Uploaded by Sal Sham

MEP

advertisement
ELECTRICAL SPECIFICATION
ELECTRICAL SYMBOLS
EXIT LIGHTING FIXTURE ON EMERGENCY CIRCUITRY ARROWS AS
B.
C.
D.
E.
4.
F.
G.
H.
GENERAL
1.
THE ENTIRE ELECTRICAL INSTALLATION SHALL CONFORM TO THE
LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND LOCAL
JURISDICTION REQUIREMENTS.
K.
SHOP DRAWINGS
1.
PROVIDE SHOP DRAWINGS FOR THE FOLLOWING ITEMS: LIGHTING
FIXTURES, OCCUPANCY SENSORS , RECEPTACLES AND FIRE ALARM DEVICES
EQUIPMENT AND DEFINITIONS
1.
ALL ELECTRICAL EQUIPMENT SHALL BEAR THE UNDERWRITER’S
LABORATORIES LABEL.
2.
UNLESS SPECIFICALLY NOTED ON THE PLANS ALL CIRCUITRY,
EQUIPMENT, DEVICES, ETC., NOT NOTED EXISTING TO REMAIN OR TO BE
RELOCATED SHALL BE NEW.
L.
JUNCTION BOXES LABELING REQUIREMENTS
1. ALL JUNCTION BOXES FOR BRANCH CIRCUITRY SHALL BE CLEARLY LABELED
WITH PANEL DESIGNATION AND CIRCUIT NUMBERS.
PANELBOARDS
1.
PROVIDE A TYPED CIRCUIT DIRECTORY FOR THE ENTIRE PANELBOARD
REVISED UNDER THIS CONTRACT.
2.
CONTRACTOR SHALL PHASE BALANCE ALL PANELBOARDS AS
NECESSARY.
3.
THE BRANCH CIRCUITS SHOWN FOR ITEMS SERVED AS INDICATED.
CONTRACTOR SHALL FIELD COORDINATE ALL BRANCH CIRCUITS
ACCORDINGLY.
BRANCH CIRCUITRY SHOWN ON FLOOR PLAN CONNECTED TO A DESIGNATED
CIRCUIT EXACT POSITION OF CIRCUIT BREAKER SHALL BE AFTER REMOVAL OF
OUTLETS UNDER DEMOLITION. CONTRACTOR SHALL UTILIZE ALL C/B’S
BECOMING SPARE
CIRCUIT BREAKERS
1. ALL NEW CIRCUIT BREAKERS TO BE INSTALLED IN NEW PANELS SHALL BE
BOLT-ON TYPE.
SWITCHES, RECEPTACLES, TELEPHONE OUTLETS AND DATA OUTLETS
1.
WHERE TWO OR MORE DEVICES OF THE SAME VOLTAGE ARE SHOWN
M.
TOGETHER ON THE PLANS, A GANGED PLATE SHALL BE USED. DEVICES OF
DIFFERENT VOLTAGES SHALL BE SEPARATED HORIZONTALLY BY 6” BUT SHALL
BE HORIZONTALLY OR VERTICALLY ALIGNED.
2.
ALL RECEPTACLES, TELEPHONE, AND DATA OUTLETS SHOWN ON A WALL
BACK TO BACK SHALL BE OFFSET A MINIMUM OF 6" HORIZONTALLY.
LIGHTING FIXTURES
1.
COORDINATE ALL LIGHTING FIXTURES WITH SPRINKLERS, MECHANICAL N.
EQUIPMENT AND ARCHITECTURAL CEILING PLAN TO AVOID CONFLICT. GRID
LAYOUT ON PLANS IS APPROXIMATE, ADJUST AND COORDINATE LIGHTING
FIXTURES IN FIELD PER ARCHITECTS REFLECTED CEILING PLAN.
2.
PROVIDE FINISHED FRAMES FOR ALL RECESSED LIGHTING FIXTURES,
TYPE TO BE COORDINATE ALL FIXTURE TYPES WITH CEILING SYSTEM BEFORE
ORDERING FIXTURES. PROVIDE ALL MOUNTING ATTACHMENTS FOR A
O.
COMPLETE INSTALLATION. LIGHTING FIXTURES SHALL BE SUPPORTED PER
LOCAL CODE REQUIREMENTS.
3.
ALL NEW LIGHTING FIXTURES SHALL BE INSTALLED COMPLETE WITH
P.
LAMPS. SEE LIGHTING FIXTURE SCHEDULE FOR LAMPS AND TYPE OF
BALLASTS REQUIREMENTS AND/OR PLANS.
4.
COLOR OF LIGHTING FIXTURES SHALL BE AS SELECTED BY THE
ARCHITECT.
I. BRANCH CIRCUITRY AND FEEDER
1.
ALL CONDUCTORS SHALL BE COPPER.
2.
