HYBRID LOAD-ADAPTIVE VARIABLE-SPEED GENERATING SET: NEW SYSTEM TOPOLOGY AND CONTROL STRATEGY W. Koczara *, L. Grzesiak**, Warsaw University of Technology, Poland 00-661 Warszawa Tel +48 22 6294991, Fax. +48 22 6256633 *Visiting Professor to the University of Pretoria, South Africa Tel +27 12 420 3190 Fax. +27 12 362 5000 *E- mail: koczara@isep.pw.edu.pl **E-mail: grzesiak@isep.pw.edu.pl M. da Ponte, Volt-Ampere, Pretoria, South Africa, P.O. Box 4245, Pretoria 0001 Fax +27 12 324 4203, Tel. +27 12 328 6551 E-mail: vanetcom@cis.co.za ABSTRACT The paper notes the changing circumstances of the electricity industry, in which generators will have an increasing role to play at consumer level, for base load, peak shaving and UPS purposes. The characteristics of various constant and variable-speed engine-driven generating systems are reviewed. A novel, load-adaptive generation technology with automatically adjusted speed – namely the Hygen system – is introduced, a working model (already in service) described, and some test results provided. The novel application of a controllable converter to the alternator output and the unique topology and control strategy of a power electronic converter system have made possible the successful integration of engine, alternator, energy storage devices and microcomputer control to produce an intelligent energy delivery system with manifold variations in application, and power ratings into the megawatt range. The greatest benefits of the system are that it delivers reliable, no-break, high quality power at constant voltage and constant frequency, suitable for all loads including modern electronic appliances and other sensitive equipment; and that it maintains its performance and high quality of supply under even the most abusive load conditions with which conventional generators and UPS units or combinations thereof cannot cope without sustaining damage or compromising their performance or output quality. Moreover, it does so with considerably greater fuel economy than constant speed gensets; alternatively it can be optimised for a number of other priorities e.g. maximum power. INTRODUCTION It was James Watt’s steam engine that made possible the large scale commercial generation and distribution of electricity, and in turn enabled the quantum leaps we have seen in electronic engineering, for example in the fields of computing and communications. Sadly, however, electricity generation and distribution is still by and large based on the technology and philosophy of a century ago. Though some refinements have been made in materials, design and manufacturing processes, so much capital and technological investment has been made in centralised generation feeding large grids, that even the most adventurous lateral thinking stood little chance of finding alternatives to this tried and trusted system, now at the end of its design life. As we tread the threshold of the new Millennium, it is the “offspring” of electricity – namely electronics and power electronics – that have come to the aid of the ageing parent industry by making possible the economic generation of electricity on smaller (and even small!) scale. In brief, these new technologies are enabling fresh approaches to power generation theory and practice that were inconceivable only a few years ago, in respect of centralised power stations feeding national and even international grids, and also in respect of distributed and island power generation. The purpose of this paper is to look at developments in this essential industry, and introduce an attractive new technology – namely Hygen, the novel hybrid load-adaptive adjustable-speed system with programmable engine torque control. A NEW SCENARIO - DISTRIBUTED AND ISLAND GENERATION In effect, the move towards deregulating the electricity utilities is stimulating distributed generation, which will crystallise in much smaller local power stations – on and off-grid - and a proliferation of distributed generating units at consumer level [1]. A new electricity industry will emerge [2] in which small power plants (up to several Megawatts) comprising new technology reciprocating and/or turbine engines driving alternators at variable and/or high speed [2], [3] [4], [5] and [6], will feature predominantly. Waste heat exploitation is also developing rapidly and will drive overall efficiencies above the eighties. The fledgling fuel cell technologies [7] and [8] are attractive alternatives which show great potential, but they have yet to progress up the path of experimental development to maturity. A technical barrier which poses a major obstacle in the application of fuel cell technology is the limitation in output power ramp, e.g., 10% of rated power per minute [7]. The varying nature of load profiles imposes load changes which almost without exception require a complementary system such as high capacity energy storage or other means of supplementing the fuel cell system in a load levelling function. THE UNFORTUNATE LEGACY OF GENERATOR SET SIZING Engine-driven generating plants are also sensitive to varying load power demand and the nature of the load current, which affect the allowable voltage variation – both in the steady state and under transient conditions. It is common practice to oversize generator sets to compensate for voltage-distorting non-linear loads and cope with large step loads as well as intermittent overloads and impact loads such as those caused by the starting of induction motors. Naturally, in larger generating plants where the rated power of the induction motor is relatively small in comparison with the rated power of the generating plant, this problem is insignificant. Conventional gensets are heavily oversized in relation to prevalent load conditions. The established practice of sizing generator capacity for worst case load scenarios according to volt ampere power (kVA) and a power factor of 0.8, has resulted in generator sets operating with light loads for long periods. Installations in which generator sets