Steam Test Procedure for Horizontal Sterilizer prior to testing and commissioning
(1. ALL VALVES AS MENTIONED BELOW ARE TO BE OPENED / CLOSED MANUALLY,
AND ALL BY PASS VALVES, if any ARE TO BE CLOSED AT ALL TIMES.)
2. Fixed Saddle foundation Hold Down Nuts be taken out during steam test.
Step 1: Closed Both Doors.
Check and ensure all valves and steriliser door, are fully closed. (SAFE)
Step 2
Open Condensate Valve, followed by Steam Inlet valve gradually open 15%.
Feed in steam for 20 minutes
Open steam inlet valve 30% and feed in steam 30 minutes.
Check the condensate exhaust until hot air/steam ventilation.
Check the expansion of sterilizer’s body.
Step 3
Close Condensate Valve
Open steam inlet valve 60% Raise pressure to 3psi and close the Steam Inlet valve
Maintain for 15 minutes
Step 4
Close steam inlet valve, Open Condensate Valve
Release pressure to 0 psi
Step 5
Open Steam Inlet Valve 80%
Close Condensate Valve
Raise pressure to 7psi and close the Steam Inlet Valve
Maintain for 15 minutes
Step 6
Open Condensate Valve
Release pressure to 0 psi
Step 7
Open Steam Inlet Valve 80%
Close Condensate Valve
Raise pressure to 15psi and close the Steam Inlet Valve
Maintain for 15 minutes, check if any steam leaking and expansion of shell body.
Step 8
Open Condensate Valve
Release pressure to 0 psi
Step 9
Open Steam Inlet Valve 100%
Close Condensate Valve
Raise pressure to 30psi and close the Steam Inlet Valve
Maintain for 15 minutes, check if any steam leaking
Step 10
Open Condensate Valve
Release pressure to 0 psi
Step 11
Open Steam Inlet Valve 100%
Close Condensate Valve
Raise pressure to 45psi and close the Steam Inlet Valve
Maintain for 15 minutes, check if any steam leaking
Set the pressure relief valve accordingly.
Step 12
Open Condensate Valve
Release pressure to 0 psi
The sterilizer shall back to it normal position check the saddles support.
Steam test of new sterilizer must be in very patient and gradually step by step. The above procedure is for
reference only without obligation.
The Sterilizer is now ready for Testing & Commissioning with FFB.