DETECTION SYSTEMS Dual Hydrogen Control Panel (DHCP) Installation and Operation Manual HA0156P01 Rev. D 120V & 220V Bottom Entry Contents Introduction ..................................................................................................................................... 6 Specifications .................................................................................................................................. 7 System Description ......................................................................................................................... 8 Gas Analyzers (Sensor Cells QT-290A, QT-290B, Controller PCB HD0039G01, I/O PCB HD0043G01, Display PCB HD0138G03) ................................................................................... 8 Control/Display Panel ................................................................................................................ 9 Sensor Cell Assembly ................................................................................................................. 9 Flow Indicators with Metering Valves (FI-2971, FI-2972) .......................................................... 9 Total Gas Flowmeter (FI-2973) .................................................................................................. 9 Differential Pressure Gage (PDI-292) ....................................................................................... 10 Differential Pressure Transmitter (PDT-292) ............................................................................ 10 Purifiers ................................................................................................................................... 10 Moisture Indicators (MI-2971, MI-2972, MI-2973) ................................................................... 10 Metering Valves (HO-2971, HO-2972, HO-2973, HO-2974) ...................................................... 10 Installation .................................................................................................................................... 11 Cabinet Mounting .................................................................................................................... 11 Lifting ...................................................................................................................................... 11 Electrical Connections ............................................................................................................. 11 Contacts/Signals ...................................................................................................................... 12 Circuit Protection ..................................................................................................................... 12 System Operation ......................................................................................................................... 13 DHCP Initialization .................................................................................................................. 13 Flow Calibration ...................................................................................................................... 14 Gas Calibration ....................................................................................................................... 14 Normal Operation .................................................................................................................... 15 Purge Operation ....................................................................................................................... 16 Mode Menu .............................................................................................................................. 16 Cell Output Voltages ................................................................................................................ 18 Maintenance ................................................................................................................................. 19 Daily ........................................................................................................................................ 19 Weekly...................................................................................................................................... 19 Every Six Months ..................................................................................................................... 19 When the Generator is Down ................................................................................................... 19 Component Replacement Instructions .......................................................................................... 20 Removing a Gas Analyzer Sensor ............................................................................................. 20 Removing a Processor Circuit Board ........................................................................................ 20 Removing the Input/Output (I/O) Circuit Board ......................................................................... 21 Removing Solenoid Valves Coils ............................................................................................... 21 1 HA0156P01 Rev. D Removing Moisture Indicators .................................................................................................. 21 Removing Gas Purifiers ........................................................................................................... 22 Removing Flow Meters............................................................................................................. 22 HA0156P01 Rev. D 2 Figures Figure 1 - DHCP Outline ............................................................................................................................. 25 Figure 2 - DHCP Main Junction Box, Internal Component ........................................................................... 27 Figure 3 - Customer Interface Connections ................................................................................................. 28 Figure 4 - DHCP Wiring Diagram ............................................................................................................... 29 Figure 4a - DHCP Wiring Diagram ............................................................................................................. 31 Figure 5 - DHCP Piping Schematic ............................................................................................................. 33 Figure 6 - Analyzer Status ........................................................................................................................... 35 Figure 7 - DHCP Display ............................................................................................................................ 36 Figure 8 - DHCP Display Descriptions ........................................................................................................ 37 Figure 9 - DHCP Status .............................................................................................................................. 38 Figure 10 - DHCP Customer Contacts ........................................................................................................ 39 Figure 11 - Valve/Switch Configuration, Normal % H2 in Air ....................................................................... 40 Figure 12 - Valve/Switch Configuration, Purge % H2 in CO2 ....................................................................... 40 Figure 13 - Valve/Switch Configuration, Purge % Air in CO2 ...................................................................... 41 Figure 14 - Valve/Switch Configuration, Case .............................................................................................. 41 Figure 15 - Valve/Switch Configuration, Confirmation Mode, Turbine End .................................................... 