TAG DCP-1 TP-2 WH-1,2 XT-1 PLUMBING FIXTURE SCHEDULE MINIMUM ROUGH IN CONNECTION SIZE SPECIFICATION CW HW DRAIN COMMENTS ELECTRIC TAG - TRAP PRIMER, ELECTRONIC: PPP MODEL DTS-4 MOUNTED CABINET WITH PRIME COAT ACCESS DOOR, FOUR TRAP PRIMER LINE OUTLETS. 1/2" WATER HEATER: HTP PHOENIX PH199-119, COMMERCIAL WATER HEATER. 119 GAL, STAINLESS STEEL TANK, MODULATING BURNER, NATURAL GAS FIRED, 237 GPH RECOVERY @ 100° F RISE. PROVIDE ACID NEUTRALIZATION KIT. 3/4" EXPANSION TANK: AMTROL THERM-X-TROL. ST-12C-DD, 6.4 GALLON, 3/4"NPT CONNECTION 3/4" 3/4" 3/4" - - - 3/4" OUT 120V, 6W TRAP PRIMER, SURFACE T&P RELIEF VALVE 208V, 4 KW, 33.3AMPS - - - 3 YEARS COMMERCIAL TANK WARRANTY. NEUTRALIZATION KIT, PIPE IW TO MOP RECEPTOR SEE DETAIL 2/P3.0. SET AT 140°F. MASS APPROVAL CODE P3-0818-56 GAS INPUT (CFH) EQUIPMENT SERVED PIPE LENGTH (LF) FITTING EQUIVALENT LENGTH (LF) TOTAL EQUIVALENT LENGTH (LF) GAS PIPE SIZE RTU-1 GAS ROOFTOP UNIT 350 75' 65' 140' 2" BRANCH MAINS GUH-1 GAS UNIT HEATER 260 80' 60' 140' 11/4" BRANCH GUH-2 GAS UNIT HEATER 260 80' 60' 140' 11/4" BRANCH GUH-3 GAS UNIT HEATER 260 75' 50' 125' 11/4" BRANCH GUH-4 GAS UNIT HEATER 260 125' 50' 175' 11/4" BRANCH ERU-1 GAS ENERGY RECOVERY UNIT 125 70' 50' 120' 1" BRANCH WH-1 WATER HEATER 199 120' 50' 170' 11/4" BRANCH WH-2 WATER HEATER 199 120' 50' 170' 11/4" BRANCH 1,913 125' 50' 175' 4" MAIN HEADER TOTAL LONGEST RUN IS TO GUH-1 LAV-1 3.2 GALLON ACCEPTANCE VOLUME GAS EQUIPMENT LOAD & SIZING SCHEDULE TAG TMV-1 LEONARD POINT OF USE THERMOSTATIC MIXING VALVE MODEL 170-LF-BP-CP CHROME PLATED BRASS FINISH, LEAD FREE. MINIMUM 0.25 GPM, MAXIMUM 4.0 GPM AT 5 PSI DROP MAX. MB-1 MOP SINK: FIAT SBC3636 MOLDED STONE MOP RECEPTOR COMPLETE WITH 830AA SERVICE SINK FAUCET, 889CC MOP HANGER BRACKET, 1239BB ALUMINUM BUMPERGUARD WITH VINYL INSERT AND MSG3636 WALL GUARD PLUMBING SPECIALTIES SCHEDULE MINIMUM ROUGH IN CONNECTION SIZE SPECIFICATION CW HW S OR W V COMMENTS BFP-1 BACKFLOW PREVENTER: WATTS 2" LF009-QT CAST COPPER, LEAD-FREE, W/ QUARTER TURN BALL VALVES. 2" - - - MAIN WATER ENTRANCE BFP-2 BACKFLOW PREVENTER: WATTS 1" LF009-QT CAST COPPER, LEAD-FREE, W/ QUARTER TURN BALL VALVES. 1" - - - WATER SERVICE COFFEE KIOSK HOSE BIBB: CHICAGO FAUCET 952-1/2CP HOSE BIBB WITH ATMOSPHERIC VACCUM BREAKER, 1/2" NPT FEMALE THREADED INLET,3/4" MALE HOSE THREAD OUTLET AND TEE HANDLE. 1/ " 2 HB-A - FD-B FLOOR DRAIN : WATTS FD-100-B-7 CAST IRON FLOOR DRAIN WITH HEAVY DUTY NICKEL BRONZE STRAINER AND TRAP PRIMER CONNECTION - FS-1 FLOOR SINK: ZURN ZN1900-P-2 CAST IRON FLOOR SINK, 12"x12"x6" DEEP LIGHT DUTY NB GRATE AND RIM, HALF GRATE, ACID RESISTANT COATING, TRAP PRIMER CONNECTION, ALUMINUM BUCKET - WCO WALL CLEANOUT: ZURN Z1441 WALL CLEANOUT PLUG WITH COVER FCO FLOOR CLEANOUT : WATTS CO20 CAST IRON ADJUSTABLE FLOOR CLEANOUT W/ ROUND TOP GCO GRADE CLEANOUT: ZURN Z1400-S-VP CAST IRON ON-GRADE FLOOR CLEANOUT FD-A - - WB-1 WASHING MACHINE BOX: GUY GRAY MODEL BB200TS GALVANIZED STEEL 1/ " 2 WATER SUPPLY BOX: WATER-TITE 87978 SQUARE WATER OUTLET BOX WITH LEAD FREE QUARTER TURN VALVE WITH ARRESTER. PROVIDE BRAIDED S.S. CONNECTOR. 1/ " 2 TP-1 TRAP PRIMER: PRECISION PLUMBING PRODUCTS PRO1-ULP500 LEAD FREE 1/ " 2 WH-1 ELECTRIC WATER HEATER: A.O. SMITH DURA-POWER DEL20 COMMERCIAL ELECTRIC WATER HEATER, 20 GALLON, 150 PSI WORKING PRESSURE, HIGH DENSITY ANODE ROD, GLASSLINED, ZINC PLATED COPPER SHEATH HEATING ELEMENT, THERMOSTAT AND HIGH TEMPERATURE CUTOFF SWITCH, BACKED ENAMEL OUTER JACKET, FOAM INSULATION. 18GPH @ 90° RISE. HOLDRITE 50-SWHP-WM . WALL-HUNG PLATFORM 26-1/2″X26-1/2″X2-1/2″, STEEL DRAIN - PROVIDE P-TRAP WITH TRAP PRIMER CONNECTION 2" REFER TO PLANS REFER TO PLANS SK-2 - 4" 1-11 FIXTURE UNITS, BASED ON PDI STANDARDS 3/ " 4 3/4" SK-1 PROVIDE 1/2" CW TRAP PRIMER WATER LINE CONNECTION TO FLOOR DRAIN. 2" 3" - PROVIDE 1/2" CW TRAP PRIMER WATER LINE CONNECTION TO FLOOR DRAIN. 2" 3" - PROVIDE (1) HB EACH MOUNTED 1'-6" AFF UNDER THE LAV OF THE MEN'S AND WOMEN'S ROOMS. - 2" - - SHOCK ABSORBER / WATER HAMMER ARRESTOR: ZURN Z-1700-100 SHOKTROL WATER HAMMER ARRESTOR. WSB-1 - - SA-1 - SH-2 1/ " 2 11/2" 2" - - T&P RELIEF VALVE 3/4" OUT - UR-1 SEE DETAIL 6/P3.01 208V, 4 KW, 33.3AMPS 3 YEARS COMMERCIAL TANK WARRANTY. NEUTRALIZATION KIT, PIPE IW TO MOP RECEPTOR SEE DETAIL 2/P3.0. SET AT 140°F. MASS APPROVAL CODE P3-0818-56 WC-1 & WC-3 NOTES: 1. REFER TO ARCHITECTURAL FLOOR PLANS AND INTERIOR ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT OF EACH FIXTURE. WC-2 SPECIALTY EQUIPMENT SCHEDULE MINIMUM ROUGH IN CONNECTION SIZE EQUIP TAG EQUIPMENT QTY CW CWF (FILTERED) 03 COFFEE MAKER 2 X 04 ESPRESSO MAKER 1 X 05 RESTAURANT COFFEE MAKER 2 08 COMMERCIAL DISHWASHER 3 10 ICE MAKER, UNDERCOUNTER 1 15 GLASS WASHER 1 20 WASHER 1 HW HW (125°F) (140°F) S OR W (DIRECT) IW VENT GAS COMMENTS SHOWER: AKER BY MAAX MODEL 141402-L ACRYLIC ALCOVE ONE-PIECE TRANSFER SHOWER W/CENTER DRAIN, TEXTURED BOTTOM, GRAB BARS, AND FOLD-UP L-SHAPED SEAT. COMES COMPLETE WITH CHROME PRESSURE BALANCE MIXING VALVE WITH HAND-HELD SHOWER, CHROME 24" SLIDE BAR AND 60" FLEXIBLE HOSE. PROVIDE WEIGHTED CURTAIN ROD, SHOWER CURTAIN, HEAVY DUTY S.S. OR CHROME BRASS ROLLER SHOWER CURTAIN RINGS. PROVIDE VINYL COLLAPSIBLE DAM AND BRASS SHOWER DRAIN. COMPONENTS SHALL BE METAL AND NONMETALLIC CONSTRUCTION, PLATED IN STANDARD POLISHED CHROME FINISH. SHOWER: AKER BY MAAX MODEL 141402-L ACRYLIC ALCOVE ONE-PIECE TRANSFER SHOWER W/CENTER DRAIN, TEXTURED BOTTOM, GRAB BARS, AND FOLD-UP L-SHAPED SEAT. COMES COMPLETE WITH CHROME PRESSURE BALANCE MIXING VALVE WITH HAND-HELD SHOWER, CHROME 24" SLIDE BAR AND 60" FLEXIBLE HOSE. PROVIDE WEIGHTED CURTAIN ROD, SHOWER CURTAIN, HEAVY DUTY S.S. OR CHROME BRASS ROLLER SHOWER CURTAIN RINGS. PROVIDE VINYL COLLAPSIBLE DAM AND BRASS SHOWER DRAIN. COMPONENTS SHALL BE METAL AND NONMETALLIC CONSTRUCTION, PLATED IN STANDARD POLISHED CHROME FINISH. HAND WASH SINK: ELKAY LUSTERTONE MODEL LRADQ172055 CLASSIC STAINLESS STEEL 17"x20", SINGLE BOWL DROP-IN SINK. SINK IS MANUFACTURED FROM 18 GAUGE 304 STAINLESS STEEL WITH A LUSTROUS SATIN FINISH, REAR CENTER DRAIN PLACEMENT, AND BOTTOM ONLY PADS. SINGLE HOLE CENTERED. ELKAY LK500LGN05T4 SINGLE HOLE DECK MOUNT GOOSENECK SPOUT KITCHEN FAUCET WITH 4" WRISTBLADE HANDLES. FAUCET HAS A FLOW RATE OF 1.5 GPM, AND IS MADE OF SOLID BRASS, WITH A CERAMIC DISC VALVE. FAUCET REQUIRES 1 FAUCET HOLE. PROVIDE LK99 STRAINER. 1/2" x 3/8"CP BRASS STOPS AND SUPPLIES TO SUIT (2). 1-1/2" x 2" CP BRASS P-TRAP TO SUIT. TRUEBRO HANDICAPPED INSULATION KIT. KITCHEN SINK: ELKAY LUSTERTONE MODEL LRADQ332265PD CLASSIC STAINLESS STEEL 33"x22", DOUBLE BOWL DROP-IN SINK. SINK IS MANUFACTURED FROM 18 GAUGE 304 STAINLESS STEEL WITH A LUSTROUS SATIN FINISH, REAR CENTER DRAIN PLACEMENT, AND BOTTOM ONLY PADS. SINGLE HOLE CENTERED. ELKAY LKGT1041CR SINGLE HOLE DECK MOUNT GOURMET KITCHEN FAUCET WITH PULL-OUT SPRAY AND LEVER HANDLE. FAUCET HAS A FLOW RATE OF 1.75 GPM, AND IS MADE OF SOLID BRASS, WITH A CERAMIC DISC VALVE. FAUCET REQUIRES 1 FAUCET HOLE. PROVIDE LK99 STRAINER. 1/2" x 3/8"CP BRASS STOPS AND SUPPLIES TO SUIT (2). 1-1/2" x 2" CP BRASS P-TRAP TO SUIT. TRUEBRO HANDICAPPED URINAL: AMERICAN STANDARD INSULATION PINTBROOK KIT. MODEL 6002.001, WALL MT, WHITE, VITREOUS CHINA TOP SPUD URINAL (.125-0.5 GPF), WITH AMERICAN STANDARD 6063.051.002 HARD WIRED SENSOR OPERATED FLUSH VALVE (0.5 GPF). PROVIDE JAY R SMITH 0635 SERIES STRUCTURAL STEEL URINAL CARRIER COMPLETE WITH ALL REQUIRED HARDWARE TO SUIT. WATER CLOSET: AMERICAN STANDARD AFWALL MODEL 2631.101 WALL-MOUNT, BACK SPUD, ELONGATED, WHITE, VITREOUS CHINA, 1.28 GPF, WITH 5905.100 ELONGATED HEAVY DUTY OPEN FRONT SEAT LESS COVER. WITH SLOAN ROYAL 152 ESS-1.28.TMO-2-10-3/4-LDIM-HW IN WALL SENSOR FLUSHOMETER WITH ACCESS PANEL AND TRUE MECHANICAL OVERRIDE, HARD WIRED AND JAY R. SMITH FIXTURE CARRIER COMPLETE WITH ALL REQUIRED HARDWARE TO SUIT MOUNTING ORIENTATION. WATER CLOSET: AMERICAN STANDARD AFWALL MODEL 2631.101 WALL-MOUNT, BACK SPUD, ELONGATED, WHITE, VITREOUS CHINA, 1.28 GPF, WITH 5905.100 ELONGATED HEAVY DUTY OPEN FRONT SEAT LESS COVER. WITH SLOAN ROYAL 152 ESS-1.28.TMO-2-10-3/4-LDIM-HW IN WALL SENSOR FLUSHOMETER WITH ACCESS PANEL AND TRUE MECHANICAL OVERRIDE, HARD WIRED AND JAY R. SMITH FIXTURE CARRIER COMPLETE WITH ALL REQUIRED HARDWARE TO SUIT MOUNTING ORIENTATION. S OR W COMMENTS MOUNT LAV IN ACCORDANCE WITH ADA FOR HANDICAP REQUIREMENTS. PROVIDE TMV-1 BELOW, SET TO 105 ° F. 1/ " 2 1/ " 2 11/2" TO 2" 11/2" MOUNT LAV IN ACCORDANCE WITH ADA FOR HANDICAP REQUIREMENTS. 1/ " 2 1/ " 2 TO 3/8" 1/ " 2 1/ " 2 11/2" TO 2" TO 3/8" - WITH SHUTOFF, STRAINER, AND IDW HOSE 1/2" 1/2" DRAIN X IDW TO FD PROVIDE WASHER BOX NOTES: 1. ALL EQUIPMENT, FIXTURES AND FAUCETS SHOWN ON THIS SCHEDULE SHALL BE FURNISHED BY THE FOOD SERVICE CONTRACTOR, UNLESS NOTED OTHERWISE. MAJOR EQUIPMENT SHALL BE SET IN PLACE BY THE FOOD SERVICE CONTRACTOR. THE PLUMBING CONTRACTOR SHALL INSTALL ALL PLUMBING RELATED FAUCETS AND HARDWARE. THE PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL ALL REQUIRED TRAPS, SUPPLIES, STOPS, INDIRECT WASTE PIPING AND NECESSARY HARDWARE AS REQUIRED FOR A COMPLETE INSTALLATION. 