All manuals and user guides at all-guides.com Liebert® PDX 80-165 kW Indoor Room Cooling Units with Modulating Capacity Econophase Version - 50 Hz User Manual English, Cod. 265133, rev. 29.08.2019 Use only with: ● Liebert® MC, EconoPhase Version ● Liebert® EconoPhase, Pumped Refrigerant Module All manuals and user guides at all-guides.com Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This document, written in English, is the original version. Conventions DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation that, if not avoided, could result in death or serious injury. CAUTION indicates a hazardous situation that, if not avoided, may result in minor or moderate injury. NOTICE indicates a property damage message. NOTICE The manual is retained for the entire service life of the machine; The user reads the manual carefully before carrying out any operations on the machine; The unit control must be used exclusively for the purpose which it is intended for; the manufacturer takes no liabil­ity in case of an incorrect use or a modification of the unit control WARNING This manual was prepared to enable the end user to carry out only the operation that can be done with the panels closed. Only qualified personnel are allowed to carry out operations that require opening of the door or the equipment panels. The panel key supplied with the unit must be kept by a person responsible for the maintenance. CAUTION Before proceeding with installation, read all instructions, verify that all parts are included and check the nameplate to make sure the voltage matches available utility power. For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts, locate the identification label on the outside of the unit. WARNING This unit operates and restarts automatically. If the electrical connection is live, there are residual risks: electric shock, burns, moving parts, automatic restarting from the remote control. • Before any operation that requires opening of the door or the equipment panels (maintenance, cleaning, etc.), disconnect the unit from the power supply. The ON/OFF switch on the control panel does not isolate the power from the unit, even in the “unit off” mode. To cut off the power supply, open the insulation device (main switch) which is positioned on the electrical panel cover, behind the door on the left: MAIN SWITCH Unscrew the door and open it to access the main switch. • After opening the door pay attention to the cable and components still energized. • Open the main switch to cut off the power before removing any protective cover. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com WARNING The supply cable of the main switch contains live high-voltage. • The manufacturer highly recommends that the final customer installs on site an external main switch, easy to reach and to facilitate a quick and easy shutdown enabling the power of the unit to be cut off. Refer to the unit electrical schematics for the installation. Follow all local codes. CAUTION If the unit door is open while the fans are operating, the airflow may suddenly slam the door closed. There is a risk of being hit by the door and hands being crushed. • Before opening the door, switch off the unit using the local or remote control panel or the external main switch (if installed). If small objects are left loose in the fans bay after any maintenance operation, it may result in the object ejection at the fans start-up. There is a risk of being hit by small objects. • Install all protection panels or a grid before starting up the fans after any maintenance operation. Position the floor panels also below the unit with the fans below the floor. WARNING If the internal compartments are open immediately after the machine has been switched off, there might be some hazards related to: • Components still at high temperature: electrical heaters, humidifier and steam distributor, hot water piping. • Rotating elements (fan impellers, they might continue to rotate for a while by inertia) • Sharp edges, splinters and exposed fasteners Pay attention to the warning labels on the unit. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Attention: data relevant to the unit supplied is indicated on the inboard label (see the blank facsimile below). Data in the manual is referred to standard conditions and can be modified without any advance notice. 28 POS. 31 30 32 1 4 7 10 Evaporator fan Locked Rotor Ampere [A] 6 Evaporator fan quantity 55 66 9 Condenser fan quantity 10 Electrical heating Ampere 8 99 11 Electrical heating steps 12 Humidifier Ampere 13 Steam production capacity 14 Max. unit AC Ampere 15 Max. unit DC Ampere 16 Rated peak withstand current 17 Rated short-time current 18 Refrigerant type 19 High pressure switch Stop 20 High pressure switch Restart 21 Low pressure switch Stop 22 Low pressure switch Restart 23 Min. room operation temperature 24 Max. room operation temperature 25 Min. room operation humidity 26 Max. room operation humidity 27 Max. refrigeration circuit pressure 28 Manufacturing plant 29 Manufacturing date 30 Model 31 Serial number 32 Power input 17 17 24 24 25 Evaporator fan Full Load Ampere [A] 5 Condenser fan Locked Rotor Ampere [A] 22 22 23 4 Condenser fan Full Load Ampere [A] 20 20 21 Compressor quantity 8 18 19 Compressor Locked Rotor Ampere [A] 3 7 16 16 15 15 2 33 13 13 14 Compressor Full Load Ampere [A] 22 11 12 DESCRIPTION 1 26 26 27 29 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Model Nomenclature / Digit Numbers 1 2 3 4 5 6 7 8 9 10 11 12 13 P X Digit 1 and 2 PX Liebert® PDX Digit 6 Air Discharge D Downflow Up E Downflow Down 14 15 16 17 18 19 20 21 22 Digit 7 System Type P Air Cooled + predisposition for pumped refrigerant economizer Digit 3, 4 and 5 Unit Model Digit 8 - Airflow Digit 16 - Colour L = Premium Fan Module 1 = Black Vertiv RAL 7021 Digit 9 - Main Power Supply Digit 17 - High Voltage Option 3 = Single 400V / 3ph / 50 Hz + N X = Dual Circuit Digital Scroll R410A with EEV T = Dual Power Supply parallel + Magnetic circuit breaker for 10A three phases U = Dual Power Supply Alternate with ATS + Magnetic circuit breaker for 10A three phases Digit 11 - Humidification Digit 18 - Package Option 0 = None H = Infrared Humidifier U = Ultra Sonic Humidifier S = Electrode Humidifier Digit 19 - Monitoring Digit 10 - Cooling System Digit 12 - Microprocessor Control 2 = Inner Display only T sensor 3 = Inner Display TH sensor U = Small Cold fire display T sensor B = Small Cold fire display TH sensor C = Large Cold fire display T sensor D = Large Cold fire display TH sensor Digit 13 - Heating & Re- Heating 0 = None 1 = Electric heating Std Capacity 2 = Electric heating High Capacity Digit 14 - Air Filter Efficiency 1 = F5 (EU5) dust spot 3 = F5 (EU5) dust spot + Clogged Filter H = Predisposition for damper L = Predisposition for plenum installation N = No IS Housing 0 = No Card C = Sitescan Monitoring through INTELLISLOT IS-485EXI P = MODBUS, BACnet, SNMP, Web through IS-UNITY card Digit 20 - Sensors 0 = None Digit 21 - Packaging P = PLP And Pallet C = PLP and Wooden Crate S = Seaworthy Digit 22 - Special Requirements A = Standard Vertiv X = Special Vertiv Digit 15 - Condensing Control 1 = Air Cooled or Water cooled with Standard Pressure, 2 way MBV Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com 1 - Liebert® PDX EconoPhase System description 1.1 - Liebert® PDX EconoPhase System Liebert® PDX EconoPhase System is designed to provide precision air conditioning to computer racks in a data center or computer room as efficiently and effectively as possible. A Liebert® PDX EconoPhase System is composed of: • Liebert® PDX EconoPhase version - High Efficiency, Digital Scroll, floor-mounted indoor unit • Liebert® MC™ Condenser EconoPhase version - Air-cooled microchannel condenser, premium version • Liebert® PDX EconoPhase - Liebert® PDX EconoPhase pump refrigerant module The Liebert® PDX EconoPhase is an add-on module for use with an air-cooled Liebert® PDX system. The Liebert® PDX EconoPhase will allow the system to switch to Liebert® PDX EconoPhase operation when the outdoor temperature is low enough to provide the required temperature difference between the inside air and the outside air, providing significant energy savings because there is no need to operate the compressor. At lower temperatures, the system switches one or both circuits from Compressor Mode to Pump Mode. The pump consumes roughly 1/10th of the power consumed by the compressor. The Liebert® PDX EconoPhase system maintains this energy efficiency by employing the heat absorption properties of a liquid (pumped refrigerant) through a phase change. Refrigerant is pumped as a liquid, becomes a gas within the Liebert® PDX evaporator and then is returned to the Liebert® MC where it condenses to a liquid. The subcooled liquid refrigerant from the condenser is then run directly into the Liebert® PDX EconoPhase pumps and is circulated back to the Liebert® PDX unit (see Figure 1). The system will operate as a typical air-cooled direct expansion system when outdoor ambient conditions are unfavorable to EconoPhase operation. The pumps in the Liebert® PDX EconoPhase pump module are turned off and bypassed during compressor operation. Fig.1 - Pressure enthalpy diagram, pumped refrigerant Liebert® EconoPhase Liquid L iquid/V a por Mix V a por Condenser (DX Mode) Pressure Indoor Unit Condenser (Pump Mode) Tradtional Vapor Compression Cycle EconoPhase Cycle Enthalpy Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 1 All manuals and user guides at all-guides.com 1.2 - Liebert® PDX EconoPhase version The Liebert® PDX is a full- featured precision air conditioner intended for data centers, network closets, technological rooms (laboratories, metrological rooms, museums), new and existing constructions, raised and non- raised floors, moderate to high density heat loads, also in combination with cold aisle containments (up to 10 kW/Rack). It provides all the necessary functions of a standard precision air conditioner, including cooling, heating, humidification, dehumidification, air filtration, condensate management, temperature control, alarm functions and data communications. Thanks to Copeland’s Digital Scroll and electronic expansion valve availability, Liebert® PDX can achieve a continuous spectrum of capacity output, ensuring a very tight and precise control on room temperature. Liebert® PDX can rapidly change from one capacity duty to another. Therefore it controls environmental parameters even working with swiftly changing heat loads. In Digital Scroll Cooling system depending on the unit size the modulating capacity range is between 15% and 100% of the nominal capacity. The compressor can drop down to 10%, but the system will decrease in efficiency. Thanks to the capacity modulation we can reduce the starting and stopping of the compressor which uses a lot of power and puts a great amount of stress on the components; therefore we Downflow Up 2 can enhance efficiency and life of the system. With the Liebert® PDX range we are able to manage unexpected very high ambient temperatures, maintaining the system active, reducing HP alarm and troublesome stops of the unit. In fact, when the discharge pressure reaches the limit value, the compressor capacity is limited to a fraction of the actual request, in this way restricting the heat rejection and allowing the system running without interruptions. If, after a defined time, the condensing pressure comes back within the limit, the capacity will be modulated in the usual way. Reliability of the Liebert® PDX is also maximized, thanks to the fewer system parts and simple electronic controls which reduces the unit maintenance. Digital Scroll motor runs at a constant speed throughout the operating range. This unique feature increases the applicability of the Liebert® PDX units into technological rooms, as it eliminates the need for expensive electromagnetic suppression electronics require to ensure electromagnetic compatibility. The Digital function maintains the maximum refrigerant velocity through the pipes. As a result of these reasons, Liebert® PDX units do not need oil return components. Liebert® PDX is designed on modular concept. The Liebert® PDX is supplied as a single unit (height 1970 mm), where coil and fan sections are connected. The units are available Downflow Down Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com 1.3 - Liebert MC™ EconoPhase Version The Liebert® MC air-cooled microchannel condenser is a lowprofile, direct-drive propeller fan-type air-cooled unit suitable for mounting outdoors. It provides heat rejection for either one or two separate refrigeration circuits, matches the heat rejection capacity corresponding with the outdoor ambient temperature and with each corresponding compressor heat rejection requirements. Constructed with an aluminum cabinet, galvanized steel frame and microchannel coil, the unit is quiet and corrosion resistant. The condenser is quickly and easily installed because all internal wiring is completed at the factory with only electrical connections and communications connections to be made at the job site. All electrical connections and controls are enclosed in an integral weatherproof section of the condenser. The Liebert® EconoPhase pumped refrigerant system will always use the premium version condenser. In EconoPhase operation, the premium control board uses inputs from the indoor unit, condenser refrigerant temperatures and ambient temperatures to modulate the EC fan motor speed from 0 to 100% RPM, maintaining the refrigerant temperature setpoint. The control system provides temperature control for outdoor ambient as low as -35°C in pumped refrigerant Liebert® EconoPhase operation. 1.4 - Liebert® EconoPhase Pump Refrigerant Module The Liebert® EconoPhase is an option for a Liebert® PDX EconoPhase Version air-cooled system. The Liebert® EconoPhase allows an air-cooled direct expansion system to switch from vapor compression operation to pumped refrigerant operation when the outdoor temperature is low enough to provide the required temperature difference between the inside air and the outside air. are found throughout this manual and the manual of Liebert® EconoPhase Pump Refrigerant Module. • Liebert EconoPhase Operation - Liebert® EconoPhase operation is possible when the outdoor temperature is low enough to provide the required temperature difference between the indoor air and the outside air. This mode turns the compressors Off and turns the Liebert® EconoPhase pumps On. • Refrigerant Pumping - During Liebert® EconoPhase operation, the refrigerant is pumped around the air-cooled loop instead of going through the vapor compression cycle. System pressures will vary significantly depending on whether the system is operating in standard aircooled mode or in Liebert® EconoPhase operation. • Energy Savings - The coefficient of performance of the system increases significantly during the EconoPhase operation which results in significant energy savings for the user. • EEV - The system uses an electronic expansion valve during both direct expansion and EconoPhase operation. The EEV results in energy savings and helps the pump maintain proper differential during EconoPhase operation. • Piping - The condenser piping is larger than what is typically specified for Liebert® air-cooled Precision Cooling systems. The pipe sizing still allows oil return to the compressor and also allows for efficient operation in both modes of operation. All field piped lines must be insulated because the fluid temperatures can be well below the dew point during EconoPhase operation. All outdoor insulation must be UV rated and rated for outdoor use. • Unit/Module Communications - A CANbus connection links the Liebert PDX and the air-cooled condenser to achieve the most efficient operation as well as the condenser and the Liebert® EconoPhase module. Fig. 2 - Liebert EconoPhase module 1.6 - Operating Modes Each circuit on a system combining a Liebert® EconoPhase, Liebert DSE and Liebert MC has six distinct operating modes: • • • • • • 1.5 Standard Air-Cooled System vs. Liebert® PDX EconoPhase System Idling with compressor and pumps Off Startup Compressor operation