SYSIEM OVERVIEW SYSTEM OVERVIEW The Lab-Volt Refrigeration Training System consists ofrefrigeration components, as wellas instrumentation and control components. These components are located on the front paneland at the rear bottom of the trainer, as Figures 1-1 and 1-2 show. (ln Figure 1-2, the protecting plate along the mountang base of the compressor/condenser assembly is not shown). . The refrigeration components include a compressor, a condenser, expansion devices (capillaries and a thermostatic expansion valve), an evaporator, and refrigerant copper tubing. . The instrumentation and control components permit the electrical control, monitoring, and protection of the refrigeration components. They include highand low-pressure gauges, a lhermostat, a solenoid valve, as well as pressure and temperature lransmitters. An electronic pressure controller keepsthe compressor operating at proper levels. ln addition, an electrical control panel, located at the bottom of the trainer front panel, provides electrical switches and control knobs to set the system under various configurations. Silk-screened on the righlhand side of this panel is a diagram that shows the electrical connections between the system components requiring an AC voltage to operate. Banana.jacks permit the measurement of this voltage at various points of the system for maintenance and troubleshooting purposes. The Refrigeration Training System is intended for use with the Heat, Ventilating, and Air Conditioning (LVHVAC) software, which permits the real{ime monitoring of lhe system variables. This requires that the computer used to run LVHVAC be connected to the Refrigeration Training System, via a USB connection. SYSTEM OVERVIEW Figure 1-1. Front view of the Refrigeration Training System. CIRGLED NUMBER CIRCLED COMPONENT NUMBER COMPONENT 1 Solenoid valve 10 Low (LP)- and high (HP)-pressure gauqes 2 Filter/drier 11 Pressure controller 3 Liquid indicator 12 4 Water collectinq trav Two-way hand-operated valves 13 Main POWER switch COMPRESSOR switch 5 14 EVAPOMTOR-FAN SPEED control knob with on/off switch 6 Expansion (metering) devices 15 CONDENSER-FAN SPEED control knob with on/off switch 7 Evaporator and its fan 16 HEAT LOAD switch 8 Cooling chamber 17 I Remote bulb thermostat 18 Electrical diagram with banana jacks USB port 19 Faults access panel Table 1-1 . Components located on the front panel (ref. to Figure 1-,1). SYSTEM OVERVIEW Figure1.2'ViewoftherearbottomoftheRefrigerationTrainingSystem. CIRCLED NUMBER COMPONENT 20 Suction line accumulator 21 High-pressure controller with manually-reset breaker 22 Refrigerant receiver 23 Compressor 24 Forced-air condenser (ref' to Figure Table .l -2. components located at the rear bottom of the trainer REFRIGEr.',J7o/n{rF'// Gs 1 -2)' SYSIEM OVERVIEW Technical Data Table 1-3 provides technical data on the Refrigeration Training System, at 120 VAC and 2201240 VAC. This table is also provided as a reference in Appendix A of the manual. COMPONENT TECHNICAL DATA 120 VAC 2201240 V AC Compressor Hermetic-type, 124 W (0.'167 hp), start capacitor, thermally protected, 1 15 VAC, 60 Hz, 18-A lockedrotor current (LRA), 2.9-A rated load current (RLA) Hermetic-type, 186 W (0.2s0 hp), sta( capacitor, thermally protected, 2001240 VAC, 50 Hz, 12.3-A locked-rotor current (LRA), 2.3-A rated load curent (RLA) Refrigerant R-134a R-134a Nominal charge 1.09 kg (2.4 lb) 1.09 kg (2.4 lb) oit Polyol esther Polyol esther Evaporator Forced-air coil with yariable-speed fan, enclosed in a cooling chamber, 120 VAC, 60 Hz, 0.58 A Forced-air coil with variable-speed fan, enclosed in a cooling chamber, 240 V, 50/60 Hz, 0.35 A Condenser Forced-air coil with variable-speed fan, 120 VAC, 60 Hz, 0.41 A Forced-air coil with variable-speed fan, 230 VAC, 50/60 Hz, 0.2 A Thermostat setpoint (typicat) 5"C (41'F) conlroller Cut-in (typicat) pressure Pressure settings 5'C (41'F) (1) 2.07 barg (30 psig) (1) 2.07 barg (30 psig) (cr1) Delay (ASd) Cut-out pressure (CO'1) Operating Lower point pressures (typical) Highest point 1 bar gauge (barg) = 1OO Null Null 0.69 barg ('10 psig) 1.4 barg (20 psig) (r) 7.6 barg (1'10 pstg; kpa gauge = 14.S psa (1) t1t 0.69 barg (10 psig) 1.4 barg (20 psig) (r) 7.6 barg (110 psig) gauge (psig) Table 1-3. Technicaldata on the Ref.igeration Training System. (rt (1) REF RI G ERATI O N F U N D AM ENTALS Energy Energy is the ability to do work. Energy exists in two forms, potential and kinetic: . Potential energy is energy a body possesses due to its position or particular physical or chemical state. . Kinetic energy is energy a body possesses due to its motion. Depending on the work to be done, energy can be described as thermal. mechanical, electrical, etc. Energy is measured in different units, such as . . metric or S.l. units of joules (J). Since the joule is a relatively small unit, the kilojoule (kJ) is used more often. imperialunits of British thermal units (Btu)in thecontextof refrigeration systems. The relationship between the above units is as follows: 1000J=1kJ=0.949Btu Temperature Temperature is a measure oflhe average kinetic energy ofthe particles that make up a body. The greater the kinetic energy of the Particles is, the higher the temperature of the body will be. Thermal Energy and its Transfer Whenever two bodies of different temperatures are broughl together, the particles of the two bodies will collide due to their random motion. The particles of the hotter body, which have greater kinetic energy, will be slowed down by the collisions, while the slower particles of the cooler body will get faster. As a result ofthese collisions, thermalenergy from the hotter body will be transferred to the cooler body. This will cause the temperature of the hotter body to decrease and the temperature of the cooler body to increase. This phenomena is referred to as thermal energy transfer (or heat transfer). Thermal energy transfer, if left to itself, will continue until the particles of the two bodies have equal amounts of thermal energy. When this condition occurs, the tvvo bodies have equal amounls ofthermal energy. The two bodies have attained equal temperatures and are said to be in thermal equilibrium. REF RI G E RATI O N F U N D AM ENTA LS There are three mechanisms by which lhermal energy transfer occurs, which are conduction, convection, and radiation. . Conduction: thermal energy is transferred by direct contact between the particles ofa Single body, or between the particles of two (or more) bodies in good thermal contact with each other. . Convection: thermal energy is transferred between the particles of a fluid. Convection can be natural or forced. Natural convection causes the heated fluid to become lighter and rise up into a cooler, denser region. Forced convection is the forced circulation of a fluid by a mechanical device such as a fan or pump. . Radiation: thermal energy is transferred through the effects of electromagnetic radiation. For example, the effect of radiation from lhe sun warming your face while the surrounding air is relatively cool. Basic Principles of Refrigeration Systems The main function of a refrigeration system is to remove thermal energy (heat) from a place and transfer it to another place. All refrigeration systems follow these basic principles: 1. Thermal energy, when lost or gained by a fluid (a liquid or a gas), normally causes the temperature of the fluid to change. The gained or lost energy that causes a change in temperature is called sensible heat. 2. A change of state is said to occur when a fluid changes lo a gas or a liquid. When it changes from liquid to gas, the fluid absorbs thermal energy. When it changes from gas to liquid, the fluid loses thermal energy. 3. During a change of state, the thermal energy gained or lost by the fluid does not cause a change in the temperature ofthe fluid. This occurs because the gained or lost energy goes into changing only the potential energy of the fluid, not its kinetic energy. Consequently, the gained or lost energy is called latent heat. During a change of state, the temperature of the fluid is proportional to the saturation pressure of the fluid. 4. Metallic parts used in a refrigeration system are selected as a function of their thermal conductivity. As figure 2-1 shows, a refrigeration system contains four basic devices: - a compressor; a condenser; an expansion (metering) device: an evaporator. REF RIG ERATI O N F U N DAM ENTALS I I REFRIGERANT FLOW <:- / 7 LlaUlD LINE H(mNStOl{ (mETER|NG) DEVICE CONDENSER EVAPORATOR 4, &I THERMAL ENERGY SUCTION LINE SUPERHEATED VAPOR REFRIGERATED SMCE I COMPRESSOR HIGH.PRESSURE (GoNDENSTNG) SIDE LOW+RESSURE (cooLING) SIDE DARK I RED COLOR KEY LIGHT RED tt ll HIGH. HIGH. PRESSURE GAS PRESSURE LIOUID DARK BLUE I LOW- PRESSURE LIQUID LIGHT BLUE L__l LOWPRESSURE GAS Figure 2-1. The four basic components of a refrigeration system' The Refrigeration Cycle ln Figure 2-1, the compressor is the heart of the refrigeration system: it makes the refriglrant flow through the system. To do so, it creates, along with the expansion device, a difference in pressure between the low-pressure (cooling) and highpressure (condensing) sides of the system' As the refrigerant flows through the system, it gives up or absorbs thermal energy by changing from gas to liquid, and then returning from liquid to gas' - The compressor produces a hightemperature, high-pressure superheated vapor(') at its HP (discharge) side. (1)Avaporissaidtobesuperheatedwhenitstemperatureishigherthanthalnormallycorrespondingtoitscurrentpressure. lnthiscondition, the vapor is fully saturated. REFRI G ERATI O N TRAI N I NG SYSTEM REF RIGERATION F U N DAM ENTALS - This vapor enters the condenser and, as it flows through the tubing coils, gives up thermal energy until it turns into a high-pressure saturated liquid. Once it has lost all its latent heat(2), the liquid is said to be subcooled(3). - The subcooled liquid from the condenser then flows through the expansion device, where it is forced through a restriction or a small orifice. Due to its high resislance, the expansion device regulates the flow of refrigerant and causes a drop in the pressure of the refrigerant, thereby decreasing its boiling point accordingly. ThiS causes part ofthe liquid to turn into vapor, and the temperature of the remaining liquid to decrease. - The mixture of liquid and vapor then flows through the evaporator, where it absorbs thermal energy until it becomes a saturated vapor. This absorption of thermal energy causes the temperature in the refrigerated space to decrease. The saturated vapor further absorbs thermal energy before it leaves the evaporator, turning into a surperheated vapor. This prevents liquid refrigerant