File 0140 L1 L2 GND L3 L1 OFF F U 1 F U 2 460 V H1 H3 230 V H2 H1 H4 H3 H2 A1 B1 15 B2 B2 STOP B3STOP STOP 1B1 15 Supply voltage ON H4 START 2 M OL 3 16 18 B3 A2 16 18 Electrostatically Shielded Transformer F U 5 Power On F U 6 X1A F U 4 H M L 21 31 43 53 14 22 32 44 54 AC 1 Status (N.O. or N.C.) 2 5 6 8 9 10 12 14 (+) 13 (–) A1/+ 15 25 Z1 Z2 NONHAZARDOUS LOCATIONS FIBER OPTIC TRANSCEIVER Supply voltage FIBER OPTIC PUSH BUTTON, SELECTOR SWITCH, LIMIT SWITCH, ETC. A1 15 B2 B1 B3 15 H 16 18 B3 A2 16 18 CLASS 9005 TYPE FT B1 B2 16 18 26 28 A2/– L M Vs 2 Levels FIBER OPTIC CABLE ELECTRICAL CONNECTIONS 1 3 5 L1 L2 L3 A1 BOUNDARY SEAL TO BE IN ACCORDANCE WITH ARTICLE 501-5 OF THE NATIONAL ELECTRICAL CODE L2 A1 A2 A2 L3 3 L1 T1 T2 T3 L2 1CT M L1 CIRCUIT BREAKER OR DISCONNECT SWITCH FIBER OPTIC CABLE L2 4 Optional HAZARDOUS LOCATIONS CLASS I GROUPS A, B, C & D CLASS II GROUPS E, F & G CLASS III X2 Green X1 M 2 Levels 13 X3 Orange LOAD Location X2A 22 14 R F U 3 L1 21 13 START Optional Connection X1 115 V X2 AC L2 START T1 T2 M MOTOR 3CT M L3 T3 SOLID STATE OVERLOAD RELAY 1 TO 120 V SEPARATE CONTROL MOTOR STOP 2 T1 T1 T2 T3 2 4 6 Wiring Diagram Book www.epdatech.com T2 START OT* T3 M M * OT is a switch that opens when an overtemperature condition exists (Type MFO and MGO only) For more books join our telegram group Click here to join https://t.me/engubook TRADEMARKS QWIK-STOP® and ALHPA-PAK® are registered trademarks of Square D. NEC® is a registered trademark of the National Fire Protection Association. COPYRIGHT NOTICE © 1993 Square D. All rights reserved. This document may not be copied in whole or in part, or transferred to any other media, without the written permission of Square D. PLEASE NOTE: Electrical equipment should be serviced only by qualified electrical maintenance personnel, and this document should not be viewed as sufficient instruction for those who are not otherwise qualified to operate, service or maintain the equipment discussed. Although reasonable care has been taken to provide accurate and authoritative information in this document, no responsibility is assumed by Square D for any consequences arising out of the use of this material. www.epdatech.com Table of Contents Standard Elementary Diagram Symbols ..................... 1-3 NEMA and IEC Markings and Schematic Diagrams ...... 4 Control and Power Connection Table 4 Terminology ...................................................................... 5 Examples of Control Circuits .......................................... 6 2-Wire Control 6 3-Wire Control 6-9 Shunting Thermal Units During Starting Period 10 Overcurrent Protection for 3-Wire Control Circuits 11 AC Manual Starters and Manual Motor Starting Switches ........................................................... 12 Class 2510 12 Class 2511 and 2512 13 2-Speed AC Manual Starters and IEC Motor Protectors...................................................... 14 Class 2512 and 2520 14 GV1/GV3 14 Drum Switches................................................................ 15 Class 2601 15 DC Starters, Constant and Adjustable Speed.............. 16 Class 7135 and 7136 16 Reversing DC Starters, Constant and Adjustable Speed ........................................................... 17 Class 7145 and 7146 17 Mechanically Latched Contactors ................................ 18 Class 8196 18 Medium Voltage Motor Controllers.......................... 18-25 Class 8198 18-25 Solid State Protective Relays ................................... 26-27 Class 8430 26-27 General Purpose Relays ................................................ 28 Class 8501 28 NEMA Control Relays..................................................... 29 Class 8501 and 9999 29 General Purpose Relays ................................................ 30 Class 8501 30 Sensing Relays............................................................... 30 RM2 LA1/LG1 30 IEC Relays.................................................................. 31-32 IEC D-Line Control Relays 31 Class 8501 32 Type P Contactors..................................................... 33-35 Class 8502 33-35 Class 8702 35 Type T Overload Relays............................................ 33-35 Class 9065 33-35 Type S AC Magnetic Contactors.............................. 36-40 Class 8502 36-40 IEC Contactors .......................................................... 41-42 IEC Contactors and Auxiliary Contact Blocks 41 Input Modules and Reversing Contactors 42 Type S AC Magnetic Starters ................................... 43-50 Class 8536 43-50 8538 and 8539 45,49 1-Phase, Size 00 to 3 43 2-Phase and 3-Phase, Size 00 to 5 44 3-Phase, Size 6 45 3-Phase, Size 7 46 3-Phase Additions and Special Features 47-50 Integral Self-Protected Starters ............................... 51-57 Integral 18 State of Auxiliary Contacts 51-52 Integral 32 and 63 State of Auxiliary Contacts 53-54 Wiring Diagrams 55-57 Type S AC Combination Magnetic Starters ............ 58-59 Class 8538 and 8539 58-59 3-Phase, Size 0-5 58 3-Phase Additions and Special Features 59 Reduced Voltage Controllers ................................... 60-66 Class 8606 Autotransformer Type 60-61 Class 8630 Wye-Delta Type 62-63 Class 8640 2-Step Part-Winding Type 64 Class 8647 Primary-Resistor Type 65 Class 8650 and 8651 Wound-Rotor Type 66 Solid State Reduced Voltage Starters .......................... 67 Class 8660 ALPHA PAK®, Type MD-MG 67 Solid State Reduced Voltage Controllers ............... 68-70 Class 8660 Type MH, MJ, MK and MM 68-70 ® www.epdatech.com i Table of Contents Type S AC Reversing Magnetic Starters71-72 Class 873671-72 2- and 3-Pole71 3- and 4-Pole72 Pneumatic Timing Relays and Solid State Industrial Timing Relays95-96 Class 905095-96 Timers97 Class 905097 Type S AC 2-Speed Magnetic Starters73-76 Class 881073-76 Special Control Circuits75-76 Transformer Disconnects98 Class 907098 Multispeed Motor Connections76-77 1- Phase76 3-Phase76-77 Enclosure Selection Guide99 Conductor Ampacity and Conduit Tables100-101 Programmable Lighting Controllers78 Class 886578 Wire Data102 AC Lighting Contactors79-81 Class 890379-81 Load Connections79 Control Circuit Connections80 Panelboard Type Wiring81 Electrical Formulas103-104 Electronic Motor Brakes81-82 Class 8922 QWIK-STOP®81-82 List of Tables Table 1 Standard Elementary Diagram Symbols 1 Table 2 NEMA and IEC Terminal Markings 4 Table 3 NEMA and IEC Controller Markings and Elementary Diagrams 4 Fiber Optic Transceivers82 Class 900582 Table 4 Control and Power Connections for Across-the-Line Starters, 600 V or less4 Table 5 Motor Lead Connections 64 Photoelectric and Inductive Proximity Switches83 Class 900683 Table 6 Enclosures for Non-Hazardous Locations 99 Table 7 Enclosures for Hazardous Locations 99 Table 8 Conductor Ampacity100 Table 9 Ampacity Correction Factors 101 Table 10 Adjustment Factors 101 Table 11 Ratings for 120/240 V, 3-Wire, Single-Phase Dwelling Services101 Table 12 AWG and Metric Wire Data 102 Table 13 Electrical Formulas for Amperes, Horsepower, Kilowatts and KVA 103 Table 14 Ratings for 3-Phase, Single-Speed, Full-Voltage Magnetic Controllers for Nonplugglng and Nonjogging Duty 103 Table 15 Ratings for 3-Phase, Single-Speed, Full-Voltage Magnetic Controllers for PlugStop, Plug-Reverse or Jogging Duty 104 Table 16 Power Conversions 104 Duplex Motor Controllers82 Class 894182 Photoelectric and Proximity Sensors84-89 XS, XSC, XSF and XSD84 XS and XTA85 SG, ST and XUB86 XUM, XUH, XUG, XUL and XUJ87 XUE, XUR, XUD, XUG and XUE S88 XUV89 Limit Switches and Safety Interlocks90-92 Class 900791 XCK and MS92 Pressure Switches and Transducers93 Class 9012, 9013, 9022 and 902593 Level Sensors and Electric Alternators94 Class 9034 and 903994 ® ii www.epdatech.com For more books join our telegram group Click here to join https://t.me/engubook Standard Elementary Diagram Symbols The diagram symbols in Table 1 are used by Square D and, where applicable, conform to NEMA (National Electrical Manufacturers Association) standards. Table 1 Standard Elementary Diagram Symbols SWITCHES Disconnect Circuit Interrupter SELECTORS Circuit Breakers w/ Thermal OL Circuit Breakers w/ Magnetic OL 2-Position Selector Switch J K A1 A2 J K A1 A2 Pressure & Vacuum Switches N.O. N.C. Liquid Level Switches N.O. Temperature Actuated Switches N.O. N.C. N.C. 3-Position Selector Switch K L J A1 A2 J Limit Switches N.O. Speed (Plugging) N.C. F F Anti-Plug A1 F A2 K L 2-Position Selector Push Button Held Closed A Held Open R Flow Switches N.O. N.C. R N.O. 1 2 3 4 Selector Position Foot Switches A N.C. B B Push Button Contacts 1-2 3-4 Free Depressed Free Depressed = contact closed PUSH BUTTONS – MOMENTARY CONTACT N.O. N.C. N.O. & N.C. (double circuit) Mushroom Head Wobble Stick PUSH BUTTONS – MAINTAINED CONTACT 2 Single Circuits Illuminated 1 Double Circuit R PILOT LIGHTS Non Push-to-Test INSTANT OPERATING CONTACTS Push-to-Test w/ Blowout N.O. N.C. w/o Blowout N.O. N.C. TIMED CONTACTS Contact action retarded after coil is: Energized Deenergized N.O.T.C. A N.C.T.O. N.O.T.O. N.C.T.C. G (indicate color by letter) www.epdatech.com 1 Standard Elementary Diagram Symbols Table 1 Standard Elementary Diagram Symbols (cont'd) TRANSFORMERS INDUCTORS Iron Core Auto Air Core Iron Core Air Core OVERLOAD RELAYS Thermal Current Dual Voltage AC MOTORS Single Phase Magnetic 3-Phase Squirrel Cage 2-Phase, 4-Wire Wound Rotor DC MOTORS Armature Shunt Field (show 4 loops) Series Field (show 3 loops) Commutating or Compensating Field (show 2 loops) WIRING Not Connected Connected Power Control Terminal CAPACITORS Fixed Ground Mechanical Connection Mechanical Interlock Connection RESISTORS Adjustable Fixed Heating Element Adjustable, by Fixed Taps Rheostat, Potentiometer or Adjustable Taps RES H RES RES SEMICONDUCTORS Diode or Half Wave Rectifier Tunnel Diode Full Wave Rectifier NPN Transistor C AC + DC Zener Diode DC B Bidirectional Breakdown Diode Triac PNP Transistor UJT, N Base C SCR Gate Turn-Of Thyristor A B2 G E AC 2 Photosensitive Cell E B1 E UJT, P Base B2 E B PUT www.epdatech.com B1 K Standard Elementary Diagram Symbols Table 1 Standard Elementary Diagram Symbols (cont'd) OTHER COMPONENTS Bell Annunciator Buzzer Horn, Alarm, Siren,etc. Meter (indicate type by letters) VM + Battery – Fuse Meter Shunt Thermocouple SUPPLEMENTARY CONTACT SYMBOLS SPST, N.O. Single Break Double Break SPST, N.C. Single Break Double Break SPDT Single Break Double Break DPST, 2 N.O. Single Break Double Break DPST, 2 N.C. Single Break Double Break DPDT Single Break Double Break IEC SYMBOLS Push Buttons N.C. N.O. Coil Aux. Contacts N.O. N.C. Contactor Breakers STATIC SWITCHING CONTROL Limit Switch, N.O., Static Control Static switching control is a method of switching electrical circuits without the use of contacts, primarily by solid state devices. To indicate static switching control, use the symbols shown in this table, enclosing them in a diamond as shown. TERMS SPST: SPDT: DPST: DPDT: Single Pole, Single Throw Single Pole, Double Throw Double Pole, Single Throw Double Pole, Double Throw N.O.: N.C.: T.O.: T.C.: Normally Open Normally Closed Timed Open Timed Closed www.epdatech.com PUT: SCR: Triac: UJT: Programmable Unijunction Transistor Silicon Controlled Rectifier Bidirectional Triode Thyristor Unijunction Transistor 3 NEMA and IEC Markings and Schematic Diagrams Control and Power Connection Table Table 2 NEMA and IEC Terminal Markings NEMA L1 L2 L3 T1 T2 T3 No standard designation No specific marking Alphanumeric, corresponding to incoming line and motor terminal designations Control Terminals Power Terminals Coil Terminals IEC 1 3 5 2 4 6 A1 14 A1 A3 A1 B1 A2 B2 22 Single digit numeric, odd for supply lines, even for load connections 2-digit numeric, 1st designates sequence, 2nd designates function (1-2 for N.C., 3-4 for N.O.) Power Terminals Control Terminals Table 3 A1 A2 A2 A3 A2 One Winding Tapped Winding Tapped Winding Two Windings Coil Terminals NEMA and IEC Controller Markings and Elementary Diagrams NEMA 3 1/L1 L2 L1 L3 L2 START 1 2 T1 T2 STOP 2 3 M OL T3 Typical Controller Markings Typical Elementary Diagram IEC A1 1 3 5 13 21 A2 2 4 6 14 22 11 STOP 12 23 START Table 4 96 Typical Elementary Diagram Control and Power Connections for Across-the-Line Starters, 600 V or less (From NEMA standard ICS 2-321A.60) Line Markings Ground, when used Motor Running Overcurrent, units in: 1 element 2 element 3 element Control Circuit Connected to For Reversing, Interchange Lines 4 A2 95 24 23 Typical Controller Markings 24 A1 1-Phase 2-Phase, 4-Wire 3-Phase L1, L2 L1, L3: Phase 1 L2, L4: Phase 2 L1, L2, L3 L1 is always ungrounded — L2 L1 — — — L1, L4 — — — L1, L2, L3 L1, L2 L1, L3 L1, L2 — L1, L3 L1, L3 www.epdatech.com For more books join our telegram group Click here to join https://t.me/engubook Terminology WIRING DIAGRAM A wiring diagram shows, as closely as possible, the actual location of all component parts of the device. The open terminals (marked by an open circle) and arrows represent connections made by the user. Since wiring connections and terminal markings are shown, this type of diagram is helpful when wiring the device or tracing wires when troubleshooting. Bold lines denote the power circuit and thin lines are used to show the control circuit. Black wires are conventionally used in power circuits and red wire in control circuits for AC magnetic equipment. A wiring diagram is limited in its ability to completely convey the controller’s sequence of operation. The elementary diagram is used where an illustration of the circuit in its simplest form is desired. ELEMENTARY DIAGRAM An elementary diagram is a simplified circuit illustration. Devices and components are not shown in their actual positions. All control circuit components are shown as directly as possible, between a pair of vertical lines representing the control power supply. Components are arranged to show the sequence of operation of the devices and how the device operates. The effect of operating various auxiliary contacts and control devices can be readily seen. This helps in troubleshooting, particularly with the more complex controllers. This form of electrical diagram is sometimes referred to as a “schematic” or “line” diagram. www.epdatech.com 5 Examples of Control Circuits 2- and 3-Wire Control Elementary Diagrams Low Voltage Release and Low Voltage Protection are the basic control circuits encountered in motor control applications. The simplest schemes are shown below. Other variations shown in this section may appear more complicated, but can always be resolved into these two basic schemes. Note: The control circuits shown in this section may not include overcurrent protective devices required by applicable electrical codes. See page 11 for examples of control circuit overcurrent protective devices and their use. Low Voltage Release: 2-Wire Control FIG. 1 Low Voltage Protection: 3-Wire Control L1 L2 M 3 1 FIG. 2 OL L1 1 L2 STOP START M 3 2 OL M PILOT DEVICE SUCH AS LIMIT SWITCH, PRESSURE SWITCH, ETC. Low voltage release is a 2-wire control scheme using a maintained contact pilot device in series with the starter coil. This scheme is used when a starter is required to function automatically without the attention of an operator. If a power failure occurs while the contacts of the pilot device are closed, the starter will drop out. When power is restored, the starter will automatically pickup through the closed contacts of the pilot device. The term “2-wire” control is derived from the fact that in the basic circuit, only two wires are required to connect the pilot device to the starter. Low voltage protection is a 3-wire control scheme using momentary contact push buttons or similar pilot devices to energize the starter coil. This scheme is designed to prevent the unexpected starting of motors, which could result in injury to machine operators or damage to the driven machinery. The starter is energized by pressing the Start button. An auxiliary holding circuit contact on the starter forms a parallel circuit around the Start button contacts, holding the starter in after the button is released. If a power failure occurs, the starter will drop out and will open the holding circuit contact. When power is restored, the Start button must be operated again before the motor will restart. The term “3-wire” control is derived from the fact that in the basic circuit, at least three wires are required to connect the pilot devices to the starter. 