 1 Cooling 4.00 1 Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°C, equivalent refrigerant piping: 5m, level difference: 0m. 2 Heating Nominal heating capacities are based on: indoor 4.52 2 temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m Longest length actual 300m 140m 120m (4-8HP)/ 150m (10-12HP) Minimum length between outdoor unit and first branch - Minimum piping length between BP and indoor unit - 2m Maximum piping length between BP and indoor unit - 15m 40m 40m Longest length after first branch Level difference between indoor and outdoor units Level difference between indoor units 1 Stylish indoors connected 5m 50m (40m1) 30m 15m 15m 3 4 5 40m maximum Total piping length VRV indoors connected 150m Actual piping length Flexible piping design 2 15m Level difference between indoor units 1 50m Level difference between indoor and outdoor units 0 Outdoor unit in lowest position 69 VRV IV S-series technologies Refrigerantcooled PCB Super aero grille The spiral shaped ribs are aligned with the direction of discharge flow in order to minimise turbulence and reduce noise. › Reliable cooling because it is not influenced by ambient air temperature › Smaller switchbox for smoother air flow through the heat exchanger increasing heat exchange efficiency with 5% Vane fixed to rotor Rotor Improved fan blades Old New Air streams collide and generate loss Compressor Separate Collision Swing type > no oil separator Vane & rotor are unified resulting in: › Reduced noise level › Longer compressor life › Higher efficiency thanks to the absence of internal refrigerant leakage between high and low pressure side Air streams are smoothed around V-cut and reduces air flow loss E-Pass heat exchanger Optimising the heat exchanger’s path layout prevents heat being transferred from the overheated gas section to the sub-cooled liquid section which is a more efficient way to use the heat exchanger. I-demand function Limit maximum power consumption. The newly introduced current sensor minimizes the difference between the actual power consumption and the predefined power consumption. Standard heat exchanger e-Pass heat exchanger In 85 °C In 85 °C 43 °C 55 °C 27 °C 55 °C 27 °C 60 °C 50 °C 55 °C Out 45 °C Out 45 °C Power consumption Predefined limit Time 70 Mini VRV PIPE RUN OF 70M ALLOWS INSTALLATION AWAY FROM THE HOUSE LARGE VILLA APPLICATION PARAPET INSTALLATION OFFICE ROOFTOP INSTALLATION 71 RXYSCQ-TV1 VRV IV S-series compact heat pump The most compact VRV ʯ Compact & lightweight single fan design makes the unit almost unnoticeable ʯ Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, air handling units and Biddle air cutains ʯ Wide range of indoor units: either connect VRV or stylish indoor units such as Daikin Emura, Nexura ... ʯ Incorporates VRV IV standards & technologies: Variable Refrigerant Temperature and full inverter compressors ʯ Possibility to limit peak power consumption between 30 and 80%, for example during periods with high power demand ʯ Night quiet mode reduces sound pressure with up to 8dBa ʯ Contains all standard VRV features 823mm RXYSCQ-TV1 Only 823mm high! ErP 2021 COMPLIANT Already fully compliant Sound pressure reduction of up to 8dBa with the low noise option to LOT 21 - Tier 2 Published data with real-life indoor units Connectable stylish indoor units 15 CLASS Round flow cassette Fully flat cassette Slim concealed ceiling unit Concealed ceiling unit with inverter driven fan Daikin Emura - Wall mounted unit Stylish - Wall mounted unit Perfera - Wall mounted unit Ceiling suspended unit Nexura - Floor standing unit Floor standing unit Concealed floorstanding unit 20 CLASS 25 CLASS 35 CLASS 42 CLASS 50 CLASS 60 CLASS 71 CLASS FCAG-B FFA-A9 FDXM-F9 FBA-A(9) FTXJ-MW/MS FTXA-AW/BS/BB/BT CTXM-N / FTXM-N FHA-A(9) FVXG-K FVXM-F FNA-A9 Access all technical information on RXYSCQ-TV1 at my.daikin.eu or click here NEW Outdoor unit Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. 6°CWB Recommended combination ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Dimensions Unit HeightxWidthxDepth Weight Unit Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type/GWP Charge Piping connections Liquid OD Gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) RXYSCQ HP kW kW kW % % 4TV1 5TV1 4 12.1 8.4 14.2 3 x FXSQ25A2VEB + 1 x FXSQ32A2VEB 322.8 182.3 8.1 4.6 5 14.0 9.7 16.0 4 x FXSQ32A2VEB 303.4 185.1 7.7 4.7 64 62.5 162.5 823x940x460 89 69.0 52.0 -5.0~46.0 -20.0~15.5 R-410A/2,087.5 3.7/7.7 9.52 50.0 130.0 mm kg dBA dBA °CDB °CWB kg/TCO2Eq mm mm m Hz/V A 68.0 51.0 15.9 70.0 182.0 70.0 53.0 19.1 300 1~/50/220-240 32 (1)Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). 72 6TV1 6 15.5 10.7 18.0 2 x FXSQ32A2VEB + 2 x FXSQ40A2VEB 281.3 186.0 7.1 RXYSQ-TV9 / TY9 / TY1 VRV IV S-series heat pump Space saving solution without compromising on efficiency ʯ Space saving trunk design for flexible installation ʯ Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, air handling units and Biddle air cutains ʯ Wide range of indoor units: either connect VRV or stylish indoor units such as Daikin Emura, Nexura ... ʯ Wide range of units (4 to 12HP) suitable for projects up to 200m² with space limitations ʯ Incorporates VRV IV standards & technologies: Variable Refrigerant Temperature and full inverter compressors ʯ Possibility to limit peak power consumption between 30 and 80%, for example during periods with high power demand ʯ Contains all standard VRV features RXYSQ4-6TV9_TY9 ErP 2021 COMPLIANT Already fully compliant to LOT 21 - Tier 2 Published data with real-life indoor units Connectable stylish indoor units 15 CLASS Round flow cassette Fully flat cassette Slim concealed ceiling unit Concealed ceiling unit with inverter driven fan Daikin Emura - Wall mounted unit Stylish - Wall mounted unit Perfera - Wall mounted unit Ceiling suspended unit Nexura - Floor standing unit Floor standing unit Concealed floorstanding unit 20 CLASS 25 CLASS 35 CLASS 42 CLASS 50 CLASS 60 CLASS 71 CLASS 6TY9 6 15.5 10.2 18.0 268.3 174.1 6.8 4.4 8TY1 8 22.4 14.9 25.0 247.3 165.8 10TY1 10 28.0 19.6 31.5 247.4 162.4 4.2 4.1 12TY1 12 33.5 23.5 37.5 256.5 169.6 6.5 4.3 70.0 100.0 125.0 150.0 FCAG-B FFA-A9 FDXM-F9 FBA-A(9) FTXJ-MW/MS FTXA-AW/BS/BB/BT CTXM-N / FTXM-N FHA-A(9) FVXG-K FVXM-F FNA-A9 Access all technical information on RXYSQ-TV9 at my.daikin.eu or click here Outdoor unit Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. RXYSQ/RXYSQ/RXYSQ HP kW kW kW % % 6°CWB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Dimensions Unit HeightxWidthxDepth Weight Unit Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type/GWP Charge Piping connections Liquid OD Gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) mm kg dBA dBA °CDB °CWB kg/TCO2Eq mm mm m Hz/V A 4TV9 4 12.1 8.0 14.2 278.9 171.6 7.0 4.4 5TV9 5 14.0 9.2 16.0 270.1 182.9 6.8 4.6 6TV9 6 15.5 10.2 18.0 278.0 192.8 7.0 4.9 4TY9 4 12.1 8.0 14.2 269.2 154.4 6.8 3.9 50.0 62.5 70.0 50.0 130.0 162.5 5TY9 5 14.0 9.2 16.0 260.5 164.5 6.6 4.2 64 62.5 162.5 182.0 130.0 1,345x900x320 104 69.0 70.0 68.0 51.0 50.0 -5.0~46.0 68.0 50.0 182.0 69.0 70.0 51.0 6.3 260.0 325.0 390.0 1,430x940x320 1,615x940x460 144 175 180 73.0 74.0 76.0 55.0 57.0 -5.0~52.0 -20.0~15.5 R-410A/2,087.5 3.6/7.5 15.9 19.1 5.5/11.5 9.52 15.9 7.0/14.6 19.1 22.2 8.0/16.7 12.7 25.4 300 1N~/50/220-240 32 3N~/50/380-415 16 25 32 Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). 73 VRV IV i-series heat pump for indoor installation unique patented concept Air curtain Biddle Air curtain for VRV (CYV) 22 Indoor units VRV type indoor units Ventilation Heat Reclaim ventilation (ALB/VAM/ VKM) AHU connection kit Control systems › Night quiet mode › Full inverter compressors › Low noise function VRV IV standards: Variable refrigerant temperature Customize your VRV for best seasonal efficiency & comfort › Sine wave DC inverter › DC fan motor › E-pass heat exchanger › I demand function › Manual demand function VRV configurator For detailed explanation of these functions refer to VRV iv Software for simplified commissioning, configuration and customisation 74 technologies tab Invisible › Consider a wider range of properties because › Seamless integration into the surroundings as only outdoor installation is not a factor › Open for business sooner because getting building permits is simplified › No need for a roof installation or back alley the grille is visible installation Quiet › Highly suited to densely populated areas such as city centres thanks to their low operating sound › Dedicated modes reduce sound further to comply with inner-city noise regulations < Heat exchanger sound not louder Compressor sound not louder than a normal conversation than a refrigerator Lightweight parts › can be installed by two people 75 Unique split outdoor unit for indoor installation Compact and easy to hide, the compressor can be installed at floor level, in a back office, storage room, technical area or in a kitchen, while the heat exchanger can be installed in a false ceiling space. This means that the air conditioning system is completely invisible and does not take up expensive commercial floor space. Unrivalled flexibility thanks to the fact that the outdoor unit is split into two parts 1 1 2 2 1. The heat exchanger can be installed in a false ceiling space. 2. The compressor is compact and easy to hide, this element can be installed at floor level, in a back office, storage room, technical area or in a kitchen. This means that the air conditioning system is completely invisible and does not take up expensive commercial floor space. VRV Indoor units Heat exchanger unit Max. 70 m Max. 30 m Compressor unit Max. total piping length: 140m (5HP) / 300m (8HP) 76 Invisible air suction and air discharge 77 The problem solver for many installation issues Example 1 High flexibilty The other way around: install the modules where if fits your customer, not where it is the best fit for the outdoor unit If there is no flat roof or backgarden available for installation of the outdoor unit, VRV IV i-series offers the solution. The suction and exhaust can be installed at the façade or at the rear of the building as the inverter fans allows ESP to be adjusted to the length of the ductwork. The compressor module can be installed up to 30 m from the heat exchanger unit in a storage room, .... 78 Flexible installation thanks to inverter fans Example 2 Shorter pipe runs to the indoor units reduces installation costs compared to rooftop or back alley installation Back alley or rooftop needs very long piping lengths › Long installation time › Additional cost › Capacity loss VRV IV i-series can be installed close to the indoor units › Quicker installation › Lower cost › No capacity loss long distance short distance Example 3 No need for bulky and expensive sound countermeasures To comply with city regulation countermeasures are needed for standard units › Expensive sound cages might be needed to reduce sound (standard outdoor unit sound = 50~60 dBA) › Inside installation using expensive floor space Reduced floor space Other VRF technical aera stock kitchen More floor space VRV IV i-series With VRV IV i-series you easily comply with city regulation without additional measures › Operation sound 47 dBA for 5HP model (flexible to install in corridor, shop area, …) or lower with attenuator › No floor space is used as units can be installed in false ceiling, against the wall, … sound cage € Expensive counter measures Other VRF No additional measures needed VRV IV i-series = stock kitchen SHOP SHOP 79 Patented V-shape heat exchanger for best surface to volume ratio Optimised air flow and temperature distribution › Best performance for defrost (tested in high humidity down to -20°C). 8 patents Patented perforated and insulated partition plate › Reduces conductivity and prevents cold bridges Only 400mm high ʯ Fits easily in any false ceiling Super efficient centrifugal fans › Over 50% efficiency increase compared to sirocco fan Standard delivered filter › with the unit to prevent dirt from entering the heat exchanger 80 › Patented backward- curved blade technology › More pressure increase Compressor unit with rotating switchbox Flexible and easy to install Flexibility by back and top refrigerant connection possibility Rotating switchbox › For easy access to all compressor parts Only 77 kg (5HP) Tube-in-tube subcool heat exchanger › This patented heat exchanger increases the capacity of the system by ensuring optimal state of refrigerant in the heat exchanger module. This in turn increases overall efficiency. No drain connection needed › Thanks to natural evaporation › Minimized cold surface to reduce dew formation › Fast and easy installation Non welded bottom casing › Avoids any corrosion risk Small footprint › Maximizes useable floor space (600 x 554 mm for 5HP) › Can easily be mounted in a storage room, back office, … 81 SB.RKXYQ-T(8) VRV IV heat pump for indoor installation The invisible VRV ʯ Unique VRV heat pump for indoor installation ʯ Unrivalled flexibility because the unit is split up into two elements: the heat exchanger and the compressor SB.RKXYQ5T8 Heat exchanger unit Max. 70 m VRV Indoor units Max. 30 m Compressor unit can be above heat exchanger unit as well Compressor unit ʯ Highly suited to densely populated areas thanks to the low operation sound and seamless integration into surrounding architecture as only the grille is visible ʯ Incorporates VRV IV standards & technologies: Variable Refrigerant Temperature, VRV configurator and full inverter compressors ʯ Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, air handling units and Biddle air cutains ʯ Lightweight units (max. 105kg) can be installed by two people ʯ Unique V-shape heat exchanger results in compact dimensions (h/e unit only 400mm high) allowing false ceiling installation, while ensuring top efficiency ʯ Super efficient centrifugal fans (over 50% ErP 2021 efficiency increase compared to sirocco fan) ʯ Small footprint compressor unit (760 x 554 mm) Already fully compliant maximizing useable floor space to LOT 21 - Tier 2 ʯ Contains all standard VRV features COMPLIANT Published data with real-life indoor units Access all technical information on SB-RKXYQ-T at my.daikin.eu or click here System System SB.RKXYQ Heat exchanger unit Compressor unit Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. 6°CWB Recommended combination ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Piping connections Liquid OD Gas OD Between Compressor Liquid module (CM) and heat Gas exchanger module (HM) Between Compressor Liquid module (CM) and indoor Gas units (IU) Total piping length System HP kW kW kW % % Access all technical information on SB-RKXYQ-T(8) at my.daikin.eu or click here 5T8 RDXYQ5T8 RKXYQ5T8 5 14.0 10.4 16.0 4 x FXSQ32A2VEB 200.1 149.3 5.1 3.8 10 62.5 162.5 260.0 OD OD mm mm mm mm 19.1 OD OD mm mm 15.9 19.1 m 140 300 Heat exchanger module - RDXYQ 5T8 8T 397x1,456x1,044 95 103 55 100 77.0 81 47.0 54 R-410A/-/1N~/50/220-240 10 Compressor module - RKXYQ 5T8 8T 701x600x554 701x760x554 79 105 60.0 64 47.0 48 R-410A/2,087.5 2.00/4.20 4.00/8.35 3N~/50/380-415 16 20 Actual Outdoor unit module HeightxWidthxDepth Dimensions Unit Weight Unit Fan Air flow rate Cooling Nom. Sound power level Cooling Nom. Sound pressure level Cooling Nom. Refrigerant Type/GWP Charge Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) mm kg m³/min dBA dBA kg/TCO2Eq Hz/V A 12.7 22.2 9.52 (1)Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% ≤ CR ≤130%). 82 8T RDXYQ8T RKXYQ8T 8 22.4 12.9 25.0 4 x FXMQ50P7VEB 191.1 140.9 4.9 3.6 17 100.0 VRV IV C series + Where heating is priority without compromising on efficiency Air curtain Biddle Air curtain for VRV (CYV) 22 Indoor units VRV type indoor units Residential type indoor units (such as Daikin Emura) Control systems Ventilation Heat Reclaim ventilation (ALB/VAM/ VKM) AHU connection kit › 7 segment display › Automatic refrigerant charge › Refrigerant containment check › Night quiet mode › Low noise function › Connectable to stylish indoor units (Only for single modules) › Full inverter compressors VRV IV standards: › Gas cooled PCB › 4 side heat exchanger Variable refrigerant temperature › Reluctance brushless DC compressor Customize your VRV for best seasonal efficiency & comfort › DC fan motor VRV configurator › E-pass heat exchanger Software for simplified commissioning, configuration and customisation › Sine wave DC inverter › I demand function › Manual demand function 83 ARGUE CARDS VRV IV+ heat pump, optimised for cold climates RXYLQ-T High heating capacity at low ambient temperatures › Stable heating capacity available down to -15°C WB! VRV3-C VRV4-C HEATING CAPACITY [KW] Where heating is priority without compromising on efficiency 50 45 40 35 30 25 -25 -20 -15 -10 -5 20 0 5 10 AMBIENT TEMPERATURE [°CWB] HIGH PRESSURE › New vapour injection scroll compressor optimised for low load • UNIQUE back-pressure control: Pressure port increases pressure below the scroll in low load operation, preventing refrigerant leak and increasing efficiency • UNIQUE Injection structure with check valve: Prevents volume backflow during low load operation typically occuring with standard vapour injection compressors › Variable Refrigerant Temperature adjusts refrigerant temperature to match the load PRESSURE High partial load efficiency PRESSURE PORT LOWER PRESSURE High reliability down to -25°C WB › Hot gas bypass prevents ice buildup at the bottom of the heat exchanger 84 High seasonal efficiency ErP 2021 COMPLIANT Already fully compliant › Measured with indoor units for real applications! › ALL information for indoor units used available on our eco-design website: Already fully compliant https://energylabel.daikin.eu/eu/en_US/lot21.html to LOT 21 - Tier 2 The known VRV IV standards Variable Refrigerant Temperature VRV configurator Total solution Daikin Emura Wall mounted unit Nexura Floor standing unit Fully flat cassette Biddle air curtain Air handling unit for ventilation Low temperature hydrobox 85 RXYLQ-T VRV heat pump optimised for heating Where heating is priority without compromising on efficiency ʯ Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, air handling units and Biddle air cutains ʯ Wide range of indoor units: possibility to combine VRV with stylish indoor units (Daikin Emura, Nexura, ...) ʯ Incorporates VRV IV standards & technologies: Variable Refrigerant Temperature, VRV configurator, 7 segment display and full inverter compressors, 4-side heat exchanger, refrigerant cooled PCB, new DC fan motor, ... ʯ Free combination of outdoor units to meet installation space or efficiency requirements ErP 2021 ʯ Wide piping flexibility: 30m indoor COMPLIANT height difference, maximum piping length: 190m, total piping length: 500m Already fully compliant ʯ Less installation time and smaller to LOT 21 - Tier 2 footprint Published data with compared to previous model thanks to real-life indoor units removal of function unit ʯ Specifically developed for heating operation in low ambient conditions, making it suitable for single source heating ʯ Stable heating capacity down to -15°C, thanks to vapour injection compressor ʯ Extended operation range down to -25°C in heating ʯ High reliability in severe conditions, thanks to hot gas bypass circuit in the heat exchanger ʯ 15% increased heating capacity at high relative humidity (2°CDB/1°CWB and RH=83%) vs previous model ʯ Shorter defrost and heat up time, compared to standard VRV heat pump ʯ Very economical solution as a smaller outdoor unit model can be used compared to the standard series Access all technical information on RXYLQ-T at my.daikin.eu or click here Outdoor unit Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. 6°CWB Recommended combination ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Dimensions Unit HeightxWidthxDepth Weight Unit Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type/GWP Charge Piping connections Liquid OD Gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Outdoor unit System 6°CWB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Piping connections Liquid OD Gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) 12T 12 33.5 37.5 37.50 6 x FXMQ50P7VEB 274.4 137.6 6.93 3.51 64 (1) 210 300 390 1,685x1,240x765 302 81 59 -5.0~43.0 -25.0~16.0 R-410A/2,087.5 11.8/24.6 175 250 325 mm kg dBA dBA °CDB °CWB 77 56 kg/TCO2Eq mm mm m 9.5 22.2 HP kW kW kW % % mm mm m Hz/V A 14T 14 40 45 45.00 1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 270.1 137.1 6.83 3.5 245 350 455 81 59 12.7 28.6 500 Hz/V A Outdoor unit module 1 Outdoor unit module 2 Prated,c Prated,h Max. Recommended combination 10T 10 28 31.5 31.50 4 x FXMQ63P7VEB 251.4 144.3 6.36 3.68 % % RXYLQ Capacity range Cooling capacity Heating capacity 86 RXYLQ HP kW kW kW 3N~/50/380-415 25 32 16T RXMLQ8T RXMLQ8T 16 44.8 18T RXYLQ10T RXMLQ8T 18 50.4 20T RXYLQ10T RXYLQ10T 20 56 50 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 56.5 3 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 63 2 x FXMQ50P7VEB + 6 x FXMQ63P7VEB 261.8 138.0 3.52 6.62 255.7 140.5 3.59 6.47 251.4 144.3 3.68 6.36 280 400 520 12.7 28.6 315 450 585 15.9 28.6 350 500 650 15.9 28.6 40 45 50 22T RXYLQ10T RXYLQ12T 22 61.5 69 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB 263.0 140.3 3.58 6.65 64 (1) 385 550 715 15.9 28.6 500 24T RXYLQ12T RXYLQ12T 24 67 26T RXYLQ12T RXYLQ14T 26 73.5 28T RXYLQ14T RXYLQ14T 28 80 75 4 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 274.4 137.6 3.51 6.93 82.5 7 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 270.8 137.1 3.50 6.84 90 6 x FXMQ50P7VEB + 4 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 270.1 137.1 3.50 6.83 420 600 780 15.9 455 650 845 490 700 910 19.1 34.9 3N~/50/380-415 60 FXSQ-A VRV indoor unit FXFQ-B VRV indoor unit FVXG-K Nexura BPMKS967A2 FTXJ-MW Daikin Emura RXYLQ-T Connectable stylish indoor units 20 CLASS Daikin Emura - Wall mounted unit Stylish - Wall mounted unit Nexura - Floor standing unit Floor standing unit 25 CLASS 35 CLASS 42 CLASS 50 CLASS FTXJ-MW/MS FTXA-AW/BS/BB/BT FVXG-K FVXM-F BPMKS box needed to connect RA indoors to VRV IV Outdoor unit System RXYLQ Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. Recommended combination 6°CWB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Piping connections Liquid OD Gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Outdoor unit Dimensions Weight Sound power level Sound pressure level Operation range Refrigerant Piping connections Power supply Current - 50Hz Unit HeightxWidthxDepth Unit Cooling Nom. Cooling Nom. Cooling Min.~Max. Heating Min.~Max. Type/GWP Charge Liquid OD Gas OD Total piping System Actual length Phase/Frequency/Voltage Maximum fuse amps (MFA) HP kW kW kW % % mm mm m 30T RXYLQ10T RXYLQ10T 34T RXYLQ10T RXYLQ12T 30 84 32T RXYLQ10T RXYLQ10T RXYLQ12T 32 89,5 94,5 9 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 100,5 8 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 251.4 144.3 3.86 6.36 259.1 141.6 3.61 6.55 106,5 3 x FXMQ50P7VEB + 9 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 266.8 139.2 3.56 6.74 525 750 975 19,1 34,9 560 800 1040 19,1 34,9 595 850 1105 19,1 34,9 Hz/V A RXMLQ mm kg dBA dBA °CDB °CWB 34 95 36T RXYLQ12T RXYLQ12T 38T RXYLQ12T RXYLQ12T RXYLQ14T 38 107 36 101 112,5 120 2 x FXMQ50P7VEB 6 x FXMQ50P7VEB + 10 x FXMQ63P7VEB + 10 x FXMQ63P7VEB + 2 x FXMQ80P7VEB 274.4 271.6 137.6 137.1 3.51 3.50 6.93 6.86 64 (1) 630 665 900 950 1170 1235 19,1 19,1 41,3 500 40T RXYLQ12T RXYLQ14T 42T RXYLQ14T RXYLQ14T 40 114 42 120 127,5 9 x FXMQ50P7VEB + 9 x FXMQ63P7VEB 135 12 x FXMQ63P7VEB + 4 x FXMQ80P7VEB 270.3 137.1 3.50 6.83 270.1 137.1 3.50 6.83 700 1000 1300 19,1 41,3 735 1050 1365 19,1 3N~/50/380-415 80 90 kg/TCO2Eq mm mm m 8T 1,685x1,240x765 302 75,0 55,0 -5.0~43.0 -25.0~16.0 R-410A/2,087.5 11.8/24.6 9.5 19.1 500 Hz/V A 3N~/50/380-415 20 (1) Actual number of connectable indoor units depends on the indoor unit type and the connection ratio restriction for the system 87 The Post, 5-star hotel, VRV IV 88 Replacement VRV Quick & quality replacement for R-22 and R-407C systems 22 Air curtain Biddle Air curtain for VRV (CYV) Indoor units VRV type indoor units Ventilation Heat Reclaim ventilation (VAM/VKM) AHU connection kit Control systems VRV III VRV IV+ Q Heat pump Variable refrigerant temperature Customize your VRV for best seasonal efficiency & comfort VRV configurator Software for simplified commissioning, configuration and customisation For more information on these features refer to the VRV IV technologies tab › 7 segment display › Automatic refrigerant charge › Night quiet mode Heat pump & Heat recovery › Low noise function › Automatic refrigerant charge › Full inverter compressors › Night quiet mode › Gas cooled PCB › Low noise function › 4 side heat exchanger › Full inverter compressors › Reluctance brushless DC compressor › Reluctance brushless DC compressor › Sine wave DC inverter › Sine wave DC inverter › DC fan motor › DC fan motor › E-pass heat exchanger › E-pass heat exchanger › I demand function › I demand function › Manual demand function › Manual demand function 89 Replacement technology The quick and quality way of upgrading R-22 and R-407C systems These benefits will convince your customer: Drastically improve your efficiency, comfort and reliability Avoid loss of business Lower long-term costs Replacing now prevents unplanned, lengthy downtime of air conditioning systems. It also avoids loss of business for shops, complaints from guests in hotels, lower working efficiency and loss of tenants in offices. EU Directives prohibit system repairs with R-22 after January 1, 2015. Delaying the required R-22 replacement until an unplanned system breakdown is a losing game. Replacement day will come. Installing a technically advanced system lowers energy consumption and maintenance costs from day one. Quick and easy installation No interruption of daily business while replacing the system thanks to phased-in, fast installation. Up to 48% less consumption Smaller footprint, more performance Thanks to a smaller footprint, Daikin outdoor units save space. Also, more indoor units can be connected to the new outdoor unit compared to the old system, allowing to increase capacity. Comparison of 10HP systems: Cooling mode Heating mode R-22 (RSXY-KA7) R-407C (RSXYP-L7) R-410A (RXYQQ-T) Keep your refrigerant piping Your copper pipes will last for multiple generations The Daikin low-cost upgrade solution ! Replace indoor units and BS boxes Contact your local dealer to check compatibility in case you need to keep the indoor units. ! 90 Replace outdoor units › copper pipes used in air conditioning systems tested by Daikin will last over 60 years after installation. › Japan/China have replaced with VRV Q-series already 10 years ago! Umeda Center Building, Japan › original A/C system: 20 years in use › replacement with VRV Q-series: 2006 - 2009 › capacity up from 1620HP to 2322HP › SHASE renewal award: 2013 (1st) ! Planning your replacement in future? Monitor your system now! Your building use might have changed over the years. Monitoring and Daikin expert advice prepare you for an optimum replacement to maximize efficiency and comfort, while minizing the investment cost of your new system. VRV-Q benefits to increase your profit: Optimise your business Compare installation steps Less installation time Conventional solution VRV-Q 1 2 3 4 5 6 7 1 Recover refrigerant 2 Remove units Tackle more projects in less time thanks to faster installation. It is more profitable than replacing the full system with new piping. Lower installation costs Reducing installation costs enables you to offer customers the most cost-effective solution and improve your competitive edge. Replace non-Daikin systems It is a trouble-free replacement solution for Daikin systems and for systems made by other manufacturers. Recover refrigerant Remove units Remove refrigerant pipes Install new piping and wiring Install new units Leak test Vacuum drying 8 Refrigerant charging 9 Collect contamination 10 Test operation Re-use existing piping and wiring 3 Install new units 4 Leak test 5 Vacuum drying 6 A uromatic refrigerant charging, cleaning and testing â Easy as one-two-three A simple solution for replacement technology enables you to handle more projects for more customers in less time and offer them the best price! Everybody wins. Up to 45% shorter installation time Automatic refrigerant charge The unique automatic refrigerant charge eliminates the need to calculate refrigerant volume and ensures that the system will operate perfectly. Not knowing the exact piping lengths because of changes or mistakes in case you didn’t do the original installation or replacing a competitor installation no longer poses a problem. Automatic pipe cleaning One touch convenience: › Measure and charge There is no need to clean inside piping as this is handled automatically by the VRV-Q unit. Finally the test operation is performed automatically to save time. › Automatic pipe refrigerant cleaning › Test operation 91 RQCEQ-P3 Replacement VRV, heat recovery Quick & quality replacement for R-22 and R-407C systems ʯ Cost effective and fast replacement as only the outdoor and indoor unit needs to be replaced, meaning almost no work has to be carried out inside the building ʯ Efficiency gains of more than 40% can be realized, thanks to technological developments in heat pump technology and the more efficient R-410A refrigerant ʯ Less intrusive and time consuming installation compared to installing a new system, as the refrigerant piping can be maintained ʯ Unique automatic refrigerant charge eliminates the need to calculate refrigerant volume and allows safe replacement of competitor replacement ʯ Automatic cleaning of refrigerant piping ensures a clean piping network, even when a compressor breakdown has occurred ʯ Possibility to add indoor units and increase capacity without changing the refrigerant piping ʯ Possibility to spread the various stages of repclacement thanks to the modular design of the VRV system ʯ Accurate temperature control, fresh air provision, air handling units and Biddle air curtains all integrated in a single system requiring only one single point of contact (RXYQQ-U only) ʯ Incorporates VRV IV standards & technologies: Variable Refrigerant ʯ Temperature and full inverter compressors (RXYQQ-U only) ʯ Free combination of outdoor units to meet installation space or ʯ efficiency requirements (RXYQQ-U only) RQCEQ712-848P3 ErP 2021 COMPLIANT Already fully compliant to LOT 21 - Tier 2 Published data with real-life indoor units Access all technical information on RQCEQ-P3 at my.daikin.eu or click here Outdoor unit System System Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Outdoor unit module 4 Capacity range Cooling capacity Prated,c Heating capacity Prated,h Recommended combination ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Piping connections Liquid OD Gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Outdoor unit module Dimensions Unit HeightxWidthxDepth Weight Unit Air flow rate Cooling Nom. Fan Type Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type/GWP Charge Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) 92 RQCEQ HP kW kW % % mm mm m Hz/V A RQEQ-P3 mm kg m³/min 280P3 RQEQ140P3 RQEQ140P3 360P3 RQEQ180P3 RQEQ180P3 460P3 500P3 540P3 636P3 712P3 744P3 816P3 848P3 RQEQ140P3 RQEQ180P3 RQEQ212P3 RQEQ140P3 RQEQ180P3 RQEQ212P3 RQEQ140P3 RQEQ180P3 RQEQ212P3 RQEQ180P3 RQEQ212P3 RQEQ212P3 RQEQ180P3 RQEQ212P3 RQEQ180P3 RQEQ212P3 10 13 16 18 20 22 24 26 28 30 28.0 36.0 46.0 50.0 54.0 60.0 70.0 72.0 78.0 80.0 32.0 40.0 52.0 56.0 60.0 67.2 78.4 80.8 87.2 89.6 4 x FXMQ63P7VEB 4 x FXMQ50P7VEB 4 x FXMQ63P7VEB 4 x FXSQ32A2VEB 12 x FXSQ40A2VEB 3 x FXSQ40A2VEB 4 x FXSQ32A2VEB 4 x FXSQ32A2VEB 7 x FXSQ40A2VEB 4 x FXSQ40A2VEB + 2 x FXMQ63P7VEB + 2 x FXMQ80P7VEB + 8 x FXSQ40A2VEB + 9 x FXSQ50A2VEB + 9 x FXSQ40A2VEB + 6 x FXSQ40A2VEB + 9 x FXSQ50A2VEB + 12 x FXSQ50A2VEB + 3 x FXSQ50A2VEB + 6 x FXSQ50A2VEB 200 185 191 201 198 186 194 204 187 159 157 161 150 148 157 153 155 157 21 28 34 39 43 47 52 56 60 64 140 180 230 250 270 318 356 372 408 424 280 360 500 540 636 712 744 816 848 364 468 598 650 702 827 926 967.0 1,061 1,102 9.52 12.7 15.9 19.1 22.2 25.4 28.6 34.9 300 30 40 50 60 140P3 3~/50/400 70 80 180P3 1,680x635x765 212P3 175 179 95 dBA dBA °CDB °CWB 79 kg/TCO2Eq Hz/V A 10.3/21.5 15 90 110 Propeller fan 83 -5~43 -20~15.5 R-410A/2,087.5 10.6/22.1 3~/50/380-415 20 87 11.2/23.4 22.5 RQYQ-P / RXYQQ-U Replacement VRV, heat pump RXYQQ8-12U Access all technical information on RQYQ-P at my.daikin.eu or click here Outdoor unit Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. Recommended combination 6°CWB ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Dimensions Unit HeightxWidthxDepth Weight Unit Air flow rate Cooling Nom. Fan Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type/GWP Charge Piping connections Liquid OD Gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Outdoor unit System + Module System Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Capacity range Cooling capacity Prated,c Heating capacity Prated,h Max. 6°CWB Recommended combination ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index connec- Min. tion Nom. Max. Piping connections Liquid OD Gas OD Total piping System Actual length Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Access all technical information on RXYQQ-U at my.daikin.eu or click here RXYQQ/RQYQ-P HP kW kW kW % % mm kg m³/min dBA dBA °CDB °CWB 140P 5 14.0 16.0 4 x FXSQ32A2VEB 8U 8 22.4 13.7 25.0 4 x FXFQ50AVEB 10U 10 28.0 16.0 31.5 4 x FXFQ63AVEB 194 137 10 62.5 125 162.5 1,680x635x765 175 95 79 -5~43 -20~15.5 302.4 167.9 7.6 267.6 168.2 6.8 kg/TCO2Eq mm mm m 11.1/23.2 9.52 15.9 Hz/V A 3~/50/380-415 15 RXYQQ HP kW kW kW % % mm mm m Hz/V A 22U RXYQQ10U RXYQQ12U 4.3 100.0 125.0 260.0 325.0 1,685x930x765 198 78.0 79.1 57.0 5.9/12.3 6.0/12.5 9.52 19.1 22.2 20 25 24U RXYQQ8U RXYQQ16U 12U 12 33.5 18.4 37.5 6 x FXFQ50AVEB 14U 16U 18U 20U 14 16 18 20 40.0 45.0 50.4 52.0 20.6 23.2 27.9 31.0 45.0 50.0 56.5 63.0 1 x FXFQ50AVEB 4 x FXFQ63AVEB 3 x FXFQ50AVEB 2 x FXFQ50AVEB + 5 x FXFQ63AVEB + 2 x FXFQ80AVEB + 5 x FXFQ63AVEB + 6 x FXFQ63AVEB 247.8 250.7 236.5 238.3 233.7 161.4 155.4 157.8 163.1 156.6 6.3 6.0 5.9 4.1 4.0 4.2 4.0 64 (1) 150.0 175.0 200.0 225.0 250.0 390.0 455.0 520.0 585.0 650.0 1,685x1,240x765 275 308 83.4 80.9 85.6 83.8 87.9 61.0 60.0 63.0 62.0 65.0 -5.0~43.0 -20.0~15.5 R-410A/2,087.5 6.3/13.2 10.3/21.5 11.3/23.6 11.7/24.4 11.8/24.6 12.7 15.9 28.6 300 3N~/50/380-415 32 40 50 26U 28U 30U 32U 34U 36U 38U 40U 42U RXYQQ12U RXYQQ16U RXYQQ8U RXYQQ10U RXYQQ14U RXYQQ16U RXYQQ18U RXYQQ16U RXYQQ18U RXYQQ20U RXYQQ10U RXYQQ12U RXYQQ16U RXYQQ20U RXYQQ18U RXYQQ16U 22 24 26 28 30 32 34 36 38 40 42 61.5 67.4 73.5 78.5 83.9 90.0 95.4 97.0 102.4 111.9 118.0 34.4 36.9 39.0 41.6 46.3 46.4 51.1 54.2 60.7 62.3 62.4 69.0 75.0 82.5 87.5 94.0 100.0 106.5 113.0 119.5 125.5 131.5 6 x FXFQ50AVEB 4 x FXFQ50AVEB 7 x FXFQ50AVEB 6 x FXFQ50AVEB 9 x FXFQ50AVEB 8 x FXFQ63AVEB 3 x FXFQ50AVEB 2 x FXFQ50AVEB 6 x FXFQ50AVEB 9 x FXFQ50AVEB 12 x FXFQ63AVEB + 4 x FXFQ63AVEB + 4 x FXFQ63AVEB + 5 x FXFQ63AVEB + 4 x FXFQ63AVEB + 5 x FXFQ63AVEB + 4 x FXFQ80AVEB + 9 x FXFQ63AVEB + 10 x FXFQ63AVEB + 10 x FXFQ63AVEB + 9 x FXFQ63AVEB + 4 x FXFQ80AVEB + 2 x FXFQ80AVEB + 2 x FXFQ80AVEB + 2 x FXFQ80AVEB + 2 x FXFQ80AVEB 274.5 269.9 264.2 257.8 256.8 251.7 253.3 250.8 272.4 263.5 261.2 171.2 167.0 164.6 166.0 169.8 163.1 166.2 162.4 167.5 170.0 165.5 6.9 6.8 6.7 6.5 6.4 6.3 6.9 6.7 6.6 4.4 4.3 4.2 4.3 4.2 4.1 4.3 4.2 64 275.0 300.0 325.0 350.0 375.0 400.0 425.0 450.0 475.0 500.0 525.0 715.0 780.0 845.0 910.0 975.0 1,040.0 1,105.0 1,170.0 1,235.0 1,300.0 1,365.0 15.9 19.1 28.6 34.9 41.3 300 63 3N~/50/380-415 80 Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) 100 93 Water cooled + VRV IV W series Ideal for high rise buildings, using water as heat source Unified range for heat pump & heat recovery and standard & geothermal series 22 Air curtain Biddle Air curtain for VRV (CYV) Indoor units VRV type indoor units OR Residential type indoor units (such as Daikin Emura, ...) Hot water High temperature hydrobox Low temperature hydrobox Control systems Ventilation Heat Reclaim ventilation (ALB/VAM/ VKM) AHU connection kit Widest range of BS boxes for the fastest installation VRV IV standards: › 7 segment display Variable refrigerant temperature › Connectable to stylish indoor units Customize your VRV for best seasonal efficiency & comfort › Full inverter compressors › Connectable to LT hydrobox › Connectable to HT hydrobox VRV configurator › Reluctance brushless DC compressor Software for simplified commissioning, configuration and customisation › Sine wave DC inverter For more information on these features refer to the VRV IV technologies tab 94 › Manual demand function ARGUE CARDS Water-to-air heat pump Welcome a new range of features More flexibility Most compact casing in the market! › Mixed connection of HT hydroboxes and VRV indoor units › Connects to stylish indoor units such as Daikin Emura, Nexura, … (no mixed connection with other indoors possible) › Extension of the range: 8-10-12-14HP, combinable up to 42HP while keeping the most compact casing in the market › Extended piping length up 165m (actual) › Extended indoor unit height difference to 30m More capacity › Up to 72% increased capacity (!) per model thanks to new compressor and larger heat exchanger 8 to 14 HP 16 to 28 HP 30 to 42 HP Unique zero heat dissipation principle › No need for ventilation or cooing in the technical room › Control heat dissipation to achive maximum efficiency: set target technical room temperature and unit regulates actual heat dissipation Easier commissioning & customisation › 7 segment display › 2 analogue input signals allowing external control of - ON-OFF (e.g. compressor) - Operation mode (cooling / heating) - Limit of capacity - Error signal Total solution Daikin Emura wall mounted unit Nexura Fully flat cassette Floor standing unit Biddle air curtain Air handling unit for ventilation Low temperature hydrobox High temperature hydrobox 95 With all existing standard functions Indoor installation makes unit invisible from the outside › Seamless integration in the surrounding architecture as you cannot see the unit › Highly suited for sound sensitive areas as there is no external operation sound › Very flexible indoor installation as there is no heat dissipation › Superior efficiency, even in the most extreme outside conditions, especially in geothermal operation Unified range for heat pump & heat recovery and standard & geothermal series Variable water flow control › The variable water flow control option reduces excessive energy use by the circulation pump. › By controlling a variable water valve, the water flow is reduced when possible, saving energy. › Via 0~10 volt Cooling tower (Closed type), boiler Flow Valve Input Signal Variable water Flow Control Valve Lower refrigerant concentration levels Inverter Pump Water-cooled VRV systems typically have less refrigerant per system making it ideal to comply with the EN378 legislation limiting the amount of refrigerant in hospitals and hotels. The refrigerant levels remain limited thanks to: › limited distance between outdoor and indoor unit › modularity: enabling small systems per floor instead of one big system. Thanks to the water circuit heat recovery is still possible in the entire building Single port Maximum design flexibility and installation speed BS1Q 10,16,25A › Quickly and flexibly design your system with a unique range of single and multi BS boxes. › A wide variety of compact and lightweight multi BS boxes greatly reduces installation time. › Free combination of single and multi BS boxes 2-stage heat recovery Multi port: 4 – 6 – 8 – 10 – 12 – 16 BS 4 Q14 A BS 6, 8 Q14 A BS 10, 12 Q14 A BS 16 Q14 A Stacked configuration STAGE 1 Heat recovery between indoor units STAGE 2 Heat recovery between outdoor units Water piping Refrigerant piping (Heat recovery and heat pump) Ceiling height Cooling tower (Closed type), boiler Heat rejected to loop 14HP Indoor units mainly cooling, partly heating 14HP VRV-W Heat absorbed from loop Indoor units mainly heating, partly cooling 96 VRV-W 14HP 3.3m height Crystal Tower BREEAM Design Phase: Excellent rating A great and well-known example of a Daikin Total Solution leading to high energy-efficient HVAC consumption › A combination of VRV, Sky Air and Applied systems ensuring all offices and common areas are fully air conditioned. › Water-cooled VRV as the main contributor to total HVAC energy efficiency due to its two-stage heat recovery system. › Flexibility: individual thermal control and comfort with VRV on each floor and space. › Problem-free connection between Daikin units and the LonWorks BMS system ensures the building’s total energy consumption is properly monitored and controlled. Location 48 Lancu de Hunedoara Boulevard Bucharest Romania Building details Built-up area: 24,728 m² Total usable area: 20,020 m² Floors: 4 basements, 15 floors, technical floor Building height: 72 m Office space per level: approx. 1,000 m² Daikin systems installed › › › › › › 67 x VRV water-cooled units 2 x VRV outdoor heat pump units 289 VRV indoor units (265 ducts, 24 x cassettes) 5 x Sky Air with Roundflow Cassettes 4 x air-cooled water chillers 11 x DMS504B51 (LonWorks gateway) Awards › Green Building of the Year 2012 (ROGBC) › Environmental Social & Sustainability award (ESSA) 97 Innovations for maximum flexibility and ease of installation 0m m 980mm Horizontal or vertical piping connection 56 767mm Highly improved efficiency thanks to enlarged heat exchanger Easy access to components Easy front plate removal step 1 98 Rotating switchbox step 2 Zero heat dissipation principle › No need for ventilation or cooling of the technical room › Enhancing installation flexibility and reliability of parts Heat dissipation coil cools down the unit to achieve a neutral heat balance in the technical room PCB generates heat Compessor generates heat Minimal technical room space required. technology › VRV configurator › 7 segment display 99 Application example Closed evaporative cooling tower used for cooling, Chiller used for heating Closed evaporative cooling tower Chiller Cooling mode Expansion tank Strainer 100 Circulator Pump Heat exchanger Flow valve or flow control valve Stop valve Flow switch Three way valve Heating mode Refrigerant flow Benefits of this setup When to use? › Chiller is only used when cooling tower capacity is not enough and/or when cooling and heating load of VRV is unbalanced very energy efficient installation › In case the chiller is operating, a renewable heat source (air) is used, contributing to BREEAM score. › It is possible to downsize the cooling tower, making the installation more compact › When there is anyway a chiller used for other purposes in the building › When space for outdoor installation is limited › Efficiency / green building certification schemes oriented projects Application example Dry cooler used for cooling, boiler used for heating Closed evaporative cooling tower Boiler Cooling mode Expansion tank Strainer Circulator Pump Heat exchanger Flow valve or flow control valve Stop valve Flow switch Three way valve Benefits of this setup › Simple, cost efficient. Good option to use VRV technology in high-rise building › Does not make any special demand to the building/project/ installation location › Provides high efficiency as for hotel application it is usual to have simultaneous cooling and heating load. Heating mode Refrigerant flow › Heat recovery process in the water loop often allows the water temperature to stay within acceptable range even without using drycooler and boiler. When to use? › For high-rise buildings or other places where VRV Water Cooled is preferable because of installation conditions 101 Application example Geothermal operation Hot water tank Ground loop with vertical boreholes Expansion tank Circulator Pump Liquid heater Buffer tank Heat exchanger Flow switch Cooling mode Heating mode Strainer 102 Stop valve Flow valve or flow control valve Refrigerant flow Three way valve Benefits of this setup When to use? › Very energy efficient › Ground loop can be in service for a very long time, so future equipment upgrades/replacements are easy › Vertical boreholes provide more stable water temperature (= Constant high efficiency) and do not occupy a lot of ground space. › When the soil is suitable for geothermal loops and there is availability of geothermal installation expertise locally › For the projects with high requirements to energy efficiency, green building certification oriented Ground loop Examples Open system Uses water from a well or surface water (river, lake). The water is pumped back to a second well or surface water Conditions: › At 20 m depth water has a constant temperature of 10°C through the year › Surface water cools down to 5°C during winter Can be the most economical type of geothermal system Constant ground water temperature has positive impact on heat pump efficiency O Risk to damage system components because of water quality a secondary loop might be required to protect the heat exchanger O Water should be tested for acidity, mineral content, organic content and corosiveness: O In many areas open systems are prohibited due to environmental concerns Closed system Uses water pipes that are buried in the ground and exchange heat with the ground Vertical system conditions › Typical depth: 30-140 m. Below 15 m, the temperature of the ground is constant around 10°C Less surface space required Very constant ground temperature O Expensive due to drilling cost For smaller applications also horizontal loops can be used Horizontal loop system › Typical trench depth: 1 – 2 m. The ground temperature varies, but always above 5°C (Exception: in cold areas) › Slinky loop: the plastic geothermal loop pipe is coiled in overlapped circles and flattened (Installed where there is not enough space for closed horizontal) Installation is easier and less expensive than vertical closed loops. O Mainly for small applications as the property land should be large enough O You cannot plant trees or build constructions over the land containing the loop. O Glycol is needed to prevent freezing of the water. 103 RWEYQ-T9 VRV IV water cooled+ series Ideal for high rise buildings, using water as heat source ʯ Environmental conscious solution: reduced CO2 emmisions thanks to the use of geothermal energy as a renewable energy source and typical lower refrigerant levels making it ideal to comply with EN378 ʯ Covers all thermal needs of a building via a single point of contact: accurate temperature control, ventilation, air handling units, Biddle air curtains and hot water ʯ Unique zero heat dissipation principle obviates the need for ventilation or cooling in the technical room, maximising installation flexiblity ʯ Wide range of indoor units: possibility to combine VRV with stylish indoor units (Daikin Emura, Nexura, ...) ʯ Incorporates VRV IV standards & technologies: Variable Refrigerant Temperature, VRV configurator, 7-segment display and full inverter compressors ʯ Developed for easy installation and servicing: choice between top or front connection for refrigerant piping and rotating switch box for easy access to serviceable parts ʯ Compact & lightweight design can be stacked for maximum space saving: 42HP can be installed in less than 0,5m² floorspace ʯ 2-stage heat recovery: first stage between indoor units, second stage between outdoor units thanks to the storage of energy in the water circuit ʯ Unified model for heat pump and heat recovery version and geothermal and standard operation ʯ Variable Water Flow control option increases flexibility and control ʯ 2 analogue input signals allowing external control of ON-OFF, operation mode, error signal, … ʯ Contains all standard VRV features VRV-W Level difference between the VRV-W and indoor units: 50m if the VRV-W is above 40m if the VRV-W is below VRV-W Level difference between indoor units: 30m Indoor installation Unlimited water piping length Water piping Refrigerant piping ErP 2021 COMPLIANT Already fully compliant to LOT 21 - Tier 2 Published data with real-life indoor units Connectable stylish indoor units 20 CLASS Daikin Emura - Wall mounted unit Stylish - Wall mounted unit Nexura - Floor standing unit Floor standing unit 25 CLASS 35 CLASS 42 CLASS 50 CLASS FTXJ-MW/MS FTXA-AW/BS/BB/BT FVXG-K FVXM-F BPMKS box needed to connect RA indoors to VRV IV (RYYQ / RXYQ) Access all technical information on RWEYQ-T9 at my.daikin.eu or click here Outdoor unit Capacity range Cooling capacity Heating capacity Prated,c Prated,h Max. 6°CWB Recommended combination ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index Min. connection Nom. Max. Dimensions Unit HeightxWidthxDepth Weight Unit Sound power level Cooling Nom. Sound pressure level Cooling Nom. Inlet water tempe- Cooling Min.~Max. Operation range rature Heating Min.~Max. Temperature around Max. casing Humidity around Cooling~Heating Max. casing Refrigerant Type/GWP Charge Piping connections Liquid OD Gas OD HP/LP gas OD Drain Size Inlet/Outlet Size Water Total piping length System Actual Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) 104 RWEYQ HP kW kW kW % % 8T9 8 22.4 25.0 25.0 4 x FXMQ50P7VEB 326.8 524.3 8.4 13.3 10T9 10 28.0 31.5 31.5 4 x FXMQ63P7VEB 307.8 465.9 7.9 11.8 100.0 125.0 12T9 12 33.5 37.5 37.5 6 x FXMQ50P7VEB 359.0 436.0 9.2 11.1 14T9 14 40.0 45.0 45.0 1 x FXMQ50P7VEB + 5 x FXMQ63P7VEB 330.7 397.1 8.5 10.1 150.0 175.0 450.0 525.0 64 (1) 300.0 mm kg dBA dBA °CDB °CWB °CDB 375.0 980x767x560 195 65.0 48.0 197 71.0 50.0 72.0 56.0 74.0 58.0 10~45 10~45 40 % 80~80 R-410A/2,087.5 kg/TCO2Eq mm mm mm m Hz/V A 7.9/16.5 9.52 19.1 (2) 15.9 (3) / 19.1 (4) 22.2 (2) 19.1 (3) / 22.2 (4) 19.1 (3) / 28.6 (4) 14mm OD/ 10mm ID ISO 228-G1 1/4 B/ISO 228-G1 1/4 B 500 3N~/50/380-415 20 9.6/20.0 12.7 28.6 (2) 22.2 (3) / 28.6 (4) 25 Stage 1 heat recovery between indoor units Cooling Extracted heat delivers free hot water and heating Hot water Heating + Domestic hot water 45°C - 75°C Air handling unit 25°C - 75°C Low temp. radiator Underfloor heating VRV indoor units Daikin solar panel BS-Box Domestic hot water tank 45°C - 75°C BS-Box 25°C - 35°C RWEYQ-T9 Heating only hydrobox for VRV Cooling tower (Closed type), boiler Underfloor heating Stage 2 heat recovery between outdoor units or Low temp. radiator 25°C - 45°C 25°C - 35°C Liquid pipe Gas pipe Discharge gas pipe Hot water Reversible low temperature hydrobox Heat rejected to loop * Above system configuration are for illustration purpose only. RWEYQ HP kW kW kW % % Actual Outdoor unit System System Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Capacity range Cooling capacity Prated,c Heating capacity Prated,h Max. 6°CWB Recommended combination ηs,c ηs,h SEER SCOP Maximum number of connectable indoor units Indoor index Min. connection Nom. Max. Piping connections Liquid OD Gas OD HP/LP gas OD Total piping length System Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Heat absorbed from loop Heat absorbed from loop Outdoor unit System System Outdoor unit module 1 Outdoor unit module 2 Capacity range Cooling capacity Prated,c Heating capacity Prated,h Max. 6°CWB ηs,c ηs,h SEER SCOP Recommended combination Maximum number of connectable indoor units Indoor index Min. connection Nom. Max. Piping connections Liquid OD Gas OD HP/LP gas OD Total piping length System Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Heat rejected to loop mm mm mm m Hz/V A RWEYQ HP kW kW kW % % Actual mm mm mm m Hz/V A 16T9 18T9 20T9 22T9 24T9 26T9 28T9 RWEYQ8T RWEYQ10T RWEYQ12T RWEYQ14T RWEYQ8T RWEYQ10T RWEYQ12T RWEYQ14T 16 18 20 22 24 26 28 44.8 50.4 56.0 61.5 67.0 73.5 80.0 50.0 56.5 62.5 69.0 75.0 82.5 90.0 50.0 56.5 62.5 69.0 75.0 82.5 90.0 307.6 308.7 298.1 311.3 342.6 322.5 306.1 459.2 491.1 466.8 447.9 434.5 406.9 387.9 7.9 7.7 8.0 8.8 8.3 7.9 11.7 12.5 11.9 11.4 11.1 10.4 9.9 4 x FXMQ63P7VEB 6 x FXMQ50P7VEB 4 x FXMQ50P7VEB 8 x FXMQ63P7VEB 12 x FXMQ50P7VEB 7 x FXMQ50P7VEB 2 x FXMQ50P7VEB + 2 x FXMQ80P7VEB + 4 x FXMQ63P7VEB + 4 x FXMQ63P7VEB + 5 x FXMQ63P7VEB + 10 x FXMQ63P7VEB 64 (1) 200.0 225.0 250.0 275.0 300.0 325.0 350.0 600.0 675.0 750.0 825.0 900.0 975.0 1,050.0 12.7 15.9 19.1 28.6 (2) 34.9 (2) 28.6 (3) / 28.6 (4) 28.6 (3) / 28.6 (4) 28.6 (3) / 34.9 (4) 22.2 (3) / 28.6 (4) 500 3N~/50/380-415 32 35 40 50 30T9 32T9 34T9 36T9 38T9 40T9 42T9 RWEYQ10T RWEYQ12T RWEYQ14T RWEYQ10T RWEYQ12T RWEYQ14T RWEYQ10T RWEYQ12T RWEYQ14T 30 32 34 36 38 40 42 84.0 89.5 95.0 100.5 107.0 113.5 120.0 94.5 100.5 106.5 112.5 120.0 127.5 135.0 94.5 100.5 106.5 112.5 120.0 127.5 135.0 12 x FXMQ63P7VEB 6 x FXMQ50P7VEB 12 x FXMQ50P7VEB 18 x FXMQ50P7VEB 13 x FXMQ50P7VEB 8 x FXMQ50P7VEB 3 x FXMQ50P7VEB + 8 x FXMQ63P7VEB + 4 x FXMQ63P7VEB + 5 x FXMQ63P7VEB + 10 x FXMQ63P7VEB 15 x FXMQ63P7VEB 308.3 318.2 342.5 352.3 338.8 341.4 332.9 467.2 456.1 447.0 438.5 419.4 404.4 391.2 7.9 8.2 8.8 9.0 8.7 8.5 11.9 11.6 11.4 11.2 10.7 10.3 10.0 64 (1) 375.0 400.0 425.0 450.0 475.0 500.0 525.0 1,125.0 1,200.0 1,275.0 1,350.0 1,425.0 1,500.0 1,575.0 19.1 (2) 34.9 41.3 28.6 (3) / 34.9 (4) 41.3 (3) / 34.9 (4) 500 3N~/50/380-415 50 63 80 (1) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) | (2) In case of heat pump system, gas pipe is not used (3) In case of heat recovery system (4) In case of heat pump system 105 VRV Indoor units One of the widest ranges on the market, it currently compromises no less than 26 different stylish and elegant models in 116 different variants. All designed to maximise comfort, minimise operating noise and simplify installation and servicing. 