FUNCTIONING AND SIZING OF AIR VALVES By Luís M.M. da Silveira e Silva Abstract: The three main functions of 1 air valves in water supply pipelines are: I) air release under pressure, II) air admission during vacuum conditions, and III) release of large amounts of air during filling. In the present paper, they are presented the two basic types of air valves (small orifice and large orifice), analyzed the fundaments of their functioning and reviewed the usual location criteria. They are established general formulas for the flow of air through orifices (isentropic flow) which can be used to pre-size any air valve. Finally it is presented a detailed discussion concerning Function I air valves; topics include air inception, air release from flow, removal of air by water flow and pratical sizing criteria. -------------------------------------------- 1 Civil Engineer, Hydraulics and Water Resources Specialist COBA SA, Av. 5 Outubro,323. 1600-Lisboa. Portugal. 1996 Key words: Air valves, air removing, air release, isentropic flow, pipeline design INTRODUCTION Air in pressure pipelines is known to be a potential source of problems particularly if it comes out of solution and forms air pockets. Obviously, the best way to avoid air in a pipe is to avoid its entry trough careful design and proper operation of the systems; however the world is not perfect and as stated by Lescovitch (1972), “air can enter a pipeline in many insidious ways”. In the other hand, as reported by Wisner et al. (1975) the velocities required to hydraulically clear out all air-pockets, are too high, and consequently uneconomical, to be recommended. For these reasons mechanical venting is normally adopted, being air valves are the most popular choice. The present paper addresses some key questions concerning the role, location and sizing of air valves in water supply systems, and in particular along the profile of transmission pipelines. The presentation starts with the basic functions of air valves in a water system, functioning principles, main types of air valves, and the laws of air flow through orifices, whose knowledge is essential to correctly size these devices. A brief vocabulary, with some of the most common designations is presented. It follows a summary of the usual criteria for the location of a these valves according with the function of the air valve. In the final part it is presented a detailed discussion concerning the location and dimensioning criteria of the so-called Functions I air valves, i.e. valves to purge small air volumes released from the line. The focus of the discussion is directed to air inception, air conservation and to the mechanism of air release from a saturated air-water solution. FUNCTIONS The three basic functions of air valves in a pressure system are: I. air release at service pressure II. air admittance under vacuum conditions at atmospheric pressure (vacuum breaker) III. release of large amounts of air at atmospheric pressure Air release under pressure corresponds to the purging of small amounts air which came out from solution as a result of a reduction of the air solubility capacity of water, or a decrease of the hydraulic carrying capacity of air in the form of bubbles released earlier. Admission of large amounts of air at atmospheric pressure is done to avoid vacuum conditions (as for example, during the draining of the pipeline), or to impose a fixed pressure condition in a certain section of the line (as for instance, in a transition of pressure flow to free surface flow). Vacuum impose a significant underpressure (given by the difference between atmospheric and vapor pressure) which may lead to the pipe rupture, loss of ability due to excessive strain and sucking of joints, deterioration of interior lining and contamination by impurities or contaminated groundwater. Exhaustion of large amounts air at atmospheric pressure occurs during the pressurization of a line in the sequence of a previous depressurization. The most typical example is the filling of a line. The main difference between Functions I and III, concerns the pressure at which air is exhausted and not the absolute magnitude of air flow-rate; in fact as it will be seen below, air valves intended for Function III are not able to deaerate flow under pressure. FUNCTIONING PRINCIPLES The basic functioning principle of a classic air release valve is buoyancy. In the figure below are represented the forces that act over the float of a simple non-guided air release valve; for simplicity they are neglected interaction between air