OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 Rev sh. 1 of 51 S1 SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS S1 30-03-2021 Final Issue R. RAVISANKAR N. P. PRADEEPA N. SAIPRASAD A2 16-03-2021 Issued for Review R. RAVISANKAR N. P. PRADEEPA N. SAIPRASAD A1 19-02-2021 Issued for Review R. RAVISANKAR N. P. PRADEEPA N. SAIPRASAD Rev. Date Description Prepared Checked Approved This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 2 of 51 S1 TABLE OF CONTENTS 1. INTRODUCTION PROJECT DETAILS 2. 2.2.1 2.2.2 2.3.1 2.3.2 2.3.3 GENERAL INFORMATION SCOPE OF THE DOCUMENT ABBREVIATIONS AND DEFINITIONS Definitions Abbreviations REFERENCE DOCUMENTS Codes Reference Literature Reference Project Documents 4 4 4 4 4 4 4 5 5 6 6 3. UNITS OF MEASUREMENT 6 4. PERMANENT LOADS 7 MATERIAL SELF WEIGHT (DL) BUILDINGS PERMANENT LOAD (DB) WEIGHT AND PRESSURE OF SOIL (DS) PRESTRESSING LOADS (P) DEAD LOAD ON ROOF (DD) 5. 5.1.1 5.1.2 5.1.3 5.1.4 5.1.5 5.1.6 5.1.7 5.2.1 5.2.2 5.2.3 5.2.4 5.2.5 5.2.6 5.3.1 5.3.2 5.3.3 6. 6.1.1 LIVE LOADS (L) LIVE LOADS IMPOSED FOR AN EXTENDED TIME Equipment, electrical & instrument cables and piping Loads (EE, EO) Buildings defined Imposed loads due to equipment (BE) Friction Loads (TLf) Weight and pressure of water/ other materials (BP) Vibrating Machinery Load (DYN) Shrinkage and Creep of concrete (CS) Differential settlings effects of Foundations (DS) LIVE LOADS IMPOSED FOR A SHORT TIME Equipment & piping Hydraulic test loads (ET) Maintenance load (ML) Occupancy Live Loads (LL) Buildings live loads (BL) Snow Load (S) Thermal Loads (T) LIVE LOADS IMPOSED FOR A VERY SHORT TIME Wind load (W) Impact and surge Loads (IL) Construction load (CL) RANDOM LOADS (A) EARTHQUAKE LOADS (E) Seismic force exerted by Soil BLAST LOADS FOR BUILDINGS (B) LOADS DUE TO FAILURE OF BEARING ELEMENT (C) 7 7 7 8 8 8 9 9 10 11 11 12 12 12 12 12 12 13 14 14 15 16 16 19 21 21 21 27 28 29 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS VEHICLE SHOCK LOADS (V) 7. LOADS ON ROADS AND PAVING LIGHT TRAFFIC CONCRETE PAVEMENT HEAVY TRAFFIC CONCRETE PAVEMENT 8. 8.1.1 8.1.2 1. 2. 2.1. 2.2. 2.3. 2.4. 2.5. LOAD COMBINATIONS ULS LOAD COMBINATIONS Steel structures Concrete Structures SLS LOADS COMBINATIONS LIQUID RETAINING STRUCTURES ANNEX 1 ANNEX 2 VERTICAL WALLS OF RECTANGULAR PLAN BUILDINGS FLAT ROOFS MONO PITCH ROOFS DUO PITCH ROOFS CANOPY ROOFS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 3 of 51 S1 29 30 30 31 32 33 34 34 36 36 38 39 39 41 43 45 47 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 4 of 51 S1 1. INTRODUCTION PROJECT DETAILS HAIFA CHEMICALS AMMONIA PLANT Project intends to build an Anhydrous Ammonia Plant having a nominal rated capacity of 300 MTPD based on 350 days of operation per year at End of Run (EOR) plant catalyst condition. Haldor Topsoe is the Technology licensor for the Ammonia unit. The Project includes also two 1500 MT (design two and erect only one) fully refrigerated ammonia storage tanks with auxiliary equipment located on another plot at the same site. Most of the Ammonia (70-75%) will be consumed continuously by the Nitric Acid production plants on site. About 20-25% will be transported out of site by road tankers. Surplus ammonia will be refrigerated and stored at atmospheric pressure. The Ammonia Plant (AP) utilities will be integrated to the extent practicable with the existing utilities infrastructure at Mishor Rotem CONTRACTOR’s SOW includes Basic and Detail engineering, Procurement of materials, Fabrication, Construction, Commissioning and Start-up of facilities at Haifa Chemicals site at Mishor Rotem, Southern Negev, Israel 2. GENERAL INFORMATION SCOPE OF THE DOCUMENT This specification defines general criteria and methods of calculation of design loads and load combinations for the design of civil works and structures for the HAIFA Chemical New Ammonia Plant within the existing Haifa Chemicals site at Mishor Rotem, Southern Negev, Israel. This specification is not applicable to Ammonia Storage Tanks. ABBREVIATIONS AND DEFINITIONS 2.2.1 Definitions PROJECT OWNER PMC LICENSOR CONTRACTOR SUB CONTRACTOR 2.2.2 HAIFA CHEMICALS AMMONIA PLANT HAIFA NEGEV TECHNOLOGIES LTD ADYR CONSTRUCTIONS HALDOR TOPSOE SERVIZI ENERGIA ITALIA (SEI) – Saipem SPA GALIL ENGINEERING Abbreviations Nil This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 5 of 51 S1 REFERENCE DOCUMENTS The following documents are to be considered as integral part of this specification, as well as their addenda and reference documents. Latest edition valid at date of contract award will have to be considered. If local codes requirements are more stringent than the ones here specified, local codes shall prevail 2.3.1 Codes • • • • SI 109 SI 412 SI 413 SI 413 part 2 • SI 413 part 2.1 • SI 413 part 2.2 • SI 413 part 2.3 • SI 413 part 2.4 • • SI 414 SI 931 part 1 Weight of Materials and parts of Buildings Loads on Structures: Characteristic Loads Design provisions for earthquake resistance of buildings Design provisions for earthquake resistance: Non-building structures- general Design provisions for earthquake resistance: steel storage racks systems Design provisions for earthquake resistance: Non-building structures- tanks on the ground for liquid containing Design provisions for earthquake resistance: Non building structures – elevated tanks and vessels for liquids and gases Design provisions for earthquake resistance: Non building structures – Above ground pipelines in industrial facilities Characteristic Loads on Buildings: Wind Loads Fire resistance tests- Elements of building construction- General requirements For foundations and concrete structures: • • • • • • SI 466 Part 1 SI 466 Part 2 SI 466 Part 3 SI 466 Part 4 SI 940 ACI 351.3R Concrete Code: General Principles Concrete Code: Reinforced and Unreinforced Concrete Structures Concrete Code: Prestressed Concrete Concrete Code: Precast Concrete Elements and Structures Foundation for Buildings Foundations for dynamic equipment. Codes for steel structures: • • • • • • • SI 1225 Part 1: SI 1225 Part 4: SI 755: SI 1142: IS 14122 part 4: IS 2279: EN 10025 Steel Structure Code - general Steel Structure Code: design for earthquake resistance Finishing material (non-flammable) Stairs railing Fixed ladders Resistance to slipping of the walking plane Hot rolled products of non-alloys structural steel This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 Rev sh. 6 of 51 S1 Additional International Codes for the design of foundations for vibrating machinery: • • BS CP 2012 Part1 ISO 10816 • ISO 1940/1 2.3.2 Code of practice for foundations of machinery. Mechanical vibration – Evaluation of machine vibration by measurements on non – rotating parts Mechanical vibration – Balance quality requirements of rigid rotors – Determination of permissible residual unbalance Reference Literature D.D. Barkan Dynamic of bases and foundations; Mc Graw Hill 1962 Richard –Hall -Woods Vibrations of soils and foundations; Prentice Hall; 1970 J.E. Bowles Foundation analysis and design; Mc Graw Hill; Fifth Ed. ASCE Petroc. Committee Wind loads for Petrochemical Facilities ASCE Petroc. Committee Design of Blast Resistant Buildings in Petrochemical Facilities 2.3.3 Reference Project Documents Job Specifications: i) Specification for design Criteria for concrete structure and foundations H00-CA-E-11001 ii) Specification for