Available online at www.sciencedirect.com Available online at www.sciencedirect.com ScienceDirect ScienceDirect Procedia Engineering 00 (2017) 000–000 Available online at www.sciencedirect.com Procedia Engineering 00 (2017) 000–000 ScienceDirect www.elsevier.com/locate/procedia www.elsevier.com/locate/procedia Procedia Engineering 202 (2017) 305–311 4th International Colloquium "Transformer Research and Asset Management” 4th International Colloquium "Transformer Research and Asset Management” Transferred Voltages due to Single Phase Earth Fault on Power Transferred Voltages due to Single Phase Earth Fault on Power Transformers Transformers Kosjenka Capuder Bikića,a,*, Mislav Gazdovićaa, Franjo Kelemenaa, Aleksandar Lojpuraa Kosjenka Capuder Bikić *, Mislav Gazdović , Franjo Kelemen , Aleksandar Lojpur a a Končar Power Transformers, Josipa Mokrovića 12, Zagreb, Croatia Končar Power Transformers, Josipa Mokrovića 12, Zagreb, Croatia Abstract Abstract In the event of an earth fault in one of the two systems of a three-winding transformer, an increase in the starIn voltage the event of aninearth fault in one of the twovoltage systems a three-winding transformer, an increase the starpoint occurs the disturbed system. This is of transferred to the undisturbed systems due toincapacitive point voltage occurs in the disturbed system. This voltage is transferred to the undisturbed systems due to capacitive coupling, to affected earth faulty system and to earth. As a result, three phase voltages to earth are different in coupling, toand affected earth faulty systemto and earth. As aservice result,status. three phase voltages to earth are different in magnitude phase position compared theirtoundisturbed magnitude phase compared to theirisundisturbed service the status. In this and paper the position mesh analysis method used to calculate neutral point shift of the faulted winding In thistopaper meshofanalysis method is used calculate winding the neutral pointwhich shift isofnot theearth faulted winding necessary obtainthe values transferred voltages to thetounaffected (the one faulted). The necessary obtain values of transferred thewinding unaffected one which is not earth faulted). The results aretoanalyzed to investigate the voltages influencetoof andwinding network(the neutral grounding (insulated, solidly results aregrounded analyzedover to investigate influence grounded, impedance)the on the results.of winding and network neutral grounding (insulated, solidly grounded, grounded over impedance) on the results. © © 2017 2017 The The Authors. Authors. Published Published by by Elsevier Elsevier Ltd. Ltd. © 2017 The Authors. Published by Ltd. committee Peer-review under of the Peer-review under responsibility responsibility of Elsevier the organizing organizing committee of of ICTRAM ICTRAM 2017. 2017. Peer-review under responsibility of the organizing committee of ICTRAM 2017. Keywords: Power transformer, transient voltages, overvoltages, ground fault, neutral phase shift Keywords: Power transformer, transient voltages, overvoltages, ground fault, neutral phase shift 1. Introduction 1. Introduction The most frequent causes of temporary over voltages are faults, load rejection, resonance and ferroresonance. most frequent temporary over voltages areon faults, load rejection, ferroresonance. TheThe magnitude of over causes voltagesofdue to ground faults depends the method of systemresonance groundingand (solidly grounded, The magnitude of overhigh voltages due togrounded ground faults depends onsystems), the method system grounding grounded, resistance grounded, resistance or ungrounded theofequivalent sequence(solidly impedances seen resistance grounded, high resistance grounded or ungrounded systems), the equivalent sequence impedances seen * Corresponding author. Tel.: +38513795427 * Corresponding Tel.: +38513795427 E-mail address:author. kosjenka.capuder@siemens.com E-mail address: kosjenka.capuder@siemens.com This work has been supported in part by the Croatian Science Foundation under the project number IP-2013-1118. This work has been supported in part by the Croatian Science Foundation under the project number IP-2013-1118. 1877-7058 © 2017 The Authors. Published by Elsevier Ltd. Peer-review the organizing committee 1877-7058 ©under 2017responsibility The Authors. of Published by Elsevier Ltd. of ICTRAM 2017. Peer-review under responsibility of the organizing committee of ICTRAM 2017. 