ALL BRANCH CIRCUITRY AND FEEDER SHALL COMPLY WITH THE UTEST
NATIONAL ELECTRICAL CODE (N.E.C.) LOCAL JURISDICTION AND LOCAL STATE
CODE REQUIREMENTS. THE FOLLOWING ARE SOME ACCEPTABLE WIRING
METHOD REQUIREMENTS.
J. INDOOR USE BRANCH CIRCUITRY
1.
METAL CLAD CABLE (MC CABLE) IS PERMITTED TO SERVE
RECEPTACLES/LIGHTING AND OTHER EQUIPMENT LOAD. METAL CLAD CABLE
MC IS PERMITTED TO RUN CONCEALED AREA SUCH AS CEILING SPACE AND
FINISHED WALL AREA ONLY. CONTRACTOR SHALL FOLLOW ELECTRICAL
SYMBOLS LIST ALL HOMERUN BRANCH CIRCUITRY FOR THE INDOOR
EQUIPMENT SHALL BE INSTALLED IN EMT
GENERAL NOTES IN REGARDS TO BRANCH CIRCUITRY AND FEEDER
1.
USE OF ALUMINUM CONDUIT SHALL NOT BE PERMITTED.
2.
ALL BRANCH CIRCUITRY AND FEEDERS SHALL BE RUN CONCEALED.
3.
ALL CIRCUITRY RUNS ARE DIAGRAMMATIC. THE CONTRACTOR SHALL
DETERMINE IN FIELD THE MOST SUITABLE ROUTES.
4.
MINIMUM SIZE EMT OR CONDUIT SHALL BE 3/4’’. UNLESS MULTIPLE
HOMERUN CIRCUITS REQUIRES URGER SIZE CONDUIT.
5.
NO NONMETALLIC CONDUIT SHALL BE USED FOR BRANCH CIRCUIT
WORK ABOVE GRADE
WIRE AND CABLE
1.
FEEDERS: FEEDER SHALL BE ALUMINUM . INSULATION SHALL BE THW
OR THHN/THWN.
2.
COLOR CODE: ALL WIRING SHALL BE COLOR CODED THROUGHOUT AS
PER N.E.C. REQUIREMENTS.
3.
ALL CONDUCTORS SHALL BE COPPER, MINIMUM #2 AWG.
4.
ALL RECEPTACLES, LIGHTING FIXTURES, MOTORS, ETC.. SHALL BE
GROUNDED PER N.E.C. ALL RECEPTACLE CIRCUITS SHALL CONTAIN A #12
INSULATED GROUND CONDUCTORS
5.
RUN MULTIPLE HOMERUNS TO ALTERNATELY NUMBERED PANELBOARD
CIRCUITS (I.E., 1,3,5) SERVING LIGHTING, GENERAL RECEPTACLES, AND
MOTORS. ANY CIRCUITS SERVING, ISOLATED GROUND RECEPTACLES OR
RECEPTACLES SERVING COMPUTER EQUIPMENT, WHEN THE CONTRACTOR
RUN CIRCUITRY IN MULTIPLE HOMERUNS. CONTRACTOR SHALL OVERSIZE THE
NEUTRAL CONDUCTOR TO A MINIMUM 200% OF THE CAPACITY OF PHASE
CONDUCTORS SIZE THE EMT/CONDUIT ACCORDINGLY WHERE NECESSARY.
6.
ALL EMPTY RACEWAYS SHALL CONTAIN A DRAG WIRE. EMPTY
RACEWAYS 2” OR LARGER IN SIZE SHALL HAVE A MAXIMUM OR 2 - 90 DEGREES
BENDS PER RUN. WHERE REQUIRED, PROVIDE PULL BOXES PER N.E.C.
REQUIREMENTS.
7.
FINAL CONNECTION TO ALL MOTORS OR VIBRATING EQUIPMENT SHALL
BE WITH FLEXIBLE CONDUIT OR LIQUID-TIGHT FLEXIBLE CONDUIT FOR
OUTDOOR.
8.
ALL 120 VOLT CIRCUIT HOMERUNS WHICH ARE OVER 100 LINEAR FEET
SHALL BE A MINIMUM OF #10 CONDUCTORS OR AS SHOWN ON THE PLANS.
9.
EXPOSED AND CONCEALED CIRCUITRY SHALL BE RUN TIGHT TO CEILING
SLAB IN A NEAT WORKMANLIKE MANNER. ALL RUNS SHALL BE PARALLEL OR
PERPENDICULAR TO BUILDING WALL.
GROUNDING
1.
PROVIDE GROUND TO ALL DEVICES PER N.E.C. REQUIREMENTS.
2.
PROVIDE SERVICE GROUND CONDUCTORS SIZE PER NEC
REQUIREMENTS.
3.
PROVIDE EQUIPMENT GROUND CONDUCTORS SIZE PER NEC
REQUIREMENTS.
FIRE SEALANT MATERIALS
1.
