Setting IDB Parameters, R10 to R12, 06A, 06B OPERATING INSTRUCS Copyright © Ericsson AB 2007 – All Rights Reserved Disclaimer No part of this document may be reproduced in any form without the written permission of the copyright owner. The contents of this document are subject to revision without notice due to continued progress in methodology, design and manufacturing. Ericsson shall have no liability for any error or damage of any kind resulting from the use of this document. 2/1543-LZA 701 0001 Uen H 2007-05-01 Contents Contents 1 Introduction 1 1.1 Work Process for Setting the IDB Parameters 1 1.2 Revision Information 3 2 Prerequisites 5 3 Creating IDB 7 4 Connecting the OMT 9 5 Reading the IDB 11 6 Opening IDB from File 13 7 Defining Present RUs 15 8 Defining Alarm Inputs (External Alarms) 17 9 Defining ALNA/TMA Parameters 21 10 Defining Loss and Checking the Total Gain Value 23 11 Defining Battery Backup Time Test Parameters 25 12 Defining Battery Parameters 27 13 Defining Climate 31 14 Defining Delay 33 15 Defining GPS Parameters 35 16 Defining Hardware Information 37 17 Defining PCM 39 17.1 Transmission Interface E1, 75 39 17.2 Transmission Interface E1, 120 39 17.3 Transmission Interface T1, 100 41 17.4 Defining LBO Parameters as Short Haul 43 17.5 Defining LBO Parameters as Long Haul Manually 45 17.6 Defining LBO Parameters as Long Haul Automatically 47 2/1543-LZA 701 0001 Uen H 2007-05-01 Setting IDB Parameters, R10 to R12, 06A, 06B 17.7 Defining LBO Parameters when Transmission Characteristics are Unknown 50 18 Defining RBS Identity 51 19 Defining System Voltage 53 20 Defining TEI 55 21 Defining TNOM 57 22 Defining VSWR Limits 59 23 Saving IDB 63 24 Installing IDB 65 2/1543-LZA 701 0001 Uen H 2007-05-01 Introduction 1 Introduction This document describes how to set the IDB parameter, excluding TG synchronization parameters, using the Operation and Maintenance Terminal (OMT). The document is for use with BTS R10, R11, R12, 06A or 06B software. For more detailed information on the use of the OMT, for example, when to define a parameter, why the parameter should be set, which values are valid, and the consequences of not setting a parameter, see OMT User’s Manual, EN/LZN 720 0001. Note: For OMT Version R31 and later, the OMT parameters are also included as on-line help. The IDB parameters can be loaded to the RBS in two ways: 1.1 • By connecting the OMT to the DXU and installing the IDB • By inserting a flash card with the new IDB into the DXU Work Process for Setting the IDB Parameters This section describes the work process for setting the IDB parameters. Information about which procedures that must be followed is given in the Site Installation Documentation. 2/1543-LZA 701 0001 Uen H 2007-05-01 1 Setting IDB Parameters, R10 to R12, 06A, 06B Start Connecting the OMT Creating IDB Reading IDB Opening IDB from File Defining Present RUs Defining Alarm Inlets (External Alarms) Defining ALNA/TMA Parameters Defining Loss and Checking the Total Gain Value Defining Battery Backup Time Test Parameters Defining Battery Parameters Defining Climate Defining Delay A P014549C Figure 1 2 Work Process for Setting the IDB Parameters (Part 1 of 2) 2/1543-LZA 701 0001 Uen H 2007-05-01 Introduction A Defining GPS Parameters Defining Hardware Information Defining PCM Defining RBS Identity Defining System Voltage Defining TEI Defining TNOM Defining VSWR Limits Saving IDB Installing IDB P014550D Figure 2 1.2 Work Process for Setting the IDB Parameters (Part 2 of 2) Revision Information Rev. H • VSWR section updated with note that this does not apply to RBS 2116 or RBS 2216 • Word "SID” changed to Site Installation Documentation 2/1543-LZA 701 0001 Uen H 2007-05-01 3 Setting IDB Parameters, R10 to R12, 06A, 06B 4 2/1543-LZA 701 0001 Uen H 2007-05-01 Prerequisites 2 Prerequisites Before setting the IDB parameters, ensure the following: • The test record from the document Verifying Antenna Systems is available • The RBS Synchronization Manual is available, if TG synchronization is used, see: • Documentation and tools necessary for the work must be available. OMT The OMT kit contains the OMT software and user’s manual, as well as a cable (RPM 517 54/3) used to connect the OMT to the RBS in the field. Various kit versions are available depending on the configuration of the RBS and its software. Contact your Ericsson market unit representative for more information. Documentation The following documents are referenced in this document, ensure that they are available: • Site Installation Documentation • OMT User’s Manual, EN/LZN 720 0001 • RBS SW Update, 13/1541-LZA 701 0001 • Verifying Antenna Systems, 1/1532-LZA 701 0001. • Setting TG Synchronization Parameters, for specific RBS. Only if TG synchronization is used. • GPS Synchronization in RBS *, RBS specific document. Only if GPS parameters shall be set. 2/1543-LZA 701 0001 Uen H 2007-05-01 5 Setting IDB Parameters, R10 to R12, 06A, 06B 6 2/1543-LZA 701 0001 Uen H 2007-05-01 Creating IDB 3 Creating IDB This section describes how to define the configuration setup in the OMT. Note: If the flash card has to be removed when creating the IDB, see the document RBS SW Update. Defining Transmission Interface 1. Start the OMT. 2. On the RBS 2000 menu, click Disconnect to logically disconnect the OMT from the RBS. 3. On the Configuration menu, click Create IDB to open the Create IDB window. 4. Select transmission interface. Defining Cabinet Setup 5. To add cabinets to the Cabinet Setup box, click New to open the Define Setup for Cabinet window. 6. In the Cabinet Type box, select the cabinet type. 7. In the Power System box, select power system. 8. In the Climate System box, select climate system (if applicable). 9. Click OK. Defining Antenna Sector Setup 10. To add antenna sectors to the Antenna Sector Setup box, click New to open the Antenna Systems for Sector window. 11. In the Antenna Systems for Sector window, click New to open the Define Antenna System window. 12. In the Frequency box, select the frequency used. 13. In the CDU type box, select the CDU type used. 14. In the duplexer type box, select the duplexer type used (if applicable). 15. In the TMA box, select one of the following: 2/1543-LZA 701 0001 Uen H 2007-05-01 7 Setting IDB Parameters, R10 to R12, 06A, 06B BTS R10 or R11 software, and RBS not equipped with dTRU: Yes if TMAs without external power have been installed. No if externally-powered TMAs have been installed BTS R10 software and RBS equipped with dTRU: Yes if TMAs have been installed. BTS R12, 06A or 06B software: Yes if TMAs have been installed. No if TMAs have not been installed No if TMAs have not been installed 16. In the TX combining box, select the applicable combining type. 17. In the RX antenna sharing box, select if RX antenna sharing will be used (if applicable). 18. In the RX diversity box, select the applicable RX diversity type. 19. Click OK in the Define Antenna System window to confirm. 20. If additional antenna systems will be defined in the sector, then repeat the steps above. 21. In the Antenna Systems for Sector window, verify that the correct parameters have been entered. Click OK. 22. Define the remaining antenna sectors as described above. 