Gratitude In appreciation and gratitude to The Custodian of the Two Holy Mosques King Abdullah Bin Abdul Aziz Al Saud And H.R.H. Prince Sultan Bin Abdul Aziz Al Saud Crown Prince, Deputy Premier, Minister of Defence & Aviation and Inspector General For their continuous support and gracious consideration, the Saudi Building Code National Committee (SBCNC) is honored to present the first issue of the Saudi Building Code (SBC). Saudi Building Code Requirements 201 301 302 303 304 305 306 401 501 Architectural Structural – Loading and Forces Structural – Testing and Inspection Structural – Soil and Foundations Structural – Concrete Structures Structural – Masonry Structures Structural – Steel Structures Electrical Mechanical 601 701 Energy Conservation 901 Existing Buildings 801 SBC 801 Sanitary Fire Protection 2007 PREFACE PREFACE The Saudi Building Code (SBC) is a set of legal, administrative and technical regulations and requirements that specify the minimum standards of construction for building in order to ensure public safety and health. A Royal Decree dated 11th June 2000 order the formation of a national committee composed of representatives of Saudi universities and governmental and private sectors. In September 2001, the Council of Ministers approved the general plan of the National Committee to develop a national building code for the Kingdom of Saudi Arabia. To choose a base code for the Saudi Building Code, a number of Codes have been studied. The National Committee has been acquainted with the results of the national researches and the international codes from the U.S.A., Canada and Australia, also, the European Code, and Arab Codes. It has also sought the opinions of specialists in relevant Saudi universities, governmental and private sectors through holding a questionnaire, a symposium and specialized workshops, in the light of which, (ICC) has been chosen to be a base code for the Saudi Building Code. The International Code Council (ICC) grants permission to the Saudi Building Code National Committee (SBCNC) to include all or any portion of material from the ICC codes, and standards in the SBC and ICC is not responsible or liable in any way to SBCNC or to any other party or entity for any modifications or changes that SBCNC makes to such documents. Toward expanding the participation of all the specialists in the building and construction industry in the Kingdom through the governmental and private sectors, the universities and research centers, the National Committee took its own decisions related to code content by holding specialized meetings, symposiums and workshops and by the help of experts from inside and outside of Saudi Arabia. The technical committees and sub-committees started their work in April 2003 to develop the Saudi Building Code that adapts the base code with the social and cultural environment, the natural and climatic conditions, types of soil and properties of materials in the Kingdom. The Saudi Building Code Fire Protection Requirements (SBC 801) was based on the International Fire Code (IFC) 2003 edition, beside the materials published by the National Fire Protection Association (NFPA). NFPA allow the Saudi Building Code National committee (SBCNC) to utilize (NFPA) codes and standards as reference documents in part or in full. The development process of SBC 801 followed the methodology approved by the Saudi Building Code National Committee. Many changes and modifications were made on the base code and only SI units were used throughout the Code. The changes were intended to compose a comprehensive set of provisions, to the best possible extent, for materials, environmental conditions, and construction practices prevailing in the Kingdom. SBC 801 2007 Preface / 1 NATIONAL COMMITTEE The Saudi Building Code National Committee Mohammad H. Al-Nagadi, MSc. Chairman Mohammad S. Al-Haddad, PhD. Vice Chairman Nabil A. Molla, MSc. Member Khalid M. Qattan, PhD. Member Abdul-Ghani H. Al-Harbi, BSc. Member Ahmad A. Al-Yousef, BSc. Member Tamim A. Samman, PhD. Member Rajeh Z. Al-Zaid, PhD. Member Mustafa Y. Al-Mandil, PhD. Member Tariq M. Nahhas, PhD. Member Ali O. Al-Zaid, BSc. Member Ministry of Municipal and Rural Affairs King Abdul-Aziz City for Science and Technology Saudi Arabian Standards Organization Ministry of Interior Ministry of Transportation Ministry of Water and Electricity King Abdul-Aziz University King Saud University King Fahd University of Petroleum and Minerals Umm Al-Qura University Council of Saudi Chambers of Commerce and Industry Former Members of the Saudi Building Code National Committee Khalid Y. Al-Khalaf, PhD. Saudi Arabian Standards Organization Chairman 1423 up to 1426H Abdul-Aziz A. Al-Abdul-Karim, BSc. Member Ahmad A. Al-Johdali, BSc. Member Ministry of Municipal and Rural Affairs Ministry of Transportation SBC 801 2007 National Committee/1 CONSULTATIVE COMMITTEE The Consultative Committee � Ali O. Al-Zaid, BSc. Member of the Saudi Building Code National Committee Chairman Rajeh Z. Al-Zaid, PhD. Vice Chairman Siraj M. Mas'oudi, MSc. Member Mustafa Y. Al-Mandil, PhD. Member Ali A. Shash, PhD. Member Abdul-Rahman A. Al-Tassan, PhD. Member Ahmad B. Al-Shuraim, PhD. Member Abdul-Hameed A. Al-Ohaly, PhD. Member Ala'uddin Shibl, PhD. Member Ibrahim S. Al-Jadhai, PhD. Member Abdullah I. Al-Boeis, BSc. Member Tariq A. Al-Khalifa, PhD. Member Member of the Saudi Building Code National Committee Saudi Arabian Standards Organization Member of the Saudi Building Code National Committee Head of the Administrative and Legal Technical Committee Head of the Architectural Technical Committee Head of the Structural Technical Committee Head of the Electrical Technical Committee Head of the Mechanical Technical Committee Head of the Sanitary Technical Committee Head of the Fire Protection Technical Committee Head of the Seismic Requirements Technical Committee Secretariat General of the Saudi Building Code National Committee Mohammad A. Bin-Hussien, PhD. Former Secretary Mohammed G. Al-Najrani, BSc. Acting Secretary Fuad A. Bukhari, Arch. Coordinator Former Secretary General Acting Secretary General Director of Technical Affairs – SBCNC SBC 801 2007 Consultative Committee /1 TECHNICAL COMMITTEE The Technical Committee for Fire Protection � Abdullah I. Al-Boiez, BSc. Chairman Gharman H. Shehri, BSc. Member Mohammed A. Al-Nahari, BSc. Colonel. Member Saad M. Al-Bishry, BSc. Captain. Member Sa’eed M. Al-Zahrani, PhD. Member Tawfik I. Al-Juraid, BSc. Member Sultan A. Al-Sultan, BSc. Member Mohammed A. Al-Amry, BSc. Member Fuad A. Bukhari, Arch. Coordinator King Abdul-Aziz City for Science and Technology Supreme Commission of Industrial Safety and Security General Administration of Civil Defence General Administration of Civil Defence King Saud University Saudi Arabian Standards Organization Saudi Aramco Industrial Development Fund Saudi Building Code National Committee SBC 801 2007 Consultative Committee /1 CONTENTS TABLE OF CONTENTS DEFINITIONS CHAPTER 1: Section 1.1 General 1.2 General Definitions CHAPTER 2: Section 2A 2A.1 2A.2 2A.3 2A.4 2A.5 2A.6 2A.7 2A.8 2A.9 2A.10 2A.11 2A.12 2B 2B.1 2B.2 2B.3 2B.4 2B.5 2B.6 2B.7 2B.8 2B.9 2B.10 2B.11 2B.12 2B.13 2B.14 2B.15 2B.16 2B.17 2B.18 USE AND OCCUPANCY CLASSIFICATION AND SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY Use and Occupancy Classification General Classification Assembly Group A Business Group B Educational Group E Factory Group F High-Hazard Group H Institutional Group I Mercantile Group M Residential Group R Storage Group S Utility and Miscellaneous Group U Special Detailed Requirements Based on Use and Occupancy Scope Covered Mall Buildings High-Rise Buildings Atriums Underground Buildings Motor-Vehicle-Related Occupancies Group I-2 Group I-3 Motion Picture Projection Rooms Stages and Platforms Special Amusement Buildings Aircraft-Related Occupancies Combustible Storage Hazardous Materials Groups H-1, H-2, H-3, H-4 and H-5 Application of Flammable Finishes Drying Rooms Organic Coatings CHAPTER 3: GENERAL BUILDING HEIGHTS AND AREAS Section 3.1 General 3.2 Definitions 3.3 General Height and Area Limitations 3.4 Height Modifications 3.5 Mezzanines SBC 801 2007 Contents/1 CONTENTS 3.6 3.7 3.8 CHAPTER 4: Section 4A 4A.1 4A.2 4A.3 4B 4B.1 4B.2 4B.3 4B.4 4B.5 4B.6 4B.7 4B.8 4B.9 4B.10 4B.11 4B.12 4B.13 4B.14 4B.15 4B.16 4B.17 4B.18 4B.19 4B.20 4B.21 CHAPTER 5: Section 5A 5A.1 5A.2 5A.3 5A.4 5A.5 5A.6 5A.7 5A.8 5A.9 5A.10 5A.11 5A.12 5A.13 SBC 801 Area Modifications Unlimited Area Buildings Special Provisions TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Types of Construction General Construction Classification Combustible Materials in Types I and II Construction Fire-Resistance-Rated Construction General Definitions Fire-Resistance Ratings and Fire Tests Exterior Walls Fire Walls Fire Barriers Shaft Enclosures Fire Partitions Smoke Barriers Smoke Partitions Horizontal Assemblies Penetrations Fire-resistant Joint Systems Fire-resistance Rating of Structural Members Opening Protectives Ducts and Air Transfer Openings Concealed Spaces Fire-resistance Requirements for Plaster Thermal- and Sound-Insulating Materials Prescriptive Fire Resistance Calculated Fire Resistance GENERAL PRECAUTIONS AGAINST FIRE, EMERGENCY PLANNING AND PREPAREDNESS, FIRE SERVICE FEATURES BUILDING SERVICES AND SYSTEMS General Precautions Against Fire General Definitions Asphalt Kettles Combustible Waste Material Ignition Sources Motion Picture Film and Screens Open Burning and Recreational Fires Open Flames Powered Industrial Trucks Smoking Vacant Premises Vehicle Impact Protection Fueled Equipment 2007 Contents/2 CONTENTS 5A.14 5A.15 5B 5B.1 5B.2 5B.3 5B.4 5B.5 5B.6 5B.7 5B.8 5C 5C.1 5C.2 5C.3 5C.4 5C.5 5C.6 5C.7 5C.8 5C.9 5C.10 5D 5D.1 5D.2 5D.3 5D.4 5D.5 5D.6 5D.7 5D.8 5D.9 5D.10 CHAPTER 6: Section 6.1 6.2 6.3 6.4 6.5 6.6 Indoor Displays Miscellaneous Combustible Materials Storage Emergency Planning and Preparedness General Definitions Public Assemblages and Events Fire Safety and Evacuation Plans Emergency Evacuation Drills Employee Training and Response Procedures Hazard Communication Use and Occupancy-Related Requirements Fire Service Features General Definitions Fire Apparatus Access Roads Access to Building Openings and Roofs Premises Identification Key Boxes Hazards to Fire Fighters Fire Protection Water Supplies Fire Command Center Civil Defence Access to Equipment Building Services and Systems General Definitions Fuel-Fired Appliances Emergency and Standby Power Systems Electrical Equipment, Wiring and Hazards Mechanical Refrigeration Elevator Recall and Maintenance Stationary Lead-Acid Battery Systems Valve-Regulated Lead-Acid (VRLA) Battery Systems Commercial Kitchen Hoods INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS General Definitions Furnishings Decorative Vegetation Decorations and Trim Interior Finish and Decorative Materials CHAPTER 7: FIRE PROTECTION SYSTEMS Section 7.1 General 7.2 Definitions 7.3 Automatic Sprinkler Systems 7.4 Alternative Automatic Fire-Extinguishing Systems 7.5 Standpipe Systems 7.6 Portable Fire Extinguishers SBC 801 2007 Contents/3 CONTENTS 7.7 7.8 7.9 7.10 7.11 7.12 7.13 Fire Alarm and Detection Systems Emergency Alarm Systems Smoke Control Systems Smoke and Heat Vents Explosion Control Civil Defence Connections Fire Pumps CHAPTER 8: MEANS OF EGRESS Section 8.1 General 8.2 Definitions 8.3 General Means of Egress 8.4 Occupant Load 8.5 Egress Width 8.6 Means of Egress Illumination 8.7 Accessible Means of Egress 8.8 Doors, Gates and Turnstiles 8.9 Stairways and Handrails 8.10 Ramps 8.11 Exit Signs 8.12 Guards 8.13 Exit Access 8.14 Exit and Exit Access Doorways 8.15 Exit Access Travel Distance 8.16 Corridors 8.17 Exits 8.18 Number of Exits and Continuity 8.19 Vertical Exit Enclosures 8.20 Exit Passageways 8.21 Horizontal Exits 8.22 Exterior Exit Ramps and Stairways 8.23 Exit Discharge 8.24 Assembly 8.25 Emergency Escape and Rescue 8.26 Means of Egress for Existing Buildings 8.27 Maintenance of the Means of Egress CHAPTER 9: EXISTING STRUCTURES Section 9.1 General 9.2 Definitions 9.3 Additions, Alterations or Repairs 9.4 Fire Escapes 9.5 Glass Replacement 9.6 Change of Occupancy 9.7 Historic Buildings 9.8 Moved Structures 9.9 Accessibility for Existing Buildings 9.10 Compliance Alternatives SBC 801 2007 Contents/4 CONTENTS CHAPTER 10: FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION Section 10.1 General 10.2 Definitions 10.3 Temporary Heating Equipment 10.4 Precautions Against Fire 10.5 Flammable and Combustible Liquids 10.6 Flammable Gases 10.7 Explosive Materials 10.8 Owner’s Responsibility for Fire Protection 10.9 Fire Alarm Reporting 10.10 Access for Fire Fighting 10.11 Means of Egress 10.12 Water Supply for Fire Protection 10.13 Standpipes 10.14 Automatic Sprinkler System 10.15 Portable Fire Extinguishers 10.16 Motorized Equipment 10.17 Safeguarding Roofing Operations CHAPTER 11: AVIATION FACILITIES Section 11.1 General 11.2 Definitions 11.3 General Precautions 11.4 Aircraft Maintenance 11.5 Portable Fire Extinguishers 11.6 Aircraft Fueling 11.7 Helistops and Heliports CHAPTER 12: FLAMMABLE FINISHES Section 12.1 General 12.2 Definitions 12.3 Protection of Operations 12.4 Spray Finishing 12.5 Dipping Operations 12.6 Electrostatic Apparatus 12.7 Powder Coating 12.8 Automobile Undercoating 12.9 Organic Peroxides and Dual-Component Coatings 12.10 Floor Surfacing and Finishing Operations 12.11 Indoor Manufacturing of Reinforced Plastics 12.12 Combustible Dust-Producing Operations 12.12.1 General 12.12.2 Definitions 12.12.3 Precautions 12.12.4 Explosion Protection SBC 801 2007 Contents/5 CONTENTS CHAPTER 13: DRY CLEANING Section 13.1 General 13.2 Definitions 13.3 Classifications 13.4 General Requirements 13.5 Operating Requirements 13.6 Spotting and Pretreating 13.7 Dry Cleaning Systems 13.8 Fire Protection CHAPTER 14: FRUIT AND CROP RIPENING Section 14.1 General 14.2 Definitions 14.3 Ethylene Gas 14.4 Sources of Ignition 14.5 Combustible Waste 14.6 Ethylene Generators 14.7 Warning Signs CHAPTER 15: FUMIGATION AND THERMAL INSECTICIDAL FOGGING Section 15.1 General 15.2 Definitions 15.3 Fire Safety Requirements CHAPTER 16: SEMICONDUCTOR FABRICATION FACILITIES Section 16.1 General 16.2 Definitions 16.3 General Safety Provisions 16.4 Storage 16.5 Use and Handling CHAPTER 17: LUMBER YARDS AND WOODWORKING FACILITIES Section 17.1 General 17.2 Definitions 17.3 General Requirements 17.4 Fire Protection 17.5 Plywood, Veneer and Composite Board Mills 17.6 Log Storage Areas 17.7 Storage of Wood Chips and Hogged Material Associated With Timber and Lumber Production Facilities 17.8 Storage and Processing of Wood Chips, Hogged Material, Fines, Compost and Raw Product Associated with Yard Waste and Recycling Facilities 17.9 Exterior Storage of Finished Lumber Products SBC 801 2007 Contents/6 CONTENTS CHAPTER 18: MANUFACTURE OF ORGANIC COATINGS Section 18.1 General 18.2 Definitions 18.3 General Precautions 18.4 Electrical Equipment and Protection 18.5 Process Structures 18.6 Process Mills and Kettles 18.7 Process Piping 18.8 Raw Materials in Process Areas 18.9 Raw Materials and Finished Products CHAPTER 19: INDUSTRIAL OVENS Section 19.1 General 19.2 Definitions 19.3 Location 19.4 Fuel Piping 19.5 Interlocks 19.6 Fire Protection 19.7 Operation and Maintenance CHAPTER 20: Section 20.1 20.2 20.3 20.4 20.5 20.6 20.7 20.8 20.9 20.10 20.11 MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES General Definitions Location of Dispensing Devices Dispensing Operations Operational Requirements Flammable and Combustible Liquid Motor Fuel-Dispensing Facilities Liquefied Petroleum Gas Motor Fuel-Dispensing Facilities Compressed Natural Gas Motor Fuel-Dispensing Facilities Hydrogen Motor Fuel-Dispensing and Generation Facilities Marine Motor Fuel-Dispensing Facilities Repair Garages CHAPTER 21: HIGH-PILED COMBUSTIBLE STORAGE Section 21.1 General 21.2 Definitions 21.3 Commodity Classification 21.4 Designation of High-Piled Storage Areas 21.5 Housekeeping and Maintenance 21.6 General Fire Protection and Life Safety Features 21.7 Solid-Piled and Shelf Storage 21.8 Rack Storage 21.9 Automated Storage 21.10 Specialty Storage SBC 801 2007 Contents/7 CONTENTS CHAPTER 22: TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES Section 22.1 General 22.2 Definitions 22.3 Temporary Tents, Canopies and Membrane Structures 22.4 Temporary and Permanent Tents, Canopies and Membrane Structures CHAPTER 23: TIRE REBUILDING AND TIRE STORAGE Section 23.1 General 23.2 Definitions 23.3 Tire Rebuilding 23.4 Precautions Against Fire 23.5 Outdoor Storage 23.6 Civil Defence Access 23.7 Fencing 23.8 Fire Protection 23.9 Indoor Storage Arrangement CHAPTER 24: WELDING AND OTHER HOT WORK Section 24.1 General 24.2 Definitions 24.3 General Requirements 24.4 Fire Safety Requirements 24.5 Gas Welding and Cutting 24.6 Electric Arc Hot Work 24.7 Calcium Carbide Systems 24.8 Acetylene Generators 24.9 Piping Manifolds and Hose Systems for Fuel Gases and Oxygen CHAPTER 25: HAZARDOUS MATERIALS—GENERAL PROVISIONS Section 25.1 General 25.2 Definitions 25.3 General Requirements 25.4 Storage 25.5 Use, Dispensing and Handling CHAPTER 26: AEROSOLS Section 26.1 General 26.2 Definitions 26.3 Classification of Aerosol Products 26.4 Inside Storage of Aerosol Products 26.5 Outside Storage 26.6 Retail Display 26.7 Manufacturing Facilities SBC 801 2007 Contents/8 CONTENTS CHAPTER 27: COMBUSTIBLE FIBERS Section 27.1 General 27.2 Definitions 27.3 General Precautions 27.4 Loose Fiber Storage 27.5 Baled Storage CHAPTER 28: COMPRESSED GASES Section 28.1 General 28.2 Definitions 28.3 General Requirements 28.4 Storage of Compressed Gases 28.5 Use and Handling of Compressed Gases 28.6 Medical Gas Systems 28.7 Compressed Gases Not Otherwise Regulated CHAPTER 29: CORROSIVE MATERIALS Section 29.1 General 29.2 Definitions 29.3 General Requirements 29.4 Storage 29.5 Use CHAPTER 30: CRYOGENIC FLUIDS Section 30.1 General 30.2 Definitions 30.3 General Requirements 30.4 Storage 30.5 Use and Handling CHAPTER 31: EXPLOSIVES AND FIREWORKS Section 31.1 General 31.2 Definitions 31.3 Record Keeping and Reporting 31.4 Explosive Materials Storage and Handling 31.5 Manufacture, Assembly and Testing of Explosives, Explosive Materials and Fireworks 31.6 Small Arms Ammunition 31.7 Blasting 31.8 Fireworks Display CHAPTER 32: FLAMMABLE AND COMBUSTIBLE LIQUIDS Section 32.1 General 32.2 Definitions 32.3 General Requirements 32.4 Storage SBC 801 2007 Contents/9 CONTENTS 32.5 32.6 Dispensing, Use, Mixing and Handling Special Operations CHAPTER 33: FLAMMABLE GASES Section 33.1 General 33.2 Definitions 33.3 General Requirements 33.4 Storage 33.5 Use CHAPTER 34: FLAMMABLE SOLIDS Section 34.1 General 34.2 Definitions 34.3 General Requirements 34.4 Storage 34.5 Use 34.6 Magnesium CHAPTER 35: HIGHLY TOXIC AND TOXIC MATERIALS Section 35.1 General 35.2 Definitions 35.3 Highly Toxic and Toxic Solids and Liquids 35.4 Highly Toxic and Toxic Compressed Gases 35.5 Ozone Gas Generators CHAPTER 36: LIQUEFIED PETROLEUM GASES Section 36.1 General 36.2 Definitions 36.3 Installation of Equipment 36.4 Location of Containers 36.5 Prohibited Use of LP-Gas 36.6 Dispensing and Overfilling 36.7 Safety Precautions and Devices 36.8 Fire Protection 36.9 Storage of Portable LP-Gas Containers Awaiting Use or Resale 36.10 Containers Not in Service 36.11 Parking and Garaging CHAPTER 37: ORGANIC PEROXIDES Section 37.1 General 37.2 Definitions 37.3 General Requirements 37.4 Storage 37.5 Use SBC 801 2007 Contents/10 CONTENTS CHAPTER 38: OXIDIZERS Section 38.1 General 38.2 Definitions 38.3 General Requirements 38.4 Storage 38.5 Use CHAPTER 39: PYROPHORIC MATERIALS Section 39.1 General 39.2 Definitions 39.3 General Requirements 39.4 Storage 39.5 Use 39.6 Silane Gas CHAPTER 40: PYROXYLIN (CELLULOSE NITRATE) PLASTICS Section 40.1 General 40.2 Definitions 40.3 General Requirements 40.4 Storage and Handling CHAPTER 41: UNSTABLE (REACTIVE) MATERIALS Section 41.1 General 41.2 Definitions 41.3 General Requirements 41.4 Storage 41.5 Use CHAPTER 42: WATER-REACTIVE SOLIDS AND LIQUIDS Section 42.1 General 42.2 Definitions 42.3 General Requirements 42.4 Storage 42.5 Use APPENDIX A REFERENCED STANDARDS APPENDIX B FIRE-FLOW REQUIREMENTS FOR BUILDINGS Section B1 General B2 Definitions B3 Modifications B4 Fire Area B5 Fire-Flow Requirements for Buildings SBC 801 2007 Contents/11 CONTENTS APPENDIX C FIRE HYDRANT LOCATIONS AND DISTRIBUTION Section C1 General C2 Location C3 Number of Fire Hydrants C4 Consideration of Existing Fire Hydrants C5 Distribution of Fire Hydrants APPENDIX D FIRE APPARATUS ACCESS ROADS Section D1 General D2 Required Access D3 Minimum Specifications D4 Commercial and Industrial Developments D5 Aerial Fire Apparatus Access Roads D6 Multiple-Family Residential Developments D7 One- or Two-Family Residential Developments APPENDIX E HAZARD CATEGORIES Section E1 General E2 Hazard Categories E3 Evaluation of Hazards APPENDIX F HAZARD RANKING Section F1 General F2 Referenced Standards APPENDIX G Section G1 SBC 801 CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS General 2007 Contents/12 DEFINITIONS CHAPTER 1 DEFINITIONS SECTION 1.1 GENERAL 1.1.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the purposes of these code requirements, have the meanings shown in this chapter. 1.1.2 Interchangeability. Words used in the present tense include the future; words stated in the masculine gender include the feminine and neuter; the singular number includes the plural and the plural, the singular. 1.1.3 Terms defined in other codes. Where terms are not defined in these code requirements and are defined in the SBC 201, SBC 501 or SBC 701, such terms shall have the meanings ascribed to them as in those code requirements. 1.1.4 Terms not defined. Where terms are not defined through the methods authorized by this section, such terms shall have ordinarily accepted meanings such as the context implies. Webster’s Third New International Dictionary of the English Language, Unabridged, shall be considered as providing ordinarily accepted meanings. SECTION 1.2 GENERAL DEFINITIONS ACCESSIBLE MEANS OF EGRESS. See Section 8.2.1. AEROSOL. See Section 26.2.1. Level 1 aerosol products. See Section 26.2.1. Level 2 aerosol products. See Section 26.2.1. Level 3 aerosol products. See Section 26.2.1. AEROSOL CONTAINER. See Section 26.2.1. AEROSOL WAREHOUSE. See Section 26.2.1. AGENT. A person who shall have charge, care or control of any structure as owner, or agent of the owner, or as executor, executrix, administrator, administratrix, trustee or guardian of the estate of the owner. Any such person representing the actual owner shall be bound to comply with the provisions of these code requirements to the same extent as if that person was the owner. AIR-SUPPORTED STRUCTURE. See Section 22.2.1. AIRCRAFT OPERATION AREA (AOA). See Section 11.2.1. AIRPORT. See Section 11.2.1. AISLE ACCESSWAY. See Section 8.2.1. SBC 801 2007 1/1 DEFINITIONS ALARM NOTIFICATION APPLIANCE. See Section 7.2.1. ALARM SIGNAL. See Section 7.2.1. ALARM VERIFICATION FEATURE. See Section 7.2.1. ALTERNATING TREAD DEVICE. See Section 8.2.1. AMMONIUM NITRATE. See Section 31.2.1. ANNUNCIATOR. See Section 7.2.1. APPROVED. Acceptable to the Building code official. AREA OF REFUGE. See Section 8.2.1. ARRAY. See Section 21.2.1. ARRAY, CLOSED. See Section 21.2.1. AUDIBLE ALARM NOTIFICATION APPLIANCE. See Section 7.2.1. AUTOMATIC. See Section 7.2.1. AUTOMATIC FIRE-EXTINGUISHING SYSTEM. See Section 7.2.1. AUTOMATIC SPRINKLER SYSTEM. See Section 7.2.1. AUTOMOTIVE MOTOR FUEL-DISPENSING FACILITY. See Section 20.2.1. AVERAGE AMBIENT SOUND LEVEL. See Section 7.2.1. BARRICADE. See Section 31.2.1. Artificial barricade. See Section 31.2.1. Natural barricade. See Section 31.2.1. BARRICADED. See Section 31.2.1. BATTERY, LEAD ACID. See Section 5D.2.1. BATTERY SYSTEM, STATIONARY LEAD ACID. See Section 5D.2.1. BIN BOX. See Section 21.2.1. BLAST AREA. See Section 31.2.1. BLAST SITE. See Section 31.2.1. BLASTER. See Section 31.2.1. SBC 801 2007 1/2 DEFINITIONS BLASTING AGENT. See Section 31.2.1. BLEACHERS. See Section 8.2.1. BOILING POINT. See Section 25.2.1. BONFIRE. See Section 5A.2.1. BRITISH THERMAL UNIT (BTU). The heat necessary to raise the temperature of 0.454 kg of water by 0.5565°C. BULK OXYGEN SYSTEM. See Section 38.2.1. BULK PLANT OR TERMINAL. See Section 32.2.1. BULK TRANSFER. See Section 32.2.1. BULLET RESISTANT. See Section 31.2.1. CANOPY. See Section 22.2.1. CARBON DIOXIDE EXTINGUISHING SYSTEM. See Section 7.2.1. CARTON. A cardboard or fiberboard box enclosing a product. CEILING LIMIT. See Section 25.2.1. CHEMICAL. See Section 25.2.1. CHEMICAL NAME. See Section 25.2.1. CLEAN AGENT. See Section 7.2.1. CLOSED CONTAINER. See Section 25.2.1. CLOSED SYSTEM. The use of a solid or liquid hazardous material involving a closed vessel or system that remains closed during normal operations where vapors emitted by the product are not liberated outside of the vessel or system and the product is not exposed to the atmosphere during normal operations; and all uses of compressed gases. Examples of closed systems for solids and liquids include product conveyed through a piping system into a closed vessel, system or piece of equipment. COLD DECK. See Section 17.2.1. COMBUSTIBLE DUST. See Section 12.2.1. COMBUSTIBLE FIBERS. See Section 27.2.1. COMBUSTIBLE LIQUID. See Section 32.2.1. Class II. See Section 32.2.1. SBC 801 2007 1/3 DEFINITIONS Class IIIA. See Section 32.2.1. Class IIIB. See Section 32.2.1. COMMERCIAL COOKING APPLIANCES. See Section 5D.2.1. COMMODITY. See Section 21.2.1. COMMON PATH OF EGRESS TRAVEL. See Section 8.2.1. COMPRESSED GAS. See Section 28.2.1. COMPRESSED GAS CONTAINER. See Section 28.2.1. COMPRESSED GAS SYSTEM. See Section 28.2.1. CONSTANTLY ATTENDED LOCATION. See Section 7.2.1. CONSTRUCTION DOCUMENTS. The written, graphic and pictorial documents prepared or assembled for describing the design, location and physical characteristics of the elements of the project necessary for obtaining a permit. CONTAINER. See Section 25.2.1. CONTAINMENT SYSTEM. See Section 35.2.1. CONTAINMENT VESSEL. See Section 35.2.1. CONTINUOUS GAS DETECTION SYSTEM. See Section 16.2.1. CONTROL AREA. See Section 25.2.1. CORRIDOR. See Section 8.2.1. CORROSIVE. See Section 29.2.1. CRYOGENIC CONTAINER. See Section 30.2.1. CRYOGENIC FLUID. See Section 30.2.1. CRYOGENIC VESSEL. See Section 30.2.1. CYLINDER. See Section 25.2.1. DEFLAGRATION. See Section 25.2.1. DELUGE SYSTEM. See Section 7.2.1. DESIGN PRESSURE. See Section 25.2.1. DETACHED BUILDING. See Section 25.2.1. SBC 801 2007 1/4 DEFINITIONS DETEARING. See Section 12.2.1. DETECTOR, HEAT. See Section 7.2.1. DETONATING CORD. See Section 31.2.1. DETONATION. See Section 31.2.1. DETONATOR. See Section 31.2.1. DIP TANK. See Section 12.2.1. DISCHARGE SITE. See Section 31.2.1. DISPENSING. See Section 25.2.1. DISPENSING DEVICE, OVERHEAD TYPE. See Section 20.2.1. DISPLAY SITE. See Section 31.2.1. DOOR, BALANCED. See Section 8.2.1. DRAFT CURTAIN. See Section 21.2.1. DRY-CHEMICAL EXTINGUISHING AGENT. See Section 7.2.1. DRY CLEANING. See Section 13.2.1. DRY CLEANING PLANT. See Section 13.2.1. DRY CLEANING ROOM. See Section 13.2.1. DRY CLEANING SYSTEM. See Section 13.2.1. EARLY SUPPRESSION FAST-RESPONSE (ESFR) SPRINKLER. See Section 21.2.1. EGRESS COURT. See Section 8.2.1. ELECTROSTATIC FLUIDIZED BED. See Section 12.2.1. EMERGENCY ALARM SYSTEM. See Section 7.2.1. EMERGENCY CONTROL STATION. See Section 16.2.1. EMERGENCY ESCAPE AND RESCUE OPENING. See Section 8.2.1. EMERGENCY EVACUATION DRILL. See Section 5B2.1. EMERGENCY VOICE/ALARM COMMUNICATIONS. See Section 7.2.1. SBC 801 2007 1/5 DEFINITIONS EXCESS FLOW CONTROL. See Section 25.2.1. EXCESS FLOW VALVE. See Section 35.2.1. EXHAUSTED ENCLOSURE. See Section 25.2.1. EXISTING. Buildings, facilities or conditions which are already in existence, constructed or officially authorized prior to the adoption of these code requirements. EXIT. See Section 8.2.1. EXIT ACCESS. See Section 8.2.1. EXIT DISCHARGE. See Section 8.2.1. EXIT DISCHARGE, LEVEL OF. See Section 8.2.1. EXIT ENCLOSURE. See Section 8.2.1. EXIT, HORIZONTAL. See Section 8.2.1. EXIT PASSAGEWAY. See Section 8.2.1. EXPANDED PLASTIC. See Section 21.2.1. EXPLOSION. See Section 25.2.1. EXPLOSIVE. See Section 31.2.1. High Explosive. See Section 31.2.1. Low Explosive. See Section 31.2.1. Mass-detonating Explosives. See Section 31.2.1. MOI (UN/DOTn) Class 1 Explosives. See Section 31.2.1. Division 1.1. See Section 31.2.1. Division 1.2. See Section 31.2.1. Division 1.3. See Section 31.2.1. Division 1.4. See Section 31.2.1. Division 1.5. See Section 31.2.1. Division 1.6. See Section 31.2.1. EXPLOSIVE MATERIAL. See Section 31.2.1. EXTRA-HIGH-RACK COMBUSTIBLE STORAGE. See Section 21.2.1. FABRICATION AREA. See Section 16.2.1. FACILITY. A building or use in a fixed location including exterior storage areas for flammable and combustible substances and hazardous materials, piers, wharves, tank farms and similar uses. This term includes recreational vehicles, mobile home and manufactured housing parks, sales and storage lots. SBC 801 2007 1/6 DEFINITIONS FALLOUT AREA. See Section 31.2.1. FALSE ALARM. The willful and knowing initiation or transmission of a signal, message or other notification of an event of fire when no such danger exists. FINES. See Section 17.2.1. FIRE ALARM. The giving, signaling or transmission to any public fire station, or company or to any officer or employee thereof, whether by telephone, spoken word or otherwise, of information to the effect that there is a fire at or near the place indicated by the person giving, signaling, or transmitting such information. FIRE ALARM BOX, MANUAL. See Section 7.2.1. FIRE ALARM CONTROL UNIT. See Section 7.2.1. FIRE ALARM SIGNAL. See Section 7.2.1. FIRE ALARM SYSTEM. See Section 7.2.1. FIRE APPARATUS ACCESS ROAD. See Section 5C.2.1. FIRE AREA. See Section 7.2.1. FIRE CHIEF. The chief officer of the Civil Defence serving the jurisdiction, or a duly authorized representative. BUILDING CODE OFFICIAL. Designated authority charged with the administration and enforcement of the code, or a duly authorized representative. FIRE COMMAND CENTER. See Section 5C.2.1. CIVIL DEFENCE MASTER KEY. See Section 5C.2.1. FIRE DETECTOR, AUTOMATIC. See Section 7.2.1. FIRE DOOR ASSEMBLY. Any combination of a fire door, frame, hardware, and other accessories that together provide a specific degree of fire protection to the opening. FIRE EXIT HARDWARE. See Section 8.2.1. FIRE LANE. See Section 5C.2.1. FIRE PARTITION. A vertical assembly of materials designed to restrict the spread of fire in which openings are protected. FIRE POINT. See Section 32.2.1. FIRE PROTECTION SYSTEM. See Section 7.2.1. SBC 801 2007 1/7 DEFINITIONS FIRE SAFETY FUNCTIONS. See Section 7.2.1. FIREWATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the Civil Defence. FIREWORKS. See Section 31.2.1. Fireworks, 1.4G. See Section 31.2.1. Fireworks, 1.3G. See Section 31.2.1. FIREWORKS DISPLAY. See Section 31.2.1. FLAMMABLE CRYOGENIC FLUID. See Section 30.2.1. FLAMMABLE FINISHES. See Section 12.2.1. FLAMMABLE GAS. See Section 33.2.1. FLAMMABLE LIQUEFIED GAS. See Section 33.2.1. FLAMMABLE LIQUID. See Section 32.2.1. Class IA. See Section 32.2.1. Class IB. See Section 32.2.1. Class IC. See Section 32.2.1. FLAMMABLE MATERIAL. A material capable of being readily ignited from common sources of heat or at a temperature of 316oC or less. FLAMMABLE SOLID. See Section 34.2.1. FLAMMABLE VAPORS OR FUMES. See Section 25.2.1. FLASH POINT. See Section 32.2.1. FLEET VEHICLE MOTOR FUEL-DISPENSING FACILITY. See Section 20.2.1. FLOOR AREA, GROSS. See Section 8.2.1. FLOOR AREA, NET. See Section 8.2.1. FLUIDIZED BED. See Section 12.2.1. FOAM-EXTINGUISHING SYSTEM. See Section 7.2.1. FOLDING AND TELESCOPIC SEATING. See Section 8.2.1. FUEL LIMIT SWITCH. See Section 32.2.1. SBC 801 2007 1/8 DEFINITIONS FUMIGANT. See Section 15.2.1. FUMIGATION. See Section 15.2.1. FURNACE CLASS A. See Section 19.2.1. FURNACE CLASS B. See Section 19.2.1. FURNACE CLASS C. See Section 19.2.1. FURNACE CLASS D. See Section 19.2.1. GAS CABINET. See Section 25.2.1. GAS ROOM. See Section 25.2.1. GRANDSTAND. See Section 8.2.1. GUARD. See Section 8.2.1. HALOGENATED EXTINGUISHING SYSTEM. See Section 7.2.1. HANDLING. See Section 25.2.1. HANDRAIL. See Section 8.2.1. HAZARDOUS MATERIAL. See Section 25.2.1. HAZARDOUS PRODUCTION MATERIAL (HPM). See Section 16.2.1. HEALTH HAZARD. See Section 25.2.1. HELIPORT. See Section 11.2.1. HELISTOP. See Section 11.2.1. HI-BOY. See Section 5A.2.1. HIGH-PILED COMBUSTIBLE STORAGE. See Section 21.2.1. HIGH-PILED STORAGE AREA. See Section 21.2.1. HIGHLY TOXIC. See Section 35.2.1. HIGHLY VOLATILE LIQUID. A liquefied compressed gas with a boiling point of less than 20oC. HIGHWAY. See Section 31.2.1. HOGGED MATERIALS. See Section 17.2.1. SBC 801 2007 1/9 DEFINITIONS HOOD. See Section 5D.2.1. Type I. See Section 5D.2.1. HOT WORK. See Section 24.2.1. HOT WORK AREA. See Section 24.2.1. HOT WORK EQUIPMENT. See Section 24.2.1. HOT WORK PERMITS. See Section 24.2.1. HOT WORK PROGRAM. See Section 24.2.1. HPM FLAMMABLE LIQUID. See Section 16.2.1. HPM ROOM. See Section 16.2.1. IMMEDIATELY DANGEROUS TO LIFE AND HEALTH (IDLH). See Section 25.2.1. IMPAIRMENT COORDINATOR. See Section 7.2.1. INCOMPATIBLE MATERIALS. See Section 25.2.1. INHABITED BUILDING. See Section 31.2.1. INITIATING DEVICE. See Section 7.2.1. IRRITANT. A chemical which is not corrosive, but which causes a reversible inflammatory effect on living tissue by chemical action at the site of contact. A chemical is a skin irritant if, when tested on the intact skin of albino rabbits by the methods of CPSC 16CFR Part 1500.41 for an exposure of four or more hours or by other appropriate techniques, it results in an empirical score of 5 or more. A chemical is classified as an eye irritant if so determined under the procedure listed in CPSC 16CFR Part 1500.42 or other approved techniques. KEY BOX. See Section 5C.2.1. LABELED. Equipment or material to which has been attached a label, symbol or other identifying mark of a nationally recognized testing laboratory, inspection agency or other organization concerned with product evaluation that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling is indicated compliance with nationally recognized standards or tests to determine suitable usage in a specified manner. LIMITED SPRAYING SPACE. See Section 12.2.1. LIQUEFIED NATURAL GAS (LNG). See Section 20.2.1. LIQUEFIED PETROLEUM GAS (LP-gas). See Section 36.2.1. SBC 801 2007 1/10 DEFINITIONS LIQUID. See Section 25.2.1. LIQUID STORAGE ROOM. See Section 32.2.1. LISTED. Equipment or materials included on a list published by an approved testing laboratory, inspection agency or other organization concerned with current product evaluation that maintains periodic inspection of production of listed equipment or materials, and whose listing states that equipment or materials comply with approved nationally recognized standards and have been tested or evaluated and found suitable for use in a specified manner. LONGITUDINAL FLUE SPACE. See Section 21.2.1. LOW-PRESSURE TANK. See Section 30.2.1. LOWER EXPLOSIVE LIMIT (LEL). See Section 25.2.1. LOWER FLAMMABLE LIMIT (LFL). See Section 25.2.1. MAGAZINE. See Section 31.2.1. Indoor. See Section 31.2.1. Type 1. See Section 31.2.1. Type 2. See Section 31.2.1. Type 3. See Section 31.2.1. Type 4. See Section 31.2.1. Type 5. See Section 31.2.1. MAGNESIUM. See Section 34.2.1. MANUAL FIRE ALARM BOX. See Section 7.2.1. MANUAL STOCKING METHODS. See Section 21.2.1. MARINE MOTOR FUEL-DISPENSING FACILITY. See Section 20.2.1. MATERIAL SAFETY DATA SHEET (MSDS). See Section 25.2.1. MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA. See Section 25.2.1. MEANS OF EGRESS. See Section 8.2.1. MECHANICAL STOCKING METHODS. See Section 21.2.1. MEMBRANE STRUCTURE. See Section 22.2.1. MOBILE FUELING. See Section 32.2.1. MOI. Ministry of Interior. SBC 801 2007 1/11 DEFINITIONS MORTAR. See Section 31.2.1. MOT. Ministry of Transportation. MULTIPLE-STATION ALARM DEVICE. See Section 7.2.1. MULTIPLE-STATION SMOKE ALARM. See Section 7.2.1. NESTING. See Section 28.2.1. NET EXPLOSIVE WEIGHT (net weight). See Section 31.2.1. NORMAL TEMPERATURE AND PRESSURE (NTP). See Section 25.2.1. NOSING. See Section 8.2.1. NUISANCE ALARM. See Section 7.2.1. OCCUPANCY CLASSIFICATION. For the purposes of these code requirements, certain occupancies are defined as follows: Assembly Group A. Assembly Group A occupancy includes, among others, the use of a building or structure, or a portion thereof, for the gathering together of persons for purposes such as civic, social or religious functions, recreation, food or drink consumption or awaiting transportation. A room or space used for assembly purposes by less than 50 persons and accessory to another occupancy shall be included as a part of that occupancy. Assembly areas with less than 69.7 m2 and which are accessory to another occupancy according to Section 2A.2.2.1 are not assembly occupancies. Assembly occupancies which are accessory to Group E in accordance with Section 2A.2.2 are not considered assembly occupancies. Religious educational rooms and religious auditoriums which are accessory to mosques in accordance with Section 2A.2.2 and which have occupant loads of less than 100 shall be classified as A-3. A building or tenant space used for assembly purposes by less than 50 persons shall be considered a Group B occupancy. Assembly occupancies shall include the following: A-1 Assembly uses, usually with fixed seating, intended for the production and viewing of performing arts or motion pictures including but not limited to: Motion picture theaters Symphony and concert halls Television and radio studios admitting an audience Theaters A-2 Assembly uses intended for food and/or drink consumption including, but not limited to: Banquet halls Restaurants A-3 Assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A, including, but not limited to: Amusement arcades Art galleries Bowling alleys SBC 801 2007 1/12 DEFINITIONS Mosques Community halls Courtrooms Exhibition halls Gymnasiums (without spectator seating) Indoor swimming pools (without spectator seating) Indoor tennis courts (without spectator seating) Lecture halls Libraries Museums Waiting areas in transportation terminals Pool and billiard parlors A-4 Assembly uses intended for viewing of indoor sporting events and activities with spectator seating including, but not limited to: Arenas Skating rinks Swimming pools Tennis courts A-5 Assembly uses intended for participation in or viewing outdoor activities including, but not limited to: Amusement park structures Bleachers Grandstands Stadiums Business Group B. Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional or service-type transactions, including storage of records and accounts. Business occupancies shall include, but not be limited to, the following: Airport traffic control towers Animal hospitals, kennels, pounds Banks Barber and beauty shops Car wash Civic administration Clinic—outpatient Dry cleaning and laundries; pick-up and delivery stations and self-service Educational occupancies above the 12th grade Electronic data processing Laboratories; testing and research Motor vehicle showrooms Post offices Print shops Professional services (architects, attorneys, dentists, physicians, engineers, etc.) Radio and television stations Telephone exchanges Educational Group E. Educational Group E occupancy includes, among others, the use of a building or structure, or a portion thereof, by six or more persons at any one time for educational purposes through the 12th grade. Educational rooms and auditoriums, which are accessory to mosques in SBC 801 2007 1/13 DEFINITIONS accordance with Section 5A.2.2 and have occupant loads of less than 100, shall be classified as Group A-3 occupancies. Day care. The use of a building or structure, or portion thereof, for educational, supervision or personal care services for more than five children older than 21/2 years of age shall be classified as an E occupancy. Factory Industrial Group F. Factory Industrial Group F occupancy includes, among others, the use of a building or structure, or a portion thereof, for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations that are not classified as a Group H high-hazard or Group S storage occupancy. Factory Industrial F-1 Moderate-Hazard Occupancy. Factory Industrial uses which are not classified as Factory Industrial Group F-2 shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, the following: Aircraft Appliances Athletic equipment Automobiles and other motor vehicles Bakeries Bicycles Boats Brooms or brushes Business machines Cameras and photo equipment Canvas and similar fabric Carpet and rugs (includes cleaning) Disinfectants Dry cleaning and dyeing Electric generation plants Electronics Engines (including rebuilding) Food processing Furniture Hemp products Jute products Laundries Leather products Machinery Metals Millwork (sash and doors) Motion picture and television filming (without spectators) Musical instruments Optical goods Paper mills or products Photographic film Plastic products Printing or publishing Recreational vehicles Refuse incineration Shoes Soaps and detergents Textiles SBC 801 2007 1/14 DEFINITIONS Tobacco Trailers Upholstering Wood; distillation Woodworking (cabinet) Factory Industrial F-2 Low-Hazard Occupancy. Factory industrial uses involving the fabrication or manufacturing of noncombustible materials which, during finishing, packaging or processing do not involve a significant fire hazard, shall be classified as Group F-2 occupancies and shall include, but not be limited to, the following: Brick and masonry Ceramic products Foundries Glass products Gypsum Ice Metal products (fabrication and assembly) High-Hazard Group H. High-hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the manufacturing, processing, generation or storage of materials that constitute a physical or health hazard in quantities in excess of those found in Tables 2A.7.7(1) and 2A.7.7(2). (See also definition of “Control area)”. Exception: Occupancies as provided for in the SBC 201 shall not be classified as Group H, but shall be classified in the occupancy which they most nearly resemble. High-hazard Group H-1. Buildings and structures containing materials that pose a detonation hazard, shall be classified as Group H-1. Such materials shall include, but not be limited to, the following: Explosives: Division 1.1 Division 1.2 Division 1.3 Exception: Materials that are used and maintained in a form where either confinement or configuration will not elevate the hazard from a mass fire to mass explosion hazard shall be allowed in Group H-2 occupancies. Division 1.4 Exception: Articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco and Firearms regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles shall be allowed in Group H-3 occupancies. Division 1.5 Division 1.6 Organic peroxides, unclassified detonable Oxidizers, Class 4 Unstable (reactive) materials, Class 3 detonable, and Class 4 Detonable pyrophoric materials High-hazard Group H-2. Buildings and structures containing materials that pose a deflagration hazard or a hazard from accelerated burning shall be classified as Group H-2. Such materials shall include, but not be limited to, the following: SBC 801 2007 1/15 DEFINITIONS Class I, or II or IIIA flammable or combustible liquids which are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 pounds per square inch (103.4 kPa) gauge Combustible dusts Cryogenic fluids, flammable Flammable gases Organic peroxides, Class I Oxidizers, Class 3, that are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 103.4 kPa gauge Pyrophoric liquids, solids and gases, nondetonable Unstable (reactive) materials, Class 3, nondetonable Water-reactive materials, Class 3 High-hazard Group H-3. Buildings and structures containing materials that readily support combustion or that pose a physical hazard shall be classified as Group H-3. Such materials shall include, but not be limited to, the following: Class I, II or IIIA flammable or combustible liquids which are used or stored in normally closed containers or systems pressurized at less than 103.4 kPa gauge Combustible fibers Consumer fireworks, 1.4G (Class C, Common) Cryogenic fluids, oxidizing Flammable solids Organic peroxides, Class II and Class III Oxidizers, Class 2 Oxidizing gases Unstable (reactive) materials, Class 2 Water-reactive materials, Class 2 High-hazard Group H-4. Buildings and structures which contain materials that are health hazards shall be classified as Group H-4. Such materials shall include, but not be limited to, the following: Corrosives Highly toxic materials Toxic materials High-hazard Group H-5. Semiconductor fabrication facilities and comparable research and development areas in which hazardous production materials (HPM) are used and the aggregate quantity of materials is in excess of those listed in Tables 2A.7.7(1) and 2A.7.7(2). Such facilities and areas shall be designed and constructed in accordance with Section 2B.15.9. Institutional Group I. Institutional Group I occupancy includes, among others, the use of a building or structure, or a portion thereof, in which people, cared for or living in a supervised environment and having physical limitations because of health or age, are harbored for medical treatment or other care or treatment, or in which people are detained for penal or correctional purposes or in which the liberty of the occupants is restricted. Institutional occupancies shall be classified as Group I-1, I-2, I-3 or I-4. Group I-1. This occupancy shall include buildings, structures or parts thereof housing more than 16 persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services. The occupants are capable of responding to an emergency situation without physical assistance from staff. This group shall include, but not be limited to, the following: SBC 801 2007 1/16 DEFINITIONS Alcohol and drug centers Assisted living facilities Congregate care facilities Convalescent facilities Group homes Half-way houses Residential board and care facilities Social rehabilitation facilities A facility such as the above with five or fewer persons shall be classified as Group R-3. A facility such as above, housing at least six and not more than 16 persons, shall be classified as Group R-4. Group I-2. This occupancy shall include buildings and structures used for medical, surgical, psychiatric, nursing or custodial care on a 24-hour basis of more than five persons who are not capable of self-preservation. This group shall include, but not be limited to, the following: Hospitals Nursing homes (both intermediate care facilities and skilled nursing facilities) Mental hospitals Detoxification facilities A facility such as the above with five or fewer persons shall be classified as Group R-3. A child care facility which provides care on a 24-hour basis to more than five children 21/2 years of age or less shall be classified as Group I-2. Group I-3. This occupancy shall include buildings and structures which are inhabited by more than five persons who are under restraint or security. An I-3 facility is occupied by persons who are generally incapable of self-preservation due to security measures not under the occupants’ control. This group shall include, but not be limited to, the following: Correctional centers Detention centers Jails Prerelease centers Prisons Reformatories Buildings of Group I-3 shall be classified as one of the occupancy conditions indicated in Sections 2A.8.4.1 through 2A.8.4.5 (see Section 2B.8.1). Condition 1. This occupancy condition shall include buildings in which free movement is allowed from sleeping areas and other spaces where access or occupancy is permitted, to the exterior via means of egress without restraint. A Condition 1 facility is permitted to be constructed as Group R. Condition 2. This occupancy condition shall include buildings in which free movement is allowed from sleeping areas and any other occupied smoke compartment to one or more other smoke compartments. Egress to the exterior is impeded by locked exits. Condition 3. This occupancy condition shall include buildings in which free movement is allowed within individual smoke compartments, such as within a residential unit comprised of individual sleeping units and group activity spaces, where egress is impeded by remote-controlled release of means of egress from such smoke compartment to another smoke compartment. Condition 4. This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Remote-controlled release is SBC 801 2007 1/17 DEFINITIONS provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments. Condition 5. This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Staff-controlled manual release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments. Group I-4, day care facilities. This group shall include buildings and structures occupied by persons of any age who receive custodial care for less than 24 hours by individuals other than parents or guardians, relatives by blood marriage, or adoption, and in a place other than the home of the person cared for. A facility such as the above with five or fewer persons shall be classified as Group R-3. Places of worship during religious functions are not included. Adult care facility. A facility that provides accommodations for less than 24 hours for more than five unrelated adults and provides supervision and personal care services shall be classified as Group I-4. Exception: Where the occupants are capable of responding to an emergency situation without physical assistance from the staff the facility shall be classified as Group A-3. Child care facility. A facility that provides supervision and personal care on less than a 24-hour basis for more than five children 21/2 years of age or less shall be classified as Group I-4. Exception: A child day care facility which provides care for more than five but no more than 100 children 21/2 years or less of age, when the rooms where such children are cared for are located on the level of exit discharge and each of these child care rooms has an exit door directly to the exterior, shall be classified as Group E. Mercantile Group M. Mercantile Group M occupancy includes, among others, buildings and structures or a portion thereof, for the display and sale of merchandise, and involves stocks of goods, wares or merchandise incidental to such purposes and accessible to the public. Mercantile occupancies shall include, but not be limited to, the following: Department stores Drug stores Markets Motor fuel-dispensing facilities Retail or wholesale stores Sales rooms Residential Group R. Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classed as Institutional Group I. Residential occupancies shall include the following: R-1 Residential occupancies where the occupants are primarily transient in nature including: Boarding houses (transient) Hotels (transient) Motels (transient) R-2 Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including: Apartment houses SBC 801 2007 1/18 DEFINITIONS Boarding houses (not transient) Dormitories Fraternities and sororities Hotels (nontransient) Motels (nontransient) Vacation timeshare properties R-3 Residential occupancies where the occupancies are primarily permanent in nature and not classified as R-1, R-2, or I and where buildings do not contain more than two dwelling units, or adult and child care facilities that provide accommodations for five or fewer persons of any age for less than 24-hours. Adult and child care facilities that are within a single-family home are permitted. R-4 Residential occupancies shall include buildings arranged for occupancy as Residential Care/Assisted Living Facilities including more than five but not more than 16 occupants. Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3 except for the height and area limitations provided in Section 3.3. Storage Group S. Storage Group S occupancy includes, among others, the use of a building or structure, or a portion thereof, for storage that is not classified as a hazardous occupancy. Moderate-hazard storage, Group S-1. Buildings occupied for storage uses which are not classified as Group S-2 including, but not limited to, storage of the following: Aerosols, Level 2 and 3 Aircraft repair hangar Bags, cloth, burlap and paper Bamboo and rattan Baskets Belting, canvas and leather Books and paper in rolls or packs Boots and shoes Buttons, including cloth covered, pearl or bone Cardboard and cardboard boxes Clothing, woolen wearing apparel Cordage Furniture Furs Glue, mucilage, paste and size Grain Horn and combs, other than celluloid Leather Linoleum Lumber Motor vehicle repair garages (complying with the International Building Code and containing less than the maximum allowable quantities of hazardous materials) Photo engraving Resilient flooring Silk Soap SBC 801 2007 1/19 DEFINITIONS Sugar Tires, bulk storage of Tobacco, cigars, cigarettes and snuff Upholstering and mattress Wax candles Low-hazard storage, Group S-2. Includes, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thickness divisions; or in paper wrappings. Such products may have a negligible amount of plastic trim such as knobs, handles, or film wrapping. Storage uses shall include, but not be limited to, storage of the following: Aircraft hangar Asbestos Cement in bags Chalk and crayons Dairy products in nonwaxed coated paper containers Dry cell batteries Electrical coils Electrical motors Empty cans Food products Foods in noncombustible containers Fresh fruits and vegetables in nonplastic trays or containers Frozen foods Glass Glass bottles, empty or filled with noncombustible liquids Gypsum board Inert pigments Ivory Metal desks with plastic tops and trim Metal parts Metals Mirrors Oil-filled and other types of distribution transformers Parking garages (open or enclosed) Porcelain and pottery Stoves Talc and soap stones Washers and dryers Miscellaneous Group U. Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and maintained to conform to the requirements of the SBC commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following: Agricultural buildings Aircraft hangar, accessory to a one- or two-family residence (see Section 2B.12.3) Barns Carports Fences more than 1.83 m high Grain silos, accessory to a residential occupancy SBC 801 2007 1/20 DEFINITIONS Greenhouses Livestock shelters Private garages Retaining walls Sheds Stables Tanks Towers OCCUPANT LOAD. See Section 8.2.1. OPEN BURNING. See Section 5A.2.1. OPEN SYSTEM. The use of a solid or liquid hazardous material involving a vessel or system that is continuously open to the atmosphere during normal operations and where vapors are liberated, or the product is exposed to the atmosphere during normal operations. Examples of open systems for solids and liquids include dispensing from or into open beakers or containers, dip tank and plating tank operations. OPERATING BUILDING. See Section 31.2.1. OPERATING PRESSURE. The pressure at which a system operates. ORGANIC COATING. See Section 18.2.1. ORGANIC PEROXIDE. See Section 37.2.1. Class I. See Section 37.2.1. Class II. See Section 37.2.1. Class III. See Section 37.2.1. Class IV. See Section 37.2.1. Class V. See Section 37.2.1. Unclassified detonable. See Section 37.2.1. OUTDOOR CONTROL AREA. See Section 25.2.1. OVERCROWDING. A condition that exists when either there are more people in a building, structure or portion thereof than have been authorized or posted by the Building code official, or when the Building code official determines that a threat exist to the safety of the occupants due to persons sitting and/or standing in locations that may obstruct or impede the use of aisles, passages, corridors, stairways, exits or other components of the means of egress. OWNER. A corporation, firm, partnership, association, organization and any other group acting as a unit, or a person who has legal title to any structure or premises with or without accompanying actual possession thereof, and shall include the duly authorized agent or attorney, a purchaser, devisee, fiduciary and any person having a vested or contingent interest in the premises in question. OXIDIZER. See Section 38.2.1. Class 4. See Section 38.2.1. SBC 801 2007 1/21 DEFINITIONS Class 3. See Section 38.2.1. Class 2. See Section 38.2.1. Class 1. See Section 38.2.1. OXIDIZING GAS. See Section 38.2.1. OZONE-GAS GENERATOR. See Section 35.2.1. PANIC HARDWARE. See Section 8.2.1. PASS-THROUGH. See Section 16.2.1. PERMISSIBLE EXPOSURE LIMIT (PEL). See Section 25.2.1. PESTICIDE. See Section 25.2.1. PHYSICAL HAZARD. See Section 25.2.1. PLOSOPHORIC MATERIAL. See Section 31.2.1. PLYWOOD and VENEER MILLS. See Section 17.2.1. POWERED INDUSTRIAL TRUCK. See Section 5A.2.1. PRESSURE VESSEL. See Section 25.2.1. PRIMARY CONTAINMENT. The first level of containment, consisting of the inside portion of that container which comes into immediate contact on its inner surface with the material being contained. PROCESS TRANSFER. See Section 32.2.1. PROPELLANT. See Section 26.2.1. PROXIMATE AUDIENCE. See Section 31.2.1. PUBLIC WAY. See Section 8.2.1. PYROPHORIC. See Section 39.2.1. PYROTECHNIC COMPOSITION. See Section 31.2.1. PYROTECHNIC SPECIAL EFFECT. See Section 31.2.1. PYROTECHNIC SPECIAL-EFFECT MATERIAL. See Section 31.2.1. RAILWAY. See Section 31.2.1. RAMP. See Section 8.2.1. RAW PRODUCT. See Section 17.2.1. SBC 801 2007 1/22 DEFINITIONS READY BOX. See Section 31.2.1. RECORD DRAWINGS. See Section 7.2.1. RECREATIONAL FIRE. See Section 5A.2.1. REDUCED FLOW VALVE. See Section 35.2.1. REFINERY. See Section 32.2.1. REFRIGERANT. See Section 5D.2.1. REFRIGERATION SYSTEM. See Section 5D.2.1. REGISTERED DESIGN PROFESSIONAL. An architect or engineer, registered or licensed to practice professional architecture or engineering, as defined by the statutory requirements of the professional registration laws of the state in which the project is to be constructed. REMOTE EMERGENCY SHUTOFF DEVICE. See Section 32.2.1. REMOTE SOLVENT RESERVOIR. See Section 32.2.1. REPAIR GARAGE. See Section 20.2.1. RESIN APPLICATION AREA. See Section 12.2.1. RESPONSIBLE PERSON. See Section 24.2.1. RETAIL DISPLAY AREA. See Section 26.2.1. ROLL COATING. See Section 12.2.1. RUBBISH (TRASH). Combustible and noncombustible waste materials, including residue from the burning of coal, wood, coke or other combustible material, paper, rags, cartons, tin cans, metals, mineral matter, glass crockery, dust and discarded refrigerators, and heating, cooking or incinerator-type appliances. SAFETY CAN. See Section 25.2.1. SCISSOR STAIR. See Section 8.2.1. SECONDARY CONTAINMENT. See Section 25.2.1. SEGREGATED. See Section 25.2.1. SELF-SERVICE MOTOR FUEL-DISPENSING FACILITY. See Section 20.2.1. SEMICONDUCTOR FABRICATION FACILITY. See Section 16.2.1. SBC 801 2007 1/23 DEFINITIONS SERVICE CORRIDOR. See Section 16.2.1. SHELF STORAGE. See Section 21.2.1. SINGLE-STATION SMOKE ALARM. See Section 7.2.1. SLEEPING UNIT. See Section 7.2.1. SMALL ARMS AMMUNITION. See Section 31.2.1. SMALL ARMS PRIMERS. See Section 31.2.1. SMOKE ALARM. See Section 7.2.1. SMOKE DETECTOR. See Section 7.2.1. SMOKE-PROTECTED ASSEMBLY SEATING. See Section 8.2.1. SMOKELESS PROPELLANTS. See Section 31.2.1. SOLID. See Section 25.2.1. SOLID SHELVING. See Section 21.2.1. SOLVENT DISTILLATION UNIT. See Section 32.2.1. SOLVENT OR LIQUID CLASSIFICATIONS. See Section 13.2.1. Class I solvents. See Section 13.2.1. Class II solvents. See Section 13.2.1. Class IIIA solvents. See Section 13.2.1. Class IIIB solvents. See Section 13.2.1. Class IV solvents. See Section 13.2.1. SPECIAL AMUSEMENT BUILDING. A building that is temporary, permanent or mobile that contains a device or system that conveys passengers or provides a walkway along, around or over a course in any direction as a form of amusement arranged so that the egress path is not readily apparent due to visual or audio distractions or an intentionally confounded egress path, or is not readily available because of the mode of conveyance through the building or structure. SPECIAL INDUSTRIAL EXPLOSIVE DEVICE. See Section 31.2.1. SPRAY AREA. See Section 12.2.1. SPRAY BOOTH. See Section 12.2.1. SPRAY ROOM. See Section 12.2.1. STAIR. See Section 8.2.1. SBC 801 2007 1/24 DEFINITIONS STAIRWAY. See Section 8.2.1. STAIRWAY, EXTERIOR. See Section 8.2.1. STAIRWAY, INTERIOR. See Section 8.2.1. STAIRWAY, SPIRAL. See Section 8.2.1. STANDPIPE SYSTEM, CLASSES OF. See Section 7.2.1. Class I system. See Section 7.2.1. Class II system. See Section 7.2.1. Class III system. See Section 7.2.1. STANDPIPE, TYPES OF. See Section 7.2.1. Automatic dry. See Section 7.2.1. Automatic wet. See Section 7.2.1. Manual dry. See Section 7.2.1. Manual wet. See Section 7.2.1. Semiautomatic dry. See Section 7.2.1. STATIC PILES. See Section 17.2.1. STEEL. Hot- or cold-rolled as defined by the Saudi Building Code. STORAGE, HAZARDOUS MATERIALS. See Section 25.2.1. STORY ABOVE GRADE PLANE. Any story having its finished floor surface entirely above grade plane, except that a basement shall be considered as a story above grade plane where the finished surface of the floor above the basement is: 1. More than 1.8 m above grade plane; 2. More than 1.8 m above the finished ground level for more than 50 percent of the total building perimeter; or 3. More than 3.7 m above the finished ground level at any point. SUPERVISING STATION. See Section 7.2.1. SUPERVISORY SERVICE. See Section 7.2.1. SUPERVISORY SIGNAL. See Section 7.2.1. SUPERVISORY SIGNAL-INITIATING DEVICE. See Section 7.2.1. SYSTEM. See Section 25.2.1. TANK. A vessel containing more than 227 L. TANK, ATMOSPHERIC. See Section 25.2.1. TANK, PORTABLE. See Section 25.2.1. TANK, PRIMARY. See Section 32.2.1. SBC 801 2007 1/25 DEFINITIONS TANK, PROTECTED ABOVE GROUND. See Section 32.2.1. TANK, STATIONARY. See Section 25.2.1. TANK VEHICLE. See Section 25.2.1. TENT. See Section 22.2.1. THEFT RESISTANT. See Section 31.2.1. THERMAL INSECTICIDAL FOGGING. See Section 15.2.1. TIMBER AND LUMBER PRODUCTION FACILITIES. See Section 17.2.1. TIRES, BULK STORAGE OF. See Section 7.2.1. TOOL. See Section 16.2.1. TORCH-APPLIED ROOF SYSTEM. See Section 24.2.1. TOXIC. See Section 35.2.1. TRANSVERSE FLUE SPACE. See Section 21.2.1. TRASH. See “Rubbish.” TROUBLE SIGNAL. See Section 7.2.1. UNAUTHORIZED DISCHARGE. See Section 25.2.1. UNSTABLE (REACTIVE) MATERIAL. See Section 41.2.1. Class 4. See Section 41.2.1. Class 3. See Section 41.2.1. Class 2. See Section 41.2.1. Class 1. See Section 41.2.1. UNWANTED FIRE: A fire not used for cooking, heating or recreational purposes or one not incidental to the normal operations of the property. USE (MATERIAL). See Section 25.2.1. VALVE-REGULATED LEAD-ACID (VRLA) BATTERY: See Section 5D.2.1. VAPOR AREA. See Section 12.2.1. VAPOR PRESSURE. See Section 25.2.1. VENTED (FLOODED) LEAD-ACID BATTERY. See Section 5D.2.1. SBC 801 2007 1/26 DEFINITIONS VISIBLE ALARM NOTIFICATION APPLIANCE. See Section 7.2.1. WATER-REACTIVE MATERIAL. See Section 42.2.1. Class 3. See Section 42.2.1. Class 2. See Section 42.2.1. Class 1. See Section 42.2.1. WET-CHEMICAL EXTINGUISHING AGENT. See Section 7.2.1. WINDER. See Section 8.2.1. WIRELESS PROTECTION SYSTEM. See Section 7.2.1. WORKSTATION. See Section 16.2.1. ZONE. See Section 7.2.1. SBC 801 2007 1/27 USE AND OCCUPANCY CLASSIFICATION CHAPTER 2 USE AND OCCUPANCY CLASSIFICATION AND SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 2A USE AND OCCUPANCY CLASSIFICATION SECTION 2A.1 GENERAL 2A.1.1 Scope. The provisions of this chapter shall control the classification of all buildings and structures as to use and occupancy. SECTION 2A.2 CLASSIFICATION General. Structures or portions of structures shall be classified with respect to occupancy in one or more of the groups listed below. Structures with multiple uses shall be classified according to Section 2A.2.3. Where a structure is proposed for a purpose which is not specifically provided for in SBC 201, such structure shall be classified in the group which the occupancy most nearly resembles, according to the fire safety and relative hazard involved. 1. Assembly (see Section 2A.3): Groups A-1, A-2, A-3, A-4 and A-5 2. Business (see Section 2A.4): Group B 3. Educational (see Section 2A.5): Group E 4. Factory and Industrial (see Section 2A.6): Groups F-1 and F-2 5. High Hazard (see Section 2A.7): Groups H-1, H-2, H-3, H-4 and H-5 6. Institutional (see Section 2A.8): Groups I-1, I-2, I-3 and I-4 7. Mercantile (see Section 2A.9): Group M 8. Residential (see Section 2A.10): Groups R-1, R-2, R-3 as applicable in Section 101.2, and R-4 9. Storage (see Section 2A.11): Groups S-1 and S-2 10. Utility and Miscellaneous (see Section 2A.12): Group U 2A.2.1.1 Incidental use areas. Spaces which are incidental to the main occupancy shall be separated or protected, or both, in accordance with Table 2A.2.1.1 or the building shall be classified as a mixed occupancy and comply with Section 2A.2.3. Areas that are incidental to the main occupancy shall be classified in accordance with the main occupancy of the portion of the building in which the incidental use area is located. Exception: Incidental use areas within and serving a dwelling unit are not required to comply with this section. 2A.2.1.1.1 Separation. Where Table 2A.2.1.1 requires a fire-resistance-rated separation, the incidental use area shall be separated from the remainder of the building with a fire barrier. Where Table 2A.2.1.1 permits an automatic fire-extinguishing system without a fire barrier, the incidental use area shall be separated by construction capable of resisting the passage of smoke. The partitions shall extend from the floor to the underside of the fire-resistance-rated floor/ceiling assembly or fireresistance-rated roof/ceiling assembly or to the underside of the floor or roof deck above. Doors shall be self-closing or automatic-closing upon detection of smoke. Doors shall not have air transfer openings and shall not be undercut in excess of the clearance permitted in accordance with NFPA 80. 2A.2.1 SBC 801 2007 2/1 USE AND OCCUPANCY CLASSIFICATION 2A.2.2 2A.2.2.1 Accessory use areas. A fire barrier shall be required to separate accessory use areas classified as Group H in accordance with Section 2A.2.3.1, and incidental use areas in accordance with Section 2A.2.1.1. Any other accessory use area shall not be required to be separated by a fire barrier provided the accessory use area occupies an area not more than 10 percent of the area of the story in which it is located and does not exceed the tabular values in Table 5C.3 for the allowable height or area for such use. Assembly areas. Accessory assembly areas are not considered separate occupancies if the floor area is equal to or less than 70 m2. Assembly areas that are accessory to Group E are not considered separate occupancies. Accessory educational rooms, multi-purpose halls and auditoriums with occupant loads of less than 100 are not considered separate occupancies. TABLE 2A.2.1.1 INCIDENTAL USE AREAS ROOM OR AREA Furnace room where any piece of equipment is over 117 kW per hour input Rooms with any boiler over 103.5 kPa and 7.5 kW Refrigerant machinery rooms Parking garage (Section 2B.6.2) Hydrogen cut-off rooms SEPARATIONa 1 hour or provide automatic fire-extinguishing system 1 hour or provide automatic fire-extinguishing system 1 hour or provide automatic sprinkler system 2 hours; or 1 hour and provide automatic fireextinguishing system 1hour fire barriers and floor/ceiling assemblies in Group B, F, H, M, S and U occupancies. 2 hours fire barriers and floor/ceiling assemblies in Group A, E, I and R occupancies. 2 hours and automatic sprinkler system 2 hours; or 1 hour and provide automatic fireextinguishing system Incinerator rooms Paint shops, not classified as Group H, located in occupancies other than Group F Laboratories and vocational shops, not classified as 1 hour or provide automatic fire-extinguishing system Group H, located in Group E or I-2 occupancies 2 Laundry rooms over 9 m 1 hour or provide automatic fire-extinguishing system Storage rooms over 9 m2 1 hour or provide automatic fire-extinguishing system Group I-3 cells equipped with padded surfaces 1 hour Group I-2 waste and linen collection rooms 1 hour Waste and linen collection rooms over 9 m2 1 hour or provide automatic fire-extinguishing system Stationary lead-acid battery systems having a liquid 1hour fire barriers and floor/ceiling assemblies in capacity of more than 379 liters used for facility Group B, F, H, M, S and U occupancies. 2 hours fire standby power, emergency power or uninterrupted barriers and floor/ceiling assemblies in Group A, E, I power supplies and R occupancies a. Where an automatic fire-extinguishing system is provided, it need only be provided in the incidental use room or area. 2A.2.3 SBC 801 Mixed occupancies. Where a building is occupied by two or more uses not included in the same occupancy classification, the building or portion thereof shall comply with Section 2A.2.3.1 or 2A.2.3.2 or a combination of these sections. Exceptions: 1. Occupancies separated in accordance with Section 5C.8. 2. Areas of Group H-2, H-3, H-4 or H-5 occupancies shall be separated from any other occupancy in accordance with Section 2A.2.3.2. 3. Where required by Table 2B.15.3.2, areas of Group H-1, H-2 or H-3 occupancy shall be located in a separate and detached building or structure. 4. Accessory use areas in accordance with Section 2A.2.2. 5. Incidental use areas in accordance with Section 2A.2.1.1. 2007 2/2 USE AND OCCUPANCY CLASSIFICATION 2A.2.3.1 2A.2.3.2 2A.2.4 Non-separated uses. Each portion of the building shall be individually classified as to use. The required type of construction for the building shall be determined by applying the height and area limitations for each of the applicable occupancies to the entire building. The most restrictive type of construction, so determined, shall apply to the entire building. All other code requirements shall apply to each portion of the building based on the use of that space except that the most restrictive applicable provisions of Section 2B.3 and Chapter 7 shall apply to these non-separated uses. Fire separations are not required between uses, except as required by other provisions. Separated uses. Each portion of the building shall be individually classified as to use and shall be completely separated from adjacent areas by fire barrier walls or horizontal assemblies or both having a fire-resistance rating determined in accordance with Table 2A.2.3.2 for uses being separated. Each fire area shall comply with these code requirements based on the use of that space. Each fire area shall comply with the height limitations based on the use of that space and the type of construction classification. In each story, the building area shall be such that the sum of the ratios of the floor area of each use divided by the allowable area for each use shall not exceed one. Exception: Except for Group H and I-2 areas, where the building is equipped throughout with an automatic sprinkler system, installed in accordance with Section 7.3.3.1.1, the fire-resistance ratings in Table 2A.2.3.3 shall be reduced by 1 hour but to not less than 1 hour and to not less than that required for floor construction according to the type of construction. Spaces used for different purposes. A room or space that is intended to be occupied at different times for different purposes shall comply with all the requirements that are applicable to each of the purposes for which the room or space will be occupied. SECTION 2A.3 ASSEMBLY GROUP A 2A.3.1 SBC 801 Assembly Group A. Assembly Group A occupancy includes, among others, the use of a building or structure, or a portion thereof, for the gathering together of persons for purposes such as civic, social or religious functions, recreation, food or drink consumption or awaiting transportation. A room or space used for assembly purposes by less than 50 persons and accessory to another occupancy shall be included as a part of that occupancy. Assembly areas with less than 70 m2 and which are accessory to another occupancy according to Section 2A.2.2.1 are not assembly occupancies. Assembly occupancies which are accessory to Group E in accordance with Section 2A.2.2 are not considered assembly occupancies. Educational rooms, multi-purpose halls and auditoriums which are accessory to mosques in accordance with Section 2A.2.2 and which have occupant loads of less than 100 shall be classified as A-3. Assembly occupancies shall include the following: A-1 Assembly uses, usually with fixed seating, intended for the production and viewing of the performing arts or motion pictures including, but not limited to: Motion picture theaters Symphony and concert halls Television and radio studios admitting an audience Theaters 2007 2/3 SBC 801 F-2 H-1 H-2 2007 H-5 ------- F-1 ------- E --- Bb --- A-5 4 4 4 4 4 1 3 1 1 NP 2 1 1 ----------------- A-4 2 2 2 2 2 1 2 1 1 NP 2 1 ------------------- A-3 --2 2 2 2 2 2 3 2 NP 4 3 A-1 ----2 2 2 2 2 3 2 NP 4 3 A-2e ------2 2 2 2 3 2 NP 4 3 A-3 --------2 2 2 3 2 NP 4 3 A-4 ----------2 2 3 2 NP 4 3 A-5 ------------2 3 2 NP 2 1 Bb --------------3 2 NP 4 3 E ----------------3 NP 2 1 F-1 ------------------NP 2 1 F-2 --------------------NP NP H-1 ----------------------1 H-2 ------------------------H-3 ------------------------H-4 ------------------------H-5 ------------------------I-1 ------------------------I-2 ------------------------I-3 ------------------------I-4 ------------------------Mb ------------------------R-1 ------------------------R-2 R3, R------------------------4 ------------------------S-1 ------------------------S-2c ------------------------U NP = Not permitted. a. See Exception 1 to Section 2A.2.3.2 for reductions permitted. b. Occupancy separation need not be provided for storage areas within Groups B and M if the: 1. Area is less than 10 percent of the floor area; 2. Area is provided with an automatic fire-extinguishing system and is less than 279 m2; or 3. Area is less than 93 m2. c. Areas used only for private or pleasure vehicles shall be allowed to reduce separation by 1 hour. d. See exception to Section 2A.2.3.2. e. Commercial kitchens need not be separated from the restaurant seating areas that they serve. A-2 H-4 A-1 H-3 USE ------- --- 2 2 2 2 2 2 2 3 2 NP 4 4 4 4 --------------- I-1 ------- --- 2 2 2 2 2 2 2 3 2 NP 4 3 4 4 2 ------------- I-2 ------- --- 2 2 2 2 2 2 2 3 2 NP 4 3 4 4 2 2 ----------- I-3 TABLE 2A.2.3.2 REQUIRED SEPARATION OF OCCUPANCIES (HOURS)a ------- --- 2 2 2 2 2 2 2 3 2 NP 4 3 4 3 2 2 2 --------- I-4 ------- --- 2 2 2 2 2 2 2 3 2 NP 2 1 1 1 2 2 2 2 ------- Mb ------- --- 2 2 2 2 2 2 2 3 2 NP 4 3 4 4 2 2 2 2 2 ----- R-1 2/4 ------- --- 2 2 2 2 2 2 2 3 2 NP 4 3 4 4 2 2 2 2 2 2 --- R-2 ------- --- R-3, R4 2 2 2 2 2 2 2 3 2 NP 4 3 4 4 2 2 2 2 2 2 2 ------- 3 3 3 3 3 3 3 3 3 3 NP 2 1 1 1 4 3 3 3 3 3 3 S-1 3 ----- 2d 2 2 2 2 2 2 2 3 2 NP 2 1 1 1 3 2 2 2 2 2 2 S-2c 3 1 --- 1d 1 1 1 1 1 1 1 3 1 NP 1 1 1 3 2 1 1 1 1 1 1 U USE AND OCCUPANCY CLASSIFICATION 2A.3.1.1 A-2 Assembly uses intended for food and/or drink consumption including, but not limited to: Banquet halls Restaurants Cafes A-3 Assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A including, but not limited to: Amusement arcades Art galleries Bowling alleys Mosques Community halls Courtrooms Dance halls (not including food or drink consumption) Exhibition halls Funeral centers Gymnasiums (without spectator seating) Indoor swimming pools (without spectator seating) Indoor tennis courts (without spectator seating) Lecture halls Libraries Museums Waiting areas in transportation terminals Pool and billiard parlors A-4 Assembly uses intended for viewing of indoor sporting events and activities with spectator seating including, but not limited to: Arenas Skating rinks Swimming pools Tennis courts A-5 Assembly uses intended for participation in or viewing outdoor activities including, but not limited to: Amusement park structures Bleachers Grandstands Stadiums Non-accessory assembly use. A building or tenant space used for assembly purposes by less than 50 persons shall be considered a Group B occupancy. SECTION 2A.4 BUSINESS GROUP B 2A.4.1 SBC 801 Business Group B. Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional or servicetype transactions, including storage of records and accounts. Business occupancies shall include, but not be limited to, the following: Airport traffic control towers Animal hospitals, kennels and pounds Banks Barber and beauty shops Car wash Civic administration 2007 2/5 USE AND OCCUPANCY CLASSIFICATION Clinic – outpatient Dry cleaning and laundries; pick-up and delivery stations and self-service Educational occupancies above the 12th grade for male/female Electronic data processing Laboratories; testing and research Motor vehicle showrooms Post offices Print shops Professional services (architects, attorneys, dentists, physicians, engineers, etc.) Radio and television stations Telephone exchanges SECTION 2A.5 EDUCATIONAL GROUP E 2A.5.1 Educational Group E. Educational Group E occupancy includes, among others, the use of a building or structure, or a portion thereof, by six or more persons at any one time for educational purposes through the 12th grade. Educational rooms, multi-purpose halls and auditoriums, which are accessory to mosques in accordance with Section 2A.2.2 and have occupant loads of less than 100, shall be classified as A-3 occupancies. 2A.5.2 Day care. The use of a building or structure, or portion thereof, for educational, supervision or personal care services for more than five children older than 21/2 years of age, shall be classified as a Group E occupancy. SECTION 2A.6 FACTORY GROUP F 2A.6.1 Factory Industrial Group F. Factory Industrial Group F occupancy includes, among others, the use of a building or structure, or a portion thereof, for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations that are not classified as a Group H hazardous or Group S storage occupancy. 2A.6.2 Factory Industrial F-1 Moderate-Hazard Occupancy. Factory industrial uses which are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, the following: Aircraft Appliances Athletic equipment Automobiles and other motor vehicles Bakeries Medical products over 12-percent alcohol content Bicycles Boats Brooms or brushes Business machines Cameras and photo equipment Canvas or similar fabric Carpets and rugs (includes cleaning) Clothing SBC 801 2007 2/6 USE AND OCCUPANCY CLASSIFICATION Construction and agricultural machinery Disinfectants Dry cleaning and dyeing Electric generation plants Electronics Engines (including rebuilding) Food processing Furniture Hemp products Jute products Laundries Leather products Machinery Metals Millwork (sash & door) Motion pictures and television filming (without spectators) Musical instruments Optical goods Paper mills or products Photographic film Plastic products Printing or publishing Recreational vehicles Refuse incineration Shoes Soaps and detergents Textiles Tobacco Trailers Upholstering Wood; distillation Woodworking (cabinet) 2A.6.3 Factory Industrial F-2 Low-Hazard Occupancy. Factory industrial uses that involve the fabrication or manufacturing of noncombustible materials which during finishing, packing or processing do not involve a significant fire hazard shall be classified as F-2 occupancies and shall include, but not be limited to, the following: Medical products; up to and including 12-percent alcohol content Brick and masonry Ceramic products Foundries Glass products Gypsum Ice Metal products (fabrication and assembly) SECTION 2A.7 HIGH-HAZARD GROUP H 2A.7.1 SBC 801 High-Hazard Group H. High-Hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the 2007 2/7 USE AND OCCUPANCY CLASSIFICATION manufacturing, processing, generation or storage of materials that constitute a physical or health hazard in quantities in excess of those found in Tables 5A.7.7(1) and 5A.7.7(2) (see also definition of “Control area”). 2A.7.2 Definitions. The following words and terms shall, for the purposes of this section and as used elsewhere in these code requirements, have the meanings shown herein. AEROSOL. A product that is dispensed from an aerosol container by a propellant. Aerosol products shall be classified by means of the calculation of their chemical heats of combustion and shall be designated Level 1, 2 or 3. Level 1 aerosol products. Those with a total chemical heat of combustion that is less than or equal to 20 kJ/g. Level 2 aerosol products. Those with a total chemical heat of combustion that is greater than 20 kJ/g, but less than or equal to 30 kJ/g. Level 3 aerosol products. Those with a total chemical heat combustion that is greater than 30 kJ/g. AEROSOL CONTAINER. A metal can or a glass or plastic bottle designed to dispense an aerosol. Metal cans shall be limited to a maximum size of 1,000 ml. Glass or plastic bottles shall be limited to a maximum size of 118 ml. BARRICADE. A structure that consists of a combination of walls, floor and roof, which is designed to withstand the rapid release of energy in an explosion and which is fully confined, partially vented or fully vented; or other effective method of shielding from explosive materials by a natural or artificial barrier. Artificial barricade. An artificial mound or revetment a minimum thickness of 914 mm. Natural barricade. Natural features of the ground, such as hills, or timber of sufficient density that the surrounding exposures that require protection cannot be seen from the magazine or building containing explosives when the trees are bare of leaves. BOILING POINT. The temperature at which the vapor pressure of a liquid equals the atmospheric pressure of 101 kPa gage or 760 mm of mercury. Where an accurate boiling point is unavailable for the material in question, or for mixtures, which do not have a constant boiling point, for the purposes of this classification, the 20-percent evaporated point of a distillation performed in accordance with ASTM D 86, shall be used as the boiling point of the liquid. CLOSED SYSTEM. The use of a solid or liquid hazardous material involving a closed vessel or system that remains closed during normal operations where vapors emitted by the product are not liberated outside of the vessel or system and the product is not exposed to the atmosphere during normal operations; and all uses of compressed gases. Examples of closed systems for solids and liquids include product conveyed through a piping system into a closed vessel, system or piece of equipment. SBC 801 COMBUSTIBLE DUST. Finely divided solid material that is 420 microns or less in diameter and which, when dispersed in air in the proper proportions, could be ignited by a flame, spark or other source of ignition. Combustible dust will pass through a U.S. No. 40 standard sieve. 2007 2/8 USE AND OCCUPANCY CLASSIFICATION COMBUSTIBLE FIBERS. Readily ignitable and free-burning fibers, such as cocoa fiber, cloth, cotton, excelsior, hay, hemp, henequen, istle, jute, kapok, oakum, rags, sisal, Spanish moss, straw, tow, wastepaper or other like materials. COMBUSTIBLE LIQUID. A liquid having a closed cup flash point at or above 38°C. Combustible liquids shall be subdivided as follows: Class II. Liquids having a closed cup flash point at or above 38°C and below 60°C. Class IIIA. Liquids having a closed cup flash point at or above 60°C and below 93°C. Class IIIB. Liquids having a closed cup flash point at or above 93°C. The category of combustible liquids does not include compressed gases or cryogenic fluids. COMPRESSED GAS. A material, or mixture of materials which: 1. Is a gas at 20°C or less at 101 kPa of pressure; and 2. Has a boiling point of 20°C or less at 101 kPa which is either liquefied, non-liquefied or in solution, except those gases which have no other health or physical-hazard properties are not considered to be compressed until the pressure in the packaging exceeds 282 kPa at 20°C. The states of a compressed gas are categorized as follows: 1. Non-liquefied compressed gases are gases, other than those in solution, which are in a packaging under the charged pressure and are entirely gaseous at a temperature of 20°C. 2. Liquefied compressed gases are gases that, in a packaging under the charged pressure, are partially liquid at a temperature of 20°C. 3. Compressed gases in solution are non-liquefied gases that are dissolved in a solvent. 4. Compressed gas mixtures consist of a mixture of two or more compressed gases contained in a packaging, the hazard properties of which are represented by the properties of the mixture as a whole. CONTROL AREA. Spaces within a building that are enclosed and bounded by exterior walls, fire walls, fire barriers and roofs, or a combination thereof, where quantities of hazardous materials not exceeding the maximum allowable quantities per control area are stored, dispensed, used or handled. CORROSIVE. A chemical that causes visible destruction of, or irreversible alterations in, living tissue by chemical action at the point of contact. A chemical shall be considered corrosive if, when tested on the intact skin of albino rabbits by the method described in DOTn 49 CFR, Part 173.137, such a chemical destroys or changes irreversibly the structure of the tissue at the point of contact following an exposure period of 4 hours. This term does not refer to action on inanimate surfaces. CRYOGENIC FLUID. A liquid having a boiling point lower than 101°C at an absolute pressure of 101 kPa. SBC 801 DEFLAGRATION. An exothermic reaction, such as the extremely rapid oxidation of a flammable dust or vapor in air, in which the reaction progresses through the unburned material at a rate less than the velocity of sound. A 2007 2/9 USE AND OCCUPANCY CLASSIFICATION deflagration can have an explosive effect. DETACHED BUILDING. A separate single-story building, without a basement or crawl space, used for the storage or use of hazardous materials and located an approved distance from all structures. DETONATION. An exothermic reaction characterized by the presence of a shock wave in the material which establishes and maintains the reaction. The reaction zone progresses through the material at a rate greater than the velocity of sound. The principal heating mechanism is one of shock compression. Detonations have an explosive effect. DISPENSING. The pouring or transferring of any material from a container, tank or similar vessel, whereby vapors, dusts, fumes, mists or gases are liberated to the atmosphere. EXPLOSIVE. Any chemical compound, mixture or device, the primary or common purpose of which is to function by explosion. The term includes, but is not limited to, dynamite, black powder, pellet powder, initiating explosives, detonators, safety fuses, squibs, detonating cord, igniter cord, igniters and display fireworks, 1.3G (Class B, Special). The term “explosive” includes any material determined to be within the scope of USC Title 18: Chapter 40 and also includes any material classified as an explosive other than consumer fireworks, 1.4G (Class C, Common) by the hazardous materials regulations of DOTn 49 CFR. High explosive. Explosive material, such as dynamite, which can be caused to detonate by means of a No. 8 test blasting cap when unconfined. Low explosive. Explosive material that will burn or deflagrate when ignited. It is characterized by a rate of reaction that is less than the speed of sound. Examples of low explosives include, but are not limited to, black powder; safety fuse; igniters; igniter cord; fuse lighters; fireworks, 1.3G (Class B, Special) and propellants, 1.3C. Mass-detonating explosives. Divisions 1.1, 1.2 and 1.5 explosives alone or in combination, or loaded into various types of ammunition or containers, most of which can be expected to explode virtually instantaneously when a small portion is subjected to fire, severe concussion, impact, the impulse of an initiating agent or the effect of a considerable discharge of energy from without. Materials that react in this manner represent a mass explosion hazard. Such an explosive will normally cause severe structural damage to adjacent objects. Explosive propagation could occur immediately to other items of ammunition and explosives stored sufficiently close to and not adequately protected from the initially exploding pile with a time interval short enough so that two or more quantities must be considered as one for quantity-distance purposes. SBC 801 MOI (UN/DOTn) Class 1 explosive. The former classification system used by DOTn included the terms “high” and “low” explosives as defined herein. The following terms further define explosives under the current system applied by (DOTn for all explosive materials defined as hazard Class 1 materials). Compatibility group letters are used in concert with the division to specify further limitations on each division noted (i.e., the letter G identifies the material as a pyrotechnic substance or article containing a pyrotechnic substance and similar materials). 2007 2/10 USE AND OCCUPANCY CLASSIFICATION Division 1.1. Explosives that have a mass explosion hazard. A mass explosion is one which affects almost the entire load instantaneously. Division 1.2. Explosives that have a projection hazard but not a mass explosion hazard. Division 1.3. Explosives that have a fire hazard and either a minor blast hazard or a minor projection hazard or both, but not a mass explosion hazard. Division 1.4. Explosives that pose a minor explosion hazard. The explosive effects are largely confined to the package and no projection of fragments of appreciable size or range is to be expected. An external fire must not cause virtually instantaneous explosion of almost the entire contents of the package. Division 1.5. Very insensitive explosives. This division is comprised of substances that have a mass explosion hazard, but that are so insensitive there is very little probability of initiation or of transition from burning to detonation under normal conditions of transport. Division 1.6. Extremely insensitive articles which do not have a mass explosion hazard. This division is comprised of articles that contain only extremely insensitive detonating substances and which demonstrate a negligible probability of accidental initiation or propagation. FIREWORKS. Any composition or device for the purpose of producing a visible or audible effect for entertainment purposes by combustion, deflagration or detonation that meets the definition of 1.4G fireworks or 1.3G fireworks as set forth herein. FIREWORKS, 1.3G. (Formerly Class B, Special Fireworks.) Large fireworks devices, which are explosive materials, intended for use in fireworks displays and designed to produce audible or visible effects by combustion, deflagration or detonation. Such 1.3G fireworks include, but are not limited to, firecrackers containing more than 130 milligrams (2 grains) of explosive composition, aerial shells containing more than 40 grams of pyrotechnic composition, and other display pieces which exceed the limits for classification as 1.4G fireworks. Such 1.3G fireworks are also described as fireworks, 49 CFR (172) by the DOTn. FIREWORKS, 1.4G. (Formerly Class C, Common Fireworks.) Small fireworks devices containing restricted amounts of pyrotechnic composition designed primarily to produce visible or audible effects by combustion. Such 1.4G fireworks which comply with the construction, chemical composition and labeling regulations of the DOTn, 49 CFR (172) for fireworks, and the local Consumer Product Safety Commission (CPSC) as set forth in CPSC 16 CFR: Parts 1500 and 1507 are not explosive materials for the purpose of these code requirements. FLAMMABLE GAS. A material that is a gas at 20°C or less at 101 kPa of pressure [a material that has a boiling point of 20°C or less at 101 kPa)] which: 1. Is ignitable at 101 kPa when in a mixture of 13 percent or less by volume with air; or 2. Has a flammable range at 101 kPa with air of at least 12 percent, regardless of the lower limit. The limits specified shall be determined at 101 kPa of pressure and a temperature of 20°C in accordance with (ASTM E 681). SBC 801 FLAMMABLE LIQUEFIED GAS. A liquefied compressed gas which, under a charged pressure, is partially liquid at a temperature of 20°C and which is 2007 2/11 USE AND OCCUPANCY CLASSIFICATION flammable. FLAMMABLE LIQUID. A liquid having a closed cup flash point below 38°C. Flammable liquids are further categorized into a group known as Class I liquids. The Class I category is subdivided as follows: Class IA. Liquids having a flash point below 23°C and a boiling point below 38°C. Class IB. Liquids having a flash point below 23°C and a boiling point at or above 38°C. Class IC. Liquids having a flash point at or above 23°C and below 38°C. The category of flammable liquids does not include compressed gases or cryogenic fluids. FLAMMABLE MATERIAL. A material capable of being readily ignited from common sources of heat or at a temperature of 316°C or less. FLAMMABLE SOLID. A solid, other than a blasting agent or explosive, that is capable of causing fire through friction, absorption or moisture, spontaneous chemical change, or retained heat from manufacturing or processing, or which has an ignition temperature below 100°C or which burns so vigorously and persistently when ignited as to create a serious hazard. A chemical shall be considered a flammable solid as determined in accordance with the test method of CPSC 16 CFR; Part 1500.44, if it ignites and burns with a self-sustained flame at a rate greater than 2.5 mm per second along its major axis. FLASH POINT. The minimum temperature in degrees Fahrenheit at which a liquid will give off sufficient vapors to form an ignitable mixture with air near the surface or in the container, but will not sustain combustion. The flash point of a liquid shall be determined by appropriate test procedure and apparatus as specified in ASTM D 56, ASTM D 93 or ASTM D 3278. HANDLING. The deliberate transport by any means to a point of storage or use. HAZARDOUS MATERIALS. Those chemicals or substances that are physical hazards or health hazards as defined and classified in this section and these code requirements, whether the materials are in usable or waste condition. HEALTH HAZARD. A classification of a chemical for which there is statistically significant evidence that acute or chronic health effects are capable of occurring in exposed persons. The term “health hazard” includes chemicals that are toxic or highly toxic, and corrosive. SBC 801 HIGHLY TOXIC. A material which produces a lethal dose or lethal concentration that falls within any of the following categories: 1. A chemical that has a median lethal dose (LD50) of 50 milligrams or less per kilogram of body weight when administered orally to albino rats weighing between 200 and 300 grams each. 2. A chemical that has a median lethal dose (LD50) of 200 milligrams or less per kilogram of body weight when administered by continuous contact for 24 hours (or less if death occurs within 24 hours) with the bare skin of albino rabbits weighing between 2 and 3 kilograms each. 3. A chemical that has a median lethal concentration (LC50) in air of 200 parts 2007 2/12 USE AND OCCUPANCY CLASSIFICATION per million by volume or less of gas or vapor, or 2 milligrams per liter or less of mist, fume or dust, when administered by continuous inhalation for 1 hour (or less if death occurs within 1 hour) to albino rats weighing between 200 and 300 grams each. Mixtures of these materials with ordinary materials, such as water, might not warrant classification as highly toxic. While this system is basically simple in application, any hazard evaluation that is required for the precise categorization of this type of material shall be performed by experienced, technically competent persons. INCOMPATIBLE MATERIALS. Materials that, when mixed, have the potential to react in a manner that generates heat, fumes, gases or by-products which are hazardous to life or property. OPEN SYSTEM. The use of a solid or liquid hazardous material involving a vessel or system that is continuously open to the atmosphere during normal operations and where vapors are liberated, or the product is exposed to the atmosphere during normal operations. Examples of open systems for solids and liquids include dispensing from or into open beakers or containers, dip tank and plating tank operations. OPERATING BUILDING. A building occupied in conjunction with the manufacture, transportation or use of explosive materials. Operating buildings are separated from one another with the use of intraplant or intraline distances. ORGANIC PEROXIDE. An organic compound that contains the bivalent structure and which may be considered to be a structural derivative of hydrogen peroxide where one or both of the hydrogen atoms have been replaced by an organic radical. Organic peroxides can pose an explosion hazard (detonation or deflagration) or they can be shock sensitive. They can also decompose into various unstable compounds over an extended period of time. Class I. Those formulations that are capable of deflagration but not detonation. Class II. Those formulations that burn very rapidly and that pose a moderate reactivity hazard. Class III. Those formulations that burn rapidly and that pose a moderate reactivity hazard. Class IV. Those formulations that burn in the same manner as ordinary combustibles and that pose a minimal reactivity hazard. Class V. Those formulations that burn with less intensity than ordinary combustibles or do not sustain combustion and that pose no reactivity hazard. Unclassified detonable. Organic peroxides that are capable of detonation. These peroxides pose an extremely high explosion hazard through rapid explosive decomposition. SBC 801 OXIDIZER. A material that readily yields oxygen or other oxidizing gas, or that readily reacts to promote or initiate combustion of combustible materials. Examples of other oxidizing gases include bromine, chlorine and fluorine. Class 4. An oxidizer that can undergo an explosive reaction due to contamination or exposure to thermal or physical shock. Additionally, the oxidizer will enhance the burning rate and can cause spontaneous ignition of combustibles. Class 3. An oxidizer that will cause a severe increase in the burning rate of 2007 2/13 USE AND OCCUPANCY CLASSIFICATION combustible materials with which it comes in contact or that will undergo vigorous self-sustained decomposition due to contamination or exposure to heat. Class 2. An oxidizer that will cause a moderate increase in the burning rate or that causes spontaneous ignition of combustible materials with which it comes in contact. Class 1. An oxidizer whose primary hazard is that it slightly increases the burning rate but which does not cause spontaneous ignition when it comes in contact with combustible materials. OXIDIZING GAS. A gas that can support and accelerate combustion of other materials. PHYSICAL HAZARD. A chemical for which there is evidence that it is a combustible liquid, compressed gas, cryogenic, explosive, flammable gas, flammable liquid, flammable solid, organic peroxide, oxidizer, pyrophoric or unstable (reactive) or water-reactive material. PYROPHORIC. A chemical with an auto-ignition temperature in air, at or below a temperature of 54°C. PYROTECHNIC COMPOSITION. A chemical mixture that produces visible light displays or sounds through a self-propagating, heat-releasing chemical reaction which is initiated by ignition. TOXIC. A chemical falling within any of the following categories: 1. A chemical that has a median lethal dose (LD50) of more than 50 milligrams per kilogram, but not more than 500 milligrams per kilogram of body weight when administered orally to albino rats weighing between 200 and 300 grams each. 2. A chemical that has a median lethal dose (LD50) of more than 200 milligrams per kilogram but not more than 1,000 milligrams per kilogram of body weight when administered by continuous contact for 24 hours (or less if death occurs within 24 hours) with the bare skin of albino rabbits weighing between 2 and 3 kilograms each. 3. A chemical that has a median lethal concentration (LC50) in air of more than 200 parts per million but not more than 2,000 parts per million by volume of gas or vapor, or more than 2 milligrams per liter but not more than 20 milligrams per liter of mist, fume or dust, when administered by continuous inhalation for 1 hour (or less if death occurs within 1 hour) to albino rats weighing between 200 and 300 grams each. SBC 801 UNSTABLE (REACTIVE) MATERIAL. A material, other than an explosive, which in the pure state or as commercially produced, will vigorously polymerize, decompose, condense or become self-reactive and undergo other violent chemical changes, including explosion, when exposed to heat, friction or shock, or in the absence of an inhibitor, or in the presence of contaminants, or in contact with incompatible materials. Unstable (reactive) materials are subdivided as follows: Class 4. Materials that in themselves are readily capable of detonation or explosive decomposition or explosive reaction at normal temperatures and pressures. This class includes materials that are sensitive to mechanical or localized thermal shock at normal temperatures and pressures. 2007 2/14 USE AND OCCUPANCY CLASSIFICATION Class 3. Materials that in themselves are capable of detonation or of explosive decomposition or explosive reaction but which require a strong initiating source or which must be heated under confinement before initiation. This class includes materials that are sensitive to thermal or mechanical shock at elevated temperatures and pressures. Class 2. Materials that in themselves are normally unstable and readily undergo violent chemical change but do not detonate. This class includes materials that can undergo chemical change with rapid release of energy at normal temperatures and pressures, and that can undergo violent chemical change at elevated temperatures and pressures. Class 1. Materials that in themselves are normally stable but which can become unstable at elevated temperatures and pressure. WATER-REACTIVE MATERIAL. A material that explodes; violently reacts; produces flammable, toxic or other hazardous gases; or evolves enough heat to cause self-ignition or ignition of nearby combustibles upon exposure to water or moisture. Water-reactive materials are subdivided as follows: Class 3. Materials that react explosively with water without requiring heat or confinement. Class 2. Materials that may form potentially explosive mixtures with water. Class 1. Materials that may react with water with some release of energy, but not violently. 2A.7.3 High-Hazard Group H-1. Buildings and structures which contain materials that present a detonation hazard shall be classified as Group H-1. Such materials shall include, but not be limited to, the following: Explosives: Division 1.1 Division 1.2 Division 1.3 Exception: Materials that are used and maintained in a form where either confinement or configuration will not elevate the hazard from a mass fire to mass explosion hazard shall be allowed in H-2 occupancies. Division 1.4 Exception: Articles, including articles packaged for shipment, that are not regulated as an explosive under Bureau of Alcohol, Tobacco and Firearms regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles shall be allowed in H-3 occupancies. Division 1.5 Division 1.6 Organic peroxides, unclassified detonable Oxidizers, Class 4 Unstable (reactive) materials, Class 3 detonable, and Class 4 Detonable pyrophoric materials 2A.7.4 High-Hazard Group H-2. Buildings and structures which contain materials that present a deflagration hazard or a hazard from accelerated burning shall be classified as Group H-2. Such materials shall include, but not be limited to, the following: Class I, II or IIIA flammable or combustible liquids which are used or stored in normally open containers or systems, or in closed containers or systems SBC 801 2007 2/15 USE AND OCCUPANCY CLASSIFICATION pressurized at more than 103.4 kPa gage Combustible dusts Cryogenic fluids, flammable Flammable gases Organic peroxides, Class I Oxidizers, Class 3, that are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 1,03.3 kPa gage Pyrophoric liquids, solids and gases, non-detonable Unstable (reactive) materials, Class 3, non-detonable Water-reactive materials, Class 3 2A.7.5 High-Hazard Group H-3. Buildings and structures that contain materials that readily support combustion or present a physical hazard shall be classified as Group H-3. Such materials shall include, but not be limited to, the following: Class I, II or IIIA flammable or combustible liquids which are used or stored in normally closed containers or systems pressurized at less than 103 kPa gage Combustible fibers Consumer fireworks, 1.4G (Class C, Common) Cryogenic fluids, oxidizing Flammable solids Organic peroxides, Classes II and III Oxidizers, Classes 1 and 2 Oxidizing gases Unstable (reactive) materials, Class 2 Water-reactive materials, Class 2 2A.7.6 High-Hazard Group H-4. Buildings and structures which contain materials that are health hazards shall be classified as Group H-4. Such materials shall include, but not be limited to, the following: Corrosives Highly toxic materials Toxic materials 2A.7.7 Group H-5 structures. Semiconductor fabrication facilities and comparable research and development areas in which hazardous production materials (HPM) are used and the aggregate quantity of materials is in excess of those listed in Tables 2A.7.7(1) and 2A.7.7(2). Such facilities and areas shall be designed and constructed in accordance with Section 2B.15.9. 2A.7.8 Multiple hazards. Buildings and structures containing a material or materials representing hazards that are classified in one or more of Groups H-1, H-2, H-3 and H-4 shall conform to the code requirements for each of the occupancies so classified. 2A.7.9 Exceptions: The following shall not be classified in Group H, but shall be classified in the occupancy which they most nearly resemble. Hazardous materials in any quantity shall conform to the requirements of SBC 201, including Section 2B.14, and these code requirements: 1. Buildings and structures that contain not more than the maximum allowable quantities per control area of hazardous materials as shown in Tables 2A.7.7(1) and 2A.7.7(2) provided that such buildings are maintained in accordance with these code requirements. SBC 801 2007 2/16 USE AND OCCUPANCY CLASSIFICATION 2. Buildings utilizing control areas in accordance with Section 2B.14.2 that contain not more than the maximum allowable quantities per control area of hazardous materials as shown in Tables 2A.7.7(1) and 2A.7.7(2). 3. Buildings and structures occupied for the application of flammable finishes, provided that such buildings or areas conform to the requirements of Section 2B16 and these code requirements. 4. Wholesale and retail sales and storage of flammable and combustible liquids in mercantile occupancies conforming to these code requirements. 5. Closed systems housing flammable or combustible liquids or gases utilized for the operation of machinery or equipment. SBC 801 2007 2/17 Organic peroxide Flammable solid Combination Flammable liquid (IA, IB, IC) Flammable liquidsc Flammable gas Explosives Cryogenic Flammable Consumer fireworks (Class C Common) Cryogenic Oxidizing Combustible fiber Combustible liquidc, i MATERIAL Not Applicable UD I II III IV V Not Applicable Not Applicable Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.4G Division 1.5 Division 1.6 Gaseous Liquefied IA IB and IC 1.4G CLASS II IIIA IIIB Loose Baled Not Applicable 0.45e, f 2.3d, e 22.7d, e 56.8d, e Not limited Not limited H-1 H-2 H-3 H-3 Not Applicable Not Applicable SBC 801 54.5d, e Not Applicable Not Applicable 0.45e, g 0.45e, g 2.3e, g 22.7e, g 56.8d, e, l 0.45e, g 0.45d, e, g Not Applicable Not Applicable 56.8d, e, l (2.8) (28) Not Applicable Not Applicable Solid kgs (cubic meters) H-3 H2 or H-3 H-2 or H-3 H-2 H-1 H-1 H-1 or H-2 H-3 H-3 H-1 H-1 H-3 H-3 H-2 H-3 GROUP WHEN THE MAXIMUM ALLOWABLE QUANTITY IS EXCEEDED H-2 or H-3 H-2 or H-3 Not Applicable Not Applicable (0.45)e, g (2.3)d, e (22.7)d, e (56.8)d, e Not limited Not limited 454d, e, h e, g (0.45) (0.45)e, g (2.3)e, g (22.7)e, g Not Applicable (0.45)e, g Not Applicable Not Applicable 114d, e 114d, e 454d, e 170d Not Applicable 170d Liquid liters (kgs) 454d, e 1,249d, e 49,962e, f Not Applicable STORAGEb 2007 (continued) Not Applicable Not Applicable 0.114g 0.45d 22.7d 56.8d Not limited Not limited 56.8d Not Applicable Not Applicable Not Applicable 28d, e Not Applicable Not Applicable Not Applicable Solid kgs (cubic meters) (2.8) (28) Not Applicable Not Applicable Not Applicable 0.114g 0.114g 0.45g 22.7g Not Applicable 0.114g Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Gas cubic meters at NTP g Not Applicable (0.114)g (0.45) (22.7)d (56.8)d Not limited Not limited 454d, h (0.114) (0.114)g (0.45)g (22.7)g Not Applicable (0.114)g Not Applicable Not Applicable 114d, e 114d 454d 170d Not Applicable 170d Liquid liters (kgs) 454d 1,249d 49,962e,f Not Applicable 2/18 Not Applicable Not Applicable Not Applicable 28d, e Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Gas cubic meters at NTP USE-CLOSED SYSTEMSb 0.114g 0.45d 4.5d 11.4d Not limited Not limited 11.4d Not Applicable (0.57) (5.7) Not Applicable Not Applicable Not Applicable 0.114g 0.114g 0.45g Not Applicable Not Applicable 0.114g Not Applicable Not Applicable Not Applicable Not Applicable Solid kgs (cubic meters) Not Applicable (0.114)g (0.45)d (4.5)d (11.4)d Not limited Not limited 114d, h (0.114)g (0.114)g (0.45)g Not Applicable Not Applicable (0.114)g Not Applicable Not Applicable 38d 114d 38d Not Applicable 38d Liquid liters (kgs) 114d 303d 12,491f Not Applicable USE-OPEN SYSTEMSb TABLE 2A.7.7(1) a, j, m MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD USE AND OCCUPANCY CLASSIFICATION Gaseous Liquefied CLASS 4 3k 2 1 H-3 Not Applicable Solid kgs (cubic meters) 0.45e, g 4.5d, e 113.5d, e 1,816e, f Liquid liters (kgs) (0.45)e, g (4.5)d, e (113.5)d, e (1,816)e, f Not Applicable 57d, e STORAGEb 42.5d, e Not Applicable Not Applicable Gas cubic meters at NTP Not Applicable Solid kgs (cubic meters) 0.114g 0.9d 113.5d 1,816f Liquid liters (kgs) (0.114)g (0.9)d (113.5)d (1,816)f Not Applicable 57d, e 42.5d, e Not Applicable Not Applicable Gas cubic meters at NTP USE-CLOSED SYSTEMSb Not Applicable Solid kgs (cubic meters) 0.114g 0.9d 22.7d 454f Not Applicable Liquid liters (kgs) (0.114)g (0.9)d (22.7)d (454)f USE-OPEN SYSTEMSb Pyrophoric material SBC 801 2007 2/19 Not (1.8)e, g 1.42e, g 0.45g (0.45)g 0.28e, g 0 0 H-2 1.8e, g Applicable 4 (0.45)e, g 0.28e, g 0.114g (0.114)g 0.057e, g 0.114g (0.114)g H-1 0.45e, g 2.3d, e (2.3)d, e 1.42d, e 0.45d (0.45) 0.28 d, e 0.45d (0.45)d 3 H-1 or H-2 Unstable (reactive) 22.7d, e (22.7)d, e 7.1d, e 22.7d 7.1d, e 4.5d (4.5)d (22.7)d 2 H-3 Not Limited Not Limited Not Limited Not Limited Not Limited Not Limited Not Limited Not Limited 1 Not Applicable H-2 3 2.3d, e (2.3)d, e (2.3)d (0.45)d 2.3d 0.45d Not Not Water reactive H-3 2 22.7d, e (22.7)d, e 22.7d (22.7)d 4.5d (4.5)d Applicable Applicable 1 Not Applicable Not Limited Not Limited Not Limited Not Limited Not Limited Not Limited NL = Not Limited; N/A = Not Applicable; UD = Unclassified Detonable a. For use of control areas, see Section 2B.14.2. b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers not exceeding 5 liters. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 5 liters. d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively. e. Quantities shall be increased 100 percent when stored in approved cabinets, gas cabinets, exhausted enclosures or safety cans as specified in these code requirements. Where Note d also applies, the increase for both notes shall be applied accumulatively. f. The permitted quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. g. Permitted only in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. h. Containing not more than the maximum allowable quantity per control area of Class IA, IB or IC flammable liquids. i. Inside a building, the maximum capacity of a combustible liquid storage system that is connected to a fuel-oil piping system shall be 2,498 liters provided such system conforms to these code requirements. j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. k. A maximum quantity of 91 kilograms of solid or 76 liters of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance purposes, operation or sanitation of equipment. Storage containers and the manner of storage shall be approved. l. Net weight of the pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition of the fireworks is not known, 25 percent of the gross weight of the fireworks, including packaging, shall be used. m. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 2B.14.2.4, see Table 2B.14.2.4. Oxidizing gas Oxidizer MATERIAL GROUP WHEN THE MAXIMUM ALLOWABLE QUANTITY IS EXCEEDED H-1 H-2 H-3 H-3 TABLE 2A.7.7(1)—(continued) a, j, m MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD USE AND OCCUPANCY CLASSIFICATION 227 Toxic SBC 801 (227)i 23f 2007 227 4.5 0.57 (4.5) i h 2,270 Solid kgse 23f, g Gas cubic meterse 1,893 STORAGEd Liquid liters (kgs)e, f (227)i (4.5) i 1,893 23f 0.57 h 23f, g USE-CLOSED SYSTEMSb Liquid liters (kgs)e Gas cubic meterse 2/20 56.8 1.4 454 (56.8)i (1.4)i 379 USE-OPEN SYSTEMSb Solid kgse Liquid liters (kgs)e a. For use of control areas, see Section 2B.14.2. b. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs consumer or industrial products, and cosmetics, containing not more than 50 percent by volume of watermiscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 5 liters. c. For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 2B.14.2.4, see Table 2B.14.2.4. d. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. e. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 7.3.3.1.1. Where Note f also applies, the increase for both notes shall be applied accumulatively. f. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, gas cabinets, or exhausted enclosures. Where Note e also applies, the increase for both notes shall be applied accumulatively. g. A single cylinder containing 68 kilograms or less of anhydrous ammonia in a single control area in a nonsprinklered building shall be considered a maximum allowable quantity. Two cylinders, each containing 68 kilograms or less in a single control area shall be considered a maximum allowable quantity provided the building is equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. h. Allowed only when stored in approved exhausted gas cabinets or exhausted enclosures. i. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. 4.5 2,270 Solid kgse, f Highly toxic Corrosive MATERIAL TABLE 2A.7.7(2) a,b,c MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIAL POSING A HEALTH HAZARD USE AND OCCUPANCY CLASSIFICATION USE AND OCCUPANCY CLASSIFICATION 6. 7. 8. 9. 10. 11. 12. 13. 14. Cleaning establishments that utilize combustible liquid solvents having a flash point of 60°C or higher in closed systems employing equipment listed by an approved testing agency, provided that this occupancy is separated from all other areas of the building by 1 hour fire-resistance-rated fire barrier walls or horizontal assemblies or both. Cleaning establishments which utilize a liquid solvent having a flash point at or above 93°C. Refrigeration systems. The storage or utilization of materials for agricultural purposes on the premises. Stationary batteries utilized for facility emergency power, uninterrupted power supply or telecommunication facilities provided that the batteries are provided with safety venting caps and ventilation is provided in accordance with the SBC 501. Corrosives shall not include personal or household products in their original packaging used in retail display or commonly used building materials. Buildings and structures occupied for aerosol storage shall be classified as Group S-1, provided that such buildings conform to the requirements of these code requirements. Display and storage of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in quantities not exceeding the maximum allowable quantity per control area in Group M or S occupancies complying with Section 2B14.2.4 (Hazardous Materials). The storage of black powder, smokeless propellant and small arms primers in Groups M and R-3 and special industrial explosive devices in Groups B, F, M and S, provided such storage conforms to the quantity limits and requirements prescribed in these code requirements. SECTION 2A.8 INSTITUTIONAL GROUP I 2A.8.1 Institutional Group I. Institutional Group I occupancy includes, among others, the use of a building or structure, or a portion thereof, in which people are cared for or live in a supervised environment, having physical limitations because of health or age are harbored for medical treatment or other care or treatment, or in which people are detained for penal or correctional purposes or in which the liberty of the occupants is restricted. Institutional occupancies shall be classified as Group I-1, I-2, I-3 or I-4. 2A.8.2 Group I-1. This occupancy shall include buildings, structures or parts thereof housing more than 16 persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services. The occupants are capable of responding to an emergency situation without physical assistance from staff. This group shall include, but not be limited to, the following: Residential board and care facilities Assisted living facilities Halfway houses Group homes Congregate care facilities Social rehabilitation facilities Alcohol and drug treatment centers SBC 801 2007 2/21 USE AND OCCUPANCY CLASSIFICATION Convalescent facilities A facility such as the above with five or fewer persons shall be classified as a Group R-3 or shall comply with SBC 100. A facility such as above, housing at least six and not more than 16 persons, shall be classified as Group R-4. 2A.8.3 2A.8.3.1 2A.8.4 2A.8.4.1 2A.8.4.2 2A.8.4.3 2A.8.4.4 2A.8.4.5 SBC 801 Group I-2. This occupancy shall include buildings and structures used for medical, surgical, psychiatric, nursing or custodial care on a 24-hour basis of more than five persons who are not capable of self-preservation. This group shall include, but not be limited to, the following: Hospitals Nursing homes (both intermediate-care facilities and skilled nursing facilities) Mental hospitals Detoxification facilities A facility such as the above with five or fewer persons shall be classified as Group R-3 or shall comply with SBC 100 Child care facility. A child care facility that provides care on a 24-hour basis to more than five children 21/2 years of age or less shall be classified as Group I-2. Group I-3. This occupancy shall include buildings and structures that are inhabited by more than five persons who are under restraint or security. An I-3 facility is occupied by persons who are generally incapable of self-preservation due to security measures not under the occupants’ control. This group shall include, but not be limited to, the following: Prisons Jails Reformatories Detention centers Correctional centers Prerelease centers Buildings of Group I-3 shall be classified as one of the occupancy conditions indicated in Sections 2A.8.4.1 through 2A.8.4.5 (see Section 2B.8.1). Condition 1. This occupancy condition shall include buildings in which free movement is allowed from sleeping areas, and other spaces where access or occupancy is permitted, to the exterior via means of egress without restraint. A Condition 1 facility is permitted to be constructed as Group R. Condition 2. This occupancy condition shall include buildings in which free movement is allowed from sleeping areas and any other occupied smoke compartment to one or more other smoke compartments. Egress to the exterior is impeded by locked exits. Condition 3. This occupancy condition shall include buildings in which free movement is allowed within individual smoke compartments, such as within a residential unit comprised of individual sleeping units and group activity spaces, where egress is impeded by remote-controlled release of means of egress from such a smoke compartment to another smoke compartment. Condition 4. This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Remote-controlled release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments. Condition 5. This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Staff-controlled manual release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments. 2007 2/22 USE AND OCCUPANCY CLASSIFICATION 2A.8.5 2A.8.5.1 2A.8.5.2 Group I-4, day care facilities. This group shall include buildings and structures occupied by persons of any age who receive custodial care for less than 24 hours by individuals other than parents or guardians, relatives by blood, marriage or orphanage, and in a place other than the home of the person cared for. A facility such as the above with five or fewer persons shall be classified as a Group R-3 or shall comply with SBC 100. Places of worship during religious functions are not included. Adult care facility. A facility that provides accommodations for less than 24 hours for more than five unrelated adults and provides supervision and personal care services shall be classified as Group I-4. Exception: A facility where occupants are capable of responding to an emergency situation without physical assistance from the staff shall be classified as Group A3. Child care facility. A facility that provides supervision and personal care on less than a 24-hour basis for more than five children 21/2 years of age or less shall be classified as Group I-4. Exception: A child day care facility that provides care for more than five but no more than 100 children 21/2 years or less of age, when the rooms where such children are cared for are located on the level of exit discharge and each of these child care rooms has an exit door directly to the exterior, shall be classified as Group E. SECTION 2A.9 MERCANTILE GROUP M 2A.9.1 Mercantile Group M. Mercantile Group M occupancy includes, among others, buildings and structures or a portion thereof, for the display and sale of merchandise, and involves stocks of goods, wares or merchandise incidental to such purposes and accessible to the public. Mercantile occupancies shall include, but not be limited to, the following: Department stores Drug stores Markets Motor fuel-dispensing facilities Retail or wholesale stores Sales rooms 2A.9.2 Quantity of hazardous materials. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored or displayed in a single control area of a Group M occupancy shall not exceed the quantities in Table 2B.14.2.4. SECTION 2A.10 RESIDENTIAL GROUP R 2A.10.1 SBC 801 Residential Group R. Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classified as an Institutional Group I. Residential occupancies shall include the following: R-1 Residential occupancies where the occupants are primarily transient in nature, including: Boarding houses (transient) 2007 2/23 USE AND OCCUPANCY CLASSIFICATION Hotels (transient) Motels (transient) R-2 Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including: Apartment houses Boarding houses (not transient) Dormitories Fraternities and sororities Vacation timeshare properties Hotels (non-transient) Motels (non-transient) R-3 Residential occupancies where the occupants are primarily permanent in nature and not classified as R-1, R-2, R-4 or I and where buildings do not contain more than two dwelling units as applicable in SBC 100, or adult and child care facilities that provide accommodations for five or fewer persons of any age for less than 24 hours. Adult and child care facilities that are within a single-family home are permitted to comply with SBC 100. R-4 Residential occupancies shall include buildings arranged for occupancy as residential care/assisted living facilities including more than five but not more than 16 occupants, excluding staff. Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3 except as otherwise provided for in SBC 201 or in accordance with SBC 100. 2A.10.2 Definitions. The following words and terms shall, for the purposes of this section and as used elsewhere in these code requirements, have the meanings shown herein. BOARDING HOUSE. A building arranged or used for lodging for compensation, with or without meals, and not occupied as a single-family unit. DORMITORY. A space in a building where group sleeping accommodations are provided in one room, or in a series of closely associated rooms, for persons not members of the same family group, under joint occupancy and single management, as in college dormitories or fraternity houses. DWELLING UNIT. A single unit providing complete, independent living facilities for one or more persons, including permanent provisions for living, sleeping, eating, cooking and sanitation. PERSONAL CARE SERVICE. The care of residents who do not require chronic or convalescent medical or nursing care. Personal care involves responsibility for the safety of the resident while inside the building. RESIDENTIAL CARE/ASSISTED LIVING FACILITIES. A building or part thereof housing persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment which provides personal care services. The occupants are capable of responding to an emergency situation without physical assistance from staff. This classification shall include, but not be limited to, the following: residential board and care facilities, assisted living facilities, halfway houses, group homes, congregate care facilities, social rehabilitation facilities, alcohol and drug abuse treatment centers and convalescent facilities. SBC 801 2007 2/24 USE AND OCCUPANCY CLASSIFICATION SECTION 2A.11 STORAGE GROUP S 2A.11.1 Storage Group S. Storage Group S occupancy includes, among others, the use of a building or structure, or a portion thereof, for storage that is not classified as a hazardous occupancy. 2A.11.2 Moderate-hazard storage, Group S-1. Buildings occupied for storage uses which are not classified as Group S-2 including, but not limited to, storage of the following: Aerosols, Levels 2 and 3 Aircraft repair hangar Bags; cloth, burlap and paper Bamboos and rattan Baskets Belting; canvas and leather Books and paper in rolls or packs Boots and shoes Buttons, including cloth covered, pearl or bone Cardboard and cardboard boxes Clothing, woolen wearing apparel cordage Furniture Furs Glues, mucilage, pastes and size Grains Horns and combs, other than celluloid Leather Linoleum Lumber Motor vehicle repair garages complying with the maximum allowable quantities of hazardous materials listed in Table 2A.7.7(1) (see Section 2B.6.6) Photo engravings resilient flooring silks Soaps Sugar Tires, bulk storage of Tobacco, cigars, and cigarettes Upholstery and mattresses Wax candles 2A.11.3 Low-hazard storage, Group S-2. Includes, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim, such as knobs, handles or film wrapping. Storage uses shall include, but not be limited to, storage of the following: Aircraft hangar Asbestos Medical products up to and including 12-percent alcohol in metal, glass or ceramic containers Cement in bags Chalk and crayons Dairy products in non-waxed coated paper containers SBC 801 2007 2/25 USE AND OCCUPANCY CLASSIFICATION Dry cell batteries Electrical coils electrical motors Empty cans Food products Foods in noncombustible containers Fresh fruits and vegetables in non-plastic trays or containers Frozen foods Glass Glass bottles, empty or filled with noncombustible liquids Gypsum board Inert pigments Ivory Meats Metal cabinets Metal desks with plastic tops and trim Metal parts Metals Mirrors Oil-filled and other types of distribution transformers Parking garages, open or enclosed Porcelain and pottery Stoves Talc and soap stones Washers and dryers SECTION 2A.12 UTILITY AND MISCELLANEOUS GROUP U 2A.12.1 SBC 801 General. Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and maintained to conform to the requirements of the Saudi Building Code commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following: Agricultural buildings Aircraft hangars, accessory to a one- or two-family residence (see Section 2B.12.3) Barns Carports Fences more than 1.8 m high Grain silos, accessory to a residential occupancy Greenhouses Livestock shelters Private garages Retaining walls Sheds Stables Tanks Towers 2007 2/26 USE AND OCCUPANCY CLASSIFICATION SECTION 2B SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 2B.1 SCOPE 2B.1.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in these code requirements, the provisions of this chapter apply to the special uses and occupancies described herein. SECTION 2B.2 COVERED MALL BUILDINGS 2B.2.1 Scope. The provisions of this section shall apply to buildings or structures defined herein as covered mall buildings not exceeding three floor levels at any point nor more than three stories above grade. Except as specifically required by this section, covered mall buildings shall meet applicable provisions of these code requirements. Exceptions: 1. Foyers and lobbies of Groups B, R-1 and R-2 are not required to comply with this section. 2. Buildings need not comply with the provisions of this section where they totally comply with other applicable provisions of these code requirements. 2B.2.2 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in these code requirements, have the meanings shown herein. ANCHOR BUILDING. An exterior perimeter building of a group other than H having direct access to a covered mall building but having required means of egress independent of the mall. COVERED MALL BUILDING. A single building enclosing a number of tenants and occupants such as retail stores, drinking and dining establishments, entertainment and amusement facilities, passenger transportation terminals, offices, and other similar uses wherein two or more tenants have a main entrance into one or more malls. For the purpose of this chapter, anchor buildings shall not be considered as a part of the covered mall building. FOOD COURT. A public separate seating area for male/families located in the mall that serves adjacent food preparation tenant spaces. GROSS LEASABLE AREA. The total floor area designed for tenant occupancy and exclusive use. The area of tenant occupancy is measured from the centerlines of joint partitions to the outside of the tenant walls. All tenant areas, including areas used for storage, shall be included in calculating gross leasable area. MALL. A roofed or covered common pedestrian area within a covered mall building that serves as access for two or more tenants and not to exceed three levels that are open to each other. SBC 801 2007 2/27 USE AND OCCUPANCY CLASSIFICATION 2B.2.3 Lease plan. Each covered mall building owner shall provide both the building authority and fire civil defense with a lease plan showing the location of each occupancy and its exits after the certificate of occupancy has been issued. No modifications or changes in occupancy or use shall be made from that shown on the lease plan without prior approval of the building official. 2B.2.4 Means of egress. Each tenant space and the covered mall building shall be provided with means of egress as required by this section and these code requirements. Where there is a conflict between the requirements of these code requirements and the requirements of this section, the requirements of this section shall apply. 2B.2.4.1 Determination of occupant load. The occupant load permitted in any individual tenant space in a covered mall building shall be determined as required by these code requirements. Means of egress requirements for individual tenant spaces shall be based on the occupant load thus determined. Occupant formula. In determining required means of egress of the mall, the number of occupants for whom means of egress are to be provided shall be based on gross leasable area of the covered mall building (excluding anchor buildings) and the occupant load factor as determined by the following equation. 2B.2.4.1.1 OLF = ((0.00007) (GLA) + 25) X 0.0929 Where: OLF = The occupant load factor (square meters per person). GLA = The gross leasable area (square meters). 2B.2.4.1.2 2B.2.4.1.3 2B.2.4.1.4 2B.2.4.2 2B.2.4.3 2B.2.4.3.1 2B.2.4.4 SBC 801 (Equation 4-1) OLF range. The occupant load factor (OLF) is not required to be less than 2.8 and shall not exceed 4.6. Anchor buildings. The occupant load of anchor buildings opening into the mall shall not be included in computing the total number of occupants for the mall. Food courts. The occupant load of a food court shall be determined in accordance with Section 8.3. For the purposes of determining the means of egress requirements for the mall, the food court occupant load shall be added to the occupant load of the covered mall building as calculated above. Number of means of egress. Wherever the distance of travel to the mall from any location within a tenant space used by persons other than employees exceeds 23 m or the tenant space exceeds an occupant load of 50, not less than two means of egress shall be provided. Arrangements of means of egress. Assembly occupancies with an occupant load of 500 or more shall be so located in the covered mall building that their entrance will be immediately adjacent to a principal entrance to the mall and shall have not less than one-half of their required means of egress opening directly to the exterior of the covered mall building. Anchor building means of egress. Required means of egress for anchor buildings shall be provided independently from the mall means of egress system. The occupant load of anchor buildings opening into the mall shall not be included in determining means of egress requirements for the mall. The path of egress travel of malls shall not exit through anchor buildings. Malls terminating at an anchor building where no other means of egress has been provided shall be considered as a dead-end mall. Distance to exits. Within each individual tenant space in a covered mall building, the maximum distance of travel from any point to an exit or entrance to the mall 2007 2/28 USE AND OCCUPANCY CLASSIFICATION 2B.2.4.5 2B.2.4.5.1 2B.2.4.6 2B.2.5 2B.2.5.1 shall not exceed 61 m. The maximum distance of travel from any point within a mall to an exit shall not exceed 61 m. Access to exits. Where more than one exit is required, they shall be so arranged that it is possible to travel in either direction from any point in a mall to separate exits. The minimum width of an exit passageway or corridor from a mall shall be 1.7 m. Exception: Dead ends not exceeding a length equal to twice the width of the mall measured at the narrowest location within the dead-end portion of the mall. Exit passageway enclosures. Where exit passageway enclosures provide a secondary means of egress from a tenant space, doors to the exit passageway enclosures shall be 1 hour fire doors. Such doors shall be self-closing and be so maintained or shall be automatic-closing by smoke detection. Service areas fronting on exit passageways. Mechanical rooms, electrical rooms, building service areas and service elevators are permitted to open directly into exit passageways provided that the exit passageway is separated from such rooms with 1 hour fire-resistance-rated walls and 1 hour opening protectives. Mall width. For the purpose of providing required egress, malls are permitted to be considered as corridors but need not comply with the requirements of Section 8.5.1 of these code requirements where the width of the mall is as specified in this section. Minimum width. The minimum width of the mall shall be 6.1 m. The mall width shall be sufficient to accommodate the occupant load served. There shall be a minimum of 3.1 m clear exit width to a height of 2.4 m between any projection of a tenant space bordering the mall and the nearest kiosk, vending machine, bench, display opening, food court or other obstruction to means of egress travel. 2B.2.6 Types of construction. The area of any covered mall building, including anchor buildings, of Type I, II, III and IV construction, shall not be limited provided the covered mall building and attached anchor buildings and parking garages are surrounded on all sides by a permanent open space of not less than 18.3 m and the anchor buildings do not exceed three stories in height. The allowable height and area of anchor buildings greater than three stores in height shall comply with Section 3.3, as modified by Sections 3.4 and 3.6. The construction type of open parking garages and enclosed parking garages shall comply with Sections 2B.6.3 and 2B.6.4 respectively. 2B.2.7 Fire-resistance-rated separation. Fire-resistance-rated separation is not required between tenant spaces and the mall. Fire-resistance-rated separation is not required between a food court and adjacent tenant spaces or the mall. Attached garage. An attached garage for the storage of passenger vehicles having a capacity of not more than nine persons and open parking garages shall be considered as a separate building where it is separated from the covered mall building by a fire barrier having a fire-resistance rating of at least 2 hours. Exception: Where an open parking garage or enclosed parking garage is separated from the covered mall building or anchor building a distance greater than 3.1 m, the provisions of Table 4A.2 shall apply. Pedestrian walkways and tunnels which attach the open parking garage or enclosed parking garage to the covered mall building or anchor building shall be constructed in accordance with Section 4.4 of SBC 201. Tenant separations. Each tenant space shall be separated from other tenant spaces 2B.2.7.1 2B.2.7.2 SBC 801 2007 2/29 USE AND OCCUPANCY CLASSIFICATION 2B.2.7.3 2B.2.7.3.1 2B.2.8 2B.2.8.1 by a fire partition complying with Section 4B.8. A tenant separation wall is not required between any tenant space and the mall. Anchor building separation. An anchor building shall be separated from the covered mall building by fire walls complying with Section 4B.6. Exception: Anchor buildings of not more than three stories above grade which have an occupancy classification of the same uses permitted as tenants of the covered mall building shall be separated by 2 hours fire resistive fire-barriers complying with Section 4B.6. Openings between anchor building and mall. Except for the separation between Group R-1 sleeping units and the mall, openings between anchor buildings of Type IA, IB, IIA and IIB construction and the mall need not be protected. Automatic sprinkler system. The covered mall building and buildings connected shall be provided throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1, which shall comply with the following: 1. The automatic sprinkler system shall be complete and operative throughout occupied space in the covered mall building prior to occupancy of any of the tenant spaces. Unoccupied tenant spaces shall be similarly protected unless provided with approved alternate protection. 2. Sprinkler protection for the mall shall be independent from that provided for tenant spaces or anchors. Where tenant spaces are supplied by the same system, they shall be independently controlled. Exception: An automatic sprinkler system shall not be required in spaces or areas of open parking garages constructed in accordance with Section 2B.6.2. Standpipe system. The covered mall building shall be equipped throughout with a standpipe system as required by Section 7.5.3.3. 2B.2.9 Smoke control. A smoke control system shall be provided where required for atriums in Section 2B.4. 2B.2.10 Kiosks. Kiosks and similar structures (temporary or permanent) shall meet the following requirements: 1. Combustible kiosks or other structures shall not be located within the mall unless constructed of any of the following materials: 1.1 Fire-retardant-treated wood complying with Section 11.14 of SBC 201. 1.2 Foam plastics having a maximum heat release rate not greater than 105 Btu/h when tested in accordance with the exhibit booth protocol in UL 1975. 1.3 Aluminum composite material (ACM) having a flame spread index of not more than 25 and a smoke-developed index of not more than 450 when tested as an assembly in the maximum thickness intended for use in accordance with ASTM E 84. 2. Kiosks or similar structures located within the mall shall be provided with approved fire suppression and detection devices. 3. The minimum horizontal separation between kiosks or groupings thereof and other structures within the mall shall be 6.1 m. 4. Each kiosk or similar structure or groupings thereof shall have a maximum area of 28 m2. 2B.2.11 Security grilles and doors. Horizontal sliding or vertical security grilles or doors that are a part of a required means of egress shall conform to the following: 1. They shall remain in the full open position during the period of occupancy by SBC 801 2007 2/30 USE AND OCCUPANCY CLASSIFICATION the general public. 2. Doors or grilles shall not be brought to the closed position when there are more than 10 persons occupying spaces served by a single exit or 50 persons occupying spaces served by more than one exit. 3. The doors or grilles shall be openable from within without the use of any special knowledge or effort where the space is occupied. 4. Where two or more exits are required, not more than one-half of the exits shall be permitted to include either a horizontal sliding or vertical rolling grille or doors. 2B.2.12 Standby power. Covered mall buildings exceeding 4,645 m2 shall be provided with standby power systems that are capable of operating the emergency voice/alarm communication system. 2B.2.13 Emergency voice/alarm communication system. Covered mall buildings exceeding 4,645 m2 in total floor area shall be provided with an emergency voice/alarm communication system. Emergency voice/alarm communication systems serving a mall required or otherwise, shall be accessible to the fire civil defense. The system shall be provided in accordance with Section 7.7.2.12.2. Plastic signs. Within every store or level and from sidewall to sidewall of each tenant space facing the mall, plastic signs shall be limited as specified in Sections 2B.2.14.1 through 2B.2.14.5. 2B.2.14.1 Area. Plastic signs shall not exceed 20 percent of the wall area facing the mall. 2B.2.14.2 Height and width. Plastic signs shall not exceed a height of 914 mm, except if the sign is vertical, the height shall not exceed 2438 mm and the width shall not exceed 914 mm. 2B.2.14.3 Location. Plastic signs shall be located a minimum distance of 457 mm from adjacent tenants. 2B.2.14.4 Plastics other than foam plastics. Plastics other than foam plastics used in signs shall be light-transmitting plastics complying with Section 11.6.4 of SBC 201 or shall have a self-ignition temperature of 343°C or greater when tested in accordance with ASTM D 1929, and a flame spread index not greater than 75 and smoke-developed index not greater than 450 when tested in the manner intended for use in accordance with ASTM E 84 or meet the acceptance criteria of Section 6.3.2.1 when tested in accordance with NFPA 286. 2B.2.14.4.1 Encasement. Edges and backs of plastic signs in the mall shall be fully encased in metal. 2B.2.14.5 Foam plastics. Foam plastics used in signs shall have flame-retardant characteristics such that the sign has a maximum heat-release rate of 150 kilowatts when tested in accordance with UL 1975 and the foam plastics shall have the physical characteristics specified in this section. Foam plastics used in signs installed in accordance with Section 2B2.14 shall not be required to comply with the flame spread and smoke-developed indexes specified in Section 11.3.3 of SBC 201. 2B.2.14.5.1 Density. The minimum density of foam plastics used in signs shall not be less than 320 kg/m3. 2B.2.14.5.2 Thickness. The thickness of foam plastic signs shall not be greater than 12.7 mm. 2B.2.14 2B.2.15 SBC 801 Civil defense access to equipment. Rooms or areas containing controls for airconditioning systems, automatic fire-extinguishing systems or other detection, suppression or control elements shall be identified for use by the fire Civil 2007 2/31 USE AND OCCUPANCY CLASSIFICATION Defence. SECTION 2B.3 HIGH-RISE BUILDINGS 2B.3.1 Applicability. The provisions of this section shall apply to buildings having occupied floors located more than 23 m above the lowest level of Civil Defence vehicle access. Exception: The provisions of this section shall not apply to the following buildings and structures: 1. Airport traffic control towers in accordance with Section 2B.12. 2. Open parking garages in accordance with Section 2B.6.3. 3. Buildings with an occupancy in Group A-5 in accordance with Section 2A3.1. 4. Low-hazard special industrial occupancies in accordance with Section 3.3.1.2. 5. Buildings with an occupancy in Group H-1, H-2 or H-3 in accordance with Section 2B.15. 2B.3.2 Automatic sprinkler system. Buildings and structures shall be equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1 and a secondary water supply where required by Section 7.3.3.5.2. Exception: An automatic sprinkler system shall not be required in spaces or areas of: 1. Open parking garages in accordance with Section 2B.6.3. 2. Telecommunications equipment buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided that those spaces or areas are equipped throughout with an automatic fire detection system in accordance with Section 7.7.2 and are separated from the remainder of the building with fire barriers consisting of 1 hour fire-resistance-rated walls and 2 hours fireresistance-rated floor/ceiling assemblies. 2B.3.3 Reduction in fire-resistance rating. The fire-resistance-rating reductions listed in Sections 2B.3.3.1 and 2B.3.3.2 shall be allowed in buildings that have sprinkler control valves equipped with supervisory initiating devices and water-flow initiating devices for each floor. Type of construction. The following reductions in the minimum construction type allowed in Table 4A.1 shall be allowed as provided in Section 2B.3.3: 1. Type IA construction shall be allowed to be reduced to Type IB. 2. In other than Groups F-1, M and S-1, Type IB construction shall be allowed to be reduced to Type IIA. 3. The height and area limitations of the reduced construction type shall be allowed to be the same as for the original construction type. Shaft enclosures. The required fire-resistance rating of the fire barrier walls enclosing vertical shafts, other than exit enclosures and elevator hoistway enclosures, shall be reduced to 1 hour where automatic sprinklers are installed within the shafts at the top and at alternate floor levels. 2B.3.3.1 2B.3.3.2 2B.3.4 Emergency escape and rescue. Emergency escape and rescue openings required by Section 8.25 are not required. 2B.3.5 Automatic fire detection. Smoke detection shall be provided in accordance with Section 7.7.2.12.1. SBC 801 2007 2/32 USE AND OCCUPANCY CLASSIFICATION 2B.3.6 Emergency voice/alarm communication systems. An emergency voice/alarm communication system shall be provided in accordance with Section 7.7.2.12.2. 2B.3.7 Fire civil defense communications system. A two-way fire civil defense communications system shall be provided for Civil Defence use in accordance with Section 7.7.2.12.3. 2B.3.8 Fire command. A fire command center complying with Section 7.11 shall be provided in a location approved by the Civil Defence. 2B.3.9 Elevators. Elevator operation and installation shall be in accordance with SBC 501. 2B.3.10 Standby power. A standby power system complying with SBC 401 shall be provided for standby power loads specified in Section 2B.3.10.2. Special requirements for standby power systems. If the standby system is a generator set inside a building, the system shall be located in a separate room enclosed with 2 hours fire-resistance-rated fire barrier assemblies. System supervision with manual start and transfer features shall be provided at the fire command center. Standby power loads. The following are classified as standby power loads: 1. Power and lighting for the fire command center required by Section 2B.3.8; 2. Electrically powered fire pumps; 3. Ventilation and automatic fire detection equipment for smokeproof enclosures. Standby power shall be provided for elevators in accordance with SBC 501. 2B.3.10.1 2B.3.10.2 2B.3.11 2B.3.11.1 2B.3.12 2B.3.12.1 Emergency power systems. An emergency power system complying with SBC 401 shall be provided for emergency power loads specified in Section 2B.3.11.1. Emergency power loads. The following are classified as emergency power loads: 1. Exit signs and means of egress illumination required by Chapter 8; 2. Elevator car lighting; 3. Emergency voice/alarm communications systems; 4. Automatic fire detection systems; and 5. Fire alarm systems. Stairway door operation. Stairway doors other than the exit discharge doors shall be permitted to be locked from stairway side. Stairway doors that are locked from the stairway side shall be capable of being unlocked simultaneously without unlatching upon a signal from the fire command center. Stairway communications system. A telephone or other two-way communications system connected to an approved constantly attended station shall be provided at not less than every fifth floor in each required stairway where the doors to the stairway are locked. 2B.3.13 Smokeproof exit enclosures. Every required stairway serving floors more than 23 m above the lowest level of civil defense vehicle access shall comply with Sections 7.9.20 and 8.19.1.8. 2B.3.14 Seismic considerations. For seismic considerations, see SBC 301. SBC 801 2007 2/33 USE AND OCCUPANCY CLASSIFICATION SECTION 2B.4 ATRIUMS 2B.4.1 2B.4.1.1 General. Vertical openings meeting the requirements of this section are not required to be enclosed in other than Group H occupancies. Definition. The following word and term shall, for the purposes of this chapter and as used elsewhere in these code requirements, have the meaning shown herein. ATRIUM. An opening connecting two or more stories other than enclosed stairways, elevators, hoistways, escalators, plumbing, electrical, air-conditioning or other equipment, which is closed at the top and not defined as a mall. Stories, as used in this definition, do not include balconies within assembly groups or mezzanines that comply with Section 3.5. 2B.4.2 Use. The floor of the atrium shall not be used for other than low fire hazard uses and only approved materials and decorations in accordance with these code requirements shall be used in the atrium space. Exception: The atrium floor area is permitted to be used for any approved use where the individual space is provided with an automatic sprinkler system in accordance with Section 7.3.3.1.1. 2B.4.3 Automatic sprinkler protection. An approved automatic sprinkler system shall be installed throughout the entire building. Exceptions: 1. That area of a building adjacent to or above the atrium need not be sprinklered provided that portion of the building is separated from the atrium portion by a 2 hours fire barrier wall or horizontal assembly or both. 2. Where the ceiling of the atrium is more than 17 m above the floor, sprinkler protection at the ceiling of the atrium is not required. 2B.4.4 Smoke control. A smoke control system shall be installed in accordance with Section 7.9. Exceptions: 1. Smoke control is not required for floor openings meeting the requirements of Section 4B.7.2, Exception 2, 7, 8 or 9. 2. Smoke control is not required for floor openings meeting the requirements of Section 8.19.1, Exception 8 or 9. 2B.4.5 Enclosure of atriums. Atrium spaces shall be separated from adjacent spaces by a 1 hour fire barrier wall. Exceptions: 1. A glass wall forming a smoke partition where automatic sprinklers are spaced 1.8 m or less along both sides of the separation wall, or on the room side only if there is not a walkway on the atrium side, and between 102 mm and 305 mm away from the glass and so designed that the entire surface of the glass is wet upon activation of the sprinkler system. The glass shall be installed in a gasketed frame so that the framing system deflects without breaking (loading) the glass before the sprinkler system operates. 2. A glass-block wall assembly in accordance with SBC 305 and having a 3/4 hour fire protection rating. 3. The adjacent spaces of any three floors of the atrium shall not be required to be separated from the atrium where such spaces are included in computing the SBC 801 2007 2/34 USE AND OCCUPANCY CLASSIFICATION 2B.4.6 atrium volume for the design of the smoke control system. Standby power. Equipment required to provide smoke control shall be connected to a standby power system in accordance with Section 7.9.11. 2B.4.7 Interior finish. The interior finish of walls and ceilings of the atrium shall not be less than Class B with no reduction in class for sprinkler protection. 2B.4.8 Travel distance. In other than the lowest level of the atrium, where the required means of egress is through the atrium space, the portion of exit access travel distance within the atrium space shall not exceed 61 m. SECTION 2B.5 UNDERGROUND BUILDINGS 2B.5.1 General. The provisions of this section apply to building spaces having a floor level used for human occupancy more than 9.1 m below the lowest level of exit discharge. Exceptions: 1. One- and two-family dwellings, sprinklered in accordance with Section 7.3.3.1.3. 2. Parking garages with automatic fire suppression systems in compliance with Section 2B.5.3. 3. Fixed guideway transit systems. 4. Grandstands, bleachers, stadiums, arenas and similar facilities. 5. Where the lowest story is the only story that would qualify the building as an underground building and has an area not exceeding 139 m2 and has an occupant load less than 10. 2B.5.2 Construction requirements. The underground portion of the building shall be of Type I construction. 2B.5.3 Automatic sprinkler system. The highest level of exit discharge serving the underground portions of the building and all levels below shall be equipped with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1. Water-flow switches and control valves shall be supervised in accordance with Section 7.3.4. 2B.5.4 Compartmentation. Compartmentation shall be in accordance with Sections 2B.5.4.1 through 2B.5.4.3. Number of compartments. A building having a floor level more than 18.3 m below the lowest level of exit discharge shall be divided into a minimum of two compartments of approximately equal size. Such compartmentation shall extend through the highest level of exit discharge serving the underground portions of the building and all levels below. Exception: The lowest story need not be compartmented where the area does not exceed 139 m2 and has an occupant load of less than 10. Smoke barrier penetration. The separation between the two compartments shall be of minimum 1 hour fire barrier wall construction that shall extend from floor slab to floor deck above. Openings between the two compartments shall be limited to plumbing and electrical piping and conduit penetrations fire stopped in accordance with Section 4B.12. Doorways shall be protected by door assemblies that are automatic-closing by smoke detection in accordance with Section 4B.15.3 2B.5.4.1 2B.5.4.2 SBC 801 2007 2/35 USE AND OCCUPANCY CLASSIFICATION 2B.5.4.3 2B.5.5 2B.5.5.1 2B.5.5.2 and shall be provided with gasketing and a drop sill to minimize smoke leakage. Where provided, each compartment shall have an air supply and an exhaust system independent of the other compartments. Elevators. Where elevators are provided, each compartment shall have direct access to an elevator. Where an elevator serves more than one compartment, an elevator lobby shall be provided and shall be separated from each compartment by a 1 hour fire barrier wall. Doors shall be gasketed, have a drop sill, and be automatic-closing by smoke detection installed in accordance with Section 7.7.10. Smoke control system. A smoke control system shall be provided in accordance with Sections 2B.5.5.1 and 2B.5.5.2. Control system. A smoke control system is required to control the migration of products of combustion in accordance with Section 7.9 and the provisions of this section. Smoke control shall restrict movement of smoke to the general area of fire origin and maintain means of egress in a usable condition. Smoke exhaust system. Where compartmentation is required, each compartment shall have an independent smoke control system. The system shall be automatically activated and capable of manual operation in accordance with Section 7.7.2.18. 2B.5.6 Fire alarm systems. A fire alarm system shall be provided where required by Section 7.7.2.19. 2B.5.7 Public address. A public address system shall be provided where required by Section 7.7.2.19.1. 2B.5.8 Means of egress. Means of egress shall be in accordance with Sections 2B.5.8.1 and 2B.5.8.2. Number of exits. Each floor level shall be provided with a minimum of two exits. Where compartmentation is required by Section 2B.5.4, each compartment shall have a minimum of one exit and shall also have an exit access doorway into the adjoining compartment. Smokeproof enclosure. Every required stairway serving floor levels more than 9.1 m below its level of exit discharge shall comply with the requirements for a smokeproof enclosure as provided in Section 8.19.1.8. 2B.5.8.1 2B.5.8.2 2B.5.9 2B.5.9.1 2B.5.9.2 2B.5.10 2B.5.10.1 SBC 801 Standby power. A standby power system complying with SBC 401 shall be provided standby power loads specified in Section 2B.5.9.1. Standby power loads. The following loads are classified as standby power loads. 1. Smoke control system. 2. Ventilation and automatic fire detection equipment for smokeproof enclosures. 3. Fire pumps. Standby power shall be provided for elevators in accordance with SBC 501. Pick-up time. The standby power system shall pick up its connected loads within 60 seconds of failure of the normal power supply. Emergency power. An emergency power system complying with SBC 401 shall be provided for emergency power loads specified in Section 2B.5.10.1. Emergency power loads. The following loads are classified as emergency power loads: 1. Emergency voice/alarm communications systems. 2. Fire alarm systems. 2007 2/36 USE AND OCCUPANCY CLASSIFICATION 3. Automatic fire detection systems. 4. Elevator car lighting. 5. Means of egress and exit sign illumination as required by Chapter 8. 2B.5.11 Standpipe system. The underground building shall be provided throughout with a standpipe system in accordance with Section 7.5. SECTION 2B.6 MOTOR-VEHICLE-RELATED OCCUPANCIES 2B.6.1 2B.6.1.1 2B.6.1.2 2B.6.1.3 2B.6.1.4 SBC 801 Private garages and carports. Classification. Buildings or parts of buildings classified as Group U occupancies because of the use or character of the occupancy shall not exceed 93 m2 in area or one story in height except as provided in Section 2B.6.1.2. Any building or portion thereof that exceeds the limitations specified in this section shall be classified in the occupancy group other than Group U that it most nearly resembles. Area increase. Group U occupancies used for the storage of private or pleasuretype motor vehicles where no repair work is done or fuel dispensed are permitted to be 279 m2, when the following provisions are met: 1. For a mixed occupancy building, the exterior wall and opening protection for the Group U portion of the building shall be as required for the major occupancy of the building. For such mixed occupancy building, the allowable floor area of the building shall be as permitted for the major occupancy contained therein. 2. For a building containing only Group U occupancy, the exterior wall and opening protection shall be as required for a Group R-1 or R-2 occupancy. More than one 279 m2 Group U occupancy shall be permitted to be in the same building, provided each 279 m2 area is separated by fire walls complying with Section 4B.6. Garages and carports. Carports shall be open on at least two sides. Carport floor surfaces shall be of approved noncombustible material. Carports not open on at least two sides shall be considered a garage and shall comply with the provisions of this section for garages. Exception: Asphalt surfaces shall be permitted at ground level in carports. The area of floor used for parking of automobiles or other vehicles shall be sloped to facilitate the movement of liquids to a drain or toward the main vehicle entry doorway. Separation. Separations shall comply with the following: 1. The private garage shall be separated from the dwelling unit and its attic area by means of a minimum 12.7 mm gypsum board applied to the garage side. Garages beneath habitable rooms shall be separated from all habitable rooms above by not less than 16 mm Type X gypsum board or equivalent. Door openings between a private garage and the dwelling unit shall be equipped with either solid wood doors, or solid or honeycomb core steel doors not less than 35 m thick, or doors in compliance with Section 4B.15.3.3. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. 2. Ducts in a private garage and ducts penetrating the walls or ceilings separating the dwelling unit from the garage shall be constructed of a minimum 0.48 mm sheet steel and shall have no openings into the garage. 3. A separation is not required between a Group R-3 and U carport provided the carport is entirely open on two or more sides and there are not enclosed areas 2007 2/37 USE AND OCCUPANCY CLASSIFICATION 2B.6.2 2B.6.2.1 2B.6.2.2 2B.6.2.3 2B.6.2.4 2B.6.2.5 2B.6.2.6 2B.6.2.7 2B.6.2.8 2B.6.2.9 2B.6.3 2B.6.3.1 2B.6.3.2 above. Parking garages. Classification. Parking garages shall be classified as open, as defined in Section 2B.6.3, or enclosed and shall meet the appropriate criteria in Section 2B.6.4. Also see Section 3.8 for special provisions for parking garages. Clear height. The clear height of each floor level in vehicle and pedestrian traffic areas shall not be less than 2.1 m. Vehicle and pedestrian areas accommodating van-accessible parking required by Section 9.6.5 of the SBC 201 shall conform to ICC A117.1. Guards. Guards shall be provided in accordance with Section 8.12 at exterior and interior vertical openings on floor and roof areas where vehicles are parked or moved and where the vertical distance to the ground or surface directly below exceeds 762 mm. Vehicle barriers. Parking areas shall be provided with exterior or interior walls or vehicle barriers, except at pedestrian or vehicular accesses, designed in accordance with SBC 301. Vehicle barriers not less than 607 mm high shall be placed at the ends of drive lanes, at the end of parking spaces where the difference in adjacent floor elevation is greater than 305 mm. Ramps. Vehicle ramps shall not serve as an exit element. Floor surface. Parking surfaces shall be of concrete or similar noncombustible and nonabsorbent materials. Exception: Asphalt parking surfaces are permitted at ground level. The area of floor used for parking of automobiles or other vehicles shall be sloped to facilitate the movement of liquids to a drain or toward the main vehicle entry doorway. Mixed separation. Parking garages shall be separated from other occupancies in accordance with Section 2A.2.1.1. Special hazards. Connection of a parking garage with any room in which there is a fuel-fired appliance shall be by means of a vestibule providing a two-doorway separation. Exception: A single door shall be allowed provided the sources of ignition in the appliance are at least 457 mm above the floor. Attached to rooms. Openings from a parking garage directly into a room used for sleeping purposes shall not be permitted. Open parking garages. Scope. Except where specific provisions are made in the following subsections, other requirements of these code requirements shall apply. Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in these code requirements, have the meanings shown herein. MECHANICAL-ACCESS OPEN PARKING GARAGES. Open parking garages employing parking machines, lifts, elevators or other mechanical devices for vehicles moving from and to street level and in which public occupancy is prohibited above the street level. OPEN PARKING GARAGE. A structure or portion of a structure with the openings as described in Section 2B.6.3.3.1 on two or more sides that is used for the parking or storage of private motor vehicles as described in Section 2B.6.3.4. SBC 801 RAMP-ACCESS OPEN PARKING GARAGES. Open parking garages 2007 2/38 USE AND OCCUPANCY CLASSIFICATION employing a series of continuously rising floors or a series of interconnecting ramps between floors permitting the movement of vehicles under their own power from and to the street level. 2B.6.3.3 2B.6.3.3.1 2B.6.3.4 2B.6.3.5 2B.6.3.5.1 Construction. Open parking garages shall be of Type I, II or IV construction. Open parking garages shall meet the design requirements of SBC 301. For vehicle barriers, see Section 2B.6.2.4. Openings. For natural ventilation purposes, the exterior side of the structure shall have uniformly distributed openings on two or more sides. The area of such openings in exterior walls on a tier must be at least 20 percent of the total perimeter wall area of each tier. The aggregate length of the openings considered to be providing natural ventilation shall constitute a minimum of 40 percent of the perimeter of the tier. Interior walls shall be at least 20 percent open with uniformly distributed openings. Exception: Openings are not required to be distributed over 40 percent of the building perimeter where the required openings are uniformly distributed over two opposing sides of the building. Uses. Mixed uses shall be allowed in the same building as an open parking garage subject to the provisions of Sections 2A.2.3, 2B.2.7.1, 2B.6.3.13, 3.8.3, 3.8.5 and 3.8.8 Area and height. Area and height of open parking garages shall be limited as set forth in Chapter 3 for Group S-2 occupancies and as further provided for in Section 2A.2.3. Single use. When the open parking garage is used exclusively for the parking or storage of private motor vehicles, with no other uses in the building, the area and height shall be permitted to comply with Table 2B.6.3.5, along with increases allowed by Section 2B.6.3.6. Exception: The grade-level tier is permitted to contain an office, waiting and toilet rooms having a total combined area of not more than 93 m2. Such area need not be separated from the open parking garage. In open parking garages having a spiral or sloping floor, the horizontal projection of the structure at any cross section shall not exceed the allowable area per parking tier. In the case of an open parking garage having a continuous spiral floor, each 2.9 m of height, or portion thereof, shall be considered a tier. The clear height of a parking tier shall not be less than 2.1 m, except that a lower clear height is permitted in mechanical-access open parking garages where approved by the building official. TABLE 2B.6.3.5 OPEN PARKING GARAGES AREA AND HEIGHT Ramp access IA Unlimited IB TYPE OF CONSTRUCTION SBC 801 HEIGHT (in tiers) AREA PER TIER (square meters) Mechanical access Automatic sprinkler system No Yes Unlimited Unlimited Unlimited Unlimited 12 tiers 12 tiers 18 tiers IIA 4,645 10 tiers 10 tiers 15 tiers IIB 4,645 8 tiers 8 tiers 12 tiers IV 4,645 4 tiers 4 tiers 4 tiers 2007 2/39 USE AND OCCUPANCY CLASSIFICATION 2B.6.3.6 2B.6.3.7 2B.6.3.8 2B.6.3.9 2B.6.3.10 2B.6.3.11 2B.6.3.12 2B.6.3.13 2B.6.4 SBC 801 Area and height increases. The allowable area and height of open parking garages shall be increased in accordance with the provisions of this section. Garages with sides open on three-fourths of the building perimeter are permitted to be increased by 25 percent in area and one tier in height. Garages with sides open around the entire building perimeter are permitted to be increased 50 percent in area and one tier in height. For a side to be considered open under the above provisions, the total area of openings along the side shall not be less than 50 percent of the interior area of the side at each tier, and such openings shall be equally distributed along the length of the tier. Allowable tier areas in Table 2B.6.3.5 shall be increased for open parking garages constructed to heights less than the table maximum. The gross tier area of the garage shall not exceed that permitted for the higher structure. At least three sides of each such larger tier shall have continuous horizontal openings not less than 762 mm in clear height extending for at least 80 percent of the length of the sides, and no part of such larger tier shall be more than 61 m horizontally from such an opening. In addition, each such opening shall face a street or yard accessible to a street with a width of at least 9.1 m for the full length of the opening, and standpipes shall be provided in each such tier. Open parking garages of Type IB and II construction, with all sides open, shall be unlimited in allowable area where the height does not exceed 23 m. For a side to be considered open, the total area of openings along the side shall not be less than 50 percent of the interior area of the side at each tier, and such openings shall be equally distributed along the length of the tier. All portions of tiers shall be within 61 m horizontally from such openings. Location on property. Exterior walls and openings in exterior walls shall comply with Tables 4A.1 and 4A.2. The distance from an adjacent property line shall be determined in accordance with Table 4A.2 and Section 4B.4. Means of egress. Where persons other than parking attendants are permitted, open parking garages shall meet the means of egress requirements of Chapter 8 where no persons other than parking attendants are permitted, there shall not be less than two 914 mm exit stairways. Lifts shall be permitted to be installed for use of employees only, provided they are completely enclosed by noncombustible materials. Standpipes. Standpipes shall be installed where required by the provisions of Chapter 7. Sprinkler systems. Where required by other provisions or these code requirements, automatic sprinkler systems and standpipes shall be installed in accordance with the provisions of Chapter 7. Enclosure of vertical openings. Enclosure shall not be required for vertical openings except as specified in Section 2B.6.3.8. Ventilation. Ventilation, other than the percentage of openings specified in Section 2B.6.3.3.1, shall not be required. Prohibitions. The following uses and alterations are not permitted: 1. Vehicle repair work. 2. Parking of buses, trucks and similar vehicles. 3. Partial or complete closing of required openings in exterior walls by tarpaulins or any other means. 4. Dispensing of fuel. Enclosed parking garages. Enclosed vehicle parking garages and portions thereof that do not meet the definition of open parking garages shall be limited to the 2007 2/40 USE AND OCCUPANCY CLASSIFICATION 2B.6.4.2 2B.6.5 2B.6.5.1 2B.6.5.2 2B.6.6 2B.6.6.1 2B.6.6.2 2B.6.6.3 2B.6.6.4 2B.6.6.5 2B.6.6.6 2B.6.6.6.1 SBC 801 allowable heights and areas specified in Table 3.3. Roof parking is permitted. Ventilation. A mechanical ventilation system shall be provided in accordance with the SBC 501. Motor fuel-dispensing facilities. Construction. Motor fuel-dispensing facilities shall be constructed in accordance with these code requirements and this section. Canopies. Canopies under which fuels are dispensed shall have a clear, unobstructed height of not less than 4.1 m to the lowest projecting element in the vehicle drive-through area. Canopies and their supports over pumps shall be of non-combustible materials, fire-retardant-treated wood complying with Chapter 4, wood of Type IV sizes or of construction providing 1 hour fire resistance. Combustible materials used in or on a canopy shall comply with one of the following: 1. Shielded from the pumps by a noncombustible element of the canopy, or wood of Type IV sizes; 2. Plastics covered by aluminum facing having a minimum thickness of 0.30 mm or corrosion-resistant steel having a minimum base metal thickness of 0.41 mm. The plastic shall have a flame spread index of 25 or less and a smokedeveloped index of 450 or less when tested in the form intended for use in accordance with ASTM E 84 and a self-ignition temperature of 343°C or greater when tested in accordance with ASTM D 1929; or 3. Panels constructed of light-transmitting plastic materials shall be permitted to be installed in canopies erected over motor vehicle fuel-dispensing station fuel dispensers, provided the panels are located at least 3.1 m from any building on the same property and face yards or streets not less than 12.2 m in width on the other sides. The aggregate areas of plastics shall not exceed 93 m2. The maximum area of any individual panel shall not exceed 9.3 m2. Repair garages. General. Repair garages shall be constructed in accordance with these code requirements and this section. This occupancy shall not include motor fueldispensing facilities, as regulated in Section 2B.6.5. Mixed uses. Mixed uses shall be allowed in the same building as a repair garage subject to the provisions of Section 2A.2.3. Ventilation. Repair garages shall be mechanically ventilated in accordance with the SBC 501. The ventilation system shall be controlled at the entrance to the garage. Floor surface. Repair garage floors shall be of concrete or similar noncombustible and nonabsorbent materials. Exception: Slip-resistant, nonabsorbent, interior floor finishes having a critical radiant flux not more than 0.45 W/cm2, as determined by NFPA 253, shall be permitted. Heating equipment. Heating equipment shall be installed in accordance with the SBC 501. Gas detection system. Repair garages used for repair of vehicles fueled by nonodorized gases, such as hydrogen and non-odorized LNG, shall be provided with an approved flammable gas-detection system. System design. The flammable gas-detection system shall be calibrated to the types of fuels or gases used by vehicles to be repaired. The gas detection system shall be designed to activate when the level of flammable gas exceeds 25 percent of the lower explosive limit. Gas detection shall also be provided in lubrication or 2007 2/41 USE AND OCCUPANCY CLASSIFICATION 2B.6.6.6.2 2B.6.6.6.3 chassis repair pits of garages used for repairing non-odorized LNG-fueled vehicles. Operation. Activation of the gas detection system shall result in all of the following: 1. Initiation of distinct audible and visual alarm signals in the repair garage. 2. Deactivation of all heating systems located in the repair garage. 3. Activation of the mechanical ventilation system, where the system is interlocked with gas detection. Failure of the gas detection system. Failure of the gas detection system shall result in the deactivation of the heating system, activation of the mechanical ventilation system when the system is interlocked with the gas detection system and cause a trouble signal to sound in an approved location. SECTION 2B.7 GROUP I-2 2B.7.1 General. Occupancies in Group I-2 shall comply with the provisions of this section and other applicable provisions of these code requirements. 2B.7.2 Corridors. Corridors in occupancies in Group I-2 shall be continuous to the exits and separated from other areas in accordance with Section 2B.7.3 except spaces conforming to Sections 2B.7.2.1 through 2B.7.2.4. Spaces of unlimited area. Waiting areas and similar spaces constructed as required for corridors shall be permitted to be open to a corridor, only where all of the following criteria are met: 1. The spaces are not occupied for patient sleeping units, treatment rooms, hazardous or incidental use areas as defined in Section 2A.2.1.1. 2. The open space is protected by an automatic fire detection system installed in accordance with Section 7.7. 3. The corridors, onto which the spaces open, in the same smoke compartment, are protected by an automatic fire detection system installed in accordance with Section 7.7, or the smoke compartment in which the spaces are located is equipped throughout with quick-response sprinklers in accordance with Section 7.3.3.2. 4. The space is arranged so as not to obstruct access to the required exits. Nurses’ stations. Spaces for doctors’ and nurses’ charting, communications and related clerical areas shall be permitted to be open to the corridor, when such spaces are constructed as required for corridors. Mental health treatment areas. Areas wherein mental health patients who are not capable of self-preservation are housed, or group meeting or multipurpose therapeutic spaces other than incidental use areas as defined in Section 2A.2.1.1, under continuous supervision by facility staff, shall be permitted to be open to the corridor, where the following criteria are met: 1. Each area does not exceed 140 m2. 2. The area is located to permit supervision by the facility staff. 3. The area is arranged so as not to obstruct any access to the required exits. 4. The area is equipped with an automatic fire detection system installed in accordance with Section 7.7.2. 5. Not more than one such space is permitted in any one smoke compartment. 6. The walls and ceilings of the space are constructed as required for corridors. Gift shops. Gift shops less than 46.5 m2 in area shall be permitted to be open to the corridor provided the gift shop and storage areas are fully sprinklered and 2B.7.2.1 2B.7.2.2 2B.7.2.3 2B.7.2.4 SBC 801 2007 2/42 USE AND OCCUPANCY CLASSIFICATION storage areas are protected in accordance with Section 2A.2.1.1. 2B.7.3 2B.7.3.1 2B.7.3.2 2B.7.4 2B.7.4.1 2B.7.4.2 Corridor walls. Corridor walls shall be constructed as smoke partitions. Corridor doors. Corridor doors, other than those in a wall required to be rated by Section 2A.2.1.1 or for the enclosure of a vertical opening or an exit, shall not have a required fire protection rating and shall not be required to be equipped with self-closing or automatic-closing devices, but shall provide an effective barrier to limit the transfer of smoke and shall be equipped with positive latching. Roller latches are not permitted. Other doors shall conform to Section 4B.15.3. Locking devices. Locking devices that restrict access to the patient room from the corridor, and that are operable only by staff from the corridor side, shall not restrict the means of egress from the patient room except for patient rooms in mental health facilities. Smoke barriers. Smoke barriers shall be provided to subdivide every story used by patients for sleeping or treatment and to divide other stories with an occupant load of 50 or more persons, into at least two smoke compartments. Such stories shall be divided into smoke compartments with an area of not more than 2,092 m2 and the travel distance from any point in a smoke compartment to a smoke barrier door shall not exceed 61 m. The smoke barrier shall be in accordance with Section 4B.9. Refuge area. At least 2.8 m2 per patient shall be provided within the aggregate area of corridors, patient rooms, treatment rooms, lounge or dining areas and other low-hazard areas on each side of each smoke barrier. On floors not housing patients confined to a bed or litter, at least 0.56 m2 per occupant shall be provided on each side of each smoke barrier for the total number of occupants in adjoining smoke compartments. Independent egress. A means of egress shall be provided from each smoke compartment created by smoke barriers without having to return through the smoke compartment from which means of egress originated. 2B.7.5 Automatic sprinkler system. Smoke compartments containing patient sleeping units shall be equipped throughout with an automatic fire sprinkler system in accordance with Section 7.3.3.1.1. The smoke compartments shall be equipped with approved quick-response or residential sprinklers in accordance with Section 7.3.3.2. 2B.7.6 Automatic fire detection. Corridors in nursing homes (both intermediate-care and skilled nursing facilities), detoxification facilities and spaces permitted to be open to corridors by Section 2B.7.2 shall be protected by an automatic fire detection system installed in accordance with Section 7.7. Exceptions: 1. Corridor smoke detection is not required where patient sleeping units are provided with smoke detectors that comply with UL 268. Such detectors shall provide a visual display on the corridor side of each patient sleeping unit and an audible and visual alarm at the nursing station attending each unit. 2. Corridor smoke detection is not required where patient sleeping unit doors are equipped with automatic door-closing devices with integral smoke detectors on the unit sides installed in accordance with their listing, provided that the integral detectors perform the required alerting function. 2B.7.7 Secured yards. Grounds are permitted to be fenced and gates therein are permitted SBC 801 2007 2/43 USE AND OCCUPANCY CLASSIFICATION to be equipped with locks, provided that safe dispersal areas having 2.8 m2 for bed and litter patients and 0.56 m2 for ambulatory patients and other occupants are located between the building and the fence. Such provided safe dispersal areas shall not be located less than 15.3 m from the building they serve. SECTION 2B.8 GROUP I-3 2B.8.1 General. Occupancies in Group I-3 shall comply with the provisions of this section and other applicable provisions of these code requirements (see Section 2A.8.4). 2B.8.2 Mixed occupancies. Portions of buildings with an occupancy in Group I-3 that are classified as a different occupancy shall meet the applicable requirements of these code requirements for such occupancies. Where security operations necessitate the locking of required means of egress, provisions shall be made for the release of occupants at all times. Means of egress from detention and correctional occupancies that traverse other use areas shall, as a minimum, conform to requirements for detention and correctional occupancies. Exception: It is permissible to exit through a horizontal exit into other contiguous occupancies that do not conform to detention and correctional occupancy egress provisions but that do comply with requirements set forth in the appropriate occupancy, as long as the occupancy is not a high-hazard use. 2B.8.3 Means of egress. Except as modified or as provided for in this section, the provisions of Chapter 8 shall apply. Door width. Doors to resident sleeping units shall have a clear width of not less than 711 mm. Sliding doors. Where doors in a means of egress are of the horizontal-sliding type, the force to slide the door to its fully open position shall not exceed 220 N with a perpendicular force against the door of 220 N. Spiral stairs. Spiral stairs that conform to the requirements of Section 8.3.3.3.9 are permitted for access to and between staff locations. Exit discharge. Exits are permitted to discharge into a fenced or walled courtyard. Enclosed yards or courts shall be of a size to accommodate all occupants, a minimum of 15.3 m from the building with a net area of 1.4 m2 per person. Sallyports. A sallyport shall be permitted in a means of egress where there are provisions for continuous and unobstructed passage through the sallyport during an emergency egress condition. Vertical exit enclosures. One of the required vertical exit enclosures in each building shall be permitted to have glazing installed in doors and interior walls at each landing level providing access to the enclosure, provided that the following conditions are met: 1. The vertical exit enclosure shall not serve more than four floor levels. 2. Vertical exit enclosure doors shall not be less than 3/4-hour fire doors complying with Section 4B.14.2. 3. The total area of glazing at each floor level shall not exceed 3.23 m2 and individual panels of glazing shall not exceed 0.84 m2. 4. The glazing shall be protected on both sides by an automatic fire sprinkler system. The sprinkler system shall be designed to wet completely the entire surface of any glazing affected by fire when actuated. 2B.8.3.1 2B.8.3.2 2B.8.3.3 2B.8.3.4 2B.8.3.5 2B.8.3.6 SBC 801 2007 2/44 USE AND OCCUPANCY CLASSIFICATION 5. The glazing shall be in a gasketed frame and installed in such a manner that the framing system will deflect without breaking (loading) the glass before the sprinkler system operates. 6. Obstructions, such as curtain rods, drapery traverse rods, curtains, drapes or similar materials shall not be installed between the automatic sprinklers and the glazing. 2B.8.4 2B.8.4.1 2B.8.4.2 2B.8.4.3 2B.8.4.4 2B.8.5 SBC 801 Locks. Egress doors are permitted to be locked in accordance with the applicable use condition. Doors from an area of refuge to the exterior are permitted to be locked with a key in lieu of locking methods described in Section 2B.8.4.1. The keys to unlock the exterior doors shall be available at all times and the locks shall be operable from both sides of the door. Remote release. Remote release of locks on doors in a means of egress shall be provided with reliable means of operation, remote from the resident living areas, to release locks on all required doors. In Occupancy Conditions 3 or 4, the arrangement, accessibility and security of the release mechanism(s) required for egress shall be such that with the minimum available staff at any time, the lock mechanisms are capable of being released within 2 minutes. Exception: Provisions for remote locking and unlocking of occupied rooms in Occupancy Condition 4 are not required provided that not more than 10 locks are necessary to be unlocked in order to move occupants from one smoke compartment to a refuge area within 3 minutes. The opening of necessary locks shall be accomplished with not more than two separate keys. Power-operated doors and locks. Power-operated sliding doors or poweroperated locks for swinging doors shall be operable by a manual release mechanism at the door, and either emergency power or a remote mechanical operating release shall be provided. Exception: Emergency power is not required in facilities with 10 locks or less complying with the exception to Section 2B.8.4.1. Redundant operation. Remote release, mechanically operated sliding doors or remote release, mechanically operated locks shall be provided with a mechanically operated release mechanism at each door, or shall be provided with a redundant remote release control. Relock capability. Doors remotely unlocked under emergency conditions shall not automatically relock when closed unless specific action is taken at the remote location to enable doors to relock. Vertical openings. Vertical openings shall be enclosed in accordance with Section 4B.7. Exception: A floor opening between floor levels of residential housing areas is permitted without enclosure protection between the levels, provided that both of the following conditions are met: 1. The entire normally occupied areas so interconnected are open and unobstructed so as to enable observation of the areas by supervisory personnel. 2. Means of egress capacity is sufficient to provide simultaneous egress for all occupants from all interconnected levels and areas. The height difference between the highest and lowest finished floor levels shall not exceed 70 m. Each story, considered separately, has at least one-half of its individual required means of egress capacity provided by exits leading directly out of that story without traversing another story within the interconnected area. 2007 2/45 USE AND OCCUPANCY CLASSIFICATION 2B.8.6 2B.8.6.1 2B.8.6.2 2B.8.6.3 2B.8.7 2B.8.7.1 2B.8.7.2 2B.8.7.3 2B.8.7.4 2B.8.8 SBC 801 Smoke barrier. Occupancies in Group I-3 shall have smoke barriers complying with Section 4B.9 to divide every story occupied by residents for sleeping, or any other story having an occupant load of 50 or more persons, into at least two smoke compartments. Exception: Spaces having direct exit to one of the following, provided that the locking arrangement of the doors involved complies with the requirements for doors at the compartment barrier for the use condition involved: 1. A public way. 2. A building separated from the resident housing area by a 2 hours fireresistance-rated assembly or 15.3 m of open space. 3. A secured yard or court having a holding space 15.3 m from the housing area that provides 0.56 m2 or more of refuge area per occupant, including residents, staff and visitors. Smoke compartments. The maximum number of residents in any smoke compartment shall be 200. The travel distance to a door in a smoke barrier from any room door required as exit access shall not exceed 46 m. The travel distance to a door in a smoke barrier from any point in a room shall not exceed 61 m. Refuge area. At least 0.56 m2 per occupant shall be provided on each side of each smoke barrier for the total number of occupants in adjoining smoke compartments. This space shall be readily available wherever the occupants are moved across the smoke barrier in a fire emergency. Independent egress. A means of egress shall be provided from each smoke compartment created by smoke barriers without having to return through the smoke compartment from which means of egress originates. Subdivision of resident housing areas. Sleeping areas and any contiguous day room, group activity space or other common spaces where residents are housed shall be separated from other spaces in accordance with Sections 2B.8.7.1 through 2B.8.7.4. Occupancy Conditions 3 and 4. Each sleeping area in Occupancy Conditions 3 and 4 shall be separated from the adjacent common spaces by a smoke-tight partition where the travel distance from the sleeping area through the common space to the exit access corridor exceeds 15.3 m. Occupancy Condition 5. Each sleeping area in Occupancy Condition 5 shall be separated from adjacent sleeping areas, corridors and common spaces by a smoketight partition. Additionally, common spaces shall be separated from the exit access corridor by a smoke-tight partition. Openings in room face. The aggregate area of openings in a solid sleeping room face in Occupancy Conditions 2, 3, 4 and 5 shall not exceed 77,419 mm2. The aggregate area shall include all openings including door undercuts, food passes and grilles. Openings shall be not more than 914 mm above the floor. In Occupancy Condition 5, the openings shall be closeable from the room side. Smoke-tight doors. Doors in openings in partitions required to be smoke tight by Section 2B8.7 shall be substantial doors, of construction that will resist the passage of smoke. Latches and door closures are not required on cell doors. Windowless buildings. For the purposes of this section, a windowless building or portion of a building is one with non-openable windows, windows not readily breakable or without windows. Windowless buildings shall be provided with an engineered smoke control system to provide ventilation (mechanical or natural) in accordance with Section 7.9 for each windowless smoke compartment. 2007 2/46 USE AND OCCUPANCY CLASSIFICATION SECTION 2B.9 MOTION PICTURE PROJECTION ROOMS 2B.9.1 2B.9.1.1 General. The provisions of this section shall apply to rooms in which ribbon-type cellulose acetate or other safety film is utilized in conjunction with electric arc, xenon or other light-source projection equipment that develops hazardous gases, dust or radiation. Where cellulose nitrate film is utilized or stored, such rooms shall comply with NFPA 40. Projection room required. Every motion picture machine projecting film as mentioned within the scope of this section shall be enclosed in a projection room. Appurtenant electrical equipment, such as rheostats, transformers and generators, shall be within the projection room or in an adjacent room of equivalent construction. 2B.9.2 Construction of projection rooms. Every projection room shall be of permanent construction consistent with the construction requirements for the type of building in which the projection room is located. Openings are not required to be protected. The room shall have a floor area of not less than 7.44 m2 for a single machine and at least 3.7 m2 for each additional machine. Each motion picture projector, floodlight, spotlight or similar piece of equipment shall have a clear working space of not less than 762 mm by 762 mm on each side and at the rear thereof, but only one such space shall be required between two adjacent projectors. The projection room and the rooms appurtenant thereto shall have a ceiling height of not less than 2.3 m. The aggregate of openings for projection equipment shall not exceed 25 percent of the area of the wall between the projection room and the auditorium. Openings shall be provided with glass or other approved material, so as to close completely the opening. 2B.9.3 Projection room and equipment ventilation. Ventilation shall be provided in accordance with the SBC 501. Projection room. Supply air. Each projection room shall be provided with adequate air supply inlets so arranged as to provide well-distributed air throughout the room. Air inlet ducts shall provide an amount of air equivalent to the amount of air being exhausted by projection equipment. Air is permitted to be taken from the outside; from adjacent spaces within the building, provided the volume and infiltration rate is sufficient; or from the building air-conditioning system, provided it is so arranged as to provide sufficient air when other systems are not in operation. Exhaust air. Projection rooms are permitted to be exhausted through the lamp exhaust system. The lamp exhaust system shall be positively interconnected with the lamp so that the lamp will not operate unless there is the required airflow. Exhaust air ducts shall terminate at the exterior of the building in such a location that the exhaust air cannot be readily re-circulated into any air supply system. The projection room ventilation system is permitted to also serve appurtenant rooms, such as the generator and rewind rooms. Each projection machine shall be provided with an exhaust duct that will draw air from each lamp and exhaust it directly to the outside of the building. The lamp exhaust is permitted to serve to exhaust air from the projection room to provide room air circulation. Such ducts shall be of rigid materials except for a flexible connector approved for the purpose. The projection lamp or projection room exhaust system, or both, is permitted to be combined but shall not be interconnected with any other exhaust or return system, or both, within the 2B.9.3.1 2B.9.3.1.1 2B.9.3.1.2 SBC 801 2007 2/47 USE AND OCCUPANCY CLASSIFICATION building. 2B.9.4 Lighting control. Provisions shall be made for control of the auditorium lighting and the means of egress lighting systems of theaters from inside the projection room and from at least one other convenient point in the building. 2B.9.5 Miscellaneous equipment. Each projection room shall be provided with rewind and film storage facilities. SECTION 2B.10 STAGES AND PLATFORMS 2B.10.1 Applicability. The provisions of this section shall apply to all parts of buildings and structures that contain stages or platforms and similar appurtenances as herein defined. 2B.10.2 Definitions. The following words and terms shall, for the purposes of this section and as used elsewhere in these code requirements, have the meanings shown herein. FLY GALLERY. A raised floor area above a stage from which the movement of scenery and operation of other stage effects are controlled. GRIDIRON. The structural framing over a stage supporting equipment for hanging or flying scenery and other stage effects. PINRAIL. A rail on or above a stage through which belaying pins are inserted and to which lines are fastened. PLATFORM. A raised area within a building used for religious teaching/lecturing, the presentation of music, plays or other entertainment; the head table for special guests; the raised area for lecturers and speakers; boxing and wrestling rings; theater-in-the-round stages; and similar purposes wherein there are no overhead hanging curtains, drops, scenery or stage effects other than lighting and sound. A temporary platform is one installed for not more than 30 days. PROSCENIUM WALL. The wall that separates the stage from the auditorium or assembly seating area. STAGE. A space within a building utilized for entertainment or presentations, which includes overhead hanging curtains, drops, scenery or stage effects other than lighting and sound. Stage area shall be measured to include the entire performance area and adjacent backstage and support areas not separated from the performance area by fire-resistance-rated construction. Stage height shall be measured from the lowest point on the stage floor to the highest point of the roof or floor deck above the stage. 2B.10.3 2B.10.3.1 SBC 801 Stages. Stage construction shall comply with Sections 2B.10.3.1 through 2B.10.3.7. Stage construction. Stages shall be constructed of materials as required for floors for the type of construction of the building in which such stages are located. 2007 2/48 USE AND OCCUPANCY CLASSIFICATION 2B.10.3.1.1 2B.10.3.2 2B.10.3.3 2B.10.3.4 2B.10.3.5 2B.10.3.5.1 2B.10.3.5.2 2B.10.3.5.3 SBC 801 Exceptions: 1. Stages of Type IIB or IV construction with a nominal 51 mm wood deck, provided that the stage is separated from other areas in accordance with Section 2B.10.3.5. 2. In buildings of Type IIA, IIIA and VA construction, a fire-resistance-rated floor is not required, provided the space below the stage is equipped with an automatic fire-extinguishing system in accordance with Section 7.3 or 7.4. 3. In all types of construction, the finished floor shall be constructed of wood or approved noncombustible materials. Openings through stage floors shall be equipped with tight-fitting, solid wood trap doors with approved safety locks. Stage height and area. Stage areas shall be measured to include the entire performance area and adjacent backstage and support areas not separated from the performance area by fire-resistance-rated construction. Stage height shall be measured from the lowest point on the stage floor to the highest point of the roof or floor deck above the stage. Galleries, gridirons, catwalks and pinrails. Beams designed only for the attachment of portable or fixed theater equipment, gridirons, galleries and catwalks shall be constructed of approved materials consistent with the requirements for the type of construction of the building; and a fire-resistance rating shall not be required. These areas shall not be considered to be floors, stories, mezzanines or levels in applying these code requirements. Exception: Floors of fly galleries and catwalks shall be constructed of any approved material. Exterior stage doors. Where protection of openings is required, exterior exit doors shall be protected with fire doors that comply with Section 4B.15. Exterior openings that are located on the stage for means of egress or loading and unloading purposes, and that are likely to be open during occupancy of the theater, shall be constructed with vestibules to prevent air drafts into the auditorium. Proscenium wall. Where the stage height is greater than 15.3 m, all portions of the stage shall be completely separated from the seating area by a proscenium wall with not less than a 2 hours fire-resistance rating extending continuously from the foundation to the roof. Proscenium curtain. The proscenium opening of every stage with a height greater than 15.3 m shall be provided with a curtain of approved material or an approved water curtain complying with Section 7.3.3.1.1. The curtain shall be designed and installed to intercept hot gases, flames and smoke, and to prevent a glow from a severe fire on the stage from showing on the auditorium side for a period of 20 minutes. The closing of the curtain from the full open position shall be effected in less than 30 seconds, but the last 2.4 m of travel shall require not less than 5 seconds. Activation. The curtain shall be activated by rate-of-rise heat detection installed in accordance with Section 7.7.10 operating at a rate of temperature rise of 8 to 11°C per minute, and by an auxiliary manual control. Fire test. A sample curtain with a minimum of two vertical seams shall be subjected to the standard fire test specified in ASTM E 119 for a period of 30 minutes. The curtain shall overlap the furnace edges by an amount that is appropriate to seal the top and sides. The curtain shall have a bottom pocket containing a minimum of 58 N/m of batten. The exposed surface of the curtain shall not glow, and flame or smoke shall not penetrate the curtain during the test period. Unexposed surface temperature and hose stream test requirements are not applicable to the proscenium fire safety curtain test. Smoke test. Curtain fabrics shall have a smoke-developed rating of 25 or less 2007 2/49 USE AND OCCUPANCY CLASSIFICATION when tested in accordance with ASTM E 84. 2B.10.3.5.4 Tests. The completed proscenium curtain shall be subjected to operating tests prior to the issuance of a certificate of occupancy. Scenery. Combustible materials used in sets and scenery shall be rendered flame resistant in accordance with Section 6.5. Foam plastics and materials containing foam plastics shall comply with Section 11.3 of SBC 201 and these code requirements. 2B.10.3.7 Stage ventilation. Emergency ventilation shall be provided for stages larger than 93 m2 in floor area, or with a stage height greater than 15.3 m. Such ventilation shall comply with Section 2B.10.3.7.1 or 2B.10.3.7.2. 2B.10.3.7.1 Roof vents. Two or more vents constructed to open automatically by approved heat-activated devices and with an aggregate clear opening area of not less than 5 percent of the area of the stage shall be located near the center and above the highest part of the stage area. Supplemental means shall be provided for manual operation of the ventilator. Curbs shall be provided as required for skylights in Section 11.10.2 of SBC 201. Vents shall be labeled. 2B.10.3.7.2 Smoke control. Smoke control in accordance with Section 7.9 shall be provided to maintain the smoke layer interface not less than 1.8 m above the highest level of the assembly seating or above the top of the proscenium opening where a proscenium wall is provided in compliance with Section 2B.10.3.4. 2B.10.3.6 2B.10.4 2B.10.4.1 2B.10.5 2B.10.5.1 2B.10.5.2 SBC 801 Platform construction. Permanent platforms shall be constructed of materials as required for the type of construction of the building in which the permanent platform is located. Permanent platforms are permitted to be constructed of fireretardant-treated wood for Type I, II, and IV construction where the platforms are not more than 762 mm above the main floor, and not more than one-third of the room floor area and not more than 279 m2 in area. Where the space beneath the permanent platform is used for storage or any other purpose other than equipment, wiring or plumbing, the floor construction shall not be less than 1hour fireresistant construction. Where the space beneath the permanent platform is used only for equipment, wiring or plumbing, the underside of the permanent platform need not be protected. Temporary platforms. Platforms installed for a period of not more than 30 days are permitted to be constructed of any materials permitted by the code. The space between the floor and the platform above shall only be used for plumbing and electrical wiring to platform equipment. Dressing and appurtenant rooms. Dressing and appurtenant rooms shall comply with Sections 2B.10.5.1 through 2B.10.5.4. Separation from stage. Where the stage height is greater than 15.3 m, the stage shall be separated from dressing rooms, scene docks, property rooms, workshops, storerooms and compartments appurtenant to the stage and other parts of the building by a fire barrier wall and horizontal assemblies or both with not less than a 2 hours fire-resistance rating with approved opening protectives. For stage heights of 15.3 m or less, the required stage separation shall be a fire barrier wall and horizontal assemblies, or both, with not less a 1 hour fire-resistance rating with approved opening protectives. Separation from each other. Separate dressing rooms for each gender, scene docks, property rooms, workshops, storerooms and compartments appurtenant to the stage shall be separated from each other by fire barrier wall and horizontal assemblies, or both, with not less than a 1 hour fire-resistance rating with approved opening protectives. 2007 2/50 USE AND OCCUPANCY CLASSIFICATION 2B.10.5.3 2B.10.5.4 Opening protectives. Openings other than to trunk rooms and the necessary doorways at stage level shall not connect such rooms with the stage, and such openings shall be protected with fire door assemblies that comply with Section 4B.15. Stage exits. At least one approved means of egress shall be provided from each side of the stage; and from each side of the space under the stage. At least one means of escape shall be provided from each fly gallery and from the gridiron. A steel ladder, alternating tread stairway or spiral stairway is permitted to be provided from the gridiron to a scuttle in the stage roof. 2B.10.6 Automatic sprinkler system. Stages shall be equipped with an automatic fireextinguishing system in accordance with Chapter 7. The system shall be installed under the roof and gridiron, in the tie and fly galleries and in places behind the proscenium wall of the stage and in dressing rooms, lounges, workshops and storerooms accessory to such stages. Exceptions: 1. Sprinklers are not required under stage areas less than 1.2 m in clear height utilized exclusively for storage of tables and chairs, provided the concealed space is separated from the adjacent spaces by not less than 15.9 mm Type X gypsum board. 2. Sprinklers are not required for stages 93 m2 or less in area and 15.3 m or less in height where curtains, scenery or other combustible hangings are not retractable vertically. Combustible hangings shall be limited to a single main curtain, borders, legs and a single backdrop. 2B.10.7 Standpipes. Standpipe systems shall be provided in accordance with Section 7.5. SECTION 2B.11 SPECIAL AMUSEMENT BUILDINGS 2B.11.1 General. Special amusement buildings having an occupant load of 50 or more shall comply with the requirements for the appropriate Group A occupancy and this section. Amusement buildings having an occupant load of less than 50 shall comply with the requirements for a Group B occupancy and this section. Exception: Amusement buildings or portions thereof that are without walls or a roof and constructed to prevent the accumulation of smoke. For flammable decorative materials, see these code requirements. 2B.11.2 Special amusement building. A special amusement building is any temporary or permanent building or portion thereof that is occupied for amusement, entertainment or educational purposes and that contains a device or system that conveys passengers or provides a walkway along, around or over a course in any direction so arranged that the means of egress path is not readily apparent due to visual or audio distractions or is intentionally confounded or is not readily available because of the nature of the attraction or mode of conveyance through the building or structure. 2B.11.3 Automatic fire detection. Special amusement buildings shall be equipped with an automatic fire detection system in accordance with Section 7.7. 2B.11.4 Automatic sprinkler system. Special amusement buildings shall be equipped throughout with an automatic sprinkler system in accordance with Section SBC 801 2007 2/51 USE AND OCCUPANCY CLASSIFICATION 7.3.3.1.1. Where the special amusement building is temporary, the sprinkler water supply shall be of an approved temporary means. Exception: Automatic fire sprinklers are not required where the total floor area of a temporary special amusement building is less than 93 m2 and the travel distance from any point to an exit is less than 15.3 m. 2B.11.5 Alarm. Actuation of a single smoke detector, the automatic sprinkler system or other automatic fire detection device shall immediately sound an alarm at the building at a constantly attended location from which emergency action can be initiated including the capability of manual initiation of requirements in Section 7.7.2.11.2. 2B.11.6 Emergency voice/alarm communications system. An emergency voice/alarm communications system shall be provided in accordance with Sections 7.7.2.11 and 7.7.2.12.2, which is also permitted to serve as a public address system and shall be audible throughout the entire special amusement building. 2B.11.7 Exit marking. Exit signs shall be installed at the required exit or exit access doorways of amusement buildings. Approved directional exit markings shall also be provided. Where mirrors, mazes or other designs are utilized that disguise the path of egress travel such that they are not apparent, approved low level exit signs and directional path markings shall be provided and located not more than 203 mm above the walking surface and on or near the path of egress travel. Such markings shall become visible in an emergency. The directional exit marking shall be activated by the automatic fire detection system and the automatic sprinkler system in accordance with Section 7.7.2.11.2. 2B.11.8 Interior finish. The interior finish shall be Class A in accordance with Section 6.3.1. SECTION 2B.12 AIRCRAFT-RELATED OCCUPANCIES 2B.12.1 2B.12.1.1 2B.12.1.2 2.B.12.1.3 SBC 801 Airport traffic control towers. General. The provisions of this section shall apply to airport traffic control towers not exceeding 140 m2 per floor occupied only for the following uses: 1. Airport traffic control cab, 2. Electrical and mechanical equipment rooms, 3. Airport terminal radar and electronics rooms, 4. Office spaces incidental to the tower operation, 5. Lounges for employees, including sanitary facilities. Type of construction. Airport traffic control towers shall be constructed to conform to the height and area limitations of Table 2B.12.1.2. Egress. A minimum of one exit stairway shall be permitted for airport traffic control towers of any height provided that the occupant load per floor does not exceed 15. The stairway shall conform to the requirements of Section 8.9. The stairway shall be separated from elevators by a minimum distance of one-half of the diagonal of the area served measured in a straight line. The exit stairway and elevator hoistway are permitted to be located in the same shaft enclosure, provided they are separated from each other by a 4-hour separation having no openings. Such stairway shall be pressurized to a minimum of 43 Pa and a maximum of 101 Pa in the shaft relative to the building with stairway doors closed. Stairways need 2007 2/52 USE AND OCCUPANCY CLASSIFICATION not extend to the roof as specified in Section 8.9.12. The provisions of Section 2B.3 do not apply. Exception: Smokeproof enclosures as set forth in Section 8.9.1.8 are not required where required stairways are pressurized. TABLE 2B.12.1.2 HEIGHT AND AREA LIMITATIONS FOR AIRPORT TRAFFIC CONTROL TOWERS HEIGHTa MAXIMUM AREA TYPE OF CONSTRUCTION (meters) (square meters) IA Unlimited 139.4 a. 2B.12.1.4 2B.12.1.5 2B.12.1.6 2B.12.2 2B.12.2.1 2B.12.2.2 2B.12.2.3 2B.12.2.4 2B.12.2.5 SBC 801 IB 73 139.4 IIA 30.5 139.4 IIB 26 139.4 IIIA 19.8 139.4 Height to be measured from grade to cab floor. Automatic fire detection systems. Airport traffic control towers shall be provided with an automatic fire detection system installed in accordance with Section 7.7.2. Standby power. A standby power system that conforms to SBC 401 shall be provided in airport traffic control towers more than 19.8 m in height. Power shall be provided to the following equipment: 1. Pressurization equipment, mechanical equipment and lighting. 2. Elevator operating equipment. 3. Fire alarm and smoke detection systems. Accessibility. Airport traffic control towers need not be accessible as specified in the provisions of Chapter 9 of SBC 201. Aircraft hangar. Exterior walls. Exterior walls located less than 9.1 m from property lines, lot lines or a public way shall have a fire-resistance rating not less than 2 hours. Basements. Where hangars have basements, the floor over the basement shall be of Type IA construction and shall be made tight against seepage of water, oil or vapors. There shall be no opening or communication between the basement and the hangar. Access to the basement shall be from outside only. Floor surface. Floors shall be graded and drained to prevent water or fuel from remaining on the floor. Floor drains shall discharge through an oil separator to the sewer or to an outside vented sump. Heating equipment. Heating equipment shall be placed in another room separated by 2 hours fire-resistance-rated construction. Entrance shall be from the outside or by means of a vestibule providing a two-doorway separation. Exceptions: 1. Unit heaters suspended at least 3.1 m above the upper surface of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hangar and at least 2.4 m above the floor in shops, offices and other sections of the hangar communicating with storage or service areas. 2. A single interior door shall be allowed, provided the sources of ignition in the appliances are at least 457 mm above the floor. Finishing. The process of “doping,” involving use of a volatile flammable solvent, or of painting, shall be carried on in a separate detached building equipped with automatic fire-extinguishing equipment in accordance with Section 7.3. 2007 2/53 USE AND OCCUPANCY CLASSIFICATION 2B.12.2.6 Fire suppression. Aircraft hangars shall be provided with fire suppression as required in NFPA 409. Exception: Group II hangars as defined in NFPA 409 storing private aircraft without major maintenance or overhaul are exempt from foam suppression requirements. 2B.12.3 Residential aircraft hangars. Residential aircraft hangars as defined in Section 2B.12.3.1 shall comply with Sections 2B.12.3.2 through 2B.12.3.6. Definition. The following word and term shall, for the purposes of this chapter and as used elsewhere in these code requirements, have the meaning shown herein. 2B.12.3.1 RESIDENTIAL AIRCRAFT HANGAR. An accessory building less than 186 m2 and 6.1 m in height, constructed on a one- or two-family residential property where aircraft are stored. Such use will be considered as a residential accessory use incidental to the dwelling. 2B.12.3.2 2B.12.3.3 2B.12.3.4 2B.12.3.5 2B.12.3.6 2B.12.4 2B.12.4.1 2B.12.4.2 2B.12.4.3 2B.12.4.4 2B.12.4.5 2B.12.4.6 SBC 801 Fire separation. A hangar shall not be attached to a dwelling unless separated by walls having a fire-resistance rating of not less than 1 hour. Such separation shall be continuous from the foundation to the underside of the roof and un-pierced except for doors leading to the dwelling unit. Doors into the dwelling unit must be equipped with self-closing devices and conform to the requirements of Section 4B.15 with at least a 102 mm noncombustible raised sill. Openings from a hanger directly into a room used for sleeping purposes shall not be permitted. Egress. A hangar shall provide two means of egress. One of the doors into the dwelling shall be considered as meeting only one of the two means of egress. Smoke detection. Smoke alarms shall be provided within the hangar in accordance with Section 7.7.2.21. Independent systems. Mechanical and plumbing drain, waste and vent (DWV) systems installed within the hangar shall be independent of the systems installed within the dwelling. Building sewer lines may connect outside the structures. Exception: Smoke detector wiring and feed for electrical sub-panels in the hangar. Height and area limits. Residential aircraft hangars shall not exceed 186 m2 in area and 6.1 m in height. Aircraft paint hangars. Aircraft painting operations where flammable liquids are used in excess of the maximum allowable quantities per control area listed in Table 2A.7.7(1) shall be conducted in an aircraft paint hangar that complies with the provisions of Section 2B.12.4. Occupancy group. Aircraft paint hangars shall be classified as Group H-2. Aircraft paint hangars shall comply with the applicable requirements of these code requirements and the SBC 201 for such occupancy. Construction. The aircraft paint hangar shall be of Type I or II construction. Operations. Only those flammable liquids necessary for painting operations shall be permitted in quantities less than the maximum allowable quantities per control area in Table 2A.7.7(1). Spray equipment cleaning operations shall be conducted in a liquid use, dispensing and mixing room. Storage. Storage of flammable liquids shall be in a liquid storage room. Fire suppression. Aircraft paint hangars shall be provided with fire suppression as required in NFPA 409. Ventilation. Aircraft paint hangars shall be provided with ventilation as required in the SBC 501. 2007 2/54 USE AND OCCUPANCY CLASSIFICATION 2B.12.5 2B.12.5.1 2B.12.5.2 Heliports and helistops. General. Heliports and helistops may be erected on buildings or other locations where they are constructed in accordance with this section. Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in these code requirements, have the meanings shown herein. HELIPORT. An area of land or water or a structural surface that is used, or intended for use, for the landing and taking off of helicopters, and any appurtenant areas that are used, or intended for use, for heliport buildings and other heliport facilities. HELISTOP. The same as a “Heliport,” except that no fueling, de-fueling, maintenance, repairs or storage of helicopters is permitted. 2B.12.5.3 2B.12.5.4 2B.12.5.5 2B.12.5.6 Size. The touchdown or landing area for helicopters of less than 1,588 kg shall be a minimum of 6.1 m in length and width. The touchdown area shall be surrounded on all sides by a clear area having a minimum average width at roof level of 4.6 m but with no width less than 1.5 m. Design. Helicopter landing areas and the supports thereof on the roof of a building shall be noncombustible construction. Landing areas shall be designed to confine any flammable liquid spillage to the landing area itself and provisions shall be made to drain such spillage away from any exit or stairway serving the helicopter landing area or from a structure housing such exit or stairway. For structural design requirements, see SBC 301. Means of egress. The means of egress from heliports and helistops shall comply with the provisions of Chapter 8. Landing areas located on buildings or structures shall have two or more means of egress. For landing platforms or roof areas less than 18.3 m in length, or less than 187 m2 in area, the second means of egress may be a fire escape or ladder leading to the floor below. Rooftop heliports and helistops. Rooftop heliports and helistops shall comply with NFPA 418. SECTION 2B.13 COMBUSTIBLE STORAGE 2B.13.1 General. High-piled stock or rack storage in any occupancy group shall comply with these code requirements. 2B.13.2 Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1 hour fire-resistant construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 45 mm in thickness. Exceptions: 1. Areas protected by approved automatic sprinkler systems. 2. Group R-3 and U occupancies. SECTION 2B.14 HAZARDOUS MATERIALS 2B.14.1 SBC 801 General. The provisions of this section shall apply to buildings and structures 2007 2/55 USE AND OCCUPANCY CLASSIFICATION occupied for the manufacturing, processing, dispensing, use or storage of hazardous materials. 2B.14.1.1 Other provisions. Buildings and structures with an occupancy in Group H shall also comply with the applicable provisions of Section 2B.15 and these code requirements. 2B.14.1.2 Materials. The safe design of hazardous material occupancies is material dependent. Individual material requirements are also found in Sections 2A.7 and 2B.15, and in the SBC 501 and these code requirements. 2B.14.1.2.1 Materials. The safe design of hazardous material occupancies is material dependent. Individual material requirements are also found in Sections 2A.7 and 2B.15, and in the SBC 501 and these code requirements. 2B.14.1.2.2 Aerosols. Level 2 and 3 aerosol products shall be stored and displayed in accordance with the code requirements. See Section 2A.11.2 and these code requirements for occupancy group requirements. 2B.14.1.3 Information required. Separate floor plans shall be submitted for buildings and structures with an occupancy in Group H, identifying the locations of anticipated contents and processes so as to reflect the nature of each occupied portion of every building and structure. A report identifying hazardous materials including, but not limited to, materials representing hazards that are classified in Group H to be stored or used, shall be submitted and the methods of protection from such hazards shall be indicated on the construction documents. The opinion and report shall be prepared by a qualified person, firm or corporation approved by the concerning building official and shall be provided without charge to the enforcing agency. 2B.14.2 2B.14.2.1 2B.14.2.2 Control areas. Control areas shall be those spaces within a building where quantities of hazardous materials not exceeding the maximum quantities allowed by these code requirements are stored, dispensed, used or handled. Construction requirements. Control areas shall be separated from each other by not less than a 1 hour fire barrier constructed in accordance with Chapter 4. Number. The maximum number of control areas within a building shall be in accordance with Table 2B.14.2.2. TABLE 2B.14.2.2 DESIGN AND NUMBER OF CONTROL AREAS FLOOR LEVEL Higher than 9 7-9 6 5 Above grade 4 3 2 1 1 Below grade 2 Lower than 2 PERCENTAGE OF THE MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREAa 5 5 12.5 12.5 12.5 50 75 100 75 50 Not Allowed NUMBER OF CONTROL AREAS PER FLOORb 1 2 2 2 2 2 3 4 3 2 Not Allowed FIRERESISTANCE RATING FOR FIRE BARRIERS IN HOURSc 2 2 2 2 2 1 1 1 1 1 Not Allowed a. Percentages shall be of the maximum allowable quantity per control area shown in Tables 2A.7.7(1) and 2A.7.7(2), with all increases allowed in the notes to those tables. b. There shall be a maximum of two control areas per floor in Group M occupancies and in buildings or portions of buildings having Group S occupancies with storage conditions and quantities in accordance with Section 2B.14.2.4. c. Fire barriers shall include walls and floors as necessary to provide separation from other portions of the building. SBC 801 2007 2/56 USE AND OCCUPANCY CLASSIFICATION 2B.14.2.3 2B.14.2.4 2B.14.3 Separation. The required fire-resistance rating for fire barrier assemblies shall be in accordance with Table 2B.14.2.2. The floor construction of the control area, and the construction supporting the floor of the control area, shall have a minimum 2 hours fire-resistance rating. Hazardous material in Group M display and storage areas and in Group S storage areas. The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials permitted within a single control area of a Group M or S occupancy or an outdoor control area is permitted to exceed the maximum allowable quantities per control area specified in Tables 2A.7.7(1) and 2A.7.7(2) without classifying the building or use as a Group H occupancy, provided that the materials are displayed and stored in accordance with these code requirements and quantities do not exceed the maximum allowable specified in Table 2B.14.2.4. Ventilation. Rooms, areas or spaces of Group H in which explosive, corrosive, combustible, flammable or highly toxic dusts, mists, fumes, vapors or gases are or may be emitted due to the processing, use, handling or storage of materials shall be mechanically ventilated as required by these code requirements and the SBC 501. Ducts conveying explosives or flammable vapors, fumes or dusts shall extend directly to the exterior of the building without entering other spaces. Exhaust ducts shall not extend into or through ducts and plenums. TABLE 2B.14.2.4 MAXIMUM ALLOWABLE QUANTITY PER INDOOR AND OUTDOOR CONTROL AREA IN GROUP M AND S OCCUPANCIES NONFLAMMABLE SOLIDS AND NONFLAMMABLE AND NONCOMBUSTIBLE LIQUIDS d,e,f MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA Solids Liquids kilograms liters CONDITION Materiala Class A. Health-hazard materials—nonflammable and noncombustible solids and liquids 1. Corrosivesb, c Not Applicable 4,427 2. Highly toxics Not Applicable 9.1b, c b, c 3. Toxics Not Applicable 454 B. Physical-hazard materials—nonflammable and noncombustible solids and liquids 4 Not Allowed 3 522g b, c 1. Oxidizers 2 1,022h 1 8,172i, j 4 Not Allowed 3 250 b, c 2. Unstable (reactives) 2 522 1 Not Limited 3b, c 250 3. Water (reactives) 2b, c 522 1 Not Limited 3,690 7.6b, c 379 Not Allowed 435 852 6,813i, j Not Allowed 208 435 Not Limited 208 435 Not Limited a. Hazard categories are as specified in these code requirements. b. Maximum allowable quantities shall be increased 100 percent in buildings that are sprinklered in accordance with Section 7.3.3.1.1. When Note c also applies, the increase for both notes shall be applied accumulatively. c. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, in accordance with these code requirements. When Note b also applies, the increase for both notes shall be applied accumulatively. d. See Table 2B.14.2.2 for design and number of control areas. e. Allowable quantities for other hazardous material categories shall be in accordance with Section 2A.7. f. Maximum quantities shall be increased 100 percent in outdoor control areas. g. Maximum amounts are permitted to be increased to 1,022 kilograms when individual packages are in the original sealed containers from the manufacturer or packager and do not exceed 4.5 kilograms each. h. Maximum amounts are permitted to be increased to 2,043 kilograms when individual packages are in the original sealed containers from the manufacturer or packager and do not exceed 4.5 kilograms each. i. Quantities are unlimited where protected by an automatic sprinkler system. j. Quantities are unlimited in an outdoor control area. SBC 801 2007 2/57 USE AND OCCUPANCY CLASSIFICATION Exception: Ducts conveying vapor or fumes having flammable constituents less than 25 percent of their lower flammable limit (LFL) are permitted to pass through other spaces. Emissions generated at workstations shall be confined to the area in which they are generated as specified in these code requirements and the SBC 501. The location of supply and exhaust openings shall be in accordance with the SBC 501. Exhaust air contaminated by highly toxic material shall be treated in accordance with these code requirements. A manual shutoff control for ventilation equipment required by this section shall be provided outside the room adjacent to the principal access door to the room. The switch shall be of the break-glass type and shall be labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF. 2B.14.4 Hazardous material systems. Systems involving hazardous materials shall be suitable for the intended application. Controls shall be designed to prevent materials from entering or leaving process or reaction systems at other than the intended time, rate or path. Automatic controls, where provided, shall be designed to be failing safe. 2B.14.5 Inside storage, dispensing and use. The inside storage, dispensing and use of hazardous materials in excess of the maximum allowable quantities per control area of Tables 2A.7.7(1) and 2A.7.7(2) shall be in accordance with Sections 2B.14.5.1 through 2B.14.5.5 of these code requirements and the SBC 201. Explosion control. Explosion control shall be provided in accordance with these code requirements as required by Table 2B.14.5.1 where quantities of hazardous materials specified in that table exceed the maximum allowable quantities in Table 2A.7.7(1) or where a structure, room or space is occupied for purposes involving explosion hazards as required by Section 2B.15 or these code requirements. Monitor control equipment. Monitor control equipment shall be provided where required by these code requirements. Automatic fire detection systems. Group H occupancies shall be provided with an automatic fire detection system in accordance with Section 7.7.2. Standby or emergency power. Where mechanical ventilation, treatment systems, temperature control, alarm, detection or other electrically operated systems are required, such systems shall be provided with an emergency or standby power system in accordance with the SBC 401. Exceptions: 1. Storage areas for Class I and II oxidizers. 2. Storage areas for Class III, IV and V organic peroxides. 3. Storage, use and handling areas for highly toxic or toxic materials as provided for in these code requirements. 4. Standby power for mechanical ventilation, treatment systems and temperature control systems shall not be required where an approved fail-safe engineered system is installed. 2B.14.5.1 2B.14.5.2 2B.14.5.3 2B.14.5.4 2B.14.5.5 SBC 801 Spill control, drainage and containment. Rooms, buildings or areas occupied for the storage of solid and liquid hazardous materials shall be provided with a means to control spillage and to contain or drain off spillage and fire protection water discharged in the storage area where required in these code requirements. The methods of spill control shall be in accordance with these code requirements. 2007 2/58 USE AND OCCUPANCY CLASSIFICATION TABLE 2B.14.5.1 EXPLOSION CONTROL REQUIREMENTSa MATERIAL HAZARD CATEGORY Combustible dustsc Cryogenic flammables Explosives Flammable gas Flammable liquid Organic peroxides Oxidizer liquids and solids Pyrophoric gas Unstable (reactive) Water-reactive liquids and solids SPECIAL USES Acetylene generator rooms Grain processing Liquefied petroleum gasdistribution facilities Where explosion hazards existf a. b. c. d. e. f. g. CLASS EXPLOSION CONTROL METHODS Explosion (deflagration) venting or explosion (deflagration) Barricade construction prevention systemsb — — Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.5 Division 1.6 Gaseous Liquefied IAd IBe U I 4 — 4 3 Detonable 3 Nondetonable 3 2g Not Required Not Required Required Required Not Required Not Required Required Required Not Required Not Required Not Required Not Required Required Required Required Not Required Required Required Not Required Not Required Not Required Required Required Not Required Not Required Required Required Not Required Not Required Required Required Required Required Not Permitted Not Permitted Not Permitted Required Not Permitted Not Permitted Required Required Required — — Not Required Not Required Required Required — Not Required Required Detonation Deflagration Required Not Required Not Permitted Required See Section 2B.14.1.3. See other chapters of these code requirements. As generated during manufacturing or processing. See definition of “Combustible dust” in Chapter 2. Storage or use. In open use or dispensing. Rooms containing dispensing and use of hazardous materials when an explosive environment can occur because of the characteristics or nature of the hazardous materials or as a result of the dispensing or use process. A method of explosion control shall be provided when Class 2 water-reactive materials can form potentially explosive mixtures. 2B.14.6 2B.14.6.1 SBC 801 Outdoor storage, dispensing and use. The outdoor storage, dispensing and use of hazardous materials shall be in accordance with these code requirements. Weather protection. Where weather protection is provided for sheltering outdoor hazardous material storage or use areas, such storage or use shall be considered outdoor storage or use, provided that all of the following conditions are met: 1. Structure supports and walls shall not obstruct more than one side or more than 25 percent of the perimeter of the storage or use area. 2. The distance from the structure and the structure supports to buildings, lot lines, public ways or means of egress to a public way shall not be less than the distance required for an outside hazardous material storage or use area without weather protection. 3. The overhead structure shall be of approved noncombustible construction with a maximum area of 140 m2. Exception: The increases permitted by Section 3.6 apply. 2007 2/59 USE AND OCCUPANCY CLASSIFICATION 2B.14.7 2B.14.7.1 2B.14.7.2 2B.14.7.3 Emergency alarms. Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as set forth herein. Storage. An approved manual emergency alarm system shall be provided in buildings, rooms or areas used for storage of hazardous materials. Emergency alarm-initiating devices shall be installed outside of each interior exit or exit access door of storage buildings, rooms or areas. Activation of an emergency alarm-initiating device shall sound a local alarm to alert occupants of an emergency situation involving hazardous materials. Dispensing, use and handling. Where hazardous materials having a hazard ranking of 3 or 4 in accordance with NFPA 704 are transported through corridors or exit enclosures, there shall be an emergency telephone system, a local manual alarm station or an approved alarm-initiating device at not more than 45.7 m intervals and at each exit and exit access doorway throughout the transport route. The signal shall be relayed to an approved central, proprietary or remote station service or constantly attended on-site location and shall also initiate a local audible alarm. Supervision. Emergency alarm systems shall be supervised by an approved central, proprietary or remote station service or shall initiate an audible and visual signal at a constantly attended on-site location. SECTION 2B.15 GROUPS H-1, H-2, H-3, H-4 AND H-5 2B.15.1 Scope. The provisions of this section shall apply to the storage and use of hazardous materials in excess of the maximum allowable quantities per control area listed in Section 2A.7.9. Buildings and structures with an occupancy in Group H shall also comply with the applicable provisions of Section 2B.14 and these code requirements. 2B.15.2 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in the code, have the meanings shown herein. CONTINUOUS GAS-DETECTION SYSTEM. A gas detection system where the analytical instrument is maintained in continuous operation and sampling is performed without interruption. Analysis is allowed to be performed on a cyclical basis at intervals not to exceed 30 minutes. EMERGENCY CONTROL STATION. An approved location on the premises where signals from emergency equipment are received and which is staffed by trained personnel. EXHAUSTED ENCLOSURE. An appliance or piece of equipment that consists of a top, a back and two sides providing a means of local exhaust for capturing gases, fumes, vapors and mists. Such enclosures include laboratory hoods, exhaust fume hoods and similar appliances and equipment used to locally retain and exhaust the gases, fumes, vapors and mists that could be released. Rooms or areas provided with general ventilation, in themselves, are not exhausted enclosures. SBC 801 FABRICATION AREA. An area within a semiconductor fabrication facility and related research and development areas in which there are processes using hazardous production materials. Such areas are allowed to include ancillary rooms or areas such as dressing rooms and offices that are directly related to the 2007 2/60 USE AND OCCUPANCY CLASSIFICATION fabrication area processes. FLAMMABLE VAPORS OR FUMES. The concentration of flammable constituents in air that exceed 10 percent of their lower flammable limit (LFL). GAS CABINET. A fully enclosed, noncombustible enclosure used to provide an isolated environment for compressed gas cylinders in storage or use. Doors and access ports for exchanging cylinders and accessing pressure-regulating controls are allowed to be included. GAS ROOM. A separately ventilated, fully enclosed room in which only compressed gases and associated equipment and supplies are stored or used. HAZARDOUS PRODUCTION MATERIAL (HPM). A solid, liquid or gas associated with semiconductor manufacturing that has a degree-of-hazard rating in health, flammability or reactivity of Class 3 or 4 as ranked by NFPA 704 and which is used directly in research, laboratory or production processes that have as their end product materials that are not hazardous. HPM FLAMMABLE LIQUID. An HPM liquid that is defined as either a Class I flammable liquid or a Class II or Class IIIA combustible liquid. HPM ROOM. A room used in conjunction with or serving a Group H-5 occupancy, where HPM is stored or used and which is classified as a Group H-2, H-3 or H-4 occupancy. IMMEDIATELY DANGEROUS TO LIFE AND HEALTH (IDLH). The concentration of airborne contaminants which poses a threat of death, immediate or delayed permanent adverse health effects, or effects that could prevent escape from such an environment. This contaminant concentration level is established by the National Institute of Occupational Safety and Health (NIOSH) based on both toxicity and flammability. It generally is expressed in parts per million by volume (ppm v/v) or milligrams per cubic meter (mg/m3). If adequate data do not exist for precise establishment of IDLH concentrations, an independent certified industrial hygienist, industrial toxicologist, appropriate regulatory agency or other source approved by the code official shall make such determination. LIQUID. A material that has a melting point that is equal to or less than 20°C and a boiling point that is greater than 20°C at 101 kPa. When not otherwise identified, the term “liquid” includes both flammable and combustible liquids. LIQUID STORAGE ROOM. A room classified as a Group H-3 occupancy used for the storage of flammable or combustible liquids in an unopened condition. LIQUID USE, DISPENSING AND MIXING ROOMS. Rooms in which Class I, II and IIIA flammable or combustible liquids are used, dispensed or mixed in open containers. LOWER FLAMMABLE LIMIT (LFL). The minimum concentration of vapor in air at which propagation of flame will occur in the presence of an ignition source. The LFL is sometimes referred to as “LEL” or “lower explosive limit.” SBC 801 2007 2/61 USE AND OCCUPANCY CLASSIFICATION NORMAL TEMPERATURE AND PRESSURE (NTP). A temperature of 21°C and a pressure of 101 kPa. SERVICE CORRIDOR. A fully enclosed passage used for transporting HPM and purposes other than required means of egress. SOLID. A material that has a melting point, decomposes or sublimes at a temperature greater than 20°C. STORAGE, HAZARDOUS MATERIALS. 1. The keeping, retention or leaving of hazardous materials in closed containers, tanks, cylinders or similar vessels, or 2. Vessels supplying operations through closed connections to the vessel. USE (MATERIAL). Placing a material into action, including solids, liquids and gases. WORKSTATION. A defined space or an independent principal piece of equipment using HPM within a fabrication area where a specific function, laboratory procedure or research activity occurs. Approved or listed hazardous materials storage cabinets, flammable liquid storage cabinets or gas cabinets serving a workstation are included as part of the workstation. A workstation is allowed to contain ventilation equipment, fire protection devices, detection devices, electrical devices and other processing and scientific equipment. 2B.15.3 2B.15.3.1 SBC 801 Location on property. Group H shall be located on property in accordance with the other provisions of this chapter. In Group H-2 or H-3, not less than 25 percent of the perimeter wall of the occupancy shall be an exterior wall. Exceptions: 1. Liquid use, dispensing and mixing rooms having a floor area of not more than 46.5 m2 need not be located on the outer perimeter of the building where they are in accordance with these code requirements and NFPA 30. 2. Liquid storage rooms having a floor area of not more than 93 m2 need not be located on the outer perimeter where they are in accordance with these code requirements and NFPA 30. 3. Spray paint booths that comply with these code requirements need not be located on the outer perimeter. Group H minimum distance to lot lines. Regardless of any other provisions, buildings containing Group H occupancies shall be set back a minimum distance from lot lines as set forth in Items 1 through 4 below. Distances shall be measured from the walls enclosing the occupancy to lot lines, including those on a public way. Distances to assumed property lines drawn for the purposes of determination of exterior wall and opening protection are not to be used to establish the minimum distance for separation of buildings on sites where explosives are manufactured or used when separation is provided in accordance with the quantity distance tables specified for explosive materials in these code requirements. 1. Group H-1. Not less than 23 m and not less than required by these code requirements. Exceptions: 1. Fireworks manufacturing buildings separated in accordance with NFPA 1124. 2. Buildings containing the following materials when separated in accordance 2007 2/62 USE AND OCCUPANCY CLASSIFICATION with Table 2B.15.3.1: 2.1 Organic peroxides, unclassified detonable. 2.2 Unstable reactive materials Class 4. 2.3 Unstable reactive materials, Class 3 detonable. 2.4 Detonable pyrophoric materials. 2. Group H-2. Not less than 9.1 m where the area of the occupancy exceeds 93 m2 and it is not required to be located in a detached building. 3. Groups H-2 and H-3. Not less than 15.3 m where a detached building is required (see Table 2B.15.3.2). 4. Groups H-2 and H-3. Occupancies containing materials with explosive characteristics shall be separated as required by these code requirements. Where separations are not specified, the distances required shall not be less than the distances required by Table 2B.15.3.1. TABLE 2B.15.3.1 MINIMUM SEPARATION DISTANCES FOR BUILDINGS CONTAINING EXPLOSIVE MATERIALS QUANTITY OF EXPLOSIVE MATERIALa Kilograms Kilograms over not over 0.9 2.3 2.3 4.5 4.5 9.1 9.1 13.6 13.6 18.2 18.2 22.7 22.7 34.1 34.1 45.4 45.4 56.8 56.8 68.1 68.1 90.8 90.8 113.5 113.5 136.2 136.2 181.6 181.6 227.0 227.0 272.4 272.4 317.8 317.8 363.2 363.2 408.6 408.6 454.0 454.0 544.8 544.8 635.6 635.6 726.4 726.4 817.2 817.2 454 908 1,135 1,135 1,362 1,362 1,816 1,816 2,270 2,270 2,724 2,724 3,178 3,178 3,632 3,632 4,086 4,086 4,540 4,540 5,448 SBC 801 MINIMUM DISTANCE (meters) Lot lines and inhabited buildingsc b Barricaded d 21 27 34 38 43 46 52 58 61 66 72 78 82 90 98 104 108 114 119 122 130 137 143 149 154 166 177 194 209 223 235 244 255 264 267 (Continued) 2007 Unbarricaded 43 55 67 76 85 91 104 116 122 131 143 155 165 180 195 207 216 229 238 244 259 274 287 299 308 332 354 387 418 445 469 488 509 527 533 Separation of magazinesd,e, f 3.7 4.9 6.1 6.7 7.3 8.5 9.1 9.8 11 11.6 12.8 14 14.6 16.5 17.7 19 19.5 20 21 22 24 25 26 27 27 30 32 35 37 40 41 44 46 48 50 2/63 USE AND OCCUPANCY CLASSIFICATION TABLE 2B.15.3.1—Continued MINIMUM SEPARATION DISTANCES FOR BUILDINGS CONTAINING EXPLOSIVE MATERIALS QUANTITY OF EXPLOSIVE MATERIALa Kilograms Kilograms not over over 5,448 6,356 6,356 7,264 7,264 8,172 8,172 9,080 9,080 11,350 11,350 13,620 13,620 15,890 15,890 18,160 18,160 20,430 20,430 22,700 22,700 24,970 24,970 27,240 27,240 29,510 29,510 31,780 31,780 34,050 34,050 36,320 36,320 38,590 38,590 40,860 40,860 43,130 43,130 45,400 45,400 49,940 49,940 54,480 54,480 59,020 59,020 63,560 63,560 68,100 68,100 72,640 72,640 77,180 77,180 81,720 81,720 86,260 86,260 90,800 90,800 95,340 95,340 104,420 104,420 113,500 113,500 124,850 124,850 136,200 MINIMUM DISTANCE (meters) Lot linesb and inhabited buildingsc Separation of magazinesd, e, f Barricadedd Unbarricaded 270 274 287 297 322 344 367 389 408 427 445 462 477 491 504 517 527 536 546 553 559 565 572 576 579 590 599 607 613 619 626 640 657 675 693 539 549 573 594 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 610 613 619 626 640 657 675 693 53 55 57 60 64 68 73 76 79 82 85 88 91 94 98 101 104 107 110 113 119 125 131 137 143 149 155 162 168 174 180 192 204 219 235 a. The number of kilograms of explosives listed is the number of pounds of trinitrotoluene (TNT) or the equivalent kilograms of other explosive. b. The distance listed is the distance to lot line, including lot lines at public ways. c. For the purpose of this table, an inhabited building is any building on the same property that is regularly occupied by people. Where two or more buildings containing explosives or magazines are located on the same property, each building or magazine shall comply with the minimum distances specified from inhabited buildings and, in addition, they shall be separated from each other by not less than the distance shown for “Separation of magazines,” except that the quantity of explosive materials contained in detonator buildings or magazines shall govern in regard to the spacing of said buildings or magazines from buildings or magazines, as a group, shall be considered as one building or magazine, and the total quantity of explosive materials stored in such group shall be treated as if the explosive were in a single building or magazine located on the site of any building or magazine of the group, and shall comply with the minimum distance specified from other magazines or inhabited buildings. d. Barricades shall effectively screen the building containing explosives from other buildings, public ways or magazines. Where mounds or reverted walls of earth are used for barricades, they shall not be less than 0.9 meter in thickness. A straight line from the top of any side wall of the building containing explosive materials to the eave line of any other building, magazine or a point 3.7 meters. Above the centerline of a public way shall pass through the barricades. e. Magazine is a building or structure, other than an operating building, approved for storage of explosive materials. Portable or mobile magazines not exceeding 11 m2 in area need not comply with the requirements of SBC 201, however, all magazines shall comply with these code requirements. f. The distance listed is permitted be reduced by 50 percent where approved natural or artificial barriers are provided in accordance with the requirements in Note d. SBC 801 2007 2/64 USE AND OCCUPANCY CLASSIFICATION 2B.15.3.2 Group H-1 and H-2 or H-3 detached buildings. Where a detached building is required by Table 2B.15.3.2, there are no requirements for wall and opening protection based on location on property. TABLE 2B.15.3.2 REQUIRED DETACHED STORAGE DETACHED STORAGE IS REQUIRED WHEN THE QUANTITY OF MATERIAL EXCEEDS THAT LISTED HEREIN Solids and Liquids Gases Material Class (tonnes)a,b (cubic meters)a,b Maximum Allowable Division 1.1 Quantity Maximum Allowable Division 1.2 Quantity Maximum Allowable Division 1.3 Quantity Explosives Not Applicable Maximum Allowable Division 1.4 Quantity Division 1.4c 0.907 Maximum Allowable Division 1.5 Quantity Maximum Allowable Division 1.7 Quantity Maximum Allowable Maximum Allowable Oxidizers Class 4 Quantity Quantity Maximum Allowable Maximum Allowable Unstable (reactives) detonable Class 3 or 4 Quantity Quantity Class 3 1,089 Not Applicable Oxidizer, liquids and solids Class 2 1,814 Not Applicable Maximum Allowable Detonable Not Applicable Quantity Maximum Allowable Organic peroxides Class I Not Applicable Quantity Class II 22.7 Not Applicable Class III 45.4 Not Applicable Class 3 0.907 57 Unstable (reactives) nondetonable Class 2 22.7 283 Class 3 0.907 Not Applicable Water reactives Class 2 22.7 Not Applicable Pyrphoric gases Not Applicable Not Applicable 57 a. For materials that are detonable, the distance to other buildings or lot lines shall be as specified in Table 2B.15.3.1 based on trinitrotoluene (TNT) equivalence of the material. For materials classified as explosives, see Chapter 31. For all other materials, the distance shall be as indicated in Section 2B.15.3.1. b. Maximum Allowable Quantity” means the maximum allowable quantity per control area set forth in Table 2A.7.7(1). c. Limited to Division 1.4 materials and articles, including articles packaged for shipment, that are not regulated as an explosive under MOI (Bureau of Alcohol, Tobacco and Firearms (BATF)) regulations or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles, providing the net explosive weight of individual articles does not exceed 0.5 kilograms. 