ANY PENETRATION TO THE FIRE WALLS. CONTRACTOR SHALL PROVIDE
FIRE SEALANT MATERIALS AT EVERY POINT WHERE OCCURRED. FIRE
SEALANT MATERIALS MANUFACTURER SHALL BE SUBMITTED TO THE
ARCHITECT FOR APPROVAL PRIOR TO APPLICATION.
REQUIREMENTS - SEE SCHEDULE
PANELBOARD - SEE SCHEDULE. MOUNTING HEIGHT TO CENTERLINE
ST
ABOVE FINISHED FLOOR 6' - 0 " TO TOP.
GROUNDED (HUBBELL #5362). COLOR OF DEVICE AND FACE PLATE
IF NO NOTED.
SHALL BE AS SELECTED BY THE ARCHITECT. MOUNTING HEIGHT
TO
DISCONNECT SWITCH - SEE DRAWING FOR VOLTAGE, POLES AND
CENTERLINE ABOVE FINISHED FLOOR 18” UON.
AMPERAGE RATING.
WALL MOUNTED DOUBLE DUPLEX RECEPTACLE - 2P, 3W, 20A,
HOMERUN TO PANELBOARD. NUMBER OF ARROWHEADS INDICATE
A-1
125V,
NUMBER OF
GROUNDED (HUBBELL #5362). COLOR OF DEVICE AND FACE PLATE
CIRCUITS. NUMERALS AND LETTERS ADJACENT TO ARROWHEADS
SHALL BE AS SELECTED BY THE ARCHITECT. MOUNTING HEIGHT
INDICATE
TO CENTERLINE ABOVE FINISHED FLOOR 18” UON.
ASSIGNED PANEL AND CIRCUIT NUMBERS. SEE PANEL SCHEDULE
FOR AMPERAGE
2-HEAD BATTERY LIGHTING UNIT
RATING OF EACH CIRCUIT BREAKER AND CONDUCTOR SIZES
CIRCUITRY INSTALLED CONCEALED IN WALL OR ABOVE CEILING.
J
J
NUMBER
OF TICKS INDICATE NUMBER OF CONDUCTORS. IF NO TICKS MARK
INDICATE 2
MOTOR RATED SWITCH WITH THERMAL OVERLOAD
WALL MOUNTED DUPLEX RECEPTACLE - 2P, 3W, 20A, 125V,
MOTOR CONNECTION - HORSEPOWER AS INDICATED, FRACTIONAL
JUNCTION BOX - CEILING OR WALL MOUNTED
SINGLE POLE SWITCH - ARROW HART #1991. COLOR OF
S
(TWO) CONDUCTORS IN RACEWAY. SEE PANEL SCHEDULE FOR
DEVICE AND FACE PLATE SHALL BE WHITE.
MOUNTING HEIGHT TO CENTERLINE ABOVE FINISHED
FLOOR 4' - 0".
CONDUCTOR SIZES.
THREE WAY SWITCH . COLOR OF DEVICE AND FACE SHALL BE
SM
OCCUPANCY SENSOR FOR THE SMALL INDIVIDUAL OFFICE, +48”
SET @ LESS THAN 15 MINUTES WATTSTOPPER CAT# DW-100
COLOR TO BE SELECTED BY THE ARCHITECT.
OC
S3
A.F.F. MOTION SENSOR SHALL BE AS MANUF. BY WATTSTOPPER
WITH TIME DELAY SHALL BE
WORK SCHEDULE
1.
COORDINATE WITH ARCHITECT AND/OR OWNER’S REPRESENTATIVE FOR
WORK SCHEDULE REQUIREMENTS
FINAL TESTING
1.
AT THE TIME OF FINAL INSPECTION AND TEST, ALL CONNECTIONS AND
TERMINATIONS AT PANELBOARDS, DEVICES, EQUIPMENT, AS WELL ALL
SPLICES MUST BE ALL COMPLETED. EACH BRANCH CIRCUIT AND ITS
RESPECTIVE CONNECTED EQUIPMENT MUST TEST FREE OF SHORT CIRCUIT
COMPLETION OF THE WORK, CLEAN AND POLISH ALL EXPOSED SURFACES IN
ACCORDANCE WITH THE MANUFACTURER’S RECOMMENDATIONS.
INDICATED. FIXTURES TO COMPLY WITH LOCAL JURISDICTION
ELECTRICAL SYMBOLS
OCCUPANCY SENSOR, CEILING MOUNTED AS MANUF. BY
WATTSTOPPER.
SD
WHITE
MOUNTING HEIGHT TO CENTERLINE ABOVE FINISHED FLOOR 4' - 0"
SMOKE DETECTOR
3985 GEORGIA ST,
SAN DIEGO, CA 92103
A.
SPECIAL OUTLET. COORDINATE EXACT NEMA CONFIGURATIONS
OF OUTLET WITH OWNER’S REPRESENTATIVE AND EXACT
MOUNTING HEIGHT PRIOR TO ROUGH-IN.
