IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 5, MAY 2012 2367 Improved Active Frequency Drift Anti-islanding Detection Method for Grid Connected Photovoltaic Systems Ahmad Yafaoui, Student Member, IEEE, Bin Wu, Fellow, IEEE, and Samir Kouro, Member, IEEE Abstract—As more distributed generators join the utility grid, the concern of possible undetected islanding operation increases. This concern is due to the safety hazards this phenomenon imposes on the personnel and equipment. Passive anti-islanding detection methods monitor grid parameters to detect islanding, whereas active methods inject a perturbation into the current waveform to drive these parameters out of limit when islanding occurs. The performance of active methods, such as conventional active frequency drift (AFD), is limited by the amount of total harmonic distortion (THD) they inject into the grid, which defines its nondetection zone. In this paper, an improved AFD anti-islanding method is presented based on a different current distortion injection waveform. The proposed method generates 30% less THD compared to classic AFD, resulting in faster island detection and improved nondetection zone. The performance of the proposed method is derived analytically, simulated using Matlab and verified experimentally using a prototype setup. A single-phase grid-tied photovoltaic distributed generation system is used for the simulation and experimental setup, and considered as potential application. Index Terms—Active frequency drift, anti-islanding detection, distributed generation, photovoltaic energy conversion. I. INTRODUCTION HE increase in penetration levels of distributed generation (DG) into the grid, such as photovoltaic and wind energy systems, has raised the concern about undetected islanding operation [1]–[3]. Islanding is a phenomenon in which the grid-tied inverter of a distributed generation system and some of the local loads are disconnected from the rest of the grid. If this condition is not detected and the generation (e.g., from a photovoltaic or wind energy source) remains operative, the isolated DG system will stay energized by the inverter [4]–[6]. This situation is undesirable since it is a potentially dangerous condition for the maintenance personnel and may cause damage to the inverter and loads in the case of unsynchronized reconnection of the grid due to phase difference between the grid and inverter voltage [7], [8]. T Manuscript received April 28, 2011; revised July 22, 2011; accepted September 25, 2011 Date of current version February 27, 2012. Recommended for publication by Associate Editor Pedro Rodriguez. A. Yafaoui and B. Wu are with the Electrical and Computer Engineering Department, Ryerson University, Toronto, ON M5B2K3 Canada (e-mail: yafaoui.ahmad@ryerson.ca; bwu@ee.ryerson.ca). S. Kouro is with the Electronics Engineering Department, Universidad Tecnica Federico Santa Maria,Valparaiso 1680, Chile (e-mail:samir. kouro@ieee.org.). Digital Object Identifier 10.1109/TPEL.2011.2171997 The IEEE Standard 929 and Standard 1547 demand the use of an anti-islanding detection feature by the grid connected inverter [9], [10]. The standards also suggest test procedures and set the limits for the grid parameters, as shown in Table I [9]–[11]. Passive and active methods have been proposed to detect the islanding of the system and force the inverter to cease energizing the loads. Passive methods are those methods which use the grid parameters and measurements (voltage, frequency, harmonic content, etc.) in order to detect islanding operation . The boundary limits of these parameters define the nondetection zone (NDZ). If the local loads have similar power capacity of the DG system, i.e., all the generated power is consumed locally, then voltage and current levels at the point of common coupling (PCC) will only vary slightly when islanding occurs. The system variables will be then within the boundary limits and the islanding condition will remain undetected. Passive methods have, therefore, a large NDZ. Nevertheless, passive methods are conceptually simple and easy to implement and do not introduce any change to the power quality of the system. In order to reduce the NDZ, particularly in cases where the local loads are close in capacity to the DG system, active detection methods have been proposed. In active methods, a perturbation is injected in the current waveform to drive one