2B.15.4 2B.15.4.1 SBC 801 Special provisions for Group H-1 occupancies. Group H-1 occupancies shall be in buildings used for no other purpose, shall not exceed one story in height and be without basement, crawl spaces or other under-floor spaces. Roofs shall be of lightweight construction with suitable thermal insulation to prevent sensitive material from reaching its decomposition temperature. Group H-1 occupancies containing materials which are in themselves both physical and health hazards in quantities exceeding the maximum allowable quantities per control area in Table 2A.7.7(2) shall comply with requirements for both Group H-1 and H-4 occupancies. Floors in storage rooms. Floors in storage areas for organic peroxides, pyrophoric materials and unstable (reactive) materials shall be of liquid-tight, noncombustible construction. 2007 2/65 USE AND OCCUPANCY CLASSIFICATION 2B.15.5 2B.15.5.1 2B.15.5.2 2B.15.6 Special provisions for Group H-2 and H-3 occupancies. Group H-2 and H-3 occupancies containing quantities of hazardous materials in excess of those set forth in Table 2B.15.3.2 shall be in buildings used for no other purpose, shall not exceed one story in height and shall be without basements, crawl spaces or other under-floor spaces. Group H-2 and H-3 occupancies containing water-reactive materials shall be resistant to water penetration. Piping for conveying liquids shall not be over or through areas containing water reactives, unless isolated by approved liquid-tight construction. Exception: Fire protection piping. Floors in storage rooms. Floors in storage areas for organic peroxides, oxidizers, pyrophoric materials, unstable (reactive) materials and water-reactive solids and liquids shall be of liquid-tight, noncombustible construction. Waterproof room. Rooms or areas used for the storage of water-reactive solids and liquids shall be constructed in a manner that resists the penetration of water through the use of waterproof materials. Piping carrying water for other than approved automatic fire sprinkler systems shall not be within such rooms or areas. Smoke and heat venting. Smoke and heat vents complying with Section 7.10 shall be installed in the following locations: 1. In occupancies classified as Group H-2 or H-3, any of which are over 1,394 m2 in single floor area. Exception: Buildings of noncombustible construction containing only noncombustible materials. 2. In areas of buildings in Group H used for storing Class 2, 3 and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water-reactive materials as required for a Class V hazard classification. Exception: Buildings of noncombustible construction containing only noncombustible materials. Group H-2. Occupancies in Group H-2 shall be constructed in accordance with Sections 2B.15.7.1 through 2B.15.7.4 and this code. 2B.15.7.1 Combustible dusts, grain processing and storage. The provisions of Sections 2B.15.7.1.1 through 2B.15.7.1.5 shall apply to buildings in which materials that produce combustible dusts are stored or handled. Buildings that store or handle combustible dusts shall comply with the applicable provisions of NFPA 61, NFPA 120, NFPA 651, NFPA 654, NFPA 655, NFPA 664 and NFPA 85, and this code. 2B.15.7.1.1 Type of construction and height exceptions. Buildings shall be constructed in compliance with the height and area limitations of Chapter 3 for Group H-2; except that where erected of Type I or II construction, the heights and areas of grain elevators and similar structures shall be unlimited, and where of Type IV construction, the maximum height shall be 20 m and except further that, in isolated areas, the maximum height of Type IV structures shall be increased to 26 m. 2B.15.7.1.2 Grinding rooms. Every room or space occupied for grinding or other operations that produce combustible dusts shall be enclosed with fire barriers and horizontal assemblies or both that have not less than a 2 hours fire-resistance rating where the area is not more than 279 m2, and not less than a 4-hour fire-resistance rating where the area is greater than 279 m2. 2B.15.7.1.3 Conveyors. Conveyors, chutes, piping and similar equipment passing through the enclosures of rooms or spaces shall be constructed dirt tight and vapor tight, and be of approved noncombustible materials complying with SBC 501. 2B.15.7 SBC 801 2007 2/66 USE AND OCCUPANCY CLASSIFICATION 2B.15.7.1.4 Explosion control. Explosion control shall be provided as specified in these code requirements, or spaces shall be equipped with the equivalent mechanical ventilation complying with the SBC 501. 2B.15.7.1.5 Grain elevators. Grain elevators, non-alcoholic malt houses and buildings for similar occupancies shall not be located within 9.1 m of interior lot lines or structures on the same lot, except where erected along a railroad right-of-way. 2B.15.7.1.6 Coal pockets. Coal pockets located less than 9.1 m from interior lot lines or from structures on the same lot shall be constructed of not less than Type IB construction. Where more than 9.1 m from interior lot lines, or where erected along a railroad right-of-way, the minimum type of construction of such structures not more than 20 m in height shall be Type IV. 2B.15.7.2 2B.15.7.2.1 2B.15.7.2.1.1 2B.15.7.2.2 2B.15.7.2.3 2B.15.7.2.4 2B.15.7.2.5 2B.15.7.2.6 2B.15.7.2.7 2B.15.7.2.8 2B.15.7.2.9 SBC 801 Flammable and combustible liquids. The storage, handling, processing and transporting of flammable and combustible liquids shall be in accordance with the SBC 501 and these code requirements. Mixed occupancies. Where the storage tank area is located in a building of two or more occupancies, and the quantity of liquid exceeds the maximum allowable quantity for one control area, the use shall be completely separated from adjacent fire areas in accordance with the requirements of Section 2A.2.3.2. Height exception. Where storage tanks are located within only a single-story building, the height limitation of Section 3.3 shall not apply for Group H. Tank protection. Storage tanks shall be noncombustible and protected from physical damage. A fire barrier wall or horizontal assemblies or both around the storage tank(s) shall be permitted as the method of protection from physical damage. Tanks. Storage tanks shall be approved tanks conforming to the requirements of these code requirements. Suppression. Group H shall be equipped throughout with an approved automatic sprinkler system, installed in accordance with Section 7.3. Leakage containment. A liquid-tight containment area compatible with the stored liquid shall be provided. The method of spill control, drainage control and secondary containment shall be in accordance with this code. Exception: Rooms where only double-wall storage tanks conforming to Section 2B.15.7.2.3 are used to store Class I, II and IIIA flammable and combustible liquids shall not be required to have a leakage containment area. Leakage alarm. An approved automatic alarm shall be provided to indicate a leak in a storage tank and room. The alarm shall sound an audible signal, 15 dBA above the ambient sound level, at every point of entry into the room in which the leaking storage tank is located. An approved sign shall be posted on every entry door to the tank storage room indicating the potential hazard of the interior room environment, or the sign shall state: WARNING, WHEN ALARM SOUNDS, THE ENVIRONMENT WITHIN THE ROOM MAY BE HAZARDOUS. The leakage alarm shall also be supervised in accordance with Chapter 9 to transmit a trouble signal. Tank vent. Storage tank vents for Class I, II or IIIA liquids shall terminate to the outdoor air in accordance with these code requirements. Room ventilation. Storage tank areas storing Class I, II or IIIA liquids shall be provided with mechanical ventilation. The mechanical ventilation system shall be in accordance with the SBC 501 and these code requirements. Explosion venting. Where Class I liquids are being stored, explosion venting shall be provided in accordance with this code. 2007 2/67 USE AND OCCUPANCY CLASSIFICATION 2B.15.7.2.10 2B.15.7.3 2B.15.7.3.1 2B.15.7.3.2 2B.15.7.3.3 2B.15.7.3.3.1 2B.15.7.3.3.2 2B.15.7.3.3.3 2B.15.7.3.4 2B.15.7.3.4.1 2B.15.7.3.5 SBC 801 Tank openings other than vents. Tank openings other than vents from tanks inside buildings shall be designed to ensure that liquids or vapor concentrations are not released inside the building. Liquefied petroleum gas-distribution facilities. The design and construction of propane, butane, propylene, butylene and other liquefied petroleum gasdistribution facilities shall conform to the applicable provisions of Sections 2B.15.7.3.1 through 2B.15.7.3.5.2. The storage and handling of liquefied petroleum gas systems shall conform to these code requirements. The design and installation of piping, equipment and systems that utilize liquefied petroleum gas shall be in accordance with and approved method. Liquefied petroleum gasdistribution facilities shall be ventilated in accordance with the SBC 501 and Section 2B.15.7.3.1. Air movement. Liquefied petroleum gas-distribution facilities shall be provided with air inlets and outlets arranged so that air movement across the floor of the facility will be uniform. The total area of both inlet and outlet openings shall be at least 645 mm2 for each 0.093 m2 of floor area. The bottom of such openings shall not be more than 152 mm above the floor. Construction. Liquefied petroleum gas-distribution facilities shall be constructed in accordance with Section 2B.15.7.3.3 for separate buildings, Section 2B.15.7.3.4 for attached buildings or Section 2B.15.7.3.5 for rooms within buildings. Separate buildings. Where located in separate buildings, liquefied petroleum gasdistribution facilities shall be occupied exclusively for that purpose or for other purposes having similar hazards. Such buildings shall be limited to one story in height and shall conform to Sections 2B.15.7.3.3.1 through 2B.15.7.3.3.3. Floors. The floor shall not be located below ground level and any spaces beneath the floor shall be solidly filled or shall be unenclosed. Materials. Walls, floors, ceilings, columns and roofs shall be constructed of noncombustible materials. Explosion venting. Explosion venting shall be provided in accordance with these code requirements. Attached buildings. Where liquefied petroleum gas-distribution facilities are located in an attached structure, the attached perimeter shall not exceed 50 percent of the perimeter of the space enclosed and the facility shall comply with Sections 2B.15.7.3.3 and 2B.15.7.3.4.1. Where the attached perimeter exceeds 50 percent, such facilities shall comply with Section 2B.15.7.3.5. Fire separation assemblies. Separation of the attached structures shall be provided by fire barrier walls and horizontal assemblies, or both, having a fireresistance rating of not less than 1 hour and shall not have openings. Fire barrier walls and horizontal assemblies, or both, between attached structures occupied only for the storage of LP-gas are permitted to have fire doors that comply with Section 4B.14. Such fire barrier walls and horizontal assemblies, or both, shall be designed to withstand a static pressure of at least 4,788 Pa, except where the building to which the structure is attached is occupied by operations or processes having a similar hazard. Rooms within buildings. Where liquefied petroleum gas-distribution facilities are located in rooms within buildings, such rooms shall be located in the first story above grade plane and shall have at least one exterior wall with sufficient exposed area to provide explosion venting as required in these code requirements. The building in which the room is located shall not have a basement or unventilated crawl space and the room shall comply with Sections 2B.15.7.3.5.1 and 2B.15.7.3.5.2. 2007 2/68 USE AND OCCUPANCY CLASSIFICATION 2B.15.7.3.5.1 2B.15.7.3.5.2 2B.15.7.4 2B.15.8 2B.15.8.1 2B.15.8.2 2B.15.8.3 Materials. Walls, floors, ceilings and roofs of such rooms shall be constructed by an approved noncombustible materials. Common construction. Walls and floor/ceiling assemblies common to the room and to the building within which the room is located shall have a fire barrier wall and horizontal assembly or both of not less than 1 hour and without openings. Common walls for rooms occupied only for storage of LP-gas are permitted to have opening protectives complying with Section 4B.14. Such walls and ceiling shall be designed to withstand a static pressure of at least 4,788 Pa. Exception: Where the building, within which the room is located, is occupied by operations or processes having a similar hazard. Dry cleaning plants. The construction and installation of dry cleaning plants shall be in accordance with the requirements of these code requirements, the SBC 501, the SBC 701 and NFPA 32. Dry cleaning solvents and systems shall be classified in accordance with this code. Groups H-3 and H-4. Groups H-3 and H-4 shall be constructed in accordance with the applicable provisions of these code requirements. Gas rooms. When gas rooms are provided, such rooms shall be separated from other areas by not less than a 1hour fire barrier. Floors in storage rooms. Floors in storage areas for corrosive liquids and highly toxic or toxic materials shall be of liquid-tight, noncombustible construction. Separation—highly toxic solids and liquids. Highly toxic solids and liquids not stored in approved hazardous materials storage cabinets shall be isolated from other hazardous materials storage by construction having a 1 hour fire-resistance rating. Group H-5. General. In addition to the requirements set forth elsewhere in these code requirements, Group H-5 shall comply with the provisions of Section 2B.15.9 and other code requirements. 2B.15.9.2 Fabrication areas. 2B.15.9.2.1 Hazardous materials in fabrication areas. 2B.15.9.2.1.1 Aggregate quantities. The aggregate quantities of hazardous materials stored and used in a single fabrication area shall not exceed the quantities set forth in Table 2B.15.9.2.1.1. Exception: The quantity limitations for any hazard category in Table 2B.15.9.2.1.1 shall not apply where the fabrication area contains quantities of hazardous materials not exceeding the maximum allowable quantities per control area established by Tables 2A.7.7(1) and 2A.7.7(2). 2B.15.9.2.1.2 Hazardous production materials. The maximum quantities of hazardous production materials stored in a single fabrication area shall not exceed the maximum allowable quantities per control area established by Tables 2A.7.7(1) and 2A.7.7(2). 2B.15.9.2.2 Separation. Fabrication areas, whose sizes are limited by the quantity of hazardous materials allowed by Table 2B.15.9.2.1.1, shall be separated from each other, from exit access corridors, and from other parts of the building by not less than 1 hour fire barriers. Exceptions: 1. Doors within such fire barrier walls, including doors to corridors, shall be only self-closing fire assemblies having a fire-protection rating of not less than 3/4 hour. 2. Windows between fabrication areas and exit access corridors are permitted to 2B.15.9 2B.15.9.1 SBC 801 2007 2/69 USE AND OCCUPANCY CLASSIFICATION be fixed glazing listed and labeled for a fire protection rating of at least 3/4 hour in accordance with Section 4B.14. TABLE 2B.15.9.2.1.1 QUANTITY LIMITS FOR HAZARDOUS MATERIALS IN A SINGLE FABRICATION AREA IN GROUP H-5a SOLIDS (kg / m2) HAZARD CATEGORY PHYSICAL-HAZARD MATERIALS Combustible dust Combustible fiber Combustible liquid Combination Class I, II and IIIA Cryogenic gas Explosives Flammable gas Flammable liquid Combination Class IA, IB and IC Combination Class I, II and IIIA Flammable solid Organic peroxide Oxidizing gas Combination of gaseous and liquefied Oxidizer Combination Pyrophoric material Unstable reactive Water reactive HEALTH-HAZARD MATERIALS Corrosives Highly toxic Toxics Note b Loose Baled II IIIA IIIB Note b Note b Not Applicable Flammable Oxidizing Not Applicable Note b Gaseous Liquefied A IB IC Not Applicable Not Applicable 0.005 Unclassified detonable Class I Class II Class III Class IV Class V Gaseous Liquefied Class 4 Class 3 Class 2 Class 1 Class 1, 2, 3 Class 4 Class 3 Class 2 Class 1 Class 3 Class 2 Class 1 Note b Note b 0.122 0.488 Not Limited Not limited LIQUIDS (liters / m2) Not Applicable Not Applicable 0.00025 0.0005 Not Limited 0.001 Not Applicable Note b Not Applicable 0.00006 0.00063 0.00063 0.00063 0.001 Not Applicable GAS (m3 @ NTP/m2) Not Applicable Not Applicable Not Applicable Note c 0.38 Note b Note b Note c Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable Note b 0.015 0.015 0.015 0.015 Note b Note b 0.122 0.488 Not Limited Note b 1.22 Not Limited Note b 0.00008 0.00008 0.00008 0.00008 0.00003 Note b 0.00006 0.00025 Not Limited 0.00003 0.00063 Not Limited 0.38 0.38 0.38 Not Limited Not Limited Not Limited Not Limited Not Limited Not Limited Not Applicable Notes c and d Note b Note b Note b Not Limited Not Applicable Not Limited Note c Note c a. Hazardous materials within piping shall not be included in the calculated quantities. b. Quantity of hazardous materials in a single fabrication shall not exceed the maximum allowable quantities per control area in Tables 2A.7.7(1) and 2A.7.7(2). c. The aggregate quantity of flammable, pyrophoric, toxic and highly toxic gases shall not exceed 255 cubic meters at NTP. d. The aggregate quantity of pyrophoric gases in the building shall not exceed the amounts set forth in Table 2B.15.3.2. 2B.15.9.2.3 Location of occupied levels. Occupied levels of fabrication areas shall be located at or above the first story above grade plane. 2B.15.9.2.4 Floors. Except for surfacing, floors within fabrication areas shall be of noncombustible construction. SBC 801 2007 2/70 USE AND OCCUPANCY CLASSIFICATION Openings through floors of fabrication areas are permitted to be unprotected where the interconnected levels are used solely for mechanical equipment directly related to such fabrication areas (see also Section 2B.15.9.2.5). Floors forming a part of an occupancy separation shall be liquid tight. 2B.15.9.2.5 Shafts and openings through floors. Elevator shafts, vent shafts and other openings through floors shall be enclosed when required by Section 4B.7. Mechanical, duct and piping penetrations within a fabrication area shall not extend through more than two floors. The annular space around penetrations for cables, cable trays, tubing, piping, conduit or ducts shall be sealed at the floor level to restrict the movement of air. The fabrication area, including the areas through which the ductwork and piping extend, shall be considered a single conditioned environment. 2B.15.9.2.6 Ventilation. Mechanical exhaust ventilation shall be provided throughout the fabrication area at the rate of not less than 0.044 L/S/m2 of floor area. The exhaust air duct system of one fabrication area shall not connect to another duct system outside that fabrication area within the building. A ventilation system shall be provided to capture and exhaust fumes and vapors at workstations. Two or more operations at a workstation shall not be connected to the same exhaust system where either one or the combination of the substances removed could constitute a fire, explosion or hazardous chemical reaction within the exhaust duct system. Exhaust ducts penetrating occupancy separations shall be contained in a shaft of equivalent fire-resistance construction. Exhaust ducts shall not penetrate fire walls. Fire dampers shall not be installed in exhaust ducts. 2B.15.9.2.7 Transporting hazardous production materials to fabrication areas. Hazardous production materials shall be transported to fabrication areas through enclosed piping or tubing systems that comply with Section 2B.15.9.6.1, through service corridors complying with Section 2B.15.9.4, or in exit access corridors as permitted in the exception to Section 2B.15.9.3. The handling or transporting of hazardous production materials within service corridors shall comply with these code requirements. 2B.15.9.2.8 Electrical. 2B.15.9.2.8.1 General. Electrical equipment and devices within the fabrication area shall comply with the SBC 401. The requirements for hazardous locations need not be applied where the average air change is at least four times that set forth in Section 2B.15.9.2.6 and where the number of air changes at any location is not less than three times that required by Section 2B.15.9.2.6. The use of re-circulated air shall be permitted. 2B.15.9.2.8.2 Workstations. Workstations shall not be energized without adequate exhaust ventilation. See Section 2B.15.9.2.6 for workstation exhaust ventilation requirements. 2B.15.9.3 SBC 801 Exit access corridors. Exit access corridors shall comply with Chapter 8 and shall be separated from fabrication areas as specified in Section 2B.15.9.2.2. Exit access corridors shall not contain HPM and shall not be used for transporting such materials, except through closed piping systems as provided in Section 2B.15.9.6.3. Exception: Where existing fabrication areas are altered or modified, HPM is allowed to be transported in existing exit access corridors, subject to the following conditions: 1. Corridors. Exit access corridors adjacent to the fabrication area where the 2007 2/71 USE AND OCCUPANCY CLASSIFICATION alteration work is to be done shall comply with Section 8.16 for a length determined as follows: 1.1 The length of the common wall of the corridor and the fabrication area; and 1.2 For the distance along the exit access corridor to the point of entry of HPM into the exit access corridor serving that fabrication area. 2. Emergency alarm system. There shall be an emergency telephone system, a local manual alarm station or other approved alarm-initiating device within exit access corridors at not more than 46 m intervals and at each exit and exit access doorway. The signal shall be relayed to an approved central, proprietary or remote station service or the emergency control station and shall also initiate a local audible alarm. 3. Pass-throughs. Self-closing doors having a fire-protection rating of not less than 1 hour shall separate pass-throughs from existing exit access corridors. Pass-throughs shall be constructed as required for the exit access corridors, and protected by an approved automatic fire-extinguishing system. 2B.15.9.4 Service corridors. 2B.15.9.4.1 Occupancy. Service corridors shall be classified as Group H-5. 2B.15.9.4.2 Use conditions. Service corridors shall be separated from exit access corridors as 2B.15.9.4.3 2B.15.9.4.4 2B.15.9.4.5 2B.15.9.4.6 2B.15.9.4.6.1 2B.15.9.4.6.2 2B.15.9.4.6.3 2B.15.9.4.6.4 2B.15.9.4.6.5 SBC 801 required by Section 2B.15.9.2.2. Service corridors shall not be used as a required exit access corridor. Mechanical ventilation. Service corridors shall be mechanically ventilated as required by Section 2B.15.9.2.6 or at not less than six air changes per hour, whichever is greater. Means of egress. The maximum distance of travel from any point in a service corridor to an exit, exit access corridor or door into a fabrication area shall not exceed 23 m. Dead ends shall not exceed 1.22 m in length. There shall be not less than two exits, and not more than one-half of the required means of egress shall require travel into a fabrication area. Doors from service corridors shall swing in the direction of egress travel and shall be self-closing. Minimum width. The minimum clear width of a service corridor shall be 1.5 m, or 838 mm wider than the widest cart or truck used in the corridor, whichever is greater. Emergency alarm system. Emergency alarm systems shall be provided in accordance with this section and Sections 2B.14.7.1 and 2B.14.7.2. The maximum allowable quantity per control area provisions shall not apply to emergency alarm systems required for HPM. Service corridors. An emergency alarm system shall be provided in service corridors, with at least one alarm device in each service corridor. Exit access corridors and exit enclosures. Emergency alarms for exit access corridors and exit enclosures shall comply with Section 2B.14.7.2. Liquid storage rooms, HPM rooms and gas rooms. Emergency alarms for liquid storage rooms, HPM rooms and gas rooms shall comply with Section 2B.14.7.1. Alarm-initiating devices. An approved emergency telephone system, local alarm manual pull stations, or other approved alarm-initiating devices are allowed to be used as emergency alarm-initiating devices. Alarm signals. Activation of the emergency alarm system shall sound a local alarm and transmit a signal to the emergency control station. 2007 2/72 USE AND OCCUPANCY CLASSIFICATION 2B.15.9.5 Storage of hazardous production materials. 2B.15.9.5.1 General. Storage of HPM in fabrication areas shall be within approved or listed 2B.15.9.5.2 2B.15.9.5.2.1 2B.15.9.5.2.2 2B.15.9.5.2.3 2B.15.9.5.3 2B.15.9.5.4 2B.15.9.5.5 2B.15.9.5.6 2B.15.9.5.7 2B.15.9.5.8 SBC 801 storage cabinets or gas cabinets, or within a workstation. The storage of hazardous production materials in quantities greater than those listed in Tables 2A.7.7(1) or 2A.7.7(2) shall be in liquid storage rooms, HPM rooms or gas rooms as appropriate for the materials stored. The storage of other hazardous materials shall be in accordance with other applicable provisions of these code requirements and these code requirements. Construction. HPM rooms and gas rooms. HPM rooms and gas rooms shall be separated from other areas by not less than a 2 hours fire barrier where the area is 27.9 m2 or more and not less than a 1 hour fire barrier where the area is less than 27.9 m2. Liquid storage rooms. Liquid storage rooms shall be constructed in accordance with the following requirements: 1. Rooms in excess of 46.5 m2 shall have at least one exterior door approved for Civil Defence access. 2. Rooms shall be separated from other areas by fire barriers having a fireresistance rating of not less than 1 hour for rooms up to 13.9 m2 in area and not less than 2 hours where the room is more than 13.9 m2 in area. 3. Shelving, racks and wainscoting in such areas shall be of noncombustible construction or wood of not less than 25 mm nominal thickness. 4. Rooms used for the storage of Class I flammable liquids shall not be located in a basement. Floors. Except for surfacing, floors of HPM rooms and liquid storage rooms shall be of noncombustible liquid-tight construction. Raised grating over floors shall be of noncombustible materials. Location. Where HPM rooms, liquid storage rooms and gas rooms are provided, they shall have at least one exterior wall and such wall shall be not less than 9.1 m from property lines, including property lines adjacent to public ways. Explosion control. Explosion control shall be provided where required by Section 2B.14.5.1. Exits. Where two exits are required from HPM rooms, liquid storage rooms and gas rooms, one shall be directly to the outside of the building. Doors. Doors in a fire barrier wall, including doors to corridors, shall be selfclosing fire assemblies having a fire-protection rating of not less than 3/4 hour. Ventilation. Mechanical exhaust ventilation shall be provided in liquid storage rooms, HPM rooms and gas rooms at the rate of not less than 0.044 L/S/m2 of floor area or six air changes per hour, whichever is greater, for categories of material. Exhaust ventilation for gas rooms shall be designed to operate at a negative pressure in relation to the surrounding areas and direct the exhaust ventilation to an exhaust system. Emergency alarm system. An approved emergency alarm system shall be provided for HPM rooms, liquid storage rooms and gas rooms. 1. Emergency alarm-initiating devices shall be installed outside of each interior exit door of such rooms. Activation of an emergency alarm-initiating device shall sound a local alarm and transmit a signal to the emergency control station. 2. An approved emergency telephone system, local alarm manual pull stations or other approved alarm-initiating devices are allowed to be used as emergency alarm-initiating devices. 2007 2/73 USE AND OCCUPANCY CLASSIFICATION 2B.15.9.6 Piping and tubing. 2B.15.9.6.1 General. Hazardous production materials piping and tubing shall comply with this section and ANSI B31.3. 2B.15.9.6.2 Supply piping and tubing. HPM having a health-hazard ranking of 3 or 4. Systems supplying HPM liquids or gases having a health-hazard ranking of 3 or 4 shall be welded throughout, except for connections, to the systems that are within a ventilated enclosure if the material is a gas, or an approved method of drainage or containment is provided for the connections if the material is a liquid. 2B.15.9.6.2.2 Location in service corridors. Hazardous production materials supply piping or tubing in service corridors shall be exposed to view. 2B.15.9.6.2.3 Excess flow control. Where HPM gases or liquids are carried in pressurized piping above 103.4 kPa, excess flow control shall be provided. Where the piping originates from within a liquid storage room, HPM room or gas room, the excess flow control shall be located within the liquid storage room, HPM room or gas room. Where the piping originates from a bulk source, the excess flow control shall be located as close to the bulk source as practical. 2B.15.9.6.3 Installations in exit access corridors and above other occupancies. The installation of hazardous production material piping and tubing within the space defined by the walls of exit access corridors and the floor or roof above or in concealed spaces above other occupancies shall be in accordance with Section 2B.15.9.6.2 and the following conditions: 1. Automatic sprinklers shall be installed within the space unless the space is less than 152 mm in the least dimension. 2. Ventilation not less than six air changes per hour shall be provided. The space shall not be used to convey air from any other area. 3. Where the piping or tubing is used to transport HPM liquids, a receptor shall be installed below such piping or tubing. The receptor shall be designed to collect any discharge or leakage and drain it to an approved location. The 1hourenclosure shall not be used as part of the receptor. 4. HPM supply piping and tubing and HPM nonmetallic waste lines shall be separated from the exit access corridor and from occupancies other than Group H-5 by construction as required for walls or partitions that have a fire protection rating of not less than 1 hour. Where gypsum wallboard is used, joints on the piping side of the enclosure are not required to be taped, provided the joints occur over framing members. Access openings into the enclosure shall be protected by approved fire-resistance-rated assemblies. 5. Readily accessible manual or automatic remotely activated fail-safe emergency shutoff valves shall be installed on piping and tubing other than waste lines at the following locations: 5.1 At branch connections into the fabrication area. 5.2 At entries into exit access corridors. Exception: Transverse crossings of the corridors by supply piping that is enclosed within a ferrous pipe or tube for the width of corridor need not comply with Items 1 through 5. 2B.15.9.6.4 Identification. Piping, tubing and HPM waste lines shall be identified in accordance with ANSI A13.1 to indicate the material being transported. 2B.15.9.7 Continuous gas-detection systems. A continuous gas-detection system shall be provided for HPM gases when the physiological warning properties of the gas are at a higher level than the accepted permissible exposure limit (PEL) for the gas and for flammable gases in accordance with this section. 2B.15.9.6.2.1 SBC 801 2007 2/74 USE AND OCCUPANCY CLASSIFICATION 2B.15.9.7.1 Where required. A continuous gas-detection system shall be provided in the areas identified in Sections 2B.15.9.7.1.1 through 2B.15.9.7.1.4. 2B.15.9.7.1.1 Fabrication areas. A continuous gas-detection system shall be provided in fabrication areas when gas is used in the fabrication area. 2B.15.9.7.1.2 HPM rooms. A continuous gas-detection system shall be provided in HPM rooms when gas is used in the room. 2B.15.9.7.1.3 Gas cabinets, exhausted enclosures and gas rooms. A continuous gas-detection system shall be provided in gas cabinets and exhausted enclosures. A continuous gas-detection system shall be provided in gas rooms when gases are not located in gas cabinets or exhausted enclosures. 2B.15.9.7.1.4 Exit access corridors. When gases are transported in piping placed within the space defined by the walls of an exit access corridor, and the floor or roof above the exit access corridor, a continuous gas-detection system shall be provided where piping is located and in the exit access corridor. Exception: A continuous gas-detection system is not required for occasional transverse crossings of the corridors by supply piping that is enclosed in a ferrous pipe or tube for the width of the corridor. 2B.15.9.7.2 Gas-detection system operation. The continuous gas-detection system shall be capable of monitoring the room, area or equipment in which the gas is located at or below the PEL or ceiling limit of the gas for which detection is provided. For flammable gases, the monitoring detection threshold level shall be vapor concentrations in excess of 20 percent of the lower explosive limit (LFL). Monitoring for highly toxic and toxic gases shall also comply with the requirements for such material in these code requirements. 2B.15.9.7.2.1 Alarms. The gas detection system shall initiate a local alarm and transmit a signal to the emergency control station when a short-term hazard condition is detected. The alarm shall be both visual and audible and shall provide warning both inside and outside the area where the gas is detected. The audible alarm shall be distinct from all other alarms. 2B.15.9.7.2.2 Shutoff of gas supply. The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for which gas is detected when a short-term hazard condition is detected. Automatic closure of shutoff valves shall comply with the following: 1. Where the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure, the shutoff valve in the gas cabinet or exhausted enclosure for the specific gas detected shall automatically close. 2. Where the gas-detection sampling point initiating the gas detection system alarm is within a room and compressed gas containers are not in gas cabinets or an exhausted enclosure, the shutoff valves on all gas lines for the specific gas detected shall automatically close. 3. Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribution manifold enclosure, the shutoff valve supplying the manifold for the compressed gas container of the specific gas detected shall automatically close. Exception: Where the gas-detection sampling point initiating the gas detection system alarm is at the use location or within a gas valve enclosure of a branch line downstream of a piping distribution manifold, the shutoff valve for the branch line located in the piping distribution manifold enclosure shall automatically close. 2B.15.9.8 Manual fire alarm system. An approved manual fire alarm system shall be provided throughout buildings containing Group H-5. Activation of the alarm system shall initiate a local alarm and transmit a signal to the emergency control SBC 801 2007 2/75 USE AND OCCUPANCY CLASSIFICATION station. The fire alarm system shall be designed and installed in accordance with Section 7.7. 2B.15.9.9 Emergency control station. An emergency control station shall be provided on the premises at an approved location, outside of the fabrication area and shall be continuously staffed by trained personnel. The emergency control station shall receive signals from emergency equipment and alarm and detection systems. Such emergency equipment and alarm and detection systems shall include, but not necessarily be limited to, the following where such equipment or systems are required to be provided either in Section 2B.15.9 or elsewhere in these code requirements: 1. Automatic fire sprinkler system alarm and monitoring systems. 2. Manual fire alarm systems. 3. Emergency alarm systems. 4. Continuous gas-detection systems. 5. Smoke detection systems. 6. Emergency power system. 2B.15.9.10 Emergency power system. An emergency power system shall be provided in Group H-5 occupancies where required in Section 2B.15.9.10.1. The emergency power system shall be designed to supply power automatically to required electrical systems when the normal electrical supply system is interrupted. 2B.15.9.10.1 Where required. Emergency power shall be provided for electrically operated equipment and connected control circuits for the following systems: 1. HPM exhaust ventilation systems. 2. HPM gas cabinet ventilation systems. 3. HPM exhausted enclosure ventilation systems. 4. HPM gas room ventilation systems. 5. HPM gas detection systems. 6. Emergency alarm systems. 7. Manual fire alarm systems. 8. Automatic sprinkler system monitoring and alarm systems. 9. Electrically operated systems required elsewhere in these code requirements applicable to the use, storage or handling of HPM. 2B.15.9.10.2 Exhaust ventilation systems. Exhaust ventilation systems are allowed to be designed to operate at not less than one-half the normal fan speed on the emergency power system where it is demonstrated that the level of exhaust will maintain a safe atmosphere. 2B.15.9.11 Fire sprinkler system protection in exhaust ducts for HPM. 2B.15.9.11.1 2B.15.9.11.2 2B.15.9.11.3 SBC 801 General. Automatic fire sprinkler system protection shall be provided in exhaust ducts conveying vapors, fumes, mists or dusts generated from HPM in accordance with this section and the SBC 501. Metallic and noncombustible, nonmetallic exhaust ducts. Automatic fire sprinkler system protection shall be provided in metallic and noncombustible, nonmetallic exhaust ducts where all of the following conditions apply: 1. Where the largest cross-sectional diameter is equal to or greater than 254 mm. 2. The ducts are within the building. 3. The ducts are conveying flammable vapors or fumes. Combustible nonmetallic exhaust ducts. Automatic fire sprinkler system protection shall be provided in combustible nonmetallic exhaust ducts where the largest cross-sectional diameter of the duct is equal to or greater than 254 mm. Exceptions: 1. Ducts listed or approved for applications without automatic fire sprinkler 2007 2/76 USE AND OCCUPANCY CLASSIFICATION 2B.15.9.11.4 system protection. 2. Ducts not more than 3.7 m in length installed below ceiling level. Automatic sprinkler locations. Sprinkler systems shall be installed at 3.7 m intervals in horizontal ducts and at changes in direction. In vertical ducts, sprinklers shall be installed at the top and at alternate floor levels. SECTION 2B.16 APPLICATION OF FLAMMABLE FINISHES 2B.16.1 General. The provisions of this section shall apply to the construction, installation and use of buildings and structures, or parts thereof, for the spraying of flammable paints, varnishes and lacquers or other flammable materials or mixtures or compounds used for painting, varnishing, staining or similar purposes. Such construction and equipment shall comply with these code requirements. 2B.16.2 Spray rooms. Spray rooms shall be enclosed with fire barrier walls and horizontal assemblies or both with not less than a 1hour fire-resistance rating. Floors shall be waterproofed and drained in an approved manner. Surfaces. The interior surfaces of spray rooms shall be smooth and shall be so constructed to permit the free passage of exhaust air from all parts of the interior and to facilitate washing and cleaning, and shall be so designed to confine residues within the room. Aluminum shall not be used. 2B.16.2.1 2B.16.3 2B.16.3.1 2B.16.4 Spraying spaces. Spraying spaces shall be ventilated with an exhaust system to prevent the accumulation of flammable mist or vapors in accordance with the SBC 501. Where such spaces are not separately enclosed, noncombustible spray curtains shall be provided to restrict the spread of flammable vapors. Surfaces. The interior surfaces of spraying spaces shall be smooth and continuous without edges, and shall be so constructed to permit the free passage of exhaust air from all parts of the interior and to facilitate washing and cleaning, and shall be so designed to confine residues within the spraying space. Aluminum shall not be used. Fire protection. An automatic fire-extinguishing system shall be provided in all spray, dip and immersing spaces and storage rooms, and shall be installed in accordance with Chapter 7. SECTION 2B.17 DRYING ROOMS 2B.17.1 General. A drying room or dry kiln installed within a building shall be constructed entirely of approved noncombustible materials or assemblies of such materials regulated by the approved rules or as required in the general and specific sections of Section 2B of Chapter 2 for special occupancies and where applicable to the general requirements of SBC 501. 2B.17.2 Piping clearance. Overhead heating pipes shall have a clearance of not less than 51 mm from combustible contents in the dryer. 2B.17.3 Insulation. Where the operating temperature of the dryer is 79°C or more, metal enclosures shall be insulated from adjacent combustible materials by not less than 305 mm of airspace, or the metal walls shall be lined with 6.35 mm insulating mill SBC 801 2007 2/77 USE AND OCCUPANCY CLASSIFICATION board or other approved equivalent insulation. 2B.17.4 Fire protection. Drying rooms designed for high-hazard materials and processes, including special occupancies as provided for in Section 2B of Chapter 2, shall be protected by an approved automatic fire-extinguishing system conforming to the provisions of Chapter 7. SECTION 2B.18 ORGANIC COATINGS 2B.18.1 Building features. Manufacturing of organic coatings shall be done only in buildings that do not have pits or basements. 2B.18.2 Location. Organic coating manufacturing operations and operations incidental to or connected therewith shall not be located in buildings having other occupancies. 2B.18.3 Process mills. Mills operating with close clearances and that process flammable and heat-sensitive materials, such as nitrocellulose, shall be located in a detached building or noncombustible structure. 2B.18.4 Tank storage. Storage areas for flammable and combustible liquid tanks inside of structures shall be located at or above grade and shall be separated from the processing area by not less than 2 hours fire-resistance-rated fire barriers. 2B.18.5 Nitrocellulose storage. Nitrocellulose storage shall be located on a detached pad or in a separate structure or a room enclosed with no less than 2 hours fireresistance-rated fire barriers. 2B.18.6 Finished products. Storage rooms for finished products that are flammable or combustible liquids shall be separated from the processing area by fire barriers having a fire-resistance rating of at least 2 hours, and openings in the walls shall be protected with approved opening protectives. SBC 801 2007 2/78 GENERAL BUILDING HEIGHTS AND AREAS CHAPTER 3 GENERAL BUILDING HEIGHTS AND AREAS SECTION 3.1 GENERAL 3.1.1 Scope. The provisions of this chapter control the height and area of structures hereafter erected and additions to existing structures. 3.1.2 Premises identification. Approved numbers or addresses shall be provided for new buildings in such a position as to be clearly visible and legible from the street or roadway fronting the property. Letters or numbers shall be a minimum 76 mm in height and stroke of minimum 12.7 mm of a contrasting color to the background itself. SECTIONS 3.2 DEFINITIONS 3.2.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. AREA, BUILDING. The area included within surrounding exterior walls (or exterior walls and fire walls) exclusive of vent shafts and courts. Areas of the building not provided with surrounding walls shall be included in the building area if such areas are included within the horizontal projection of the roof or floor above. BASEMENT. That portion of a building that is partly or completely below grade plane (See “Story above grade plane” in Chapter 1). A basement shall be considered as a story above grade plane where the finished surface of the floor above the basement is: 1. More than 1.8 m above grade plane; 2. More than 1.8 m above the finished ground level for more than 50 percent of the total building perimeter; or 3. More than 3.7 m above the finished ground level at any point. GRADE PLANE. A reference plane representing the average of finished ground level adjoining the building at exterior walls. Where the finished ground level slopes away from the exterior walls, the reference plane shall be established by the lowest points within the area between the building and the lot line or, where the lot line is more than 1.8 m from the building, between the building and a point 1.8 m from the building. HEIGHT, BUILDING. The vertical distance from grade plane to the average height of the highest roof surface. HEIGHT, STORY. The vertical distance from top to top of two successive finished floor surfaces; and, for the topmost story, from the top of the floor finish to the top of the ceiling joists or, where there is not a ceiling, to the top of the roof rafters. SBC 801 INDUSTRIAL EQUIPMENT PLATFORM. An unoccupied, elevated platform in an industrial occupancy used exclusively for mechanical systems or industrial process equipment, including the associated elevated walkways, stairs and ladders 2007 3/1 GENERAL BUILDING HEIGHTS AND AREAS necessary to access the platform (see Section 3.5.5). MEZZANINE. An intermediate level or levels between the floor and ceiling of any story with an aggregate floor area of not more than one-third of the area of the room or space in which the level or levels are located (see Section 3.5). STORY. That portion of a building included between the upper surface of a floor and the upper surface of the floor or roof next above (also see “Basement” and “Mezzanine”). SECTION 3.3 GENERAL HEIGHT AND AREA LIMITATIONS 3.3.1 3.3.1.1 3.3.1.2 3.3.1.3 3.3.1.4 3.3.2 General. The height and area for buildings of different construction types shall be governed by the intended use of the building and shall not exceed the limits in Table 3.3 except as modified hereafter. Each part of a building included within the exterior walls or the exterior walls and fire walls where provided shall be permitted to be a separate building. Basements. Basements need not be included in the total allowable area provided they do not exceed the area permitted for a one-story building. Special industrial occupancies. Buildings and structures designed to house lowhazard industrial processes that require large areas and unusual heights to accommodate crane ways or special machinery and equipment including, among others, rolling mills; structural metal fabrication shops and foundries; or the production and distribution of electric, gas or steam power, shall be exempt from the height and area limitations of Table 3.3. Buildings on same lot. Two or more buildings on the same lot shall be regulated as separate buildings or shall be considered as portions of one building if the height of each building and the aggregate area of buildings are within the limitations of Table 3.3 as modified by Sections 3.4 and 3.6. The provisions of this code applicable to the aggregate building shall be applicable to each building. Type I construction. Buildings of Type I construction permitted to be of unlimited tabular heights and areas are not subject to the special requirements that allow unlimited area buildings in Section 3.7 or unlimited height in Sections 3.3.1.2 and 3.4.3 or increased height and areas for other types of construction. Party walls. Any wall located on a property line between adjacent buildings, which is used or adapted for joint service between the two buildings, shall be constructed as a fire wall in accordance with Section 4B.6, without openings and shall create separate buildings. SECTION 3.4 HEIGHT MODIFICATIONS 3.4.1 SBC 801 General. The heights permitted by Table 3.3 shall only be increased in accordance with this section. Exception: The height of one-story aircraft hangars, aircraft paint hangars and buildings used for the manufacturing of aircraft shall not be limited if the building is provided with an automatic fire-extinguishing system in accordance with Chapter 7 and is entirely surrounded by public ways or yards not less in width than one and one-half times the height of the building. 2007 3/2 GENERAL BUILDING HEIGHTS AND AREAS TABLE 3.3 ALLOWABLE HEIGHT AND BUILDING AREAS Height limitations shown as stories and meters above grade plane. Area limitations as determined by the definition of “Area, building,” per floor. GROUP A-1 A-2 A-3 A-4 A-5 B E F-1 F-2 H-1 H-2 H-3 H-4 H-5 I-1 I-2 I-3 I-4 M R-1 R-2a R-3a R-4 S-1 S-2b-c Uc Hgt(S) Hgt(m) S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A S A TYPE I A B UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL 1 6,401 UL 6,401 UL UL UL UL 3 UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL 160 5 UL 11 UL 11 UL 11 UL UL UL 11 UL 5 UL 11 UL 11 UL 1 5,029 3 5,029 6 18,288 7 UL 3 UL 9 16,764 4 UL 4 UL 5 18,440 11 UL 11 UL 11 UL 11 UL 11 UL 11 14,630 11 24,079 5 10,820 TYPE OF CONSTRUCTION TYPE II TYPE III TYPE IV A B A B HT 65 3 4,724 3 4,724 3 4,724 3 4,724 UL UL 5 11,430 3 8,077 4 7,620 5 11,278 1 3,353 2 3,353 4 8,077 5 11,430 3 11,430 4 5,791 2 4,572 2 4,572 3 8,077 4 6,553 4 7,315 4 7,315 4 UL 4 7,315 4 7,925 5 11,887 4 5,791 55 2 2,591 2 2,896 2 2,896 2 2,896 UL UL 4 7,010 2 4,420 2 4,724 3 7,010 1 2,134 1 2,134 2 4,267 3 5,334 3 7,010 3 3,048 1 3,353 1 3,353 2 3,962 4 3,810 4 4,877 4 4,877 4 UL 4 4,877 3 5,334 4 7,925 2 2,591 65 3 4,267 3 4,267 3 4,267 3 4,267 UL UL 5 8,687 3 7,163 3 5,791 4 8,687 1 2,896 2 2,896 4 5,334 5 8,687 3 8,687 4 5,029 1 3,658 2 3,200 3 7,163 4 5,639 4 7,315 4 7,315 4 UL 4 7,315 3 7,925 4 11,887 3 4,267 55 2 2,591 2 2,896 2 2,896 2 2,896 UL UL 4 5,791 2 4,420 2 3,658 3 5,486 1 2,134 1 2,134 2 3,962 3 5,334 3 5,791 3 3,048 NP NP 1 2,286 2 3,962 4 3,810 4 4,877 4 4,877 4 UL 4 4,877 3 5,334 4 7,925 2 2,591 65 3 4,572 3 4,572 3 4,572 3 4,572 UL UL 5 10,973 3 7,772 4 10,211 5 24,536 1 3,200 2 3,200 4 7,772 5 10,973 3 10,973 4 5,486 1 3,658 2 3,658 3 7,772 4 6,248 4 6,248 4 6,248 4 UL 4 6,248 4 7,772 5 11,735 4 5,486 TYPE V A B 50 2 3,505 2 3,505 2 3,505 2 3,505 UL UL 3 5,486 1 5,639 2 4,267 3 6,401 1 2,286 1 2,286 2 3,048 3 5,486 3 5,486 3 3,200 1 2,896 2 2,286 1 5,639 3 4,267 3 3,658 3 3,658 3 UL 3 3,658 3 4,267 4 6,401 2 2,743 40 1 1,676 1 1,829 1 1,829 1 1,829 UL UL 2 2,743 1 2,896 1 2,591 2 3,962 NP NP 1 914 1 1,524 2 1,981 2 2,743 2 1,372 NP NP 1 1,524 1 2,743 1 2,743 2 2,134 2 2,134 3 UL 2 2,134 1 2,743 2 4,115 1 1,676 UL = Unlimited, NP = Not permitted; a = As applicable in SBC 100; b.= For open parking structures, see Section 2B.6.3; and c.= For private garages, see Section 2B.6.1. SBC 801 2007 3/3 GENERAL BUILDING HEIGHTS AND AREAS 3.4.2 Automatic sprinkler system increase. Where a building is equipped throughout with an approved automatic sprinkler system in accordance with Section 7.3.3.1.1, the value specified in Table 3.3 for maximum height is increased by 6.1 m and the maximum number of stories is increased by one story. These increases are permitted in addition to the area increase in accordance with Sections 3.6.2 and 3.6.3. For Group R buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 7.3.3.1.2, the value specified in Table 3.3 for maximum height is increased by 6.1 m and the maximum number of stories is increased by one story, but shall not exceed four stories or 18.3 m, respectively. Exceptions: 1. Group I-2 of Type IIB, III, IV or V construction. 2. Group H-1, H-2, H-3 or H-5. 3. Fire-resistance rating substitution in accordance with Table 4A.1 (FR Rated Requirements for Building Elements). 3.4.3 Roof structures. Towers, spires, steeples and other roof structures shall be constructed of materials consistent with the required type of construction of the building except where other construction is permitted by Section 6.9.2.1 of SBC 201. Such structures shall not be used for habitation or storage. The structures shall be unlimited in height if of noncombustible materials and shall not extend more than 6.1 m above the allowable height if of combustible materials (see Chapter 6 of SBC 201 for additional requirements). SECTION 3.5 MEZZANINES 3.5.1 General. A mezzanine or mezzanines in compliance with this section shall be considered a portion of the floor below. Such mezzanines shall not contribute to either the building area or number of stories as regulated by Section 3.3.1. The area of the mezzanine shall be included in determining the fire area defined in Section 4A.2. The clear height above and below the mezzanine floor construction shall not be less than 2.1 m. 3.5.2 Area limitation. The aggregate area of a mezzanine or mezzanines within a room shall not exceed one-third of the area of that room or space in which they are located. The enclosed portions of rooms shall not be included in a determination of the size of the room in which the mezzanine is located. In determining the allowable mezzanine area, the area of the mezzanine shall not be included in the area of the room. Exception: The aggregate area of mezzanines in buildings and structures of Type I or II construction for special industrial occupancies in accordance with Section 3.3.1.2 shall not exceed two-thirds of the area of the room. 3.5.3 Egress. Each occupant of a mezzanine shall have access to at least two independent means of egress where the common path of egress travel exceeds the limitations of Section 8.4.2.5. Where a stairway provides a means of exit access from a mezzanine, the maximum travel distance includes the distance traveled on the stairway measured in the plane of the tread nosing. Exceptions: 1. A single means of egress shall be permitted in accordance with Section SBC 801 2007 3/4 GENERAL BUILDING HEIGHTS AND AREAS 8.4.2.1. 2. Accessible means of egress shall be provided in accordance with Section 8.3.2.13. 3.5.4 Openness. A mezzanine shall be open and unobstructed to the room in which such mezzanine is located except for walls not more than 1067 mm high, columns and posts. Exceptions: 1. Mezzanines or portions thereof are not required to be open to the room in which the mezzanines are located, provided that the occupant load of the aggregate area of the enclosed space does not exceed 10 add units. 2. A mezzanine having two or more means of egress is not required to be open to the room in which the mezzanine is located, if at least one of the means of egress provides direct access to an exit from the mezzanine level. 3. Mezzanines or portions thereof are not required to be open to the room in which the mezzanines are located, provided that the aggregate floor area of the enclosed space does not exceed 10 percent of the mezzanine area. 4. In industrial facilities, mezzanines used for control equipment are permitted to be glazed on all sides. 5. In Group F occupancies of unlimited area, meeting the requirements of Section 3.7.2 or 3.7.3, mezzanines or portions thereof are not required to be open to the room in which the mezzanines are located, provided that an approved fire alarm system is installed throughout the entire building or structure and notification appliances are installed throughout the mezzanines in accordance with the provisions of NFPA 72. In addition, the fire alarm system shall be initiated by automatic sprinkler water flow. 3.5.5 Industrial equipment platforms. Industrial equipment platforms in buildings shall not be considered as a portion of the floor below. Such equipment platforms shall not contribute to either the building area or the number of stories as regulated by Section 3.3.1. The area of the industrial equipment platform shall not be included in determining the fire area. Industrial equipment platforms shall not be a part of any mezzanine, and such platforms and the walkways, stairs and ladders providing access to an equipment platform shall not serve as a part of the means of egress from the building. Area limitations. The aggregate area of all industrial equipment platforms within a room shall not exceed two-thirds of the area of the room in which they occur. Where an equipment platform is located in the same room as a mezzanine, the area of the mezzanine shall be determined by Section 3.5.2, and the combined aggregate area of the equipment platforms and mezzanines shall not exceed twothirds of the room in which they occur. Fire suppression. Where located in a building that is required to be protected by an automatic sprinkler system, industrial equipment platforms shall be fully protected by sprinklers above and below the platform, where required by the standards referenced in Section 7.3.3. Guards. Equipment platforms shall have guards where required by Section 8.12.1. 3.5.5.1 3.5.5.2 3.5.5.3 SBC 801 2007 3/5 GENERAL BUILDING HEIGHTS AND AREAS SECTION 3.6 AREA MODIFICATIONS 3.6.1 General. The areas limited by Table 3.3 shall be permitted to be increased due to frontage (If) and automatic sprinkler system protection (Is) in accordance with the following: (Equation 3-1) 3.6.1.1 3.6.2 Where: Aa = Allowable area per floor (square meters). At = Tabular area per floor in accordance with Table 3.3 (square meters). = Area increase due to frontage (percent) as calculated in accordance with If Section 3.6.2. Is = Area increase due to sprinkler protection (percent) as calculated in accordance with Section 3.6.3. Basements. A single basement need not be included in the total allowable area provided such basement does not exceed the area permitted for a one-story building. Frontage increase. Every building shall adjoin or have access to a public way to receive an area increase for frontage. Where a building has more than 25 percent of its perimeter on a public way or open space having a minimum width of 6.1 m, the frontage increase shall be determined in accordance with the following: (Equation 3-2) 3.6.2.1 3.6.2.2 SBC 801 Where: If = Area increase due to frontage F = Building perimeter which fronts on a public way or open space having 6.1 m open minimum width (meters) P = Perimeter of entire building (meters) = Width of public way or open space (meters) in accordance with Section W 3.6.2.1. Width limits. W must be at least 6.1 m and the quantity W divided by 30 shall not exceed 1.0 where the value of W varies along the perimeter of the building, the calculation performed in accordance with Equation 3-2 shall be based on the weighted average of each portion of exterior wall and open space where the value of W is between 6.1 and 9.1 m. Exception: The quantity W divided by 30 shall be permitted to not exceed 2.0 when all of the following conditions exist: 1. The building is permitted to be unlimited in area by Section 3.7; and 2. The only provision preventing unlimited area is compliance with the 18.3 m public way or yard requirement, as applicable. Open space limits. Such open space shall be either on the same lot or dedicated for public use and shall be accessed from a street or approved fire lane. 2007 3/6 GENERAL BUILDING HEIGHTS AND AREAS 3.6.3 Automatic sprinkler system increase. Where a building is protected throughout with an approved automatic sprinkler system in accordance with Section 7.3.3.1.1, the area limitation in Table 3.3 is permitted to be increased by an additional 200 percent (Is=200 percent) for multistory buildings and an additional 300 percent (Is=300 percent) for single-story buildings. These increases are permitted in addition to the height and story increases in accordance with Section 3.4.2. Exceptions: 1. Buildings with an occupancy in Group H-1, H-2 or H-3. 2. Fire-resistance rating substitution in accordance with Table 4A.1, Note d. 3.6.4 Area determination. The maximum area of a building with more than one story shall be determined by multiplying the allowable area of the first floor (Aa), as determined in Section 3.6.1, by the number of stories as listed below. 1. For two-story buildings, multiply by 2; 2. For three-story or higher buildings, multiply by 3; and 3. No story shall exceed the allowable area per floor (Aa), as determined in Section 3.6.1 for the occupancies on that floor. Exceptions: 1. Unlimited area buildings in accordance with Section 3.7. 2. The maximum area of a building equipped with an automatic sprinkler system in accordance with Section 7.3.3.1.2 shall be determined by multiplying the allowable area per floor (Aa), as determined in Section 3.6.1 by the number of stories. SECTION 3.7 UNLIMITED AREA BUILDINGS 3.7.1 Non-sprinklered, one story. The area of a one-story, Group F-2 or S-2 building shall not be limited when the building is surrounded and adjoined by public ways or yards not less than 18.3 m in width. 3.7.2 Sprinklered, one story. The area of a one-story, Group B, F, M or S building or a one-story Group A-4 building of other than Type V construction shall not be limited when the building is provided with an automatic sprinkler system throughout in accordance with Section 7.3.3.1.1, and is surrounded and adjoined by public ways or yards not less than 18.3 m in width. Exceptions: 1. Buildings and structures of Type I and II construction for rack storage facilities which do not have access by the public shall not be limited in height provided that such buildings conform to the requirements of Section 3.7.1 and NFPA 231C. 2. The automatic sprinkler system shall not be required in areas occupied for indoor participant sports, such as tennis, skating, swimming and equestrian activities, in occupancies in Group A-4, provided that: 2.1 Exit doors directly to the outside are provided for occupants of the participant sports areas, and 2.2 The building is equipped with a fire alarm system with manual fire alarm boxes installed in accordance with Section 7.7. SBC 801 2007 3/7 GENERAL BUILDING HEIGHTS AND AREAS 3.7.3 Two story. The area of a two-story, Group B, F, M or S building shall not be limited when the building is provided with an automatic sprinkler system in accordance with Section 7.3.3.1.1 throughout, and is surrounded and adjoined by public ways or yards not less than 18.3 m in width. 3.7.4 Reduced open space. The permanent open space of 18.3 m required in Sections 3.7.1, 3.7.2 and 3.7.3 shall be permitted to be reduced to not less than 12.2 m provided the following requirements are met: 1. The reduced open space shall not be allowed for more than 75 percent of the perimeter of the building. 2. The exterior wall facing the reduced open space shall have a minimum fireresistance rating of 3 hours. 3. Openings in the exterior wall, facing the reduced open space, shall have opening protectives with a fire-resistance rating of 3 hours. 3.7.5 Group A-3 buildings. The area of a one-story, Group A-3 building used as a prayer hall, community hall, exhibition hall, gymnasium, lecture hall, indoor swimming pool or tennis court of Type I or II construction shall not be limited when all of the following criteria are met: 1. The building shall not have a stage other than a platform. 2. The building shall be equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. 3. The assembly floor shall be located at or within 533 mm of street or grade level and all exits are provided with ramps complying with Section 8.10.1 to the street or grade level. 4. The building shall be surrounded and adjoined by public ways or yards not less than 18.3 m in width. 3.7.6 High-hazard use groups. Group H-2, H-3 and H-4 fire areas shall be permitted in unlimited area buildings having occupancies in Groups F and S, in accordance with the limitations of this section. Fire areas located at the perimeter of the unlimited area building shall not exceed 10 percent of the area of the building nor the area limitations specified in Table 3.3 as modified by Section 3.6.2, based upon the percentage of the perimeter of the fire area that fronts on a street or other unoccupied space. Other fire areas shall not exceed 25 percent of the area limitations specified in Table 3.3. Fire-resistance-rating requirements of fire barrier assemblies shall be in accordance with Table 2A.2.3.3. 3.7.7 Aircraft paint hangar. The area of a one-story, Group H-2 aircraft paint hangar shall not be limited where such aircraft paint hangar complies with the provisions of Section 2B.12.4 and is entirely surrounded by public ways or yards not less in width than one and one-half times the height of the building. 3.7.8 Group E buildings. The area of a one-story Group E building of Type II, IIIA or IV construction shall not be limited when the following criteria are met: 1. Each classroom shall have not less than two means of egress, with one of the means of egress being a direct exit to the outside of the building complying with Section 8.17. 2. The building is equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. SBC 801 2007 3/8 GENERAL BUILDING HEIGHTS AND AREAS 3. The building is surrounded and adjoined by public ways or yards not less than 18.3 m in width. 3.7.9 Motion picture theaters. In buildings of Type I or II construction, the area of one-story motion picture theaters shall not be limited when the building is provided with an automatic sprinkler system throughout in accordance with Section 7.3.3.1.1 and is surrounded and adjoined by public ways or yards not less than 18.3 m in width. SECTION 3.8 SPECIAL PROVISIONS 3.8.1 General. The provisions in this section shall permit the use of special conditions that are exempt from, or modify, the specific requirements of this chapter regarding the allowable heights and areas of buildings based on the occupancy classification and type of construction, provided the special condition complies with the provisions specified in this section for such condition and other applicable requirements of this code. 3.8.2 Group S-2 enclosed parking garage with Group A, B, M or R above. A basement and/or the first story above grade plane of a building shall be considered as a separate and distinct building for the purpose of determining area limitations, continuity of fire walls, limitation of number of stories and type of construction, when all of the following conditions are met: 1. The basement and/or the first story above grade plane is of Type IA construction and is separated from the building above with a horizontal assembly having a minimum 3 hours fire-resistance rating. 2. Shaft, stairway, ramp or escalator enclosures through the horizontal assembly shall have not less than a 2-hour fire-resistance rating with opening protectives in accordance with Table 4B.16.3. Exception: Where the enclosure walls below the horizontal assembly have not less than a 3 hours fire-resistance rating with opening protectives in accordance with Table 4B.16.3 (Fire Door & Fire Shutter Fire Protection Ratings), the enclosure walls extending above the horizontal assembly shall be permitted to have a 1-hour fire-resistance rating provided: 1. The building above the horizontal assembly is not required to be of Type I construction; 2. The enclosure connects less than four stories, and 3. The enclosure opening protectives above the horizontal assembly have a minimum 1-hour fire protection rating. 3. The building above the horizontal assembly contains only Group A having an assembly room with an occupant load of less than 300, or Group B, M or R; and 4. The building below the horizontal assembly is a Group S-2 enclosed parking garage, used for the parking and storage of private motor vehicles. Exceptions: 1. Entry lobbies, mechanical rooms and similar uses incidental to the operation of the building shall be permitted. 2. Group A having an assembly room with an occupant load of less than 300, or Group B or M shall be permitted in addition to those uses incidental to SBC 801 2007 3/9 GENERAL BUILDING HEIGHTS AND AREAS the operation of the building (including storage areas), provided that the entire structure below the horizontal assembly is protected throughout by an approved automatic sprinkler system. 5. The maximum building height in feet shall not exceed the limits set forth in Table 3.3 for the least restrictive type of construction involved. 3.8.3 Group S-2 enclosed parking garage with Group S-2 open parking garage above. A Group S-2 enclosed parking garage located in the basement or first story below a Group S-2 open parking garage shall be classified as a separate and distinct building for the purpose of determining the type of construction when the following conditions are met: 1. The allowable area of the structure shall be such that the sum of the ratios of the actual area divided by the allowable area for each separate occupancy shall not exceed 1.0. 2. The Group S-2 enclosed parking garage is of Type I or II construction and is at least equal to the fire-resistance requirements of the Group S-2 open parking garage. 3. The height and the number of the floors above the basement shall be limited as specified in Table 2B.6.3.5 (Open Parking Garages Area & Height). 4. The floor assembly separating the Group S-2 enclosed parking garage and Group S-2 open parking garage shall be protected as required for the floor assembly of the Group S-2 enclosed parking garage. Openings between the Group S-2 enclosed parking garage and Group S-2 open parking garage, except exit openings, shall not be required to be protected. 5. The Group S-2 enclosed parking garage is used exclusively for the parking or storage of private motor vehicles, but shall be permitted to contain an office, waiting room and toilet room having a total area of not more than 93 m2, and mechanical equipment rooms incidental to the operation of the building. 3.8.4 Parking beneath Group R. Where a maximum one-story above grade plane Group S-2 parking garage, enclosed or open, or combination thereof, of Type I construction or open of Type IV construction, with grade entrance, is provided under a building of Group R, the number of stories to be used in determining the minimum type of construction shall be measured from the floor above such a parking area. The floor assembly between the parking garage and the Group R above shall comply with the type of construction required for the parking garage and shall also provide a fire-resistance rating not less than the mixed occupancy separation required in Section 2A.2.3.3. 3.8.5 Group R-2 buildings of Type IIIA construction. The height limitation for buildings of Type IIIA construction in Group R-2 shall be increased to six stories and 23 m where the first-floor construction above the basement has a fireresistance rating of not less than 3 hours and the floor area is subdivided by 2-hour fire-resistance-rated fire walls into areas of not more than 279 m2. 3.8.6 Group R-2 buildings of Type IIA construction. The height limitation for buildings of Type IIA construction in Group R-2 shall be increased to nine stories and 30.5 m where the building is separated by not less than 15.3 m from any other building on the lot and from property lines, the exits are segregated in an area enclosed by a 2-hour fire-resistance-rated fire wall and the first-floor construction SBC 801 2007 3/10 GENERAL BUILDING HEIGHTS AND AREAS has a fire-resistance rating of not less than 11/2 hours. 3.8.7 3.8.7.1 SBC 801 Open parking garage beneath Groups A, I, B, M and R. Open parking garages constructed under Groups A, I, B, M and R shall not exceed the height and area limitations permitted under Section 2B.6.3. The height and area of the portion of the building above the open parking garage shall not exceed the limitations in Section 3.3 for the upper occupancy. The height, in both feet and stories, of the portion of the building above the open parking garage shall be measured from grade plane and shall include both the open parking garage and the portion of the building above the parking garage. Fire separation. Fire separation assemblies between the parking occupancy and the upper occupancy shall correspond to the required fire-resistance rating prescribed in Table 2A.2.3.3 for the uses involved. The type of construction shall apply to each occupancy individually, except that structural members, including main bracing within the open parking structure, which is necessary to support the upper occupancy, shall be protected with the more restrictive fire-resistance-rated assemblies of the groups involved as shown in Table 4A.1. Means of egress for the upper occupancy shall conform to Chapter 8 and shall be separated from the parking occupancy by fire barriers having at least a 2-hour fire-resistance rating as required by Section 4B.7, with self-closing doors complying with Section 4B.16. Means of egress from the open parking garage shall comply with Section 2B.6.3. 2007 3/11 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION CHAPTER 4 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 4A TYPES OF CONSTRUCTION SECTION 4A.1 GENERAL 4A.1.1 Scope. The provisions of this chapter shall control the classification of buildings as to type of construction. SECTION 4A.2 CONSTRUCTION CLASSIFICATION 4A.2.1 4A.2.1.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 4A.2.2 through 4A.2.5. The building elements shall have a fire-resistance rating not less than that specified in Table 4A.1 and exterior walls shall have a fire-resistance rating not less than that specified in Table 4A.2. Minimum requirements. A building or portion thereof shall not be required to conform to the details of a type of construction higher than that type, which meets the minimum requirements based on occupancy even though certain features of such a building actually conform to a higher type of construction. 4A.2.2 Types I and II. Type I and II construction are those types of construction in which the building elements listed in Table 4A.1 are of noncombustible materials. 4A.2.3 Type III. Type III construction is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of any material permitted by these code requirements. Fire-retardant-treated wood framing shall be permitted within exterior wall assemblies of a 2-hour rating or less. 4A.2.4 Type IV. Type IV construction (Heavy Timber, HT) is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of solid or laminated wood without concealed spaces. The details of Type IV construction shall comply with the provisions of this section. Fireretardant-treated wood framing shall be permitted within exterior wall assemblies with a 2-hour rating or less. Columns. Wood columns shall be sawn or glued laminated and shall not be less than 200 mm, nominal, in any dimension where supporting floor loads and not less than 150 mm nominal in width and not less than 200 mm nominal in depth where supporting roof and ceiling loads only. Columns shall be continuous or superimposed and connected in an approved manner. Floor framing. Wood beams and girders shall be of sawn or glued-laminated timber and shall be not less than 150 mm nominal in width and not less than 250 mm nominal in depth. Framed sawn or glued-laminated timber arches, which spring from the floor line and support floor loads, shall be not less than 200 mm nominal in any dimension. Framed timber trusses supporting floor loads shall have members of not less than 200 mm nominal in any dimension. 4A.2.4.1 4A.2.4.2 SBC 801 2007 4/1 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4A.2.4.3 4A.2.4.4 4A.2.4.5 4A.2.4.6 4A.2.4.7 4A.2.5 Roof framing. Wood-frame or glued-laminated arches for roof construction, which spring from the floor line or from grade and do not support floor loads, shall have members not less than 150 mm nominal in width and have less than 200 mm nominal in depth for the lower half of the height and not less than 150 mm nominal in depth for the upper half. Framed or glued laminated arches for roof construction that spring from the top of walls or wall abutments, framed timber trusses and other roof framing, which do not support floor loads, shall have members not less than 100 mm nominal in width and not less than 150 mm nominal in depth. Spaced members shall be permitted to be composed of two or more pieces not less than 76 mm nominal in thickness where blocked solidly throughout their intervening spaces or where spaces are tightly closed by a continuous wood cover plate of not less than 51 mm nominal in thickness secured to the underside of the members. Splice plates shall be not less than 76 mm nominal in thickness. Where protected by approved automatic sprinklers under the roof deck, framing members shall be not less than 76 mm nominal in width. Floors. Floors shall be without concealed spaces. Wood floors shall be of sawn or glued-laminated planks, splined or tongue-and-groove, of not less than 76 mm nominal in thickness covered with 25 mm nominal dimension tongue-and-groove flooring, laid crosswise or diagonally, or 13 mm particleboard or planks not less than 100 mm nominal in width set on edge close together and well spiked and covered with 25 mm nominal dimension flooring or 12 mm wood structural panel or 13 mm particleboard. The lumber shall be laid so that no continuous line of joints will occur except at points of support. Floors shall not extend closer than 13 mm to walls. Such 13 mm space shall be covered by a molding fastened to the wall and so arranged that it will not obstruct the swelling or shrinkage movements of the floor. Corbeling of masonry walls under the floor shall be permitted to be used in place of molding. Roofs. Roofs shall be without concealed spaces and wood roof decks shall be sawn or glued laminated, splined or tongue-and-groove plank, not less than 51 mm thick, 32 mm wood structural panel (exterior glue), or of planks not less than 76 mm nominal in width, set on edge close together and laid as required for floors. Other types of decking shall be permitted to be used if providing equivalent fire resistance and structural properties. Partitions. Partitions shall be of solid wood construction formed by not less than two layers of 25 mm matched boards or laminated construction 100 mm thick, or of 1-hour fire-resistance-rated construction. Exterior structural members. Where a horizontal separation of 6.1 m or more is provided, wood columns and arches conforming to heavy timber sizes shall be permitted to be used externally. Type V. Type V construction is that type of construction in which the structural elements, exterior walls and interior walls are of any materials permitted by these code requirements. SECTION 4A.3 COMBUSTIBLE MATERIALS IN TYPES I AND II CONSTRUCTION 4A.3.1 SBC 801 Allowable materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 4A.3.1.1 through 4A.3.1.3: 1. Fire-retardant-treated wood shall be permitted in: 2007 4/2 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. SBC 801 1.1. Nonbearing partitions where the required fire-resistance rating is 2 hours or less. 1.2. Nonbearing exterior walls where no fire rating is required. 1.3. Roof construction as permitted in Table 4A.1, Note c, Item 3. Thermal and acoustical insulation, other than foam plastics, having a flame spread index of not more than 25. Exceptions: 1. Insulation placed between two layers of noncombustible materials without an intervening airspace shall be allowed to have a flame spread index of not more than 100. 2. Insulation installed between a finished floor and solid decking without intervening airspace shall be allowed to have a flame spread index of not more than 200. Foam plastics in accordance with Chapter 11 of the SBC 201. Roof coverings that have an A, B or C classification. Interior floor finish and interior finish, trim and millwork such as doors, door frames, window sashes and frames. Where not installed over 4.6 m above grade, show windows, nailing or furring strips, wooden bulkheads below show windows, their frames, aprons and show cases. Finished flooring applied directly to the floor slab or to wood sleepers that are firestopped in accordance with Section 4B.17.2.7. Partitions dividing portions of stores, offices or similar places occupied by one tenant only and which do not establish a corridor serving an occupant load of 30 or more shall be permitted to be constructed of fire-retardanttreated wood, 1-hour fire-resistance-rated construction or of wood panels or similar light construction up to 1.83 m in height. Platforms as permitted in Section 2B.10. Combustible exterior wall coverings, balconies, bay or oriel windows, or similar appendages in accordance with Chapter 5 of the SBC 201. Blocking such as for handrails, millwork, cabinets, and window and door frames. Light-transmitting plastics as permitted by Chapter 11 of the SBC 201. Mastics and caulking materials applied to provide flexible seals between components of exterior wall construction. Exterior plastic veneer installed in accordance with Section 11.5.2 of the SBC 201. Nailing or furring strips as permitted by Section 6.3.3. Heavy timber as permitted by Note c, Item 2, to Table 4A.1 and Sections 4A.2.4.7 and 5.6.3 of the SBC 201. Aggregates, component materials and admixtures as permitted by Section 4B.3.2.2. Sprayed cementitious and mineral fiber fire-resistance-rated materials installed to comply with SBC 302. Materials used to protect penetrations in fire-resistance-rated assemblies in accordance with Section 4B.12. Materials used to protect joints in fire-resistance-rated assemblies in accordance with Section 4B.13. Materials allowed in the concealed spaces of buildings of Type I and II construction in accordance with Section 4B.17.5. Materials exposed within plenums complying with SBC 501. 2007 4/3 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4A.3.1.1 4A.3.1.2 4A.3.1.3 Ducts. The use of nonmetallic ducts shall be permitted when installed in accordance with the limitations of the SBC 501. Piping. The use of combustible piping materials shall be permitted when installed in accordance with the limitations of the SBC 501 and the SBC 501. Electrical. The use of electrical wiring methods with combustible insulation, tubing, raceways and related components shall be permitted when installed in accordance with the limitations of the SBC 501. TABLE 4A.1 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (hours) BUILDING ELEMENT Structural framea Including columns, girders, trusses Bearing walls Exteriorf Interior Nonbearing walls and partitions Exterior Nonbearing walls and partitions Interiore TYPE I A B TYPE II Ad B TYPE III Ad B 3b 2b 1 0 1 0 HT 1 0 3 3b 2 2b 1 1 0 0 2 1 2 0 2 1/HT 1 1 0 0 See Section 4A.2.4.6 0 0 TYPE IV HT TYPE V Ad B See Table 4A.2 0 0 0 0 0 0 Floor construction Including supporting beams and 2 2 1 0 1 0 HT 1 0 joists Roof construction Including supporting beams and 0 1c 0 HT 1c 0 11/2c 1c 1c joists a. The structural frame shall be considered to be the columns and the girders, beams, trusses and spandrels having direct connections to the columns and bracing members designed to carry gravity loads. The members of floor or roof panels which have no connection to the columns shall be considered secondary members and not a part of the structural frame. b. Roof supports: Fire-resistance ratings of structural frame and bearing walls are permitted to be reduced by 1 hour where supporting a roof only. c. 1. Except in Factory-Industrial (F-1), Hazardous (H), Mercantile (M) and Moderate-Hazard Storage (S1) occupancies, fire protection of structural members shall not be required, including protection of roof framing and decking where every part of the roof construction is 6.1 m or more above any floor immediately below. Fire-retardant-treated wood members shall be allowed to be used for such unprotected members. 2. In all occupancies, heavy timber shall be allowed where a 1-hour or less fire-resistance rating is required. 3. In Type I and II construction, fire-retardant-treated wood shall be allowed in buildings including girders and trusses as part of the roof construction when the building is: i. Two stories or less in height; ii. Type II construction over two stories; or iii. Type I construction over two stories and the vertical distance from the upper floor to the roof is 6.1 m or more. d. An approved automatic sprinkler system in accordance with Section 7.3.3.1.1 shall be allowed to be substituted for 1-hour fire-resistance-rated construction, provided such system is not otherwise required by other provisions of the code or used for an allowable area increase in accordance with Section 3.6.3 or an allowable height increase in accordance with Section 3.4.2. The 1-hour substitution for the fire resistance of exterior walls shall not be permitted. e. Not less than the fire-resistance rating required by other sections of these code requirements. f. Not less than the fire-resistance rating based on fire separation distance (see Table 4A.2). SBC 801 2007 4/4 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4A.2 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCEa FIRE SEPARATION DISTANCE (meters) TYPE OF CONSTRUCTION GROUP H GROUP F-1, M, S-1 GROUP A, B, E, F-2, I, Rb, S-2, U < 1.5c All 3 2 1 � 1.5 IA 3 2 1 < 3.1 Others 2 1 1 � 3.1 IA, IB 2 1 1 < 9.1 IIB, VB 1 0 0 Others 1 1 1 All 0 0 0 � 9.1 a. b. c. Load-bearing exterior walls shall also comply with the fire-resistance rating requirements of Table 4A.1. Group R-3 and Group U when used as accessory to Group R-3, as applicable in SBC 100 shall not be required to have a fire-resistance rating where the fire separation distance is 0.9 m or more. See Section 3.3.2 for party walls. SECTION 4B FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 4B.1 GENERAL 4B.1.1 Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated construction separation of adjacent spaces to safeguard against the spread of fire and smoke within a building and the spread of fire to or from buildings. SECTION 4B.2 DEFINITIONS 4B.2.1 Definitions. The following words and terms shall, for the purposes of this chapter, and as used elsewhere in these code requirements, have the meanings shown herein. ANNULAR SPACE. The opening around the penetrating item. CEILING RADIATION DAMPER. A listed device installed in a ceiling membrane of a fire-resistance-rated floor/ceiling or roof/ceiling assembly to limit automatically the radiative heat transfer through an air inlet/outlet opening. COMBINATION FIRE/SMOKE DAMPER. A listed device installed in ducts and air transfer openings designed to close automatically upon the detection of heat and to also resist the passage of air and smoke. The device is installed to operate automatically, controlled by a smoke detection system, and where required, is capable of being positioned from a remote command station. DAMPER. See “Ceiling radiation damper,” “Combination fire/smoke damper,” “Fire damper” and “Smoke damper.” SBC 801 2007 4/5 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION DRAFT STOP. A material, device or construction installed to restrict the movement of air within open spaces of concealed areas of building components such as crawl spaces, floor/ceiling assemblies, roof/ceiling assemblies and attics. F RATING. The time period that the through-penetration firestop system limits the spread of fire through the penetration when tested in accordance with ASTM E 814. FIRE AREA. The aggregate floor area enclosed and bounded by firewalls, fire barriers, exterior walls or fire-resistance-rated horizontal assemblies of a building. FIRE BARRIER. A fire-resistance-rated vertical or horizontal assembly of materials designed to restrict the spread of fire in which openings are protected. FIRE DAMPER. A listed device, installed in ducts and air transfer openings of an air distribution system or smoke control systems, designed to close automatically upon detection of heat, to interrupt migratory airflow, and to restrict the passage of flame. Fire dampers are classified for use in either static systems that will automatically shutdown in the event of a fire, or in a dynamic system that continues to operate during a fire. A dynamic fire damper is tested and rated for closure under airflow. FIRE DOOR. The door component of a fire door assembly. FIRE DOOR ASSEMBLY. Any combination of a fire door, frame, hardware, and other accessories that together provide a specific degree of fire protection to the opening. FIRE PARTITION. A vertical assembly of materials designed to restrict the spread of fire in which openings are protected. FIRE PROTECTION RATING. The period of time that an opening protective assembly will maintain the ability to confine a fire as determined by tests prescribed in Section 4B.15. Ratings are stated in hours or minutes. FIRE RESISTANCE. That property of materials or their assemblies that prevents or retards the passage of excessive heat, hot gases or flames under conditions of use. FIRE-RESISTANCE RATING. The period of time a building element, component or assembly maintains the ability to confine a fire, continues to perform a given structural function, or both, as determined by the tests, or the methods based on tests, prescribed in Section 4B.3. FIRE-RESISTANT JOINT SYSTEM. An assemblage of specific materials or products that are designed, tested, and fire-resistance rated in accordance with either ASTM E 1966 or UL 2079 to resist for a prescribed period of time the passage of fire through joints made in or between fire-resistance-rated assemblies. FIRE SEPARATION DISTANCE. The distance measured from the building face to the closest interior lot line, to the centerline of a street, alley or public way, SBC 801 2007 4/6 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION or to an imaginary line between two buildings on the lot. The distance shall be measured at right angles from the face of the wall. FIRE WALL. A fire-resistance-rated wall having protected openings, which restricts the spread of fire and extends continuously from the foundation to or through the roof, with sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall. FIRE WINDOW ASSEMBLY. A window constructed and glazed to give protection against the passage of fire. FIREBLOCKING. Building materials installed to resist the free passage of flame to other areas of the building through concealed spaces. FLOOR FIRE DOOR ASSEMBLY. A combination of a fire door, a frame, hardware and other accessories installed in a horizontal plane, which together provide a specific degree of fire protection to a through opening in a fireresistance-rated floor (see Section 4B.12.4.6). JOINT. The linear opening in or between adjacent fire-resistance-rated assemblies that is designed to allow independent movement of the building in any plane caused by thermal, seismic, wind or any other loading. MEMBRANE PENETRATION. An opening made through one side (wall, floor or ceiling membrane) of an assembly. MEMBRANE-PENETRATION FIRESTOP. A material, device or construction installed to resist for a prescribed time period the passage of flame and heat through openings in a protective membrane in order to accommodate cables, cable trays, conduit, tubing, pipes or similar items. PENETRATION FIRESTOP. A through-penetration fire stop or a membranepenetration fire stop. SELF-CLOSING. As applied to a fire door or other opening, means equipped with an approved device that will ensure closing after having been opened. SHAFT. An enclosed space extending through one or more stories of a building, connecting vertical openings in successive floors, or floors and roof. SHAFT ENCLOSURE. The walls or construction forming the boundaries of a shaft. SMOKE BARRIER. A continuous membrane, either vertical or horizontal, such as a wall, floor, or ceiling assembly, that is designed and constructed to restrict the movement of smoke. SMOKE COMPARTMENT. A space within a building enclosed by smoke barriers on all sides, including the top and bottom. SMOKE DAMPER. A listed device installed in ducts and air transfer openings that is designed to resist the passage of air and smoke. The device is installed to SBC 801 2007 4/7 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION operate automatically, controlled by a smoke detection system, and where required, is capable of being positioned from a remote command station. SPLICE. The result of a factory and/or field method of joining or connecting two or more lengths of a fire-resistant joint system into a continuous entity. T RATING. The time period that the penetration fire stop system, including the penetrating item, limits the maximum temperature rise to 163°C above its initial temperature through the penetration on the non-fire side when tested in accordance with ASTM E 814. THROUGH PENETRATION. An opening that passes through an entire assembly. THROUGH-PENETRATION FIRE STOP SYSTEM. An assemblage of specific materials or products that are designed, tested and fire-resistance rated to resist for a prescribed period of time the spread of fire through penetrations. The F and T rating criteria for penetration fire stop systems shall be in accordance with ASTM E 814. See definitions of “F rating” and “T rating.” SECTION 4B.3 FIRE-RESISTANCE RATINGS AND FIRE TESTS 4B.3.1 Scope. Materials prescribed herein for fire resistance shall conform to the requirements of this chapter. 4B.3.2 Fire-resistance ratings. The fire-resistance rating of building elements shall be determined in accordance with the test procedures set forth in ASTM E 119 or in accordance with Section 4B.3.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire-resistance-rated building elements shall not reduce the required fire-resistance rating. Exception: In determining the fire-resistance rating of exterior bearing walls, compliance with the ASTM E 119 criteria for unexposed surface temperature rise and ignition of cotton waste due to passage of flame or gases is required only for a period of time corresponding to the required fire-resistance rating of an exterior nonbearing wall with the same fire separation distance, and in a building of the same group. When the fire-resistance rating determined in accordance with this exception exceeds the fire-resistance rating determined in accordance with ASTM E 119, the fire exposure time period, water pressure, and application duration criteria for the hose stream test of ASTM E 119 shall be based upon the fireresistance rating determined in accordance with this exception. Nonsymmetrical wall construction. Interior walls and partitions of nonsymmetrical construction shall be tested with both faces exposed to the furnace, and the assigned fire-resistance rating shall be the shortest duration obtained from the two tests conducted in compliance with ASTM E 119. When evidence is furnished to show that the wall was tested with the least fire-resistant side exposed to the furnace, subject to acceptance of the building official, the wall need not be subjected to tests from the opposite side (see Section 4B.4.5 for exterior walls). 4B.3.2.1 SBC 801 2007 4/8 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.3.2.2 4B.3.2.3 Combustible components. Combustible aggregates are permitted in gypsum and Portland cement concrete mixtures approved for fire-resistance-rated construction. Any approved component material or admixture is permitted in assemblies if the resulting tested assembly meets the fire-resistance test requirements of these code requirements. Restrained classification. Fire-resistance-rated assemblies tested under ASTM E 119 shall not be considered to be restrained unless evidence satisfactory to the building official is furnished by the registered design professional showing that the construction qualifies for a restrained classification in accordance with ASTM E 119. Restrained construction shall be identified on the plans. 4B.3.3 Alternative methods for determining fire resistance. The application of any of the alternative methods listed in this section shall be based on the fire exposure and acceptance criteria specified in ASTM E 119. The required fire resistance of a building element shall be permitted to be established by any of the following methods or procedures: 1. Fire-resistance designs documented in approved sources. 2. Prescriptive designs of fire-resistance-rated building elements as prescribed in Section 4B.20. 3. Calculations in accordance with Section 4B.21. 4. Engineering analysis based on a comparison of building element designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E 119. 5. Alternative protection methods as allowed by a building official. 4B.3.4 Noncombustibility tests. The tests indicated in Sections 4B.3.4.1 and 4B.3.4.2 shall serve as criteria for acceptance of building materials as set forth in Sections 4A.2.2, 4A.2.3 and 4A.2.4 in Type I, II, III and IV construction. The term “noncombustible” does not apply to the flame spread characteristics of interior finish or trim materials. A material shall not be classified as a noncombustible building construction material if it is subject to an increase in combustibility or flame spread beyond the limitations herein established through the effects of age, moisture or other atmospheric conditions. Elementary materials. Materials required to be noncombustible shall be tested in accordance with ASTM E 136. Composite materials. Materials having a structural base of noncombustible material as determined in accordance with Section 4B.3.4.1 with a surfacing not more than 3 mm thick that has a flame spread index not greater than 50 when tested in accordance with ASTM E 84 shall be acceptable as noncombustible materials. 4B.3.4.1 4B.3.4.2 SECTION 4B.4 EXTERIOR WALLS 4B.4.1 General. Exterior walls shall be fire-resistance rated and have opening protection as required by this section. 4B.4.2 Projections. Cornices, eave overhangs, exterior balconies and similar architectural appendages extending beyond the floor area shall conform to the requirements of this section and Section 5.6 of the SBC 201. Exterior egress balconies and exterior exit stairways shall also comply with Sections 8.13.5 and 8.22.1. Projections shall not extend beyond the distance determined by the following two methods, whichever results in the lesser projection: SBC 801 2007 4/9 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.4.2.1 4B.4.2.2 4B.4.2.3 1. A point one-third the distance to the lot line from an assumed vertical plane located where protected openings are required in accordance with Section 4B.4.8. 2. More than 300 mm into areas where openings are prohibited. Type I and II construction. Projections from walls of Type I or II construction shall be of noncombustible materials or combustible materials as allowed by Sections 5.6.3 and 5.6.4 of the SBC 201. Type III, IV or V construction. Projections from walls of Type III, IV or V construction shall be of any approved material. Combustible projections. Combustible projections located where openings are not permitted or where protection of openings is required shall be of at least 1-hour fire-resistance-rated construction, Type IV construction or as required by Section 5.6.3 of the SBC 201. Exception: Type V construction shall be allowed for R-3 occupancies, as applicable in SBC 201. 4B.4.3 Buildings on the same lot. For the purposes of determining the required wall and opening protection and roof-covering requirements, buildings on the same lot shall be assumed to have an imaginary line between them. Where a new building is to be erected on the same lot as an existing building, the location of the assumed imaginary line with relation to the existing building shall be such that the exterior wall and opening protection of the existing building meet the criteria as set forth in Sections 4B.4.5 and 4B.4.8. Exception: Two or more buildings on the same lot shall either be regulated as separate buildings or shall be considered as portions of one building if the aggregate area of such buildings is within the limits specified in Chapter 3 for a single building. Where the buildings contain different occupancy groups or are of different types of construction, the area shall be that allowed for the most restrictive occupancy or construction. 4B.4.4 Materials. Exterior walls shall be of materials permitted by the building type of construction. 4B.4.5 Fire-resistance ratings. Exterior walls shall be fire-resistance rated in accordance with Tables 4A.1 and 4A.2. The fire-resistance rating of exterior walls with a fire separation distance of greater than 1.52 m shall be rated for exposure to fire from the inside. The fire-resistance rating of exterior walls with a fire separation distance of 1.52 m or less shall be rated for exposure to fire from both sides. 4B.4.6 Structural stability. The wall shall extend to the height required by Section 4B.4.11 and shall have sufficient structural stability such that it will remain in place for the duration of time indicated by the required fire-resistance rating. 4B.4.7 Unexposed surface temperature. Where protected openings are not limited by Section 4B.4.8, the limitation on the rise of temperature on the unexposed surface of exterior walls as required by ASTM E 119 shall not apply. Where protected openings are limited by Section 4B.4.8, the limitation on the rise of temperature on the unexposed surface of exterior walls as required by ASTM E 119 shall not apply provided that a correction is made for radiation from the unexposed exterior wall surface in accordance with the following formula: (Equation 4B.-1) Ae = A+ (Af � Feo) SBC 801 2007 4/10 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Where: Ae = Equivalent area of protected openings. = Actual area of protected openings. A Af = Area of exterior wall surface in the story under consideration exclusive of openings, on which the temperature limitations of ASTM E 119 for walls are exceeded. Feo = An “equivalent opening factor” derived from Figure 4B.4.7 based on the average temperature of the unexposed wall surface and the fireresistance rating of the wall. FIGURE 4B.4.7 EQUIVALENT OPENING FACTOR 4B.4.8 Allowable area of openings. The maximum area of unprotected or protected openings permitted in an exterior wall in any story shall not exceed the values set forth in Table 4B.4.8. Where both unprotected and protected openings are located in the exterior wall in any story, the total area of the openings shall comply with the following formula: A a � Au au (Equation 4B.-2) � 1.0 Where: = Actual area of protected openings, or the equivalent area of protected A openings, Ae (see Section 4B.4.7). = Allowable area of protected openings. a Au = Actual area of unprotected openings. au = Allowable area of unprotected openings. SBC 801 2007 4/11 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.4.8 MAXIMUM AREA OF EXTERIOR WALL OPENINGSa CLASSIFICATION OF OPENING Unprotected Protected a. b. c. d. e. f. g. h. 0 to 1e,h Not Permittedg Not Permitted Greater than 1 to 1.5b Not Permittedb,g 15% FIRE SEPARATION DISTANCE (meters) Greater Greater Greater Greater than than than than d,f c,d,f c,f 1.5 to 3 3 to 4.5 4.5 to 6 6 to 7.5c,f Greater than 7.5 to 9c,f 10%g 15%g 25%g 45%g 70%g 25% 45% 75% No Limit No Limit Greater than 9 No Limit No Limit Values given are percentage of the area of the exterior wall. For occupancies in Group R-3, as applicable in SBC 201, the maximum percentage of unprotected and protected exterior wall openings shall be 25 percent. The area of openings in an open parking structure with a fire separation distance of greater than 3 m shall not be limited. For occupancies in Group H-2 or H-3, unprotected openings shall not be permitted for openings with a fire separation distance of 4.5m or less. For requirements for fire walls for buildings with differing roof heights, see Section 4B.5.6.1. The area of unprotected and protected openings is not limited for occupancies in Group R-3, as applicable in SBC 201, with a fire separation distance greater than 1.5m. Buildings whose exterior bearing wall, exterior nonbearing wall and exterior structural frame are not required to be fire-resistance-rated shall be permitted to have unlimited unprotected openings. Includes accessory buildings to Group R-3 as applicable in SBC 201. 4B.4.8.1 4B.4.8.2 Automatic sprinkler system. In buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1, the maximum allowable area of unprotected openings in occupancies other than Groups H-1, H-2 and H-3 shall be the same as the tabulated limitations for protected openings. First story. In occupancies other than Group H, unlimited unprotected openings are permitted in the first story of exterior walls facing a street that have a fire separation distance of greater than 4.5 m, or facing an unoccupied space. The unoccupied space shall be on the same lot or dedicated for public use, shall not be less than 9 m in width, and shall have access from a street by a posted fire lane in accordance with these code requirements. 4B.4.9 Vertical separation of openings. Openings in exterior walls in adjacent stories shall be separated vertically to protect against fire spread on the exterior of the buildings where the openings are within 1.5 m of each other horizontally and the opening in the lower story is not a protected opening in accordance with Section 4B.15.4.8. Such openings shall be separated vertically at least 1 m by spandrel girders, exterior walls or other similar assemblies that have a fire-resistance rating of at least 1 hour or by flame barriers that extend horizontally at least 0.75 m beyond the exterior wall. Flame barriers shall also have a fire-resistance rating of at least 1 hour. The unexposed surface temperature limitations specified in ASTM E 119 shall not apply to the flame barriers or vertical separation unless otherwise required by the provisions of these code requirements. Exceptions: 1. This section shall not apply to buildings that are three stories or less in height. 2. This section shall not apply to buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. 3. Open parking garages. 4B.4.10 Vertical exposure. For buildings on the same lot, approved protectives shall be provided in every opening that is less than 4.5 m vertically above the roof of an adjoining building or adjacent structure that is within a horizontal fire separation distance of 4.5 m of the wall in which the opening is located. SBC 801 2007 4/12 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Exception: Opening protectives are not required where the roof construction has a fire-resistance rating of not less than 1 hour for a minimum distance of 3 m from the adjoining building and the entire length and span of the supporting elements for the fire-resistance-rated roof assembly has a fire-resistance rating of not less than 1 hour. 4B.4.11 4B.4.11.1 SBC 801 Parapets. Parapets shall be provided on exterior walls of buildings. Exceptions: A parapet need not be provided on an exterior wall where any of the following conditions exist: 1. The wall is not required to be fire-resistance rated in accordance with Table 4A.2 because of fire separation distance. 2. The building has an area of not more than 93 m2 on any floor. 3. Walls that terminate at roofs of not less than 2-hour fire-resistance-rated construction or where the roof, including the deck and supporting construction, is constructed entirely of noncombustible materials. 4. One-hour fire-resistance-rated exterior walls that terminate at the underside of the roof sheathing, deck or slab, provided: 4.1 Where the roof/ceiling framing elements are parallel to the walls, such framing and elements supporting such framing shall not be of less than 1hour fire-resistance-rated construction for a width of 1.2 m measured from the interior side of the wall for Groups R and U and 3 m for other occupancies. 4.2 Where roof/ceiling framing elements are not parallel to the wall, the entire span of such framing and elements supporting such framing shall not be of less than 1-hour fire-resistance-rated construction. 4.3 Openings in the roof shall not be located within 1.5 m of the 1-hour fireresistance-rated exterior wall for Groups R and U and 3 m for other occupancies. 4.4 The entire building shall be provided with not less than a Class B roof covering. 5. In occupancies of Groups R-2 and R-3 as applicable in SBC 201, both provided with a Class C roof covering, the exterior wall shall be permitted to terminate at the roof sheathing or deck in Type III, IV and V construction provided: 5.1 The roof sheathing or deck is constructed of approved noncombustible materials or of fire-retardant-treated wood, for a distance of 1.2 m; or 5.2 The roof is protected with 16 mm Type X gypsum board directly beneath the underside of the roof sheathing or deck, supported by a minimum of nominal 50 mm ledgers attached to the sides of the roof framing members, for a minimum distance of 1.2 m. 6. Where the wall is permitted to have at least 25 percent of the exterior wall areas containing unprotected openings based on fire separation distance as determined in accordance with Section 4B.4.8. Parapet construction. Parapets shall have the same fire-resistance rating as that required for the supporting wall, and on any side adjacent to a roof surface, shall have noncombustible faces for the uppermost 500 mm, including counter flashing and coping materials. The height of the parapet shall not be less than 0.75 m above the point where the roof surface and the wall intersect. Where the roof slopes toward a parapet at a slope greater than two units vertical in 12 units horizontal (16.7-percent slope), the parapet shall extend to the same height as any portion of the roof within a fire separation distance where protection of wall openings is required, but in no case shall the height be less than 750 mm. 2007 4/13 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.4.12 4B.4.12.1 4B.4.13 4B.4.13.1 4B.4.14 Opening protection. Windows required to be protected in accordance with Sections 4B.4.8, 4B.4.9, or 4B.4.10 shall comply with Section 4B.15.4.8. Other openings required to be protected with fire doors or shutters in accordance with Sections 4B.4.8, 4B.4.9 and 4B.4.10 shall comply with Section 4B.15.3. Exception: Fire protective assemblies are not required where the building is protected throughout by an automatic sprinkler system and the exterior openings are protected by an approved water curtain using automatic sprinklers approved for that use. The sprinklers and the water curtain shall be installed in accordance with NFPA 13. Unprotected openings. Where protected openings are not required by Section 4B.4, windows and doors shall be constructed of any approved materials. Glazing shall conform to the requirements of Chapter 11 of the SBC 201. Joints. Joints made in or between exterior walls required by this section to have a fire-resistance rating shall comply with Section 4B.13. Exception: Joints in exterior walls that are permitted to have unprotected openings. Voids. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 4B.13.4. Ducts and air transfer openings. Penetrations by air ducts and air transfer openings in fire-resistance-rated exterior walls required to have protected openings shall comply with Section 4B.16. Exception: Foundation vents installed in accordance with these code requirements are permitted. SECTION 4B.5 FIRE WALLS 4B.5.1 General. Each portion of a building separated by one or more fire walls that comply with the provisions of this section shall be considered a separate building. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates groups that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Fire walls located on lot lines shall also comply with Section 3.3.2. Such fire walls (party walls) shall be constructed without openings. 4B.5.2 Structural stability. Fire walls shall have sufficient structural stability under fire conditions to allow collapse of construction on either side without collapse of the wall for the duration of time indicated by the required fire-resistance rating. 4B.5.3 Materials. Fire walls shall be of any approved noncombustible materials. Exception: Buildings of Type V construction. 4B.5.4 Fire-resistance rating. Fire walls shall have a fire-resistance rating of not less than that required by Table 4B.5.4. SBC 801 2007 4/14 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.5.4 FIRE WALL FIRE-RESISTANCE RATINGS FIRE-RESISTANCE RATING (hours) 3a 3 4b 2 GROUP A, B, E, H-4, I, R-1, R-2, U F-1, H-3b, H-5, M, S-1 H-1, H-2 F-2, S-2, R-3, R-4 a. b. 4B.5.5 4B.5.5.1 4B.5.5.2 SBC 801 Walls shall be not less than 2-hour fire-resistance rated where separating buildings of Type II or V construction. For Group H-1, H-2 or H-3 buildings, also see Sections 2B.15.4 and 2B.15.5. Horizontal continuity. Fire walls shall be continuous from exterior wall to exterior wall and shall extend at least 500 mm beyond the exterior surface of exterior walls. Exceptions: 1. Fire walls shall be permitted to terminate at the interior surface of combustible exterior sheathing or siding provided the exterior wall has a fire-resistance rating of at least 1 hour for a horizontal distance of at least 1.2 m on both sides of the fire wall. Openings within such exterior walls shall be protected by fire assemblies having a fire protection rating of not less than 3/4 hour. 2. Fire walls shall be permitted to terminate at the interior surface of noncombustible exterior sheathing, exterior siding or other noncombustible exterior finishes provided the sheathing, siding, or other exterior noncombustible finish extends a horizontal distance of at least 1.2 m on both sides of the fire wall. 3. Fire walls shall be permitted to terminate at the interior surface of noncombustible exterior sheathing where the building on each side of the fire wall is protected by an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. Exterior walls. Where the fire wall intersects the exterior walls, the fire-resistance rating for the exterior walls on both sides of the fire wall shall have a 1-hour fireresistance rating with 3/4-hour opening protection where opening protection is required. The fire-resistance rating of the exterior wall shall extend a minimum of 1.2 m on each side of the intersection of the fire wall to exterior wall. Exterior wall intersections at fire walls that form an angle equal to or greater than 180 degrees (3.14 rad) do not need exterior wall protection. Horizontal projecting elements. Fire walls shall extend to the outer edge of horizontal projecting elements such as balconies, roof overhangs, canopies, marquees and architectural projections that are within 1.2 m of the fire wall. Exceptions: 1. Horizontal projecting elements without concealed spaces provided the exterior wall behind and below the projecting element has not less than 1-hour fireresistance-rated construction for a distance not less than the depth of the projecting element on both sides of the firewall. Openings within such exterior walls shall be protected by fire assemblies having a fire protection rating of not less than 3/4 hour. 2. Noncombustible horizontal projecting elements with concealed spaces, provided a minimum 1-hour fire-resistance-rated wall extends through the concealed space. The projecting element shall be separated from the building by a minimum of 1-hour fire-resistance-rated construction for a distance on each side of the firewall equal to the depth of the projecting element. The wall 2007 4/15 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION is not required to extend under the projecting element where the building exterior wall is not less than 1-hour fire-resistance-rated for a distance on each side of the firewall equal to the depth of the projecting element. Openings within such exterior walls shall be protected by fire assemblies having a fire protection rating of not less than 3/4 hour. 3. For combustible horizontal projecting elements with concealed spaces, the fire wall need only extend through the concealed space to the outer edges of the projecting elements. The exterior wall behind and below the projecting element shall be of not less than 1-hour fire-resistance-rated construction for a distance not less than the depth of the projecting elements on both sides of the fire wall. Openings within such exterior walls shall be protected by fire assemblies having a fire-protection rating of not less than 3/4 hour. 4B.5.6 4B.5.6.1 SBC 801 Vertical continuity. Fire walls shall extend from the foundation to a termination point at least 750 mm above both adjacent roofs. Exceptions: 1. Stepped buildings in accordance with Section 4B.5.6.1. 2. Two-hour walls shall be permitted to terminate at the underside of the roof sheathing, deck or slab provided: 2.1 The lower roof assembly within 1.2 m of the wall has not less than a 1hour fire-resistance rating and the entire length and span of supporting elements for the rated roof assembly has a fire-resistance rating of not less than 1 hour. 2.2 Openings in the roof shall not be located within 1.2 m of the fire wall. 2.3 Each building shall be provided with not less than a Class B roof covering. 3. Walls shall be permitted to terminate at the underside of noncombustible roof sheathing, deck, or slabs where both buildings are provided with not less than a Class B roof covering. Openings in the roof shall not be located within 1.2 m of the fire wall. 4. In buildings of Type III, IV and V construction, walls shall be permitted to terminate at the underside of combustible roof sheathing or decks provided: 4.1 There are no openings in the roof within 1.2 m of the fire wall, 4.2 The roof is covered with a minimum Class B roof covering, and 4.3 The roof sheathing or deck is constructed of fire-retardant-treated wood for a distance of 1.2 m on both sides of the wall or the roof is protected with 16 mm Type X gypsum board directly beneath the underside of the roof sheathing or deck, supported by a minimum of 50 mm ledgers attached to the sides of the roof framing members for a minimum distance of 1.2 m on both sides of the fire wall. 5. Buildings located above a parking garage designed in accordance with Section 3.8.2 shall be permitted to have the fire walls for the buildings located above the parking garage extend from the horizontal separation between the parking garage and the buildings. Stepped buildings. Where a fire wall serves as an exterior wall for a building and separates buildings having different roof levels, such wall shall terminate at a point not less than 750 m above the lower roof level, provided the exterior wall for a height of 4.5 m above the lower roof is not less than 1-hour fire-resistance- rated construction from both sides with openings protected by assemblies having a 3/4hour fire protection rating. Exception: Where the fire wall terminates at the underside of the roof sheathing, deck or slab of the lower roof, provided: 2007 4/16 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 1. The lower roof assembly within 3 m of the wall has not less than a 1-hour fireresistance rating and the entire length and span of supporting elements for the rated roof assembly has a fire-resistance rating of not less than 1 hour. 2. Openings in the lower roof shall not be located within 3 m of the fire wall. 4B.5.7 Combustible framing in fire walls. Adjacent combustible members entering into a concrete or masonry firewall from opposite sides shall not have less than a 100 mm distance between embedded ends. Where combustible members frame into hollow walls or walls of hollow units, hollow spaces shall be solidly filled for the full thickness of the wall and for a distance not less than 100 mm above, below and between the structural members, with noncombustible materials approved for fire blocking. 4B.5.8 Openings. Each opening through a firewall shall be protected in accordance with Section 4B.15.3 and shall not exceed 11 m2. The aggregate width of openings at any floor level shall not exceed 25 percent of the length of the wall. Exceptions: 1. Openings are not permitted in party walls constructed in accordance with Section 3.3.2. 2. Openings shall not be limited to 11 m2 where both buildings are equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1. 4B.5.9 Penetrations. Penetrations through firewalls shall comply with Section 4B.12. 4B.5.10 Joints. Joints made in or between fire walls shall comply with Section 4B.13. 4B.5.11 Ducts and air transfer openings. Ducts and air transfer openings shall not penetrate fire walls. Exception: Penetrations by ducts and air transfer openings of fire walls that are not on a lot line shall be allowed provided the penetrations comply with Sections 4B.12 and 4B.16. The size and aggregate width of all openings shall not exceed the limitations of Section 4B.5.8. SECTION 4B.6 FIRE BARRIERS 4B.6.1 General. Fire barriers used for separation of shafts, exits, exit passageways, horizontal exits or incidental use areas, to separate different occupancies, to separate a single occupancy into different fire areas, or to separate other areas where a fire barrier is required elsewhere in these code requirements or the SBC 201, shall comply with this section. 4B.6.2 Materials. The walls and floor assemblies shall be of materials permitted by the building type of construction. 4B.6.3 Fire-resistance rating. The fire-resistance rating of the walls and floor assemblies shall comply with this section. Shaft enclosures. The fire-resistance rating of the fire barrier separating building areas from a shaft shall comply with Section 4B.7.4. Exit enclosures. The fire-resistance rating of the fire barrier separating building areas from an exit shall comply with Section 8.19.1. 4B.6.3.1 4B.6.3.2 SBC 801 2007 4/17 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.6.3.3 4B.6.3.4 4B.6.3.5 4B.6.3.6 4B.6.3.7 Exit passageway. The fire-resistance rating of the separation between building areas and an exit passageway shall comply with Section 8.20.1. Horizontal exit. The fire-resistance rating of the separation between building areas connected by a horizontal exit shall comply with Section 8.21.1. Incidental use areas. The fire barrier separating incidental use areas shall have a fire-resistance rating of not less than that indicated in Table 2A.2.1.1. Separation of mixed occupancies. Where the provisions of Section 2A.2.3.2 are applicable, the fire barrier separating mixed occupancies shall have a fireresistance rating of not less than that indicated in Section 2A.2.3.2 based on the occupancies being separated. Single-occupancy fire areas. The fire barrier separating a single occupancy into different fire areas shall have a fire-resistance rating of not less than that indicated in Table 4B.6.3.7. TABLE 4B.6.3.7 FIRE-RESISTANCE RATING REQUIREMENTS FOR FIRE BARRIER ASSEMBLIES BETWEEN FIRE AREAS OCCUPANCY GROUP H-1, H-2 FIRE-RESISTANCE RATING (hours) 4 F-1, H-3, S-1 3 A, B, E, F-2, H-4, H-5, I, M, R, S-2 2 U 1 4B.6.4 Continuity of fire barrier walls. Fire barrier walls shall extend from the top of the floor/ceiling assembly below to the underside of the floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous through concealed spaces such as the space above a suspended ceiling. The supporting construction for fire barrier walls shall be protected to afford the required fire-resistance rating of the fire barrier supported except for 1-hour fireresistance-rated incidental use area separations as required by Table 2A.2.1.1 in buildings of Type IIB, IIIB and VB construction. Hollow vertical spaces within the fire barrier wall shall be fire stopped at every floor level. Exceptions: 1. The maximum required fire-resistance rating for assemblies supporting fire barriers separating tank storage as provided for in Section 2B.15.7.2.1 shall be 2 hours, but not less than required by Table 4A.1 for the building construction type. 2. Shaft enclosure shall be permitted to terminate at a top enclosure complying with Section 4B.7.12. 