2-Wire Control: Maintained Contact Hand-OFF-Auto Selector Switch FIG. 3 L1 L2 A1 A2 3-Wire Control: Momentary Contact Multiple Push Button Station FIG. 4 L1 L2 START I I HAND OFF AUTO A1 3A M OL 1 STOP STOP STOP START 2 M 3 OL START 1A 2A A2 M 2-WIRE CONTROL DEVICE A Hand-Off-Auto selector switch is used on 2-wire control applications where it is desirable to operate the starter manually as well as automatically. The starter coil is manually energized when the switch is turned to the Hand position and is automatically energized by the pilot device when the switch is in the Auto position. 6 When a motor must be started and stopped from more than one location, any number of Start and Stop push buttons may be wired together. It is also possible to use only one Start-Stop station and have several Stop buttons at different locations to serve as an emergency stop. www.epdatech.com Examples of Control Circuits 3-Wire Control Elementary Diagrams 3-Wire Control: Pilot Light Indicates when Motor is Running FIG. 1 L1 1 3-Wire Control: Pilot Light Indicates when Motor is Stopped L2 STOP START M 3 2 FIG. 2 L1 OL L2 1 STOP START 3 2 M OL M M M R G A pilot light can be wired in parallel with the starter coil to indicate when the starter is energized, indicating the motor is running. 3-Wire Control: Push-to-Test Pilot Light Indicates when Motor is Running FIG. 3 L1 1 L2 STOP START M 3 2 A pilot light may be required to indicate when the motor is stopped. This can be implemented by wiring a normally-closed auxiliary contact on the starter in series with the pilot light, as shown above. When the starter is deenergized, the pilot light illuminates. When the starter picks up, the auxiliary contact opens, turning off the light. 3-Wire Control: Illuminated Push Button Indicates when Motor is Running FIG. 4 L1 OL L2 1 STOP 2 START* 3 M OL M M R TEST R * * Pushing on pilot light operates Start contacts. When the Motor Running pilot light is not lit, there may be doubt as to whether the circuit is open or whether the pilot light bulb is burned out. To test the bulb, push the color cap of the Pushto-Test pilot light. 3-Wire Control: Fused Control Circuit Transformer and Control Relay 3-Wire Control: Fused Control Circuit Transformer FIG. 5 The illuminated push button combines a Start button and pilot light in one unit. Pressing the pilot light lens operates the Start contacts. Space is saved by using a two-unit push button station instead of three. L1 L2 FIG. 6 L1 L2 CR FU2 FU1 START STOP M M OL START M STOP GROUND (If used) CR OL M GROUND (If used) As an operator safety precaution, a step-down transformer can be used to provide a control circuit voltage lower than line voltage. The diagram above shows one way to provide overcurrent protection for control circuits. A starter coil with a high VA rating may require a control transformer of considerable size. A control relay and a transformer with a low VA rating can be connected so the normally-open relay contact controls the starter coil on the primary or line side. Square D Size 5 Combination Starter Form F4T starters use this scheme. www.epdatech.com 7 Examples of Control Circuits 3-Wire Control Elementary Diagrams Jogging: Selector Switch and Start Push Button FIG. 1 Jogging: Selector Push Button FIG. 2 FPO 7-2 FPO 7-1 Jogging, or inching, is defined by NEMA as the momentary operation of a motor from rest for the purpose of accomplishing small movements of the driven machine. One method of jogging is shown above. The selector switch disconnects the holding circuit contact and jogging may be accomplished by pressing the Start push button. A selector push button may be used to obtain jogging, as shown above. In the Run position, the selector-push button provides normal 3-wire control. In the Jog position, the holding circuit is broken and jogging is accomplished by depressing the push button. Jogging: Control Relay Jogging: Control Relay for Reversing Starter FIG. 3 FIG. 4 FPO 7-4 FPO 7-3 When the Start push button is pressed, the control relay is energized, which in turn energizes the starter coil. The normallyopen starter auxiliary contact and relay contact then form a holding circuit around the Start push button. When the Jog push button is pressed, the starter coil is energized (independent of the relay) and no holding circuit forms, thus jogging can be obtained. This control scheme permits jogging the motor either in the forward or reverse direction, whether the motor is at standstill or rotating. Pressing the Start-Forward or Start-Reverse push button energizes the corresponding starter coil, which closes the circuit to the control relay.The relay picks up and completes the holding circuit around the Start button. As long as the relay is energized, either the forward or reverse contactor remains energized. Pressing either Jog push button will deenergize the relay, releasing the closed contactor. Further pressing of the Jog button permits jogging in the desired direction. 3-Wire Control: More than 1 Starter, 1 Push Button Station Controls all 3-Wire Control: Reversing Starter FIG. 5 FIG. 6 FPO 7-5 FPO 7-6 When one Start-Stop station is required to control more than one starter, the scheme above can be used. A maintained overload on any one of the motors will drop out all three starters. 8 3-wire control of a reversing starter can be implemented with a Forward-Reverse-Stop push button station as shown above. Limit switches may be added to stop the motor at a certain point in either direction. Jumpers 6 to 3 and 7 to 5 must then be removed. www.epdatech.com Examples of Control Circuits 3-Wire Control Elementary Diagrams 3-Wire Control: Reversing Starter Multiple Push Button Station 3-Wire Control: Reversing Starter w/ Pilot Lights to Indicate Motor Direction FIG. 2 FIG. 1 More than one Forward-Reverse-Stop push button station may be required and can be connected in the manner shown above. 3-Wire Control: 2-Speed Starter Pilot lights may be connected in parallel with the forward and reverse contactor coils, indicating which contactor is energized and thus which direction the motor is running. 3-Wire Control: 2-Speed Starter w/ 1 Pilot Light to Indicate Motor Operation at Each Speed FIG. 4 FIG. 3 3-wire control of a 2-speed starter with a High-Low-Stop push button station is shown above. This scheme allows the operator to start the motor from rest at either speed or to change from low to high speed. The Stop button must be operated before it is possible to change from high to low speed. This arrangement is intended to prevent excessive line current and shock to motor and driven machinery, which results when motors running at high speed are reconnected for a lower speed. One pilot light may be used to indicate operation at both low and high speeds. One extra normally-open auxiliary contact on each contactor is required. Two pilot lights, one for each speed, may be used by connecting pilot lights in parallel with high and low coils (see reversing starter diagram above). Plugging: Plugging a Motor to a Stop from 1 Direction Only Anti-Plugging: Motor to be Reversed but Must Not be Plugged FIG. 5 FIG. 6 Plugging is defined by NEMA as a braking system in which the motor connections are reversed so the motor develops a counter torque, thus exerting a retarding force. In the above scheme, forward rotation of the motor closes the normally-open plugging switch contact and energizing control relay CR. When the Stop push button is operated, the forward contactor drops out, the reverse contactor is energized through the plugging switch, control relay contact and normally-closed forward auxiliary contact. This reverses the motor connections and the motor is braked to a stop. The plugging switch then opens and disconnects the reverse contactor. The control relay also drops out. The control relay makes it impossible for the motor to be plugged in reverse by rotating the motor rotor closing the plugging switch. This type of control is not used for running in reverse. Anti-plugging protection is defined by NEMA as the effect of a device that operates to prevent application of counter-torque by the motor until the motor speed has been reduced to an acceptable value. In the scheme above, with the motor operating in one direction, a contact on the anti-plugging switch opens the control circuit of the contactor used for the opposite direction. This contact will not close until the motor has slowed down, after which the other contactor can be energized. www.epdatech.com 9 For more books join our telegram group Click here to join https://t.me/engubook Examples of Control Circuits Shunting Thermal Units During Starting Period Elementary Diagrams Shunting Thermal Units During Starting Period FIG. 1 Article 430-35 of the NEC describes circumstances under which it is acceptable to shunt thermal units during abnormally long accelerating periods. 430-35. Shunting During Starting Period. (a) Nonautomatically Started. For a nonautomatically started motor, the overload protection shall be permitted to be shunted or cut out of the circuit during the starting period of the motor if the device by which the overload protection is shunted or cut out cannot be left in the starting position and if fuses or inverse time circuit breakers rated or set at not over 400 percent of the full-load current of the motor are so located in the circuit as to be operative during the starting period of the motor. FPO 9-1 (b) Automatically Started. The motor overload protection shall not be shunted or cut out during the starting period if the motor is automatically started. Exception. The motor overload protection shall be permitted to be shunted or cut out during the starting period on an automatically started motor where: (1) The motor starting period exceeds the time delay of available motor overload protective devices, and (2) Listed means are provided to: a. Sense motor rotation and to automatically prevent the shunting or cut out in the event that the motor fails to start, and b. Limit the time of overload protection shunting or cut out to less than the locked rotor time rating of the protected motor, and c. Provide for shutdown and manual restart if motor running condition is not reached. Figures 1 and 2 show possible circuits for use in conjunction with 3-wire control schemes. Figure 1 complies with NEC requirements. Figure 2 exceeds NEC requirements, but the additional safety provided by the zero speed switch might be desirable. Figure 3 shows a circuit for use with a 2-wire, automatically started control scheme that complies with NEC requirements. UL or other listed devices must be used in this arrangement. FIG. 2 FPO 9-2 FIG. 3 FPO 9-3 10 www.epdatech.com Examples of Control Circuits Overcurrent Protection for 3-Wire Control Circuits Elementary Diagrams 3-Wire Control: Fusing in 1 Line Only FIG. 1 3-Wire Control: Fusing in Both Lines L1 L2 FIG. 2 L1 FU1 FU2 FU1 START STOP M OL M START STOP 3-Wire Control: Fusing in Both Primary and Secondary Lines L1 L2 FIG. 4 L1 FU2 L2 FU4 FU3 PRI PRI FU1 X1 STOP SEC START X2 FU2 X1 M OL STOP X2 M OL M Control circuit transformer with fusing in both primary lines, no secondary fusing and all lines ungrounded. Control circuit transformer with fusing in both primary lines and both secondary lines, with all lines ungrounded. 3-Wire Control: Fusing in Both Primary Lines and 1 Secondary Line L1 L2 FU1 SEC START M FIG. 5 OL Common control with fusing in both lines and with both lines ungrounded. 