23. Click OK in the Create IDB window, when all antenna sectors are defined. Selecting the Final Configuration 24. In the Final Configuration Selection window, select the site cell configuration (SCC). 25. Verify that the correct parameters have been entered. Click OK. 26. In the OMT dialogue box asking ‘‘Do you want to reuse data in the previous configuration?’’, click one of the following: Yes (for IDB modification only) No (for configuration of entirely new IDB) 27. In the OMT dialogue box asking ‘‘Do you really want to overwrite the IDB data in the OMT?’’, click Yes. 8 2/1543-LZA 701 0001 Uen H 2007-05-01 Connecting the OMT 4 Connecting the OMT This section describes how to physically connect the OMT to the RBS. 1. Connect the OMT cable from the PC serial port 1 to the OMT port on the DXU. 2. Start the OMT. 2/1543-LZA 701 0001 Uen H 2007-05-01 9 Setting IDB Parameters, R10 to R12, 06A, 06B 10 2/1543-LZA 701 0001 Uen H 2007-05-01 Reading the IDB 5 Reading the IDB This section describes how to read the IDB to check that the values of the IDB parameters are correct. 1. On the RBS 2000 menu, click Connect. 2. On the Configuration menu, click Read IDB. 3. On the Configuration menu, click Display and Information to enter the Display Information window. 4. Select IDB and click Run. Check the parameters in the table below. Table 1 Reading and Checking IDB Check that the Following Parameters are Correct: OK Transmission interface Cabinet configuration(s) Antenna sector configuration(s) 5. Close the Display Information window. 6. Check the present RUs by choosing View in the Menu and select Cabinet. 7. If the IDB parameters in the table above need to be set, then see Section 3 on page 7. If the IDB parameters above are correct, set the applicable site-specific IDB parameters from the list below. Follow the procedures defined in the following sub-sections: 2/1543-LZA 701 0001 Uen H 2007-05-01 11 Setting IDB Parameters, R10 to R12, 06A, 06B • Alarm inlets (external alarms) • ALNA/TMA parameters • Defining loss and checking the total gain value • Battery backup time test parameters • Battery parameters • Climate • Delay • GPS Parameters • Hardware Information • Transmission (PCM) parameters • RBS Identity • System voltage • TEI value • TNOM parameters • VSWR alarm limits 8. On the RBS 2000 menu, select Disconnect to disconnect the OMT logically from the RBS. 12 2/1543-LZA 701 0001 Uen H 2007-05-01 Opening IDB from File 6 Opening IDB from File This section describes how to open a saved IDB file from disk. 1. Start the OMT. 2. In the Configuration menu, select Open IDB. 3. Locate and select the saved IDB file to be opened. 4. Click Open in the Open IDB dialog box to confirm. 2/1543-LZA 701 0001 Uen H 2007-05-01 13 Setting IDB Parameters, R10 to R12, 06A, 06B 14 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Present RUs 7 Defining Present RUs This section describes how to check and, if necessary, define the RUs which are present (or not present) in the RBS. To avoid Hardware and IDB inconsistency, the RBS must know which RUs should be present. By setting RUs to Present/Not present, the RBS recognizes which RUs can be used (present) and which are not present. The following RUs are not automatically updated and must therefore be defined: • BFU • DC/DC converter • EPC bus • FCU • PSU • TMA CM The following RUs are automatically marked as present when the RU is detected: Note: The RUs cannot be removed when in traffic. • TRU • DRU • RRU Define the RUs Present/Not present as follows: 1. If the OMT is not logically disconnected from the RBS, then click Disconnect on the RBS 2000 menu. 2. On the Configuration menu, click Define and Present RUs to open the Define Present RUs window. 3. If necessary, move the RUs in the configuration used to the Present box by selecting the RU to be moved and clicking the ← key (or double-clicking the RUs to be moved). If RUs Not Present in the configuration are in the Present box, then move them to the Not Present box by clicking the → key. 2/1543-LZA 701 0001 Uen H 2007-05-01 15 Setting IDB Parameters, R10 to R12, 06A, 06B 4. Click OK when finished. 16 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Alarm Inputs (External Alarms) 8 Defining Alarm Inputs (External Alarms) This section describes how to define the external alarms, if applicable. To enable the supervision of devices connected to the external alarm interface of the RBS, several parameters need to be set. For an overview of the available parameter settings for external alarms, see table below. Table 2 External Alarm Settings Parameter Valid Values Default Description Type • Closing Closing Specifies how an external device indicates an alarm and must be set to enable correct supervision. A fault is indicated by closing or breaking the sensor loop. 0 Uniquely identifies the external alarm equipment. The value is sent in external alarm reports to the O&M centre. Level 1 Indicates the severity of the external alarm. The operator determines the values to be used for the alarms. An empty character string The operator can add a description of the external alarm. The value is sent to the O&M centre in external alarm reports. • Breaking • 0–9 ID • A–F Severity • Level 1 • Level 2 Comment Character string with up to 62 characters. Valid character s are: 0..9 A..Z space ! # $ % &’()*+,-. /: ;<=>? _ Note: Some DC/DC converters are factory-installed to alarm input 16 in the external alarm unit. Input 16 is therefore unavailable in such cases. Note: If a smoke detector is factory-installed it is hard-coded to alarm input 2 and 3 in the external alarm unit. Inputs 2 and 3 are therefore unavailable in such cases. 1. On the Configuration menu, click Define and Alarm Inlets to open the Define Alarm Inlets window. 2/1543-LZA 701 0001 Uen H 2007-05-01 17 Setting IDB Parameters, R10 to R12, 06A, 06B 2. In the Alarm Inlet Information window, select an unused alarm inlet. 3. In the Inlet Usage box, select ‘‘External Alarm’’. 4. In the Type box, define the alarm type as ‘‘Closing’’ (when there is an alarm, the alarm cable closes) or ‘‘Breaking’’ (when there is an alarm, the alarm cable breaks). 5. In the ID box, select an alarm inlet number. 6. In the Severity box, set the severity level of the alarm. 7. Add a comment in the Comment box, if required. 8. Click Apply after defining the alarm. 9. Repeat steps 2 to 8 to define the remaining alarms. 