106 VRV IV indoor units VRV indoor units 107 Ceiling mounted cassette units NEW PANELS UNIQUE FXFQ-B114 UNIQUE FXZQ-A115 FXCQ-A116 UNIQUE FXKQ-MA117 Concealed ceiling units Auto cleaning filter for concealed ceiling units SLIMMEST IN CLASS Multi zoning kit 42 118 FXDQ-A3119 FXSQ-A 120 FXMQ-P7 / FXMQ-MB 121 Wall mounted unit FXAQ-A123 Ceiling suspended units FXHQ-A124 UNIQUE FXUQ-A125 Floor standing units SLIMMEST IN CLASS FXNQ-A126 FXLQ-P127 Stylish indoor units 128 BPMKS 128 Accessory to connect stylish indoor units 128 Wall mounted UNIQUE DESIGN UNIT FTXJ-MW/MS130 C/FTXA-AW/BS/BT/BB131 Floor standing UNIQUE RADIATING PANEL FVXG-K132 FVXM-F133 107 VRV Indoor Concealed ceiling unit with high esp Round flow cassette Slim concealed ceiling unit 108 VRV Indoor Concealed floor standing unit Hot water production Fully flat cassette 109 Indoor units Products overview Type Model Ceiling mounted cassette Concealed ceiling Wall mounted 15 20 25 32 40 50 63 71 80 100 125 140 200 250 FXFQ-B Unique design that integrates fully flat into the ceiling › Perfect integration in standard architectural ceiling tiles › Blend of iconic design and engineering excellence › Intelligent sensors save energy and maximize comfort › Small capacity unit developed for small or well-insulated rooms › Flexibility to suit every room layout FXZQ-A 2-way blow ceiling mounted cassette Thin, lightweight design installs easily in narrow ceiling spaces › Depth of all units is 620mm, ideal for narrow ceiling spaces › Flexibility to suit every room layout › Reduced energy consumption thanks to DC fan motor › The flaps close entirely when the unit is not operating › Optimum comfort with automatic air flow adjustment to the required load FXCQ-A Ceiling mounted corner cassette 1-way blow unit for corner installation › Compact dimensions enable installation in narrow ceiling voids › Flexible installation thanks to different air discharge options FXKQ-MA Slim concealed ceiling unit Slim design for flexible installation › Compact dimensions enable installation in narrow ceiling voids › Medium external static pressure up to 44Pa › Only grilles are visible › Small capacity unit developted for small of well-insulated rooms › Reduced energy consumption thanks to DC fan motor FXDQ-A3 Auto cleaning filter option Multi zoning option Concealed ceiling unit with medium ESP Slimmest yet most powerfull medium static pressure unit on the market! › S limmest unit in class, only 245mm › Low operating sound level › Medium external static pressure up to 150Pa facilitates using flexible ducts of varying lengths › Automatic air flow adjustment function measures the air volume and static pressure and adjusts it towards the nominal air flow, guaranteeing comfort FXSQ-A Multi zoning option Concealed ceiling unit with high ESP ESP up to 200, ideal for large sized spaces › Optimum comfort guaranteed no matter the length of ductwork or type of grilles, thanks to automatic air flow adjustment › Reduced energy consumption thanks to DC fan motor › Flexible installation as the air suction direction can be altered from rear to bottom suction FXMQ-P7 Concealed ceiling unit with high ESP ESP up to 270, ideal for extra large sized spaces › Only grilles are visible › Large capacity unit: up to 31.5 kW heating capacity FXMQ-MB For rooms with no false ceilings nor free floor space › Flat, stylish front panel is more easy to clean › Small capacity unit developted for small of well-insulated rooms › Reduced energy consumption thanks to DC fan motor › The air is comfortably spread up- and downwards thanks to 5 different discharge angles FXAQ-A For wide rooms with no false ceilings nor free floor space › Ideal for comfortable air flow in wide rooms thanks to Coanda effect › Rooms with ceilings up to 3.8m can be heated or cooled very easily! › Can easily be installed in both new and refurbishment projects › Can even be mounted in corners or narrow spaces without any problem › Reduced energy consumption thanks to DC fan motor FXHQ-A Unique Daikin unit for high rooms with no false ceilings nor free floor space › Rooms with ceilings up to 3.5m can be heated up or cooled down very easily! › Can easily be installed in both new and refurbishment projects › Flexibility to suit every room layout › Reduced energy consumption thanks to DC fan motor FXUQ-A For perimeter zone air conditioning › Can be installed in front of glass walls or free standing as both the front and the back are finished › Ideal for installation beneath a window › Requires very little installation space › Wall mounted installation facilitates cleaning beneath the unit FXLQ-P Ideal for installation in offices, hotels and residential applications › Discretely concealed in the wall, leaving only the suction and discharge grilles visible › Can even be installed underneath a window › Requires very little installation space as the depth is only 200mm › High ESP allows flexible installation FXNQ-A UNIQUE Ceiling suspended Product name 360° air discharge for optimum efficiency and comfort › Auto cleaning function ensures high efficiency › Intelligent sensors save energy and maximize comfort › Flexibility to suit every room layout › Lowest installation height in the market! › Widest choice ever in decoration panel designs and colors Round flow cassette Floor standing Capacity class (kW) UNIQUE Fully flat cassette Wall mounted unit Ceiling suspended unit UNIQUE 4-way blow ceiling suspended unit Floor standing unit Concealed floor standing unit Cooling capacity (kW)1 1.7 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0 Heating capacity (kW)2 1.9 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5 (1) Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m (2) Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m 110 Indoor units Products overview Stylish indoor units Depending on the application, Split and Sky Air indoor units can be connected to our VRV IV and VRV IV S-series outdoor units. Refer to the outdoor unit portfolio for combination restrictions. Concealed ceiling Wall mounted Ceiling suspended Floor standing 20 25 35 42 50 60 71 FCAG-B Fully flat cassette FFA-A9 Slim concealed ceiling unit FDXM-F9 Concealed ceiling unit with inverter-driven fan FBA-A(9) Daikin Emura Wall mounted unit FTXJ-MW/MS Stylish Wall mounted unit FTXA-AW/ BS/BB/BT Perfera Wall mounted unit CTXM-N FTXM-N Ceiling suspended unit FHA-A(9) Nexura floor standing unit FVXG-K Floor standing unit FVXM-F Concealed floor standing unit FNA-A9 (incl. auto-cleaning function1) Ceiling mounted cassette 15 RXYLQ-T Product name Round flow cassette RWEYQ-T94 Model RXYSCQ-TV13 RXYSQ-TV93 RXYSQ-TY9/TY13 Type RXYQ-U Capacity class (kW) RYYQ-U Connectable outdoor unit 1 Decoration panel BYCQ140DG9 or BYCQ140DGF9 + BRC1E* or BRC1H* needed 2 To connect stylish indoor units a BPMKS unit is needed 3 A mix of RA indoor units and VRV indoor units is not allowed. 4 Only in heat pump operation Auto cleaning filter option 111 Indoor units We care Benefits overview Home leave operation During absence, indoor comfort levels can be maintained Fan only The air conditioner can be used as fan, blowing air without cooling or heating Auto cleaning filter Floor and presence sensor Auto cooling-heating changeover Automatically selects cooling or heating mode to achieve the set temperature Air treatment Whisper quiet When starting to warm up or when the thermostat is off, the air discharge direction is set horizontally and the fan to low speed, to prevent draught. After warming up, air discharge and fan speed are set as desired Daikin indoor units are whisper quiet. Also the outdoor units are guaranteed not to disturb the quiet of the neightbourhood Air filter Removes airborne dust particles to ensure a steady supply of clean air Humidity control Comfort Draught prevention The filter automatically cleans itself. Simplicity of upkeep means optimum energy efficiency and maximum comfort without the need for expensive or time-consuming maintenance The presence sensor directs the air away from any person detected in the room. The floor sensor detects the average floor temperature and ensures an even temperature distribution between ceiling and floor Dry programme Allows humidity levels to be reduced without variations in room temperature Other funtcions Remote control & timer Air flow Ceiling soiling prevention 112 Vertical auto swing The air discharge of the indoor unit is specially designed to prevent air being blown against the ceiling to prevent ceiling stains Possibility to select automatic vertical moving of the air discharge louvre, for uniform air flow and temperature distribution Fan speed steps Multiple fan speeds to select,to optimize comfort levels Individual flap control Individual flap control via the wired remote controller makes it simple to fix the position of each flap individually, to suit any new room configuration. Optional closure kits are available as well Weekly timer Timer can be set to start and stop operation anytime on a daily or weekly basis Infrared remote control Infrared remote control with LCD to remotely control your indoor unit Wired remote control Wired remote control to remotely control your indoor unit Centralised control Centralised control to to control several indoor units from one single point Multi zoning Allows up to 6 individual climate zones with one indoor unit Auto-restart The unit restarts automatically at the original settings after power failure Self-diagnosis Simplifies maintenance by indicating system faults or operating anomalies Drain pump kit Facilitates condensation draining from the indoor unit Multi tenant The indoor unit’s main power supply can be turned off when leaving the building or for servicing purposes Ceiling mounted cassette units Wall mounted unit Concealed ceiling units Ceiling suspended units Floor standing units FXFQ-B FXZQ-A FXCQ-A FXKQ-MA FXDQ-A3 FXSQ-A FXMQ-P7 FXMQ-MB FXAQ-A FXHQ-A FXUQ-A FXNQ-A FXLQ-P G1* (G3* in case of auto cleaning panel) G1* G1* 3 + auto 3 + auto 3 + auto 2 Standard Standard Standard Standard Standard Standard Standard Optional ( ) ( ) ( ) G1* G1* F8* (optional) G1* G1* G1* G1* 3 2 Optional Optional Standard ( ) ( ) 3 3 + auto 3 2 2 3 3 + auto * Filter grade category are an indication, filters are not certified. 113 FXFQ-B Round flow cassette 360° air discharge for optimum efficiency and comfort ʯ Automatic filter cleaning results in higher efficiency & comfort and lower maintenance costs. ʯ Two optional intelligent sensors improve energy efficiency and comfort ʯ Widest choice ever in decoration panels: Designer, standard and autocleaning panels in white (RAL9010) and black (RAL9005) ʯ Bigger flaps and unique swing pattern improve equal air distribution ʯ Individual flap control: flexibility to suit every room layout without changing the location of the unit! ʯ Lowest installation height in the market: 214mm for class 20-63 ʯ Optional fresh air intake ʯ Branch duct discharge allows to optimize air distribution in irregular shaped rooms or to supply air to small adjacent rooms FXFQ-B BRC1H519W7 BRC7FB532F Main unit Branch discharge Main discharge ʯ Standard drain pump with 675mm lift increases flexibility and installation speed White panel White auto cleaning panel Black panel Black design panel 675 mm Access all technical information on FXFQ-B at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Dimensions Weight Casing Decoration panel Fan Total capacity Total capacity Cooling Heating Unit Unit Material Model Nom. Nom. Nom. Nom. HeightxWidthxDepth Dimensions Weight Air flow rate 50Hz HeightxWidthxDepth Cooling Heating Low/High Low/High Air filter Type Sound power level Cooling High Sound pressure level Cooling Low/Nom./High Heating Low/Nom./High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control 114 FXFQ kW kW kW kW mm kg mm kg m³/min m³/min dBA dBA dBA mm mm Hz/V A 20B 2.20 2.5 25B 2.80 3.2 32B 3.60 4.0 40B 4.50 5.0 0.04 0.04 19 204x840x840 20 50B 5.60 6.3 0.05 0.05 63B 7.10 8.0 0.06 0.06 80B 100B 9.00 11.20 10.0 12.5 0.09 0.12 0.09 0.11 246x840x840 24 125B 14.00 16.0 0.19 0.18 288x840x840 26 21 Galvanised steel plate Standard panels: BYCQ140E - white with grey louvers / BYCQ140EW - full white / BYCQ140EB - black Auto cleaning panels BYCQ140EGF - white / BYCQ140EGFB - black Designer panels: BYCQ140EP - white / BYCQ140EPB - black Standard panels: 50x950x950 / Auto cleaning panels: 130x950x950 / Designer panels: 50x950x950 Standard panels: 5.4 / Auto cleaning panels: 10.3 / Designer panels: 5.4 8.8/12.5 9.5/13.6 10.5/15.0 10.5/16.5 12.4/22.8 12.4/26.5 19.9/33.0 8.8/12.5 9.5/13.6 10.5/15.0 10.5/16.5 12.4/22.8 12.4/26.5 19.9/33.0 Resin net 49 51 53 55 60 61 30.0/33.0/35.0 30.0/34.0/38.0 30.0/37.0/43.0 36.0/41.0/45.0 28.0/29.0/31.0 29.0/31.0/33.0 30.0/33.0/35.0 30.0/34.0/38.0 30.0/37.0/43.0 36.0/41.0/45.0 28.0/29.0/31.0 29.0/31.0/33.0 R-410A/2,087.5 6.35 9.52 12.70 15.90 VP25 (O.D. 32 / I.D. 25) 1~/50/60/220-240/220 16 BRC7FA532F / BRC7FA532FB / BRC7FB532F / BRC7FB532FB BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 FXZQ-A Fully flat cassette Unique design in the market that integrates fully flat into the ceiling ʯ Fully flat integration in standard architectural ceiling tiles, leaving only 8mm ʯ Remarkable blend of iconic design and engineering excellence with an elegant finish in white or a combination of silver and white ʯ Two optional intelligent sensors improve energy efficiency and comfort ʯ 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc. ʯ Individual flap control: flexibility to suit every room layout without changing the location of the unit! FXZQ-A BRC1H519W7, BRC7F530W-S ʯ Optional fresh air intake ʯ Standard drain pump with 630mm lift increases flexibility and installation speed 500 mm Access all technical information on FXZQ-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Dimensions Weight Casing Decoration panel Decoration panel 2 Decoration panel 3 Decoration panel 4 Fan Total capacity Total capacity Cooling Heating Unit Unit Material Model Colour Dimensions Weight Model Colour Dimensions Weight Model Colour Dimensions Weight Model Colour Dimensions Weight Air flow rate 50Hz Nom. Nom. Nom. Nom. HeightxWidthxDepth HeightxWidthxDepth mm kg HeightxWidthxDepth mm kg HeightxWidthxDepth mm kg HeightxWidthxDepth mm kg m³/min m³/min Cooling Heating Low/High Low/High Air filter Type Sound power level Cooling High Sound pressure level Cooling Low/Nom./High Heating Low/Nom./High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control Dimensions do not include control box FXZQ kW kW kW kW mm kg dBA dBA dBA mm mm Hz/V A 15A 1.70 1.90 20A 2.20 2.50 0.043 0.036 25A 2.80 3.20 32A 3.60 4.00 0.045 0.038 40A 4.50 5.00 0.059 0.053 50A 5.60 6.30 0.092 0.086 260x575x575 15.5 16.5 18.5 Galvanised steel plate BYFQ60C2W1W White (N9.5) 46x620x620 2.8 BYFQ60C2W1S SILVER 46x620x620 2.8 BYFQ60B2W1 White (RAL9010) 55x700x700 2.7 BYFQ60B3W1 WHITE (RAL9010) 55x700x700 2.7 6.5/8.5 6.5/8.7 6.5/9.0 7.0/10.0 8.0/11.5 10.0/14.5 6.5/8.5 6.5/8.7 6.5/9.0 7.0/10.0 8.0/11.5 10.0/14.5 Resin net 49 50 51 54 60 25.5/28.0/31.5 25.5/29.5/32.0 25.5/30.0/33.0 26.0/30.0/33.5 28.0/32.0/37.0 33.0/40.0/43.0 25.5/28.0/31.5 25.5/29.5/32.0 25.5/30.0/33.0 26.0/30.0/33.5 28.0/32.0/37.0 33.0/40.0/43.0 R-410A/2,087.5 6.35 12.7 VP20 (I.D. 20/O.D. 26) 1~/50/60/220-240/220 16 BRC7EB530W (standard panel) / BRC7F530W (white panel) / BRC7F530S (grey panel) BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 115 FXCQ-A 2-way blow ceiling mounted cassette Thin, lightweight design installs easily in narrow corridors ʯ Depth of all units is 620mm, ideal for narrow spaces ʯ Individual flap control: flexibility to suit every room layout without changing the location of the unit! FXCQ20-40A ʯ Stylish unit blends easily with any interior. The flaps close entirely when the unit is not operating and there are no air intake grilles visible ʯ Fresh air intake integrated in the same system thus reducing installation cost as no additional ventilation device is required BRC1H519W7, BRC7F5C52 Fresh air intake opening in casing ʯ Branch duct discharge allows to optimize air distribution in irregular shaped rooms or to supply air to small adjacent rooms * Brings in up to 10% of fresh air into the room ʯ Optimum comfort guaranteed with automatic air flow adjustment to the required load ʯ Maintenance operations can be performed by removing the front panel Branch discharge Main unit Main discharge ʯ Standard drain pump with 580mm lift increases flexibility and installation speed 580 mm Access all technical information on FXCQ-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Total capacity Nom. Total capacity Nom. Cooling Nom. Heating Nom. Dimensions Unit HeightxWidthxDepth Weight Unit Casing Material Decoration panel Model Colour Dimensions HeightxWidthxDepth Weight Air flow rate - 50Hz Cooling Low/High Fan Air filter Type Sound power level Cooling Nom./High Sound pressure level Cooling Low/Nom./High Heating Low/Nom./High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control 116 FXCQ kW kW kW kW mm kg mm kg m³/min 20A 2.2 2.5 0.031 0.028 7.5/10.5 dBA 46/48 dBA 28.0/30.0/32.0 dBA 28.0/30.0/32.0 mm mm Hz/V A 25A 2.8 3.2 32A 3.6 4.0 40A 4.5 5.0 0.041 0.037 50A 63A 5.6 7.1 6.3 8.0 0.039 0.059 0.063 0.035 0.056 0.060 305x775x620 305x990x620 19 22 25 Galvanised steel plate BYBCQ40HW1 BYBCQ63HW1 Fresh white (6.5Y 9.5/0.5) 55x1,070x700 55x1,285x700 10 11 8/11.5 8.5/12 10.5/15 11.5/16 Resin net with mold resistance 47/50 48/50 49/52 51/53 53/55 29.0/31.0/34.0 30.0/32.0/34.0 31.0/33.0/36.0 31.0/35.0/37.0 32.0/37.0/39.0 29.0/31.0/34.0 30.0/32.0/34.0 31.0/33.0/36.0 31.0/35.0/37.0 32.0/37.0/39.0 R-410A/2,087.5 6.35 12.7 VP25 (O.D. 32 / I.D. 25) 1~/50/220-240 16 BRC7C52 BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 80A 125A 9.0 14.0 10.0 16.0 0.090 0.149 0.086 0.146 305x1,445x620 33 38 BYBCQ125HW1 55x1,740x700 13 18.5/26 22.5/32 54/58 33.0/38.0/42.0 33.0/38.0/42.0 9.52 15.9 58/62 38.0/42.0/46.0 38.0/42.0/46.0 FXKQ-MA Ceiling mounted corner cassette 1-way blow unit for corner installation ʯ Compact dimensions, can easily be mounted in a narrow ceiling void (only 220mm ceiling space required, 195 with panel spacer, available as accessory) ʯ Optimum air flow conditions are created by either downward air discharge or frontal air discharge (via optional grille) or a combination of both FXKQ-MA Downward discharge Frontal discharge BRC1H519W7, BRC4C61 Closed decoration panel Combination ʯ Maintenance operations can be performed by removing the front panel ʯ Standard drain pump with 330mm lift increases flexibility and installation speed 330 mm Access all technical information on FXKQ-MA at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Dimensions Weight Casing Decoration panel Fan Air filter Sound power level Sound pressure level Refrigerant Piping connections Power supply Current - 50Hz Control systems Total capacity Nom. Total capacity Nom. Cooling Nom. Heating Nom. Unit HeightxWidthxDepth Unit Material Model Colour Dimensions HeightxWidthxDepth Weight Air flow rate - 50Hz Cooling Low/High Type Cooling High Cooling Low/High Type/GWP Liquid OD Gas OD Drain Phase/Frequency/Voltage Maximum fuse amps (MFA) Infrared remote control Wired remote control FXKQ kW kW kW kW mm kg mm kg m³/min dBA dBA mm mm Hz/V A 25MA 2.8 3.2 32MA 3.6 4.0 0.066 0.046 40MA 4.5 5.0 0.076 0.056 215x1,110x710 31 Galvanised steel plate BYK45FJW1 White 70x1,240x800 8.5 9/11 10/13 Resin net with mold resistance 54 56 33.0/38.0 34.0/40.0 R-410A/2,087.5 6.35 12.7 VP25 (O.D. 32 / I.D. 25) 1~/50/60/220-240/220 15 BRC4C61 BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 63MA 7.10 8.00 0.105 0.085 215x1,310x710 34 BYK71FJW1 70x1,440x800 9.5 15/18 58 37.0/42.0 9.52 15.9 117 Multi zoning kit The multi-zoning system is a room-by-room controller. It is fitted with motorised dampers, which immediately adapt using Daikin ducted solutions. This system supports control of up to 8 zones via a centralised thermostat located in the main room and individual thermostats for each of the zones. Benefits How does it work? Increased comfort 20°C › Increases comfort levels by allowing more individual zone control - Up to 8 individual zones can be served thanks to separate modulating dampers - Individual thermostat for room-by-room or zone-by-zone control 19°C Zoning box: fully pre-assembled plenum with dampers 21°C Easy to install › Automatic air flow adjustment according to the demand › Easy to install, integrates with the Daikin indoor units and system controls › Time saving as plenum comes fully pre-assembled with dampers, and control boards › Reduces the amount of refrigerant required in the installation Plug and play plenum Individual zone thermostats Blueface - Airzone Main Thermostat › Color graphic interface for controlling zones › Wired communication Concealed ceiling unit Motorized dampers Airzone Zone Thermostat › Graphic interface with low-energy e-ink screen for controlling zones › Radio communication Airzone Zone Thermostat › Thermostat with buttons for controlling the temperature › Radio communication Electronic control panel AZCE6BLUEFACECB AZCE6THINKRB AZCE6LITERB Compatibility FDXM-F9 Number of motorised dampers 2 3 4 Standard Ceiling Void 5 6 7 8 Compact Ceiling Void 118 2 Reference AZEZ6DAIST07XS2 AZEZ6DAIST07S2 AZEZ6DAIST07XS3 AZEZ6DAIST07S3 AZEZ6DAIST07S4 AZEZ6DAIST07M4 AZEZ6DAIST07M5 AZEZ6DAIST07L5 AZEZ6DAIST07M6 AZEZ6DAIST07L6 AZEZ6DAIST07L7 AZEZ6DAIST07XL7 AZEZ6DAIST07L8 AZEZ6DAIST07XL8 AZEZ6DAISL01S2 Dimensions H x W x D (mm) FBA-A(9) 300 x 930 x 454 • • • • 300 x 930 x 454 • • • • • • • • 300 x 1,638 x 454 • • 300 x 1,140 x 454 • • • 515 x 1,425 x 454 • • • • • • 515 x 1,425 x 454 • • • 3 AZEZ6DAISL01S3 210 x 720 x 444 AZEZ6DAISL01M4 210 x 930 x 444 5 AZEZ6DAISL01L5 210 x 1,140 x 444 FXSQ-A • • • • 300 x 1,425 x 454 4 FXDQ-A3 • • 300 x 930 x 454 210 x 720 x 444 ADEA-A 25 35 50 60 35 50 60 71 100 125 140 71 100 125 15 20 25 32 40 50 63 15 20 25 32 40 50 63 71 80 100 125 140 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • FXDQ-A3 rear suction Slim concealed ceiling unit Slim design for flexible installation ʯ Compact dimensions, can easily be mounted in a ceiling void of only 240mm outblow SERIE A (15, 20, 25, 32) bottom suction 200 mm FXDQ15-32A3 700 mm 50 mm ʯ Medium external static pressure up to 44Pa facilitates unit use with flexible ducts of varying lengths ʯ Discretely concealed in the wall: only the suction and discharge grilles are visible ʯ 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc. ʯ Auto cleaning filter option ensures maximum efficiency, comfort and reliability by regular filter cleaning ʯ Multi zoning kit allows multiple individually-controlled climate zones to be served by one indoor unit ʯ Flexible installation, as the air suction direction can be altered from rear to bottom suction BRC1H519W7, BRC4C65 ʯ Standard drain pump with 750mm lift increases flexibility and installation speed 750 mm Access all technical information on FXDQ-A3 at my.daikin.eu or click here Access all technical information on BAE20A at my.daikin.eu or click here Auto cleaning filter option More information on multi zoning kit in the controls chapter Indoor unit Cooling capacity Heating capacity Power input - 50Hz Total capacity Total capacity Cooling Heating Nom. Nom. Nom. Nom. Required ceiling void > Dimensions Unit HeightxWidthxDepth Weight Unit Casing Material Air flow rate - 50Hz Cooling Low/High Fan External static Nom./High pressure - 50Hz Air filter Type Sound power level Cooling High Sound pressure level Cooling Low/Nom./High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control FXDQ kW kW kW kW mm mm kg 15A3 1.70 1.90 m³/min Pa 6.4/7.5 20A3 2.20 2.50 25A3 2.80 3.20 32A3 3.60 4.00 0.071 0.068 40A3 4.50 5.00 0.078 0.075 50A3 5.60 6.30 0.099 0.096 63A3 7.10 8.00 0.110 0.107 240 200x750x620 22.0 200x950x620 26.0 200x1,150x620 29.0 Galvanised steel dBA 50 dBA 27.0/31.0/32.0 mm mm Hz/V A 6.4/8.0 8.5/10.5 10/30.0 Removable / washable 51 52 27.0/31.0/33.0 28.0/32.0/34.0 R-410A/2,087.5 6.35 12.7 VP20 (I.D. 20/O.D. 26) 1~/50/60/220-240/220 16 BRC4C65 / BRC4C66 BRC1H519W7/S7/K7 / BRC1E53A/B/C/ BRC1D52 10.0/12.5 15/44.0 13.0/16.5 53 29.0/33.0/35.0 54 30.0/34.0/36.0 9.52 15.9 119 FXSQ-A Concealed ceiling unit with medium ESP Slimmest yet most powerful medium static pressure unit on the market outblow ʯ Slimmest unit in class, only 245mm (300mm built-in height) and therefore narrow ceiling voids are no longer a challenge rear suction bottom suction 245 mm FXSQ-A ʯ Quiet operation: down to 25dBA sound pressure level ʯ Medium external static pressure up to 150Pa facilitates using flexible ducts of varying lengths ʯ Possibility to change ESP via wired remote control allows optimisation of the supply air volume ʯ Discretely concealed in the wall: only the suction and discharge grilles are visible ʯ 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc. ʯ Multi zoning kit allows multiple individually-controlled climate zones to be served by one indoor unit ʯ Optional fresh air intake ʯ Flexible installation: air suction direction can be altered from rear to bottom suction and choice between free use or connection to optional suction grilles ////////////////////////////////////////// For free use into a false ceiling ////////////////////////////////////////// For connecting onto a suction canvas (not supplied by Daikin) BRC1H519W7, BRC4C65 ʯ Standard built-in drain pump with 625mm lift increases flexibility and installation speed 625 mm ////////////////////////////////////////// For direct connection to Daikin panel (via EKBYBSD kit) External static pressure (Pa) Automatic Airflow Adjustment function Automatically selects the most appropriate fan curve to achieve the units’ nominal air flow within ±10% Fan characteristic curves Air flow (rated) Air flow (actual) Why? After installation the real ducting will frequently differ from the initially calculated air flow resistance the real air flow may be much lower or higher than nominal , leading to a lack of capacity or uncomfortable air temperature Automatic Airflow Adjustment function will adapt the unit’s fan speed to any ducting automatically (10 or more fan curves are a­ vailable on every model), making installation much faster Access all technical information on FXSQ-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Total capacity Nom. Total capacity Nom. Cooling Nom. Heating Nom. Dimensions Unit HeightxWidthxDepth Weight Unit Casing Material Fan Air flow rate Cooling Low/High 50Hz Heating Low/High External static Nom./High pressure - 50Hz Air filter Type Sound power level Cooling High Sound pressure level Cooling Low/Nom./High Heating Low/Nom./High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control 120 Air flow (with automatic adjustment) Duct resistance curves ± Air flow (m3/min) More information on multi zoning kit in the controls chapter FXSQ kW kW kW kW mm kg m³/min m³/min Pa 15A 1.70 1.90 6.5/8.7 6.5/8.7 dBA dBA 25.0/28.0/29.5 dBA 26.0/29.0/31.5 mm mm Hz/V A 20A 25A 2.20 2.80 2.50 3.20 0.090 0.086 245x550x800 23.5 32A 3.60 4.00 0.096 0.092 6.5/9.0 6.5/9.0 7.0/9.5 7.0/9.5 30/150 54 25.0/28.0/30.0 26.0/29.0/32.0 24.0 40A 50A 63A 80A 100A 125A 140A 4.50 5.60 7.10 9.00 11.20 14.00 16.00 5.00 6.30 8.00 10.0 12.5 16.0 18.0 0.151 0.154 0.188 0.213 0.290 0.331 0.386 0.147 0.150 0.183 0.209 0.285 0.326 0.382 245x1,550x800 245x700x800 245x1,000x800 245x1,400x800 28.5 29.0 35.5 36.5 46.0 47.0 51.0 Galvanised steel plate 28.0/39.0 11.0/15.0 11.0/15.2 15.0/21.0 16.0/23.0 23.0/32.0 26.0/36.0 11.0/15.0 11.0/15.2 15.0/21.0 16.0/23.0 23.0/32.0 26.0/36.0 28.0/39.0 40/150 50/150 Resin net 60 59 61 64 29.0/32.0/35.0 27.0/30.0/33.0 29.0/32.0/35.0 31.0/34.0/36.0 33.0/36.0/39.0 34.0/38.0/41.5 29.0/34.0/37.0 28.0/32.0/35.0 30.0/34.0/37.0 31.0/34.0/37.0 33.0/37.0/40.0 34.0/38.5/42.0 R-410A/2,087.5 6.35 9.52 12.7 15.9 VP20 (I.D. 20/O.D. 26), drain height 625 mm 1~/50/60/220-240/220 16 BRC4C65 BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 55 26.0/29.0/31.0 27.0/30.0/33.0 FXMQ-P7 / FXMQ-MB Concealed ceiling unit with high ESP Ideal for large sized spaces FXMQ-P7: ESP up to 200 Pa outblow ʯ Possibility to change ESP via wired remote control allows optimisation of the supply air volume ʯ High external static pressure up to 200Pa facilitates extensive duct and grille network ʯ Discretely concealed in the wall: only the suction and discharge grilles are visible ʯ Fresh air intake integrated in the same system thus reducing installation cost as no additional ventilation device is required rear suction FXMQ50-80P7 bottom suction Fresh air intake opening in casing Fresh air intake position BRC1H519W7, BRC4C65 ʯ Standard built-in drain pump with 625mm lift increases flexibility and installation speed 625 mm * Brings in up to 10% of fresh air into the room ʯ Flexible installation, as the air suction direction can be altered from rear to bottom suction FXMQ-MB: ESP up to 270 Pa ʯ High external static pressure up to 270Pa facilitates extensive duct and grille network ʯ Discretely concealed in the wall: only the suction and discharge grilles are visible ʯ Large capacity unit: up to 31.5 kW heating capacity External static pressure (Pa) Automatic Airflow Adjustment function Automatically selects the most appropriate fan curve to achieve the units’ nominal air flow within ±10% Fan characteristic curves Air flow (rated) Why? Air flow (actual) After installation the real ducting will frequently differ from the initially calculated air flow resistance the real air flow may be much lower or higher than nominal , leading to a lack of capacity or uncomfortable air temperature Automatic Airflow Adjustment function will adapt the unit’s fan speed to any ducting automatically (10 or more fan curves are a­ vailable on every model), making installation much faster Air flow (with automatic adjustment) Duct resistance curves ± Access all technical information on FXMQ-P7 at my.daikin.eu or click here Indoor unit Cooling capacity Total capacity Nom. Nom. Heating capacity Total capacity Nom. Nom. Power input - 50Hz Cooling Nom. Heating Nom. Required ceiling void > Dimensions Unit HeightxWidthxDepth Weight Unit Casing Material Decoration panel Model Colour Dimensions HeightxWidthxDepth Weight Fan Air flow rate Cooling Low/High 50Hz Heating Low/High External static Nom./High pressure - 50Hz Air filter Type Sound power level Cooling Nom./High Sound pressure level Cooling Low/High Heating Low/High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control FXMQ kW kW kW kW kW kW mm mm kg mm kg m³/min m³/min Pa Access all technical information on FXMQ-MB at my.daikin.eu or click here 50P7 5.6 63P7 7.1 80P7 9.0 6.3 8.0 10.0 0.110 0.098 0.120 0.108 0.171 0.159 350 100P7 11.2 12.5 0.176 0.164 125P7 14.0 200MB 22.4 250MB 28.0 16.0 25.0 31.5 0.241 0.229 0.895 0.895 1.185 1.185 300x1,000x700 35 15.0/18.0 15.0/18.0 dBA dBA dBA -/61 37/41 37/41 mm mm 6.35 12.7 300x1,400x700 46 Galvanised steel plate BYBS71DJW1 BYBS125DJW1 White (10Y9/0.5) 55x1,100x500 55x1,500x500 4.5 6.5 16.0/19.5 20.0/25.0 23.0/32.0 28.0/39.0 16.0/19.5 20.0/25.0 23.0/32.0 28.0/39.0 100/200 -/64 38/42 38/42 Resin net -/67 -/65 -/70 40/44 40/44 39/43 39/43 R-410A/- Hz/V A Air flow (m3/min) 470x1,380x1,100 132 -x-x50/58 62/72 -/- 160/270 170/270 75/76 45/48 -/R-410A/2,087.5 9.52 15.9 VP25 (I.D. 25/O.D. 32) 1~/50/60/220-240/220 19.1 22.2 PS1B 1~/50/220-240 16 BRC4C65 BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 121 122 FXAQ-A Wall mounted unit For rooms with no false ceilings nor free floor space ʯ Flat, stylish front panel blends easily within any interior décor and is easier to clean ʯ Can easily be installed in both new and refurbishment projects ʯ The air is comfortably spread up- and downwards thanks to 5 different discharge angles that can be programmed via the remote control ʯ Maintenance operations can be performed easily from the front of the unit FXAQ-A BRC1H519W7, BRC7EA628 Access all technical information on FXAQ-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Total capacity Nom. Total capacity Nom. Cooling Nom. Heating Nom. Dimensions Unit HeightxWidthxDepth Weight Unit Fan Air flow rate Cooling Low/High 50Hz Air filter Type Sound power level Cooling High Sound pressure level Cooling Low/High Heating Low/High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control FXAQ kW 15A 1.7 kW kW kW mm kg m³/min 1.9 dBA dBA dBA mm mm Hz/V A 20A 2.2 25A 2.8 2.5 3.2 0.02 7.0/8.4 51.0 28.5/32.0 28.5/33.0 32A 3.6 40A 4.5 50A 5.6 63A 7.1 4.0 0.04 5.0 0.02 0.02 8.0 0.05 0.06 7.0/9.8 9.7/12.2 6.3 0.03 0.04 290x1,050x269 15 11.5/14.4 13.5/18.3 58.0 35.5/41.0 35.5/42.0 63.0 38.5/46.5 38.5/47.0 0.03 0.03 290x795x266 12 7.0/9.1 7.0/9.4 52.0 28.5/33.0 28.5/34.0 Washable resin net 55.0 28.5/37.5 33.5/37.0 28.5/38.5 33.5/38.0 R-410A/2,087.5 6.35 12.7 VP13 (I.D. 15/O.D. 18) 1~/50/220-240 16 BRC7EA628 / BRC7EA629 BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 53.0 28.5/35.0 28.5/36.0 9.52 15.9 123 FXHQ-A Ceiling suspended unit For wide rooms with no false ceilings nor free floor space ʯ Ideal for comfortable air flow in wide rooms thanks to Coanda effect: up to 100° discharge angle FXHQ63A ʯ Even rooms with ceilings up to 3.8m can be heated up or cooled down very easily without capacity loss ʯ Can easily be installed in both new and refurbishment projects ʯ Can easily be mounted in corners and narrow spaces, as it only needs 30mm lateral service space Air outlet Air inlet 30 or more (Service space) //////////////////////////// Obstruction //////////////////////////////////// //////////////////////////////////////////// ////////////////////// ////////////////////// 30 or more (Service space) BRC1H519W7, BRC7G53 ≥300 ʯ Fresh air intake integrated in the same system thus reducing installation cost as no additional ventilation device is required Fresh air intake opening in casing * Brings in up to 10% of fresh air into the room ʯ Reduced energy consumption thanks to specially developed DC fan motor and drain pump ʯ Stylish unit blends easily with any interior. The flaps close entirely when the unit is not operating and there are no air intake grilles visible Access all technical information on FXHQ-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Dimensions Weight Casing Fan Total capacity Total capacity Cooling Heating Unit Unit Material Air flow rate 50Hz Nom. Nom. Nom. Nom. HeightxWidthxDepth Cooling Heating Low/High Low/High Air filter Type Sound power level Cooling Nom./High Sound pressure level Cooling Low/Nom./High Heating Low/Nom./High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control 124 FXHQ kW kW kW kW mm kg 32A 3.6 4.0 0.107 0.107 235x960x690 24 m³/min m³/min 10.0/14.0 10.0/14.0 dBA dBA dBA 52/54 31.0/34.0/36.0 31.0/34.0/36.0 mm mm 6.35 12.7 Hz/V A 63A 7.1 8.0 0.111 0.111 235x1,270x690 33 Resin 14.0/20.0 14.0/20.0 Resin net with mold resistance 53/55 34.0/35.0/37.0 34.0/35.0/37.0 R-410A/2,087.5 100A 11.2 12.5 0.237 0.237 235x1,590x690 39 19.0/29.5 19.0/29.5 55/62 34.0/37.0/44.0 34.0/37.0/44.0 9.52 15.9 VP20 (I.D. 20/O.D. 26) 1~/50/220-240 16 BRC7GA53-9 BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 FXUQ-A 4-way blow ceiling suspended unit Unique Daikin unit for high rooms with no false ceilings nor free floor space ʯ Even rooms with ceilings up to 3.5m can be heated up or cooled down very easily without capacity loss ʯ Can easily be installed in both new and refurbishment projects ʯ Individual flap control: flexibility to suit every room layout without changing the location of the unit! FXUQ-A UNIQUE BRC1H519W7, BRC7C58 ʯ Stylish unit blends easily with any interior. The flaps close entirely when the unit is not operating and there are no air intake grilles visible ʯ Optimum comfort guaranteed with automatic air flow adjustment to the required load ʯ 5 different discharge angles between 0 and 60°can be programmed via the remote control ʯ Standard drain pump with 500mm lift increases flexibility and installation speed VP20 ≤500 ////////////////////////////////////////////// Access all technical information on FXUQ-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Dimensions Weight Casing Fan Total capacity Total capacity Cooling Heating Unit Unit Material Air flow rate 50Hz Nom. Nom. Nom. Nom. HeightxWidthxDepth FXUQ kW kW kW kW mm kg 71A 8.0 9.0 0.090 0.073 100A 11.2 12.5 0.200 0.179 198x950x950 26 27 Resin Cooling Heating Low/High Low/High Air filter Type Sound power level Cooling Nom./High Sound pressure level Cooling Low/Nom./High Heating Low/Nom./High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control m³/min m³/min 16.0/22.5 16.0/22.5 21.0/31.0 21.0/31.0 Resin net with mold resistance dBA dBA dBA mm mm Hz/V A 56/58 36.0/38.0/40.0 36.0/38.0/40.0 62/65 40.0/44.0/47.0 40.0/44.0/47.0 R-410A/2,087.5 9.52 15.9 I.D. 20/O.D. 26 1~/50/60/220-240/220-230 16 BRC7C58 BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 125 FXNQ-A Concealed floor standing unit Designed to be concealed in walls ʯ Discretely concealed in the wall: only the suction and discharge grilles are visible ʯ Requires very little installation space as the depth is only 200mm FXNQ-A BRC1H519W7, BRC4C65 ʯ Its low height (620 mm) enables the unit to fit perfectly beneath a window ʯ High ESP allows flexible installation Access all technical information on FXNQ-A at my.daikin.eu or click here Indoor unit Cooling capacity Heating capacity Power input - 50Hz Dimensions Weight Casing Fan Total capacity Total capacity Cooling Heating Unit Unit Material Air flow rate 50Hz Nom. Nom. Nom. Nom. HeightxWidthxDepth Cooling Low/High Heating Low/High Nom./High External static pressure - 50Hz Air filter Type Sound power level Cooling High Sound pressure level Cooling Low/Nom./High Heating Low/Nom./High Refrigerant Type/GWP Piping connections Liquid OD Gas OD Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control 126 FXNQ 20A 25A 32A kW kW kW kW mm kg 2.20 2.50 2.80 3.20 0.071 0.068 620 / 720x790x200 23.5 3.60 4.00 m³/min m³/min Pa 6.4/8.0 6.4/8.0 10/41.0 40A 50A 4.50 5.60 5.00 6.30 0.078 0.099 0.075 0.096 620 / 720x990x200 27.5 Galvanised steel plate 8.5/10.5 10.0/12.5 8.5/10.5 10.0/12.5 10/42.0 15/52.0 15/59.0 63A 7.10 8.00 0.110 0.107 620 / 720x1,190x200 32.0 13.0/16.5 13.0/16.5 15/55.0 Resin net dBA dBA dBA mm mm Hz/V A 51 27.0/28.5/30.0 27.0/28.5/30.0 52 28.0/30.0/32.0 28.0/30.0/32.0 R-410A/2,087.5 53 29.0/31.0/33.0 29.0/31.0/33.0 6.35 12.7 VP20 (I.D. 20/O.D. 26) 1~/50/60/220-240/220 16 BRC4C65 BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 54 32.0/33.0/35.0 32.0/33.0/35.0 9.52 15.9 FXLQ-P Floor standing unit For perimeter zone air conditioning ʯ Unit can be installed as free standing model by use of optional back plate ʯ Its low height enables the unit to fit perfectly beneath a window ʯ Stylish modern casing finished in pure white (RAL9010) and iron grey (RAL7011) blends easily with any interior ʯ Requires very little installation space FXLQ20,25P /////////////////////////////////////////////////////////// /////////////////////////////////////////////////////////// ////////////////// //////////////////////////////// BRC1H519W7, BRC4C65 //////////////////////////////// Floor standing Wall mounted ʯ Wall mounted installation facilitates cleaning beneath the unit where dust tends to accumulate ʯ Wired remote control can easily be integrated in the unit Access all technical information on FXLQ-P at my.daikin.eu or click here Indoor unit FXLQ 20P 25P 32P 40P 50P 63P Cooling capacity Total capacity Nom. kW 2.2 2.8 3.6 4.5 5.6 7.1 Heating capacity Total capacity Nom. kW 2.5 3.2 4.0 5.0 6.3 Power input - 50Hz Cooling Nom. kW Heating Nom. Unit HeightxWidthxDepth Dimensions 0.05 8.0 0.09 0.11 kW 0.05 0.09 0.11 mm 600x1,000x232 600x1,140x232 600x1,420x232 Weight Unit Fan Cooling Air filter Air flow rate - 50Hz Type kg Sound power level Cooling High dBA 54 57 58 59 Sound pressure level Cooling Low/High dBA 32/35 33/38 34/39 35/40 Heating Low/High dBA 32/35 33/38 34/39 35/40 Low/High m³/min 27 32 6.0/7 6.0/8 38 8.5/11 11.0/14 12.0/16 Resin net Refrigerant Type/GWP R-410A/2,087.5 Piping connections Liquid OD mm 6.35 9.52 Gas OD mm 12.7 15.9 Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) Control systems Infrared remote control Wired remote control O.D. 21 (Vinyl chloride) Hz/V A 1~/50/60/220-240/220 15 BRC4C65 BRC1H519W7/S7/K7 / BRC1E53A/B/C / BRC1D52 127 VRV heatpump combined with stylish indoor units Combine VRV indoor units with stylish indoor units on a VRV IV heat pump FXSQ-A VRV indoor unit FXFQ-B VRV indoor unit FVXG-K Nexura BPMKS967A2 FTXJ-MW/MS Daikin Emura VRV IV heat pump RYYQ-U RXYQ-U RXYLQ-T RWEYQ-T9 Connect only stylish indoor units to VRV IV S-series or VRV IV W-series outdoor units FCAG-B BPMKS967A2 FTXJ-MW/MS - Daikin Emura FBA-A › RXYSCQ-TV1 RXYSQ-TV9/TY9 RXYSQ-T8Y/TY1 BPMKS967A2 FVXG-K - Nexura * Special order unit, contact your local sales representative for more information BPMKS967A Branch provider To connect Split and Sky Air indoor units to VRV outdoor units Branch provider BPMKS967A2 Connectable indoor units Max. indoor unit connectable capacity Max. connectable combination Dimensions Height x Width x Depth Weight 128 BPMKS967A2 mm kg BPMKS967A2 1~2 1~3 14.2 71+71 20.8 60+71+71 180x294x350 7 8 Indoor units Products overview Stylish indoor units Depending on the application, Split and Sky Air indoor units can be connected to our VRV IV and VRV IV S-series outdoor units. Refer to the outdoor unit portfolio for combination restrictions. Concealed ceiling Wall mounted Ceiling suspended Floor standing 20 25 35 42 50 60 71 FCAG-B Fully flat cassette FFA-A9 Slim concealed ceiling unit FDXM-F9 Concealed ceiling unit with inverter-driven fan FBA-A(9) Daikin Emura Wall mounted unit FTXJ-MW/MS Stylish Wall mounted unit FTXA-AW/ BS/BB/BT Perfera Wall mounted unit CTXM-N FTXM-N Ceiling suspended unit FHA-A(9) Nexura floor standing unit FVXG-K Floor standing unit FVXM-F Concealed floor standing unit FNA-A9 (incl. auto-cleaning function1) Ceiling mounted cassette 15 RXYLQ-T Product name RWEYQ-T94 Model Round flow cassette RXYSCQ-TV13 RXYSQ-TV93 RXYSQ-TY9/TY13 Type RXYQ-U Capacity class (kW) RYYQ-U Connectable outdoor unit 1 Decoration panel BYCQ140DG9 or BYCQ140DGF9 + BRC1E* or BRC1H* needed 2 To connect stylish indoor units a BPMKS unit is needed 3 A mix of RA indoor units and VRV indoor units is not allowed. 4 Only in heat pump operation Auto cleaning filter option 129 FTXJ-MW/MS Wall mounted unit Design at its best, delivering superior efficiency and comfort › Remarkable blend of iconic design and engineering excellence › › STANDARD › INCLUDED › FTXJ-MW with an elegant finish in silver and anthracite or in matt crystal white Daikin Emura has been awarded with Reddot design award 2014 by an international jury, thanks to its excellent design Designed to perfectly balance technological leadership and the beauty of aerodynamics Online controller : control your indoor from any location with an app, via your local network or internet Whisper quiet in operation: the operating of the unit can hardly be heard. The sound pressure level goes down to 19dBA! FTXJ-MS ARC499A9 Indoor unit Dimensions Weight Air filter Fan FTXJ Unit HeightxWidthxDepth mm Unit kg Type Silent operation/Low/ m³/min Air flow rate Cooling Medium/High Heating Silent operation/Low/ m³/min Medium/High Sound power level Cooling dBA Heating dBA Sound pressure level Cooling Silent operation/Low/High dBA Heating Silent operation/Low/High dBA Control systems Infrared remote control Wired remote control Power supply Phase/Frequency/Voltage Hz/V 130 20MW 20MS 25MW 2.6/4.4/6.6 /8.9 3.8/6.3/8.4 /10.2 Standard Included 25MS 35MW 35MS 303x998x212 12.0 Removable / washable 2.9/4.8/7.8 /10.9 50MS 3.6/6.8/8.9 /10.9 3.8/6.3/8.6 /11.0 4.1/6.9/9.6 /12.4 5.0/8.1/10.5 /12.6 19/28/41 59 59 20/26/45 20/29/45 60 60 32/35/46 32/35/47 54 56 19/25/38 19/28/40 50MW ARC466A9 1~/50/220-240 FTXA-AW/BS/BT/BB + RXA-A/B Wall mounted unit Most compact design wall mounted unit ʯ A compact and functional design suitable for all interiors in a white, black, silver and blackwood coloured elegant finish ʯ The Coanda effect optimises the airflow for a comfortable climate. By using specially designed flaps, a more focused airflow allows a better temperature distribution throughout the whole room ʯ The intelligent thermal sensor determines the current room temperature and distributes air evenly throughout the room before switching to an airflow pattern that directs warm or cool air to areas that need it STANDARD ʯ Online controller: control your indoor from any location with an INCLUDED app, via your local network or internet ʯ Powerful air purification increases indoor air quality with Daikin Flash Streamer technology ʯ Practically inaudible: the unit runs so quietly, you will almost forget it is there. Indoor unit Dimensions Weight Air filter Fan FTXA CTXA15 AW/BS/BT/BB 20AW/BS/BT/BB Unit HeightxWidthxDepth mm Unit kg Type Air flow rate Cooling Silent operation/Low/ m³/min 4.6 / 6.1 / 8.2 / 11.0 4.6/6.1/8 /11.0 Medium/High Heating Silent operation/Low/ m³/min 4.5/6.4/8.7 /10.9 Medium/High Sound power level Cooling dBA 57 Sound pressure level Cooling Silent operation/Low/High dBA 19/25/39 Heating Silent operation/Low/High dBA 19/25/39 Control systems Infrared remote control Wired remote control Power supply Phase/Frequency/Voltage Hz/V FTXA-AW FTXA-BS FTXA-BT FTXA-BB ARC466A58 25AW/BS/BT/BB 35AW/BS/BT/BB 295x798x189 12 Removable / washable 4.6/6.1/9 /11.5 4.6/6.1/9 /11.9 4.5/6.4/9.0 /11.1 4.5/6.4/9.0 /11.5 19/25/40 19/25/41 19/25/40 19/25/41 ARC466A58 BRC073 1~/50/220-240 integrated in PCB 42AW/BS/BT/BB 50AW/BS/BT/BB 4.6/7.2/10 /13.1 5.2/7.6/10 /13.5 5.2/7.7/10.5 /14.6 5.7/8.2/11.1 /15.1 60 21/29/45 21/29/45 24/31/46 24/31/46 24/33/46 131 FVXG-K Floor standing unit with radiant heat panel Stylish floor standing unit with radiant heat panel for comfortable heat and very low noise › The aluminium part of the front panel of the Nexura indoor unit › › › › › › has the capability of warming up, just like a traditional radiator, to add even more comfort on cold days Quiet and discrete, Nexura offers you the best in heating and cooling, in comfort and design The indoor unit distributes air at the sound of a whisper. The noise produced amounts to barely 22dB(A) in cooling and 19dB(A) in radiant heat mode. In comparison, the ambient sound in a quiet room amounts to 40dB(A) on average. Comfortable vertical auto swing ensures draught-free operation and prevents ceiling soiling Online controller (optional): control your indoor from any location with an app, via your local network or internet Can be installed against a wall or recessed Its low height enables the unit to fit perfectly beneath a window ARC466A2 Indoor unit Dimensions Unit Weight Unit Air filter Type Fan - Air flow rate Cooling High/Low/Silent operation m³/min 8.9/5.3/4.5 9.1/5.3/4.5 10.6/7.3/6.0 Heating High/Low/Silent operation m³/min 9.9/5.7/4.7 10.2/5.8/5.0 12.2/7.8/6.8 Sound power level HeightxWidthxDepth FVXG mm FVXG-K 25K kg 50K 22 Removable / washable / mildew proof Cooling dBA 52 Heating dBA 53 Sound pressure level Cooling High/Low/Silent operation dBA Heating High/Low/Silent operation/Radiant heat dBA Control systems Infrared remote control Power supply Phase / Frequency / Voltage 58 60 38/26/23 39/27/24 44/36/32 39/26/22/19 40/27/23/19 46/34/30/26 ARC466A2 Hz / V (3) Operation range in combination with Nexura, FVXG-K, cooling: min. 10°CDB - max. 46°CDB; heating: min. -15°CWB - max. 18°CWB 132 35K 600x950x215 1~ / 50 / 220-240 FVXM-F Floor standing unit Floor standing unit for optimal heating comfort thanks to dual airflow › Its low height enables the unit to fit perfectly beneath a window › Can be installed against a wall or recessed › Vertical auto swing moves the discharge flaps up and down for efficient air and temperature distribution throughout the room › Online controller (optional): control your indoor from any loca- FVXM-F tion with an app, via your local network or internet ARC452A1 Indoor unit Dimensions Weight Air filter Fan Unit Unit Type Air flow rate HeightxWidthxDepth FVXM mm kg Silent operation/Low/ m³/min Medium/High Heating Silent operation/Low/ m³/min Medium/High Sound power level Cooling dBA Heating dBA Silent operation/Low/High dBA Sound pressure level Cooling Silent operation/Low/High dBA Heating Control systems Infrared remote control Wired remote control Power supply Phase/Frequency/Voltage Hz/V Cooling 25F 4.1/4.8/6.5 /8.2 35F 600x700x210 14 Removable / washable 4.5/4.9/6.7 /8.5 6.6/7.8/8.9 /10.1 4.4/5.0/6.9 /8.8 4.7/5.2/7.3 /9.4 7.1/8.5/10.1 /11.8 52 52 23/26/38 23/26/38 24/27/39 24/27/39 ARC452A1 1~/50/220-230-240 50F 57 58 32/36/44 32/36/45 133 Hot water Efficient hot water production for underfloor heating, radiators and air handling units, or for producing hot water for sinks, baths and showers. Integrating heat recovery into the VRV system means that the production of hot water is virtually free. 134 Hot water Hot water 135 Low temperature hydrobox HXY-A8136 High temperature hydrobox HXHD-A8137 Accessories for hot water 138 Hydrobox range Capacity class (kW) Type Low temperature hydrobox High temperature hydrobox Product name HXY-A8 HXHD-A8 Model 80 125 For high efficiency space heating and cooling › Ideal for hot or cold water in underfloor, air handling units, low temperature radiators … › Hot/cold water from 5° to 45°C › Large operation range (down to -20°C and up to 43°C) › Fully integrated water-side components save time on system design › Space saving contemporary wall hung design For efficient hot water production and space heating › Ideal for hot water in bathrooms, sinks and for underfloor heating, radiators, air handling units, … › Hot water from 25 to 80°C › "Free" heating and hot water through heat recovery › Uses heat pump technology to produce hot water efficiently, providing up to 17% savings compared to a gas boiler › Possibility to connect thermal solar collectors 200 Leaving water temperature range 5 °C - 45 °C 25 °C - 80 °C 135 HXY-A8 Low temperature hydrobox for VRV For high efficiency space heating and cooling ʯ Air to water connection to VRV for applications such as underfloor, air handling units, low temperature radiators, … ʯ Leaving water temperature range from 5°C to 45°C without electric heater ʯ Super wide operating range for hot/cold water production from -20 to +43°C ambient outdoor temperature ʯ Saves time on system design as all water-side components are fully integrated with direct control over leaving water temperature ʯ Space saving contemporary wall mounted design ʯ No gas connection or oil tank needed ʯ Connectable to VRV IV heat pump and heat recovery HXY-A8 Liquid pipe Gas pipe F1, F2 communication Hot/cold water VRV indoor units Air handling unit Low temp. radiator VRV IV heat pump VRV IV heat recovery Under floor heating Access all technical information on HXY-A8 at my.daikin.eu or click here Indoor Unit Cooling capacity Nom. Heating capacity Nom. Dimensions Unit Weight Unit Casing Colour Operation range Cooling Height x Width x Depth HXY 080A8 125A8 kW 8.0 (1) 12.5 (1) kW 9.00 (2) mm kg Refrigerant Precoated sheet metal Ambient Min. ~ Max. °CDB Water side Min. ~ Max. °C 5 ~ 20 Ambient Min. ~ Max. °C -20 ~ 24 Water side Min. ~ Max. °C 25 ~ 45 Type 10 ~ 43 R-410A GWP Refrigerant circuit 44 White Material Heating 14.00 (2) 890 x 480 x 344 2,087.5 Gas side diameter mm Liquid side diameter mm 9.5 Water circuit Piping connections diameter inch G 1"1/4 (female) Power supply Phase / Frequency / Voltage Hz / V 1~ / 50 / 220-240 Current Recommended fuses (1) Tamb 35°C - LWE 18°C (DT=5°C) | (2) DB/WB 7°C/6°C - LWC 35°C (DT=5°C) 136 A 15.9 6~16 HXHD-A8 High temperature hydrobox for VRV For efficient hot water production and space heating ʯ Air to water connection to VRV for applications such as bathrooms, sinks, underfloor heating, radiators and air handling units ʯ Leaving water temperature range from 25 to 80°C without electric heater ʯ „Free“ heating and hot water production provided by transferring heat from areas requiring cooling to areas requiring heating or hot water ʯ Uses heat pump technology to produce hot water efficiently, providing up to 17% savings compared to a gas boiler ʯ Possibility to connect thermal solar collectors to the domestic hot water tank ʯ Super wide operating range for hot water production from -20 to +43°C ambient outdoor temperature ʯ Saves time on system design as all water-side components are fully integrated with direct control over leaving water temperature ʯ Various control possibilities with weather dependant set point or thermostat control ʯ The indoor unit and domestic hot water tank can be stacked to save space, or installed next to each other, if only limited height is available ʯ No gas connection or oil tank needed ʯ Connectable to VRV IV heat recovery HXHD-A8 EKHWP-B EKHWP-B VRV indoor units Liquid pipe Gas pipe Discharge gas pipe F1, F2 communication Hot water 45°C - 75°C Daikin solar panel Domestic hot water 25°C - 75°C BS-Box Air handling unit Domestic hot water tank 45°C - 75°C BS-Box Low temp. radiator Heating only hydrobox for VRV VRV heat recovery Under floor heating 25°C - 35°C Access all technical information on HXHD-A8 at my.daikin.eu or click here Indoor Unit Heating capacity Dimensions Weight Casing Nom. Unit Unit Colour Material Sound power level Nom. Sound pressure level Nom. Night quiet mode Operation range Heating Domestic hot water Refrigerant Water circuit Power supply Current Height x Width x Depth HXHD kW mm kg 125A 14.0 200A 22.4 705 x 600 x 695 92.0 147 Metallic grey Precoated sheet metal dBA dBA dBA Level 1 Ambient Water side Ambient Water side Min. ~ Max. Min. ~ Max. Min. ~ Max. Min. ~ Max. Type GWP Charge Piping connections diameter Heating water Water volume Max. ~ Min. system Phase / Frequency / Voltage Recommended fuses 55.0 (2) 42.0 (2) / 43.0 (3) 38 (2) °C °C °CDB °C 60.0 (2) 46.0 (2) / 46.0 45 (2) -20.0 ~ 20 / 24 (1) 25 ~ 80.0 -20.0 ~ 43.0 45 ~ 75 R-134a 1,430 kg inch l 2.00 2.60 200 ~ 20 400 ~ 20 Hz / V A 1~ / 50 / 220-240 20 3~ / 50 / 380-415 16 G 1" (female) (1) Field setting | (2) Sound levels are measured at: EW 55°C; LW 65°C | (3) Sound levels are measured at: EW 70°C; LW 80°C 137 Accessories for hot water EKHWP-B Domestic hot water tank Plastic domestic hot water tank with solar support ʯ Tank designed for connection with drainback thermal solar system ʯ Available in 300 and 500 liters ʯ Large hot water storage tank to provide domestic hot water at any time ʯ Heat loss is reduced to a minimum thanks to the high quality insulation ʯ Space heating support possible (500l tank only) Accessory Casing Dimensions Weight Tank Heat exchanger EKHWP Colour Material Unit Height Width Depth Unit Empty Water volume Material Maximum water temperature Insulation Heat loss Energy efficiency class Standing heat loss Storage volume Domestic Quantity Tube material hot water Face area Internal coil volume Operating pressure Average specifc thermal output Charging Quantity Tube material Face area Internal coil volume Operating pressure Average specifc thermal output Auxiliary so- Tube material lar heating Face area Internal coil volume Operating pressure Average specifc thermal output mm mm mm kg l EKHWP300B 300B 1,650 595 615 58 294 °C kWh/24h 1.5 W l 64 294 m² l bar W/K 5.600 27.1 m² l bar W/K 3 13 m² l bar W/K EKHWP500B 2,790 500B Traffic white (RAL9016) / Dark grey (RAL7011) Impact resistant polypropylene Polypropylen 85 1.7 B 72 477 1 Stainless steel (DIN 1.4404) 5.800 28.1 6 2,825 1 Stainless steel (DIN 1.4404) 3 1,300 - 1,660 790 790 82 477 4 18 1,800 Stainless steel (DIN 1.4404) 1 4 3 280 EKHWP-PB Domestic hot water tank Pressureless domestic hot water tank with solar support ʯ Tank designed for connection with pressurised thermal solar system ʯ Available in 300 and 500 liters ʯ Large hot water storage tank to provide domestic hot water at any time ʯ Heat loss is reduced to a minimum thanks to the high quality insulation ʯ Space heating support possible (500l tank only) Accessory Casing Dimensions Weight Tank Heat exchanger 138 EKHWP Colour Material Unit Height Width Depth Unit Empty Water volume Material Maximum water temperature Insulation Heat loss Energy efficiency class Standing heat loss Storage volume Domestic Quantity Tube material hot water Face area Internal coil volume Operating pressure Average specifc thermal output Charging Quantity Tube material Face area Internal coil volume Operating pressure Average specifc thermal output Pressurised solar Average specifc thermal output Auxiliary so- Tube material lar heating Face area Internal coil volume Operating pressure Average specifc thermal output mm mm mm kg l EKHWP300PB 300PB 1,650 595 615 58 294 °C kWh/24h 1.5 W l 64 294 m² l bar W/K m² l bar W/K W/K m² l bar W/K EKHWP500PB 5.600 27.1 2,790 3 13 1,300 390.00 - 500PB Traffic white (RAL9016) / Dark grey (RAL7011) Impact resistant polypropylene Polypropylen 85 B 1 Stainless steel (DIN 1.4404) 6 1 Stainless steel (DIN 1.4404) 3 1,660 790 790 89 477 1.7 72 477 5.900 28.1 2,825 4 18 1,800 840.00 Stainless steel (DIN 1.4404) 1 4 3 280 Accessories for hot water EKS(V/H)-P Solar collector Thermal solar collector for hot water production ʯ Solar collectors can produce up to 70% of the energy needed for hot water production - a major cost saving ʯ Horizontal and vertical solar collector for domestic hot water production ʯ High efficiency collectors transfer all the short-wave solar radiation into heat as a result of their highly selective coating ʯ Easy to install on roof tiles EKSV21P EKSH26P Accessory Mounting Dimensions Weight Volume Surface Coating Absorber Glazing Allowed roof angle Operating pressure Stand still temperature Thermal performance Auxiliary EKSV/EKSH Unit Unit HeightxWidthxDepth Outer Aperture Absorber Min.~Max. Max. Max. collector efficiency (ηcol) Zero loss collector efficiency η0 Heat loss coefficient a1 Temperature dependence of the heat loss coefficient a2 Thermal capacity Solpump Solstandby Annual auxiliary electricity consumption Qaux mm kg l m² m² m² ° bar °C % % W/m².K W/m².K² kJ/K W W kWh EKSV26P 21P 26P Vertical 1,006x85x2,000 33 1.3 2.01 1.800 1.79 Horizontal 2,000x85x1,300 42 1.7 2.1 2.60 2.360 2.35 Micro-therm (absorption max. 96%, Emission ca. 5% +/-2%) Harp-shaped copper pipe register with laser-welded highly selective coated aluminium plate Single pane safety glass, transmission +/- 92% 15~80 6 192 61 0.781 0.784 4.240 4.250 0.006 0.007 4.9 6.5 - EKSRDS2A/EKSRPS4A Pump station ʯ Save energy and reduce CO2 emissions with a solar system for domestic hot water production ʯ Pump station connectable to unpressurised solar system ʯ Pump station and control provide the transfer of solar heat to the domestic hot water tank EKSRPS4A Accessory Mounting Dimensions Weight Operation range Operating pressure Stand still temperature Thermal performance Control Power supply Sensor Power supply intake Auxiliary EKSRPS4A/EKSRDS2A Unit HeightxWidthxDepth Unit Ambient temperature Min.