Uploaded by salahaljunaid

Emerson NetSure 801

advertisement
Complete Network Power Products
for Business-Critical Continuity™
2008 2009 Catalog
~
6
2
8
3
5
11
2
7
7
1
9
4
9
4
5
6
2
8
3
5
11
2
7
7
1
9
4
9
4
5
Grid-to-chip protection for your critical investments
investments
No other organization can match the
scope of Emerson Network Power’s
product offerings and service
reach, nor provide such complete
grid-to-chip protection to ensure
Business-Critical
Business-Cri
tical Continuity
™
for your technology
investment.
Services
Emerson Network Power supports
these Centers of Expertise with the
largest global services organiza
organization
tion in the
industry, delivering:
1
2
2
–
Design, installation and startup
–
Warranty
Warra
nty service
–
Preventive maintenance
–
24x7 remote monitoring
monitoring
–
Emergency service
–
Site audits
1
11
6
10
0
6
11
9
8
5
3
6
Contents
A Full Spectrum of Products of Emerson
Network Power
DC POWER
1
OUTSIDE PLANT
16
AC POWER
23
RACKS & INTEGRATED CABINETS
41
PRECISION COOLING
43
MONITORING
48
EMBEDDED POWER
54
EMERSON NETWORK POWER.
THE GLOBAL LEADER IN ENABLING
BUSINESS-CRITICAL CONTINUITY.™
AC POWER
CONNECTIVITY
DC POWER
EMBEDDED COMPUTING
EMBEDDED POWER
DC POWER
MONITORING
OUTSIDE PLANT
POWER SWITCHING
& CONTROLS
PRECISION COOLING
RACKS & INTEGRATED
CABINETS
SERVICES
SURGE PROTECTION
Supporting voice and communications networks with
dependable DC power solutions. We ’ve built on trusted
names-lorain®,Actura and PS-to create NetSure™
DCPower Solutions ,the next-generation global technology
platform that delivers the most rigorous network-power
applications,with an unparalleled breadth DC power ,
distribution,control and monitoring systems.
DC Power.
Yet another way Emerson Network Power
enables Business-Critical Continuity™.
1
DC Power System
DC Power System
Confi guration Matrix
Large system
2
Medium System
Medium System
Small System
NetSure 801
P S486 00-3/2 900 -X5
PS48 250 -1 A/290 0
PS4 825 0-1B/2 900
Max. Power
348kW
34.8kW
14.5kW
14.5kW
14.5kW
9.6kW
Voltage
-48V
-48V
-48V
-48V
-48V
-48V
Max. Current
6000A
600A
250A
250A
250A
165A
Max. Number of Rectifiers
60
12
5
5
5
3
Rectifier Type
R48-5800
R48-2900
R48-2900
R48-2900
R48-2900
R48-3200,R48-2900
Controller Type
M810G
M500F
M501D
M501D
M501D
M501D
Dimension
Multi-cabinet system
600×600×2000
600×600×2000
600×400×2000
600×400×700
600×600×1600
or 584×327×132
Medium System
Medium System
Small System
Small System
Medium System
PS4875/25
P S482 50-1C/29 00
PS24600/75
PS48 165 /320 0
PS48360/1800
PS48300/1800-X6
PS48120/1800-X6
Max. Power
20.88kW
17.4kW
6.96kW
4.35kW
17.4kW
7.2kW
PSC48150/25
Voltage
-48V
-48V
-48V
-48V
+24V
-48V
Max. Current
360A
300A
120A
75A
600A
150A
Max. Number of Rectifiers
12
10
4
3
8
6
Rectifier Type
R48-1800
R48-1800
R48-1800
HD4825-3
HD2475-2
C24/48-1200
Controller Type
M501D
M501D
M501D
PSM-A10
PSM-A11
Dimension
600×600×2000
600×600×1600
600×600×2000
450×260×700
600×600×2000
200×400×1460
Business-Critical Continuity™
NetSure 801
Stand-alone DC Power Series
-48VDC
up to 348kW
R48-5800
Applications





Large and medium switching offi ce
Level-1 transmission backbone line
GSM mobile switching office, mobile tandem e xchange
CDMA mobile switching office, mobile tandem e xchange
DC Internet data center
M810G
System features
















Space saving, 116kW(2000A@58V) capacity one cabinet
Capacity expandable up to 348kW(6000A@58V)
Three-phase rectifi ers (R48-5800) and SCU+(M810G) inside
Wide AC input range, 260V to 530Vac, up to 600Vac endurance without damage
System Effi ciency high up to 93%
Power factor high up to 0.99
Output current Walk-in available
Rectifiers and controller hot swappable
Front access
Top or bottom cabling
Surge protection on AC, DC and signal side
Modularized design for system and function unit
TCP/IP, SNMP, web browser support
Rectifier CE/UL approved
Compliance with EN60590 and EN300386, ROHS
Patented energy-saving mode
3
DC Power System
Affi liated Cabinet
AC distribution cabinet
Features







Local large LCD display
Dual mains auto/manual switchover
Front access, Top / bottom cabling
DC emergency lighting available
Expandable up to f ive AC cabinets
Lightning proof and electric Compliance with IEC
ROHS Compatible
AC distribution cabinet
DC distribution cabinet
Features







DC distribution cabinet
4
Independent monitoring unit for decentralized supply
Local large LCD display
Front access, Top / bottom cabling
DC emergency lighting available
Expandable up to 8 DC cabinets
Lightning proof and electric Compliance with IEC
ROHS Compatible
Business-Critical
Busines
s-Critical Continuity™
PD48/2000HF
High Ohmic Power Distribution Cabinet
Features





Up to 120 branches high/low ohmic output
Local large LCD display
Front access
Lightning proof and electric Compliance with IEC
ROHS Compatible
PD48/2000HF
PD48/1200BFH
Integrated AC/DC Distribution Cabinet
Features







AC.DC distribution unit in one cabinet
Space saving
Local large LCD display
Dual mains auto/manual switchover
Front access
Lightning proof and electric Compliance with IEC
ROHS Compatible
Dimensions And Weight
Cabinet
Rectifier Rack
AC Cabinet
DC Cabinet
DC High Ohmic
Distribution Cabinet
Integrated AC/DC
Distribution Cabinet
Rectifier
Controller
Cabinet / module
Rack10
Rack
1000
00-6
-6 Ca
Cabi
bine
nett
Rack
Ra
ck20
2000
00-6
-6 Ca
Cabi
bine
nett
PD38
PD
380/
0/40
400A
0AFH
FH-6
-6/X
/X1
1
PD380/
PD3
80/630A
630AFHFH-6/X
6/X1
1
PD380/630AFA
PD48
PD
48/1
/160
600D
0DFF-6/
6/X1
X1
PD48
PD
48/2
/250
500D
0DFF-6/
6/X1
X1
capacity
1000
10
00A
A
2000
20
00A
A
400A
40
0A
630A
630A
1600
16
00A
A
2500
25
00A
A
W×D×H, mm
600×600×2000
600
600
60
0×600×2000
800
80
0×600×2000
800×600×2000
800×600×2000
800
80
0×600×2000
800
80
0×600×2000
Weigh t ( kg
kg)
140(exclude recti
140(exclude
rectifier)
fier)
180(exclude
180(exc
lude recti
rectifier)
fier)
240
240
Manual switchover
250
Automatic switchover
280
290
PD48/2000HF
2000A
800×600×2000
320
P D4
D48 /1
/120 0B
0BF H
1 20
200 A
800×600×2000
320
R48-5800
M810G
5800W
/
244×372×88
243.5×161×88
7.8
2
PD48/1200BFH

DC Power System
PS48600-3/2900-X5
Integrative DC Power Series
-48VDC
up to 34.8kW
Applications

PS48600-3/2900-X5



2G, 3G mobile base stations
Medium exchanges, rural telecom networks and access networks
Transmission relay stations
Microwave/satellite communications stations
Features






R48-2900








M500F
Capacity up to 34.8kW (600A @ 58V)
Rectifiers R48-2900(2900W)and SCU inside
Wide input voltage range (85 to 290Vac), up to 415Vac endurance without damage
Effi ciency high
h igh up to 93%
93 %
Power factor high up to 0.99
Output current Walk-in available
Patented energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Rectifiers and controller hot swappable
Front access
Top or bottom cabling
Rectifi
Recti
fier CE/UL approval
appro val
Compliance with RoHS
Dimensions And Weight
Cabinet
Rectifier
Controller
6
model
PS48600-3/2900-X5
R48-2900
M500F
W×D×H, mm
600×600×20
2000
00
85.5×287×132.5
Weight (kg)
140(
14
0(re
rect
ctifi
ifier ex
excl
clud
uded
ed))
3.5
Business-Critical Continuity™
PS48250-1A/2900
PS48250-1B/2900
PS48250-1C/2900
(ACTURA Flex 48330)
Integrative DC Power Series
-48VDC
up to 14.5kW
Applications