3-Wire Control: Fusing in Both Primary Lines FU1 M M GND Common control with fusing in one line only and with both lines ungrounded or, if user’s conditions permit, with one line grounded. FIG. 3 L2 3-Wire Control: Fusing in Both Primary and Secondary Lines For Large Starters using Small Transformer FIG. 6 L1 L2 FU2 FU3 PRI FU4 M CR FU3 STOP SEC START PRI M OL FU1 FU2 X1 M GND STOP SEC START X2 CR OL M Control circuit transformer with fusing in one secondary line and both primary lines, with one line grounded. Control circuit transformer with fusing in both primary lines and both secondary lines, with all lines ungrounded. Used for large VA coils only. www.epdatech.com 11 AC Manual Starters and Manual Motor Starting Switches Class 2510 Manual Motor Starting Switches: Class 2510 Type K FIG. 1 T1 FIG. 2 L1 T1 L1 L1 T2 T3 L2 L3 T3 L2 T1 L3 PILOT LIGHT (IF USED) R PILOT LIGHT (IF USED) R T3 T1 T2 T3 MOTOR MOTOR 2-Pole, 1-Phase 3-Pole, 3-Phase Fractional Horsepower Manual Starters: Class 2510 Type F FIG. 3 FIG. 4 T2 FIG. 5 T2 L2 L2 L1 L1 T2 A O H R T1 T1 PILOT LIGHT (IF USED) PILOT LIGHT (IF USED) R T1 T2 T1 MOTOR 2 1 L1 4 3 PILOT LIGHT (IF USED) R T1 T2 2 MOTOR 1-Pole L2 A O H 4 2-WIRE CONTROL DEVICE 2-Pole T2 4 MOTOR 2-Pole w/ Selector Switch Integral Horsepower Manual Starters: Class 2510 Size M0 and M1 FIG. 6 L1 L2 FIG. 7 L1 L2 T2 FIG. 8 L1 L2 FIG. 9 L1 L2 L3 T1 T2 T3 FIG. 10 L1 L2 L3 T1 T2 T3 L2 L3 L1 T1 T2 T1 T1 T2 T1 T2 T1 MOTOR T2 T1 T3 T1 T2 T3 T1 T2 T3 MOTOR MOTOR T3 MOTOR MOTOR 2-Pole, 1-Phase 3-Pole, DC 3-Pole, 1-Phase 3-Pole, 3-Phase 3-Pole, 3-Phase w/ additional Interlock (Form X) ® 12 www.epdatech.com AC Manual Starters and Manual Motor Starting Switches Class 2511 and 2512 AC Reversing Manual Starters and Manual Motor Starting Switches: Class 2511 FIG. 1 FIG. 2 REV FWD T1 L1 T2 L2 T3 L3 L1 L2 L3 T1 T2 T3 T1 T2 T3 T1 T2 T3 MOTOR MOTOR Reversing Manual Motor Starting Switch Type K, 3-Pole, 3-Phase Reversing Manual Starter Sizes M0 and M1, 3-Pole, 3-Phase AC 2-Speed Manual Motor Starting Switches: Class 2512 Type K FIG. 4 FIG. 3 FPO 12-6b FPO 12-6a 2-Pole, 1-Phase w/ Pilot Lights 3-Pole, 3-Phase AC 2-Speed Manual Motor Starters: Class 2512 Type F FIG. 5 FIG. 6 FPO 13-1b FPO 13-1a 2-Unit, 2-Pole w/ Mechanical Interlock and Pilot Lights 3-Unit, 2-Pole w/ Selector Switch and Pilot Lights ® www.epdatech.com 13 2-Speed AC Manual Starters and IEC Motor Protectors Class 2512 and 2520 and Telemecanique GV1/GV3 2-Speed AC Manual Motor Starters: Class 2512 Size M0 and M1 FIG. 1 L1 L2 L3 T2 T11 T13 T1 T3 T12 MOTOR T1 T2 T3 T11 T12 T13 2-Speed Manual Starter for Wye-Connected, Separate Winding Motor Motor Protective Switches: Class 2520 FIG. 2 1/L1 3/L2 FIG. 3 5/L3 1/L1 3/L2 5/L3 FIG. 4 1/L1 3/L2 5/L3 2/T1 4/T2 6/T3 2/T1 4/T2 6/T3 2/T1 4/T2 6/T3 T1 T2 T3 T1 T3 T3 MOTOR MOTOR MOTOR 3-Pole, 3-Phase 2-Pole Application 1-Pole Application IEC Manual Starters: GV1/GV3 FIG. 5 1/L1 3/L2 5/L3 FIG. 6 FIG. 7 GV3 B• D1 I> I> I> 2/T1 4/T2 6/T3 GV3 A08 95 D2 96 23 14 22 14 24 14 24 34 GV1 A06 98 GV3 A0• Fault Signalling Contacts 13 14 24 32 GV3 A09 97 I> 21 GV1 A05 13 23 33 C2 I> GV1 A02 13 GV1 A03 13 23 31 GV3 D• C1 GV3 M• Motor Protector FIG. 8 < GV1 A01 GV3 Voltage Trips GV1 A07 13 23 33 13 23 31 14 24 34 14 24 33 GV1 A0• Contact Block ® 14 www.epdatech.com Drum Switches Class 2601 Drum Switches: Class 2601 REVERSE OFF MOTOR FORWARD 1 2 1 2 1 2 3 4 3 4 3 4 5 6 5 6 5 6 1 2 3 4 5 6 DRUM SW. MOTOR 1 2 3 4 5 6 MOTOR DRUM SW. FIG. 3 MOTOR DRUM SW. 1 2 3 4 5 6 LINE 1-Phase, Capacitor or Split-Phase Motor FIG. 5 LINE MOTOR 1-Phase, 4-Lead Repulsion Induction Motor FIG. 6 LINE 3-Phase, 3-Wire Motor Internal Switching FIG. 4 DRUM SW. START FIG. 2 HANDLE END RUN FIG. 1 DRUM SW. 1 2 3 4 5 6 LINE 1-Phase, 3-Lead Repulsion Induction Motor FIG. 7 LINE DRUM SW. LINE MOTOR 1 2 1 2 3 4 3 4 5 6 5 6 COMMON 2-Phase, 4-Wire Motor MOTOR LINE 1 2 3 4 5 6 DC, Shunt Motor DRUM SW. 1 LINE 2 ARMATURE 3 4 5 6 DC, Series Motor FIG. 10 MOTOR DRUM SW. LINE 1 2 ARMATURE SERIES FIELD DRUM SW. SERIES FIELD ARMATURE SHUNT FIELD MOTOR FIG. 9 SHUNT FIELD 2-Phase, 3-Wire Motor FIG. 8 3 4 5 6 DC, Compound Motor ® www.epdatech.com 15 DC Starters, Constant and Adjustable Speed Class 7135 and 7136 Constant Speed DC Starter: Class 7135 FIG. 1 FPO 15-1 Typical Elementary Diagram for NEMA Size 2, 3 and 4 Adjustable Speed DC Starter: Class 7136 FIG. 2 FPO 15-2 Typical Elementary Diagram for NEMA Size 2, 3 and 4 Acceleration Contactors: Class 7135, 7136, 7145 and 7146 NEMA Size 1 2 3 4 5 No. of Acceleration Contactors 1 2 2 2 3 ® 16 www.epdatech.com Reversing DC Starters, Constant and Adjustable Speed Class 7145 and 7146 Reversing Constant Speed DC Starter: Class 7145 FIG. 1 FPO 16-1 Typical Elementary Diagram for NEMA Size 2, 3 and 4 Reversing Adjustable Speed DC Starter: Class 7146 FIG. 2 FPO 16-2 Typical Elementary Diagram for NEMA Size 2, 3 and 4 ® www.epdatech.com 17 Mechanically Latched Contactors and Medium Voltage Motor Controllers Class 8196 and 8198 Mechanically Latched Contactor: Class 8196 Type FL13, FL23, FL12 and FL22 FIG. 1 FPO 17-2 150% Full-Voltage, Non-Reversing Squirrel Cage Motor Controller: Class 8198 Type FC11, FC21, FC13, FC23, FC12 and FC22 FIG. 2 FPO 17-1 145% ® 18 www.epdatech.com Medium Voltage Motor Controllers Class 8198 Full-Voltage Squirrel Cage Motor Controller: Class 8198 Type FCR1 and FCR2 FIG. 1 FPO 17-3 160% ® www.epdatech.com 19 Medium Voltage Motor Controllers Class 8198 Reduced-Voltage, Primary Reactor, Non-Reversing Squirrel Cage Motor Controller: Class 8198 Type RCR1 and RCR2 FIG. 1 FPO 18-1 130% ® 20 www.epdatech.com Medium Voltage Motor Controllers Class 8198 Reduced-Voltage, Primary Reactor, Autotransformer, Non-Reversing Squirrel Cage Motor Controller: Class 8198 Type RCA1 and RCA2 FIG. 1 FPO 18-2 150% ® www.epdatech.com 21 Medium Voltage Motor Controllers Class 8198 Full Voltage, Non-Reversing Synchronous Motor Controller: Class 8198 Type FS1 and FS2 FIG. 1 FPO 19-1 170% ® 22 www.epdatech.com For more books join our telegram group Click here to join https://t.me/engubook Medium Voltage Motor Controllers Class 8198 Reduced-Voltage, Primary Reactor, Non-Reversing Synchronous Motor Controller: Class 8198 Type RS1 and RS2 FIG. 1 FPO 19-2 140% ® www.epdatech.com 23 Medium Voltage Motor Controllers Class 8198 Reduced-Voltage, Autotransformer, Non-Reversing Synchronous Motor Controller: Class 8198 Type RSA1 and RSA2 FIG. 1 FPO 20-1 160% ® 24 www.epdatech.com Medium Voltage Motor Controllers Class 8198 Full-Voltage, Non-Reversing, Brushless Synchronous Motor Controller: Class 8198 Type FSB1 and FSB2 FIG. 1 FPO 20-2 155% ® www.epdatech.com 25 Solid State Protective Relays Class 8430 Solid State Protective Relays: Class 8430 Type DAS, DASW, DASV and DASVW FIG. 1 L1 L2 L3 M OL T1 M OL T2 M OL T3 MOTOR START STOP OL M Dashed lines represent optional contacts 12 L1 14 22 L2 L3 24 11 With the line voltage connections directly at the motor terminals, the relay will detect all phase loss conditions ahead of the connection points. However, the motor may sustain a momentary “bump” in the reverse condition if the proper phase sequence is not present. M 21 FIG. 2 L1 L2 L3 STOP START M 12 L1 14 22 L2 L3 24 11 Dashed lines represent optional contacts M OL T1 M OL T2 M OL T3 MOTOR With the line voltage connections ahead of the starter, the motor can be started in the reverse direction. The relay cannot detect a phase loss on the load side of the starter. OL M 21 Solid State Protective Relays: Class 8430 FIG. 3 FIG. 4 FIG. 5 4 5 3 Input Signal 2 L1 L2 L3 A1 11 21 B1 B2 1 2 3 4 5 6 1 8 6 L1 7 L2 L3 Type MPS 240V FIG. 6 1 2 3 4 5 6 7 8 9 12 14 22 24 A2 VS 7 8 9 10 11 12 Dashed lines represent optional contacts (DIAW and DUAW devices only) Type DIA, DIAW, DUA and DUAW A B L3 L2 L1 Type MPD Type MPS 480V ® 26 www.epdatech.com Solid State Protective Relays Class 8430 Load Detector Relay: Class 8430 Type V FIG. 1 FPO 22-1 Wiring Diagram FPO 22-3 Elementary Diagram (Common Control) Load Converter Relay: Class 8430 Type G FIG. 2 FPO 22-2 ® www.epdatech.com 27 For more books join our telegram group Click here to join https://t.me/engubook General Purpose Relays Class 8501 Control Relays: Class 8501 Type CO and CDO FIG. 2 FIG. 1 Type CO6 and CDO6 FIG. 3 Type CO7 and CDO7 FIG. 4 Type CO8 and CDO8 FIG. 5 Type CO21 and CDO21 FIG. 6 Type CO15 and CDO15 Type CO16, CDO16, CO22 and CDO22 Control Relays: Class 8501 Type UBS FIG. 7 START L1 M STOP L2 M 9 10 8 5 TERMINAL NUMBERS Control Relays: Class 8501 Type K FIG. 8 FIG. 9 FIG. 10 1 3 4 6 1 3 7 9 4 6 7 9 8 RESET A B COMMON LATCH 4 3 B A FIG. 12 FIG. 11 1 6 2 7 1 Type KU, KF, KX, KUD, KFD and KXD 2-Pole Type KL 6 7 9 FIG. 13 6 A B – + + – LATCH RESET Type KLD 8 Type KP and KPD 2-Pole 3 4 5 1 2 3 4 5 6 7 8 9 A B 5 7 4 8 3 9 2 10 1 Type KU, KF, KX, KUD, KFD and KXD 3-Pole 11 Type KP and KPD 3-Pole ® 28 www.epdatech.com NEMA Control Relays Class 8501 and 9999 10 A Control Relay w/ Convertible Contacts: Class 8501 Type X FIG. 1 FPO 27-1 * Note: Class 8501 Type XO••••XL, XDO••••XL, XDO••••XDL and XO••••XDL latch relays use the same diagram except for the addition of an unlatch coil (8 poles maximum). Timer Attachment: Class 9999 Type XTD and XTE FIG. 2 TIMED CONTACTS 14 2 N.O. 1 N.C. 1 N.O. 14 14 13 13 13 14 POLE #13 14 2 N.C. 14 POLE #14 Note: All contacts are convertible. 13 13 ON DELAY (TDE) 13 OFF DELAY (TDD) No. of Timed Contacts Class 9999 Type 2 XTD XTE Pole No.* 13 14 O 1 * O = N.O. Contact 1 = N.C. Contact ® www.epdatech.com 29 General Purpose Relays and Sensing Relays Class 8501 and Telemecanique RM2 LA1/LG1 Miniature Control Relays: Class 8501 Type RS and RSD FIG. 1 FIG. 2 1 1 4 5 5 8 9 9 12 14 (+) 13 (–) Type RS42 and RSD42 Type RS41 and RSD41 FIG. 3 FIG. 4 1 2 3 4 8 5 6 7 8 12 9 10 11 12 1 2 4 5 6 9 10 14 (+) 13 (–) 14 (+) 13 (–) 14 (+) 13 (–) Type RS4, RSD4, RS14, RSD14, RS24, RSD24, RS34, RSD34, RS44 and RSD44 Type RS43 and RSD43 Control Relays w/ Intrinsically Safe Terminals: Class 8501 Type TO41 and TO43 FIG. 6 FIG. 5 1 ON 2 3 4 5 6 OFF SUPPLY VOLTAGE OFF ON 7 8 9 10 11 12 Non-Hazardous Location Terminals Intrinsically Safe Terminals Sensing Relays: RM2 LA1/LG1 FIG. 7 M H 16 18 B1 B2 A1 15 B3 B1 B2 B1 B2 15 16 18 B3 A2 H L H M Supply voltage Supply voltage L A1 15 B2 B1 B3 M B2 B1 B3 16 18 X A2 1 Level RM2 LG1 H = High level electrode L = Low level electrode 16 18 X 2 Levels 15 M = Reference electrode (common) RM2 LA1 ® 30 www.epdatech.com IEC Relays IEC D-Line Control Relays (for input modules see page 42) Control Relays: CA2 and CA3 FIG. 1 A1 13 23 33 43 NO NO NO NO A2 14 24 34 FIG. 2 44 13 21 33 43 NO NC NO NO A2 14 22 34 FIG. 3 44 3 N.O. & 1 N.C. Instantaneous CA2 DN31 and CA3 DN31 4 N.O. Instantaneous CA2 DN40 and CA3 DN40 FIG. 4 A1 A1 13 21 35 NO NC NC 47 NO A2 14 48 22 36 13 21 31 43 NO NC NC NO A2 14 22 32 44 2 N.O. & 2 N.C. Instantaneous CA2 DN22 and CA3 DN22 FIG. 5 2 N.O. & 2 N.C. Instantaneous, w/ 2 Make-Before-Break CA2 DC22 and CA3 DC22 A1 E1 A1 E2 A2 13 21 31 NO NC NC 14 22 43 NO 32 44 2 N.O. & 2 N.C. Instantaneous w/ Mechanical Latch CA2 DK22 and CA3 DK22 Front-Mounted Standard Instantaneous Auxiliary Contact Blocks: LA1 FIG. 6 FIG. 7 53 61 NO NC 54 53 63 NO NO 62 54 52 54 62 76 54 54 64 74 FIG. 13 72 52 62 72 53 61 71 81 NO NC NC NC 84 51 61 71 81 NC NC NC NC 84 4 N.O. LA1 DN40 2 N.O. & 2 N.C. w/ 2 Make-Before-Break LA1 DC22 62 FIG. 10 54 2 N.O. & 2 N.C. LA1 DN22 53 63 73 83 NO NO NO NO 88 53 61 71 83 NO NC NC NO 62 2 N.C. LA1 DN02 FIG. 12 53 61 75 87 NO NC NC NO FIG. 9 51 61 NC NC 64 2 N.O. LA1 DN20 1 N.O. & 1 N.C. LA1 DN11 FIG. 11 FIG. 8 62 72 82 1 N.O. & 3 N.C. LA1 DN13 FIG. 14 53 61 73 83 NO NC NO NO 82 54 4 N.C. LA1 DN04 62 74 84 3 N.O. & 1 N.C. LA1 DN31 Front-Mounted Damp- and Dust-Protected Instantaneous Auxiliary Contact Blocks: LA1 FIG. 15 53 NO 63 NO 54 64 FIG. 16 53 NO 63 NO 54 64 FIG. 17 54 2 N.O. w/ Grounding Screw LA1 DY20 2 N.O. LA1 DX20 FIG. 18 53 63 73 83 NO NO NO NO 64 74 53 61 73 83 NO NC NO NO 84 54 2 Dusttight N.O. & 2 N.O. LA1 DZ40 62 74 84 2 Dusttight N.O. & 1 N.O. & 1 N.C. LA1 DZ31 Front-Mounted Time Delay Auxiliary Contacts: LA2 and LA3 45 E1 46 E2 FIG. 24 A2 LA6 DK2 58 66 Off Delay, 1 N.O. & 1 N.C. LA3 DR 53/ NO 83 NO E2 65 NC Side-Mounted Auxiliary Contact Blocks: LA8 A1 A2 LA6 DK1 FIG. 23 57 NO 54/ 61/ NC 71 NC E1 68 FIG. 21 62/ 1 N.O. & 1 N.C. Instantaneous LA8 DN11 FIG. 25 53/ NO 83 NO Front-Mounted Mechanical Latch Adder Blocks: LA6 A1 56 On Delay, 1 N.C. w/ 1 Offset N.O. LA2 DS On Delay, 1 N.O. & 1 N.C. LA2 DT FIG. 22 67 NO 54/ 63/ NO 73 NO 68 55 NC 84 56 FIG. 20 72 67 NO 84 55 NC 74 FIG. 19 64/ 2 N.O. Instantaneous LA8 DN20 ® www.epdatech.com 31 IEC Relays Class 8501 Miniature IEC Relays: Class 8501 Type PR 1 FIG. 1 A1 13 21 NO NC A2 14 PR 1.11 E FIG. 2 33 41 NO NC PRD 1.11 E A1 PV 11 22 34 42 14 44 PV 02 PRD 1.20 E A2 PV 20 34 31 41 NC NC 13 23 NO NO PR 1.20 E 33 43 NO NO 32 24 Type PR 1 and PRD 1 Relays 42 Type PV Adder Decks for PR 1.20 E Alternating Relays: Class 8501 Type PHA FIG. 3 relay coil A1 13 23 13 14 energized deenergized closed open 14 A2 24 23 24 closed open ® 32 www.epdatech.com Type P Contactors and Type T Overload Relays Class 8502 and 9065 Power Terminals FIG. 1 Coil Terminals 1 3 5 2 4 6 FIG. 2 A1 A2 Power terminals on contactors, overloads and switches are single digits – odd for line side terminals and even for load side terminals. Coil terminals are designated by a letter and a number. Terminals for a single winding coil are designated “A1” and “A2”. Overload Relay Contact Terminals Auxiliary Contact Terminals FIG. 3 FIG. 4 Location 13 21 31 43 53 95 97 96 98 With Isolated N.O. Alarm Contact 14 22 32 44 95 Status (N.O. or N.C.) 54 Auxiliary contacts on contactors, relays and push button contacts use 2-digit terminal designations, as shown in the diagram above. The first digit indicates the location of the contact on the device. The second digit indicates the status of the contacts, N.O. or N.C. “1” and “2” indicate N.C. contacts. “3” and “4” indicate N.O. contacts. 