Practical Electrical Wiring Standards - AS 3000:2018 THIS BOOK WAS DEVELOPED BY IDC TECHNOLOGIES WHO ARE WE? IDC Technologies is internationally acknowledged as the premier provider of practical, technical training for engineers and technicians. We specialize in the fields of electrical systems, industrial data communications, telecommunications, automation and control, mechanical engineering, chemical and civil engineering, and are continually adding to our portfolio of over 60 different workshops. Our instructors are highly respected in their fields of expertise and in the last ten years have trained over 200,000 engineers, scientists and technicians. With offices conveniently located worldwide, IDC Technologies has an enthusiastic team of professional engineers, technicians and support staff who are committed to providing the highest level of training and consultancy. TECHNICAL WORKSHOPS TRAINING THAT WORKS We deliver engineering and technology training that will maximize your business goals. In today’s competitive environment, you require training that will help you and your organization to achieve its goals and produce a large return on investment. With our ‘training that works’ objective you and your organization will: • Get job-related skills that you need to achieve your business goals • Improve the operation and design of your equipment and plant • Improve your troubleshooting abilities • Sharpen your competitive edge • Boost morale and retain valuable staff • Save time and money EXPERT INSTRUCTORS We search the world for good quality instructors who have three outstanding attributes: 1. Expert knowledge and experience – of the course topic 2. Superb training abilities – to ensure the know-how is transferred effectively and quickly to you in a practical, hands-on way 3. Listening skills – they listen carefully to the needs of the participants and want to ensure that you benefit from the experience. Each and every instructor is evaluated by the delegates and we assess the presentation after every class to ensure that the instructor stays on track in presenting outstanding courses. HANDS-ON APPROACH TO TRAINING All IDC Technologies workshops include practical, hands-on sessions where the delegates are given the opportunity to apply in practice the theory they have learnt. REFERENCE MATERIALS A fully illustrated workshop book with hundreds of pages of tables, charts, figures and handy hints, plus considerable reference material is provided FREE of charge to each delegate. ACCREDITATION AND CONTINUING EDUCATION Satisfactory completion of all IDC workshops satisfies the requirements of the International Association for Continuing Education and Training for the award of 1.4 Continuing Education Units. IDC workshops also satisfy criteria for Continuing Professional Development according to the requirements of the Institution of Electrical Engineers and Institution of Measurement and Control in the UK, Institution of Engineers in Australia, Institution of Engineers New Zealand, and others. CERTIFICATE OF ATTENDANCE Each delegate receives a Certificate of Attendance documenting their experience. 100% MONEY BACK GUARANTEE IDC Technologies’ engineers have put considerable time and experience into ensuring that you gain maximum value from each workshop. If by lunchtime on the first day you decide that the workshop is not appropriate for your requirements, please let us know so that we can arrange a 100% refund of your fee. ONSITE WORKSHOPS All IDC Technologies Training Workshops are available on an on-site basis, presented at the venue of your choice, saving delegates travel time and expenses, thus providing your company with even greater savings. OFFICE LOCATIONS AUSTRALIA • CANADA • INDIA • IRELAND • MALAYSIA • NEW ZEALAND • POLAND • SINGAPORE • SOUTH AFRICA • UNITED KINGDOM • UNITED STATES idc@idc-online.com www.idc-online.com Visit our website for FREE Pocket Guides IDC Technologies produce a set of 6 Pocket Guides used by thousands of engineers and technicians worldwide. Vol. 1 – ELECTRONICS Vol. 4 – INSTRUMENTATION Vol. 2 – ELECTRICAL Vol. 5 – FORMULAE & CONVERSIONS Vol. 3 – COMMUNICATIONS Vol. 6 – INDUSTRIAL AUTOMATION To download a FREE copy of these internationally best selling pocket guides go to: www.idc-online.com/downloads/ On-Site Training SAVE MORE THAN 50% OFF the per person cost CUSTOMISE the training to YOUR WORKPLACE! Have the training delivered WHEN AND WHERE you need it! All IDC Technologies Training Workshops are available on an on-site basis, presented at the venue of your choice, saving delegates travel time and expenses, thus providing your company with even greater savings. For more information or a FREE detailed proposal contact Kevin Baker by e-mailing: training@idc-online.com IDC TECHNOLOGIES Worldwide Offices AUSTRALIA Telephone: 1300 138 522 • Facsimile: 1300 138 533 West Coast Office 1031 Wellington Street, West Perth, WA 6005 PO Box 1093, West Perth, WA 6872 East Coast Office PO Box 1750, North Sydney, NSW 2059 CANADA Toll Free Telephone: 1800 324 4244 • Toll Free Facsimile: 1800 434 4045 Suite 402, 814 Richards Street, Vancouver, NC V6B 3A7 INDIA Telephone : +91 444 208 9353 35 4th Street, Kumaran Colony, Vadapalani, Chennai 600026 IRELAND Telephone : +353 1 473 3190 • Facsimile: +353 1 473 3191 PO Box 8069, Shankill Co Dublin MALAYSIA Telephone: +60 3 5192 3800 • Facsimile: +60 3 5192 3801 26 Jalan Kota Raja E27/E, Hicom Town Center Seksyen 27, 40400 Shah Alam, Selangor NEW ZEALAND Telephone: +64 9 263 4759 • Facsimile: +64 9 262 2304 Parkview Towers, 28 Davies Avenue, Manukau City PO Box 76-142, Manukau City POLAND Telephone: +48 12 6304 746 • Facsimile: +48 12 6304 750 ul. Krakowska 50, 30-083 Balice, Krakow SINGAPORE Telephone: +65 6224 6298 • Facsimile: + 65 6224 7922 100 Eu Tong Sen Street, #04-11 Pearl’s Centre, Singapore 059812 SOUTH AFRICA Telephone: +27 87 751 4294 or +27 79 629 5706 • Facsimile: +27 11 312 2150 68 Pretorius Street, President Park, Midrand PO Box 389, Halfway House 1685 UNITED KINGDOM Telephone: +44 20 8335 4014 • Facsimile: +44 20 8335 4120 Suite 18, Fitzroy House, Lynwood Drive, Worcester Park, Surrey KT4 7AT UNITED STATES Toll Free Telephone: 1800 324 4244 • Toll Free Facsimile: 1800 434 4045 7101 Highway 71 West #200, Austin TX 78735 Website: www.idc-online.com Email: idc@idc-online.com Presents Practical Electrical Wiring Standards AS 3000:2018 Revision 7 Website: www.idc-online.com E-mail: idc@idc-online.com IDC Technologies Pty Ltd PO Box 1093, West Perth, Western Australia 6872 Offices in Australia, New Zealand, Singapore, United Kingdom, Ireland, Malaysia, Poland, United States of America, Canada, South Africa and India Copyright © IDC Technologies 2012. All rights reserved. First published 2008 All rights to this publication, associated software and workshop are reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted in any form or by any means electronic, mechanical, photocopying, recording or otherwise without the prior written permission of the publisher. All enquiries should be made to the publisher at the address above. Disclaimer Whilst all reasonable care has been taken to ensure that the descriptions, opinions, programs, listings, software and diagrams are accurate and workable, IDC Technologies do not accept any legal responsibility or liability to any person, organization or other entity for any direct loss, consequential loss or damage, however caused, that may be suffered as a result of the use of this publication or the associated workshop and software. In case of any uncertainty, we recommend that you contact IDC Technologies for clarification or assistance. Trademarks All logos and trademarks belong to, and are copyrighted to, their companies respectively. Acknowledgements IDC Technologies expresses its sincere thanks to all those engineers and technicians on our training workshops who freely made available their expertise in preparing this manual. Contents 1 Introduction to AS/NZS 3000:2018 1.1 1.2 1.3 1.4 1.5 1.6 1.7 2 3 4 5 Objectives of the course Need for rules and regulations Background and evolution of AS/NZS 3000 Scope of AS/NZS 3000 Wiring Rules General exceptions and exclusions Other related regulations and standards Summary 1 1 2 4 6 9 9 11 Electrical Distribution Systems 13 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 13 15 17 18 20 23 24 25 27 28 29 Evolution of electrical distribution systems Ac systems and dc systems Poly-phase ac circuits Vectorial representations Advantages of three phase systems Ac system connections HV and LV distribution systems Importance of earthing Importance of testing and verification Distribution systems in special locations Summary Design of Electrical Equipment and Safety 31 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 3.10 31 32 33 35 40 45 45 46 47 47 Objectives of safe design Preventing electric shocks Importance of insulation in electrical safety Importance of enclosures in ensuring safety Prevention of adverse thermal effects Isolation arrangements Earthing and interlocks Equipment selection Role of codes and standards in installation safety Summary Earthing of Electrical Systems 50 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 50 54 56 56 64 64 70 72 73 Unearthed and earthed systems Supply system (source) earthing or functional earthing Protective earthing Prevention of shock hazards Protective earth conductors Earthing practices in low voltage consumer installations Earth fault loop impedance Sensing of earth faults Summary Section 1 – Scope, Application and Fundamental Principles 75 5.1 Scope and application areas (clauses 1.1 and 1.2) 75 5.2 5.3 5.4 5.5 5.6 5.7 5.8 6 Section 2 – General Arrangement, Control and Protection 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.10 6.11 6.12 6.13 6.14 6.15 6.16 6.17 7 Definitions (clause 1.4) Protection for safety (clause 1.5) Design of an electrical installation (clause 1.6) Selection of electrical equipment (clause 1.7) Verification (inspection and testing) (clause 1.8) Compliance requirements (clause 1.9) Summary 76 81 84 84 86 86 87 90 Selection of switchgear and controlgear (clause 2.1) 90 Arrangement of electrical installation (clause 2.2) 91 Electrical equipment control requirements (clause 2.3) 93 Isolation 93 Main isolation switches (clause 2.3.3) 95 Other main switches (clause 2.3.4) 96 Emergency switching (clause 2.3.5) 96 Switches for maintenance (clause 2.3.6) 97 Functional (control) switching (clause 2.3.7) 97 Fault protection and protective devices (clauses 2.4 and 2.5) 98 Discrimination and coordination of protective devices 106 Simplified protective device selection (appendix C, C3) 108 Residual current devices for protection (clause 2.6) 110 Automatic disconnection time (appendix B) 112 Protection against voltage effects (clauses 2.7 and 2.8) 113 Switchboards (clause 2.9) 114 Summary 118 Section 3 – Selection and Installation of Wiring Systems 121 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 7.9 7.10 7.11 7.12 121 123 123 125 129 133 133 134 137 140 140 141 Types of wiring systems (clause 3.2) Selection criteria (clause 3.1) External influences (clause 3.3) Sizing of conductors Installation requirements of wiring systems Enclosure of cables (clause 3.10) Cables installed in conduits (appendix C, clause C6) Underground wiring systems (clause 3.11) Aerial wiring systems (clause 3.12) Cables supported by a catenary (clause 3.13) Earth sheath return systems (clause 3.16) Summary ii 8 9 10 Section 4 – Selection and Installation of Appliances and Accessories 143 8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 8.11 8.12 8.13 143 144 145 146 147 145 151 152 154 155 156 156 156 Section 5 – Earthing Arrangements and Earthing Conductors 159 9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 9.9 9.10 159 160 162 165 167 168 169 171 175 175 Requirements of earthing system (clauses 5.1 and 5.2) Multiple Earthed Neutral system (clause 5.3) Selection of earthing conductor (clauses 5.3.2-5.3.3) Earthing connections (clauses 5.3.4-5.3.6) Equipment earthing (clause 5.4) Earthing arrangements (clause 5.5) Equipotential bonding (clause 5.6) Earth fault loop impedance (clause 5.7 and appendix B) Earthing requirements for other systems (clause 5.8) Summary Section 6 – Damp Situations 177 10.1 10.2 177 10.3 10.4 10.5 10.6 10.7 10.8 11 Selection and installation criteria (clause 4.1) Protection against thermal effects (clause 4.2) Connection of electrical equipment (clause 4.3) Socket-outlets (clause 4.4) Lighting equipment and accessories (clause 4.5) Cooking appliances and heating systems Electricity converters (clause 4.12) Motors (clause 4.13) Transformers (clauses 4.14-4.16) Capacitors (clause 4.15) Airconditioning and heat pump systems Lifts Summary Basic requirements (clause 6.1) Locations of baths, showers or fixed water containers (clause 6.2) Swimming pools, paddling pools and spa pools/tubs (clause 6.3) Fountains and water features (clause 6.4) Locations containing sauna heaters (clause 6.5) Refrigeration rooms (clause 6.6) Sanitization and general hosing down areas (clause 6.7) Summary 178 185 189 191 193 193 194 Section 7 – Special Electrical Installations 196 11.1 11.2 11.3 11.4 11.5 11.6 11.7 11.8 11.9 196 197 200 203 206 207 208 210 210 Applicable areas (clause 7.1) Safety services (clause 7.2) Electricity generation systems (clause 7.3) Electrical separation (clause 7.4) Extra-low voltage electrical installations (clause 7.5) High voltage electrical installations (clause 7.6) Hazardous areas (clause 7.7) Other specific installations (clause 7.8) Supplies for electric vehicles (NZ only) iii 12 11.10 Summary 210 Section 8 – Verification 213 12.1 12.2 12.3 12.4 12.5 213 214 215 217 223 Basic objectives and requirements (clause 8.1) Safety precautions and testing devices Visual inspection (clause 8.2) Mandatory tests (clause 8.3) Summary Appendix 1 Determination of Maximum Demand for Electrical Installations 225 Appendix 2 Wiring Systems Classification 234 Appendix 3 IEC Classification of Supply Systems based on Earthing Practices 239 Appendix 4 Earthing Regulations and Practices from Other National Codes 247 Appendix 5 Practical Exercises 255 Appendix 6 Answers to Exercises 271 Appendix 7 Reducing the Impact of Power Supply Outages 286 Appendix 8 Electrical Conduits 289 Appendix 9 Installation of Arc Fault Detection Devices 292 Appendix 10 Guidance for Installation of Electrical Vehicle Socket – Outlets and Charging Stations 295 Appendix 11 Dc Circuit Protection Application Guide iv 298 1 Introduction to AS/NZS 3000:2018 The latest edition of AS/NZS 3000 Wiring Rules was published in the year 2018. This standard, approved by the council of standards in Australia and New Zealand, defines the regulations to be adopted in selection, design and installation of Electrical distribution systems mainly falling under low voltage category. In this chapter we will go through the history of this standard and the objectives with which this standard had been framed along with a review on the needs and benefits of such regulations. The chapter also includes an overview on the scope of this standard with brief introduction to the various topics covered in the standard and how they are organized in the latest publication before going into a more detailed discussion on each of the sections and their importance in the subsequent chapters. Learning objectives • • • • • • • • 1.1 Objectives of the course Need for regulations Background and evolution of AS/NZS 3000 Objectives of the AS/NZS 3000 regulations Scope of Wiring Rules General exclusions Other related standards and regulations Arrangement of AS/NZS 3000 Objectives of the course The objective of this course is to familiarize the participants with the Australian / New Zealand Wiring Rules (Fifth edition) published as Australia / New Zealand standard AS/NZS 3000: 2018. This standard covers the requirements to be adopted for electrical installations of nominal voltages up to and including 1000V ac and 1500V dc. It contains stipulations covering issues of safety, selection, installation testing and verification of electrical equipment in common areas as well as in special locations. The topics contained in the standard are of interest and relevance to all practitioners of electrical technology whether they are designers of electrical installations, erection engineers or personnel responsible for operation and maintenance of the installations. In order to appreciate the requirements and stipulations contained in the standard better, it is necessary to have a clear understanding of the fundamental principles that the standard aims to address. In preparing this manual an attempt has been made to give the reader an insight into the relevance of the stipulations of the standard by first touching upon the basics of the relevant aspects of electrical theory before going on to study the requirements contained in the standard. As such the chapters of this manual cover the following main objectives of this course. 2 Practical Electrical Wiring Standards - AS 3000:2018 • • • • • • Review the basic electrical theory related to selection of equipment and circuit connections in low voltage systems and the importance of the regulations defining the rules for safe use of electrical equipment and systems Review the important and basic safety aspects related to electrical systems covering insulation, enclosure, earthing, etc. Review the various sections and requirements of AS/NZS:3000: 2018 Areas of applications of these regulations in Electrical installation Understand the simple calculations for these systems related to conductor sizes, main and earthing conductor sizes, maximum demand, etc. to ensure safe design and reliable operation Review on the recommended checks and tests to be carried out in an electrical installation before energisation and also periodically to ensure its longevity. 1.2 • • • • • • • • • Need for rules and regulations Today the rules and regulations have become necessary to ensure that the people in the society get fair deal in every aspect of their daily life. These can range from the basic need for food to specific needs related to the travel, dresses, etc. With electricity becoming an important commodity in the modern society it is necessary to ensure that it is used in a safe and reliable manner. The electrical system today comprises of power generation limited to specific locations in a country but its transmission, distribution and consumption being extended to all the parts and remote corners, in an extensive and elaborate manner. Hence it is absolutely essential that the distribution systems and consumer equipments are designed and installed with features that would ensure safe consumption of electricity and also help regular maintenance, revamping, additions/ alterations, etc in a safe way. With due consideration for the same, regulations have been brought in to specify the kind of features essential for the safe use and also strictly enforced as rules to fulfill the following. To ensure uniform practices in the construction/ installation for enabling interchangeability for identical equipment when needed and also for avoiding interchangeability when not desired to meet the fundamental safety aspects. To ensure a stable source of supply and loads in the system for longevity in service of the equipment as well as for the electrical systems. To define the aspects that are to be considered in the design of the systems such as characteristics of available supply, nature of demand, emergency supplies for safety services, environmental considerations, conductors to be used, type of wiring, protective equipment, emergency control, isolation and switching, accessibility for operation etc in order achieve the earlier two. To ensure availability of correct and dependable electrical equipment to suit the voltage and frequency of the supply system followed in the country. To enable the designers in selecting correct and matching devices that shall be uniformly available in the market satisfying basic safety needs To make certain that the manufacturers, designers and installation contractors follow uniform regulations for the safety of people, properties and livestock coming in close contact with these systems in day to day life To support quality and reliability of installations and equipments for safe and continuous service. To ensure safety against shocks, and also against failures or damages due to thermal effects consequent to over current, fault current and over voltage. To aid equipment erection using good workmanship and proper materials, use of conductors with proper sizing and rating, proper jointing and connections at terminal points, installations in a manner not to cause temperatures in excess of the design temperatures and verification and testing of equipment periodically to avoid degradation. We will illustrate few of these major objectives further. 1.2.1 Ease of Interfacing Imagine for a moment, that there are no standards for electrical appliances. The result would be that each product manufacturer might choose a different voltage rating for his product. It would mean that we will have electrical heaters, ovens, toasters etc. each of different voltage, different plugs, Introduction to AS/NZS 3000:2018 3 etc that cannot work on a common electrical system but would require tailor made system to serve their purpose. Your power supply company might have a distribution voltage that is unsuitable for any or all of your gadgets. This obviously is not helpful and not desirable. Thus a standard has to be established and its adherence made mandatory within a national or geographical entity so that generation, transmission, distribution and utilization of electrical energy are done at stipulated voltages and frequency which will vary only within acceptable bands specified for each parameter. Such a standard enables the designer of an appliance to choose a suitable voltage and frequency at which the appliance can function and also the variations of these parameters which have to be taken care of in the design for the operational range of the appliance. It also allows the designer to select appropriate conductors and configuration of power supply connectors forming part of the appliance. In turn, this enables people to buy an off-the shelf appliance and connect it to the electrical outlet at home and use it without worrying too much about the suitability of the appliance for the electric supply provided by the power company. Anyone who has traveled with a device made in one country and tried to use in another where different standards prevail would certainly appreciate the convenience which uniform standards provide us with. Also the use of standards reduces the number of variant appliance designs a manufacturer has to plan and manufacture; an issue which will have adverse cost implications to the manufacturer and hence to the buyer. Low cost mass production is thus a direct result of standards benefitting millions across the globe. 1.2.2 Ensuring Quality of supply, equipment and installation Equipment and installations have to deliver functionalities for which they are designed without any undue hazards to the users or the environment for their entire design life under varying operating conditions. The provisions of a standard therefore define the parameters for functionality, safety and maintainability. They also contain stipulations that lay down the tests that the device has to withstand to either prove a design (by what are called Type tests conducted on prototypes or selected samples) or ensure that the output and quality parameters are met (by Routine Tests done on each piece manufactured). Thus when you buy an appliance or equipment that is declared as conforming to a particular standard, you have an assurance that it will perform under conditions defined by the standard, is safe to use and will deliver the output or functionalities which the manufacturer furnishes in accordance with the standard for the period it is expected to serve. An installation standard has a similar objective too. When an installation is carried out in accordance with a standard, it has to follow the methodologies stipulated in the standard using recommended accessories which, in turn will ensure that the installation achieves the intended quality minima, is safe for personnel and environment, and will have adequate provisions for maintainability. An installation standard also usually lays down the procedures for initial inspection and testing for certifying that the installation is fit to be put in service and the periodicity and detail of subsequent inspections and testing to ensure that it is fit to remain in service till the next scheduled inspection. 1.2.3 Ensuring safety The regulations also specify some of the finer aspects related to the practices to be adopted right from basic design, during selection, installation and also tests/ verifications to be carried out periodically so that the people and livestock in close proximity to these systems are protected against various hazards commonly prevailing in such systems. The following are some of the main regulations defined in the standards and are expected to be followed by the system designers so that safety becomes part of the design, selection and installation when the systems are put into use. • Regulations for protection against direct and indirect contacts that otherwise could lead to shocks 4 Practical Electrical Wiring Standards - AS 3000:2018 • Regulations for enclosure and equipment design features for protection against thermal effects, over current, fault current and over voltage that otherwise could lead to fire accidents or equipment failures. • Methods to be followed for selection of electrical equipment with guidelines for properly sizing the conductors, providing emergency services, safe isolation and switching, accessibility, etc • Erection methods to be followed to ensure minimum quality with consistent workmanship by use of proper materials, proper jointing and connections and methods to safeguard against high surface temperatures, etc • Regulations and mandatory procedures for inspection and testing of equipment by competent personnel to ensure that the installed equipments meet some basic characteristics desired in the regulations and also are having provisions for taking out the failed equipments from service without impacting the healthy equipments. 1.3 Background and evolution of AS/NZS 3000 This Standard was prepared by the Joint Standards Australia/Standards New Zealand Committee EL001, represented by the following agencies/ authorities. • Australian Building Codes Board • Australian Energy Council • Australian Industry Group • Communications, Electrical and Plumbing Union - Electrical Division • Consumer New Zealand • Consumers Federation of Australia • Electrical Contractors Association of New Zealand • Electrical Regulatory Authorities Council • Electrical Safety New Zealand • Electrical Workers Registration Board • ElectroComms & Energy Utilities Industries Skills Council • Energy Efficiency & Conservation Authority of New Zealand • Energy Networks Australia • Engineers Australia • Institute of Electrical Inspectors • Master Electricians Australia • National Electrical and Communications Association • National Electrical Switchboard Manufacturers Association • New Zealand Manufacturers and Exporters Association • NSW Department of Industry, Skills and Regional Development • Wellington Electrical Association • WorkSafe New Zealand The earlier 2000 edition superseded Australian standard AS 3000:1991, Electrical installations – Buildings, structures and premises (known as SAA Wiring Rules). In New Zealand the 2000 edition had superseded selected parts of NZS 3000:1997 Electrical installations – Buildings, structures and premises (known as the NZS Wiring Rules). The 2000 edition was further updated with Amendments No. 1 (September 2001), No. 2 (April 2002) and No. 3 (July 2003). The development of the 2018 edition of the standard had been based on the following considerations by the council of standards. a) new technology, new equipment and improved installation techniques; b) industry feedback regarding readability and compliance; c) identification and clarification of normative (mandatory) requirements and informative guidance material throughout the document; and d) experience gained in the application of the previous edition as expressed to Standards Australia and Standards New Zealand. Introduction to AS/NZS 3000:2018 5 During preparation of this Standard, reference was made to IEC 60364, Electrical installations of buildings (all parts) and acknowledgment is made of the assistance received from this source. The 2007 edition had been published on 12 November 2007 after being approved on behalf of the Council of Standards Australia on 19 October 2007 and on behalf of the Council of Standards New Zealand on 9 November 2007. This Standard was superseded by AS/NZS 3000: 2010 from its date of publication. The edition was improved with additional diagrammatic representation of concepts and by including more practical examples adopted in the user installations as desired by the industry. The edition is divided into two parts with Part 1 (Section-1) covering Scope, application and fundamental principles of safe electricity use and is generally made complete in itself without cross-referencing to Part 2. The edition also establishes the ‘deemed to comply’ status of AS/NZS 3018 relating to simple domestic applications. National requirements Certain provisions of the Standard have a different application in Australia and New Zealand. The following symbols appearing in the outer margin indicate that the identified Section or Clause is: (i) Applicable in Australia only. (ii) Applicable in New Zealand only. Informative appendices An informative appendix is for information or guidance only. Informative appendices provide additional information intended to assist in the understanding or use of the Standard. Deemed to comply The term ‘deemed to comply’ means that a requirement can be met by following a specified Standard or method. So, where an installation is carried out in accordance with the specified Standard or method, within the text of this Standard, the installation is ‘deemed to comply’ with the requirements of this Standard. Conformance to a deemed to comply Standard may exceed the minimum requirements of this Standard. Objectives of AS/NZS 3000 The main objective of regulations for electrical installations in any country is to provide the rules for the design and erection of electrical installations for safety and proper functioning. It is also necessary that when use of a new material or invention in an installation results in deviation from one or more stipulations already prevailing in the regulations, the degree of safety shall not get compromised by such deviation. The fact of such use shall also be recorded on the electrical installation certificate as reference for anyone who is concerned with the safe functioning of the installation. Keeping these basic objectives and to enable ease of understanding of the regulations, the AS/NZS 3000 Wiring rules standard is divided into two main parts – Part 1 and Part 2. This Standard comprises two parts, as set out below, with both parts bound as one document. Part 1 provides uniform essential elements that constitute the minimum regulatory requirements for a safe electrical installation. Part 1 also provides an alternative regulatory vehicle for Australian and New Zealand regulators seeking to move from the present prescription of AS/NZS 3000 in electrical installation safety and licensing legislation. Part 1 satisfies the following objectives: • To allow its content to be called up in regulation as a separate Part or together with Part 2. • To be generally complete in itself to avoid cross-referencing to Part 2. • To provide high level safety performance outcomes/conditions without prescriptive work methods that demonstrate means of compliance (which are in Part 2). 6 Practical Electrical Wiring Standards - AS 3000:2018 • To establish an enforcement link to Part 2. Failure to comply with a work method in Part 2 would breach the requirements of Part 1 unless an alternative method is used. • To establish the ‘deemed to comply’ status of Part 2, confirming that installations that comply with Part 2 comply with the requirements of Part 1. • To maintain alignment with IEC 60364, Low voltage electrical installations (series), developments at the level of essential safety. • To provide a mechanism for acceptance of alternative design and installation practices that are not addressed in, or are inconsistent with those given in the ‘deemed to comply’ Part 2. This mechanism is intended to apply where departures from the methods in Part 2 are significant rather than minor aspects that remain within the flexibility of Part 2. • To detail requirements for designers or installers seeking to apply an alternative method to the ‘deemed to comply’ methods contained in Part 2. Part 2 provides installation practices that are deemed to comply with the essential safety requirements of Part 1. Part 2 satisfies the following objectives: • To allow it to be called up in regulation, in addition to Part 1, to reflect a range of regulatory adoption options. • To incorporate and elaborate on all requirements of Part 1 with additional requirements and recommendations to clarify and support compliance. • To restore certain requirements, recommendations and examples of typical, effective compliant solutions from previous editions. • To emphasize common, practicable and cost-effective methods that achieve safety compliance, fitness for purpose and a level of good practice rather than overly conservative or obscure measures. • To make greater use of figures and examples to promote understanding of common or difficult aspects, e.g. line diagrams, alternative overcurrent device locations, ingress protection (IP) rating and switchboard access. 1.4 Scope of AS/NZS 3000 Wiring Rules This Standard sets out requirements for the design, construction and verification of electrical installations, including the selection and installation of electrical equipment forming part of such electrical installations. These requirements are intended to protect persons, livestock, and property from electric shock, fire and physical injury hazards that may arise from an electrical installation that is used with reasonable care and with due regard to the intended purpose of the electrical installation. In addition, guidance is provided so that the electrical installation will function correctly for the purpose intended and takes into account mitigating the foreseeable adverse effects of disruption to supply. Changes to AS/NZS 3000:2018 include the following: Section 1: 1. 2. 3. 4. 5. 6. 7. 8. New and revised definitions are indicated in Clause 1.4 by an asterisk (*) in the left margin. The definition of mains supply has been removed. ‘Direct contact’ and ‘indirect contact’ are now designated ‘basic protection’ and ‘fault protection’. IP ratings revised to suit local environmental conditions. Requirements for conductors with green/yellow insulation are specified. References to AS/NZS 3018 have been replaced with references to other Standards. Requirements for alterations and repairs have been clarified and expanded. New Part 1 solutions have been added along with details on where they may be used. Section 2: Introduction to AS/NZS 3000:2018 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Operating characteristics of switchgear, control gear and switchboards have been added. Origin requirements of sub-mains and final subcircuits have been added. Requirements for main switch operations have been added. Positions of overload protective devices have been clarified. Requirements for alternate positions of short circuit protective devices have been updated. Discrimination/selectivity of protective devices has been expanded. Protection requirements for switchboard internal arcing faults have been enhanced. Requirements for RCD protected circuits in domestic, non-domestic, non-residential and medical installations have been added, and RCD requirements for alterations and repairs clarified. Illustration of basic clearances for switchboard access has been updated. New clause on arc fault detection devices and their installation requirements has been added. Requirements for switchboard installations at 800 A or greater have been enhanced, including access and egress, switchroom door sizes and minimum clearances around switchboards in switchrooms. Further clarification has been provided regarding rising mains tee-offs. Section 3: 1. Improved installation safety requirements for cables that pass through bulk thermal insulation. 2. Colour identification of active, neutral and earth conductors further clarified. 3. Requirements for wiring systems installed in positions where they are likely to be disturbed have been clarified. 4. Requirements have been clarified for cables of different electrical installations in common enclosures and for segregation of cables. 5. Requirements for segregation of cables of different voltage levels have been clarified. Section 4: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. Revised figures identify where IP rated equipment is to be installed. The requirements for installation wiring connected via an installation coupler have been revised. Electric vehicle socket-outlet requirements now included. Requirements for lighting equipment and accessories have been revised. Requirements for the safe installation of recessed luminaires have been enhanced, and an updated list of luminaire classifications added. Requirements for cooking appliance switching devices clarified for improved safety outcomes. Gas appliances and equipment isolation requirements clarified. Further clarification of isolator requirements for airconditioning and heat pump systems. A new clause and figures have been added relating to electrical equipment installed in locations requiring protection from the weather. Installation and location requirements for socket-outlets for electric vehicle charging stations have been added. Clearance requirements for socket-outlets and switches from open gas or electric cooking appliances have been added. Requirements for isolating switches to be installed adjacent to all fixed wired water heaters have been added. Requirements on hazardous areas presented by gas relief vent terminals have been added. Requirements for airconditioners and heat pumps where the internal unit (or units) are supplied from a switchboard or circuit separate to that of the compressor, and new exceptions have been added. Requirements for lifts installed for general use and that are not emergency lifts (safety services) have been added. Section 5: 1. MEN system further defined for clarity. 7 8 Practical Electrical Wiring Standards - AS 3000:2018 2. 3. 4. 5. MEN connection requirements have been added regarding location in an accessible position. Acceptable earth electrodes types have been updated. Earthing requirements for SELV and PELV systems have been updated. Equipotential bonding requirements have been expanded and clarified through enhanced requirements for showers, bathrooms, pools and spas. 6. Earthing of conductive building materials in combined outbuildings. 7. Earthing requirements for individual outbuildings and combined outbuildings. 8. Earthing requirements for conductive switchboard enclosures associated with unprotected consumer mains. 9. Earthing of conductive reinforcing in combined outbuildings that contain showers or baths. 10. Conductive pool structures and the bonding connection point required to be installed and bonded to the installation earthing system regardless of other specified requirements. 11. Figure showing bonding arrangements for pools and spas has been added. 12. Requirements on conductive fixtures and fittings installed within arm’s reach of the pool edge, and that are in contact with the general mass of earth, either directly or indirectly, have been added. Section 6: 1. Additional content applying to water containers into which persons do not normally put a part or all of their body. 2. Installation requirements for deluge showers have been clarified. 3. Showers Zone 1 has been clarified for different shower head configurations. 4. Fixed water container size reduced from 45 L to 40 L. 5. A figure for showers with a hinged door has been included. 6. Specified capacity for spa pools or tubs has been increased from 500 L to 680 L. 7. Electricity generation systems, including inverters have been excluded from being installed in classified zones. 8. Clause excluding pools and spas from being located in areas containing electrical equipment owned by the electricity distributor, that result in such electrical equipment being incorporated into any classified zone. Section 7: 1. Clause 7.2, Safety services, has been restructured. 2. Installation requirements for electricity generation systems have been reviewed and clarified in line with applicable Standards. 3. Electric vehicle charging system requirements have been added. 4. Clause 7.8, Standards for specific electrical installations, has been revised. Section 8: 1. A number of clauses split into subclauses to differentiate between general, application, visual inspection, test requirements and accepted values. 2. Extra low voltage installation testing requirements have been relocated to Section 8 from Section 7. 3. Clarification of RCD testing and EFLI testing. 4. The date of initial energization is now required to be recorded at the installation switchboard. Appendices: 1. Appendix A—Now a single list of referenced Standards. 2. Appendix B—Table from FAQ34 (voltage drop and EFLI values comparison) added for further guidance. 3. Appendix C—Expanded and the information provided on maximum demand has been clarified and updated. Introduction to AS/NZS 3000:2018 9 4. Appendix D—Revised to provide more comprehensive guidance information for the construction of private aerial lines. 5. Appendix E—Updates incorporated and building classifications Class 1 and Class 10 have been added. 6. Appendix F—A recent update carried out by Committee EL-024 on protection against lightning. 7. Appendix K—Switchboard equipment summary has been added to provide a checklist of requirements for switchboards. 8. Appendix L—Appendix deleted. Formerly on first aid in Australia. 9. Appendix M—Formerly on first aid in New Zealand. This content was deleted and a new Appendix on reducing the impact of power supply outages has been added to provide guidance on continuity of supply and back up plans. 10. Appendix N—New Appendix to provide guidance on the types and variations of conduit available for electrical installations. 11. Appendix O—New Appendix to provide guidance on the installation of Arc Fault Detection Devices (AFDDs). 12. Appendix P—New Appendix to provide guidance for circuits intended to supply energy to electric vehicles. 13. Appendix Q—New Appendix to provide guidance for the selection of circuit protection and switching devices when being operated on a d.c.supply that would be deemed to meet the design, equipment selection and installation criteria of this Standard. 1.1 General exceptions and exclusions Italic print in the Code indicates exceptions or variations to requirements. Exceptions generally give specific examples where the requirements do not apply or where they are varied for certain applications. They may contain requirements. Examples are also presented in italic text. As applicable in any country, the wiring rules does NOT cover the requirements for design/manufacture of electrical equipment but limits itself to their selection and application in electrical installations. 1.2 Other related regulations and standards Appendix A of the standard provides detailed list of other regulations and standards that are referenced in the rules. Table 1.1 tries to identify some of the important standards that are to be additionally reviewed by the practitioners to ensure compliance with the stipulations in AS/NZS 3000. 10 Practical Electrical Wiring Standards - AS 3000:2018 Table 1.1 Partial list of standards/ regulations referred in AS/NZS 3000 Standard AS 2067 AS 60269 AS 60947 AS 60947.2 AS 60947.4.1 AS 60947.8 AS/NZS 2430 AS/NZS 3008 AS/NZS 3008.1.1 AS/NZS 3439 AS/NZS 3439.1 AS/NZS 3439.2 AS/NZS 3439.5 AS/NZS 3820 AS/NZS 5000 AS/NZS 5000.1 AS/NZS 5000.2 AS/NZS 61009 ABCA and NZBC Title Switchgear assemblies and ancillary equipment for alternating voltages above 1 kV Low-voltage fuses Low-voltage switchgear and controlgear Part 2: Circuit-breakers Part 4.1: Contactors and motor-starters—Electro mechanical contactors and motor-starters Part 8: Control units for built-in thermal protection (PTC) for rotating electrical machines Classification of hazardous areas Electrical installations—Selection of cables—Cables for alternating voltages up to and including 0.6/1 kV Part 1.1: Typical Australian installation conditions Low-voltage switchgear and controlgear assemblies Part 1: Type-tested and partially type-tested assemblies Part 2: Particular requirements for busbar trunking systems (busways) Part 5: Particular requirements for assemblies intended to be installed outdoors in public places—Cable distribution cabinets (CDCs) for power distribution in networks Essential safety requirements for low voltage electrical equipment Electric cables—Polymeric insulated Part 1: Electric Polymeric insulated cables for working voltages up to and including 0.6/1 (1.2) kV Part 2: Electric Polymeric insulated cables for working voltages up to and including 450/750 V Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs) Building Code of Australia (ABCA) and the New Zealand Building Code (NZBC) A number of other standards covering fire protection systems, storage battery systems, hoists, elevators, etc are also listed for further reference and guidance, which are not covered in this table. Introduction to AS/NZS 3000:2018 11 Summary The regulations are needed to ensure uniform practices adopted in all equipment and installation practices for safety and reliability of the installations. AS/NZS 3000 standard covers regulations to be followed for design, selection and installation of LV electrical systems of common and special premises in Australia and New Zealand. The 2018 year edition had been updated with many illustrations and worked out examples compared to the earlier edition based on the feedback from industry and the end users. The standard is divided into two parts. Part-1 of the standard provides basic compliance requirements to be met in the design, selection and installation of the systems with an objective to achieve high level of safety in the systems without referencing part-2. The second part is divided into a number of sections and outlines guidelines and procedures to be adopted by the designers and installation contractors for achieving the high level safety objectives of part-1 in specific application areas. This book is not intended to replace the AS/NZS Wiring Rules as a work of reference but is merely an introduction to it. As all of us are aware, the standards are dynamic in nature in the manner that they continuously undergo amendments and revisions to match the pace of the growth in the technology. In case further information is required it is recommended that the participants shall directly refer the standard as well as other references such as the reference documents identified in appendix A of the standard. A lot of published literature is available on these topics by industry bodies and reputed manufacturers of electrical equipment as well as on the Internet and can be referred for assistance in solving specific problems one may come across. 12 Practical Electrical Wiring Standards - AS 3000:2018 2 Electrical Distribution Systems Electrical distribution is a specialized subject and in this chapter we will see how the electrical distribution systems evolved over the last two centuries with power demand running into millions of watts. A review will be made on the features of ac and dc systems and also the importance of poly-phase distribution. We will spend some time in understanding why three phase ac system is the preferred choice for generation, transmission and distribution. We will also cover the vectorial representation followed for defining ac parameters and the methods of connections employed in three phase ac installations. A review will also be made on the importance of earthing and testing/ verifications on these systems. Learning objectives • • • • • • • • • • 2.1 Evolution of electrical distribution systems Ac systems and dc systems Polyphase ac circuits Vectorial representations Advantages of three phase systems Ac system connections HV and LV distributions systems Importance of Earthing Importance of Testing and verification Distribution systems in special locations Evolution of electrical distribution systems When Michael Faraday invented the first electricity generator, he could have hardly imagined that an entire new technology will follow his invention and electricity would become an integral part of our daily life. Today, it is difficult to carry on with most of our routine activities without electricity being available. This has naturally given rise to an extensive electrical network in all parts of the globe for generation and distribution of electric power. In its most simple form, an electrical circuit (figure 2.1) consists of: • A source • A load • Conductors that carry the load current from the source to the load 14 Practical Electrical Wiring Standards - AS 3000:2018 Conductors S Source Figure 2.1 A Simple Electrical Circuit The source could be a primary or secondary battery, a generator driven by a prime mover or a photovoltaic cell. The load is an energy consuming device which converts electricity into some other form of energy. It can be a motor which converts electrical to motive energy, a lamp which converts electricity into light energy, a heating element converting electricity into heat or a chemical reactor such as an electrolytic cell. Conductors are materials which carry the electrical current from the source to the load and back thus completing the electrical circuit and are made of materials such as copper or aluminium. Though most metals conduct electricity to some extent their electrical resistance is much higher than the above two materials. This simple circuit is not a very practical system and needs other devices to work properly. Rarely a source feeds just a single load. Also the loads need to be connected and disconnected as and when required. So we now have an improved version of the basic circuit (Figure 2.2). Figure 2.2 An Improved Version of Electrical Circuit The source needs to be isolated from the distribution system too. And also the distribution system needs to have a single point control. With these facilities added, the system now looks like the one in figure 2.3, which can be assumed to almost represent a system connected by a single source. Electrical Distribution Systems 15 Figure 2.3 A More Practical Version of the Basic Circuit Today, the electrical systems in any country comprise of hundreds of large power sources and millions of consumer and industry loads separated by long distances with most of their feeding substations interconnected with more than one source to ensure that a load connected from the substation can have continuity of power supply. For this purpose all the substations are interconnected with provisions either to feed another substation or to receive power from another substation incorporating interlocks and changeover provisions, as needed. All these requirements add a lot of complexity to the distribution systems, which is outside the purview of this manual. However we can conclude that a simple system shown in figure 2.3 is no longer adequate and we have distribution systems that comprise of multiple voltage levels and multiple types of energy sources to meet the ever growing power needs. 2.2 AC systems and DC systems The systems we saw above show the loads being directly connected to the source. In other words, the source and loads operate (nearly) at the same voltage. When the quantity of power to be handled increases, the conductors which carry this power have to operate at higher and higher currents (as per the formula Power = Voltage × Current assuming a pure resistance to be the load) the voltage being a constant value decided by the consuming appliances. Electrical power that is used in everyday life is broadly divided into two main categories viz., ac (Alternating Current) power and dc (Direct Current) power. In the case of dc power, the electrons flow in one direction only. In the case of ac power, the electrons oscillate back and forth at a defined frequency. Edison's inventions, from the light bulb to the electric fan, were based on dc electricity. Though dc can be generated using dc machines with rotating armature and stationary field windings, the capacity is limited because of the need for a commutator/brush gear within the machine. Further, transmission of dc power over long distances cannot be as easily achieved as ac power. In today’s world dc power is mostly derived from stationary batteries of Lead acid type, Nickel Cadmium type, etc and naturally the sizes of these dc sources become unmanageable for high power applications. Hence the use of dc power is limited to standby power/ emergency generator starting applications with a reasonably large sizes of dc sources. Small gadgets like mobile phones, cameras, etc. use smaller dc sources. Another factor to be considered is the efficiency of transmission. Any electrical conductor has a critical value of current beyond which the power loss in the conductor (computed by the formula P = I × I × R, I being the current and R the resistance of the conductor) will cause the conductor to attain excessive temperatures. The equilibrium temperature that the conductor attains is decided by the following factors. 16 Practical Electrical Wiring Standards - AS 3000:2018 • • • Power loss I2R converted to heat. (It is worth noting that the resistance of the conductor material is not constant but will increase with temperature according to the temperature coefficient of resistance for the material). Heat dissipation from the conductor to the environment through conduction, convection and radiation decided by the conductor geometry. In the case of insulated conductors and cables, the heat dissipation will have to be done through the layers of insulation. Capacity of the conductor to store the heat (decided by the specific heat of the material and the mass of the conductor). The temperature attained by the conductor is limited by the value which, the insulating material used to insulate the conductor can tolerate without suffering failure of insulation (or in the case of bare conductors to support it). An insulating material has a negative coefficient of resistance and beyond a critical temperature the insulation can become conductive. It may also lose mechanical strength in the process of heating up. The resulting short circuit faults would cause much higher currents. In extreme cases, the conductor itself can attain temperatures close to its melting point and melt away. The ways to prevent excessive conductor heating is to increase the conductor size and put a number of conductors in parallel. This again has physical limits beyond which the conductor capacity cannot be increased. Alternatively, the system voltage can be increased so that the current value for a given quantum of power transmitted will reduce in inverse proportion. This will necessitate use of thicker insulation in the appliances to withstand the higher voltages, which in turn will make the appliances more expensive. Also there are practical limits beyond which voltage cannot be increased without compromising economy and safety. The ideal solution is therefore to use a mix of voltages so that transmission, distribution and consumption each adopts an optimum voltage value decided by economic considerations appropriate to the application. AC systems give us an easy way to get these mixed voltages using a transformer, which can either step up or step down the voltage as required. Transformers step up the voltage for transmission of power over long distances and near the loads, the voltage is stepped down again to a value convenient for consuming appliances. Generators are capable of generating various waveforms but the requirement to be able to transform voltage magnitudes leads to the choice of a sinusoidal wave. This is the only waveform which will transform into another sinusoid. The sinusoidal primary current produces a sinusoidal magnetic field within the transformer which induces an emf in the secondary which is proportional to the rate of change of the magnetic field (i.e. the differential). The differential of a sine wave is another sine wave - just shifted by 90 degrees. Within a short span time since the invention of electricity, the advantages of ac power became apparent. Ac power requires simpler and robust generator design and is also very easy to transmit over long distances. Although dc power continues to be used in equipment, it is invariably obtained by conversion of ac power could be readily converted to run dc appliances—which is another advantage offered by the ac power. Since transmission of power is more economical at higher voltages, ac power transmission and distribution systems deploying transformers have become the norm in power industry. Transformers are also very useful as components within equipment where they are utilized to derive lower voltages to suit the application requirements. In modern power systems, transmission of power at high dc voltages has been found to possess specific advantages and is being used increasingly in specific segments. But this is more of an exception than the norm and is yet to attain the pre-eminent position of ac systems in the power industry. The discussion of the same is beyond the scope of this manual. Ac systems have thus become a standard all over the world for electrical generation and distribution systems. Figure 2.4 illustrates the simplified basic configuration of an ac system. In Electrical Distribution Systems 17 most cases, transmission as well as distribution is done at more than one voltage to make the system more efficient (in other words, reducing the power loss in the conductors). This is done depending on the quantum of power transferred and the distances over which it is done Figure 2.4 A simplified configuration of ac system 2.3 Poly-phase AC circuits As you would have noticed, the circuits that are shown in the earlier paragraphs have two conductors, one going to the load and one returning from the load. This is called a single phase ac system. A single-phase supply is suited to certain types of loads such as Lighting and heating. But when it comes to rotary electro-dynamic equipment, such as a motor, it has some disadvantages. This prompted the use of a different type of a system where more than two conductors are used. A D C N E S Note N and S are the poles of the rotor magnetic System A and B are terminals on the stator winding One pole pitch apart C is the mid-point of the winding D and E divide the winding into three Equal parts Figure 2.5 Theory of Poly-phase generator B 18 Practical Electrical Wiring Standards - AS 3000:2018 A simple generator consists of a stator winding, a rotor and a field winding. Figure 2.5 shows the winding (on the stator or the fixed portion) of a simple electrical generator and two adjacent poles on the rotor (rotating part) of the generator. Please take note of the location points A, B, C, D and E in the windings which are referred in the following section to indicate the voltage generated. The first ac generators with a single set of windings and a rotating magnet generated single-phase voltage. Generators with spatially displaced windings generating poly-phase ac voltage were a later development. A single-phase power system results in higher current for transferring a given amount of energy, which increases the size of generators and also the conductors required to carry the current over long distances. The advantages of three-phase power and the economy achieved in generation and transmission of electricity were then evident and it became the norm for all ac electrical systems. Ac power consumed today is divided into single phase and three-phase power, though generation is with three phases. Though single phase power is used today both in industries and commercial/residential applications, their usage is limited to final distribution circuits for low capacity devices such as lighting, small pumps, small capacity air conditioners, computers, etc. Again, this single-phase power is actually derived out of the three phase system and does not require any special equipment / devices for separation of three phase power to single phase, when needed. 2.4 Vectorial Representations The ac generator in a power plant is coupled to a prime mover, which is made to rotate (move) by its primary energy source, which can be a liquid fuel, gas, water (in hydroelectric power stations) etc. The prime mover drives the rotor of the generator at the required speed. This in turn produces an alternating voltage at the generator’s three output terminals in sinusoidal form, which is the most commonly followed system for generation and transmission. The waveform in one of the phases will be as shown in figure 2.6, with time on X-axis and the voltage value on the Y-axis. The arrow lines by the side of the waveform basically indicate its angular position at that particular time and the instantaneous value of the wave form is given by the vertical line length from the arrow end. Figure 2.6 AC sinusoidal voltage and vector representation The above variation in the magnitude and the relative angle from 0 to 3600 is termed as one cycle and the voltage in one phase is represented by a vector line, which makes 3600 rotation for one full cycle. AC generators produce this kind of sinusoidal voltages at 50 or 60 cycles per second (known as the frequency of the electrical source and expressed in cycles/second or Hertz) in its three phases with B phase lagging A phase by 1200 and leading phase C by 1200. Though the arrows in the figure 2.6 are shown as moving in clockwise direction (from 0 to peak), it is generally a practice to show the vector traveling in anti clock direction. These three phases A, B and C are represented as three rotating vectors as shown in figure 2.7. Electrical Distribution Systems 19 Figure 2.7 Regular anticlockwise phase voltage rotation Referring to the single phase generator shown in the earlier figure 2.5, the voltage generated across A and B is the resultant of the voltages in each turn whose phasors lie along the semicircle with diameter AB and can be vectorially shown as in figure 2.8. Figure 2.8 Voltage phasors and relationship of a generator The generator is provided with three independent windings in such a way as to produce the voltages in the above fashion. The windings at one end are brought to terminals A, B and C (this is different from A, B, C identified in figure 2.5) and the other ends are interconnected to form the neutral end of the generator. Though the windings can also be connected in Delta form, it is not followed in generators. It is also an established practice to connect the neutral terminal to the ground through a resistance called Neutral Grounding Resistor (NGR) to limit the fault currents in 20 Practical Electrical Wiring Standards - AS 3000:2018 the generator during earth fault. Further, it is to be noted that when multiple generators are connected to supply a common bus, the phase angles of voltages at terminals A, B and C of all generators shall be exactly same as otherwise it would lead to severe short circuit conditions. The other major parameter to be matched is the magnitude of the voltage of parallel-operated generators at these terminals, which shall be almost equal (V A , V B , V C in figure 2.9). The three-phase system is adopted for use in electrical systems all over the world. Even when single-phase loads are to be fed they are essentially fed from taking the supply from any one phase of the three-phase system. The three-phase systems are represented by phasors and waveforms as shown in figure 2.9. Figure 2.9 Voltage Phasors and Wave Forms in a 3-Phase System 2.5 Advantages of three phase systems One of the main advantages of a three-phase system is the simplicity of motors designed to run on it. This requires an understanding on the basic principle of single phase motor and three phase motor. A single phase motor can be electrically represented by the figure 2.10. The winding is in fact a fixed coil energized with an ac voltage. Electrical Distribution Systems 21 Figure 2.10 Single Phase Motor The input voltage produces a magnetic field which is alternating too as represented by the wave form in figure 2.11. The intensity of the magnetic field varies in magnitude and direction along the axis of the coil. When a rotor is placed in such a field, it does not experience any torque. Thus a single phase ac motor is not self starting. Of course, one can use commutators and split windings to make the motor self-starting but these arrangements introduce complexities in the system. Figure 2.11 Single Phase Motor-Magnetic Field Waveform On the other hand, a three phase motor can be represented by three coils 120 degree apart each energized by one phase of the supply system which are also 120 degree apart electrically. It can be shown that this arrangement produces a magnetic field which is of constant magnitude and rotates in the physical space at a speed decided by the supply system frequency and the number of virtual poles in the winding. A magnetic rotor placed in the system will lock into the rotating field and rotate with it. This makes a three phase motor self-starting without adding any complexities. 22 Practical Electrical Wiring Standards - AS 3000:2018 A three phase system thus has the following advantages: • For a given size of a motor power output is higher than a single phase system. • Similarly, when a given amount of power is transmitted by a three system at a given voltage over a given distance, the least amount conductor material is used for achieving the same efficiency. • Single phase motors are not self starting but three phase motors are. Also three phase motors produce uniform torque which is ideal for the loads being run from such a system. • It is difficult to operate single phase alternators in parallel since the synchronizing torque is much lower. Today’s power plants invariably generate three-phase ac power at hundreds and thousands of Megawatts. The box below shows a comparison of power handled for single phase, two-phase, 3phase and m-phase systems. It can be seen that the power output of a two phase system is 41.4% higher than that of the single phase system and for the three phase system it is 50% higher than the single phase system. Beyond this, the increase obtained by increasing the no. of phases to higher values becomes marginal. Even for an infinite number of phases, the additional output is only 7% higher than the 3-phase system. Electrical Distribution Systems 23 A generator thus works at a power output near the theoretical maximum value when it feeds a three-phase system. 2.6 AC system connections Two types of connections are possible in a three-phase system as illustrated in figure 2.12. This is applicable both for a source and a load. Possible combinations of source and load are shown in figure 2.13 (a 1 –a 2 , b 1 –b 2 and c 1 –c 2 are the end of the windings of each phase interconnected among them to form Star or Delta connection as shown in the figures). Fig. 2.12 Star and Delta Configurations Most systems use the star connection at the source, which gives them a flexibility to feed both three phase and single-phase loads. This is a de-facto distribution system standard in most parts of the world for low voltage distribution systems and unless otherwise stated, will be the one that will figure in our discussions further. A 3-phase 4-wire system is necessary when single-phase loads (loads across one phase and neutral) are supplied by the system. In this case the neutral of the source and the load will have to be connected by a neutral conductor. When the current drawn from each of the phases have equal magnitude and same phase angle, the system is said to have a balanced load. In a balanced 3-phase 4-wire system the neutral current is zero. In case only three phase equipment such as motors are fed from the system, then the neutral conductor can be dispensed with. In such case, the system becomes a 3-phase 3-wire system. A source may feed a combination of loads requiring a 3-wire system and 4-wire system. 24 Practical Electrical Wiring Standards - AS 3000:2018 Figure 2.13 Three Phase System Connections 2.7 HV and LV distribution systems Any electrical system intended to serve many consumers, whether in a plant or a township or a country, primarily consists of equipment with different voltage ratings mostly based on economic considerations. This is mainly made possible by the use of transformers, which are the backbones of efficient electrical distribution at minimum losses. The use of equipment at different voltage levels have led to the need for demarcation of type of equipment based on their normal operating voltage, which is termed as Nominal operating voltage of the equipment. The main reason for demarcation is to limit the cost of equipment to be used at a Electrical Distribution Systems 25 particular voltage and the current to be transmitted over the conductors. The ac operating voltages are broadly divided to three main categories Viz., • Low Voltage (LV) referring to voltages up to 1kV but generally the operating voltage seldom is expected to be between 500 to 1000V under this category. • High Voltage (HV) referring to all voltages above 1000V. However per ANSI standards, voltages above 69kV are termed as HV. It is also a general practice to refer this range (>69kV) as Extra High Voltage (EHV) in Europe and Asian countries, though EHV term is not commonly adopted in all countries including Australia. • Medium Voltage (MV) is another term referring to equipment above 1kV up to and including 69kV as per ANSI. In some parts of the world, MV is generally termed up to 3.3kV, beyond which the term HV is applied. In Australia ac voltages up to 1000V and dc voltages upto 1500V come under low voltage category. AS/NZS-3000 primarily specifies rules for the installations that are connected at these specific voltages. The low voltage distribution is the most common system and almost everyone is in contact in day to day life on these low voltage systems and equipments ranging from simple lighting system under which you may be reading this chapter to different types of switches and switchboards controlling such systems. The LV systems are mainly intended for small power loads whose ratings may range from fractional to a few hundreds of HP. 2.8 Importance of earthing Earthing is one of the important considerations in safety of electrical installations and in this chapter we will try to have brief fundamental principles on the concept of earthing and a separate chapter provides more details and requirements on the same. The earliest electrical distributions systems were unearthed ones with no connection to earth at all. Even though such systems still exist in specific areas, they are the exceptions rather than the rule. By and large some form of earthing is adopted for all power systems, as they provide some important functions for safety and reliability of system. We review below the reasons for earthing. We know that the insulating layer around the current carrying conductors in electrical systems is prone to deterioration. When a failure of insulation takes place due to aging and/or external factors such as electrical, mechanical or thermal stresses, it is necessary to detect the point of failure so that repairs can be undertaken. In a system that has no earth reference, it is not at all easy to correctly pinpoint the faulted location. Refer to Figure 2.14, which shows such a system. It can be seen that due to the absence of a conducting path through earth, there will be no current flow for a protective device to sense and isolate the faulty circuit. However if a second fault occurs in the unaffected lines at some other point in the system it can cause a shorting path to be made available resulting in the flow of high magnitude fault currents that can be detected by protective devices. Fig 2.14 Fault in Unearthed System 26 Practical Electrical Wiring Standards - AS 3000:2018 To detect and isolate the first faulted circuit as soon as the fault develops without waiting for a second fault to happen, we need to connect one of the two poles of the source S to the earth as shown in figure 2.15. In three phase electrical system, it is the center point of the star connected winding that is usually earthed. It would be of interest to note that the connection of the system to the earth in figure 2.15 is only at the source. The return current from the load flows through the neutral conductor back to the source. For this reason, the neutral needs to be always insulated usually to the same degree as the line conductor. When there is an insulation failure in the line conductor, high current flows through the electrical circuits and through the earth path back to the source. The magnitude of this current depends on the resistance of the earth path (called the earth loop resistance). The current flow in this path can be detected by appropriate protective equipment. Figure 2.15 Effect of Earthing the System Thus one of the primary purposes of earthing the source is to permit easy detection of faults in electrical systems by providing a path for the flow of currents from the fault point through the earth (and sometimes the earth mass) back to the source. This earthing is referred as functional earthing in AS/NZS 3000. Now let us take a step further and see as to why a separate earth reference is necessary at the consumer point or the load side equipment. While Figure 2.15 shows that the source is earthed, it does not indicate another point of connection to earth. However, in practical systems, the fact that a failure of insulation takes place does not mean that a earth connection is automatically established. This can only be done if the point of failure is connected to earth using low resistance earth path. Such a path is created using a reference earth bus at the consumer end and connecting the metallic housing of all electrical equipment to this bus (Refer Figure 2.16). Figure 2.16 Fault Current Flow in an earthed System Electrical Distribution Systems 27 It should be noted that the neutral of the electrical load is isolated from the earth and the connection between neutral and earth is still at the source point only. Thus the earth reference at the consumer or load end fulfils the primary function of providing a metallic return path to allow for earth fault current to flow with a minimum of earth loop impedance. This allows the earth fault currents to attain sufficient magnitudes that can be detected easily without resorting to any special sensitive protective equipment. Hence it can be concluded that earthing primarily serves the following purposes with respect to the connected systems and the source. • It ensures the contact surfaces of the electrical systems are at or near zero potential to guarantee basic safety under normal conditions (Protective earthing) • To permit easy detection of faults using it as a path for the flow of currents from the fault point through the earth back to the source for disconnection of source to avoid catastrophic accidents As we have seen earlier there are different types of connections possible at the source and the load ends. The earthing methods are suitably chosen matching the system connections to detect faults and to minimize fault currents. The different types of earthing and the earthing practices adopted/ recommended will be discussed in detail later. It is essential to have a clear understanding on the following important definitions related to earthing, as we proceed further. • Earth: The conductive mass of the Earth whose electric potential at any point is conventionally taken as zero. • Protective Earthing: Connection of exposed conductive parts of an installation to the earth through earthing terminals. • Functional Earthing: Earth connection for proper functioning of equipment like suppression of noise signals in instrumentation circuits and not for enabling safety. • Earthing Terminal: The terminal or bar provided for the connection of protective conductors and functional earthing conductors to the earth. 2.9 Importance of testing and verification The continuity of power distribution depends on the reliability of the electrical equipment in a system. While the reliability of many equipment have increased manifold during the last century, it is not recommended to connect any finished equipment to a system directly from the manufacturing place, unless its performance is proven. The manufacturers in the initial days had to think of many ways to prove the worthiness and reliability of their equipment. Nevertheless due to various reasons, manufacturers duplicating proven equipment also gained entry into the market. This had led to claims and counterclaims by the sellers with the consumers and end users getting confused. However the concepts have changed and bringing equipment under common umbrella to prove their performance have slowly become the practice in every country. Each country had established committees and organizations to ensure the uniformity and performance of electrical equipment in an orderly way. This had led to the release of electrical standard in each country for all the electrical equipment. The major content of most of these cover the minimum tests that are to be conducted on an equipment in an environment, which may be severe than normal the operating conditions, in terms of their voltage and current levels. With the sharing of knowledge among the intellectuals from different regions and with the globalization leading to use of electrical equipment from different parts of the world, a common way to establish the capability of equipment had been accepted leading to mandatory testing of electrical equipment before being put into use. The tests and the methods to be followed are covered in all Electrical standards. It can be concluded that testing electrical equipments is necessary • To prove the performance of an equipment before being put into service • To ensure that the equipment are assessed on a common basis with respect to their technical capabilities 28 Practical Electrical Wiring Standards - AS 3000:2018 • • To give confidence to the end user about the capability and performance of the equipment where it is to be used. To establish an assurance showing that the distribution system as well as the equipment will not cause any damage to the property and personnel, when they are put into service. It is to be noted that most of the tests are carried out in a manufacturer’s works under some specific conditions. However when the equipment is connected to a system it is not possible to assume that the system conditions will be matching the equipment requirements. Hence it is vital that a complete testing and verification of the distribution system is carried out by authorized personnel in a step by step method to verify that the system complies with all the established standards. The quality of an electrical installation and ensuring safety of personnel who operate and maintain the installation are important issues. Carrying out the design and construction of an installation as per applicable standards, regulations and codes of practice is crucial in ensuring the quality, safety and integrity of the installation, since standards and codes put must emphasis on matters pertaining to safety. An installation must be inspected for conformity with the applicable regulations and for safety on completion of erection and thereafter periodically. AS/NZS Wiring rules stipulate various requirements to achieve these objectives. Planning, design and erection of an electrical system need extreme care in order to ensure that the installations are safe for the personnel who use, operate and maintain them. Proper planning using the methods of systematic assessment given in Section 8 of the Wiring Rules will ensure that the installations function as intended and are not unduly affected by the presence of external influences. Proper design of the system and selection of equipment, which form part of the installation, ensure that the system is safe and remains safe over its entire intended life. Proper erection ensures that the equipment operates and meets the functional requirements as intended. Inspection verifies the compliance with regulations and safety requirements. AS/NZS 3000 standard specifies the verifications to be adopted in an installation and it is also mandatory that the system is not energized unless the verifications are completed and certified by licensed personnel. This ensures that the system will be safe to be put into service thereby serving the objectives of the standard. It is also necessary that periodical inspection and verification is carried out on the systems. This is because of the ageing factors of the systems and also due to environmental conditions like temperature, dust, etc affecting the performance of the equipment resulting in systems deterioration over a period of time. Periodical verifications ensure identifying defective parts for rectifications and replacements, as required. It is also helpful for adding new loads and/or doing alterations in the systems as a part of refurbishment and new technological innovations. Hence it can be concluded that the inspection serves the following objectives. • To ensure that a new installation is safe to energize, operate and maintain • To ensure that the installation remains safe during its operation without deterioration • To ensure that additions/modifications to an existing installation do not impair its safety. 