Detuned reactor calculation This example will show Calculations of detuned reactor installed series with capacitor banks of 80kVAr 525V and 100 kVAr 525V with factor reactor 7 % in 50Hz. 1. detuned reactor calculation in 80 kVAr 525 V Capacitance from Capacitor bank 80kVAr / 525V 0.525 0.08 1 1 0.924 2 2 3.445Ω Resonance frequency equation: 1 2 √ This detuned Reactor has a factor reactor 7 % . it means that when this filter operated in 50 Hz system value of capacitance is 7% from reactance. 0.07 2 0.07 2 2 0.07 2 2 √ √0.07 50 With this value,we will get resonance frequency when detuned reactor applied in capacitor bank. 1 2 √ 50 √0.07 189 L at resonance frequency is 1 0.911Ω 2 0.911Ω 2 0.768 Xl and Xc when this filter applied in 50 Hz system are, 1 3.445Ω 2 2 0.241Ω Reactive power output when detuned reactor applied with capacitor bank in series at 525V , 0.525 3.445 0.241 86.025 if detuned reactor and capacitor bank installed in 400V so, the reactive power output will be reduced. 400 525 86.025 49.9 2. detuned reactor calculation in 100 kVAr 525 V Capacitance from Capacitor bank 100 kVAr / 525V 0.525 0.1 2.756Ω 1 1 2 1.155 2 Resonance frequency equation 1 2 √ This detuned Reactor has a factor reactor 7 % . it means that when this filter operated in 50 Hz system value of capacitance is 7% from reactance. 0.07 2 0.07 2 2 0.07 2 √0.07 50 2 √ With this value,we will get resonance frequency when detuned reactor applied in capacitor bank. 1 2 √ 50 √0.07 189 L at resonance frequency is 1 0.729Ω 2 0.729Ω 2 0.614 Xl and Xc when this filter applied in 50 Hz system are, 1 2 2 2.756ΩΩ 0.193Ω Reactive power output when detuned reactor applied with capacitor bank in series at 525V. 0.525 2.756 0.193 107.54 if detuned reactor and capacitor bank installed in 400V so, the reactive power output will be reduced. 400 525 62.4 107.54