10. Click OK when all alarms have been defined. If the RBS contains an internal factory-installed DC/DC converter, see document RBS Product Description. The alarm output of the DC/DC converter is connected to the alarm inlets. Define the DC/DC converter as an external alarm with the following parameters: Alarm Inlet 0/16 Inlet Usage External Alarm Type Breaking ID F Severity 1 Comment DC/DC CONVERTER FAILURE If the RBS contains a smoke detector, the alarm outputs of the smoke detector is connected to the alarm inlets. Define the smoke detector alarms as external alarms with the following parameters: 18 Alarm Inlet 0/2 Inlet Usage External Alarm Type Breaking ID 1 Severity 1 Comment FIRE 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Alarm Inputs (External Alarms) Alarm Inlet 0/3 Inlet Usage External Alarm Type Breaking ID 2 Severity 2 Comment SMOKE DETECTOR FAILURE 2/1543-LZA 701 0001 Uen H 2007-05-01 19 Setting IDB Parameters, R10 to R12, 06A, 06B 20 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining ALNA/TMA Parameters 9 Defining ALNA/TMA Parameters This section describes how to set the ALNA/TMA parameters (if applicable). The TMA parameters must be set when a TMA is connected and the characteristics of the TMA are different from the default values in the IDB files in the OMT. If any parameter is missing, the default values should be used. 1. On the Configuration menu, click Define and ALNA/TMA. 2. In the Define ALNA/TMA window, select the appropriate TMA and click Run. 3. Set the parameters listed below. See the installation instructions for the TMA. Table 3 ALNA/TMA Parameters Parameter Valid Values Default Description TMA type • GSM • GSM 800/900/ 1800/1900 (Ericsson standard GSM TMA) Determines the TMA type, how the TMA is to be supervised, how faults are to be reported, and whether the TMA has bypass functionality. This parameter must be changed when a TMA type other than the GSM (Ericsson standard GSM TMA) or compatible TMA is used. Available TMA types also depend on the configuration • TDMA • GSM bypass • TDMA bypass • Externally powered TX group delay 0 – 1, 000 ns 22 ns Specifies the TX signal delay in the TMA. TMA TX group delay is part of the total TX path delay in the RBS, which is needed to synchronize the TX burst transmission of all TRXs. If the default value differs from the value in the TMA equipment specification, then it must be updated. RX group delay 0 – 1, 000 ns 101 ns TMA RX group delay is part of the total RX path delay in the RBS which is needed to calibrate the timing in the TRX receiver. If the default value differs from the value in the TMA equipment specification, then it must be updated. 2/1543-LZA 701 0001 Uen H 2007-05-01 21 Setting IDB Parameters, R10 to R12, 06A, 06B Table 3 ALNA/TMA Parameters Parameter Loss (1) Valid Values Default Description 24 dB – +24 dB GSM 800/900/ 1800: 12 dB The TMA loss is part of the total RX path loss in the RBS, which is needed to calibrate the TRX and thereby optimize the RF performance of the RBS. If the TMA loss parameter differs from the default values it must be updated. GSM 1900: 10.934 dB RX frequency range (MHz) 824.2 – 848.8 MHz (GSM 800) 880.2 – 914.8 MHz (GSM 900) Specifies the supported RX frequency range for the TMA. 1710.2 – 1784.8 MHz (GSM 1800) 1850.2 – 1909.8 MHz (GSM (2) 1900) Current supervision limits 0 – 500 mA GSM 800/900: 33 mA (low) 237 mA (high) GSM 1800/1900: 33 mA (low) Specifies the limits of TMA current supervision. One type of fault is set if the supply current to the TMA is constantly above the high limit or below the low limit. Another type of fault is set if the TMA repeatedly alters the supply current to above or below the high limit. The parameters must be updated if the current supervision limits for the TMA differ from the default values. 150 mA (high) (1) TMA loss = 0TMA gain (2) Valid values = default values Note: If externally powered TMAs have been configured, then the current supervision limits cannot be set. 4. Click OK when all parameters are set. 5. Repeat steps 2 to 4 for all TMAs. Close the Define ALNA/TMA window. 22 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Loss and Checking the Total Gain Value 10 Defining Loss and Checking the Total Gain Value This section describes how to define the loss of the RX feeders and to check that the total gain value is within limits. Defining Loss To sustain uplink RX sensitivity and optimize the RF performance of the RBS, it is essential to define the correct value for the loss parameter. That includes losses from jumper cables, combiners, splitters and RF filters of an RX feeder chain with attached TMA. For a TMA configuration, this means that if the feeder loss value, measured and calculated in the document Verifying Antenna Systems, differs from the default loss value of 3.996 dB, then the loss parameter must be updated to the feeder loss value. See test record from Verifying Antenna Systems. For non-TMA configurations, the loss parameter is kept to the default value of 0 dB. The default value may be kept in this case, because the feeder loss is not part of the total RX path loss in this type of configuration. This is how to define loss: 1. On the Configuration menu, click Define and Loss to open the Define Loss window. 2. Select the appropriate RX feeder (for example FEED_TXA_RXA 0), and click Run. 3. In the Define Loss window, enter the Total Feeder Attenuation from the test record for Antenna System Tests and click OK. 4. Repeat steps 2 to 3 for each RX feeder. 5. Close the Define Loss window, when finished. Checking the Total Gain Value The purpose of this check is to ensure that the Total Gain value is within system performance limits. 1. Calculate the Total Gain value using the following formula: Total Gain = TMA Gain - Total Feeder Attenuation 2. Compare the calculated value to the Max. and Min. values in the table below. 2/1543-LZA 701 0001 Uen H 2007-05-01 23 Setting IDB Parameters, R10 to R12, 06A, 06B Gain TOTmin ≤ Total Gain ≤ Gain TOTmax See example below. Table 4 System Performance Limits GSM System Gain TOT (dB) Min. Max. GSM 800/900 7 10 GSM 1800/1900 7 12 The values in the table guarantee the specified sensitivity performance, and that the GSM specification is met. The following example illustrates what is said above. Preconditions: GSM 1800/1900 CDU-G TMA Gain = 12 dB Total Feeder Attenuation = 4 dB Total Gain = TMA Gain - Total Feeder Attenuation = = 12 – 4 = 8 dB Result: 7 ≤ 8 ≤ 12 Example 1 24 Checking that the Total Gain Value is Within Limits 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Battery Backup Time Test Parameters 11 Defining Battery Backup Time Test Parameters This section describes how to define the test parameters for the battery backup time test. This test is used to check the battery backup time continuously, without the need for personnel on site. The result is saved in the RBS, and can be read by site personnel using the OMT. If enabled, the test forces the RBS run on battery backup until it reaches a system voltage level (22.5 – 23.5 V) set by the user, where the test will stop. The time run on battery backup is measured and compared with the expected backup time defined for the batteries. The test is considered successful if the measured backup time exceeds the expected backup time. Table 5 Battery Backup Time Test Parameters Parameter Valid Values Default Description Enable test • Yes (enabled) No (disabled) Enables the battery backup time test. • No (disabled) Start date YY-MM-DD YY-MM-DD The battery backup time test is a cyclic function and it is therefore necessary to state a start date for the test. Start time 00:00 – 23:59 00:00 (hh:mm) (hh:mm) Defines the time of day when the battery backup time test is performed. Voltage level 22.5 – 23.5 V to stop the test 2/1543-LZA 701 0001 Uen H 2007-05-01 23.0 V Defines the voltage level that stops the test. The test must be stopped before the batteries are fully discharged. A low level means a longer test period, which gives a more reliable test result. However, the batteries will be more discharged, so more time must elapse before a mains failure can be handled. A high level results in a greater difference between the measured backup time and the true backup time. The disconnect level main parameter defines the true backup time, and the voltage level that stops the test must be at least 0.3 V higher than the disconnect level. 