96 98 With Non-Isolated N.O. Alarm Contact Overload contact terminals are marked with two digits. The first digit is “9”. The second digits are “5” and “6” for a N.C. and “7” and “8” for a N.O. isolated contact. If the device has a non-isolated alarm contact (single pole), the second digits of the N.O. terminals are “5” and “8”. Class 8502 Type PD or PE Contactor w/ Class 9065 Type TR Overload Relay FIG. 5 FPO 30-2 120% Wiring Diagram FPO 30-2 120% Elementary Diagram ® www.epdatech.com 33 Type P Contactors and Type T Overload Relays Class 8502 and 9065 Class 8502 Type PG or PD Contactor w/ Class 9065 Type TD Overload Relay FIG. 1 FPO 30-3 120% FPO 30-3 120% Wiring Diagram Elementary Diagram Class 8502 Type PE Contactor w/ Class 9065 Type TE Overload Relay FIG. 2 FPO 30-4 120% FPO 30-4 120% Elementary Diagram Wiring Diagram Class 8502 Type PF, PG or PJ Contactor w/ Class 9065 Type TF, TG or TJ Overload Relay FIG. 3 FPO 31-1 120% FPO 31-1 120% Wiring Diagram Elementary Diagram ® 34 www.epdatech.com Type P Reversing Contactors and Type T Overload Relays Class 8502, 8702 and 9065 Class 8502 Type PJ or PK Contactor w/ Class 9065 Type TJE Overload Relay FIG. 4 FPO 31-2 120% FPO 31-2 120% Wiring Diagram Elementary Diagram Class 8702 Type PDV or PEV Reversing Contactor w/ Class 9065 Type TR Overload Relay FIG. 1 FPO 31-3 Elementary Diagram FPO 31-3 120% Elementary Diagram ® www.epdatech.com 35 Type S AC Magnetic Contactors Class 8502 AC Magnetic Contactors: Class 8502 Type S FIG. 1 3 L1 FIG. 2 L2 3 T1 L2 T1 MOTOR T1 T2 T2 T1 2 1-Pole, Size 0 and 1 FIG. 3 2-Pole, Size 00, 0 and 1 FIG. 4 3 L1 3 L2 1 T2 T1 T2 T3 MOTOR L1 L2 L3 T1 T2 T3 1 MOTOR 2 T1 T2 2 3-Pole, Size 00 to 5 2-Pole, Size 2 to 5 FIG. 5 L2 MOTOR 2 T1 L1 1 1 FIG. 6 3 L1 T1 T3 T4 T2 L3 L4 3 L2 L1 1 L2 L3 T2 T3 T1 T2 T3 X2 MOTOR MOTOR 2 T1 T3 T4 T2 2 4-Pole, Size 0, 1 and 2 T1 5-Pole, Size 0, 1 and 2 FIG. 7 FIG. 8 TO SEPARATE CONTROL 2- and 3-Wire Control for Figure 1 to 5 3 X2 Separate Control for Figure 6 ® 36 www.epdatech.com Type S AC Magnetic Contactors Class 8502 Size 6, 3-Pole Contactor – Common Control Class 8502 Type SH Series B FIG. 1 Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Short-Circuit Protection Rating of branch circuit protective device must comply with applicable electrical codes and the following limitations: Max. Rating Type of Device Class K5 or RK5 time-delay fuse 600 A Class J, T or L fuse 1200 A Inverse-time circuit breaker 800 A Elementary Diagram ® www.epdatech.com 37 For more books join our telegram group Click here to join https://t.me/engubook Type S AC Magnetic Contactors Class 8502 Size 6, 3-Pole Contactor – Separate Control Class 8502 Type SH Form S Series B FIG. 1 Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Short-Circuit Protection Rating of branch circuit protective device must comply with applicable electrical codes and the following limitations: Max. Rating Type of Device Class K5 or RK5 time-delay fuse 600 A Class J, T or L fuse 1200 A Inverse-time circuit breaker 800 A Elementary Diagram ® 38 www.epdatech.com Type S AC Magnetic Contactors Class 8502 Size 7, 3-Pole Contactor – Common Control Class 8502 Type SJ Series A FIG. 1 Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Short-Circuit Protection Rating of branch circuit protective device must comply with applicable electrical codes and the following limitations: Max. Rating Type of Device Class K5 or RK5 time-delay fuse 600 A Class J, T or L fuse 1600 A Inverse-time circuit breaker 2000 A Elementary Diagram ® www.epdatech.com 39 Type S AC Magnetic Contactors Class 8502 Size 7, 3-Pole Contactor – Separate Control Class 8502 Type SJ Form S Series A FIG. 1 Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Short-Circuit Protection Rating of branch circuit protective device must comply with applicable electrical codes and the following limitations: Max. Rating Type of Device Class K5 or RK5 time-delay fuse 600 A Class J, T or L fuse 1600 A Inverse-time circuit breaker 2000 A Elementary Diagram ® 40 www.epdatech.com IEC Contactors IEC Contactors and Auxiliary Contact Blocks (for Input Modules see page 42) 3- and 4-Pole Contactors: LC1 and LP1 (Terminal markings conform to standards EN 50011 and 50012) FIG. 1 A1 A2 1 L1 3 L2 5 13 L3 NO T1 2 T2 4 T3 6 FIG. 2 A1 A2 14 A1 A2 5 21 L3 NC T1 2 T3 6 22 T2 4 FIG. 3 1 L1 3 L2 5 L3 7 L4 T1 2 T2 4 T3 6 T4 8 FIG. 5 A1 1 A2 R1 2 A2 FIG. 6 3 R4 4 D12 008 and D25 008 D12 004 to D80 004 T1 2 5 L3 T2 4 13 21 NO NC T3 6 14 22 D40 11 to D95 11 R3 R2 1 3 L1 L2 A1 D09 01 to D32 01 D09 10 to D32 10 FIG. 4 1 3 L1 L2 A1 R1 1 3 R3 A2 R2 2 4 R4 D40 008 to D80 008 Front-Mounted Standard Instantaneous Auxiliary Contact Blocks: LA1 FIG. 8 94 FIG. 7 43 54 FIG. 10 53 63 NO NO 62 54 FIG. 11 51 61 NO NO 64 52 53 NO 62 54 61 71 NC NC 83 NO 62 84 72 FIG. 12 53 NO 61 71 NC NC 54 62 81 NC 72 82 93 44 1 N.O. & 1 N.C LA1 DN 11 1 N.O. LA1 DN 10 FIG. 14 92 FIG. 13 FIG. 9 53 61 NO NC NO 41 NO 2 N.O. LA1 DN 20 53 NO 61 75 NC NC 54 62 FIG. 15 87 NO 76 2 N.C. LA1 DN 02 53 NC 54 88 63 73 NC NC 64 74 2 N.O. & 2 N.C. LA1 DN 22 FIG. 16 83 NC 51 NC 84 61 71 NC NC 52 62 72 1 N.O. & 3 N.C. LA1 DN 13 FIG. 17 81 NC 82 53 NO 61 73 NC NO 83 NO 54 62 84 74 91 42 2 N.O. & 2 N.C. w/ 2 Make-Before-Break LA1 DC 22 1 N.C. LA1 DN 01 4 N.O. LA1 DN 40 4 N.C. LA1 DN 04 3 N.O. & 1 N.C. LA1 DN 31 Front-Mounted Damp- and Dust-Protected (IP 54) Instantaneous Auxiliary Contact Blocks: LA1 FIG. 18 53 N0 63 NO 54 64 FIG. 19 53 N0 63 NO 54 64 FIG. 20 53 N0 63 N0 73 N0 83 N0 54 64 74 84 FIG. 21 53 61 N0 NC 73 N0 83 N0 54 62 74 84 2 N.O. (5-24 V) w/ Grounding Screw 2 Dusttight N.O. (24-50 V) & 2 N.O. 2 Dusttight N.O. (24-50 V) & 1 N.O. & 1 N.C. LA1 DY 20 LA1 DZ 40 LA1 DZ 31 2 N.O. LA1 DX 20 Front-Mounted Time Delay Auxiliary Contacts: LA2 and LA3 56 On Delay, 1 N.O. w/ 1 Offset N.O. LA2 DS• E1 45 E1 46 E2 Side-Mounted Auxiliary Contact Blocks: LA8 FIG. 27 A1 A2 A2 LA6 DK 2, LA6 DK 3 53/ NO 83 NO E2 LA6 DK 1 FIG. 26 Off Delay, 1 N.O. & 1 N.C. LA3 DR• 54/ 61/ NC 71 NC A1 66 62/ 1 N.O. & 1 N.C. Instantaneous LA8 DN 11 FIG. 28 53/ NO 83 NO Front-Mounted Mechanical Latch Adder Blocks: LA6 FIG. 25 58 84 On Delay, 1 N.O. & 1 N.C. LA2 DT• 68 54/ 63/ NO 73 NO 68 57 65 NO NC 72 56 FIG. 24 55 67 NC NO 84 FIG. 23 55 67 NC NO 74 FIG. 22 64/ 2 N.O. Instantaneous LA8 DN 20 ® www.epdatech.com 41 IEC Contactors Input Modules and Reversing Contactors Input Modules: LA4 FIG. 2 FIG. 1 FIG. 3 AC/DC PLC AC A1 A2 B2 A1 A2 AC/DC B1 A1 A2 A/M 0 0 t A1 A2 A1 + E1 A1 A2 K K Off Delay Timer Module LA4 DR On Delay Timer Module LA4 DT AC A1 1/0 A2 K FIG. 4 t E2 AC A2 A1 FIG. 5 AC A1 + E1 E2 A1 A2 Auto-Manual-Off Control Module LA4 DM AC A2 FIG. 6 AC A1 A2 + E1 A1 K Relay Interface Amplifier Module w/ Manual Override, LA4 DL Relay Interface Amplifier Module LA4 DF AC A2 A2 K K E2 Solid State Interface Amplifier Module LA4 DW Contactors: LC2, LP2 and LA9 FIG. 8 FIG. 7 A1 1 3 5 1 3 5 A1 A2 2 4 6 2 4 6 A2 FIG. 9 01 01 U V W A1 1 3 5 7 1 3 5 7 A1 A2 2 4 6 8 2 4 6 8 A2 A1 A1 A2 A2 02 21 21 02 KM2 KM2 22 KM1 A2 22 KM1 A2 Reversing Contactor 3-Pole, for Motor Control LC2, LP2 D0901 to D3201 Transfer Contactor, 4-Pole, Mechanically Interlocked LC2, LP2 D12004 to D8004 Mechanical Interlock w/ Electrical Interlock LA9 D0902, D4002 and D8002 ® 42 www.epdatech.com Type S AC Magnetic Starters Class 8536 1-Phase, Size 00 to 3 1-Pole, 1-Phase Magnetic Starters, Size 00 to 3: Class 8536 Type S FIG. 1 * Marked “OL” if alarm contact is supplied Wiring Diagram Elementary Diagram Single Phase Starter w/ Single Voltage Motor FIG. 2 * Marked “OL” if alarm contact is supplied Note: Starters are factory-wired with coil connected for the higher voltage. If starter is used on lower voltage, connect per coil diagram. Wiring Diagram Elementary Diagram Single Phase Starter w/ Dual Voltage Motor 3-Pole, 3-Phase Magnetic Starters, Size 00 to 3, Connected for Single Phase: Class 8536 Type S FIG. 3 * Marked “OL” if alarm contact is supplied Wiring Diagram Elementary Diagram 3-Phase Starter Connected for Single Phase, Single Voltage Motor ® www.epdatech.com 43 Type S AC Magnetic Starters Class 8536 2-Phase and 3-Phase, Size 00 to 5 4-Pole, 2-Phase Magnetic Starters: Class 8536 Type S FIG. 1 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 0, 1 and 2 FIG. 2 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 3 and 4 3-Pole, 3-Phase Magnetic Starters: Class 8536 Type S FIG. 3 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 00 to 4 FIG. 4 ▲ If alarm contact is supplied, a single (3 thermal unit) overload block is furnished, fed from 3 current transformers. * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 5 ® 44 www.epdatech.com Type S AC Magnetic Starters Class 8536, 8538 and 8539 3-Phase, Size 6 3-Pole, 3-Phase Magnetic Starters, Size 6 – Common Control Class 8536/8538/8539 Type SH Series B FIG. 1 Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Elementary Diagram ® www.epdatech.com 45 Type S AC Magnetic Starters Class 8536 3-Phase, Size 7 3-Pole, 3-Phase Magnetic Starters, Size 7 – Common Control Class 8536 Type SJ Series A FIG. 1 Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Elementary Diagram ® 46 www.epdatech.com Type S AC Magnetic Starters Class 8536 3-Phase Additions and Special Features 3-Pole, 3-Phase Magnetic Starters, Size 00 to 4: Class 8536 Type S FIG. 1 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Form A – Start-Stop Push Button Mounted in Cover FIG. 2 * Marked “OL” if alarm contact is supplied Wiring Diagram Elementary Diagram Form C – Hand-Off-Auto Selector Switch Mounted in Cover FIG. 3 * Marked “OL” if alarm contact is supplied ∆ Single or dual voltage primary connection per transformer nameplate. Wiring Diagram ∆ Single or dual voltage primary connection per transformer nameplate. Elementary Diagram Form F4T – Control Circuit Transformer and Primary Fuses ® www.epdatech.com 47 Type S AC Magnetic Starters Class 8536 3-Phase Additions and Special Features 3-Pole, 3-Phase Magnetic Starters, Size 00 to 4: Class 8536 Type S FIG. 1 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Form S – Separate Control FIG. 2 * Marked “OL” if alarm contact is supplied On NEMA Size 3 and 4 starters, holding circuit contact is in position #1. Max. of 3 external auxiliary contacts on NEMA Size 00. Wiring Diagram Elementary Diagram Form X – Additional Auxiliary Contacts 3-Pole, 3-Phase Magnetic Starters, Size 5: Class 8536 Type S FIG. 3 ∆ * Marked “OL” if alarm contact is supplied ∆ If alarm contact is supplied, a single (3 thermal unit) overload block is furnished, fed from 3 current transformers Wiring Diagram Elementary Diagram Form F4T – Control Circuit Transformer and Primary Fuses ® 48 www.epdatech.com Type S AC Magnetic Starters Class 8536, 8538 and 8539 3-Phase Additions and Special Features 3-Pole, 3-Phase Magnetic Starters, Size 6 – Separate Control Class 8536/8538/8539 Type SH Form S Series B FIG. 1 Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Elementary Diagram ® www.epdatech.com 49 Type S AC Magnetic Starters Class 8536 3-Phase Additions and Special Features 3-Pole, 3-Phase Magnetic Starters, Size 7 – Separate Control Class 8536 Type SJ Form S Series A FIG. 1 Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Elementary Diagram ® 50 www.epdatech.com Integral Self-Protected Starters Integral 18 State of Auxiliary Contacts State of Auxiliary Contacts for LD1 FIG. 1 LD1 Auxiliary contact actuators 1 3 5 L1 L2 L3 AUTO + 0 AUTO + 0 A1 A2 Auxiliary contacts 2 LA1-LB019 LA1-LB017 LA1-LB015 LA1LB001 LA1LB031 LA1-LB034 T1 T2 T3 4 6 Contact open Contact closed Off AUTO On, contactor open AUTO On, contactor closed 13 23 31 95 97 13 31 97 13 31 95 41 16 18 16 18 6 8 14 24 32 96 98 14 32 98 14 32 96 42 15 17 15 17 5 7 13 23 31 95 97 13 31 97 13 31 95 41 16 18 16 18 6 8 14 24 32 96 98 14 32 98 14 32 96 42 15 17 15 17 5 7 13 23 31 95 97 13 31 97 13 31 95 41 16 18 16 18 6 8 14 24 32 96 98 14 32 98 14 32 96 42 15 17 15 17 5 7 13 23 31 95 97 13 31 97 13 31 95 41 16 18 16 18 6 8 14 24 32 96 98 14 32 98 14 32 96 42 15 17 15 17 5 7 13 23 31 95 97 13 31 97 13 31 95 41 16 18 16 18 6 8 14 24 32 96 98 14 32 98 14 32 96 42 15 17 15 17 5 7 13 23 31 95 97 13 31 97 13 31 95 41 16 18 16 18 6 8 14 24 32 96 98 14 32 98 14 32 96 42 15 17 15 17 5 7 13 23 31 95 97 13 31 97 13 31 95 41 16 18 16 18 6 8 14 24 32 96 98 14 32 98 14 32 96 42 15 17 15 17 5 7 13 23 31 95 97 13 31 97 13 31 95 41 16 18 16 18 6 8 14 24 32 96 98 14 32 98 14 32 96 42 15 17 15 17 5 7 TRIP. + Tripped on overload Tripped on short circuit Off after short circuit Manual reset TRIP. + TRIP. + TRIP. + RESET ® www.epdatech.com 51 For more books join our telegram group Click here to join https://t.me/engubook Integral Self-Protected Starters Integral 18 State of Auxiliary Contacts State of Auxiliary Contacts for LD5 FIG. 1 LD5 Auxiliary contact actuators 1 3 5 L1 L2 L3 A1A2 AUTO + 0 A1A2 Auxiliary contacts LA1-LB015 2 Contact open Contact closed T1 T2 T3 4 6 Off AUTO On, contactor open AUTO On, contactor II closed AUTO On, contactor I closed Tripped on overload Tripped on short circuit Off after short circuit Manual reset LA1-LB019 LA1-LB017 LA1LB001 LA1-LB021 LA1LB001 On Integral 13 23 31 95 97 13 31 97 13 31 95 41 13 23 31 16 18 41 6 8 14 24 32 96 98 14 32 98 14 32 96 42 14 24 32 15 17 42 5 7 13 23 31 95 97 13 31 97 13 31 95 41 13 23 31 16 18 41 6 8 14 24 32 96 98 14 32 98 14 32 96 42 14 24 32 15 17 42 5 7 13 23 31 95 97 13 31 97 13 31 95 41 13 23 31 16 18 41 6 8 14 24 32 96 98 14 32 98 14 32 96 42 14 24 32 15 17 42 5 7 13 23 31 95 97 13 31 97 13 31 95 41 13 23 31 16 18 41 6 8 14 24 32 96 98 14 32 98 14 32 96 42 14 24 32 15 17 42 5 7 13 23 31 95 97 13 31 97 13 31 95 41 13 23 31 16 18 41 6 8 14 24 32 96 98 14 32 98 14 32 96 42 14 24 32 15 17 42 5 7 13 23 31 95 97 13 31 97 13 31 95 41 13 23 31 16 18 41 6 8 14 24 32 96 98 14 32 98 14 32 96 42 14 24 32 15 17 42 5 7 13 23 31 95 97 13 31 97 13 31 95 41 13 23 31 16 18 41 6 8 14 24 32 96 98 14 32 98 14 32 96 42 14 24 32 15 17 42 5 7 13 23 31 95 97 13 31 97 13 31 95 41 13 23 31 16 18 41 6 8 14 24 32 96 98 14 32 98 14 32 96 42 14 24 32 15 17 42 5 7 13 23 31 95 97 13 31 97 13 31 95 41 13 23 31 16 18 41 6 8 14 24 32 96 98 14 32 98 14 32 96 42 14 24 32 15 17 42 5 7 TRIP. + TRIP. + TRIP. + TRIP. + RESET ® 52 www.epdatech.com Integral Self-Protected Starters Integral 32 and 63 State of Auxiliary Contacts State of Auxiliary Contacts for LD4 FIG. 1 LD4 Auxiliary contact actuators 1 3 5 L1 L2 L3 AUTO + 0 U U A1 A2 Auxiliary contacts T1 T2 T3 2 4 6 Contact open Contact closed LD4 LA1-LC010 LA1-LC012 LA1-LC020 LA1-LC030 98 13 23 31 (63) 53 05 95 14 24 32 54 (64) 08 98 13 23 31 53 14 24 32 05 95 14 24 32 54 13 23 31 08 98 13 23 31 53 14 24 32 05 95 14 24 32 54 13 23 31 08 98 13 23 31 53 14 24 32 05 95 14 24 32 54 96 98 13 23 31 08 98 13 23 31 53 95 14 24 32 05 95 14 24 32 54 06 08 96 98 13 23 31 08 98 13 23 31 53 05 95 14 24 32 05 95 14 24 32 54 16 18 06 08 96 98 13 23 31 08 98 13 23 31 53 14 24 32 15 05 95 14 24 32 05 95 14 24 32 54 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 53 14 24 32 15 05 95 14 24 32 05 95 14 24 32 54 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 53 14 24 32 15 05 95 14 24 32 05 95 14 24 32 54 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 53 14 24 32 15 05 95 14 24 32 05 95 14 24 32 54 13 23 31 16 18 06 08 96 98 13 23 31 14 24 32 15 05 95 14 24 32 13 23 31 16 18 06 08 96 98 13 23 31 14 24 32 15 05 95 13 23 31 16 18 06 08 96 98 14 24 32 15 05 95 13 23 31 16 18 06 08 96 98 14 24 32 15 05 95 13 23 31 16 18 06 08 14 24 32 15 05 13 23 31 16 18 14 24 32 15 13 23 31 08 Off + isolation Off On, contactor open AUTO On, contactor closed AUTO Tripped, on overload TRIP. + Off, after overload TRIP. + Tripped, on short circuit TRIP. + Off, after short circuit TRIP. + Manual reset TRIP. + RESET ® www.epdatech.com 53 Integral Self-Protected Starters Integral 32 and 63 State of Auxiliary Contacts State of Auxiliary Contacts for LD5 FIG. 1 LD5 Auxiliary contact actuators 1 3 5 L1 L2 L3 AUTO A2 A1 + 0 U A2 A1 U Auxiliary contacts LA1-LC010 T1 T2 T3 2 4 6 LA1-LC012 LA1-LC020 LA1-LC021 98 13 23 31 13 23 31 53 63 LA1-LC031 13 23 31 16 18 06 08 96 98 13 23 31 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 08 Contact open Contact closed Off + isolation 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 14 24 32 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 13 23 31 16 18 06 08 96 98 13 23 31 08 98 13 23 31 13 23 31 53 63 15 05 95 14 24 32 05 95 14 24 32 14 24 32 54 64 Off On, both contactors open AUTO On, contactor open AUTO On, contactor closed AUTO Tripped on overload TRIP. + Off, after overload TRIP. + Tripped on short circuit TRIP. + Off after short circuit TRIP. + Manual reset TRIP. + 14 24 32 RESET ® 54 www.epdatech.com Integral Self-Protected Starters Wiring Diagrams Integral 18 FIG. 1 FIG. 2 1 3 5 L1 L2 L3 1 3 5 L1 L2 L3 A1 A2 A1 A2 A1 A2 I T1 2 II T2 T3 4 6 T1 T2 4 2 T3 6 