Compressor-to-pump changeover Pump operation Pump-to-compressor changeover A circuit will run most of the time in either compressor or pump operation mode. These modes both efficiently remove heat from the conditioned space and reject it via the air-cooled condenser. The flow paths during each mode of operation are detailed in Figures 3 and 4. A couple of differences to note between Compressor Mode and Liebert® EconoPhase operation: • The unit does not dehumidify in Liebert® EconoPhase operation. If dehumidification is desired, Liebert® EconoPhase operation must be disabled. • Bubbles may be seen in the site glass in the indoor unit when the system is in Liebert® EconoPhase operation. This does not necessarily mean the system is low on charge. There are differences between the standard air-cooled system and a system designed with the Liebert® EconoPhase. The user must be aware of these differences to achieve the best operation. This section summarizes the differences; more detailed explanations Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 3 All manuals and user guides at all-guides.com Fig.3 - Compressorized operation flow path Check Valve Condenser Solenoid Valve Pump Check Valve Electronic Expansion Valve Check Valve Compressor Evaporator Fig.4 - Pump operation flow path Check Valve Condenser Solenoid Valve Pump Check Valve Electronic Expansion Valve Check Valve Evaporator 4 Compressor Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com 1.7 - Module Communications The Liebert® PDX (room unit), Liebert MC™ (microchannel condenser) and Liebert® EconoPhase (Pumped Refrigerant Economizer) require communication when combined into a system. This is done through a CANbus communication interface. A CANbus cable must be connected from the Liebert® PDX at the designated terminal(s) to TB49 on the Liebert® MC condenser board. If there is an additional condenser, TB50 of the first condenser will continue out to TB49 on the second condenser. In a system equipped with a Liebert® EconoPhase, the CANbus cable must be connected from TB50 on the last condenser to TB49 on the Liebert® EconoPhase CANbus terminal block. The two devices that are connected at the ends of the CANbus will require termination to be set by jumper or plug. One end will be at the last outdoor device in the connection chain; the other end of the CANbus is either in the indoor unit or at a remote sensor. To terminate, place a jumper on J6 Pins 1 and 2 on the Liebert® MC condenser or Liebert® EconoPhase board. For other Liebert® iCOM boards directly associated with the indoor unit, terminate by placing a jumper on P78 Pins 2 and 3. See Fig. 5 for CANbus connections, jumper and DIP switch settings. • Length Restrictions • The indoor Liebert® PDX can be no more than 100m from the condenser. The CAN communication cable can be longer, but the total length should not exceed 150m between the indoor Liebert® PDX unit and all outdoor equipment. • • • Cable Type • Conductors-22-18AWG stranded, tinned copper • Twisted pair (one pair is required for connection) • Braided shield or foil shield with drain wire • Low capacitance (<=15pF/ft) • Cat5e or similar • UL approved temperature rated to 75°C (167°F) • UL approved voltage rated to 300V • UV - and moisture - resistant if not run in conduit • Plenum rated-NEC type CMP, if required by national or local codes High Voltage Restrictions • Do not run communications cable with high voltage cable. • When routing cable, avoid laying, fastening or coiling near or on high voltage wiring, conduit, or light ballasts. Communication signals in equipment may be disturbed. • Keep communications cable away from other electrical noise sources. Environmental and Safety • Vertiv® recommends routing cable inside conduit where the cable exits the building to outdoor units, between outdoor units and any other location where environmental conditions could degrade the cable’s integrity. • Follow all national and local codes regarding cable routing, ratings, etc. Fig.5 - CANbus connections TB50 TB49 TB50 TB50 Liebert EconoPhase Circuit 1 On 1 J6 1 2 3 4 5 6 7 8 3 Liebert EconoPhase Circuit 2 CAN On 1 J6 3 1 2 3 4 5 6 7 8 CAN TB49 TB49 Factory-Installed CANbus Cable Field-Installed CANbus Cable TB50 TB49 Liebert EconoPhase CANbus Terminal Block Liebert MC Unit Circuit 2 On 1 J6 3 1 2 3 4 5 6 7 8 CAN On P67 TB50 Indoor Unit With Liebert iCOM TB49 Liebert MC Unit Circuit 1 Connect wire 3 to PIN1and wire 4 to PIN3 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 1 J6 3 1 2 3 4 5 6 7 8 CAN 5 All manuals and user guides at all-guides.com 1.8 - Description of Liebert® EconoPhase Operation • The Liebert® EconoPhase unit enables the Liebert® PDX system to operate in any of three modes to control temperature, depending on the outdoor temperature and the load. • Compressor Mode • Pump Mode • Mixed Mode When the outdoor temperature becomes low enough to provide the required temperature difference between the inside air and the outside air, there is no need to compress the refrigerant to a higher pressure/temperature. When the outdoor temperature is low enough, the system switches from Compressor Mode to Pump Mode or to Mixed Mode. • Compressor Mode: All available compressors may be used to maintain the control temperature. All the available Liebert® EconoPhase pumps are Off. The control will typically run in this mode when the load and temperatures are such that full or partial Liebert® EconoPhase operation is not possible, or because certain pumps have experienced alarms. • Pump Mode: All of the available pumps may be used to maintain the Control Temperature. All the compressors in the system are Off. The control will typically run in this mode when load and temperatures permit. Mixed Mode: The pump in Circuit 1 is On and the compressor(s) in Circuit 2 is On. Some systems may not have Mixed Mode capability, depending on the manufacture date. Contact the factory to inquire about a software upgrade. 1.8.1 EconoPhase Control EconoPhase operation has three main controlled parameters: • return or supply air temperature control • refrigerant temperature • pump pressure differential (outlet pressure - inlet pressure) Room Temperature When the system is in Pump Mode, the room temperature is controlled by modulating the pump speed with a variable frequency drive. The load requirement will determine if one pump or two are needed. Figure 8 shows the sequence of operation in terms of pump speed. Minimum speed is 45% and maximum speed is 100%. See Table 2 for more detail on the events shown in Figure 8 and the conditions that trigger action. The pump startup routine calls for a start speed of 80%. The pump will run for up to 60 seconds at 80% with the EEV at 60% while waiting on the pump pressure differential to reach at least 0.83 bar to indicate that flow has been established. If the pump establishes flow, the speed will change from 80% to the required control speed as shown on the curves in Figure 6. Fig.6 - Two-circuit pump control Pump y Speed E C Maximum Pump Speed I Pump 1 L D Minimum Pump Speed B 0 G J A 20% Pump 2 H K 40% F 55% 75% 100% x Capacity Pump 1 under manual control Pump 1 under PID control Pump 2 under manual control Pump 2 under PID control 6 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Tab. 1 - Description of events and actions in Figure 6 Event Condition to Trigger Action B to A Pump 2 Off; and (Pump 1 at minimum speed for 60 sec.; and Delta T [indoor air temperature - setpoint] < -1.7°C Pump 1 turns Off; Pump 2 remains Off A to B Both Pump 1 and Pump 2 Off; and Delta T > 0°C Pump 1 turns On and runs on PID; Pump 2 remains Off F to G Pump 2 Off; and Pump 1 at maximum speed for 60 seconds; and Delta T > -0.6°C Pump 2 turns On at starting speed, then goes to minimum speed immediately. Pump 1 continues to run on PID At E and H upward Pump 1 at maximum speed; and Pump 2 at minimum speed; and Delta T > -0.6°C Pump 1 runs at maximum speed, while Pump 2 runs on PID At E and H downward Pump 1 at maximum speed; and Pump 2 at minimum speed; and Delta T < -0.6°C Pump 1 runs on PID, while Pump 2 runs at minimum speed J to K Pump 2 Early Startup Action Both Pump 1 and Pump 2 at minimum speed for 60 sec.; and Pump 2 turns Off, while Pump 1 runs at minimum Delta T < -0.6°C speed Pump 2 Off; and Delta T > 1.1°C As seen in the last row of Table 1, an exception to the “F to G” event, in which Pump 2 starts if Pump 1 is at its maximum speed for 60 seconds and Delta T (Room Air Temperature - Setpoint) is > 0.6°C, is that Pump 2 will start when Delta T > 1.1°C even if Pump 1 is not at its maximum speed. In that event, Pump 2 starts via the startup routine and then goes immediately to its minimum position. In the case of a transition from Compressor Mode to Pump Mode, the pumps will be given initial speeds based on the call for cooling at the time of transition. The pumps will go to this initial speed after the startup routine is completed. This will mean that, depending on the load, both pumps will start immediately at the transition to Pump Mode from Compressor Mode. When the system is in Mixed Mode, the room temperature is controlled either by modulating the digital compressor(s) on Circuit 2 with the pump on Circuit 1 at 100%, or by modulating the pump speed on Circuit 1 with the compressor(s) operating at the minimum digital percent. Refrigerant Temperature When a circuit is running in Pump Mode, the refrigerant temperature is controlled by the condenser fan speed. When a circuit switches from Compressor Mode to Pump Mode, the condenser fan speed control changes from pressure control to temperature control, with the controlled parameter being condenser outlet refrigerant temperature. The default setpoint on Circuit 1 is 7.2°C, while on Circuit 2 it is 2.8°C. The condenser fan speed will modulate to provide the respective temperature. But if the outdoor temperature is warm enough, or if the load is high enough, the fans might be at 100% and the actual refrigerant temperature might be above the setpoint. In that case, the temperature will depend on the heat rejection capability of the condenser at the given conditions. Actual fan speed will depend on the load and the outdoor temperature. The fan speed will be lower for a given heat load with lower outdoor temperature in order to maintain the setpoint. Because the refrigerant temperature could be below the dew point inside, the indoor piping must be insulated to prevent condensation. In addition, the outdoor piping must be insulated so that heat is not lost to the outdoor air at very low ambient temperatures, causing the refrigerant temperature to fall and increasing the possibility of frost at the evaporator. Pump Pressure Differential The pump pressure differential must to be maintained above a minimum for cooling and lubricating flow to be provided to the pump motor and bearings. The differential is controlled by EEV position. When the system switches to EconoPhase operation, the EEV Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 No action to Pump 1; turn On Pump 2 at 80% speed, once the startup procedure is finished, step change to minimum speed immediately control changes from superheat control to manual control. The Liebert® iCOM then signals the EEV to control its position based on pump differential. The default minimum EEV position is 50% and the maximum is 80%. The pump differential setpoint is 20 psid. If the pump is running at a high speed at steady state, the EEV may be at 80% and the actual pump differential may be above 25 psid. In that case, the EEV will stay at 80% and the differential will just be a function of pump speed and system pressure drop. If the pump differential drops below 5 psid continuously for 30 minutes, the system will switch to direct expansion mode for 30 minutes. The system will switch back to EconoPhase operation if the conditions are still compatible. 1.8.2 Pump Startup Routine When either pump attempts to start, the first attempt will be at 80% speed. If flow is not established (as detected by pump differential being at least 12 psi within 60 seconds), the pump will turn Off for 10 seconds before trying again at 90% speed. If flow is still not established, the pump will turn Off for 10 seconds before trying again at 100% speed. If flow is not established after the 100% speed attempt, the system will switch to DX mode for 10 minutes before attempting to start the pumps again if the conditions are still compatible. The second startup routine is the same as above. If the second startup attempt is unsuccessful, the system will switch to DX mode for 60 minutes before trying again. The third startup routine will be the same as above. If the third startup attempt is unsuccessful, a “Pump Startup Fail” alarm will be displayed and EconoPhase operation will be locked out until the user manually resets the event at the Liebert® iCOM. 1.8.3 Switch from Compressor Operation to Pump Operation The Liebert® iCOM will run the system in the most efficient operating mode, given the load and temperature conditions. If Mixed Mode is available, the system will change from Compressor Mode to Mixed Mode when partial Liebert® EconoPhase operation is possible and from Compressor or Mixed Mode to Pump Mode when full Liebert® EconoPhase operation is possible. 1.8.4 Switch from Pump Operation to Compressor Operation The unit will switch from Pump Mode to Mixed Mode or Compressor Mode when at least one of the following is true: • The difference between the actual controlled air temperature and the setpoint is 75% into the Cooling Proportional Band for 5 minutes. The default is 75%, but the percentage can be changed at the Liebert® iCOM. 7 All manuals and user guides at all-guides.com NOTE At startup and at switchover from compressor operation to pump operation, more time is allowed to bring the temperature under control, but the temperature will never be allowed to go outside the cooling proportional band. 1.8.5 Loop Temperatures While the outdoor loop temperature could be close to the same on both circuits, the indoor loop temperatures (in most cases) and pressures in Circuit 1 will be higher than in Circuit 2 because of the staged cooling evaporator design in the Liebert® DA125. The Suct Ref Temp will be a function of load, return air temperature and pump speed. Table 2 shows some representative loop temperatures for EconoPhase at the outdoor rating condition, 1.6°C, for several heat load conditions and two return air conditions. System pressure drop for a given application will affect these temperatures because of its impact on flow rates for a given pump speed. The Liebert® EconoPhase page on the Liebert® iCOM® display shows Dis Ref Temp (pump outlet temperature) and Suct Ref Temp (evaporator outlet temperature). NOTE The data in Table 2 is from a system tested in controlled conditions and is for reference only. • • • • The pump differential pressure is below 34 kPa for 30 minutes. The refrigerant temperature leaving the pump is below -1.1°C for 60 minutes. The pump does not establish flow at a pump startup attempt. Power is lost at the Liebert® EconoPhase unit. Tab. 2 - Representative Liebert® EconoPhase loop temperatures at 1.6°C outdoor temperature Load, % 100 75 50 25 100 75 50 25 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Outdoor RA Temp. Temp. Dis Ref Suct Ref Suction SH Evap Saturation Pump Speed, % °C °C Temp. °C Temp °C °C Temp °C 1.6 29.4 100 60 1.11 4.4 27.7 20 -5.6 -5.2 15.5 7.4 1.6 29.4 100 46 1.11 2.7 25.5 20.5 -7.6 -2.2 15.5 4.7 1.6 29.4 64 45 7.7 2.7 28.8 23.8 0.4 2 10.7 4.2 1.6 29.4 54 Off 5 NA 28.8 NA 3.7 NA 7.5 NA 1.6 23.8 100 55 10 2.7 14.4 16.1 -16.4 -7.2 13 5.4 1.6 23.8 100 45 10.5 3.3 13.8 17.7 -16.9 -5 13.3 4.7 1.6 23.8 69 Off 7.7 NA 22.7 NA -6 NA 11.2 NA 1.6 23.8 54 Off 5 NA 23.3 NA -1.5 NA 7.3 NA 1.8.6 Mechanical Considerations The Liebert® EconoPhase pump is located at the condenser (receiver) outlet and always needs liquid at its inlet for proper function. The lines between the receiver and the Liebert® EconoPhase unit must be sloped down toward the Liebert® EconoPhase unit without any traps and with minimal bends. Traps in those lines will prevent the pump from establishing and from maintaining flow. 8 It is equally important to pump operation that the receiver be sufficiently above the Liebert® EconoPhase unit; refer to Figure 13 for the proper height difference. It is also important that the circuits do not get crossed between the indoor unit, the condenser and the Liebert® EconoPhase unit. If they get crossed, the system will not operate correctly, either in DX mode or in Liebert® EconoPhase operation. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Fig.7 - Piping schematic EconoPhase Unit Differential Check Valve Factory installed Relief Valve Liebert MC Condenser Check Valve Receiver Solenoid Ball Valve Valve Ball Valve Hot Gas Discharge Includes Factory Traps No External Trap Required PX****P room unit Tandem Compressor Differential Check Valve Liquid Evaporator Coil Service Valve Oil trap every 6 m of vertical piping Suction Check Valve Oil trap on the horizontal discharge line before each lift Service Valve Check Valve Electronic Expansion Valve Refrigerant Piping Field Piping Shut-off Valve Liquid Return Check Valve 10 bar (145 psi) 1. Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. 2. Schematic representation shown. Do not use for specific connection locations. 3. Vertical height of condenser above indoor unit shall be no greater than 18.0m. 4. All indoor and outdoor field refrigerant piping must be insulated, 12mm minimum thickness. All outdoor insulation must be UV- and ozone-resistant Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 9 All manuals and user guides at all-guides.com 1.9 - Operating limits The units are designed to operate within working ranges (see Tab. 3). These limits are referred to new machines or to those that have been correctly installed and serviced. The warranty clauses are no longer valid for any possible damage or malfunction that may occur during or due to operation outside the application values. Tab. 3 - Operating limits Room air conditions Temperature: From 20°C to 35° C Humidity ratio From 5.5 g/kg to 12 g/kg Relative humidity From 20% to 60% Temperature: From 26°C to 40° C Room air conditions Humidity ratio PX150 - PX165 From 5.5 g/kg to 12 g/kg Relative humidity From 20% to 60% Temperature: Storage conditions From -20°C to 50° C Max. 90% RH, Relative humidity preventing surface condensation. Power supply tolerances V ± 10% Hz ± 2 Note: The allowed thermal load shall not be lower than 20% of nominal air conditioner cooling capacity. Lower thermal load will drive to imprecise temperature and humidity control and frequent compressor(s) switch on/off. Note: The minimum condensing temperature for PX150-165 is 40 °C. Outdoor temperature: lower limit Exceeding the winter low temperature limits could drive to issues at the microprocessor control, at the electric devices and at the fan operation. Normally with these low temperatures the compressor is stopped and the EconoPhase is active. In case of compressor running, exceeding these temperatures could stop the compressor(s) by Low Pressure transducer. Reset to normal operation can only be carried out manually through the unit control. Remote condenser Vertiv fan speed control (VARIEX) required. It is standard available on the MC Condenser EconoPhase version Outdoor temperature: higher limit This limit is determined by coupled condenser model. Exceeding this limit (or a lack of maintenance), the compressor(s) could stop by High Pressure switch. Reset to normal operation can only be carried out manually. Approved Remote Air Condenser To ensure safe and correct operation, best performance, and longest life the units must be connected only to remote condensers approved by Vertiv. The warranty clauses are no longer valid if the unit is connected to an unapproved remote condenser. Relative position room unit vs. remote condenser From unit to condenser, max distance up to 60 m equivalent length up to 100 m equivalent length Max geodetic height between condenser and room unit. The condenser located below the room unit is not allowed. from 0 m to 18 m from 0 m to 18 m Requirements Pipe diameter see Tab. 6 see Tab. 6 Oil traps on vertical line of gas refrigerant every 6 m, max every 6 m, max Extra oil charge see Tab. 7(Enc. B) see Tab. 7(Enc. B) Remote condenser fan speed control (VARIEX) installation mandatory mandatory design oversized +20% Hot Gas Reheat not allowed not allowed Insulation external liquid pipe line mandatory mandatory Condenser down to - 35° C 10 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com 2 - Preliminary operations 2.1 - Safety Information WARNING! Risk of top-heavy unit falling over! Improper handling can cause equipment damage, injury, or death! Read all of the following instructions before attempting to move, lift, remove packaging, or preparing unit for installation. 2.5 - Handling the Unit While Packaged • • • CAUTION! Risk of sharp edges, splinters and exposed fasteners! Can cause personal injury! Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from the unit or prepare the unit for installation. CAUTION! • Risk of overhead interference! Can cause unit and/or structure damage! The unit may be too tall to fit through a doorway while on the skid. Measure the unit and doorway heights and refer to the installation plans prior to moving the unit to verify clearances. • • • NOTICE! Risk of unit damage if improperly stored! Keep the unit vertically upright, indoors, and protected from dampness, freezing temperatures, and contact damage. • Transport unit using a fork lift or pallet jack; otherwise use a crane with slings, in this case use spreader bars to avoid risk of crushing. If using a fork lift or pallet jack, make sure the fork (if adjustable) are spread to the widest allowable distance to still fit under the skid. Also, ensure the fork length and distance is suitable for the unit length and to ensure the unit stability. When moving the packaged unit with a fork lift, lift the unit from the WARNING designated side of the unit not higher than 152 mm off the ground. If circumstances require the unit to be lifted higher than 152mm great Unit weight is unbalanced. Improper lifting can cause personal injury, death, or care shall be exercised and all CENTER OF damage to unit. Lift unit from this side only. GRAVITY by-standing personnel are to be no HEAVY SIDE! closer than 5 m to the lift point of the unit. Always refer to the location of the Center of Gravity indicators when lifting the unit from any other side. Use the center of gravity indicators on the unit panels to determine the position of the slings. Center of gravity varies per unit size and selected options. Slings shall be equally spaced on either side of the center of gravity indicator, and with the widest allowable distance. Be sure that the distance between slings guaranties the unit stability. Place the slings between the unit bottom rails and the skid. NOTICE! The conditioner must never be installed outdoor. See drawings in Enclosure C. 2.2 - Equipment Inspection Upon arrival of the unit, and before unpacking, verify that the labeled equipment matches the Bill of Lading. Carefully inspect all items for either visible or concealed damage. Damage should be immediately reported to the carrier and a damage claim filled in with a copy sent to your sales representative. Equal Distance 2.3 - Packing material All material used to package this unit is recyclable. Please save for future use, or dispose of the material appropriately. 2.4 - Recommended Unit Handling Equipment 2.6 - Unpacking the Unit 1. Remove the exterior stretch wrap packaging material from around the unit, exposing the protective corner and side packaging planks. 2. Remove the top cover, corner and side packaging planks from the unit Pallet Jack Fork Lift Piano Jacks Spreader Bars and Slings Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 Equal Distance 11 All manuals and user guides at all-guides.com 2.7 - Moving to the Installation Location with Piano Jacks Make sure the floor can support the unit when being moved with piano jacks. Adequate support (e.g. metal plates) should be used to cover the floor to distribute the weight on the floor. 1. 2.8 - Unit Weight Tab. 4 - Unit Weight Models A [kg] Packaging [kg] Standard Weight Unit Acquire piano jacks and place them into a position so one is at each end of the unit. PX082 931 42 PX094 929 42 PX104 931 42 PX120 954 42 PX150 1080 58 PX165 1080 58 3 - Positioning 2. Remove 4 bolts from the pallet, two on each side. Bolts can be removed by using a socket wrench, openend wrench or pliers. Depending on the unit air discharge configuration there are different kinds of positioning. • Before proceeding with the installation of all units see overall dimensions and service area drawings in Enclosure C Installation Drawings • Make sure the floor can support the unit weight (see point 2.8 Unit weights) • If required, accessories are available to support the unit in the final position, to help with water connection and the maintenance operation. See Enclosures E - Accessories 3. 4. 5. • • • • Place a protective material between the unit and the piano jacks and straps. Using the piano jacks, the unit can be moved to the site for installation (min. two technicians are required). Piano Jacks Removal Place the unit as low as the piano jacks will allow Undo all the strapping holding the piano jacks to the unit Use a pry bar or a similar device to lift the unit high enough allowing the removal of the piano jacks on each side Remove all material used to protect the unit from the piano jacks and strapping To move the Fan and the Coil Module of the Extended Height unit use the above instructions (point 1 to 5). 12 NOTICE: Ensure isolation between the air conditioner and the floor to avoid vibration transmission. 3.1 - Positioning: Downflow Up. • • The units have to be installed on the floor Downflow Up version - a raised floor with an opening below the unit is required to ensure the correct airflow under the floor. See Enclosure C. 1. To move the unit use the piano jacks. Make sure the floor can support the unit when being moved with piano jacks. Place protective material between the unit and the piano jacks and straps. 2. 3. With the unit secured to the piano jacks it can be moved to the site for installation (min. two technicians are required). 3.2 - Positioning: Downflow Down. A raised floor is required for this installation. The fan section is installed completely under the floor allowing the correct airflow below the floor. See Enclosure C 1. Attach 4 shackles M12 to the coil module (not supplied). Use appropriate shackles to lift the total assembled unit load. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com 2. Use sling and a 4 point lifting bar (not supplied) to lift the unit and place it on the floor in the right position. 4 - Refrigeration connections 4.1 - Refrigeration pipeline connections The air condensing units are delivered helium- pressurized at 2 bar. CAUTION: The discharge operation of the room unit pressurized with helium (at 2 bar) and the unbrazing of the bottoms from the connections must be carried out as last operations, immediately followed by the connection and emptying of the whole system. Downflow Down position Right position of the Downflow Down unit respect the floor level. All dimensions in mm It is the responsibility of the customer to ensure the right support below the unit; if necessary accessories are available. See enclosure E. 4.1.1 - General layout 1. In soft or hard copper. The diameter required is stated in Tab. 6. If the installer intends to use pipes of a larger diameter (e.g. for long winding runs) then consult HPAC Technical Sales Support. Use as short refrigeration pipelines as possible to minimize the total charge of refrigerant and the pressure drops. Lay the horizontal gas pipes with 1% downward gradient towards the refrigerant flow. 2. Reduce the number of bends, which must be of large radius, to a minimum. 3. Insulate the piping as specified in Tab. 5. If the pipes are put next to electrical cables it is advised to insulate them to avoid damage to cable insulation. 4. There must be a minimum separation of 20mm between the gas and liquid pipelines. If this is not possible insulate both lines. 5. Support both horizontal and vertical pipes with vibrationdamping clamps (which include rubber gaskets). Place these every 1.5 - 2 m. Note: In PX082, PX094, PX104, PX120, both circuits have tandem compressors: each tandem compressor is composed of one scroll compressor and one digital scroll compressor. Note: Seal any gap between the unit and the floor edge with a gasket. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 13 All manuals and user guides at all-guides.com Fig. 8 - Recommended condenser and Liebert® EconoPhase™ unit locations, typical unit arrangement diagram layout Top View Circuit 1 Circuit 2 Air-Cooled Condenser Air-Cooled Condenser Entering Hot Gas Line CIRCUIT 1 *Liquid line from Condenser 28mm. Do Not Trap Line Slope toward Liebert EconoPhase unit 50.8mm per 3m. Top View 1067mm Minimum Clearance Liebert EconoPhase Unit Liquid Line to Liebert EconoPhase from Bottom of Receiver Entering Hot Gas Line CIRCUIT 2 Minimum Clearance: see relevant User Manual * Liquid from Condenser 28mm Do Not Trap Line Slope toward Liebert EconoPhase unit 50.8mm per 3m. * Liquid from Condenser 28mm" Do Not Trap Line Slope toward Liebert EconoPhase unit 50.8mm per 3m. CIRCUIT 1 CIRCUIT 2 1524mm 1524mm leg height Typical; see Note 1. Factory-Supplied, Field-Installed Field Piping 1. For proper pump function, a minimum elevation difference of 1524 mm must be maintained between the bottom of condenser box to the bottom of Liebert EconoPhase unit. 2. All indoor and outdoor field refrigerant piping must be insulated, 12.7mm minimum. All outdoor insulation must be UV- and ozone-resistant. 14 *Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance. **Components supplied by Liebert and must be field-installed. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Tab. 5 - Condenser positioning CONDENSER POSITION INSULATION 4.1.3 - Installing pipelines THE FOLLOWING OPERATIONS MUST BE CARRIED OUT BY AN EXPERIENCED REFRIGERATION TECHNICIAN. CONDENSER ABOVE CONDITIONER gas NOTICE: The discharge operation of the room unit pressurized with helium (at 2 bar) and the unbrazing of the bottoms from the connections must be carried out as last operations, immediately followed by the connection and emptying of the whole system. required liq. required 1. PRE (see **) gas 1% room unit liquid 6m (see *) LAYOUT 1% (*) Oil traps every 6 m of vertical piping (*) Oil traps every 6 m of vertical pipping. Create an oil trap on the horizonthal discharge line before each lift. (**) See paragraph 1.9 - Operating limits 2. 4.1.2 - Pipe diameter The diameters of the connecting pipes between the conditioner and the condensing unit listed in Tab. d must be respected, otherwise the guarantee becomes invalid.. Tab. 6 - Pipe diameters (room unit - remote condenser - pump module) 3. STANDARD PIPE DIAMETERS (Valid for equivalent lengths up to 100 m) MOD. copper tube external diametre x thickness [mm] R410A Gas Liquid from condenser to PRE Liquid from PRE to room unit PX082 28 x 1.5 28 x 1.5 22 x 1.5 PX094 28 x 1.5 28 x 1.5 22 x 1.5 PX104 28 x 1.5 28 x 1.5 22 x 1.5 PX120 28 x 1.5 28 x 1.5 22 x 1.5 PX150 35 x 1.5 35 x 1.5 28 x 1.5 PX165 35 x 1.5 35 x 1.5 28 x 1.5 WARNING: Due to higher pressure with R410A, use copper pipes and copper fittings with thickness 1.5mm when external pipe diameters are higher than 18mm (22 and 28mm) Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 Lay the piping, taking note of the following: • Welding: • All joints must be braze-welded. • Avoid butt welds by using sleeves or enlarging one of the pipes using a pipe opener. • Use silver-based solders and the correct apparatus. • Guarantee a correct weld as a refrigerant leak, or a faulty weld which leads to a leak later on, can seriously damage the air conditioner. • Always use large-radius curves (bending radius at least equal to pipe diameter). Bend the pipes as follows: • soft copper: by hand or bending device. • hard copper: use preformed curves. Do not overheat the pipes when welding so as to minimize oxidation. Connect the pipes to the condenser: • Condensers with butt-welded pipe connections: cut the pipe, enlarge it and weld it to the pipeline. • Condensers with threaded tap connections: flange the pipes and connect. RESPECT THE DIRECTION OF REFRIGERANT FLOW (SEE LABELS ON REFRIGERANT CONNECTIONS). Wash out the pipelines as follows: a. Plug up the free ends of the pipes. b. Connect a helium or nitrogen cylinder, fitted with a reducer (max. pressure 10 bar), to the ¼” SAE Schrader valve of the condenser. c. Pressurize the pipes with helium or nitrogen. d. Unplug the pipes instantaneously. e. Repeat a) - d) several times. THIS OPERATION IS IMPORTANT TO AVOID REFRIGERANT FILTER CLOGGING, ESPECIALLY WHEN HARD COPPER PIPING IS USED. 4. 