ant the float and inertia forces (relevant in unsteady flows). Fig. 1- Simple air release valve For the air valve to function it is necessary that the apparent weight (total weight minus buoyancy) overcomes the resultant of pressure forces caused by the difference between interior pressure and outside atmospheric pressure; i.e.: V (gf - gw m) > (p - patm) Ao (1) in which m is the immerse fraction of the float (immerse volume divided by total volume, 0 m 1) and Ao the area of orifice Dividing by gw and rearranging (1), one obtains: m < df - hw Ao/ V (2) in which hw= (p - patm) /gw, is the piezometric height (pressure head in mwc) and df= gf /gw, é a the relative float density. For a given air valve, df, Ao e V are fixed data. The right member of (2) depends only of hw as indicated in Fig. 2. Fig. 2- Zone of operation of a Function I air valve The completely emerged condition of the float (m=0) is obtained for: hcol = V df /Ao (3) This pressure head is designated by gluing pressure and it represents the maximum possible operating pressure for a given air valve; for operating pressures bigger than that value, the float is unable to descend, being compressed (glued) against the orifice. The Figure illustrates the classical solutions to extend the operating region: − augmenting df - limited improvements, since its is convenient to have d f < 1; − augmenting V - used by some manufacturers (e.g. GEC (1978)) but not by the majority since it leads to an increase of the overall dimensions of the valve; − reducing Ao - the most common solution, which however implies a decrease in the venting capacity Supposing for example a spherical float 100 mm diameter and df= 0.9; for a maximum pressure head of 100 m (10 bar), the orifice diameter must be smaller than 4 mm. It is not therefore difficult to conclude that the evacuation of large amount of air as in Function III, requiring large venting areas, is not compatible with the purging under pressure which imposes relatively small venting areas. For these reasons there are normally two basic types of air valves: − small orifice ones, intended for Function I, with areas calibrated for the water line pressure, governed by buoyancy. − large orifice ones, intended for Functions II and/or III, functioning with pressures near the atmospheric pressure, governed by the laws of flow of air trough orifices For the large orifice valves buoyancy is used, but only to close the valve after the complete exhaustion of air. In fact, in order to prevent valve to blow shut, the valve is designed so that the float is kept outside of air draft, or that, the resultant of aerodynamic forces of escaping air maintain the valve open (aero-kinetic principle, Lescovitch, 1972). Air-valve opening is achieved by pressure difference the very same way as a classic check valve. AIR FLOW TROUGH ORIFICES The isentropic flow of air trough orifices is governed by the following equations (Wylie & Streeter, 1978): − Air entry. Subsonic regime: p ' m = CdiAi 7p00 p0 with 1.4286 p0 > p > 0.53 p0 p po − 1.714 (4) − Air entry. Sonic or critical regime : − ' m =C 0.686 with p < 0.53 p0 diAi RT0 p0 (5) − Air outlet. Subsonic regime: p 1.4286 p 1.714 m' = Cdo Ao 7p 0 − 0 p p with p0 /0.53 > p > p0 (6) − Air outlet. Sonic or critical regime: − 0.686 m' = CdoAo p RT0 with p > p0 / 0.53 (7) in which m’ is the mass flow-rate of air. Considering m’= Qar and the gas state equation p/ = RT, the above equations can be transformed and expressed only in terms of the volumetric flow-rate of air referred to the interior pipe conditions, Qar. Introducing p’= p/p0 , and assuming p0 1 bar = 105 Pa, T 10 ºC= 283 K; T0 20 ºC= 293 K, the following equations are obtained: − Air entry. Sonic or critical regime : Qar = 754CdiA i with p'1.4286 − p'1.714 p' 1 > p’ > 0.53 − Air entry. Sonic or critical regime : (8) Qar = with 195CdiAi p' p’ < 0.53 (9) − Air outlet. Subsonic regime: Qar = 754CdoAo (1/p' ) 1.4286 with − (1/p') 1.714 1 / 0.53 > p’ > 1 (10) − Air outlet. Sonic or critical regime: Qar = 195 Cdo Ao with p’ > 1 / 0.53 (11) Fig. 3 presents the graphical plot Qar / Cdi Ai or Qar / Cdo Ao versus p’ correspondent to the above equations. The plot is completely general and may be used to pre-dimension any air valve. Fig. 3- Air flow trough orifices Example 1: Pre-dimension an air valve to admit 1.5 m3/s of air (air flow referred to pipe interior conditions) with a maximum vacuum head of 3 mwc. Supposing p0= 10 mwc, one has p= 7 mwc and p’= 0.7. From Fig. 3 (or equation 4.5, valid for subsonic air inlet), Qar / Cdi Ai, = 260 