2. THE PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL THE DOMESTIC WATER HEATER 104V (REFER TO DWH-1 ON PLUMBING EQUIPMENT SCHEDULE). 1 P-1 FLOOR DRAIN RD ROOF DRAIN - WH 1/ " 2 3" BRITISH THERMAL UNIT BTUH BRITISH THERMAL UNITS PER HOUR CO CLEANOUT CFH CUBIC FEET PER HOUR CFM CUBIC FEET PER MINUTE FCO FLOOR CLEANOUT CLG CEILING GCO GRADE CLEANOUT CP CHROME PLATED W&T WASTE AND TRAP (P-TRAP) CO CLEANOUT CTE CONNECT TO EXISTING CW COLD WATER HB WH 1/ " 2 1/ " 2 2" WHA/SA CTE ETBR HOSE BIB DIA DIAMETER DWG DRAWING WALL HYDRANT WATER HAMMER ARRESTOR/SHOCK ABSORBER CONNECT TO EXISTING EXISTING TO BE REMOVED FLOW IN DIRECTION OF ARROW MOUNT SHR AND ALL COMPONENTS IN ACCORDANCE WITH ADA FOR HANDICAP REQUIREMENTS. 1/ " 2 1/ " 2 2" S=.01 S=.02 PITCH IN FEET PER FOOT (1% OR 1/ " 8 PER FOOT) PITCH IN FEET PER FOOT (2% OR 1/ " 4 PER FOOT) STRAINER 11/2" PIPE SLEEVE EXPANSION JOINT MOUNT SINK AND ALL COMPONENTS IN ACCORDANCE WITH ADA FOR HANDICAP REQUIREMENTS. NUM KEY NOTE DESIGNATION HWRP 1/ " 2 1/ " 2 2" 11/2" HOT WATER RECIRC PUMP 1/ " 2 1/ " 2 2" 11/2" TMV S 3/ " 4 - 2" 11/2" MOUNT UR IN ACCORDANCE WITH ADA FOR HANDICAP REQUIREMENTS. RPBP TPV 1" - 4" 2" T MOUNT WC IN ACCORDANCE WITH ADA FOR HANDICAP REQUIREMENTS. 1" - 4" ELEVATION ETR EXISTING TO REMAIN EX EXISTING FFE FINISH FLOOR ELEVATION FLR FLOOR FCO FLOOR CLEANOUT FP FIRE PROTECTION FPM FEET PER MINUTE FW FILTERED WATER FT FOOT GPF GALLON(S) PER FLUSH GPM GALLON(S) PER MINUTE GC GENERAL CONTRACTOR GI GREASE INTERCEPTOR HC HANDICAPPED HP HORSE POWER HW HOT WATER HWR HOT WATER RETURN HZ HERTZ INV INVERT INDIRECT WASTE KW KILOWATTS SHUT-OFF VALVE (BALL VALVE) LPC LIMIT OF PLUMBING CONTRACTOR MBH 1,000 BTU'S PER HOUR MECH MECHANICAL NC NORMALLY CLOSED CHECK VALVE NO NORMALLY OPEN GAS SHUT-OFF VALVE NTS NOT TO SCALE NIC NOT IN CONTRACT OED OPEN END DRAIN BALANCING VALVE PC PLUMBING CONTRACTOR BACK WATER VALVE PH PHASE PLBG PLUMBING PSI THERMOSTATIC MIXING VALVE SOLENOID VALVE OS&Y DOWN EL/ELEV. IW GATE VALVE MOUNT SINK AND ALL COMPONENTS IN ACCORDANCE WITH ADA FOR HANDICAP REQUIREMENTS. DN BOW VENT TRAP PRIMER OUTSIDE SCREW AND YOKE VALVE RPBP REDUCED PRESSURE BACKFLOW PREVENTER RPM POUNDS PER SQUARE INCH REDUCED PRESSURE BACKFLOW PREVENTER REVOLUTIONS PER MINUTE SA SHOCK ABSORBER TEMPERATURE PRESSURE-RELIEF VALVE SS SOIL STACK VACUUM RELIEF VALVE SPEC SPECIFICATION AQUASTAT TP TRAP PRIMER (CW CONNECTION) TYP TYPICAL V VENT VACUUM BREAKER TEMPERATURE GAUGE PRV PRESSURE REDUCING VALVE VB PG PRESSURE GAUGE VS VENT STACK VTR VENT THROUGH ROOF GLOBE VALVE 2" BALANCING STATION VIV VALVE IN VERTICAL W WASTE WC WATER COLUMN WV WET VENT 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 hvac CSI Engineering fire protection This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 MILLION AIR- PEASE EXETER ROAD PORTSMOUTH, NH 03801 Sullivan Construction, LLC. PIPING LEGEND DETAIL DESIGNATION NUMBER DETAIL DESIGNATION DRAWING AG ABOVE GROUND PIPING (SINGLE LINE) BG BELOW GROUND PIPING (DOUBLE LINE) CW COLD WATER PIPING HW HOT WATER PIPING HOT WATER RECIRC PIPING (RETURN) TW TW TEMPERED HOT WATER SUPPLY TW TWR TEMPERED HOT WATER RETURN HOT WATER SUPPLY (140°) 140°F FIXTURE / EQUIPMENT TAG HOT WATER RECIRCULATING (140°) 140°F S,W V 12/1/2022 2:06:48 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt CONTINUATION UNION 11/2" (XX) XX-# COLD WATER FILTERED CONT TEE LOOKING UP POWERED EQUIPMENT DESIGNATION POWERED EQUIPMENT DATA XX CWF CAP ON END OF PIPE 2" MOUNT SHR AND ALL COMPONENTS IN ACCORDANCE WITH ADA FOR HANDICAP REQUIREMENTS. BUILDING BTU TEE LOOKING DOWN 1/ " 2 BELOW FINISHED FLOOR BLDG AREA DRAIN RISER DOWN (ELBOW) HB BFF AD RISER UP (ELBOW) PROVIDE AT EACH LAV-1 AND LAV-2. SET FOR 110° F HOT WATER. ABOVE FINISH FLOOR TRENCH DRAIN HWR XX AFF TD 11/2" DESIGNATION INDICATOR 1/2" FD V NOTES: 1. ROUGH IN SIZES NOTED ARE THE MINIMUM SIZES AS REQUIRED AT THE FIXTURE CONNECTION. PIPE SIZES MAY BE LARGER DEPENDING ON DISTANCE FROM MAINS, PIPING PITCH, VENTING RULES, OTHER CONDITIONS AND LAYOUT, ETC. REFER TO THE FLOOR PLANS FOR SPECIFIC PIPE SIZING. 2. REFER TO ARCHITECTURAL FLOOR PLANS AND INTERIOR ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT OF EACH FIXTURE. 3. ALL VITREOUS CHINA FIXTURES SHALL BE WHITE. ALL FAUCETS SHALL BE CHROME PLATED BRASS UNLESS NOTED OTHERWISE. X X HW ABBREVIATIONS plumbing FLOOR DRAIN : WATTS FD-100-B-7 CAST IRON FLOOR DRAIN WITH HEAVY DUTY NICKEL BRONZE STRAINER AND TRAP PRIMER CONNECTION - LAVATORY: KOHLER K-20000, CAXTON, RECTANGLE UNDER MOUNT BATHROOM SINK, OVERFLOW DRAIN, VITREOUS CHINA, 1281904-7 UNDER MOUNT, COLOR WHITE, 15 11/16" x 20 1/4" x 7 5/16" DEEP . INSTALL IN RECOMMENDED ADA INSTALLATION. BRADLEY S53-3500 VERGE FAUCET- LINE A SERIES, BRUSHED BACK STAINLESS FINISH, TOUCH FREE DUAL SENSOR ACTIVATION, BATTERY, CAST BRASS CONSTRUCTION, STRAIGHT GRID DRAIN ASSEMBLY. MATCHING VERFE DECK MOUNTED SOAP DISPENSER 1/ "x3/ " CP BRASS STOPS AND SUPPLIES TO SUIT 6-3500, TOP FILL. 2 8 1/ " 1CP BRASS TAIL PIECE W/GRID DRAIN AND 1 1/ "x1 1/ " CP (2). 4 2 4 BRASS P-TRAP TO SUIT. TRUEBRO HANDICAPPED INSULATION KIT. LAVATORY: AMERICAN STANDARD MODEL 0475.047 AQUALYN, VITREOUS CHINA, DROP-IN COUNTERTOP OVAL LAVATORY. AMERICAN STANDARD 7755.205 SELECTRONIC BATTERY POWERED SENSOR OPERATED CHROME PLATED BRASS LAV-2 FAUCET, CENTER HOLE. 1/2"x3/8" CP BRASS STOPS AND SUPPLIES TO SUIT (2). 1 1/4" CP BRASS TAIL PIECE W/GRID DRAIN AND 1 1/2"x11/4" CP BRASS P-TRAP TO SUIT. TRUEBRO HANDICAPPED INSULATION KIT. SH-1 TOTAL EQUIVALENT DESIGN LENGTH: 175' DESIGN PRESSURE: LOW PRESSURE .5 PSI (14" WC) MINIMUM PRESSURE REQUIRED: 8" WC MAXIMUM PRESSURE DROP: 0.50" WC SPECIFIC GRAVITY: 0.60 TAG SPECIFICATION CW DOMESTIC HOT WATER RE-CIRCULATING PUMP: TACO 006-BC7-IFC, BRONZE, 3250 RPM. 115V, 1/40 HP, 1 PH, 0.52 A GENERAL LEGEND MINIMUM ROUGH IN CONNECTION SIZE electrical PLUMBING EQUIPMENT SCHEDULE SOIL OR WASTE PIPING VENT ABOVE PIPING RL RW RAIN WATER PIPING (STORM DRAINAGE) ORL ORL OVERFLOW RAIN WATER PIPING (STORM) IW IW INDIRECT WASTE PIPING G G NATURAL GAS PIPING GV GV Scale: Date: Project Number: 1" = 10'-0" 12.02.2022 2021-167 GAS VENT PIPING REVISIONS NO. DESCRIPTION DATE PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION SCHEDULE OF DRAWINGS DWG# COVID 19 SYSTEM QUESTIONS GENERAL NOTE: 1. THE CONTRACTOR SHALL COORDINATE WITH OWNER, BUILDING OCCUPANTS AND CLIENTS MANAGERS FOR ALL REQUIRED COVID-19 SAFETY MEASURES TO BE EMPLOYED AT THE SITE. ALL PROTOCOLS SHALL BE IMPLEMENTED DURING CONSTRUCTION. ALL COVID-19 PROTOCOLS SHALL BE TAKEN INTO CONSIDERATION WHEN SUBMITTING A BID AND NO CHANGE ORDERS WILL BE ISSUED TO COVER SUCH COST, INCLUDING, BUT NOT LIMITED TO EFFECTS ON SCHEDULING OF WORK AND MANPOWER. DRAWING TITLE P0.01 LEGEND, NOTES & ABBREVIATIONS P1.00a UNDERSLAB PLAN - PART A P1.00b UNDERSLAB PLAN - PART B P1.01a GROUND LEVEL FLOOR PLAN - PART A P1.01b GROUND LEVEL FLOOR PLAN - PART B P1.02a SECOND FLOOR PLAN - PART A P1.02b SECOND FLOOR PLAN - PART B P1.03a ROOF PLAN - LOW ROOF P1.03b ROOF PLAN - HANGAR ROOF P2.01 ENLARGED PLANS, NOTES & DETAILS P2.02 ENLARGED PLANS P3.01 DETAILS P4.01 SPECIFICATIONS LEGEND, NOTES & ABBREVIATIONS P0.01 COPYRIGHT C 2022 GENERAL PLUMBING NOTES 1. REFER TO DRAWING P0.01 FOR LEGENDS, ABBREVIATIONS AND GENERAL NOTES. 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com F DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 G CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 G 2 3 4 5 STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 6 H MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 H @ 1/8"/FT 2.81 3.81 hvac 5' HIGH WALLS H.5 2"W UP SEE SITE PLAN FOR CONTINUATION 4"UP TO GCO 00 2"W BY G.C. PORTE COCHÈRE H.1 X 2"V UP UP 2" CW Engineering fire protection 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 3" UP TO FCO MILLION AIR- PEASE 1-1/2"V UP 6" W 1" CW 1" CW UP 3"W&T UP J.2 4" W 1"CW UP 2"CW UP BY G.C. 2"V UP EJ 3"W&T UP J.3 3" W 4"W UP 2"V UP 3"W&T UP Sullivan Construction, LLC. J.4 4"W UP K 4" W 4"W UP TO VERTICAL CARRIER I.1 J.5 1-1/2"W UP 2" W 4" W 3"W&T UP UP TO FD-1 EXETER ROAD PORTSMOUTH, NH 03801 J.1 4" W 8"RL UP UP TO FCO-1 J UP TO FD 2"W UP 3" UP TO FCO Y 2"W UP 2"W UP 2"V UP 3"W&T 3"W&T UP 1-1/2"V UP (DISHWASHER) EJ 4" UP TO FCO 4"W UP 3"W&T UP 1"CW UP 3"W UP 3" W 2" W 3"W&T UP 3" W 4" UP TO FCO GIRT LINE 0 3"W&T UP 4"W UP CSI plumbing electrical H.5 This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 3"W&T UP 1-1/2"W UP 4"UP TO FCO 2"V UP 3"W&T UP Z 1.1 J.7 L ENCLOSURE BY ARCHITECT 12/1/2022 2:06:51 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt W 2" I.2 Scale: Date: Project Number: 2"W UP M 1/8" = 1'-0" 12.02.2022 2021-167 I.3 REVISIONS NO. K.1 K.9 1.9 2.8 3.8 5. 1 UNDERSLAB PLAN - PART A PLUMBING 1/8" = 1'-0" DESCRIPTION DATE PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION UNDERSLAB PLAN - PART A 4.8 P1.00a COPYRIGHT C 2022 GENERAL PLUMBING NOTES 1. REFER TO DRAWING P0.01 FOR LEGENDS, ABBREVIATIONS AND GENERAL NOTES. 