from entering the compressor. - This low-temperature, low-pressure superheated vapor then goes to the LP (suction) side of the compressor, where it is compressed and turned into a high{emperature, high-pressure superheated vapor, to start a new refrigeration cycle. Note: Superheat does not necessaily mean that the refrigerant is hot. ln fact, superheated vapor can bequitecold. Similarly, subcooted does not necessarily mean that the refigerant is cold, as it can be quite warm. Pressure Measurements Pressure can be measured in different units. such as . . . metric units of bars (bar); S.l. units of kilopascats (kPa): imperial units of pounds-force per square inch (psi). The relationship between the above unils is as follows: 1 bar = 101.3 kPa = 14.7 psi To monitor a refrigeration cycle, pressure measurements must be performed along the system. This can be performed by using pressure gauges, which provide a direcl visual reading of the pressure on a dial. r2) Latent heat, es earlier menlioned, is lhe energy gained or lost during a change of slate that does not cause a change in the lemperature of the liquid or gas. l:) A liquid is said to be subcooled when its temperature is lower lhan that nofinally corresponding lo ils curent pressure. REF RIG ERATI O N F U N D AM ENTALS There are several types of pressure gauges, including: - absolute pressure gauges; gauge pressure gauges; compound pressure gauges. Ab sol ute Pressure Gauges The air pressure in outer space is 0 bar (0 psi or 0 kPa), because there is no air (perfect vacuum). When measured with respect to vacuum, pressure is called absolute pressure. Absolute pressure gauges, therefore, measure pressure with respecl to vacuum. At atmospheric pressure, they provide a non-null reading of about 1 bar absolute. (14.7 psia or 101.3 kPa absolute). Because of this, they are not commonly used in refrigeration systems. 'Atmospheric pressure at sea level. Gauge Pressure Gauges When measured with respect to atmospheric pressure, pressure is called gauge pressure. Gauge pressure gauges, therefore, provide a null reading of 0 bar gauge (barg) at atmospheric pressure (or 0 psig, 0 kPa gauge, etc., depending on how the gauge is graduated). Thus, atmospheric pressure is not included in the gauge pressure reading. REFRIG ERATIO N FUN DAM ENTALS Gauge pressure gauges are commonly used in the high-pressure section of refrigeration systems. A gauge pressure gauge is shown in Figure 2-2. ,,V,,,* AT OSPHERIC PRESSURE 0 barg , 0 p.lg - I bar abs. / 14.7 psla Figure 2-2. Gauge pressure gauge (barg/psig readings). As a summary, Table 2-1 indicates the relationship between absolute and gauge pressure measurements, in the metric, imperial, and S.l. systems of units. METRIC IMPERIAL s.t. 0 barg = 0 psig = 0 kPa gauge = 1 bar abs. = 14.7 psia = 101 .3 kPa abs. '1 = 14.7 barg psig = 101.3 kPa gauge Table 2-1. Relationship between gauge and absolute pressure measurements. REF RI G ERAN A N F U N DAM ENTALS Compoun d Pressure Gauges Compound pressure gauges can permit the measurement of either gauge or absolute pressures, as Figure 2-3 shows. The gauge can read pressures above atmospheric pressure, in barg, psig, or kPa gauge, depending on how it is graduated. - It can also read pressures below atmospheric pressure, in bar abs., psia, of mercury (mmHg), or inches of water (inHrO), for example, millimeters depending on how it is graduated. bars or / pors / ATUOSPHERIC PRESSURE (0barg/0pelg) io 40 so --_____--> \ barabs.orpeia \ Figure 2-3. Compound gauge. Temperature Measurements ln addition to pressure measurements, temperature measurements must be performed to monitor a refrigeration cycle. Temperature is measured on a temperature scale. There are fourtemperature scales whic'h are in use today: the Celsius scale, the Kelvin scale, the Fahrenheit scale, and the Rankine scale. Appendix C shows a comparison of the four temperature scales. ln refrigeration systems, the Celsius (S.1. and metric unit) or Fahrenheit (imperial unit) scales are normallY used. . The water boiling point corresponds to 100 on the Celsius scale, or 212 on the Fahrenheit scale. REFRI G ERAT I O N TRAI N I NG SYS TEM R EF RIG ERATI O N F U N DAM ENTA LS . The ice melting point corresponds to O on the Celsius scale, or 32 on the Fahrenheit scale. Based on these two points, temperature measuremenls can be converted from degrees Celsius to degrees Fahrenheit, and vice versa, as indicated inTable 2-2. S.I. OR METRIC FACTOR Degrees Celsius ('C) x '1.8 + 32 IMPERIAL = Degrees Fahrenheit ("F) FACTOR 32 x 0.55 S.I. OR METRIC Degrees Celsius ('C) Table 2-2. Temperature conversion. Refrigerants A refrigerant is a fluid that can absorb or give up thermal energy (sensible and latent heat). The amount of thermal energy gained or lost by a refrigerant under specific conditions is delermined by the type of the refrigerant. A property of refrigerants is that their boiling point at any given pressure is low, in comparison with other types of fluids. The refrigerant used in the Lab-Volt Refrigeration Training System is R-134a. This chlorine-free refrigeranl was designed to replace the R-12 refrigerant. lt has no effect on the ozone layer [Ozone Depletion Potential (OZp) = O], whiie its properties make it suitable for a variety of air-conditioning and refrigeration applications. REF RI G ERATI O N F U N D AM ENTALS Table 2-3liststhe temperature-pressure relationship forthe R-134a refrigerant under salurated condition. REFRIGERANT TEMPERATURE REFRIGERANT PRESSURE -17.6"C (0"F) 0.43 barg (6.3 psig) -14.9"C (5'F) 0.61 barg (8.8 psig) -12.1'C (10'F) 0.80 barg (1'1.6 psig) -6.6'C (20"F) 1 .24 barg (18.0 psig) 1.77 barg (25.6 psig) 1.1'C (30'F) 4.4"C (40'F) 2.38 barg (34.5 psig) 9.9'C (50'F) 3.10 barg (44.9 psig) 15.4'C (60'F) 3.92 barg (56.9 psig) 20.9"C (70'F) 4.88 barg (70.7 psig) 26.4'C (80'F) 5.96 barg (86.4 psig) 31.9"C (eo"F) 7.20 barg (104.2 psig) 37.4'C (100"F) 8 58 barg ('124.3 psig) 42.9"C (110'F) 10.13 barg (146.8 psig) 48.4'C (120"F) 1 53.9'C (130'F) 13.8 barg (13.8 psig) '1 .86 barg (171 .9 psig) "C (140"F) 15.91 barg (230.5 psig) 64.9"C (150" F) 18.24 bary (264.4 psig) 59.4 Table 2-3. R.1 34a temperature-pressure .elationship. The figures in Table 2-3 come from the reference chart shown in Figure 2-4. This chart, provided by the refrigerant's manufacturer, is usually provided on the form of a practical pocket guide. lt shows the temperature-pressure relationship for different types of refrigerants (e.g. R-22, R-123, R-134a, R-404A, etc.). As indicated on the chart, the boiling point of the R-134a is -26.'l "C (-14.9'F) at atmospheric pressure. Oil is used in refrigeration systems to lubricate and cool the compressor and compressor motor. Because of this, some amount of oil is present in the circulating refrigerant. REF RIG ERATI O N F U N DAM ENTALS @0D, Sur".."frigerants R.l3ila BOILING POINT AT AT OSPHERIC PRESSURE :l f1 i! ; gl g Figure 2-4. Refrigerant manufacturer's chart. REFRIGERATION COMPO,MMS FART 0 !ntroduction As mentioned earlier, a refrigeration system consists of refrigeration components, as well as instrumentation and control components. are'. a compressor, a condenser, an expansion device, and an evaporator. Additional refrigeration components are necessary to ensure the safe and efficient operation of the system, as well as its maintenance and troubleshooting, as Figure 3-1 shows: The basic refrigeration components - a liquid receiver; a filter/drier; a moisture/liquid indicator; a suction line accumulator; service valves. ln this job sheet, you will study the operation of the components highlighted in Figure 3-1 . You will study the operation of the other components in the next exercise. REFRTGERATTON COMPOTVEVTS (PART 0 EVAPORATOR sPAl{stoN ( ETERrl{c) DEVICES MANUAL VALVES MOISTURE LIOUID INDICATOR SUCTION FILTER DRIER <-- CO / LIOUID RECEIVER PRESSOR DISCHARGE CONDENSER Figure 3-1. Retrigeration components of the system. Compressor The compressor draws low-pressure superheated vapor from the cooling (Lp) side of the system at its suction inlet. lt compresses it to a high-pressure superheated vapor and expels it, through its discharge outlet, to the condensing (Hp) side of the system. Figure 3-2 shows the compressor used on the Refrigeration Training System. This compressor is of the reciprocating type. lt is said to be hermetic because it is totally encased in a sealed housing. The housing contains an electric motor, a crank shaft, a single cylinder, and lhe compressor. (Note that reciprocating compressors can have more than one cylinder). / REFRTGERATION COMPONEMS FART t) The rotation of the motor and crank shaft makes the cylinder piston move back and forth (reciprocate). For every compression stroke ofthe piston, a new volume of vapor is compressed and discharged at a high pressure. The motor is cooled by the transfer of thermal energy from the stator to the case (conduction), and by passing the returning vapor around the motor windings (forced convection) before it is compressed. A length of tubing (called process stub) connected to the case provides access to the refrigerant inside the compressor for servicing purposes, and can be resealed once lhe compressor is repaired. However, hermetic compressors are often replaced instead of repaired, because lhe compressor case is welded closed. The compressor needs a certain amount of oil for lubrication of its moving parts. sucnox col{PRESSOR TERIIINAL (hrLET) UtlE DISCHARGE (OUTLET} LINE COVER PROCESS TUBE (STUB) Figure 3.2. Reciprocating hermetic compressor of the Refrigeration Training System. C o m p re ssor Cha racleristlcs lmportant characteristics of a compressor are the volumetric flow rate, the volumetric efficiency, and the compression ratio. . The volumetric flow rate is the volume of gaseous refrigerant discharged by the compressor per unit of time. The formula for calculating the theoretical volumetric flow rate is as follows: Notei r/min stands for revolutions per minute. Metric units: volumetric flow rate(r"r.in) = Displacement(m3/r) . 5haft speeduT,niny REFRTGERATTON COMPONE TTS ?ART t) lmperial units: Volumetric flow ratelr3rmin; = Displacemen\fl3/i . speed,,rmin) "n.L When the compressor is of the reciprocating type, the volumetric flow rate is the volume displaced by the cylinder(s) on each piston stroke (distance traveled from bottom to top): n2 v.'4 rTu L.N.n where Vp = D= L= N= n= . Volumetric flow rate [m3/min or ft3/min)] Diameter of cylinder piston (m or ft) Length of the piston stroke (m or ft) Compressor speed (number of revolutions/min) Number of cylinder(s) The actual volumetric flow rate of the compressor is less than the theoretical volumetric flow rate because of internal pressure losses across the cylinder valves. The ratio of actual volumetric flow rate to theoretical volumetric flow rate is called the volumetric efficiency. lt is expressed as: Volumetric efficiency(%) Actual volumetric flow rate . 