m/s. Assuming Cdi = 0.6 one calculates equivalent to an orifice 111 mm Ai = 1.5/ 260/ 0.6 = 0.0096 m2, which is diameter. As a rule, air valves manufacturers present in their catalogues dimensioning graphs or formulas relating air flows with pressure (gauge or absolute). These abacus or formulas take into account the particular characteristics of each valve and should always be preferred for the final dimensioning. It is however important to note that volumetric flow-rates presented in the catalogues are normally referred to standard atmospheric conditions and for this reason they cannot used straightforward in the dimensioning. Designating Qar atm the volumetric flow-rate at standard atmospheric conditions, and Qar air flow-rate at pipe conditions (Note: Qar= Qwater), the continuity gives: Qar= Qar atm p0/p T0/T (12) I.e., standard atmospheric air flow-rates have to be multiplied by: p0/p T0/T p0/p= 1/p’ to get air flow-rates referred to interior pipe conditions. CLASSIFICATION AND USUAL TYPES In the technical literature multiple classifications and designations of air valves can be found. Very frequently they are hybrid designations which mix construction characteristics (point of view of the manufacturer) with function (point of view of the user). This non-uniformity is closely associated technological progress, which has produced in the last years many different designs, combining the same valve, functions and operating principles very different. It is therefore very difficult, and most probably useless, to conceive an unique classification. Nevertheless, for the sake of clarity, it is recommended that function (or functions) of the apparatus should be always indicated. Some examples of currently used designations are given below: − Small orifice air valve, basic type defined above, primarily intended for Function I − Small orifice air valve. basic type defined above, intended for Functions II and/or III − Simple effect air valve, normally, Function I − Double effect air valve, hybrid designation to be avoided. Normally it refers to large orifice air valves previewed Functions II and/or III; some other times it designates double air valves, for triple function − Triple function air valve, valve performing functions I, II and III. − Double air valve, apparatus composed by two air valves, a small orifice one, and a large orifice one, in a single body. It is the most popular type of triple function air valve. − Combined air valve, usually it is a double air valve. There are however some manufacturers that use this name to designate valves with a single float which drives a nozzle, or as in some other designs, a membrane, which in its ascending movement, shut different venting areas. As a rule they are triple function air valve − Piloted air valves. Usually globe or angle regular valves, piloted by a small orifice air-valve. They are normally used as triple function valves in special conditions such as high air flows and/or very high pressures. − Air inlet valves, ordinary or specially profiled check valve which only let air in (Function II air valves). AIR VALVE LOCATION Most of the authors agree that air valves should be located in the following points along the pipeline profile (cf. Fig. 3): a) peaks b) upstream of isolating valves in ascending stretches c) downstream of isolating valves in descending stretches d) points of sharp decrease in slope in ascending stretches e) points of sharp increase in slope in descending stretches Fig. 4-Air valves location along pipe profile In addition, some authors, recommend to place double air valves (i.e., triple function) every 500 m to 1000 m (Lescovitch, 1972). Stephenson (1981) does this very same recommendation but without specifying the type of valve. Triple function air valves are normally recommended at peaks. Lescovitch (1972), indicates that peak should be referred to the hydraulic grade line rather than horizontal; Stephenson (1981), goes further and defines peaks relative to both lines- horizontal and hydraulic grade. Points b) and c) are particular cases of peaks; they are so when the isolating valve is closed. In these points recommendations are - triple function air valves (Stephenson, 1981), or, more simply - air valves for Functions II and III (Cary, 1992). For points d) and e) recommendations vary between small orifice air valves for Functions I (Lescovitch 1972, Stephenson 1981), to large orifice air valve Functions II and III (Cary, 1992). Some manufacturers (e.g. A.R.I., 1990), recommend to install air valves at all changes in slope, including