operate at an average load of 20% to 30% of installed capacity are common in smaller power systems, e.g. up to 300kVA. For light loads, the specific fuel consumption is very poor, in that incomplete combustion does not utilise all the fuel. Worse still - the unburnt fuel dilutes the oil in the cylinders and thereby causes excessive wear in the cylinder walls, cylinder glazing and carbon build-up. These harmful and destructive conditions result in severe deterioration in engine performance and inflict premature engine failure – typically at 20% of design life. To avert these harmful effects, manufacturers insist that engines operate with loads above 50%. In larger installations, the common problem of under-loading engines is overcome by employing costly multiple generator sets running synchronously and controlled automatically so as to operate with acceptable capacity factors at all times. Although the partial backup thus provided is an important benefit, the complexity of such a system is obvious and loading is guaranteed only up to 50% of capacity. For higher capacity factors, some form of Demand Side Management is required, which in effect, only manages the problem and does not solve it. In small plants – particularly installations comprised of a single genset - dummy loads are recommended, which adversely affect the fuel economy and drive operating costs through the ceiling. Generator set/UPS combinations to provide extended autonomy are increasing rapidly in number and in size (up to 1 MVA). UPS systems are themselves often voltage-polluting non-linear loads – there is the rare exception – and therefore exacerbate the problem of oversizing the generator set with a multiplier effect. According to some application practices, the generator set is sized to be two to three times the non-linear load power. If the generator set is sized according to volt ampere power using the industry standard power factor of 0.8 (common practice), a 50kVA UPS installation will require a 100kVA/80kW generator set. The typical active load power (kW) for a 50kVA UPS system is of the order of 35kW at full load. If for example the average load is 40% of installed capacity, it will result in an average load of 14kW. This corresponds to 17,5% of the active power (kW) rating of the machine. All other implications aside, this solution is without question bad engineering practice and will culminate in disastrous results. A better approach is to size the engine according to the active load power demand (kW) and the generator according to the oversizing practice, namely, two to three times the volt ampere power (kVA). Although this is a more sound engineering practice, such a design is still not optimal as it addresses the symptoms rather than the cause. This approach requires specially designed alternators or UPS systems with power factor correction, which draw sinusoidal current from the supply. Providing extended no-break power with a genset and UPS system combination – without taking special measures - compounds the problem of oversizing and under-loading. HYGEN IN BRIEF The novel Hygen* system overcomes the abovementioned shortcomings effectively and paves the way for a new approach to an old problem. Hygen is an engine and environment friendly, load-adaptive adjustable-speed electricity generating and Uninterruptible Power Supply (UPS) system with energy storage - in a hybrid configuration. Using systems engineering principles, it integrates engine, alternator, energy storage devices, power electronic converters and microcomputer control to produce a fully integrated intelligent energy delivery system with manifold and almost limitless variations in applications – base load, UPS and peak shaving. It delivers reliable, no-break, high quality power at constant voltage and constant frequency suitable for all loads including modern electronic appliances and other sensitive equipment. It maintains its performance and high quality of supply even under the most adverse load conditions with which conventional generators and Uninterruptible Power Supply (UPS) units – or combinations thereof – cannot cope without sustaining damage or compromise in performance or output quality. Unquestionably, it does so far more economically than conventional gensets which operate at constant speed – with up to 70% fuel saving and 500% longer engine life in some applications. The Hygen system presented in this paper (designed for low power application) comprises an aircooled permanent magnet alternator (specially designed for rectifier loads) mechanically integrated into a modified diesel engine (the outer rotor of the alternator replacing the engine flywheel), a bank of lead acid batteries connected in series with boost charger and individual equalisation chargers, a multiple power electronic converter system and a microprocessor control system with interactive operator interface. A highly compact unit was achieved by “optimal” integration of the modules. The system is equipped with comprehensive protection in the form of surge protection, fuses and circuit breakers for all modules. The protection devices include signal contacts which provide the microprocessors with information on their status or condition – crucial to the self-diagnostic function of the system. Its operator interface displays information on all the monitored and measured parameters of the system and empowers the operator to control the machine and access its status, condition and performance information through a user friendly and interactive panel. Facilities for remote monitoring and control by PC include a RS232 serial port for direct connection to PC or via modem and a coupler for linking up with the machine by means of fibre optic cable. Windows compatible software provides virtual instrumentation and control features which can be easily customised. Routine checks, startup tests and maintenance support are possible anywhere by hooking up to a notebook PC and a telephone line, and clicking the mouse, even when in flight between