100 Theor. volumetric llow rate Small compressors used in domestic refrigeration syslems have volumetric efficiencies between 40 and 75o/o, with 50% being an average value. Larger commercial compressors have volumetric efficiencies between 50 and 80%, with 70% being an average value. The compression ratio (a pure number) indicates the efficiency of the compressor when using a particular refrigerant. lt is expressed as: Compression ratio = Absolute pressure on suction side Absolute pressure on discharge side For a single stage reciprocating compressor, the maximum allowable compressor ratio should be below 10. Table 3-1 lists typical compression ratios for different refrigerants under normal conditions of 30"C (86"F) condensing temperature and -15'C (5'F) evaporating lemperature. A value of 4.7 for refrigerant R-134a means that the absolute discharge pressure should be less than 4.7 times that of the absolute suction pressure. A higher ratio can result in a loss of efficiency and in possible damage to the compressor. "The compression rulio oI 4.7 for the R-134a refrigerant is for a condensing temperature of 54.4"C (130'F) and an evaporating temperature of 1.7'C (35"F). REFRTGERATTON COMPONENTS REFRIGERANT COMPRESSION RATIO R-22 4.16 R-134a* 4.70 R-717 4.94 R-718 6.95 R-744 3.10 R-764 5.61 qART t) Table 3-1. Maximum typical compression ratios for different refrigerants' Liquid Receiver The liquid receiver is normally placed downstream of the condenser. lt stores liquid refrigerant in excess and ensures a constant supply of liquid to the expansion device. The liquid receiver is used in refrigeration systems that use an expansion valve as the expansion (metering) device. The liquid receiver is unnecessary when the metering device is a capillary tube, because in that case, all the liquid refrigerant remains stored in the evaporator. Typically, the liquid receiver should be large enough to hold all the refrigerant in the system, because it will have to store all the refrigerant when the system is shut down for repair or servicing. Figure 3-3 shows a liquid receiver of the same type as the one installed on the Refrigeration Training System. The receiver is designed for vertical mounting. The receiver outlet is equipped with a Rotalock@valve used for initial refrigerant filling. ROTALOCK VALVE INLET (FROM CONDEI{SER OUTLET) OUTLET GO FTLTER DR|ER) ' Figure 3-3. Liquid receiver of the Refrigeration System. REFRTGERATTON COMPOTVEVTS PART t) FiltedDrier The filter/drier is normally installed downstream of the liquid receiver. The filter removes contaminanls such as dust, dirt, metal fillings, rust, from the flowing refrigerant to prevent clogging of the small restriction of the expansion device and damage to the compressor. The drier collects and holds moisture from the refrigerant. The arrow points in the direction of refrigerant flow (from inlet to ouflet). DIRECTION OF REFRIGERANT FLOW OUTLET Figure 3.4. Fitter/drier. Moisture/Liquid lndicator The moisture/liquid indicator is normally installed just upstream of the expansion (metering) device. lt consists of a sight glass and a sensing element that are used to check the charge and condition of the flowing liquid refrigerant, as Figure 3-5 shows. . . Bubbles seen through the sight glass can indicate a lack of refrigerant, a low discharge pressure, or some form of restriction in the liquid line. The color of the sensing element changes as the amount of moisture in the refrigerant changes. By matching the color of the element with the colors on the surrounding scale, the moisture content can be determined. With refrigerant R-134a, for example, dark blue is often used to indicate a dry system and a salmon color indicates a wet system. (However, the color selection is arbitrary and varies by manufacturer). REFRTGERATTON COMPONENTS qART t) COLOR SCALE SENSING ELEMENT Figure 3-5. Moisture/liquid indicator. Suction Line Accumulator The suction line accumulator is placed just upstream of the compressor. lt is used to prevent sudden surges of liquid refrigerant and oil from reaching the compressor. Refrigerant flood back to the compressor is a frequent cause of broken compressor valves, blown gaskets, and bent connecting rods. OUTLET FO COMPRESSOR) INLET (FROI EVAPORATOR) I I V LEAK+ROOF FUSIBLE PLUG METERING HOLE Figure 3-6. Suction line accumulator. REFRTGERATTON COMPOTVEVTS PART 0 or horizontal. Figure 3-6 shows a vertical accumulator. lt consists of a U-shaped tube with a small metering hole at the bottom, where small amounts of liquid refrigerant and oil are temporarily collected. The metering hole sends this mixture with the gaseous refrigerant, at a controlled rate, to the compressor. Since the liquid boils as it flows through the suction line, only the oil and refrigerant go to the compressor. Accumulators are either vertical It is very important that the inlet and outletofthe accumulator be correcfly connected an to prevent refrigerant and oil from becoming trapped. The selection of accumulator is based on the following factors: . . . . the pressure drop created by the accumulator, which must not be too high; the ability of the accumulalor lo return refrigerant at an adequate rate; the refrigerant holding capacity ofthe accumulator, which should not be less than 50% of the total system refrigerant capacity; the diameter, length, and orientation of the accumulator, which must suit your application. REFRIGERATION COMPOTVEMS qART tt) AND ENTHALPY DIAGRAM lntroduction ln the previous job sheet, you familiarized yourself with part of the refrigeration components that make up a basic refrigeration system. ln this job sheet, you will study the remainder of these components: the condenser, the expansion (metering) device, and the evaporator, as Figure 4-1 shows. EVAPORATOR EXPANSION (METERING) L.- AIUAL VALVES OISTURE LIOUID INDICATOR ^stsilil.?sFJ fi_ COMPRESSOR Figure 4-1. Refrigeration components of the system. R E F R I G ER AT I O N IRA'IV"VG SYSIEM FILTER DRIER / LIQUID RECEIVER ' REFRTGERATTON COMPOTVENTS AND ENTHALPY DIAGRAM ?ART t0 You willthen familiarize yourself with the pressure/enthalpy diagram of a refrigerant. You will learn how this diagram can be used to graphically represent the refrigeration cycle of a system. Condenser The condenser removes thermal energy from the superheated vapor discharged by the compressor, turning it into a saturated liquid. At the outlet of the condenser, this liquid, because it has lost all its latent energy, is said to be subcooted. The thermal energy removed by the condenser is transferred to the surrounding air, as long as the temperature of the air stays lower than the condensing temperature of the refrigerant. - As Figure 4-2 shows, a condenser consists of copper or aluminum tubing bent in a serpentine shape through which the refrigerant is conducted. - As the refrigerant flows through the tubing, thermal energy from the refrigerant transfers to the coils by forced convection and by conduction. THERMAL \lt FROtf, COMPRESSOR ENERGY REJECTED \t/ -* HIGH+RESSURE SUPERHEATED VAPOR &I** HIGH+RESSURE LIQUIO REFRIGERANT METER|NG DEvlcE / t\ +\ THERMAL ENERGY REJECTED Figure 4-2. Removal of thermal energy through the condenser tubing. Thermal energy from the tubing then transfers to the air flowing across the coils by convection, causing the temperature of the refrigerant to decrease. The convection is forced by a fan. The higher the rotation speed of the fan is, the faster the circulation of fresh air across the tubing and, therefore, the higher the rate of thermal energy transfer between the tubing and the air. Attached to the tubing is a web of thin metallic fins that increase the surface of thermal energy transfer between the tubing and the surrounding air, which further increases the rate of thermal energy transfer by forced convection. REFRIGERATTON COMPOTVEMS (PART tt) AND ENTHALPY DIAGRAM Figure 4-3 shows the condenser used on the Refrigeration Training System. (b) FRONTVTEW (A) REARVTEW Figure 4-3. Condenser used on the Refrigeration Training System. Expansion (Metering) Device The expansion device is connected between the condenser and the evaporator. lt makes the breakpoint between the high- and low-pressure sides of the system. The expansion device consists of a restriction or small orifice, through which the liquid refrigerant from the condenser is forced to flow. This creates a drop in the pressure of the refrigerant, thereby decreasing its boiling point accordingly. This in turn causes part of the liquid to turn into vapor, and the temperature of the remaining liquid to decrease. Due to its high resistance to the flow of refrigerant, the expansion device regulates (meters)this flow to the evaporator. The Refrigeration Training System has two types of expansion (metering) devices: . capillary tubes, which have a fixed restriction (orifice size); and . a thermostatic expansion valve, whose restriction can be adjusted. Capillary Tube A capillary tube is a simple length of tube having an inside diameter smaller than that of the main refrigerant line, as Figure 4-4 shows. Because of this, the capillary tube restricts and meters the liquid refrigerant. R EF RI G E RAT I O N TRAI N I NG S YSTEM REFRTGERATTON COMPOTVEVTS qART tD AND ENTHALPY DIAGRAM The friction and evaporation of the refrigerant that takes place within the tube are responsible for the pressure drop created across the capillary tube. The longer the capillary tube, the greater the created pressure drop, for any given diameter of the tube. The Refrigeration Training System comes with two capillary tubes, mounted on the front panel, just ahead ofthe evaporator. They both have the same inner diameter, but they are of differing lengths, allowing you to test the effect that this difference makes on the operation of the system. Since capillary tubes offer a flxed restriction to refrigerant flow, they do not have the ability of thermostatic expansion valves (TEV'S) to adapt to significant changes in the heat load. REFRIGERAI{T FLOW SiIALL.DIA*IETER J--l CaPTLLARY IUBTNG HIGH+RESSURE SUBCOOLED LIQUIO LOW+RESSURE FRO IXTURE TO EVAPORATOR COT{DENSER LARGEROIATETER REFRIGERA T TUBIiIG Figure 4-4. capillary tube op€ration. Thermostatic Expansion Valve (TEV) A thermostatic expansion valve (TEV) is a device that meters the flow rate of refrigerant to the evaporator by adapting it to any changes in the heat load. lt allows more refrigerant to flow when the evaporalor warms up and, conversely, it