4B.6.5 Horizontal fire barriers. Horizontal fire barriers shall be constructed in accordance with Section 4B.11. 4B.6.6 Exterior walls. Where exterior walls serve as a part of a required fire-resistancerated enclosure, such walls shall comply with the requirements of Section 4B.4 for exterior walls and the fire-resistance-rated enclosure requirements shall not apply. Exception: Exterior walls required to be fire-resistance-rated in accordance with Section 8.22.6. 4B.6.7 Openings. Openings in a fire barrier wall shall be protected in accordance with Section 4B.14. Openings shall be limited to a maximum aggregate width of 25 SBC 801 2007 4/18 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION percent of the length of the wall, and the maximum area of any single opening shall not exceed 11 m2. Openings in exit enclosures shall also comply with Section 8.20.4. Exceptions: 1. Openings shall not be limited to 11 m2 where adjoining fire areas are equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. 2. Fire doors serving an exit enclosure. 3. Openings shall not be limited to 11 m2 or an aggregate width of 25 percent of the length of the wall where the opening protective assembly has been tested in accordance with ASTM E 119 and has a minimum fire-resistance rating not less than the fire-resistance rating of the wall. 4B.6.8 4B.6.8.1 Penetrations. Penetrations through fire barriers shall comply with Section 4B.12. Prohibited penetrations. Penetrations into an exit enclosure shall only be allowed when permitted by Section 8.20.5. 4B.6.9 Joints. Joints made in or between fire barriers shall comply with Section 4B.13. 4B.6.10 Ducts and air transfer openings. Penetrations by ducts and air transfer openings shall comply with Sections 4B.12 and 4B.16. SECTION 4B.7 SHAFT ENCLOSURES 4B.7.1 General. The provisions of this section shall apply to vertical shafts where such shafts are required to protect openings and penetrations through floor/ceiling and roof/ceiling assemblies. 4B.7.2 Shaft enclosure required. Openings through a floor/ceiling assembly shall be protected by a shaft enclosure complying with this section. Exceptions: 1. A shaft enclosure is not required for openings totally within an individual residential dwelling unit and connecting four stories or less. 2. A shaft enclosure is not required in a building equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1 for an escalator opening or stairway which is not a portion of the means of egress protected according to Item 2.1 or 2.2: 2.1 Where the area of the floor opening between stories does not exceed twice the horizontal projected area of the escalator or stairway and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. In other than Groups B and M, this application is limited to openings that do not connect more than four stories. 2.2 Where the opening is protected by approved power-operated automatic shutters at every floor penetrated. The shutters shall be of noncombustible construction and have a fire-resistance rating of not less than 1.5 hours. The shutter shall be so constructed as to close immediately upon the actuation of a smoke detector installed in accordance with Section 7.7.11 and shall completely shutoff the well opening. Escalators shall cease operation when the shutter begins to close. The shutter shall operate at a speed of not more than 150 mm/s and shall be equipped with a sensitive leading edge to arrest its progress SBC 801 2007 4/19 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION where in contact with any obstacle, and to continue its progress on release therefrom. 3. A shaft enclosure is not required for penetrations by pipe, tube, conduit, wire, cable, and vents protected in accordance with Section 4B.12.4. 4. A shaft enclosure is not required for penetrations by ducts protected in accordance with Section 4B.12.4. Grease ducts shall be protected in accordance with the SBC 501. 5. A shaft enclosure is not required for floor openings complying with the provisions for covered malls or atriums. 6. A shaft enclosure is not required for approved masonry chimneys, where annular space protection is provided at each floor level in accordance with Section 4B.17.2.5. 7. In other than Groups I-2 and I-3, a shaft enclosure is not required for a floor opening that complies with the following: 7.1 Does not connect more than two stories. 7.2 Is not part of the required means of egress system except as permitted in Section 8.19.1. 7.3 Is not concealed within the building construction. 7.4 Is not open to a corridor in Group I and R occupancies. 7.5 Is not open to a corridor on nonsprinklered floors in any occupancy. 7.6 Is separated from floor openings serving other floors by construction conforming to required shaft enclosures. 8. A shaft enclosure is not required for automobile ramps in open parking garages and enclosed parking garages constructed in accordance with Sections 2B.6.3 and 2B.6.4, respectively. 9. A shaft enclosure is not required for floor openings between a mezzanine and the floor below. 10. A shaft enclosure is not required for joints protected by a fire-resistant joint system in accordance with Section 4B.13. 11. Where permitted by other sections of these code requirements. 4B.7.3 Materials. The shaft enclosure shall be of materials permitted by the building type of construction. 4B.7.4 Fire-resistance rating. Shaft enclosures shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more and not less than 1 hour where connecting less than four stories. The number of stories connected by the shaft enclosure shall include any basements but not any mezzanines. Shaft enclosures shall be constructed as fire barriers in accordance with Section 4B.6. Shaft enclosures shall have a fire-resistance rating not less than the floor assembly penetrated, but need not exceed 2 hours. 4B.7.5 Continuity. Shaft enclosure walls shall extend from the top of the floor/ceiling assembly below to the underside of the floor or roof slab or deck above and shall be securely attached thereto. These walls shall be continuous through concealed spaces such as the space above a suspended ceiling. The supporting construction shall be protected to afford the required fire-resistance rating of the element supported. Hollow vertical spaces within the shaft enclosure construction wall shall be fire stopped at every floor level. 4B.7.6 Exterior walls. Where exterior walls serve as a part of a required shaft enclosure, such walls shall comply with the requirements of Section 4B.4 for exterior walls and the fire-resistance-rated enclosure requirements shall not apply. SBC 801 2007 4/20 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Exception: Exterior walls required to be fire-resistance rated in accordance with Section 8.22.6. 4B.7.7 4B.7.7.1 4B.7.8 4B.7.8.1 Openings. Openings in a shaft enclosure shall be protected in accordance with Section 4B.15 as required for fire barriers. Such openings shall be self-closing or automatic-closing by smoke detection. Prohibited openings. Openings other than those necessary for the purpose of the shaft shall not be permitted in shaft enclosures. Penetrations. Penetrations in a shaft enclosure shall be protected in accordance with Section 4B.12 as required for fire barriers. Prohibited penetrations. Penetrations other than those necessary for the purpose of the shaft shall not be permitted in shaft enclosures. Ducts shall not penetrate exit shaft enclosures. Exception: Duct penetrations as permitted in Section 8.20.5. 4B.7.9 Joints. Joints in a shaft enclosure shall comply with Section 4B.13. 4B.7.10 Ducts and air transfer openings. Penetrations of a shaft enclosure by ducts and air transfer openings shall comply with Sections 4B.12 and 4B.16. 4B.7.11 Enclosure at the bottom. Shafts that do not extend to the bottom of the building or structure shall: 1. Be enclosed at the lowest level with construction of the same fire-resistance rating as the lowest floor through which the shaft passes, but not less than the rating required for the shaft enclosure; 2. Terminate in a room having a use related to the purpose of the shaft. The room shall be separated from the remainder of the building by construction having a fire-resistance rating and opening protectives at least equal to the protection required for the shaft enclosure; or 3. Be protected by approved fire dampers installed in accordance with their listing at the lowest floor level within the shaft enclosure. Exceptions: 1. The fire-resistance-rated room separation is not required provided there are no openings in or penetrations of the shaft enclosure to the interior of the building except at the bottom. The bottom of the shaft shall be closed off around the penetrating items with materials permitted by Section 4B.17.3.1 for draft stopping, or the room shall be provided with an approved automatic fire suppression system. 2. A shaft enclosure containing a refuse chute or laundry chute shall not be used for any other purpose and shall terminate in a room protected in accordance with Section 4B.7.13.4. 3. The fire-resistance-rated room separation and the protection at the bottom of the shaft are not required provided there are no combustibles in the shaft and there are no openings or other penetrations through the shaft enclosure to the interior of the building. 4B.7.12 Enclosure at the top. A shaft enclosure that does not extend to the underside of the roof deck of the building shall be enclosed at the top with construction of the same fire-resistance rating as the topmost floor penetrated by the shaft, but not less than the fire-resistance rating required for the shaft enclosure. SBC 801 2007 4/21 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.7.13 4B.7.13.1 4B.7.13.2 4B.7.13.3 4B.7.13.4 4B.7.13.5 4B.7.13.6 4B.7.14 4B.7.14.1 SBC 801 Refuse and laundry chutes. Refuse and laundry chutes, access and termination rooms and incinerator rooms shall meet the requirements of Sections 4B.7.13.1 through 4B.7.13.6. Exception: Chutes serving and contained within a single dwelling unit. Refuse and laundry chute enclosures. A shaft enclosure containing a refuse or laundry chute shall not be used for any other purpose and shall be enclosed in accordance with Section 4B.7.4. Openings into the shaft, including those from access rooms and termination rooms, shall be protected in accordance with this section and Section 4B.15. Openings into chutes shall not be located in exit access corridors. Opening protectives shall be self-closing or automatic-closing upon the actuation of a smoke detector installed in accordance with Section 7.7.10, except that heat-activated closing devices shall be permitted between the shaft and the termination room. Materials. A shaft enclosure containing a refuse or laundry chute shall be constructed of materials as permitted by the building type of construction. Refuse and laundry chute access rooms. Access openings for refuse and laundry chutes shall be located in rooms or compartments completely enclosed by construction that has a fire-resistance rating of not less than 1 hour and openings into the access rooms shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour and shall be self-closing or automaticclosing upon the detection of smoke. Termination room. Refuse and laundry chutes shall discharge into an enclosed room completely separated from the remainder of the building by construction that has a fire-resistance rating of not less than 1 hour and openings into the termination room shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour and shall be self-closing or automatic-closing upon the detection of smoke. Refuse chutes shall not terminate in an incinerator room. Refuse and laundry rooms that are not provided with chutes need only comply with Table 2A.2.1.1. Incinerator room. Incinerator rooms shall comply with Table 2A.2.1.1. Automatic fire sprinkler system. An approved automatic fire sprinkler system shall be installed in accordance with Section 7.3.2.10.2. Elevator and dumbwaiter shafts. Elevator hoist way and dumbwaiter enclosures shall be constructed in accordance with Section 4B.7.4 and SBC 501. Elevator lobby. Elevators opening into a fire-resistance-rated corridor as required by Section 8.16.1 shall be provided with an elevator lobby at each floor containing such a corridor. The lobby shall separate the elevators from the corridor by fire partitions and the required opening protection. Elevator lobbies shall have at least one means of egress complying with Chapter 8 and other provisions within these code requirements. Exceptions: 1. In office buildings, separations are not required from a street-floor elevator lobby provided the entire street floor is equipped with an automatic sprinkler system in accordance with Section 7.3.3.1.1. 2. Elevators not required to be located in a shaft in accordance with Section 4B.7.2. 3. Where additional doors are provided in accordance with SBC 501. Such doors shall be tested in accordance with UL 1784 without an artificial bottom seal. 4. In other than Group I-3, and buildings more than four stories above the lowest level of Civil Defence vehicle access, lobby separation is not required where the building, including the lobby and corridors leading to the lobby, is 2007 4/22 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION protected by an automatic sprinkler system installed throughout in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. SECTION 4B.8 FIRE PARTITIONS 4B.8.1 General. The following wall assemblies shall comply with this section: 1. Walls separating dwelling units in the same building. 2. Walls separating sleeping units in occupancies in Group R-1, hotel occupancies, R-2 and I-1. 3. Walls separating tenant spaces in covered mall buildings as required by Section 2B.2.7.2. 4. Corridor walls as required by Section 8.16.1. 4B.8.2 Materials. The walls shall be of materials permitted by the building type of construction. 4B.8.3 Fire-resistance rating. The fire-resistance rating of the walls shall be 1 hour. Exceptions: 1. Corridor walls as permitted by Table 8.16.1. 2. Dwelling unit and sleeping unit separations in buildings of Type IIB, IIIB and VB construction shall have fire-resistance ratings of not less than 1/2 hour in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. 4B.8.4 Continuity. Fire partitions shall extend from the top of the floor assembly below to the underside of the floor or roof slab or deck above or to the fire-resistancerated floor/ceiling or roof/ceiling assembly above, and shall be securely attached thereto. If the partitions are not continuous to the deck, and where constructed of combustible construction, the space between the ceiling and the deck above shall be fire blocked or draft stopped in accordance with Sections 4B.17.2.1 and 4B.17.3.1 at the partition line. The supporting construction shall be protected to afford the required fire-resistance rating of the wall supported, except for tenant and sleeping unit separation walls and exit access corridor walls in buildings of Type IIB, IIIB and VB construction. Exceptions: 1. The wall need not be extended into the crawl space below where the floor above the crawl space has a minimum 1-hour fire-resistance rating. 2. Where the room-side fire-resistance-rated membrane of the corridor is carried through to the underside of a fire-resistance-rated floor or roof above, the ceiling of the corridor shall be permitted to be protected by the use of ceiling materials as required for a 1-hour fire-resistance-rated floor or roof system. 3. Where the corridor ceiling is constructed as required for the corridor walls, the walls shall be permitted to terminate at the upper membrane of such ceiling assembly. 4. The fire partition separating tenant spaces in a mall, complying with Section 2B.2.7.2, is not required to extend beyond the underside of a ceiling that is not part of a fire-resistance-rated assembly. A wall is not required in attic or ceiling spaces above tenant separation walls. 5. Fire blocking or draft stopping is not required at the partition line in Group R-2 buildings that do not exceed four stories in height provided the attic space is subdivided by draft stopping into areas not exceeding 279 m2 or above every two dwelling units, whichever is smaller. SBC 801 2007 4/23 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 6. Fire blocking or draft stopping is not required at the partition line in buildings equipped with an automatic sprinkler system installed throughout in accordance with Section 7.3.3.1.1 or 7.3.3.1.2 provided that automatic sprinklers are installed in combustible floor/ceiling and roof/ceiling spaces. 4B.8.5 Exterior walls. Where exterior walls serve as a part of a required fire-resistancerated enclosure, such walls shall comply with the requirements of Section 4B.4 for exterior walls and the fire-resistance-rated enclosure requirements shall not apply. 4B.8.6 Openings. Openings in a fire partition shall be protected in accordance with Section 4B.15. 4B.8.7 Penetrations. Penetrations through fire partitions shall comply with Section 4B.12. 4B.8.8 Joints. Joints made in or between fire partitions shall comply with Section 4B.13. 4B.8.9 Ducts and air transfer openings. Penetrations by ducts and air transfer openings shall comply with Sections 4B.12 and 4B.16. SECTION 4B.9 SMOKE BARRIERS 4B.9.1 General. Smoke barriers shall comply with this section. 4B.9.2 Materials. Smoke barriers shall be of materials permitted by the building type of construction. 4B.9.3 Fire-resistance rating. A 1-hour fire-resistance rating is required for smoke barriers. Exception: Smoke barriers constructed of minimum 2.5-mm-thick steel in Group I-3 buildings. 4B.9.4 Continuity. Smoke barriers shall form an effective membrane continuous from outside wall to outside wall and from floor slab to floor or roof deck above, including continuity through concealed spaces, such as those found above suspended ceilings, and interstitial structural and mechanical spaces. The supporting construction shall be protected to afford the required fire-resistance rating of the wall or floor supported in buildings of other than Type IIB, IIIB or VB construction. Exception: Smoke barrier walls are not required in interstitial spaces where such spaces are designed and constructed with ceilings that provide resistance to the passage of fire and smoke equivalent to that provided by the smoke barrier walls. 4B.9.5 Openings. Openings in a smoke barrier shall be protected in accordance with Section 4B.15. Exception: In Group I-2, where such doors are installed across corridors, a pair of opposite-swinging doors without a center mullion shall be installed having vision panels with approved fire-resistance-rated glazing materials in approved fireresistance-rated frames, the area of which shall not exceed that tested. The doors shall be close fitting within operational tolerances, and shall not have undercuts, louvers or grilles. The doors shall have head and jamb stops, astragals or rabbets at meeting edges and automatic-closing devices. Positive-latching devices are not required. SBC 801 2007 4/24 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.9.6 Penetrations. Penetrations through smoke barriers shall comply with Section 4B.12. 4B.9.7 Joints. Joints made in or between smoke barriers shall comply with Section 4B.13. 4B.9.8 Duct and air transfer openings. Penetrations by duct and air transfer openings shall comply with Sections 4B.12 and 4B.16. SECTION 4B.10 SMOKE PARTITIONS 4B.10.1 General. Smoke partitions installed as required elsewhere in the code shall comply with this section. 4B.10.2 Materials. The walls shall be of materials permitted by the building type of construction. 4B.10.3 Fire-resistance rating. Unless required elsewhere in the code, smoke partitions are not required to have a fire-resistance rating. 4B.10.4 Continuity. Smoke partitions shall extend from the floor to the underside of the floor or roof deck above or to the underside of the ceiling above where the ceiling membrane is constructed to limit the transfer of smoke. 4B.10.5 Openings. Windows shall be sealed to resist the free passage of smoke or be automatic-closing upon detection of smoke. Doors in smoke partitions shall comply with this section. Louvers. Doors in smoke partitions shall not include louvers. Smoke and draft-control doors. Where required elsewhere in the code, doors in smoke partitions shall be tested in accordance with UL 1784 with an artificial bottom seal installed across the full width of the bottom of the door assembly. The air leakage rate of the door assembly shall not exceed 0.0154 cubic meter per second per square meter (m3/s/m2) [15.4 (mm3/s/mm2)] of door opening at 25 Pa for both the ambient temperature test. Self-closing or automatic-closing doors. Where required elsewhere in the code, doors in smoke partitions shall be self-closing or automatic-closing in accordance with Section 4B.15.3.7.3. 4B.10.5.1 4B.10.5.2 4B.10.5.3 4B.10.6 Penetrations and joints. The space around penetrating items and in joints shall be filled with an approved material to limit the free passage of smoke. 4B.10.7 Ducts and air transfer openings. Air transfer openings in smoke partitions shall be provided with a smoke damper complying with Section 4B.16.3.2. Exception: Where the installation of a smoke damper will interfere with the operation of a required smoke control system in accordance with Section 7.9, approved alternative protection shall be utilized. SECTION 4B.11 HORIZONTAL ASSEMBLIES 4B.11.1 General. Floor and roof assemblies required to have a fire-resistance rating shall comply with this section. 4B.11.2 SBC 801 Materials. The floor and roof assemblies shall be of materials permitted by the 2007 4/25 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION building type of construction. 4B.11.3 4B.11.3.1 4B.11.3.2 4B.11.3.3 Fire-resistance rating. The fire-resistance rating of floor and roof assemblies shall not be less than that required by the building type of construction. Where the floor assembly separates mixed occupancies, the assembly shall have a fireresistance rating of not less than that required by Section 2A.2.3.2 based on the occupancies being separated. Where the floor assembly separates a single occupancy into different fire areas, the assembly shall have a fire-resistance rating of not less than that required by Section 4B.6.3.7. Floor assemblies separating dwelling units in the same building or sleeping units in occupancies in Group R-1, hotel occupancies, R-2 and I-1 shall be a minimum of 1-hour fire-resistance-rated construction. Exception: Dwelling unit and sleeping unit separations in buildings of Type IIB, IIIB, and VB construction shall have fire-resistance ratings of not less than 1/2 hour in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. Ceiling panels. Where the weight of lay-in ceiling panels, used as part of fireresistance-rated floor/ceiling or roof/ceiling assemblies, is not adequate to resist an upward force of 48 Pa, wire or other approved devices shall be installed above the panels to prevent vertical displacement under such upward force. Access doors. Access doors shall be permitted in ceilings of fire-resistance-rated floor/ceiling and roof/ceiling assemblies provided such doors are tested in accordance with ASTM E 119 as horizontal assemblies and labeled by an approved agency for such purpose. Unusable space. In 1-hour fire-resistance-rated floor construction, the ceiling membrane is not required to be installed over unusable crawl spaces. In 1-hour fire-resistance-rated roof construction, the floor membrane is not required to be installed where unusable attic space occurs above. 4B.11.4 Continuity. Assemblies shall be continuous without openings, penetrations or joints except as permitted by this section and Sections 4B.7.2, 4B.12.4 and 4B.13. Skylights and other penetrations through a fire-resistance-rated roof deck are permitted to be unprotected, provided that the structural integrity of the fireresistance-rated roof construction is maintained. Unprotected skylights shall not be permitted in roof construction required to be fire-resistance rated in accordance with Section 4B.4.10. The supporting construction shall be protected to afford the required fire-resistance rating of the horizontal assembly supported. 4B.11.5 Penetrations. Penetrations through fire-resistance-rated horizontal assemblies shall comply with Section 4B.12. 4B.11.6 Joints. Joints made in or between fire-resistance-rated horizontal assemblies shall comply with Section 4B.13. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 4B.13.4. 4B.11.7 Ducts and air transfer openings. Penetrations by ducts and air transfer openings shall comply with Sections 4B.12 and 4B.16. SECTION 4B.12 PENETRATIONS 4B.12.1 SBC 801 Scope. The provisions of this section shall govern the materials and methods of 2007 4/26 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION construction used to protect through penetrations and membrane penetrations. 4B.12.2 Installation details. Where sleeves are used, they shall be securely fastened to the assembly penetrated. The space between the item contained in the sleeve and the sleeve itself and any space between the sleeve and the assembly penetrated shall be protected in accordance with this section. Insulation and coverings on or in the penetrating item shall not penetrate the assembly unless the specific material used has been tested as part of the assembly in accordance with this section. Fire-resistance-rated walls. Penetrations into or through fire walls, fire barriers, smoke barrier walls, and fire partitions shall comply with this section. 4B.12.3.1 Through penetrations. Through penetrations of fire-resistance-rated walls shall comply with Section 4B.12.3.1.1 or 4B.12.3.1.2. Exception: Where the penetrating items are steel, ferrous or copper pipes or steel conduits, the annular space between the penetrating item and the fire-resistancerated wall shall be permitted to be protected as follows: 1. In concrete or masonry walls where the penetrating item is a maximum 150 mm nominal diameter and the opening is a maximum 0.093 m2, concrete, grout or mortar shall be permitted where installed the full thickness of the wall or the thickness required to maintain the fire-resistance rating; or 2. The material used to fill the annular space shall prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature fire conditions under a minimum positive pressure differential of 2.5 Pa at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated. 4B.12.3.1.1 Fire-resistance-rated assemblies. Penetrations shall be installed as tested in an approved fire-resistance-rated assembly. 4B.12.3.1.2 Through-penetration firestop system. Through penetrations shall be protected by an approved penetration fire stop system installed as tested in accordance with ASTM E 814 or UL 1479, with a minimum positive pressure differential of 2.5 Pa of water and shall have an F rating of not less than the required fire-resistance rating of the wall penetrated. 4B.12.3.2 Membrane penetrations. Membrane penetrations shall comply with Section 4B.12.3.1. Where walls and partitions are required to have a minimum 1-hour fireresistance rating, recessed fixtures shall be installed such that the required fire resistance will not be reduced. Exceptions: 1. Steel electrical boxes that do not exceed 0.0103 m2 in area provided the total area of such openings does not exceed 0.0645 m2 for any 9.3 m2 of wall area. Outlet boxes on opposite sides of the wall shall be separated as shown: 1.1 By a horizontal distance of not less than 600 mm; 1.2 By a horizontal distance of not less than the depth of the wall cavity where the wall cavity is filled with cellulose loose fill, rock wool or slag mineral wool insulation; 1.3 By solid fire blocking in accordance with Section 4B.17.2.1; 1.4 By protecting both outlet boxes by listed putty pads; or 1.5 By other listed materials and methods. 2. Membrane penetrations for listed electrical outlet boxes of any material are permitted provided such boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing. Outlet boxes on opposite sides of the wall shall be separated as follows: 2.1 By a horizontal distance of not less than 600 mm; 4B.12.3 SBC 801 2007 4/27 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.12.3.3 4B.12.3.4 2.2 By solid fire blocking in accordance with Section 4B.17.2.1; 2.3 By protecting both outlet boxes by listed putty pads; or 2.4 By other listed materials and methods. 3. The annular space created by the penetration of a fire sprinkler provided it is covered by a metal escutcheon plate. Ducts and air transfer openings. Penetrations of fire-resistance-rated walls by ducts and air transfer openings that are not protected with fire dampers shall comply with this section. Dissimilar materials. Noncombustible penetrating items shall not connect to combustible items beyond the point of fire stopping unless it can be demonstrated that the fire-resistance integrity of the wall is maintained. Horizontal assemblies. Penetrations of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected in accordance with Section 4B.7. Penetrations permitted by Exceptions 3 and 4 of Section 4B.7.2 shall comply with Sections 4B.12.4.1 through 4B.12.4.4. Exception: Penetrations located within the same room or undivided area as floor openings not required to have a shaft enclosure in accordance with Exception 1, 2, 5, 7, 8 or 9 in Section 4B.7.2. 4B.12.4.1 Through penetrations. Through penetrations of fire-resistance-rated horizontal assemblies shall comply with Section 4B.12.4.1.1 or 4B.12.4.1.2. Exceptions: 1. Penetrations by steel, ferrous or copper conduits, pipes, tubes, vents, concrete, or masonry through a single fire-resistance-rated floor assembly where the annular space is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature fire conditions under a minimum positive pressure differential of 2.5 Pa at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated. Penetrating items with a maximum 150 mm nominal diameter shall not be limited to the penetration of a single fire-resistance-rated floor assembly provided that the area of the penetration does not exceed 0.093 m2 in any 9.3 m2 of floor area. 2. Penetrations in a single concrete floor by steel, ferrous or copper conduits, pipes, tubes and vents with a maximum 150 mm nominal diameter provided concrete, grout or mortar is installed the full thickness of the floor or the thickness required to maintain the fire-resistance rating. The penetrating items with a maximum 150 mm nominal diameter shall not be limited to the penetration of a single concrete floor provided that the area of the penetration does not exceed 0.093 m2. 3. Electrical outlet boxes of any material are permitted provided that such boxes are tested for use in fire-resistance-rated assemblies and installed in accordance with the tested assembly. 4B.12.4.1.1 Fire-resistance-rated assemblies. Penetrations shall be installed as tested in the approved fire-resistance-rated assembly. 4B.12.4.1.2 Through-penetration firestop system. Through penetrations shall be protected by an approved through-penetration fire stop system installed and tested in accordance with ASTM E 814 or UL 1479, with a minimum positive pressure differential of 2.5 Pa. The system shall have an F rating and a T rating of not less than 1 hour but not less than the required rating of the floor penetrated. Exception: Floor penetrations contained and located within the cavity of a wall do not require a T rating. 4B.12.4 SBC 801 2007 4/28 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Membrane penetrations. Penetrations of membranes that are part of a fireresistance-rated horizontal assembly shall comply with Section 4B.12.4.1.1 or 4B.12.4.1.2. Where floor/ceiling assemblies are required to have a minimum 1hour fire-resistance rating, recessed fixtures shall be installed such that the required fire resistance will not be reduced. Exceptions: 1. Membrane penetrations by steel, ferrous or copper conduits, electrical outlet boxes, pipes, tubes, vents, concrete, or masonry-penetrating items where the annular space is protected either in accordance with Section 4B.12.4.1 or to prevent the free passage of flame and the products of combustion. Such penetrations shall not exceed an aggregate area of 0.0645 m2 in any 9.3 m2 of ceiling area in assemblies tested without penetrations. 2. Membrane penetrations by listed electrical outlet boxes of any material are permitted provided such boxes have been tested for use in fire-resistance-rated assemblies and are installed in accordance with the instructions included in the listing. 3. The annular space created by the penetration of a fire sprinkler provided it is covered by a metal escutcheon plate. 4B.12.4.3 Nonfire-resistance-rated assemblies. Penetrations of horizontal assemblies without a required fire-resistance rating shall meet the requirements of Section 4B.7 or shall comply with Sections 4B.12.4.3.1 through 4B.12.4.3.2. 4B.12.4.3.1 Noncombustible penetrating items. Noncombustible penetrating items that connect not more than three stories are permitted provided that the annular space is filled with an approved noncombustible material to resist the free passage of flame and the products of combustion. 4B.12.4.3.2 Penetrating items. Penetrating items that connect not more than two stories are permitted provided that the annular space is filled with an approved material to resist the free passage of flame and the products of combustion. 4B.12.4.4 Ducts and air transfer openings. Penetrations of horizontal assemblies by ducts and air transfer openings that are not required to have dampers shall comply with this section. Ducts and air transfer openings that are protected with dampers shall comply with Section 4B.16. 4B.12.4.5 Dissimilar materials. Noncombustible penetrating items shall not connect to combustible materials beyond the point of fire stopping unless it can be demonstrated that the fire-resistance integrity of the horizontal assembly is maintained. 4B.12.4.6 Floor fire doors. Floor fire doors used to protect openings in fire-resistance-rated floors shall be tested in the horizontal position in accordance with ASTM E 119, and shall achieve a fire-resistance rating not less than the assembly being penetrated. Floor fire doors shall be labeled by an approved agency. 4B.12.4.2 SECTION 4B.13 FIRE-RESISTANT JOINT SYSTEMS 4B.13.1 SBC 801 General. Joints installed in or between fire-resistance-rated walls, floor or floor/ceiling assemblies and roofs or roof/ceiling assemblies shall be protected by an approved fire-resistant joint system designed to resist the passage of fire for a time period not less than the required fire-resistance rating of the wall, floor or roof in or between which it is installed. Fire-resistant joint systems shall be tested in accordance with Section 4B.13.3. The void created at the intersection of a floor/ceiling assembly and an exterior curtain wall assembly shall be protected in accordance with Section 4B.13.4. 2007 4/29 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Exception: Fire-resistant joint systems shall not be required for joints in all of the following locations: 1. Floors within a single dwelling unit. 2. Floors where the joint is protected by a shaft enclosure in accordance with Section 4B.7. 3. Floors within atriums where the space adjacent to the atrium is included in the volume of the atrium for smoke control purposes. 4. Floors within malls. 5. Floors within open parking structures. 6. Mezzanine floors. 7. Walls that are permitted to have unprotected openings. 8. Roofs where openings are permitted. 9. Control joints not exceeding a maximum width of 16 mm and tested in accordance with ASTM E 119. 4B.13.2 Installation. Fire-resistant joint systems shall be securely installed in or on the joint for its entire length so as not to dislodge, loosen or otherwise impair its ability to accommodate expected building movements and to resist the passage of fire and hot gases. 4B.13.3 Fire test criteria. Fire-resistant joint systems shall be tested in accordance with the requirements of either ASTM E 1966 or UL 2079. Nonsymmetrical wall joint systems shall be tested with both faces exposed to the furnace, and the assigned fire-resistance rating shall be the shortest duration obtained from the two tests. When evidence is furnished to show that the wall was tested with the least fireresistant side exposed to the furnace, subject to acceptance of the building official, the wall need not be subjected to tests from the opposite side. Exception: For exterior walls with a horizontal fire separation distance greater than 1.5 m, the joint system shall be required to be tested for interior fire exposure only. 4B.13.4 Exterior curtain wall/floor intersection. Where fire-resistance-rated floor or floor/ceiling assemblies are required, voids created at the intersection of the exterior curtain wall assemblies and such floor assemblies shall be sealed with an approved material or system to prevent the interior spread of fire. Such material or systems shall be securely installed and capable of preventing the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature fire conditions under a minimum positive pressure differential of 2.5 Pa for the time period at least equal to the fire-resistance rating of the floor assembly. Height and fire-resistance requirements for curtain wall spandrels shall comply with Section 4B.4.9. SECTION 4B.14 FIRE-RESISTANCE RATING OF STRUCTURAL MEMBERS 4B.14.1 Requirements. The fire-resistance rating of structural members and assemblies shall comply with the requirements for the type of construction and shall not be less than the rating required for the fire-resistance-rated assemblies supported. Exception: Fire barriers and fire partitions as provided in Sections 4B.6.4 and 4B.8.4, respectively. 4B.14.2 Protection of structural members. Protection of columns, girders, trusses, beams, lintels or other structural members that are required to have a fire- SBC 801 2007 4/30 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.14.2.1 4B.14.2.2 4B.14.2.3 4B.14.2.4 4B.14.2.5 resistance rating shall comply with this section. Individual protection. Columns, girders, trusses, beams, lintels or other structural members that are required to have a fire-resistance rating and that support more than two floors or one floor and roof, or support a load-bearing wall or a non loadbearing wall more than two stories high, shall be individually protected on all sides for the full length with materials having the required fire-resistance rating. Other structural members required to have a fire-resistance rating shall be protected by individual encasement, by a membrane or ceiling protection as specified in Section 4B.11, or by a combination of both. Columns shall also comply with Section 4B.14.2.2. Column protection above ceilings. Where columns require a fire-resistance rating, the entire column, including its connections to beams or girders, shall be protected. Where the column extends through a ceiling, fire resistance of the column shall be continuous from the top of the floor through the ceiling space to the top of the column. Truss protection. The required thickness and construction of fire-resistance-rated assemblies enclosing trusses shall be based on the results of full-scale tests or combinations of tests on truss components or on approved calculations based on such tests that satisfactorily demonstrate that the assembly has the required fire resistance. Attachments to structural members. The edges of lugs, brackets, rivets and bolt heads attached to structural members shall be permitted to extend to within 25 mm of the surface of the fire protection. Reinforcing. Thickness of protection for concrete or masonry reinforcement shall be measured to the outside of the reinforcement except that stirrups and spiral reinforcement ties are permitted to project not more than 13 mm into the protection. 4B.14.3 Embedment and enclosures. Pipes, wires, conduits, ducts or other service facilities shall not be embedded in the required fire protective covering of a structural member that is required to be individually encased. 4B.14.4 Impact protection. Where the fire protective covering of a structural member is subject to impact damage from moving vehicles, the handling of merchandise or other activity, the fire protective covering shall be protected by corner guards or by a substantial jacket of metal or other noncombustible material to a height adequate to provide full protection, but not less than 1.5 m from the finished floor. 4B.14.5 Exterior structural members. Load-bearing structural members located within the exterior walls or on the outside of a building or structure shall be provided with the highest fire-resistance rating as determined in accordance with the following: 1. As required by Table 4A.1 for the type of building element based on the type of construction of the building; 2. As required by Table 4A.1 for exterior bearing walls based on the type of construction; and 3. As required by Table 4A.2 for exterior walls based on the fire separation distance. 4B.14.6 Bottom flange protection. Fire protection is not required at the bottom flange of lintels, shelf angles and plates, spanning not more than 1.8 m whether part of the structural frame or not, and from the bottom flange of lintels, shelf angles and plates not part of the structural frame, regardless of span. SBC 801 2007 4/31 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 4B.15 OPENING PROTECTIVES 4B.15.1 General. Opening protectives required by other sections of these code requirements shall comply with the provisions of this section. 4B.15.2 Fire-resistance-rated glazing. Labeled fire-resistance-rated glazing tested as part of a fire-resistance-rated wall assembly in accordance with ASTM E 119 shall not be required to comply with this section. 4B.15.3 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 4B.15.3.1, 4B.15.3.2 or 4B.15.3.3 and the fire protection rating indicated in Table 4B.15.3. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and NFPA 80. Exceptions: 1. Labeled protective assemblies that conform to the requirements of this section or UL 10A, UL 14B and UL 14C for tin-clad fire door assemblies. 2. Floor fire doors shall comply with Section 4B.12.4.6. Side-hinged or pivoted swinging doors. Side-hinged and pivoted swinging doors shall be tested in accordance with NFPA 252 or UL 10C. After 5 minutes into the NFPA 252 test, the neutral pressure level in the furnace shall be established at 1 m or less above the sill. Other types of doors. Other types of doors, including swinging elevator doors, shall be tested in accordance with NFPA 252 or UL 10B. The pressure in the furnace shall be maintained as nearly equal to the atmospheric pressure as possible. Once established, the pressure shall be maintained during the entire test period. 4B.15.3.1 4B.15.3.2 TABLE 4B.15.3 FIRE DOOR AND FIRE SHUTTER FIRE PROTECTION RATINGS TYPE OF ASSEMBLY Fire walls and fire barriers having a required fire-resistance rating greater than 1 hour Fire barriers having a required fireresistance rating of 1 hour: Shaft exit enclosure and exit passageway walls Other fire barriers Fire partitions: Corridor walls Other fire partitions Exterior walls a. b. SBC 801 REQUIRED ASSEMBLY RATING (hours) 4 3 2 1½ MINIMUM FIRE DOOR AND FIRE SHUTTER ASSEMBLY RATING (hours) 3 3a 1½ 1½ 1 1 1 ¾ 1 0.5 1 3 2 1 1/3b 1/3b ¾ 1½ 1½ ¾ Two doors, each with a fire protection rating of 1 ½ hours, installed on opposite sides of the same opening in a fire wall, shall be deemed equivalent in fire protection rating to one 3-hour fire door. For testing requirements, see Section 4B.15.3.3. 2007 4/32 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Door assemblies in corridors and smoke barriers. Fire door assemblies required to have a minimum fire protection rating of 20 minutes where located in corridor walls or smoke barrier walls having a fire-resistance rating in accordance with Table 4B.15.3 shall be tested in accordance with NFPA 252 or UL 10C without the hose stream test. If a 20-minute fire door assembly contains glazing material, the glazing material in the door itself shall have a minimum fire protection rating of 20 minutes and be exempt from the hose stream test. Glazing material in any other part of the door assembly, including transom lites and side lites, shall be tested in accordance with NFPA 257, including the hose stream test, in accordance with Section 4B.15.4. Fire door assemblies shall also meet the requirements for a smoke- and draft-control door assembly tested in accordance with UL 1784 with an artificial bottom seal installed across the full width of the bottom of the door assembly. The air leakage rate of the door assembly shall not exceed 0.01524 m3/s/m2 of door opening at 25 Pa for both the ambient temperature and elevated temperature tests. Louvers shall be prohibited. Exceptions: 1. View ports that require a hole not larger than 25 mm in diameter through the door, have at least a 6 mm glass disc and the holder is of metal that will not melt out where subject to temperatures of 927°C. 2. Corridor door assemblies in occupancies of Group I-2 shall be in accordance with Section 2A.7.3.1. 3. Unprotected openings shall be permitted for corridors in multi theater complexes where each motion picture auditorium has at least one-half of its required exit or exit access doorways opening directly to the exterior or into an exit passageway. 4B.15.3.4 Doors in vertical exit enclosures and exit passageways. Fire door assemblies in vertical exit enclosures and exit passageways shall have a maximum transmitted temperature end point of not more than 232°C above ambient at the end of 30 minutes of standard fire test exposure. Exception: The maximum transmitted temperature end point is not required in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. 2 4B.15.3.4.1 Glazing in doors. Fire-protection-rated glazing in excess of 0.065 m shall be permitted in fire door assemblies when tested in accordance with NFPA 252 as components of the door assemblies and not as glass lights, and shall have a maximum transmitted temperature end point of 232°C in accordance with Section 4B.15.3.4. Exception: The maximum transmitted temperature end point is not required in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. 4B.15.3.5 Labeled protective assemblies. Fire door assemblies shall be labeled by an approved agency. The labels shall comply with NFPA 80, and shall be permanently affixed to the door or frame. 4B.15.3.5.1 Fire door labeling requirements. Fire doors shall be labeled showing the name of the manufacturer, the name of the third-party inspection agency, the fire protection rating and, where required for fire doors in exit enclosures by Section 4B.15.3.4, the maximum transmitted temperature end point. Smoke and draft control doors complying with UL 1784 shall be labeled as such. Labels shall be approved and permanently affixed. The label shall be applied at the factory or location where fabrication and assembly are performed. 4B.15.3.5.2 Oversized doors. Oversized fire doors shall bear an oversized fire door label by an approved agency or shall be provided with a certificate of inspection furnished 4B.15.3.3 SBC 801 2007 4/33 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.15.3.5.3 4B.15.3.5.4 4B.15.3.6 4B.15.3.6.1 4B.15.3.6.2 4B.15.3.6.3 4B.15.3.6.4 4B.15.3.7 4B.15.3.7.1 4B.15.3.7.2 4B.15.3.7.3 SBC 801 by an approved testing agency. When a certificate of inspection is furnished by an approved testing agency, the certificate shall state that the door conforms to the requirements of design, materials and construction, but has not been subjected to the fire test. Smoke and draft control door labeling requirements. Smoke and draft control doors complying with UL 1784 shall be labeled in accordance with Section 4B.15.3.5.1 and shall show the letter “S” on the fire rating label of the door. This marking shall indicate that the door and frame assembly are in compliance when listed or labeled gasketing is also installed. Fire door frame labeling requirements. Fire door frames shall be labeled showing the names of the manufacturer and the third-party inspection agency. Glazing material. Fire-protection-rated glazing conforming to the opening protection requirements in Section 4B.15.3 shall be permitted in fire door assemblies. Size limitations. Wired glass used in fire doors shall comply with Table 4B.15.4.3. Other fire-protection-rated glazing shall comply with the size limitations of NFPA 80. Exceptions: 1. Fire-protection-rated glazing in fire doors located in fire walls shall be prohibited except that where serving as a horizontal exit, a self-closing swinging door shall be permitted to have a vision panel of not more than 0.0645 m2 without a dimension exceeding 250 mm. 2. Fire-protection-rated glazing shall not be installed in fire doors having a 1 ½ hour fire protection rating intended for installation in fire barriers, unless the glazing is not more than 0.0645 m2 in area. Exit and elevator protectives. Approved fire-protection-rated glazing used in fire doors in elevator and stairway shaft enclosures shall be so located as to furnish clear vision of the passageway or approach to the elevator or stairway. Labeling. Fire-protection-rated glazing shall bear a label or other identification showing the name of the manufacturer, the test standard and the fire protection rating. Such label or other identification shall be issued by an approved agency and shall be permanently affixed. Safety glazing. Fire-protection-rated glazing installed in fire doors or fire window assemblies in areas subject to human impact in hazardous locations shall comply with Chapter 11 of the SBC 201. Door closing. Fire doors shall be self-closing or automatic-closing in accordance with this section. Exception: Fire doors located in common walls separating sleeping units in Group R-1 shall be permitted without automatic-closing or self-closing devices. Latch required. Unless otherwise specifically permitted, single fire doors and both leaves of pairs of side-hinged swinging fire doors shall be provided with an active latch bolt that will secure the door when it is closed. Automatic-closing fire door assemblies. Automatic-closing fire door assemblies shall be self-closing in accordance with NFPA 80. Smoke-activated doors. Automatic-closing fire doors installed in the following locations shall be automatic-closing by the actuation of smoke detectors installed in accordance with Section 7.7.10 or by loss of power to the smoke detector or hold-open device. Fire doors that are automatic-closing by smoke detection shall not have more than a 10-second delay before the door starts to close after the smoke detector is actuated. 1. Doors installed across a corridor. 2. Doors that protect openings in horizontal exits, exits or exit access corridors 2007 4/34 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION required to be of fire-resistance-rated construction. 3. Doors that protect openings in walls required to be fire-resistance rated by Table 2A.2.1.1. 4. Doors installed in smoke barriers in accordance with Section 4B.9.5. 5. Doors installed in fire partitions in accordance with Section 4B.8.6. 6. Doors installed in a fire wall in accordance with Section 4B.5.8. 4B.15.3.7.4 Doors in pedestrian ways. Vertical sliding or vertical rolling steel fire doors in openings through which pedestrians travel shall be heat activated or activated by smoke detectors with alarm verification. 4B.15.3.8 Swinging fire shutters. Where fire shutters of the swinging type are installed in exterior openings, not less than one row in every three vertical rows shall be arranged to be readily opened from the outside, and shall be identified by distinguishing marks or letters not less 150 mm high. 4B.15.3.9 Rolling fire shutters. Where fire shutters of the rolling type are installed, such shutters shall include approved automatic-closing devices. 4B.15.4 4B.15.4.1 4B.15.4.2 Fire-protection rated glazing. Glazing in fire window assemblies shall be fire protection rated in accordance with this section and Table 4B.15.4. Glazing in fire doors shall comply with Section 4B.15.3.6. Fire-protection-rated glazing installed as an opening protective in fire partitions, smoke barriers and fire barriers shall be tested in accordance with and shall meet the acceptance criteria of NFPA 257 for a fire protection rating of 45 minutes. Fire-protection-rated glazing shall also comply with NFPA 80. Fire-protection-rated glazing required in accordance with Section 4B.4.12 for exterior wall opening protection shall be tested in accordance with and shall meet the acceptance criteria of NFPA 257 for a fire protection rating as required in Section 4B.15.4.7. Exceptions: 1. Wired glass in accordance with Section 4B.15.4.3. 2. Fire-protection-rated glazing in 0.5-hour fire-resistance-rated partitions is permitted to have an 0.33-hour fire protection rating. Testing under positive pressure. NFPA 257 shall evaluate fire-protection-rated glazing under positive pressure. Within the first 10 minutes of a test, the pressure in the furnace shall be adjusted so at least two-thirds of the test specimen is above the neutral pressure plane, and the neutral pressure plane shall be maintained at that height for the balance of the test. Nonsymmetrical glazing systems. Nonsymmetrical fire-protection-rated glazing systems in fire partitions, fire barriers or in exterior walls with a fire separation of 1.5 m or less pursuant to Section 4B.4 shall be tested with both faces exposed to the furnace, and the assigned fire protection rating shall be the shortest duration obtained from the two tests conducted in compliance with NFPA 257. TABLE 4B.15.4 FIRE WINDOW ASSEMBLY FIRE PROTECTION RATINGS TYPE OF ASSEMBLY Interior walls: Fire walls Fire barriers and fire partitions REQUIRED ASSEMBLY RATING (hours) All >1 1 1 Smoke barriers >1 Exterior walls 1 Party walls All a. Not permitted except as specified in Section 4B.15.2. SBC 801 2007 MINIMUM FIRE WINDOW ASSEMBLY RATING (hours) NPa NPa ¾ ¾ 1½ ¾ NPa 4/35 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.15.4.3 Wired glass. Steel window frame assemblies of 3 mm minimum solid section or of not less than nominal 1-mm-thick formed sheet steel members fabricated by pressing, mitering, riveting, interlocking or welding and having provision for glazing with 6 mm wired glass where securely installed in the building construction and glazed with 6 mm labeled wired glass shall be deemed to meet the requirements for a 3/4-hour fire window assembly. Wired glass panels shall conform to the size limitations set forth in Table 4B.15.4.3. OPENING FIRE PROTECTION RATING 3 hours TABLE 4B.15.4.3 LIMITING SIZES OF WIRED GLASS PANELS MAXIMUM AREA (square mm) 0 MAXIMUM HEIGHT (mm) 0 MAXIMUM WIDTH (mm) 0 0 0 0 1 and 1 ½ hours 64,500 835 250 ¾ hours 836,180 1,370 1,370 Not Limited Not Limited Not Limited 836,180 1,370 1,370 1 ½ hour doors in exterior walls 20 minutes Fire window assemblies Nonwired glass. Glazing other than wired glass in fire window assemblies shall be fire-protection-rated glazing installed in accordance with and complying with the size limitations set forth in NFPA 80. 4B.15.4.5 Installation. Fire-protection-rated glazing shall be in the fixed position or be automatic-closing and shall be installed in approved frames. 4B.15.4.6 Window mullions. Metal mullions that exceed a nominal height of 3.7 m shall be protected with materials to afford the same fire-resistance rating as required for the wall construction in which the protective is located. 4B.15.4.7 Interior fire window assemblies. Fire-protection-rated glazing used in fire window assemblies located in fire partitions and fire barriers shall be limited to use in assemblies with a maximum fire-resistance rating of 1 hour in accordance with this section. 4B.15.4.7.1 Where permitted. Fire-protection-rated glazing shall be limited to fire partitions designed in accordance with Section 4B.8 and fire barriers utilized in the applications set forth in Sections 4B.6.3.5 and 4B.6.3.6 where the fire-resistance rating does not exceed 1 hour. 4B.15.4.7.2 Size limitations. The total area of windows shall not exceed 25 percent of the area of a common wall with any room. 4B.15.4.8 Exterior fire window assemblies. Exterior openings, other than doors, required to be protected by Section 4B.4.12, where located in a wall required by Table 4A.2 to have a fire-resistance rating of greater than 1 hour, shall be protected with an assembly having a fire protection rating of not less than 1 ½ hours. Exterior openings required to be protected by Section 4B.4.8, where located in a wall required by Table 4A.2 to have a fire-resistance rating of 1 hour, shall be protected with an assembly having a fire protection rating of not less than 3/4 hour. Exterior openings required to be protected by Section 4B.4.9 or 4B.4.10 shall be protected with an assembly having a fire protection rating of not less than 3/4 hour. Openings in non fire-resistance-rated exterior wall assemblies that require protection in accordance with Section 4B.4.8, 4B.4.9 or 4B.4.10 shall have a fire protection rating of not less than 3/4 hour. 4B.15.4.4 SBC 801 2007 4/36 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.15.4.9 Labeling requirements. Fire-protection-rated glazing shall bear a label or other identification showing the name of the manufacturer, the test standard, and the fire protection rating. Such label or identification shall be issued by an approved agency and shall be permanently affixed. SECTION 4B.16 DUCTS AND AIR TRANSFER OPENINGS 4B.16.1 4B.16.1.1 4B.16.2 4B.16.2.1 4B.16.2.2 4B.16.3 4B.16.3.1 General. The provisions of this section shall govern the protection of ducts and air transfer openings in fire-resistance-rated assemblies. Ducts and air transfer openings without dampers. Ducts and air transfer openings that penetrate fire-resistance-rated assemblies and are not required by this section to have dampers shall comply with the requirements of Section 4B.12. Installation. Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling dampers located within air distribution and smoke control systems shall be installed in accordance with the requirements of this section, the manufacturer’s installation instructions and listing. Smoke control system. Where the installation of a fire damper will interfere with the operation of a required smoke control system in accordance with Section 7.9, approved alternative protection shall be utilized. Hazardous exhaust ducts. Fire dampers for hazardous exhaust duct systems shall comply with the SBC 501. Damper testing and ratings. Dampers shall be listed and bear the label of an approved testing agency indicating compliance with the standards in this section. Fire dampers shall comply with the requirements of UL 555. Only fire dampers labeled for use in dynamic systems shall be installed in heating, ventilation and air-conditioning systems designed to operate with fans on during a fire. Smoke dampers shall comply with the requirements of UL 555S. Combination fire/smoke dampers shall comply with the requirements of both UL 555 and UL 555S. Ceiling radiation dampers shall comply with the requirements of UL 555C. Fire protection rating. Fire dampers shall have the minimum fire protection rating specified in Table 4B.16.3.1 for the type of penetration. TABLE 4B.16.3.1 FIRE DAMPER RATING TYPE OF PENETRATION MINIMUM DAMPER RATING (hour) Less than 3-hour fire resistance-rated assemblies 1.5 3-hour or greater fire resistance-rated assemblies 3 4B.16.3.1.1 Fire damper actuating device. The fire damper actuating device shall meet one SBC 801 of the following requirements: 1. The operating temperature shall be approximately 10°C above the normal temperature within the duct system, but not less than 70°C. 2. The operating temperature shall be not more than 140°C where located in a smoke control system complying with Section 7.9. 3. Where a combination fire/smoke damper is located in a smoke control system complying with Section 7.9, the operating temperature rating shall be approximately 10°C above the maximum smoke control system designed operating temperature, or a maximum temperature of 177°C. The temperature 2007 4/37 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION shall not exceed the UL 555S degradation test temperature rating for a combination fire/smoke damper. 4B.16.3.2 Smoke damper ratings. Smoke damper leakage ratings shall not be less than Class II. Elevated temperature ratings shall not be less than 120°C. 4B.16.3.2.1 Smoke damper actuation methods. The smoke damper shall close upon actuation of a listed smoke detector or detectors installed in accordance with Section 7.7.10 and one of the following methods, as applicable: 1. Where a damper is installed within a duct, a smoke detector shall be installed in the duct within 1.5 m of the damper with no air outlets or inlets between the detector and the damper. The detector shall be listed for the air velocity, temperature and humidity anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate. 2. Where a damper is installed above smoke barrier doors in a smoke barrier, a spot-type detector listed for releasing service shall be installed on either side of the smoke barrier door opening. 3. Where a damper is installed within an unducted opening in a wall, a spot-type detector listed for releasing service shall be installed within 1.5 m horizontally of the damper. 4. Where a damper is installed in a corridor wall, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor. 5. Where a total-coverage smoke detector system is provided within areas served by a heating, ventilation and air-conditioning (HVAC) system, dampers shall be permitted to be controlled by the smoke detection system. 4B.16.4 Access and identification. Fire and smoke dampers shall be provided with an approved means of access, large enough to permit inspection and maintenance of the damper and its operating parts. The access shall not affect the integrity of fireresistance-rated assemblies. The access openings shall not reduce the fireresistance rating of the assembly. Access points shall be permanently identified on the exterior by a label having letters not less than 13 mm in height reading: SMOKE DAMPER or FIRE DAMPER. Access doors in ducts shall be tight fitting and suitable for the required duct construction. 4B.16.5 Where required. Fire dampers, smoke dampers, combination fire/smoke dampers and ceiling radiation dampers shall be provided at the locations prescribed in this section. Where an assembly is required to have both fire dampers and smoke dampers, combination fire/smoke dampers or a fire damper and a smoke damper shall be required. Fire walls. Ducts and air transfer openings permitted in fire walls in accordance with Section 4B.5.11 shall be protected with approved fire dampers installed in accordance with their listing. Fire barriers. Duct and air transfer openings of fire barriers shall be protected with approved fire dampers installed in accordance with their listing. Exception: Fire dampers are not required at penetrations of fire barriers where any of the following apply: 1. Penetrations are tested in accordance with ASTM E119 as part of the fireresistance-rated assembly. 2. Ducts are used as part of an approved smoke control system in accordance with Section 7.9. 3. Such walls are penetrated by ducted HVAC systems, have a required fireresistance rating of 1 hour or less, are in areas of other than Group H and are in 4B.16.5.1 4B.16.5.2 SBC 801 2007 4/38 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. For the purposes of this exception, a ducted HVAC system shall be a duct system for conveying supply, return or exhaust air as part of the structure’s HVAC system. Such a duct system shall be constructed of sheet steel not less than 0.5 mm (26 gage) thickness and shall be continuous from the air-handling appliance or equipment to the air outlet and inlet terminals. 4B.16.5.3 Shaft enclosures. Ducts and air transfer openings shall not penetrate a shaft serving as an exit enclosure except as permitted by Section 8.20.5. 4B.16.5.3.1 Penetrations of shaft enclosures. Shaft enclosures that are permitted to be penetrated by ducts and air transfer openings shall be protected with approved fire and smoke dampers installed in accordance with their listing. Exceptions: 1. Fire dampers are not required at penetrations of shafts where: 1.1 Steel exhaust subducts extended at least 560 mm vertically in exhaust shafts provided there is a continuous airflow upward to the outside, or 1.2 Penetrations are tested in accordance with ASTM E 119 as part of the rated assembly, or 1.3 Ducts are used as part of an approved smoke control system designed and installed in accordance with Section 7.9, and where the fire damper will interfere with the operation of the smoke control system, or 1.4 The penetrations are in parking garage exhaust or supply shafts that are separated from other building shafts by not less than 2-hour fireresistance-rated construction. 2. In Group B occupancies, equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1, smoke dampers are not required at penetrations of shafts where: 2.1 Bathroom and toilet room exhaust openings with steel exhaust subducts, having a wall thickness of at least 0.5 mm that extend at least 560 mm vertically and the exhaust fan at the upper terminus, powered continuously in accordance with the provisions of Section 7.9.11, maintains airflow upward to the outside, or 2.2 Ducts are used as part of an approved smoke control system, designed and installed in accordance with Section 7.9, and where the smoke damper will interfere with the operation of the smoke control system, or 3. Smoke dampers are not required at penetration of exhaust or supply shafts in parking garages that are separated from other building shafts by not less than 2-hour fire-resistance-rated construction. 4B.16.5.4 Fire partitions. Duct penetrations in fire partitions shall be protected with approved fire dampers installed in accordance with their listing. Exceptions: In occupancies other than Group H, fire dampers are not required where any of the following apply: 1. The partitions are tenant separation and corridor walls in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1 or 7.3.3.1.2 and the duct is protected as a through penetration in accordance with Section 4B.12. 2. The duct system is constructed of approved materials in accordance with the SBC 501 and the duct penetrating the wall meets all of the following minimum requirements: 2.1 The duct shall not exceed 0.065 m2. 2.2 The duct shall be constructed of steel a minimum 0.55 mm in thickness. 2.3 The duct shall not have openings that communicate the corridor with SBC 801 2007 4/39 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION adjacent spaces or rooms. 2.4 The duct shall be installed above a ceiling. 2.5 The duct shall not terminate at a wall register in the fire-resistance-rated wall. 2.6 A minimum 300 mm long by 1.5 mm thick steel sleeve shall be centered in each duct opening. The sleeve shall be secured to both sides of the wall and all four sides of the sleeve with minimum 38 mm by 38 mm by 1.5 mm steel retaining angles. The retaining angles shall be secured to the sleeve and the wall with No. 10 (M5) screws. The annular space between the steel sleeve and wall opening shall be filled with rock (mineral) wool batting on all sides. 4B.16.5.4.1 Corridors. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a corridor enclosure required to have smoke and draft control doors in accordance with Section 4B.15.3.3. Exceptions: 1. Smoke dampers are not required where the building is equipped throughout with an approved smoke control system in accordance with Section 7.9, and smoke dampers are not necessary for the operation and control of the system. 2. Smoke dampers are not required in corridor penetrations where the duct is constructed of steel not less than 0.5 mm in thickness and there are no openings serving the corridor. 4B.16.5.5 Smoke barriers. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a smoke barrier. Smoke dampers and smoke damper actuation methods shall comply with Section 4B.16.3.2.1. Exception: Smoke dampers are not required where the openings in ducts are limited to a single smoke compartment and the ducts are constructed of steel. 4B.16.6 4B.16.6.1 SBC 801 Horizontal assemblies. Penetrations by ducts and air transfer openings of a floor, floor/ceiling assembly or the ceiling membrane of a roof/ceiling assembly shall be protected by a shaft enclosure that complies with Section 4B.7 or shall comply with this section. Through penetrations. In occupancies other than Groups I-2 and I-3, a duct and air transfer opening system constructed of approved materials in accordance with the SBC 501 that penetrates a fire-resistance-rated floor/ceiling assembly that connects not more than two stories is permitted without shaft enclosure protection provided a fire damper is installed at the floor line. Exception: A duct is permitted to penetrate three floors or less without a fire damper at each floor provided it meets all of the following requirements. 1. The duct shall be contained and located within the cavity of a wall and shall be constructed of steel not less 0.5 mm in thickness. 2. The duct shall open into only one dwelling unit or sleeping unit and the duct system shall be continuous from the unit to the exterior of the building. 3. The duct shall not exceed 100 mm nominal diameter and the total area of such ducts shall not exceed 0.0645 m2 for any 9.3 m2 of floor area. 4. The annular space around the duct is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E 119 time-temperature conditions under a minimum positive pressure differential of 2.5 Pa at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated. 2007 4/40 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.16.6.2 4B.16.6.3 4B.16.7 5. Grille openings located in a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be protected with a ceiling radiation damper in accordance with Section 4B.16.6.2. Membrane penetrations. Where duct systems constructed of approved materials in accordance with the SBC 501 penetrate a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly, shaft enclosure protection is not required provided an approved ceiling radiation damper is installed at the ceiling line. Where a duct is not attached to a diffuser that penetrates a ceiling of a fireresistance-rated floor/ceiling or roof/ceiling assembly, shaft enclosure protection is not required provided an approved ceiling radiation damper is installed at the ceiling line. Ceiling radiation dampers shall be tested in accordance with UL 555C and constructed in accordance with the details listed in a fire-resistance-rated assembly or shall be labeled to function as a heat barrier for air-handling outlet/inlet penetrations in the ceiling of a fire-resistance-rated assembly. Ceiling radiation dampers shall not be required where ASTM E 119 fire tests have shown that ceiling radiation dampers are not necessary in order to maintain the fireresistance rating of the assembly. Ceiling radiation dampers shall not be required where exhaust duct penetrations are protected in accordance with Section 4B.12.4.2 and the exhaust ducts are located within the cavity of a wall, and do not pass through another dwelling unit or tenant space. Nonfire-resistance-rated assemblies. Duct systems constructed of approved materials in accordance with the SBC 501 that penetrate nonfire-resistance-rated floor assemblies and that connect not more than two stories are permitted without shaft enclosure protection provided that the annular space between the assembly and the penetrating duct is filled with an approved noncombustible material to resist the free passage of flame and the products of combustion. Duct systems constructed of approved materials in accordance with the SBC 501 that penetrate nonfire-resistance-rated floor assemblies and that connect not more than three stories are permitted without shaft enclosure protection provided that the annular space between the assembly and the penetrating duct is filled with an approved noncombustible material to resist the free passage of flame and the products of combustion, and a fire damper is installed at each floor line. Exception: Fire dampers are not required in ducts within individual residential dwelling units. Flexible ducts and air connectors. Flexible ducts and air connectors shall not pass through any fire-resistance-rated assembly. Flexible air connectors shall not pass through any wall, floor or ceiling. SECTION 4B.17 CONCEALED SPACES 4B.17.1 General. Fire blocking and draft stopping shall be installed in combustible concealed locations in accordance with this section. Fire blocking shall comply with Section 4B.17.2. Draft stopping in floor/ceiling spaces and attic spaces shall comply with Sections 4B.17.3 and 4B.17.4, respectively. The permitted use of combustible materials in concealed spaces of noncombustible buildings shall be limited to the applications indicated in Section 4B.17.5. 4B.17.2 Fire blocking. In combustible construction, fire blocking shall be installed to cut off concealed draft openings (both vertical and horizontal) and shall form an effective barrier between floors, between a top story and a roof or attic space. Fire SBC 801 2007 4/41 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION blocking shall be installed in the locations specified in Sections 4B.17.2.2 through 4B.17.2.7. 4B.17.2.1 Fire blocking materials. Fire blocking shall consist of 50 mm nominal lumber or two thicknesses of 25 mm nominal lumber with broken lap joints or one thickness of 18 mm wood structural panel with joints backed by 18 mm wood structural panel or one thickness of 20 mm particleboard with joints backed by 20 mm particleboard. Gypsum board, cement fiber board, batts or blankets of mineral wool or glass fiber or other approved materials installed in such a manner as to be securely retained in place shall be permitted as an acceptable fire block. Batts or blankets of mineral or glass fiber or other approved non-rigid materials shall be permitted for compliance with the 3000 mm horizontal fire blocking in walls constructed using parallel rows of studs or staggered studs. Loose-fill insulation material shall not be used as a fire block unless specifically tested in the form and manner intended for use to demonstrate its ability to remain in place and to retard the spread of fire and hot gases. The integrity of fire blocks shall be maintained. 4B.17.2.1.1 Double stud walls. Batts or blankets of mineral or glass fiber or other approved non-rigid materials shall be allowed as fire blocking in walls constructed using parallel rows of studs or staggered studs. 4B.17.2.2 Concealed wall spaces. Fire blocking shall be provided in concealed spaces of stud walls and partitions, including furred spaces, and parallel rows of studs or staggered studs, as follows: a. Vertically at the ceiling and floor levels. b. Horizontally at intervals not exceeding 3 m. 4B.17.2.3 Connections between horizontal and vertical spaces. Fire blocking shall be provided at interconnections between concealed vertical stud wall or partition spaces and concealed horizontal spaces created by an assembly of floor joists or trusses, and between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings, cove ceilings and similar locations. 4B.17.2.4 Stairways. Fire blocking shall be provided in concealed spaces between stair stringers at the top and bottom of the run. Enclosed spaces under stairs shall also comply with Section 8.19.1.5. 4B.17.2.5 Ceiling and floor openings. Where annular space protection is provided in accordance with Exception 6 of Section 4B.7.2, Exception 1 of Section 4B.12.4.2, or Section 4B.12.4.3, fire blocking shall be installed at openings around vents, pipes, ducts, chimneys and fireplaces at ceiling and floor levels, with an approved material to resist the free passage of flame and the products of combustion. Factory-built chimneys and fireplaces shall be fire blocked in accordance with UL 103 and UL 127. 4B.17.2.6 Architectural trim. Fire blocking shall be installed within concealed spaces of exterior wall finish and other exterior architectural elements where permitted to be of combustible construction in Section 9.6 of the SBC 201 or where erected with combustible frames, at maximum intervals of 6 m. If non-continuous, such elements shall have closed ends, with at least 100 mm of separation between sections. Exceptions: 1. Fire blocking of cornices is not required in single-family dwellings, as applicable in SBC 201. Fire blocking of cornices of a two-family dwelling as applicable in SBC 201 is required only at the line of dwelling unit separation. 2. Fire blocking shall not be required where installed on noncombustible framing and the face of the exterior wall finish exposed to the concealed space is covered by one of the following materials: 2.1 Aluminum having a minimum thickness of 0.5 mm. SBC 801 2007 4/42 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 2.2 4B.17.2.7 4B.17.3 4B.17.3.1 4B.17.3.2 4B.17.3.3 Corrosion-resistant steel having a base metal thickness not less than 0.4 mm at any point. 2.3 Other approved noncombustible materials. Concealed sleeper spaces. Where wood sleepers are used for laying wood flooring on masonry or concrete fire-resistance-rated floors, the space between the floor slab and the underside of the wood flooring shall be filled with an approved material to resist the free passage of flame and products of combustion or fire blocked in such a manner that there will be no open spaces under the flooring that will exceed 9.3 m2 in area and such space shall be filled solidly under permanent partitions so that there is no communication under the flooring between adjoining rooms. Exceptions: 1. Fire blocking is not required for slab-on-grade floors in gymnasiums. 2. Fire blocking is required only at the juncture of each alternate lane and at the ends of each lane in a bowling facility. Draft stopping in floors. In combustible construction, draft stopping shall be installed to subdivide floor/ceiling assemblies in the locations prescribed in Sections 4B.17.3.2 through 4B.17.3.3. Draft stopping materials. Draft stopping materials shall not be less than 13 mm gypsum board, 10 mm wood structural panel, 10 mm particleboard or other approved materials adequately supported. The integrity of draft stops shall be maintained. Groups R-1, R-2, R-3 and R-4. Draft stopping shall be provided in floor/ceiling spaces in Group R-1 buildings, in Group R-2 buildings as applicable in SBC 201 with three or more dwelling units, in Group R-3 buildings as applicable in SBC 201 with two dwelling units and in Group R-4 buildings. Draft stopping shall be located above and in line with the dwelling unit and sleeping unit separations. Exceptions: 1. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. 2. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.2, provided that automatic sprinklers are also installed in the combustible concealed spaces. Other groups. In other groups, draft stopping shall be installed so that horizontal floor areas do not exceed 93 m2. Exception: Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. Draft stopping in attics. In combustible construction, draft stopping shall be installed to subdivide attic spaces and concealed roof spaces in the locations prescribed in Sections 4B.17.4.2 and 4B.17.4.3. Ventilation of concealed roof spaces shall be maintained in accordance with Section 7.3.2 of the SBC 201. 4B.17.4.1 Draft stopping materials. Materials utilized for draft stopping of attic spaces shall comply with Section 4B.17.3.1. 4B.17.4.1.1 Openings. Openings in the partitions shall be protected by self-closing doors with automatic latches constructed as required for the partitions. 4B.17.4.2 Groups R-1 and R-2. Draft stopping shall be provided in attics, mansards, overhangs or other concealed roof spaces of Group R-2 buildings with three or more dwelling units and in all Group R-1 buildings. Draft stopping shall be installed above, and in line with, sleeping unit and dwelling unit separation walls that do not extend to the underside of the roof sheathing above. 4B.17.4 SBC 801 2007 4/43 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.17.4.3 4B.17.5 Exceptions: 1. Where corridor walls provide a sleeping unit or dwelling unit separation, Draft stopping shall only be required above one of the corridor walls. 2. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. 3. In occupancies in Group R-2 that do not exceed four stories in height, the attic space shall be subdivided by draft stops into areas not exceeding 279 m2 or above every two dwelling units, whichever is smaller. 4. Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.2, provided that automatic sprinklers are also installed in the combustible concealed spaces. Other groups. Draft stopping shall be installed in attics and concealed roof spaces, such that any horizontal area does not exceed 279 m2. Exception: Draft stopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. Combustibles in concealed spaces in Type I or II construction. Combustibles shall not be permitted in concealed spaces of buildings of Type I or II construction. Exceptions: 1. Combustible materials in accordance with Section 4A.3. 2. Combustible materials complying with Section 4A.2 of the SBC 501. 3. Class A interior finish materials. 4. Combustible piping within partitions or enclosed shafts installed in accordance with the provisions of these code requirements. Combustible piping shall be permitted within concealed ceiling spaces where installed in accordance with the SBC 501 and the SBC 701. SECTION 4B.18 FIRE-RESISTANCE REQUIREMENTS FOR PLASTER 4B.18.1 Thickness of plaster. The minimum thickness of gypsum plaster or Portland cement plaster used in a fire-resistance-rated system shall be determined by the prescribed fire tests. The plaster thickness shall be measured from the face of the lath where applied to gypsum lath or metal lath. 4B.18.2 Plaster equivalents. For fire-resistance purposes, 13 mm of unsanded gypsum plaster shall be deemed equivalent to 20 mm of one-to-three gypsum sand plaster or 25 mm of Portland cement sand plaster. 4B.18.3 Noncombustible furring. In buildings of Type I and II construction, plaster shall be applied directly on concrete or masonry or on approved noncombustible plastering base and furring. 4B.18.4 Double reinforcement. Plaster protection more than 25 mm in thickness shall be reinforced with an additional layer of approved lath embedded at least 20 mm from the outer surface and fixed securely in place. Exception: Solid plaster partitions or where otherwise determined by fire tests. 4B.18.5 Plaster alternatives for concrete. In reinforced concrete construction for nonstructural considerations, gypsum plaster or Portland cement plaster is permitted to be substituted for 13 mm of the required poured concrete protection, except that a minimum thickness of 10 mm of poured concrete shall be provided in SBC 801 2007 4/44 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION reinforced concrete floors and 25 mm in reinforced concrete columns in addition to the plaster finish. However, for structural considerations, reinforced concrete shall be in accordance with SBC 304. SECTION 4B.19 THERMAL- AND SOUND-INSULATING MATERIALS 4B.19.1 General. Insulating materials, including facings such as vapor retarders and vaporpermeable membranes, similar coverings, and all layers of single and multilayer reflective foil insulations, shall comply with the requirements of this section. Where a flame spread index or a smoke-developed index is specified in this section, such index shall be determined in accordance with ASTM E 84. Any material that is subject to an increase in flame spread index or smoke-developed index beyond the limits herein established through the effects of age, moisture, or other atmospheric conditions shall not be permitted. Exceptions: 1. Fiberboard insulation shall comply with an approved method. 2. Foam plastic insulation shall comply with Chapter 11 of the SBC 201. 3. Duct and pipe insulation and duct and pipe coverings and linings in plenums shall comply with the SBC 501. 4B.19.2 Concealed installation. Insulating materials, where concealed as installed in buildings of any type of construction, shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450. Exception: Cellulose loose-fill insulation that is not spray applied, complying with the requirements of Section 4B.19.6, shall only be required to meet the smoke-developed index of not more than 450. Facings. Where such materials are installed in concealed spaces in buildings of Type III, IV or V construction, the flame spread and smoke-developed limitations do not apply to facings, coverings, and layers of reflective foil insulation that are installed behind and in substantial contact with the unexposed surface of the ceiling, wall or floor finish. 4B.19.2.1 4B.19.3 4B.19.3.1 Exposed installation. Insulating materials, where exposed as installed in buildings of any type of construction, shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450. Exception: Cellulose loose-fill insulation that is not spray applied complying with the requirements of Section 4B.19.6 shall only be required to meet the smokedeveloped index of not more than 450. Attic floors. Exposed insulation materials installed on attic floors shall have a critical radiant flux of not less than 0.12 watt per square centimeter when tested in accordance with ASTM E 970. 4B.19.4 Loose-fill insulation. Loose-fill insulation materials that cannot be mounted in the ASTM E 84 apparatus without a screen or artificial supports shall comply with the flame spread and smoke-developed limits of Sections 4B.19.2 and 4B.19.3 when tested in accordance with CAN/ULC S102.2. Exception: Cellulose loose-fill insulation shall not be required to comply with this test method, provided such insulation complies with the requirements of Section 4B.19.6. 4B.19.5 Roof insulation. The use of combustible roof insulation not complying with Sections 4B.19.2 and 4B.19.3 shall be permitted in any type of construction SBC 801 2007 4/45 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION provided it is covered with approved roof coverings directly applied thereto. 4B.19.6 Cellulose loose-fill insulation. Cellulose loose-fill insulation shall comply with CPSC 16 CFR, Part 1209 and CPSC 16 CFR, Part 1404. Each package of such insulating material shall be clearly labeled in accordance with CPSC 16 CFR, Part 1209 and CPSC 16 CFR, Part 1404. 4B.19.7 Insulation and covering on pipe and tubing. Insulation and covering on pipe and tubing shall have a flame spread index of not more than 25 and a smoke-developed index of not more than 450. SECTION 4B.20 PRESCRIPTIVE FIRE RESISTANCE 4B.20.1 4B.20.1.1 4B.20.1.2 4B.20.1.3 4B.20.1.4 4B.20.1.5 SBC 801 General. The provisions of this section contain prescriptive details of fireresistance-rated building elements. Examples of materials of construction and assemblies listed in Table 4B.20.1(1) for structural parts, Table 4B.20.1(2) for walls and partitions and Table 4B.20.1(3) for floor and roof systems shall be assumed to have the fire-resistance ratings prescribed therein. These tables should be extended to include the materials and assemblies available locally in the Kingdom of Saudi Arabia. Where materials that change the capacity for heat dissipation are incorporated into a fire-resistance-rated assembly, fire test results or other substantiating data shall be made available to the building official to show that the required fire-resistance-rating time period is not reduced. Thickness of protective coverings. The thickness of fire-resistant materials required for protection of structural members shall be not less than set forth in Table 4B.20.1(1), except as modified in this section. The figures shown shall be the net thickness of the protecting materials and shall not include any hollow space in back of the protection. Unit masonry protection of steel columns. Where required, metal ties shall be embedded in transverse joints of unit masonry for protection of steel columns. Such ties shall be as set forth in Table 4B.20.1(1) or be equivalent thereto. Reinforcement for cast-in-place concrete protection for steel columns. Cast-inplace concrete protection for steel columns shall be reinforced at the edges of such members with wire ties of not less than 5 mm in diameter wound spirally around the columns on a pitch of not more than 200 mm or by equivalent reinforcement. Plaster application. The finish coat is not required for plaster protective coatings where they comply with the design mix and thickness requirements of Tables 4B.20.1(1), 4B.20.1(2) and 4B.20.1(3). Bonded prestressed concrete tendons. For members having a single tendon or more than one tendon installed with equal concrete cover measured from the nearest surface, the cover shall not be less than that set forth in Table 4B.20.1(1). For members having multiple tendons installed with variable concrete cover, the average tendon cover shall not be less than that set forth in Table 4B.20.1(1), provided: 1. The clearance from each tendon to the nearest exposed surface is used to determine the average cover. 2. In no case can the clear cover for individual tendons be less than one-half of that set forth in Table 4B.20.1(1). A minimum cover of 20 mm for slabs and 25 mm for beams is required for any aggregate concrete. 3. For the purpose of establishing a fire-resistance rating, tendons having a clear covering less than that set forth in Table 4B.20.1(1) shall not contribute more 2007 4/46 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION than 50 percent of the required ultimate moment capacity for members less than 0.226 m2 in cross-sectional area and 65 percent for larger members. For structural design purposes, however, tendons having a reduced cover are assumed to be fully effective. SECTION 4B.21 CALCULATED FIRE RESISTANCE 4B.21.1 4B.21.1.1 General. The provisions of this section contain procedures by which the fire resistance of specific materials or combinations of materials is established by calculations. These procedures apply only to the information contained in this section and shall not be otherwise used. The calculated fire resistance of concrete, concrete masonry and clay masonry assemblies shall be permitted in accordance with ACI 216.1/TMS 0216.1. The calculated fire resistance of steel assemblies shall be permitted in accordance with Chapter 5 of ASCE/SFPE 29. Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in these code requirements, have the meanings shown herein. CERAMIC FIBER BLANKET. A mineral wool insulation material made of alumina-silica fibers and weighing 64 to 160 kg/m3. CONCRETE, CARBONATE AGGREGATE. Concrete made with aggregates consisting mainly of calcium or magnesium carbonate, such as limestone or dolomite, and containing 40 percent or less quartz, chert, or flint. CONCRETE, CELLULAR. A lightweight insulating concrete made by mixing a preformed foam with Portland cement slurry and having a dry unit weight of approximately 480 kg/m3. CONCRETE, LIGHTWEIGHT AGGREGATE. Concrete made with aggregates of expanded clay, shale, slag or slate or sintered fly ash or any natural lightweight aggregate meeting ASTM C 330 and possessing equivalent fireresistance properties and weighing 1,360 to 1,840 kg/m3. CONCRETE, PERLITE. A lightweight insulating concrete having a dry unit weight of approximately 480 kg/m3 made with perlite concrete aggregate. Perlite aggregate is produced from a volcanic rock which, when heated, expands to form a glass-like material of cellular structure. CONCRETE, SAND-LIGHTWEIGHT. Concrete made with a combination of expanded clay, shale, slag, slate, sintered fly ash, or any natural lightweight aggregate meeting ASTM C 330 and possessing equivalent fire-resistance properties and natural sand. Its unit weight is generally between 1,680 and 1,920 kg/m3. CONCRETE, SILICEOUS AGGREGATE. Concrete made with normal-weight aggregates consisting mainly of silica or compounds other than calcium or magnesium carbonate, which contains more than 40-percent quartz, chert, or flint. CONCRETE, VERMICULITE. A lightweight insulating concrete made with vermiculite concrete aggregate which is laminated micaceous material produced SBC 801 2007 4/47 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION by expanding the ore at high temperatures. When added to a Portland cement slurry the resulting concrete has a dry unit weight of approximately 480 kg/m3. GLASS FIBERBOARD. Fibrous glass roof insulation consisting of inorganic glass fibers formed into rigid boards using a binder. The board has a top surface faced with asphalt and kraft reinforced with glass fiber. MINERAL BOARD. A rigid felted thermal insulation board consisting of either felted mineral fiber or cellular beads of expanded aggregate formed into flat rectangular units. TABLE 4B.20.1(1) MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS STRUCTURAL PARTS TO BE PROTECTED ITEM NUMBER 1-1.1 1-1.2 1-1.3 1-1.4 1-1.5 1-1.6 1-2.1 1-3.1 1. Steel columns and all of primary trusses 1-3.2 1-3.3 1-3.4 1-4.1 1-5.1 1-6.1 SBC 801 INSULATING MATERIAL USED Carbonate, lightweight and sand-lightweight aggregate concrete, members 150 × 150 mm or greater (not including sandstone, granite and siliceous gravel)a Carbonate, lightweight and sand-lightweight aggregate concrete, members 200 × 200 mm or greater (not including sandstone, granite and siliceous gravel)a Carbonate, lightweight and sand-lightweight aggregate concrete, members 305 × 305 mm or greater (not including sandstone, granite and siliceous gravel)a Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 150 × 150 mm or greatera Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 200 × 200 mm or greatera Siliceous aggregate concrete and concrete excluded in Item 1-1.1, members 305 × 305 mm or greatera Clay or shale brick with brick and mortar filla 100 mm hollow clay tile in two 50 mm layers; 13 mm mortar between tile and column; 10 mm metal mesh 1.2 mm wire diameter in horizontal joints; tile filla 50 mm hollow clay tile; 20 mm mortar between tile and column; 10 mm metal mesh 1.2 mm wire diameter in horizontal joints; limestone concrete fill;a plastered with 20 mm gypsum plaster. 50 mm hollow clay tile with outside wire ties 2 mm diameter at each course of tile or 10 mm metal mesh 1.2 mm diameter wire in horizontal joints; limestone or trap-rock concrete fill1 extending 25 mm outside column on all sides 50 mm hollow clay tile with outside wire ties 2 mm diameter at each course of tile with or without concrete fill; 20 mm mortar between tile and column Cement plaster over metal lath wire tied to 20 mm cold-rolled vertical channels with 1.3 mm (No. 18 B.W. gage) wire ties spaced 75 to 150 mm on center. Plaster mixed 1: 2 ½ by volume, cement to sand Vermiculite concrete, 1:4 mix by volume over paperbacked wire fabric lath wrapped directly around column with additional 50 mm ×50 mm 1.6 mm/1.6 mm (No. 16/16 B.W. gage) wire fabric placed 10 mm from outer concrete surface. Wire fabric tied with 1.3 mm (No. 18 B.W. gage) wire spaced 150 mm on center for inner layer and 50 mm on center for outer layer Perlite or vermiculite gypsum plaster over metal lath wrapped around column and furred 32 mm from column flanges. Sheets lapped at ends and tied at 150 mm intervals with 1.3 mm (No. 18 B.W. gage) tie wire. Plaster pushed through to flanges (Continued) 2007 MINIMUM THICKNESS OF INSULATING MATERIAL FOR THE FOLLOWING FIRE-RESISTANCE PERIODS (mm) 4 3 2 1 hour hour hour hour 65 50 40 25 50 40 25 25 40 25 25 25 75 50 40 25 65 50 25 25 50 25 25 25 95 — — 60 100 — — — 75 — — — — — 75 — — — — 50 — — 65b 22 50 — — — 40 25 — — 4/48 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(1) – continued MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS STRUCTURAL PARTS TO BE PROTECTED ITEM NUMBER 1-6.2 1-6.3 1-6.4 1-6.5 1-7.1 1-7.2 1. Steel columns and all of primary trusses 1-7.3 1-8.1 2-1.1 2. Webs or flanges of steel beams and girders 2-1.2 2-2.1 SBC 801 INSULATING MATERIAL USED Perlite or vermiculite gypsum plaster over self-furring metal lath wrapped directly around column, lapped 25 mm and tied at 150 mm intervals with 1.3 mm (No. 18 B.W. gage) wire Perlite or vermiculite gypsum plaster on metal lath applied to 20 mm cold-rolled channels spaced 610 mm apart vertically and wrapped flatwise around column Perlite or vermiculite gypsum plaster over two layers of 13 mm plain full-length gypsum lath applied tight to column flanges. Lath wrapped with 25 mm hexagonal mesh of No. 20 gage wire and tied with doubled 0.9 mm diameter (No. 18 B.W. gage) wire ties spaced 585 mm on center. For three-coat work, the plaster mix for the second coat shall not exceed 46 Kg of gypsum to 0.07 m3 of aggregate for the 3-hour system Perlite or vermiculate gypsum plaster over one layer of 13 mm plain full-length gypsum lath applied tight to column flanges. Lath tied with doubled 1.3 mm (No. 18 B.W.gage) wire ties spaced 585 mm on center and scratch coat wrapped with 25 mm hexagonal mesh 0.9 mm (No. 20 B.W. gage) wire fabric. For three-coat work, the plaster mix for the second coat shall not exceed 46 Kg of gypsum to 0.07 m3 of aggregate Multiple layers of 13 mm gypsum wallboardc adhesivelyd secured to column flanges and successive layers. Wallboard applied without horizontal joints. Corner edges of each layer staggered. Wallboard layer below outer layer secured to column with doubled 1.3 mm (No. 18 B.W. gage) steel wire ties spaced 380 mm on center. Exposed corners taped and treated Three layers of 16 mm Type X gypsum wallboard.c First and second layer held in place by 3 mm diameter by 35 mm long ring shank nails with 8 mm diameter heads spaced 610 mm on center at corners. Middle layer also secured with metal straps at mid-height and 460 mm from each end, and by metal corner bead at each corner held by the metal straps. Third layer attached to corner bead with 25 mm long gypsum wallboard screws spaced 305 mm on center Three layers of 16 mm Type X gypsum wallboard,c each layer screw attached to 40 mm steel studs 0.45 mm thick (No. 25 carbon sheet steel gage) at each corner of column. Middle layer also secured with 1.3 mm (No. 18 B.W. gage) double-strand steel wire ties, 610 mm on center. Screws are No. 6 by 25 mm spaced 610 mm on center for inner layer, No. 6 by 40 mm spaced 305 mm on center for middle layer and No. 8 by 60 mm spaced 305 mm on center for outer layer Wood-fibered gypsum plaster mixed 1:1 by weight gypsum-to-sand aggregate applied over metal lath. Lath lapped 25 mm and tied 150 mm on center at all end, edges and spacers with 1.3 mm (No. 18 B.W. gage) steel tie wires. Lath applied over 13 mm spacers made of 20 mm furring channel with 50 mm legs bent around each corner. Spacers located 25 mm from top and bottom of member and a maximum of 1 m on center and wire tied with a single strand of 1.3 mm (No. 18 B.W. gage) steel tie wires. Corner bead tied to the lath at 150 mm on center along each corner to provide plaster thickness Carbonate, lightweight and sand-lightweight aggregate concrete (not including sandstone, granite and siliceous gravel) with 75 mm or finer metal mesh placed 25 mm from the finished surface anchored to the top flange and providing not less than 55 square millimeter of steel area per meter in each direction Siliceous aggregate concrete and concrete excluded in Item 2-1.1 with 75 mm or finer metal mesh placed 25 mm from the finished surface anchored to the top flange and providing not less than 55 square millimeter of steel area per meter in each direction Cement plaster on metal lath attached to 20 mm cold-rolled channels with 1.3 mm (No. 18 B.W. gage) wire ties spaced 75 to 150 mm on center. Plaster mixed 1: 2 ½ by volume, cement to sand 2007 MINIMUM THICKNESS OF INSULATING MATERIAL FOR THE FOLLOWING FIRE-RESISTANCE PERIODS (mm) 4 3 2 1 hour hour hour hour 45 35 25 — 40 — — — 65 50 — — — 50 — — — — 50 25 — — 50 — — 50 — — — — 40 — 50 40 25 25 65 50 40 25 — — 65b 22 4/49 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(1) – continued MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS STRUCTURAL PARTS TO BE PROTECTED ITEM NUMBER 2-3.1 2-4.1 2. Webs or flanges of steel beams and girders 2-4.2 3. Bonded pretensioned reinforcement in prestressed concretee 3-1.1 4. Bonded or unbonded posttensioned tendons in prestressed concretee,i SBC 801 4-1.1 4-1.2 INSULATING MATERIAL USED Vermiculite gypsum plaster on a metal lath cage, wire tied to 4.2 mm diameter (No. 8 B.W. gage) steel wire hangers wrapped around beam and spaced 405 mm on center. Metal lath ties spaced approximately 125 mm on center at cage sides and bottom Two layers of 16 mm Type X gypsum wallboardc are attached to Ushaped brackets spaced 610 mm on center. 0.45 mm thick (No. 25 carbon sheet steel gage) 40 mm deep by 25 mm galvanized steel runner channels are first installed parallel to and on each side of the top beam flange to provide a 13 mm clearance to the flange. The channel runners are attached to steel deck or concrete floor construction with approved fasteners spaced 305 mm on center. Ushaped brackets are formed from members identical to the channel runners. At the bent portion of the U-shaped bracket, the flanges of the channel are cut out so that 40 mm deep corner channels can be inserted without attachment parallel to each side of the lower flange. As an alternate, 500 mm thick (No. 24 carbon sheet steel gage) 25 mm × 50 mm runner and corner angles may be used in lieu of channels, and the web cutouts in the U-shaped brackets may be omitted. Each angle is attached to the bracket with 13 mm-long No. 8 self-drilling screws. The vertical legs of the U-shaped bracket are attached to the runners with one 13 mm long No. 8 self-drilling screw. The completed steel framing provides a 55 mm and 40 mm space between the inner layer of wallboard and the sides and bottom of the steel beam, respectively. The inner layer of wallboard is attached to the top runners and bottom corner channels or corner angles with 32 mm-long No. 6 self-drilling screws spaced 405 mm on center. The outer layer of wallboard is applied with 45 mm-long No. 6 self-drilling screws spaced 200 mm on center. The bottom corners are reinforced with metal corner beads Three layers of 16 mm Type X gypsum wallboardc attached to a steel suspension system as described immediately above utilizing the 0.45 mm thick (No. 25 carbon sheet steel gage) 25 mm × 50 mm lower corner angles. The framing is located so that a 55 mm and 50 mm space is provided between the inner layer of wallboard and the sides and bottom of the beam, respectively. The first two layers of wallboard are attached as described immediately above. A layer of 0.9 mm thick (No. 20 B.W. gage) 25 mm hexagonal galvanized wire mesh is applied under the soffit of the middle layer and up the sides approximately50 mm. The mesh is held in position with the No. 6 40 mm-long screws installed in the vertical leg of the bottom corner angles. The outer layer of wallboard is attached with No. 6 60 mmlong screws spaced 200 mm on center. One screw is also installed at the mid-depth of the bracket in each layer. Bottom corners are finished as described above Carbonate, lightweight, sand-lightweight and siliceousf aggregate concrete Beams or girders Solid slabsh Carbonate, lightweight, sand-lightweight and siliceousf aggregate concrete unrestrained members: Solid slabsh Beams and girdersj 200 mm wide greater than 305 mm wide Carbonate, lightweight, sand-lightweight and siliceous aggregate Restrained members:k Solid slabsh Beams and girdersj 200 mm wide greater than 300 mm wide (Continued) 2007 MINIMUM THICKNESS OF INSULATING MATERIAL FOR THE FOLLOWING FIRE-RESISTANCE PERIODS (mm) 4 3 2 1 hour hour hour hour — 22 — — — — 32 — — 50 — — 100g 75g 65 40 — 50 40 25 — 50 40 — 75 115 65 65 50 45 40 32 25 20 — 65 50 50 45 45 40 — — 4/50 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(1) – continued MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS STRUCTURAL PARTS TO BE PROTECTED 5. Reinforcing steel in reinforced concrete columns, beams, girders and trusses 6. Reinforcing steel in reinforced concrete joistsl 7. Reinforcing and tie rods in floor and roof slabsl a. b. c. d. e. f. g. h. i. j. k. l. ITEM NUMBER INSULATING MATERIAL USED MINIMUM THICKNESS OF INSULATING MATERIAL FOR THE FOLLOWING FIRE-RESISTANCE PERIODS (mm) 4 3 2 1 hour hour hour hour Carbonate, lightweight and sand-lightweight aggregate concrete, members 300 mm or larger, square or round. (Size limit does not apply to beams and girders monolithic with floors) 40 40 40 40 Siliceous aggregate concrete, members 300mm or larger, square or round. (Size limit does not apply to beams and girders monolithic with floors) 50 40 40 40 6-1.1 Carbonate, lightweight and sand-lightweight aggregate concrete. 32 32 25 20 6-1.2 Siliceous aggregate concrete 45 40 25 20 7-1.1 Carbonate, lightweight and sand-lightweight aggregate concrete. 25 25 20 20 7-1.2 Siliceous aggregate concrete 32 25 25 20 5-1.1 Reentrant parts of protected members to be filled solidly. Two layers of equal thickness with a 20 mm airspace in between. For all of the construction with gypsum wallboard described in Table 4B.20.1(1), gypsum base for veneer plaster of the same size, thickness and core type shall be permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard and the joints on the face layer are reinforced, and the entire surface is covered with a minimum of 1.6 mm gypsum veneer plaster. An approved adhesive qualified under ASTM E 119. Where lightweight or sand-lightweight concrete having an oven-dry weight of 1,760 kilogram per cubic meter or less is used, the tabulated minimum cover shall be permitted to be reduced 25 percent, except that in no case shall the cover be less than 20 mm in slabs or 40 mm in beams or girders. For solid slabs of siliceous aggregate concrete, increase tendon cover 20 percent. Adequate provisions against spalling shall be provided by U-shaped or hooped stirrups spaced not to exceed the depth of the member with a clear cover of 25 mm. Prestressed slabs shall have a thickness not less than that required in Table 4B.20.1(3) for the respective fire resistance time period. Fire coverage and end anchorages shall be as follows: Cover to the prestressing steel at the anchor shall be 13 mm greater than that required away from the anchor. Minimum cover to steel-bearing plate shall be 25 mm in beams and 20 mm in slabs. For beam widths between 200 mm and 305 mm, cover thickness shall be permitted to be determined by interpolation. Interior spans of continuous slabs, beams and girders shall be permitted to be considered restrained. For use with concrete slabs having a comparable fire endurance where members are framed into the structure in such a manner as to provide equivalent performance to that of monolithic concrete construction. SBC 801 2007 4/51 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(2) RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa,o,p MATERIAL ITEM NUMBER 1-1.1 1-1.2 1-1.3 1. Brick of clay or shale 1-2.1 2. Combination of clay brick and load-bearing hollow clay tile 3. Concrete masonry units 4. Solid concreteh, i 2-1.1 2-1.2 3-1.1f,g 3-1.2f,g 3-1.3f 3-1.4f,g 4-1.1 5-1.1 5-1.2 5. Glazed or unglazed facing tile, nonloadbearing 5-1.3 5-1.4 5-1.5 5-1.6 5-1.7 5-1.8 6-1.1 6. Solid gypsum plaster 6-1.2 SBC 801 CONSTRUCTION Solid brick of clay or shalec Hollow brick, not filled. Hollow brick unit wall, grout or filled with perlite, vermiculite or expanded shale aggregate. 100 mm nominal thick units at least 75 percent solid backed with a hat-shaped metal furring channel 20 mm thick formed from 500 mm sheet metal attached to the brick wall on 610 mm centers with approved fasteners, and 13 mm Type X gypsum wallboard attached to the metal furring strips with 25 mm-long Type S screws spaced 200 mm on center 100 mm solid brick and 100 mm tile (at least 40 percent solid) 100 mm solid brick and 200 mm tile (at least 40 percent solid) Expanded slag or pumice Expanded clay, shale or slate Limestone, cinders or air-cooled slag Calcareous or siliceous gravel Siliceous aggregate concrete Carbonate aggregate concrete Sand-lightweight concrete Lightweight concrete One 50 mm unit cored 15 percent maximum and one 100 mm unit cored 25 percent maximum with 20 mm mortar-filled collar joint. Unit positions reversed in alternate courses One 50 mm unit cored 15 percent maximum and one 100 mm unit cored 40 percent maximum with 20 mm mortar-filled collar joint. Unit positions side with 20 mm gypsum plaster. Two wythes tied together every fourth course with 0.8 mm (No. 22 gage) corrugated metal ties One unit with three cells in wall thickness, cored 29 percent maximum One 50 mm unit cored 22 percent maximum and one 100 mm unit cored 41 percent maximum with 6 mm mortar-filled collar joint. Two wythes tied together every third course with 0.8 mm (No. 22 galvanized sheet steel gage) corrugated metal ties One 100 mm unit cored 25 percent maximum with 20 mm gypsum plaster on one side One 100 mm unit with two cells in wall thickness, cored 22 percent maximum One 100 mm unit cored 30 percent maximum with 20 mm vermiculite gypsum plaster on one side One 100 mm unit cored 39 percent maximum with 20 mm gypsum plaster on one side 20 mm by 1.4 mm (No. 16 carbon sheet steel gage) vertical cold-rolled channels, 405 mm on center with 1.2 kilogram flat metal lath applied to one face and tied with 1.3 mm (No. 18 B.W. Gage) wire at 150 mm spacing. Gypsum plaster each side mixed 1:2 by weight, gypsum to sand aggregate 20 mm by 1.4 mm (No. 16 carbon sheet steel gage) cold-rolled channels 405 mm on center with metal lath applied to one face and tied with 1.3 mm (No. 18 B.W. gage) wire at 150 mm spacing. Perlite or vermiculite gypsum plaster each side. For three-coat work, the plaster mix for the second coat shall not exceed 46 kilograms of gypsum to 0.07 m3 of aggregate for the 1-hour system (Continued) 2007 MINIMUM FINISHED THICKNESS FACE-TO-FACEb (mm) 4 3 2 1 hour hour hour hour 150 125 95 70 125 110 85 60 170 — — 140 — 110 125d 75 — 200 — — 300 — — — 120 130 150 160 180 170 135 130 100 110 125 135 160 145 115 110 80 90 100 105 125 115 95 90 55 65 70 70 90 80 70 65 — 160 — — — 170 — — — — 150 — — — 150 — — — 120 — — — — 100 — — 115 — — — — 115 — — — 50d 65d 50d 4/52 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(2) – continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa,o,p MATERIAL ITEM NUMBER 6-1.3 6-2.1 6. Solid gypsum plaster 6-2.2 6-2.3 7. Solid perlite and portland cement 7-1.1 8. Solid neat wood fibered gypsum plaster 8-1.1 9. Solid wallboard partition 9-1.1 10-1.1 10. Hollow (studless) gypsum wallboard partition 10-1.2 11-1.1 11. Noncombustible studs—interior partition with plaster each side 11-1.2 11-1.3 SBC 801 CONSTRUCTION 20 mm by 1.4 mm (No. 16 carbon sheet steel gage) vertical cold-rolled channels, 400 mm on center with 10 mm gypsum lath applied to one face and attached with sheet metal clips. Gypsum plaster each side mixed 1:2 by weight, gypsum to sand aggregate Studless with 13 mm full-length plain gypsum lath and gypsum plaster each side. Plaster mixed 1:1 for scratch coat and 1:2 for brown coat, by weight, gypsum to sand aggregate Studless with 13 mm full-length plain gypsum lath and perlite or vermiculite gypsum plaster each side Studless partition with 10 mm rib metal lath installed vertically adjacent edges tied 150 mm on center with 1.3 mm (No. 18 gage) wire ties, gypsum plaster each side mixed 1:2 by weight, gypsum to sand aggregate Perlite mixed in the ratio of 0.08 cubic meters to 46 kilograms of portland cement and machine applied to stud side of 40 mm mesh by 1.5-mm (No. 17 B.W. gage) paper-backed woven wire fabric lath wire-tied to 100 mm-deep steel trussed wirej studs 405 mm on center. Wire ties of 1.3 mm (No. 18 B.W. gage) galvanized steel wire 150 mm on center vertically 20 mm by 1.4 mm (No. 16 carbon sheet steel gage) cold-rolled channels, 305 mm on center with 1.2 kilogram flat metal lath applied to one face and tied 1.3 mm (No. 18 B.W. gage) wire at 150 mm spacing. Neat gypsum plaster applied each side One full-length layer 13 mm Type X gypsum wallboarde laminated to each side of 25 mm fulllength V-edge gypsum coreboard with approved laminating compound. Vertical joints of face layer and coreboard staggered at least 75 mm One full-length layer of 16 mm Type X gypsum wallboarde attached to both sides of wood or metal top and bottom runners laminated to each side of 25 mm× 150 mm full-length gypsum coreboard ribs spaced 610 mm on center with approved laminating compound. Ribs centered at vertical joints of face plies and joints staggered 610 mm in opposing faces. Ribs may be recessed 150 mm from the top and bottom 25 mm regular gypsum V-edge full-length backing board attached to both sides of wood or metal top and bottom runners with nails or 40 mm drywall screws at 610 mm on center. Minimum width of runners 40 mm. Face layer of 13 mm regular fulllength gypsum wallboard laminated to outer faces of backing board with approved laminating compound 85 mm × 1.1 mm (No. 18 carbon sheet steel gage) steel studs spaced 610 mm on center. 16 mm gypsum plaster on metal lath each side mixed 1:2 by weight, gypsum to sand aggregate 85 mm × 1.4 mm (No. 16 carbon sheet steel gage) approved nailablek studs spaced 610 mm on center. 16 mm neat gypsum wood-fibered plaster each side over 10 mm rib metal lath nailed to studs with 6d common nails, 200 mm on center. Nails driven 32 mm and bent over 100 mm × 1.1 mm (No. 18 carbon sheet steel gage) channel-shaped steel studs at 405 mm on center. On each side approved resilient clips pressed onto stud flange at 405 mm vertical spacing, 6 mm pencil rods snapped into or wire tied onto outer loop of clips, metal lath wire-tied to pencil rods at 150 mm intervals, 50 mm perlite gypsum plaster, each side (Continued) 2007 MINIMUM FINISHED THICKNESS FACE-TO-FACEb (mm) 4 3 2 1 hour hour hour hour — — — 50d — — — 50d — — 65d 50d — — — 50d — — 80d — — — 50d — — — 50d — — — — 60d — — 115d — — — — 120d — — 140 — — 195d — — 4/53 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(2) – continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa,o,p MATERIAL ITEM NUMBER 11-1.4 12-1.1l, m 12. Wood studs interior partition with plaster each side 12-1.2l 12-1.3l 12-1.4l 13-1.1 13. Noncombustible studs—interior partition with gypsum wallboard each side 13-1.2 13-1.3 14.Wood studs— interior partition with gypsum Wallboard each side SBC 801 14-1.1h, m CONSTRUCTION 65 mm × 1.1 mm (No. 18 carbon sheet steel gage) steel studs spaced 405 mm on center. Wood fibered gypsum plaster mixed 1:1 by weight gypsum to sand aggregate applied on 0.34-kilograms metal lath wire tied to studs, each side. 20 mm plaster applied over each face, including finish coat 50 mm × 100 mm wood studs 405 mm on center with 16 mm gypsum plaster on metal lath. Lath attached by 4d common nails bent over or No. 14 gage by 32 mm by 20 mm crown width staples spaced 150 mm on center. Plaster mixed 1:1 1½ for scratch coat and 1:3 for brown coat, by weight, gypsum to sand aggregate 50 × 100 mm wood studs 405 mm on center with metal lath and 22 mm neat wood-fibered gypsum plaster each side. Lath attached by 6d common nails, 180 mm on center. Nails driven 32 mm and bent over 50 mm × 100 mm wood studs 405 mm on center with 10 mm perforated or plain gypsum lath and 13 mm gypsum plaster each side. Lath nailed with 30 mm by No. 13 gage by 8 mm head plasterboard blued nails, 100 mm on center. Plaster mixed 1:2 by weight, gypsum to sand aggregate 50 mm × 100 mm wood studs 405 mm on center with 10 mm Type X gypsum lath and 13 mm gypsum plaster each side. Lath nailed with 30 mm by No. 13 gage by 8 mm head plasterboard blued nails, 125 mm on center. Plaster mixed 1:2 by weight, gypsum to sand aggregate 0.45 mm (No. 25 carbon sheet steel gage) channelshaped studs 610 mm on center with one full-length layer of 16 mm Type X gypsum wallboarde applied vertically attached with 25 mm long No. 6 drywall screws to each stud. Screws are 200 mm on center around the perimeter and 305 mm on center on the intermediate stud. The wallboard may be applied horizontally when attached to 90 mm studs and the horizontal joints are staggered with those on the opposite side. Screws for the horizontal application shall be 200 mm on center at vertical edges and 305 mm on center at intermediate studs 0.45 mm (No. 25 carbon sheet steel gage) channelshaped studs 635 mm on center with two full-length layers of 13 mm Type X gypsum wallboarde applied vertically each side. First layer attached with 25 mm-long, No. 6 drywall screws, 200 mm on center around the perimeter and 305 mm on center on the intermediate stud. Second layer applied with vertical joints offset one stud space from first layer using 40 mm long, No. 6 drywall screws spaced 230 mm on center along vertical joints, 305 mm on center at intermediate studs and 640 mm on center along top and bottom runners 1.4 mm (No. 16 carbon sheet steel gage) approved nailable metal studse 610 mm on center with fulllength 16 mm Type X gypsum wallboarde applied vertically and nailed 180 mm on center with 6d cement-coated common nails. Approved metal fastener grips used with nails at vertical butt joints along studs 50 mm × 100 mm wood studs 405 mm on center with two layers of 10 mm regular gypsum wallboarde each side, 4d coolern or wallboardn nails at 200 mm on center first layer, 5d coolern or wallboardn nails at 200 mm on center second layer with laminating compound between layers, joints staggered. First layer applied full length vertically, second layer applied horizontally or vertically (Continued) 2007 MINIMUM FINISHED THICKNESS FACE-TO-FACEb (mm) 4 3 2 1 hour hour hour hour — — 110d — — — — 130 — — 140d — — — — 135 — — — 135 — — — 75d — — 90d — — — — 125 — — — 125 4/54 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(2) – continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa,o,p MATERIAL ITEM NUMBER 14-1.2l, m 14-1.3l, m 14-1.4l 14.Wood studs— interior partition with gypsum Wallboard each side 14-1.5l, m 14-1.6l 15-1.1l, m 15-1.2l, m 15. Exterior or interior walls 15-1.3l, m 15-1.4 SBC 801 CONSTRUCTION 50 mm × 100 mm wood studs 405 mm on center with two layers 13 mm regular gypsum wallboarde applied vertically or horizontally each sidek, joints staggered. Nail base layer with 5d coolern or wallboardn nails at 200 mm on center face layer with 8d coolern or wallboardn nails at 200 mm on center 50 mm × 100 mm wood studs 610 mm on center with 16 mm Type X gypsum wallboarde applied vertically or horizontally nailed with 6d coolern or wallboardn nails at 180 mm on center with end joints on nailing members. Stagger joints each side 50 mm × 100 mm fire-retardant-treated wood studs spaced 610 mm on center with one layer of 16 mm Type X gypsum wallboarde applied with face paper grain (long dimension) parallel to studs. Wallboard attached with 6d coolern or wallboardn nails at 180 mm on center 50 mm × 100 mm wood studs 405 mm on center with two layers 16 mm Type X gypsum wallboarde each side. Base layers applied vertically and nailed with 6d coolern or wallboardn nails at 230 mm on center. Face layer applied vertically or horizontally and nailed with 8d coolern or wallboardn nails at 180 mm on center. For nail-adhesive application, base layers are nailed 150 mm on center. Face layers applied with coating of approved wallboard adhesive and nailed 305 mm on center 50 mm × 75 mm fire-retardant-treated wood studs spaced 610 mm on center with one layer of 16 mm Type X gypsum wallboarde applied with face paper grain (long dimension) at right angles to studs. Wallboard attached with 6d cement-coated box nails spaced 180 mm on center Exterior surface with 20 mm drop siding over 13 mm gypsum sheathing on 50 mm × 100 mm wood studs at 405 mm on center, interior surface treatment as required for 1-hour-rated exterior or interior 50 mm × 100 mm wood stud partitions. Gypsum sheathing nailed with 45 mm by No. 11 gage by 11 mm head galvanized nails at 200 mm on center. Siding nailed with 7d galvanized smooth box nails 50 mm × 100 mm wood studs 405 mm on center with metal lath and 20 mm cement plaster on each side. Lath attached with 6d common nails 180 mm on center driven to 25 mm minimum penetration and bent over. Plaster mix 1:4 for scratch coat and 1:5 for brown coat, by volume, cement to sand 50 mm × 100 mm wood studs 405 mm on center with 22 mm cement plaster (measured from the face of studs) on the exterior surface with interior surface treatment as required for interior wood stud partitions in this table. Plaster mix 1:4 for scratch coat and 1:5 for brown coat, by volume, cement to sand 90 mm No. 16 gage noncombustible studs 405 mm on center with 22 mm cement plaster (measured from the face of the studs) on the exterior surface with interior surface treatment as required for interior, nonbearing, noncombustible stud partitions in this table. Plaster mix 1:4 for scratch coat and 1:5 for brown coat, by volume, cement to sand (Continued) 2007 MINIMUM FINISHED THICKNESS FACE-TO-FACEb (mm) 4 3 2 1 hour hour hour hour — — — 140 — — — 120 — — — 120d — — 150 — — — — 90d — — — Varies — — — 135 — — — Varies — — — Variesd 4/55 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(2) – continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa,o,p MATERIAL ITEM NUMBER 15-1.5m 15. Exterior or interior walls 15-1.6l, m 15-1.7l, m SBC 801 CONSTRUCTION 60 mm × 95 mm clay face brick with cored holes over 13 mm gypsum sheathing on exterior surface of 50 mm × 100 mm wood studs at 405 mm on center and two layers 16 mm Type X gypsum wallboarde on interior surface. Sheathing placed horizontally or vertically with vertical joints over studs nailed 150 mm on center with 45 mm × No. 11 gage by 11 mm head galvanized nails. Inner layer of wallboard placed horizontally or vertically and nailed 200 mm on center with 6d coolern or wallboardn nails. Outer layer of wallboard placed horizontally or vertically and nailed 200 mm on center with 8d coolern or wallboardn nails. All joints staggered with vertical joints over studs. Outer layer joints taped and finished with compound. Nail heads covered with joint compound. 