low points. Bedsides aforementioned points, concerning the pipeline profile, air valves are usually recommended in the following points: − downstream of pumps − downstream of regulating valves and controlling diaphragms − upstream of convergents or diaphragms − upstream of meters Obviously placement and types of air valves depend of assumed criteria. For example, if one admits that vacuum is not a problem, it is possible to dispense Function II air valves at points d) and e); further, if it is considered that there will not be any release or significant accumulation of air at those points, one may avoid to install any air valve there. On the other hand, in a very long stretch with a slope near the hydraulic gradient, it may be necessary to place air valves at regular intervals. In the next section, there shall be refined criteria concerning the Function I air valves. DIMENSIONING FUNCTIONS I AIR VALVES Usual Criteria The most common criterion for sizing air release valves is due to Lescovitch (1972), which considers an air flow-rate of 2 % of water flow rate at atmospheric pressure. The 2 % value is proposed by this author as the normal solubility coefficient of air on water, which ranges between 1.5 % at 30 ºC to 2.9 % at 0 ºC. One immediate criticism of this criterion is that it does not take into account the number of air valves. For example, systems on Fig. 5 would have similar air flows per valve. Fig. 5. Identical systems with different number of air valves Pont à Mousson (1990), presents an example of calculation of an air release valve, where it is introduced the concept of pressure reduction along the path. The example considers a pumping main, 2036 m3/h water flow, 11 bar absolute pressure at an initial section (where it is implicitly assumed water is air saturated) and a 1.75 bar pressure decrease between the said initial point and the point where the air valve is placed. Admitting a solubility coefficient C= 0.0252, released gas flow-rate is given by: − 0.0252 x 1.75 / (11-1.75) x 2036 = 9.7 m3/h. It is noticeable that only 19 % of all potentially soluble air is released in the aforementioned air valve (potentially soluble air is 2.52 % x 2036 m3/h= 51 m3/h). Denoting with subscript 1 the initial section and the air valve section with subscript 2, the generalization of the reasoning gives the following equation (Note: valid for constant temperature): Qar released = C (p1 -p2) / p2 Qw (13) On the cited reference it is not given any indication concerning the way to implement the methodology in a real system (either a pumping system or gravity) with several air valves. Cary (1992) proposes for pumping mains an equation similar to (13), but divided by a reduction coefficient which can assume values 1, 2 or 3, depending on the number of neighboring air valves near the point under consideration. For this author p1 represents the pressure at the first section of the line (discharge flange of the pump). To compare above criteria, one must convert first air flow from Lescovitch criterion which refers to standard atmospheric conditions to interior pipe conditions; denoting p0 the atmospheric pressure and p2 the pressure at the section containing the air valve, the Lescovitch criterion is given by: Qar released = 0.02 p 0 / p2 Qw (14) Assuming a solubility coefficient C= 0.02, one can see that (14) coincides with (13) for p1 - p2 = p0 . Air Release Equation (13) may be easily demonstrated applying Henry’s law and the continuity principle to the air mass between two arbitrary sections 1 and 2, as follows: − Assumed existing air mass at section 1= C Qw p1 / (RT1) (Air dissolved assuming saturation) − Existing air mass at section 2 = Existing air mass at section 1 (steady flow) − Dissolved air mass at section 2 = C Qw p2 / (RT2) (Air dissolved assuming saturation) Released air at section 2 is given by the difference between total air mass constant) and dissolved air mass, i.e.: Qar released 2 = C Qw (p1 T2/T1 - p2) /p2 (15) Note that (15) transforms itself in (13) for constant temperature. Coherence with the continuity principle requires that equation (15 or 16) is recurrent; i.e., the amount of air available to be discharged on the further downstream air valves is the one that is maintained dissolved at pressure p2. On the other hand, if pressure increases (p2 > p1 ) one would have from (15) (Qar < 0); i.e., air will not release. More precisely, for air to release in a given vent it is necessary that the elevation at that vent is higher than the highest elevation of all upstream air valves, as