The Hong Kong Polytechnic University Per Unit Why per unit? • • • • • • • Multiple voltage levels: 400kV, 275kV, 132kV, 11kV, 400V Makes circuit analysis rather confusing Transformer impedance (Ω) depends on prim/sec referral Normalize all quantities to help understanding Avoid confusion due to transformers Ideal transformer winding can be eliminated (assumes proper specification of base values) Voltages, currents and impedances expressed in per unit do not change when referred from primary to secondary • Per unit impedances of equipment of similar type are usually similar if equipment ratings are used as base values • Manufacturer usually specify impedance of item of plant in per unit (or percent) using nameplate rating as base • Per unit values result in more meaningful data 1 The Hong Kong Polytechnic University Per Unit Basic Units • The 4 basic electrical quantities are: ‒ Voltage V (volt) ‒ Current I (amp) ‒ Impedance Z (ohm) ‒ Power S (VA) • For single‐phase circuits, ‒ V(volt) = Z(ohm) × I(amp); ‒ S (VA) = V(volt) × I(amp)* 2 The Hong Kong Polytechnic University Per Unit Per unit notation • In per unit notation, the physical quantity is expressed as a fraction of the reference value, i.e. per unit value = actual value/base value in the same unit. e.g. V(in per unit) = V(in kV)/V base (in kV) where the base value is a reference value for magnitude. • In per unit notation we would like to keep the basic relations: Spu = Vpu Ipu* Vpu = Zpu Ipu; • Hence the base quantities should be chosen such that: Base voltage (VB) = base impedance (ZB) × base current (IB) Base power (SB) = base voltage (VB) × base current(IB) 3 The Hong Kong Polytechnic University Per Unit Base Values • Thus only two of the base quantities can be arbitrarily chosen, the other two will follow directly. • It is common practice to specify base power (SB) and base voltage (VB). • Then it follows base current base impedance IB = SB/VB ZB = VB/IB =VB2/SB 4 The Hong Kong Polytechnic University Per Unit Base values for 3‐phase systems • For 3‐phase systems it is common practice to describe system operation with: total 3‐phase power S = S3‐φ line voltage V = Vline line current I = Iline equivalent impedance/phase Z = Zph with (in magnitude) Vline = √3ZphIline S3‐φ = √3VlineIline 5 The Hong Kong Polytechnic University Per Unit • Hence if base values are chosen for: total 3‐phase power SB line voltage VB Then base line current: IB = SB/ √3VB base impedance: ZB = VB/ √3IB = VB2/SB 6 The Hong Kong Polytechnic University Per Unit • Supply: 400 V, 50 Hz, 3‐phase • Load: 3 identical coils with Z = 20+j15 Ω in star connection • Find: line current, power supplied, power factor Take (for example) Base power (total 3‐phase) SB = 10 kVA Base voltage (line‐to‐line) VB = 400 V Then Base current IB = SB/√3VB = 14.43 A Base impedance ZB = VB2/SB = 16 Ω Given V = 400 V = 1.0 p.u Z = 25∠36.9o Ω = 1.5625∠36.9o p.u. 7 The Hong Kong Polytechnic University Per Unit • Current I = V/Z = 1.0 /1.5625 p.u. = 0.64 p.u. = 0.64×14.43 A = 9.235 A • Apparent power S = VI = 1.0×0.64 = 0.64 p.u. = 6.4 kVA • Power factor p.f. = cos 36.9o = 0.8 • Active power P = VI × pf = 0.64 × 0.8 = 0.512 p.u. = 0.512 × 10 = 5.12 kW. 8 The Hong Kong Polytechnic University Per Unit Base values for a transformer • In a transformer, two circuits are not directly connected but magnetically coupled. The voltages of the windings are in the ratio of turns and currents in inverse ratio. • For the coupled circuit, we should then choose ‒ The same base power ‒ Base voltages in the ratio of turns • This will ensure Spu, Vpu, Ipu, to remain unchanged when passing through an ideal transformer. 9 The Hong Kong Polytechnic University Per Unit Let n1,n2 be the number of turns in primary and secondary winding. Z1, Z2 be the primary and secondary winding impedance. Total impedance referred to primary: ZT1 = Z1 + (n1/n2) 2 Z2 Total impedance referred to secondary: ZT2 = Z2 + (n2/n1)2 Z1 = (n2/n1)2 ZT1 If base values were chosen for the transformer: VB1 = (n1/n2)VB2. SB1 = SB2; Then IB1 = (n2/n1)IB2 ; ZB1 = (n1/n2)2 ZB2 Thus per unit impedance of transformer Zpu = ZT1/ZB1 = ZT2/ZB2 is the same whether we use the total impedance referred to primary or secondary 10 The Hong Kong Polytechnic University Per Unit Equivalent circuit for transformer • In the per unit representation, the equivalent circuit of a transformer is a simple winding impedance Zpu (with excitation branch ignored). (Ipu)1 (Vpu)1 (Zpu) (Ipu)2 (Vpu)2 11 The Hong Kong Polytechnic University Per Unit Base Conversion • If the per unit values are given based on SB1 and VB1 which are different from the chosen base SB2 and VB2 for analysis, the given per unit values must be modified before they can be used. Thus (Vpu)2 = V/VB2 = (Vpu)2 × VB1/VB2 (Spu)2 = S/SB2 = (Spu)1 × SB1/SB2 (Ipu)2 = I/IB2 = (Ipu)1 × IB1/IB2 = (Ipu)1 × VB2/VB1 x SB1/SB2 (Zpu)2 = Z/ZB2 = (Zpu)1×ZB1/ZB2 = (Zpu)1× (VB1/VB2)2 x SB2/SB1 12 13 14 The Hong Kong Polytechnic University Per Unit Advantages • Normally we are dealing with numbers near unity rather than over a wide range. • Provides a more meaningful comparison of parameters of machines with different ratings. • As the per unit values of parameters of a machine of a given design normally falls within a certain range, a typical value can be used if such parameters are not provided. 15