design Criteria for foundations for vibrating machinery H00-CA-E-11002 iii) Specification for design Criteria for steel Structures H00-CA-E-11601 iv) Ammonia Plant – Rotem Plain Design Response Spectra 2020.09.15 1229 Ammonia Plant_PSHA-T_rev1 v) Basic Engineering Design Data (BEDD) H00-ZA-E-09201 3. UNITS OF MEASUREMENT The SI units will be used in design, in particular: Length m, mm Mass kg Concentrated force, weight N, kN Linear distributed force kN/m Surface distributed force kN/m2 Specific weight kN/m3 Pressure, stress N/mm2 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 7 of 51 S1 4. PERMANENT LOADS The following loads shall be considered as permanent loadings in the loading combinations to be considered for the design as specified in paragraph 8 Material Self Weight Buildings Weight and Pressure of SOIL Prestressing forces Dead Load on Roofs (DL) (BD) (DS) (P) (DD) MATERIAL SELF WEIGHT (DL) This permanent load is the self-weight of structures and the weight of all materials permanently fastened thereto or supported thereby, such as fireproofing, insulations and walkways The specific gravity of materials shall be assumed according to SI 109; for soil and basic construction materials, the following values shall be assumed, unless a more appropriate evaluation is made: • • • • • • • • Density of soil Density of reinforced concrete Density of plain concrete Density of structural steel Handrail Grating Insulation Roof 18.00 kN/m³ 25.00 kN/m³ 24.00 kN/m³ 78.50 kN/m³ 0.20 kN/m 0.33 kN/m² Based on piping spec. kN/m³ Based on Vendor spec BUILDINGS PERMANENT LOAD (DB) In addition to the weight of the building structure determined by its nominal dimensions and bulk densities, the load of partitions shall be considered as their actual weight. When the partitions’ weight is not greater than 4.0kN/m, the load may be calculated as an alternative distributed load of: - 0.75kN/m2 1.5 kN/m2 for partitions having a weight not greater than 2.0 kN/m for partitions having a weight not greater than 4.0 kN/m If the load of the floor is designed to bear a live load of 5.0 kN/m2 or greater, or partitions have a weight not greater than 1.0 kN/m, there is no need to take into account the partitions weight. WEIGHT AND PRESSURE OF SOIL (DS) The weight of soil above foundations and the earth pressure on walls will be considered as permanent loads determined as per SI 940. This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 8 of 51 S1 Calculations for walls will be carried out using the following coefficient formulae as applicable: ϕ = (from the soil report) angle of internal friction Ka= tg2 (45-ϕ/2) active pressure coefficient (for flat fill and vertical surface) Kp = tg2 (45+ϕ/2) passive pressure coefficient (for flat fill and vertical surface) K0 = at rest pressure coefficient for flat surfaces 0.5 for loose sand 0.45 for dense sand 0.6 for silt 0.7-1.0 for clay For cantilever retaining walls earth pressure shall be evaluated adopting the active earth pressure coefficient Ka. For pits, concrete basins, and other buried structures, which can be considered as rigid structures, the earth pressure coefficient K0 shall be considered. From the Geotechnical report, ground water table is not encountered in the bore holes. PRESTRESSING LOADS (P) The prestressing force values shall be considered as permanent loads determined as per SI 466 Part 3. DEAD LOAD ON ROOF (DD) Light- weight Roofs shall be capable to carry an additional dead load of 0.5 kN/m, to simulate an accumulated dust layer 5. LIVE LOADS (L) The following loads shall be considered as variable loads in the loading combinations to be considered for the design as specified in Section 8 of this document. Live loads imposed for an extended time • • • • • • Equipment/piping weight in Erection Equipment/piping weight in Operation Building Defined Imposed Load Friction thermal load Vibrating Machinery loads Weight and pressure of water and other fluids (EE) (EO) (BE) (TLf) (DYN) (BP) This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. Contractor Job No OWNER HAIFA NEGEV TECHNOLOGIES LTD 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS • • Shrinkage and Creep of materials Differential settlings effects of Foundations H00 H00-CA-E-11600 Rev sh. 9 of 51 S1 (CS) (DS) Live loads imposed for a short time • • • • • • Occupancy Imposed Loads Buildings Variable Imposed Loads Snow Loads Thermal loads due to site temperature variations Maintenance Load Equipment/piping weight in Test (LL) (BL) (S) (T) (ML) (ET) Live loads imposed for a very short time • • • Wind Load Impact and surge Loads Construction Load (W) (IL) (CL) LIVE LOADS IMPOSED FOR AN EXTENDED TIME 5.1.1 Equipment, electrical & instrument cables and piping Loads (EE, EO) Equipment/cables/piping erection (EE) This load includes the weight of piping and equipment e.g., columns, vessels, exchangers, tanks in its empty condition. Unless otherwise stated by piping department, the process piping empty weight shall be assumed as the 40% of the piping weight considered full of water. During the erection stage, a load equal to the 10% of the operation weight can be assumed for the self-weight of the empty cable trays. Self-weight of equipment, pipes, cable trays etc. shall be considered as live load (and not as a dead load). Equipment/cables/piping operation (EO) This load includes the weight of piping and equipment (comprising platforms and ladders attached to the equipment itself, fireproofing, insulation etc), solids and fluids normally inside the equipment/piping during operation This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 Rev sh. 10 of 51 S1 Unless otherwise stated by piping department, the weight of piping system on pipe racks may be assumed equal to 1.5 kN/m2 for pipes not larger than 12” in diameter. The weight of larger diameter pipes shall be specifically considered. Unless otherwise stated, for cable trays weight shall be considered as follows. For electrical trays 300mm wide tray = 100 kg/m per layer. 600mm wide tray = 150 kg/m for layer. For Instrumentation trays 300mm wide tray = 90 kg/m per layer. 600mm wide tray = 170 kg/m for layer. During detailed design, the piping loads and cable trays loads will be re- assessed by the piping designer and the design will be modified if required. 