allows less refrigerant to flow when lhe evaporator cools down. A TEV consists of a diaphragm wlth a valve and seat, and a spring that is adjusted to obtain the desired level of superheat. As Figure 4-5 (a) shows, an external thermal bulb, partly filled with liquid refrigerant, senses the temperature of the refrigerant at the outlet of the evaporator. . . The difference between the temperature sensed by the bulb and that of the refrigerant in the evaporator results in a pressure difference that acts on the spring of the TEV to modify the TEV opening accordingly. Thus, when the sensed temperature becomes lower than the TEv-superheat setting, the TEV opening is decreased to reduce the flow of refrigerant entering the evaporator. Conversely, when the sensed temperature becomes higher than the TEV-superheat setting, the TEV opening is increased to increase the flow of refrigerant entering the evaporator. REFRTGERATTON COMPONEVTS (PART lt) AND ENTHALPY DIAGRAM . When the compressor is stopped, the valve is automatically closed to stop the flow of refrigerant to the evaporator. On the Refrigeration Training System, the TEV is mounted on the front panel of the trainer, just ahead of the cooling chamber. As Figure 4-5 (b)shows, the thermal bulb of the TEV is attached to the suction line of the system. REFRTGERATTON COMPONE TTS qART t0 AND ENTHALPY DIAGRAM THERMAL BULB LIOUID LINE (a) Thermostatic expansion valve construction _ - EVAPORATOR TO SUCTION LINE (b) Thermal bulb and capillary tube connected to evaporator inlet (trainer interval view) Figure 4-5. Thermostatic expansion valve. Evaporator The evaporator, located within the cooling chamber, turns the mixture of liquid and gas refrigerant coming out of the expansion device into a Iow-pressure superheated vapor. ln the process, the evaporator removes thermal energy from the cooling chamber. REFRTGERATTON COMPONETVTS PART il) AND ENTHALPY DIAGRAM An evaporator is basically 'Figure constructed the same as a condenser. As 4-6 shows, the evaporator consists of copper or aluminum tubing bent in a serpentine shape through which the refrigerant is conducted. COOLING CHAilIBER THERTIAL LOW+RESSURE ENERGY SUPERHEATED VAPOR ABSORBED \l / tl /l\ /l\ ""rt'rI * COMPRESSOR SUCTION EXPANSION DEVICE THERMAL ENERGY ABSORBED LOW+RESSURE TTIXTURE OF LIQUIDAND GAS Figure 4-6. Absorption of thermal energy through the evaporator tubing. As the refrigerant (mixture of gas and liquid) flows through the evaporator, thermal energy from the warmer air in the cooling chamber transfers to the refrigerant, through the evaporator tubing, by conduction, and through air recirculation by the forced convection created by the evaporator fan. The higher the rotation speed of the fan is, the faster the recirculation created by the fan and, therefore, the higher the rate of thermal energy transfer between the surrounding air and the refrigerant. Attached to the tubing is a web of thin metallic fins that increase the surface of thermal energy transfer between the tubing and the surrounding air, which further increases the rate of thermal energy transfer by forced convection. As it flows through the tubing of the evaporator, the refrigerant absorbs thermal energy (sensible heat). This increases its temperature to the boiling point. As it further absorbs thermal energy (latent heat), the refrigerant turns into dry vapor. The vapor then flows from the evaporator outlet to the suction side of the compressor. REF RtG ERATT O N CO M pOrVErVrS (p ART I 0 AND ENTHALPY DIAGRAM Figure 4-7 shows the evaporator of the Refrigeration Training System. This evaporator is of the forced-circulation type, and is enclosed, along with an electric fan, in a compact metal housing. AIR FLOW OUT ELECTRICAL wlRII{G TO HEAT LOAD (LIGHT BULBS) t-.o fl,.....*ro FRO EXPANSPN DEvlcE sucnoN Lll{E AccuItluLrAToR ff DRAII{ AIR FLOW II{ Figure 4-7. Evaporator used on the Refrigeration Training System. Enthalpy Table The amount ofthermalenergy per unit ofmass ofa refrigerant is called enthalpy (or heat content). Enthalpy can be measured in different units, such as . . metric or S.l. units of kilojoules per kilogram (kJ/kg); imperial units of British thermal units per pound-mass (Btu/lbm). As it flows through the evaporator to refrigerate the space, the refrigerant absorbs lhermal energy. Consequently, the enthalpy of the vapor at the ouflet of the evaporator is greater than that of the liquid al the inlet of the expansion device. The thermal energy absorbed per unit of mass of the refrigerant is called the refrigeration effect. Refrigerant manufacturers normally provide tables indicating the enthalpy of their refrigerants at various temperatures. Appendix D, for example, is a table indicating the enthalpy of saturated liquid and vapor for the R-134a refrigerant, at different temperalures. Take a look at this table. REFRIGERATION COMPOTVE TTS PART t0 AND ENTHALPY DIAGRAM Pressure-Enthal py Diagrams ln addition to tables, refrigerant manufacturers provide diagrams that show the enthalpy of their refrigerant as a function of absolute pressure. The pressure/enthalpy diagram of the R-134a, for example, is shown in Figures 4-8 (S.1. units) and 4-9 (imperial units). . The horizontal axis of the diagram is graduated in enthalpy units, while the vertical axis is graduated in absolute pressure units. . Two curves on the diagram indicate the changes in state between saturated vapor (right-hand curve)and saturated liquid (left-hand curve). . Between these two curves are horizontal lines of constant temperature. . A point representing the current refrigerant properties (pressure, enthalpy, and temperature) that is located on a horizontal line indicates that the refrigerant is a mixture of tiquid and vapor. lf this point is located on or to the right of the saturated vapor curve, the refrigerant is superheated. lf this point is located on or to the left of the saturated liquid curve, the refrigerant is subcooled. REFRIGERATTON COMPOTVEVTS AND ENTHALPY DIAGRAM ?ART t0 ABSOLUTE ABSOLUTE PRESSURE PRESSURE abe.) (b.r, ab..) (liP., 4n I 10 )ul'rrnt l l uolochcnr ie.rls HFC-134a I Pressure Enthalpy Diagram {SlUnits) 6 4 100 80 CRINCAL 60 AREA PRESSURE 40 20 SATUMTED 1 0.8 8 0.6 6 0.4 4 o.2 2 LIQUID LINE 0.1 SATURATED 0.08 VAPOR 0.06 uitE 0.04 0.02 ET{THALPY 0.01 100 250 =2l0kJ/kg I 300 =270kJrkg Figure 4-8. Pressure/enthalpy diagram for the R-134a (S.1. units). (kJ /ks) REFRIGERATTON COMPOTVEVTS (PART tt) AND ENTHALPY DIAGRAM ABSOLUTE PRESSURE I)trl)rutl 1000 l l^< la' sl lrrotircltcttt icals HFC-134a 800 ,,1 i t9 lt o ,o @ Pressure-Enthalpy Draqram (ErElish Units) 600 i CRMCAL I PRESSURE V, AREA z tcr ,\ 400 ili li5l El lr;l is.f'o,K I li ti o @ SATURATED LIOUID 100 LIE 80 60 40 SATURATED VAPOR LII{E 10 I 6 4 t I q Qqea o ooo o o 99oo o cioo I I I !'i 7P! :ss c5oci ra, c, (o .DO, W tttlti.t; 't I lUlll; ESdee o' o oro' o o oo oo ddc'o ;-8ot 1,4 ):-tt 'll,'t ENTHALPY (Btu / lbm) =25Bh!rlbm =53Btu/lbm Figure 4-9. Pressure/enthalpy diagram for the R-134a (imperial units). R EF RIG E RATI O N IRA'^"/VG SYSIE'}' REFRTGERATTON COMPONEVTS AND ENTHALPY DIAGRAM FART il) The pressure/enthalpy diagram ofa refrigerant can be used to determine the amount of thermal energy absorbed or removed by the refrigerant between two points. ln Figure 4-8, for example, a point indicates that at 50"C, saturated liquid refrigerant contains around 270 kJlkg of enthalpy, while another point indicates that at 7"C, saturated liquid refrigerant contains 210 kJ/kg of enthalpy; consequently, if a decrease in liquid temperature from 50"C to 7'C occurs through an evaporator, each kilogram of liquid entering the evaporator theoretically loses 60 kJ of thermal energy. However, the actual decrease in temperature produced under these conditions will be lower, due to the fact that latent thermal energy (latent heat of vaporization) is absorbed by the liquid changing to vapor in the evaporator. Graphical Representation of the Refrigeration Cycle The refrigeration cycle of a syslem can be represented by a simplification of the pressure-enthalpy diagram of the refrigerant it uses. The refrigerant cycle is a quadrilateral representing the refrigerant properties (pressure, temperature, enthalpy) at any point of the cycle. Figure 4-10, for example, shows a refrigeration cycle ofthe Lab-Volt Refrigeration Training System, displayed in the LVHVAC software. lcons indicate the typical equipment associated with each phase of the refrigeration cycle. . . The horizontalline O ts O corresponds to a change ofstate from vapor to liquid, as the refrigerant flows through the condenser. The temperature and absolute pressure of the refrigerant stay constant, but the enthalpy decreases from right to left. The pressure is at lhe compressor discharge (HP) level. At point O, high-pressure subcooled liquid reaches the inlet of the expansion device. . Between points O and g, the refrigerant flows through the expansion device: its absolute pressure drops, while its enthalpy stays conStant. Part ofthe liquid tums into vapor. . The horizontalline g O corresponds lo a change of state from liquid to vapor, as the refrigerant flows through lhe evaporator. The lemperature and absolute pressure of the refrigerant stay constant, but the enthalpy increases from left to right. The pressure is at the compressor suction (LP) level. . { At point O, low-pressure superheated vapor reaches the compressor suction inlet. . . Between points O and O, the compressor compresses the vapor, causing the absolute pressure of the refrigerant lo rise, and its enthalpy to also rise. At point O, high-pressure superheated vapor is expelled from the compressor discharge outlet. REFRTGERATTON COMPOTVENTS FART lt) AND ENTHALPY DIAGRAM . At point 6, the discharged vapor reaches the condenser inlet, and a new refrigeration cycle begins. PBs.,/Enth.b, tx.tqrd trr I Pressure/Enthalpy Diagram - R134a 10.0 ,: o It 6 o6 c, f o o c o , o l) {to HEAT OF couPREssloN 250 I I n5 3S hthalpv ftrke) I Figure 4-'10. Pressure/enthalpy diagram for the R-134a (metric units). NRE, Heat of Compression, and Coefficient of Performance lmportantcharacteristics of a refrigeration system are:the net refrigeration effect, the heat of compression, and the coefficient of performance. These properties can be determined graphically by using the system's refrigeration cycle (refer to Figure 4-10.) . The net refrigeration effect (N.R.E.) is the enthalpy removed by evaporation' lt is determined by drawing vertical lines downward from points @ and O. The REFRTGERATTON COMPOTVENTS AND ENTHALPY DIAGRAM d ?ART tD ifference on the enthalpy (horizontal) axis where the lines cross this axis is equal to the N.R.E. . . The heat of compression is