0.9 mm (No. 20 galvanized sheet gage) corrugated galvanized steel wall ties 20 mm by 170 mm attached to each stud with two 8d coolern or wallboardn nails every sixth course of bricks 50 mm × 150 mm fire-retardant-treated wood studs 405 mm on center. Interior face has two layers of 16 mm Type X gypsum with the base layer placed vertically and attached with 6d box nails 305 mm on center. The face layer is placed horizontally and attached with 8d box nails 200 mm on center at joints and 305 mm on center elsewhere. The exterior face has a base layer of 16 mm Type X gypsum sheathing placed vertically with 6d box nails 200 mm on center at joints and 305 mm on center elsewhere. An approved building paper is next applied, followed by self-furred exterior lath attached with 65 mm, No. 12 gage galvanized roofing nails with a 10 mm diameter head and spaced 150 mm on center along each stud. Cement plaster consisting of a 13 mm brown coat is then applied. The scratch coat is mixed in the proportion of 1:3 by weight, cement to sand with 4.5 kilograms of hydrated lime and 1.5 kilograms of approved additives or admixtures per sack of cement. The brown coat is mixed in the proportion of 1:4 by weight, cement to sand with the same amounts of hydrated lime and approved additives or admixtures used in the scratch coat 50 mm × 150 mm wood studs 405 mm on center. The exterior face has a layer of 16 mm Type X gypsum sheathing placed vertically with 6d box nails 200 mm on center at joints and 305 mm on center elsewhere. An approved building paper is next applied, followed by 25 mm by No. 18 gage self-furred exterior lath attached with 8d by 65 mm long galvanized roofing nails spaced 150 mm on center along each stud. Cement plaster consisting of a 13 mm scratch coat, a bonding agent and a 13 mm brown coat and a finish coat is then applied. The scratch coat is mixed in the proportion of 1:3 by weight, cement to sand with 4.5 kilograms of hydrated lime and 1.5 kilograms of approved additives or admixtures per sack of cement. The brown coat is mixed in the proportion of 1:4 by weight, cement to sand with the same amounts of hydrated lime and approved additives or admixtures used in the scratch coat. The interior is covered with 10 mm gypsum lath with 25 mm hexagonal mesh of 0.9 mm (No. 20 B.W. gage) woven wire lath furred out 8 mm and 25 mm perlite or vermiculite gypsum plaster. Lath nailed with 30 mm by No. 13 gage by (Continued) 2007 MINIMUM FINISHED THICKNESS FACE-TO-FACEb (mm) 4 3 2 1 hour hour hour hour — — 250 — — — 210 — — — 215 — 4/56 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(2) – continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa,o,p MATERIAL ITEM NUMBER 15-1.8l,m 15. Exterior or interior walls 15-1.9 15-1.10 SBC 801 CONSTRUCTION 8 mm head plasterboard glued nails spaced 125 mm on center. Mesh attached by 45 mm by No. 12 gage by 10 mm head nails with 10 mm furrings, spaced 200 mm on center. The plaster mix shall not exceed 46 kilograms of gypsum to 0.07 m3 of aggregate 50 mm × 150 mm wood studs 405 mm on center. The exterior face has a layer of 16 mm Type X gypsum sheathing placed vertically with 6d box nails 200 mm on center at joints and 305 mm on center elsewhere. An approved building paper is next applied, followed by 40 mm by No. 17 gage self-furred exterior lath attached with 8d by 65 mm long galvanized roofing nails spaced 150 mm on center along each stud. Cement plaster consisting of a 13 mm scratch coat, and a 13 mm brown coat is then applied. The plaster may be placed by machine. The scratch coat is mixed in the proportion of 1:4 by weight, plastic cement to sand. The brown coat is mixed in the proportion of 1:5 by weight, plastic cement to sand. The interior is covered with 10 mm gypsum lath with 25 mm hexagonal mesh of No. 20 gage woven wire lath furred out 8 mm and 25 mm perlite or vermiculite gypsum plaster. Lath nailed with 30 mm by No. 13 gage by 8 mm head plasterboard glued nails spaced 125 mm on center. Mesh attached by 45 mm by No. 12 gage by 10 mm head nails with 10 mm furrings, spaced 200 mm on center. The plaster mix shall not exceed 46 kilograms of gypsum to 0.07 cubic meters of aggregate 100 mm No. 18 gage, nonload-bearing metal studs, 405 mm on center, with 25 mm portland cement lime plaster [measured from the back side of the 0.34-kilograms expanded metal lath] on the exterior surface. Interior surface to be covered with 25 mm of gypsum plaster on 0.34 kilograms expanded metal lath proportioned by weight – 1:2 or scratch coat, 1:3 for brown, gypsum to sand. Lath on one side of the partition fastened to 6 mm diameter pencil rods supported by No. 20 gage metal clips, located 405 mm on center vertically, on each stud. 75 mm thick mineral fiber insulating batts friction fitted between the studs Steel studs 1.5 mm thick, 100 mm deep or 150 mm at 405 mm or 610 mm centers, with 13 mm Glass Fiber Reinforced Concrete (GFRC) on the exterior surface. GFRC is attached with flex anchors at 610 mm on center, with 125 mm leg welded to studs with two 13 mm-long flare-bevel welds, and 100 mm foot attached to the GFRC skin with 16 mm thick GFRC bonding pads that extend 65 mm beyond the flex anchor foot on both sides. Interior surface to have two layers of 13 mm Type X gypsum wallboarde The first layer of wallboard to be attached with 25 mm-long Type S buglehead screws spaced 610 mm on center and the second layer is attached with 40 mm-long Type S screws spaced at 305 mm on center. Cavity is to be filled with 125 mm of 65 kg/m3 (nominal) mineral fiber batts. GFRC has 40 mm returns packed with mineral fiber and caulked on the exterior (Continued) 2007 MINIMUM FINISHED THICKNESS FACE-TO-FACEb (mm) 4 3 2 1 hour hour hour hour — — 215 — — — 165d — — — 165 — 4/57 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(2) – continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa,o,p MATERIAL ITEM NUMBER 15-1.11 15-1.12q 15-1.13q 15. Exterior or interior walls 15-1.14q 15-1.15q 15-1.16q SBC 801 CONSTRUCTION Steel studs 1.5 mm thick, 100 mm deep or 150 mm at 405 mm or 610 mm centers, respectively, with 13 mm Glass Fiber Reinforced Concrete (GFRC) on the exterior surface. GFRC is attached with flex anchors at 610 mm on center, with 125 mm leg welded to studs with two 13 mm-long flare-bevel welds, and 100 mm foot attached to the GFRC skin with 16 mm-thick GFRC bonding pads that extend 65 mm beyond the flex anchor foot on both sides. Interior surface to have one layer of 16 mm Type X gypsum wallboarde, attached with 32 mm-long Type S buglehead screws spaced 305 mm on center. Cavity is to be filled with 125 mm of 65 kg/m3 (nominal) mineral fiber batts. GFRC has 40 mm returns packed with mineral fiber and caulked on the exterior 50 mm × 150 mm wood studs at 405 mm with double top plates, single bottom plate; interior and exterior sides covered with 16 mm Type X gypsum wallboard, 1.22 m wide, applied horizontally or vertically with vertical joints over studs, and fastened with 60 mm Type S drywall screws, spaced 305 mm on center. Cavity filled with 140 mm mineral wool insulation 50 mm × 150 mm wood studs at 405 mm with double top plates, single bottom plate; interior and exterior sides covered with 16 mm Type X gypsum wallboard, 1.22 m wide, applied horizontally or vertically with vertical joints over studs, and fastened with 60 mm Type S drywall screws, spaced 180 mm on center. Cavity to be filled with 140 mm mineral wool insulation minimum 41 kg/m3 (nominal) 50 mm × 100 mm wood studs at 405 mm with double top plates, single bottom plate; interior and exterior sides covered with 16 mm Type X gypsum wallboard and sheathing, respectively, 1.22 m wide, applied horizontally or vertically with vertical joints over studs, and fastened with 60 mm Type S drywall screws, spaced 305 mm on center. Cavity to be filled with 90 mm mineral wool insulation 50 mm × 100 mm wood studs at 405 mm with double top plates, single bottom plate; interior sides covered with 16 mm Type X gypsum wallboard, 1.22 m wide, applied horizontally unblocked, and fastened with 60 mm Type S drywall screws, spaced 305 mm on center, wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound. Exterior covered with 10 mm wood structural panels (oriented strand board), applied vertically, horizontal joints blocked and fastened with 6d common nails (bright) – 305 mm on center in the field, 150 mm on center panel edges. Cavity to be filled with 90 mm mineral wool insulation. Rating established for exposure from interior side only 50 mm × 150 mm wood studs at 405 mm centers with double top plates, single bottom plate; interior side covered with 16 mm Type X gypsum wallboard, 1.22 m wide, applied horizontally or vertically with vertical joints over studs and fastened with 60 mm Type S drywall screws, spaced 305 mm on center, exterior side covered with 11 mm wallboard joints covered with paper tape and joint compound, fastener heads covered with joint (Continued) 2007 MINIMUM FINISHED THICKNESS FACE-TO-FACEb (mm) 4 3 2 1 hour hour hour hour — — — 155 — — — 170 — — — 170 — — — 120 — — — 115 — — — 165 4/58 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(2) – continued RATED FIRE-RESISTANCE PERIODS FOR VARIOUS WALLS AND PARTITIONSa,o,p MATERIAL ITEM NUMBER 15-1.17q 16. Exterior walls rated for fire resistance from the inside only in accordance with Section 4B.4.5. a. b. c. d. e. f. g. h. i. j. k. l. m. n. o. p. q. 16-1.1q CONSTRUCTION compound; wood structural panels (oriented strand board) fastened with 6d common nails (bright) spaced 305 mm on center in the field and 150 mm on center along the panel edges. Cavity to be filled with 140 mm mineral wool insulation. Rating established from the gypsum-covered side only 50 mm × 150 mm wood studs at 610 mm centers with double top plates, single bottom plate; interior and exterior side covered with two layers of 16 mm Type X gypsum wallboard, 1.22 m wide, applied horizontally with vertical joints over studs. Base layer fastened with 60 mm. Type S drywall screws, spaced 610 mm on center, and face layer fastened with Type S drywall screws, spaced 200 mm on center, wallboard joints covered with paper tape and joint compound, fastened heads covered with joint compound. Cavity to be filled with 140 mm mineral wool insulation 50 mm × 100 mm wood studs at 405 mm centers with double top plates, single bottom plate; interior side covered with 16 mm Type X gypsum wallboard, 1.22 m wide, applied horizontally unblocked, and fastened with 60 mm. Type S drywall screws, spaced 305 mm on center, wallboard joints covered with paper tape and joint compound, fastener heads covered with joint compound. Exterior covered with 10 mm wood structural panels (oriented strand board), applied vertically, horizontal joints blocked and fastened with 6d common nails (bright) – 305 mm on center in the field, and 150 mm on center panel edges. Cavity to be filled with 90 mm mineral wool insulation. Rating established for exposure from interior side only MINIMUM FINISHED THICKNESS FACE-TO-FACEb (mm) 4 3 2 1 hour hour hour hour — — 195 — — — — 115 Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood framing. Thickness shown for brick and clay tile are nominal thicknesses unless plastered, in which case thicknesses are net. Thickness shown for concrete masonry and clay masonry is equivalent thickness defined in Section 4B.21.3.1 for concrete masonry and Section 4B.21.4.1.1 for clay masonry. Where all cells are solid grouted or filled with silicone-treated perlite loose-fill insulation; vermiculite loose-fill insulation; or expanded clay, shale or slate lightweight aggregate, the equivalent thickness shall be the thickness of the block or brick using specified dimensions as defined in SBC 305. Equivalent thickness may also include the thickness of applied plaster and lath or gypsum wallboard, where specified. For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is at least 75 percent of the gross cross-sectional area measured in the same plane. Shall be used for nonbearing purposes only. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size, thickness and core type shall be permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and the entire surface is covered with a minimum of 1.6 mm gypsum veneer plaster. The fire-resistance time period for concrete masonry units meeting the equivalent thicknesses required for a 2-hour fire-resistance rating in Item 3, and having a thickness of not less than 195 mm is 4 hours when cores which are not grouted are filled with silicone-treated perlite loose-fill insulation; vermiculite loose-fill insulation; or expanded clay, shale or slate lightweight aggregate, sand or slag having a maximum particle size of 10 mm. The fire-resistance rating of concrete masonry units composed of a combination of aggregate types or where plaster is applied directly to the concrete masonry shall be determined in accordance with ACI 216.1/TMS 216. Lightweight aggregates shall have a maximum combined density of 1,040 kilograms per cubic meter. See also Note b. The equivalent thickness shall be permitted to include the thickness of cement plaster or 1.5 times the thickness of gypsum plaster applied in accordance with the requirements of Chapter 10 of the SBC 201. Concrete walls shall be reinforced with horizontal and vertical temperature reinforcement as required by SBC 304. Studs are welded truss wire studs with 4.5 mm (No. 7 B.W. gage) flange wire and 4.5 mm (No. 7 B.W. gage) truss wires. Nailable metal studs consist of two channel studs spot welded back to back with a crimped web forming a nailing groove. Wood structural panels shall be permitted to be installed between the fire protection and the wood studs on either the interior or exterior side of the wood frame assemblies in this table, provided the length of the fasteners used to attach the fire protection are increased by an amount at least equal to the thickness of the wood structural panel. The design stress of studs shall be reduced to 78 percent of allowable F’c with the maximum not greater than 78 percent of the calculated stress with studs having a slenderness ratio le/d of 33. For properties of cooler or wallboard nails, see ASTM C 514, ASTM C 547 or ASTM F 1667. Generic fire-resistance ratings (those not designated as PROPRIETARY in the listing) in the GA 600 shall be accepted as if herein listed. NCMA TEK 5-8, shall be permitted for the design of fire walls. The design stress of studs shall be equal to a maximum of 100 percent of the allowable F’c calculated in accordance with Section 2306 of the Saudi Building Code. SBC 801 2007 4/59 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(3) MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa, q FLOOR OR ROOF CONSTRUCTION 1. Siliceous aggregate concrete 2. Carbonate aggregate concrete 3. Sand-lightweight concrete 4. Lightweight concrete ITEM NUMBER 1-1.1 2-1.1 3-1.1 4-1.1 5-1.1 5. Reinforced concrete 5-2.1 6-1.1 6-2.1 6. Steel joists constructed with a poured reinforced concrete slab on metal lath forms or steel form unitsd,e 6-3.1 6-4.1 SBC 801 CEILING CONSTRUCTION Slab (no ceiling required). Minimum cover over nonprestressed reinforcement shall not be less than 20 mmb Slab with suspended ceiling of vermiculite gypsum plaster over metal lath attached to 20 mm cold-rolled channels spaced 305 mm on center. Ceiling located 150 mm minimum below joists 10 mm Type X gypsum wallboardc attached to 0.45 mm (No. 25 carbon sheet steel gage) by 22 mm deep by 65 mm hatshaped galvanized steel channels with 25 mm-long No. 6 screws. The channels are spaced 610 mm on center, span 890 mm and are supported along their length at 890 mm intervals by 0.8-millimeter (No. 21 galvanized sheet gage) galvanized steel flat strap hangers having formed edges that engage the lips of the channel. The strap hangers are attached to the side of the concrete joists with 4 mm by 32 mm long power-driven fasteners. The wallboard is installed with the long dimension perpendicular to the channels. All end joints occur on channels and supplementary channels are installed parallel to the main channels, 305 mm each side, at end joint occurrences. The finished ceiling is located approximately 305 mm below the soffit of the floor slab Gypsum plaster on metal lath attached to the bottom cord with single 1.6 mm (No. 16 gage) or doubled 1.3 mm (No. 18 gage) wire ties spaced 150 mm on center. Plaster mixed 1:2 for scratch coat, 1:3 for brown coat, by weight, gypsum-to-sand aggregate for 2-hour system. For 3-hour system plaster is neat Vermiculite gypsum plaster on metal lath attached to the bottom chord with single 1.6 mm (No.16 gage) or doubled 1.3 mm (No. 18 B.W. gage) wire ties 150 mm on center Cement plaster over metal lath attached to the bottom chord of joists with single 1.6 mm (No.16 gage) or doubled 1.3 mm (No. 18 B.W. gage) wire ties spaced 150 mm on center. Plaster mixed 1:2 for scratch coat, 1:3 for brown coat for 1-hour system and 1:1 for scratch coat, 1:1 ½ for brown coat for 2-hour system, by weight, cement to sand Ceiling of 16 mm Type X wallboardc attached to 22 mm deep by 65 mm by 0.5 mm (No. 25 carbon sheet steel gage) hat-shaped furring channels 305 mm on center with 25 mm long No. 6 wallboard screws at 200 mm on center. Channels wire tied to bottom chord of joists with doubled 1.3 mm (No. 18 B.W. gage) wire or suspended below joists on wire hangersg (Continued) 2007 THICKNESS OF MINIMUM FLOOR OR ROOF THICKNESS OF SLAB CEILING (mm) (mm) 4 3 2 1 4 3 2 1 hour hour hour hour hour hour hour hour 180 160 125 90 — — — — 170 145 115 80 — — — — 135 130 115 110 95 90 70 65 — — — — — — — — 75 50 — — 25 20 — — — — 65 — — — 16 — — — 65 60 — — 20 16 — 50 — — — 16 — — — — — 50 — — — 16f — — 65 — — — 16 — 4/60 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(3) – continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa, q FLOOR OR ROOF CONSTRUCTION 6. Steel joists constructed with a poured reinforced concrete slab on metal lath forms or steel form unitsd,e 7. Reinforced concrete slabs and joists with hollow clay tile fillers laid end to end in rows 65 mm or more apart; reinforcement placed between rows and concrete cast around and over tile. 8. Steel joists constructed with a reinforced concrete slab on top poured on a 13 mm deep steel deck.e ITEM NUMBER 6-5.1 7-1.1 7-1.2 8-1.1 9. 75 mm deep cellular steel deck with concrete slab on top. Slab thickness measured to top. 9-1.1 10. 40 mm-deep steel roof deck on steel framing. Insulation board, 480 kg/m3 density, composed of wood fibers with cement binders of thickness shown bonded to deck with unified asphalt adhesive. Covered with a Class A or B roof covering. 10-1.1 11.40 mm-deep steel roof deck on steel-framing wood fiber insulation board, 280 kg/m3 density on top applied over a 7 kilogram asphaltsaturated felt. Class A or B roof covering. 11-1.1 SBC 801 CEILING CONSTRUCTION Wood-fibered gypsum plaster mixed 1:1 by weight gypsum to sand aggregate applied over metal lath. Lath tied 150 mm, on center to 20 mm channels spaced 345 mm on center. Channels secured to joists at each intersection with two strands of 1.3 mm (No. 18 B.W. gage) galvanized wire 16 mm gypsum plaster on bottom of floor or roof construction None Vermiculite gypsum plaster on metal lath attached to 20 mm cold-rolled channels with 1.3 mm (No. 18 B.W. gage) wire ties spaced 150 mm on center Suspended ceiling of vermiculite gypsum plaster base coat and vermiculite acoustical plaster on metal lath attached at 150 mm intervals to 20 mm cold-rolled channels spaced 305 mm on center and secured to 40 mm cold-rolled channels spaced 915 mm on center with 1.6 mm (No. 16 B.W. gage) wire. 40 mm channels supported by 4.2 mm (No. 8 gage) wire hangers at 915 mm on center. Beams within envelope and with a 65 mm airspace between beam soffit and lath have a 4-hour rating Ceiling of gypsum plaster on metal lath. Lath attached to 20 mm furring channels with 1.3 mm (No. 18 B.W. gage) wire ties spaced 150 mm on center. 20 mm channel saddle tied to 50 mm channels with doubled 1.6 mm (No. 16 B.W. gage) wire ties. 50 mm channels spaced 915 mm on center suspended 50 mm below steel framing and saddle-tied with 4.2 mm (No. 8 B.W. gage) wire. Plaster mixed 1:2 by weight, gypsum-to-sand aggregate Ceiling of gypsum plaster on metal lath. Lath attached to 20 mm furring channels with 1.3 mm (No. 18 B.W. gage) wire ties spaced 150 mm on center. 20 mm channels saddle tied to 50 mm channels with doubled 1.6 mm (No. 16 B.W. gage) wire ties. 50 mm channels spaced 915 mm on center suspended 50 mm below steel framing and saddle tied with 4.2 mm (No. 8 B.W. gage) wire. Plaster mixed 1:2 for scratch coat and 1:3 for brown coat, by weight, gypsum-to-sand aggregate for 1hour system. For 2-hour system, plaster mix is 1:2 by weight, gypsum-to-sand aggregate (Continued) 2007 THICKNESS OF MINIMUM FLOOR OR ROOF THICKNESS OF SLAB CEILING (mm) (mm) 4 3 2 1 4 3 2 1 hour hour hour hour hour hour hour hour — — 65 — — — 20 — — — 200h — — — 16 — — — — 140i — — — — 65j — — — 20 — — — 65 — — — 30k — — — — — 50 25 — — 20l 20l — — 40 25 — — 22g 20l 4/61 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(3) – continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa, q FLOOR OR ROOF CONSTRUCTION 12.40 mm deep steel roof deck on steel-framing insulation of rigid board consisting of expanded perlite and fibers impregnated with integral asphalt waterproofing; density 145 to 195 kg/m3 secured to metal roof deck by 13 mm wide ribbons of waterproof, cold-process liquid adhesive spaced 150 mm apart. Steel joist or light steel construction with metal roof deck, insulation, and Class A or B built-up roof covering.e ITEM NUMBER CEILING CONSTRUCTION 12-1.1 Gypsum-vermiculite plaster on metal lath wire tied at 150 mm intervals to 20 mm furring channels spaced 305 mm on center and wire tied to 50 mm runner channels spaced 815 mm on center. Runners wire tied to bottom chord of steel joists 13-1.1 13. Double wood floor over wood joists spaced 405 mm on center.m,n 13-1.2 13-1.3 13-1.4 14. Plywood stressed skin panels consisting of 16 mm-thick interior C-D (exterior glue) top stressed skin on 50 mm × 150 mm nominal (minimum) stringers. Adjacent panel edges joined with 8d common wire nails spaced 150 mm on center. Stringers spaced 305 mm maximum on center. SBC 801 14-1.1 Gypsum plaster over 10 mm Type X gypsum lath. Lath initially applied with not less than four 30 mm by No. 13 gage by 8 mm head plasterboard blued nails per bearing. Continuous stripping over lath along all joist lines. Stripping consists of 75 mm wide strips of metal lath attached by 40 mm by No. 11 gage by 13 mm head roofing nails spaced 150 mm on center. Alternate stripping consists of 75 mm wide 1.3 mm diameter wire stripping weighing 0.54 kilograms per square meter and attached by No.16 gage by 40 mm by 20 mm crown width staples, spaced 100 mm on center. Where alternate stripping is used, the lath nailing may consist of two nails at each end and one nail at each intermediate bearing. Plaster mixed 1:2 by weight, gypsum-to-sand aggregate Cement or gypsum plaster on metal lath. Lath fastened with 40 mm by No. 11 gage by 11 mm head barbed shank roofing nails spaced 125 mm on center. Plaster mixed 1:2 for scratch coat and 1:3 for brown coat, by weight, cement to sand aggregate Perlite or vermiculite gypsum plaster on metal lath secured to joists with 40 mm by No. 11 gage by 11 mm head barbed shank roofing nails spaced 125 mm on center 13 mm Type X gypsum wallboardc nailed to joists with 5d coolero or wallboardo nails at 150 mm on center. End joints of wallboard centered on joists 13 mm-thick wood fiberboard weighing 240 to 290 kilograms per cubic meter installed with long dimension parallel to stringers or 10 mm C-D (exterior glue) plywood glued and/or nailed to stringers. Nailing to be with 5d coolero or wallboardo nails at 305 mm on center. Second layer of 13 mm Type X gypsum wallboardc applied with long dimension perpendicular to joists and attached with 8d coolero or wallboardo nails at 150 mm on center at end joints and 200 mm on center elsewhere. Wallboard joints staggered with respect to fiberboard joints (Continued) 2007 THICKNESS OF MINIMUM FLOOR OR ROOF THICKNESS OF SLAB CEILING (mm) (mm) 4 3 2 1 4 3 2 1 hour hour hour hour hour hour hour hour — — 25 — — — 22 — — — — — — — — 22 — — — — — — — 16 — — — — — — — 16 — — — — — — — 13 — — — — — — — 25 4/62 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(3) – continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa, q FLOOR OR ROOF CONSTRUCTION 15. Vermiculite concrete slab proportioned 1:4 (Portland cement to vermiculite aggregate) on a 40 mmdeep steel deck supported on individually protected steel framing. Maximum span of deck 2.1 meter where deck is less than 0.5 mm (No. 26 carbon steel sheet gage) or greater. Slab reinforced with 100 × 200 mm 2.8/2.1 mm (No. 12/14 B.W. gage) welded wire mesh. 16. Perlite concrete slab proportioned 1:6 (portland cement to perlite aggregate) on a 32 mm-deep steel deck supported on individually protected steel framing. Slab reinforced with 100 × 200 mm 2.8/2.1 mm (No. 12/14 B.W. gage) welded wire mesh. 17. Perlite concrete slab proportioned 1:6 (portland cement to perlite aggregate) on a 14 mm-deep steel deck supported by steel joists 1.22 m on center. Class A or B roof covering on top. 18. Perlite concrete slab proportion-ed 1:6 (portland cement to perlite aggregate) on 32 mm-deep steel deck supported on individually protected steel framing. Maximum span of deck 2.1 meter where deck is less than 0.5 mm (No. 26 carbon sheet steel gage) and 2.4 meter where deck is 0.5 mm (No. 26 carbon sheet steel gage)or greater. Slab reinforced with 1.1 mm (No. 19 B.W. gage) hexagonal wire mesh. Class A or B roof covering on top. 19. Floor and beam construction consisting of 75 mm-deep cellular steel floor unit mounted on steel members with 1:4 (proportion of portland cement to perlite aggregate) perlite-concrete floor slab on top. SBC 801 THICKNESS OF MINIMUM FLOOR OR ROOF THICKNESS OF SLAB CEILING (mm) (mm) 4 3 2 1 4 3 2 1 hour hour hour hour hour hour hour hour ITEM NUMBER CEILING CONSTRUCTION 15-1.1 None — — — 75j — — — — 16-1.1 None — — — 90j — — — — 17-1.1 Perlite gypsum plaster on metal lath wire tied to 20 mm furring channels attached with 1.6 mm (No. 16 B.W. gage) wire ties to lower chord of joists — 50p 50p — — 22 20 — 18-1.1 None — 60p 60p — — — — — 50p — — — 25l — — — 19-1.1 Suspended envelope ceiling of perlite gypsum plaster on metal lath attached to 20 mm cold-rolled channels, secured to 40 mm cold-rolled channels spaced 1.07 m on center supported by 5.2 mm (No. 6 B.W. gage) wire 915 mm on center. Beams in envelope with 75 mm minimum airspace between beam soffit and lath have a 4-hour rating (Continued) 2007 4/63 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(3) – continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa, q FLOOR OR ROOF CONSTRUCTION 20. Perlite concrete proportioned 1:6 (portland cement to perlite aggregate) poured to 3 mm thickness above top of corrugations of 35 mm-deep galvanized steel deck maximum span 2.4 meter for 0.6-mm (No. 24 galvanized sheet gage) or 2.1 meter for 0.5-mm (No. 26 galvanized sheet gage) with deck supported by individually protected steel framing. Approved polystyrene foam plastic insulation board having a flame spread not exceeding 75 (25 mm to 100 mm thickness) with vent holes that approximate 3 percent of the board surface area placed on top of perlite slurry. A 0.61 m by 1.22 m insulation board contains six 70 mm diameter holes. Board covered with 60 mm minimum perlite concrete slab. 21. Slab reinforced with mesh consisting of 1.1 mm (No. 19 B.W. gage) galvanized steel wire twisted together to form 50 mm hexagons with straight 1.6 mm (No. 16 B.W. gage) galvanized steel wire woven into mesh and spaced 75 mm. Alternate slab reinforcement shall be permitted to consist of 100 mm × 200 mm, 2.8/2.1 mm (No. 12/4 B.W. gage), or 50 mm × 50 mm, 2.1/2.1-mm (No. 14/14 B.W. gage) welded wire fabric. Class A or B roof covering on top. 22. Wood joists, floor trusses and flat or pitched roof trusses spaced a maximum 610 mm o.c. with 13 mm wood structural panels with exterior glue applied at right angles to top of joist or top chord of trusses with 8d nails. The wood structural panel thickness shall not be less than nominal 13 mm. SBC 801 THICKNESS OF MINIMUM FLOOR OR ROOF THICKNESS OF SLAB CEILING (mm) (mm) 4 3 2 1 4 3 2 1 hour hour hour hour hour hour hour hour ITEM NUMBER CEILING CONSTRUCTION 20-1.1 None — — Varies — — — — — 21-1.1 None — — Varies — — — — — — — — Varies — — — 32 22-1.1 Base layer 16 mm Type X gypsum wallboard applied at right angles to joist or truss 610 mm o.c. with 32 mm Type S or Type W drywall screws 610 mm o.c. Face layer 16 mm Type X gypsum wallboard or veneer base applied at right angles to joist or truss through base layer with 50 mm Type S or Type W drywall screws 305 mm o.c. at joints and intermediate joist or truss. Face layer Type G drywall screws placed 50 mm back on either side of face layer end joints, 305 mm o.c. (Continued) 2007 4/64 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.20.1(3) – continued MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMSa,q FLOOR OR ROOF CONSTRUCTION 23. Steel joists, floor trusses and flat or pitched roof trusses spaced a maximum 610 mm o.c. with 13 mm wood structural panels with exterior glue applied at right angles to top of joist or top chord of trusses with No. 8 screws. The wood structural panel thickness shall not be less than nominal 13 mm nor less than required by SBC 306. 24. Wood I-joist (minimum joist depth 235 mm with a minimum flange depth of 35 mm and a minimum flange cross sectional area of 1,485 square millimeters) at 610 mm o.c. spacing with 1 × 4 (nominal) wood furring strip spacer applied parallel to and covering the bottom of the bottom flange of each member, tacked in place. 50 mm mineral fiber insulation, 56 kg/m3 (nominal) installed adjacent to the bottom flange of the I-joist and supported by the 1 × 4 furring strip spacer. a. b. c. d. e. f. g. h. i. j. k. l. m. n. o. p. q. ITEM NUMBER CEILING CONSTRUCTION 23-1.1 Base layer 16 mm Type X gypsum board applied at right angles to steel framing 610 mm on center with 25 mm Type S drywall screws spaced 610 mm on center. Face layer 16 mm Type X gypsum board applied at right angles to steel framing attached through base layer with 40 mm Type S drywall screws 305 mm on center at end joints and intermediate joints and 40 mm Type G drywall screws 305 mm on center placed 50 mm back on either side of face layer end joints. Joints of the face layer are offset 610 mm from the joints of the base layer 24-1.1 13 mm deep single leg resilient channel 405 mm on center (channels doubled at wallboard end joints), placed perpendicular to the furring strip and joist and attached to each joist by 50 mm Type S drywall screws. 16 mm Type C gypsum wallboard applied perpendicular to the channel with end joints staggered at least 1.22 m and fastened with 30 mm Type S drywall screws spaced 175 mm on center. Wallboard joints to be taped and covered with joint compound THICKNESS OF MINIMUM FLOOR OR ROOF THICKNESS OF SLAB CEILING (mm) (mm) 4 3 2 1 4 3 2 1 hour hour hour hour hour hour hour hour — — — Varies — — — 32 — — — Varies — — — — Staples with equivalent holding power and penetration shall be permitted to be used as alternate fasteners to nails for attachment to wood framing. When the slab is in an unrestrained condition, minimum reinforcement cover shall not be less than 40 mm for 4-hour (siliceous aggregate only); 32 mm for 4- and 3-hour; 25 mm for 2-hour (siliceous aggregate only); and 20 mm for all other restrained and unrestrained conditions. For all of the construction with gypsum wallboard described in this table, gypsum base for veneer plaster of the same size, thickness and core type shall be permitted to be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard, and the joints on the face layer are reinforced and the entire surface is covered with a minimum of 1.6 mm gypsum veneer plaster. Slab thickness over steel joists measured at the joists for metal lath form and at the top of the form for steel form units. (a) The maximum allowable stress level for H-Series joists shall not exceed 151,690 kPa. (b) The allowable stress for K-Series joists shall not exceed 179,270 kPa, the nominal depth of such joist shall not be less than 250 mm and the nominal joist weight shall not be less than 7.5 kg/m. Cement plaster with 7 kilograms of hydrated lime and 1.4 kilograms of approved additives or admixtures per bag of cement. Gypsum wallboard ceilings attached to steel framing shall be permitted to be suspended with 40 mm cold-formed carrying channels spaced 1.22 m on center, which are suspended with No. 8 SWG galvanized wire hangers spaced 1.22 m on center. Cross-furring channels are tied to the carrying channels with No. 18 SWG galvanized wire hangers spaced 1.22 m on center. Cross-furring channels are tied to the carrying channels with No. 18 SWG galvanized wire (double strand) and spaced as required for direct attachment to the framing. This alternative is also applicable to those steel framing assemblies recognized under Note q. Six-inch hollow clay tile with 50 mm concrete slab above. Four-inch hollow clay tile with 40 mm concrete slab above. Thickness measured to bottom of steel form units. Five-eighths inch of vermiculite gypsum plaster plus 13 mm of approved vermiculite acoustical plastic. Furring channels spaced 305 mm on center. Double wood floor shall be permitted to be either of the following: (a) Subfloor of 25 mm nominal boarding, a layer of asbestos paper weighing not less than 6.4 kilograms per 9.3 square meters and a layer of 25 mm nominal tongue-and-groove finished flooring; or (b) Subfloor of 25 mm nominal tongue-and-groove boarding or 12 mm wood structural panels with exterior glue and a layer of 25 mm nominal tongue-and-groove finished flooring or 15 mm wood structural panel finish flooring or a layer of Type I Grade M-1 particleboard not less than 16 mm thick. The ceiling shall be permitted to be omitted over unusable space, and flooring shall be permitted to be omitted where unusable space occurs above. For properties of cooler or wallboard nails, see ASTM C 514, ASTM C 547 or ASTM F 1667. Thickness measured on top of steel deck unit. Generic fire-resistance ratings those not designated as PROPRIETARY in the listing in the GA 600 shall be accepted as if herein listed. SBC 801 2007 4/65 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Concrete assemblies. The provisions of this section contain procedures by which the fire-resistance ratings of concrete assemblies are established by calculations. 4B.21.2.1 Concrete walls. Cast-in-place and precast concrete walls shall comply with Section 4B.21.2.1.1. Multiwythe concrete walls shall comply with Section 4B.21.2.1.2. Joints between precast panels shall comply with Section 4B.21.2.1.3. Concrete walls with gypsum wallboard or plaster finish shall comply with Section 4B.21.2.1.4. 4B.21.2.1.1 Cast-in-place or precast walls. The minimum equivalent thicknesses of cast-inplace or precast concrete walls for fire-resistance ratings of 1 hour to 4 hours are shown in Table 4B.21.2.1.1. For solid walls with flat vertical surfaces, the equivalent thickness is the same as the actual thickness. The values in Table 4B.21.2.1.1 apply to plain, reinforced or prestressed concrete walls. 4B.21.2 TABLE 4B.21.2.1.1 MINIMUM EQUIVALENT THICKNESS OF CAST-IN-PLACE OR PRECAST CONCRETE WALLS, LOAD-BEARING OR NONLOADBEARING MINIMUM WALL THICKNESS (mm) FOR FIRE-RESISTANCE RATING OF CONCRETE TYPE 1-hour 1 ½ -hour 2-hour 3-hour 4-hour Siliceous 90 110 125 160 175 Carbonate 80 100 115 145 170 Sand-Lightweight 70 85 95 115 135 Lightweight 65 80 90 110 130 4B.21.2.1.1.1 Hollow-core precast wall panels. For hollow-core precast concrete wall panels in which the cores are of constant cross section throughout the length, calculation of the equivalent thickness by dividing the net cross-sectional area (the gross cross section minus the area of the cores) of the panel by its width shall be permitted. 4B.21.2.1.1.2 Core spaces filled. Where all of the core spaces of hollow-core wall panels are filled with loose-fill material, such as expanded shale, clay, or slag, or vermiculite or perlite, the fire-resistance rating of the wall is the same as that of a solid wall of the same concrete type and of the same overall thickness. 4B.21.2.1.1.3 Tapered cross sections. The thickness of panels with tapered cross sections shall be that determined at a distance 2t or 150 mm, whichever is less, from the point of minimum thickness, where t is the minimum thickness. 4B.21.2.1.1.4 Ribbed or undulating surfaces. The equivalent thickness of panels with ribbed or undulating surfaces shall be determined by one of the following expressions: For s � 4t, the thickness to be used shall be t For s � 2t, the thickness to be used shall be te For 4t > s > 2t, the thickness to be used shall be � 4t � t � �� � 1�� �t e � t � � s � (Equation 4B.-3) Where: s = Spacing of ribs or undulations. t = Minimum thickness. Equivalent thickness of the panel calculated as the net cross-sectional te = area of the panel divided by the width, in which the maximum thickness used in the calculation shall not exceed 2t. SBC 801 2007 4/66 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 4B.21.2.1.2 Multiwythe walls. For walls that consist of two wythes of different types of THICKNESS OF OUTSIDE WYTHE OF CARBONATE OR SILICEOUS AGGREGATE CONCRETE (mm) THICKNESS OF OUTSIDE WYTHE OF SAND-LIGHTWEIGHT CONCRETE (mm) 4B.21.2.1.2.1 concrete, the fire-resistance ratings shall be permitted to be determined from Figure 4B.21.2.1.2. Two or more wythes. The fire-resistance rating for wall panels consisting of two or more wythes shall be permitted to be determined by the formula: 1.7 R � �R10.59 � R20.59 � � � Rn0.59 � (Equation 4B.-4) Where: R = The fire endurance of the assembly, minutes. R1, R2, and Rn = The fire endurances of the individual wythes, minutes. Values of Rn0.59 for use in Equation 4B.-4 are given in Table 4B.21.2.1.2(1). Calculated fire-resistance ratings are shown in Table 4B.21.2.1.2(2). INSIDE WYTHE CARBONATE 120 INSIDE WYTHE SILICEOUS 120 100 100 80 4 hr. 80 60 3 hr. 60 40 1 hr. 20 4 hr. 3 hr. 40 2 hr. 1 hr. 20 2 hr. 0 0 0 30 60 90 0 120 30 60 90 120 THICKNESS OF INSIDE WYTHE (mm) THICKNESS OF INSIDE WYTHE (mm) OUTSIDE WYTHE CARBONATE OUTSIDE WYTHE SILICEOUS 120 120 4 hr. 100 3 hr. 80 40 20 20 0 0 0 30 2 hr. 60 1 hr. 40 3 hr. 80 2 hr. 60 4 hr. 100 60 90 1 hr. 0 120 30 60 90 120 THICKNESS OF INSIDE WYTHE OF SAND-LIGHTWEIGHT CONCRETE (mm) FIGURE 4B.21.2.1.2 FIRE-RESISTANCE RATINGS OF TWO-WYTHE CONCRETE WALLS SBC 801 2007 4/67 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TYPE OF MATERIAL Siliceous aggregate concrete Carbonate aggregate concrete Sand-lightweight concrete Lightweight concrete Insulating concretea Airspaceb a. b. c. 40 TABLE 4B.21.2.1.2(1) VALUES OF Rn0.59 FOR USE IN EQUATION 4B.-4 THICKNESS OF MATERIAL (mm) 50 65 75 90 100 115 125 140 150 165 175 5.3 6.5 8.1 9.5 11.3 13.0 14.9 16.9 18.8 20.7 22.8 25.1 5.5 7.1 8.9 10.4 12.0 14.0 16.2 18.1 20.3 21.9 24.7 27.2c 6.5 8.2 10.5 12.8 15.5 18.1 20.7 23.3 26.0c Note c Note c Note c 6.6 8.8 11.2 13.7 16.5 19.1 21.9 24.7 27.8c Note c Note c Note c 9.3 13.3 16.6 18.3 23.1 26.5c Note c Note c Note c Note c Note c Note c – – – – – – – – – – – – 3 Dry unit weight of 560 kg/m or less and consisting of cellular, perlite or vermiculite concrete. The Rn0.59 value for 40 mm to 90 mm airspace is 3.3. The Rn0.59 value for 65 mm to 90 mm airspaces is 6.7. The fire-resistance rating for this thickness exceeds 4 hours. TABLE 4B.21.2.1.2(2) FIRE-RESISTANCE RATINGS BASED ON R0.59 a. Ra, MINUTES 60 R0.59 11.20 120 16.85 180 21.41 240 25.37 Based on Equation 4B.4 Foam plastic insulation. The fire-resistance ratings of precast concrete wall panels consisting of a layer of foam plastic insulation sandwiched between two wythes of concrete shall be permitted to be determined by use of Equation 4B.-4. Foam plastic insulation with a total thickness of less than 25 mm shall be disregarded. The Rn value for thickness of foam plastic insulation of 25 mm or greater, for use in the calculation, is 5 minutes; therefore Rn0.59 = 2.5. 4B.21.2.1.3 Joints between precast wall panels. Joints between precast concrete wall panels which are not insulated as required by this section shall be considered as openings in walls. Uninsulated joints shall be included in determining the percentage of openings permitted by Table 4B.4.8. Where openings are not permitted or are required by these code requirements to be protected, the provisions of this section shall be used to determine the amount of joint insulation required. Insulated joints shall not be considered openings for purposes of determining compliance with the allowable percentage of openings in Table 4B.4.8. 4B.21.2.1.3.1 Ceramic fiber joint protection. Figure 4B.21.2.1.3.1 shows thicknesses of ceramic fiber blankets to be used to insulate joints between precast concrete wall panels for various panel thicknesses and for joint widths of 10 mm and 25 mm for fire-resistance ratings of 1 hour to 4 hours. For joint widths between 10 mm and 25 mm, the thickness of ceramic fiber blanket is allowed to be determined by direct interpolation. Other tested and labeled materials are acceptable in place of ceramic fiber blankets. 4B.21.2.1.2.2 SBC 801 2007 4/68 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION THICKNESS OF CERAMIC BLANKET "C" (mm) 100 4 hr. 25 mm JOINT WIDTH 4 hr. 3 hr. 75 3hr. 2 hr. 50 1 hr. 25 0 75 100 125 150 175 200 THICKNESS OF CERAMIC BLANKET "C" (mm) PANEL THICKNESS (mm) 75 10 mm JOINT WIDTH 50 2 hr. 25 3hr. 2 hr. 3 hr. 4 hr. 1 hr. 4 hr. 1 hr. 0 75 100 125 150 175 200 PANEL THICKNESS (mm) FIGURE 4B.21.2.1.3.1 CERAMIC FIBER JOINT PROTECTION 4B.21.2.1.4 Walls with gypsum wallboard or plaster finishes. The fire-resistance rating of cast-in-place or precast concrete walls with finishes of gypsum wallboard or plaster applied to one or both sides shall be permitted to be calculated in accordance with the provisions of this section. 4B.21.2.1.4.1 Nonfire-exposed side. Where the finish of gypsum wallboard or plaster is applied to the side of the wall not exposed to fire, the contribution of the finish to the total fire-resistance rating shall be determined as follows: The thickness of the finish shall first be corrected by multiplying the actual thickness of the finish by the applicable factor determined from Table 4B.21.2.1.4(1) based on the type of aggregate in the concrete. The corrected thickness of finish shall then be added to the actual or equivalent thickness of concrete and fire-resistance rating of the concrete and finish determined from Table 4B.21.2.1.1, Figure 4B.21.2.1.2 or Table 4B.21.2.1.2(1). 4B.21.2.1.4.2 Fire-exposed side. Where gypsum wallboard or plaster is applied to the fireexposed side of the wall, the contribution of the finish to the total fire-resistance rating shall be determined as follows: The time assigned to the finish as established by Table 4B.21.2.1.4(2) shall be added to the fire-resistance rating determined from Table 4B.21.2.1.1 or Figure 4B.21.2.1.2, or Table 4B.21.2.1.2(1) for the concrete alone, or to the rating determined in Section 4B.21.2.1.4.1 for the concrete and finish on the nonfire-exposed side. 4B.21.2.1.4.3 Nonsymmetrical assemblies. For a wall having no finish on one side or different types or thicknesses of finish on each side, the calculation procedures of Sections 4B.21.2.1.4.1 and 4B.21.2.1.4.2 shall be performed twice, assuming either side of the wall to be the fire-exposed side. The fire-resistance rating of the wall shall not exceed the lower of the two values. Exception: For an exterior wall with more than 1.5 m of horizontal separation, the fire shall be assumed to occur on the interior side only. SBC 801 2007 4/69 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.2.1.4(1) MULTIPLYING FACTOR FOR FINISHES ON NONFIRE-EXPOSED SIDE OF WALL TYPE OF AGGREGATE USED IN CONCRETE OR CONCRETE MASONRY TYPE OF FINISH APPLIED TO MASONRY WALL Portland cement-sand plaster Gypsum-sand plaster or gypsum wallboard Gypsum-vermiculite or perlite plaster a. Concrete: siliceous or carbonate Masonry: siliceous or calcareous gravel 1.00 Concrete: sand lightweight concrete Masonry: limestone, cinders or unexpected slag 0.75a Concrete: light-weight concrete Masonry: expanded shale, clay or slate 0.75a Concrete: pumice, or expanded slag 0.50a 1.25 1.00 1.00 1.00 1.75 1.50 1.50 1.25 For Portland cement-sand plaster 16 mm or less in thickness and applied directly to the masonry on the nonfire-exposed side of the wall, the multiplying factor shall be 1.00. Minimum concrete fire-resistance rating. Where finishes applied to one or both sides of a concrete wall contribute to the fire-resistance rating, the concrete alone shall provide not less than one-half of the total required fire-resistance rating. Additionally, the contribution to the fire resistance of the finish on the nonfireexposed side of a load-bearing wall shall not exceed one-half the contribution of the concrete alone. 4B.21.2.1.4.5 Concrete finishes. Finishes on concrete walls that are assumed to contribute to the total fire-resistance rating of the wall shall comply with the installation requirements of Section 4B.21.3.2.5. 4B.21.2.2 Concrete floor and roof slabs. Reinforced and prestressed floors and roofs shall comply with Section 4B.21.2.2.1. Multicourse floors and roofs shall comply with Sections 4B.21.2.2.2 and 4B.21.2.2.3, respectively. 4B.21.2.2.1 Reinforced and prestressed floors and roofs. The minimum thicknesses of reinforced and prestressed concrete floor or roof slabs for fire-resistance ratings of 1 hour to 4 hours are shown in Table 4B.21.2.2.1. 4B.21.2.1.4.4 TABLE 4B.21.2.1.4(2) TIME ASSIGNED TO FINISH MATERIALS ON FIRE-EXPOSED SIDE OF WALL FINISH DESCRIPTION Gypsum wallboard 10 mm 13 mm 16 mm 2 layers of 10 mm 1 layer 10 mm, 1 layer 13 mm 2 layers 13 mm Type X gypsum wallboard 13 mm 16 mm Portland cement-sand plaster applied directly to concrete masonry Portland cement-sand plaster on metal lath 20 mm 22 mm 25 mm Gypsum sand plaster on 10 mm gypsum lath 13 mm 16 mm 20 mm Gypsum sand plaster on metal lath 20 mm 22 mm 25 mm TIME (minute) 10 15 20 25 35 40 25 40 See Note a 20 25 30 35 40 50 50 60 80 a. The actual thickness of Portland cement-sand plaster, provided it is 16 mm or less in thickness, shall be permitted to be included in determining the equivalent thickness of the masonry for use in Table 4B.21.3.2. SBC 801 2007 4/70 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.2.2.1 MINIMUM SLAB THICKNESS (mm) FIRE-RESISTANCE RATING (hour) 4B.21.2.2.1.1 4B.21.2.2.1.2 CONCRETE TYPE 1 1½ 2 3 4 Siliceous 90 110 125 160 175 Carbonate 80 100 115 145 170 Sand-lightweight 70 85 95 115 135 Lightweight 65 80 90 110 130 Hollow-core prestressed slabs. For hollow-core prestressed concrete slabs in which the cores are of constant cross section throughout the length, the equivalent thickness shall be permitted to be obtained by dividing the net cross-sectional area of the slab including grout in the joints, by its width. Slabs with sloping soffits. The thickness of slabs with sloping soffits (see Figure 4B.21.2.2.1.2) shall be determined at a distance 2t or 150 mm, whichever is less, from the point of minimum thickness, where t is the minimum thickness. FIGURE 4B.21.2.2.1.2 DETERMINATION OF SLAB THICKNESS FOR SLOPING SOFFITS 4B.21.2.2.1.3 Slabs with ribbed soffits. The thickness of slabs with ribbed or undulating soffits (see Figure 4B.21.2.2.1.3) shall be determined by one of the following expressions, whichever is applicable: For s � 4t, the thickness to be used shall be t For s � 2t, the thickness to be used shall be te For 4t > s > 2t, the thickness to be used shall be � 4t � t � �� � 1�� �t e � t � � s � (Equation 4B.-5) Where: s = Spacing of ribs or undulations. t = Minimum thickness. te = Equivalent thickness of the slab calculated as the net area of the slab divided by the width, in which the maximum thickness used in the calculation shall not exceed 2t. SBC 801 2007 4/71 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION FIGURE 4B.21.2.2.1.3 SLABS WITH RIBBED OR UNDULATING SOFFITS 4B.21.2.2.2 Multicourse floors. The fire-resistance ratings of floors that consist of a base slab 4B.21.2.2.3 4B.21.2.2.3.1 4B.21.2.2.4 4B.21.2.3 4B.21.2.3.1 4B.21.2.3.2 4B.21.2.3.3 SBC 801 of concrete with a topping (overlay) of a different type of concrete shall comply with Figure 4B.21.2.2.2. Multicourse roofs. The fire-resistance ratings of roofs which consist of a base slab of concrete with a topping (overlay) of an insulating concrete or with an insulating board and built-up roofing shall comply with Figures 4B.21.2.2.3(1) and 4B.21.2.2.3(2). Heat transfer. For the transfer of heat, three-ply built-up roofing contributes 10 minutes to the fire-resistance rating. The fire-resistance rating for concrete assemblies such as those shown in Figure 4B.21.2.2.3(1) shall be increased by 10 minutes. This increase is not applicable to those shown in Figure 4B.21.2.2.3(2). Joints in precast slabs. Joints between adjacent precast concrete slabs need not be considered in calculating the slab thickness provided that a concrete topping at least 25 mm thick is used. Where no concrete topping is used, joints must be grouted to a depth of at least one-third the slab thickness at the joint, but not less than 25 mm, or the joints must be made fire resistant by other approved methods. Concrete cover over reinforcement. The minimum thickness of concrete cover over reinforcement in concrete slabs, reinforced beams and prestressed beams shall comply with this section. Slab cover. The minimum thickness of concrete cover to the positive moment reinforcement shall comply with Table 4B.21.2.3(1) for reinforced concrete and Table 4B.21.2.3(2) for prestressed concrete. These tables are applicable for solid or hollow-core one-way or two-way slabs with flat undersurfaces. These tables are applicable to slabs that are either cast in place or precast. For precast prestressed concrete not covered elsewhere, the procedures contained in PCI MNL 124 shall be acceptable. Reinforced beam cover. The minimum thickness of concrete cover to the positive moment reinforcement (bottom steel) for reinforced concrete beams is shown in Table 4B.21.2.3(3) for fire-resistance ratings of 1 hour to 4 hours. Prestressed beam cover. The minimum thickness of concrete cover to the positive moment prestressing tendons (bottom steel) for restrained and unrestrained prestressed concrete beams and stemmed units shall comply with the values shown in Tables 4B.21.2.3(4) and 4B.21.2.3(5) for fire-resistance ratings of 1 hour to 4 hours. Values in Table 4B.21.2.3(4) apply to beams 200 mm or greater in width. Values in Table 4B.21.2.3(5) apply to beams or stems of any width, 2007 4/72 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION THICKNESS OF SAND-LIGHTWEIGHT CONCRETE OVERLAY (mm) provided the cross-section area is not less than 25,810 mm2. In case of differences between the values determined from Table 4B.21.2.3(4) or 4B.21.2.3(5), it is permitted to use the smaller value. The concrete cover shall be calculated in accordance with Section 4B.21.2.3.3.1. The minimum concrete cover for nonprestressed reinforcement in prestressed concrete beams shall comply with Section 4B.21.2.3.2. CARBONATE BASE SILICEOUS BASE 120 120 100 100 4 hr. 80 60 60 3 hr. 40 1 hr. 20 4 hr. 80 3 hr. 40 2 hr. 1 hr. 20 2 hr. 0 0 0 30 60 90 0 120 30 60 90 120 THICKNESS OF NORMAL WEIGHT CONCRETE BASE SLAB (mm) OVERLAY THICKNESS (mm) CARBONATE OVERLAY SILICEOUS OVERLAY 120 120 4 hr. 100 3 hr. 80 40 20 20 0 0 0 30 2 hr. 60 1 hr. 40 3 hr. 80 2 hr. 60 4 hr. 100 60 90 1 hr. 0 120 30 60 90 120 THICKNESS OF SAND-LIGHTWEIGHT CONCRETE BASE SLAB (mm) FIGURE 4B.21.2.2.2 FIRE-RESISTANCE RATINGS FOR TWO-COURSE CONCRETE FLOORS SBC 801 2007 4/73 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION CELLULAR CONCRETE CONCRETE SILICEOUS BASE (a) T H IC K N ESS O F C EL LU LA R CO N C RETE O V E RLA Y (m m ) CARBONATE BASE SAND-LIGHTWEIGHT BASE 75 75 75 4 hr. 50 2 hr. 3 hr. 25 1 hr. 4 hr. 50 2 hr. 3 hr. 25 1 hr. 2 hr. 3 hr. 25 1 hr. 0 0 0 0 25 50 0 75 100 4 hr. 50 25 50 0 75 100 25 50 75 100 THICKNESS OF CONCRETE BASE SLAB (mm) PERLITE CONCRETE (b) THICKNESS OF PERLITE CONCRETE OVERLAY (mm) CONCRETE SILICEOUS BASE CARBONATE BASE 75 4 hr. 50 2 hr. 3 hr. 50 4 hr. 3 hr. 2 hr. 25 1 hr. 25 1 hr. 75 SAND-LIGHTWEIGHT BASE 100 100 100 0 25 50 75 2 hr. 3 hr. 1 hr. 0 0 100 25 4 hr. 50 0 0 75 25 50 75 0 100 25 50 75 100 THICKNESS OF CONCRETE BASE SLAB (mm) VERMICULITE CONCRETE (c) THICKNESS OF VERMICULITE CONCRETE OVERLAY (mm) CONCRETE SAND-LIGHTWEIGHT BASE SILICEOUS BASE CARBONATE BASE 100 100 100 75 4 hr. 75 4 hr. 75 50 2 hr. 3 hr. 50 2 hr. 3 hr. 50 1 hr. 25 0 0 0 0 25 50 75 100 1 hr. 25 1 hr. 25 4 hr. 2 hr. 3 hr. 0 25 50 75 100 0 25 50 75 100 THICKNESS OF CONCRETE BASE SLAB (mm) FIGURE 4B.21.2.2.3(1) FIRE-RESISTANCE RATINGS FOR CONCRETE ROOF ASSEMBLIES 4B.21.2.3.3.1 SBC 801 Calculating concrete cover. The concrete cover for an individual tendon is the minimum thickness of concrete between the surface of the tendon and the fireexposed surface of the beam, except that for ungrouped ducts, the assumed cover thickness is the minimum thickness of concrete between the surface of the duct and the fire-exposed surface of the beam. For beams in which two or more tendons are used, the cover is assumed to be the average of the minimum cover of the individual tendons. For corner tendons (tendons equal distance from the bottom and side), the minimum cover used in the calculation shall be one-half the actual value. For stemmed members with two or more prestressing tendons located along the vertical centerline of the stem, the average cover shall be the distance from the 2007 4/74 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION bottom of the member to the centroid of the tendons. The actual cover for any individual tendon shall not be less than one-half the smaller value shown in Tables 4B.21.2.3(4) and 4B.21.2.3(5), or 25 mm, whichever is greater. STANDARD 3-PLY BUILT-UP ROOFING (d) THICKNESS OF MINERAL BOARD, mm MINERAL BOARD CONCRETE SILICEOUS BASE CARBONATE BASE SAND-LIGHTWEIGHT BASE 75 75 4 hr 13 hr 50 2 hr 25 75 4 hr 50 25 3 hr. 2 hr. 25 1 hr 1 hr 1 hr. 0 0 25 4 hr. 50 3 hr 2 hr 50 75 0 25 100 50 75 100 25 50 75 100 THICKNESS OF CONCRETE BASE SLAB (mm) STANDARD 3-PLY BUILT-UP ROOFING GLASS FIBER BOARD (e) THICKNESS OF GLASS FIBER BOARD (mm) CONCRETE SAND LIGHTWEIGHT BASE SILICEOUS BASE CARBONATE BASE 75 75 75 50 3 hr. 2 hr. 25 25 0 75 100 25 125 1 hr. 0 0 50 2 hr. 1 hr. 1 hr. 25 4 hr. 3 hr. 2 hr. 25 50 4 hr. 50 4 hr. 3 hr. 50 75 100 125 25 50 75 100 125 THICKNESS OF CONCRETE BASE SLAB (mm) FIGURE 4B.21.2.2.3(2) FIRE-RESISTANCE RATINGS FOR CONCRETE ROOF ASSEMBLIES TABLE 4B.21.2.3(1) COVER THICKNESS FOR REINFORCED CONCRETE FLOOR OR ROOF SLABS (mm) CONCRETE AGGREGATE TYPE Siliceous Carbonate Sand-lightweight or lightweight 1 20 20 20 FIRE-RESISTANCE RATING (hours) Restrained Unrestrained 1½ 2 3 4 1 1½ 2 3 20 20 20 20 20 20 25 32 20 20 20 20 20 20 20 32 20 20 20 20 20 20 20 32 4 40 32 32 TABLE 4B.21.2.3(2) COVER THICKNESS FOR PRESTRESSED CONCRETE FLOOR OR ROOF SLABS (mm) CONCRETE AGGREGATE TYPE Siliceous Carbonate Sand-lightweight or lightweight SBC 801 1 20 20 20 FIRE-RESISTANCE RATING (hours) Restrained Unrestrained 1½ 2 3 4 1 1½ 2 3 20 20 20 20 30 40 45 60 20 20 20 20 25 35 40 55 20 20 20 20 25 35 40 50 2007 4 70 60 60 4/75 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.2.3(3) MINIMUM COVER FOR MAIN REINFORCING BARS OF REINFORCED CONCRETE BEAMSc (APPLICABLE TO ALL TYPES OF STRUCTURAL CONCRETE) RESTRAINED OR UNRESTRAINEDa BEAM WIDTHb (mm) 125 175 Restrained � 250 125 175 Unrestrained � 250 FIRE-RESISTANCE RATING (hours) 1½ 2 3 1 a 4 20 20 20 20 20 20 20 20 20 25 20 20 32a 20 20 20 20 20 25 20 20 32 20 20 � 45 25 � 75 45 a. Tabulated values for restrained assemblies apply to beams spaced more than 1.2 m on center. For restrained beams spaced 1.2 m or less on center, minimum cover of 20 mm is adequate for ratings of 4 hours or less. b. For beam widths between the tabulated values, the minimum cover thickness can be determined by direct interpolation. c. The cover for an individual reinforcing bar is the minimum thickness of concrete between the surface of the bar and the fire-exposed surface of the beam. For beams in which several bars are used, the cover for corner bars used in the calculation shall be reduced to one-half of the actual value. The cover for an individual bar must be not less than onehalf of the value given in Table 4B.21.2.3(3) nor less than 20 mm. TABLE 4B.21.2.3(4) MINIMUM COVER FOR PRESTRESSED CONCRETE BEAMS 200 mm OR GREATER IN WIDTH RESTRAINED OR UNRESTRAINEDa CONCRETE AGGREGATE TYPE Restrained Carbonate or siliceous Carbonate or siliceous Sand lightweight Sand lightweight Unrestrained BEAM WIDTHb (mm) 200 � 305 200 � 305 200 Carbonate or siliceous Carbonate or siliceous Sand lightweight Sand lightweight � 305 200 � 305 FIRE-RESISTANCE RATING (hours) 1 1½ 2 3 4 40 40 40 40 40 40 40 40 40 40 40 40 45a 40 40 40 65a 50a 50a 40a 40 40 40 40 45 40 40 40 65 50a 50 40 125c 65 85 50 � 75 � 65 a. Tabulated values for restrained assemblies apply to beams spaced more than 1.2 m on center. For restrained beams spaced 1.2 m or less on center, minimum cover of 20 mm is adequate for 4-hour ratings or less. b. For beam widths between 200 mm and 305 mm, minimum cover thickness can be determined by direct interpolation. c. Not practical for 200 mm-wide beam but shown for purposes of interpolation. SBC 801 2007 4/76 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.2.3(5) MINIMUM COVER FOR PRESTRESSED CONCRETE BEAMS OF ALL WIDTHS RESTRAINED OR UNRESTRAINEDa Restrained Unrestrained CONCRETE AGGREGATE TYPE BEAM AREAb A (square mm) All Carbonate or siliceous Sand lightweight All Carbonate or siliceous Sand lightweight 25,810 � A � 96,780 96M780 < A � 193,560 193,560 < A 96,780 < A 25,810 � A � 96,780 96,780 < A � 193,560 193,560 < A 96,780 < A FIRE-RESISTANCE RATING (hours) 1 1½ 2 3 4 40 40 50 65 — 40 40 40 45 65 40 40 40 40 50 40 40 40 40 50 50 65 — — — 40 45 65 — — c 40 40 50 75 100c 100c 40 40 50 75c a. Tabulated values for restrained assemblies apply to beams spaced more than 1.2 m on center. For restrained beams spaced 1.2 m or less on center, minimum cover of 20 mm is adequate for 4-hour ratings or less. b. The cross-sectional area of a stem is permitted to include a portion of the area in the flange, provided the width of the flange used in the calculation does not exceed three times the average width of the stem. c. U-shaped or hooped stirrups spaced not to exceed the depth of the member and having a minimum cover of 25 mm shall be provided. TABLE 4B.21.2.4 MINIMUM DIMENSION OF CONCRETE COLUMNS (mm) TYPES OF CONCRETE FIRE-RESISTANCE RATING (hours) 1 1½ 2a 3a 4b Siliceous 200 230 250 305 355 Carbonate 200 230 250 280 305 Sand-lightweight 200 215 230 265 305 a. b. The minimum dimension is permitted to be reduced to 200 mm for rectangular columns with two parallel sides at least 915 mm in length. The minimum dimension is permitted to be reduced to 250 mm for rectangular columns with two parallel sides at least 915 mm in length. 4B.21.2.4 Concrete columns. Concrete columns shall comply with this section. 4B.21.2.4.1 Minimum size. The minimum overall dimensions of reinforced concrete columns for fire-resistance ratings of 1 hour to 4 hours shall comply with Table 4B.21.2.4. 4B.21.2.4.2 Minimum cover for R/C columns. The minimum thickness of concrete cover to the main longitudinal reinforcement in columns, regardless of the type of aggregate used in the concrete, shall not be less than 25 mm times the number of hours of required fire resistance or 50 mm, whichever is less. 4B.21.2.4.3 Columns built into walls. The minimum dimensions of Table 4B.21.2.4 do not apply to a reinforced concrete column that is built into a concrete or masonry wall provided all of the following are met: 1. The fire-resistance rating for the wall is equal to or greater than the required rating of the column; 2. The main longitudinal reinforcing in the column has cover not less than that required by Section 4B.21.2.4.2; and 3. Openings in the wall are protected in accordance with Table 4B.15.4. Where openings in the wall are not protected as required by Section 4B.15.4, the minimum dimension of columns required to have a fire-resistance rating of 3 hours or less shall be 200 mm, and 250 mm for columns required to have a fireSBC 801 2007 4/77 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION resistance rating of 4 hours, regardless of the type of aggregate used in the concrete. 4B.21.2.4.4 Precast cover units for steel columns. See Section 4B.21.5.1.4. 4B.21.3 4B.21.3.1 4B.21.3.1.1 4B.21.3.1.2 4B.21.3.1.3 4B.21.3.1.4 4B.21.3.2 4B.21.3.2.1 4B.21.3.2.2 4B.21.3.2.3 SBC 801 Concrete masonry. The provisions of this section contain procedures by which the fire-resistance ratings of concrete masonry are established by calculations. Equivalent thickness. The equivalent thickness of concrete masonry construction shall be determined in accordance with the provisions of this section. Concrete masonry unit plus finishes. The equivalent thickness of concrete masonry assemblies, Tea, shall be computed as the sum of the equivalent thickness of the concrete masonry unit, Te, as determined by Section 4B.21.3.1.2, 4B.21.3.1.3, or 4B.21.3.1.4, plus the equivalent thickness of finishes, Tef, determined in accordance with Section 4B.21.3.2: Tea = Te + Tef (Equation 4B.-6) Te = Vn /LH = Equivalent thickness of concrete masonry unit (mm). Where: Vn = Net volume of masonry unit (mm3). L = Specified length of masonry unit (mm). H = Specified height of masonry unit (mm). Ungrouted or partially grouted construction. Te shall be the value obtained for the concrete masonry unit determined in accordance with ASTM C 140. Solid grouted construction. The equivalent thickness, Te, of solid grouted concrete masonry units is the actual thickness of the unit. Airspaces and cells filled with loose-fill material. The equivalent thickness of completely filled hollow concrete masonry is the actual thickness of the unit when loose-fill materials are: sand, pea gravel, crushed stone, or slag that meet ASTM C 33 requirements; pumice, scoria, expanded shale, expanded clay, expanded slate, expanded slag, expanded fly ash, or cinders that comply with ASTM C 331; or perlite or vermiculite meeting the requirements of ASTM C 549 and ASTM C 516, respectively. Concrete masonry walls. The fire-resistance rating of walls and partitions constructed of concrete masonry units shall be determined from Table 4B.21.3.2. The rating shall be based on the equivalent thickness of the masonry and type of aggregate used. Finish on nonfire-exposed side. Where plaster or gypsum wallboard is applied to the side of the wall not exposed to fire, the contribution of the finish to the total fire-resistance rating shall be determined as follows: The thickness of gypsum wallboard or plaster shall be corrected by multiplying the actual thickness of the finish by applicable factor determined from Table 4B.21.2.1.4(1). This corrected thickness of finish shall be added to the equivalent thickness of masonry and the fire-resistance rating of the masonry and finish determined from Table 4B.21.3.2. Finish on fire-exposed side. Where plaster or gypsum wallboard is applied to the fire-exposed side of the wall, the contribution of the finish to the total fireresistance rating shall be determined as follows: The time assigned to the finish as established by Table 4B.21.2.1.4(2) shall be added to the fire-resistance rating determined in Section 4B.21.3.2 for the masonry alone, or in Section 4B.21.3.2.1 for the masonry and finish on the nonfire-exposed side. Nonsymmetrical assemblies. For a wall having no finish on one side or having different types or thicknesses of finish on each side, the calculation procedures of this section shall be performed twice, assuming either side of the wall to be the fire-exposed side. The fire-resistance rating of the wall shall not exceed the lower of the two values calculated. 2007 4/78 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Exception: For exterior walls with more than 1.5 m of horizontal separation, the fire shall be assumed to occur on the interior side only. 4B.21.3.2.4 Minimum concrete masonry fire-resistance rating. Where the finish applied to a concrete masonry wall contributes to its fire-resistance rating, the masonry alone shall provide not less than one-half the total required fire-resistance rating. 4B.21.3.2.5 Attachment of finishes. Installation of finishes shall be as follows: 1. Gypsum wallboard and gypsum lath applied to concrete masonry or concrete walls shall be secured to wood or steel furring members spaced not more than 405 mm on center (o.c.). 2. Gypsum wallboard shall be installed with the long dimension parallel to the furring members and shall have all joints finished. 3. Other aspects of the installation of finishes shall comply with the applicable provisions of this Chapter and Chapter 10 of the SBC 201. TABLE 4B.21.3.2 MINIMUM EQUIVALENT THICKNESS (mm) OF BEARING OR NONBEARING CONCRETE MASONRY WALLSa,b,c,d FIRE-RESISTANCE RATING (hours) TYPE OF AGGREGATE Pumice or expanded slag Expanded shale, clay or slate Limestone, cinders or unexpanded slag Calcareous or siliceous gravel ½ ¾ 1 1¼ 1½ 1¾ 2 2¼ 2½ 2¾ 40 50 55 65 70 75 80 85 45 55 65 75 85 85 90 95 100 105 110 115 120 125 130 50 60 70 80 85 95 100 110 115 120 125 130 140 145 150 50 60 70 80 90 100 105 115 120 125 135 140 145 150 160 90 3 3¼ 3½ 3¾ 4 95 100 105 110 115 120 a. Values between those shown in the table can be determined by direct interpolation. b. Where combustible members are framed into the wall, the thickness of solid material between the end of each member and the opposite face of the wall, or between members set in from opposite sides, shall not be less than 93 percent of the thickness shown in the table. c. Requirements of ASTM C 55, ASTM C 73 or ASTM C 90 shall apply. d. Minimum required equivalent thickness corresponding to the hourly fire-resistance rating for units with a combination of aggregate shall be determined by linear interpolation based on the percent by volume of each aggregate used in manufacture. 4B.21.3.3 4B.21.3.4 SBC 801 Multiwythe masonry walls. The fire-resistance rating of wall assemblies constructed of multiple wythes of masonry materials shall be permitted to be based on the fire-resistance rating period of each wythe and the continuous airspace between each wythe in accordance with the following formula: R A � �R10.59 � R20.59 � � � Rn0.59 � A1 � A2 � � � An � 1.7 (Equation 4B.-7) Where: RA = Fire endurance rating of the assembly (hours). R1, R2, ..., Rn = Fire endurance rating of wythes for 1, 2, n (hours), respectively. A1, A2, ...., An = 0.30, factor for each continuous airspace for 1, 2, ..., n, respectively, having a depth of 13 mm or more between wythes. Concrete masonry lintels. Fire-resistance ratings for concrete masonry lintels shall be determined based upon the nominal width of the lintel and the minimum thickness of concrete masonry or concrete, or any combination thereof, covering the main reinforcing bars, as determined according to Table 4B.21.3.4, or by approved alternate methods. 2007 4/79 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.3.4 MINIMUM COVER OF LONGITUDINAL REINFORCEMENT IN FIRE-RESISTANCE-RATED REINFORCED CONCRETE MASONRY LINTELS (mm) FIRE-RESISTANCE RATING (hours) 1 2 3 4 40 50 — — 40 40 45 75 40 40 40 45 NOMINAL WIDTH OF LINTEL (mm) 150 200 250 or greater 4B.21.3.5 Concrete masonry columns. The fire-resistance rating of concrete masonry columns shall be determined based upon the least plan dimension of the column in accordance with Table 4B.21.3.5 or by approved alternate methods. TABLE 4B.21.3.5 MINIMUM DIMENSION OF CONCRETE MASONRY COLUMNS (mm) FIRE-RESISTANCE RATING (hours) 1 2 3 4 200 250 305 355 Clay brick and tile masonry. The provisions of this section contain procedures by which the fire-resistance ratings of clay brick and tile masonry are established by calculations. 4B.21.4.1 Masonry walls. The fire-resistance rating of masonry walls shall be based upon the equivalent thickness as calculated in accordance with this section. The calculation shall take into account finishes applied to the wall and airspaces between wythes in multi wythe construction. 4B.21.4.1.1 Equivalent thickness. The fire-resistance ratings of walls or partitions constructed of solid or hollow clay masonry units shall be determined from Table 4B.21.4.1(1) or 4B.21.4.1(2). The equivalent thickness of the clay masonry unit shall be determined by Equation 4B.-8 when using Table 4B.21.4.1(1). The fire-resistance rating determined from Table 4B.21.4.1(1) shall be permitted to be used in the calculated fire-resistance rating procedure in Section 4B.21.4.2. Te = Vn /LH (Equation 4B.-8) Where: Te = The equivalent thickness of the clay masonry unit (mm). Vn = The net volume of the clay masonry unit (mm3). L = The specified length of the clay masonry unit (mm). H = The specified height of the clay masonry unit (mm). 4B.21.4 4B.21.4.1.1.1 SBC 801 Hollow clay units. The equivalent thickness, Te, shall be the value obtained for hollow clay units as determined in accordance with ASTM C67. 2007 4/80 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.4.1(1) FIRE-RESISTANCE PERIODS OF CLAY MASONRY WALLS MINIMUM REQUIRED EQUIVALENT THICKNESS FOR FIRE RESISTANCEa,b,c (mm) 1 hour 2 hour 3 hour 4 hour 70 95 125 150 MATERIAL TYPE Solid brick of clay or shaled Hollow brick or tile of clay or shale, unfilled Hollow brick or tile of clay or shale, grouted or filled with materials specified in Section 4B.21.4.1.1.3 a. b. c. d. 60 85 110 125 75 110 140 170 Equivalent thickness as determined from Section 4B.21.4.1.1. Calculated fire resistance between the hourly increments listed shall be determined by linear interpolation. Where combustible members are framed in the wall, the thickness of solid material between the end of each member and the opposite face of the wall, or between members set in from opposite sides, shall not be less than 93 percent of the thickness shown. For units in which the net cross-sectional area of cored brick in any plane parallel to the surface containing the cores is at least 75 percent of the gross cross-sectional area measured in the same plane. TABLE 4B.21.4.1(2) FIRE-RESISTANCE RATINGS FOR BEARING STEEL FRAME BRICK VENEER WALLS OR PARTITIONS WALL OR PARTITION ASSEMBLY Outside facing of steel studs: 13 mm wood fiberboard sheathing next to studs, 20 mm airspace formed with 20 mm × 40 mm wood strips placed over the fiberboard and secured to the studs; metal or wire lath nailed to such strips, 95 mm brick veneer held in place by filling 20 mm airspace between the brick and lath with mortar. Inside facing of studs: 20 mm unsanded gypsum plaster on metal or wire lath attached to 8 mm wood strips secured to edges of the studs Outside facing of steel studs: 25 mm insulation board sheathing attached to studs, 25 mm airspace, and 95 mm brick veneer attached to steel frame with metal ties every 5th course. Inside facing of studs: 22 mm sanded gypsum plaster (1:2 mix) applied on metal or wire lath attached directly to the studs Same as above except use 22 mm vermiculite— gypsum plaster or 25 mm sanded gypsum plaster (1:2 mix) applied to metal or wire Outside facing of steel studs: 13 mm gypsum sheathing board, attached to studs, and 95 mm brick veneer attached to steel frame with metal ties every 5th course. Inside facing of studs: 13 mm sanded gypsum plaster (1:2 mix) applied to 13 mm perforated gypsum lath securely attached to studs and having strips of metal lath 75 mm wide applied to all horizontal joints of gypsum lath SBC 801 2007 PLASTER SIDE EXPOSED (hours) BRICK FACED SIDE EXPOSED (hours) 1.5 4 1.5 4 2 4 2 4 4/81 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Solid grouted clay units. The equivalent thickness of solid grouted clay masonry units shall be taken as the actual thickness of the units. 4B.21.4.1.1.3 Units with filled cores. The equivalent thickness of the hollow clay masonry units is the actual thickness of the unit when completely filled with loose-fill materials of: sand, pea gravel, crushed stone, or slag that meet ASTM C 33 requirements; pumice, scoria, expanded shale, expanded clay, expanded slate, expanded slag, expanded fly ash, or cinders in compliance with ASTM C 331; or perlite or vermiculite meeting the requirements of ASTM C 549 and ASTM C 516), respectively. 4B.21.4.1.2 Plaster finishes. Where plaster is applied to the wall, the total fire-resistance rating shall be determined by the formula: R = (Rn0.59 + pl)1.7 (Equation 4B-9) Where: R = The fire endurance of the assembly (hours). Rn = The fire endurance of the individual wall (hours). pl = Coefficient for thickness of plaster. Values for Rn0.59 for use in Equation 4B-9 are given in Table 4B.21.4.1(3). Coefficients for thickness of plaster shall be selected from Table 4B.21.4.1(4) based on the actual thickness of plaster applied to the wall or partition and whether one or two sides of the wall are plastered. 4B.21.4.1.3 Multiwythe walls with airspace. Where a continuous airspace separates multiple wythes of the wall or partition, the total fire-resistance rating shall be determined by the formula: R = (R10.59 + R20.59 + ....+ Rn0.59 + as )1.7 (Equation 4B-10) Where: R = The fire endurance of the assembly (hours). R1, R2 and Rn = The fire endurance of the individual wall (hours). as = Coefficient for continuous airspace. Values for Rn0.59 for use in Equation 4B-10 are given in Table 4B.21.4.1(3). The coefficient for each continuous airspace of 13 mm to 90 mm separating two individual wythes shall be 0.3. 4B.21.4.1.4 Nonsymmetrical assemblies. For a wall having no finish on one side or having different types or thicknesses of finish on each side, the calculation procedures of this section shall be performed twice, assuming either side to be the fire-exposed side of the wall. The fire resistance of the wall shall not exceed the lower of the two values determined. Exception: For exterior walls with more than 1.5 m of horizontal separation, the fire shall be assumed to occur on the interior side only. 4B.21.4.1.1.2 TABLE 4B.21.4.1(3) VALUES OF Rn0.59 SBC 801 Rn0.59 R (hours) 1 1.0 2 1.50 3 1.91 4 2.27 2007 4/82 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.4.1(4) COEFFICIENTS FOR PLASTER, pl a a. THICKNESS OF PLASTER (mm) 13 ONE SIDE 0.3 TWO SIDE 0.6 16 0.37 0.75 20 0.45 Values listed in table are for 1:3 sanded gypsum plaster. 0.90 TABLE 4B.21.4.1(5) REINFORCED MASONRY LINTELS NOMINAL LINTEL WIDTH (mm) MINIMUM LONGITUDINAL REINFORCEMENT COVER FOR FIRE RESISTANCE (mm) 1 hour 2 hour 3 hour 4 hour 150 40 50 NP NP 200 40 40 45 75 40 40 40 45 250 or more NP = Not permitted. TABLE 4B.21.4.1(6) REINFORCED CLAY MASONRY COLUMNS FIRE-RESISTANCE RATING (hour) COLUMN SIZE 1 2 3 4 Minimum column dimension (mm) 4B.21.4.2 200 250 305 355 Multiwythe walls. The fire-resistance rating for walls or partitions consisting of two or more dissimilar wythes shall be permitted to be determined by the formula: � R � R10.59 � R20.59 � � � Rn0.59 � 1.7 (Equation 4B.-11) Where: R = The fire endurance of the assembly (hours). R1, R2 and Rn = The fire endurance of the individual wall (hours). Values for Rn0.59 for use in Equation 4B.-11 are given in Table 4B.21.4.1(3). 4B.21.4.2.1 Multiwythe walls of different material. For walls that consist of two or more wythes of different materials (concrete or concrete masonry units) in combination with clay masonry units, the fire-resistance rating of the different materials shall be permitted to be determined from Table 4B.21.2.1.1 for concrete; Table 4B.21.3.2 for concrete masonry units or Table 4B.21.4.1(1) or 4B.21.4.1(2) for clay brick and tile masonry units. 4B.21.4.3 Reinforced clay masonry lintels. Fire-resistance ratings for clay masonry lintels shall be determined based on the nominal width of the lintel and the minimum covering for the longitudinal reinforcement in accordance with Table 4B.21.4.1(5). 4B.21.4.4 Reinforced clay masonry columns. The fire-resistance ratings shall be determined based on the least plan dimension of the column in accordance with Table 4B.21.4.1(6). The minimum cover for longitudinal reinforcement shall be 50 mm. 4B.21.5 SBC 801 Steel assemblies. The provisions of this section contain procedures by which the fire-resistance ratings of steel assemblies are established by calculations. 2007 4/83 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Structural steel columns. The fire-resistance ratings of steel columns shall be based on the size of the element and the type of protection provided in accordance with this section. 4B.21.5.1.1 General. These procedures establish a basis for determining the fire resistance of column assemblies as a function of the thickness of fire-resistant material and, the weight, W, and heated perimeter, D, of steel columns. As used in these sections, W is the average weight of a structural steel column in kilograms per linear meter. The heated perimeter, D, is the inside perimeter of the fire-resistant material in millimeters as illustrated in Figure 4B.21.5.1(1). 4B.21.5.1.1.1 Nonload-bearing protection. The application of these procedures shall be limited to column assemblies in which the fire-resistant material is not designed to carry any of the load acting on the column. 4B.21.5.1.1.2 Embedments. In the absence of substantiating fire-endurance test results, ducts, conduit, piping, and similar mechanical, electrical, and plumbing installations shall not be embedded in any required fire-resistant materials. 4B.21.5.1.1.3 Weight-to-perimeter ratio. Table 4B.21.5.1(1) contains weight-to-heatedperimeter ratios (W/D) for both contour and box fire-resistant profiles, for some wide flange shapes. For different fire-resistant protection profiles or column cross sections, the weightto-heated-perimeter ratios (W/D) shall be determined in accordance with the definitions given in this section. 4B.21.5.1 FIGURE 4B.21.5.1(1) DETERMINATION OF THE HEATED PERIMETER OF STRUCTURAL STEEL COLUMNS 4B.21.5.1.2 Gypsum wallboard protection. The fire resistance of structural steel columns with weight to-heated-perimeter ratios (W/D) less than or equal to 0.214 and which are protected with Type X gypsum wallboard shall be permitted to be determined from the following expression: � h�W ' / D � � � � 2.976 � R = 130 � Where: = R = H = D W’ = 0.75 (Equation 4B.-12) Fire resistance (minutes). Total thickness of gypsum wallboard (mm). Heated perimeter of the structural steel column (mm). Total weight of the structural steel column and gypsum wallboard protection (kilogram per linear meter). W’ = W + 800hD/106. Alternatively, the determination of the fire resistance of structural steel columns from Figure 4B.21.5.1(4) is permitted for various thicknesses of gypsum wallboard as a function of the weight-to-heated-perimeter ratio (W/D) of the column. SBC 801 2007 4/84 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION For structural steel columns with weight-to-heated-perimeter ratios (W/D) greater than 0.21, the thickness of gypsum wallboard required for specified fire-resistance ratings shall be the same as the thickness determined for a wide flange shape with W/D equals to 0.21. 4B.21.5.1.2.1 Attachment. The gypsum wallboard shall be supported as illustrated in either Figure 4B.21.5.1(2) for fire-resistance ratings of 4 hours or less, or Figure 4B.21.5.1(3) for fire-resistance ratings of 3 hours or less. 4B.21.5.1.2.2 Gypsum wallboard equivalent to concrete. The determination of the fire resistance of structural steel columns from Figure 4B.21.5.1(4) is permitted for various thicknesses of gypsum wallboard as a function of the weight-to-heatedperimeter ratio (W/D) of the column. For structural steel columns with weight-toheated-perimeter ratios (W/D) greater than 0.21, the thickness of gypsum wallboard required for specified fire-resistance ratings shall be the same as the thickness determined for a wide flange shape with W/D equals to 0.21. 4B.21.5.1.3 Spray-applied fire-resistant materials. The fire resistance of wide-flange structural steel columns protected with spray-applied fire-resistant materials, as illustrated in Figure 4B.21.5.1(5), shall be permitted to be determined from the following expression: R = [ C1 (W / D) + C2 ] h (Equation 4B.-13) Where: R = Fire resistance (minutes h = Thickness of spray-applied fire-resistant material (mm) D = Heated perimeter of the structural steel column (mm) C1 and C2 = Material-dependent constants W = Weight of structural steel column (kilograms per linear meter) FIGURE 4B.21.5.1(2) GYPSUM WALLBOARD PROTECTED STRUCTURAL STEEL COLUMNS WITH SHEET STEEL COLUMN COVERS SBC 801 2007 4/85 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION 1. 2. 3. Structural steel column, either wide flange or tubular shapes. Type X gypsum wall board in accordance with ASTM C 36). For single-layer applications, the wallboard shall be applied vertically with no horizontal joints. For multiple-layer applications, horizontal joints are permitted at a minimum spacing of 2.4 m, provided that the joints in successive layers are staggered at least 305 mm. The total required thickness of wallboard shall be determined on the basis of the specified fire-resistance rating and the weight-to-heatedperimeter ratio (W/D) of the column. For fire-resistance ratings of 2 hours or less, one of the required layers of gypsum wallboard may be applied to the exterior of the sheet steel column covers with 25 mm long Type S screws spaced 25 mm from the wallboard edge and 200 mm on center. For such installations, 0.38-mm minimum thickness galvanized steel corner beads with 40 mm legs shall be attached to the wallboard with Type S screws spaced 305 mm on center. For fire-resistance ratings of 3 hours or less, the column covers shall be fabricated from 0.6mm minimum thickness galvanized or stainless steel. For 4-hour fire-resistance ratings, the column covers shall be fabricated from 0.6-mm minimum thickness stainless steel. The column covers shall be erected with the Snap Lock or Pittsburgh joint details. For fireresistance ratings of 2 hours or less, column covers fabricated from 0.68-mm minimum thickness galvanized or stainless steel shall be permitted to be erected with lap joints. The lap joints shall be permitted to be located anywhere around the perimeter of the column cover. The lap joints shall be secured with 13 mm-long No. 8 sheet metal screws spaced 305 mm on center. The column covers shall be provided with a minimum expansion clearance of 10 mm per linear meter between the ends of the cover and any restraining construction. Material-dependent constants. The material-dependent constants, C1 and C2, shall be determined for specific fire-resistant materials on the basis of standard fire endurance tests in accordance with Section 4B.3.2. Unless evidence is submitted to the building official substantiating a broader application, this expression shall be limited to determining the fire resistance of structural steel columns with weightto-heated-perimeter ratios (W/D) between the largest and smallest columns for which standard fire-endurance test results are available. 4B.21.5.1.3.2 Spray-applied identification. Spray-applied fire-resistant materials shall be identified by density and thickness required for a given fire-resistance rating. 4B.21.5.1.4 Concrete-protected columns. The fire resistance of structural steel columns protected with concrete, as illustrated in Figure 4B.21.5.1(6) (a) and (b), shall be permitted to be determined from the following expression: 4B.21.5.1.3.1 R = Ro (1 + 0.03m) (Equation 4B.-14) where: Ro = 73 (W/D)0.7 + 0.107 × (h1.6/kc0.2) × (1 + 30784 (H/pccch (L + h))0.8) As used in these expressions: R = Fire endurance at equilibrium moisture conditions (minutes) Ro = Fire endurance at zero moisture content (minutes) M = Equilibrium moisture content of the concrete by volume (percent) W = Average weight of the steel column (kilograms per linear meter) D = Heated perimeter of the steel column (mm) H = Thickness of the concrete cover (mm) kc = Ambient temperature thermal conductivity of the concrete (Watt/m.�K) H = Ambient temperature thermal capacity of the steel column = 0.46W (kJ/m.�K) pc = Concrete density (kg/m3) cc = Ambient temperature specific heat of concrete (kJ/kg.�K) L = Interior dimension of one side of a square concrete box protection (mm) SBC 801 2007 4/86 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION FIGURE 4B.21.5.1(3) GYPSUM WALLBOARD PROTECTED STRUCTURAL STEEL COLUMNS WITH STEEL STUD/SCREW ATTACHMENT SYSTEM 1. 2. 3. 4. 5. 6. 7. SBC 801 Structural steel column, either wide flange or tubular shapes. 40 mm deep studs fabricated from 0.45-mm minimum thickness galvanized steel with 35 mm or 37 mm legs. The length of the steel studs shall be 13 mm less than the height of the assembly. Type X gypsum wall board in accordance with ASTM C 36). For single-layer applications, the wallboard shall be applied vertically with no horizontal joints. For multiple-layer applications, horizontal joints are permitted at a minimum spacing of 2.4 m, provided that the joints in successive layers are staggered at least 305 mm. The total required thickness of wallboard shall be determined on the basis of the specified fire-resistance rating and the weight-to-heated-perimeter ratio (W/D) of the column. Galvanized 0.38-mm minimum thickness steel corner beads with 40 mm legs attached to the wallboard with 25 mm-long Type S screws spaced 305 mm on center. 1.3 mm (No. 18 SWG) steel tie wires spaced 610 mm on center. Sheet metal angles with 50 mm legs fabricated from 0.56-mm minimum thickness galvanized steel. Type S screws, 25 mm long, shall be used for attaching the first layer of wallboard to the steel studs and the third layer to the sheet metal angles at 610 mm on center. Type S screws 45 mm long shall be used for attaching the second layer of wallboard to the steel studs and the fourth layer to the sheet metal angles at 305 mm on center. Type S screws 60 mm long shall be used for attaching the third layer of wallboard to the steel studs at 305 mm on center. 2007 4/87 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION FIGURE 4B.21.5.1(4) FIRE RESISTANCE OF STRUCTURAL STEEL COLUMNS PROTECTED WITH VARIOUS THICKNESSES OF TYPE X GYPSUM WALLBOARD a. The W/D ratios for typical wide flange columns are listed in Table 4B.21.5.1(1). For other column shapes, the W/D ratios shall be determined in accordance with Section 4B.21.5.1.1. FIGURE 4B.21.5.1(5) WIDE FLANGE STRUCTURAL STEEL COLUMNS WITH SPRAY-APPLIED FIRE-RESISTANT MATERIALS SBC 801 2007 4/88 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION FIGURE 4B.21.5.1(6) CONCRETE PROTECTED STRUCTURAL STEEL COLUMNSa,b a. When the inside perimeter of the concrete protection is not square, L shall be taken as the average of L1 and L2. When the thickness of concrete cover is not constant, h shall be taken as the average of h1 and h2. b. Joints shall be protected with a minimum 25 mm thickness of ceramic fiber blanket but in no case less than one-half the thickness of the column cover (see Section 4B.21.2.1.3). 4B.21.5.1.4.1 Reentrant space filled. For wide-flange steel columns completely encased in concrete with all reentrant spaces filled [Figure 4B.21.5.1(6)(c)], the thermal capacity of the concrete within the reentrant spaces shall be permitted to be added to the thermal capacity of the steel column, as follows: H = 0.46W + 1 × 10-6 pccc (bfd � As) (Equation 4B.-15) Where: bf = Flange width of the steel column (mm) d = Depth of the steel column (mm) As = Cross-sectional area of the steel column (square mm) 4B.21.5.1.4.2 Concrete properties unknown. If specific data on the properties of concrete are not available, the values given in Table 4B.21.5.1(2) are permitted. 4B.21.5.1.4.3 Minimum concrete cover. For structural steel column encased in concrete with all reentrant spaces filled, Figure 4B.21.5.1(6)(c) and Tables 4B.21.5.1(7) and 4B.21.5.1(8) indicate the thickness of concrete cover required for various fireresistance ratings for typical wide-flange sections. The thicknesses of concrete indicated in these tables also apply to structural steel columns larger than those listed. 4B.21.5.1.4.4 Minimum precast concrete cover. For structural steel columns protected with precast concrete column covers as shown in Figure 4B.21.5.1(6)(a), Tables 4B.21.5.1(9) and 4B.21.5.1(10) indicate the thickness of the column covers required for various fire-resistance ratings for typical wide-flange shapes. The thicknesses of concrete given in these tables also apply to structural steel columns larger than those listed. 4B.21.5.1.4.5 Masonry protection. The fire resistance of structural steel columns protected with concrete masonry units or clay masonry units as illustrated in Figure 4B.21.5.1(7), shall be permitted to be determined from the following expression: R = 1.24 (W/D)0.7 + [0.0018 (Te1.6/km0.2) ] � [1.0 + 392.76 { (As/dm Te) / (0.25p + Te) }0.8 ] SBC 801 2007 (Equation 4B.-16) 4/89 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Where: = R W = = D Te = km = As dm P = = = Fire-resistance rating of column assembly (hours). Average weight of steel column (kg/m3). Heated perimeter of steel column (mm) [see Figure 4B.21.5.1(7)]. Equivalent thickness of concrete or clay masonry unit (mm) (see Table 4B.21.3.2 Note a or Section 4B.21.4.1). Thermal conductivity of concrete or clay masonry unit (Watt/m.�K) [see Table 4B.21.5.1(3)]. Cross-sectional area of steel column (square mm). Density of the concrete or clay masonry unit (kg/m3). Inner perimeter of concrete or clay masonry protection (mm) [see Figure 4B.21.5.1(7)]. 4B.21.5.1.4.6 Equivalent masonry thickness. For structural steel columns protected with concrete masonry, Table 4B.21.5.1(5) gives the equivalent thickness of concrete masonry required for various fire-resistance ratings for typical column shapes. For structural steel columns protected with clay masonry, Table 4B.21.5.1(6) gives the equivalent thickness of clay masonry required for various fire-resistance ratings for typical column shapes. FIGURE 4B.21.5.1(7) CONCRETE OR CLAY MASONRY PROTECTED STRUCTURAL STEEL COLUMNS d = tweb = w = SBC 801 Depth of a wide flange column, outside diameter of pipe column, or outside dimension of structural tubing column (mm). Thickness of web of wide flange column (mm). Width of flange of wide flange column or outside dimension of structural tubing column (mm). 2007 4/90 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.5.1(1) W/D RATIOS FOR STEEL COLUMNS in. ×lb/ft mm×kg/m kg/m Area As mm2 mm mm mm mm Contour Profile kg/m/mm W14×233 W360×347 347 44200 407 27.2 404 43.7 0.146 0.214 W14×211 W360×314 314 39900 399 24.9 401 39.6 0.133 0.196 W14×193 W360×287 287 36600 393 22.6 399 36.6 0.123 0.181 W14×176 W360×262 262 33500 387 21.1 398 33.3 0.113 0.167 W14×159 W360×237 237 30100 380 18.9 395 30.2 0.103 0.153 W14×145 W360×216 216 27600 375 17.3 394 27.7 0.094 0.140 W14×82 W360×122 122 15500 363 13 257 21.7 0.071 0.098 W14×68 W360×101 101 12900 357 10.5 255 18.3 0.059 0.083 W14×53 W360×79 79 10100 354 9.4 205 16.8 0.052 0.071 W14×43 W360×64 64 8140 347 7.7 203 13.5 0.043 0.058 W12×190 W310×283 283 36000 365 26.9 322 44.1 0.144 0.206 W12×170 W310×253 253 32200 356 24.4 319 39.6 0.130 0.187 W12×152 W310×226 226 28900 348 22.1 317 35.6 0.118 0.170 W12×136 W310×202 202 25800 341 20.1 315 31.8 0.106 0.154 W12×72 W310×107 107 13600 311 10.9 306 17 0.059 0.087 W12×58 W310×86 86 11000 310 9.1 254 16.3 0.053 0.076 W12×50 W310×74 74 9490 310 9.4 205 16.3 0.052 0.072 W12×40 W310×60 60 7590 303 7.5 203 13.1 0.043 0.059 W10×112 W250×167 167 21300 289 19.2 265 31.8 0.104 0.151 W10×100 W250×149 149 19000 282 17.3 263 28.4 0.094 0.137 W10×88 W250×131 131 16700 275 15.4 261 25.1 0.084 0.122 W10×77 W250×115 115 14600 269 13.5 259 22.1 0.074 0.109 W10×68 W250×101 101 12900 264 11.9 257 19.6 0.066 0.097 W10×54 W250×80 80 10200 256 9.4 255 15.6 0.053 0.078 W10×45 W250×67 67 8550 275 8.9 204 15.7 0.050 0.070 W10×33 W250×49.1 49.1 6250 247 7.4 202 11 0.038 0.055 W8×40 W200×59 59 7560 210 9.1 205 14.2 0.048 0.071 W8×35 W200×52 52 6660 206 7.9 204 12.6 0.043 0.063 W8×31 W200×46.1 46.1 5860 203 7.2 203 11.8 0.038 0.057 W8×28 W200×41.7 41.7 5310 205 7.2 166 11.8 0.039 0.056 W8×24 W200×35.9 35.9 4580 201 6.2 165 10.2 0.034 0.049 W8×18 W200×26.6 26.6 3390 207 5.8 133 8.4 0.028 0.039 Shape Designation Weight d tw bf tf Box Profile kg/m/mm TABLE 4B.21.5.1(2) PROPERTIES OF CONCRETE PROPERTY Thermal conductivity (kc) Specific heat (cc) Density (Pc) Equilibrium (free) moisture content (m) by volume SBC 801 NORMAL WEIGHT CONCRETE STRUCTURAL LIGHTWEIGHT CONCRETE 0.84 kJ/kg · K 0.84 kJ/kg · oK 1.64 Watt/m · oK o 2400 kg/m3 4% 2007 0.61 Watt/m · oK 1750 kg/m3 5% 4/91 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.5.1(3) THERMAL CONDUCTIVITY OF CONCRETE OR CLAY MASONRY UNITS DENSITY (dm) OF UNITS THERMAL CONDUCTIVITY (km) (kg/m3) OF UNITS (Watt/m · oK) Concrete Masonry Units 1280 0.358 1360 0.395 1440 0.436 1520 0.481 1600 0.533 1680 0.588 1760 0.651 1840 0.720 1920 0.794 2000 0.879 2080 0.971 2160 1.073 2240 1.186 2320 1.312 2400 1.449 Clay Masonry Units 1920 2080 2.16 3.89 TABLE 4B.21.5.1(4) WEIGHT-TO-HEATED-PERIMETER RATIOS (W/D) FOR TYPICAL WIDE FLANGE BEAM AND GIRDER SHAPES Shape Designation in.×lb/ft mm×kg/m W36×300 W36×280 W36×260 W36×245 W36×230 W33×241 W33×221 W33×201 W33×152 W30×211 W30×191 W30×173 W30×132 W920×446 W920×417 W920×387 W920×365 W920×342 W840×359 W840×329 W840×299 W840×226 W760×314 W760×284 W760×257 W760×196 SBC 801 weight kg/m 446 417 387 365 342 359 329 299 226 314 284 257 196 Area As mm2 57000 53300 49300 46400 43600 45800 42000 38100 28900 40100 36200 32600 25100 Depth d mm 933 928 921 916 912 868 862 855 851 786 779 773 770 2007 tw mm 24 22.5 21.3 20.3 19.3 21.1 19.7 18.2 16.1 19.7 18 16.6 15.6 Width bf mm 423 422 420 419 418 403 401 400 294 384 382 381 268 tf mm 42.7 39.9 36.6 34.3 32 35.6 32.4 29.2 26.8 33.4 30.1 27.1 25.4 Contour Profile kg/m/mm 0.144 0.136 0.126 0.120 0.113 0.124 0.114 0.104 0.089 0.117 0.106 0.097 0.085 Box Profile kg/m/mm 0.195 0.183 0.171 0.162 0.153 0.168 0.155 0.142 0.113 0.161 0.146 0.133 0.108 4/92 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.5.1(5) FIRE RESISTANCE OF CONCRETE MASONRY PROTECTED STEEL COLUMNS Shape Designation in. x lb/ft W14×82 W14×68 W14×53 W14×43 W12×72 W12×58 W12×50 W12×40 W10×68 W10×54 W10×45 SBC 801 mm x kg/m W360×122 W360×101 W360×79 W360×64 W310×107 W310×86 W310×74 W310×60 W250×101 W250×80 W250×67 W/D kg/m/mm 0.09839 0.08252 0.07066 0.05818 0.08671 0.07624 0.07184 0.05929 0.09693 0.07828 0.06994 Concrete Masonry Density (kg/m3) Minimum Required Equivalent Thickness For Fire-resistance Rating of Concrete Masonry Protection Assembly Te (mm) 1-hour 2-hour 3-hour 4-hour 1280 18 39 58 75 1600 22 46 66 84 1760 24 49 70 89 1920 26 52 74 93 1280 21 42 61 79 1600 25 49 69 88 1760 27 52 73 92 1920 28 55 77 97 1280 23 45 65 82 1600 27 52 72 91 1760 29 54 76 95 1920 31 57 80 99 1280 25 48 68 86 1600 29 55 76 94 1760 31 57 79 98 1920 33 60 83 102 1280 20 42 61 78 1600 24 48 69 87 1760 26 51 72 92 1920 28 54 76 96 1280 22 44 63 81 1600 26 50 71 90 1760 28 53 75 94 1920 30 56 78 98 1280 23 45 65 82 1600 27 51 72 91 1760 29 54 76 95 1920 31 57 80 100 1280 25 49 68 86 1600 29 55 76 95 1760 31 57 79 99 1920 33 60 83 103 1280 19 40 59 76 1600 23 47 67 86 1760 25 50 71 90 1920 27 53 75 94 1280 22 44 63 81 1600 26 50 71 90 1760 28 53 75 94 1920 30 56 79 98 1280 23 46 66 83 1600 27 52 73 92 1760 29 55 77 96 1920 31 58 80 100 2007 4/93 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.5.1(5) – Continued FIRE RESISTANCE OF CONCRETE MASONRY PROTECTED STEEL COLUMNS Shape Designation in. x lb/ft W10×33 W8×40 W8×31 W8×24 W8×18 mm x kg/m W250�49.1 W200�59 W200�46.1 W200�35.9 W200�26.6 W/D kg/m/mm 0.05468 0.07108 0.05677 0.04904 0.03912 Concrete Masonry Density (kg/m3) Minimum Required Equivalent Thickness For Fire-resistance Rating of Concrete Masonry Protection Assembly Te (mm) 1-hour 2-hour 3-hour 4-hour 1280 27 50 70 88 1600 31 56 77 96 1760 32 59 81 100 1920 34 62 84 104 1280 23 46 66 84 1600 27 53 74 93 1760 29 55 77 97 1920 31 58 81 101 1280 26 50 70 88 1600 30 56 77 96 1760 32 59 81 100 1920 34 61 84 104 1280 28 52 72 90 1600 32 58 80 99 1760 34 61 83 102 1920 36 63 86 106 1280 31 55 76 94 1600 35 61 82 101 1760 36 63 85 105 1920 38 66 89 109 Note: Tabulated values assume 25-mm air gap between masonry and steel section. SBC 801 2007 4/94 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.5.1(6) FIRE RESISTANCE OF CLAY MASONRY PROTECTED STEEL COLUMNS Shape Designation W/D kg/m/mm Concrete Masonry Density (kg/m3) Minimum Required Equivalent Thickness For Fire-Resistance Rating of Concrete Masonry Protection Assembly, Te (mm) 1-hour 2-hour 3-hour 4-hour in. x lb/ft mm x kg/m W14×82 W360×122 0.09839 1920 2080 31 35 61 68 86 96 108 120 W14×68 W360×101 0.08252 1920 2080 34 38 64 71 89 99 112 123 W14×53 W360×79 0.07066 1920 2080 36 41 67 74 92 102 115 126 W14×43 W360×64 0.05818 1920 2080 39 43 70 77 95 105 118 129 W12×72 W310×107 0.08671 1920 2080 33 38 63 71 89 98 111 122 W12×58 W310×86 0.07624 1920 2080 35 40 66 73 91 101 114 125 W12×50 W310×74 0.07184 1920 2080 36 40 67 74 92 102 115 126 W12×40 W310×60 0.05929 W10×68 W250×101 0.09693 1920 2080 1920 2080 39 43 32 36 70 77 62 69 96 105 87 97 118 129 110 121 W10×54 W250×80 0.07828 1920 2080 35 40 66 73 91 101 114 125 W10×45 W250×67 0.06994 1920 2080 37 41 68 75 93 103 116 127 W10×33 W250×49.1 0.05468 1920 2080 40 45 71 79 97 106 120 131 W8×40 W200×59 0.07108 1920 2080 37 41 68 75 94 103 116 128 W8×31 W200×46.1 0.05677 1920 2080 40 45 71 78 97 106 120 131 W8×24 W200×35.9 0.04904 1920 2080 42 46 73 80 99 108 122 133 W8×18 W200×26.6 0.03912 1920 44 76 102 124 2080 49 83 111 135 Note: Tabulated values assume 25-mm air gap between masonry and steel section. SBC 801 2007 4/95 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.5.1(7) MINIMUM COVER (mm) FOR STEEL COLUMNS ENCASED IN NORMAL-WEIGHT CONCRETEa [FIGURE 4B.21.5.1(6)(c)] Shape Designation W/D Fire-Resistance Rating (hours) in. x lb/ft mm x kg/m kg/m/mm 1 1.5 2 3 4 W14×233 W360�347 0.146 25 25 25 40 55 W14×211 W360�314 0.133 25 25 25 40 55 W14×193 W360�287 0.123 25 25 25 40 55 W14×176 W360�262 0.113 25 25 25 40 55 W14×159 W360�237 0.103 25 25 25 40 60 W14×145 W360�216 0.094 25 25 25 45 60 W12×190 W310�283 0.144 25 25 25 45 60 W12×170 W310�253 0.130 25 25 25 45 60 W12×152 W310�226 0.118 25 25 30 45 60 W12×136 W310�202 0.106 25 25 30 45 65 W10×112 W250�167 0.104 25 25 30 50 70 W10×100 W250�149 0.094 25 25 35 50 70 W10×88 W250�131 0.084 25 25 35 55 70 W10×77 W250�115 0.074 25 25 35 55 70 W8×35 W200�52 0.043 25 30 45 65 85 W8×28 W200�41.7 0.039 25 35 45 70 90 W8×24 W200�35.9 0.034 25 35 45 70 90 W8×18 W200�26.6 0.028 25 40 50 70 95 a. The tabulated thicknesses are based upon the assumed properties of normalweight concrete given in Table 4B.21.5.1(2). TABLE 4B.21.5.1(8) MINIMUM COVER (mm) FOR STEEL COLUMNS ENCASED IN STRUCTURAL LIGHTWEIGHT CONCRETEa [FIGURE 4B.21.5.1(6)(c)] in. x lb/ft mm x kg/m W/D kg/m/mm W14×233 W360�347 W14×211 W360�314 W14×193 Shape Designation 1 1.5 2 3 4 0.146 25 25 25 30 40 0.133 25 25 25 30 40 W360�287 0.123 25 25 25 30 40 W14×176 W360�262 0.113 25 25 25 30 40 W14×159 W360�237 0.103 25 25 25 30 45 W14×145 W360�216 0.094 25 25 25 30 45 W12×190 W310�283 0.144 25 25 25 30 45 W12×170 W310�253 0.130 25 25 25 30 45 W12×152 W310�226 0.118 25 25 25 35 45 W12×136 W310�202 0.106 25 25 25 35 45 W10×112 W250�167 0.104 25 25 25 40 50 W10×100 W250�149 0.094 25 25 25 40 55 W10×88 W250�131 0.084 25 25 25 40 55 W10×77 W250�115 0.074 25 25 25 40 55 W8×35 W200�52 0.043 25 25 35 50 65 W8×28 W200�41.7 0.039 25 25 35 55 70 W8×24 W200�35.9 0.034 25 30 35 55 70 W200�26.6 0.028 25 30 40 60 75 W8×18 a. SBC 801 Fire-Resistance Rating (hours) The tabulated thicknesses are based upon the assumed properties of structural lightweight concrete given in Table 4B.21.5.1(2). 2007 4/96 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION TABLE 4B.21.5.1(9) MINIMUM COVER (mm) FOR STEEL COLUMNS IN NORMAL-WEIGHT PRECAST COVERSa [FIGURE 4B.21.5.1(6)(a)] Shape Designation a. Fire-Resistance Rating (hours) in. � lb/ft mm�kg/m W/D kg/m/mm 1 1.5 2 3 4 W14×233 W360�347 0.146 40 40 40 60 80 W14×211 W360�314 0.133 40 40 40 60 80 W14×193 W360�287 0.123 40 40 40 65 85 W14×176 W360�262 0.113 40 40 45 65 85 W14×159 W360�237 0.103 40 40 45 70 90 W14×145 W360�216 0.094 40 40 50 70 90 W12×190 W310�283 0.144 40 40 40 60 80 W12×170 W310�253 0.130 40 40 40 65 85 W12×152 W310�226 0.118 40 40 45 65 85 W12×136 W310�202 0.106 40 40 45 70 90 W10×112 W250�167 0.104 40 40 45 70 90 W10×100 W250�149 0.094 40 40 50 70 90 W10×88 W250�131 0.084 40 40 50 75 95 W10×77 W250�115 0.074 40 40 55 75 95 W8×35 W200�52 0.043 40 50 65 85 110 W8×28 W200�41.7 0.039 40 50 65 90 110 W8×24 W200�35.9 0.034 40 55 65 90 110 W8×18 W200�26.6 0.028 40 55 70 95 115 The tabulated thicknesses are based upon the assumed properties of normal- weight concrete given in Table 4B.21.5.1(2). TABLE 4B.21.5.1(10) MINIMUM COVER (mm) FOR STEEL COLUMNS IN STRUCTURAL LIGHTWEIGHT PRECAST COVERSa [FIGURE 4B.21.5.1(6)(a)] Shape Designation a. SBC 801 in. � lb/ft mm�kg/m W/D kg/m/mm W14×233 W360�347 W14×211 W14×193 Fire-Resistance Rating (hours) 1 1.5 2 3 4 0.146 40 40 40 40 60 W360�314 0.133 40 40 40 45 60 W360�287 0.123 40 40 40 45 65 W14×176 W360�262 0.113 40 40 40 50 65 W14×159 W360�237 0.103 40 40 40 50 65 W14×145 W360�216 0.094 40 40 40 55 70 W12×190 W310�283 0.144 40 40 40 45 60 W12×170 W310�253 0.130 40 40 40 45 60 W12×152 W310�226 0.118 40 40 40 50 65 W12×136 W310�202 0.106 40 40 40 50 70 W10×112 W250�167 0.104 40 40 40 50 70 W10×100 W250�149 0.094 40 40 40 55 70 W10×88 W250�131 0.084 40 40 40 55 75 W10×77 W250�115 0.074 40 40 40 60 75 W8×35 W200�52 0.043 40 40 50 70 90 W8×28 W200�41.7 0.039 40 40 55 75 90 W8×24 W200�35.9 0.034 40 45 55 75 95 W8×18 W200�26.6 0.028 40 45 55 80 95 The tabulated thicknesses are based upon the assumed properties of structural lightweight concrete given in Table 4B.21.5.1(2). 2007 4/97 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Structural steel beams and girders. The fire-resistance ratings of steel beams and girders shall be based upon the size of the element and the type of protection provided in accordance with this section. 4B.21.5.2.1 Determination of fire resistance. These procedures establish a basis for determining resistance of structural steel beams and girders which differ in size from that specified in approved fire-resistant assemblies as a function of the thickness of fire-resistant material and the weight (W) and heated perimeter (D) of the beam or girder. As used in these sections, W is the average weight of a structural steel member in kilograms per linear meter. The heated perimeter, D, is the inside perimeter of the fire-resistant material in millimeters as illustrated in Figure 4B.21.5.2. 4B.21.5.2.1.1 Weight-to-heated perimeter. The weight-to-heated-perimeter ratios (W/D), for both contour and box fire-resistant protection profiles, for some wide flange shapes used as beams or girders are given in Table 4B.21.5.1(4). For different shapes, the weight-to-heated-perimeter ratios (W/D) shall be determined in accordance with the definitions given in this section. 4B.21.5.2.1.2 Beam and girder substitutions. Except as provided for in Section 4B.21.5.2.2, structural steel beams in approved fire-resistant assemblies shall be considered the minimum permissible size. Other beam or girder shapes shall be permitted to be substituted provided that the weight-to-heated-perimeter ratio (W/D) of the substitute beam is equal to or greater than that of the beam specified in the approved assembly. 4B.21.5.2 FIGURE 4B.21.5.2 DETERMINATION OF THE HEATED PERIMETER OF STRUCTURAL STEEL BEAMS AND GIRDERS 4B.21.5.2.2 Spray-applied fire-resistant materials. The provisions in this section apply to unrestrained structural steel beams and girders protected with spray-applied fireresistant materials. Larger or smaller unrestrained beam and girder shapes shall be permitted to be substituted for beams specified in approved unrestrained or restrained fire-resistant assemblies provided that the thickness of the fire-resistant material is adjusted in accordance with the following expression: � �W / D1 � � 0.60 � h2 � � 1 � h1 �� �W2 / D2 � � 0.60 �� (Equation 4B.-17) Where: h = Thickness of spray-applied fire-resistant material in mm W = Weight of the structural steel beam or girder in kg/m D = Heated perimeter of the structural steel beam or girder in mm SBC 801 2007 4/98 TYPES OF CONSTRUCTION AND FIRE-RESISTANCE-RATED CONSTRUCTION Subscript 1 refers to the beam and fire-resistant material thickness in the approved assembly. Subscript 2 refers to the substitute beam or girder and the required thickness of fire-resistant material. 4B.21.5.2.2.1 Minimum thickness. Equation 4B.-17 is limited to beams with a weight-toheated-perimeter ratio (W/D) of 0.022 or greater. The minimum thickness of fireresistant material shall not be less than 10 mm. 4B.21.5.2.3 Structural steel trusses. The fire resistance of structural steel trusses protected with fire-resistant materials spray applied to each of the individual truss elements shall be permitted to be determined in accordance with this section. The thickness of the fire-resistant material shall be determined in accordance with Section 4B.21.5.1.3. The weight-to-heated-perimeter ratio (W/D) of truss elements which can be simultaneously exposed to fire on all sides shall be determined on the same basis as columns, as specified in Section 4B.21.5.1.1. The weight-to-heatedperimeter ratio (W/D) of truss elements which directly support floor or roof construction shall be determined on the same basis as beams and girders, as specified in Section 4B.21.5.2.1. SBC 801 2007 4/99 GENERAL PRECAUTIONS AGAINST FIRE CHAPTER 5 GENERAL PRECAUTIONS AGAINST FIRE, EMERGENCY PLANNING AND PREPAREDNESS FIRE SERVICE FEATURES BUILDING SERVICES AND SYSTEMS SECTION 5A GENERAL PRECAUTIONS AGAINST FIRE SECTION 5A.1 GENERAL 5A.1.1 Scope. The provisions of this section shall govern the occupancy and maintenance of all structures and premises for precautions against fire and the spread of fire. 5A.1.2 Permits. Permits shall be required as set forth in SBC 100 for the activities or uses regulated by Sections 5A.6, 5A.7, 5A.8.3, 5A.8.4, 5A.8.5 and 5A.15. SECTION 5A.2 DEFINITIONS 5A.2.1 Definitions. The following words and terms shall, for the purposes of this section and as used elsewhere in these code requirements, have the meanings shown herein. BONFIRE. An outdoor fire utilized for ceremonial purposes. HI-BOY. A cart used to transport hot roofing materials on a roof. OPEN BURNING. The burning of materials wherein products of combustion are emitted directly into the ambient air without passing through a stack or chimney from an enclosed chamber. Open burning does not include road flares, smudge pots and similar devices associated with safety or occupational uses typically considered open flames or recreational fires. For the purpose of this definition, a chamber shall be regarded as enclosed when, during the time combustion occurs, only apertures, ducts, stacks, flues or chimneys necessary to provide combustion air and permit the escape of exhaust gas are open. POWERED INDUSTRIAL TRUCK. A forklift, tractor, platform lift truck or motorized hand truck powered by an electrical motor or internal combustion engine. Powered industrial trucks do not include farm vehicles or automotive vehicles for highway use. RECREATIONAL FIRE. An outdoor fire burning materials other than rubbish where the fuel being burned is not contained in an incinerator, outdoor fireplace, barbeque grill or barbeque pit and has a total fuel area of 900 mm or less in diameter and 0.6 m or less in height for pleasure, ceremonial, cooking, warmth or similar purposes. SECTION 5A.3 ASPHALT KETTLES 5A.3.1 SBC 801 Transporting. Asphalt (tar) kettles shall not be transported over any highway, road or street when the heat source for the kettle is operating. 2007 5/1 GENERAL PRECAUTIONS AGAINST FIRE Exception: Asphalt (tar) kettles in the process of patching road surfaces. 5A.3.2 Location. Asphalt (tar) kettles shall not be located within 6.1 m of any combustible material, combustible building surface or any building opening and within a controlled area identified by the use of traffic cones, barriers or other approved means. Asphalt (tar) kettles and pots shall not be utilized inside or on the roof of a building or structure. Roofing kettles and operating asphalt (tar) kettles shall not block means of egress, gates, roadways or entrances. 5A.3.3 Location of fuel containers. Fuel containers shall be located at least 3 m from the burner. Exception: Containers properly insulated from heat or flame are allowed to be within 0.6 m of the burner. 5A.3.4 Attendant. An operating kettle shall be attended by a minimum of one employee knowledgeable of the operations and hazards. The employee shall be within 30.5 m of the kettle and have the kettle within sight. Ladders or similar obstacles shall not form a part of the route between the attendant and the kettle. 5A.3.5 Fire extinguishers. There shall be a portable fire extinguisher complying with Section 7.6 and with a minimum 40-B:C rating within 7.6 m of each asphalt (tar) kettle during the period such kettle is being utilized, and one additional portable fire extinguisher with a minimum 40-B:C rating on the roof being covered. 5A.3.6 Lids. Asphalt (tar) kettles shall be equipped with tight-fitting lids. 5A.3.7 Hi-boys. Hi-boys shall be constructed of noncombustible materials. Hi-boys shall be limited to a capacity of 208 L. Fuel sources or heating elements shall not be allowed as part of a hi-boy. 5A.3.8 Roofing kettles. Roofing kettles shall be constructed of noncombustible materials. 5A.3.9 Fuel containers under air pressure. Fuel containers that operate under air pressure shall not exceed 76 L in capacity and shall be approved. SECTION 5A.4 COMBUSTIBLE WASTE MATERIAL 5A.4.1 5A.4.1.1 5A.4.1.2 5A.4.1.3 SBC 801 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. Waste material. Accumulations of wastepaper, wood, hay, straw, weeds, litter or combustible or flammable waste or rubbish of any type shall not be permitted to remain on a roof or in any court, yard, vacant lot, alley, parking lot, open space, or beneath a grandstand, bleacher, pier, wharf, manufactured home, recreational vehicle or other similar structure. Vegetation. Weeds, grass, vines or other growth that is capable of being ignited and endangering property, shall be cut down and removed by the owner or occupant of the premises. Space underneath seats. Spaces underneath grandstand and bleacher seats shall be kept free from combustible and flammable materials. Except where enclosed in not less than 1 hour fire-resistance-rated construction in accordance with the 2007 5/2 GENERAL PRECAUTIONS AGAINST FIRE Chapter 4, spaces underneath grandstand and bleacher seats shall not be occupied or utilized for purposes other than means of egress. 5A.4.2 Storage. Storage of combustible rubbish shall not produce conditions that will create a nuisance or a hazard to the public health, safety or welfare. 5A.4.3 Containers. Combustible rubbish, and waste material kept within a structure shall be stored in accordance with Sections 5A.4.3.1 through 5A.4.3.3. Spontaneous ignition. Materials susceptible to spontaneous ignition, such as oily rags, shall be stored in a listed disposal container. Contents of such containers shall be removed and disposed of daily. Capacity exceeding 0.15 m3. Containers with a capacity exceeding 0.15 m3 shall be provided with lids. Containers and lids shall be constructed of noncombustible materials or approved combustible materials. Capacity exceeding 1.15 m3. Dumpsters and containers with an individual capacity of 1.15 m3 or more shall not be stored in buildings or placed within 1.5 m of combustible walls, openings or combustible roof eave lines. Exceptions: 1. Dumpsters or containers in areas protected by an approved automatic sprinkler system complying with Chapter 7. 2. Storage in a structure shall not be prohibited where the structure is of Type I or Type IIA construction, located not less than 3 m from other buildings and used exclusively for dumpster or container storage. 5A.4.3.1 5A.4.3.2 5A.4.3.3 SECTION 5A.5 IGNITION SOURCES 5A.5.1 Clearance from ignition sources. Clearance between ignition sources, such as light fixtures, heaters and flame-producing devices, and combustible materials shall be maintained in an approved manner. 5A.5.2 Hot ashes and spontaneous ignition sources. Hot ashes, cinders, smoldering coals or greasy or oily materials subject to spontaneous ignition shall not be deposited in a combustible receptacle, within 3 m of other combustible material including combustible walls and partitions or within 0.6 m of openings to buildings. Exception: The minimum required separation distance to other combustible materials shall be 0.6 m where the material is deposited in a covered, noncombustible receptacle placed on a noncombustible floor, ground surface or stand. 5A.5.3 Open-flame warning devices. Open-flame warning devices shall not be used along an excavation, road, or any place where the dislodgment of such device might permit the device to roll, fall or slide on to any area or land containing combustible material. 5A.5.4 Deliberate or negligent burning. It shall be unlawful to deliberately or through negligence set fire to or cause the burning of combustible material in such a manner as to endanger the safety of persons or property. SBC 801 2007 5/3 GENERAL PRECAUTIONS AGAINST FIRE SECTION 5A.6 MOTION PICTURE FILM AND SCREENS 5A.6.1 Motion picture projection rooms. Electric arc, xenon or other light source projection equipment which develops hazardous gases, dust or radiation and the projection of ribbon-type cellulose nitrate film, regardless of the light source used in projection, shall be operated within a motion picture projection room complying with Section 2.22 of SBC 201. 5A.6.2 Cellulose nitrate film storage. Storage of cellulose nitrate film shall be in accordance with NFPA 40. SECTION 5A.7 OPEN BURNING AND RECREATIONAL FIRES 5A.7.1 General. A person shall not kindle or maintain or authorize to be kindled or maintained any open burning unless conducted and approved in accordance with this section. 5A.7.2 Permit required. A permit shall be obtained from the building official in accordance with SBC 100 prior to kindling a fire for recognized silvicultural or range or wildlife management practices, prevention or control of disease or pests, or a bonfire. Application for such approval shall only be presented by and permits issued to the owner of the land upon which the fire is to be kindled. Authorization. Where required local law or regulations, open burning shall only be permitted with prior approval from the local air and water quality management authority, provided that all conditions specified in the authorization are followed. Prohibited open burning. Open burning that will be offensive or objectionable because of smoke or odor emissions when atmospheric conditions or local circumstances make such fires hazardous shall be prohibited. The building official is authorized to order the extinguishment by the permit holder or the Civil Defence of open burning which creates or adds to a hazardous or objectionable situation. 5A.7.2.1 5A.7.2.2 5A.7.3 5A.7.3.1 5A.7.3.2 5A.7.4 SBC 801 Location. The location for open burning shall not be less than 15.2 m from any structure, and provisions shall be made to prevent the fire from spreading to within 15.2 m of any structure. Exceptions: 1. Fires in approved containers that are not less than 4.6 m from a structure. 2. The minimum required distance from a structure shall be 7.6 m where the pile size is 900 mm or less in diameter and 0.6 m or less in height. Bonfires. A bonfire shall not be conducted within 15.2 m of a structure or combustible material unless the fire is contained in a barbecue pit. Conditions which could cause a fire to spread within 15.2 m of a structure shall be eliminated prior to ignition. Recreational fires. Recreational fires shall not be conducted within 7.6 m of a structure or combustible material. Conditions which could cause a fire to spread within 7.6 m of a structure shall be eliminated prior to ignition. Attendance. Open burning, bonfires or recreational fires shall be constantly attended until the fire is extinguished. A minimum of one portable fire extinguisher complying with Section 7.6 with a minimum 4-A rating or other approved on-site fire-extinguishing equipment, such as dirt, sand, water barrel, 2007 5/4 GENERAL PRECAUTIONS AGAINST FIRE garden hose or water truck, shall be available for immediate utilization. SECTION 5A.8 OPEN FLAMES 5A.8.1 General. This section shall control open flames, fire and burning on all premises. 5A.8.2 Where prohibited. A person shall not take or utilize an open flame or light in a structure, vessel, boat or other place where highly flammable, combustible or explosive material is utilized or stored. Lighting appliances shall be well-secured in a glass globe and wire mesh cage or a similar approved device. Throwing or placing sources of ignition. No person shall throw or place, or cause to be thrown or placed, a lighted match, cigar, cigarette, matches, or other flaming or glowing substance or object on any surface or article where it can cause an unwanted fire. 5A.8.2.1 Open flame. A person shall not utilize or allow to be utilized, an open flame in connection with a public meeting or gathering for purposes of deliberation, worship, entertainment, amusement, instruction, education, recreation, awaiting transportation or similar purpose in assembly or educational occupancies without first obtaining a permit in accordance with SBC 100. 5A.8.3.1 Open-flame cooking devices. Charcoal burners and other open-flame cooking devices shall not be operated on combustible balconies or within 3 m of combustible construction. Exceptions: 1. One- and two-family dwellings. 2. Where buildings, balconies and decks are protected by an automatic sprinkler system. 5A.8.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LPgas container with a water capacity greater than 1.14 kg shall not be located on combustible balconies or within 3 m of combustible construction. Exception: One- and two-family dwellings. 5A.8.3.2 Open-flame decorative devices. Open-flame decorative devices shall comply with all of the following restrictions: 1. Class I and Class II liquids and LP-gas shall not be used. 2. Liquid or solid-fueled lighting devices containing more than 237 ml of fuel must self-extinguish and not leak fuel at a rate of more than 1.26 ml per minute if tipped over. 3. The device or holder shall be constructed to prevent the spillage of liquid fuel or wax at the rate of more than 1.26 ml per minute when the device or holder is not in an upright position. 4. The device or holder shall be designed so that it will return to the upright position after being tilted to an angle of 45 degrees from vertical. Exception: Devices that self-extinguish if tipped over and do not spill fuel or wax at the rate of more than 1.26 ml per minute if tipped over. 5. The flame shall be enclosed except where openings on the side are not more than 9.5 mm diameter or where openings are on the top and the distance to the top is such that a piece of tissue paper placed on the top will not ignite in 10 seconds. 6. Chimneys shall be made of noncombustible materials and securely attached to the open-flame device. Exception: A chimney is not required to be attached to any open-flame device SBC 801 2007 5/5 5A.8.3 GENERAL PRECAUTIONS AGAINST FIRE 5A.8.3.3 5A.8.3.4 5A.8.3.5 5A.8.3.6 5A.8.3.7 5A.8.4 5A.8.4.1 5A.8.5 SBC 801 that will self-extinguish if the device is tipped over. 7. Fuel canisters shall be safely sealed for storage. 8. Storage and handling of combustible liquids shall be in accordance with Chapter 32. 9. Shades, where used, shall be made of noncombustible materials and securely attached to the open-flame device holder or chimney. 10. Candelabras with flame-lighted candles shall be securely fastened in place to prevent overturning, and shall be located away from occupants using the area and away from possible contact with drapes, curtains or other combustibles. Location near combustibles. Open flames such as from candles, lanterns, kerosene heaters, and gas-fired heaters shall not be located on or near decorative material or similar combustible materials. Aisles and exits. Candles shall be prohibited in areas where occupants stand, or in an aisle or exit. Ceremonies. When, in the opinion of the building official, adequate safeguards have been taken, participants in ceremonies are allowed to carry hand-held candles, and sandle wood burner. Hand-held candles and sandle wood burner shall not be passed from one person to another while lighted. Theatrical performances. Where approved, open-flame devices used in conjunction with theatrical performances are allowed to be used when adequate safety precautions have been taken in accordance with NFPA 160. Group A occupancies. Open-flame devices shall not be used in a Group A occupancy. Exceptions: 1. Open-flame devices are allowed to be used in the following situations, provided approved precautions are taken to prevent ignition of a combustible material or injury to occupants: 1.1 Where necessary for ceremonial purposes in accordance with Section 5A.8.3.5. 1.2 On stages and platforms as a necessary part of a performance in accordance with Section 5A.8.3.6. 1.3 Where candles on tables are securely supported on substantial noncombustible bases and the candle flames are protected. 2. Heat-producing equipment complying with Chapter 6 and the SBC 501. 3. Gas lights are allowed to be used provided adequate precautions satisfactory to the building official are taken to prevent ignition of combustible materials. Torches for removing paint. Persons utilizing a torch or other flame-producing device for removing paint from a structure shall provide a minimum of one portable fire extinguisher complying with Section 7.6 and with a minimum 4-A rating, two portable fire extinguishers, each with a minimum 2-A rating, or a water hose connected to the water supply on the premises where such burning is done. The person doing the burning shall remain on the premises 1 hour after the torch or flame-producing device is utilized. Permit. A permit in accordance with SBC 100 shall be secured from the building official prior to the utilization of a torch or flame-producing device to remove paint from a structure. Open-flame devices. Torches and other devices, machines or processes liable to start or cause fire shall not be operated or used in or upon hazardous fire areas, except by a permit in accordance with SBC 100 secured from the building official. Exception: Use within inhabited premises or designated campsites which are a 2007 5/6 GENERAL PRECAUTIONS AGAINST FIRE 5A.8.5.1 5A.8.5.2 minimum of 9.1 m from grass, grain, brush or forest-covered areas. Signals and markers. Flame-employing devices, such as lanterns or kerosene road flares, shall not be operated or used as a signal or marker in or upon hazardous fire areas. Exception: The proper use of fuses at the scenes of emergencies or as required by standard railroad operating procedures. Portable fueled open-flame devices. Portable open-flame devices fueled by flammable or combustible gases or liquids shall be enclosed or installed in such a manner as to prevent the flame from contacting combustible material. Exceptions: 1. LP-gas-fueled devices used for sweating pipe joints or removing paint in accordance with Chapter 36. 2. Cutting and welding operations in accordance with Chapter 24. 3. Torches or flame-producing devices in accordance with Section 5A.8.4. 4. Candles and open-flame decorative devices in accordance with Section 5A.8.3. SECTION 5A.9 POWERED INDUSTRIAL TRUCKS 5A.9.1 General. Powered industrial trucks shall be operated and maintained in accordance with this section. 5A.9.2 Battery chargers. Battery chargers shall be of an approved type. Combustible storage shall be kept a minimum of 900 mm from battery chargers. Battery charging shall not be conducted in areas accessible to the public. 