continents. It is packaged in a super-silent canopy with a 60 litre onboard fuel tank giving up to four days’ operation depending on the load profile, and incorporates all necessary measures for compliance with ------------------------------------------------------------------------* The Hygen system forms the subject matter of South African patent No. 97/11503 and international patent application No. PCT/EP 97/07273 designating inter alia Europe, USA, Australia, Canada, Japan and China. stringent EMI standards. Details of the Hygen system** are given in Table 1, and a visual presentation in the adjoining photograph. TOPOLOGY OF THE HYGEN SYSTEM The production of high quality output power with constant voltage and constant frequency, using a variable-speed electricity generating unit, is made possible by the application of new technology power electronic AC/DC/AC converters and micro-computer control [5]. A block diagram of the load-adaptive adjustable-speed system is shown in Figure 1. The speed of the engine- generator unit IEG, comprising an engine ENG and a permanent magnet AC generator PMG, is automatically adjusted according to the active load power demand and thus generates a three phase output voltage and frequency which is proportional to speed. The voltage and variable frequency (three phase) output of the generator PMG is fed to an active boost rectifier ABR wherein it is rectified by rectifier R to form the primary DC voltage, DC link1. The voltage of DC link1 is boosted by booster B to provide a regulated secondary DC voltage, DC link2, referred to as the DC Bus. An energy storage system ESS is connected to the DC Bus through a bi-directional converter BDC to form the power conditioning energy storage PCES module. The DC Bus supplies a DC/AC inverter IF which in conjunction with an output filter produces a sinusoidal, constant voltage and constant frequency output. The protection module P consists of surge suppression devices and circuit breakers. The load LD represents typical real-world loads which produce diverse load profiles with dramatic variations in load power demand. A multiple micro-processor control system MMC communicates with all the modules via a number of sensors, controls the operation of the modules individually and manages their interaction at system level to produce a high quality electrical output from an “optimised” energy efficient fuel input. The control system incorporates an operator-machine interface which displays information on all the mechanical, electrical and electronic parameters of the system including the status of the protection modules. In addition, it provides a RS232 serial port and a fibre optic coupler for a remote control and monitoring computer RCM. POWER AND ENERGY FLOW MANAGEMENT The Hygen system presented herein uses a diesel engine-generator unit as primary energy source and a lead-acid battery bank as secondary energy source. Figure 2 depicts the power flow between the engine-generator unit, the energy storage battery and the load. There are four basic states of operation namely, S1, S2, S3 and S4, as illustrated in figures 2a, 2b, 2c and 2d respectively. In figure 2a (S1) power (Pe) from the engine-alternator and active boost rectifier ABR, flows directly to the load Pl (Pe =Pl). ------------------------------------------------------------------** The Hygen system was designed, developed and hand manufactured by the Volt Ampere Group of Pretoria, South Africa in co-operation with the Warsaw University of Technology, Poland and the University of Pretoria, South Africa. In figure 2b (S2) power flows from the battery Pb to the load Pl (Pb = Pl) when the battery is charged and engine operation is uneconomical or undesirable. In this operating mode, the Hygen system is similar to the well known and widely used UPS systems. The engine is in standby mode and automatically cuts in when the battery is discharged to a pre-determined level. In Figure 2c (S3), the power flows from the engine Pe to the load Pl and the battery Pb (Pe = Pb + Pl). The engine supplies power to the load and replenishes the battery energy. In figure 2d power flows in parallel, from the engine Pe and from the battery Pb to the load Pl (Pl = Pe + Pb). The battery supports the engine and augments the output power to produce high peak power for relatively short periods. The system peak power capability is thus the sum of maximum engine power and maximum battery power. The battery can be sized to meet the load power demand during periods when engine operation is undesirable or uneconomical, and to support the engine and augment the output power to meet peak load power demands of short duration. Therefore, in applications where high peak load power demands are of relatively short duration, the engine-generator unit does not need to be sized according to the peak load power demand. A smaller and cheaper engine which is more economical to run will suffice, as it is supported by the battery. This contrasts with the need to over-size a conventional generator set to cope with peak loads. This intermittent high peak load capability also enables the system to maintain its high quality output voltage in transient conditions e.g. switching high step loads or impact loads. At the lower end, when the load power demand is too small, under-loading is averted by utilising some of the engine power to charge the battery as depicted in Figure 2c. When the battery is fully charged and if the light-load power demand persists, the engine is automatically stopped and the battery supplies power to the load as depicted in Figure 2b. Small plants are particularly exposed to under-loading while in larger units it is not so common. There is thus no need for fuel sapping dummy loads to prevent under-loading, which makes the Hygen system a very economical one to operate in applications with extended low power demands e.g. low power demand at night. STRATEGY OF CONTROL The AC generator PMG output which varies in voltage and frequency as a function of speed is