of the system parameters out of its limits during islanding operation [12], [13]. Among the active methods the active frequency drift (AFD) method has drawn increased attention in literature because of its capability to effectively detect islanding with a smaller NDZ [14]–[18]. In AFD, a perturbation is injected to the current waveform that makes the inverter drift the frequency in case of islanding operation, which does not happen when the grid is available. The frequency drift can then be easily detected with the boundary limits. Unfortunately, the smaller NDZ obtained with AFD compared to passive methods comes at expense of increased THD which degrades the power quality provided by the grid-tied converter [19]. The loss in power quality is inherent to AFD due to the distortion injected to the current waveform. In order to minimize the impact on power quality, several variations of the AFD method had been suggested in literature like the AFD with pulsation of chopping fraction [14]. However, these methods introduce a design compromise or tradeoff between the amount of distortion added to the system and the reduction of the NDZ. In this work, a new distortion injection to the current waveform is presented and analyzed. The proposed perturbation introduces lower THD to the current waveform, while improving 0885-8993/$26.00 © 2011 IEEE 2368 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 5, MAY 2012 TABLE I GRID PARAMETER LIMITS STANDARDS the NDZ compared to AFD. The performance of the proposed method is derived analytically and simulated using MATLAB. Validation of the analysis and simulation is obtained experimentally using a prototype setup. A single phase grid-tied photovoltaic distributed generation system with local RLC loads, as suggested in the IEEE Standard 929 and IEEE Standard 1547.1, is considered as application for the simulation and experimental setup. II. ACTIVE FREQUENCY DRIFT METHOD OVERVIEW In order to better understand the proposed method, first an overview of the classic AFD method is presented. This analysis is also necessary for comparison purposes in later sections of the paper. The AFD method is based on the injection of a current waveform distortion to the original reference current of the inverter, to force a frequency drift in case of islanding operation. By introducing a zero conduction time tz at the end of each half cycle, as shown in Fig. 1, the phase angle of the fundamental component of the current is shifted. During normal grid connected operation the inverter usually operates with unity power factor and is synchronized to the grid voltage and will operate at grid frequency. In islanding operation, the added distortion to the current will produce a permanent drift in the operating frequency toward the local load resonance frequency in order to keep unity power factor. This drift will eventually reach the frequency boundary limits set for islanding detection. The dead Fig. 1. AFD method: (a) Original reference current and AFD reference current waveforms. (b) Original reference current and injected current waveforms. time tz in which zero current is forced and the period of the original signal T can be related to each other to define the chopping factor Cf used to perturb the waveform as Cf = 2tz . T (1) YAFAOUI et al.: IMPROVED ACTIVE FREQUENCY DRIFT ANTI-ISLANDING DETECTION METHOD The AFD reference current waveform shown in Fig. 1(a) can be defined as: ⎧ ⎪ I sin(2π f´t) → 0 ≤ ωt < π − tz ⎪ ⎪ ⎪ ⎨0 → π − tz ≤ ωt < π (2) iaf d (t) = ´ ⎪ I sin(2π f t) → π ≤ ωt < 2π − t ⎪ z ⎪ ⎪ ⎩ 0 → 2π − tz ≤ ωt ≤ 2π 1 where f´ = f ( 1−C ). f Basically, the chopping factor defines the amount of drift introduced to the frequency f . Note that since the current waveform has a different frequency f´, the vertical axis is shifted to facilitate the zero current period tz . The distortion introduced by tz can be deducted from the original reference current, as shown in Fig 1(b). Note that, according to (1), the greater tz , the greater the chopping factor; hence, a larger perturbation is introduced to the current. In contrast, if tz = 0, from (1) Cf is also zero, and replacing in (2) the AFD reference current waveform is equal to the original reference current waveform (iaf d (t) = I sin(2πf t)). When this modified waveform is applied to an isolated DG system with an RLC load, the frequency of the load will change according to the following equation [20]–[22] : −1 = 0.5πCf . (3) arg R−1 + (jωL)−1 + jωC This method is effective for resistive loads but has a larger NDZ for some RLC load combinations. To overcome this problem positive feedback AFD methods have been proposed [23]. These improve the NDZ for different load types, but still affect the power quality introducing a higher THD. A. Parameter Relations for Islanding Detection Analysis Undetected islanding can happen when there is a balance between the power (both active and reactive) delivered by the inverters and consumed by the local loads of the DG system. A mismatch would lead to a change in the amplitude, frequency, or both of the load voltage, consequently resulting in islanding detection. This mismatch can be forced by injecting reactive power to the system by introducing a distortion to the current waveform. The relationship between the reactive power mismatch ∆Q and the frequency threshold can be obtained by [24] 2 2 f f ∆Q < Qf · 1 − < (4) Qf · 1 − fm in P fm ax where P is the active power, f the grid frequency, fm in , fm ax under/over frequency threshold, and Qf is the quality factor. The quality factor is defined as the reactive power stored in L or C divided by the active power consumed in R. In order to drive the load frequency out of limit faster and with smaller NDZ, a larger ∆Q/P is needed. With the limit values of the frequency specified in Table I, fm in = 59.3 Hz, fm ax = 60.5, f = 60, and a quality factor of Qf = 2.5, (4) is in 2369 the range of −5.95% ≤ ∆Q ≤ 4.11%. P (5) For nonsinusoidal waveforms the active power is defined in IEEE Standard 1459-2010 [25] as P = V · I1 · cos(φ1 ) (6) where I1 and φ1 are the rms value and the phase angle of the fundamental waveform, respectively. On the other hand, the reactive power is defined as Q = V · I1 · sin(φ1 ) (7) Q = tan(φ1 ). P (8) from which Equation (8) shows the relation between the reactive power generated by the distortion of the current waveform and the phase angle of the fundamental waveform. In the AFD method, a distortion is added to the current, which forces the fundamental component of the current to shift by angle φ1 . It is known from [14] that Q/P = T HD for the AFD method. Consequently, increasing the reactive power injected into the load to reduce the NDZ will increase the THD of the current wave form. B. THD Problem in AFD Method For the AFD method to be effective, Cf needs to be fairly large, which directly affects the THD of the current waveform [12], [23]. The relationship between THD and Cf has been reported to be linear [14], [23]. The maximum allowable Cf is limited by the maximum THD (<5% according to Table I). It is mentioned that a Cf of 0.046 results in a THD of 4.88% [17]. Hence, like most of the active methods, the AFD reduces the quality of the power delivered to the grid. Generally speaking, the larger the chopping factor, the smaller the NDZ and the higher the THD for AFD based methods. The injected current waveform used in AFD shown in Fig. 1(b), introduces high low-order frequency harmonics to the original current waveform. This can be seen from the fact that the injected current waveform changes slowly over half cycle of the original reference current. In other words, the phase shift of the fundamental component (φ1 ) is achieved gradually over half cycle, which in consequence translates to high low-order harmonics. This has motivated the present work to find different perturbations that lead to a reduced THD reference current but with same or better NDZ features. III. IMPROVED AFD ANTI-ISLANDING METHOD Instead of introducing a gradual change in the current waveform over half cycle, a sudden change can also introduce the necessary phase shift of the fundamental component (φ1 ) while introducing less THD. The following section describes the proposed waveform, which is analyzed analytically and compared to classic AFD. 2370 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 5, MAY 2012 Fig. 3. Fig. 2. Proposed improved AFD method: (a) Original reference current and proposed injected current waveforms. (b) Original reference current and proposed reference current waveforms. An effective way to shift the fundamental component phase angle of a sine wave is by introducing a step change in the amplitude in the 1st and 3rd or 2nd and 4th quarters of the waveform. This perturbation injection and the resulting reference waveform are illustrated in Fig. 