10/16/2019 LV Ecofit™ Solutions Training Presented by: Camilo Mendoza October 2018 LV Ecofit™ Solution Training Introduction The Ecofit™ Solution Offer What to collect in the site? Ecofit™ Plug and Play Solution Installation and Testing of Masterpact P&P Solution Ecofit™ Masterkit Solution Installation and testing of Masterkit Solution Ecofit Compact C – Compact NS Maintenance and associated tools 1 10/16/2019 The goal of this training Customer satisfaction • Customer satisfaction by providing highly skilled technical support on a system scope (increase their proficiency level) • Maintain the country competence to develop the business and customer confidence/loyalty • Consolidate and develop the installed base service business Confidential Property of Schneider Electric | Page 3 For whom? Target • You are: • Schneider Electric field service representatives (FSR) Prerequisites • Service experience on Masterpact NT/NW • Offer knowledge (product experience, previous training or e-learning). • General knowledge on circuit breaker protection and settings (short time, long time…) • E-Learning “Get started with MTZ” • PC + Smartphone (Android if possible, or iOS) Confidential Property of Schneider Electric | Page 4 2 10/16/2019 Learning objectives Be able to… • Describe the right Ecofit solutions • Describe the services linked to Masterpact MTZ • Update an installation for next EcoStruxure capabilities • Explain or answer customer queries & technical questions • Install new digital module , upgrade the equipment • Carry out preventive maintenance on Masterpact NT/NW/MTZ according to the Maintenance Guide and associated procedures. • Carry out diagnosis and repair following a failure on site. • Use the service tools available • Find and exploit the usefull documentations • Configure the breaker and its communication modules Confidential Property of Schneider Electric | Page 5 Confidential Property of Schneider Electric | Page 6 3 10/16/2019 60% Exercises Programme 40% Presentation Duration of the training: 4 days Day 1 • Introduction • LV Ecofit Solution Offer • What to collect in the site? • Ecofit Plug and Play solution Day 2 • Ecofit Masterkit Solution Day 3 • aaaaa Day 4 • aaaaa • Installation and Testing of Masterkit Solution • Maintenance and associated tools • Installation and Testing of Plug and Play Solution Confidential Property of Schneider Electric | Page 7 Agenda proposal : • 09:00hrs - Start in the morning • 10:15hrs – 10:30hrs - Break • 12:00hrs -13:30hrs - Lunch • 15:00hrs – 15:15hrs - Break • 16:30hrs Wrap up of the day - We encourage your : - Curiosity - Engagement - Respect ( please wait for the breaks to do your mails or calls ) Confidential Property of Schneider Electric | Page 8 4 10/16/2019 Trainees introduction Crossed interview (15’) • Each trainee interviews the person sitting next to her/him • Then introduces herself/himself to the group: • Name • Position • Organization / country • Experience • Expectations of the training session Confidential Property of Schneider Electric | Page 9 FSR Safety Process Key Messages Risk taking is never acceptable when it comes to the health and safety of our people. Jean-Pascal Tricoire President and Chief Executive Officer Optional caption goes here. Duis maximus venenatis laoreet. Aliquam et ipsum condimentum. « I count on each one of you to play your role and together we will protect our health and safety! » Confidential Property of Schneider Electric | Page 10 5 10/16/2019 FSR Safety Process Key Messages Safety is at the heart of all our service operations. Therefore we have a comprehensive collection of safety information. The first is our Health and Safety Policy This document is the Schneider Electric Safety Mission Statement. Confidential Property of Schneider Electric | Page 11 FSR Safety Process Key Messages The Schneider Electric Life Saving Rules contains some safety guidelines that can be used at work or at home. Confidential Property of Schneider Electric | Page 12 6 10/16/2019 FSR Safety Process Key Messages The Safety and Occupational Health Policy is a comprehensive document which describes in detail our policies we deploy to keep our people safe. Confidential Property of Schneider Electric | Page 13 FSR Safety Process Key Messages Inside the PPE Global Directive GSD015 and the associated Guidance Document illustrates the PPE policy and when it should be applied. The FSE will be supplied with PPE and it is his responsibility to ensure that he has the correct PPE and that it is in good condition. Confidential Property of Schneider Electric | Page 14 7 10/16/2019 FSR Safety Process Key Messages Before starting any task the FSR must first carry out a risk assessment and using the PreService Site Safety Plan . For anymore Safety information or documentation you can find these on the SERE Website Confidential Property of Schneider Electric | Page 15 FSR Safety Process Key Messages According to our statistics for every 600 Near Misses there are 10 accidents needing medical treatment and 1 fatal accident. If we are to reduce the number of accidents and injuries it is imperative we use the Schneider Globes system to report Near Misses. Confidential Property of Schneider Electric | Page 16 8 10/16/2019 Safety for the Training Centre Confidential Property of Schneider Electric | Page 17 Safety practice to be observed at the Schneider Abu Dhabi Training Center First Aid Providers and Fire Wardens Mosbah Fezzai Oji Emuejerhi Mohammed Shamsheer (FA) (FA) (FW) • In case of any emergency and medical issue, kindly contact one of them. • In case they are not available, contact the respective assisting agency as per below nos. Safety Practice Item Emergency Telephone Numbers Civil Defense - 997 Police – 999 Ambulance - 998 Evacuation Fire Extinguishers Manual Call Point First Aid Box Jayapal Muthu (FW) When Needed / Required • • • Dial Civil Defense contact no. in case of fire incident. Any Police assistance dial the respective emergency no. For any Ambulance assistance dial the respective no. • • • • • • Identify the location of the evacuation plan placards in the Training Center. Identify the 2 emergency exits and where to assemble incase of an evacuation. Identify the location of the nearest Fire Extinguisher inside the vicinity of the training center. Ensure the inspection sticker is updated and safety pin is in tacked. Identify the location of the nearest manual call point inside the training center. Only use in case of uncontrolled fire incident. • • Identify the location of the nearest first aid box. Ask assistance with the above trained first aider. Confidential Property of Schneider Electric | Page 18 9 10/16/2019 Rules during assembling and disassembling operation. • When we assemble or disassemble the product, we may carry some heavy spare parts. To protect ourself, we need to wear mechanical gloves and security coqule. Confidential Property of Schneider Electric | Page 19 Safety reminder for this training Mechanical hazards o o o o o o Falling objects Rotating gears Sharp edges Stored energy Mechanical failure Guillotine Cuts, fractures, amputation…… PAIN! Protect yourself & your team! Confidential Property of Schneider Electric | Page 20 10 10/16/2019 Safety reminder for this training Electrical hazards Insulation failures Internal arc Overheating Overvoltage Faulty equipment