8"RW AND 4"W CONT. BY G.C. 1 3"V UP A 2"V UP UP TO FCO-2 UP TO FCO-2 4" W 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com B 4" W OS-1 DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 4"W&J DRAIN OUTLET BACK WATER VALVE TRENCH DRAINSEE GROUND LEVEL PART B CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 D STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 UP TO FCO-2 E CSI Engineering fire protection plumbing electrical hvac This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 MILLION AIR- PEASE F EXETER ROAD PORTSMOUTH, NH 03801 Sullivan Construction, LLC. G G @ 1/8"/FT 2 3 4 5 6 H H 2.81 5' HIGH WALLS H.5 H.5 Scale: Date: Project Number: 0 00 1/8" = 1'-0" 12.02.2022 2021-167 PORTE COCHÈRE REVISIONS H.1 UP NO. X GIRT LINE 12/1/2022 2:06:52 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt 3.81 UP J.2 REFER TO UNDERSLAB PART A PLAN FOR ALL PLUMBING IN THIS AREA DESCRIPTION DATE EJ J J.1 EJ J.3 J.4 1.1 1 1.9 5. PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION UNDERSLAB PLAN - PART B UNDERSLAB PLAN - PART B PLUMBING 1/8" = 1'-0" P1.00b COPYRIGHT C 2022 GENERAL PLUMBING NOTES 1. REFER TO DRAWING P0.01 FOR LEGENDS, ABBREVIATIONS AND GENERAL NOTES. 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com F DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 G CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 G HANGAR 150 2 3 4 5 6 H H 2.81 3.81 1/2"CW DP 1/2"HW DP WB-1 2"W&T UP 2"V UP UP 124 125 123 2"W&T 2"W&T 6"ORL UP X STOR UP CO 122 CO J.2 1"CW DN 1"CW DN J.3 1/2"CW DP BFP-2 SK-1 EWH 1 1/2"CW DP & 1/2"HW DP AND RUN UNDER COUNTER TO SK-1 JAN 121 FD-B 2"W UP 1-1/2"V DN 2"V UP 2"W&T UP ELECTRICAL ? ? CO 128 FD-B WC-2 WC-1 2"V RISE 2"V UP 2"W&T UP 1-1/2" CW DROP 1-1/2" HW DROP K 2"W&T UP I.1 CAFE CART 133 FD-B 3"FCO STORAGE BAGS 120 118 135 116-S EJ CLOS STAIR 2 134 ST-2 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 MILLION AIR- PEASE J FD-B 113 LAV-1 WOMEN LAV-1 114 WC-1 FD-B 2"W&T UP J.1 FD-B BEVERAGE 1/2" HW DP 2"W DN & 2"V RISE 1/2" CW DP FIRE PUMP 112 1/2"CW DP 4"W UP WSB-1 WC-1 2"W&T UP FD-B UR-1 LAV-1 MEN WC-2 115 4"W DN LAV-1 (4) 1-1/2"W DN & 1-1/2" V RISE FD-B J.4 EXETER ROAD PORTSMOUTH, NH 03801 FW Sullivan Construction, LLC. 1/2" FW UP TO EACH SUPPLY BOX INSTALLED ABOVE BACKSPLASH F-1 2"W&T UP FILTER IN CABINET UR-1 117 4"FCO Engineering SK-1 1/2" HW 2"W&T UP CO CORR MAIL 2 P2.02 CSI 4"FCO 130 108 FCO-1 LINE 132 fire protection EL-1 Y SERVICE AREA 4"W UP 3"V UP FD-B ELEV 2"V DN SK-2 131 This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 4"W DN 2"V DN 119 CORR 4" W OFFICE FCO MECH MB-1 3"W DN 1/2" CW DROP 1/2" HW DROP WEST ENTRY 2"VTR 2"V DN 2" V UP 129 TP 3/4"CW DP 2"W DN & 2"V RISE 1 P2.02 6"ORL @ 1/4"/FT 6" DOWNSPOUT NOZZLE 24" AFG EJ FD-B 2"W UP 4" W (2) 2"W&T UP 4"W UP 1 1/2"V DN 1" CW DN 2" CW DN FD-B BFP-1 127 electrical CORRIDOR LSM TP H.1 2"W UP LAUNDRY TP FLIGHT PLAN 4"GCO TP 4" W CSR hvac CO TP 4"W UP ST-1 GIRT LINE PORTE COCHÈRE 2"W&T UP plumbing 0 CO 4" W 4"W UP 4"W DN 2"W&T STAIR 1 H.5 2"W&T UP 2"W&T UP CO MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 2"W DN & 1 1/2"V RISE TP 5' HIGH WALLS H.5 00 STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 J.5 CONDIMENTS 103 4"W DN 2"V DN 4" W DN Z WEST LOBBY 1.1 101 J.7 EAST ENTRY 110 L RECEPTION 102 I.2 2"W UP 2"W DN EAST LOBBY 12/1/2022 2:06:56 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt SEATING M 104 105 I.3 CONFERENCE CONFERENCE 107 106 Scale: Date: Project Number: 1/8" = 1'-0" 12.02.2022 2021-167 SOUTH ENTRY 109 REVISIONS NO. DESCRIPTION DATE K.1 K.9 1.9 PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION 2.8 3.8 5. GROUND LEVEL - PART A PLUMBING 1 1/8" = 1'-0" 4.8 GROUND LEVEL FLOOR PLAN PART A P1.01a COPYRIGHT C 2022 GENERAL PLUMBING NOTES 1. REFER TO DRAWING P0.01 FOR LEGENDS, ABBREVIATIONS AND GENERAL NOTES. 1 NEW GAS METER A 3" G UP 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com FCO-2 3" V UP DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 B FCO-2 CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 TD-1 D STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 FCO-2 E CSI Engineering fire protection plumbing electrical hvac This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 HANGAR MILLION AIR- PEASE 150 F EXETER ROAD PORTSMOUTH, NH 03801 Sullivan Construction, LLC. G G 2 3 4 5 6 H H 3.81 5' HIGH WALLS H.5 H.5 Scale: Date: Project Number: 1/8" = 1'-0" 12.02.2022 2021-167 REVISIONS 0 00 PORTE COCHÈRE NO. H.1 X UP J.2 REFER TO GROUND FLOOR PART A PLAN FOR ALL PLUMBING IN THIS AREA J J.1 J.3 J.4 1 DATE EJ EJ 1.1 DESCRIPTION UP GIRT LINE 12/1/2022 2:06:57 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt 2.81 1.9 5. PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION GROUND LEVEL FLOOR PLAN PART B GROUND LEVEL - PART B PLUMBING 1/8" = 1'-0" P1.01b COPYRIGHT C 2022 GENERAL PLUMBING NOTES 1. REFER TO DRAWING P0.01 FOR LEGENDS, ABBREVIATIONS AND GENERAL NOTES. 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com F DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 G STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 HANGAR 150 2 OPEN TO BELOW 3 4 5 MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 6 H 1 P2.01 2 P2.01 3 P2.01 hvac FS-1 220 0 SH-1 READY READY SH-2 DN 217 00 222 LAV-2 CORR fire protection 227 FD-A CORR WC-3 LAV-2 214 LAV-2 1 1/4" CW 3/4" HWR READY WC-3 DN FD-A SH-1 READY 221 J.2 1" HW EXPANSION JOINT GUTTER AND DOWNSPOUT (2) 3"CPVC EJ & DN UP MECH. 215 SH-2 READY FD-A 211 6"RL DN TO 8"RL DN Y STORAGE WC-3 LAV-2 213 (2) 3"CPVC UP & DN ELEV READY (2") FD-A FD-A 1 1/4"G UP TO RTU LAV-2 WC-3 LAV-2 WC-3 Sullivan Construction, LLC. J.4 LOUNGE 216 3/4" HW FD-A READY EL-1 EXETER ROAD PORTSMOUTH, NH 03801 J.1 1/2" HW DP 2" W DN & 2" V RISE 1/2" CW DP EJ SH-1 208 J ST-2 SH-2 228 EJ 1" CW 3/4" HW LAV-2 2" V DN SIM. STAIR 2 READY SH-2 WC-3 2"G DN SK-2 FD-A 225 6"ORL DN 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 MILLION AIR- PEASE WC-3 LAV-2 1 1/2" CW 3/4" HWR FD-A ELEC 1" HW WC-3 LAV-2 WC-3 LAV-2 218 J.3 Engineering 212 ST-1 X CSI 230 READY SH-1 224 FD-A WC-3 STAIR 1 COMMON AREA HSK FD-A H.1 electrical 1 1/4" G HANGAR BALCONY plumbing H.5 This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. J.5 READY 210 209 FS-1 SH-1 2"V DN ALIGN Z SH-2 3/4" HWR 3/4" CW OPEN TO BELOW OPEN TO BELOW ALIGN 1/2" HW 4 P2.01 1.1 5 P2.01 J.7 L 12/1/2022 2:07:04 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt I.2 1/2" CW DP 2" W DN & 2" V RISE 1/2" HW DP M SK-1 SEATING I.3 Scale: Date: Project Number: 1/8" = 1'-0" 12.02.2022 2021-167 204 REVISIONS STORAGE LOBBY STAIR 203 ST-3 NO. DESCRIPTION DATE DECK 205 1/2" CW DP PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION K.1 1.9 K.9 2.8 3.8 4.8 1 5. SECOND FLOOR PLAN - PART A SECOND FLOOR - PART A PLUMBING 1/8" = 1'-0" P1.02a COPYRIGHT C 2022 GENERAL PLUMBING NOTES 1. REFER TO DRAWING P0.01 FOR LEGENDS, ABBREVIATIONS AND GENERAL NOTES. 1 3"G DN A 3/4"G UP TO GUH 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com 3/4"G UP TO GUH 3/4" G 1 1/4" G B 3" G DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 D STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 3" G MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 E CSI Engineering fire protection plumbing electrical hvac This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 MILLION AIR- PEASE F HANGAR 150 EXETER ROAD PORTSMOUTH, NH 03801 Sullivan Construction, LLC. 3" G G 2 3 4 5 6 3/4"G UP TO GUH H 3/4"G UP TO GUH 1 1/4" G 2" G 12/1/2022 2:07:05 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt OPEN TO BELOW H.5 Scale: Date: Project Number: DN 1/8" = 1'-0" 12.02.2022 2021-167 REVISIONS 00 NO. DESCRIPTION DATE H.1 SIM. X REFER TO SECOND FLOOR PART A PLAN FOR ALL PLUMBING IN THIS AREA DN J J.2 J.1 EJ PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION EJ GUTTER AND DOWNSPOUT EJ 1.1 1 1.9 5. SECOND FLOOR PLAN - PART B SECOND FLOOR - PART B PLUMBING 1/8" = 1'-0" P1.02b COPYRIGHT C 2022 GENERAL PLUMBING NOTES 1. 3 4 5 REFER TO DRAWING P0.01 FOR LEGENDS, ABBREVIATIONS AND GENERAL NOTES. 6 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com F DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 G STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 H hvac electrical CSI Engineering fire protection 0 plumbing H.5 This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 00 MILLION AIR- PEASE X 5. EXETER ROAD PORTSMOUTH, NH 03801 J J.1 RD-1 Y 2 6" REG. AND OVERFLOW RD Sullivan Construction, LLC. J.4 H.1 J.5 K J.2 I.1 I.2 Z 2.81 3.81 1.1 J.7 L 12/1/2022 2:07:06 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt I.3 Scale: Date: Project Number: K.1 1/8" = 1'-0" 12.02.2022 2021-167 M REVISIONS NO. J.3 DESCRIPTION DATE PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION 1.9 K.9 2.8 3.8 4.8 1 ROOF PLAN LOW ROOF ROOF PLAN - LOW ROOF - PLUMBING 1/8" = 1'-0" P1.03a COPYRIGHT C 2022 GENERAL PLUMBING NOTES 1. 