7/5/2019 676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup 676995 | Date Created: 03/19/2015 | Last Updated: 01/16/2019 Access Level: Everyone Print Question How do I setup the 1769-SM2 module and PowerFlex 4/5 class drive? Environment PowerFlex 4 (22A) PowerFlex 40 (22B) PowerFlex 400 (22C) PowerFlex 40P (22D) PowerFlex 4M (22F) PowerFlex 523 (25A) PowerFlex 525 (25B) Answer The 1769-SM2 Compact I/O to DSI module provides a Compact I/O connection for PowerFlex 4-Class drives. It can be used with a MicroLogix 1500, CompactLogix, or a remote 1769-based adapter such as the 1769-ADN. Refer to the PowerFlex 1769-SM2 Compact I/O DSI/Modbus Communications Module (http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1769-um013_-en-p.pdf), Publication 1769-UM013 for a full list of features and setup options. https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995 1/7 7/5/2019 676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup The following should be set in the PowerFlex 4/40/40P AC drives Parameter Value P36 - [Start Source] 5 (Comm Port) P38 - [Speed Reference] 5 (Comm Port) A103 - [Comm Data Rate] 4 (“19.2K”) A104 - [Comm Node Addr] 1-247 (must be unique) A107 - [Comm Format] 0 (“RTU 8-N-1”) https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995 2/7 7/5/2019 676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup The following should be set in the PowerFlex 4M AC drives Parameter Value P106 - [Start Source] 5 (Comm Port) P108 - [Speed Reference] 5 (Comm Port) C302 - [Comm Data Rate] 4 (“19.2K”) C303 - [Comm Node Addr] 1-247 (must be unique) C306 - [Comm Format] 0 (“RTU 8-N-1”) The following should be set in the PowerFlex 400 AC drives Parameter Value P36 - [Start Source] 5 (Comm Port) P38 - [Speed Reference] 5 (Comm Port) C103 - [Comm Data Rate] 4 (“19.2K”) C104 - [Comm Node Addr] 1-247 (must be unique) C102 - [Comm Format] 0 (“RTU 8-N-1”) The following should be set in the PowerFlex 523/525 AC drives Parameter Value P46 - [Start Source 1] 3 (Serial/DSI) https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995 3/7 7/5/2019 676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup P47 - [Speed Reference 1] 3 (Serial/DSI) C123 - [RS485 Data Rate] 4 (“19.2K”) C124 - [Comm Node Addr] 1-247 (must be unique) C127 - [RS485 Format] 0 (“RTU 8-N-1”) The following should be setup for the 1769-SM2 module. Please note whether you are using Controller or Parameter mode: Set the 2 switches on the card. One is for single vs multi-drive mode. The other is for controller vs. parameter setup. Note: This switch sets ALL Channels to mulit or single drive mode. If one channel has more than 1 drive and another only has 2, set to multidrive then set that channel's DSI I/O Cfg to 0. For Controller Setting: The 1769-SM2 uses the configuration data downloaded from the controller on power-up and when the controller is placed in run mode. The data is configured using RSLogix 500, or RSLogix 5000/Studio 5000. ( ) are for PowerFlex 520 parameters. If no description, this is a user preference setting. https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995 4/7 7/5/2019 676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup Parameter Name CH1 Idle Action Word 0 Word 14 Word 28 Flt Cfg Logic Word 1 Word 15 Word 29 Flt Cfg Ref Word 2 Word 16 Word 30 DSI I/O Cfg Word 3 Word 17 Word 31 Drive 0 Addr Word 4 Word 18 Word 32 Set this to the unique address of drive 1. Should match A104 (C124) Drive 1 Addr Word 5 Word 19 Word 33 Set this to the unique address of drive 2. Should match A104 (C124) Drive 2 Addr Word 6 Word 20 Word 34 Set this to the unique address of drive 3. Should match A104 (C124) Drive 3 Addr Word 7 Word 21 Word 35 Set this to the unique address of drive 4. Should match A104 (C124) Drive 4 Addr Word 8 Word 22 Word 36 Set this to the unique address of drive 5. Should match A104 (C124) RTU Baud Rate Word 9 Word 23 Word 37 CH2 CH3 RTU Format Word 10 Word 24 Word 38 RTU Rx Delay Word 11 Word 25 Word 39 RTU Tx Delay Word 12 Word 26 Word 40 RTU Msg Timeout Word 13 Word 27 Word 41 Description Set this to (number of drives - 1). Ex. If 3 drives are used enter 2. Set this to a value of '1' for 19.2k Baud Set this to a value of '0' for 8-N-1 Example below https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995 5/7 7/5/2019 676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup For Parameter Setup: The 1769-SM2 uses its internal parameter settings to configure the module. The data is configured using an optional, external PowerFlex 4-Class HIM, DriveExplorer, or DriveExecutive. The following parameters are the minimum to be set up. There are more that are user preference. The parameters below are for Ch1. Use the respective parameters for your Channel. () denotes a 520-series parameter number. 1. Parameter 07 [DSI I/O Cfg 1] - Set this to (number of drives - 1). Ex. If 3 drives are used enter 2 2. Parameter 09 [Drive 0 Addr 1] - Set this to the unique address of drive 1. Should match A104 (C124) in drive 1 3. Parameter 10 [Drive 1 Addr 1] - Set this to the unique address of drive 2. Should match A104 (C124) in drive 2 4. Parameter 11 [Drive 2 Addr 1] - Set this to the unique address of drive 3. Should match A104 (C124) in drive 3 5. Parameter 12 [Drive 3 Addr 1] - Set this to the unique address of drive 4. Should match A104 (C124) in drive 4 6. Parameter 13 [Drive 4 Addr 1] - Set this to the unique address of drive 5. Should match A104 (C124) in drive 5 7. Parameter 14 [RTU Baud Rate 1] - Set this to a value of '1' for 19.2k Baud 8. Parameter 15 [RTU Format 1] - Set this to a value of '0' for 8-N-1 https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995 6/7 7/5/2019 676995 - 1769-SM2 and PowerFlex 4/5 Class Multidrive Setup Power cycle the system (both the Drives and controller) and put the controller in Run mode after these are set. The SM2 module CHx should have a solid green LED now. Note: It is not possible to connect to the drive via drive software by bridging across the 1769-SM2 module Attachments Multidrive Mode.pdf (367596 bytes) (//rockwellautomation.custhelp.com/ci/fattach/get/1154844/0/filename/Multidrive Mode.pdf) DISCLAIMER This knowledge base web site is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not intended to constitute application, design, software or other professional engineering advice or services. Before making any decision or taking any action, which might affect your equipment, you should consult a qualified professional advisor. ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES. ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you. https://rockwellautomation.custhelp.com/app/answers/detail/a_id/676995 7/7