the enthalpy added to the vapor, mainly by the work done by the compressor. lt is determined by drawing vertical lines downward from points O and 19. The difference on the enthalpy (horizontal) axis where the lines cross this axis is equal to the heat of compression. The coefficient of performance (COP) is a pure number indicating the efficiency ofthe refrigeration cycle. lt corresponds to the ratio ofthe enthalpy removed by evaporation (N.E.R.) to the enthalpy added to the vapor during the compressing phase. ln equalion form: Coefficient of performance Net refrigeration effect = Heat of compression (kJ,ks orBtu/bm) {kJ,rs or Bru/tbm) The higher the coefficient of performance, the better the efficiency of the system. The COP of refrigeration syslems varies according to the conditions under which they operate and the components constituting them. Therefore, this figure should not be used to compare the performance of two refrigeration systems that operate under differing conditions and/or that are not entirely made up of the same componenls. lnformation Job Sheet ,{ ELECTRICAL CONTROL OF REFRIGERATION SYSTEI'S lntroduction Refrigeration systems require electricity to operate. Consequently, it is important to know the basic principles of electricity and electrical control when working on these systems. Basic Principles Electricity is a form of energy used for lighting, heating, or providing control and power to do work. lt is produced by the flow of tiny particles of matter called electrons through a conducting material. Examples of conducting materials are iron, copper, and aluminum. Electrical components such as wires, lamps, solenoids, fan motors, thermostats, and electronic transmitters all use conducting material, and so allow electrons to pass through them. To produce a flow of electrons, the electrical components must be connected to a source of electromotive force that pushes the electrons through the components. This source may be either a generator or a battery. For example, Figure 5-1 shows a battery pushing electrons through electrical wires to energize the solenoid of a solenoid valve. As a result, a magnetic field is created around the solenoid. <- OOO 'T;""_ Figure 5-1. Simple electrical circuit. The electromotive force exerted by a source is called voltage. The magnitude of the voltage is measured in volts (V). The instrument used to measure voltage is called a voltmeter. There is always an opposition to the flow of electrons through an electrical component. This opposition to electron flow is called resistance. Resistance is measured in ohms (a). The instrument used to measure resistance is called an ohmmeter. ELECTRICAL CONTROL OF REFRIGERAT'ON SYSIEMS The result of electrons flowing through an electrical component is called current. The magnitude of the currenl is measured in amperes (A). One ampere is equal to the motion of6.24 x 1018 electrons past a cross section in 1 second. The instrument used to measure current is called an ammeter. Types of Electric Current Current flow through an electrical circuit may be one of two types: direct current or alternating cunent. . Direct current (DC) is the type of current produced by batteries and dc power supplies: the direction of the electric charges remains constant. Figure 5-2 (a) shows the symbol used to represent a DC power source in electrical diagrams. The current, l, flows by convention from the positive, or hot (+) terminal of the source lowards the negative, or common (-) terminal. I ^r T) l+ | ' \ ') \--l' t______* GBOUNDED WIRE = (CONNECTED TO EARTH) OV (a) DC power source (b) AC power sourco Figure 5-2. Symbols used to represent Dc and Ac power sources in electrical diagrams. . Alternating current (AC) is the type of current supplied to most houses and businesses: the electric charges varies in a cyclicai way, as opposed to DC current. Although DC current was the first type developed by Thomas Edison, AC cu rrent was proved to be much less expensive lo transmit over long distances by Serbian scientist Nikola Tesla, after what was called the "War of Currents", and is therefore more commonly used. Figure 5-2 (b) shows the symbols used to represent an AC power source in electrical diagrams. The flow of cunent in an AC circuit continuously reverses itself, flowing from the line (L, or hot side) terminal towards the neutral (N, or common) side, and vice-versa. However, the convention used is the same as for DC circuits: the current flows from the L side to the N side. ELECTRICAL CONTROL OF REFRIGERAT'O'V SYSTEMS For safety purposes, it is a common practice to connect the low-voltage side of an AC circuit to the earth. The voltage ofthe earth is 0 V. This practice is called grounding. As Figure 5-2 (b) shows, lhe wire connecting the N (low-voltage side) of the power source to the earth is called the grounded wire. The grounded wire is the green conductor in the US (or green-yellow conductor in Europe and Asia) of the line power cord. Ohm's Law Ohm's law states that the magnitude of the current flowing through an electrical component is equal to the voltage drop across lhe component divided by the resistance of the component: (^, Current... Voltaoe dropM Resistance (o) Reformulated to calculate the voltage drop: VoltagedropM = Resistance(o) x Currentlel Or to calculate the resistance: Resistance Voltage dropu) (o) Current 11y ln Figure 5-1 , for example, if the resistance of the solenoid is 10 O, and the current flowing through the solenoid is 2 A, the voltage drop across the solenoid will be 20 V. Electrical Power The capability of an electrical source lo move electrons through a circuit is called electrical power. DC circuits ln DC voltage circuits, electrical power is measured in watts (W). The amount of power generated by the electrical source is equal to the voltage supplied by the source multiplied by the current drawn by the circuit. ln equation form: Power* = Voltage M x Current 6y Part of the electrical power generated by the source is dissipated as heat by each component in the circuit, due to the resistance, or opposition to the current flow, of the components. Usually, most of the power is consumed by an electrical device called a load to perform a useful work such as producing light (lamp), providing rotary motion (motor), moving a plunger (solenoid), etc. The amount of power consumed by a load is equal to the voltage drop across this load, multiplied by the current flowing through it. (lt is also equal to the square of the REF RI G E RAT I O N T RA I N I N G S YSTE'U ELECTRICAL CONTROL OF REFRIGERAT'O'V SYSTEMS current flowing through the load, multiplied by the resistance ofthe load.) ln equation form: Consumed power@ = Voltagedrop, x Current 1n1 lf, for example, the voltage drop across the solenoid in Figure 5-1 is 10 V, and the current flowing through the solenoid is 2 A, then the power consumed by the solenoid will be 20 W. AC circuits ln AC voltage circuits, not all the power generated by the AC source goes to the load. Part of this power returns to the source, due to the inductive and capacitive components of the circuit. The power returning to the source is called reactive power. Reactive power is measured in volts-amperes (VAR). The power actually consumed by the load is equal to the product ofthe voltage and the current produced by the source, multiplied by a power factor. That portion of power is called true, or real power, and is measured in watts (W). The power factor is usually expressed as a pure number comprised between 0 and 1. lf, for example, the power factor is 0.7, then 70% of the power golng to the load will be consumed by the load. True power, in watts, can be measured by using a wattmeter. Closed and Open Circuits Figure 5-3 shows a simple AC circuit used to power a compressor motor. This circuit includes a 120-(2201240-\ V AC source, a POWER switch with normally open (NO) contacl, a pressure switch with normally closed (NC), contact and a compressor. The POWER switch allows an operator to make lhe cunent flow through the circuit or to stop it. The pressure swilch is used for safety: its NC contact allows the current to flow to the compressor as long as the circuit pressure stays within the pressure range allowed by the culin and cut-out settings of the pressure controller. . When the operator actuates the POWER switch [Figure 5-3 (a)1, this switch contact goes from open to closed. Since the pressure-switch contact is also closed, a complete conducting path is established, starting at the line (L) terminal of the source, through the switches and lhe compressor motor, back to the neutral (N) terminal of the source. As a result, the circuit is in the closed condition, and a currenl flows through the circuit. Consequently, the compressor motor is running. . When the operator returns the POWER switch to the normal (deactuated) state lFigure 5-3 (b)1, this switch contact goes from closed to open. This breaks the continuity of the conducting path at the POWER SWITCH. As a result, the circuit is in an open condition, and the current can no longer flow through the circuit. Consequently, the compressor motor is off. The same thing would occur if, for example, the pressure-switch contact were to go closed to open due to a circuit pressure reaching the cut-in or cut-out setting of lhe pressure controller. ELECTRICAL CONTROL OF REFRIG ERATION SYSTEMS POWER SWITCH IN NORMAL STATE PRESSURE SWITCH .^. 