42 Figure 16 - Valve/Switch Configuration, Confirmation Mode, Collector End.................................................. 42 Figure 17 - Valve/Switch Configuration, Calibrate N2 (Both Analyzers) ....................................................... 43 Figure 18 - Valve/Switch Configuration, Calibrate CO2 (Both Analyzers) .................................................... 43 Figure 19 - Valve/Switch Configuration, Calibrate H2 (Both Analyzers) ....................................................... 44 Figure 20 - Valve/Switch Configuration, Calibrate N2 (Turbine End) ............................................................ 44 Figure 21 - Valve/Switch Configuration, Calibrate N2 (Collector End) .......................................................... 45 Figure 22 - Valve/Switch Configuration, Calibrate CO2 (Turbine End) .......................................................... 45 Figure 23 - Valve/Switch Configuration, Calibrate CO2 (Collector End) ....................................................... 46 Figure 24 - Valve/Switch Configuration, Calibrate H2 (Turbine End) ............................................................ 46 Figure 25 - Valve/Switch Configuration, Calibrate H2 (Collector End) .......................................................... 47 Figure 26 - Parts List ................................................................................................................................... 48 3 HA0156P01 Rev. D HA0156P01 Rev. D 4 Dual Hydrogen Control Panel (DHCP) System Important Information THIS EQUIPMENT OPERATES AT VOLTAGE LEVELS THAT CAN BE HAZARDOUS TO PERSONNEL. READ THE SECTION ABOUT SAFETY CONSIDERATIONS BEFORE INSTALLING OR SERVICING. THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAINTENANCE. SHOULD FURTHER INFORMATION BE DESIRED, OR SHOULD PARTICULAR PROBLEMS ARISE THAT ARE NOT COVERED SUFFICIENTLY FOR THE PURCHASER’S PURPOSES, REFER THE MATTER TO ENVIRONMENT ONE CORPORATION. IT IS THE RESPONSIBILITY OF SITE MANAGEMENT TO ASSURE THAT ONLY TRAINED/QUALIFIED PERSONNEL OPERATE AND/OR SERVICE THIS EQUIPMENT. Dual Hydrogen Control Panel (DHCP) System Safety Considerations THE SYSTEM ELECTRONICS ENCLOSURE AND CUSTOMER INTERFACE ENCLOSURE CONTAIN 115 AND OR 230 VOLTS AC. THIS VOLTAGE APPEARS AT THE AC POWER STRIP AND VARIOUS OTHER POINTS. EQUIPMENT OPERATION INVOLVES A FLAMMABLE GAS (HYDROGEN) UNDER PRESSURE. APPROPRIATE MEASURES MUST BE TAKEN TO PREVENT LEAKS AND AVOID SOURCES OF IGNITION. ALL ELECTRICAL CONNECTIONS BETWEEN THE SYSTEM ELECTRONICS, CUSTOMER INTERFACE AND DISPLAY/CONTROL PANEL SHOULD BE TESTED AND VERIFIED TO BE CORRECT. ALL WIRING MUST BE IN ACCORDANCE WITH LOCAL CODE AND/OR CENELEC STANDARD EN50014. ALL GAS CONNECTIONS TO THE PANEL MUST BE LEAK CHECKED PRIOR TO APPLYING AC POWER. CHECK FOR LEAKS AT ALL TUBING AND MECHANICAL CONNECTIONS. IF LEAKS ARE FOUND, DETERMINE THE CAUSE AND REPAIR. REPEAT THE LEAK CHECK UNTIL THE PANEL IS DETERMINED TO BE LEAK TIGHT. 5 HA0156P01 Rev. D Introduction Modern high capacity turbine generators use hydrogen gas as a cooling medium. Two reasons for using hydrogen are 1) hydrogen has the best heat transfer characteristics of any gas; and 2) the low atomic weight of hydrogen makes it the lightest and, therefore, has the lowest density of any stable gas (10 percent that of air at a purity of 98 percent), resulting in the lowest windage losses. The hydrogen auxiliary system exists to maintain the quality and quantity of cooling gas required to ventilate the conducting and rotating parts of hydrogen cooled generators. Gland seals are used to prevent hydrogen leakage through the clearance between the shaft and the frame. In order to maintain hydrogen gas purity of approximately 98 percent, some generators use a seal gland system, where a small quantity of hydrogen gas is continuously scavenged from two (collector end and turbine end) seal drain enlargements and discharged into the atmosphere. The Dual Hydrogen Control Panel (DHCP) contains two independent Generator Gas Analyzers (GGA’s) and circuitry to control the rate of scavenging in order to maintain high gas purity. Environment One’s microprocessor-controlled Generator Gas Analyzer (GGA), with its triple-range sensor cell, is capable of measuring 70 to 100 percent H2 in Air, 0 to 100 percent H2 in CO2 and 0 to 100 percent Air in CO2. Each GGA continuously analyzes the generator cooling gas, displays gas purity in real time and has a corresponding 4 to 20 mA output. In the event that the gas purity falls to a warning or alarm level, a visual indication is given and alarm contacts are switched. The GGA’s triple-range sensor cell also monitors purge gases used during generator shutdown and maintenance. Purge gas purity is displayed and a corresponding 4 to 20 mA output is provided for H2 in CO2 or Air in CO2. HA0156P01 Rev. D 6 Specifications Input Voltage 120 Vac 50/60 Hz 220 Vac 50/60 Hz Ambient Temperature 32 F to 125 F (0 C to 52 C) Maximum Pressure 100 psi Ambient Location Class 1, Division 1, Group B Gas Analyzer Sensing Unit Switchable — Triple Range (70-100% H 2 in Air) (0-100% H2 in CO2) (0-100% Air in CO2) Accuracy +/- 1% of full scale @ 80-100% H 2 in Air Outputs 4-20 mA current output Alarm Levels Alarm and warning levels are adjustable Relay Contact Rating 30V/1A DC 120V/0.5A AC 125V/0.005A (Resistive) DC Data Retention Lithium battery-supported RAM 10 years minimum Indicators AC power, Trouble, Normal (H2 in Air), Purge (H2 in CO2), Purge (Air in CO2), Calibrate H 2, Calibrate CO2, Calibrate N 2, One 3-character LED numeric displays, One 16-character LCD display Weight 475 lbs (standard) 1,100 lbs (NEMA 3R) Dimensions 17” d x 64 3/4” h x 36” w (standard) 27.5” d x 72” h x 42” w (NEMA 3R) 7 HA0156P01 Rev. D System Description The Dual Hydrogen Control Panel (DHCP) is designed for use on hydrogen-cooled generators. It is designed to operate in Class 1, Division 1, Group B hazardous areas. The DHCP analyzes and, in real time, displays the hydrogen gas purity on built-in numeric displays. Environment One’s GGA can be supplied as an Ex, CE labeled system for Zone 1 environments. Contact Environment One for details. The major components of the DHCP include: • 2 completely independent, generator gas analyzers (GGA) • 2 hydrogen gas flow indicators with metering valves • 1 total hydrogen gas flow indicator • 1 fan differential pressure transmitter and gage • 3 hydrogen gas purifiers • 3 moisture indicators • 4 metering valves • Numerous isolation valves • 2 local display panels that indicate gas purity and specific operating conditions Gas Analyzers (Sensor Cells QT-290A, QT-290B, Controller PCB HD0039G01, I/O PCB HD0043G01, Display PCB HD0138G03) Analyzers and their printed circuit boards (PCBs) are interchangeable. Each analyzer is comprised of a sensing unit, controller PCB, sensor cells and input/output (I/O) PCB. All PCB’s are housed in the main junction box (Figure 1); local display panels are mounted on the front of the panel (Figure 1). Each analyzer independently provides purity monitoring, calibration, mode selection, sensor unit control, alarm electronics, data logging, system inputs/outputs and sensing unit linearization. See Figure 8 for display panel features and functions. Fail-safe operation of the Gas Analyzers is ensured by: 1. On power-up the GGA must execute and pass qualifying self tests. Failure in any test results in termination of operation and annunciation of the condition causing the failure. 