ECM1500 Outdoor Cabinet User Manual Version Revision date BOM V1.3 December 3, 2009 31012154 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Copyright © 2009 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice. Safety Precautions To reduce the chance of accident, please read the safety precautions very carefully before operation. The "Caution, Note, Warning, Danger" in this book and on the product do not represent all the safety points to be observed, and are only supplement to various safety points. Therefore, the installation and operation personnel must receive strict training and master the correct operations and all the safety points before operation. When operating Emerson products, the operation personnel must observe the safety rules in the industry, the general safety points and special safety instructions specified in this book. If you purchase an outdoor power supply without SPD, you should install an SPD at the front-end of AC input, otherwise, the power supply system will generate over-voltage. Electrical Safety I. Hazardous voltage Danger Some components of the outdoor cabinet system carry hazardous voltage in operation. Direct contact or indirect contact through moist objects with these components will result in fatal injury. Observe safety rules in the industry when installing the power supply system. The installation personnel must be licensed to operate high voltage and AC power. In operation, the installation personnel are not allowed to wear conductive objects, such as watches, bracelets, bangles and rings. When you spot the cabinet with water or moisture, turn off the power immediately. In moist environment, precautions must be taken to keep moisture out of the power supply system. "Prohibit" warning label must be attached to the switches and buttons that are not permitted to operate during installation. Danger High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance with the local rules and regulations. Only those who are licensed to operate high voltage and AC power can perform high voltage operations. Danger To avoid electric shock hazard for outdoor environment and outdoor equipment, the non-professionals are prohibited to operate or maintain the outdoor power supply system. II. Tools Warning In high voltage and AC operation, specialized tools must be used. III. Thunderstorm Danger Never operate on high voltage, AC, iron tower or mast in the thunderstorm. In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be well earthed in time to avoid damage by lightning strikes. IV. ESD Note The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the sensitive components. The other end of the ESD wrist strap must be well earthed. V. Short circuit Danger During operation, never short the positive and negative poles of the DC distribution unit of the outdoor cabinet system, or the non-earth pole of the outdoor cabinet system and the earth. The power supply system is a constant-voltage DC power device, short circuit will result in equipment burning and endanger human safety. VI. Reverse connection Warning Never reverse-connect the AC input live line and neutral line, or else the system will be damaged. Check the polarity of the cable and connection terminal when performing DC live operations. As the operation space in the DC distribution unit is very tight, please carefully select the operation space. Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation. Use insulated tools. In live operation, keep the arm, wrist and hand tense, so that when the tool in operation slips, the movement of the human body and tool is reduced to a minimum. Battery Danger Before any operation on battery, read carefully the safety precautions for battery transportation and the correct battery connection method. Warning If customers prepare batteries themselves, the battery installation and maintenance should meet relevant safety standards. Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent battery short circuit and overflow of electrolyte. The overflow of electrolyte will erode the metal objects and PCBs, thus causing equipment damage and short circuit of PCBs. Before any operation on battery, pay attention to the following points: 1. Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist. 2. Use specialized insulated tools. 3. Use eye protection device, and take preventive measures. 4. Wear rubber gloves and apron to guard against electrolyte overflow. 5. In battery transportation, the electrode of the battery should always be kept facing upward. Never put the battery upside down or slanted. Connection And Testing Of The Outdoor Cabinet Before installing subrack power supply in the cabinet, you should finish the connection and testing of the subrack power supply according to the corresponding subrack power supply user manual and then testing the outdoor cabinet. Others I. Sharp object Warning When moving equipment by hand, wear protective gloves to avoid injury by sharp object. II. Power cable Note Noti c Please verify the cable labels before connection. III. Signal cables Note Noti c The signal cables should be routed at least 150mm away from power cables. Contents Chapter 1 Overview ............................................................................................................................................................ 1 1.1 Model Description ................................................................................................................................................. 1 1.2 Composition & Configuration ................................................................................................................................ 1 1.3 Operating Theory .................................................................................................................................................. 4 1.4 Features................................................................................................................................................................ 5 Chapter 2 Installation .......................................................................................................................................................... 6 2.1 Safety Regulations................................................................................................................................................ 