120 (230) VAC SOURCE ') '----/ (a) Closed \ COMPRESSOH MOTOR RUNNING circuit (b) Open circuit Figure 5-3. A simple AC circuit used to power a compressor motor. Measuring voltage, resistance, and current As previously mentioned, voltage is measured with a voltmeter, resistance is measured with an ohmmeter, and current is measured with an ammeter. These meters are available as separate units, but they are usually found combined in a single enclosure called a multimeter. Figure 5-4 shows how to measure voltage drop, current, and resistance in an AC circuit. . To measure the voltage drop across a component, connect a voltmeter or multimeter set to measure AC volts across the component terminals, as Figure 5-a (a) shows. Then turn on the source. . To measure the current flowing through a component, make sure the power source is turned off, then connect an ammeter or multimeter placed in ammeter mode in series with the component, as Figure 5-4 (b) shows. Then, turn on the power source. REF RIG ERATI O N TRAI N I NG S YSTEM E LECT RI CA L C O N T RO L O F REF RI G E RAT I O,il S YS TEI'S POWER SWITCH ACTUATED 3 VOLTMETER (a) Measuring voltage across the compressor 3 (b) Measuring current drawn by the compressor (c) Measuring compressor resistance Figure 54. Measuring voltage, resistance, and current in an AC circuit. ELECTRICAL CONTROL OF REFRIGERAT'O'V SYSTEMS Note: Serles means that all the current will llow through the component and the rest of the circuit when the power source is turned on. . To measure the resistance of a component, make sure the power source lS TURNED OFF, then disconnect the component from the circuit. This may require you to open one or more circuit connections. Connect an ohmmeter or multimeter placed in ohmmeter mode across the component terminals, as Figure 5-4 (c) shows. The ohmmeter has its own inlemal power source (battery) that supplies a current used to test the resistance of the component. Resistance measurements are often used to test the electrical continuity of a component. When the resistance of a component is very high or infinite (- Q), the component is said to be open. When the resistance is null, the component is said to be shorted (0 O). CAUTION! Never measure resistance in a circuitrYhile the power source is turned on. Failure to observe this rule may cause permanent damage to the meter' Series and Parallel Circuits A series circuit consists of electrical components that are all connected in series, as Figure 5-5 (a) shows: . . . The total resistance of the circuit, Rr, seen by the source, is equal to the sum of the resistances of each circuit component. The current flowing through the circuit is equal to the source voltage divided by the total resistance. Whenever a circuit component is open (of infinite resistance), no current will flow through the circuit. The source voltage will be present across the open component. A parallel circuit consists of electrical components that are parallel, or branch connected. Figure 5-5 (b) shows a simple parallel circuit: . . . The voltage across each branch is equal to the source voltage. Each branch has its own resistance. The total resistance, Rr, seen bythe source is equal to or lower than that of the branch of lowest resistance. The current flowing through the circuit is equal to the source voltage divided by the total, or equivalent circuit resistance. . Whenever a component in a branch is open, the source voltage will be present across the open component. ELECTRICAL CONTROL OF REFRI GERATIO N SYSTEMS v = 120 (230) VAC v = 120 (230) VAC r20 (230) vAc RI = 7.4A (a) Series circuit v = 120 (230) VAC v = 120 (230) VAC o2a "3[?EB. 120 (230) vAC a ^ CoMPRESSOR MOTOR soo ,31[" a3=75O Rr=5'8O (b) Parallel circuit Figure 5-5. Series and parallel circuits. Electrical control circuits are usually a combination of parallel and series branches, like the circuit used to control the Refrigeration Training system, shown in Figure 5-6: ' Each separate branch is used to control the turning on or turning off of a specific device independently. ' When the HEAT LOAD switch is actuated, the heat source becomes energized. However, this does not affect the solenoid valve, the evaporator fan, or the compressor motor in the other branches. ELECTRICAL CONTROL OF REFRIGERATION SYSTEMS . When the speed of the evaporator or condenser fan is varied, using the associated SPEED CONTROL knob, the voltage across the fan changes. However, the voltage across the heat source, solenoid valve, or compressor motor does not change. ELECTRONIC PRESSURE CONTROLLEB CoMPBESSOR Y --a/o--------------s4 THERMOSTAT COMPRESSOB SOLENOID VALVE EVAPOBATOR FAN CONDENSER FAN ll t-o/o--l COMPRESSOFI (22O t 24OVAC MOOELS ONLY) Figure 5-6. Electrical control panel of the Refrigeration Training System. Safety Rules Working on electrical equipment requires that you observe the necessary precautions, due to the possibility of electric shocks and/or damage to the equipment. Motor circuits, for example, may carry very high currents that can cause severe electric shocks. Even small currents may be dangerous under certain conditions. ln fact, the higher the circuit voltage, the higher the current that can flow through the human body and, therefore, the greater the possibility for a severe or fatal shock. The risk is increased when working in a wet room, or on components that are damp and not insulated. a. Never connect or disconnect electrical leads or components while the electrical power source is ON. b. When performing voltage or current measurements, the test leads or probes of the multimeter, voltmeter, or ammeter should have a protective covering over their ends to avoid the risk of short circuits and electric shocks, since these measurements require that the electrical power source be on. REF RI G ERAT I O N TRAI N I NG SYSTEM ELECTRICAL CONTROL OF REFRIGERATION SYSTEMS c. To increase your protection against electric shocks, always use screwdrivers, wrenches, or pliers that have insulated handles. Moreover, use rubber gloves, rubber-sole shoes, or rubber boots. d. Never leave any electrical lead unconnected. This may cause you to receive an electric shock when you touch the unconnected end of a lead while the electrical power source is on. This may also cause a short circuit to occur when the unconnected end of a lead touches a metal surface. e. All parts of a refrigeration system that can cause electric shocks must be properly grounded. For example, the ground (green wire of the electrical power cord) is normally connected to the ground wire of the motor compressor. / i PRESSURE AND TEMPERATURE CONTROL I N REF RI G E RAT'OA' S YS TE'}'S Pressure Controllers Pressure controllers are used in refrigeration systems for safety and pressure control. They sense pressure and switch the compressor on or off when the desired pressure (setpoint) is reached by breaking a conducting path in the electrical control circuitry. Pressure controllers come in two different types:the low-pressure type, and the highpressure type. . The low-pressure controller is found on the low-pressure (suction or LP) side ofthe refrigeration system. lt maintains the pressure on the LP side ofthe system below the level required to ensure efficient vaporization of the liquid refrigerant within the evaporator. At the same time, the low-pressure controller provides safety control against pulling vacuums, thereby preventing damage to the compressor. Moreover, by controlling the LP-side pressure, the low-pressure controller can also be used to control the temperature in the cooling chamber. This occurs bemuse changes in the evaporator temperature result in changes in lhe suction pressure. A thermostat maytherefore be unnecessarywhen the low-pressure controller starts and stops the compressor at the desired temperatures and pressures. Finally, the low-pressure controller can also prevenl the formation of ice on the evaporator. . The high-pressure controller is found on the high-pressure (discharge or HP) side of the refrigeration system. lt is used mainly for safety purposes: it prevenls the pressure on the HP side from becoming excessively high, thereby preventing rupture of components in the system. At the same time, the high-pressure controller maintains the pressure on lhe HP side to the level required to ensure efflcient condensation of the gaseous refrigerant within the condenser. a Bourdon tube as the pressure as the sensed pressure varies. expand or contracl These elements element. sensing When the pressure reaches the setpoint, an electrical contacl is mechanically closed or open to make or break a conducting path in the electrical control circuitry. Pressure controllers often use a bellows or PRESSURE AND TEMPERATURE CONTROL I N R E F R I G E RAI'O'V S YS TE'US The Electronic Pressure Controller of the Refrigeration Training System This controller, shown in Figure 6-1, can acl as either a low- or high-pressure controller, depending on lhe pressure range (user adjustable) and on the type of transducer used. As the figure shows, the controller mainly consists of a pressure transducer, and an LCD display with touchpad. - The pressure transducer produces a DC voltage proportional to the sensed pressure. The sensed pressure appears on the LCD display, in psig, and is refreshed every two seconds. - When the sensed pressure reaches the cut-in or cut-out setpoints, an internal relay with SPDT contacts becomes actuated, shifting its NO and NC contacts to their opposite state. A stalus LED on the front face of the controller indicates whether the relay is energized (LED is on) or deenergized (LED is off). - The 3-button touchpad allows the user to adjust the cut-in and cut-out setpoints. . . The Cut-ln setpoint (cil) sets the pressure (in psig)atwhich the intemalrelay of the controller is energized. The Cut-Out setpoint (col)sets the pressure (in psig) at which the internal relay of lhe controller is de-energized. lsecondary setpoints (ci2 and co2) are also available, but they are unused for the control of the Refrigeration Training System.l - Once cil and col have been adjusted, the conlroller automatically selects the necessary mode of control. The selected mode is indicated on the LCD display: ooen-Hioh ffi or ooen-towfl PRI ARY SETPOINTS TRANSDUCER SENSED (GAUGE) PRESSURE oPE .t-ow CONTROL ODE HARNESS Figu.e 6-'1. The elect.onic pressure controller of the Refrigeration Training System. PRESSURE AND TEMPERATURE CONTROL IN REFRIGERAT'O'V SYSTEMS The pressure controller has three selectable ranges for the cut-in and cut-out setpoints. This range is factory setto 0-100 psig (0-6.9 barg). Given this range and the type of pressure transducer used on the system, the controller will automatically select the Open-low mode and therefore acl as a low-pressure controller. Operation Figure 6-2 shows the operation of the controller when cil and 30 psig (2.'l barg) and 10 psig (0.69 barg), respectively. . . col are adjusted to The controller stops the compressor if the pressure on the LP side reaches the cut-out point of 10 psig (0.69 barg). The LP-side pressure is then allowed to rise to the cut-in point of 30 psig (2.1 barg): at that point, the controller restarts the compressor. . The LP-side pressure is then allowed to decrease lo the cutout point, and so on. 100 psig (6.9 barg) LED IS ON I 30 p6ig (2.1 ba€) I CUT-IN (cil) COMPRESSOH RESTARTS I SETPOINT DIFFEHENTIAL I LED ON OB OFF '10 psig (0.69 barg) CUT-OUT (col ) COMPRESSOR STOPS I LEO IS OFF 0 psis (0 bars) Figure 6.2. Operation ofthe electronic pressure controller in the open-low mode, with set to 30 psig (2.1 barg) and 10 psig (0.69 barg), respectively. cil and col Thermostal Controllers Temperature controllers, orthermostats, are used in refrigeration systems for safety and temperature control. They sense temperalure and switch a device, such as a compressor or a solenoid valve, on or off when the desired temperature (setpoint) is reached. PRESSURE AND TEMPERATURE CONTROL I N REF RI G E RAT'O'V