1 3 4 5 REFER TO DRAWING P0.01 FOR LEGENDS, ABBREVIATIONS AND GENERAL NOTES. 6 A 4" VTR 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com B DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 D STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 E CSI Engineering fire protection plumbing electrical hvac This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 MILLION AIR- PEASE F EXETER ROAD PORTSMOUTH, NH 03801 Sullivan Construction, LLC. G H 12/1/2022 2:07:06 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt H.5 Scale: Date: Project Number: 3" VTR 3" VTR 1/8" = 1'-0" 12.02.2022 2021-167 REVISIONS 3" VTR NO. DESCRIPTION DATE 5. J J.1 PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION J.2 1 1.1 2 H.1 1.9 2.81 3.81 ROOF PLAN HANGAR ROOF ROOF PLAN - HANGAR ROOF - PLUMBING 1/8" = 1'-0" P1.03b COPYRIGHT C 2022 4 R BATHROOM R BATHROOM 222A SH-1 227A 1/2" CW DP 1/2" HW DP 1/2" HW DP 1/2" CW DP SH-1 (3) 2" V DN FS-1 READY READY 1/2" CW DP 1/2" HW DP READY 222 217 224 (2") FD-A 1" CW R BATHROOM FD-A LAV-2 LAV-2 WC-3 FD-A (2") 1" HW 3/4" HWR R BATHROOM 221 EXPANSION JOINT (TYP 3) ELEC 218 SH-1 1 1/2" CW 1" HW 3/4" HWR 225 J J SH-1 1/2" HW DP 1/2" CW DP 1.9 228A 1" CW 3/4" HW FD-A 1" CW (2") CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 SH-1 READY 228 R BATHROOM 2"CW DN 1 1/2"HW DN 3/4"HWR DN 221A 1/2" CW DP 1/2" HW DP 2.81 2 DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 R BATHROOM J 1/2" HW DP 1/2" CW DP SECOND FLOOR - READY ROOMS 217 & 218 PLAN 1/4" = 1'-0" 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com WC-3 READY READY 218A 2" V DN 1" CW DP 3" VTR 2" V DN 1" CW DP 2" V DN LAV-2 LAV-2 1 1/2" CW 1" HW 3/4" HWR 1 1/4" CW WC-3 (2) CW DP (2) HW DP 2" W DN & 2" V RISE 1" CW DP 3" VTR 2" V DN 1" CW DP 2" V DN 1" CW 3/4" HW 3/4" HWR (2") 3/4" HW 2" V DN LAV-2 1" CW 3/4" HW 2" V DN 1" CW DP 3" VTR 2" V DN 1" CW DP 2" V DN (2)1/2" CW DP (2)1/2" HW DP 2" W DN & 2" V RISE (2)1/2" HW DP (2)1/2" CW DP 2" W DN & 2" V RISE 1" CW 1" CW 3/4" HW LAV-2 1" CW (2") 3/4" HW 1 1/2" CW 1" HW 3/4" HWR WC-3 217A 1 SH-1 227 HSK STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 3.81 SECOND FLOOR - READY ROOMS 221 & 222 PLAN 1/4" = 1'-0" 3 SECOND FLOOR - READY ROOMS 227 & 228 PLAN 1/4" = 1'-0" MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 CSI Engineering 4 fire protection 1/2" CW DP 1/2" HW DP 1/2" HW DP 1/2" CW DP SPECIALTY EQUIPMENT SCHEDULE EQUIP TAG J.1 J.1 (2") 211 208 1" CW 3/4" HW 1" CW 3/4" HW LAV-2 WC-3 1" CW 3/4" HW FS-1 R BATHROOM HW (140°F) COFFEE MAKER 2 1/2" 04 ESPRESSO MAKER 1 1/2" 05 RESTAURANT COFFEE MAKER 2 1/2" 08 COMMERCIAL DISHWASHER 3 10 ICE MAKER, UNDERCOUNTER 1 15 GLASS WASHER 1 1/2" 1/2" 20 WASHER 1 3/4" 3/4" 2" V DN 2" V DN COMMENTS IW EXETER ROAD PORTSMOUTH, NH 03801 1" 1/2" 1/2" 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 3/4" WITH SHUTOFF, STRAINER, AND IDW HOSE 1/2" 1/2" DRAIN 1-1/4" TO/FROM WSDU Sullivan Construction, LLC. IDW TO FD NOTES: 1. ALL EQUIPMENT, FIXTURES AND FAUCETS SHOWN ON THIS SCHEDULE SHALL BE FURNISHED BY OTHERS, UNLESS NOTED OTHERWISE. MAJOR EQUIPMENT SHALL BE SET IN PLACE BY THE GENERAL CONTRACTOR. THE PLUMBING CONTRACTOR SHALL INSTALL ALL PLUMBING RELATED FAUCETS AND HARDWARE. THE PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL ALL REQUIRED TRAPS, SUPPLIES, STOPS, INDIRECT WASTE PIPING AND NECESSARY HARDWARE AS REQUIRED FOR A COMPLETE INSTALLATION. WC-3 READY 209 210 CWF (FILTERED) 03 LAV-2 SH-1 READY CW 208A WC-3 1" CW 3/4" HW 1" CW QTY R WC 1" CW DP 3" VTR 2" V DN 1" CW DP 3/4" HWR 1/2" HW 3/4" CW FD-A (2") FD-A (2") LAV-2 (2)1/2" CW DP (2)1/2" HW DP 2" W DN & 2" V RISE 3" V DN LAV-2 SH-1 1" CW 3/4" HW 1/2" CW WC-3 READY 1" CW 1" HW 3/4" HWR FD-A STORAGE 213 (2") 1/2" CW 211A 1/2" HW R WC READY 1/2" HW 1/2" HW SH-1 EQUIPMENT 2" W DN This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. MILLION AIR- PEASE MINIMUM ROUGH IN CONNECTION SIZE J plumbing electrical hvac R BATHROOM (2") FD-A 209A SH-1 2" W DN 1/2" HW DP 1/2" CW DP 210A 12/1/2022 2:07:13 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt 1/2" CW DP 1/2" HW DP 2.81 4 SECOND FLOOR - READY ROOMS 210 & 211 PLAN 1/4" = 1'-0" 3.81 5 Scale: Date: Project Number: SECOND FLOOR - READY ROOMS 208 & 209 PLAN 1/4" = 1'-0" As indicated 12.02.2022 2021-167 REVISIONS NO. DESCRIPTION DATE PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION ENLARGED PLANS, NOTES & DETAILS P2.01 COPYRIGHT C 2022 0 00 0 00 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com X DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 X CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 5 STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 6 MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 Y Y H.5 CSI Engineering fire protection plumbing electrical hvac This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 MILLION AIR- PEASE EXETER ROAD PORTSMOUTH, NH 03801 Z Sullivan Construction, LLC. Z 5. J 12/1/2022 2:07:15 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt 1 GROUND LEVEL - CAFE CART ENLARGED PLAN 1/4" = 1'-0" 2 5. GROUND LEVEL - SERVICE AREA ENLARGED PLAN 1/4" = 1'-0" Scale: Date: Project Number: 1/4" = 1'-0" 12.02.2022 2021-167 REVISIONS NO. DESCRIPTION DATE PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION ENLARGED PLANS P2.02 COPYRIGHT C 2022 BFP-1 REDUCED PRESSURE BACKFLOW PREVENTER WITH FULL SIZE DRAIN LINE. TERMINATE AT FLOOR DRAIN WITH CODE REQUIRED AIR-GAP PRESSURE GAUGE 3"CW TO SYSTEM INSULATION SHIELD SCHEDULE FULL PORT BALL VALVE IF STREET PRESSURE EXCEEDS 80 PSI PROVIDE PRV, SET FOR 70 PSI TOP CLEARANCE FOR TESTING PIPE SIZE DIM. A GA. OF STEEL UP TO 4" 12" 18 5" & 6" 18" 16 ABOVE 6" 24" 14 THREADED HANGER ROD 12" INTEGRAL BALL VALVES (TYPICAL) ADJUSTABLE HANGER W/ ROLLER (FOR 4" TO 6" PIPE) HEAVY DUTY CLEVIS HANGER (FOR ½" UP TO & INCLUDING 3" PIPE) TRAPEZE PIPE HANGER THREADED HANGER ROD L THREADED HANGER ROD LOCKING NUT AIR GAP FITTING PIPE CLAMPS WITH ELASTOMER OR NYLON INSULATOR (TYP) SUPPORT NUT 3/4" IW DRAIN LINE PROVIDE WATER METER 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com 3" STRAINER INSULATION 3/4"DV 18-24" 36" TO 48" ABOVE FLOOR 3" GATE VALVE C L C L PIPE ° 135 GALVANIZED INSULATION SHIELD 12" LONG. FLOOR DRAIN 1/2 OF A 1/2 OF A INSULATION SHIELD SEE SCHEDULE A TIE BACK RODS TO FINISH FLOOR WATER SERVICE DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 PIPE COVERING PROTECTION 16 GA. SADDLE PROVIDE HEAT TRACING CABLE WHERE INDICATED. ONE STRIP FOR PIPES 6" AND SMALLER. TWO STRIPS FOR PIPES 8" AND LARGER PIPE UN-INSULATED PIPING (TYP) METAL CHANNEL STRUT RIGID INSULATION AT SHIELD INSULATED PIPING WITH PIPE CLAMP. PROVIDE WITH INSULATION SHIELD. NOTES: PIPE HANGER/SHIELD DETAIL NOTES: 1. FURNISH TO OWNER ONE TEST KIT AND SPARE PARTS KIT. 2. THIS CONTRACTOR SHALL ACT AS THE OWNERS AGENT IN SEEKING APPROVAL FROM ALL LOCAL AND STATE AUTHORITIES. THIS CONTRACTOR SHALL SUBMIT ALL PLANS,SPECS. AND APPLICATIONS REQUIRED FOR APPROVAL AND PAY ALL FEES. 3. SEE FLOOR PLANS FOR SIZES 4. TEST AND CERTIFY EACH INSTALLATION. 2 1. CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 SEE SPECIFICATION FOR HANGER SIZES. 1 PIPE HANGER DETAILS WATER SERVICE DETAIL NTS STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 SHUTOFF VALVE 1/2" 1/ " 2 WALL STANDARD WEIGHT STEEL PIPE SLEEVE CW CW FAUCET SINK DISHWASHER DISCHARGE 1/2" COPPER PIPING FROM PIPING IN CEILING TRAP PRIMER W/ VACUUM BREAKER CW SUPPLY ABOVE CEILING OR UNDER FIXTURE COUNTER MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 COUNTER TOP STOP VALVE INSTANTANEOUS ELECTRIC WATER HEATER (EWH-2) STOP VALVE JUNCTION BOX BY ELECTRICAL CONTRACTOR 1/ "CW 2 PROVIDE FLEXIBLE COPPER TUBING AS REQ'D. CW COLD WATER SUPPLY 1/ "HW 2 1/ " 2 FLOOR DRAIN TRAP PRIMER DISTRIBUTION UNIT (MOUNT ON WALL) ICE MAKER CONNECTION SIOUX CHIEF MODEL #696 SERIES CW TO FLOOR DRAINS W/TRAP PRIMER CONNECTIONS, SEE DRAWINGS FOR NUMBER CONNECT TO REFRIGERATOR ICE MAKER OR COFFEE MAKER 1/ " 2 THREE WAY ANGLE STOP VALVE BALL VALVE SUPPLY UNION 1/ "HW SUPPLY 2 TO DISHWASHER 1/ " 2 CARRIER PIPE (SIZE VARIES) SUPPLY DISHWASHER (BY OTHERS) FINISH FLOOR SEAL ASSEMBLY (SEE NOTE BELOW) NOTES: FINISHED FLOOR 8 POINT OF USE MIXING VALVE DETAIL NTS 7 INSTANTANEOUS ELECTRIC WATER HEATER NTS 6 WATER SUPPLY BOX W/ MINI ARRESTOR DETAIL NTS 5 TRAP PRIMER DETAIL 4 DISHWASHER CONNECTION UNDER COUNTER NTS Engineering fire protection SEAL ASSEMBLY SHALL BE MODULAR MECHANICAL TYPE CONSISTING OF INTERLOCKING RUBBER LINKS SHAPED TO CONTINUOUSLY FILL IN THE ANNULAR SPACE BETWEEN PIPE & WALL OPENING PRESSURE PLATES SHALL BE DELRIN PLASTIC BOLTS & NUTS SHALL BE 18.8 STAINLESS STEEL SEALING ELEMENT SHALL BE EPDM RUBBER 1/4" CSI 3 WATERTIGHT SLEEVE DETAIL NTS plumbing HOT WATER SUPPLY (140°F) POINT OF USE MIXING VALVE TMV-1 (BEHIND P-TRAP) hvac electrical HOT WATER SUPPLY (110°F FOR LAVS, 130°F FOR SINKS) CW HW This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 MILLION AIR- PEASE EXETER ROAD PORTSMOUTH, NH 03801 Sullivan Construction, LLC. NC AQUASTAT W/ PIPEWELL 3/ " 4 USE A REVERSE RETURN 2" INTERMATIC INC. MODEL T171 24 HR. DIAL TIME CLOCK WITH SKIPPER FEATURE. UNION 2" 2" REDUCER (IF REQUIRED) HVAC UNIT BY HVAC CONTRACTOR RP 1 1/2" T 1 1/2" VERTICAL TEE GAS COCK(TYPICAL) T 1 T & P RELIEF VALVE (TYP) FULL SIZE DISCHARGE TO ADJACENT MOP RECEPTOR WH-1 WH-1 REGULATOR 3" MIN. SEDIMENT LEG XT-1 SEISMIC EXPANSION JOINT PROVIDE PIPE SUPPORT 4"CONCRETE PAD BY G.C. NOTES: FINISHED FLOOR 12/1/2022 2:07:15 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt 1. 