~Max. Max. Max. collector efficiency (ηcol) Zero loss collector efficiency η0 Type Power consumption Phase/Frequency/Voltage Solar panel temperature sensor Storage tank sensor Return flow sensor Feed temperature and flow sensor Solpump Solstandby Annual auxiliary electricity consumption Qaux mm kg °C bar °C % % W Hz/V W W kWh EKSRPS4A On side of tank 815x142x230 6.4 5~40 85 EKSRDS2A On wall 410x314x154 6 0~40 6 120 - Digital temperature difference controller with plain text display 2 5 1~/50/230 /50/230 Pt1000 PTC PTC Voltage signal (3.5V DC) Indoor unit 37.3 23 2.00 5.00 92.1 89 139 Daikin offers the widest range in DX ventilation in the market. With a variety of ventilation solutions from small heat recovery ventilation to large scale air handling units we help provide a fresh, healthy and comfortable environment in offices, hotels, stores and other commercial environments. 140 Ventilation ErP 2018 COMPLIANT Why choose Daikin ventilation 142 ERV / HRV - Energy/Heat recovery ventilation units 144 ALB-LBS/RBS - Modular L Smart 146 Heater for Modular L Smart 147 VAM-FC9/VAM-J148 Heater for VAM 149 VKM-GB(M)150 Daikin air handling units with DX connection 151 Advantages151 Overview of VRV & ERQ condensing units 152 Control possibilities 153 Integration in third party AHU Expansion valves & Control boxes Selection procedure 156 156 157 For latest data, please consult my.daikin.eu 141 5 Why choose Daikin ventilation reasons Daikin’s ventilation range is unique in the market 1 Market leading controls & connectivity › Interlock of ventilation and air conditioning system • Control ERV/HRV and air conditioning from the same controller • Aligns the operation mode between the systems to save energy › Easy integration in the total solution • Online control and monitoring via the Daikin Cloud Service • Full portfolio integration in the intelligent Touch Manager, Daikin's cost-effective mini BMS › User-friendly controller with premium design • Intuitive touch button control 21°C 2 Unique installation benefits › Integrates seamlessly in the Daikin total solution, ensuring a single point of contact › Total fresh air solution with Daikin supplying both the VAM/Modular L Smart and the electrical heater › Daikin AHU and condensing unit connect Plug & Play thanks to same pipe diameters, factory mounted controls, expansion valves, etc. 142 Why choose Daikin ventilation 3 › › › › High energy efficiency Up to 92% energy Energy recovery of up to 92%, reducing running costs Free nighttime cooling using fresh outside air Inverter driven centrifugal fans ErP compliant 4 recovery Best comfort › Wide range of units to control fresh air and humidity › Wide range of optional filters to suit the application available up to ePM1 80% (F9) › Special paper heat exchanger recovers heat and moisture from extract air to warm up and humidify fresh air to comfortable levels (VAM, VKM) 5 Top reliability › Most extensive testing before new units leave the factory › Widest support network and after sales service › All spare parts available in Europe Did you know? CO2 levels and ventilation rates all have significant, independent impacts on cognitive function: ErP 2021 COMPLIANT COGNITIVE FUNCTION SCORES … + 61% + 101% IN GREEN BUILDING IN ENHANCED CONDITIONS GREEN BUILDING CONDITIONS 143 Widest range of DX integrated ventilation on the market Daikin offers a variety of solutions from small energy recovery ventilation to large-scale air handling units for the provision of fresh air ventilation to homes, or commercial premises. Ventilation solutions Daikin offers state-of-the-art ventilation solutions that can easily be integrated into any project: › Unique portfolio within DX manufacturers › High-quality solutions complying with the highest Daikin quality standards › Seamless integration of all products to provide the best indoor climate › All Daikin products connected to a single controller for complete control of the HVAC system. Energy Recovery Ventilation Our energy recovery units recover sensible energy (Modular L Pro / Modular L Smart) or total (sensible + latent) energy (VAM/VKM), substantially reducing the load on the air conditioning system up to 40%. Ventilation with DX connection - Control over fresh air temperature Daikin offers a range of inverter condensing units to be used in combination with Daikin AHUs for ultimate control over the fresh air. There are 4 control possibilities when combining AHU and Daikin outdoor units hence offering all the required flexibility for any installation. Indoor units can be combined to the same outdoor unit to reduce the installation costs. For falseceiling installations where space is a constraint, the VKM can fit perfectly to deliver fresh air at a comfortable temperature and it has an optional humidification element. 144 Five components of indoor air quality Ventilation › Ventilation: Ensures the provision of fresh air › Energy recovery: Delivers energy savings by transferring heat and Energy recovery moisture between airflows › Air processing: Delivers the right supply temperature to decrease the indoor unit load › Humidification: Ensures relative indoor humidity levels are respected › Filtration: Separates pollen, dust and pollution odours that are harmful to individuals’ health Air processing Humidification Filtration Fresh air portfolio Decentralised systems 150 500 1,000 2,000 2,500 3,000 › › › › › D-AHU MODULAR L (SMART) › › › › 3,500 15,000 25,000 140,000 [m3/h] High efficiency counterflow heat exchanger Free-cooling operation EC centrifugal fan Wide range of options Smart version connects Plug & Play to Sky Air / VRV systems Compact size High energy efficient paper recovering sensible and latent heat EC fan motors Filter clogging alarm based on pressure VAM-FC9 / VAM-J › With DX coil for post-treated fresh air › Increased comfort › Humidifier option VKM-GB(M) › › › › High efficiency aluminium plate heat exchanger Pre-configured sizes Plug & Play pre-configured controls With DX or water coil option Centralised systems D-AHU MODULAR P › Rotary heat exchanger (sorption and sensible technology) › Pre-configured sizes › Plug & Play pre-configured controls › With DX or water coil option D-AHU MODULAR R › › › › Fully customizable Plug & play 4 types of control With DX or water coil option D-AHU Professional 145 ALB-LBS/RBS Modular L Smart Return Air Fresh Air Premium efficiency heat recovery unit Supply Air Exhaust Air Highlights Right drain connection (ALB-RBS) › Connects Plug&Play into the Sky Air and VRV control network › Easy installation and commissioning › Internal pre-filter stage (up to ePM1 50% (F7) + ePM1 80% (F9)) making the unit reach highest indoor air quality requirements. › Wide air flow coverage from 150m3/h to 3,450m3/h › Exceeding ErP 2018 requirements › Best choice when compactness is needed (only 280 mm height up to 550 m3/h) › 50 mm double skin panel (120 kg/m3) for a maximum sound and thermal insulation Fresh Air EC centrifugal fan Return Air Exhaust Air › Maximum ESP available 600 Pa (depending on model sizes and airflow) › Inverter driven with IE4 premium efficiency motor › High-efficient blade profiling › Reduced energy consumption › Optimized SFP (Specific Fan Power) for an efficient unit operation Supply Air Left drain connection (ALB-LBS) Heat exchanger For integration with Applied systems, please refer to the Modular L, in the AHU chapter › Premium quality counter flow plate heat exchanger › Up to 93% of the thermal energy recovered › High grade aluminum allowing optimum corrosion protection Technical details D-AHU Modular L Smart ALB-RBS/LBS m3/h Airflow Heat exchanger thermal efficiency1 External static pressure Nom. Temperature after heat exchanger1 Nom. Max ESP @ nom. airflow 02 03 04 05 06 07 300 600 1200 1500 2300 3000 % 90 91 90 90 92 91 Pa 100 100 100 100 100 100 °C 19,4 19,5 19,4 19,2 19,8 19,5 Pa 400 450 260 270 250 210 Current Nom. A 0,52 1,17 1,91 2,48 3,76 5,39 Power input Nom. kW 0,12 0,27 0,44 0,57 0,87 1,24 kW/m3/s 1,24 1,49 1,28 1,32 1,32 1,46 SFPv2 ERP compliant Electrical supply ErP 2018 Compliant Phase ph 1 1 1 1 1 1 Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 V Voltage Main unit dimensions Rectangular duct flange 220/240 Vac 220/240 Vac 220/240 Vac 220/240 Vac 220/240 Vac 220/240 Vac Width mm 920 1100 1600 1600 2000 2000 Height mm 280 350 415 415 500 500 Length mm 1660 1800 2000 2000 2000 2000 Width mm 250 400 500 500 700 700 Height mm 150 200 300 300 400 400 dB 48 54 57 53 60 57 dBA 34 39 41 37 44 41 kg 125 180 270 280 355 360 Unit Sound Power Level (Lwa) Unit Sound Pressure Level3 Weight unit 1. Winter design condition: Outdoor: -5°C, 90% Indoor: 22°C,50% 2. SFPv is a parameter that quantifies the fan efficiency (the lower it is the better will be). This reduces if airflow decreases. 3. According to EN3744. Surrounding, Directivity (Q) = 2, @ 1,5m distance 146 ALD-HEFB Electrical heater for Modular L Smart › Total solution for fresh air with Daikin supply of both Modular L Smart and electrical heaters › Increase comfort in low outdoor temperature thanks to the heated outdoor air › Integrated electrical heater concept (no additional accessories required) › Standard dual flow and temperature sensor › Heater only consumes what is required to pre-heat to the desired minimum fresh air temperature; thus saving energy Electrical heater for Modular L Smart (ALD) Capacity kW Connectable Modular L Smart size 02HEFB 03HEFB 05HEFB 1,5 3 7,5 15 02 03 04, 05 06, 07 13,1 10,9 21,7 17k ohms at -20 °C 10k ohms at +10 °C 18k ohms at -20 °C 10k ohms at +10 °C Supply voltage Output current (maximum) (A) Temperature sensor 230V,1ph 6,6 07HEFB 400V,3ph 15k ohms at -20 °C 16k ohms at -20 °C 10k ohms at +10 °C 10k ohms at +10 °C Temperature control range - 20 °C to 10 °C Control fuse Mini Circuit Breaker 6 A LED indicators "Yellow = Airflow fault Red = Heat ON” Mounting holes Depends on duct size Maximum ambient adjacent to terminal box 30°C (during operation) Auto high temperature cutout 75°C Pre-set Manual reset high temperature cutout 120°C Pre-set Width (mm) 470 620 720 920 Depth (mm) 370 370 370 370 Height (mm) 193 243 343 443 147 VAM-FC9/VAM-J Energy recovery ventilation Diamond shape heat exchanger! Return air Supply air Ventilation with heat recovery as standard › Thinnest High Efficiency Enthalpy Heat Exchanger in the market (J-series) › Energy saving ventilation using indoor heating, cooling and moisture recovery › Free cooling possible when outdoor temperature is below indoor temperature (eg. during nighttime) › Prevent energy losses from over-ventilation while improving indoor air quality with optional CO2 sensor › Possibility to change ESP via wired remote control al- Exhaust air Fresh air lows optimisation of the supply air volume (J - series) › Can be used as stand alone or integrated in the Sky Air or VRV system › Wide range of units: air flow rate from 150 up to 2,000 m³/h › Shorter installation time thanks to easy adjustment of nominal air flow rate, so less need for dampers compared with traditional installation › No drain piping needed › Can operate in over- and under pressure › Total solution for fresh air with Daikin supply of both VAM / VKM and electrical heaters Ventilation Power input - 50Hz Temperature exchange efficiency - 50Hz Enthalpy exchange efficiency - 50Hz Heat exchange mode Nom. Ultra high/High/Low Bypass mode Nom. Ultra high/High/Low Ultra high/High/Low Cooling Ultra high/High/Low Heating Ultra high/High/Low Operation mode Heat exchange system Heat exchange element Dimensions Unit Weight Unit Casing Material Fan Air flow rate - 50Hz External static pressure - 50Hz Air filter Sound pressure level - 50Hz Type Heat exchange mode Bypass mode HeightxWidthxDepth ErP 2021 COMPLIANT VAM/VAM 150FC9 kW 0.132/0.111/ 0.058 0.161/0.079/ 0.097 /0.070 / 0.164 /0.113 / 0.247 /0.173 / 0.303 /0.212 / 0.416 /0.307 / 0.548 /0.384 / 0.833 /0.614 / 0.064 0.039 0.054 0.081 0.103 0.137 0.191 0.273 kW 0.132/0.111/ 0.058 0.161/0.079/ 0.085 /0.061 / 0.148 /0.100 / 0.195 /0.131 / 0.289 /0.194 / 0.417 /0.300 / 0.525 /0.350 / 0.835 /0.600 / 0.064 0.031 0.045 0.059 0.086 0.119 0.156 0.239 250FC9 350J 500J % 77.0 (1) / 72.0 (2)/ 74.9 (1) / 69.5 (2)/ 85.1 /86.7 / 78.3 (1) / 72.3 (2)/ 76.0 (1) / 70.0 (2)/ 90.1 82.8 (1) / 73.2 (2) 80.1 (1) / 72.0 (2) % 60.3 (1)/61.9 (1)/ 60.3 (1)/61.2 (1)/ 65.2 /67.9/ 67.3 (1) 64.5 (1) 74.6 % 66.6 (1)/67.9 (1)/ 66.6 (1)/67.4 (1)/ 72.4 (1) 70.7 (1) mm kg Ultra high/High/ Low m³/h Bypass mode Ultra high/High/ Low m³/h Heat exchange mode High efficiency filters available: ePM10 70% (M6), ePM1 55% (F7) and ePM1 70% (F8) 285x776x525 24.0 150 /140 /105 250 /230 /155 150 /140 /105 250 /230 /155 Ultra high/High/Low Pa 90 /87/40 70 /63/25 Ultra high/High/Low dBA 27.0 /26.0 /20.5 28.0 /26.0 /21.0 Ultra high/High/Low dBA 27.0 /26.5 /20.5 28.0 /27.0 /21.0 75.5 /77.6 / 82.0 °CDB mm Hz/V A kWh/(m².a) kWh/(m².a) kWh/(m².a) m³/h W dB kWh/a kWh/a kWh/a kWh/a 34.5 (1)/ 32.0 (1)/ 29.0 (1) 34.5 (1)/ 32.0 (1)/ 28.0 (1) 150 15.0 -56.0 (5) -60.5 (5) -22.1 (5) -27.0 (5) -0.100 (5) -5.30 (5) D / See note 5 B / See note 5 130 207 129 160 40 43 18.9 (5) 13.6 (5) 41.0 (5) 40.6 (5) 80.2 (5) 79.4 (5) 18.5 (5) 18.4 (5) 200 51 1500J 2000J 84.3 /86.4 / 90.5 82.5 /84.2 / 87.7 79.6 /81.8 / 86.1 83.2 /84.8 / 88.1 79.6 /81.8 / 86.1 59.2 /61.8 / 69.5 59.2 /63.8 / 73.1 67.7 /70.7 / 76.8 62.6 /66.4 / 74.0 68.9 /71.8 / 77.5 62.6 /66.4 / 74.0 69.0 /72.2 / 78.7 73.1 /76.3 / 82.7 72.8 /75.3 / 80.2 68.6 /71.7 / 77.9 73.8 /76.1 / 80.8 68.6 /71.7 / 77.9 Multidirectional fibrous fleeces (G3) 39.0 (1)/ 39.0 (1)/ 42.0 (1)/ 36.0 (1)/ 36.0 (1)/ 38.5 (1)/ 31.0 (1) 30.5 (1) 32.5 (1) 38.0 (1)/ 40.0 (1)/ 42.5 (1)/ 34.5 (1)/ 36.5 (1)/ 40.0 (1)/ 30.5 (1) 30.5 (1) 32.5 (1) 0°C~40°CDB, 80% RH or less 250 1~ ; 50/60 ; 220-240/220 16.0 54 58 61 - (1)Measured according to JIS B 8628 | (2)Measured at reference flow rate according to EN13141-7 | (5) At reference flow rate in accordance with commission regulation (EU) No 1254/2014 148 148 1000J 80.0 /82.5 / 87.6 37.5 (1)/ 35.0 (1)/ 30.5 (1) 38.0 (1)/ 35.0 (1)/ 29.5 (1) 100 800J Heat exchange mode, bypass mode, fresh-up mode Air to air cross flow total heat (sensible + latent heat) exchange Specially processed non-flammable paper 368x1,354x920 368x1,354x1,172 301x1,113x886 46.5 61.5 79.0 Galvanised steel plate 350 (1)/ 500 (1)/ 650 (1)/ 800 (1)/ 1,000 (1)/ 300 (1)/ 425 (1)/ 550 (1)/ 680 (1)/ 850 (1)/ 200 (1) 275 (1) 350 (1) 440 (1) 550 (1) 350 (1)/ 500 (1)/ 650 (1)/ 800 (1)/ 1,000 (1)/ 300 (1)/ 425 (1)/ 550 (1)/ 680 (1)/ 850 (1)/ 200 (1) 275 (1) 350 (1) 440 (1) 550 (1) 90 (1)/70.0 /50.0 (1) Multidirectional fibrous fleeces Operation range Around unit Connection duct diameter Power supply Phase/Frequency/Voltage Current Maximum fuse amps (MFA) Specific energy con- Cold climate sumption (SEC) Average climate Warm climate SEC class Maximum flow rate at Flow rate 100 Pa ESP Electric power input Sound power level (Lwa) Annual electricity consumption Annual heating saved Cold climate Average climate Warm climate 650J 731x1,354x1,172 157 1,500 (1)/ 1,275 (1)/ 825 (1) 1,500 (1)/ 1,275 (1)/ 825 (1) 2,000 (1)/ 1,700 (1)/ 1,100 (1) 2,000 (1)/ 1,700 (1)/ 1,100 (1) 42.0 (1)/ 39.0 (1)/ 33.5 (1) 42.0 (1)/ 39.0 (1)/ 32.5 (1) 45.0 (1)/ 41.5 (1)/ 36.0 (1) 45.0 (1)/ 41.0 (1)/ 35.0 (1) 2x250 62 65 NEW GSIEKA Electrical heater for VAM › Total solution for fresh air with Daikin supply of both VAM and electrical heaters › Increased comfort in low outdoor temperature thanks to the heated outdoor air › Integrated electrical heater concept (no additional accessories required) › Standard dual flow and temperature sensor › Flexible setting with adjustable setpoint › Increased safety with 2 cut-outs: manual & automatic GSIEKA Capacity Duct diameter kW mm Connectable VAM Dimensions 10009 0.9 100 15018 1.8 150 20024 2.4 200 VAM150FC9 VAM250FC9 VAM350,500J GSIEKA10009 GSIEKA15018 GSIEKA20024 25030 3.0 250 VAM650J, VAM800J, VAM1000J 35530(1) 3.0 355 VAM1500J, VAM2000J GSIEKA25030 GSIEKA35530 Height mm 171 221 271 321 426 Depth mm 100 150 200 250 355 Width mm 370 370 370 370 373 45 100 170 265 535 13.1 m/s Minimum air velocity / airflow m³/h 1.5 Power supply 1~230 VAC/50Hz Nominal current Heating power Connection duct diameter Operation range A 4.1 8.2 10.9 13.1 kW 0.9 1.8 2.4 3.0 3.0 mm 100 150 200 250 355 Min. °C -40°C Max. °C 40°C Rel. Humidity % Temperature sensor 90% 10 kΩ at +25°C / TJ-K10K Temperature sensor range - 30°C to 105°C Temperature set point range - 10°C to 50°C LED 1 LED indicators LED 2 Ambient temperature adjacent to controller flashing every 5 seconds heater is starting up flashing every second air flow detected, heating allowed OFF no power supply or no flow ON problem with duct temperature sensor, set point potentiometer or PTC airflow sensor OFF heater is not operation ON heater is operating 0°C to +50°C Auto high temperature cut-out 50°C Manual reset high temperature cut-out 100°C 149 VKM-GB/VKM-GBM Energy recovery ventilation, humidification and air processing Post heating or cooling of fresh air for lower load on the air conditioning system › Energy saving ventilation using indoor heating, cooling and moisture recovery › Creates a high quality indoor environment by pre conditioning of incoming fresh air › Humidification of the fresh air results in comfortable indoor humidity level, even during heating › Free cooling possible when outdoor temperature is below indoor temperature (eg. during nighttime) › Low energy consumption thanks to DC fan motor › Prevent energy losses from over-ventilation while improving indoor air quality with optional CO2 sensor › Shorter installation time thanks to easy adjustment of nominal air flow rate, so less need for dampers compared with traditional installation › Specially developed heat exchange element with High Efficiency Paper (HEP) › Can operate in over- and under pressure Ventilation Power input - 50Hz Heat exchange mode Bypass mode Nom. Nom. VKM-GB/VKM-GBM Ultra high/ kW High/Low Ultra high/ kW High/Low kW kW % Fresh air condition- Cooling Heating ing load Temperature Ultra high/High/Low exchange efficiency - 50Hz Enthalpy exchange Cooling Ultra high/High/Low Heating Ultra high/High/Low efficiency - 50Hz Operation mode Heat exchange system Heat exchange element Humidifier System Dimensions Unit HeightxWidthxDepth Weight Unit Casing Material Fan-Air flow rate Heat exchange mode Ultra high/High/Low Bypass mode Ultra high/High/Low - 50Hz Fan-External static Ultra high/High/Low pressure - 50Hz Air filter Type Sound pressure level Heat exchange mode Ultra high/High/Low Bypass mode Ultra high/High/Low - 50Hz Operation range Around unit Supply air Return air On coil temperature Cooling/Max./Heating/Min. Refrigerant Control Type GWP Connection duct diameter Piping connections Liquid OD Gas OD Water supply Drain Power supply Phase/Frequency/Voltage Current Maximum fuse amps (MFA) 150 % % VKM80-100GB(M) 50GB 0.270/0.230/ 0.170 0.270/0.230/ 0.140 4.71 / 1.91 / 3.5 5.58 / 2.38 / 3.5 80GB 0.330/0.280/ 0.192 0.330/0.280/ 0.192 7.46 / 2.96 / 5.6 8.79 / 3.79 / 5.6 100GB 0.410/0.365/ 0.230 0.410/0.365/ 0.230 9.12 / 3.52 / 7.0 10.69 / 4.39 / 7.0 50GBM 0.270/0.230/ 0.170 0.270/0.230/ 0.170 4.71 / 1.91 / 3.5 5.58 / 2.38 / 3.5 80GBM 0.330/0.280/ 0.192 0.330/0.280/ 0.192 7.46 / 2.96 / 5.6 8.79 / 3.79 / 5.6 100GBM 0.410/0.365/ 0.230 0.410/0.365/ 0.230 9.12 / 3.52 / 7.0 10.69 / 4.39 / 7.0 76/76/77.5 78/78/79 74/74/76.5 76/76/77.5 78/78/79 74/74/76.5 64/64/67 67/67/69 mm kg 387x1,764x832 94 m³/h m³/h Pa 500/500/440 500/500/440 66/66/68 62/62/66 64/64/67 66/66/68 62/62/66 71/71/73 65/65/69 67/67/69 71/71/73 65/65/69 Heat exchange mode / Bypass mode / Fresh-up mode Air to air cross flow total heat (sensible + latent heat) exchange Specially processed non-flammable paper Natural evaporating type 387x1,764x1,214 387x1,764x832 387x1,764x1,214 110 112 100 119 123 Galvanised steel plate 750/750/640 950/950/820 500/500/440 750/750/640 950/950/820 750/750/640 950/950/820 500/500/440 750/750/640 950/950/820 210/170/140 210/160/110 dBA dBA °CDB °CDB °CDB °CDB 39/37/35 40/38/35.5 mm mm mm mm 200 Hz/V A 150/100/70 41.5/39/37 41.5/39/37 -15/43 250 - 200/150/120 Multidirectional fibrous fleeces 41/39/36.5 38/36/34 41/39/36.5 39/36/34.5 0°C~40°CDB, 80% RH or less -15°C~40°CDB, 80% RH or less 0°C~40°CDB, 80% RH or less Electronic expansion valve R-410A 2,087.5 200 6.35 12.7 PT3/4 external thread 1~/50/220-240 15 205/155/105 110/70/60 40/37.5/35.5 41/38/36 40/38/35.5 41/39/35.5 -15/43 250 6.4 Daikin’s air handling units solutions You will find your match Why choose Daikin air handling units with a DX connection? Simplifying business Complete range of possibilities The unique total solution approach by Daikin helps businesses to propose better cross-pillar solutions, to increase their success ratio by providing unmatchable product combinations to the end-user and to simplify the life of installers by supplying highquality products coming from the same manufacturer. Contrary to other manufacturers, Daikin does not use OEM products in its AHU with DX offer. Many competitors are either offering OEM DX outdoor units or OEM AHU which create additional problems when warranties or faults arise. Having a single interface for your business makes Daikin the right choice. Thanks to the most complete offer in the market, Daikin has the solution for all types of commercial applications requiring fresh air. Daikin provides ventilation solutions based on AHU from 2,500 m3/h up to 140,000 m3/h either with natural heat recovery or more advanced ventilation solutions where a VRV outdoor unit can be connected to the Daikin AHU for ultimate climate control. The harmonized control, between the VRV outdoor unit and the AHU, offer outstanding reliable operation of the system when connected to an iTM. One-stop shop Daikin is the only global manufacturer in the market capable of offering a true Plug & Play solution where Daikin AHUs manufactured by Daikin Applied Europe and certified by Eurovent, offer off-the-shelf compatibility with Daikin’s unique VRV outdoor unit range for the best performance in the market. This unique integration of cross-pillar products under the same umbrella, gives the customer both peace-of-mind and added value when promoting a total solution approach. Advantages › Unique manufacturer offering a complete range › Plug & Play solution › Direct iTM compatibility 151 Overview of VRV & ERQ condensing units Why use VRV and ERQ condensing units for connection to air handling units? High Efficiency Daikin heat pumps are renowned for their high energy efficiency. Integrating the AHU with a heat recovery system is even more effective since an office system can frequently be in cooling mode while the outdoor air is too cold to be brought inside in an unconditioned state. In this case heat from the offices is merely transferred to heat up the cold fresh air. Outside air = 10°C Fresh air supplied at 21°C. The temperature difference with the outdoor air is heated up efficiently by heat recovery via A/C system Indoor temperature 22°C, needs cooling because of solar radiation. The excessive heat can be transferred to the AHU. Fast response to changing loads resulting in high comfort levels Daikin ERQ and VRV units respond rapidly to fluctuations in supply air temperature, resulting in a steady indoor temperature and resultant high comfort levels for the end user. The ultimate is the VRV range which improves comfort even more by offering continuous heating, also during defrost. Easy Design and Installation The system is easy to design and install since no additional water systems such as boilers, tanks and gas connections etc. are required. This also reduces both the total system investment and running cost. Daikin Fresh air package › Plug & Play connection between VRV/ERQ and the entire D-AHU modular range. › Factory fitted and welded DX coil control and expansion valve kits. VRV IV or ERQ condensing unit Factory fitted and welded fresh air package Electronic expansion valve (EKEXV) Control box (EKEQ) 152 Control possibilities In order to maximise installation flexibility, 4 types of control systems are offered W control: Off the shelf control of air temperature (discharge temperature, suction temperature, room temperature) via any DDC controller, easy to setup X control: Precise control of air temperature (discharge temperature, suction temperature, room temperature) requiring a preprogrammed DDC controller (for special applications) 1. W control (TS/TR/TROOM control): 2. X control (TS/TR/TROOM control): Air temperature control via DDC controller Room temperature is controlled as a function of the air handling unit suction or discharge air (customer selection). The DDC controller is translating the temperature difference between set point and air suction temperature (or air discharge temperature or room temperature) into a proportional 0-10V signal which is transferred to the Daikin control box (EKEQFCBA). This voltage modulates the capacity requirements of the outdoor unit. 0-10V TEXT EXT Control boxbox: Daikin control EKEQFCBA EKEQFCBA Precise air temperature control via DDC controller Room temperature is controlled as a function of the air handling unit suction or discharge air (customer selection). The DDC controller is translating the temperature difference between set point and air suction temperature (or air discharge temperature or room temperature) into a reference voltage (0-10V) which is transferred to the Daikin control box (EKEQFCBA). This reference voltage will be used as the main input value for the compressor frequency control. OR OR AHU AHU DDC DDC Z control: Control of air temperature (suction temperature, room temperature) via Daikin control (no DDC controller needed) Y control: Control of refrigerant (Te/Tc) temperature via Daikin control (no DDC controller needed) TTR R DDC DDC + TETC TTOA OA - TTS 0-10V TEXT EXT Control boxbox: Daikin control EKEQFCBA EKEQFCBA By fixed evaporating /condensing temperature A fixed target evaporating or condensing temperature can be set by the customer. In this case, room temperature is only indirectly controlled. A Daikin wired remote control (BRC1* - optional) have to be connected for initial set-up but not required for operation. TEXT EXT + TETC - TTS S TTROOM ROOM AHU BRC1D* BRC1D* BRC1E* BRC1E* BRC1H* Control box box Control IV) EKEQMCBA (VRV IV) EKEQDCB EKEQDCB (ERQ) OR OR TR = Return air temperature TOA = Outdoor air temperature TC = Condensing temperature Possibility Z EKEQDCB EKFQMCBA* TRR + TE TTOA OA TE = Evaporating temperature EKEQFCBA S TEXT EXT TEXT = Extraction air temperature Option kit TTS Control your AHU just like a VRV indoor unit with up to 100% fresh air Allows the possibility to control the AHU just like a VRV indoor unit. Meaning temperature control will be focused on return air temperature from the room into the AHU. Requires BRC1* for operation. The only control that allows the combination of other indoor units to the AHU at the same time. TS = Supply air temperature Possibility W Possibility X Possibility Y - 4. Z control (TS/TROOM control): TRR TTOA OA R TTROOM ROOM 3. Y control (TE/TC control): Control box box EKEQFCBA EKEQFCBA TTR + TETC TTOA OA S TTROOM ROOM BRC1D* BRC1D* BRC1E* BRC1E* BRC1H* OR OR AHU AHU - TC TS TTROOM ROOM TROOM = Room air temperature Features Off-the-shelf DDC controller that requires no pre-configuration Pre-configured DDC controller required Using fixed evaporating temperature, no set point can be set using remote control Using Daikin infrared remote control BRC1* Temperature control using air suction temperature or room temperature (via remote sensor) * EKEQMCB (for ’multi’ application) 153 Daikin Fresh air package - VRV connections - for larger capacities (from 8 to 54HP) An advanced solution for both pair and multi application › › › › › › Inverter controlled units Heat recovery, heat pump R-410A Control of room temperature via Daikin control Large range of expansion valve kits available BRC1H519W/S/K is used to set the set point temperature (connected to the EKEQMCBA). › Connectable to all VRV heat recovery and heat pump systems W, X, Y control for VRV IV heat pump Z control for all VRV outdoor units Refrigerant piping F1-F2 P1-P2 154 Daikin Fresh air package - ERQ connections ERQ - for smaller capacities (from 100 to 250 class) A basic fresh air solution for pair application › › › › › Inverter controlled units Heat pump R-410A Wide range of expansion valve kits available Perfect for the Daikin Modular air handling unit The “Daikin Fresh Air Package” provides a complete Plug & Play Solution including AHU, ERQ or VRV Condensing Unit and all unit control (EKEQ, EKEX, DDC controller) factory mounted and configured. The easiest solution with only one point of contact. Ventilation Capacity range Cooling capacity Heating capacity Power input Nom. Nom. Cooling Heating EER COP Dimensions Weight Casing Fan-Air flow rate Power supply Current Ventilation Capacity range Cooling capacity Heating capacity Power input EER COP Dimensions Weight Casing Fan-Air flow rate Sound power level Sound pressure level Operation range Refrigerant Piping connections Power supply Current 100AV1 4 11.2 12.5 2.81 2.74 125AV1 5 14.0 16.0 3.51 3.86 140AV1 6 15.5 18.0 4.53 4.57 3.42 3.94 3.99 4.56 Unit Unit Material Cooling Heating Sound power level Cooling Sound pressure level Cooling Heating Operation range Cooling Heating On coil temperature Refrigerant Type Charge Piping connections Nom. Nom. ERQ HP kW kW kW kW ERQ-AW1 HeightxWidthxDepth Nom. Nom. Nom. Nom. Nom. Min./Max. Min./Max. Heating/Min./Cooling/Max. m³/min m³/min dBA dBA dBA °CDB °CWB °CDB 102 66 50 52 105 67 51 53 -5/46 -20/15.5 10/35 R-410A 4.0 8.4 2,087.5 Expansion valve (electronic type) 9.52 kg TCO₂eq GWP Control Liquid OD Gas OD Drain OD Phase/Frequency/Voltage Maximum fuse amps (MFA) mm mm mm Hz/V A Nom. Nom. Cooling Heating ERQ HP kW kW kW kW Unit Unit Material Cooling Heating Nom. Nom. Cooling Heating On coil temperature Type Charge 4.15 1,345x900x320 120 Painted galvanized steel plate 106 mm kg Nom. Nom. HeightxWidthxDepth Nom. Nom. Min./Max. Min./Max. Heating/Min./Cooling/Max. GWP Control Liquid OD Gas OD Phase/Frequency/Voltage Maximum fuse amps (MFA) mm kg 15.9 19.1 26x3 1N~/50/220-240 32.0 125AW1 5 14.0 16.0 3.52 4.00 3.98 4.00 1,680x635x765 159 m³/min m³/min dBA dBA °CDB °CWB °CDB 95 95 72 54 kg TCO₂eq 6.2 12.9 mm mm Hz/V A 69 53 55 15.9 16 200AW1 8 22.4 25.0 5.22 5.56 4.29 4.50 1,680x930x765 187 Painted galvanized steel plate 171 171 78 57 -5/43 -20/15 10/35 R-410A 7.7 16.1 2,087.5 Electronic expansion valve 9.52 19.1 3N~/50/400 25 250AW1 10 28.0 31.5 7.42 7.70 3.77 4.09 240 185 185 58 8.4 17.5 22.2 155 Expansion valves & control boxes Integration of ERQ and VRV in third party air handling units a wide range of expansion valve kits and control boxes Combination table Control box ERQ100 1-phase ERQ125 ERQ140 ERQ125 3-phase ERQ200 ERQ250 VRV III VRV IV H/P / VRV IV W-series VRV IV S-series VRV IV H/R VRV IV i-series • • • • Expansion valve kit EKEQDCB EKEQFCBA EKEQMCBA Z control W,X,Y control Z control P P P P P P P P P P P P n1 EKEXV50 n1 EKEXV63 P P P n1 EKEXV80 P P P P n1 EKEXV100 P P P P P n1 EKEXV125 P P P P P P n1 EKEXV140 P P P P P n1 EKEXV200 P P n1 EKEXV250 P P n1 EKEXV400 n1 EKEXV500 n1 Mixed connection with VRV indoor units Not possible Mandatory - P (1 -> 3) n2 n2 n2 n2 n2 n2 n2 n2 n2 n2 n2 Possible (not mandatory) - n1 - n1 n1 n1 n1 n1 n1 n1 n1 n1 n1 Mandatory P (pair application): combination depends on the capacity of the air handling unit n1 (multi application) - Combination of AHUs and VRV DX indoors (mandatory). To determine the exact quantity please refer to the engineering data book. n2 (multi application) - Combination of AHUs and VRV DX indoors (not mandatory). To determine the exact quantity please refer to the engineering data book. Control box EKEQFA can be connected to some types of VRV IV outdoor units (with a maximum of 3 boxes per unit). Do not combine EKEQFA control boxes with VRV DX indoor units, RA indoor units or hydroboxes Capacity table Cooling EKEXV Class 50 63 80 100 125 140 200 250 400 500 Heating Allowed heat exchanger Allowed heat exchanger capacity (kW) volume (dm3) Minimum Standard Maximum Minimum Maximum 5.0 5.6 6.2 1.33 1.65 6.3 7.1 7.8 1.66 2.08 7.9 9.0 9.9 2.09 2.64 10.0 11.2 12.3 2.65 3.30 12.4 14.0 15.4 3.31 4.12 15.5 16.0 17.6 4.13 4.62 17.7 22.4 24.6 4.63 6.60 24.7 28.0 30.8 6.61 8.25 35.4 45.0 49.5 9.26 13.2 49.6 56.0 61.6 13.2 16.5 EKEXV Class 50 63 80 100 125 140 200 250 400 500 Saturated evaporating temperature: 6°C Air temperature: 27°C DB / 19°C WB Allowed heat exchanger Allowed heat exchanger capacity (kW) volume (dm3) Minimum Standard Maximum Minimum Maximum 5.6 6.3 7.0 1.33 1.65 7.1 8.0 8.8 1.66 2.08 8.9 10.0 11.1 2.09 2.64 11.2 12.5 13.8 2.65 3.30 13.9 16.0 17.3 3.31 4.12 17.4 18.0 19.8 4.13 4.62 19.9 25.0 27.7 4.63 6.60 27.8 31.5 34.7 6.61 8.25 39.8 50.0 55.0 9.26 13.2 55.1 63.0 69.3 13.2 16.5 Saturated condensing temperature: 46°C Air temperature: 20°C DB EKEXV - Expansion valve kit for air handling applications Ventilation Dimensions Unit Weight Unit Sound pressure level Nom. Operation range On coil Heating Min. temperature Cooling Max. Refrigerant Type / GWP Piping connections Liquid OD EKEXV mm kg dBA °CDB °CDB 50 63 80 100 125 140 401x215x78 2.9 45 10 (1) 35 (2) 200 250 400 500 12.7 15.9 R-410A / 2.087,5 mm 6.35 9.52 (1) The temperature of the air entering the coil in heating mode can be reduced to -5°CDB. Contact your local dealer for more information. (2) 45% Relative humidity. EKEQ - Control box for air handling applications Ventilation Application Outdoor unit Dimensions Weight Power supply EKEQ Unit Unit Phase/Frequency/Voltage mm kg Hz/V FCBA See note ERQ / VRV DCB Pair ERQ 132x400x200 3.9 MCBA Multi VRV 3.6 1~/50/230 The combination of EKEQFCBA and ERQ is in pair application. The EKEQFCBA can be connected to some type of VRV IV outdoor units with a maximum of 3 control boxes. The combination with DX indoor units, hydroboxes, RA outdoor units, ... is not allowed. Refer to the combination table drawing of the outdoor unit for details. 156 Selection procedure Pair application selection › the outdoor unit is connected to ONE COIL (with single circuit or maximum 3 interlaced circuits) using up to 3 control boxes › indoor unit combination is not allowed › only works with X, W, Y control Step 1: Required AHU capacity An AHU with double flow, heat recovery and 100% fresh air is to be installed in Europe where the outdoor sizing temperature is 35 ºCDB and the target supply air temperature for fresh air is 25 ºCDB. Load calculations point to a required capacity of 45kW. By checking on the EKEXV capacity table, for cooling operation, 40kW falls within the 400 class valve. Since 40kW is not the nominal capacity, a class adjustment has to be done. 40/45=0,89 and 0,89x400=356. So the capacity class of the expansion valve kit is 356. Step 3: Control box selection In this particular case, the control will work with precise air temperature control. Only W or X control allow this. Since the consultant wants to use an “off-the-shelf” DDC module, the EKEQFCBA box with W control allows easy set-up due to pre-set factory values. Step 2: Outdoor unit selection For this AHU, a VRV IV heat pump model with continuous heating is going to be used (RYYQ-T series). For a capacity of 40kW at 35 ºCDB, an outdoor of 14HP (RYYQ14T) is selected. The capacity class of the 14 HP outdoor unit is 350. Total connection ratio of the system is 356/350=102% hence it falls within the range 90-110%. Multi application selection › the outdoor unit can be connected to MULTIPLE COILS (and their control boxes) › indoor units are also connectable but not mandatory › only works with Z control Step 1: Required AHU capacity Step 2: Outdoor unit selection An AHU with double flow, heat recovery and 100% fresh air is to be installed in Europe where the outdoor sizing temperature is 35 ºCDB and the target supply air temperature for fresh air is 25 ºCDB. On top of this, for this building, 5 round-flow cassette units FXFQ50A will also be connected to this OU. Load calculations point to a required capacity of 20kW for the AHU and 22,5 kW for the indoor untis. By checking on the EKEXV capacity table, for cooling operation, 20kW falls within the 200 class valve. Since 22,4 kW is the nominal capacity, a class adjustment has to be done. 20/22,4=0,89 and 0,89x200=178. So the capacity class of the expansion valve kit is 178. Total capacity class of the indoor unit system is 178+250=428 For this system where a AHU is connected with indoor units, it is mandatory to use a heat recovery unit. By consulting the engineering databook for REYQ-T, the total required capacity of 42,5 kW requires a 16HP model REYQ16T. Which will deliver 45kW at the design temperature of 35 ºCDB. This unit has a capacity class of 400. Total connection ratio of the system is 428/400=107% hence it falls within the range 50-110%. Step 3: Control box selection In this particular case, the only available control is Z control and the combination of AHU and VRV DX indoor units requires EKEQMCBA control box. 157 Biddle air curtains Biddle air curtains provide highly efficient solutions for retailers and consultants to combat the issue of climate separation across their outlet or office doorway. 158 Biddle air curtains Biddle air curtains connected to Daikin Heat Pumps ‘Open Door’ Trading High efficiency and low CO2 emission Although the customer-friendly aspects of open door trading are widely appreciated by retail and commercial outlet managers, open doors can also give rise to massive losses in conditioned warm or cold air and hence, energy. Biddle air curtains however, not only preserve indoor temperatures and generate significant savings, they also represent an invitation for customers, to enter a pleasant trading and working environment. An efficient outdoor/indoor climate separation limits heat loss through the door opening and enhances the efficiency of the air conditioning system. Combining Biddle air curtains with Daikin heat pumps can lead to savings up to 72% compared to electric air curtains and a paypack period of less than 1.5 years! Air curtain size selector Door height (m) 3.0 2.5 2.3 S 2.4 2.15 M L 2.75 2.0 S M L S 2.3 M 2.5 L Favourable Normal Unfavourable Covered shopping mall or No opposite open doors, Location at a corner or revolving door entrance little direct wind, building square, multiple floors and/ with ground floor only or open stairwell Biddle comfort air curtian nomenclature CY V S 150 DK 80 F S C Controller (standard) Color. B=White (RAL6010), S: Grey (RAL9006) Installation type: F=Freehanging, C=Cassette, R=Recessed Capacity class (kW) Daikin direct expansion Door width (cm) Range. S=small, M=Medium, L=Large, XL= Extra Large Connectable to VRV Biddle comfort air curtain Portfolio Type Product name Biddle air curtain free hanging CYV S/M/L-DK-F Biddle air curtain cassette CYV S/M/L-DK-C Biddle air curtain recessed CYV S/M/L-DK-R › A payback time of less than 1.5 years compared to electrical air curtains › Easy and quick installation › Maximum energy efficiency thanks to rectifier technology › 85% air separation efficiency › Cassette model (C): mounted into a false ceiling enhancing aesthetics › Free-hanging model (F): easy wall mounted installation › Recessed model (R) : neatly concealed in the ceiling 159 CYVS/M/L-DK-F/C/R Biddle air curtain for VRV Packtime of less than 1.5 years electric air curtain 12000 10000 total cost (installation + running cost) in € › Connectable to VRV heat recovery and heat pump › VRV is among the first DX systems suitable for connection to air curtains › Free-hanging model (F): easy wall mounted installation › Cassette model (C): mounted into a false ceiling leaving only the decoration panel visible › Recessed model (R): neatly concealed in the ceiling › Provides virtually free air curtain heating via recovered heat from indoor units in cooling mode (in case of VRV heat recovery) › Easy and quick to install at reduced costs since no additional water sytems, boilers and gas connections are required › PATENTED TECHNOLOGY: Maximum energy efficiency stemming from almost zero down flow turbulence, optimised air flow and the application of advanced discharge rectifier technology › Around 85% air separation efficiency, greatly reducing both heat loss and required indoor unit heating capacity 8000 Daikin heat pump with Biddle air curtain* 6000 4000 2000 0 1 years 2 VRV Network Solution Biddle comfort air curtain (CY) Integration in a VRV total solution * Payback period and gains calculated based upon the following: Air curtain is 9hrs/day – 156 days year (1,404 hrs/year) in use. Annual energy consumption for an electric air curtain: 3,137EUR (COP = 0.95). Typical installation cost: 1,000EUR; Typical equipment cost: 2,793EUR. Annual energy consumption for CYQS200DK100FBN and ERQ100AV: 748EUR (COP 4.00). Typical installation cost: 2,000EUR; Typical equipment cost: 5,150EUR. Calculation based upon electricity cost: 0,1705EUR /kWh 160 Biddle air curtain for VRV CYVM150DK80FSC CYVM150DK80CSN CYVM150DK80RSN Access all technical information on Biddle air curtains at my.daikin.eu or click here Small Heating capacity Power input Delta T Casing Dimensions Speed 3 Fan only Heating Speed 3 Colour Unit Nom. Nom. Height F/C/R Width F/C/R Depth F/C/R Required ceiling void > Door height Max. Door width Max. Weight Unit Fan-Air flow rate Heating Speed 3 Sound pressure level Heating Speed 3 Refrigerant Type / GWP Piping connections Liquid/OD/Gas/OD Required accessories (should be ordered separately) Power supply Voltage kW kW kW K mm mm mm mm m m kg m³/h dBA mm V Medium CYVS100DK80 *BC/*SC CYVS150DK80 *BC/*SC CYVS200DK100 *BC/*SC 7.40 0.23 0.23 19 9.0 0.35 0.35 11.6 0.46 0.46 CYVS250DK140 *BC/*SC CYVM100DK80 *BC/*SC CYVM150DK80 *BC/*SC CYVM200DK100 *BC/*SC CYVM250DK140 *BC/*SC 16.2 9.2 11.0 13.4 19.9 0.58 0.37 0.56 0.75 0.94 0.58 0.37 0.56 0.75 0.94 15 16 17 14 13 15 BN: RAL9010 / SN: RAL9006 270/270/270 1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548 1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548 590/821/561 420 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 1.0 1.5 2.0 2.5 1.0 1.5 2.0 2.5 56 66 83 107 57 73 94 108 1,164 1,746 2,328 2,910 1,605 2,408 3,210 4,013 47 49 50 51 50 51 53 54 R-410A / 2,087.5 9.52/16.0 9.52/19.0 9.52/16.0 9.52/19.0 Daikin wired remote control (BRC1H51(9)W/S/K / BRC1E53A/B/C / BRC1D52) 230 Large Heating capacity Power input Delta T Casing Dimensions Speed 3 Fan only Heating Speed 3 Colour Unit Nom. Nom. Height F/C/R Width F/C/R Depth F/C/R Required ceiling void > Door height Max. Door width Max. Weight Unit Fan-Air flow rate Heating Speed 3 Sound pressure level Heating Speed 3 Refrigerant Type / GWP Piping connections Liquid/OD/Gas/OD Required accessories (should be ordered separately) Power supply Voltage kW kW kW K mm mm mm mm m m kg m³/h dBA mm V CYVL100DK125*BC/*SC 15.6 0.75 0.75 CYVL150DK200*BC/*SC 23.3 1.13 1.13 CYVL200DK250*BC/*SC CYVL250DK250*BC/*SC 29.4 31.1 1.50 1.88 1.50 1.88 15 14 12 BN: RAL9010 / SN: RAL9006 370/370/370 1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548 774/1,105/745 520 3.0 (1) / 2.75 (2) / 2.5 (3) 3.0 (1) / 2.75 (2) / 2.5 (3) 3.0 (1) / 2.75 (2) / 2.5 (3) 3.0 (1) / 2.75 (2) / 2.5 (3) 1.0 1.5 2.0 2.5 76 100 126 157 3,100 4,650 6,200 7,750 53 54 56 57 R-410A / 2,087.5 9.52/16.0 9.52/19.0 9.52/22.0 Daikin wired remote control (BRC1H51(9)W/S/K / BRC1E53A/B/C / BRC1D52) 230 (1) Favorable conditions: covered shopping mall or revolving door entrance (2) Normal conditions: little direct wind, no opposite open doors, building with ground floor only (3) Unfavorable conditions: location at a corner or square, multiple floors and/or open stairway 161 Control Systems Connect with Daikin If you are a user or installer it is important you can interact with our systems in the easiest way, from anywhere you are. For any user our interfaces create peace of mind that their system is running in the best possible way. Depending on the type of user and application Daikin develops controls and cloud services to ensure the best experience. › For home owners it means app control of their home comfort. › For hotel owners it means easy and stylish personal control for guests, with an integration in hotel booking software for central control › For technical managers it means cloud access to all sites, with the possibility to benchmark, optimize performance › For installers it means easy transfer of settings during commissioning, remote retrieval of errors and preventive alerts to save time on maintenance or interventions Our controls enable you to connect with your customer, save time, improve your comfort intelligently and reduce energy bills. Remote monitoring 24/7 162 White Silver Black Control Systems New online controller for VRV New premium design wired remote control Control Systems 163 Application overview 164 Individual control systems Daikin Online controller Madoka wired remote controller Wired / infrared remote controllers Multi-zone controller 166 166 168 170 172 Centralised control systems 174 Centralised remote controller / Unified ON/OFF controller / Schedule timer 174 175 176 178 Tabl et Standard protocol interfaces 182 Modbus interface 182 KNX Interface 185 PMS Interface for hotels 186 BACnet Interface187 LonWorks Interface188 Daikin Configurator Tool 189 Daikin Cloud Service for commercial DX systems 190 Other devices Wireless room temperature sensor Wired room temperature sensor Other integration devices 192 192 192 193 Options & Accessories 195 163 Application overview Control solutions summary Daikin offers various control solution adapted to the requirements of even the most demanding commercial application. › Advanced control solutions for those customers that expect Daikin to deliver a mini BMS solution, including advance energy management › Basic control solutions for those customers with few requirements and limited budget › Integrating control solutions for those customers that would like to integrate Daikin units into their existing BMS system Shop Unit control Integrating control Advanced control Tablet BRP069* BRC1H519W7/ S7/K7 RTD-20 RTD-Net KLIC-DI EKMBDXA DCC601A51 DCM601A51 1 unit for 32 indoor unit(s) (5) 1 iTM for 64 indoor unit(s) (groups) (1) (limited) (2) (2) (6) (2) (2) (3) (3) Smartphone 1 remote 1 gateway 1 gateway for 1 gateway for 1 gateway for control for up controller for for 1 indoor 1 indoor unit 1 indoor unit max. 64 indoor to 50 indoor 1 indoor unit unit (group) (group) unit(s) (groups) units (group) & 10 outdoors Automatic control of A/C Limit control possibilities for shop staff Create zones within the shop Interlock with eg. Alarm, PIR sensor Integration into smart home systems (7) Integrate Daikin units into existing BMS via Modbus Integrate Daikin units into existing BMS via KNX Integrate Daikin units into existing BMS via HTTP Monitor energy consumption (4) (4) Advanced energy management Allows free cooling Voice control (6) Integrate Daikin products cross pillars into Daikin BMS Integrate third party products into Daikin BMS Online control Manage multiple sites (1) 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Via Daikin cloud service (3) Through own IT set-up (not Daikin cloud server) (4) Not available on all indoors (5) Up to 10 DCC601A51 can be combined as a single site on Daikin Cloud Service (6) Only for BRP069C51, connection to Google Assistant and Amazon Alexa; (7) only for BRP069C51, contact your local sales representative for an overview of available services. Hotel Unit control Integrating control Advanced control PMS Interface BRC1H519W7/S7/K7 RTD-HO 1 remote controller 1 gateway for 1 for 1 indoor unit indoor unit (group) (group) Hotel guest can control & monitor basic functionalities from his room Limit control possibilities for hotel guests Interlock with window contact Interlock with key-card Integrate Daikin units into existing BMS via Modbus Integrate Daikin units into existing BMS via KNX (2) (2) KLIC-DI 1 gateway for 1 indoor unit DCM010A51 1 interface for up to 1 iTM for 64 indoor 2,500 indoor units unit(s) (groups) (1) (3) Integrate Daikin units into existing BMS via HTTP Integrate Daikin unit control in hotel booking software Oracle Opera PMS Monitor energy consumption Advanced energy management Integrate Daikin products cross pillars into Daikin BMS Integrate third party products into Daikin BMS Online control (1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Via BRP7A51 adapter (3) requires KNX compatible controller 164 DCM601A51 Application overview Office Unit control Integrating control Advanced control Tablet BRC1H519W7/S7/K7 EKMBDXA 1 gateway for max. 1 remote controller 64 indoor unit(s) for 1 indoor unit (groups) & 10 (group) outdoors Automatic control of A/C Limit control possibilities for office staff 1 gateway for 64 indoor unit(s) (groups) Centralised control for management Local control for office staff DMS504B51 Integrate Daikin units into existing BMS via Modbus DMS502A51 DCC601A51 DCM601A51 1 gateway for 128 indoor unit(s) 1 unit for 32 indoor 1 iTM for 64 indoor (groups), 20 out- unit(s) (groups) (5) unit(s) (groups) (1) doors (2) (4) through Web Remote management Integrate Daikin units into existing BMS via HTTP Integrate Daikin units into existing BMS via LonTalk Integrate Daikin units into existing BMS via BACnet Energy consumption read out (3) Monitor energy consumption Advanced energy management (6) PPD software to distribute used kWh/indoor unit (4) (4) (7) (5) Integrate Daikin cross pillar products into Daikin BMS (4) (4) Integrate third party products into Daikin BMS Online control Manage multiple sites (1) 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) extension (DAM411B51) needed to have up to 256 indoor unit(s) (groups), 40 outdoors (3) Not available on all indoor units (4) Via Daikin cloud service (5) Through own IT set-up (not Daikin cloud sever) (5) Up to 10 DCC601A51 can be combined as a single site on Daikin Cloud Service (6) via DAM412B51 option (7) via DCM002A51 option Infrastructure cooling Automatic control of A/C Back-up operation Duty rotation Limit control possibilities in the technical cooling room Unit Integrating Advanced BRC1H519W7/S7/K7 RTD-10 DCM601A51 1 remote controller for 1 indoor unit (group) (2) 1 gateway for 1 indoor unit (group) Up to 8 gateways can be linked together 1 iTM for 64 indoor unit(s) (groups) (1) If room temperature above max., then show alarm & start standby unit. If an error occurs, an alarm will be shown. If an error occurs, activate an alarm output Via KRP2/4A option (3) Via WAGO I/O (1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Infrastructure cooling functions only compatible with indoor units connected to RZQG*/RZAG* outdoor units. (3) See option list of indoor unit 165 Individual control systems Daikin Online controller NEW BRP069C51 Always in control, no matter where you are The Daikin Online Controller application can control and monitor the status of your system up to 50 split air conditioning units and allows you to: Monitor: › The status of your air conditioner system › Consult energy consumption graphs (Split only) Control: › The operation mode, set temperature, fan speed and powerful mode, air direction and filtering (streamer) function (Available functions depending on connected model) › Remotely control your system and domestic hot water › Zone control: control multiple units at once › Voice control via Amazon Alexa or Google Assistant › Integration in smart home eco systems (contact your local sales representative for connectable systems) Schedule: › Schedule the set temperature and operation mode with up to 6 actions per day for 7 days › Enable holiday mode › View in an intuitive mode › Demand control/power limitation (Split only) App with intuitive lay-out 166 Control Schedule Monitor Monitor Control operation mode, temperature, air purification, fan speed & air direction Schedule the set temperature, operation mode and fan speed or holiday periods Monitor your energy consumption Monitor the rooms in your house Connectable VRV indoor units: > FXFA-A > FXZA-A > FXDA-A > FXSA-A > FXAA-A INTUITIVE ONLINE AND VOICE CONTROL 167 Individual control systems Madoka wired remote controller The beauty of simplicity. Silver RAL 9006 (metallic) BRC1H519S7 Black RAL 9005 (matte) BRC1H519K7 White RAL9003 (glossy) BRC1H519W7 User-friendly wired remote controller with premium design Madoka combines refinement and simplicity › Sleek and elegant design › Intuitive touch-button control NEW › › Three colours to match any interior › Compact, measures only 85 x 85 mm NEW › 168 Three display options: standard, detailed and new symbolic view Advanced settings copy function and commissioning via smartphone Madoka Assistant Simplifies the advanced settings such as schedule or set point limitation Visual interface simplifies advanced settings such as schedule setting, energy saving activation, setting restrictions, etc. NEW Save field settings and schedules on your phone and upload to multiple controllers, saving time and cost Easy and quick commissioning Featuring Bluetooth® low energy technology Easy setting of schedules Advanced user settings Installer settings Field settings 169 Individual control systems BRC1H519W7 / BRC1H519S7 / BRC1H519K7 Madoka wired remote controller for Sky Air and VRV A complete redesigned controller focussed to enhance user experience BRC1H519W7 › › NEW › › Sleek and elegant design Intuitive touch-button control Three display options: standard, detailed and new symbolic view Direct access to basic functions (on/off, set point, mode, target values, fan speed, louvres, filter icon & reset, error & code) › Three colours to match any interior › Compact, measures only 85 x 85 mm › Real time clock with auto update to daylight saving time Hotel application features BRC1H519S7 › Energy saving through key card, window contact integration and set point limitation (BRP7A*) › Flexible setback function ensures room temperature remains within comfortable limits to ensure guest comfort Key card and window contact integration P1 P2 Adaptor (BRP7A*) Key card (field supply) BRC1H519K7 Window contact (field supply) Madoka Madoka Assistant: Advanced settings can be easily done via your smartphone A range of energy-saving functions that Other functions can be selected individually NEW › Save field settings and schedules on your phone and › Temperature range restriction: Save on energy by setting the low temperature limit in cooling mode and the high temperature limit in heating mode (1) › Setback function › Adjustable presence detector and floor sensor (available on the Round Flow and Fully Flat Cassettes) › Automatic temperature reset › Auto off timer Kilowatt-hour consumption tracking (2) upload to multiple controllers, saving time and cost › Up to three independent schedules can be programmed, allowing you to switch easily between them throughout the year (e.g. summer/winter/ mid-season) › Menu settings can be individually locked or restricted › The outdoor unit can be set to quiet mode and power consumption limit control by schedule (3) › Real-time clock that updates automatically for daylight saving The kWh indicator displays indicative power consumption for the last day/month/year. Cost-effective solution for infrastructure cooling applications > Only in combination with RZAG* / RZQG* > Duty rotation After a certain period of time, the operating unit will go into standby and the standby unit will take over, extending the system lifetime. Rotation interval can be set for 6, 12, 24, 72 or 96 hours, as well as weekly. > Back-up operation: if one unit fails, the other unit will start automatically (1) Also available in auto cooling/heating changeover mode (2) For