2.10 Distribution systems in special locations Special locations may be classified as those that require additional precautions to ensure proper operation of the equipment and safety for the persons coming or working close to such locations. These are also locations that require special attention for maintaining continuous power supply to large areas. AS/NZS 3000 requirements cover additional precautions needed for design, selection and installation of distribution systems in such special installations. Some of the special installations covered by the standard are given below: • Electrical systems for safety services (emergency supply systems) • Electricity generating stations Electrical Distribution Systems 29 • • • Locations storing explosive substances or process areas that generate explosive gases so the operation of electrical equipment can lead to arcing, fire and explosions unless special precautions are taken. Systems operating at high voltages Construction/ demolition sites, shows/ carnivals, outdoor sites under heavy conditions, etc. In locations like bathrooms and swimming pools the system insulation can be affected by moisture and water entering the electrical equipment and wiring systems. These locations also demand special attention to maintain safety and reliability. The requirements to be complied in these installations are covered in a separate section of the standard. We will discuss the specific guidelines needed in the electrical distribution systems in all such special installations in subsequent chapters. 2.11 Summary Over the years the electrical systems evolved with incorporation of isolation switches at source and load ends for better control and reliability of the ever growing systems with many interconnections added to improve reliability and continuity of power supply at consumer ends. Though dc and single phase systems were the beginning of electrical distribution, the power distribution moved to three phase ac systems in today’s world due to specific advantages related to these systems. The major advantages with three phase systems are the reduction in transmission and distribution losses compared to single phase systems including other economical advantages like easy and efficient voltage transformation, optimum conductor sizing, etc. The ac system parameters that vary in magnitude with time can be represented by straight line vectors. The angular positions of respective vectors show the relative phase shift between different voltages and currents at any instant. The three phase ac systems are connected in the form of star or delta to meet specific distribution needs with star + neutral combination being commonly adopted in low voltage systems to enable single phase distribution at still lower voltages AS/NZS 3000 primarily covers the LV distribution systems adopted in almost all installations to distribute power supply to lighting, sockets, fans, etc. Earthing is an important requirement to detect faults in electrical distribution systems. Protective earthing of equipment maintains safety for personnel coming close to or in contact with surfaces enclosing live conductors by ensuring all contact surfaces are at zero potential. Testing of the equipment at manufacturers’ works and again at field prior to energisation is necessary to ensure that the equipments meet the specific purposes and operating conditions for which they are designed and manufactured. Verification and testing of an installation before putting into service is a mandatory requirement as per AS/NZS 3000 and the specific guidelines will be reviewed in a subsequent chapter. 30 Practical Electrical Wiring Standards - AS 3000:2018 3 Design of Electrical Equipment and Safety The safety of an electrical system depends on its application from the design stage onwards. AS/NZS: 3000 Wiring rules covers the safety requirements for design, selection, installation of electrical equipments and distribution systems in detail. In this chapter we will understand the common electrical hazards and the importance of safe design to overcome these hazards. Since insulation and enclosures play major roles in providing safety, we will review the salient requirements and classification methods of these two features in electrical designs. A brief presentation on the prevention methods followed for isolation under fault conditions and fire hazards is also provided with typical details of the protective devices adopted for the same. We will also review the common practices followed for isolation and interlocking to ensure safety in the electrical systems. Learning objectives • • • • • • • • • 3.1 Objectives of safe design Insulation and its role in safety Types and classification of insulation Enclosures for safety IP Classification for enclosures Adverse thermal effects and prevention Prevention of hazards by Isolation and interlocks Equipment selection Role of standards in safety Objectives of safe design The rules and standards for electrical systems stipulate guidelines that are mostly focused towards safety of electrical equipment and installations. Many of such requirements for safety in respect of electrical equipment and installations must be addressed at the design and planning stage itself. Any unsafe situations arising from faulty design or incorrect selection cannot be easily rectified later, and, if at all it is possible to do so, the cost of rectifications or modifications as well as time required to make the installation safe are likely to be prohibitively high. Enough attention is therefore needed at the design and planning stage itself to ensure that the equipment or installation is safe to operate and maintain, and remains so during its entire service life. 32 Practical Electrical Wiring Standards - AS 3000:2018 Safety through design has the primary objective of eliminating hazards that can arise from the use of equipment both under normal circumstances as well as abnormal situations. The most common hazards associated with electrical equipment are: • Electric shock and internal organ damage due to passage of electricity through human body • Burns on skin at point of contact and injuries by electric shock combined with fall • Temperature hazards during operation • Arc flash causing external burns and injuries by explosive expansion of air due to the arc. In addition, fire hazard through combustible components of electrical equipment or from materials stored in the vicinity of electrical equipment, mechanical hazards from motive equipment and from impact of parts dislodged due to an arc fault and corrosion/explosion hazards from electro-chemical equipment are also likely to occur. Thus, the following basic safety aspects need to be addressed while designing electrical equipment. • Electric shocks • Arcing due to breakdown of insulation • Mechanical failures and injury to personnel • Burns due to high surface temperature. • Fire in nearby combustible materials • Features to ensure isolation and prevent accidental switching • Earthing facilities and interlocking to prevent accidents due to incorrect operations We will deal with these aspects in further detail in the ensuing sections of this chapter. 3.2 Preventing electric shocks Shock hazard is possible as a result of direct contact or indirect contact. Direct contact hazard can be prevented by using appropriate insulation, by proper enclosure of live parts, by placing obstacles for contact with exposed live parts or by placing live parts out of reach. The last named is applicable for all outdoor installations where proper clearances are provided to ensure that there could be no direct contact during normal operations in the vicinity of live conductors. The other method of preventing danger by direct (or indirect) contact is by the use of Separated Extra Low Voltage (SELV) systems. The voltage in these systems is so low that body current through direct contact can be withstood without harm for indefinitely long periods. Such use may be limited only for specific cases such as certain types of hand-tools, hand-lamps or other body-worn electrical gear and will not be further discussed here. Indirect contact occurs when a fault takes place in electrical equipment (usually as a result of insulation failure) between live parts or between live parts and an exposed metallic enclosure. Minimizing the hazard from indirect contact is probable by: • Limiting the voltage of contact (touch/step/transferred) surfaces and • Limiting the time of contact Limiting the voltage of contact is largely through adopting proper earthing practices as we discussed in earlier chapter. Limiting the time of contact under faults is possible through properly designed protective relaying that can sense the fault conditions. The importance of proper design of earthing and protection systems need not therefore be overemphasized. But prevention being better than cure, all attempts must be made to avoid the occurrence of a fault in the first place for which insulation is a fundamental choice. We can ascertain from the foregoing discussion that insulation plays an important part in avoiding dangers from both direct and indirect contact. Enclosures mainly act as a protective barrier against direct contact with live parts. By virtue of properly earthing the enclosures, that ensures early detection of faults, indirect hazard can also be minimized. The enclosures also offer safety against arc faults and protect live parts from ingress of dust and water, thus reducing the possibilities of insulation failures. Safety aspects in electrical equipment design and selection 33 3.3 Importance of insulation in electrical safety No electrical equipment can be designed, constructed or used without insulating materials in some form or other, as they are needed to maintain the potential difference between the active parts of an installation for its proper functioning. Insulation materials can be solid such as insulators used for support of live conductors, insulating materials applied over windings and so on; they can be liquid, such as the dielectric oils used in transformers, or they can be in gaseous state, an example being the sulphur hexa-fluoride (SF 6 ) gas used in HV switchgear and circuit breakers. Even vacuum behaves as an insulating medium as there are no molecules that can conduct electricity. Naturally gaseous and liquid dielectrics have to be used in combination with solid dielectrics in any practical installation. Thus solid insulating materials play a crucial role in safety, in particular, when the insulating materials are applied over conductors. Insulation helps to prevent short circuit between live conductors, and between live conductor and the enclosures of equipment. Both of these are important from a safety point of view. A short circuit between live conductors can result in excessive currents flowing through the system resulting in extreme thermal and mechanical stresses in the conductors and in the system as a whole. There is also a danger of an arc flash developing because of such a fault. On the other hand, a fault between a live conductor and an equipment enclosure will cause the exposed metallic enclosure of faulty equipment to become live and cause an indirect contact hazard. Insulation materials have certain specific properties which decide their suitability for any specific application. One such property is their voltage withstand rating and the other is their operating temperature limit. The voltage withstand rating is expressed usually as kV/mm or some other such unit of thickness, and electrical stress beyond this limit, may result in a breakdown of the insulating material. Once a material thus breaks down, it may show signs of burning and becomes a good conductor; it is no longer useful as insulation. Similarly, each insulating material has a temperature limit beyond which it will get destroyed and is not usable as insulation. The composition of the material used as insulation decides the temperature withstanding capability. Insulating materials used for windings of electrical machinery are classified based on their temperature rating which is generally as per table 3.1. Table 3.1 Insulation classes of adopted in Electrical Machinery Class of Insulation A Limiting hot spot temperature 105 deg C Common materials/ combination E 120 deg C Dry chemical, Halon, CO 2 B 130 deg C Mica, asbestos, glass fiber, and similar inorganic materials with suitable bonding, impregnating or coating substances. F 155 deg C Mica, asbestos or glass fiber base with a high temperature resistant binding organic or inorganic material H 180 deg C Silicone elastomer and Mica, asbestos, or glass fiber base with a high temperature resistant binding material like silicone resins Cotton, silk, paper, and similar organic materials, impregnated or immersed in oil, and enamel applied on wires. 34 Practical Electrical Wiring Standards - AS 3000:2018 The properties of any insulating material generally deteriorate with age until it is no longer able to serve as insulation at the original ratings. This leads to sudden insulation failures even when the material is operating within its stated ratings. It should also be noted that prolonged operation at higher than limit values of temperature will cause faster ageing and lead to early insulation failure. High and repeated voltage and mechanical stresses can also cause breaking of insulating material and will lead to failures. Insulation failures are caused by the following conditions: • Temperature in excess of the limiting value (most common) • Voltage stress beyond its rated withstand value • Ageing of insulation • Excessive mechanical stresses Preventing unforeseen insulation failures is therefore important from the viewpoint of electrical safety. The following steps during the design phase will help to reduce failures and obtain longer life from insulation. 3.3.1 Preventing temperature related failures The approach here is to operate the insulation within its rated temperature under all operating conditions. • Design with suitable class of insulating material depending on anticipated operating temperatures • Consider maximum expected ambient temperature • Design on the basis of maximum internal temperature (hot spot) • Consider final temperature after a short circuit fault where required • Provide adequate safety margin or choose higher class • Provide protective devices to isolate a circuit in the event of abnormalities so that abnormal temperatures are detected well in advance and prevented While specifying electrical equipment, it is essential to state the ambient temperatures appropriate to the installation. In critical equipment, it is usual to also specify a higher safety margin for operating temperature by specifying a higher class of insulation and stipulate temperature restriction corresponding to a lower class. For example, a turbo generator stator may be specified with class F insulation but with design temperature corresponding to class B. The trade-off here is between optimizing the cost of the equipment against the cost of a failure during operation and consequential losses. 3.3.2 Preventing voltage stress related failures Failure due to voltage stress can not be a common occurrence. The design withstand value of an insulation is governed by the Basic Impulse Level of the system which is usually quite high compared to the operating voltage (Example: a 10 kV system may have a BIL of 75 kV or even 90 kV). This is to prevent failures during voltage surges occurring due to lightning strike or switching. Design approach here should be: • Design with required thickness/layers of material • Design for maximum expected voltage • Provide protection against unexpected over-voltage by external surge protection devices (SPD) Surge protection is not a mandatory requirement per AS/NZS 3000. Appendix F of the standard provides informative details on selection and installation of Surge protection devices (SPD) in low voltage systems that can limit transient overvoltages caused either by power line disturbances or by natural events like lightning strikes on exposed conductors. SPDs should be installed after the main switch but prior to any RCD devices. Type of surge protection shall be selected to meet the kind of protection needed as noted below. Safety aspects in electrical equipment design and selection 35 • • • • Primary SPDs should be installed near the origin of the electrical installation or in the main switchboard. Secondary protection in the form of plug-in surge filters or distribution board protection may be warranted for premises containing sensitive electronic equipment. Such secondary protection should be coordinated with the upstream SPDs in line with the manufacturer’s instructions. For most domestic single-phase supplies in urban environments, a maximum surge rating of 40 kA per phase for an 8/20 µs impulse and a minimum working voltage of 275 V AC is suitable. In the case of installations in exposed locations, e.g. high lightning areas, long overhead service lines, industrial and commercial premises, it may be prudent to install SPDs with a higher surge rating, typically 100 kA per phase for an 8/20 µs impulse. 3.3.3 Preventing ageing related failures An insulating material cannot work indefinitely. Ageing is more rapid with exposures to constant high temperatures. To obtain a long life from insulation, it should not be allowed to operate at temperatures higher than its rated value. The design should aim at an optimum point between initial cost and life obtainable. 3.3.4 Preventing failures due to mechanical stresses Mechanical stresses develop in insulation due to various reasons. One such reason is stress due to centrifugal forces caused by rotation or by electrodynamic forces. Such failures are normally observed in the overhang portion of the windings of electrical rotating machinery. Mechanical stresses can also be caused due to electromagnetic forces occurring during short circuits. In busbar systems, these can result in damages to the support insulators as well as to the conductors. Such failures can be prevented by proper mechanical design of equipment with adequate supports. 3.3.5 Insulators for transmission systems and outdoor yards In addition to the classes of insulation discussed above, other solid insulating materials such as ceramics (porcelain) are used as insulating materials for conductor support in overhead lines and switchyards. The temperature limit of these insulators is very high. Failures in this type of insulators are either due to voltage stress or mechanical damage (which sometimes follows a voltage break down). These insulators bear the brunt of surges due to a direct lightning strike or induced surges resulting from a direct strike on nearby conductors. Since lines do not have any surge protection devices, a failure can take place across an insulator, thereby creating an earth fault. Failures can be prevented by the following measures: • Design for appropriate clearance/creepage distances for the concerned system voltage • Heavy duty/longer creepage insulators to be selected in areas prone to dust and corrosion. • Switchyard equipment shall be protected using surge arrestors in points of line termination and near major equipment such as transformers • Provide surge grading for multi-element insulators • Provide on-line washing equipment for critical installations 3.4 Importance of enclosures in ensuring safety Enclosures serve many important functions in electrical equipment. The first is naturally that of providing protection against direct contact by preventing access. Another function of enclosures is protection of electrical equipment from the ingress of water and dust, which can result in equipment failures. Enclosures also serve to contain and divert an arc flash within the equipment and provide safety to operating personnel from burns and the explosive effects of faults. Enclosures are characterized by their degree of protection which is expressed by using the International Protection (IP) classification. 36 Practical Electrical Wiring Standards - AS 3000:2018 3.4.1 IP Classification IP Classification is an alphanumeric code consisting of the following characters: • Prefix of the letters IP followed by a 2- digit group denoting protection offered against entry of solid objects and liquids • First digit: Protection against entry of solid objects (Numerals used 0 to 6, or letter X), with the 0 depicting NIL protection and 6 providing the highest possible protection against dust. • Second digit: Protection against entry of liquid (Numerals 0 to 8) with 0 depicting NIL protection and 8 denoting the highest possible protection from water like submerged in water for a long time. • A character X in place of the numerals means that the particular protection characteristic is not relevant in the given situation or it may be because it is defined in the subsequent group The above method of classification with two numerals the most common adopted for equipments meeting IEC, European and Australian standards. USA follows different method of enclosure classification as specified by NEMA (National Electrical Manufacturers Association) and is generally applied for equipments used within North America. Tables 3.2 and 3.3 give the explanation of the first and second numerals adopted in IP category in accordance with AS 60529, which is given in AS/NZS 3000 appendix G. Table 3.2 IP Classification – Meaning of the first digit (Source: AS/NZS 3000, Figure G1a) First Protection offered against solid Numeral particles 0 No protection Protection of persons against access with Non-protected 1 Full penetration ≥ 50 mm diameter sphere Back of hand 2 Full penetration ≥ 12.5 mm dia sphere Finger 3 Access probe penetration ≥ 2.5 mm dia Tool 4 Access probe penetration ≥ 1.0 mm dia Wire 5 Limited ingress of dust (no harmful deposit) Wire 6 Totally protected against ingress of dust Wire Safety aspects in electrical equipment design and selection 37 Table 3.3 IP Classification – Meaning of the second digit (Source: AS/NZS 3000, Figure G1b) Second Numeral Protection offered against Water Protection from effects of 0 No protection Non-protected 1 Vertically falling drops with limited ingress Vertically dripping 2 Vertically falling drops with enclosure tilted 15° from the vertical. Limited ingress permitted Dripping up to 15° from the vertical 3 Sprays at 60° from the vertical with limited ingress Limited spraying 4 Splashed from all directions with limited ingress Splashing 5 Jets of water with limited ingress Hosing jets in all directions 6 Strong jets with limited ingress permitted Strong hosing jets from all directions 7 Immersion between 15 cm and 1 m Temporary immersion 8 Long periods of immersion under pressure Continuous immersion Though, not strictly followed by many users and industries, it is also an optional requirement to specify two additional alphabets as the third and fourth characters after the first two numeric values. The first additional alphabet (one of the four - A, B, C or D) specifies the protection offered by the enclosures from entry of objects like tool, wire, etc. The second/supplementary alphabet (one of the four – H, M, S or W) defines the operation suitability of the enclosure under certain applications like HV, specific weather conditions, etc. Tables 3.4 and 3.5 provide ready reference for the meanings of these alphabets. The IP rating shall suit the environmental conditions and the relevant mounting position as specified by the manufacturer. NOTE: This applies in particular to parts of enclosures that might serve as— (a) a floor; or (b) a surface where objects on surrounding surfaces may be displaced into openings. 38 Practical Electrical Wiring Standards - AS 3000:2018 Table 3.4 IP Classification – Meaning of the first additional alphabet (Source: AS/NZS 3000, Figure G1c) First additional alphabet Protection offered Protection of persons against access with Back of hand A Penetration of 50 mm diameter sphere up to barrier do not contact hazardous parts B Test finger penetration to a maximum of 80 mm must not contact hazardous parts Finger C Wire of 2.5 mm diameter × 100 mm long must not contact hazardous parts when spherical stop face is partially entered Tool D Wire of 1.0 mm diameter × 100 mm long must not contact hazardous parts when spherical stop face is partially entered Wire Table 3.5 IP Classification – Meaning of the supplementary alphabet (Source: AS/NZS 3000, Figure G1d) Supplementary alphabet H Protection offered Example High voltage apparatus M Tested for harmful effects from the ingress of water when the movable parts of the equipment are in motion The rotor of a rotating machine S Tested for harmful effects from the ingress of water when the movable parts of the equipment are stationary The rotor of a rotating machine W Suitable for use under specified weather conditions when provided with additional protective features or processes A typical example of enclosure specification as per IP Classification is given below by way of illustration: I P 56 D W stands for an enclosure which is: • Dust proof (First numeral 5) • Water tight (Second numeral 6) • Protected against access with a wire of 1mm diameter and 100 mm long (Additional letter D) • Suitable for use under specified weather conditions (Supplementary letter W) While on this subject, it may be recalled that it is also a practice to achieve safety against direct contact by using obstacles. An obstacle is designed to prevent: • Unintentional approach to a live part and • Unintentional contact with a live part while operating on/near energized equipment Safety aspects in electrical equipment design and selection 39 A part used as an obstacle must fulfill the following criteria: • Obstacles shall be secured to prevent unintentional removal • Removal should be possible only through the use of a tool or key • An obstacle should have a minimum protection rating of IP XX B. It must be noted that the door of a switchgear cubicle, which is opened using screwed wing-knobs, will not qualify as an obstacle. On the other hand, a bus chamber protected with a bolted cover would be deemed to have adequate protection against direct contact. Therefore, an IP classification serves to ascertain that an enclosure serves as an obstacle for direct contact with live parts as well as providing protection against the ingress of water and dust. As far as protection against arc fault hazard is concerned, an enclosure must ensure that it can withstand the explosive effect of a fault in the equipment within, without incurring physical damage. It must not have any openings through which flames can pass, which could harm the operator. Preferably, it should have some kind of explosion venting arrangement, which will help to deflect the arc gases in a safe manner away from operating personnel. Examples of such arrangements can be found in phase segregated terminal boxes of HV motors, which are provided with an explosion diaphragm at the lower part to release arc products. Many designs of HV metal clad switchgear provide hinged vent flaps at the top, which will open and release arc gases if there is an arc fault in the bus, breaker or cable compartment. Safety of the operator who will be normally standing in front of the cubicle is therefore ensured. Enclosures for electrical equipment for use in areas containing hazardous gases will have to be designed in accordance with relevant regulations to withstand an explosion of gases within the enclosure, in addition to meeting the protection against dust and water. These designs will require appropriate testing and certification for safety. 3.4.2 Placing live parts beyond ‘arm’s reach’ When work is carried out near exposed live parts, a safe clearance must be maintained with reference to the live parts, so that the worker does not accidentally come into contact with these parts. It must be remembered that in the case of HV equipment, the intense electric field generated around the live parts mat, causes the surrounding air to break down and conduct so that one may get electrocuted even without directly touching a live part. This danger does not exist in LV systems. Exposed conducting parts of a system must be located in such a way that during normal work in the vicinity of live equipment, safe clearances are always maintained appropriate to the working voltage. This is achieved by placing the live part out of ‘arm's reach’ from the envelope of minimum safe clearance for: • An exposed conductive part • An extraneous conductive part • A bare live part of any other system The same will have to be modified for HV systems by adding the minimum clearance for the specific operating voltage. The voltage dependent clearances will thus have to be calculated from the arm’s reach positions. For example, if the minimum safe clearance for 220 kV is stipulated as say 3000 mm, the minimum clearance from earth should be 5500 mm to place the conductor out of arm’s reach for an operator standing on the ground with his arm fully extended. In case there are any structures beneath the conductor on which the operator may stand, the clearance should be appropriately increased. A similar approach is also applied in AS/NZS 3000, which is explained in a subsequent chapter. Note that ‘arm’s reach’ defined above assumes that no metallic tools, long conducting objects (such as ladders) etc. are being held by the worker. Figure 3.1 illustrates the principle of ‘arm’s reach’ in all the three axes for LV systems as per IEE regulations. 40 Practical Electrical Wiring Standards - AS 3000:2018 Figure 3.1 Definition of ‘arm’s reach’ (Source IEE Wiring Regulations) 3.5 Prevention of adverse thermal effects Adverse thermal effects of electrical equipments include: • Burns due to high surface temperature • Fire in nearby combustible materials • Fire originating from electrical equipment • Arcing due to breakdown of insulation • Mechanical failures and injury to personnel due to arc faults One of the main design features for limiting thermal hazards is the protection against overloads (overcurrents) and short circuit faults. This is obtained through circuit protective devices such as fuses, protective relays and circuit breakers. This section briefly discusses these devices. 3.5.1 Protection with fuses Fuses are perhaps the simplest and cheapest device used for interrupting an electrical circuit under short circuit or excessive overload, current magnitudes. It is used for overload and short circuit protection in high voltage up to 66kV and low voltage up to 400V installations. The action of the fuse is based on the heating effect of the electric current. In normal operating conditions, when current flowing through the circuit is within safe limits, the heat developed in the fuse element carrying this current is readily dissipated into the surrounding air and therefore the fuse element remains below a temperature below its melting point. However when a fault such as short circuit occurs or when load connected in a circuit exceeds its capacity, the current exceeds the limiting value and the heat generated due to this excessive current cannot be dissipated fast enough. As a result, the fusible element gets heated, melts and breaks the circuit. In this way, it protects the equipment or an installation from damage due to excessive current. Advantages of fuses: • It needs no maintenance • Its operation is automatic • It interrupts enormous short circuit currents without noise, flame, gas or smoke • The minimum time of operation is made much smaller than that of the circuit breaker • The smaller sizes of fuse elements impose a current-limiting effect under short circuit conditions • Its inverse time current characteristic enables its use for overload protection Disadvantages with fuses: • Considerable time is lost in rewiring or replacing fuses after operation Safety aspects in electrical equipment design and selection 41 • • On heavy short circuits, discrimination between fuses in series cannot be obtained unless there are considerable differences in the relative sizes of the fuses concerned The current time characteristic of the fuse cannot be correlated with a protective device Figure 3.2 shows a high rupturing capacity fuse and a typical fuse element. Figure 3.2 HRC Fuse and element 3.5.2 Protection with relays Protection schemes required for the protection of power system components against abnormal conditions such as fault etc. consists of protective relaying and circuit breakers. The main functions of protective relaying are the detection of the presence of faults and their locations; to initiate the speedy removal from service of any element of the power system when it suffers short circuit, or when it starts to operate in any abnormal manner which might cause damage. Protective relays function as a sensing device. It senses the fault, determines the location and finally sends a tripping command to the circuit breaker. After getting the command from the relay, the circuit breaker disconnects the faulted element. The relays employed for protection against short circuits are operated by virtue of the current or voltage supplied to them by current transformers and/ or voltage transformers. Failure in the system is indicated by relative changes in currents or voltages supplied to the protective relaying equipment. Relays can be of electromechanical type, static type (analog) or numerical type (digital). A complete description of these devices is beyond the scope of this text. A circuit breaker is a device which interrupts the abnormal or fault currents and in addition, performs the function of a switch. Circuit breakers are mechanical devices designed to close or open a set of fixed and moving contacts, thereby closing or opening an electrical circuit under normal or abnormal condition. It consists of fixed and moving contacts which touch each other and carry the current under normal operating condition i.e. when the circuit breaker is closed. When fault occurs in any parts of the system, the trip coil of a circuit breaker becomes energized through the protective relay (or a release) and the moving contact is pulled apart by some mechanism, thereby opening the circuit. The separation of current carrying parts produces an arc. This arc not only delays current interruption process, but also generates lots of heat, which may cause damage to the system. To extinguish the arc within the shortest possible time is the main concern of the circuit breaker. Hence it is necessary to use special extinguishing mediums like vacuum, oil, SF6 in HV applications while low voltage breakers can be interrupted in air with suitable designs to avoid spread of arcs to the surrounding materials. For low voltage applications, air circuit breakers (ACB) and moulded case circuit breakers (MCCB) are the most commonly used types to open and close a circuit under normal conditions. 42 Practical Electrical Wiring Standards - AS 3000:2018 These are having features to trip under abnormal fault conditions of over load and short circuit. Miniature circuit breakers are basically mini version of moulded breakers and are generally available for use upto a maximum of around 100 amperes. Single pole and multipole versions are available for MCB’s whereas the MCCB’s and ACB’s are available in three/ four pole versions for isolating all three phases + neutral simultaneously. These are usually fitted with internal releases to sense and open under fault conditions, though external relays are used for ACB’s in major applications involving higher currents. 3.5.3 Protection against Fire hazards One of the major hazards of electrical installations is fire. Many electrical types of equipment contain flammable materials; for example, mineral oil cooled transformers and oil circuit breakers. Even PVC, which is used as insulation and as a sheathing material of electrical cables, is combustible. Often, the reason for fire is an electrical short circuit fault. Excessive currents and arcing can cause fire in combustible equipment components. In some cases, materials stored nearby can catch fire and cause a further spreading of the fire. Apart from the general destruction to life and property, electrical fires have other repercussions also. For example, cable fires emit toxic and corrosive gases since the PVC insulation contains hydrogen and chlorine. The dense black fumes also limit visibility and impede fire-fighting attempts. Hydrogen chloride emitted by cable fires can react with water (used in fire fighting) to form hydrochloric acid. This acid can condense on the surface of electrical components and printed circuit boards in control room panels, causing irreversible damage, even when the equipments are not directly affected by the fire. Appropriate measures must be incorporated in the design of an electrical installation. These measures must help to prevent fires, sense incipient fires should they occur, contain their spread and extinguish fires. We will briefly discuss these measures below. Fires can be avoided to a large extent by preventing insulation failures and short circuits through adequate design. Since fires are often caused by short circuits, the protective devices for clearing a short circuit fault must be fast acting in order to limit the energy flowing into the faulty equipment. LV circuits must be protected with high rupturing capacity fuses of appropriate short circuit rating or by current limiting circuit breakers. Another precaution is to avoid using fire-prone equipment. For example, mineral oil cooled transformers can be replaced with dry type/cast resin transformers when indoor use is required. Oil circuit breakers should be replaced by air/vacuum/SF6 circuit breakers. Cables running close to furnaces or other combustion zones prone to flames must be given fireproof coating to avoid starting a cable fire. Storage of combustible substances in substations, cable vaults and in the vicinity of electric equipment enclosures, which may attain high temperatures during operation, should be avoided. Many electrical fires start due to arcing faults in branch circuits. Normal circuit breakers with short circuit protection cannot sense an arcing condition, as the current initially remains low due to the high impedance of the arc. Only when the intense heat produced by the arc damages the adjacent insulation, a full short circuit develops, causing the breaker to operate. Normally, by this time, a fire would already have started. Containing fires If a fire occurs, it must be contained within as small a space as possible. Providing fire partitions in electrical switchgear rooms and cable vaults is a common practice. Similarly, large mineral oilcooled transformers should be segregated using firewalls. By limiting the amount of combustible substances present within a given enclosed space, the severity of the fire is reduced and fire fighting can be more localized and therefore effective. Cable faults should use fire proof doors with certified withstand ratings. Openings through which cables pass from one enclosure to another must be sealed with approved fire seals. Special care is needed to ensure that ventilation systems do not cause the spread of fire between compartmentalized fire zones. Suitable interlocking may be used to stop ventilation to, not only affected areas, but to other areas communicating with the affected areas through duct work. Fire dampers with fusible elements can be deployed in ducting and in ventilation openings between different rooms to automatically close in the event of a fire. Also, the materials used in an installation should not cause fast propagation of the fire. Self- Safety aspects in electrical equipment design and selection 43 extinguishing insulation, fire-retarding/low smoke emitting materials etc. are used in cables intended for critical installations. Sensing fires Early warning devices within electrical equipment or rooms should be used to give an alarm of fires should they occur. Examples are infrared sensors and photoelectric sensors to detect temperature build up and incipient arc faults within enclosed electrical equipment. They will also be useful in triggering fire-extinguishing systems. Multiple types of detectors should be used in cable vaults (example: Ionization detector and smoke detector) with cross zoning for positive sensing of fires. Linear heat detecting cables are useful in cable vaults to supplement conventional detection systems. Addressable detectors connected to microprocessor based fire alarm and control equipment, enable precise information to be available regarding the origin and spread of cable fires. Fire extinguishing systems Critical installations should be protected with fire extinguishing arrangements. Appropriate methods of fire fighting must be used for each type of installation. Portable fire extinguishers may be provided in smaller electrical installations where elaborate automated arrangements may not be viable. Figure 3.3 shows the common types of hand-held extinguishers which are provided with color-coding for easy identification. Water and foam extinguishers are not recommended for use in electrical fires. Figure 3.3 Examples of hand-held fire extinguishers Table 3.6 shows the application of fire-extinguishers for different types of fire. The number of extinguishers and locations will depend on local codes/guidelines. 44 Practical Electrical Wiring Standards - AS 3000:2018 Table 3.6 Application of fire extinguishers Class of Fire A Nature of fire Common combustibles: wood, paper, cloth, rubber, trash and most plastics Suitable extinguisher type Water type B Flammable liquids: gasoline, kerosene, oil, grease, solvents and paint Dry chemical, Halon, CO 2 C Live electrical equipment: motors, computers, wiring and appliances Dry chemical, Halon, CO 2 In large substations and electrical installations, it is normal practice to provide integrated fire protection systems with sensors, fire alarms and extinguishing schemes all operating together in automated fashion. Figure 3.4 shows such a typical integrated fire detection-alarm-extinguishing system for use in electrical switchgear rooms with carbon-dioxide (CO 2 ) as the extinguishing medium. The smoke sensor shown is a photocell type and contains a light emitter and a receiver. When smoke enters the sensor and reflects the light of the emitter on to the sensor, the sensor gives a signal to the monitoring unit. The other alternative type sensor is the ionization type, with special gas sensing elements which output a signal when they sense the gases of the combustion. The monitoring circuit gives audible and visual alarms, allowing the personnel inside the substation to evacuate to safety. After a preset time delay, the monitoring unit opens gas valves releasing CO 2 or halon into the fire zone. Personnel should evacuate during the alarm period, in order to avoid the risk of becoming asphyxiated. To avoid false alarms caused by mal-functioning of the sensors, a voting system is used, whereby at least two sensors need to sense the fire and relay a signal to the control unit, in order for the control unit to initiate an action. Figure 3.4 Integrated fire-fighting system using CO 2 It is necessary to check the gas cylinders periodically. Although CO 2 is non-toxic, it causes asphyxiation and care must be taken to make the system inoperative whilst personnel are in the room. This is usually achieved by inserting a stop pin into the lever valve to prevent operation. Control rooms and other high value assets are protected by Halon (or non-CFC equivalent) flooding systems. Because a low concentration of the gas is adequate to extinguish the fire, there is Safety aspects in electrical equipment design and selection 45 no danger of asphyxiation as exists with CO 2 . As such, there is no need to evacuate personnel before the system releases the gas. Of course, evacuation is still necessary from a fire safety point of view but it need not precede the gas release. Transformer fire-fighting systems use a fine water/emulsion spray with frangible bulbs mounted on the transformer tank to sense the fire. These bulbs are made from thin-walled glass: the bulbs break in the event of a fire and the resultant release of a pressurizing medium senses the fire. Cable fireextinguishing systems use linear detecting cables to detect a fire, with water spray nozzles for quenching the fire. Linear detection cables run along cableways and can effectively sense a fire and help to locate the cableway where a fire has taken place. 3.6 Isolation arrangements It has been well proven that most electrical accidents occur as a result of improper isolation of equipment before work on a normally live part is taken up. Around 60% of accidents are due to improper or insecure isolation. Isolation ensures that an equipment is disconnected fully from all electrical sources and work on that equipment can be safely carried out. Continued isolation must be ensured until the equipment, which has been previously isolated, is fit to be put back into service. A sudden re-energisation may cause electrocution, if the people working on the equipment presume that it is dead (and therefore safe to work on). Accidental re-energisation of drives may cause unexpected starting of mechanical equipment, which may, in turn, cause injury to those working on the equipment. It is important to distinguish between devices used for isolation and those used for functional switching. ISOLATION is a function intended to cut off, for reasons of safety, the supply from all or a discrete section of the installation, by separating the installation from every source of energy. Examples: Switch, disconnector, circuit breaker FUNCTIONAL SWITCHING is intended to switch on or off, or vary the supply of electrical energy to all or part of an installation for normal operating purposes. Example: A contactor. Isolation is primarily a safety function and generally uses manually operated/controlled equipment. A switch is a special isolator, which can perform switching of load currents and can also close on faults. Switches are also usually manually controlled. Functional switching devices are those intended to perform load control. Functional switching equipments are not normally used as isolation devices and are often remotely/automatically operated. Certain devices such as circuit breakers may perform both functions, particularly when mounted on a withdrawable carriage, which can ensure positive isolation. A circuit breaker, which cannot be withdrawn from the operating position, should be treated only as a functional device and must be supplemented by other isolating devices. Once a device is properly isolated, it must be prevented from accidental reenergisation using mechanical interlocks, padlocking of operating handles or other safety features. Such facilities should be integrated into the equipment design itself. 3.7 Earthing and interlocks Any equipment, which has been isolated, must also be earthed to prevent accidental energisation. Earthing is the best means of ensuring safety of personnel. No work should be performed on equipment unless it is visibly earthed. In case earthing has been applied at a remote point, a portable earth clamp should be applied close to the work spot. Checking by voltage indicator prior to earthing is necessary to avoid inadvertent earthing of live conductors, thereby creating a short circuit fault. After isolating the equipment or section required to be maintained, it is necessary to connect it to earth to ensure the safety of personnel. Where earth switches are available (as is the case with outdoor HV switchyards and GIS substations), they can be used for this purpose. In other cases, 46 Practical Electrical Wiring Standards - AS 3000:2018 approved types of portable earth clamps must be used. Whether switch or clamp, they short circuit all three phases and connect them to earth at the point of work. This serves two purposes: • The part where work is carried out is clamped to earth potential. This will also minimize any voltages that can be induced because of stray magnetic fields • If there is any inadvertent re-energisation when work is being carried out, it creates a three-phase metallic short circuit which will cause the circuit protective devices to operate In the case of indoor switchgear panels, such earthing is normally carried out at the outgoing terminals of the feeding cubicle at the time of rendering the circuit dead. But in certain cases, the work may be carried out in some other place. In that case, a portable earth clamp must be used close to the point of work, in such a way that it is between the supply side and the point of work. The correct placement of the clamp involves firstly connecting the earth lead of the clamp, followed by the line leads one by one. This operation may be performed by first lightly touching the line clamp to each phase at the point of work, taking due precautions to avoid being exposed to any arc, in case the point of work is still live. Where induced voltages may be present, earth clamps should be used at two points to ensure that a circulating current is set up and the voltage is effectively controlled. The current rating of the clamp conductor or switch must be adequate to carry the induced current safely with minimum voltage drop. Otherwise overheating may occur, exposing working personnel to temperature hazards. Interlocks operate to remove hazards prior to access. Interlocks disable electrical sources and/or mechanical hazards. The means for interlocking must be reliable; often, the switch or device must be cycle-tested. The interlock should only consist of electro-mechanical components and should not rely on logic circuits or semiconductors. An analysis should show that a single fault cannot render the interlock circuit inoperable. Should it fail, it must fail in the safe mode (i.e., hazard locked-out). Other general considerations include: • All hazards must be removed before the cover can be opened • The interlock switch cannot be defeated by hand or without a tool • The door or cover cannot be closed with the switch defeated Safety interlocks should be fitted to all enclosures to prevent access with conductors LIVE. Mechanical and electro-mechanical interlocks are preferred for permanent enclosures; the simpler the method of operation the more effective it is likely to be. Permanent interlock systems should be positively operated, must be fail safe, and may, as an advantage, have the wiring segregated from other wiring. For less permanent experiments simple electrical interlocks may be quite adequate. 3.8 Equipment Selection The common rules for selection and erection of equipment consists of five main criteria: • Operational conditions and external influence • Compliance with standard • Accessibility • Identification and notices • Mutual detrimental influences These requirements are common rules and must be applied to every installation irrespective of its location and environment. The equipment must, of course, be fit for purpose and suitable for all the relevant operating conditions as well as for the external influences as shown in table 3.7. Safety aspects in electrical equipment design and selection 47 Table 3.7 Equipment selection on basis of operation Aspect Requirement Voltage Equipment shall be suitable for nominal voltage to earth or between phases as per application. Current To be suitable for design current: account to be taken of capacitive and inductive effects. To be suitable for fault current: for the duration of the fault. Frequency Where frequency affects the characteristic of the equipment, the rated frequency of the equipment must match that of supply Power The power characteristics of the equipment to be suitable for the duty demands Compatibility Equipment not to cause harmful effects to other equipments nor to the supply Compliance with standards: In terms of the selection and erection of equipment rule contained in Regulation, the equipment must be constructed to an acceptable current standard. The other factors of good installations are: • Equipment performance: reference to standard specification • Sound engineering principles and code of practice • The correct functioning of equipment as specified by user. The specific guidelines of AS/NZS 3000 in respect of selection of equipment for LV systems are detailed in a subsequent chapter. 3.9 Role of codes and standards in installation safety Various standards and codes of practice are available on electrical equipment and installations. These may be national standards such as ANSI, BS etc., international standards (IEC for example) or industry-based standards (examples include IEE, IEEE, UL etc.). All such standards and practices reflect the experience gained over decades of designing and operating electrical installations and thus attempt to provide guidelines for design and installation of systems, so that they operate in a trouble-free and safe manner. Apart from these standards, locally applicable codes and statutory regulations have been put in place by each country, specifically covering their philosophy and approach to safety in design and installation. By applying these standards and codes, a designer or installer can ensure satisfactory performance and safe operating conditions. Appendix-A of AS/NZS 3000 lists out the various codes and regulations to be followed to achieve the safety objectives of the standard. 3.10 Summary Many of the requirements for safety in respect of electrical equipment and installations must be addressed at the design and planning stages, as unsafe situations arising from faulty design or incorrect selection cannot be easily rectified later. Safety through design has the primary objective of eliminating hazards that can arise from the use of equipment, both under normal circumstances as well as in abnormal situations. The main safety features to be incorporated in the design of any electrical equipment are: preventing electric shock, preventing adverse thermal effects and providing features to ensure isolation and prevent accidental switching. Insulation plays an important part in avoiding dangers from both direct and indirect contact. Insulating materials/components prevent short circuit between live conductors and between live conductors and the enclosures of equipment. Insulation failures by thermal or voltage stress must be avoided 48 Practical Electrical Wiring Standards - AS 3000:2018 by proper design of equipment. External protection devices, such as surge arrestors, must be provided to prevent failures due to transient over voltages. Enclosures act as a barrier against direct contact with live parts and by virtue of properly earthing the enclosures, indirect hazard can be minimized also. They also provide safety against arc faults and protect live parts from the ingress of dust and water, thereby avoiding insulation failures. Obstacles to prevent unintentional contact and the placing of a live part out of arm’s reach are ways in which direct contact can be avoided. Adverse thermal effects are a result of high temperatures occurring during equipment operation in exposed metallic enclosures and conducting parts. Adverse thermal effects can be prevented by limiting the temperature of conducting parts as well as accessible parts, by measures such as the adequate sizing of conductors based on temperature limits. Harmful thermal effects can further be avoided by limiting the possibility of contact with parts under high temperature. One of the major hazards of electrical installations is fire. Appropriate measures must be incorporated in the design of an electrical installation to prevent, contain, sense and extinguish fires. Around 60% of the accidents involving electrical equipment are the results of improper or insecure isolation. Isolation should ensure that equipment is disconnected fully from all electrical sources and can be safely maintained. Continued isolation must be ensured until the equipment which has been previously isolated, is fit to be put back into service. Once a device is properly isolated, it must be prevented from accidental re-energisation by using mechanical interlocks, padlocking of operating handles or other safety features. Such facilities should be integrated into the equipment design itself. Safety aspects in electrical equipment design and selection 49 4 Earthing of Electrical Systems In this chapter, we will review the limitations of unearthed systems and the basic theory behind earthing of electrical installation. The chapter also covers the common earthing methods adopted at the source end and the load ends and some important safety issues related with earthing like direct and indirect shock hazards, protective devices operation, thermal capacity of protective conductors etc. The basic types of earth fault sensing devices and their operations will be explained. We also will review the common earthing practices recommended and adopted at LV consumer installations. The chapter will be concluded with the methods adopted for earth fault detection and the importance of low earth loop impedance, which is one of the important requirements of AS/NZS 3000. Learning objectives • • • • • • • • 4.1 Unearthed and earthed systems System Earthing (at the source) and methods adopted Protective Earthing(at the load ends) Shock hazards and importance of protective earthing Protective earth conductors Common earthing practices in LV consumer ends Earth loop impedance and its importance. Detection of earth fault currents Unearthed and earthed systems Before going into the earthing methods, we will have a review on unearthed systems and their limitations in ensuring safety. 4.1.1 Unearthed Systems As discussed in earlier, providing a reference earth in an electrical system is essential for safe operation. But there are certain cases in which a system can be operated without such a reference. By definition, an electrical system which is not intentionally connected to the earth at any point is an unearthed system. However it should be noted that a connection to earth of sort does exist due to the presence of capacitances between the live conductors and earth that provides a reference. But these capacitive reactances are so high that they cannot provide a reliable reference. Figure 4.1 illustrates this point. In some cases the neutral of potential transformer primaries connected to the system is earthed also thus giving a reference of earth in the system. 50 Practical Electrical Wiring Standards - AS 3000:2018 Line ZL Load S ZN Neutral S : Source of Voltage V ZL : Impedance of Line Conductor to Earth ( Combination of Insulation Resistance and line to Earth Capacitance ) ZN : Impedance of Neutral Conductor to Earth Normally : ZL ≈ ZN Therefore : VL = VN = V / 2 Figure 4.1 A Virtual Earth in an Unearthed System It may be noted that normally the capacitance values being equal, the lines L1 and L2 are roughly at a potential equal to half the voltage of the source from the earth. (It is possible to demonstrate this by measurement of a high impedance device such as an electrostatic type of voltmeter). The main advantage cited for unearthed systems is that when there is a fault in the system involving earth the resulting currents are so low that they do not pose an immediate problem to the system. Therefore the system can continue without interruption which could be important when an outage will be expensive in terms of lost production or can give rise to life threatening emergencies. The second advantage is that one need not invest on elaborate protective equipment as well as earthing systems, thus reducing the overall cost of the system. (In practice this is however offset somewhat by the higher insulation ratings which this kind of system calls for due to practical considerations). The disadvantages of unearthed systems are as follows. • In all but very small electrical systems, the capacitances which exist between the system conductors and the earth can result in the flow of current at the faulted point which can cause repeated arcing and build up of excessive voltage with reference to earth. This is far more destructive and can cause multiple insulation failures in the system at the same instant. • The second disadvantage in practical systems is to be able to find out the exact location of the fault, which could take far more time than with earthed systems. This is because the detection of fault is usually done by means of a broken Delta connection in the Voltage transformer circuit and to detect exact fault location, a Earthing of Electrical Systems 51 • complex system of earth fault protection is required which negates the cost advantage we originally talked about. Also a second earth fault occurring in a different phase when one unresolved fault is present will result in a short circuit in the system. Due to these overwhelming disadvantages very rarely, if ever, distribution systems are operated as unearthed. However part of electrical distribution is sometimes done using Separated Extra Low Voltage systems (SELV) which are essentially unearthed systems of low voltage on a limited scale with the objective of enhanced safety in vulnerable situations. We will see more about such systems in later chapters. 4.1.2 Earthed Systems Figure 4.2 shows the various types of earthing methods that are possible and adopted in ac systems. System Earthing UnEarthed Impedance Earthing Resistance Low Resistance High Resistance Earthed Solid Earthing Reactance Low Reactance Tuned High Reactance Figure 4.2 Earthing Methods in electrical systems The diagrammatic representation of these different earthing techniques and the equivalent impedances from the source to the earth are shown in Figure 4.3. 52 Practical Electrical Wiring Standards - AS 3000:2018 Figure 4.3 Earthing Techniques and Equivalent Impedances Earthing of Electrical Systems 53 4.2 Supply system (source) earthing or Functional earthing 4.2.1 Solidly earthed As is evident from the name, a solidly earthed system is one where the neutral of the system is directly connected to earth without introducing any intentional resistance in the earth circuit. A solidly earthed system clamps the neutral tightly to earth and ensures that when there is a earth fault in one phase, the voltage of the healthy phases with reference to earth does not increase to values appreciably higher than the value under the normal operating conditions. The advantages of this system are: • A fault is readily detected and therefore isolated quickly by circuit protective devices. • It is easy to identify and selectively trip the faulted circuit so that power to the other circuits or consumers can continue unaffected. (Contrast this with the unearthed system where a system may have to be extensively disturbed to enable detection of the faulty circuit). • No possibility of transient over voltages. The main disadvantage is that when applied in distribution circuits of higher voltage (5 kV and above), the very low earth impedance results in extremely high fault currents almost equal to or in some cases higher than the system’s three phase short circuit currents. This can increase the rupturing duty ratings of the equipment to be selected in these systems. Such high currents may not have serious consequences if the failure happens in the distribution conductors (overhead or cable). But when a fault happens inside a device such as a motor or generator such currents will result in extensive damage to active magnetic parts through which they flow to reach the earth. For these reasons use of solid earthing of neutral is restricted to systems of lower voltage (380V/400V/480V) used normally in consumer premises. In all the other cases some form of earthing impedance is always used for reducing damage to critical equipment components. 4.2.2 Earthing through neutral resistance This is by far the most common type of earthing method adopted in medium voltage circuits. The system is earthed by a resistor connected between the neutral point and earth. The advantages of this type of earthing are as follows. • Reducing damage to active magnetic components by reducing the fault current. • To minimize the fault energy so that the flash or arc blast effects are minimal thus ensuring safety of personnel near the fault point. • To avoid transient over voltages and the resulting secondary failures. • To reduce momentary voltage dips, which can be caused if, the fault currents were higher as in the case of a solidly earthed system. • To have sufficient fault current flow to permit easy detection and isolation of faulted circuits. Resistance earthing can again be sub-divided into two categories, viz., high resistance earthing and low resistance earthing. High resistance earthing limits the current to about 10 Amps. But to ensure that transient over voltages do not occur, this value should be more than the system capacitance to earth current. As such, the applications for high resistance earthing are somewhat limited to cases with very low tolerance to higher earth fault currents. A typical case is that of large turbine generators which are directly connected to a high voltage transmission system through a step up transformer. The capacitance current in generator circuits is usually very low permitting values earth fault currents to 54 Practical Electrical Wiring Standards - AS 3000:2018 be as low as 10 amps. The low current ensures minimal damage to generator magnetic core thus avoiding expensive factory repairs. Figure 4.4 illustrates a practical case of earthing the neutral of a generator of this type. Figure 4.4 Earthing of a Turbine Generator Neutral through a High Resistance On the other hand, a low resistance earthing is designed for earth fault currents of 100 amps or more with values of even 1000 amps being common. The value of earth fault current is still far lower than three phase system fault currents. This method is most commonly used in industrial medium voltage distribution systems and has all the advantages of transient limitation, easy detection and limiting severe arc or flash damages from happening. 4.2.3 Earthing with neutral reactance In this method of earthing, an inductor is used to connect the system neutral to earth. This also limits the earth fault current which is dependent on the phase to neutral voltage and the neutral impedance. It is usual to choose the value of the inductor in such a way that the earth fault current is restricted to a value between 25% and 60% of the three phase fault current to prevent the possibility of transient over voltages occurring. Even these values of fault current are high if damage prevention to active parts is the objective. 4.2.4 Resonant earthing using neutral reactor To avoid the problem of very high earth fault currents with standard/fixed impedances, the method of resonant earthing can be adopted. Resonant earthing is a variant of reactor earthing with the reactance value of the neutral reactor chosen such that the earth fault current through the reactor is equal to the current flowing through the system capacitances under such fault condition. This enables the fault current to be almost cancelled out resulting in a very low magnitude of current which is in phase with the voltage. This serves the objectives of low earth fault current as well as avoiding arcing (capacitive) faults which are the cause of transient over voltages. This type of earthing is common in systems of 15 kV (primary distribution) range with mainly overhead lines but is not used in industrial systems where the reactor tuning can get disturbed due to system configuration changes caused by switching on or off cable feeders (with high capacitive currents) frequently. Earthing of Electrical Systems 55 4.3 Protective earthing Protective earthing refers to the connection of the exposed metal parts (e.g. enclosures of electrical equipment) as well as extraneous metal parts (like cable support systems) of an installation to earth usually either in the installation itself or through protective earth conductors to the earthed point of the supply source system. The basic objectives of protective earthing are as follows. • To reduce electric shock hazards to personnel. • To provide a low impedance return path for earth fault currents to the power source so that the occurrence of fault can be sensed by the circuit protective devices and faulty circuit can be safely isolated. • To minimize fire or explosion hazard by providing an earth path of adequate rating matching the let through energy by circuit protective devices. • To provide a path for conducting away leakage current (small currents flowing through electrical protective insulation around live conductors) and for accumulated static charges. • To clamp an entire LV installation to as near earth potential as practically possible when an accidental contact to a higher voltage system occurs (e.g., an internal fault between MV and LV windings in a distribution transformer). To ensure operation of protection of the higher voltage system in such an eventuality. We will discuss the salient aspects of protective earthing in detail below 4.4 Prevention of shock hazards 4.4.1 Impact of shock currents The human body presents a certain amount of resistance to the flow of electric current. This however is not a constant value. It depends on factors such as body weight and the manner in which contact occurs and the parts of the body that are in contact with the earth. Figure 4.5 gives the resistances of different parts of a human body, through which a current may flow when it comes in contact with live points inadvertently or under fault conditions. 56 Practical Electrical Wiring Standards - AS 3000:2018 RB RF RF RMF RB : Resistance of human body for current flow between hands, hand to feet or between feet ( assumed as 1000 ohms ) RF : Resistance of soil below the foot assumed as a circular plate RMF : Mutual resistance of soil between the feet Figure 4.5 Resistance of Human Body to Current Flow If the flow of current through the human body involves the heart muscles, it can produce a condition known as fibrillation of the heart indicating cardiac malfunction. If allowed to continue, this can cause death. The value of current flowing in the human body creates different effects based on its value and duration. Table 4.1 shows typical impacts on humans for specific values of currents flowing through their bodies. Earthing of Electrical Systems 57 Table 4.1 Effects of currents through human bodies Current in mA Effect on human body 0.5 – 2 Threshold of perception 2 – 10 Painful sensation, increasing with current 10 – 25 Cramp and inability to 'let go'. Increase in blood pressure. Danger of asphyxiation from respiratory muscular contraction. 25 – 80 Severe muscular contraction sometimes involving bone fractures. Increased blood pressure. Loss of consciousness from heart and/or respiratory failure. Over 80 Burns at points of contact. Death from ventricular fibrillation (uncoordinated contractions of the heart muscles so that it ceases to pump). Persons are not normally accidentally electrocuted between phases or phase to neutral but almost all accidents are phase to earth. Figure 4.6 illustrates the four stages of the effects due to a current flow through the body: • Perception – tingling – about 1mA. • Let-go threshold level – about 10mA. • Non-let-go threshold level – 16mA. • Constriction of the therasic muscles – death by asphyxiation and ventricular fibrillation – about 70 …100mA. Figure 4.6 Effect of currents through human bodies 58 Practical Electrical Wiring Standards - AS 3000:2018 The threshold of time for which a human body can withstand depends on the body weight and the current flowing through the body. An empirical relation has been developed to arrive at this value. ts = SB IB 2 ------------------------------- 4.1 Where, t s = Duration of exposure in seconds (0.3 to 3 seconds time limits) I B = RMS current value through the body in amperes S B = Empirical constant taken as 116 for 50kg and 157 for 70kg body weight Using the above factors and assuming a normal body weight of 70 kg, it can be calculated that IB = 0.157 ts ------------------------------- 4.2 Using the above relationship, it can be calculated that an average 70kg body can withstand about 90 milliamperes while for 50kg body it would be about 67 milliaperes both for a maximum duration of 3 seconds before going to heart fibrillation. However the point to remember is that even small currents a couple of seconds can lead major accidents which can be common due to touch potential values increasing to appreciable levels under fault conditions. Hence the current leakage devices shall be able to sense very low currents in the order of milliamperes and operate very fast to provide effective protections from shock currents. A considerable portion of the body resistance is due to the outer skin and any loss of skin due to burning in contact with electrical conductors can lower the resistance and quickly raise the current flow to dangerous values. Also, moisture e.g. from bathing also reduces skin resistance by about half impacting double the current flow for the same voltages. Hence the values of currents given in this section shall be used with care, as these are based on very normal conditions. 4.4.2 Touch and Step Potential Electric shock hazard can be either ‘direct’ or ‘indirect’. Direct shock is the condition when a human body comes into direct contact with a part that is normally live. In this case the current flow through the body will be the governed by the voltage at the point of contact and earth and resistance of the human body. Part of the system impedance may also be included in the current path but this can be neglected since the value is usually negligible in comparison to the body resistance. Indirect contact is the condition when a potential is applied on a human body by a part of the system which is not directly in contact with a live part or not expected to be. First case is when a human body is in contact with an external or extraneous conductive part of an electrical installation and there is a fault in the system involving earth. For example a person standing on the earth with his hand touching the earthed metallic enclosure of electrical equipment and a fault occurs between the live conductor of the equipment and the enclosure. The other is the case of a potential difference between two points on the earth arising out of an earth fault in a system which is applied across the two feet when being kept at a distance of about 1 meter. This kind of earth fault usually happens in high voltage electrical switchyards when a live conductor snaps and falls on the earth. This creates appreciable potential differences which arise when the high voltage gets dissipated into the soil. The typical situations explained above may happen in two ways either between two hands or between one hand and both feet as illustrated in figure 4.7. Since the human body presents different values of resistance to the flow of electricity in these two paths, the voltage limits for tolerance of human body are to be calculated individually for both cases which follow further. Earthing of Electrical Systems 59 ~ ~ ( a ) Potential applied between two hands ~ ( b ) Potential between one hand and both feet RB RF RF RMF ( c ) EQ. circuit for ( b ) ~ RF ~ RMF RB RF ( d ) Potential applied between the feet ( e ) EQ. Circuit for ( d ) RB : Body resistance RF : Contact resistance of one foot and ground RMF : Mutual resistance between both feet Figure 4.7 Modes of Application of Electric Potential Case-1: The Resistance of contact with live/exposed conductive part (under fault condition) by both hands is given by the following relation: R A = R B + 0.5 (R F + R MF ) -------------------------------- 4.3 Where, R A = Touch voltage circuit resistance in ohms R B = Body resistance usually taken as 1000 ohms R F = Self resistance of each foot to remote earth in ohms R MF = Mutual resistance between the feet in ohms Case-2: Resistance offered when the earth contact is through the feet is given by: R A = RB + 2 ( RF − RMF ) -------------------------------- 4.4 Where, R A is the step voltage circuit resistance in ohms and other factors being same as indicated under equation 4.3. 60 Practical Electrical Wiring Standards - AS 3000:2018 The accidental contact that happens in buildings or other consumer installations is mostly of the first case. The voltage of tolerance in this mode as calculated using the resistance in case-1 is called as Touch Potential. The occurrence of the second mode of contact is specific to outdoor electrical substations with structure mounted equipment. The voltage value arrived at for case-2 is known as Step Potential. Since the body resistance is almost fixed under normal conditions, the voltage to which a human body is subjected is the main factor influencing the current flow through the body in the case of a direct shock condition. Minimizing of direct shock hazard can be done in two ways • By using lower voltage systems or • By making the probability of such contact as low as possible. The first involves use of extra low voltage systems. The second can be achieved by providing suitable barriers to prevent accidental contact and by providing adequate clearance between exposed live parts and work areas so that a person working in the area is not within an ‘arms reach’ of exposed conductors. Where possible, residual current devices sensitive enough to detect accidental contact (by detecting the leakage current that such a contact causes) can be deployed. Usually such devices can be put in final circuits feeding low power equipment where possibility of direct human contact is high (e.g. utility socket outlets, or low capacity domestic circuits) and the normal leakage current through insulation is negligible. Indirect shock hazards are minimized by design of commercial, industrial and domestic electrical installations and their earthing methods with due consideration to touch potential that can arise during abnormal or fault conditions. 