6 2.2 Installation Preparation ......................................................................................................................................... 6 2.3 Mechanical Installation.......................................................................................................................................... 7 2.3.1 Installing The Outdoor Cabinet .................................................................................................................. 7 2.3.2 Opening And Closing Cabinet Door........................................................................................................... 8 2.4 Electrical Installation ............................................................................................................................................. 9 2.4.1 Connecting Power Cables ......................................................................................................................... 9 2.4.2 Connecting Signal Cables ....................................................................................................................... 11 2.4.3 Sealing The Entry Holes .......................................................................................................................... 11 2.5 Battery Installation .............................................................................................................................................. 11 2.6 Installation Check................................................................................................................................................ 12 Chapter 3 Testing.............................................................................................................................................................. 13 3.1 Startup ................................................................................................................................................................ 13 3.2 Alarm Check And System Operation Status Check ............................................................................................ 13 3.3 Final Steps .......................................................................................................................................................... 13 Chapter 4 Maintenance ..................................................................................................................................................... 14 4.1 Routine Maintenance .......................................................................................................................................... 14 4.2 Replacing Parts Of Forced Ventilation Model Outdoor Cabinet .......................................................................... 15 4.2.1 Replacing Heat Control Board ................................................................................................................. 15 4.2.2 Replacing Fans........................................................................................................................................ 16 4.2.3 Replacing Door Status Sensor ................................................................................................................ 18 4.3 Replacing Parts Of Heat Exchanger Model Outdoor Cabinet ............................................................................. 18 4.3.1 Replacing Environment Climate Control Unit........................................................................................... 18 4.3.2 Replacing Fans........................................................................................................................................ 20 4.3.3 Replacing Heater ..................................................................................................................................... 21 4.3.4 Replacing Door Status Sensor ................................................................................................................ 21 4.4 Replaciing Parts Of Air-condition Model Outdoor Cabinet .................................................................................. 22 4.4.1 Replacing air-conditioner ......................................................................................................................... 22 4.4.2 Replacing Emergent Ventilation Unit ....................................................................................................... 22 4.4.3 Replacing Door Status Sensor ................................................................................................................ 22 Appendix 1 Technical And Engineering Parameters ......................................................................................................... 23 Appendix 2 Wiring Diagram............................................................................................................................................... 24 Appendix 3 Schematic Diagram ........................................................................................................................................ 27 Chapter 1 Overview 1 Chapter 1 Overview ECM1500 outdoor cabinet (outdoor cabinet for short) is a power supply system used outdoors. It provides outdoor protection and operation environment. It contains thermal control units and AC power distribution units. The cabinet can accommodate different Emerson subrack power supplies according to your requirement so as to form power supply systems with different capacities. This chapter introduces the model description, composition & configuration, operating theory and features of the outdoor cabinet. 