Sky Air FBA, FCAG and FCAHG pair combinations only 170 (3) Only available on RZAG*, RZASG*, RZQG*, RZQSG* Individual control systems BRC1E53A/B/C User friendly remote control for Sky Air and VRV A series of energy saving functions that can be individually selected › › › › Graphical display of indicative electricity consumption (Function available in combination with FBA-A, FCAG Demand control (1) Temperature range limit Setback function Presence & floor sensor connection (available on round flow and fully flat cassette) › kWh indication (2) › Set temperature auto reset › Off timer › Cost-effective solution for infrastructure cooling applications and FCAHG) > Only in combination with Sky Air A-series or Seasonal Smart outdoor unit (1) Only available on RZAG*, RZASG*, RZQG*, RZQSG* Other functions › › › › Up to 3 independent schedules Possibility to individually restrict menu functions Choice of display between symbol or text Real time clock with auto update to daylight saving time › Built-in backup power for clock (up to 48 hours). Settings are always kept in case of power loss. › Supports multiple languages: BRC1E53A: English, German, French, Dutch, Spanish, Italian, Portuguese BRC1E53B: English, Czech, Croatian, Hungarian, Romanian, Slovenian, Bulgarian BRC1E53C: English, Greek, Russian, Turkish, Polish, Slovak, Albanian I (2) For Sky Air FBA, FCAG and FCAHG pair combinations only BRC1D52 Wired remote control for Sky Air and VRV › Schedule timer: Five day actions can be set › Home leave (frost protection): during absence, the indoor temperature can be maintained at a certain level. This function can also switch the unit ON/OFF › User friendly HRV function, thanks to the introduction of a button for ventilation mode and fan speed › Immediate display of fault location and condition › Reduction of maintenance time and costs BRC1D52 ARC4*/BRC4*/BRC7* Infrared remote control Operation buttons: ON / OFF, timer mode start / stop, timer mode on / off, programme time, temperature setting, air flow direction (1), operating mode, fan speed control, filter sign reset (2), inspection (2)/ test indication (2) Display: Operating mode, battery change, set temperature, air flow direction (1), programmed time, fan speed, inspection / test operation (2) ARC466A1 1.Not applicable for FXDQ, FXSQ, FXNQ, FBDQ, FDXM, FBA 2. For FX** units only 3.For all features of the remote control, refer to the operation manual BRC4*/BRC7* 171 Individual control systems Multi-zone controller The multi-zoning system is a room-by-room controller. It is fitted with motorised dampers, which immediately adapt using Daikin ducted solutions. This system supports control of up to 8 zones connected to one indoor unit via a centralised thermostat located in the main room and individual thermostats for each of the zones. Zoning box: fully pre-assembled plenum with dampers Return air plenum to connect circular duct to Daikin indoor unit Supply air grille + plenum to connect to circular duct Return air grille + plenum to connect to circular duct Compatibility FDXM-F9 Number of motorised dampers 2 3 4 Standard Ceiling Void 5 6 7 8 Compact Ceiling Void 172 2 Reference AZEZ6DAIST07XS2 AZEZ6DAIST07S2 AZEZ6DAIST07XS3 AZEZ6DAIST07S3 Dimensions H x W x D (mm) 300 x 930 x 454 300 x 930 x 454 AZEZ6DAIST07M4 300 x 1,140 x 454 AZEZ6DAIST07M5 AZEZ6DAIST07L5 AZEZ6DAIST07M6 AZEZ6DAIST07L6 AZEZ6DAIST07L7 AZEZ6DAIST07XL7 AZEZ6DAIST07L8 AZEZ6DAIST07XL8 AZEZ6DAISL01S2 • • • • 300 x 1,638 x 454 • • • • • 515 x 1,425 x 454 • • • • • • 515 x 1,425 x 454 • • • 3 AZEZ6DAISL01S3 210 x 720 x 444 AZEZ6DAISL01M4 210 x 930 x 444 5 AZEZ6DAISL01L5 210 x 1,140 x 444 FXSQ-A • • • • • • • • 4 FXDQ-A3 • • • • 300 x 1,425 x 454 210 x 720 x 444 ADEA-A • • 300 x 930 x 454 AZEZ6DAIST07S4 FBA-A(9) 25 35 50 60 35 50 60 71 100 125 140 71 100 125 15 20 25 32 40 50 63 15 20 25 32 40 50 63 • • • • • • • • • • • • • • • 125 • • • 140 • • • • • • • • • • • • • • • • • • • • •• • • •• • • • • 71 80 100 • • Controls 3 controller versions are available to choose from: Colour, touch or simplified Blueface - main thermostat › Intuitive graphical, colour touch screen for controlling multiple zones AZCE6BLUEFACECB (Wired) Think - zone thermostat › Graphic touch button with low-energy e-ink screen for controlling single zones AZCE6THINKCB (Wired) AZCE6THINKRB (Wireless) Lite - zone thermostat › Simplified thermostat with touch buttons for temperature control AZCE6LITECB (Wired) AZCE6LITERB (Wireless) AZX6WSCLOUDDINC (Ethernet) AZX6WSCLOUDDINR (WiFi) ʯ Optional bus cable (2 x 0.5 mm² | 2 x 0.22 mm²), 10m length: AZX6CABLEBUS10, 100m length: AZX6CABLEBUS100 Webserver for remote control BACnet gateway › Cloud based remote control of multizoning kit(s) › Configruation and control of zones (temperature, operation mode, ...) › Access via webportal, or Android/IOS application › › › › AZX6BACNET Allows ON/OFF control of each zone Control of temperature for each zone Status indication of operation mode One gateway needed per system Grilles and plenums Supply air grilles and plenums Return air grilles and plenums Return air grille with integrated filter Wall type supply grille › With horizontal and vertical adjustable flaps › Filters particles from the air RDHV040015BKX RRFR050050BTX RLQV040015BKX PREJ0400150T Ceiling type supply grille Plenum for return grille › With horizontal flaps angled at 15° › Vertical flaps can be adjusted manually › To connect 1 up to 4 circular ducts to the return air grille › Diameter 250mm BR500 Plenum for supply grille Plenum for return air › To connect circular ducts to discharge grille › Insulated, galvanised steel › Diameter 250mm › To connect 1 up to 4 circular ducts to the Daikin concealed ceiling units › Diameter 250mm › Different sizes (XS, S, M, L, XL) to fit the indoor unit AZCEZDAPR07* 173 Centralised control systems Centralised remote controller Centralised control of the Sky Air and VRV system can be achieved via 3 user friendly compact remote controllers. These controls may be used independently or in combination with: 1 group = several (up to 16) indoor units in combination 1 zone = several groups in combination. A centralised remote control is ideal for use in tenanted commercial buildings subject to random occupation, enabling indoor units to be classified in groups per tenant (zoning). The schedule timer programmes the schedule and operation conditions for each tenant and the control can easily be reset according to varying requirements. DCS302C51 Centralised remote control Providing individual control of 64 groups (zones) of indoor units. › a maximum of 64 groups (128 indoor units, max. 10 outdoor units) can be controlled › a maximum of 128 groups (128 indoor units, max. 10 outdoor units) can be controlled via 2 centralised remote controls in separate locations › zone control › group control › malfunction code display › maximum wiring length of 1,000m (total: 2,000m) › air flow direction and air flow rate of HRV can be controlled › expanded timer function DST301B51 Schedule timer Enabling 64 groups to be programmed. › › › › a maximum of 128 indoor units can be controlled 8 types of weekly schedule a maximum of 48 hours back up power supply a maximum wiring length of 1,000m (total: 2,000m) DCS301B51 Unified ON/OFF control Providing simultaneous and individual control of 16 groups of indoor units. › › › › › 174 a maximum of 16 groups (128 indoor units) can be controlled 2 remote controls in separate locations can be used operating status indication (normal operation, alarm) centralised control indication maximum wiring length of 1,000m (total: 2,000m) Centralised control systems DCS601C51 Detailed & easy monitoring and operation of VRV systems (max. 64 indoor units groups). third party controller (domotics, BMS, etc.) via http interface Fire alarm Ethernet Forced OFF contact input DIII-NET Indoor units HRV DCS601C51 Languages › English › French › German › Italian › Spanish › Dutch › Portuguese System layout › Up to 64 indoor units can be controlled › Touch panel (full colour LCD via icon display) Control › Individual control (set point, start/stop, fan speed) (max. 64 groups/indoor units) › Set back shedule › Enhanced scheduling function (8 schedules, 17 patterns) › Flexible grouping in zones › Yearly schedule › Fire emergency stop control › Interlocking control › Increased HRV monitoring and control function › Automatic cooling / heating change-over › Heating optimization › Temperature limit › Password security: 3 levels (general, administration & service) › Quick selection and full control › Simple navigation Monitoring › Visualisation via Graphical User Interface (GUI) › Icon colour display change function › Indoor units operation mode › Indication filter replacement Cost performance › Free cooling function › Labour saving › Easy installation › Compact design: limited installation space › Overall energy saving Open interface › Communication to any third party controller (domotics, BMS, etc.) is possible via open interface (http option DCS007A51) Connectable to › VRV › HRV › Sky Air › Split (via interface adapter) 175 Centralised control systems Table t DCC601A51 Advanced • Intuitive and user-friendly interface • Flexible concept for stand alone centralised controller and multi site applications • Total solution thanks to integration of 3rd party equipment • Monitor & control your small commercial building, no matter where you are with Cloud connection 2 solutions: Cloud solution › Flexible online control from any device (Laptop, tablet...) › Monitor & control one or multiple sites › Benchmark the energy consumption of different installa- Local solution › Offline centralised control › Stylish optional screen fits any interior tions (1) › Energy consumption follow-up to comply System layout with local regulations Local solution Online control from any device Alarm Window contact Pulse input or AL-CCD07-VESA-1 Digital input Table t DCC601A51 WAGO power supply CPU module I/O module Split, , , ventilation, air curtains (1) For VRV and Sky Air R-32 ranges the consumption data is integrated; for other (HVAC) systems, field supplied kWh meters will be required 176 … Centralised control systems From one to ∞ sites Total solution LOCAL CONTROL › Total solution thanks to a large integration of Daikin products and 3rd party equipment › Connect a wide range of units (Split, Sky Air, VRV, Ventilation, Biddle air curtains) › Simply control your entire building centrally › Increased customer shopping experience by better management of your shop comfort level Daikin Cloud Services Installer/ technical manager Customer › Control your building no matter where you are › Monitor and control multiple sites › Installer or technical manager can remotely login to the cloud for first trouble- shooting › Benchmark the energy consumption of different installations (1) › Manage & track your energy use User friendly touch control NEW › Stylish Daikin supplied optional screen Clear dashboard overview for local control fits any interior › Intuitive and user-friendly interface › Full solution with simple control › Easy commissioning Flexible › Pulse/digital inputs for 3rd party equipment such as kWh meters, emergency input, window contact, … Energy management and consumption follow up › Modular concept allows your cloud to grow with your business › Control up to 32 indoor units per controller and 320 units per site (1) only available in combination with certain indoor units Pulse input Digital input Indoor uit Functions overview Languages System layout N° of connectable indoor units Local solution Cloud solution Depends on local device EN, DE, FR, NL, ES, IT, EL, PT, RU, TR, DA, SV, NO, FI, CS, HR, HU, PL, RO, SL, BG, SK 32 32 Multiple sites control Monitoring & control Basic control functions (ON/OFF, mode, filter sign, setpoint, fan speed, ventilation mode, room temperature, …) Remote control prohibition All devices ON/OFF Zone control Group control Weekly schedule Yearly schedule Interlock control Set point limitation Visualisation of energy use per operation mode Connectable to DX split, Sky Air, VRV Modular L Smart, VAM, VKM ventilation Air curtains For available Daikin Cloud Service options refer to the option list 177 Centralised control systems Mini BMS with full integration across all product pillars DCM601A51 • Price competitive mini BMS • Cross-pillar integration of Daikin products • Integration of third party equipment Download the WAGO selection tool from my.daikin.eu › Easy selection of WAGO materials › Material list creation › Time saving - Includes wiring schemes - Contains commissioning/preset data for iTM Check on https://www.youtube.com/ DaikinEurope 178 Centralised control systems System overview Web Access Internet Extranet LAN 3G HTTP interface To connect intelligent Touch Manager to the Daikin Cloud Service, the IoT gateway (EU. SB.5000072) and AC/DC converter (999175A) is needed. Full control of Daikin HVAC-R portfolio Integration of third party equipment DCM601A51 ITM plus adaptor line Max. 7 adapters Di/Pi line Fire alarm Max. 200m DCM601A52 Di/Pi port kWh meter Split WAGO interface I/O module Pump Sensor air handling units I/O module Fan air curtain, hydrobox, Analog/digital/pulse objects Lighting indoor units, Chillers and AHU protocol Fan coil units BACnet/IP Conveni-pack indoor units Direct plug & play connection! Multi state objects Elevator DALI Air handling unit Alarm Lighting Protocol Sensor 179 Centralised control systems User friendliness › Intuitive user interface › Visual lay out view and direct access to indoor unit main funtions › All functions direct accessible via touch screen or via web interface Smart energy management Split › Monitoring if energy use is according to plan › Helps to detect origins of energy waste › Powerful schedules guarantee correct operation throughout the year › Save energy by interlocking A/C operation with other equipment such as heating Plug & play Flexibility › Cross-pillar integration (heating, air conditioning, applied systems, refrigeration, air handling units) › BACnet protocol for 3rd party products integration › I/O for integration of equipment such as lights, Fan coils pumps… on WAGO modules › Modular concept for small to large applications › Control up to 512 indoor unit groups via one ITM Chillers and AHU and combine multiple ITM via web interface Easy servicing and commissioning Conveni-pack indoor units › Remote refrigerant containment check reducing on site visit HRV ventilation › Simplified troubleshooting › Save time on commissioning thanks to the pre-commissioning tool › Auto registration of indoor units DALI Lighting Protocol Sensor BACnet/IP protocol Lighting Air handling unit Pump Elevator Fan Alarm Flexibility in size 64 up to 512 groups Sensor Lighting Fan Pump Sensor WAGO I/O 180 Centralised control systems Functions overview Languages Management WAGO Interface Open http interface › English › Web access › Modular integration of › Communication to any third › French › Power Proportional 3rd party equipment party controller (domotics, › German › Italian › Spanish › Dutch › Portuguese Distribution (option) › Operational history (malfunctions, …) › Large variety of input and BMS, etc.) is possible via http outputs available. For more open interface (http option details refer to the options list DCM007A51) › Smart energy management - monitor if energy use is according to plan - detect origins of energy waste › Setback function › Sliding temperature System layout Control DALI integration › Up to 512 unit groups can be › Individual control › Control and monitor the lights - DX Split, Sky Air, VRV › Easier facility management: - HRV controlled (ITM + 7 iTM Plus adapters) (512 groups) › Schedule setting (Weekly receive error signal when schedule, yearly calender, light or light controller has seasonal schedule) a malfunction › Interlock control Connectable to - Chillers (via MT3-EKCMBACIP controller) › Flexible approach and less - Daikin AHU (via MT3- › Setpoint limitation wiring needed, compared EKCMBACIP controller) › Temperature limit to classic light scheme - Fan coils › Easier to make groups and control scenes › Connection between - Daikin Altherma Flex type - LT and HT hydroboxes - Biddle Air curtains intelligent Touch Manager - WAGO I/O and DALI through WAGO - BACnet/IP protocol BACnet / IP interface - Daikin PMS interface (option DCM010A51) 181 Standard protocol interfaces Modbus Interface RTD RTD-RA › Modbus interface for monitoring and control of residential indoor units RTD-NET › Modbus interface for monitoring and control of Sky Air, VRV, VAM and VKM RTD-10 › Advanced integration into BMS of Sky Air, VRV, VAM and VKM through either: - Modbus - Voltage (0-10V) - Resistance › Duty/standby function for server rooms RTD-20 › Advanced control of Sky Air, VRV, VAM/VKM and air curtains › Clone or independent zone control › Increased comfort with integration of CO2 sensor for fresh air volume control › Save on running costs via - pre/post and trade mode - set point limitation - overall shut down - PIR sensor for adaptive deadband RTD-HO › Modbus interface for monitoring and control of Sky Air, VRV, VAM and VKM › Intelligent hotel room controller RTD-W › Modbus interface for monitoring and control of Daikin Altherma Flex Type, VRV HT hydrobox and small inverter chiller 182 Overview functions Main functions RTD-RA Dimensions HxWxD mm Key card + window contact Set back function Prohibit or restrict remote control functions (setpoint limitation, ...) Modbus (RS485) Group control 0 - 10 V control Resistance control IT application Heating interlock Output signal (on/defrost, error) Retail application Partitioned room control Air curtain RTD-NET RTD-10 80 x 80 x 37,5 (1) RTD-20 100 x100 x 22 ** *** *** **** RTD-HO (1): By combining RTD-RA devices Control functions RTD-RA RTD-NET RTD-10 RTD-20 RTD-HO On/Off Set point Mode Fan Louver HRV Damper control Prohibit/Restrict functions Forced thermo off M,C M M M M M M M M M M M M,V,R M,V,R M,V,R M,V,R M,V,R M,V,R M,V,R M M M M M M M M* M* M* M* M* M* RTD-RA RTD-NET RTD-10 RTD-20 RTD-HO M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M Monitoring functions On/Off Set point Mode Fan Louver RC temperature RC mode N° of units Fault Fault code Return air temperature (Average /Min/Max) Filter alarm Termo on Defrost Coil In/Out temperature M M M M M Main functions Dimensions On/off prohibition Modbus RS485 Dry contact control Output signal (operation error) Space heating / cooling operation Domestic hot water control Smart Grid control RTD-W HxWxD mm 100x100x22 Control functions On/Off Space heating/cooling Set point leaving water temperature (heating / cooling) Room temperature setpoint Operation mode Domestic Hot water ON Domestic Hot Water reheat Domestic Hot Water reheat setpoint Domestic Hot Water storage Domestic Hot Water Booster setpoint Quiet mode Weather dependent setpoint enable Weather dependent curve shift Fault/pump info relay choice Control source prohibition M,C M,V M M M,C M M,C M M M Smart grid mode control Prohibit Space heating/cooling Prohibit DHW Prohibit Electric heaters Prohibit All operation PV available for storage Powerful boost Monitoring functions On/Off Space heating/cooling Set point leaving water temperature (H/C) Room temperature setpoint Operation mode Domestic Hot Water reheat Domestic Hot Water storage Number of units in the group Average leaving water temperature Remocon room temperature Fault Fault code Circulation pump operation Flow rate Solar pump operation Compressor status Desinfection operation Setback operation Defrost/ start up Hot start Booster Heater operation 3-Way valve status Pump running hours accumulated Compressor running hours accumulated Actual leaving water temperature Actual return water temperature Actual DHW tank temperature (*) Actual refrigerant temperature Actual outdoor temperature M,C M M M M M M M M M,C M M M M M M M M M M M M : Modbus / R : Resistance / V : Voltage / C: control * : only when room is occupied / ** : setpoint limitation / (*) if available *** : no fan speed control on the CYV air curtain / **** : run & fault 183 Standard protocol interfaces DIII-net Modbus interface EKMBDXA Integrated control system for seamless connection between Split, Sky Air, VRV and small inverter chillers and BMS systems › › › › Communication via Modbus RS485 protocol Detailed monitoring and control of the VRV total solution Easy and fast installation via DIII-net protocol As the Daikin DIII-net protocol is being used, only one modbus interface is needed for a group of Daikin systems (up to 10 outdoor units systems). VRV network DIII- NET EKMBDXA VRV Outdoor unit Biddle air curtain HRV *via EKEQ box up to 64 units connectable per interface Sky Air network* Split network* KRP928BB2S Small inverter chiller network Building control network Security Fire alarm Power supply facility Lighting Pump * Additional centralized controller might be required. For more information contact your local dealer. Maximum number of connectable indoor units Maximum number of connectable outdoor units Communication DIII-NET - Remark Protocol - Remark Protocol - Type Protocol - Max. Wiring length Dimensions HeightxWidthxDepth Weight Ambient temperature - operation Max. Installation Power supply 184 Min. Frequency Voltage m mm kg °C °C Hz V EKMBDXA7V1 64 10 DIII-NET (F1F2) 2 wire; communication speed: 9600 bps or 19200 bps RS485 (modbus) 500 124x379x87 2.1 60 0 Indoor installation 50 220-240 Elevator Standard protocol interfaces KNX interface KLIC-DD(3) KLIC-DI Integration of Split, Sky Air and VRV in HA/BMS systems Connect split indoor units to KNX interface for Home Automation system Concept light house Domotica shutter control Controller Interface Daikin protocol/ KNX tv Connect Sky Air / VRV indoor units to KNX interface for BMS integration light Concept shop shutter control Domotica tv Controller Interface Daikin protocol/ KNX KNX interface line-up The integration of Daikin indoor units through the KNX interface allows monitoring and control of several devices, such as lights and shutters, from one central controller. One particularly important feature is the ability to programme a ‘scene’ - such as “Home leave” - in which the end-user selects a range of commands to be executed simultaneously once the scenario is selected. For instance in “Home leave” , the air conditioner is off, the lights are turned off, the shutters are closed and the alarm is on. KNX interface for KLIC-DD (3) Size 45x45x15mm Split Basic control On/Off Mode Temperature Fan speed levels Swing Advanced functionalities Error management Scenes Auto switch off Temperature limitation Initial configuration Master and slave configuration • Sky Air KLIC-DI Size 90x60x35mm VRV • • Auto, heat, dry, fan, cool Auto, heat, dry, fan, cool Auto, heat, dry, fan, cool 3 or 5 + auto Stop or movement 2 or 3 Stop or movement 2 or 3 Swing or fixed positions (5) • • • • • • Communication errors, Daikin unit errors • • • • • • • • • • • 185 Standard protocol interfaces Features PMS Interface • DCM010A51 • Hotel interface connecting Daikin HVAC with Oracle • • • • • User-friendly interface for easy front desk support in hotels, conference centers, … Compatible with Oracle Opera PMS (formerly known as Micros Fidelio) Automated push of indoor unit settings based on the Opera PMS Check-In and Check-Out commands Energy saving thanks to the possibility to limit temperature setpoint Up to 5 customized operation profiles based on weather conditions Available in 23 languages Up to 2,500 units / rooms can be managed Property Management Systems Hotel case example: › On check-in the HVAC for the room is automatically switched on › On check-out the HVAC for the room is automatically switched off. › Increased hotel customer experience by pre-heating / cooling of booked rooms Hotel front desk Check-in Check-out Room 305 OFF Room view showing room status: check-in, check-out, pre-heating / cooling status, room temperature and A/C status Multiple room types (bedroom, meeting room, …) can be defined with customized A/C settings for each type HVAC settings can be easily observed and changed by the reception desk Room 712 Leaving Arriving Check-Out room 305 Check-In room 712 ON Simplified configuration of Daikin PMS interface Hotel front desk Daikin HVAC network LAN P1 P2 VRV outdoor unit F1 F2 IFC8 VRV indoor units with individual control connector on Oracle Server Split or Sky Air indoor units with individual control PMS Interface on interface PC DCM601A51 with web interface (DCM007A51) Split or Sky Air outdoor unit 186 Standard protocol interfaces BACnet Interface DMS502A51 / EKACBACMSTP / EKCMBACIP / EKCMBACMSTP Integrated control system for seamless connection between VRV, applied systems, air handling units and BMS systems BMS › Interface for BMS system › Communication via BACnet protocol (connection via Ethernet) › Unlimited site size › Easy and fast installation › PPD data is available on BMS system (only for VRV) VRV network BACNET / ETHERNET DIII- NET DMS502A51 Central Controller VRV Outdoor unit HRV up to 256 units connectable per interface Remote Control Applied systems network iCM Intelligent Chiller Manager MicroTech III EKCMBACIP EKCM200J EKCM200J EKCM200J Air handling unit network EKCMBACIP EKCMBACMSTP Fire alarm Security Pump Lighting Power supply facility Building control network Elevator 187 Standard protocol interfaces LonWorks Interface DMS504B51 Open network integration of VRV monitoring and control functions into LonWorks networks LON BMS VRV network LonTalk DIII- NET adapter ETHERNET (TCP/IP) › Interface for Lon connection to LonWorks networks › Communication via Lon protocol (twisted pair wire) › Unlimited sitesize › Quick and easy installation DMS504B51 Central Control VRV Outdoor unit HRV up to 64 units connectable per interface Remote Control adapter LonTalk LonPoint LonPoint Security Fire alarm Building control network System 188 Daikin configurator software Daikin Configurator Tool + Software EKPCCAB4 Simplified commissioning: graphical interface to configure, commission and upload system settings Simplified commissioning The Daikin configurator for Daikin Altherma and VRV is an advanced software solution that allows for easy system configuration and commissioning: › Less time is required on the roof configuring the outdoor unit › Multiple systems at different sites can be managed in exactly the same way, thus offering simplified commissioning for key accounts › Initial settings on the outdoor unit can be easily retrieved Simplified Retrieve initial commissioning system settings 189 Daikin Cloud Service Daikin Cloud Service to achieve optimal operation Daikin Cloud Service is a cloud-based remote control and monitoring solution for DX systems. Using enhanced control, monitoring and predictive logic, Daikin Cloud Service provides real-time data and support from Daikin experts to help you identify cost-saving opportunities, increase the lifetime of your equipment and reduce the risk of unexpected issues. Monitor & control* your system no matter where you are while teaming up with Daikin experts Remote control and energy visualisation Multi-site monitoring From one to an ∞ number of sites Puts you in the driving seat of your energy management LOCAL CONTROL Control and monitor your premises, wherever you are Centralised control and monitoring of all your premises Check errors remotely without having to go on site Visualise energy consumption and reduce energy waste by comparing different premises Remote support and diagnostics Owner Installer/ technical manager Daikin specialist supervision, so you can focus on your core business Early warning of system deviations to maximise system uptime and avoid emergency repairs** Service providers have access to operational data so they arrive on site prepared Remote expert assistance in case of errors 24/7 Advice and optimisation Get the best out of your system through expert advice Periodical analysis and optimisation report by experts Personalised actions to maximise energy efficiency and comfort Increased system lifetime as the system runs as it should Daikin Cloud Service requires a subscription. Contact your local sales representative for more information. * Remote Control function via Daikin Cloud Service only available for sites with an Intelligent Tablet controller ** Only available for VRV systems 190 Daikin Cloud Service Daikin Cloud Service packages Remote control, scheduling and interlocking Energy monitoring Multi-site benchmark Alarm history and e-mail notifications Predictions and e-mail notifications ** ** Control and monitoring Remote support and diagnostics Advice and optimisation (DCC601A51 only) (DCC601A51 only) (DCC601A51 only) ✗ ✗ Operational data access ✗ Indoor use analysis ✗ Outdoor use analysis ✗ Remote diagnostic and support from Daikin ✗ Periodical analysis and optimisation advice from Daikin ✗ ✗ Can be combined with maintenance programmes: - Technical inspection - Preventive Maintenance Plan - Comprehensive Maintenance Plan ✗ ✗ Packages subject to local availability Daikin Cloud Service replaces VRV Cloud and i-Net services. Flexible solution Manage your premises according to your needs, using a local control or remotely via Daikin Cloud Service, or a combination of both. Control*, no matter where you are Daikin Cloud Service gives you full control of one or more premises wherever you are, using your PC, tablet or smartphone. Predictive logic for VRV to prevent breakdowns The operational data is continuously analysed by Daikin algorithms to predict potential failures and avoid unexpected costs. Compatible with: › Intelligent Tablet Controller (DCC601A51) › Intelligent Touch Manager (DCM601A51) + IoT gateway › LC8 + IoT gateway 1. Clear dashboard overview 2. Monitor and control your system 4. Energy management and consumption follow up 5. Multi site management 3. Easy setting of schedules * Remote Control function via Daikin Cloud Service only available for sites with an Intelligent Tablet controller ** Only available for VRV systems 191 Other devices Wireless room temperature sensor K.RSS Flexible and easy installation › Accurate temperature measurement thanks to flexible placement of the sensor › No need for wiring › No need to drill holes › Ideal for refurbishment Connection diagram Daikin indoor unit PCB (FXSQ example) Power supply – X35, X13 Air sensor – X16A, X19 RF receiver RF sensor (transmitter) Specifications Dimensions Weight Power supply Battery life Battery type Maximum range Operation range Communication mm g m °C Type Frequency MHz Wireless room temperature sensor kit (K.RSS) Wireless room temperature receiver Wireless room temperature sensor 50 x 50 ø 75 40 60 16VDC, max. 20 mA N/A N/A +/- 3 years N/A 3 Volt Lithium battery 10 0~50 RF 868.3 › Room temperature is sent to the indoor unit every 90 seconds or if the temperature difference is 0.2°C or larger. Wired room temperature sensor KRCS* › Accurate temperature measurement, thanks to flexible placement of the sensor › specifc model code for each indoor unit can be found in the option tables Specifications Dimensions (HxW) Weight Length of branch wiring 192 mm g m 60 x 50 300 12 Other devices Adapter PCBs Simple solutions for unique requirements Concept and benefits › Low cost option to satisfy simple control requirements › Deployed on single or multiple units Connectable to: Split (E)KRP1B* adapter for wiring KRP2A*/KRP4A* Wiring adapter for electrical appendices KRP58M3 SB.KRP58M51 KRP58M51 Sky Air VRV • Facilitates integration of auxiliary heating apparatus, humidifiers, fans, damper • Powered by and installed at the indoor unit • • • • • Remotely start and stop up to 16 indoor units (1 group) (KRP4A* via P1 P2) Remotely start and stop up to 128 indoor units (64 groups) (KRP2A* via F1 F2) Alarm indication/ fire shut down Remote temperature setpoint adjustment Cannot be used in combination with a central controller • Low noise and demand control option for RZQ200/250C • Low noise and demand control option for RZQG and RZQSG single phase • Includes mounting plate EKMKSA1 • Low noise and demand control option for RZQG1 and RZQSG 3 phase DTA104A* Outdoor Unit External Control Adapter • Individual or simultaneous control of VRV system operating mode • Demand control of individual or multiple systems • Low noise option for individual or multiple systems DCS302A52-9 Unification adapter for computerized control • • • • Enables unified display (operation/malfunction) and unified control (ON/OFF) from BMS system Must be used together with Intelligent Touch Controller or intelligent Touch Manager Cannot be combined with KRP2/4* Can be used for all VRV indoor models KRP928* Interface adapter for DIII-net • Allows integration of split units to Daikin central controls KRP413* Wiring adapter normal open contact / normal open pulse contact • • • • • KRP980* Adapter for split units without an S21 port • Connect a wired remote control • Connect to Daikin central controls • Allow external contact Switch off auto restart after power failure Indication of operation mode / error Remotely start /stop Remotely change operation mode Remotely change fan speed Some adapters require an installation box, refer to the option lists for more information Accessories EKRORO • External ON/OFF or forced off • Example: door or window contact EKRORO 3 • External ON/OFF or forced off • F1/F2 contact • Example: door or window contact KRC19-26A • Mechanical cool/heat selector • Allows switching over an entire system between cooling/heating/fan only • Connects to the A/B/C terminals of the unit BRP2A81 • Cool/heat selector PCB • Required to connect KRC19-26A to a VRV IV outdoor unit 193 Options & Accessories AUTO-CLEANING PANEL FILTERS INTELLIGENT SENSORS 194 Options & accessories Options & accessories 195 VRV outdoor 196 VRV indoor 200 Indoor & Hot Water 202 Ventilation 204 Control Systems 206 195 Options & accessories - outdoor VRV S-series VRV IV Heat Recovery RXYSA-AV1/AY1 REYQ 8~12 REYQ 14~20 REMQ5 Multi-module connection kit (obligatory) - Connects multiple modules into a single refrigerant system Kits Extended level difference kit - Allows outdoor unit to be more than 50m above indoor units Adapters 3-module systems BHFQ23P907 BHFQ23P1357 1 kit per system 1 kit per system Special order unit Central drain pan kit - Installs onto the underside of the outdoor unit and collects drain water from all bottom plate outlets into a single outlet. In cold areas should be heated by a field-supplied heater to prevent drain water from freezing in the drain pan. Heater tape kit - Optional electrical heater to guarantee trouble-free operation in extremely cold and humid climates (one per outdoor unit needed) BHGP26A1 Digital pressure gauge kit – displays current condensing and evaporating pressures in the system as Standard, or expansion valve positions and temperature sensor data in a special service mode. Connect to the outdoor unit PCB, for installation in the outdoor unit. External control adapter for outdoor unit - Allows to activate Low Noise Operation and three levels of demand control, limiting power consumption via external dry contacts. Connects to the F1/F2 communication line and requires power supply from an indoor unit, BSVQ box, or VRV-WIII outdoor unit. KRC19-26A Mechanical cool/heat selector – allows to switch an entire Heat Pump system, or one BS-box of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C terminals of the outdoor unit / BS-box. Cool/heat selector PCB (required to connect KRC19-26A) Others 2-module systems KKSA26A560* Cool/heat selector PCB mounting plate (only required when cool/heat selector PCB and Heater tape kit are combined) KJB111A Installation box for remote cool/heat selector KRC19-26A EKCHSC - Cool/heat selector cable EKPCCAB4 VRV configurator KKSB26B1* Demand PCB mounting plate. Needed to mount Demand PCB for one or more outdoor units. DTA109A51 DIII-net expander adapter BPMKS967A2/A3 Branch provider (for connection of 2/3 RA indoor units) EKDK04 Drain plug kit EKBPH250D EKBPH012T7A EKBPH020T7A EKBPH012T7A • • • DTA104A53/61/62 For installation into an indoor unit: exact adapter type depends on type of indoor unit. For 14-20 HP the demand PCB mouting plate is required. See Options & Accessories of indoor units • Standard on unit • • • • • • • • • • • • VRV IV S-series RXYSCQ-TV1 RXYSQ4-6TV9 RXYSQ4-6TY9 Multi-module connection kit (obligatory) - Connects multiple modules into a single refrigerant system Kits Extended level difference kit - Allows outdoor unit to be more than 50m above indoor units Central drain pan kit - Installs onto the underside of the outdoor unit and collects drain water from all bottom plate outlets into a single outlet. In cold areas should be heated by a field-supplied heater to prevent drain water from freezing in the drain pan. Heater tape kit - Optional electrical heater to guarantee trouble-free operation in extremely cold and humid climates (one per outdoor unit needed) Adapters BHGP26A1 Digital pressure gauge kit – displays current condensing and evaporating pressures in the system as Standard, or expansion valve positions and temperature sensor data in a special service mode. Connect to the outdoor unit PCB, for installation in the outdoor unit. External control adapter for outdoor unit - Allows to activate Low Noise Operation and three levels of demand control, limiting power consumption via external dry contacts. Connects to the F1/F2 communication line and requires power supply from an indoor unit, BSVQ box, or VRV-WIII outdoor unit. DTA104A53/61/62 For installation into an indoor unit: exact adapter type depends on type of indoor unit. See Options & Accessories of indoor units KRC19-26A Mechanical cool/heat selector – allows to switch an entire Heat Pump system, or one BS-box of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C terminals of the outdoor unit / BS-box. • Cool/heat selector PCB (Required to connect KRC19-26A) • EBRP2B KKSA26A560* Cool/heat selector PCB mounting plate (only required when cool/heat selector PCB and Heater tape kit are combined) KJB111A Installation box for remote cool/heat selector KRC19-26A • EKCHSC - Cool/heat selector cable (Required to connect KRC19-26A) Others EKPCCAB4 VRV configurator • • • • • • • • • • KKSB26B1* Demand PCB mounting plate. Needed to mount Demand PCB for one or more outdoor units. DTA109A51 DIII-net expander adapter BPMKS967A2/A3 Branch provider (for connection of 2/3 RA indoor units) EKDK04 Drain plug kit 196 VRV IV with continuous heating RYYQ8-12 RYYQ14-20 RYMQ8-12 VRV IV without continuous heating 2-module systems RYMQ14-20 3-module systems RXYQ8-12 RXYQ14-20 BHFQ22P1007 BHFQ22P1517 EKBPH012T7A EKBPH020T7A EKBPH012T7A EKBPH020T7A • • • • VRV IV C+series 2-module systems 3-module systems BHFQ22P1007 BHFQ22P1517 1 kit per system 1 kit per system RXYLQ RXMLQ 2-module systems 3-module systems BHFQ22P1007 BHFQ22P1517 1 kit per system 1 kit per system EKBPH012T7A EKBPH020T7A 1 kit per system 1 kit per system • • DTA104A53/61/62 For installation into an indoor unit: exact adapter type depends on type of indoor unit. For 14-20 HP the demand PCB mouting plate is required. See Options & Accessories of indoor units • • • • BRP2A81 BRP2A81 BRP2A81 BRP2A81 • 1 kit per system 1 kit per system BRP2A81 BRP2A81 (1 kit per system) (1 kit per system) • 1 kit per system 1 kit per system • • BRP2A81 BRP2A81 1 kit per system 1 kit per system BRP2A81 BRP2A81 (1 kit per system) (1 kit per system) • 1 kit per system 1 kit per system • • BRP2A81 BRP2A81 BRP2A81 BRP2A81 (1 kit per system) (1 kit per system) • • • • 1 kit per system 1 kit per system • • 1 kit per system 1 kit per system • • 1 kit per system 1 kit per system • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • VRV IV i-series SB.RKXYQ RXYSQ8-12TY1 RDXYQ5 RDXYQ8 EKDPH1RDX EKDPH1RDX RKXYQ5 RKXYQ8 DTA104A53/61/62 For installation into an indoor unit: exact adapter type depends on type of indoor unit. See Options & Accessories of indoor units • • BRP2A81 • • • • • • 197 Options & accessories - outdoor VRV IV-Q Heat Pump Replacement VRV RQYQ 140P RXYQQ8-12 RXYQQ14-20 2-module systems 3-module systems BHFQ22P1007 BHFQ22P1517 1 kit per system 1 kit per system Multi-module connection kit (obligatory) Connects multiple modules into a single refrigerant system Kits Central drain pan kit - Installs onto the underside of the outdoor unit and collects drain water from all bottom plate outlets into a single outlet. In cold areas should be heated by a field-supplied heater to prevent drain water from freezing in the drain pan. Heater tape kit - Optional electrical heater to guarantee trouble-free operation in extremely cold and humid climates (one per outdoor unit needed) BHGP26A1 Digital pressure gauge kit – displays current condensing and evaporating pressures in the system as Standard, or expansion valve positions and temperature sensor data in a special service mode. Connect to the outdoor unit PCB, for installation in the outdoor unit. External control adapter for outdoor unit - Allows to activate Low Noise Operation and three levels of demand control, limiting power consumption via external dry contacts. Connects to the F1/F2 communication line and requires power supply from an indoor unit*, BSVQ box, or VRV-WIII outdoor unit. Adapters KWC26B160 KRC19-26A Mechanical cool/heat selector – allows to switch an entire Heat Pump system, or one BS-box of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C terminals of the outdoor unit / BS-box. • EKBPH012T7A EKBPH020T7A • • DTA104A53/61/62 For installation into an indoor unit: exact adapter type depends DTA104A53/61/62 on type of indoor unit. For installation into an indoor unit: exact adapter type depends on type of indoor unit. For 14-20 HP the For 14-20 HP the demand PCB mouting plate is required. See Options & Accessories of indoor units demand PCB mouting plate is required. See Options & Accessories of indoor units • BRP2A81 Cool/heat selector PCB (required to connect KRC19-26A to VRV IV outdoor) • • 1 kit per system 1 kit per system • • 1 kit per system 1 kit per system • 1 kit per system 1 kit per system • • 1 kit per system 1 kit per system • • • • • • KKSA26A560* - Cool/heat selector PCB mounting plate (only required when cool/heat selector PCB and Heater tape kit are combined) Others KJB111A Installation box for remote cool/heat selector KRC19-26A • EKPCCAB4 VRV configurator KKSB2B61* Demand PCB mounting plate. Needed to mount Demand PCB for one or more outdoor units. DTA109A51 DIII-net expander adapter • • Refnets & branch selector boxes Refnets • Refnet Joints Capacity index 200 ≤ x < 290 Capacity index 290 ≤ x < 640 Capacity index > 640 Capacity index < 290 Capacity index 290 ≤ x < 640 KHRQM22M20T KHRQM22M29T KHRQM22M64T KHRQM22M75T KHRQM22M29H KHRQM22M64H Imperial-size connections for heat recovery pump (2-pipe) KHRQ22M20T KHRQ22M29T9 KHRQ22M64T KHRQ22M75T KHRQ22M29H KHRQ22M64H Metric-size connections for heat recovery systems (3-pipe) KHRQM23M20T KHRQM23M29T KHRQM23M64T KHRQM23M75T KHRQM23M29H KHRQM23M64H KHRQ23M20T KHRQ23M29T9 KHRQ23M64T KHRQ23M75T KHRQ23M29H KHRQ23M64H Imperial-size connections for heat recovery systems (3-pipe) EKBSVQLNP Sound reduction kit (sound insulation) KHFP26A100C Closed pipe kit KHRP26A1250C Joint kit Quiet kit (1) For installations with special requirements towards fire regulations, the insulation material can be replaced using kits EKHBFQ1 and EKHBFQ2. The kits contain insulation material that complies with EN13501-1:B-S3,dO and BS476-7 (class 1) 198 Refnet Headers Capacity index < 200 Metric-size connections for heat pump systems (2-pipe) Options for Branch selector boxes (BS box) (only for connection with VRV heat recovery system) • VRV-W IV Water-cooled VRV VRV III-Q Heat Recovery Replacement VRV Heat Pump application RQEQ 140~212 • 2-module systems 3-module systems 4-module systems BHFP26P36C BHFP26P63C BHFP26P84C 1 kit per system 1 kit per system 1 kit per system RWEYQ8-14 Heat Recovery application 2-module systems 3-module systems 2-module systems 3-module systems BHFQ22P1007 / BHFQ22P1517 (1) BHFQ22P1517 (1) BHFQ23P907 / BHFQ23P1357 (1) BHFQ23P1357 (1) DTA104A53/61/62 Installation in the RWEYQ outdoor unit possible. For installation in indoor units, use appropriate type (DTA104A53/61/62) for particular indoor unit. See Options & Accessories of indoor units • (for H/P only) 1 kit per system 1 kit per system • (for H/P only) 1 kit per system 1 kit per system • (for H/P only) 1 kit per system 1 kit per system • • • • • • • • • • • • • • • • • • Heat Recovery Branch Selector Boxes (BS-Boxes) Capacity index > 640 1-port BS1Q-A 4-port BS4Q14AV1B 6-port BS6Q14AV1B 8-port BS8Q14AV1B 10-port BS10Q14AV1B 12-port BS12Q14AV1B 16-port BS16Q14AV1B • • • • • • • • • • • • KDDN26A4 KDDN26A8 KDDN26A8 KDDN26A12 KDDN26A12 KDDN26A16 KHRQM22M75H KHRQ22M75H KHRQM23M75H KHRQ23M75H • 199 Options & accessories - indoor FXFA-A / FXFQ-B FXZA-A / FXZQ-A FXCQ 20~40A FXCQ 50~63A FXCQ 80 ~125A BYFQ60CW (white panel) BYFQ60CS (grey panel) BYFQ60B3 (Standard panel) BYBCQ40H BYBCQ63H BYBCQ125H KDBHQ56B140 (7) BDBHQ44C60 (white & grey panel) Sensor kit BRYQ140B (white panels) BRYQ140BB (black panels) BRYQ140C (white designer panel) BRYQ140CB (black designer panel) BRYQ60AW (white panel) BRYQ60AS (grey panel) Infrared remote control (incl. receiver) BRC7FA532F (white panels) BRC7FA532FB (black panels) BRC7FB532F (white designer panel) BRC7FB532FB (black designer panel) BRC7F530W (9) (10) (white panel) BRC7F530S (9) (10) (grey panel) BRC7EB530 (9) (10) (standard panel) BRC7C52 BRC7C52 BRC7C52 Madoka BRC1H519W7 (White) / BRC1H519S7 (Silver) / BRC1H519K7 (Black) User-friendly wired remote controller with premium design R-410A model: BRC1H519W7/S7/K7 R-32 model: BRC1H52W/S/K R-410A model: BRC1H519W7/S7/K7 R-32 model: BRC1H52W/S/K • • • BRC1E53A/B/C - Wired remote control with full-text interface and back-light •(18) •(18) •(18) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • DCS601C51 (12) - intelligent Touch Controller DCS302C51 (12) - Central remote controller DCS301B51 (12) (13) - Unified ON/OFF controller Panels Individual control systems for individual control DST301B51 (12) - Schedule timer RTD-NET - Modbus interface for monitoring and control for central control Centralised control systems DCC601A51 - intelligent Tablet Controller DCM601A51 - intelligent Touch Manager RTD-10 - Modbus interface for infrastructure cooling RTD-20 - Modbus interface for retail RTD-HO - Modbus interface for hotel KLIC-DI - KNX Interface EKMBDXA - Modbus interface DCM010A51 - Daikin PMS interface DMS502A51 - BACnet Interface DMS504B51 - LonWorks Interface Wiring and sensors Filters Replacement long life filter, non-woven type Auto cleaning filter KRCS - External wired temperature sensor •(15)(18) • • • • • • • • • • • • • • • KAFP551K160 KAFQ441BA60 KAFP531B50 KAFP531B80 KAFP531B160 see decoration panel KRCS01-7B KRCS01-4 KRCS01-4 KRCS01-4 KRCS01-4 SB.K.RSS_RFC (EKEWTSC-1 + K.RSS) • • • • Adapter with 2 output signals (Compressor / Error, Fan output) KRP1BA58 (2)(7) KRP1B57 Adapter with 4 output signals (Compressor / Error, Fan, Aux. heater, Humidifier output) EKRP1C12 (2)(7) EKRP1B2 EKRP1B2 EKRP1B2 EKRP1B2 Adapter for centralised external monitoring/control via dry contacts and setpoint control via 0-140Ω KRP4A53 (2)(7) KRP4A53 (2) KRP4A51 (2) KRP4A51 (2) KRP4A51 (2) K.RSS - External wireless temperature sensor Adapter for external central monitoring/control (controls 1 entire system) Adapter for keycard and/or window contact connection (2)(11) Adapter for multi-tenant applications (24VAC PCB power supply interface) KRP2A52 KRP2A51 (2) KRP2A51 (2) KRP2A51 (2) BRP7A53 BRP7A53 BRP7A51 BRP7A51 BRP7A51 DTA114A61 DTA114A61 DTA104A61 DTA104A61 DTA104A61 KRP1H98A (7) KRP1BB101 KRP1C96 (16) (17) KRP1C96 (16) (17) KRP1C96 (16) (17) Wiring kit for Remote ON/OFF or Forced OFF Standard Standard Standard Standard Standard Drain pump kit Standard Standard Standard Standard Standard KDDP55C160-1 + KDDP55D160-2 (7)(8) KDDQ44XA60 KDDFP53B50 KDDFP53B80 KDDFP53B160 External control adapter for outdoor unit (installation on indoor unit) Installation box / Mounting plate for adapter PCBs (For units where there is no space in the switchbox) Others 2-way blow KDBQ44B60 (Standard panel) Panel spacer for reducing required installation height BRC1D52 (4) - Standard wired remote control with weekly timer Building Management System & Standard protocol interfaces 4-way (600x600) Standard panels: BYCQ140E (white) / BYCQ140EW (full white)(3) / BYCQ140EB (black) Decoration panel Auto cleaning (5)(6): BYCQ140EGF (obligatory for cassette units, optional for others, rear panel for FXLQ) (white) / BYCQ140EGFB (black) Designer panels: BYCQ140EP (white) / BYCQ140EPB (black) Sealing kit for 3- or 2-directional air discharge Adapters Ceiling mounted cassette units Round flow (800x800) Multi zoning kit (for detailed model code overview refer to multizoning argue card in this catalogue) Fresh air intake kit (direct installation type) Air discharge adapter for round duct Filter chamber for bottom suction 200 (1) pump station is necessary for this option (2) Installation box is necessary for these adapters (3) The BYCQ140EW has white insulation. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140EW decoration panel in environments exposed to concentrations of dirt" (4) Not recommended because of the limitation of the functions (5) To be able to control the BYCQ140EGF(B) the controller BRC1E or BRC1H* is needed (6) The BYCQ140EGF(B) is not compatible with Multi and Split Non-Inverter Outdoor units (7) Option not available in combination with BYCQ140EGF(B) (8) Both parts of the fresh air intake are needed for each unit Concealed ceiling units (duct units) Corner (1-way blow) Slim FXKQ 25~40MA FXKQ 63MA BYK45F BYK71F BRC4C61 BRC4C61 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Medium ESP FXDA-A / FXDQ-A3 FXSA15-32A / FXSQ15-32A FXSA40-50A / FXSQ40-50A FXSA63-80A / FXSQ63-80A FXSA100-125A / FXSQ100-125A FXSA140A / FXSQ140A BRC4C65 BRC4C65 BRC4C65 BRC4C65 BRC4C65 BRC4C65 R-410A model: R-410A model: R-410A model: R-410A model: R-410A model: R-410A model: BRC1H519W7/S7/K7 BRC1H519W7/S7/K7 BRC1H519W7/S7/K7 BRC1H519W7/S7/K7 BRC1H519W7/S7/K7 BRC1H519W7/S7/K7 R-32 model: BRC1H52W/S/K R-32 model: BRC1H52W/S/K R-32 model: BRC1H52W/S/K R-32 model: BRC1H52W/S/K R-32 model: BRC1H52W/S/K R-32 model: BRC1H52W/S/K •(18) •(18) • • • • • • • • • • • • • • • •(18) •(18) • • • • • • • • • • • • • • • •(18) •(18) • • • • • • • • • • • • • • • •(18) •(18) • • • • • • • • • • • • • • • •(18) •(18) • • • • • • • • • • • • • • • •(18) •(18) • • • • • • • • • • • • • • • 15-32: BAE20A62 40-50: BAE20A82 63: BAE20A102 KRCS01-1 KRCS01-1 KRCS01-4 KRCS01-4 KRCS01-4 KRCS01-4 KRCS01-4 KRCS01-4 • • • • • • • • KRP1B61 KRP1B61 KRP1B56 EKRP1B2(2) EKRP1B2(2) EKRP1B2(2) EKRP1B2(2) EKRP1B2(2) KRP4A51 KRP4A51 KRP4A54-9 KRP4A52(2) KRP4A52(2) KRP4A52(2) KRP4A52(2) KRP4A52(2) KRP2A51 KRP2A51 KRP2A53 KRP2A51(2) KRP2A51(2) KRP2A51(2) KRP2A51(2) KRP2A51(2) BRP7A51 BRP7A51 BRP7A54 BRP7A51 BRP7A51 BRP7A51 BRP7A51 BRP7A51 DTA114A61 DTA114A61 DTA114A61 DTA114A61 DTA114A61 DTA114A61 DTA104A61 DTA104A61 Standard Standard Standard Standard DTA104A53 DTA104A61 DTA104A61 DTA104A61 DTA104A61 DTA104A61 KRP1BB101 KRP1BB101/ KRP1B100 KRP1BB101/ KRP1B100 KRP1BB101/ KRP1B100 KRP1BB101/ KRP1B100 KRP1BB101/ KRP1B100 Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard • (R-410A only) • (R-410A only) KDAP25A36A (9) Cannot be combined with sensor kit (10) Independently controllable flaps function not available (11) Only possible in combination with BRC1H* / BRC1E* (12) When fixing box is required, use KJB212A, KJB311A or KJB411A depending on the size of the controller (13) Option KEK26-1A (Noise filter) is required when installing DCS301B51 • (R-410A only) KDAP25A56A • (R-410A only) KDAP25A71A • (R-410A only) Standard • (R-410A only) KDAP25A140A (14) Wire harnass EKEWTSC is necessary (15) The active airflow circulation function is not available for this controller. (16) Up to 2 adaptor PCBs can be installed per installation box (17) Only one installation box can be installed per indoor unit (18) VRV R-32 indoor units cannot be connected to this controller 201 Options & accessories - indoor & hot water Panels Concealed ceiling units (duct units) High ESP High ESP FXMQ 50~80 FXMQ 100~125 FXMQ 200~250 FXHQ 32A Ceiling suspended units 1-way blow FXHQ 63A FXHQ 71~100A Decoration panel (obligatory for cassette units, optional for others, rear panel for FXLQ) Panel spacer for reducing required installation height Sealing kit for 3- or 2-directional air discharge Sensor kit Individual control systems Centralised control systems DCC601A51 - Intelligent Tablet Controller DCM601A51 - Intelligent Touch Manager Wiring and sensors Filters Madoka BRC1H519W(7) (White) / BRC1H519S(7) (Silver) / BRC1H519K(7) (Black) User-friendly wired remote controller with premium design Building management system + standard protocol interface Infrared remote control including receiver BRC1E53A/B/C - Wired remote control with full-text interface and back-light BRC1D52 (4) - Standard wired remote control with weekly timer DCS601C51 (12) - intelligent Touch Controller DCS302C51 (12) - Central remote control DCS301B51 (12) (13) - Unified ON/OFF control DST301B51 (12) - Schedule timer EKMBDXA - DIII-net modbus interface KLIC-DI - KNX interface DMS502A51 - BACnet interface DMS504B51 - LowWorks interface Replacement long life filter, non-woven type BRC4C65 BRC4C65 BRC4C65 BRC7GA53-9 BRC7GA53-9 BRC7GA53-9 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • KRCS01-4 • KAF372M280 (18) KAFP501A56 KAFP501A80 KAFP501A160 KRCS01-4 KRCS01-1 KRCS01-4 KRCS01-4 KRCS01-4 • • • • • KRP1B54 KRP1B54 KRP1B54 Auto cleaning filter KRCS - External wired temperature sensor K.RSS - External wireless temperature sensor Others Adapters Adapter with 2 output signals (Compressor / Error, Fan output) Adapter with 4 output signals (Compressor / Error, Fan, Aux. heater, Humidifier output) EKRP1B2 EKRP1B2 KRP1B61 Adapter for centralised external monitoring/control via dry contacts and setpoint control via 0-140Ω KRP4A51 KRP4A51 KRP4A51 KRP4A52 (2) KRP4A52 (2) KRP4A52 (2) Adapter for external central monitoring/control (controls 1 entire system) KRP2A51 KRP2A51 KRP2A51 KRP2A62 (2) KRP2A62 (2) KRP2A62 (2) BRP7A51 BRP7A52 BRP7A52 BRP7A52 DTA104A61 DTA104A62 DTA104A62 DTA104A62 KRP1D93A KRP1D93A KRP1D93A Adapter for keycard and/or window contact connection (2)(11) BRP7A51 BRP7A51 Adapter for multi-tenant applications (24VAC PCB power supply interface) DTA114A61 DTA114A61 External control adapter for outdoor unit (installation on indoor unit) DTA104A61 DTA104A61 Installation box / Mounting plate for adapter PCBs (For units where there is no space in the switchbox) KRP4A96 KRP4A96 Wiring kit for Remote ON/OFF or Forced OFF Standard Standard Standard EKRORO4 EKRORO4 EKRORO4 Drain pump kit Standard Standard KDU30M250 KDU50P60 KDU50P140 KDU50P140 KDDQ50A140 KDDQ50A140 KDDQ50A140 KDAJ25K71 KDAJ25K140 KHFP5M35 KHFP5N63 KHFP5N160 Multi zoning kit (for detailed model code overview refer to multizoning argue card in this catalogue) Fresh air intake kit (direct installation type) Air discharge adapter for round duct Filter chamber for bottom suction NEW (1) pump station is necessary for this option (2) Installation box is necessary for these adapters (3) The BYCQ140EW has white insulation. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140E decoration panel in environments exposed to concentrations of dirt” (4) Not recommended because of the limitation of the functions (5) To be able to control the BYCQ140EGF(B) the controller BRC1E is needed (6) The BYCQ140EGF(B) is not compatible with Multi and Split Non-Inverter Outdoor units (7) Option not available in combination with BYCQ140EGF(B) (8) Both parts of the fresh air intake are needed for each unit (9) Cannot be combined with sensor kit (10) Independently controllable flaps function not available (11) Only possible in combination with BRC1H* / BRC1E* (12) When fixing box is required, use KJB212A, KJB311A or KJB411A depending on the size of the controller (13) Option KEK26-1A (Noise filter) is required when installing DCS301B51 (14) Wire harnass EKEWTSC is necessary (15) The active airflow circulation function is not available for this controller. (16) Up to 2 adaptor PCBs can be installed per installation box (17) Only one installation box can be installed per indoor unit (18) Filter chamber KDJ3705L280 is necessary for this option 202 Wall mounted units 4-way blow FXUQ-A FXAQ-A Concealed FXNQ-A Floor standing units Free-standing FXLQ 20~25 FXLQ 32~40 FXLQ 50~63 EKRDP25A EKRDP40A EKRDP63A KDBHP49B140 + KDBTP49B140 BRC7C58 BRC7EA628 BRC4C65 BRC4C65 BRC4C65 BRC4C65 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • KRCS01-4 KRCS01-1B KRSC01-4 KRCS01-1 KRCS01-1 KRCS01-1 • • • • KRP1B56 KRP1B56 KRP1B61 KRP1B61 KRP1B61 KRP4AA51 (2) KRP4A54-9 KRP4A51 KRP4A51 KRP4A51 KRP2A51 / KRP2A61(2) KRP2A53 KRP2A51 KRP2A51 KRP2A51 BRP7A51 BRP7A51 BRP7A51 BRP7A51 DTA114A61 DTA114A61 EKMTAC EKMTAC EKMTAC Standard Standard Standard Standard KAFP551K160 • KRP4A53 (2) • (14) BRP7A53 DTA104A51 / DTA104A61 KRP1B97 KRP4AA93 (16)(17) EKRORO5 Standard K-KDU572EVE HXY080-125A8 HXHD125-200A8 EKHBDPCA2 EKRP1HBAA EKRP1AHTA - EKRUAHTB - EKBUHAA6(W1/V3) EKRTWA EKRTR1 EKRTETS - Domestic hot water tank - standard (stacked on top of hydrobox) - EKHTS200AC EKHTS260AC Domestic hot water tank - with possibility for solar connection Solar collector (1) Pump station - EKHWP500B EKSV26P (vertical) EKSH26P (horizontal) EKSRPS Drain pan Digital I/O PCB Demand PCB - Required to connect room thermostat Remote user interface (remocon) - Same controller as supplied with cascade unit can be mounted parallel or on other location. If 2 controllers are installed, the installer needs to select 1 master & 1 slave Back-up heater Wired room thermostat - Requires demand PCB EKRP1AHTA Wireless room thermostat - Requires demand PCB EKRP1AHTA Remote sensor for room thermostat - Requires demand PCB EKRP1AHTA 203 Options & accessories - ventilation Heat Recovery Ventilation - Modular L (Smart) Building Management System & Standard protocol interface Centralised control systems Individual control systems ALB02LBS/RBS ALB03LBS/RBS ALB04,05LBS/ RBS BRC301B61 VAM wired remote control Madoka BRC1H519W7 (White) / BRC1H519S7 (Silver) / BRC1H519K7 (Black) User-friendly wired remote controller with premium design BRC1E53A/B/C Wired remote control with full-text interface and back-light BRC1D52 Standard wired remote control with weekly timer DCC601A51 intelligent Tablet Controller DCS601C51 intelligent Touch Controller DCS302C51 Central remote control DCS301B51 Unified ON/OFF control DST301B51 Schedule timer DCM601A51 intelligent Touch Manager EKMBDXA Modbus interface DMS502A51 BACnet Interface DMS504B51 LonWorks Interface ALB06,07LBS/ RBS VAM 150FC9 VAM 250FC9 VAM 350J • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Coarse 55% (G4) ALF02G4A ALF03G4A ALF05G4A ALF07G4A ePM10 75% (M5) ALF02M5A ALF03M5A ALF05M5A ALF07M5A ePM10 70% (M6) Filters ePM1 50% (F7) EKAFVJ50F6 ALF02F7A ALF03F7A ALF05F7A ALF07F7A ePM1 55% (F7) EKAFVJ50F7 ePM1 70% (F8) EKAFVJ50F8 ePM1 80% (F9) ALF02F9A ALF03F9A ALF05F9A ALF07F9A Rail ALA02RLA ALA03RLA ALA05RLA ALA07RLA Rectangular to round duct transition ALA02RCA ALA03RC ALA05RCA ALA07RCA CO2 sensor BRYMA200 BRYMA200 BRYMA200 BRYMA200 Electrical heater ALD02HEFB ALD03HEFB ALD05HEFB ALD07HEFB ALS0290A ALS0390A ALS0590A ALS0790A High efficiency filter Mechanical accessories Replacement air filter Separate plenum GSIEKA10009 GSIEKA15018 GSIEKA20024 Wiring adapter for external monitoring/control (controls 1 entire system) KRP2A51 KRP2A51 KRP2A51 (2) Adapter PCB for humidifier KRP50-2 KRP50-2 KRP1C4 (5) Adapter PCB for third party heater BRP4A50 BRP4A50 BRP4A50A (4) Electrical accessories Silencer (900mm depth) External wired temperature sensor Adapter PCB Mounting plate Notes (1) Do not connect the system to DIII-net devices LONWorks interface, BACnet interface, …; (intelligent Touch Manager, EKMBDXA are allowed) (2) Installation box KRP1BA101 needed (3) Adapter PCB mounting plate needed, applicable model can be found in the table above (4) 3rd party heater and 3rd party humidifier cannot be combined (5) Installation box KRP50-2A90 needed (6) Contains 1 plenum and can be used for half side of the unit (up to 4 plenums can be used on 1 unit) (7) Available only with optional plenum 204 BRYMA65 Energy recovery ventilation - VAM Energy recovery ventilation VKM VAM 500J VAM 650J VAM 800J VAM 1000J VAM 1500J VAM 2000J • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • EKAFVJ50F6 EKAFVJ65F6 EKAFVJ50F7 EKAFVJ50F8 Air handling unit applications VKM 50GB (M) VKM 80GB (M) VKM 100GB (M) EKEQ FCBA (1) EKEQ DCB (1) EKEQ MCBA (1) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • EKAFVJ100F6 EKAFVJ100F6 EKAFVJ100F6 x2 EKAFVJ100F6 x2 EKAFVJ65F7 EKAFVJ100F7 EKAFVJ100F7 EKAFVJ100F7 x2 EKAFVJ100F7 x2 EKAFVJ65F8 EKAFVJ100F8 EKAFVJ100F8 EKAFVJ100F8 x2 EKAFVJ100F8 x2 KAF242H80M KAF242H100M KAF242H100M KAF241H80M KAF241H100M KAF241H100M BRYMA65 BRYMA100 BRYMA200 EKPLEN200 (6) EKPLEN200 (6) BRYMA200 BRYMA200 BRYMA65 BRYMA65 BRYMA100 BRYMA100 GSIEKA20024 GSIEKA25030 GSIEKA25030 GSIEKA25030 KRP2A51 (2) KRP2A51 (2) KRP2A51 (2) KRP2A51 (2) KRP2A51 (2) KRP2A51 (2) BRP4A50A (4) BRP4A50A (4) BRP4A50A (4) KRP1C4 (5) KRP1C4 (3/5) KRP1C4 (5) KRP1C4 (5) KRP1C4 (3/5) KRP1C4 (3/5) BRP4A50A (4) BRP4A50A (4) BRP4A50A (4) BRP4A50A (4) BRP4A50A (3/4) BRP4A50A (4) BRP4A50A (4) BRP4A50A (3/4) BRP4A50A (3/4) BRP4A50A (4) BRP4A50A (4) BRP4A50A (4) GSIEKA35530 (7) KRCS01-1 EKMP65VAM EKMPVAM 205 Options - Control systems Individual and centralised controls BRC1D* BRC1E* • • • • BRC1H* Electical box KJB111A Electical box KJB212A(A) (1) DCS301B51 DST301B51 • • DCS302C51 DCS601C51 • • Madoka Assistant app for advanced settings • Electical box KJB311A(A) • Electical box KJB411AA (1) recommended as wider (more stable mounting) Intelligent Tablet Controller - DCC601A51 Tabl et Wired screen for local control Options for local control Daikin Cloud Service options • - - • AL-CCD07-VESA-1 Control and monitoring package Remote support and diagnostics package Advise and optimisation package Commissioning tool Software update tool Software - • • - • • Daikin Cloud Service requires a subscription. Contact your local sales representative for more information Standard protocol interfaces - DMS502A51 BACnet Interface DIII-net expansion board (2 ports), connects up to 128 additional indoor units DAM411B51 • Digital pulse inputs (12) for PPD functionality DAM412B51 • Differential Pressure Sensor 4-20 mA 0-160 kPa EKQDP2M016 Differential Pressure Sensor 4-20 mA 0-250 kPa EKQDP2M020 • • • • • • Intelligent Chiller Manager 206 Differential Pressure Sensor 4-20 mA 0-400 kPa EKQDP2M040 Differential Pressure Sensor 4-20 mA 0-600 kPa EKQDP2M060 ModBus RTU communication module EKCM200J BACnet IP communication module EKCMBACIP Options - Control systems Intelligent Touch Manager - DCM601A51 Daikin Cloud Service options (2) iTM plus adapter – Allows connection of an additional 64 indoor units/groups. Up to 7 adapters can be connected DCM601A52 • iTM PPD software – Allows distribution of used kWh by indoor units connected to the iTM DCM002A51 • iTM HTTP interface - Allows communication to any third party controller via http interface DCM007A51 • iTM Energy navigator – Energy management option DCM008A51 • iTM BACnet Client option – Enables integration of third party devices to the iTM via the BACnet/IP protocol. (This is not a gateway and cannot replace DMS502A51) DCM009A51 • Property Management System (PMS) interface option Enables to connect to third party PMS systems DCM010A51 • Oracle Opera PMS Monitoring package • Remote support and diagnostics package • Advise and optimisation package • WAGO interface options for intelligent Touch Manager Required or optional WAGO base modules Module type Model code Specifications 24 V DC power supply 787-712 100 to 240 V AC —> 24 V DC, 2.5 A Required Communications unit (Bus coupler) WGDCMCPLR2 RS-485, Max:115.2kbps, not programmable Required Connector (1) 750-960 Required Terminator module 750-600 Required Power supply module 750-613 IN: 24 V DC, OUT: 5 V DC Optional Supported WAGO I/0 modules I/0 module type Di Model code Specifications 750-400 No-voltage contact input Contact rating: 24 V DC / 4.5 mA“ 750-432 8 750-513/000-001 No-voltage contact output Contact rating: 230 V AC / 30 V DC, 2 A 2 750-504 No-voltage contact output Contact rating: 24 V DC / 0.5 A 4 750-455 2 4 Rated at −10 to 10 V: 13-bit resolution 2 750-459 Rated at 0 to 10 V: 12-bit resolution 4 750-555 Rated at 4 to 20 mA: 12-bit resolution 2 4 750-560 Rated at −10 to 10 V: 10-bit resolution 2 750-559 Rated at 0 to 10 V: 12-bit resolution 4 750-461/020-000 NTC20K thermistor 2 750-461 750-460 750-461/000-003 750-460/000-003 50-461/000-004 750-461/000-005 750-460/000-005 Pi Rated at 4 to 20 mA: 12-bit resolution 750-479 750-554 Thermistor 4 750-430 750-454 Ao 2 No-voltage contact input Contact rating: 24 V DC / 2.8 mA Do Ai N° of contacts 750-638 Pt 100/RTD Pt 1000/RTD Ni 100/RTD Ni1000 TK6180/RTD Minimum pulse width: 1 ms 2 4 2 4 2 2 4 2 (1) This connector must be attached to a communications unit that is connected to the RS485 port (2-pin) of the iTM unit. (2) To connect intelligent Touch Manager to the Daikin Cloud Service, the IoT gateway (EU.SB.5000072) and AC/DC converter (999175A) is needed. 207 We’re here to help you! Online and offline Online and offline VRV selection software Business portal via mobile or desktop my.daikin.eu Full BIM object library available bim.daikin.eu 208 Tools & platforms Tools & platforms 209 Literature overview 210 Supporting tools, software and apps 212 30 years of history 216 209 Literature overview for professional network Solutions catalogues: Reference books: Reference catalogue Reference catalogue Daikin commercial and industrial references Commercial & Industrial applications 213 Water-to-air heat pump Main benefits, application examples and specs of VRV IV i-series product range Detailed info on VRV IV W-series, application examples, technical system design background Water-to-air heat pump using water as a heat source Scale up your expectations 40 30 20 10 2016 2018 2020 2022 2024 2026 2028 RZAG-A › Guarantees operation in both heating and cooling mode down to -20°C › Reliable in operation thanks to refrigerant cooled PCB › Maximum piping length up to 50m and 30m in height difference › Connectable to all common Sky Air models and Perfera (FTXM) wall mounted unit Industry leading technology in the most compact casing ever Variable Refrigerant Temperature Replacement technology Infrastructure cooling › Reliable in operation thanks to refrigerant cooled PCB › Very long piping lengths up to 85m › Market-leading serviceability and handling • Easy access to all components • 7-segment display 147 Madoka Split, Sky Air, VRV, Chillers, Refrigeration, Daikin Altherma Detailed info on BRC1H* remote control Low height large Sky Air Advance-series RZA-D / FDA-A Large Sky Air system for commercial applications in the most compact casing ever Replacement technology Pair, twin, triple, double twin application Pair, twin, triple, double twin application 146 More details and final information can be found on my.daikin.eu › Unique, low-height single fan portfolio › Best in class performance: SEER up to 8.02 (A++) › Lower environmental impact thanks to R-32 refrigerant › Suits infrastructure cooling applications › Guaranteed operation in both cooling and heating down to -20°C Modbus Interface › Unique, low-height single fan portfolio › 20 and 25 kW capacity › High efficiency: SEER up to 6.25 › Lower environmental impact thanks to R-32 refrigerant › Guaranteed operation in both cooling and heating down to -20 °C › Reliable in operation thanks to refrigerant cooled PCB › Very long piping lengths up to 100 m › Market-leading serviceability and handling • Easy access to all components • 7-segment display 605 Low height large Sky Air Advance-series RZA-D Sky Air Advance-series Main benefits and specs of the low height RZA-D* series RTD modbus interface Integration of Daikin portfolio in BMS system via Modbus › Indoor unit control via 0~10 volt, dry contact or resistance contact 306 Product catalogues: 308 Sky Air Catalogue Product catalogue 2019 for professionals A unique success story repeated NEW Daikin Europe N.V. for professionals 6 Predefined sizes Compliant with VDI 6022 Exceeding ERP 2018 requirement Plug & Play Controls Exhaust Air Supply Air ALB Return Air Naamloze Vennootschap Zandvoordestraat 300 · 8400 Oostende · Belgium · www.daikin.eu · BE 0412 120 336 · RPR Oostende (Responsible Editor) Daikin Europe N.V. participates in the Eurovent Certified Performance programme for Liquid Chilling Packages and Hydronic Heat Pumps, Fan Coil Units and Variable Refrigerant Flow systems. Check ongoing validity of certificate: www.eurovent-certification.com WINNER ECPEN18 - 200 2018 winner 100 Product catalogue 2018 Flexibility to meet your needs Fresh Air airflow direction Including Detailed technical information & benefits of the VRV total solution VRV Modular L Premium efficiency heat recovery unit UNIQUE Patents pending Reduced runningcosts Improved room air quality Minimal time required for filter cleaning Unique technology 04/18 The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V. The present publication supersedes ECPEN17-200. Printed on non-chlorinated paper. VRV Product catalogue 2018 for professionals Detailed technical information & benefits on Sky Air VRV Catalogue Auto cleaning filter for concealed ceiling units Sky Air Sky Air Alpha-series and Round Flow cassette 210 › Retail applications › Hotel applications › IT applications › Heating interlock › Alarm signal Minimum running costs, maximum flexibility. Fast installation, top reliability, perfect comfort. ErP iant compl 2021 THE BEST ER PARTN FOR GREEN ING BUILD RT SUPPO OUR BIM VISIT ION APPLICAT ON SUITE WWW.DA IKIN.EU/B Ventilation Catalogue Ventilation Product catalogue 2020 for professionals Detailed info on Ventilation products Fresh air for the residential and commercial sector Heat recovery ventilation and air handling applications IM 200 RE CL 1 203 223 VRV IV S-series VRV IV S-series Certified Reclaimed Refrigerant Allocation External Certified Quality Reclaimed refrigerant meets AHRI700 certified standards, assessed by an independent laboratory, and so is the same quality as virgin refrigerant. IFI Reclaimed and reused within Europe Reclaimed means the refrigerant is regenerated in a high quality way, in line with the F-gas regulation definition. This means that units with reclaimed refrigerant support the F-gas regulation by recovery and reclaim within the European Union. ED Certified Allocated Quantity 148 Detailed info on RTD controls and applications RTD ED RE CL F -G AS Mini VRV L∞P by Daikin Main benefits and specs of RXYSQTV9/TY9 series with reclaimed refrigerant RI › Capacities from 3,5 to 6kW › Top efficient outdoor units up to A++ › Lower environmental impact thanks to R-32 refrigerant › Suits infrastructure cooling applications › Replacement technology › Exclusively offered for pair applications IF I REF RZAG-A Extension of the Sky Air Alpha-series range for light commercial applications and technical cooling RZAG-N* Sky Air Alpha-series Main benefits and specs of the low height RZAG-N* RZAG-NV1/NY1 Make a positive choice and reuse refrigerant to avoid more than 150,000 kg of virgin gas being produced each year D Inverter RZAG-A mini Sky Air Alpha-series Main benefits and specs of RZAG-A series 28/06/17 14:28 ME cooling Low height Sky Air Alpha-series Low height Sky Air Alpha-series 1. Minimising the impact of new equipment, by reducing the use of high GWP F-gases › Changing to lower GWP HFCs and non-HFC gases for specific sectors (e.g. use of R-32 for residential sector, etc.) › Reducing refrigerant charges 2. Reducing the use of refrigerants for servicing HVAC-R equipment › Reducing leakages › Servicing ban on HFC with GWP > 2,500 for refrigeration equipment above 40 TCO2eq charge, (e.g. R-404A) 3. Increasing recovery and reuse of HFCs (only new HFC gases are part of the HFC phase down scheme) AI Infrastructure Mini Sky Air Alpha-series 2030 L∞P by Daikin Detailed info on L∞P by Daikin where reclaimed refrigerant is reused N 50 T IO CA 60 RT 70 CE 80 N 90 T IO CA EU phase down targets towards 100 ECPEN17-605_F-gas Regulation_07.indd 1 RT To reduce the environmental impact of refrigerants, the EU wants to reduce the consumption and consequently reduce the use in air conditioners and other applications. However, HFCs remain necessary in many applications because of their energy efficiency, safety and economic benefits. There is no ban nor a phase out of HFCs, but a gradual phase down to a level that remains necessary for a sustainable growth of the air conditioning, heat pump and refrigeration industry. CE No HFC ban but a phase down, why? There are 3 main areas with specific actions to achieve the phase down: % of baseline consumption allowed 140 Ready for the 2030 A/C market Certified Reclaimed refrigerant Certified Reclaimed Refrigerant Allocation LO 214 Details on the F-gas regulation and how Daikin is prepared for the future HVAC-R market RI Clear installer benefits why to choose Daikin for infrastructure cooling F-gas regulation New F-gas Regulation REF Clear installer benefits of VRV replacement technology 210 D Mini Sky Air Alpha-series Variable Refrigerant Temperature Offering like-for-like R-410A flexibility ME Infrastructure cooling Baseline = the average HFC consumption between 2009 and 2012 Product flyers: COMPLIANT AI Replacement Technology 0 The quick and quality way of upgrading R-22 and R-407C systems ErP 2021 Industry-leading real life efficiencies AL for installers CO Lower CO2 equivalents 209 Virgin and reclaimed refrigerant are used in the Daikin Europe factory. Through an audit process we ensure the reclaimed refrigerant is administratively allocated to the VRV IV+ and Mini VRV factory charge. NT Replacement technology Lower CO2 equivalent and market-leading efficiencies RA Focus topics: 207 Join us to create a sustainable future VRV 5 Main benefits and specs of VRV 5 GE 208 VRV 5 S-series ALL O VRV IV heat pumps for indoor installation VRV5 S-Series NT Compact VRV IV heat pumps for residential and light commercial applications VRV IV i-series i Keep looking you’ll never find me Main benefits, application examples and specs of VRV IV S-series product range RA VRV IV S-series Keep looking you’ll never find me GE Product profiles: Reclaiming R-410A is just the start With a huge potential of R-410A available in existing installations, we invite you to join our mission in creating this circular economy. Today for R-410A and for other refrigerants in future. 224 for your customers Solutions catalogues: Commercial Solutions Green Buiding Solutions Daikin offers solutions for commercial applications Green building solutions 100 Sustainable design with Daikin HVAC-R systems Reference books: Maximise your BREEAM score Clear building owner/ investor benefits why to choose Daikin for a green building, with emphasis on BREEAM Maximise your BREEAM score with Daikin Solutions BREEAM categories Overview of how to score BREEAM points with Daikin Hotel Solutions Hotel solutions for hotel owners Heating - air conditioning - hot water - ventilation - refrigeration - control Clear building owner/investor benefits why to choose Daikin for a hotel 218 International New Construction 2016 216 221 Success Case study Success case study Hotel Van der Valk, Mons ›A Daikin total solution Vandervalk hotel case In depth info on the VRV total solution at a Vandervalk hotel 219 Product profiles: Intelligent Touch Manager Control systems Intelligent Touch Manager Detailed benefits of Intelligent Touch Manager Tablet intelligent Tablet Controller Intelligent Tablet Controller Daikin Cloud Serivce Details on the Daikin Cloud connection Daikin Cloud Service Detailed benefits of Intelligent Tablet Controller Remote monitoring and control for commercial DX systems An intelligent approach to air conditioning management Mini Building Management System Advanced centralised controller with cloud connection ECPEN19-542_V04.indd 1 302 Focus topics: SPLIT, SKY AIR, VRV, CHILLERS The phase-out period for R-22 is over. Act now! Avoid loss of business and replace your air conditioning system now! 303 18/09/2018 10:39 542 Replacement technology Clear building owner/investor benefits of replacement technology 15-215 Technical documentation: Download all technical documentation such as engineering databooks, selection software, installation and operation manuals and service manuals directly from our business portal: my.daikin.eu 211 Supporting tools, software and apps www.daikineurope.com/ support-and-manuals/ software-downloads Web based Xpress selection software Making selection easy, anythime, anywhere › Web & cloudbased, access to your projects from anywhere, anyplace… › Platform (Windows, Mac, …) and hardware (laptop, desktop, tablet) independent › Re-engineered GUI for maximum easy of use › No need to do local installation › No tool updates required (always latest version available) › Possibility to copy / share projects Easy selection, anytime, anywhere Main functions Toolbox Working area Detailed properties Import / Export / Delete indoors 212 Easy editing of piping Intuitive interface Clear wiring overview, easy to make control groups Clear overview of control groups and central controls Other selection software VRV Pro Ventilation Xpress Enables VRV air conditioning systems to be engineered in a precise and economical way, taking into account the complex piping rules. Moreover, it ensures optimum operating cycles and maximum energy efficiency. › Accurate heat load calculation › Precize selection based on peak loads › Energy consumption indication Selection tool for ventilation devices (VAM, VKM). The selection is based on given supply/extract airflows (including fresh up and given ESP of supply/extract ducting: › Determines size of electrical heaters › Visualisation of psychrometric chart › Visualisation of selected configuration › Required field settings mentioned in the report Webbased ASTRA selection for air handling units WAGO selection tool A powerful tool to select the right Air Handling Units for your needs. › 3D interface › quick selection procedures › new print-out possibilities and report shapes The WAGO Selection Tool is specifically designed to select the optimal WAGO I/O system for your needs. › Easy selection of WAGO materials › Material list creation › Time saving • Includes wiring schemes • Contains commissioning/preset data for 213 Plugins and third-party software tools Building Information Modelling (BIM) support www.daikin.eu/ bim › BIM improves efficiency of design and build phase › Daikin is among the first to supply a full library of BIM objects for its VRV products VRV CAD 2D › Displays VRV pipe design on a Autocad 2D floorplan › Improves project management › Accurately calculates the pipe dimensions and refnets › Determines the outdoor unit size › Validates VRV pipe rules › Accounts for the extra refrigerant charge, including a max room concentration check Energy simulation and design aid tools Seasonal simulator › The Seasonal Simulator is an innovative software tool that calculates and compares potential seasonal efficiency ratings. › This user-friendly tool compares various Daikin systems, annual power consumption, CO2 emissions, and much more, to present an accurate ROI calculation in a matter of minutes. Psychrometrics diagram NEW › The Psychrometrics Diagram Viewer demonstrates the changing properties of moist air. › With this tool, users can choose two points with specific conditions, plot them on the diagram and select actions to change the conditions, i.e. heat, cool and mix air. 214 http://www. daikineurope. com/autocad/ index.jsp Service tools Error code app Quickly know the meaning of fault codes, for each product family and the potential cause D-Checker D-checker is a software application used to record and monitor operation data of Daikin applied, split, Multi-split, Sky-air units, Daikin Altherma LT, ground source heat pump, Hybrid, ZEAS, Conveni-pack & R410A Booster unit Bluetooth adaptor NEW Monitoring of Split, Sky Air and VRV data via any bluetooth device › No need to access the outdoor unit Diagnosis of the Bluetooth system possible: • Connects with D-Checker software (for laptops) • Connects with monitoring app (for tablets or smartphones) Computer with Bluetooth VRV Service-Checker › Connected via F1/F2 bus to check multiple systems at the same time › Connection of external pressure sensors possible Online support Internet Business portal Find our solution for different applications: › Experience our new extranet that thinks with you at my.daikin.eu › Find information in seconds via a powerful search › Customise the options so you see only info relevant for you › Access via mobile device or desktop Supermarket Technical Restaurant Hotel Store & shop Home Bank Office Industry Sport & Leisure my.daikin.eu ON THE R OA D AT C U S TO M E RS AT THE OFFICE › Get more commercial details on our flagship products via our dedicated minisites › See our references HOTEL PORTA FIRA www.daikineurope.com/references 215 Over 30 years of VRV History 1987 1998 2004 2008 Introduction the original VRV air conditioning system to Europe, invented by Daikin in 1982 › Up to 6 indoor units connected to 1 outdoor unit Launch inverter series with R-407C › Up to 16 indoor units connected to 1 outdoor unit Expand to light commercial sector with VRVII-S › Available in 4, 5, 6HP capacities › 1 system can be installed in up to 9 rooms Launch of heat pump optimised for heating (VRV III-C) › Extended operation down to -25C › 2-stage compressor systems 1987 1991 1998 2003 2004 2005 2003 1991 Introduce VRV heat recovery › Simultaneous cooling and heating 216 Introduce VRVII-- the first R-410A VRF system Available in cooling, heat pump and heat recovery › 40 units connected to single refrigerant circuit 2005 Extends VRVII inverter range with water cooled VRV-WIII › Available in heat pump and heat recovery 2006-2007 2006-2007 Launch the extensively re-engineered VRVIII › Available in cooling, heat pump and heat recovery › Automatic charging and testing › Up to 64 units connected to 1 system 2008 2015 Launch of VRV IV S-series › Most compact unit in the market › Widest range in the market 2015 Launch of VRV IV i-series › The invisible VRV › Unique product concept 2011 Launch total solution concept › Integrate hot water production and Biddle air curtains into VRV system › Connectable to Daikin Emura and Nexura › 400,000 outdoors units sold › 2.2 million indoor units sold 2010 2011 2010 Launch of replacement VRV (VRVIII-Q) › Upgrade to replace older VRV units using R-22 refrigerant 2012 2015 2012-2014 Setting new standards with the launch of VRV IV › 28% improved seasonal efficiency › Continuous heating on heat pumps › Available in heat pump, heat recovery, water-cooled and replacement series 2019 2020 Launch of VRV IV+ series › New compressor for increased seasonal efficiency › Available in heat recovery, heat pump, optimised for heating and water-cooled versions VRV 5 S-series › Completely redesign unit for R-32 refrigerant › Easier to handle and more flexible to install then ever! 2019 2020 2019 Launch of L∞P by Daikin › Re-use of existing refrigerant › Creating a circular economy of refrigerants 217 218 Technical drawings Technical drawings 219 Outdoor units 220 Indoor units 246 Hot water 286 Biddle air curtains 291 Ventilation 294 219 Technical drawings Outdoor units RXYSA-AV1 / AY1 221 REYQ-U / REMQ-U / RYYQ-U / RYMQ-U / RXYQ-U / RXYQQ-U 225 RXYSCQ-TV1 / RXYSQ-TV9 / TY9 / TY1 227 RDXYQ-T(8) / RKXYQ-T(8) 237 RXMLQ-T - RXYLQ-T 239 RQCEQ-P3240 RQYQ-P243 RWEYQ-T9245 220 RXYSA-AV1/AY1 30 171 36 55 485 (480~490) 758 30 41 101 4 holes for anchor bolts M12 40 460 171 4 1100 3 2 1 7 7 51 45 869 6 6 5 95 175 90 12 53 95 45 325 25 70 25 53 70 90 150 53 26 95 190 45 5 99 150 17 103 58 71 17 8 Liquid pipe connection ·Ø9.5· brazing 3 Service port (in the unit) 4 Electronic connection and grounding terminal ·M5· (in the switch box) 46 59 51 246 5 1 Gas pipe connection ·Ø22.2· brazing 2 45 50 109 289 163 163 163 5 Refrigerant piping intake 6 Knockout hole. 7 Knockout hole. 8 Drain outlet RZA-D 250 250 Wall * For optimal serviceability, provide ≥·250·mm of free space. For more installation and service space guidelines, see drawing ·3D069554·. 3D120935 221 RXYSA-AV1/AY1 RXYSA-AV1 RXYSA-AY1 Single unit ( ) | Single row of units ( ) Suction side In the illustration below, the service space at the suction side is based on 35°C DB and cooling operation. Foresee more space in the following cases: - When the suction side temperature regularly exceeds this temperature. - When the heat load of the outdoor units is expected to regularly exceed the maximum operating capacity. Discharge side Take refrigerant piping work into account when positioning the units. If your lay out does not match with any of the layouts below, contact your dealer. Single unit ( eB eD HD ) |Single row of units ( E C c HU D d e B H B b a A C c HU HD E eD Hu Hb,Hd 1 2 B A,B,C B,E A,B,C,E D D,E Hd>Hu Hd≤Hu Hb≤½Hu Hd>Hu ½Hu>Hb≤Hu Hb>Hu Hd≤½Hu Hd≤Hu ½Hu<Hd≤Hu Hd>Hu Hd>Hu Hd≤½Hu Hd≤Hu ½Hu<Hd≤Hu Hb≤½Hu Hd>Hu ½Hu<Hb≤Hu Hb>Hu Hd≤½Hu Hd≤Hu ½Hu<Hd≤Hu Hd>Hu B,D,E A,B,C A,B,C,E D D,E e B,D ≥100(1) B HB b ≥100(1) D d (1) A,B,C,D E a,b,c,d,e eB Hb Hd Hu B,D eB eD A~E a A B,D,E ) a ≥ 100(1) ≥ 150(1) ≥ 200(1) ≥ 200(1) b ≥ 100 ≥ 100 ≥ 100 ≥ 150 c (mm) d ≥ 100 ≥ 150 ≥ 100 ≥ 100 ≥ 250 ≥ 250 ≥ 500 ≥ 500 ≥ 500 ≥ 500 ≥ 750 ≥ 1000 ≥ 100 ≥ 200 ≥ 1000 ≥ 1000 ≥ 300 ≥ ≥ 300 1000 ≥ 1000 e eB ≥ 1000 ≥ 1000 eD ≤500 ≤500 ≥ 1000 ≤500 ≥ 1000 ≥ 1000 ≤500 ≤500 ≥ 1000 ≥ 1000 ≤500 ≤500 ≥ 1000 ≤500 ≥ 300 ≥ 250 ≥ 300 ≥ 300 ≥ 300 ≥ 1000 ≥ 1000 ≥ 1000 ≥ 1500 ≥ 1500 PATTERN≥ 1000 1 ≥ 1250 ≥ 1000 ≤500 ≥ 1000 ≥ 1000 ≤500 ≤500 ≥ 250 ≥ 300 ≥ 1500 ≥ 1500 ≥ 1000 ≥ 1000 ≤500 ≤500 1 1+2 For better serviceability, use a distance ≥250 mm Obstacles (walls/baffle plates) Obstacle (roof) Minimum service space between the unit and obstacles A, B, C, D and E Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle B Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle D Height of the unit Height of obstacles B and D Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit. Maximum two units can be installed. Not allowed 1D128513 222 RXYSA-AV1/AY1 RXYSA-AV1 RXYSA-AY1 Multiple rows of units ( Multiple rows of units ( ) ) ≥100(1) ≥100(1) H ≥100 B b ≥100(1) ≥2000 ≥100(1) ≥3000 ≥100(1) ≥200 ≥100(1) ≥1000 ≥ 600 H U ≥1500 Hb Hu Hb≤½Hu ½Hu<Hb≤Hu b (mm) b≥250 b≥ 300 Hb>Hu (1) For better serviceability, use a distance ≥250 mm Not allowed 1D128513 223 RXYSA-AV1 RXYSA-AV1/AY1 RXYSA-AY1 Stacked units (max.2 levels) ( Stacked units (max.2 levels) ( ) ) A2 A1 ≥100(1) A2 ≥100(1) ≥500 A2 ≥500 ≥1000 B1 ≥300 B2 ≥100(1) B2 ≥100(1) ≥100(1) ≥1000 B2 ≥100(1) ≥300 (1) A1=>A2 For better serviceability, use a distance ≥250 mm (A1) If there is danger of drainage dripping and freezing between the upper and lower units… (A2) Then install a roof between the upper and lower units. Install the upper unit high enough above the lower unit to prevent ice buildup at the upper unit's bottom plate. B1=>B2 (B1) If there is no danger of drainage dripping and freezing between the upper and lower units… (B2) Then it is not required to install a roof, but seal the gap between the upper and lower units to prevent discharged air from flowing back to the suction side through the bottom of the unit. 1D128513 224 VIEW ALL REYQ-U TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL RYYQ-U TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL RXYQ-U TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL RXYQQ-U TECHNICAL DRAWINGS ON MY.DAIKIN.EU REMQ5U / REYQ8-12U / RXYQQ8-12U / RXYQ8-12U / RYYQ8-12U / RYMQ8-12U / RXYTQ8UYF REMQ5U Pitch of foundation bolt holes 766 100 66 160 106 AB Detail ·B· Detail ·A· 4-15x22.5mm 353 8 134 125 107 335 729 190 RXYTQ8-UYF AA RXYQ8-12U RYMQ8-12U 112 RXYQQ8-12U 3 70 2 1 Pitch of foundation bolt holes REYQ8-12U Oblong hole 10 View ·C· Foundation bolt hole 1685 11 4 7 6 179 131 276 259 515 122 9 76 76 Detail ·B· 137 Notes 97 Detail ·A· 328 1. Detail ·A· and detail ·B· indicate the dimensions after fixing the attached piping. 2. Items ·4 - 10:· 3. Gas pipe 5 107 Model 272 765 373 Knockout hole. AA RYYQ8-12U, RXYQ8-12U, RXYQQ8-12U,RXYTQ8U C 246 REMQ5U, RYMQ8-12U, REYQ8-12U AB 240 930 : : : : RYYQ8U, RYMQ8U, RXYQ8U, RXYQQ8U, RXYTQ8U RYYQ10U, RYMQ10U, RXYQ10U, RXYQQ10U REMQ5U, REYQ8-12U RYYQ12U, RYMQ12U, RXYQ12U, RXYQQ12U Liquid pipe RYYQ8-10U, RYMQ8-10U, RXYQ8-10U, RXYQQ8-10U, REMQ5U, REYQ8-12U, RXYTQ8U : Grounding terminal Pipe routing hole (bottom) Pipe routing hole (front) Power cord routing hole (bottom) Power cord routing hole (front) Power cord routing hole (front) Power cord routing hole (front) Power cord routing hole (side) Equalising pipe connection port 3 High pressure/low pressure gas pipe 2 Gas pipe connection port 1 Liquid pipe connection port No. Part name Ø ·19.1· brazing connection Ø ·22.2· brazing connection Ø ·25.4· brazing connection Ø ·28.6· brazing connection 11 10 Ø ·9.5· brazing connection : Ø ·12.7· brazing connection RYYQ12U, RYMQ12U, RXYQ12U, RXYQQ12U Equalising pipe RYMQ8-10U : Ø ·19.1· brazing connection RYMQ12U : Ø ·22.2· brazing connection High pressure/low pressure gas pipe : Ø ·19.1· brazing connection REMQ5U, REYQ8-12U Inside of the switch box (·M8·) 9 8 7 6 5 4 Ø65 Ø27 Ø65 Ø80 Ø65 See note ·3·. See note ·3·. See note ·3·. Remark 2D119001 REYQ14-20U / RXYQQ14-20U / RXYQ14-20U / RYYQ14-20U / RYMQ14-20U / RXYTQ10-16UYF 71 160 106 AA 4-15x22.5mm - Detail B Detail A Oblong hole 125 8 70 729 AB 310 100 393 134 107 1076 3 112 2 Pitch of foundation bolt holes Pitch of foundation bolt holes 1 210 REYQ14-20U RXYQQ14-20U RXYQ14-20U RXYTQ10-16U RYYQ14-20U RYMQ14-20U 10 View C Foundation bolt hole 1685 11 4 7 6 137 179 97 DETAIL B DETAIL A 765 5 107 272 328 C 373 1. Detail A and detail B indicate the dimensions after fixing the attached piping.1. 2. Items 4 - 10: 131 276 76 76 Notes 259 515 122 9 Knockout hole. 1240 3. Gas pipe Ø 22.2 brazing connection RXYTQ10U REYQ14-20U Ø 25.4 brazing connection RYYQ14-20U, RYMQ14-20U, RXYQ14-20U, RXYQQ14-20U, Ø 28.6 brazing connection RXYTQ12-16U Liquid pipe RXYTQ10U Ø 9.5 brazing connection RYYQ14-16U, RYMQ14-16U, RXYQ14-16U, RXYQQ14-16U, REYQ14-20U, Ø 12.7 brazing connection RXYTQ12-16U Ø 15.9 brazing connection RYYQ18-20U, RYMQ18-20U, RXYQ18-20U, RXYQQ18-20U Equalising pipe RYMQ14-16U Ø 22.2 brazing connection 11 Grounding terminal 10 Pipe routing hole (bottom) RYMQ18-20U High pressure/low pressure gas pipe Ø 28.6 brazing connection REYQ14-20U Ø 22.2 brazing connection 2 Gas pipe connection port 1 Liquid pipe connection port No. Part name Model RXYQ14-20U, RYYQ14-20U, RXYQQ14-20U, RXYTQ10-16U RYMQ14-16U, REYQ14-20U RYMQ18-20U Pipe routing hole (front) Power cord routing hole (bottom) Power cord routing hole (front) Power cord routing hole (front) Power cord routing hole (front) Power cord routing hole (side) Equalising pipe connection port 3 High pressure/low pressure gas pipe 9 8 7 6 5 4 AA 240 240 AB 155 192 Inside of the switch box (M8) Ø65 Ø27 Ø65 Ø80 Ø65 See note 3. See note 3. See note 3. Remark 2D119091 225 VIEW ALL REYQ-U TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL RYYQ-U TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL RXYQ-U TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL RXYQQ-U TECHNICAL DRAWINGS ON MY.DAIKIN.EU REMQ-U / REYQ-U / RXYQQ-U / RXYQ-U / RYYQ-U / RYMQ-U / RXYTQ-UYF REMQ5U REYQ8-20U RXYQQ8-20U For single unit installation RXYQ8-20U For installation in rows RYYQ8-20U RYMQ-20U Pattern 1 Pattern 1 Pattern 1 300 or more 10 or more 10 or more 20 or more 500 or more Pattern 2 Front 20 or more 10 or more 10 or more 500 or more Pattern 2 100 or more 300 or more 300 or more 300 or more Front 20 or more 10 or more 100 or more 10 or more Front 50 or more 50 or more 100 or more 500 or more 300 or more Front 20 or more 10 or more 100 or more 900 or more Front 20 or more 20 or more 10 or more Front Front 50 or more Front 100 or more 50 or more 50 or more Front 100 or more 50 or more 50 or more 500 or more Front 50 or more 100 or more 300 or more 400 or more 500 or more 100 or more 500 or more Wall height unrestricted 10 or more 500 or more 50 or more Wall height unrestricted Pattern 3 10 or more 20 or more 10 or more 10 or more 500 or more Pattern 2 Front 600 or more 50 or more Front 10 or more 500 or more Pattern 3 200 or more 20 or more 10 or more 100 or more 300 or more Front 500 or more 600 or more 500 or more 50 or more 10 or more Front 400 or more Front 100 or more 500 or more 50 or more 50 or more 100 or more 50 or more 50 or more 100 or more Notes 1. Height of the walls in case of patterns 1 and 2: Front: 1500mm Suction side: 500mm Side: height unrestricted 50 or more Front 500 or more 200 or more < Unit : mm > h2 Front 10 or more For centralised group layout h1 Suction side 555 2. If the walls are higher than mentioned above, then additional service space is needed: - suction side: service space + h1/2 - front side: service space + h2/2 Front When the design outdoor ambient temperature exceeds 35°C or the load exceeds maximum ability of much generation load of heat in all outdoor unit, make sure the suction-side space is broader than the space shown on this drawing. 1555 The installation space shown on this drawing is based on cooling operation at 35°C (outdoor temperature). < Unit : mm > 3. When installing the units, select the pattern that best fits the available space. Always keep in mind to leave sufficient space for a person to pass between unit and wall and for the air to circulate freely. If more units are to be installed than are catered for in the above patterns, your layout should take into account of the possibility of short circuits. 4. Provide sufficient space at the front to connect refrigerant piping (comfortably). 3D118467 226 VIEW ALL RXYSCQ-TV1 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL RXYSQ-TV9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RXYSCQ-TV1 4 holes for anchor bolts 30 M12 Gas pipe connection ·AA· flare Liquid pipe connection ·Ø9.52· flare Service port (in the unit) High pressure Service port (in the unit) Additional refrigerant charge Grounding terminal Inside of the switch box (·M5·) Refrigerant piping intake (knockout hole) Power supply wiring intake (knockout hole ·Ø53·) Control wiring intake (knockout hole ·Ø27·) Drain pipe connection (outside diameter ·Ø26·) 1 3 490 460 (485-495) 2 52 4 5 30 37 170 60 101 150 620 6 7 8 9 40 940 Model RXYSCQ4TMV1B RXYSCQ5TMV1B RXYSCQ6TMV1B AA Ø15.9 Ø15.9 Ø19.1 5 2 1 4 823 3 6 88 9 19 80 69 17 62 59 118 102 104 17 52 19 100 151 7 8 53 95 60 53 95 289 313 6 6 216 20 130 21 89 32 98 3D098107A RXYSQ-TV9 / TY9 RXYSQ-T8V/T8Y 1 140 140 620 30 350 (345~355) M12 320 4 holes for anchor bolts 59 43 30 40 94 Gas pipe connection A 2 Liquid pipe connection Ø9.5 flare 3 (2X) Service port (in the unit) 4 Electronic connection and grounding terminal M5 (in the switch box) 5 Refrigerant piping intake 6 Power supply wiring intake (knockout hole Ø34) 7 Control wiring intake (knockout hole Ø27) 8 Drain outlet 4 Model 900 30 A RMXS112E8V1B 3 2 1 RMXS140E8V1B Ø19.1 brazed connection RMXS160E8V1B Ø19.1 brazed connection RXYSQ4PA7V1B Ø15.9 flared connection RXYSQ5PA7V1B Ø15.9 flared connection RXYSQ6PA7V1B Ø19.1 brazed connection 1345 ERX100A9V1B 7 7 5 117 58 102 70 5 376 191 223 148 55 84 ERX140A9V1B 13 67 5 6 Ø15.9 flared connection GCA125BD4 Ø15.9 flared connection GCA140BD4 Ø19.1 brazed connection RXYSQ4PA7Y1B Ø15.9 flared connection RXYSQ5PA7Y1B Ø15.9 flared connection RXYSQ6PA7Y1B Ø19.1 brazed connection 7 145 16 45 95 80 54 89 142 71 8 19 54 6 19 Ø15.9 flared connection Ø19.1 brazed connection 16 89 24 95 60 423 430 5 Ø15.9 flared connection ERX125A9V1B GCA100BD4 52 55 6 Ø19.1 brazed connection Model A RA indoor unit VRV indoor unit RXYSQ4(P8/T7/T8)V(1)B Ø19.1 brazed connection Ø15.9 flared connection RXYSQ5(P8/T7/T8)V(1)B Ø19.1 brazed connection Ø15.9 flared connection RXYSQ6(P8/T7/T8)V(1)B Ø19.1 brazed connection RXYSQ4(P8/T7/T8)Y(1)B Ø19.1 brazed connection Ø15.9 flared connection RXYSQ5(P8/T7/T8)Y(1)B Ø19.1 brazed connection Ø15.9 flared connection RXYSQ6(P8/T7/T8)Y(1)B Ø19.1 brazed connection 3TW303741E 227 VIEW ALL RXYSQ-TY9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL RXYSQ-TY1 TECHNICAL DRAWINGS ON MY.DAIKIN.EU RXYSQ8TY1 RXYSQ8TY1 30 61 48 320 M12 350 (345-355) 30 4 holes for anchor bolts 44 96 620 160 30 160 940 3 5 1430 4 2 1 8 8 7 6 8 55 13 145 16 16 68 67 151 68 90 52 80 19 142 9 223 19 54 89 89 6 7 84 55 54 95 95 60 6 6 53 95 7 67 1 Gas pipe connection Ø19.1 brazing 2 Liquid pipe connection Ø9.52 brazing 3 Service port (in the unit) High pressure 4 Service port (in the unit) Additional refrigerant charge 5 Grounding terminal 6 Refrigerant piping intake (knockout hole) Inside of the switch box (M5) 47 395 191 7 Power supply wiring intake (knockout hole Ø34) 8 Control wiring intake (knockout hole Ø27) 9 Drain pipe connection (outside diameter Ø26) 3D098108 52 30 460 490 (485-495) 64 49 30 RXYSQ10-12TY1 RXYSQ10-12TY1 97 170 620 150 940 40 5 4 3 2 633 52 95 6 59 118 102 62 228 20 130 21 89 53 154 9 216 100 22 95 6 53 8 7 88 28 60 626 1615 1 98 32 19 80 1 RXYSQ10TMY1B: Gas pipe connection Ø22.2 brazing RXYSQ12TMY1B: Gas pipe connection Ø25.4 brazing 2 RXYSQ10TMY1B: Liquid pipe connection Ø9.52 brazing RXYSQ12TMY1B: Liquid pipe connection Ø12.7 brazing 3 Service port (in the unit) Additional refrigerant charge 4 Service port (in the unit) High pressure 5 Grounding terminal Inside of the switch box (M8) 6 Refrigerant piping intake (knockout hole) 7 Control wiring intake (knockout hole Ø27) 8 Power supply wiring intake (knockout hole Ø53) 9 Drain pipe connection (outside diameter Ø26) 3D098109 VIEW ALL RXYSCQ-TV1 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RXYSCQ-TV1 RXYSCQ-TV1 (B) When there are obstacles on discharge sides. l Required instalation space No obstacle above 1 Stand-alone installation The unit of values is mm. (A) When there are obstacles on suction sides l 500 or more No obstacle above 2 Series installation (2 or more) 1 Stand-alone installation l Obstacle on the suction side only 250 or more 250 or more 100 or more l Obstacle on both sides 1000 or more 100 or more 100 or more 250 or more 500 or less Obstacle above, too 1000 or more l 1 Stand-alone installation 2 Series installation (2 or more) l Obstacle on both sides 500 or more 250 or more 2 Series installation (2 or more) 250 or more 500 or less Obstacle above, too 1 Stand-alone installation l Obstacle on the suction side, too 250 or more 250 or more 1000 or more (C) When there are obstacles on both suction and discharge sides. 500 or less l Obstacle on the suction side, and both sides 1000 or more 100 or more Pattern 1 When the obstacles on the discharge side is higher than the unit. (There is no height limit for obstructions on the intake side.) l No obstacle above 1 Stand-alone installation 150 or more 250 or more 150 or more 100 or more 500 or more 2 Series installation (2 or more) l Obstacle on the suction side, and both sides 2 Series installation (2 or more) 500 or less 1000 or more l 500 or less 300 or more 1000 or more 250 or more 1000 or more 100 or more 250 or more 250 or more 1000 or more 250 or more 300 or more 250 or more 250 or more 300 or more 1000 or more 3D089310A 229 VIEW ALL RXYSCQ-TV1 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RXYSCQ-TV1 RXYSCQ-TV1 2 Series installation Obstacle above, too 500 or less 500 or less The relations between H, A and L are as follows. 1000 or more 1 Stand-alone installation 1000 or more The relations between H, A and L are as follows. Set the stand as: 250 or more 250 or more Set the stand as: Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series. 1000 or more 500 or less The relations between H, A and L are as follows. 250 or more 1000 or more (D) Double-decker installation 1 Obstacle on the discharge side 250 or more Close the gap Z (the gap between the upper an lower outdoor units) to prevent the discharged air from being bypassed. Don not stack more than two units. 1000 or more 2 Obstacle on the suction side 300 or more Pattern 2 Close the gap Z (the gap between the upper an lower outdoor units) to prevent the discharged air from being bypassed. Don not stack more than two units. When the obstacle on the discharge side is lower than the unit: (There is no height limit for obstructions on the intake side.) 250 or more No obstacle above 1 Stand-alone installation 100 or more 500 or more Drain piping construction dimension Close the bottom of the installation frame to prevent the discharged air from being bypassed. 2 Series installation (2 or more) Drain piping construction dimension Set the stand as: Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series. 300 or more (E) Multiple rows of series installation (on the rooftop, etc.) 1 One row of Stand-alone installation 2 Series installation (2 or more) 100 or more The relations between H, A and L are as follows. 250 or more 2000 or more 250 or more 200 or more 2 Rows of series installation (2 or more) 1000 or more The relations between H, A and L are as follows. Obstacle above, too 1500 or more 1 Stand-alone installation Can not be installed The relations between H, A and L are as follows. 500 or less Close the bottom of the installation frame to prevent the discharged air from being bypassed. 250 or more 1000 or more Set the stand as: 250 or more 3000 or more 1000 or more 600 or more 1500 or more 3D089310A 230 VIEW ALL RXYSQ-TV9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL RXYSQ-TY9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RXYSQ-TV9/TY9 RXYSQ-TV1 RXYSQ4-6TY1 (B) When there are obstacles on discharge sides. l Required instalation space No obstacle above 1 Stand-alone installation The unit of values is mm. (A) When there are obstacles on suction sides l No obstacle above 500 or more 2 Series installation (2 or more) 1 Stand-alone installation l Obstacle on the suction side only 100 or more l Obstacle on both sides 1000 or more 100 or more 100 or more 250 or more Obstacle above, too 500 or less 1000 or more l 1 Stand-alone installation 2 Series installation (2 or more) l Obstacle on both sides 500 or more 2 Series installation (2 or more) 500 or less 500 or less Obstacle above, too 1 Stand-alone installation l Obstacle on the suction side, too 1000 or more 300 or more 200 or more 1000 or more (C) When there are obstacles on both suction and discharge sides. 500 or less l Obstacle on the suction side, and both sides 1000 or more 100 or more Pattern 1 When the obstacles on the discharge side is higher than the unit. (There is no height limit for obstructions on the intake side.) l No obstacle above 1 Stand-alone installation 150 or more 250 or more 150 or more 100 or more 500 or more 2 Series installation (2 or more) l Obstacle on the suction side, and both sides 2 Series installation (2 or more) 500 or less 1000 or more l 1000 or more 100 or more 1000 or more 250 or more 300 or more 250 or more 250 or more 300 or more 1000 or more 3D045696D 231 VIEW ALL RXYSQ-TY9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL RXYSQ-TV9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU RXYSQ-TV9/TY9 RXYSQ-TV1 RXYSQ4-6TY1 2 Series installation Obstacle above, too 500 or less 500 or less The relations between H, A and L are as follows. 1000 or more 1 Stand-alone installation 1000 or more The relations between H, A and L are as follows. Set the stand as: 250 or more (D) Double-decker installation 2 Series installation (2 or more) 1 Obstacle on the discharge side Set the stand as: Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series. 300 or more Pattern 2 Close the gap A (the gap between the upper an lower outdoor units) to prevent the discharged air from being bypassed. Don not stack more than two units. 1000 or more 2 Obstacle on the suction side Close the gap A (the gap between the upper an lower outdoor units) to prevent the discharged air from being bypassed. Don not stack more than two units. Drain piping construction dimension 500 or less 1000 or more The relations between H, A and L are as follows. 1500 or more Drain piping construction dimension Set the stand as: Close the bottom of the installation frame to prevent the discharged air from being bypassed. Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series. When the obstacle on the discharge side is lower than the unit: (There is no height limit for obstructions on the intake side.) No obstacle above 1 Stand-alone installation 100 or more 500 or more (E) Multiple rows of series installation (on the rooftop, etc.) 300 or more 1 One row of Stand-alone installation 2 Series installation (2 or more) 100 or more The relations between H, A and L are as follows. 2000 or more 200 or more 2 Rows of series installation (2 or more) 1000 or more The relations between H, A and L are as follows. Obstacle above, too 1 Stand-alone installation 1500 or more Can not be installed The relations between H, A and L are as follows. Set the stand as: Close the bottom of the installation frame to prevent the discharged air from being bypassed. 1000 or more 500 or less 3000 or more 600 or more 1000 or more 1500 or more 3D045696D 232 VIEW ALL RXYSQ-TY1 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RXYSQ-8TY1 RXYSQ8TY1 2. Where there is an obstacle on the discharge side: (a) No obstacle above (1) Stand-alone installation Required installation space The unit of these values is mm. 1. Where there is an obstacle on the suction side: (a) No obstacle above (1) Stand-alone installation 0 50 (2)Series installation (2 or more) (NOTE) • Obstacle on the suction side only 10 mo0 or re re mo or 10 mo0 or re ore rm 0o 10 or 00 10 ore m • Obstacle on both sides (b) Obstacle above, too (1) Stand-alone installation ss r le 0o 1000 or more 50 r 0o 10 ore m 10 mo0 or re (2) Series installation (2 or more) (NOTE) 10 mo0 or re • Obstacle on both sides or 00 10 ore m 10 mo0 or re (2) Series installation (2 or more) (NOTE) 10 mo 00 or re r 0o 30 re mo 20 mo 0 or re 10 mo0 or re ss r le 0o 50 ss r le 0o 50 1000 or more (b) Obstacle above, too (1) Stand-alone installation 10 mo0 or re 1000 or more 10 mo0 or re • Obstacle on the suction side, too or 00 10 ore m r 0o 10 ore m 3.Where there are obstacles on both suction and discharge sides: Pattern 1 • Obstacle on the suction side and both sides 15 mo0 or re r 1000 or more 0o 50 s les Where the obstacle on the discharge side is higher than the unit: (There is no height limit for obstructions on the intake side) (a) No obstacle above (1) Stand-alone installation r 0o 15 ore m 15 mo0 or re or 00 10 ore m (2) Series installation (2 or more) (NOTE) • Obstacle on the suction side and both sides 10 mo0 or re 10 mo 0 or re 10 mo 00 or re NOTE When install the units in a line, have to leave the distance over 100 mm between the two units. ss r le 0o 50 10 mo0 or re 1000 or more 10 mo0 or re (2)Series installation (2 or more) (NOTE) r 0o 10 ore m 20 mo 0 or re r 0o 30 ore m or 00 10 ore m r 0o 30 re mo 3D068442R 233 VIEW ALL RXYSQ-TY1 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RXYSQ-8TY1 RXYSQ8TY1 (2) Series installation (NOTE) The relations between H, A and L are as follows: The relations between H, A and L are as follows: Close the bottom of the installation frame to prevent the discharged air from being bypassed. ore rm Ao (2)Series installation (2 or more) (NOTE) H<L Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series. If the distance exceeds the figure in the ( ), then it’s no need to set the stand. r 0o 50 ess l H<L 10 mo0 or re 4. Double-decker installation (a) Obstacle on the discharge side (NOTE). 10 mo0 or re Close the gap A (the gap between the upper and lower outdoor units) to prevent the discharged air from being bypassed. 1000 or more L≤H r A o re o or m 00 re 5 1 o ) m 00 (22 r 0o 25 ore m The relations between H, A and L are as follows: L A 0 < L ≤ 1/2 H 1000 1/2 H < L ≤ H 1250 Set the stand as: L ≤ H. 10 mo0 or re Do not stack more than two units. Set the board (field supply) as the detail A between two units to prevent the drainage from frozing. Leave the enough space between the layer one and the board. Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series. re o rm Ao Pattern 2 r 0o 30 ore m or 00 10 ore m (b) Obstacle on the suction side (NOTE). Close the gap A (the gap between the upper and lower outdoor units) to prevent the discharged air from being bypassed. 10 mo0 or re Do not stack more than two units. Set the board (field supply) as the detail A between two units to prevent the drainage from frozing. Leave the enough space between the layer one and the board. Where the obstacle on the discharge side is lower than the unit: (There is no height limit for obstructions on the intake side) (a) No obstacle above (1) Stand-alone installation 500 or more H<L 1000 or more L≤ H L≤H L A 0 < L ≤ 1/2H 1000 1/2 H < L≤H 1250 Set the stand as: L≤H r 0o 50 ess l L A 0 < L ≤ 1/2 H 250 1/2 H < L ≤ H 300 Set the stand as: L ≤ H. 1000 or more r 0o 50 ess l 500 or more (b) Obstacle above, too (1) Stand-alone installation r 0o 30 ore m L≤H or 00 10 ore m r 0o 10 ore m 5. Multiple rows of series installation (on the rooftop, etc.) (a) One row of stand-alone installation (2) Series installation (2 or more) (NOTE) The relations between H, A and L are as follows: L 0 < L ≤ 1/2 H 1/2 H < L ≤ H A 250 300 or 00 20 ore m 10 mo0 or re 10 mo0 or re or 00 15 ore m r A o re mo (b) Obstacle above, too (1) Stand-alone installation Close the bottom of the installation frame to prevent the discharged air from being bypassed. If the distance exceeds the figure in the ( ), then it’s no need to set the stand. The relations between H, A and L are as follows: H<L r 0o 50 ess l L A 0 < L ≤ 1/2 H 250 1/2 H < L ≤ H 300 Cannot be installed. 10 mo0 or re 10 mo0 or re 1000 or more H<L L A 0 < L ≤ 1/2 H 100 1/2 H < L ≤ H 200 Set the stand as: L ≤ H. r A o re o or m 0 0 10 ore ) m 00 (17 r 0o 20 ore m (b) Rows of series installation (2 or more) L≤H The relations between H, A and L are as follows: L≤H or 00 10 ore m r 0o 10 ore m 10 mo0 or re 10 mo0 or re 10 mo0 or re ore rm Ao or 00 30 ore m 10 mo0 or re or 00 15 ore m r 0o 60 ore m NOTE When install the units in a line, have to leave the distance over 100 mm between the two units. 234 3D068442R VIEW ALL RXYSQ-TY1 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RXYSQ10-12TY1 RXYSQ10-12TY1 2. Where there is an obstacle on the discharge side: (a) No obstacle above (1) Stand-alone installation Required installation space The unit of these values is mm. 1. Where there is an obstacle on the suction side: (a) No obstacle above (1) Stand-alone installation (2)Series installation (2 or more) (NOTE) • Obstacle on the suction side only 10 mo 0 or re 10 mo 0 or re ore rm 00 10 • Obstacle on both sides (b) Obstacle above, too (1) Stand-alone installation r o 00 10 re mo 10 mo 0 or re (2)Series installation (2 or more) (NOTE) 10 mo 00 or re r 0o 30 re mo 20 mo 0 or re • Obstacle on the suction side, too 10 mo0 or re ss r le 0o 50 ss r le 0o 50 1000 or more (b) Obstacle above, too (1) Stand-alone installation 10 mo0 or re 1000 or more 10 mo 0 or re • Obstacle on both sides ss r le 0o 50 r 0o 10 re mo 10 mo 0 or re (2)Series installation (2 or more) (NOTE) re mo or 1000 or more 0o 10 10 mo 0 or re ore rm 0o 50 or 00 10 ore m r 0o 10 re mo 3.Where there are obstacles on both suction and discharge sides: Pattern 1 15 mo 0 or re 0 50 or s les 1000 or more • Obstacle on the suction side and both sides Where the obstacle on the discharge side is higher than the unit: (There is no height limit for obstructions on the intake side) (a) No obstacle above (1) Stand-alone installation r 0o 15 re mo 15 mo 0 or re r o 00 10 re mo (2)Series installation (2 or more) (NOTE) • Obstacle on the suction side and both sides (2)Series installation (2 or more) (NOTE) 10 mo 0 or re 10 mo 0 or re 10 mo 0 or re 10 mo 00 or re NOTE When install the units in a line, have to leave the distance over 100 mm between the two units. ss r le 0o 50 1000 or more 10 mo 0 or re r 0o 10 re mo 20 mo 0 or re r 0o 30 re mo or 00 10 re mo r 0o 30 re mo 3D083122L 235 VIEW ALL RXYSQ-TY1 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RXYSQ10-12TY1 RXYSQ10-12TY1 (2) Series installation (NOTE) H<L L A 0 < L ≤ 1/2 H 1000 1/2 H < L ≤ H 1250 Set the stand as: L ≤ H. 1000 or more L≤H L≤H Close the bottom of the installation frame to prevent the discharged air from being bypassed. ore rm Ao (2) Series installation (2 or more) (NOTE) H<L Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series. If the distance exceeds the figure in the ( ), then it’s no need to set the stand. r A o re o or m 00 re 5 1 o ) m 00 (22 r 0o 25 ore m r 0o 50 ess l H<L 10 mo0 or re Close the gap A (the gap between the upper and lower outdoor units) to prevent the discharged air from being bypassed. 