Bad LOTO process o Operating error o o o o o o Fire, equipment damage, burns, toxic gases, electric shock, electrocution, pain & death. Protect yourself & your team! Confidential Property of Schneider Electric | Page 21 Personal Protective Equipment (PPE) Hard hat Safety footwear Safety clothing Face shield Eye protectio n Ear protection Appropriat e gloves Remove jewellery Use the CORRECT equipment ADAPTED to the TASK Confidential Property of Schneider Electric | Page 22 11 10/16/2019 Safety symbols Check your PPE Confidential Property of Schneider Electric | Page 23 LV Ecofit™ Solution Training Introduction The Ecofit™ Solution Offer What to collect in the site? Ecofit™ Plug and Play Solution Installation and Testing of Masterpact P&P Solution Ecofit™ Masterkit Solution Installation and testing of Masterkit Solution Ecofit Compact C – Compact NS Maintenance and associated tools 12 10/16/2019 Low voltage circuit breakers Schneider Electric a great history Selpact & DA 60/70’s Masterpact M 1987 Masterpact NT / NW 2000 2013 Masterpact MTZ Smart Panels Bridge electrical distribution to internet of things Confidential Property of Schneider Electric | Page 25 Masterpact M Commercialised from 1987 to 2003 The Masterpact M range offered a large selection of performance levels : o Ratings from 800 to 6300A. o 3 or 4 pole o Fixed or drawout versions Confidential Property of Schneider Electric | Page 26 13 10/16/2019 Masterpact M Dimensions o A single frame size from 800 to 3200 A. o A common height and depth from 800 to 6300 A. Confidential Property of Schneider Electric | Page 27 Masterpact M Performance levels Confidential Property of Schneider Electric | Page 28 14 10/16/2019 Masterpact MTZ Commercialised in 2017 : A new digital user experience • Masterpact MTZ is available in 3 sizes : MTZ1 630-1600A Not changed • • • • MTZ2 800-4000A Same ratings 630A-6300A Same breaker and chassis frame size Same power connection Same IEC61439-2 switchboard certificate Changes MTZ3 4000-6300A « Standard » • MTZ1 Icu improved from 50 to 66kA • Certified embedded Class 1 energy meter • Vibration, EMC, temperature withstand improvements • Real time self-diagnosis « Optional » • Native direct Ethernet connection Confidential Property of Schneider Electric | Page 29 Masterpact MTZ Performance levels N1 Common applications H1 Industrial sites with high shortcircuits or 2 transformers H2 Incoming point high level of performance and discrimination H3 Very high-performance Highly critical applications L1 High current-limiting capacity & High level of discrimination Icu kA at 440V Ics = 100% Icu Confidential Property of Schneider Electric | Page 30 15 10/16/2019 Masterpact M Control units o Masterpact M08 to M63 circuit breakers are equipped with microprocessor-based electronic control units. o Each control unit for the Masterpact M range corresponds to a given application (instantaneous, distribution, selective, universal). Confidential Property of Schneider Electric | Page 31 New Micrologic X control units 2.0X LI : Long-time + Instantaneous LSIG: LSI + Ground fault 6.0X Not changed • Same basic protection LI, LSI, LSIG, LSIV « Changes Standard » 5.0X LSI : LI + Short-time LSIV: LSI + Earth leakage 7.0X • Reduced Micrologic references • Scalability thru « Digital Modules » • USB and wireless connectivity • Smart devices application • Dual protection setting capability « Optional » • Digital modules • Voltage power supply module (VPS) Only 4 references to cover all the needs Confidential Property of Schneider Electric | Page 32 16 10/16/2019 ECOFITTM Masterpact M - MTZ solutions Control unit substitution Selection of the control unit Confidential Property of Schneider Electric | Page 33 Your turn…. Masterpact M16N1 is equivalent to ….Masterpact MTZ2 16N1 STR28D is equivalent to …Micrologic 6.0X Masterpact M50H1 is equivalent to… Masterpact MTZ3 50H1 Confidential Property of Schneider Electric | Page 34 17 10/16/2019 ! Let’s talk about risks: the future Masterpact M Lifecycle 2003 1986 Masterpact M Lifecycle Start of Commercialization Very big risk for the customer ! 2013 2018 End of Commercialization End of Full scope commercialization M Spare Parts Lifecycle Full Spare Parts supply guaranteed Masterpact M commercialization EcofitTM Spare Parts only The availability of spare parts not guaranteed Confidential Property of Schneider Electric | Page 35 ECOFITTM Masterpact M solutions 1. ‘’Plug & Play’’ 2. Masterkit corresponds to 75% of the Installed base requirements Rest of the installed base addressed by Masterkit Functions Masterpact M chassis kept in place Masterpact NW adapted to Plug&Play Removed Masterpact M Performance 3200A 6300A Confidential Property of Schneider Electric | Page 36 18 10/16/2019 Current ECOFIT Masterpact M solutions using current Masterpact NW are adapted to embed the latest Masterpact MTZ NEW ECOFIT Masterpact M Plug&Play (IEC version) NEW ECOFIT Masterpact M Masterkit (IEC version) Masterpact M chassis kept in place Removed complete Masterpact M Masterpact MTZ adapted to Plug&Play Masterpact MTZ Removed Masterpact M Masterkit specific power connections Masterkit Masterpact MTZ Confidential Property of Schneider Electric | Page 37 Our Solutions Features and benefits • Features: • ECOFIT Masterpact M Plug and Play solution • Benefits: o For drawout circuit breakers (800A-3200A only) o No need for a complete shutdown of the installation (Except for particular cases) o Ultra-fast retrofit solution: ensures reliability of electrical installations equipped with Masterpact M o Easy to execute with 2 simple operations in less than 30 mins (Does not include LOTO procedures, time for safety precautions,…) o Installation time : 1 to 2 hours Confidential Property of Schneider Electric | Page 38 19 10/16/2019 Our Solutions Features and benefits • Features: • ECOFIT Masterpact M Masterkit solution • Benefits: For both fixed and drawout devices (800A – 6300A) with rear connections only. Shutdown required Installation time : 4 to 8 hours Reduced installation down time thanks to pre-designed connections for easy retrofit of your Masterpact M No modification of power connection required No modification of door cutouts (up to M32) Confidential Property of Schneider Electric | Page 39 ECOFITTM Masterpact M Plug&Play solution description Innovative and ultra-fast ECOFITTM solution to guarantee the durability of electrical installations equipped with Masterpact M. Plug & Play Masterpact M chassis kept in place No shut down Masterpact NW adapted to Plug&Play 30 minutes* Removed Masterpact M • Guaranteed spare parts for original chassis • High performances of Masterpact NW • Up to 3200A – Withdrawable version only * Do not include LO/TO procedures, time for safety precautions,… Confidential Property of Schneider Electric | Page 40 20 10/16/2019 ECOFITTM Masterpact M - MTZ Masterkit solution With the Masterkit offer, you have absolutely everything you need to replace easily an old Masterpact M Masterkit Masterpact MTZ Limited shut down • Supplied adapted or loose components Specific Masterkit power connections or • High performances of Masterpact MTZ2/3 • Up to 6300A – Fixed / Withdrawable versions Loose components without device Confidential Property of Schneider Electric | Page 41 Our solutions How to identify the device to be replacedThe most important