illustrated on Fig. 6. Fig. 6. Differentiated air release along pipe profile Generalization of equation (15), assuming constant temperature, gives: Qar j= Qw C (pm -pj) / pj with pm >pj ; pm= min{p1, p2 ... pj-1} (16) where j denotes the section with the air valve under analyis and m the section uspstream with the smallest absolute pressure. Note: It is assumed in the present derivation that the only existing air is dissolved and that each air valve is adequately sized to exhaust all incoming free and/or released air; if that does not happen and flow-rate is able to hydraulically drag air downstream and/or reabsorb it, this same air, or part of it, will be available to be released in the next air valves, which, incidentally, may be situated at lower elevations. Criticism of Usual Criteria. Sources of Air Referred criteria assume that air to be exhausted is air that saturates water at a given pressure, forgetting the obvious fact that air valves can only vent air previously existent an that there is not air creation by the simple fact of raising the pressure. Usual sources of air within water supply systems are: i) vortices at reservoirs and intakes ii)deficient sealing in pump glands or pipe joints in systems with negative gauge pressures (e.g. suction pipes) iii)localized depressions originating sub-atmospheric pressures, as for instance, downstream of near closed constrained regulating valves iv)low pressures arising from bad layout design, or too low operating flows compared with the design capacity of the pipeline. This last situation is very typical of gravity systems underfed from upstream v) remaining air not totally removed during a previous filling operation vi)negative gauge pressure transients due to waterhammer phenomena (pump stoppage, rapid valve closure, etc.) vii)temperature raise along the line viii)free fall and/or hydraulic jump, in dissipating energy devices, breaking tanks, reservoir arrivals, etc. ix)deliberated air injection for anti-cavitation protection or as a mean of alleviating waterhammer overpressures. Besides air from source v) and, sometimes vi) and vii), which will always be present in a pipeline (however not for long), it can be stated that in most cases, a pipeline correctly designed, built and operated, will not release air along its extent. The amount of air a pipeline carries coincides with the mass amount of air contained at the departure reservoir; i.e., approx. 2 % at atmospheric pressure, and this will not be released unless pipe is subject to vacuum or temperature raises. On the other hand, other sources such as i) and ii), point to situations where large amounts of air can be entrained, eventually overcoming the solubility capacity and originating an over-saturated flow. In the case of vortex at intakes, Lescovitch (1972) and Pont à Mousson (1990) refer air flow-rates from 5 to 10 %, in volume, of water flow-rate. For hydraulic jumps, the U.S. Army Corps of Engineers (1966) presents the following envelope formula: max = 0.03 (Fr -1) 1.06 (17) in which Fr, is the Froude number upstream of upstream supercritical flow (Fr > 1) and the gas fraction given by Qar/Qw. Example: Let there be a pipeline D= 1 m, Qw= 1m3/s, i= 5 %, rug= 0.3 mm. For uniform supercritical flow: y= 0.28 m, V= 5.6 m/s, Fr= 4, from where one obtains max 0.1; meaning that the jump may entrain an airflow of about 10 % of liquid flow. Depending on particular conditions air-flows up to 40 % of liquid flow are possible. In short it is necessary to analyze each case with the necessary precautions in order to identify and quantify possible air sources. Hydraulic Removal of Air Another important aspect to be taken into consideration, is the capacity of the flow to remove (clear) by itself bubbles or air pockets that they may raise or accumulate in certain sections of the pipeline, provided velocity is high enough. A comprehensive analysis of this problem is presented by Wisner et al., (1975), who present the following envelope for the minimum clearing velocity, Vc , of air pockets: Vc/ (g D)1/2 = 0.25 sin1/2 + 0.825 in which (18) is the pipe angle with the horizontal in a descendent reach. Table 1 shows the resolution of such an expression for some typical values. TABLE 1: Air Clearing Velocity, Vc (m/s) Data from some other authors suggest that the influence of slope on the clearing velocity is stronger. However it is noted that the above expression is an envelope formula and not a functional relationship. Summary. Proposed Criteria Air valves for Functions I must be installed: − in special