5. 6. 7. 8. Open all the room unit shut- off valve. Discharge the room unit pressurized with helium (at 2 bar) opening the charge valves so that all the branches of the circuit are discharged (e.g. on the receiver, on the low pressure side and on the compressor delivery). Unbraze the bottoms from the connections of the room unit. Fix (weld) the pipes to the connections on the air conditioner. Connect the refrigerant safety valve to the outdoor with a copper pipe sized in order to satisfy the requirements of EN13136 (i.e. till 10m length, i 26mm). 15 All manuals and user guides at all-guides.com Tab. 7 - Weight of refrigerant contained in piping during operation EXTERNAL PIPE DIAMETER gas(*) liquid (+), at different condensing temperatures R410A (kg/m) 35.0 0C 46.0 0C 57.0 0C 22 x 1.5 (mm) 0.027 0.286 0.265 0.240 28 x 1.5 0.047 0.496 0.459 0.416 35 x 1.5 0.076 0.812 0.751 0.681 (*) Due to the small weight influence (at 15.5 bar - discharge temp. 650C), only 46.36 kg/m3 for R410A is considered. (+) Liquid pressure and density varies according to condensing temperature (see refrigerant tables). Tab. 8 - Equivalent lengths (m) of: curves, shut-off and non-return valves Nominal diameter (mm) 16 90 45 180 90 12 0.50 0.25 0.75 2.10 1.90 14 0.53 0.26 0.80 2.20 2.00 16 0.55 0.27 0.85 2.40 2.10 18 0.60 0.30 0.95 2.70 2.40 22 0.70 0.35 1.10 3.20 2.80 28 0.80 0.45 1.30 4.00 3.30 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com 4.2 - Vacuum creation and refrigerant charge 5. NOTICE: Check the refrigerant type to be used on the data plate of the air conditioner and on the refrigerating compressor. Fig. 9 - Vacuum Pump and refrigerant charging cylinder connections for vacuum creation and refrigerant charge 11a 14 11 6. 7. 13 8. Break the vacuum as follows: a) Close the cock (10a) for the vacuum pump (10). b) Open the cock of the refrigerant cylinder (11a) until the system reaches a pressure value of about 1 bar. NOTICE: The refrigerant must be introduced and charged on evaporator inlet (5/16 Shrader valve) taking only liquid fluid from the cylinder. c) At this point both the vacuum pump and the refrigerant cylinder can be disconnected as follows: c1) close the cylinder cock (11a) c2) close the way 5/16” SAE of the connected Schrader valves. Inspect all connections/joints using a leak detector. If a nleak is found, empty the pipes and the condenser, seal the leak and repeat the instructions in 3) - 6). Now the machine is ready for completing the charge and the start-up. Charge the refrigerant (ONLY LIQUID) by means of the charge valve placed at the evaporator inlet. 4.2.2 - R410A refrigerant charge (*) 1. 2. 3. R.L. 4. 12 5. 10a 6. 7. 10b 10 Start the unit as described in para. 7.1. Manually start the compressor (when the unit is equipped with tandem compressors start both of them), ensure the unit is not in the dehumidification phase). Guarantee a constant condensing temperature (preferably 42-45°C); if necessary, partially obstruct the condenser coil surface or limit its ventilating power to obtain these conditions. Charge the unit until the working conditions of the entire refrigeration circuit have become normal. Using a manometer, check that the evaporating temperature is above 00C. Verify that the superheat is 6-8 K (to do this refer to para. 10.1). Follow the diagram below to define the charge. Measuring condensing temperature and evaporating temperature at the compressor, find in the diagram the target subcooling then adjust the charge to match the target subcooling found (subcooling should be measured at the expansion valve inlet). With scroll compressor cooling systems, during the charge adjustment, the compressors have to be at the full capacity. PDX 2÷5 ° C evap. temp. 5÷8 ° C evap. temp. 8÷12 ° C evap. temp. 14 12 1. Open all cocks of the system including those used for pressurizing (ambient unit and condensing unit). With this operation all the components of the refrigerating circuit must be subject to vacuum. 2. Connect a proper, high efficiency vacuum pump (10) suitable for polyester oils to the couplings: - Compressor intake and delivery using the 5/16 Schrader valves welded on the piping. - Schrader coupling (12) fit on the liquid receiver. - Schrader coupling (13) fit on the compressor or fan space, if the reheating coil option is available. 3. Provide for a connection with refrigerant cylinder before making vacuum. 4. Make the system vacuum up to 0.3 absolute mbar and after 3 hours check if 1.3 absolute mbar have not been exceeded. This condition ensures a humidity lower than 50 ppm inside the system. If the complete vacuum is not possible, this means that there are some leaks (to be removed according to the instructions in 6 below). NEVER USE THE COMPRESSOR TO CREATE A VACUUM (THIS INVALIDATES ITS GUARANTEE). Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 10 8 6 4 2 0 25 30 35 40 45 50 55 60 Condensing temperature [° C] PDX SMART AISLE APPLICATION 8÷12 ° C evap. temp. 12÷15 ° C evap. temp. 14 12 subcooling [K] 4.2.1 - R410A precharge subcooling [K] (*) only with reheating coil (optional) 15÷20 ° C evap. temp. 10 8 6 4 2 0 25 30 35 40 45 50 55 60 Condensing temperature [° C] 4.3 - Refrigeration circuits (see Enclosure D) See drawings in Enclosure D. 17 All manuals and user guides at all-guides.com 5 - Water connections Fig. 11 - Wye vs. Delta power supply connection diagram Wye Power Supply Connection 5.1 - General warnings Delta Power Supply Connection ENSURE THAT THE TUBING DOES NOT OBSTRUCT THE AIR FLOW (Downflow units only). IF THE TUBING IS TO RUN OUTDOORS, ADD ETHYLENE GLYCOL TO THE CIRCUIT. 5.2 - Water connections 5.2.1 - Condensate drain (for unit without condensate pump); (Fig. 10): • • • • Use galvanized steel, PVC or flexible polythene tubing. Allow a 1% gradient towards the drain. It is necessary to make a drain trap (1) placed at least 200mm below the drain tray (2). In the Upflow configuration units the drain trap must be placed under the unit, in the false floor. Caution: If the drain trap is done inside the fan module in the Downflow configurations attach the tube and the drain trap properly to the fan module frame using a cable tie, avoiding the risk of contact with fans. Fill the drain trap with water (3). Fig. 10 - Condensate drain 2 1 min. 200 mm Acceptable Power Supplies-380V to 460V Nominal Units (TT System, TNS System or TNC System) • 380V wye with solidly grounded neutral and 220V line-toground • 460V wye with solidly grounded neutral and 277V line-toground. Unacceptable Power Supplies - 380V to 460V Nominal Units (IT System) • Wye with high-resistance (or impedance) ground • Delta without ground or with floating ground • Delta with corner ground • Delta with grounded center tap. If the unit must be installed in the IT System, contact Vertiv Technical department prior to installation. 6.3 - Power supply cable connection. • 3 min. 100 mm • BRACKET to be connected by user 5.2.2 - Humidifier (optional): See Enclosure A. 6 - Electrical connections 6.1 - Electrical connections 1. • • • Before proceeding with the electrical connections, ensure that: all electrical components are undamaged; all terminal screws are tight; the supply voltage and frequency are as indicated on the unit. • • • Connect the cable to the Line inlet terminal board. See Fig.12 power supply cable path. For units with dual power supply option do not connect the power cable supply as illustrated in Fig. 12; two supply cables must be arranged and connected to the additional electrical panel placed near the main electrical panel. Use the cable size defined according to maximum current absorbed, the supply voltage, the installation type and the local specification. For unit with dual power supply both supply cables must be dimensioned as described above. The system/line cable protection is to be arranged by the customer. Use a protection with differential switch. If the system is equipped with EC fans, use a B type switch. Use multipolar cables with sheath (CEI2022, IEC 60332) only. Do not fit the supply cable in the raceways inside the machine electric board. See electrical data in Enclosure B: Technical data tables. WARNING: For the units (in particular if the external display isn’t installed) must be provided an external main switch, easy to access, to facilitate, when necessary the unit shutdown. Fig. 12 - Power supply cable connection. 6.2 - Wye vs. Delta Connection Power Supply for PDX The Liebert® PDX EC Fan Model is designed to operate with Wyeconnected power. It will not operate properly with Delta connected power. A field-supplied isolation transformer or other power solutions will be needed for proper function. The electronically commutated motors included in the Liebert® PDX are suitable for connection to power supplies with a solidly grounded neutral. 18 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Fig. 13 - Available terminals AUXILIARY TERMINAL BOX 4 compressors (Cooling + Electr. heating + Humidification) remote on- off (CLOSE = ON) 394 0394 clogged filter (CF) (CLOSE = OK) 362 361 (*) water leakage (LWD) 710 720 GENERAL ALARM (400, 401 NC = alarm or unit off) WARNING (300, 301 NC = warning or unit off) smokestat firestat (AAP) optional (CLOSE = ON) 400 (NC) 401 (C) 402 (NO) 300 (NC) 301 (C) 302 (NC) 86 83 operating fan (CLOSE = ON) 70 71 operating compressor 1 (CLOSE = ON) 72 73 operating compressor 2 (CLOSE = ON) operating compressor 3 (CLOSE = ON) 74 75 operating compressor 4 (CLOSE = ON) 78 79 user alarm 1 (CLOSE = OK) user alarm 2 (CLOSE = OK) 70C Liebert MC Condenser, common control signal 71C Liebert MC Condenser, circuit 1 control signal 230C Liebert MC Condenser, circuit 2 control signal 76 77 86 030 86 82 70C 71C 230C Note: Connect 70C terminal with Liebert MC Condenser terminal 700, connect 71C terminal with Liebert MC Condenser terminal 710, connect 230C terminal with Liebert MC Condenser terminal 230. • • • • Right side: internal low voltage field wiring pathways Left side: internal high voltage field wiring pathways Use the cable bushing on the back of the panel to get into the electrical panel. Use cable tie to fix the power and low voltage cable to the electrical panel. With any of these failures, the motor stops (electronically - no potential separation), the status relay is released. NO automatic restart. To reset the alarm, power supply has to be switched off for min. 20 s once motor is at standstill. • For cable entrance holes details see Enclosure D. Wiring connections (Fig. 13): • Connection for remote on-off must be done by the installer. • The General Alarm terminals allow remote alarm signaling. • In case of short circuit, check the sticking of the involved switch and replace it. 6.4 - Protection degree IP2x check After whole of the connections and installation works, comprising ceiling elements (plenum, ducting) and floor elements (base frame), check and verify the protection degree IP2x (protection against finger access, std. IEC 60364-1) at the boundary of the air conditioner. 6.5 - Protective features of EC fan The EC fan has been provided with the following protective features: • Electronics overheating protection • Motor overheating protection • Locked rotor protection • Short circuit at the motor output Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 • Mains under-voltage detection: if mains voltage falls below 3ph/290Vac (typical value) for 5s minimum, motor will be switched off (only by electronics, no potential separation), status relay is released. If mains voltage returns to correct values, the motor will restart automatically. Phase failure recognition: if one phase fails for 5s minimum, motor will be switched off (only by electronics, no potential separation), status relay is released. If all 3 phases return to correct values, the motor will restart automatically within 10-40s. The power supply for an external speed setting potentiometer is short-circuit protected. Motor is overload-protected via motor current limitation. Warning! Leakage current of the motor is approx. 7 mA. 19 All manuals and user guides at all-guides.com 7 - Start-up 7.1 - First start-up (or after long standstill) TO PREVENT COMPRESSOR DAMAGE THE CRANKCASE(S) MUST BE PREHEATED FOR AT LEAST 4 HOURS BEFORE CONDITIONER START-UP (FAILURE TO DO SO INVALIDATES THE GUARANTEE). Start the air conditioner as follows: 1. Open all valves in the refrigeration circuit according to the instruction label attached to the valve. 2. Ensure that the refrigerant charge is correct (see Chap. 4). 3. Using a leak detector, verify that there are no refrigerant leaks. If there are any, then repair the leak and recharge as described in Chap. 4. 4. At least 4 hours before start-up, close the main switch and miniature circuit breaker for transformers’ protection on the electrical panel. In the control system factory setting the stand alone mode is standard. The stand alone mode gives the possibility of turning on the unit simply rotating the main switch on the electric panel. The yellow LED on the Control case will light after turning the unit on, showing the presence of the electric power. If the LED does not light up: • check the electric panel power supply; • check the protection devices (e.g.: thermal switches); • check the fuses. 5. Verify the operation of the crankcase heater. 6. (With Electronic Expansion Valve option) The battery is normally charged enough by the supplier to pass properly the production test. In case the unit has been left for long period without power the level of charge could be reduced further. If after Power ON the iCOM control should generate the “EEV1/2 Battery failure” warning, please wait approx 24h before to decide to change the battery; this will give necessary time for recharge; if after this time the warning event is still present, then replace the battery with a new one. 7. Check that there are no water leakages. 8. If an external condenser is installed, start it by supplying power to it. 9. Close all MCBs on the electrical panel. 10. Check the supply voltage on all phases. 11. Check the supply voltage on all phases for the external condenser, if fitted. 12. ENSURE THAT THE COMPRESSOR HAS BEEN PREHEATED FOR AT LEAST 4 HOURS BEFORE STARTING THE UNIT. 13. Start the unit by pressing ON/OFF on the external display (on the internal display if the external display is not installed) 14. Check the electrical absorption of all components (see Chap. 6). 15. Check the electrical absorption of the external condenser/ Dry cooler, if fitted. 16. IMPORTANT - If the compressor makes a loud and unusual noise IT IS NECESSARY TO INVERT the electrical connections of the phases supplying the corresponding scroll compressor, which accepts only one direction of rotation. 17. Ensure that the fans rotate in the correct direction (see arrow on fan). CAUTION: risk of contact with rotating devices. 18. Ensure that all control system settings are correct and that there are no alarms (see Control manual). 19. Verify the Fresh Air Intake operation (if fitted). 