1.1 Model Description The outdoor cabinet is available in three models, configured with different models of thermal control unit (forced ventilation, heat exchanger and air-condition). Taking the forced ventilation model for example, the model description of the outdoor cabinet is given in Figure 1-1. EC M 1500 F 1 - 48 300 Internal power capacity: 300A, 150A, 120A Internal power voltage:48Vdc Version No. Thermal control method: F (forced ventilation), H (heat exchanger), A (air-condition) Maximum heat productivity in cabinet:1500W Application: mobile network integrated cabinet Emerson outdoor cabinet Figure 1-1 Model description 1.2 Composition & Configuration Composition The outdoor cabinet is composed of thermal control units, power distribution units and related structures. Three models of thermal control units are available: forced ventilation, heat exchanger and air-condition. Configuration 1. The configuration of the forced ventilation model outdoor cabinet is given in Table 1-1. Table 1-1 Configuration list of the forced ventilation model outdoor cabinet Component Thermal control unit Power distribution unit Configuration Fan 4 pieces Heat control board 1 piece Heat control extension board 1 piece AC power distribution 1 route 10A single-phase AC socket; one route 25A single-phase AC input MCB DC power distribution DC input terminals Power and reserved space Sharing space: 15U, you can adjust space according to requirement Door status sensor 1 piece ECM1500 Outdoor Cabinet User Manual 2 Chapter 1 Overview The structure of the forced ventilation model outdoor cabinet is shown in Figure 1-2. Figure 1-2 Structure of the forced ventilation model outdoor cabinet 2. The configuration of the heat exchanger model outdoor cabinet is given in Table 1-2. Table 1-2 Configuration list of the heat exchanger model outdoor cabinet Component Thermal control unit Power distribution unit Configuration Fan 4 pieces Environment climate control unit 1 piece AC power distribution 1 route 10A single-phase AC socket; one route 25A single-phase AC input MCB DC power distribution DC input terminals Power and reserved space Sharing space: 15U, you can adjust space according to requirement Door status sensor 1 piece The structure of the heat exchanger model outdoor cabinet is shown in Figure 1-3. Figure 1-3 Heat exchanger model outdoor cabinet ECM1500 Outdoor Cabinet User Manual Chapter 1 Overview The configuration of the air-condition model outdoor cabinet is given in Table 1-3. Table 1-3 Configuration list of the air-condition model outdoor cabinet Component Thermal control unit Power distribution unit Configuration Outdoor air-condition 1 piece Emergent ventilation unit 1 set AC power distribution 1 route 10A single-phase AC socket; 1 route 25A single-phase AC input MCB DC power distribution DC input terminals Power and reserved space Sharing space: 15U, you can adjust space according to requirement Door status sensor 1 piece The structure of the air-condition model outdoor cabinet is shown in Figure 1-4. Figure 1-4 Air-condition model outdoor cabinet ECM1500 Outdoor Cabinet User Manual 3 4 Chapter 1 Overview 1.3 Operating Theory Heat dissipation theory for forced ventilation model outdoor cabinet The cold air is sucked in through the front door air filter at the lower part of the outdoor cabinet. It passes through the battery compartment, user equipment and subrack power supply in turn. Finally, the hot air is discharged by the fans at the top of the outdoor cabinet. In this way, the equipment and power modules in the cabinet are cooled, as shown in Figure 1-5. Heat dissipation fan Air outlet Subrack power supply Sharing space Air inlet Figure 1-5 Heat dissipation access for forced ventilation model outdoor cabinet Heat dissipation theory for heat exchanger model outdoor cabinet A heat exchanger is fitted on the door of the outdoor cabinet. It can exchange the heat between the cold air outside the cabinet and the hot air inside the cabinet. In this way, the equipment and power modules in the cabinet are cooled, as shown in Figure 1-6. Internal circulation air inlet of heat exchanger Internal circulation air outlet of heat exchanger Figure 1-6 Heat dissipation theory for heat exchanger model outdoor cabinet ECM1500 Outdoor Cabinet User Manual Chapter 1 Overview 5 Heat dissipation theory for air-condition model outdoor cabinet An outdoor air-conditioner is fitted on the door of the outdoor cabinet to cool the cabinet. It is in this that the equipment and power modules in the cabinet are cooled. In case of air-conditioner fault or AC mains failure, the emergent ventilation units automatically startup to dissipate heat emergently, as shown in Figure 1-7. Top emergent ventilation fan Return air inlet of air-condition Outdoor air-condition Air outlet of air-condition Figure 1-7 Heat dissipation theory for air-condition model outdoor cabinet 1.4 Features z Variable subrack power supply: The outdoor cabinet can accommodate standard 19” and 23” subrack power supply. z Variable space: The power space, reserved space and the battery compartment space are interchangeable. You can adjust the space according to the actual requirement. z Thermal control unit: Three different models are available for your selection according to the local, environment and requirement. z Safety guideline: The equipment compartment satisfies IP*5 waterproof requirement and IP5* dustproof requirement. z Environment pollution level within the outdoor cabinets is 2. ECM1500 Outdoor Cabinet User Manual 6 Chapter 2 Installation Chapter 2 Installation This chapter introduces installation and cable connection. Strictly follow the instructions provided in this chapter to carry out the installation and cable connection. 2.1 Safety Regulations Certain components in this power supply system have hazardous voltage and current. To ensure personnel safety, always follow the instructions below: 1. Only the trained personnel with adequate knowledge of the outdoor cabinet shall carry out the installation. The Safety Precautions listed before the Contents of this manual and local safety rules in force shall be adhered to during installation. 2. All external circuits below -48V connected to the power supply system must comply with the SELV requirement defined in IEC 60950. 3. To avoid electric shock, do not conduct any operation or maintenance within the outdoor cabinet under thunderstorm or humid weather. 4. Make sure that the outdoor cabinet is powered off before any operations can be carried out within the cabinet. 5. The power cables should be routed and protected properly, so that the cables are kept away from the operation and maintenance personnel. 