Design of Structural Elements 120 5.2.8 Steel Reinforcement Modulus of Elasticity: Es (Clause 2.4.2.3) The modulus of elasticity of reinforcement is equal to tanθ, where θ is the angle of the linear section of the stress-strain curve given in Figure 2.2 of the code. This should be taken as 200 kN/mm2 as indicated in Figure 5.12. 5.2.9 Material Partial Safety Factors: γm (Clause 2.4.4.1) As indicated in Section 2.4 when using limit state design: Design strength = Characteristic strength γm The appropriate values of γm for concrete and reinforcement are given in Table 2.2 of Clause 2.4.4.1 as: γm = = = = ≥ 1.5 1.25 1.4 1.05 1.5 for concrete in flexure or axial load, for concrete shear strength without reinforcement, for bond strength between the reinforcement and the concrete, for reinforcement, for other conditions e.g. bearing stresses. 5.2.10 Durability (Clauses 2.2.4 and 3.1.5) The integrity of reinforced concrete depends on its ability to prevent corrosion of the reinforcement when exposed to a wide range of environmental conditions, e.g. ranging from ‘mild exposure’ such as concrete surfaces protected against weather or aggressive conditions to ‘most severe’ or ‘abrasive’ conditions in which concrete surfaces may be frequently exposed to sea water spray, de-icing salts or the abrasive actions of machinery. The classification of exposure conditions in terms of ‘moderate’, ‘severe’, ‘very severe’, ‘most severe’ and ‘abrasive’ is defined in Table 3.2 of the code. In addition to protection against corrosion of the steel (Table 3.3), fire resistance requirements (Table 3.4) are also necessary to allow sufficient time to evacuate a building and prevent premature failure, spalling of the concrete must be avoided and adequate bond forces must develop between the reinforcement and the concrete. The essential elements of design which ensure adequate durability are the structural form/detailing and the amount of concrete cover provided to protect the steel, as illustrated in Figure 5.13. cover cover cover cover Figure 5.13 Design of Reinforced Concrete Elements 121 Concrete cover is defined as the thickness of concrete between the outer surface of the steel reinforcement and the nearest concrete surface. The actual concrete cover provided varies due to a number of factors such as: ♦ construction tolerances inherent in building the formwork (i.e. the mould into which the concrete is cast), ♦ variations in dimensions of the reinforcement resulting from the cutting and bending of the steel, and ♦ errors occurring during the fixing of the steel in the formwork. The limiting values of cover given in Tables 3.3 and 3.4 of the code which ensure adequate provision to satisfy durability and fire protection are specified in terms of ‘nominal’ cover to all reinforcement including the links. As indicated in Clause 3.3.1.1, the nominal cover is: ‘… the dimension used in design and indicated on the drawings. The actual cover to all reinforcement should never be less than the nominal cover minus 5 mm …’ There a number of criteria to be considered when determining the nominal cover. They are: ♦ Bar size (Clause 3.3.1.2) Single bars: nominal cover ≥ main bar diameter d1 diameter d1 Figure 5.14(a) nominal cover nominal cover Paired bars: nominal cover ≥ 2 d1 where d1 is the main bar diameter diameter d1 Figure 5.14(b) nominal cover nominal cover Bundled bars: nominal cover ≥ 2 Aequivalent π where Aequivalent is the cross-sectional area equal to the sum of the cross-sectional areas of the bars in the bundle 2 e.g. In Figure 5.14(c) Aequivalent = 4 × πd1 4 diameter d1 - Figure 5.14(c) nominal cover nominal cover 122 Design of Structural Elements ♦ Nominal maximum aggregate size (Clause 3.3.1.3) Nominal cover ≥ nominal maximum size of aggregate minimum thickness of concrete section i.e. normally ≤ 4 In most cases, 20 mm aggregate is suitable. ♦ Uneven surfaces (Clause 3.3.1.4) When concrete is cast on uneven surfaces (e.g. earth or blinding, which is finely crushed aggregate rolled on the top of compacted fill such as hardcore) additional cover to that indicated in Table 3.3 should be provided as shown in Figure 5.15. nominal cover > 75 mm uneven earth surface Concrete cast directly on the earth – nominal cover from average soil level nominal cover > 40 mm blinding layer hardcore Concrete cast on an adequate blinding layer (e.g. 50 mm thick) Figure 5.15 ♦ Ends of straight bars (Clause 3.3.2) Normally 40 mm cover is provided at the ends of straight bars, as shown in Figure 5.16, however as indicated in this clause where the end of a floor or roof unit is not exposed to the weather or to condensation, cover is not mandatory. nominal cover Figure 5.16 In Clause 7.3 of the code recommendations are given to ensure that the reinforcement is properly placed and the required cover obtained. This is achieved during construction by inserting spacer blocks and chairs in the formwork, on the reinforcement as indicated in Design of Reinforced Concrete Elements 123 Figures 5.17 and 5.18. The spacers must be designed such that they are durable and will not lead to corrosion of the reinforcement or to spalling of the concrete. The use of spacer blocks constructed on site from concrete is not permitted. Concrete spacer Plastic spacer Spacer for vertical application Figure 5.17 Single and continuous high wire chairs for top steel – particularly in cantilevers Figure 5.18 5.2.10.1 Minimum Dimensions (Clause 3.3.6 and Figure 3.2) In addition to nominal cover requirements, the code also specifies minimum dimensions (i.e. beam widths, rib widths, floor and wall thicknesses, and column widths) for some structural elements to provide adequate fire resistance. The dimensions are given to ensure minimum periods of fire resistance ranging from 0.5 hours to 4 hours and relate specifically to the covers given in Table 3.4. 