Below is an example of duct sizing The load calculation indicates a heat gain of 28,000 BTUH, Therefore a 2-1/2 ton A/C unit is needed. The total system CFM is 1000 (for heating only, use the furnace cfm). The cfm of each branch is determined using the example shown for room C. The return trunk must handle 1000 cfm. The first section of the supply trunk must handle 1000 cfm while the second section will have to handle the remaining 517 cfm Room C 3000 btuh Heat Gain (obtain from room-by-room load calculation) 3000/28,000 X 1000 = 107 CFM C 107 cfm 125 cfm 88 cfm 1000 cfm AHU 1000 cfm 1000 cfm A return 517 cfm 68 cfm 110 cfm 110 cfm External static pressure of air handler @ 100 cfmwet coil Air filter registers Grille Total Available Static Pressure 50 cfm 123 cfm 84 cfm Measured length of duct (A to B ) = Equivalent lengths of turns and fittings between A and B = Total effective length = 135 cfm B 65 feet 190 feet 255 feet .5” w.c -.10” w.c. -.15” w.c. -.03” w.c. -.03” w.c. .19’ w.c. Friction Rate= .19 X 100 255 = .075” w.c. (Size all ducts at this friction rate) Use the Friction Rate (.075) to size all trunks and branches Return and first section of supply trunk will be 20” diameter (1000 cfm @ .075” w.c. Second section of supply trunk will be 16” diameter (517 cfm @.075’ w.c.) Outlet C will be 8” diameter (107 cfm @ .075” w.c.) Size the remaining outlets according to their CFM @ .075” w.c.