10 DOMESTIC WATER HEATING DIAGRAM WATER TIGHT SLEEVE NTS PAINT EXTERIOR GAS PIPING WITH GRAY RUSTOLIUM PAINT 9 OUTDOOR HVAC GAS EQUIPMENT CONNECTION DETAIL Scale: Date: Project Number: 1" = 10'-0" 12.02.2022 2021-167 NTS REVISIONS NO. DESCRIPTION DATE PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION DETAILS P3.01 COPYRIGHT C 2022 A. GENERAL CONDITIONS 2. 12/1/2022 2:07:15 PM C:\Users\mbrake\Documents\2021-167 Million Air at Pease_Plumbing_mbrake.rvt 4. 5. SCOPE OF WORK: 2.1. WITHOUT LIMITING THE GENERALITY THEREOF, PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT AS REQUIRED TO FURNISH AND INSTALL COMPLETE PLUMBING AND RELATED SYSTEMS AS FOLLOWS: 2.1.1. POTABLE DOMESTIC COLD WATER, HOT WATER AND HOT WATER RECIRC SYSTEMS AS REQUIRED TO CONNECT TO NEW PLUMBING FIXTURES THROUGHOUT THE PROJECT. 2.1.2. POTABLE DOMESTIC TEMPERED WATER SUPPLY AND RETURN SYSTEMS AS REQUIRED TO CONNECT TO NEW EMERGENCY PLUMBING FIXTURES THROUGHOUT THE PROJECT. 2.1.3. NON-POTABLE COLD WATER, HOT WATER AND HOT WATER RECIRC SYSTEMS AS REQUIRED TO CONNECT TO NEW LAB FIXTURES THROUGHOUT THE PROJECT. 2.1.4. SANITARY WASTE AND VENT SYSTEM AS REQUIRED TO CONNECT TO NEW PLUMBING FIXTURES THROUGHOUT THE PROJECT. 2.1.5. GARAGE WASTE AND VENT SYSTEM AS REQUIRED TO CONNECT TO NEW GARAGE FLOOR DRAINS AND TRENCH DRAINS THROUGHOUT THE PROJECT. 2.1.6. KITCHEN WASTE AND VENT SYSTEM AS REQUIRED TO CONNECT TO NEW KITCHEN FIXTURES THROUGHOUT THE PROJECT. 2.1.7. LAB WASTE AND VENT SYSTEM AS REQUIRED TO CONNECT TO NEW LAB FIXTURES THROUGHOUT THE PROJECT. 2.1.8. RAINWATER (STORM) DRAINAGE SYSTEMS AS REQUIRED TO CONNECT TO NEW ROOF AND AREA DRAINS THROUGHOUT THE PROJECT. 2.1.9. FUEL GAS (NATURAL) SYSTEM AS REQUIRED TO CONNECT TO NEW FIXTURES AND EQUIPMENT THROUGHOUT THE PROJECT. 2.1.10. ALTERATIONS, ADDITIONS AND/OR REMOVAL OF EXISTING PLUMBING SYSTEMS AND FIXTURES WITHIN THE RENOVATED AREAS AS SHOWN IN ORDER TO CONFORM TO THE NEW SPACE REQUIREMENTS. 2.1.11. ALL PIPE, FITTINGS, VALVES, SLEEVES, HANGERS, SUPPORTS, EXPANSION JOINTS AND RELATED COMPONENTS AS REQUIRED FOR COMPLETE INSTALLATION OF EACH SYSTEM. 2.1.12. PIPE INSULATION FOR ALL COLD WATER, HOT WATER AND HOT WATER RECIRC PIPING INCLUSIVE OF MAINS AND BRANCH PIPING AS REQUIRED. PIPE INSULATION FOR ALL HORIZONTAL RAINWATER PIPING INCLUSIVE OF ROOF DRAIN BODIES. 2.1.13. ACCESS PANELS FOR CONCEALED COMPONENTS AS REQUIRED (FURNISHING ONLY). CORE DRILLING AS REQUIRED. 2.1.14. PLUMBING FIXTURES, FAUCETS, TRIM, SUPPLIES, STOPS, CARRIERS AND ALL RELATED HARDWARE AS REQUIRED FOR A COMPLETE INSTALLATION. PLUMBING EQUIPMENT INCLUSIVE OF ALL VALVES, DRAINS, UNIONS, PRESSURE GAUGES, TEMPERATURE GAUGES AND RELATED HARDWARE AS REQUIRED FOR A COMPLETE INSTALLATION. 2.1.15. TESTING, ADJUSTING, BALANCING, FLUSHING AND STERILIZING. ALL PERMITS AND FEES AS APPLICABLE. COMPLETE (1) ONE YEAR GUARANTEE FOR ALL WORK. RELATED WORK BY OTHER: 3.1. THE FOLLOWING RELATED WORK SHALL BE DONE BY OTHERS. COORDINATE THE WORK OF THIS TRADE WITH THE RELATED WORK OF EACH RESPECTIVE CONTRACTOR: 3.1.1. CUTTING AND PATCHING, TEMPORARY WATER, HEAT, FIRE PROTECTION AND TOILET FACILITIES, TEMPORARY POWER AND LIGHTING, EXCAVATION AND BACKFILL, CONCRETE AND MASONRY SUPPORTS AND EQUIPMENT BASES, FLASHING AND CAULKING, FINISH PAINTING, HEATING, VENTILATING AND AIR CONDITIONING, FIRE PROTECTION, ELECTRICAL POWER AND WIRING, FURNISHING OF TOILET ROOM ACCESSORIES, INSTALLATION OF ACCESS PANELS, FOOD SERVICE EQUIPMENT, FOUNDATIONS AND TRENCHING. INTENT OF THE DRAWINGS: 4.1. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT SHOW EVERY PIPE, FITTING, ELBOW AND BEND. THIS CONTRACTOR SHALL PROVIDE ALL NECESSARY PIPING, FITTINGS, VALVES, SLEEVES, HANGERS, SUPPORTS, EXPANSION JOINTS AND COMPONENTS AS REQUIRED BY CODE FOR COMPLETE SYSTEMS AS NOTED ABOVE AND IN ACCORDANCE WITH THE NEW AND EXISTING ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL ELEMENTS IN THE SPACE. SUBMITTAL REQUIREMENTS: 5.1. UPON CONTRACT AWARD, SUBMIT A LIST OF THE PROPOSED MANUFACTURER'S THAT IS INTENDED TO BE USED ON THIS PROJECT FOR APPROVAL. THIS LIST MAY INCLUDE BOTH THE MANUFACTURER'S THAT ARE SPECIFIED HERE AS WELL AS PROPOSED OR EQUAL MANUFACTURER'S. ONCE THIS LIST IS APPROVED BY THE ENGINEER, NO SUBSTITUTIONS SHALL BE ALLOWED. APPROVAL OF THE LIST OF MANUFACTURERS' DOES NOT RELIEVE THIS CONTRACTOR OF THE RESPONSIBILITY OF MEETING ALL REQUIREMENTS OF THE SPECIFICATIONS WITH REGARDS TO QUALITY AND PERFORMANCE CRITERIA. 5.2. SUBMITTALS SHALL BE PROVIDED IMMEDIATELY AFTER CONTRACT AWARD WITH AMPLE TIME FOR ENGINEER's REVIEW PRIOR TO INSTALLATION. SUBMITTALS SHALL INCLUDE ALL QUALITY, PERFORMANCE AND DIMENSIONAL INFORMATION AS REQUIRED FOR PROPER REVIEW. SUBMITTALS SHALL BE CONCISE AND GENERALLY IN 8-1/2" x11" FORMAT OR INCREMENTS THEREOF. PROVIDE (6) SETS OF COMPLETE SUBMITTALS OF THE FOLLOWING ITEMS: 5.2.1. COORDINATION DRAWINGS OF ALL PLUMBING WORK. 5.2.2. PIPING AND FITTINGS FOR EACH PIPING SYSTEM AS SPECIFIED. 5.2.3. PLUMBING FIXTURES, FAUCETS AND TRIM AS LISTED IN THE SCHEDULES. 5.2.4. PLUMBING EQUIPMENT AS LISTED IN THE SCHEDULES. 6. 7. 8. 2. PROJECT CLOSE OUT REQUIREMENTS: 6.1. AT THE CLOSE OF THE PROJECT, BUT PRIOR TO FINAL PAYMENT OR RELEASE OF RETAINAGE, PROVIDE THE FOLLOWING CLOSE OUT ITEMS FOR REVIEW AND APPROVAL (NOTE THAT SOME OF THESE ITEMS REQUIRE ON GOING MAINTENANCE): 6.1.1. OPERATING PARTS AND MAINTENANCE MANUALS FOR ALL PLUMBING EQUIPMENT, FIXTURES, FAUCETS AND TRIM AS LISTED IN THE SCHEDULES. 6.1.2. PROVIDE THE OWNER OR HIS REPRESENTATIVE A TRAINING SESSION FOR INSTRUCTION IN THE USE OF ALL FIXTURES AND EQUIPMENT AS LISTED IN THE SCHEDULES. THE APPROVED OPERATING PARTS AND MAINTENANCE MANUALS SHALL BE MADE AVAILABLE AND USED DURING THIS TRAINING SESSION. 6.1.3. MAINTAIN A COMPLETE SET OF RECORD DRAWINGS AT THE PROJECT SITE. WORKING PROGRESS, AS INSTALLED, INCLUSIVE OF ALL CHANGES TO THE CONTRACT, SHALL BE RECORDED ON A WEEKLY BASIS ON THE RECORD DRAWINGS. AT THE END OF THE PROJECT, THE RECORD DRAWINGS SHALL BE USED TO PREPARE THE AS-BUILT DRAWINGS. THE RECORD DRAWINGS SHALL BE SUBMITTED WITH THE AS-BUILT DRAWINGS FOR. 6.1.4. PROVIDE COMPLETE AS-BUILT DRAWINGS OF ALL WORK UNDER THIS SECTION PRIOR TO FINAL INSPECTION AND SIGN OFF. AS-BUILTS SHALL BE PROVIDED IN BOTH HARD COPY (1 SET) AND ELECTRONIC FORMAT, AUTOCAD RELEASE 2015 OR HIGHER. GUARANTEE: 7.1. GUARANTEE ALL MATERIALS, EQUIPMENT AND LABOR AGAINST ALL DEFECTS FOR ONE YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION. PROVIDE ADDITIONAL GUARANTEES FROM MANUFACTURERS OF EQUIPMENT AS APPLICABLE. 3. DESIGN CRITERIA: 8.1. THE ENGINEER HAS PROVIDED A DESIGN (DRAWINGS, SPECIFICATIONS AND CALCULATIONS) AND HAS SPECIFIED THE DESIGN CRITERIA TO BE USED BY THE INSTALLING CONTRACTOR. THE INSTALLING CONTRACTOR SHALL FURNISH AND INSTALL ALL SYSTEMS IN ACCORDANCE WITH THE DESIGN CRITERIA INCLUSIVE OF ALL CHANGES OR MODIFICATIONS. THE ENGINEER SHALL REVIEW AND APPROVED THE INSTALLING CONTRACTOR'S SUBMITTALS AND SHOP DRAWINGS. THE ENGINEER SHALL PERFORM PERIODIC INSPECTIONS AND CERTIFY THE SYSTEM INSTALLATION FOR CODE COMPLIANCE UPON COMPLETION. 8.2. DOMESTIC COLD AND HOT WATER SIZING DESIGN CRITERIA SHALL BE BASED ON HUNTER'S FIXTURE UNIT METHOD FOR LIGHT COMMERCIAL DESIGN USING PRESSURE AND FRICTION LOSS CALCULATIONS FOR COPPER PIPE AND FITTINGS NOT TO EXCEED 8 FPS. 8.3. SANITARY AND LAB WASTE AND VENT SIZING DESIGN CRITERIA SHALL BE BASED ON THE MASSACHUSETTS STATE PLUMBING CODE FIXTURE UNIT METHOD USING VARIOUS PITCH CALCULATION FOR VARIOUS PIPE SIZES AS APPLICABLE. 8.4. FUEL GAS SYSTEMS DESIGN CRITERIA SHALL BE BASED ON NFPA 54 NATIONAL FUEL GAS CODE AND THE MASSACHUSETTS STATE FUEL GAS CODE USING TOTAL CONNECTED BTUH OR CFH LOAD METHOD AND FRICTION LOSS BASED ON SCHEDULE 40 STEEL PIPE WITH A TOTAL PRESSURE DROP AS INDICATED OVER THE LONGEST RUN. B. MATERIALS AND PRODUCTS 1. PIPING: 1.1. WATER PIPING SHALL BE TYPE "L" COPPER TUBING WITH WROUGHT COPPER OR CAST BRASS SOLDER FITTINGS AND LEAD-FREE SOLDER JOINTS CONFORMING TO ASTM B-88, ANSI STANDARD B16.18, B16.18A AND B16.22 RESPECTIVELY OR VIEGA PRO-PRESS. FITTINGS AND JOINTS FOR PIPING 21/2" AND LARGER MAY BE VIEGA PRO-PRESS OR VICTAULIC COPPER GROOVED FITTINGS WITH ROLL GROOVED COPPER TUBE JOINT AND APPROVED NEOPRENE GASKETS AT THE CONTRACTOR'S OPTION. EXPOSED WATER PIPING IN FINISHED AREAS SHALL BE CHROME PLATED. 