Self-Protected Reversing Starter w/ Protection Module LB• Integral 18 LD5 LB130 + LB1 LB03P Self-Protected Starter w/ Protection Module LB• Integral 18 LD1 L80 Integral 32 FIG. 3 FIG. 5 1 3 5 L1 L2 L3 A1 A2 g ( 1 L1 T1 T2 T3 2 4 6 A1 3 L2 ) 5 L3 A2 A1 A2 Starter w/ Isolator Integral 32 LD4 FIG. 4 External control circuit 1 3 5 L1 L2 L3 A1 A2 Handle operator Control circuit contact Instantaneous trip mechanism (Trip coil) Protection module trip mechanism T1 T2 T3 2 4 6 Protection module Thermal trip Magnetic trip T1 T2 T3 2 4 6 Reversing Starter w/ Isolator Integral 32 LD5 Starter w/o Isolator Integral 32 LD1 Protection Modules: LB• FIG. 6 FIG. 7 T1 T2 T3 2 4 6 Thermal and Magnetic Trip LB1 T1 T2 T3 2 4 6 Magnetic Trip Only LB6 ® www.epdatech.com 55 Integral Self-Protected Starters Wiring Diagrams Auxiliary Contact Blocks FIG. 1 LA1 LC010 LA1 LC012 LA1 LC020 13 23 31 13 23 31 13 23 31 14 24 32 14 24 32 14 24 32 9698 98 95 95 0608 08 05 05 Trip signal 1 Short-circuit signal Knob position signal Auto + O 16 1 Contactor signalling placed on the right 18 15 For LD1 or LD4 and reverser LD5 (mounted on right) LA1 LC010, LA1 LC012 and LA1 LC020 FIG. 2 FIG. 3 LA1 LC030 (63) 53 (63) 53 54 (64) 54 (64) 1 or 2 LA1 LC030 Remote Reset Units1 for LD1, LD4 and LD5 AUTO TRIP + O RESET AC B4 AC M B1 13 23 31 LA1 LC031 14 24 32 2 Contactor signalling placed on the left Isolating contacts (mounted on left) LA1 LC031 Trip Units for LD1, LD4 and LD5 Use of the LA1 LC020 contact block prevents the mounting of trip or remote units FIG. 6 AC A1 + E1 - E1 AC A2 C1 A1 A2 D1 LA1 LC180, LA1 LD180 U< C2 D2 FIG. 8 AC A1 + E1 - E1 AC A2 For starter and reverser already fitted with a block, LA1 LC010 or LA1 LC012. LA1 LC052 Interface Modules FIG. 7 B2 B3 FIG. 4 2 For reversing LD5 (mounted on left) LA1 LC021 For LD4 w/ isolating contacts (mounted on left) LA1 LC030 FIG. 5 LA1 LC021 LA1 LC07•• A1 A2 LA1 LC580, LA1 LD580 ® 56 www.epdatech.com Integral Self-Protected Starters Wiring Diagrams Add-on Blocks: LA1 LB0•• FIG. 1 Contactor breakers Trip signal LA1 LB015 13 23 31 LA1 LB017 13 31 LA1 LB019 13 31 14 24 32 14 14 95 97 97 95 96 98 98 96 32 LA1 LB001 41 32 42 and For LD1 (mounted on right) FIG. 2 FIG. 3 LA1 - LB034 5 7 6 LA1 - LB031 Knob position 8 15 17 42 15 17 Signal 16 18 Contacts integrated into device 14 24 32 5 7 6 8 Short circuit signal 0 Auto 15 17 Short circuit signal Contactor breakers LA1 - LB021 13 23 31 LA1 - LB001 41 Auto 0 Signal 16 18 16 18 For LD1 (mounted on left) For LD5 (mounted on left) Time Delay Modules FIG. 4 Control Module FIG. 5 AC A1 Knob position AC A1 A2 FIG. 6 A2 B2 TSX AC B1 A1 0 t 0 A1 A2 A/M 1/0 t A2 A1 A1 K K On Module LA4 DT A2 A2 K Off Module LA4 DR Auto-Man-Stop Module LA4 DM Interface Modules FIG. 7 AC A1 + - E1 AC A2 E2 A1 FIG. 8 + AC A1 - E1 A1 A2 AC A2 E2 FIG. 9 AC A1 Solid State Module LA4 DW - AC A2 E2 A1 A2 A2 K K K + E1 Relay Module LA4 DF Relay Module w/ Manual Override LA4 DL Voltage Converters: LA1 LC080 and LA1 LD080 FIG. 11 Control by supply switching 24 or 48V E1 + A1 DC - (OV) E3 AC A2 FIG. 12 110V + A1 DC - (OV) E2 Low voltage control 24 or 48V E1 E1 Supply FIG. 10 AC A2 E3 + {- A1 DC AC A2 E2 E2 Low voltage input For 24 or 48 V Supply For 110 V Supply For 24 or 48 V Supply w/ Low Voltage Input ® www.epdatech.com 57 Type S AC Combination Magnetic Starters Class 8538 and 8539 3-Phase, Size 0-5 (see pages 45 and 49 for Size 6) 3-Pole, 3-Phase Combination Starters: Class 8538 and 8539 Type S FIG. 1 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 0-4 FIG. 2 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 5 ® 58 www.epdatech.com Type S AC Combination Magnetic Starters Class 8538 and 8539 3-Phase Additions and Special Features 3-Pole, 3-Phase Combination Starters w/ Control Circuit Transformer and Primary Fuses: Class 8538 and 8539 Type S Form F4T FIG. 1 L1 L2 L3 2-WIRE CONTROL (If used) 2 START DISCONNECTING MEANS, PROVIDED BY USER OR WITH CONTROLLER 3 START 1 STOP 2 OL 3 M M STOP L1 1 L2 L3 FU2 X2 X1 3-WIRE CONTROL FU1 SEC 3 1 PRI FU2 FU1 GROUND (If used) PRI X2 M SEC 3 A 2-WIRE CONTROL GROUND (If used) ALARM (IF SUPPLIED) T1 T2 T3 A * T1 L1 L2 OL COM MOTOR 1 DISCONNECTING MEANS 2 T2 L3 T3 M OL M OL M OL * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 0-4 FIG. 2 L1 L2 L3 2-WIRE CONTROL (If used) 2 START DISCONNECTING MEANS, PROVIDED BY USER OR WITH CONTROLLER 3 START 1 STOP 2 OL 3 CR STOP M CR 1 3-WIRE CONTROL X2 X1 1 L1 L2 L3 SEC FU2 FU1 FU1 3 PRI M X2 M T1 T2 T3 A A GROUND (If used) ALARM (IF SUPPLIED) * COM 1 L1 L2 OL L3 T1 T2 DISCONNECTING MEANS SEC 2 MOTOR GROUND (If used) CR 3 2-WIRE CONTROL FU2 PRI M OL M OL M OL T3 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 5 ® www.epdatech.com 59 Reduced Voltage Controllers Class 8606 Autotransformer Type, Size 2-6 Reduced Voltage Autotransformer Controllers w/ Closed Transition Starting: Class 8606 Size 2-5 FIG. 1 L3 50 0 100 84 65 OL T1 OL T2 1S AT R 2S MOTOR AT 2S 1S R TR 0 L2 2S 100 84 65 50 L1 CIRCUIT BREAKER OR DISCONNECT SWITCH R OL T3 1S TR R R 1S 1S 2S 2S 2 WIRE CONTROL DEVICE (IF USED) START STOP OL 3 2 1 TR TR Reduced Voltage Autotransformer Controller w/ Closed Transition Starting: Class 8606 Size 6 FIG. 2 L3 50 0 100 84 65 2S T1 1OL 1S AT R 2CT T2 2S MOTOR 2OL AT 2S R 1S 0 L2 1CT 100 84 65 50 L1 CIRCUIT BREAKER OR DISCONNECT SWITCH R 3CT T3 3OL 1TR R 1TR 1S 1S 2TR 2TR 2S R 1S 2S (H1) PRI (X1) SEC (X2) R (H1) PRI (X1) SEC (X2) 2 WIRE CONTROL DEVICE (if used) START STOP 1 GROUND (if used) 3 2 OL 1TR 1TR ® 60 www.epdatech.com For more books join our telegram group Click here to join https://t.me/engubook Reduced Voltage Controllers Class 8606 Autotransformer Type, Size 7 Reduced Voltage Autotransformer Controllers w/ Closed Transition Starting: Class 8606 Size 7 FIG. 1 L3 50 0 100 84 65 1CT T1 2CT T2 1S AT R 2S MOTOR AT 2S 1S R 0 L2 2S 100 84 65 50 L1 CIRCUIT BREAKER OR DISCONNECT SWITCH R 3CT T3 SOLID STATE OVERLOAD RELAY 1TR R (H1) PRI 1TR (X1) SEC (X2) 1S 1S 2TR 2TR (H1) PRI (X1) SEC (X2) 2S R 1S 2S (H1) PRI (X1) SEC (X2) R (H1) PRI (X1) SEC (X2) 2 WIRE CONTROL DEVICE (If used) START STOP 1 GROUND (If used) 3 2 OL 1TR 1TR ® www.epdatech.com 61 Reduced Voltage Controllers Class 8630 Wye-Delta Type, Size 1Y∆-5Y∆ Wye-Delta Type Reduced Voltage Controllers, Size 1Y∆-5Y∆: Class 8630 FIG. 1 FPO 46-1 110% Size 1Y∆-5Y∆ Controllers with Open-Transition Starting FIG. 2 FPO 46-2 110% Size 1Y∆-5Y∆ Controllers with Closed-Transition Starting ® 62 www.epdatech.com Reduced Voltage Controllers Class 8630 Wye-Delta Type, Size 6Y∆ Wye-Delta Type Reduced Voltage Controllers, Size 6Y∆: Class 8630 FIG. 1 FPO 46-3 110% Size 6Y∆ Controller with Open-Transition Starting FIG. 2 FPO 46-4 110% Size 6Y∆ Controller with Closed-Transition Starting ® www.epdatech.com 63 Reduced Voltage Controllers Class 8640 2-Step, Part-Winding Type Table 5 Motor Lead Connections Part Winding Schemes 1/2 Wye or Delta 6 Leads 1/2 Wye 9 Leads [1] 1/2 Delta 9 Leads [1] [2] A T1 Lettered Terminals in Panel B C D E F T2 T3 T7 T8 T9 T1 T2 T3 T7 T8 T9 T1 T8 T3 T6 T2 T9 Connect terminals T4, T5 and T6 together at terminal box. [2] Part Winding Schemes Lettered Terminals in Panel B C D E F T2 T9 T7 T8 T3 2/3 Wye or Delta 6 Leads A T1 2/3 Wye 9 Leads [1] T1 T2 T9 T7 T8 T3 T1 T4 T9 T6 T2 T3 2/3 Delta 9 Leads [2] Connect terminals T4 and T8, T5 and T9, T6 and T7 together in 3 separate pairs at terminal box. Part-Winding Reduced Voltage Controllers: Class 8640, Size 1PW-7PW FIG. 2 FIG. 1 Size 1PW-4PW, 2-Step Part-Winding Controllers Size 5PW, 2-Step Part-Winding Controller FIG. 4 FIG. 3 Size 6PW, 2-Step Part-Winding Controller ➀ Disconnect means (optional): 2 required, 1 for each motor winding. Size 7PW, 2-Step Part-Winding Controller ➁ See Table 5 for motor lead connections. ® 64 www.epdatech.com Reduced Voltage Controllers Class 8647 Primary-Resistor Type 3-Phase Primary-Resistor Reduced Voltage Controllers: Class 8647, Size 1-7 FIG. 1 RES M L3 FIG. 2 T1 M DISCONNECT MEANS (OPTIONAL) L2 OL L1 DISCONNECT MEANS (OPTIONAL) L1 A RES M OL T2 L2 MOTOR A RES M OL T3 L3 RES OL T1 RES OL T2 A M MOTOR A RES M OL T3 A A TR A TR M M TR TR A A 2 WIRE CONTROL DEVICE (if used) 2 WIRE CONTROL DEVICE (if used) START STOP 1 3 2 START STOP OL 1 TR TR Size 5 L3 1CT RES A M 2CT M L1 T2 MOTOR A L2 2OL 3CT RES A F U 2 T1 1OL RES M FIG. 4 T3 L3 3OL DISCONNECT MEANS (OPTIONAL) L2 DISCONNECT MEANS (OPTIONAL) M L1 F U 3 1TR M 1CT T1 RES 2CT T2 MOTOR A M RES 3CT T3 A SOLID STATE OVERLOAD RELAY F U 3 1TR 2TR RES A F U 2 1TR TR TR Size 1-4 FIG. 3 OL 3 2 1TR 2TR 2TR 2TR M (H1) PRI M A (X1) SEC (H1) PRI (X1) SEC M M (X2) A (H1) PRI A (H1) PRI FU1 (X1) SEC (X1) SEC (X2) (X2) A 2 WIRE CONTROL DEVICE (if used) (H1) PRI FU1 (X1) SEC GROUND (if used) START STOP 1 (X2) 3 2 OL 1TR 1TR (X2) 2 WIRE CONTROL DEVICE (if used) START STOP 1 GROUND (if used) 3 2 OL 1TR 1TR Size 7 Size 6 ® www.epdatech.com 65 Reduced Voltage Controllers Class 8650 and 8651 Wound-Rotor Type Wound-Rotor Reduced Voltage Controllers: Class 8650 and 8651 FIG. 1 FPO 49-3 135% Non-Reversing Wound-Rotor Motor Controller w/ 3 Points of Acceleration Class 8650 FIG. 2 FPO 49-4 135% Reversing Wound-Rotor Motor Controller w/ 3 Points of Acceleration Class 8651 ® 66 www.epdatech.com Solid State Reduced Voltage Starters Class 8660 ®, Type MD-MG ALPHA PAK ALPHA PAK® Solid State Reduced Voltage Starters: Class 8660 Type MD-MG FIG. 1 1CT CIRCUIT BREAKER OR DISCONNECT SWITCH M L1 L2 L3 T1 T2 M MOTOR 3CT M T3 SOLID STATE OVERLOAD RELAY TO 120 V SEPARATE CONTROL STOP START OT* * OT is a switch that opens when an overtemperature condition exists (Type MFO and MGO only) M M Type MD (16 A), ME (32 A), MF (64 A) and MG (128 A) L1 L2 L3 CIRCUIT BREAKER OR DISCONNECT SWITCH FIG. 2 ISO M ISO M 1CT T1 T2 MOTOR ISO 3CT M T3 SOLID STATE OVERLOAD RELAY TO 120 V SEPARATE CONTROL STOP START OT* M M CR * OT is a switch that opens when an overtemperature condition exists (Type MFO and MGO only) TR TR ISO ALARM CR Type MD (16 A), ME (32 A), MF (64 A) and MG (128 A) w/ Isolation Contactor ® www.epdatech.com 67 Solid State Reduced Voltage Controllers Class 8660 Type MH, MJ, MK and MM Solid State Reduced Voltage Controllers: Class 8660 Type MH, MJ, MK and MM FIG. 1 Type MH (200 A), MJ (320 A), MK (500 A) and MM (750 A) FIG. 2 Type MH (200 A) w/ Shorting Contactor FIG. 3 Type MJ (320 A), MK (500 A) and MM (750 A) w/ Shorting Contactor ® 68 www.epdatech.com Solid State Reduced Voltage Controllers Class 8660 Type MH, MJ, MK and MM Solid State Reduced Voltage Controllers: Class 8660 Type MH, MJ, MK and MM FIG. 1 FPO 51-1 130% Type MH (200 A) w/ Isolation Contactor FIG. 2 FPO 51-2 130% Type MJ (320 A), MK (500 A) and MM (750 A) w/ Isolation Contactor ® www.epdatech.com 69 Solid State Reduced Voltage Controllers Class 8660 Type MH, MJ, MK and MM Solid State Reduced Voltage Controllers: Class 8660 Type MH, MJ, MK and MM FIG. 1 FPO 51-3 130% Type MH (200 A) w/ Isolation Contactor and Shorting Contactor FIG. 2 FPO 51-4 130% Type MJ (320 A), MK (500 A) and MM (750 A) w/ Isolation Contactor and Shorting Contactor ® 70 www.epdatech.com Type S AC Reversing Magnetic Starters Class 8736 2- and 3-Pole Reversing Starters, 2- and 3-Pole, Size 00-1: Class 8736 Type S FPO 52-1 FIG. 1 FPO 52-1 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram 2-Pole, w/ Single Phase, 3-Lead Motor FIG. 2 FPO 52-2 * Marked “OL” if alarm contact is supplied FPO 52-2 Elementary Diagram Wiring Diagram 3-Pole, w/ Single Phase, 4-Lead Repulsion-Induction Motor FPO 53-1 FIG. 3 FPO 53-1 * Marked “OL” if alarm contact is supplied Wiring Diagram Elementary Diagram 3-Pole, w/ Single Phase, 4-Lead Capacitor or Split-Phase Motor ® www.epdatech.com 71 Type S AC Reversing Magnetic Starters Class 8736 3- and 4-Pole Reversing Starters, 3- and 4-Pole: Class 8736 Type S FIG. 1 FPO 53-2 FPO 53-2 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 00-2, 4-Pole, 2-Phase FIG. 2 FPO 53-3 * Marked “OL” if alarm contact is supplied FPO 53-3 Elementary Diagram Wiring Diagram Size 00-4, 3-Pole, 3-Phase FIG. 3 FPO 54-1 FPO 54-1 Elementary Diagram Wiring Diagram Size 5, 3-Pole, 3-Phase ® 72 www.epdatech.com Type S AC 2-Speed Magnetic Starters Class 8810 Starters for 2-Speed, 2-Winding (Separate Winding), 3-Phase Motors: Class 8810 Type S FPO 54-2 FIG. 1 FPO 54-2 Elementary Diagram Wiring Diagram Size 0-4 FIG. 2 FPO 54-3 Size 5 Wiring Diagram Starters for 2-Speed, 1-Winding (Consequent Pole), Constant or Variable Torque, 3-Phase Motors: Class 8810 Type S FPO 55-1 FIG. 3 FPO 55-1 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 0-2 ® www.epdatech.com 73 Type S AC Reversing Magnetic Starters Class 8810 Starters for 2-Speed, 1-Winding (Consequent Pole), Constant or Variable Torque, 3-Phase Motors: Class 8810 Type S FIG. 2 FIG. 1 FPO 55-3 FPO 55-2 * Marked “OL” if alarm contact is supplied Size 5 Wiring Diagram Size 3 and 4 Wiring Diagram Starters for 2-Speed, 1-Winding (Consequent Pole), Constant Horsepower, 3-Phase Motors: Class 8810 Type S FPO 55-4 FIG. 3 FPO 55-4 * Marked “OL” if alarm contact is supplied Elementary Diagram Wiring Diagram Size 0-2 FIG. 4 FIG. 5 FPO 56-2 75% FPO 56-1 75% * Marked “OL” if alarm contact is supplied * Marked “OL” if alarm contact is supplied Size 3 and 4 Wiring Diagram Size 0, w/ High-Off-Low Selector Switch (Form C7) Wiring Diagram ® 74 www.epdatech.com 2-Speed Magnetic Starters Class 8810 Special Control Circuits Form R1 Form R2 FIG. 1 FIG. 2 FPO 57-2 FPO 57-1 Compelling Relay, Requiring Motor Starting in Low Speed Accelerating Relay, Providing Timed Acceleration to Selected Speed Form R3 Form R2R3 FIG. 4 FIG. 3 FPO 57-3 FPO 57-4 Accelerating Relay and Decelerating Relay Decelerating Relay, w/ Time Delay During Transfer from Higher to Lower Speed Form R1R3 FIG. 5 Form A10C FPO 57-5 FIG. 6 FPO 57-6 Compelling Relay and Decelerating Relay Hand-Off-Auto Selector Switch and High-Low Push Button Form CC17 Form A10CR1 FIG. 7 FIG. 8 FPO 57-7 Hand-Off-Auto Selector Switch and High-Low Selector Switch FPO 57-8 Hand-Off-Auto Selector Switch and High-Low Push Button w/ Compelling Relay/Timer ® www.epdatech.com 75 2-Speed Magnetic Starters and Multispeed Motor Connections Class 8810 Special Control Circuits and 1- and 3-Phase Motor Connections Form C25 Form CC17 R2R3 FIG. 1 FIG. 2 FPO 57-10 120% FPO 57-9 Hand-Off-Auto Selector Switch and High-Low Selector Switch w/ Accelerating and Decelerating Relay/Timer High-Low-Off-Auto Selector Switch Multispeed Motor Connections: 1-Phase, 2-Speed Motors FIG. 3 T1 T2 T3 FIG. 4 T4 T1 T2 T3 FIG. 5 T4 COM A B Speed L1 L2 Open Together Speed L1 L2 Open Together Speed L1 L2 Open Together Low High T1 T3 T2 T4 T3,T4 T1,T2 — — Low High T3 T1 T4 T2 T1,T2 T3,T4 — — Low High COM COM A B B A — — 2 Windings FIG. 6 T1 2 Windings COM FIG. 7 