1000 or more L≤H Close the bottom of the installation frame to prevent the discharged air from being bypassed. Only two units can be installed for this series ore r 0o 30 ore m rm Ao Pattern 2 10 mo0 or re 4. Double-decker installation (a) Obstacle on the discharge side (NOTE). The relations between H, A and L are as follows: L A 0 < L ≤ 1/2 H 1000 1/2 H < L ≤ H 1250 Set the stand as: L ≤ H. 10 mo0 or re 500 or more The relations between H, A and L are as follows: r 0o 50 ess l L A 0 < L ≤ 1/2 H 250 1/2 H < L ≤ H 300 Set the stand as: L ≤ H. 1000 or more r 0o 50 ess l Do not stack more than two units. Set the board (field supply) as the detail A between two units to prevent the drainage from frozing. Leave the enough space between the layer one and the board. or 00 10 ore m (b) Obstacle on the suction side (NOTE). Close the gap A (the gap between the upper and lower outdoor units) to . prevent the discharged air from being bypassed Where the obstacle on the discharge side is lower than the unit: 10 mo0 or re Do not stack more than two units. Set the board (field supply) as the detail A between two units to prevent the drainage from frozing. (There is no height limit for obstructions on the intake side) (a) No obstacle above (1) Stand-alone installation 500 or more (b) Obstacle above, too (1) Stand-alone installation The relations between H, A and L are as follows: Leave the enough space between the layer one and the board. r 0o 30 ore m L≤H or 00 10 ore m r 0o 10 ore m 5. Multiple rows of series installation (on the rooftop, etc.) (a) One row of stand-alone installation (2) Series installation (2 or more) (NOTE) The relations between H, A and L are as follows: L 0 < L ≤ 1/2 H 1/2 H < L ≤ H A 250 300 or 00 20 ore m 10 mo0 or re 10 mo0 or re or 00 15 ore m r A o re mo (b) Obstacle above, too (1) Stand-alone installation Close the bottom of the installation frame to prevent the discharged air from being bypassed. If the distance exceeds the figure in the ( ), then it’s no need to set the stand. (b) Rows of series installation (2 or more) H<L r 0o 50 ess l L A 0 < L ≤ 1/2 H 250 1/2 H < L ≤ H 300 Cannot be installed. 10 mo0 or re 10 mo0 or re 1000 or more H<L L A 0 < L ≤ 1/2 H 100 1/2 H < L ≤ H 200 Set the stand as: L ≤ H. r A o re r mo 0o 0 10 ore ) m 00 (17 r 0o 20 ore m The relations between H, A and L are as follows: L≤H The relations between H, A and L are as follows: L≤H or 00 10 ore m r 0o 10 ore m 10 mo0 or re 10 mo0 or re 10 mo0 or re ore rm Ao or 00 30 ore m 10 mo0 or re or 00 15 ore m r 0o 50 ore m NOTE When install the units in a line, have to leave the distance over 100 mm between the two units. 236 3D083122L VIEW ALL RDXYQ-T TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL RKXYQ-T TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RDXYQ-T(8) RDXYQ-T8 63 239 5 4 149 1044 705 Suspension position 255 62 45 9 (4x) View A 1456 1498 Suspension position 8 1196 7 6 A 27 25 117 298 397 99 26 67 102 2 3 1 659 9 8 7 6 5 4 3 2 1 No. Hook Service door Air discharge side Air suction side Wiring intake (low voltage wiring) Wiring intake (high voltage wiring) Drain outlet Gas pipe connection port Liquid pipe connection port Part name 716 Transmission wiring connection Power supply connection VP25 Ø 19.1 brazing connection Ø 12.7 brazing connection Remark 2D112002 RKXYQ-T(8) SB.RKXYQ-T8 AA Model RKXYQ5T RKXYQ8T 4x AA 600 760 AB AC 426 85 600 78 AD 59 55 AE 55 52 AF 57 55 AG 54 52 AH 337 197 AJ 365 222 17 554 Foundation bolt hole Notes Indoor unit RKXYQ5T : Ø 15.9 brazing connection RKXYQ8T : Ø 19.1 brazing connection 2. Heat exchanger unit RKXYQ5T : Ø 19.1 brazing connection RKXYQ8T : Ø 22.2 brazing connection 1. 118 7 57 View A 101 Indoor unit 8 AF 3 AG 701 6 4 AH 1 AJ Heat exchanger unit 88 2 120 5 AE AD AB Pitch of foundation bolt holes A AC 15 516 Pitch of foundation bolt holes Handle Pipe routing hole Wiring intake (low voltage wiring) 5 Wiring intake (high voltage wiring) 4 Gas pipe connection port 3 Liquid pipe connection port 2 Gas pipe connection port 1 Liquid pipe connection port No. Part name 8 7 6 Knockout hole. Transmission wiring connection Power supply connection See note 1. Ø 9.5 brazing connection See note 2. Ø 12.7 brazing connection Remark 3D098827A 237 Detailed technical drawings VIEW ALL RKXYQ-T TECHNICAL DRAWINGS ON MY.DAIKIN.EU RDXYQ-T(8) 100 or more Air discharge side Air suction side 500 or more 10 or more 100 or more 50 or more 3D098834 RKXYQ-T(8) SB.RKXYQ-T8 10 or more 10 or more 10 or more 10 or more 500 or more RDXYQ-T VIEW ALL RDXYQ-T TECHNICAL DRAWINGS ON MY.DAIKIN.EU Front view Top view 3D098835 238 VIEW ALL RXYLQ-T TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RXMLQ-T - RXYLQ-T RXMLQ-T RXYLQ-T 1 2 Pitch of foundation bolt holes 1076 393 134 107 112 106 160 AA 10 Oblong hole Foundation bolt hole View ·C· 4-15x2 2.5 Detail ·B· Detail ·A· 8 125 70 729 192 AB 310 71 100 E Pitch of foundation bolt holes 3 mm - 11 1685 RXMLQ-T RXYLQ-T 4 For installation in rows 7 9 (FRONT) 76 or more 500 137 765 DETAIL B (Pattern 2) 179 10 or more 20 or more 300 or more 20 or more (FRONT) 500 or more97 107 DETAIL A 10 or more 10 or more 5 C 10 or more 373 Notes 1240 50 or more 100 or more (FRONT) 100 or more 500 or more 500 or brazing more RXMLQ8T E Ø ·19.1· connection RXMLQ-T RXYTQ10T, RXYLQ10T E Ø ·22.2· brazing connection REYQ14-20T Ø ·25.4· brazing connection (Pattern 3) (Pattern 3) RXYLQ-T Wall heightconnection unrestricted E Ø ·28.6· brazing RYYQ14-20T, RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T, RXYTQ12-16T, RXYLQ12-14T Wall height Liquid pipe 300 or more Eunrestricted E RXYTQ10T, RXMLQ8T, RXYLQ10T or moreconnection Ø ·9.5· 300 brazing RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T, RXYTQ12-16T, RXYLQ12-14T Ø ·12.7· brazing connection RYYQ18-20T, RYMQ18-20T, RXYQ18-20T, RXYQQ18-20T Ø ·15.9· brazing connection ForEqualising single unit installation For installation in rows For centralized group layout pipe 400 or more Ø ·22.2· 400 or more (FRONT) (FRONT) RYMQ14-16T brazing connection 200 or more 200 or more RYMQ18-20T Ø ·28.6· brazing connection For single unit installation For installation in rows High pressure/low pressure gas(Pattern pipe 1) (Pattern 1) (Pattern 1) REYQ14-20T Ø ·22.2· brazing connection 300 or more (Pattern 1) 300 or more 300 or(Pattern more 1) 10 or (FRONT) 500 or more more 50 or more (Pattern 1) (Pattern 3) (FRONT) 500 or more (FRONT) 200 or more (Pattern 2) 100 or more (FRONT) 500 or more 10 or more 50 or more 50 or more (FRONT) 200 or more 10 or more 10050orormore more 50 or more (FRONT) 500 or more Wall height unrestricted Wall height unrestricted 400 or more 200 or more more 50 or more 100 or (Pattern 1) more 20 or more 100 or more (Pattern 3) 50 or more or more Wall height300(FRONT) 500 or more 300 or more unrestricted 20 or more 20 or more 10 or more 10 or more (FRONT) 50 or more (FRONT) 400 or more 500 or more 400 or more 200 or more (FRONT) 200 or more NOTES 100 or more 20 or more 10 or more 10 or more 300 or more 2 Gas pipe connection port For centralized group 1 Liquid pipe connection port No. Part name 20 or more 210 10 or more 10 or more 100 or more 10 or more 20 or more 900 or more (Pattern 1) 300 or more 10 or more 10 or more (FRONT) 500 or more 10 or more 10 or more 300 or more 20 or more (FRONT) 100 or more 20 or more 10 or more 10 or more 10 or more 10 or more 20 or more or more 10 or 20 or more 10 or 20 more 20 or10more more or more (FRONT) 10 or more (FRONT) 500 or more 10 or more 50 or more (FRONT) 100 or more 50 or more 50 or more 100 or more more 50 or Wall height unrestricted more 50 or more 300(FRONT) 50 100 or more(FRONT) 50 or more 100 or more or more or more 50 or more 500 or more 500 or more (FRONT) 100 or more 300 or more 100 or more 50 20orormore more 50 or more 100 or more 20 or more 300 or more50 or20more 10 or more (FRONT) or more (FRONT) 10 or more 10 100orormore more (FRONT) (FRONT) 50 or10more 100 or more more 400 or (FRONT) 500 or more or more 400 or 500more or more 600500 or more or more 200 or more 100 or more 50 or more 50 or more 50 or more 100 or more 10 or more 500 or more (FRONT) Ø65 (FRONT) Ø27 100 or more Ø65 500 or more Ø80 Ø65 50 or more 50 or more 100 or more 50 or more 600 or more 300 or more See note ·3·. 100 or more See note ·3·. See note ·3·. Remark 50 or more 50 or more 100 or more (FRONT) 500 or more 50 or more <Unit = mm> 2D079533E 500 or more (FRONT) 500 or more 10 or more 20 or more 10 or more 10 or more 500 or more Inside of the switch box (·M8·) (FRONT) 900 or more 20 or more 500 or more 10 or more 10 or more 10 or more 20 or more 900 or more more 10 or more 500300orormore 20 or more 10 or more 10 or more (Pattern 2) (FRONT) 100 or more 500 or more100 or 20 or more (FRONT) 300 or more 10 or more 10 or more (FRONT) 600 or more 20 or more layout 300 or more (FRONT) 500 or more For centralized group layout 50 or (Pattern 3) (Pattern 3) (FRONT) 500 or more (FRONT) 500 or more (Pattern 2) 50 or more 11 Grounding terminal 10 Pipe routing hole (bottom) E 100 or 100 or9 Pipe routing hole (front) more more8 Power cord routing hole (bottom) 50 or 7 cord routing 50 or more Power (FRONT) 100 orhole more(front)more 50 or more 6 Power 500cord or more routing hole (front) 5 Power cord routing hole (front) 100 or 4 Power cord routing hole (side) more Equalising port 50 or more (FRONT)pipe connection 50 or more 100 or more 3 High 500 pressure/low pressure gas pipe50 or more or more (Pattern 2) 300 or more 10 or more (Pattern 2) (Pattern 3) 300 or more (FRONT) 500 or more 300 or more Wall height unrestricted 300 or more 50 or more 100 or more (Pattern 1) (Pattern 3) 300 or more 10 or more For installation in rows 20 or more (Pattern 2) 100 or more AB 205 240 20 or more (FRONT) 500 or more (FRONT) 100 or more (FRONT) 500 or 500more or more 50 or more 600 or more 50 or more 50 or more 100 or more 500 or more 10 or more 500 or more 50 or more 600 or more 300 or more 10 or more 100 or more 50 or more 50 or more 50 or more 100 or more 900 or (FRONT) more 500 or more (FRONT) 500 or more 50 or more 1. Heights of walls in case of patterns 1 and 2: <Unit = mm> 100Front: or more 1500mm 300 or more <Unit = mm> 20 or more 10 or more 10 or more (FRONT) 10 or more 20 or more 500 or more 10 or more Suction side: 500mm 500 or more 10 or more 20 or more 10 or more (FRONT) Side: Height unrestricted 2) Installation space as shown on (Pattern this drawing is based on the cooling operation at 35 degrees outdoor air temperature. (FRONT)the design 100 or more 50 orair moretemperature exceeds 35 degrees or the load exceeds maximum ability of much generation load of heat in all outdoor unit, take the suction side space more When outdoor 500 or more broadly than the space as shown on this drawing. 100 or 500 or more (FRONT) 100 or more be added to the front and suction side service spaces respectively as shown in the figure on the right. 2. If the above wall heights are more exceeded then h2/2 and h1/2 should 50 be or selected from those shown above in order to obtain the best fit in the Wall installing height unrestricted 3. When the units50most appropriate pattern should or more more 50 or more 50 or more (FRONT) 100 or more 100 or more (FRONT) space available. Always keep in mind the person and wall100and also for the air to 50circulate 50 or more 500 orneed more to leave enough space for a 500 or more to pass between units or more freely. or more 300 or more (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of600short or morecircuits). 100 or 4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably. more 300 or more 3D079542 50 or more (FRONT) 50 or more 100 or more (FRONT) 400 or more 500 or more 50 or more 100 or more 50 or more 50 or more 100 or more (FRONT) 500 or more 50 or more <Suction side> 50 or For single unit installation (FRONT) 10 or 600more or more 10 or more (FRONT) 500 or more (Pattern 2) 100 or more 20 or more 300 or more 10 or more 10 or more 10 or more (Pattern 2) 100 or more 50 or more 20 or more (FRONT) 500 or more 10 or more 10 or more <Front> (Pattern 2) (FRONT) 500 or more 20 or more <Suction side> 10 or 300 or more more (FRONT) 20 or more RXMLQ-T -moreRXYLQ-T 500 or more (FRONT) 600 or more <Front> RXMLQ-T RXYLQ-T 10 or more AA 240 328 100 or more RXMLQ-T 1. Detail ·A· and detail ·B· indicate the dimensions after fixing the attached piping. 50 or 2. Items ·4 - 10:·Knockout hole. RXYLQ-T 50 or more more (FRONT) 3. Gas pipe RYMQ14-16T, RXYQQ14-16T, REYQ14-20T (FRONT) RYMQ18-20T, RXYQQ18-20T 500 or more 272 (Pattern 2) 100 or more Model 300 or more 131 276 10 or more 10 or more 259 300 or more <Suction side> 300 or more 76 (Pattern 1) 122 (Pattern 1) 515 (Pattern 1) For centralized group layout 6 <Front> For single unit installation <Unit = mm> <Suction side> <Front> NOTES 1. Heights of walls in case of patterns 1 and 2: Front: 1500mm Suction side: 500mm NOTES Side: Height unrestricted 1. Heights of walls in case of patterns 1 and 2: Installation space as shown on this drawing is based on the cooling operation at 35 degrees outdoor air temperature. Front: 1500mm When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability of much generation load of heat in all outdoor unit, take the suction side space more Suction side: 500mm broadly than the space as shown on this drawing. Side: Height unrestricted 2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right. Installation space as shown on this drawing is based on the cooling operation atthe 35units degrees air temperature. 3. When installing mostoutdoor appropriate pattern should be selected from those shown above in order to obtain the best fit in the When the design outdoor air temperature exceeds 35 degrees or the available. load exceeds maximum ability of much generation load of in alltooutdoor unit, take space more space Always keep in mind the need to leave enough space forheat a person pass between units the and suction wall and side also for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits). broadly than the space as shown on this drawing. 4. Thebe units should to leave sufficient space atspaces the front for the on site workon to be 2. If the above wall heights are exceeded then h2/2 and h1/2 should added tobe theinstalled front and suction side service respectively asrefrigerant shown in piping the figure thecarried right.out comfortably. 3. When installing the units most appropriate pattern should be3D079542 selected from those shown above in order to obtain the best fit in the space available. Always keep in mind the need to leave enough space for a person to pass between units and wall and also for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits). 4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably. 3D079542 NOTES 1. Heights of walls in case of patterns 1 and 2: Front: 1500mm Suction side: 500mm Side: Height unrestricted Installation space as shown on this drawing is based on the cooling operation at 35 degrees outdoor air temperature. When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability of much generation load of heat in all outdoor unit, take the suction side space more broadly than the space as shown on this drawing. 2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right. 3. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available. Always keep in mind the need to leave enough space for a person to pass between units and wall and also for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits). 3D079542 239 VIEW ALL RQCEQ-P3 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RQCEQ280-360P3 RQCEQ280-360P3 Oblong holes (Pitch of foundation bolt holes) (Pitch of foundation bolt holes) Oblong holes (Foundation bolt holes) (Pitch of foundation bolt holes) (Foundation bolt holes) Outdoor unit 1 Outdoor unit 2 or more SPACE EXAMPLE FOR INSTALLATION (Front) or more Unit: mm Model name RQCEQ280P3 RQCEQ360P3 or more < Suction side > or more < Front > or more or more Outdoor unit 1 RQEQ140P3 RQEQ180P3 Drawing N° 3D066441A 3D066441A Outdoor unit 2 RQEQ140P3 RQEQ180P3 Drawing N° 3D066441A 3D066441A NOTES 1. Heights of walls Front: 1500mm Suction side: 500mm Side: Height unrestricted The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35°C. The installation space of suction side shown above must be expanded in the following case. - Design outdoor temperature becomes over 35°C. - Operating over Max. operating load (In case of causing a heavy heating load at indoor unit side) 2. If the above wall heights are exceeded then h2/2 and h1/2 should be addes tot the front and suction side service spaces respectively as shown in the following figure. 3. When installing the units the most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available alway bearing in mind the need to leave enough room for a person to pass between nuits and wall for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.) 4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out confortably. 3D066856A 240 VIEW ALL RQCEQ-P3 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RQCEQ460-636P3 RQCEQ460-636P3 Oblong holes (Foundation bolt hole) Oblong holes (Pitch of foundation bolt holes) (Pitch of foundation bolt holes) (Pitch of foundation bolt holes) Oblong holes (Foundation bolt hole) (Pitch of foundation bolt holes) (Foundation bolt hole) Outdoor Unit 1 Outdoor Unit 2 Outdoor Unit 3 or more or more SPACE EXAMPLE FOR INSTALLATION < Front > or more or more or more or more < Suction side > or more or more Unit:mm Model name RQCEQ460P3 RQCEQ500P3 RQCEQ540P3 RQCEQ636P3 Outdoor unit 1 RQEQ180P 3 RQEQ180P3 RQEQ180P3 RQEQ212P 3 Drawing N° 3D066441A 3D066441A 3D066441A 3D066441A Outdoor unit 2 RQEQ140P3 RQEQ180P3 RQEQ180P3 RQEQ212P3 Drawing N° 3D066441A 3D066441A 3D066441A 3D066441A Outdoor unit 3 RQEQ140P3 RQEQ140P3 RQEQ180P3 RQEQ212P3 Drawing N° 3D066441A 3D066441A 3D066441A 3D066441A NOTES 1. Heights of walls Front: 1500mm Suction side: 500mm Side: Height unrestricted The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35°C. The installation space of suction side shown above must be expanded in the following case. - Design outdoor temperature becomes over 35°C. - Operating over Max. operating load (In case of causing a heavy heating load at indoor unit side) 2. If the above wall heights are exceeded then h2/2 and h1/2 should be addes tot the front and suction side service spaces respectively as shown in the following figure. 3. When installing the units the most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available alway bearing in mind the need to leave enough room for a person to pass between nuits and wall for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.) 4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out confortably. 3D066860A 241 VIEW ALL RQCEQ-P3 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RQCEQ721-848P3 RQCEQ712-848P3 Oblong holes (Foundation bolt hole) Oblong holes (Foundation bolt hole) A Oblong holes Oblong holes (Pitch of foundation bolt holes) (Pitch of foundation bolt holes) (Pitch of foundation bolt holes) (Foundation bolt hole) (Pitch of foundation bolt holes) (Foundation bolt hole) (Foundation bolt hole) Outdoor Unit 1 Outdoor Unit 2 Outdoor Unit 3 Outdoor Unit 4 or more or more or more SPACE EXAMPLE FOR INSTALLATION or more < Front > or more or more or more or more or more < Suction side > or more Unit: mm Model name RQCEQ712P3 RQCEQ744P3 RQCEQ816P3 RQCEQ848P3 Outdoor unit 1 RQEQ212P3 RQEQ212P3 RQEQ212P3 RQEQ212P3 Drawing N° 3D066441A 3D066441A 3D066441A 3D066441A Outdoor unit 2 RQEQ180P3 RQEQ212P3 RQEQ212P3 RQEQ212P3 Drawing N° 3D0664413 3D0664413 3D0664413 3D0664413 Outdoor unit 3 RQEQ180PA RQEQ180PA RQEQ212PA RQEQ212PA Drawing N° 3D066441A 3D066441A 3D066441A 3D066441A Outdoor unit 4 RQEQ140P3 RQEQ140P3 RQEQ180P3 RQEQ212P3 Drawing N° 3D066441A 3D066441A 3D066441A 3D066441A NOTES 1. Heights of walls Front: 1500mm Suction side: 500mm Side: Height unrestricted The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35°C. The installation space of suction side shown above must be expanded in the following case. - Design outdoor temperature becomes over 35°C. - Operating over Max. operating load (In case of causing a heavy heating load at indoor unit side) 2. If the above wall heights are exceeded then h2/2 and h1/2 should be addes tot the front and suction side service spaces respectively as shown in the following figure. 3. When installing the units the most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available alway bearing in mind the need to leave enough room for a person to pass between nuits and wall for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.) 4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out confortably. 3D066865A 242 VIEW ALL RQYQ-P TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RQYQ140P RQYQ140P (Pitch of foundation bolt holes) 4-15 x 22.5 - mm - Oblong holes (Foundation bolt hole) (Pitch of foundation bolt holes) 4-15 x 22.5 - mm - Oblong holes (Foundation bolt hole) BACK SIDE UP PART (Pitch of foundation bolt holes) (Pitch of foundation bolt holes) RQYQ140P BACK SIDE UP PART DETAIL FOR FRONT SIDE DETAIL FOR FRONT SIDE (knock-out hole) (knock-out hole) DETAIL FOR BOTTOM SIDE (knock-out hole) (knock-out hole) (knock-out hole) DETAIL FOR BOTTOM SIDE (knock-out hole) (knock-out hole) (knock-out hole) No. 1 2 3 4 No. 5 1 6 2 7 3 8 4 9 5 10 6 7 8 9 10 Parts name Liquid pipe connection port Gas pipe connection port Grounding terminal Power cord routing hole (side) Parts name Power cord routing hole (front) Liquid pipe connection port Power cord routing hole (front) Gas pipe connection port Power cord routing hole (bottom) Grounding terminal Wire routing hole (front) Power cord routing hole (side) Pipe routing hole (front) Power cord routing hole (front) Pipe routing hole (bottom) Power cord routing hole (front) Power cord routing hole (bottom) Wire routing hole (front) Pipe routing hole (front) Pipe routing hole (bottom) Remarks ø9.5 Brazing connection See note 3. (knock-out hole) Inside of switch box (M8) ø62 Remarks ø45 ø9.5 Brazing connection ø27 See note 3. ø50 Inside of switch box (M8) ø27 ø62 See note 2. ø45 See note 2. ø27 ø50 ø27 See note 2. See note 2. 3D066442 NOTES 1 shows the dimensions after fixing the accessory pipes. (knock-out hole) 2. For piping connection method (front and bottom sides) see the installation manual. 3 Gas pipe NOTES ø15.9 Brazing connection: RQYQ140P 1 shows the dimensions after fixing the accessory pipes. 3D066442 2. For piping connection method (front and bottom sides) see the installation manual. 3 Gas pipe ø15.9 Brazing connection: RQYQ140P 243 VIEW ALL RQYQ-P TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RQYQ140P 3 For single unit installation < Pattern 1 > For installation in rows < Pattern 1 > 300 or more 300 or more < Front > 10 or more 10 or more 10 or more 500 or more 20 or more 20 or more 20 or more 500 or more 10 or more < Front > < Pattern 2 > < Pattern 2 > 100 or more 100 or more < Front > 50 or more 50 or more 50 or more 500 or more 100 or more 500 or more 100 or more 100 or more 50 or more < Front > < Pattern 3 > < Pattern 3 > Wall heigh unrestricted Wall heigh unrestricted 300 or more 300 or more < Front > 400 or more 200 or more 400 or more 200 or more 400 or more < Front > < Unit : mm > < Unit : mm > For centralized group layout < Pattern 1 > < Pattern 1 > 300 or more < Pattern 1 > 300 or more < Front > < Front > 500 or more < Front > 10 or more 20 or more 10 or more 10 or more 600 or more 20 or more 10 or more 10 or more 20 or more < Front > < Front > 10 or more 500 or more 20 or more 300 or more 10 or more 500 or more 10 or more < Pattern 2 > 10 or more 20 or more 10 or more < Pattern 2 > 100 or more 20 or more 10 or more 900 or more < Front > 10 or more 500 or more < Pattern 2 > 100 or more 500 or more < Front > < Front > < Front > 50 or more 100 or more 50 or more 50 or more 500 or more 100 or more 500 or more 50 or more < Front > 100 or more 50 or more 600 or more 50 or more < Front > 50 or more 100 or more 500 or more 50 or more 100 or more 50 or more 100 or more 50 or more 500 or more 50 or more < Front > 100 or more 50 or more < Unit : mm > 3D066327A NOTES 1. 2. 3. 244 h1 < Suction Side > 500 mm < Front > 1500 mm h2 4. Heights of walls in case of patterns 1 and 2: Front: 1500 mm Suction side: 500mm Side: Height unrestricted. Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature. When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor unit, take the suction side space more broadly than the space to be shown in this drawing. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate freely.. (If more units are to be installed than are catered for in the above patterns your layout should take account to the possibility of short circuits.) The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably. VIEW ALL RWEYQ-T9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings RWEYQ-T9 Top view Bottom view Part name Remark 1 Liquid pipe 2 Suction pipe 3 2 See table 1. See table 2. See table 3. External pipe thread ISO 228-G1 1/4 B External pipe thread ISO 228-G1 1/4 B Flexible hose (inside diameter: Ø 10mm) M8 Ø 25 Ø 25 3 Gas pipe 4 Water IN connection 1 7 Grounding terminal 8 Power supply wiring intake 25 74 79 5 Water OUT connection 6 Drain outlet 88 9 Cable inlet 9 134 179 516 Item 600 80.5 80.5 8 224 Foundation bolt type: 4x Ø17 269 Right-side view Front view Rear view 560 476 980 5 Manufacturer label 92 4 88 7 288 6 767 Table 1 RWEYQ8T9 Model Operation mode Liquid pipe Suction pipe Gas pipe (high/low pressure) Heat pump Heat recovery Heat recovery Ø 9.5 Ø 22.2 Ø 19.1 Ø 19.1 Ø 19.1 Ø 15.9 RWEYQ12T9 RWEYQ10T9 Heat pump Ø 9.5 Ø 22.2 Heat pump RWEYQ14T9 Heat pump Heat recovery Ø 28.6 Heat recovery Ø 12.7 Ø 12.7 Ø 28.6 Ø 28.6 Ø 19.1 Ø 28.6 Ø 22.2 Notes 1. The grounding terminal is located in the switch box. 2. The pipe connections are brazed connections. 3. In case of a heat pump, the suction pipe is not used. 2D108932A RWEYQ-T9 Service space (Front) 2 11-13/16 (300) or more 2 11-13/16 (300) or more 13-3/4 (350) or less 11-13/16 (300) or more 2 11-13/16 (300) or more Water piping installation space 35-7/16 (900) or more Outside unit Service space (Rear) Outside unit Outside unit Service space (Front) Service space (Front) 13/16 (20) or more 13/16 20) or more 13-3/4 (350) or less Service space (Rear) 35-7/16 (900) or more For installation in rows 2 11-13/16 (300) or more Service space (Rear) 2 11-13/16 (300) or more 19-11/16 (500) or more For single unit installation 2 11-13/16 (300) or more 19-11/16 (500) or more RWEYQ-T9 13/16 (20) or more 13/16 (20) or more : Required Service Space : Ventilation Space Water piping installation space Front view 3-15/16 (100) or more 9-13/16 (250) or less Right side view Unit: in. (mm) NOTES 1. This space is necessary when refrigerant piping is connected to the top of the unit. 2. This ventialition space is necessary when heat rejection cancellation (Zero energy sissipation) is not active. 3D109304B 245 Technical drawings Indoor units FXFA-A / FXFQ-B 247 FXZA-A / FXZQ-A 249 FXCQ-A250 FXKQ-MA252 FXDA-A / FXDQ-A3 253 FXSA-A / FXSQ-A 258 FXMQ-P7 / FXMQ-MB 266 FXAQ-A272 FXHQ-A274 FXUQ-A275 FXNQ-A276 FXLQ-P280 FTXJ-MW - FTXJ-MS 282 C/FTXA-AW/BS/BT/BB283 FVXG-K284 FVXM-F285 246 VIEW ALL FXFA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXFQ-B TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXFA-A / FXFQ-B WITH STANDARD PANEL FXFQ-B Notes 1. Location of nameplate The unit nameplate is located on the control box cover. The decoration panel nameplate is located on the piping-side panel frame, under the corner cover. 2. When installing optional accessories, refer to their respective documentation. 3. Make sure the distance between the ceiling and the cassette does not exceed ·35·mm. The maximum ceiling opening is ·910·mm. 4. When the conditions in the ceiling exceed 30°C ambient temperature and 80% relative humidity, or when fresh air is inducted into the ceiling, additional insulation is required (polyethylene foam, thickness ≥·10·mm) 5. When installing a sensor kit, there will be a sensor on this location. For details, see the drawing of the sensor kit. 6. When installing a wireless controller, there will be a receiver on this location. For details, see the drawing of the wireless controller. 7 ·300· or less 6 See note ·5·. 8 420 A 860-910 Air fan 100 81 100 81 85 Suspension bolt 100 100 85 100 100 350 121.5 25.4 80 FCAG35/50/60/71BVEB FXFQ20/25/32/40/50/63BVEB FCAG100/125/140BVEB FCAHG71/100/125/140HVEB FXFQ80/100/125BVEB ARROW VIEW C Item Name Respect the distances shown on the figure. Ceiling-mounted lighting 80 80 330 350 121.5 95 110 40 280 4 - M8 OR M10 DETAIL B ·2· places Opposite side 121.5 96.5 54.5 54.5 0-675 175 10 Required installation space 130 2D121655 ·2700· or more 35 See note ·3·. DETAIL B ·2· places Opposite side 350 2 53 67 4 1 3 AA 340 150 Adjustable 55 5 FCAG100/125/140BVEB FCAHG71/100/125/140HVEB FCAG35/50/60/71BVEB FXFQ80/100/125BVEB FXFQ20/25/32/40/50/63BVEB 950 840 See note ·3·. B 35 See note ·3·. 100 80 Suspension position 96.5 95 Piping side See note ·6·. C 25.4 350 121.5 10 AB 840 100 950 213 780 Ceiling opening Ø75 710 55 67 53 54.5 54.5 96.5 420 Ceiling opening DETAIL A ·2· places Opposite side 96.5 See note ·3·. DETAIL A ·2· places Opposite side 860-910 Suspension position 9 Drain side 1 Liquid pipe connection port Gas pipe connection port Drain pipe connection 4 Power supply wiring intake 5 Transmission wiring intake hole 6 Air discharge outlet 7 Air suction grille 8 Corner decoration cover 9 Drain hose 10 Knockout hole. ·1500· or more 2 3 ·200· or more Other unit ·1500· or more ·1500· or more ·200· or more ·1500· or more ·2000· or more ·4000· or more ·1500· or more Required installation space If a discharge outlet is closed up with the "sealin g member" option kit, then the required installation space on that (closed up) side is ·500·mm instead of ·1500·mm. 2D121655 FXFA-A / FXFQ-B WITH AUTO CLEANING PANEL FXFQ-B Notes 1. Location of nameplate FXFQ-B The unit nameplate is located on the control box cover. decoration panel nameplate is located on the piping-side panel frame, under the corner cover. 1.The Location of nameplate 2. When installing optional referbox to their The unit nameplate is locatedaccessories, on the control cover.respective documentation. 3. Make sure the distance between the ceiling andpiping-side the cassette doesframe, not exceed The decoration panel nameplate is located on the panel under·35·mm. the corner cover. maximum ceiling opening is ·910·mm. 2.The When installing optional accessories, refer to their respective documentation. When thethe conditions the ceiling ambient temperature and 80% relative humidity, or when fresh air is inducted into the ceiling, additional insulation is required (polyethylene foam, thickness ≥·10·mm). 3.4.Make sure distancein between theexceed ceiling 30°C and the cassette does not exceed ·35·mm. 5. When installing a sensor kit,isthere will be a sensor on this location. For details, see the drawing of the sensor kit. The maximum ceiling opening ·910·mm. 4. When the conditions in the ceiling exceed 30°C ambient temperature and 80% relative humidity, or when fresh air is inducted intoSee the note ceiling, foam, thickness ≥·10·mm). 6 (polyethylene ·5·.additional insulation is7required ·300· or less Drain side 8 420 5. When installing a sensor kit, there will be a sensor on this location. For details, see the drawing of the sensor kit. Air fan Other unit Ceiling-mounted lighting (*2) (*2) Other unit Air fan (*1) (*3) 256 (*1) ·1500· or more (*3) 256 ·2000· or more ·1500· ·4000· or moreor more ·2000· or more 10° 10° ·4000· or more 10° 10° (*1)Not applicable to recessed lighting. (*2)Required space for entering with vacuum cleaner tube. (*3)Make sure theto decoration panel discharge outlet is not blocked. (*1)Not applicable recessed lighting. (*2)Required space for entering with vacuum cleaner tube. (*3)Make sure the decoration panel discharge outlet is not blocked. 35 See note ·3·. 35 See note ·3·. 950 950 280 C 4 - M8 OR M10ARROW VIEW 330 Suspension ·1500· bolt or more ·200· or more ARROW VIEW C ·1500· or more ·1500· or more or more ·1500· ·200· or more ·1500· or more·200· or more ·1500· or more 81 81 Piping Piping Air suction grille Installation direction Air suction grille Installation direction 100 100 85 80 85 DETAIL B Item Name ·2· places DETAIL B Opposite side ·2· places 350 121.5 Opposite side Required installation space Piping 100 100 FCAG100/125/140BVEB FCAHG71/100/125/140HVEB FXFQ80/100/125BVEB FCAG100/125/140BVEB FCAHG71/100/125/140HVEB FXFQ80/100/125BVEB ·200· or more Piping 350 350 121.5 121.5 25.4 25.4 350 121.5 ·1500· or more ·1500· or more If a discharge outlet is closed up with the "sealing member" option kit, then the required installation space on that (closedinstallation up) side is ·500·mm Required space instead of ·1500·mm. Dust If a discharge outlet is closed up with theopening "sealing member" option kit, then the required installation space on that (closed up) side is ·500·mm instead of ·1500·mm. Dust opening 80 80 2 2 280 330 FCAG35/50/60/71BVEB FCAG100/125/140BVEB 95 FCAHG71/100/125/140HVEB FXFQ20/25/32/40/50/63BVEB FXFQ80/100/125BVEB FCAG35/50/60/71BVEB FCAG100/125/140BVEB FXFQ20/25/32/40/50/63BVEB FCAHG71/100/125/140HVEB FXFQ80/100/125BVEB ·2· places DETAIL B Opposite side ·2· places 350 121.5 Opposite side 95 1 100 100 100 80 80 100 350 350 121.5 121.5 25.4 25.4 4 - M8 OR M10 Suspension bolt 1 4 4 67 96.5 53 80 213 213 840 340 ·2·67 places 96.5 53 Opposite side 95 5 5 3 3 DETAIL B 950 840 95 Piping side 1 Liquid pipe connection port Item Name 350 121.5 81 81 100 100 100 100 7 Ceiling-mounted lighting B Piping side 950 85 85 53 753 96.5 96.5 67 67 35 See note ·3·. 35 See note ·3·. AB AB 54.5 54.5 96.5 54.5 96.5 54.5 B C C 55 840 Ø75 340 ·2· places DETAIL OppositeAside 54.554.5 96.5 Ø7510 10 DETAIL A ·2· DETAIL places A Opposite side ·2· places 54.554.5 96.5 Opposite side 190 190 230 230 55 A AA AA 90 255 2550-6750-675 Adjustable Adjustable 420 710 Suspension position 420 860-910 710 Ceiling openingposition See note ·3·. Suspension 860-910 55 840 55 Ceiling opening See note ·3·. Drain side 8 DETAIL A 90 40 9 6 A 40 9 7 100 100 100 100 80 80 See note ·5·. 420 780 780 Suspension position Suspension position 860-910 860-910 See note CeilingCeiling opening See·3·. note ·3·. opening ·300· or less 210 210 Required installation space space Required installation ·2700··2700· or more or more Notes FCAG35/50/60/71BVEB FXFQ20/25/32/40/50/63BVEB FCAG35/50/60/71BVEB FXFQ20/25/32/40/50/63BVEB 2 13 24 35 46 57 68 79 810 9 10 Gas pipe connection port Liquid Drain pipe pipe connection port Gas pipesupply connection Power wiringport intake Drain pipe connection Transmission wiring intake hole Power supply wiring Air discharge outlet intake Transmission wiring intake hole Air suction grille Air discharge outlet cover Corner decoration Air suction Drain hosegrille Corner decoration Knockout hole. cover Drain hose Knockout hole. 2D121658 2D121658 247 VIEW ALL FXFA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL FXFQ-B TECHNICAL DRAWINGS ON MY.DAIKIN.EU FXFA-A / FXFQ-B WITH DESIGNER PANEL FXFQ-B Notes 1. Location of nameplate The unit nameplate is located on the control box cover. The decoration panel nameplate is located on the piping-side panel frame, under the corner cover. 2. When installing optional accessories, refer to thei r respective documentation. 3. Make sure the distance between the ceiling and the cassette does not exceed ·35·mm. The maximum ceiling opening is ·910·mm. 4. When the conditions in the ceiling exceed 30°C ambient temperature and 80% relative humidity, or when fresh air is inducted into the ceiling, additional insulation is required (polyethylene foam, thickness ≥·10·mm). 5. When installing a sensor kit, there will be a sensor on this location. For details, see the drawing of the sensor kit. 6. When installing a wireless controller, there will be a receiver on this location. For details, see the drawing of the wireless controller. 7 6 ·300· or less See note ·5·. 8 Drain side DETAIL A ·2· places Opposite side A 35 See note ·3·. Air fan 100 350 121.5 25.4 100 80 80 DETAIL B ·2· places Opposite side 80 DETAIL B ·2· places Opposite side 350 121.5 350 121.5 100 81 100 53 67 95 152 192 2 280 330 4 - M8 ORM10 Suspension bolt 81 85 FCAG100/125/140BVEB FCAHG71/100/125/140HVEB FXFQ80/100/125BVEB ARROW VIEW C 100 100 85 FCAG35/50/60/71BVEB FXFQ20/25/32/40/50/63BVEB Item Name Respect the distances shown on the figure. Ceiling-mounted lighting 1 AA 4 FCAG35/50/60/71BVEB FXFQ20/25/32/40/50/63BVEB FCAG100/125/140BVEB FCAHG71/100/125/140HVEB FXFQ80/100/125BVEB 96.5 5 340 3 96.5 54.554.5 35 See note ·3·. 840 172 ·2700· or more Required installation space 217 0-675 45 52 Adjustable C 100 95 Piping side 950 See note ·6·. 55 67 96.5 53 80 10 AB B 100 350 121.5 25.4 950 Ø75 420 710 Suspension position 860-910 See note ·3·. Ceiling opening 55 840 DETAIL A ·2· places Opposite side 54.554.5 96.5 213 9 860-910 See note ·3·. Ceiling opening 780 Suspension position 420 ·1500· or more Liquid pipe connection port Gas pipe connection port Drain pipe connection Power supply wiring intake Transmission wiring intake hole Air discharge outlet Flat grille assembly Corner decoration cover Drain hose Knockout hole. 1 2 ·200· or more Other unit 3 ·1500· or more ·1500· or more 4 5 ·200· or more ·1500· or more ·2000· or more ·4000· or more 6 ·1500· or more 7 Required installation space 8 9 10 If a discharge outlet is closed up with the "sealing member" option kit, then the required installation space on that (closed up) side is ·500·mm instead of ·1500·mm. 2D121703 FXFA-A / FXFQ-B WITH FRESH AIR INTAKE FXFQ-B 55 Duct 840 Left side Piping side 328 427 840 328 427 See note ·3·. See note ·3·. (1000) 0 1 4 5 3 6 Inlet Ø148 A 207 317 725 Suction chamber 455 1. When installing a fresh air intake kit, provide a service access panel. Designer decoration panel Ceiling opening 2. Field construction 3. This corner discharge outlet needs to be closed. 4. When installing a duct fan, use a wiring adapter to link the duct fan to the fan of the indoor unit. 5. The intake air flow rate is recommended to be ≤20% of the air flow rate at high fan speed. If the intake air flow rate is too large, the operating sound may increase, and the detection of the indoor unit suction temperature may be affected. 6. This indicates the distance between the T-joint inlet and the indoor unit inlet when the T-tube is connected. 248 2 Air flow rate [m³/min] T-joint Field supply 455 Ceiling opening AB Suction chamber Decoration panel Duct View ·A· Service access panel Right side ·450 x 450 mm· or more See note ·1·. 140 130 120 110 100 90 80 70 60 50 40 30 20 10 165 275 AA 448 508 Ø148 Drain side Static pressure in chamber [Pa] 55 Notes AB Model name FCAG35/50/60/71BVEB FXFQ20/25/32/40/50/63BVEB FCAG100/125/140BVEB 306 348 FXFQ80/100BVEB FCAHG71/100/125/140HVEB 348 390 FXFQ125BVEB AA 264 306 3D121741 VIEW ALL FXZA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXZQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXZA-A / FXZQ-A NEW PANEL FXZQ-A Decoration panel 585-595 (Ceiling opening space) Fresh white N9.5 Daikin Silver 300 or less 533 (Suspension position) Service access panel 450x450mm or more 533 (Suspension position) Pipe connection side 585-595 (Ceiling opening space) BYFQ60C2W1W BYFQ60C2W1S Drain connection side A Arrow view 4-M4 Hole Outdoor air intake (direct connection) B Arrow view • Required space Note) 2. 1500 mm or more 1500 mm or more 1500 mm or more 1500 mm or more Adjustable (0-630) When the discharge grill is closed, the required space is 200mm or more Notes: 1. Sticking locations for manufacturer`s label Manufacturer`s label for indoor unit: on the bell mouth inside suction grille. Manufacturer`s label for decoration panel: on the inner frame inside suction grille. 2. In case of using infrared remote controller, this position will be a signal receiver. Refer tot the drawing of infrared remote controller in detail. 3. When the temperature and humidity in the ceiling exceed 30ºC and RH 80%, or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more, Glasswool or polyethylene foam) is required. 4. Though the installation is acceptable up to maximum of 595mm square ceiling opening, keep the clearance of 10mm or less between the main unit and the ceiling opening so that the panel overlap allowance can be ensured. For height installation 10 or less Note ) 4. 1500 mm or more 10 or less Suspension bolt Required space From the floor 2500 or more 300 mm or more C Arrow view 1 Liquid piping connection ø 6.4 Flare connection 2 Gas piping connection ø 12.7 Flare connection 3 Drain piping connection VP20 (O.D. ø 26) 4 Power supply connection 5 Remote control code and wiring connection 6 Air discharge grille 7 Suction grill 8 Drain hose (accessory) I.D. ø 25 Outlet 3D082052 FXZA-A / FXZQ-A OLD PANEL Decoration panel 585-660 (Ceiling opening space) 300 or less Pipe connection side 533 (Suspension posotion) Drain connection side 585-660 (Ceiling opening space) 533 (Suspension posotion) Service access panel 450x450mm or more 4-M4 Hole Outdoor air intake (direct connection) B Arrow view • Required space 1500 mm or more A Arrow view Note) 2. 1500 mm or more 1500 mm or more 1500 mm or more Notes: 1. Sticking locations for manufacturer’s label Manufacturer’s label for indoor unit: on the bell mouth inside suction grille. Manufacturer’s label for decoration panel: on the inner frame inside suction grille. 2. In case of using infrared remote controller, this position will be a signal receiver. Refer tot the drawing of infrared remote controller in detail. 3. When the temperature and humidity in the ceiling exceed 30ºC and RH 80%, or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more, Glasswool or polyethylene foam) is required. 4. Though the installation is acceptable up to maximum of 660mm square ceiling opening, keep the clearance of 45 mm or less between the main unit and the ceiling opening so that the panel overlap allowance can be ensured. 1 Liquid piping connection ø 6.4 Flare connection 2 Gas piping connection ø 12.7 Flare connection 3 Drain piping connection VP20 (O.D. ø 26) 4 Power supply connection 5 Remote control code and wiring connection 6 Air discharge grille 7 Suction grill 8 Drain hose (accessory) I.D. ø 25 Outlet For height installation Note ) 4. From the floor 2500 or more Suspension bolt 45 or less 1500 mm or more 45 or less Required space 295 mm or more Adjustable (0-645) C Arrow view When the discharge grill is closed, the required space is 200mm or more 3D082161A 249 VIEW ALL FXCQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXCQ20-40A Branch duct connection 520 (Hanger bolt pitch) 640 (Ceiling opening) FXCQ20-40A CL 820 (Hanger bolt pitch) B View 1030 (Ceiling opening) 300 or less Hanger bolt (Knock hole) Fresh air intake 2500 or more 4-M4 Hole (Circumference) Suction space 1000 or more 355 or more Adjustable Branch duct connection Pitch center diameter ø 176 CL Notes: Required space Floor line 1500 mm or more 1. Sticking locations for manufacturer`s label Manufacturer`s label for indoor unit: Suction panel inner side`s control box lid surface Manufacturer`s label for decoration panel: Suction panel inner side`s panel frame surface 2. When installing an optional accessory, refer to the installation drawings. 3. In case of using infrared remote controller, this position will be a signal receiver. Refer tot the drawing of infrared remote controller in detail. 4. When the temperature and humidity in the ceiling exceed 30ºC and RH 80%, the additional insulation is required. Insulation: Thickness 10mm or more, Glass wool or polyethylene foam. 5. Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall. 1500 mm or more Brand name plate (Note 3) A View 100 mm or more 1 Liquid piping connection ø 6.4 mm Flare connection 2 Gas piping connection ø 12.7 mm Flare connection 3 Drain piping connection VP25 (O.D. ø 32, I.D. ø 25) 4 Wiring penetrating hole 5 Air outlet 6 Air inlet 7 Drain Hose (Accesory) 8 Suction panel O.D. ø 32 (Main body side connection : O.D. ø 26) 3D079628 FXCQ50A Branch duct connection 520 (Hanger bolt pitch) 640 (Ceiling opening) FXCQ50A CL 1035 (Hanger bolt pitch) B View 1245 (Ceiling opening) 300 or less Hanger bolt (Knock hole) Fresh air intake CL Notes: 1. Sticking locations for manufacturer`s label Manufacturer`s label for indoor unit: Suction panel inner side`s control box lid surface Manufacturer`s label for decoration panel: Suction panel inner side`s panel frame surface 2. When installing an optional accessory, refer to the installation drawings. 3. In case of using infrared remote controller, this position will be a signal receiver. Refer tot the drawing of infrared remote controller in detail. 4. When the temperature and humidity in the ceiling exceed 30ºC and RH 80%, the additional insulation is required. Insulation: Thickness 10mm or more, Glass wool or polyethylene foam. 5. Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall. 2500 or more 4-M4 Hole (Circumference) Suction space 1000 or more 355 or more Adjustable Branch duct connection Pitch center diameter ø 176 Required space Floor line 1500 mm or more Brand name plate (Note 3) 1500 mm or more A View 1 Liquid piping connection ø 6.4mm Flare connection 2 Gas piping connection ø 12.7 mm Flare connection 3 Drain piping connection VP25 (O.D. ø 32, I.D. ø 25) 4 Wiring penetrating hole 5 Air outlet 6 Air inlet 7 Drain Hose (Accesory) 8 Suction panel 100 mm or more O.D. ø 32 (Main body side connection : O.D. ø 26) 3D079629 250 VIEW ALL FXCQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXCQ63A Branch duct connection 520 (Hanger bolt pitch) 640 (Ceiling opening) FXCQ63A CL 1035 (Hanger bolt pitch) B View 1245 (Ceiling opening) 300 or less Hanger bolt (Knock hole) Fresh air intake 2500 or more 4-M4 Hole (Circumference) Suction space 1000 or more 355 or more Adjustable Branch duct connection Pitch center diameter ø 176 CL Notes: Required space Floor line 1. Sticking locations for manufacturer`s label Manufacturer`s label for indoor unit: Suction panel inner side`s control box lid surface Manufacturer`s label for decoration panel: Suction panel inner side`s panel frame surface 2. When installing an optional accessory, refer to the installation drawings. 3. In case of using infrared remote controller, this position will be a signal receiver. Refer tot the drawing of infrared remote controller in detail. 4. When the temperature and humidity in the ceiling exceed 30ºC and RH 80%, the additional insulation is required. Insulation: Thickness 10mm or more, Glass wool or polyethylene foam. 5. Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall. 1500 mm or more Brand name plate (Note 3) A View 1500 mm or more 100 mm or more 1 Liquid piping connection ø 9.5mm Flare connection 2 Gas piping connection ø 15.9 mm Flare connection 3 Drain piping connection VP25 (O.D. ø 32, I.D. ø 25) 4 Wiring penetrating hole 5 Air outlet 6 Air inlet 7 Drain Hose (Accesory) 8 Suction panel O.D. ø 32 (Main body side connection : O.D. ø 26) 3D079630 FXCQ80-125A Branch duct connection 520 (Hanger bolt pitch) 640 (Ceiling opening) FXCQ80-125A CL 820 (Hanger bolt pitch) 1030 (Ceiling opening) B View 300 or less Hanger bolt (Knock hole) Fresh air intake CL Required space Floor line Notes: 1. Sticking locations for manufacturer`s label Manufacturer`s label for indoor unit: Suction panel inner side`s control box lid surface Manufacturer’s label for decoration panel: Suction panel inner side`s panel frame surface 2. When installing an optional accessory, refer to the installation drawings. 3. In case of using infrared remote controller, this position will be a signal receiver. Refer tot the drawing of infrared remote controller in detail. 4. When the temperature and humidity in the ceiling exceed 30ºC and RH 80%, the additional insulation is required. Insulation: Thickness 10mm or more, Glass wool or polyethylene foam. 5. Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall. 2500 or more 4-M4 Hole (Circumference) Suction space 1000 or more 355 or more Adjustable Branch duct connection Pitch center diameter ø 176 1500 mm or more Brand name plate (Note 3) A View 1500 mm or more 100 mm or more 1 Liquid piping connection ø 9.5 mm Flare connection 2 Gas piping connection ø 15.9 mm Flare connection 3 Drain piping connection VP25 (O.D. ø 32, I.D. ø 25) 4 Wiring penetrating hole 5 Air outlet 6 Air inlet 7 Drain Hose (Accesory) 8 Suction panel O.D. ø 32 (Main body side connection : O.D. ø 26) 3D079631 251 VIEW ALL FXKQ-MA TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXKQ25, 32, 40MA FXKQ25,32,40MA Required installation space 1,500 mm or more 200 mm or more 200 mm or more 760 (Ceiling opening) 350 (Suspension position) 20 mm or more Nr. 1 1,150 (Suspension position) 1,200 (Ceiling opening) Front discharge duct position 1,000 or more Suspension bolt Required installation space 4-M4 hole Name Liquid pipe connection Description ø 6.4 Flare connection 2 Gas pipe connection ø 12.7 Flare connection 3 Drain pipe connection VP25 (O.D. ø 32) 4 Wire intake 5 Interunit wiring connection 6 Grounding terminal 7 Discharge 8 Air suction grille 9 Long life filter 10 Suspension bolt Inside switch box (M4) NOTES 1 Location of unit’s name plate: • For main body: Bottom part of fan housing inside of air suction grille. • For decoration panel: Service lid face inside of air suction grille. 2 When installing an optional accessory, refer to the installation drawings. 3D038840 FXKQ63MA FXKQ63MA Required installation space 1,500 mm or more 200 mm or more 200 mm or more 760 (Ceiling opening) 350 (Suspension position) 20 mm or more Nr. 1 1,350 (Suspension position) 1,400 (Ceiling opening) Front discharge duct position 1,000 or more Suspension bolt (Required installation space) 6-M4 hole Name Liquid pipe connection Description ø 9.5 Flare connection ø 15.9 Flare connection 2 Gas pipe connection 3 Drain pipe connection 4 Wire intake 5 Interunit wiring connection 6 Grounding terminal 7 Discharge 8 Air suction grille 9 Long life filter 10 Suspension bolt VP25 (O.D. ø 32) Inside switch box (M4) NOTES 1 2 Location of unit’s name plate: • For main body: Bottom part of fan housing inside of air suction grille. • For decoration panel: Service lid face inside of air suction grille. When installing an optional accessory, refer to the installation drawings. 3D038841 252 VIEW ALL FXDA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXDQ-A3 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXDQ15-32A3 FXDA15-32A FXDQ15-32A 300 or more 300 or more 240 or more 20 or more (Suspension bolt pitch) 20 or more (Service space) (Service space of installation box for adapter PCB) 400 or more (In case of bottom-suction) Ceiling Service space 16x ø 4,7 holes 300 or more Adjustable (0-600) (Suspension bolt pitch) Suspension bolt View A Inspection door (ceiling opening) 16xM5 holes 14xM4 holes In case of back suction Notes: 1 2 3 4 5 6 7 8 9 10 11 16xM5 holes Liquid pipe connection Gas pipe connection Drain pipe connection Drain hose (accesory) control box Transmisiion wiring connection Power supply connection Suspension bracket Inspection cover Socket for drain Air filter (accessory) ø 6.4 Flare connection ø 12.7 Flare connection VP20 (O.D. ø 26, I.D. ø 20) ID ø 25 (Outlet) In case of bottom-suction 1. In case of back-suction, mount chamber cover to botttom side of the unit. In case of bottom-suction, mount chamber cover to back side of the unit. 2. Locations of unit`s name plate: control box cover. 3. Mount the air filter at the suction side. (Use an air filter whose dust collecting efficiency is at least 50% in a gravimetric technique). It can not be equipped with air filter (accessory) when connecting duct to suction side. 3D081435 FXDQ40-50A3 FXDA40-50A FXDQ40-50A 300 or more 400 or more (In case of bottom-suction) 240 or more 20 or more (Suspension bolt pitch) (Service space) 20 or more 300 or more (Service space of installation box for adapter PCB) Ceiling Service space Adjustable (0-600) 22 x ø 4,7 hole (Suspension bolt pitch) View A Inspection door (ceiling opening) 300 or less Suspension bolt 20xM5 holes 18xM4 holes In case of back suction Notes: 20xM5 holes In case of bottom-suction 1 2 3 4 5 6 7 8 9 10 11 Liquid pipe connection Gas pipe connection Drain pipe connection Drain hose (accesory) control box Transmission wiring connection Power supply connection Suspension bracket Inspection cover Socket for drain Air filter (accessory) ø 6.4 Flare connection ø 12.7 Flare connection VP20 (O.D. ø 26, I.D. ø 20) ID ø 25 (Outlet) 1. In case of back-suction, mount chamber cover to botttom side of the unit. In case of bottom-suction, mount chamber cover to back side of the unit. 2. Locations of unit`s name plate: control box cover. 3. Mount the air filter at the suction side. (Use an air filter whose dust collecting efficiency is at least 50% in a gravimetric technique). It can not be equipped with air filter (accessory) when connecting duct to suction side. 3D081436 253 VIEW ALL FXDA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL FXDQ-A3 TECHNICAL DRAWINGS ON MY.DAIKIN.EU FXDQ63A3 FXDA63A FXDQ63A 300 or more 300 or more (Service space of installation box for adapter PCB) 240 or more 20 or more 20 or more (Suspension bolt pitch) (Service space) 400 or more (In case of bottom-suction) Ceiling 26x ø 4,7 holes Service space View A Inspection door (ceiling opening) (Suspension bolt pitch) Adjustable (0-600) 300 or less Suspension bolt 24xM5 holes 18xM4 holes In case of back suction 24xM5 holes 1 2 3 4 5 6 7 8 9 10 11 In case of bottom-suction Liquid pipe connection Gas pipe connection Drain piping connection Drain hose (accesory) control box Transmission wiring connection Power supply connection Suspension bracket Inspection cover Socket for drain Air filter (accessory) ø 9.5 Flare connection ø 15,9 Flare connection VP20 (O.D. ø 26, I.D. ø 20) ID ø 25 (Outlet) Notes: 1. In case of back-suction, mount chamber cover to bottom side of the unit. In case of bottom-suction, mount chamber cover to back side of the unit. 2. Locations of unit’s name plate: control box cover. 3. Mount the air filter at the suction side. (Use an air filter whose dust collecting efficiency is at least 50% in a gravimetric technique). It can not be equipped with air filter (accessory) when connecting duct to suction side. 3D081441 FXDQ15A3 FXDQ15A3 FXDA15A 40 35 SP fE External static pressure [Pa] 30 it o m li er Hi gh p Up 25 Hi gh Hi gh ES P ES P ES P 20 P 15 f ES it o SP r lim d E pe ar Up Stand P SP h ES Hig it of E r lim e Low an nd da rd ES P ES P 5 ard ES Sta rd da an St St 10 P 0 6 6.5 7 7.5 8 8.5 9 Air flow rate [m³/min] Notes The remote controller can be used to switch between 'high' and 'low'. The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP' and 'high ESP' by remote controller setting. 