1.2. SANITARY WASTE AND VENT BELOW GROUND SHALL BE HUB AND SPIGOT CAST IRON PIPE WITH HUB AND SPIGOT CAST IRON FITTINGS CONFORMING TO ASTM A-74 AND HS 74, MANUFACTURED IN ACCORDANCE WITH CAST IRON SOIL PIPE INSTITUTE (CISPI) STANDARD 301 AND PAMPHLET 100. JOINTS SHALL BE MADE WITH NEOPRENE PUSH JOINT GASKET AND APPROVED LUBRICANT. 1.3. SANITARY WASTE AND VENT PIPING ABOVE GROUND SHALL BE HUBLESS CAST IRON SERVICE WEIGHT PIPING WITH HUBLESS CAST IRON FITTINGS CONFORMING TO ASTM A-888, MANUFACTURED IN ACCORDANCE WITH CAST IRON SOIL PIPE INSTITUTE (CISPI) STANDARD 301 AND PAMPHLET 100. JOINTS SHALL BE MADE WITH DOUBLE CLAMP, FOUR BAND RETAINER SLEEVE AND NEOPRENE GASKET. WASTE AND VENT PIPING 2" AND SMALLER MAY BE TYPE "M" COPPER TUBING CONFORMING TO ASTM B-88 WITH WROUGHT COPPER DRAINAGE PATTERN FITTINGS AND LEAD-FREE SOLDER JOINT CONFORMING TO ANSI B16-23 (EXCEPT AT URINALS). 1.4. SANITARY WASTE AND VENT PIPING MAY BE SCHEDULE 40 PVC PIPING WITH APPROVED PVC-DWV FITTINGS AS ALLOWED BY CODE. JOINTS SHALL BE MADE WITH THE SOLVENT WELD METHOD IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. REQUIRED FIRE RATED SEALING AND EXPANSION JOINTS SHALL BE PROVIDED IN ACCORDANCE WITH CODE. 1.5. LAB WASTE AND VENT PIPING ABOVE GROUND SHALL BE POLYPROPYLENE ACID RESISTANT PIPING WITH POLYPROPYLENE HEAT FUSION FITTINGS. JOINTS SHALL BE MADE WITH HEAT FUSION SEAL METHOD IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. 1.6. GAS PIPING 2" AND SMALLER SHALL BE SCHEDULE 40 SEAMLESS STEEL PIPE CONFORMING TO ASTM A120 WITH CAST IRON STANDARD WEIGHT OR BLACK MALLEABLE THREADED FITTINGS AND JOINT COMPOUND OR SCHEDULE 40 BLACK STEEL PIPE WITH VIEGA MegaPress G FITTINGS WITH HNBR SEALING ELEMENT AND CONFORM TO ANSI LC 4; 70 PSI. USE AND INSTALLATION OF FITTINGS MUST BE PER MANUFACTURER'S STANDARDS. 1.7. GAS PIPING 21/2" AND LARGER SHALL BE SCHEDULE 40 BLACK STEEL PIPE WITH BEVELED ENDS WITH STANDARD WEIGHT CARBON STEEL BEVELED END FITTINGS JOINED BY BUT WELDING IN ACCORDANCE WITH MASSACHUSETTS PLUMBING CODE SECTION 5.03. OR SCHEDULE 40 BLACK STEEL PIPE WITH VIEGA MegaPress G FITTINGS WITH HNBR SEALING ELEMENT AND CONFORM TO ANSI LC 4: 70 PSI. USE AND INSTALLATION OF FITTINGS MUST BE PER MANUFACTURER'S STANDARDS. 1.8. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL GAS TRAIN VENTS PER MASSACHUSETTS PLUMBING CODE SECTION 7.04 FOR ALL GAS FIRED EQUIPMENT REQUIRING GAS TRAINS. 1.9. UNIONS FOR PIPING TWO INCHES AND SMALLER SHALL BE 125 PSI SWP (STEAM WORKING PRESSURE) BRASS GROUND JOINT TYPE. FLANGES FOR PIPING 21/2" AND LARGER SHALL BE 125 PSI SWP FLAT FACED CAST BRASS, MALLEABLE STEEL OR CAST IRON FLANGES CONFORMING TO ANSI STANDARDS. FLANGES SHALL HAVE RUBBER FULL FACED GASKETS. 1.10. MATING OF FERROUS AND NONFERROUS PIPING SHALL BE SEPARATED WITH FLANGES, EXTRA HEAVY BRASS FITTINGS OR DIELECTRIC FITTINGS APPROVED FOR SUCH APPLICATION. FLANGES SHALL HAVE RUBBER GASKETS (1/16 INCH MINIMUM THICKNESS) AND TEFLON LINERS INSTALLED IN THE BOLT HOLES. PHYSICAL CONTACT BETWEEN FERROUS AND NONFERROUS FLANGES, INCLUDING THE BOLTS, NUTS AND WASHERS SHALL NOT BE PERMITTED. 1.11. JOINTS BETWEEN COPPER OR BRASS FITTINGS AND CAST IRON FITTINGS SHALL BE MADE WITH MANHOFF FITTINGS SCREWED INTO THREADED PIPE AND CAULKED INTO THE CAST IRON PIPE. 1.12. WELDED JOINTS SHALL BE PERFORMED BY A CERTIFIED WELDER WITH CERTIFICATION(S) FOR EACH SPECIFIC JOINT AND APPLICATION. VALVES AND SPECIALTIES: 2.1. VALVES FOR ALL PIPING SYSTEMS (COLD WATER, HOT WATER, FUEL GAS, ETC.) SHALL BE AS MANUFACTURED BY WATTS, APOLLO, JENKINS OR APPROVED EQUAL. VALVES SHALL BE OF ONE MANUFACTURER FOR THE ENTIRE PROJECT. WATTS VALVES ARE SPECIFIED HERE AS A GUIDE FOR THE TYPE AND QUALITY TO BE PROVIDED UNDER THIS SPECIFICATION. 2.1.1. VALVES SHALL BE PROVIDED WITH BUNA-N, TFE OR EPDM SEATS FOR THE SERVICE INTENDED. THE PRESSURE CLASSIFICATION FOR ALL VALVES IS WATER OIL GAS (WOG) PRESSURE RATING OR STEAM WORKING PRESSURE (SWP) RATING AS INDICATED. ALL VALVE LEVER HANDLES SHALL BE COLOR CODED IN CONFORMANCE WITH ANSI STANDARD AS-131. 2.1.2. SHUT-OFF VALVES FOR WATER SYSTEMS SHALL BE 150 PSI WOG TWO PIECE BALL VALVE WITH VINYL GRIP LEVER HANDLE. SHUT-OFF VALVES FOR FUEL GAS SYSTEMS SHALL BE EITHER 150 PSI WOG TWO PIECE BALL VALVE WITH TEE HANDLE OR 150 PSI WOG LUBRICATED PLUG TYPE VALVE. VALVES USED FOR BALANCING OR CONTROLLING FLOW SHALL BE CIRCUIT SETTER TYPE BALL VALVE. CHECK VALVES SHALL BE ALL BRONZE SWING CHECK TYPE, 125 CLASS SWP. 2.1.3. SERVICE SHUT-OFF VALVES FOR WATER PIPING: WATTS B-6000 OR B-6001 SERIES ALL BRONZE BALL VALVE. 2.1.4. SERVICE SHUT-OFF VALVES FOR GAS PIPING: WATTS B-6000-UL SERIES ALL BRONZE BALL VALVE WITH TEE HANDLE. SERVICE SHUTOFF VALVES FOR GAS PIPING 21/2" AND LARGER MAY BE WATTS CAST LUBRICATED FLANGED PLUG VALVE IN LIEU OF THE ABOVE SPECIFIED BALL VALVES AT THE CONTRACTOR'S OPTION. 2.1.5. BALANCING VALVES FOR WATER PIPING: WATTS CIRCUIT SETTER TYPE ALL BRONZE BALL VALVE. 2.1.6. CHECK VALVES FOR WATER PIPING 2" AND SMALLER: WATTS CV OR CVY SERIES SWEAT OR THREADED ALL BRONZE CHECK. CHECK VALVES FOR WATER PIPING 21/2" AND LARGER: WATTS 411 SERIES CHECK VALVE WITH FLANGED ENDS. 2.1.7. DRAIN VALVES FOR WATER PIPING: WATTS B-6000-CC OR B-6001-CC 3/4" ALL BRONZE HOSE END VALVE WITH CAP AND CHAIN. 2.1.8. SHOCK ARRESTERS SHALL BE MANUFACTURED IN ACCORDANCE WITH PDI STANDARD WH201. SA-A (0 TO 11 WFU), SA-B (12 TO 32 WFU). HANGERS AND ACCESSORIES: 3.1. ALL HORIZONTAL AND VERTICAL PIPING SHALL BE PROPERLY SUPPORTED FROM THE BUILDING STRUCTURE BY STEEL RODS, INSERTS, BEAM CLAMPS, FRICTION CLAMPS, HANGERS AND BRACKETS AS REQUIRED. CARPENTER PATTERSON CATALOG NUMBERS SPECIFIED HEREIN AND ARE INTENDED AS A GUIDE FOR THE TYPE AND QUALITY TO BE FURNISHED AND INSTALLED BY THIS CONTRACTOR. 3.2. FRICTION CLAMPS SHALL BE EQUAL TO FIGURES 126 FOR CAST IRON OR STEEL PIPE AND 126 CT FOR COPPER PIPE. 3.3. HANGERS FOR CAST IRON, STEEL AND ALL INSULATED PIPING (INCLUDING INSULATED COPPER) SHALL BE CLEVIS TYPE EQUAL TO FIGURE 100. HANGERS FOR UN-INSULATED COPPER AND BRASS PIPING SHALL BE FACTORY APPLIED COPPER PLATED STEEL BAND HANGERS FIGURE 1ACT. RODS AND NUTS SHALL ALSO BE FACTORY APPLIED COPPER PLATED. 3.4. EXTENSION TYPE SPLIT RING HANGERS WITH WALL PLATES FOR CAST IRON AND STEEL PIPE SHALL BE EQUAL TO FIGURES 81, 85 AND 90. EXTENSION TYPE SPLIT RING HANGERS WITH WALL PLATES FOR COPPER AND BRASS PIPE SHALL BE EQUAL TO FIGURES 81-CT, 85-CT AND 90-CT. 3.5. WHERE THREE OR MORE PIPES ARE INSTALLED PARALLEL TO EACH OTHER, FABRICATED GANG TYPE HANGERS MAY BE USED IN LIEU OF THE SPECIFIED HANGERS. GANG HANGERS SHALL BE CONSTRUCTED OF UNISTRUT OR OTHER APPROVED MATERIAL SPECIFICALLY DESIGNED FOR THIS APPLICATION. PIPE SADDLE CLAMPS, PIPE SADDLE INSULATION PROTECTORS OR ROLLER CLAMPS SHALL BE USED IN CONJUNCTION WITH THE UNISTRUT AS APPLICABLE. CLAMPS SHALL BE CONSTRUCTED OF 18 GAUGE STEEL. GANG HANGERS SHALL BE SIZED TO PROVIDE FOR INSULATION AND PIPE SADDLES FOR INSULATED PIPING WHEN APPLICABLE. NEOPRENE PROTECTORS SHALL BE PROVIDED FOR UN-INSULATED COPPER PIPING. 3.6. ALL HANGERS SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE BY STEEL THREADED RODS AS REQUIRED. THREADED RODS IN CONTACT WITH COPPER OR BRASS PIPING SHALL BE COPPER OR PLASTIC COATED. STEEL ROD SIZES SHALL BE AS FOLLOWS: PIPE SIZE 1/2" TO 2" - 3/8" ROD PIPE SIZE 21/2" TO 4" - 1/2" ROD PIPE SIZE 5" TO 8" - 5/8" ROD PIPE SIZE 10" & LARGER - 3/4" ROD 3.7. PIPE SADDLE INSULATION PROTECTORS SHALL BE PROVIDED FOR ALL HORIZONTAL INSULATED PIPING. PIPE SADDLES SHALL BE CONSTRUCTED OF GALVANIZED STEEL, FORMED TO A 180 DEGREE ARC, 12 INCHES LONG, EQUAL TO FIGURE 265P, 18 GAUGE TYPE H. 3.8. HANGER RODS FOR INSTALLATIONS OTHER THAN THOSE SPECIFIED SHALL BE SIZED IN ACCORDANCE WITH THE RECOMMENDED LOAD CAPACITIES OF ASTM SPECIFICATION A-107. 3.9. INSERTS SHALL BE INDIVIDUAL OR STRIP TYPE OF PRESSED STEEL CONSTRUCTION WITH ACCOMMODATION FOR REMOVABLE NUTS AND THREADED RODS UP TO 3/4" DIAMETER, PERMITTING LATERAL ADJUSTMENT. INDIVIDUAL INSERTS SHALL HAVE AN OPENING AT THE TOP TO ALLOW REINFORCING RODS UP TO 1/2" DIAMETER TO BE PASSED THROUGH THE INSERT BODY. STRIP INSERTS SHALL HAVE ATTACHED RODS WITH HOOKED ENDS TO ALLOW FASTENING TO REINFORCING RODS. 3.10. SEISMIC RESTRAINTS: PROVIDE SEISMIC RESTRAINTS IN ACCORDANCE WITH THE MASSACHUSETTS STATE BUILDING CODE, CURRENT ADOPTED EDITION. 4. 5. 