2. Following power-up and/or system reset, the GGA is continuously supervised by an independent watchdog monitor that serves to reset it should its operation become erratic. HA0156P01 Rev. D 8 (Gas Analyzers cont’d) 3. The GGA is completely self-supervised and continuously checks itself for legal processor functioning, internal voltages, analog-to-digital conversion accuracy, integrity of cabling and relay operation. Any faults are immediately annunciated as “trouble” on the display and accompanied by a change in the corresponding relay state. See Analyzer Failure for more information. Control/Display Panel The Control/Display Panel provides control of all functions of the GGA as well as complete annunciation of the status of the GGA (Figure 7). Functions are accessed by means of a four-button membrane-switch keypad and 16-character Liquid Crystal Display (LCD). Generally, pressing the Fn (Function) key causes the LCD to continuously scroll the names of the GGA’s available functions. A function may then be accessed by pressing the ENTER key when the function name appears. To signal confirmation, the function name flashes briefly. The Display Panel provides Light Emitting Diodes (LEDs) to annunciate the Normal (H2 in air), Purge (H2 in CO2 and air in CO2), and Calibrate (H2, CO2 and N2) GGA states. In addition, they indicate Warning, Alarm and Trouble conditions. A green LED indicates AC Power. It is important to understand that, should the GGA go into either Warning and/or Alarm, it will lock into continuous monitoring of the gas stream. No other function can be accessed unless the Alarm/Warning Reset key is first pressed. To permit a system level initialization (“cold start”), a momentary push-button, located behind the Display Panel (Figure 7) in the upper right hand corner, may be pressed. Since all calibration constants are stored in non-volatile memory, these values will not be lost should the system be initialized or should it lose, then regain, AC power. Sensor Cell Assembly The sensor cell assembly is comprised of a sampling thermistor and a reference thermistor — both operated at very low power in a self-heated mode — embedded in a temperatureregulated cell block. Gas purity is derived as a function of the thermal conductivity of the gas mixture to the heat output of the thermistors under known constraints. See Cell Output Voltages for a detailed description for the sensor cell. Flow Indicators with Metering Valves (FI-2971, FI-2972) Two low-flow gas indicators with needle metering valves are used to adjust the hydrogen gas flow through each sensing unit (Analyzer 1 and Analyzer 2, Figure 1). Both have a direct read scale with a range of 90 to 900 cc/min, calibrated with hydrogen. Note: Flow indication changes with different gases. For hydrogen, the flow should be set for 500 cc/min. Total Gas Flowmeter (FI-2973) A high flow gas indicator is used to indicate the scavenging flows (Total Flow, Figure 1). The high flow gas indicator has a direct read scale with a range of 540 to 5,400 cc/min when calibrated with hydrogen. Note: Flow indication changes with different gases. Metering valves adjust the flow of the collector end low flow, collector end high flow, turbine end low flow and turbine end high flow. See Flow Calibration for flow settings. HA0156P01 Rev. D 9 Differential Pressure Gage (PDI-292) A differential pressure gage measures the generator fan differential pressure (Fan Differential, Figure 1). The standard differential pressure gage has dual scales with ranges of 0 to 30 inches H 2O and 0 to 76.2 gm/cm2. Some units may be equipped with special gage scales. Differential Pressure Transmitter (PDT-292) A differential pressure transmitter provides an output signal corresponding to the generator fan differential pressure (Figure 1). This 4 to 20 mA output is externally provided by the Mark V and corresponds to 0 to 30 inches H2O. Some units may be equipped with a special range. Purifiers Three gas purifiers remove foreign matter from the hydrogen stream (Turbine End Purifier, Case Purifier, Collector End Purifier; Figure 1). Removal of oil, water and particles above 12 microns is accomplished through the use of molecular sieve materials and special filters. The filters are available in replaceable cartridges, HA0139P02. Moisture Indicators (MI-2971, MI-2972, MI-2973) Three moisture indicators indicate the downstream presence of moisture in the hydrogen stream (Turbine End Moisture, Collector End Moisture, Case Moisture; Figure 1). The units are supplied with a dyed silica gel, which gradually changes from blue (at relative humidity less than 4 percent) to pink (at relative humidity higher than 40 percent). These devices are replaceable. Metering Valves (HO-2971, HO-2972, HO-2973, HO-2974) Four needle metering valves provide adjustment for the scavenging flow rates (Collector End Low Flow, Turbine End Low Flow, Collector End High Flow, Turbine End High Flow; Figure 1). See Flow Calibration for flow settings. HA0156P01 Rev. D 10 Installation Follow the installation instructions to ensure proper installation of the equipment. The exact location of the DHCP should be in accordance with the recommendations made by General Electric or its authorized representative. Cabinet Mounting Choose a location that is not subject to extremes of dust, temperature, vibration or shock. The panel should be accessible for service, with adequate clearance to open the enclosure and display panel doors (Figure 1). The DHCP has four foundation bolt openings (Figure 1). The openings allow you to insert four 5/8-inch bolts for securing the panel to the floor. The bolts are isolated from the panel through the use of compression vibration insulators. Use fasteners that are compatible with the mounting surface and able to support the weight of the panel. Lifting bolts at the top of the panel allow for easy connection to overhead cranes. Lifting The DHCP should be lifted by the pair of eye bolts provided at the top of the frame. Electrical Connections Prior to applying power to the DHCP unit, ensure that the local power source matches the power rating on the DHCP nameplate. The DHCP unit is shipped with all isolation and metering valves closed. All gas lines must be connected to the DHCP and leak-tested before continuing. Electrical connections are made through four 3/4-inch male conduit unions at the bottom or top of the panel (Figure 1). System power requirements are 120 or 220 Volts AC (systems are supplied for specifically 120 V or 220 V). The AC power source should be reliable and not subject to severe transients. Total load max.: 400 watts. Electrical connections, located inside of the main junction box, are accessed by removing 32 3/4” hex captive bolts. Two guide studs are provided for assistance in removal/replacement. CAUTION! Do not scratch sealing surfaces on the main junction box. The main junction box lid weighs 50 lbs (22.7 kg). Take precautions during removal. Prior to opening the main junction box, remove power from the DHCP and ensure the system is free of hydrogen. Wire routing should be in accordance with Figure 3 or 4. This ensures that noise generated from the AC power and contacts does not interfere with the signals. Connections are made to barrier type terminal strips (Figure 3). 