2G, 3G mobile base stations
Medium exchanges, rural telecom networks and access networks
Transmission relay stations
Microwave/satellite communications stations
PS48250-1A/2900
Features
















Capacity up to 14.5kW (250A @ 58V)
Rectifiers R48-2900(2900W)and SCU inside
Super fl exible confi guration
Wide input voltage range (85 to 290Vac), up to 415Vac endurance without damage
Effi ciency high up to 93%
Power factor high up to 0.99
Output current Walk-in available
Patented energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Rectifiers and controller hot swappable
Front access
Top cabling
Inner 660Ah battery shelves optional
Rectifier CE/UL approval
Compliance with RoHS
Dimensions And Weight
Cabinet
Rectifier
Controller
model
PS48250-1A/2900
PS48250-1B/2900
PS48250-1C/2900
R48-2900
M500F
PS48250-1B/2900
PS48250-1C/2900
W×D×H, mm
600×600×2 00 0
600×400×2 00 0
600×400×7 00
85.5×287×132.5
Weight (kg)
1 35 (r ec ti fier ex cl ud ed)
1 25 (r ec ti fier ex cl ud ed)
6 0 ( rec ti fier ex cl ud ed)
3.5
7
DC Power System
PS48165/3200
(ACTURA OPTIMA 48200)
Integrative DC Power Series
-48VDC
up to 9.6kW
Applications




2G, 3G mobile base stations
Medium exchanges, rural telecom networks and access networks
Transmission relay stations
Microwave/satellite communications stations
PS48165/3200 mode1
Features










PS48165/3200 mode2




PS48165/3200 mode3
Capacity up to 9.6kW (165A @ 58V)
Rectifiers R48-3200(3200W)and SCU inside
Wide input voltage range (85 to 290Vac), up to 415Vac endurance without damage
Effi ciency high up to 93%
Power factor high up to 0.99
Output current Walk-in available
Patented energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Rectifiers and controller hot swappable
Top cabling
Inner dual battery shelves optional
Rectifier CE/UL approval
Compliance with RoHS
Dimensions And Weight
Cabinet
S ub rac k
8
model
PS48165/3200 mode 1
PS48165/3200 mode 2
P S4 81 65 /3 20 0 m od e 3
W×D×H, mm
600×600×1600
600×400×1600
5 84×327×132
Weight (kg)
75(rectifier excluded)
65(rectifier excluded)
20(rectifier excluded)
Distribution U nit Location
Top
rear
Business-Critical Continuity™
PS48360/1800
(ACTURA Flex 48420)
Integrative DC Power Series
-48VDC
up to 20.8kW
Applications




2G, 3G mobile base stations
Medium exchanges, rural telecom networks and access networks
Transmission relay stations
Microwave/satellite communications stations
R48-1800
Features















Capacity up to 20.8kW (360A @ 58V)
Rectifiers R48-1800(1740W)and SCU inside
Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
Efficiency high up to 92%
Power factor high up to 0.99
Output current Walk-in available
Patented energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Rectifiers and controller hot swappable
Front access
Top cabling
Inner 660Ah battery shelves optional
Rectifier CE/UL approval
Compliance with RoHS
Dimensions And Weight
Cabinet
model
PS48360/1800-X1
PS48360/1800-X2
PS48360/1800-X3
W×D×H, mm
600×600×2 00 0
600×400×2 00 0
600×600×1 80 0
Weight (kg)
1 35 (r ec tifi er e xc lu ded )
1 25 (r ec tifi er e xc lu ded )
1 00 (r ec tifi er e xc lu ded )
M501D
PS48360/1800

DC Power System
PS48300/1800-X6
Integrative DC Power Series
-48VDC
up to 14.7kW
Applications




PS48300/1800-X6
Features











M501D
2G, 3G mobile base stations
Medium exchanges, rural telecom networks and access networks
Transmission relay stations
Microwave/satellite communications stations



Capacity up to 14.7kW (300A @ 58V)
Rectifiers R48-1800(1740W)and SCU inside
Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
Effi ciency high up to 92%
Power factor high up to 0.99
Output current Walk-in available
Patented energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Rectifiers and controller hot swappable
Front access
Top/Bottom cabling
Rectifier CE/UL approval
Compliance with RoHS
Dimensions And Weight
Cabinet
R48-1800
10
model
PS48300/1800-X6
W×D×H, mm
600×600×1600
Weight (kg)
130(rectifier excluded)
Business-Critical Continuity™
PS48120/1800-X6
Integrative DC Power Series
-48VDC
up to 6.96kW
Applications





2G, 3G mobile base stations
small exchanges, rural telecom networks and access networks
Transmission relay stations
Microwave/satellite communications stations
Railway stations
Features















PS48120/1800-X6
Capacity up to 6.96kW (120A @ 58V)
Rectifiers R48-1800(1740W)and SCU inside
Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
Effi ciency high up to 92%
Power factor high up to 0.99
Output current Walk-in available
Patented energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Rectifiers and controller hot swappable
Front access
Top/Bottom cabling
Inner 330Ah battery shelves optional
Rectifier CE/UL approval
Compliance with RoHS
M501D
Dimensions And Weight
Cabinet
model
PS48120/1800-X6
W×D×H, mm
600×600×2 00 0
Weight (kg)
1 10 (r ec tifier e xc lu ded )
R48-1800
11
DC Power System
PS4875/25
Wall-mounted Integrative DC Power Series
-48VDC
up to 4.35kW
Applications



PS4875/25


2G, 3G mobile base stations
Small exchanges, rural telecom networks and access networks
Transmission relay stations
Microwave/satellite communications stations
Railway stations
Features















Capacity up to 4.35kW (75A @ 58V)
Rectifiers HD4825-3(1450W )inside
Wall-mounted for space saving
Wide input voltage range (90 to 290Vac), up to 415Vac endurance without damage
Effi ciency high up to 90%
Power factor high up to 0.99
Output current Walk-in available
Patented energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Rectifiers and controller hot swappable
Front access
Top cabling
Rectifier CE approval
Compliance with RoHS
Dimensions And Weight
Cabinet
12
model
PS4875/25
W×D×H, mm
450×260×7 00
Weight (kg)
4 0( re cti fier e xc lu ded )
Business-Critical Continuity™
PS4890/800 (ACTURA 48201)
Subrack DC Power Series
-48VDC
up to 4.8kW
Applications



2G, 3G mobile base stations
small access networks
Microwave/satellite communications stations
Features













19” Subrack system
Capacity up to 2.4kW one subrack, 4.8kW dual subracks
Rectifiers R48-800(800W)and SCU inside
Wide input voltage range (85 to 300Vac)
Effi ciency high up to 91%
Power factor high up to 0.99
Output current Walk-in available
Patented energy-saving mode available
Intelligent monitoring and remote control
BLVD, LLVD optional
Rectifiers and controller hot swappable
Rectifier CE/UL approval
Compliance with RoHS
Dimensions And Weight
model
PS4890/800 single subrack
PS4890/800 dual subracks
W×D×H, mm
485×345×90
485×345×180
Weight (kg)
8.8(rectifier excluded)
17.9(rectifier excluded)
13
DC Power System
PS24600/75
Integrative DC Power Series
+24VDC
up to 17.4kW
Applications




PS24600/75
2G, 3G mobile base stations
Medium exchanges, rural telecom networks and access networks
Transmission relay stations
Microwave/satellite communications stations
Key Features












Capacity up to 17.4kW (600A @29V)
Rectifiers HD2475-2(2175W )inside
Wide input voltage range (120 to 290Vac), up to 415Vac endurance without damage
Effi ciency high up to 88%
Power factor high up to 0.99
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Rectifiers and controller hot swappable
Front access
Top or bottom cabling
Rectifier CE approval
Compliance with RoHS
Dimensions And Weight
Cabinet
Rectifier
Controller
14
model
PS48600-3/2900-X5
HD2475-2
PSM-A11
W×D×H, mm
600×600×2 00 0
105
×400×245
Weight (kg)
1 58 (r ec ti fier ex clu de d)
8
Business-Critical Continuity™
PSC48150/25
Integrative DC Power Series
+24Vdc/-48Vdc, 7.2kW
Applications




2G, 3G mobile base stations
Medium exchanges
Transmission relay stations
Microwave/satellite communications stations
Features