SWITCH BANK
DL
DAYLIGHT SENSOR
ABBREVIATIONS
A
AMPERE
AFF
ABOVE FINISHED FLOOR
AIC
AMPERES INTERRUPTING CAPACITY C CONDUIT/EMT
C/B
CIRCUIT BREAKER
EC
EMPTY CONDUIT/EMT. PROVIDE PULL WIRE
EMT ELECTRICAL METALLIC TUBING
G
HP
GROUND
HORSEPOWER
MCB
MAIN CIRCUIT BREAKER
MTD
MOUNTED
NIC
NOT IN CONTRACT
KW
KILOWATTS
P
PNL
POLE
PANEL
R
RECESSED
LF
LINEAR FEET
S
UON
SURFACE
UNLESS OTHERWISE NOTED
V
VOLT
W
WIRE
MTD
DATE
DESCRIPTION
ISSUE:
PROJECT NO:
CAD FILE:
DATE:
MOUNTED
OC
ON CEILING
EG
EQUIPMENT GROUND
IG
ISOLATED GROUND
FACP
MARK
FIRE ALARM CONTROL PANEL
DRAWN BY:
Sal Sham
CHECKED BY:
COPYRIGHT:
SHEET TITLE:
ELECTRICAL NOTES
DRAWING SHEET NO:
E000
NOTES:
A- 6
WP
A- 6
D
A- 6
A-6
WP
PANEL A
WP
A- 6
A-6
C - 15,17
A-6
1. NEWLY INSTALLED, REPLACED, OR RELOCATED RECEPTACLES SHALL BE TAMPER-RESISTANT (TR).
ALL RECEPTACLES SHALL BE GFCI PROTECTED AND TAMPER-RESISTANT (TR). IF ANY NEW/ADDITIONAL OUTLETS ARE INSTALLED, THE BATHROOM SHALL HAVE A DEDICATED 20-AMP CIRCUIT.
2. EXHAUST FANS WITH A MINIMUM VENTILATION RATE OF 50 CFM ARE REQUIRED IN ALL BATHROOMS, EVEN IF AN OPERABLE WINDOW IS INSTALLED. EXHAUST FANS AND LIGHTING SHALL
HAVE SEPARATE CONTROL SWITCHES (EVEN IF A COMBINATION UNIT IS INSTALLED). THE EXHAUST FAN MAY NEED TO BE SUPPLIED BY A GFCI PROTECTED CIRCUIT BASED ON THE
MANUFACTURER’S REQUIREMENTS.
3. LIGHTING FIXTURES LOCATED WITHIN 3 FEET HORIZONTALLY AND 8 FEET VERTICALLY OF THE BATHTUB RIM OR SHOWER STALL THRESHOLD SHALL BE LISTED FOR A DAMP LOCATION, OR
LISTED FOR WET LOCATIONS WHERE SUBJECT TO SHOWER SPRAY.
4. EACH BATHROOM SHALL HAVE ONE LIGHT FIXTURE CONTROLLED BY A VACANCY SENSOR SWITCH THAT REQUIRES A MANUAL ON ACTIVATION (DOES NOT AUTOMATICALLY TURN ON) AND
AUTOMATICALLY TURNS OFF WITHIN 30 MINUTES AFTER THE ROOM IS VACATED. ALL OTHER LIGHT FIXTURES SHALL BE CONTROLLED BY A VACANCY SENSOR OR DIMMER
5. GFCI PROTECTION SHALL BE PROVIDED FOR ALL COUNTERTOP RECEPTACLES, RECEPTACLES WITHIN 6 FEET OF A SINK (INCLUDING BELOW COUNTER AND BEHIND AN APPLIANCE), AND FOR
RECEPTACLES SUPPLYING DISHWASHERS. THE RESET BUTTON FOR GFCI RECEPTACLES SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION (I.E. NOT BEHIND AN APPLIANCE).
6. COUNTERTOP RECEPTACLES SHALL BE LOCATED SO THAT NO POINT ALONG THE WALL IS MORE THAN 24 INCHES FROM A RECEPTACLE.
7. COUNTERTOP RECEPTACLES SHALL BE LOCATED NO MORE THAN 20 INCHES ABOVE THE COUNTERTOP.
8. ISLANDS/PENINSULAS SHALL HAVE AT LEAST ONE RECEPTACLE MOUNTED NOT MORE THAN 12 INCHES BELOW THE COUNTERTOP AND WHERE THE COUNTERTOP DOES NOT EXTEND MORE
THAN 6 INCHES BEYOND ITS BASE.
9. ELECTRIC STOVES AND OVENS SHALL BE SUPPLIED WITH A 40- OR 50- AMP BRANCH CIRCUIT.
10. COUNTERTOP RECEPTACLES SHALL BE SUPPLIED BY A MINIMUM OF TWO 20-AMP BRANCH CIRCUITS.
11. A DEDICATED CIRCUIT IS REQUIRED FOR CORD AND PLUG CONNECTED RANGE EXHAUST HOODS. SEPARATE CIRCUITS MAY BE REQUIRED FOR THE GARBAGE DISPOSAL, DISHWASHER, AND
BUILT-IN MICROWAVE BASED ON THE MANUFACTURER’S REQUIREMENTS AND THE MOTOR RATING.