5.1.2 Buildings defined Imposed loads due to equipment (BE) For buildings consider the following Defined imposed Loads: a) Control Room/Sub-station Unless actual equipment (switchgears, cabinets, UPS, consoles and batteries) load is known, the following loads shall be considered as a minimum for design: main structure (beams, columns, and foundations) - 6.00 kN/m² for vertical load evaluation - 6.00 kN/m² for horizontal load (earthquake) evaluation. such loads shall be uniformly distributed over the entire room occupied by equipment concrete slab supporting the equipment - 10.00 kN/m² uniformly distributed over the entire slab However as soon as the actual applied loads are known (at a further stage of the project), floor slabs shall be checked through to ensure that actual loads are not greater than the above considered ones. b) HVAC system Actual load due to roof-mounted equipment for HVAC system shall be considered for all buildings. However, if the actual loads are not available, the following loads shall be considered as uniformly distributed over the HVAC equipment installation area: - 5.00 kN/m² to evaluate vertical loads (IS 412 table 1 item 9.3) This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS 5.1.3 Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 11 of 51 S1 5.00 kN/m² to evaluate horizontal loads (earthquake). Friction Loads (TLf) Friction Loads acting on structures and foundations are thermal loads caused by the expansion/contraction of equipments or pipes. To calculate thermal loads caused by equipment and pipes, the following friction coefficient f shall be used: • • • • • Teflon to Teflon Teflon to stainless steel Steel to steel Steel to concrete Concrete to soil f = 0.08 f = 0.10 f = 0.30 f = 0.45 f = 0.4 unless otherwise stated in the “Geotechnical Report” Unless otherwise stated by piping department, for pipe racks supporting multiple pipes (more than 3 pipes per layer) of diameters less than 12”, an average friction coefficient of 0.15 shall be considered to estimate the longitudinal thermal friction load to be applied to local supporting beams only. However, an estimated thermal friction loads equal to 5% of the total piping weight in both horizontal directions shall be accumulated and carried into pipe rack struts, columns, braced anchor frames and foundations. Such thermal friction loads shall not be combined with random loads. Friction loads include also pipe anchor and guide loads produced from thermal expansion and internal pressure loads. Pipe anchor and guide loads only shall be combined with other random loads, based on specific information provided by the piping designer. Loads on special pipe supports (fix points, stoppers, guides etc.) on pipe racks and pipe supports shall be considered based on the piping stress analysis. The value of these loads is generally known only on the late stages of the design. The design of the pipe rack/ pipe support will be checked once these loads are calculated by the piping designer and the design will be updated as required. 5.1.4 Weight and pressure of water/ other materials (BP) This load includes ground water pressure or pressure of bulk materials acting against structures, retaining walls and foundations. Calculations for walls will be carried, as defined in 4.3. considering the appropriate densities and internal friction coefficient as per material contained. ϕ = (From the soil report) K0 = 1-Sinϕ Angle of internal friction (At rest pressure coefficient) This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 12 of 51 S1 For cantilever retaining walls pressure shall be evaluated adopting the active earth pressure coefficient Ka. For pits, concrete basins and other buried structures, which can be considered as rigid structures, the earth pressure coefficient at rest K0 shall be considered. 5.1.5 Vibrating Machinery Load (DYN) Vibration loads are those forces and moments caused by rotating or reciprocating machinery such as compressors, turbines, fan, blowers, and pumps. The evaluation of such loads shall be done on the base of Manufacturer's documents and as indicated in project specification H00-CA-E-11002. 5.1.6 Shrinkage and Creep of concrete (CS) These effects shall be determined as per SI 466 part 1, App. B (Amendment 4), or EN-1992. 5.1.7 Differential settlings effects of Foundations (DS) These effects shall be determined as per SI 940 taking into consideration the bedding module of the soil and its variation in various zones of the structure. In determining the forces resulting from such effects, stages of structure erection shall be taken into consideration. LIVE LOADS IMPOSED FOR A SHORT TIME 5.2.1 Equipment & piping Hydraulic test loads (ET) This test load is the weight of the equipment/piping including the weight of water necessary to perform the hydraulic test. 5.2.2 Maintenance load (ML) Maintenance loads are temporary forces due to dismantling, repair or painting of equipment. Exchangers bundle pulling Structures and foundations supporting heat exchangers shall be designed to withstand a longitudinal force applied at the centroid of the tube bundle. Such force shall be supported by the fixed saddle only, and it shall be equal to the weight of the bundle (50% of the bundle weight when using pulling screws) or to 10 kN, whichever is bigger. In case of stacked exchangers, it shall be assumed that the bundle pulling of exchangers shall not be contemporary. This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS 5.2.3 Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 13 of 51 S1 Occupancy Live Loads (LL) Live loads shall be the maximum loads expected by the intended use or occupancy and consists of the following movable loads: • • • • persons, portable machinery, tools and, for buildings, furniture, business machines and archive materials. materials temporarily stored during maintenance such as exchanger parts, pipes and fittings, valves. materials normally stored during operation such as tools, maintenance equipment, catalysts and chemicals. passing or staying vehicles, trucks, and operating machines. Live loads shall be uniformly distributed over the horizontal projection of the specified areas and have the minimum values specified SI 412, in particular or in addition to it for equipment structures the following values shall be considered • • • • • • • • • • • Storage areas: to be determined considering the intended use of the area, but never less than 6.00 kN/m2 (2.00 kN/m2 in erection load combinations) Catwalks and landings 2.50 kN/m2 as per SI 412 Table 1 (S.No.13.1.1) Operating and maintenance areas 5.00 kN/m2 as per SI 412 Table 1 (S.No.9.3) Operating equipment platforms 5.00 kN/m2 as per SI 412 Table 1 (S.No.9.3) Stairs, walks and access platforms 5.00 kN/m2 as per SI 412 Table 1 (S.No.13.5) Ladders 1.5 kN (to be considered for local checks only) as per SI 14122 Part 4 Handrails 0.75 kN/m (linear load) applied on the upper rail in each direction (Mid rail shall be designed to support 70% of this load). There are infilling panels as part of the handrail's structure, the linear load shall be combined with 50% of the design wind forces as per SI 1142. Flat roof or sloped up to 10% 1,5 kN/m2 as per SI 412 Table 1 (S.No.12.3) Non accessible roof (lightweight sloped roofs) 0.5 kN/m2 Roofs whose slope exceeds 10% 0.75 kN/m2 Roofs used for roofing footpaths 5.0 kN/m2 as per SI 412 Table 1 (S.No.12.4) In addition to the uniformly distributed live loads, all beams forming part of the main framing system or supporting major floors shall be designed for a concentrated live load of 10.0 kN at their mid-span to allow for construction/erection loads and possible pipes and cable tray loads. This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 14 of 51 S1 The 10.0kN loads shall be considered for the individual beam design but will not be considered as having cumulative effect for column foundation design. For equipment supporting structures only, the following considerations on live loads apply: - In maintenance and erection conditions, live loads specified in this paragraph acting on work and on pedestrian areas shall be combined with the erection weight of the equipment and be applied to a single storey at a time in the event of multi storey structures. -In operating conditions, no reduction in live loads shall be considered for roof and floor: 5.2.4 Buildings live loads (BL) For buildings