converted to DC by rectifier R, forming the primary DC link, DC link1. The voltage of DC link1 is boosted by the booster B in the active boost rectifier ABR to form the secondary DC link, DC link2, referred to as the DC Bus. The active boost rectifier ABR is a variable ratio converter which boosts the primary DC link voltage and regulates it according to a predetermined voltage reference (the first DC Bus threshold). A current control loop regulates the current according to a predetermined current reference signal which is representative of the engine torque. This current reference signal may be altered and shaped in a signal conditioner so that it represents any desired engine torque/speed characteristic. Figure 3 illustrates the engine continuous torque/speed characteristic Tr and the desired torque/speed characteristic Th which will result in the lowest fuel consumption for load-adaptive adjustable-speed operation between a constant minimum speed operating point (ωmin) and a constant maximum speed operating point (ωmax). The specific fuel consumption contours, F1 to F5 are also shown. F1 represents the region of lowest fuel consumption, known as the “sweet spot”. The curve Tp represents the part-load torque/speed characteristic and resembles the engine’s rated torque curve Tr. Engine designers are compelled to compromise the engine’s fuel efficiency at rated torque Tr1 to accommodate a reasonable fuel efficiency at part-loads Tp e.g. Tp < load torque < Tr1. When the engine is running at the minimum constant speed point (ωmin), and LD increases, the current in the active boost rectifier ABR, and hence the alternator current, is allowed to increase. The engine’s load torque is proportional to the alternator current and therefore increases accordingly. When the engine’s load torque reaches point P1 on the desired torque curve Th, the current control loop in the active boost rectifier ABR regulates the current according to the reference signal which represents the desired engine load torque characteristics Th for the most economical operation. When the load LD exceeds the output power of the engine at a given moment – the power is the product of its speed and torque – the regulated current in the active boost rectifier ABR limits the alternator output. Consequently, the alternator, and hence the engine cannot meet the load demand. The DC Bus is therefore “starved” of power and the voltage decreases as the DC Bus capacitors deliver power to the load. The voltage control loop detects the lower voltage and activates the engine speed governor so that the engine speed increases. The alternator voltage, which is proportional to the speed, increases accordingly. Therefore the alternator output power and the engine’s output power increase accordingly. When the voltage is restored to the predetermined DC Bus voltage, the first threshold, the engine speed stabilises at the higher speed and hence higher power level, thereby restoring the balance of power between the engine-alternator output and load. The alternator current, and hence the engine load torque, will follow the desired curve Th as the speed increases with increased load power demand. When the load power demand corresponds to the torque at maximum speed P2, the engine runs at constant speed. Beyond this load, the alternator current will be permitted to increase up to its maximum rated current, which corresponds to the maximum continuous engine torque and hence maximum power at the maximum speed, point P3 on the rated torque curve Tr Conversely, when the load power decreases to P2, the power balances will be disturbed and the voltage in the DC Bus will rise above the reference threshold. The voltage control loop will activate the engine speed governor to reduce the speed until the voltage is restored to the reference threshold. The engine speed will again stabilise at the lower operating point. When the load torque decreases to P1, the engine will run again at minimum constant speed and the current will decrease as the load decreases. The torque curve Ti represents the maximum intermittent torque of the engine. The difference in torque between the Ti and Th represents the excess torque Ta which enables engine acceleration under load. Note that at minimum speed the desired regulated torque curve Th is made to deviate from the most economical curve so that acceleration torque Ta is available at all times. Whilst in this example the engine torque versus speed characteristic is programmed for fuel efficiency, it should be noted that the system can be programmed to optimise other performance parameters e.g. maximum load. Referring back to Figure 1, the power conditioning and energy storage system PCES supports the DC Bus when the power flow from the generator is insufficient to meet the power demand of load LD. In this instance, the DC Bus voltage falls below its first threshold. Energy from the battery is pumped to the DC Bus, thereby regulating the DC Bus voltage at a second threshold, marginally lower than the first threshold, that will meet the minimum requirements of the DC/AC inverter. The energy delivered to the load from the battery is replenished when the power balance is restored and there is excess engine capacity. Figure 4 shows a simplified diagram of the relationship between the total output power Pl when the generator power Pe is supported by the battery power Pb, and the speed. Note that the battery charging power Pb1 is considerably lower than the battery output power Pb2 in order to extend battery life. (Pb1<< Pb2). Constant speed operating points are indicated by ω min for low speed and ω max for high speed operation respectively. The generator power is represented by the curve Pe (Pe = ωT). The total available power Pl therefore also follows a similar curve Pe and is augmented by the battery power Pb (Pl = Pe + Pb, with Pb being constant as depicted). The inverter is controlled by an additional control loop and high quality power is produced at the inverter and output filer IF, even