NFPA 80 – Fire Doors Russell J Corriveau CFDI, CAI, RL Fire Door Overview NFPA 80: Swing Fire Doors & NFPA 101: Delayed Egress Devices 20170429 R1 Copyright © 2016, 2017 ASSA ABLOY Sales and Marketing Group, Inc., an ASSA ABLOY Group company.. All rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY Sales and Marketing Group, Inc. is prohibited. ± ± × × Chapter 6 Swinging Doors with Builders Hardware 6.4.4.2.2 Fire exit hardware 6.4.4 Locks or Latches. 6.4.4.2.2 Fire exit hardware shall have a permanently attached label that bears the serial number and shows the manufacturer’s name and type of approval. 60 Fire Exit Hardware must be labeled with Serial Number, Manufacturer and type of approval. 60 Copyright 2015 NFPA 80 2013 Edition Chapter 6.4.4.2.2 Chapter 6 Swinging Doors with Builders Hardware 6.4.4.2.3 The label shall differentiate 6.4.4 Locks or Latches. 6.4.4.2.3 The label shall differentiate between panic hardware, which is not acceptable for use on fire doors, and fire exit hardware. 61 Panic Hardware Fire Exit Hardware Labels for Panic and Fire Rated Device must be different and Panic Hardware can not be used on Fire Rated Doors. 61 Copyright 2015 NFPA 80 2013 Edition Chapter 6.4.4.2.3 4.5.3.1 Number of Means of Egress. Two means of egress, as a minimum, shall be provided in every building or structure, section, and area where size, occupancy, and arrangement endanger occupants attempting to use a single means of egress that is blocked by fire or smoke. The two means of egress shall be arranged to minimize the possibility that both might be rendered impassable by the same emergency condition. A minimum of 2 means of egress are required for all occupied building and structures. 13 Point Fire Door Inspection Check list 1) Labels are clearly visible and legible. 2) No open holes or breaks exist in surfaces of either the door or frame. 3) Glazing, vision light frames, & glazing beads are intact and securely fastened in place, if so equipped 4) The door, frame, hinges, hardware, and noncombustible threshold are secured, aligned, and in working order with no visible signs of damage. 5) No parts are missing or broken. 6) Door clearances do not exceed clearances listed in 4.8.4 and 6.3.1.7. 7) The self-closing device is operational; that is, the active door completely closes when operated from the full open position. 13 Point Fire Door Inspection Check list 8) If a coordinator is installed, the inactive leaf closes before the active leaf. 9) Latching hardware operates and secures the door when it is in the closed position. 10) Auxiliary hardware items that interfere or prohibit operation are not installed on the door or frame. 11) No field modifications to the door assembly have been performed that void the label. 12) Meeting edge protection, gasketing and edge seals, where required, are inspected to verify their presence and integrity. 13) Signage affixed to a door meets the requirements listed in 4.14.