5A.9.3 Ventilation. Ventilation shall be provided in an approved manner in batterycharging areas to prevent a dangerous accumulation of flammable gases. 5A.9.4 Fire extinguishers. Battery-charging areas shall be provided with a fire extinguisher complying with Section 7.6 having a minimum 4-A:20-B:C rating within 6.1 m of the battery charger. 5A.9.5 Refueling. Powered industrial trucks using liquid fuel or LP-gas shall be refueled outside of buildings or in areas specifically approved for that purpose and in accordance with Chapter 32 or 36. 5A.9.6 Repairs. Repairs to fuel systems, electrical systems and repairs utilizing open flame or welding shall be done in approved locations outside of buildings or in areas specifically approved for that purpose. SECTION 5A.10 SMOKING 5A.10.1 General. The smoking or carrying of a lighted pipe, cigar, cigarette or any other type of smoking paraphernalia or material is prohibited in the areas indicated in this section. 5A.10.2 Prohibited areas. Smoking shall be prohibited where conditions are such as to make smoking a hazard, and in spaces where flammable or combustible materials are stored or handled. SBC 801 2007 5/7 GENERAL PRECAUTIONS AGAINST FIRE 5A.10.3 “No Smoking” signs. The building official is authorized to order the posting of “No Smoking” signs in a conspicuous location in each structure or location in which smoking is prohibited. The content, lettering, size, color and location of required “No Smoking” signs shall be approved. 5A.10.4 Removal of signs prohibited. A posted “No Smoking” sign shall not be obscured, removed, defaced, mutilated or destroyed. 5A.10.5 Compliance with “No Smoking” signs. Smoking shall not be permitted nor shall a person smoke, throw or deposit any lighted or smoldering substance in any place where “No Smoking” signs are posted. 5A.10.6 Ash trays. Where smoking is permitted, suitable noncombustible ashtrays or match receivers shall be provided on each table and at other appropriate locations. 5A.10.7 Burning objects. Lighted matches, cigarettes, cigars or other burning object shall not be discarded in such a manner that could cause ignition of other combustible material. 5A.10.8 Hazardous environmental conditions. When the building official determines that hazardous environmental conditions necessitate controlled use of smoking materials, the ignition or use of such materials in mountainous, brush-covered or forest-covered areas or other designated areas is prohibited except in approved designated smoking areas. SECTION 5A.11 VACANT PREMISES 5A.11.1 5A.11.1.1 5A.11.1.2 5A.11.2 5A.11.2.1 5A.11.2.2 SBC 801 General. Temporarily unoccupied buildings, structures, premises or portions thereof, including tenant spaces, shall be safeguarded and maintained in accordance with this section. Abandoned premises. Buildings, structures and premises for which an owner cannot be identified or located by dispatch of a certificate of mailing to the last known or registered address, which persistently or repeatedly become unprotected or unsecured, which have been occupied by unauthorized persons or for illegal purposes, or which present a danger of structural collapse or fire spread to adjacent properties shall be considered abandoned, declared unsafe and abated by demolition or rehabilitation in accordance with the SBC 100. Tenant spaces. Storage and lease plans required by these code requirements shall be revised and updated to reflect temporary or partial vacancies. Safeguarding vacant premises. Temporarily unoccupied buildings, structures, premises or portions thereof shall be secured and protected in accordance with this section. Security. Exterior openings and interior openings accessible to other tenants or unauthorized persons shall be boarded, locked, blocked or otherwise protected to prevent entry by unauthorized individuals. Fire protection. Fire alarm, sprinkler and standpipe systems shall be maintained in an operable condition at all times. Exceptions: 1. When the premises have been cleared of all combustible materials and debris and, in the opinion of the building official, the type of construction, fire 2007 5/8 GENERAL PRECAUTIONS AGAINST FIRE 5A.11.2.3 separation distance and security of the premises do not create a fire hazard. 2. Where buildings will not be heated and fire protection systems will be exposed to freezing temperatures, fire alarm and sprinkler systems are permitted to be placed out of service and standpipes are permitted to be maintained as dry systems (without an automatic water supply) provided the building has no contents or storage, and windows, doors and other openings are secured to prohibit entry by unauthorized persons. Fire separation. Fire-resistance-rated partitions, fire barriers, and fire walls separating vacant tenant spaces from the remainder of the building shall be maintained. Openings, joints, and penetrations in fire-resistance-rated assemblies shall be protected in accordance with Chapter 4. 5A.11.3 Removal of combustibles. Persons owning, or in charge or control of, a vacant building or portion thereof, shall remove from all accumulations of combustible materials, flammable or combustible waste or rubbish and shall securely lock or otherwise secure doors, windows and other openings to prevent entry by unauthorized persons. The premises shall be maintained clear of waste or hazardous materials. Exceptions: 1. Buildings or portions of buildings undergoing additions, alterations, repairs, or change of occupancy in accordance with the SBC 201, where waste is controlled and removed as required by Section 5A.4. 2. Seasonally occupied buildings. 5A.11.4 Removal of hazardous materials. Persons owning or having charge or control of a vacant building containing hazardous materials regulated by Chapter 25 shall comply with the facility closure requirements of Section 25.1.6. SECTION 5A.12 VEHICLE IMPACT PROTECTION 5A.12.1 General. Vehicle impact protection required by these code requirements shall be provided by posts that comply with Section 5A.12.2 or by other approved physical barriers that comply with Section 5A.12.3. 5A.12.2 Posts. Guard posts shall comply with all of the following requirements: 1. Constructed of steel not less than 100 mm in diameter and concrete filled. 2. Spaced not more than 1.2 m between posts on center. 3. Set not less than 900 mm deep in a concrete footing of not less than a 381 mm diameter. 4. Set with the top of the posts not less than 900 mm above ground. 5. Located not less than 900 mm from the protected object. 5A.12.3 Other barriers. Physical barriers shall be a minimum of 900 mm in height and shall resist a force of 53,375 N applied 900 mm above the adjacent ground surface. SECTION 5A.13 FUELED EQUIPMENT 5A.13.1 SBC 801 Fueled equipment. Fueled equipment, including but not limited to motorcycles, mopeds, lawn-care equipment and portable cooking equipment, shall not be stored, operated or repaired within a building. 2007 5/9 GENERAL PRECAUTIONS AGAINST FIRE 5A.13.1.1 5A.13.2 Exceptions: 1. Buildings or rooms constructed for such use in accordance with the SBC. 2. Where allowed by Section 5A.13. Removal. The building official is authorized to require removal of fueled equipment from locations where the presence of such equipment is determined by the building official to be hazardous. Group R occupancies. Vehicles powered by flammable liquids, Class II combustible liquids, or compressed flammable gases shall not be stored within the living space of Group R buildings and shall be separated from other occupancies in accordance with the SBC. SECTION 5A.14 INDOOR DISPLAYS 5A.14.1 General. Indoor displays constructed within any occupancy shall comply with Sections 5A.14.2 through 5A.14.4. 5A.14.2 Fixtures and displays. Fixtures and displays of goods for sale to the public shall be arranged so as to maintain free, immediate and unobstructed access to exits as required by Chapter 8. 5A.14.3 Highly combustible goods. The display of highly combustible goods, including but not limited to fireworks, flammable or combustible liquids, liquefied flammable gases, oxidizing materials, pyroxylin plastics and agricultural goods, in main exit access aisles, corridors, covered malls, or within 1.5 m of entrances to exits and exterior exit doors is prohibited when a fire involving such goods would rapidly prevent or obstruct egress. 5A.14.4 Vehicles. Liquid or gas-fueled vehicles, boats or other motorcraft shall not be located indoors except as follows: 1. Batteries are disconnected. 2. Fuel in fuel tanks does not exceed one-quarter tank or 19 L (whichever is least). 3. Fuel tanks and fill openings are closed and sealed to prevent tampering. 4. Vehicles, boats or other motorcraft equipment are not fueled or defueled within the building. SECTION 5A.15 MISCELLANEOUS COMBUSTIBLE MATERIALS STORAGE 5A.15.1 General. Storage, use and handling of miscellaneous combustible materials shall be in accordance with this section. A permit shall be obtained in accordance with SBC 100. 5A.15.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. Ceiling clearance. Storage shall be maintained 0.6 m or more below the ceiling in nonsprinklered areas of buildings or a minimum of 457 mm below sprinkler head deflectors in sprinklered areas of buildings. Means of egress. Combustible materials shall not be stored in exits or exit 5A.15.2.1 5A.15.2.2 SBC 801 2007 5/10 GENERAL PRECAUTIONS AGAINST FIRE 5A.15.2.3 5A.15.2.4 5A.15.3 5A.15.3.1 5A.15.3.2 enclosures. Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 44.5 mm in thickness. Storage shall not be placed on exposed joists. Exceptions: 1. Areas protected by approved automatic sprinkler systems. 2. Group R-3 and Group U occupancies. Outside storage. Outside storage of combustible materials shall not be located within 3 m of a property line. Exceptions: 1. The separation distance is allowed to be reduced to 900 mm for storage not exceeding 1.8 m in height. 2. The separation distance is allowed to be reduced when the building official determines that no hazard to the adjoining property exists. Storage beneath overhead projections from buildings. Combustible materials stored or displayed outside of buildings that are protected by automatic sprinklers shall not be stored or displayed under nonsprinklered eaves, canopies or other projections or overhangs. Height. Storage in the open shall not exceed 6.1 m in height. SECTION 5B EMERGENCY PLANNING AND PREPAREDNESS SECTION 5B.1 GENERAL 5B.1.1 Scope. Reporting of emergencies, coordination with emergency response forces, emergency plans, and procedures for managing or responding to emergencies shall comply with the provisions of this section. Exception: Firms that have approved on-premises fire-fighting organizations and that are in compliance with approved procedures for fire reporting. 5B.1.2 Approval. Where required by these code requirements, fire safety plans, emergency procedures, and employee training programs shall be approved by the building official. 5B.1.3 Emergency forces notification. In the event an unwanted fire occurs on a property, the owner or occupant shall immediately report such condition to the fire department. Building employees and tenants shall implement the appropriate emergency plans and procedures. No person shall, by verbal or written directive, require any delay in the reporting of a fire to the fire department. Making false report. It shall be unlawful for a person to give, signal, or transmit a false alarm. Alarm activations. Upon activation of a fire alarm signal, employees or staff shall immediately notify the fire department. 5B.1.3.1 5B.1.3.2 SBC 801 2007 5/11 GENERAL PRECAUTIONS AGAINST FIRE 5B.1.3.3 Emergency evacuation drills. Nothing in this section shall prohibit the sounding of a fire alarm signal for the carrying out of an emergency evacuation drill in accordance with the provisions of Section 5B.5. 5B.1.4 Interference with fire department operations. It shall be unlawful to interfere with, attempt to interfere with, conspire to interfere with, obstruct or restrict the mobility of or block the path of travel of a fire department emergency vehicle in any way, or to interfere with, attempt to interfere with, conspire to interfere with, obstruct or hamper any fire department operation. 5B.1.5 Security device. Any security device or system that emits any medium that could obscure a means of egress in any building, structure or premise shall be prohibited. SECTION 5B.2 DEFINITIONS 5B.2.1 Definition. The following word and term shall, for the purposes of this section and as used elsewhere in these code requirements, have the meaning shown herein. EMERGENCY EVACUATION DRILL. An exercise performed to train staff and occupants and to evaluate their efficiency and effectiveness in carrying out emergency evacuation procedures. SECTION 5B.3 PUBLIC ASSEMBLAGES AND EVENTS 5B.3.1 5B.3.1.1 5B.3.1.2 SBC 801 General. When, in the opinion of the building official, it is essential for public safety in a place of assembly or any other place where people congregate, because of the number of persons, or the nature of the performance, exhibition, display, contest or activity, the owner, agent or lessee shall provide one or more fire watch personnel, as required and approved, to remain on duty during the times such places are open to the public, or when such activity is being conducted. The fire watch personnel shall keep diligent watch for fires, obstructions to means of egress and other hazards during the time such place is open to the public or such activity is being conducted and take prompt measures for remediation of hazards, extinguishment of fires that occur and assist in the evacuation of the public from the structures. Public safety plan. In other than Group A or E occupancies, where the building official determines that an indoor or outdoor gathering of persons has an adverse impact on public safety through diminished access to buildings, structures, fire hydrants and fire apparatus access roads or where such gatherings adversely affect public safety services of any kind, the building official shall have the authority to order the development of, or prescribe a plan for, the provision of an approved level of public safety. Contents. The public safety plan, where required by Section 5B.3.1.1, shall address such items as emergency vehicle ingress and egress, fire protection, emergency medical services, public assembly areas and the directing of both attendees and vehicles (including the parking of vehicles), vendor and food concession distribution, and the need for the presence of law enforcement, and fire and emergency medical services personnel at the event. 2007 5/12 GENERAL PRECAUTIONS AGAINST FIRE SECTION 5B.4 FIRE SAFETY AND EVACUATION PLANS 5B.4.1 General. Fire safety and evacuation plans shall comply with the requirements of this section. 5B.4.2 Where required. An approved fire safety and evacuation plan shall be prepared and maintained for the following occupancies and buildings. 1. Group A, other than Group A occupancies used exclusively for purposes of mosques that have an occupant load less than 2,000. 2. Group E. 3. Group H. 4. Group I. 5. Group R-1. 6. Group R-4. 7. High-rise buildings. 8. Group M buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. 2 9. Covered malls exceeding 4,645 m in aggregate floor area. 10. Underground buildings. 11. Buildings with an atrium and having an occupancy in Group A, E or M. 5B.4.3 Contents. Fire safety and evacuation plan contents shall be in accordance with Sections 5B.4.3.1 and 5B.4.3.2. Fire evacuation plans. Fire evacuation plans shall include the following: 1. Emergency egress or escape routes and whether evacuation of the building is to be complete or, where approved, by selected floors or areas only. 2. Procedures for employees who must remain to operate critical equipment before evacuating. 3. Procedures for accounting for employees and occupants after evacuation has been completed. 4. Identification and assignment of personnel responsible for rescue or emergency medical aid. 5. The preferred and any alternative means of notifying occupants of a fire or emergency. 6. The preferred and any alternative means of reporting fires and other emergencies to the fire department or designated emergency response organization. 7. Identification and assignment of personnel who can be contacted for further information or explanation of duties under the plan. 8. A description of the emergency voice/alarm communication system alert tone and preprogrammed voice messages, where provided. Fire safety plans. Fire safety plans shall include the following: 1. The procedure for reporting a fire or other emergency. 2. The life safety strategy and procedures for notifying, relocating, or evacuating occupants. 3. Site plans indicating the following: 3.1 The occupancy assembly point. 3.2 The locations of fire hydrants. 3.3 The normal routes of fire department vehicle access. 4. Floor plans identifying the locations of the following: 4.1 Exits. 2007 5/13 5B.4.3.1 5B.4.3.2 SBC 801 GENERAL PRECAUTIONS AGAINST FIRE 4.2 Primary evacuation routes. 4.3 Secondary evacuation routes. 4.4 Accessible egress routes. 4.5 Areas of refuge. 4.6 Manual fire alarm boxes. 4.7 Portable fire extinguishers. 4.8 Occupant-use hose stations. 4.9 Fire alarm annunciators and controls. 5. A list of major fire hazards associated with the normal use and occupancy of the premises, including maintenance and housekeeping procedures. 6. Identification and assignment of personnel responsible for maintenance of systems and equipment installed to prevent or control fires. 7. Identification and assignment of personnel responsible for maintenance, housekeeping and controlling fuel hazard sources. 5B.4.4 Maintenance. Fire safety and evacuation plans shall be reviewed or updated annually or as necessitated by changes in staff assignments, occupancy, or the physical arrangement of the building. 5B.4.5 Availability. Fire safety and evacuation plans shall be available in the workplace for reference and review by employees, and copies shall be furnished to the building official for review upon request. SECTION 5B.5 EMERGENCY EVACUATION DRILLS 5B.5.1 General. Emergency evacuation drills complying with the provisions of this section shall be conducted in the occupancies listed in Section 5B.4.2 or when required by the building official. Drills shall be designed in cooperation with the local authorities. 5B.5.2 Frequency. Required emergency evacuation drills shall be held at the intervals specified in Table 5B.5.2 or more frequently where necessary to familiarize all occupants with the drill procedure. 5B.5.3 Leadership. Responsibility for the planning and conduct of drills shall be assigned to competent persons designated to exercise leadership. 5B.5.4 Time. Drills shall be held at unexpected times and under varying conditions to simulate the unusual conditions that occur in case of fire. 5B.5.5 Record keeping. Records shall be maintained of required emergency evacuation drills and include the following information: 1. Identity of the person conducting the drill. 2. Date and time of the drill. 3. Notification method used. 4. Staff members on duty and participating. 5. Number of occupants evacuated. 6. Special conditions simulated. 7. Problems encountered. 8. Weather conditions when occupants were evacuated. 9. Time required to accomplish complete evacuation. SBC 801 2007 5/14 GENERAL PRECAUTIONS AGAINST FIRE 5B.5.6 Notification. Where required by the building official, prior notification of emergency evacuation drills shall be given to the building official. TABLE 5B.5.2 FIRE AND EVACUATION DRILL FREQUENCY AND PARTICIPATION GROUP OR OCCUPANCY FREQUENCY PARTICIPATION Group A Quarterly Employees a. b. Group E Monthlya All occupants Group I Quarterly on each shift Employeesb Group R-1 Quarterly on each shift Employees Group R-4 Quarterly on each shift Employeesb The frequency shall be allowed to be modified in accordance with Section 5B.8.3.2. Fire and evacuation drills in residential care assisted living facilities shall include complete evacuation of the premises in accordance with Section 5B.8.10.5. Where occupants receive habilitation or rehabilitation training, fire prevention and fire safety practices shall be included as part of the training program. 5B.5.7 Initiation. Where a fire alarm system is provided, emergency evacuation drills shall be initiated by activating the fire alarm system. 5B.5.8 Accountability. As building occupants arrive at the assembly point, efforts shall be made to determine if all occupants have been successfully evacuated or have been accounted for. 5B.5.9 Recall and reentry. An electrically or mechanically operated signal used to recall occupants after an evacuation shall be separate and distinct from the signal used to initiate the evacuation. The recall signal initiation means shall be manually operated and under the control of the person in charge of the premises or the official in charge of the incident. No one shall reenter the premises until authorized to do so by the official in charge. SECTION 5B.6 EMPLOYEE TRAINING AND RESPONSE PROCEDURES 5B.6.1 General. Employees in the occupancies listed in Section 5B.4.2 shall be trained in the fire emergency procedures described in their fire evacuation and fire safety plans. Training shall be based on these plans and as described in Section 5B.4.3. 5B.6.2 Frequency. Employees shall receive training in the contents of fire safety and evacuation plans and their duties as part of new employee orientation and at least annually thereafter. Records shall be kept and made available to the building official upon request. 5B.6.3 Employee training program. Employees shall be trained in fire prevention, evacuation and fire safety in accordance with Sections 5B.6.3.1 through 5B.6.3.3. Fire prevention training. Employees shall be apprised of the fire hazards of the 5B.6.3.1 SBC 801 2007 5/15 GENERAL PRECAUTIONS AGAINST FIRE 5B.6.3.2 5B.6.3.3 materials and processes to which they are exposed. Each employee shall be instructed in the proper procedures for preventing fires in the conduct of their assigned duties. Evacuation training. Employees shall be familiarized with the fire alarm and evacuation signals, their assigned duties in the event of an alarm or emergency, evacuation routes, areas of refuge, exterior assembly areas, and procedures for evacuation. Fire safety training. Employees assigned fire-fighting duties shall be trained to know the locations and proper use of portable fire extinguishers or other manual fire-fighting equipment and the protective clothing or equipment required for its safe and proper use. SECTION 5B.7 HAZARD COMMUNICATION 5B.7.1 General. The provisions of Sections 5B.7.2 through 5B.7.7 shall be applicable where hazardous materials subject to permits under Section 25.1.5 are located on the premises or where required by the building official. 5B.7.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. 5B.7.3 Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable local regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 25.3.5. 5B.7.4 Training. Persons responsible for the operation of areas in which hazardous materials are stored, dispensed, handled or used shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of a fire, leak or spill. Responsible persons shall be designated and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses and identification of the locations where hazardous materials are located, and shall have access to Material Safety Data Sheets and be knowledgeable in the site emergency response procedures. 5B.7.5 Hazardous Materials Inventory Statement. Where required by the building official, each application for a permit shall include a Hazardous Materials Inventory Statement (HMIS) in accordance with Section 25.1.5.2. 5B.7.6 Hazardous Materials Management Plan. Where required by the building official, each application for a permit shall include a Hazardous Materials Management Plan (HMMP) in accordance with Section 25.1.5.1. The building official is authorized to accept a similar plan required by other regulations. 5B.7.7 Facility closure plans. The permit holder or applicant shall submit to the building official a facility closure plan in accordance with Section 25.1.6.3 to terminate storage, dispensing, handling or use of hazardous materials. SBC 801 2007 5/16 GENERAL PRECAUTIONS AGAINST FIRE SECTION 5B.8 USE AND OCCUPANCY-RELATED REQUIREMENTS 5B.8.1 General. In addition to the other requirements of this section, the provisions of this section are applicable to specific occupancies listed herein. 5B.8.2 Group A occupancies. Group A occupancies shall comply with the requirements of Sections 5B.8.2.1 and 5B.8.2.2 and Sections 5B.1 through 5B.6. Seating plan. The fire safety and evacuation plans for assembly occupancies shall include the information required by Section 5B.4.3 and a detailed seating plan, occupant load, and occupant load limit. Deviations from the approved plans shall be allowed provided the occupant load limit for the occupancy is not exceeded and the aisles and exit access ways remain unobstructed. Announcements. In theaters, motion picture theaters, auditoriums and similar assembly occupancies in Group A used for non-continuous programs, an audible announcement shall be made not more than 10 minutes prior to the start of each program to notify the occupants of the location of the exits to be used in the event of a fire or other emergency. Exception: In motion picture theaters, the announcement is allowed to be projected upon the screen in a manner approved by the building official. 5B.8.2.1 5B.8.2.2 5B.8.3 5B.8.3.1 5B.8.3.2 5B.8.3.3 5B.8.3.4 5B.8.4 5B.8.4.1 5B.8.4.2 5B.8.4.3 SBC 801 Group E occupancies. Group E occupancies shall comply with the requirements of Sections 5B.8.3.1 through 5B.8.3.4 and Sections 5B.1 through 5B.6. First emergency evacuation drill. The first emergency evacuation drill of each school year shall be conducted within 10 days of the beginning of classes. Emergency evacuation drill deferral. In severe climates, the building official shall have the authority to modify the emergency evacuation drill frequency specified in Section 5B.5.2. Time of day. Emergency evacuation drills shall be conducted at different hours of the day or evening, during the changing of classes, when the school is at assembly, during the recess or gymnastic periods, or during other times to avoid distinction between drills and actual fires. Assembly points. Outdoor assembly areas shall be designated and shall be located a safe distance from the building being evacuated so as to avoid interference with fire department operations. The assembly areas shall be arranged to keep each class separate to provide accountability of all individuals. Group H-5 occupancies. Group H-5 occupancies shall comply with the requirements of Sections 5B.8.4.1 through 5B.8.4.4 and Sections 5B.1 through 5B.7. Plans and diagrams. In addition to the requirements of Section 5B.4 and Section 5B.7.6, plans and diagrams shall be maintained in approved locations indicating the approximate plan for each area, the amount and type of HPM stored, handled and used, locations of shutoff valves for HPM supply piping, emergency telephone locations and locations of exits. Plan updating. The plans and diagrams required by Section 5B.8.4.1 shall be maintained up to date and the building official and fire department shall be informed of all major changes. Emergency response team. Responsible persons shall be designated the on-site emergency response team and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses, identifying locations where HPM is stored, handled and used, and be 2007 5/17 GENERAL PRECAUTIONS AGAINST FIRE 5B.8.4.4 5B.8.5 5B.8.5.1 5B.8.5.2 5B.8.5.3 5B.8.5.4 5B.8.5.5 5B.8.6 5B.8.6.1 5B.8.6.2 5B.8.7 5B.8.7.1 5B.8.7.2 SBC 801 familiar with the chemical nature of such material. An adequate number of personnel for each work shift shall be designated. Emergency drills. Emergency drills of the on-site emergency response team shall be conducted on a regular basis but not less than once every three months. Records of drills conducted shall be maintained. Group I-1 occupancies. Group I-1 occupancies shall comply with the requirements of Sections 5B.8.5.1 through 5B.8.5.5 and Sections 5B.1 through 5B.6. Fire safety and evacuation plan. The fire safety and evacuation plan required by Section 5B.4 shall include special staff actions including fire protection procedures necessary for residents and shall be amended or revised upon admission of any resident with unusual needs. Staff training. Employees shall be periodically instructed and kept informed of their duties and responsibilities under the plan. Such instruction shall be reviewed by the staff at least every two months. A copy of the plan shall be readily available at all times within the facility. Resident training. Residents capable of assisting in their own evacuation shall be trained in the proper actions to take in the event of a fire. The training shall include actions to take if the primary escape route is blocked. Where the resident is given rehabilitation or habilitation training, training in fire prevention and actions to take in the event of a fire shall be a part of the rehabilitation training program. Residents shall be trained to assist each other in case of fire to the extent their physical and mental abilities permit them to do so without additional personal risk. Drill frequency. Emergency evacuation drills shall be conducted at least six times per year, two times per year on each shift. Twelve drills shall be conducted in the first year of operation. Drills are not required to comply with the time requirements of Section 5B.5.4. Resident participation. Emergency evacuation drills shall involve the actual evacuation of all residents to a selected assembly point. Group I-2 occupancies. Group I-2 occupancies shall comply with the requirements of Sections 5B.8.6.1 and 5B.8.6.2 and Sections 5B.1 through 5B.6. Drills are not required to comply with the time requirements of Section 5B.5.4. Evacuation not required. During emergency evacuation drills, the movement of patients to safe areas or to the exterior of the building is not required. Coded alarm signal. When emergency evacuation drills are conducted after visiting hours or when patients or residents are expected to be asleep, a coded announcement is allowed instead of audible alarms. Group I-3 occupancies. Group I-3 occupancies shall comply with the requirements of Sections 5B.8.7.1 through 5B.8.7.4 and Sections 5B.1 through 5B.6. Employee training. Employees shall be instructed in the proper use of portable fire extinguishers and other manual fire suppression equipment. Training of new staff shall be provided promptly upon entrance on duty. Refresher training shall be provided at least annually. Staffing. Group I-3 occupancies shall be provided with 24-hour staffing. Staff shall be within three floors or 91.5 m horizontal distance of the access door of each resident housing area. In Use Conditions 3, 4 and 5, as defined in Chapter 1, the arrangement shall be such that the staff involved can start release of locks necessary for emergency evacuation or rescue and initiate other necessary 2007 5/18 GENERAL PRECAUTIONS AGAINST FIRE 5B.8.7.3 5B.8.7.4 5B.8.8 5B.8.8.1 5B.8.8.2 5B.8.8.3 5B.8.9 5B.8.9.1 5B.8.9.2 5B.8.9.3 5B.8.10 5B.8.10.1 5B.8.10.2 5B.8.10.3 SBC 801 emergency actions within 2 minutes of an alarm. Exception: Staff shall not be required to be within three floors or 91.5 m in areas in which all locks are unlocked remotely and automatically in accordance with Section 2.21 of SBC 201. Notification. Provisions shall be made for residents in Use Conditions 3, 4 and 5, as defined in Chapter 1, to readily notify staff of an emergency. Keys. Keys necessary for unlocking doors installed in a means of egress shall be individually identifiable by both touch and sight. Group R-1 occupancies. Group R-1 occupancies shall comply with the requirements of Sections 5B.8.8.1 through 5B.8.8.3 and Sections 5B.1 through 5B.6. Evacuation diagrams. A diagram depicting two evacuation routes shall be posted on or immediately adjacent to every required egress door from each hotel, motel or dormitory guestroom. Emergency duties. Upon discovery of a fire or suspected fire, hotel, motel and dormitory employees shall perform the following duties: 1. Activate the fire alarm system, where provided. 2. Notify the public fire department. 3. Take other action as previously instructed. Fire safety and evacuation instructions. Information shall be provided in the fire safety and evacuation plan required by Section 5B.4 to allow guests to decide whether to evacuate to the outside, evacuate to an area of refuge, remain in place, or any combination of the three. Group R-2 occupancies. Group R-2 occupancies shall comply with the requirements of Sections 5B.8.9.1 through 5B.8.9.3 and Sections 5B.1 through 5B.6. Emergency guide. A fire emergency guide shall be provided which describes the location, function and use of fire protection equipment and appliances accessible to residents, including fire alarm systems, smoke alarms, and portable fire extinguishers. The guide shall also include an emergency evacuation plan for each dwelling unit. Maintenance. Emergency guides shall be reviewed and approved in accordance with Section 5B.1.2. Distribution. A copy of the emergency guide shall be given to each tenant prior to initial occupancy. Group R-4 occupancies. Group R-4 occupancies shall comply with the requirements of Sections 5B.8.10.1 through 5B.8.10.5 and Sections 5B.1 through 5B.6. Fire safety and evacuation plan. The fire safety and evacuation plan required by Section 5B.4 shall include special staff actions, including fire protection procedures necessary for residents, and shall be amended or revised upon admission of a resident with unusual needs. Staff training. Employees shall be periodically instructed and kept informed of their duties and responsibilities under the plan. Such instruction shall be reviewed by the staff at least every two months. A copy of the plan shall be readily available at all times within the facility. Resident training. Residents capable of assisting in their own evacuation shall be trained in the proper actions to take in the event of a fire. The training shall include actions to take if the primary escape route is blocked. Where the resident is given 2007 5/19 GENERAL PRECAUTIONS AGAINST FIRE 5B.8.10.4 5B.8.10.5 rehabilitation or habilitation training, training in fire prevention and actions to take in the event of a fire shall be a part of the rehabilitation training program. Residents shall be trained to assist each other in case of fire to the extent their physical and mental abilities permit them to do so without additional personal risk. Drill frequency. Emergency evacuation drills shall be conducted at least six times per year, two times per year on each shift. Twelve drills shall be conducted in the first year of operation. Drills are not required to comply with the time requirements of Section 5B.5.4. Resident participation. Emergency evacuation drills shall involve the actual evacuation of all residents to a selected assembly point and shall provide residents with experience in exiting through all required exits. All required exits shall be used during emergency evacuation drills. Exception: Actual exiting from windows shall not be required. Opening the window and signaling for help shall be an acceptable alternative. Covered mall buildings. Covered mall buildings shall comply with the provisions of Sections 5B.8.11.1 through 5B.8.11.3. 5B.8.11.1 Lease plan. A lease plan shall be prepared for each covered mall building. The plan shall include the following information in addition to that required by Section 5B.4.3.2: 1. Each occupancy, including identification of tenant. 2. Exits from each tenant space. 3. Fire protection features, including the following: 3.1 Fire department connections. 3.2 Fire command center. 3.3 Smoke management system controls. 3.4 Elevators and elevator controls. 3.5 Hose valves outlets. 3.6 Sprinkler and standpipe control valves. 3.7 Automatic fire-extinguishing system areas. 3.8 Automatic fire detector zones. 3.9 Fire barriers. 5B.8.11.1.1 Approval. The lease plan shall be submitted to the building official for approval, and shall be maintained on site for immediate reference by responding fire service personnel. 5B.8.11.1.2 Revisions. The lease plans shall be revised annually or as often as necessary to keep them current. Modifications or changes in tenants or occupancies shall not be made without prior approval of the building official and building official. 5B.8.11.2 Tenant identification. Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background. Exception: Tenant identification is not required for anchor stores. 5B.8.11.3 Maintenance. Unoccupied tenant spaces shall be: 1. Kept free from the storage of any materials. 2. Separated from the remainder of the building by partitions of at least 12.7-mmthick gypsum board or an approved equivalent to the underside of the ceiling of the adjoining tenant spaces. 3. Without doors or other access openings other than one door that shall be kept key locked in the closed position except during that time when opened for inspection. 4. Kept free from combustible waste and bedroom-swept clean. SBC 801 2007 5/20 5B.8.11 GENERAL PRECAUTIONS AGAINST FIRE SECTION 5C FIRE SERVICE FEATURES SECTION 5C.1 GENERAL 5C.1.1 Scope. Fire service features for buildings, structures and premises shall comply with this section. 5C.1.2 Permits. A permit shall be required as set forth in SBC 100. 5C.1.3 Construction documents. Construction documents for proposed fire apparatus access, location of fire lanes and construction documents and hydraulic calculations for fire hydrant systems shall be submitted to the Civil Defence for review and approval prior to construction. 5C.1.4 Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles in accordance with Section 5C.5.2. SECTION 5C.2 DEFINITIONS 5C.2.1 Definitions. The following words and terms shall, for the purposes of this section and as used elsewhere in these code requirements, have the meanings shown herein. FIRE APPARATUS ACCESS ROAD. A road that provides fire apparatus access from a fire station to a facility, building or portion thereof. This is a general term inclusive of all other terms such as fire lane, public street, private street, parking lot lane and access roadway. FIRE COMMAND CENTER. The principal attended or unattended location where the status of the detection, alarm communications and control systems is displayed, and from which the system(s) can be manually controlled. CIVIL DEFENCE MASTER KEY. A limited issue key of special or controlled design to be carried by Civil Defence officials in command which will open key boxes on specified properties. FIRE LANE. A road or other passageway developed to allow the passage of fire apparatus. A fire lane is not necessarily intended for vehicular traffic other than fire apparatus. KEY BOX. A secure, tamperproof device with a lock operable only by a Civil Defence master key, and containing building entry keys and other keys that may be required for access in an emergency. SBC 801 2007 5/21 GENERAL PRECAUTIONS AGAINST FIRE SECTION 5C.3 FIRE APPARATUS ACCESS ROADS 5C.3.1 5C.3.1.1 5C.3.1.2 5C.3.1.3 5C.3.2 5C.3.2.1 5C.3.2.2 5C.3.2.3 5C.3.2.4 5C.3.2.5 5C.3.2.6 5C.3.2.7 SBC 801 Where required. Fire apparatus access roads shall be provided and maintained in accordance with Sections 5C.3.1.1 through 5C.3.1.3. Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 45.7 m of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The building official is authorized to increase the dimension of 45.7 m where: 1. The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1, 7.3.3.1.2 or 7.3.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, water ways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies. Additional access. The building official is authorized to require more than one fire apparatus access road based on the potential for impairment of a single road by vehicle congestion, condition of terrain, climatic conditions or other factors that could limit access. High-piled storage. Civil Defence vehicle access to buildings used for high-piled combustible storage shall comply with the applicable provisions of Chapter 21. Specifications. Fire apparatus access roads shall be installed and arranged in accordance with Sections 5C.3.2.1 through 5C.3.2.7. Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 6.1 m, except for approved security gates in accordance with Section 5C.3.6, and an unobstructed vertical clearance of not less than 4.1 m. Authority. The building official shall have the authority to require an increase in the minimum access widths where they are inadequate for fire or rescue operations. Surface. Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide allweather driving capabilities. Turning radius. The required turning radius of a fire apparatus access road shall be determined by the building official. Dead ends. Dead-end fire apparatus access roads in excess of 45.7 m in length shall be provided with an approved area for turning around fire apparatus. Bridges and elevated surfaces. Where a bridge or an elevated surface is part of a fire apparatus access road, the bridge shall be constructed and maintained in accordance with MOT standards or (AASHTO Standard Specification for Highway Bridges). Bridges and elevated surfaces shall be designed for a live load sufficient to carry the imposed loads of fire apparatus. Vehicle load limits shall be posted at both entrances to bridges when required by the building official. Where elevated surfaces designed for emergency vehicle use are adjacent to surfaces which are not designed for such use, approved barriers, approved signs or both shall be installed and maintained when required by the building official. Grade. The grade of the fire apparatus access road shall be within the limits established by the building official based on the Civil Defence’s apparatus. 2007 5/22 GENERAL PRECAUTIONS AGAINST FIRE 5C.3.3 Marking. Where required by the building official, approved signs or other approved notices shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs or notices shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. 5C.3.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 5C.3.2.1 shall be maintained at all times. 5C.3.5 Required gates or barricades. The building official is authorized to require the installation and maintenance of gates or other approved barricades across fire apparatus access roads, trails or other accessways, not including public streets, alleys or highways. Secured gates and barricades. When required, gates and barricades shall be secured in an approved manner. Roads, trails and other accessways that have been closed and obstructed in the manner prescribed by Section 5C.3.5 shall not be trespassed on or used unless authorized by the owner and the building official. Exception: The restriction on use shall not apply to public officers acting within the scope of duty. 5C.3.5.1 5C.3.6 Security gates. The installation of security gates across a fire apparatus access road shall be approved by the fire chief. Where security gates are installed, they shall have an approved means of emergency operation. The security gates and the emergency operation shall be maintained operational at all times. SECTION 5C.4 ACCESS TO BUILDING OPENINGS AND ROOFS 5C.4.1 Required access. Exterior doors and openings required by these code requirements or the SBC 201 shall be maintained readily accessible for emergency access by the Civil Defence. An approved access walkway leading from fire apparatus access roads to exterior openings shall be provided when required by the building official. 5C.4.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 19.1 mm wide and at least 150 mm high on a contrasting background. Required Civil Defence access doors shall not be obstructed or eliminated. Exit and exit access doors shall comply with Chapter 8. Access doors for high-piled combustible storage shall comply with Section 21.6.6.1. 5C.4.3 Stairway access to roof. New buildings four or more stories in height, except those with a roof slope greater than four units vertical in 12 units horizontal (33.3 percent slope), shall be provided with a stairway to the roof. Stairway access to the roof shall be in accordance with Section 8.9.12. Such stairway shall be marked at street and floor levels with a sign indicating that the stairway continues to the roof. 2007 5/23 SBC 801 GENERAL PRECAUTIONS AGAINST FIRE Where roofs are used for roof gardens or for other purposes, stairways shall be provided as required for such occupancy classification. SECTION 5C.5 PREMISES IDENTIFICATION 5C.5.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 100 mm high with a minimum stroke width of 12.7 mm. 5C.5.2 Street or road signs. Streets and roads shall be identified with approved signs. Temporary signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles. Signs shall be of an approved size, weather resistant and be maintained until replaced by permanent signs. SECTION 5C.6 KEY BOXES 5C.6.1 5C.6.1.1 5C.6.2 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for lifesaving or fire-fighting purposes, the building official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the building official. Locks. An approved lock shall be installed on gates or similar barriers when required by the building official. Key box maintenance. The operator of the building shall immediately notify the building official and provide the new key when a lock is changed or rekeyed. The key to such lock shall be secured in the key box. SECTION 5C.7 HAZARDS TO FIRE FIGHTERS 5C.7.1 Trapdoors to be closed. Trapdoors and scuttle covers, other than those that are within a dwelling unit or automatically operated, shall be kept closed at all times except when in use. 5C.7.2 5C.7.2.1 Shaftway markings. Vertical shafts shall be identified as required by this section. Exterior access to shaftways. Outside openings accessible to the Civil Defence and which open directly on a hoistway or shaftway communicating between two or more floors in a building shall be plainly marked with the word SHAFTWAY in red letters at least 150 mm high on a white background. Such warning signs shall be placed so as to be readily discernible from the outside of the building. Interior access to shaftways. Door or window openings to a hoistway or shaftway from the interior of the building shall be plainly marked with the word SHAFTWAY in red letters at least 150 mm high on a white background. Such warning signs shall be placed so as to be readily discernible. Exception: Marking shall not be required on shaftway openings which are readily 2007 5/24 5C.7.2.2 SBC 801 GENERAL PRECAUTIONS AGAINST FIRE discernible as openings onto a shaftway by the construction or arrangement. 5C.7.3 Pitfalls. The intentional design or alteration of buildings to disable, injure, maim or kill intruders is prohibited. No person shall install and use firearms, sharp or pointed objects, razor wire, explosives, flammable or combustible liquid containers, or dispensers containing highly toxic, toxic, irritant or other hazardous materials in a manner which may passively or actively disable, injure, maim or kill a fire fighter who forcibly enters a building for the purpose of controlling or extinguishing a fire, rescuing trapped occupants or rendering other emergency assistance. SECTION 5C.8 FIRE PROTECTION WATER SUPPLIES 5C.8.1 Required water supply. An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction. 5C.8.2 Type of water supply. A water supply shall consist of reservoirs, pressure tanks, elevated tanks, water mains or other fixed systems capable of providing the required fire flow. Private fire service mains. Private fire service mains and appurtenances shall be installed in accordance with NFPA 24. Water tanks. Water tanks for private fire protection shall be installed in accordance with NFPA 22. 5C.8.2.1 5C.8.2.2 5C.8.3 Fire flow. Fire flow requirements for buildings or portions of buildings and facilities shall be determined by an approved method. 5C.8.4 Water supply test. The building official shall be notified prior to the water supply test. Water supply tests shall be witnessed by the building official or approved documentation of the test shall be provided to the building official prior to final approval of the water supply system. 5C.8.5 Fire hydrant systems. Fire hydrant systems shall comply with Sections 5C.8.5.1 through 5C.8.5.6. Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 122 m from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the building official. Exceptions: 1. For Group R-3 and Group U occupancies, the distance requirement shall be 183 m. 2. For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2, the distance requirement shall be 183 m. Inspection, testing and maintenance. Fire hydrant systems shall be subject to periodic tests as required by the building official. Fire hydrant systems shall be maintained in an operative condition at all times and shall be repaired where defective. Additions, repairs, alterations and servicing shall comply with approved 2007 5/25 5C.8.5.1 5C.8.5.2 SBC 801 GENERAL PRECAUTIONS AGAINST FIRE 5C.8.5.3 5C.8.5.4 5C.8.5.5 5C.8.5.6 standards. Private fire service mains and water tanks. Private fire service mains and water tanks shall be periodically inspected, tested and maintained in accordance with NFPA 25 at the following intervals: 1. Private fire hydrants (all types): Inspection annually and after each operation; flow test and maintenance annually. 2. Fire service main piping: Inspection of exposed, annually; flow test every 5 years. 3. Fire service main piping strainers: Inspection and maintenance after each use. Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, Civil Defence inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The Civil Defence shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. Clear space around hydrants. A 900 mm clear space shall be maintained around the circumference of fire hydrants except as otherwise required or approved. Physical protection. Where fire hydrants are subject to impact by a motor vehicle, guard posts or other approved means shall comply with Section 5A.12. SECTION 5C.9 FIRE COMMAND CENTER 5C.9.1 SBC 801 Features. Where required by other sections of these code requirements and in all buildings classified as high-rise buildings by the SBC, a fire command center for Civil Defence operations shall be provided. The location and accessibility of the fire command center shall be approved by the Civil Defence. The fire command center shall be separated from the remainder of the building by not less than a 12 hour fire-resistance-rated fire barrier. The room shall be a minimum of 9 m with a minimum dimension of 2.4 m. A layout of the fire command center and all features required by this section to be contained therein shall be submitted for approval prior to installation. The fire command center shall comply with NFPA 72 and shall contain the following features: 1. The emergency voice/alarm communication system unit. 2. The Civil Defence communications system. 3. Fire-detection and alarm system annunciator system. 4. Annunciator visually indicating the location of the elevators and whether they are operational. 5. Status indicators and controls for air-handling systems. 6. The fire-fighter’s control panel required by Section 7.9.16 for smoke control systems installed in the building. 7. Controls for unlocking stairway doors simultaneously. 8. Sprinkler valve and water-flow detector display panels. 9. Emergency and standby power status indicators. 10. A telephone for Civil Defence use with controlled access to the public telephone system. 11. Fire pump status indicators. 12. Schematic building plans indicating the typical floor plan and detailing the building core, means of egress, fire protection systems, fire-fighting equipment and Civil Defence access. 13. Work table. 2007 5/26 GENERAL PRECAUTIONS AGAINST FIRE 14. 15. Generator supervision devices, manual start and transfer features. Public address system, where specifically required by other sections of these code requirements. SECTION 5C.10 CIVIL DEFENCE ACCESS TO EQUIPMENT 5C.10.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the Civil Defence. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. SECTION 5D BUILDING SERVICES AND SYSTEMS SECTION 5D.1 GENERAL 5D.1.1 Scope. The provisions of this section shall apply to the installation, operation and maintenance of fuel-fired appliances and heating systems, emergency and standby power systems, electrical systems and equipment, mechanical refrigeration systems, elevator recall, stationary lead-acid battery systems and commercial kitchen hoods. 5D.1.2 Permits. Permits shall be obtained for refrigeration systems and battery systems as set forth in SBC 100. SECTION 5D.2 DEFINITIONS 5D.2.1 Definitions. The following words and terms shall, for the purposes of this section and as used elsewhere in these code requirements, have the meanings shown herein. BATTERY, LEAD ACID. A group of electrochemical cells interconnected to supply a nominal voltage of DC power to a suitably connected electrical load. The number of cells connected in series determines the nominal voltage rating of the battery. The size of the cells determines the discharge capacity of the entire battery. BATTERY SYSTEM, STATIONARY LEAD ACID. A system which consists of three interconnected subsystems: 1. A lead-acid battery. 2. A battery charger. 3. A collection of rectifiers, inverters, converters, and associated electrical equipment as required for a particular application. SBC 801 COMMERCIAL COOKING APPLIANCES. Appliances used in a commercial food service establishment for heating or cooking food and which produce grease vapors, steam, fumes, smoke or odors that are required to be removed through a 2007 5/27 GENERAL PRECAUTIONS AGAINST FIRE local exhaust ventilation system. Such appliances include deep fat fryers; upright broilers; griddles; broilers; steam-jacketed kettles; hot-top ranges; under-fired broilers (charbroilers); ovens; barbecues; rotisseries; and similar appliances. For the purpose of this definition, a food service establishment shall include any building or a portion thereof used for the preparation and serving of food. HOOD. An air-intake device used to capture by entrapment, impingement, adhesion or similar means, grease and similar contaminants before they enter a duct system. Type I. A kitchen hood for collecting and removing grease vapors and smoke. REFRIGERANT. The fluid used for heat transfer in a refrigerating system; the refrigerant absorbs heat and transfers it at a higher temperature and a higher pressure, usually with a change of state. REFRIGERATION SYSTEM. A combination of interconnected refrigerantcontaining parts constituting one closed refrigerant circuit in which a refrigerant is circulated for the purpose of extracting heat. VALVE-REGULATED LEAD-ACID (VRLA) BATTERY. A lead-acid battery consisting of sealed cells furnished with a valve that opens to vent the battery whenever the internal pressure of the battery exceeds the ambient pressure by a set amount. In VRLA batteries, the liquid electrolyte in the cells is immobilized in an absorptive glass mat (AGM cells or batteries) or by the addition of a gelling agent (gel cells or gelled batteries). VENTED (FLOODED) LEAD-ACID BATTERY. A lead-acid battery consisting of cells that have electrodes immersed in liquid electrolyte. Flooded lead-acid batteries have a provision for the user to add water to the cell and are equipped with a flame-arresting vent which permits the escape of hydrogen and oxygen gas from the cell in a diffused manner such that a spark, or other ignition source, outside the cell will not ignite the gases inside the cell. SECTION 5D.3 FUEL-FIRED APPLIANCES 5D.3.1 5D.3.1.1 5D.3.1.2 5D.3.1.3 5D.3.1.4 SBC 801 Installation. The installation of nonportable fuel gas appliances and systems shall be carried out by an approved method. The installation of all other fuel-fired appliances, other than internal combustion engines, oil lamps and portable devices such as blow torches, melting pots and weed burners, shall comply with this section and the SBC 501. Manufacturer’s instructions. The installation shall be made in accordance with the manufacturer’s instructions and applicable local rules and regulations. Where it becomes necessary to change, modify, or alter a manufacturer’s instructions in any way, written approval shall first be obtained from the manufacturer. Approval. The design, construction and installation of fuel-fired appliances shall be in accordance with the SBC 100 and the SBC 501. Electrical wiring and equipment. Electrical wiring and equipment used in connection with oil-burning equipment shall be installed and maintained in accordance with Section 5D.5 and the SBC 401. Fuel oil. The grade of fuel oil used in a burner shall be that for which the burner is approved and as stipulated by the burner manufacturer. Oil containing gasoline 2007 5/28 GENERAL PRECAUTIONS AGAINST FIRE shall not be used. Waste crankcase oil shall be an acceptable fuel in Group F, M and S occupancies, when utilized in equipment listed for use with waste oil and when such equipment is installed in accordance with the manufacturer’s instructions and the terms of its listing. 5D.3.1.5 Access. The installation shall be readily accessible for cleaning hot surfaces; removing burners; replacing motors, controls, air filters, chimney connectors, draft regulators, and other working parts; and for adjusting, cleaning and lubricating parts. 5D.3.1.6 Testing, diagrams and instructions. After installation of the oil-burning equipment, operation and combustion performance tests shall be conducted to determine that the burner is in proper operating condition and that all accessory equipment, controls, and safety devices function properly. 5D.3.1.6.1 Diagrams. Contractors installing industrial oil-burning systems shall furnish not less than two copies of diagrams showing the main oil lines and controlling valves, one copy of which shall be posted at the oil-burning equipment and another at an approved location that will be accessible in case of emergency. 5D.3.1.6.2 Instructions. After completing the installation, the installer shall instruct the owner or operator in the proper operation of the equipment. The installer shall also furnish the owner or operator with the name and telephone number of persons to contact for technical information or assistance and routine or emergency services. 5D.3.1.7 Clearances. Working clearances between oil-fired appliances and electrical panelboards and equipment shall be in accordance with the SBC 401. Clearances between oil-fired equipment and oil supply tanks shall be in accordance with NFPA 31. 5D.3.2 Chimneys. Masonry chimneys shall be constructed in accordance with the SBC 305. Factory-built chimneys shall be installed in accordance with the SBC 501. Metal chimneys shall be constructed and installed in accordance with NFPA 211. 5D.3.3 Fuel oil storage systems. Fuel oil storage systems shall be installed in accordance with these code requirements. Fuel oil piping systems shall be installed in accordance with the SBC 501. Maximum outside fuel oil storage above ground. Where connected to a fuel-oil piping system, the maximum amount of fuel oil storage allowed outside above ground without additional protection shall be 2,500 L. The storage of fuel oil above ground in quantities exceeding 2,500 L shall comply with NFPA 31. Maximum inside fuel oil storage. Where connected to a fuel-oil piping system, the maximum amount of fuel oil storage allowed inside any building shall be 2,500 L. Where the amount of fuel oil stored inside a building exceeds 2,500 L, the storage area shall be in compliance with the SBC 201. Underground storage of fuel oil. The storage of fuel oil in underground storage tanks shall comply with NFPA 31. 5D.3.3.1 5D.3.3.2 5D.3.3.3 5D.3.4 5D.3.4.1 5D.3.5 SBC 801 Portable unvented heaters. Portable unvented fuel-fired heating equipment shall be prohibited in occupancies in Groups A, E, I, R-1, R-2, R-3 and R-4. Exception: Listed and approved unvented fuel-fired heaters in one- and twofamily dwellings. Prohibited locations. Unvented fuel-fired heating equipment shall not be located in, or obtain combustion air from, any of the following rooms or spaces: sleeping rooms, bathrooms, toilet rooms or storage closets. Heating appliances. Heating appliances shall be listed and shall comply with this 2007 5/29 GENERAL PRECAUTIONS AGAINST FIRE 5D.3.5.1 5D.3.5.2 5D.3.6 5D.3.6.1 5D.3.6.2 5D.3.6.3 5D.3.6.4 5D.3.6.5 5D.3.7 5D.3.7.1 5D.3.8 5D.3.8.1 5D.3.8.2 5D.3.8.3 SBC 801 section. Guard against contact. The heating element or combustion chamber shall be permanently guarded so as to prevent accidental contact by persons or material. Heating appliance installation. Heating appliances shall be installed in accordance with the manufacturer’s instructions, the SBC 401, and the SBC 501. Chimneys and appliances. Chimneys, incinerators, smokestacks or similar devices for conveying smoke or hot gases to the outer air and the stoves, furnaces, fireboxes or boilers to which such devices are connected, shall be maintained so as not to create a fire hazard. Masonry chimneys. Masonry chimneys that, upon inspection, are found to be without a flue liner and that have open mortar joints which will permit smoke or gases to be discharged into the building, or which are cracked as to be dangerous, shall be repaired or relined with a listed chimney liner system installed in accordance with the manufacturer’s installation instructions or a flue lining system installed in accordance with the SBC requirements and appropriate for the intended class of chimney service. Metal chimneys. Metal chimneys which are corroded or improperly supported shall be repaired or replaced. Decorative shrouds. Decorative shrouds installed at the termination of factorybuilt chimneys shall be removed except where such shrouds are listed and labeled for use with the specific factory-built chimney system and are installed in accordance with the chimney manufacturer’s installation instructions. Factory-built chimneys. Existing factory-built chimneys that are damaged, corroded or improperly supported shall be repaired or replaced. Connectors. Existing chimney and vent connectors that are damaged, corroded or improperly supported shall be repaired or replaced. Discontinuing operation of unsafe heating appliances. The building official is authorized to order that measures be taken to prevent the operation of any existing stove, oven, furnace, incinerator, boiler or any other heat-producing device or appliance found to be defective or in violation of code requirements for existing appliances after giving notice to this effect to any person, owner, firm or agent or operator in charge of the same. The building official is authorized to take measures to prevent the operation of any device or appliance without notice when inspection shows the existence of an immediate fire hazard or when imperiling human life. The defective device shall remain withdrawn from service until all necessary repairs or alterations have been made. Unauthorized operation. It shall be a violation of these code requirements for any person, user, firm or agent to continue the utilization of any device or appliance (the operation of which has been discontinued or ordered discontinued in accordance with Section 5D.3.7), unless written authority to resume operation is given by the building official. Removing or breaking the means by which operation of the device is prevented shall be a violation of these code requirements. Incinerators. Commercial, industrial and residential-type incinerators and chimneys shall be constructed in accordance with the SBC 501. Residential incinerators. Residential incinerators shall be of an approved type. Spark arrestor. Incinerators shall be equipped with an effective means for arresting sparks. Restrictions. Where the building official determines that burning in incinerators 2007 5/30 GENERAL PRECAUTIONS AGAINST FIRE 5D.3.8.4 5D.3.8.5 5D.3.9 located within 152 m of mountainous, brush or grass-covered areas will create an undue fire hazard because of atmospheric conditions, such burning shall be prohibited. Time of burning. Burning shall take place only during approved hours. Discontinuance. The building official is authorized to require incinerator use to be discontinued immediately if the building official determines that smoke emissions are offensive to occupants of surrounding property or if the use of incinerators is determined by the building official to constitute a hazardous condition. Gas meters. Above-ground gas meters, regulators and piping subject to damage shall be protected by a barrier complying with Section 5A.12 or otherwise protected in an approved manner. SECTION 5D.4 EMERGENCY AND STANDBY POWER SYSTEMS 5D.4.1 5D.4.1.1 5D.4.2 5D.4.2.1 5D.4.2.2 5D.4.2.3 5D.4.2.4 5D.4.2.5 5D.4.2.6 5D.4.2.7 5D.4.2.8 5D.4.2.9 5D.4.2.10 5D.4.2.11 SBC 801 Installation. Emergency and standby power systems shall be installed in accordance with the SBC 401, NFPA 110 and NFPA 111. Existing installations shall be maintained in accordance with the original approval. Stationary generators. Stationary emergency and standby power generators required by these code requirements shall be listed in accordance with UL 2200. Where required. Emergency and standby power systems shall be provided where required by Sections 5D.4.2.1 through 5D.4.2.18. Group A occupancies. Emergency power shall be provided for emergency voice/alarm communication systems in Group A occupancies in accordance with Section 7.7.2.1.2. Smoke control systems. Standby power shall be provided for smoke control systems in accordance with Section 7.9.11. Exit signs. Emergency power shall be provided for exit signs in accordance with Section 8.11.5.3. Means of egress illumination. Emergency power shall be provided for means of egress illumination in accordance with Section 8.6.3. Accessible means of egress elevators or platform lifts. Standby power shall be provided for elevators or platform lifts that are part of an accessible means of egress in accordance with Section 8.7.4 or 8.7.5, respectively. Horizontal sliding doors. Standby power shall be provided for horizontal sliding doors in accordance with Section 8.8.1.3.3. Semiconductor fabrication facilities. Emergency power shall be provided for semiconductor fabrication facilities in accordance with Section 16.3.15. Membrane structures. Emergency power shall be provided for exit signs in temporary tents and membrane structures in accordance with Section 22.3.12.6.1. Standby power shall be provided for auxiliary inflation systems in permanent membrane structures in accordance with the SBC requirements. Hazardous materials. Emergency or standby power shall be provided in occupancies with hazardous materials in accordance with Sections 25.4.7 and 25.5.1.5. Highly toxic and toxic materials. Emergency power shall be provided for occupancies with highly toxic or toxic materials in accordance with Sections 35.4.2.2.8 and 35.4.3.2.6. Organic peroxides. Standby power shall be provided for occupancies with organic peroxides in accordance with Section 37.4.1.11. 2007 5/31 GENERAL PRECAUTIONS AGAINST FIRE 5D.4.2.12 5D.4.2.13 5D.4.2.14 5D.4.2.14.1 5D.4.2.14.1.1 5D.4.2.14.1.2 5D.4.2.14.1.3 5D.4.2.14.2 5D.4.2.14.2.1 5D.4.2.14.3 5D.4.2.15 5D.4.2.15.1 5D.4.2.15.1.1 5D.4.2.15.1.2 SBC 801 Pyrophoric materials. Emergency power shall be provided for occupancies with silane gas in accordance with Sections 39.6.2.3 and 39.6.4.3. Covered mall buildings. Covered mall buildings exceeding 4,645 m2 shall be provided with standby power systems which are capable of operating the emergency voice/alarm communication. High-rise buildings. Standby power, light and emergency systems in high-rise buildings shall comply with the requirements of Sections 5D.4.2.14.1 through 5D.4.2.14.3. Standby power. A standby power system shall be provided. Where the standby system is a generator set inside a building, the system shall be located in a separate room enclosed with 2-hour fire-resistance-rated fire barrier assemblies. System supervision with manual start and transfer features shall be provided at the fire command center. Fuel supply. An on-premises fuel supply, sufficient for not less than 2-hour fulldemand operation of the system, shall be provided. Exception: Where the system is supplied with pipeline natural gas and is approved. Capacity. The standby system shall have a capacity and rating that supplies all equipment required to be operational at the same time. The generating capacity is not required to be sized to operate all of the connected electrical equipment simultaneously. Connected facilities. Power and lighting facilities for the fire command center and elevators specified in Sections 5B.3.8 and 5B.3.9, as applicable, and electrically powered fire pumps required to maintain pressure, shall be transferable to the standby source. Standby power shall be provided for at least one elevator to serve all floors and be transferable to any elevator. Separate circuits and fixtures. Separate lighting circuits and fixtures shall be required to provide sufficient light with an intensity of not less than 11 lux measured at floor level in all means of egress corridors, stairways, smoke proof enclosures, elevator cars and lobbies, and other areas which are clearly a part of the escape route. Other circuits. Circuits supplying lighting for the fire command center and mechanical equipment rooms shall be transferable to the standby source. Emergency systems. Exit signs, exit illumination as required by Chapter 8, and elevator car lighting are classified as emergency systems and shall operate within 10 seconds of failure of the normal power supply and shall be capable of being transferred to the standby source. Exception: Exit sign, exit and means of egress illumination are permitted to be powered by a standby source in buildings of Group F and S occupancies. Underground buildings. Emergency and standby power systems in underground buildings covered in Chapter 2 of SBC 201 shall comply with Sections 5D.4.2.15.1 and 5D.4.2.15.2. Standby power. A standby power system complying with the SBC 401 shall be provided for standby power loads as specified in Section 5D.4.2.15.1.1. Standby power loads. The following loads are classified as standby power loads: 1. Smoke control system. 2. Ventilation and automatic fire detection equipment for smokeproof enclosures. 3. Fire pumps. 4. Standby power shall be provided for elevators in accordance with the SBC 401 and 501. Pickup time. The standby power system shall pick up its connected loads within 60 seconds of failure of the normal power supply. 2007 5/32 GENERAL PRECAUTIONS AGAINST FIRE 5D.4.2.15.2 Emergency power. An emergency power system complying with the SBC 401 5D.4.2.15.2.1 5D.4.2.16 5D.4.2.17 5D.4.2.18 5D.4.2.18.1 5D.4.2.18.2 5D.4.2.18.3 5D.4.2.18.4 5D.4.3 5D.4.3.1 5D.4.3.2 SBC 801 shall be provided for emergency power loads as specified in Section 5D.4.2.15.2.1. Emergency power loads. The following loads are classified as emergency power loads: 1. Emergency voice/alarm communication systems. 2. Fire alarm systems. 3. Automatic fire detection systems. 4. Elevator car lighting. 5. Means of egress lighting and exit sign illumination as required by Chapter 8. Group I-3 occupancies. Power-operated sliding doors or power-operated locks for swinging doors in Group I-3 occupancies shall be operable by a manual release mechanism at the door, and either emergency power or a remote mechanical operating release shall be provided. Exception: Emergency power is not required in facilities where provisions for remote locking and unlocking of occupied rooms in Occupancy Condition 4 are not required as set forth in the SBC. Airport traffic control towers. A standby power system shall be provided in airport traffic control towers more than 19.8 m in height. Power shall be provided to the following equipment: 1. Pressurization equipment, mechanical equipment and lighting. 2. Elevator operating equipment. 3. Fire alarm and smoke detection systems. Elevators. In buildings and structures where standby power is required or furnished to operate an elevator, the operation shall be in accordance with Sections 5D.4.2.18.1 through 5D.4.2.18.4. Manual transfer. Standby power shall be manually transferable to all elevators in each bank. One elevator. Where only one elevator is installed, the elevator shall automatically transfer to standby power within 60 seconds after failure of normal power. Two or more elevators. Where two or more elevators are controlled by a common operating system, all elevators shall automatically transfer to standby power within 60 seconds after failure of normal power where the standby power source is of sufficient capacity to operate all elevators at the same time. Where the standby power source is not of sufficient capacity to operate all elevators at the same time, all elevators shall transfer to standby power in sequence, return to the designated landing and disconnect from the standby power source. After all elevators have been returned to the designated level, at least one elevator shall remain operable from the standby power source. Venting. Where standby power is connected to elevators, the machine room ventilation or air conditioning shall be connected to the standby power source. Maintenance. Emergency and standby power systems shall be maintained such that the system is capable of supplying service within the time specified for the type and duration required. Schedule. Inspection, testing and maintenance of emergency and standby power systems shall be in accordance with an approved schedule established upon completion and approval of the system installation. Written record. Written records of the inspection, testing and maintenance of emergency and standby power systems shall include the date of service, name of the servicing technician, a summary of conditions noted and a detailed description of any conditions requiring correction and what corrective action was taken. Such 2007 5/33 GENERAL PRECAUTIONS AGAINST FIRE 5D.4.3.3 5D.4.4 5D.4.4.1 5D.4.5 records shall be kept on the premises served by the emergency or standby power system and be available for inspection by the building official. Switch maintenance. Emergency and standby power system transfer switches shall be included in the inspection, testing and maintenance schedule required by Section 5D.4.3.1. Transfer switches shall be maintained free from accumulated dust and dirt. Inspection shall include examination of the transfer switch contacts for evidence of deterioration. When evidence of contact deterioration is detected, the contacts shall be replaced in accordance with the transfer switch manufacturer’s instructions. Operational inspection and testing. Emergency power systems, including all appurtenant components shall be inspected and tested under load in accordance with NFPA 110 and NFPA 111. Exception: Where the emergency power system is used for standby power or peak load shaving, such use shall be recorded and shall be allowed to be substituted for scheduled testing of the generator set, provided that appropriate records are maintained. Transfer switch test. The test of the transfer switch shall consist of electrically operating the transfer switch from the normal position to the alternate position and then return to the normal position. Supervision of maintenance and testing. Routine maintenance, inspection and operational testing shall be overseen by a properly instructed individual. SECTION 5D.5 ELECTRICAL EQUIPMENT, WIRING AND HAZARDS 5D.5.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the SBC 401. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. 5D.5.2 Illumination. Illumination shall be provided for service equipment areas, motor control centers and electrical panelboards. 5D.5.3 Working space and clearance. A working space of not less than 760 mm in width, 900 mm in depth and 2 m in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 760 mm, the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. Exceptions: 1. Where other dimensions are required or allowed by the SBC 401. 2. Access openings into attics or under-floor areas which provide a minimum clear opening of 560 mm by 760 mm. Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. 5D.5.3.1 5D.5.4 SBC 801 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug 2007 5/34 GENERAL PRECAUTIONS AGAINST FIRE 5D.5.4.1 5D.5.4.2 5D.5.4.3 5D.5.5 5D.5.5.1 5D.5.5.2 5D.5.5.3 5D.5.5.4 strips or any other device not complying with the SBC 401 shall be prohibited. Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage. Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Power supply. Extension cords shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance. Ampacity. The ampacity of the extension cords shall not be less than the rated capacity of the portable appliance supplied by the cord. Maintenance. Extension cords shall be maintained in good condition without splices, deterioration or damage. Grounding. Extension cords shall be grounded when serving grounded portable appliances. 5D.5.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 5D.5.7 Appliances. Electrical appliances and fixtures shall be tested and listed in published reports of inspected electrical equipment by an approved agency and installed in accordance with all instructions included as part of such listing. 5D.5.8 Electrical motors. Electrical motors shall be maintained free from excessive accumulations of oil, dirt, waste and debris. 5D.5.9 Temporary wiring. Temporary wiring for electrical power and lighting installations is allowed for a period not to exceed 90 days. Temporary wiring methods shall meet the applicable provisions of the SBC 401. Exception: Temporary wiring for electrical power and lighting installations is allowed during periods of construction, remodeling, repair or demolition of buildings, structures, equipment or similar activities. Attachment to structures. Temporary wiring attached to a structure shall be attached in an approved manner. 5D.5.9.1 SECTION 5D.6 MECHANICAL REFRIGERATION 5D.6.1 Scope. Refrigeration systems shall be installed in accordance with the SBC 501. 5D.6.2 Refrigerants. The use and purity of new, recovered, and reclaimed refrigerants shall be in accordance with the SBC 501. SBC 801 2007 5/35 GENERAL PRECAUTIONS AGAINST FIRE 5D.6.3 Refrigerant classification. Refrigerants shall be classified in accordance with the SBC 501. 5D.6.4 Change in refrigerant type. A change in the type of refrigerant in a refrigeration system shall be in accordance with the SBC 501. 5D.6.5 Access. Refrigeration systems having a refrigerant circuit containing more than 100 kg of Group A1 or 14 kg of any other group refrigerant shall be accessible to the Civil Defence at all times as required by the building official. 5D.6.6 Testing of equipment. Refrigeration equipment and systems having a refrigerant circuit containing more than 100 kg of Group A1 or 14 kg of any other group refrigerant shall be subject to periodic testing in accordance with Section 5D.6.6.1. A written record of required testing shall be maintained on the premises. Tests of emergency devices or systems required by this section shall be conducted by persons trained and qualified in refrigeration systems. Periodic testing. The following emergency devices or systems shall be periodically tested in accordance with the manufacturer’s instructions and as required by the building official. 1. Treatment and flaring systems. 2. Valves and appurtenances necessary to the operation of emergency refrigeration control boxes. 3. Fans and associated equipment intended to operate emergency ventilation systems. 4. Detection and alarm systems. 5D.6.6.1 5D.6.7 Emergency signs. Refrigeration units or systems having a refrigerant circuit containing more than 100 kg of Group A1 or 14 kg of any other group refrigerant shall be provided with approved emergency signs, charts, and labels in accordance with NFPA 704. Hazard signs shall be in accordance with the SBC 501 for the classification of refrigerants listed therein. 5D.6.8 Refrigerant detector. Machinery rooms shall contain a refrigerant detector with an audible and visual alarm. The detector, or a sampling tube that draws air to the detector, shall be located in an area where refrigerant from a leak will concentrate. The alarm shall be actuated at a value not greater than the corresponding TLVTWA values shown in the SBC 501 for the refrigerant classification. Detectors and alarms shall be placed in approved locations. Exception: Detectors are not required for ammonia systems where the machinery room complies with the SBC 501. 5D.6.9 Remote controls. Remote control of the mechanical equipment and appliances located in the machinery room shall be provided at an approved location immediately outside the machinery room and adjacent to its principal entrance. Refrigeration system. A clearly identified switch of the break-glass type shall provide off-only control of electrically energized equipment and appliances in the machinery room, other than refrigerant leak detectors and machinery room ventilation. Ventilation system. A clearly identified switch of the break-glass type shall provide on-only control of the machinery room ventilation fans. Emergency control box. Emergency control boxes shall be provided for refrigeration systems required to be equipped with a treatment system, flaring 2007 5/36 5D.6.9.1 5D.6.9.2 5D.6.9.3 SBC 801 GENERAL PRECAUTIONS AGAINST FIRE 5D.6.9.3.1 5D.6.9.3.2 5D.6.9.3.3 5D.6.9.3.4 5D.6.9.3.5 system or ammonia diffusion system. Location. Emergency control boxes shall be located outside of the building at an approved accessible location. All portions of the emergency control box shall be 1.8 m or less above the adjoining grade. Construction. Emergency control boxes shall be of iron or steel not less than 1.4 mm in thickness and provided with a hinged cover and lock. Operational procedure. Valves and switches shall be identified in an approved manner as to the sequential procedure to be followed in the event of an emergency. Identification. Emergency control boxes shall be provided with a permanent label on the outside cover reading: CIVIL DEFENCE USE ONLY – REFRIGERANT CONTROL BOX, and including the name of the refrigerant in the system. Hazard identification in accordance with NFPA 704 shall be posted inside and outside of the control box. Instructions. Written instructions and information shall be provided and located in the emergency control box designating the following information: 1. Instructions for suspending operation of the system in the event of an emergency. 2. The name, address and emergency telephone numbers to obtain emergency service. 3. The location and operation of emergency discharge systems. 5D.6.10 Storage, use and handling. Flammable and combustible materials shall not be stored in machinery rooms for refrigeration systems having a refrigerant circuit containing more than 100 kg of Group A1 or 14 kg of any other group refrigerant. Storage, use or handling of extra refrigerant or refrigerant oils shall be as required by Chapters 25, 28, 30 and 32. Exception: This provision shall not apply to spare parts, tools, and incidental materials necessary for the safe and proper operation and maintenance of the system. 5D.6.11 Termination of relief devices. Pressure relief devices, fusible plugs and purge systems for refrigeration systems containing more than 3 kg of flammable, toxic or highly toxic refrigerants shall be provided with an approved discharge system as required by Sections 5D.6.11.1, 5D.6.11.2 and 5D.6.11.3. Discharge piping and devices connected to the discharge side of a fusible plug or rupture member shall have provisions to prevent plugging the pipe in the event of the fusible plug or rupture member functions. Flammable refrigerants. Systems containing flammable refrigerants having a density equal to or greater than the density of air shall discharge vapor to the atmosphere only through an approved treatment system in accordance with Section 5D.6.11.4 or a flaring system in accordance with Section 5D.6.11.5. Systems containing flammable refrigerants having a density less than the density of air shall be permitted to discharge vapor to the atmosphere provided that the point of discharge is located outside of the structure at not less than 4.6 m above the adjoining grade level and not less than 6.1 m from any window, ventilation opening or exit. Toxic and highly toxic refrigerants. Systems containing toxic or highly toxic refrigerants shall discharge vapor to the atmosphere only through an approved treatment system in accordance with Section 5D.6.11.4 or a flaring system in accordance with Section 5D.6.11.5. Ammonia refrigerant. Systems containing ammonia refrigerant shall discharge vapor to the atmosphere through an approved treatment system in accordance with 2007 5/37 5D.6.11.1 5D.6.11.2 5D.6.11.3 SBC 801 GENERAL PRECAUTIONS AGAINST FIRE 5D.6.11.4 5D.6.11.5 5D.6.11.6 Section 5D.6.11.4, a flaring system in accordance with Section 5D.6.11.5, or through an approved ammonia diffusion system in accordance with Section 5D.6.11.6, or by other approved means. Exceptions: 1. Ammonia/water absorption systems containing less than 10 kg of ammonia and for which the ammonia circuit is located entirely outdoors. 2. When the building official determines, on review of an engineering analysis prepared in accordance with SBC 100, that a fire, health or environmental hazard would not result from discharging ammonia directly to the atmosphere. Treatment systems. Treatment systems shall be designed to reduce the allowable discharge concentration of the refrigerant gas to not more than 50 percent of the IDLH at the point of exhaust. Treatment systems shall be in accordance with Chapter 35. Flaring systems. Flaring systems for incineration of flammable refrigerants shall be designed to incinerate the entire discharge. The products of refrigerant incineration shall not pose health or environmental hazards. Incineration shall be automatic upon initiation of discharge, shall be designed to prevent blowback, and shall not expose structures or materials to threat of fire. Standby fuel, such as LP gas, and standby power shall have the capacity to operate for one and one-half the required time for complete incineration of refrigerant in the system. Ammonia diffusion systems. Ammonia diffusion systems shall include a tank containing 4 L of water for each 1 kg of ammonia that will be released in 1 hour from the largest relief device connected to the discharge pipe. The water shall be prevented from freezing. The discharge pipe from the pressure relief device shall distribute ammonia in the bottom of the tank, but no lower than 10.1 m below the maximum liquid level. The tank shall contain the volume of water and ammonia without overflowing. 5D.6.12 Discharge location for refrigeration machinery room ventilation. Exhaust from mechanical ventilation systems serving refrigeration machinery rooms capable of exceeding 25 percent of the LFL or 50 percent of the IDLH shall be equipped with approved treatment systems to reduce the discharge concentrations of flammable, toxic or highly toxic refrigerants to those values or lower. 5D.6.13 Notification of refrigerant discharges. The building official shall be notified immediately when a discharge becomes reportable under local regulations in accordance with Section 25.3.3.1. 5D.6.14 Records. A written record shall be kept of refrigerant quantities brought into and removed from the premises. Such records shall be available to the building official. 5D.6.15 Electrical equipment. Where refrigerants of Groups A2, A3, B2 and B3, as defined in the SBC 501, are used, refrigeration machinery rooms shall conform to the Class I, Division 2 hazardous location classification requirements of the SBC 401. Exception: Ammonia machinery rooms that are provided with ventilation in accordance with SBC 501. SBC 801 2007 5/38 GENERAL PRECAUTIONS AGAINST FIRE SECTION 5D.7 ELEVATOR RECALL AND MAINTENANCE 5D.7.1 Required. Existing elevators with a travel distance of 25 level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3. New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1. 5D.7.2 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS. The emergency sign shall not be required for elevators that are part of an accessible means of egress complying with Section 8.7.4. 5D.7.3 Elevator keys. Keys for the elevator car doors and fire-fighter service keys shall be kept in an approved location for immediate use by the Civil Defence. SECTION 5D.8 STATIONARY LEAD-ACID BATTERY SYSTEMS 5D.8.1 Scope. Stationary lead-acid battery systems using vented (flooded) lead-acid batteries having an electrolyte capacity of more than 189 L used for facility standby power, emergency power, or uninterrupted power supplies shall comply with this section. Valve-regulated lead-acid batteries are not subject to the requirements of this section, but shall comply with Section 7.9. 5D.8.2 Safety venting. Batteries shall be provided with safety venting caps. 5D.8.3 Room design and construction. Enclosure of stationary lead-acid system rooms shall comply with the SBC 201. The battery systems are permitted to be in the same room with the equipment they support. 5D.8.4 Spill control and neutralization. An approved method and materials for the control and neutralization of a spill of electrolyte shall be provided. The method and materials shall be capable of controlling and neutralizing a spill from the largest lead-acid battery to a pH between 7.0 and 9.0. Ventilation. Ventilation shall be provided in accordance with the SBC 501 and the following: 1. The ventilation system shall be designed to limit the maximum concentration of hydrogen to 1.0 percent of the total volume of the room; or 2. Continuous ventilation shall be provided at a rate of not less than 0.0051 m3/(s · m2) of floor area of the room. 5D.8.5 5D.8.6 Signs. Doors into rooms or buildings containing stationary lead-acid battery systems shall be provided with approved signs. The signs shall state that the room contains lead-acid battery systems, that the battery room contains energized electrical circuits, and that the battery electrolyte solutions are corrosive liquids. 5D.8.7 Seismic protection. The battery systems shall be seismically braced in accordance with the SBC 201. 2007 5/39 SBC 801 GENERAL PRECAUTIONS AGAINST FIRE 5D.8.8 Smoke detection. An approved automatic smoke detection system shall be installed in battery rooms in accordance with Section 7.7.2.23. SECTION 5D.9 VALVE-REGULATED LEAD-ACID (VRLA) BATTERY SYSTEMS 5D.9.1 Scope. Valve-regulated lead-acid (VRLA) battery systems having an electrolyte capacity of more than 189 L used for facility standby power, emergency power or uninterrupted power supplies (UPS) shall comply with this section. 5D.9.2 Safety vents. VRLA batteries shall be equipped with self-resealing flame-arresting safety vents. 5D.9.3 Thermal runaway. VRLA battery systems shall be provided with a listed device or other approved method to preclude, detect and control thermal runaway. 5D.9.4 Room design and construction. Enclosure of VRLA battery system rooms shall comply with the SBC 201. The battery systems are permitted to be in the same room with the equipment they support. When VRLA battery systems are installed in a separate equipment room accessible only to authorized personnel, they shall be allowed to be installed on an open rack for ease of maintenance. When a VRLA battery system is situated in an occupied work center, it shall be housed in a noncombustible cabinet or other enclosure to prevent access by unauthorized personnel. 5D.9.5 Neutralization. An approved manual method and materials for the neutralization of a release of electrolyte shall be provided. The method and materials shall be capable of controlling and neutralizing a release of 3 percent of the capacity of the largest VRLA cell or block in the room to a pH between 7.0 and 9.0. 5D.9.6 Room ventilation. Ventilation shall be provided to limit the maximum concentration of hydrogen to 1 percent of the total volume of the room during the worst-case event of simultaneous “boost” charging of all batteries in the room. Where calculations are not provided to substantiate the ventilation rate, continuous ventilation at a rate of not less than 0.0051 m3/(s · m2) of floor area of the room shall be provided. The ventilation shall be either mechanically or naturally induced. 5D.9.7 Cabinet ventilation. Where VRLA batteries are installed inside a cabinet, the cabinet shall be vented. The cabinet ventilation shall limit the maximum concentration of hydrogen to 1 percent of the total volume of the cabinet during the worst-case event of simultaneous “boost” charging of all batteries in the cabinet. Where calculations are not provided to substantiate the ventilation rate, continuous ventilation at a rate of not less than 0.0051 m3/(s · m2) of floor area covered by the cabinet shall be provided. The ventilation shall be either mechanically or naturally induced. The room in which the cabinet is installed shall also be ventilated as required in Section 7.9.6. 5D.9.8 Signs. Doors into electrical equipment rooms containing VRLA battery systems shall be provided with approved signs. The signs shall state that the room contains lead-acid battery systems and contains energized electrical circuits. Where VRLA 2007 5/40 SBC 801 GENERAL PRECAUTIONS AGAINST FIRE batteries are contained in cabinets in occupied work centers, the cabinet enclosures shall be located within 3 m of the equipment that they support. The cabinets shall have exterior labels that identify the manufacturer and model number of the system and electrical rating (voltage and current) of the contained battery system. Within the cabinet there shall be signs that indicate the relevant electrical, chemical and fire hazards. 5D.9.9 Seismic protection. The battery systems shall be seismically braced in accordance with the SBC 301. 5D.9.10 Smoke detection. An approved automatic smoke detection system shall be installed in rooms containing VRLA battery systems in accordance with Section 7.7.2.23. SECTION 5D.10 COMMERCIAL KITCHEN HOODS 5D.10.1 General. Commercial kitchen exhaust hoods shall comply with the requirements of the SBC 501. 5D.10.2 Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. SBC 801 2007 5/41 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS CHAPTER 6 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS SECTION 6.1 GENERAL 6.1.1 Scope. The provisions of this chapter shall govern furniture and furnishings, interior finishes, interior trim, decorative materials and decorative vegetation in buildings. Sections 6.3, 6.4 and 6.5 shall be applicable to new and existing buildings. Section 6.6 shall be applicable to existing buildings. SECTION 6.2 DEFINITIONS 6.2.1 Terms defined in Chapter 1. Words and terms used in this chapter and defined in Chapter 1 shall have the meanings ascribed to them as defined therein. SECTION 6.3 FURNISHINGS 6.3.1 6.3.1.1 6.3.1.2 6.3.1.3 6.3.2 6.3.2.1 6.3.2.2 6.3.3 SBC 801 General requirements. The provisions of Sections 6.3.1.1 through 6.3.1.3 shall be applicable to all occupancies covered by Sections 6.3.2 through 6.3.7. Explosive and highly flammable materials. Furnishings or decorations of an explosive or highly flammable character shall not be used. Fire-retardant coatings. Fire-retardant coatings shall be maintained so as to retain the effectiveness of the treatment under service conditions encountered in actual use. Obstructions. Furnishings or other objects shall not be placed to obstruct exits, access thereto, egress there from or visibility thereof. Group A. The requirements in Sections 6.3.2.1 and 6.3.2.2 shall apply to occupancies in Group A. Foam plastics. Exposed foam plastic materials and unprotected materials containing foam plastic used for decorative purposes or stage scenery or exhibit booths shall have a maximum heat release rate of 100 kilowatts (kW) when tested in accordance with UL 1975. Exceptions: 1. Individual foam plastic items or items containing foam plastic where the foam plastic does not exceed 0.45 kg in weight. 2. Cellular or foam plastic shall be allowed for trim not in excess of 10 percent of the wall or ceiling area, provided it is not less than 320 kg/m3 in density, is limited to 12.7 mm in thickness and 100 mm in width, and complies with the requirements for Class B interior wall and ceiling finish, except that the smoke-developed index shall not be limited. Motion picture screens. The screens upon which motion pictures are projected shall be either flame resistant, as demonstrated by complying with NFPA 701, or shall comply with the requirements for a Class B interior finish. Group E. The requirements in Sections 6.3.3.1 and 6.3.3.2 shall apply to occupancies in Group E. 2007 6/1 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS 6.3.3.1 6.3.3.2 6.3.4 6.3.4.1 6.3.4.2 6.3.5 6.3.5.1 6.3.5.2 6.3.5.3 SBC 801 Storage in corridors and lobbies. Clothing and personal effects shall not be stored in corridors and lobbies. Exceptions: 1. Corridors protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. 2. Corridors protected by an approved smoke detection system installed in accordance with Section 7.7. 3. Storage in metal lockers provided the minimum required egress width is maintained. Artwork. Artwork and teaching materials shall be limited on the walls of corridors to not more than 20 percent of the wall area. Group I-4, day care facilities. The requirements in Sections 6.3.4.1 and 6.3.4.2 shall apply to day care facilities classified in Group I-4. Storage in corridors and lobbies. Clothing and personal effects shall not be stored in corridors and lobbies. Exceptions: 1. Corridors protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. 2. Corridors protected by an approved smoke detection system installed in accordance with Section 7.7. 3. Storage in metal lockers provided the minimum required egress width is maintained. Artwork. Artwork and teaching materials shall be limited on walls of corridors to not more than 20 percent of the wall area. Group I-2, nursing homes and hospitals. The requirements in Sections 6.3.5.1 through 6.3.5.3 shall apply to nursing homes and hospitals classified in Group I-2. Upholstered furniture. Newly introduced upholstered furniture shall be shown to resist ignition by cigarettes as determined by tests conducted in accordance with NFPA 261 and shall have a char length not exceeding 38 mm. Exceptions: 1. Upholstered furniture belonging to the patient in sleeping rooms of nursing homes (Group I-2), provided that a smoke detector is installed in such rooms. Battery-powered, single-station smoke alarms shall be permitted. 2. Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. Upholstered furniture heat release rate. Newly introduced upholstered furniture shall have limited rates of heat release when tested in accordance with ASTM E 1537 or NFPA 266. 1. The peak rate of heat release for the single upholstered furniture item shall not exceed 250 kW. Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. 2. The total energy released by the single upholstered furniture item during the first 5 minutes of the test shall not exceed 40 mega joules (mJ). Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. Mattresses, heat-release rate. Newly introduced mattresses in Group I-2 occupancies shall have limited rates of heat release when tested in accordance with ASTM E 1590 or NFPA 267. 2007 6/2 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS 6.3.5.4 6.3.6 6.3.6.1 6.3.6.2 6.3.6.3 6.3.7 6.3.7.1 6.3.7.2 SBC 801 1. The peak rate of heat release for the mattress shall not exceed 250 kW. Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. 2. The total energy released by the mattress during the first 5 minutes of the test shall not exceed 40 mJ. Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. Identification. Upholstered furniture shall bear the label of an approved agency, confirming compliance with the requirements of Sections 6.3.5.1 and 6.3.5.2. Group I-1, board and care facilities. The requirements in Sections 6.3.6.1 through 6.3.6.3 shall apply to board and care facilities classified in Group I-1. Upholstered furniture. Newly introduced upholstered furniture shall meet the requirements for Class I when tested in accordance with NFPA 260. Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system. Mattresses. New mattresses shall have a char length not exceeding 50 mm. Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system. Mattresses, heat-release rate. Newly introduced mattresses in Group I-1 occupancies shall have limited rates of heat release when tested in accordance with ASTM E 1590 or NFPA 267. 1. The peak rate of heat release for the mattress shall not exceed 250 kW. Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system. 2. The total energy released by the mattress during the first 5 minutes of the test shall not exceed 40 mJ. Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system. Group I-3, detention and correction facilities. The requirements in Sections 6.3.7.1 through 6.3.7.6 shall apply to detention and correction facilities classified in Group I-3. Upholstered furniture classification. Newly introduced upholstered furniture shall meet the requirements for Class I where tested in accordance with NFPA 260. Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. Upholstered furniture heat release rate. Newly introduced upholstered furniture shall have limited rates of heat release, as follows: 1. The peak rate of heat release for the single upholstered furniture item shall not exceed 250 kW. Exceptions: 1. In Use Condition I, II and III occupancies, as defined in the SBC 201, upholstered furniture in rooms or spaces protected by approved smoke detectors that initiate, without delay, an alarm that is audible in that room or space. 2. Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. 2. The total energy released by the single upholstered furniture item during the first 5 minutes of the test shall not exceed 40 mJ. 2007 6/3 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS 6.3.7.3 6.3.7.4 6.3.7.5 6.3.7.6 Exception: Upholstered furniture in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. Mattresses, char length. Newly introduced mattresses shall have a char length not exceeding 50 mm. Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. Mattresses, heat release rate. Newly introduced mattresses in detention and correctional occupancies shall have limited rates of heat release when tested in accordance with ASTM E 1590 or NFPA 267, as follows: 1. The peak rate of heat release for the mattress shall not exceed 250 kW. Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. 2. The total energy released by the mattress during the first 5 minutes of the test shall not exceed 40 mJ. Exception: Mattresses in rooms or spaces protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1. Wastebaskets. Wastebaskets and other waste containers shall be of noncombustible or other approved materials. Wastebasket lids. Waste containers with a capacity of more than 76 L shall be provided with a lid of noncombustible or other approved material. SECTION 6.4 DECORATIVE VEGETATION 6.4.1 6.4.1.1 6.4.1.2 6.4.1.3 Natural cut trees. Natural cut trees, where permitted by this section, shall have the trunk bottoms cut off at least 12.7 mm above the original cut and shall be placed in a support device complying with Section 6.4.1.2. Restricted occupancies. Natural cut trees shall be prohibited in Group A, E, I-1, I-2, I-3, I-4, M, R-1, R-2 and R-4 occupancies. Exception: Trees located in areas protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2 shall not be prohibited in Groups A, E, M, R-1 and R-2. Support devices. The support device that holds the tree in an upright position shall be of a type that is stable and that meets all of the following criteria: 1. The device shall hold the tree securely and be of adequate size to avoid tipping over of the tree. 2. The device shall be capable of containing a minimum 2 days supply of water. 3. The water level, when full, shall cover the tree stem at least 50 mm. The water level shall be maintained above the fresh cut and checked at least once daily. Dryness. The tree shall be removed from the building whenever the needles or leaves fall off readily when a tree branch is shaken or if the needles are brittle and break when bent between the thumb and index finger. The tree shall be checked daily for dryness. 6.4.2 Obstruction of means of egress. The required width of any portion of a means of egress shall not be obstructed by decorative vegetation. 6.4.3 Open flame. Candles and open flames shall not be used on or near decorative vegetation. Natural cut trees shall be kept a distance from heat vents and any open flame or heat-producing devices at least equal to the height of the tree. SBC 801 2007 6/4 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS 6.4.3.1 Electrical fixtures and wiring. The use of unlisted electrical wiring and lighting on decorative vegetation shall be prohibited. 6.4.4 Artificial vegetation. Artificial decorative vegetation shall be flame resistant or flame retardant. Such flame resistance or flame retardance shall be documented and certified by the manufacturer in an approved manner. Electrical fixtures and wiring. The use of unlisted electrical wiring and lighting on decorative vegetation shall be prohibited. The use of electrical wiring and lighting on metal artificial trees shall be prohibited. 6.4.4.1 SECTION 6.5 DECORATIONS AND TRIM 6.5.1 6.5.1.1 6.5.1.2 General. In occupancies of Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall be flame resistant in accordance with Section 6.5.2 and NFPA 701 or be noncombustible. In Groups I-1 and I-2, combustible decorations shall be flame retardant unless the decorations, such as photographs and paintings, are of such limited quantities that a hazard of fire development or spread is not present. In Group I-3, combustible decorations are prohibited. Noncombustible materials. The permissible amount of noncombustible decorative material shall not be limited. Flame-resistant materials. The permissible amount of flame-resistant decorative materials shall not exceed 10 percent of the aggregate area of walls and ceilings. Exception: In auditoriums of Group A, the permissible amount of flame-resistant decorative material shall not exceed 50 percent of the aggregate area of walls and ceiling where the building is equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1, and where the material is installed in accordance with Section 7.11 of SBC 201. 6.5.2 Acceptance criteria and reports. Where required to be flame resistant, decorative materials shall be tested by an approved agency and pass Test 1, as described in NFPA 701, or such materials shall be noncombustible. Reports of test results shall be prepared in accordance with NFPA 701 and furnished to the Building code official upon request. 6.5.3 Foam plastic. Foam plastic used as interior trim shall comply with Sections 6.5.3.1 through 6.5.3.4. 3 Density. The minimum density of the interior trim shall be 320 kg/m . Thickness. The maximum thickness of the interior trim shall be 12.7 mm and the maximum width shall be 200 mm. Area limitation. The interior trim shall not constitute more than 10 percent of the aggregate wall and ceiling area of a room or space. Flame spread. The flame spread rating shall not exceed 75 where tested in accordance with ASTM E 84. The smoke-developed index shall not be limited. 6.5.3.1 6.5.3.2 6.5.3.3 6.5.3.4 6.5.4 SBC 801 Pyroxylin plastic. Imitation leather or other material, consisting of or coated with a pyroxylin or similarly hazardous base, shall not be used in Group A occupancies. 2007 6/5 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS 6.5.5 Trim. Material used as interior trim shall have a minimum Class C flame spread index and smoke-developed index. Combustible trim, excluding handrails and guardrails, shall not exceed 10 percent of the aggregate wall or ceiling area in which it is located. SECTION 6.6 INTERIOR FINISH AND DECORATIVE MATERIALS 6.6.1 General. The provisions of this section shall limit the allowable flame spread and smoke development of interior finishes and decorative materials in existing buildings based on location and occupancy classification. Exceptions: 1. Materials having a thickness less than 1.0 mm applied directly to the surface of walls and ceilings. 2. Exposed portions of structural members complying with the requirements of buildings of Type IV construction in accordance with the SBC 201 shall not be subject to interior finish requirements. Requirements based on occupancy. Interior finish and decorative materials shall be restricted by combustibility and flame resistance according to occupancy group in accordance with Table 6.6.3. Foam plastics. Cellular or foam plastics shall not be used as interior finish or trim. Exceptions: 1. Cellular or foam plastic materials shall be permitted on the basis of fire tests that substantiate their combustibility characteristics for the use intended under actual fire conditions. 2. Cellular or foam plastic shall be permitted for trim not in excess of 10 percent 3 of the wall or ceiling area, provided such trim is not less than 320 kg/m in density, is limited to 12.7 mm in thickness and 200 mm in width, and complies with the requirements for Class A or B interior wall and ceiling finish except that the smoke rating shall not be limited. Obstruction of means of egress. No decorations or other objects shall be placed to obstruct exits, access thereto, egress there from, or visibility thereof. 6.6.1.1 6.6.1.2 6.6.1.3 6.6.2 6.6.2.1 6.6.2.1.1 SBC 801 Wall and ceiling finish. Interior wall and ceiling finishes shall be classified in accordance with Section 7.11 of SBC 201. Such interior finishes shall be grouped in the following classes in accordance with their flame spread and smokedeveloped index. Class A: Flame spread index 0-25 Smoke-developed index 0-450 Class B: Flame spread index 26-75 Smoke-developed index 0-450 Class C: Flame spread index 76-450 Smoke-developed index 0-450 Exception: Materials, other than textiles, tested in accordance with Section 6.6.2.1. Interior wall and ceiling finishes other than textiles. Interior wall or ceiling finishes, other than textiles, shall be permitted to be tested in accordance with NFPA 286. Finishes tested in accordance with NFPA 286 shall comply with Section 6.6.2.1.1. Acceptance criteria. During the 40 kW exposure, the interior finish shall comply with Item 1. During the 160 kW exposure, the interior finish shall comply with Item 2. During the entire test, the interior finish shall comply with Item 3. 2007 6/6 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS 6.6.2.2 6.6.2.3 6.6.2.3.1 6.6.2.3.2 6.6.2.4 6.6.2.5 6.6.2.6 SBC 801 1. During the 40 kW exposure, flames shall not spread to the ceiling. 2. During the 160 kW exposure, the interior finish shall comply with the following: 2.1 Flame shall not spread to the outer extremity of the sample on any wall or ceiling. 2.2 Flashover, as defined in NFPA 286, shall not occur. 3. The total smoke released throughout the NFPA 286 test shall not exceed 1,000 2 m. Stability. Interior finish materials regulated by this chapter shall be applied or otherwise fastened in such a manner that such materials will not readily become detached when subjected to a room temperature of 93°C for not less than 30 minutes. Textiles. Textile wall coverings shall have a Class A flame spread rating when tested in accordance with ASTM E 84 and be protected by approved automatic sprinklers installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2 or the covering shall meet the criteria of Section 6.6.2.3.1 or 6.6.2.3.2 when tested in accordance with NFPA 265 using the product-mounting system, including adhesive, of actual use. Method A. When using method A, flame shall not spread to the ceiling during a 40 kW exposure. During the 150 kW exposure, all of the following criteria shall be met: 1. Flame shall not spread to the outer extremity of the sample on the 2.4 m by 3.7 m wall. 2. The specimen shall not burn to the outer extremity of the 06-m-wide samples mounted vertically in the corner of the room. 3. Burning droplets that are judged by the Building Code official to be capable of igniting the textile wall covering or that persist in burning for 30 seconds or more shall not be formed and dropped to the floor. 4. Flashover, as defined in NFPA 265, shall not occur. 5. The maximum instantaneous net peak rate of heat release shall not exceed 300 kW. Method B. When using method B, flame shall not spread to the ceiling during the 40 kW exposure. During the 150 kW exposure, all of the following criteria shall be met: 1. Flame shall not spread to the outer extremity of the sample on the 2.4 by 3.7 m wall. 2. Flashover, as defined in NFPA 265, shall not occur. Trim and incidental finish. Interior wall and ceiling finish not in excess of 10 percent of the aggregate wall and ceiling areas of any room or space shall be permitted to be Class C materials. Expanded vinyl wall coverings. Expanded vinyl wall coverings shall comply with the requirements for textile wall and ceiling materials and their use shall comply with Section 6.6.2.2. Exception: Expanded vinyl wall or ceiling coverings complying with Section 6.6.2.1 shall not be required to comply with Sections 6.6.2 and 6.6.3. Fire-retardant coatings. The required flame spread or smoke-developed classification of surfaces shall be permitted to be achieved by application of approved fire-retardant coatings, paints or solutions to surfaces having a flame spread rating exceeding that permitted. Such applications shall comply with NFPA 703 and the required fire-retardant properties shall be maintained or renewed in accordance with the manufacturer’s instructions. 2007 6/7 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS Wall and ceiling finish requirements. Interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 6.6.3 for the group and location designated. Interior wall and ceiling finish materials, other than textiles, tested in accordance with NFPA 286 and meeting the acceptance criteria of Section 6.6.2.1.1, shall be permitted to be used where a Class A classification in accordance with ASTM E 84 is required. 6.6.3 TABLE 6.6.3 k INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY GROUP A-1l & A-2 A-3f, l,A-4, A-5 B, E, M, R1, R-4 F H I-1 I-2 I-3 I-4 R-2 R-3 S U SPRINKLEREDm Exit access Vertical exits corridors and exit and other passagewaysa, b exitways B B B B C B B B A B C C C B C C B C B Aj B C C C No Restrictions Rooms and enclosed spacesc C NONSPRINKLERED Exit access corridors Vertical exits Rooms and and other and exit enclosed passagewaysa, b spacesc exitways d A A Be C A C C Cg C Bh, i C Bh, i C C C A B A A A A A B C B Ad B C A B A A A B C B No Restrictions C C C B B B B B C C C Class C interior finish materials shall be permitted for wainscotting or paneling of not more than 93 m2 of applied surface area in the grade lobby where applied directly to a noncombustible base or over furring strips applied to a noncombustible base and fire blocked as required by Section 7.11 of SBC 201. b. In vertical exits of buildings less than three stories in height of other than Group I-3, Class B interior finish for unsprinklered buildings and Class C for sprinklered buildings shall be permitted. c. Requirements for rooms and enclosed spaces shall be based upon spaces enclosed by partitions. Where a fireresistance rating is required for structural elements, the enclosing partitions shall extend from the floor to the ceiling. Partitions that do not comply with this shall be considered as enclosing spaces and the rooms or spaces on both sides shall be considered as one. In determining the applicable requirements for rooms and enclosed spaces, the specific occupancy thereof shall be the governing factor regardless of the group classification of the building or structure. d. Lobby areas in Group A-1, A-2 and A-3 occupancies shall not be less than Class B. e. Class C interior finish materials shall be permitted in Group A occupancies with an occupant load of 300 persons or less. f. For mosques and places or worship, wood used for ornamental purposes, trusses, paneling, or chancel furnishing shall be permitted. g. Class B required where building exceeds two stories. h. Class C interior finish materials shall be permitted in administrative spaces. i. Class C interior finish materials shall be permitted in rooms with a capacity of four persons or less. j. Class B materials shall be permitted as wainscoting extending not more than 1,219 mm above the finished floor in exit access corridors. k. Finish materials as provided for in other sections of these code requirements. l. Motion picture screens shall comply with Section 6.3.2.2. m. Applies when the vertical exits, exit passageways, exit access corridors or exitways, or rooms and spaces are protected by a sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. a. SBC 801 2007 6/8 FIRE PROTECTION SYSTEMS CHAPTER 7 FIRE PROTECTION SYSTEMS SECTION 7.1 GENERAL 7.1.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation, inspection, operation, testing and maintenance of all fire protection systems. 7.1.2 Construction documents. The Building official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Statement of compliance. Before requesting final approval of the installation, where required by the Building official, the installing contractor shall furnish a written statement to the Building official that the subject fire protection system has been installed in accordance with approved plans and has been tested in accordance with the manufacturer’s specifications and the appropriate installation standard. Any deviations from the design standards shall be noted and copies of the approvals for such deviations shall be attached to the written statement. 7.1.2.1 7.1.3 Permits. Permits shall be required as set forth in SBC 100. 7.1.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. Required fire protection systems. Fire protection systems required by these code requirements or the SBC 201 shall be installed, repaired, operated, tested and maintained in accordance with these code requirements. Nonrequired fire protection systems. Any fire protection system or portion thereof not required by these code requirements or the SBC 201 shall be allowed to be furnished for partial or complete protection provided such installed system meets these code requirements and the SBC 201. Additional fire protection systems. In occupancies of a hazardous nature, where special hazards exist in addition to the normal hazards of the occupancy, or where the Building official determines that access for fire apparatus is unduly difficult, the Building official shall have the authority to require additional safeguards. Such safeguards include, but shall not be limited to, the following: automatic fire detection systems, fire alarm systems, automatic fire-extinguishing systems, standpipe systems, or portable or fixed extinguishers. Fire protection equipment required under this section shall be installed in accordance with these code requirements and the applicable referenced standards. Appearance of equipment. Any device that has the physical appearance of life safety or fire protection equipment but that does not perform that life safety or fire protection function, shall be prohibited. 7.1.4.1 7.1.4.2 7.1.4.3 7.1.4.4 7.1.5 SBC 801 Installation acceptance testing. Fire detection and alarm systems, fireextinguishing systems, fire hydrant systems, fire standpipe systems, fire pump 2007 7/1 FIRE PROTECTION SYSTEMS 7.1.5.1 7.1.6 7.1.6.1 systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the Building official. The Building official shall be notified before any required acceptance testing. Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved. Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Standards. Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table 7.1.6.1. TABLE 7.1.6.1 FIRE PROTECTION SYSTEM MAINTENANCE STANDARDS SYSTEM Portable fire extinguishers Carbon dioxide fire-extinguishing system Halon 1301 fire-extinguishing systems Dry-chemical extinguishing systems Wet-chemical extinguishing systems Water-based fire protection systems Fire alarm systems Water-mist systems Clean-agent extinguishing systems STANDARD NFPA 10 NFPA 12 NFPA 12A NFPA 17 NFPA 17A NFPA 25 NFPA 72 NFPA 750 NFPA 2001 7.1.6.2 Records. Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the Building official upon request. 7.1.7 Systems out of service. Where a required fire protection system is out of service, the Civil Defence and the Building official shall be notified immediately and, where required by the Building official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. Where utilized, fire watches shall be provided with at least one approved means for notification of the Civil Defence and their only duty shall be to perform constant patrols of the protected premises and keep watch for fires. Impairment coordinator. The building owner shall assign an impairment coordinator to comply with the requirements of this section. In the absence of a specific designee, the owner shall be considered the impairment coordinator. Tag required. A tag shall be used to indicate that a system, or portion thereof, has been removed from service. Placement of tag. The tag shall be posted at each Civil Defence connection, system control valve, fire alarm control unit, fire alarm annunciator and fire command center, indicating which system, or part thereof, has been removed from service. The Building official shall specify where the tag is to be placed. Preplanned impairment programs. Preplanned impairments shall be authorized 7.1.7.1 7.1.7.2 7.1.7.3 7.1.7.4 SBC 801 2007 7/2 FIRE PROTECTION SYSTEMS 7.1.7.5 7.1.7.6 7.1.8 7.1.8.1 by the impairment coordinator. Before authorization is given, a designated individual shall be responsible for verifying that all of the following procedures have been implemented: 1. The extent and expected duration of the impairment have been determined. 2. The areas or buildings involved have been inspected and the increased risks determined. 3. Recommendations have been submitted to management or building owner/ manager. 4. The Civil Defence has been notified. 5. The insurance carrier, the alarm company, building owner/manager, and other authorities having jurisdiction have been notified. 6. The supervisors in the areas to be affected have been notified. 7. A tag impairment system has been implemented. 8. Necessary tools and materials have been assembled on the impairment site. Emergency impairments. When unplanned impairments occur, appropriate emergency action shall be taken to minimize potential injury and damage. The impairment coordinator shall implement the steps outlined in Section 7.1.7.4. Restoring systems to service. When impaired equipment is restored to normal working order, the impairment coordinator shall verify that all of the following procedures have been implemented: 1. Necessary inspections and tests have been conducted to verify that affected systems are operational. 