2(a) and (b), respectively, for the case in which the 2nd and 4th quarter are considered. The resulting reference current waveform is defined by ⎧ I sin(ωt) → 0 ≤ ωt < π/2 ⎪ ⎪ ⎪ ⎨ I sin(ωt) − KI → π/2 ≤ ωt < π (9) i(t) = ⎪ I sin(ωt) → π ≤ ωt < 3π/2 ⎪ ⎪ ⎩ I sin(ωt) + KI → 3π/2 ≤ ωt ≤ 2π where I is the current amplitude, ω the grid frequency, and K the distortion factor. In order to analyze the harmonic contents and the phase angle of proposed current waveform, the Fourier series coefficients of the fundamental components are found a1 = ∞ a0 + [an cos(ωn t) + bn sin(ωn t)] 2 n=1 (10) 2KI π (11) b1 = I 1 − I1 = I 1+ φ1 = tan−1 2K π (12) 8K 2 4K − 2 π π (13) a1 b1 = tan−1 2K π − 2K The rms value of the current waveform is defined as 2π 1 i2 (t)dt Irm s = 2π 0 (14) where a1 and b1 are the cosine and sine components of the series, and I1 and φ1 are the amplitude, and displacement angle of the fundamental waveform, respectively. (15) then the rms value for the proposed current waveform can be obtained replacing (9) in (15), which yields 1 2K K2 − + . 2 π 2 Irm s = I · A. Proposed Current Waveform Distortion F (t) = THD versus Q/P for both methods. (16) In addition, the THD of the current waveform is defined as 2 2 Irm I1 s − I1rm s (17) THD = , with I1rm s = √ . I1rm s 2 Replacing (16) and (13) in (17) yields THD = π2 K 2 (π 2 − 8) . − 4πK + 8K 2 (18) In addition, by replacing in (8) the terms (11), (12), and (14), the Q/P ratio of the proposed waveform can be computed as 2K Q = . P π − 2K (19) Using (18) and (19) the THD and the Q/P ratio can be calculated for different distortion factors (K). For example, with a distortion factor of K = 0.075 the THD of the current waveform is 3.42% and a Q/P ratio of 5%. When compared with traditional AFD, in order to generate the same Q/P ratio of 5%, the THD of the AFD current waveform increases to 5% (more than 30% increase in distortion). Fig. 3 shows the THD versus Q/P curve for both methods at different values of their respective distortion factors K and Cf . It is obvious that the proposed method always generates less harmonic distortion at any given Q/P value. Based on the above analysis, it can be concluded that: i) The proposed method can achieve the same results of the conventional AFD method with about 30% reduction in THD. ii) Alternatively, if the maximum allowed THD is considered to be 5%, which is obtained with K = 0.108 for a Q/P = 7.4% in the proposed method, then compared to the traditional AFD method which with Cf = 0.046 it will generate Q/P = 4.8%, there is about a 50% increase in YAFAOUI et al.: IMPROVED ACTIVE FREQUENCY DRIFT ANTI-ISLANDING DETECTION METHOD Fig. 5. 2371 DG photovoltaic grid connected system with local RLC load. TABLE 2 DG CIRCUIT PARAMETERS Fig. 4. Practical proposed improved AFD method: (a) Original reference current and practical injected current waveform (b) Original reference current and practical reference current waveform. reactive power injected to the system resulting in better islanding detection. IV. IMPLEMENTED WAVEFORM The proposed current waveform illustrated in Fig. 2 has one drawback: The fast changes in current, when crossing zero, are difficult to implement in practice. The current controller is not able to follow this sudden change in reference accurately. Therefore, a slight modification is introduced to the proposed waveform which eliminates the fast change in current at zero crossing. The proposed practical current injection and the resulting reference current waveform are shown in Fig. 4(a) and (b), respectively. Note that the original motivation, which is to concentrate the perturbation in the 2nd and 4th quarter of the waveform still holds. The resulting waveform can be defined by ⎧ I sin(ωt) → 0 ≤ ωt < π/2 ⎪ ⎪ ⎪ ⎪ ⎪ I sin(ωt) − KI → π/2 ≤ ωt < π − α ⎪ ⎪ ⎪ ⎪ ⎨0 → π − α ≤ ωt < π (20) í(t) = ⎪ I sin(ωt) → π ≤ ωt < 3π/2 ⎪ ⎪ ⎪ ⎪ ⎪ I sin(ωt) + KI → 3π/2 ≤ ωt < 2π − α ⎪ ⎪ ⎪ ⎩ 0 → 2π − α ≤ ωt ≤ 2π where α = arcsin(K). For this new current waveform, the Fourier coefficients and the rms value can be computed following same steps as for previous waveform, which yields K2 I 2KI − π π √ arcsin(K) K 1 − K2 ′ b1 = I 1 − − π π a′1 = ′ Irm s = I· √ 3K 1 − K 2 arcsin(K) · (1 + 2K 2 ) 1 K2 + − − . 