25 Setting IDB Parameters, R10 to R12, 06A, 06B Table 5 Battery Backup Time Test Parameters Parameter Valid Values Default Description Test interval 60 – 365 days 182 days Defines the number of days between the battery backup time test. The battery can wear out prematurely if the test is done too frequently. Also note that repeating a test with different load profiles gives a more accurate test result. Expected backup time 00:00 – 23:59 00:00 (hh:mm) (hh:mm) The expected backup time is compared with the measured backup time. If it is longer than the measured time, then the test is passed. The RBS does not know how much backup time to expect. To find out whether the backup time is long enough it is necessary to enter the expected backup time, which is the same as the backup time planned for the site. Note that the default value is 00:00 (no backup time), which means that the test will always be successful. 1. On the Configuration menu, click Define and Battery Backup Time Test Parameters to open the Define Battery Backup Time Test Parameters window. 2. Enable the test by clicking Yes. 3. Enter the start date and time for the test, using the up/down arrows. 4. Enter the system voltage at which the Battery backup Test is to stop. 5. Enter the test interval (in days). 6. Enter the expected backup time for the batteries, using the up/down arrows. 7. Click OK when finished. 26 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Battery Parameters 12 Defining Battery Parameters This section describes how to define the battery parameters. The settings of the battery parameters define the performance of the batteries and their lifetime. The setting of the Alarm Raise limit defines the operating temperatures of the batteries. This parameter must not be changed for Ericsson batteries supplied with the RBS. System voltage (define using the Define System Voltage function) must be adapted to the chosen charging algorithm. This is particularly important when using fixed float charging voltages. 1. On the Configuration menu, click Define and Battery Parameters to open the Define Battery Parameters window. 2. Select the object to be defined, and click Run. 3. Enter the parameters listed in the table below: Table 6 Battery Parameters Parameter Valid values Default Description Disconnect level prioritized 20.0 – 23.8 V 20.8 V Defines the level at which the batteries are disconnected. Prioritized supply is (1) intended for TM equipment . This is the low voltage disconnect function, which is designed to protect the battery from being overdischarged. Disconnect level main 20.2 – 24.0 V 21.0 V Sets the voltage at which the RBS is disconnected from the batteries and indicates how long the battery backup (2) time will be. Reconnect level 24.0 – 26.0 V 25.5 V Defines the system voltage at which prioritized supply and batteries are to be reconnected. Alarm raise limit 55 – 60C 55C Defines the temperature at which a high temperature alarm is raised. Batteries are disconnected when the temperature reaches 5 above the alarm raise limit, and are reconnected when the temperature drops 5 below the alarm raise limit. In service date YYYY-MM-DD YYYY-MM-DD Used by the battery log function and when set indicates that new batteries have been installed. 2/1543-LZA 701 0001 Uen H 2007-05-01 27 Setting IDB Parameters, R10 to R12, 06A, 06B Table 6 Battery Parameters Parameter Valid values Charging mode Default Description Temperature-c ompensated Defines the type of charging algorithm to use. The battery type and configuration affect the parameter setting. Temperaturecompensated Temperature-compensated charging is recommended for lead–acid batteries. It uses high float-charging voltages at low battery temperature and low float-charging voltages at high temperatures. It can be used when using shared batteries if the battery temperature sensors are located in the same measuring positions. Fixed voltage Fixed voltage, also called fixed float-charging voltage, is recommended when using non-lead batteries or shared batteries Temperaturecompensated + Boost event See the description of temperaturecompensated above. Boost charging is used to obtain optimal charging since low charging could reduce battery life. Boost event is initiated when the battery voltage drops below 22.5 V. Temperaturecompensated, no Boost time The only difference between boost event and boost time is the start time. Boost time is initiated at midnight when the start date occurs and then at regular intervals. Temperaturecompensated + Boost event/time Boost event/time is initiated both when the battery voltage drops below 22.5 V and at midnight when the start date occurs and then at regular intervals. See descriptions of boost time and boost event above. Perform first boost charging YYYY-MM-DD YYYY-MM-DD The parameter defines the first time that boost time charging is initiated. Days between boost charging 30 – 365 days 175 days The parameter defines the time interval where charging is conducted, when boost time is selected as the charging mode. Boost charge time, boot time 1 – 24 h 6h The parameter defines the duration of the charging when boost time charging is used. Boost charge time, boost event 1 – 24 h 6h The parameter defines the duration of charging when boost event charging is used. (1) Prioritized supply is supported only for the BFU-02, BFU-04, BFU-21, or BFU-22. (2) A low-level result in a long backup time for the RBS, but a short backup time for the TM equipment. 28 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Battery Parameters 4. Click OK, when all parameters are set. 5. Repeat steps 2 to 4 for remaining objects to be defined. 6. Click Close when finished. 2/1543-LZA 701 0001 Uen H 2007-05-01 29 Setting IDB Parameters, R10 to R12, 06A, 06B 30 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Climate 13 Defining Climate This section describes how to define the climate unit. This parameter gives input to the climate unit about how it is to function. 1. On the Configuration menu, click Define and Climate to open the Define Climate window. 2. Select the appropriate climate name. 3. Click OK when finished. 2/1543-LZA 701 0001 Uen H 2007-05-01 31 Setting IDB Parameters, R10 to R12, 06A, 06B 32 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Delay 14 Defining Delay This section describes how to define ESB and RX and TX feeder delay. The parameter specifies the RF signal delay in the feeder. If the total feeder delay value, measured and calculated in the document Verifying Antenna Systems, differs from the default delay (configuration dependent). Then the delay parameter must be updated to the total feeder delay value (0-10000 ns): See test record from Verifying Antenna Systems. Note: If TG synchronization is to be defined, see the document Setting TG Synchronization Parameters. 1. On the Configuration menu, click Define and Delay to open the Define Delay window. 2. Select the cable to define the delay for and click Run. 3. Enter the delay value (in ns) and click OK. 4. Repeat steps 2 to 3 for remaining cables. 5. Click Close when finished. 