SYS IEMS Figure 6-3, for example, shows a lhermostat ofthe fluid pressure type similar to that used on the Refrigeration Training System. The thermostat mainly consists of a thermal bulb, an SPDT switch, and a setpoint adjustmenl knob with dial. . The thermal bulb is used as the temperature sensing element. lt is linked to the thermostat via a capillary tube. The bulb is usually mounled on the evaporator side or in the cooling chamber. The bulb is filled with refrigerant, and is therefore sensitive to temperature changes. As the temperature of the refrigerant changes at the bulb, a bellows expands or contracts accordingly, acting on the SPDT switch, through a mechanical link. . The setpoint adjustment knob permits adjustment of the setpoint (desired temperalure in the chamber) on a calibrated dial. BULB ^DIFFERENTIAL RANGE } ADJUSTiIENT DI,AL AIUUST ENT SCALE -'z ELECTRICAL CONNECTIONS TO SPDT SIVTICH Figure 6-3. lnternal construction of a thermostat. Operation Assume that the NO contact ofthe thermostat SPDT switch is used. As long as the temperature sensed by the bulb is above the setpoint, the switch is actuated, causing its NO contact to be closed. This makes a conducting path in the electrical control circuit. Once the temperature has decreased lo the adjusted setpoint, the NO contact opens to break the conducting path in the electrical control circuit. The temperature in the cooling chamber then increases by a certain amount before lhe NO contacl closes again to re-make the eleclrical circuit. PRESSURE AND TEMPERATURE CONTROL I N REF RI G ERAT'O'V S YS TEMS The difference between the adjusted setpoint and the temperature at which the NO contact closes to re-make the conducting path is called the differential. A differential is required to prevent the NO contact from oscillating between the closed and open conditions when the temperature is around the setpoint. The differential is fixed on some models, while adjustable on others. The thermostat shown in Figure 6-3, for example, has an adjustable differential which can be set by sliding a lever along a scale plate. Solenoid Valves Solenoid valves are used in refrigeration systems to control the flow of liquid refrigerant to the evaporator. The solenoid valve is installed in the liquid line upstream of the expansion (metering) device. The intended purpose is to prevent liquid refrigerant from flowing to the evaporator when the desired temperature is reached. Solenoid valves are also used in multi-chamber systems to permit independent control of the temperature in each chamber. ln large refrigeration systems, they permit the control of several evaporator sections, as the heat load varies. Figure 6-4 shows a cross-section view of a direct-operated, two-way solenoid valve similar to that used on the Refrigeration Training System. The valve is fully closed (non-passing)when the solenoid is de-energized, and fully open (passing) when the solenoid is energized. . When a current flows through the solenoid, a plunger is attracted toward the center ofthe valve solenoid. This shifts the valve to the open condition, allowing the refrigerant to flow to the evaporator. A minimum pressure drop is required across the valve lo keep the valve in the open condition. . When the current flow to the solenoid is intenupted, the solenoid becomes deenergized. This causes a spring and the weight of the plunger to force lhe valve stem against the valve seat, shifting the valve in the closed condition. This stops the flow of refrigerant to the evaporator. PRESSURE AND TEMPERATURE CONTROL I N REF RI G E RAT'O'V S YSTEMS --'r-- INLET RE OVABLE SOLENOIO PLUNGER VALVE SEAT CUTdWAY VIEW Figure 6-4. cross-section view of a direct.operated, two.way solenoid valve. A thermostat normally controls the flow of current to the valve solenoid to keep the temperature in the cooling chamber around the setpoint, as Figure 6-5 shows. . . When the adlusted setpoint is lower than the temperature sensed in the cooling chamber, the thermostat NO contacl is closed to energize the solenoid of the valve. The valve is in the open condition, allowing the refrigerant to flow to the evaporator in order to produce a decrease in the temperature of the cooling chamber. When the temperature in the cooling chamber has decreased to the thermostat setpoint, the thermostat NO contact opens to de-energize the solenoid valve. This shifts the valve to the closed condition, thereby stopping the flow of refrigerant to lhe evaporalor. The compressor will continue to run until the low-pressure setpoint of the pressure controller is reached, causing the compressor to slop. PRESSURE AND TEMPERATURE CONTROL IN REFRIGERAT'ON SYSIEMS { THERTIIAL BULB /'---------\ _ _ _ rHERirosrAr LOW+RESSURE CONTROLLER 6)l I I , I 1#) V I Figure 6-5. Schematic diagram of a simple refrigeration system. THERMOSTATIC EXPANSION VALVE ADJUSTMENT lntroduction Figure 7-'l shows a refrigeration cycle for the R134-a. Each point used to plot this quadrilateral (in red) represents the refrigerant properties (pressure, temperature, enthalpy) at a speciflc point of the cycle. . . Points of the quadrilateral that are located on horizontal lines (lines of constant temperature) indicate that the refrigerant is a mixture of liquid and vapor. Points ofthe quadrilateral that are located on the saturated vapor curve indicate that the refrigerant is at the boiling point, and that it has completely turned into vapor. Points ofthe quadrilateralthat are located to the right ofthe saturated vaporcurve indicate that thermal energy has been added to the vapor: the vapor is said to be superheated. . Points of the quadrilateral that are located on the saturated liquid curve indicate that the refrigerant is at the condensing point, and that it has completely turned into liquid. Points of the quadrilateral that are located to the left of the saturated liquid curve indicate that thermal energy has been removed from the liquid: the liquid is said to be subcooled. THERMOSTATIC EXPANSION VALVE ADJUSTMENT AASOLUTE PRESSURE ( Pa,.b..) I 10 )ul\rnt urrrrthtntic.rls 4 i I 2 i li I o, ,. r<) o I o' I t 1r I o:. o gF ><)\ U, ?.,'?e 1R rl fi \i/. ,I fl i\ it t\ i, 4cn, cn LIOUID SUBCOOLING -:8o 70',--+ VAPOR SUPERHEATING lit ii li 1l'l,l iil,u I q ,!I (ol (o ,'.\ iij i; t' -o' o l--o ,' 6' rl 1t+ rfi-l,*t:t-t-lrrtt 7r'f"- 1i /l &o' . I I' ,o ,.o r-$ a: '-r4Ll:lil'L^ili tll I 0.06 v J- /l ll 0.04 il 3: +ilti[!lJ]i : l:: :::3:/: ffi tlt l. o q3 q oooo ci --l-L r,Q ;- trrooal.,olJ.rok)ro o ci; ,: ?-rt:, ; rr, ot. 1t! rrt 0.01 t. ti('Ir: .-{l"'c J! o.2 o.o2 ilfli I :li o oro o c, I t; k Ilsi E. ii, I ? I II 0.8 0.08 I I o I t": 0.6 c) ll ti Ol li li (or0 i 1 ",1' R I 0. ,i s. Pressure-Enthalpy Diagram (Sl Units) 6 0.4 .l' / l HFC-134a I 1 I jl t8 & o ffTfi-fifi 400 450 Figure 7-1. Vapor superheating and liquid subcooling. THERMOSTATIC EXPANSION VALVE ADJUSTMENT Superheat The saturated vapor normally becomes superheated nearthe end ofthe evaporator. Before it leaves the evaporator, the superheated vapor continues to absorb thermal energy: this ensures that liquid refrigerantwill not enterthe compressor suction inlet. The superheat of the superheated vapor at a given point is equal to the difference between the temperature of the vapor and the temperature at which the vapor becomes saturated, for a given pressure. The superheat of the vapor is usually measured by using the steps below (refer to Figure 7 -2\: . . . Firsl, measure the pressure of the superheated vapor at the evaporator outlet (that is, where the sensing bulb ofthe thermostatic expansion valve is located); Then, find the saturation temperature corresponding to the measured pressure on a pressure-temperature (P/T) chart; Finally, calculate the difference between the saluration temperature and the temperature of the superheated vapor at the evaporator outlet. The result corresponds to the superheat. €.6rc (22.D 1.6 lztt OUILET 0'c (32'R 1.6 barg (22.4 Fls) b.rg D,,tgl -5.6'C (22"F) 1.6 barg 122.1 rigl 5.6.C (ro.F) SUPERHEAT Figure 7.2. The pressure/temperature (PT) method of measuring sup€rheat. Since there is usually no pressure port at the evaporator outlet, the pressure is often measured at the compressor service valve instead. Therefore, in commercial units, an additional value of 0.14 to 0.2barg (2or 3 psig) is usually added to the pressure measured at lhe service valve, to take account of the pressure drop that occurs in the refrigerant line between the evaporator outlet and the compressor suction inlet. REFRIG ERATIO N TRAIN ING SYSTEM THERMOSTATIC EXPANSION VALVE ADJUSTMENT The measured superheat gives an indication of the efficiency of the evaporator coil. For example, a high superheat can indicate thal the evaporator is operating very inefficiently, because the refrigerant is vaporizing too quickly in the evaporator coil. A high superheat can result in poor heat transfer in the cooling chamber. On the other hand, a negative superheat value indicates that the refrigerant is not completely vaporized at the evaporator outlet, which can cause liquid refrigerant to reach the compressor suction inlet, and in turn can cause premature failure of the compressor. Table 7-1 indicates the recommended superheat for high-, medium-, and lowtemperalure refrigeration systems. REFRIGERATION SYSTEM RECOMMENDED SUPERHEAT High-temperature [-1.1 "C (30'F) and above in the evaporatorl Between 5.5 and 6.6" ('10 and 12'F) approximately -1.1 "C Medium{emperature [between -1 6'C and (0'F and 30'F in the evaporator)l Between 2.8 and 5.5'C (5 and 10 F) approximately Low-temperature [below -16"C (0"F) in the evaporalor)l Between 1.1 and 2.8'C (2 and 5"F) approximately Table 7-1. Recommended superheat for high-, medium-, and low-temperature refrigeration systems. ln many refrigeration systems, the superheat can be adiusted by turning a screw on the thermostatic expansion valve (TEV). Turning the screw in the clockwise direction will increase the superheat. Turning the screw in the counterclockwise direction will decrease the superheat. Before measuring the superheat, the system should be allowed to run for around 15 minutes. Subcooling Subcooling is the removal of thermal energy from the refrigerant, after it has completely turned into a saturated liquid. Subcooling takes place in the condenser, and is dependent upon proper airflow in lhe condenser, room temperature, and refrigerant pressure in the condenser. Subcooling increases the efficiency of some refrigeration systems, the liquid refrigeranl being cooled before it passes the metering device. One method of subcooling a refrigerant is to run the liquid line and suction line together. This method also serves to superheat the cool refrigerant in