T4 T1 1 Winding COM FIG. 8 T4 T1 COM T4 Speed L1 L2 Open Together Speed L1 L2 Open Together Speed L1 L2 Open Together Low High COM COM T1 T4 T4 T1 — — Low High T1 T1 T4 COM COM — — T1,T4 Low High T1 T1 COM T4 — COM T1,T4 — 1 Winding 1 Winding 1 Winding Multispeed Motor Connections: 3-Phase, 2-Speed Motors FIG. 9 FIG. 10 T4 T3 FIG. 11 T4 T1 T3 T4 T1 T1 T3 T5 Speed L1 L2 L3 Low High T1 T6 T2 T4 T3 T5 Open Together — T4,T5,T6 All others — 1 Winding, Constant Horsepower FIG. 12 T1 T3 Speed Low High L1 L2 T13 L3 T1 T2 T3 T11 T12 T13 Separate Windings Speed L1 L2 L3 Low High T1 T6 T2 T4 T3 T5 T12 Open All others All others T6 Open Together All others — — T1,T2,T3 T3 Speed Low High T2 L1 L2 T13 T17 L3 T1 T2 T3 T11 T12 T13,T17 T6 Speed L1 L2 L3 Low High T1 T6 T2 T4 T3 T5 Open Together All others — — T1,T2,T3 1 Winding, Variable Torque FIG. 14 T11 T1 T2 T5 1 Winding, Constant Torque FIG. 13 T11 T2 T2 T5 T6 T2 T12 T1 T3 T2 T13 T7 Open Speed All others All others Low High Separate Windings T11 L1 L2 T1 T2 T11 T12 T12 L3 Open T3,T7 T13 All others All others Separate Windings ® 76 www.epdatech.com Multispeed Motor Connections 3-Phase Multispeed Motor Connections: 3-Phase, 2-Speed Motors FIG. 1 T1 FIG. 2 T11 T1 FIG. 3 T5 T1 T11 T2 T4 T4 T2 T14 L3 L2 T12 T6 T3 T7 T2 T13 T17 Speed L1 Low High L2 T12 L3 Open T1 T2 T3,T7 T11 T12 T13,T17 T3 T3 Speed All others All others L1 Low High Separate Windings L3 T1 T1,T5 L2 L4 Open T5 T2 T6 T3 T2,T6 T4 T13 Speed L1 Low High T3,T4 — 2-Phase, 1 Winding, Variable Torque L4 Open T1 T3 T2 T4 All others T11 T13 T12 T14 All others 2-Phase, Separate Windings Multispeed Motor Connections: 3-Phase, 3-Speed Motors FIG. 4 T4 FIG. 5 T11 T4 T3 T1 T7 L1 Low 2nd High L2 L3 T12 Open Together Speed L1 Low 2nd High T1 L1 Low 2nd High T13 T12 L3 Open Together Speed T3 T5 T13 All others All others All others — T1,T2,T3 — Low 2nd High T6 L2 T1 T2 T6 T4 T11 T12 Together L1 T12 T15 L3 L2 T1 T2 T11 T12 T6 T4 Together 2 Windings, Constant Torque FIG. 9 T14 T1 T11 T13 T3 T13 T12 L3 Open Together Speed T3 T13 T5 All others All others All others — — T1,T2,T3 Low 2nd High T6 T16 Open Low T1 T2 T3 All others — 2nd T11 T12 T13,T17 All others — High T16 T14 T15 All others T11,T12,T13,T17 T11 T2 T5 2 Windings, Variable Torque T2 Speed L1 L2 T1 T3 T2 Open T4 T11 T3 L3 T3 T12 T1 T2 T3,T7 All others — T11 T12 T13 All others — T6 T4 T5 All others T1,T2,T3,T7 FIG. 8 T4 T5 L2 T11 T17 2 Windings, Constant Torque 2 Windings, Constant Torque Speed T13 T6 T13 T2 T5 T1 T2 T3,T7 All others — T6 T4 T5 — T1,T2,T3,T7 T11 T12 T13 All others — FIG. 7 T14 T1 T1 T7 T6 T13 T2 T5 Speed FIG. 6 T11 T3 2 Windings, Variable Torque L1 T2 T15 L2 L3 T1 T2 T11 T12 T16 T14 T3 T13 T15 T12 T16 Open Together All others — All others — All others T11,T12,T13 2 Windings, Variable Torque Multispeed Motor Connections: 3-Phase, 4-Speed Motors FIG. 10 T4 T3 FIG. 11 T14 T1 T13 T4 T11 FIG. 12 T14 T3 T1 T13 T4 T14 T13 T3 T11 T1 T7 T7 T2 T5 Speed Low 2nd 3rd High L1 L2 T6 L3 T1 T2 T3 T6 T4 T5,T7 T11 T12 T13 T16 T14 T15,T17 T15 T17 T12 Open T16 Speed All others T4,T5,T6,T7 All others — All others T14,T15,T16,T17 All others — T4 T1 T7 T2 T5 Low 2nd 3rd High T15 T17 T12 T6 L3 Open T1 T2 T3 T11 T12 T13 T6 T4 T5,T7 T16 T14 T15,T17 T16 Speed All others T4,T5,T6,T7 All others T14,T15,T16,T17 All others — All others — T4 T2 T5 Together L1 Low 2nd 3rd High 2 Windings, Constant Horsepower FIG. 14 T14 L2 T6 L2 L3 T12 T15 Open T16 Together T1 T2 T3,T7 All others — T6 T4 T5 All others T1,T2,T3,T7 T11 T12 T13,T17 All others — T16 T14 T15 All others T11,T12,T13,T17 2 Windings, Constant Torque FIG. 15 T14 T4 T14 T13 T3 Speed L1 Low 2nd 3rd High 2 Windings, Constant Horsepower FIG. 13 T7 T2 T5 Together T11 T17 L1 L2 T11 T17 T6 L3 T15 Open T1 T3 T12 T16 Together T1 T2 T3,T7 All others — T11 T12 T13,T17 All others — T6 T4 T5 All others T1,T2,T3,T7 T16 T14 T15 All others T11,T12,T13,T17 2 Windings, Constant Torque T5 Speed Low 2nd 3rd High T2 L1 T6 L2 T11 T13 L3 T1 T2 T3 T6 T4 T5 T11 T12 T13 T16 T14 T15 T15 T12 T16 T5 Open Together Speed All others All others All others All others — T1,T2,T3 — T11,T12,T13 Low 2nd 3rd High 2 Windings, Variable Torque T1 T3 T2 L1 T6 L2 T11 T13 L3 T1 T2 T3 T11 T12 T13 T6 T4 T5 T16 T14 T15 T15 T12 T16 Open Together All others All others All others All others — — T1,T2,T3 T11,T12,T13 2 Windings, Variable Torque ® www.epdatech.com 77 For more books join our telegram group Click here to join https://t.me/engubook Programmable Lighting Controllers Class 8865 Programmable Lighting Controller: Class 8865 Type TC12 FIG. 1 CIRCUIT 12 CIRCUIT 9 CIRCUIT 8 RELAY OUTPUT CONNECTIONS CIRCUITS 7-12 CIRCUIT 11 CIRCUIT 10 35 CIRCUIT 7 18 19 17 20 16 CIRCUIT 6 21 15 22 14 23 13 CIRCUIT 5 24 12 25 11 26 10 CIRCUIT 4 27 9 28 8 29 7 30 6 CIRCUIT 3 RELAY OUTPUT CONNECTIONS CIRCUITS 1-6 31 5 32 4 CIRCUIT 2 33 3 34 2 CIRCUIT 1 1 INPUTS Demand Input 36 +1– +2– +3– +4– +5– +6– +7– +8– 24 VAC INPUT ® 78 www.epdatech.com AC Lighting Contactors Class 8903 Load Connections Load Connections for AC Lighting Contactors: Class 8903 FIG. 1 FIG. 2 L1 L1 L2 L2 IF USED LOAD LOAD IF USED LOAD LOAD Vload = Vline-tol-line Vload L2 = Vline-to-lineLN L1 1-Phase, 2-Wire, Single Load FIG. 3 L1 L2 1-Phase, 2-Wire, Multiple Loads FIG. 4 LN L1 L2 IF USED LN IF USED LOAD LOAD Vload = Vline-to-neu- LOAD Vload = Vline-to-line 1-Phase, 3-Wire, Loads Connected Line-to-Neutral FIG. 5 L1 L2 1-Phase, 3-Wire, Load Connected Line-to-Line FIG. 6 L3 L1 LOAD L2 LOAD L3 LOAD LOAD LOAD Vload = Vline-to-line L1 1.732 L2 L3 Vload = Vline-to-line LN 3-Phase, 3-Wire, Wye-Connected Load FIG. 7 L1 L2 L3 LOAD Iload = Icontacts 1.732 3-Phase, 3-Wire, Delta-Connected Load LN LOAD IF USED LOAD LOAD Vload = Vline-to-neu- Application Limits: 1. Voltage between line side conductors must not exceed line-to-line voltage rating of contactor. 2. Vload must not exceed volts-per-load rating of contactor. 3. Line current carried by any contact must not exceed ampere rating of contactor. For contact ratings, refer to the Square D Digest. 3-Phase, 4-Wire, Loads Connected Line-to-Neutral ® www.epdatech.com 79 AC Lighting Contactors Class 8903 Control Circuit Connections Control Circuit Connections for Electrically-Held Contactors: Class 8903 Type L and S FIG. 1 ON OFF To AC common or separate control supply COIL FIG. 4 M On-Off Push Button (Form A12) FIG. 2 2-WIRE PILOT DEVICE A1 A2 COIL I I HAND OFF AUTO To AC common or separate control supply A1 A2 A1 To AC common or separate control supply Direct Control from Pilot Device FIG. 3 COIL 2-WIRE PILOT DEVICE A2 I I ON OFF COIL A1 To AC common or separate control supply A2 On-Off Selector Switch (Form C6) Hand-Off-Auto Selector Switch (Form C) Control Circuit Connections for Mechanically-Held Contactors: Class 8903 Type LX and S FIG. 5 COIL CLEARING CONTACTS (Supplied) ON FIG. 6 A1 A2 LATCH I ON OFF LATCH 14 17 14 A OFF UNLATCH 15 18 A2 To AC common or separate control supply On-Off Push Button (Form A3) B On-Off Selector Switch (Form C6) COIL CLEARING CONTACTS (Supplied) FIG. 8 1-POLE PILOT DEVICE CR CR LATCH COIL CLEARING CONTACTS (Supplied) LATCH 14 17 A To AC common or separate control supply A UNLATCH 15 B 2-POLE PILOT DEVICE 17 A1 18 To AC common or separate control supply FIG. 7 COIL CLEARING CONTACTS (Supplied) I 14 UNLATCH 15 Control from 2-Pole Pilot Device 17 A 18 B CR To AC common or separate control supply UNLATCH 15 18 B 1-Pole Pilot Device w/ CR relay (Form R6) ® 80 www.epdatech.com AC Lighting Contactors and Electronic Motor Brakes Class 8903 and 8922 Panelboard Type Wiring: Class 8903 Type PB, 30-225 A FIG. 1 FIG. 3 FIG. 4 L1 L2/N O ON ON Control Circuit – Standard O CR1 CR2 CR2 L2/N CR1 CR + L C L = Line (common) O = Open (unlatch) C = Close (latch) Control Circuit – 2-Wire Control (Form R6) – SC C L1 BR SO O CR T3 O L1 L CR T2 L C OFF FIG. 2 2-Wire Pilot Device T1 L2/N C L1 L3 C L OFF L2 Control Circuit – Long-Distance Control (Form R62) Omit middle pole for 2-pole unit Power Circuit QWIK-STOP® Electronic Motor Brake: Class 8922 FIG. 5 CUSTOMER CONTROL CIRCUIT F1 F1 ETB 10/18 15 18 Xo START OL M Xo M OL T1 F2 M OL T2 F2 M OL T3 L2 [1] STOP F2 L1 MOTOR L3 + M 24 VDC – M F3 [3] ETB 10/18 [2] F3 [3] L1 L+ L2 L– [4] [1] Contacts 15 and 18 close when L1 and L2 are energized. PLC [2] When controlling electronic motor brake ETB 10/18 with a PLC (programmable logic control), terminals Xo-Xo must be jumpered. B– B1 [3] Semiconductor fuses. B+ [4] Connection for ETBS only. POWER CIRCUIT Type ETB10, ETB18 and ETBS18 w/ Internal Braking Contactor FIG. 6 CUSTOMER CONTROL CIRCUIT F1 F1 ETB 20/800 B STOP START OL T1 F2 M OL T2 F2 M OL T3 MOTOR + 24 VDC M B Xo OL L3 M M 25 28 M L2 [1] 15 18 F2 L1 – F3 [3] ETB 20/800 Xo F3 M [3] PLC [2] L1 L+ B L2 L– B [4] [1] Contacts 15 and 18 close when L1 and L2 are energized. [2] When controlling electronic motor brake ETB 20/800 with a PLC B– B1 (programmable logic control), terminals Xo-Xo must be jumpered. B+ [3] Semiconductor fuses. [4] POWER CIRCUIT QWIK-STOP is a registered trademark of Square D. Connection for ETBS only. Type ETB20-ETB800 and ETBS20-ETBS800 ® www.epdatech.com 81 Electronic Motor Brakes, Duplex Motor Controllers and Fiber Optic Transceivers Class 8922, 8941 and 9005 QWIK-STOP® Electronic Motor Brake: Class 8922 Type ETBC FIG. 1 CUSTOMER CONTROL CIRCUIT F1 F2 M OL T1 F2 M OL T2 F2 M OL T3 L1 F1 L2 1 2 L3 [1] 3 MOTOR M START 4 5 ETBC M M F3 [2] L1 B T1/2 L2 B T2/4 [1] To control electronic motor PLC 9 + B– 10 – B+ [2] M 6 7 F3 OL STOP 24 VDC INPUT brake ETBC with input B+/B–, terminals 3 and 4 must be jumpered. [2] Semiconductor fuses. QWIK-STOP is a registered trademark of Square D. Type ETBC AC Duplex Motor Controller: Class 8941 FIG. 2 Fiber Optic Transceiver: Class 9005 FIG. 3 14 OUTPUT 12 11 POWER 86 GAIN ADJ. SCREW GAIN OUTPUT STATUS LED SETUP LED SETUP OUTPUT FIBER RELEASE FIBER RELEASE LEVER FIBER A1 Elementary Diagram for Duplex Motor Controller w/ Electric Alternator INPUT A2 Transceiver, Front View FIG. 4 HAZARDOUS LOCATIONS CLASS I GROUPS A, B, C & D CLASS II GROUPS E, F & G CLASS III NONHAZARDOUS LOCATIONS FIBER OPTIC TRANSCEIVER FIBER OPTIC PUSH BUTTON, SELECTOR SWITCH, LIMIT SWITCH, ETC. FIBER OPTIC CABLE CLASS 9005 TYPE FT FIBER OPTIC CABLE ELECTRICAL CONNECTIONS BOUNDARY SEAL TO BE IN ACCORDANCE WITH ARTICLE 501-5 OF THE NATIONAL ELECTRICAL CODE Location ® 82 www.epdatech.com Photoelectric and Inductive Proximity Switches Class 9006 Photoelectric Switches: Class 9006 Type PE1 (Obsolete) FIG. 1 FIG. 2 AC thru-beam emitter has no output switching capability, therefore leakage current is not applicable. Thru-beam emitter is connected directly across the AC line and typically draws 15 mA. Connect load in series. To prevent damage, all switches except emitters must have load connected to switch. 2-Wire AC, Single Device Operation AC Emitter FIG. 3 FIG. 4 DC thru-beam emitter has no output switching capability, therefore it requires only a 2-wire cable connected directly across the DC. Thru-beam emitter draws a maximum of 45 mA. DC switches cannot be wired in series. To prevent damage, all switches except emitters must have load connected to switch. 4-Wire DC, Single Device Operation, 10-30 VDC, 250 mA Max. Load DC Emitter Photoelectric Switches: Class 9006 Type PE6 and PE7 (Obsolete) Photoelectric Switches: Class 9006 Type PEA120 (Obsolete) FIG. 5 FIG. 8 12-24 VDC, Sinking (NPN) FIG. 6 These switches are light operated only. 12-24 VDC, Sourcing (PNP) Beam broken = load deenergized Beam unbroken = load energized FIG. 7 Diagram shows contact arrangement with beam broken. 120 VAC, Emitter Only 120 VAC Amplifier Inductive Proximity Switches: Class 9006 Type PS (Obsolete) FIG. 9 FIG. 10 2-Wire AC, N.O. FIG. 12 FIG. 11 2-Wire AC, N.C. FIG. 13 2-Wire DC, N.O. 2-Wire AC, N.O. or N.C. FIG. 14 4-Wire DC, Sinking (NPN) 4-Wire DC, Sourcing (PNP) ® www.epdatech.com 83 Inductive Proximity Sensors XS, XSC, XSF and XSD XS Tubular Inductive Proximity Sensors FIG. 1 +/– BN/3 FIG. 2 for connector version only BN/2 NO BU/4 –/+ BU/3 2-Wire DC, Non-Polarized FIG. 3 BN/1 FIG. 5 BN/1 + PNP BK/4 NO BK/2 NC NO NC NO – BU/3 BN/1 BN/1 – 3-Wire DC, N.O. or N.C. WH/2 – BU/3 (NO), BN/1 (NC) + NC BU/3 + BK/4 PNP – NO NO BK/4 NPN BK/2 NC BK/4 NO BN/1 (NO), BU/3 (NC) + BU/3 + NPN L2 –/+ 2-Wire AC/DC FIG. 4 PNP L1 +/– AC/DC BU/3 + NPN BK/4 BK/4 WH/2 – – BN/1 (NO), BU/3 (NC) 3-Wire DC, N.O. and N.C., Complementary 3-Wire DC, Selectable PNP/NPN, N.O./N.C. XSC Rectangular Inductive Proximity Sensors FIG. 6 +/– 3 FIG. 7 5 FIG. 8 L1 FIG. 9 5 1 PNP AC/DC NO NC 4 –/+ 3 +/– 4 –/+ NO 6 NO 7 8 L2 8 BK 5 L1 6 L2 5 AC/DC NC NC 7 7 BK 2-Wire AC, Programmable 2-Wire DC, Non-Polarized NO NC 6 2 3 – 1 NPN + NO 6 NC 8 3 2-Wire AC/DC, Programmable + 4 4 2 – 3-Wire DC, N.O. or N.C. XSF Rectangular Inductive Proximity Sensors FIG. 11 FIG. 10 1 NO NC L1 1 PNP 4 NO NC + 2 2 L2 3 – 1 L1 1 NPN + 4 L2 NO NC 3 2-Wire AC, Programmable N.O. or N.C. 4 2 – 3-Wire DC, N.O. or N.C. XSD Rectangular Inductive Proximity Sensors FIG. 13 FIG. 12 3 NO FIG. 14 +/– 4 –/+ 3 +/– NO 7 NC 4 8 –/+ NC 7 NO 2 – 1 NPN + NO L2 2-Wire AC, Programmable N.O. or N.C. + 3 NC 3 2-Wire DC, Non-Polarized 4 NC L1 LOAD 8 1 PNP 4 2 – 3-Wire DC, N.O. or N.C. ® 84 www.epdatech.com Inductive and Capacitive Proximity Sensors XS and XTA AA A XS Tubular Inductive Proximity NAMUR Sensors ed to a solid state in ut (e.g. : ST1 CC/CS, TSX DET 466) Ri = 1K BN-1 + Object + present 7...12V DC _ FIG. 1 Object absent BU-2 - BN-1 + BU-2 - I < 1mA Ri = 1K FIG. 2 Wiring diagram - + + BN + proximity sensor _ 1 BU - (110...240 V) (110...240V) ACHzP= AC P = 5 VA, 50 XZD 7...12V DC I > 3mA A 2 } 4 2.F 2.0 1.+ Non-Intrinsically Safe Applications (Normal Safe Zone), Connected to a Solid State Input With XZD Power Supply/Relay Amplifier Unit XS Inductive Proximity Sensors w/ Analog Output FIG. 3 FIG. 4 Output current @ 24 V: 0-10 mA 0-16 mA @ 48 V: 0-10 mA Value of Load R (max.) 1800 Ω 1125 Ω 4200 Ω Output current @ 24 V: 4-14 mA 4-20 mA @ 48 V: 4-14 mA 2-Wire DC FIG. 5 Value of Load R (max.) 640 Ω 450 Ω These sensors may be wired in the 2- or 3-wire mode, depending on the current output characteristics required. 