11 HA0156P01 Rev. D Contacts/Signals The DHCP includes alarm and status relays (Figures 3, 9, 10). They are: • Warning Relay Both a normally open and a normally closed contact (single pole, double throw configuration) is provided and a warning is signaled by an energized relay. • Alarm Relay Both a normally open and a normally closed contact (single pole, double throw configuration) is provided and an alarm is signaled by an energized relay. • Trouble Relay Both a normally open and a normally closed contact (single pole, double throw configuration) is provided and Trouble is signaled by an energized relay. • 4-20 mA output signals are provided for Analyzer #1, Analyzer #2 and the DP Transmitter (Figure 3). • The 4-20 mA signals for Analyzer #1 and Analyzer #2 correspond to 70 to 100 percent in Normal mode (H2 in air) and 0 to 100 percent in Purge modes (H2 and CO2 & Air in CO2). • Analyzer #1 and Analyzer #2’s output signals are internally powered. These signals are not to be powered by the Mark V, Mark VI. • The 4-20 mA signal for the DP Transmitter is powered by the Mark V, Mark VI. See Figure 3 for locations of signals on terminal block. See Figures 9 and 10 for description of conditions where relays are activated. Circuit Protection Each GGA is individually fused. A half-amp slo-blo fuse, located on the Input/Output PCB, provides circuit protection. HA0156P01 Rev. D 12 System Operation The DHCP’s main purpose is to analyze and display the hydrogen gas purity of hydrogen cooled generators. This section describes system operation. DHCP Initialization With system power on, press the RESET push-button on the backside of the DISPLAY PANEL (Figure 7). Reset each of the two gas analyzer units separately. The GGA will perform several self tests and, if they are successful, the DISPLAY PANEL will respond with (a) all discrete LEDs lit; (b) all segments and the tenths place decimal point of the GAS PURITY display lit; and (c) all pixels of the LCD display on. Within several seconds (a) all discrete LEDs, except the AC POWER and TROUBLE LEDS, will turn off; (b) all segments, except the tenths place decimal point of the GAS PURITY display will turn off; and (c) the display will indicate LINKING …, as the DISPLAY PANEL initiates communication with the rest of the system. Communication should be established within several seconds and the LCD display will then echo the results of cold-start initialization: • GGA ANALYZER READY • INITIALIZING … • 12 BIT ADC … • … CALIBRATED Note: If calibration is unsuccessful then the LCD will display 12 BIT ADC ERROR. After annunciating TROUBLE, the processor will be stopped because, at this point in the start-up sequence, this condition is a fatal error. Contact Environment One at (518) 346-6161. • 8 BIT ADC … • … CALIBRATED Note: If calibration is unsuccessful then the LCD will display 8 BIT ADC ERROR. After annunciating TROUBLE, the processor will be stopped because, at this point in the start-up sequence, this condition is a fatal error. Contact Environment One at (518) 346-6161. • Iout SET TO 4 mA where Iout is the 4-20 mA GGA output. See below. • Tcell = XX.X 0C (where XX.X is the instantaneous cell block temperature). For an indeterminate period (normally not exceeding 15 minutes for a cold start), the LCD will display the real-time temperature of the sensor cell block. When the temperature rises to 55.0 C +/- 0.5 C, the system will advance and the display will indicate: • ANALYZER READY After this last message, all discrete LEDs will go out except AC POWER and TROUBLE. In response to the prompts NORMAL (H2/AIR), CONFIGURE VALVES, permit the sample gas to flow through the sensor then press the ENTER key. This is the NORMAL mode of operation. See Normal for more information. For a first time installation, it is essential that a gas sensor calibration be performed on the system. Also, the faults log should be cleared. See System for more information. 13 HA0156P01 Rev. D Flow Calibration Refer to Figure 5 for piping component location and Figures 11 through 25 for valve configurations. With the DHCP system in normal operation, manually close all isolation valves and metering valves. Set CE low flow. Open isolation valve HV-2973. Adjust the collector end low flow metering valve HO-2974 for a flow setting of approximately 1000 SCCM at total flow meter FI-2973. Set CE high flow. While Mark V is energizing FY-2973, adjust the collector end high flow metering valve HO-2973 for a total flow of approximately 2000 SCCM at total flow meter FI2973. After adjustment is made, ensure that FY-2973 is de-energized by the generator control system (Mark V). Set Cell #2 flow. Open isolation valves HV-2974, HV-2982 and HV-2981; adjust the flow meter/metering valve FI-2972 for a flow of approximately 500 SCCM. Total flow meter FI2973 should indicate approximately 1500 SCCM. Close HV-2973, HV-2974, HV-2982 and HV-2981. Set TE low flow. Open isolation valve HV-2971. Adjust the turbine end low flow metering valve HO-2972 for a flow setting of approximately 1000 SCCM at total flow meter FI-2973. Set TE high flow. While Mark V is energizing FY-2971, adjust the turbine end high flow metering valve HO-2971 for a total flow of approximately 2000 SCCM at total flow meter FI2973. After adjustment is made, ensure that FY-2971 is de-energized by the generator control system (Mark V). Set Cell #1 flow. Open isolation valves HV-2972, HV-2979 and HV-2980. Adjust the indicator/metering valve FI-2971 for a flow of approximately 500 SCCM. Total flow meter FI-2973 should indicate approximately 1500 SCCM. Open HV-2973, HV-2974, HV-2982 and HV-2981. Total flow meter FI-2973 should indicate approximately 3000 SCCM. Gas Calibration Calibrate each of the two gas analyzer units separately. Press the Fn key on the GGA. Wait until the display scrolls to the prompt GAS CALIBRATION then press the ENTER key. The display will scroll the prompts CALIBRATE H2, CALIBRATE CO2 and CALIBRATE N2. Wait until the display scrolls to the prompt CALIBRATE H2 then press the ENTER key. In response to the prompts CALIBRATE H2, CONFIGURE VALVES, permit the hydrogen calibration gas to flow through the sensor. With the calibration gas flowing the LCD will display the voltage output of the reference cell sensor in the format Vref=X.XXX VDC. Press the Fn key to cancel the calibration at this point, if desired; this will permit a return to the main menu. If desired to continue the calibration, observe the reference voltage and, if it appears stable (i.e., a final change of not greater than 1 to 2 mV per minute), press the ENTER key. The LCD will display the voltage output of the sample cell sensor in the format “Vcell=X.XXXVDC.” Again, the calibration may be terminated by pressing Fn. If it is HA0156P01 Rev. D 14 (Gas Calibration Cont’d) continued, observe the sample cell voltage as it adjusts to the flowing H 2 calibration span gas. When it appears stable (i.e., a final change of not greater than 1 mV per minute, which occurs within approximately 15 minutes) press the ENTER key. The LCD will display H2 CALIBRATED. This concludes H 2 calibration. The display will scroll the prompts CALIBRATE H 2, CALIBRATE CO2 and CALIBRATE N 2. Press the Fn key on the GGA to return to the main menu or to continue gas calibration, wait until the display scrolls to the prompt CALIBRATE CO2 and press the ENTER key. In response to the prompts CALIBRATE CO2, CONFIGURE VALVES, permit the CO2 calibration gas to flow through the sensor. With the calibration gas flowing the LCD will display the voltage output of the reference cell sensor in the format Vref=X.XXX VDC. If desired to cancel the calibration at this point, press the Fn key; this will permit a return to the main menu. If desired to continue the calibration, observe the reference voltage and, if it appears stable (i.e., a final change of not greater than 1 to 2 mV per minute), press the ENTER key. The LCD will display the voltage output of the sample cell sensor in the format Vcell=X.XXX VDC. Again, the calibration may be terminated by pressing Fn. If it is continued, observe the sample voltage as it adjusts to the flowing CO2 calibration zero gas. When it appears stable (i.e., a final change of not greater than 1 to 2 mV per minute, which occurs within approximately 15 minutes), press the ENTER key. The LCD will display CO2 CALIBRATED. This concludes CO2 calibration. The display will scroll the prompts CALIBRATE H2, CALIBRATE CO2 and CALIBRATE N2. Press the Fn key on the GGA to return to the main menu, or to continue gas calibration, wait until the display scrolls to the prompt CALIBRATE N2, press the ENTER key. In response to the prompts CALIBRATE N2, CONFIGURE VALVES, permit the nitrogen calibration gas to flow through the sensor. With the calibration gas flowing the LCD will display the voltage output of the reference cell sensor in the format Vref=X.XXX VDC. If desired to cancel the calibration at this point, press the Fn key; this will permit a return to the main menu. If desired to continue the calibration, observe the