consider the following live loads: a) Offices for General Use 3.0 kN/m2 b) Offices with Fixed Computers 3.5 kN/m2 c) Analyzer Room 3.0 kN/m2 as per SI 412 Table 1 (S.No.8.1) d) Control Room/Sub-station • offices and corridors • switchgears, cabinets, UPS, consoles and battery rooms: 3 kN/m2 - if equipment layout is known consider a uniformly distributed load of 3kN/m2 applied over the area not covered by equipment - otherwise consider a uniform distributed load of 15 kN/m2 applied over the entire equipment room e) Access balconies to cabinet, UPS, console and switchboard room, shall be designed for a uniformly distributed load of 10.00 kN/m² acting over the balcony area. f) Stairs shall be designed assuming a live load of 5.00 kN/m². 5.2.5 Snow Load (S) Snow load shall be evaluated according to SI 412 Section 4 assuming: Characteristic snow load at ground level S0 = 0.20 kN/m² Exposure factor Ce = 1.0 Type of Structure factor (roofs having a self-weight<1kN/m2 Cc = 1.2 Essential Structure factor Ci = 1.0 μ as per SI 412 Annex A – refer to Annex 1 for common cases Sr=S0*μ*Ce*Cc*Ci This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS 5.2.6 Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 15 of 51 S1 Thermal Loads (T) Thermal loads are those forces caused by site temperature variations. Expansion joint should be foreseen at a distance not longer than 40m in order to limit the effects of temperature variations. According to SI 412 Section 5.2 effects of thermal variations on structures will be accounted for considering the following values for ∆T as per Table 10 of SI 412 (4) If the structure or part of it is not exposed to radiation, the differential temperature given in the table may be reduced, for erection in the winter season, by 10°C. (5) For the case of a dark exterior face (gray shade of bare concrete, etc), the differential temperature given in the table shall be increased by 10°C Since the season & length of erection/installation cannot be determined in advance with certainty. The plant structures shall be designed for the two extreme cases of: i) positive temperature change for the structure erected in winter, including the effect of solar radiation ii) negative temperature change for structure erected in summer. a) Design thermal conditions for reinforced concrete structures Design thermal expansion variation ∆T=50+10(5) =60°C This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. Contractor Job No OWNER HAIFA NEGEV TECHNOLOGIES LTD 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 Rev sh. 16 of 51 S1 ∆T=-20.0°C Design thermal contraction variation b) Design thermal conditions for steel structures Design thermal expansion variation Design thermal contraction variation ∆T=50+20=70.0°C ∆T=-20.0°C The linear deformations due to the temperature variation shall be evaluated considering a thermal expansion coefficient of: 1.2x10-5 °C-1 for steel structures 1.0x10-5 °C-1 for concrete structures LIVE LOADS IMPOSED FOR A VERY SHORT TIME 5.3.1 Wind load (W) The wind load shall be evaluated in accordance with IS 414, considering the following parameters: Fundamental value of the basic wind velocity Terrain category vb,0 = 30 m/s II According to SI 414, the wind force acting on a structure or structural element of reference area Aref is: Wind load Where: directional factor Season factor Orography factor Turbulence factor Fw=qb*ce(z)*cs*cd*cf*Aref qb=1/2*ρ∗vb2= vb2/1.6 vb=cdir*cseason*vb,0 ce(z)= cr2(z)*co2(z)*(1+7*Iv(z)) Iv(z)=kt/(co(z)*ln(z/z0)) cr=kr*ln(z/z0) cf= force coefficient cdir=1 cseason=1 co(z)=1 kt=1 Cs*Cd=1 For terrain category II zo zmin kr 0.05 2 0.19 Hence: This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 17 of 51 z cr Iv(z) qb*ce(z) (N/m2) 5 0,875 0,217 1085 10 1,007 0,189 1323 20 1,138 0,167 1580 30 1,215 0,156 1740 40 1,270 0,150 1857 50 1,312 0,145 1950 100 1,444 0,132 2253 S1 For horizontal vessels and exchangers, the projected area Aref to be considered in total wind force calculation shall be increased to allow for platforms, insulation and piping. Surface increase factors are shown in the following table: Vessel Diameter (m) Increase Factor 0.50 – 1.00 1.6 1.01 – 1.50 1.4 1.51 – 2.00 1.3 2.01 – 3.00 1.2 > 3.00 1.1 Spherical 1.1 For pipe racks in addition to the wind acting on the structure the action on pipe tracks shall be evaluated considering (ref ASCE Petroc. Committee - Wind loads for Petrochemical Facilities): a) For wind blowing in the transversal direction, the wind load on piping shall be calculated considering a piping tributary area as follows: A = L (D +0.1W) b) For wind blowing in the longitudinal direction, the wind load on piping shall be calculated considering a piping tributary area as follows: A = L x0.05xW Where A = tributary area L = pipe rack frame spacing This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 Rev sh. 18 of 51 S1 W = pipe rack width D= max diameter as per information on Single line Drawings from piping ptm For cable tray layer the same criteria adopted in a) and b) shall be followed substituting ‘D’ with ‘h’ (height of cable tray) and ‘W’ as width of cable trays instead of width of pipe-rack. As minimum, the following force coefficients (cf) shall be used for the evaluation of wind load on single elements: • • • • • structural steel profiles cable trays pipes air coolers concrete sections 1.8 1.8 0.8 1.4 1.8 On Piperack frames shielding factors shall not be applied to the leeward faces. For determining Wind pressure on surfaces consider the following Wind pressure acting on the external surfaces of a structure, we : we = qb*ce(ze)* cpe where: ze is the reference height for the external pressure given in IS 414 (extract can be found in Annex 2) cpe is the pressure coefficient for the external pressure, ref Annex 2 for common cases. Wind pressure acting on the internal surfaces of a structure, wi , should be obtained from wi = qb*ce(zi)* cpi where: zi is the reference height for the internal pressure given in IS 414 (extract can be found in Annex 2) This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 19 of 51 S1 cpi is the pressure coefficient for the internal pressure, ref Annex 2 for common cases. The wind force, Fw acting on a structure or a structural element may be determined by vectorial summation of the forces Fw,e, Fw,i and Ffr calculated from the external and internal pressures and the frictional forces resulting from the friction of the wind parallel to the external surfaces, calculated using the following Expression: Ffr=qb*ce(z)*cfr*Afr cfr is the friction coefficient (ref to values in below table for roof, walls and parapets) Afr is the area of external surface parallel to the wind 5.3.2 Impact and surge Loads (IL) Impact loads are forces caused by moving objects, such as bridge-cranes and monorails, on their supporting structures, on their runways or where they place the lifted loads. For structures supporting live loads, which induce impact, the design live loads shall be increased for the impact effect. The increase of loads due to impact shall be according to SI 412 table 11, and as a minimum the following shall be considered: Horizontal loads shall be taken from the manufacturer's documents, or, if not available, from SI 412, section 5.6. The horizontal loads act simultaneously with the vertical loads. The most unfavourable location of the loads