20 20. Once the system is operating under load, check the various components, as follows: • Verify that the fans are operating properly. • Ensure that the temperature and relative humidity are being controlled, and that the humidifier (optional) and heating steps (optional) operate when required. • Ensure that the compressor operates when required. • Ensure that the fan operation controller on the external condenser is calibrated correctly, and that it controls the fan operation. • Check oil level inside compressors, where compressor’s oil level sight glass is available, after 30 min of compressors running at maximum capacity: oil level must be between ½ and ¾ of sight glass. In tandem compressors the oil level must be checked with both compressors running at maximum capacity (note: when only one compressor is running, the oil level inside the compressor that is not currently running could be at the minimum and the compressor, that is running, at the maximum level; when one compressor is running at maximum capacity and one compressor is running in modulating capacity, the oil level in the latter one could be between 1/2 and the minimum). 7.2 - Starting and stopping • ALWAYS ENSURE THAT EACH CRANKCASE HAS BEEN PREHEATED. FOR BRIEF STOPPAGES KEEP THE SUPPLY TO THE CRANKCASE HEATER. Turn on the unit operating on the ON/OFF switch placed on the display. If the ON/OFF remote device is not installed, the green LED on the Control case will light up together with the LED placed below the ON/OFF switch. The fan starts immediately (the fan always works when the unit is ON); after 2 minutes the regulation is activated, so the cooling (compressor), heating (electric heaters), humidifying and dehumidifying devices can start. Adjust the set-point as indicated in Control manual. Stop the unit putting the ON/OFF switch in OFF. • The main switch on the electrical panel inside the unit should be switched off if the unit is stopped for a long time. 7.3 - Automatic restart If desired, the unit will automatically restart on the return of power after a supply interruption (see Control manual). If the power interruption is expected to be of several hours, to avoid an automatic cold restart of the compressor stop the unit before the black-out and, on the return of power, allow the compressor to preheat before restarting the unit. 7.4 - Checking the refrigeration piping pressure drops Liebert® PDX is equipped with connections to check the refrigeration piping pressure drops: room unit → condenser →room unit To carry out this operation it is necessary to use 2 calibrated manometers and connect them as follows: M1, connected to the compressor delivery valve; M2, connected to the Schrader valve (1) of Fig. 14. When the compressor is running, check M1 and M2. N.B.: Repeat this test, inverting the manometers: to calculate the correct p consider the average value of the two readings. Refrigeration pipeline Pressure drops (Δ p bar), at 45°C • At the same geodetic level: Δ p (bar) = M1-M2 • When condenser is above the room unit: Δp (bar) = M1-M2+geodetic difference (m x 1,1:10,2) • When condenser is below the room unit: Δ p (bar) = M1-M2-geodetic difference (m x 1,1:10,2) Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Fig. 14 - Refrigerant line components different electrical sources. It is possible to chose between different solutions: • Dual Power Supply Parallel: 2 separate power supplies: during normal working mode both are present, during emergency situation only the main one is present. This means that during emergency mode full cooling redundancy is granted disabling heating and humidifying. This last option allows, during emergency mode, to reduce unit power absorption and therefore Genset or UPS sizes. • Dual Power Supply Alternate Basic Version: 2 separate power supplies: each power supply is able to completely feed the unit. In case of failure of the main supply the unit automatically switches to the second power supply. This allows having a complete power supply redundancy or in case needed to have during emergency mode full cooling redundancy disabling heating and humidifying. This last option allows during emergency mode to reduce unit power absorption and therefore Genset or UPS sizes. 2 4 1 3 from Liquid Receiver 11 Filter dryer inletinlet Schrader valve Filter dryer Schrader 22 Filter dryer Filter dryer 33 Sight glass Sight glass 44 Solenoid valve (only(only with thermostatic valve) expansion valve) Solenoid valve with thermostatic valve • DX mode Compressor(s) starts and the air flow is reduced, thereby causing dehumidification (refer also to Control manual). 8 - Operation Unit operation is completely automatic. The below sequence explains how the unit operates : • The air, sucked in by the fan, enters the unit. • The air is immediately filtered. • The TEMPERATURE sensor or HUMITEMP (temperature + rel. humidity) sensor (check type installed), verifies the state of the inlet air, and relays this information to the control system. • Filtered new air is injected into the air stream via the Fresh Air Intake (optional). • The treated air passes through the fans, which operate continuously, and is then dispersed out of the unit. • The air passes from the underfloor void into the room via air distribution outlets. For “DOWNFLOW” units installed on raised floor: switch off the machine before the floor panels removal within a distance of 850mm from the machine, to avoid risks of contact with rotating devices (fans) moving and with hot heating elements. (see Fig. 15). • The control system compares the relayed information to the set point and proportional band values programmed into its memory: it then commands the air conditioner to treat the air as follows (see also Control manual): • HEATING This can take one of three forms: • electrical heating (optional): the heating elements heat the air passing over them. There is 1 heating step. • Note: To protect the unit from superheating, one automatic reset sensor set at 40°C and one or more manual reset thermostats set at 120°C are installed. • Note: If, during dehumidification, the ambient temperature drops below a specified level, dehumidification will be stopped if necessary (see LOW LIMIT intervention in Control manual). • HUMIDIFICATION - optional The humidifier creates steam, which is distributed into the air stream via the steam distribution pipe (see also Enclosure A, F, G). Note: Manual control can be performed using the control system (see Control manual). Fig. 15 - Safe floor panels removal 850 mm COOLING The compressor (scroll compressor or digital scroll compressor, with modulating capacity) is started and the cold refrigerant flows through the evaporator, thus cooling the air passing over it. For compressor operation see Control manual. In dual circuit units, the evaporator is a dual stage coil, so the air is cooled first by one circuit (circuit n°1, compressor(s) on the left side) and then by the other one (circuit n°2, compressor(s) on the right side) . Temperature and pressure values related to the two refrigerant circuits can be different. • DEHUMIDIFICATION - optional DUAL POWER SUPPLY - optional This option allows a supply of electrical power from two Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 9 - Calibrations & Regulation (at start-up) The air conditioner has already been factory tested and calibrated, but it is very important to check, at start-up, the superheating. See Tab. 5 and Tab. 6 (Enclosure B) that show all valves. • The air conditioner has already been factory tested and calibrated. • For calibrations of instruments installed on the external condensers/Dry coolers refer to the relevant manual. • For control system calibrations refer to Control manual (to prevent erratic operations do not use temperature sand rel. humidity set points/proportional bands which differ excessively from the Standard Settings). 21 All manuals and user guides at all-guides.com WARNING: Before any calibration with the unit operating, remove the call for humidification and electrical heating at the control. 9.1 - Water leakage sensor (Liquistat) 9.2 - Environment protection A misuse or an incorrect calibration of the unit leads to an increased energy consumption, resulting in an economic and environmental damage. Use the freecooling function, if available. Due to high flooding alarm device sensitivity, to the end to avoid undesirable alarm signal because of few sporadic water drops, place the sensors at a minimum distance of 500 mm from the unit base perimeter. This solution assures alarm intervention for real flooding risk only. 22 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com 10 - Maintenance and Spare Parts 10.1 - Safety instructions All maintenance operations must be carried out strictly by observing the European and National accident prevention regulations. We refer especially to the accident prevention regulations concerning electrical systems, refrigerators, and manufacturing resources. Maintenance may be done to air conditioning equipment only by authorized and qualified technicians. In order to keep all warranties valid, the maintenance must adhere to the manufacturer’s regulations. DANGER: The work should be done in the system only when it is at standstill. Do this by switching off the air conditioner at the controller and the main switch. Post a warning sign saying: “DO NOT SWITCH ON.” Electrical components of device have to be switched off and be checked that they are not under voltage. Ignoring the safety instructions can be dangerous to persons as well as to the environment. Soiled parts always cause a loss of performance and for switch or control devices can lead to the break-down of a plant. 10.2 - Spare parts Only original spare parts made by Vertiv may be used. Using third party material can invalidate the warranty. When making inquiries always refer to the ”Component List” supplied with the equipment and specify the model number, serial number and, if available, also the part number. NOTES: 1) When a faulty component is replaced, follow the relevant manufacturer instructions. 2) When the spare parts must be welded, be careful not to damage the internal parts (gaskets, seals, o-rings, etc.). 10.3 - Maintenance schedule Monthly, quarterly, biannual and annual checks are to be conducted according to the following guidelines. All tasks and periods listed here are regulations from the manufacturer and need to be documented in an inspection report. CAUTION: All these tasks should be carried out only by an authorized and trained technician. We recommend the Vertiv Customer Service 10.4 - Air filter check and replacement It is important to check the state of the air filter every month to maintain a good efficiency of air distribution through the evaporator coil. CAUTION: Sharp edges, splinters and exposed fasteners can cause personal injury! Only properly trained personnel, electrically instructed, wearing appropriate safety headgear, gloves, shoes and glasses can carry out this operation! DOWNFLOW UNITS Filter Bracket 1) Switch off the unit and open the front panel with the key. Note : Some components inside the unit can be still at high temperature, wait a few minutes before starting the maintenance operation. 2) Unscrew and remove the filter brackets. 3) Remove air filters. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 23 All manuals and user guides at all-guides.com 10.5 - EC fan replacement WARNING! There is a risk of the fans and panel falling down and causing an injury during the replacement operation. Due to the weight of the fans (approx. 35 kg) and the panel (up to 25 kg), two technicians are required to carry out the fan replacement. BEFORE COMMENCING, ALWAYS CUT ALL THE ELECTRIC SUPPLY CIRCUITS ON THE MACHINE OFF. Only properly trained and qualified personnel should work on this equipment. How to remove the fans Remove the front panel (or a grid) to get access to the fan bays (see pictures below). Downflow Up Downflow Down Note: • Downflow Down - remove floor panels positioned in front of the unit to get access to the fan section frontal grid. Remove any obstacles in front of the fans to allow the fan extraction (e.g. the raised floor structure, piping) Downflow Up 1) Disconnect the fan electrical cable from the connector. 2) Remove the 2 front screws “a” from the fan support (one screw on each side of the sli ding bars) b 24 a 3) Loosen the 2 rear screws “b” of the fan support (one screw on each side of the sliding bars) 4) Slide down the fan by pulling the handle. 5) Remove completely the 2 screws “b” on the back of the fan. 6) Pull the handle to slide the fan out of the bay Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Maintenance schedule FANS WARNING: do not reach into the fan while the fan wheel is runnin g. AIR FILTERS NEW AIR FILTER (ifinstalled) CONTROL SYSTEM HUMIDIFIER (ifinstalled) SWITCH CABINET POWER CIRCUITS WARNING: electrical cables and electrical components of the air conditioner are under voltage. REFRIGERATION CIRCUIT CAUTION: Fluo ride refrigerants increase the greenhouse effect and are subject to restrictions and norms, according to the national and European regulations. ELECTRONIC EXPANSION VALVE and SUPERHEATING CONTROLLER Check for soiling, damage corrosion, and proper fixing. Check bearings noise. Measure the current and power consumption. Cleaning to preserve the function. Check for soiling, damage, corrosion. Check state offilter. Clean or replace if necessary. Carry out controls more frequently in dusty environments. X X see air filter. Clean or replace X Check for proper and functionally correct installation and surrounding conditions. Check the function of the LEDs of the display’s control system and the alarms. Check the connections for electrical and mechanical function. Check the functional elements (e.g. operational controls and display devices). Check the electrical/electronic and pneumatic input signals (e.g. sensors, remote controllers, command variable) for compliance with nominal values. Check control function, control signals and safety chains. Adjust control function and control signals. X X 1 Year 6 Months COMPONENT 3 Months MAINTENANCE PERIOD EVERY X X X X X X X X X X X See Enclosure A, F, G. Check the power supply on all phases. Check the connections for electrical and mechanical function. Check the power supply at all terminals. Measure power consumption at all connected consumers. Set, adjust and tighten the functional elements (e.g. operational controls and display devices). Check safety equipment, e.g. thermal switch. Replace fuses (every 2 - 3 years) Check protective covers for completeness. Measure the working pressures and temperatures (to be done by a refrigeration technician). Check the power consumption, measure head temperature and check for possible abnormal operating sounds. Make sure that there is no frost building up on the evaporator and compressor. Check function of all regulating devices (power regulators, valves, etc.). Check safety devices for function. If the quantity of the refrigerant is not enough, detect the leakage if any. Then reclaim, void, repair and charge. If the quantity of refrigerant is not enough, it needs to be reclaimed and refilled with completely new refrigerant. Check oil level at the sight glass (where sight glass is available). Carry out a test to ceck humidity inside oil Check crankcase heater for function. Check digital modulation - solenoid valve X X X X X X X X X X X X X X X X X See appropriate manual. (ifinstalled) EXTERNAL CONDENSER/ See appropriate manual. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 25 All manuals and user guides at all-guides.com 10.6 - Refrigeration circuit WHEN REPAIRING THE REFRIGERATION CIRCUIT, COLLECT ALL REFRIGERANT IN A CONTAINER: DO NOT ALLOW IT TO ESCAPE. • • When removing (for repairs) or charging refrigerant, it must always be done on both the high and low pressure sides of the compressor simultaneously. The compressor copper plated steel connections should be welded with a silfos material containing a minimum of 5% silver. 10.6.2 - Oil charge R410A The oil to be used when topping up (only if there are any leaks) is EMKARATE RL 32-3MA or Mobil EAL Arctic 22CC (see Tab. 9 and Tab. 10). Tab. 9 - EMKARATE RL 32-3MA oil Viscosity at 40 0C : 31.2 cSt Viscosity at 100 0C : 5.6 cSt Viscosity index (ISO Grade) : 32 Tab. 10 - Mobil Arctic EAL 22CC oil Density (at 15 0C) : 0.967 kg/l Flash point (C.O.C.) : 245 °C Pour point : <-54 °C Viscosity at 40 0C : 23.6 cSt Viscosity at 100 C : 4.7 cSt Viscosity index (ASTM D2270) : 130 0 These oils rapidly absorb the humidity present in the air when they are exposed to the atmosphere. If the oil absorbs humidity, the ester molecules can break down, forming acidity. We therefore recommend exposing the oil for as short time as possible (no more than a few minutes) and, in case of topping up, using exclusively the oil indicated on the refrigerating compressor. Normally 1 or 2-litre cans are available for this purpose; once they are opened, they must be completely used up. They must not be used after a long period, as they absorb humidity. It is therefore obvious that the taps of the compressor must only be turned after the whole plant has been subjected to a vacuum and partial filling. 