1877-7058 © 2017 The Authors. Published by Elsevier Ltd. Peer-review under responsibility of the organizing committee of ICTRAM 2017. 10.1016/j.proeng.2017.09.718 Kosjenka Capuder Bikić et al. / Procedia Engineering 202 (2017) 305–311 Kosjenka Capuder Bikić et al. / Procedia Engineering 00 (2017) 000–000 306 2 from the fault location and the fault impedance. Their duration depends on the fault clearance time and therefore on the design of the protection system. An estimation of the duration and magnitude of these over voltages is crucial for selection of surge arresters in most power systems. [1] The grounding system determines the over voltages that can occur during a fault to ground. A single phase to ground fault shifts the ground potential at the fault location, depending on the severity of this shift on the grounding configuration. On a solidly grounded system with a good return path to the grounding source, the shift is usually negligible. On an ungrounded system, a full offset may occur and the phase-to-ground voltage on the unfaulted phases approaches the phase-to-phase voltage value. [2] Nomenclature HV MV LV EFF high voltage winding of a transformer middle voltage winding of a transformer low voltage winding Earth fault factor 2. Calculation Model for single-phase to earth short circuit on MV side is presented in Pogreška! Izvor reference nije pronađen., where UrHV_U, UrHV_V and UrHV_W are rated voltages for each phase on HV side of the transformers with corresponding network inductance ZNHV. UrMV_U, UrMV_V and UrMV_W are rated voltages for each phase on MV side of the transformers with corresponding network inductance ZNMV. The calculation of the parameters from Fig. 1 is presented in [3]. Two different cases were considered: • MV network solidly grounded (ZNgr = 0 in Fig. 1) • MV network ungrounded (ZNgr = ∞ in Fig. 1) Each of those two cases will be analyzed for a range of transformer ground impedances 0 ≤ Zgr ≤ ∞. Fig. 1 Model for single phase to earth fault on MV side For short-circuit on MV side, new position of neutral point is calculated according to Fig. 1: U NMV = I 7 ⋅ Z gr [ kV ] (1) Kosjenka Capuder Bikić et al. / Procedia Engineering 202 (2017) 305–311 Kosjenka Capuder Bikić et al. / Procedia Engineering 00 (2017) 000–000 307 3 The neutral point shift of MV system is capacitevely transffered to LV system (Fig. 2) as described in (2), where CMV/LV is a capacitance between MV and LV winding and CLV0 and CMV0 are capacitances betwen LV (MV) winding and earth. Fig. 2 Capacitance system between MV and LV winding U NLV = U NMV ⋅ CMV / LV [ kV ] CMV / LV + CLV 0 For a transformer with vector group Yyd, the voltage system of MV and LV winding is as presented in Fig. 3. Fig. 3 Voltage system for MV and LV winding Maximum voltage on LV winding ULVmax is calculated according to: (2) Kosjenka Capuder al. / Procedia Engineering 202 000–000 (2017) 305–311 Kosjenka Capuder Bikić etBikić al. / et Procedia Engineering 00 (2017) 308 4 2 U LV max = U NLV 2 U U + LV − 2 ⋅U NLV ⋅ LV ⋅ cos α [ kV ] 3 3 (3) 3. Case study Calculation of transient over voltages will be performed on a real case transformer. Input data for the transformer is presented in Table 1, where Sr is rated power of the transformer; UrHV, UrMV and UrLV are rated voltages; uscHV/MV, uscHV/LV and uscMV/LV are rated short-circuit voltages between windings referred to rated power Sr. Table 1 Input data of the transformer Sr [MVA] 370 Vector group Yyd UrHV [kV] 220 UrMV [kV] 123 UrLV [kV] 24 uscHV/MV [%] 16.1 uscHV/LV [%] 44.77 uscMV/LV [%] 25.16 SscHV [MVA] 26700 SscMV [MVA] 8700 3.1. Results As mentioned, two different cases were considered: • CASE 1: MV network solidly grounded (ZNgr = 0 in Fig. 1) • CASE 2: MV network ungrounded (ZNgr = ∞ in Fig. 1) Each of them was analyzed for a range of transformer ground impedances 0 ≤ Zgr ≤ ∞. The faulted phase is phase C, while the other two phases A and B are 'healthy' phases. Results obtained for CASE 1 are presented in Table 2, where UNMV is neutral shift of the MV system; UA and UB are voltages on unfaulted phases of the MV system; UNLV is neutral shift of the LV system and ULVmax is the maximum voltage of the LV system. Table 2 Results for CASE 1 RuzMVtr [Ω] UNMV [kV] 0 1 2 3 5 7 10 25 50 100 500 ∞ 0 14.12∟-118.7° 21.02∟-99.5° 23.859∟-88.8° 25.855∟-78.2° 26.495∟-73.2° 26.86∟-69.4° 