2. Supervisors have been advised that protection is restored. 3. The Civil Defence has been advised that protection is restored. 4. The building owner/manager, insurance carrier, alarm company, and other involved parties have been advised that protection is restored. 5. The impairment tag has been removed. Removal of or tampering with equipment. It shall be unlawful for any person to remove, tamper with or otherwise disturb any fire hydrant, fire detection and alarm system, fire suppression system, or other fire appliance required by these code requirements except for the purpose of extinguishing fire, training purposes, recharging or making necessary repairs, or when approved by the Building official. Removal of or tampering with appurtenances. Locks, gates, doors, barricades, chains, enclosures, signs, tags or seals which have been installed by or at the direction of the Building official shall not be removed, unlocked, destroyed, tampered with or otherwise vandalized in any manner. 7.1.9 Modifications. No person shall remove or modify any fire protection system installed or maintained under the provisions of these code requirements or the SBC 201 without approval by the building official. 7.1.10 Threads. Threads provided for fire department connections to sprinkler systems, standpipes, yard hydrants or any other fire hose connection shall be compatible with the connections used by the local Civil Defence. 7.1.11 Acceptance tests. Fire protection systems shall be tested in accordance with the requirements of these code requirements and the SBC 201. When required, the tests shall be conducted in the presence of the building official. Tests required by these code requirements, the SBC 201 and the standards listed in these code requirements shall be conducted at the expense of the owner or the owner’s SBC 801 2007 7/3 FIRE PROTECTION SYSTEMS representative. It shall be unlawful to occupy portions of a structure until the required fire protection systems within that portion of the structure have been tested and approved. 7.1.12 7.1.12.1 7.1.12.2 7.1.12.3 7.1.13 Supervisory service. Where required, fire protection systems shall be monitored by an approved supervising station in accordance with NFPA 72. Automatic sprinkler systems. Automatic sprinkler systems shall be monitored by an approved supervising station. Exceptions: 1. A supervising station is not required for automatic sprinkler systems protecting one- and two-family dwellings. 2. Limited area systems serving fewer than 20 sprinklers. Fire alarm systems. Fire alarm systems required by the provisions of Section 7.7.2 of these code requirements shall be monitored by an approved supervising station in accordance with Section 7.7.15. Exceptions: 1. Single- and multiple-station smoke alarms required by Section 7.7.2.10. 2. Smoke detectors in Group I-3 occupancies. 3. Supervisory service is not required for automatic sprinkler systems in one- and two-family dwellings. Group H. Manual fire alarm, automatic fire-extinguishing and emergency alarm systems in Group H occupancies shall be monitored by an approved supervising station. Exception: When approved by the building official, on-site monitoring at a constantly attended location shall be permitted provided that notifications to the fire department will be equal to those provided by an approved supervising station. Fire areas. Where buildings, or portions thereof, are divided into fire areas so as not to exceed the limits established for requiring a fire protection system in accordance with this chapter, such fire areas shall be separated by fire barriers having a fire-resistance rating of not less than that determined in accordance with Section 4.6.3.7 of the SBC 201. SECTION 7.2 DEFINITIONS 7.2.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in these code requirements, have the meanings shown herein. ALARM NOTIFICATION APPLIANCE. A fire alarm system component such as a bell, horn, speaker, light, or text display that provides audible, tactile, or visible outputs, or any combination thereof. ALARM SIGNAL. A signal indicating an emergency requiring immediate action, such as a signal indicative of fire. ALARM VERIFICATION FEATURE. A feature of automatic fire detection and alarm systems to reduce unwanted alarms wherein smoke detectors report alarm conditions for a minimum period of time, or confirm alarm conditions within a given time period, after being automatically reset, in order to be accepted as a valid alarm-initiation signal. SBC 801 2007 7/4 FIRE PROTECTION SYSTEMS ANNUNCIATOR. A unit containing one or more indicator lamps, alphanumeric displays, or other equivalent means in which each indication provides status information about a circuit, condition or location. AUDIBLE ALARM NOTIFICATION APPLIANCE. A notification appliance that alerts by the sense of hearing. AUTOMATIC. As applied to fire protection devices, is a device or system providing an emergency function without the necessity for human intervention and activated as a result of a predetermined temperature rise, rate of temperature rise, or combustion products. AUTOMATIC FIRE-EXTINGUISHING SYSTEM. An approved system of devices and equipment which automatically detects a fire and discharges an approved fire-extinguishing agent onto or in the area of a fire. AUTOMATIC SPRINKLER SYSTEM. A sprinkler system, for fire protection purposes, is an integrated system of underground and overhead piping designed in accordance with fire protection engineering standards. The system includes a suitable water supply. The portion of the system above the ground is a network of specially sized or hydraulically designed piping installed in a structure or area, generally overhead, and to which automatic sprinklers are connected in a systematic pattern. The system is usually activated by heat from a fire and discharges water over the fire area. AVERAGE AMBIENT SOUND LEVEL. The root mean square, A-weighted sound pressure level measured over a 24-hour period. CARBON DIOXIDE EXTINGUISHING SYSTEM. A system supplying carbon dioxide (CO2) from a pressurized vessel through fixed pipes and nozzles. The system includes a manual or automatic-actuating mechanism. CLEAN AGENT. Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave a residue upon evaporation. CONSTANTLY ATTENDED LOCATION. A designated location at a facility staffed by trained personnel on a continuous basis where alarm or supervisory signals are monitored and facilities are provided for notification of the Civil Defence or other emergency services. DELUGE SYSTEM. A sprinkler system employing open sprinklers attached to a piping system connected to a water supply through a valve that is opened by the operation of a detection system installed in the same area as the sprinklers. When this valve opens, water flows into the piping system and discharges from all sprinklers attached thereto. DETECTOR, HEAT. A fire detector that senses heat produced by burning substances. Heat is the energy produced by combustion that causes substances to rise in temperature. DRY-CHEMICAL EXTINGUISHING AGENT. A powder composed of small particles, usually of sodium bicarbonate, potassium bicarbonate, urea-potassiumSBC 801 2007 7/5 FIRE PROTECTION SYSTEMS based bicarbonate, potassium chloride or monoammonium phosphate, with added particulate material supplemented by special treatment to provide resistance to packing, resistance to moisture absorption (caking) and the proper flow capabilities. EMERGENCY ALARM SYSTEM. A system to provide indication and warning of emergency situations involving hazardous materials. EMERGENCY VOICE/ALARM COMMUNICATIONS. Dedicated manual or automatic facilities for originating and distributing voice instructions, as well as alert and evacuation signals pertaining to a fire emergency, to the occupants of a building. FIRE ALARM BOX, MANUAL. See “Manual fire alarm box.” FIRE ALARM CONTROL UNIT. A system component that receives inputs from automatic and manual fire alarm devices and is capable of supplying power to detection devices and transponder(s) of off-premises transmitter(s). The control unit is capable of providing a transfer of power to the notification appliances and transfer of condition to relays of devices. FIRE ALARM SIGNAL. A signal initiated by a fire alarm-initiating device such as a manual fire alarm box, automatic fire detector, water-flow switch, or other device whose activation is indicative of the presence of a fire or fire signature. FIRE ALARM SYSTEM. A system or portion of a combination system consisting of components and circuits arranged to monitor and annunciate the status of fire alarm or supervisory signal-initiating devices and to initiate the appropriate response to those signals. FIRE AREA. The aggregate floor area enclosed and bounded by fire walls, fire barriers, exterior walls, or fire-resistance-rated horizontal assemblies of a building. FIRE DETECTOR, AUTOMATIC. A device designed to detect the presence of a fire signature and to initiate action. FIRE PROTECTION SYSTEM. Approved devices, equipment and systems or combinations of systems used to detect a fire, activate an alarm, extinguish or control a fire, control or manage smoke and products of a fire or any combination thereof. FIRE SAFETY FUNCTIONS. Building and fire control functions that are intended to increase the level of life safety for occupants or to control the spread of the harmful effects of fire. FOAM-EXTINGUISHING SYSTEM. A special system discharging a foam made from concentrates, either mechanically or chemically, over the area to be protected. HALOGENATED EXTINGUISHING SYSTEM. A fire-extinguishing system using one or more atoms of an element from the halogen chemical series: fluorine, chlorine, bromine and iodine. SBC 801 2007 7/6 FIRE PROTECTION SYSTEMS IMPAIRMENT COORDINATOR. The person responsible for the maintenance of a particular fire protection system. INITIATING DEVICE. A system component that originates transmission of a change-of-state condition, such as in a smoke detector, manual fire alarm box, or supervisory switch. LISTED. Equipment, materials or services included in a list published by an organization acceptable to the building official and concerned with evaluation of products or services that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services and whose listing states either that the equipment, material or service meets identified standards or has been tested and found suitable for a specified purpose. MANUAL FIRE ALARM BOX. A manually operated device used to initiate an alarm signal. MULTIPLE-STATION ALARM DEVICE. Two or more single-station alarm devices that can be interconnected such that actuation of one causes all integral or separate audible alarms to operate. It also can consist of one single-station alarm device having connections to other detectors or to a manual fire alarm box. MULTIPLE-STATION SMOKE ALARM. Two or more single-station alarm devices that are capable of interconnection such that actuation of one causes all integral or separate audible alarms to operate. NUISANCE ALARM. An alarm caused by mechanical failure, malfunction, improper installation, or lack of proper maintenance, or an alarm activated by a cause that cannot be determined. RECORD DRAWINGS. Drawings (“as builts”) that document the location of all devices, appliances, wiring, sequences, wiring methods, and connections of the components of a fire alarm system as installed. SINGLE-STATION SMOKE ALARM. An assembly incorporating the detector, the control equipment, and the alarm-sounding device in one unit, operated from a power supply either in the unit or obtained at the point of installation. SLEEPING UNIT. A room or space in which people sleep, which can also include permanent provisions for living, eating, and either sanitation or kitchen facilities but not both. Such rooms and spaces that are also part of a dwelling unit are not sleeping units. SMOKE ALARM. A single or multiple-station alarm responsive to smoke and not connected to a system. SMOKE DETECTOR. A listed device that senses visible or invisible particles of combustion. SBC 801 2007 7/7 FIRE PROTECTION SYSTEMS SMOKEPROOF ENCLOSURE. An exit stairway designed and constructed so that the movement of the products of combustion produced by a fire occurring in any part of the building into the enclosure is limited. STANDPIPE SYSTEM, CLASSES OF. Standpipe classes are as follows: Class I system. A system providing 65 mm hose connections to supply water for use by Civil Defence and those trained in handling heavy fire streams. Class II system. A system providing 40 mm hose stations to supply water for use primarily by the building occupants or by the Civil Defence during initial response. Class III system. A system providing 40 mm hose stations to supply water for use by building occupants and 65 mm hose connections to supply a larger volume of water for use by fire departments and those trained in handling heavy fire streams. STANDPIPE, TYPES OF. Standpipe types are as follows: Automatic dry. A dry standpipe system, normally filled with pressurized air, that is arranged through the use of a device, such as a dry pipe valve, to admit water into the system piping automatically upon the opening of a hose valve. The water supply for an automatic dry standpipe system shall be capable of supplying the system demand. Automatic wet. A wet standpipe system that has a water supply that is capable of supplying the system demand automatically. Manual dry. A dry standpipe system that does not have a permanent water supply attached to the system. Manual dry standpipe systems require water from a fire department pumper to be pumped into the system through the Civil Defence connection in order to supply the system demand. Manual wet. A wet standpipe system connected to a water supply for the purpose of maintaining water within the system but which does not have a water supply capable of delivering the system demand attached to the system. Manual wet standpipe systems require water from a Civil Defence pumper (or the like) to be pumped into the system in order to supply the system demand. Semi-automatic dry. A dry standpipe system that is arranged through the use of a device, such as a deluge valve, to admit water into the system piping upon activation of a remote control device located at a hose connection. A remote control activation device shall be provided at each hose connection. The water supply for a semi-automatic dry standpipe system shall be capable of supplying the system demand. SUPERVISING STATION. A facility that receives signals and at which personnel are in attendance at all times to respond to these signals. SUPERVISORY SERVICE. The service required to monitor performance of guard tours and the operative condition of fixed suppression systems or other systems for the protection of life and property. SUPERVISORY SIGNAL. A signal indicating the need of action in connection with the supervision of guard tours, the fire suppression systems or equipment, or the maintenance features of related systems. SUPERVISORY SIGNAL-INITIATING DEVICE. An initiating device such as a valve supervisory switch, water level indicator, or low-air pressure switch on SBC 801 2007 7/8 FIRE PROTECTION SYSTEMS a dry-pipe sprinkler system whose change of state signals an off-normal condition and its restoration to normal of a fire protection or life safety system; or a need for action in connection with guard tours, fire suppression systems or equipment, or maintenance features of related systems. TIRES, BULK STORAGE OF. Storage of tires where the area available for storage exceeds 566 m3. TROUBLE SIGNAL. A signal initiated by the fire alarm system or device indicative of a fault in a monitored circuit or component. VISIBLE ALARM NOTIFICATION APPLIANCE. A notification appliance that alerts by the sense of sight. WET-CHEMICAL EXTINGUISHING AGENT. A solution of water and potassium-carbonate-based chemical, potassium-acetate-based chemical or a combination thereof, forming an extinguishing agent. WIRELESS PROTECTION SYSTEM. A system or a part of a system that can transmit and receive signals without the aid of wire. ZONE. A defined area within the protected premises. A zone can define an area from which a signal can be received, an area to which a signal can be sent, or an area in which a form of control can be executed. SECTION 7.3 AUTOMATIC SPRINKLER SYSTEMS 7.3.1 7.3.1.1 General. Automatic sprinkler systems shall comply with this section. Alternative protection. Alternative automatic fire-extinguishing systems complying with Section 7.4 shall be permitted in lieu of automatic sprinkler protection where recognized by the applicable standard and approved by the Building official. 7.3.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in this section. Exception: Spaces or areas in telecommunications buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries and standby engines, provided those spaces or areas are equipped throughout with an automatic fire alarm system and are separated from the remainder of the building by a wall with a fire-resistance rating of not less than 1 hour and a floor/ceiling assembly with a fire-resistance rating of not less than 2 hours. Group A. An automatic sprinkler system shall be provided throughout buildings and portions thereof used as Group A occupancies as provided in this section. For Group A-1, A-2, A-3, and A-4 occupancies, the automatic sprinkler system shall be provided throughout the floor area where the Group A-1, A-2, A-3 or A-4 occupancy is located, and in all floors between the Group A occupancy and the level of exit discharge. For group A-5 occupancies, the automatic sprinkler system shall be provided in the spaces indicated in Section 7.3.2.1.5. Group A-1. An automatic sprinkler system shall be provided for Group A-1 occupancies where one of the following conditions exists: 7.3.2.1 7.3.2.1.1 SBC 801 2007 7/9 FIRE PROTECTION SYSTEMS 7.3.2.1.2 7.3.2.1.3 7.3.2.1.4 7.3.2.1.5 7.3.2.2 7.3.2.3 7.3.2.3.1 7.3.2.4 7.3.2.4.1 7.3.2.4.2 SBC 801 1. The fire area exceeds 1,115 m2; 2. The fire area has an occupant load of 300 or more; 3. The fire area is located on a floor other than the level of exit discharge; or 4. The fire area contains a multitheater complex. Group A-2. An automatic sprinkler system shall be provided for Group A-2 occupancies where one of the following conditions exists: 1. The fire area exceeds 465 m2; 2. The fire area has an occupant load of 300 or more; or 3. The fire area is located on a floor other than the level of exit discharge. Group A-3. An automatic sprinkler system shall be provided for Group A-3 occupancies where one of the following conditions exists: 1. The fire area exceeds 1.1 m2; 2. The fire area has an occupant load of 300 or more; or 3. The fire area is located on a floor other than the level of exit discharge. Exception: Areas used exclusively as participant sports areas where the main floor area is located at the same level as the level of exit discharge of the main entrance and exit. Group A-4. An automatic sprinkler system shall be provided for Group A-4 occupancies where one of the following conditions exists: 1. The fire area exceeds 1.1 m2; 2. The fire area has an occupant load of 300 or more; or 3. The fire area is located on a floor other than the level of exit discharge. Exception: Areas used exclusively as participant sports areas where the main floor area is located at the same level as the level of exit discharge of the main entrance and exit. Group A-5. An automatic sprinkler system shall be provided in concession stands, retail areas, press boxes, and other accessory use areas in excess of 93 m2. Group E. An automatic sprinkler system shall be provided for Group E occupancies as follows: 1. Throughout all Group E fire areas greater than 1.9 m2 in area. 2. Throughout every portion of educational buildings below the level of exit discharge. Exception: An automatic sprinkler system is not required in any fire area or area below the level of exit discharge where every classroom throughout the building has at least one exterior exit door at ground level. Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exist: 1. Where a Group F-1 fire area exceeds 1.1 m2; 2. Where a Group F-1 fire area is located more than three stories above grade; or 3. Where the combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 2.2 m2. Woodworking operations. An automatic sprinkler system shall be provided throughout all Group F-1 occupancy fire areas that contain woodworking operations in excess of 232 m2 which generate finely divided combustible waste or which use finely divided combustible materials. Group H. Automatic sprinkler systems shall be provided in high-hazard occupancies as required in Sections 7.3.2.4.1 through 7.3.2.4.3. General. An automatic sprinkler system shall be installed in Group H occupancies. Group H-5 occupancies. An automatic sprinkler system shall be installed throughout buildings containing Group H-5 occupancies. The design of the 2007 7/10 FIRE PROTECTION SYSTEMS 7.3.2.4.3 sprinkler system shall not be less than that required under the SBC 201 for the occupancy hazard classifications in accordance with Table 7.3.2.4.2. Where the design area of the sprinkler system consists of a corridor protected by one row of sprinklers, the maximum number of sprinklers required to be calculated is 13. Pyroxylin plastics. An automatic sprinkler system shall be provided in buildings, or portions thereof, where cellulose nitrate film or pyroxylin plastics are manufactured, stored or handled in quantities exceeding 45 kg. TABLE 7.3.2.4.2 GROUP H-5 SPRINKLER DESIGN CRITERIA OCCUPANCY HAZARD CLASSIFICATION LOCATION 7.3.2.5 7.3.2.6 7.3.2.6.1 7.3.2.7 7.3.2.8 7.3.2.8.1 7.3.2.8.2 SBC 801 Fabrication areas Ordinary Hazard Group 2 Service corridors Ordinary Hazard Group 2 Storage rooms without dispensing Ordinary Hazard Group 2 Storage rooms with dispensing Extra Hazard Group 2 Corridors Ordinary Hazard Group 2 Group I. An automatic sprinkler system shall be provided throughout buildings with a Group I fire area. Exception: An automatic sprinkler system installed in accordance with Section 7.3.3.1.2 or 7.3.3.1.3 shall be allowed in Group I-1 facilities. Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one of the following conditions exists: 1. Where a Group M fire area exceeds 1.1 m2; 2. Where a Group M fire area is located more than three stories above grade; or 3. Where the combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 2,230 m2. High-piled storage. An automatic sprinkler system shall be provided as required in Chapter 21 in all buildings of Group M where storage of merchandise is in highpiled or rack storage arrays. Group R. An automatic sprinkler system installed in accordance with Section 7.3.3 shall be provided throughout all buildings with a Group R fire area. Group S-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exist: 1. Where a Group S-1 fire area exceeds 1.1 m2; 2. Where a Group S-1 fire area is located more than three stories above grade; or 3. Where the combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 2,230 m2. Repair garages. An automatic sprinkler system shall be provided throughout all buildings used as repair garages in accordance with the SBC 201, as follows: 1. Buildings two or more stories in height, including basements, with a fire area containing a repair garage exceeding 929 m2. 2. One-story buildings with a fire area containing a repair garage exceeding 1.1 m2. 3. Buildings with a repair garage servicing vehicles parked in the basement. Bulk storage of tires. Buildings and structures where the area for the storage of 3 tires exceeds 566 m shall be equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1. 2007 7/11 FIRE PROTECTION SYSTEMS Group S-2. An automatic sprinkler system shall be provided throughout buildings classified as an enclosed parking garage in accordance with the SBC 201 or where located beneath other groups. Exception: Enclosed parking garages located beneath Group R-3 occupancies. 7.3.2.9.1 Commercial parking garages. An automatic sprinkler system shall be provided throughout buildings used for storage of commercial trucks or buses where the fire area exceeds 464 m2. 7.3.2.10 All occupancies except Groups R-3 and U. An automatic sprinkler system shall be installed in the locations set forth in Sections 7.3.2.10.1 through 7.3.2.10.1.3. Exception: Group R-3 and Group U. 7.3.2.10.1 Stories and basements without openings. An automatic sprinkler system shall be installed in every story or basement of all buildings where the floor area exceeds 140 m2 and where there is not provided at least one of the following types of exterior wall openings: 1. Openings below grade that lead directly to ground level by an exterior stairway complying with Section 8.9 or an outside ramp complying with Section 8.10. Openings shall be located in each 15.2 m, or fraction thereof, of exterior wall in the story on at least one side. 2 2. Openings entirely above the adjoining ground level totaling at least 1.86 m in each 15.2, or fraction thereof, of exterior wall in the story on at least one side. 7.3.2.10.1.1 Opening dimensions and access. Openings shall have a minimum dimension of not less than 762 mm. Such openings shall be accessible to the Civil Defence from the exterior and shall not be obstructed in a manner that fire fighting or rescue cannot be accomplished from the exterior. 7.3.2.10.1.2 Openings on one side only. Where openings in a story are provided on only one side and the opposite wall of such story is more than 23.0 m from such openings, the story shall be equipped throughout with an approved automatic sprinkler system or openings as specified above shall be provided on at least two sides the story. 7.3.2.10.1.3 Basements. Where any portion of a basement is located more than 23.0 m from openings required by Section 7.3.2.10.1, the basement shall be equipped throughout with an approved automatic sprinkler system. 7.3.2.10.2 Rubbish and linen chutes. An automatic sprinkler system shall be installed at the top of rubbish and linen chutes and in their terminal rooms. Chutes extending through three or more floors shall have additional sprinkler heads installed within such chutes at alternate floors. Chute sprinklers shall be accessible for servicing. 7.3.2.10.3 Buildings more than 16.8 meters in height. An automatic sprinkler system shall be installed throughout buildings with a floor level having an occupant load of 30 or more that is located 16.8 m or more above the lowest level of Civil Defence vehicle access. Exceptions: 1. Airport control towers. 2. Open parking structures. 3. Occupancies in Group F-2. 7.3.2.11 During construction. Automatic sprinkler systems required during construction, alteration and demolition operations shall be provided in accordance with Section 10.13. 7.3.2.12 Other hazards. Automatic sprinkler protection shall be provided for the hazards indicated in Sections 7.3.2.12.1 and 7.3.2.12.2. 7.3.2.12.1 Ducts conveying hazardous exhausts. Where required by the SBC 501, automatic sprinklers shall be provided in ducts conveying hazardous exhaust, flammable or combustible materials. 7.3.2.9 SBC 801 2007 7/12 FIRE PROTECTION SYSTEMS 7.3.2.12.2 7.3.2.13 Exception: Ducts where the largest cross-sectional diameter of the duct is less than 254 mm. Commercial cooking operations. An automatic sprinkler system shall be installed in a commercial kitchen exhaust hood and duct system where an automatic sprinkler system is used to comply with Section 7.4. Other required suppression systems. In addition to the requirements of Section 7.3.2, the provisions indicated in Table 7.3.2.13 also require the installation of a suppression system for certain buildings and areas. TABLE 7.3.2.13 ADDITIONAL REQUIRED FIRE-EXTINGUISHING SYSTEMS SECTION 8.24.6.2.3 12.4.1 12.4.6 12.5.1 12.5.6.1 12.5.8.4 13.8.2 13.8.3 16.3.10 16.3.10.1.1 16.3.10.2 16.3.10.3 16.3.10.4 16.3.10.4 16.3.10.4.2 17.7.3 17.8.7 19.6.1 19.6.2 Table 21.6.2 21.6.4 25.3.8.4.1 25.3.8.5.3 25.4.5 25.5.1.8 26.4.4.1 27.4.5 31.6.5.2.1 31.6.5.2.3 32.4.3.7.5.1 32.4.3.8 32.5.3.7.3 35.4.1.2 35.4.1.3 SBC 801 SUBJECT Smoke-protected seating Spray finishing in Group A, E, I or R Spray booths and rooms Dip-tank rooms Dip tanks Hardening and tempering tanks Dry cleaning plants Dry cleaning machines HPM facilities HPM work station exhaust HPM gas cabinets HPM corridors HPM exhaust HPM noncombustible ducts HPM combustible ducts Lumber production conveyor rooms Recycling facility conveyor rooms Class A and B ovens Class C and D ovens Storage fire protection Storage Gas rooms Exhausted enclosures Indoor storage of hazardous materials Indoor dispensing of hazardous materials Aerosol warehouses Storage of more than 28 m3 of loose combustible fibers Storage of smokeless propellant Storage of small arms primers Flammable and combustible liquid storage rooms Flammable and combustible liquid storage warehouses Flammable and combustible liquid Group H-2 or H-3 areas Gas cabinets for highly toxic and toxic gas Exhausted enclosures for highly toxic and toxic gas (Continued) 2007 7/13 FIRE PROTECTION SYSTEMS TABLE 7.3.2.13 – continued ADDITIONAL REQUIRED FIRE-EXTINGUISHING SYSTEMS SECTION 35.4.2.2.6 35.4.3.3 39.6.2.2 40.4.1.1 40.4.1.3 40.4.2 SUBJECT Gas rooms for highly toxic and toxic gas Outdoor storage for highly toxic and toxic gas Exhausted enclosures or gas cabinets for silane gas Pyroxylin plastic storage cabinets Pyroxylin plastic storage vaults Pyroxylin plastic storage and manufacturing Installation requirements. Automatic sprinkler systems shall be designed and installed in accordance with Sections 7.3.3.1 through 7.3.3.7. 7.3.3.1 Standards. Sprinkler systems shall be designed and installed in accordance with Section 7.3.3.1.1, 7.3.3.1.2 or 7.3.3.1.3. 7.3.3.1.1 Sprinkler systems. Where the provisions of these code requirements require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 except as provided in Section 7.3.3.1.1.1. 7.3.3.1.1.1 Exempt locations. Automatic sprinklers shall not be required in the following rooms or areas where such rooms or areas are protected with an approved automatic fire detection system in accordance with Section 7.7.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from any room merely because it is damp, of fire-resistance rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the Building official. 3. Generator and transformer rooms separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours. 4. In rooms or areas that are of noncombustible construction with wholly noncombustible contents. 7.3.3.1.2 Sprinkler systems. Where allowed in buildings of Group R, up to and including four stories in height, automatic sprinkler systems shall be installed throughout in accordance with NFPA 13R. 7.3.3.1.2.1 Balconies. Sprinkler protection shall be provided for exterior balconies and ground floor patios of dwelling units where the building is of Type V construction. Sidewall sprinklers that are used to protect such areas shall be permitted to be located such that their deflectors are within 25 mm to 150 mm below the structural members, and a maximum distance of 350 mm below the deck of the exterior balconies that are constructed of open wood joist construction. 7.3.3.1.3 Sprinkler systems. Where allowed, automatic sprinkler systems installed in oneand two-family dwellings shall be installed throughout in accordance with NFPA 13D. 7.3.3.2 Quick-response and residential sprinklers. Where automatic sprinkler systems are required by these code requirements, quick-response or residential automatic sprinklers shall be installed in the following areas in accordance with Section 7.3.3.1 and their listings: 1. Throughout all spaces within a smoke compartment containing patient sleeping 7.3.3 SBC 801 2007 7/14 FIRE PROTECTION SYSTEMS units in Group I-2 in accordance with the SBC 201. 2. Dwelling units and sleeping units in Group R and I-1 occupancies. 3. Light-hazard occupancies as defined in NFPA 13. 7.3.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 1.2 m in width. Not less than a 0.9 m clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers. Exception: Kitchen equipment under exhaust hoods protected with a fireextinguishing system in accordance with Section 7.4. 7.3.3.4 Actuation. Automatic sprinkler systems shall be automatically actuated unless specifically provided for in these code requirements. 7.3.3.5 Water supplies. Water supplies for automatic sprinkler systems shall comply with this section and the standards referenced in Section 7.3.3.1. The potable water supply shall be protected against backflow in accordance with the requirements of this section and the SBC 701. 7.3.3.5.1 Domestic services. Where the domestic service provides the water supply for the automatic sprinkler system, the supply shall be in accordance with this section. 7.3.3.5.1.1 Limited area sprinkler systems. Limited area sprinkler systems serving fewer than 20 sprinklers on any single connection are permitted to be connected to the domestic service where a wet automatic standpipe is not available. Limited area sprinkler systems connected to domestic water supplies shall comply with each of the following requirements: 1. Valves shall not be installed between the domestic water riser control valve and the sprinklers. Exception: An approved indicating control valve supervised in the open position in accordance with Section 7.3.4. 2. The domestic service shall be capable of supplying the simultaneous domestic demand and the sprinkler demand required to be hydraulically calculated by NFPA 13, NFPA 13R or NFPA 13D. 7.3.3.5.1.2 Residential combination services. A single combination water supply shall be permitted provided that the domestic demand is added to the sprinkler demand as required by NFPA 13R. 7.3.3.5.2 Secondary water supply. A secondary on-site water supply equal to the hydraulically calculated sprinkler demand, including the hose stream requirement, shall be provided for high-rise buildings in Seismic Design Category C, D, E or F as determined by the SBC 201. The secondary water supply shall have a duration not less than 30 minutes as determined by the occupancy hazard classification in accordance with NFPA 13. Exception: Existing buildings. 7.3.3.6 Hose threads. Fire hose threads used in connection with automatic sprinkler systems shall be approved and shall be compatible with Civil Defence hose threads. 7.3.3.7 Civil Defence connections. The location of Civil Defence connections shall be approved by the Building official. 7.3.4 SBC 801 Sprinkler system monitoring and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, and water-flow switches on all sprinkler systems shall be electrically supervised. 2007 7/15 FIRE PROTECTION SYSTEMS 7.3.4.1 7.3.4.2 7.3.4.3 Exceptions: 1. Automatic sprinkler systems protecting one- and two-family dwellings. 2. Limited area systems serving fewer than 20 sprinklers. 3. Automatic sprinkler systems installed in accordance with NFPA 13R where a common supply main is used to supply both domestic water and the automatic sprinkler system, and a separate shutoff valve for the automatic sprinkler system is not provided. 4. Jockey pumps control valves that are sealed or locked in the open position. 5. Control valves to commercial kitchen hoods, paint spray booths or dip tanks that are sealed or locked in the open position. 6. Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position. 7. Trim valves to pressure switches in dry, preaction and deluge sprinkler systems that are sealed or locked in the open position. Signals. Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA 72 or, when approved by the Building official, shall sound an audible signal at a constantly attended location. Exceptions: 1. Underground key or hub valves in roadway boxes provided by the municipality or public utility are not required to be monitored. 2. Backflow prevention device test valves, located in limited area sprinkler system supply piping, shall be locked in the open position. In occupancies required to be equipped with a fire alarm system, the backflow preventer valves shall be electrically supervised by a tamper switch installed in accordance with NFPA 72 and separately annunciated. Alarms. Approved audible devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Floor control valves. Approved supervised indicating control valves shall be provided at the point of connection to the riser on each floor in high-rise buildings. 7.3.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 7.1. 7.3.6 Existing buildings. The provisions of this section are intended to provide a reasonable degree of safety in existing structures not complying with the minimum requirements of the SBC 201 by requiring installation of an automatic fireextinguishing system. Pyroxylin plastics. All structures occupied for the manufacture or storage of articles of cellulose nitrate (pyroxylin) plastic shall be equipped with an approved automatic fire-extinguishing system. Vaults located within buildings for the storage of raw pyroxylin shall be protected with an approved automatic sprinkler system capable of discharging 68 L/min/m2 over the area of the vault. 7.3.6.1 SBC 801 2007 7/16 FIRE PROTECTION SYSTEMS SECTION 7.4 ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS 7.4.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards. 7.4.2 Where required. Automatic fire-extinguishing systems installed as an alternative to the required automatic sprinkler systems of Section 7.3 shall be approved by the Building official. Automatic fire-extinguishing systems shall not be considered alternatives for the purposes of exceptions or reductions permitted by other requirements of these code requirements. Hood system suppression. Each required commercial kitchen exhaust hood and duct system required by Section 4.10 to have a Type I hood shall be protected with an approved automatic fire-extinguishing system installed in accordance with these code requirements. 7.4.2.1 7.4.3 7.4.3.1 7.4.3.2 7.4.3.3 7.4.3.4 7.4.3.5 7.4.4 7.4.4.1 7.4.4.2 SBC 801 Installation. Automatic fire-extinguishing systems shall be installed in accordance with this section. Electrical wiring. Electrical wiring shall be in accordance with the SBC 401. Actuation. Automatic fire-extinguishing systems shall be automatically actuated and provided with a manual means of actuation in accordance with Section 7.4.11.1. System interlocking. Automatic equipment interlocks with fuel shutoffs, ventilation controls, door closers, window shutters, conveyor openings, smoke and heat vents, and other features necessary for proper operation of the fireextinguishing system shall be provided as required by the design and installation standard utilized for the hazard. Alarms and warning signs. Where alarms are required to indicate the operation of automatic fire-extinguishing systems, distinctive audible, visible alarms and warning signs shall be provided to warn of pending agent discharge. Where exposure to automatic-extinguishing agents poses a hazard to persons and a delay is required to ensure the evacuation of occupants before agent discharge, a separate warning signal shall be provided to alert occupants once agent discharge has begun. Audible signals shall be in accordance with Section 7.7.10.2. Monitoring. Where a building fire alarm system is installed, automatic fireextinguishing systems shall be monitored by the building fire alarm system in accordance with NFPA 72. Inspection and testing. Automatic fire-extinguishing systems shall be inspected and tested in accordance with the provisions of this section prior to acceptance. Inspection. Prior to conducting final acceptance tests, the following items shall be inspected: 1. Hazard specification for consistency with design hazard. 2. Type, location and spacing of automatic and manual-initiating devices. 3. Size, placement and position of nozzles or discharge orifices. 4. Location and identification of audible and visible alarm devices. 5. Identification of devices with proper designations. 6. Operating instructions. Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with 2007 7/17 FIRE PROTECTION SYSTEMS 7.4.4.2.1 7.4.4.3 7.4.5 7.4.5.1 7.4.5.2 7.4.6 7.4.6.1 7.4.6.2 7.4.7 7.4.7.1 7.4.8 7.4.8.1 7.4.8.2 7.4.8.3 SBC 801 this section and Section 7.7 to verify proper operation. Audible and visible signals. The audibility and visibility of notification appliances signaling agent discharge or system operation, where required, shall be verified. Monitor testing. Connections to protected premises and supervising station fire alarm systems shall be tested to verify proper identification and retransmission of alarms from automatic fire-extinguishing systems. Wet-chemical systems. Wet-chemical extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 17A and their listing. System test. Systems shall be inspected and tested for proper operation at 6 months intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. Extinguishing system units shall be weighed and the required amount of agent verified. Stored pressure-type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals indicated by the manufacturer. Fusible link maintenance. Fixed temperature-sensing elements shall be maintained to ensure proper operation of the system. Dry-chemical systems. Dry-chemical extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 17 and their listing. System test. Systems shall be inspected and tested for proper operation at 6 months intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. Extinguishing system units shall be weighed, and the required amount of agent verified. Stored pressure-type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals indicated by the manufacturer. Fusible link maintenance. Fixed temperature-sensing elements shall be maintained to ensure proper operation of the system. Foam systems. Foam-extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 11, NFPA 11A and NFPA 16 and their listing. System test. Foam-extinguishing systems shall be inspected and tested at intervals in accordance with NFPA 25. Carbon dioxide systems. Carbon dioxide extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 12 and their listing. System test. Systems shall be inspected and tested for proper operation at 12 months intervals. High-pressure cylinders. High-pressure cylinders shall be weighed and the date of the last hydrostatic test shall be verified at 6 months intervals. Where a container shows a loss in original content of more than 10 percent, the cylinder shall be refilled or replaced. Low-pressure containers. The liquid-level gauges of low-pressure containers shall be observed at one-week intervals. Where a container shows a content loss of more than 10 percent, the container shall be refilled to maintain the minimum gas 2007 7/18 FIRE PROTECTION SYSTEMS 7.4.8.4 7.4.8.4.1 7.4.8.5 7.4.9 7.4.9.1 7.4.9.2 7.4.9.3 7.4.9.3.1 7.4.9.4 7.4.10 7.4.10.1 7.4.10.2 7.4.10.3 7.4.11 SBC 801 requirements. System hoses. System hoses shall be examined at 12 months intervals for damage. Damaged hoses shall be replaced or tested. At five-year intervals, all hoses shall be tested. Test procedure. Hoses shall be tested at not less than 17,238 kPa for highpressure systems and at not less than 6,206 kPa for low-pressure systems. Auxiliary equipment. Auxiliary and supplementary components, such as switches, door and window releases, interconnected valves, damper releases and supplementary alarms, shall be manually operated at 12 months intervals to ensure that such components are in proper operating condition. Halon systems. Halogenated extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 12A and their listing. System test. Systems shall be inspected and tested for proper operation at 12 months intervals. Containers. The extinguishing agent quantity and pressure of containers shall be checked at 6 months intervals. Where a container shows a loss in original weight of more than 5 percent or a loss in original pressure (adjusted for temperature) of more than 10 percent, the container shall be refilled or replaced. The weight and pressure of the container shall be recorded on a tag attached to the container. System hoses. System hoses shall be examined at 12 months intervals for damage. Damaged hoses shall be replaced or tested. At 5 years intervals, all hoses shall be tested. Test procedure. For Halon 1301 systems, hoses shall be tested at not less than 10,343 kPa for 4,137 kPa charging pressure systems and not less than 6,206 kPa for 2,482 kPa charging pressure systems. For Halon 1211 hand-hose line systems, hoses shall be tested at 17,238 kPa for high-pressure systems and 6,206 kPa for low-pressure systems. Auxiliary equipment. Auxiliary and supplementary components, such as switches, door and window releases, interconnected valves, damper releases and supplementary alarms, shall be manually operated at 12 months intervals to ensure such components are in proper operating condition. Clean-agent systems. Clean-agent fire-extinguishing systems shall be installed, maintained, periodically inspected and tested in accordance with NFPA 2001 and their listing. System test. Systems shall be inspected and tested for proper operation at 12 months intervals. Containers. The extinguishing agent quantity and pressure of the containers shall be checked at 6 months intervals. Where a container shows a loss in original weight of more than 5 percent or a loss in original pressure, adjusted for temperature, of more than 10 percent, the container shall be refilled or replaced. The weight and pressure of the container shall be recorded on a tag attached to the container. System hoses. System hoses shall be examined at 12 months intervals for damage. Damaged hoses shall be replaced or tested. All hoses shall be tested at 5-year intervals. Commercial cooking systems. The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment and exhaust systems of the type and arrangement protected. Preengineered automatic dry and wet-chemical extinguishing systems 2007 7/19 FIRE PROTECTION SYSTEMS 7.4.11.1 7.4.11.2 7.4.11.3 7.4.11.3.1 7.4.11.4 7.4.11.4.1 7.4.11.5 7.4.11.6 7.4.11.6.1 SBC 801 shall be tested in accordance with UL 300 and listed and labeled for the intended application. Other types of automatic fire-extinguishing systems shall be listed and labeled for specific use as protection for commercial cooking operations. The system shall be installed in accordance with these code requirements, its listing and the manufacturer’s installation instructions. Automatic fire-extinguishing systems of the following types shall be installed in accordance with the referenced standard indicated, as follows: 1. Carbon dioxide extinguishing systems, NFPA 12. 2. Automatic sprinkler systems, NFPA 13. 3. Foam-water sprinkler system or foam-water spray systems, NFPA 16. 4. Dry-chemical extinguishing systems, NFPA 17. 5. Wet-chemical extinguishing systems, NFPA 17A. Exception: Factory-built commercial cooking recirculating systems that are tested in accordance with UL 197 and listed, labeled and installed in accordance with SBC 501. Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area, a minimum of 3 m and a maximum of 6.1 m from the kitchen exhaust system. The manual actuation device shall be located a minimum of 1.2 m and a maximum of 1.5 m above the floor. The manual actuation shall require a maximum force of 178 N and a maximum movement of 350 mm to actuate the fire suppression system. Exception: Automatic sprinkler systems shall not be required to be equipped with manual actuation means. System interconnection. The actuation of the fire suppression system shall automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual. Carbon dioxide systems. When carbon dioxide systems are used, there shall be a nozzle at the top of the ventilating duct. Additional nozzles that are symmetrically arranged to give uniform distribution shall be installed within vertical ducts exceeding 6.1 m and horizontal ducts exceeding 15.2 m. Dampers shall be installed at either the top or the bottom of the duct and shall be arranged to operate automatically upon activation of the fire-extinguishing system. When the damper is installed at the top of the duct, the top nozzle shall be immediately below the damper. Automatic carbon dioxide fire-extinguishing systems shall be sufficiently sized to protect all hazards venting through a common duct simultaneously. Ventilation system. Commercial-type cooking equipment protected by an automatic carbon dioxide extinguishing system shall be arranged to shutoff the ventilation system upon activation. Special provisions for automatic sprinkler systems. Automatic sprinkler systems protecting commercial-type cooking equipment shall be supplied from a separate, readily accessible, indicating-type control valve that is identified. Listed sprinklers. Sprinklers used for the protection of fryers shall be listed for that application and installed in accordance with their listing. Commercial cooking equipment. Portable fire extinguishers shall be provided within a 9.1 m travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. Ventilation system. The ventilation system in connection with hoods shall be operated at the required rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used. 2007 7/20 FIRE PROTECTION SYSTEMS 7.4.11.6.2 7.4.11.6.3 7.4.11.6.4 7.4.11.6.5 Grease extractors. Where grease extractors are installed, they shall be operated when the commercial-type cooking equipment is used. Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the Building official upon completion. Fusible link and sprinkler head replacement. Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer’s instructions. Exception: Frangible bulbs are not required to be replaced annually. SECTION 7.5 STANDPIPE SYSTEMS 7.5.1 General. Standpipe systems shall be provided in new buildings and structures in accordance with this section. Fire hose threads used in connection with standpipe systems shall be approved and shall be compatible with Civil Defence hose threads. The location of Civil Defence hose connections shall be approved. In buildings used for high-piled combustible storage, fire protection shall be in accordance with Chapter 21. 7.5.2 Installation standards. Standpipe systems shall be installed in accordance with this section and NFPA 14. 7.5.3 Required installations. Standpipe systems shall be installed where required by Sections 7.5.3.1 through 7.5.3.6 and in the locations indicated in Sections 7.5.4, 7.5.5 and 7.5.6. Standpipe systems are permitted to be combined with automatic sprinkler systems. Exception: Standpipe systems are not required in Group R-3 occupancies. Building height. Class III standpipe systems shall be installed throughout buildings where the floor level of the highest story is located more than 9.1 m above the lowest level of the Civil Defence vehicle access, or where the floor level of the lowest story is located more than 9.1 m below the highest level of Civil Defence vehicle access. Exceptions: 1. Class I standpipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. 2. Class I manual standpipes are allowed in open parking garages where the highest floor is located not more than 45.7 m above the lowest level of Civil Defence vehicle access. 3. Class I manual dry standpipes are allowed in open parking garages that are subject to freezing temperatures, provided that the hose connections are located as required for Class II standpipes in accordance with Section 7.5.5. 4. Class I standpipes are allowed in basements equipped throughout with an automatic sprinkler system. Group A. Class I automatic wet standpipes shall be provided in nonsprinklered Group A buildings having an occupant load exceeding 1,000 persons. 7.5.3.1 7.5.3.2 SBC 801 2007 7/21 FIRE PROTECTION SYSTEMS 7.5.3.3 7.5.3.4 7.5.3.4.1 7.5.3.5 7.5.3.6 7.5.4 SBC 801 Exceptions: 1. Open-air-seating spaces without enclosed spaces. 2. Class I automatic dry and semiautomatic dry standpipes or manual wet standpipes are allowed in buildings where the highest floor surface used for human occupancy is 22.9 m or less above the lowest level of Civil Defence vehicle access. Covered mall buildings. A covered mall building shall be equipped throughout with a standpipe system where required by Section 7.5.3. Covered mall buildings not required to be equipped with a standpipe system by Section 7.5.3 shall be equipped with Class I hose connections connected to a system sized to deliver 946.3 L/min at the most hydraulically remote outlet. Hose connections shall be provided at each of the following locations: 1. Within the mall at the entrance to each exit passageway or corridor. 2. At each floor-level landing within enclosed stairways opening directly on the mall. 3. At exterior public entrances to the mall. Stages. Stages greater than 93 m2 shall be equipped with a Class III wet standpipe system with 40 mm and 65 mm hose connections on each side of the stage. Exception: Where the building or area is equipped throughout with an automatic sprinkler system, the hose connections are allowed to be supplied from the automatic sprinkler system and shall have a flow rate of not less than that required by NFPA 14 for Class III standpipes. Hose and cabinet. The 40 mm hose connections shall be equipped with sufficient lengths of 40 mm hose to provide fire protection for the stage area. Hose connections shall be equipped with an approved adjustable fog nozzle and be mounted in a cabinet or on a rack. Underground buildings. Underground buildings shall be equipped throughout with a Class I automatic wet or manual wet standpipe system. Helistops and heliports. Buildings with a helistop or heliport that are equipped with a standpipe shall extend the standpipe to the roof level on which the helistop or heliport is located in accordance with Section 11.7.5. Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: 1. In every required stairway, a hose connection shall be provided for each floor level above or below grade. Hose connections shall be located at an intermediate floor level landing between floors, unless otherwise approved by the Building official. 2. On each side of the wall adjacent to the exit opening of a horizontal exit. 3. In every exit passageway at the entrance from the exit passageway to other areas of a building. 4. In covered mall buildings, adjacent to each exterior public entrance to the mall and adjacent to each entrance from an exit passageway or exit corridor to the mall. 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3 percent slope), each standpipe shall be provided with a hose connection located either on the roof or at the highest landing of stairways with stair access to the roof. An additional hose connection shall be provided at the top of the most hydraulically remote standpipe for testing purposes. 6. Where the most remote portion of a nonsprinklered floor or story is more than 45.7 m from a hose connection or the most remote portion of a sprinklered floor or story is more than 61 m from a hose connection, the Building official 2007 7/22 FIRE PROTECTION SYSTEMS 7.5.4.1 7.5.4.2 7.5.5 7.5.5.1 7.5.5.2 7.5.5.3 7.5.6 7.5.6.1 7.5.6.2 7.5.7 7.5.7.1 7.5.7.2 SBC 801 is authorized to require that additional hose connections be provided in approved locations. Protection. Risers and laterals of Class I standpipe systems not located within an enclosed stairway or pressurized enclosure shall be protected by a degree of fire resistance equal to that required for vertical enclosures in the building in which they are located. Exception: In buildings equipped throughout with an approved automatic sprinkler system, laterals that are not located within an enclosed stairway or pressurized enclosure are not required to be enclosed within fire-resistance-rated construction. Interconnection. In buildings where more than one standpipe is provided, the standpipes shall be interconnected in accordance with NFPA 14. Location of Class II standpipe hose connections. Class II standpipe hose connections shall be accessible and shall be located so that all portions of the building are within 9.1 m of a nozzle attached to 30.5 m of hose. Groups A-1 and A-2. In Group A-1 and A-2 occupancies with occupant loads of more than 1,000, hose connections shall be located on each side of any stage, on each side of the rear of the auditorium, on each side of the balcony, and on each tier of dressing rooms. Protection. Fire-resistance-rated protection of risers and laterals of Class II standpipe systems is not required. Class II system 25 mm hose. A minimum 25 mm hose shall be allowed to be used for hose stations in light-hazard occupancies where investigated and listed for this service and where approved by the Building official. Location of Class III standpipe hose connections. Class III standpipe systems shall have hose connections located as required for Class I standpipes in Section 7.5.4 and shall have Class II hose connections as required in Section 7.5.5. Protection. Risers and laterals of Class III standpipe systems shall be protected as required for Class I systems in accordance with Section 7.5.4.1. Interconnection. In buildings where more than one Class III standpipe is provided, the standpipes shall be interconnected at the bottom. Cabinets. Cabinets containing fire-fighting equipment, such as standpipes, fire hose, fire extinguishers or Civil Defence valves, shall not be blocked from use or obscured from view. Cabinet equipment identification. Cabinets shall be identified in an approved manner by a permanently attached sign with letters not less than 51 mm high in a color that contrasts with the background color, indicating the equipment contained therein. Exceptions: 1. Doors not large enough to accommodate a written sign shall be marked with a permanently attached pictogram of the equipment contained therein. 2. Doors that have either an approved visual identification clear glass panel or a complete glass door panel are not required to be marked. Locking cabinet doors. Cabinets shall be unlocked. Exceptions: 1. Visual identification panels of glass or other approved transparent frangible material that is easily broken and allows access. 2. Approved locking arrangements. 3. Use Group I-3. 2007 7/23 FIRE PROTECTION SYSTEMS 7.5.8 Dry standpipes. Dry standpipes shall not be installed. Exception: Where subject to freezing and in accordance with NFPA 14. 7.5.9 Valve supervision. Valves controlling water supplies shall be supervised in the open position so that a change in the normal position of the valve will generate a supervisory signal at the supervising station required by Section 7.3.4. Where a fire alarm system is provided, a signal shall also be transmitted to the control unit. Exceptions: 1. Valves to underground key or hub valves in roadway boxes provided by the municipality or public utility do not require supervision. 2. Valves locked in the normal position and inspected as provided in these code requirements in buildings not equipped with a fire alarm system. 7.5.10 During construction. Standpipe systems required during construction and demolition operations shall be provided in accordance with Section 10.13. 7.5.11 Existing buildings. Existing structures with occupied floors located more than 15.2 m above or below the lowest level of Civil Defence access shall be equipped with standpipes installed in accordance with Section 7.5. The standpipes shall have an approved Civil Defence connection with hose connections at each floor level above or below the lowest level of Civil Defence access. The Building official is authorized to approve the installation of manual standpipe systems to achieve compliance with this section where the responding Civil Defence is capable of providing the required hose flow at the highest standpipe outlet. SECTION 7.6 PORTABLE FIRE EXTINGUISHERS 7.6.1 Where required. Portable fire extinguishers shall be installed in the following locations. 1. In all Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In all Group A, B and E occupancies equipped throughout with quick-response sprinklers, fire extinguishers shall be required only in specialhazard areas. 2. Within 9.1 m of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 10.15.1. 5. Where required by the sections indicated in Table 7.6.1. 6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the Building official. 7.6.2 General requirements. Fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Exception: The travel distance to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies. 7.6.3 Size and distribution. For occupancies that involve primarily Class A fire hazards, the minimum sizes and distribution shall comply with Table 7.6.3(1). Fire extinguishers for occupancies involving flammable or combustible liquids with depths of less than or equal 6.35 mm shall be selected and placed in accordance SBC 801 2007 7/24 FIRE PROTECTION SYSTEMS with Table 7.6.3(2). Fire extinguishers for occupancies involving flammable or combustible liquids with a depth of greater than 6.35 mm or involving combustible metals shall be selected and placed in accordance with NFPA 10. Extinguishers for Class C fire hazards shall be selected and placed on the basis of the anticipated Class A or Class B hazard. 7.6.4 Cooking grease fires. Fire extinguishers provided for the protection of cooking grease fires shall be of an approved type compatible with the automatic fireextinguishing system agent and in accordance with Section 7.4.11.5. 7.6.5 Conspicuous location. Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the Building official determines that the hazard posed indicates the need for placement away from normal paths of travel. 7.6.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. 7.6.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. 7.6.8 Cabinets. Cabinets used to house fire extinguishers shall not be locked. Exceptions: 1. Where fire extinguishers subject to malicious use or damage are provided with a means of ready access. 2. In Group I-3 occupancies and in mental health areas in Group I-2 occupancies, access to portable fire extinguishers shall be permitted to be locked or to be located in staff locations provided the staff has keys. TABLE 7.6.1 ADDITIONAL REQUIRED PORTABLE FIRE EXTINGUISHERS SECTION SBC 801 SUBJECT 2.3 (SBC 201) Asphalt kettles 2.7 (SBC 201) Open burning 2.8 (SBC 201) Open flames 2.9 (SBC 201) Powered industrial trucks 11.5.2 Aircraft towing vehicles 11.5.3 Aircraft welding apparatus 11.5.4 Aircraft fuel-servicing tank vehicles 11.5.5 Aircraft hydrant fuel-servicing vehicles 11.5.6 Aircraft fuel-dispensing stations 11.7.7 Heliports and helistops 13.8.4 Dry cleaning plants 10.15.1 Buildings under construction or demolition (Continued) 2007 7/25 FIRE PROTECTION SYSTEMS TABLE 7.6.1 (Continued) ADDITIONAL REQUIRED PORTABLE FIRE EXTINGUISHERS SECTION SUBJECT 10.17.3 Roofing operations 12.4.6.4 Spray-finishing operations 12.5.5 Dip-tank operations 17.4.2 Lumberyards/woodworking facilities 17.8.8 Recycling facilities 17.9.5 Exterior lumber storage 18.3.5 Organic-coating areas 19.6.3 Industrial ovens 20.5.5 Motor fuel-dispensing facilities 20.10.6.4 Marine motor fuel-dispensing facilities 20.11.6 Repair garages 21.6.1 Rack storage 22.4.12 Tents, canopies and membrane structures 23.8.2 Tire rebuilding/storage 24.4.2.6 Welding and other hot work 27.3.6 Combustible fibers 31.8.11 Fireworks 32.3.2.1 Flammable and combustible liquids, general 32.4.3.3.1 32.4.3.7.5.2 Liquid storage rooms for flammable and combustible liquids Indoor storage of flammable and combustible liquids 32.5.4.9 32.6.2.7 Solvent distillation units 32.6.4.10.1 Bulk plants and terminals for flammable and combustible liquids Commercial, industrial, governmental or manufacturing establishments— fuel dispensing 32.6.5.4.5 Farms and construction sites—flammable and combustible liquids storage 32.6.6.4 Tank vehicles for flammable and combustible liquids 34.6.5.7 Flammable solids 36.8.2 LP-gas TABLE 7.6.3(1) FIRE EXTINGUISHERS FOR CLASS A FIRE HAZARDS ORDINARY (Moderate) LIGHT (Low) EXTRA (High) HAZARD HAZARD HAZARD OCCUPANCY OCCUPANCY OCCUPANCY Minimum Rated Single Extinguisher Maximum Floor Area Per Unit of A 2-Ac 2-A 4-Aa 278.7 m2 139.4 m2 93 m2 Maximum Floor Area For Extinguisherb 1,045 m2 1,045 m2 1,045 m2 22.9 m 22.9 m 22.9 m Maximum Travel Distance to Extinguisher a. Two 9.5 litre water-type extinguishers shall be deemed the equivalent of one 4-A rated extinguisher. b. NFPA 10 Appendix E-3-3 provides more details concerning application of the maximum floor area criteria. c. Two water-type extinguishers each with a 1-A rating shall be deemed the equivalent of one 2-A rated extinguisher for Light (Low) Hazard Occupancies. SBC 801 2007 7/26 FIRE PROTECTION SYSTEMS TABLE 7.6.3(2) FLAMMABLE OR COMBUSTIBLE LIQUIDS WITH DEPTHS OF LESS THAN OR EQUAL TO 6.4 MM MAXIMUM TRAVEL DISTANCE TO BASIC MINIMUM EXTINGUISHER EXTINGUISHERS TYPE OF HAZARD RATING (meters) 5-B 9.1 Light (Low) 10-B 15.2 10-B 9.1 Ordinary (Moderate) 20-B 15.2 40-B 9.1 Extra (High) 80-B 15.2 NOTE. For requirements on water-soluble flammable liquids and alternative sizing criteria, see NFPA 10, Sections 3-3 and 3-4. 7.6.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 18 kg shall be installed so that its top is not more than 1.5 m above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 18 kg shall be installed so that its top is not more than 1.1 m above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 102 mm. 7.6.10 Wheeled units. Wheeled fire extinguishers shall be conspicuously located in a designated location. SECTION 7.7 FIRE ALARM AND DETECTION SYSTEMS 7.7.1 7.7.1.1 7.7.1.2 7.7.2 SBC 801 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing buildings and structures. The requirements of Section 7.7.2 are applicable to new buildings and structures. The requirements of Section 7.7.3 are applicable to existing buildings and structures. Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Equipment. Systems and their components shall be listed and approved for the purpose for which they are installed. Where required – new buildings and structures. An approved manual, automatic, or manual and automatic fire alarm system shall be provided in new 2007 7/27 FIRE PROTECTION SYSTEMS 7.7.2.1 7.7.2.1.1 7.7.2.1.2 7.7.2.2 7.7.2.3 SBC 801 buildings and structures in accordance with Sections 7.7.2.1 through 7.7.2.23. Where automatic sprinkler protection installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2 is provided and connected to the building fire alarm system, automatic heat detection required by this section shall not be required. An approved automatic fire detection system shall be installed in accordance with the provisions of these code requirements and NFPA 72. Devices, combinations of devices, appliances and equipment shall comply with Section 7.7.1.2. The automatic fire detectors shall be smoke detectors, except that an approved alternative type of detector shall be installed in spaces such as boiler rooms where, during normal operation, products of combustion are present in sufficient quantity to actuate a smoke detector. Group A. A manual fire alarm system shall be installed in accordance with NFPA 72 in Group A occupancies having an occupant load of 300 or more. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy. Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler water flow. System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal using an emergency voice/alarm communications system in accordance with NFPA 72. Exception: Where approved, the prerecorded announcement is allowed to be manually deactivated for a period of time, not to exceed 3 minutes, for the sole purpose of allowing a live voice announcement from an approved, constantly attended location. Emergency power. Emergency voice/alarm communications systems shall be provided with an approved emergency power source. Group B. A manual fire alarm system shall be installed in Group B occupancies having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler water flow. Group E. A manual fire alarm system shall be installed in Group E occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. Exceptions: 1. Group E occupancies with an occupant load of less than 50. 2. Manual fire alarm boxes are not required in Group E occupancies where all the following apply: 2.1 Interior corridors are protected by smoke detectors with alarm verification. 2.2 Auditoriums, cafeterias, gymnasiums and the like are protected by heat detectors or other approved detection devices. 2.3 Shops and laboratories involving dusts or vapors are protected by heat detectors or other approved detection devices. 2.4 Off-premises monitoring is provided. 2.5 The capability to activate the evacuation signal from a central point is provided. 2.6 In buildings where normally occupied spaces are provided with a twoway communication system between such spaces and a constantly 2007 7/28 FIRE PROTECTION SYSTEMS attended receiving station from where a general evacuation alarm can be sounded, except in locations specifically designated by the Building official. 7.7.2.4 Group F. A manual fire alarm system shall be installed in Group F occupancies that are two or more stories in height and have an occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler water flow. 7.7.2.5 Group H. A manual fire alarm system shall be installed in Group H-5 occupancies and in occupancies used for the manufacture of organic coatings. An automatic smoke detection system shall be installed for highly toxic gases, organic peroxides and oxidizers in accordance with Chapters 35, 37 and 38, respectively. 7.7.2.6 Group I. A manual fire alarm system and an automatic fire detection system shall be installed in Group I occupancies. An electrically supervised, automatic smoke detection system shall be provided in waiting areas that are open to corridors. Exception: Manual fire alarm boxes in patient sleeping areas of Group I-1 and I-2 occupancies shall not be required at exits if located at all nurses’ control stations or other constantly attended staff locations, provided such stations are visible and continuously accessible and that travel distances required in Section 7.7.4.1 are not exceeded. 7.7.2.6.1 Group I-2. Corridors in nursing homes (both intermediate care and skilled nursing facilities), detoxification facilities and spaces open to the corridors shall be equipped with an automatic fire detection system. Exceptions: 1. Corridor smoke detection is not required in smoke compartments that contain patient sleeping rooms where patient sleeping units are provided with smoke detectors that comply with UL 268. Such detectors shall provide a visual display on the corridor side of each patient sleeping unit and shall provide an audible and visual alarm at the nursing station attending each unit. 2. Corridor smoke detection is not required in smoke compartments that contain patient sleeping rooms where patient sleeping unit doors are equipped with automatic door-closing devices with integral smoke detectors on the unit sides installed in accordance with their listing, provided that the integral detectors perform the required alerting function. 7.7.2.6.2 Group I-3 occupancies. Group I-3 occupancies shall be equipped with a manual and automatic fire alarm system installed for alerting staff. 7.7.2.6.2.1 System initiation. Actuation of an automatic fire-extinguishing system, a manual fire alarm box or a fire detector shall initiate an approved fire alarm signal which automatically notifies staff. Presignal systems shall not be used. 7.7.2.6.2.2 Manual fire alarm boxes. Manual fire alarm boxes are not required to be located in accordance with Section 7.7.4 where the fire alarm boxes are provided at staffattended locations having direct supervision over areas where manual fire alarm boxes have been omitted. Manual fire alarm boxes are allowed to be locked in areas occupied by detainees, provided that staff members are present within the subject area and have keys readily available to operate the manual fire alarm boxes. 7.7.2.6.2.3 Smoke detectors. An approved automatic smoke detection system shall be installed throughout resident housing areas, including sleeping areas and contiguous day rooms, group activity spaces and other common spaces normally accessible to residents. SBC 801 2007 7/29 FIRE PROTECTION SYSTEMS 7.7.2.7 7.7.2.7.1 7.7.2.8 7.7.2.8.1 7.7.2.8.2 7.7.2.8.3 SBC 801 Exceptions: 1. Other approved smoke-detection arrangements providing equivalent protection, including, but not limited to, placing detectors in exhaust ducts from cells or behind protective guards listed for the purpose, are allowed when necessary to prevent damage or tampering. 2. Sleeping units in Use Conditions 2 and 3. 3. Smoke detectors are not required in sleeping units with four or fewer occupants in smoke compartments that are equipped throughout with an approved automatic sprinkler system. Group M. A manual fire alarm system shall be installed in Group M occupancies, other than covered mall buildings complying with Section 2.15 of the SBC 201, having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system and the alarm notification appliances will activate upon sprinkler water flow. Occupant notification. During times that the building is occupied, in lieu of the automatic activation of alarm notification appliances, the manual fire alarm system shall be allowed to activate an alarm signal at a constantly attended location from which evacuation instructions shall be initiated over an emergency voice/alarm communication system installed in accordance with Section 7.7.2.12.2. The emergency voice/alarm communication system shall be allowed to be used for other announcements provided the manual fire alarm use takes precedence over any other use. Group R-1. Fire alarm systems shall be installed in Group R-1 occupancies as required in Sections 7.7.2.8.1 through 7.7.2.8.3. Manual fire alarm system. A manual fire alarm system shall be installed in Group R-1 occupancies. Exceptions: 1. A manual fire alarm system is not required in buildings not more than two stories in height where all individual guestrooms and contiguous attic and crawl spaces are separated from each other and public or common areas by at least 1 hour fire partitions and each individual guestroom has an exit directly to a public way, exit court or yard. 2. Manual fire alarm boxes are not required throughout the building when the following conditions are met: 2.1 The building is equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2; 2.2 The notification appliances will activate upon sprinkler water flow; and 2.3 At least one manual fire alarm box is installed at an approved location. Automatic fire alarm system. An automatic fire alarm system shall be installed throughout all interior corridors serving guestrooms. Exception: An automatic fire detection system is not required in buildings that do not have interior corridors serving guestrooms and each guestroom has a means of egress door opening directly to an exterior exit access that leads directly to an exit. Smoke alarms. Smoke alarms shall be installed as required by Section 7.7.2.10. In buildings that are not equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2, the smoke alarms in guestrooms shall be connected to an emergency electrical system and shall be annunciated by guestroom at a constantly attended location from which the fire alarm system is capable of being manually activated. 2007 7/30 FIRE PROTECTION SYSTEMS Group R-2. A manual fire alarm system shall be installed in Group R-2 occupancies where: 1. Any dwelling unit or sleeping unit is located three or more stories above the lowest level of exit discharge; 2. Any dwelling unit or sleeping unit is located more than one story below the highest level of exit discharge of exits serving the dwelling unit or sleeping unit; or 3. The building contains more than 16 dwelling units or sleeping units. Exceptions: 1. A fire alarm system is not required in buildings not more than two stories in height where all dwelling units or sleeping units and contiguous attic and crawl spaces are separated from each other and public or common areas by at least 1 hour fire partitions and each dwelling unit or sleeping unit has an exit directly to a public way, exit court or yard. 2. Manual fire alarm boxes are not required throughout the building when the following conditions are met: 2.1 The building is equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1 or Section 7.3.3.1.2; 2.2 The notification appliances will activate upon sprinkler flow; and 2.3 At least one manual fire alarm box is installed at an approved location. 3. A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2, provided that dwelling units either have a means of egress door opening directly to an exterior exit access that leads directly to the exits or are served by open-ended corridors designed in accordance with Section 8.22.6, Exception 4. 7.7.2.10 Single and multiple-station smoke alarms. Listed single and multiple-station smoke alarms shall be installed in accordance with the provisions of these code requirements and the household fire-warning equipment provisions of NFPA 72. 7.7.2.10.1 Where required. Single or multiple-station smoke alarms shall be installed in the locations described in Sections 7.7.2.10.1 through 7.7.2.10.1.4. 7.7.2.10.1.1 Group R-1. Single or multiple-station smoke alarms shall be installed in all of the following locations in Group R-1: 1. In sleeping areas. 2. In every room in the path of the means of egress from the sleeping area to the door leading from the sleeping unit. 3. In each story within the sleeping unit, including basements. For sleeping units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. 7.7.2.10.1.2 Groups R-2, R-3, R-4 and I-1. Single or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and I-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided 7.7.2.9 SBC 801 2007 7/31 FIRE PROTECTION SYSTEMS that the lower level is less than one full story below the upper level. 7.7.2.10.1.3 Group I-1. Single or multiple-station smoke alarms shall be installed and 7.7.2.10.2 7.7.2.10.3 7.7.2.10.4 7.7.2.11 7.7.2.11.1 7.7.2.11.2 7.7.2.11.3 SBC 801 maintained in sleeping areas in occupancies in Group I-1. Single or multiplestation smoke alarms shall not be required where the building is equipped throughout with an automatic fire detection system in accordance with Section 7.7.2.6. Power source. In new construction, required smoke alarms shall receive their primary power from the building wiring where such wiring is served from a commercial source and shall be equipped with a battery backup. Smoke alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for overcurrent protection. Exception: Smoke alarms are not required to be equipped with battery backup in Group R-1 where they are connected to an emergency electrical system. Interconnection. Where more than one smoke alarm is required to be installed within an individual dwelling unit or sleeping unit in Group R-2, R-3 or R-4, or within an individual sleeping unit in Group R-1, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. Acceptance testing. When the installation of the alarm devices is complete, each detector and inter-connecting wiring for multiple-station alarm devices shall be tested in accordance with the household fire warning equipment provisions of NFPA 72. Special amusement buildings. An approved automatic smoke detection system shall be provided in special amusement buildings in accordance with this section. Exception: In areas where ambient conditions will cause a smoke detection system to alarm, an approved alternative type of automatic detector shall be installed. Alarm. Activation of any single smoke detector, the automatic sprinkler system or any other automatic fire detection device shall immediately sound an alarm at the building at a constantly attended location from which emergency action can be initiated, including the capability of manual initiation of requirements in Section 7.7.2.11.2. System response. The activation of two or more smoke detectors, a single smoke detector with alarm verification, the automatic sprinkler system or other approved fire detection device shall automatically: 1. Cause illumination of the means of egress with light of not less than 1 footcandle (11 lux) at the walking surface level; 2. Stop any conflicting or confusing sounds and visual distractions; and 3. Activate an approved directional exit marking that will become apparent in an emergency. Such system response shall also include activation of a prerecorded message, clearly audible throughout the special amusement building, instructing patrons to proceed to the nearest exit. Alarm signals used in conjunction with the prerecorded message shall produce a sound which is distinctive from other sounds used during normal operation. The wiring to the auxiliary devices and equipment used to accomplish the above fire safety functions shall be monitored for integrity in accordance with NFPA 72. Emergency voice/alarm communication system. An emergency voice/alarm communication system, which is also allowed to serve as a public address system, shall be installed in accordance with NFPA 72 and be audible throughout the entire special amusement building. 2007 7/32 FIRE PROTECTION SYSTEMS High-rise buildings. Buildings having floors used for human occupancy located more than 22.9 m above the lowest level of Civil Defence vehicle access shall be provided with an automatic fire alarm system and an emergency voice/alarm communication system in accordance with Section 7.7.2.12.2. Exceptions: 1. Airport traffic control towers in accordance with Section 7.7.2.22 and the SBC 201. 2. Open parking garages in accordance with Section 2.19 of the SBC 201. 3. Buildings with an occupancy in Group A-5 in accordance with Section 2.3 of the SBC 201. 4. Low-hazard special occupancies in accordance with Section 3.3 of the SBC 201. 5. Buildings with an occupancy in Group H-1, H-2 or H-3 in accordance with Section 2.28 of the SBC 201. 7.7.2.12.1 Automatic fire detection. Smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector required by this section shall operate the emergency voice/alarm communication system. Smoke detectors shall be located as follows: 1. In each mechanical equipment, electrical, transformer, telephone equipment or similar room which is not provided with sprinkler protection, elevator machine rooms, and in elevator lobbies. 2. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 0.94 m3/s. Such detectors shall be located in a serviceable area downstream of the last duct inlet. 3. At each connection to a vertical duct or riser serving two or more stories from a return air duct or plenum of an air-conditioning system. In Group R-1 and R2 occupancies, a listed smoke detector is allowed to be used in each return-air riser carrying not more than 2.4 m3/s and serving not more than 10 air-inlet openings. 7.7.2.12.2 Emergency voice/alarm communication system. The operation of any automatic fire detector, sprinkler water-flow device or manual fire alarm box shall automatically sound an alert tone followed by voice instructions giving approved information and directions on a general or selective basis to the following terminal areas on a minimum of the alarming floor, the floor above, and the floor below in accordance with the building’s fire safety and evacuation plans required by Section 5.4. 1. Elevator lobbies. 2. Corridors. 3. Rooms and tenant spaces exceeding 93 m2 in area. 4. Dwelling units and sleeping units in Group R-2 occupancies. 5. Sleeping units in Group R-1 occupancies. 6. Areas of refuge as defined in Section 8.2. Exception: In Group I-1 and I-2 occupancies, the alarm shall sound in a constantly attended area and a general occupant notification shall be broadcast over the overhead page. 7.7.2.12.2.1 Manual override. A manual override for emergency voice communication shall be provided for all paging zones. 7.7.2.12.2.2 Live voice messages. The emergency voice/alarm communication system shall also have the capability to broadcast live voice messages through speakers located in elevators, exit stairways, and throughout a selected floor or floors. 7.7.2.12.2.3 Standard. The emergency voice/alarm communication system shall be designed and installed in accordance with NFPA 72. 7.7.2.12 SBC 801 2007 7/33 FIRE PROTECTION SYSTEMS 7.7.2.12.3 7.7.2.13 7.7.2.14 7.7.2.15 7.7.2.16 7.7.2.17 7.7.2.18 7.7.2.18.1 7.7.2.18.2 7.7.2.19 7.7.2.19.1 7.7.2.20 SBC 801 Civil Defence communication system. An approved two-way, Civil Defence communication system designed and installed in accordance with NFPA 72 shall be provided for Civil Defence use. It shall operate between a fire command center complying with Section 3.9 and elevators, elevator lobbies, emergency and standby power rooms, fire pump rooms, areas of refuge and inside enclosed exit stairways. The Civil Defence communication device shall be provided at each floor level within the enclosed exit stairway. Exception: Civil Defence radio systems where approved by the Civil Defence. Atriums connecting more than two stories. A fire alarm system shall be installed in occupancies with an atrium that connects more than two stories. The system shall be activated in accordance with Section 7.7.7. Such occupancies in Group A, E or M shall be provided with an emergency voice/alarm communication system complying with the requirements of Section 7.7.2.12.2. High-piled combustible storage areas. An automatic fire detection system shall be installed throughout high-piled combustible storage areas where required by Section 21.6.5. Delayed egress locks. Where delayed egress locks are installed on means of egress doors in accordance with Section 8.8.1.8.6, an automatic smoke or heat detection system shall be installed as required by that section. Aerosol storage uses. Aerosol storage rooms and general-purpose warehouses containing aerosols shall be provided with an approved manual fire alarm system where required by these code requirements. Lumber, plywood and veneer mills. Lumber, plywood and veneer mills shall be provided with a manual fire alarm system. Underground buildings with smoke exhaust systems. Where a smoke exhaust system is installed in an underground building in accordance with the SBC 201, automatic fire detectors shall be provided in accordance with this section. Smoke detectors. A minimum of one smoke detector listed for the intended purpose shall be installed in the following areas: 1. Mechanical equipment, electrical, transformer, telephone equipment, elevator machine or similar rooms. 2. Elevator lobbies. 3. The main return and exhaust air plenum of each air-conditioning system serving more than one story and located in a serviceable area downstream of the last duct inlet. 4. Each connection to a vertical duct or riser serving two or more floors from return air ducts or plenums of heating, ventilating and air-conditioning systems, except that in Group R occupancies, a listed smoke detector is allowed to be used in each return-air riser carrying not more than 2.4 m3/s and serving not more than 10 air inlet openings. Alarm required. Activation of the smoke exhaust system shall activate an audible alarm at a constantly attended location. Underground buildings. Where the lowest level of a structure is more than 18.3 m below the lowest level of exit discharge, the structure shall be equipped throughout with a manual fire alarm system, including an emergency voice/alarm communication system installed in accordance with Section 7.7.2.12.2. Public address system. Where a fire alarm system is not required by Section 7.7.2, a public address system shall be provided which shall be capable of transmitting voice communications to the highest level of exit discharge serving the underground portions of the structure and all levels below. 2 Covered mall buildings. Covered mall buildings exceeding 4,645 m in total floor area shall be provided with an emergency voice/alarm communication system. An 2007 7/34 FIRE PROTECTION SYSTEMS 7.7.2.21 7.7.2.22 7.7.2.23 7.7.3 7.7.3.1 7.7.3.1.1 7.7.3.1.2 7.7.3.1.3 7.7.3.1.4 7.7.3.1.5 SBC 801 emergency voice/alarm communication system serving a mall, required or otherwise, shall be accessible to the Civil Defence. The system shall be provided in accordance with Section 7.7.2.12.2. Residential aircraft hangars. A minimum of one listed smoke alarm shall be installed within a residential aircraft hangar as defined in the SBC 201 and shall be interconnected into the residential smoke alarm or other sounding device to provide an alarm which will be audible in all sleeping areas of the dwelling. Airport traffic control towers. An automatic fire detection system shall be provided in airport traffic control towers. Battery rooms. An approved automatic smoke detection system shall be installed in areas containing stationary lead-acid battery systems having a liquid capacity of more than 189 L. The detection system shall be supervised by an approved central, proprietary, or remote station service or a local alarm which will sound an audible signal at a constantly attended location. Where required—retroactive in existing buildings and structures. An approved manual, automatic or manual and automatic fire alarm system shall be installed in existing buildings and structures in accordance with Sections 7.7.3.1 through 7.7.3.1.8. Where automatic sprinkler protection is provided in accordance with Section 7.3.3.1.1 or 7.3.3.1.2 and connected to the building fire alarm system, automatic heat detection required by this section shall not be required. An approved automatic fire detection system shall be installed in accordance with the provisions of these code requirements and NFPA 72. Devices, combinations of devices, appliances and equipment shall be approved. The automatic fire detectors shall be smoke detectors, except an approved alternative type of detector shall be installed in spaces such as boiler rooms where, during normal operation, products of combustion are present in sufficient quantity to actuate a smoke detector. Occupancy requirements. A fire alarm system shall be installed in accordance with Sections 7.7.3.1.1 through 7.7.3.1.8. Exception: Occupancies with an existing, previously approved fire alarm system. Group E. A fire alarm system shall be installed in existing Group E occupancies in accordance with Section 7.7.2.3. Exceptions: 1. A building with a maximum area of 93 m2 that contains a single classroom and is located no closer than 15.2 m from another building. 2. Group E with an occupant load less than 50. Group I-1. A fire alarm system shall be installed in existing Group I-1 residential care/assisted living facilities. Exception: Where each sleeping room has a means of egress door opening directly to an exterior egress balcony that leads directly to the exits in accordance with Section 8.13.5, and the building is not more than three stories in height. Group I-2. A fire alarm system shall be installed in existing Group I-2 occupancies in accordance with Section 7.7.2.6. Group I-3. A fire alarm system shall be installed in existing Group I-3 occupancies in accordance with Section 7.7.2.6.1. Group R-1 hotels and motels. A fire alarm system shall be installed in existing Group R-1 hotels and motels more than three stories or with more than 20 guestrooms. Exception: Buildings less than two stories in height where all guestrooms, attics and crawl spaces are separated by 1 hour fire-resistance-rated construction and each guestroom has direct access to a public way, exit court or yard. 2007 7/35 FIRE PROTECTION SYSTEMS 7.7.3.1.6 7.7.3.1.7 7.7.3.1.8 7.7.3.2 7.7.3.2.1 7.7.3.2.2 SBC 801 Group R-1 boarding and rooming houses. A fire alarm system shall be installed in existing Group R-1 boarding and rooming houses. Exception: Buildings that have single-station smoke alarms meeting or exceeding the requirements of Section 7.7.2.10.1 and where the fire alarm system includes at least one manual fire alarm box per floor arranged to initiate the alarm. Group R-2. A fire alarm system shall be installed in existing Group R-2 occupancies more than three stories in height or with more than 16 dwelling units or sleeping units. Exceptions: 1. Where each living unit is separated from other contiguous living units by fire barriers having a fire-resistance rating of not less than 0.75 hour, and where each living unit has either its own independent exit or its own independent stairway or ramp discharging at grade. 2. A separate fire alarm system is not required in buildings that are equipped throughout with an approved supervised automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2 and having a local alarm to notify all occupants. 3. A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2, provided that dwelling units either have a means of egress door opening directly to an exterior exit access that leads directly to the exits or are served by open-ended corridors designed in accordance with Section 8.22.6, Exception 4. Group R-4. A fire alarm system shall be installed in existing Group R-4 residential care/assisted living facilities. Exceptions: 1. Where there are interconnected smoke alarms meeting the requirements of Section 7.7.2.10 and there is at least one manual fire alarm box per floor arranged to sound continuously the smoke alarms. 2. Other manually activated, continuously sounding alarms approved by the Building official. Single and multiple-station smoke alarms. Single and multiple-station smoke alarms shall be installed in existing Group R occupancies in accordance with Sections 7.7.3.2.1 through 7.7.3.2.3. General. Existing Group R occupancies not already provided with single-station smoke alarms shall be provided with approved single-station smoke alarms. Installation shall be in accordance with Section 7.7.2.10, except as provided in Sections 7.7.3.2.2 and 7.7.3.2.3. Interconnection. Where more than one smoke alarm is required to be installed within an individual dwelling unit in Group R-2, R-3 or R-4, or within an individual sleeping unit in Group R-1, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed. Exceptions: 1. Interconnection is not required in buildings that are not undergoing alterations, repairs or construction of any kind. 2. Smoke alarms in existing areas are not required to be interconnected where alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for interconnection without the 2007 7/36 FIRE PROTECTION SYSTEMS 7.7.3.2.3 7.7.4 7.7.4.1 7.7.4.2 7.7.4.3 7.7.4.4 7.7.4.5 removal of interior finishes. Power source. In Group R occupancies, single-station smoke alarms shall receive their primary power from the building wiring provided that such wiring is served from a commercial source and shall be equipped with a battery backup. Smoke alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for overcurrent protection. Exception: Smoke alarms are permitted to be solely battery operated: in existing buildings where no construction is taking place; in buildings that are not served from a commercial power source; and in existing areas of buildings undergoing alterations or repairs that do not result in the removal of interior walls or ceiling finishes exposing the structure, unless there is an attic, crawl space or basement available which could provide access for building wiring without the removal of interior finishes. Manual fire alarm boxes. Manual fire alarm boxes shall be installed in accordance with Sections 7.7.4.1 through 7.7.4.5. Location. Manual fire alarm boxes shall be located not more than 1.5 m from the entrance to each exit. Additional manual fire alarm boxes shall be located so that travel distance to the nearest box does not exceed 61 m. Exception: Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system, the notification appliances will activate on sprinkler water flow and manual activation is provided from a normally occupied location. Height. The height of the manual fire alarm boxes shall be a minimum of 1,067 mm and a maximum of 1.2 m measured vertically, from the floor level to the activating handle or lever of the box. Color. Manual fire alarm boxes shall be red in color. Signs. Where fire alarm systems are not monitored by a supervising station, an approved permanent sign shall be installed adjacent to each manual fire alarm box that reads: WHEN ALARM SOUNDS – CALL FIRE DEPARTMENT. Exception: Where the manufacturer has permanently provided this information on the manual fire alarm box. Protective covers. The Building official is authorized to require the installation of listed manual fire alarm box protective covers to prevent malicious false alarms or provide the manual fire alarm box with protection from physical damage. The protective cover shall be transparent or red in color with a transparent face to permit visibility of the manual fire alarm box. Each cover shall include proper operating instructions. A protective cover that emits a local alarm signal shall not be installed unless approved. 7.7.5 Power supply. The primary and secondary power supply for the fire alarm system shall be provided in accordance with NFPA 72. 7.7.6 Wiring. Wiring shall comply with the requirements of the SBC 401 and NFPA 72. Wireless protection systems utilizing radio-frequency transmitting devices shall comply with the special requirements for supervision of low-power wireless systems in NFPA 72. 7.7.7 Activation. Where an alarm notification system is required by another section of these code requirements, it shall be activated by: 1. Required automatic fire alarm system. SBC 801 2007 7/37 FIRE PROTECTION SYSTEMS 2. Sprinkler water-flow devices. 3. Required manual fire alarm boxes. 7.7.8 Presignal system. Presignal systems shall not be installed unless approved by the Building official and the Civil Defence. Where a presignal system is installed, 24 hours personnel supervision shall be provided at a location approved by the Civil Defence, in order that the alarm signal can be actuated in the event of fire or other emergency. 7.7.9 Zones. Each floor shall be zoned separately and a zone shall not exceed 2.1 m2. The length of any zone shall not exceed 91.4 m in any direction. Exception: Automatic sprinkler system zones shall not exceed the area permitted by NFPA 13. Zoning indicator panel. A zoning indicator panel and the associated controls shall be provided in an approved location. The visual zone indication shall lock in until the system is reset and shall not be canceled by the operation of an audiblealarm silencing switch. High-rise buildings. In buildings that have floors located more than 22.9 m above the lowest level of Civil Defence vehicle access that are occupied for human occupancy, a separate zone by floor shall be provided for all of the following types of alarm-initiating devices where provided: 1. Smoke detectors. 2. Sprinkler water-flow devices. 3. Manual fire alarm boxes. 4. Other approved types of automatic fire detection devices or suppression systems. 7.7.9.1 7.7.9.2 7.7.10 7.7.10.1 7.7.10.1.1 7.7.10.1.2 7.7.10.1.3 SBC 801 Alarm notification appliances. Alarm notification appliances shall be provided and shall be listed for their purpose. Visible alarms. Visible alarm notification appliances shall be provided in accordance with Sections 7.7.10.1.1 through 7.7.10.1.4. Exceptions: 1. Visible alarm notification appliances are not required in alterations, except where an existing fire alarm system is upgraded or replaced, or a new fire alarm system is installed. 2. Visible alarm notification appliances shall not be required in exits as defined in Section 8.2.1. Public and common areas. Visible alarm notification appliances shall be provided in public areas and common areas. Employee work areas. Where employee work areas have audible alarm coverage, the wiring system shall be designed so that visible alarm notification appliances can be integrated into the alarm system. Groups I-1 and R-1. Group I-1 and R-1 sleeping units in accordance with Table 7.7.10.1.3 shall be provided with a visible alarm notification appliance, activated by both the in-room smoke alarm and the building fire alarm system. 2007 7/38 FIRE PROTECTION SYSTEMS TABLE 7.7.10.1.3 VISIBLE AND AUDIBLE ALARMS 6 to 25 SLEEPING ACCOMMODATIONS WITH VISIBLE AND AUDIBLE ALARMS 2 26 to 50 4 51 to 75 7 76 to 100 9 101 to 150 12 151 to 200 14 201 to 300 17 301 to 400 20 401 to 500 22 501 to 1,000 5% of total 1,001 and over 50 plus 3 for each 100 over 1,000 NUMBER OF SLEEPING UNITS 7.7.10.1.4 7.7.10.2 7.7.11 SBC 801 Group R-2. In Group R-2 occupancies required by Section 7.7 to have a fire alarm system, all dwelling units and sleeping units shall be provided with the capability to support visible alarm notification appliances in accordance with ICC A117.1. Audible alarms. Audible alarm notification appliances shall be provided and sound a distinctive sound that is not to be used for any purpose other than that of a fire alarm. The audible alarm notification appliances shall provide a sound pressure level of 15 decibels (dBA) above the average ambient sound level or 5 dBA above the maximum sound level having a duration of at least 60 seconds, whichever is greater, in every occupied space within the building. The minimum sound pressure levels shall be: 70 dBA in occupancies in Groups R and I-1; 90 dBA in mechanical equipment rooms; and 60 dBA in other occupancies. The maximum sound pressure level for audible alarm notification appliances shall be 120 dBA at the minimum hearing distance from the audible appliance. Where the average ambient noise is greater than 105 dBA, visible alarm notification appliances shall be provided in accordance with NFPA 72 and audible alarm notification appliances shall not be required. Exception: Visible alarm notification appliances shall be allowed in lieu of audible alarm notification appliances in critical care areas of Group I-2 occupancies. Fire safety functions. Automatic fire detectors utilized for the purpose of performing fire safety functions shall be connected to the building’s fire alarm control panel where a fire alarm system is required by Section 7.7.2. Detectors shall, upon actuation, perform the intended function and activate the alarm notification appliances or activate a visible and audible supervisory signal at a constantly attended location. In buildings not required to be equipped with a fire alarm system, the automatic fire detector shall be powered by normal electrical service and, upon actuation, perform the intended function. The detectors shall be located in accordance with NFPA 72. 2007 7/39 FIRE PROTECTION SYSTEMS 7.7.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble. 7.7.13 Access. Access shall be provided to each detector for periodic inspection, maintenance and testing. 7.7.14 Fire-extinguishing systems. Automatic fire-extinguishing systems shall be connected to the building fire alarm system where a fire alarm system is required by another section of these code requirements or is otherwise installed. 7.7.15 Monitoring. Where required by this chapter or by the SBC 201, an approved supervising station in accordance with NFPA 72 shall monitor fire alarm systems. Exception: Supervisory service is not required for: 1. Single and multiple-station smoke alarms required by Section 7.7.2.10. 2. Smoke detectors in Group I-3 occupancies. 3. Automatic sprinkler systems in one- and two-family dwellings. 7.7.16 Automatic telephone-dialing devices. Automatic telephone-dialing devices used to transmit an emergency alarm shall not be connected to any Civil Defence telephone number unless approved by the Building official. 7.7.17 Acceptance tests. Upon completion of the installation of the fire alarm system, alarm notification appliances and circuits, alarm-initiating devices and circuits, supervisory-signal initiating devices and circuits, signaling line circuits, and primary and secondary power supplies shall be tested in accordance with NFPA 72. 7.7.18 Record of completion. A record of completion in accordance with NFPA 72 verifying that the system has been installed in accordance with the approved plans and specifications shall be provided. 7.7.19 Instructions. Operating, testing and maintenance instructions and record drawings (“as builts”) and equipment specifications shall be provided at an approved location. 7.7.20 Inspection, testing and maintenance. The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in accordance with this section and Chapter 7 of NFPA 72. Maintenance required. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection or any other feature is required for compliance with the provisions of these code requirements, such device, 7.7.20.1 SBC 801 2007 7/40 FIRE PROTECTION SYSTEMS 7.7.20.2 7.7.20.3 7.7.20.4 7.7.20.4.1 7.7.20.5 equipment, system, condition, arrangement, level of protection or other feature shall thereafter be continuously maintained in accordance with applicable NFPA requirements or as directed by the Building official. Testing. Testing shall be performed in accordance with the schedules in Chapter 7 of NFPA 72 or more frequently where required by the Building official. Where automatic testing is performed at least weekly by a remotely monitored fire alarm control unit specifically listed for the application, the manual testing frequency shall be permitted to be extended to annual. Exception: Devices or equipment that are inaccessible for safety considerations shall be tested during scheduled shutdowns where approved by the Building official, but not less than every 18 months. Detector sensitivity. Detector sensitivity shall be checked within 1 year after installation and every alternate year thereafter. After the second calibration test, where sensitivity tests indicate that the detector has remained within its listed and marked sensitivity range (or 4 percent obscuration light grey smoke, if not marked), the length of time between calibration tests shall be permitted to be extended to a maximum of 5 years. Where the frequency is extended, records of detector-caused nuisance alarms and subsequent trends of these alarms shall be maintained. In zones or areas where nuisance alarms show any increase over the previous year, calibration tests shall be performed. Method. To ensure that each smoke detector is within its listed and marked sensitivity range, it shall be tested using either a calibrated test method, the manufacturer’s calibrated sensitivity test instrument, listed control equipment arranged for the purpose, a smoke detector/control unit arrangement whereby the detector causes a signal at the control unit where its sensitivity is outside its acceptable sensitivity range or other calibrated sensitivity test method acceptable to the Building official. Detectors found to have a sensitivity outside the listed and marked sensitivity range shall be cleaned and recalibrated or replaced. Exceptions: 1. Detectors listed as field adjustable shall be permitted to be either adjusted within the listed and marked sensitivity range and cleaned and recalibrated or they shall be replaced. 2. This requirement shall not apply to single-station smoke alarms. Testing device. Detector sensitivity shall not be tested or measured using a device that administers an unmeasured concentration of smoke or other aerosol into the detector. Maintenance, inspection and testing. The building owner shall be responsible for ensuring that the fire and life safety systems are maintained in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for maintaining, inspecting and testing such systems. A written record shall be maintained and shall be made available to the Building official. SECTION 7.8 EMERGENCY ALARM SYSTEMS 7.8.1 Group H occupancies. Emergency alarms for the detection and notification of an emergency condition in Group H occupancies shall be provided as required in Chapter 25. 7.8.2 Group H-5 occupancy. Emergency alarms for notification of an emergency condition in an HPM facility shall be provided as required in Section 16.3.12. A continuous gas detection system shall be provided for HPM gases in accordance SBC 801 2007 7/41 FIRE PROTECTION SYSTEMS with Section 16.3.13. 7.8.3 Highly toxic and toxic materials. Where required by Section 35.4.2.2.10, a as detection system shall be provided for indoor storage and use of highly toxic and toxic compressed gases. 7.8.4 Ozone gas-generator rooms. A gas detection system shall be provided in ozone gas-generator rooms in accordance with Section 35.5.3.2. 7.8.5 Repair garages. A flammable-gas detection system shall be provided in repair garages for vehicles fueled by non-odorized gases in accordance with Section 20.11.7.2. 7.8.6 Refrigeration systems. Refrigeration system machinery rooms shall be provided with a refrigerant detector in accordance with Chapter 4 of the SBC 201. SECTION 7.9 SMOKE CONTROL SYSTEMS 7.9.1 Scope and purpose. This section applies to mechanical or passive smoke control systems when they are required for new buildings or portions thereof by provisions of the SBC 201 or these code requirements. The purpose of this section is to establish minimum requirements for the design, installation and acceptance testing of smoke control systems that are intended to provide a tenable environment for the evacuation or relocation of occupants. These provisions are not intended for the preservation of contents, the timely restoration of operations, or for assistance in fire suppression or overhaul activities. Smoke control systems regulated by this section serve a different purpose than the smoke and heat-venting provisions found in Section 7.10. Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the SBC 501. 7.9.2 General design requirements. Buildings, structures, or parts thereof required by the SBC 201 or these code requirements to have a smoke control system or systems shall have such systems designed in accordance with the applicable requirements of Section 7.9 and the generally accepted and well-established principles of engineering relevant to the design. The construction documents shall include sufficient information and detail to describe adequately the elements of the design necessary for the proper implementation of the smoke control systems. These documents shall be accompanied with sufficient information and analysis to demonstrate compliance with these provisions. 7.9.3 Special inspection and test requirements. In addition to the ordinary inspection and test requirements to which buildings, structures and parts thereof are required to undergo, smoke control systems subject to the provisions of Section 7.9 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its final installed condition. The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests. Such commissioning shall be in accordance with generally accepted engineering practice and, where possible, based on published standards for the particular testing involved. The special inspections and tests required by this section shall be conducted under the same terms as in the SBC 100. SBC 801 2007 7/42 FIRE PROTECTION SYSTEMS 7.9.4 7.9.4.1 7.9.4.2 7.9.4.3 7.9.4.4 7.9.4.5 7.9.4.6 7.9.5 7.9.5.1 7.9.5.2 SBC 801 Analysis. A rational analysis supporting the types of smoke control systems to be employed, the methods of their operations, the systems supporting them, and the methods of construction to be utilized shall accompany the construction documents submission and include, but not be limited to, the items indicated in Sections 7.9.4.1 through 7.9.4.6. Stack effect. The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the system’s capabilities. In determining the maximum probable stack effect, altitude, elevation, weather history and interior temperatures shall be used. Temperature effect of fire. Buoyancy and expansion caused by the design fire in accordance with Section 7.9.9 shall be analyzed. The system shall be designed such that these effects do not adversely interfere with the system’s capabilities. Wind effect. The design shall consider the adverse effects of wind. Such consideration shall be consistent with the wind-loading provisions of the SBC 301. Systems. The design shall consider the effects of the heating, ventilating and airconditioning (HVAC) systems on both smoke and fire transport. The analysis shall include all permutations of systems status. The design shall consider the effects of the fire on the heating, ventilating and air-conditioning systems. Climate. The design shall consider the effects of low temperatures on systems, property and occupants. Air inlets and exhausts shall be located so as to prevent snow or ice blockage. Duration of operation. All portions of active or passive smoke control systems shall be capable of continued operation after detection of the fire event for not less than 20 minutes. Smoke barrier construction. Smoke barriers shall comply with the SBC 201. Smoke barriers shall be constructed and sealed to limit leakage areas exclusive of protected openings. The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios: 1. Walls: A/Aw = 0.001 00 2. Exit enclosures: A/Aw = 0.00035 3. All other shafts: A/Aw = 0.00150 4. Floors and roofs: A/AF = 0.00050 where: 2 A = Total leakage area, m . AF = Unit floor or roof area of barrier, m2. Aw = Unit wall area of barrier, m2. The leakage area ratios shown do not include openings due to doors, operable windows or similar gaps. These shall be included in calculating the total leakage area. Leakage area. Total leakage area of the barrier is the product of the smoke barrier gross area monitored by the allowable leakage area ratio, plus the area of other openings such as gaps and operable windows. Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems. Passive smoke control systems tested using other approved means such as door fan testing shall be as approved by the Building official. Opening protection. Openings in smoke barriers shall be protected by automaticclosing devices actuated by the required controls for the mechanical smoke control system. Door openings shall be protected by door assemblies complying with the 2007 7/43 FIRE PROTECTION SYSTEMS 7.9.5.2.1 7.9.6 7.9.6.1 7.9.6.2 requirements of the SBC 201 for doors in smoke barriers. Exceptions: 1. Passive smoke control systems with automatic-closing devices actuated by spot-type smoke detectors listed for releasing service installed in accordance with Section 7.7.11. 2. Fixed openings between smoke zones which are protected utilizing the airflow method. 3. In Group I-2, where such doors are installed across corridors, a pair of opposite-swinging doors without a center mullion shall be installed having vision panels with approved fire-rated glazing materials in approved fire-rated frames, the area of which shall not exceed that tested. The doors shall be close fitting within operational tolerances, and shall not have undercuts, louvers or grilles. The doors shall have head and jamb stops, astragals or rabbets at meeting edges, and automatic-closing devices. Positive-latching devices are not required. 4. Group I-3. 5. Openings between smoke zones with clear ceiling heights of 4.3 m or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size. Ducts and air transfer openings. Ducts and air transfer openings are required to be protected with a minimum Class II, 121°C smoke damper complying with the SBC 201. Pressurization method. The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers. Maintenance of a tenable environment is not required in the smoke-control zone of fire origin. Minimum pressure difference. The minimum pressure difference across a smoke barrier shall be 0.015 mm water gage in fully sprinklered buildings. In buildings allowed to be other than fully sprinklered, the smoke control system shall be designed to achieve pressure differences at least two times the maximum calculated pressure difference produced by the design fire. Maximum pressure difference. The maximum air pressure difference across a smoke barrier shall be determined by required door-opening or closing forces. The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 8.8.1.2. Opening and closing forces for other doors shall be determined by standard engineering methods for the resolution of forces and reactions. The calculated force to set a side-hinged, swinging door in motion shall be determined by: Where: = A = d = F Fdc = = K = W �P = 7.9.7 SBC 801 F = Fdc + K(WA �P )/2(W- d) (Equation 7-1) 2 Door area, m . Distance from door handle to latch edge of door, m. Total door opening force, N. Force required to overcome closing device, N. Coefficient 1.0. Door width, m. Design pressure difference, Pa. Airflow design method When approved by the Building official, smoke migration through openings fixed in a permanently open position, which are located between smoke-control zones by the use of the airflow method, shall be permitted. The 2007 7/44 FIRE PROTECTION SYSTEMS 7.9.7.1 design airflow shall be in accordance with this section. Airflow shall be directed to limit smoke migration from the fire zone. The geometry of openings shall be considered to prevent flow reversal from turbulent effects. Velocity. The minimum average velocity through a fixed opening shall not be less than: 1/2 Where: = h = Tf To = = v v = 119.9 [h (Tf - To)/Tf] (Equation 7-2) Height of opening, m. Temperature of smoke, °K. Temperature of ambient air, °K. Air velocity, m/minute. 7.9.7.2 Prohibited conditions. This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system, unduly intensify the fire, disrupt plume dynamics or interfere with exiting. In no case shall airflow toward the fire exceed 1.02 m/s. Where the formula in Section 7.9.7.1 requires airflows to exceed this limit, the airflow method shall not be used. 7.9.8 Exhaust method. When approved by the Building official, mechanical smoke control for large enclosed volumes, such as in atriums or malls, shall be permitted to utilize the exhaust method. The design exhaust volumes shall be in accordance with this section. Exhaust rate. The height of the lowest horizontal surface of the accumulating smoke layer shall be maintained at least 3.0 m above any walking surface which forms a portion of a required egress system within the smoke zone. The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations. Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted. Makeup airflow rates, when measured at the potential fire location, shall not exceed 1.02 m/s toward the fire. The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits. Axisymmetric plumes. The plume mass flow rate (mp), in kg/s, shall be determined by placing the design fire center on the axis of the space being analyzed. The limiting flame height shall be determined by: 7.9.8.1 7.9.8.2 (Equation 7-3) 2/5 zl = 0.166Qc Where: mp = Plume mass flow rate, kg/s. = Total heat output. Q Qc = Convective heat output, kW. (The value of Qc shall not be taken as less than 0.70 Q.) = Height from top of fuel surface to bottom of smoke layer, m. z = Limiting flame height, m. The zl value must be greater than the fuel zl equivalent diameter (see Section 7.9.9). for z > zl mp = = 0.071 Qc1/3 z5/3 + 0.0018Qc for z > zl mp = 0.035Qc SBC 801 2007 7/45 FIRE PROTECTION SYSTEMS for z > zl mp = 0.032Qc3/5 z To convert mp from pounds per second of mass flow to a volumetric rate, the following formula shall be used: (Equation 7-4) V = 60 mp/ � Where: = Volumetric flow rate, m3/s. V � = Density of air at the temperature of the smoke layer, [kg/m3 (T: in °C)]. 7.9.8.3 Balcony spill plumes. The plume mass flow rate (mp) for spill plumes shall be determined using the geometrically probable width based on architectural elements and projections in the following equation: 2 1/3 (Equation 7-5) mp= 0.36(QW ) (zb + 0.25H) Where: = H mp = = Q W = = zb 7.9.8.4 Window plumes. The plume mass flow rate (mp) shall be determined from: Where: Aw = Hw = mp = zw = a 7.9.8.5 SBC 801 mp = 0.68(AwHw 1/2 1/3 ) (zw+a) 5/3 + 1.5 AwHw 1/2 (Equation 7-6) Area of the opening, square m2. Height of the opening, m. Plume mass flow rate, kg/s. Height from the top of the window or opening to the bottom of the smoke layer, m. = 2.4Aw2/5 Hw1/5 - 2.1Hw Plume contact with walls. When a plume contacts one or more of the surrounding walls, the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant. Use of this provision requires calculation of the plume diameter, that shall be calculated by: Where: = d Ta = Tc = = z Tc = 7.9.9 Height above fire to underside of balcony, m. Plume mass flow rate, kg/s. Total heat output. Plume width at point of spill, m. Height from balcony, m. d = 0.48 (Tc/Ta) 1/2 z (Equation 7-7) Plume diameter, m. Ambient air temperature, °K. Plume centerline temperature, °K. Height at which Tc is determined, m. 2/3 -5/3 0.08 TaQc z + Ta Design fire. The design fire shall be based on a Q of not less than 5,275 kW unless a rational analysis is performed by the registered design professional and approved by the Building official. The design fire shall be based on the analysis in accordance with Section 7.9.4 and this section. 