2.2 Installation Preparation Unpacking inspection The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done by representatives of both the user and Emerson Network Power Co., Ltd. To inspect the equipment, you should open the packing case, take out the packing list and check against the packing list that the equipment is correct and complete. Make sure that the equipment is delivered intact. Preparing tools The installation tools are given in Table 2-1. The tools must be insulated and ESD-proof processed before they are used. Table 2-1 Tool Installation tools Specification Tool Combination wrench (hatch, club) Adjustable wrench Electrician diagonal pliers Electrician sharp nose pliers Wrench set (10#, 13#, 16#, 18#, 21#) 200mm 150mm 150mm Steel tape 5m Electric knife Normal type Digital multimeter Gradienter Blinkers Normal type To prevent splash Impact electric drill Power socket Fireproof mud Configured in the accessories Safety shoes Specification Box wrench 16mm Cross screwdriver Slotted screwdriver Wire cutters Hydraulic-pressure compaction pincher 100mm, 200mm 100mm, 200mm Maximum 300mm2 Hammer ECM1500 Outdoor Cabinet User Manual Maximum 300mm2 Three and a half bit digital display With Φ14 impact aiguille With 5m cable To prevent puncture and for insulation Chapter 2 Installation 7 2.3 Mechanical Installation 2.3.1 Installing The Outdoor Cabinet The outdoor cabinet must be installed directly onto the cement floor. Step 1: Mark the specific installation position of the outdoor cabinet It is recommended to determine the installation position in compliance with the clearance requirements given in Table 2-2. Table 2-2 Clearances Installation clearances Front Top Left Right Back 750mm 700mm 100mm 100mm 100mm Step 2: Install expansion bolts 480 657 For forced ventilation model outdoor cabinet, by referring to Figure 2-1; for heat exchanger model and air-condition model outdoor cabinet, by referring to Figure 2-2, it is recommended to enlarge the installation size of the cabinet base because of the existence of the anti-toppling device (see Figure 2-3), determine the exact central points of the installation holes on the floor, and mark them with a pencil or oil pen. Use the electric drill (aiguille: Φ14) to dig holes (depth: 70mm) at the marked points. Clean the drilled holes off dust. Put the expansion bolts into the holes and knock them with a hammer till they are totally in. 88.5 650 700 Figure 2-1 Installation size 1 of the cabinet base (unit: mm) 1100 480±0.5 130 900 650±0.5 Expansion bolt Front door Figure 2-2 Installation size 2 of the cabinet base (unit: mm) Step 3: Fix the cabinet ECM1500 Outdoor Cabinet User Manual 8 Chapter 2 Installation Move the cabinet to the installation position. Make the installation holes on the base coincide with those dug on the floor. Screw the M10 anchor bolt down into the expansion pipe in the floor. Pay attention to move the cabinet from the pallet in factory and install the anti-toppling device, as shown in Figure 2-3. After installation, the cabinet should stand firmly no matter how it is shaken, then you can remove the anti-toppling device from the inside of the cabinet. Anti-toppling device Figure 2-3 Anti-toppling device 2.3.2 Opening And Closing Cabinet Door You need to open and close the cabinet door during the cabinet installation, operation and maintenance. Procedures for opening and closing the cabinet door are as follows: Step 1: Insert the key into the keyhole, and turn the key clockwise until the door handle pops out. Step 2: Turn the handle counter-clockwise 90°, as shown in Figure 2-4. Pull the handle until the door opens. 90° Figure 2-4 Turning the handle ECM1500 Outdoor Cabinet User Manual Chapter 2 Installation 9 Step 3: Adjust the door stay bar to the position shown in Figure 2-5 to prevent the door from closing automatically. Door stay bar Figure 2-5 Door stay bar Step 4: Restore the door stay bar to its original position and close the door. Finally, turn the handle to its original position and press it down until a click is heard. 2.4 Electrical Installation All the cables must be put through metal pipes for protection. The metal pipe should be connected to the PE bar reliably. Plastic coated metal hoses are recommended. Earth cable and AC input cables enter the cabinet through the right side of the cabinet bottom. Signal cables, user equipment cables and DC cables enter the cabinet through the left side of the cabinet bottom. 2.4.1 Connecting Power Cables Connecting earth cable Step 1: Cut the cable bushings covering the cabling holes (shown in Figure 2-6) on the bottom plate of the cabinet with an electrician knife. Step 2: Lead the earth cable into the cabinet through a cabling hole, and route it along the cable holders, as shown in Figure 2-6. Step 3: Connect one end of the earth cable to the earth terminal in the cabinet, and solder the other end to the earth metal base reliably. ECM1500 Outdoor Cabinet User Manual 10 Chapter 2 Installation Step 4: Use nylon cable ties to tie the earth cable to the cable holders. AC input MCB Earth terminal Cable holder Cabling hole Figure 2-6 Positions of earth terminal and cabling hole Connecting AC input cables If the outdoor cabinet has been installed Emerson matched subrack before delivery, the AC cable connection between subrack and cabinet should have been done by Emerson. You only need to connect the AC input cables according to the subrack user manual. If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 220V AC power to the AC input MCB on the right side of the cabinet (shown in Figure 2-6), so as to ensure the cabinet operation. Connecting DC cables If the outdoor cabinet has been installed Emerson matched subrack before delivery, the DC cable connection between subrack and cabinet should have been done by Emerson. You only need to connect load cables according to the subrack user manual. If the outdoor cabinet has not been installed Emerson matched subrack before delivery, you should connect 48V DC power to DC input terminal on the left side of the cabinet (shown in Figure 2-7), so as to ensure the cabinet operation. ECM1500 Outdoor Cabinet User Manual Chapter 2 Installation 11 2.4.2 Connecting Signal Cables The cabinet provides four pairs of dry contacts for the user. All the dry contacts must be connected to the signal output terminal block, which is fixed on the left side of the cabinet. The position of the signal output terminal block is shown in Figure 2-7. DC input terminal Signal output terminal block Figure 2-7 Position of signal output terminal block Peel the signal cables and insert their ends into the corresponding terminals, then fasten the connection by tightening the screws on the terminals. The functions of the dry contact are given in Table 2-3. Table 2-3 Port No. 1, 2 Dry contact functions Definition Remark Over temperature alarm Default value 3, 4 Thermal control unit failure Default value 5, 6 Door alarm Default value 7, 8 Spare Configurable 2.4.3 Sealing The Entry Holes After cable connection, use fireproof mud to seal the cabling holes (shown in Figure 2-6). 