reference voltage and, if it appears stable (i.e., a final change of not greater than 1 to 2 mV per minute) press the ENTER key. The LCD will display the voltage output of the sample cell sensor in the format Vcell=X.XXX VDC. Again, the calibration may be terminated by pressing Fn. If it is continued, observe the sample voltage as it adjusts to the flowing N 2 calibration zero/span gas. When it appears stable (i.e., a final change of not greater than 1 to 2 mV per minute, which occurs within approximately 15 minutes) press the ENTER key. The LCD will display N 2 CALIBRATED. This concludes N 2 calibration. Press the Fn key to return to the main menu. This concludes the gas sensor calibration of the GGA system. Normal Operation Note: It is important to verify the lines connecting LE025 to the turbine-end seal drain enlargement, LE026 to the collector-end seal oil enlargement and LE028 to the case fan pressure are filled with hydrogen before placing the system in Normal operation. NORMAL operation of the GGA system can be accessed by first pressing the Fn key to access the main menu and, then, pressing the ENTER key when the display scrolls to the prompt NORMAL (H2 in Air). In response to the prompts NORMAL (H2 in Air), CONFIGURE VALVES, permit the sample gas to flow through the sensor then press the ENTER key. In HA0156P01 Rev. D 15 (Normal Operation Cont’d) the NORMAL mode of operation the GGA can respond to both WARNING and ALARM levels. Both levels are programmable (see SETTINGS, above, for detailed information). The 4-20 mA current output of the GGA corresponds to 70 to 100 percent gas purity and the GGA must remain below the WARNING or ALARM level for a minimum of one minute to generate an alarm. Should the GGA go into WARNING, it will energize the WARNING RELAY (Figure 3) and illuminate the WARNING LED. Further system operation is locked out until the WARNING RESET key is pressed (at which point the GGA will revert to NORMAL operation). Purge Operation To monitor a purge operation, first press the Fn key to access the main menu, and then press ENTER when the display scrolls to the prompt PURGE (H2 in CO2) or PURGE (Air in CO2) key. In response to either the prompt PURGE (H2 in CO2) or PURGE (Air in CO2), CONFIGURE VALVES, permit the sample gas to flow through the sensor then press the ENTER key. The Display Panel will respond with the corresponding PURGE (H2 in CO2) or PURGE (Air in CO2) LED illuminated. In this mode the 4 to 20 mA current output of each GGA corresponds to 0 to 100 percent gas purity. There is no alarm level for either of the PURGE operations. Mode Menu The following items are available by pressing the Fn key: • NORMAL (H2/AIR) This item, when displayed, can be selected by pressing the ENTER key. See Normal Operation for more information. • PURGE This item, when displayed, can be selected by pressing the ENTER key. See Purge Operation for more information. • GAS CALIBRATION This item, when displayed, can be selected by pressing the ENTER key. See Gas Calibration for more information. • SETTINGS This item, when displayed, can be selected by pressing the ENTER key. If selected, two sub-items will be displayed: ALARM LEVEL and WARNING LEVEL. These sub-items permit adjustment of the levels at which system alarm and warning are annunciated. To adjust the ALARM LEVEL, press the ENTER key when this sub-item appears. The LCD will display the current purity level (in percent purity) at, or above which, the system will annunciate an alarm condition. This value can be adjusted, by using the UP ARROW and DOWN ARROW keys, between 80 percent and 1 percent less than the setting for the warning level. The new level can be selected by pressing the ENTER key. The new level will not be selected if the Fn key is pressed instead. To adjust the WARNING LEVEL, press the ENTER key when this sub-item appears. The LCD will display the current purity level (in percent purity) at, or above which, the system will annunciate a warning condition. This value can be adjusted, by using the UP ARROW and DOWN ARROW keys, between 1 percent more than the setting for the alarm level and 99.9 percent. The new level can be selected by pressing the ENTER key. The new level will not be selected if the Fn key is pressed instead. The system will not permit the alarm and warning levels to have the same value; it will also not permit the alarm level to be higher than the warning level. • SYSTEM This item, when displayed, can be selected by pressing the ENTER key. If selected, five sub-items will be displayed: “MONITOR Tcell,” “SHOW FAULTS LOG,” HA0156P01 Rev. D 16 (Mode Menu Cont’d) “CLEAR FAULTS LOG,” “RUN DIAGNOSTICS” and “SHOW PROGRAM ID.” Pressing the ENTER key when a sub-item appears selects that sub-item. Selecting the sub-item MONITOR Tcell permits a real time readout of the temperature of the gas sensor cell. Press the Fn key to terminate. The GGA is a self-supervised system and can identify and trap detected faults in its operation. Whenever a fault is detected the TROUBLE LED is illuminated, the TROUBLE RELAY is de-energized, and a description of the fault is logged (stored and latched). Faults can be displayed by pressing the ENTER key when the sub-item SHOW FAULTS LOG is displayed. Fault conditions that can be detected include errors in the system’s 8- and 12-bit analog-todigital converters, power supply voltages, supervisory loop errors and gas sensor cell block temperature. Press the Fn key to terminate. The faults log can be erased by pressing the ENTER key when the sub-item CLEAR FAULTS LOG is displayed. If selected, the LCD will prompt CLEAR LOG? Press the ENTER key to clear all logged faults. Once executed the display will indicate LOG CLEARED for approximately two seconds and then go blank, leaving the system in the NORMAL mode. Pressing the Fn key instead will blank the display and place the system in the NORMAL mode without clearing the faults. Pressing the ENTER key when the sub-item RUN DIAGNOSTICS is displayed permits a readout of the GGA’s initial cell reference voltage, the output voltages of all power supplies, tests the system’s Normal, Trouble, Alarm and Warning relays, and the Membrane Keypad on the Display Panel. At any point press Fn to terminate testing. The test sequence is: 1. The LCD will display Vref=X.XXXVDC. This parameter is the voltage of the cell reference thermistor and was stored at the time of the last calibration of the cell (whether H2, CO2 or N2). 2. The LCD will display Vh2=X.XXXVDC. This parameter is the voltage of the hydrogen calibration constant and was stored at the time of the last calibration of the cell. 3. The LCD will display Vco2=X.XXXVDC. This parameter is the voltage of the carbon dioxide calibration constant and was stored at the time of the last calibration of the cell. 4. The LCD will display Vn2=X.XXXVDC. This parameter is the voltage of the nitrogen calibration constant and was stored at the time of the last calibration of the cell. 5. The LCD will display Vadc> X.XXVDC. This parameter is the reference voltage of the 12 bit analog-to-digital converter and will range between 3.97 and 4.22 VDC. 6. The LCD will display +5V> X.XXVDC. This parameter is the output of the +5 volt digital supply and will range between 4.50 and 5.50 VDC. 7. The LCD will display +12V> XX.XVDC. This parameter is the output of the +12 volt digital supply and will range between 10.8 and 13.2 VDC. 8. The LCD will display +15V> XX.XVDC. This parameter is the output of the +15 volt analog supply and will range between 13.5 and 16.5 VDC. 9. The LCD will display ”-15V> XX.XVDC. This parameter is the output of the -15 volt analog supply and will range between -13.5 and -16.5 VDC. 17 HA0156P01 Rev. D (Mode Menu Cont’d) For the above voltages, the LCD will flash an ERROR message alternately with the voltage if the measured voltage is out of limit. 