under the most adverse load conditions. A REVIEW OF SOME ALTERNATIVE GENERATING SYSTEMS Constant speed generators? Constant speed electricity generators need no introduction. Suffice it to say that it is the most widely used system in applications ranging from watts to the largest of power stations. Substantial development efforts costing millions of dollars, over many years, have been put into improving the speed governors of engines so that the speed deviation from synchronous speed is minimal e.g. 1 –2 % speed regulation. In Figure 5, the torque versus constant speed is depicted by the vertical line Tc1. The engine load torque is directly related to the load; the engine speed governor merely responds to load charges by increasing or decreasing the fuel rate in an attempt to maintain the speed constant. The engine torque follows the load torque directly up or down the constant speed line as depicted by the vertical torque line Tc1 for a constant speed engine. More often than not, the rated torque at P4 does not correspond to the engine’s best point of operation, the “sweet spot”. But assuming that the rated torque does correspond to the engine’s “sweet spot” and that an imaginary engine map with fuel consumption contours is appropriately placed on the graph, with P4 in the “sweet spot”, it will be evident that economical operation at constant speed is restricted to a very small region in the map. Furthermore, in most engine maps, the fuel consumption contours do not cross the torque line Tc1 for torque values below, say, 50% of rated torque. Engine manufacturers explain that the engine should in any event not operate in this region for long periods. An equivalent Hygen system will use a much smaller engine with a lower rated torque to produce the same power (Pe = ωT) corresponding to the equal powers at P4 and P3 for constant and variable speed respectively. It is evident in Figure 3 that with the Hygen technology, the engine torque is regulated so that the most economical operation is maintained over a wide range of speed and hence power. Furthermore, operating in the under-loaded region is averted because the part of the torque range which falls outside the fuel consumption contours of the engine map is very small - and load torque can be sufficiently increased by charging the battery. Variable speed generators? Variable speed generators/alternators have been in use for decades. In aircraft, variable-speed constant frequency generators have been used for many years. However, in these and most other applications, e.g. wind generators, variable speed is a given condition and power converters/conditioners merely convert the variable voltage and variable frequency to a constant voltage and constant frequency. Wind generators with ratings into the Megawatt power range are operating on wind farms and delivering electric power to the grid through double conversion power electronic converters. Manually adjusted speed generators? A spin-off of the matured variable-speed generator technology is the “dial-a-speed” generator set with manually adjusted speed, at the lower end of the power range. Figure 6 shows a block diagram of the system in which an engine is equipped with a mechanism for manual speed adjustment and drives a permanent magnet alternator. The speed is adjusted to operate at a constant speed in accordance with the required maximum load. The torque characteristic of this system is depicted by the constant speed, vertical line Tc2 in Figure 5. The principle of operation is similar to that of constant speed operation depicted by the line Tc1. However, when the speed is adjusted, the line Tc2 will move laterally depending on the adjusted speed and the rated torque (and hence rated power) will correspond to P5 which follows the torque curve Tv. (Between points P6 and P7, it is significantly lower than the engine’s rated torque Tr, so that unpredictable load fluctuations are accommodated.) Its output power (P = ωT), voltage and frequency vary with speed. The alternator output is rectified to form a DC Bus. A PWM inverter converts the variable DC voltage to a specified constant AC voltage (e.g.110V) and constant frequency (e.g.60Hz). The inverter can tolerate limited variations in voltage through its PWM operation as long as the DC Bus voltage is higher than the required output voltage. However, restrictions in voltage variation limit the speed range, and applications using this system are thus restricted to small power installations e.g. mobile homes, boats or yachts, where there is good control over the load and the operator is able to apply strict Demand Side Management. The step loads and the speed range are also limited so as to avoid nuisance tripping of the protection devices and prevent engines from stalling. Whilst this is an improvement on constant speed operation, practical application of the system is restricted. Naturally, by adjusting the engine speed, and hence its output power, the engine can be made to operate at a power level which marginally exceeds the required maximum load. The benefits of this system are thus slightly lower fuel consumption, lower noise levels and constant voltage/frequency, even when the speed is manually adjusted (within limits) to a lower level during light load periods such as at night. Under-loading also is thus mitigated and sometimes averted. Load-following variable-speed generators? An extension of the “dial-a-speed” system is the load-following variable-speed generator with additional engine speed governor, a means of sensing the load, and a control system which responds to load changes by effecting an appropriate change in engine speed. The topology of this system is similar to that shown in Figure 6. There may or may not be an energy storage system to support the engine/alternator and augment the output power. The torque versus speed characteristic of this system is depicted by the curve Tv in Figure 5. Note the smaller speed range and - again - the lower torque between minimum and maximum speed operating