4.4.3 Protective earthing for preventing shock hazards Protective earthing of electrical equipment is primarily concerned with connecting exposed parts of the equipment (that are conductive in nature but not normally live) to the earthing system through conductors known as protective earth conductors. For the earthing to offer effective protection, the earth fault current flowing (due to internal insulation failure or any other reason) through the equipment enclosure to the earth return path shall not allow the enclosure voltage to exceed the Touch Potential. This is also applicable to other parts that normally do not carry electric current. (Figure 4.8) Earthing of Electrical Systems 61 Equipment with Earthed Enclosure Line ~ Fault SOURCE Ig Neutral Earthing Path with Impedance Zg VTOUCH Figure 4.8 Voltage Pattern during Earth Fault The touch potential to be limited to achieve safety can be calculated by the application of Ohm’s law i.e. V touch = Ig x Zg, where Ig is the maximum earth fault current that is expected to flow and Zg is the resistance of the earth circuit. Refer figure 4.9. Ig is dependent on the type of system earthing adopted and the system voltage. Figure 4.9 Voltage of enclosure during flow of ground fault current Hence it is to be understood that for ensuring human safety against indirect shock hazards, the primary requirement is to limit the value of the voltage appearing on the external conductive parts 62 Practical Electrical Wiring Standards - AS 3000:2018 of electrical equipment. This will ensure that accidental human contact with these enclosures will not exceed the allowable touch potential which otherwise would result in fatal electrocution or serious injuries. 4.4.4 Earth potential rise during earth faults The role of the earth resistance of an installation needs to be properly understood. Most designers as well as vendors dealing with equipment that are susceptible to electrical noise (such as computers or communication devices) lay emphasis on low values of earth resistance in installations. This is not necessarily a factor in deciding the safety of the installation. Let us take for example, an installation where the source and consumer installation are separated by considerable distance. In case there is no metallic connection between the protective earth of the consumer and the source earth point, the earth fault currents tend to flow through the earth mass. This causes an elevation of earth mass potential at the receiving end. This condition is more relevant to three wire systems in medium voltage systems where usually metallic earth return paths between source and receiving equipment are absent, as shown in figure 4.10 Figure 4.10 Earth potential rise during earth faults However, in most low voltage applications (with some exceptions due to earthing methods) there is a metallic continuity between the neutral of the source and the protective earth of the installation. In such cases, the degree of potential rise of the local earth mass will be lower due to the lower impedance between the enclosure and the Earth. The main point to be remembered (in either case) is that the potential difference of the enclosure with reference to local earth mass is what essentially matters in rendering the system safe, regardless of the actual resistance to earth. The emphasis should be on achieving the lowest loop impedance for earth faults, particularly in LV installations rather than low earth resistance. This will enable sufficient flow of earth fault currents and will facilitate their quick detection and isolation as further explained subsequently. Earthing of Electrical Systems 63 4.5 Protective earth conductors It is very much important that the protective earth conductor mentioned in the previous paragraph or any other circuit component, which serves protective function, should be designed to withstand the resulting fault current without developing excessive temperature or causing sparking at the joints. This will happen if the joints in the conductor or other bonding connections are improperly executed. This condition must be true for the magnitude and duration of the current required for protective devices to operate and isolate the faulty circuit. It is therefore necessary to ensure good quality workmanship in these installations as otherwise the high temperatures or sparking may cause fires in the premises where they are installed. Particular care is needed in the case of installations where hazardous or inflammable materials/mixtures are present. Good conductivity and low corrosion are the primary requirements for a good earth conductor. It is common practice to use copper as earthing conductor, though other materials like aluminium, galvanized iron, etc are adopted for the protective earthing. AS/NZS 3000 details out calculations and tables to decide the size of these earth conductors, which will be discussed in a later chapter. 4.6 Earthing practices in low voltage consumer installations Low Voltage systems supplying to consumer premises are mostly solidly earthed. Protective earth connection in consumer premises (or extending the supply system’s earth to consumer premises) is however done in different ways. 4.6.1 Common categories of earthing systems The common categories of earthing of consumer installations use 2 to 4 alphabets combining the letters T, N, C and S which denote the following in line with IEC-60364. • T represents the distribution system is directly connected to earth—at the neutral point of the supply transformer • N indicates that the exposed conductive parts are connected to the earthed point of the distribution system • C means neutral and protective conductor functions are combined in a single conductor (the neutral conductor of the distribution system) • S represents the protective conductor function is separated from the neutral—separate conductors within the installation. Accordingly following types of earthing systems are possible in LV consumer installations with three phase power supply source. • TN-C system: A system in which a single conductor is provided to have a combined function of neutral and protective conductor throughout the supply and consumer installation. Here the neutral is earthed at the source and also along the distribution points. • TN-S system: In this system, independent conductors are provided for separate functions of neutral and protective earth throughout the system. • TN-C-S system: Here the Supply system combines neutral and earth, but they are separated out in the installation. A TN-C-S system requires that the PEN conductor is earthed at multiple points (about every 40m) to reduce the danger created by a break. In this system it is therefore essential to maintain the connection integrity of the common neutral-cum-earth conductor. • TT/IT systems: Here no earth conductor is provided by the supplier and installation requires its own earth rod (common with overhead supply lines and portable generator with no earth connection). Illustrations and more details of these systems are given in a separate appendix of this manual. 64 Practical Electrical Wiring Standards - AS 3000:2018 4.6.2 Requirements of TN-C-S system This is the system commonly adopted by many utility installations including Australia, where it is named as MEN – multiple earthed neutral – systems. Under the MEN system, the neutral conductor (PEN) of the distribution system is earthed at the source of supply at regular intervals throughout the system and at each electrical installation connected to the system. Within the electrical installation, the earthing system is separated from the neutral conductor and is arranged for the connection of the exposed conductive parts of equipment. The MEN system as installed in Australia and New Zealand differs from the IEC system. Both systems are identical in principle but vary in detail. For further details refer to AS/NZS 61439 and AS/NZS 3007. The MEN system and its various parts are illustrated in Figures 4.11 and 4.12. Figure 4.11 shows a general arrangement and Figure 4.12 an alternative arrangement in an owner or user operated supply substation installation. IEC 60364 series describes the MEN system as a TN-C-S system with the letters signifying — T the distribution system is directly connected to earth—at the neutral point of the supply transformer; N the exposed conductive parts are connected to the earthed point of the distribution system—at the MEN connection; C the neutral and protective conductor functions are combined in a single conductor (the neutral conductor of the distribution system); S the protective conductor function is separated from the neutral— separate conductors within the installation. Figure 4.11 Multiple earthed neutral (MEN) system of earthing – General arrangements PEN distribution/TN-C-S Earthing of Electrical Systems 65 Figure 4.12 Alternative earthing arrangement in an owner or user operated supply substation installation Like all others systems, TN-C-S does not prevent a fault occurring, but will ensure that the fault protection device operates quickly when that fault appears. This is a function of the earth loop resistance. Sufficiently low loop resistance will cause high currents but can be cleared faster. A lower current could result in a longer duration of fault because of which the energy dissipation through the point of fault can be quite high and could easily start a fire. An installation connected to a TN-C-S supply is subject to special requirements concerning the size of earthing and bonding leads, which are generally larger in cross-section than those for installations fed by supplies with other types of earthing. Full discussions with the Electricity Supply Company are necessary before commencing such an installation to ensure that their needs will be satisfied. Some installations cannot be connected to a TN-C supply due to the danger of neutral currents flowing from the network to earth via the earthed parts of the installation e.g. petrol stations or the absence of an equipotential zone e.g. construction sites. 4.6.3 Earth electrodes The connection to earth mass in an electrical installation is normally achieved by using earth electrodes which are buried or driven into the earth mass for sufficient depth of not less than 2 to 3 meters. Several types of earth electrodes using different materials, physical configurations and designs are in wide spread use and follow usually the local standards that govern electrical installations. A typical earth electrode arrangement is shown in figure 4.13. 66 Practical Electrical Wiring Standards - AS 3000:2018 Cover Slab Ground Level For water addition From earth bus Brick Chamber Soil around earth pit Galvanised steel electrode 3 M Long ; 40 mm Dia Pit filled with hygroscopic mixture ( Charcoal + salt ) Figure 4.13 A typical earth electrode used in electrical installations Several earth electrodes are bonded/ interconnected together to form an earth grid and are usually provided at substations for achieving satisfactory results. The general requirements that influence the choice of earth electrodes are as follows. • The need for achieving minimum acceptable earth resistance appropriate to the installation involved. • The need to maintain this resistance all round the year in varying climatic conditions. • The type of soil where the earthing is carried out. • Presence of agents that can cause corrosion of elements buried in earth. • The performance of such electrodes (considering the ground resistance of the electrode as an indicator) depends on the type of soil, its composition, conductivity, presence of moisture, soil temperature, etc. Several ground electrodes bonded together to form a cluster are usually provided for achieving satisfactory results. The electrode design and methods of installation will be dependent on these requirements. Earth resistance of an earthing system will vary at different times depending on conditions such as temperature and moisture content of the soil. Measurement of soil resistivity should be carried out where values are critical and used in the design of earthing system of an installation and verified by earth resistance measurements on completion of an installation. In areas of high soil resistivity, appropriate soil treatment should be undertaken to achieve desirable values of earth resistance. It will also be evident from the above discussions that being a critical factor in the safety of installation and personnel, the earthing system will have to be periodically monitored to ensure that its characteristics do not drift beyond acceptable limits. This forms part of initial verification and certification of installations as well as periodic inspection. Earthing of Electrical Systems 67 An appendix of this manual provides further insights to the earthing and earth electrode practices recommended/ followed in some other National codes. 4.6.4 Equipotential bonding Equipotential bonding refers to the method of physical interconnections between various exposed– conductive-parts and extraneous conductive parts to maintain all of them at substantially the same potential. Earthed equipotential zone is a zone within which exposed-conductive- parts and extraneousconductive- parts are maintained at substantially the same potential by bonding, such that, under fault conditions, the difference in potential between simultaneously accessible exposed and extraneous conductive parts will not cause electric shock. We have seen earlier in this chapter that when an earth fault takes place in an installation, the external conducting surfaces of the installation and the earth mass in the vicinity may attain higher potential with reference to the source earth. There is thus a possibility that a dangerous potential may develop between the conducting parts of non electrical systems including building structures and the external conducting parts of electrical installations as well as the surrounding earth. This may give rise to undesirable current flow through paths that are not normally designed to carry current (such as joints in building structures) and also cause hazardous situations of indirect shock. It is therefore necessary that all such parts are bonded to the electrical service earth point of the building to ensure safety of occupants. This is called equipotential bonding. Bonding is the practice of connecting all accessible metalwork - whether associated with the electrical installation (known as exposed-conductive- parts) or not (extraneous- conductive- parts) to the system earth. In a building there are typically a number of services other than electrical supply that employ metallic connections in their design. These include water piping, gas piping, HVAC ducting and so on. A building may also contain steel structures in its construction. There are two aspects to the equipotential bonding; the main bonding where services enter the building and supplementary bonding within rooms, particularly kitchens and bathrooms. Main bonding should interconnect the incoming gas, water and electricity service where these are metallic but can be omitted where the services are run in plastic as is frequently the case nowadays. Internally, bonding should link any items which are likely to either be at earth potential or which may become live in the event of a fault and which are sufficiently large that they can contact a significant part of the body or can be gripped. Small parts, other than those likely to be gripped, are ignored because the instinctive reaction to a shock is muscular contraction which will break the circuit. Supplementary equipotential bonding is normally recommended in the systems as automatic disconnection by itself cannot ensure safety because the time required for disconnection exceeds safe limits for humans. The local supplementary equipotential bonding reduces the potential difference to lower values thus making the system much safer. Figure 4.14 illustrates this condition. 68 Practical Electrical Wiring Standards - AS 3000:2018 Exposed Conductive Enclosure Line Source Extraneous Conductive Part Ia Neutral R Supplematery Equipotential Bonding Main Equipotential Bonding Rg Protective Earth Conductor Figure 4.14 Equivalent circuit with equipotential arrangement In each electrical installation, main equipotential bonding conductors (earthing wires) are required to connect the following to the main earthing terminal of the installation. • metal water service pipes • metal gas installation pipes • other metal service pipes and ducting • metal central heating and air conditioning systems • exposed metal structural parts of the building • lightning protection systems It is important to note that the reference above is always to metal pipes. If the pipes are made of plastic, they do not call for bonding. If the incoming pipes are made of plastic, but the pipes within the electrical installation are made of metal, the main bonding must be carried out. The bonding is being applied on the customer side of any meter, main stopcock or insulating insert and of course to the metal pipes of the installation. Such bonding is also necessary between the earth conductors of electrical systems and those of separately derived computer power supply systems, communication, signal and data systems and lightning protection earthing of a building. Many equipment failures in sensitive computing and communication equipment are attributable to the insistence of the vendors to keep them separated from the electrical service earth. Besides equipment failures such a practice also poses safety hazards particularly when lightning discharges take place in the vicinity. In such cases large potential difference can arise for very short periods between metal parts of different services unless they are properly bonded. Earthing of Electrical Systems 69 Lightning strikes can lead to flashovers if a lower impedance route to earth is available through the electrical system. Bonding is therefore required for protection of structures from Lightning. Sometimes the bonding is reinforced by additional bonding higher up the structure. Supplementary or additional equipotential bonding (earthing) is required in locations of increased shock risk. In domestic premises the locations identified as having this increased shock risk are rooms containing a bath or shower (bathrooms) and in the areas surrounding swimming pools. However there is no specific requirement to carry out supplementary bonding in domestic kitchens, wash rooms and lavatories that do not have a bath or shower. That is not to say that supplementary bonding in a kitchen or wash room is wrong but it is not necessary. Supplementary bonding is carried out to the earth terminal of equipment within the bathroom with exposed-conductive part. A supplementary bond is not run back to the main earth. Metal window frames are not required to be supplementary bonded unless they are electrically connected to the metallic structure of the building. Metal baths supplied by metal pipes do not require supplementary bonding if all the pipes are bonded and there is no other connection of the bath to earth. All bonding connections must be accessible and shall preferably be labeled to caution against accidental disconnections. Certain types of non-electrical machinery and equipments can cause a build up of static charge during their operation and this charge accumulates on the surface of the equipment parts (for instance, a flat rubber belt around two metal pulleys, which is a very common type of motive power transmission, generates a lot of static electricity). When a sufficient amount of charge is built up, a spark-over can occur between the charged part and any grounded body nearby. Such spark-over carries sufficient energy that can cause explosions in hazardous environments and fires in case combustible materials are located nearby. It is therefore necessary to provide bonding of the parts by suitable metallic connections to earth where charge build up can occur. Bonding prevents such build-up static charges which can also lead to shock hazards. 4.7 Earth fault loop impedance In the study above, it has been observed that the impedance of the earth system shall be limited to ensure proper detection of earth fault currents. The impedance of the earth fault current loop starting and ending at the point of earth fault is termed as the earth fault loop impedance. The earth fault loop impedance comprises the following starting from the point of fault. • The circuit protective conductor • The consumers earthing terminal and earthing conductor • The metallic or earth return path impedance as applicable • The path through the earthed neutral point of the transformer • The transformer winding and • The phase conductor from the transformer to the point of fault When a fault to an enclosure takes place in any electrical equipment, the return path through the earth mass alone is insufficient to operate the protective devices such as over-current release or fuses. This is so because the impedance between the enclosure and the earth mass is usually high enough to severely restrict the flow of fault currents, particularly in low voltage systems. In such cases it is imperative that a low impedance earth return path to the source is available, so that fault current of adequate magnitudes to cause operation of protective devices is ensured. The circuit protective conductor fulfills this function of a low impedance connection. Figure 4.15 explains this point. 70 Practical Electrical Wiring Standards - AS 3000:2018 Equipment Line S V Neutral IG1 RGS RGL (A) Grounding Path is completed through Earth Line G Neutral Metallic Grounding Path (RM) Ig2 RGL RGS (B) Grounding path completed through metallic connection of very low impedance IG1 = V/(RGL+RGS) , IG2 = V/ {RM* (RGL+RGS)} / (RM+RGL+RGS) IG1 will be very low because RGL+RGS may be of the order of a few ohms. IG2 will be much higher because of much lower parallel impedance(RM) metallic ground return path Figure 4.15 Earth Return Path and its importance. Earthing of Electrical Systems 71 4.8 Sensing of earth faults Figure 4.16 a to c shows the common methods adopted for sensing earth fault currents. One or more of these approaches are used depending on the system importance and the descriptions of these methods are given below. A Neutral B C R (a) A Neutral B C R (b) A Neutral B C R (c) Figure 4.16 Earth Fault detection circuits 72 Practical Electrical Wiring Standards - AS 3000:2018 • • • 4.9 In case the power supply source (such as the transformer) is a part of the system, a current transformer (CT) and relay is provided in the earth connection of the neutral of the transformer. (Figure 4.16 a). This is possible in substations and large commercial/industrial distribution systems. By a single current transformer enclosing all phase and neutral conductors (called as core balance or zero sequence CT). Such a transformer detects the earth fault currents and can operate a sensitive relay. (Figure 4.16 b). Its principle is used in residual current devices recommended in AS/NZS 3000 for LV consumer installations which will be described later. This device is capable of sensing very low value of earth fault/earth leakage currents and trips the circuit faster. This device can sense the current flowing when a human body comes into direct contact with a live part of the insulation. By individual current transformer in phase and neutral conductors and providing a relay in summation circuit to detect unbalance between the sum of phase currents and the return neutral current. (Figure 4.16 c) Summary Though unearthed systems can be adopted, in majority of the installations it is always a practice to implement earthed systems. There are different types of earthing systems followed at source using low/ high resistance, reactors, etc as well as solid earthing without any of these devices. The impedances in the neutral circuits basically limit the earth fault current but however solid earthing is the preferred choice for LV consumer premises for better safety. It is understood that a small flow of currents of more than 25 milli-amperes can lead to fatal death for humans and hence it is very important to ensure shock protection by use of proper earthing methods and devices. The protective earthing at load ends ensures that the touch potential values of the enclosures are limited to safe limits under fault conditions and helps to minimize the effects of direct and indirect contacts and associated shock hazards. There are different types of earthing practices adopted in LV installations. TN-C-S system with multiple earthing is usually adopted in utility consumer installations with common protective earth and neutral (PEN) conductors from the source and independent neutral and earth within the installation. The indirect shock hazards can be avoided by minimizing touch potential values with properly designed protective earthing. Protective earthing is to be carried out using adequately sized protective earth conductors having good conductivity and non-corrosive characteristics. The sizes of the earth conductors are usually standardized and given in the regulations for different loads and these can also be decided using established calculation procedures for known fault current values and duration. The equipotential bonding of various external parts is also a common practice to ensure better safety and avoid static charge buildup in addition to keeping low earth impedance. Earth potential may get elevated during earth fault conditions but it may not be sufficient to drive the current through the devices which are provided for earth fault detection, if the impedance is high. Hence there is a need to keep the earth loop impedance as low as possible for better detection of earth fault currents and to ensure early disconnection. There are established methods to sense earth faults through direct measurement or by unbalance in the phase and neutral currents and are incorporated based on distribution system size and its importance. Earthing of Electrical Systems 73 5 Section 1 - Scope, Application and Fundamental Principles This chapter will review the contents covered in section-1 of the AS/NZS 3000. First we will go through the definitions for a few important electrical terms applicable in the electrical systems outlined and used in the standard. This will be followed by the discussions on the major hazards associated with the electrical systems and their effects on the installations and safety of the consumers. We will also discuss the guidelines given in this section that are to be followed by the designers and contractors in design, selection and installation of the electrical systems for preventing the likely dangers associated with these hazards to ensure safety for people and properties. The applicable clause numbers of AS/NZS 3000 are identified in the respective section headings (here and in all subsequent chapters) as guidance for quick reference to the standard. Learning objectives • • • • • • • • 5.1 Scope and application areas Definitions Protection for safety Design of an electrical installation Selection of electrical equipment Installation of electrical equipment Verification and testing Compliance requirements Scope and application areas (clauses 1.1, 1.2) Section-1 of AS/NZS standard specifies the basic compliances to be necessarily met by the LV electrical installations to ensure high level safety for the personnel, livestock and properties in close proximity to these installations by applying the stipulations given related to the following activities. • Design of electrical installations • Selection and installation of electrical equipment forming part of such electrical installations • Procedures for construction and verification of electrical installations The rules in this section are basically intended: • To protect persons, livestock, and property from hazards likely to arise from an electrical installation when under use 74 Practical Electrical Wiring Standards - AS 3000:2018 • • As the guidelines by following which the electrical installation will function correctly for the desired application For application through legislative requirements, made in each State and Territory of Australia and in New Zealand, concerned with the safety of electrical installations by relevant statutory authorities The principal application of this Standard is to the electrical installations in use or being established in all types of premises and land used by electricity consumers. Nevertheless, at the discretion of competent personnel, these rules can be referenced to or applied through legislative or other requirements in matters such as • Safety of work places (like Occupational Health & Safety legislation and associated codes) • Safe design and construction of buildings (like building codes of Australia and New Zealand) • Electricity generation, transmission and distribution systems (Power plants, transmission/distribution lines, substations, etc) • Safe connection to electricity distribution systems. (Like service rules and conditions stipulated by local electricity distributors for supply of power) • Qualifications of electricity workers 5.2 Definitions (Clause 1.4) In the earlier chapters we have come across many terms commonly used in electrical distribution systems defining the safety, protection and associated features. In section-1 of AS/NZS 3000 most of the common terms used in the standard are defined for the purpose of better clarity and understanding by all those who are concerned with electricity distribution and its use. In this part of the chapter we will have a brief review of these definitions, with further explanations for study/ guidance. Accessible, readily: Capable of being reached quickly and without climbing over or removing obstructions, or using a movable ladder, and in any case not more than 2.0 m above the ground, floor or platform. Active conductors: Any conductor that is maintained at a difference of potential from the neutral or earthed conductor. In a system that does not include a neutral or earthed conductor, all conductors are considered to be active conductors. Aerial conductor: Any stranded conductor (including aerial bundled conductors) that is supported by insulators or purpose-designed fittings above the ground and is directly exposed to the weather. Appliance: In this standard the term appliance refers to a power consuming device A consuming device, other than a lamp, in which electricity is converted into heat, motion, or any other form of energy, or is substantially changed in its electrical character.. • Appliance, fixed: An appliance that is fastened to a support or otherwise secured in a • • • • specific location. Appliance, hand-held: A portable appliance intended to be held in the hand during normal use, the motor, if any, forming an integral part of the appliance. Appliance, Portable: Either an appliance that is moved while in operation or an appliance that can easily be moved from one place to another while connected to the supply. Appliance, stationary: Either a fixed appliance or an appliance having a mass exceeding 18 kg and not provided with a carrying handle. Arm's reach: A zone extending from any point on a surface where persons usually stand or move about, to the limits that a person can reach with the hand in any direction without assistance (e.g. tools or ladder) Figure 4.1 is the extract from the AS/NZS Section 1- Scope, Application and Fundamental Principles 75 3000 with dimensions identified in meters defining the arm’s reach zone, without considering tools that could be used in the hand to reach little further. It can be noted that these zones are generally matching the IEE regulation definition for the same. Please take note of the difference among the term “accessible” defined earlier, “arm’s reach” as well as the three different dimensions 2.5m, 1.25m and 0.75m in the figure based on the possibility of arm’s ability to reach a point in a particular direction, to have a full understanding on the various possibilities of an exposure to a hazardous situation under normal conditions. Figure 4.1 Zone of arm’s reach (Source: AS/NZS: 3000, Figure 1.1) • Barrier: A part providing basic protection from any usual direction of access. o o • Basic insulation (Clause 1.4.73 Insulation system) Basic protection (Clause 1.4.97 Protection, basic) Circuit-breaker: A switch suitable for opening a circuit automatically, as a result of predetermined conditions, such as those of overcurrent or undervoltage, or by some form of external control. (In the following definitions the term ‘equipment’ basically refers to electrical equipment operating within an enclosure. In the standard, the electrical equipments are broadly classified as class I, class II and class III to imply the kind of protection offered by the respective equipments over and above the insulation on the live parts) • Class I equipment: Equipment in which protection against electric shock does not rely on basic insulation only, but which includes an additional safety precaution in that accessible conductive parts are connected to the protective earthing conductor in the electrical installation in such a way that accessible parts cannot become live in the event of a failure of the basic insulation. • Class II equipment: This type of equipment shall include additional safety precautions for the live parts like double insulation or reinforced insulation. This class is further sub divided in the standard as below. 76 Practical Electrical Wiring Standards - AS 3000:2018 • • • Insulation-encased Class II equipment: Equipment having durable and substantially continuous enclosures of insulating material enveloping all metal parts, with the exception of small parts, such as nameplates, screws and rivets, etc Metal-encased Class II equipment: Equipment having a substantially continuous metal enclosure and double insulation used throughout and adopting reinforced insulation wherever application of double insulation is not viable. Class III equipment: In this type, protection against electric shock relies on supply at SELV (separated extra-low voltage - definition follows later) and where voltages higher than SELV are not generated. It usually refers to equipments operating with SELV supply that is considered inherently safe against shocks. Contact, direct (Direct contact): A person getting in contact with a conductor or conductive part which is live in normal service. Figure 1.2 below is the drawing from the standard explaining this definition. Basic protection (protective earthing) is mandatory at these parts. Figure 4.2 Direct contact (Source: Figure 1.2, AS/NZS: 3000 Wiring Rules) Contact, indirect (indirect contact): Contact with a conductive part which is not normally live but becomes live under fault conditions (due to insulation failure or some other cause). Figure 4.3 below shows the possible indirect contact with a live part. Faulty protection (of the appropriate type) is recommended for parts that are expected to face such breakdowns. Figure 4.3 Indirect contact (Source: Figure 1.3, AS/NZS 3000 Wiring Rules) Section 1- Scope, Application and Fundamental Principles 77 • Cord, flexible: Usually refers to a flexible cable but with conductors not exceeding 4 sqmm or 0.31mm diameter and also having not more than 5 cores. • Current, overload (Overload current): An overcurrent occurring in a circuit that is electrically sound. • Current, fault: A current resulting from an insulation failure or from the bridging of insulation. • Current, short-circuit: A fault current resulting from a fault of negligible impedance between live conductors having a difference in potential under normal operating conditions. The fault path may include the path from active via earth to the neutral. • Damp situation: A situation in which moisture is either permanently present, or intermittently present to such an extent as would be likely to impair the effectiveness or safety of an electrical installation that complies with this standard for ordinary situations. Normally refers to locations that are using water or a like substance. • Earthed situation: A situation wherein there is a reasonable chance of a person touching exposed conductive parts and, at the same time, coming into contact with earth or with any conducting medium that may be in electrical contact with the earth or through which a circuit may be completed to earth.. • Earth Fault-loop impedance: The impedance of the earth fault-current loop (active-toearth loop) starting and ending at the point-of-earth fault. • Equipotential bonding: Electrical connections intended to bring exposed conductive parts or extraneous conductive parts to the same or approximately the same potential, but not intended to carry current in normal service. • Exposed conductive part: A conductive part of electrical equipment that—  can be touched with the standard test finger as specified in AS/NZS 3100; and  is not a live part but can become live if basic insulation fails. • Extraneous conductive part: A conductive part that does not form part of an electrical installation but that may be at the electrical potential of a local earth. NOTE: Examples of extraneous conductive parts include the following: (a) Metal waste, water or gas pipe from outside. (b) Cooling or heating system parts. (c) Metal or reinforced concrete building components. (d) Steel-framed structure. (e) Floors and walls of reinforced concrete without further surface treatment. (f) Tiled surfaces, conductive wall coverings. (g) Conductive fittings in washrooms, bathrooms, lavatories, toilets, etc. (h) Metallized papers. • Main earthing conductor: A conductor connecting the main earthing terminal/ connection or bar to the earth electrode or to the earthing system of the source of supply. • Multiple earthed neutral (MEN) system: A system of earthing in which the parts of an installation, required under this Standard to be earthed, are connected to the general mass of earth and, in addition, are connected within the installation to the neutral conductor of the supply system or the PEN conductor. 78 Practical Electrical Wiring Standards - AS 3000:2018 • Protective earthing conductor: An earthing conductor, other than a main earthing conductor, intended to carry earth fault currents and connecting any portion of the earthing system to the portion of the electrical installation or electrical equipment required to be earthed, or to any other portion of the earthing system. • Residual current device (RCD) - A device intended to isolate supply to protected circuits, socketoutlets or electrical equipment in the event of a current flow to earth that exceeds a predetermined value. • Safety service: A system or component that operates to identify an emergency, or is intended to operate during an emergency, and is primarily associated with the safety of persons evacuating a building, fire-fighting operations or fire suppression. • SELV (separated extra-low voltage): An extra-low voltage system that is electrically separated from earth and from other systems in such a way that a single fault cannot give rise to the risk of electric shock. • Switchgear: Equipment for controlling the distribution of electrical energy or for controlling or protecting circuits, machines, transformers, or other equipment. Usually incorporates isolating devices like circuit breaker, isolator, etc. • Touch current: Electric current which passes through a human body or an animal body when that body touches one or more accessible parts of electrical equipment or an electrical installation, under normal or fault conditions (Refer figures 4.2 and 4.3). • Touch voltage: Voltage appearing on when two or more accessible parts are touched simultaneously. • Voltage: Differences of potential normally existing between conductors and between conductors and earth. The voltages are classified as below in AS/NZS 3000.  Extra-low voltage - not exceeding 50V ac or 120 V ripple-free dc.  Low voltage - exceeding extra-low voltage, but not exceeding 1000 V ac or 1500 V dc.  High voltage - exceeding low voltage. Section 1- Scope, Application and Fundamental Principles 79 5.3 Protection for safety (Clause 1.5) The standard identifies three major types of risk associated with use of electricity Viz., • Shock current • Excessive temperatures • Explosions Section 1, AS/NZS 3000 stipulates rules that are to be applied in electrical installations to safeguard the persons, livestock and properties against the above three major risks. We will see the probable reasons for getting exposed to these risks and hazards connected with them. Shock current: It represents the current that can accidentally flow in human bodies and live stock due to either direct contact under normal service or indirect contact under fault conditions, causing fatal and/or major organ failures. Excessive temperatures: The excessive temperatures can cause burns, fires and other injurious effects unless controlled or safeguarded. It is most likely that persons, equipment and materials adjacent to electrical equipment can be subjected to the following harmful effects because of the heat developed by electrical equipment or thermal radiation. • Combustion or degradation of materials • Burns • Impairment of the safe function of installed equipment. Explosions: When electrical equipments are operated in areas where explosive gases or dusts may be present, the sparking associated can cause ignition of surrounding gases or dusts leading to explosions that can cause irreparable damage to all persons and materials located close to such areas. The main remedy or action needed to safeguard against the above hazards is providing suitable control and isolation devices that are proven to defend such hazards and can help in maintenance of electrical equipment, without getting exposed or affected under such hazards. The isolation device can completely isolate the equipment from all electricity sources external to the equipment, so that the main cause (power) of any of the three hazards is removed at the point of hazard. Control devices shall be designed and arranged in such a way to satisfy the following two main requirements • They shall be separate/ independent from the control of other equipment • They can not be unintentionally interrupted by the operation of some other equipment. AS/NZS 3000 recommends the following guidelines to be adopted to ensure safe design of the installation to safeguard the people and installation from these three common hazards of electricity use. 5.3.1 Shock currents Shocks are effects felt by humans and live stock when currents flow through their bodies. Shock currents can flow with direct as well as indirect contacts. The standard recommends the implementation of the following to prevent direct and indirect contacts. Direct contact prevention to safeguard against shock: The electrical equipment and systems shall be provided with either one or any combination of the following methods to prevent direct contact thereby avoiding shock currents. • By providing insulation capable of withstanding the mechanical, chemical, electrical and thermal influences to which they may be subjected in service which can be removed by destruction only (It is to be noted that though Paints, varnishes, enamels 80 Practical Electrical Wiring Standards - AS 3000:2018 • • • or similar products offer some insulation, these are not considered as insulation to protect against direct contact). By providing barriers or enclosures that are provided with adequate degree of protection (IP classification) enclosing the live parts to prevent contact with live parts. The barriers shall be installed such a way that these can not be unintentionally removed except by means of a key or a special tool or an interlocking device that can isolate the live supply before opening the barrier. Barriers and enclosures shall be firmly secured and shall have adequate stability and strength to withstand any appreciable distortion that might be caused by the stresses likely to occur in normal operation, including external influences, in such a way that the required degrees of protection and separation from live parts are maintained and unaffected. By providing obstacles between live parts and the accessible parts. However as per the standard, the obstacles can be acceptable only for installations under direct control or direct supervision of competent persons as means for safeguarding against unintentional contacts with live parts. These are not effective for intentional contacts. By placing the equipment out of reach to prevent direct contact under normal conditions. This is also recommended only for installations under direct control or direct supervision of competent persons. While on this subject, it is once again stressed that RCD’s are not considered to provide basic protection against direct contacts but only a mean to isolate supply after a direct contact initiates an earth leakage current. Protection methods against possible shocks from indirect contacts are basically referred as Fault protection methods and following are the recommended methods for achieving the same. • By means of automatic disconnection of mains supply on the occurrence of a fault that can cause a current flow through a body likely to get in contact with live parts, equal to or greater than the shock current of around 15 to 30 milli-amperes or when the touch voltage exceeds 50 V ac or 120 V ripple-free dc. AS/NZS Rules specify a maximum disconnection time under faults for final subcircuits that supply sockets/ handheld portable equipment for 230/400V applications shall be 0.4 seconds for effective protection against shocks. RCD’s are accepted means to provide the fault protection (against indirect contacts). • By having double or reinforced insulation (Class II equipment) or equivalent insulation so that the flow of fault current passing through a body can be prevented. • By electrical separation of the particular circuit to avoid shock current flow under faults. Live parts of a separated circuit shall not be connected at any point to earth or to another circuit to achieve this protection. • By limiting the fault current that can pass through a body to a safe value lower than the shock current. Section-1 stipulates that automatic disconnection time in 230/400V systems shall be less than 0.4 seconds for final subcircuits that supply the following: • socket-outlets having rated currents not exceeding 63 A • hand-held Class I equipment • Portable equipment intended for manual movement during use. The disconnection time can be extended to a maximum of 5 seconds for circuits other than the above including submains and final subcircuits supplying any fixed or stationary equipment. Separated extra-low voltage (SELV) or protected extra-low voltage (PELV) systems are also accepted as means of providing both basic and fault protection against shocks under some specific conditions like proper segregation from a higher voltage circuits than for which they are rated. More details about SELV and PELV are given in section-2 of the standard and will be covered later. Section 1- Scope, Application and Fundamental Principles 81 5.3.2 Thermal effects Though heat is generated as part of electricity consumption in most of the equipments, the same exceeding acceptable limits is a major hazard to the persons, livestock and the installations. Table 5.1 highlights some of the effects of the temperatures/ burns on human bodies based on the duration. Table 5.1 Effects of higher temperatures on human bodies Skin temperature Time duration Effect on skin 1100 F 6 hours Cell breakdown begins 1580 F 1 second Complete cell destruction 1760 F 0.1 second Curable burn 2050 F 0.1 second Incurable burn Unacceptable thermal effects due to electricity use can be prevented by properly arranging the equipments like keeping them away from external heat sources and also by providing adequate ventilation in the areas where such equipments are being operated. These practices will ensure that design operating temperature of the equipment/ system is never exceeded. Following are some of the factors recommended for reducing the thermal effects from the electricity. Preventing fire propagation: Designing and/or executing an installation shall be carried out in such a way that equipment arrangement inside premises shall NOT • obstruct escape routes, either directly or by the products of combustion; or • contribute to, or propagate a fire; or • attain a temperature high enough to ignite adjacent material; or • adversely affect means of egress from a structure. Prevention of high currents: Providing suitable protection from overcurrent and earth fault current by either limiting such currents and/or ensuring automatic disconnection beyond permissible currents. Prevention of voltage effects: Protection against abnormal voltages due to faults with circuits operating at different voltages and/ or voltages caused due to induction effects. The protection against thermal effects due to voltages is normally achieved by segregation between different voltage circuits and also by providing sensing devices that automatically disconnect on detecting overvoltages. (Protection against overvoltage, like the one originating from lightning or from switching operations, is not a requirement of this Standard). Prevention of induction effects: It is also necessary that disconnected, redundant or unused conductors associated with conductors that run inside the distribution systems/ equipment shall be terminated and protected at both ends in the same manner as is required for live conductors to avoid induction effects due to such unused conductors leading to temperature rise in the systems. 5.3.3 Other safety protection methods AS/NZS 3000 requires that the design and selection of equipment shall also consider the following protection features for the safety of personnel involved with such installations. • Protection against injury from normal and unexpected mechanical movements of equipments, generally by means of emergency isolation switches 82 Practical Electrical Wiring Standards - AS 3000:2018 • 5.4 Protection against external influences like exposure to weather, water, flora, fauna, seismic activity, excessive dampness, corrosive fumes, galvanic action, accumulation of dust, steam, oil, temperature, explosive atmospheres, vibration or any other influence to which the electrical installation may be exposed under the conditions of its use leading to insulation failures, short circuits, etc. Design of an electrical installation (Clause 1.6) The design of the installation covering electrical equipments, accessories and their interconnections shall take care of the following factors. • Shall protect persons, livestock and property from harmful effects caused by the electricity under use • Shall function correctly as intended • Shall connect, operate safely and be compatible with the electricity distribution system, or other source of supply to which the electrical installation is to be connected • Shall minimize inconvenience to the people in the event of a fault • Shall facilitate safe operation, inspection, testing and maintenance of the equipment For reliable, continuous and correct operation during its service life, the equipment design shall take into account the following supply characteristics, as may be applicable: • Nature of supply, ac or d.c • Nature and number of conductors, like Phase, neutral and protective earthing conductors for ac. and equivalent conductors for dc • Nominal Voltage and voltage tolerances. (The usual tolerances applicable for Australia for 230/400 V is +10% to −6% as per AS 60038 and for New Zealand it is 230/400 V +6% to −6% in line with IEC 60038) • Frequency and frequency tolerances (normally +/- 5%) • Maximum current that can be supplied (by the source/system/ interconnecting board). • Prospective short-circuit current (for safe breaking of the circuit under fault conditions) • Protective measures inherent in the system installation, e.g. MEN earthing system • Limits on the use of equipment (Duty cycle, duration, etc) • Harmonic current or other limitations The below factors shall be calculated or alternatively assessed in approved manner / established practices and duly considered in the system design as appropriate to ensure that the installation shall be able to meet its expected performance requirements. • Maximum demand of the total installation in amperes or kW to decide the capacity of conductors, back-up protection, etc • Voltage drop upto the terminals of the equipment so that same can be limited so as not to affect the equipment functioning/ usage During distribution design, it is necessary that every electrical installation shall be divided into a number of circuits so that following objectives are achieved by such arrangements: • To avoid danger and minimize inconvenience in the event of a fault; and • To facilitate safe operation, inspection, testing and maintenance 5.5 Selection and installation of electrical equipment (Clause 1.7) AS/NZS 3000 recommends that the following aspects shall be duly taken into consideration in the selection and installation of electrical equipment to be operated in an installation. • It shall operate in a safe and reliable manner and • It shall be able to perform under reasonably expected abnormal conditions like overload, fault or external influences ensuring that these conditions do not cause a danger like electric shock, fire, high temperature or physical injury to the persons and live stock Section 1- Scope, Application and Fundamental Principles 83 • electrical equipment shall be installed in accordance with the requirements of this Standard and the additional requirements as specified in the manufacturer’s instructions Installation work practice Electrical equipment shall be installed in accordance with safe and sound work practices, including the following: a) Appropriate construction and operating characteristics of equipment to protect against mechanical, environmental or other external influences b) Installation instructions provided by the equipment supplier c) Adequate and safe access or working space is provided to equipment requiring operation or maintenance d) Adequate strength and durability of fixings, fastenings and supports e) Particular needs of the user/operator f) Installation wiring conductors shall be clearly identified to indicate their intended function as active, neutral, main earthing, protective earthing or equipotential bonding conductors Conductors with a green or green/yellow (G/Y) combination core insulation colour or sleeving colour are strictly reserved for identifying the main earthing conductor, protective earthing (PE) conductor, or the equipotential bonding (EPB) conductor. Live conductors shall not be insulated or sheathed with green, yellow or green/yellow combination colours in installation wiring. Exception: In New Zealand only, there is no restriction on sheath colour. g) The polarization of socket-outlets shall be in accordance with the product specification and shall be consistent throughout the installation h) Semi-enclosed rewireable fuses shall not be installed i) Condensation issues—a breathing/pressure equalization valve shall be installed to assist with changes in humidity and drainage of moisture j) Electrical equipment shall be installed to manufacturer’s instructions to ensure that the marked IP rating is maintained The equipments in an installation are generally sourced from different manufacturers based on cost, schedule, availability of features, usage requirements, etc. While doing such selections, it shall be necessary that the selected equipment satisfies the following requirements. • It shall meet the essential safety requirements for low voltage electrical equipment specified by AS/NZS 3820 • It shall be manufactured with the safe design, construction, installation and performance requirements specified by an Australian, New Zealand or Australian/New Zealand Standard that is appropriate and relevant to the type of electrical equipment (as per appendix-A of the standard) • Where an Australian/New Zealand Standard appropriate and relevant to the type of electrical equipment does not exist, it shall meet the requirements of a recognized international or national Standard of another country that is appropriate and relevant to the type of electrical equipment and to the electrical installation conditions in Australia and New Zealand It is to be noted that equipment which bears the Regulatory Compliance Mark satisfies the relevant regulatory requirements for electrical safety and can be presumed to comply with the above stipulations. Regulatory Authorities may also accept other marks or means to determine whether particular equipment satisfies the relevant regulatory requirements for electrical safety. In case of selecting equipments that are expected to be functioning in damp situations, following conditions shall be studied thoroughly before specifying / choosing the equipment for such areas. • Its proven capability to operate safely near or within a damp or wet environment (by established certification and past performance) 84 Practical Electrical Wiring Standards - AS 3000:2018 • • Its capability to ensure the required protection against an increased risk of electric shock in locations due to presence of water or high humidity in these areas; and The adequacy of such protection offered to take care of any consequent damages that may be expected from the presence of water or high humidity It is to be noted that every alteration of, or addition to, an existing electrical installation shall be considered as a new electrical installation and all relevant provisions of this Standard shall be applied to every such alteration or addition from design stage upto selection/ installation. While taking up alterations or additions to an existing electrical installation it shall be ensured that such additions/ alterations shall not bring up the following issues on any portion of the already existing electrical installation, or electrical equipment connected thereto. • Carry currents or sustain voltages in excess of those permitted by this Standard or • Ultimately used in any manner that is not in accordance with this Standard. 5.6 Verification (Inspection and Testing) (Clause 1.8) AS/NZS 3000 recommends the following actions in regard to verification and testing of installations. • It is necessary that all electrical installations including any alterations, additions and repairs to electrical installations shall be inspected as far as practicable prior to being placed in service or use to verify that the installation meets the requirements of this Standard as appropriate. • Precautions shall be taken to avoid danger to persons and damage to property/ installed equipment during inspection and testing. • Where the installation is an extension or alteration of an existing installation, it shall be verified that such extension or alteration complies with this Standard and does not impair the safety or performance of the existing installation in any way. • To verify the correct connection of conductors to protective switching and control devices as part of inspection. Section 8 of the standard sets out requirements for the verification and testing of electrical installations and we will review the same in detail in a subsequent chapter. 5.7 Compliance requirements (Clause 1.9) Compliance with Part 2 of this Standard In Australia only, electrical installations that meet all of the relevant requirements of Part 2 of this Standard are deemed to meet Part 1 of this Standard. Compliance with the requirements of other standards Refer to Clause 7.8 for standards applicable to specific electrical installations and Appendix A for a list of referenced Standards. Additions, alterations or repairs to an existing installation constructed to a Part 1 design and installation solution shall not alter the compliance of the existing installation with Part 1. Repairs to existing electrical installations or parts thereof may be effected using methods that were acceptable when that part of the electrical installation was originally installed, provided that the methods satisfy the fundamental safety principles of Part 1 of this Standard. It is possible that because of some unusual requirements, application or intended use, certain electrical installations or portions of electrical installations may not be able to meet Part 2 of this Standard. However the standard permits use of specific design and installation method for such installations as detailed below, so that compliance question is taken care of. • Such designs shall satisfy the fundamental safety principles of Part 1 of this Standard and Section 1- Scope, Application and Fundamental Principles 85 • • Shall result in a degree of safety from physical injury, fire and electric shock not less than that which, in other circumstances, would be achieved by compliance with the particular requirements of this Standard; and Shall satisfy the other requirements of this Standard as detailed in this Clause. The remaining portions of such installations shall comply with Part 2 of this Standard. If all or part of the design/construction of the electrical installation is not based on the deemed to comply methods in Part 2 of this Standard, this choice must be made by the designer prior to final certification of construction by the person carrying out the construction. It is expected that any departures from Part 2 of this Standard must be formally acknowledged by the owner or operator of the installation. In all above cases, it is essential that the designer shall document the Part 1 design. Such documentation shall be in the English language and clearly identify the following, including. • the owner or operator’s acknowledgment as to any departure from Part 2 of the Standard • any requirements where the design requires specific installation use by the owner or operator of the electrical installation and provide a copy of these requirements to the owner or operator • why Part 2 of AS/NZS 3000 was not adopted • the verification requirements that are required to be undertaken to ensure full compliance with the requirements of the Standard • how compliance with Part 1 of the Standard is being achieved with alternative designs/ features • the verification(s) undertaken to ensure full compliance with AS/NZS 3000, and the results of such verification Such documentation shall be retained by the designer in the office and further a full set shall be kept on-site at the electrical installation in the custody of person having overall responsibility for the installation. All parts of an electrical installation that do not comply with Part 2 of this Standard shall be verified as complying with the specific design and with Part 1 of this Standard prior to being placed in service. Persons undertaking designs that depart from Part 2 of AS/NZS 3000 shall be competent. 5.8 Summary In this chapter we reviewed some of the common terms used/ adopted in the electrical systems that are also referenced in the AS/NZS 3000 The standard identifies shock currents, excessive temperatures and explosions as three major risks associated with electricity use and provides guidelines to be implemented for minimize the hazards due to these risks. Shock currents due to direct contacts can be prevented by use of proper insulation, by providing suitable barriers, by providing obstacles or by keeping the equipment out of reach under normal conditions of use. RCD’s are recommended to protect against shock currents but they are not capable of preventing shock currents. Hazards associated with high temperature risk can be minimized or prevented by proper arrangement of equipments with adequate space around them, by providing protective devices to disconnect the supply/ equipment in quick time in case of high currents and voltage effects that are common sources of high temperatures. It is also essential that personnel in an installation shall be protected against injury from moving equipments. The equipments shall also be protected against external influences like weather, dampness, corrosion, etc. The equipment design shall duly consider the applicable power supply characteristics taking care of probable variations. The distribution system design shall adopt a number of circuits for feeding the 86 Practical Electrical Wiring Standards - AS 3000:2018 various equipments and loads so as to avoid inconvenience due to supply disruptions and also to facilitate safe operation of individual items. While selecting equipments it shall be ensured that they meet relevant standards of AS/NZS as applicable or equivalent international standards. The installation shall adopt sound practices and consider important factors like prevention of external influences/ hazards, adopting manufacturer’s recommendations, ensuring proper polarization of sockets, etc., so that the system can be safely operated without causing any hazards. It is also necessary that the completed installation shall be verified for compliance to standards and tested in line with guidelines given in section-8 of the standard. All part-1 design compliance shall be properly documented and kept as records in the installation for ready reference. In case of any deviations to the standard, the reasons for the same shall also be documented with alternative designs adopted indicating clearly how such alternative designs meet the safety stipulations of the standard. 6 Section 2 – General Arrangement, Control and Protection Section-2 of the AS/NZS 3000 gives the recommendations the control of electrical systems and equipments with proper switchgear and control gear incorporating isolation switches and protective devices to ensure safety for people and properties from the probable hazards during the use of electricity. In this chapter we will discuss the safe practices to be adopted for safe isolation of electrical circuits in case of abnormal conditions and implementation of circuits to facilitate these controls. We will also discuss the main protective devices to be incorporated in the low voltage distribution systems including the need and methods for coordinating these devices for proper isolation of faulty circuits without affecting the healthy systems. The chapter also covers the stipulations given in the standard related to safe layout arrangements, design features of internal components, etc., for electrical switchboards. Learning objectives • • • • • • • • • • 6.1 Arrangement of Electrical circuits and equipments Electrical equipment control requirements Isolation requirements of ac and dc systems Requirements and arrangement of isolation switches Emergency switching requirements Fault protection and protective devices Discrimination and Coordination of protective devices Residual Current devices for protection Protection against abnormal voltages Switchboards and requirements Selection and installation of switchgear and controlgear (Clause 2.1) For proper design, correct construction and safe operation of the electrical installations, it is very much essential to properly select the switchgear and controlgear which protect and control the various circuits and equipments in an installation. Following are some of the important considerations to be taken into account while selecting the Switchgear and controlgear in an installation. • The switchgear shall facilitate control or isolation of the total electrical installation in case of major shutdowns and emergency situations. It shall also be able to achieve the 88 Practical Electrical Wiring Standards - AS 3000:2018 • • • • • 6.2 isolation of individual circuits or individual items of apparatus for safe maintenance, testing, fault detection or repair, as and when needed The switchgear shall be able to monitor and automatically disconnect the main power supply in the event of an overload, short-circuit or excess earth leakage current in the electrical installation or individual circuits being protected It shall also offer protection against failures of equipments and associated systems from overvoltage or undervoltage conditions To achieve these functions safely, the switchgear and controlgear shall be grouped and interconnected as per requirements, enclosed in appropriate manner for protection against external influences and shall be located in such a way to ensure safe and easy access at all times It shall be able to control and protect the circuits and apparatus that are intended to be protected without affecting the other parts of the installation (selectivity) Installed in accordance with the requirements of this Section, and the additional requirements as specified in the manufacturer’s instructions Arrangement of electrical installation (Clause 2.2) To ensure safe operation of different apparatus and equipment in an installation, it is necessary that the electrical distribution system shall be divided into an appropriate number of separate circuits taking into account the following: • Some equipment may be operated independently and some may be operating as a group. For proper segregation of the different circuits, the designer of the system shall identify the relationship between the various equipments including any specific requirements of some equipment to be operated as a group as well as the special needs to be met by the end user of the installation. • Selection of the rating of the circuit components in relation to the load characteristics and operating characteristics of the equipment to be connected in that circuit • The limitations in the system like possibilities of supply failure to critical equipment, overload conditions due to specific operation needs, etc., and the features that are to be added to locate a fault consequent to a circuit failure, for corrective actions • The features to be incorporated in the circuits to help and perform maintenance works, alterations, additions, etc. for specific parts of the installation without a need for interrupting or affecting the supply to other parts of the installation that can still continue to be in service under such works • To ensure that circuits for safety services are separated from the circuits normally used to supply the remainder of the electrical installation, so that these safety services can remain unaffected or controlled independently as appropriate under emergency situations It is recommended to group the circuits of an installation and ensure that the respective groups are separated from each other in such a way that each can be independently controlled with suitable controlgears matching specific characteristics/ load duty cycles. Typical groups of loads can be • Lighting • Socket-outlets • Heating and/or air conditioning appliances • Motor-driven equipments • Auxiliary services, such as indication and control • Safety services Appendix B clause B2 provides recommendation for typical radial distribution arrangement incorporating circuits divided as per the above grouping and each group provided with independent controls/ isolation arrangements at the respective incoming points to get the following benefits. • One circuit only will be shut down (by fuses or circuit-breakers) in case of a fault in that circuit, without disturbing other circuits • Finding the location of the fault is getting simplified Section 2 - General Arrangement, Control and Protection 89 • • Maintenance or extensions to a circuit can be performed by isolating this circuit keeping the remainder of the electrical installation in service Conductor sizes can be optimized to suit the decreasing demand towards the final subcircuits The appendix recommends due consideration of the following design aspects while concluding the circuit arrangements for the various services and loads. • Determine the minimum current-carrying capacity for conductors, dependent upon the method of installation and the external influences • Determine voltage drop requirements for the minimum conductor sizes and increase the same, if conditions demand a lower drop • Determine the automatic disconnection of supply requirements for the type of loads/ circuits • Determine overcurrent and short circuit requirements and include necessary devices coordinated with the chosen conductors As per appendix C of the Standard, each item of equipment that has a current rating in excess of 20 A per phase should be connected to a separate and distinct circuit. Where more than one item of equipment (<20A) is to be connected to a circuit, it is recommended for limiting the maximum number of points in a circuit taking into consideration ALL the following: • Number and type of each load group (lighting, socket-outlets or appliances, etc.) to be supplied in combination from a single circuit • The operating characteristics of the different items of equipment, including periodic and daily duty cycles • Circuit current for the operating conditions and the coordination with cable and protective device ratings to minimize the risk of an overload fault • The likely effects of an overload fault on the circuit, including loss of supply to critical equipment needed for a special function, e.g. security, emergency, medical or critical information and telecommunications purposes The appendix C in the Standard also includes a table (No. C1) (Table A1.1 in appendix A of this manual) which gives guidelines for deciding the number of points for lighting, 10A/15A/ 20Asockets, etc. that can be connected from a subcircuit based on the conductor size, protective breaker rating, etc along with the maximum watts to be limited. It can be noted from the table C1 in the standard that sockets are not permitted in a subcircuit unless the minimum breaker size is 13 amperes and cable size is 2.5 sqmm, exception being a socket-outlet installed more than 2.3 m above a floor for the exclusive connection of a luminaire as a lighting point. While designing the circuits, each single-phase circuit, and each multiphase circuit that requires a neutral conductor for the operation of connected equipment, shall preferably incorporate a separate neutral conductor. However a common neutral conductor may be used for two or more circuits subject to satisfying the following conditions: • The continuity of the common neutral conductor shall be maintained in such a way that it does not depend on connections at the terminals of electrical equipment, including control switches. It means that neutral shall not be connected through terminals or switches as these are likely to get disturbed and isolate the neutral inadvertently during normal service • Final subcircuits shall be controlled and protected by linked circuit breakers or linked switches that cannot break automatically • The neutral conductor shall be marked to identify the associated active conductors in each switchboard • Single appliances with alternative sources of supply (such as a water heater, space heater or air conditioner) shall have one common isolating switch controlling all sources of supply 90 Practical Electrical Wiring Standards - AS 3000:2018 The current-carrying capacity and size of a neutral conductor shall be determined from the currentcarrying capacity of the associated active conductors and shall be installed in accordance with the provisions of Section 3 of the Standard, which are covered in our next chapter. Appendix C of AS/NZS 3000 provides guidelines on deciding the operating loads of different groups, designing the different circuit arrangements and selection of associated protective devices for safe and reliable operation of an installation. These guidelines are informative in nature for design purposes and are covered in a separate appendix of this manual. While planning the system, the maximum demand of power in consumer mains, submains and final subcircuits shall take into account the intended present usage pattern in the installation and the likely future growth by adopting any of the following procedures. • By direct calculations generally considering the recommendations set forth in appendix-C of the standard (Appendix-1 of this book) • By making proper assessment of the duty cycles, occupancy conditions, etc., by competent personnel • By direct measurement during normal service by means of appropriate demand meters recording the demand over definite periods of every 15 minutes • By the current rating / capacity of the breaking device in limiting the demand It is also necessary that operating characteristics of the distribution system like nominal voltage rating, current rating, frequency, temperature rise, duty, and fault level shall all be duly considered while selecting equipments and appliances and putting them into service. In regard to the current rating, the assessment shall consider the normal continuous current as well as the short term maximum current likely to flow in the system including the likely duration of such higher currents for proper operation of the system without interruptions. 6.3 Electrical equipment control requirements (clause 2.3) Electrical installations shall include necessary devices to ensure prevention and/or removal of common hazards associated with the electrical installation in addition to ensuring maintenance of electrically activated equipment. The standard classifies such control devices, according to one or more of the specific functionalities, as noted below: • Isolation (to enable isolation of supply to electrical equipment with features to prevent electrical equipment from being inadvertently energized) • Emergency (to help removal of an unexpected danger during operation in the shortest possible time) • Mechanical maintenance (to enable safe maintenance of the circuits/ equipments without the possibility of getting electrocuted) • Functional (to control a circuit for operational control only and not for any safety reasons.) All the above devices ensure a deliberate action to be carried out in addition to the normal method of operation required to energize a circuit. These deliberate actions include one or combination of the following to prevent inadvertent energization. • Provision for fitting of a padlock in the device used for isolation • Putting up warning tags or notices to caution against energizing the equipment. • Location of such devices within a lockable space or enclosure that cannot be accessed without key and/or special permissions. Following paragraphs give further recommendations related to the incorporation of the main control devices identified above. 6.4 Isolation Isolation is one of the important operations to isolate the source of hazard/ fault in causing further damages during fault conditions, fires, etc. In this part of the standard, stipulations are given on the Section 2 - General Arrangement, Control and Protection 91 practices to be followed for incorporation and proper use of isolation switches in electrical distribution systems for safety, which are covered in the following paragraphs. 