2 2 2π 2π (23) Since the values for the distortion factor are small (K ≤ 0.1) the quadratic terms K 2 ≪ 1 can be neglected. In addition, for small values of K the following holds: arcsin(K) ∼ = K. Replacing both approximations in (21), (22), and (23) yields to the same results obtained for the originally proposed waveform from (11) to (19). In summary, the small modification introduced to eliminate the fast change in current at zero crossing and make the proposed waveform practical, does not affect the THD and NDZ achieved with the originally proposed waveform. V. SIMULATION RESULTS In order to verify the proposed method, a single phase photo(21) voltaic distributed generation system with a local RLC load has been considered. The power circuit of the system is shown in (22) Fig. 5. The system parameters are listed in Table II. The simulations for both AFD and the proposed method were implemented 2372 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 5, MAY 2012 Fig. 8. Fig. 6. Inverter current: a) for AFD with C f = 0.046, b) for original proposed method with K = 0.08, c) for practical proposed method with K = 0.08. NDZ of both ADF and proposed methods for different C n o rm . than with classic AFD. Again, these results are consistent with the ones obtained analytically in previous section, thus verifying the validity of (10)–(22). This also confirms that the approximation introduced by the practical implementation waveform of the proposed method does not affect the power quality and is a valid approach to overcome the drawback of the original current injection waveform. When the proposed waveform is applied to an RLC load, the frequency at the PCC will change during islanding until the load phase angle is equal to the displacement angle of the fundamental waveform φ1 given in (14) as shown below arg R−1 + (jωL)−1 + jωC = tan−1 Fig. 7. Inverter current spectrum: (a) for AFD with C f = 0.046, (b) for original proposed method with K = 0.08, for practical proposed method with K = 0.08. in Matlab/Simulink platform together with over/under voltage and over/under frequency relays. The active frequency drift method was simulated with chopping factor of Cf = 0.046. The resulting current waveform is shown in Fig. 6(a). The simulation of proposed method was performed considering a distortion factor of K = 0.08. These values were chosen since they generate the same Q/P as shown before. The resulting current waveforms for both the original and practical cases are shown in Fig. 6(b) and (c), respectively. The spectra of the three current waveforms are compared in Fig. 7 along with their THD values. Note that the fundamental component amplitude in Fig. 7 corresponds to 100% and appears truncated to show in more detail the harmonic content. The THD value obtained for classic AFD current waveform is found to be 4.90% which coincides with the data given in [14] and discussed in the above analysis. The proposed methods resulted in current waveforms with THD of 3.65% and 3.64%, respectively, around a 30% lower 2K π − 2K . (24) The NDZ of the proposed method can be obtained using (24). Fig. 8 shows the NDZ of both AFD and the proposed method mapped into the load space that is characterized by the quality factor Qf and the normalized load capacitance Cnorm . This mapping method relates the NDZ to the IEEE Standard 929-2000 requirements in an efficient way [21]. This graph is obtained for AFD method with Cf = 0.046 and the proposed method with K = 0.105 which both generate same THD = 4.9%. Although both methods have same NDZ shape in relation to the quality factor, the proposed method has a higher NDZ, making the islanding formation in the vicinity of balanced load more unlikely. This holds particularly for Qf <5, which is the usual case in practical applications. The simulation of the islanding phenomena is performed with load capacitor C = 139.2 µF whose normalized capacitance is Cnorm = 1.01, and Qf = 2.5, which is one of the load combinations required by IEEE Standard 929-2000 to test against islanding. This load combination is a point shown in Fig. 8 that lies inside the NDZ of the AFD but outside the NDZ of the proposed method. Here also AFD method with Cf = 0.046 and proposed method with K = 0.105 were used. The utility breaker was opened after four cycles to simulate the grid disconnection. As expected, the AFD method fails to detect the islanding and the inverter continues to energize the load beyond the 2 s limit, as shown in Fig. 9(a). Whereas the proposed method forces the frequency of the PCC to increase above the limit in nine cycles which triggers the over frequency relay and causes the islanding YAFAOUI et al.: IMPROVED ACTIVE FREQUENCY DRIFT ANTI-ISLANDING DETECTION METHOD Fig. 11. 