2.5 Battery Installation The battery compartment can accommodate a battery string of capacity not higher than 50Ah. Batteries are classified into front-terminal battery and general battery. Note 1. The batteries may carry dangerous current. Before connecting the battery cables, make sure all the battery input MCBs are off. 2. Make sure that the battery cable polarities are correct. Otherwise, both the battery and the cabinet will be damaged! 3. Insulate the installation tools. Be careful not to damage the plastic battery case or the battery terminals during installation. Check before installation 1. Check that the battery shells are in good condition. 2. Check that the polarities of the terminals are in accordance with the polarity marks on the battery shell. 3. Check that the terminal screws are fastened. ECM1500 Outdoor Cabinet User Manual 12 Chapter 2 Installation Installation procedures Note 1. When installing two battery strings or more, install the lower battery string first. While removing them, remove the upper battery string first. 2. This chapter is applicable to Emerson subrack and battery cables. It is a reference when you configure subrack and battery cables for yourself. Step 1: Open the battery MCBs and AC input MCBs. Step 2: Place the batteries one by one in the battery compartment from right to left, with distance between adjacent batteries at least 10mm. Step 3: Remove the battery terminal covers, and connect the plate electrodes between the batteries in turn. Note that the mid-voltage sampling cable should be connected to the plate electrode between the second and the third batteries. Step 4: Connect the positive battery cables (red) in the battery compartment to the battery positive terminals. Connect the negative battery cables (black) in the battery compartment to the battery negative terminals. Attach the acid and alkali integration box (battery accessory) to the internal side of the right panel of the cabinet. Step 5: After installing the battery strings, use the 3M double-side adhesive tape pasted on the battery temperature sensor to paste the sensor onto the center of the upper-layer battery string. Step 6: Measure the battery string voltage. If the voltage value is correct, replace the battery terminal covers. 2.6 Installation Check After installation, check the installation against the list given in Table 2-4. Table 2-4 Check item No. 1 2 3 Cabinet installation 4 5 6 7 1 2 Electrical connection 3 4 5 6 Installation check list Description Check that the cabinet is level, upright and steadily fixed Check that all bolts are tightened, especially those in electrical connections, that all bolts have plain washers and spring washers, and that the washers are not reversed Check that there are no irrelevant materials in the cabinet, and clear them away if any Check that the cabinet paint is intact. If there are scratches, paint them immediately with antirust paint to prevent corrosion Clean up the cabinet Check that the door can move freely, the locks are in good condition and the door stay bar is fixed Check that the dummy plates are installed at the reserved space where no customer device is installed. Check that the burglarproof components (if configured) and battery baffles (if configured) are installed Verify the specifications of all MCBs and cables Check the correctness of bus bar connections, input and output cable connection, and connection between the power system and the system grounding Check the correctness of the batteries number and connection, and battery strings polarities Make sure all the cable connections are firm and reliable Check the connection point, line sequence and polarities of DC cables. Check the connection polarities of the batteries. Check that the connection points are fixed and the cable connections are correct and reliable Check that the cables are tidy, and the cable binding is normative ECM1500 Outdoor Cabinet User Manual Chapter 3 Testing 13 Chapter 3 Testing This chapter introduces the testing after installation. The corresponding safety rules shall be adhered to in the testing. This testing should be done after the subracks in the cabinet are tested. 3.1 Startup Note Before the test, inform the chief manufacturer representative. Only the trained electrical engineer can maintain and operate this equipment. In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets, bangles and rings. During operation, parts of this equipment carry hazardous voltage. Misoperation can result in severe or fatal injuries and property damage. Before the test, check the equipment to ensure the proper earthing. Make sure that the AC input and DC input are normal. Forced ventilation check After power-on, the heat control board enters self testing and the fans accelerate to full speed gradually. After a few minutes, the fans stop. If the environmental temperature is about 35°C, the fans will operate at low speed. Heat exchanger check After power-on, the simple control unit enters self testing and the fans accelerate to full speed gradually. After a few minutes, the fans stop. If the environmental temperature is about 35°C, the internal fans will operate at low speed and the external fans will stop. Air-condition check After power-on, the air-condition starts to operate. If the environmental temperature is about 35°C, the internal fans of the air-condition will operate at low speed and the compressors of the external fans will stop. 3.2 Alarm Check And System Operation Status Check Alarm check Disconnect the thermal control units, so as to check that if the thermal control units can trigger thermal control unit alarm. System operation status check There should be no alarms during normal system operation. 