6.4.1 Isolation of ac and dc conductors A normal ac circuit uses a minimum of two conductors to provide supply to equipment. Though it may look that breaking any of these conductors could isolate the equipment from being operated, for safety reasons it is necessary to ensure that isolation switches are properly adopted as noted below for the ac circuits. Phase conductors: All active conductors of an ac circuit shall be capable of being isolated by a device used for isolating its supply. No switch or circuit-breaker shall be inserted in the neutral conductor functioning as neutral + protective earth conductor (PEN). Neutral conductor isolation shall be normally avoided in other ac circuits but may be provided subject to taking into consideration of the following conditions • A switched neutral pole may be provided subject to the conditions that the neutral circuit shall not open before opening the corresponding active pole and also that it shall close before the active pole is closed. • Where an item of switchgear is required to disconnect all the live conductors of a circuit, it shall be having provisions to ensure that the neutral conductor cannot be disconnected or reconnected without the respective active conductors also being disconnected or reconnected simultaneously. • A switch controlling a fire pump shall open the neutral conductor also. Earthing conductor of an ac circuit shall never be isolated or switched and shall remain intact under all conditions of service, shutdown and maintenance. It shall also be remembered that fuses shall not be inserted in ac neutral circuits because these fuses may likely open (blow) under fault conditions defeating all the above considerations related to neutral isolation. In regard to the dc circuits it shall be ensured that both the poles of a dc circuit shall be capable of being isolated by a device for isolation, except in cases where one pole is connected to earth at the source end. It shall however be noted that a semiconductor (solid-state) device shall NOT be used for isolation purposes, in both ac and dc circuits. 6.4.2 Requirements and arrangement of isolation switches Devices for isolation of a circuit shall be able to satisfy ALL the requirements stipulated below: • Shall be capable of withstanding an impulse voltage likely to occur at the point of installation, or shall have an appropriate contact gap to withstand the impulse without breaking. • Shall not falsely show that the contacts are open leading to confusions and dangerous situations. • Shall clearly and reliably indicate the positions of the device. (Usually it can be with symbols like ‘O’ for OFF and ‘I’ for ON engraved in the device). • Shall be designed and installed with suitable features that prevent unintentional closure due to external forces/ causes like vibration, etc. • Shall disconnect all active conductors of the relevant supply, when operated. • Shall be readily available near the equipment to be isolated to enable isolation as quickly as possible when needed. In addition, following design requirements shall be met by the isolation switches for specific applications as appropriate. 92 Practical Electrical Wiring Standards - AS 3000:2018 • • Where a device adopted for isolation is not capable of breaking or interrupting normal load current, suitable measures shall be taken to prevent operating of such a device while carrying the current i.e. it shall open or close only when there is no current flowing in the circuit. Suitable measures recommended are means of interlocking its operation with an associated circuit breaker which shall be operated before operating this isolation device or ensuring that these devices can be operated only by authorized persons. Where a switching device is used for isolation, it shall be capable of being secured in the open position and it shall not accidentally go back to the close position, when left in open position. Where switching is NOT required, the isolation can be achieved by adopting any one of the following. • Multi-pole or single-pole disconnectors (off load isolators) • Plugs and socket-outlets • Fuses or removable links • Special terminals that do not require the removal of a conductor. All devices used for isolation shall be clearly identified to indicate the circuit or equipment that they isolate, when operated. 6.5 Main isolation switches (Clause 2.3.3) These are isolation switches that isolate the whole supply of an installation. It is mandatory that the supply to every electrical installation shall be controlled from a main switchboard by means of one or more main isolating switches provided therein to control the whole of the electrical installation. Main switches used for isolation of main supply shall be decided taking into account the following requirements: • The number of main switches, their location, arrangement and identification shall be such to allow for their effective operation (of isolating the supply) in an emergency situation with minimum efforts. • Where multiple supplies are provided, each supply shall be controlled by an independent main switch or switches located on its respective (main) switchboard. • Each part of an electrical installation supplying an emergency system shall be controlled by a main switch or switches and the same shall be separate from those used to control the remainder of the electrical installation. Following are the items that need NOT be controlled by the main isolation switches as that might bypass some controls during operation or disturb some other equipment’s function needed for safety located in the vicinity of the switch. • Consumer mains. • Equipment installed for service protection, control or electricity consumption metering purposes, etc as may be required by an electricity distributor. • Ancillary equipment, measuring devices and associated wiring that are required to be connected to the supply side of the main switch or switches generally confined within the switchboard. • Equipment such as voltage sensing equipment, connected on the supply side of a main switch usually for protection. • Fault-current limiters. • Surge diverters installed to protect consumers mains or main switchboards. Main switches shall be accessible when needed and shall be properly identified to facilitate operation or to avoid accidental operation. The standard specifies that the main switches shall satisfy the following access and identification requirements. • These shall be readily accessible without any obstruction and (handles) shall be located not more than two meters above the ground, floor or a suitable platform to Section 2 - General Arrangement, Control and Protection 93 • • • • • • 6.6 enable easy operation by a person of normal height standing on ground, floor or platform without requiring any other tools. Buildings with multiple occupants are usually provided with metering and distribution starting at a common point in the premises. These premises shall have independent main switch(es) accessible to the respective occupier(s) to isolate their portion of installation when needed by them for attending any works or repairs. Alternatively each occupier shall have ready access to the main isolation switch of the total installation. All such switches shall be legibly marked ‘MAIN SWITCH’ and shall be easily distinguishable from other switchgear components/ switches by means of grouping, colouring or any other recognized methods to ensure easy identification and also enable fast operation under emergency situations. Where more than one main switch is provided, each of these switches shall be marked to identify clearly the electrical installation or portion it controls, to avoid confusions or misjudgment by persons operating the switches. Switches isolating an alternate supply or transferring an alternate supply when operated shall indicate the position of the switch at which the alternative supply is getting controlled. In installations having more than one supply, a prominent notice shall be provided indicating the presence of such other supplies and the location of other main switchboards corresponding to such supplies at each main switchboard, to ensure that all alternate supplies are also easily and correctly located and isolated under emergency conditions. All switches shall be clearly identified to indicate the circuits that they isolate. In case a circuit cannot be isolated in a distribution board or a switchgear assembly for functional reasons, a warning shall be affixed to that board or assembly identifying such circuits and the isolating point. Other main switches (Clause 2.3.4) Though a main switch is normally required where the utility company brings in the main supply, few more additional main switches might be needed in the installation depending on the internal distribution arrangements. Take the case of an outbuilding, an independent structure of a premise that is completely separated from the area containing the switchboard through which the premise receives the supply. The standard recommends that the electrical installation in such an outbuilding shall be considered as a separate electrical installation and provided with a main switch for its installation, if it meets the following conditions. • It has a maximum demand of 100 A or more per phase • It is provided with a switchboard. Further, every submain and final subcircuit exceeding 100 A per phase shall be controlled by a separate isolating switch on the switchboard at which the circuit originates. This requirement may not be applied in locations where fault-current limiters or fuses protect small submains which are teed off from larger submains, e.g. Rising sub mains at each floor. The other items with separate main switches are • A generating set or UPS system used as the alternative supply in an installation. • Appliances and accessories, socket outlets, heaters, capacitors, motors, etc. generally covered in section-4 of the standard. 6.7 Emergency switching (Clause 2.3.5) There are installations which are prone for emergency conditions requiring immediate disconnection of its power supply alone, without disturbing the main supply. The standard recommends adoption of emergency switching for removing an unexpected danger in the following installations. • Machinery. • Conveyors 94 Practical Electrical Wiring Standards - AS 3000:2018 • • • • • • • • • Groups of machines operating simultaneously. Pumping facilities for flammable liquids. Ventilation systems. Certain large buildings, e.g. department stores. Electrical testing and research facilities that use different types of high voltage equipments and devices. Boiler rooms. Large kitchens. Teaching laboratories. High-voltage discharge lighting, e.g. neon signs. Means for such emergency switching shall consist of a single switch isolating the main supply to the equipment or simultaneously operating several items by single action to isolate the particular hazard. The standard recommends that a device adopted for emergency switching shall satisfy the following requirements. • The switches used for systems with motors shall be capable of breaking the full-load current of the relevant parts of the electrical installation being isolated. Since the motors draw very high currents when they get stalled due to some problems or operating conditions, the isolating switch shall be able to break such stalled motor currents as well, where appropriate. • The switch shall be operated manually directly interrupting the main circuit, where feasible. A device operated by remote control such as a circuit-breaker or a contactor also may be permitted as emergency switch, in which case it shall be capable of opening on de-energization (fail safe control) of its coil, or another technique of suitable reliability shall be employed • It shall have means to be kept in latching or being restrained in the ‘OFF’ or ‘STOP’ position unless the hazard is removed for safe supply restoration. • It shall not re-energize the relevant part of the electrical installation upon release of the device i.e. no auto restart feature shall be provided for such switch. • It shall have a manual resetting feature for re-energizing or closing before the electrical equipment can be switched ON again. 6.8 Switches for maintenance (Clause 2.3.6) It is necessary to consider devices for disconnecting the power supply to specific electrically powered items where mechanical maintenance might involve a risk of physical injury, if supply is kept ON. Such maintenance switches shall meet the following normal requirements. • Shall have capability for manual operation; • Shall clearly and reliably indicate the ‘OFF’ position. • Shall be designed or installed in such a manner as to prevent unintentional closure. These switches shall additionally incorporate following facilities to prevent accidental starting of the electrically powered equipment during mechanical maintenance and/or shut down. • locking the switch in the open position or • a means of shutting down the switch in a lockable enclosure or • facilities for the attachment of a warning notice or notices Locking provisions may NOT be provided where such shut down is continuously under the control of the person performing maintenance. Like any other isolation switches, devices used for shutting down during mechanical maintenance shall be marked and located such that they are readily identifiable with its corresponding equipment and are convenient for the intended use. 6.9 Functional (control) switching (Clause 2.3.7) Devices adopted for switching off electrical equipment or part of an electrical installation for ONLY operational reasons but do not involve safety requirements are called functional switches. Typical examples could be a switch that switches off a lamp or an appliance where the main circuit Section 2 - General Arrangement, Control and Protection 95 feeding other loads connected in that circuit may still be operating without getting disturbed. These may be standard ON/OFF switches, semiconductor (solid state) devices, or contactors. Disconnectors, fuses or links shall not be used for functional switching purposes. A single functional switching device may be used to control several items of an apparatus intended to operate simultaneously. Following are the conditions that generally call for using functional switches. • A part of a circuit that may be required to be controlled independent of other parts of the electrical installation, say a pump motor in a residential unit. • In general, any current consuming apparatus requiring control shall be provided with an appropriate functional switching device to control it separately. As per the standard, the functional switches shall meet the following requirements: • They shall be suitable for the duties that they might be required to perform for the particular load or group of loads to be controlled. The type of load (continuous, intermittent, inrush currents, etc) to be controlled, the frequency of operation of the switch (number of times per day, per hour, etc) and the anticipated number of operations (over a normal period) should be taken into account when assessing the onerous duty to be met by such switches. • These switches are not required to switch all active conductors of a circuit, like a lamp switch which isolates only the phase. • Functional switching devices that are used for controlling loads having a significantly low power factor shall be subject to an appropriate de-rating factor, unless device is designed for the same. • Functional switching devices need NOT be identified to indicate the ‘ON’ or ‘OFF’ position except when these are adopted for common appliances say a water kettle. 6.10 Fault protection and protective devices (Clauses 2.4, 2.5) It is necessary to provide appropriate protection devices to protect equipments from common faults expected in the LV distribution systems. This will avoid potential damages to the equipment as well as the surrounding equipments or properties depending on the severity and duration of such faults. Following methods of protection are recognized in this Standard to minimize the faults and its causes, as we have seen in section 5.3.1 of this manual (Protection against shocks due to indirect contacts). • Automatic disconnection of supply. • The use of Class II equipment with double or reinforced insulation. • Electrical separation of live parts without connecting to earth or any other circuit. While the first method requires a monitoring device to open a circuit, the other two methods are construction features of equipments. We will have a brief review on the automatic disconnection devices which are covered in detail in the standard for selection, coordination, etc in the following paragraphs. 6.10.1 Automatic disconnection Automatic disconnection refers to disconnection of equipment or system from source of supply under fault conditions. The automatic disconnection is essentially intended to limit the prospective touch voltage arising between simultaneously accessible conductive parts in the event of a fault. Limiting the touch voltage is generally achieved with following provisions in the LV electrical installations. • Connecting exposed conductive parts of a system to a protective earthing conductor. • Disconnection of supply by a protective device when the continuously monitored current by this device exceeds its pre-set safety value. The most common devices that are employed to provide automatic disconnection of mains under specific fault conditions in low voltage systems are enclosed fuse-links, Miniature circuit-breakers (MCB’s) and Moulded-case circuit-breakers (MCCB’s) that monitor over currents/ short circuit 96 Practical Electrical Wiring Standards - AS 3000:2018 currents and isolate the circuit when these go beyond acceptable limits. In addition, fixed setting residual current devices (RCD’s) are used for protection against shock currents which automatically disconnect supply when earth leakage currents exceed a safe value. These devices are also referred to as residual current circuit breakers, earth leakage circuit breakers (RCCB, ELCB), etc in some countries. While the fuses blow themselves to isolate a circuit, the MCB’s and MCCB’s include thermal and magnetic devices that monitor and actuate their trip coils to open the breaker contacts and disconnect the circuit automatically. The modern MCB’s and MCCB’s are usually provided with electronic protection. While MCB’s and fuses are designed and rated to operate for specific/fixed currents, MCCB’s are mostly provided with adjustable settings to select the current for automatic disconnection purpose. For larger currents in the range of 1000 amperes and above in bigger installations, air circuit breakers are employed up to around 5000 amperes. These are also nowadays provided with electronic trip releases with adjustable settings to protect against over current, short circuit and earth fault having different characteristic curves. Unlike the fuses and breaker types discussed above, the residual current device (RCD) senses the unbalance (i.e. residual difference) between the currents in the phase and neutral conductors of a single phase circuit (or between sum of three phase currents and neutral current in a three phase circuit). These unbalances are normally caused by currents getting bypassed (leaked) to earth through persons coming in contact with the circuit or due to any other internal leakages, which are unacceptable. Once the leakage current exceeds a preset value typically in the order of few milliamperes, the trip coil of the device is actuated by the internal circuit to open the main contacts. Optionally these devices are available with combination of MCB’s for overcurrent and short circuit protections but such protections are achieved by an independent circuit different from the earth leakage monitoring circuit. Figure 6.1 illustrates these different protective devices which are widely used in all parts of the world. Section 2 - General Arrangement, Control and Protection 97 Figure 6.1 Typical low voltage protective devices All these protective devices are connected in series with the circuit being protected and carry the load current under normal conditions. All these devices except RCD have inverse characteristics of current Vs operating time, with curve drawn on logarithmic graph. The RCD is an instantaneous tripping device. Table 6.1 gives the common ranges of currents for which these devices are usually adopted. Characteristics of the fuses, MCB’s and MCCB’s are generally as shown in the figures 6.2 and 6.3. 98 Practical Electrical Wiring Standards - AS 3000:2018 Table 6.1 Common protective devices in LV systems for automatic disconnection Device Over current operation From fraction of amperes to hundreds of amperes Short circuit current operation Upto around 100kA Earth leakage current operation Not applicable MCB’s From fraction of amperes to about 100 amperes Upto around 10kA Not applicable MCCB’s Normally beyond 100 A and generally upto about 1000 Amperes Upto around 50kA Optional ACB’s Above 800 amps Upto around 120kA Optional RCD’s Not applicable Not applicable From 30 to 300mA Time Fuses Current Figure 6.2 Typical fuse characteristics Long delay (bimetal) operation area 100% Instantaneous (electromagnet) operation area Overcurrent Thermal/Hydraulic-Magnetic Operating time Operating time Section 2 - General Arrangement, Control and Protection 99 100% ramp Overcurrent Electronic Figure 6.3 Typical characteristics of MCB/MCCB It is to be noted that semi-enclosed re-wireable fuses shall not be used as means of disconnection due to their unreliability and possibilities of safety hazards while inserting/ replacing blown fuses. 6.10.2 Protection against overcurrent The standard recommends arrangement of overcurrent protection for consumer mains in accordance with one of the following methods. • Providing both short-circuit protection and overload protection at the origin of the consumers mains (at the point of supply) • Providing short-circuit protection at the origin of the consumers mains and overload protection at the main switchboard In addition, an overcurrent protective device or devices ensuring protection against overload current and short-circuit current shall also be placed at the origin of every circuit and at each point where a reduction (distribution transit points) occurs in the current carrying capacity of the conductors. Devices for protection against overcurrent shall not be provided for circuits where unexpected opening of the circuit could cause a danger that might be greater than the danger of overcurrent itself e.g. emergency system supplies, lifting magnets, exciter circuits of machines and the CT secondary circuits. It is preferable to consider alarm provisions in these circuits to caution such faults for taking suitable action by competent personnel in place of automatic disconnection. The overcurrent protection devices have inverse-time characteristics. These shall be rated for interrupting capacity at least equal to the prospective shortcircuit current at the point of installation. The equipment or circuit being protected shall be able to carry the overload current for a specified duration till interrupted by the protective device. Following are the common devices used/ recommended for overload protection in LV distribution systems. • Circuit-breakers incorporating short-circuit and overload releases. • Circuit-breaker + fuse combinations. • Enclosed fuse links and Fuse combination units 6.10.3 Selection of the breaker/ fuse rating Circuit breakers and fuses are the most common protective devices for overload protection in LV systems. The current ratings of these protective devices and the equipment/ cable being protected shall be coordinated to satisfy the following equation. 100 Practical Electrical Wiring Standards - AS 3000:2018 I B ≤ I N ≤ I Z ………………………. 6.1 where, I B = the maximum current or maximum demand for which the circuit is designed I N = the nominal current rating of the protective device I Z = the continuous current-carrying capacity of the conductor The equation 6.1 is apparent for safe design. AS/NZS 60529 specifies effective currents to flow in the respective protective devices to make them operate in conventional time, which are based on the operating characteristics of a typical circuit breaker and fuse manufactured in the country. For circuit breakers, it shall be 1.45 I N (for effective breaking) and for fuses, it shall be 1.6 I N (for fusing) If I 2 is the current of the device to ensure its effective operation, considering equation 6.1, we have, • I 2 ≤ 1.45 × In for a breaker I 2 of a fuse shall be ≤ 90% I Z (based on 1.45/1.6 = 0.9) • I 2 ≤ 0.9 × I Z for fuse Hence, while choosing the nominal ratings I N of the breaker or fuse, following equations shall be considered. • I B ≤ I N ≤ I Z in case of breakers • I B ≤ I N ≤ 0.9 I Z in case of fuses Since the breakers are usually provided with adjustable operating currents, it shall be ensured that the selected breaker can be set for a particular I N applicable for a circuit. As already seen, the overload protection is to be avoided in case where its operation can cause more danger than overload itself. In addition, AS/NZS 3000 stipulates that the overload protective device for equipment or a subcircuit may be omitted in any of the following situations. • If effective protection is provided by a protective device located on the supply side of its origin or the point of reduction in current-carrying capacity. • For a conductor on the load side of a change in current-carrying capacity that is effectively protected by an overload protective device located on the supply side of the conductor OR for a conductor supplying electrical equipment that is not capable of causing an overload current (like an heating appliance) and the conductor has no other branch circuits or socket-outlets connected between the origin of the conductor and the electrical equipment • For installations of telecommunications, control, signaling and the like. 6.10.4 Protection against shortcircuit current Protective devices shall be provided to interrupt any shortcircuit current flowing in the conductors before such current causes danger due to thermal and mechanical effects produced in them and connections. Similar to overload protective devices, short circuit protection device shall be installed at the origin of every circuit and at each point where a reduction occurs in the current-carrying capacity of the conductors. These may also be omitted in case of dangers due to interruptions causing more danger than short circuits itself. These may also be omitted for conductors connecting generators, transformers, rectifiers or batteries to their associated switchboards subject to wiring not placed close to flammable materials and remainder of their circuits are provided with short protection at the switchboards. The time (t) in which a given shortcircuit current (I) will raise the conductors from the highest admissible duty temperature to the limit temperature may be approximated by the following equation. Section 2 - General Arrangement, Control and Protection 101 t= K 2 S2 ………………………. 6.2 I2 where t = short circuit duration in seconds K = factor dependent on the material of the conductor, the insulation and the initial and the final temperatures that decides the maximum short circuit current the conductor can carry for a specific duration (e.g. for copper conductors with PVC insulation, K = 111 for 40°C ambient). S = cross-sectional area of the conductor in mm2 I = effective short-circuit current in amperes (r.m.s) AS/NZS 3000 provides illustrative figures showing the connection positions of overload and short circuit protective devices in typical LV installation circuits. Some of these illustrations are reproduced in figure 6.4 for better understanding of the stipulations. Main supply Main supply Overload and Short circuit Protectoion device Short circuit Protectoion device A Overload and short circuit protective device Overload and short circuit protective device Sub circuits No branch circuits between A, B B Over load protective device Basic Protection in every main circuit and every subcircuit A B Over load protective device Alternate position for overload protective devices Figure 6.4 Typical positions of protective devices (based on AS/NZS 3000) 6.10.5 Protection against Internal arcing Fault currents Internal arcing of a switchboard is one major hazard that shall be prevented by proper protective features. The arcing is possible due to arcing fault currents to the earthed parts while the equipment is in service, or when the device is undergoing maintenance checks during which time the insertion and removal to source of supply can lead to high arcing currents. Arcs created by a fault do not remain stationary. The interaction between an arc and the electromagnetic field caused by the fault current flow will cause the arc to move away from the source point with the arc behaving very much like a conductor placed in a magnetic field. The arc also causes sudden heating of the air in its immediate vicinity causing a violent expansion much like an explosion. This can result in the dislocation of loose components around the fault point and their being thrown like projectiles outwards from the arc. Following are some important effects of arc flash: • Electric arcs produce some of the highest temperatures known to occur on earth: up to 35000 degree Fahrenheit. This is four times the temperature of the sun’s surface 102 Practical Electrical Wiring Standards - AS 3000:2018 • • • The intense heat from the arc causes a sudden expansion of air. This results in a blast with very strong air pressure All known materials are vaporized at this temperature. When materials vaporize they expand in volume. The air blast can spread molten metal to great distances with force Energy released is a function of system voltage, fault current magnitude and fault duration For low voltage systems, a 3 to 4 inch arc can become stabilized and persist for an extended period of time. Figure 6.5 gives the temperature characteristics and effects of arcing fault currents, if allowed to continue for a few cycles without disconnecting the main circuit. Figure 6.5 Typical consequences of arcing fault currents AS/NZS 3000 recommends that protection against arcing currents shall be provided for all larger current (800 A or more per phase) switchboards by automatic disconnection of the system using suitable sensing devices to limit as far as practicable the harmful effects of an internal arcing fault. In addition, the following construction/ installation design features are essential to reduce the probability of initiation of arcing currents. • Additional insulation • Separation methods to reduce the prospect of initiation of a switchboard internal arcing fault between live parts of different phases and components (by having busbars, control units, main power terminals, etc separated from each other using proper insulated barriers with sufficient clearances) • Having proper settings for protection against possible arcing currents by adopting time setting as per equation 6.3 given below The arcing fault current between phases, or between phase and earth, is found to be in the maximum range of around 60% of the prospective shortcircuit current. Refer table 6.2. Section 2 - General Arrangement, Control and Protection 103 Table 6.2 Typical values of arcing fault currents Maximum short circuit current Arcing fault currents 10kA 6.56kA 20kA 11.85kA 30kA 16.76kA 40kA 21.43kA Hence the protection shall be initiated, i.e. pick up of disconnection device shall be done at a current preferably at around 30% of the three-phase prospective fault level to ensure effective protection. Accordingly, to minimize damage to the switchboard, the interrupting time is recommended not to exceed the value obtained from the following equation. t= Ke × Ir I1f.5 ………………………. 6.3 Where, t = clearing time in seconds l f = 30% of the prospective fault current l r = current rating of the switchboard k e = 250 constant, based on acceptable volume damage Protective devices, such as arc fault detection devices (AFDDs), may be used to protect against the effects of arc faults for final subcircuits, including fire hazards. Typical applications include the following: (a) In premises with sleeping accommodation (b) In locations with risks of fire due to the nature of processed or stored materials (e.g. barns, wood-working shops, stores of combustible materials) (c) In locations with combustible construction materials (e.g. wooden buildings) (d) In fire propagating structures 6.11 Discrimination and coordination of protective devices The protective devices take some minimum time to first effectively detect and then to isolate the circuits completely. During such time there is a possibility of heavy currents flowing in these devices till the fault is cleared. The energy that is flowing through these devices and circuits is called let through energy which is calculated with the formula I2t, where I is the let through current in amperes and t is the duration of this let through current in seconds. Since short circuit currents are much more than the normally occurring overload currents, it is very much essential that the characteristics of the protective devices shall be coordinated in such a way that the energy let through by the short-circuit protective device does not exceed that which can be withstood by the overload protective device without getting damaged. Where multiple protective devices are connected in series, it is possible that the same currents are detected or flowing in all the protective devices along the path. The characteristic curves (time Vs current) of these protective devices are typically of inverse time characteristics as already noted. Hence as a standard requirement to ensure selectivity, discrimination between protective devices shall be ensured by having time/current curve of downstream device below that of upstream protective device(s) for a given fault current. During such times it shall also be ensured by proper settings that the other protective device(s) monitoring the healthy circuits shall not operate/ impact their circuits. 104 Practical Electrical Wiring Standards - AS 3000:2018 Figure 6.6 shows the typical curves of different protective devices 1, 2, 3 all connected in a series circuit having device 1 closer to the source and device 2 located between 1 and 3, typically drawn on logarithmic scale. 1 Time 3 2 t1 t2 t3 I Current Figure 6.6 Typical time discrimination for fault current protection by multiple devices in a series circuit It can be noted that the same magnitude of overload current would be carried by all the three devices for a fault after device 3. Here we expect the device 3 to operate earlier so that devices 1 and 2 do not operate once the fault is cleared. This will also ensure that some other circuits connected between 1, 2 as well as 2, 3 are not affected for a fault away from these circuits. For achieving the same, it is necessary that the time of operation of device 1 shall be > device 2 shall be > device 3 for a fault closest to device 3. This is realized by choosing the curve of a device (for the rating or selected setting) matching its location in the circuit and by ensuring these curves do not cross each other in the operating current range of a particular circuit. Consider an example of a system having breakers C1 and C2 in series, with C1 breaker ahead of C2 breaker. The discrimination of protection shall be ensured by following criteria: • For ratings of C2 greater than or equal to 800 A, discrimination shall be provided between overload curves and up to the instantaneous setting of C1 • For ratings of C2 greater than or equal to 250 A and less than 800 A, discrimination shall be provided between overload curves and is recommended up to the instantaneous setting of C1 Discrimination of breakers is deemed to be achieved if; • the overload setting of C1 ≥1.6 × C2, e.g. 1000 A for C1 with 630 A for C2 and • the instantaneous setting of C1 ≥1.6 × C2, e.g. C1=5 ×1000 A with C2=5 × 630 A. • For ratings of C2 less than 250 A, C1 ≥ 2 × C2 In a similar way, discrimination between HRC fuses F1 and F2 (F2 in downstream) in series is deemed to be achieved if; • For times >0.01 s when F1 ≥ 1.6 × F2., e.g. 16 A with 10 A • For times < 0.01 s when F1 ≥ 2 × F2., e.g. 20 A with 10 A (based on the total I2 t of F2 ≤ pre-arcing I2 t of F1) Figure 6.7 shows the typical recommendation given in the standard for circuit breakers C1 and C2 connected in series as explained above. Section 2 - General Arrangement, Control and Protection 105 Figure 6.7 Coordination of breaker characteristics in series (Source: AS/NZS 3000, figure 2.13) Appendix-B, clause B3 of the standard also gives additional details related to the selection criteria for breakers and fuses and the need to match the ratings of protective devices with the circuit being protected. Figure 6.8 gives the typical overcurrent characteristic curves of fuses and circuit breakers which shall be kept below the damage curve of the protected cable, to achieve real protection. Figure 6.8 Typical overcurrent protection of cables (Source: AS/NZS 3000, Figure B2) 6.12 Simplified protective device selection (Appendix C, C3) In the above section, we understood the need for selection of protective devices matching the current capacity of the conductors. AS/NZS 3008.1 series provide a comprehensive set of tables and calculation methods taking into account different cable/conductor types, installation methods and external influences to determine the current carrying capacity of the cables under different conditions. However for many typical and simple applications, the need to refer AS/NZS 3008.1 may not be warranted and an alternative approach may be considered - that is by limiting the current that can be provided to the circuit by the selection of appropriately rated protective devices. Tables C5 and C6 of appendix C provide guidance on the ratings of protective devices for singlephase and three-phase cable applications respectively, for use with cables of cross-sectional area 106 Practical Electrical Wiring Standards - AS 3000:2018 from 1 mm2 to 25 mm2, under a range of installation conditions. Table 6.3 given here is part of those tables for immediate reference. Table 6.3 Protective device ratings for different cable sizes (Source: AS/NZS 3000, Table C6) The settings given in Table 6.3 are for cables used in single phase applications. For settings related to unenclosed cables used in three phase applications, table C7 of AS/NZS 3000 may be referred. It is to be noted that the tables are only for immediate cross checks. Exact installation conditions like grouping, multiple circuits, etc shall be taken into account for further improvements on the selection, where the installation conditions warrant such finer selections. On similar lines, appendix I provides guidance to the ratings of circuit-breakers and existing semienclosed rewireable fuses or plug-in circuit-breakers that may be used to provide protection against overload where alterations, additions or repairs involve the use of existing conductors of an imperial size. These recommendations are as per table 6.4. Section 2 - General Arrangement, Control and Protection 107 Table 6.4 Protective device ratings for imperial size cables (Source: AS/NZS 3000, Table I1) V 75 insulation Two-core sheathed cable of imperial size Installation conditions 1/.044 V 60 insulation CB (Amps) Rewireable Fuse in existing CB or plug (Amps) CB (Amps) Rewireable Fuse in existing CB or plug (Amps) Unenclosed 13 10 10 8 1/.044 Partially surrounded 10 8 8 6 3/.029 Unenclosed 16 12 13 10 3/.029 Partially surrounded 13 8 10 6 3/.036 Unenclosed 20 16 16 10 3/.036 Partially surrounded 16 10 10 8 1/.064 Unenclosed 20 16 16 12 1/.064 Partially surrounded 16 10 13 8 7/.029 Unenclosed 32 20 25 16 7/.029 Partially surrounded 20 16 16 12 7/.036 Unenclosed 40 25 32 20 7/.036 Partially surrounded 25 20 20 16 7/.044 Unenclosed 50 32 40 25 7/.044 Partially surrounded 32 25 25 20 6.13 Residual current devices for protection (Clause 2.6) Requirements for RCD protected circuits in domestic, non-domestic, non-residential and medical installations have been added, and RCD requirements for alterations and repairs clarified in the 2018 issue of the Standard. Figure 6.9 shows the typical principle of an RCD, where an unbalance in the coil of the RCD due to earth leakages leads to tripping of the main power contacts of the device by internal circuitry. RCD is usually provided with a test pushbutton to check its healthiness to operate under real leakages. 108 Practical Electrical Wiring Standards - AS 3000:2018 Figure 6.9 Typical RCD circuit operation with phase and neutral current unbalance It is to be noted that RCD is always an additional protection over and above the overcurrent and short circuit protection recommended. The use of fixed setting RCD’s with a rated operating residual current not exceeding 30mA is recognized as providing additional protection in areas where excessive earth leakage current in the event of failure of other measures of protection or carelessness by users could present a significant risk of electric shock. Reasons for 30mA choice are: • RCD’s with a sensitivity of 30mA will operate before fibrillation of the heart • Use of a 10mA RCD may cause unwanted tripping and needs to be considered only if absolutely needed The nominal rated current of an RCD installed shall be more than the maximum of the following two values to ensure that the device is not allowed to carry beyond its normal rated current. • The maximum demand of the portion of the electrical installation being protected by the device • The highest current rating of any overload protective device on the electrical installation part being protected RCD’s shall be complying with AS/NZS 3190, AS/NZS 61008.1 or AS/NZS 61009.1. In New Zealand, an RCD shall be of a type where tripping is ensured for residual alternating current as well as residual pulsating direct current. In Australia, an RCD shall be of the type that tripping is ensured when the waveform is sinusoidal and not necessary for residual pulsating d.c.. No earthing or protective bonding conductor shall pass through the magnetic circuit of an RCD to avoid false operation and/or nullifying the effects of residual currents. It is necessary to incorporate RCD protection operating at a maximum residual current of 30mA in all types of residential installations for all final subcircuits that supply the following: • one or more socket-outlets • Lighting points (This term includes combination fan, light and heater units, exhaust fans and ceiling sweep fans in an installation) • Directly connected hand-held electrical equipment, e.g. directly connected hair dryers or tools forming part of domestic/ residential installations Section 2 - General Arrangement, Control and Protection 109 In case of non-residential installations, protection by RCD with a maximum residual current of 30mA shall be applied in the following circuits. • Final subcircuits supplying socket-outlets where the rated current of any individual socket-outlet does not exceed 20 A and • Final subcircuits supplying lighting where any portion of the circuit has a rated current not exceeding 20 A and • Final subcircuits supplying directly connected hand-held electrical equipment, e.g. hair dryers or tools Nevertheless, the RCD requirement may be omitted for a socket-outlet or a connecting device specifically intended for the connection of a fixed or stationary electric cooking appliance like a range, oven or hotplate unit subject to meeting the following conditions. • The socket-outlet is located in a position that is not likely to be accessed for general purposes and • The socket-outlet is clearly marked to indicate the restricted purpose of the socketoutlet and that RCD protection is not provided In some of the installations a single RCD may not be sufficient to control multiple loads because of the nature of loads connected in the system and a single RCD might trip the supply to the whole installation. Hence to ensure minimum impact with the operation of a RCD, AS/NZS 3000 recommends the restriction of load points in the final subcircuits as below, mainly for residential installations. • not more than three final subcircuits shall be protected by a single RCD • In case of more than one final subcircuit, a minimum of two RCDs shall be installed Australian installations are normally to be provided with 30mA RCD to ensure human safety against shock currents. However type ‘S’ RCD with a rated residual current in the range 100mA to 300mA may be used as a main switch in a domestic electrical installation basically as additional protection against the initiation of fire caused by current leakage across insulation in addition to the 30mA RCD in the subcircuits for protection against shock currents. Use of RCD with sensitivities BELOW 30mA is not mandatory in Australia. However in New Zealand, additional protection by RCD with a maximum residual current of 10mA is desired for final subcircuits supplying socket-outlets in areas accessible by children like • kindergartens • day care centres for pre-school children • Primary schools In case of additions/ alterations involving complete replacement of circuit protection on a switchboard, additional protection by RCD shall be provided for the final subcircuits supplied from that switchboard. Similarly new socket-outlets that are added to an existing circuit shall also be protected by an RCD. 6.14 Automatic disconnection time (Appendix B) Effective fault protection by means of automatic disconnection of supply is based on disconnecting the mains supply to the affected section by means of a protective device. This method of protection relies on the combination of two conditions: • Provision of a conducting path for circulating the fault current designated as ‘earth fault-loop’ • The interruption of the fault current within a maximum time by an appropriate protective device. This maximum time depends on parameters, such as the highest touch voltage, the probability of a fault, and the probability of a person touching equipment during a fault. 110 Practical Electrical Wiring Standards - AS 3000:2018 Acceptable limits of touch voltage and duration under fault conditions are based on knowledge of the effects of electric current on the human body that we reviewed earlier. AS/NZS 60479 defines two components that permit the establishment of a relationship between the prospective touch voltage that does not usually result in harmful physiological effects on any person subjected to that touch voltage and its acceptable duration. These two components are; • The effect on the human body of electrical currents of various magnitudes and durations flowing through the body and • The electrical impedance of the human body as a function of touch voltage IEC/TR 61200-413 gives the maximum duration that a person may be in contact with an exposed live part of a circuit for a range of touch voltages in the form of a curve (touch voltage Vs acceptable time) under normal conditions that are dry with floor having substantial resistance (Curve L for dry conditions) giving duration in milliseconds. These recommendations are; • It may be possible by a person to sustain a touch voltage of 50 V indefinitely • Same person can not sustain a touch voltage of 100 V and must be disconnected A study was made of the influence of the variations in the different parameters on the value of the prospective touch voltage U T and it is noted that the touch voltage in a subcircuit for a nominal voltage U 0 can be calculated as below. UT = c × U0 × m ………………………. 6.4 (1 + m) The touch voltage in a system is dependent on the two parameters as below • A parameter ‘c’ that represents the proportion of the supply voltage available at the reference point during operation of the protective device, that may vary from a value of 0.6 for a circuit very far from the source to a value of 1.0 for a circuit supplied directly from the source. • A parameter ‘m’ which is the ratio of the cross-sectional area of the phase conductor to the cross-sectional area of the protective earthing conductor in the circuit considered. Using a mean value for c=0.8 and a ratio m = 1, that exist in most of the final subcircuits, the prospective touch voltage U T using equation 6.4 for a 230V circuit can be calculated as equal to 0.8 × 230 × 1/2 = 92 Volts. According to curve L for dry condition referred above, this corresponds to a disconnection time of 0.4 seconds. Accordingly it is stipulated that for a 230 V supply, disconnection time for earth faults SHALL NOT exceed 0.4 second for final subcircuits that supply socket-outlets having rated currents not exceeding 63 A or hand-held Class I equipment or portable equipment intended for manual movement during use. The disconnection time shall not exceed 5 seconds for such of those circuits where it can be proved that people are not exposed to touch voltages that exceed the safe values, during the fault conditions 6.15 Protection against voltage effects (Clauses 2.7, 2.8) 6.15.1 Overvoltage protection Following are the causes for overvoltage that can lead to unsafe situations in an installation, which might be normally difficult to assess quantitatively in advance. • An insulation fault between the electrical installation and a circuit of higher voltage. • Switching operations. • Atmospheric phenomena (lightning). Section 2 - General Arrangement, Control and Protection 111 • Resonant phenomena. Hence it is necessary that external sensing devices would be needed to detect such unforeseen situations to ensure safe/ automatic disconnection. Overvoltage protective devices shall generally meet the following requirements • Overvoltage protective devices shall be reliable and shall not operate at voltages less than or equal to the highest normal operating voltage to avoid unnecessary tripping leading to disturbances under normal operation/ short time fluctuations within tolerance limits. • They shall not cause hazards to persons or livestock while operating. • Transformer windings that operate at different voltages shall be insulated from one another by insulation with a specified test voltage or by conductive screen connected to the protective earthing conductor to ensure automatic disconnection of the supply in the event of a fault. AS/NZS 3000 does not cover requirements of installations for protection against overvoltages due to lightning effects. AS/NZS 1768 shall be referred to decide the need/ type of lightning protection requirements for a building. 6.15.2 Undervoltage protection This protection is not normally mandatory but shall be employed where a drop in voltage could cause damage to an electrical installation or part of an electrical installation or electrical equipment, unless such damage is considered an acceptable risk. Generally undervoltage isolation need not be instantaneous. It shall have suitable time delay to take care of voltage drops during starting of motors and supply voltage fluctuations lasting few cycles. In addition, further time delay may be incorporated to isolate the equipment after detecting undervoltage subject to the condition that the electrical equipment being protected can withstand a brief interruption or loss of voltage without danger. 6.16 Switchboards (Clause 2.9) A switchboard or switchboards is normally provided in an electrical installation for receiving the main supply and for the mounting of switchgear protective devices. A main switchboard shall be provided for each electrical installation system for mounting the main switch or switches when the multiple earth neutral (MEN) system of earthing is used. Switchboard construction generally complying with the relevant requirements of the AS 3439 series is considered to meet the safety requirements of AS/NZS 3000. The standard AS/NZS 3000 stipulates guidelines for the location and the layout arrangements of switchboards in low voltage installations and these recommendations are covered in the following paragraphs. 6.16.1 Location Requirements While locating a switchboard in an installation, it is important to take into account the following considerations. • The switchboard shall be installed in well-ventilated places to minimize the high temperature risks and associated hazards. • It shall be protected against the effects of moisture to which they may be exposed by adopting suitable enclosure, roof, etc. Moisture is generally the direct cause for current leakages, shortcircuits, etc. • The location shall meet the present and future requirements of the premises/ installation by ensuring sufficient space for the initial installation and future replacement of individual items of the control/ protective devices as reasonably anticipated and for undisturbed accessibility to facilitate safe operation, testing, inspection, maintenance and repair expected during normal service life of the switchboard and installation. 112 Practical Electrical Wiring Standards - AS 3000:2018 6.16.2 Layout and exit requirements The layout of switchboards in an installation shall meet the following stipulations of the standard. • Shall be located such that the switchboard and its access is not obstructed by the structure or contents of the building or by fittings and fixtures within the building • Shall be provided with adequate space around the switchboard on all sides where persons have to pass through for safely and effectively operating and adjusting the equipment/ devices provided in the switchboard. • Shall be provided with sufficient exit facilities for the room or enclosed area accommodating the switchboard to enable a person leaving the vicinity of a switchboard under emergency conditions in a safe manner within the shortest possible time. A switchboard is considered to have sufficient access for regular operation and maintenance when it is meeting the following conditions. • A minimum undisturbed space of 600mm around all sides of the switchboard even with the switchgear doors in fully open position and/or with the large internal drawout type circuit breakers, if any, are racked out. • Minimum 750mm wide by 1980mm high openings or doorways for the switchboard room to allow necessary access to the switchboard room or enclosure (approximately 2.5 feet x 6.5 feet). In addition, the following design features shall be adopted for the access/ exit doors of the switchboard rooms. • The doors of switch rooms or rooms dedicated to switchboards shall always open in the direction of exit. The doors located close to the switchboard shall be able to be opened from inside of the room without using any key or tool. • Where more than one door is provided for access to the same switchboard, those doors should be spaced well apart, possibly one at each end and others, if any, equally spaced in between. • Doors of enclosures dedicated to switchboards opening into a passage or narrow access way, due to space limitations, shall have suitable provisions to keep these doors properly secured in the open position so that workers are prevented from inadvertently getting pushed towards the switchboard when they use the access way during the course of their works. Figure 6.10 identifies most of these requirements for a typical installation. Section 2 - General Arrangement, Control and Protection 113 Figure 6.10 Typical clearances to be maintained for switchboards (Source: AS/NZS 3000 figure 2.19) In regard to safe exit facilities for the rooms with switchboards, it is necessary to provide more than one alternative emergency exit path when a switchboard is of the type meeting ANY ONE of the following system design requirements. • It has a prospective short-circuit current of 15 kA or more • It is supplied by a circuit with a nominal capacity of not less than 800 A per phase • It is more than three metres in length. 6.16.3 Exclusion of areas for switchboard locations The standard stipulates to restrict locating the switchboards in the following areas. • Within 1.2m above the ground, floor or platform level. This condition is generally applicable for boards with easily accessible live parts. However this condition may not be considered, if access to live parts is provided with suitable barriers and/or accessed by authorized personnel with proper locking arrangements. • Above open water containers or fixed or stationary cooking appliances unless the switchboard is provided with a suitable enclosure meeting required classifications or it is installed in an exclusive cupboard with close-fitting doors, preventing it from these containers/ appliances • Within close proximity of a bath or shower or above specific zones of a swimming pool or spa pool. Exact distances and zones of installing switchboards in such damp locations are covered in a separate section. • Within a sauna • Within a refrigeration room • In locations adopting sanitization or hosing-down operations, unless the switchboard provided with a minimum degree of protection of IPX6 • Fire exit and egress path locations • Near fire-hose reels or within a cupboard containing a fire-hose reel • Near automatic fire-sprinklers (main switchboards as well as safety services boards) • In hazardous areas as defined in AS/NZS 2430, unless they are meeting hazardous area construction/ certification requirements 114 Practical Electrical Wiring Standards - AS 3000:2018 6.16.4 Switchboard construction Switchboard construction shall meet the following stipulations/ requirements as per the standard. • Live parts shall have protection against easy access/ arm’s reach by means of suitable enclosures and/or barriers, though some exceptions may be permitted in nondomestic installations subject to additional protection and access control to live parts • The switchboard shall be able to withstand the mechanical, electrical and thermal stresses that are likely to occur in the service conditions to ensure unimpeded service • To avoid shortcircuit arcing currents through air between bare live conductors of different potentials, it is necessary to maintain minimum clearances between such parts. All bare conductors and bare live parts of a switchboard shall be rigidly fixed and ensured that a minimum clearance or creepage distance in air is maintained between such conductors or parts of opposite polarity or phase and between such conductors or parts and earth in accordance with the AS/NZS 3439 or AS/NZS 61439 series of Standards and these are not disturbed during the service • Where two or more circuit-breakers are mounted in the same row, the operating means/ handles of these devices shall be orientated in one common direction that would cause its circuit to open or close, without mismatch • Fuse using screw-in carriers shall be connected in such a way that the centre contact is on the supply side of the fuse base 6.16.5 Bars or links Bars or links provided in the switchboards shall have facilities for securely terminating the conductors between metal surfaces. All screws which are in direct contact with conductors on tunnel type terminals shall be of the type designed not to cut the conductor. It is preferable to consider two screws to provide enough contact and strength for tunnel type connections. One screw may be considered adequate if the outside diameter of the screw is not less than 80% of the tunnel diameter. Alternatively, the connections shall be arranged such that the conductor is clamped by suitable ferrules or plates in direct contact with the conductor. Neutral bar/links shall be of adequate current-carrying capacity and shall be located in an accessible position to allow all conductors to be safely connected without moving other nearby cables or isolating the supply to the switchboard. These shall be designed such that the incoming neutral conductor cannot be inadvertently disconnected from the bar or link. Separate neutral terminals shall be provided for the incoming neutral conductor terminating at the switchboard and also for all the neutral conductor(s) associated with each outgoing circuit originating at the switchboard. 6.16.6 Identification Main switchboard and the access rooms/ doors shall be properly identified with legible writing/ engraving giving the names of the switchboards and cautioning about the rooms for taking suitable precautions or to be aware of the hazards while entering. Notices indicating the location of the main switchboard shall be of permanent construction and shall incorporate the term ‘MAIN SWITCHBOARD’ in contrasting colours. Terminals of bars, links, circuit-breakers, fuses and other electrical equipment mounted on a switchboard shall be marked or arranged to identify the corresponding active and neutral connection for each circuit. The terminals for the connection of the MEN link and for the main neutral conductor shall be legibly and indelibly marked at the main neutral bar or link. Some times, the MEN connection may be made at another location such as a substation. In such cases, the location of the MEN connection shall be clearly identified at the main switchboard. Section 2 - General Arrangement, Control and Protection 115 6.16.7 Switchboard Wiring The switchboard wiring shall be designed and installed to withstand any thermal and magnetic effects on the conductors. In case of switchboards are provided with hinged door or where there are provisions to remove switchboard panel covers, all conductors connected to the switchboard shall incorporate the following features. • Have sufficient free length of free cable(s) to allow the panel to be disturbed or moved into a position little away for carrying out any future works, when needed • Have proper arrangements to suitably fix and retain the wires in position without getting unduly stressed or moved at the terminals of electrical equipment when the panel is getting moved or being fixed in its location • Shall be arranged to prevent undue pressure on electrical equipment mounted behind the panel • Wiring shall be installed in such a manner that, in the event of fire, the spread of fire will be kept to a minimum. Where a switchboard is enclosed in a case or surround, any wiring systems entering the switchboard enclosure should pass through openings which provide a close fit. In some cases internal sealing should also be considered to avoid ingress of foreign matters/ dust particles and fire. 6.17 Summary Section-2 of AS/NZS 3000 defines requirements for safe operation of an installation with proper control and isolation of power supply feeding the total installation as well as the faulty circuits depending on the nature of the fault conditions. These are achieved by means of switchgear and controlgear incorporating the suitable devices to monitor fault currents. To ensure proper monitoring, the circuitry of the installation shall incorporate proper grouping of different loads to achieve selectivity in isolation. The switchboard controlling the installation shall withstand all external influences for uninterrupted service with adequate ventilation and safe access arrangements. AS/NZS 3000 recognizes four switching conditions in an installation Viz., isolation, Emergency, mechanical maintenance and functional switching. These switches shall incorporate provisions for pad locking them in OFF position to avoid them getting inadvertently closed when unsafe. Adequately rated isolation switches are required at the main supply receiving point of the installation. Where multiple supplies are involved, each supply shall be provided with a main switch. Additional main switches may be called for in an installation when the power demand extended to an outbuilding is 100A or more per phase. Emergency switches are adopted for motors, conveyors, etc to isolate the supply to the particular load to ensure prevention of possible hazards under some unhealthy situations. The maintenance switches are used to shutdown the power supply to a load to be maintained and to prevent electrocution during its maintenance. Functional switches are used for just controlling individual loads of an installation without disturbing power supply to any other circuit or device. Overcurrent and shortcircuit current protections in LV systems are achieved by using fuses/MCB/ MCCB/ ACB based on the nominal current and/or fault current to be sensed and these devices directly carry the load current under normal and fault conditions. These devices shall be selected and characteristics coordinated to ensure discrimination in isolation. Shortcircuit protection is to be considered at the point of supply while overload devices may be located in the subcircuits. Protection against arcing current faults is needed when the switchboard rating exceeds 800 amperes. These high current boards require proper insulation and internal live parts segregation to minimize the possibility of arcing faults. The standard also provides the recommended settings to be adopted for typical protective devices like circuit breakers and fuses based on the conductor sizes to limit the currents carried by such conductors. 116 Practical Electrical Wiring Standards - AS 3000:2018 The supply disconnection under earth leakages can be achieved by incorporating 30mA sensitivity residual current device in all residential circuits controlling socket outlets, lighting and hand held equipments. It might also be necessary to consider more RCD’s to minimize the disturbances to the total installation. Protection against overvoltage and undervoltage, though not mandatory, will ensure protecting the equipments and installation from the possible influence of temperature effects. It is necessary to consider these protections with some time delay to take care of short time disturbances in the power supply while some big equipment are switched. The rooms enclosing main switchboards shall have exit doors properly arranged based on the size and importance of the boards. It is necessary to ensure provision of barriers, maintaining proper clearances and proper connections of bars, links, terminals, wires, etc within the switchboard for better reliability in its operation. Section 2 - General Arrangement, Control and Protection 117 7 Section 3 – Selection and Installation of Wiring Systems Wiring systems distribute the power for voltage transformation and electricity consumption in electrical installations. These comprise of bare or insulated conductors made of good conductivity materials and routed in associated enclosures, trays, supports, etc. Both underground and above ground wiring system requirements are covered under Section-3 of AS/NZS 3000. In this chapter we will review the types of wiring systems commonly adopted in the LV systems and the recommendations given in the standard for the requirements to be complied by the wiring systems. Our study will also include selection methods of conductor sizes to meet the current capacity and voltage drop constraints of a system. We will also review the recommended guidelines for the installation practices to be adopted for these wiring systems. Learning objectives • • • • • • • • • • 7.1 Types and selection of wiring systems External influences Sizing of conductors based on current capacity Voltage drop considerations in conductor sizing Installation requirements of wiring systems Enclosure of cables Underground wiring systems Aerial wiring systems Cables supported by a catenary Earth sheath return systems Types of wiring systems (clause 3.2) The power supply to an installation from the utility companies and its distribution within the installation are accomplished by means of bare or insulated conductors made of copper or aluminium. The term ‘cable’ is normally used to conductors covered with insulation. With the evolution of distribution systems and advances in technological front, the insulated cables have also undergone many improvements to achieve higher safety and efficiency in transmitting and distributing power. The cables can be classified in many ways, notable being voltage class (High voltage and low voltage cables), End application (Power and control), conductor material (copper, Aluminium, etc), insulation adopted (PVC, XLPE, etc), additional protection offered (armoured, unarmoured, screened, lead sheathed, etc), number of conductors (single core, three core, etc) and so on. Following are the common types of cables used for low voltage applications in Australia with either copper or aluminium as the main conductors. 118 Practical Electrical Wiring Standards - AS 3000:2018 • • • Insulated and sheathed types. The normal insulations adopted for the conductors are polyvinyl chloride (PVC) and cross linked poly-ethylene (XLPE). These cables may be unarmoured types or armoured types with or without additional screen (screen generally adopted for HV cables). The cables are usually coved by an overall outer sheath made of PVC, black being the common colour for power cables, though other colours are possible Mineral insulated, metal sheathed (MIMS) cables adopted in specific applications/ areas prone for high operating temperatures Earthing cables, either PVC insulated or bare Figure 7.1 shows typical construction features of common cables of single core and three core cables used in LV systems illustrating the conductor/ insulation/ armour arrangements. Figure 7.1 Typical cross section of a power cable with single/multiple conductors AS/NZS 3000 classifies these wiring systems based on the installation methods adopted in a location and discusses broadly about the following types of wiring systems for low voltage applications. • Open wiring systems (without enclosure) • Enclosed wiring systems • Supported on catenaries • Supported over insulators (called aerial conductors, mostly bare) Generally catenary type and insulator supported aerial wiring systems are run above the ground. The term Catenary is generally referred for overhead lines supported in cantilever arrangement hanging outside the poles. The catenary types referred in the standard are mainly for systems adopted in LV installations in Australia for indoor as well as outdoor applications while aerial conductors are invariably limited for outdoor use exposed to weather conditions. The open and enclosed wiring systems mostly adopted within installations usually comprise of insulated cables (with exception of earth conductor) and are normally routed as below. • On a surface directly clamped or on cable tray or ladder or in trunking (duct) • On a surface partly surrounded by thermal insulation • On a surface fully surrounded by thermal insulation • Buried direct in the ground and covered by soil Section 3 - Selection and Installation of Wiring Systems 119 7.2 Selection criteria (clause 3.1) The design and installation of electrical wiring systems shall meet the following requirements to ensure high level of safety: • Shall incorporate protection against physical contact with live parts of the system. This can be achieved by covering the wiring systems with durable insulation materials or by placing the live parts out of reach • The selection of the conductor sizes shall meet the current-carrying capacity, voltage drop and other minimum size requirements to provide continuous and reliable service • Further reliability is to be achieved by providing electrical continuity of all interconnections, joints and terminations within the system • The wiring systems shall be adequately supported by properly fabricated supports, suspensions and fixings along their routes, as appropriate • The selection of all materials of the wiring system like cables, trays, enclosures, etc shall meet its intended area of application e.g. fire-resistance, explosion protection, safety services • Shall be protected against mechanical damage, environmental and other external influences by adopting enclosure or other approved means • Installed in accordance with the requirements of this Section and the additional requirements as specified in the manufacturer’s instructions 7.3 External influences (Clause 3.3) Though cables are selected based on application requirements and economic considerations, it is also necessary to take care that they are not affected by exposure to the customary external influences expected in an application. Following are the typical factors these are exposed, which shall be duly considered while selecting and installing the wiring systems for reliable and extended life in any installation. • Ambient temperatures (vary from place to place and time/ seasons) • Heat sources • Water or high humidity • Solid bodies • Corrosion/ Pollution • Mechanical forces • Vibration and other kinds of stresses • Flora/ Fauna • Solar radiation • Hazardous areas • Thermal insulation The materials adopted in the wiring system shall be capable to take care of the expansion/ contraction due to varying temperatures in the ambience during its normal service without getting degraded or disturbed in its inherent characteristics. Following are the standard design ambient temperatures to be considered for the wiring systems while making their selection: • In case of cables running in air, for all methods of installation, reference ambient temperature shall be 40°C in Australia and 30°C in New Zealand. • In case of cables buried direct in the ground or installed in underground enclosures, the same shall be 25°C for Australia and 15°C for New Zealand. If materials of these systems in an installation are likely to face temperatures above 60°C or below 0°C, manufacturer’s instructions shall be followed. Another common issue with the wiring system is the probable presence of heat sources nearby and the standard recommends considering the following alternatives to overcome the influences of such heat sources. • Shielding against the heat source. 120 Practical Electrical Wiring Standards - AS 3000:2018 • • • • • Placing the systems sufficiently away from the source of heat. Selecting a system duly considering the additional temperature rise which may occur due to such exposure. Reducing the current being carried by the conductor ( by choosing little larger size) Local reinforcement or substitution of insulating material. A method equivalent to one or more of those listed in Items (a) to (e). Appendix-H of the standard classifies the types of wiring systems based on their ability to maintain circuit integrity under fire conditions for specified time and mechanical damage of specified severity, similar to IP classification of enclosures. The salient requirements and methods of classification for wiring systems are briefly covered in a separate appendix of this manual. High humidity and entry of water could lead to insulation failures and fault conditions. Hence when wiring systems are installed in humid conditions or in close proximity to water substances, following recommendations shall be considered. • Selection of suitable wiring system that is not damaged by the presence of high humidity or entry of water. • In case water is likely to be collected in the service period including possibilities of condensation on a wiring system (its enclosure), right and proper drainage points shall be provided along its route with provisions for harmless escape. • If a wiring system is prone to face wave action (water currents), additional mechanical protection would be required to overcome its effects. Entry of foreign particle present in the vicinity can also affect the performance of the wiring system if it exceeds permitted limits as accumulation would disturb the free flow of air along the system ultimately leading to poor dissipation of heat. Hence it is necessary to consider suitable provisions to keep away or clearing such accumulation by suitable means. In regard to use of wiring systems in corrosive and polluting areas, the materials chosen shall have sufficient resistance to survive such atmospheric conditions. It is also possible that when dissimilar materials are placed in contact or interconnected, galvanic action can take place corroding the anode part. Similarly there could be some materials which can cause mutual deterioration or hazardous degradation of items in close proximity. The installation shall ensure such materials are kept away and are not in contact with wiring systems including their enclosures/ supports. In a similar way presence of flora and fauna in the surroundings can also affect the performance of the wiring system which shall be avoided or where unavoidable, materials selected shall be able to overcome the probable hazards created by such plants and pet animals. The other possibilities that could affect wiring systems are the mechanical forces during normal service due to external factors or nature of operation of equipments in the area. The wiring systems likely to face mechanical forces shall overcome or avoid their effects by duly considering the following. • Mechanical characteristics of the wiring system to suit and withstand such forces intermittently or continuously. • Selecting the proper location to run the wiring the system which can avoid possibility of exposure to such mechanical forces. • Provision of additional local or general mechanical protection to take care of the possible impacts arising out of such forces. The following practices are recommended for the cable installations to reduce the effects of mechanical stresses due to such mechanical impacts. • Provision of adequate supports either continuously or at appropriate intervals matching the cable weight. • Use of suitable fixings to hold the cable in position without getting damaged. • Ensuring proper connections to match the cable size and its termination ends so that mechanical strains at joints and terminations are kept to the minimum. Section 3 - Selection and Installation of Wiring Systems 121 • • 7.4 Ensuring minimum bending radius limits of cables where applicable. Additional flexibility provisions to take care of any movement or tension during normal use. Sizing of conductors AS/NZS 3000 recommends sizes of conductors adopted in wiring systems to be decided taking into account any or all the following: • Current carrying capacity of the conductor (Normal and short circuit conditions, as appropriate) in line with applicable standards and manufacturer recommendations • Minimum size criteria related to specific circuits • Acceptable voltage drop at the equipment terminals Following paragraphs cover the salient recommendations on these considerations. 7.4.1 Current carrying capacity (Clause 3.4) The current carrying capacity of a cable or conductor is decided by its material, cross section, and the insulation. But in all these cases the basic criteria is the maximum temperature that is allowed in these cables/ conductors while carrying the specific current. The cable selection in Australia and New Zealand are to meet the operating temperature limits as given in table 7.1, while carrying the maximum expected current in the system where these cables are used. These are based on the specific characteristics of the insulation adopted for different types of cables (manufactured in line with AS/NZS 5000 series, AS/NZS 3191, AS/NZS 3808 and AS/NZS 60702.1). Table 7.1 Temperature limits for cables (Source: AS/NZS 3000, Table 3.2) Operating temperature of conductor O C Type of cable insulation Under Normal use Maximum permissible Thermoplastic types V-75 HFI-75-TP, TPE-75 V-90 HFI-90-TP, TP-90 V-90HT 75 75 75 75 75 75 75 75 75 75 Elastomeric types R-EP-90 R-CPE-90, R-HF-90, R-CSP-90 R-HF-110, R-E-110 R-S-150 90 90 110 150 90 90 110 150 Cross-linked polyethylene X-90, X-90UV, X-HF-90 X-HF-110 90 110 90 110 MIMS 100 250 Other types PE, LLDPE 70 70 Generally the ratings as per manufacturers’ recommendations shall be considered in case of variations to the values specified in table 7.1 or in applicable standards. However Polymeric cables with normal operating temperatures below 75°C shall NOT be adopted in Australian and New Zealand conditions. 