2373 Experimental setup power circuit diagram. Fig. 9. Voltage and current at PCC: a) for AFD with C f = 0.046, b) for proposed method with K = 0.105 . Fig. 12. Experimental voltage and current waveforms together with frequency spectrum for the AFD method with C f = 0.046. Fig. 10. System frequency evolution for AFD with C f = 0.046 and proposed method with K = 0.105. operation to be detected, as shown in Fig. 9(b). This effect can be more clearly appreciated in the evolution of the frequency of the system for both methods shown together for comparison in Fig. 10. VI. EXPERIMENTAL RESULTS An experimental prototype has been built in order to test the proposed method. The corresponding power circuit of the setup is shown in Fig. 11. The grid-tied inverter is constructed as a MOSFET H-bridge followed by an LC filter (L = 1.3 mH and C = 3 µF), and connected to an RLC load. A digital signal processor board (TMS320F2812) is used to generate a 20 KHz unipolar PWM gate signals and to implement a proportional resonant current controller which is a typical controller for single phase ac systems to ensure zero steady state error [26], [27] . Fig. 12 shows the voltage and current waveform of the AFD method with a chopping factor of Cf = 0.046, the THD in the current was measured using the power analyzer YOKOGAWA PZ4000 to be 5.16%. The measured active and reactive power were P = 334 W and Q = 17.4 VAR, respectively. Also the frequency spectrum of the current waveform is shown, the third and fifth harmonics are the dominant harmonics in accordance with the simulation results shown in Fig. 7 Fig. 13 shows the voltage and current waveform of the proposed method with K = 0.08. The THD of the current was measured to be 3.91%. The measured active and reactive power were P = 335 W and Q = 18.2 VAR, respectively. The experimental results shown in Figs. 12 and 13 match the simulated results of Figs. 6 and 7 for the AFD and the proposed method, respectively. Note that when both methods generate the same amount of reactive power to shift the frequency in case of islanding, the proposed method features a lower THD than the AFD method, as demonstrated analytically and the frequency spectrum of the current waveform of the proposed method has lower third and fifth harmonics as has been shown previously in the simulation results shown in Fig. 7. 2374 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 5, MAY 2012 Fig. 15. Islanding test result for the proposed method with K = 0.105. Fig. 16. = 1. Islanding test result for the AFD method with C f = 0.046 and Q f Fig. 13. Experimental voltage and current waveforms together with frequency spectrum for the proposed method with K = 0.08. Fig. 14. Islanding test result for the AFD method with C f = 0.046. The islanding detection test is carried first in accordance with IEEE 929-2000 standard with load quality factor Qf set to 2.5 and with the same parameters as the ones used for simulation and listed in Table II. The AFD method chopping factor is Cf = 0.046 . As can be seen from Fig. 14, the inverter fails to detect the islanding after the grid is disconnected and continues to energize the load beyond the 2 s limit. The same test is repeated with the proposed method and distortion factor is set to K = 0.105, which results the same amount of harmonic distortion as the AFD method with Cf = 0.046. The inverter detects islanding operation as the load frequency increases beyond the limit (60.5 Hz) and discontinues energizing the load, as can be seen from Fig. 15. The second islanding test is carried with the load quality factor Qf set to 1.0 and Cnorm = 1.02 as required by IEEE 1547.1 standard. Note that this operating point is outside the NDZ of both methods, as can be seen from Fig. 8. The AFD method chopping factor is set to Cf = 0.046 and the proposed method distortion factor is set to K = 0.105. It is clear from Figs. 16 and 17 that the proposed method is faster in detecting the islanding due to the extra reactive power injected in the load Fig. 17. Islanding test result for the proposed method with K = 0.105 and Q f = 1. during islanding. Note that there is a three cycle delay after the frequency reaches the limit before the inverter stops, which is necessary to eliminate false tripping. VII. CONCLUSION