27.15∟-63.8° 27.2∟-61.9° 27.2∟-60.9° 27.22∟-60.2° - UA [kV] 69.31∟-357.5° 67.04∟-0.8° 68.22∟-3.1° 69.57∟-3.9° 71.15∟-4.2° 71.92∟-4.1° 72.5∟-4.1° 73.31∟-3.8° 73.57∟-3.7° 73.69∟-3.6° 73.79∟-3.6° 73.82∟-3.6° UB [kV] 69.31∟-122.5° 73.9∟-122.3° 75.65∟-120.5° 75.89∟-119.3° 75.56∟-118.1° 75.22∟-117.5° 74.9∟-117.2° 74.28∟-116.7° 74.05∟-116.5° 73.94∟-116.5° 73.84∟-116.4° 73.82∟-116.4° UNLV [kV] ULVmax [kV] 0 5.19 7.73 8.77 9.51 9.74 9.88 9.98 10.00 10.00 10.01 - 0 18.53 20.91 21.90 22.59 22.82 22.95 23.05 23.07 23.07 23.07 - The voltage vector system for the faulted MV winding for ground impedance of 2Ω is presented in Fig. 4. Kosjenka Capuder Bikić et al. / Procedia Engineering 202 (2017) 305–311 Kosjenka Capuder Bikić et al. / Procedia Engineering 00 (2017) 000–000 309 5 Fig. 4 Voltage vector system of MV winding for CASE 1 Vector uT (green in Fig. 4) is the neutral shift of the MV system which is then transferred to the LV system according to (2) i (3) as shown in Fig. 3. The neutral point shift of the faulted system for different transformer grounding impedances behaves as shown in Fig. 5. Maximum neutral point shift occurs for the ungrounded voltage system and in this case it's 0.3 p.u. of the rated phase-to-phase MV voltage. Fig. 5 Neutral point shift for 0 ≤ Zgr ≤ ∞, CASE 1 Kosjenka Capuder Bikić et al. / Procedia Engineering 00 (2017) 000–000 Kosjenka Capuder Bikić et al. / Procedia Engineering 202 (2017) 305–311 6 310 Results obtained for CASE 2 is presented in Table 3. Table 3 Results for CASE 2 RuzMVtr [Ω] UNMV [kV] 0 1 2 3 5 7 10 25 50 100 500 ∞ 0 15.87∟-137.1° 29.60∟-125.4° 40.23∟-115.5° 53.50∟-101.1° 60.27∟-91.9° 65.09∟-83.6° 69.95∟-69.9° 70.75∟-65° 70.90∟-62.5° 71.00∟-60.5° - UA [kV] 103.9∟-23.7° 102∟-26.3° 102.4∟-28.9° 104.3∟-30.8° 108.9∟-32.5° 112.5∟-32.9° 115.8∟-32.7° 120.5∟-31.4° 121.9∟-30.8° 122.5∟-30.4° 122.9∟-30.1° 123∟-30° UB [kV] 103.9∟-96.3° 107.8∟-98.1° 112.3∟-98.6° 116.2∟-98.4° 121∟-96.9 ° 123.2∟-95.6° 124.3∟-94.2° 124.4∟-91.7° 123.8∟-90.8° 123.5∟-90.4° 123.1∟-90.1° 123∟-90° UNLV [kV] ULVmax [kV] 0 5.83 10.88 14.79 19.67 22.16 23.93 25.72 26.01 26.07 26.10 - 0 19.13 23.91 27.67 32.42 34.85 36.59 38.35 38.64 38.69 38.73 - As in CASE 1, the neutral point shift of the faulted system behaves as shown in Fig. 6. Maximum neutral point shift occurs for the ungrounded voltage system and in this case it's 1 p.u. of the rated phase-to-phase MV voltage. Fig. 6 Neutral point shift for 0 ≤ Zgr ≤ ∞, CASE 2 Kosjenka Capuder Bikić et al. / Procedia Engineering 202 (2017) 305–311 Kosjenka Capuder Bikić et al. / Procedia Engineering 00 (2017) 000–000 311 7 4. Conclusion In symmetrical three phase systems, in case of ground faults, resulting three phase voltages against earth are different in magnitude and phase compared to their normal service values. These voltages are then transmitted to physically adjacent but potentially unconnected systems due to capacitive coupling to affected earth - faulted system, to earth and to each other. This causes a shift of neutral point in delta connection or of neutral point in star connection. The resultant voltages against earth on the terminals of the shifted system can be higher than voltages in the normal service on windings under consideration. Therefore, the calculation and analysis of such faults is necessary in order to ensure the safety of the transformer. In this paper, the case of a real transformer in service was analyzed to determine the influence of the grounding configuration on both the transformer and the network system. The results naturally confirm that for a solidly grounded transformer, there is no neutral point shift. However, for an ungrounded transformer, the neutral shift can reach the phase-to-phase voltage in case of an ungrounded network system. For solidly grounded network system, the neutral point shift is not as severe but it should be taken into account in the transformer design process. References [1] IEC 60071-2:1996-12 Standard, Insulation Co-ordination – Part 2: Application Guide [2] Juan A. Martinez-Velasco, Universitat Politecnica de Catalunya, Barcelona, Spain, Transient Analysis of Power Systems; solution techniques, tools and applications. IEEE Press [3] K. Capuder Bikić, G. Plišić, Ž. Štih, Generic Approach to Calculation of Short Circuit Currents in Power Transformers, 3rd International Colloquium Transformer Research and Asset Management, Split, Croatia, 2014