systems (e.g. pipelines with alternating stretches free flow/ pressure flow; pipelines with flow or pressure regulating valves and energy dissipators; pipelines with air injecting devices or Function II air valves, for cavitation control; pipelines subject to temperature gradients or local variations) − in badly conceived or operated systems subject to transient or permanent depressurizations, vortexes and insufficient submergence at sumps and intakes, unexpected temperature variations − to prevent situations arising from accidents and aging of the materials that may ultimately lead to air ingestion and subsequent release (e.g., ruptures, corrosion holes, loss of sealing ability in pumps and suction pipes) − as a means to control airflow and ensure complete air exhaustion in the case of usage of Function II air valves for waterhammer protection However in the majority of the cases, there will not be big needs for Functions I air valves. The feeling that these devices do not work properly, may well result from the very simple fact that, usually, there is not air to exhaust. One of the exceptions to this rule is the remaining air not totally removed by Function III air valves during a previous filling operation. This situation justifies per si the need of air valves at all peaks. An aspect which has deserved little attention in the technical literature so far, is the mechanism of air release. Air release is due to the diminishing of the solubility capacity of the water caused by a reduction of pressure or a raise in the temperature. The analysis of the mechanism of air liberation, together with the continuity equation, shows that, theoretically, the only effective air valves are the ones placed in peaks which are higher than the preceding highest peak, counting from the point of air inception; air valves in intermediate peaks or downstream of the highest peak will not release air. Still, one should bear in mind that not all air that may be present is dissolved an that there is a strong (and complex) interaction between air and water flows. It is therefore possible that air may be dragged by flow and accumulate at an intermediate peak, or some other, quite far from the point of inception. In short, it is recommended to install function air valves in all peaks relative to hydraulic grade line and horizontal line. Except for special cases it is not necessary to install air valves in the middle of ascending stretches. To determine air release flows it is proposed to adopt the Lescovitch (1972) criterion, which gives sensible results, in spite its physical background is doubtful. Air sizing flows must be raised in cases where there is evidence of significant air production/ inception, specially for the dimensioning of the air valves nearer the air source. In these cases equations (15) or (16) or a more comprehensive model considering both advection and air absorption, could be used for a more precise evaluation. Selection of air release valves shall be done taking into account air flows and pressure. In systems where static pressure is very different from service(s) pressure(s) there may be a need of installing two sets of air release valves in the same profile, with different operating pressures. CONCLUSIONS Basic air valves types have been presented and the principles of operation discussed. It is proposed to class air valves according to its function on a water supply system, viz. I)- small volume air release, II) large volume air inlet, and III) large volume air outlet valves. Functions I air valves are usually small orifice valves and they function according to the buoyancy principle. The analysis of the factors governing the equilibrium of the buoyant body explained why the size of orifices decrease with the pressure and the existence of a limiting pressure beyond which the air release valve is unable to function. Function II and III air valves are large orifice ones and its functioning is governed by air flow laws trough orifices. In the paper they are presented the isentropic flow laws concerning air mass and they are deduced general expressions relating volumetric air flow-rate referred to inside pipe conditions with pressure and orifice area; these expressions can be used to pre-dimension any air valve. Principal rules for placement of air valves in a water supply systems were reviewed; these cover function I, II and III air valves. In the last section of the paper it is presented a detailed discussion concerning criteria for sizing Functions I air valves. Focus has been directed to the concepts