6. SLEEVES AND ESCUTCHEONS: 4.1. ALL PIPING PASSING THROUGH INTERIOR FLOORS, WALLS, OR PARTITIONS SHALL BE PROVIDED WITH SLEEVES HAVING AN INTERNAL DIAMETER 1" LARGER THAN THE OUTSIDE DIAMETER OF THE PIPE (OR INSULATION), PROVIDING A MINIMUM 1/2" ANNULAR SPACE AROUND THE PIPE. 4.2. SLEEVES THROUGH INTERIOR NON-MASONRY WALLS OR PARTITIONS SHALL BE 22 GAUGE GALVANIZED SHEET STEEL. SLEEVES THROUGH INTERIOR MASONRY WALLS SHALL BE SCHEDULE 40 BLACK STEEL PIPE. 4.3. ALL PIPING PASSING THROUGH EXTERIOR WALLS SHALL BE PROVIDED WITH SLEEVES HAVING AN INTERNAL DIAMETER 3" LARGER THAN THE OUTSIDE DIAMETER OF THE PIPE, PROVIDING A MINIMUM 11/2" ANNULAR SPACE AROUND THE PIPE. 4.4. SLEEVES THROUGH EXTERIOR WALLS SHALL EXTEND A MINIMUM OF 6" BEYOND THE INTERIOR AND EXTERIOR SURFACE AND SHALL BE PROVIDED WITH A NEOPRENE BOOT ON EACH SIDE OF THE SLEEVE ATTACHED TO THE PIPE PROVIDING A WATERTIGHT FLEXIBLE SEAL. 4.5. ESCUTCHEONS SHALL BE PROVIDED WHERE PIPING PASSES THROUGH WALLS OR FLOORS EXPOSED TO VIEW. ESCUTCHEONS SHALL BE CHROME PLATED BRASS OR COPPER TYPE WITH A SET SCREW TO PROPERLY HOLD ESCUTCHEON IN PLACE. SMOKE AND FIRE STOPPING: 5.1. ALL PIPING PASSING THROUGH SMOKE OR FIRE RATED WALLS, FLOORS, OR CEILINGS SHALL HAVE STEEL SLEEVES EXTENDING 2" BEYOND THE RATED SURFACE. THE ANNULAR SPACE BETWEEN THE PIPING AND THE SLEEVE SHALL BE COMPLETELY SEALED WITH APPROVED FIRE STOPPING MATERIAL. PIPE INSULATION: 6.1. INSULATION SHALL BE OWENS CORNING, CERTAIN-TEED, KNAUF OR APPROVED EQUAL. ALL INSULATION, MASTICS, ADHESIVES, COVERS AND RELATED WORK SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND PUBLISHED LITERATURE. MATERIALS SHALL MEET REQUIREMENTS OF THE ADHESIVE AND SEALANT COUNCIL STANDARDS. 6.2. ALL INSULATION (AS INSTALLED) SHALL HAVE COMPOSITE FIRE AND SMOKE HAZARD RATINGS AS TESTED BY PROCEDURE ASTM-E-84, MFPA-255, AND UL-723, NOT EXCEEDING A FLAME SPREAD OF 25 AND SMOKE DEVELOPED OF 50 WHEN COMPARED WITH RED OAK AS 100, AS PER NFPA AND NMFU PAMPHLETS 90A AND 90B. TRANSMISSION RATES OF VAPOR BARRIERS SHALL NOT EXCEED 0.002 PERMS. 6.3. ALL SEALERS, TAPE, ADHESIVES AND MASTICS USED IN CONJUNCTION WITH THE INSULATION SPECIFIED HEREIN SHALL POSSESS THE MAXIMUM POSSIBLE FIRE-SAFE REQUIREMENTS PER CODE AND SHALL BE OF A TYPE APPROVED BY UNDERWRITERS LABORATORIES (UL), FACTORY MUTUAL (FM) OR THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA). 2.3. PIPE, FITTINGS AND JOINTS IN PVC-DWV PIPING SYSTEMS SHALL BE ASSEMBLED USING APPROVED SCHEDULE 40 PIPE, PVC DRAINAGE WASTE AND VENT FITTINGS WITH SOLVENT WELDED JOINTS, ALL ASSEMBLED TO PROVIDE A WATERTIGHT SEAL. PIPING SHALL BE CUT CLEAN, SQUARE AND TRUE. PIPING ENDS SHALL BE SMOOTH AND FREE OF ANY BURRS. PIPE AND FITTINGS SHALL BE FIRMLY SET, PROPERLY ALIGNED USING APPROVED PRIMER AND SOLVENT CEMENT IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. ALL PIPE AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE PLASTIC PIPE INSTITUTE (PPI) STANDARDS. 2.4. PIPE, FITTINGS AND JOINTS IN ACID RESISTANT POLYPROPYLENE PIPING SYSTEMS SHALL BE ASSEMBLED USING APPROVED SCHEDULE 40 PIPE, POLYPROPYLENE DRAINAGE WASTE AND VENT FITTINGS WITH FUSION SEAL WELDED JOINTS, ALL ASSEMBLED TO PROVIDE A WATERTIGHT SEAL. PIPING SHALL BE CUT CLEAN, SQUARE AND TRUE. PIPING ENDS SHALL BE SMOOTH AND FREE OF ANY BURRS. PIPE AND FITTINGS SHALL BE FIRMLY SET, PROPERLY ALIGNED AND FUSION WELDED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. ALL PIPE AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE PLASTIC PIPE INSTITUTE (PPI) STANDARDS. 2.5. PIPE AND FITTINGS FOR THREADED STEEL, COPPER OR BRASS PIPE SHALL BE ASSEMBLED USING APPROVED PIPE OR TUBE, IPS THREADED FITTINGS AND IPS THREADS CUT SQUARE AND TRUE. FOR FIELD CUT THREADS, NOTE THE INTERNAL LENGTH OF THREADS IN FITTINGS AND PROXIMITY OF INTERNAL SEAT TO DETERMINE HOW FAR PIPE SHOULD BE THREADED INTO JOINT. ALIGN THREADS AT POINT OF ASSEMBLY. APPLY APPROPRIATE TAPE OR JOINT COMPOUND TO THE EXTERNAL PIPE THREADS. ASSEMBLE JOINT TO APPROPRIATE THREAD DEPTH. DO NOT USE PIPE WITH DAMAGED THREADS. ALL PIPE AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH ANSI SPECIFICATION B120.1 FOR TAPERED PIPE THREADS. 6.4. VALVES, FITTINGS, FLANGES AND ACCESSORIES SHALL HAVE THE SAME INSULATION THICKNESS AS THE ADJACENT PIPE. FITTING COVERS SHALL BE OF THE FACTORY MOLDED PLASTIC TYPE. 6.5. LONGITUDINAL SEAMS AND END JOINT SEALING STRIPS SHALL BE SEALED WITH A FIRE RETARDANT COATING HAVING A VAPOR TRANSMISSION OF NO MORE THAN 1.0 PERM. ENDS OF INSULATION AT TERMINATION POINTS AND AT PIPE SUPPORTS SHALL BE SEALED WITH A BRUSH COAT OF VAPOR BARRIER COATING. 6.6. ALL WATER AND HOT WATER / RECIRC PIPING AND FITTINGS SHALL BE I INSULATED WITH FIBERGLASS INSULATION AND ALL SERVICE VAPOR JACKET. THICKNESS (MINIMUM) AS FOLLOWS: 6.6.1. COLD WATER IN HEATED SPACE, 1/2". 6.6.2. COLD WATER AND TRAP PRIMER LINES HEAT TRACED IN UNHEATED SPACE, 1". 6.6.3. HOT WATER / RECIRC UNDER 11/2" DIAMETER, 1". 6.6.4. HOT WATER / RECIRC 11/2" DIAMETER AND OVER, 11/2". 7. ANY ABOVE GROUND RAIN / STORM WATER PIPING AND FITTINGS (INCLUSIVE OF ROOF DRAIN BODIES) SHALL BE INSULATED WITH ONE INCH THICK FIBERGLASS INSULATION AND ALL SERVICE VAPOR JACKET. DUCT WRAP SHALL NOT BE ALLOWED ON PIPING. 8. ABOVE GROUND SANITARY WASTE PIPING HEAT TRACED IN UNHEATED AREAS SHALL BE THE SAME AS FOR RAIN / STORM WATER ABOVE AND BE 1" THICK. 9. CLEANOUTS: 9.1. SHALL BE AS MANUFACTURED BY JR SMITH, JOSAM, ZURN OR APPROVED EQUAL. REFER TO THE DRAWINGS AND SCHEDULES FOR TYPES AND PERFORMANCE CRITERIA. 9.2. CLEANOUTS IN CAST IRON WASTE PIPING SHALL BE STANDARD PIPE SIZE CONFORMING IN THICKNESS TO THAT REQUIRED FOR PIPE AND FITTINGS AND SHALL EXTEND NOT LESS THAN 3/4" ABOVE THE HUB OF THE PIPE. THE CLEANOUT PLUG SHALL BE OF CAST BRASS AND SHALL BE PROVIDED WITH A RAISED NUT, 3/4" HIGH. CLEANOUTS IN COPPER WASTE PIPING SHALL BE SOLDERED CAST BRASS CLEANOUT FITTINGS WITH EXTRA HEAVY BRASS SCREW PLUGS OF THE SAME SIZE AS THE PIPING. 10. ACCESS PANELS: 10.1. ACCESS PANELS SHALL BE AS MANUFACTURED BY MICRO PRODUCTS, VENTLOCK, KNAPP OR APPROVED EQUAL. MINIMUM SIZE SHALL BE 12"x12". ACCESS PANELS SHALL BE FIRE RATED WHERE REQUIRED. 10.2. FURNISH ACCESS PANELS AS REQUIRED FOR PIPING COMPONENTS AND EQUIPMENT SUCH AS CLEANOUTS, VALVES, SHOCK ARRESTERS, ETC., LOCATED WITHIN CONCEALED WALLS AND CEILINGS. PIPING SHALL BE LAID OUT IN SUCH A MANNER AS TO MINIMIZE THE NUMBER OF ACCESS PANELS REQUIRED. LOCATE COMPONENTS REQUIRING ACCESS ABOVE ACCESSIBLE CEILINGS WHERE POSSIBLE. COORDINATE THE LOCATION OF ACCESS PANELS WITH THE GENERAL CONTRACTOR AND APPROPRIATE SUBCONTRACTOR FOR PROPER INSTALLATION. 11. PLUMBING FIXTURES: 11.1. PROVIDE PLUMBING FIXTURES AND TRIM COMPLETE WITH FAUCETS, FIXTURE CARRIERS, DRAIN OUTLETS, TAILPIECES, P-TRAPS AND STOPS AND SUPPLIES. REFER TO THE DRAWING SCHEDULES FOR FIXTURE TYPES, MODEL NUMBERS AND PERFORMANCE CRITERIA. 11.2. VITREOUS CHINA AND ENAMELED CAST IRON PLUMBING FIXTURES SHALL BE AS MANUFACTURED BY KOHLER, AMERICAN STANDARD, ELJER OR APPROVED EQUAL. STAINLESS STEEL SINKS SHALL BE AS MANUFACTURED BY ELKAY, JUST, OR APPROVED EQUAL. WATER COOLERS SHALL BE AS MANUFACTURED BY HALSEY TAYLOR, ELKAY, OASIS, OR APPROVED EQUAL. MOP RECEPTORS AND SERVICE SINKS SHALL BE AS MANUFACTURED BY FIAT, STERN-WILLIAMS, MUSTEE, OR APPROVED EQUAL. 11.3. PLUMBING FIXTURE FAUCETS AND TRIM SHALL BE AS MANUFACTURED BY KOHLER, AMERICAN STANDARD, ELJER OR APPROVED EQUAL. 11.4. EMERGENCY EYE AND FACE WASH FIXTURES SHALL BE AS MANUFACTURED BY GUARDIAN OR APPROVED EQUAL. 11.5. DRAINAGE SPECIALTIES SUCH AS FLOOR DRAINS, AREA DRAINS, ROOF DRAINS AND CLEAN OUTS SHALL BE AS MANUFACTURED BY WATTS, JR SMITH, ZURN OR APPROVED EQUAL. 11.6. STOPS AND SUPPLIES SHALL BE AS MANUFACTURED BY KOHLER, AMERICAN STANDARD, ELJER, McGUIRE, OR APPROVED EQUAL. STOPS AND SUPPLIES SHALL BE COPPER SWEAT EXTENSION TYPE WITH COPPER RISER, ESCUTCHEON, LOOSE KEY UNLESS OTHERWISE NOTED AND CHROME PLATED BRASS WHERE EXPOSED. 11.7. P-TRAPS SHALL BE 17 GAUGE CAST BRASS WITH CLEANOUT, CHROME PLATED WHERE EXPOSED. TRAPS SHALL BE 11/4"x11/2" FOR LAVATORIES AND 11/2"x11/2" FOR SINKS. 11.8. FIXTURES DESIGNATED FOR BARRIER FREE USE SHALL BE MOUNTED IN ACCORDANCE WITH THE AMERICANS WITH DISABILITIES ACT (ADA) AS WELL AS MAAB, STATE AND LOCAL CODES. 12. PLUMBING EQUIPMENT: 12.1. PROVIDE PLUMBING EQUIPMENT COMPLETE WITH ALL ASSOCIATED SERVICE VALVES, DRAIN VALVES, COMPONENTS AND MOUNTING HARDWARE AS REQUIRED FOR A COMPLETE INSTALLATION. REFER TO THE DRAWING SCHEDULES FOR EQUIPMENT TYPES, MODEL NUMBERS AND PERFORMANCE CRITERIA. 12.2. DOMESTIC WATER HEATERS SHALL BE AS MANUFACTURED BY AO SMITH, STATE, RHEEM, OR APPROVED EQUAL. 12.3. HOT WATER RECIRC PUMPS SHALL BE AS MANUFACTURED BY TACO, BELL & GOSSETT, THRUSH OR APPROVED EQUAL. 12.4. GAS, SAND AND OILY WATER RETENTION WATERTIGHT GAS AND SAND TRAP SHALL BE AS MANUFACTURED BY SHEA CONCRETE PRODUCTS OR APPROVED EQUAL. 13. HEAT TRACING 13.1. HEAT TRACING SHALL BE CHROMALOX CPR CABLE SELF- REGULATING POLYMER CORE CABLE AND CONNECTIONS KITS, OR EQUAL, CUT-TOLENGTH 3 WATTS/FT 208-277V AND FEATURES 16 GAUGE COPPER BUS WIRES TO PERMIT MAXIMIZE CIRCUIT LENGTHS. 3. 4. 5. 6. 7. 273 CORPORATE DRIVE PORTSMOUTH, NH 03801 T 603.436.2551 F 603.436.6973 www.jsainc.com DESIGN ARCHITECT Bexhill Group 1907 Sabine Street, Suite 140 Houston, TX 77007 713 300 4999 VALVES AND SPECIALTIES INSTALLATION: 3.1. VALVES SHALL BE INSTALLED ON ALL COLD AND HOT WATER SYSTEMS, ABOVE ACCESSIBLE CEILINGS, AT ALL BRANCHES FROM MAINS, GROUPS OF PLUMBING FIXTURES, EQUIPMENT SOURCES AND OTHER LOCATIONS AS REQUIRED TO FACILITATE THE SHUT-DOWN, DRAINING, RE-FILLING AND MAINTENANCE OF SYSTEMS. 