12. DINING AREA, BREAKFAST ROOM, PANTRY, OR SIMILAR AREA SHALL BE SUPPLIED BY A 20-AMP CIRCUIT, THE COUNTERTOP CIRCUITS MAY BE USED TO SUPPLY THESE AREAS.
13.ALL LIGHTING FIXTURES SHALL BE CONTROLLED BY EITHER A DIMMER SWITCH OR BY A VACANCY SENSOR SWITCH THAT REQUIRES A MANUAL ON ACTIVATION (DOES NOT AUTOMATICALLY
TURN ON) AND AUTOMATICALLY TURNS OFF WITHIN 30 MINUTES AFTER THE ROOM IS VACATED.
14. ALL LIGHT FIXTURES SHALL CONTAIN BULBS THAT ARE LABELED AS JA8-2016 (JA8-2016-E FOR SEALED LENS OR RECESSED FIXTURE). SCREW BASE BULBS ARE PERMITTED, EXCEPT IN
RECESSED LIGHTING FIXTURES.
15. RECESSED LIGHTING SHALL BE LISTED AS IC (ZERO CLEARANCE TO INSULATION) AND AT (AIR TIGHT), BE SEALED/CAULKED BETWEEN THE FIXTURE HOUSING AND CEILING, SHALL NOT
CONTAIN A SCREW BASE SOCKET, AND CONTAIN BULBS MARKED WITH JA8-2016-E EFFICIENCY LABEL.
16. ALL OUTDOOR LIGHTING SHALL BE CONTROLLED BY A MANUAL ON AND OFF SWITCH AND BE CONTROLLED BY PHOTOCELL AND MOTION SENSOR
A-6
UTILIT
A- 6
A- 6
D - 15,17
GFCI
GFCI
GFCI
GFCI
D- 13
C- 13
B- 13
A- 17
3985 GEORGIA ST,
SAN DIEGO, CA 92103
B - 15,17
GROUND FLOOR POWER PLAN
1/4" = 1'-0"
GROUND BAR
B- 18
NEUTRAL BAR
WP
GFCI
B- 7
B- 8
B- 7
TV
B- 6
B- 6
CLOSET
BATH
B- 8
BEDROOM
CONNECT AS REQUIRED
GFCI
BY CODE
LIVING
B- 18
FLOOR CONCRETE SLAB
WP
B- 7
#3/0 GROUNDING
CONDUCTOR
B- 7
TV
WP
B- 6
GROUNDING
B- 18
B- 6
BONDING JUMPER
CLAMPS
MAIN DISTRIBUTION PANEL
B- 6
PANEL B
WATER PIPE
DINING
GFCI
B- 7
B- 8
BATH
#3/0 GROUNDING CONDUCTOR
TV
B- 8
B- 2
KITCHEN
B- 3
B- 6
B- 7
B- 7
CLOSET
GROUNDING ROD
PROJECT NO:
B- 6
DESCRIPTION
CAD FILE:
DATE:
DRAWN BY:
B- 5
Sal Sham
CHECKED BY:
REF.
B- 1
GFCI
COPYRIGHT:
6'-0" OR
SHEET TITLE:
MORE
GROUND & 1ST FLOOR
POWER PLANS
1ST FLOOR POWER PLAN
1/4" = 1'-0"
DATE
ISSUE:
B- 4
B- 12
MARK
GROUNDING CLAMP
TV
B- 7
GFCI GFCIGFCI
GFCI
DW
BEDROOM
GFCI GFCI
WP
B- 18
GROUNDING DETAIL
NOT TO SCALE
DRAWING SHEET NO:
E001
A - 19
D
CEILING FAN WITH LAMP
C- 16
A- 10
A- 5
WP
A- 5
LED SURFACE MNT. DISC LIGHT
(2.7K-5K 16 W)
(WET LISTED AT SHOWERS)
D- 16
EXTERIOR LISTED LED WALL SCONCE
(WAC LIGHTING RUBIX WALL LIGHT)
B- 16
EXHAUSTER FAN
WP A- 5
SECURITY CAMERA
A- 10
UTILIT
3985 GEORGIA ST,
SAN DIEGO, CA 92103
GROUND FLOOR LIGHTING PLAN
1/4" = 1'-0"
B- 9
B- 9
BEDROOM
BATH
CLOSET
B- 9
B- 9
B- 9
WALL FRAMING
LIVING
B- 9
B- 11
B- 11
B- 9
SD
CO
STAPLE EVERY 4.5 FEET
B- 14
B- 11
B- 14
CO
B- 14
SD
STAPLE NOT REQUIRED
WHERE CABLE RUN
THROUGH HOLES IN
FRAMING MEMBERS
STAPLE WITHIN 12
INCHES OF
ELECTRICAL BOX
B- 11
DINING
B- 11
STAPLE WHERE CABLE
CHANGED DIRECTION
B- 10
B- 10
B- 10
SD
B- 10
BATH
MARK
CO
BEDROOM
DATE
DESCRIPTION
ISSUE:
B- 10
B- 11
B- 10
PROJECT NO:
CAD FILE:
KITCHEN
ELECTRICAL BOX
ATTACHED TO STUD
DATE:
DRAWN BY:
B- 10
CABLE SUPPORT INSIDE WALL
REF.