2/1543-LZA 701 0001 Uen H 2007-05-01 33 Setting IDB Parameters, R10 to R12, 06A, 06B 34 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining GPS Parameters 15 Defining GPS Parameters This section describes how to define the GPS parameters. To be able to use GPS as a synchronization source, the RBS must be equipped with a GPS receiver. A GPS receiver is used to achieve a synchronized radio network and works as reference for RF frequency generation and GSM time-based counters. Parameters for the GPS are set according to the table below. Table 7 GPS Parameters Parameter Valid Values Default Description GPS present • Yes No The parameter is automatically changed to Yes when GPS receiver hardware is added. If the GPS receiver is removed, the parameter must be manually set to No. • No GPS RX delay 0 – 65535 ns 0 ns The parameter defines the delays in the GPS receiver, antenna, and cables and is important in achieving a synchronized network. GPS RX DXU 0 – 65535 ns 0 ns The parameter defines the delays from the GPS receiver to the DXU, including delays in the OVP unit and is important in achieving a synchronized network. Note: If the GPS receiver is used only as a reference for RF frequency generation, then it is not necessary to set the GPS RX delay and GPS RX DXU parameters. For more information on GPS Installation, see the document GPS Synchronization in RBS * 1. On the Configuration menu, click Define and GPS Parameters to open the Define GPS Parameters window. 2. Select Yes for GPS present. 3. Enter the GPS RX delay (in ns), that is, the delay in GPS antenna, GPS feeder cables and the GPS receiver. 4. Enter the GPS RX DXU delay, that is, the delay from the receiver to the DXU, including the delay in the OVPs. 5. Click OK when finished. 2/1543-LZA 701 0001 Uen H 2007-05-01 35 Setting IDB Parameters, R10 to R12, 06A, 06B 36 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining Hardware Information 16 Defining Hardware Information This section describes how to define hardware information for hardware units such as feeder cables, fans, a passive RU, or cabinet with memory, if applicable. The hardware information is defined to make the RBS inventory information, available in the OMT and at the O&M centre, more complete. Defined hardware information can be displayed, using the OMT functions Display Inventory List and Display Information, or at the O&M centre. 1. On the Configuration menu, click Define and Hardware Info to open the Define HW Info window. 2. Select the applicable HW unit in the list, and click Run. 3. Enter the hardware information listed below, and click OK when finished. • Product No. • Serial No. • HW Rev. • Comment 4. Repeat steps 2 to 3 for all applicable HW units. 5. Close the window when finished. 2/1543-LZA 701 0001 Uen H 2007-05-01 37 Setting IDB Parameters, R10 to R12, 06A, 06B 38 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining PCM 17 Defining PCM This section describes how to define the PCM paramaters for transmission. 17.1 , see: Section 17.1 on page 39 • For transmission interface E1, 75 • For transmission interface E1, 120 see Section 17.2 on page 39 • For transmission interface T1, 100 see Section 17.3 on page 41 Transmission Interface E1, 75 This section describes how to define the PCM parameters for transmission interface E1, 75 . 1. On the Configuration menu, click Define and PCM. 2. Set the parameters according to the table and instructions below. 3. Click OK when all parameters are set. Table 8 PCM Parameter Settings for Transmission Interface E1, 75 PCM Parameter Settings Transmission Interface E1 Network Topology See Site Installation Documentation Sync Source See Site Installation Documentation CRC-4 See Site Installation Documentation Spare bits See Site Installation Documentation Receiver Sensitivity 17.2 A Short haul B Short haul C Short haul D Short haul Transmission Interface E1, 120 This section describes how to define the PCM parameters for transmission interface E1, 120 . Note: Calculating the total attenuation of the entire RBS chain is only necessary if multidrop (in combination with OVPs with bypass relays) is used. 2/1543-LZA 701 0001 Uen H 2007-05-01 39 Setting IDB Parameters, R10 to R12, 06A, 06B 1. On the Configuration menu, click Define and PCM. 2. Set the parameters according to the table and instructions below. 3. Click OK when all parameters are set. Table 9 PCM Parameter Settings for Transmission Interface E1, 120 PCM Parameter Settings Transmission Interface E1 Network Topology See Site Installation Documentation Sync Source See Site Installation Documentation CRC-4 See Site Installation Documentation Spare bits See Site Installation Documentation Receiver Sensitivity A See instructions below B C D The instructions below describe how to calculate the cable attenuation between the Far End and the RBS. The cable attenuation determines whether receiver sensitivity is to be set to short or long haul. Use of long haul requires that the equipment at the far end supports long haul. Far End RBS 1 A(C) B(D) RBS 2 A(C) B(D) RBS 3 A(C) B(D) P008428C Figure 3 System View for Transmission Interface E1, 120 1. Calculate the cable attenuation between the Far End and the RBS according to the following formula: Cable attenuation = cable length x cable attenuation per metre (or foot). If multidrop is used then calculate the attenuation of the entire RBS chain, because Receiver Sensitivity A (C) is determined by the total attenuation of the chain from port A (C) to Far End. Receiver Sensitivity B (D) is determined by the total attenuation to the last RBS in the chain. 2. If the cable attenuation is less than 6 dB, set the receiver sensitivity to short haul. If the cable attenuation is greater than 6 dB, set the receiver sensitivity to long haul. 40 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining PCM 3. Set unused ports to short haul. The following example illustrates what is said above. RBS 1 Far End A C B D 150m 0,03 dB/m P010439A In this example, Far End and the RBS refer to the figure above. The cable length between the RBS and the Far End is 150 m. The cable attenuation for the cable between the RBS and the Far End is 0.03 dB/m 1. Calculate the cable attenuation between the Far End and the RBS: 150 m x 0.03 dB/m = 4.5 dB 2. Set Receiver Sensitivity A for the RBS to “Short haul” 3. Set Receiver Sensitivity B, C and D for the RBS to “Short haul" (not connected). Example 2 17.3 Calculating the Receiver Sensitivity Parameters for Transmission Interface E1, 120 Transmission Interface T1, 100 This section describes how to define parameters for transmission interface T1. When using the cable length for calculations in the following sections, the cable used must be the reference cable (multipair 22 AWG office cable) or similar. 1. Find the transmission interface type in the Site Installation Documentation, and use the table below to find the applicable section with instructions for setting the parameters. 