+24V/-48V DC/DC system
Capacity up to 7.2kW
Wide DC input voltage range: 21V~29V
DC/DC module(1200W)inside
DC/DC converter Hot-swappable
Extremely low radiation, meeting
Relay output for alarm port
Complete lightning proof in input and output rated at 5KA(8/20us)
Complete fault protection functions
Optional remote monitor and control
Front access
Compliance with RoHS
PSC48150/25
Dimensions And Weight
Cabinet
DC/DC converter
model
PSC48150/25
C24/48-1200
W×D×H, mm
200×400×146 0
85.5×287×132.5
Weight (kg)
45 (rectifier excluded)
2.5
1
EMERSON NETWORK POWER.
THE GLOBAL LEADER IN ENABLING
BUSINESS-CRITICAL CONTINUITY.™
AC POWER
CONNECTIVITY
DC POWER
EMBEDDED COMPUTING
EMBEDDED POWER
OUTSIDE
PLANT
MONITORING
OUTSIDE PLANT
POWER SWITCHING
& CONTROLS
PRECISION COOLING
RACKS & INTEGRATED
CABINETS
SERVICES
SURGE PROTECTION
Protecting and moving voice ,video and data from the
central office closer to the subscriber. We deliver a f ull line of
enclosures,cabinets and shelters that meet the networked
world’s demands for high speed without interruption,
from MESA® and DEC integrated enclosure solutions to
Emerson Network Power ES, EC, EPC outdoor power solutions
to cross-connects to ProFORM® distribution terminals to
NetSpanTM Integrated FTTx Solutions.
OUTSIDE PLANT. Yet another way Emerson Network power
enables Business-Critical Continuity™.
16
Business-Critical Continuity™
EPC48180/1800-FA
-48VDC Outdoor Power Cabinet
Applications



Outdoor stations of GSM, UMTS, CDMA
Fiber optic transmission systems
Digital loop carriers
Features





















Capacity up to 10.44kW (180A @ 58V)
Totally front access in favor of space-saving
Forced vent cooling system
Patent design of Isolated air channel for safe operation
IP55 for equipment chamber
Forced vent cooling for battery chambers
Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
Rectifiers R48-1800(1740W) and SCU inside
Efficiency high up to 92%
Power factor high up to 0.99
Output current Walk-in available
Perfect fan speed control for energy-saving
Patent energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Class B+C lightning protection optional
Rectifiers and controller hot swappable
Inner dual 330Ah battery Chambers
Rectifier CE/UL approval
Compliance with EN60950 and IEC60950, RoHS
H-mast platform installation available
EPC48180/1800-FA
Dimensions And Weight
Cabinet
model
EPC48180/1800-FA
W×D×H, mm
700×700×1700
Weight (kg)
150(rectifiers and batteries excluded)
17
Outside
Plant
EPC48120/1800-F
-48VDC Outdoor Power Cabinet
Applications



EPC48120/1800-F
Outdoor stations of GSM, UMTS, CDMA
Fiber optic transmission systems
Digital loop carriers
Features





















Capacity up to 6.96kW (120A @ 58V)
Totally front access in favor of space-saving
Forced vent cooling system
IP45 for equipment chamber
Patent design of Isolated air channel for safe operation
Forced vent cooling for battery chambers
Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
Rectifiers R48-1800(1740W)and SCU inside
Effi ciency high up to 92%
Power factor high up to 0.99
Output current Walk-in available
Perfect fan speed control for energy-saving
Patent energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Class B+C lightning protection optional
Rectifiers and controller hot swappable
Inner dual 330Ah battery Chambers
Rectifier CE/UL approval
Compliance with EN60950 and IEC60950, RoHS
H-mast platform installation available
Dimensions And Weight
Cabinet
18
model
EPC48120/1800-F
W×D×H, mm
600×630×1500
Weight (kg)
140(rectifiers and batteries excluded)
Business-Critical Continuity™
EPC48120/1800-HA(B)
-48VDC Outdoor Power Cabinet
Applications



Outdoor stations of GSM, UMTS, CDMA
Fiber optic transmission systems
Digital loop carriers
Features























Capacity up to 6.96kW (120A @ 58V)
Totally front access in favor of space-saving
Heat-exchange cooling system
IP55 for equipment chamber
Wide operation temperature, -40~+45℃ optional
Patent design of Isolated air channel for safe operation
Forced vent cooling for battery chambers
Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
Rectifiers R48-1800(1740W)and SCU inside
Efficiency high up to 92%
Power factor high up to 0.99
Output current Walk-in available
Perfect fan speed control for energy-saving
Patent energy-saving mode available
Intelligent monitoring and remote control
Surge protection on AC, DC and signal side
Class B+C lightning protection optional
Rectifiers and controller hot swappable
Inner dual 330Ah battery Chambers
Rectifier CE/UL approval
CE mark
Compliance with EN60950 and IEC60950, RoHS
H-mast platform installation available
EPC48120/1800-HB
Dimensions And Weight
Cabinet
model
EPC48120/1800-HA
EPC48120/1800-HB
EPC48120/1800-HA
Op. temp.
-10 +45℃
-40 +45℃
~
W ×D×H, mm
Weight (kg)
600×600×1700
150(rectifiers and batteries excluded)
~
19
Outside
Plant
EC200T/01
Outdoor Battery Cabinet
Applications



EC200T/01
Outdoor stations of GSM, UMTS, CDMA
Fiber optic transmission systems
Digital loop carriers
Features






Cater up to 3 strings of 165Ah batteries
Thermoelectricity cooler (TEC) inside
Inner temperature 5~15℃ below outside ambient
IP55
Dry-contact alarm for fans and door sensor
Compliance with RoHS
Dimensions And Weight
Cabinet
20
model
EC150F/01
Op. temp.
-10 +55℃
~
W×D×H, mm
650×720×1 40 0
Weight (kg)
1 00 (ba tt eri es e xc lu ded )
Business-Critical Continuity™
EC150F/01
Outdoor Battery Cabinet
Applications



Outdoor stations of GSM, UMTS, CDMA
Fiber optic transmission systems
Digital loop carriers
EC150F/01
Features





Cater up to 2 strings of 165Ah batteries
Forced vent cooling
IP34
Dry-contact alarm for fans and door sensor
Compliance with RoHS
Dimensions And Weight
Cabinet
model
EC150F/01
Op. temp.
-10~+45℃
W ×D×H, mm
700×700×1 00 0
Weight (kg)
1 00 (b at ter ies ex cl ude d)
21
Outside
Plant
EC100F/01
Outdoor Battery Cabinet
Applications



Outdoor stations of GSM, UMTS, CDMA
Fiber optic transmission systems
Digital loop carriers
EC100F/01
Features





Cater up to 2 strings of 165Ah batteries
Forced vent cooling
IP34
Dry-contact alarm for fans and door sensor
Compliance with RoHS
Dimensions And Weight
Cabinet
22
model
EC100F/01
Op. temp.
-10 +45℃
~
W×D×H, mm
600×600×1 00 0
Weight (kg)
1 00 (ba tt eri es e xc lu ded )
EMERSON NETWORK POWER.
THE GLOBAL LEADER IN ENABLING
BUSINESS-CRITICAL CONTINUITY.™
AC POWER
CONNECTIVITY
DC POWER
EMBEDDED COMPUTING
EMBEDDED POWER
AC POWER
MONITORING
OUTSIDE PLANT
POWER SWITCHING
& CONTROLS
PRECISION COOLING
RACKS & INTEGRATED
CABINETS
SERVICES
SURGE PROTECTION
Sustaining critical operations that simply can ’t
go down. We deliver a full range of uninterruptible
Liebert® AC power systems and complete
associated power distribution and enclosures ,
from individual products to integrated systems
that keep network closets up and running.
AC Power.
Yet another way Emerson Network
Power enables Business-Critical Continuity™.
23
AC Power
AC POWER
Confi guration Matrix
24
Small System
Medium System
Small System
SERIES:
US11R
iTrust 31
iTrust 2G
RATING:
1/2/3KVA
10/15/20KVA
3/6/9/12/15/18KVA
MOUNTING:
Tower/Rack
Tower
Tower/Rack
I/O:
1-ph./1-ph.
3-ph./1-ph.
1-ph./1-ph.
VOLTAGE:
220/230/240 (L-N)
380/220
220 (L-N)
FREQUENCY:
50Hz
50Hz
50Hz
Large system
Medium System
SERIES:
NX
Hipulse-U
RATING:
10/15/20/30/40/60/80/100/120/140/160/200KVA
MOUNTING:
Tower
Tower
Tower
I/O:
3-ph./3-Ph.
3-ph./3-ph.
1-ph./1-ph.
VOLTAGE:
380/400/415 (L-L)
380/400/415 (L-L)
220(L-N)
FREQUENCY:
50/60Hz
50/60Hz
50Hz
160/200/300/400KVA
Outdoor UPS
2KVA/3KVA
Business-Critical Continuity™
US11-R Series
1/2/3KVA