1/2" = 1'-0"
Sal Sham
CHECKED BY:
COPYRIGHT:
SHEET TITLE:
GROUND & 1ST FLOOR
LIGHTING PLANS
1ST FLOOR LIGHTING PLAN
1/4" = 1'-0"
DRAWING SHEET NO:
E002
NOTES:
1. NEWLY INSTALLED, REPLACED, OR RELOCATED RECEPTACLES SHALL BE TAMPER-RESISTANT (TR).
ALL RECEPTACLES SHALL BE GFCI PROTECTED AND TAMPER-RESISTANT (TR). IF ANY NEW/ADDITIONAL OUTLETS ARE INSTALLED, THE BATHROOM SHALL HAVE A DEDICATED 20-AMP CIRCUIT.
2. EXHAUST FANS WITH A MINIMUM VENTILATION RATE OF 50 CFM ARE REQUIRED IN ALL BATHROOMS, EVEN IF AN OPERABLE WINDOW IS INSTALLED. EXHAUST FANS AND LIGHTING SHALL
HAVE SEPARATE CONTROL SWITCHES (EVEN IF A COMBINATION UNIT IS INSTALLED). THE EXHAUST FAN MAY NEED TO BE SUPPLIED BY A GFCI PROTECTED CIRCUIT BASED ON THE
MANUFACTURER’S REQUIREMENTS.
3. LIGHTING FIXTURES LOCATED WITHIN 3 FEET HORIZONTALLY AND 8 FEET VERTICALLY OF THE BATHTUB RIM OR SHOWER STALL THRESHOLD SHALL BE LISTED FOR A DAMP LOCATION, OR
LISTED FOR WET LOCATIONS WHERE SUBJECT TO SHOWER SPRAY.
4. EACH BATHROOM SHALL HAVE ONE LIGHT FIXTURE CONTROLLED BY A VACANCY SENSOR SWITCH THAT REQUIRES A MANUAL ON ACTIVATION (DOES NOT AUTOMATICALLY TURN ON) AND
AUTOMATICALLY TURNS OFF WITHIN 30 MINUTES AFTER THE ROOM IS VACATED. ALL OTHER LIGHT FIXTURES SHALL BE CONTROLLED BY A VACANCY SENSOR OR DIMMER
5. GFCI PROTECTION SHALL BE PROVIDED FOR ALL COUNTERTOP RECEPTACLES, RECEPTACLES WITHIN 6 FEET OF A SINK (INCLUDING BELOW COUNTER AND BEHIND AN APPLIANCE), AND FOR
RECEPTACLES SUPPLYING DISHWASHERS. THE RESET BUTTON FOR GFCI RECEPTACLES SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION (I.E. NOT BEHIND AN APPLIANCE).
6. COUNTERTOP RECEPTACLES SHALL BE LOCATED SO THAT NO POINT ALONG THE WALL IS MORE THAN 24 INCHES FROM A RECEPTACLE.
7. COUNTERTOP RECEPTACLES SHALL BE LOCATED NO MORE THAN 20 INCHES ABOVE THE COUNTERTOP.
8. ISLANDS/PENINSULAS SHALL HAVE AT LEAST ONE RECEPTACLE MOUNTED NOT MORE THAN 12 INCHES BELOW THE COUNTERTOP AND WHERE THE COUNTERTOP DOES NOT EXTEND MORE
THAN 6 INCHES BEYOND ITS BASE.
9. ELECTRIC STOVES AND OVENS SHALL BE SUPPLIED WITH A 40- OR 50- AMP BRANCH CIRCUIT.
10. COUNTERTOP RECEPTACLES SHALL BE SUPPLIED BY A MINIMUM OF TWO 20-AMP BRANCH CIRCUITS.
11. A DEDICATED CIRCUIT IS REQUIRED FOR CORD AND PLUG CONNECTED RANGE EXHAUST HOODS. SEPARATE CIRCUITS MAY BE REQUIRED FOR THE GARBAGE DISPOSAL, DISHWASHER, AND
BUILT-IN MICROWAVE BASED ON THE MANUFACTURER’S REQUIREMENTS AND THE MOTOR RATING.
12. DINING AREA, BREAKFAST ROOM, PANTRY, OR SIMILAR AREA SHALL BE SUPPLIED BY A 20-AMP CIRCUIT, THE COUNTERTOP CIRCUITS MAY BE USED TO SUPPLY THESE AREAS.