2350 Ω 3-Wire DC XTA Tubular Capacitive Proximity Sensors , BN BU FIG. 6 BN L1 L2 PNP BN + NPN BK + BK Gn* BU * Ground for XTA A115 only - BU - 3-Wire DC 2-Wire AC ® www.epdatech.com 85 Magnet Actuated Proximity Sensors and Photoelectric Sensors SG, ST and XUB SG Magnet Actuated Proximity Sensors, Surface Mount Style FIG. 1 FIG. 2 L2 L1 FIG. 3 L2 L1 Black Red LOAD LOAD White SGA 8016, SGA 8031, SGA 8182, SGA 8053, SGA 8176, SGA 8177, SG0 8168 and SG08239 SGB 8175 LOAD LOAD SG2 8195 SG Magnet Actuated Proximity Sensors, Limit Switch Style FIG. 4 FIG. 5 L2 L1 FIG. 6 L2 L1 NO Com LOAD LOAD NC SG0 8003, SG1 8004, SGA 8005 and SGA 8040 FIG. 7 + + SG0 L8003 and SG1 L8004 FIG. 8 Com – + + SG1 8056 is normally closed. Connect red terminal (+) to power source. Connect minus (-) terminal to load. Housing must be connected to minus. LOAD SG0 B8114, SG1 B8147, SG0 BL8114, SG0 BL8147 and SGC 8142-T-P LOAD SGC 8027 and SGC 8025 - L LOAD LOAD SG0 8079 and SG1 8056 SG Magnet Actuated Proximity Sensors, Tubular Style FIG. 9 FIG. 10 L2 L1 NO LOAD Com LOAD LOAD NC SGC 8058 and SGC 8181 SGA 8057, SGA 8189, SGA 8072, SGA 8179, SGA 8180 and SGA 8038 SG Magnet Actuated Proximity Sensors, Maintained Contact FIG. 11 FIG. 12 L2 L1 L1 LOAD 2 1 6.8k SGA 8018, SGO 8026 L2 LOAD 3 SGO 8110 ST Grounded Probe Switch FIG. 13 FIG. 14 Blk Gnd Wht Red L1 L2 LOAD hot 1 L1 hot housing neutral Target connected to ground 2 3 4 Not used L2 LOAD neutral Target connected to ground. Housing must be grounded for proper operation. Cable Wiring ST switches may be wired in series or parallel. For series operation, connect red lead (terminal 4) to black lead (terminal 1) of other switch. The voltage drop across each switch (in the closed state) does not exceed 2 VAC. Terminal strip Wiring XUB Short Range Tubular Photoelectric Sensors FIG. 16 FIG. 15 2-Wire AC FIG. 17 AC Emitter DC Emitter ® 86 www.epdatech.com Photoelectric Sensors XUM, XUH, XUG, XUL and XUJ XUM Miniature High Performance Photoelectric Sensors FIG. 1 + Light Prog. FIG. 2 FIG. 3 Test W OG - Dark BN BK J BN BK H LOAD LOAD + Light Prog . OG Test LOAD BU BU W XUH and XUG Medium Range Photoelectric Sensors LOAD - Dark NPN Output PNP Output 5-Wire AC XUL Subcompact Photoelectric Sensors FIG. 4 Emitter DC FIG. 5 Connector, PNP output BN 1 4 BU 3 Prog. 2 Emitter + light - dark DC 3 wire Connector, NPN output PNP output Prog. 2 + light + light BK DC connector NPN output BN 1 + light - dark AC/DC OG RD + BK BU OG AC/DC Relay output AC/DC versions - dark - dark Prog. BU 4 3 BU OG AC/DC 1 BN BK Prog. BN 2 prog. BU BN AC/DC 4 Output – DC AC/DC XUJ Compact High Performance Photoelectric Sensors FIG. 7 FIG. 6 FIG. 8 FIG. 9 1 Dark 2 Light 3 – NPN – or + + 4 + PNP 1 kΩ 5-Wire Relay, AC/DC AC/DC Microchange DC Connector 5 6 DC Output LOAD Test DC Output Microchange DC Connector ® www.epdatech.com 87 Photoelectric Sensors and Security Light Barriers XUE, XUR, XUD, XUG and XUE S XUE Long Range Plug-In Photoelectric Sensors FIG. 1 FIG. 2 FIG. 3 XUE A DC Emitter XUE H, NPN FIG. 5 FIG. 4 FIG. 6 XUE F XUE H, PNP XUE T XUR Color Registration Photoelectric Sensors FIG. 8 FIG. 7 PNP NPN XUD Amplifiers FIG. 9 XUG Amplifiers FIG. 10 BN PNP H + OG BK BU FIG. 11 Light Mode: Connect to + BN Dark Mode: Connect to – NPN J + BK – OG – BU Light Mode: Connect to + Dark Mode: Connect to – XUD J XUD H for XUF N Plastic Fiber Optics – DC models XUE S Security Light Barriers FIG. 12 FIG. 13 5 6 T1 T2 Open to test A1 L1 A2 L2 Emitter 3 4 1 L1 2 L2 Receiver ® 88 www.epdatech.com Photoelectric Sensors XUV XUV Photoelectric Sensors w/ Separate Optical Heads FIG. 1 + H Grey Test W J + LOAD BU W Gating Sensor BN BK H FIG. 2 PNP Synchro LOAD BK BU LOAD + – Grey Synchro – NPN – LOAD Test J PNP Output FIG. 3 BN Gating Sensor NPN Output 1 CHANNEL AMPLIFIER Terminals 13 15 17 19 A Potentiometers 2 4 6-8 13 15 17 19 TERMINALS L1 Supply L2 Supply Relay output (1 contact) Receiver (white wire) Receiver shielded cable Emitter shield Emitter (red wire) 1 2 A 1 2 3 SWITCHES Light/Dark Monostable timer (pulse stretcher) POTENTIOMETERS Sensitivity adjustment LED INDICATORS Green: power supply Red: unstable Yellow: output Switches 1 LED indicators 2 4 2 1 2 3 6 8 Terminals 2 CHANNEL AMPLIFIER – FORM C RELAY 10 12 14 16 18 20 Terminals 9 11 13 15 17 19 A Potentiometers B Switches 2 1 23 4 3 4 2 4 6 8 1 3 5 7 1 LED indicators 5 Terminals 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 TERMINALS L1 Supply L2 Supply NC output, Channel 2 NC output, Channel 1 Common, Channel 2 Common, Channel 1 NO output, Channel 2 NO output, Channel 1 12 VDC output for synchro sensors 12 VDC output for synchro sensors Synchronization, Channel 2, NPN Synchronization, Channel 1, NPN Emitter shield, Channel 1 Receiver, Channel 1 (white wire) Emitter, Channel 1 (red wire) Receiver shield, Channel 1 Emitter shield, Channel 2 Receiver, Channel 2 (white wire) Emitter, Channel 2 (red wire) Receiver shield, Channel 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 TERMINALS L1 Supply L2 Supply Output test (1 contact relay) Output test (1 contact relay) Channel 1 output (1 contact relay) Channel 1 output (1 contact relay) Channel 2 output (1 contact relay) Channel 2 output (1 contact relay) 12 VDC output for synchro sensors 12 VDC output for synchro sensors Synchronization, Channel 2, NPN Synchronization, Channel 1, NPN Emitter shield, Channel 1 Receiver, Channel 1 (white wire) Emitter, Channel 1 (red wire) Receiver shield, Channel 1 Emitter shield, Channel 2 Receiver, Channel 2 (white wire) Emitter, Channel 2 (red wire) Receiver shield, Channel 2 1 2 3 4 A B 1 2 3 4 5 SWITCHES Monostable timer (pulse stretcher), Channel 1 Light/Dark, Channel 1 Monostable timer (pulse stretcher), Channel 2 Light/Dark, Channel 2 POTENTIOMETERS Sensitivity adjustment, Channel 1 Sensitivity adjustment, Channel 2 LED INDICATORS Green: power supply Red: unstable, Channel 1 Yellow: output, Channel 1 Red: unstable, Channel 2 Yellow: output, Channel 2 2 CHANNEL LOGIC MODULE 10 12 14 16 18 20 Terminals 9 11 13 15 17 19 LED indicators 5 6 Potentiometers A 7 8 9 10 B C Switches 1 23 4 5 67 8 1 2 3 4 LED indicators 2 4 6 8 1 3 5 7 Terminals SWITCHES Time delay, Channel 1 (0.05 to 3 s or 1 to 60 s) Time delay, Channel 1 (On/Off) Time delay mode (mono. or adjustable time delay) Leading/Trailing edge selection Logic function (And/Or) Logic function (On/Off) Light/Dark, Channel 1 Light/Dark, Channel 2 POTENTIOMETERS A Time delay, Channel 1 B Sensitivity adjustment, Channel 1 C Sensitivity adjustment, Channel 2 LED INDICATORS 1 Green: power supply 2 Red: output test 3 Yellow: output, Channel 1 4 Yellow: output, Channel 2 5 Green: synchronization, Channel 1 6 Yellow: detection, Channel 1 7 Red: unstable, Channel 1 8 Green: synchronization, Channel 2 9 Yellow: detection, Channel 2 10 Red: unstable, Channel 2 1 2 3 4 5 6 7 8 AC Wiring Diagrams ® www.epdatech.com 89 Limit Switches Class 9007 Contact Forms for Class 9007 Limit Switches FIG. 1 Limit Switches: Class 9007 Type C FIG. 2 FIG. 3 Types C52, C54 1-Pole FIG. 4 Type C62 2-Pole, Same Polarity Each Pole Type C66 2-Pole, 2-Stage, Same Polarity Each Pole FIG. 5 FIG. 6 [1] On CR switches, terminals 1-4 on left side are for CW rotation and terminals 5-8 on right side are for CCW rotation. Types C68T5, C68T10, CR67T5 [1] and CR67T10 [1] 2-Pole Neutral Position, Same Polarity Each Pole Type C Reeds Limit Switches: Class 9007 Type XA FIG. 8 FIG. 7 Type XA73 Reeds Type XA75 Reeds ® 90 www.epdatech.com For more books join our telegram group Click here to join https://t.me/engubook Limit Switches Class 9007 Limit Switches: Class 9007 Type AW FIG. 2 FIG. 1 Type AW12 and AW14 Type AW18 FIG. 3 FIG. 4 [1] FIG. 5 [1] If lever arm is placed at same end of box as conduit, N.O. contacts become N.C. and vice versa. Type AW16 w/ Lever Arm Opposite Conduit Hole [1] FIG. 6 If lever arm is placed at same end of box as conduit, N.O. contacts become N.C. and vice versa. Type AW19 w/ Lever Arm Opposite Conduit Hole [1] FIG. 7 Type AW32, AW34, AW42 and AW44 FIG. 8 Type AW36 and AW46 Type AW38 and AW48 Type AW39 and AW49 Limit Switches: Class 9007 Type SG – GATE GARDTM Switch FIG. 9 FIG. 10 Type SGS1DK Type SGP1 ® www.epdatech.com 91 Limit Switches and Safety Interlocks XCK and MS XCK Limit Switches FIG. 1 FIG. 2 SPDT, 1 N.O. and 1 N.C. Positive Opening, Snap Action FIG. 3 2 SPDT, 2 N.O. and 2 N.C. SPDT, Isolated N.O. and N.C. Positive Opening, Slow-Make Slow-Break XCK Safety Interlocks FIG. 4 FIG. 5 13 21 FIG. 6 LED 24 VDC AC 24 VDC 21 13 22 14 L1 21 13 14 22 14 Orange LOAD No polarity SPDT, Positive Opening, Slow-Make Slow-Break X3 X1 22 X3 Orange LOAD X2 Green X1 0V SPDT, w/ 24 VDC LED, Positive Opening, Slow-Make Slow-Break AC Note: N.O. and N.C. contacts are shown with key inserted and fully engaged. L2 SPDT, w/ 2 Pilot Lights, Positive Opening, Slow-Make Slow-Break Contact Blocks for XY2CE Limit Switches FIG. 7 21 13 FIG. 8 21 11 FIG. 9 11 FIG. 10 13 FIG. 11 X1 X1 X2 22 Zb 14 XEN P2151, Isolated N.C. and N.O. 22 12 Zb 12 XEN P2141, Isolated N.C. and N.O. X2 Za 14 XEN P2051, N.C./N.O., 12 and 14 same polarity Indicator Light, Direct Indicator Light w/ Resistance MS Miniature Limit Switches FIG. 12 FIG. 13 White Black Green Black Orange Red Red SPST White Green SPDT ® 92 www.epdatech.com Pressure Switches and Transducers Class 9012, 9013, 9022 and 9025 Pressure and Temperature Switches: Class 9012 and 9025 Type G FIG. 1 FIG. 2 FIG. 3 Machine Tool, SPDT, 1 N.O. and 1 N.C. Machine Tool, DPDT, 2 N.O. and 2 N.C. FIG. 4 Industrial, SPST, 1 N.O. and 1 N.C. FIG. 5 Machine Tool, SPDT, 1 N.O. and 1 N.C. w/ Form H10 Machine Tool, SPDT, 1 N.O. and 1 N.C. w/ Form H11 Commercial Pressure Switches: Class 9013 Type CS FIG. 6 Acceptable Wiring Schematics Pressure Transducers: Class 9022 Type PTA and PTB FIG. 7 + – DC SUPPLY FIG. 8 Black DC SUPPLY TRANSDUCER White or Red Brown TRANSDUCER Red + LOAD – FIG. 9 + DC SUPPLY – TRANSDUCER 4 LOAD Black 2 1 3 LOAD Type PTA, 2-Wire FIG. 10 + Type PTA, 3-Wire – DC SUPPLY Green + Type PTA, 4-Wire DC SUPPLY – TRANSDUCER TRANSDUCER Red FIG. 11 LOAD A B FIG. 12 + DC SUPPLY – TRANSDUCER LOAD C Red Green Black White LOAD Type PTB, 2-Wire Type PTB, 3-Wire Type PTB, 4-Wire ® www.epdatech.com 93 Level Sensors and Electric Alternators Class 9034 and 9039 Level Sensors: Class 9034 Types LSD and LSV FIG. 1 Wiring Diagram Elementary Diagram Output selection of both sensors in maximum (N.C. when absent). Both devices at max. setting. Fill Cycle, Tank Full FIG. 2 Wiring Diagram Elementary Diagram Output selection of both sensors in minimum (N.O. when absent). Both devices at min. setting. Drain Cycle, Tank Empty Electric Alternators: Class 9039 Type X FIG. 3 Set pilot device A contacts to close before pilot device B contacts. Connections shown are for common control. If motor line voltage is different from voltage rating stamped on alternator coil terminals, alternator must be connected to motor lines thru control transformers. Control circuit conductors require overcurrent protection in accordance with applicable electrical codes. * Overlapping contact. FPO 69-1 ® 94 www.epdatech.com Pneumatic Timing Relays Class 9050 Pneumatic Timing Relays: Class 9050: Type AO FIG. 1 FIG. 2 Type AO10E FIG. 3 Type AO10D FIG. 7 FIG. 8 Type AO11E Type AO20E FIG. 9 Type AO11D FIG. 13 FIG. 14 Type AO12E FIG. 20 Type AO210DE Type AO20D Type AO21E FIG. 21 Type AO21D FIG. 22 FIG. 25 Type AO111DE Type AO121DE FIG. 18 Type AO112DE Type AO122DE FIG. 24 Type AO221DE Type AO222DE Pneumatic Timing Relays: Class 9050: Types B and C FIG. 26 FIG. 27 FIG. 28 Off Delay Type HO10E, On Delay Type AO120DE FIG. 12 FIG. 23 Type AO220DE Pneumatic Timing Relays: Class 9050: Type HO Type AO110DE FIG. 17 Type AO22D Type AO212DE FIG. 6 FIG. 11 FIG. 16 Type AO22E Type AO211DE FIG. 5 FIG. 10 FIG. 15 Type AO12D FIG. 19 FIG. 4 Type HO10D, Off Delay On Delay Type B Off Delay On Delay Type C ® www.epdatech.com 95 Pneumatic Timing Relays and Solid State Industrial Timing Relays Class 9050 Class 9050 Pneumatic Timing Relays: Typical Elementary Diagrams FIG. 1 FIG. 2 Interval, Momentary Start FIG. 3 On Delay Interval, Maintained Start FIG. 4 FIG. 5 Off Delay Repeat Cycle Solid State Industrial Timing Relays: Class 9050 Types FS and FSR FIG. 6 FIG. 7 L1 L2 AC Supply Voltage FPO 71-1 L1 L2 C1 Timed Contacts C2 C3 Instantaneous C5 Contacts (optional) P1 C6 C7 C4 C8 External Initiating Contact Elementary Diagram Wiring Diagram Solid State Industrial Timing Relays: Class 9050 Type FT FIG. 8 FIG. 9 L1 L2 AC Supply Voltage FPO 71-2 C1 C3 C5 C7 L1 L2 Instantaneous Contacts (optional) P C2 C4 Timed Contacts C6 C8 External Initiating Contact Elementary Diagram Wiring Diagram ® 96 www.epdatech.com Timers Class 9050 Solid State Industrial Timing Relays: Class 9050 Type JCK FIG. 1 FIG. 2 FIG. 3 External Initiating Contact 4 External Initiating Contact (used in one-shot and off-delay mode only) 6 5 5 3 6 7 8 4 6 5 7 7 2 3 1 8 + 9 – 1 11 + – Control Power Polarity markings are for DC units only. JCK 60 is AC only. 8 3 9 10 2 Control Power 4 1 Terminals 5 and 10 are internally jumpered. Applying power to terminal 7 or jumpering from terminal 5 to 7 through an external contact initiates the timer. Type JCK 11-19, 31-39 and 51-60 10 2 Polarity markings are for DC units only. 11 Control Power Type JCK 21-29 and 41-49 Type JCK 70 Solid State Timers: Class 9050 Type D FIG. 4 FIG. 5 A1/+ 15 25 FIG. 6 A1 15 25 A1/+ 15 25 Z1 Z2 16 18 26 28 A2/– A1 15 25 Z1 Z2 16 18 26 28 A2 16 18 26 28 A2/– Vs Vs Vs Type DER, DZM, DTR, DWE, DEW and DBR FIG. 7 Type DERP, DERLP, DWEP and DZMP 16 18 26 28 A2 Vs Type DAR Type DARP Solid State Timers: Class 9050 Type M FIG. 8 FIG. 9 17 25 A1 15 18 26 A2 16 18 A2 Vs Type MAN, MBR, MER, MEW, MTG, MWE and MZM A1 Vs Type MAR ® www.epdatech.com 97 Transformer Disconnects Class 9070 Transformer Disconnects: Class 9070 Note: Some factory modifications, depending on enclosure and transformer VA size selected, are not available. Consult factory modification chart. FIG. 1 L1 L2 FIG. 2 GND L3 L1 L2 GND L3 OFF OFF ON ON F U 1 F U 2 F U 1 460 V H1 F U 2 460 V 230 V H3 H2 H4 H1 H3 H2 H4 H1 H3 230 V H2 H1 H4 Optional Connection F U 5 X1A F U 4 R R Power On F U 3 X2B X2A F U 5 F U 4 X2A Optional For Size 1 Enclosures except w/ Form E23 L1 F U 6 X1A Optional FIG. 3 L2 For Size 1 Enclosures w/ Form E23 FIG. 4 GND L3 L1 L2 GND L3 OFF OFF ON F U 1 ON F U 2 F U 1 H3 F U 2 230 V 460 V H1 H2 H4 H1 H3 230 V 460 V H2 H4 H1 H3 H2 H4 Optional Connection F U 5 X1A F U 4 R R Power On F U 3 X2B X2A H3 H2 H4 Electrostatically Shielded Transformer X1 115 V X2 Power On X1B H1 Optional Connection X1 115 V X2 F U 3 H4 Electrostatically Shielded Transformer X1 115 V X2 Power On X1B H2 Optional Connection X1 115 V X2 F U 3 H3 X1A F U 7 F U 5 X1B F U 6 F U 8 X2B F U 4 X2A Optional Optional For Size 2 Enclosures except w/ Form E23 For Size 2 Enclosures w/ Form E23 ® 98 www.epdatech.com Enclosure Selection Guide Table 6 Enclosures for Non-Hazardous Locations Provides Protection Against NEMA NEMA NEMA NEMA NEMA NEMA Type 5 Type 1 Type 3 [1] Type 3R [1] Type 4 [2] Type 4X [2] Type 12 [3] Type 12K NEMA Type 13 Accidental contact w/ enclosed equipment Yes Yes Yes Yes Yes Yes Yes Yes Yes Falling dirt Yes Yes Yes Yes Yes Yes Yes Yes Yes Falling liquids and light splashing … Yes Yes Yes Yes … Yes Yes