122 Practical Electrical Wiring Standards - AS 3000:2018 Higher continuous operating temperatures are permissible for bare metal sheathed cables subject to taking into account the following • Suitability of cable terminations and mountings. • Locating the cable away from combustible materials. • Locating the cable away from locations where there are more possibilities for persons touching the exposed surfaces. • Protection against other environmental and external influences. • Minimizing and limiting the temperature rise on the terminals of electrical equipment. Where a single cable is unable to meet the expected current capacity needed, two or more parallel conductors may be permitted when unavoidable. In such cases, the cable selection and installation shall duly consider the following. • Minimum cross-sectional area of each parallel conductor shall be 4 sqmm. • Parallel conductors shall be of same material and same cross-sectional area to ensure equal impedance and current sharing. • These shall have approximately the same length and shall also substantially follow the same route. • Both ends of all the parallel conductors shall be effectively joined by clamping, soldering or other suitable means. • The selected current-carrying capacity of the conductors shall take into account the method of installation and applicable derating factors. • Continuous current rating of each conductor may be selected to be below the overall current to be carried together (due to sharing). However each individual parallel conductor shall be rated to withstand the prospective fault-current available at the point of installation by choosing appropriate cross section and no reduction due to sharing is to be applied for the SC rating. It is also necessary that suitable protective devices coordinated with the continuous currentcarrying capacity of the cables shall be provided upstream of these cables such that the protective devices operate and trip the circuits below the maximum current rating of the cables. (Refer the previous chapter). 7.4.2 Minimum size of conductors (Clause 3.5) AS/NZS 3000 recommends minimum size of conductors to be used for the various low voltage circuits in an installation. Table 7.2 gives the details of the same as recommended in the standard (not applicable for switchboard and ELV circuits). Table 7.2 Minimum size of cable conductors in electrical installation (Source: AS/NZS 3000, Table 3.3) Conductor Type of conductors Purpose Insulated conductors Insulated conductors Insulated conductors Bare conductors Insulated flexible Aerial wiring Aerial wiring Socket outlets Other circuits Control and signal Power/ earthing Power/ earthing Material Copper Copper Copper Copper Copper Copper Aluminium Minimum cross section mm2 2.5 1.0 0.5 6 0.75 6 16 Following are the recommendations in regard to the minimum size of neutral conductors to be adopted and as may be noted, these are mostly interdependent on the main phase conductors. Section 3 - Selection and Installation of Wiring Systems 123 • • 7.4.3 In case of single-phase two-wire circuits, the neutral conductor or conductors of consumers main, submain or final subcircuits shall have a current-carrying capacity not less than the current-carrying capacity of the associated active conductor or the total current to be carried, in case of multiple active conductors. In case of multiphase systems, the neutral conductor of multiphase consumers mains, sub mains or final sub circuits shall have a current capacity of not less than that of the largest associated active conductor. Also the current-carrying capacity of the neutral conductor of a multiphase circuit shall take into account the harmonic currents to be carried (if applicable) which is normally taken as 100% of the maximum harmonics flowing in the system. Harmonics are generated by the use of computers, fluorescent lamps, variable speed devices, etc. Voltage drop considerations (Clause 3.6 and Appendix C) The cable conductors have inherent resistance leading to a voltage drop from source to the equipment terminals, while they carry the currents. The manufacturers and applicable standards normally specify the positive and negative tolerance limits to the operating voltage of equipment for getting long and satisfactory performance. It is necessary that, under normal service conditions, the voltage at the terminals of any power consuming electrical equipment shall be not less than the lower limit specified by the relevant standard and/or manufacturer. Where the electrical equipment concerned is not covered by a standard, the voltage at the terminals shall be such as not to impair the safe and reliable functioning of the concerned electrical equipment. Since it is not possible to limit the current, the only option is to reduce the conductor resistance by increasing its section. It is stipulated that the cross-sectional area of every current-carrying conductor shall be such that the voltage drop between the point of supply (mains) of the low voltage electrical installation and any point in that electrical installation does not exceed 5% of the nominal supply voltage at the mains. However in case the point of supply is the low voltage terminals of a substation located on the premises containing the electrical installation and dedicated to the particular installation, the permissible voltage drop may be increased to 7%. For calculating the voltage drop in a circuit, the maximum current in the conductor during normal operations shall be considered as per below recommendations: • Total of the connected load supplied or Maximum demand of the circuit or Current rating of the circuit protective device at which the installation would trip under faults. • For final sub circuits having distributed load (such as socket-outlets or lighting), half the current rating of the protective device may be used due to diversity factor. • In case of parallel conductors, the maximum current carried by a single conductor under normal current sharing conditions may be considered for calculating the drop Appendix C of AS/NZS 3000, clause C4 provides a table to determine the voltage drop in typical single and three phase circuits based on the formula given in AS/NZS 3008.1 series. The basic formula used in the AS/NZS 3008.1 series for voltage drop calculation in a circuit is Vd = (L × I × Vc ) …………………………… 7.1 1000 Where, V d = Voltage drop on circuit in volts (V) L = Route length of circuit; in metres (m) I = Circuit current (usually maximum demand) in amperes (A) V c = Cable voltage drop per ampere-metre length of the circuit; in millivolts per ampere-metre, (mV/Am) When the voltage drop is expressed in percentage as % V d in terms of the circuit voltage V o in volts, the equation 7.1 becomes, %Vd = (L × I × Vc ) 100 ………………… 7.2 × 1000 Vo 124 Practical Electrical Wiring Standards - AS 3000:2018 Which can be simplified in terms of Am per % V d as below (L × I ) 10 × V0 = % …………………….. 7.3 % Vd VC Using the above formula Table 7.3 provides the values of right hand side of the terms (10 × Vo)/Vc, using the values of Vc from the AS/NZS 3008.1.1 series considering common PVC cable types operating at 75°C for 230V (single phase) and 400V (three-phase) circuits respectively. This table of appendix-C can be used to quickly calculate the voltage drop of any circuit and also to choose a correct cable size based on the permissible drop while adopting these standard cables when current and length are known. Typical worked out examples using this table are also given below. Table 7.3 Reference Table to calculate voltage drop of circuits (Source: AS/NZS 3000, Table C8) Am per %V d Cable conductor size 230V circuits 400V circuits 1 sqmm 45 90 1.5 sqmm 70 140 2.5 sqmm 128 256 4 sqmm 205 412 6 sqmm 306 615 10 sqmm 515 1,034 16 sqmm 818 1,643 25 sqmm 1,289 2,588 35 sqmm 1,773 3,560 50 sqmm 2,377 4,772 70 sqmm 3,342 6,712 95 sqmm 4,445 8,927 Example 1: To decide the minimum size of cable for a permissible voltage drop To find the minimum size of cable for a current of 60 amperes in 230V circuit with a length of 50metres and to limit the voltage drop at 3%, Am of the conductor is = 60 × 50 = 3000 ampere metres So Am for the required 3% drop = 3000/3 = 1000 Select a value, which is above this figure from the table. We note that the PVC cable size for this application shall be 25 sqmm minimum corresponding to 1289 Am per %Vd Section 3 - Selection and Installation of Wiring Systems 125 Example2: To find the likely voltage drop for the selected cable matching minimum current carrying capacity Expected voltage drop for a route length of 100metres in a 400V circuit for a current of 40A: Am of the cable is = 40 × 100 = 4000 ampere metres Considering a size of the cable as 10 sqmm or 16 sqmm that can carry 40 amperes, the corresponding values of amperes per %Vd, for these cables are 1034 and 1643 respectively. Hence for the expected 4000 ampere-metres, the dropFor 10 sqmm cable = 4000/1034 = 3.87 % For 16 sqmm cable = 4000/1643 = 2.43% Depending on the permissible voltage drop, the cable size can be selected. 7.5 Installation requirements of wiring systems The standard provides stipulations for the installation of wiring systems on the following aspects: • Electrical connections • Identification of wiring systems • Cable installation practices 7.5.1 Electrical connections (Clause 3.7) Connection forms an important factor for effective distribution related to receiving supply at a point or feeding power to the equipment. These normally involve conductor to terminal interconnections and the standard recommends following factors to be duly taken care for ensuring good and reliable connections. • Material of the conductor (copper/ aluminium) and its insulation type. • Number and shape of the stranded wires forming the conductor. • Cross-sectional area of the conductor. • Number of parallel conductors to be connected together at a point. • Temperature likely to be attained by the end terminals in normal service such that the effectiveness of the insulation of the cable conductors is not impaired. • Suitable prevention methods to avoid entry of moisture and the siphoning of water through any cable or wiring enclosure. When connecting aluminium conductors, the following unique issues associated with the use of aluminium should be considered: • Removal of the aluminium oxide film getting formed at the conductor termination ends. • The relative softness of aluminium, especially at increasing temperatures during operating conditions. • The different coefficient of linear expansion of aluminium and other metals. • Possible galvanic actions due to contacts with dissimilar metals (Normally equipment terminals may be copper or brass) The following considerations are necessary when connections are executed. • Insulation at ends shall not be removed beyond the required length as needed for termination. When connections are made between insulated conductors, these connection points shall also be insulated with a degree of insulation not inferior to the insulations used for the conductors. Damaged insulation during installation shall be reinstated. • Connections shall be strong enough to avoid getting loosened due to vibrations, etc • Use of mechanical connection devices for the connection of conductors shall comply with standards and these shall be used as per manufacturer’s recommendations. • The stranded conductors shall be retained together by using crimping tools. 126 Practical Electrical Wiring Standards - AS 3000:2018 • • • • • • • 7.5.2 The connections shall not impact any undue mechanical stress on the conductors during installation and service. When soldered connections are adopted, it shall take into consideration the temperature rise and stress under fault conditions, as these can easily dislodge these connections Joints shall be avoided in flexible cords as they are prone for failures during normal use. Ensure that these are always used with cable couplers for joining In case of connections involving Aerial conductors, no soldering connections shall be adopted and these shall take into consideration exposure to Sun, weather conditions, etc All underground cable connections shall be sealed to prevent the entry of moisture at these points. Earthing conductor connections shall be made considering the possibilities of failures and methods implemented to avoid such failures. The improvements can be achieved by independent retention method in case of soldered connections, use of proper screws depending on terminal types, etc. Joints in cables shall be enclosed like using a junction box to provide adequate protection against possible external influences. Identification of wiring systems (Clause 3.8) Installation wiring conductors shall be clearly identified indicating their intended function like active conductor, neutral conductor, earthing conductor or equipotential bonding conductor. It is usual to adopt insulation having specific colours to enable easy identification. Table 7.4 gives the recommended colours of insulation to be used for various services. Colour identification by sleeving or other means, using colours corresponding to those listed in Table 7.4 may be adopted as a means of identification mainly at the termination ends at switchboards, etc., and such sleeving or other means shall be of colour-fast, non-conductive material compatible with the cable and its location. Table 7.4 Insulation colour codes in electrical installation (Source: AS/NZS 3000, Table 3.4) Function of conductors Recommended Insulation colour Protective earth Yellow or Green + Yellow Equipotential bonding Yellow or Green + Yellow Neutral Black / Light blue Active Any colour other than the above combinations of Green, yellow, Green/yellow, black or light blue. Some exceptions for colour identification are permitted for the conductors under the following circumstances/ usage. • Protective earthing and equipotential earthing conductors: In case of aerial bare conductors, screen conductor and limitations in the manufacturing like use of silicon compounds. • Active/ neutral conductors: For insulated multi core cables identification may be done with different means like numbering, lettering, etc and in case of insulated aerial conductors, identification may be done by ribs. 7.5.3 Cable installation practices (Clause 3.9) Section 3 - Selection and Installation of Wiring Systems 127 Wiring systems shall be installed in accordance with the generally accepted safe and sound practices that can protect the electrical installation against mechanical or electrical failure under normal service, wear and tear, as well as under any abnormal conditions that may reasonably be anticipated. Following are some of the important provisions to be considered. • Proper fixing with saddles, clamps, etc at regular intervals to prevent cable sags. • Abrasion protection like use of bushings when passing near metallic surfaces. It is necessary to consider protection against mechanical damages for the wiring systems in the following cases as the systems in these locations are most likely to get disturbed knowingly or unknowingly. • Located in or under the floors • Located above the roofs • Suspended below the ceilings • Concealed in the walls • Below raised floors At locations where the wiring systems change directions along the route, cables of the wiring system shall be bent in a manner that their sheathing or insulation shall not get damaged or stressed. The recommended bending radii for the cables shall be adopted as per manufacturer’s guidelines. Where such guidelines are readily unavailable, it shall be ensured that adopted bending radius is minimum 6 times the cable diameter for unarmoured sheathed cables and minimum 12 times the cable diameter for armoured sheathed cables. In addition to the mechanical protection wiring systems shall be installed in an earthed metallic armouring, screen, covering/ enclosure or protected with an RCD of 30mA sensitivity in the following installations • Systems concealed within 50 mm from the surface of a wall, floor, ceiling or roof • Systems located more than 150 mm from internal wall-to-wall or wall-toceiling corners • Systems fixed in position by either fasteners or passing through an opening in a structural member. • Systems passing through a structural member, or fixed in position, within 50 mm from the face of the supporting member to which the lining or roofing material is attached It shall be noted that insulated, unsheathed cables enclosed in conductive wiring enclosures shall not be installed without short-circuit protection. In case of low voltage track systems following stipulations generally govern. • The complete track system shall be installed so that it is open to view throughout its entire length (not necessarily from one position). • The entry of dust or contamination shall be minimized and the system shall be supported securely in position without sagging or undue stress. It is necessary to consider suitable segregation or adopt double insulation when the wiring systems are run in same enclosure or run very close to other systems/ installations as applicable in the following typical cases to avoid detrimental effects and consequent failures. • Systems of different electrical installations. • Different parts of the same electrical installation. • Circuits of an electrical installation operating at different voltages, such as extra-low voltage and low voltage. • Circuits of an electrical installation supplying different safety services. • Circuits of safety services and the remainder of the electrical installation • Between electrical installations and non-electrical installations, such as gas and water lines. 128 Practical Electrical Wiring Standards - AS 3000:2018 • Between electrical installations and telecommunications/ data cable installations. Following recommendations are to be considered in such cases. • Conductors that form part of different electrical installations shall not be installed within a common enclosure. • Cables of high voltage circuits and cables of low or extra-low voltage circuits shall not be enclosed in the same wiring system. • Wiring systems shall not be installed in the vicinity of services that produce heat, smoke or fumes likely to be detrimental to the wiring system. • Wiring systems shall be suitably protected against the hazards likely to arise from the presence of other services in normal use. A typical segregation arrangement commonly applied with electrical communication cables is as shown in figure 7.2. Figure 7.2 Segregation of LV and communication cable (Source: AS/NZS 3000, Figure 3.8) Selection and installation of wiring systems shall be ensured in such a way as to minimize the spread of fires. Wiring systems, such as conduits, cable ducting, cable trunking, busbars or busbar trunking systems and flush boxes that penetrate elements of building construction with requirements for adherence to a specified fire rating shall be internally sealed to the degree of firerating of the respective element before penetration and shall also be externally sealed. The sealing materials shall be of adequate mechanical stability to withstand the stresses that may arise through damage to the support of the wiring system because of fire and shall also permit thermal movement of the wiring system without reduction of the sealing quality. In a.c. circuits, the eddy current and circulating currents are quite common due to mutual inductance effects with closed metal parts and other energized systems at varying potential values. It is necessary to avoid such unnecessary currents to prevent overheating of cables and wiring systems, associated failures, etc. Following are some of the recommendations to keep off such eddy currents and circulating currents in the installation. • Single-core cables in lead or other non-ferrous metal sheathing may be used for a.c. circuits subject to running them in trefoil formation throughout their entire length except for less than 2 metres at either end for termination purpose. • Where trefoil formations are not possible, the cables shall be placed as near as practicable to each other with the sheathing of the cables bonded at both ends and at intervals not exceeding 30 metres along the cable run, by a conductor having conductivity not less than that of the cable sheath. Section 3 - Selection and Installation of Wiring Systems 129 7.6 Enclosure of cables (Clause 3.10) Insulated, unsheathed cables shall be enclosed in a wiring enclosure throughout their entire length, though it is not mandatory to always install sheathed cables in a wiring enclosure. However where the sheath of a cable is removed for termination, joints, etc., the exposed cores of the cable shall be adequately enclosed. Following stipulations apply for such enclosed wiring systems similar to open wiring systems. • Preventing entry of water • Proper supports of systems and enclosures at such points • Ensuring Mechanical and Electrical Continuity • Adoption of proper Bending radii • Passage for conductors in conduits with bushings and to avoid sharp angle that could fail in due course, etc • Terminations securely anchored to avoid disconnections due to mechanical forces, vibrations, etc • Provision for normal expansions due to ambient and service conditions. • Opening/ access provisions for cable trunking. • Avoiding spread of fire Following are some of the common wiring enclosures adopted in the installations. These shall be chosen to have adequate strength and shall be of adequate size to meet the number, size and weight of cables to be enclosed within them, including provisions for future additions/ alterations. • Steel conduits or other metallic tubing or conduits. • Flexible metallic conduits. • Rigid and flexible non-metallic conduits. • Corrugated non-metallic conduits. • Cable trunking with or without compound filling. 7.7 Cables installed in conduits (Appendix C, clause C6) In LV systems, installing the wires and the cables in metallic/ PVC conduits is the most common practice. Appendix C, clause C6 provides guidelines for the number of cables to be installed in conduits, which is an essential reference while designing the systems. The number of cables that can be installed in a circular conduit is dependent on the size of the conduit vis-à-vis size of the cables. It is also necessary to maintain adequate free space inside the conduits for pulling the cables in them, to take care of the reduction of space available from the circular geometry of the cables and enclosures, which is termed as space factor. The number of cables to be limited in a conduit is given by the following relation. Number of cables per conduit = Internal cross sec tion area of conduit × Space factor …. 7.4 Total cross sec tion area of all cables AS/NZS 3000 recommends the following space factors to be adopted for this purpose. • For one cable in a conduit: 0.5 • For two cables in a conduit: 0.33 • For three or more cables in a conduit: 0.4 Refer to Tables, C10, C11 and C12 of the standard which provide data on the maximum number of cables recommended per conduit based on the equation 7.4 for single core, two core and four core PVC V90 cables used in most of the installations. These tables use manufacturer’s data for cables with standard conduits of bore dimensions for rigid PVC, corrugated and profile wall smooth bore types given in AS/NZS 2053 Parts 2, 5 and 6. The tables are on the assumptions that the conduit is relatively short in length, clear of obstructions and distortions, and quantity and arrangement of impediments, such as bends, is minimized. Where this is not the case, the number of cables given in the tables should be reduced suitably to ensure that the maximum cable pulling tension and bending radius are not exceeded. It is also to be noted 130 Practical Electrical Wiring Standards - AS 3000:2018 that the current carrying capacity of cables in conduits is suitably reduced due to poor heat dissipation which shall be duly considered while selecting the cable sizes. AS/NZS 3008 provides de-rating factors for grouping of cables in conduits. 7.8 Underground wiring systems (Clause 3.11) Where cables are installed underground, they shall meet the following requirements. • Shall be suitable for the environment in which they are placed • Shall have proper protection against inadvertent damage likely to be caused by manual or mechanical excavation works which are the common hazards to such systems. • Shall be provided with suitable warning notices, marking or other acceptable means to minimize the risk of inadvertent damage likely to be caused by manual or mechanical excavation works. The underground wiring systems are broadly classified into three main categories in the standard as noted below. Category A: Where the wiring system is suitable for installation below ground due to its inbuilt characteristics without any further need of mechanical protection. Following are the systems that are recognized to fall under category A. • Cables enclosed in heavy-duty insulating conduit without further mechanical protection. • Cables enclosed in insulating wiring enclosures encased within concrete. • Sheathed cables enclosed in galvanized steel pipe (not standard metal) without further mechanical protection. • Armoured sheathed cables or neutral-screened cables buried direct in the ground without mechanical protection. Category B: Where the wiring system is suitable for installation below ground only when provided with additional mechanical protection for the cable or cable enclosure. Following are sthe ystems that fall under category B. • Cables enclosed in medium-duty insulating conduit with additional mechanical protection. • Sheathed cables buried direct in the ground with extra mechanical protection. Category C: Where the wiring system is laid within a channel chased in the surface of rock and covered with concrete. Any Category A or Category B wiring system that comprises cables not installed in a wiring enclosure shall be laid on a bed of not less than 50 mm thick sand or friable soil free of sharp stone and covered by not less than 50 mm thick of the same material. In case of Category B wiring system, additional mechanical protection shall meet ALL the following requirements. • Shall be placed within 75 mm above the wiring system • Shall be not less than 150 mm wide covering the full system • Shall overlap the wiring system by at least 40 mm on either side The category B systems are to be provided with one or combination of the following features related to such additional protections. • Precast concrete slabs having a thickness of not less than 40 mm and a classification of not less than grade 20 in accordance with AS 3600 or NZS 3104. • Concrete slabs cast on-site having a thickness of not less than 100 mm. • A continuous concrete pour having a thickness of not less than 75 mm. • Fibrous cement slabs having a thickness of not less than 12 mm. • Bricks manufactured specifically for the protection of electric cables. • Polymeric cable cover strip complying with AS 4702. Section 3 - Selection and Installation of Wiring Systems 131 Underground wiring systems shall be installed with a minimum depth including cover and protection as per Table 7.5. The depth shall be considered from the upper surface of the ground or below any poured concrete laid on that surface to the upper surface of the wiring system of a Category A and C systems or to the upper surface of the additional mechanical protection of a Category B system. Table 7.5 Depth of underground wiring systems (Source: AS/NZS 3000, Table 3.6) Location of wiring system Within confines of a building external to a building Covering on the surface of ground above the wiring system Poured concrete of 75 mm minimum Thickness No surface covering or less than 75 mm thickness of concrete Poured concrete of 75 mm minimum Thickness No surface covering or less than 75 mm thickness of concrete Category A Category B Category C 0mm (just below) 0mm (just below) 0mm (just below) 500 mm 500 mm 50 mm 300 mm 300 mm 50 mm 500 mm 500 mm 50 mm The standard gives typical illustrations highlighting these recommendations. For immediate understanding some of these illustrations given in the standard are shown in figures 7.3 to 7.5 here. The note identified in these drawings refers to the sand bedding requirements of the category A and B systems noted earlier. Figure 7.3 Category A installation located below 75mm minimum thick concrete (Source: AS/NZS 3000, Figure 3.10) 132 Practical Electrical Wiring Standards - AS 3000:2018 Figure 7.4 Category B installation located below natural ground (Source: AS/NZS 3000, Figure 3.14) Figure 7.5 Typical Category C installation (Source: AS/NZS 3000, Figure 3.16) Wiring systems installed underground shall be identified by an orange marker tape complying with AS/NZS 2648.1. In order to provide early detection of the presence of underground wiring during excavation work, these marker tapes shall be positioned at approximately 50% of the depth of cover above the wiring system or any additional mechanical protection provided for that system. In case of category C type chased in rock, orange marker tape shall be laid directly on top of the wiring system before the concrete is poured. All underground wiring systems shall be spaced not less than 100 mm from other underground services, though relevant authorities may insist for higher distances also. Typical recommendations of the standard on this requirement are reproduced in table 7.6 here. Table 7.6 Minimum separation between UG services and UG wiring systems (Source: AS/NZS 3000, Table 3.7) Minimum separation to UG LV wiring system Minimum separation of the service line enclosure to LV system earth electrode Water service pipes upto 65mm internal dia 100 mm 500 mm Water service pipes above 300 mm 500 mm Type of Service Section 3 - Selection and Installation of Wiring Systems 133 65mm internal dia 7.9 Saitary drainage 100 mm Storm water drainage 100 mm Gas 100 mm Telecommunication 100 mm 500 mm 600 mm 500 mm ---- Aerial wiring systems (clause 3.12) Following are the typical features considered for aerial wiring systems running above ground in outdoor installations, with copper or aluminium as the material of the conductor. Generally aerial systems may not be allowed by regulatory authorities in areas with dense high bushes due to possibilities of quick spreading of fire. • Hard-drawn bare conductors • polymeric insulated cables • neutral-screened cables • Parallel-webbed, twisted, or bundled insulated cables. It is necessary that the aerial conductors shall be insulated for the following situations: • For any conductor span that is attached to a building or structure except those between and supported by two independent poles or similar independent supports. • For any conductor span running close to a building, building opening or structure within arms reach. • Above swimming pools and areas where sailing craft or irrigation pipes are used. • In areas declared by the responsible Fire Authority as being subject to bushfires, where required by the regulatory authority or the electricity distributor. The minimum size of aerial conductors shall be as follows: • Copper or aluminium conductors installed as aerial conductors shall have not less than seven strands and shall be not smaller than 6 mm2 for copper or 16 mm2 for aluminium. • Aerial steel conductors shall have not less than three strands. Aerial conductors for low voltage systems shall be installed such that clearances from ground, buildings and structures other than public roadways are not less than those given in Table 7.7 and the length of span of aerial conductors shall not exceed the values specified in Table 7.8 for the appropriate type and size of conductor. For more details refer relevant tables of the Standard. Table 7.7 Minimum clearances for aerial conductors (Source: AS/NZS 3000, Table 3.8) Type of aerial conductors Minimum height above buildings, structures, ground or elevated areas Over areas Over roofs Over other Over areas used for roofs and not used used by traffic or structures by vehicles resort vehicles From buildings: Horizontal clearance from walls, etc. Bare live 5.5 m 5.0 m 3.7 m 3.0 m 2.0 m Insulated and 4.6 m 3.0 m 3.0 m 2.0 m 1.0 m 134 Practical Electrical Wiring Standards - AS 3000:2018 unsheathed live Neutral screened cable 4.6 m 3.0 m 2.7 m 0.5 m 1.0 m Table 7.8 Maximum unsupported spans of aerial conductors (Source: AS/NZS 3000, Table 3.9) Type of Service Cross section Maximum span Insulated annealed copper including neutral-screened ≥6 sqmm 60 m Insulated hard-drawn copper including two-, three- and fourcore twisted but excluding neutral-screened 6 sqmm 10 sqmm ≥16 sqmm 40 m 50 m 60 m Neutral-screened cables with harddrawn copper conductors - two conductors - three conductors - four conductors - two, three or four conductors Upto 10 sqmm Upto 10 sqmm Upto 10 sqmm 16 sqmm 40 m 60 m 50 m 60 m Insulated or bare aluminium excluding neutral-screened 16 sqmm ≥25 sqmm 50 m 60 m Aerial bundled cables (aluminium conductor) ≥25 sqmm 60 m The aerial conductors are usually supported on pin insulators above the poles. Pin-type insulators shall not be used for supporting aerial conductors in following situations; instead strain types shall be adopted. • Where the strain tends to lift or otherwise separate the conductors from the insulators • Where the direction of the conductors is changed by more than 30°. Section 3 - Selection and Installation of Wiring Systems 135 Figure 7.6 Typical aerial conductors on poles with pin and strain insulators Any hardware or fittings used in association with the aerial line shall be made of corrosion-resistant material or shall be suitably protected against corrosion, to withstand exposed the weather conditions for providing safe and longer life. The aerial conductors of different voltages and different services shall be adequately spaced to prevent contact with each other under all conditions of sag and sway, quite common in varying temperature conditions. It shall be ensured that the spacing between conductors at supports, measured in any direction shall be not less than the values identified in table 7.9. Table 7.9 Spacing between aerial conductors at supports (Source: AS/NZS 3000, Table 3.10) ≤10 m Spacing for insulated conductors 0.2 m Spacing for bare conductors 0.4 m >10 m upto 25 m 0.3 m 0.5 m >25 m upto 45 m 0.4 m 0.6 m >45 m upto 60 m 0.5 m 0.7 m Span There are many tables available in appendix D of the standard giving minimum sizes of posts, poles and struts for aerial line sizes up to 2 × 4core 95 sqmm aluminium and 4 × 7/3.5 sqmm copper conductors with a maximum total weight of 2.7 kg/m. The appendix in the standard covers details related to the following types of poles and supports. • Timber posts and poles • Square timber struts • Angle iron struts 136 Practical Electrical Wiring Standards - AS 3000:2018 • • • Steel poles Steel square section Fabricated steel poles. The sizes of poles and supports are dependent on the normal loading applied by the tension of the aerial conductors which is a factor of the conductor type, span length between supports and the acceptable design sag. Appendix D, Tables D3 to D12 of the standard shall be referred to select the correct type of poles based on the application requirements. 7.10 Cables supported by a catenary (Clause 3.13) Cables supported by a catenary shall be stranded types with double insulation or the equivalent of double insulation, ensuring suitability for Sun light when employed in outdoor. Following guidelines shall be adopted when designing and installing wiring systems on catenary supports. • The catenary shall provide uniform support • It shall consist of material resistant to corrosion or deterioration like the main wiring system • Shall be adequately and effectively fixed at both ends • Shall be capable of withstanding all mechanical stresses likely to occur in service especially effects of wind or ice • Shall be mounted at a sufficient height above the ground to prevent danger to persons or livestock, or damage to the cable being supported. Cables supported by a catenary wire in indoor shall maintain not less than 100 mm from any moving parts or parts of equipment operating at an elevated temperature. 7.11 Earth sheath return systems (Clause 3.16) The earth sheath return system is one where the copper sheath of a mineral insulated metal sheathed (MIMS) cable is used as both a protective earthing (PE) conductor and a neutral (N) conductor simultaneously as a PEN conductor. As per the standard, copper sheath cables alone may be used as a combined protective earthing and neutral (PEN) conductor and shall be installed taking into consideration of the following. • The sheath shall be of adequate cross-sectional area and conductivity. • The ESR shall be adopted only in electrical installations where the MEN system of earthing is used and shall commence at the location where the neutral and earthing conductors are connected to form the MEN connection. • Where the ESR system is adopted as a neutral and protective earth to electrical equipment, then the neutral and protective earth shall not be combined again to form another ESR system. • The ESR system shall not be installed in hazardous areas. • Conductors used in an ESR system shall have a minimum size of 2.5 mm2. • At every joint in the sheathing and at terminations, the continuity of the earthing conductor shall be ensured by a bonding conductor in addition to sealing and clamping of the external conductor • The resistance of the bonding conductor at joints should not exceed that of the cable sheath. • Two conductors, one for earth and one for neutral shall be separately used at each termination. • Where several cables are associated, e.g. single-core cables used in a multiphase circuit, the cables shall be arranged in trefoil or run close to each other as discussed earlier. • There shall be identification on the switchboard at which the circuit originates to indicate that the circuit is using the ESR system. • No switch shall operate in the neutral conductor of an ESR system. • Only electrical equipment identified as suitable for use in conjunction with an ESR system shall be used. Section 3 - Selection and Installation of Wiring Systems 137 It may be noted that the circuits employing ESR systems are unable to be protected by RCD’s. 7.12 Summary The wiring systems comprise of bare/ insulated cable conductors supported and/or enclosed in suitable covers like trunkings, trays, pipes, etc. Section-3 of AS/NZS 3000 covers wiring systems that may be open type, closed type or supported on catenaries/ insulators. In wiring systems, these types shall be selected and installed to take care of external influences like ambient temperature, heat sources, water, humidity, mechanical forces, corrosion, etc. The ambient temperature for these systems is generally taken as 40 deg C in Australian conditions and 30 deg C in New Zealand conditions. To take care of external forces, the systems shall be properly supported at regular intervals ensuring proper connections, bending radii, etc. The sizing of the conductors in wiring systems shall be based on the current capacity requirements of the circuit and acceptable voltage drop within the installation. In regard to current carrying capacity the maximum operating load of the circuit shall be considered with suitable load factors. It is also necessary to ensure that the minimum size adopted in power circuits is 2.5 sqmm copper for insulated cables, 6 sqmm for aerial copper conductors, 16 sqmm for aerial aluminium conductors, etc. In regard to voltage drop considerations a 5% drop is considered nominal, though in specific cases where the substation is internal to the installation, a 7% drop is accepted. The standard also specifies guidelines to be adopted for electrical connections, proper identification of cables and terminating ends including best practices to be adopted in the installation practices. In case of aluminium connections, it is necessary to take care of the flexibility of aluminium at higher temperature and formation of aluminium oxide. The insulation of the earth cables are generally identified with yellow, Green or their combination. For neutral cables, the standard recommends black or light blue colour insulation to be adopted while for active conductors these shall preferably be brown for single phase and red, white, dark blue for the three phase circuits. Additional mechanical protection and abrasion protection shall be considered depending on cables laid in walls, near metal surfaces, etc. The cable enclosures shall also be installed taking care of bending radii, supports, mechanical protection, etc like bare cables. The Standard defines three classifications of wiring systems for underground applications. Category A is without additional mechanical protection like cables in heavy conduits, armoured cables, etc. whereas category B adopts additional mechanical protection e.g. cables in medium duty conduits, direct buried sheathed cables, etc. Category C type is chased in rock with concrete poured as its covering. In all these underground cable categories, their locations shall be identified with orange tapes above the cables along their paths to caution the presence of cables during excavation. Systems of different installations and different services shall be segregated generally maintaining a minimum clearance of 100mm between electrical and non electrical pipes. The aerial conductors shall be supported with poles and insulators at specified spans based on conductor cross section. These are generally avoided in bushy areas to avoid fire spreads. These are to be maintained at a minimum height of about 2 to 6 meters from ground level depending on the areas above which these are routed. The conductors shall also be spaced with a minimum of 200mm to 700mm between them depending on the type (bare or insulated) and the span adopted. Earth sheath return systems are generally adopted in MIMS cables where the neutral and earth are combined as a single PEN conductor and recommended in MEN systems. These systems shall not adopt switched neutral and can not be protected by RCD’s for leakages. 138 Practical Electrical Wiring Standards - AS 3000:2018 8 Section 4 – Selection and Installation of Electrical Equipment The reliability of electrical systems also depends upon correct selection and installation of equipment and appliances to provide satisfactory and safe service during its life period, without creating problems to the source as well. In section 4 of AS/NZS 3000, recommendations are provided for correct selection and installation of common appliances used in electrical installations. The section briefs recommendations on the socket outlets, lighting systems, heating systems, etc., commonly adopted in low voltage systems. We will also review the recommendations related to selection and installation of major electrical equipments like motors, transformers, etc. Learning objectives • • • • • • • 8.1 Selection and installation criteria Protection against thermal effects Connection of Electrical equipment Requirements for Socket-outlet connections Requirements for Lighting systems Requirements of Cooking appliances and electrical heating systems Basic requirements for major equipments like Electricity converters, Motors, Transformers, and Capacitors Selection and installation criteria (Clause 4.1) In our earlier chapters we reviewed the requirements related to design, construction features and safe practices to be followed for the electrical installations. The electrical equipment operating in such installations shall be selected and installed with features as may be needed to take care of the following to serve their purpose. • Shall be able to function properly under all external influences to which they are likely to be exposed during service life • They shall prevent any adverse effects on the electrical installation during their operation and use • Shall operate safely when properly assembled, installed and connected to supply as per approved specifications, standards and good manufacturing practices • It shall be ensured that there is no danger from electric shock, fire, high temperature or physical injury in the event of reasonably expected conditions of overload, abnormal operation, fault or any external influences 140 Practical Electrical Wiring Standards - AS 3000:2018 While equipments are expected to satisfactorily give the intended service based on the supply characteristics, they shall also be able to function properly under one or more of the following external influences that might be expected in a particular installation. Accordingly the equipments shall have suitable design aspects by incorporating additional means of protection features to effectively protect themselves and the installation against the presence and extent of such external influences. • Mechanical forces, vibrations, etc. • Exposure to adverse weather including rain, snow, ice and ultra violet rays from Sun as applicable when installed outdoor • Presence of water and possibilities of splashing, spraying, submersion or high humidity in the areas of operation • Flora, including vines, weeds, flowers and plants of all types • Fauna, including cats, dogs, horses, cattle, etc. • Excessive dampness and poorly sealed underground cellars, etc. • Corrosive fumes, liquids or polluting substances, particularly those used in a sanitization process associated with the food industry • Galvanic action with dissimilar metals • Accumulation of dust or solid foreign bodies • Steam • Oil • High and low temperatures • Explosive atmospheres (often referred to as ‘hazardous areas’) • Seismic activity (earthquakes and tremors) Following electrical disturbances that might be expected out of the equipment operation shall be assessed and equipments and installation shall be provided with specific protection features to avoid these effects impacting the supply characteristics to other equipments and other installations. • Power factor – High or low • Excessive voltage fluctuations due to abnormal duty cycles and internal characteristics • Severe distortion of current waveforms, like effects of harmonics • Electromagnetic interferences 8.2 Protection against thermal effects (Clause 4.2) High temperature of the installation and equipments can lead to burns, fire accidents, etc., and shall be avoided for ensuring safety and protection to people and properties. Hence following recommendations shall be followed to effectively protect the installation and systems against high temperature effects: • Selection and installation such that temperature characteristics of the installed equipment do not adversely affect itself or the electrical installation feeding it or any other installation in close proximity, whether electrical or not • Provision of adequate ventilation where more heat is expected to be generated in normal operation so that the operating temperatures are maintained well below the rated or specified limits applicable for the installation One of the major dangers associated with the high temperatures is fire. Hence following precautions shall be taken while installing equipments to prevent possibilities of spread of fire in case of abnormal faulty conditions: • Avoid installation in a position where it might cause a fire hazard • Plan the storage of flammable materials suitably • If electrical equipment is expected to attain surface temperatures that would cause a fire hazard to adjacent materials, or expected to cause arcs and sparks, it shall be installed in an enclosure of applicable temperature or with low thermal conductance. Alternatively they shall be screened suitably and kept away at sufficient distance to dissipate the heat. Section 4 - Selection and Installation of Electrical Equipment 141 • • • • Use of flammable or combustible material for enclosures shall be totally avoided. Also ensure that in case of enclosures made of special materials, they meet the service temperature requirements. Electrical equipment, including switches, socket-outlets and other accessories shall be with a minimum horizontal separation of 300 mm and vertical separation of 600mm from any opening of a fire rated wall, ceiling or floor The openings made for electrical equipment installed in fire-rated barriers shall not penetrate beyond 50% of the thickness of the barrier The temperatures of accessible parts of electrical equipment within arm’s reach shall be limited to a maximum temperature as stipulated in table 8.1. Where part of the electrical installation is likely to attain a temperature exceeding these limits, under normal load conditions, shall be guarded so as to prevent accidental contact even if it is for a short period as these could cause burns. Table 8.1 Limits of temperature rise for parts within arm’s reach (Source: AS/NZS 3000, Table 4.1) 8.3 Accessible part Metallic parts Non Metallic parts Operation with hand held 55 deg C 65 deg C Parts intended to be touched but not hand held 70 deg C 80 deg C Parts that need not be touched during normal operation 80 deg C 90 deg C Connection of electrical equipment (Clause 4.3) Following are the recommended or standard types of connections adopted for connection of electrical equipments to source of power supply. In all these cases the source and equipment shall be as close as possible with proper mechanical protection for the connecting cable/ wires; • Direct connection with or without installation coupler • By socket-outlet through a plug usually with flexible cord attached to the equipment • By using connecting device like junction box, ceiling rose or permanent connecting device The equipment wiring forming part of equipment and interconnecting the equipment to the source of supply shall meet the following stipulations: • It shall be as short as practicable. A maximum flexible cord or cable length of 2.5 m is recommended • It shall have a current-carrying capacity not less than the maximum load of the connected appliance or luminaire. The minimum cross-sectional area of 0.75 mm2 for flexible cords is recommended, other than those specified for portable or hand-held appliances and luminaires • These shall be protected against short-circuit with fuses, etc • In case of metallic or conductive enclosures, these shall include a protective earthing conductor of suitable cross-sectional area that will ensure operation of the circuit protective device, in the event of a fault to earth, without damage to the protective earthing conductor 142 Practical Electrical Wiring Standards - AS 3000:2018 8.4 Socket-outlets (Clause 4.4) Socket outlets are common power distribution devices in any installation. As you might have come across, the socket outlet construction and voltage ratings differ in various countries as per local practices and distribution voltages. Figure 8.1 shows some of the different models of socket outlets used in many countries including Australia and New Zealand. Figure 8.1 Typical socket outlets and matching plugs in LV systems Socket outlets require matching plugs to ensure safe and reliable connection. The Standard requires the following minimum features to be ensured for these outlets: • Shall have their voltage conspicuously marked. This is normally engraved during manufacture • The socket outlets shall adopt different construction features to ensure plugs or equipments of different voltages are not connected to a particular voltage rated sockets. The construction shall prevent insertion of an extra-low voltage plug into a socket-outlet connected to a circuit of greater than extra-low voltage. AS/NZS 3112 contains a specific plug and socket-outlet arrangement recommended for ELV applications. • The socket and plug connections shall incorporate protection against contact with live pins of plugs, when inserted or during equipment operation • Insertion and removal of plugs shall not cause damage to the equipment cord due to improper matching • The plug insertions shall exactly fit into the outlets and the connections shall ensure additional protection against touching/ coming in contact with the pins of plugs by that might not be fully inserted into the socket outlets (e.g. in areas frequented by children) • All sockets shall be provided with an earthing contact As an additional safety, it is preferable to consider the following for the socket installation to avoid accidental contacts and shocks. • Using recessed type socket-outlets • Using plugs with insulated pins • Placing the socket-outlets out of reach Section 4 - Selection and Installation of Electrical Equipment 143 The standard recommends following to be taken care in specific conditions of installation of outlets: • Shall be protected from entry and accumulation of dust and water where these outlets are provided on floors or horizontal planes • Where outlets are installed within 75 mm of a floor, the corresponding plug shall be withdrawn in the horizontal plane • The plugs shall not become loose or malfunction due to gravity, vibration or the weight of the flexible cord or cable • Where the outlets are provided for the connection of a fixed or stationary appliance or a luminaire that is not readily accessible, the socket-outlet shall be securely fixed to a structure or support to ensure that no mechanical strain is placed on the installation wiring connections when inserting or removing the plug to the outlet • The requirements related to socket outlets in damp and wet areas will be covered in a subsequent chapter • Where socket-outlets are installed in building surfaces that are required to provide fire-resistance or acoustic properties, measures shall be taken to ensure that these properties are maintained Each socket-outlet shall be individually controlled by a separate switch that complies with either AS/NZS 3133, AS/NZS 60669.1 or AS 60947.3 and shall switch ON/OFF all active conductors. The switch shall have a current rating, at its operating voltage, not less than the current rating of the socket-outlet it controls. A maximum of two outlets are permitted to be controlled by a switch subject to the outlets being adjacent to each other. In such cases, the current rating of the switch shall be not less than the total current rating of the two socket-outlets or the current rating of the overcurrent protective device on the circuit; whichever is less. Each switch operating a socket-outlet shall be as close as practicable to the socket-outlet and shall be clearly marked to indicate the socket-outlet(s) or the connected electrical equipment that the switch controls. In specific cases, where the switch is located little away from the socket-outlet it shall be installed in a convenient and readily accessible position as close as practicable to the socket-outlet; and both the switch and the socket-outlet shall be provided with legible, indelible and uniform labels indicating their relationship. Such markings are not mandatory where the socket-outlet is located more than 2.5 metres above the ground, floor or platform level provided for the connection of a specific lamp, luminaire or appliance and which is not accessible for general use. Polarization of sockets is important for safe use with due consideration for the following: • Where socket-outlets of the same type form part of an electrical installation the order of connection of the socket-outlets shall be the same • All socket-outlets for three-pin-flat pin plugs shall have earth, active and neutral in a clockwise direction, when viewed from the front of the outlet 8.5 Lighting equipment and accessories (Clause 4.5) This part of the section covers specific requirements related to lamp holders which are normally used for incandescent lamps (now increasingly fitted with compact fluorescent lamps) and luminaires with specific types of lamps. Requirements for the safe installation of recessed luminaires have been enhanced, and an updated list of luminaire classifications added in the 2018 issue of the Standard. The lamp holders shall be located to minimize the risk of direct contact with live parts of a lampholder when the lamp is removed or replaced and also to avoid mechanical damage to the lamp or lamp-holder. Lamps, luminaires and their associated ancillary gear shall be so installed as not to cause undue temperature rise, ignition or deterioration of the materials on which they are mounted. 144 Practical Electrical Wiring Standards - AS 3000:2018 The luminaires shall be made of materials that are rated with the temperatures expected in the areas of operation. Following additional protections are recommended where lamps are operating close to flammable materials: • The lamps shall be suitably shielded by a shade, reflector, guard or enclosure to prevent contact with the hazardous material • Some lamps such as spotlights generate heat in the illuminated surface due to their basic principle of operation. These kinds of lamps shall be separated by such a distance that the material will not attain excessive temperature. Table 8.1 gives the minimum distances to be maintained in such cases where information is not provided by the manufacturer. Table 8.2 Minimum distances of lamps to flammable materials (Source: AS/NZS 3000, Table 4.2) Lamp Rating ≤ 100 Watts Minimum distance to flammable material 0.6 m > 100 and upto 300 Watts 1.0 m > 300 watts 1.8 m Recessed type luminaires are increasingly used in air conditioned modern installations. In case of adopting such luminaires, the temperature rise at the rear of a recessed luminaire shall be limited to prevent damage to adjacent materials and to minimize risks of fire. These shall be ensured by employing luminaires certified for such applications or by providing fire resistant enclosures. It is also necessary that such recessed luminaires and their auxiliary equipments are installed to facilitate sufficient cooling air movement through or around the luminaire so as not to impair the thermal insulation or other material, common in such installations. Where thermal insulation is of a type that is not fixed in position, e.g. loose fill, a barrier or guard constructed of fire-resistant material, these luminaires shall be provided and secured in position to maintain the necessary clearance. Figure 8.2 gives minimum clearances to be maintained for recessed type luminaires based on the type of lamps used. Section 4 - Selection and Installation of Electrical Equipment 145 Figure 8.2 Minimum clearances for recessed luminaires (Source: AS/NZS 3000, Figure 4.9) Recessed luminaires are classified as follows by AS/NZS 60598.2.2:2016, Appendix ZZ: (a) Non-IC luminaire A recessed luminaire (b) Do-not-cover luminaire (c) CA90 luminaire (d) CA135 luminaire (New Zealand only) (e) IC luminaire IC-4 luminaire 146 Practical Electrical Wiring Standards - AS 3000:2018 Cooking appliances and heating systems Electricity is used for generating heat for the functioning of cooking appliances, water heaters, room heaters, etc. Following paragraphs highlight some of the important stipulations covering these appliances and heaters. 8.6.1 Cooking appliances (Clause 4.7) This is generally a fixed or stationary cooking appliance having an open cooking surface incorporating electric heating elements like cooktop, deep fat fryer, barbecue griddle, etc. These appliances shall be provided with a switch operating in all active conductors of the power supply to appliance. The switch shall be mounted close to the appliance in a visible accessible position. The switch should be mounted within 2 metres of the cooking appliance but not on the cooking appliance. This requirement does not apply to enclosed cooking appliances such as wall ovens, microwave ovens and grills. In New Zealand, a cooking appliance shall be connected to the electrical installation wiring by a socket-outlet or by a coupler having suitable current rating. Requirements for cooking appliance switching devices are clarified in issue 2018 of the Standard for improved safety outcomes. 8.6.2 Hot water and steam appliances (Clause 4.8) All appliances producing hot water or steam normally operate with thermostat controlling their functions. These appliances shall be additionally protected against overheating by means of an appropriate non-self resetting device, functioning independently of the thermostat. Every unvented water heater shall be installed in such a direction that the pressure relief devices and the protective device terminals are readily accessible for operation, inspection and adjustment, as may be needed. The over temperature protection fitted to unvented water heaters shall operate directly in the circuit wiring to the heater elements and shall NOT be arranged for control through relays or contactors. These shall also be provided with an independent isolating switch in addition to any automatic switch incorporated in the heater structure and the isolating switch shall be installed on or adjacent to the water heater or on the switchboard at which the water heater final subcircuit originates. 8.6.3 Room heaters (Clause 4.9) These are normally installed permanently as one or multiple units in applicable rooms. All room heaters shall have the following provisions to ensure safe operation. • An individual isolating switch is a must for each room heater or for controlling each group of room heaters • The isolating switch shall be installed in a readily accessible position in the same room or just adjacent to its room entrance or on the switchboard at which the room heater final subcircuit originates 8.6.4 Heating cable systems (Clause 4.10) Cables for electric heating systems may be laid in floors and ceilings. These cables shall be of the appropriate type meeting such heating applications. While installing electrical heating cables, following requirements shall be met. • Shall not be in contact with flammable materials • Shall be completely and adequately embedded in the substance they are intended to heat • Shall not suffer any detrimental effect due to flexing or movement of the substance in which they are embedded Section 4 - Selection and Installation of Electrical Equipment 147 The heating cables shall also be provided with separate functional & isolation switches similar to the room heaters. All heating cables shall be provided with following additional safety protection features. • RCD with a fixed rated residual current not exceeding 30 mA • Earthing of all conductive covers or where the floor heaters are without a conductive covering, an earthed metallic grid with a spacing not exceeding 30 mm shall be provided above the under-floor heating cable • Adequate mechanical protection to prevent damage • Suitable signs and identification cautioning their existence 8.1 Electricity converters (Clause 4.12) These are basically electrical devices that convert the a.c. to d.c. or some stabilized form using electronic circuits or rotary equipments. The converters covered by this standard are: • Uninterruptible power systems (UPS) • Semiconductor power converters (and inverters) • Voltage stabilizers • Motor-generator sets • Rotary converters Figure 8.3 Static UPS-General configuration Figure 8.4 Rotary converter system 148 Practical Electrical Wiring Standards - AS 3000:2018 It is recommended to refer relevant standards applicable for selection and installation of specific converters like AS/NZS 62040 series for UPS, AS 3011 for batteries, etc. The Wiring rules specify following as the minimum safety requirements to be complied in installations using such converters. • The converted supply shall be controlled by a manually operated isolating switch, or switches, at the output of the converter, or at the switchboard to which the output is connected, and shall be located adjacent to the converter equipment • Each electricity converter shall be controlled by switches or devices suitable for starting and stopping the converter. Where there is more than one switch or device for this purpose, they shall be grouped together and shall be clearly identified. • An electricity converter shall be so arranged that it cannot supply energy upstream of the point of connection to the installation (reverse feeding) either directly or indirectly. This may be achieved with suitable components or interlocking arrangements. All converters shall be provided with overcurrent protective devices which shall be located as close as practicable to the output terminals of the electricity converter. The unprotected interconnecting conductors shall never exceed 15 metres in length. Such interconnecting conductors shall be covered with metal or non flammable material. Electricity converters, particularly static converters, such as UPS, shall be arranged to ensure that the continuity of the neutral conductor to the load is not interrupted during bypass or maintenance switching. The output of an electricity converter shall be provided with the same type of earthing system used for the associated electrical installation. Harmonic currents are common in installations adopting converters. Where an electricity converter is intended to operate in parallel with a network or other source, circulating harmonic currents shall be limited so that the current-carrying capacity of the conductors is not exceeded. Such harmonic currents are normally limited by use of filters or suitable impedance in the converter circuits. The battery installations can produce harmful acids that could corrode the floors and nearby materials and it is necessary to ensure proper precautions to avoid spillages and to provide acid resistant tiles where needed (These requirements are getting reduced with sealed types increasingly used in modern installations). Similarly these are also susceptible to release gases and suitable protections shall be needed to ensure safety to people and properties in such battery installations. 8.2 Motors (Clause 4.13) Every motor functions. • • • in an installation shall be provided with a switching device to give the following To start and stop the motor Emergency stopping Isolating the motor for mechanical maintenance It is generally possible to achieve all the above functions with one switch. In certain installations, one switch may be controlling a group of motors connected within a system like a split air conditioner unit. It is not mandatory to have such switches where the motors are part of the appliances or rated below 150VA or when connected through socket outlets having their own isolating switch. Since motors draw large currents during starting and also while getting stuck up without rotation due to unknown reasons ((locked rotor and stall currents), it is necessary to consider switches adequately rated to meet such high currents, without getting impaired. These currents may be considered four times the motor rated full load current in case of d.c. motors and eight times the rated currents for a.c. motors, when manufacturer’s data is unavailable. Section 4 - Selection and Installation of Electrical Equipment 149 Where unexpected restarting of a motor might cause danger, such motor shall be provided with means to prevent automatic restarting after stopping. Similarly where reversal in direction of motor during such restarting could pose danger, suitable protections shall be provided to avoid reverse direction of rotation. Motors shall have protective devices to protect against overload and this is mandatory for all motors rated above 0.37 kW. These devices shall be properly coordinated with the motor characteristics and other system protection devices. Over temperature of motor windings shall be avoided by proper selection of the motor ratings in line with the load to be operated. In addition proper over temperature protection methods shall be adopted for unattended motors as noted below • Motors having a voltage rating > 480V a.c. for shaded-pole type motors • Motors rated for > 240V a.c. for other motors • Other types of motors that are rated above 2250 watts Figure 8.5 Typical three phase motor circuit with basic protections The over temperature protection is generally achieved by proving thermal overload devices in the motor circuits or by having built-in thermal devices. The over temperature may also be due to intermittent over load currents for short durations, motor duty cycles with frequent starts/ stops, etc. The over temperature protective device shall isolate the motor supply directly once such high temperatures are detected. Such isolation shall be atleast in one pole of a d.c. or an a.c. motor supplied with earthed systems. In case of unearthed systems, the isolation shall be in all poles of a d.c. motor and atleast in 2 poles of an a.c. motor. 150 Practical Electrical Wiring Standards - AS 3000:2018 Figure 8.6 Typical temperature rise of a motor winding with varying duty cycles. The over temperature device is not mandatory for motors associated with fire protection device or where such opening of motor circuit could create a hazard and also for unattended submersible pump motors immersed in water that have a rating not greater than 2250 W. It shall not be out of place to mention that the motors covered by this standard are mostly motors forming part of appliances and normally encountered in day to day use of residential and commercial installations. Depending on the importance and size of motors, many more protection devices are available and are selected/ incorporated for the safety of the installation and economical reasons. 8.3 Transformers (Clauses 4.14, 4.16) Similar to the motors, transformers is a separate subject not possible to be covered in this text. The standard is not intended to detail requirements for all types of transformers and is basically limited to the installation requirements related to the low voltage side of a transformer used in low voltage installations. This standard does not cover requirements of instrument transformers used in metering and protection circuits, luminous discharge types and transformers used in motors/ similar equipments. The Standard stipulates that conductors connected to the secondary windings of a transformer shall be controlled with isolation switches and protected against over current and fault conditions like short circuit by use of correctly matched devices. The autotransformer shall not be used to supply equipments having a voltage rating of less than its highest input or output voltage. For step up transformers no connection shall be made between the primary and secondary windings, other than by a protective earth conductor. The transformers when installed inside an enclosed area shall be provided with suitable ventilation. Oil filled transformers with a liquid dielectric having a flashpoint <250°C and with total capacity more than 50 litres shall be provided with an oil collection pit to drain the oil in the event of fires. In addition installing such transformers in a chamber of adequate fire resistance and/or provision of sills or other means shall be considered. Section 4 - Selection and Installation of Electrical Equipment 151 Figure 8.7 Typical indoor transformer installation with oil pit 8.4 Capacitors (Clause 4.15) Capacitors are devices normally used for improving the power factor of an a.c. system. These are also used in applications such as motor starting, harmonic filters, etc. The capacitors in a circuit can cause high inrush currents and hence the switching devices and connected distribution systems used for the capacitors shall be designed to match these high currents. In addition to selecting the capacitors for the highest voltages and currents and temperatures they are likely to be operating, the associated accessories shall also be chosen to match the high switching currents of these capacitor units. The Standard recommends considering the following design requirements in a capacitor installation. • Switches shall be provided for capacitor units like any standard electrical equipment. The operating duty for the circuit breakers, contactors and switches used for switching the capacitors shall be AC 6b rating as per AS 60947. • The conductors connected to the capacitor shall have a current-carrying capacity not less than 135% of the rated current of the capacitor; or the setting of the circuitbreaker; whichever is the greater • In case of capacitors permanently connected to a motor circuit, Conductor current rating shall be not less than one-third of the rating of the motor circuit conductors or 135% of the rated current of the capacitor; whichever is the greater • Capacitors with values greater than 0.5 μF shall be provided with a discharge path The capacitors retain the voltage at their terminals for some time duration even after its main power supply is disconnected. Hence discharging the voltage at the capacitor terminals is an important requirement to ensure safety when maintenance or repair works are taken up on systems with capacitors. Hence as a safety, voltage between the capacitor terminals shall be reduced to less than or equal to 50 Volts within one minute after disconnecting the power supply for capacitors rated upto 650V and within five minutes of disconnecting supply for capacitors rated above 650 V, before any work is taken up in the capacitor circuits (even in case of discharges it is recommended to physically measure the voltage before any work is taken up). 152 Practical Electrical Wiring Standards - AS 3000:2018 For capacitors connected in parallel with appliances terminals permanently, (capacitors controlled by the controlgear of the appliance itself), the windings of the appliance shall be connected to form a permanent discharge path for the capacitor. No switch or fuse shall be inserted between the capacitor and the appliance unless the capacitor itself incorporates a permanently connected discharge device. In case of independent capacitors used in a system, the capacitor shall be controlled by a circuitbreaker fitted with an overcurrent release. In such cases, provision shall be made for the discharge of the capacitor by the use of auxiliary contacts of the circuit-breaker which automatically connect a discharge device to the capacitor immediately it is disconnected from the supply or by incorporating a permanently connected discharge device in parallel with the capacitor. This is generally applicable for individual shunt capacitors rated not more than 100 kvar operating independently or in parallel with groups of shunt capacitors. Like appliance capacitors, it is essential that no fuse or switch shall be connected between the auxiliary contacts of the circuitbreaker and the discharge device. In circuits with automatic operation, a capacitor may be controlled by a quick make-and-break switch or contactor and protected by fuses. In such cases, the switching shall incorporate some sort of manual operation to cater for the individual isolation of each capacitor or for the capacitor bank as a whole. Like transformers, capacitors also use dielectric oil internally, though the quantity per capacitor may be much less. Nevertheless, necessary precautions shall be taken to prevent burning of this liquid dielectric oil and in the unlikely event of fires, the products of combustion of the liquid (flame, smoke, toxic gases) shall be prevented spreading to other parts of the premises by suitable installation and segregation practices. 8.5 Airconditioning and heat pump systems Requirements for airconditioners and heat pumps where the internal unit (or units) are supplied from a switchboard or circuit separate to that of the compressor, and new exceptions have been added in 2018 issue of the Standard. Airconditioning and heat pump systems incorporating a compressor shall be provided with an isolating switch (lockable) in accordance with Clause 2.3.2.2, installed adjacent to but not on the unit, which isolates all parts of the system, including ancillary equipment, such as head units, from the same location. For split system airconditioning units, where the manufacturer requires the airconditioning system to be connected to the electricity supply by means of a plug and socket at the internal unit, the isolating switch installed at the external unit shall control the socket-outlet located at the internal unit. 8.6 Lifts Requirements for lifts installed for general use and that are not emergency lifts (safety services) have been added. 