This paper presents an improved active anti-islanding detection method that can detect islanding with less total harmonic distortion compared to the conventional AFD method. The rms value and the Fourier series coefficients of the current waveform of the proposed method are obtained and used to derive analytically some of the operational characteristics of the method. Simulation and experimental results of proposed method show a 30% reduction of THD in the current waveform. Considering the limits of THD set by IEEE Standard 929-2000 and IEEE Standard 1547.1, this method is able to detect the islanding faster with better NDZ. The proposed method could be enhanced further by adding a positive feedback such that the distortion factor K becomes a function of the frequency drift, YAFAOUI et al.: IMPROVED ACTIVE FREQUENCY DRIFT ANTI-ISLANDING DETECTION METHOD as in the active frequency drift with positive feedback method (AFDPF). REFERENCES [1] P. Du, Z. Ye, E. Aponte, J. Nelson, and L. Fan, “Positive-feedback-based active anti-islanding schemes for inverter-based distributed generators: Basic principle, design guideline, and performance analysis,” IEEE Trans. Power Electron., vol. 25, no. 12, pp. 2941–2948, Dec. 2010. [2] F.-S. Pai, J.-M. Lin, and S.-J. Huang, “Design of an inverter array for distributed generations with flexible capacity operations,” IEEE Trans. Ind. Electron., vol. 57, no. 12, pp. 3927–3934, Dec. 2010. [3] J.-H. Kim, J.-G. Kim, Y.-H. Ji, Y.-C. Jung, and C.-Y. Won, “An islanding detection method for a grid-connected system based on the goertzel algorithm,” IEEE Trans. Power Electron., vol. 26, no. 4, pp. 1049–1055, Apr. 2011. [4] A. Pigazo, M. Liserre, R. Mastromauro, V. Moreno, and A. Dell’Aquila, “Wavelet-based islanding detection in grid-connected pv systems,” IEEE Trans. Ind. Electron., vol. 56, no. 11, pp. 4445–4455, Nov. 2009. [5] I. Balaguer-Alvarez, Q. Lei, S. Yang, U. Supatti, and Z. Peng, “Control for grid-connected and intentional islanding operations ofdistributed power generation,” IEEE Trans. Ind. Electron., 2010. [6] D. Velasco, C. Trujillo, G. Garcera and, and E. Figueres, “An active antiislanding method based on phase-pll perturbation,” IEEE Trans. Power Electron., vol. 26, no. 4, pp. 1056–1066, Apr. 2011. [7] H. Zeineldin, “A q-f droop curve for facilitating islanding detection of inverter-based distributed generation,” IEEE Trans. Power Electron., vol. 24, no. 3, pp. 665–673, Mar. 2009. [8] W. Bower and M. E. Ropp, “Evaluation of islanding detection methods for photovoltaic utility-interactive photovoltaic systems,” International Energy Agency, Paris, France, Tech. Rep. IEA-PVPS T5-09, 2002. [9] IEEE Recommended Practice for Utility Interface of Photovoltaic (pv) Systems, IEEE Standard 929-2000. [10] Ieee Standard for Interconnecting Distributed Resources With Electric Power Systems, IEEE Standard 1547-2003. [11] Ieee Standard Conformance Test Procedures for Equipment Interconnecting Distributed Resources With Electric Power Systems, IEEE Standard 1547.1-2005. [12] T. T. Ma, “Novel voltage stability constrained positive feedback antiislanding algorithms for the inverter-based distributed generator systems,” Renewable Power Generat., IET, vol. 4, no. 2, pp. 176–185, 2010. [13] S.-K. Kim, J.-H. Jeon, J.-B. Ahn, B. Lee, and S.-H. Kwon, “Frequencyshift acceleration control for anti-islanding of a distributed-generation inverter,” IEEE Trans. Ind. Electron., vol. 57, no. 2, pp. 494–504, Feb. 2010. [14] Y. Jung, J. Choi, B. Yu, G. Yu, and J. So in A novel active frequency drift method of islanding prevention for the grid-connected photovoltaic inverter, Jun., 2005, pp. 1915–1921. [15] V. John, Z. Ye, and A. Kolwalkar, “Investigation of anti-islanding protection of power converter based distributed generators using frequency domain analysis,” IEEE Trans. Power Electron., vol. 19, no. 5, pp. 1177– 1183, Sep. 2004. [16] Y. Jin, Q. Song, and W. Liu, “Anti-islanding protection for distributed generation systems based on reactive power drift,” in Proc. 35th Annu. Conf. IEEE Ind. Electron. (IECON) 2009, Porto, Portugal, Nov., pp. 3970– 3975. [17] L. Lopes and H. Sun, “Performance assessment of active frequency drifting islanding detection methods,” IEEE Trans. Energy Convers., vol. 21, no. 1, pp. 171–180, Mar. 2006. [18] P. Du, Z. Ye, E. Aponte, J. Nelson, and L. Fan, “Positive-feedback-based active anti-islanding schemes for inverter-based