10. The LCD will display “RELAY TEST …” The system will cause each relay to be energized. If no errors are detected, the LCD will display” RELAYS PASS.” If an error is detected, the LCD will display “RELAYS FAIL,” “FAILURE IN,” then “NORMAL RELAY,” “TROUBLE RELAY,” “ALARM RELAY” or “WARNING RELAY.” 11. The LCD will display “KEYPAD TEST …” Press each key on the Membrane Keypad on the DISPLAY PANEL, reserving the ENTER key for last (this key will terminate the test). As each key is pressed the LCD will echo the name of the key. Program instructions for the microcontroller within the GGA system are stored in Read Only Memory (ROM) chips located within the system. The program identification and revision level, in the format P_GGA Rev X.X, can be displayed by pressing the ENTER key when the sub-item SHOW PROGRAM ID is displayed. Pressing the Fn key terminates this item. REMINDER! Should the system go into trouble, access the menu items SHOW FAULTS LOG and RUN DIAGNOSTICS for more information. Cell Output Voltages The sensor cell is principally comprised of a sampling thermistor and a reference thermistor embedded in a temperature regulated cell block. The voltage derived from the reference thermistor (this voltage is displayed as “cr”) is used to compensate for any non-purity related variations in the voltage output of the sample thermistor (this voltage is displayed as “s”). When a cell is calibrated, the value of cr is stored in non-volatile memory as the parameter Vref. Subsequently, during normal operation, the real time value of cr is mathematically combined with Vref to form a term compensating s. This operation ensures long-term measurement accuracy of the sensor cell. The output voltages of these thermistors can be viewed directly (i.e., prior to any computation) in real time by pressing the UP arrow. This information is updated every half second and is displayed in the format s=X.XXX cr=X.XXX, where, again, s stands for the sample thermistor voltage and cr stands for the current value of the reference thermistor voltage. The display of these voltages may be canceled at any time by pressing the DOWN arrow. The parameter Vref is displayed during calibration and diagnostics. HA0156P01 Rev. D 18 Maintenance The Dual Hydrogen Control Panel (DHCP) is designed for reliable, trouble-free operation. Periodic checks and maintenance are easy. Following the required maintenance checks will ensure safe trouble free operation of this equipment. Daily Check and adjust DHCP analyzer and scavenging flow rates. See Flow Calibration. Check hydrogen purity. Weekly 1. Visually inspect the moisture indicators. A blue medium indicates dry hydrogen, while a pink medium indicates excessive moisture in the hydrogen gas sample that may affect the stability of the Generator Gas Analyzers. Replace or regenerate the Moisture Indicator and replace the Gas Purifier if the medium is pink. Refer to Removal of Moisture Indicators and Gas Purifiers. 2. Blow down purifiers by first removing cap at the base of the isolation valve and then open the valve itself. It is advisable to have a container available to collect any fluid contained within the purifier. CAUTION: THE PURIFIERS MAY CONTAIN HYDROGEN GAS; USE PROPER SAFETY PRECAUTIONS. Every Six Months 1. Check Analyzer power and calibration voltages. 2. Calibrate Generator Gas Analyzers, as necessary. 3. Run Diagnostics. When the Generator is Down During periods when the generator is shut down, it is recommended that either a) power be maintained to the DHCP, or b) the DHCP be isolated by placing all isolation valves in “off” position. 19 HA0156P01 Rev. D Component Replacement Instructions The hydrogen analyzer sensing units, input/output circuit board, processor circuit boards, power supplies and intrinsically safe barriers are located inside the main junction box. To gain access to the inside of the main junction box for service, remove the 32, 3/4-inch captive bolts. Two guide studs assist with removal/replacement. CAUTION! Do not scratch sealing surfaces on the main junction box. The main junction box lid weighs 50 lbs (22.7 kg). Take precautions during removal. Prior to opening the main junction box, remove power from the HCP and ensure the system is free of hydrogen. Removing a Gas Analyzer Sensor To remove a hydrogen analyzer from a flameproof enclosure: 1. Disconnect AC input power. 2. Manually close isolation valves HV-2979, HV-2980, HV-2982 and HV-2981. 3. Remove the cover of the main junction box. 4. Remove 4 screws used to secure processor and I/O boards (see Figure 2). 5. Remove the 12-pin cable connector from the sensor circuit board. 6. Remove inlet and outlet tubing connections from the analyzer with a 7/16-inch wrench. 7. Remove mounting hardware (4 slotted screws). 8. To reinstall sensor cell, reverse above process, then leak check. Removing a Processor Circuit Board To remove a processor circuit board from the main junction box: 1. Disconnect AC input power. 2. Close isolation valves HV-2985, HV-2986, HV-2983 and HV-2973A. 3. Remove the main junction box cover. 4. To remove the upper processor board, disconnect the 40-pin ribbon cable and remove the 4 nuts (11/32). 5. Install the new processor board in reverse order. 6. Check that pin #1 on the ribbon connector is properly aligned. HA0156P01 Rev. D 20 Removing the Input/Output (I/O) Circuit Board 1. Disconnect AC input power. 2. Close Isolation valves HV-2985, HV-2986, HV-2983 and HV-2973A. 3. Remove the main junction box cover. 4. Remove the processor board. Disconnect the 60-pin ribbon cable and 4 nuts (11/32). 5. Remove the 8 slotted screws, which hold the board in place and spacers in place (4 on top, 4 on bottom of board). 6. Remove all wiring connections to the terminal blocks on the Input/Output board. 7. Disconnect power supply connections to the Input/Output board. 8. Disconnect the analyzer cell, 12-pin headers. 9. The Input/Output board can now be removed. Install the new input/Output board in reverse order. Removing Solenoid Valves Coils All solenoid valves are connected in the main junction box. Once the inoperable solenoid valve is located, remove AC power and manually close all isolation valves. 1. Reach under the solenoid and remove the top cap by prying it off. 2. Push the solenoid valve body down and slide the nameplate/retainer off. 3. Open the closest (small, adjacent) junction box to the solenoid valve and locate the 3 solenoid valve wires. 4. Cut and strip the wires. 5. Install the new solenoid valve. 6. Splice the wires together using a butt splice. 7. Replace the (small, adjacent) junction box cover. 8. Restore AC power and manually reopen the isolation valves. Removing Moisture Indicators Three moisture indicators and three gas purifiers are located on the front of the panel (Figure 1). To remove moisture indicators: 1. Disconnect AC input power. 2. Manually close all isolation valves. 21 HA0156P01 Rev. D (Removing Moisture Indicators cont’d) 3. Unscrew moisture indicator by hand. 4. Replace moisture indicator by screwing in the replacement by hand. 5. Open isolation valves HV-2971, HV-2972, HV-2979, HV-2980, HV-2973, HV-2974, HV2981, HV-2982 and HV-2978. 6. Perform leak check. 7. Reconnect AC input power. Removing Gas Purifiers 1. Disconnect AC input power. 2. Manually close all isolation valves. 3. Release pressure within purifier housing by opening drain at HV-2971A, HV-2972A or HV2973A, as appropriate. 4. Remove 8 bolts (1/2” hex) at bottom flange of purifier housing. 5. Remove purifier cartridge and two associated gaskets. 6. Replace cartridge and gaskets. 7. Resecure bolts (to 120” lbs torque). 8. Close drain. 9. Open isolation valves HV-2971, HV-2972, HV-2979, HV-2980, HV-2973, HV-2974, HV2981, HV-2982 and HV-2978. 10. Perform leak check. 11. Reconnect AC input power. Removing Flow Meters 1. Disconnect AC input power. 2. Manually close all isolation valves. 3. Remove tubing fittings and locking nuts from the back of the flowmeter. 