8.7 Summary The selection and installation of electrical equipment and appliances shall take care of the external influences they are likely to face during the service without affecting the electrical installation and ensuring basic safety features like prevention of shock, high thermal effects, etc. The selection and Section 4 - Selection and Installation of Electrical Equipment 153 installation shall incorporate means to avoid disturbances to the supply such as power factor, voltage fluctuations, harmonics and electro magnetic interferences. The equipments shall be installed to ensure that they do not become source of fire when located close to flammable substances. This is to be accomplished by adopting proper metal enclosure, segregation, use of certified equipments, etc. The standard specifies maximum limiting temperatures for accessible metallic and non metallic parts of the equipment and its enclosures, which shall be ensured in an applicable installation. The connection of an equipment or appliance may be direct or through a socket and/or with an installation coupler or through a junction box, ceiling rose, etc. It shall be ensured that the wires from such connecting devices to the equipment shall be as short as practicable with ratings matching the equipment/ appliance being connected. These shall be protected with fuses and earth continuity. Each socket outlet shall be installed with an isolating switch matching the socket rating, unless the installation permits it without switch. The matching plug shall exactly fit into its socket and the installation shall ensure avoidance of accidental contacts of open pins of the plug during insertion or removal. Specific guidelines are to be followed when these sockets are mounted on horizontal plane or within 75mm from a floor level. Lighting equipments may be simple lamp holders with matching lamps or luminaires designed for specific lamps. These lighting accessories shall incorporate basic safety features to enable safe access and safe lamp replacement as may be needed. The recessed luminaires in air conditioned areas shall be installed ensuring minimum distances from the insulation materials and also with enough clearances all around to facilitate adequate air circulation. The standard also covers requirements related to cooking appliances, heating systems, etc. These shall all be provided with proper thermal protective devices and isolation switches for safe functioning. The heating cables in floor shall ensure proper grounding practices to avoid accidental contacts. In regard to electricity converters like UPS, stabilizers, etc, it is necessary to provide individual isolation switches with provisions to avoid back feeing to the supply system, where such possibilities exist. The harmonic currents shall be taken care while adopting electronic converter systems in an installation by means of properly sized conductors and by providing harmonic filters. Battery installations of converters like UPS would require special precautions to avoid accidental contacts to their terminals and possible acid spillages. Motors shall be provided with isolating switch for emergency stopping as near as possible. Motors rated above 0.37kW shall be provided with thermal protection to avoid high winding temperatures and consequent failures. A separate study on motor requirements shall be needed to decide on the other protections to be adopted for a motor. Transformer requirements related to low voltage connections are covered in this standard. When total oil in transformer installation is beyond 50 litres, it is necessary to provide separate pits for oil drainage during fires and oil leakages. In regard to the low voltage capacitors it is necessary that the switching devices and conductors associated in their circuits are designed to match the high switching currents of the capacitors. Another important requirement for capacitors is provision of discharge path for charged capacitors, when disconnected from the mains before it could be accessed for any maintenance work. 154 Practical Electrical Wiring Standards - AS 3000:2018 9 Section 5 - Earthing Arrangements and Earthing Conductors In an earlier section we reviewed about the importance of the earthing in electrical systems. In this chapter we will review the AS/NZS 3000 requirements related to design and installation of earthing in low voltage systems with specific stipulations on the MEN system commonly adopted for LV distribution systems in Australia. We will also discuss the earthing conductor size selection procedures and recommended arrangements for equipment earthing. A brief review will be made on the equipotential bonding and earthing requirements for non electrical services. The chapter will also cover the earth fault loop impedance and the recommendations on the earth loop impedance value to be maintained in the LV systems. Learning objectives • • • • • • • • 9.1 Requirements of Earthing system Multiple Earthed Neutral (MEN) system Earthing conductors Equipment earthing Earthing arrangements Equipotential bonding Earth fault loop impedance and need for limiting circuit lengths Earthing requirements for other (non-electrical) systems Requirements of earthing system (Clauses 5.1, 5.2) The earthing arrangements shall be selected and installed with necessary features to perform some important functions expected from them for safe operation of the electrical installations. The following paragraphs give the various features that are commonly adopted in a system to ensure its safe operation: • The supply to the protected part or a circuit shall be automatically disconnected in the event of a shortcircuit of live conductors to earth or excessive earth leakage current to avoid consequent hazards like fire, shocks, etc. This is achieved by means of protective earthing arrangements to enable proper sensing of fault conditions for immediate disconnection. • There are some equipment/ devices that require an earth reference to function correctly rather than for safety purposes. This is achieved through functional earthing (FE) arrangements, e.g. Cathodic protection, radio interference signal suppression, clean earth in instrumentation systems, etc 154 Practical Electrical Wiring Standards - AS 3000:2018 • • It is necessary that the system shall be able to mitigate voltages appearing on exposed conductive parts of equipment and extraneous conductive parts of the installation due to various reasons like mutual inductance, etc that would make these parts getting charged and becoming unsafe during normal service. This is achieved through equipotential bonding arrangements and by having features to provide connection of exposed conductive parts and extraneous conductive parts to earth. Until the isolation of a fault by automatic disconnection, the system fault path shall be capable of carrying sufficient quantity of earth fault and earth leakage currents without danger or failure from thermal, electromechanical, mechanical, and environmental and other external influences. This is achieved by providing effective and reliable low fault loop impedance path in the earth circuit so that the fault conditions can be monitored and sensed correctly to ensure disconnection at appropriate times Three phase LV systems usually have the source neutral earthed solidly. Connecting an impedance between neutral and earth is not a recommended practice for consumer LV installations. Majority of the installations under the purview of AS/NZS 3000 are provided with solid earthing for the LV neutral. However where impedance is added in the neutral, like in the case of some special installations and in some diesel generator installation, etc., it shall be ensured to meet the following requirements. • The value of earthing resistance shall be in accordance with the protective and functional requirements of the electrical installation and shall be continuously effective • earth-fault currents and earth-leakage currents shall be carried by the impedance without danger, particularly ensuring that associated thermal, thermo/ electromechanical stresses do not affect the system/ safety requirements • Shall be adequately robust and if needed, shall have additional mechanical protection appropriate to meet the external influences expected in the system/ environments 9.2 Multiple Earthed Neutral system (Clauses 5.3) Multiple Earthed System (MEN) described in Australia and New Zealand standards is similar to TN-C-S system defined in IEC 60364 and IEE wiring regulations which we briefly covered in an earlier chapter with an appendix giving more details on the same. The letters in TN-C-S refer to the following: • T - the distribution system is directly connected to earth—at the neutral point of the supply transformer • N - The exposed conductive parts are connected to the earthed point of the distribution system. It is neutral or if neutral is unavailable it could be one of the phases • C - the neutral and protective conductor functions are combined in a single conductor (the PEN conductor of the source) • S - the protective conductor function is separated from the neutral—separate neutral and earth conductors within the installation The 2018 issue of the Standard defines the MEN system for further clarity. MEN connection requirements have been added regarding location in an accessible position. In every electrical installation there shall be an MEN connection (also known as the MEN link) at the main switchboard that receives the mains supply from the distributor. The function of the MEN connection is to enable the earthing of the supply system neutral conductor within the electrical installation. This is done by means of a connection from the main earthing terminal/connection or bar of the installation to the earthing terminal provided on the MEN link. Where the MEN connection is done using insulated conductors, the insulation shall be colored green or in a combination of green and yellow. An MEN System in an installation generally comprises of all the following components: Section 5 - Earthing Arrangements and Earthing Conductors 155 • • • • • • Protective earthing conductors connecting all exposed conductive parts within the plant as required Main earthing conductor (Copper or aluminium) used for interconnecting all these protective earth conductors to the earth Main earthing terminal, connection or bar of the plant used for terminating one end of the main earthing conductor with its other end connected to earth electrode MEN link/connection from the above earthing terminal/connection/bar to the mains supply neutral bar Earth electrode within the plant connecting all the above parts to the earth through the main earth conductor Equipotential bonding conductors of extraneous conductive and other parts as applicable/ available in the system Typical MEN systems showing connections to earth at consumer installation and substations are shown in figures 9.1 and 9.2. Figure 9.1 General arrangement of MEN connections (Source: AS/NZS 3000, Figure 5.1) 156 Practical Electrical Wiring Standards - AS 3000:2018 Figure 9.2 Alternative arrangement of MEN connections (Source: AS/NZS 3000, Figure 5.2) 9.3 Selection of earthing conductor (Clauses 5.3.2, 5.3.3) Copper is the most common and recommended conductor to be adopted for earthing connections. Copper conductors used for earthing shall be of high conductivity type and may be in any one of the following forms: • Multi-strand conductors • Circular braided conductors • Solid conductors subject to a minimum cross-sectional area of 10 mm2 and a minimum thickness of 1.5 mm except where a cable standard permits a smaller conductor size The cross-sectional area of a copper main earthing conductor with multiple strands shall be not less than 4 mm2 and need not be greater than 120 mm2. The next alternative is using aluminium earthing conductors which shall meet the following requirements: • Solid conductors of 10 mm2 or less (without strands) • Minimum 16 mm2 conductors for main earthing conductors • The installation shall provide satisfactory terminations with features to prevent corrosion • Shall not be installed underground or in other damp situations unless it is designed for these conditions Materials other than copper or aluminium also may be used as an earthing conductor. In such cases the resistance of the alternative material shall be not greater than the resistance of the equivalent copper earthing conductor size determined in accordance with appropriate methods. Also its degree of corrosion resistance shall not be inferior to copper/ aluminium. Protective earthing conductors may include the following: (a) Earthing conductors that comply with Clause 5.3.2.1, separately installed (b) Earthing conductors that comply with Clause 5.3.2.1, in a common enclosure with live conductors. Section 5 - Earthing Arrangements and Earthing Conductors 157 (c) Earthing conductors in multi-core cables (d) Busbars Under special conditions following may be accepted as earthing conductors: • Conductive conduit, tube, pipe, trunking and similar wiring enclosures subject to enclosing live conductors within • Conductive sheaths, armours and screens of cables that are parts of the live conductor cable • General conductive framework subject to ensuring proper connections for earth continuity • Catenary wires not less than seven strands and with a minimum cross-sectional area of 8.5mm2, constructed of hard-drawn copper or galvanized low carbon (mild) steel Earthing conductors shall be provided with insulation except for the following options: • Aerial conductors • Flat braided conductors • Busbars • Sheaths of MIMS cable • Catenary supports • Metallic wiring enclosures • Copper earthing conductors buried direct in the ground 9.3.1 Minimum size of earthing conductors Sizing of a copper earthing conductor can be generally chosen from Table 9.1 given in this section and the size is normally based on the cross-sectional area of the largest active conductor supplying the portion of the electrical installation being protected. In case of using earth conductors of different material, the considerations given in earlier section shall be taken into account, subject to acceptance of such alternative materials by competent personnel and relevant authorities. For installations using a number of parallel connected active conductors in the mains, the equivalent active conductor size shall be determined by summing up the cross-sectional areas of the individual largest active conductors of the system. Then the minimum earth conductor size shall be chosen from the table in relation to the equivalent size so arrived or where the equivalent size is not appearing in the table in relation to the next larger size of the equivalent size. In some cases the size of the main earthing conductor need not be determined in relation to the size of the largest main active conductor size. Following are the typical cases, where sizes different from the main active conductor are accepted and it may be necessary to cross check those sizes based on calculations method in larger systems: • Where double insulation is maintained between the point of supply and the load terminals of the protective devices for the submains and final subcircuits from the main switchboard, the minimum size of the main earthing conductor may be determined in relation to the cross-sectional area of the largest active conductor of the outgoing submain or final subcircuit. • Where the cross-sectional area of the consumers’ mains is chosen to be larger than that required to carry the maximum demand of the installation because of voltagedrop limitations, the minimum size of the main earthing conductor may be chosen in relation to the minimum cross-sectional area of the cable size required to carry the maximum demand. • Copper or aluminium conductors installed as aerial earthing conductors shall have not less than seven strands and shall be not smaller than 6 sqmm for copper or 16 sqmm for aluminium. Sizes marked with # in table 9.1 may have to be increased in case of higher fault currents, mainly to lower the earth fault loop impedance. 158 Practical Electrical Wiring Standards - AS 3000:2018 Table 9.1 Minimum earth conductor sizes (Source: AS/NZS 3000, Table 5.1) Minimum earth conductor sizes for smaller systems and loads shall be decided depending on the application and insulation types as noted below: • Minimum size of copper earthing conductor in the form of single-core insulated cable or flexible cord shall be 2.5 sqmm • Minimum size of an earthing conductor incorporated with associated live conductors in sheathed multicore cable shall be 1 sqmm Section 5 - Earthing Arrangements and Earthing Conductors 159 • 9.3.2 Minimum size of earthing conductor in the sheath of a multicore flexible cord, shall be not less than the cross-sectional area of the largest active conductor in the flexible cord provided largest active conductor in the flexible cord is in between 0.5 and 2.5 sqmm, mainly for such of those flexible cords used to supply a hand-held or portable appliance Size of earthing conductors by calculations The minimum cross-sectional area can also be determined by calculation using the following equation, based on fault current to be carried and its duration. This equation is to be used only for systems having disconnection times not less than 0.1 second but not exceeding 5 seconds. S= I2 × t K ………………………. 9.1 where S = cross-sectional area of protective earthing conductor, in sqmm I = RMS value of the fault current in amperes that would flow through the overcurrent protective device of the circuit concerned in the event of a short-circuit of negligible impedance t = the disconnecting time of the overcurrent protective device in seconds, corresponding to the value of fault current I K = factor dependent on the material of the protective earthing conductor, the insulation and other parts and the initial and the final temperatures (e.g. for copper conductors with PVC insulation not laid up with other conductors, K = 136 and for bare copper K=170) If a calculation results in non-standard size, conductors of the nearest higher standard crosssectional area available in the market shall be used. Functional earthing conductors that are solely for correct operation of electrical equipment, or to permit reliable and proper functioning of electrical installations need not comply with requirements for main and protective earthing conductors. The sizes are usually chosen low but with adequate strands/ protection to ensure reliable connection. Where earthing combines both protective and functional purposes, the requirements for protective conductors shall be adopted for sizing. 9.4 Earthing connections (Clauses 5.3.4, 5.3.5, 5.3.6) The main switchboard of every electrical installation shall be provided with a main earthing terminal/connection or bar at an accessible and relatively undisturbed position, as we noted in an earlier chapter. The following conductors of the installation shall be connected to this main earth connection in the switchboard, either directly or indirectly, to form an equipotential bonding network. • Protective earthing conductors. • Main earthing conductor. • MEN connection. • Equipotential bonding conductors. • Functional earthing conductors, if required. It is recommended that the functional earth connection is independent to the protective earth, as otherwise it may be conflicting with the manufacturers requirements. Thus functional earth connection shall preferably be limited to the main earth connection point only. 9.4.1 MEN Connection In every electrical installation there shall be an MEN connection (also known as the MEN link) at the main switchboard. 160 Practical Electrical Wiring Standards - AS 3000:2018 NOTE: The function of the MEN connection is to connect the earthing system within the electrical installation to the supply neutral conductor by means of a connection from the main earthing terminal/connection or bar to the earthing terminal on the main neutral bar. Exceptions: 1) The NE connection may be made at an earth bar within an owner or user operated supply substation (refer to Figure 5.2) 2) The NE connection may be made at an electricity distributor neutral bar within the electrical installation, e.g. at the supply substation or meter panel, if so required by the distributor 3) The NE connection may be made through an earthing conductor or terminal, provided by the electricity distributor NOTE: An earthing conductor or terminal provided by the electricity distributor may include a special earthing conductor, the conductive sheath of a supply cable, or a neutral bar at a substation. The MEN or NE connection shall be located in an accessible position for disconnection and testing purposes. The minimum size of this MEN connection conductor shall be not less than the current carrying capacity of the main supply neutral conductor. However in some cases depending on non provision of the shortcircuit protection arrangement or non provision of double insulation at supply end may demand a higher MEN conductor size to be used. Where the MEN connection is insulated, the insulation shall be colored green or in a combination of green and yellow in accordance with Clause 3.8 of the Standard. 9.4.2 Earth electrodes The connection of the electrical installation earthing system to the general mass of earth shall be achieved by means of one or more earth electrodes of acceptable types. The materials and dimensions of the earth electrode shall be chosen to withstand corrosion and shall have adequate mechanical strength based on the nature of the soil and environmental conditions. Table 9.2 gives typical types and installation of earth electrodes recommended in the standard. Table 9.2 Acceptable types of earth electrodes (Source: AS/NZS 3000, Table 5.2) Section 5 - Earthing Arrangements and Earthing Conductors 161 Based on the soil conditions commonly prevalent, it is usual to consider the vertical earth electrodes to be driven to a minimum depth of: 1.2 metres in Australia and 1.8 metres in New Zealand. In case of using strip-type earth electrodes buried in a horizontal trench, these shall be laid at a depth having not less than 0.5 metre from soil surface and with a minimum horizontal length of 3 metres in Australia and 7.5 metres In New Zealand. Following requirements shall be met for the earth electrodes and their installation methods to ensure the desired protection and safety: • Shall have effective contact with moist soil that shall not be subject to excessive drying out. This may have to be done either by keeping them exposed to outdoor conditions where cold conditions prevail or covering the electrodes suitably to avoid loss of moisture in case of hot conditions. • Shall be separated from conductive enclosures of other buried services such as water, gas, telecommunications and flammable liquid, to reduce possible electrolytic/ galvanic corrosion • The main earthing connection to an earth electrode shall be accessible for the purposes of inspection, testing or modifications, as may be needed at any time 9.5 Equipment earthing (Clause 5.4) As we reviewed earlier, it is necessary to ensure all equipment are provided with protective earthing connected to earth to keep the touch potential of contact surfaces to zero or within acceptable limits. The equipment shall be connected to earth by means of conductors in the form of cables, cords, busbars or similar forms of current-carrying material or through another earthing medium such as conductive parts of cables, wiring enclosures, switchboard framework, etc available in a system. It is necessary to ensure that all the following are kept connected to earth under all conditions: • Earthing contact of every socket-outlet • Every lighting point • Transformers supplying ELV lighting systems • Exposed conductive parts of luminaires • Conductive poles, posts, struts, brackets, stay wires and other conductive supports of low voltage aerial conductors • Parts of structural metalwork, including conductive building materials • Exposed conductive parts of a submersible pump Following items need not be earthed: • Electrical equipment complying with AS/NZS 3100 for double insulation • Cables affording double insulation normally connecting to such equipment • Exposed conductive parts supplied by an SELV or a PELV system Structural metalwork including conductive building materials Structural metalwork forming the frame of a structure containing an electrical installation or part thereof, including sheds or similar structures that are permanently connected to the electrical installation wiring, shall be earthed. The size of the earthing conductor used for earthing the frames shall be determined from Clause 5.3.3 in relation to the cross-sectional area of the largest active conductor that is contained within the framework of that electrical installation. For combined outbuildings, each outbuilding shall contain its own individual bonding connection to the conductive frames within that outbuilding. All other conductive building materials shall be earthed where— a) the risk of contact with live parts of electrical equipment or insulated, unsheathed cables exists; or b) double insulation of cables in contact with conductive building materials is not permanently and effectively maintained. 162 Practical Electrical Wiring Standards - AS 3000:2018 9.6 Earthing arrangements (Clause 5.5) A main earthing conductor shall be taken from the main earthing terminal/connection or bar provided at the main switchboard to an earth electrode located as close as possible and in as direct a manner as possible. It shall not be connected to the terminal of any accessory, luminaire or appliance. The connection of the main earthing conductor to the earth electrode shall meet the following requirements: • be accessible for visual inspection and for the purposes of testing • be made by means of a suitable device having good conductivity and in accordance with the manufacturer’s recommendations • be protected against mechanical damage and corrosion • be prominently labeled indicating WARNING: ‘MAIN ELECTRICAL EARTHING CONDUCTOR—DO NOT DISCONNECT’ to caution against accidental disconnection. The resistance of the main earthing conductor, measured between the main earthing terminal/connection/bar end and the earth electrode including the connection to the earth electrode, shall be not more than 0.5 Ω. Protective earthing connections of equipments shall be directly connected to the main earthing conductor or to another point on an earthing system that is subsequently connected to the main earthing conductor. These may be done through one or a combination of the following: • To an earthing terminal/connection or bar at the main switchboard provided specifically for the connection of earthing conductors and which is directly connected to the main earthing conductor • To any point on the main earthing conductor • To an earthing terminal/connection or bar at a distribution board provided specifically for the connection of protective earthing conductors • Any point on a protective earthing conductor providing facilities for earthing at a distribution board It shall however be noted that a protective earthing conductor of a distribution board shall not be used for the connection of earthing facilities for another distribution board or for connection of an equipment fed by another switchboard. Continuity of earthing connections shall be ensured by adopting proper connection practices. Star or cutting washers or similar devices that effectively cut through paint or similar coatings are acceptable across bolted or clamped joints. Where electrical equipment is connected in the form of a plug and socket-outlet, appliance plug or similar connecting device, connection of exposed conductive parts to earth shall be made automatically, before the live connections are made while inserting the plug. In a similar way, it shall be ensured that when any plug portion is withdrawn from the corresponding socket-outlet the earth connections are NOT broken before the live connections are broken. 9.6.1 Outbuildings All parts of an electrical installation in or on an outbuilding that are required to be earthed in accordance with Clause 5.4 shall be earthed by one of the following methods: a) Individual outbuildings The earthing system in an individual outbuilding shall be either— i) connected to a protective earthing conductor connected in accordance with Clause 5.5.2.1; or ii) connected as a separate MEN installation in accordance with Clauses 5.5.3.1(c) and 5.5.3.2. Section 5 - Earthing Arrangements and Earthing Conductors 163 b) Combined outbuildings The earthing system in a combined outbuilding shall be connected to a protective earthing conductor, connected in accordance with Clause 5.5.2.1, and shall not be connected as a separate MEN installation. Separate MEN installation The earthing system in a separate MEN installation shall be connected to the submain neutral conductor supplying the outbuilding. In this case, the submain neutral conductor supplying the outbuilding is a combined protective earthing and neutral (PEN) conductor. The electrical installation in the outbuilding shall be regarded as a separate electrical installation, and shall be earthed in accordance with other relevant Clauses of this Standard.. 9.6.2 Wiring systems Exposed conductive parts of wiring enclosures shall be earthed at the end adjacent to the switchboard or accessory at which the wiring enclosure originates. Similar procedure shall be followed for earthing connections of the conductive sheathing, armouring or screening of cables or cords. 9.6.3 Unprotected consumers mains Exposed conductive parts associated with consumers mains that are not protected with short circuit protection on the supply side shall be earthed by a conductor with a current-carrying capacity not less than that of the main neutral conductor. This conductor shall be connected to the main neutral conductor or bar or the main earthing terminal/connection or bar. The cross-sectional area of the MEN connection shall be not less than that of the main neutral conductor. 9.6.4 Protection of earthing connections The earthing connections and conductors shall be suitably protected against mechanical damages by ensuring that the clamps, clips, etc that are holding the cables do not pass through the conductor strands and guarding these with metallic barriers or other suitable means. Similarly these shall be protected from chemical deterioration due to corrosive effects by using corrosion resistant materials and by ensuring prevention of moisture by sealing as well as prevention of contacts between dissimilar metals, etc. Using the available wiring enclosures to include earthing conductors shall also be considered, wherever possible. 9.7 Equipotential bonding (Clause 5.6) Equipotential bonding requirements have been expanded and clarified through enhanced requirements for showers, bathrooms, pools and spas in 2018 issue of the Standard. Equipotential bonding arrangements shall be provided to avoid any potential differences that may occur between electrical equipment connected to the electrical installation earthing system and any conductive piping (including taps, etc) that may independently be in contact with the mass of earth. It is necessary to adopt equipotential bonding for the fixed extraneous conductive parts generally for all the following applications. • Conductive water piping. It shall be bonded to earth as close as practicable to the entry of the conductive water piping to the building • Other metallic piping systems. These may not be bonded in case they are effectively earthed by connection to an associated item of electrical equipment e.g. water pipes connecting the electric hot water systems. • Metal cable sheaths and metallic wiring enclosures • Any conductive reinforcing within a concrete floor or wall of a room containing a shower or bath. • The exposed conductive part of any electrical equipment in the swimming and spa pools within the classified zones and any exposed conductive parts of electrical 164 Practical Electrical Wiring Standards - AS 3000:2018 • equipment that are not separated from live parts by double insulation and are in contact with the pool water, including water in the circulation or filtering system. Telephone and telecommunication earthing systems at an enclosed terminal provided for the purpose or directly to the earth electrode by an independent connecting device and shall be clearly identified. Additional equipotential bonding requirements apply for: (a) Patient areas of hospitals, medical and dental practices and dialyzing locations, in accordance with AS/NZS 3003 (b) Explosive atmospheres, in accordance with Clause 7.7 (c) Telecommunications installations, in accordance with AS/NZS 3015 (d) Film, video and television sites, in accordance with AS/NZS 4249 (e) Photovoltaic arrays, in accordance with AS/NZS 5033 (f) Grid connected inverters, in accordance with AS/NZS 4777.1 (g) Generating systems, in accordance with Clause 7.3 (h) Separated circuits, in accordance with Clause 7.4 Conductive water piping Conductive water piping that is both— (a) installed and accessible within the building containing the electrical installation; and (b) continuously conductive from inside the building to a point of contact with the ground, shall be bonded to the earthing system of the electrical installation Bonding conductor size shall generally take into consideration the following recommendations as per the standard. • Metallic piping, cable sheaths and wiring enclosures shall have a cross-sectional area of not less than 4 sqmm. • Metallic parts of wet areas like showers, pools, etc shall have a cross-sectional area of not less than 4 sqmm. • Telephone and telecommunication earthing system shall have a cross-sectional area of not less than 6 sqmm. • Refer to AS/NZS 2381.1 and the AS/NZS 61241 series of Standards for minimum sizes of equipotential bonding of items in hazardous areas. It may be noted that bonding of extraneous conductive parts and their connection to the earthing system also help to get reduction in earth fault-loop impedance that is necessary to keep the disconnection time within a short time, as applicable. Section 5 - Earthing Arrangements and Earthing Conductors 165 9.8 Earth fault loop impedance (Clause 5.7 and Appendix B) The path available or used for the circulation of fault current in a system is called the earth fault loop. In an MEN system, the earth fault loop comprises of the following parts. • The active conductor as far as the point of the fault, including supply mains, service line, consumers mains, submains (if any) and the final subcircuit • The protective earthing conductor (PE), including the main earthing terminal/connection/ bar and MEN link connection • The neutral-return path, consisting of the neutral conductor (N) between the main neutral terminal/bar and the neutral point at the transformer, including supply mains, service line and consumer mains • The path through the neutral point of the transformer and the transformer winding The impedance of the earthing system shall be limited to that which will generate sufficient current in the protective device to cause operation of that device within the required time. The following equation fulfils this requirement. ZS ≤ U0 ………………………. ………………………9.3 Ia Where Zs = the impedance of the earth fault-loop comprising the source, the active conductor up to the point of the fault and the return conductor between the point of the fault and the source I a = the current required to cause the automatic operation of the disconnecting protective device within the required disconnection time U o = the nominal a.c. r.m.s. voltage to earth (230 V) Figure 9.3 shows the impedance path of an earth loop in common LV systems covering the supplier and customer installations together. At the instant of the fault, current will flow through the earth fault-loop and its magnitude is limited only by the total system impedance Zs that is equal to the sum of all the individual impedances in the loop as below. Zs = Z AB + Z BC + Z CD + Z DE + Z EF + Z FG + Z GH + Z HA …………9.4 As noted from figure, impedances Z AB , Z BC , Z FG , Z GH and Z HA are all upstream of the protective device within the electrical installation and are regarded as being external to the reference point; accordingly they may be collectively referred to as Z ext . The remainder that are downstream (or ‘internal’ within the installation) may be referred to as Zint (Z CD , Z EF ), therefore, Zs = Zext + Zint. 166 Practical Electrical Wiring Standards - AS 3000:2018 Figure 9.3 Simplified MEN system identified with earth fault loop (Source: AS/NZS 3000, Figure B5) When an electrical installation is being designed, Zext may or may not be available (it will depend on the electricity distributor’s transformer and supply cables). If it is not available Zint may be determined by either of the following two methods: Method 1: When the length and cross-sectional area of conductors are known, we know from above that Zint = Z CD + Z EF ……………………………………………...9.5 Reactance may generally be ignored for conductors of 35 mm2 or less where the active and earthing conductors are in close proximity to one another. Thus, for such circuits, the current I a may be calculated using only conductor resistance as per the following equation. Ia = U0 ………………………. ………………………9.6 R PE + R L Where U O = the nominal a.c. r.m.s. voltage to earth R PE = the resistance of the protective earthing conductor from the reference point to the exposed conductive part (See figure 9.3) R L = the resistance of the phase (active) conductor from the reference point to the exposed conductive part. In case of finer values using impedance values for conductors, these are available in the AS/NZS 3008.1 series and referring to the tables in the standard for the known conductor sizes, Z int can be arrived at. Section 5 - Earthing Arrangements and Earthing Conductors 167 Method 2: When the length and cross-sectional area of the supply conductors are not known, it may be assumed that there will always be 80% or more of the nominal phase voltage available at the position of the circuit protective device. Therefore, Zint should be not greater than 0.8 Zs. This may be expressed as follows: Zint = 0.8 U o /I a …………………………………………..9.7 Above equation may be expressed in terms of circuit length by considering (active and earth) conductor sizes and protective device tripping current. This gives rise to the following equation. L max = 0.8 U 0 S ph S pe I a ρ (S ph + S pe ) …………………………………9.8 Where, L max = Maximum route length of the conductor in metres Uo = nominal phase volts (230 V) ρ = resistivity at normal working temperature in Ω-mm2/m = 22.5 × 10−3 for copper = 36 × 10−3 for aluminium Ia = Trip current setting for the instantaneous operation of a circuit-breaker; or the current that assures operation of the protective fuse concerned, in the specified time S ph = cross-sectional area of the active conductor of the circuit concerned in mm2 S pe = cross-sectional area of the protective earthing conductor concerned in mm2 It is not desirable to have an impedance value that can affect the operation of a protective device, when provided resulting in the fault to continue without disconnection. Hence it is always important to crosscheck the loop impedance for effective and correct operation for the expected fault currents. The impedance values are basically functions of route lengths and conductor sizes. The formula given in equation 9.8 can be used to calculate the maximum route lengths beyond which the impedance of a particular size of conductor would limit the magnitude of the shortcircuit current below that is required to operate the protective device. Appendix B, Table B1 can be used as a ready reference to find typical maximum conductor lengths of a conductor size for safe operation of a protective device of particular rating. Once the length is exceeded in an installation, alternate conductor (higher cross section) shall have to be chosen to reduce the overall loop impedance for effective operation of the device. Table 9.3 here provides a glimpse of some part of the Table B1 for immediate understanding of typical maximum circuit lengths for a few conductor sizes commonly used in low voltage installations. . 168 Practical Electrical Wiring Standards - AS 3000:2018 Table 9.3 Maximum circuit lengths of conductors for protective device ratings (Source: AS/NZS 3000, Table B1) Minimum current Ia for circuit-breakers considered for the purpose of the values arrived in Table 9.3 is the mean tripping current as per the applicable standard AS/NZS 60898. Type B breaker = 4 × rated current Type C breaker = 7.5 × rated current Type D breaker = 12.5 × rated current Ia for fuses are approximate mean values taken from AS 60269.1. From the table 9.3, it may be noted that for say a conductor size of 25 sqmm, if the protective device rating chosen is 100 amperes, the cable length using type B breaker shall be just below 100metres to limit the overall loop impedance. Where the actual circuit length is more than 100metres, there is no alternative other than to go for the next conductor size with a different device rating. During actual operation changing the device rating may be possible but it is impossible to modify the conductor sizes without associated implications of cost, matching devices, etc. Hence the conductor size selection at the stage of design is very much important as otherwise, it could create serious implications at a later date. The maximum route lengths given in the table for the phase conductor are from the point of connection to the point of use and are related to a disconnection time of 0.4 seconds for the device under use. When the nominal phase voltage of the electrical installation is not 230 V, the maximum Section 5 - Earthing Arrangements and Earthing Conductors 169 length may be determined by multiplying the lengths in this table by a factor of Uo/230 e.g. for a nominal phase voltage of 240 V, the factor ~1.04 may be used. For other cable sizes/ protective device ratings, reference shall be made to table B2 in AS/NZS 3000 appendix B. 9.9 Earthing requirements for other systems (Clause 5.8) In general, the earthing arrangements of the following systems should be independent systems; however, if they are connected to the electrical installation main earthing system they should not reduce the integrity of the electrical installation earthing system: • Lightning protection. • Static electricity protection. • Radio frequency interference (RFI)-screened installations. • Information technology installations. • Explosion protection systems. • Cathodic protection systems. 9.10 Summary The earthing system in an installation plays an important role to ensure that the touch voltage of all contact surfaces are kept at earth potential for safety of persons in case of short circuit currents between live parts to the earth. The earthing connections adopted for achieving this objective is called protective earthing. This is different from functional earthing which is basically intended some specific operations purpose like cathodic protection, etc and not for safety purpose. The value of earth resistance determines the system’s ability to minimize the touch potential and the earth fault loop impedance determines the minimum time taken by protective device for operation under the specific fault current of the system, both of which shall be as low as possible. It is necessary to adopt correct sizes of earthing conductors to carry the expected fault currents in a system. The earth conductor is usually made of copper and AS/NZS 3000 recommends minimum size of main earth conductor to be considered for the system which is generally based on the active conductor sizes of the main supply. It is also necessary to use the calculations method to arrive at the earth conductor sizes depending on the likely short circuit currents and the short circuit current protection adopted in the system. In Australia the LV installations are usually adopted with multiple earthed neutral systems which are equivalent of TN-C-S system specified in IEC. The MEN system consists of a common neutral and protective earth conductor from the main power supply distribution company which is terminated usually on the main switchboard of the installation. It is necessary that the protective earthing connections from various equipments of the consumer installation are connected to the MEN point at the main switchboard, directly or indirectly. The MEN point at the switchboard is connected to the earth through an earth electrode of atleast 1.2 m depth made of acceptable material (copper or steel rod/ strip) of sufficient size as per the recommendations of the standard. For reliable earthing system it is necessary to ensure that the earth connections of all equipments and extraneous conductive parts are securely done by using corrosion resistant material with suitable protections adopted to safeguard against mechanical forces and corrosion effects. It is necessary that all conductive pipes, reinforcing parts in wet areas, etc are also connected to the earth by means equipotential bonding with minimum 4 sqmm copper conductors. The earth fault loop impedance shall be effectively controlled within a reasonable value to ensure safe disconnection time of 0.4 seconds is achieved by the protective device adopted for short circuit protection. Guidelines are available to choose proper conductor sizes and protective device ratings, which shall be duly considered during design stages. 170 Practical Electrical Wiring Standards - AS 3000:2018 10 Section 6 – Damp Situations Moisture and humidity are the major concerns for maintaining the electrical insulation characteristic which is very vital for the reliable operation of the electrical systems and to avoid flash over, shock currents, etc. Hence it is very important that the electrical systems operated in areas that are constantly exposed to water shall be selected and installed with utmost care to maintain insulation properties and safety. Locations from bath/ shower/ water containers used by common man in every residential installation to comparatively commercialized areas like swimming pools, spa pools, sauna heaters, etc frequented by many people always use water; hence these areas demand special attention for selecting and installing proper electrical equipments. Section 6 of AS/NZS 3000 stipulates the rules to be followed for the electrical systems installed in. such damp locations. In defining these rules, AS/NZS 3000 divides such areas into multiple zones depending on the quantum of water exposure likely to be faced by these installations at the water storage/consuming points as well as at the locations surrounding such areas. Based on these defined zones, the standard recommends the types and characteristics of systems to be adopted in each damp area to minimize the possibility of common hazards expected. Learning objectives • • • • • • • Basic requirements to be met in damp areas Requirements in bath, showers or other fixed water container areas Requirements in swimming pools, paddling pools and spa pools or tubs Requirements in fountains and water features Requirements in locations containing sauna heaters Requirements in Refrigeration rooms Requirements in General hosing down areas 10.1 Basic requirements (Clause 6.1) Generally electrical equipments in damp situations shall meet all the basic safety requirements related to construction, protection systems, earthing, etc as stipulated in Part-1, Section-1 and Part2, sections-2 to 5 we reviewed till now for protection of personnel and properties from the hazards of electricity use. The installations in damp situation have no exception for these stipulations. Nevertheless, section-6 of the standard stipulates some of the important and specific requirements to be considered additionally for electrical installations in damp situations over and above the rules covered in the earlier sections. These additional requirements are basically aimed for meeting the following objectives and functions in damp areas. • An increased risk of electric shock is always possible for electrical installations operating in damp areas due to more likelihood of contacts by the body with earth potential through constantly available water or moisture in these areas which are good 170 Practical Electrical Wiring Standards - AS 3000:2018 • conductors of electricity. There are also more chances for the reduction in body resistance of the persons in contact with water in these areas that can easily enhance the flow of dangerous shock currents at lower contact potential values when compared to such possibilities in general areas. Hence the systems installed in these damp areas shall be able to minimize the additional risks of increased direct contacts through water and moisture as well as dangerous leakage currents at very low touch potential on contact surfaces, by adopting adequate and foolproof safety measures. The enclosures of electrical equipment are usually specified with IPXX category of protection in which the second X defines how much resistance the enclosure can offer against entry of water. In damp areas, there are always more chances for water entering into the enclosures of electrical items/ appliances in different directions with different forces due to varying patterns and constant use of water and also more chances of high humidity affecting the insulation characteristics. These can lead to short circuit currents and associated hazards. Hence the equipment enclosures selected and installed in damp areas shall be able to offer adequate protection against water and humidity to minimize insulation failures for ultimately safeguarding the personnel and properties from such hazards and possible damages. The standard stipulates specific additional requirements to be considered to meet the above two important objectives of the installations in the following common damp locations, which are covered in the subsequent paragraphs: • Baths, showers and other fixed water containers • Swimming pools, paddling pools and spa pools or tubs • Fountains and water features • Saunas • Refrigeration rooms • Sanitization and general hosing-down operations 10.2 Locations of baths, showers or fixed water containers(Clause 6.2) The requirements specified in this part of the standard apply to electrical installations in locations containing a bath, shower or other fixed water containers (those designed to contain water for normal use but exclude fortuitous containers or areas not intended to contain water for normal operations) and also in locations just adjacent to these areas classified into specific zones, depending on the degree of possibility of water or moisture entering and impacting safety in those zones. 10.2.1 Baths and showers Areas containing baths, showers, etc including surrounding areas are divided into four zones Viz., 0, 1, 2 and 3 and the standard defines the type and specific requirements to be adopted for the electrical installations in each of these four zones. It is to be noted that there are some minor variations to the distances defining the upper limit of boundaries for some of the zones in Australia and New Zealand. Zone 0 shall be the complete interior part of a bath or a shower base which could be either a raised hob or a depression in the floor irrespective of whether the water stagnates for some time or gets drained fast in this area. Zone 1 for a bath (but without shower) shall be the area covered between the following boundary planes: • Zone 0 boundary plane at the bottom, which is generally the top of the curbed bath area • The complete vertical projection planes taken along the sides of the internal rim of the bathing location all around Section 6 - Damp situations 171 • Horizontal plane lying at top above the zone 0 top which is defined at a maximum height of 2.5 metre above zone 0 boundary plane for Australian Installations and at a maximum height of 2.25m above zone 0 boundary plane for New Zealand installations, assuming there is no shower fixed in the bath area. When the bath contains a shower, the vertical projection of zone-1 boundary considered just along the sides of rim in the above case shall be shifted outwards and taken at 1.2 metre radial distance from fixed plumbing connection of the shower, subject to having the plumbing connection of the shower at a maximum height of 2.4metres in Australia and 2.25 metres in New Zealand. Where the height of plumbing connection of shower exceeds 2.4 m in Australia, or 2.25 m in New Zealand, the horizontal plane boundary at top of Zone-1 boundary shall also be extended upwards to the actual height of the plumbing connection, with the vertical boundary on the sides remaining at the same 1.2m. Zone 2 of the bath/ shower area shall be the area contained within the following planes: • The floor plane just outside zone 1 • Area covered between the end vertical projection plane limiting Zone 1 (that might vary depending on presence of shower) and the parallel vertical plane located further outwards at 0.6 m from this Zone 1 vertical projection • The horizontal plane 2.25 m above the floor at the top Zone 3 shall be the area limited by the following planes. • The floor plane outside zone 2 • The vertical plane between Zone 2 end defined above and the parallel vertical plane 2.4 m further external to Zone 2 boundary along the sides • The horizontal plane above Zone 2 top at 2.5 m above the floor in Australia and horizontal plane above Zone 2 top at 2.25 m in New Zealand (depending on shower height) at top • In Australia, Zone 3 includes the area above Zone 2 up to 2.5 m above the floor at top of the bath, whereas it starts from 2.25m in New Zealand. Showers Zone 1 has been clarified for different shower head configurations in 2018 issue of the Standard. Figure 10.1 illustrates these four zones and their limits for a typical bath without a shower in plan view (all dimensions are in meters). 172 Practical Electrical Wiring Standards - AS 3000:2018 Figure 10.1 Plan view defining the classified zone limits of bath without shower and barriers (Source: AS/NZS 3000, Figure 6.1) Figure 10.2 shows the elevation views defining these zone classifications of the bath locations without shower as well as with shower where the plumbing connection is located below a height of 2.25m from the floor level. It can be noted that zone 1 boundary is getting extended upto 1.2m from plumbing connection when provided with shower instead of bath rim end when it is without shower. These figures also depict the 2.5m and 2.25m rules to be applied in Australia and New Zealand. Section 6 - Damp situations 173 Figure 10.2 Elevation views showing classified zone limits of bath/ shower without barriers (Source: AS/NZS 3000, Figures 6.2, 6.4) Though the bath with shower in the figure 10.2 shows an overall dimension of 1.2+0.6+2.4= 4.2m as the end of zone 3, all bath rooms may not extend upto this length. Hence a wall of a room located within this distance from bath area (in any direction) will effectively become the end of zone 3 in that direction. Similarly ceilings, walls with or without windows, doors and floors that are limiting the distances of the surrounding walls in a bath room also will limit the associated zones, as applicable. Further it is possible to reduce or prevent the force of water coming out of the shower by providing some intentional barriers, such as screens, doors, curtains and fixed partitions along the rim or just after the rim. Such barriers which effectively offer adequate and constant protection against spraying water from the shower may also be considered to limit the extent of 174 Practical Electrical Wiring Standards - AS 3000:2018 zone 1 classified in the earlier cases, subject to keeping such barriers upto a height of minimum 1.8metres from the floor level of the bath. Figure 10.3 defines the changes applicable to the limits of zones having a 1.8m high barrier which can be located at ≤ 1.2 meters and accordingly zone 1 end also will get shifted towards the bath location effectively reducing the other zone limits as well, compared to areas having no such barrier. Figure 10.3 Elevation view showing classified zone limits of bath shower with vertical barrier (Source: AS/NZS 3000, Figure 6.11) 10.2.2 Fixed water containers These are permanently installed water containers installed or located above ground to store water for general residential uses made of concrete or any other material. In these installations, only two zones (Zones 0 and 2) are classified in the standard, which is described below. Here it shall be noted that the limiting boundary distances of zone 2 from zone 0 end will vary depending on the capacity of water stored in the container. Zone 0 shall be the area of the interior of the water container Zone 2 for an individual water container with a capacity not exceeding 40 litres and having fixed water outlets shall be the area contained within the boundary planes as described below: • Zone 0 boundary plane at bottom • The vertical plane located 0.15 m away all around the internal rim of the water container in the sides • The horizontal plane 0.4 m from the water container top Zone 2 for water containers having either a capacity exceeding 40 litres or a water outlet through a flexible hose shall be the area contained within the following limits: • Zone 0 boundary at bottom • The vertical plane located 0.5 m away from the internal rim of the water container on the sides • The horizontal plane 1.0 m from the water container top, at the top Figure 10.4 gives the typical limits of the zones for the second case (>40L) defined above. Section 6 - Damp situations 175 Figure 10.4 Classified zone limits for water containers> 40L or with flexible outlets (Source: AS/NZS 3000, Figure 6.11) 10.2.3 Equipment features and protection requirements In the bath, shower and water container areas, the following measures of protection against electric shocks observed in earlier chapters shall NOT be considered and are strictly prohibited, because these measures can not control the water though these may control people. • Protection by means of obstacles to prevent access to live parts • Protection by placing equipments out of reach of the people Hence it is necessary to achieve the required safety requirements by adopting equipments having suitable construction meeting the characteristics needed or avoiding the use/ installation of the items in case the required characteristics can not be met at these locations. It is also to be noted that in these locations as well as in the areas discussed subsequently, an equipment satisfying requirements of one particular zone will satisfy requirements of other lower zones (Note: safety requirements for Zone0> Zone 1> Zone 2> Zone 3) and not vice-versa. Accordingly equipment satisfying zone 0 requirements can be used in all zones, equipment satisfying Zone 2 requirements shall be used only in Zone 2 and 3, and so on. It is necessary to check the suitability of zones for equipment as certified by manufacturers or certifying authorities to take a decision of installing the same at other zones, when such options are explored. Following are some of the rules that shall be considered/ assessed before taking a decision to install a particular electrical item in the shower, bath and water container areas. Except for luminaires, no other electrical devices like sockets, switches and switchboards are permitted in Zone 0 of these areas. Following are the MINIMUM degree of IP classification protection to be offered by the equipments located at respective zones in these areas (Note that only the second numeral of IP classification is important in these areas). • In Zone 0: IPX7 • In Zones 1 and 2: IPX5 in communal baths/ showers; IPX4 in other locations • In Zone 3: IPX5 in communal baths/ showers; No specific limitation in other locations 176 Practical Electrical Wiring Standards - AS 3000:2018 It is to be noted that the degree of protection required in communal areas used by many people exceed the requirements defined for residential areas normally used by limited number of persons. Socket-outlets shall not be installed in Zone 0 or 1. Also socket-outlets shall not be installed within 0.3 metre of the floor of a bathroom, laundry or other similar location where the floor is likely to get drenched. Similarly no socket outlets are permitted in zone 2 and 3 if they fall within 0.3 m of zone 1 boundary. However socket-outlets may be installed within Zones 2 and 3 beyond this 0.3 m limit, in case these socket outlets are protected by an RCD with a fixed rated residual current not exceeding 30mA subject to enclosing the outlets in a cupboard that maintains the minimum enclosure classification applicable for the zone. As a special concession, socket outlets installed in Zone-2 may be without RCD if the appliance used is of the automatic switching type like a shaver supply unit complying with AS/NZS 3194. Similarly socket-outlets installed in Zone 3 supplied as an SELV or a PELV system can also be without RCD protection. Switches and accessories are not to be installed in Zone 0 and also within 0.3 metres of Zones 1, 2 and 3. Beyond 0.3 m, these may be permitted subject to satisfying the minimum enclosure IP category noted above. Switchboards are not permitted in all the zones of these installations. Table 10.1 in a nutshell summarizes the stipulations for areas containing bath, shower and water containers. Table 10.1 Electrical items requirements in classified zones of bath, shower and water container (Source: AS/NZS 3000, Table 6.1) Section 6 - Damp situations 177 10.3 Swimming pools, paddling pools and spa pools/tubs (Clause 6.3) The requirements for spa pools/ tubs are divided into three categories as noted below. • Spa pools/ tubs having maximum capacity of 680 litres are considered to be same as the bath shower we reviewed just above. Accordingly spa pools and tubs upto 680 litres capacity shall follow zone classifications and installation requirements as defined under section 10.2 above. • Spa pools and tubs having capacities beyond 5000 litres are considered to have same characteristics like swimming pools and paddling wheels. The requirements for installations at these locations are given in clause 10.3.1 below along with swimming pools and paddling wheels. • Separate zone classifications are applicable for spa pools/ tubs having 680 to 5000 litres capacity and these are defined in the subsequent section 10.3.2. It may be noted that similar to the bath areas, ceilings, walls with or without windows, doors and floors, barriers and fixed partitions, e.g. a 1.8 m solid fence, that limit the extent of a room or area containing a swimming pool, paddling pool, spa pool or tub and fixed partitions that provide effective protection against spraying or splashing water, will limit the associated zones defined for these areas. 10.3.1 Swimming pools, paddling pools and spa pools/tubs > 5000 litres Three zones zone 0, 1 and 2 are applicable in these areas, as defined below: Zone 0 shall be the area of the interior of the water containing part of the swimming pool or paddling pool upto its brim level. Zone 1 shall be the area limited between; • Zone 0 limit and surface expected to be occupied by persons on the sides of the pools/ tubs at the bottom • a vertical plane 2.0 m from the internal rim of the water container along the sides • The horizontal plane upto 2.50 m above the floor or the surface at the top of the pool/ tub 178 Practical Electrical Wiring Standards - AS 3000:2018 In addition following considerations shall be applied for zone 1, when the pool contains a diving board, springboard, starting block or a slide: • vertical plane situated 1.50 m all around the diving board, springboard, starting block or slide • Horizontal plane 2.50 m above the highest surface expected to be occupied by persons at the top Zone 2 shall be bounded by the planes as noted below: • Area between the vertical plane limiting Zone 1 and the parallel vertical plane 1.50 m external to Zone 1 • the floor, or surface expected to be occupied by persons at the bottom • The horizontal plane 2.50 m above such floor or surface at the top 10.3.2 Spa Pools or Tubs between 500 to 5000 litres capacity For capacities from 500 to 5000L, following defines the zone limits. Zone 0 shall be the area of the interior of the spa pool or tub. Zone 1 shall be the area limited by: • Zone 0 at the bottom • the vertical plane 1.25 m from the internal rim of the pool or tub and the floor, or the surface expected to be occupied by persons along the sides and • The horizontal plane 2.50 m above the floor or surface at the top Figures 10.5 and 10.6 give some typical illustrations reproduced from AS/NZS 3000 showing the above definitions. Figure 10.5 Classified zone limits for in-ground swimming pools (Source: AS/NZS 3000, Figure 6.15) Section 6 - Damp situations 179 Figure 10.6 Classified zone limits for spa pools / tubs not exceeding 5000 litres capacity (Source: AS/NZS 3000, Figure 6.18) 10.3.3 Electrical installation requirements Following requirements shall be considered for the electrical items to be installed within the various zones of swimming pools, paddling wheels and spa pools/ tubs discussed above. As like bath areas, protections by means of obstacles or by placing items out of reach are NOT permitted in these areas. Where electrical equipment is in contact with pool water, failure of insulation may result in a hazardous voltage appearing across or through the pool water. A very low voltage is sufficient to present a hazard to persons immersed in the water. Protective measures to be considered are; • locating the electrical equipments at a considerable distance away from these locations with all plumbing connections made of non-conductive material • Metal grids or barriers inserted in any plumbing connections between the electrical equipment and pool and connected to the equipotential bonding system • Use of an RCD with a fixed rated residual current not exceeding 30 mA to protect circuits supplying Class I (earthed conductive parts) equipments installed in these areas Following are the IP classifications permitted in the respective zones for the enclosures of the electrical live items to be installed in these areas; • Zone 0: IPX8 • Zone 1: IPX5 • Zone 2: IPX4 The wiring systems installed in these areas shall be able to prevent entry of moisture and water. Accordingly bare aerial conductors shall not be installed above Zones 0, 1 or 2. Other types of aerial (insulated) cables may be installed subject to meeting the safety clearances defined in the earlier chapter (Section 3, Clause 3.12 of AS/NZS 3000). 180 Practical Electrical Wiring Standards - AS 3000:2018 Socket-outlets shall not be installed in Zone 0. However these may be considered in zone 1 area subject to meeting ALL the following conditions: • Enclosure having the required ingress protection • Outlets located at a height of not less than 0.45metres above the ground level and at a horizontal distance beyond 1.25 metres from the internal rim of the water container • Supplied from an independent circuit or operation at SELV/PELV or controlled by RCD having less than 30mA sensitivity For zone 2, the first and third of the above conditions shall apply and there is no restriction of distances for locating the devices from zone 1 boundary limit. The luminaires, appliances and other standard electrical equipment are permitted in all zones of these areas subject to meeting enclosure IP classification and designed/ constructed for use at swimming pools, etc. Further the following additional requirements shall be met. Zone 0 luminaires, appliances, etc shall be rated and supplied as below: • Shall be rated below 12V AC/ 30V ripple free d.c. • Shall be operating as SELV/ PELV system • Shall be supplied from a source located outside zone 0 Zone 2 luminaires, etc shall meet ANY ONE of the following requirements: • Shall be supplied as an SELV/ PELV system • Shall be of class II (double insulation) construction • Shall be class I type with earthing and RCD backup protection against current leakages Table 10.2 summarizes the stipulations to be considered in swimming pools, paddling wheels and spa pools/ tubs for ready reference. Table 10.2 Electrical items requirements in classified zones of swimming pools, paddling wheels or spa pools/ tubs (Source: AS/NZS 3000, Table 6.2) Equipment Zone 0 Zone 1 Zone 2 In the following table, all multiple conditions numbered with i), ii), etc shall be considered together for a zone, where given. Socket – Outlets Not permitted Switches/ accessories Not permitted Not permitted for general use. (i) IPX4 AND (ii) (a) separated supply For pools, equipment satisfying OR (b) SELV/PELV all i, ii and iii below are supply acceptable OR (c) RCD protection (i) IPX5 AND (ii) (a) ≥0.45 m high and ≥1.25m from internal rim OR (b) under and ≥0.5 m from edge of fixed continuous horizontal barrier ≥1.25m wide (iii) (a) separated supply OR (b) SELV or PELV supply OR (c) RCD protection IPX5 IPX4 Section 6 - Damp situations 181 Appliances, Luminaires and other equipment (i) IPX8 AND (i) IPX5 AND (ii) cerified for use (ii) (a) SELV or PELV supply AND OR (iii)12V a.c./30 V d.c. (b) Class II construction SELV or PELV OR (c) Class I construction supply from source fixed in position and outside zone AND RCD protection (iv) No earth (i) IPX4 AND (ii) (a) SELV/ PELV supply OR (b) Separated supply OR (c) Class II construction OR (d) Class I construction and RCD protection Heating cable systems Not applicable Permitted where embedded in the floor area under the Zone and protected with earthing (Refer previous chapter) As for Zone 1 Switchboards Not permitted Not permitted Not permitted Electricity generation Systems Not permitted Not permitted Not permitted Electricity distributor’s electrical equipment Not permitted Not permitted Not permitted 182 Practical Electrical Wiring Standards - AS 3000:2018 10.4 Fountains and water features (Clause 6.4) In addition to taking care of reduced body resistance and increased chances of contacts with live parts, the requirements under this section are also intended to protect electrical material and electrical equipment from the corrosive effects of chemicals used in the treatment of water in fountains and water features. However it is to be noted that the stipulations given under this section need not be applied for fountains or water features which comply with any of the following: • the depth of water is within 300mm or • Suitable means are provided in these areas to restrict entry of persons to the water Similar to the other areas, ceilings, walls with or without windows, doors and floors that limit the extent of a room or area containing a fountain or water feature and fixed partitions that provide effective protection against spraying or splashing water, limit the associated zones defined below. 10.4.1 Zone definitions Two zones (Zones 0 and 1) are classified for fountains and water features: Zone 0 shall be the area of the interior of the water storing part including any recesses in their walls or floors or the interior of water jets or waterfalls. Zone 1 shall be the area limited by: • Zone 0 limit at the bottom • the parallel vertical plane 2.0 m from the internal rim of the water containers on the sides • The floor or surface expected to be occupied by persons in the immediate surroundings and the horizontal plane 2.50 m above the zone 0 boundary plane When the fountain or water feature contains sculptures and decorative water containers, following areas shall be suitably added/ extended for zone 1: • Parallel vertical plane situated 1.50 m around the sculptures and decorative water containers at the sides • Horizontal plane 2.50 m above the sculptures and decorative water containers at the top Figures 10.7 and 10.8 give typical zones for a fountain and water feature discussed above. Section 6 - Damp situations 183 Figure 10.7 Zone boundary limits for fountains and water features – Plan view (Source: AS/NZS 3000, Figure 6.20) Figure 10.8 Zone boundary limits for fountains and water features – Elevation view (Source: AS/NZS 3000, Figure 6.21) 184 Practical Electrical Wiring Standards - AS 3000:2018 10.4.2 Electrical equipment features/ installation As like other areas, protections by means of obstacles or by placing items out of reach are NOT permitted in these areas. Protective measures to be considered are: • earthed system with RCD protection having a fixed rated residual current < 30 mA or • supplied at either extra-low voltage or low voltage through an isolating transformer complying with AS/NZS 61558, but not earthed Degree of protection of enclosures in these zones shall meet the following minimum classifications: • In Zone 0: IPX8 • In Zone 1: IPX5 Wiring systems for a fountain or water feature shall be installed so as to prevent entry of moisture to any connection and water siphoning through any wiring enclosure or cable. The types recommended are elastomer or thermoplastic insulated and sheathed copper cables or flexible cords suitable for immersion in the type of water being used. Where these wiring systems are likely to face mechanical damages, installing these in a wiring enclosure is recommended. Socket-outlets shall not be permitted in Zone 0 or Zone 1.Switches and other accessories shall not be installed in Zone 0. However switches and other accessories may be installed in Zone 1 subject to providing the required IP enclosure. Luminaires, appliances and other electrical equipment shall be permitted where designed and constructed specifically for use in a fountain or water feature and provided with the required degree of protection. In addition the following conditions shall apply: • Zone 0 luminaires, appliances, etc shall be operated as SELV/ PELV system and supplied from a source located outside zone 0 with a nominal rating of below 12V a.c./ 30V ripple free d.c. These shall not be provided with earthing in accordance with the ELV supplied luminaire requirements we studied in the chapter on earthing recommendations (Section 5 of the standard) • Zone 2 luminaires, etc shall be supplied as an SELV/ PELV system or shall be of class II (double insulation) construction or shall be of class I construction with earthing and 30mA RCD backup protection against current leakages. NO switchboard shall be installed within the classified zones similar to the other areas discussed earlier. 10.5 Locations containing sauna heaters (Clause 6.5) There is no zone 0 applicable for rooms or enclosures containing heating equipment used exclusively for sauna heating. Three zones 1, 2 and 3 are defined for these applications. Zone 1 shall be limited by; • Parallel vertical plane 0.5 meter from the external edge of the sauna heater on the sides • floor, or surface expected to be occupied by persons at the bottom • The cold side of the thermal insulation of the ceiling at the top Zone 2 shall be the area limited by; • vertical plane between Zone 1 and the cold side of the thermal insulation of the walls of the sauna room or enclosure at the sides • floor, or surface expected to be occupied by persons at the bottom • The horizontal plane 1.0 m above the floor at the top Section 6 - Damp situations 185 Zone 3 shall be the area limited by the; • Same as zone 2 limit on the sides • Location between horizontal plane 1.0 m above the floor and the cold side of the thermal insulation of the ceiling at the top Figure 10.9 shows typical sauna heater area defining the zones indicated above in the elevation view. Figure 10.9 Zone boundary limits for sauna heaters – Elevation view (Source: AS/NZS 3000, Figure 6.22) As like other areas, protections by means of obstacles or by placing electrical items out of reach are NOT permitted in these areas. Installation of electrical equipment and wiring in classified zones shall consider the following stipulations: • Only electrical equipment belonging to the sauna heater shall be permitted in zone 1 • Zone 3 Electrical equipment shall be suitable to withstand a minimum temperature of 125°C and the insulation of conductors shall be suitable to withstand a minimum temperature of 170°C • There are no special requirements concerning heat resistance of electrical equipment in zone 2, except for meeting enclosure IP classification Any equipment in these areas, other than sauna heater, shall be protected by an RCD with a fixed rated residual current < 30 mA. Degree of protection required for electrical enclosures shall be at least IPX4B or IP24 for all permitted items within the sauna room. Wiring systems should be installed outside the zones, on the cold side of the thermal insulation. If the wiring system is installed in Zone 1 or 3 on the warm side of the thermal insulation, the system shall be heat-resistant type meeting the maximum temperatures indicated above. Metallic sheaths 186 Practical Electrical Wiring Standards - AS 3000:2018 and metallic conduits shall not be accessible in normal use. Suitable types of wiring systems recommended are insulated, unsheathed cables in non-metallic enclosures or sheathed cables. Socket-outlets, switches and other accessories shall not be installed within a sauna room or enclosure except those forming part of the sauna heater. A switchboard shall not be installed within any classified zone of a sauna heater. 10.6 Refrigeration rooms (Clause 6.6) These are increasingly used as freezers or cold rooms to refrigerate and preserve food articles and some other items. These are rooms bounded by walls with insulations and temperatures maintained at same value in all parts of the room. Hence in these rooms only one zone (no need of numbering) is applicable, which comprises of all of the area within the refrigeration room. As like other areas, protections by means of obstacles or by placing items out of reach are NOT permitted in these areas. Electrical equipment within the room shall have protection classification of at least IPX4B or IP24 Wiring in these areas shall be of a type that will not be affected by the operating temperature of the room and that will not provide pockets or channels in which moisture might accumulate, or allow to get passed into electrical equipment. PVC cables are not to be considered in these areas due to sub zero temperature which are susceptible to failures due to possibilities of bending, flexing or vibration at temperatures below approximately 0°C. Following wirings are permitted for use in the refrigeration rooms: • Unenclosed sheathed cables including MIMS cables • Insulated or sheathed cables enclosed in a wiring enclosure that has adequate draining facilities Sealing shall be done with a compound that does not set hard for each wiring enclosure at points passing from refrigerated to non-refrigerated space and at cable entry points into motors, luminaires, switches, etc. Socket-outlets, switches/ accessories and controlgear having the required degree of protection and that are permanently sealed shall alone be used in these areas. Lamp holders shall be the all-insulated type or any other suitable type that precludes the possibility of any external metal portion becoming live. Lamp holders shall not be suspended within 2.50 m of the floor or ground with a flexible pendant. Fixed appliances shall be fitted with internal heaters or in enclosures that would prevent the retention of moisture in addition to meeting the IP classification, as specified. A switchboard shall not be installed in a refrigeration room. 10.7 Sanitization and general hosing down areas (Clause 6.7) Some of the well known areas where sanitization and hosing down operations are frequently carried out are as below: • Areas keeping livestock • Areas producing feed, fertilizers, vegetable or animal products or where these items are stored, prepared or processed • Areas growing plants, such as greenhouses or hydroponic installations • Areas where agricultural or horticultural products are produced, prepared or processed, e.g. dairies, drying, stewing, pressing out, fermenting, butchering, meat processing, etc • Car wash bays, etc. Section 6 - Damp situations 187 Here also just one zone is classified which comprises of areas that are normally affected by the sanitization and hosing down operations and shall generally be bounded by the following: • Location between the floor or the base of a recess in the floor and a horizontal plane 2.0 m above this floor top • Side walls enclosing the area of these operations • Location on a ceiling within 1.0 m of walls surrounding the area As like other areas, protections by means of obstacles or by placing items out of reach are NOT permitted in these areas. Degree of protection for enclosures shall be minimum IPX5 where low or medium pressure hosingdown is used and shall be minimum IPX6 in areas where high pressure hosing is adopted. Though switchboards are allowed only in these damp areas, it is subject to maintaining the minimum degree of protection of IPX6. The switchboards and wiring enclosures shall ensure adequate protection against water and moisture entry into the electrical items by proper sealing. 10.8 Summary Section-6 of AS/NZS 3000 specifies the rules applicable for electrical systems and installations in the damp areas like bath, shower, swimming pools, fountains, etc, where water presence exists all the time or most of the time. Such damp areas affect the moisture content and humidity in the surroundings also which will directly impact the insulation of electrical systems. There are also more chances for getting direct contacts to live conductors through water used in these areas. Further, persons exposed to damp areas have their body resistance considerably reduced which increases the chances of shock currents due to low touch potential possible in these areas. Hence the electrical installations shall be able to offer adequate safety protection against possibilities of shock currents and water/ moisture issues by choosing proper enclosures for electrical items and taking other safety precautions in these areas. The standard divides each of these damp areas into different zones suffixed with numerals 0, 1, 2, etc indicating the severity of water exposure chances in a particular zone for a particular application. The lower the numeral, higher are the chances for electrocution demanding additional safety precautions in such zones compared to zones suffixed with a higher numeral. Zone 0 in case of baths, fountains, water containers etc are the parts carrying water and no electrical items are permitted in zone 0 except for luminaires subject to limiting their operating voltages and using certified items, etc. Zone 1 is usually defined upto some distance on the sides and upto some height from zone 0 boundary top with distances in the order of about 1.5metres to 2.5meters. Areas beyond zone 2 are classified as zone 3 upto some distances/ height away from zone 2 limits. A barrier with a minimum height of 1.8 metre at boundary of zone 0 as well as walls, ceilings, windows, etc around the damp areas normally limit the extents / dimensions of these zones. This barrier could be simple screens in bath/ shower areas and shall be solid walls in most of the other areas like swimming pools, etc. No switchboards are permitted in any of these installations, except in areas where hosing down operations are carried out. It is necessary to ensure all enclosures are adequately protected with proper IP category usually having its second digit in the order of 7 or 8 for items located in zones 0 and 1 of specific installations; with second digit of 4 or higher for items located in zone 2 and 3 in most of the installations. It is also necessary to consider RCD protection or SELV/PELV systems in most of the areas, mainly in classified zones 0 and 1 to minimize the possibilities of shock currents and the associated hazards. 