Yes Dust, lint, fibers and flyings … … … Yes Yes Yes Yes Yes Yes Hosedown and splashing water … … … Yes Yes … … … … Oil and coolant seepage … … … … … … Yes Yes Yes Oil and coolant spraying and splashing … … … … … … … … Yes Corrosive agents … … … … Yes … … … … Rain, snow and sleet [4] … Yes Yes [5] Yes … … … … … [5] Yes Yes … … … Windblown dust [1] … Yes Intended for outdoor use. [2] Intended for indoor and outdoor use. [3] Square D Industrial Control design NEMA Type 12 enclosures may be field modified for outdoor applications. [4] External operating mechanisms are not required to be operable when the enclosure is ice covered. [5] Square D Industrial Control design NEMA Type 4 enclosures provide protection against these environments. Table 7 Enclosures for Hazardous Locations Enclosure Class [1] Group [1] 7B 7C 7D 9E 9F 9G Hydrogen, manufactured gas I B Yes … … … … … Ethyl ether, ethylene, cyclopropane I C Yes Yes … … … … Gasoline, hexane, naphtha, benzine, butane, propane, alcohol, acetone, benzol, natural gas, lacquer solvent I D Yes Yes Yes … … … Metal dust Il E … … … Yes … … Carbon black, coal dust, coke dust Il F … … … … Yes … Flour, starch, grain dust Il G … … … … Yes Yes Provides Protection Against [1] NEMA Type 7 NEMA Type 9 As described in Article 500 of the National Electrical Code. ® www.epdatech.com 99 Conductor Ampacity and Conduit Tables Based on 1993 National Electrical Code Ampacity Based on NEC® Table 310-16 — Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, Not More Than Three Conductors in Raceway or Cable. Based on 30 °C Ambient Temperature. Trade Size of Conduit or Tubing Based on NEC Chapter 9, Table 1 and Tables 3A, 3B, 3C, 4 and 5B. Refer to Chapter 9 for Maximum Number of Conductors in Trade Sizes of Conduit or Tubing. Dimensions of Insulated Conductors for Conduit Fill Determined from NEC Chapter 9 Tables 5 and 5A. For information on temperature ratings of terminations to equipment, see NEC Section 110-14c. Underlined conductor insulation types indicates ampacity is for WET locations. See NEC Table 310-13. Table 8 Conductor Ampacity based on NEC Table 310-16 ALUMINUM CONDUCTORS THWN, XHHW Conduit Conduit Conduit Conduit 3W 3W 4W [2] 4W [2] THHN, XHHW Conduit Conduit 3W 4W [2] Wire Size AWG kcmil Table 310-16 Ampacity Insulated Copper THHW, THW, RW, USE 90 °C (194 °F) Conductor Insulation [1] Table 310-16 Ampacity Insulated Copper Wire Size AWG kcmil Table 310-16 Ampacity Insulated Copper 75 °C (167 °F) Conductor Insulation [1] 75 °C (167 °F) Conductor Insulation [1] 90 °C (194 °F) Conductor Insulation [1] THHW, THW, USE Table 310-16 Ampacity Insulated Copper COPPER CONDUCTORS XHHW Conduit Conduit Conduit Conduit 3W 3W 4W [2] 4W [2] THHN, XHHW Conduit Conduit 3W 4W [2] †14 20 … … 1/2 1/2 25 1/2 1/2 … … … … … … … … … †12 25 … … 1/2 1/2 30 1/2 1/2 †12 20 … … 1/2 1/2 25 1/2 1/2 †10 35 … … 1/2 1/2 40 1/2 1/2 †10 30 … … 1/2 1/2 35 1/2 1/2 8 50 3/4 1 1/2 [3] 3/4 55 1/2 [3] 3/4 8 40 3/4 3/4 1/2 3/4 45 1/2 3/4 3/4 [4] 3/4 [4] 6 65 1 1 3/4 75 3/4 6 50 3/4 1 3/4 3/4 60 3/4 3/4 4 85 1 1-1/4 1 1 95 1 1 4 65 1 1 3/4 1 75 3/4 1 3 100 1-1/4 1-1/4 1 1-1/4 110 1 1-1/4 3 75 … … … … 85 … … 2 115 1-1/4 1-1/4 1 1-1/4 130 1 1-1/4 2 90 1 1-1/4 1 1-1/4 100 1 1-1/4 1 130 1-1/4 1-1/2 1-1/4 1-1/2 150 1-1/4 1-1/2 1 100 1-1/4 1-1/2 1-1/4 1-1/2 115 1-1/4 1-1/2 1/0 150 1-1/2 2 1-1/4 1-1/2 170 1-1/4 1-1/2 1/0 120 1-1/4 1-1/2 1-1/4 1-1/2 135 1-1/4 1-1/2 2/0 175 1-1/2 2 1-1/2 2 195 1-1/2 2 2/0 135 1-1/2 2 1-1/4 1-1/2 150 1-1/4 1-1/2 3/0 200 2 2 1-1/2 2 225 1-1/2 2 3/0 155 1-1/2 2 1-1/2 2 175 1-1/2 2 4/0 230 2 2-1/2 2 2 260 2 2 4/0 180 2 2 1-1 /2 2 205 1-1/2 2 250 255 2-1/2 2-1/2 2 2-1/2 290 2 2-1/2 250 205 2 2-1/2 2 2 230 2 2 300 285 2-1/2 3 2 2-1/2 320 2 2-1/2 300 230 2 2-1/2 2 2-1/2 255 2 2-1/2 350 310 2-1/2 3 2-1/2 3 350 2-1/2 3 350 250 2-1/2 3 2-1/2 3 280 2-1/2 3 305 2-1/2 2-1/2 [5] 3 350 2-1/2 3 400 335 3 3 2-1/2 3 380 2-1/2 3 400 270 2-1/2 3 2-1/2 500 380 3 3-1/2 3 3 430 3 3 500 310 3 3 2-1/2 600 420 3 3-1/2 3 3-1/2 475 3 3-1/2 600 340 3 3-1/2 3 3 385 3 3 700 460 3-1/2 4 3 3-1/2 520 3 3-1/2 700 375 3 3-1/2 3 3-1/2 420 3 3-1/2 750 475 3-1/2 4 3-1/2 4 535 3-1/2 4 750 385 3 3-1/2 3 3-1/2 435 3 3-1/2 800 490 3-1/2 4 3-1/2 4 555 3-1/2 4 800 395 … … … … 450 … … 900 520 4 5 3-1/2 4 585 3-1/2 4 900 425 … … … … 480 … … 1000 545 4 5 3-1/2 5 615 3-1/2 5 1000 445 3-1/2 4 3-1/2 4 500 3-1/2 4 [1] [2] Unless otherwise permitted in the Code, the overcurrent protection for conductor types marked with an with an obelisk (†) shall not exceed 15 A for No. 14, 20 A for No. 12 and 30 A for No. 10 copper, or 15 A for No. 12 and 25 A for No. 10 aluminum after any correction factors for ambient temperature and number of conductors have been applied.. [3] 2-1/2 [5] #8 XHHW copper wire requires 3/4" conduit for 3W. [4] #6 XHHW copper wire requires 1" conduit for 3Ø4W. [5] 400 kcmil aluminum wire requires 3" conduit for 3Ø4W. On a 4-wire, 3-phase wye circuit where the major portion of the load consists of nonlinear loads such as electric discharge lighting, electronic computer/data processing, or similar equipment there are harmonic currents present in the neutral conductor and the neutral shall be considered to be a current-carrying conductor. NEC is a Registered Trademark of the National Fire Protection Association. ® 100 www.epdatech.com Conductor Ampacity and Conduit Tables Based on 1993 National Electrical Code Ampacity Correction Factors: For ambient temperatures other than 30 °C (86 °F), multiply the ampacities listed in Table 8 by the appropriate factor listed in Table 9. Adjustment Factors: Where the number of current-carrying conductors in a raceway or cable exceeds three, reduce the allowable ampacities as shown in Table 9. Table 9 Ampacity Correction Factors Ambient Temperature (°C) 75 °C (167 °F) Conductors 90 °C (194 °F) Conductors Table 10 Adjustment Factors Ambient Temperature (°F) No. of Current-Carrying Inductors Values in Tables as Adjusted for Ambient Temperature 4-6 80% 21-25 1.05 1.04 70-77 26-30 1.00 1.00 78-86 7-9 70% 31-35 .94 .96 87-95 10-20 50% 36-40 .88 .91 96-104 21-30 45% 41-45 .82 .87 105-113 31-40 40% 46-50 .75 .82 114-122 41 and above 35% 51-55 .67 .76 123-131 56-60 .58 .71 132-140 61-70 .33 .58 141-158 71-80 … .41 159-176 For exceptions, see exceptions to Note 8 of NEC® Table 310-16. Ratings for 120/240 V, 3-Wire, Single-Phase Dwelling Services: The ratings in Table 11 are permitted ratings for dwelling unit service and feeder conductors which carry the total load of the dwelling. The grounded conductor (neutral) shall be permitted to be not more than 2 AWG sizes smaller than the ungrounded conductors, provided the requirements of 215-2, 220-22 and 230-42 are met. Table 11 Ratings for 120/240 V, 3-Wire, Single-Phase Dwelling Services – see NEC 310-16 Note 3 Rating (A) 100 110 125 150 175 200 225 250 300 350 400 Copper 4 AWG 3 AWG 2 AWG 1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 350 kcmil 400 kcmil Aluminum 2 AWG 1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil 350 kcmil 500 kcmil 600 kcmil NEC 240-3 Protection of Conductors: Conductors, other than flexible cords and fixture wires, shall be protected against overcurrent in accordance with their ampacities as specified in NEC Section 310-15, unless otherwise permitted in parts (a) through (m). NEC 220-3 (a) Continuous and Noncontinuous Loads: The branch circuit rating shall not be less than the noncontinuous load plus 125% of the continuous load (see exception for 100% rated devices). NEC 220-10 (b) Continuous and Noncontinuous Loads: Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall not be less than the noncontinuous load plus 125% of the continuous load (see exception for 100% rated devices). NEC 430-22 (a) Single Motor Circuit Conductors: Branch circuit conductors supplying a single motor shall have an ampacity not less than 125% of the motor full-load current rating (see exceptions). NEC is a Registered Trademark of the National Fire Protection Association. ® www.epdatech.com 101 Wire Data Table 12 AWG Size Conductor dia. (mm) 29 Conductor dia. (in) Resistance @ 20 °C (68 °F) Ohm per ft .08180 .2684 .01240 .06743 .2212 .01264 .06491 .2130 .01398 .05309 .1742 .01420 .05143 .1687 .01575 .04182 .1372 .01594 .04082 .1339 .01772 .03304 .1084 .01790 .03237 .1062 .01969 .02676 .08781 .02010 .02567 .08781 .02205 .02134 .07000 .02257 .02036 .06679 .02480 .01686 .05531 .02535 .01614 .05531 .02795 .01280 .04201 .02846 .01280 .04201 .750 .02953 .01190 .03903 .800 .03150 .01045 .03430 .315 .355 27 .400 26 .450 25 .500 24 .560 23 .630 22 .710 21 20 AWG Size Ohm per m .01126 28 13 Conductor dia. (mm) Conductor dia. (in) Resistance @ 20 °C (68 °F) Ohm per ft Ohm per m 1.900 .07480 .001853 .006081 2.000 .07874 .001673 .005488 .08081 .001588 .005210 2.120 .08346 .001489 .004884 2.240 .08819 .001333 .004375 12 11 .09074 .001260 .004132 2.360 .09291 .001201 .003941 2.500 .09843 .001071 .003512 .1019 .0009988 .003277 2.650 .1043 .0009528 .003126 2.800 .1102 .0008534 .002800 10 9 .1144 .0007924 .002500 3.000 .1181 .0007434 .002439 3.150 .1240 .0006743 .002212 .1285 .0006281 .002061 3.350 .1319 .0005662 .001956 3.550 .1398 .0005309 .001742 8 7 .1443 .0004981 .001634 3.750 .1476 .0004758 .001561 4.000 .1575 .0004182 .001372 .1620 .0003952 .001296 .03196 .01015 .03331 .850 .03346 .009261 .05038 .900 .03543 .008260 .02642 4.250 .1673 .0003704 .001215 .03589 .008051 .02642 4.500 .1772 .0003304 .001084 .950 .03740 .007414 .02432 1.000 .03937 .006991 .02195 19 18 .04030 .006386 .02095 1.060 .04173 .005955 .01954 1.120 .04409 .005334 .01750 .04526 .005063 .01661 1.180 .04646 .004805 .01577 1.250 .04921 .004282 .01405 17 16 .05082 .004016 .01317 1.320 .05197 .003840 .01260 1.400 .05512 .004016 .01317 .05707 .003414 .01045 1.500 .05906 .002974 .009756 1.600 .06299 .002526 .008286 15 14 13 AWG and Metric Wire Data 6 5 .1819 .0003134 .001028 4.750 .1870 .0002966 .0009729 5.000 .1968 .0002676 .0008781 .2043 .0002485 .0008152 .2205 .0002134 .0007000 .2294 .0001971 .0006466 .2480 .0001686 .0005531 .2576 .0001563 0005128 .2795 .0001327 .0004355 .2893 .0001239 .0004065 .3150 .0001045 .0003430 .3249 .00009825 .0003223 .3543 .00008260 .0002710 .3648 .00007793 .0002557 .3937 .00006691 .0002195 .4096 .00006182 .0002195 .4600 .00004901 .0001608 .4646 .00004805 .0001577 4 5.600 3 6.300 2 7.100 1 8.000 0 9.000 2/0 .06408 .002315 .007596 1.700 .06693 .002315 .007596 3/0 10.000 1.800 .07087 .002065 .006775 4/0 .07196 .002003 .006571 11.800 ® 102 www.epdatech.com Electrical Formulas Table 13 Electrical formulas for Amperes, Horsepower, Kilowatts and KVA Single phase 3-phase Direct current I x E x PF 1000 I x E x 1.73 x PF 1000 IxF 1000 IxE 1000 I x E x 1.73 1000 — I x E x % Eff x PF 746 I x E x 1.73 x %Eff x PF 746 I x E x %Eff 746 HP x 746 E x %Eff x PF HP x 746 1.73 x E x %Eff x PF HP x 746 E x %Eff Amperes when Kilowatts is known KW x 1000 E x PF KW x 1000 1.73 x E x PF KW x 1000 E Amperes KVA x 1000 E KVA x 1000 1.73 x E — To find Kilowatts KVA Horsepower (output) Amperes when Horsepower is known E=Volts l = Amperes %Eff = Percent efficiency PF = Power factor HP = Horsepower KVA = Kilovolt-Amps Average Efficiency and Power Factor Values of Motors: When actual efficiencies and power factors of the motors to be controlled are not known, the following approximations may be used: Efficiencies: DC motors, 35 hp and less: DC motors, above 35 hp: Synchronous motors (at 100% PF): 80% to 85% 85% to 90% 92% to 95% “Apparent” efficiencies (Efficiency x PF): 3-phase induction motors, 25 hp and less: 3-phase induction motors above 25 hp: Decrease these figures slightly for single phase induction motors. Table 14 Ratings for 3-Phase, Single-Speed, Full-Voltage Magnetic Controllers for Nonplugglng and Nonjogging Duty Continous Current Rating (A) Size of Controller [1] 70% 80% Horsepower at [1] 60 Hz 200 V 60 Hz 230 V 50 Hz 380 V 60 Hz 460 or 575 V Service-Limit Current Rating (A) 00 9 1-1/2 1-1/2 1-1/2 2 11 0 18 3 3 5 5 21 1 27 7-1/2 7-1/2 10 10 32 2 45 10 15 25 25 52 3 90 25 30 50 50 104 4 135 40 50 75 100 156 5 270 75 100 150 200 311 6 540 150 200 300 400 621 7 810 — 300 — 600 932 These horsepower ratings are based on typical locked-rotor current ratings. For motors having higher locked-rotor currents, use a larger controller to ensure its locked-rotor current rating is not exceeded. ® www.epdatech.com 103 Electrical Formulas Table 15 Ratings for 3-Phase, Single-Speed, Full-Voltage Magnetic Controllers for Plug-Stop, Plug-Reverse or Jogging Duty [1] Horsepower at [1] Continous Current Rating (A) Size of Controller 60 Hz 200 V 60 Hz 230 V 50 Hz 380 V 1-1/2 1-1/2 1-1/2 0 18 1 27 3 3 2 45 7-1/2 10 3 90 15 20 4 135 25 30 5 270 60 6 540 125 60 Hz 460 or 575 V Service-Limit Current Rating (A) 2 21 5 5 32 15 15 52 30 30 104 50 60 156 75 125 150 311 150 250 300 621 These horsepower ratings are based on typical locked-rotor current ratings. For motors having higher locked-rotor currents, use a larger controller to ensure its locked-rotor current rating is not exceeded. Table 16 Power Conversions From to kW to PS to hp to ft-lb/s 1 kW (kilowatt) = 1010 erg/s 1 1.360 1.341 737.6 1 PS (metric horsepower) 0.7355 1 0.9863 542.5 1 hp (horsepower) 0.7457 1.014 1 1 ft-lb/s (foot-pound per sec) 1.356 x 10-3 1.843 x 10-3 1.818 x 550.0 10-3 1 ® 104 www.epdatech.com From single products to complete systems, look to Square D. Square D Company is a leading manufacturer and supplier of electrical distribution, automation and industrial control products. The full line of Square D and Telemecanique brand products are available from an extensive network of Square D distributors located throughout North America. Square D Company is part of Groupe Schneider, an $11 billion global manufacturer of electrical distribution, automation and industrial equipment, a company whose primary business resides in those markets. Square D has been serving industrial and construction markets, as well as public utilities, individual consumers and government agencies for over 85 years. We offer unsurpassed quality, innovative design and a committed staff of trained sales representatives and service technicians willing to stand behind every product we sell. For further information on how we can help fill your electrical needs, call your local Square D field representative or authorized Square D distributor. Square D Company Automation and Control Business P.O. Box 27446, Raleigh, N.C. 27611, USA Square D Canada 6675 Rexwood Road Mississauga, Ontario L4V 1V1 Square D Company Mexico, SA de C.V. Calz. Javier Rojo Gomez No. 1121 Col. Guadalupe del Moral, Iztapalapa 09300 Mexico D.F., Mexico 0140CT9201 (Supersedes SM304R10) Printed in USA © 1993 Square D All Rights Reserved www.epdatech.com