Applications






Servers/Storage/Workstation
Telecommunication, VoIP
Small Office Network
Data Warehouses
Medical Diagnostics
Process Automation Equipmentsv
Special Features











Rack/Tower design, adaptable for table and 19' IT rack application
Double conversion, true on-line style
Fully digital control
Input surge suppressor equipped
CE marked
IGBT based rectifier and excellent input performance
Super wide input window
Mutiple AC output connections
2U height
High EMC performance, classB achieved
Intelligent battery management
Dimensions And Weight
Model Name
US11R-0010
US11R-0010L
US11R-0020
US11R-0020L
US11R-0030
US11R-0030L
UF-B0007-06
UF-B0009-06
Size(WDH in MM)
440×400×87
440×400×87
440×400×87
440×400×87
440×400×87
440×400×87
440×400×87
440×400×87
Weight(Kg)
17.5
7.8
29.1
9.6
30.5
10.5
20.5
21.5
Note: US11R-0020 will be shipped with a VF-B0007-06
US11R-0023 will be shipped with a VF-B0009-06
25
AC Power
US11-R Series Datasheet
US11R-0010
US11R-0010L
1KVA
Model
Nominal Power Rating at 0.7 PF
Input Parameters
Rectifier Type
IGBT-based PFC(Power Factor Correction)
Input Voltage
220Vac,
Permissible Input Voltage Range
Permissible Input Frequency Range
Input Power Factor at nominal voltage
Battery
Battery Type
Nominal Battery Bus
Recharging Time to 90% Recovery
Output Parameters
Inverter Type
Output Power
Output Connection
Output Voltage
Output Frequency
Output Voltage THD
Capability to handle High Crest Factor Load
Capability to handle Step L oad
120-288Vac
50Hz ±2%,5%,7%,10% User selectable
≥0.99
Overload Capability
System Parameters & Standards
AC-AC Efficiency
Switch Time When Input Fails
Noise
Display
Dimension (W×D×H)mm
U-Height
Weight (Standard/L model)
Safety
EMI /EMC
Inmunity
Surge Protection
Protection
Communication & Management
Interface Port
Web/SNMP Card
Environmental Parameters
Operating Temperature Range
Relative Humidity
Maximum Altitude above MSL
26
US11R-0020
US11R-0020L
2KVA
US11R-0030
US11R-0030L
3KVA
1-ph, 3-w
Maintenace Free, V RLA (Valve Regu lated Lead Acid)
36Vdc
72Vdc
<4 hours
<4 hours
72Vdc
<4 hours
IGBT-based Inverter
0.7kW
1.4kW
GB/IEC
GB/IEC
220Vac, 1-ph, 3-w
50Hz ±0.2%
<3% at linear load; < 5% at non-linear load
3:1 (compliant with IEC 62040-3)
10 0%
105% FL Infi nite
105-125% FL for 5 mins
125-150% FL for 1min
>150% FL for 10s
>89%
2.1kW
GB/IEC/Terminal
>90%
>90%
0s
<43dB
LED
440×400×87
2u
17.5/7.8kg
EN62040-1-1, CE Marked
EN50091-2 Class B
EN50082-1
IEC 60664-1 Level IV
IP21
<45dB
2u
29.1/9.6
Serial / Dry Contact / SNMP Card
Optional
0 ℃ to 40℃ (UPS) & 25℃ ±5 (Battery)
0% to 95% (non-condensing)
1500m (as per IEC 62040-3)
2u
30.5/10kg
Business-Critical Continuity™
UH31 Series 10/15/20KVA

Applications

Small data centers of banks/stock exchanges, server groups, small/middle computer rooms,
offices, PC groups, important facilities, etc
Features











Three phases input, one phase output ( 220/230Vac)
True on-line style
IGBT based rectifier/inverter
DSP control
Super wide input window (-45% +15%)
On-line operation when input phases lose
D-class surge suppressor equipped
Intelligent battery management
Chinese/English LCD interface available
Class A EMC standard acquired
Input phase loss tolerance
~
Dimensions And Weight
Model Name
UH31-0100L
UH31-0150L
UH31-0200L
Size(WDH in MM)
280×875×770
280×875×770
280×875×770
Weight(Kg)
97
97
116
27
AC Power
UH31 Series Datasheet
Model
Nominal Power Rating at 0.7 PF
Input Parameters
Rectifier Type
Input Voltage
Permissible Input Voltage Range
Permissible Input Frequency Range
Input Power Factor at nominal voltage
Battery
Battery Type
Nominal Battery Bus
Output Parameters
Inverter Type
Output Power
Bypass Voltage Ran ge
Output Voltage
Output Voltage Regulation
Output Frequency
Output Voltage THD
Capability to handle High Crest
Factor Load
Capability to handle Step Load
Overload Capability
System Parameters &Standards
AC-AC Efficiency
S wit ch Ti me W hen I np ut F ai ls
Noise
Display
Dimension (W×D×H)
Weight (Standard/L model)
Safety
Im mu ni ty
EMC
Surge Protection
Parameters &Standards
Operating Temperature Range
Relative Humidity
Maximum Altitude above MSL
28
UH31-0100L
10KVA
UH31L-0150
15KVA
UH31-0200L
20KVA
IGBT-based PFC (PF Corrected)
380Vac, 3-ph, 4-w
120Vac-276Vac
45-55Hz
≥0.95
VRLA (Value Regulated Lead Acid)
480Vdc
480Vdc
480Vdc
IGBT-based Inverter
7kW
10.5kW
120 Vac -25 3Vac
220Vac, 1-ph, 3-w
±0.5%
50Hz
< 3% at linear load; < 5% at non-linear load
3:1 (compliant with IEC 62040-3)
14kW
100%
105-125% FL for 10 mins
125-150% FL for 1min
>150% FL for 200ms
>91%
>92%
0s
<55dB
<60dB
LED+LCD
280×875×770mm
97kg
116kg
EN60950
EN 61 00 0-4 -2 ,3 ,4 ,6 ,8 ,1 1 L ev el I II , EN 61 00 0-4 -5 L ev el I V
EN55022 Class A
IEC 60664-1 Level IV
0 ℃ to 40℃ (UPS) & 25℃ ±5℃ (Battery)
0% to 95% (n on-condensing)
1500m (as per IEC 62040-3)
Business-Critical Continuity™
iTrust 2G Series UPS
Applications




Industrial equipments
Small data centers
Computing centers
Telecommunication network hubs
Features











Modular Design- Plug & Play
N+X Redundancy - Higher reliability
Easy and cheap expansion- Modules only
Online during maintenance- By simply replacing modules
Space saving - Compact Design
Large Capacity Battery Affordable -Extendable 10A/20A charger available
Energy Saving - High Efficiency and excellent input PF
Higher adaptability to harsh input - Extremely Wide Input window
Longer battery life available - Intelligent Battery Management
Quiet - Low noise
Less worry - Self diagnosis and Fault Prediction
Dimensions And Weight
Model Name
Power Module
UF-P0030
Battery Module
UF-B0007-8
10A Charger Module
UFP-BCH110/10
20A Charger Module
UFP-BCH110/20
6-Bay Rack
UP11-0180/6
12-Bay Rack
UP11-0180/12
Size(WDH in MM)
436 × 412 × 85
436 × 400 × 36
436 × 412 × 85
436 × 412 × 85
500 × 552 × 994
500 × 552 × 1492
Weight(Kg)
10.4
26
7.6
10.4
70
105
29
AC Power
iTrust 2G Series Datasheet
Models
Model Name
Input Parameters
Rectifier Type
Input Voltage
Permissible Input Voltage Range
Permissible Input Frequency Range
Input Power Factor at nominal voltage
Ace
Battery
Battery Type
Nominal Battery Bus
Output Parameters
Inverter Type
Output Rating
Output Power Factor
Output Voltage
Output Voltage Regulation
Output Frequency
Capability to handle High Crest Factor Load
Capability to handle Step Load
Compliance to EMC Class-A
Overload Capability
System Performance
AC-AC Efficiency
Transfer Time When Input Fail
Environmental Parameters
Operating Temperature Range
Relative Humidity
Maximum Altitude above MSL
Physical Parameters &Standards
Colour
Degree of Protection
30
3KVA
6KVA
2.4kW
4.8kW
UP11-0180/12(12-Bay)
9KVA
12KVA
7.2kW
9.6kW
UP11-0180/6(6-Bay)
IGBT-based PFC
220Vac/1ph/3w
120-288Vac
45-55Hz
≥0.99 without any Filter
VRLA
96Vdc
IGBT-based
3/6/9/12/15/18 KVA
0.8
220Vac/1ph/3w
1%
50Hz
3:1
10 0%
Applicable for both Radiated & Conducted
105% FL for continuous running
125% FL for 10 minutes
150% FL for 10 S
> 90%
0s
0 ℃to 40℃ (UPS)
0% to 95% (non-condensing)
1500m (as per IEC 62040 3)
Black
IP21
15KVA
12kW
18KVA
14.4kW
Business-Critical Continuity™
NX Series UPS
Applications