188 Practical Electrical Wiring Standards - AS 3000:2018 11 Section 7 - Special Electrical Installations Section 7 of AS/NZS 3000 defines requirements to be met by specific installations that necessitate special attention due to their functions or unique characteristics and the same are covered in this chapter. We will discuss the requirements for safety services that come into prominence during emergency situations like fire, etc. Our study will also cover the specific requirements for captive electricity generating systems used in electrical installations as alternative supply. The chapter also includes the basic requirements of separated supply systems and the features of SELV and PELV systems that are extensions to these separated supply systems. We will also go through the stipulations given in the standard regarding HV installations, hazardous area requirements and temporary installations like demolition sites, shows and carnivals, etc. Learning objectives • • • • • • • Requirements for safety services Requirements for Electricity generation systems Protection by electrical separation Requirements for Extra-low voltage electrical installations Requirements for High voltage electrical installations Requirements for explosive hazard areas Requirements for other installations like demolition sites, shows and carnivals, etc. 11.1 Applicable areas (clause 7.1) This section covers the minimum requirements to be adopted in the design, selection and installation of electrical systems for the following services/ installations: • Electrical systems feeding safety services • Electricity generation systems • Systems supplied by electrical separation • Extra-low voltage electrical installations • High voltage electrical installations • Installations in areas where an explosive hazard may arise • Electrical installations of construction and demolition sites, electro medical treatment areas; relocatable installations and the sites, marinas and recreational boats, shows and carnivals, shows and carnivals, cold cathode illumination systems, telecommunication networks power supplies, cranes and hoists, lifts, generating sets, 188 Practical Electrical Wiring Standards - AS 3000:2018 outdoor sites under heavy conditions, electric fences; and film, video and television sites. 11.2 Safety services (Clause 7.2) The term ‘safety services’ refers to parts of the electrical installation in building areas that are essential for the safe operation of the important services like fire detection, fire alarm and extinguishing systems, smoke control systems, evacuation systems such as lifts, etc., The power supply to these services cannot be bypassed or kept on hold under any circumstances as otherwise it could compromise the protection to people and properties within the building. The rules for safety services are intended to ensure that electricity supply is not inadvertently disconnected for electrical equipment that are required to be operated during emergency conditions, especially where there is no alternative supply to feed such demanding services. These were named as “emergency services” till the previous edition of this standard. The supplies associated with these services are generally prefixed with “emergency” and/or “essential” in the building codes of Australia and New Zealand. Fire and fire control equipment in major buildings comprise generally all the following parts: • Fire hydrant pumps to pump water in fire water lines for different locations to control the fire • Pumps to feed for automatic sprinkler systems, water spray or deluge systems and similar fire-extinguishing systems • Pumps feeding through fire-hose reels, where such hose reels could be the only means of fire protection to spread water, i.e. in locations where fire hydrants and automatic fire-sprinkler systems are NOT installed • Fire detection and alarm systems to initiate prompt actions at the correct times • Air-handling systems that are required to exhaust fumes and gases and to control the spread of fire and smoke during fire accidents The expression ‘safety services’ generally excludes items which do not affect the operation of the safety equipment like the following: • Escalators or moving walkways (travelators). • A lift in a single private residence that is installed in accordance with AS/NZS 1735.18 need not comply with the requirements of this Clause (Clause 7.2) • Lifts that are not defined as emergency lifts in the National Construction Code (NCC) or New Zealand Building Code (NZBC) • Pumps for ‘jacking’ or water pressure maintenance, the failure of which does not deprive the fire hydrant or sprinkler pump of adequate water supply. • Fire detection, alarm and intercom systems with battery backup complying with AS 1670 or NZS 4512 • Smoke alarms installed in single private residences (see Clause 4.6 for information relating to smoke alarms). Evacuation equipment coming under safety services include intercom/speaker systems used under emergency conditions, emergency lighting systems in egress paths, lifts used for carrying people (excluding lifts in residential houses), etc. Following are the essential requirements to be met by the supply systems feeding safety services: • Separation of supplies feeding safety services from supplies that are feeding rest of the installation/services • Incorporation of properly discriminated protective devices • Providing alternate sources of power supply The following paragraphs define the minimum regulations for implementing the above features in the electrical systems controlling safety services. Section 7 - Special Electrical Installations 189 11.2.1 Separation of supply Separation refers to provision of isolation switches to separate or independently control supply to an area without disturbing other areas, which is a fundamental safety concept we discussed earlier. In regard to power supply for safety services areas, it is stipulated that each part of an electrical installation supplying a safety service shall be controlled by a main switch or switches that shall be independent of other switches used to control the remainder of the electrical installation. It is necessary that the control circuits of the safety services are also made independent similar to the power circuits. The switches controlling various services in an installation are to be typically segregated / arranged as per figure 11.1 Figure shows the main isolation switch, and the separation switches controlling the safety services, doing the separation function, we are discussing here. Figure 11.1 Typical supply separation for safety services (Source: AS/NZS 3000, Figure 7.2A) The safety services in a building structure that is fire-separated portion of a main building (usually separated by 120 minutes fire rated walls) or structure that is regarded as a separate building (out building) shall also be provided with independent switches for controlling the internal safety services. These switches in such independent buildings shall be separated from the switches controlling other parts as well as other types of safety services in the main premises. Similarly the lifts intended for safety services for emergency fighting and emergency evacuation shall be provided with switch controls independent of switches controlling supplies to the other common lifts within the same building. All these main switches of the safety services and their connections shall ensure the following: • They shall not be controlled by any main switch/ switches of the general electrical installation • Accordingly, these shall be connected on the supply side of applicable general installation main switches so that these services continue to receive power supply even when the upstream main switch is operated for isolation. This condition may not be applicable for safety services provided with alternative supplies, high voltage main switch, etc. • They shall control only electrical equipment that is regarded as safety services, exception being the lighting and socket-outlet circuits in rooms housing fire hydrant 190 Practical Electrical Wiring Standards - AS 3000:2018 • • • • • • or sprinkler pumps subject to incorporating properly rated over current and RCD protection in these circuits No switch shall be introduced between the main switch of safety services and switchboards from which safety services supply is derived These switches shall be adequately protected against mechanical damage in case their location or conditions of use warranting the same All these switches shall be kept closed (ON) under normal conditions. These might be kept OFF only by authorized personnel or under maintenance after ensuring alternate safety system/ necessary precautions. Identification and labeling shall be legible and easily locatable using contrasting colour to help for easy operation under emergency conditions. These switches shall have caution notice marked “IN THE EVENT OF FIRE, DO NOT SWITCH OFF’. The wiring systems used in power supply and control of safety services equipment shall be capable of maintaining an adequate supply to such equipment when exposed to fire. It is preferable to consider wiring systems of specific WS classification in line with AS/NZS 3013 It shall be ensured that the conductors of safety services are not enclosed with different safety services or with conductors of any other system. Adopting a segregation of atleast 50mm or providing effective barrier from the other service conductors is recommended when the safety service wiring systems are to be run without enclosures. The fire water pump motors may generally be designed for automatic operation upon detection of fire with their main power contactors controlled from remote. It is necessary to provide a manually operated isolating switch on the supply side of such automatically controlled pump motor controller which shall remain ON under all normal conditions. This switch shall be installed adjacent to or on the pump motor controller panel and shall be provided with a device for locking the switch in the closed (ON) position to avoid inadvertent opening. 11.2.2 Protective devices and discrimination It is necessary that protective devices against fault currents shall be avoided in safety systems where the operation of the protective devices may pose more danger than the fault currents themselves. However where overcurrent protective devices are provided, these shall be selected such that a fault on one safety service will not result in loss of supply to other safety services and a fault on the general electrical installation will not result in loss of supply to safety services. To ensure proper discrimination with circuit breaker and high starting currents of the large size motors used in such systems, the characteristics of overcurrent protective devices provided on circuits supplying fire-pump motors shall meet ALL the following requirements: • Inverse time characteristic • Rated to carry 125% of the full-load motor current continuously or shall have to match 125% of the circuit-breaker setting adopted • Shall open the circuit in not less than 20 seconds at 600% of the full-load motor current after taking care of currents during start up • Where a single device protects multiple motors in a group, it shall be selected with rating equal to 125% of the sum of the all motor rated currents and 600% rated current of the largest motor in the group It is also necessary to AVOID over temperature protection for fire-pump motors as the operation of these devices might reduce the operating time of these pumps during emergencies. The control and interlocking circuit for automatic operation of fire-pump motor shall meet the following stipulations: • It shall be directly fed from the active and neutral conductor of the pump circuit • Shall be arranged to ensure that the active conductor of the control circuit is directly connected to the coil of the operating device within the starter Section 7 - Special Electrical Installations 191 • It shall not be provided with additional overload protective devices other than those provided for the pump-motor main circuit 11.2.3 Alternative supply systems Alternative supply systems in low voltage installations are usually diesel generating sets or similar ones used to generate power supply at the same nominal voltage and frequency as the mains supply. These are brought into operation to maintain continuous supply to safety services in case of failures or maintenance of the main power supply feeding the building. In such installations, a changeover switch is adopted to feed the safety services to choose the power source. This changeover switch shall be installed on the main switch board to enable connecting the safety services from the alternative source, when it is needed. It shall be necessary to have a reasonably accurate assessment on operating loads of different safety services to ensure that the generating sets and other independent sources of supply are selected with adequate capacity to supply all the safety services simultaneously. While doing such sizing, allowance would also be required for motor start-up by plant sequencing and for motor starting currents, as applicable. 11.3 Electricity Generation Systems (clause 7.3) The requirements stipulated under this part of the standard either supplement or amend the requirements of Sections 2 to 6 of AS/NZS 3000 covered so far. These stipulations are applicable for all types of electricity generation systems that supply power directly to an electrical installation or a part of it, either continuously or whenever demanded, whether standalone set or operated in parallel with grid. The rules are applicable for the following alternative sources normally adopted in low voltage installations: (a) Alternative and supplementary supply: A generator set, typically combustion engine-driven, that— (i) provides an alternative or stand-by ac electricity supply in the event of failure of the normal power supply to the installation; or (ii) is used as the primary power supply to an electrical installation; or (iii) is used as part of a stand-alone power system. (b) Stand-alone power system: A system that is not connected to the power distribution system of a network provider. Stand-alone systems may be supplied with power from one or more of the following: (i) Photovoltaic array (ii) Wind turbine or mini-hydro turbine (iii) Engine driven generator set in the form of an ac supply or a dc supply. (c) Inverter system: An inverter system that provides an ac power supply from an interactive inverter using a renewable energy source, such as photovoltaic, wind turbine or mini-hydro turbine. In the event of the renewable energy output available exceeding the electrical installation load, subject to formal approval of the electricity distributor, any surplus energy available is exported into the distribution system. If the output available from the renewable energy sources is insufficient for the installation loading, the shortfall in energy required is imported from the network. The interactive inverter of the system also provides control of the exporting and importing of energy from the system and network. (d) Battery system A battery system that provides supply from an alternative energy source, such as a generator set, photovoltaic array, wind turbine or mini-hydro turbine, to charge a battery bank and provide a d.c. supply to an electrical installation. Individual AS/NZS publications are available covering each of the above systems and it is necessary to refer those applicable standards for proper selection and features to be applied in these systems. The following paragraphs give the minimum standards to be considered for these systems. 192 Practical Electrical Wiring Standards - AS 3000:2018 11.3.1 Control and protection requirements The supply output from an alternative generation source shall be controlled by an isolating switch or switches located just at its terminal ends or at the installation switchboard from which the alternative source feeds supply to the installation. In addition suitable control switches or devices shall be provided for starting and stopping electricity generation system. In case multiple switch or devices are used for this purpose they shall be grouped together and clearly identified. The electrical system of the generation unit shall be so arranged that it shall not be able to backfeed its generated power upstream to the grid from the point of its connection in the installation, by adopting suitable interlocks. However in some installations the backfeeding of excess power to the grid might be allowed, like installations having cogeneration/ captive power generating units operating in parallel with the supply grid. This is allowed subject to incorporation of proper protective devices and after entering into an agreement with utility company. The isolating switch(es) used to control the supply output from a generating unit shall be installed adjacent to or on the electricity generation system so that a person operating the switch has a clear view of any person working on the electricity generation system. The switch may be combined with overcurrent protection (like MCCB/ACB). These shall have manual operating provision and the manual operation shall NOT be overpowered through intentional/ accidental bypassing or by internal controls of the unit like a programmable control systems, etc. Where batteries form part of the generating system, these shall also be controlled by an independent switch located just adjacent to the batteries or controlled together with the main power isolating switch. Generating systems shall be provided with the following minimum protections generally complying with the rules discussed in the earlier chapters. • Overcurrent protection • Short circuit and earth fault protection • Protective earthing Overcurrent/ overload protective devices of power generation systems shall be located as close as practicable to the output terminals of the electricity generation system. It shall be ensured that the unprotected interconnecting conductors to an electrical installation are as short as practicable and shall never be more than 15 metres in length. It is necessary to assess the short circuit ratings of such systems and to incorporate devices having adequate capacity to withstand the effects of such fault currents. Where these generating units operate in parallel with grid the possible circulating harmonic currents in such systems shall be limited by using compensating windings in the generator or by implementing suitable filters, impedance, etc. Where changeover switches are employed for feeding the generated alternative power, the changeover device shall open all active conductors of the normal supply when the alternate supply is getting connected to the installation. Figure 11.2 shows the changeover arrangement involving 4 poles of main source and generator. Where three pole switches are employed, the neutral of the generator will be directly connected to the earth without the fourth pole. Section 7 - Special Electrical Installations 193 Figure 11.2 Alternative supply connection to a switchboard with 4 pole changeover switch and a local MEN connection (Source: AS/NZS 3000, Figure 7.3) The method of connection of a grid-connected inverter system shall be in accordance with the AS 4777 series of Standards and shall also meet any stipulations by the electricity distributor. Figure 11.3 shows typical grid connected system and the change over arrangement normally agreed by supply distributors. Figure 11.3 Typical grid connection of alternative supply with inverter (Source: AS/NZS 3000, Figure 7.7) In stand alone generator system (generator not operating in parallel with the grid), the consumer installation mains requiring alternate source of supply shall be connected directly from the output of the electricity generating system, typically as shown in figure 11.4. This shall be provided with a local MEN connection like in the utility supply. 194 Practical Electrical Wiring Standards - AS 3000:2018 Figure 11.4 Typical connection of standalone generator with local MEN connection (Source: AS/NZS 3000, Figure 7.4) 11.3.2 Neutral and earthing connections The generation system shall incorporate protective earthing in line with AS/NZS 3000 section 5 stipulations and MEN connections, exception being generators rated below 25kVA but only when used as separated supply. The neutral to earth connection (MEN connection) of the generation system shall also be made within the installation at the switchboard to which the electricity generation system is connected. The incoming neutral of a generator to its main MEN switchboard shall be directly connected without any switch. However, where multiple engine-driven generating sets are operated in parallel, the connection to the neutral point of the windings of each generating set to earth shall be controlled through independent isolating switches. This is to ensure that only one neutral point of any one of the generators is connected to earth at any time of parallel operation to avoid circulating currents through these sets. It shall also be necessary that neutral and earth conductors of a set are not operated in parallel, except when the conductors are adequately rated to carry the maximum rated fault current of the generator distribution system. 11.4 Electrical Separation (Clause 7.4) Electrical separation refers to isolated supply, where the supply to a load is isolated from the main source by adopting isolation transformers of suitable ratings with ratio of 1:1 or downwards, being common in LV systems. Protection by electrical separation is one of the recognized methods of safety in the standard and is recommended to prevent shock current due to contact with exposed conductive parts that get energized during internal faults. 11.4.1 Typical arrangement A separated supply could be achieved by any one of the following alternatives • Using an isolating transformer with its output supply separated from the mains input with use of double insulation or equivalent • Connecting a generator output having its output separated from the frame of the generator • An isolated inverter similar to the isolating transformer The separated supply shall meet all the following requirements: Section 7 - Special Electrical Installations 195 • • • • Separated circuit voltage shall not exceed 500 Volts All live parts of a separated circuit shall be reliably and effectively electrically separated from all other circuits, including other separated circuits and earth within the same installation The earthing connections are prohibited in these systems. Exposed conductive parts of electrical equipment supplied by a separated circuit shall NOT be connected to the protective earthing conductor or to the exposed conductive parts of the source of supply. Cables and supply flexible cords to electrical equipment from separated supply shall be protected against mechanical damages or otherwise arranged so as to ensure that any damage that might occur is readily visible to ensure easy detection and to minimize faults Figure 11.5 gives different types of separated supplies and their connection possibilities as recognized in the standard. 196 Practical Electrical Wiring Standards - AS 3000:2018 Notes referred in the figure: 1 If Class II, omit earth connection from final subcircuit. 2 Transformer or generator output protections may adopt a double-pole circuit breaker or HRC fuse. 3 Equipotential bonding conductors of sockets must be insulated and NOT connected to earth. In case of multiple socket outlets all earth pins shall be interconnected but isolated from earth. 4 An RCD cannot serve the purpose when the equipotential bond is connected to the frame of the generator Figure 11.5 Typical separated supply sources and their connections (Source: AS/NZS 3000, Figure 7.8) It might be quite possible that a separated circuit feeds supply to multiple equipments in an installation. In such cases, the exposed conductive parts of all those equipments shall be connected together by an insulated equipotential bonding conductor. It shall also be ensured that this bonding conductor is separated and is not connected to earth or a protective earthing conductor or exposed conductive parts of another circuit or another separated circuit or any extraneous conductive parts in the installation. In multiple equipment systems it is also necessary to take care that all the following are connected to the equipotential bonding conductor • Earthing contact of all socket-outlets • Earthing conductors in any supply cable or flexible cord installed on the separated circuit. The multiple equipment system connected from separated supply requires the following stipulations also to be met. • Exposed conductive parts of the source of supply that are earthed, shall not be simultaneously accessible with any exposed conductive part of the separated circuit. • A protective device shall operate to disconnect the separated circuit automatically in the event of two faults resulting in exposed conductive parts being connected to live parts of different polarity. • If the protective device is a circuit-breaker, the protective device shall open in all unearthed conductors substantially together. 11.4.2 Verification The separation adopted in each of the separated circuits shall be checked physically and verified by proper tests in addition to the other verification guidelines applicable for electrical installations as per section 8 of the standard, covered in the next chapter. The measurements shall be made using a 500V dc insulation resistance tester to find values of the insulation resistance across the following: • Separated circuit and the transformer primary winding, if a transformer is the source of the separated supply • Separated circuit and any other wiring • One separated circuit and any other separated circuit • Separated circuit and earth • Exposed conductive parts and earth • Exposed conductive parts and earth contact of a socket-outlet in single equipment systems In case of multiple equipments connected from separate supply, the insulation resistance measurements would be needed across the following: • The separated circuit and the equipotential bonding conductor • Equipotential bonding conductor and earth • Equipotential bonding conductor and any equipotential bonding conductor of another separated circuit in the installation Insulation resistance obtained by all such measurements shall be a minimum of 1 MΩ. Section 7 - Special Electrical Installations 197 In addition, the continuity of bonding conductors shall be checked by measuring resistance of the equipotential interconnections in the separated circuit. The resistance values so measured shall not exceed 0.5Ω 11.5 Extra-low voltage electrical installations (clause 7.5) As we have seen, the voltage value is one of the main components deciding the shock current values and separation is able to achieve safety from the intricacies of the main supply. The extra voltage installations covered in this section try to achieve both these benefits by having separated supplies with lower operating voltages not exceeding 50V ac or 120V ripple-free dc. Following are the recognized extra low voltage systems. • Separated extra-low voltage (SELV) where no protective earthing is adopted. • Protected extra-low voltage (PELV), where one conductor of the output circuit is earthed Both PELV and SELV systems shall meet the following basic requirements: • The source of supply shall be so arranged that nominal operating voltage shall not have the possibility of exceeding the limits of 50 V ac or 120 V ripple-free dc • Live parts of the circuits shall be electrically segregated from each other and from circuits at higher voltages An electrical installation operating at extra-low voltage but not complying with the above requirements shall be deemed to be operating at low voltage and shall be subject to the relevant requirements of other sections of the wiring rules. Following are the recognized ways of arranging SELV and PELV systems. • A safety isolating transformer complying with AS/NZS 61558 to step down to the required range of ELV values • A source of current that is independent of voltages. It can be an engine-driven generator or an electrochemical source such as a battery. • A source of current separated from higher voltage electrical installations, such as a motor-generator set, with electrically separate windings having a degree of electrical separation equivalent to that of an isolation transformer • Electronic devices where the voltage at the output terminals cannot exceed extra-low voltage even in the case of an internal fault. In these cases, the output terminals may be allowed to have momentary voltages exceeding ELV limitations under transient conditions but it is subject to the condition that the voltage at the output terminals automatically and immediately gets reduced to extra-low voltage as soon as contact is made with live parts under direct or indirect contacts. Live parts of these systems shall be arranged in such a way that short-circuits or arcing between live parts or between live parts and other conductive materials will not take place under the reasonably expected service and environmental conditions. Other specific requirements to be met by SELV/PELV systems are as below: • The drop in voltage at any point in an extra-low voltage electrical installation shall be limited to be within 10% of the nominal value when all live conductors are carrying the circuit operating current, unless the equipment is capable of operating at still lower values as per manufacturer’s guarantees • The supply to an extra-low voltage electrical installation shall be controlled by a main switch or switches operating in all unearthed conductors, provided that the operation of the main switch for the high voltage part of the electrical installation does not cause disconnection of the main supply (possible when ELV supply is derived from main supply) • Every extra-low voltage circuit shall be individually protected at its origin against overload and short-circuit by adopting a fuse or a circuit-breaker 198 Practical Electrical Wiring Standards - AS 3000:2018 • • • • 11.5.1 Plugs in ELV circuits shall not be able to enter sockets of other voltage systems and similarly the sockets shall not accept plugs of other voltage systems ELV Sockets shall not have a contact for a protective earthing conductor Conductors and insulation of cables shall be suitable for the intended purpose and need not be further protected unless installation conditions so demand The separation of live parts from those of other circuits and from earth shall be confirmed by a measurement of the insulation resistance. The insulation resistance value shall be not less than 0.5 MΩ when tested with a 250 V dc insulation resistance tester. SELV system additional requirements In line with the requirements of separated supply systems, SELV circuits shall not be connected to other circuits or earth or earthing conductors/ exposed conductive parts of another system as well as extraneous conductive parts in the installation. However connection to extraneous conductive parts may be made where electrical equipment is inherently required to be so connected but subject to complying with the condition that the extraneous conductive parts shall not attain a voltage exceeding that of the SELV circuit. In dry indoor conditions, where the nominal voltage of SELV exceeds 25 V ac or 60 V ripple-free dc, protection against electric shock due to direct contact shall be provided using barriers/ enclosures or alternatively by adopting proper insulation. In wet and outdoor conditions these protection barriers/ insulation might be warranted for all voltages. Where barriers/ enclosure are provided they shall afford a minimum protection category of IPXXB or IP2X or when provided with insulation, it shall be capable of withstanding a test voltage of 500 V ac for 1 minute. A switch used for isolation in SELV circuit may operate in one less conductor than the number of conductors used in the circuit. 11.5.2 PELV system additional requirements PELV circuits differ from SELV in the way that one conductor of the output circuit is earthed by an appropriate connection to earth normally at the source of the equipment where from the SELV originates. The direct contact shall be prevented in PELV circuits from 6 V ac or 15 V ripple-free dc operating voltage onwards. However, in dry indoor conditions, live parts of PELV circuits can be considered for protection from direct contact only for circuits exceeding 25 V ac or 60 V ripple-free dc, subject to ensuring that a large contact area (more than 8000 sqmm) with the human body is not expected in such dry installations. The prevention of direct contact to live conductors is achieved by use of barriers/ enclosures or proper insulation. When such protection is provided with barriers or enclosures they shall afford a minimum degree of protection equal to IPXXB or IP2X. Alternatively, when insulation is adopted it shall be capable of withstanding a test voltage of 500V ac for 1 minute. A switch used for isolation in PELV circuit shall operate in all unearthed conductors. 11.6 High voltage electrical installations (clause 7.6) For protection and earthing purposes, this clause applies to all the electrical equipment up to and including any low voltage cables as well as low voltage switchgear associated with high voltage transformers. The standard recommends that high voltage parts of these installations shall follow the requirements as stipulated under AS2067 in Australia and follow the requirements as stipulated under New Zealand Electrical Regulations in New Zealand. Section 7 - Special Electrical Installations 199 The below mentioned installations incorporating high voltages in their internal systems and operation are NOT covered under this category. • Electric discharge (neon or equivalent type) illumination systems • X-ray equipment • High frequency equipment • High voltage wiring and electrical equipment enclosed within self contained electrical equipment where appropriate precautions have been taken to prevent contact with high voltage conductors for supplying low voltage in the installation The standard specifies that the low voltage parts of HV installations shall generally follow all the rules and regulations specified from sections 1 to 6. In regard to the HV parts of these installations, the standard recommends to duly take care of the following features in design, selection and testing phases. • Insulation levels to withstand highest voltage and/or impulse withstand voltages • Minimum clearances to live parts taking into account electrode configurations and impulse withstand voltages • Minimum clearances under special conditions • The application of various devices connected to the system • The methods of installation of equipment, cables and accessories • General requirements of installations regarding choice of circuit arrangement, documentation, transport routes, lighting, operational safety and labelling • Special requirements with respect to buildings • Protection measures with respect to access • Protection measures with respect to fire • Provision of earthing such that the system operates under all conditions and ensures safety of human life where there is legitimate access • Testing The details related to the above topics are quite voluminous and cannot be covered in this manual except that we need to understand that all the basic requirements related to insulation, access, isolation, protective earthing, protective devices, enclosures, minimum safety clearances, testing, etc required for LV systems as covered in this manual are equally important for high voltage installations also. The main difference being the amount of voltages and power controlled in HV installations which are comparatively much higher than LV systems and hence the HV installations require additional features to achieve the same kind of safety expected in low voltage systems. 11.7 Hazardous areas (clause 7.7) The subject on Hazardous area and its definitions/ requirements is specialized and is relevant not only for electrical equipments but also for process and instrumentation applications. The hazardous areas recognized in Australian Standards follow the guidelines as per IEC standards that are somehow different from the guidelines followed in USA. The basic awareness needed in these areas is that the electrical devices are always prone to create sparks due to movement of energized contacts which can easily become the main source of fire in areas that accommodate or process explosive chemicals, flammable liquids and the like. Hence it is necessary that electrical installations in hazardous areas shall be able to prevent the sources of fire (sparks) from the electrical parts coming in contact with hazardous substances present in such explosive/ flammable areas. These are usually achieved by accommodating live parts in special enclosures or by adopting special design features to minimize the possibility of sparks coming in contact with external hazardous gases or substances prevailing in the surroundings. The hazardous materials that are of concern are: • Flammable Gases/ Vapour • Flammable liquids having partial pressure to liberate flammable vapour at normal conditions 200 Practical Electrical Wiring Standards - AS 3000:2018 • Combustible dust / Flakes or fibres that burn when mixed with air or in layer form that could burn when ignited In AS/NZS 3000 following two general hazardous areas are recognized • Gas hazardous areas - in which flammable gases or vapors may be present in the area in sufficient quantities to produce an explosive gas atmosphere. Three Zones (Zone 0, Zone 1 and Zone 2) are recognized in these areas and defined in AS 2430.1. • Dust hazardous areas - which are hazardous because of the presence of combustible dust, fibers or flyings. Three Zones (Zone 20, Zone 21, Zone 22) are recognized in these areas and defined in AS/NZS 61241.3 The higher the zone number, the smaller is the risk of an explosion in that zone. Table 11.1 identifies the typical zone classifications specified in the IEC/AS for flammable gases and flammable liquids producing flammable vapour. It may be recalled that the classified zones in damp areas also try to follow a similar concept. Section 7 - Special Electrical Installations 201 Table 11.1 IEC/AS Hazardous area classifications Zone Condition of the area 0 An area in which an Explosive gas/air mixture is continually present or present for long periods 1 An area in which a gas/air mixture is likely to occur in normal operation 2 An area in which a gas/air mixture is not likely to occur in normal operation, and if it occurs, it will exist only for a short time Table 11.2 gives typical zones applied for areas frequented with combustible dust materials. Generally it is considered that 1 mm or less thickness of dust is not likely to result in formation of explosive atmosphere and may not require special precautions. Table 11.2 IEC/AS Hazardous area classifications for combustible dust Zone Condition of the area 20 An area in which combustible dust, as a cloud, is present continuously or frequently, during normal operation, in sufficient quantity to be capable of producing an explosive concentration of combustible dust in mixture with air, and / or where layers of dust of uncontrollable and excessive thickness can be formed. 21 An area in which combustible dust, as a cloud, is likely to occur during normal operation, in sufficient quantity to be capable of producing an explosive concentration of combustible dust in mixture with air. 22 An area in which combustible dust, as a cloud, can occur only infrequently and persist only for a short period, or in which accumulation of dust layer can give rise to an explosive concentration of combustible dust in mixture with air. Selection and installation of electrical equipment in all these hazardous areas shall comply with the appropriate requirements as specified in AS/NZS 2381.1 or AS/NZS 61241.14 and normal equipments shall not be used. Additional competencies, inspection techniques and maintenance / repair methods in these hazardous areas shall be based on the requirements given in the applicable parts of the AS/NZS 2381 and AS/NZS 61241 series 11.8 Other specific installations (clause 7.8) Following special installations are recognized in this standard for complying with safety norms highlighted and it is recommended to refer the respective standard indicated against each in regard to the regulations to be followed in such installations. • Construction and demolition sites - AS/NZS 3012 • Electromedical treatment areas - AS/NZS 3003 202 Practical Electrical Wiring Standards - AS 3000:2018 • • • • • • • • Transportable structures and vehicles including their site supplies - AS/NZS 3001 Marinas and recreational boats - AS/NZS 3004 Shows and carnivals shall comply with AS/NZS 3002 Cold-cathode illumination systems (electric discharge illumination systems) AS/NZS 3832 Extra-low voltage (d.c.) power supply installations within public telecommunications networks - AS/NZS 3015 Generating sets for the supply of electricity at voltages normally exceeding 50 V a.c. or 120 V d.c. - AS/NZS 3010 Electric fences - AS/NZS 3014 and AS/NZS 3016 Electrical equipment and temporary electrical installations on film, video and television sites - AS/NZS 4249 Any other LV installations not covered in these standards shall follow the requirements as per AS/NZS 3000, as appropriate to the type and nature of the installation. 11.9 Supplies for electric vehicles (NZ only) The particular requirements of this Clause (Clause 7.9) supplement or amend the requirements of Sections 2 to 7 of this Standard for parts of electrical installations intended for the charging of electric vehicles for New Zealand only. NOTES: 1 Appendix P contains information on the modes of charging used for charging systems used for electric vehicles. 2 Appendix C contains guidance on assessing the contribution of electric vehicle charging to maximum demand of an installation 11.10 Summary Section 7 of AS/NZS 3000 specifies requirements to be complied in special installations such as safety services, alternative supply systems, separated supply installations, etc including construction/ demolition sites, shows and carnivals, etc. The term safety services refers to emergency systems that are to be operated in emergency situations to safeguard personnel and properties and includes fire and smoke detection/ control systems, evacuation systems like lifts, etc. The installations shall essentially consider separation of power supplies feeding equipments of safety services so that these services can be independently controlled in all conditions including emergency situations with normal or alternative supply arrangements. These services shall incorporate properly rated and discriminated protective devices and be ensured for uninterrupted availability to take care of any kind of emergency situation at any time. The captive power generation systems can be any of the sources like engine-generator set, inverters with batteries, etc. These systems shall also include basic protection features such as overcurrent protection, shortcircuit protection and protective earthing like the other main installations generally in line with the stipulations covered in this standard. Normally these may be operated as stand alone system or in parallel with grid with single or multiple sets. 4pole/ 3pole changeover switches are adopted to feed areas requiring alternative supply. The neutral of a generator shall be connected to the main MEN connection without any isolating device. However where multiple generating sets are operated in parallel it is necessary to connect one generator neutral alone to the earth with the others kept open to prevent circulating currents. To achieve this suitable isolation switches shall be incorporated in each generator neutral circuit. Electrical separation is normally used by having an isolation transformer and avoiding all earthing connections for the conductive and extraneous parts in an installation. In these systems, it is recommended to interconnect all earthing contacts of socket outlets, cables, etc to an equipotential bonding conductor that is insulated from earth for easy verification/ testing. It is important to Section 7 - Special Electrical Installations 203 verify the conformity of separated supply systems mainly in regard to separation of earth connections, equipotential connection, etc. The separated extra low voltages and protected extra low voltage (SELV and PELV) systems are sources rated below 50V a.c. or 120V d.c. SELV systems do not adopt protective earthing while PELV systems have one conductor of output circuits connected to earth. These ELV systems can be combination of isolation transformers and/or electronic devices rated to supply the required currents without exceeding the specified limits. It shall be ensured that the conductors of all separated systems are isolated from those of the other systems. It is also essential to adopt special types of socket-outlets and plugs so as to avoid interchange with high voltage supplies/ appliances. In dry conditions these ELV systems need not have additional protection for shock hazards upto 25V a.c. or 60V d.c. However additional protection by using suitable barrier or adopting suitable insulation shall be provided beyond these ratings. In regard to HV installations, hazardous areas and other specific installations, the standard recommends referring the other applicable AS/NZS/IEC standards for specific requirements but it is necessary that these systems shall also ensure all basic safety requirements expected as per AS/NZS 3000 with some special construction to take of the hazards and characteristics expected in these systems. 204 Practical Electrical Wiring Standards - AS 3000:2018 12 Section 8 – Verification Section 8 of AS/NZS 3000 provides guidelines for verification of various parts of an electrical installation to check for their compliance with the stipulations given in this standard before the systems are put into service. In this chapter we will review the importance and requirements of these verifications along with the brief verification checklists given in the standard for major parts of a typical LV installation. We will also go through the tests to be conducted on the systems before and after energisation along with the stipulated guideline values to be considered for verifying such test results. The tests include insulation resistance tests, fault loop impedance measurements, RCD testing, etc and are mandatory for all LV installations. Learning objectives • • • • • • • Basic requirements Checklist and documentation Mandatory tests Testing sequence Insulation and polarity tests Measurement of earth fault loop impedance RCD testing 12.1 Basic objectives and requirements (clause 8.1) AS/NZS 3000 stipulations so far covered are all with the main objective of ensuring safety to personnel, properties and livestock. There is no doubt the objective can be achieved but it is important that the installation follows all the key recommendations of the standard. As we have seen in the initial chapter, the equipment and installation need to successfully pass the tests to prove that they will provide the safe and expected performance during actual service. Section-8 of the standard is aimed to achieve the above goal by providing guidelines and specific instructions covering the following. • To verify that the requirements of this Standard have been met by the new electrical installations as well by any alterations, additions or repairs to an existing electrical installation • All the new and altered installations after completion are inspected as far as is practicable to ensure for correct ratings and for correct installation as per established standards. In regard to the modifications, alterations, additions or the repairs to an existing installation it is compulsory to ensure that these do not impair the safety of the existing electrical installation. 206 Practical Electrical Wiring Standards - AS 3000:2018 • After the above inspection, all the new and altered systems are tested for checking their correct design and ratings by means of established procedures using reasonably simple instruments to ascertain that the equipment and installation will provide safe and satisfactory performance under the specific supply and environmental conditions. Though most of the tests and inspections are done before energisation, certain types of tests may have to be made after the electrical installation has been placed in service, to check integrity with the supplier systems as well and for checking proper operation of some specific and important devices like RCDs. Section-8 of the standard recommends the following steps to complete the verification and testing of the installations: • Visual Inspection to verify that all external provisions, connections and safety clearances as per the norms are provided and available • Mandatory tests shall be conducted after completion of inspection for checking compliance of the installation and equipment to the basic design and safe performance needs • Establishment of system conditions based on tests covering different parts of the installation by measuring insulation resistance, loop impedance, etc including checks on circuit connections, polarity, etc and ensure that they all meet basic acceptable requirements for successful operation without impairing safety to the installation. • Tests on RCDs. It is to be noted that there might be requirements to refer other standards for some of the tests on specific installations such as separated supplies, SELV and PELV installations, electromedical installations, transportable structures and vehicles and marinas, etc for which the standards identified in appendix-A shall be referred. It is also essential to have records of all the tests with the date of initial energisation of an installation on-site. 12.2 Safety precautions and testing devices The main objective of AS/NZS 3000 is to ensure safety of persons and avoid damage to property and electrical installation equipment and there is no exception for these objectives during inspection and testing as well. Hence it is necessary to ensure that all the inspections and tests are carried out applying well defined safety practices, so that there are no untoward incidents or causes that could affect the people, properties and the installation during these verifications and tests. Following are the minimum precautions needed as per AS/NZS 3017. This standard also provides illustrations on the test setups to be adopted for the various tests recommended in AS/NZS 3000. • Treat all equipment, such as cables and terminations, etc as being energized until proven otherwise before getting in contact with them • Follow safe working practices as per AS/NZS 4836 like use of proper PPE, etc • Understand the correct use of the equipment to be used and its rating before applying a test voltage or passing a test current • Ensure that the equipment being used, including any test leads, probes or clips are suitable for the test voltages, are in good working order and have no damaged or loose parts that might lead to direct contacts with test voltages Following are some of the main instruments and devices needed to complete most of the tests recommended in AS/NZS 3000. • Insulation resistance tester • Ohmmeter • Voltage indicator (e.g. lamp, neon, LED device or meter) • Suitable probes • Trailing leads • A range of resistors of known values Section 8 – Verification 207 • • A suitable instrument for measuring fault-loop impedance and A suitable instrument or device for checking the operation of a RCD Where appropriate, the instruments used for tests should have valid calibration from approved laboratories for their correct measurements. 12.3 Visual Inspection (Clause 8.2) It is necessary that the visual inspection shall be carried out when the installation works have been completed and before the relevant part of the electrical installation is to be placed in service to use normal supply. It might also be possible that the visual inspection of some part of the electrical installation may not be accessible on completion of works due to the type of enclosure in the building structure, etc. In such cases, it is recommended to complete the inspection of that part during the course of the installation itself and making proper records before covering up. Basically the visual inspection is aimed to check and ensure compliance of all the following. • Availability of protection features to safeguard against direct contact with live parts, e.g. availability of insulation and enclosure for the electrical equipment. • Availability of protection features to defend against indirect contact in equipments having exposed conductive parts based on the type and nature of the installation e.g. provision of double insulation or isolating transformers, in specific areas. • Protection methods adopted against the common hazardous parts and conditions, e.g. enclosure door conditions, guarding or screening of flammable materials, protection from hot surfaces and parts that may cause physical injury when operating, etc. • Protections available to prevent spreading of fire during fire accidents, e.g. sealing provisions for wiring systems while penetrating fire barriers. • General conditions of various parts of an electrical equipment which are likely to create hazards in due course of time because of the nature of the surroundings and other conditions of the installation e.g. signs of damage on external and internal parts of an equipment that could impair safe operation and/ or its disconnection. Following paragraphs highlight some of the common checks to be made on different parts of a typical low voltage installation. These may not be exhaustive but cover most of the salient points that are important in the respective parts. 12.3.1 Checks on consumer mains Verify the compliance of consumer mains for the following: • Current carrying capacity of the system based on the demand expected • Voltage drop is likely to be within limits, e.g. minimum size of conductors for the current expected • Conditions of underground installation e.g. enclosure conditions/ material, depth of burial, mechanical protection provided, etc. • Aerial connection practices adopted, e.g. maintenance of safety clearance distances. • Proper connection of wiring at the mains • Space availability for maintenance checks/future modifications • Protection against external influences, mostly weather conditions likely to be faced while in service 12.3.2 Verifying switchboards The switchboards of the installation shall be visually inspected for the following requirements. • Location, e.g. unobstructed access, exit doors and egress path sizes • Protective devices installed, e.g. rating of overload and residual current protective devices, expected normal and fault current ratings and compliance of component ratings to the same • Provision of isolating devices and their features, e.g. main isolation switches, locking features, etc. 208 Practical Electrical Wiring Standards - AS 3000:2018 • • • • • 12.3.3 Connecting devices and their arrangements, e.g. neutral/earth bars and active links Connection and fixing methods adopted for wiring and switchgear Identification and labelling provisions on the switchboard Protection against external influences like IP classification, etc to meet the conditions of a location Ventilation conditions Verifying wiring systems Following checks are recommended on the wiring systems of the installation. • Conductor size – Current carrying capacity and voltage drop based on main circuit and subcircuit ratings • Identification of cable cores with colour, sleeving, etc as per acceptable norms • Adequate support and fixing for all the wires and associated parts like enclosures, etc. • Conditions of connections like bending radii, adequate supports, etc. • Conditions of enclosures like material, sealing, etc. • Compliance to particular installation conditions, e.g. underground with proper identifications/ protections, aerial with proper spans/ supports, emergency systems arrangements, etc. • Segregation of electrical installations from other services, as needed, like barriers, distances, etc. • Protection against external influences, e.g. grinding of or protection against sharp corners, enclosure IP classification, armouring, etc. 12.3.4 Checks on Electrical equipment Availability of following provisions and features shall be checked • Provision of isolation and switching devices for protection against injury from mechanical movement devices and motors • Provision of isolation and switching devices for protection against high temperature effects e.g. motors, room heaters, water heaters • Locking devices and caution labels • Provision of individual switching devices for particular electrical equipment/ appliances e.g. socket outlets, cooking appliances, etc • Particular installation conditions, e.g. locations affected by water, explosive atmospheres, extra-low voltage, high voltage and provisions made to take care of such conditions • Compliance with applicable Standard of an equipment or device, as applicable • Quality and conditions of the connection, support and fixing arrangements provided for the switches, socket outlets, distribution systems, etc. • Protection against external influences as needed like barriers, covers, etc. 12.3.5 Checks on earthing The earthing system plays an important role in the safety condition of an installation and hence it is important that all earthing provisions as per the standard requirements are complying to ensure safety. Following are the typical checks needed. • Proper MEN connection at the main switchboard or any other recognized location • Earth electrode provision, type, location and material as per acceptable practice • Earthing conductors, e.g. material, conductor size, identification with colour codes for insulation, etc. • Equipotential bonding conductor provisions, as needed, including their size, identification, etc. • Proper connections, joints and terminations of earthing conductors at all equipments, links, busbars, etc. • Protection against external influences with conduits, etc as may be needed • Earthing arrangements for other non electrical systems Section 8 – Verification 209 • Creation of earthed situation that will ensure earthing of additional electrical equipment 12.3.6 Fixed wire appliances Ensure following checks on the appliances with fixed wiring • They are correctly positioned and are suitable for the environment in which they are located • Connections of conductors to electrical equipment are correct. When this connection is via flexible cord the cord shall be anchored at both the electrical appliance and the supply fitting • Electrical appliances are correctly mounted and protected against mechanical damage • Covers are in place preventing access to live parts or basic insulation After completing all the checks for the various items of an installation, the checklist forms shall be duly filled to confirm compliance to the requirements and retained for future records. 12.4 Mandatory tests (clause 8.3) Following are the mandatory tests to be carried out on an installation before energisation to verify its compliance with the standard. • Condition and continuity of the earthing system (by means of resistance measurement for main earthing, protective earthing and bonding conductors) • Insulation resistance of various switchboards and circuits • Polarity of the connections • Correct circuit connections • Measurement of earth fault loop impedance to confirm automatic disconnection of supply within acceptable time, when needed • Operation of RCDs 12.4.1 Sequence of tests It is recommended to adopt the sequence as per figure 12.1 for the various mandatory tests to be done on an installation. Figure 12.1 Sequence of mandatory tests (Source: AS/NZS 3000, Figure 8.1) 210 Practical Electrical Wiring Standards - AS 3000:2018 If the electrical installation fails a test, it could be due to some unexpected or unknown fault conditions prevailing in the equipment or in its connections. Such faulty conditions shall be located, analyzed and rectified, after which that test and any preceding tests that might have been influenced due to such fault condition shall be repeated once again to prove compliance. AS/NZS 3017 shall be referred which provides detailed procedures and setups to be followed while carrying out the various mandatory tests highlighted in figure 12.1. 12.4.2 Continuity tests of the earthing system The continuity of earthing system is most important to serve its purpose of safety and hence the continuity of the earthing system is to be checked for ensuring proper protection under energized conditions. • The circuit protective devices shall be able to detect if there is a fault between live parts to the earth due to either direct or indirect contacts and will operate without fail • The electrical equipment parts that are earthed have sufficiently low earth resistance values and these parts will not reach dangerous voltages when faults occur Following verifications and tests are recommended to check conformity of main earthing and equipotential bonding systems: • Check and ensure continuity of the main earthing conductor between the main switchboard and the earth electrode • Measure and ensure that the resistance of the main earthing conductor including earth rod is within 0.5Ω • Check continuity of connections between any point on the installation required to be earthed and the switchboard earth bar or terminal, as applicable • Ensure that the protective earthing conductor sizes provided are meeting the installation fault conditions and active conductor sizes as per the standard • Ensure that all fixed wired appliances that require earthing (Class I equipments) are connected to earth, using recommended conductor sizes • Ensure that the connection between any point on the installation required to be equipotentially bonded and the switchboard earth bar is continuous • Measure and ensure that the resistance of each equipotential bonding conductor does not exceed 0.5 Ω 12.4.3 Insulation Resistance tests Insulation resistance tests are intended to verify the adequacy of the insulation between live conductors and earth and ensure its integrity while energizing or operating with the normal operating voltages of the system or equipment. This test is essential to prevent the following hazards common with insulation failures. • Shock hazards from inadvertent contacts • Fire hazards from short-circuits • Equipment damage during energisation or after some time Insulation resistance test is done using 500V DC insulation resistance test instrument, usually termed as megger instrument. The resistance is measured between the active conductors, active conductor to neutral and active conductors to earth, etc by maintaining 500V DC between the terminals to be tested for one minute. It shall be ensured that the insulation resistance value so measured between various isolated/ separated parts is minimum 1 MΩ on the 500 V DC instrument. Where consumers mains or submains are not of significant length, e.g. with say 50 m of polymeric cables, the insulation resistance values in excess of 50 MΩ can be expected. Similarly a lower value in the order of about 10 kilo ohms (0.01 MΩ) may be acceptable for sheathed heating elements of appliances or some other higher or lower value as permitted in the applicable standard for the item under test at the discretion of authorized testing personnel. Figure 12.2 shows typical arrangement for measuring insulation resistance between active conductor to other conductors and earth using the instrument, with all untested parts grouped and connected to earth. Section 8 – Verification 211 Figure 12.2 Typical arrangements for Insulation resistance test on cables 12.4.4 Polarity and correct circuit connection checks Polarity checks are related to verifying the arrangement of active, neutral and earth conductors to prevent the following problems: • Shock hazards that can happen due to transposition of active and neutral conductors of the consumers mains or sub mains (with MEN connection at outbuilding or detached portion) resulting in the earthing system to carry a substantial voltage • Combinations of incorrect connections among active, neutral and earthing conductors resulting in the exposed conductive parts of the electrical installation becoming alive when supply is given • The wrong connection of switches in neutral conductors instead of active conductors, impacting the parts of appliances, such as appliances and lamp holders to remain energized even when the switches are in the ‘OFF’ position, that can easily lead to shocks and faults The verification of correct circuit connections is intended to ensure the following: • Protective earthing conductors do not carry current under normal operating conditions • No short circuit is prevalent in the system that can otherwise lead to short-circuit current between live conductors and through part of the earthing system upon energisation causing considerable fire damage or personal injury, particularly in high current locations • Interconnection of different circuits for safe functioning and operation of the various equipments of the installation, as applicable Most of the above checks are done by visual inspections, resistance tests, voltage measurements, test lamps, etc. 12.4.5 Verification of resistance and impedance Though the standard specifies provision of RCD’s for socket outlets, there are some exceptions where an installation includes circuits containing socket-outlets that are not protected by an RCD. 212 Practical Electrical Wiring Standards - AS 3000:2018 In such cases, it is necessary to verify that the impedance for detection of small currents is within acceptable values and automatic disconnection of supply during earth faults is possible under leakage conditions. These tests shall be done as below: • Verification of the total resistance (Rphe) of the active and protective earthing conductors, without energizing the system • Verification of the earth fault-loop impedance, after connecting the supply The second test is performed to verify the integrity of the MEN connections and the test covers all the components of the earth fault-loop including the upstream neutral (PEN) conductors, which will be effective with the mains supply. These tests will prove that the protective device will operate to disconnect an earth fault current within the stipulated operating time without touch voltage getting exceeded as per the standard. The standard includes two tables to cross check the correct values to be achieved for Rph and earth fault loop impedance for different conductor sizes and protective device ratings. The loop impedance measurements should be carried out using a measuring instrument capable of reading low resistance values keeping MEN connection intact and ensuring safety for the instrument operator. Where supply is not available, the resistance of the conductors of each individual circuit may be measured by connecting an ohmmeter with the following arrangement illustrated in figure 12.3. • One lead on the active conductor and protective earthing conductor connected together at the origin of the particular circuit, where the protective device is normally fitted • With the above arrangement, connecting one lead of the ohmmeter to the active conductor and the other lead to the associated protective earthing conductor at a considerable distance away from the origin The value of resistance (Rphe) so obtained shall not exceed the value in table 8.2 given in AS/NZS 3000 (Table 3.2 in AS/NZS 3017) for the appropriate conductor size and type of protective device. Section 8 – Verification 213 Figure 12.3 Typical setup for individual circuit earth fault loop impedance measurement (Source: AS/NZS 3017, Figure 3.22 ) Maximum values of earth fault-loop impedance (Zs at 230 V) to be obtained in such measurements are given in table 12.1 for different types of circuit breakers and fuses commonly adopted in the LV installations. 214 Practical Electrical Wiring Standards - AS 3000:2018 Table 12.1 Maximum allowable earth fault loop impedance for 230V circuits (Source: AS/NZS 3000, Table 8.1) Table 12.1 does not include 5 seconds disconnection time circuit-breakers as these are intended to operate in the instantaneous tripping zone for earth faults. The values of Zs in the Table are based on the equation, Zs = Uo/Ia, we reviewed earlier while discussing on earth fault loop impedance. Where Z s = earth fault-loop impedance of the circuit U o = nominal phase voltage (230 V) of the system I a = current causing automatic operation of the protective device. For arriving at the maximum permissible impedance for the required disconnection time, I a for circuit-breakers for the different types are chosen as the mean tripping current in line with AS/NZS 60898 as noted below. Type B = 4 × rated current Type C = 7.5 × rated current Type D = 12.5 × rated current I a for fuses are approximate mean values considered from AS 60269.1 Section 8 – Verification 215 12.4.6 RCD testing Though RCD’s are provided their operation can not be taken for granted. These shall be tested for proper operation under normal supply conditions, immediately after energisation for making any rectifications, if needed. It may be recalled that the RCD’s are to satisfactorily perform with pure sinusoidal voltages in Australia, while in New Zealand these shall be suitable for operation during leakages in pulsating dc circuits also. The tests to check proper operation of each RCD in each final subcircuit protected by an RCD shall be done as below. • Using an integral testing device which causes the device to operate under rated residual alternating current and (in New Zealand) residual pulsating direct current conditions. If the RCD being tested is marked with the symbol confirming that it is a type A RCD, the residual direct pulsating current testing may be omitted (in New Zealand). • By using a test plug with a resistor between the active and earth pins and checking the operation of the device when energized with the supply. Though use of integral test device may establish the RCD is functioning correctly and prove the integrity of the electrical and mechanical elements within the tripping device, it does not prove the continuity of the main earthing conductor or the associated circuit protective earthing conductors or any earth electrode or other means of earthing or any other part of the associated electrical earthing in the installation. The test is considered successful if the RCD trips instantaneously to isolate the main supply. 12.5 Summary Section-8 of AS/NZS 3000 details the guidelines to be followed for inspection and testing on new installation as well as for alterations/ modifications to an existing installation for making sure that the installation complies with the stipulations of the standard and hence is safe to operate. It is also necessary all applicable safety norms are strictly in place while the tests are conducted. Most of the tests are to be conducted using proper test instruments without energizing the main supply. Some tests shall be done after installation is put into service. Section-8 also provides checklists for completing visual inspections on various parts of an installation covering consumer mains, switchboards, equipments, earthing systems, etc. After visual inspection, the mandatory tests shall be conducted in the sequence recommended i.e. earth resistance test, insulation resistance test, polarity and connection tests, resistance measurement, earth fault loop impedance measurement and finally the tests on RCD’s provided in subcircuits. The earth resistance values of main earthing conductor shall not exceed 0.5 ohms for an installation including earth rod and MEN connection and also for bonding connections. The insulation resistance tests shall give a value of not less than 1 Mega ohms with 500V DC across the insulated parts. Some exceptions to this value may be considered based on the types of materials and circuits adopted. Polarity and circuit connection tests are essential to verify there are no exchange in active, neutral and earth conductors while completing terminations at various parts of the installation as these could cause short circuits, fire hazards, etc upon energisation. The combined resistance of the active and protective earthing conductors without connecting mains supply and the earth fault loop impedance after getting mains supply shall be measured, to check their impact on the disconnection times of protective devices. The resistance and earth fault loop impedance values shall be within the maximum values specified in the tables given in the standard based on the conductor sizes (for resistance), protective device rating and disconnection time needed for various types of circuit breakers and fuses commonly adopted in LV installations. Tests on RCD’s shall be verified by using integral test device or any suitable device for their correct tripping at or just below the rated residual current. 216 Practical Electrical Wiring Standards - AS 3000:2018 Section-8 of AS/NZS 3000 shall be referred along with AS/NZS 3017 to understand the instruments needed and the test setups to be adopted for completing the recommended tests. All test results shall be properly recorded along with energisation date and kept for access at site. Section 8 – Verification 217 Appendix 1 Determination of Maximum Demand for Electrical Installations A1.1 Introduction Appendix C of AS/NZS 3000 provides guidelines that are useful in determining the power demand of an installation that is ultimately critical in deciding the conductor sizes, protective device settings, reliable and safe operation of a system, etc during the design and selection of electrical distribution systems. This part of our manual briefly covers the salient recommendations given in the standard for the calculation of maximum demand in common LV installation, which is referred to as “after diversity maximum demand” While individual load control device and current are based on the nominal current rating of the load, all the loads in most of the plants do not operate simultaneously. Some devices (like refrigerators, heating loads, etc) include automatic ON/OFF controls due to which the currents drawn by such loads do vary under normal use. Similarly all sockets in an installation may not be serving at all the times. Hence to decide the maximum load of a system it is not necessary to just sum of all the nominal amperes of different loads but instead you need to apply some factors (Less than 1, referred to as diversity factor) to decide the actual current to be considered during the design and selection stages of an installation. AS/NZS 3000 divides the LV installations into two major types as below: • Domestic installations basically serving as residences of families in single and multi apartment buildings • Non domestic installations where people gather for pleasure, business, education, etc like motels, schools, churches, etc including factories and business houses The standard provides tables associated with each of the above type of installation for the diversity factors to be applied for various electrical loads so as to assess the “after diversity maximum demand” for the purpose of to be met by the main supply. The tables given in the standard may also be used to come to a conclusion on the power demand to be met by captive units that might be planned to supply a part or full installation, with due consideration on manufacturer’s recommendations and inrush currents for large inductive/ capacitive loads. 