points P6 and P7! The means of sensing the load may take the form of measuring the output current/power or the voltage in the DC Bus, which falls when the load increases and rises when the load decreases. In one of the control schemes, a voltage sensor senses the DC Bus voltage fall/rise and the control system increases/decreases the engine speed, and hence the alternator and DC Bus Voltage, respectively. In the load torque ranges below P6, and between P7 and P3, the system operates similarly to the constant speed generators. However, for speed adjustment, the torque versus speed characteristic between points P6 and P7 depends on the generator design, the DC Bus characteristics and the control scheme. (The system is designed for a particular engine/alternator match, or operating point or specific operating condition). As the load increases/decreases, the speed is increased/decreased in order to maintain the DC Bus voltage within the limits required by the inverter. This is a paradox to some extent because on the one hand the DC Bus voltage must not exceed the limits of the inverter, whilst on the other hand the voltage will vary in relation to speed (and load current, depending on the voltage versus load characteristic of the alternator). However, without going into too much detail, these problems can be overcome by imposing some restrictions on the system e.g. limiting the speed range, limiting the step load capability and generally oversizing the system to allow for derating according to site conditions e.g. ambient temperature and altitude above sea level, and thereby achieving some measure of autonomy. This is clearly shown in Figure 5 by the torque versus speed curve Tv. If the exercise of placing the imaginary engine map with fuel consumption contours is repeated, it will be evident that this system, although an improvement on constant-speed operation, does not operate in the most economical region. The load-following variable-speed systems are limited in application to small sizes due to their inherent design and to problems caused by real-world loads and load profiles. They require special measures such as: Oversizing to cope with large step loads or, alternatively, imposing restrictions on the nature and size of loads which can be switched on at any given time (Demand Side Management). Oversizing to guarantee performance under varying site conditions e.g. ambient temperature and altitude above sea level. Limitation of the operating speed range to avoid large variations in permanent magnet alternator voltage, and to guarantee engine acceleration when responding to unpredictable step loads. Oversizing and a narrow speed range thus negate the benefits of variable-speed operation. COMPARATIVE FUEL CONSUMPTION FOR VARIOUS LOADS In the Hygen system, the unique innovation and major step forward in adjustable-speed generators is the application of a controllable boost rectifier which enables precise regulation of the engine load torque according to a programmable characteristic. In this example, the engine operation follows the “optimum” operating region in which the lowest specific fuel consumption is achieved. See Figure 3 and 5. Referring to Figure 5, and if the “imaginary engine map” is appropriately placed as previously described, Hygen’s superior performance and economic operation are obvious. The gap is huge – a saving of up to 70% in fuel consumption in some applications. Figure 7 depicts the typical power versus speed curve and the corresponding fuel consumption contours for a diesel engine. The fuel consumption for constant speed operation (4 pole and 2 pole), manually-adjustable speed operation, the load-following adjustable-speed operation and Hygen are shown. The various lines relating to the power levels in the graph show the corresponding fuel consumption for the four systems. Again, Hygen’s superior performance and economic operation “stand out like an oasis in the desert”. Fuel consumption for various loads are compared in the table below Specific fuel consumption is designated by F1–F10 where: F1 < F2 < F3 < F4 < F5 < F6 < F7 < F8 < F9 < F10 LOAD LEVEL 1-2-3-4-5 6-7-8-9 10-11-12-13 14-15-16 17-18-19 20-21 • (4) (1) (2) (3) (4) NB: HYGEN F6 – F7 F1 – F2 F1 F1 – F2 F2 –F3 F5 – F6 F5 – F6 CS-4P F8 – F9 F1 – F2 -(2) -(2) -(2) -(2) -(2) VS -(1) F4 – F5 F3 F3 – F4 F6 – F7 F5 – F6 F5 – F6 MAS (3) -(1) F4 – F5 F3 F3 – F4 F6 – F7 F5 – F6 F5 – F6 CS-2P -(1) -(1) F9 – F10 F8 F7 – F8 F6 – F7 -(2) Operation not recommended (under-loading). Operation not possible (over-loading). Clearly, at 4 pole speed a larger engine is required! In the manually-adjusted speed system, the speed can be adjusted between minimum and maximum, according to the power versus speed characteristic of the load-following variable-speed system. (This adjustment can be represented by moving the vertical line in Figure 7 laterally.) The same limitations with reference to oversizing and speed apply. At maximum load, Hygen’s fuel consumption is similar to the other systems. As the part-load decreases, the benefits accruing from the Hygen increase dramatically. With due consideration to real-world load profiles and their low load factors, it is clearly evident from Figure 7 and the above table that Hygen’s performance in terms of fuel consumption is superior by a wide margin. However, although the above refers to optimisation for fuel efficiency, Hygen can, with programmable torque control, optimise its operation to suit various criteria and applications. HYGEN’S OUTPUT TESTS WITH REAL-WORLD LOADS Although the voltage controller is programmed to limit the maximum switching frequency, the quality of Hygen’s output voltage shown in Figure 8A is exceptionally high. Figure 8a shows the voltage waveform and Figure 8b the harmonic spectrum with the highest harmonic at 0.32% of the fundamental frequency. Because the quality of voltage is exceptionally high for all partload and rated load conditions, test results of only extreme load conditions are presented. Figure 9a shows the