Server Rooms and Mid-sized Data Centers
Telecommunication (Fixed, WiLL & Mobile) Billing Computers
Networks (LAN, MAN & WAN), InfoCom and WiFi Hot Spots
Industrial Process & Motion Automations for Mid-sized Plants
Medical Diagnostic / Imaging Equipment
Features












Full digital control based on latest DSP
Advanced Vector Control to Achieve Excellent Output Performance
'Green UPS' Design with High input power factor : 0.99 Low input current harmonic of less than : 3%
Wide input window : 208-477V (L-L voltage)
Parallel up to 6 units, No MSS needed
High Efficiency: up to 94%
Compact Footorint and Front Access
Unique Dual Bus design
Flexible Power Walk-in
Built-in Redundancies to Achieve High Reliability(fans/auxiliary power supply card/..)
Intelligent battery management
Self diagnosis
Dimensions And Weight
Model Name
NXe-10KVA
NXe-15KVA
NXe-20KVA
NXe-30KVA
NXa-40KVA
NXa-60KVA
NXa-80KVA
NXa-100KVA
NXa-120KVA
NXa-140KVA
NXa-160KVA
NXa-200KVA
Size(WDH in MM)
600×700×1400
600×700×1400
600×700×1400
600×700×1400
600×825×1600
600×825×1600
600×825×1600
700×825×1800
700×825×1800
1000×825×1800
1000×825×1800
1000×825×1800
Weight(Kg)
180
204
204
260
340
400
445
720
720
824
973
973
31
AC Power
NX Series Datasheet
Nxe10
Nxe15
Nxe 20
Nxa30
Nxa40
Nxa60
Nxa80
Nxa100
Nxa120 Nxa140
Nxa160 Nxa200
Models
NominalPowerRatingat0.8PF 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 140KVA 160KVA 200KVA
Input Parameters
Rectifier Type
IGBT-based Vector Controlled PFC (PF Corrected)
Input Voltage
380/400/415Vac (Accepted from 305-477Vac without Batt. Use)
In pu t F re qu en cy
4 0- 70 Hz
Input Current THD
<3% (without any Filter)
Input Power Factor
≥0.99 (without any Filter)
Flexi Power Walk-In
5 to 30S (Selectable)
Battery
Battery Type
VRLA (Value Regulated Lead Acid) / Wet-Flooded / NiCd
End-Cell Voltage
Selectable from 1.60-1.90Vdc/Cell (VRLA)
DC ripple Current in fl oat
<5%(C10 AH Capacity) RMS Value
mode
DC ripple Voltage in
<1% (RMS Value)
fl oat & Const V Ch.mode
Temperature
Standard (for in-build batteries for 10/15/20/30/40 KVA)
Compensated Battery
Optional (fo r all other battery confi guration s)
Charging
In-Built VRLA Battery
Optionally applicable for 10/15/20/30/40 KVA
Availability
Output Parameters
Inverter Type
IGBT-based Vector, Repetitive & PI Controlled
Output Power
8kW 12kW
16kW
24kW 32kW
48kW
64kW
80kW
96kW 112kW 128kW 160kW
Output Voltage
380/400/415Vac * (Nominal: 400V) 3-ph, 4-w (Ph+N)
Output Voltage
±0.5%
Regulation
O ut pu t F re qu en cy
5 0/ 60±0.05Hz Regulation
Output Voltage THD
1% (max)
Max. Crest Factor Load
3:1 (compliant with IEC 62040-3)
Capability to handle
100%
Step Load
Max. Leading PF Load
Up to 0.9
Voltage Displacement
120o±1oel (with 100% unbalanced load)
Overload Capability
110 for 60 minutes, 125 for 10 minutes, 150 for 1 minutes
Standards
EMC Class
Class A (Applicable for both Radiated & Conducted)
Enclosure IP
IP 20 even with front door in opened condition, IP21 Optional
Standards &
IEC 62040-3, IEC 62040-2, IEC 62040-1-1, IEC 60146-1-1, IEC 61000-4-2,4,5,6,8,11, EN 50091-1-1,
Conformities
EN 50091-2, EN 50091-3, EN60950, EN 60529, ANSI C62.41 (IEEE 587)
Environmental Parameters
Operating Temperature
0 to 40℃ (UPS) & 25 ±5℃ (Battery)
Range
Relative Humidity
0 to 95% (non-condensing)
Maximum Altitude
1000m (as per IEC 62040-3)
above MSL
32
Business-Critical Continuity™
Hipulse-U Series 160/200/300/400KVA

Applications









Medinm & large Data Center
Telecommunication
Industrial Automation
Transport Automation
Banking, Insurance and Financial Sernices
Software Development Houses/Software Technology Parks(STP)
Building Automation
Medical Diagnostics
Satellite
Features


















Fully Digital, Twin DSP controlled.
Rated at 0.9 output power factor to deliner more real power
Handle Leading Power factor Loads withour KW de-rating under specified conditions
On-Line Double Conversion
IGBT-based PWM Inverter
Wide input voltage tolerance(+15/15%)
Wide input frequency tolerance(45Hz-65Hz)
High overload capability of static bypass(14 times for 10 milliseconds and 10 times for 100
nukkusecibds)
Built-in maintenance bypass(Single and 1+N Models)
Wrap-around maintenance bypass(optional)
Front acces for spares replacement and preventive maintenance
Easy Dual bus Configuration architecture
Adjustable frequency synchronisation window up to 9% in the static bypass
Provision of automatic battery circuit breaker instead of using conventional isolator in the DC path
Field protocols ModBus/Jbus
Eady Scalability (Parallel 1+N configuration up to 6 modules paralleling)without centralised Main
Static Switch (MSS)
Bypass Switch
Compact footorint
Dimensions And Weight
Model Name
Hipusle U-160KVA, 6 Pulse
Hipusle U-160KVA, 12 Pulse
Hipusle U-200KVA, 6 Pulse
Hipusle U-200KVA, 12 Pulse
Hipusle U-300KVA, 6 Pulse
Hipusle U-300KVA, 12 Pulse
Hipusle U-400KVA, 6 Pulse
Hipusle U-400KVA, 12 Pulse
Size(WDH in MM)
1250×840×1910
1640×840×1910
1250×840×1910
1640×840×1910
1640×840×1910
2280×840×1910
2280×840×1910
2280×840×1910
Weight(Kg)
1200
1725
1350
2000
1600
2200
2100
2750
33
AC Power
Hipulse-U Series Datasheet
Hipulse UPS System
Nominal Rating(KVA)(0.9pf)/kW
160/144
200/180
300/270
400/360
Rectifier Type
6P
12P
6P
12P
6P
12P
6P
12P
Input
Voltage
380/400/415V(+/-15%)-3Ph-4w(rectifier:290-498V)
Frequency
50 or 60Hz +/-5%
ITHD
4 to 9% with optional harmonic filter
Power Factor
0.90-0.95 with optional harmonic filter
Output
Voltage
380/400/415V-3Ph-4w
Voltage stability
-Steady state
+/-0.5%
-100% Load Step
+/3%
Frequency
50 or 60Hz
Frequency Stability
-Synchronised with the bypass supply
+/0.5 Hz, +/-1 Hz, +/-2Hz, +/-3Hz(settable)
-Auto-Synchronised
+/0.1%
Overload copacity from inverter at vominal voltage
-3 Ph
110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute
-1 Ph
200% for 30 seconds
short circuit current from inverter
-3 Ph
1.5 in for 5 seconds (in acordance with EN 50091-1-1)
-1 Ph
2.9 in for 5 seconds
2.2 in for 5 seconds
Voltage Distortion with Linear Load
<3%
Voltage Distortion with 100%
<5%
Non-Linear Load
Max.Deliverable Power
100%
with Non-Linear Load(CF-3:1)
Max Unbalanced Load
100%
Voltage Displacement With
120o+/-1oel
100% Unbalanced Load
Output Voltage Dissymmetry
2%
with 100% Unbalanced Load
Standards and Approvals
Safety / EMC / Design
IEC60950-1,IEC62040-1-1,UL1778,IEC62040-2 CLASS A,EN50091-CLASS A,IEC62040-3
European Directives
CE
73/23/EEC and 89/336/EEC
34
Business-Critical Continuity™
Outdoor Series
Application