10.6.3 - Oil topping-up of an installed circuit If oil leakages occur, the topping-up operation is necessary. (Contact the local Service before intervention). 10.7 - Dismantling the unit The machine has been designed and built to ensure continuous operation. The working life of some of the main components, such as the fan, depends on the maintenance that they receive. CAUTION: The unit contains substances and components hazardous for the environment (electronic components, lead gel battery, refrigerating gases and oils). At the end of the useful life, when the unit is dismantled, the operation must be carried out by specialized refrigerating technicians. The unit must be delivered to suitable centers specialized for the collection and disposal of equipment containing hazardous substances. The lead gel battery, refrigeration fluid and the lubricating oil inside the circuit must be recovered according to the laws in force in the relevant country. 26 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com 10.8 - Regulation (EU) no. 517/2014 (F-gas) Stationary air conditioners placed into the European Community market and operating with fluorinated greenhouse gases (F- gas, such as R407C, R134a, R410A), they have to comply since Jan 1, 2015 with the F- gas Regulation (EU) No. 517/2014. It replaces the Re. (EU) no. 342/2006, applied since July 4, 2007. By the way, the refrigerants as R22 are not F- gas and their relevant regulation is Reg. (EU) no. 2037/2000. Following notes have to be considered when operating with the above mentioned equipments: • Fluorinated greenhouse gases are covered by the Kyoto Protocol. • The fluorinated greenhouse gases in this equipment should not be vented to the atmosphere. • Referring to the value noted in Annex I and Annex IV of Regulation (EU) No 517/2014 here below the global warming potential (GWP) of some major F- gases or mixtures: R- 134a R- 407C R- 410A GWP 1430 GWP 1774 GWP 2088 • Operators of the above mentioned applications, which contain fluorinated greenhouse gases, shall, using all measures which are technically feasible and do not entail disproportionate cost: a. Prevent leakage of these gases and as soon as possible repair any detected leakage. b. Ensure that they are checked for leakage by certified personnel. c. Ensure for putting in place arrangements for the proper recovery by certified personnel. d. In case of applications containing 5 tons CO2 equivalent, i.e. 2.4 kg of R410A (10 tons in case of hermetically sealed system) or more of F- gases: certified personnel and Companies (according to Reg. 303/2008) provides regular leak testing (according to Reg. 1516/2007 and Reg. 1497/2007) and maintain records of maintenance activities in a dedicated log book. e. Recovery for the purpose of recycling, reclamation or destruction of the fluorinated greenhouse gases, pursuant to Art. 8 of the Regulation shall take place before the final disposal of that equipment and, when appropriate, during its servicing and maintenance. • Operator, according to Regulation Article 2, point 8, means the natural or legal person exercising actual power over the technical functioning of products and equipment covered by this Regulation. The State may, in defined, specific situations, designate the owner as being responsible for the operator’s obligations. Where large installations are involved, service companies are contracted to carry out maintenance or servicing. In these cases the determination of the operator depends on the contractual and practical arrangements between the parties. • Direct methods of leakage checking approved by the manufacturer (Reg. 1516/2007 and Reg. 1497/2007) a. Gas detection device adapted to the refrigerant in the system;the sensitive of portable gas detection devices (as a direct test method) shall be at least five grams par year. b. Proprietary bubble solutions / soapsuds. • Additional information located into a dedicated label of unit (Reg. 1494/2007) a. Where fluorinated greenhouse gas is foreseen to be added to the equipment outside of the manufacturing site at the point of installation, a dedicated label accommodates notation of both the quantity (kg) pre-charged in the manufacturing plant and of the quantity charged at the installation site as well as the resulting total quantity of f-gas as a combination of the above mentioned quantities, in a manner which conforms to the legibility and indelibility. Our split units are usually not pre-charged on factory, in this case the total quantity of refrigerant charged in the unit has to be written in the relevant label, during the commissioning operation at the installation site. b. Our packaged units (not split) operating with f - gas are usually full charged on factory and the total amount of refrigerant charge is already reported on the label. In this case, the label has no need of further written information. c. In generally, the above mentioned information has been located in the main nameplate of relevant unit. d. For equipment with double refrigeration circuits, in regards to differentiates requirements on the basis of the quantity of f-gas contained, the required information about refrigerant charge quantities has to be listed separately for each individual circuit. e. For equipments with separate indoor and outdoor sections connected by refrigerant piping, the label information will be on that part of the equipment which is initially charged with the refrigerant. In case of a split system (separate indoor and outdoor sections) without a factory pre-charge of refrigerant, the mandatory label information will be on that part of the product or equipment which contains the most suitable service points for charging or recovering the fluorinated greenhouse gas(es). • Safety data sheets of f-gases used in the products are available on demand. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 27 All manuals and user guides at all-guides.com Enclosure A - Electrode Humidifier A.1 - Electrode humidifier The operation of immersed electrode humidifiers is based on a very simple physical principle. As common drinking water contains a certain quantity of dissolved mineral salts, and is consequently slightly conductive, applying a voltage to metal electrodes immersed in the water creates an electric current that heats the water until producing steam (Joule effect). The quantity of steam produced is proportional to the electric current, which is in turn proportional to the level of water. In order to obtain optimum performance from the humidifier it is advisable to read this manual carefully. Tab. 1 - Humidair specifications HUMIDAIR MODEL MAIN POWER SUPPLIES (V ± 10%) KUEC2E SETTING ABSORBED POWER MAX. CYLINDER MAX. SUPPLY CURRENT WATER VOLUME WATER QUANTITY MAX. DRAIN WATER QUANTITY [kg/h] (*) [A] [kW] [l] [l/min.] [l/min.] 400V / 3ph / 50Hz 3.9…13.0 13 9 5.5 0.6 10.0 For humidifier current (FLA) and rated power, refer to electrical features in the Enclosure B. (*) Unit is factory- set to produce about 50% of the maximum value (see iCOM manual). A.2 - Installation The humidifier is supplied already mounted within the air conditioner. The only necessary operations are the connections for the supply water and drain water. Supply Water. Only use mains drinking water with: • Pressure between 0.1 and 0.8MPa (1 and 8 bars), temperature between 1 and 40° C and an instant flow rate no higher than the rated flow of the fill solenoid valve, the connection is R ¾ (ISO 7/1); • Hardness no greater than 400 ppm of CaCO3 (40° fH), conductivity range: 75- 1250 μS/cm; no organic compounds. supply water characteristics Hydrogen ions Specific conductivity at 20° C(σR, 20° C) unit of measure normal water min. water with low salt content max min. max. (pH) 7 8.5 7 8.5 (σR, 20° C) S/cm 350 1250 75 350 Total dissolved solids(cR) mg/l (1) (1) (1) (1) Dry residue at 180° C(TH) mg/l (1) (1) (1) (1) Total hardness mg/l CaCO3 100 (2) 400 50 (2) 160 Temporary hardness mg/l CaCO3 60 300 30 (3) 100 Iron + Manganese mg/l Fe+Mn = 0.2 = 0.2 ppm Cl- = 30 = 20 mg/l SiO2 = 20 = 20 Residual chlorine mg/l Cl2 = 0.2 = 0.2 Calcium sulphate mg/l CaSO4 = 100 = 60 Metallic Impurities mg/l 0 0 0 0 Solvents, thinners, detergents, lubricants mg/l 0 0 0 0 Chlorides Silica (1)= values depend on the specific conductivity; in general: CR ≈0.65 * σR, 20° C; R180 ≈0,93 * σR, 20° C (2) = not less than 200% of the chloride content in mg/l CL(3) = not less than 300% of the chloride content in mg/l CL- There is not reliable relationship between hardness and conductivity of the water Important: • • • do not treat the water with softeners, this may cause the entrainment of foam, affecting the operation of the unit; do not add disinfectants or anti-corrosive compounds to the water, as these are potential irritants; the use of well water, industrial water or water from cooling circuits and, in general,any potentially chemically or bacteriologically contaminated water is not recommended. Connection: For the supply water connection see the details in Fig. 1 (point 11- 14) Drain Water. • • • A-1 This contains the same substances dissolved in the supply water, however in larger quantities; It may reach a temperature of 100° C; It is not toxic and can be drained into the sewerage system, category 3, EN 1717. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure A - Electrode Humidifier Important: For drain water connection see details in Fig. 1: • Use a drain hose Ø 32 mm, maximum length 10 m with minimum5% gradient, don’t make siphon on this hose to avoid back pressures in the drain piping. For configuration with bigger length or high head consider the PDX option with condensate pump. • Dispose the drain hose into an ordinary drainage network. (the drainage network should have a siphon (see Fig. 1) and must be able to withstand temperatures up to 100° C and able to drain water flow up to 10l/min. • Pay attention in the manual drainage of the steam cylinder if the drainage network isn’t able to drain 10 l/min, risk of water overflow on the humidifier. A.2.1 - Electrode humidifier components 1. chassis 2. fill tank 2a. conductivity electrodes 3. cylinder 3a. high level electrodes 3b. immersed electrodes 3c. filter inside the cylinder 4. cylinder fastening strap 5. hose kit 5a. supply hose 5b. fill hose 5c. drain pump and overflow outlet hose 5d. drain hose 6. fill solenoid valve 7. drain pump 8. drain connection (diameter 32mm) 9. steam outlet 10. steam distribution hose 11. manual valve (not supplied) 12. mechanical filter (not supplied) 13. supply hose (not supplied) 14. connection hose 15. drain hose with siphon (not supplied) Fig. 1 - The humidifier and its components Supply limit Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 A-2 All manuals and user guides at all-guides.com Enclosure A - Electrode Humidifier A.3 - Start - up and operation A.3.1 - Start - up Before using the humidifier, check the following: • • • • • Supply and drain connections. That the cut- off tap is open. All wiring. Earthing. Steam hose connection between steam cylinder and distributor. To start the humidifier simply switch on the air conditioner, which will in turn automatically start and stop the humidifier as required. The (adjustable) parameters which determine humidifier operation have already been factory- preset (see iCOM manual). A.3.2 - Operation Water contains even a small quantity of salts in solution, is a conductor of electricity. Therefore, if the steam cylinder is filled with water and a potential difference is applied between the electrodes, the water behaves like an ordinary electrical resistance and becomes hot, thus creating steam. The steam production rate can be controlled by varying the water level in the cylinder; the higher the water level, the deeper the electrodes are immersed into it and the greater the steam production. Note 1 In case of low water conductivity consult HPAC Technical Sales Support. Note 2 When starting with an empty cylinder, the water conductivity is normally insufficient for the HUMIDIFIER STEAM OUTPUT to be reached immediately. Therefore the humidifier produces as much steam as possible to fill the cylinder completely. Any evaporation water is immediately refilled. The drain valve is kept shut and therefore, as the steam does not contain any salts, the conductivity of the water within the cylinder slowly increases until the HUMIDIFIER STEAM OUTPUT is obtained. The length of the start- up period depends upon the water conductivity. For very conductive water it may occur that the HUMIDIFIER STEAM OUTPUT is obtained immediately. A.4 - Maintenance Important: the cylinder may be hot. Let it cool down before touching it or use protective gloves. A.4.1 - Cylinder replacement • • • • • • Completely drain the water contained in the cylinder; Turn the appliance off and open the disconnect switch on the mains power line (safety procedure); Remove the steam hose from the cylinder; Disconnect the electrical connections from the top of the cylinder; Release the cylinder from the fastening device and lift it up to remove it; Fit the new cylinder in the humidifier by performing the previous operations in reverse. A.4.2 - Cylinder maintenance (see cylinder instruction sheet) The life of the cylinder depends on several factors, including: the complete filling with lime scale and/or the partial or complete corrosion of the electrodes, the correct use and sizing of the humidifier, the output and the quality of the water, as well as careful and regular maintenance. Due to the aging of the plastic and the consumption of the electrodes, even an operable steam cylinder has a limited life and it is, therefore, recommended to replace it after 5 years or 10,000 operating hours. Important: the humidifier and its cylinder contain live electrical components and hot surfaces, and therefore all service and/or maintenance operations must be performed by expert and qualified personnel, who are aware of the necessary precautions. Before performing any operations on the cylinder, check that the humidifier is disconnected from the power supply; carefully read and follow the instructions contained in the humidifier manual. Remove the cylinder from the humidifier only after having drained it completely. Check that the model and the power supply voltage of the new cylinder correspond to the one being replaced. A.4.3 - Periodical checks • • • • • A-3 After one hour of operation: for both disposable and openable cylinders, check that there are no significant water leaks. Every fifteen days or no more than 300 operating hours: for both disposable and openable cylinders check operation, that there are no significant water leaks and the general condition of the casing. Check that during operation there are no arcs or sparks between the electrodes. Every three months or no more than 1000 operating hours: for disposable cylinders,check operation, that there are no significant water leaks and, if necessary, replace the cylinder; for openable cylinders, check that there are no markedly blackened parts on the casing: if this is the case, check the condition of the electrodes and, if necessary, replace them together with the O-rings and the cover gasket. Annually or no more than 2500 operating hours: for disposable cylinders, replace the cylinder; for openable cylinders check operation, that there are no significant water leaks, the general conditions of the container, check that there are no markedly blackened parts on the casing; replace the electrodes together with the O- rings and the cover gasket. After five years or no more than 10,000 operating hours: for both disposable and openable cylinders, replace the cylinder. After extended use or alternatively when using water with a high salt content, the solid deposits that naturally form on the electrodes may Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure A - Electrode Humidifier reach the stage where they also stick to the inside wall of the cylinder; in the event of especially conductive deposits, the consequent heat produced may overheat the plastic and melt it, and, in more severe cases,puncture the cylinder, allowing water to leak back into the tank. As a precaution, check, at the frequency recommended further on, for deposits and the blackening of the wall of the cylinder, and replace the cylinder if necessary. Warning: always disconnect the appliance before touching the cylinder in the event of leaks, as current may be running through the water. A.4.4 - Replacement and maintenance of other components Fill solenoid valve: after having disconnected the cables and the tubing, remove the solenoid valve and check the condition of the inlet filter; clean if necessary using water and a soft brush. Supply and drain manifold: check that there are no solid residues in the cylinder attachment, remove any impurities. Check that the gasket (O- ring) is not damaged or cracked; if necessary, replace it. Drain pump: disconnect the power supply, remove motor body unscrew the fastening three screws; remove any impurities and rinse. Supply tank & conductivity meter : check that there are no obstructions or solid particles and that the electrodes for measuring the conductivity are clean, remove any impurities and rinse. Hose kit: check that the hoses are free and do not contain impurities; remove any impurities and rinse. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 A-4 All manuals and user guides at all-guides.com Enclosure B - Technical data table Tab. 1 - Electrical data with premium fan module DIGITAL SCROLL Cooling System Configuration Cooling Fan(s) + Compressor(s) Cooling + Electrical heaters (Dehumidification) Fan(s) + Compressor(s) + Electrical heaters Cooling + Electrical heating + Humidification Fan(s) + Compressor(s) + electrode or infrared humidifier Model PX082 PX094 PX104 PX120 PX150 PX165 PX082 PX094 PX104 PX120 PX150 PX165 PX082 PX094 PX104 PX120 PX150 PX165 Power supply 400 V / 3 Ph + N / 50 Hz + earth 400 V / 3 Ph + N / 50 Hz + earth 400 V / 3 Ph + N / 50 Hz + earth FLA [A] LRA [A] Residual- Current Circuit Breakers Inn = 0.3A (400V)* 73 73 77 101 142 160 76 76 78 101 174 192 87 87 91 115 156 173 148 174 172 219 250 300 148 174 172 219 283 332 148 174 172 219 264 313 100A “C” 100A “C” 100 A “C” 125 A “C” 160 A “C” 200 A “C” 100A “C” 100A “C” 100A “C” 125A “C” 200A “C” 200A “C” 100A “C” 100A “C” 125A “C” 125A “C” 160 A “C” 200 A “C” min./max. Cu cable size 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 10..70mm2 * ATTENTION Only universal (type B, B+) RCD protective devices are permitted. NOTES: • The cables have to be sized in compliance with local standards and according to the type and characteristics (e.g. Amperes) of installation. • The data in the tables do not consider the absorbed current from the condensate pump and for other options not explicitly described. • The specific energy allowed to flow from the circuit breakers, installed by the user, must be lower than 300.000A2 x s. • Prescriptions on the differential relay required to the user: • for special places (healthcare facilities, etc...) comply with the local regulations; • For ordinary places, a low sensitivity is suggested (300 mA) coordinated with the value of the ground heater (IEC 364): Ra 50/Ia (Art. 413.1.4.1, CEI 648 or IEC60364445); • In case of frequent over-voltages with mains impulse, it is advisable to install a selective differential and to evaluate the need for adopting other devices; • The FLA is for units without the options of condensate pump and condensing unit; • The FLA is for units with AUTOMATIC FUNCTIONS only: in manual mode operation the FLA must be lower than the max. current of the main switch. Tab. 2 - EC fan connections Model version with premium fan module PX082 A PX094 A PX104 A PX120 A PX150 A PX165 A STD 8,3 9 9,4 9,4 7,9 9,6 EC Fan signal [VDC]* Downflow Up Downflow Down Dehumidification STD Dehumidification 7,3 8 7 8 8,6 7,6 8,4 8,9 7,9 8,4 8,9 7,9 6,9 7,5 6,5 8,6 8,9 7,9 NOTE: The EC fan settings can be modified acting on the control display (see Control manual). (*) Setting for Nominal Airflow at standard conditions, Filters class F5, ESP: Downflow Up 20 Pa; Downflow Frontal 0 Pa. Tab. 3 - Electrical data (standard components) Component Model version with premium fan module PX082 A PX094 A PX104 A PX120 A PX150 A PX165 A EC Fan (400V / 3Ph / 50Hz) Downflow Up Downflow Down LRA Nominal power* Nominal power* OA* [A] FLA [A] OA* [A] FLA [A] LRA [A] [A] [kW] [kW] 3x2.63 3x5 3x0.1 3x1.73 3x2.35 3x5 3x0.1 3x1.54 3x3.21 3x5 3x0.1 3x2.13 3x2.87 3x5 3x0.1 3x1.9 3x3.54 3x5 3x0.1 3x2.35 3x3.16 3x5 3x0.1 3x2.1 3x3.55 3x5 3x0.1 3x2.36 3x3.16 3x5 3x0.1 3x2.1 4x3,18 4x7,4 4x0,1 4x2,06 4x2,82 4x7,4 4x0,1 4x1,81 4x5,72 4x7,4 4x0,1 4x3,76 4x4,66 4x7,4 4x0,1 4x3,09 (*) At standard operating conditions, Filters class F5, ESP: Downflow Up 20 Pa; Downflow Frontal 0 Pa. (**)At nominal operating conditions: Condensing temperature 450C - Room conditions 24C / 50% RH B-1 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure B - Technical data table Component OA** [A] FLA [A] 16.56+16.5 15+14.90 21.76+21.85 28.14+24.76 36,63+30,77 35.89+45.38 2x15+2x15 2x15+2x15 2x16.20+2x16.2 2x22+2x21 2x31+2x25 2x34+2x31 Model version with premium fan module PX082 PX094 PX104 PX120 PX150 PX165 COMPRESSOR (400V / 3Ph / 50Hz) Nominal power** LRA [A] [kW] Digital Scroll 2x75+2x75 9.35+9.29 2x101+2x101 10.68+10.64 2x101+2x101 11.2+11.22 2x118+2x111 14.82+12.72 2x140+2x118 19,53+16,77 2x174+2x140 19.08+22.89 Winding resistance (Ohm) (2.26+2.27)+(2.26+2.27) (1.79+1.79)+(1.79+1.79) (1.79+1.79)+(1.79+1.79) (1.23+1.24)+(1.47+1.36) (1,11+1,11)+(1,23+1,24) (0,83+0,83)+(1,11+1,11) (*) At standard operating conditions, Filters class F5, ESP: Downflow Up 20 Pa; Downflow Frontal 0 Pa. (**)At nominal operating conditions: Condensing temperature 450 C - Room conditions 360 C / 24% RH Tab. 4 - Electrical data (optional components) ELECTRICAL HEATING COMPONENT Std. Capacity Model FLA Nominal power [A] [kW] ELECTRODE HUMIDIFIER Opt. High Capacity FLA [A] Nominal power [kW] PX082 32.5 22.5 PX094 32.5 22.5 PX104 32.5 22.5 32.5 22.5 PX150 32.5 22.5 PX165 32.5 22.5 FLA [A] CONDENSATE PUMP Nominal power [kW] FLA [A] Nominal power [kW] 9.0 1.6 0.15 (400V / 3Ph / 50Hz) PX120 10.8 7.5 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 13.0 B-2 All manuals and user guides at all-guides.com Enclosure B - Technical data table Tab. 5 - Calibrations of electrical components COMPONENT SETTING High Pressure transducer (HP) NOTES CONTACT Range 0-45 barg Output 0-5 V (see Control manual) Low Pressure transducer (LP) High Pressure Switch (HP) Range 0-17.3 barg Output 0-5 V STOP START 37.0 30.0 1 barg 1.5 barg (see Control manual) Reset Normally closed (fixed setting - manual reset) Clogged filter differential pressure switch (CF) Normally closed Filter F5 = 3 mbar Setting ring Tab. 6 - Adjustments and calibrations of valves (see Enclosed D - Refrigeration circuits) B-3 Component Calibration & Operating Application Electronic expansion valve Superheating control 6 8K Version with EEV Model Drawing ALCO EX5/6/7 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure B - Technical data table Tab. 7 - R410A refrigerant and oil charge MODEL BASE REFRIGERANT CHARGE (2) [kg - each circuit] Microchannel Coil Condenser PX082 PX094 PX104 PX120 PX150 PX165 25.4 25.4 26.9 26.9 27.7 30.7 BASE OIL CHARGE (1) [Liter, oil within compressor, each circuit] initial oil charge 2x1.8 2x1.8 2x1.8 2x3.25 2x3,8 2x3,5 Max topping up Max System Refrigerant Charge before oil addition (3) [kg – each circuit] Oil to be added over the Max System Refrigerant Charge (3) [Litre – each circuit] 13 13 13 13 13 13 a a a a a a 2x1.7 2x1.7 2x1.7 2x3.14 2x3,14 2x3,14 a = (0.025 x (total refrigerant charge for each circuit [kg] - max system refrigerant charge before oil addition [kg])) + 0.09 Tab. 7a - Refrigerant pipe charge EXTERNAL PIPE DIAMETER (mm) Gas [kg/m] 14 x 1 16 x 1 18 x 1 22 x 1.5 28 x 1.5 35 x 1.5 0,0108 0,0147 0,0192 0,0271 0,0469 0,076 35.0° C 0,1142 0,1554 0,2030 0,2862 0,4956 0,812 liquid at different condensing temperatures (3) R410A [kg/m] 46.0° C 0,1056 0,1438 0,1878 0,2648 0,4585 0,7512 57.0° C 0,0958 0,1304 0,1703 0,2402 0,4158 0,6812 (1) The recommended oil for units with R410A refrigerant is EMKARATE RL 32- 3MA. (2) Total basic reference charge useful for unit coupled with the remote condenser suggested for ambient temperature up to 35°C, the relevant liquid receiver (12.5 l) and the pumped refrigerant Econophase. With Smart Aisle application increase refrigerant charge up to 10%. The correct charge must be precisely defined in field, starting with about 80% of the basic reference charge and following the instruction given in para. 4.2. (3) Topping up is requested for short pipeline too, due to the extra-charge of refrigerant. NOTICE: Check oil level inside compressor, where compressor’s oil level sight glass is available, after 30 min. of compressor running at maximum capacity: oil level must be between 1/2 and 3/4 of sight glass. In tandem compressors the oil level must be checked with both compressors running at maximum capacity (note: when only one compressor is running, the oil level inside the compressor that is not currently running could be at the minimum and the compressor, that is running, at the maximum capacity; when one compressor is running at maximum capacity and one compressor is running in modulating capacity, the oil level in the latter one could be between 1/2 and the minimum). Note: The air conditioner is supplied pressurized with helium at 2 bar. Tab. 7b - Condenser ambient selection per circuit, 350C room temperature. Indoor model PX082 PX094 PX104 PX120 PX150 PX165 35° C MCL055 MCL055 MCM080 MCM080 MCL110 MCL165 Outdoor Design Ambient Max Temperature 40° C MCL055 MCM080 MCM080 MCL110 MCL165 MCL165 Tab. 7c - Condenser refrigerant charge with 12.5 l liquid receiver - as reference Model MCL055 MCM080 MCL110 MCL165 Charge kg 12..9 14.4 17.8 22.6 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 46° C MCM080 MCM080 MCL110 MCL110 MCL165 MCL165 Tab. 7d - Liebert EconoPhase module charge - as reference Model Charge per circuit, kg PR 125 2.5 B-4 All manuals and user guides at all-guides.com Enclosure C - Installation drawings Fig. 1 Overall dimensions and Service Area DOWNFLOW DOWN E* D D G G DOWNFLOW UP A* Floor Level F MAX 800 600 Floor Level Tab. 1 - Overall dimensions - Service area (referring to Fig. 1) Unit Downflow Downflow Models B Up Down [mm] A* [mm] E* [mm] PX082 PX094 2550 1970* 1370* PX104 PX120 PX150 3350 2570 1970 PX165 Plenum 500- 600700- 800900 Options AVAILABLE PLENUM HEIGHTS: D [mm] Plenum for silencing cartridges Plenum for high efficiency filters 600- 900 600- 900 F (free space between unit bottom and basement): max. 800 mm (base frame/legs kit availability) min. 600mm (to get declared performances) min. 300mm (minimum working conditions) G (free space between ceiling and unit top or plenum top if installed): min. 600mm (to get declared performances) min. 300mm (minimum working conditions) * In Downflow Up units with predisposition for damper and plenum installation (digit 18 = H or L) the unit is shipped with a connecting flange 50 mm high fixed on the unit top, so the unit is 50 mm higher. If required, the flange can be removed by unscrewing the fixing screws (removing the side panel to access the screws head) and repositioned later. C-1 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure C - Installation drawings Fig. 2 Hole in the floor for Downflow versions Downflow Up Downflow Down Tab. 2 - Hole in the floor for Downflow units, dimensions in mm Configuration Downflow Up PX082 PX094 PX104 PX120 PX150 PX165 A 2450 3250 B C* A 760 70 2526 760 70 3326 B 840 840 C* A B C* A B C* A B C* 30 2506 820 30 2532 846 20 2570 885 50 30 3306 820 30 3332 846 20 3370 885 50 Unit With Base Frame ** With Legs kit ** Downflow Down With floor tiles support kit ** * Minimal distance of the working unit from the back wall. Caution: In order to assemble and/or install accessories, a larger distance might be required. In that case, the unit can be moved in the working position after installation / assembly procedures. ** Optional accessories - see details in Enclosures E. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 C-2 All manuals and user guides at all-guides.com Enclosure D - Refrigerant, hydraulic and electrical connections Tab. 1 - Electrical data with basic fan module PX082 Model Unit Connection CD HF Humidifier feed IL2 OG1 OG2 PX104 PX120 PX150 PX165 ECONOPHASE Refrigerant liquid line inlet 1* Refrigerant liquid line inlet 2* Refrigerant gas line outtlet 1* Refrigerant gas line outlet 2 * Condensate drain IL1 PX094 O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø18 mm O.D. Ø22 mm O.D. Ø22 mm O.D. Ø22 mm O.D. Ø28 mm O.D. Ø28 mm O.D. Ø28 mm O.D. Ø22 mm O.D. Ø22 mm O.D. Ø22 mm O.D. Ø28 mm O.D. Ø28 mm O.D. Ø28 mm I.D. Ø20 [mm] R ½ - ISO 7/1 (Electrode Humidifier), O.D. 6 [mm] (Infrared Humidifier) HD Humidifier drain EC Electrical power supply EC aux Low voltage cables I.D. Ø32 [mm] (Electrode Humidifier), I.D. Ø22 [mm] (Infrared Humidifier) Ø 48 [mm] Ø 40 - Ø 36 [mm] * Connection size only. The connecting pipe diameter depends on unit model, see Tab. 6 in par. 4.1.2 Fig. 1 - Refrigerant, water and electrical connections PX082-094-104-120 ECONOPHASE, top view 2550 102 HD/HF 890 CD OG2 193 IL2 132,5 230 190 560 EC aux 480 IL1 OG1 132,5 215 193 EC 117 117 223 Fig. 2 - Refrigerant, water and electrical connections PX150-165 ECONOPHASE, top view 3350 86 86 118 193 OG2 118 193 279 IL2 279 890 579 EC aux OG1 121 D-1 EC IL1 579 CD CD 121 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure D - Refrigerant, hydraulic and electrical connections Fig. 3 - Refrigerant circuit EconoPhase version - Dual circuits - Tandem DIGITAL SCROLL compressors - EEV 15 15 T T 11 11 ØE1 ØE2 6 6 16 16 MC 2 1 12 (FOR PX120) T 20 ØB2 1 1 20 (FOR PX082-094-104) 12 T T (FOR PX120) 9 3 FG 6 20 (FOR PX082-094-104) 9 FG 18 MC 2 2 12 ØB1 TANDEM MC 10 12 COMP. COMP. T 20 ØB2 ØD 10 2 1 ØD COMP. MC ØB1 TANDEM 6 COMP. 6 3 6 18 6 6 19 19 8 ØC ØA1 13 8 ØC ØA2 17 13 6 6 17 13 13 SUPPLYING LIMIT EXTERNAL TO PDX UNIT Nr. DESCRIPTION 6 ACCESS VALVE 5/16 20 NTC TEMPERATURE SENSOR FOR DIGITAL COMP. 3 HIGH PRESSURE SWITCH 19 ACCESS VALVE 1/4 2 CRANKCASE HEATER 18 HIGH PRESSURE TRANSDUCER 1 COMPRESSOR 17 CHECK VALVE 10 bar (145 psi) 16 LOW PRESSURE TRANSDUCER EEV 15 EVAPORATOR PX082A 22 22 22 13 SHUT-OFF VALVE PX094A 22 22 12 CHECK VALVE PX104A 22 11 TEMPERATURE SENSOR FOR EEV PX120A 28 10 ELECTRONIC EXPANSION VALVE EEV PX150A 9 SIGHT GLASS PX165A 8 FILTER DRYER Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 Model ØA1 ØA2 ØB1 ØB2 ØC ØD ØE1 ØE2 22 18 18 28 28 22 22 18 22 28 28 22 22 22 18 22 28 28 28 22 28 18 22 28 35 28 28 28 28 18 22 35 35 28 28 28 28 18 22 35 35 D-2 All manuals and user guides at all-guides.com Enclosure E - Accessories E.1 Kit Legs E.2 Baseframe Legs kit can be supplied on request to support Liebert® PDX when installed with a raised floor. The legs are fixed with the unit frame and allow to support the unit at different height, three kits are available with different height: adjustable in the range: h1 30 - 370 mm; h2 370 - 570 mm; h3 570 - 800 mm. A base frame can be supplied on request to support Liebert® PDX when installed with a raised floor. The frame could be regulated with a height from 120 mm to 800 mm and the unit is fixed on it. E.3 Fresh air module E.4 Vertical flow extension hood Downflow PX082 …120 The fresh air kit, optional, has a G3 class filter installed on the intake side of the fan and is connected to the PDX unit with a 100 mm diameter plastic duct. As the fresh air intake is positioned close to the fan suction, it will easily mix with the recirculation air. E-1 An extension hood can be supplied on request and can be installed on top of the unit. It is available with different height: 500 mm; 600 mm; 700 mm; 800 mm; 900 mm. It has the same design as the unit and consists of sandwich panels lined with non-flammable insulation material of class 0 (ISO 1182.2), density 30 kg/m3. Note: In downflow units it is required a flange 50 mm high to connect the extension hood to the unit (see E.10). Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure E - Accessories E.5 Hood with high efficiency air filter E.6 Plenum with silencing cartridges Optional high efficiency filters, filtration class F6, F7 and F9 in accordance with the CEN EN 779 standard, are made of fiberglass filter media. The filters are placed in ”V” sections with a solid external frame in polypropylene and can withstand remarkable pressure and flow variations. These filters will be installed within an additional duct on the unit top. Note: In downflow units it is required a flange 50 mm high to connect the hood to the unit (see E.10). These are special cartridges made of self - extinguishing material with a high noise attenuation capacity. They are guaranteed against disintegration and release of particles do to friction of the air. Despite a small additional pressure drop, these cartridges provide a remarkable sound power level reduction. Note: In downflow units it is required a flange 50 mm high to connect the plenum to the unit (see E.10). E.7 Horizontal hood with grill E.8 Floor tiles support kit A supply plenum with horizontal air flow can be installed on top of the unit. The 600 mm high plenum has the same design as the unit; it consists of sandwich panels lined with non-flammable insulation material of class 0 (ISO 1182.2), density 30 kg/m3. It is equipped with a double deflection grill. Floor tiles support kit can be supplied on request to support tiles around Liebert® PDX Downflow Down, when installed with a raised floor. Floor tiles support is fixed on the unit frame/fan module and allows to support tiles until 40 mm thickness. With a correct installation, the maximum admitted vertical distributed load on the perimeter is 180 kg/m. I.e.: on the lateral side, 870 mm long, the maximum admitted distributed load is 157 kg. Floor tiles support is earthed with the unit frame. Follow local rules for system grounding. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 E-2 All manuals and user guides at all-guides.com Enclosure E - Accessories E.9 Fans maintenance kit Fans maintenance kit can be supplied on request to support tiles on Liebert® PDX Downflow Down when installed with a raised floor. Fans maintenance kit allows maintenance operations, in particular fans replacement, when the fans are installed below the floor level. Removing tiles on the frontal area, it is possible to lift some footboards, moving them on the lower level, creating a service volume in the raised floor. With a correct installation, the maximum admitted vertical distributed load is 600 kg/m2. Footboards are designed to support distributed load as indicated above, and the maximum concentrated load is 150 kg (on the area 50x50 mm). Fans maintenance kit must be earthed following the local rules. 50 E.10 Connecting Flange In Downflow Up, Downflow Down units with predisposition for damper, economizer and plenum installation (digit 18 = H or L) the unit is shipped with a connecting flange 50 mm high fixed on the E-3 unit top, so the unit is 50 mm higher. If required, the flange can be removed by unscrewing the fixing screws (removing the side panel to access the screws head) and repositioned later. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure F - Infrared Humidifier F. 1 - Infrared Humidifier The infrared humidifier design consists of quartz lamps mounted above a stainless steel water reservoir. The lamps never come in contact with the water. When humidification of room air is required, infrared rays generate water vapor-without impurities or odor, within seconds. In order to obtain optimum performance from the humidifier it is advisable to read this manual carefully. Tab. 1 - Infrared Humidifier specifications UNIT MODEL PAN MAIN POWER SUPPLIES (V ± 10%) NOMINAL CAPACITY [kg/h] ABSORBED CURRENT [A] POWER INPUT [kW] PX082...165 Stainless steel 400V / 3ph / 50Hz 10 13.9 9.6 F. 2 - Installation The infrared humidifier is supplied already mounted within the air conditioner. The only necessary operations are the connections for the supply water and drain water. Supply Water. • • • Maximum water pressure 200 kPa Size humidifier supply line for 3.8 l/min, with a minimum water pressure of 138 kPa Do not supply de-ionized water to the humidifier Drain Water. • This contains the same substances dissolved in the supply water, however in larger quantities; • It may reach a temperature of 100 ° C; • It is not toxic and can be drained into the sewerage system, category 3, EN 1717. • Dispose the drain hose into an ordinary drainage network. The drainage network should have a siphon and must be able to withstand temperatures up to 100° C F. 2.1 - Infrared humidifier components 1. humidifier pan 6. discharge connection 2. humidifier standpipe 7. supply line 3. solenoid valve flow regulation 8. manual reset thermostat 4. float switch 9. infrared bulbs 5. junction block Fig. 1 - The infrared humidifier and its components Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 F-1 All manuals and user guides at all-guides.com Enclosure F - Infrared Humidifier F. 3 - Start - up and operation F. 3.1 - Start - up Before using the humidifier, check the following: • Supply and drain connections. • That the cut- off tap is open. • All wiring. • Earthing. To start the humidifier simply switch on the air conditioner, which will, in turn, automatically start and stop the humidifier as required. The (adjustable) parameters which determine humidifier operation have already been factory- preset (see iCOM manual). F. 3.2 - Operation During normal humidifier operation, deposits of mineral solids will collect in the humidifier pan and on the float switch. These must be cleaned periodically to ensure proper operation. Frequency of cleaning must be locally established because it depends on humidifier usage and local water quality. A spare pan is recommended to reduce maintenance time at unit. The Liebert auto-flush system can greatly increase the time between cleanings, but does not eliminate the need for periodic checks and maintenance. F. 4 - Maintenance WARNING: Optical radiation; the humidifier components may be hot. Let it cool down before touching it or use protective gloves. The infrared humidifier contains live electrical components and hot surfaces and therefore all service and/or maintenance operations must be performed by expert and qualified personnel, who are aware of the necessary precautions. Before performing any operations, check that the humidifier is disconnected from the power supply; carefully read and follow the instructions contained in the manual. F. 4.1 - Cleaning Humidifier Pan and Float Switch Before turning off unit: 1. With the unit operating, remove call for humidification at the Liebert iCOM control. 2. Let the blower operate 5 minutes to allow the humidifier and water to cool. 3. Turn the unit Off at the Liebert iCOM control. 4. Open the air conditioner door and remove safety panels, if installed. 5. Pull out the humidifier standpipe in pan. 6. Inspect the O- ring (replace if necessary). 7. Let the pan drain and the condensate pump operate (if applicable). 8. Disconnect power from the unit. 9. Disconnect the drain coupling from the bottom of the pan. 10. Remove the thermostat from the bottom of the pan and retaining screws from sides of pan. 11. Slide pan out. 12. Loosen scale on the side and bottom of the pan with a stiff nylon brush or plastic scraper. 13. Flush with water. 14. Carefully clean the scale from the float switch (make sure to reinstall correctly; see Figure 2). 15. Reinstall the pan, thermostat, standpipe, drain coupling, cover and screws into the humidifier. 16. Operate the humidifier and check for leaks. Fig. 2 - Correct orientation of float switch Correct Switch Orientation F-2 Incorrect Switch Orientation Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure F - Infrared Humidifier F. 4.2 - Changing Humidifier Lamps CAUTION: Touching quartz lamps with bare hands will severely shorten bulb life. Skin oils create hot spots on lamp surface. Wear clean cotton gloves when handling lamps. 1. 2. 3. 4. 5. 6. 7. 8. 9. Remove the humidifier pan (see F.4.1 - Cleaning Humidifier Pan and Float Switch, Steps 1 to 11). Disconnect power from the unit. At the humidifier, remove the screws and cover from the high- voltage compartment. Disconnect one end of the purple jumper wires. Using a continuity meter, locate the burned- out lamp. Remove the lamp brackets under the lamps. Loosen the two screws securing the lamp lead wires to the junction block. Pull the bulb straight down and discard it. Wrap the lead wires once around the new lamp’s metal ends. This will support the lamp and allow for thermal expansion. Insert the lead wires into the junction block and torque the screws 10. Reassemble by reversing Steps 1 to 9. F. 4.3 - Periodical checks 1. 2. 3. 4. 5. 6. Check drain lines and trap for clogs Check/clean pan for mineral deposits Clean reflector Check water make- up valve for leaks Check humidifier lamps (replace if burnt out) Check wire connections (inside humidifier box) Tab. 2 - Infrared Humidifier-troubleshooting Symptom Possible Cause Check or Remedy Check water supply. Humidifier pan not filling Check fill valve operation Check drain stand pipe adjustment Check for clogged waterline No humidification Control not calling for humidity Check monitor status Humidity contact not pulling in Check visually. If contact is made, check line voltage after contactor and fuses or CBs. Check for open humidifier safety stat Humidifier bulb burned out Replace bulb. Loosen lead on old bulb. Trim excess lead length on new bulb to avoid shorts. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 F-3 All manuals and user guides at all-guides.com Enclosure G - Ultrasonic Humidifier G. 1 - Ultrasonic Humidifier Ultrasonic Humidifier operates on the principle of ultrasonic nebulization. A 48 VAC voltage is rectified on an oscillator circuit and transformed into a high frequency signal of 1.65MHz. This signal is transmitted to a transducer installed in the water which then transforms the signal into high frequency automatic vibrations. The built-in transducers - also called ”thickness transducers” - change their thickness 1.65 million times per second in accordance with the signal of 1.65 MHz applied. Ultrasonic Humidifier can work only with demineralized water with conductivity < 5 μS/cm(up to 20 μS/cm for a short time). If demineralized water is not available, provide demineralizer (not supplied). Ultrasonic Humidifier is controlled by a microprocessor-based electronic controller. It includes control board, driver board and remote display board, all of them housed inside the humidifier electrical panel, located behind Liebert® PDX door. The functioning logic of the Ultrasonic Humidifier is PROPORTIONAL. The controller comes complete with DSP card which allows to display and modify all the parameters of the humidifier as well as to detect any abnormal condition via alarm messages. For safety reason and in order to obtain optimum performance from the humidifier, this manual and the HSU08RM000 manual must be read carefully Tab. 1 - Ultrasonic Humidifier specifications Humidifier Model POWER SUPPLIES (V AC) SETTINGS [kg/h] NUMBER OF TRANSDUCERS ABSORBED POWER [W] HSU08RM000 48 0…6.0 16 670 G. 2 - Installation The Ultrasonic humidifier is supplied mounted within one base module 400 mm height. The base module with humidifier is supplied stand alone and it will be installed and connected with the air conditioner on field. The module can be installed on the raised floor, see Fig. 1, or in the raised floor, see Fig. 2 (front and bottom module opened, sides and back module closed). When installed in the raised floor it is necessary to remove the module frontal panel to have also frontal air delivery. A base frame, available on request, is required to support ultrasonic humidifier module. Ensure 1 meter of free space (without obstacles) on ultrasonic humidifier module outlet. For Extended Height unit, connect the fan module above the humidifier module and the coil module above the fan module. Connect humidifier electrical cable, coming from the air conditioner, to the ultrasonic humidifier. Connect water supply, water drain, safety overflow and humidifier drain pan water drain. The relevant piping connections shall be in material resistant to fully demineralized water. Refer to HSU08RM000 manual for details. Fig. 1 - Ultrasonic humidifier module on the raised floor, frontal and lateral views G-1 Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com Enclosure G - Ultrasonic Humidifier Fig. 2 - Ultrasonic humidifier module in the raised floor, frontal and lateral views Supply Water. • • • • Supply fully demineralized water with conductivity<5 μS/cm. If demineralized water is not available, provided mineralizer (not supplied); Water pressure from 50 kPa to 500 kPa; Water temperature from 8° C to 40° C; Dust or dirt must not get into the water lines; Refer to HSU08RM000 manual for details. Drain Water. • • • The drain water contains the same substances dissolved in the supply water, however in larger quantities; It is not toxic and can be drained into the sewerage system, category 3, EN 1717; Dispose the drain hose into an ordinary drainage network (the drainage network should have a siphon). Refer to HSU08RM000 manual for details. G. 2.1 - Infrared humidifier components 1. Humidifier 2. Fan case 3. Mist guide cover 4. Fan 5. Metal plug 6. Cable 7. Metal plug 8. Cable 9. Water drain 10. 11. 12. 13. 14. 15. 16. 17. 18. Safety overflow Mist guide pipe Ring and nut Humidifier drain pan Air filter Water supply connection Check valve (to be provided by the Customer) Damper Humidifier drain pan water drain Fig. 3 - The Ultrasonic humidifier and its components Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 G-2 All manuals and user guides at all-guides.com Enclosure G - Ultrasonic Humidifier G. 3 - Start - up and operation G. 3.1 - Start - up Before using the humidifier, check the following: • Supply and drain connections. • That the cut- off tap is open. • All wiring. • Earthing. To start the humidifier simply switch on the air conditioner, which will, in turn, automatically start and stop the humidifier as required. The (adjustable) parameters which determine humidifier operation have already been factory-preset (see iCOM manual). Refer to iCOM manual and HSU08RM000 manual for details. G. 3.2 - Operation Ultrasonic humidifier operates on the principle of ultrasonic nebulization. The mist generated in the water tank by means of the transducer is blown into the room by the built-in fan. The humidifier consists of nebulization modules, solenoid valve for the control of the supply water, float switch and a case that houses the fan. Refer to HSU08RM000 manual for details. G. 4 - Maintenance If the humidifier is not used for a long period, the water must be drained off. NEVER operate the humidifier without air supply. Before performing any operations, check that the humidifier is disconnected from the power supply; carefully read and follow the instructions contained in the manual. G. 4.1 - Periodical checks 1. 2. 3. 4. G-3 Check drain lines and trap for clogs Check/clean pan for dust Check wire connections (inside humidifier box) Check status of humidifier air filters Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019 All manuals and user guides at all-guides.com All manuals and user guides at all-guides.com VertivCo.com | Vertiv - EMEA, via Leonardo Da Vinci 16/18, Zona Industriale Tognana, 35028 Piove di Sacco (PD) Italy, Tel: +39 049 9719 111, Fax: +39 049 5841 257 © 2016 Vertiv Co. All rights reserved. Vertiv, the Vertiv logo and Vertiv Liebert HPF are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. Liebert® PDX, EconoPhase Version - UM - 265133 - 29.08.2019