3.2. SHOCK ARRESTERS SHALL BE INSTALLED ON ALL COLD AND HOT WATER PIPING, ABOVE ACCESSIBLE CEILINGS, AT GROUPS OF PLUMBING FIXTURES OR EQUIPMENT THAT MAY PRODUCE WATER HAMMER IN ACCORDANCE WITH PDI STANDARD WH201. PLUMBING FIXTURE AND EQUIPMENT INSTALLATION: 4.1. INSTALL PLUMBING FIXTURES, FAUCETS, TRIM, CARRIERS, STOPS, SUPPLIES AND ALL RELATED COMPONENTS IN ACCORDANCE WITH THE MANUFACTURES USERS RECOMMENDATIONS. 4.2. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH LOCAL, STATE AND FEDERAL CODES AND MANUFACTURE'S APPROVED LITERATURE. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE, REPAIR AND REPLACEMENT. EQUIPMENT THAT IS COMPRISED OF PUMPS OR MOTORS SHALL BE PROVIDED WITH SPRING VIBRATION ISOLATION MOUNTS OR HANGERS TO MINIMIZE SOUND AND VIBRATION TRANSMISSION TO THE BUILDING STRUCTURE. VIBRATION ISOLATORS SHALL HAVE 95" EFFICIENCY AT ALL FREQUENCIES. 4.3. PROVIDE FACTORY START-UP, SHAKE DOWN AND COMMISSIONING FOR ALL EQUIPMENT PROVIDED UNDER THIS SECTION. TRAINED FACTORY PERSONNEL SHALL ENSURE PROPER START-UP, COMMISSIONING AND OPERATION OF EACH PIECE OF EQUIPMENT. NOTIFY THE OWNER AND ARCHITECT/ENGINEER IN ADVANCE SO THAT PERSONNEL MAY WITNESS ALL START-UPS. PROVIDE FACTORY TRAINING IN THE OPERATION OF ALL EQUIPMENT TO THE OWNER'S DESIGNATED PERSONNEL. CLEANING, FLUSHING AND PROJECT MAINTENANCE: 5.1. FLUSH ALL SYSTEMS UNTIL CLEAN. DISINFECT ALL POTABLE COLD AND HOT WATER SYSTEMS WITH CHLORINE IN ACCORDANCE WITH THE PLUMBING CODE REQUIREMENTS. ADJUST ALL SYSTEMS FOR PROPER WATER FLOW AND TEMPERATURE AS REQUIRED. 5.2. UNUSED MATERIAL AND WASTE DEBRIS RESULTING FROM THE PERFORMANCE OF WORK SHALL BE REMOVED ON A REGULAR BASIS TO AN ONSITE LOCATION. HAZARDOUS MATERIALS AND WASTE SHALL BE DISPOSED OF IN ACCORDANCE WITH THE EPA AND ALL LOCAL, STATE AND NATIONAL CODES OR ORDINANCES. TESTING, BALANCING AND ADJUSTING: 6.1. TEST AND PROVIDE INSPECTIONS FOR ALL SYSTEMS IN ACCORDANCE WITH THE PLUMBING CODE. SANITARY WASTE AND VENT SYSTEMS SHALL BE TESTED WITH A MINIMUM OF 10 FOOT HEAD OF WATER. DOMESTIC WATER SYSTEMS SHALL BE TESTED WITH POTABLE WATER UNDER A MINIMUM PRESSURE OF 150 PSIG OR 1.50 TIMES THE WORKING STREET PRESSURE. GAS SYSTEMS SHALL BE TESTED UNDER A MINIMUM PRESSURE OF 100 PSIG AND SUBJECT TO LOCAL INSPECTION. 6.2. UPON COMPLETION OF EACH SYSTEM TEST, PROVIDE COMPLIANCE TEST CERTIFICATES FOR EACH SYSTEM AS NOTED ABOVE. 6.3. BALANCE AND ADJUST THE DOMESTIC HOT WATER RECIRC SYSTEM IN ACCORDANCE WITH THE PLUMBING CODE. CHECK THE OPERATION OF EVERY PUMP, MOTOR, DRIVE AND DAMPER OPERATOR. MAKE ALL REQUIRED BALANCING AND ADJUSTMENTS TO BRING THE SYSTEM TO WITHIN PLUS OR MINUS 5% OF THE DESIGN CONDITIONS. CIVIL Hoyle Tanner & Associates, Inc. Pease International Tradeport 100 International Drive, Suite 360 Portsmouth, NH 03801 603-413-2904 STRUCTURAL Summit Engineering 5 Greenleaf Woods Drive, #302 Portsmouth, NH 03801 t. (603) 319-1817 MEP FP CSI Engineering LLC Portsmouth, NH 03801 Tel # 603-319-8244 hvac CSI Engineering fire protection plumbing 3. RELATED DOCUMENTS AND GENERAL REQUIREMENTS: 1.1. THIS PLUMBING CONTRACTOR SHALL PROVIDE "CERTIFICATE OF INSURANCE" SHOWING CONTRACTOR'S LIABILITY INSURANCE IN AMOUNTS AS REQUIRED BY THE OWNER. 1.2. REVIEW ALL ARCHITECTURAL, STRUCTURAL, CIVIL, HVAC, ELECTRICAL, FIRE PROTECTION AND PLUMBING DRAWINGS TO IDENTIFY CONDITIONS AFFECTING THE WORK OF THIS SECTION. VISIT SITE AND NOTE EXISTING CONDITIONS. NOTIFY ANY DISCREPANCIES TO THE ARCHITECT IN WRITING. 1.3. ALL WORK COVERED CONSISTS OF FURNISHING ALL MATERIALS, LABOR, EQUIPMENT AND SUPPLIES NECESSARY TO PROVIDE A COMPLETE WORKING SYSTEM REQUIRED PER THE DESIGN DRAWINGS AND MASSACHUSETTS STATE CODES. 1.4. ALL EQUIPMENT AND MATERIALS FURNISHED UNDER THE PLUMBING CONTRACT, LABOR, AND TESTING PERFORMED HEREIN SHALL BE IN COMPLETE ACCORDANCE WITH THE MASSACHUSETTS STATE BUILDING CODE, INTERNATIONAL FUEL GAS CODE, STATE PLUMBING CODE, LOCAL ORDINANCES AND REGULATIONS OF THE CITY OR TOWN, NATIONAL FIRE PROTECTION ASSOCIATION AND INSURANCE REGULATIONS AND REQUIREMENTS GOVERNING SUCH WORK. 1.5. PRIOR TO BID: THE PLUMBING SUBCONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH ALL TRADE DRAWINGS AND ASPECTS OF THE SCOPE AND EXISTING CONDITIONS TO WHICH THE WORK WILL BE INSTALLED. ANY DISCREPANCIES BETWEEN THE SCOPE OF WORK SHOWN ON THE DRAWINGS AND ANY CONDITIONS SHALL BE SUBMITTED TO THE ARCHITECT IN WRITING. FAILURE OF THE CONTRACTOR TO DO SO SHALL NOT CONSTITUTE AN EXTRA TO THE CONTRACT. 1.6. THIS CONTRACTOR SHALL CAREFULLY COORDINATE ALL WORK INSTALLED WITH THAT OF ALL OTHER TRADES. PROTECT ALL NEW AND EXISTING WORK BEFORE, DURING AND AFTER INSTALLATION. 1.7. CERTIFICATES OF APPROVAL: UPON COMPLETION OF ALL WORK, THE PLUMBING SUBCONTRACTOR SHALL FURNISH, IN DUPLICATE, CERTIFICATES OF INSPECTIONS FROM ALL INSPECTORS AND AUTHORITIES HAVING JURISDICTION, NOTARIZED LETTERS FROM THE MANUFACTURERS STATING THAT AUTHORIZED FACTORY ENGINEERS HAVE INSPECTED AND TESTED THE INSTALLATION OF THEIR RESPECTIVE SYSTEMS AND FOUND TO BE IN PERFECT OPERATING CONDITION. 1.8. DEMOLITION WORK: PARTICULAR CARE SHALL BE TAKEN TO AVOID CREATING HAZARDS ON THE SITE OR CAUSING DISRUPTION OF SERVICE IN THE BUILDING. ALL EXISTING EQUIPMENT TO BE REMOVED SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. ALL EXISTING EQUIPMENT TO BE TURNED OVER TO THE OWNER SHALL BE PRESENTED TO THE OWNER IN GOOD CONDITION AT A LOCATION DESIGNATED BY THE OWNER. ALL OTHER EQUIPMENT SHALL BE REMOVED FROM THE PREMISES. REMOVE ALL ABANDONED PIPING AND EQUIPMENT NOT BUILT INTO BUILDING CONSTRUCTION. WHERE CEILING OR WALLS ARE REMOVED, ALL ABANDONED PIPING SHALL BE REMOVED AND ENDS OF LIVE SERVICES CAPPED. ABANDONED ELEMENTS BUILT INTO WALLS OR LOCATED ABOVE EXISTING INACCESSIBLE CEILINGS SHALL REMAIN AND ENDS CAPPED AND MARKED ABANDONED. 1.9. CONTINUITY OF SERVICES: SERVICES SHALL NOT BE INTERRUPTED WITHOUT OWNER'S APPROVAL. WHEN AN INTERRUPTION OF SERVICE BECOMES NECESSARY, CONTRACTOR SHALL CONSULT WITH THE OWNER AND SCHEDULE THE PROPER TIME TO DO THE SHUT-DOWN. SCHEDULE MUST NOT DELAY NOR INTERFERE WITH THE PROGRESS OF THE PROJECT. electrical 1. This CAD Document is an instrument of professional service, and shall not be used, in whole or in part, for any project other than for which it was created without the express, written consent of CSI ENGINEERING LLC. Any unauthorized use, reuse, modification or alteration, including automated conversion of this document shall be at the user's sole risk without liability or legal exposure to CSI ENGINEERING LLC ©2010 - 2022 CSI ENGINEERING LLC. 125 AVIATION AVE. SUITE 4 PORTSMOUTH, NH 03801 603-319-8244 MILLION AIR- PEASE EXETER ROAD PORTSMOUTH, NH 03801 Sullivan Construction, LLC. PIPE IDENTIFICATION AND VALVE TAGS: 7.1. ALL PLUMBING SYSTEMS SHALL BE LABELED AT EACH VALVE, AT EACH BRANCH, AT EACH PIPE PASSAGE THROUGH WALL AND AT INTERVALS OF NOT MORE THAN 20 FEET WITH COLOR CODED SEMI-RIGID SETMARK PIPE MARKERS WITH ARROWS INDICATING THE DIRECTION OF FLOW. ALL VALVES SHALL BE TAGGED WITH 1-1/2 INCH DIAMETER BRASS TAGS AND NUMBERED IN SEQUENCE FROM POINT OF ORIGIN. VALVE CHARTS SHALL BE PLACED UNDER GLASS, FRAMED AND PRESENTED TO THE OWNER. C. EXECUTION 1. 2. GENERAL INSTALLATION: 1.1. INSTALL SYSTEMS PER CODE, AS STRAIGHT AND DIRECT AS POSSIBLE, NEATLY SPACED, FORMING RIGHT ANGLES OR PARALLEL LINES WITH THE BUILDING STRUCTURE. HORIZONTAL RUNS OF PIPING SHALL BE INSTALLED AS HIGH AND AS TIGHT TO STRUCTURE AS POSSIBLE. IT SHALL BE POSSIBLE TO DRAIN THE WATER FROM ALL SECTIONS PIPING. PITCH PIPING BACK TO DRAIN VALVES AS REQUIRED. VERTICAL RISERS SHALL BE FIRMLY SUPPORTED BY RISER CLAMPS AND HANGERS. COMPLY WITH CODE REQUIREMENTS FOR SUPPORT SPACING AND LOCATIONS. PROVIDE SEISMIC PROTECTION WHERE REQUIRED BY CODE. 1.2. ALL PIPING SHALL BE KEPT A SUFFICIENT DISTANCE FROM OTHER WORK SO THAT FINISHED SURFACES ARE NOT LESS THAN 2 INCHES FROM OTHER WORK. 1.3. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE STRUCTURAL ENGINEER AS REQUIRED. ALL OPENINGS SHALL BE SIZED FROM APPROVED SHOP DRAWINGS. PIPING, FITTING AND JOINT INSTALLATION: 2.1. PIPE, FITTINGS AND JOINTS IN COPPER SYSTEMS SHALL BE ASSEMBLED USING APPROVED COPPER TUBE, COPPER OR CAST BRASS SWEAT FITTINGS, LEAD FREE SOLDER AND NON-CORROSIVE FLUX. PIPING SHALL BE REAMED SMOOTH AFTER CUTTING. ALL PIPE AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE COPPER DEVELOPMENT ASSOCIATION (CDA) STANDARDS. 2.2. PIPE, FITTINGS AND JOINTS IN HUBLESS CAST IRON SYSTEMS SHALL BE ASSEMBLED USING APPROVED MECHANICAL COMPRESSION TYPE COUPLINGS CONSISTING OF NEOPRENE COLLAR, STAINLESS STEEL BOLTS AND NUTS ALL ASSEMBLED TO PROVIDE A WATERTIGHT SEAL. PIPE, FITTINGS AND JOINTS IN HUB AND SPIGOT CAST IRON SYSTEMS SHALL BE ASSEMBLED USING APPROVED CAST IRON PIPE, RESILIENT RUBBER GASKETED PUSH JOINTS AND LUBRICANT. ALL CAST IRON PIPE AND FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE CAST IRON SOIL PIPE INSTITUTE (CISPI) STANDARD 301-75 AND PAMPHLET 100. Scale: Date: Project Number: 12.02.2022 2021-167 REVISIONS NO. DESCRIPTION DATE PROGRESS SET 12.02.2022 NOT FOR CONSTRUCTION SPECIFICATIONS P4.01 COPYRIGHT C 2022