Outdoor BTS
Special Features















Natural cooling, high system reliability achieved
Dual conversion, online style
Fully digital control
Auto start up when mains recovered
Super wide input window (150-310V L-N)
IP55 protection level
Wide operation Temperature: -40-550C
High level surge suppressor can be equipped inside; (Optional)
Boosted/oat charging auto transfer
3 mounting options available (wall/mask/oor)
Zero output interrupt when input fails
Optional charger for quick battery recovery in long backup system
Heater optional for cold area
Optional Battery cabinet available with maximum 4 hours backup time at full load
Power module separate with battery enclosure, high system exibilit y achieved
Dimensions And Weight
Model Name
Outdoor 2KVA UPS
Outdoor 3KVA UPS
Battery Cabinet (South Type)
Battery Cabinet (North Type)
*: Including Mounting Kit,36Kg Net
**: Including Mounting Kit,42Kg Net
UH11-0020LC
UH11-0030LC
U6-100C3S
U6-100C3N
Size(WDH in MM)
485×263×615
485×263×615
850×550×1170
850×550×1170
Weight(Kg)
53*
59**
70
72
35
AC Power
Outdoor Series Datasheet
Capacity
Model Name
Input
Rated Voltage
Voltage Range
Frequency
Power Factor
Output
Powe Factor
Normal Voltage
Frequency
Frequency Tracking Rate
Inverter Overload Capability
Peak Factor
Bypass Voltage
Efficiency (NormalMode)
Sheft Time
Utility Failure
Shift between invertermode and
bypass mode (Synchronized )
Insulation
In su lation Resistanc e
Dielectric Strength
Environment
O per ati on tem per at ur e
Storage temperatu re
r el ati ve h um idi ty
altitude
Protection Level
Noise
36
2KVA/3KVA
UH11-0020LC, UH11-0030LC
220Vac
150-310Vac
45~65Hz
> 0.98
0.7 temp<5℃ 0.6 temp>10℃
220Vac 3%
50Hz
≤1 Hz/s
105%-125%, 5mins, >125%, 20s,
3:1
150~310Vac
>89%
0ms
< 10ms
>2MΩ(500Vdc)
(Output to earth Input to earth)2820Vdc,leakage current <3.5mA for 1min without arc or
breakdown
-4 0℃ -55℃
-40 ℃ -70℃
1 0% -1 00 % ( no c on den si ng )
Under 4000m, over 4000m, de-rated,
IP55
<40dB
Business-Critical Continuity™
Monitoring Solutions
Our Monitoring Solution Includes 5 Parts
1.Point-to-point and internet-based network remote monitoring, unlimited with the number of
nodes
2.SNMP Card: An internet node, providing UPS with Ethernet communication capability
3.UPS Network Adapter: Monitoring UPS products of other brands
4.UPS Adapter for Equipment Room Signals Applied together with our SNMP Card, realizing
centralized monitoring and processing of multi environment measures such as temperature,
humidity, infrared, door alarm, water immersion ( 8 analogues and 8 dry contacts)
5.Wireless MODEM: Able to send wireless messages, reporting UPS operation status and alarms to
the customers and realizing No-Man-On-Duty
Features













Java programming language. Web-based general-purpose monitoring software
Compatible with multi operation systems, eg., Windows, Linux, Solaris, AIX, HP-UX, etc.
Can log on via any computer on network
UPS by-layer management mode
Complete history records for inquiry, statistics and preview before printing
Multi alarming: Sound, paging, email and messages, etc.
Multi language versions, on-line upload and upgrade
WEB-configured interfaces, very easy to operate
Large storage of history records
Least system resource occupied
Strict safety management mechanism
On-line smooth access system for new equipment
Multi system environment measures accessible
37
AC Power
SiteMonitor
1. Easy installation
2. Clear display of UPS operation status
Can name based on requirements and
display by layer
Click on UPS icons to check all operation
indices and historical records online, with
power status completely in hand
3. Easy setting and adjustment
Under authorization, a network
administrator can remotely control the
center, eg. operate turnoff, battery selfdiagonosis, erase after sound alarm, etc.
38
Model selection and confi guration
Business-Critical Continuity™
SNMP Card-A Bridge Connecting
UPS and Network
The SNMP card is based on TCP/IP communication protocol and can also
support SNMP, HTTP(web server), Telnet communication protocols to meet the
needs of all sorts of networks
Features





Supports web browse and NMS management systems
Software can be updated on line
10/100M network self-adapting
Hot plug-in/plug-out supported
All the settings can be done through software
39
AC Power
Intelligent Battery Management
Auto-adaptable on EOD(End Of Discharge) Adjustment


Different discharging solution for short backup-time system (<1h) and long backup-time
system(>1h)
The data of different models of batteries are stored in DSP and the UPS will detect the discharging
current and automatically adjust the EOD for best performance of the battery. In this way, overdischarge of battery is avoided
Self-diagnosis

Battery self-diagnosis can be set to operate periodically via front panel
Auto-switch between Boost and Float Recharging

Shorten recharging period and prolong the battery life by 50%
Temperature Compensation

40
Auto-adjustment for fl oat charging voltage according to ambient temperature
EMERSON NETWORK POWER.
THE GLOBAL LEADER IN ENABLING
BUSINESS-CRITICAL CONTINUITY.™
AC POWER
CONNECTIVITY
DC POWER
EMBEDDED COMPUTING
EMBEDDED POWER
RACKS & INTEGRATED CABINETS
MONITORING
OUTSIDE PLANT
POWER SWITCHING
& CONTROLS
PRECISION COOLING
RACKS & INTEGRATED
CABINETS
SERVICES
SURGE PROTECTION
Optimizing technology and performance needs
for the global IT and telecom markets. We deliver
standard and customized integrated cabinet
solutions that meet unique and specifi c needs,
from knürr and Liebert® rack solutions for
customer rooms of all sizes to knürr ,MESA® and
Netspan™、Matrix™ enclosures and shelters for
wireline and wireless applications.
RACKS & INTEGRATED CABINETS .Yet another
way Emerson Network power enables BusinessCritical Continuity™.
41
Racks & Integrated Cabinets
Server Enclosure Systems
Rack system and IT total solution
Emerson Network Power Co.,Ltd. Launched the high reliability and high
availability rack system and IT room total solution that suit the features of
blade server based on its deep understanding in the user ’s requirements for IT
application and the existing issues.
Applications



Network access rooms
Computer rooms
Data center
Features and Benefits





World-leading heat dissipation design: The 83% perforating rate that is the highest in the world
meets the heat dissipation requirement of high thermal-density of blade server
Special modular structure: Modular structure and modular installation: Convenient storage and
transportation, fast and convenient disassembly and assembly
Reliable and stable power supply and distribution design: double conversion online UPS, the total
power distribution solution meets the different customer requirements
Convenient cable management: Comprehensive cable management accessories meet the
different cable management requirements
Advanced rack monitoring and safety system: Remote monitoring to the rack environment,
including temperature, humidity, door alarm and smoke, etc
Miracel Series:
Product Type
NR-M060820
SR-M061020
SR-M061220
SR-M081020
SR-M081220
Accessories
42
Capacity
42U
42U
42U
42U
42U
Width(mm)
Distance(mm)
High(mm)
600
800
2000
600
1000
2000
600
1200
2000
800
1000
2000
800
1200
2000
Fan, plinth, cable management unit, power distribution unit, etc.
EMERSON NETWORK POWER.
THE GLOBAL LEADER IN ENABLING
BUSINESS-CRITICAL CONTINUITY.™
AC POWER
CONNECTIVITY
DC POWER
EMBEDDED COMPUTING
EMBEDDED POWER
PRECISION COOLING
MONITORING
OUTSIDE PLANT
POWER SWITCHING
& CONTROLS
PRECISION COOLING
RACKS & INTEGRATED
CABINETS
SERVICES
SURGE PROTECTION
Maintaining precise temperature for reliable equipment
performance. We deliver “chip-to-room cooling ”-the
most comprehensive range of liebert® precision-cooling
solutions,which protect mission-critical applications
from even the slightest increase in temperature.
PRECISION COOLING. Yet another way Emerson
Network power enables Business-Critical Continuity™.
43
Precision Air Conditioning
Liebert DataMate3000(S)
Precision cooling for Small Equipment Rooms
DataMate3000 series air conditioning is developed by Emerson Network Power
Co., Ltd. for small equipment rooms. The system provides 5.5kW , 7.5kW and
12.5kW cooling capacities and many configuration options.
Applications