information to find Rated insulation voltage Breaking capacity Short time withstand Type of breaker Rated frequency Rated operational voltage Confidential Property of Schneider Electric | Page 42 21 10/16/2019 Your turn…Match the labels with the proper equipment No modification to the power connection points No modifications to the switchboard door or busbar Both fixed and withdrawable devices Installation time : 4 to 8 hours 800 A – 6300 A 800 A – 3200 A 75% of the installed base Only withdrawable devices Installation time: 1 to 2 hours Masterkit No shutdown Plug & Play Confidential Property of Schneider Electric | Page 43 Answers Masterkit Plug & Play Installation time : 4 to 8 hours Installation time: 1 to 2 hours No modification to the power connection points No modifications to the switchboard door or busbar Both fixed and withdrawable devices No shutdown 800 A – 6300 A 800 A – 3200 A Only withdrawable devices 75% of the installed base Confidential Property of Schneider Electric | Page 44 22 10/16/2019 LV Ecofit™ Solution Training Introduction The Ecofit™ Solution Offer What to collect in the site? Ecofit™ Plug and Play Solution Installation and Testing of Masterpact P&P Solution Ecofit™ Masterkit Solution Installation and testing of Masterkit Solution Maintenance and associated tools Our Solutions – How to choose What to check during a site survey on a potential Masterpact M ECOFIT solution offer? o Circuit Breaker characteristics • Rating and performance • No. of poles o Type of control unit o Installation mode (Fixed or Withdrawable) o Condition of the chassis o • Condition and operation of the chassis • Clusters: A shutdown is required. If they are in good condition, they can be cleaned and regreased (using the recommended original grease*). If not you must replace them with original spare parts. Accessories (External current sensor, Source changeover system, interlocks and etc.) *Original grease used in manufacturing : Amblygon TA15/2 Confidential Property of Schneider Electric | Page 46 23 10/16/2019 LV Ecofit™ Solution Training Introduction The Ecofit™ Solution Offer What to collect in the site? Ecofit™ Plug and Play Solution M-MTZ Installation and Testing of Masterpact P&P Solution Ecofit™ Masterkit Solution Installation and testing of Masterkit Solution Ecofit Compact C – Compact NS Maintenance and associated tools ECOFITTM Masterpact M - MTZ Plug & Play restrictions Application restrictions •Does not cover 1000V applications, DC applications or corrosion protection • For all performance levels except L1 • • •Does not apply to switchdisconnectors, the solution is only available with Masterpact NW switch-disconnectors. Is not recommended when the Masterpact M chassis has a test position switch (CT) installed Confidential Property of Schneider Electric | Page 48 24 10/16/2019 ECOFITTM Masterpact M - MTZ external neutral sensor 3-pole circuit breakers equipped with external neutral current sensor • The external neutral current sensor used with the STR control unit is not compatible with Micrologic X control units • A new external neutral current sensor compatible with Masterpact MTZ must be installed*. Note : In case of distribution network with several circuit breakers with ground fault protection, we recommend to change all circuit breakers and their external neutral current sensors. *Shutdown is required Confidential Property of Schneider Electric | Page 49 ECOFITTM Masterpact M - MTZ source changeover Mechanical interlocking For the Plug & Play solution • A Masterpact M may be interlocked with a Plug & Play device equipped with specific interlocking part (reference EF548613) For the Masterkit solution • All Masterpact M devices with mechanical interlocking must be replaced as well as the corresponding interlocking system Confidential Property of Schneider Electric | Page 50 25 10/16/2019 ECOFITTM Masterpact M – MTZ source changeover Electrical interlocking Electrical interlocking is possible between Masterpact M and Masterpact MTZ devices using the same existing components : ACP, IVE unit, BA or UA automatic controllers •Note : In cases where a source changeover is involved in the solution, extra special attention should be paid during the risk analysis for the impact on associated devices and the customers continuity of service. Confidential Property of Schneider Electric | Page 51 ECOFITTM Masterpact M – MTZ communication The Plug&Play solution is now FUTURE READY with Masterpact MTZ Since May 2018, communication is available Special support Note : The ECOFIT Masterpact M with Masterpact MTZ Plug & Play solution does not offer the EIFE interface : Standard ULP The status of the connected (CE) and disconnected (CD) position switches on the original Masterpact M chassis are not available Confidential Property of Schneider Electric | Page 52 26 10/16/2019 Dimensions and mounting Two identical frame sizes using the same mounting system as the Masterpact NT/NW range Fixed • For Masterpact MTZ1, it is increased by 13 mm, and Masterpact MTZ2/3 by 3 mm only at the front cover level • The baseline of the breaker basic frame is not changed • • • Same connection points Drawout Same fixing points Integration of Masterpact MTZ in Prisma, Blokset or Okken cubicles does not require design or modification of parts Confidential Property of Schneider Electric | Page 53 Modernization of your electrical distribution equipment ECOFIT Solutions • Enhances your process reliability • Optimizes your maintenance service costs & limits your investments (extend lifetime of your LV switchboard and replace only active components, while leaving switchboard structure intact) • Maintains compliance with evolving industry standards and legislation • Ensures the safety of your personnel and surrounding equipment by using the latest technology • Quality of works as operations are performed by Schneider Electric or other skilled and trained personnel, certified by Schneider Electric using appropriate tools Prolong your switchgear lifetime Optimize your maintenance service costs and limits your investments ECOFIT BENEFITS Maintain compliance with evolving industry standards and legislation Ensure the safety of your personnel and surrounding equipment by using the latest technology 2 Access to Energy Management with the new Micrologic X Confidential Property of Schneider Electric | Page 54 27 10/16/2019 Compatibility MTZ in previous range chassis * Reverse is not possible Masterpact NT/NW chassis can be used for Masterpact MTZ, WITH WIRING MODIFICATION TO DO* Schneider Electric has also developed tested solution to upgrade obsolete Masterpact M with Masterpact MTZ ( Q2 2017) Plug & Play Masterkit The ECOFIT Masterpact Plug & Play solution lets you retrofit the latest generation of Masterpact MTZ circuit breakers in the existing Masterpact M chassis. The ECOFIT Masterkit solution enables you to benefit from all the enhanced features of Masterpact MTZ circuit breakers and accessories without modifying the busbars. It requires total shutdown of the installation to access the busbars Auxiliary circuits wiring has to be modified according procedure Solution available for withdrawable type only, 3P and 4P, 800 to 3200 A. Solution available for fixed and drawout types, 3P and 4P, 800 to 6300 A. Confidential Property of Schneider Electric | Page 55 MTZ Accessories - incompatibility cases Substitution Guide • Due to different limitations on the ascendant compatibility, and more in particular due to improvements in the product architecture for reliability purposes, there are few accessories from Masterpact MTZ not compatible with Masterpact NT/NW: • • • • • • • M2C MN diag voltage releases Performer/Sensor plugs M2C/M6C signalization module Front cove External PTE Etc. Confidential Property of Schneider Electric | Page 56 28 10/16/2019 NT/NW Accessories - incompatibility cases • Due to different innovative features in the new offer (firmware, electrical and front face), there are few accessories from Masterpact NT/NW not compatible with Masterpact MTZ: • • • Micrologic control units, • Etc. MN coils MN coils voltage releases Some communication modules (FDM121/IFM) Confidential Property of Schneider Electric | Page 57 Exercise #5 Case-study & Brainstorming (1h) • Propose an MTZ upgrade of a given architecture. • CASE #1 : basic replacement (NW fixed 3P, without com ; the client wants a dual setting) • CASE #2 : advanced replacement (NW motorized -coils XF & MX, CCM module, same need of a dual setting) • Argue in favour of your architecture: what is to be upgraded ? What are the consequences upon the firmware ? Of which devices ? • Compare group options and trainer architecture Substitution UC1 - Statement Substitution UC1 - Correction Confidential Property of Schneider Electric | Page 58 Substitution Guide 29 10/16/2019 LV Ecofit™ Solution Training Introduction The Ecofit™ Solution Offer What to collect in the site? Ecofit™ Plug and Play Solution M-MTZ Installation and Testing of Masterpact P&P Solution Ecofit™ Masterkit Solution Installation and testing of Masterkit Solution Ecofit Compact C – Compact NS Maintenance and associated tools Difference between an ECOFITTM Masterpact M Plug&Play & a standard Masterpact MTZ2 Standard Masterpact MTZ2 Ecofit Plug&Play Adaptation kit Modified block and cover Confidential Property of Schneider Electric | Page 60 30 10/16/2019 ECOFITTM Masterpact M - MTZ Plug & Play solution Description ECOFITTM Masterpact M Plug & Play solution requires a Masterpact M chassis in full working order If the chassis is bent or damaged, a Plug & Play solution is not possible and the Masterkit solution must be used However, spare parts are still available including: o Clusters o Racking handle o Interlocking kits o Power connections o Auxiliary contacts Confidential Property of Schneider Electric | Page 61 Precautions and checks 4 key points to check Confidential Property of Schneider Electric | Page 62 31 10/16/2019 ECOFITTM Masterpact M - MTZ Plug&Play solution Condition of existing equipment o Remove the existing circuit breaker o Check condition of original chassis - Check for any bent or distorted parts and carry out a racking test (in and out) without the circuit breaker and check the movement and/or condition of the following parts: • The safety shutters • The clusters (Requires shutdown to inspect, clean and regrease*or replace) • The auxiliary connector plate • The drawer side plates o Check the horizontal alignment of the auxiliary connector plate and adjust it if necessary o Check the depth of the chassis mechanism and adjust it if necessary o Check the effort to insert/remove the circuit breaker Confidential Property of Schneider Electric | Page 63 *Original grease used in manufacturing : Amblygon TA15/2 LUNCH Confidential Property of Schneider Electric | Page 64 32 10/16/2019 Your turn…. Using the catalogue Which Masterpact MTZ Ecofit solution can be ordered to replace your Masterpact M ? And now, a quick demonstration of the Low Voltage Ecofit Selector tool Confidential Property of Schneider Electric | Page 65 WORKSHOP ECOFITTM Masterpact M - MTZ Plug&Play solution o What do you need to do to carry out a Plug & Play installation? o Create a method checklist Confidential Property of Schneider Electric | Page 66 33 10/16/2019 ECOFITTM Masterpact M - MTZ Plug&Play solution Identification, part removal and replacement 1. Identify your equipment (Kit with options, Masterpact MTZ P&P circuit breaker…..) 2. Check the Masterpact M performance plate and compare it with the Masterpact MTZ 3. Note the STR protection settings 4. Disconnect auxiliary wires and remove the auxiliary wiring connector plate 5. Remove the right and left drawer plates 6. Clean and regrease* the moving parts in the chassis 7. Never mix greases, always use the exact grease that was used on the original product. 8. Install the new right and left drawer plates 9. Install the auxiliary wiring connector plate and connect the auxiliary wires. *Original grease used in manufacturing : Isoflex Topas L152 Confidential Property of Schneider Electric | Page 67 ECOFITTM Masterpact M - MTZ Plug&Play solution MTZ installation and functional checks • Install the Masterpact MTZ in the chassis • Carry out racking test (Connected/Test/Disconnected positions) while checking the smooth operation in the chassis and put in « Test » position. • Set the Micrologic X protection settings with noted/saved STR settings • Test the Micrologic X with Ecoreach • Test the operation of the customers auxiliaries (Motor, Coils, Contacts etc….) • Rack out the Masterpact MTZ to the « Disconnected » position. Confidential Property of Schneider Electric | Page 68 34 10/16/2019 Workshop…. ECOFITTM Masterpact M - MTZ Plug&Play solution Now it is your turn to carry out a Plug & Play installation Let’s do it safely LA3 Confidential Property of Schneider Electric | Page 69 Safety instruction Failure to take these precautions could expose the person carrying out the work and people nearby to serious bodily injury which could cause death. • All work must be performed with the power off, device open and discharged. • This equipment should only be assembled by professionals. • The manufacturer shall not be held responsible for any failure to comply with the instructions given in the manual. • Risk of electrocution, burns or explosion The device should only be installed and serviced by professionals. Switch off the general and auxiliary power supply to the device prior to any work on or in the device. Always use an appropriate voltage detection device to confirm the absence of voltage. Replace all interlocks, doors and covers before energizing the device. Confidential Property of Schneider Electric | Page 70 35 Slide 69 LA3 à supprimer Laurence AMIGUES, 4/11/2019 10/16/2019 Precautions and checks Measure the diagonals to make sure the chassis is not distorted or warped. (A = B) Confidential Property of Schneider Electric | Page 71 Precautions and checks Verification s Carry out a racking test (in and out) without the circuit breaker and check the movement of the followings: 1. The safety shutters 2. The auxiliary connector plate 3. The drawer side plates Check that all the moving parts are working properly (ex. Pawls, cams…etc) Check the clusters. If they are in good condition, clean and lubricate. If not replace them. Check for any bent or distorted parts that could hinder insertion of the Masterpact circuit breaker. Confidential Property of Schneider Electric | Page 72 36 10/16/2019 Precautions and checks 4 Points to watch Confidential Property of Schneider Electric | Page 73 Components Receiving your Masterpact Plug & Play NW08-32 (Box contents) Box contents: 1. 