3.3 Final Steps Disconnect all test equipment from the outdoor cabinet and make sure that materials irrelevant to the equipment have been all removed. Restore the outdoor cabinet to its original condition and close the cabinet door. Check and handover the equipment that the user has purchased. Note down all the operations taken, including time of the operation and name of the operator. OK Comments If any defect is found in this equipment, inform the personnel responsible for the contract. If repairing is needed, please fill in the FAILURE REPORT and send the report together with the faulty unit to the repairing center for fault analysis. ECM1500 Outdoor Cabinet User Manual 14 Chapter 4 Maintenance Chapter 4 Maintenance This chapter describes the routine maintenance, alarm and fault handling, and part replacement of the power supply system. Note 1. The maintenance must be conducted in compliance with relevant safety rules. 2. Only the trained personnel with adequate knowledge about the outdoor cabinet shall work on the internal parts of the system. 4.1 Routine Maintenance Inspect the power supply system periodically and shoot the troubles in time if any. The routine maintenance items are given in Table 4-1. Table 4-1 Item Thermal control unit Paint and galvanization layer on the cabinet Front door air filter (for forced ventilation model and air-condition model) Period Routine maintenance list Inspection method Guide Check alarm and operation states. If the thermal control units run abnormally, refer this chapter to replace relevant components Once half a year Visual inspection Once half a year Visual inspection If there is any paint peeling or scratches, mend the painting immediately Visual inspection If dust accumulated on the front door air filter, loosen the fixing screws of the air filter cover of the front door (shown in Figure 4-1). Then take off the air filter cover and brush off the dust. If the air filter is damaged, replace it. Finally, replace the air filter cover Once half a year Air filter Fixing screw of air filter Air filter Fixing screw of air filter Air-condition model outdoor cabinet Forced ventilation model outdoor cabinet Figure 4-1 Air filter ECM1500 Outdoor Cabinet User Manual Chapter 4 Maintenance 4.2 Replacing Parts Of Forced Ventilation Model Outdoor Cabinet 4.2.1 Replacing Heat Control Board Replace the heat control board using the following procedures: Step 1: Loosen the two fixing screws to remove the cover (shown in Figure 4-2), and then you can see the heat control board. The appearance of the heat control board is shown in Figure 4-3. Fixing screw of cover Cover Figure 4-2 Cover position SW2 SW1 Alarm indicator Figure 4-3 Appearance of the heat control board ECM1500 Outdoor Cabinet User Manual 15 16 Chapter 4 Maintenance Step 2: Disconnect J11, J12 and J2 terminals (shown in Figure 4-4) in sequence, and then disconnect the rest connection terminals on the heat control board. H1 J7 J6 SW1 SW2 ON J2 J10 J12 J11 H2 J3 H4 H3 B Figure 4-4 Heat control board terminals layout Step 3: Loosen the fixing screws on the heat control board. Replace the heat control board with a new one. Step 4: Reverse connection sequence in step 2 to connect terminals, so as to check that the indicators show correctly when fan fails. In normal condition, no alarm indicators will be on. Step 5: Set the SW2 switch according to Table 4-2. Table 4-2 Name Label on the corresponding cover Bit “1” Bit “2” Switch Setting description of the SW2 Silk print on the corresponding fan control board SW2 (shown in Figure 4-3) Setting description Put the switch to the ‘ON’ position (default), see Figure 4-3 Put the switch to the ‘OFF’ position (default), see Figure 4-3 Step 6: Press the SW1 self-test button (shown in Figure 4-3) to ensure that the fan can start normally. Step 7: Replace the cover of the heat control board. 4.2.2 Replacing Fans Fan alarm circuit The fan-cooling unit of the outdoor cabinet is mainly composed of 2 ~ 4 axial flow fans. The fan alarm circuit is shown in Figure 4-5, where the blue line is the alarm line. VCC (Red) (Blue) MOTOR DRIVER IC R FG SIGNAL VCE (Black) GROUND (Yellow) Figure 4-5 VFG Ic Illustration of the fan alarm circuit ECM1500 Outdoor Cabinet User Manual Chapter 4 Maintenance 17 Fan alarm indicators The position of the alarm indicators is shown in Figure 4-3. The alarm indicators 1 ~ 4 on the heat control board correspond to fans 1 ~ 4 (alarm indicator 5 is the temperature sensor alarm indicator). Fan replacing procedures If the fan is faulty, the corresponding indicator will be on. Follow the following procedures to replace the fan. Step 1: Make sure that the fan-control terminals (J11 and J12 are hot pluggable) on the heat control board are inserted firmly. The fan-control terminals are shown in Figure 4-4. Step 2: Ensure that Bit 2 of SW2 switch is put to the “OFF” position. Step 3: Press the SW1 self-test button (shown in Figure 4-3). If the fans do not work, make sure that the fan cables are perfect. Step 4: Loosen the fixing screws at the cabinet top cover to open the top cover. (Opening the top cover, pull it forward and then lift up its front not more than 30°. Otherwise the top cover will be fallen.) Step 5: Disconnect the fan power terminals at the top of the cabinet. Use a multimeter to measure the voltage between the positive power cable and the negative power cable. Check if the voltage is close to the DC output voltage (54.0V). If the fan power voltage is normal, the fans are damaged. Carry out the next step. Step 6: Loosen the fixing screws of the fans and replace the fans, as shown in Figure 4-6. Fan Figure 4-6 Fan position Step 7: Reconnect the fan power terminals, and press SW1 self-test button (shown in Figure 4-3) to ensure that the fan can startup normally. Step 8: Replace the cabinet top cover. ECM1500 Outdoor Cabinet User Manual 18 Chapter 4 Maintenance 4.2.3 Replacing Door Status Sensor There is a door status sensor installed in the cabinet for detecting the close or open status of the cabinet door. The alarm will be eliminated only when the cabinet door is closed. The door status sensor requires no particular maintenance; just replace it when it is damaged. If the door is closed, while the door status sensor alarm occurs, the sensor must have been damaged. The position of the sensor is shown in Figure 4-7. Remove the sensor top cover and then the two screws. Replace the old sensor with a new one and finally fix the sensor and the signal cables with the screws. Door status sensor Figure 4-7 Position of the door status sensor 4.3 Replacing Parts Of Heat Exchanger Model Outdoor Cabinet 4.3.1 Replacing Environment Climate Control Unit Appearance and terminal layout The appearance of the environment climate control unit is shown in Figure 4-8, and the terminal layout is shown in Figure 4-9. DIP switch Earth nut Figure 4-8 Environment climate control unit ECM1500 Outdoor Cabinet User Manual Chapter 4 Maintenance J3 FAN2 J8 J14 J4 FAN3 TEMP. FAN4 J12 AC_OFF ALMOUT J5 SW101 J10 LED_FAULT LED_ALM LED_RUN J6 RS232 J11 J9 SW100 CAN J13 J7 J15 Figure 4-9 TEMP.