5.2.11 Example 5.1: Nominal Cover 1 A rectangular reinforced concrete beam inside a building is simply supported and is required to support precast concrete units as shown in Figure 5.19. Using the data given, determine: (i) (ii) the nominal cover required to the underside of the beam, and the minimum width of beam required. Data: Exposure condition Characteristic strength of concrete Nominal maximum aggregate size Diameter of main tension steel Diameter of shear links Minimum required fire resistance (fcu) (hagg) mild 40 N/mm2 20 mm 25 mm 8 mm 1.5 hours Design of Structural Elements 124 main steel b Figure 5.19 Solution: (i) Clause 3.3.1.2 Nominal cover ≥ (main bar diameter − link diameter) ≥ (25 − 8) = 17 mm Clause 3.3.1.3 Nominal cover ≥ nominal maximum aggregate size > 20 mm Clause 3.3.3 Exposure condition is mild Grade of concrete is C40 Table 3.3 Nominal cover ≥ 20 mm* Clause 3.3.6 Minimum fire resistance = 1.5 hr The beam is simply supported Table 3.4 Nominal cover ≥ 20 mm* The required nominal cover = 20 mm *Note: Under these conditions this value can be reduced to 15 mm when the maximum aggregate size does not exceed 15 mm. (ii) Clause 3.3.6 Figure 3.2 The minimum beam width b to satisfy the required 1.5 hours. fire resistance = 200 mm 5.2.12 Example 5.2: Nominal Cover 2 A continuous, ribbed floor slab covering a car parking area is exposed on the underside and protected on the topside as shown in Figure 5.20. Using the data given determine: (i) (ii) (iii) the nominal cover required to the underside of the rib, the nominal cover required to the topside of the floor, and the minimum floor thickness and width of rib required. Data: Characteristic strength of concrete Nominal maximum aggregate size Diameter of main tension steel Diameter of shear links Minimum required fire resistance 35 N/mm2 20 mm 32 mm 10 mm 2.0 hours (fcu) (hagg) h rib width b Figure 5.20 Design of Reinforced Concrete Elements 125 Solution: (i) Clause 3.3.1.2 Nominal cover ≥ (main bar diameter − link diameter) ≥ (32 − 10) = 22 mm Clause 3.3.1.3 Nominal cover ≥ nominal maximum aggregate size ≥ 20 mm Table 3.2 Exposure condition is moderate Grade of concrete is C35 Table 3.3 Nominal cover ≥ 35 mm Clause 3.3.6 Minimum fire resistance = 2.0 h The rib is continuous Table 3.4 Nominal cover ≥ 35 mm* The required nominal cover to the underside of the ribs = 35 mm (ii) The topside of the slab is protected and hence the exposure condition is mild: Table 3.3 Nominal cover ≥ 20 mm Clause 3.3.6 Minimum fire resistance = 2.0 h The floor is continuous Table 3.4 Nominal cover ≥ 25 mm The required nominal cover to the topside of the floor = 25 mm (iii) Clause 3.3.6 Figure 3.2 The minimum rib width b to satisfy the required 2.0 hours fire resistance = 125 mm This can be achieved if the bars are placed vertically, as shown. The minimum width b required to accommodate the bars and the cover = (35 + 10 +32 + 10 + 35) = 122 mm < 125 mm If the bars are placed horizontally, assuming a gap of 25 mm (i.e. [hagg + 5 mm], see Clause 3.12.11.1), the minimum width required = [2 × (35 + 10 + 32) + 25] ≈ 180 mm > 125 mm Clause 3.3.6 Figure 3.2 The minimum floor thickness h to satisfy the required 2.0 hours fire resistance = 125 mm *Note: In the case of the cover exceeding 40 mm for dense or 50 mm for lightweight aggregate concrete there is a danger of spalling. If the ribbed slab were simply supported then Note 2 in Table 3.4 indicates that additional measures would be necessary to reduce the risks of spalling, as indicated in section 4 of BS 8110:Part 2:1985. Possible measures include an applied finish by hand or spray of plaster, the provision of a false ceiling as a fire barrier, the use of lightweight aggregates, the use of sacrificial tensile steel, or the provision of supplementary reinforcement in the form of welded steel fabric placed within the cover at 20 mm from the concrete face. Design of Structural Elements 126 5.2.13 Example 5.3: Nominal Cover 3 A ground floor slab in a warehouse building is constructed on a blinded, compacted layer of hardcore as shown in Figure 5.21. Using the data given, determine the nominal cover required to the underside of the slab. Data: Characteristic strength of concrete (fcu) Nominal maximum aggregate size (hagg) Diameter of main tension steel 35 N/mm2 20 mm 20 mm ground floor slab blinding cover hardcore Figure 5.21 Solution: (i) Clause 3.3.1.2 Nominal cover ≥ main bar diameter ≥ 20 mm Clause 3.3.1.3 Nominal cover ≥ nominal maximum aggregate size ≥ 20 mm Clause 3.3.3 Exposure condition is mild Grade of concrete is C35 Table 3.3 Nominal cover ≥ 20 mm Clause 3.3.1.4 Since this slab is cast against an adequate blinding Table 3.4 Nominal cover ≥ 40 mm The required nominal cover = 40 mm 5.3 Flexural Strength of Sections The flexural strength (i.e. the ultimate moment of resistance of a cross-section) is determined assuming the following conditions as given in Clause 3.4.4.1, BS8110:Part 1. ♦ Plane sections remain plane, i.e. surface A surface A before deformation after deformation The surface of any cross-section does not distort out-of-plane during deformation. Figure 5.22