254 3D081424C VIEW ALL FXDA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXDQ-A3 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXDQ20-25A3 FXDA20-25A FXDQ20-25A3 Notes (mmH 2 O) (mmH 2 O) 5 50 5 4 40 3 Up pe r Hi lim gh it ES of E P SP 6 External static pressure [Pa] 6 60 4 H High ESP H High ESP 30 The remote controller can be used to switch between 'high' and 'low'. The air flow is factory-set to 'standard'. It is possible to switch between 'standard ES P' and 'high ESP' by remote controller setting. 3 Low High ESP P 2 20 1 10 S fE it o lim ESP r we gh Lo Hi 2 P S fE to mi SP r li d E pe dar p U tan S H Standard ESP 1 M Standard ESP Low Standard ESP 6 (mmH 2 O) 7 8 9 (mmH 2 O) Air flow rate [m³/min] 3D086736B FXDQ32A3 FXDA32A Notes (mmH 2 O) (mmH2O) 6 60 6 5 50 5 4 40 pe r Hi limi gh t o ES f E P S Up 30 3 M Low High ESP High ESP H 20 Standard ESP SP fE it o SP lim E er dard p Up Stan 2 S of E mit er li ESP Low High M Standard ESP 1 4 H High ESP P 2 External static pressure [Pa] 3 The remote controller can be used to switch between 'high' and 'low'. The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP' and 'high ESP' by remote controller setting. P 1 10 Low Standard ESP (mmH2O) 6 7 8 9 (mmH2O) Air flow rate [m³/min] 3D081425C 255 VIEW ALL FXDA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings 3D081426C VIEW ALL FXDQ-A3 TECHNICAL DRAWINGS ON MY.DAIKIN.EU FXDQ40A3 FXDA40A Notes mmH2O mmH2O 5 50 6 per li Hig mit o h E f ES SP P 60 The remote controller can be used to switch between 'high' and 'low'. The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP' and 'high ESP' by remote controller setting. 5 H High ESP Up 6 40 4 External static pressure [Pa] Low 3 2 H Standard ESP 30 3 M Standard ESP Up St pe an r li da m rd it o ar f E d ES SP P 20 1 4 M High ESP High ESP 2 P f ES to mi SP r li we igh E H Lo 1 10 it of ESP Lower lim d ESP ar Standard Low Standard ESP mmH2O 7 8 9 11 10 mmH2O 13 12 Air flow rate [m³/min] 3D081426C FXDQ50A3 FXDQ50A3 FXDA50A [mmH2O] Notes [mmH2O] 7 6 60 6 5 50 2 P Up p Hig er lim hE SP it of E S High ESP 4 H Standard ESP 3 30 20 SP fE to mi r li we SP Lo gh E Hi P 3 40 The remote controller can be used to switch between 'high' and 'low'. The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP' and 'high ESP' by remote controller setting. 5 H M High ESP U St ppe an r da lim rd it ES of E P S 4 External static pressure [Pa] 7 70 2 M Standard ESP Low 1 High ESP 10 Low Standard ESP [mmH2O] 8 9 1 it of ESP Lower lim P ES Standard 10 11 12 13 14 15 [mmH2O] Air flow rate [m³/min] 3D081427C 256 VIEW ALL FXDQ-A3 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXDQ60A3 FXDA60A (mmH2O) (Pa) (mmH2O) Notes: 1. Remote controller can be used to switch between `HIGH` and `LOW`. (`H`, `M` and `L` for FDQ-A2VEB model) 2. The air flows is set to `STANDARD` before leaving the factory. It is possible to switch between `STANDARD ESP` and `HIGH ESP` by remote controller. Upper limit of external static pressure (high ESP) External static pressure 63A VIEW ALL FXDA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU H (High ESP) M (High ESP) H (Standard ESP) Low (High ESP) Lower limit of external static pressure (high ESP) Upper limit of external static pressure (standard ESP) M (Standard ESP) Low (Standard ESP) Lower limit of external static pressure (standard ESP) (Pa) (mmH2O) Air flow rate(m³/h) (mmH2O) 3D081429B 257 VIEW ALL FXSA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL FXSQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU FXSQ15-32A FXSQ15-32A FXSA15-32A 2x65=130 38 100 65 50 800 301 KJ KC KH KE 110 245 178 140 25 40 300 or more Service space 69 342 210 550 Suspension bolt Fresh air intake position 109 Ø100 (Knockout hole.) 170 ARROW VIEW A 365 32 KF 179.2 50 500 or more Service space KD 504 145 588 Suspension position 4x65=260 150 145 95 KA 210 2x140=280 126 P.C.D. 4-M4 (CLASS 2) 50 KK Suspension position KB ARROW VIEW A 630 KG Item Description Name KA Liquid pipe connection port Ø6.35 flared connection KB Gas pipe connection port Ø12.70 flared connection KC Drain pipe connection VP20 (OD Ø26, ID Ø20) KD Wiring connection KE Power supply connection KF Drain outlet KG Air filter KH Air suction side / / VP20 (OD Ø26, ID Ø20) KJ Air discharge side KK Nameplate / / / / Notes 1. When installing optional accessories, refer to their respective documentation. 3D094888A 2. The ceiling depth varies according to the documentation of the specific system. 69 2x65=130 KJ 800 301 KC KE KH 110 178 245 38 100 65 50 140 25 40 492 210 700 Suspension bolt ) Fresh air intake position 109 Ø100 (Knockout hole. 170 300 or more Service space FXSQ40-50A FXSQ40-50A FXSA40-50A ARROW VIEW A 3x140=420 126 P.C.D. 515 4-M4 (CLASS 2) 738 32 KF 500 or more Service space Suspension position 179 50 50 KK KD 654 4x145=590 95 KA Suspension position KB KG 630 ARROW VIEW A 210 6x65=390 42 Item 258 Name KA Liquid pipe connection port Ø6.35 flared connection KB Gas pipe connection port Ø12.70 flared connection KC Drain pipe connection VP20 (OD Ø26, ID Ø20) KD Wiring connection KE Power supply connection KF Drain outlet KG Air filter KH Air suction side KJ Air discharge side KK Nameplate 155 130 130 120 5- Ø 4.7 HOLE Description / / VP20 (OD Ø26, ID Ø20) / / / / Notes 1. When installing optional accessories, refer to their respective documentation. 2. The ceiling depth varies according to the documentation of the specific system. 3D094919A VIEW ALL FXSA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXSQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXSQ63-80A 38 65 100 301 KC KJ KE KH 110 178 245 800 40 50 140 25 69 792 210 1000 Suspension bolt ) 2x65=130 (Knockout hole. Fresh air intake position 109 Ø 100 170 300 or more Service space FXSQ63-80A FXSA63-80A ARROW VIEW A 32 5x146=730 815 179 KF 500 or more Service space 50 KD 954 1038 Suspension position 6x145=890 95 11x65=715 KA 210 126 P.C.D. 4 x M4 (CLASS 2) 50 KK 630Suspension position KB 42 Item ARROW VIEW A KG 135 125 98 117 135 125 100 KG 8- Ø 4.7 HOLE Description Name KA Liquid pipe connection port Ø9.52 flared connection KB Gas pipe connection port Ø15.90 flared connection KC Drain pipe connection VP20 (OD Ø26, ID Ø20) KD Wiring connection KE Power supply connection KF Drain outlet KG Air filter KH Air suction side / / VP20 (OD Ø26, ID Ø20) KJ Air discharge side KK Nameplate / / / / Notes 1. When installing optional accessories, refer to their respective documentation. 2. The ceiling depth varies according to the documentation of the specific system. 3D094916A 65 800 301 KJ KC KE KH 110 178 245 140 100 50 25 69 40 210 1400 1192 Suspension bolt 2x65=130 ) Fresh air intake position 38 Ø100 (Knockout hole. 109 170 300 or more Service space FXSQ100-125A FXSQ100-125A FXSA100-125A ARROW VIEW A KK 7x156=1092 1215 32 KF 179 50 50 126 P.C.D. 4 x M4 (CLASS 2) KD 500 or more Service space 1354 8X150=1200 1438 Suspension position 95 KA 630Suspension position KB 42 Item Name 150 147.5 147.5 115 115 150 147.5 147.5 115 Liquid pipe connection port Ø9.52 flared connection KB Gas pipe connection port Ø15.90 flared connection KC Drain pipe connection VP20 (OD Ø26, ID Ø20) KD Wiring connection KE Power supply connection KF Drain outlet Air filter KH Air suction side KJ Air discharge side KK Nameplate ARROW VIEW A KG 10x Ø 4.7 HOLE Description KA KG KG 226 16x65=1040 / / VP20 (OD Ø26, ID Ø20) / / / / Notes 1. When installing optional accessories, refer to their respective documentation. 2. The ceiling depth varies according to the documentation of the specific system. 3D094917A 259 VIEW ALL FXSA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXSQ140A VIEW ALL FXSQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU 69 25 40 50 800 301 KJ KC KE KH 110 178 245 140 100 65 1342 210 1550 Suspension bolt 2x65=130 ) Fresh air intake position 38 62 109 Ø100 (Knockout hole. 170 300 or more Service space FXSQ140A FXSA140A ARROW VIEW A 8x156=1248 1365 126 P.C.D. 4 x M4 (CLASS 2) 1588 60 32 KF 500 or more Service space 179 KD 50 1504 9x150=1350 Suspension position 18x65=1170 50 KK 95 210 60 KA 630 Suspension position KB Item KG ARROW VIEW A 10x Ø4.7 HOLE 151 123 122 123 116 115 151 123 122 123 116 42 KG Description Name KA Liquid pipe connection port Ø9.52 flared connection KB Gas pipe connection port Ø15.90 flared connection KC Drain pipe connection VP20 (OD Ø26, ID Ø20) KD Wiring connection KE Power supply connection KF Drain outlet KG Air filter KH Air suction side / / VP20 (OD Ø26, ID Ø20) KJ Air discharge side KK Nameplate / / / / Notes 1. When installing optional accessories, refer to their respective documentation. 3D094928A 2. The ceiling depth varies according to the documentation of the specific system. FXSQ15A FXSQ15A FXSA15A 200 200 Fan characteristics (1) Fan characteristics (3) Air flow autoadjustment H-Tap *1 External static pressure [Pa] Upper limit of ESP 150 150 M-Tap *1 *1 Upper limit of ESP *1 H-Tap *2 L-Tap *1 L T (*1) L T*2 (*1) M-Tap*2 Upper limit of ESP L-Tap *2 50 External static pressure [Pa] Lower limit of ESP 100 *3 *2 Lower limit of ESP H-Tap *3 Upper limit of ESP M-Tap *3 L-Tap *3 *3 Lower limit of ESP 0 5,5 6,5 1. 7,5 8,5 Air flow rate [m³/min] H-Tap 100 M-Tap L-Tap 50 2. Lower limit of ESP 0 5,5 9,5 6,5 7,5 Airflow rate [m /min] 8,5 9,5 3 1. Upper limit of ESP by air flow auto adjustment External static pressure [Pa] Mark *1 *2 *3 260 MAX STD ESP [Pa] 150 100 50 2. Lower limit of ESP by air flow auto adjustment Fan characteristics (2) Field setting with remote control Air flow rate range (H) 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 7,5 Airflow rate [m /min] 3 8,5 9,5 Notes 1. The fan characteristics shown are in "fan only" mode. 2. ESP: External Static Pressure 3D096999 VIEW ALL FXSA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXSQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXSQ20-25A FXSQ20-25A FXSA20-25A 200 200 Fan characteris�cs (1) Fan characteris�cs (3) Air flow auto adjustment H-Tap *1 150 150 1. Upper limit of ESP *1 M-Tap *1 H-Tap *2 L-Tap *1 *2 M-Tap *2 Upper limit of ESP *2 Lower limit of ESP L-Tap *2 50 External sta�c pressure [Pa] External sta�c pressure [Pa] *1 Upper limit of ESP 100 Lower limit of ESP *3 H-Tap *3 Upper limit of ESP M-Tap *3 L-Tap *3 100 5,5 *3 6,5 7,5 8,5 M-Tap 50 0 Lower limit of ESP 0 H-Tap 9,5 L-Tap Lower limit of ESP 5,5 External sta�c pressure [Pa] 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 7,5 8,5 9,5 Air flow rate [m /min] Air flow rate [m /min] ESP [Pa] 150 100 30 MAX STD 6,5 3 3 Mark *1 *2 *3 2. 1. Upper limit of ESP by air flow auto adjustment 2. Lower limit of ESP by air flow auto adjustment Fan characteris�cs (2) Field se�ng with remote control Air flow rate range (H) 8 9 FXSQ32A 10 Notes 1. The fan characteris�cs shown are in "fan only" mode. 2. ESP: External Sta�c Pressure 3D095680A Air flow rate [m3/min] 200 200 Fan characteristics (1) M-Tap *1 [Pa] static pressure [Pa] External static pressure External Upper limit of ESP 100 *1 Lower limit of ESP Upper limit of ESP M-Tap *2 L-Tap *2 Upper limit of ESP Lower limit of ESP *3 100 Upper limit of ESP L-Tap *1 *2 H-Tap *3 *2 H-Tap M-Tap *3 L-Tap *3 *3 Lower limit of ESP Upper limit of ESP 0 5,5 Mark *1 *2 *3 0 6,5 M-Tap *2 L-Tap *2 7,5 Upper ESPlimit [Pa]of ESP 5,5 200 190 Mark 180 *1 170 MAX *2 160 *3 150 STD 140 130 200 120 190 110 180 100 170 90 160 80 150 70 140 60 130 50 120 40 110 30 100 20 90 10 80 0 70 60 8 50 40 30 20 10 0 8 150 100 30 8,5 ESP [Pa] 150 100 30 10,5 100 H-Tap 150 Upper limit of ESP 1. M-Tap L-Tap 50 2. 100 5,5 6,5 L-Tap 7,5 H-Tap Lower limit of ESP M-Tap 0 50 8,5 Air flow rate [m3/min] 1. Upper limit of ESP by air flow auto adjustment 2. Lower limit of ESP by air flow auto adjustment *3 9,5 1. Fan characteristics (3) Air flow auto adjustment Lower limit of ESP Fan characteristics (2) Field setting with remote control 7,5 8,5 Air flow rate range (H) *2 Lower limit of ESP Upper limit of ESP H-Tap *3 M-Tap *3 L-Tap *3 6,5 9,5 Air flow rate [m3/min] *3 MAX STD *2 Lower limit of ESP *1 M-Tap *1 *1 50 50 H-Tap *2 H-Tap *1 L-Tap *1 *2 External static pressure External [Pa] static pressure [Pa] 150 200 150 Fan characteristics (3) Air flow auto adjustment H-Tap *1 150 *1 [Pa] static pressure [Pa] External static pressure External 200 Fan characteristics (1) FXSQ32A FXSQ32A FXSA32A 9,5 10,5 2. Lower limit of ESP 0 10,5 5,5 6,5 7,5 8,5 9,5 10,5 Air flow rate [m3/min] Air flow rate [m /min] 3 1. Upper limit of ESP by air flow auto adjustment 2. Lower limit of ESP by air flow auto adjustment Fan characteristics (2) Field setting with remote control Air flow rate range (H) 9 10 11 Notes 1. The fan characteristics shown are in "fanonly" mode. 2. ESP: External Static Pressure 11 Notes 1. The fan characteristics shown are in "fanonly" mode. 2. ESP: External Static Pressure Air flow rate [m3/min] 9 10 3D095681A Air flow rate [m3/min] 261 3D095681A VIEW ALL FXSA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL FXSQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU FXSQ40A FXSQ40A FXSA40A 200 200 H-Tap *1 150 External sta�c pressure [Pa] 150 External sta�c pressure [Pa] *1 Lower limit of ESP *1 M-Tap *1 Upper limit of ESP 100 H-Tap *2 L-Tap *1 Lower limit of ESP L-Tap *2 H-Tap *3 *3 Upper limit of ESP M-Tap *3 L-Tap *3 0 9 Mark *1 *2 *3 External sta�c pressure [Pa] *2 M-Tap *2 *2 Upper limit of ESP 50 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Fan characteris�cs (3) Air flow auto adjustment Fan characteris�cs (1) 10 MAX STD 12 13 100 H-Tap M-Tap 50 L-Tap 14 15 0 16 17 2. Lower limit of ESP 9 10 11 12 13 14 15 16 17 Air flow rate [m3/min] Air flow rate [m3/min] ESP [Pa] 150 100 30 1. *3 Lower limit of ESP 11 Upper limit of ESP 1. Upper limit of ESP by air flow auto adjustment 2. Lower limit of ESP by air flow auto adjustment Fan characteris�cs (2) Field se�ng with remote control Air flow rate range (H) 13 14 15 16 17 Air flow rate [m3/min] Notes 1. The fan characteris�cs shown are in "fan only" mode. 2. ESP: External Sta�c Pressure 3D095682A FXSQ50A FXSQ50A FXSA50A 200 200 Fan characteristics (1) Fan characteristics (3) Air flow auto adjustment H-Tap *1 150 150 Upper limit of ESP 1. *1 *1 Lower limit of ESP M-Tap *1 M-Tap *2 *2 Lower limit of ESP L-Tap *2 *3 Upper limit of ESP H-Tap *3 L-Tap *3 M-Tap *3 *3 Lower limit of ESP 0 Mark *1 *2 *3 MAX STD 10 ESP [Pa] 150 100 30 11 12 13 Air flow rate [m³/min] 14 15 100 H-Tap M-Tap 50 L-Tap 2. Lower limit of ESP 0 16 17 9 10 11 12 13 Air flow rate [m³/min] 14 15 16 17 1. Upper limit of ESP by air flow auto adjustment 2. Lower limit of ESP by air flow autoa djustment Fan characteristics (2) Field settingwith remote control 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Air flow rate range (H) 13 14 15 Air flow rate [m³/min] 262 *2 Upper limit of ESP 9 External static pressure [Pa] H-Tap *2 L-Tap *1 50 External static pressure[Pa] External static pressure [Pa] Upper limit of ESP 100 16 17 Notes 1. The fan characteristics shown are in "fan only" mode. 2. ESP: External Static Pressure 3D095688A VIEW ALL FXSA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXSQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXSQ63A FXSQ63A FXSA63A 200 200 Fan characteristics (3) Air flow auto adjustment Fan characteristics (1) H-Tap*1 M-Tap*1 *1 Upper limit of ESP 100 H-Tap*2 L-Tap*1 L T (*1) *2 Upper limit of ESP 50 *2 M-Tap*2 Lower limit of ESP L-Tap*2 *3 H-Tap*3 Upper limit of ESP M-Tap*3 *3 Lower limit of ESP 0 12 Mark *1 *2 *3 External static pressure [Pa] External static pressure [Pa] 1. *1 Lower limit of ESP L-Tap*3 External static pressure [Pa] Upper limit of ESP 150 150 MAX STD 13 14 15 16 17 18 Air flow rate[m³/min] 19 20 21 22 23 100 H-Tap M-Tap 50 L-Tap 2. Lower limit of ESP 0 24 12 13 14 15 16 17 18 Air flow rate[m³/min] 19 20 21 22 23 24 1. Upper limit of ESP by air flow auto adjustment ESP [Pa] 150 100 30 2. Lower limit of ESP by air flow auto adjustment Fan characteristics (2) Field setting with remote control 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Air flow rate range (H) 18 19 20 21 22 Air flow rate[m³/min] 23 24 Notes 1. The fan characteristics shown are in "fan only" mode. 2. ESP: External Static Pressure 3D095690A FXSQ80A FXSQ80A FXSA80A 200 200 Fan characteristics (3) Air flow auto adjustment Fan characteristics (1) H-Tap*1 150 150 M-Tap*1 External static pressure [Pa] Upper limit of ESP 100 H-Tap*2 L-Tap*1 *2 Lower limit of ESP L-Tap*2 *3 Upper limit of ESP H-Tap*3 M-Tap*3 L-Tap*3 Lower limit of ESP 0 13,5 Mark *1 *2 *3 External static pressure [Pa] M-Tap*2 *2 Upper limit of ESP 50 14,5 MAX STD 15,5 16,5 17,5 18,5 19,5 Air flow rate[m³/min] ESP [Pa] 150 100 40 1. Lower limit of ESP External static pressure [Pa] *1 Upper limit of ESP *1 20,5 21,5 22,5 23,5 24,5 *3 100 H-Tap M-Tap L-Tap 50 2. Lower limit of ESP 0 25,5 13,5 26,5 14,5 15,5 16,5 17,5 18,5 19,5 20,5 21,5 22,5 23,5 24,5 25,5 26,5 Air flow rate[m³/min] 1. Upper limit of ESP by air flow auto adjustment 2. Lower limit of ESP by air flow auto adjustment Fan characteristics (2) Field setting with remote control Air flow rate range (H) 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 19,5 20,5 21,5 Air flow rate[m³/min] 22,5 23,5 24,5 25,5 26,5 Notes 1. The fan characteristics shown are in "fan only" mode. 2. ESP: External Static Pressure 3D095692A 263 VIEW ALL FXSA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL FXSQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU FXSQ100A FXSQ100A FXSA100A 200 200 Fan characteristics (3) Air flow auto adjustment Fan characteristics (1) H-Tap*1 External static pressure [Pa] 100 *1 M-Tap*1 Lower limit of ESP H-Tap*2 L-Tap*1 *2 Upper limit of ESP M-Tap*2 L-Tap*2 *3 50 External static pressure [Pa] *1 Upper limit of ESP Lower limit of ESP Upper limit of ESP *2 H-Tap*3 M-Tap*3 L-Tap*3 *3 Lower limit of ESP 0 H-Tap M-Tap External static pressure [Pa] L-Tap 50 2. Lower limit of ESP 0 19,5 20,5 21,5 22,5 23,5 24,5 25,5 26,5 27,5 28,5 29,5 30,5 31,5 32,5 33,5 34,5 35,5 36,5 Air flow rate[m³/min] MAX STD 1. 100 19,5 20,5 21,5 22,5 23,5 24,5 25,5 26,5 27,5 28,5 29,5 30,5 31,5 32,5 33,5 34,5 35,5 36,5 Mark *1 *2 *3 Upper limit of ESP 150 150 Air flow rate[m³/min] 1. Upper limit of ESP by air flow auto adjustment ESP [Pa] 150 100 40 2. Lower limit of ESP by air flow auto adjustment Fan characteristics (2) Field setting with remote control Air flow rate range (H) 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 27 28 29 30 31 32 Air flow rate[m³/min] 33 34 35 36 37 Notes 1. The fan characteristics shown are in "fan only" mode. 2. ESP: External Static Pressure 3D095696A FXSQ125A FXSQ125A FXSA125A 200 200 Fan characteristics (3) Air flow auto adjustment Fan characteristics (1) H-Tap*1 Upper limit of ESP 150 150 M-Tap*1 *1 External static pressure [Pa] *1 Upper limit of ESP External static pressure [Pa] Lower limit of ESP 100 L-Tap*1 *2 L-Tap*2 50 *2 Lower limit of ESP *3 Upper limit of ESP H-Tap*3 M-Tap*3 L-Tap*3 *3 Lower limit of ESP 0 23 Mark *1 *2 *3 External static pressure [Pa] M-Tap*2 Upper limit of ESP 22 264 H-Tap*2 24 MAX STD 25 26 27 28 29 30 31 Air flow rate[m³/min] ESP [Pa] 150 100 50 32 33 34 35 36 37 38 39 40 41 1. 100 H-Tap M-Tap 50 2. L-Tap Lower limit of ESP 0 22 23 24 25 26 27 28 29 30 31 Air flow rate[m³/min] 32 33 34 35 36 37 38 39 40 41 1. Upper limit of ESP by air flow auto adjustment 2. Lower limit of ESP by air flow auto adjustment Fan characteristics (2) Field setting with remote control Air flow rate range (H) 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 30,5 31,5 32,5 33,5 34,5 35,5 Air flow rate[m³/min] 36,5 37,5 38,5 39,5 40,5 41,5 Notes 1. The fan characteristics shown are in "fan only" mode. 2. ESP: External Static Pressure 3D095697A VIEW ALL FXSA-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXSQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXSQ140A FXSQ140A FXSA140A 200 200 Fan characteristics (1) Fan characteristics (3) Air flow auto adjustment H-Tap*1 150 M-Tap*1 *1 *1 Upper limit of ESP External static pressure [Pa] External static pressure [Pa] 150 Lower limit of ESP H-Tap*2 100 L-Tap*1 M-Tap*2 *2 *2 Lower limit of ESP Upper limit of ESP 50 L-Tap*2 *3 H-Tap*3 M-Tap*3 Upper limit of ESP L-Tap*3 *3 Lower limit of ESP 0 1. Upper limit of ESP 100 H-Tap M-Tap 50 L-Tap 2. Lower limit of ESP 0 25 26 27 28 29 30 31 32 33 Air flow rate[m³/min] 34 35 36 37 38 39 40 41 42 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 Air flow rate[m³/min] 1. Upper limit of ESP by air flow auto adjustment Mark *1 *2 *3 MAX STD ESP [Pa] 150 100 50 2. Lower limit of ESP by air flow auto adjustment Fan characteristics (2) Field setting with remote control External static pressure [Pa] Air flow rate range (H) 200 190 180 170 160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 35 36 37 38 Air flow rate[m³/min] 39 40 41 42 Notes 1. The fan characteristics shown are in "fan only" mode. 2. ESP: External Static Pressure 3D096688A 265 VIEW ALL FXMQ-P7 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXMQ50P7 FXMQ50P7 DETAIL B VIEW A-A Ø125 (Knock out hole) fresh air intake position 350 or more (Service space) Suspension bolt 500 or more (Service space) 6 x M5 (On circumference) DETAIL B Item 1 2 3 4 5 6 7 8 9 10 Name Liquid pipe connection Gas pipe connection Drain pipe connection Remote control wiring connection Power supply connection Drain hole Air filter Air suction side Air discharge side Nameplate Description Ø6.35 Flare connection Ø12.70 Flare connection VP25 (0D Ø32, ID Ø25) VP20 (0D Ø32, ID Ø25) - 631 (Suspension position) 1038 (Suspension position) 3TW32694-1 NOTES 1 Refer to ‘outlook drawing for installing optional accessories’ when installing optional accessories. 2 The required ceiling depth varies according to the configuration of the specific system. 3 For maintenance of the air filter, it is necessary to provide a service access panel. Refer to the ‘filter installation method’ drawing. FXMQ63-80P7 FXMQ63-80P7 (Knock out hole) Fresh air intake position 350 or more (Service space) Suspension bolt Detail B 500 or more (Service space) (On circumference) Item Name 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Remote control wiring connection 5 Power supply connection 6 Drain hole 7 Air filter 8 Air suction side 9 Air discharge side 10 Nameplate 631 (Suspension position) 390 or more (Service space) 1038 (Suspension position) (Ceiling opening) Description ø 9.52 Flare connection ø 15.90 Flare connection VP25 (OD ø 32, ID ø 25) VP25 (OD ø 32, ID ø 25) - Detail B (Ceiling opening) NOTES View A-A 1. Refer to the outlook drawing of optional accessories when installing them. 2. The required ceiling depth varies according to the configuration of the specific system. 3. For maintenance of the air filter, it is necessary to provide a service access panel. 4. Optional decoration panel: BYBS71DJW1 (light ivory white 10Y9/0.5) With decoration panel 3TW31234-1B 266 VIEW ALL FXMQ-P7 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXMQ-MB TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXMQ100-125P7 FXMQ100-125P7 (Knock out hole) Fresh air intake position 350 or more (Service space) Suspension bolt Detail B 500 or more (Service space) (On circumference) (Ceiling opening) 631 (Suspension position) 390 or more (Service space) 1438 (Suspension position) Detail B View A-A Item Name 1 Liquid pipe connection 2 Gas pipe connection 3 Drain pipe connection 4 Remote control wiring connection 5 Power supply connection 6 Drain hole (Ceiling opening) 8 9 10 Air suction side Air discharge side Nameplate Description ø 9.52 Flare connection ø 15.90 Flare connection VP25 (OD ø 32, ID ø 25) VP25 (OD ø 32, ID ø 25) - NOTES 1. Refer to the outlook drawing of optional accessories when installing them. 2. The required ceiling depth varies according to the configuration of the specific system. 3. For maintenance of the air filter, it is necessary to provide a service access panel. 4. Optional decoration panel: BYBS125DJW1 (light ivory white 10Y9/0.5) 3TW31254-1B With decoration panel FXMQ-MB piping size (Field supply) gas side indoor unit liquid side Attached piping Attached piping 32 - ø 4.7 Hole (all around) Note 1. Location of unit`s name plate: Control box surface 32 - ø 4.7 Hole (all around) approx. 600 650 or more (service space) 32 - ø 4.7 Hole (all around) View A Inspection hole 600 or more 1100 or more (Service space) Discharge side suction side (Note 2) 1 Liquid pipe connection 2 Gas pipe connection Attendant piping connection 3 Ground terminal M5 (inside switch box) 4 View A 16 - ø 8 Hole (all around) Flare connection Control box 5 Power supply wiring connection 6 Transmision wiring connection 7 Hook 8 Discharge flange 9 Suction flange 10 Attached piping 11 Name plate 12 Drain piping connection M10 Brazing PS1B internal thread Major dia. ø33.349 Major dia. ø33.391 13 Water supply port 3D096007 267 VIEW ALL FXMQ-P7 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXMQ50P7 Fan characteristics (1) Fan characteristics (3) (airflow auto adjustment) Upper limit of ESP (max ESP) H (max ESP) Lower limit of ESP (max ESP) M (max ESP) L (max ESP) Upper limit of ESP (std ESP) M (std ESP) H (std ESP) L (std ESP) Lower limit of ESP (std ESP) External static pressure [Pa] External static pressure [Pa] FXMQ50P7 Upper limit of ESP Upper limit of ESP by airflow auto adjustment H Lower limit of ESP by airflow auto adjustment M L Lower limit of ESP Airflow [m /min] 3 Airflow [m /min] 3 Fan characteristics (2) (Field setting with remote control) External static pressure [Pa] Range of available air flow rate (H) Airflow [m /min] 3 3TW32698-1 NOTES 1. Fan characteristics as shown are in “fan only” mode. 2. ESP: External static pressure FXMQ63P7 Fan characteristics (1) Fan characteristics (3) (airflow auto adjustment) H (max ESP) Upper limit of ESP (max ESP) M (max ESP) Lower limit of ESP (max ESP) L (max ESP) H (std ESP) Upper limit of ESP (std ESP) M (std ESP) Lower limit of ESP (std ESP) L (std ESP) Airflow [m /min] 3 External static pressure [Pa] External static pressure [Pa] FXMQ63P7 Upper limit of ESP by airflow auto adjustment Upper limit of ESP H M Lower limit of ESP by airflow auto adjustment L Lower limit of ESP Airflow [m /min] 3 Fan characteristics (2) (Field setting with remote control) External static pressure [Pa] Range of available air flow rate (H) Airflow [m /min] 3 NOTES 1. Fan characteristics as shown are in “fan only” mode. 2. ESP: External static pressure 268 3TW32708-1 VIEW ALL FXMQ-P7 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXMQ80P7 Fan characteristics (1) Fan characteristics (3) (airflow auto adjustment) H (max ESP) Upper limit of ESP (max ESP) M (max ESP) Lower limit of ESP (max ESP) L (max ESP) H (std ESP) Upper limit of ESP (std ESP) M (std ESP) Lower limit of ESP (std ESP) L (std ESP) External static pressure [Pa] External static pressure [Pa] FXMQ80P7 Upper limit of ESP by airflow auto adjustment Upper limit of ESP H M Lower limit of ESP by airflow auto adjustment L Lower limit of ESP Airflow [m3/min] Airflow [m3/min] Fan characteristics (2) (Field setting with remote control) External static pressure [Pa] Range of available air flow rate (H) Airflow [m3/min] 3TW32718-1 NOTES 1. Fan characteristics as shown are in “fan only” mode. 2. ESP: External static pressure FXMQ100P7 Fan characteristics (1) Fan characteristics (3) (airflow auto adjustment) H (max ESP) Upper limit of ESP (max ESP) M (max ESP) Lower limit of ESP (max ESP) L (max ESP) Upper limit of ESP (std ESP) H (std ESP) M (std ESP) Lower limit of ESP (std ESP) L (std ESP) Airflow [m3/min] External static pressure [Pa] External static pressure [Pa] FXMQ100P7 Upper of ESP Upper limit limit of ESP by by airflow adjustment airflow autoauto adjustment H Upper limit of ESP Upper limit of ESP M Lower limit of ESP by airflow auto adjustment L Lower limit of ESP Lower limit of ESP Airflow [m3/min] Fan characteristics (2) Fan characteristics (2) (Field setting with remote control) (Field setting with remote control) External static pressure [Pa] Range of available air flow rate (H) Range of available air flow rate (H) Airflow [m3/min] 3TW32728-1 NOTES 1. Fan characteristics as shown are in “fan only” mode. 2. ESP: External static pressure. 269 VIEW ALL FXMQ-MB TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL FXMQ-P7 TECHNICAL DRAWINGS ON MY.DAIKIN.EU FXMQ125P7 Fan characteristics (1) Upper limit of ESP (max ESP) M (max ESP) L (max ESP) Fan characteristics (3) (airflow auto adjustment) H (max ESP) H (std ESP) Upper limit of ESP (std ESP) M (std ESP) L (std ESP) Lower limit of ESP (max ESP) Lower limit of ESP (std ESP) External static pressure [Pa] External static pressure [Pa] FXMQ125P7 Upper limit of ESP Upper limit of ESP by airflow auto adjustment H M L Lower limit of ESP by airflow auto adjustment L Lower limit of ESP Airflow [m3/min] Airflow [m3/min] Fan characteristics (2) (Field setting with remote control) External static pressure [Pa] Range of available air flow rate (H) Airflow [m3/min] 3TW32738-1 NOTES 1. Fan characteristics as shown are in “fan only” mode. 2. ESP: External static pressure FXMQ200MB FXMQ200MB 50hZ 220-240V (mmH2O) (mmH2O) (Pa) high (High ESP) Upper limit of external static pressure (high ESP) Notes: 1. Remote controller can be used to switch between `HIGH` and `LOW`. 2. The air flows is set to `STANDARD` before leaving the factory. It is possible to switch between `STANDARD ESP` and `HIGH ESP` by remote controller. Lower limit of external static pressure (high ESP) External static pressure Low (High ESP) High (Standard ESP) Upper limit of external static pressure (standard ESP) Low (Standard ESP) Lower limit of external static pressure (standard ESP) Air flow rate(m³/min) 270 4D095421 VIEW ALL FXMQ-MB TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXMQ250MB FXMQ250MB (mmH2O) (mmH2O) (Pa) high (High ESP) Upper limit of external static pressure (high ESP) Notes: 1. Remote controller can be used to switch between `HIGH` and `LOW`. 2. The air flows is set to `STANDARD` before leaving the factory. It is possible to switch between `STANDARD ESP` and `HIGH ESP` by remote controller. Lower limit of external static pressure (high ESP) Low (High ESP) External static pressure (Pa) 50hZ 220-240V High (Standard ESP) Upper limit of external static pressure (standard ESP) Low (Standard ESP) Lower limit of external static pressure (standard ESP) Air flow rate(m³/min) 4D095422 271 VIEW ALL FXAQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXAQ15-32A FXAQ15-32A Hole for piping Hole for piping About 365 Drain hose About 420 Gas pipe About 460 Liquid pipe 30 or more Dimensions of fully opened front panel 450 Indoor air flow 290 Front grille fixing screws Front panel Front grille Hole for piping 795 Heating Standard location of holes in the wall 625 107.6 14 Blade angle For installation in high places 50 or more Required space Required space Up/down (automatic) Cooling Dry Knockout hole. 120 or less Air outlet Horizontal blade Hole for piping 50 or more Knockout hole. Location of nameplate 2500 or more 266 Required space Hole for piping 90 or more Required space Hole for piping 62 Outer dimensions of the unit Fan Refrigerant filter 57° Left/right (manual) 0 8 80 About 290 Flexible pipe About 308 Flexible pipe About 415 Gas pipe Ø 12.7mm CuT About 460 Liquid pipe Ø 6.4mm CuT About 475 Drain hose VP13 60 ° 45 45° Notes 1) The mark shows the piping direction. 2) Do not place any objects under the indoor unit. In case of high humidity (>80%), clogged drain 105 42° 25° 55° 64° 50° 44 27° 58° Hole for embedded piping Hole for embedded piping 12° 16° 98 44 4° 19° Inside diameter: 15mm outlets, or dirty air filters, condensate may drop out. 3D111370 Outside diameter: 18mm 29 FXAQ40-50A FXAQ40-50A Hole for piping Hole for piping 30 or more Dimensions of fully opened front panel 450 Indoor air flow Location of nameplate 2500 or more 269 290 Front grille fixing screws Front panel 50 or more Knockout hole. 14.5 Blade angle 4° 25° 55° Left/right (manual) 57° 42° Refrigerant filter 80 60 45° Notes 1) The ° 45 Hole for embedded piping mark shows the piping direction. 2) Do not place any objects under the indoor unit. In case of high humidity (>80%), clogged drain outl ets, or dirty air filters, condensate may drop out. 272 0 8 About 290 Flexible pipe About 300 Flexible pipe About 415 Gas pipe Ø 12.7mm CuT About 460 Liquid pipe Ø 6.4mm CuT About 475 Drain hose VP13 105 50° Outer dimensions of the unit 44 58° 52 12° 16° 64° 894 Hole for embedded piping 44 19° Standard location of holes in the wall Fan Heating 27° 104 For installation in high places 50 or more Required space 1050 Required space Up/down (automatic) Cooling Dry Hole for piping Hole for piping Knockout hole. 120 or less Air outlet Horizontal blade Front grille Required space About 365 Drain hose About 420 Gas pipe About 460 Liquid pipe 90 or more Required space Hole for piping Hole for piping 98 Inside diameter: 15mm Outside diameter: 18mm 3D111369 VIEW ALL FXAQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXAQ63A FXAQ63A About 365 Drain hose About 420 Gas pipe About 460 Liquid pipe Hole for piping Hole for piping 30 or more Required space Hole for piping 90 or more Required space Hole for piping Dimensions of fully opened front panel 2500 or more Indoor air flow Location of nameplate Front grille fixing screws Front panel Front grille Knockout hole Blade angle Cooling Dry Horizontal blade 50 or more Required space 120 or less For installation in high places Air outlet Hole for piping Hole for piping Standard location of holes in the wall Up/down (automatic) Heating Knockout hole 50 or more Required space Outer dimensions of the unit Fan HOLE FOR CONCRETE WALL HOLE FOR CONCRETE WALL USE TAPE MEASURE AS SHOWN 125mm TO UNIT LEFT SIDE FACE Position the end of tape measure at UNIT WIDTH: 1050 mm UNIT HEIGHT: 290 mm PIPING HOLE CENTER 83mm TO THE LEFT PLACE A LEVEL unit center Gas pipe end Refrigerant filter Left/right (manual) Hole for embedded piping 100mm TO UNIT RIGHT SIDE FACE PIPING HOLE CENTER: 90 mm DOWN TO UNIT OUTLINE 525mm TO THE RIGHT AND LEFT 145mm UP AND DOWN Liquid pipe end IF FIXING UNIT TO THIS PLATE WITH SCREW FIX THIS PLATE TO THE WALL WITH SCREW Hole for embedded piping PIPING HOLE CENTER 100mm TO THE RIGHT About 290 Flexible pipe About 300 Flexible pipe About 415 Gas pipe ø 15.9mm CuT About 460 Liquid pipe ø 9.5mm CuT About 475 Drain hose VP13 Inside diameter: 15 mm NOTES 1. The mark shows the piping direction. 2. Do not place any objects under the indoor unit. In case of high humidity (>80%), clogged drain outlets or dirty air filters, condensate may drop out. Outside diameter: 18 mm 3D111368 273 VIEW ALL FXHQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXHQ32A FXHQ32A Connection position of fresh air intake kit Position slit hole for taking out in piping back (view from the front) (required space) (required space) (hanging bolt pitch) ø 100 (knock-out hole) (hanging bolt pitch) Hanging bolt 300 or more (required space) From the floor side 2500 or more For height installation Position: hole wall for taking out in piping back (view from the front) 30 or more (service space) obstacle THE FRONT 30 or more Nr (service space) 1 Air discharge grille 2 Air suction grille Air filter brand nameplate (note 2) 3 floor side Gas pipe connection Liquid pipe connection ø 15.9 flare ø 9.5 flare 6 Drain pipe connection VP20 7 Earth terminal (inside electric components box) Hanger bracket Backward piping and wiring connection open lid 8 9 10 slit hole Left back pipe connection Left side drain pipe connection slit hole slit hole Right side drain pipe connection Hole of wall for taking out in piping back slit hole 14 Location of unit`s name plate: bottom of fan housing inside the suction grille. In case of using infrared remote controller, this position will be a signal receiver. Refer tot the drawing of infrared remote control in detail. Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, the drain outlet are choked up and the air filter are dirty, dew may fall. Upward piping and wiring connection open lid Right side pipe connection 12 15 1. 2. 3. M4 11 13 NOTES Description 5 4 Drain pipe connection VP20 (for left piping) Name ø 100 16 Upward drain pipe connection ø 60 17 Upward gas pipe connection Upward liquid pipe connection Power source wiring and unit wiring back connection ø 36 ø 26 Power source wiring and unit wiring upper connection ø 29 18 19 20 ø 29 3D080029 FXHQ63A FXHQ63A (suspension position) (required space) Position slit hole for taking out in piping back (view from the front) suspension bolt (required space) Position: hole wall for taking out in piping back (view from the front) 300 or more For height installation From the floor side 2500 or more (required space) (suspension position) Connection position of fresh air intake kit ø 100 (knock-out hole) 30 or more (service space) 30 or more (service space) FRONT brand nameplate note 2 obstacle floor side NOTES 1. Location of unit`s name plate: bottom of fan housing inside the suction grille. 2. In case of using infrared remote control, this position will be a signal receiver. Refer tot the drawing of infrared remote control in detail. 3. Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, the drain outlet are choked up and the air filter are dirty, dew may fall. Drain pipe connection VP20 (for left piping) Name Nr Description 1 Air discharge grille 11 Right side pipe connection slit hole 2 Air suction grille Air filter 12 Left back pipe connection Left side drain pipe connection slit hole slit hole slit hole 3 13 5 Gas pipe connection Liquid pipe connection ø 15.9 flare ø 9.5 flare 15 Right side drain pipe connection Hole of wall for taking out in piping back 6 Drain pipe connection VP20 16 Upward drain pipe connection ø 60 7 Earth terminal (inside electric components box) Hanger bracket Backward piping and wiring connection open lid M4 17 Upward gas pipe connection Upward liquid pipe connection Power source wiring and unit wiring back connection ø 36 ø 26 Power source wiring and unit wiring upper connection ø 29 4 8 9 10 Upward piping and wiring connection open lid 14 18 19 20 ø 100 ø 29 3D069632A 274 VIEW ALL FXHQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL FXUQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXHQ100A FXHQ100A (required space) Position slit hole for taking out in piping back (view from the front) (suspension position) suspension bolt Position: hole wall for taking out in piping back (view from the front) (required space) For height installation from the floor side 2500 or more (required space) (suspension position) Connection position of fresh air intake kit ø 100 (knock-out hole) 30 or more (service space) 30 or more (service space) FRONT obstacle brand nameplate note 2 floor side brand nameplate Drain pipe connection VP20 Name Nr NOTES 1. Location of unit`s name plate: bottom of fan housing inside the suction grille. 2. In case of using infrared remote control, this position will be a signal receiver. Refer tot the drawing of infrared remote control in detail. 3. Don’t put anything under indoor unit because dew may fall by reason of following: 1. The humidity is 80% or more. 2. The drain outlet is stopped up. 3. The air filter is dirty. Description 1 Air discharge grille 11 Right side pipe connection slit hole 2 Air suction grille Air filter 12 Left back pipe connection Left side drain pipe connection slit hole slit hole slit hole 3 13 5 Gas pipe connection Liquid pipe connection ø 15.9 flare ø 9.5 flare 15 Right side drain pipe connection Hole of wall for taking out in piping back 6 Drain pipe connection VP20 16 Upward drain pipe connection ø 60 7 Earth terminal (inside electric components box) Hanger bracket Backward piping and wiring connection open lid M4 17 Upward gas pipe connection Upward liquid pipe connection Power source wiring and unit wiring back connection ø 36 ø 26 Power source wiring and unit wiring upper connection ø 29 4 8 9 10 14 18 19 20 Upward piping and wiring connection open lid ø 100 ø 29 3D069633D FXUQ-A 1500mm or more Notes: 1. Sticking locations for manufacturer`s label: On the control box lid inside suction grile. 2. When installing an optional accessory, refer to the installation drawings. 3. When closing the discharge grill (2 or 3 way discharge), direction of pipe connection will be limited, please refer to installation manual. 4. PLease do not place the thing been damp and troubled under an indoor unit. When the case where humidity in more 80% or more, and drain outlet are choked up and the air filter are dirty, dew may fail. 1500mm or more 1500mm or more 835 Hanging location (Unit: mm) Brand name plate (note 2) 1500mm or more When closing the air outlet, the required space is 30mm or more (Note 3) 835 Hanging location Brand name plate Gas piping and drain connection location for upper piping Gas piping and drain connection location for rear piping Gas piping and drain connection location for right piping Hanging bolt A arrow view Hight of hanger 2500mm or more (required space) A arrow view Drain piping can be raised up to 600mm from the top surface of the product 1 Liquid piping connection ø 9.5 Flare 2 Gas piping connection ø 15.9 Flare 3 Drain piping connection VP20 4 Air outlet 5 Suction grille 6 Corner cover 7 Right Pipe / wiring connection 8 Rear Pipe / wiring connection 9 Piping penetration cover 10 Elbow (accesory) - External dia, ø 26 11 L-Bent piping (accesory) - ø 15.9 flare 275 VIEW ALL FXNQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXNQ20-32A FXNQ20-32A 790 300 ARROW VIEW B 680 80 170 156 ARROW VIEW A 200 620 662 4x150=600 740 20 or more Suspension position 100 16- Ø4.7 HOLE 5x100=500 130 63 330 179.4 100 KD KF 48 KK 790 KJ 5x100=500 50 10 42 50 300 or more Service space 240 or more 90 KH 8.4 ARROW VIEW A 723 100 or more 500 KC 620 KA Suspension position KH 310 4-M8~M10 48 24 60 Suspension bolt KB 12.5 19.5 14-M4 20 or more 57.5 Inspection door KJ KE 46 16- Ø 4.3 HOLE 601 171 ARROW VIEW B Front suction 4- Ø5 HOLE 180 116 100 KG 5x100=500 16- Ø 4.3 HOLE 601 810 830 Item Bottom suction Name Description KA Liquid pipe connection port Ø6.40 flared connection KB Gas pipe connection port Ø12.7 flared connection KC Drain pipe connection VP20 (OD Ø26, ID Ø20) KD Drain hose ID Ø25 KE Control box / KF Transmission line / KG Power supply connection / KH Suspension bracket / KJ Air filter / KK Mounting foot / Notes 1. When installing optional accessories, refer to their respective documentation. 2. The ceiling depth varies according to the documentation of the specific system. 3D096749A FXNQ40-50A FXNQ40-50A 300 990 ARROW VIEW B 880 200 60 KD 90 130 KH 63 310 723 620 100 or more 500 KC KH 330 Suspension position KA 48 24 100 179.4 4-M8~M10 48 8.4 KF KK 42 50 KJ KJ 7x100=700 50 990 300 or more Service space 10 240 or more 100 22- Ø 4.7 HOLE 8x100=800 Suspension bolt ARROW VIEW A 156 Suspension position 20 or more KB 18-M4 940 170 20 or more 57.5 ARROW VIEW A Inspection door 12.5 90 19.5 4x150=600 80 620 862 90 801 KE 46 20- Ø 4.3 HOLE ARROW VIEW B 171 Front suction 7x100=700 116 100 4- Ø 5 HOLE 180 KG 801 1010 20-Ø 4.3 HOLE 1030 Bottom suction Item Name Description KA Liquid pipe connection port Ø6.4 flared connection KB Gas pipe connection port Ø12.70 flared connection KC Drain pipe connection VP20 (OD Ø26, ID Ø20) KD Drain hose ID Ø25 KE Control box / KF Transmission line / KG Power supply connection / KH Suspension bracket / KJ Air filter / KK Mounting foot / Notes 1. When installing optional accessories, refer to their respective documentation. 2. The ceiling depth varies according to the documentation of the specific system. 3D096747 276 VIEW ALL FXNQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXNQ63A FXNQ63A ARROW VIEW B 300 200 80 156 170 57.5 620 1080 1060 6x150=900 19.5 12.5 1190 ARROW VIEW A Inspection door 18-M4 1140 20 or more Suspension position 20 or more 10x100=1000 100 24 KH 130 63 620 100 179.4 KD KF 48 8.4 ARROW VIEW A 723 100 or more 500 KC KH 330 Suspension position KA 48 90 310 4-M8~M10 KB 26- Ø4.7 HOLE 60 Suspension bolt KK 300 or more 1190 10 42 50 Service space 240 or more 50 KJ KJ 9x100=900 1001 24-Ø4.3 HOLE KE 46 171 ARROW VIEW B Front suction 4- Ø5 HOLE 180 116 100 KG 9x100=900 1001 24- Ø4.3 HOLE 75 1210 1230 Item Bottom suction Name Description KA Liquid pipe connection port Ø9.52 flared connection KB Gas pipe connection port Ø15.9 flared connection KC Drain pipe connection VP20 (OD Ø26, ID Ø20) KD Drain hose ID Ø25 KE Control box / KF Transmission line / KG Power supply connection / KH Suspension bracket / KJ Air filter / KK Mounting foot / Notes 1. When installing optional accessories, refer to their respective documentation. 2. The ceiling depth varies according to the documentation of the specific system. 3D096740A FXNQ20-25A (mmH2O) (mmH2O) 50 4 40 3 2 4 H High ESP H Hi 30 High ESP 3 Low High ESP 20 t imi er l Low h ESP Hig P S fE to mi r li ESP pe rd Up nda Sta 1 The remote controller can be used to switch between 'high' and 'low'. The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP' and 'high ESP' by remote controller setting. 5 SP 5 6 Up p gh er li ES mit P of E 60 External static pressure [Pa] 6 Notes 2 SP of E H Standard ESP 10 1 M Standard ESP Low Standard ESP (mmH2O) 6 7 Air flow rate [m³/min] 8 9 (mmH2O) 3D086736B 277 VIEW ALL FXNQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXNQ32A (mmH2O) (mmH2O) 50 4 40 3 Notes The remote controller can be used to switch between 'high' and 'low'. 6 The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP' and 'high ESP' by remote controller setting. 5 30 4 H Up Hi pe gh r li ES mit P of ES P 5 External static pressure [Pa] 6 60 High ESP 3 M Low High ESP High ESP H Standard ESP SP 2 20 fE it o lim SP er rd E p a Up and St m er li Low ESP h Hig M Standard ESP 1 2 SP E it of 1 10 Low Standard ESP 7 6 (mmH2O) 8 9 Air flow rate [m³/min] (mmH2O) 3D081425C FXNQ40A (mmH2O) (mmH2O) 5 50 4 6 H High ESP 40 External static pressure [Pa] Low 3 The remote controller can be used to switch between 'high' and 'low'. The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP' and 'high ESP' by remote controller setting. 5 P 60 Up p Hig er lim hE SP it of E S 6 Notes 4 M High ESP High ESP H Standard ESP 30 2 20 1 10 3 M Standard ESP P ES of it im ESP l r d pe ar Up and St 2 SP fE to mi r li we P Lo h ES g i H 1 it of ESP Lower lim ESP Standard Low Standard ESP (mmH2O) 7 8 9 10 11 12 13 (mmH2O) Air flow rate [m³/min] 3D081426C 278 VIEW ALL FXNQ-A TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXNQ50A (mmH2O) (mmH2O) 7 7 Notes The remote controller can be used to switch between 'high' and 'low'. The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP' and 'high ESP' by remote controller setting. 6 6 5 External static pressure [Pa] 4 Up p Hig er lim hE SP it of E S P 5 High ESP 4 H Standard ESP 3 SP fE to mi r li we SP Lo gh E Hi U St ppe an r da lim rd it ES of E P SP 3 H M High ESP 2 2 M Standard ESP Low High ESP 1 1 it of ESP Lower lim ESP Standard Low Standard ESP 8 (mmH2O) 9 10 11 12 13 14 15 (mmH2O) Air flow rate [m³/min] 3D081427C FXNQ63A (mmH2O) (mmH2O) 7 6 6 External static pressure [Pa] 3 Up Hig per h E limi SP t of E 5 4 The remote controller can be used to switch between 'high' and 'low'. The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP' and 'high ESP' by remote controller setting. SP 7 Notes 5 H High ESP M High ESP 4 3 H Low Standard ESP High ESP P f ES 2 o mit er li Low ESP h Hig SP fE it o lim SP er rd E p Up nda Sta 2 M Standard ESP 1 Standard ESP (mmH2O) 8 1 it of ESP Lower lim ESP Standard Low 9 10 11 12 13 14 15 (mmH2O) Air flow rate [m³/min] 3D081429C 279 VIEW ALL FXLQ-P TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXLQ20-25P FXLQ20-25P 20 or more 100 or more 1750 or more 100 or more Discharge Suction Front of face 1000 or more Base Required installation space Piping hole (rear) 4-12x30 Oblong hole Hole for rear mounting Level adjusting screw in standard accessory 4xM6 2-12x18 Oblong hole Hole for fixing to the foor Wiring hole (bottom) Item 1 2 3 4 5 Name Liquid pipe connection Gas pipe connection Drain pipe connection Switch box Air filter Description Ø6.4 Flare connection Ø12.7 Flare connection O.D.Ø21 Piping hole (bottom) 3TW32294-1 FXLQ32-40P FXLQ32-40P 20 or more 100 or more 1750 or more 100 or more Discharge Suction Front of face 1000 or more Base Required installation space Piping hole (rear) 4-12x30 Oblong hole Hole for rear mounting Level adjusting screw in standard accessory 4xM6 2-12x18 Oblong hole Hole for fixing to the floor Item Name Liquid pipe connection Gas pipe connection Drain pipe connection Description ø6.4 Flare connection ø12.7 Flare connection O.D. ø21 Switch box Wiring hole (bottom) Piping hole (bottom) Air filter 3TW32314-1 280 VIEW ALL FXLQ-P TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FXLQ50-63P FXLQ50-63P 20 or more 100 or more 1750 or more 100 or more Discharge Suction Front of face 1000 or more Base Required installation space Piping hole (rear) 4-12x30 Oblong hole Hole for rear mounting Model Level adjusting screw in standard accessory 4xM6 2-12x18 Oblong hole Hole for fixing to the floor Item Name Liquid pipe connection Gas pipe connection Drain pipe connection Wiring hole (bottom) Piping hole (bottom) Description øA Flare connection øB Flare connection O.D. ø21 Switch box Air filter 3TW32334-1 281 VIEW ALL FTXJ-MW TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FTXJ20-35MW - FTXJ20-35MS FTXJ20-35MW FTXJ20-35MS Right side See note 2. Rear side Rear side Left side See note 2. Front grille fixing screws Located inside of the unit (ARC466A9) Up/down (automatic) Operating state Earth terminal (M4) On the front grille Nameplate On the front grille Blade angle Wireless remote control Service cover fixing screw On the front grille 998 1) O F F Signal transmitter Heating Cooling 2) O n Terminal block with earth terminal Located inside of the unit 58.5 21.5 30° 303 20° 50° See note 3. Bottom side 212 18 214 238 Intelligent Eye sensor Air discharge range 70° Fan Dry 189 Bottom side See note 3. Including mounting plate Intelligent Eye lamp 25° Operation lamp Timer lamp Room temperature sensor Located inside of the unit 25° 50° 50° Signal receiver Flap Indoor unit On/OFF switch Left/right (automatic) Bottom view Drain hose Connecting part Inside diameter: 16mm Outside diameter: 18mm The length of the connection hose outside the unit is 465mm. 35° 35° Gas pipe ø9.5CuT The length of the pipe outside the unit is 350mm. Liquid pipe ø6.4 The length of the pipe outside the unit is 400mm. 674.5 Indoor air flow 303 270.5 30 min 20 200 Required space for service and ventilation Minimum space for air passage Standard location of holes in the wall 50 min 50 min Service space 350 min 142 500 min 49 49 Service space 250 min 151 Required space for the signal receiver Notes ø 65 Hole for embedded piping 1. The ·( )· mark shows the piping direction. 2. In this case, the optional grille is required. 3. In this case, cut the grille according to the paper pattern. 2D092462A FTXJ50MW - FTXJ50MS FTXJ50MW FTXJ50MS Right side See note 2. Rear side Rear side Left side See note 2. Front grille fixing screws Located inside of the unit (ARC466A9) Up/down (automatic) Operating state Earth terminal (M4) On the front grille Nameplate On the front grille Blade angle Wireless remote control Service cover fixing screw On the front grille 998 1) O F F Signal transmitter Heating Cooling 2) O n Terminal block with earth terminal Located inside of the unit 58.5 21.5 30° 303 20° 50° 18 212 See note 3. Bottom side 70° Fan Dry 238 214 Intelligent Eye sensor Air discharge range 189 Bottom side See note 3. Including mounting plate Intelligent Eye lamp 25° Operation lamp Timer lamp Room temperature sensor Located inside of the unit 25° 50° 50° Signal receiver Flap Indoor unit On/OFF switch Left/right (automatic) Bottom view Drain hose Connecting part Inside diameter: 16mm Outside diameter: 18mm The length of the connection hose outside the unit is 465mm. 35˚ 35˚ Gas pipe ø12.7CuT The length of the pipe outside the unit is 350mm. Liquid pipe ø6.4 The length of the pipe outside the unit is 400mm. Required space for service and ventilation Minimum space for air passage 200 Indoor air flow 50 min 50 min Service space 49 49 Service space 350 min 142 151 ø 65 Hole for embedded piping 282 250 min Notes 1. The ·( )· mark shows the piping direction. 2. In this case, the optional grille is required. 3. In this case, cut the grille according to the paper pattern. 500 min 303 270.5 30 min 674.5 20 Standard location of holes in the wall Required space for the signal receiver 2D092503A VIEW ALL FTXA-AW TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings CTXA-AW/AS/AT - FTXA-AW/AS/AT ·30· or more Required space for service and ventilation Indoor air flow Minimum space for air passage Dimensions of fully opened front panel Including mounting plate 375 Piping length ·500· or more 189 ·50· or more Service space Front panel 295 Air outlet ·50· or more Service space ±·380·mm Drain hose 798 736 Right side Left side Intelligent Eye sensor Front grille ±·385·mm Gas pipe ±·420·mm Liquid pipe Rear side Blade angle Heating Cooling 70° 55° 180° Wi-Fi label Located inside of the unit 180° 20° 20° 150° 110° Nameplate Located inside of the unit Indoor unit On/OFF switch Timer lamp Intelligent Eye lamp Operation lamp Signal receiver Standard location of holes in the wall 798 17 Front grille fixing screws Located inside of the unit Horizontal blade 605 110 Humidity sensor Located inside of the unit Wireless remote control Signal transmitter 65 65 150 ±·400·mm ·Ø 12.7 / 9.5mm· CuT ±·440·mm Liquid pipe ·Ø 6.4mm· CuT 189 155 Outer dimensions of the unit 44.5 O 44.5 21.5 O 58.5 Gas pipe Hole for embedded piping ±·450·mm ARC466A33 Drain hose Inside diameter: ·14·mm Outside diameter: ·16·mm Hole for embedded piping 3D113513B CTXA-AW/AS/AT - FTXA-AW/AS/AT • Main specifications • Outside size Items Outside 150.9 46.9 Material of resin WARNING VOLTAGE Applicable laws Ambient conditions 27.5 Connector(Model: B04B-PASK) (1pin:Vin 2pin:Ans 3pin:HL 4pin:GND) Storage temperature Operating ambient temperature Operating ambient humidity Basic specifications Input voltage Maximum output voltage Rating output voltage Rating output current Hi Lo ON/OFF Hi <=> Lo Switching Current monitor Detectable over current Detectable low voltage Generation amount of Ozone Method of mounting 8.5 • Method of mounting Don’t blockage the vent of streamer unit. Ensure the exit wind speed 0.2m/sec of the vent. Ensure the spatial distance 8.5mm over at the vent of streamer unit. R20 Ensure the spatial distance 8.5mm over at the vent of streamer unit by products. 20 138.4 0.2m/s over Contents 150.9 × 46.9 × 27.5mm 100g ABS UL94-5VA Over CTI600V Electrical Appliance and Material Safety Act IEC60335-1(4th), IEC60335-2-65(4th) -25~70 (Non-Energization) -10~60 (Energization) 5~95%RH (No dew deposit) 14V±5% 6.5±0.5kV 5.0±0.5kV 55.5μA±10% 10μA±10% Inputted voltage into Vin (ON/OFF) Inputted 5V into HL (Loe tap) Yes Yes Under 3kV 4.26ml/hr (Hi 14±2℃ 50±10%RH) Fixing by the right and left hook Fixing by the screw section Outside size Weight Material Flame retardance Tracking index R20 The vent of streamer unit (The other side the same) 8.5 Flow of air Don’t arrange conduction material within 20mm of the aluminum tape (Except for the unit fixing screw). 