the suction line to ensure that no liquid refrigerant enters the compressor suction inlet. TH ERM OSTA TIC EXPA'VS'ON VALVE ADJ U STM ENT To measure subcooling, use the steps below: . . . . . Measure the pressure of the liquid refrigerant as it leaves the condenser. Once the pressure of the liquid refrigerant has been measured at the condenser, add 0.14 to 0.2 barg (2 or 3 psig) to the measured pressure to take account of the friction in the liquid line and of the vertical rise. Find the saturation temperature corresponding to the resulting pressure on a pressure-temperature chart. Convert the resulting pressure into the corresponding saturation temperature by using a pressure-temperature (PT) chart. Finally, find the difference (in absolute value) between the saturation temperature and the temperature at the evaporator inlet. The result corresponds to the subcooling value. RE F RI G ERATI O N TRAI N I NG SYSTEM I *rr*,ur*n ,o* r*o,*,*n "rrrr* | 6 TROUBLESHOOTING lntroduction A fault in any part of a refrigeration system will usually show up as an unsatisfactory temperature or operating condition. Each system has its own characteristics. Consequently, lhe more familiar you are with the system, the quicker and easier it is to find faults and correct the problem. To keep track ofthe system conditions, ensure maximum performance, and detect suspect or faulty operation, maintenance technicians perform regular inspections of the equipment, where they mark down operation data in an inspection report. lmportant conditions to know about a refrigeration system are . . the temperature of the evaporator and condenser during the operation cycle; the discharge pressure and suction pressure during the operation cycle. The operating conditions are lhen compared to the designed conditions in the system when a fault is suspected. A drastic variation in a system's temperature or pressure from the designed conditions can indicate system malfunction. The two basic principles employed as a guide for troubleshooting a fault are . . to observe the symptoms of the fault; asking questions concerning the malfunction. These two principles are used by system manufaclurers to build troubleshooting charts. These charts, which take the form of tables or diagrams, consist of step-bystep observations and questions used to approach the problem and locate the fault in a logical and systematic way. Electrical Faults Electrical faults are often the cause of refrigeration syslem breakdown. Many electrical faults occur as a result of poor or corroded connections on components. Some electrical faults are more obvious than others. These faults can usually be found and repaired before any damage is caused, either to the system or chamber being refrigerated. Examples of electrical faults are listed below. R EF RIG E RAT I O N IRA'IV,,VG SYSIEM TROUBLESHOOTING Evaporator Fan and Associated Circuit Failure A fault occurring in the evaporator fan and associaled circuit is usually indicated by the fan blade not turning and decreased cooling in the cooling chamber. Since less heat is absorbed in the evaporator, the suction pressure decreases from its normal pressure. This drastically reduces the efficiency of the system. Condenser Fan and Associated Cicuit Failure A fault occurring in the condenser fan and associaled circuit can also be indicated by the fan blade not turning. This creates a higher head pressure since less heat is being removed from the condenser coil. This will cause a greater pressure differential, resulting in a warm cooling area. Compressor Motor and Associated Circuit Failure A fault occurring in the compressor motor can appear in the following ways: the compressor will not run, which will result in no cooling and equal pressures on bolh sides of the system. The fault may be the result of an open winding on the compressor motor. Before replacing the compressor, you should first check for external troubles, including the power connections, lhe internal thermostat, the wire terminals, the compressor relay, and lhe compressor capacitor (if any). Once these components have been found operational, the compressor motor is probably at fault. Pressure Controller and Associated Circuit Failure A typical fault in a high- or low-pressure controller can be a broken or loose connection. This type offault can be indicated in several ways. The compressorwill not run, and the system will therefore not operate. Troubleshooting Electrical Control Circuits Troubleshooting the electrical control section of a refrigeration system requires that a systematic troubleshooting procedure be used, in orderto Iimit the numberoftests to be performed. The best way to start is to observe the symptoms in order to relate the problem to a specific section of the circuitry. The choice of which circuit section to analyze should not be done on a random basis, as industrial control circuits can be quite complex. The two most often used methods of troubleshooting are the voltmeter method and the ohmmeter method. TROUBLESHOOTING Voltmeter Method of Troubleshooting The voltmeter method consists in tracing the voltage along a circuit branch or path suspected to be defective, using a voltmeter. Basically, this method requires that the voltage supplied to each component in the branch or path be checked to detect an abnormal voltage level. Figure B-1 shows this method for the electrical control circuit of the training system, when a problem is suspected in the branch of the solenoid valve. ELECTRONIC PRESSURE CONTROLLER POWER swrrcH (cLosED) :' CoMPRESSOH Y ----<v--o----------<: o ^z 120 (230) VAC THERMOSTAT SPEED CONTROL = 120 (230) VAC_ SPEED CONTBOL 120 (230) VAC < 120 (230) VAC TP4 TP3 < 120 (230) vAc TP6 120 (230) vAC , ,, , HEAT SOURCE EVAPOBATOR FAN VALVE CONOENSER FAN I I I I | 1l tll rl L-Ol-O--l1r ''utttt COMPHESSOR (22O tt - tt -tttt"' -t--t'ttt I 24OVAC MODELS ONLY) VOLTMETER Figure 8-1. The voltmeter method of troubleshooting a circuit branch. The AC source voltage is checked first. With the POWER switch set to ON (closed), the positive (+) terminal of the voltmeter is connected to TP1 , while the common (COM) terminal of the voltmeter is connected to TP2 (circuit COMMON). The voltmeter should indicate the source voltage. lf not, the source itself, the POWER switch, or the leads connecting these components may be damaged or open. lf the supply voltage is correct, the + terminal of the voltmeter is moved to measure the voltage applied to the solenoid of the valve (TP3), while the COM terminal is left connected to the common side of the solenoid valve (TP2). Assuming that the sensed temperature is above the thermostat setpoint, the thermostat switch should be closed, so that the voltmeter should indicate the REF RIG ERATI O N TRAI N I NG SYSTEM TROUBLESHOOTING source voltage approximately. lf not, the thermostat, the solenoid valve, or the leads connecting these components (between TP1 and TP2 ) may be damaged or open (infinite resistance). It is important to understand, here, that voltage tracing along a branch or conducting path requires that allthe components in that path be in the closed condition to permit the flow of current through the path. The same method could be used, for example, to test the branch ofthe evaporator fan. ln that case, a voltage divider is created at the SPEED CONTROL knob. Consequently, if there is no fault in this branch, the voltage between TP4 and TP2 will be less than the source vollage, and will be 0 V if the knob switch is set to OFF. Ohmmeter Method of Troubleshooting The ohmmeter method, also called continuity test method, consists in testing the completeness of a path for the purpose of detecting a broken conneclion leading to a component or a fault in the component. lt requires that the resistance of each componenl and lead in the path be measured with an ohmmeter to detect an open, or infinite-resistance condition. When the path to test has two or more branches in parallel, the ohmmeter method requires that each branch be tested separately by disconnecting the branches from each other. Figure 8-2, for example, shows ohmmeter lesting of the heat source of the training system. The test leads ofthe ohmmeter are connected across the heat source. Since the branch of the heat source has other branches in parallel, this branch must be opened otherwise the measured resistance will correspond to the equivalent resistance of all the other branches, not that of the heat source only. This condition can easily be fulfilled just by opening the HEAT LOAD switch. To lest the solenoid valve, the same principle applies: the thermostat NO contact must be open, that is, lhe temperature in the cooling chamber must be lowerthan the thermostat setpoint, in order for the branch of the valve to be isolated from lhe others. Otherwise, you will have to open the branch leading to the valve (at TP3), as the figure shows. The same principle applies to test the continuity of the evaporator fan, compressor, or condenser fan. TROUBLESHOOTING ELECTRONIC PRESSURE CONTROLLER POWER SWITCH COMPBESSOR (oPEN) THERMOSTAT 120 (230) VAC , , I ! I HEAT SOURCE EVAPOFATOR FAN tP2 LEGEND: I or=* cncur 1z- BRANCH I OHMMETER Figure 8-2. The ohmmeter method of testing the continuity of a branch or component. RE F RI G ERATI O N TRAI N I NG SYSTE'U Appendix ff TechnicalData on the Refrigeration Training System COMPONENT TECHNICAL OATA 120 VAC 220t240 Compressor Hermetic-type, 124 W (0.167 hp), start capacitor, thermally protected, 115 VAC, 60 Hz, 18-A lockedrotor cunent (LRA), 2.9-A rated load current (RLA) Hermetic-type, 186 W (0.250 hp), start capacitor, thermally protected, 200i240 VAC, 50 Hz, 12.3-A locked-rotor current (LRA), 2.3-A rated load current (RLA) Refrigerant R-134a R-134a Nominal charge 1.09 ks (2.4 lb) 1.09 ks (2.4 lb) oil Polyol esther Polyol esther Evaporator Forced-air coil with variable-speed fan, enclosed in a cooling chamber, 120 VAC, 60 Hz, 0.58 A Forced-air coil with variable-speed fan, enclosed in a cooling chamber, 240 VAC, 50/60 Hz, 0.35 A Condenser Forced-air coilwith variable-speed fan, 120 VAC, 60 HZ, 0.41 A Forced-air coil with variable-speed fan, 230 VAC, 50i60 Hz, 0.2 A Thermostat setpoint (typical) 5"C (41'F) 5'C (41"F) controller Cut-in (typical) pressure Pressure settings 2.07 barg (30 psig) (1) V AC 2.07 barg (30 psig) (1) (cl1) Delay (ASd) Cut-out Null Null 0.69 barg (10 psig) 1r) 0.69 barg (10 psig) (1) pressure (CO'l ) Operating Lower point 1.4 barg (20 psig) 1r) 1.4 barg (20 psig) (1r pressures (typical) Highest point ri) 1 bargauge 7.6 barg (1'10 psig) (1r 7.6 barg ('110 psig) (barg)= 100 kPa gauge = 14.5 psagauge (psig) Table A-'1. Technical data on the Refrigeration Training System. 11)