Mobile base stations and control centers
Communications base stations
Outdoor equipment rooms
Microwave/Satellite earth stations
Medium ,Small computer rooms
Features and Benefits










High sensible cooling capacity and energy efficient. Saves 20-30% energy as compared to
"comfort" air conditioner
Provides consta nt temperature and humi dity, high air flow rate and low energy consumption to
meet specifi c reqirements of computer rooms
Copeland scroll compressor provides high reliability, efficiency and maximum li fe
Large LCD display, password protection and self diagnosis
Wide input voltage range, allowing voltage fl uctuation 20%
Phase loss protection ,phase order detection, automatic regulation to phase disorder
Automatic startup when utility is recovered
Front access ,easy for maintenance and fl exible installation
Standard port for monitoring equipment
Flexible and automatic switchover and alternative operation between master and slave
Dimensions And Weight
model
Indoor model
DataMate3000(s)
Outdoor model
44
DME05W
DME07W
DME07M
DME12M
DMC07W
DMC12W
W×D×H, mm
510×386×1740
510×386×1740
500×550×1900
500×550×1900
702×408×626
702×408×1238
Weight (kg)
80
85
150
160
34
58
Capacity
5.5 kW
7.5 kW
7.5 kW
12.5 kW
7.5kW
12.5 kW
Business-Critical Continuity™
Liebert PEX
Precision cooling for medium/large equipment room
The Liebert PEX is the next generation precision air conditioning system from
Emerson Network Power. The PEX is the latest in a long line of advanced
products from the Liebert family designed to support business-critical
applications.
Applications







Data Centres
Telecom/CATV
Computer Rooms
Labs and Test Rooms
Network Centres
Production Facilities
Hospitals and medical diagnostic rooms
Features and Benefits








Front access for convenient maintenance. There is no need to keep back or sides clear
The Liebert iCOM™ control system offers the highest capabilities of unit control, communication
and monitoring
ICOM network provides a choice of Teamwork, Lead/Lag and Cascade functions
A-Frame Evaporator Coils has larger surface to provide even air flow distribution. Its heat exchange
is highly efficient
Unique fan driving system ensures stable system operation and more efficient airflow
Infrared Humidifier, Full capacity achieved in 5-6 seconds using almost any water quality;
Approved for direct connection to potable water supplies; Autoflush™ cycle helps remove mineral
deposits
All compressorised models are designed to operate on either HCFC R22 or HFC R407C refrigerants
High kW to footprint ratio
45
Precision Air Conditioning
Dimensions And Weight
model
P1020
P1025
P1030
P1035
P2045
P2055
P2040
P2050
P2060
P2070
P3080
P3090
P3100
46
Total Capacity(kW)
(24℃/50%RH)
20.0
23.1
30.1
33.1
45.0
53.2
41.0
46.4
60.6
66.9
81.4
89.3
100.0
Weight (kg)
365
375
385
388
530
570
622
661
680
687
825
825
835
L×W×H, mm
853×874×1970
1704×874×1970
2553×874×1970
Business-Critical Continuity™
Liebert XD
Flexible, Energy-Saving Cooling Solutions For High Heat Density
Applications
Applications




IDC
Blade servers
High density servers and communications switches
Rooms existing high heat density
Features and Benefits






Can cool more than 30 kW per rack
Floor-mount, rack-mount and ceiling-mount modules, plus a choice of cooling capacities, cover
any application requirements
Pumped refrigerant solutions are ideal for use around electronic equipment. No water into the
room
Scalable – add or move fan coils as your needs
Energy effi cient. Total energy savings potential of up to 40% can be achieved with the Liebert XD
solution
Minimal fl oor space requirements all ow more room for I T equipment
Dimensions And Weight
model
Main Unit
Cooling Module
XDP160
XDC160
XDO20
XDV10
XDH20
XDH32
Total Capacity(kW)
(24℃/50%RH)
140
130
17.7
8.3
19
27
Weight (kg)
W×D×H, mm
372
817
68
35
112
112
965×864×1981
1879×879×1981
1829×610×572
597×(749-1003)×355
300×1066×1982
300×1066×1982
47
EMERSON NETWORK POWER.
THE GLOBAL LEADER IN ENABLING
BUSINESS-CRITICAL CONTINUITY.™
AC POWER
CONNECTIVITY
DC POWER
EMBEDDED COMPUTING
EMBEDDED POWER
MONITORING
MONITORING
OUTSIDE PLANT
POWER SWITCHING
& CONTROLS
PRECISION COOLING
RACKS & INTEGRATED
CABINETS
SERVICES
Managing critical equipment activity at multiple
sites and site monitoring around the clock. We
make it easy in today ’s ROL-driven business
environment,with 24/7 remote and selfmonitoring systems and services that provide
continuous oversight of data centers ,computer
rooms and network closets ,as well as wireless ,
wireline and enterprise telecom applications.
MONITORING.
Yet another way Emerson Network
power enables Business-Critical Continuity™.
48
SURGE PROTECTION
Business-Critical Continuity™
Emerson Power Equipment And
Environment Monitoring System
Benefits


Emerson Power Equipment and Environment Monitoring System is applicable to
monitoring in real time and managing in unity power supply equipment (power
system, battery, UPS, generator and low-voltage distributor), airconditioning
equipment and environment(door alarm, temperature, humidity, smoke
detection, water immersion, infrared and scene)in telecom exchanges and base
stations
After11-year development and optimization, Emerson monitoring system
has become a total solution including hardware, software and transmission
products. The monitoring solution can be customized to adapt to different
regions, different maintenance management mechanisms, different exchanges
and different transmission resources. The solution can meet the demands of
monitoring the whole power equipment, environment of both fixed and mobile
telecom networks



Series

Emerson power equipment and environment monitoring system

Single version system
Applications

Power equipment and environment monitoring system
Applicable to monitoring p ower equipment, environment in switch site, base stations,transmission
relay stations
Features Of Monitoring Center


supervision center SC consists of database server, console, printer and auxiliary equipment
The server collects, saves, analyzes and manages all monitoring data from monitoring end office
SU. It gives various alarms (sound & light alarm, email, message, etc.) in case of monitored object's
failure

Real time alarms
In case of monitored object's failure,
the monitoring system can give alarm
within 30 seconds
Multiple alarm reports
There are sound & light alarm, printed
alarm, paging alarm,mobile short
message alarm, E-mail alarm and voice
alarm
Flexible networking
Flexible single or mixed networks can
be set up through CE1, DDN/LL, ISDN,
PSTN and WAN
Supports maintenance management
Provides maintenance anlysis
data,improves maintenance efficiency
and cuts maintenance cost
Real time data collection
The system operates around the clock
and reports in real time the monitored
equipment and environment's
conditions. The system provides firsthand data to evaluate equipment
conditions.
Wide-range monitored objects
The monitored objects include HV
and LV distribution equipment,
power system, air conditioning,diesel
generator, battery and UPS; and also
include environment data in relation
to temperature, humidity, water
immersion, smoke and door
Fexible Transmission Networking
Monitoring center SC, monitoring station SS and monitoring end office SU can form a wide area
network through IP, 2M, DDN, ISDN, PSTN and WAN
49
Monitoring
Communication Solution of
Monitoring System
IP Networking
Features:





Using the available
TCP/IP network in site
Supportive of HTTP, TELNET, FTP
Remote debugging and upgrade
Applicable to:IDC room, MSC room, 3G base station, GPRS and CDMA site
Server
Console
LAN
Host
IP network
IDU
IDU
IDU
IDU
IDU
IDU
Server
Console
LAN
Host
BRG-POOL
E1
Emerson Power Equipment And Environment
Monitoring Software V4.39
Emerson IP Video Monitoring Software
50
IDU
IDU
E1
IDU
IDU
IDU
IDU
Business-Critical Continuity™
Solution of large site



The SU has IDU and sensors
Applicable to: exchange station, switch centers ( MSC)
Monitored equipment: HV and LV, generator diesel, AC distribution, rectifier, DC distribution,
battery strings,DC converter, inverters and air-conditioner, it can also be applied to acquire
theenvironment data, such as smoke detector, temperature and humidity sensor, access control
andwater detector
Generator
Monitoring
Center
Transmission
Low Voltage
Distribution
diesel level
DC Power
Intrusion detector
For Door
IDU-HOST
Smoke Detector
Battery
Water Leakage
Communication line
Power line
Temperature
And Humidity
Air
Condition
solution of small site