1 auxiliary wiring connector plate 2. 1 accessory kit including labels and connectors 3. 2 drawer side plates 4. 1 plug and play NW08-32 manual (Ref. 51263541NO) 5. 1 masterpact Plug & Play NW08-32 6. 1 Masterpact NW user manual 7. 1 Micrologic control manual 8. Breaker mismatch protection manual 9. Installation manual OPTIONAL 10. Mechanical interlocking kit (Ref. EF548613) Confidential Property of Schneider Electric | Page 74 37 10/16/2019 Identification The Plug & Play range of circuit breakers and switchdisconnectors offer current ratings from 800 A to 3,200 A. Four different performance levels are available: N1: standard with total discrimination H1: high performance with total discrimination H2: high performance with discrimination limited to instantaneous protection L1: high level of current limiting, with some discrimination Confidential Property of Schneider Electric | Page 75 Identification Rating plate Confidential Property of Schneider Electric | Page 76 38 10/16/2019 Controls and indicators Understanding the controls and indicators of Masterpact NW Circuit Breaker 1 CB open and discharged 2 CB open, charged and not ready to close 3 CB open, charged and ready to close 4 CB closed and discharged 5 CB closed and charged Confidential Property of Schneider Electric | Page 77 Identifying the position of drawout P&P Circuit Breaker Confidential Property of Schneider Electric | Page 78 39 10/16/2019 Charging the circuit breaker • Manual Charging: Automatic Charging: • Pulling the handle down completely • until you hear a “click”. If the MCH gear motor is installed, the spring is automatically charged after closing. Confidential Property of Schneider Electric | Page 79 Parts of the Chassis Arc chute cover Handle grip 2 disconnected position carriage switches Aux. and control unit connection block Door inter lock Pull out hand grip Racking handle storage Confidential Property of Schneider Electric | Page 80 Position indicator Terminal Shield 4 connected position carriage switch Safety shutter Shutter locking block Racking interlock Padlocking facilities for connected or disconnected position Keylocks for connected or disconnected position Racking handle 40 10/16/2019 Parts of circuit breaker Confidential Property of Schneider Electric | Page 81 Rear views of circuit breaker Confidential Property of Schneider Electric | Page 82 41 10/16/2019 Plug and play retrofit operation Preparing the chassis Disconnection of the Masterpact M Circuit Breaker Removal of Masterpact M Circuit Breaker from the chassis Confidential Property of Schneider Electric | Page 83 Plug and play retrofit operation Preparing the chassis Removing the old auxiliary wiring connector plate Confidential Property of Schneider Electric | Page 84 42 10/16/2019 Plug and play retrofit operation Preparing the chassis For devices manufactured before 25 June 1989, modify the original top front plate (2 springs). Confidential Property of Schneider Electric | Page 85 Plug and play retrofit operation Preparing the chassis Checking the version of the top front plate. 1. If the top front plate is having a 2-springs. 2. If equipped with 2-springs it has to me modified. Note: Only one spring is required. Confidential Property of Schneider Electric | Page 86 43 10/16/2019 Plug and play retrofit operation Preparing the chassis Replace the right and left drawer plates Confidential Property of Schneider Electric | Page 87 Plug and play retrofit operation Preparing the chassis Replace the right and left drawer plates Confidential Property of Schneider Electric | Page 88 44 10/16/2019 Plug and play retrofit operation Preparing the chassis Confidential Property of Schneider Electric | Page 89 Plug and play retrofit operation Preparing the chassis Confidential Property of Schneider Electric | Page 90 45 10/16/2019 BREAK Confidential Property of Schneider Electric | Page 91 Workshop…. ECOFITTM Masterpact M - MTZ Plug&Play solution Functional test and micrologic setting Let’s do it safely Confidential Property of Schneider Electric | Page 92 46 10/16/2019 ECOFITTM Masterpact M - MTZ Plug&Play solution Keypoints 1. The Plug&Play solution is only available for drawout circuit breakers rated 800A-3200A. 2. No need for a complete shutdown of the installation, except during the first inspection of the Masterpact M chassis condition or when cleaning and regreasing or replacing the clusters. 3. Remember the 4 points to watch when carrying out a P&P retrofit solution. 4. Be familiar with the parts included in the P&P kit and their usage. 5. Follow the chassis preparation sequence of work and be aware of the cautions. 6. Finish with a functional test of the P&P ACB and the control unit. Confidential Property of Schneider Electric | Page 93 Evaluation • o Your expectations: met or more questions? o What are your 3 main takeaways for Ecofit plug and play? o Module evaluation: Quizz Confidential Property of Schneider Electric | Page 94 47 10/16/2019 LV Ecofit™ Solution Training Introduction The Ecofit™ Solution Offer What to collect in the site? Ecofit™ Plug and Play Solution M-MTZ Installation and Testing of Masterpact P&P Solution Ecofit™ Masterkit Solution Installation and testing of Masterkit Solution Ecofit Compact C – Compact NS Maintenance and associated tools ECOFITTM Masterpact M - MTZ Masterkit solution Accessories Installation kit / Riser block Power isolation Supplied with • Fixing and connection screws • Clamps, door accessories... Auxiliary wiring Confidential Property of Schneider Electric | Page 96 48 10/16/2019 ECOFITTM Masterpact M - MTZ Masterkit solution Advantages No modification of power circuit connections required No modification of switchboard door required (up to 3200A) Solution tested and complying with IEC 60947-2 standard ECOFIT™ Masterpact M Masterkit brings all benefits and the enhanced features of Masterpact MTZ circuit breakers and accessories. The installation requires a shut down to access to the busbars. Once upgraded, the switchboard is fully compatible with the Masterpact MTZ range, opening the door to circuit-breaker interchangeability. Installation down time is reduced because there is no need to modify the busbars. Confidential Property of Schneider Electric | Page 97 ECOFITTM Masterpact M - MTZ Masterkit solution Applications Fixed and withdrawable devices with rear connection only L1 type: only for withdrawable versions on M08 to M20 Overlapping of the busbar connections : Check the overlapping dimensions of the power busbars on the Masterpact M. If the dimensions are higher than B, a Masterkit solution cannot be used unless the busbars are modified. Does not apply for 1000V and DC Applications nor >M32 Neutral on right side Not suitable for Masterpact MTZ with corrosion protection Confidential Property of Schneider Electric | Page 98 49 10/16/2019 WORKSHOP 2 ECOFITTM Masterpact M - MTZ Masterkit identification, part removal and preparation 3. Check your kit. Check the Masterpact MTZ performance plate and compare it with the Masterpact M Note the STR protection settings 4. 5. 6. 7. 8. Remove the existing drawout device. Remove access panels and cubicle door Check the overlapping of the busbar connections Remove the auxiliary wiring and power connections Remove the fixed device or chassis. 9. Prepare the the fixed device or chassis support 10. Prepare the auxiliary wiring 1. 