13.ALL LIGHTING FIXTURES SHALL BE CONTROLLED BY EITHER A DIMMER SWITCH OR BY A VACANCY SENSOR SWITCH THAT REQUIRES A MANUAL ON ACTIVATION (DOES NOT AUTOMATICALLY
TURN ON) AND AUTOMATICALLY TURNS OFF WITHIN 30 MINUTES AFTER THE ROOM IS VACATED.
14. ALL LIGHT FIXTURES SHALL CONTAIN BULBS THAT ARE LABELED AS JA8-2016 (JA8-2016-E FOR SEALED LENS OR RECESSED FIXTURE). SCREW BASE BULBS ARE PERMITTED, EXCEPT IN
RECESSED LIGHTING FIXTURES.
15. RECESSED LIGHTING SHALL BE LISTED AS IC (ZERO CLEARANCE TO INSULATION) AND AT (AIR TIGHT), BE SEALED/CAULKED BETWEEN THE FIXTURE HOUSING AND CEILING, SHALL NOT
CONTAIN A SCREW BASE SOCKET, AND CONTAIN BULBS MARKED WITH JA8-2016-E EFFICIENCY LABEL.
16. ALL OUTDOOR LIGHTING SHALL BE CONTROLLED BY A MANUAL ON AND OFF SWITCH AND BE CONTROLLED BY PHOTOCELL AND MOTION SENSOR
C- 18
WP
GFCI
C- 7
C- 7
TV
C- 6
C- 8
C- 6
CLOSET
BATH
C- 8
BEDROOM
GFCI
LIVING
WP
C- 18
C- 7
C- 7
C- 6
TV
WP
C- 6
C- 18
C- 6
C- 6
PANEL C
GFCI
DINING
C- 7
C- 8
BATH
KITCHEN
C- 6
C- 6
TV
C- 4
C- 5
C- 12
REF.
C- 1
GFCI
3985 GEORGIA ST,
SAN DIEGO, CA 92103
GFCI GFCI
GFCI
CLOSET
C- 7
DW
C- 7
GFCI
C- 3
C- 7
BEDROOM
C- 8
GFCI
TV
C- 2
GFCI
WP
C- 18
2ND FLOOR POWER PLAN
1/4" = 1'-0"
D- 18
WP
GFCI
D- 7
D- 8
D- 7
TV
D- 6
WP
D- 6
A - 19
A- 8
A- 8
WP
CLOSET
BATH
D- 8
WP
BEDROOM
WP
GFCI
A- 15
A- 8
LIVING
A - 19
D- 18
WP
D- 7
D- 7
D- 6
TV
WP
D- 6
D- 18
D- 6
D- 6
PANEL D
A- 16
GFCI
WP A- 18
DINING
D- 7
D- 8
WP
BATH
MARK
D- 18
BEDROOM
D- 8
GFCI
GFCI
D- 7
D- 2
DW
TV
GFCI
WP
D- 7
DATE
ISSUE:
KITCHEN
D- 6
D- 6
PROJECT NO:
A- 12,14
D- 3
A- 11,13
WP
TV
WP
CAD FILE:
DATE:
GFCI
D- 4
DRAWN BY:
D- 5
CLOSET
GFCI
GFCI
D- 7
D - 12
DESCRIPTION
REF.D- 1
GFCI
2' HEIGHT
A- 8
A- 8
WP
WP
Sal Sham
CHECKED BY:
COPYRIGHT:
SHEET TITLE:
3RD FLOOR POWER PLAN
ROOF POWER & LIGHTING PLAN
1/4" = 1'-0"
1/4" = 1'-0"
2ND & 3RD FLOOR POWER
PLANS
DRAWING SHEET NO:
E003
SOLAR SYSTEM AND RV
6.2 KW
A - 19
C- 9
INVERTER
5
5
TV
BEDROOM
5
3
5
C- 9
4
CLOSET
7
M
7
M
M
7
M
BATH
2
9
6
8
8
8
EXISTING
PANEL
PANEL A
PANEL B
PANEL C
PANEL D
C- 9
C- 9 C- 9
C- 9
C- 11
C- 11
LIVING
C- 9
CO
SD
TV
1
C- 14
GROUND FLOOR
C- 11
C- 14
CO
C- 14
SD
ELECTRICAL RISER DIAGRAM
NOT TO SCALE
C- 11
C- 11
FEEDER AND EQUIPMENT NOTES
C- 10
C- 10
DINING
C- 10
C- 10
BATH
SD
BEDROOM
1. INCOMING ELECTRICAL FROM POWER CO.
2. (N) MAIN SWITCH 800A 1PH.
3. COPPER FEEDERS 3 2-600 + 1 1/0 GND IN 2-3 1/2" CONDUIT.
4. (N) SOCKET METER 800A, 120/240V, 1PH.