distributed generators: Basic principle, design guideline, and performance analysis,” IEEE Trans. Power Electron., vol. 25, no. 12, pp. 2941–2948, Dec. 2010. [19] M. Ciobotaru, V. Agelidis, R. Teodorescu, and F. Blaabjerg, “Accurate and less-disturbing active anti-islanding method based on pll for gridconnected converters,” IEEE Trans. Power Electron., vol. 25, no. 6, pp. 1576–1584, Jun. 2010. [20] M. E. Ropp, M. Begovic, and A. Rohatgi, “Prevention of islanding in gridconnected photovoltaic systems,” Progr. Photovolt.: Res. Appl., vol. 7, no. 1, pp. 39–59, Jan./Feb. 1999. [21] F. Liu, Y. Kang, and S. Duan, “Analysis and optimization of active frequency drift islanding detection method,” in Proc. 22nd Annu. IEEE Appl. Power Electron. Conf. (APEC) 2007, pp., 1379–1384. [22] X. Zhu, G. Shen, and D. Xu, “Evaluation of afd islanding detection methods based on ndzs described in power mismatch space,” in Proc. IEEE [23] [24] [25] [26] [27] 2375 Energy Conversion Congress and Exposition (ECCE) 2009, San Jose, CA, Sep. 2009, pp. 2733–2739. M. Ropp, M. Begovic, and A. Rohatgi, “Analysis and performance assessment of the active frequency drift method of islanding prevention,” IEEE Trans. Energy Convers., vol. 14, no. 3, pp. 810–816, Sep. 1999. Z. Ye, A. Kolwalkar, Y. Zhang, P. Du, and R. Walling, “Evaluation of antiislanding schemes based on nondetection zone concept,” IEEE Trans. Power Electron., vol. 19, no. 5, pp. 1171–1176, Sep. 2004. Ieee Standard Definitions for the Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced Conditions, IEEE Standard 1459-2010. R. Teodorescu, F. Blaabjerg, U. Borup, and M. Liserre, “A new control structure for grid-connected lcl pv inverters with zero steady-state error and selective harmonic compensation,” in Proc. 19th Annu. IEEE Appl. Power Electron. Conf. Expo. (APEC), 2004, vol. 1, pp. 580–586. M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, “Control of single-stage single-phase pv inverter,” in Proc. Eur. Conf. Power Electron. Appl. 2005, Dresden, Germany, p. 10. Ahmad Yafaoui (S’95) received the Bachelor and Master degrees in electrical engineering from Middle East Technical University, Ankara Turkey, in 1996 and 1998, respectively. He is currently a Ph.D. student at Ryerson University, Toronto, Canada. He worked as Senior Design Engineer from 1998 to 2006. His research interests include solar energy conversion systems and DC/DC converter. Bin Wu (S’89-M’92-SM’99-F’08) received the Ph.D. degree in electrical and computer engineering from the University of Toronto, Canada, in 1993. After being with Rockwell Automation, Canada, as a Senior Engineer, he joined Ryerson University, Toronto, Canada, where he is currently a Professor and NSERC/Rockwell Industrial Research Chair in power electronics and electric drives. He has published more than 200 technical papers, authored/coauthored two Wiley-IEEE Press books, and holds more than 20 awarded/pending patents in the area of power conversion, advanced controls, adjustable-speed drives, and renewable energy systems. Dr. Wu received the Gold Medal of the Governor General of Canada, the Premier’s Research Excellence Award, Ryerson Distinguished Scholar Award, Ryerson Research Chair Award, and the NSERC Synergy Award for Innovation. He is a fellow of Engineering Institute of Canada (EIC) and Canadian Academy of Engineering (CAE). He is an Associate Editor of the IEEE TRANSACTIONS ON POWER ELECTRONICS and IEEE CANADIAN REVIEW. Samir Kouro (S’04-M’08) was born in Valdivia, Chile, in 1978. He received the M.Sc. and Ph.D. degrees in electronics engineering from the Universidad Técnica Federico Santa Marı́a (UTFSM), Valparaı́so, Chile, in 2004 and 2008, respectively. In 2004, he joined the Electronics Engineering Department, UTFSM, as a Research Assistant, and became an Associated Researcher, in 2008, and Research Academic, in 2011. From 2009 to 2011 he was on a Postdoctoral stay in the Department of Electrical and Computer Engineering, Ryerson University, Toronto, Canada. His research interests include power converters, variable-speed drives, and renewable energy conversion systems. He has coauthored one book, two book chapters, and more than 50 refereed journal and conference papers. Dr. Kouro has served as Guest Editor in one special section of the IEEE TRANSACTION ON INDUSTRIAL ELECTRONICS and was recipient of the Best Paper Award of 2008 of the IEEE INDUSTRIAL ELECTRONICS magazine.