2. Confidential Property of Schneider Electric | Page 99 WORKSHOP 2 ECOFITTM Masterpact M - MTZ Masterkit parts installation, preparation and function checks 1. Position the fixed device or chassis 2. Connect the power connections. 3. Install the Masterpact MTZ in the chassis 4. Connect/disconnect the Masterpact MTZ while checking the smooth operation in the chassis and put in « Test » position. 5. Set the Micrologic X protection settings with noted/saved STR settings 6. Test the Micrologic X with Ecoreach 7. Test the operation of the customers auxiliaries (Motor, Coils, Contacts etc….) 8. Rack out the Masterpact MTZ to the « Disconnected » position. Confidential Property of Schneider Electric | Page 100 50 10/16/2019 LV Ecofit™ Solution Training Introduction The Ecofit™ Solution Offer What to collect in the site? Ecofit™ Plug and Play Solution M-MTZ Installation and Testing of Masterpact P&P Solution Ecofit™ Masterkit Solution Installation and testing of Masterkit Solution Ecofit Compact C – Compact NS Maintenance and associated tools LV ECOFIT™ Compact C – Compact NS Product information • Compact C • Compact NS ECOFITTM Compact C – Compact NS solutions • Plug and Play • Compactkit ECOFITTM Compact C – Compact NS guidelines • Guidelines • Workshop Confidential Property of Schneider Electric | Page 102 51 10/16/2019 Compact C801 – C1251 Commercialised from 1993 to 2007 The Compact C range offered a selection of performance levels : o Ratings from 800 to 1250A. o 3 or 4 pole o Fixed or drawout versions o A single frame size from 800 to 1250 A. o A common height and depth from 800 to 1250 A. Confidential Property of Schneider Electric | Page 103 Compact NS630b – NS1600 Commercialised from 2000 The Compact NS range offered a selection of performance levels : o Ratings from 630 to 1600A. o 3 or 4 pole o Fixed or drawout versions o A single frame size from 630 to 1600 A. o A common height and depth from 630 to 1600 A. Confidential Property of Schneider Electric | Page 104 52 10/16/2019 Compact NS630b – NS1600 Performance levels Confidential Property of Schneider Electric | Page 105 Compact NS630b – NS1600 Control units Basic A E P Confidential Property of Schneider Electric | Page 106 53 10/16/2019 LV ECOFIT™ Compact C – Compact NS solutions Performance level comparisons – circuit breakers Confidential Property of Schneider Electric | Page 107 LV ECOFIT™ Compact C – Compact NS solutions Performance level comparisons – switch disconnectors Confidential Property of Schneider Electric | Page 108 54 10/16/2019 LV ECOFIT™ Compact C – Compact NS solutions Control unit substitution Confidential Property of Schneider Electric | Page 109 Your turn…. Compact C1001 is equivalent to ….Compact NS1000 STR25 is equivalent to …Micrologic 6.0A Compact C1251 is equivalent to… Compact NS1250 Confidential Property of Schneider Electric | Page 110 55 10/16/2019 LV ECOFIT™ Compact C – Compact NS Product information • Compact C • Compact NS ECOFITTM Compact C – Compact NS solutions • Plug and Play • Compactkit ECOFITTM Compact C – Compact NS guidelines • Guidelines • Workshops Confidential Property of Schneider Electric | Page 111 Our Solutions Features and benefits • Features: • LV ECOFIT™ Compact C – Compact NS plug and play solution • Benefits: o For drawout devices (800A-1250A) o Normally only the circuit supplied by the device must be de-energised. o Shutdown of the entire installation is not required (Except for particular cases). o Ultra-fast retrofit solution o Easy to execute with 2 simple operations in less than 30 mins (Does not include LOTO procedures, time for safety precautions,…) o Installation time : 1 - 2 hours Confidential Property of Schneider Electric | Page 112 56 10/16/2019 Our Solutions Features and benefits • Features: • LV ECOFIT™ Compact C – Compact NS Compactkit solution • Benefits: For fixed devices (800A – 1250A). Shutdown required to access the busbars Installation down time is reduced because there is no need to modify the busbars Installation time : 3 to 6 hours Confidential Property of Schneider Electric | Page 113 Our solutions How to identify the device to be replaced 1. 2. 3. 4. 5. 6. Rated insulation voltage. Breaking capacity. Short time withstand. Type of breaker/switch. Rated frequency. Rated operational voltage Confidential Property of Schneider Electric | Page 114 57 10/16/2019 Our Solutions – How to choose What to check during a site survey on a potential Compact C ECOFIT solution offer? o Device characteristics • Rating and performance • No. of poles o Type of control unit o Installation mode (Fixed or Withdrawable) o Condition of the chassis o • Condition and operation of the chassis • Clusters*: If they are in good condition, they can be cleaned and regreased (using the recommended original grease**). If not they must be replaced. Accessories (External current sensor, Source changeover system, interlocks and etc.) *Shutdown is required **Original grease used in manufacturing : Amblygon TA15/2 Confidential Property of Schneider Electric | Page 115 ECOFITTM Compact C – Compact NS P+P restrictions Application restrictions • For all Compact C performance levels except L1 • • P+P is not suitable if the drawout device is adapted with a RED operating handle. •Does not cover 1000V AC applications, 690V AC applications, source changeover, Marine or DC applications not cover industrial environments with high concentration of sulphur compounds SO2. • Compactkit is not suitable for front connection with edgewise connectors or extended rotary handle or CNOMO conversion • If door opens to the left: not suitable for rotary handle operation •Does • Confidential Property of Schneider Electric | Page 116 58 10/16/2019 ECOFITTM Compact C – Compact NS external neutral sensor 3-pole circuit breakers equipped with external neutral current sensor • The external neutral current sensor used with the STR control unit is not compatible with Micrologic control units • A new external neutral current sensor compatible with Compact NS must be installed*. Important Note : In case of distribution network with several circuit breakers with ground fault protection, change all circuit breakers and their external neutral current sensors. *Shutdown is required Confidential Property of Schneider Electric | Page 117 ECOFITTM Compact C – Compact NS solution Description ECOFITTM Compact C Plug & Play solution requires a chassis in full working order If the chassis is bent or damaged, a Plug & Play solution is not possible and the Compactkit solution must be used However, spare parts are still available including: o Set of 2 clusters o Lockable bolt on fixed chassis o Set of fixed female connectors Confidential Property of Schneider Electric | Page 118 59 10/16/2019 Your turn…. Using the catalogue Which Ecofit solution can be ordered to replace your Compact C ? And now, a demonstration of the Ecofit Selector tool Confidential Property of Schneider Electric | Page 119 LV ECOFIT™ Compact C – Compact NS Product information • Compact C • Compact NS ECOFITTM Compact C – Compact NS solutions • Plug and Play • Compactkit ECOFITTM Compact C – Compact NS guidelines • Guidelines • Workshops Confidential Property of Schneider Electric | Page 120 60 10/16/2019 ECOFITTM Compact C – Compact NS Plug and Play solution Condition of existing equipment o Check condition