218 Practical Electrical Wiring Standards - AS 3000:2018 A1.2 Domestic installations These are divided into two types Viz., single residence and multiple living blocks with further division of four categories as below for applying the diversity factors to the loads: • Single living unit • 2 to 5 living units • 6 to 20 living units • 21 and above units A1.2.1 Load grouping for domestic installations The loads in domestic installations are usually divided into separate and multiple circuits as we reviewed in the manual. The standard groups the common domestic loads using the alphabets A, B, etc as given below. It also includes some more sub-grouping as given in brackets for each type of load: • A. Lighting points (Indoor and outdoor) • B. Socket outlet points (10A, 15A and 20A- Refer I,J also) • C. Home appliances (like ranges, cooking appliances, washing machines, etc or exclusive sockets provided for such appliances) • D. Heating and Air conditioning (or sockets provided for such items) • E. Instantaneous water heaters • F. Storage water heaters • G. Spa and swimming pool heaters • H. Communal lighting (applicable for multiple units only) • I. Socket outlets rated below 10 amperes but not covered by any other group including B (normally considered for multiple units only) • J. Appliances rated above 10 amperes in three categories Viz., dryers and water heaters, space heating and air conditioning, swimming pools and spa heaters (applicable for multiple units only) • K. Lifts (Not to be taken as part of domestic load for demand assessment but shall be considered as non domestic for the purpose of subcircuit design) • L. Motors (Same consideration like lifts, to be considered as non domestic) • M. Any other loads not covered above Table C1 in the standard gives the recommendations on currents and/or diversity factors to be considered for the different groups identified above. Most of these recommendations are included in Tables A1.1 and A1.2 attached at the end of this appendix. While referring to the tables, it must be remembered that for such of the loads indicated as ‘not applicable’, if provided in an installation, their contributions shall be their respective nominal current ratings and shall be added to the current contribution from other load groups to arrive at a conservative maximum demand. A1.2.2 Demand calculations Following are the important points to be considered while making the demand calculations. • In case of Multiphase systems - Divide the total points of lighting by the number of phases (3) and round the result to the next integer for consideration in each phase • 2 points per every meter run shall be considered for the lighting tracks, taking 0.5A/m per phase as the connected load • Fluorescent lamps and discharge lamps shall include the wattages of the ballasts/ capacitors, etc. for their normal current before applying the recommended diversity • Socket outlets installed above 2.3 meters used for luminaires or for connecting appliances rated below 150 watts may be considered as one lighting point – Group A • Permanently connected load rated below 10 Amperes may be included as part of socket outlet – Group B category (i) Determination of Maximum Demand for Electrical Installations 219 A1.3 Non domestic installations These installations are divided into two categories as below for the purpose of load assessment: • Residential institutions, hotels, boarding houses, hospitals and motels • Factories, shops, stores, schools, churches and business premises A1.3.1 Load grouping for non-domestic installations The loads in non domestic premises are also divided in line with the domestic loads and identified with alphabets as given below with further break-up in brackets against respective loads: • A. Lighting points in places other than those in fuel dispensing units • B. Socket outlets (10A and above 10A. Here 10A sockets shall be further divided as free outlets or with permanently installed loads) • C. Appliances for cooking, heating and cooling, including instantaneous water heaters • D. Motors excluding those in lifts and fuel dispensing units (includes motors used for domestic use) • E. Lifts (includes lifts used in domestic buildings) • F. Fuel dispensing units (Both lighting and motors together) • G. Swimming pools, spa, saunas • H. Welding machines • J. X ray equipment • K. Other loads not covered above Table A1.2 gives part of table C2 in regard to the diversity factors to be applied for the various load groups given above. A1.4 Additional guidelines Table A1.4 provides maximum current values that are to be considered for a final subcircuit feeding an individual appliance of specific power ratings. Same current values may be applied for multiple appliances used in a system having combined total power equal to the values given in this table e.g. appliance consisting of oven and hotplates. Table A1.4 Current Values to be considered for appliance wattages Appliance full-load rating per phase Upto 5000 W Maximum demand to be considered 16 A Exceeding 5000 W but within 8000 W 20 A Exceeding 8000 W but within 10000 W 25 A Exceeding 10000 W but within 13000 W 32 A Exceeding 13000 W 40 A In the case of welding machines, total demand needs to be decided using a diversity factor that varies with the number of machines connected in an installation. Following factors are recommended for arriving at maximum currents/ demand when an installation is likely to be operated with two or more arc welding machines: • Upto two largest welding machines: 100% of each rated primary current plus • Next largest welding machine: 85% of the rated primary current; plus • Next largest welding machine: 70% of the rated primary current; plus 220 Practical Electrical Wiring Standards - AS 3000:2018 • All other welding machines: 60% of the rated primary current It means that an installation using six arc welding machines each rated for x amperes is expected to have a demand contribution of (2x+0.85x+0.7x+1.2x) amperes from these six welding machines. For resistance welding machines, the maximum current that may be considered is 70% of the rated primary current shall be considered for seam and automatically fed machine and 50% of the rated primary current for manually operated, non-automatic machine. The additional diversity factors based on duty cycles may be applied over these currents as per applicable standard of the machine. A1.5 Steps for demand calculations The standard recommends adopting the following steps in assessing the maximum demand of an installation: • Decide whether the installation is domestic or non domestic or mixed to conclude the table to be used for deciding the diversity factors applicable • Group the loads as A, B, C, etc. • In case of multiphase systems, divide the loads phase wise and decide the number of lighting points, sockets, etc group wise in each phase • List out the maximum rated amperes against each load group • Multiply these group wise currents with the applicable diversity factor as per table (depending on quantity of each group loads) to decide the maximum currents of each group • Sum up the maximum currents in amperes so arrived for each load group, which is the maximum demand expected for the installation (phase wise, if applicable) A1.6 Sample calculations Reference may be made to appendix-C of AS/NZS 3000 that provides various worked out examples considering different load group combinations for both domestic and non domestic installations. Example calculations using the relevant tables are provided in the exercises forming part of this manual. Determination of Maximum Demand for Electrical Installations 221 Table A1.1 Current and diversity factors for multiple domestic installations (Source: AS/NZS 3000, Table C1) 222 Practical Electrical Wiring Standards - AS 3000:2018 Determination of Maximum Demand for Electrical Installations 223 Table A1.3 Current Ratings and diversity factors for non-domestic installations 224 Practical Electrical Wiring Standards - AS 3000:2018 Determination of Maximum Demand for Electrical Installations 225 Appendix 2 Wiring Systems Classification A2.1 Basic criteria The common causes of damages on the wiring systems are accidental fires and mechanical impacts likely to occur during their service. A wiring system can be provided with protection against these causes in the following ways to minimize the damages • Unenclosed or enclosed wiring systems routed suitably by using fireresisting building structural elements with suitable supports and fixings to get the desired protection and NOT using any fire rated elements • By using fire-rated elements of building construction The degree of protection normally varies for the different methods and hence it is important to differentiate the kind of protections offered by each system. The end user might be at a loss to understand the actual protection achievable by a particular system unless some simple method is available to weigh the different systems on a common ground. AS/NZS 3013 provides guidelines for classifying these systems for this purpose. The wiring system classification helps the end users in identifying a wiring system’s capability to maintain circuit integrity under fire conditions for a definite time period and against mechanical damage of a specific severity. This classification is analogous to the IP classification (defining the degree of protection against entry of dust/tools and water inside enclosures) and is recognized by using letters ‘WS’ (to mean wiring system) followed by two characters using X, 1, 2, 3, 4 or 5 to define the degree of protection offered against fire and mechanical forces. “X” normally means that a required protection is inapplicable for a specific system. Table A2.1 indicates the explanations to the characters used for identifying a wiring system’s capability. A third letter W after the two characters means that the system had been type tested to prove its integrity for protection against fire for the specified duration and then hosed with water. 226 Practical Electrical Wiring Standards - AS 3000:2018 Wiring system suppliers shall provide installers with complete details of fixing and support methods to be followed for the wiring system to achieve the desired protections against fire and mechanical forces including instructions related to the correct orientation of the wiring system. Installers shall install wiring systems strictly in accordance with the supplier’s instructions to ensure getting the desired protection. Table A2.1 Classification adopted in wiring systems First character: Protection against Exposure to fire Character used in first and Minimum time for second maintaining circuit integrity place Second character: Protection against mechanical damage Type of mechanical force capable to withstand Not applicable X Not applicable 15 minutes 1 Light impact only 30 minutes 2 Moderate impact only 60 minutes 3 Heavy impact 90 minutes 4 Very heavy impact 120 minutes 5 Extremely heavy impact A2.2 Specific wiring systems to be adopted Table A2.2 shows types of recommended systems for selected applications along with the minimum fire protection obtained from these systems. Table A2.2 Specific recommendations on wiring systems for common applications Equipment/ applications Wiring systems recommended Pumpset systems associated with the operation of residential sprinkler pumps WS2X. Minimum 30 minutes fire exposure shall be possible Pumpsets for other purposes WS5X – Minimum 120 minutes fire exposure shall be possible Smoke-venting equipment and Electrical operated Passenger and goods lifts Not below WS52 for circuits supplying these Central emergency lighting circuits WS4X for submains and certain final subcircuits Substation or main switchboard WS53W in locations likely to get damage by motor vehicles; elsewhere WS52W or a minimum fire-resistance of two hours Wiring systems Classification 227 A2.3 Wiring systems with or without enclosures Some wiring systems need not depend on fire-rated elements of building construction for thermal protection. The required protection can be achieved either by having unenclosed systems with some sort of integral protection as part of material characteristic during manufacture or by having an enclosed system with a protective cover outside the wiring to take care of the impact and cutting energies to meet the desired classification requirement levels per AS/NZS 3013. The protections with enclosures may be metallic or non metallic. Non-metallic types are normally expected to provide mechanical protection between −15 to +60°C. In case of any extended ranges or reduced ranges these shall be certified by manufacturer by means of external marking over the non metallic enclosures. Table A2.3 provides some suggestions on the wiring systems to be typically considered for common applications, but remember that some external influences might call for higher categories, as well. Table A2.3 Wiring system types for typical applications System type General application areas WSX1 In internal domestic or office situations where some damage is common. WSX2 In passageways in domestic office and commercial locations where impact by hand trucks and barrows is most likely. WSX3 In car parks and driveways where occasional impact of cars or light vehicles is quite possible. WSX4 In areas where impact by vehicles not exceeding two tonnes but with solid frames is anticipated. WSX5 In areas where impact by laden trucks exceeding two tonnes is likely. Where wiring systems are enclosed, the protection must be able to resist the impact loads. This is usually achieved by having a complete enclosure, such as a conduit, pipe, trunking or other housing; or by adopting a barrier that is interposed between the wiring system and the possible source of impact. These enclosures shall preferably have undergone type tests to confirm their compliance to the expected impact energy and ambient temperature range of the installation. 228 Practical Electrical Wiring Standards - AS 3000:2018 Table A2.4 gives some common means that are adopted to get the expected protection from a system. Table A2.4 Wiring system types/ materials recommended for mechanical damage protections System type Protection expected Recommended types of cables/ enclosures to get the desired protection WSX1 Light protection against casual damage by pedestrians - One sheathed cable just adjacent to a projecting timber batten or similar corner to ensure the projection is not less than twice the dimension of the cable in that direction covering the cable for casual damages. - Cabling in light or medium-duty conduits - Small sheet-metal ducts with clip-on covers. - PVC duct with clip-on covers WSX2 Against damage from hand-powered wheeled devices, e.g. hand trucks and wheelbarrows and wheelbarrows - Use of Heavy-duty conduits. - Using Armored cables - Steel duct with a minimum metal thickness of 1.6 mm, a screw fixed lid and unsupported width not exceeding 100 mm. - Fabricated steel cover with metal not less than 1.6 mm thick, and unreinforced unsupported width not exceeding 100 mm. - Any WSX1 system with a 10 mm cover of plaster or concrete. - using MIMS cable WSX3 Medium-duty protection against damage from vehicles, such as cars and light commercial vehicles - Any wiring system with additional 2.0 mm sheet steel coverage with a maximum unsupported width of 100 mm. - Any WSX2 systems with an additional 1.6 mm sheet steel coverage and unsupported width not exceeding 100 mm. - Galvanized medium tube - Very heavy-duty conduits. Wiring systems Classification 229 Appendix 3 IEC Classification of Supply Systems Based on Earthing Practices A3.1 IEC definitions on supply systems IEC 60364 discusses the types of earthing adopted in low voltage installations for protection against direct and indirect contacts and provides a method of classifying the LV supply systems based on the type of earthing adopted as well as the method used to extend the system earth to consumer installations. We already reviewed the meanings of specific alphabets like T, N, etc used to define these systems. IEC standard also discusses the comparative merits of the different types of systems for specific applications. The salient features of these systems are briefed in this appendix. A3.1.1 TN system TN system refers to a system having one or more points of the source directly earthed with the exposed metal parts using protective conductors. It is further subdivided into the following types depending on the neutral-earth connection configuration. TN-C system This is a system in which the same conductor functions as the neutral and protective conductor throughout the supply and consumer installation as per figure A3.1. 230 Practical Electrical Wiring Standards - AS 3000:2018 Figure A3.1 Schematic of a TN-C system TN-S system This system incorporates separate conductors for neutral and protective earth functions throughout the system. In this type, the utility company provides a separate earth conductor back to the substation as per figure A3.2. Figure A3.2 Schematic of a TN-S system The required connection back to the substation is most commonly adopted by means of an earth clamping to the sheath of the incoming supply cable which facilitates connections to both supply side earth conductor and the consumer installation earthing terminal. TN-C-S system In this system the neutral and protective functions are done by a single conductor for part of a system. Usually the supply neutral and earth are combined at electricity distributor’s side with a conductor named as PEN (protective Earth and neutral) conductor but they are separated within the installation as shown in figure A3.3. This is also called as Protective Multiple Earthing (PME for short). The Earthing terminal of the consumer installation is connected to the supplier's neutral. IEC classification for Supply Systems based on Earthing Practices 231 Any breakage of the common neutral cum earth wire of the PEN conductor can result in the enclosures of electrical equipment inside the premises assuming line voltage when there in insulation failure. It is therefore essential to maintain the connection integrity of this common neutral-cum-earth conductor. Figure A3.3 Schematic of a TN-C-S system A3.1.2 TT and IT systems In a TT system, no earth is provided by the supplier and installation requires own earth rod (usually common with overhead supply lines) and is typically adopted as per figure A3.4. Figure A3.4 Schematic of a TT system IT Supply is, for example, portable generator with no earth connection or with impedance earth and installation using its independent earth rod as per figure A3.5. 232 Practical Electrical Wiring Standards - AS 3000:2018 Figure A3.5 Schematic of an IT system An installation connected to a protective multiple earth supply is subject to special requirements concerning the size of earthing and bonding leads, which are generally larger in cross-section than those for installations fed by supplies with other types of earthing. Full discussions with the Electricity Supply Company are necessary before commencing such an installation to ensure that their needs will be satisfied. The cross-sectional area of the equipotential bonding conductor is related to that of the neutral conductor as shown in table A3.1 Table A3.1 Minimum cross-sectional area of main equipotential bonding conductor for PME systems Neutral conductor section (mm²) Main equipotential bonding conductor section (mm²) 35 or less 10 Over 35 and up to 50 16 Over 50 and up to 95 25 A3.2 Installations where use of TN-C-S system is prohibited Danger can arise when the non-current carrying metalwork of an installation is connected to the neutral, as is the case with a PME-fed system. The earth system is effectively in parallel with the neutral, and can thus share the normal neutral current under certain conditions. This current will not only be that of the installation itself, but also be part of the neutral current of neighboring installations. It therefore follows that the earthing wires of an installation may carry a significant current even when the main supply to that installation is switched off. This could clearly cause a hazard if in a potentially explosive part of an installation, such as a petrol storage tank, the earth wire were to carry part of the neutral current of a number of installations. For this reason, the use of PME supply system is prohibited in the case of petrol filling stations. Such installations must be fed from TN-S supply systems. IEC classification for Supply Systems based on Earthing Practices 233 The difficulty of ensuring bonding requirements on construction sites means that PME supplies must not be used for temporary supplies. Electricity Supply Regulations also do not permit the use of TN-C-S supplies to feed some sites described briefly below. A3.2.1 Construction sites The objective of electrical installation on a construction site is to provide lighting and power to enable the work to proceed. By the very nature of the installation, it will be subjected to the kind of rough treatment, unlike in most fixed installations. Those working on the site may sometimes be ankle deep in mud and thus are particularly susceptible to an electric shock. They may be using portable tools in situations where danger is more likely than in most factory situations. Hence special regulations are applicable to construction power installations to minimize the danger to working personnel. Apart from the use of TN-S system certain additional requirements are also applicable, as given below: • Distribution and supply switches and isolators must be protected to minimum IP44 to protect from objects more than 1 mm thick and from splashing water. The main isolator must be capable of being locked or otherwise secured in the 'off' position. Emergency switches should disconnect all live conductors including the neutral. • Sockets on a construction site must be separated extra-low voltage (SELV) or protected by a 30mA RCD or must be electrically separate from the rest of the supply, each socket being fed by its own individual transformer. Most sockets may have to be fed at 110 V from center-tapped transformers to comply with this requirement as 12V hand tools would draw heavy currents. • Cables and their connections must not be subjected to strain, and cables must not be run across roads or walkways without mechanical protection. Circuits supplying equipment must be fed from a distribution assembly including over current protection, a local RCD if necessary. Socket outlets must be enclosed in distribution assemblies, fixed to the outside of the assembly enclosure, or fixed to a vertical wall. Sockets must not be left unattached, as is often the case on construction sites. • As the construction proceeds, the installations will be moved and frequently altered. It is usual for such installations to be subjected to thorough inspection and testing at intervals, which shall never exceed three months. • The equipment used must be suitable for the particular supply to which it is connected, and for the duty expected on site. Where more than one voltage is in use, plugs and sockets must be non-interchangeable to prevent misconnection. The requirements for construction sites also apply to sites where repairs, alterations or additions are carried out, Demolition of buildings and Civil engineering operations, such as road building, coastal protection, etc. The special requirements for construction sites do not apply to temporary buildings erected for the use of the construction workers, such as offices, toilets, cloakrooms, dormitories, canteens, meeting rooms, etc. These areas/buildings are not subject to changes as construction work progresses, and are thus exempt from these requirements. A3.2.2 Marina supply systems A marina is a location, often a harbor, for leisure craft to berth. Like residential caravans, such craft require external power supplies and shall take care of some special conditions given below. The marina often includes shore-based facilities such as offices, workshops, toilets, leisure accommodation and so on which are exempt from such special requirements. The electrical installation of a marina is subject to hazards not usually encountered elsewhere. These include the continuous presence of water and salt, the movement of the craft, increased corrosion due to the presence of salt water, galvanic action due to dissimilar metals and the possibility of equipment being submerged due to unusual wave activity in bad weather. 234 Practical Electrical Wiring Standards - AS 3000:2018 Hence the neutral of a TN-C-S system must not be connected to the earthed system of a boat so that the hazards, which follow the loss of continuity in the supply PEN conductor, are avoided. This condition rules out the use of PME supplies for marinas. Where TN-C-S supply is provided, it must be converted to a TT system at the main distribution board by provision of a separate earth electrode system of driven rods or buried mats with no overlap of resistance area with any earth associated with the TN-C-S supply. If the marina is large enough, it may be that the supply company will provide a separate transformer and a TN-S system. A common installation method is to provide a feed from the shore to a floating pontoon via a bridge or ramp, and then to equip the pontoon with socket outlets to feed the craft moored to it. Socket outlets may be single or three-phase types. Where multiple single-phase sockets are installed on the same pontoon, they must all be connected to the same phase of the supply unless fed through isolating transformers. Socket outlets should be positioned as close as possible to the berth of the vessel they feed, with a minimum of one socket per berth, although up to six sockets may be provided in a single enclosure. Each socket outlet must be provided with a means of isolation which breaks all poles on TT systems, and must be protected by an over current device such as a fuse or a circuit breaker. Groups of socket outlets must be RCD protected. Each socket or group of sockets must be provided with a durable and legible notice giving instructions for the electricity supply. A3.2.3 Caravan power supply A caravan is a leisure accommodation vehicle, which reaches its site by being towed using a vehicle. A motor caravan is used for the same purpose, but has an engine, which allows it to be driven; the accommodation module on a motor caravan may sometimes be removed from the chassis. Caravans will often contain a bath or a shower, and in these cases the special requirements for such installations will apply. Railway rolling stock is not included in the definition as a caravan. All dangers associated with fixed electrical installations are also present in and around caravans. Added to these are the problems of moving the caravan, including connection and disconnection to and from the supply, often by unskilled people. Earthing is of prime importance because the dangers of shock are greater. For example, the loss of the main protective conductor and a fault to the metalwork in the caravan is likely to go unnoticed until someone makes contact with the caravan whilst standing outside it. The requirements of the Electricity Supply Regulations do not allow the supply neutral to be connected to any metalwork in a caravan, which means that PME supplies must not be used to supply them. The power supply to a caravan must be made using approved type of coupler at a height of not more than 1.8 m from earth. The coupler socket (fixed to the caravan body) must have a springloaded lid, which will protect the socket when caravan is traveling, with a clear notice near the socket indicating voltage, current and frequency of the supply required by the caravan. This socket must be connected to a main isolator with 30mA RCD protection, which on operation will disconnect all live conductors. All metal parts of the caravan, with the exception of metal sheets forming part of the structure, must be bonded together and to a circuit protective conductor, which must not be smaller than 4 sq. mm except where it forms part of a sheathed cable or is enclosed in conduit. A3.2.4 Other locations These are locations such as swimming pools, saunas, and hospitals etc., where danger to human beings is more probable with the supply. The reason for this is that in some of the locations, the human beings are partly unclothed, without shoes and are in contact with water or their body is wet. The effect of any contact with live electrical parts could therefore be particularly dangerous. A hospital where open-heart surgery is performed poses even greater danger because of the effect of stray electric currents finding their way to the human heart through medical appliances used in the treatment. Also explosive hazards may exist in certain hospital locations handling anesthetic gases. The use of electrical systems in these cases will depend on the zone of use. These zones are IEC classification for Supply Systems based on Earthing Practices 235 defined in each case depending on the presence of vulnerable human body in the vicinity. Use of lower voltage isolated systems, earth fault alarms and RCD are advised depending on the application. 236 Practical Electrical Wiring Standards - AS 3000:2018 Appendix 4 Earthing Regulations and Practices from Other National Codes A4.1 USA- National Electrical Code (NEC) Regulations The design, installation and maintenance of earthing connections in electrical systems have been exhaustively studied and documented. Mandatory regulations have been established and are in use by different countries (example: NEC/NFPA codes of USA. Article 250 of NEC code of USA is dedicated to the subject of earthing). These regulations usually stipulate the minimum requirements to ensure safety of equipment and personnel but system designers are free to improve on them on the conservative side. NEC defines service equipment as switching and protective equipment installed at the point of entry of power from the electric power utility to the consumer premises. The provisions of NEC are meant to ensure that the electrical installation on the downstream side of the service equipment is free from defects that can cause fire, explosion or electric shock hazards under normal or fault conditions of the system. NEC recommends that all earthing electrodes including cold water piping, metallic building frames etc. used as earthing electrodes are bonded to the equipment earthing system at the service equipment earth. As discussed earlier, bonding of all building earthing in this manner ensures that no dangerous potential develops between the equipment earthing conductors, metal raceways, building structures, cold water mains etc. even though their potential with reference to the mean earth potential may be substantially higher. Any voltage difference between these points will be due to abnormal conditions such as an earth fault. But even so, the potential difference will not reach the Touch Potential limits thus ensuring that the system is free of shock hazards. Section 250-118 of NEC permits the use of various earthing conductors including tubular conduits used as cable raceway, cable armor and cable trays. Where earthing conductors are employed, it must be ensured that they are sized to withstand earth fault currents of value and duration appropriate to the circuit under consideration. If the conductor sizing is inadequate, the following may result: • Damage to the insulation of the earth conductor. In case the conductor is bare, insulation damage may occur in the phase conductor with which it is in contact. • Fusing of the earth conductor in extreme cases. Though this may result in the interruption of the fault current, it will cause the potential of the enclosure of the faulted equipment to rise beyond acceptable limits. 238 Practical Electrical Wiring Standards - AS 3000:2018 A4.2 Earthing practices as per South Africa Bureau of standards (SABS) A4.2.1 Industrial power transformer earthing Industrial power systems in South Africa typically employ the scheme shown in Fig A4.1 for earthing the MV/LV transformers. Figure A4.1 Typical industrial transformer earthing practice in South Africa It may be noted that the transformers are cable fed and they do not incorporate surge arrestors. The transformer LV neutral is earthed directly to an earth electrode and at the same time connected to the plant earthing network. The tank is connected to the earth network using at least two earth leads. The LV system neutral and the earth network of the plant to which the safety earth of all equipment is connected are thus bonded all through with metallic connections and earth fault currents return to the neutral via the metallic path. A4.2.2 Remote installations fed from pole mounted transformers The earthing requirements associated with remote MV/LV transformer fed installations are somewhat different from the approach adopted in industrial installations. These are installations with pole mounted transformer remotely installed and fed by an MV overhead line which in turn feeds isolated LV consumers through overhead lines. Moreover, the earth electrode resistance cannot be expected to be too low either. The arrangement suggested in SABS standards for this type of distribution is shown in Figure A4.2. Earthing Regulations and Practices 239 Figure A4.2 Earthing of remote distribution transformers/LV system It is noteworthy that the installation recommends the LV neutral to be earthed at a point well away from the transformer (usually at the first LV pole). The tank earthing is mainly to take care of faults between the MV system and the tank. The MV windings are protected by surge arrestors mounted on the body of the transformer and the LV neutral is connected to the transformer tank through a neutral surge arrestor. Though the MV surges will be transmitted into the LV system by the coupling effect, the high surge impedance of the LV lines will prevent the surges being propagated into the LV system. Also the surges being of very short duration will not pose a safety hazard. This design takes into account the following factors: • Need to prevent the LV neutral from assuming dangerous touch potential when an MV to tank fault occurs. • Need for limiting the voltage across the neutral arrestor. • Need for detecting MV to tank faults by MV earth fault protection A4.3 Earth Electrodes LV electrode resistance should be normally expected to permit sufficient fault currents for detection. With the LV line to neutral voltage of 240 V the resistance limit works out to 2.4 ohms, if a earth fault current of 100 amps is to be obtained. However, with the TN-C-S type of system, all equipment enclosures are directly connected to the neutral at the service inlet itself and thus the current flow does not involve the earth path at all. 240 Practical Electrical Wiring Standards - AS 3000:2018 So, the limit of LV earthing resistance is decided by the criteria of obtaining sufficient fault current when there is a MV to LV fault without involving the tank or core (refer to Figure A.4.3) Figure A4.3 Equivalent Circuit for Combined MV/LV earthing Assuming an MV Earth fault protection setting of 40 A the earth loop resistance can be arrived as 318 ohms (12700/40) for 22 kV system. The permissible earth electrode resistance works out to 273 ohms (after taking off the values of NGR and substation earth resistance). If we consider a safety factor of 400%, the maximum value of LV earth resistance can be taken as 68 ohms. The safety factor will ensure that the seasonal changes of soil resistivity will have no adverse effect on protection operation. Standard configurations are available in the code for 70 ohm electrodes and can be used in the design. A4.4 Earth electrode design factors The construction of earthing electrodes depends on the local codes applicable. The purpose however is common. It is to establish a low resistance (and preferably low impedance) path to the soil mass. It can be done using conductors that are exclusively meant for this function or by structures/ conductors used for other functions but which are essentially in contact with soil. However, while using the latter category, it must be ensured that the earth connection is not inadvertently lost during repair works or for any other reason. Factors contributing to earth electrode resistance are: • The resistance of electrode material • Contact resistance of the electrode with soil • Resistance of the soil itself The values of the first two are quite low compared to the last and can be neglected. Soil resistivity for a given type of soil may vary widely depending on: • The presence of conducting salts • Moisture content • Temperature • Level of compaction Earthing Regulations and Practices 241 IEEE 142 gives several useful tables which enable us to determine the soil resistivity for commonly encountered soils under various conditions which can serve as a guideline for designers of earthing systems. These are reproduced in tables A4.1 and A4.2. Table A4.1 Effect of temperature on soil resistivity Temperature 0C Resistivity Ohm-m -5 700 0 300 10 80 20 70 30 60 40 50 50 40 Table A4.2 Effect of moisture content on soil resistivity Moisture content % Resistivity in Ohm-m Top soil Sandy loam Red Clay 2 **** 1850 **** 4 **** 600 **** 6 1350 380 **** 8 900 280 **** 10 600 220 **** 12 360 170 1800 14 250 140 550 16 200 120 200 18 150 100 140 20 120 90 100 22 100 80 90 24 100 70 80 242 Practical Electrical Wiring Standards - AS 3000:2018 When it is not possible to obtain the minimum resistance stipulations or if the earth fault current cannot be dissipated to the soil with a single electrode, use of multiple earth rods in parallel configuration can be resorted to. The soil layers immediately surrounding the electrode contribute substantially to the electrode resistance. More than 98% of the resistance is due to a soil cylinderhemisphere of 1.1 times the electrode length. This is called the 'critical cylinder'. Placing electrodes close to each other thus interferes with the conduction of current from each electrode and lowers the effectiveness. Hence earth rods are generally arranged in a straight line or in the form of a hollow rectangle or circle with the separation between the rods not lower than the length of one rod. A4.5 Earth electrode types from some national codes Examples are given from the National Electric Code (USA) and the South African Standards below to illustrate different approaches taken for the design of earth electrodes A4.5.1 Recommendations of NEC NEC Section 250 covers the different types of electrodes. Those in the first type are metal underground water pipes, metal frame of building etc. that are not specifically installed for the purpose of being used as earth electrodes. The other type is known as ‘made electrodes’ whose specific function is for use as earth electrodes. Examples of these are metal rods/pipes driven into earth, concrete encased electrodes, buried earth ring etc. It is to be noted that NEC does not require any special earth electrodes in an installation where some form of buried underground metalwork is already present and can be used for this purpose (this aspect of NEC is totally at variance with the prescription of the Australian Standard) Metal underground water mains used as earth electrodes should be in direct contact with earth for a minimum distance of 10 ft. and made continuous by bonding around insulating joints. Also, continuity should not depend on water meters, filters or any other removable devices. The earthing rods can also be one of the following types: • An effectively earthed metal frame or structure of a building • An electrode encased in two inches of concrete located within a concrete foundation footing at the bottom part, in direct contact with the earth • A buried earth ring around a building made of at least 20 ft. of copper conductor at a depth of over 2.5 ft Underground metal gas piping system shall not be used as an electrode. Also NEC code does not permit the use of Aluminum as suitable material for earth electrodes. Where electrodes of above types are not readily available, electrodes specifically made for use as earth electrodes will have to be deployed. These electrodes shall be driven into the soil in such a way that a substantial part of their length is below the permanent moisture level of the earth in the area under consideration. When more than one electrode is used they shall be separated by more than 6 ft. and preferably by one-rod length and shall be effectively bonded so as to result in a single composite electrode system. The length of electrodes shall not be lower than 8 ft. and in the case of pipes/conduits the diameter shall not be less than ¼” trade size. Rods shall not be lower than 5/8” diameter for use as made-electrodes. The electrodes shall be galvanized or otherwise metal-coated to minimize corrosive effects of being buried in the earth. Plate electrodes of 2 sq. ft. surface area and ¼” thick made of iron/steel plates and buried in soil at a depth of 2.5 ft. can also be used as electrodes. All non-conductive coatings such as paint/enamel and rust shall be scraped of the surface of the electrodes to ensure proper contact with soil. Resistance of made-electrodes shall not be lower than 25 ohms. In case this is not so, multiple electrodes bonded together shall be used to bring down the resistance value. Earthing Regulations and Practices 243 244 Practical Electrical Wiring Standards - AS 3000:2018 A4.5.2 Recommendation of South African Standard SCSASAAL9 This standard recommends earth electrodes using buried horizontal conductors, vertically driven electrodes or a combination of both. Buried horizontal conductors are easier to install and result in less steeper potential gradients during an earth discharge. This type of electrode (called as trench electrode) must be installed as deep as practicable but not less than 500 mm below ground level. The reasons for this are: • Less prone to mechanical damage • Better current dissipation using the layer of soil above the conductor • Lower voltage gradient during discharge Vertically installed electrodes may be extended to substantial lengths (15 to 90 m depth) and are able to make contact with low resistivity soils. At these depths the soil resistivity is same throughout the year and less prone to seasonal variations that are found on the soil layers near the surface. Vertical rods are also found to have superior surge performance and are useful for electrodes meant for lightning protection of structures. Electrodes constructed from a combination of driven rods and radial array of buried conductors ensure a stable resistance value and good performance for power frequency and high frequency earth discharges. They minimize the chance of high soil potential gradients and avoid failure of earth connection due to a single electrode conductor breakage. This standard specifies the following type of electrodes: • Non extendable earth rods in a multi electrode (preferably 3-point star) configuration • Linear trench electrode • Extendable earth rods • Vertically Installed conductor Linear trench electrodes are recommended where vertical rods are not convenient to use. This standard defines the minimum resistance of the earth electrode in LV installations neutral as 68 Ohms and that of the transformer tank earth electrode (in MV installations of 11 kV or 22 kV) as 30 Ohms. The reasoning behind this stipulation was explained under section A4.3 of this appendix. Standard SCSASAAL9 defines various electrode configurations having resistance of 30, 70 and 150 Ohm in different soils in the form of tables for easy selection. Figure A4.4 identifies some of these recommended arrangements. Appendix - 5 Practical Exercises Introductory chapters to AS/NZS 3000:2007 (Chapters -1, 2, 3 and 4) S. No Question 1.1 Indicate the voltage ranges of a.c. and d.c. installations for which AS/NZS 3000 is applied 1.2 Indicate two main advantages of regulations for electrical systems 2.1 Name two reasons on which a.c. systems over score d.c. systems for power generation, transmission and distribution. 2.2 Vector 1 lags Vector 2 by 60degrees and leads vector 3 by 90 degrees. Indicate these by a vector diagram 2.3 Earth fault can not be detected in unearthed system. Is it true or false? 2.4 A delta connection in a three phase system does not have _________ 2.5 What is the main feature of functional earthing? 3.1 Indicate three likely major hazards due to shock currents 3.2 Indicate two ways of avoiding shocks or its hazards? 3.3 Name the common insulation and the temperature rise limit adopted in electrical machinery Answer 248 Practical Electrical Wiring Standards - AS 3000:2018 S. No Question 3.4 Maximum numeral used for IP classification against water entry and its meaning are 3.5 An arm’s reach distance can be reduced by use of ___________ 4.1 Main disadvantage of solid earthing is __________________ 4.2 High resistance earthing is generally limited to _______________ applications 4.3 A non-let go threshold due to shock currents is possible when the shock current value is around _________ 4.4 Most common reasons for shock currents are _________________ with live parts 4.5 Protective earthing mainly limits the ________________ of the electrical equipment enclosures. 4.6 The common LV consumer supply connection as per IEC grouping based on earthing is ________ type. 4.7 Protective earthing for non electrical metallic parts are usually done by ____________ 4.8 To sense the fault currents in a system correctly, it is necessary to limit the value of ______________ 4.9 Indicate two factors that decide the choice of earth electrode quantity and its material in a location. 4.10 Indicate the main difference between core balance CT and other CT’s used for earth fault detection. Answer Practical Exercises 249 Where direct answers cannot be given, it is advised to refer AS/NZS 3000 and indicate the applicable clause. Chapter 5 - Section-1 General Principles S. No. 5.1 Question Mark the zones of arm’s reach for a person standing on a surface shown in plan view below. Surface “S” 5.2 Indicate, as piece of electrical equipment, what is the class of the cellular phone. 5.3 Indicate the limit of the number of cores allowed in flexible cord. 5.4 A sub DB is provided with phase/neutral conductors and the system is MEN. (Neutral earthed at mains). Indicate whether neutral conductor in the DB is classified as live part or earthed part. 5.5 What are the types of ELV systems? How they differ from each? 5.6 Indicate the main reason that can affect the touch voltage of different people at an enclosure with faulty circuit. 5.7 What are the limiting values for ELV? 5.8 TRUE/FALSE – A protection offered by having removable barriers shall be provided with protective interlocks also. 5.9 What is the maximum time limit for disconnecting the mains in case of indirect contact while using hand held class I equipment? AS/NZS 3000 clause Answer 250 Practical Electrical Wiring Standards - AS 3000:2018 S. No. Question 5.10 TRUE/FALSE – RCDs can prevent shocks due to indirect contacts. 5.11 What is the maximum permissible voltage allowed without barriers in dry areas? Are there any specific conditions for this? 5.12 Indicate the types of protection recommended for live parts supplied at different voltages within a system. AS/NZS 3000 clause Answer Practical Exercises 251 Chapter 6 - Section 2 Selection of Equipment S. No. Question 6.1 A common neutral conductor may be used for two or more circuits subject to satisfying certain conditions. Indicate one such condition. 6.2 Name common methods adopted to decide the maximum demand of an installation? 6.3 List the main locations where isolation of neutral in an a.c. system should be avoided. 6.4 What are the conditions where isolation of single pole is acceptable in a d.c. circuit? 6.5 When is the electrical installation in an outbuilding is to be considered as a separate electrical installation? 6.6 Which is the odd one out? a) Fuse b) MCCB c) ACB d) RCD 6.7 TRUE/FALSE - The breaking capacity of a device protecting a feeder can be lower than the breaking capacity of the upstream protective device. 6.8 What is the accepted sensitivity of RCDs for human protection 6.9 To avoid unwanted tripping while using RCDs, ensure that the sum of the normal leakage currents of electrical equipment on the load side of an RCD is less than ______ of its rated residual current. 6.10 What is the main characteristic to be taken care while using under voltage devices in motor circuits? 6.11 _______ space around a switchboard is considered essential to facilitate emergency exit. How is this space measured? AS/NZS 3000 clause Answer 252 Practical Electrical Wiring Standards - AS 3000:2018 S. No. Question 6.12 In general, a switchboard shall not be located within ____ of the ground, floor or platform. 6.13 Name a couple of places where locating a switchboard is prohibited. AS/NZS 3000 clause Answer 6.14. The maximum permitted current capacity of a conductor in an installation is 34 amperes. Calculate the operating current for the over current protective device in case of a) MCB b) fuse. (Refer clause 2.5.3 of AS/NZS 3000) with nominal ratings close to the maximum permitted current, 6.15. Calculate the minimum cross section of PVC insulated copper conductor feeding a circuit that can develop a fault current of 10kA. Also calculate the recommended size if the protective device can isolate this circuit in 0.5 seconds in case of short circuits. Practical Exercises 253 Chapter 7 - Section 3 Wiring Systems S. No. Question 7.1 What are the ambient temperatures applicable for cables in Australia and New Zealand a) in air and b) buried below ground. 7.2 For cables exposed to direct sunlight, ambient temperature correction factor shall be considered for a temperature equal to ________ 7.3 The minimum cross section area of parallel multiple conductors used in an installation shall be _______ 7.4 The current rating of HRC fuses should not be greater than _____% of cable current-carrying capacity of circuit protected by it. 7.5 What are the minimum copper and aluminium conductor sizes for aerial applications? 7.6 Joints in flexible cords may be acceptable if done with ______ 7.7 Indicate the preferred and alternative colours of cores for the following uses: Neutral Active line 7.8 What are the recommended bending radii for unarmoured and armoured cables in the absence of manufacturer recommendations? 7.9 The support interval for a LV suspended track system shall be not more than __________ 7.10 What are the conditions under which use of different voltage level conductors are permitted without segregation in LV systems? AS/NZS 3000 clause Answer 254 Practical Electrical Wiring Standards - AS 3000:2018 S. No. Question 7.11 What precaution is needed for single core cables used in Alternating Current systems? What are the reasons for this? 7.12 Indicate a couple of features recommended for the cable trunking applications. 7.13 The spacing between aerial conductors shall be increased by a suitable margin to take care of _________________ 7.14 In dicate the factors affecting the clearances to be maintained between aerial wiring systems at the supports operating at same voltages. 7.15 In indoor applications, cables supported by a catenary wire shall be maintained not less than _______ from any moving parts of equipment operating at an elevated temperature. AS/NZS 3000 clause Answer Practical Exercises 255 Chapter 8 - Section 4 Appliances and accessories S. No. Question 8.1 What are the permitted surface temperatures for hand held electrical equipment? 8.2 A maximum flexible cord or cable length of ______ is recommended for equipment wiring. 8.3 Three-pin/flat-pin plugs shall be connected so that, when viewed from the front of the socket-outlet, the order of connection of the three points (Active, neutral and earth) shall be in the order of ___________ in a clockwise direction. 8.4 Lampholders without suitable guards shall be mounted at a minimum height of _____ above the floor. 8.5 100W lamp shall be located away at a mnimum distance of _____ from flammable materials. 8.6 Minimum clearances for recessed Halogen Luminaire lighting from the roof structure shall be _____________. 8.7 All motors rated ______kW and above shall be protected by overload protective devices. 8.8 Current rating of conductors used for capacitors connected permanently in motor circuits shall exceed ____________ of the capacitor current or ________ of the motor conductor. 8.9 400V Capacitors shall be discharged to a minimum voltage of _____ within ____ minutes of disconnection. AS/NZS 3000 clause Answer 256 Practical Electrical Wiring Standards - AS 3000:2018 S. No. 8.10 Question A drainage pit/ chamber is needed while having equipments with dielectric liquid of capacity above ___________. AS/NZS 3000 clause Answer Practical Exercises 257 Chapter 9 - Section 5 Earthing Systems S. No. Question 9.1 The MEN system is equivalent to __________ system as per IEC regulations. 9.2 The minimum cross section for solid copper earth conductor shall be ___________ 9.3 Solid earthing conductors of aluminium shall adopt a minimum size of __________. 9.4 The size of a bare earthing conductor in the same system may be ________ (smaller or larger) than an insulated earthing conductor. 9.5 The maximum size of copper conductors used for earthing connection to an electrode is usually ____________sqmm 9.6 The minimum diameter of a copper clad steel circular earth rod shall be ____mm 9.7 Name a couple of applications, where earthing of exposed parts of enclosures is avoided in an installation. 9.8 What are the minimum depths to which vertical-type earth electrodes shall be driven________________ 9.9 Indicate two conditions, where earthing of lighting points can be avoided. 9.10 The resistance between the earth bar and any structural part of an installation required to be earthed shall not exceed __________ 9.11 What is the minimum size of bare copper and aluminium earthing conductors directly buried below ground? AS/NZS 3000 clause Answer 258 Practical Electrical Wiring Standards - AS 3000:2018 9.12. Calculate the minimum cross section of bare copper earthing conductor for a system that can develop a fault current of 25 kA and incorporated with a protective device that can isolate the faulty circuit in 0.4 seconds 9.13 A 240V circuit incorporates active conductor of 35sqmm and earthing conductor of 16sqmm both copper. Calculate the maximum circuit lengths permitted while using type C breaker rated 100 amperes. Compare it with the values as per table B1 in the standard Practical Exercises 259 Chapter 10 – Section 6 Damp situations S. No. Question 10.1 Indicate two main conecrns applicable in damp situation in regard to human safety. 10.2 A barrier upto a height of ______ or upto _______ can reduce the limits for classified zones in bath area 10.3 _______ and _______ can also limit the zone distances similar to barriers 10.4 Indicate the common shock protection methods in general areas that are not accepted in damp areas 10.5 A zone 2 cerified item can be used in _______ but not in ________ 10.6 ________ are generally allowed in zone 0 areas subject to considering suitable certification. 10.7 What are the important conditions for the source of the above items permitted in zone 0? 10.8 ___________ are not permitted genarally in all damp areas except for _____________areas 10.9 Generally IP rating is not critical in Zone ____ of residential bath areas 10.10 Unlike most of the other areas, refrigeration areas differ in terms of zone classification by having ____________ AS/NZS 3000 clause Answer 260 Practical Electrical Wiring Standards - AS 3000:2018 Chapter 11 – Section 7 Specific installations S. No. Question 11.1 Indicate specific considrations for fire pump controller control supply arrangement. 11.2 __________ is one of the main design consderations to be ensured for alternative power supply when used with grid supply . 11.3 Multiple generators operating in parallel shall be provided with __________ in the neutral circuits. 11.4 Electrical separation of a.c. supplies are achieved by use of ____________ 11.5 Recommended insulation resistance for separate supply circuits shall be minimum _______ with 500V DC 11.6 Voltage drop in an extra low voltage circuit is allowed upto ________ compared to ________ in normal voltage circuit as % of nominal operating voltage. 11.7 Aerial conductors of bare and insulated conductors can be maintained with same spacing for ________ systems AS/NZS 3000 clause Answer Practical Exercises 261 Chapter 12 – Section 8 Verification S. No. Question 12.1 _________ test shall be conducted as the first test in an installation as part of verification. 12.2 Resistance of main earthing consudtor shall be limited to a valie of ___________ 12.3 Earth fault loop impedance measurement shall be done after energisation to ensure ___________________ AS/NZS 3000 clause 12.4 Cross check the fault loop impedance values tabulated in Table 8.1 for 32 amps breaker with a disconnection time of 0.4 sec for Type B and Type C breakers, taking into account the AS/NZS mean tripping currents of 4 times and 7.5 times the nominal rating for these breaker types respectively. 262 Practical Electrical Wiring Standards - AS 3000:2018 Appendix 1 – Load demand A1.1. Determine the maximum demand of a single domestic electrical installation supplied at 240V single-phase with the following loads: • 36 lighting points • 20 m of lighting track • 12nos 10 A single socket-outlets • 6nos 10 A double socket-outlets • 1no 7.5kW range • 1no 3.6kW water heater A1.2. Determine the maximum demand of the heaviest loaded phase of a motel complex supplied by three-phase 415V with the following loads: • 300nos 60 W lighting points • 60nos 100 W 1-phase exhaust fans (permanently connected) • 70nos 10 A 1-phase single socket-outlets (permanently heated or cooled area) • 6nos 15 A 1-phase socket-outlets • 1no 12 kW 3-phase electric range • 2nos 1.5kW 3-phase borewell pump motor The loads are distributed over the three phases as below Red 110 lights 18 exhaust fans 20x10A socket outlets 2 x 15 A socket-outlet 3.2 kW oven 0.75 kW pump White 90 lights 20 exhaust fans 25x10A 2 x 15 A socket-outlets 4.4 kW hotplates Blue 100 lights 22 exhaust fans 25x10A 2 x 15 A socket-outlet 4.4 kW hotplates 0.75 kW pump Practical Exercises 263 Appendix 6 S. No Answer 1.1 1.2 1000V a.c. and 1500V d.c. • Safety • Uniformity • Easy selection of equipment • Good Workmanship 2.1 • • • 2.2 voltage transformation Three phase and single phase options Avoidance of commutators in generators 2 1 3 2.3 False. Second earth fault can be detected. It is true for first fault only. 2.4 Neutral 2.5 It is not for safety purposes. 3.1 • • • • fatality Falls and injury Burns Organ damages 3.2 • • • Limiting touch voltage Disconnection within shortest time Avoid probability of contact 3.3 Class F with class B rise 3.4 8 – Continuous immersion (with water pressure) 3.5 Hand tools or ladders 4.1 Higher earth fault currents. 4.2 Large power generator 4.3 10-25 milliamperes. 4.4 Direct and indirect contacts 4.5 Touch voltages 4.6 TN-C-S 4.7 Equipotential bonding 266 Practical Electrical Wiring Standards - AS 3000:2018 S. No Answer 4.8 Earth fault loop impedance 4.9 • • • Overall earth resistance needed Soil resistivity Corrosive nature of soil 4.10 • • Not connected in series with main power circuit Primary current rating Answers for Practical Exercises 267 Chapter 5 - Section-1 General Principles S. No. AS/NZS 3000 clause 5.1 1.4.12 Answer 1.25 m 5.2 1.4.29 Class III (only SELV is used). 5.3 1.4.36 Five 5.4 1.4.63 Live part 5.5 1.4.83 and 1.4.76 5.6 1.4.95 Body resistance. 5.7 1.4.98 50V a.c. or 120V ripple free d.c. 5.8 1.5.4.4 True 5.9 1.5.5.3 0.4 second 5.10 1.5.5.2 False. They only protect from effects of shock. 5.11 1.5.7 5.12 1.5.11.2 PELV (protected ELV) and SELV (separated ELV) are the types based on whether it is electrically separated from earth or not. 25V a.c. or 60V ripple-free d.c. where a large contact area with the human body is not expected and otherwise the limits are 6V and 15V respectively. Segregation or over voltage protection 268 Practical Electrical Wiring Standards - AS 3000:2018 Chapter 6 - Section 2 Selection of Equipment Answer S. No. AS/NZS 3000 clause 6.1 2.2.1.2 • • By ensuring continuity By using links at final subcircuits 6.2 2.2.2 • • • Calculation Measurement with meter By protective device rating 6.3 2.3.2.1.1 • • consumers mains or where neutral conductor is used as a PEN conductor 6.4 2.3.2.1.2 • • One pole earthed or connected to PE conductor ELV d.c. circuit 6.5 2.3.4.1 6.6 When its demand equals or exceeds 100 amps per phase and is provided with a switchboard. RCD – Doesnot protect against a short circuit True. But subject to limiting I2 t of conductor up to the feeder within the expected capacity. 6.7 2.5.4.5 6.8 2.6.1 6.9 2.6.2.1 6.10 2.8.1 6.11 2.9.2.2 • • 6.12 2.9.2.5 1.2 metres 6.13 2.9.2.5 • • • 30mA maximum One-third Starting current and its duration. 600 mm with doors open and breakers racked out. Near baths/ showers Near egress paths Near fire exits 6.14. The maximum permitted current capacity of a conductor in an installation is 34 amperes. Calculate the operating current for the over current protective device in case of a) MCB b) fuse. (Refer clause 2.5.3 of AS/NZS 3000) with nominal ratings close to the maximum permitted current, Solution: The nominal current I N shall be less than the allowable current I Z (which is 34 amps) Nearest MCB nominal current is 32 amps. The operating current for 32A MCB is 1.45 × 32 = 46.4 amps Answers for Practical Exercises 269 For fuse, I N shall be less than 90% of 34 amps (30.6 maps). Hence fuse I N rating (closest) may be 30 amperes. The operating current will be 30 × 1.6 = 48 amperes for the fuse. NOTE: As indicated in the clause, the above are based on the assumption that the conductor is not continuously loaded to the full load current. 6.15. Calculate the minimum cross section of PVC insulated copper conductor feeding a circuit that can develop a fault current of 10kA. Also calculate the recommended size if the protective device can isolate this circuit in 0.5 seconds in case of short circuits. Solution: This is based on equation 2.4 of AS/NZS 3000. K2 S2 2 t= I K=111 for PVC insulated copper conductor. Same clause approves that the conductor can safely withstand the temperature rise caused by short circuit up to a maximum of 5 seconds. Substituting the values 10000× 5 111 S= = 201 sqmm Nearest conductor size can be 240 sqmm if there is no proper protective device. With a SC protective device operating in 0.5 seconds, it is possible to use a lower size conductor. Substitute t with 0.5 in the above equation, 10000× 0.5 111 S= = 63 sqmm. Nearest conductor standard size of 70 sqmm may be adopted with SC Protection. NOTE: K = 111 for 40°C ambient (For Australian ambient conditions). 270 Practical Electrical Wiring Standards - AS 3000:2018 Chapter 7 - Section 3 Wiring Systems S. No. AS/NZS 3000 clause Answer 7.1 3.3.2.1 • • 7.2 3.3.2.11 20°C + ambient air temperature 7.3 3.4.3 4 sqmm 7.4 3.4.4 90% 7.5 Table 3.3 7.6 3.7.2.8 7.7 Table 3.4 7.8 3.9.6 7.9 3.9.7.5 1.5 metre 7.10 3.9.8.3 • • • • 40 and 30 deg C 25 and 15 deg C Copper: 6 sqmm Aluminium: 16 sqmm Suitable cable couplers • • Black, alternatively light blue. Red , alternatively colours not associated with earth and neutral cores 6 times and 12 times of the conductor radius respectively. • cables with double insulation or cables insulated for the highest voltage they operate or cables separated by continuous barriers. 7.11 3.9.10.2 No steel wire or steel tape armour to avoid eddy current flow and consequent temperature rise in the cores. 7.12 3.10.3.9 • • • 7.13 3.12.3.1 Sags resulting while operating at higher temperatures (upto 1150 C) 7.14 Table 3.10 7.15 3.13.3 • • Opening provisions for covers Continuous through walls, floors, etc Accessibility Span whether conductors are bare or inulated. 100mm Answers for Practical Exercises 271 Chapter 8 - Section 4 Appliances and accessories S. No. AS/NZS 3000 clause Answer 8.1 Table 4.1 8.2 4.3.5 2.5m 8.3 4.4.5 Earth, active, neutral 8.4 4.5.1.1 8.5 Table 4.2 600mm 8.6 Figure 4.7 200mm 8.7 4.13.2 0.37kW 8.8 4.15.2.3 135% of capacitor or one-third of motor (whichever is greater) 8.9 4.15.3.1 50V, 1 minute 8.10 4.16 Metallic: 55 deg C Non metallic: 65 deg C 1.8m 50 litres 272 Practical Electrical Wiring Standards - AS 3000:2018 Chapter 9 - Section 5 Earthing Systems S. No. AS/NZS 3000 clause Answer 9.1 5.1.3 9.2 5.3.2.1.1 10 sqmm 9.3 5.3.2.1.2 16 sqmm 9.4 5.3.3.1.3 Smaller. Refer K factors as per standard. 9.5 5.3.3.2 9.6 Table 5.2 9.7 5.4.1.1 • • • 9.8 5.3.6.3 In Australia, 1.2 m and in New Zealand, 1.8 m 9.9 5.4.3 9.10 5.4.6.3 0.5 ohm 9.11 5.5.5.5 Copper – 35 sqmm Aluminium – Not permitted TN-C-S 120 sqmm 12mm • • • Double insulation items SELV cicruits PELV circuits Lamps in all insulated lamp holders Timber pole mounted ELV lamps 9.12. Calculate the minimum cross section of bare copper earthing conductor for a system that can develop a fault current of 25 kA and incorporated with a protective device that can isolate the faulty circuit in 0.4 seconds Solution: This is same as the earlier problem under (Chapter 6) section 2 based on equation 2.4 of the standard which appears as equation 5.1 in section 5 (5.3.3.1.3) of the standard except for the insulation t= K2 S2 I2 K=170 for bare copper conductor. Substituting the values S= 25000× 0.4 = 93sqmm 170 Answers for Practical Exercises 273 Nearest conductor size that can be used is 95sqmm. 9.13 A 240V circuit incorporates active conductor of 35sqmm and earthing conductor of 16sqmm both copper. Calculate the maximum circuit lengths permitted while using type C breaker rated 100 amperes. Compare it with the values as per table B1 in the standard Solution: This is given by equation B7 reproduced below: L MAX = 0.8U 0 S ph S pe I a ρ ( S ph + S pe ) For type C breaker, tripping current is 7.5 times 100, i.e. 750 amps Substituting the values as outline in clause B5.2.2 of the standard L MAX = 0.8 × 240 × 35 × 16 = 125 m 750 × 0.0225 × (35 + 16) Table B1 indicates permitted circuit lengths with 35 sqmm active and 10 sqmm earth conductors with 100 amps breaker, as 85m for type C at 230V. Corresponding L MAX at 240V is 1.04 × 85 = 88.4 m (Correction factor per note 4), which means another 35mtrs may be permitted by having increased earth conductor size.. (NOTE: The maximum length obtained only satisfies the fault protection requirements of Clause 1.5.5.3 i.e. automatic disconnection. The tripping time, overload, short-circuit and voltage drop requirements shall be considered independently for a final decision) 274 Practical Electrical Wiring Standards - AS 3000:2018 Chapter 10 – Section 6 Damp situations S. No. AS/NZS 3000 clause • • • 10.1 10.2 6.2.2 10.3 10.4 Answer Reduced body resistance Likleyhood of more contacts Mosture and water affecting insulation 1.8 metres or shower height, whichever is higher. Ceilings and Walls 6.2.3 etc • • Prortection by obstacles Keeping live parts out of reach 10.5 Zone 3, Zone 1/ zone 0 10.6 Lamps 10.7 • • • 10.8 Switchboards, Hosing down 10.9 Zone 3 10.10 Entire room in one zone Source located outside zone 0 12V a.c. or 30V d.c. source SELV/PELV Answers for Practical Exercises 275 Chapter 11 – Section 7 Specific installations S. No. AS/NZS 3000 clause Answer 11.1 7.2.9.4 Shall be direct tapped from main supply without control transformer. 11.2 7.3.3 Avoid backfeeding except when governed by written agreement. 11.3 7.3.6 Isolation switches 11.4 7.4.2 Isolating transformers 11.5 7.4.7.1 1 mega ohm 11.6 7.5.7 10% and 5% 11.7 7.5.11.2 ELV systems 276 Practical Electrical Wiring Standards - AS 3000:2018 Chapter 12 – Section 8 Verification S. No. AS/NZS 3000 clause 12.1 Figure 8.1 12.2 8.3.5 12.3 8.3.9.3 Answer Earth resistance test 0.5 ohm . Inclusion of upstream system 12.4 Cross check the fault loop impedance values tabulated in Table 8.1 for 32 amps breaker with a disconnection time of 0.4 sec for Type B and Type C breakers, taking into account the AS/NZS mean tripping currents of 4 times and 7.5 times the nominal rating for these breaker types respectively. Solution: Nominal Phase voltage U 0 Nominal current rating of CB IN = 230V = 32 amps I a for Type B breaker = 4times 32 amps = 128 amps Hence maximum fault loop impedance while using type B breaker = 230/128= 1.796 ohm I a for Type C breaker = 7.5 times 32 amps = 240 amps Hence maximum fault loop impedance while using type C breaker = 230/240= 0.958 ohm A similar calculation is adopted for all values in Table 8.1 of the standard. Answers for Practical Exercises 277 Appendix 1 – Load demand A1.1. Determine the maximum demand of a single domestic electrical installation supplied at 240V single-phase with the following loads: • 36 lighting points • 20 m of lighting track • 12nos 10 A single socket-outlets • 6nos 10 A double socket-outlets • 1no 7.5kW range • 1no 3.6kW water heater Solution: Refer Table C1 under column 2 for single domestic installation. Following come under Load Group A(i) 36 lighting points plus 20 m of lighting track =3+4= 7A Load Group B(i): 12 x 10 A single socket-outlets + 6 x 10 A double socket-outlets = 24 nos 10 A outlets =10+5= 15A Load Group C 7500 W range will draw a full load current = 7500/240 = 31.25A Its demand =31.25 x 0.5 = 15.6A Load Group F: Water heater 3600 W = 3600/240= 15 A Hence Total demand = 7+15+15.6 +15 = 52.6A A1.2. Determine the maximum demand of the heaviest loaded phase of a motel complex supplied by three-phase 415V with the following loads: • 300nos 60 W lighting points • 60nos 100 W 1-phase exhaust fans (permanently connected) • 70nos 10 A 1-phase single socket-outlets (permanently heated or cooled area) • 6nos 15 A 1-phase socket-outlets • 1no 12 kW 3-phase electric range • 2nos 1.5kW 3-phase borewell pump motor The loads are distributed over the three phases as below Red 110 lights 18 exhaust fans 20x10A socket outlets 2 x 15 A socket-outlet 3.2 kW oven 0.75 kW pump White 90 lights 20 exhaust fans 25x10A 2 x 15 A socket-outlets 4.4 kW hotplates Blue 100 lights 22 exhaust fans 25x10A 2 x 15 A socket-outlet 4.4 kW hotplates 0.75 kW pump Solution: This is a motel complex and hence table C2, column 2 will be applicable with 240V phase voltage. Current = Watts/ Voltage 278 Practical Electrical Wiring Standards - AS 3000:2018 Load 60W Lights 100W exhaust fans 10A sockets 15A sockets Oven/ hotplates Pump motor Total amps Group A A B(ii) B(iii) C D RED Load 110 points 0.25A/point at 240V 110×0.25×0.75 18 fans 0.417A per fan 18×0.417×0.75 20 nos 2900W total 2 nos 15 + (0.5× 15) 3200W Full amps 750W Full amps WHITE BLUE Amps Load Amps 20.625A 90 points 90×0.25×0.75 16.99A 5.63A 20 fans 6.255 20×0.417×0.75 12.08A 22.5A 13.33A 25 nos 3400W 2 nos 15 + (0.5× 15) 4400W Full amps 14.17A 22.5A 18.33A 3.125A 77.29A 78.24A Load Amps 100 points 18.75A 100×0.25×0.75 22 fans 22×0.417×0.7 5 25 nos 3400W 2 nos 15 + (0.5× 15) 4400W Full amps 750W Full amps 6.88A 14.17A 22.5A 18.33A 3.125A 83.75A Answers for Practical Exercises 279 Appendix 7 Reducing the Impact of Power Supply Outages Appendix M of the Standard provides guidance on the mitigation of adverse effects that disruption to power supply may cause in living and homecare medical situations. Where the owner or operator of an installation or part of an installation has identified it beneficial to reduce the impact of power supply outages and provide continuity of supply, the Appendix gives guidance so that the electrical installation will function correctly for the intended purpose, and take into account the mitigation of foreseeable adverse effects that disruption to power supply may cause. Active assisted living Active assisted living (AAL) systems and services enable independent living through the use of information and communications technology (ICT) by ensuring usability, accessibility, interoperability, security and safety for all users. Homecare medical Home-based medical procedures such as dialysis, respiratory support and cardiac care and tele-monitoring, which is the remote collection and transmission of data for ongoing patient management belong to this type of field. The following steps are provided to supplement the requirements of the Standard for active assisted living and homecare medical applications: (a) Enroll the electrical installation for the priority restoration in the event of supply failure with the electricity retailer and/or electricity distributor providing power supply to the electrical installation (b) Ensure that all trees have sufficient clearance from the aerial conductors to prevent damage, or interruption of electrical supply, if it is aerial power supply Arrangements Following steps are provided to supplement the requirements of the Standard for the above said applications: (a) Enroll with electricity retailer and/or electricity distributor who provides power supply to the electrical installation, for priority restoration in the event of supply failure Circuit Design for Low Voltage Installations 287 (b) Ensure that all trees have sufficient clearance from aerial conductors, if the supply to the electrical installation is by aerial conductors. Inspections should also be carried out at appropriate intervals and corrective action taken, if required. (c) Provide protection discrimination throughout the electrical installation (d) Ensure that the capacity of the mains, switchboards and final subcircuit wiring is able to supply the expected maximum loading of the electrical installation (e) Use miniature circuit breakers (MCBs) or residual current breaker with overload (RCBO) for overcurrent protection in domestic installations (f) Use a portable Type 1, 10 mA RCD for each item of medical equipment in home care areas of a domestic electrical installation (g) Ensure constant charging of batteries to maintain full charge where batteries are used as energy storage for power supply equipment and that regular maintenance of batteries is carried out according to battery manufacturers’ instructions (h) Provide for easy connection of a portable generating set, by use of a dedicated extension cord socketoutlet wiring in the electrical installation or changeover switch NOTES: 1. A grid connected inverter is not able to use the output from a PV array when the normal mains supply to the electrical installation has failed 2. An inverter/ UPS powered from a large battery may be able to provide an alternative power supply cover for a short term supply failure 288 Practical Electrical Wiring Standards - AS 3000:2018 .. Appendix 8 Electrical Conduits There are two series of Standards for electrical conduits that run in parallel within Australia and New Zealand. The first is the AS/NZS 2053 series and the second is the AS/NZS 61386 series, which is based on but not equivalent to the IEC 61386 series. The relevant Standards are as follows: • AS/NZS • 2053 Conduits and fittings for electrical installations • 2053.1 Part 1: General requirements • 2053.2 Part 2: Rigid plain conduits and fittings of insulating material • 2053.4 Part 4: Flexible plain conduits and fittings of insulating material • 2053.5 Part 5: Corrugated conduits and fittings of insulating material • 2053.6 Part 6: Profile wall, smooth bore conduits and fittings of insulating material • 61386 Conduit systems for cable management • 61386.1 Part 1: General requirements • 61386.21 Part 21: Particular requirements—Rigid conduit systems • 61386.22 Part 22: Particular requirements—Pliable conduit systems • 61386.23 Part 23: Particular requirements—Flexible conduit systems The AS/NZS 2053 series and the second is the AS/NZS 61386 series provide the marking methods for the conduits. The AS/NZS 61386 series gives the option of using the first four numerals in the classification, as a minimum, to mark conduits and fittings. First and second numerals in comparison with duty ratings in AS/NZS 203 series and AS/NZS 61386 series are shown in the below Tables. 290 Practical Electrical Wiring Standards - AS 3000:2018 Circuit Design for Low Voltage Installations 291 .. Appendix 9 Installation of Arc Fault Detection Devices (AFDDs) Appendix O of the Standard provides guidance on the selection and installation of AFDDs to mitigate the risk of igniting an electrical fire in final sub-circuits downstream of the arc fault detection device (AFDD). Fire ignition by arc faults is normally due to one or more of the following: (a) Insulation defects between live conductors leading to fault currents (b) Broken or damaged (reduced cross-section) conductors under load current conditions (c) Terminal connections with high resistance Arc fault detection devices installed in final sub-circuits are capable of detecting fault conditions that result within the installation. There are also other types of arcing fault devices used to mitigate the risk of igniting an electrical fire and or causing an electrical explosion in highcurrent circuits, high-current LV switchboards and HV switchboards, and these are not the AFDDs described in Appendix O. There are two types of arc faults: (i) Series arcing faults - Electrical arc within a single active or neutral conductor, in series with the connected load (ii) Parallel arcing faults - Electrical arc between an active and a neutral conductor, or between two active conductors of different phases, or between a live conductor and the protective conductor, in parallel with the connected load Circuit Design for Low Voltage Installations 293 Types of Arc Fault Miniature overcurrent circuit breakers (MCBs), fuses, and residual current devices (RCDs) are not capable of reliably protecting against the effects of arcing, and their response times at the level of current associated with electrical arcing. AFDDs that do not incorporate integral overcurrent or residual current protection do not provide protection against sustained thermal overloads, short-circuit currents, or residual currents at power frequency. NOTE: Installations in which the use of AFDDs may be appropriate include the following: (a) Premises with sleeping accommodation (b) Premises and locations for children, handicapped or elderly people (c) Premises for gathering of people (d) Locations with risks of fire due to the nature of processed or stored materials (e) Locations constructed with combustible materials (f) Fire propagating structures (g) Locations where irreplaceable goods are stored or displayed and may be endangered 294 Practical Electrical Wiring Standards - AS 3000:2018 .. Appendix 10 Guidance for Installation of Electrical Vehicle Socket – Outlets and Charging Stations Appendix P of the Standard provides guidance for: (a) Circuits intended to supply energy to electric vehicles (b) Circuits intended for feeding back electricity from electric vehicles into the supply system This applies to off-board equipment including the vehicle connector for charging electric road vehicles, with a rated supply voltage up to 1000 V ac or up to 1500 V dc and a rated output voltage up to 1000 V ac or up to 1500 V dc. Electric road vehicles (EV) includes plug-in hybrid road vehicles (PHEV), that derive all or part of their energy from on-board rechargeable energy storage systems, (RESS), including traction batteries. Applications to which the Appendix provides guidance are as follows: (a) The characteristics and operating conditions of off-board charging equipment (b) The connection between off-board charging equipment and electric vehicle (c) The required level of electrical safety for off-board charging equipment Requirements and tests referenced in this Standard can be found in the following Standards: (a) AS/NZS 61439 series for tests and related requirements for low-voltage switchgear and controlgear assemblies (b) IEC 62752 for the in-cable control protection device for Mode 2 charging of electric road vehicles (IC-CPD) as a part of the complete system (c) IEC 62196 series for vehicle coupler, plug and socket-outlet Exclusions The Appendix does not provide guidance on: (a) Safety aspects related to maintenance (b) Charging of trolley buses, rail vehicles, industrial trucks and vehicles designed primarily for use offroad The Appendix also provided information on the following: 296 Practical Electrical Wiring Standards - AS 3000:2018 • • • • • Definitions Maximum demand Installation Devices for protection against indirect contact by automatic disconnection of supply Other equipment such as socket-outlets and vehicle connectors, ratings of vehicle couplers, socket-outlets and plugs, permitted socket-outlets or vehicle connectors, types of connection, charging stations and cables, periodic verification Circuit Design for Low Voltage Installations 297 Appendix 11 Dc Circuit Protection Application Guide Appendix Q of the Standard provides provides guidance for the selection of circuit protection and switching devices operated on a dc supply that would be deemed to meet the design, equipment selection and installation criteria of this Standard. Where a single contact is used to interrupt the current flow of a dc circuit, consideration should be given to the size of the contact, the air gap, arc suppression and the use of multiple contacts. The Appendix provides information on the following: • The phenomenon of arc suppression • Switchgear types • Dc ratings • Provision of isolation and overcurrent protection • Switchboard locations • Final subcircuit wirings and fittings • Inverters Pre-Workshop Questionnaire Practical Electrical Wiring Standards- AS/NZ 3000:2018 Full Name City/Country Date Would you kindly answer the questions below. Please answer all questions to the best of your ability. 1. What are the main reasons for your attendance at this training workshop? Please provide two. 2. Briefly describe your main responsibilities in your current job. 3. Where/How did you hear about this workshop? IDC Technologies Brochure Web Site Colleague Other ______________________________ 4. Have you been on a previous IDC Technologies workshop? 5. In which area do you work? Trades Manager Technician IT Technologist Engineer Yes No Other(s)_____________________________ 6. How many people are in your organisation? Less than 50 7. Between 50 and 100 Greater than 100 Have you previously worked in the field of this training course? If so, in which area? Technical Questions 1. What is the maximum permitted voltage drop at any point of the distribution system? 2. What is the accepted sensitivity of RCD’s for human protection? 3. What are the conditions under which use of different voltage level conductors are permitted without segregation? 4. What is the permitted surface temperature rise for hand held electrical equipments 5. Indicate two conditions where earthing of electrical system can be avoided