i-AVT (Absence of Voltage Tester) Verifying De-Energization – a New, Safer and Quicker Approach. . When servicing electrical equipment, workers must comply with safety regulations where qualified personnel must establish an electrically safe work condition before work can commence on an electrical panel. The i-AVT (Absence of Voltage Tester) is a simple, fail-safe and intuitive product that ensures positive indication that current carrying conductors and circuit parts are de-energized and completes this task safely and quickly. 18.3% of facilities experienced personal injury and 11.7% experienced interruptions of operations, while using hand-held voltage testers.1 The i-AVT allows qualified personnel to verify that current carrying conductors are de-energized without opening the door to the electrical cabinet, eliminating the safety risk related to using hand-held voltage testers.. The i-AVT provides the following indications: • • • Positive indication of presence of voltage Positive indication of absence of voltage Positive indication of loss of phase Figure 1. Typical Application The i-AVT is mounted on the load side of a disconnect switch. • The i-AVT has two leads for each phase and two leads for ground. • The i-AVT provides a visual indicator to confirm the absence of voltage and the visual indication is green • The i-AVT has a supervisory circuit to ensure that the tester is functioning properly before and after the AVT performs voltage measurements. • If a phase conductor is connected to ground or a ground conductor is connected to phase, the green lights will not illuminate. • The i-AVT visual indicators will not illuminate green unless the phase conductors and ground leads are in direct contact with the circuit conductors being tested. 1 H.L Floyd and B.J Nenninger, “Personnel Safety and Plant Reliability Considerations in the Selection and Use of Voltage Test Instruments”, IEEE Transactions on Industry Applications, vol.33, no. 2, pp. 367-373, 1997 Phone: 905-673-1553 Toll Free: 1-888-737-4787 Fax: 905-673-8472 support@i-gard.com www.i-gard What Happens Once The Test Button is Pressed? Supervisory circuit verifies the phase voltage lights are off Supervisory circuit verifies the sensor leads are connected Supervisory circuit verifies that the energy level on the bus is low enough to conduct the test Supervisory circuit verifies that the voltage source is sufficient to conduct the test Test to verify that AC voltage is less than 3 Volts, phase to phase and phase to ground Conduct connectivity check to ensure all cables are connected correctly Test to verify that DC voltage is less than 3 Volts, phase to phase and phase to ground Conduct connectivity check to ensure all cables are connected correctly Test to verify that AC voltage is less than 3 Volts, phase to phase and phase to ground Conduct connectivity check to ensure all cables are connected correctly Test to verify that DC voltage is less than 3 Volts, phase to phase and phase to ground Conduct connectivity check to ensure all cables are connected correctly Supervisory circuit validates that the tester is functioning satisfactorily after completing absence of voltage test Visually Indicate results of absence of voltage test Green LED’s solid for 5 seconds indicates that there is no hazardous voltage present and it is safe to open the electrical panel. If the test fails, the Amber lights will remain illuminated advising to test again or troubleshoot the situation. Phone: 905-673-1553 Toll Free: 1-888-737-4787 Fax: 905-673-8472 support@i-gard.com www.i-gar NFPA 70E – Evolution of a Safety Standard. Article 120 Establishing an Electrically Safe Work Condition 120.5 Verification of an Electrically Safe Work Condition: 2018 (7) Use an adequately rated test instrument to test each phase conductor or circuit part to verify it is de-energized. Test each phase conductor or circuit part both phase-to-phase and phase-to-ground. Before and after each test, determine that the test instrument is operating satisfactorily through verification on a known voltage source. 