2/1543-LZA 701 0001 Uen H 2007-05-01 41 Setting IDB Parameters, R10 to R12, 06A, 06B Table 10 Selecting Section for Defining T1, Knowing the Transmission Interface Type If the transmission interface type is... then... DSX-1 go to Section 17.4 on page 43, Defining LBO Parameters as Short Haul. DS1 and... the signal level at the customer interface and the cable attenuation is known go to Section 17.5 on page 45, Defining LBO Parameters as Long Haul Manually. only the maximum input signal level at the far end is known go to Section 17.6 on page 47, Defining LBO Parameters as Long Haul Automatically. neither the signal level at the customer interface nor the cable attenuation are known go to Section 17.7 on page 50, Defining LBO Parameters when Transmission Characteristics are Unknown. 2. If there is no information about the transmission interface type in the Site Installation Documentation, use the cable length to find the appropriate section in the table below. Table 11 Selecting Section for Defining T1, Knowing the Cable Length If... then... the cable length is less than 655 feet go to Section 17.4 on page 43, Defining LBO Parameters as Short Haul. the cable length is more than 655 feet and... the signal level at the customer go to Section 17.5 on page 45, interface and the cable Defining LBO Parameters as attenuation is known Long Haul Manually. only the maximum input signal go to Defining LBO Parameters level at the far end is known as Long Haul Automatically Section 17.6 on page 47. neither the signal level at the customer interface nor the cable attenuation are known go to Section 17.7 on page 50, Defining LBO Parameters when Transmission Characteristics are Unknown. 3. If no information is given in Site Installation Documentation, see the table below. 42 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining PCM Table 12 If... then... there is no information about the cable length go to Section 17.7 on page 50, Defining LBO Parameters when Transmission Characteristics are Unknown. Note: 17.4 Selecting Section for Defining T1, without any Information about the Cable Length Calculating the total attenuation of the entire RBS chain is only necessary if multidrop (in combination with OVPs with bypass relays) is used. Defining LBO Parameters as Short Haul This section describes how to define the LBO parameters as short haul. 1. On the Configuration menu, click Define and PCM to open the Define PCM window. 2. Set the parameters according to the table and instructions below. 3. Click OK when all parameters are set. Table 13 PCM parameters Settings for Transmission Interface T1, Short Haul PCM Parameter Setting Transmission Interface DS1(T1) Network Topology See Site Installation Documentation Sync Source See Site Installation Documentation LBO A See instructions below LBO B LBO C LBO D FDL Use See Site Installation Documentation The instructions below describe how to calculate the LBO parameters. Customer Interface DSX-1 RBS 1 A(C) B(D) RBS 2 A(C) B(D) RBS 3 A(C) B(D) P008645B Figure 4 System View for Transmission Interface T1, Short Haul 2/1543-LZA 701 0001 Uen H 2007-05-01 43 Setting IDB Parameters, R10 to R12, 06A, 06B 1. Find out the length of the cable between the RBS and the customer interface (the cross-connection point DSX-1). See figure above. If multidrop is used, calculate the attenuation of the entire RBS chain, since LBO A (C) is determined by the total attenuation of the chain from port A (C) to the Customer Interface. LBO B (D) is determined by the total attenuation to the last RBS in the chain. If the cable length is not known, set the LBO parameters to ‘‘Short h., 0 – 133 feet’’. 2. Use the cable length and the table below to set the correct LBO parameters in the OMT. Table 14 Setting LBO Parameters to Short Haul in the OMT Cable Length Feet LBO Setting Metres (in the OMT) 0 – 133 0 – 40 Short h., 0 – 133 feet 133 – 266 40 – 81 Short h., 133 – 266 feet 266 – 399 81 – 122 Short h., 266 – 399 feet 399 – 533 122 – 162 Short h., 399 – 533 feet 533 – 655 162 – 200 Short h., 533 – 655 feet 3. Set unused ports to ‘‘Short h., 0 – 133 feet’’. The following example illustrates what is said above. RBS 1 Customer Interface (DSX-1) A C B D 200 feet (61 metres) P010440A In this example, customer interface (DSX-1) and the RBS refer to the figure above. The cable length between the RBS and the customer interface (DSX-1) is 200 feet (61 m). 1. Set LBO A for the RBS to “Short h., 133 – 266 feet” See the table above 2. Set LBO B, C and D for the RBS (not connected) to “Short h., 0 – 133 feet”. Example 3 44 Setting LBO Parameters to Short Haul 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining PCM 17.5 Defining LBO Parameters as Long Haul Manually This section describes how to define LBO as long haul, when the signal level at the customer interface and the cable attenuation is known. Signal level at the customer interface means either the maximum input signal level at the Far End, or the carrier-advised code at the network interface. See figure below. RBS Customer Interface (Far End/Network Interface) Maximum input signal level/Carrier advised code A(C) B(D) Cable attenuation P008431B Figure 5 System Parameters for Defining LBO Parameters to Long Haul 1. On the Configuration menu, click Define and PCM. 2. Set the parameters according to the table and instructions below. 3. Click OK when all parameters are set. Table 15 Manual PCM Parameters Settings for Transmission Interface T1, Long Haul PCM Parameter Settings Transmission Interface DS1(T1) Network Topology See Site Installation Documentation Sync Source See Site Installation Documentation LBO A See instructions below LBO B LBO C LBO D FDL Use See Site Installation Documentation The instructions below describe how to manually set the LBO parameters to long haul. 1. If the carrier-advised code is given in the Site Installation Documentation, use the table below to set the correct A (B, C, D) LBO parameters. If multidrop is used, calculate the attenuation of the entire RBS chain, since LBO A (C) is determined by the total attenuation of the chain from port A (C) to the Customer Interface. 2/1543-LZA 701 0001 Uen H 2007-05-01 45 Setting IDB Parameters, R10 to R12, 06A, 06B Table 16 Long Haul Parameters for Different Carrier-Advised Codes at the Network Interface Cable Attenuati on (dB) Long Haul Parameters for Different Values of the Carrier-Advised Code at the Network Interface A (0 dB) B (-7.5 dB) C (-15 dB) D (-22.5 dB) 0 – 7.5 0 -7.5 -15 -22.5 7.5 – 15 N/A 0 -7.5 -15 15 – 22.5 N/A N/A 0 -7.5 N/A N/A N/A 0 > 22.5 2. If the maximum input signal level is given in the Site Installation Documentation, use the table below to set the correct LBO A (B, C, D) parameters. Table 17 Long Haul Parameters for Different Maximum Input Signal Levels Cable Attenuati on (dB) Long Haul Parameters for Different Values of the Maximum Input Signal Level at the Far End 0 dB -7.5 dB -15 dB -22.5 dB 0 – 7.5 0 -7.5 -15 -22.5 7.5 – 15 0 0 -7.5 -15 15 – 22.5 0 0 0 -7.5 0 0 0 0 > 22.5 3. If multidrop, set LBO B (D) to ‘‘Long h., 0 dB’’. Used B (D) ports in multidrop configurations should always be set to ‘‘Long h., 0 dB’’ 4. Set unused ports to ‘‘Short h., 0 – 133 feet’’. Unused ports should always be set to ‘‘Short h., 0 – 133 feet’’. The following example illustrates what is said above. RBS 1 Network Interface A C B D Cable Carrier Advised Attenuation = 5 dB Code= -15 dB P010441A 46 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining PCM In this example, network interface and the RBS refer to the figure above. Carrier-advised code at the network interface is “C” (-15 dB). The cable attenuation is 5 dB. 1. See the table Long haul parameters for different carrier-advised codes at the network interface to find the correct LBO parameter for LBO A. 2. Set LBO A to “Long h., -15 dB” 3. Set LBO B, C and D (not connected) to “Short h., 0 - 133 feet”. Example 4 17.6 Calculating LBO Parameters Manually for Long Haul Defining LBO Parameters as Long Haul Automatically This section describes how to define LBO to long haul when the maximum input signal level at the Far End is known, but not the cable attenuation. The cable attenuation can be measured by the RBS according to the instructions below. See figure below. RBS Customer Interface (Far End) Maximum input signal level A(C) B(D) Measured cable attenuation P008626B Figure 6 System Parameters for Defining LBO Parameters Automatically to Long Haul 1. On the Configuration menu, click Define and PCM. 2. Use the table and instructions below to set the parameters. 