voltage waveform in a severe overload condition, i.e. 20 kW resistive load, which represents an overload in excess of 100%. Even under this condition the highest harmonic in Figure 9b is 1,4% of the fundamental frequency. Figure 10a shows a most difficult and troublesome load for inverters, namely, a highly inductive load, 12kVA with a very low power factor ( cos φ = 0,1564). In spite of an almost pure inductive current with a wide lagging angle (φ= 810) the waveform remains virtually unaffected. Figure 10b shows the harmonic spectrum with the highest harmonic being 0,31% of the fundamental. Figure 11 proves the reliability of the Hygen system with a step load of 14kW switched on while the engine is running at minimum speed. The battery energy is pumped to boost the DC Bus and augment the output power while the engine starts to accelerate. Figure 11 shows only a few cycles of the acceleration period, sufficient to show that the quality of the voltage is unaffected. Naturally, the frequency being synthesised in the software remains constant – compare Hygen’s superior performance under this load condition with that of conventional or other more modern variable speed generator sets. Figure 12 shows yet another severe impact load condition, namely, the starting of a 2.5 kW compressor motor. Again the quality of the output voltage is unaffected and the frequency remains constant. TO SUM UP Hygen’s unique feature and technical achievement is the novel application of a controllable converter (the active boost rectifier ABR) which regulates the alternator current, and hence the engine torque, according to any specified torque characteristic. As a result thereof, it is a highly flexible system, particularly in: Automatically adjusting its operating speed across the engine’s full speed range so that it is “optimally” loaded across a wide range of load power demands, with fuel consumption directly related to active output power (kW). Automatically derating the engine when operating conditions deviate from the standard reference conditions e.g. altitude above sea level and ambient temperature. Automatically compensating for large variations in the alternator voltage caused by wide speed variations - without compromising system efficiency, performance or safety. Optimally and efficiently controlling the power flow between its energy sources, and the load. Adapting its torque characteristic to optimise operation for various diverse applications. Its new topology and control strategy provide outstanding flexibility and application and a highquality grid-like power supply irrespective of adverse load conditions. It therefore takes variable speed generators to an unprecedented level of technical sophistication and performance. It extends the application of automatically-adjusted variable-speed generators to sizes in the megawatt range and challenges conventional generating systems with fixed speed operation, e.g. 1800/1500 and 3600/1500 rpm (60/50Hz). In base load applications the system’s low fuel consumption, low maintenance costs and extended engine life due to more efficient combustion, make it highly competitive in terms of the ultimate bottom line – life cycle costs. It can also be optimised (amongst its many possible configurations) to provide a compact, cost effective and highly competitive Uninterruptible Power Supply (UPS) system for power breaks, with engine driven back-up limited only by the availability of fuel. There is therefore no need for large battery rooms and heavy duty, large and expensive diesel engines; a smaller and less expensive automotive engine can suffice. The fact that this engine does not have the service life of a rugged industrial diesel is of no practical consequence, since average annual usage below 1000 hours can be expected. The same unit can provide a load levelling/ peak shaving function, requiring additional running hours. In this instance, however, the engine will be operating at reduced speed – thus also of no practical consequence. For larger applications, truck engines, gas turbines or other “high” speed industrial engines will provide similar benefits. CONCLUSION Increasing and changing consumer requirements will make heavier peak period demands on electricity utilities. The utilities will have to increase capacity, i.e. “oversize themselves”, with resultant costs to themselves and consumers. Alternatively, they will have to encourage peak shaving or load levelling through an appropriate price structure. The bottom line for the consumers will be the cost factor – do they pay the price of high peak loads or do they install their own generating capacity? Furthermore, with computerised industrial automation and the proliferation of electronic appliances such as computers and TVs etc, electricity consumers at all levels will demand high quality, reliable (no-break) power. Generator capacity at plant level is more expensive than normal utility rates. However, highly efficient plant level generation (in respect of fuel consumption, maintenance and engine longevity) could make the difference, and prove advantageous to consumer and utility alike. If an in-house generating facility can also provide extended UPS as well as load levelling, it will be doubly attractive. Conventional gensets are not efficient enough and do not provide these three functions, whilst load-following variable-speed operation without “torque control” addresses only the symptoms and is fraught with many problems in its practical application. By contrast, the Hygen system overcomes these shortcomings through multi-disciplinary systems engineering that successfully integrates mechanical, electrical, electronic and computer engineering into a high performance system in respect of fuel economy, engine/environment friendliness, output quality of voltage and frequency at all times, and immunity to abusive load demands – conditions that frustrate and even damage conventional generator systems. As a result, it has the capability to provide ultra-efficient generation for the electricity industry, and thereby enable the industry as a whole (including both its outdated mega power stations as well as the newly emerging distributed-generation middle-range power stations and lower-end electricity generator and UPS systems) to reshape itself more appropriately to the circumstances of the new Millennium. Naturally Hygen is equally well suited to base load applications. The novel Hygen technology creates variable-speed with programmable torque control that can be optimized for various applications. With this unique feature, it will thus replace the century old technology and prove an indispensable element in the electricity generation scenario of the 21st century. REFERENCES 1. 