Tutorial Questions and Solutions: The Per-Unit System Q1. A Y connected load consisting of three equal impedances of 10∠60º Ω is connected to an 11kV busbar at a substation by a 3Φ overhead line of impedance 0.5∠75º Ω per phase. Calculate the line-line voltage at the terminals of the load in per-unit and in kV if the base line-line voltage is 11kV and 3-phase “MegaVoltAmpere” is 10MVA. Finally calculate the current in each phase of the line in per-unit and kA. S1: ( base kVLL ) Base Impedance = 2 base MVA 3Φ 112 = = 12.1Ω 10 Load Impedance = 10∠60D = 0.826∠60D p.u. 12.1 Line Impedance = 0.5∠75D = 0.0413∠75D p.u. 12.1 Source Voltage = 1.0 p.u. Terminal Voltage = 1.0 × 0.826∠60D 0.826∠60D + 0.0413∠75D = 0.954∠ − 0.7D p.u. = 0.954∠ − 0.7D ×11kV = 10.49∠ − 0.7D kVLL Base kA = Current = base MVA3Φ 3 × base kVLL = 10 = 0.525 kA 3 ×11 1.0 = 1.155∠ − 60.7D p.u. D 0.826∠60 + 0.0413∠75 D = 1.155∠ − 60.7D × 0.525 = 0.606∠ − 60.7 D kA Q2. The sub-transient reactance of a generator (X”) is given as 0.2 per-unit based on the generator’s name-plate rating of 11.8kV, 200MVA. Calculate the per-unit impedance of the generator referred to the power system base of 11.0kV, 100MVA. S2: Znew ( p.u.) = Zold, p.u . × ( base old base MVA 3new kVLL 2 Φ × ) ( ) new base kVLL MVA3oldΦ base 11.8 2 100 = 0.115 p.u. X '' (new p.u.) = 0.2 × ( ) × 11.0 200 Q3: A 3Φ two winding transformer is rated at 75MVA, 11.8/145kV, 50Hz and the equivalent leakage impedance referred to the 11.8kV winding is Zeq = 0.22 Ω. Using the transformer ratings as base values, determine the per-unit leakage impedances referred to the 11.8kV winding and the 145kV winding. S3: Referred to the 11.8kV winding: Base Z11.8kV = Z11.8kV p .u . (base kVLL ) 2 11.82 = = = 1.86Ω base MVA 3Φ 75 0.22 = 0.12 p.u. 1.86 Calculate the per-unit impedance referred to the 145kV winding: (Theory: the p.u. impedance of an ideal transformer is the same regardless of whether it is referred to the LV or HV winding) Proof: E HV p .u . N HV × E LV (kV) LV E HV (kV) = = N base kV HV base kV HV where (N HV /N LV ) is the turns ratio of the ideal transformer. Using the transformer HV and LV voltage ratings as the HV and LV per-unit voltage base, i.e.: base kV HV V rating HV N HV = = base kV LV V rating LV N LV N HV × E LV (kV) LV then: E HV (p.u.) = N HV × base kV LV N / N LV = E LV (kV) = E LV ( p.u.) LV base kV Illustration of theory - impedance referred to the 145kV winding: base Z145kV (base kVLL ) 2 1452 = = = 280Ω base MVA3Φ 75 The leakage impedance Zeq referred to the 145kV winding: 2 Zeq-145kV = Hence: Z145kV p .u . ⎛ 145 ⎞ =⎜ ⎟ × Zeq-11.8kV = 33.22Ω ⎝ 11.8 ⎠ 33.22 = 0.12 p.u. 280 Q4: The power network shown below consists of three zones connected to each other using transformers. Transformer 1-2 is rated at 5000kVA, 11kV/66kV and its leakage reactance = 12% Transformer 2-3 is rated at 5000kVA, 66kV/33kV and its leakage reactance = 10% 1 2 2 11kV 3 66kV 33kV If the zone-2 base is 5000kVA, 66kV find per-unit impedance in 3, 2 & 1 of a 250Ω resistive load (full-load) connected to 3. Draw the impedance diagram in per-unit neglecting mag currents, transformer resistances and line impedances. Determine the voltage regulation at the load if the voltage across the 250Ω load is 32kV and the voltage at 1 remains constant during full-load and no-load conditions S4: Zone 2: Base kV2 = 66kV, Base MVA 2 = 5 MVA, Base Z 2 = 662 / 5 = 871Ω Zone 1: Base kV1 = (11/ 66) × 66 = 11kV, Base MVA1 = 5 MVA, Base Z1 = 112 / 5 = 24.2Ω Zone 3: Base kV3 = (33 / 66) × 66 = 33kV, Base MVA 2 = 5 MVA, Base Z3 = 332 / 5 = 218Ω Per-unit impedance of load in Zone 3: Z3 = 250 / 218 = 1.15 p.u. Impedance of load referred to Zone 2: Z2 = (66 / 33)2 × 250 = 1000 Ω Per-unit impedance of load referred to Zone 2: Z2 = 1000 / 871 = 1.15 p.u. Impedance of load referred to Zone 1: Z1 = (11/ 66) 2 × 1000 = 27.8 Ω Per-unit impedance of load referred to Zone 1: Z1 = 27.8 / 24.2 = 1.15 p.u. Note: The voltages, currents and external impedances expressed in per-unit do not change when they are referred from one side of a transformer to the other. Impedance diagram in per-unit: leakage reactance transformer 1-2 = 12% = 0.12 p.u. leakage reactance transformer 2-3 = 10% = 0.10 p.u. Voltage Regulation: Percent regulation = VR,NL -VR,FL VR,FL ×100 where: VR,NL is the magnitude of the no-load voltage at the load. VR,FL is the magnitude of the full-load voltage at the load. Note: full-load = 250Ω Voltage across full-load = 32kV Voltage across full-load = 32kV/base kV3 = 32 / 33 = 0.970 p.u. Load current = (0.970 + j 0) / (1.15 + j 0) = 0.843 + j 0 Voltage input to network = (0.843 + j 0) × ( j 0.12 + j 0.10) + 0.970 = 0.987∠11D p.u. No-load voltage at the load = voltage input to network. 0.987 − 0.970 Therefore: Regulation = × 100 = 1.75% 0.970 Q5: For the power network shown below, calculate, using per-unit quantities, the voltage in kV, the current in kA and the power in kW received by the load. 3 L1 G1 T1 132kV T2 11kV G1 = synchronous generator = 75MVA, 11.8kV, sync reactance Xd = j1.83 p.u. T1 = generator transformer = 75MVA, 11.8kV/145kV X = j0.125 p.u. L1 = 132kV transmission line: Z = 0.18 + j0.40 Ω/km, length = 20km. T2 = step-down transformer = 45MVA, 132kV/11kV, X = j0.125 p.u. ZL = 11kV load = 10MVA, cos φ = 0.8 (lagging). S5: The above power system should be divided into three zones interconnected by transformers T1 and T2. Zone 1 refers to the 11.8kV generator and 11.8kV winding of T1. Zone 2 refers to the 145kV T1 winding, L1 & the T2 132kV winding. Zone 3 refers to the 11.0kV winding of T2 and the load ZL . Assume a per-unit base of 100MVA and 132kV in zone 2. Zone 2: base kV2 = 132kV 1322 = 174.2Ω 100 11.8 Zone 1: base kV1 = ×132 = 10.74kV, 145 10.7 2 base Z1 = = 1.15Ω 100 11 Zone 3: base kV3 = ×132 = 11.0kV, 132 11.02 base Z3 = = 1.21Ω 100 base Z2 = 2 G1: Xd new ⎛ kV ⎞ MVA 3Φnew = Xd old × ⎜ old ⎟ × ⎝ kVnew ⎠ MVA 3Φold 2 ⎛ 11.8 ⎞ 100 = j1.83 × ⎜ = j 2.95 p.u. ⎟ × ⎝ 10.74 ⎠ 75 Note: compare Xd new calculated at the LV side of T1 with Xd new calculated at the HV side. 2 HV side: Xd new ⎛ 145 ⎞ 100 = j1.83 × ⎜ = j 2.95 p.u. ⎟ × ⎝ 132 ⎠ 75 2 ⎛ 11.8 ⎞ 100 T1: X = 0.125 × ⎜ = j 0.20 p.u. ⎟ × ⎝ 10.74 ⎠ 75 20 × (0.18 + j 0.40) L1: Z = = (0.021 + j 0.046) p.u. 174.2 2 ⎛ 11.0 ⎞ 100 T2: X = 0.125 × ⎜ = j 0.278 p.u. ⎟ × ⎝ 11.0 ⎠ 45 Load: ZL ( kVLL ) = ZL = 2 MVA 3Φ = 11.02 = 12.1∠37D 10.0 12.1∠37D = 10.0∠37D p.u. = (7.99 + j 6.02) p.u 1.21 Hence: Current in the load in p.u. I Load = 11.8∠0D /10.7 ( 0.021 + 7.99 ) + j (2.95 + 0.20 + 0.046 + 0.278 + 6.02) 1.10∠0D = = 0.088∠ − 50D p.u. D 12.43∠50 Current in load in kA (referred to 11kV winding): base MVA 3Φ I Load = I Load, p.u . × 3 × base kV3 = 0.088∠ − 50D ×100 /( 3 ×11.0) = 0.46∠ − 50D kA Line-line voltage at the load: VLoad = 3 × 0.46∠ − 50D ×12.1∠37D = 9.7∠ − 13D kV Power in the load: PLoad3Φ = 3 × VLL × I L × cos θ = 3 × 9.7 × 0.46 × 0.8 = 6.2 MW MVA in the load: MVA Load3Φ = 3 × VLL × I L = 7.7 MVA MVA Load3Φ VLL 2 9.7 2 = = = 7.7MVA ZL 12.1 ---end of the per unit tutorial questions and solutions---