with respect to the supporting system shall be considered. Dynamic amplification factors shall be taken from SI 412, section 5.6. This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS STRUCTURE Bridge Crane Runways (Electrically operated cranes) LOAD DIRECTION a) Vertical UNIT Doc. No Rev sh. 20 of 51 STATIC LOAD S1 DYNAMIC INCREASE b) Horizontal load applied at top of runway, has a value = 15% of the vertical load b) NA c) Horizontal load applied at top of runway, has a value = 10% of the maximum vertical static loads of the crane wheels ie. rated capacity of the crane and the weight of the hoist and trolley. The lateral force shall be assumed to act horizontally at the traction surface of the runway beam, in either direction perpendicular to the beam, and shall be distributed with due regard to the lateral stiffness of the runway beam and supporting structures. c) NA a) Vertical a) Maximum wheel load b) Horizontal Longitudinal b) Load applied at top of runway= 15% of the max vertical wheel load a) 25% of max wheel load b) NA a) Vertical a) Maximum wheel load b) Horizontal Longitudinal b) Horizontal Longitudinal load = 10% of lifted load c) Horizontal Transversal c) Horizontal Transversal load= 20% of lifted load b) Horizontal Longitudinal Elevators Bridge Crane Runways (Manually operated cranes) H00 H00-CA-E-11600 a) 25% of max wheel load Transversal Davits (Electrically operated) 219625 a) Maximum wheel load c) Horizontal Monorails runway (Electrically operated) Contractor Job No a) 25% of max wheel load b) NA c) NA 100%. a) Vertical a) maximum wheel load a) 10% of max wheel load b) Horizontal Longitudinal b) Load applied at top of runway= 15% of the b) NA vertical load This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS c) Horizontal Transversal Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 21 of 51 c) loads resulting from motion and incline S1 c) NA forces=5% of the maximum vertical static loads of the crane wheels ie. rated capacity of the crane and the weight of the hoist and trolley. The lateral force shall be assumed to act horizontally at the traction surface of the runway beam, in either direction perpendicular to the beam, and shall be distributed with due regard to the lateral stiffness of the runway beam and supporting structures. Each of the horizontal loads is acting simultaneously with the vertical loads. Piping surge loads shall be considered as impact loads in load combinations 5.3.3 Construction load (CL) Construction loads are temporary forces due to: lifting, erection or installation of precast members, structures, equipment. 6. RANDOM LOADS (A) EARTHQUAKE LOADS (E) The seismic load shall be defined in accordance with IS 413 considering the following PSHA spectra for the Ammonia plant (Group I data. For Ammonia Storage Area, PSHA spectra (Group II) shall be considered. Ref: 2020.09.15 1229_Amonia Plant_PSHA-T_rev1(A. Shiran, 2020-09-08) This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 22 of 51 S1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 23 of 51 S1 According to SI 413 Importance factor shall be considered in design as shown below: i) Spectra referring to 2% exceedance in 50 Years multiplied by an Importance Factor of 1.0 Class A & Class C structures: All the plant's structure will be designed as class A structures. PSHA spectra shall be used for seismic design as it is the governing case. Ammonia Plan (Group I)t T0=0.06s≤T≤0.32s Sa=SDS=1.04g 0.32s<T≤TL=11s (IS 413 App h) Sa=SD1/T=0.33g/T Ammonia Storage Plant (Group II) T0=0.04s≤T≤0.21s Sa=SDS=1.05g 0.21s<T≤TL=11s (IS 413 App h) Sa=SD1/T=0.22g/T This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 24 of 51 S1 Total Horizontal FH and vertical FV resultant design loads are: FH= Cd*W with Cd=Sa*I/K FV= 2/3 FH Where: Cd= Seismic design factor Sa= Design Spectral Response acceleration I=1.0 or 1.4, as required by the code, considering the frequency of the design earthquake and the structural category. K = Force reduction Factor (see below tables for common cases) W= total weight in force units=∑Wi with Wi total weight of Story “i” Wi = Gi+kq*(Qi+Ai*qi) M = Wi/g Gi= characteristic dead load on story “i” Qi=characteristic live load, concentrated or linear qi= characteristic distributed load over an area Ai kq= live load frequency factor – to be applied to the reduced live loads as per par. 5.2.3 for multistory structures M=seismic participating mass in a particular mode shape g=9.81 m/s2 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 25 of 51 S1 The effect of Wi (multiplied by the partial load factor γf=1 shall always be considered in seismic calculations Type of Structure Frequency Factor kq Roofs with no access and for pipe racks top elevation platform (1) 0 Dwellings, office buildings and operating floors in process structures 0.2 Auditoriums, parking and maintenance floors in process structures 0.3 Warehouses, libraries archives 0.5 Silo and reservoirs 1.0 (1) Ref to Clarification nr. 76 with HAIFA Chemicals during BIDDING STAGE “Definition of Kq factor for the different type of buildings/structures should follow the rational of actual imposed load during an earthquake. As pipe racks are not occupied on a daily basis and access to pipe racks is for maintenance only, we can assume Kq=0 as for roofs with no direct access (roofs with no direct access usually include HVAC systems to be maintained and the access is possible for maintenance technicians - same as pipe racks)” For regular structures, the horizontal components of the seismic action shall be taken to act independently in the two orthogonal directions. This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 UNIT Doc. No PLANT LOCATION: ISRAEL Rev sh. 26 of 51 S1 Force Reduction factors K for horizontal seismic action Steel Structures and Pipe Racks (SI 1225 Part 4) Moment resisting frames LOW ductility MEDIUM ductility 1.5 1.5 Frame with concentric bracings: 4 Diagonal bracings 1.5 4 2 4 V-bracings Frame with eccentric bracings’ 1.5 Reinforced concrete structures (table 5 SI 413) LOW ductility MEDIUM ductility Moment resisting Frames 1.5 3.5 Braced frames 1.5 3 Shear walls and dual systems 1.5 3 Special Structures (Table 7 SI 413) Reinforced Concrete chimneys and silos cast in situ with walls starting from foundation level, cooling towers, signs, shelves in warehouses 3.5 Chimneys and silos (not mentioned above). Vertical industrial production facilities, bunkers, antenna towers (cantilevered or anchored by cables), and all other self-supported structures not mentioned 2.8 Tanks, water towers, cantilevered structures with concentrated mass at their top, entertainment facilities and monuments 2 OTHER EQUIPMENT Skirt Supported vertical Vessels (SI 413 part 2.3 table 2.1) 2 Horizontal saddle supported vessels and leg mounted vertical (SI 413 part 2.3 table 2.1) 3 Steel tanks or fibre- reinforced plastic tanks, anchored (SI 413 part 2.2 table 3.2)- 3 Steel tanks or fibre- reinforced plastic tanks, un-anchored (SI 413 part 2.2 table 3.2) 2.5 Reinforced concrete tanks or pre- stressed concrete tanks, fixed support (SI 413 part 2.2 table 3.2) 2 Reinforced concrete tanks or pre- stressed concrete tanks, hinged non- sliding support (SI 413 part 2.2 table 3.2) 3 Other materials tanks (SI 413 part 2.2 table 3.2) 1,5 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 H00 H00-CA-E-11600 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Rev sh. 27 of 51 S1 If the structure is non-regular in elevation the above listed K values should be reduced by 20 % For matters not specifically addressed in Israeli Codes, ASCE “Guidelines for Seismic Evaluation and Design of Petrochemical Facilities” shall be used as reference. Seismic force exerted by liquids with free surface shall be evaluated according to IS413 part 2.2design provisions for earthquake resistance- non building structures- tanks on the ground for liquid containing' or API 650 - Appendix E for circular steel tanks, and Housner’s theory for other retaining structures, assuming the design response spectra set in API 650 - Appendix “E”. 