676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup
1769-SM2 and PowerFlex 4/5 Class Multidrive Setup
676995 | Date Created: 03/19/2015 | Last Updated: 01/16/2019
Access Level: Everyone

Print
Question
How do I setup the 1769-SM2 module and PowerFlex 4/5 class drive?
Environment
PowerFlex 4 (22A)
PowerFlex 40 (22B)
PowerFlex 400 (22C)
PowerFlex 40P (22D)
PowerFlex 4M (22F)
PowerFlex 523 (25A)
PowerFlex 525 (25B)
Answer
The 1769-SM2 Compact I/O to DSI module provides a Compact I/O connection for PowerFlex 4-Class drives. It
can be used with a MicroLogix 1500, CompactLogix, or a remote 1769-based adapter such as the 1769-ADN. Refer
to the PowerFlex 1769-SM2 Compact I/O DSI/Modbus Communications Module
(http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1769-um013_-en-p.pdf), Publication
1769-UM013 for a full list of features and setup options.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995
1/7
7/5/2019
676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup
The following should be set in the PowerFlex 4/40/40P AC drives
Parameter
Value
P36 - [Start Source]
5 (Comm Port)
P38 - [Speed Reference]
5 (Comm Port)
A103 - [Comm Data Rate]
4 (“19.2K”)
A104 - [Comm Node Addr]
1-247 (must be unique)
A107 - [Comm Format]
0 (“RTU 8-N-1”)
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995
2/7
7/5/2019
676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup
The following should be set in the PowerFlex 4M AC drives
Parameter
Value
P106 - [Start Source]
5 (Comm Port)
P108 - [Speed Reference]
5 (Comm Port)
C302 - [Comm Data Rate]
4 (“19.2K”)
C303 - [Comm Node Addr]
1-247 (must be unique)
C306 - [Comm Format]
0 (“RTU 8-N-1”)
The following should be set in the PowerFlex 400 AC drives
Parameter
Value
P36 - [Start Source]
5 (Comm Port)
P38 - [Speed Reference]
5 (Comm Port)
C103 - [Comm Data Rate]
4 (“19.2K”)
C104 - [Comm Node Addr]
1-247 (must be unique)
C102 - [Comm Format]
0 (“RTU 8-N-1”)
The following should be set in the PowerFlex 523/525 AC drives
Parameter
Value
P46 - [Start Source 1]
3 (Serial/DSI)
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995
3/7
7/5/2019
676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup
P47 - [Speed Reference 1]
3 (Serial/DSI)
C123 - [RS485 Data Rate]
4 (“19.2K”)
C124 - [Comm Node Addr]
1-247 (must be unique)
C127 - [RS485 Format]
0 (“RTU 8-N-1”)
The following should be setup for the 1769-SM2 module. Please note whether you are using Controller or
Parameter mode:
Set the 2 switches on the card. One is for single vs multi-drive mode. The other is for controller vs. parameter setup.
Note: This switch sets ALL Channels to mulit or single drive mode. If one channel has more than 1 drive and
another only has 2, set to multidrive then set that channel's DSI I/O Cfg to 0.
For Controller Setting:
The 1769-SM2 uses the configuration data downloaded from the controller on power-up and when the controller is
placed in run mode. The data is configured using RSLogix 500, or RSLogix 5000/Studio 5000. ( ) are for
PowerFlex 520 parameters. If no description, this is a user preference setting.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995
4/7
7/5/2019
676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup
Parameter Name
CH1
Idle Action
Word 0
Word 14 Word 28
Flt Cfg Logic
Word 1
Word 15 Word 29
Flt Cfg Ref
Word 2
Word 16 Word 30
DSI I/O Cfg
Word 3
Word 17 Word 31
Drive 0 Addr
Word 4
Word 18 Word 32 Set this to the unique address of drive 1. Should match A104 (C124)
Drive 1 Addr
Word 5
Word 19 Word 33 Set this to the unique address of drive 2. Should match A104 (C124)
Drive 2 Addr
Word 6
Word 20 Word 34 Set this to the unique address of drive 3. Should match A104 (C124)
Drive 3 Addr
Word 7
Word 21 Word 35 Set this to the unique address of drive 4. Should match A104 (C124)
Drive 4 Addr
Word 8
Word 22 Word 36 Set this to the unique address of drive 5. Should match A104 (C124)
RTU Baud Rate
Word 9
Word 23 Word 37
CH2
CH3
RTU Format
Word 10 Word 24 Word 38
RTU Rx Delay
Word 11 Word 25 Word 39
RTU Tx Delay
Word 12 Word 26 Word 40
RTU Msg Timeout
Word 13 Word 27 Word 41
Description
Set this to (number of drives - 1). Ex. If 3 drives are used enter 2.
Set this to a value of '1' for 19.2k Baud
Set this to a value of '0' for 8-N-1
Example below
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995
5/7
7/5/2019
676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup
For Parameter Setup:
The 1769-SM2 uses its internal parameter settings to configure the module. The data is configured using an optional,
external PowerFlex 4-Class HIM, DriveExplorer, or DriveExecutive. The following parameters are the minimum to be set
up. There are more that are user preference. The parameters below are for Ch1. Use the respective parameters for your
Channel. () denotes a 520-series parameter number.
1. Parameter 07 [DSI I/O Cfg 1] - Set this to (number of drives - 1). Ex. If 3 drives are used enter 2
2. Parameter 09 [Drive 0 Addr 1] - Set this to the unique address of drive 1. Should match A104 (C124) in drive 1
3. Parameter 10 [Drive 1 Addr 1] - Set this to the unique address of drive 2. Should match A104 (C124) in drive 2
4. Parameter 11 [Drive 2 Addr 1] - Set this to the unique address of drive 3. Should match A104 (C124) in drive 3
5. Parameter 12 [Drive 3 Addr 1] - Set this to the unique address of drive 4. Should match A104 (C124) in drive 4
6. Parameter 13 [Drive 4 Addr 1] - Set this to the unique address of drive 5. Should match A104 (C124) in drive 5
7. Parameter 14 [RTU Baud Rate 1] - Set this to a value of '1' for 19.2k Baud
8. Parameter 15 [RTU Format 1] - Set this to a value of '0' for 8-N-1
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995
6/7
7/5/2019
676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup
Power cycle the system (both the Drives and controller) and put the controller in Run mode after these are set. The
SM2 module CHx should have a solid green LED now.
Note: It is not possible to connect to the drive via drive software by bridging across the 1769-SM2 module
Attachments
Multidrive Mode.pdf (367596 bytes) (//rockwellautomation.custhelp.com/ci/fattach/get/1154844/0/filename/Multidrive
Mode.pdf)
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or subjects and
is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not intended to constitute
application, design, software or other professional engineering advice or services. Before making any decision or taking
any action, which might affect your equipment, you should consult a qualified professional advisor.
ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY
OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE
DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS
"AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT,
INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION
HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.
ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF
THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain
jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995