of original chassis : – Carry out a racking test (in and out) with the existing Compact C. • Check for any bent or distorted parts • Remove the existing circuit breaker • Check the contact clusters* *Requires shutdown **Original grease used in manufacturing : Amblygon TA15/2 Confidential Property of Schneider Electric | Page 121 ECOFITTM Compact C – Compact NS Plug and Play solution 2 easy steps to complete the installation 1. Adaptation of the keylock on the Compact C chassis 2. If operation through door, adaptation of the door. Confidential Property of Schneider Electric | Page 122 61 10/16/2019 ECOFITTM Compact C – Compact NS kit solution 2 easy steps to complete the installation Confidential Property of Schneider Electric | Page 123 LUNCH Confidential Property of Schneider Electric | Page 124 62 10/16/2019 WORKSHOP ECOFITTM Compact C – Compact NS Plug&Play solution o What do you need to do to carry out a Plug & Play installation? o Create a method checklist Confidential Property of Schneider Electric | Page 125 ECOFITTM Compact C – Compact NS Plug and Play solution Identification, part removal and replacement 1. 2. 3. 4. Identify your equipment (Kit with options, Compact NS P&P circuit breaker…..) Check the Compact C performance plate and compare it with the Compact NS Note the protection settings Clean and regrease* the moving parts in the chassis 5. Never mix greases, always use the exact grease that was used on the original product. 6. Adaptation of the keylock on the chassis 7. Adaptation of the door *Original grease used in manufacturing : Isoflex Topas L152 Confidential Property of Schneider Electric | Page 126 63 10/16/2019 ECOFITTM Compact C – Compact NS Plug and Play solution Compact NS installation and functional checks • Install the Compact NS in the chassis • Connect/disconnect the Compact NS while checking the smooth operation in the chassis and put in « Test » position. • Set the Micrologic protection settings with noted/saved settings • Test the Micrologic • Test the operation of the customers auxiliaries (Motor, Coils, Contacts etc….) • Rack out the Compact NS to the « Disconnected » position. Confidential Property of Schneider Electric | Page 127 Workshop…. ECOFITTM Compact C – Compact NS Plug&Play solution Now it is your turn to carry out a Plug & Play installation Let’s do it safely Confidential Property of Schneider Electric | Page 128 64 10/16/2019 BREAK Confidential Property of Schneider Electric | Page 129 Workshop…. ECOFITTM Compact C – Compact NS Plug&Play solution Functional test and micrologic setting Let’s do it safely Confidential Property of Schneider Electric | Page 130 65 10/16/2019 ECOFITTM Compact C – Compact NS Plug and Play solution Keypoints Confidential Property of Schneider Electric | Page 131 ECOFITTM Compact C – Compact NS Plug and Play solution Keypoints 1. The Plug&Play solution is only available for drawout circuit breakers rated 800A-1250A. 2. No need for a complete shutdown* of the installation 3. Remember the points to watch when carrying out a P&P retrofit solution. 4. Be familiar with the parts included in the P&P kit and their usage. 5. Follow the chassis preparation sequence of work and be aware of the cautions. 6. Finish with a functional test of the P&P CB and the control unit. *Required if replacing or greasing clusters Confidential Property of Schneider Electric | Page 132 66 10/16/2019 Evaluation • o Your expectations: met or more questions? o What are your 3 main takeaways for Ecofit Compact C plug and play? o Module evaluation: Quizz Confidential Property of Schneider Electric | Page 133 LV Ecofit™ Solution Training Introduction The Ecofit™ Solution Offer What to collect in the site? Ecofit™ Plug and Play Solution M-MTZ Installation and Testing of Masterpact P&P Solution Ecofit™ Masterkit Solution Installation and testing of Masterkit Solution Ecofit Compact C – Compact NS Maintenance and associated tools 67 10/16/2019 The true cost of a power disruption Can you afford it? • Preventive maintenance maximizes your uptime. Financial impact of 1 hour’s production shutdown • Thanks to scheduled equipment outage, less disruption to activities and less stress is generated. • It takes less time to perform preventive maintenance than emergency repair while mitigating the risk of emergency shutdown. Confidential Property of Schneider Electric | Page 135 Maintenance services stakes • Constant availability of equipment • How to avoid failure? Continuity of service • Quick repair • How to diagnose? • How to repair? Cost effectiveness Confidential Property of Schneider Electric | Page 136 68 10/16/2019 The 3 types of maintenance • Corrective maintenance • To repair equipment • Not scheduled (occurs after a failure) • Preventive maintenance • To keep the equipment working (failure is to be avoided) • Scheduled (independently of the real state of the critical components) • Periodic (or systematic) –The operation is done systematically (period of time, or number of cycles) • Condition-based –The operation is done depending on the analysis of a measurement • Predictive maintenance : with monitoring system • To keep the equipment working (failure is to be avoided) • Scheduled regarding the real state of the critical components Confidential Property of Schneider Electric | Page 137 Masterpact MTZ documentation& service tools Confidential Property of Schneider Electric | Page 138 69 10/16/2019 GLOBAL TOOLS and E&P and IT FSRs (2017 Pilots:Portugal,Russia,Poland,Italie ) BFO : • BFO : sales tool - • BFS : part of BFO dedicated services • FSA : Mobile Field Service Application ( Service Max ) customers contacts Opportunities Problems • TIPI : Mobile Technical data base / Spare parts • On site : mobile FSR job management ( IB suite/Maint2 ) OnSite - Technical I.B.management Maintenances procedures Jobs execution reports PRODIAG TOOLS IB inst data Opport.notif. W.O/I.B. S MAX /FSA - TIPI Tech. Infos. Spare parts L.O.M. Confidential Property of Schneider Electric | Page 139 Admisnistrative Installed base Work Order/ calendar Time&expenses MOBILE ( FSR) ON LINE (Planner) BFS : - Installed base Contracts Work Order Waranty Opportunity TIPI server Service tools for Masterpact MTZ • IBSuite • Prodiag Trip Unit • Installed base • Maintenance execution and reports • Diagnosis • Audit & consulting (MP4) • Zen • • • • • • • Manual & Automatic LSIG protection testing Breaking capacity Phase discrimination Earth discrimination Log book with alarms & events (due to test) Injection on primary of the current transformer (Marine) Friendly reports editing for customers • Services database of installed products • Sharing information with: – Third party (Customers) – Services technicians • Prodiag breaker • Circuit breaker diagnosis Confidential Property of Schneider Electric | Page 140 70 10/16/2019 IB suite + Prodiag trip unit Confidential Property of Schneider Electric | Page 141 ProDiag Trip Unit • Test protection functions Confidential Property of Schneider Electric | Page 142 71 10/16/2019 4. IBSuite Job creation ProDiag TripUnit manager (software) Version 1.2.2 min Confidential Property of Schneider Electric | Page 143 4. IBSuite Job creation IBSuite logiciel User guide 2015-04-09 Confidential Property of Schneider Electric | Page 144 72 10/16/2019 4. IBSuite Job creation • Select : new plant Click on “service