6.1.1 Seismic force exerted by Soil The thrust of soil against retaining structures shall also consider the effect of earthquake, as per requirements of IS 413 Chapter F In seismic design of retaining walls which are free to displace in the lateral direction (eg cantilever walls, gravity walls etc), and the base of the wall is above the water table, the active force EAE is determined as: EAE=γ*H2*KAE/2 𝐾𝐾𝐴𝐴𝐴𝐴 = 𝑐𝑐𝑐𝑐𝑐𝑐 2 (ϕ − β − θ) 2 𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐 ∙ 𝑐𝑐𝑐𝑐𝑐𝑐 2 𝛽𝛽 ∙ cos(𝛿𝛿 + 𝛽𝛽 + 𝜃𝜃) ∙ �1 − � SI 413, formula 85 sin(ϕ + 𝛿𝛿) ∙ sin(ϕ − 𝜃𝜃 − 𝑖𝑖) � cos(𝛿𝛿 + 𝛽𝛽 + 𝜃𝜃) ∙ cos(𝑖𝑖 − 𝛽𝛽) θ=arctan kh kh/PGA=0.86 (PGA/d)1/4≤1.5 2 SI 413, formula 86 SI 413, formula 87 SI 413, formula 88 Where γ= unsaturated unit soil weight H=height of retaining wall above its base φ= soil internal friction angle δ= friction angle between wall and soil backfill β= retaining wall inclination relative to vertical axis i=slope of soil behind retaining wall KAE= active earth pressure coefficient on retaining wall under earthquake conditions kh= Lateral seismic pressure coefficient d=allowable horizontal displacement at the top of the retaining wall in cm = 2cm PGA= Peak Ground Acceleration as per PSHA spectra The passive force at the base of the retaining wall shall be determined as: EPE=γ*Hp2*KPE/2 SI 413, formula 91 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS 𝐾𝐾𝑃𝑃𝑃𝑃 = 𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐 ∙ 𝑐𝑐𝑐𝑐𝑐𝑐 2 𝛽𝛽 H00 H00-CA-E-11600 UNIT Doc. No PLANT LOCATION: ISRAEL Rev sh. 28 of 51 S1 𝑐𝑐𝑐𝑐𝑐𝑐 2 (ϕ + β − θ) sin(ϕ + 𝛿𝛿) ∙ sin(ϕ − 𝜃𝜃 + 𝑖𝑖) ∙ cos(𝛿𝛿 − 𝛽𝛽 + 𝜃𝜃) ∙ �1 − � � cos(𝛿𝛿 − 𝛽𝛽 + 𝜃𝜃) ∙ cos(𝑖𝑖 + 𝛽𝛽) 2 2 SI 413, formula 92 θ=arctan kh kh=1.5 PGA SI 413, formula 87 SI 413, formula 88 Where Hp= part of the retaining wall height, subjected to passive force. The required weight of the wall in order to prevent sliding shall be determined as: 𝑊𝑊𝑊𝑊 = 1.1 ∙ cos(𝛿𝛿 + 𝛽𝛽) − sin(𝛿𝛿 + 𝛽𝛽) ∙ tan ϕ𝑏𝑏 tan ϕ𝑏𝑏 − tan 𝜑𝜑 SI 413, formula 90 Where: 1.1= Safety Factor against sliding, in the event of an earthquake φ b= friction angle between the base of the retaining wall and the soil E= maximum active force acting on the retaining wall and the soil BLAST LOADS FOR BUILDINGS (B) The design of buildings subjected to blast loadings shall be carried out in accordance with ASCE manual “Design of Blast resistant Buildings in Petrochemical Facilities”. The value of blast peak side-on overpressure and time duration shall be in accordance with Preliminary building risk assessment. This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 Rev sh. 29 of 51 S1 Below table summarizes preliminary values that shall be confirmed @ a later stage of the project: Building SSE CCR / ADMIN WORKSHOP Side-on Overpressure (HOLD) (bar-g) 0.35 0.14 0.14 (psig) 5 2 2 Positive phase duration (HOLD) (ms) 100 100 100 LOADS DUE TO FAILURE OF BEARING ELEMENT (C) For reinforced framed structures, provisions in IS 466 section 2.4 and Appendix A shall be complied with to avoid chain collapse due to the collapse of a single element or few near elements, due to explosion of a vessel, gas tank, explosion due to car hit, extreme natural force or sabotage. SI 466 calls to install means to restrain or avoid the spreading of the damage beyond the damaged area by structural continuity and ductility and avoiding sudden weakening of main elements. This should be achieved by either: • • • Reinforcement of the structural system by adding lengthwise and crosswise reinforced concrete element (in masonry walls) Design of an alternative structural system In case these options are not applicable- reinforcement of the structural elements. Provisions for these means are detailed in SI 466 Appendix A. As an alternative, in case the details are not applicable and there is no alternative structural system, the relevant components should be designed to withstand a load of 34 kN/m2 at any direction (simulation of explosion of a domestic gas container). No requirement for avoiding chain collapse due to failure of a bearing element needs be considered for steel structures. VEHICLE SHOCK LOADS (V) The columns of a structure, located close to a traffic lane and exposed to damage from motor vehicles, shall be protected from possible impact as follows, unless it is proven by a calculation that the structure will remain stable even without the column: • Columns exposed to the loads of forklifts shall be calculated for a horizontal design force of impact of 40kN, applied at a height of 0.5m above the floor • On roads where the speed limit is limited to 60 Km/h, the column shall be calculated for a horizontal design force of impact of 60kN, applied at a height of 1m above the ground next to the column This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 30 of 51 S1 These requirements do not have to be considered when protective measures are taken in form of fences and guardrails that prevent direct impact. Such fences and guardrails shall withstand the above design loads. 7. LOADS ON ROADS AND PAVING LIGHT TRAFFIC CONCRETE PAVEMENT Concentrated loads on light traffic concrete pavement shall be those for a nominal loading of forklift of 10 kN as stated in table 13 (SI 412). Same design loads apply for reinforced concrete covers for pits and trenches located in light traffic concrete paved areas Considering the above design loads for light traffic concrete paving, a minimum surcharge load of 12,5 kN/m2 on the soil shall be considered for structures below grade and for walls of retaining structures. This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. Contractor Job No OWNER HAIFA NEGEV TECHNOLOGIES LTD 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 Rev sh. 31 of 51 S1 HEAVY TRAFFIC CONCRETE PAVEMENT Design load on Heavy traffic pavement, erection and lay down areas according to SI 412 table 12 for 600 kN vehicle (Vehicle Type 3) as per following SI 412 table 12 Design loads for bridges, culverts, trench covers and underground elements in heavy traffic areas according to IS1227, load type HB: 1000kN vehicle with 4 axles 4 wheels per axle Wheel contact area 250kN/axle 250/4kN=62.5 kN/wheel 0,3mx0,3m or DIA 0,34m The surcharge on soil in vicinity to roads, areas for major assembly work and lay down areas shall be 20 kN/m2 if not otherwise stated on relevant design drawings. This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. Contractor Job No OWNER HAIFA NEGEV TECHNOLOGIES LTD 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 Rev sh. 32 of 51 S1 8. LOAD COMBINATIONS Design loads shall be combined in accordance with SI 466 for concrete structures (ref to par. 