3D095530G 283 VIEW ALL FVXG-K TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FVXG25-35K FVXG25-35K (Half concealed) Model name plate (inside) Max unit fixing screw Radiant lamp Gas pipe (ø 9.5 CuT) 85 (Half concealed) Operation lamp Installation plate Timer Lamp Room temp. thermistor Terminal block with earth terminal Hole for splint Hole for piping Hole for splint Fixed screws for front grille (inside) General rating name plate Drain socket Standard installation fixed screws (2 Locations) (Half concealed) Half concealed installation fixed screws (4 Locations) Liquid pipe (ø 6.4 CuT) Signal receiver and indoor unit on/off switch Fixed screws for air outlet cover (inside) Signal transmitter Hole for piping Drain hose VO20 I.D. ø 20 O.D. ø 26 L 220 Installation required space Infrared remote control (ARC466A2) Hole for piping Adjusting the air flow direction Air flow (indoor) (Wall hole) Right/left (manual) Up/down (automatic) Cool, Dry 150 Min. (For maintenance) Heat (Wall hole) (For performance) 50 Min. (For maintenance) Floor Floor 3D071595 Wall hole for half concealed Note) The mark (²) shows piping direction FVXG50K FVXG50K (Half concealed) Model name plate (inside) Radiant lamp Gas pipe (ø 9.5 CuT) 85 (Half concealed) Operation lamp Installation plate Timer lamp Room temp. thermistor Terminal block with earth terminal Hole for splint Hole for piping Hole for splint Fixed screws for front grille (inside) Drain socket Standard installation fixed screws (2 Locations) General rating name plate (Half concealed) Main unit fixing screw Liquid pipe (ø 6.4 CuT) Signal receiver and indoor unit on/off switch Fixed screws for air outlet cover (inside) Half concealed installation fixed screws (4 Locations) Signal transmitter Hole for piping Drain hose VO20 I.D. ø 20 O.D. ø 26 L 220 Installation required space Infrared remote control (ARC466A2) Hole for piping Adjusting the air flow direction Air flow (indoor) (Wall hole) Right/left (manual) 284 Heat (Wall hole) (For performance) 150 Min. (For maintenance) Floor Floor Note) The mark (²) shows piping direction Up/down (automatic) Cool, Dry 50 Min. (For maintenance) Wall hole for half concealed 3D071596 VIEW ALL FVXM-F TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings FVXM25-35F FVXM25-35F Adjusting the air flow direction Up/down (automatic) 25° 40 ° 1.The -> mark shows the piping direction. 20° 20° ° ° 90 90 Operation lamp Signal receiver Timer lamp Indoor unit On/OFF switch Air outlet selection switch Model name ARC452A1 Wireless remote control 210 Front grille fixing screws 644 185.8 ° ° Lower air outlet 18 Half concealed 90 90 Upward air flow limit ON 45° 58 Signal transmitter 700 666 45° Upper air outlet 45° Heating Dry Upward air flow limit OF 45° Notes Cooling Left/right (manual) 95 Half concealed Pitch of fixing holes ON/OFF Adjusting the air flow direction Half concealed 90 120.5 584 261 224.5 70 20° 20° 600 261 224.5 70 90 120.5 90 152 Wall hole 149 160 85 39 115 44 70 39 585 ~595 Hole for piping Wall hole Wall hole 121 136 670 ~690 For performance 70 18 83.2 Drain hose VP20 L=220 mm Inside diameter: 20mm Outside diameter: 26mm Pitch of fixing holes 585 ~595 Terminal block with earth terminal Room temperature sensor Liquid pipe connection Ø6.4 CuT Gas pipe connection Ø9.5 CuT 120.5 584 600 25° 40 ° MIN 50 Front grille fixing screws 83.2 39 For maintenance For performance Nameplate 630 ON/O FF MIN 50 ON/OFF 152 400 149 160 370 85 230 For performance 70 70 Hole for piping Half concealed 121 136 Drain socket 44Hole for piping Air flow Required space ARC452A1 95 670 ~690 250 400 120.5 90 250 370 230 MIN 50 115 18 Wireless remote control 210 Wall hole Hole for molding 18 39 18 83.2 Drain hose VP20 L=220 mm Inside diameter: 20mm Outside diameter: 26mm Pitch of fixing holes Operation lamp Signal receiver Timer lamp Indoor unit On/OFF switch Air outlet selection switch Model name Front grille fixing screws 630 For maintenance ° ° Drain socket 644 Pitch of fixing holes ON/O FF 90 90 Air flow Required space ° ° Front grille fixing screws Half concealed 90 90 Upward air flow limit ON 45° 45° 58 Signal transmitter 700 666 Lower air outlet 83.2 1.The -> 45° 45° Upper air outlet Hole for molding 18 Hole for piping Notes Heating Dry Upward air flow limit OF Half concealed Up/down (automatic) Cooling Left/right (manual) Terminal block with earth terminal Room temperature sensor Liquid pipe connection Ø6.4 CuT Gas pipe connection Ø9.5 CuT mark shows the piping direction. 185.8 Nameplate FVXM25-35F MIN 50 For performance 3D1087003D108700 Wall hole for half concealed installation Wall hole for half concealed installation FVXM50F Adjusting the air flow direction Notes Up/down (automatic) Cooling Heating Dry Signal transmitter 1.The -> mark shows the piping direction. 25 ° 40 ° Left/right (manual) 45° 90 20° 45° Timer lamp Indoor unit On/OFF switch ° ° 90 90 Lower air outlet Upward air flow limit ON 18 Signal receiver Half concealed ° ° 45° 58 Operation lamp 700 666 90 Upper air outlet Upward air flow limit OFF 20° 45° 185.8 FVXM50F Air outlet selection switch Model name Front grille fixing screws ARC452A1 Wireless remote control 210 95 644 Half concealed Pitch of fixing holes ON/OFF Nameplate Pitch of fixing holes 600 90 136 95 Half concealed ON/OFF Nameplate 152 70 90 149 160 85 Wall hole 585 ~595 70 83.2 121 136 152 670 ~690 For performance MIN 50 For maintenance Pitch of fixing holes Liquid pipe connection Ø6.4 CuT Gas pipe connection Ø12.7 CuT 18 Drain hose VP20 L=220 mm Inside diameter: 20mm Outside diameter: 26mm 630 ON/O FF For performance 600 Front grille fixing screws 83.2 Required space MIN 50 261 224.5 70 400 Drain socket Hole for molding 18 Hole39 for piping MIN 50 39 115 Wall hole 44 Hole for piping 70 39 For performance Wall hole for half concealed installation Wall hole 44 Hole for piping Air flow 585 ~595 115 Terminal block with earth terminal Room temperature sensor Wall hole 120.5 90 149 250 160 370 230 85 70 For performance For maintenance MIN 50 39 ARC452A1 Wireless remote control 210 121 670 ~690 ON/O FF 185.8 261 224.5 70 120.5 584 Air outlet selection switch Model 83.2name 120.5 584 630 Pitch of fixing holes Front grille fixing screws Drain hose VP20 L=220 mm Inside diameter: 20mm Outside diameter: 26mm Gas pipe connection Ø12.7 CuT Timer lamp Half concealed Air flow Required space ° 644 18 Indoor unit On/OFF switch 18 90 ° Lower air outlet Front grille fixing screws 83.2 58 Signal receiver Half concealed Drain socket 90 Hole for molding 18 Hole for piping Upward air flow limit ON Liquid pipe connection Ø6.4 CuT Operation lamp 700 666 20° 20° 45° 45° Signal transmitter 1.The -> mark shows the piping direction. 40 ° ° 400 25 ° 120.5 90 90 Upper air outlet Upward air flow limit OFF ° 230 45° 45° Notes Up/down (automatic) Cooling Heating Dry 90 250 370 Room temperature sensor Adjusting the air flow direction Left/right (manual) Half concealed FVXM50F Terminal block with earth terminal 3D108701 3D108701 Wall hole for half concealed installation 285 Technical drawings Hot water HXY-A8287 HXHD-A8288 286 VIEW ALL HXY-A8 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings HXY-A8 HXY-A8 Required space for service and ventilation Hole (ø12) for fixation to the wall Water out connection (1-1/4” F BSP) Water in connection (1-1/4” F BSP) Refrigerant liquid connection ø9.52 (flare) Refrigerant suction connection ø15.9 (flare) Pump User interface Safety valve (pressure) Air purge Expansion vessel Pressure gauge Heat exchanger (refrigerant / water) Shut off valve with drain / fill valve (1-1/4`` F BSP) (included accessory) Water filter Power supply / Communication wire entrance Service door Switchbox terminals ESP (kPa) HXY-A8 0 35 40 45 50 55 60 65 70 75 80 85 90 3D079938 HXY-A8 Unit ESP / 4000rmp / ∆T=5°C Unit ESP / 3800rmp / ∆T=8°C ∆ Maximum ESP if ∆T=5°C (heating nominal) □ Maximum ESP if ∆T=5°C (cooling nominal) 15 17.5 20 22.5 25 27.5 30 32.5 35 37.5 40 Flow (l/min) ESP: Flow External Static Pressure Water flow through the unit Notes 1. Selecting a flow outside the operating area can damage the unit or cause the unit to malfunction. See also the minimum and maximum allowed water flow range in the technical specifications. 2. Water quality must be according to EU directive 98/83 EC. 3D097625 287 VIEW ALL HXHD-A8 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings HXHD125A8 HXHD-A 1 Detail A Scale 1/3 If required (e.g. Wall fixation) Pressure gauge can be removed from waterfilter, maximum distance between waterfilter and pressure gauge ± 600 mm Left Installation 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Right installation Remote control (delivered as accessory) Installation location is outside the unit Discharge pipe connection ø12.7 solder (R410a) Liquid pipe connection ø9.5 solder (R410a) R134a Service ports 5/16” are (2x) Pressure gauge Blow off valve Drain valve water circuit Air purge Shut-off valves (2x) Wster filter Water in connection G 1° (female) Water out connection G 1° (female) Control wiring intake (knock-out hole ø37) Power supply wiring intake (knock-out hole ø37) Knock-out holes for refrigerant piping and water piping Levelling feet Discharge stop valve ø12.7 solder (R410a) Liquid stop valve ø9.5 solder (R410a) Detail A 3TW59914-1B(1) HXHD125A8 HXHD-A Left Installation Right installation Upwiring Screw fixation of top plate (both sides) Model HXHD-A8 A 355 B 270 C 300 Min. 600 (Space required for switch box removal) 3TW59914-1B(2) 288 VIEW ALL HXHD-A8 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings HXHD200A8 HXHD200A8 Detail A Scale 1/3 Left installation Right installation If required (e.g. wall fixation) Pressure gauge can be removed from waterfilter. Maximum distance between waterfilter and pressure gauge: +/- 600mm. HXHD200A8 Detail A Scale 1/3 Left installation If required (e.g. wall fixation) Pressure gauge can be removed from waterfilter. Maximum distance between waterfilter and pressure gauge: +/- 600mm. Detail A 1 Gas pipe connection ø15.9 solder (R410A) 2 Liquid pipe connection ø9.5 solder (R410A) 3 R134a service ports ø12.7 flare 4 Pressure gauge 5 Blow off valve 6 Drain valve water circuit 7 Air purge 8 Shut-off valves 9 Water filter 10 Water in connecting G 1” (female) 11 Water out connecting G 1” (female) 12 13 Control wiring intake (knock-out hole ø37) Right installation Power supply wiring intake (knock-out hole ø37) 14 1 Gas pipe connection solder (R410A) Knock-out holes for refrigerant piping andø15.9 water piping 15 Levelling feet 16 4 Pressure gauge Remote controller (delivered as accessory) installation location 5 Blow off valve is outside the unit 2 Liquid pipe connection ø9.5 solder (R410A) 3 R134a service ports ø12.7 flare 6 Drain valve water circuit 7 Air purge 8 Shut-off valves 9 Water filter 10 Water in connecting G 1” (female) 11 Water out connecting G 1” (female) 12 Control wiring intake (knock-out hole ø37) 13 Power supply wiring intake (knock-out hole ø37) 14 Knock-out holes for refrigerant piping and water piping 15 Levelling feet 16 Remote controller (delivered as accessory) installation location is outside the unit Detail A 3TW59854-1 3TW59854-1 289 VIEW ALL HXHD-A8 TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings HXHD125A8 ESP [kPa] HXHD-A8 120 110 100 90 80 70 60 50 40 30 20 10 0 Unit ESP without 3-way valve Unit ESP including 3-way valve Maximum ESP if ∆ T=10°C Maximum ESP if ∆ T=5°C 5 7 9 11 13 15 17 19 21 23 25 Flow [l/min] 27 29 31 33 35 37 39 41 Notes 1. The ESP curves are the maximum ESP curves for different (T types (pump rpm=4200 for (T=5°C; pump rpm=3800 for (T=10°C). 2. The pump of the indoor unit is inverter-controlled and functions to have a fixed (T between the return water temperature and the leaving water temperature. In case of installing a domestic hot water tank, there is an additional pressure drop over the 3-way valve (delivered as an accessory with the tank). ESP: External Static Pressure Flow: water flow through the unit Warning 1. Selecting a flow outside the operating area can damage the unit or cause the unit to malfunction. See also the minimum and maximum allowed water flow range in the technical specifications. 2. Water quality must be according to EU directive 98/83 EC. 3D097621 HXHD200A8 HXHD200A8 HXHD200A* Indoor unit ESP curve 100 Unit ESP without 3-way valve 90 Unit ESP including 3-way valve Maximum ESP if ΔT=·10·°C ESP [kPa] 80 70 60 50 40 30 20 10 0 Notes 15 17 19 21 23 25 27 29 31 33 35 37 Flow [l/min] 39 41 43 45 47 49 51 1. The ESP curves are the maximum ESP curves, with and without domestic hot water tank installed on top of the indoor unit (pump rpm: 4000). The pump of the indoor unit is inverter-controlled and functions to have a fixed ΔT between the return water temperature and the leaving water temperature. 2. In case of installing a domestic hot water tank, there is an additional pressure drop over the 3-way valve (delivered as an accessory with the tank). ESP: External Static Pressure Flow: water flow through the unit Warning 1. Selecting a flow outside the operating area can damage the unit or cause the unit to malfunction. See also the minimum and maximum allowed water flow range in the technical specifications. 2. Water quality must be according to EU directive 98/83 EC. 3D113718 290 Technical drawings Biddle air curtains CYVS_DK / CYVM_DK / CYVL_DK 292 291 Detailed technical drawings CYVS_DK_FBN/FSN / CYVM_DK_FBN/FSN / CYVL_DK_FBN/FSN CYVS_DK_FBN/FSN CYVM_DK_FBN/FSN CYVL_DK_FBN/FSN 500 250 250 40 100 197 A B O9.2 Suction grid with filter 98 H 27 D Type CYVS-DK-FBN/FSN CYVM-DK-FBN/FSN CYVL-DK-FBN/FSN L 1,000 - 1,500 2,000 - 2,500 1,000 - 1,500 2,000 - 2,500 H D U A B 270 590 93 171 119 370 774 124.5 245.5 U L 200 CU0954X-000 REMARKS 1 The 2,500mm large devices have 3 suspension brackets, where the third bracket is mounted at half the length of the device. CYVS_DK_CBN/CSN / CYVM_DK_CBN/CSN / CYVL_DK_CBN/CSN CYVS_DK_CBN/CSN CYVM_DK_CBN/CSN CYVL_DK_CBN/CSN 500 250 250 40 100 197 A B O9.2 The finishing profiles are supplied separately. Suction grid with filter 98 H 27 Screw-eye M6 L Number of suction grids per device Device length Number Suction grid length 1000 / 1500 1 1,000 / 1,500 2000 / 2500 2 1,000 / 1,250 G D CYVL-DK-CBN/CSN D U A B E F G 821 93 171 119 250 411 260 F H 270 E L 1,000 - 1,500 2,000 - 2,500 1,000 - 1,500 2,000 - 2,500 370 1,105 124.5 245.5 200 181.5 563.5 U Type CYVS-DK-CBN/CSN CYVM-DK-CBN/CSN D *1 drain grid per device 360 REMARKS 292 1 The 2,500mm large devices have 3 suspension brackets, where the third bracket is mounted at half the length of the device. 2 The mounting holes for finishing profiles in a lowered ceiling (L+8) x (D+8) mm L CU0955X-000 Detailed technical drawings CYVS_DK_RBN/RSN / CYVM_DK_RBN/RSN / CYVL_DK_RBN/RSN CYVS_DK_RBN/RSN CYVM_DK_RBN/RSN CYVL_DK_RBN/RSN 500 250 No ducts are supplied 250 40 100 197 A B O9.2 No ducts are supplied The finishing profiles are supplied separately. K Suction grid with filter 98 12 5 6 8 Number of suction grids per device Device length Number Suction grid length 1000 / 1500 1 1,000 / 1,500 2000 / 2500 2 1,000 / 1,250 *1 drain grid per device Type L H CYVS-DK-RBN/RSN CYVM-DK-RBN/RSN 1,000 - 1,500 270 2,000 - 2,500 - 1,500 CYVL-DK-RBN/RSN 1,000 2,000 - 2,500 370 E G F J D S U A B E F G 561 80125 90 171 119 92 139 260 745 80125 121.5 245.5 200 123.5 170 360 J T K M T 1048-1548 20482548 1048-1548 1044-1544 408 Ø250 2044-2544 20482548 308 Ø160 1044-1544 2044-2544 F 2500 10 U 2000 7 101.5 H 1500 S Number of ducts per device Type 1000 CYVS-DK-RBN/RSN 5 CYVM-DK-RBN/RSN CYVL-DK-RBN/RSN 3 27 D L M CU0956X-000 REMARKS 1 The 2,500mm large devices have 3 suspension brackets, where the third bracket is mounted at half the length of the device. 2 Holes (for finishing profiles) - drain (L+8) x (E+8) mm - suction (L+8) x (G+8) mm. 293 Technical drawings Ventilation ALB-LBS/RBS295 VAM-FC / VAM-J 301 VKM-GB / VKM-GBM 309 294 VIEW ALL ALB-LBS DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings ALB02RBS/LBS CONDENSATE OUTLET 1/4”G TOP VIEW BOTTOM VIEW ELECTRIC SWITCH BOX ALB03RBS/LBS CONDENSATE OUTLET 1/4”G BOTTOM VIEW TOP VIEW ELECTRIC SWITCH BOX 295 Detailed technical drawings VIEW ALL ALB-RBS DRAWINGS ON MY.DAIKIN.EU ALB04RBS/LBS CONDENSATE OUTLET 1/4”G TOP VIEW BOTTOM VIEW ELECTRIC SWITCH BOX ALB05RBS/LBS CONDENSATE OUTLET 1/4”G TOP VIEW ELECTRIC SWITCH BOX 296 BOTTOM VIEW VIEW ALL ALB-LBS DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings ALB06RBS/LBS CONDENSATE OUTLET 1/4”G TOP VIEW BOTTOM VIEW ELECTRIC SWITCH BOX ALB07RBS/LBS CONDENSATE OUTLET 1/4”G TOP VIEW BOTTOM VIEW ELECTRIC SWITCH BOX 297 VIEW ALL ALB-RBS DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings External static pressure (Pa) ALB02RBS/LBS SFPv 2 400 SF Pv 20 00 The diagram shows the available external pressure for the duct system given an airflow. SFPv = Specific Fan Power (W/m3/s) Pv SF SF Pv 80 0 00 16 SF Pv The SFPv curves are referring to the complete unit. Moreover, it includes power to both supply and extract fan divided by either the supply or extract volume whichever is the greater. 12 00 Nominal working point Airflow (m3/h) External static pressure (Pa) ALB03RBS/LBS SF Pv 24 00 The diagram shows the available external pressure for the duct system given an airflow. SFPv = Specific Fan Power (W/m3/s) SF Pv SFP v 800 SF Pv 12 SF Pv 00 Airflow (m3/h) 298 16 00 20 00 The SFPv curves are referring to the complete unit. Moreover, it includes power to both supply and extract fan divided by either the supply or extract volume whichever is the greater. Nominal working point VIEW ALL ALB-LBS DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings ALB04RBS/LBS 400 External static pressure (Pa) SFPv 2 SFPv 2000 SF Pv The diagram shows the available external pressure for the duct system given an airflow. 16 00 SFPv = Specific Fan Power (W/m3/s) SF Pv SF Pv 80 0 12 00 The SFPv curves are referring to the complete unit. Moreover, it includes power to both supply and extract fan divided by either the supply or extract volume whichever is the greater. Nominal working point Airflow (m3/h) ALB05RBS/LBS v 240 0 External static pressure (Pa) SFP SFP v 200 0 SF Pv 16 00 The diagram shows the available external pressure for the duct system given an airflow. SFPv = Specific Fan Power (W/m3/s) SF Pv SFP v 12 00 The SFPv curves are referring to the complete unit. Moreover, it includes power to both supply and extract fan divided by either the supply or extract volume whichever is the greater. 800 Nominal working point Airflow (m3/h) 299 VIEW ALL ALB-RBS DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings ALB06RBS/LBS 2 40 0 External static pressure (Pa) SFPv SFP v 200 0 SF Pv The diagram shows the available external pressure for the duct system given an airflow. 16 00 SFPv = Specific Fan Power (W/m3/s) SF Pv SF Pv 12 00 80 0 The SFPv curves are referring to the complete unit. Moreover, it includes power to both supply and extract fan divided by either the supply or extract volume whichever is the greater. Nominal working point Airflow (m3/h) ALB07RBS/LBS 00 External static pressure (Pa) SFPv 24 SFP v 200 0 The diagram shows the available external pressure for the duct system given an airflow. SF Pv SF Pv SF Pv 12 00 80 0 00 SFPv = Specific Fan Power (W/m3/s) The SFPv curves are referring to the complete unit. Moreover, it includes power to both supply and extract fan divided by either the supply or extract volume whichever is the greater. Nominal working point Airflow (m3/h) 300 16 VIEW ALL VAM-FC9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL VAM-J TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VAM150FC9 VAM150FA Maintenance space for the heat exchange elements, the air filters and fans Switch box Ceiling hook 4-14x40 oval hole Inspection hole Ø 450 285 600 Maintenance over 104 120.3 67 20 149 Supply air fan 120~250 269 SA 104 124 288 560 EA Exhaust air to outdoors 718 Sealing 20 120 Fresh air from outdoors (Outdoor air) 8 8 Return air from room Sealing 164 509 RA 288 124 164 OA Supply air to room Damper plate 149 Exhaust air fan (Maintenance cover) Exhaust spacer (Switch box) 145 760 Ø97 Ø200 145 Air filters Heat exchange elements NOTE 1 Be sure to provide the inspection hole (450x450 mm) to inspect the air filters, the exchange elements and fans. 3TW27874-1 3TW27874-1 VAM250FC9 VAM250FA Maintenance space for the heat exchange elements, the air filters and fans Switch box Ceiling hook 4-14x40 oval hole Inspection hole Ø 450 285 600 Supply air fan 120~250 269 Maintenance over 104 120.3 67 20 149 SA 509 124 288 560 164 RA OA 288 124 164 Supply air to room EA Return air from room 104 Sealing 718 20 120 Exhaust air to outdoors Sealing 8 8 Fresh air from outdoors (Outdoor air) Damper plate 149 Exhaust air fan (Maintenance cover) 760 145 Ø97 Ø200 (Switch box) 145 Heat exchange elements Air filters NOTE 1 Be sure to provide the inspection hole (450x450 mm) to inspect the air filters, the exchange elements and fans. 3TW27884-1 3TW27884-1 301 VIEW ALL VAM-J TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL VAM-FC9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VAM350-500J Ceiling hook ·4· - ·12· x ·40·mm oblong hole Exhaust air fan Damper panel 1045 Sealing material 122 22 305 122 Sealing material RA Sealing material OA 125 173 137 417 291 126 Exhaust air to outdoors Exhaust air 292 417 837 866 883 EA SA Supply air fan 122 Switch box 900 78 22 190 Inspection hole Maintenance space for the air filters, heat exchangers and fans Sealing material 200 - 300 ≥ 675 475 Sealing material Heat exchanger 78 1113 213 197 Switch box Air filter Maintenance cover Notes : 137 173 Supply air to room Supply air Fresh outdoor air Outdoor air 122 Sealing material Return air from room Room air 1.To allow for the inspection of the air filters, heat exchangers, and fans, be sure to provide the inspection hole. 3D112815C VAM650J 1266 Damper panel Sealing materi al Sealing material Sealing material 154 22 368 154 Ceiling hook ·4· - ·12· x ·40·mm oblong hole Exhaust air fan RA EA 272 491 887 920 933 Sealing material 162 211 SA Supply air to room Supply air OA Fresh outdoor air Outdoor air 200-300 ≥ 700 500 Sealing material Sealing material 22 186 Supply air fan Switch box 154 Return air from room Room air 220 211 162 493 272 222 Exhaust air to outdoors Exhaust air Inspection hole Option ·KRP2A51· Mounting plate 154 Option ·BRP4A50A· 1100 Maintenance space for the air filters, heat exchangers and fans Heat exchanger 1354 262 245 83 Notes : Maintenance cover 83 Switch box Air filter 1. To allow for the inspection of the air filters, heat exchangers, and fans, be sure to provide the inspection hole. 302 3D113502A VIEW ALL VAM-FC9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL VAM-J TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VAM800-1000J Ceiling hook ·4· - ·12· x ·40·mm oblong hole Exhaust air fan Damper panel 1266 Sealing material 154 22 368 154 Sealing material RA Sealing material 212 SA Supply air to room Supply air OA Supply air fan Sealing material Fresh outdoor air Inspection hole 650 Sealing material Maintenance space for the air filters, heat exchangers and fans 154 200-300 ≥ 850 Sealing material 22 192 Outdoor air 154 162 Room air 207 162 628 389 239 Exhaust air to outdoors Exhaust air 212 Return air from room 399 606 1144 1172 1189 EA Switch box 1100 Heat exchanger 1354 83 83 262 245 Sealing material Maintenance cover Notes : Switch box Air filter 1. To perform maintenance on the air filter, it is required to provide a service access panel. 3D112817D VAM1500-2000J (2x) 731 150 Sealing material EA Sealing material Maintenance space for the air filters, heat exchangers and fans Sealing material Inspection hole 384 air fan 20 200 - 300 ≥ 850 20 198 (2x) Supply 650 Sealing material 150 150 SA Supply air to room Supply air Fresh outdoor air Outdoor air 345 345 Return air from room Room air 218 360 577 1144 1172 1188 Exhaust air to outdoors Exhaust air OA 150 RA 1194 599 348 250 380 (4x) Sealing material Damper panel Ceiling hook ·4· - ·14· x ·40·mm oblong hole 1266 (4x) Option ·EKPLEN200· Sealing material 20 20 384 Exhaust air fan Switch box 1100 Heat exchanger 130 261 261 130 26 1354 Sealing material Notes : 405 350 330 Switch box 10 24 621 Option ·KRP2A51· Mounting plate Maintenance cover Option ·BRP4A50A· Air filter 1. To allow for the inspection of the air filters, heat exchangers, and fans, be sure to provide the inspection hole. 3D112818C 303 VIEW ALL VAM-J TECHNICAL DRAWINGS ON MY.DAIKIN.EU VAM150FC Detailed technical drawings VIEW ALL VAM-FC9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VAM150FC9 250 20m 200 External static pressure [Pa] 15m 150 Ultra-high 10m 100 High 5m Low 50 Ø 100 Pipe length 0 0 50 Notes 100 150 Air flow rate [m³/h] 200 250 1. The fan speeds are valid for ·230·V, ·50·Hz power supply. VAM250FC 4D100379 VAM250FC 4D100379 250 External static pressure [Pa] 200 Ultra-high Ø 150 Pipe length 150 High 40m 100 Low 30m 20m 50 10m 0 0 Notes 50 100 150 Air flow rate [m³/h] 200 250 300 1. The fan speeds are valid for ·230·V, ·50·Hz power supply. 4D100380 4D100380 304 VIEW ALL VAM-FC9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL VAM-J TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VAM350J 250 UH15 150 Ultra-high speed H15 125 m UH8 L15 H8 100 m External static pressure [Pa] External static pressure [Pa] 200 75 m 100 UH1 L8 50 m 50 25 m Ø200 Duct length L1 H1 0 100 150 200 250 300 350 400 300 250 200 150 UH15 100 UH8 50 UH1 0 150 450 200 High speed 200 150 100 H15 50 0 150 200 250 H1300 H8 350 400 250 300 350 400 450 Air flow rate [m³/h] External static pressure [Pa] External static pressure [Pa] Air flow rate [m³/h] 450 Air flow rate [m³/h] Notes 1.The fan curves are determined with ·1/3· of the ESP on the outdoor side (·EA & OA·), and ·2/3· of the ESP on the indoor side (·RA & SA·). EA = Exhaust air OA = Outdoor air RA = Room air SA = Supply air 2. Measured according to ·JIS B 8628 - 2003· Low speed Ultra-high speed High speed Low speed 200 150 100 50 0 L1 100 150 200 250 300 L15 L8 350 400 450 Air flow rate [m³/h] Legend L1 = Low speed lower limit L8 = Low speed factory setting L15 = Low speed upper limit H1 = High speed lower limit H8 = High speed factory setting H15 = High speed upper limit UH1 = Ultra-high speed lower limit UH8 = Ultra-high speed factory setting UH15 = Ultra-high speed upper limit 3D113493A VAM500J 250 External static pressure [Pa] 200 150 UH1 L15 L15 H8 100 80 m H8 60 m 40 m H1 L8 50 20 m L1 0 150 Ø200 Duct length 200 250 300 350 400 450 500 550 External static pressure [Pa] 100 m UH15 UH15 UH8 H15 H15 600 Ultra-high speed 250 200 150 100 UH1 0 250 300 High speed 200 150 100 0 200 H15 H1 250 300 350 400 450 500 550 Air flow rate [m³/h] Notes 1.The fan curves are determined with ·1/3· of the ESP on the outdoor side (·EA & OA·), and ·2/3· of the ESP on the indoor side (·RA & SA·). EA = Exhaust air OA = Outdoor air RA = Room air SA = Supply air 2. Measured according to ·JIS B 8628 - 2003· 350 400 450 500 550 600 Air flow rate [m³/h] H8 600 External static pressure [Pa] External static pressure [Pa] Air flow rate [m³/h] 50 UH15 UH8 50 Low speed Ultra-high speed High speed Low speed 200 150 100 50 0 150 L15 200 L1 250 300 350 400 450 L8 500 Air flow rate [m³/h] Legend L1 = Low speed lower limit L8 = Low speed factory setting L15 = Low speed upper limit H1 = High speed lower limit H8 = High speed factory setting H15 = High speed upper limit UH1 = Ultra-high speed lower limit UH8 = Ultra-high speed factory setting UH15 = Ultra-high speed upper limit 3D113494A 305 VIEW ALL VAM-J TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL VAM-FC9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VAM650J 250 UH15 150 Ultra-high speed UH8 H15 200 m H8 160 m UH1 L15 H1 100 120 m 80 m L8 50 External static pressure [Pa] External static pressure [Pa] 200 40 m Ø250 Duct length L1 0 250 350 450 550 650 750 250 200 150 100 UH15 50 0 UH8 350 450 Air flow rate [m³/h] 200 150 100 H15 H1 350 450 H8 550 650 Low speed External static pressure [Pa] External static pressure [Pa] High speed 0 250 750 Air flow rate [m³/h] 250 50 650 UH1 550 750 Air flow rate [m³/h] Notes 1.The fan curves are determined with 1/3 of the ESP on the outdoor side (EA & OA), and 2/3 of the ESP on the indoor side (RA & SA). EA = Exhaust air OA = Outdoor air RA = Room air SA = Supply air 2. Measured according to ·JIS B 8628 - 2003· 200 Ultra-high speed High speed Low speed 150 100 50 L15 0 L1 250 30 550 L8 450 650 750 Air flow rate [m³/h] Legend L1 = Low speed lower limit L8 = Low speed factory setting L15 = Low speed upper limit H1 = High speed lower limit H8 = High speed factory setting H15 = High speed upper limit UH1 = Ultra-high speed lower limit UH8 = Ultra-high speed factory setting UH15 = Ultra-high speed upper limit 3D113495A VAM800J 300 250 x x 180m 250 180m 180m 150m 200 200 u u 300 250 External static pressure [Pa] External static pressure [Pa] 300 200 150m 150m 120m 150 150 u 150 120m 120m 90m 100 90m 90m 60m 100 L8 100 xL850 50 L8 L1 , L1 300 0 60m 60m 30m 50 L1 0 400 0 300 u u 500 700 600 , 800 Air flow rate (m3/h) 300 400 500 600 700 Air flow rate 600 [m³/h] 400 700 500 800 800 x Ø250 30m 30m Duct length Ø250 Ø250 900 , Duct length Duct length 900 350300 350 300250 300 250200 250 200150 200 u 150100 150 x 100 50 100 x 50 0 0 900 High speed 300 200 150 150 u 150 150 100 0 H15 400 400 u H15 HS 500 0 400 500 600 500 600 700 800 Air flow rate (m3/h) 600 700 700 800 flow rate (m /h) Air flow rate (m /h) Air Air flow rate [m³/h] 3 3 Notes 1.The fan curves are determined with 1/3 of the ESP on the outdoor side (EA & OA), and 2/3 of the ESP on the indoor side (RA & SA). EA = Exhaust air OA = Outdoor air RA = Room air SA = Supply air 2. Measured according to ·JIS B 8628 - 2003· 306 800 600 900 800 900 900 Ultra-high speed High speed Low speed 250 900 HS 800 900 200 , , ,150 , 100 100 u50 50 50 0 u H15 100 50 500 200 200 200 150 50 700 Air flow rate (m /h) Air600 flow rate700[m³/h] 700 800 3 500 Low speed 250 250 250 250 200 100 600 500 400 Air flow rate (m3/h) Air flow rate (m3/h) External static pressure [Pa] External static pressure [Pa] u 3 300 300 250 u 50 400 0 400 Air flow rate Air flow (m /h) rate (m /h) 3 Ultra-highspeed Ultra-high Ultra-high speed speed 350 , , - - - 100 50 0 HS 900 300 400 500 600 700 800 900 0 0 Air flow rate (m3/h) 300 300 400 400 500 500 600 600 700 700 800 800 900 900 Air flow rate Air flow (m[m³/h] /h) rate (m /h) Air flow rate 3 Legend L1 = Low speed lower limit L8 = Low speed factory setting L15 = Low speed upper limit H1 = High speed lower limit H8 = High speed factory setting 3 H15 = High speed upper limit UH1 = Ultra-high speed lower limit UH8 = Ultra-high speed factory setting UH15 = Ultra-high speed upper limit 3D112837 VIEW ALL VAM-FC9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VIEW ALL VAM-J TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VAM1000J 300 H8 150 UH8 H15 120m UH1 90m 350 300 250 External static pressure [Pa] External static pressure [Pa] 250 200 Ultra-high speed 150m UH15 L15 H1 100 L8 50 L1 0 400 30m 600 700 800 900 1000 150 UH15 100 UH8 50 Ø250 Duct lenght 500 200 UH1 0 600 1100 700 800 900 1000 Air flow rate [m3/h] Air flow rate [m3/h] High speed 250 200 150 100 H15 50 0 500 600 H1 800 700 High speed 250 External static pressure [Pa] External static pressure [Pa] 300 200 150 100 50 0 H8 1000 900 1100 L15 L1 400 500 600 L8 800 700 900 Air flow rate [m3/h] Air flow rate [m3/h] Notes Legend L1 = Low speed lower limit LB = Low speed factory setting L15 = Low speed upper limit H1 = High speed lower limit H8 = High speed factory setting H15 = High speed upper limit UH1 = Ultra-high speed lower limit UH8 = Ultra-high speed factory setting UH15 = Ultra-high speed upper limit 1.The fan curves are determined with ·1/3· of the ESP on the outdoor side (·EA & OA·), and ·2/3· of the ESP on the indoor side (·RA & SA). Ultra-high speed High speed Low speed EA= Exhaust air OA = Outdoor air RA= Room air SA= Supply air 2. Measured according to ·JIS B 8628 - 2003· D112832 3D112832 VAM1500J VAM1500J UH15 250 180m UH8 150 H8 UH1 100 150m L15 120m 90m H1 L8 60m 50 30m 2xØ250 Duct length L1 0 700 900 1100 1300 1500 1700 300 250 200 UH15 150 100 250 200 150 H15 50 H8 H1 0 900 1100 1300 Air flow rate [m³/h] 1500 1700 External static pressure [Pa] External static pressure [Pa] 700 900 1100 1300 1500 1700 Air flow rate [m³/h] Low speed 250 100 UH1 0 High speed 300 UH8 50 Air flow rate [m³/h] 700 Ultra-high speed 350 H15 200 External static pressure [Pa] External static pressure [Pa] 300 200 150 100 L15 50 0 700 L1 900 1100 1300 L8 1500 Air flow rate [m³/h] Notes 1. The fan curves are determined with ·1/3· of the ESP on the outdoor side (·EA & OA·),and ·2/3· of the ESP on the indoor side (·RA & SA·). EA = Exhaust air OA = Outdoor air RA = Room air SA = Supply air 2 .Measured according to ·JIS B 8628 - 2003· Ultra-high speed High speed Low speed Legend L1 = Low speed lower limit L8 = Low speed factory setting L15 = Low speed upper limit H1 = High speed lower limit H8 = High speed factory setting H15 = High speed upper limit UH1 = Ultra-high speed lower limit UH8 = Ultra-high speed factory setting UH15 = Ultra-high speed upper limit 3D112838 3D112838 307 VIEW ALL VAM-J TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VIEW ALL VAM-FC9 TECHNICAL DRAWINGS ON MY.DAIKIN.EU VAM2000J 300 150m UH15 120m 120m 90m UH1 UH8 UH8 H15 H8 H15 200 200 150 UH1 L15 UH1 H1 H8 H8 150 150 100 90m 90m 60m L15 L8 L15 H1 H1 60m 60m 30m 100 100 50 L8 L1 L8 50 50 0L1 L1 800 800 800 2xØ250 30m 30mlength Duct 1000 1000 1000 300 1200 1400 1600 Air flow rate [m³/h] 1200 1200 1400 1400 1600 1600 Air rate High speed Air flow flow rate [m³/h] [m³/h] 1800 1800 1800 2xØ250 2xØ250 2200 2000 Duct Duct length length 2000 2000 150 200 200 100 150 150 H15 50 100 100 0 Notes 0 1000 1000 H15 H15 H8 H1 1200 1400 1600 1800 H8 H8 Air flow rate H1 [m³/h] H1 1200 1200 1400 1400 1600 1600 2000 1800 1800 2000 2000 Ultra-high speed 300 350 350 250 300 300 200 250 250 150 200 200 UH15 100 150 150 UH15 UH15 UH8 50 100 100 0 501200 50 UH1 1400 1600 1800 2000 UH8 2200 UH8 UH1 Air flow rate [m³/h]UH1 1400 1400 1600 1600 Low speed 250 200 250 250 Ultra-high speed 350 0 0 1200 1200 2200 2200 High speed 250 300 300 0 50 501000 External External External static static pressure pressure static pressure [Pa] [Pa] [Pa] 250 250 200 0 0 External External External static static pressure pressure static pressure [Pa] [Pa] [Pa] 150m 150m 120m UH15 UH8 UH15 H15 External External External static static pressure pressure static pressure [Pa] [Pa] [Pa] External External External static static pressure pressure static pressure [Pa] [Pa] [Pa] 300 300 250 1800 1800 2000 2000 2200 2200 Air flow rate [m³/h] Low speed 250 200 250 200 150 200 150 100 150 100 50 100 L15 50 0 50 0 0 L1 800 1000 1400 Air flow rate [m³/h] L1 L1 800 800 1200 1000 1000 1. The fan curves are determined with ·1/3· of the ESP on the outdoor side (·EA & OA·), and ·2/3· of the ESP on the indoor side (·RA & SA·). EA = Exhaust air Air flow rate [m³/h] Notes OA = Outdoor air RAfan = curves Room air 1. are the ESP and ·2/3· the ESP 1. The The fan curves are determined determined with with ·1/3· ·1/3· of of the ESP on on the the outdoor outdoor side side (·EA (·EA & & OA·), OA·), and ·2/3· of of the ESP on on the the indoor indoor side side (·RA (·RA & & SA·). SA·). SA = EA Exhaust air EA = Supply Exhaustair air OA air OA = = Outdoor Outdoor airto ·JIS B 8628 - 2003· 2 Measured according RA RA = = Room Room air air SA SA = = Supply Supply air air Measured according accordingto to ·JIS ·JIS B B 8628 8628 -- 2003· 2003· 22 Measured 1200 1200 1600 L8 L8 1600 1600 Legend 1400 1400 Air flow rate [m³/h] L1 Ultra-high speed High speed Low speed Ultra-high speed High speed Low speed L8 = = = = = = = = = = = = = = = = = = Legend L8 L15 L1 H1 L8 H8 L15 H15 H1 UH1 H8 UH8 H15 UH15 UH1 UH8 UH15 1800 L15 L15 1800 1800 Low speed lower limit Low speed factory setting Low speed upper limit Low speed lower limit High speed lower limit Low speed factory setting High speed factory setting Low speed upper limit High speed upper limit High speed lower limit Ultra-high speed lower limit High speed factory setting Ultra-high speed factory setting High speed upper limit Ultra-high speed upper limit Ultra-high speed lower limit Ultra-high speed factory setting Ultra-high speed upper limit 3D112839 308 VIEW ALL VKM-GB TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VKM50GB VKM50GB Air discharge grille (locally procured) Air suction grille (locally procured) Heat insulator (locally procured) EA (Exhaust air to outdoors) Branch duct (locally procured) Control box Maintenance space for the heat exchanger elements the air filters and fans Inspection hatch Inspection hatch More than 600 Round shape hood (locally procured) OA (Fresh air to outdoors) Flexible duct (locally procured) Heat insulated (locally procured) Air discharge grille (locally procured) 360 (in case of □ 450 inspection hatch) 140 (in case of □ 600 inspection hatch) Refrigerant piping (Gas pipe) (Ø 12.7 flare connection) A gradient of more than 1/30 Refrigerant piping (Liquid pipe) (Ø 6.4 flare connection) Ø 200 Nominal diameter (locally procured) OA (Fresh air to outdoors) EA (Exhaust air to outdoors) Sloping downwards at a gradient of the 1/100 Inspection hatch (locally procured) Suspention bolt (locally procured) RA (Return air from room) SA (Return air from room) NOTES 1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters heat exchange elements, and fans can easily be inspected and serviced.) 2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to prevent dew condensation.(Material: glass wool of 25mm thick) 3. Do not turn the unit upside down. 4. Make sure to install drain piping, and insulate drain piping to prevent dew condensation. 5. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming. 6. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory). 7. In areas where freezing may occur, always take steps to preventthe pipes from freezing. 8. Do not place something which shouldn’t get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air filter is very dirty. 3D083014 309 VIEW ALL VKM-GBM TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VKM50GBM VKM50GBM Air discharge grille (locally procured) Air suction grille (locally procured) Heat insulator (locally procured) EA (Exhaust air to outdoors) Round shape hood (locally procured) OA (Fresh air to outdoors) Control box Maintenance space for the heat exchanger elements the air filters, fans and humidifier Inspection hatch Inspection hatch More than 600 Branch duct (locally procured) Flexible duct (locally procured) Heat insulated (locally procured) Air discharge grille (locally procured) 360 (in case of □ 450 inspection hatch) 140 (in case of □ 600 inspection hatch) Cistern tank Water supply shut-off valve (locally procured) A gradient of more than 1/30 Ø 200 Nominal diameter (locally procured) Drain valve (locally procured) Strainer (locally procured) Refrigerant piping (Gas pipe) (Ø 12.7 flare connection) Refrigerant piping (Liquid pipe) (Ø 6.4 flare connection) OA (Fresh air to outdoors) EA (Exhaust air to outdoors) Sloping downwards at a gradient of the 1/100 □ 450 - 600 Inspection hatch (locally procured) Suspention bolt (locally procured) RA (Return air from room) SA (Return air from room) NOTES 1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters heat exchange elements, and fans can easily be inspected and serviced.) 2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to prevent dew condensation. (Material: glass wool of 25mm thick) 3. Do not turn the unit upside down. 4. Use city water or clean water. Include water supply piping with strainer, a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the inspection. 5. It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type), if you need to get your water supply from public piping. 6. Make sure the supply water 0.02MPa to 0.49MPa (0.2 kg/cm2 to 5 kg/cm2 ) 7. Make sure the supply water is between 5°C and 40°C in temperature. 8. Insulate the water supply piping to prevent condensation from forming. 9. Make sure to install drain piping, and insulate drain piping to prevent dew condensation. 10. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming. 11. Install in a location where the air around the unit or taken into the umidifier will not drop below 0°C. 12. Do not use a bent cap or a round hoodas the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory). 13. In areas where freezing may occur, always take steps to prevent the pipes from freezing. 14. Do not place something which shouldn’t get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air filter is very dirty. 15. Feed clean water. If the supply water is hard water, use a water softener because of short life. Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of hardness: 150 mg/L. (Life of humidifying element is about 1 years (1500 hours), under the supply water conditions of hardness: 400 mg/L.) 3D083011 310 VIEW ALL VKM-GB TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VKM80GB VKM80GB Air suction grille (locally procured) Heat insulator (locally procured) Air discharge grille (locally procured) EA (Exhaust air to outdoors) Branch duct (locally procured) Heat insulated (locally procured) Round shape hood (locally procured) OA (Fresh air to outdoors) Control box Maintenance space for the heat exchanger elements the air filters and fans Inspection hatch Inspection hatch More than 600 Silencer (locally procured) Flexible duct (locally procured) Air discharge grille (locally procured) 360 (in case of □ 450 inspection hatch) 140 (in case of □ 600 inspection hatch) Ø 250 Nominal diameter A gradient of more than 1/30 Refrigerant piping (Gas pipe) (Ø 12.7 flare connection) Refrigerant piping (Liquid pipe) (Ø 6.4 flare connection) (locally procured) OA (Fresh air to outdoors) EA (Exhaust air to outdoors) Sloping downwards at a gradient of the 1/100 □ 450 - 600 Inspection hatch (locally procured) Suspention bolt (locally procured) RA (Return air from room) SA (Return air from room) NOTES 1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters heat exchange elements, and fans can easily be inspected and serviced.) 2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to prevent dew condensation. (Material: glass wool of 25mm thick) 3. Do not turn the unit upside down. 4. Make sure to install drain piping, and insulate drain piping to prevent dew condensation. 5. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming. 6. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory). 7. In areas where freezing may occur, always take steps to prevent the pipes from freezing. 8. Do not place something which shouldn’t get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air filter is very dirty. 3D083015 311 VIEW ALL VKM-GBM TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VKM80GBM VKM80GBM Air suction grille (locally procured) Heat insulator (locally procured) Air discharge grille (locally procured) EA (Exhaust air to outdoors) Branch duct (locally procured) Heat insulated (locally procured) Round shape hood (locally procured) Control box Maintenance space for the heat exchanger elements the air filters, fans and humidifier Inspection hatch Inspection hatch More than 600 OA (Fresh air to outdoors) Silencer (locally procured) Flexible duct (locally procured) Air discharge grille (locally procured) 360 (in case of □ 450 inspection hatch) 140 (in case of □ 600 inspection hatch) Cistern tank Water supply shut-off valve (locally procured) A gradient of more than 1/30 Ø 250 Drain valve (locally procured) Strainer (locally procured) Refrigerant piping (Gas pipe) (Ø 12.7 flare connection) Refrigerant piping (Liquid pipe) (Ø 6.4 flare connection) Nominal diameter (locally procured) OA (Fresh air to outdoors) EA (Exhaust air to outdoors) Sloping downwards at a gradient of the 1/100 □ 450 - 600 Inspection hatch (locally procured) Suspention bolt (locally procured) RA (Return air from room) SA (Return air from room) NOTES 1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters heat exchange elements, and fans can easilybe inspected and serviced.) 2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to prevent dew condensation. (Material: glass wool of 25mm thick) 3. Do not turn the unit upside down. 4. Use city water or clean water. Include water supply piping with strainer, a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the inspection 5. It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type), if you need to get your water supply from public piping. 6. Make sure the supply water 0.02MPa to 0.49MPa (0.2 kg/cm2 to 5 kg/cm2 ) 7. Make sure the supply water is between 5°C and 40°C in temperature. 8. Insulate the water supply piping to prevent condensation from forming. 9. Make sure to install drain piping, and insulate drain piping to prevent dew condensation. 10. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming. 11. Install in a location where the air around the unit or taken into the umidifier will not drop below 0°C. 12. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory). 13. In areas where freezing may occur, always take steps to prevent the pipes from freezing. 14. Do not place something which shouldn’t get wet at the below of this unit. The dew would fall at following case,where humidity is 80% more, or the exit of drain socket is choked up, or the air filter is very dirty. 15. Feed clean water. If the supply water is hard water, use a water softener because of short life. Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of hardness: 150 mg/L. (Life of humidifying element is about 1 years (1500 hours), under the supply water conditions of hardness: 400 mg/L.) 3D083012 312 VIEW ALL VKM-GB TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VKM100GB VKM100GB Air suction grille (locally procured) Heat insulator (locally procured) Air discharge grille (locally procured) EA (Exhaust air to outdoors) Branch duct (locally procured) Heat insulated (locally procured) Round shape hood (locally procured) Control box Maintenance space for the heat exchanger elements the air filters and fans Inspection hatch Inspection hatch More than 600 OA (Fresh air to outdoors) Silencer (locally procured) Flexible duct (locally procured) Air discharge grille (locally procured) 360 (in case of □ 450 inspection hatch) 140 (in case of □ 600 inspection hatch) A gradient of more than 1/30 Ø 250 Nominal diameter (locally procured) Refrigerant piping (Gas pipe) (Ø 12.7 flare connection) Refrigerant piping (Liquid pipe) (Ø 6.4 flare connection) OA (Fresh air to outdoors) EA (Exhaust air to outdoors) Sloping downwards at a gradient of the 1/100 □ 450 - 600 Inspection hatch (locally procured) Suspention bolt (locally procured) RA (Return air from room) SA (Return air from room) NOTES 1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters heat exchange elements, and fans can easily be inspected and serviced.) 2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to prevent dew condensation. (Material: glass wool of 25mm thick) 3. Do not turn the unit upside down. 4. Make sure to install drain piping, and insulate drain piping to prevent dew condensation. 5. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming. 6. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory). 7. In areas where freezing may occur, always take steps to preventthe pipes from freezing. 8. Do not place something which shouldn’t get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air filter is very dirty. 3D083016 313 VIEW ALL VKM-GBM TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VKM100GBM VKM100GBM Air suction grille (locally procured) Heat insulator (locally procured) Air discharge grille (locally procured) EA (Exhaust air to outdoors) Branch duct (locally procured) Round shape hood (Locally procured) Control box Inspection hatch Maintenance space for the heat exchanger fans and elements the air Inspection hatch More than 600 OA (Fresh air from outdoors) Heat insulator (locally procured) Silencer (locally procured) Flexible duct (locally procured) Air discharge grille (locally procured) 360 (in case of □ 450 inspection hatch) 140 (in case of □ 600 inspection hatch) Cistern tank Water supply shut-off valve (locally procured) A gradient of more than 1/30 Ø 250 Nominal diameter Drain valve (locally procured) Strainer (accessory) Refrigerant piping (Gas pipe) (Ø 12.7 connection) Refrigerant piping (Liquid pipe) connection) (Ø 6.4 (locally procured) OA (Fresh air from outdoors) EA (Exhaust air to outdoors) Sloping downwards at a gradient of the 1/100 □ 450 • 600 Inspection hatch (locally procured) Suspension bolt (locally procured) RA (Return air from room) SA (Return air to room) NOTES 1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters, heat exchange elements, fans and humidifier elements can easily be inspected and serviced.) 2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water. Also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to prevent dew condensation. (Material: glass wool of 25mm thick) 3. Do not turn the unit upside down. 4. Use city water or clean water. Include water supply piping with strainer, a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the inspection. 5. It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type), if you need to get your water supply from public piping. 6. Make sure the supply water 0.02MPa to 0.49MPa (0.2 kg/cm2 to 5 kg/cm2 ) 7. Make sure the supply water is between 5°C and 40°C in temperature. 8. Insulate the water supply piping to prevent condensation from forming. 9. Make sure to install drain piping, and insulate drain piping to prevent dew condensation. 10. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming. 11. Install in a location where the air around the unit or taken into the humidifier will not drop below 0°C. 12. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory). 13. In areas where freezing may occur, always take steps to prevent the pipes from freezing. 14. Do not place something which shouldn’t get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air filter is very dirty. 15. Feed clean water. If the supply water is hard water, use a water softener because of short life. Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of hardness: 150 mg/L. (Life of humidifying element is about 1 years (1500 hours), under the supply water conditions of hardness: 400 mg/L.) 3D083013 314 VIEW ALL VKM-GB TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VKM50GB VKM50GB Exchange efficiency (%) Operating air flow rate range –––––– 50Hz, 220V-240V Temp eratu Enth alpy Enth chan exch ange exch ge eff icienc efficie ange Operating air flow rate range y ncy ( Operating air flow rate range Operating air flow rate range heati effic ng) ienc y (co oling ) ø200 Pipe length Ultra High External static pressure (Pa) External static pressure (Pa) alpy re ex High Low Air flow rate[m³/h] Air flow rate[m³/h] Low Air flow rate[m³/h] High Air flow rate[m³/h] Ultra High [Reading of Performance Characteristics] 2) Rated point: ● 3) The characteristic of each tap becomes a setup of the characteristic of the same code number. 1) For example: 19(29)- -07 Mode no. : 19(29) First code: (Supply ┌ 2 Exhaust ┌ 3 ) ┘ ┘ Second code no. : 07 3D082904 VKM50GBM VKM50GBM Exchange efficiency (%) Operating air flow rate range –––––– 50Hz, 220V-240V VKM50GBM Temp erature Enth alpy Enth ange exch nge e fficien effic ange ienc cy y (he efficie ating ncy ( cooli ) ng) Operating air flow rate range Operating air flow rate range Operating air flow rate range ø200 Pipe length External static pressure (Pa) External static pressure (Pa) alpy exch excha Ultra High High Low Air flow rate[m³/h] Air flow rate[m³/h] Low Air flow rate[m³/h] High Air flow rate[m³/h] Ultra High [Reading of Performance Characteristics] 1) For example: 19(29)- -07 Mode no. : 19(29) First code: (Supply ┌ 2 Exhaust ┌ 3 ) ┘ ┘ Second code no. : 07 2) Rated point: ● 3) The characteristic of each tap becomes a setup of the characteristic of the same code number. 3D082901 315 VIEW ALL VKM-GBM TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VKM80GB VKM80GB Exchange –––––– 50Hz, 220V-240V efficiency Operating air flow rate range (%) pera ture Enth alpy Enth External static pressure (Pa) alpy exch ange exch ange Air flow rate[m³/h] High Air flow rate[m³/h] Ultra High ncy ienc ange Operating air flow rate range efficie effic exch Operating air flow rate range y (he effic ating ienc ) y (co oling ) Ultra High ø250 Pipe length High External static pressure (Pa) Tem Operating air flow rate range Low Air flow rate[m³/h] Air flow rate[m³/h] Low [Reading of Performance Characteristics] 1) For example: 19(29)- -07 Mode no. : 19(29) First code: (Supply ┌ 2 Exhaust ┌ 3 ) ┘ ┘ Second code no. : 07 2) Rated point: ● 3) The characteristic of each tap becomes a setup of the characteristic of the same code number. 3D082905 VKM80GBM VKM80GBM –––––– 50Hz, 220V-240V Exchange efficiency (%) Operating air flow rate range Operating air flow rate range Operating air flow rate range Operating air flow rate range VKM80GBM rature e Enth alpy External static pressure (Pa) Enth xchang exch alpy e efficie ang ncy exch e ef ange ficie effic ncy (hea ting) ienc y (co oling ) Ultra High ø250 Pipe length External static pressure (Pa) Tempe High Low Air flow rate[m³/h] Air flow rate[m³/h] Low Air flow rate[m³/h] High Air flow rate[m³/h] Ultra High [Reading of Performance Characteristics] 1) For example: 19(29)- -07 Mode no. : 19(29) First code: (Supply ┌ 2 Exhaust ┌ 3 ) ┘ ┘ Second code no. : 07 316 2) Rated point: ● 3) The characteristic of each tap becomes a setup of the characteristic of the same code number. 3D082902 VIEW ALL VKM-GB TECHNICAL DRAWINGS ON MY.DAIKIN.EU Detailed technical drawings VKM100GB VKM100GB –––––– 50Hz, 220V-240V Exchange efficiency Operating air flow rate range (%) Operating air flow rate range pera External static pressure (Pa) halp ture y ex Ent cha hal py nge exc han ge exc han ge e effic fficie ienc ncy y (h effi Operating air flow rate range eatin cien g) cy ( coo ø250 Pipe length ling ) Ultra High High External static pressure (Pa) Tem Ent Operating air flow rate range Low Air flow rate[m³/h] Low Air flow rate[m³/h] Air flow rate[m³/h] High Air flow rate[m³/h] Ultra High [Reading of Performance Characteristics] 1) For example: 19(29)- -07 Mode no. : 19(29) First code: (Supply ┌ 2 Exhaust ┌ 3 ) ┘ ┘ Second code no. : 07 2) Rated point: ● 3) The characteristic of each tap becomes a setup of the characteristic of the same code number. 3D082906 VKM100GBM VKM100GBM Exchange efficiency (%) –––––– 50Hz, 220V-240V Operating air flow rate range En External static pressure (Pa) tha En tha lpy lpy ture exc han exc Operating air flow rate range VKM100GBM pera exc han han ge ge ge e effi effi cie ncy Operating air flow rate range fficie ncy cie Operating air flow rate range ncy (he atin (co olin g) Ultra High High g) ø200 Pipe length External static pressure (Pa) Tem Low Air flow rate[m³/h] Air flow rate[m³/h] Low Air flow rate[m³/h] High Air flow rate[m³/h] Ultra High [Reading of Performance Characteristics] 1) For example: 19(29)- -07 Mode no. : 19(29) First code: (Supply ┌ 2 Exhaust ┌ 3 ) ┘ ┘ Second code no. : 07 2) Rated point: ● 3) The characteristic of each tap becomes a setup of the characteristic of the same code number. 3D082903 317 Creating a sustainable future together Determined to reduce our environmental footprint, we aim to be CO₂-neutral by 2050. A circular economy, innovation and smart use – these are the stepping stones on our path. The time to act is now. Join us in creating a sustainable future for HVAC-R. Sowing the seeds of climate protection with Daikin Through a circular economy Through innovation Through smart use › Embrace Certified Reclaimed Refrigerant Allocation to reuse more refrigerant › Increase recovered refrigerant returns › Reuse refrigerant for maintenance with our refrigerant recycling machine › Equip our VRV 5 range with the lower GWP refrigerant R-32 › Offer high real-world seasonal efficiencies › Deploy unique auto cleaning filters to maximise efficiency 24/7 › Rigorously follow up on energy consumption via the Daikin Cloud Service › Factor in experts’ advice to continuously optimise system efficiency › Enable predictive maintenance to ensure optimum operation and uptime › Prevent energy waste with smart key cards and sensors www.daikin.eu/building-a-circular-economy Daikin Europe N.V. Naamloze Vennootschap Zandvoordestraat 300 · 8400 Oostende · Belgium · www.daikin.eu · BE 0412 120 336 · RPR Oostende (Publisher) Daikin Europe N.V. participates in the Eurovent Certified Performance programme for Liquid Chilling Packages and Hydronic Heat Pumps, Fan Coil Units and Variable Refrigerant Flow systems. Check ongoing validity of certificate: www.eurovent-certification.com ECPEN20- 200 05/20 The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V. Printed on non-chlorinated paper.