&HUM. J2 WATER FAN1 POWER DOOR SMOKE INFRARED J1 19 Terminal layout of the environment climate control unit DIP switch description DIP switch function description and setting method: 1. Bit 1 ~ 4 are used to set addresses of the environment climate control unit. OFF: 0, ON: 1. Default address: 16. The setting method of the environment climate control unit (ECCU for short) is given in Table 4-3. Table 4-3 Bit 4 0 0 0 … 1 Bit 3 0 0 0 … 1 Setting method of ECCU address Bit 21 0 0 1 … 1 Bit 1 0 1 0 … 1 Address 16 1 2 … 15 Bit 1 ~ Bit 4 have been set in factory. You can change the settings according to your communication requirement. 2. The function description and setting method of Bit 5 ~ Bit 8 are given in Table 4-4. Table 4-4 Bit No. Function sescription and setting method of Bit 5 ~ 8 Function Setting method OFF: heat exchanger model 5 Choose cabinet model ON: forced ventilation OFF: normal when open; alarm when closed 6 Choose dry contact alarm mode ON: normal when closed; alarm when open OFF: serial port termperature & humidity sensor 7* Choose sensor ON: temperature sensor Choose whether stopping fans OFF: No 8 when AC mains fails ON: Yes Note*: When Bit 7 is placed to ON position, ECCU has no humidity acquisition function Default value OFF ON ON OFF Replacing procedures of the ECCU Step 1: Loosen the two fixing screws to remove the cover, and then you can see the ECCU. The position of cover is shown in Figure 4-10. ECM1500 Outdoor Cabinet User Manual 20 Chapter 4 Maintenance Fixing screw of cover Cover Figure 4-10 Cover position Step 2: Disconnect J15 terminal (shown in Figure 4-9), and then disconnect the rest connection terminals on the ECCU. Step 3: Loosen the fixing screws on the ECCU. Replace the ECCU with a new one. Step 4: Reverse connection sequence in step 2 to connect terminals, so as to check that the LED_FAULT (shown in Figure 4-9) indicator show correctly. Under normal instance, the LED_FAULT indicator is power-off. Step 5: Place the DIP switch to the correct position according to Table 4-3 and Table 4-4. Step 6: Press the SW1 self-test button (shown in Figure 4-9) to ensure that the fan can start normally. Step 7: Replace the cover of the ECCU. 4.3.2 Replacing Fans The heat exchanger of the outdoor cabinet is mainly composed of four centrifugal fans and a heat-exchanging core. If the fan is faulty, follow the following procedures to replace the fan. Step 1: Make sure that the fan-control terminals (J1, J2, J3 and J4 are hot pluggable) on the ECCU are inserted firmly. The fan-control terminals are shown in Figure 4-9. Step 2: Place the DIP switch to the correct position according to Table 4-3 and Table 4-4. Step 3: Press the SW1 self-test button (shown in Figure 4-3). If the fans do not work, make sure that the fan cables are perfect. Step 4: Disconnect the fan power terminals on the right side of the cabinet. Use a multimeter to measure the voltage between the positive power terminal and the negative power terminal. Check if the voltage is close to the DC output voltage (54.0V). If the fan power voltage is normal, the fans are damaged. Carry out the next step. Step 5: Loosen the fixing screws to remove cover of heat exchanger (shown in Figure 4-11), and then you can see the fans. Loosen the fixing screws of the fans to replace the fans. Step 6: Reconnect the fan power terminals, and press SW101 self-test button (shown in Figure 4-9) to ensure that the fan can startup normally. Step 7: Replace the heat exchanger cover. Fixing screw of heat exchanger cover Figure 4-11 Fixing screws of heat exchanger cover ECM1500 Outdoor Cabinet User Manual Chapter 4 Maintenance 4.3.3 Replacing Heater Step 1: Switch off the AC input MCB, as shown in Figure 4-12. AC input MCB Figure 4-12 AC input MCB Step 2: Loosen the fixing screws of the heat exchanger cover to remove the cover. Step 3: Loosen the fixing screws of the heater (shown in Figure 4-13). Disconnect all the cable connectors of the heater to remove the heater. Step 4: Replace the heater with a new one. Reverse the preceding steps to install the new heater. Step 5: Check all the cable connection. If OK, power on the outdoor cabinet. Heater Figure 4-13 Heater position 4.3.4 Replacing Door Status Sensor Refer to 4.2.3 Replacing Door Status Sensor. ECM1500 Outdoor Cabinet User Manual 21 22 Chapter 4 Maintenance 4.4 Replaciing Parts Of Air-condition Model Outdoor Cabinet 4.4.1 Replacing air-conditioner Step 1: Switch off the AC input MCB, as shown in Figure 4-14. Disconnect all the cable connectors. AC input MCB Figure 4-14 AC input MCB position Step 2: Loosen the fixing screws of air-condition to remove and replace air-condition. 4.4.2 Replacing Emergent Ventilation Unit The emergent ventilation unit is composed of heat control board and fans. The replacing procedures of heat control board and fans are the same as that of the forced ventilation model outdoor cabinet. You can refer to 4.2.1 Replacing Heat Control Board and 4.2.2 Replacing Fans. 4.4.3 Replacing Door Status Sensor Refer to 4.2.3 Replacing Door Status Sensor. ECM1500 Outdoor Cabinet User Manual Appendix 1 Technical And Engineering Parameters 23 Appendix 1 Technical And Engineering Parameters Table 1 Parameter category Parameter Operating temperature Environmental EMC Technical parameters Storage temperature Relative humidity Altitude Others Conducted emission Radiated emission Immunity to EFT Immunity to ESD Immunity to Surges Immunity to radiation Immunity to conduction Safety regulation Insulation resistance Others Insulation strength MTBF ROHS Dimensions (mm) Mechanical Weight (kg) Description -10°C ~ +45°C (forced ventilation model), -40°C ~ +45°C (heat exchanger model), -40°C ~ +50°C (air-condition model) -40°C ~ +70°C 5%RH ~ 100%RH ≤ 2,000m (derating is required above 2,000m) No conductive dust or erosive gases. No possibility of explosion Class A EN55022 Level 3 EN61000-4-4 Level 3 EN61000-4-2 Level 4 EN61000-4-5 Level 3 EN61000-4-3 Level 3 EN61000-4-6 