4. Withdraw flowmeter from the front side of the DHCP. 5. To install replacement, reverse above process. 6. Perform leak check. 7. Reconnect AC input power. HA0156P01 Rev. D 22 Figures The figures that follow depict the DHCP and its components. All references in this document refer to the following figures. Please note that figures 11-25 depict portions of the DHCP. These figures are provided for easy reference in configuring isolation valves and switches. Please note that isolation valve handles and actual switches are not shown. Instead, “on,” “off” and arrow graphics are provided. Contact Environment One with questions relating to any of the figures relating to this manual. 23 HA0156P01 Rev. D HA0156P01 Rev. D 24 LOOKING DOWN AT BASE PLATE FRONT VIEW TURBINE END FLOW TOTAL FLOW Figure 1 - DHCP Outline COLLECTOR END FLOW TURBINE END ANALYAER #1 NORMAL AC POWER H2 IN AIR RESET COLLECTOR END ANALYAER #2 NORMAL TROUBLE AC POWER H2 IN AIR GAS PURITY ALARM WARNING WARNING CALIBRATE PURGE CALIBRATE H 2 IN C0 2 H2 PURGE H 2 IN C02 H2 C0 2 C0 2 AIR IN C0 2 N2 AIR IN C02 N2 Fn Fn ENTER ENTER Generator Gas Analyzer TURBINE END LINE TROUBLE GAS PURITY RESET ALARM TURBINE END LOW FLOW Generator Gas Analyzer TURBINE END HIGH FLOW OFF CONFIRMATION TURBINE END CONFIRMATION OFF OFF CONFIRMATION COLLECTOR END COLLECTOR END HIGH FLOW COLLECTOR END LOW FLOW COLLECTOR END LINE OFF SIDE VIEW OFF CALIBRATION GASES NITROGEN FAN DIFFERENTIAL PRESSURE GAGE FAN DIFFERENTIAL TRANSMITTER TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE OFF CARBON DIOXIDE OFF HYDROGEN OFF PURGE CASE OFF OFF TURBINE END MOISTURE INDICATOR CASE MOISTURE INDICATOR COLLECTOR END MOISTURE INDICATOR TURBINE END PURIFIER CASE PURIFIER COLLECTOR END PURIFIER CASE - CAL / PURGE HA0156P01 Rev D Page 25 Figure 4 - DHCP Wiring Diagram HD0156P01 Rev D Page 29 Figure 4a - DHCP Wiring Diagram HA0156P01 Rev D Page 31 Figure 5 - DHCP Piping Schematic HA0156P01 Rev D Page 33 NORMAL AC POWER H2 IN AIR RESET TROUBLE GAS PURITY ALARM WARNING CALIBRATE PURGE H 2 IN C0 2 H2 C0 2 N2 AIR IN C0 2 Fn ENTER Generator Gas Analyzer Figure 8 - DHCP Display Descriptions Figure 8A - Display Indicators Indicator Status Ref. 1 AC Power Lit when the display is powered and functioning properly Normal Lit when the GGA is measuring the concentration of hydrogen in air Alarm Lit when the GGA is measuring hydrogen in air and the concentration is below the warning level 1 Warning Lit when the GGA is in measuring hydrogen in air and the concentration is below the warning level 2 Trouble Lit when the GGA detects an abnormal condition 3, 4, 5 Calibrate H 2 Lit when the GGA is calibrating against a 100% hydrogen standard Calibrate CO2 Lit when the GGA is calibrating against a 100% carbon dioxide standard Calibrate N 2 Lit when the GGA is calibrating against a 100% nitrogen standard Purge H 2 in CO 2 Lit when the GGA is measuring the concentration of hydrogen in carbon dioxide Purge Air in CO2 Lit when the GGA is measuring the concentration of nitrogen in carbon dioxide Gas Purity Three-digit gas purity indicator (0 to 99.9%) LCD Display Displays the current menu selection when the menu is active Figure 8B - Display Keys Key Function Reset Clear the Alarm and Warning conditions in Normal mode Fn Activate the menu Enter Select a menu item UP Arrow Used with some menu options to increase the value of a constant DOWN Arrow Used with some menu options to decrease the value of a constant 37 HA0156P01 Rev. D Figure 9 - DHCP Status Condition 2 3 Typical Cause Indicators Affected 1 Alarm The GGA is measuring hydrogen in air and the concentration is below the alarm level Alarm LED + Alarm Relay 2 Warning The GGA is measuring hydrogen in air and the concentration is below the warning level Warning LED + Warning Relay 3 Tcell ERROR The sensor cell is not at a temperature of 55 ±0.5 degrees centigrade Trouble LED + Trouble Relay 4 Power Supply Problem2 One or more power supplies are not within tolerance Trouble LED + Trouble Relay 5 Lower Error3 The GGA is detecting a communication error while trying to talk to the I/O board or the display. One or more relays are defective. Trouble LED + Trouble Relay Run diagnostics to identify power supply problems. Run diagnostics to identify which loop error is present. HA0156P01 Rev. D 38 Figure 10 - DHCP Customer Contacts Contact 4 Status Ref. 4 Alarm General Purpose Energized when the GGA is measuring hydrogen in air and 1 the concentration is below the alarm level Warning General Purpose Energized when the GGA is measuring hydrogen in air and 2 the concentration is below the warning level Trouble General Purpose De-energized when the GGA detects an abnormal condition 3, 4, 5 See Figure 9 39 HA0156P01 Rev. D TURBINE END LINE TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END CONFIRMATION OFF HV-2972 CONFIRMATION COLLECTOR END OFF COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES CARBON DIOXIDE NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 OFF HV-2985 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE TURBINE END LINE COLLECTOR END HIGH FLOW TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END HV-2986 PURGE OFF HV-2984 CASE OFF HV-2983 OFF HV-2978 CASE - CAL / PURGE CONFIRMATION OFF HV-2972 OFF HYDROGEN CONFIRMATION COLLECTOR END OFF COLLECTOR END HIGH FLOW COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE OFF HV-2985 CASE - CAL / PURGE CARBON DIOXIDE OFF HV-2986 HYDROGEN OFF HV-2984 PURGE CASE OFF HV-2983 OFF HV-2978 TURBINE END LINE TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END CONFIRMATION OFF HV-2972 CONFIRMATION COLLECTOR END OFF COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES CARBON DIOXIDE NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 OFF HV-2985 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE TURBINE END LINE COLLECTOR END HIGH FLOW TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END HV-2986 PURGE OFF HV-2984 CASE OFF HV-2983 OFF HV-2978 CASE - CAL / PURGE CONFIRMATION OFF HV-2972 OFF HYDROGEN CONFIRMATION COLLECTOR END OFF COLLECTOR END HIGH FLOW COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE OFF HV-2985 CASE - CAL / PURGE CARBON DIOXIDE OFF HV-2986 HYDROGEN OFF HV-2984 PURGE CASE OFF HV-2983 OFF HV-2978 TURBINE END LINE TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END CONFIRMATION OFF HV-2972 CONFIRMATION COLLECTOR END OFF COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES CARBON DIOXIDE NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 OFF HV-2985 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE TURBINE END LINE COLLECTOR END HIGH FLOW TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END HV-2986 PURGE OFF HV-2984 CASE OFF HV-2983 OFF HV-2978 CASE - CAL / PURGE CONFIRMATION OFF HV-2972 OFF HYDROGEN CONFIRMATION COLLECTOR END OFF COLLECTOR END HIGH FLOW COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE OFF HV-2985 CASE - CAL / PURGE CARBON DIOXIDE OFF HV-2986 HYDROGEN OFF HV-2984 PURGE CASE OFF HV-2983 OFF HV-2978 TURBINE END LINE TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END CONFIRMATION OFF HV-2972 CONFIRMATION COLLECTOR END OFF COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES CARBON DIOXIDE NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 OFF HV-2985 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE TURBINE END LINE COLLECTOR END HIGH FLOW TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END HV-2986 PURGE OFF HV-2984 CASE OFF HV-2983 OFF HV-2978 CASE - CAL / PURGE CONFIRMATION OFF HV-2972 OFF HYDROGEN CONFIRMATION COLLECTOR END OFF COLLECTOR END HIGH FLOW COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE OFF HV-2985 CASE - CAL / PURGE CARBON DIOXIDE OFF HV-2986 HYDROGEN OFF HV-2984 PURGE CASE OFF HV-2983 OFF HV-2978 TURBINE END LINE TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END CONFIRMATION OFF HV-2972 CONFIRMATION COLLECTOR END OFF COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES CARBON DIOXIDE NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 OFF HV-2985 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE TURBINE END LINE COLLECTOR END HIGH FLOW TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END HV-2986 PURGE OFF HV-2984 CASE OFF HV-2983 OFF HV-2978 CASE - CAL / PURGE CONFIRMATION OFF HV-2972 OFF HYDROGEN CONFIRMATION COLLECTOR END OFF COLLECTOR END HIGH FLOW COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE OFF HV-2985 CASE - CAL / PURGE CARBON DIOXIDE OFF HV-2986 HYDROGEN OFF HV-2984 PURGE CASE OFF HV-2983 OFF HV-2978 TURBINE END LINE TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END CONFIRMATION OFF HV-2972 CONFIRMATION COLLECTOR END OFF COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES CARBON DIOXIDE NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 OFF HV-2985 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE TURBINE END LINE COLLECTOR END HIGH FLOW TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END HV-2986 PURGE OFF HV-2984 CASE OFF HV-2983 OFF HV-2978 CASE - CAL / PURGE CONFIRMATION OFF HV-2972 OFF HYDROGEN CONFIRMATION COLLECTOR END OFF COLLECTOR END HIGH FLOW COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE OFF HV-2985 CASE - CAL / PURGE CARBON DIOXIDE OFF HV-2986 HYDROGEN OFF HV-2984 PURGE CASE OFF HV-2983 OFF HV-2978 TURBINE END LINE TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END CONFIRMATION OFF HV-2972 CONFIRMATION COLLECTOR END OFF COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES CARBON DIOXIDE NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 OFF HV-2985 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE TURBINE END LINE COLLECTOR END HIGH FLOW TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END HV-2986 PURGE OFF HV-2984 CASE OFF HV-2983 OFF HV-2978 CASE - CAL / PURGE CONFIRMATION OFF HV-2972 OFF HYDROGEN CONFIRMATION COLLECTOR END OFF COLLECTOR END HIGH FLOW COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE OFF HV-2985 CASE - CAL / PURGE CARBON DIOXIDE OFF HV-2986 HYDROGEN OFF HV-2984 PURGE CASE OFF HV-2983 OFF HV-2978 TURBINE END LINE TURBINE END LOW FLOW TURBINE END HIGH FLOW HO-2972 HO-2971 OFF CONFIRMATION TURBINE END CONFIRMATION OFF HV-2972 CONFIRMATION COLLECTOR END OFF COLLECTOR END HIGH FLOW COLLECTOR END LOW FLOW HO-2973 HO-2974 COLLECTOR END LINE OFF HV-2987 OFF HV-2974 HV-2971 HV-2973 CALIBRATION GASES NITROGEN FAN DIFFERENTIAL PRESSURE GAGE PDI-292 TURBINE END-CASE/CAL/PURGE COLLECTOR END-CASE/CAL/PURGE OFF HV-2985 CASE - CAL / PURGE CARBON DIOXIDE OFF HV-2986 HYDROGEN OFF HV-2984 PURGE CASE OFF HV-2983 OFF HV-2978 Tag Number FI-2973 FI-2971 FI-2972 HV-2971 HV-2971A HV-2972 HV-2972A HV-2973 HV-2973A HV-2974 HV-2979 HV-2980 HV-2981 HV-2982 HV-2983 HV-2984 HV-2985 HV-2986 HV-2987 QT-290A QT-290B HO-2971 HO-2972 HO-2974 HO-2973 FY-2971 FY-2973 FY-2972 FY-2974 FY-2981 PDT-292 PDI-292 MI-2971 MI-2972 MI-2973 Item Description Flowmeter FM1 Indicator/Metering Valve FM2 Indicator/Metering Valve FM3 Isolation Valve IV1 Isolation Valve IV2 Isolation Valve IV11 Isolation Valve IV4 Isolation Valve IV10 Isolation Valve IV9 Isolation Valve IV12 Isolation Valve IV14 Isolation Valve IV15 Isolation Valve IV17 Isolation Valve IV16 Isolation Valve IV8 Isolation Valve IV5 Isolation Valve IV6 Isolation Valve IV7 Isolation Valve IV20 Analyzer Cell #1 Analyzer Cell #2 Metering Valve MV1 Metering Valve MV2 Metering Valve MV3 Metering Valve MV4 Solenoid Valve SV1 Solenoid Valve SV2 Solenoid Valve SV3 Solenoid Valve SV4 Solenoid Valve SV5 Differential Trans. FT1 Differential Gage FG1 Moisture Indicator MI1 Moisture Indicator MI2 Moisture Indicator MI3 HA0040P02 HA0040P01 HA0040P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HA0011P01 HC0021G01 HC0021G01 HA0010P01 HA0010P01 HA0010P01 HA0010P01 HA0014P01 HA0014P01 HA0016P01 HA0016P01 HA0016P01 HA0058P08 HA0041P01 HA0013P01 HA0013P01 HA0013P01 Manufacturer Number Brooks Instruments1355FA30CNA1A Brooks Instruments1355FFG4CNE1A Brooks Instruments1355FFG4CNE1A Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Parker 4F-B6LJ-V-SSP Environment One HC0021G01 Environment One HC0021G01 Parker 4M-V4AN-V-SS Parker 4M-V4AN-V-SS Parker 4M-V4AN-V-SS Parker 4M-V4AN-V-SS Automatic Switch EFHTL-8262G7 12060 Automatic Switch EFHTL-8262G7 12060 Automatic Switch EFHTL-8320G200 12060 Automatic Switch EFHTL-8320G200 12060 Automatic Switch EFHTL-8320G200 12060 Yokogawa Midwest 130-SC-10-00 Matheson 465 Matheson 465 Matheson 465 Supplier Manufacturer Drawing No. 540 to 5400 cc/min H2 flowmeter 90 to 900 cc/min H2 flowmeter/metering valve 90 to 900 cc/min H2 flowmeter/metering valve 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4” female isolation ball valve, SS 1/4” female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS 1/4" female isolation ball valve, SS Analyzer Cell Assembly Analyzer Cell Assembly 1/4" male-NPT ports metering valve, SS 1/4" male-NPT ports metering valve, SS 1/4" male-NPT ports metering valve, SS 1/4" male-NPT ports metering valve, SS 2 way, NC, 120V, 60 Hz solenoid valve 2 way, NC, 120V, 60 Hz solenoid valve 3 way, 120V, 60Hz solenoid valve 3 way, 120V, 60Hz solenoid valve 3 way, 120V, 60Hz solenoid valve 0 to 30" H2O, 9.5" normal differential transmitter 0 to 30" H2, dual scale differential pressure gage 1/4" NPT, male/female moisture indicator 1/4" NPT, male/female moisture indicator 1/4" NPT, male/female moisture indicator Description Figure 26 - Parts List HA0156P01 Rev. D 48 49 HA0156P01 Rev. D Replacement Plug Turbine End Purifier FU1 Case Purifier FU2 Collector End Purifier FU3 Cartridge Heater Heater I/O PC Board Controller Board Display Panel Display Board Assembly Power Supply Power Supply IS Barrier, Single IS Barrier, Single IS Barrier, Single IS Barrier, Single IS Barrier, Dual IS Barrier, Dual IS Barrier, Dual IS Barrier, Dual Flame Arrestor Housing Flame Arrestor Housing Flame Arrestor Filters Thermal Protector 220 VAC Transformer Item Description HA-45P1-1 HA-45P1-2 HA-45P1-3 HA-45P1-4 HA-45P2-1 HA-45P2-2 HA-45P2-3 HA-45P2-4 HB-18P1-1 HB-18P1-2 HA-65P1 HA-46P1 HA-106P1 HA-17P1-1 HA-17P1-2 Tag Number HA0013P02 HA0139P01 HA0139P01 HA0139P01 HA0139P02 HA0017P01 HA0017P02 HD0043G01 HD0039G01 HB0026G01 HD0138G03 HA0027P01 GA0109P03 HA0045P01 HA0045P01 HA0045P01 HA0045P01 HA0045P02 HA0045P02 HA0045P02 HA0045P02 HB0018P01 HB0018P02 HA0065P01 HA0046P01 HA0106P01 Matheson Matheson Matheson Matheson Matheson Chromalox Chromalox Environment One Environment One Environment One Environment One Tri-Mag Inc. Polytronics Crouse Hinds Crouse Hinds Crouse Hinds Crouse Hinds Crouse Hinds Crouse Hinds Crouse Hinds Crouse Hinds Environment One Environment One Leeds & Northrup Canadian Therm. Signal Supplier Manufacturer Drawing No. PLU-0070-XX 460 460 460 462 AEPS-024-220-917 AEPS-024-220-917 HD0043G01 HD0039G01 HB0026G01 HD0138G03 UV420-7 P33 1098 SB19140M1250 SB19140M1250 SB19140M1250 SB19140M1250 SB59240M0766 SB59240M0766 SB59240M0766 SB59240M0766 HB0018P01 HB0018P01 85104 E21-65-2-5 M4L-2-3 Manufacturer Number Replacement indicator plug 1/4" female NPTfilter/purifier 1/4" female NPT filter/puifier 1/4" female NPT filter/puifier Replacement cartridge 120V, 220 watt explosion proof heater 220V, 220 watt explosion proof heater input/output printed circuit board analyzer processor printed circuit board analyzer display panel analyzer display board 12 VDC power supply 15 VDC power supply single channel, isolation barrier single channel, isolation barrier single channel, isolation barrier single channel, isolation barrier dual channel, isolation barrier dual channel, isolation barrier dual channel, isolation barrier dual channel, isolation barrier flame Arrestor housing flame Arrestor housing flame Arrestor filters 65 c thermostat 220 VAC Transformer Description HA0156P01 Rev. D 50 A PCC Flow Technologies, Inc. Company Environment One Corporation 2773 Balltown Road Niskayuna, New York USA 12309–1090 Tel: (01) 518.346.6161 FAX: 518.346.6188 www.eone.com