8.1.2) and SI 1225 for steel structures (ref to par.8.1.1), considering the concurrent actions to be considered in load combinations for erection, testing, operation, and maintenance conditions as per below table (ULS=Ultimate Limit State, SLS=Serviceability Limit State, RANDOM=Random Limitation State). If local codes requirements are more stringent than the ones here specified, local codes shall prevail Load Condition Erection Test Operation Maintenance Check ULS ULS ULS & SLS RANDOM ULS Permanent Load Structural self-weight (DL) X X X X X Buildings Permanent Self weight (DB) X X X X X Weight and pressure of soil (DS) X X X X X Prestressing Forces (DP) X X X X X (EE) X Live Loads-extended time Equipment/cables/piping erection weight Equipment/cables/piping operating weight X (EO) X X X X X X (7) X X (DYN) X X Shrinkage & creep (CS) X Differential settlings (DS) Buildings defined Imposed (EB) Friction Loads (TLf) Weight and pressure of water/other fluids (BP) Vibrating machinery loads X X X X X X X X Live Loads-short time Equipment/piping test weight (ET) X (6) Superimposed live load (LL) X X X (9) X (2) Buildings live load (BL) X X X (9) X X X X X Thermal Loads - site (T) Snow Load (S) Maintenance load X X (3) (ML) X (5) Live Loads-very short time Wind load (W) Impact load (IL) Construction Load (CL) X X (4) X X X (4) X X X This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS H00 H00-CA-E-11600 Rev sh. 33 of 51 S1 Random Loads Earthquake Load (E) X (11) Blast load (B) X Failure of bearing element (C) X Vehicle Shock load (V) X (1) Consider self-weight of the empty cable tray (i.e., without cables) (2) Not to be combined with tube bundle extraction load (3) As alternative to the superimposed live load (LL) on roofing (4) Wind load can be reduced to 25% in hydrotest and maintenance conditions (5) Tube bundle extraction load shall not be considered in combination with wind load (6) In a structure where air-coolers, exchangers and several pressure vessels are installed, the air-coolers, exchangers and one pressure vessel only shall be considered together in hydrotest condition. (7) On pipe racks only one pipe at a time shall be considered in hydrotest. (8) Only the loads due to anchor and guides shall be considered acting when combined with earthquake (9) In Load combinations where Random Loads are considered, ONE random load at the time shall be considered for each load combination (10)When considered jointly with the earthquake loads, the superimposed load acting on the structure can be reduced as per Frequency Factor kq (11)Earthquake load shall be considered in both the direction as follows where X and Z is in horizontal direction and Y in vertical direction • • • +/- X +/- 0.3Y +/- 0.3Z +/- 0.3X +/- Y +/- 0.3Z +/- 0.3X +/- 0.3Y +/- Z ULS LOAD COMBINATIONS ULS Load Combinations represent the state of the structure under conditions of constant and variable loading This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. Contractor Job No OWNER HAIFA NEGEV TECHNOLOGIES LTD 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS 8.1.1 H00 H00-CA-E-11600 Rev sh. 34 of 51 S1 Steel structures Partial Safety Factors for Ultimate Limit State according to SI 1225 Table 7 (b)Live Load Combination(a) Permanent Loads (ref par 4) Loads including snow (ref par 5 excluded 5.3.1, 5.3.2,5.2.6,5.1.7) Wind (ref par 5.3.1) Crane (ref par. 5.3.2) Temperature variations (ref. par 5.2.6) Imposed Differential settlements (ref par 5.1.7) Earth quake max min max min max min max min max min max min Permanent + live 1.4 1.0 1.6 0.0 - - 1.6c 0.0c - - - - - Permanent + wind 1.4 1.0 - - 1.4 - - - - - - - - Permanent + live + wind +Temperature Variation + differential settlements 1.25 1.0 1.25 0.0 1.25 0.0 1.25 0.0 1.25 0.0 1.25 0.0 Permanent + live +Temperature Variation + differential settlements + Random 1.0 1.0 (d) (d) - - 1.0 0.0 1.0 0.0 1.0 0.0 1.0 NOTES a) The minimum values should be taken when the force reduction causes increase of the reaction. Load shall be considered as acting at the same time when the reaction in the component is increased b) Liquid pressure is considered as live load with gfmax=1.4, gfmin=0.0 c) For vertical or horizontal force only. When vertical AND horizontal forces are acting at the same time, gfmax=1.4 d) Frequency Factor Kq according to SI 413 table 8 8.1.2 Concrete Structures Partial Safety Factors for Ultimate Limit State according to SI 466 Part 1 Table 2.1 & 2.2 Table 2.1- Mandatory load combinations and partial safety factors for concrete structures at ULS (a) Load Combination NR Load Combination Partial Safety Factors for Ultimate Limit State 1 Permanent + live (maximum) 1.4 1.6 - - 2(b) Permanent + live (minimum,) 1.2 0 - - 3 Permanent + wind (maximum) 1.4 - 1.4 - 4 Permanent + wind (minimum) 1.2 - 1.2 - Permanent Live Wind Earthquake This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. Contractor Job No OWNER HAIFA NEGEV TECHNOLOGIES LTD 219625 PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Load Combination NR Load Combination 5 Permanent + live + wind 6 Permanent + live + wind (residential Buildings) 7 Permanent + live + earthquake H00 H00-CA-E-11600 UNIT Doc. No PLANT LOCATION: ISRAEL Rev sh. 35 of 51 S1 Partial Safety Factors for Ultimate Limit State Permanent 1.4 Live Wind 1.4 0.6 Earthquake - Not applicable to Haifa Plant 1.00 kq - 1.0 NOTES (a) Load combinations and partial safety factors at this table are mandatory as minimum values. (b) At a single span with cantilever, the safety factor for dead load in combination 2 will be 1.00 instead of 1.2 (c) Values of kq for different structures are listed in SI 413 Kq = 0 for roofs with no access. Kq = 0.2 Residential buildings and office buildings Kq = 0.3 Auditoriums and parking areas Kq = 0.5 Storage, libraries, and archives Kq = 1.0 silos and tanks Table 2.2-Recommended additional load combinations and partial safety factors for concrete structures at ULS (a) Load Combination NR Load Combination 11 Partial Safety Factors for Ultimate Limit State Permanent(d) Live(b)(c) Wind Snow Crane Permanent + live + wind (Nonresidential Buildings) 1.4 1.2 ψ 1.2 - - 12(b) Permanent + live + wind (dominant) +snow 1.4 1.2 ψ 1.2 0.6 - 13 Permanent + live + wind +snow (dominant) 1.4 1.2 ψ 0.6 1.2 - 14 Permanent + live (dominant) +crane 1.4 1.4 - 1.0 15 Permanent + live +crane (dominant) 1.4 1.0 - 1.2 16 Permanent + live +wind +crane (dominant) 1.4 0.6 - 1.2 17 Permanent + live +wind (dominant) +crane 1.40 1.2 - 1.0 NOTES (a) Load combinations and partial safety factors at this table are recommended only. (b) Whenever the influence of the live load reduce the reaction- this load should not be considered This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD Contractor Job No 219625 UNIT Doc. No PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS (c) H00 H00-CA-E-11600 Rev sh. 36 of 51 S1 Liquid pressure on walls and floors will be considered as a live load with partial safety factor of 1.4, when considering the operational level of the liquid. When considering the maximum possible level of the liquid, the value shall be 1.25. (d) The value of the partial safety factor for lateral earth pressure at ULS shall be 1.4 SI 466 table 2.3- Minimum frequency factor for live variable loads LOAD Frequency Factor ψ Live load on: 1 2 3 4 5 6 7 8 Non accessible roofs Residential Building, hotel