Compliant with IEC60950-1, IEC60950-22 At temperature of 15°C ~ 35°C and relative humidity not bigger than 90%RH, apply a test voltage of 500Vdc. The insulation resistances between AC circuit and earth, DC circuit and earth, and AC and DC circuits are all not less than 10MΩ (Remove the SPD, monitoring module and rectifiers from the system before the test.) AC circuit to earth: 50Hz, 2,500Vac DC circuit to earth: 50Hz, 1,000Vac Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac AC to DC circuits: 50Hz, 3,000Vac For all the three tests above, there should be no breakdown or flashover within 1min, with leakage current not bigger than 10mA 100,000hr Compliant with R5 requirement Cabinet 700 (W) × 700 (D) ×1800 (H) Internal space of 613 (W) × 570 (D) × 350 (H) battery compartment Forced ventilation ≤ 125 (excluding subrack and battery string) model cabinet Heat exchanger ≤ 180 (excluding subrack and battery string) model cabinet Air-condition model ≤ 175 (excluding subrack and battery string) cabinet Table 2 Spart part list Part Specification or model BOM Fan DC axial flow fan 32010191 Fan DC centrifugal fan 32010261 ECM1500 Outdoor Cabinet User Manual Appendix 2 Wiring Diagram 24 Appendix 2 Wiring Diagram AC Input N L 1 3 1 QFA1 2 Mains Input 4 9 10 11 12 FAN1 FAN2 FAN3 FAN4 W09 W01 Bottom cross control board door line W01 PE 4 MS PE Bar 2 L 3 4 N 19 XT 2 X1 5 6 FAN1 3 FAN2 FAN3 20 XT FAN4 PE 1 W09 2 N L 3 Bottom cross back door line W02 4 NOTE: W02_A for Europen standard socket. W02_B for American standard socket. W02_C for Chinese and British standard socket. 5 6 7 Blue Yellow Red Black solder Blue Yellow Red Black W05 Blue Yellow Red Black Blue Yellow Red Black solder Blue Yellow Red Black solder Blue Yellow Red Black W05 17 XT Blue Yellow Red Black solder Blue Yellow Red Black 18 XT W09 DC Input Bottom cross front door line 15 XT W05 16 XT 3 4 1 2 3 4 5 6 1 2 3 4 5 J11 6 U1 J12 7 U2 8 7 6 5 4 3 2 1 W03 2 1 J2 W07 J3 W08 J10 W06 Temperature sensor I 7-J1 W04 P344309U1 J6 1 2 3 J7 P345314X1 7-J3-7 7-J3-8 7-J3-1 7-J3-2 8-1 8-2 1 3 5 7 9 11 13 15 17 19 21 23 2 4 6 8 10 12 14 16 18 20 22 24 14 X3 W04 Temperature sensor I 6-J6 - W07 2 14-7 1 14-3 + 14-5 5 X2 14-1 PE BUS 1 13 T1 1 2 Door alarm 14-9 1 W07 J2 8 7 6 5 4 3 2 1 J3 1 2 6-J3 W06 6-J10 14-11 W06 7-J2 W06 Figure 1 Wiring diagram of forced ventilation model outdoor cabinet ECM1500 Outdoor Cabinet 8 MJ W08 8 7 6 5 4 3 2 1 W20 2 J1 User Manual Appendix 2 Wiring Diagram 25 AC Input N L 1 3 2 4 1 QFA1 Mains Input W09 W01 Bottom cross back door line W01 PE PE Bar 4 MS 1 2 L 3 4 N 5 6 Blue Blue 3 Black W03 1 PE 2 N W09 22 H1 2 X1 1 2 1 2 Red 19 XT Heater1 20 XT W09 15 XT W03 3 Black 21 KT1 4 W02 Blue solder Red 2 1 Black 18 XT Bottom cross front door line 23 H2 W03 Black L Black solder 17 XT Bottom cross control board door line 16 XT Heater2 5 10 FAN1 FAN2 FAN1 5 X2 + 1 2 - 11 12 FAN3 FAN4 4 FAN3 FAN4 Yellow Red Black FAN2 Blue Yellow Red Black FAN3 Blue Yellow Red Black FAN4 Blue Yellow Red Black solder FAN1* Blue Yellow Red Black solder FAN2* Blue Yellow Red Black solder FAN3* Blue Yellow Red Black solder FAN4* Blue Yellow Red Black FAN1 Blue - 14-9 FAN2 3 Door alarm PWM ALARM 5-4 5-2 - + PWM ALARM 5-4 5-2 - + PWM ALARM - + PWM ALARM 5-4 5-2 + 6-J15-2 1 W04 2 6-J15-1 8 MJ W08 14-11 W06 1 2 3 4 1 2 3 4 5 W05 1 2 3 4 5 5-4 1 2 1 2 3 6 U1 J5 W07 W08 ECCU11U1 J11 J13 W07 1 Figure 2 W07 2 J15 5-2 Temperature sensor I J8 J14 J4 1 2 3 4 13 T1 1 2 3 4 J3 1 2 Temperature sensor I J2 POWER 14-1 14-3 14-5 14-7 W05 W07 J1 W07 8 7 6 5 4 3 2 1 7 9 DC Input 6-J8 6 NOTE: W02_A for Europen standard socket. W02_B for American standard socket. W02_C for Chinese and British standard socket. 5-4 5-2 W04 Wiring diagram of heat exchanger model outdoor cabinet ECM1500 Outdoor Cabinet User Manual 6-J5-1 6-J5-2 6-J5-3 6-J5-4 8-1 8-2 1 3 5 7 9 11 13 15 17 19 21 23 2 4 6 8 10 12 14 16 18 20 22 24 14 X3 Appendix 2 Wiring Diagram 26 W05 AC Input 6-J6 Temperature sensor I N L 1 3 2 4 13 T1 1 QFA1 14 X3 Mains Input W06 W01 W17 W01 PE 4 MS PE Bar 7-J3-7 7-J3-8 19-J2-9 19-J2-10 8-1 8-2 W08 1 2 L 3 4 N 5 6 2 X1 Door alarm 3 14-9 1 PE 1 2 N 2 2 4 6 8 10 12 14 16 18 20 22 24 1 3 5 7 9 11 13 15 17 19 21 23 FAN2 Blue Yellow Red Black 3 8 MJ W17 10 FAN2 FAN1 L 4 5 6 NOTE: W02 W02_A for Europen standard socket. W02_B for American standard socket. W02_C for Chinese and British standard socket. 9 FAN1 solder 14-11 Blue Yellow Red Black solder W06 Blue Yellow Red Black Blue Yellow Red Black Temperature sensor II 19 XT 20 XT L N PE 1 2 3 4 5 J1 8 7 6 5 4 3 2 1 15 14 1312 11 10 9 J2 + 19 AC J3 W06 5 X2 1 2 - 19-J2-7 19-J2-13 3 7 U2 4 1 2 3 4 5 6 1 2 3 4 5 J11 W08 6 U1 J12 2 1 18 XT Air-condition J3 J10 J2 Temperature sensor I 7-J1 W07 1 2 J7 16 XT 1 2 3 J6 Bottom cross front door line J3 W07 7-J2 Wiring diagram of air-condition model outdoor cabinet ECM1500 Outdoor Cabinet User Manual J2 8 7 6 5 4 3 2 1 W08 6-J3 8 7 6 5 4 3 2 1 Figure 3 P345314X1 W05 P344309U1 W08 15 XT 8 7 6 5 4 3 2 1 W04 Bottom cross back door line 17 XT W08 Bottom cross control board door line 14-3 Cable from Air-condition W09 14-1 W03 19-J2-8 19-J2-14 DC Input 14-7 14-5 FAN2 6-J12-3 FAN1 6-J12-3 7 W06 W07 J1 1 2 6-J10 W07 Appendix 3 Schematic Diagram Appendix 3 Schematic Diagram L X1 QFA1 XS Door Alarm L N AC Input N to Dry Contact Terminal PE to PE bar Dry Contact Terminal Forced Ventilation Unit Over Temperature X2 C …… V- Fan A Climate unit fault C V+ - CONTROL + - -48V ALARM V+ CONTROL A + V- Fan DC Input ALARM 0V Door Alarm Spare FCUX FCU X3 Figure 4 L QFA1 X1 XS AC Input N Schematic diagram of forced ventilation model outdoor cabinet Door Alarm L N to Dry Contact Terminal PE to PE bar KT1 Dry Contact Terminal Heat Exchanger Unit A C - V- …… + CONTROL -48V ALARM V+ A Climate unit fault C V+ - DC Input External fan CONTROL V- + Internal fan ALARM X2 0V Over Temperature AC Heater Door Alarm Spare ECCU X3 Figure 5 Schematic diagram of heat exchanger model outdoor cabinet ECM1500 Outdoor Cabinet User Manual 27 28 Appendix 3 Schematic Diagram L QFA1 X1 N XS L N AC Input PE Door Alarm to Dry Contact Terminal to PE bar Air-condition Unit Dry Contact Terminal Over Temperature Alarm Fan contral Emergent Ventilation Unit X2 0V V+ Fan DC Input V- Climate unit fault Door Alarm Spare …… -48V FCU FCUX X3 Figure 6 Schematic diagram of air-condition model outdoor cabinet ECM1500 Outdoor Cabinet User Manual