2007 7/46 FIRE PROTECTION SYSTEMS 7.9.9.1 7.9.9.2 Factors considered. The engineering analysis shall include the characteristics of the fuel, fuel load, effects included by the fire, and whether the fire is likely to be steady or unsteady. Separation distance. Determination of the design fire shall include consideration of the type of fuel, fuel spacing and configuration. The ratio of the separation distance to the fuel equivalent radius shall not be less than 4. The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package. The design fire shall be increased if other combustibles are within the separation distance as determined by: (Equation 7-8) Where: q" = Incident radiant heat flux required for nonpiloted ignition, W/m2. = Heat release from fire, kW. Q = Separation distance from target to center of fuel package, m. R 1/2 R = [Q/(12 � q")] 7.9.9.3 7.9.9.4 7.9.10 7.9.10.1 Heat-release assumptions. The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material. Sprinkler effectiveness assumptions. A documented engineering analysis shall be provided for conditions that assume fire growth is halted at the time of sprinkler activation. Equipment. Equipment such as, but not limited to, fans, ducts, automatic dampers and balance dampers, shall be suitable for their intended use, suitable for the probable exposure temperatures that the rational analysis indicates, and as approved by the Building official. Exhaust fans. Components of exhaust fans shall be rated and certified by the manufacturer for the probable temperature rise to which the components will be exposed. This temperature rise shall be computed by: Ts = (Qc/mc) + (Ta) 7.9.10.2 7.9.10.3 SBC 801 (Equation 7-9) Where: = Specific heat of smoke at smokelayer temperature, kJ/kg . °K. c = Exhaust rate, kg/s. m Qc = Convective heat output of fire, kW. Ta = Ambient temperature, °K. Ts = Smoke temperature, °K. Exception: Reduced Ts as calculated based on the assurance of adequate dilution air. Ducts. Duct materials and joints shall be capable of withstanding the probable temperatures and pressures to which they are exposed as determined in accordance with Section 7.9.10.1. Ducts shall be constructed and supported in accordance with the SBC 501. Ducts shall be leak tested to 1.5 times the maximum design pressure in accordance with nationally accepted practices. Measured leakage shall not exceed 5 percent of design flow. Results of such testing shall be a part of the documentation procedure. Ducts shall be supported directly from fire-resistancerated structural elements of the building by substantial, noncombustible supports. Exception: Flexible connections (for the purpose of vibration isolation) complying with the SBC 501 and which are constructed of approved fireresistance-rated materials. Equipment, inlets and outlets. Equipment shall be located so as to not expose uninvolved portions of the building to an additional fire hazard. Outside air inlets 2007 7/47 FIRE PROTECTION SYSTEMS 7.9.10.4 7.9.10.5 7.9.11 7.9.11.1 7.9.12 7.9.12.1 7.9.12.2 7.9.12.2.1 SBC 801 shall be located so as to minimize the potential for introducing smoke or flame into the building. Exhaust outlets shall be so located as to minimize reintroduction of smoke into the building and to limit exposure of the building or adjacent buildings to an additional fire hazard. Automatic dampers. Automatic dampers, regardless of the purpose for which they are installed within the smoke control system, shall be listed and conform to the requirements of approved recognized standards. Fans. In addition to other requirements, belt-driven fans shall have 1.5 times the number of belts required for the design duty with the minimum number of belts being two. Fans shall be selected for stable performance based on normal temperature and, where applicable, elevated temperature. Calculations and manufacturer’s fan curves shall be part of the documentation procedures. Fans shall be supported and restrained by noncombustible devices in accordance with the structural design requirements of the SBC 301. Motors driving fans shall not be operated beyond their nameplate horsepower (kilowatts) as determined from measurement of actual current draw and shall have a minimum service factor of 1.15. Power systems. The smoke control system shall be supplied with two sources of power. Primary power shall be the normal building power systems. Secondary power shall be from an approved standby source complying with the SBC 401. The standby power source and its transfer switches shall be in a separate room from the normal power transformers and switch gear and shall be enclosed in a room constructed of not less than 1 hour fire-resistance-rated fire barriers, ventilated directly to and from the exterior. Power distribution from the two sources shall be by independent routes. Transfer to full standby power shall be automatic and within 60 seconds of failure of the primary power. The systems shall comply with the SBC 401. Power sources and power surges. Elements of the smoke management system relying on volatile memories or the like shall be supplied with uninterruptable power sources of sufficient duration to span 15-minute primary power interruption. Elements of the smoke management system susceptible to power surges shall be suitably protected by conditioners, suppressors or other approved means. Detection and control systems. Fire detection systems providing control input or output signals to mechanical smoke control systems or elements thereof shall comply with the requirements of Section 7.7. Such systems shall be equipped with a control unit complying with UL 864 and listed as smoke control equipment. Control systems for mechanical smoke control systems shall include provisions for verification. Verification shall include positive confirmation of actuation, testing, manual override, the presence of power downstream of all disconnects and, through a preprogrammed weekly test sequence report, abnormal conditions audibly, visually and by printed report. Wiring. In addition to meeting requirements of the SBC 401, all wiring, regardless of voltage, shall be fully enclosed within continuous raceways. Activation. Smoke control systems shall be activated in accordance with this section. Pressurization, airflow or exhaust method. Mechanical smoke control systems using the pressurization, airflow or exhaust method shall have completely automatic control. 2007 7/48 FIRE PROTECTION SYSTEMS 7.9.12.2.2 7.9.12.3 7.9.13 7.9.13.1 7.9.13.2 7.9.13.3 Passive method. Passive smoke control systems actuated by approved spot-type detectors listed for releasing service shall be permitted. Automatic control. Where completely automatic control is required or used, the automatic-control sequences shall be initiated from an appropriately zoned automatic sprinkler system complying with Section 7.3.3.1.1, manual controls that are readily accessible to the Civil Defence, and any smoke detectors required by the engineering analysis. Control air tubing. Control air tubing shall be of sufficient size to meet the required response times. Tubing shall be flushed clean and dry prior to final connections and shall be adequately supported and protected from damage. Tubing passing through concrete or masonry shall be sleeved and protected from abrasion and electrolytic action. Materials. Control air tubing shall be hard drawn copper, Type L, ACR in accordance with ASTM B 42, ASTM B 43, ASTM B 68, ASTM B 88, ASTM B 251 and ASTM B 280. Fittings shall be wrought copper or brass, solder type, in accordance with ASME B 16.18 or ASME B 16.22. Changes in direction shall be made with appropriate tool bends. Brass compression-type fittings shall be used at final connection to devices; other joints shall be brazed using a BCuP5 brazing alloy with solidus above 593°C and liquids below 816°C. Brazing flux shall be used on copper-to-brass joints only. Exception: Nonmetallic tubing used within control panels and at the final connection to devices, provided all of the following conditions are met: 1. Tubing shall be listed by an approved agency for flame and smoke characteristics. 2. Tubing and the connected device shall be completely enclosed within a galvanized or paint-grade steel enclosure of not less than 0.76 mm (No. 22 galvanized sheet gage) thickness. Entry to the enclosure shall be by copper tubing with a protective grommet of neoprene or teflon or by suitable brass compression to male-barbed adapter. 3. Tubing shall be identified by appropriately documented coding. 4. Tubing shall be neatly tied and supported within enclosure. Tubing bridging cabinet and door or moveable device shall be of sufficient length to avoid tension and excessive stress. Tubing shall be protected against abrasion. Tubing serving devices on doors shall be fastened along hinges. Isolation from other functions. Control tubing serving other than smoke control functions shall be isolated by automatic isolation valves or shall be an independent system. Testing. Control air tubing shall be tested at three times the operating pressure for not less than 30 minutes without any noticeable loss in gauge pressure prior to final connection to devices. 7.9.14 Marking and identification. The detection and control systems shall be clearly marked at all junctions, accesses and terminations. 7.9.15 Control diagrams. Identical control diagrams showing all devices in the system and identifying their location and function shall be maintained current and kept on file with the Building official, the Civil Defence and in the fire command center in format and manner approved by the Building official. 7.9.16 Fire-fighter’s smoke control panel. A fire-fighter’s smoke control panel for Civil Defence emergency response purposes only shall be provided and shall include SBC 801 2007 7/49 FIRE PROTECTION SYSTEMS 7.9.16.1 7.9.16.2 7.9.16.3 SBC 801 manual control or override of automatic control for mechanical smoke control systems. The panel shall be located in a fire command center complying with Section 5C.9 and shall comply with Sections 7.9.16.1 through 7.9.16.3. Smoke control systems. Fans within the building shall be shown on the firefighter’s control panel. A clear indication of the direction of airflow and the relationship of components shall be displayed. Status indicators shall be provided for all smoke control equipment, annunciated by fan and zone and by pilot-lamptype indicators as follows: 1. Fans, dampers and other operating equipment in their normal status – WHITE. 2. Fans, dampers and other operating equipment in their off or closed status – RED. 3. Fans, dampers and other operating equipment in their on or open status – GREEN. 4. Fans, dampers and other operating equipment in a fault status – YELLOW/AMBER. Smoke control panel. The fire-fighter’s control panel shall provide control capability over the complete smoke-control system equipment within the building as follows: 1. ON-AUTO-OFF control over each individual piece of operating smoke control equipment that can also be controlled from other sources within the building. This includes stairway pressurization fans; smoke exhaust fans; supply, return and exhaust fans; elevator shaft fans; and other operating equipment used or intended for smoke control purposes. 2. OPEN-AUTO-CLOSE control over individual dampers relating to smoke control and that are also controlled from other sources within the building. 3. ON-OFF or OPEN-CLOSE control over smoke control and other critical equipment associated with a fire or smoke emergency and that can only be controlled from the fire-fighter’s control panel. Exceptions: 1. Complex systems, where approved, where the controls and indicators are combined to control and indicate all elements of a single smoke zone as a unit. 2. Complex systems, where approved, where the control is accomplished by computer interface using approved, plain English commands. Control action and priorities. The fire-fighter’s control panel actions shall be as follows: 1. ON-OFF, OPEN-CLOSE control actions shall have the highest priority of any control point within the building. Once issued from the fire-fighter’s control panel, no automatic or manual control from any other control point within the building shall contradict the control action. Where automatic means are provided to interrupt normal, nonemergency equipment operation or produce a specific result to safeguard the building or equipment (i.e., duct freezestats, duct smoke detectors, high-temperature cutouts, temperature-actuated linkage and similar devices), such means shall be capable of being overridden by the fire-fighter’s control panel. The last control action as indicated by each firefighter’s control panel switch position shall prevail. In no case shall control actions require the smoke control system to assume more than one configuration at any one time. Exception: Power disconnects required by the SBC 401. 2. Only the AUTO position of each three-position fire-fighter’s control panel switch shall allow automatic or manual control action from other control points within the building. The AUTO position shall be the NORMAL, 2007 7/50 FIRE PROTECTION SYSTEMS nonemergency, building control position. Where a fire-fighter’s control panel is in the AUTO position, the actual status of the device (on, off, open, closed) shall continue to be indicated by the status indicator described above. When directed by an automatic signal to assume an emergency condition, the NORMAL position shall become the emergency condition for that device or group of devices within the zone. In no case shall control actions require the smoke control system to assume more than one configuration at any one time. 7.9.17 System response time. Smoke-control system activation shall be initiated immediately after receipt of an appropriate automatic or manual activation command. Smoke control systems shall activate individual components (such as dampers and fans) in the sequence necessary to prevent physical damage to the fans, dampers, ducts and other equipment. For purposes of smoke control, the firefighter’s control panel response time shall be the same for automatic or manual smoke control action initiated from any other building control point. The total response time, including that necessary for detection, shutdown of operating equipment and smoke control system startup, shall allow for full operational mode to be achieved before the conditions in the space exceed the design smoke condition. The system response time for each component and their sequential relationships shall be detailed in the required rational analysis and verification of their installed condition reported in the required final report. 7.9.18 Acceptance testing. Devices, equipment, components and sequences shall be individually tested. These tests, in addition to those required by other provisions of these code requirements, shall consist of determination of function, sequence and, where applicable, capacity of their installed condition. Detection devices. Smoke or fire detectors that are a part of a smoke control system shall be tested in accordance with Chapter 7 in their installed condition. When applicable, this testing shall include verification of airflow in both minimum and maximum conditions. Ducts. Ducts that are part of a smoke control system shall be traversed using generally accepted practices to determine actual air quantities. Dampers. Dampers shall be tested for function in their installed condition. Inlets and outlets. Inlets and outlets shall be read using generally accepted practices to determine air quantities. Fans. Fans shall be examined for correct rotation. Measurements of voltage, amperage, revolutions per minute and belt tension shall be made. Smoke barriers. Measurements using inclined manometers or other approved calibrated measuring devices shall be made of the pressure differences across smoke barriers. Such measurements shall be conducted for each possible smoke control condition. Controls. Each smoke zone, equipped with an automatic-initiation device, shall be put into operation by the actuation of one such device. Each additional device within the zone shall be verified to cause the same sequence without requiring the operation of fan motors in order to prevent damage. Control sequences shall be verified throughout the system, including verification of override from the firefighter’s control panel and simulation of standby power conditions. Special inspections for smoke control. Smoke control systems shall be tested by a special inspector. Scope of testing. Special inspections shall be conducted in accordance with the following: 7.9.18.1 7.9.18.2 7.9.18.3 7.9.18.4 7.9.18.5 7.9.18.6 7.9.18.7 7.9.18.8 7.9.18.8.1 SBC 801 2007 7/51 FIRE PROTECTION SYSTEMS 1. During erection of ductwork and prior to concealment for the purposes of leakage testing and recording of device location. 2. Prior to occupancy and after sufficient completion for the purposes of pressure-difference testing, flow measurements, and detection and control verification. 7.9.18.8.2 Qualifications. Special inspection agencies for smoke control shall have expertise in fire protection engineering, mechanical engineering and certification as air balancers. 7.9.18.8.3 Reports. A complete report of testing shall be prepared by the special inspector or special inspection agency. The report shall include identification of all devices by manufacturer, nameplate data, design values, measured values and identification tag or mark. The report shall be reviewed by the responsible registered design professional and, when satisfied that the design intent has been achieved, the responsible registered design professional shall seal, sign and date the report. 7.9.18.8.3.1 Report filing. A copy of the final report shall be filed with the Building official and an identical copy shall be maintained in an approved location at the building. 7.9.18.9 Identification and documentation. Charts, drawings and other documents identifying and locating each component of the smoke control system, and describing their proper function and maintenance requirements, shall be maintained on file at the building as an attachment to the report required by Section 7.9.18.8.3. Devices shall have an approved identifying tag or mark on them consistent with the other required documentation and shall be dated indicating the last time they were successfully tested and by whom. 7.9.19 System acceptance. Buildings, or portions thereof, required by these code requirements to comply with this section shall not be issued a certificate of occupancy until such time that the Building official determines that the provisions of this section have been fully complied with, and that the Civil Defence has received satisfactory instruction on the operation, both automatic and manual, of the system. Exception: In buildings of phased construction, a temporary certificate of occupancy, as approved by the Building official, shall be permitted provided that those portions of the building to be occupied meet the requirements of this section and that the remainder does not pose a significant hazard to the safety of the proposed occupants or adjacent buildings. 7.9.20 Smokeproof enclosures. Where required by Section 8.19.1.8 of the SBC 201, a smokeproof enclosure shall be constructed in accordance with this section. A smokeproof enclosure shall consist of an enclosed interior exit stairway that conforms to Section 8.19.1 of the SBC 201, and an outside balcony or ventilated vestibule meeting the requirements of this section. Where access to the roof is required by these code requirements, such access shall be from the smokeproof enclosure where a smokeproof enclosure is required. Access. Access to the stair shall be byway of a vestibule or an open exterior balcony. The minimum dimension of the vestibule shall not be less than the required width of the corridor leading to the vestibule but shall not have a width of less than 1.1 m and shall not have a length of less than 1.8 m in the direction of egress travel. Construction. The smokeproof enclosure shall be separated from the remainder of the building by not less than a 2 hours fire-resistance-rated fire barrier without openings other than the required means of egress doors. The vestibule shall be separated from the stairway by not less than a 2 hours fire-resistance-rated fire 7.9.20.1 7.9.20.2 SBC 801 2007 7/52 FIRE PROTECTION SYSTEMS barrier. The open exterior balcony shall be constructed in accordance with the fireresistance-rating requirements for floor construction. 7.9.20.2.1 Door closers. Doors in a smokeproof enclosure shall be self-closing or shall be automatic-closing by actuation of a smoke detector installed at the floor-side entrance to the smokeproof enclosure in accordance with Section 4B.16.4.7. The actuation of the smoke detector on any door shall activate the closing devices on all doors in the smokeproof enclosure at all levels. Smoke detectors shall be installed in accordance with Section 7.7.11. 7.9.20.3 Natural ventilation alternative. The provisions of Sections 7.9.20.3.1 through 7.9.20.3.3 shall apply to ventilation of smokeproof enclosures by natural means. 7.9.20.3.1 Balcony doors. Where access to the stairway is by way of an open exterior balcony, the door assembly into the enclosure shall be a fire door in accordance with Section 4B.16.4. 7.9.20.3.2 Vestibule doors. Where access to the stairway is by way of a vestibule, the door assembly into the vestibule shall be a fire door complying with Section 4B.16.4. The door assembly from the vestibule to the stairway shall have not less than a 20 minutes fire protection rating complying with Section 4B.16.4. 2 7.9.20.3.3 Vestibule ventilation. Each vestibule shall have a minimum net area of 1.5 m of opening in a wall facing an outer court, yard or public way that is at least 6.1 m in width. 7.9.20.4 Mechanical ventilation alternative. The provisions of Sections 7.9.20.4.1 through 7.9.20.4.4 shall apply to ventilation of smokeproof enclosures by mechanical means. 7.9.20.4.1 Vestibule doors. The door assembly from the building into the vestibule shall be a fire door complying with Section 4B.16.4. The door assembly from the vestibule to the stairway shall have not less than a 20 minutes fire protection rating in accordance with Section 4B.16.4. The door from the building into the vestibule shall be provided with gaskets or other provisions to minimize air leakage. 7.9.20.4.2 Vestibule ventilation. The vestibule shall be supplied with not less than one air change per minute and the exhaust shall not be less than 150 percent of supply. Supply air shall enter and exhaust air shall discharge from the vestibule through separate, tightly constructed ducts used only for that purpose. Supply air shall enter the vestibule within 150 mm of the floor level. The top of the exhaust register shall be located at the top of the smoke trap but not more than 150 mm down from the top of the trap, and shall be entirely within the smoke trap area. Doors in the open position shall not obstruct duct openings. Duct openings with controlling dampers are permitted where necessary to meet the design requirements, but dampers are not otherwise required. 7.9.20.4.2.1 Engineered ventilation system. Where a specially engineered system is used, the system shall exhaust a quantity of air equal to not less than 90 air changes per hour from any vestibule in the emergency operation mode and shall be sized to handle three vestibules simultaneously. Smoke detectors shall be located at the floor-side entrance to each vestibule and shall activate the system for the affected vestibule. Smoke detectors shall be installed in accordance with Section 7.7.11. 7.9.20.4.3 Smoke trap. The vestibule ceiling shall be at least 0.50 m higher than the door opening into the vestibule to serve as a smoke and heat trap and to provide an upward-moving air column. The height shall not be decreased unless approved and justified by design and test. 909.20.4.4 Stair shaft air movement system. The stair shaft shall be provided with a dampered relief opening and supplied with sufficient air to maintain a minimum positive pressure of 25 Pa in the shaft relative to the vestibule with all doors closed. SBC 801 2007 7/53 FIRE PROTECTION SYSTEMS 7.9.20.5 7.9.20.6 7.9.20.6.1 7.9.20.6.2 7.9.20.6.3 7.9.21 7.9.21.1 7.9.21.2 7.9.21.3 7.9.22 SBC 801 Stair pressurization alternative. Where the building is equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1, the vestibule is not required, provided that interior exit stairways are pressurized to a minimum of 37 Pa and a maximum of 87 Pa in the shaft relative to the building measured with all stairway doors closed under maximum anticipated stack pressures. Ventilating equipment. The activation of ventilating equipment required by the alternatives in Sections 7.9.20.4 and 7.9.20.5 shall be by smoke detectors installed at each floor level at an approved location at the entrance to the smokeproof enclosure. When the closing device for the stair shaft and vestibule doors is activated by smoke detection or power failure, the mechanical equipment shall activate and operate at the required performance levels. Smoke detectors shall be installed in accordance with Section 7.7.11. Ventilation systems. Smokeproof enclosure ventilation systems shall be independent of other building ventilation systems. The equipment and ductwork shall comply with one of the following: 1. Equipment and ductwork shall be located exterior to the building and directly connected to the smokeproof enclosure or connected to the smokeproof enclosure by ductwork enclosed by 2 hours fire-resistance-rated fire barriers. 2. Equipment and ductwork shall be located within the smokeproof enclosure with intake or exhaust directly from and to the outside or through ductwork enclosed by 2 hours fire-resistance-rated fire barriers. 3. Equipment and ductwork shall be located within the building if separated from the remainder of the building, including other mechanical equipment, by 2 hours fire-resistance-rated fire barriers. Standby power. Mechanical vestibule and stair shaft ventilation systems and automatic fire detection systems shall be powered by an approved standby power system conforming to Section 2.16.10.1 of the SBC 201 and SBC 501. Acceptance and testing. Before the mechanical equipment is approved, the system shall be tested in the presence of the building official to confirm that the system is operating in compliance with these requirements. Underground building smoke exhaust system. Where required by the SBC 201 for underground buildings, a smoke exhaust system shall be provided in accordance with this section. Exhaust capability. Where compartmentation is required, each compartment shall have an independent, automatically activated smoke exhaust system capable of manual operation. The system shall have an air supply and smoke exhaust capability that will provide a minimum of six air changes per hour. Operation. The smoke exhaust system shall be operated in the compartment of origin by the following, independently of each other: 1. Two cross-zoned smoke detectors within a single protected area or a single smoke detector monitored by an alarm verification zone or an approved equivalent method. 2. The automatic sprinkler system. 3. Manual controls that are readily accessible to the Civil Defence. Alarm required. Activation of the smoke exhaust system shall activate an audible alarm at a constantly attended location. Maintenance. Smoke control systems shall be maintained to ensure to a reasonable degree that the system is capable of controlling smoke for the duration required. The system shall be maintained in accordance with the manufacturer’s instructions and Sections 7.9.22.1 through 7.9.22.5. 2007 7/54 FIRE PROTECTION SYSTEMS 7.9.22.1 7.9.22.2 7.9.22.3 7.9.22.4 7.9.22.5 Schedule. A routine maintenance and operational testing program shall be initiated immediately after the smoke control system has passed the acceptance tests. A written schedule for routine maintenance and operational testing shall be established. Written record. A written record of smoke control system testing and maintenance shall be maintained on the premises. The written record shall include the date of the maintenance, identification of the servicing personnel and notification of any unsatisfactory condition and the corrective action taken, including parts replaced. Testing. Operational testing of the smoke control system shall include all equipment such as initiating devices, fans, dampers, controls, doors and windows. Dedicated smoke control systems. Dedicated smoke control systems shall be operated for each control sequence semi-annually. The system shall also be tested under standby power conditions. Nondedicated smoke control systems. Nondedicated smoke control systems shall be operated for each control sequence annually. The system shall also be tested under standby power conditions. SECTION 7.10 SMOKE AND HEAT VENTS 7.10.1 General. Where required by these code requirements or otherwise installed, smoke and heat vents, or mechanical smoke exhaust systems, and draft curtains shall conform to the requirements of this section. Exception: Frozen food warehouses used solely for storage of Class I and Class II commodities where protected by an approved automatic sprinkler system. 7.10.2 Where required. Approved smoke and heat vents shall be installed in the roofs of one-story buildings or portions thereof occupied for the uses set forth in Sections 7.10.2.1 through 7.10.2.4. Groups F-1 and S1. Buildings and portions thereof used as a Group F-1 or S-1 occupancy having more than 4,645 m2 of undivided area. Exception: Group S-1 aircraft repair hangars. Group H. Buildings and portions thereof used as a Group H occupancy as follows: 1. In occupancies classified as Group H-2 or H-3, any of which are more than 1,394 m2 in single floor area. Exception: Buildings of noncombustible construction containing only noncombustible materials. 2. In areas of buildings in Group H used for storing Class 2, 3 and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water-reactive materials as required for a high-hazard commodity classification. Exception: Buildings of noncombustible construction containing only noncombustible materials. High-piled combustible storage. Buildings and portions thereof containing highpiled combustible stock or rack storage in any occupancy group when required by Section 21.6.7. Exit access travel distance increase. Buildings and portions thereof used as a Group F-1 or S-1 occupancy where the maximum exit access travel distance is increased with Section 8.15.2. 7.10.2.1 7.10.2.2 7.10.2.3 7.10.2.4 SBC 801 2007 7/55 FIRE PROTECTION SYSTEMS 7.10.3 7.10.3.1 7.10.3.1.1 7.10.3.1.2 7.10.3.1.3 7.10.3.2 Design and installation. The design and installation of smoke and heat vents and draft curtains shall be as specified in this section and Table 7.10.3. Vent operation. Smoke and heat vents shall be approved and labeled and shall be capable of being operated by approved automatic and manual means. Automatic operation of smoke and heat vents shall conform to the provisions of this section. Gravity-operated drop out vents. Automatic smoke and heat vents containing heat-sensitive glazing designed to shrink and drop out of the vent opening when exposed to fire shall fully open within 5 minutes after the vent cavity is exposed to a simulated fire represented by a time-temperature gradient that reaches an air temperature of 260°C within 5 minutes. Sprinklered buildings. Where installed in buildings equipped with an approved automatic sprinkler system, smoke and heat vents shall be designed to operate automatically. Nonsprinklered buildings. Where installed in buildings not equipped with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation of a heat-responsive device rated at between 38°C and 104°C above ambient. Exception: Gravity-operated drop out vents complying with Section 7.10.3.1.1. Vent dimensions. The effective venting area shall not be less than 1.5 m2 with no dimension less than 1.2 m, excluding ribs or gutters having a total width not exceeding 150 mm. TABLE 7.10.3 REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa MINIMUM DRAFT CURTAIN DEPTH (m) MAXIMUM AREA FORMED BY DRAFT CURTAINS (m2) VENT AREA TO FLOOR AREA RATIO MAXIMUM SPACING OF VENT CENTERS (m) MAXIMUM DISTANCE TO VENTS FROM WALL OR DRAFT CURTAINb (m) 4,645 1:100 36.6 18.3 OCCUPANCY GROUP AND COMMODITY CLASSIFICATION DESIGNATED STORAGE HEIGHT (m) Group F-1 — Group S-1 I-IV (Option 1) � 6.1 1.8 929 1:100 30.5 18.3 >6.1 � 12.2 1.8 743 1:75 30.5 16.8 � 6.1 1.2 278.7 1:75 30.5 16.8 >6.1 � 12.2 1.2 278.7 1:50 30.5 16.8 � 6.1 1.8 557 1:50 30.5 16.8 >6.1 � 9.1 1.8 557 1:40 27.4 13.7 � 6.1 1.2 371.6 1:50 30.5 16.8 >6.1 � 9.1 1.2 185.8 1:30 22.9 12.2 Group S-1 I-IV (Option 2) Group S-1 High hazard (Option 1) Group S-1 High hazard (Option 2) a. b. 0.1 x H but � 1.2 Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 21. For solid-piled storage heights in excess of those indicated, an approved engineered design shall be used. The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft curtained area. 7.10.3.3 SBC 801 Vent locations. Smoke and heat vents shall be located 6.1 m or more from adjacent lot lines and fire walls and 3 m or more from fire barrier walls. Vents shall be uniformly located within the roof area above high-piled storage areas, with consideration given to roof pitch, draft curtain location, sprinkler location and structural members. 2007 7/56 FIRE PROTECTION SYSTEMS 7.10.3.4 7.10.3.4.1 7.10.3.4.2 7.10.4 7.10.4.1 7.10.4.2 Draft curtains. Where required, draft curtains shall be provided in accordance with this section. Exception: Where areas of buildings are equipped with early suppression fastresponse (ESFR) sprinklers, draft curtains shall not be provided within these areas. Draft curtains shall only be provided at the separation between the ESFR sprinklers and the conventional sprinklers. Construction. Draft curtains shall be constructed of sheet metal, lath and plaster, gypsum board or other approved materials that provide equivalent performance to resist the passage of smoke. Joints and connections shall be smoke tight. Location and depth. The location and minimum depth of draft curtains shall be in accordance with Table 7.10.3. Mechanical smoke exhaust. Where approved by the Building official, engineered mechanical smoke exhaust shall be an acceptable alternative to smoke and heat vents. Location. Exhaust fans shall be uniformly spaced within each draft-curtained area and the maximum distance between fans shall not be greater than 30.5 m. Size. Fans shall have a maximum individual capacity of 14.2 m³/s. The aggregate capacity of smoke exhaust fans shall be determined by the equation: (Equation 7-10) C = A × 300 7.10.4.3 7.10.4.4 7.10.4.5 7.10.4.6 where: 3 C = Capacity of mechanical ventilation required, in m /s. A = Area of roof vents provided in m2 in accordance with Table 7.10.3. Operation. Mechanical smoke exhaust fans shall be automatically activated by the automatic sprinkler system or by heat detectors having operating characteristics equivalent to those described in Section 7.10.3.1. Individual manual controls of each fan unit shall also be provided. Wiring and control. Wiring for operation and control of smoke exhaust fans shall be connected ahead of the main disconnect and protected against exposure to temperatures in excess of 538°C for a period of not less than 15 minutes. Controls shall be located so as to be immediately accessible to the fire service from the exterior of the building and protected against interior fire exposure by fire barriers having a fire-resistance rating not less than 1 hour. Supply air. Supply air for exhaust fans shall be provided at or near the floor level and shall be sized to provide a minimum of 50 percent of required exhaust. Openings for supply air shall be uniformly distributed around the periphery of the area served. Interlocks. On combination comfort air-handling/smoke removal systems or independent comfort air-handling systems, fans shall be controlled to shut down in accordance with the approved smoke control sequence. SECTION 7.11 EXPLOSION CONTROL 7.11.1 SBC 801 General. Explosion control shall be provided in the following locations: 1. Where a structure, room or space is occupied for purposes involving explosion hazards as identified in Table 7.11.1. 2. Where quantities of hazardous materials specified in Table 7.11.1 exceed the maximum allowable quantities in Table 25.3.1.1(1). Such areas shall be provided with explosion (deflagration) venting, explosion (deflagration) prevention systems, or barricades in accordance with this section 2007 7/57 FIRE PROTECTION SYSTEMS and NFPA 69, or NFPA 495 as applicable. Deflagration venting shall not be utilized as a means to protect buildings from detonation hazards. Required deflagration venting. Areas that are required to be provided with deflagration venting shall comply with the following: 1. Walls, ceilings and roofs exposing surrounding areas shall be designed to resist a minimum internal pressure of 4,788 Pa. The minimum internal design pressure shall not be less than five times the maximum internal relief pressure specified in Section 7.11.2, Item 5. 2. Deflagration venting shall be provided only in exterior walls and roofs. 7.11.2 TABLE 7.11.1 EXPLOSION CONTROL REQUIREMENTS MATERIAL Combustible dustsa Cryogenic fluids Explosives Flammable gas Flammable liquids Organic peroxides Oxidizer liquids and solids Pyrophoric Unstable (reactive) Water-reactive liquids and solids EXPLOSION CONTROL METHODS Explosion (deflagration) CLASS Barricade venting or explosion (deflagration) construction prevention systems Hazard Category — Not required Required Flammable Not required Required Division 1.1 Division 1.2 Division 1.3 Division 1.4 Division 1.5 Division 1.6 Gaseous Liquefied IAb IBc U I Required Required Not required Not required Required Required Not required Not required Not required Not required Required Required Not required Not required Required Required Not required Not required Required Required Required Required Not permitted Not permitted 4 Required Not permitted Gases Not required Required 4 Required 3 detonable Required 3 nondetonable Not required 3 Not required Not required 2e Special Uses Not permitted Not permitted Required Required Required Acetylene generator rooms — Not required Required Grain processing Liquefied petroleum gas distribution facilities Where explosion hazards existd — Not required Required — Not required Required Detonation Deflagration Required Not required Not permitted Required a. b. c. d. e. Combustible dusts that are generated during manufacturing or processing. See definition of Combustible Dust in Chapter 1. Storage or use. In open use or dispensing. Rooms containing dispensing and use of hazardous materials when an explosive environment can occur because of the characteristics or nature of the hazardous materials or as a result of the dispensing or use process. A method of explosion control shall be provided when Class 2 water-reactive materials can form potentially explosive mixtures. SBC 801 2007 7/58 FIRE PROTECTION SYSTEMS 3. 4. 5. 6. 7. 8. Exception: Where sufficient exterior wall and roof venting cannot be provided because of inadequate exterior wall or roof area, deflagration venting shall be allowed by specially designed shafts vented to the exterior of the building. Deflagration venting shall be designed to prevent unacceptable structural damage. Where relieving a deflagration, vent closures shall not produce projectiles of sufficient velocity and mass to cause life threatening injuries to the occupants or other persons on the property or adjacent public ways. The aggregate clear area of vents and venting devices shall be governed by the pressure resistance of the construction assemblies specified in Item 1 of this section and the maximum internal pressure allowed by Item 5 of this section. Vents shall be designed to withstand loads in accordance with the SBC 301. Vents shall consist of any one or any combination of the following to relieve at a maximum internal pressure of 958 Pa, but not less than the loads required by the SBC 301: 5.1 Exterior walls designed to release outward. 5.2 Hatch covers. 5.3 Outward swinging doors. 5.4 Roofs designed to uplift. 5.5 Venting devices listed for the purpose. Vents designed to release from the exterior walls or roofs of the building when venting a deflagration shall discharge directly to the exterior of the building where an unoccupied space not less than 15.2 m in width is provided between the exterior walls of the building and the property line. Exception: Vents complying with Item 7 of this section. Vents designed to remain attached to the building when venting a deflagration shall be so located that the discharge opening shall not be less than 3 m vertically from window openings and exits in the building and 6.1 m horizontally from exits in the building, from window openings and exits in adjacent buildings on the same property, and from the property line. Discharge from vents shall not be into the interior of the building. 7.11.3 Explosion prevention systems. Explosion prevention systems shall be of an approved type and installed in accordance with the provisions of these code requirements and NFPA 69. 7.11.4 Barricades. Barricades shall be designed and installed in accordance with NFPA 495. SECTION 7.12 CIVIL DEFENCE CONNECTIONS 7.12.1 Installation. Civil Defence connections shall be installed in accordance with the NFPA standards applicable to the system design. 7.12.2 Location. With respect to hydrants, driveways, buildings and landscaping, Civil Defence connections shall be so located that fire apparatus and hose connected to supply the system will not obstruct access to the buildings for other fire apparatus. The location of Civil Defence connections shall be approved. Visible location. Civil Defence connections shall be located on the street side of buildings, fully visible and recognizable from the street or nearest point of Civil Defence vehicle access or as otherwise approved by the Building official. 7.12.2.1 SBC 801 2007 7/59 FIRE PROTECTION SYSTEMS 7.12.2.2 Existing buildings. On existing buildings, wherever the Civil Defence connection is not visible to approaching fire apparatus, the Civil Defence connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters “CDC” at least 150 mm high and words in letters at least 51 mm high or an arrow to indicate the location. All such signs shall be subject to the approval of the Building official. 7.12.3 Access. Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimum of 1.0 m. Locking Civil Defence connection caps. The Building official is authorized to require locking caps on Civil Defence connections for water-based fire protection systems where the responding fire department carries appropriate key wrenches for removal. 7.12.3.1 7.12.4 Signs. A metal sign with raised letters at least 25 mm in size shall be mounted on all Civil Defence connections serving fire sprinklers, standpipes or fire pump connections. Such signs shall read: AUTOMATIC SPRINKLERS or STANDPIPES or TEST CONNECTION or a combination thereof as applicable. 7.12.5 Backflow protection. The potable water supply to automatic sprinkler and standpipe systems shall be protected against backflow as required by the SBC 701 and NFPA standards. 7.12.6 Inspection, testing and maintenance. All Civil Defence connections shall be periodically inspected, tested and maintained in accordance with NFPA 25. SECTION 7.13 FIRE PUMPS 7.13.1 General. Where provided, fire pumps shall be installed in accordance with this section and NFPA 20. 7.13.2 Protection against interruption of service. The fire pump, driver, and controller shall be protected in accordance with NFPA 20 against possible interruption of service through damage caused by explosion, fire, flood, earthquake, rodents, insects, windstorm, freezing, vandalism and other adverse conditions. 7.13.3 Temperature of pump room. Suitable means shall be provided for maintaining the temperature of a pump room or pump house, where required, above 5°C. Engine manufacturer’s recommendation. Temperature of the pump room, pump house or area where engines are installed shall never be less than the minimum recommended by the engine manufacturer. The engine manufacturer’s recommendations for oil heaters shall be followed. 7.13.3.1 7.13.4 SBC 801 Valve supervision. Where provided, the fire pump suction, discharge and bypass valves, and the isolation valves on the backflow prevention device or assembly shall be supervised open by one of the following methods: 1. Central-station, proprietary, or remote-station signaling service. 2. Local signaling service that will cause the sounding of an audible signal at a constantly attended location. 2007 7/60 FIRE PROTECTION SYSTEMS 3. Locking valves open. 4. Sealing of valves and approved weekly recorded inspection where valves are located within fenced enclosures under the control of the owner. 7.13.5 7.13.5.1 7.13.5.2 7.13.5.3 7.13.5.4 SBC 801 Testing and maintenance. Fire pumps shall be inspected, tested and maintained in accordance with the requirements of this section and NFPA 25. Acceptance test. Acceptance testing shall be done in accordance with the requirements of NFPA 20. Generator sets. Engine generator sets supplying emergency or standby power to fire pump assemblies shall be periodically tested in accordance with NFPA 110. Transfer switches. Automatic transfer switches shall be periodically tested in accordance with NFPA 110. Pump room environmental conditions. Tests of pump room environmental conditions, including heating, ventilation and illumination shall be made to ensure proper manual or automatic operation of the associated equipment. 2007 7/61 MEANS OF EGRESS CHAPTER 8 MEANS OF EGRESS SECTION 8.1 GENERAL 8.1.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this chapter shall control the design, construction and arrangement of means of egress components required to provide an approved means of egress from structures and portions thereof. Sections 8.3 through 8.25 shall apply to new construction. Sections 8.26 and 8.27 shall apply to existing buildings. Exception: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories above grade plane in height with a separate means of egress and their accessory structures shall not be considered in this Chapter. 8.1.2 Minimum requirements. It shall be unlawful to alter a building or structure in a manner that will reduce the number of exits or the capacity of the means of egress to less than required by these code requirements. SECTION 8.2 DEFINITIONS 8.2.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in these code requirements, have the meanings shown herein. ACCESSIBLE MEANS OF EGRESS. A continuous and unobstructed way of egress travel from any point in a building or facility that provides an accessible route to an area of refuge, a horizontal exit or a public way. AISLE ACCESSWAY. That portion of an exit access that leads to an aisle. ALTERNATING TREAD DEVICE. A device that has a series of steps between 50 and 70 degrees (0.87 and 1.22 rad) from horizontal, usually attached to a center support rail in an alternating manner so that the user does not have both feet on the same level at the same time. AREA OF REFUGE. An area where persons unable to use stairways can remain temporarily to await instructions or assistance during emergency evacuation. BLEACHERS. Tiered seating facilities. COMMON PATH OF EGRESS TRAVEL. That portion of exit access which the occupants are required to traverse before two separate and distinct paths of egress travel to two exits are available. Paths that merge are common paths of travel. Common paths of egress travel shall be included within the permitted travel distance. SBC 801 2007 8/1 MEANS OF EGRESS CORRIDOR. An enclosed exit access component that defines and provides a path of egress travel to an exit. DOOR, BALANCED. A door equipped with double-pivoted hardware so designed as to cause a semicounter balanced swing action when opening. EGRESS COURT. A court or yard which provides access to a public way for one or more exits. EMERGENCY ESCAPE AND RESCUE OPENING. An operable window, door or other similar device that provides for a means of escape and access for rescue in the event of an emergency. EXIT. That portion of a means of egress system which is separated from other interior spaces of a building or structure by fire-resistance-rated construction and opening protectives as required to provide a protected path of egress travel between the exit access and the exit discharge. Exits include exterior exit doors at ground level, exit enclosures, exit passageways, exterior exit stairs, exterior exit ramps and horizontal exits. EXIT ACCESS. That portion of a means of egress system that leads from any occupied portion of a building or structure to an exit. EXIT DISCHARGE. That portion of a means of egress system between the termination of an exit and a public way. EXIT DISCHARGE, LEVEL OF. The horizontal plane located at the point at which an exit terminates and an exit discharge begins. EXIT ENCLOSURE. An exit component that is separated from other interior spaces of a building or structure by fire-resistance-rated construction and opening protectives, and provides for a protected path of egress travel in a vertical or horizontal direction to the exit discharge or the public way. EXIT, HORIZONTAL. A path of egress travel from one building to an area in another building on approximately the same level, or a path of egress travel through or around a wall or partition to an area on approximately the same level in the same building, which affords safety from fire and smoke from the area of incidence and areas communicating therewith. EXIT PASSAGEWAY. An exit component that is separated from all other interior spaces of a building or structure by fire-resistance-rated construction and opening protectives, and provides for a protected path of egress travel in a horizontal direction to the exit discharge or the public way. FIRE EXIT HARDWARE. Panic hardware that is listed for use on fire door assemblies. FLOOR AREA, GROSS. The floor area within the inside perimeter of the exterior walls of the building under consideration, exclusive of vent shafts and courts, without deduction for corridors, stairways, closets, the thickness of interior SBC 801 2007 8/2 MEANS OF EGRESS walls, columns or other features. The floor area of a building, or portion thereof, not provided with surrounding exterior walls shall be the usable area under the horizontal projection of the roof or floor above. The gross floor area shall not include shafts with no openings or interior courts. FLOOR AREA, NET. The actual occupied area not including unoccupied accessory areas such as corridors, stairways, toilet rooms, mechanical rooms and closets. FOLDING AND TELESCOPIC SEATING. Tiered seating facilities having an overall shape and size that are capable of being reduced for purposes of moving or storing. GRANDSTAND. Tiered seating facilities. GUARD. A building component or a system of building components located at or near the open sides of elevated walking surfaces that minimizes the possibility of a fall from the walking surface to a lower level. HANDRAIL. A horizontal or sloping rail intended for grasping by the hand for guidance or support. MEANS OF EGRESS. A continuous and unobstructed path of vertical and horizontal egress travel from any occupied portion of a building or structure to a public way. A means of egress consists of three separate and distinct parts: the exit access, the exit and the exit discharge. NOSING. The leading edge of treads of stairs and of landings at the top of stairway flights. OCCUPANT LOAD. The number of persons for which the means of egress of a building or portion thereof is designed. PANIC HARDWARE. A door-latching assembly incorporating a device that releases the latch upon the application of a force in the direction of egress travel. PUBLIC WAY. A street, alley or other parcel of land open to the outside air leading to a street, that has been deeded, dedicated or otherwise permanently appropriated to the public for public use and which has a clear width and height of not less than 3.1 m. RAMP. A walking surface that has a running slope steeper than one unit vertical in 20 units horizontal (5 percent slope). SCISSOR STAIR. Two interlocking stairways providing two separate paths of egress located within one stairwell enclosure. SMOKE-PROTECTED ASSEMBLY SEATING. Seating served by means of egress that is not subject to smoke accumulation within or under a structure. STAIR. A change in elevation, consisting of one or more risers. SBC 801 2007 8/3 MEANS OF EGRESS STAIRWAY. One or more flights of stairs, either exterior or interior, with the necessary landings and platforms connecting them, to form a continuous and uninterrupted passage from one level to another. STAIRWAY, EXTERIOR. A stairway that is open on at least one side, except for required structural columns, beams, handrails and guards. The adjoining open areas shall be either yards, courts or public ways. The other sides of the exterior stairway need not be open. STAIRWAY, INTERIOR. A stairway not meeting the definition of an exterior stairway. STAIRWAY, SPIRAL. A stairway having a closed circular form in its plan view with uniform section-shaped treads attached to and radiating from a minimumdiameter supporting column. WINDER. A tread with nonparallel edges. SECTION 8.3 GENERAL MEANS OF EGRESS 8.3.1 Applicability. The general requirements specified in Sections 8.3 through 8.12 shall apply to all three elements of the means of egress system, in addition to those specific requirements for the exit access, the exit and the exit discharge detailed elsewhere in this chapter. 8.3.2 Ceiling height. The means of egress shall have a ceiling height of not less than 2.1 m. Exceptions: 1. Sloped ceilings in accordance with Section 7.8.2 of the SBC 201. 2. Ceilings of dwelling units and sleeping units within residential occupancies in accordance with Section 7.8.2 of the SBC 201. 3. Allowable projections in accordance with Section 8.3.3. 4. Stair headroom in accordance with Section 8.9.2. 5. Door height in accordance with Section 8.8.1.1. 8.3.3 Protruding objects. Protruding objects shall comply with the requirements of Sections 8.3.3.1 through 8.3.3.4. Headroom. Protruding objects are permitted to extend below the minimum ceiling height required by Section 8.3.2 provided a minimum headroom of 2 m shall be provided for any walking surface, including walks, corridors, aisles and passageways. Not more than 50 percent of the ceiling area of a means of egress shall be reduced in height by protruding objects. Exception: Door closers and stops shall not reduce headroom to less than 2.0 m. A barrier shall be provided where the vertical clearance is less than 2.1 m high. The leading edge of such a barrier shall be located 685 mm maximum above the floor. Free-standing objects. A free-standing object mounted on a post or pylon shall not overhang that post or pylon more than 300 mm where the lowest point of the leading edge is more than 685 mm and less than 2.1 m above the walking surface. Where a sign or other obstruction is mounted between posts or pylons and the clear distance between the posts or pylons is greater than 300 mm, the lowest edge 8.3.3.1 8.3.3.2 SBC 801 2007 8/4 MEANS OF EGRESS 8.3.3.3 8.3.3.4 of such sign or obstruction shall be 685 mm maximum or 2.1 m minimum above the finish floor or ground. Exception: This requirement shall not apply to sloping portions of handrails serving stairs and ramps. Horizontal projections. Structural elements, fixtures or furnishings shall not project horizontally from either side more than 100 mm over any walking surface between the heights of 685 mm and 2 m above the walking surface. Exception: Handrails serving stairs and ramps are permitted to protrude 114 mm from the wall. Clear width. Protruding objects shall not reduce the minimum clear width of accessible routes as required in Section 9.4 of the SBC 201. 8.3.4 Floor surface. Walking surfaces of the means of egress shall have a slip-resistant surface and be securely attached. 8.3.5 Elevation change. Where changes in elevation of less than 300 mm exist in the means of egress, sloped surfaces shall be used. Where the slope is greater than one unit vertical in 20 units horizontal (5 percent slope), ramps complying with Section 8.10 shall be used. Where the difference in elevation is 150 mm or less, the ramp shall be equipped with either handrails or floor finish materials that contrast with adjacent floor finish materials. Exceptions: 1. A single step with a maximum riser height of 180 mm is permitted for buildings with occupancies in Groups F, H, R-2 and R-3 as applicable in Chapter 2, and Groups S and U at exterior doors not required to be accessible by Chapter 9 of the SBC 201. 2. A stair with a single riser or with two risers and a tread is permitted at locations not required to be accessible by Chapter 9 of the SBC 201, provided that the risers and treads comply with Section 8.9.3, the minimum depth of the tread is 330 mm and at least one handrail complying with Section 8.9.11 is provided within 760 mm of the centerline of the normal path of egress travel on the stair. 3. An aisle serving seating that has a difference in elevation less than 300 mm is permitted at locations not required to be accessible by Chapter 9 of the SBC 201, provided that the risers and treads comply with Section 8.24.11 and the aisle is provided with a handrail complying with Section 8.24.13. Any change in elevation in a corridor serving nonambulatory persons in a Group I2 occupancy shall be by means of a ramp or sloped walkway. 8.3.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this shall not be diminished along the path of egress travel. 8.3.7 Elevators, escalators and moving walks. Elevators, escalators and moving walks shall not be used as a component of a required means of egress from any other part of the building. Exception: Elevators used as an accessible means of egress in accordance with Section 8.7.4. SBC 801 2007 8/5 MEANS OF EGRESS SECTION 8.4 OCCUPANT LOAD 8.4.1 8.4.1.1 8.4.1.2 8.4.1.3 Design occupant load. In determining means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be established by the largest number computed in accordance with Sections 8.4.1.1 through 8.4.1.3. Actual number. The actual number of occupants for whom each occupied space, floor or building is designed. Number by Table 8.4.1.2. The number of occupants computed at the rate of one occupant per unit of area as prescribed in Table 8.4.1.2. Number by combination. Where occupants from accessory spaces egress through a primary area, the calculated occupant load for the primary space shall include the total occupant load of the primary space plus the number of occupants egressing through it from the accessory space. 8.4.2 Increased occupant load. The occupant load permitted in any building or portion thereof is permitted to be increased from that number established for the occupancies in Table 8.4.1.2 provided that all other requirements of the code are also met based on such modified number and the occupant load shall not exceed 2 one occupant per 0.47 m of occupiable floor space. Where required by the building code official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building code official, such diagram shall be posted. 8.4.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. 8.4.4 Exiting from multiple levels. Where exits serve more than one floor, only the occupant load of each floor considered individually shall be used in computing the required capacity of the exits at that floor, provided that the exit capacity shall not decrease in the direction of egress travel. 8.4.5 Egress convergence. Where means of egress from floors above and below converge at an intermediate level, the capacity of the means of egress from the point of convergence shall not be less than the sum of the two floors. 8.4.6 Mezzanine levels. The occupant load of a mezzanine level with egress onto a room or area below shall be added to that room or area’s occupant load, and the capacity of the exits shall be designed for the total occupant load thus established. 8.4.7 Fixed seating. For areas having fixed seats and aisles, the occupant load shall be determined by the number of fixed seats installed therein. For areas having fixed seating without dividing arms, the occupant load shall not be less than the number of seats based on one person for each 450 mm of seating length. The occupant load of seating booths shall be based on one person for each 600 mm of booth seat length measured at the backrest of the seating booth. SBC 801 2007 8/6 MEANS OF EGRESS TABLE 8.4.1.2 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT FLOOR AREA IN SQ. METER. OCCUPANCY PER OCCUPANT Agricultural building 28 gross Aircraft hangars 47 gross Airport terminal Baggage claim 1.9 gross Baggage handling 28 gross Concourse 9.3 gross Waiting areas 1.4 gross Assembly Gaming floors (keno, slots, etc.) 1 gross Assembly with fixed seats See Section 8.3.2.2.9 Assembly without fixed seats Concentrated (chairs only—not fixed) 0.65 net Standing space 0.47 net Unconcentrated (tables and chairs) 1.4 net Bowling centers, allow 5 persons for each lane including 15 feet of runway, and for additional areas 0.65 net Business areas 9.3 gross Courtrooms—other than fixed seating areas 3.7 net Dormitories 4.7 gross Educational Classroom area 1.9 net Shops and other vocational room areas 4.7 net Exercise rooms 4.7 gross H-5 Fabrication and manufacturing areas 18.6 gross Industrial areas 9.3 gross Institutional areas Inpatient treatment areas 22.3 gross Outpatient areas 9.3 gross Sleeping areas 11.2 gross Kitchens, commercial 18.6 gross Library Reading rooms 4.7 net Stack area 9.3 gross Locker rooms 4.7 gross Mercantile Areas on other floors 5.6 gross Basement and grade floor areas 2.8 gross Storage, stock, shipping areas 28 gross Parking garages 18.6 gross Residential 18.6 gross Skating rinks, swimming pools Rink and pool 4.7 gross Decks 1.4 gross Stages and platforms 1.4 net Accessory storage areas, mechanical equipment room 28 gross Warehouses 47 gross SBC 801 2007 8/7 MEANS OF EGRESS 8.4.8 Outdoor areas. Yards, patios, courts and similar outdoor areas accessible to and usable by the building occupants shall be provided with means of egress as required by this chapter. The occupant load of such outdoor areas shall be assigned by the building code official in accordance with the anticipated use. Where outdoor areas are to be used by persons in addition to the occupants of the building, and the path of egress travel from the outdoor areas passes through the building, means of egress requirements for the building shall be based on the sum of the occupant loads of the building plus the outdoor areas. Exceptions: 1. Outdoor areas used exclusively for service of the building need only have one means of egress. 2. Both outdoor areas associated with Group R-3 and individual dwelling units of Group R-2, as applicable in Section 8.1.1. 8.4.9 Multiple occupancies. Where a building contains two or more occupancies, the means of egress requirements shall apply to each portion of the building based on the occupancy of that space. Where two or more occupancies utilize portions of the same means of egress system, those egress components shall meet the more stringent requirements of all occupancies that are served. SECTION 8.5 EGRESS WIDTH Minimum required egress width. The means of egress width shall not be less than required by this section. The total width of means of egress in millimeters shall not be less than the total occupant load served by the means of egress multiplied by the factors in Table 8.5.1 and not less than specified elsewhere in these code requirements. Multiple means of egress shall be sized such that the loss of any one means of egress shall not reduce the available capacity to less than 50 percent of the required capacity. The maximum capacity required from any story of a building shall be maintained to the termination of the means of egress. Exception: Means of egress complying with Section 8.24. 8.5.1 TABLE 8.5.1 EGRESS WIDTH PER OCCUPANT SERVED OCCUPANCY Occupancies other than those listed below Hazardous: H-1, H-2, H-3 and H-4 Institutional: I-2 a. WITHOUT SPRINKLER SYSTEM Other egress components Stairways (mm (mm per occupant) per occupant) WITH SPRINKLER SYSTEMa Other egress components Stairways (mm per (mm per occupant) occupant) 7.6 5.1 5.1 3.8 17.8 10.2 7.6 5.1 Not Applicable Not Applicable 7.6 5.1 Buildings equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. 8.5.2 SBC 801 Door encroachment. Doors opening into the path of egress travel shall not reduce the required width to less than one-half during the course of the swing. When fully open, the door shall not project more than 180 mm into the required width. 2007 8/8 MEANS OF EGRESS Exception: The restrictions on a door swing shall not apply to doors within individual dwelling units and sleeping units of Group R-2 and dwelling units of Group R-3. SECTION 8.6 MEANS OF EGRESS ILLUMINATION 8.6.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies. 8.6.2 Illumination level. The means of egress illumination level shall not be less than 11 lux at the floor level. Exception: For auditoriums, theaters, concert or opera halls and similar assembly occupancies, the illumination at the floor level is permitted to be reduced during performances to not less than 2.15 lux provided that the required illumination is automatically restored upon activation of a premise’s fire alarm system where such system is provided. 8.6.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise’s electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Exit access corridors, passageways and aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors and exit stairways located in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 8.23.1, in buildings required to have two or more exits. 5. The portion of the exterior exit discharge immediately adjacent to exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 5D.4. 8.6.4 Performance of system. Emergency lighting facilities shall be arranged to provide initial illumination that is at least an average of 11 lux and a minimum at any point of 1 lux measured along the path of egress at floor level. Illumination levels shall be permitted to decline to 6 lux average and a minimum at any point of 0.6 lux at the end of the emergency lighting time duration. A maximum-tominimum illumination uniformity ratio of 40 to 1 shall not be exceeded. SBC 801 2007 8/9 MEANS OF EGRESS SECTION 8.7 ACCESSIBLE MEANS OF EGRESS 8.7.1 Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress is required by Section 8.14.1 or 8.18.1 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress. Exceptions: 1. Accessible means of egress are not required in alterations to existing buildings. 2. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 8.7.3 or 8.7.4. 3. In assembly spaces with sloped floors, one accessible means of egress is required from a space where the common path of travel of the accessible route for access to the wheelchair spaces meets the requirements in Section 8.24.9. 8.7.2 Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components: 1. Accessible routes complying with Section 9.4 of the SBC 201. 2. Stairways within exit enclosures complying with Sections 8.7.3 and 8.19.1. 3. Elevators complying with Section 8.7.4. 4. Platform lifts complying with Section 8.7.5. 5. Horizontal exits. 6. Smoke barriers. Exceptions: 1. Where the exit discharge is not accessible, an exterior area for assisted rescue must be provided in accordance with Section 8.7.8. 2. Where the exit stairway is open to the exterior, the accessible means of egress shall include either an area of refuge in accordance with Section 8.7.6 or an exterior area for assisted rescue in accordance with Section 8.7.8. Buildings with four or more stories. In buildings where a required accessible floor is four or more stories above or below a level of exit discharge, at least one required accessible means of egress shall be an elevator complying with Section 8.7.4. Exceptions: 1. In buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2, the elevator shall not be required on floors provided with a horizontal exit and located at or above the level of exit discharge. 2. In buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2, the elevator shall not be required on floors provided with a ramp conforming to the provisions of Section 8.10. 8.7.2.1 8.7.3 SBC 801 Enclosed exit stairways. An enclosed exit stairway, to be considered part of an accessible means of egress, shall have a clear width of 1.2 m minimum between handrails and shall either incorporate an area of refuge within an enlarged floorlevel landing or shall be accessed from either an area of refuge complying with Section 8.7.6 or a horizontal exit. 2007 8/10 MEANS OF EGRESS Exceptions: 1. Open exit stairways as permitted by Section 8.19.1 are permitted to be considered part of an accessible means of egress. 2. The area of refuge is not required at open stairways that are permitted by Section 8.19.1 in buildings or facilities that are equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1. 3. The clear width of 1.2 m between handrails and the area of refuge is not required at exit stairways in buildings or facilities equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. 4. The clear width of 1.2 m between handrails is not required for enclosed exit stairways accessed from a horizontal exit. 5. Areas of refuge are not required at exit stairways serving open parking garages. 8.7.4 Elevators. An elevator to be considered part of an accessible means of egress shall comply with the emergency operation and signaling device requirements of Section 2.27 of ASME A17.1. Standby power shall be provided in accordance with SBC 401 and 501. The elevator shall be accessed from either an area of refuge complying with Section 8.7.6 or a horizontal exit. Exceptions: 1. Elevators are not required to be accessed from an area of refuge or horizontal exit in open parking garages. 2. Elevators are not required to be accessed from an area of refuge or horizontal exit in buildings and facilities equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. 8.7.5 Platform lifts. Platform (wheelchair) lifts shall not serve as part of an accessible means of egress, except where allowed as part of a required accessible route in Section 9.9.7 of the SBC 201. Platform lifts in accordance with SBC 401 shall be installed in accordance with ASME A18.1. Standby power shall be provided in accordance with Section 5D.4.2 for platform lifts permitted to serve as part of a means of egress. 8.7.6 Areas of refuge. Every required area of refuge shall be accessible from the space it serves by an accessible means of egress. The maximum travel distance from any accessible space to an area of refuge shall not exceed the travel distance permitted for the occupancy in accordance with Section 8.15.1. Every required area of refuge shall have direct access to an enclosed stairway complying with Sections 8.7.3 and 8.19.1 or an elevator complying with Section 8.7.4. Where an elevator lobby is used as an area of refuge, the shaft and lobby shall comply with Section 8.19.1.8 for smokeproof enclosures except where the elevators are in an area of refuge formed by a horizontal exit or smoke barrier. Size. Each area of refuge shall be sized to accommodate one wheelchair space of 760 mm by 1200 mm for each 200 occupants or portion thereof, based on the occupant load of the area of refuge and areas served by the area of refuge. Such wheelchair spaces shall not reduce the required means of egress width. Access to any of the required wheelchair spaces in an area of refuge shall not be obstructed by more than one adjoining wheelchair space. 8.7.6.1 SBC 801 2007 8/11 MEANS OF EGRESS 8.7.6.2 8.7.6.3 8.7.6.4 8.7.6.5 Separation. Each area of refuge shall be separated from the remainder of the story by a smoke barrier complying with Section 4B.9. Each area of refuge shall be designed to minimize the intrusion of smoke. Exceptions: 1. Areas of refuge located within a stairway enclosure. 2. Areas of refuge where the area of refuge and areas served by the area of refuge are equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1 or 7.3.3.1.2. Two-way communication. Areas of refuge shall be provided with a two-way communication system between the area of refuge and a central control point. If the central control point is not constantly attended, the area of refuge shall also have controlled access to a public telephone system. Location of the central control point shall be approved by the Civil Defense. The two-way communication system shall include both audible and visible signals. Instructions. In areas of refuge that have a two-way emergency communications system, instructions on the use of the area under emergency conditions shall be posted adjoining the communications system. The instructions shall include all of the following: 1. Directions to find other means of egress. 2. Persons able to use the exit stairway do so as soon as possible, unless they are assisting others. 3. Information on planned availability of assistance in the use of stairs or supervised operation of elevators and how to summon such assistance. 4. Directions for use of the emergency communications system. Identification. Each door providing access to an area of refuge from an adjacent floor area shall be identified by a sign complying with ICC A117.1 stating: AREA OF REFUGE, and including the Saudi Symbol of Accessibility. Where exit sign illumination is required by Section 8.11.2, the area of refuge sign shall be illuminated. Additionally, tactile signage complying with ICC A117.1 shall be located at each door to an area of refuge. 8.7.7 Signage. At exits and elevators serving a required accessible space but not providing an approved accessible means of egress, signage shall be installed indicating the location of accessible means of egress. 8.7.8 Exterior area for assisted rescue. The exterior area for assisted rescue must be open to the outside air and meet the requirements of Section 8.7.6.1. Separation walls shall comply with the requirements of Section 4B.4 for exterior walls. Where walls or openings are between the area for assisted rescue and the interior of the building, the building exterior walls within 3.1 m horizontally of a nonrated wall or unprotected opening shall be constructed as required for a minimum 1-hour fireresistance rating with 3/4-hour opening protectives. This construction shall extend vertically from the ground to a point 3.1 m above the floor level of the area for assisted rescue or to the roof line, whichever is lower. Openness. The exterior area for assisted rescue shall be at least 50 percent open, and the open area above the guards shall be so distributed as to minimize the accumulation of smoke or toxic gases. Exterior exit stairway. Exterior exit stairways that are part of the means of egress for the exterior area for assisted rescue shall provide a clear width of 1.2 m between handrails. 8.7.8.1 8.7.8.2 SBC 801 2007 8/12 MEANS OF EGRESS 8.7.8.3 Identification. Exterior areas for assisted rescue shall have identification as required for area of refuge that complies with Section 8.7.6.5. SECTION 8.8 DOORS, GATES AND TURNSTILES 8.8.1 8.8.1.1 8.8.1.1.1 8.8.1.2 SBC 801 Doors. Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 8.17.2. Doors provided for egress purposes in numbers greater than required by these code requirements shall meet the requirements of this section. Means of egress doors shall be readily distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors. Mirrors or similar reflecting materials shall not be used on means of egress doors. Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials. Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 800 mm. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees (1.57 rad). Where this section requires a minimum clear width of 800 mm and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 800 mm. The maximum width of a swinging door leaf shall be 1.2 m nominal. Means of egress doors in an occupancy in Group I-2 used for the movement of beds shall provide a clear width not less than 1.1 m. The height of doors shall not be less than 2.1 m. Exceptions: 1. The minimum and maximum width shall not apply to door openings that are not part of the required means of egress in occupancies in Groups R-2 and R-3 as applicable in Chapter 2. 2. Door openings to resident sleeping units in occupancies in Group I-3 shall have a clear width of not less than 710 mm. 2 3. Door openings to storage closets less than 0.9 m in area shall not be limited by the minimum width. 4. Width of door leafs in revolving doors that comply with Section 8.8.1.3.1 shall not be limited. 5. Door openings within a dwelling unit or sleeping unit shall not be less than 2.0 m in height. 6. Exterior door openings in dwelling units and sleeping units, other than the required exit door, shall not be less than 2.0 m in height. 7. Interior egress doors within a dwelling unit or sleeping unit which is not required to be adaptable or accessible. 8. Door openings required to be accessible within Type B dwelling units shall have a minimum clear width of 800 mm. Projections into clear width. There shall not be projections into the required clear width lower than 860 mm above the floor or ground. Projections into the clear opening width between 860 mm and 2.1 m above the floor or ground shall not exceed 100 mm. Door swing. Egress doors shall be side-hinged swinging. Exceptions: 1. Private garages, office areas, factory and storage areas with an occupant load of 10 or less. 2007 8/13 MEANS OF EGRESS 8.8.1.3 8.8.1.3.1 2. Group I-3 occupancies used as a place of detention. 3. Doors within or serving a single dwelling unit in Groups R-2 and R-3 as applicable in Chapter 2. 4. In other than Group H occupancies, revolving doors complying with Section 8.8.1.3.1. 5. In other than Group H occupancies, horizontal sliding doors complying with Section 8.8.1.3.3 are permitted in a means of egress. 6. Power-operated doors in accordance with Section 8.8.1.3.1. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. The opening force for interior side-swinging doors without closers shall not exceed a 22 N force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a 67 N force. The door shall be set in motion when subjected to a 133 N force. The door shall swing to a full-open position when subjected to a 67 N force. Forces shall be applied to the latch side. Special doors. Special doors and security grilles shall comply with the requirements of Sections 8.8.1.3.1 through 8.8.1.3.5. Revolving doors. Revolving doors shall comply with the following: 1. Each revolving door shall be capable of collapsing into a bookfold position with parallel egress paths providing an aggregate width of 900 mm. 2. A revolving door shall not be located within 3.1 m of the foot of or top of stairs or escalators. A dispersal area shall be provided between the stairs or escalators and the revolving doors. 3. The revolutions per minute (rpm) for a revolving door shall not exceed those shown in Table 8.8.1.3.1. 4. Each revolving door shall have a side-hinged swinging door which complies with Section 8.8.1 in the same wall and within 3.1 m of the revolving door. TABLE 8.8.1.3.1 REVOLVING DOOR SPEEDS INSIDE DIAMETER (mm) 1,980 2,130 2,290 2,440 2,590 2,740 2,896 3,050 8.8.1.3.1.1 SBC 801 POWER-DRIVENTYPE SPEED CONTROL (rpm) 11 10 9 9 8 8 7 7 MANUAL-TYPE SPEED CONTROL (rpm) 12 11 11 10 9 9 8 8 Egress component. A revolving door used as a component of a means of egress shall comply with Section 8.8.1.3.1 and the following three conditions: 1. Revolving doors shall not be given credit for more than 50 percent of the required egress capacity. 2. Each revolving door shall be credited with no more than a 50-person capacity. 3. Each revolving door shall be capable of being collapsed when a force of not more than 578 N is applied within 76 mm of the outer edge of a wing. 2007 8/14 MEANS OF EGRESS 8.8.1.3.1.2 Other than egress component. A revolving door used as other than a component of a means o f egress shall comply with Section 8.8.1.3.1. The collapsing force of a revolving door not used as a component of a means of egress shall not be more than 801 N. Exception: A collapsing force in excess of 801 N is permitted if the collapsing force is reduced to not more than 578 N when at least one of the following conditions is satisfied: 1. There is a power failure or power is removed to the device holding the door wings in position. 2. There is an actuation of the automatic sprinkler system where such system is provided. 3. There is an actuation of a smoke detection system which is installed in accordance with Section 7.7 to provide coverage in areas within the building which are within 23.0 m of the revolving doors. 4. There is an actuation of a manual control switch, in an approved location and clearly defined, which reduces the holding force to below the 578 N force level. 8.8.1.3.2 Power-operated doors. Where means of egress doors are operated by power, such as doors with a photoelectric-actuated mechanism to open the door upon the approach of a person, or doors with power-assisted manual operation, the design shall be such that in the event of power failure, the door is capable of being opened manually to permit means of egress travel or closed where necessary to safeguard means of egress. The forces required to open these doors manually shall not exceed those specified in Section 8.8.1.2, except that the force to set the door in motion shall not exceed 220 N. The door shall be capable of swinging from any position to the full width of the opening in which such door is installed when a force is applied to the door on the side from which egress is made. Full-poweroperated doors shall comply with BHMA A156.19. Power-assisted and lowenergy doors shall comply with BHMA A156.19. Exceptions: 1. Occupancies in Group I-3. 2. Horizontal sliding doors complying with Section 8.8.1.3.3. 3. For a biparting door in the emergency breakout mode, a door leaf located within a multiple-leaf opening shall be exempt from the minimum 800 mm single-leaf requirement of Section 8.8.1.1, provided a minimum 800 mm clear opening is provided when the two biparting leaves meeting in the center are broken out. 8.8.1.3.3 Horizontal sliding doors. In other than Group H occupancies, horizontal sliding doors permitted to be a component of a means of egress in accordance with Exception 5 to Section 8.8.1.2 shall comply with all of the following criteria: 1. The doors shall be power operated and shall be capable of being operated manually in the event of power failure. 2. The doors shall be openable by a simple method from both sides without special knowledge or effort. 3. The force required to operate the door shall not exceed 133 N to set the door in motion and 67 N to close the door or open it to the minimum required width. 4. The door shall be openable with a force not to exceed 67 N when a force of 1,100 N is applied perpendicular to the door adjacent to the operating device. SBC 801 2007 8/15 MEANS OF EGRESS 8.8.1.3.4 8.8.1.3.5 8.8.1.4 SBC 801 5. The door assembly shall comply with the applicable fire protection rating and, where rated, shall be self closing or automatic-closing by smoke detection, shall be installed in accordance with NFPA 80 and shall comply with Section 4B.15. 6. The door assembly shall have an integrated standby power supply. 7. The door assembly power supply shall be electrically supervised. 8. The door shall open to the minimum required width within 10 seconds after activation of the operating device. Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 1.0 m to 1.2 m vertically above the floor and within 1.5 m of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads: PUSH TO EXIT. When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. Security grilles. In Groups B, F, M and S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. Where two or more means of egress are required, not more than one-half of the exits or exit access doorways shall be equipped with horizontal sliding or vertical security grilles. Floor elevation. There shall be a floor or landing on each side of a door. Such floor or landing shall be at the same elevation on each side of the door. Landings shall be level except for exterior landings, which are permitted to have a slope not to exceed 0.25 unit vertical in 12 units horizontal (2 percent slope). Exceptions: 1. Doors serving individual dwelling units in Groups R-2 and R-3 as applicable in Section 8.1.1 where the following apply: 1.1 A door is permitted to open at the top step of an interior flight of stairs, provided the door does not swing over the top step. 2007 8/16 MEANS OF EGRESS 1.2 8.8.1.5 8.8.1.6 8.8.1.7 8.8.1.8 8.8.1.8.1 8.8.2.8.2 8.8.1.8.3 SBC 801 Screen doors and storm doors are permitted to swing over stairs or landings. 2. Exterior doors as provided for in Section 8.3.5, Exception 1, and Section 8.17.2, which are not on an accessible route. 3. In Group R-3 occupancies, the landing at an exterior doorway shall not be more than 200 mm below the top of the threshold, provided the door, other than an exterior storm or screen door, does not swing over the landing. 4. Variations in elevation due to differences in finish materials, but not more than 12.7 mm. 5. Exterior decks, patios or balconies that are part of Type B dwelling units and have impervious surfaces, and that are not more than 100 mm below the finished floor level of the adjacent interior space of the dwelling unit. Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is the greater. Doors in the fully open position shall not reduce a required dimension by more than 800 mm. When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 1.1 m. Exception: Landing length in the direction of travel in Group R-3 as applicable in Section 8.1.1 and Group U and within individual units of Group R-2 as applicable in Section 8.1.1 need not exceed 900 mm. Thresholds. Thresholds at doorways shall not exceed 19.1 mm in height for sliding doors serving dwelling units or 12.7 mm for other doors. Raised thresholds and floor level changes greater than 6.4 mm at doorways shall be beveled with a slope not greater than one unit vertical in two units horizontal (50 percent slope). Exception: The threshold height shall be limited to 200 mm where the occupancy is Group R-2 or R-3 as applicable in Section 8.1.1, the door is an exterior door that is not a component of the required means of egress and the doorway is not on an accessible route. Door arrangement. Space between two doors in series shall be 1.2 m minimum plus the width of a door swinging into the space. Doors in series shall swing either in the same direction or away from the space between doors. Exceptions: 1. The minimum distance between horizontal sliding power-operated doors in a series shall be 1.2 m. 2. Storm and screen doors serving individual dwelling units in Groups R-2 and R3 as applicable in Section 8.1.1 need not be spaced 1.2 m from the other door. 3. Doors within individual dwelling units in Groups R-2 and R-3 as applicable in Section 8.1.1 other than within Type A dwelling units. Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 9 of the SBC 201 shall not require tight grasping, tight pinching or twisting of the wrist to operate. Hardware height. Door handles, pulls, latches, locks and other operating devices shall be installed 860 mm minimum and 1.2 m maximum above the finished floor. Locks used only for security purposes and not used for normal operation are permitted at any height. Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2007 8/17 MEANS OF EGRESS 8.8.1.8.4 8.8.1.8.5 8.8.1.8.6 SBC 801 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in Mosques, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1 The locking device is readily distinguishable as locked, 2.2 A readily visible durable sign (Arabic and English) is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 25 mm high on a contrasting background, 2.3 The use of the key-operated locking device is revocable by the building code official for due cause. 3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware. 4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool. Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Exceptions: 1. On doors not required for egress in individual dwelling units or sleeping units. 2. Where a pair of doors serves a storage or equipment room, manually operated edge or surface-mounted bolts are permitted on the inactive leaf. Unlatching. The unlatching of any leaf shall not require more than one operation. Exception: More than one operation is permitted for unlatching doors in the following locations: 1. Places of detention or restraint. 2. Where manually operated bolt locks are permitted by Section 8.8.1.8.4. 3. Doors with automatic flush bolts as permitted by Section 8.8.1.8.3, Exception 3. 4. Doors from individual dwelling units and guestrooms of Group R occupancies as permitted by Section 8.8.1.8.3, Exception 4. Delayed egress locks. Approved, listed, delayed egress locks shall be permitted to be installed on doors serving any occupancy except Group A, E and H occupancies in buildings that are equipped throughout with an automatic sprinkler system in accordance with Section 7.3.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 7.7, provided that the doors unlock in accordance with Items 1 through 6 below. A building occupant shall not be required to pass through more than one door equipped with a delayed egress lock before entering an exit. 1. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system. 2. The doors unlock upon loss of power controlling the lock or lock mechanism. 3. The door locks shall have the capability of being unlocked by a signal from the fire command center. 4. The initiation of an irreversible process which will release the latch in not more than 15 seconds when a force of not more than 67 N is applied for 1 second to the release device. Initiation of the irreversible process shall activate an audible signal in the vicinity of the door. Once the door lock has been 2007 8/18 MEANS OF EGRESS 8.8.1.8.7 8.8.1.9 8.8.2 8.8.2.1 8.8.3 SBC 801 released by the application of force to the releasing device, relocking shall be by manual means only. Exception: Where approved, a delay of not more than 30 seconds is permitted. 5. A sign (Arabic and English) shall be provided on the door located above and within 300 mm of the release device reading: PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS. 6. Emergency lighting shall be provided at the door. Stairway doors. Interior stairway means of egress doors shall be openable from both sides without the use of a key or special knowledge or effort. Exceptions: 1. Stairway discharge doors shall be openable from the egress side and shall only be locked from the opposite side. 2. This section shall not apply to doors arranged in accordance with Section 2B.3.12. 3. In stairways serving not more than four stories, doors are permitted to be locked from the side opposite the egress side, provided they are openable from the egress side. Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. A maximum unlatching force of 67 N. Each door in a means of egress from an occupancy of Group A or E having an occupant load of 100 or more and any occupancy of Group H-1, H-2, H-3 or H-5 shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than one-half the width of the door measured from the latch side. Gates. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors. Exception: Horizontal sliding or swinging gates exceeding the 1.2 m maximum leaf width limitation are permitted in fences and walls surrounding a stadium. Stadiums. Panic hardware is not required on gates surrounding stadiums where such gates are under constant immediate supervision while the public is present, 2 and further provided that safe dispersal areas based on 0.28 m per occupant are located between the fence and enclosed space. Such required safe dispersal areas shall not be located less than 15.3 m from the enclosed space. See Section 8.17 for means of egress from safe dispersal areas. Turnstiles. Turnstiles or similar devices that restrict travel to one direction shall not be placed so as to obstruct any required means of egress. Exception: Each turnstile or similar device shall be credited with no more than a 50-person capacity where all of the following provisions are met: 1. Each device shall turn free in the direction of egress travel when primary power is lost, and upon the manual release by an employee in the area. 2. Such devices are not given credit for more than 50 percent of the required egress capacity. 3. Each device is not more than 1.0 m high. 2007 8/19 MEANS OF EGRESS 8.8.3.1 8.8.3.2 4. Each device has at least 400 mm clear width at and below a height of 1.0 m and at least 560 mm clear width at heights above 1.0 m. Where located as part of an accessible route, turnstiles shall have at least 900 mm clear at and below a height of 860 mm, at least 800 mm clear width between 860 mm and 2.1 m and shall consist of a mechanism other than a revolving device. High turnstile. Turnstiles more than 1.0 m high shall meet the requirements for revolving doors. Additional door. Where serving an occupant load greater than 300, each turnstile that is not portable shall have a side-hinged swinging door which conforms to Section 8.8.1 within 15.3 m. SECTION 8.9 STAIRWAYS AND HANDRAILS 8.9.1 Stairway width. The width of stairways shall be determined as specified in Section 8.5.1, but such width shall not be less than 1.1 m. See Section 8.7.3 for accessible means of egress stairways. Exceptions: 1. Stairways serving an occupant load of 50 or less shall have a width of not less than 900 mm. 2. Spiral stairways as provided for in Section 8.9.9. 3. Aisle stairs complying with Section 8.24. 4. Where a stairway lift is installed on stairways serving occupancies in Group R3, or within dwelling units in occupancies in Group R-2, both as applicable in Section 8.1.1 a clear passage width not less than 500 mm shall be provided. If the seat and platform can be folded when not in use, the distance shall be measured from the folded position. 8.9.2 Headroom. Stairways shall have a minimum headroom clearance of 2.1 m measured vertically from a line connecting the edge of the no sings. Such headroom shall be continuous above the stairway to the point where the line intersects the landing below, one tread depth beyond the bottom riser. The minimum clearance shall be maintained the full width of the stairway and landing. Exception: Spiral stairways complying with Section 8.9.9 are permitted a 2.0 m headroom clearance. 8.9.3 Stair treads and risers. Stair riser heights shall be 180 mm maximum and 100 mm minimum. Stair tread depths shall be 280 mm minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 9.5 mm. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at right angle to the tread’s leading edge. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 9.5 mm. Winder treads shall have a minimum tread depth of 0.28 m measured at a right angle to the tread’s leading edge at a point 300 mm from the side where the treads are narrower and a minimum tread depth of 0.25 m. The greatest winder tread depth at the 300 mm walk line within any flight of stairs shall not exceed the smallest by more than 9.5 mm. Exceptions: 1. Circular stairways in accordance with Section 8.9.7. 2. Winders in accordance with Section 8.9.8. SBC 801 2007 8/20 MEANS OF EGRESS 8.9.3.1 8.9.3.2 8.9.4 SBC 801 3. Spiral stairways in accordance with Section 8.9.9. 4. Aisle stairs in assembly seating areas where the stair pitch or slope is set, for sightline reasons, by the slope of the adjacent seating area in accordance with Section 8.24.11.2. 5. In occupancies in Group R-3, as applicable in Section 8.1.1, within dwelling units in occupancies in Group R-2, as applicable in Section 8.1.1, and in occupancies in Group U, which are accessory to an occupancy in Group R-3, as applicable in Section 8.1.1, the maximum riser height shall be 200 mm and the minimum tread depth shall be 250 mm, the minimum winder tread depth at the walk line shall be 250 mm, and the minimum winder tread depth shall be 150 mm. A nosing not less than 19 mm but not more than 32 mm shall be provided on stairways with solid risers where the tread depth is less than 300 mm. 6. See the Chapter 9 for the replacement of existing stairways. Dimensional uniformity. Stair treads and risers shall be of uniform size and shape. The tolerance between the largest and smallest riser or between the largest and smallest tread shall not exceed 9.5 mm in any flight of stairs. Exceptions: 1. Non-uniform riser dimensions of aisle stairs complying with Section 8.24.11.2. 2. Consistently shaped winders, complying with Section 8.9.8, differing from rectangular treads in the same stairway flight. Where the bottom or top riser adjoins a sloping public way, walkway or driveway having an established grade and serving as a landing, the bottom or top riser is permitted to be reduced along the slope to less than 100 mm in height with the variation in height of the bottom or top riser not to exceed one unit vertical in 12 units horizontal (8 percent slope) of stairway width. The no sings or leading edges of treads at such non-uniform height risers shall have a distinctive marking stripe, different from any other nosing marking provided on the stair flight. The distinctive marking stripe shall be visible in descent of the stair and shall have a slip-resistant surface. Marking stripes shall have a width of at least 25 mm but not more than 50 mm. Profile. The radius of curvature at the leading edge of the tread shall be not greater than 12.7 mm. Beveling of no sings shall not exceed 12.7 mm. Risers shall be solid and vertical or sloped from the under-side of the leading edge of the tread above at an angle not more than 30 degrees (0.52 rad) from the vertical. The leading edge (no sings) of treads shall project not more than 30 mm beyond the tread below and all projections of the leading edges shall be of uniform size, including the leading edge of the floor at the top of a flight. Exceptions: 1. Solid risers are not required for stairways that are not required to comply with Section 8.7.3, provided that the opening between treads does not permit the passage of a sphere with a diameter of 100 mm. 2. Solid risers are not required for occupancies in Group I-3. Stairway landings. There shall be a floor or landing at the top and bottom of each stairway. The width of landings shall not be less than the width of stairways they serve. Every landing shall have a minimum dimension measured in the direction of travel equal to the width of the stairway. Such dimension need not exceed 1.2 m where the stairway has a straight run. 2007 8/21 MEANS OF EGRESS Exceptions: 1. Aisle stairs complying with Section 8.24. 2. Doors opening onto a landing shall not reduce the landing to less than one-half the required width. When fully open, the door shall not project more than 180 mm into a landing. 8.9.5 8.9.5.1 8.9.5.2 Stairway construction. All stairways shall be built of materials consistent with the types permitted for the type of construction of the building, except that wood handrails shall be permitted for all types of construction. Stairway walking surface. The walking surface of treads and landings of a stairway shall not be sloped steeper than one unit vertical in 48 units horizontal (2 percent slope) in any direction. Stairway treads and landings shall have a solid surface. Finish floor surfaces shall be securely attached. Exception: In Group F, H and S occupancies, other than areas of parking structures accessible to the public, openings in treads and landings shall not be prohibited provided a sphere with a diameter of 29 mm cannot pass through the opening. Outdoor conditions. Outdoor stairways and outdoor approaches to stairways shall be designed so that water will not accumulate on walking surfaces. In other than occupancies in Group R-3, and occupancies in Group U that are accessory to an occupancy in Group R-3, treads, platforms and landings that are part of exterior stairways in climates subject to snow or ice shall be protected to prevent the accumulation of same. 8.9.6 Vertical rise. A flight of stairs shall not have a vertical rise greater than 3.7 m between floor levels or landings. Exception: Aisle stairs complying with Section 8.24. 8.9.7 Circular stairways. Circular stairways shall have a minimum tread depth and a maximum riser height in accordance with Section 8.9.3 and the smaller radius shall not be less than twice the width of the stairway. The minimum tread depth measured 300 mm from the narrower end of the tread shall not be less than 280 mm. The minimum tread depth at the narrow end shall not be less than 250 mm. Exception: For occupancies in Group R-3, and within individual dwelling units in occupancies in Group R-2, both as applicable in Section 8.1.1. 8.9.8 Winders. Winders are not permitted in means of egress stairways except within a dwelling unit. 8.9.9 Spiral stairways. Spiral stairways are permitted to be used as a component in the 2 means of egress only within dwelling units or from a space not more than 23 m in area and serving not more than five occupants, or from galleries, catwalks and gridirons in accordance with Section 8.14.6. A spiral stairway shall have a 190 mm minimum clear tread depth at a point 300 mm from the narrow edge. The risers shall be sufficient to provide a headroom of 2.0 m minimum, but riser height shall not be more than 240 mm. The minimum stairway width shall be 660 mm. 8.9.10 Alternating tread devices. Alternating tread devices are limited to an element of a means of egress in buildings of Groups F, H and S from a mezzanine not more than 23 m2 in area and which serves not more than five occupants; in buildings of SBC 801 2007 8/22 MEANS OF EGRESS 8.9.10.1 8.9.10.2 8.9.11 8.9.11.1 8.9.11.2 8.9.11.3 8.9.11.4 SBC 801 Group I-3 from a guard tower, observation station or control room not more than 23 m2 in area and for access to unoccupied roofs. Handrails of alternating tread devices. Handrails shall be provided on both sides of alternating tread devices and shall conform to Section 8.9.11. Treads of alternating tread devices. Alternating tread devices shall have a minimum projected tread of 125 mm, a minimum tread depth of 215 mm, a minimum tread width of 180 mm and a maximum riser height of 240 mm. The initial tread of the device shall begin at the same elevation as the platform, landing or floor surface. Exception: Alternating tread devices used as an element of a means of egress in buildings from a mezzanine area not more than 23 m2 in area which serves not more than five occupants shall have a minimum projected tread of 215 mm with a minimum tread depth of 270 mm. The rise to the next alternating tread surface should not be more than 200 mm. Handrails. Stairways shall have handrails on each side. Handrails shall be adequate in strength and attachment in accordance with Section 2.7 of SBC 301. Handrails for ramps, where required by Section 8.10.8, shall comply with this section. Exceptions: 1. Aisle stairs complying with Section 8.24 provided with a center handrail need not have additional handrails. 2. Stairways within dwelling units, spiral stairways and aisle stairs serving seating only on one side are permitted to have a handrail on one side only. 3. Decks, patios and walkways that have a single change in elevation where the landing depth on each side of the change of elevation is greater than what is required for a landing do not require handrails. 4. In Group R-3 occupancies, a change in elevation consisting of a single riser at an entrance or egress door does not require handrails. 5. Changes in room elevations of only one riser within dwelling units and sleeping units in Group R-2 and R-3 occupancies do not require handrails. Height. Handrail height, measured above stair tread nosings, or finish surface of ramp slope, shall be uniform, not less than 860 mm and not more than 960 mm. Intermediate handrails. Intermediate handrails are required so that all portions of the stairway width required for egress capacity are within 750 mm of a handrail. On monumental stairs, handrails shall be located along the most direct path of egress travel. Handrail graspability. Handrails with a circular cross section shall have an outside diameter of at least 32 mm and not greater than 50 mm or shall provide equivalent graspability. If the handrail is not circular, it shall have a perimeter dimension of at least 100 mm and not greater than 160 mm with a maximum cross-section dimension of 55 mm. Edges shall have a minimum radius of 0.25 mm. Continuity. Handrail-gripping surfaces shall be continuous, without interruption by newel posts or other obstructions. Exceptions: 1. Handrails within dwelling units are permitted to be interrupted by a newel post at a stair landing. 2. Within a dwelling unit, the use of a volute, turnout or starting easing is allowed on the lowest tread. 3. Handrail brackets or balusters attached to the bottom surface of the handrail 2007 8/23 MEANS OF EGRESS 8.9.11.5 8.9.11.6 8.9.11.7 8.9.12 8.9.12.1 that do not project horizontally beyond the sides of the handrail within 38 mm of the bottom of the handrail shall not be considered to be obstructions and provided further that for each 13 mm of additional handrail perimeter dimension above 100 mm, the vertical clearance dimension of 38 mm shall be permitted to be reduced by 3 mm. Handrail extensions. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight. Where handrails are not continuous between flights, the handrails shall extend horizontally at least 300 mm beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser. Exceptions: 1. Handrails within a dwelling unit that is not required to be accessible need extend only from the top riser to the bottom riser. 2. Aisle handrails in Group A occupancies in accordance with Section 8.24.13. Clearance. Clear space between a handrail and a wall or other surface shall be a minimum of 38 mm. A handrail and a wall or other surface adjacent to the handrail shall be free of any sharp or abrasive elements. Stairway projections. Projections into the required width at each handrail shall not exceed 114 mm at or below the handrail height. Projections into the required width shall not be limited above the minimum headroom height required in Section 8.9.2. Stairway to roof. In buildings four or more stories in height above grade, one stairway shall extend to the roof surface, unless the roof has a slope steeper than four units vertical in 12 units horizontal (33 percent slope). In buildings without an occupied roof, access to the roof from the top story shall be permitted to be by an alternating tread device. Roof access. Where a stairway is provided to a roof, access to the roof shall be provided through a penthouse complying with Section 6.9.2 of SBC 201. Exception: In buildings without an occupied roof, access to the roof shall be permitted to be a roof hatch or trap door not less than 1.5 m2 in area and having a minimum dimension of 600 mm. SECTION 8.10 RAMPS 8.10.1 Scope. The provisions of this section shall apply to ramps used as a component of a means of egress. Exceptions: 1. Other than ramps that are part of the accessible routes providing access in accordance with Sections 9.8.2.2 through 9.8.2.4.1 of the SBC 201, ramped aisles within assembly rooms or spaces shall conform with the provisions in Section 8.24.11. 2. Curb ramps shall comply with ICC A117.1. 3. Vehicle ramps in parking garages for pedestrian exit access shall not be required to comply with Sections 8.10.3 through 8.10.9 when they are not an accessible route serving accessible parking spaces, other required accessible elements or part of an accessible means of egress. 8.10.2 Slope. Ramps used as part of a means of egress shall have a running slope not steeper than one unit vertical in 12 units horizontal (8 percent slope). The slope of SBC 801 2007 8/24 MEANS OF EGRESS other ramps shall not be steeper than one unit vertical in eight units horizontal (12.5 percent slope). Exception: Aisle ramp slope in occupancies of Group A shall comply with Section 8.24.11. 8.10.3 Cross slope. The slope measured perpendicular to the direction of travel of a ramp shall not be steeper than one unit vertical in 48 units horizontal (2 percent slope). 8.10.4 Vertical rise. The rise for any ramp run shall be 750 mm maximum. 8.10.5 Minimum dimensions. The minimum dimensions of means of egress ramps shall comply with Sections 8.10.5.1 through 8.10.5.3. Width. The minimum width of a means of egress ramp shall not be less than that required for corridors by Section 8.16.2. The clear width of a ramp and the clear width between handrails, if provided, shall be 900 mm minimum. Headroom. The minimum headroom in all parts of the means of egress ramp shall not be less than 2.1 meters. Restrictions. Means of egress ramps shall not reduce in width in the direction of egress travel. Projections into the required ramp and landing width are prohibited. Doors opening onto a landing shall not reduce the clear width to less than 1.1 meters. 8.10.5.1 8.10.5.2 8.10.5.3 8.10.6 8.10.6.1 8.10.6.2 8.10.6.3 8.10.6.4 8.10.6.5 8.10.7 8.10.7.1 8.10.7.2 SBC 801 Landings. Ramps shall have landings at the bottom and top of each ramp, points of turning, entrance, exits and at doors. Landings shall comply with Sections 8.10.6.1 through 8.10.6.5. Slope. Landings shall have a slope not steeper than one unit vertical in 48 units horizontal (2 percent slope) in any direction. Changes in level are not permitted. Width. The landing shall be at least as wide as the widest ramp run adjoining the landing. Length. The landing length shall be 1.5 m minimum. Exception: Landings in non-accessible Group R-2 and R-3 individual dwelling units, as applicable in SBC 100 are permitted to be 900 mm minimum. Change in direction. Where changes in direction of travel occur at landings provided between ramp runs, the landing shall be 1.5 m by 1.5 m minimum. Exception: Landings in non-accessible Group R-2 and R-3 individual dwelling units, as applicable in SBC 100 are permitted to be 900 mm by 900 mm minimum. Doorways. Where doorways are located adjacent to a ramp landing, maneuvering clearances required by ICC A117.1 are permitted to overlap the required landing area. Ramp construction. All ramps shall be built of materials consistent with the types permitted for the type of construction of the building; except that wood handrails shall be permitted for all types of construction. Ramps used as an exit shall conform to the applicable requirements of Sections 8.19.1 and 8.19.1.1 through 8.19.1.3 for vertical exit enclosures. Ramp surface. The surface of ramps shall be of slip-resistant materials that are securely attached. Outdoor conditions. Outdoor ramps and outdoor approaches to ramps shall be designed so that water will not accumulate on walking surfaces. In other than occupancies in Group R-3, and occupancies in Group U that are accessory to an occupancy in Group R-3, surfaces and landings which are part of exterior ramps in 2007 8/25 MEANS OF EGRESS climates subject to snow or ice shall be designed to minimize the accumulation of same. 8.10.8 Handrails. Ramps with a rise greater than 150 mm shall have handrails on both sides complying with Section 8.9.11. 8.10.9 Edge protection. Edge protection complying with Section 8.10.9.1 or 8.10.9.2 shall be provided on each side of ramp runs and at each side of ramp landings. Exceptions: 1. Edge protection is not required on ramps not required to have handrails, provided they have flared sides that comply with the ICC A117.1 curb ramp provisions. 2. Edge protection is not required on the sides of ramp landings serving an adjoining ramp run or stairway. 3. Edge protection is not required on the sides of ramp landings having a vertical drop-off of not more than 13 mm within 250 mm horizontally of the required landing area. Railings. A rail shall be mounted below the handrail 430 mm to 480 mm above the ramp or landing surface. Curb or barrier. A curb or barrier shall be provided that prevents the passage of a 100 mm sphere, where any portion of the sphere is within 100 mm of the floor or ground surface. 8.10.9.1 8.10.9.2 8.10.10 Guards. Guards shall be provided where required by Section 8.12 and shall be constructed in accordance with Section 8.12. SECTION 8.11 EXIT SIGNS 8.11.1 SBC 801 Where required. Exits and exit access doors shall be marked by an approved exit bilingual sign (Arabic and English) readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 30.5 meters or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Exceptions: 1. Exit bilingual signs (Arabic and English) are not required in rooms or areas which require only one exit or exit access. 2. Main exterior exit doors or gates which obviously and clearly are identifiable as exits need not have exit signs where approved by the concerned building official. 3. Exit signs are not required in occupancies in Group U and individual sleeping units or dwelling units in Group R-1, R-2 or R-3. 4. Exit signs are not required in sleeping areas in occupancies in Group I-3. 5. In occupancies in Groups A-4 and A-5, exit signs are not required on the seating side of vomitories or openings into seating areas where exit signs are provided in the concourse that are readily apparent from the vomitories. Egress lighting is provided to identify each vomitory or opening within the seating area in an emergency. 2007 8/26 MEANS OF EGRESS 8.11.2 Illumination. Exit signs shall be internally or externally illuminated. Exception: Tactile signs required by Section 8.11.3 need not be provided with illumination. 8.11.3 Tactile exit signs. A tactile bilingual sign (Arabic and English) stating EXIT and complying with ICC A117.1 shall be provided adjacent to each door to an egress stairway, an exit passageway and the exit discharge. 8.11.4 Internally illuminated exit signs. Internally illuminated exit signs shall be listed and labeled and shall be installed in accordance with the manufacturer’s instructions, Section 5D.4 and SBC 401 exit signs shall be illuminated at all times. 8.11.5 Externally illuminated exit signs. Externally illuminated exit signs shall comply with Sections 8.11.5.1 through 8.11.5.3. Graphics. Every exit sign and directional exit sign shall have plainly legible letters not less than 150 mm high with the principal strokes of the letters not less than 19 mm wide. The word “EXIT” shall be bilingual (Arabic and English) and have letters having a width not less than 50 mm wide except the letter “I,” and the minimum spacing between letters shall not be less than 9.5 mm. Signs larger than the minimum established in this section shall have letter widths, strokes and spacing in proportion to their height. The word “EXIT” shall be in high contrast with the background and shall be clearly discernible when the exit sign illumination means is or is not energized. If an arrow is provided as part of the exit sign, the construction shall be such that the arrow direction cannot be readily changed. Exit sign illumination. The face of an exit sign illuminated from an external source shall have an intensity of not less than 54 lux. Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with SBC 401. Exception: Approved exit sign illumination means that provide continuous illumination independent of external power sources for a duration of not less than 90 minutes, in case of primary power loss, are not required to be connected to an emergency electrical system. 8.11.5.1 8.11.5.2 8.11.5.3 SECTION 8.12 GUARDS 8.12.1 SBC 801 Where required. Guards shall be located along open-sided walking surfaces, mezzanines, industrial equipment platforms, stairways, ramps and landings which are located more than 750 mm above the floor or grade below. Guards shall be adequate in strength and attachment in accordance with SBC 301. Guards shall also be located along glazed sides of stairways, ramps and landings that are located more than 750 mm above the floor or grade below where the glazing provided does not meet the strength and attachment requirements in SBC 301. Exception: Guards are not required for the following locations: 1. On the loading side of loading docks or piers. 2. On the audience side of stages and raised platforms, including steps leading 2007 8/27 MEANS OF EGRESS up to the stage and raised platforms. 3. On raised stage and platform floor areas such as runways, ramps and side stages used for entertainment or presentations. 4. At vertical openings in the performance area of stages and platforms. 5. At elevated walking surfaces appurtenant to stages and platforms for access to and utilization of special lighting or equipment. 6. Along vehicle service pits not accessible to the public. 7. In assembly seating where guards in accordance with Section 8.24.14 are permitted and provided. 8.12.2 Height. Guards shall form a protective barrier not less than 1.1 meters high, measured vertically above the leading edge of the tread, adjacent walking surface or adjacent seatboard. Exceptions: 1. For occupancies in Group R-3, and within individual dwelling units in occupancies in Group R-2, both as applicable in SBC 100 guards whose top rail also serves as a handrail shall have a height not less than 860 mm and not more than 960 mm measured vertically from the leading edge of the stair tread nosing. 2. The height in assembly seating areas shall be in accordance with Section 8.24.14. 8.12.3 Opening limitations. Open guards shall have balusters or ornamental patterns such that a 100 mm sphere cannot pass through any opening up to a height of 860 mm. From a height of 860 mm to 1070 mm above the adjacent walking surfaces, a sphere 200 mm in diameter shall not pass. Exceptions: 1. The triangular openings formed by the riser, tread and bottom rail at the open side of a stairway shall be of a maximum size such that a sphere of 150 mm in diameter cannot pass through the opening. 2. At elevated walking surfaces for access to and use of electrical, mechanical or plumbing systems or equipment, guards shall have balusters or be of solid materials such that a sphere with a diameter of 530 mm cannot pass through any opening. 3. In areas which are not open to the public within occupancies in Group I-3, F, H or S, balusters, horizontal intermediate rails or other construction shall not permit a sphere with a diameter of 530 mm to pass through any opening. 4. In assembly seating areas, guards at the end of aisles where they terminate at a fascia of boxes, balconies and galleries shall have balusters or ornamental patterns such that a 100 mm-diameter sphere cannot pass through any opening up to a height of 660 mm. From a height of 660 mm to 1070 mm above the adjacent walking surfaces, a sphere 200 mm in diameter shall not pass. 8.12.4 Screen porches. Porches and decks which are enclosed with insect screening shall be provided with guards where the walking surface is located more than 750 mm above the floor or grade below. 8.12.5 Mechanical equipment. Guards shall be provided where appliances, equipment, fans or other components that require service are located within 3 meters of a roof edge or open side of a walking surface and such edge or open side is located more SBC 801 2007 8/28 MEANS OF EGRESS than 750 mm above the floor, roof or grade below. The guard shall be constructed so as to prevent the passage of a 530 mm-diameter sphere. SECTION 8.13 EXIT ACCESS 8.13.1 General. The exit access arrangement shall comply with Sections 8.13 through 8.16 and the applicable provisions of Sections 8.3 through 8.12. 8.13.2 Egress through intervening spaces. Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served; are not a high-hazard occupancy and provide a discernible path of egress travel to an exit. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. An exit access shall not pass through a room that can be locked to prevent egress. Means of egress from dwelling units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms. Exceptions: 1. Means of egress are not prohibited through a kitchen area serving adjoining rooms constituting part of the same dwelling unit or sleeping unit. 2. Means of egress are not prohibited through adjoining or intervening rooms or spaces in a Group H occupancy when the adjoining or intervening rooms or spaces are the same or a lesser hazard occupancy group. Multiple tenants. Where more than one tenant occupies any one floor of a building or structure, each tenant space, dwelling unit and sleeping unit shall be provided with access to the required exits without passing through adjacent tenant spaces, dwelling units and sleeping units. Group I-2. Habitable rooms or suites in Group I-2 occupancies shall have an exit access door leading directly to an exit access corridor. Exceptions: 1. Rooms with exit doors opening directly to the outside at ground level. 2. Patient sleeping rooms are permitted to have one intervening room if the intervening room is not used as an exit access for more than eight patient beds. 3. Special nursing suites are permitted to have one intervening room where the arrangement allows for direct and constant visual supervision by nursing personnel. 4. For rooms other than patient sleeping rooms, suites of rooms are permitted to have one intervening room if the travel distance within the suite to the exit access door is not greater than 30.5 m and are permitted to have two intervening rooms where the travel distance within the suite to the exit access door is not greater than 15.3 m. 2 Suites of sleeping rooms shall not exceed 465 m . Suites of rooms, other than 2 patient sleeping rooms, shall not exceed 929 m . Any patient sleeping room, or any 2 suite that includes patient sleeping rooms, of more than 93 m shall have at least two exit access doors remotely located from each other. Any room or suite of rooms, other than patient sleeping rooms, of more than 232 m2 shall have at least two access doors remotely located from each other. The travel distance between any point in a Group I-2 occupancy and an exit access door in the room shall not exceed 15.3 m. The travel distance between any point in a suite of sleeping rooms and an exit access door of that suite shall not exceed 30.5 m. 8.13.2.1 8.13.2.2 SBC 801 2007 8/29 MEANS OF EGRESS 8.13.3 Common path of egress travel. In occupancies other than Groups H-1, H-2 and H-3, the common path of egress travel shall not exceed 23 m. In occupancies in Groups H-1, H-2, and H-3, the common path of egress travel shall not exceed 7.6 m. Exceptions: 1. The length of a common path of egress travel in an occupancy in Groups B, F and S shall not be more than 30.5 m, provided that the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 7.3.3.1.1. 2. Where a tenant space in an occupancy in Groups B, S and U has an occupant load of not more than 30, the length of a common path of egress travel shall not be more than 30.5 m. 3. The length of a common path of egress travel in occupancies in Group I-3 shall not be more than 30.5 m. 8.13.4 Aisles. Aisles serving as a portion of the exit access in the means of egress system shall comply with the requirements of this section. Aisles shall be provided from all occupied portions of the exit access which contain seats, tables, furnishings, displays and similar fixtures or equipment. Aisles serving assembly areas, other than seating at tables, shall comply with Section 8.24. Aisles serving reviewing stands, grandstands and bleachers shall also comply with Section 8.24. The required width of aisles shall be unobstructed. Exception: Doors, when fully opened, and handrails shall not reduce the required width by more than 180 mm. Doors in any position shall not reduce the required width by more than one-half. Other nonstructural projections such as trim and similar decorative features are permitted to project into the required width 38 mm from each side. Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 8.5.1 for the occupant load served, but shall not be less than 900 mm. Exception: Nonpublic aisles serving less than 50 people, and not required to be accessible by Chapter 9 need not exceed 710 mm in width. Seating at tables. Where seating is located at a table or counter and is adjacent to an aisle or aisle access way, the measurement of required clear width of the aisle or aisle accessway shall be made to a line 480 mm away from and parallel to the edge of the table or counter. The 480 mm distance shall be measured perpendicular to the side of the table or counter. In the case of other side boundaries for aisle or aisle access ways, the clear width shall be measured to walls, edges of seating and tread edges, except that handrail projections are permitted. Exception: Where tables or counters are served by fixed seats, the width of the aisle accessway shall be measured from the back of the seat. Aisle accessway for tables and seating. Aisle accessways serving arrangements of seating at tables or counters shall have sufficient clear width to conform to the capacity requirements of Section 8.5.1 but shall not have less than the appropriate minimum clear width specified in Section 8.13.4.1. Table and seating accessway width. Aisle accessways shall provide a minimum of 300 mm of width plus 12.7 mm of width for each additional 0.3 m, or fraction thereof, beyond 3.7 m of aisle accessway length measured from the center of the seat farthest from an aisle. Exception: Portions of an aisle accessway having a length not exceeding 1.8 m and used by a total of not more than four persons. 8.13.4.1 8.13.4.2 8.13.4.2.1 8.13.4.2.2 SBC 801 2007 8/30 MEANS OF EGRESS 8.13.4.2.3 Table and seating aisle accessway length. The length of travel along the aisle accessway shall not exceed 9.1 m from any seat to the point where a person has a choice of two or more paths of