order management “ Confidential Property of Schneider Electric | Page 145 4. IBSuite Job creation • start service order 1 – Select icone 2 – Service order identification 3 - Select job : Trip Unit 4 - Close 1 2&3 4 Confidential Property of Schneider Electric | Page 146 73 10/16/2019 4. IBSuite Job creation • Launching Site Clic on launch Confidential Property of Schneider Electric | Page 147 4. IBSuite Job creation • Select equipment Select equipment in menu Confidential Property of Schneider Electric | Page 148 74 10/16/2019 4. IBSuite Job creation • Installed base indentification “maintenance” 3 green light necessary Confidential Property of Schneider Electric | Page 149 4. IBSuite Job creation • Plan ProDiag Trip Unit Job Right clic on equipment Select “Plan a job” Confidential Property of Schneider Electric | Page 150 75 10/16/2019 4. IBSuite Job creation • Select Job to do select “trip unit” by lift Confidential Property of Schneider Electric | Page 151 4. IBSuite Job creation Launching selected job Right clic on “execute” Confidential Property of Schneider Electric | Page 152 76 10/16/2019 4. IBSuite Job creation Trip Unit Job is coming … Confidential Property of Schneider Electric | Page 153 4. IBSuite Job creation Welcome inside Trip Unit !!! Confidential Property of Schneider Electric | Page 154 77 10/16/2019 Micrologic X test workshop Test trip curve • Check IBSuite 3.10 is installed • Install ProDiag Trip Unit version 1.2.2 • Launch a job in IBSuite to test the trip unit • Test the trip unit with ProDiag Trip unit • Create a report Confidential Property of Schneider Electric | Page 155 Documentation Shopping Kiosk • The official documentation for the Masterpact MTZ can be found in the Shopping Kiosk. • Documents are available in French, English and Spanish. Confidential Property of Schneider Electric | Page 156 78 10/16/2019 Documentation LV Support Services BOX • There are some documents and information for the Masterpact MTZ that can be found in the LV • Support Services BOX. • You should have received a mail with the link to the BOX. • Here is the link that he sent……………………….. • https://schneider-electric.box.com/s/idg1b7g9dleakaicbogkh9bco4a7tv3j Confidential Property of Schneider Electric | Page 157 Explanation of spare part references MTZ spare parts have SP at the end of the commercial reference: - unique components, - supplied with an IS (Instruction de Services) ex. LV8xxxxxxSP Catalogue numbers & pare parts 2017 Catalogue numbers (without SP): - are sub assemblies made up of unique components created to ease the ordering and configuration of the device OR - are parts shared with other ranges (IFE, I/O, AD Module). ex. 54446 battery module 24VCC -> catalogue number is not referenced into SPEED For Example : 24VDC Standard XF closing release – – Catalogue number LV848481 = 24VDC Standard XF closing release + Terminal Block To order the same as a spare part, you would need to order : LV833659SP = 24VDC Standard XF closing release only LV847849SP = Terminal Block only Confidential Property of Schneider Electric | Page 158 79 10/16/2019 Temporary process to order MTZ spare part out of SPEED ˃ Masterpact MTZ process flow for spare parts is not fully industrialized ˃ Breaker LoB/ Services agreed on a temporary process ˃ Today, SPEED Spare-parts Help Desk Support is the right interface for internal/ external spare part requests toward the Breaker Lob ˃ Objective is to have a fully industrialized process flow for Masterpact MTZ spare parts asap, and remove that temporary process Confidential Property of Schneider Electric | Page 159 Spare-parts Support is the only interface for internal/ external Spare part request toward Partner BU Direct access to help desk support from SPEED catalogue homepage •http://speed.schneider-electric.com Use the process when LV commercial reference is not in SPEED • • • Spare part designation Commercial reference Delivery Address Confidential Property of Schneider Electric | Page 160 80 10/16/2019 Adaptation and Replacement Policy (PAR) • Who is authorized to do what? MTZ PAR table Confidential Property of Schneider Electric | Page 161 The catalogue numbers and spare-parts references • Remind how to order a Masterpact MTZ with digital tools • List all the available commercial references related to Masterpact MTZ • Indicate all the commercial references regarding Masterpact MTZ spare parts Catalogue numbers & spare parts 2017 Confidential Property of Schneider Electric | Page 162 81 10/16/2019 The FIMs • How to dismantle and replace parts Example of FIM Confidential Property of Schneider Electric | Page 163 The Masterpact MTZ User Guide • How to use the circuit-breaker • Troubleshooting MTZ User Guide Confidential Property of Schneider Electric | Page 164 82 10/16/2019 The Micrologic User Guide • How to use the Control Unit • Diagnosis and Maintenance Functions Micrologic X User Guide Confidential Property of Schneider Electric | Page 165 The Maintenance Guide • Define the 3 types of maintenance • Define the 3 levels of preventive maintenance depending on: • Operating conditions • Environment Maintenance Guide Confidential Property of Schneider Electric | Page 166 83 10/16/2019 The 3 levels of preventive maintenance • BASIC (Level II) • ADVANCED (Level III) • EXCLUSIVE 5 (Level IV) Applied for normal operating and environment conditions Confidential Property of Schneider Electric | Page 167 Basic– part 1 • Minor preventive maintenance operations • Carried out by a qualified customer service employee Maintenance Guide Confidential Property of Schneider Electric | Page 168 84 10/16/2019 Basic– part 2 Time required : • 15 minutes typically for a fixed device with all accessories installed • 20 minutes typically for a drawout device with all accessories installed Maintenance Guide Confidential Property of Schneider Electric | Page 169 Advanced • General preventive maintenance operations, carried out by a qualified customer service employee using the tools specified in the manufacturer maintenance instructions Time required : • 1 hour typically for a fixed device with all accessories installed • 1h 20min typically for a drawout device with all accessories installed Maintenance Guide Confidential Property of Schneider Electric | Page 170 85 10/16/2019 Exclusive • Major preventive and corrective maintenance operations • Carried out by the Schneider Electric after-sales support department Maintenance Guide Confidential Property of Schneider Electric | Page 171 Normal operating and environment conditions Confidential Property of Schneider Electric | Page 172 86 10/16/2019 The procedures of preventive maintenance • How to perform preventive maintenance • Each procedure is matched to an operation in the maintenance guide MTZ Maintenance procedures – Levels II & III Confidential Property of Schneider Electric | Page 173 Bridge Field Services / Bridge Front Office • Known issues & knowledge base • Need to know : serial number of breaker + Micrologic Confidential Property of Schneider Electric | Page 174 87 10/16/2019 Exercise #7 Documentation study (1h) • What are the service tools and documentation available for each type of maintenance (for Masterpact MTZ)? • Present them to the group: • What are they useful for? • How to use them? Correction Confidential Property of Schneider Electric | Page 175 Thank you! 88