120.5 Verification of an Electrically Safe Work Condition: 7) Use an adequately rated test instrument to test each phase conductor or circuit part to test for the absence of voltage. Test each phase conductor or circuit part both phase-to-phase and phase-to-ground. Before and after each test, determine that the test instrument is operating satisfactorily through verification on a known voltage source. Exception No 1: An adequately rated permanently mounted absence of voltage tester shall be permitted to be used to verify the absence of voltage… Article 120 Establishing an Electrically Safe Work Condition 120.6 Verification of an Electrically Safe Work Condition: (7) Use an adequately rated test instrument to test each phase conductor or circuit part at each point of work to test for the absence of voltage. Test each phase conductor or circuit part both phase-to-phase and phase-to-ground. Before and after each test, determine that the test instrument is operating satisfactorily through verification on a known voltage source. 2024 This Exception allowed for the use of voltage test ports. Exception No 1: An adequately rated permanently mounted test device shall be permitted to be used to verify the absence of voltage… Article 120 Establishing an Electrically Safe Work Condition 2021 Added an Exception to Rule 7, that allowed for permanently mounted test devices to be used to conduct the verification test. Rule 7 was updated and the term “verify it is de-energized” was changed to “test for the absence of voltage” The Exception was also changed and the new requirement indicated that you must use a listed absence of voltage tester to test for the absence of voltage. These changes eliminated the option to use voltage test ports. Updated Rule 7 to include the requirement to test “at each point of work”, which was always a requirement in the Exception. This clarification reinforces that position that you cannot use a voltage test port which tests at a point remote from the phase conductors or circuit parts and not at the point of work. In What Way is an Absence of Voltage Tester Different from a Voltage Test Port? The major difference between a voltage test port and an absence of voltage tester are design, functionality and certification standards. A voltage test port is a test device that is designed and tested to UL 61010 and the purpose is to measure voltage. An absence of voltage tester is designed and tested to UL 1436 and the purpose is to verify the absence of voltage, and UL contains multiple design and test clauses that a voltage test port does not comply with. The i-AVT comes in 2 models: I-AVT Standard control enclosure and display module I-AVT-R Smaller control enclosure, power source rechargeable via USB-C port on display module Certification CSA STD 22.2 #160 Certification CSA Voltage and Polarity Testers UL 1436 UL Standard for Outlet Circuit Testers and Similar Indicating Devices IEC 61508 IEC 61326-3-1 EMC Requirements IEC 61000-4-5 EMC Surge Immunity UL 61010 - 1 Transient Overvoltage Test UL 61010-2-030 Safety Requirment for Electrical Equipment for Measurement UL 746 Flammability and Impact Test IEC Functional Safety Standard IEC Electrical Equipment for Measurement and Control IEC Standard for Electrostatic Discharge UL Electrical Equipment for Measurement and Control Phone: 905-673-1553 Toll Free: 1-888-737-4787 UL Electrical Equipment for Measurement and Control UL Standard for Polymeric Enclosures Fax: 905-673-8472 support@i-gard.com www.i-gar Cost Justification of AVT Technology In addition to removing personnel from the inherent risk of conducting a live-dead-live test with the door to the electrical cabinet open, using AVT technology also saves time and money. Voltage Indicator Capital Expenditures Number of units Cost per unit Total Capital Costs Voltage Test Absence of Station Voltage Tester 1 1 $ 200.00 $ 350.00 $ 450.00 dollars* $ 200.00 $ 350.00 $ 450.00 dollars Installation Costs Time to install a unit in minutes Labor Rate (installer) Hourly rate for person performing the i-AVT installation. 30 30 45 $100.00 $100.00 $100.00 Total Installation Cost $50.00 $50.00 $75.00 Productivity Savings Time Required to Complete Absence of Voltage Test Labor Rate (tester) Hourly rate for qualified worker performing test with handheld tester. Cost per Test 30 20 0.167 $ 100.00 $50.00 $ 100.00 $33.33 $ 100.00 $0.28 Total Installed Costs Cost per Test $250.00 $50.00 $400.00 $33.33 $525.00 $0.28 How Many Tests until the AVT is more Cost Effective than a Voltage Indicator How Many Tests until the AVT is more Cost Effective than a Voltage Test Station Phone: 905-673-1553 Toll Free: 1-888-737-4787 Fax: 905-673-8472 support@i-gard.com units* 1 5.5 3.8 www.i-gar minutes* dollars/hour*