3. Click OK, when all parameters are set. Table 18 PCM Parameters Settings for Transmission Interface T1, Long Haul Automatically PCM Parameter Setting Transmission Interface DS1(T1) Network Topology See Site Installation Documentation Sync Source See Site Installation Documentation 2/1543-LZA 701 0001 Uen H 2007-05-01 47 Setting IDB Parameters, R10 to R12, 06A, 06B PCM Parameter Setting LBO A See instructions below LBO B LBO C LBO D FDL Use See Site Installation Documentation The instructions below describe how to automatically set the PCM parameters. For RBS 1 only: 1. Set LBO A (C) to ‘‘Long h. ALBO, <value of the maximum input signal level> dB’’. 2. If stand alone, set unused ports to ‘‘Short h., 0 – 133 feet’’. Unused ports are always set to ‘‘Short h., 0 – 133 feet’’. The RBS automatically sets the correct value in the IDB when the IDB is installed. Note: The following instructions apply only to multidrop. If multidrop is used, the line attenuation for RBS 1 must be measured according to the instructions below. For RBS 1: 1. Set LBO B (D) to ‘‘Long h., 0 dB’’. Used B (D) ports in multidrop are always set to ‘‘Long h., 0 dB’’ 2. On the RBS 2000 menu, click Connect. 3. On the Configuration menu, click Install IDB. The RBS will automatically set the correct value in the IDB. The RBS remains in Local mode after the IDB has been installed. 4. On the Maintenance menu, click Monitor and Lin Att PCM A (C). 5. Click on Start Monitor and read the value of the cable attenuation. The displayed value is given in deci dB (10 deci dB = 1 dB). Make a note of the value in the test record, see Verifying Antenna Systems. When configuring the IDB for RBS 2 and RBS 3, follow the instructions below. For RBS 2 and RBS 3: 6. Set LBO A (C) on RBS 2 (RBS 3) to ‘‘Long h. ALBO, 0 dB’’. 48 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining PCM 7. On the Configuration menu, click Install IDB. 8. On the Maintenance menu, click Monitor and Lin Att PCM A (C). 9. Click on Start Monitor and read the value of the cable attenuation. The displayed value is given in deci dB (10 deci dB = 1 dB). Make a note of the value in the test record. 10. Add the measured cable attenuation values. The value given by Lin Att PCM A is the cable attenuation to the previous RBS in the chain, so the measured value must be added to the value for the previous RBS(s) to obtain the total cable attenuation for the RBS in question. 11. Use the total cable attenuation value to find the long haul parameter value for LBO A (C) in the table below. Table 19 Long Haul Parameters for Different Maximum Input Signal Levels Cable Attenua tion (dB) Long Haul Parameters for Different Maximum Input Signal Levels at the Far End 0 dB -7.5 dB -15 dB -22.5 dB 0 – 7.5 0 -7.5 -15 -22.5 7.5 – 15 0 0 -7.5 -15 15 – 22.5 0 0 0 -7.5 > 22.5 0 0 0 0 12. If there is another RBS in the chain, set LBO B (D) to ‘‘Long h., 0 dB’’. Used B ports are always set to ‘‘Long h., 0 dB’’. If this is the last RBS in the chain, set LBO B (D) to ‘‘Short h., 0 – 133 feet’’. Unused ports are always set to ‘‘Short h., 0 – 133 feet’’. 13. If there is another RBS in the chain, repeat steps 6 to 11. The following example illustrates what is said above. RBS 1 Far End A C B D Maximum input signal level= -15 dB Measured cable attenuation = 5 dB P010442A 2/1543-LZA 701 0001 Uen H 2007-05-01 49 Setting IDB Parameters, R10 to R12, 06A, 06B In this example, Far End and RBS refer to the figure above. Maximum input signal level at the Far End is -15 dB. The cable attenuation is not known. 1. Set LBO A to “Long h. ALBO, -15 dB”. The cable attenuation is measured by the RBS to 5 dB. 2. The value of LBO A is set automatically by the RBS. 3. Set LBO B, C and D (not connected) to “Short h., 0 - 133 feet”. Example 5 17.7 Calculating LBO Parameters Automatically for Long Haul Defining LBO Parameters when Transmission Characteristics are Unknown This section describes how to define the LBO parameters if none of the parameters carrier-advised code, maximum input signal at the customer interface, cable attenuation or cable length are known. 1. On the Configuration menu, click Define and PCM. 2. Set the parameters. See table below. Click OK when all parameters are set. Table 20 PCM Parameters Settings for Transmission Interface T1, Transmission Characteristics Unknown PCM Parameter Settings Transmission Interface DS1(T1) Network Topology See Site Installation Documentation Sync Source See Site Installation Documentation LBO A ‘‘Long h., 0 dB’’ LBO B ‘‘Long h., 0 dB’’, if used ‘‘Short h., 0 – 133 feet’’, if unused LBO C ‘‘Long h., 0 dB’’ ‘‘Short h., 0 – 133 feet’’, if unused LBO D ‘‘Long h., 0 dB’’, if used ‘‘Short h., 0 – 133 feet’’, if unused FDL Use 50 See Site Installation Documentation 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining RBS Identity 18 Defining RBS Identity This section describes how to define the RBS Identity. Specifying a name and a description for the RBS makes the RBS easier to identify when for example connecting it by Remote OMT. 1. On the Configuration menu, click Define and RBS Identity to open the Define RBS Identity window. 2. In the RBS name field, enter the RBS name (preferably a unique name with a maximum of 20 characters). 3. In the RBS description field, enter information about the site, such as the site name or the location of the site (maximum of 100 characters). 4. Click OK. 2/1543-LZA 701 0001 Uen H 2007-05-01 51 Setting IDB Parameters, R10 to R12, 06A, 06B 52 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining System Voltage 19 Defining System Voltage This section describes how to define the system voltage. In configurations that include batteries, the system voltage is the voltage with which the batteries are charged. In configurations that do not include batteries, but include several RBSs with different power systems, all power systems must have the same system voltage for optimal operation. The voltage range set then depends on the configuration. See table below. If the voltage is not set, then the default value is 27.2 V. Table 21 System Voltage Parameter Voltage Range Configuration without Batteries 24.0 – 28.5 V Configuration with Batteries Fixed Voltage Charging TemperatureCompensating Charging 25.5 V – 28.5 V 26.7 – 27.7 V 1. On the Configuration menu, click Define and System Voltage. 