The SU has IDU and sensors
Applicable to: base station (BTS)
Monitored equipment: Low Voltage, DC power, air-conditioner, temperature and humidity sensor,
diesel level, smoke detector, door accessl and water detector
Transmission
IDU-HOST
diesel level
Intrusion detector
Smoke Detector
Water Leakage
Temperature
And Humidity
DC Power
Air
Condition
Power meter
51
Monitoring
IDU series product specifications
model
BOM
Description
IDU-HOST
02311425
IDU host
IDU-BAT1
02311434
IDU-BAT2
02311427
IDU-BRG1
02311438
IDU-BRG2
02311429
IDU-THS
33030018
Battery board 1
(1 battery group)
Battery board 2
(2 battery groups)
E1-IP network bridge
communication board
Double E1-IP network bridge
communication board
External THS temperature/
humidity sensor
Functions
10 AI inputs (compatible with digital signals), 4 DI inputs, 1 THS
temperature/humidity input channel, 4 relay outputs, with 4 serial
ports, 2 battery group voltage channels, 1 Ethernet port, 1 USB port and
2 expansion slots
Capable of monitoring 24 battery cells, 1 charge/discharge current,
auto-switchover among measurement ranges of 2V, 6V and 12V
capable of monitoring 48 battery cells, 2 charge/discharge currents,
auto-switchover among measurement ranges of 2V, 6V and 12V
2 Ethernet ports (LAN), 1 E1 port (point-to-point, cannot be upgraded
to double loop
2 Ethernet ports (LAN), 2 E1 ports (supportive of double loop)
Temperature measurement range: -10 ℃~ 50 ℃ . Precision: +/-2℃
Humidity measurement range: 5 ~95%RH. Precision: +/-5% (20 ~
80%RH, 25℃)
IDU series product mechanical specifications
Name
IDU-HOST
IDU-BAT1
IDU-BAT2
IDU-BRG2
BRG-POOL
Sizes
440 ± 1mm × 295 ± 1mm × 44 ± 1mm
122 ± 1mm × 185 ± 1mm × 1.6mm
122 ± 1mm × 185 ± 1mm × 1.6mm
122 ± 1mm × 185 ± 1mm × 1.6mm
440 ± 1mm × 295 ± 1mm × 44 ± 1mm
Weight
≤5kg
≤0.5kg
≤0.5kg
≤0.5kg
≤5kg
The features of IDU include











52
IP-network based, supportive of TCP/IP and network protocols such as HTTP, TELNET, FTP, TFTP
and DHCP
TELNET remote debugging
Highly integrated, with superb processing and storing ability of bottom data
Integrated connection with multiple intelligent devices
Low cost image monitoring solution (USB image and anti-burglary)
High standard lightning protection for all ports. Built-in SPDs are used for all ports, with lightning
protection ability 2-times higher than the international standard
Hardware self-diagnostic ability, including detection of E1 cable status, detection of board
insertion fault, and measurement of CPU usage
Network management function: IP flux statistics, IP contradiction auto-detection, and network
topology structure
Remote on-line upgrading of software
IP networking mode, supportive of transmission modes of double loop, ADSL and E1
Supportive of ADSL static IP address
Business-Critical Continuity™
BRG-POOL

BRG-POOL bridge pool ( BRG-POOL) is conversion device for E1-IP transfer function. It provides
eight independent E1-IP transfer channels and can be flexibly configured through CONSOLE
portaccording to the actual application conditions and meet the requirements of different
networkingmodes
BRG-POOL specifications
model
BRG-POOL
model
BRG-POOL
parameters
10/100M, half/full-duplex self-adaptable, RJ45 port,
Ethernet cable intercross function
Voltage input range
-38V -60Vdc
Dimensions
440mm × 295mm × 44mm
Transmission distance
~
Power
<20W
Weight
< 5kg
100m max.
53
EMERSON NETWORK POWER.
THE GLOBAL LEADER IN ENABLING
BUSINESS-CRITICAL CONTINUITY.™
AC POWER
CONNECTIVITY
DC POWER
EMBEDDED COMPUTING
EMBEDDED POWER
EMBEDDED POWER
MONITORING
OUTSIDE PLANT
POWER SWITCHING
& CONTROLS
PRECISION COOLING
RACKS & INTEGRATED
CABINETS
SERVICES
SURGE PROTECTION
Making power conversion easy for IT and
communications equipment. We deliver a broad
offering of Astec ® and Artesyn® solutions,
including AC/DC and DC/DC power supplies ,
adapters,chargers and power accessories.
EMBEDDED POWER.Yet another way Emerson
Network power enables Business-Critical
Continuity™.
54
Business-Critical Continuity™
GIE4805/2A/500-2
Mini Power System
Key Features


1 U Height and designed for 19” racks
Integrated Battery Low Voltage Disconnection function
Key Benefits

Space efficient solution with all functions integrated
GIE4805/2A/500-2







Nominal system voltage: -48 V
System rated output power @ - 54 V: 540 W
Rectifier rated output power @ - 54 V: 270 W
DC distribution branch
Branch 1
10A(FUSE)
Branch 2
10A(FUSE)
Battery
10A(FUSE)
AC input range: 90-264 V AC
Safety EN 60950
Sub rack dimensions (H x W x D): 43 x 482 x240mm
55
Embedded Power
GEPS4820F/01-10/22-EN
Mini Power System
Key Features


1 U Height and designed for 19”racks
Integrated LVD and priority load
Key Benefits

Space effi cient solution with all functi ons integrated
GEPS4820F/01-10/22-EN







56
Nominal system voltage: - 48 V
System rated output power @ - 54 V: 1600 W
Rectifier rated output power @ - 54 V: 800 W
DC distribution branch
Branch 1
10A(FUSE)
Branch 2
20A(FUSE)
Battery
20A(FUSE)
AC input range: 90-290 V AC
Safety EN 60950, UL 60950
Sub rack dimensions (H x W x D): 45.6 x 482.6 x 325mm
Business-Critical Continuity™
GIE4815/2A/1.7KW
Mini Power System
Key Features



2 U Height and designed for 19”racks
Integrated AC distribution, LVD and priority load
Remote monitoring and dry contacts
Key Benefits

Space efficient solution with all functions integrated
GIE4815/2A/1.7KW




Nominal system voltage: - 48 V
System rated output power @ - 54 V: 1700 W
Rectifier rated output power @ - 54 V: 850 W
DC distribution branch
Branch 1,2
Branch 3
Branch 4,5
Battery



5A(FUSE)
10A(FUSE)
20A(FUSE)
50A(MCB)
AC input range: 90-290 V AC
Safety EN 60950, UL 60950
Sub rack dimensions (H x W x D): 88 x 483 x 350mm
57
Embedded Power
GIE4815/3A/2.55KW
Mini Power System
Key Features



3 U Height and designed for 19”racks
Remote monitoring and dry contacts
Integrated AC distribution, surge protection, LVD and priority load
Key Benefits



Space effi cient solution with all functi ons integrated on one shelf
Robust and well proven design for tropical climates
Provides reliable DC supply
GIE4815/3A/2.55KW




Nominal system voltage: - 48 V
System rated output power @ - 54 V: 2550 W
Rectifier rated output power @ - 54 V: 850 W
DC distribution branch
Branch 1,
Branch 2,3



58
10A(MCB)
20A(MCB)
Branch 4,
50A(MCB)
Battery
63A(MCB)
AC input range: 90-290 V AC
Safety EN 60950, UL 60950
Sub rack dimensions (H x W x D): 133 x 465 x 360mm
Business-Critical Continuity™
GIE4820/3A/3.45KW
Mini Power System
Key Features



3 U Height and designed for 19”racks
Remote monitoring and dry contacts
Integrated AC distribution, surge protection, LVD and priority load
Key Benefits



Space efficient solution with all functions integrated on one shelf
Robust and well proven design for tropical climates
Provides reliable DC supply
GIE4820/3A/3.45KW




Nominal system voltage: - 48 V
System rated output power @ - 54 V: 3450 W
Rectifier rated output power @ - 54 V:1150 W
DC distribution branch
Branch 1,
Branch 2,3



10A(MCB)
20A(MCB)
Branch 4,
50A(MCB)
Battery
63A(MCB)
AC input range: 90-290 V AC
Safety EN 60950, UL 609 50
Sub rack dimensions (H x W x D): 133 x 465 x 360mm
59
Download