of “generation” and “conservation” to conclude that in most of the cases there will not be significant air flows to purge; still some situations have been identified that may lead to air release flows bigger than those usually assumed in practice. The other factors involved in the Functions I air valves problematic are the air-release mechanism, which indicates that only valves higher than previous are able to purge dissolved air, and the too much complex air water-flow interaction which may entrain non-released free air to points where it would not normally expected. The only general conclusion is that each case should be analyzed per si; the equations presented could be helpful in such an analysis. As a safety measure it is recommended the installation of Functions I air valves at all peaks relating both the piezometric line and the horizontal static line, considering a minimum air release flow of 2 % of liquid flow at atmospheric conditions (Lescovitch criterion). ACKNOWLEDGMENTS The author acknowledges the facilities given by COBA, SA. Appendix I. References Ahmed A.A. et al. (1982) “The process of aeration in closed conduit hydraulic structures.” Proc. Symposium on Scale Effects in Modelling Hydraulic Structures. Technische Akademie Essligen, Germany. A.R.I. Kfar Charuv (1990?) Water supply accessories. A.R.I. Kfar Charuv, Israel. Glenfield -Kennedy , ex-Neptune-Glenfield. (1978). Apex. Air relief valves for water systems. Biwater, UK. Cary, E. (1992). “Definition and sizing of air valves.” Revista Industria da Agua, December 1992, EPAL,Lisboa (in Portuguese). Dupont, A. (1974). Hydraulique Urbaine. Tome II. Eyrolles, Paris (in French). Ervine, D.A. & Himmo, S.K. (1982) “Modeling the behaviour of air pockets in closed conduit hydraulic systems.” Proc. Symposium on Scale Effects in Modelling Hydraulic Structures. Technische Akademie Essligen, Germany. Edmunds, R.C. (1979). “Air binding in pipes.” Journal AWWA, May 1979. GEC Alsthom, ex-Neyertec (1976). Purgeur Sonique, Duosonic, Clapet à rentrée d’air. GEC Alsthom, France. Lescovich, J.E. (1972). “Locating and sizing air-release valves.” Journal AWWA, July 1972. Martin, C.S. (1981). “Air entrainment.” Closed Conduit Flow, H.Chaudry &V.Yevjevich (eds.), W.R.P., Colorado. Meunier M. (1981). Les coups de bélier et la protection des réseaux d’eau sous pression. ENGREF, Paris (in French). Pont à Mousson (1990). Protection des réseaux. Purgex, Ventex. Pont a Mousson SA, France (in French). Stephenson D. (1981). Pipeline Design for Water Engineers (2ª ed.). Elsevier, Amsterdam. U.S.Army Corps of Engineers (1966). Hydraulic Design Criteria. Waterways Experiment Station, Vicksburg, Mississpi. Wisner, P.E. et al. (1975). “Removal of air from water lines by hydraulic means.” J.Hydr. Division, ASCE, Vol. 101, February, 1975. Wylie, E.B. & Streeter, V.L. (1978). Fluid Transients. Mc Graw Hill International, New York. Appendix II. Notation Ai = orifice area (air inlet) Ao = orifice area (air outlet) C = solubility coefficient of air in water Cd = discharge coefficient (of air valve or valve) Cdi = discharge coefficient(air inlet) Cdo = discharge coefficient(air outlet) d = air valve orifice diameter df = float density D = pipe diameter Fr = Froude number g = gravitational acceleration hcol = gluing pressure head hw = piezometric head i = pipe slope (sinus of pipe angle with horizontal) m = degree of immersion (air valve float) m’ = mass flow-rate of air p = absolute pressure p’ = pressure ratio (p’= p/p0 ) p0 = atmospheric pressure pi = absolute pressure at section i Qar = air flow-rate (inside pipe conditions) Qar atm = air flow-rate (atmospheric conditions) Qar j = released air flow at section i Qw = water flow R = gas constant, 287 Nm/ kg S = pipe section T = absolute temperature T0 = absolute temperature of atmospheric air V = float volume. Velocity Vc = air clearing velocity = gas fraction (= Qar / Qw) f = specific weight of air valve float w = specific weight of air valve float = air mass density 0 = air mass density at atmospheric conditions = pipe angle with horizontal TABLE 1: Air Clearing Velocity, Vc (m/s) D Slope (%) (m) 0.5 1 5 20 100 (1) (2) (3) (4) (5) (6) 0.25 1.3 1.3 1.4 1.5 1.6 0.5 1.9 1.9 1.9 2.1 2.3 1 2.6 2.7 2.8 2.9 3.2 1.5 3.2 3.3 3.4 3.6 4.0 FIGURE CAPTIONS Fig. 1- Simple air release valve Fig. 2- Zone of operation of a Function I air valve Fig. 3- Air flow trough orifices Fig. 4-Air valves location along pipe profile Fig. 5. Identical systems with different number of air valves Fig. 6. Differentiated air release along pipe profile