2. In the Define System Voltage window, select the applicable object and click Run. 3. Enter the system voltage and click OK. 2/1543-LZA 701 0001 Uen H 2007-05-01 53 Setting IDB Parameters, R10 to R12, 06A, 06B 54 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining TEI 20 Defining TEI This section describes how to define the TEI value. To enable the BSC to communicate with the CMRU of an RBS in a cascade chain, a unique TEI value between 12 and 63 needs to be set for each RBS in the chain. The TEI value for the RBS must also match the TEI value the BSC uses to identify the RBS. For RBSs not connected in a cascade chain, the default TEI value can be used. 1. On the Configuration menu, click Define and TEI to open the Define TEI window. 2. Select ‘‘DXU 0’’, and click Run. 3. Enter the TEI value, and click OK. 2/1543-LZA 701 0001 Uen H 2007-05-01 55 Setting IDB Parameters, R10 to R12, 06A, 06B 56 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining TNOM 21 Defining TNOM This section describes how to define the Transport Network Operation and Maintenance (TNOM) parameters, if supported by the network (DXX support). DXX support enables an O&M centre to monitor the transmission performance of an RBS. The table below describes the TNOM parameters possible to define. Note: The timeslot may not be set to a timeslot that is in use by the RBS. Table 22 TNOM Parameter Valid Values Default Values Description TNOM use • On Off Activates or deactivates DXX support in an RBS. Defines the 64 kbps timeslot on the E1/T1 link that is used for DXX support of the RBS. It needs to be set only if TNOM use is on. • Off TNOM timeslot • E1: 1 – 31 E1: 31 • T1: 1 – 24 T1: 24 TNOM node ID 1 – 65534 1 Defines a unique identifier for a node, such as an RBS in a DXX network. It must only be set if TNOM use is on and must be equal to the value set in the O&M centre. 1. On the Configuration menu, click Define and TNOM to open the Define TNOM Parameters window. 2. Set TNOM Use to ‘‘On’’. 3. In the TNOM Timeslot box, enter the value. Valid TNOM time slot values are shown in the table above. 4. In the TNOM Node ID box, enter the correct values. Valid TNOM Node ID values are found in the table above. Click OK when finished. 2/1543-LZA 701 0001 Uen H 2007-05-01 57 Setting IDB Parameters, R10 to R12, 06A, 06B 58 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining VSWR Limits 22 Defining VSWR Limits This section describes how to define VSWR limits for configuring the supervision of the antenna system. Note: This section does not apply to RBS 2116 or RBS 2216. Preconditions Before defining the VSWR limits, ensure the following: • The test results from the SWR tests are available • There are no faults in the antenna system. For information on how to test the antenna system, see the document Verifying Antenna Systems. Note: If VSWR alarms are received and no faults are found in the antenna system, the IDB needs to be updated with increased VSWR alarm limits. Defining Recommended VSWR Limits Parameters for VSWR limits are set to adjust the detection of problems with the antenna system for the specific site. Note: Examples when limits need to be defined for VSWR class 1 and 2 can be short feeder, diplexer and TMA use (typically needs higher VSWR limits). The table below describes the parameters available for the VSWR limits that could be defined. 2/1543-LZA 701 0001 Uen H 2007-05-01 59 Setting IDB Parameters, R10 to R12, 06A, 06B Table 23 VSWR Limits Parameter Valid Values Default Description VSWR supervisio n • Default Default This parameter specifies if the limits for VSWR class 1 and VSWR class 2 faults are set to default values or if the user can define them. • User defined • Default: High default values (2.8) are used for both VSWR class 1 and VSWR class 2 parameters. The VSWR class 1 and VSWR class 2 parameter values cannot be changed. This is the predefined setting for TMA configurations. The supervision detects only major faults. • User-defined: Values for the VSWR class 1 and VSWR class 2 parameters can be entered manually. This is the predefined setting for non-TMA configurations. In such cases, predefined values for VSWR class 1 and VSWR class 2 parameters are provided. VSWR class 1 See Table 24 on page 61 2.8 The parameter is used to select the threshold for VSWR class 1 faults VSWR class 2 See Table 24 on page 61 2.8 The parameter is used to select the threshold for VSWR class 2 faults 1. Select the recommended VSWR limit from the table below by cross-checking the measured VSWR value with the recommended VSWR alarm limit. For measured VSWR value (in the test record from Verifying Antenna Systems) and recommended VSWR alarm limit, see Site Installation Documentation. 60 2/1543-LZA 701 0001 Uen H 2007-05-01 Defining VSWR Limits Table 24 Recommended VSWR Limits for Different Initial VSWR Values Measured VSWR Value Recommended VSWR Limit Class 2 Limit Class 2 Limit Class 1 Limit ≤ 1.5 % ≤ 0.2 %(1) ≤ 0.01 %(1) 1.00 – 1.30 1.6 1.7 2.2 1.31 – 1.37 1.7 1.8 2.2 1.38 – 1.43 1.8 2.0 2.2 1.44 – 1.55 2.0 2.2 2.5 1.56 – 1.66 2.2 2.5 2.8 ≥ 1.67 Not recommended (1) (1) False alarm probability 2. In the Configuration menu, select Define and VSWR Limits. 3. In the Define VSWR Limits window, select the applicable object from the list and click Run. 4. In the Define VSWR Limits dialogue box, set the VSWR Class 1 and Class 2 values according to the table above and click OK. 5. Repeat steps 3 to 4 for each applicable antenna object. 6. Click Close when finished. 2/1543-LZA 701 0001 Uen H 2007-05-01 61 Setting IDB Parameters, R10 to R12, 06A, 06B 62 2/1543-LZA 701 0001 Uen H 2007-05-01 Saving IDB 23 Saving IDB In case it is necessary to reinstall the IDB, the IDB parameters must be saved on the PC. • On the Configuration menu, click Save IDB. • Give the IDB file an RBS-specific name, and save the IDB on the PC. 2/1543-LZA 701 0001 Uen H 2007-05-01 63 Setting IDB Parameters, R10 to R12, 06A, 06B 64 2/1543-LZA 701 0001 Uen H 2007-05-01 Installing IDB 24 Installing IDB This section describes how to install the IDB in the RBS by connecting the OMT to the DXU. Note: If the flash card has to be removed when installing the IDB, see the document RBS SW Update. Note: Using the OMT, always reload the software and install the appropriate IDB after moving a used flash card to another cabinet. This ensures consistent software and correct configuration. Note: The RBS must be in local mode to accept a new or modified IDB. 1. If the RBS is in remote mode, change the setting to local mode by pressing the Local/remote button on the DXU. The Local indicator will start to flash. DXU rese t Local Local/re mote P012062A 2. Wait until the Local indicator has a constant yellow light, indicating that the RBS is now in local mode. 3. Physically connect the OMT to the RBS if not already connected. See Section 4 on page 9 . 4. On the RBS 2000 menu, click Connect to logically connect the OMT to the RBS. 5. On the Configuration menu, click Install IDB. The RBS remains in local mode after the IDB has been installed. Note: 6. Do not touch the RBS when any indicators are double-flashing. See Optical Indicators and Switches. On the Configuration menu, click Site Specific Data and Display to open the site_specific_data.txt - window. Check that the correct parameters have been defined. 2/1543-LZA 701 0001 Uen H 2007-05-01 65