offices, Control room Building and Electrical Substation Public Buildings, auditoriums, industrial buildings, car parking, garages, massive roofs Parking for heavy vehicles, balconies and Warehouses Education buildings, shops, staircases 0.0 Tanks, silos Wind, snow, temperature variation Other secondary load except of live load 1.0 0.3 0.5 0.6 0.6 0.0 0.5 SLS LOADS COMBINATIONS For serviceability limit states (i.e., deflection check and crack width check), for structure stability, soil pressure check and pile load analysis the load factors shall be considered equal to 1.00 for all loads. LIQUID RETAINING STRUCTURES Liquid retaining structures have to be designed for the relevant load combinations in the following conditions: erection/maintenance condition: Empty basin, earth pressure and ground water pressure acting, other applicable loads (e.g., live, equipment loads etc.) acting. test condition: Basin full of water, earth pressure and ground water pressure not acting, other applicable loads acting (e.g. live, equipment loads etc.). This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 37 of 51 S1 operation condition: Basin with liquid at operation level, earth pressure and ground water pressure acting, other applicable loads acting (e.g., live, equipment loads etc.). This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 38 of 51 S1 1. ANNEX 1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 39 of 51 S1 2. ANNEX 2 Extracts from EC 1991 1-4- same as SI 414 2.1. VERTICAL WALLS OF RECTANGULAR PLAN BUILDINGS This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 40 of 51 S1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 41 of 51 S1 2.2. FLAT ROOFS This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 42 of 51 S1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 43 of 51 S1 2.3. MONO PITCH ROOFS This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 44 of 51 S1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 45 of 51 S1 2.4. DUO PITCH ROOFS This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 46 of 51 S1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 47 of 51 S1 2.5. CANOPY ROOFS A canopy roof is defined as the roof of a structure that does not have permanent walls The degree of blockage under a canopy roof is shown in Figure 7.15. It depends on the blockage ϕ, which is the ratio of the area of feasible, actual obstructions under the canopy divided by the crosssectional area under the canopy, both areas being normal to the wind direction. NOTE: ϕ = 0 represents an empty canopy, and ϕ = 1 represents the canopy fully blocked with contents to the downwind eaves only (this is not a closed building). The overall force coefficients, cf, and net pressure coefficients cp,net, given in Tables 7.6 & 7.7 for ϕ = 0 and ϕ = 1 take account of the combined effect of wind acting on both the upper and lower surfaces of the canopies for all wind directions. Intermediate values may be found by linear interpolation. Downwind of the position of maximum blockage, cp,net values for ϕ = 0 should be used The overall force coefficient represents the resulting force. The net pressure coefficient represents the maximum local pressure for all wind directions. It should be used in the design of roofing elements and fixings. For a mono pitch canopy (Table 7.6) the center of pressure should be taken at d/4 from the windward edge (d = along wind dimension, Figure 7.16). This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 48 of 51 S1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 49 of 51 S1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 50 of 51 S1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. OWNER HAIFA NEGEV TECHNOLOGIES LTD PLANT LOCATION: ISRAEL PROJECT: HAIFA CHEMICALS AMMONIA PLANT SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS Contractor Job No 219625 UNIT Doc. No H00 H00-CA-E-11600 Rev sh. 51 of 51 S1 This document is prepared by SEI-Saipem SPA. for HAIFA Negev Technologies Ltd. It contains proprietary and confidential information of Saipem and/or of the Technologies Licensors who will safeguard their rights according to the civil and criminal provisions of the law. It shall neither be disclosed to third parties nor used for purposes other than those for which it has been disclosed. PLANT LOCATION : ISRAEL PROJECT : HAIFA CHEMICALS AMMONIA PLANT Project Job No. : 219625 COMMENT RESOLUTION SHEET ACTION BY COMPANY Doc Date 23.02.21 Client Doc No. xxxxxxxxxxxxxxx Drawing / Document Number, Title and Revision: Doc. No.: H00-CA-E-11600 Rev. No. : A1 19.02.2021 Rev. Date: Title: ACTION BY CONTRACTOR FINAL AGREEMENT Document STATUS code by COMPANY CODE R SPECIFICATION FOR DESIGN LOADS AND LOAD COMBINATIONS PROJECT MANAGEMENT Discipline: COMPANY Originator NAME CONTRACTOR position Please provide Job Specification referenced ADYR Agreed 12 Please provide the related project specification ADYR 13 For all imposed loads of all kinds, please mention in the Specification for Design the reference for the values presented. For example: SI 412, Table-1, No. 2.1 A1 CONTRACTOR Action NAME COMPANY POSITION B. Noted. No modification required, clarification Reference documents/drawings listed in Clause follows. 2.3.3. will be provided N.Saiprasad Agreed Closed Agreed B. Noted. No modification required, clarification Reference documents listed in Clause 5.1.5 will be follows. provided N.Saiprasad Agreed Closed ADYR Agreed A. Noted. Comment will be implemented. Minimum SI 412 requirement verified, however conservative values are used where SI codal value is less than the specified value. N.Saiprasad Agreed Closed the clause relates only to Spectrum I. EPC should refer also to Spectrum II which is relevant for the Ammonia Storage Tank area. AS Agreed A. Noted. Comment will be implemented. N.Saiprasad Agreed Closed A1 It is specified that in accordance with IS 413 not only a specterum of 2% should be examined for fifty years but also a spectrum of 10% for fifty multiplied by a coefficient of 1.4. Such load case is not necessary and Owner recomends to check again with local Engineering company. AS Agreed A. Noted. Comment will be implemented. N.Saiprasad Agreed Closed A1 EPC selected a PGA value, driven from IS 413 formula for active ground forces during earthquake (according to the standard map for Mishor Rotem) with a probability of 10% for 50 years gives Z=0.12. This is a non-conservative approach for two reasons: (1) In the case of soil stability calculations related to CLASS A structures, Z value shall correspond to a return period of 2% 50 years. sleep. (2) According to IS 413 the PGA value in use, should at ground surface and not the Z value defined by the site response. AS Agreed A. Noted. Comment will be implemented. N.Saiprasad Agreed Closed A1 Load combination specified - EPC should include a sub clause for EQ load and specify the combinations given in clause 302.0 in IS 413 as follow: - X + 0.3Y + 0.3Z - 0.3X + Y + 0.3Z - 0.3X + 0.3Y + Z AS Agreed A. Noted. Comment will be implemented. N.Saiprasad Agreed Closed CP No. Rev. Page number 2.3.3 A1 6 5.1.5 A1 5.2 A1 6.1 6.1 6.1.1 08 File: H00-CA-E-11600-A2_CRS COMPANY Comments Description Comment Action Confirmation / Explanation As per TQ response from Client (TQ no. H00-SEIHCL-TQ-00001) 10% in 50y requirement need not be considered COMPANY REPLY STATUS Page 1/1