2. 3. 4. 5. 6. 7. 8. J Whitham: Utility Deregulation and The Role of Stand-by Generators. Conference papers 9th International Conference & Exhibition of Power Generating Industries. PowerGen’96 December 4-6 1996, Orange Country Centre – Orlando, Florida. USA Book IV, pp. 327-331. J Loghead: A New Electrical Industry. Editorial Power Engineering Journal, February 1998, pp. 2-3. Time for the Tine Turbines. Electrical Review. Vol. 231 No. 12 pp. 28-30. L Grzesiak, W Koczara, M Da Ponte: Novel Hybrid Load-Adaptive Variable-speed Generating System. Proceedings IEEE International Symposium on Industrial Electronics ISIE’98, Pretoria, South Africa 7-10 July 1998, pp. 271.276. Hygen Variable-speed Generating System for Quality Electric Power Supply, Technical overview, Volt Ampere, Pretoria, South Africa 1997. M Da Ponte, L Grzesiak, W Koczara, A Niedzialkowski, P Pospiech: Hybrid Generator Apparatus, South Africa Patent No. 97/11503. D R Glenn: Direct Fuel Cells: Putting Power Where You Need It. Conference papers 9th International Conference & Exhibition for Power Generating Industries. PowerGen’96 December 4-6 1996, Orange County Convention Centre – Orlando, Florida, USA. Book IV, pp. 246-254. D Dunnison, D Smith: PEM Fuel Cell Development for a Deregulated Marketplace. Conference papers 9th International Conference & Exhibition for Power Generating Industries. Power-Gen’96 December 4-6 1996, Orange County Convention Centre – Orlando, Florida, USA. Book IV, pp. 231-244. TECHNICAL INFORMATION HYGEN H03011A Modules: Diesel engine - Perkins 103-10 Permanent magnet alternator – VATECH03011A1 Power electronic converter – VATRON H03022A1 Genesis battery G12V39A10EP [x8] Basic Specifications: Rated power: 9kW/18 kVA Maximum power: 18kW, 25kVA (5 min) Power factor: 0,5 Speed range: 1400 – 3400 rpm Output voltage: 230V + 1% Output frequency: 50Hz + 0,01% Battery voltage: 96V Battery capacity: 39Ah Ambient temperature: 550C at 1700m asl Dimension LxWxH: 1500 x 750x 980 Mass: 793 kg (ready to run) Table 1 INTEGRATED ENGINE GENERATOR UNIT MAIN MULTI PROCESSOR CONTROLLER MMC ENGINE ENG ENGINE FEEDBACK & CONTROL GENERATOR PMG GENERATOR FEEDBACK & CONTROL RECTIFIER R DC link1 VOLTAGE AND CURRENT FEEDBACK & CONTROL BOOSTER B ACTIVE BOOST RECTIFIER ABR BI-DIRECTIONAL CONVERTER BDC ENERGY STORAGE SYSTEM ESS DC VOLTAGE FEEDBACK & CONTROL BATTERY CHARGING & EQUALISATION POWER CONDITIONING & ENERGY STORAGE PCES OUTPUT AC VOLTAGE CONTROL DC/AC INVERTER & OUTPUT FILTER IF DC link 2 INTERNAL DISPLAY & CONTROL STATE OF SWITCHES & PROTECTION UNITS PROTECTION P AC OUTPUT LOAD LD RCM REMOTE CONTROL & MONITORING Fig. 1. Block diagram of the Hygen load-adaptive adjustable-speed electricity generating and power supply system. a) ENGINE GENERATOR RECTIFIER Pe b) DC/AC INVERTER Pl=Pe DC/AC INVERTER Pl=Pb LOAD LOAD Pb BATTERY STORAGE c) ENGINE GENERATOR RECTIFIER Pe DC/AC INVERTER Pl=Pe-Pb LOAD Pb BATTERY STORAGE d) ENGINE GENERATOR RECTIFIER Pe DC/AC INVERTER Pl=Pe+Pb Pb BATTERY STORAGE Fig. 2. Power flow of the Hygen system a) b) c) d) S1 - Load powered from the engine, S2 - Load powered form the battery, S3 – Load and battery powered from the engine, S4 – Load powered from the engine and from the battery LOAD Ti1 TORQUE Tr1 Th P3 P2 F1 F2>F1 Tp F3>F2 P1 F4>F3 F5>F4 SPEED ωmax ωmin Fig. 3. Torque vs. speed for the Hygen system with specific fuel consumption contours. OUTPUT POWER TOTAL POWER Pl =Pb + Pe Pe2 + Pb2 Pe2 Pe1 + Pb2 GENERATOR POWER Pe BATTERY POWER Pb2 Pe1 Pb2 Pb1 SPEED ωmin ωmax Fig. 4. Output power vs. speed for Hygen with battery support. ENGINE TORQUE Ti2 Tr2 P4 Ti1 Tr1 Th TA P3 P5 P2 P6 P1 P7 Tv TC1 TC2 SPEED ωmin SPEED RANGE ωmax Fig. 5. Torque vs. speed for constant speed generators, variable speed generators and the Hygen system. ENGINE PM ALTERNATOR S RECTIFIER INVERTER 110V 60Hz N SPEED Fig. 6. Block diagram for manually-adjusted speed and load-following variable speed systems. Hygen power curve with programmable torque control ……… Net intermittent power…………………………………………. Variable-speed………………………………………………..... Engine rated power ……………………………………………. Load levels……………………………………………………... Specific fuel consumption contours……………………………. Maximum continuous power…………………………………... Fig. 7. Power vs. speed for constant-speed generators, variable-speed generators and the Hygen system. a) 0.35% b) 0.30% 0.25% 0.20% 0.15% 0.10% 0.05% 0.00% 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Fig. 8. Output voltage for no-load operation a) Voltage waveform. b) Harmonic spectrum of the output voltage. a) VOLTAGE CURRENT 1.60% b) 1.40% 1.20% 1.00% 0.80% 0.60% 0.40% 0.20% 0.00% 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Fig. 9. Output voltage and current for 20 kW resistive load (overload) a) Voltage and current waveform. b) Harmonic spectrum of output voltage. a) VOLTAGE CURRENT 0.35% b) 0.30% 0.25% 0.20% 0.15% 0.10% 0.05% 0.00% 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Fig.10. Output voltage and current for a highly inductive load of 12 kVA (cos φ = 0.1564 ) a) Voltage and current waveform b) Harmonic spectrum of the output voltage. VOLTAGE CURRENT Fig. 11. Output voltage and load current – Resistive step load – 14 kW. VOLTAGE CURRENT Fig. 12. Hygen H3011A – Output voltage and load current – Impact load of 2,5 kW induction motor coupled to an air compressor unit.