POWER SYSTEMS 2 – EE521 ASSIGNMENT 1 DUE DATE: 5th APRIL, 2023. QUESTION ONE In the three-phase system shown in Figure 1, phase a is on no load and phases b and c are short circuited to ground. The following currents are given: πΌπ = 91.65∠160.9°, πΌπ = 60.00∠90°. Find the symmetrical components of current πΌπ0 , πΌπ1 , and πΌπ2 . Figure 1 QUESTION TWO A generator is connected through a transformer to a synchronous motor. The subtransient reactances of generator and motor are 0.15 and 0.35 pu respectively. The leakage reactance of the transformer is 0.1 pu. All the reactances are calculated on a common base. A three-phase fault occurs at the terminals of the motor when the terminal voltage of the generator is 0.9 pu. The output current of generator is 1 pu and 0.8 pf leading. Find the subtransient current in pu in the fault, generator and motor. Use the terminal voltage of generator as a reference vector. QUESTION THREE The one-line diagram of a three-bus power system is shown in Figure 2. Each generator is represented by an emf behind the transient reactance. All reactances are expressed in per unit on a common 100 MVA base. The generators are running on no load at their rated voltage. Determine the fault current, bus voltages and line currents during fault when a balanced threephase fault with fault impedance j0.16 per unit occurs on bus 2. Figure 2. 1 QUESTION FOUR The system shown in Figure 3 shows an existing plant consisting of a generator 100 MVA, 30 kV with 20% subtransient reactance and a generator of 50 MVA, 30 kV with 10% subtransient reactance, connected in parallel to a 30 kV bus bar. The 30 kV bus bar feeds a transmission line via the circuit breaker C which is rated at 1250 MVA. A grid supply is connected to the station bus bar through a 500 MVA, 400/30 kV transformer with 20% reactance. Determine the reactance of a current limiting reactor X in ohm to be connected between the grid system and the existing bus bar such that the short-circuit MVA of the breaker C does not exceed the breaker capacity. Figure 3. QUESTION FIVE The reactance data for the power system shown in Figure 4 in per unit on a common base is as follows: Figure 4. Obtain the Thevenin sequence impedances for the fault at bus 1 and calculate the fault current in per unit for the following faults: (a) A three three-phase fault at buss 1. (b) A single line-to-ground fault at bus 1. (c) A line-to-line fault at bus 1. (d) A double line-to-ground fault at bus 1. QUESTION SIX A generator having a solidly grounded neutral and rated 50 MVA, 30 kV has π1 = 0.25 ππ’, π2 = 0.15 ππ’, and π0 = 0.05 ππ’. What reactance must be placed in the generator neutral to limit the fault current for a double line-to-ground fault to that of a three-phase fault? 2 QUESTION SEVEN Figure 5 shows three 15 MVA, 30 kV synchronous generators A, B and C connected through three reactors to a common bus bar. The neutral of generator C is grounded via reactor of 2.0 Ω and the neutrals of generators A and B are solidly grounded. The generator data and reactance of the reactors are tabulated below. A line-to-ground fault occurs on phase a of the common bus bar. Determine the fault current in phase a. Neglect prefault currents and assume generators are operating at their rated voltage. Figure 5. 3