5. COPPER FEEDERS 3 3/0 + 1 #6 GND IN 2" CONDUIT.
6. PANEL A 800A, 120/240 V, 1PH, 3 W - SEE PANEL SCHEDULE
7. (N) SOCKET METER 800A, 120/240V, 1PH.
8. PANEL B,C,D 100A, 120/240 V, 1PH, 3 W - SEE PANEL SCHEDULE
9. EXISTING PANEL IN THE OLD BUILDING
CO
C- 10
C- 11
C- 10
TV
A - 19
KITCHEN
TV
C- 10
THE FEEDER FROM PROPOSED BUILDING TO THE EXISTING BUILDING WILL BE
PASSING THROUGH A CONDUIT IN THE GROUND WITH 5" DIAMETER
REF.
CLOSET
3985 GEORGIA ST,
SAN DIEGO, CA 92103
WE HAVE TO MAKE A NEW PANEL FOR ADDITIONAL PV AND CONNECT IT TI THE
INVERTER, THE CONDUTE WILL BE USED FOR THIS CONNECTION
2ND FLOOR LIGHTING PLAN
1/4" = 1'-0"
D- 9
TV
BEDROOM
D- 9
CLOSET
BATH
D- 9
D- 9 D- 9
D- 9
D- 11
D- 11
D- 9
SD
PANEL TAG
PANEL LOCATION
VOLTAGE
PHASE
LIVING
CIRCUIT
TV
D- 11
D- 14
D- 14
SD
CO
D- 11
D- 11
D- 10
D- 10
BATH
1
3
5
7
9
11
13
15
17
19
21
23
DESCRIPTION
AIC 25K
MOUNTING Recessed
NEW/
EXIST.
PANEL B
-UTIL LIGHTING
PANEL D
-SPA
-FIRE PIT TABLE
WH
SECURITY CAMERA'S
LOAD BREAKER
TYPE
SIZE
HVAC; ...
100 A
--L
20 A
HVAC; ...
100 A
--R
50 A
--R
20 A
R
20 A
Lighting
20 A
POLES
Wire Size
A
2
-1
2
-2
-1
1
1
2-#1, 1-#1, 1-#8
-1-#12, 1-#12, 1-#12
2-#1, 1-#1, 1-#8
-2-#6, 1-#6, 1-#10
-1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
13.0
DINING
D- 10
D- 10
WIRE 3
RATED AMPS 800 A
MCB 800 A
CO
D- 14
A
TENANT STORAGE 128
120/240 Single
1
SD
BEDROOM
CONNECTED LOAD
CONNECTED AMPS
CO
D- 10
A
B
13.2
9.1
0.5
9.1
1.8
13.1
9.1
0.9
0.6
3.5
1.8
3.5
1.8
0.2
1.0
0.0
0.2
0.0
A
42.8
356.6
B
39.4
328.1
TOTAL
82.2
342.3 A
Wire Size
POLES
2-#1, 1-#1, 1-#8
-1-#10, 1-#10, 1-#10
1-#10, 1-#10, 1-#10
1-#12, 1-#12, 1-#12
2-#6, 1-#6, 1-#10
-1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
2
-1
1
1
2
-1
1
BREAKER LOAD
NEW/
SIZE
TYPE
EXIST.
100 A
HVAC; ...
--20 A
R
20 A
R
20 A
L
50 A
R
--20 A
L
20 A
R
DESCRIPTION
PANEL C
-GROUND LL RECEPTACLES
ROOF RECEPTACLES
OUTDOOR LIGHTING
SPA
-ROOF LIGHTING
HOT TUB RECEPTACLE
CIRCUIT
2
4
6
8
10
12
14
16
18
20
22
24
MARK
DATE
DESCRIPTION
ISSUE:
D- 11
DEMAND LOAD CALCULATION
D- 10
FACTOR
CONNECTE
D LOAD
DEMAND
LOAD
CONTINUOUS LOADS (C)
NON CONTINUOUS LOAD (NC)
TV
KITCHEN
TV
D- 10
REF.
CLOSET
3RD FLOOR LIGHTING PLAN
1/4" = 1'-0"
B
LIGHTING (L)
RECEPTACLES (R) - UNDER / OVER 10kVA
MOTOR LOADS (M)
KITCHEN (K)
WATER HEATER (WH)
SUB PANEL (SP)
DEMAND LOAD
DEMAND AMPS
PROJECT NO:
CAD FILE:
125%
59.05%
100%
7.3
55.2
0.6
9.1
32.6
0.6
DATE:
DRAWN BY:
Sal Sham
CHECKED BY:
COPYRIGHT:
61.3
255.6 A
SHEET TITLE:
2ND & 3RD FLOOR
LIGHTING PLANS
DRAWING SHEET NO:
E004
PANEL TAG
PANEL LOCATION
VOLTAGE
PHASE
B
BEDROOM 107
120/240 Single
1
WIRE 3
RATED AMPS 100 A
MCB 100 A
CIRCUIT
1
3
5
7
9
11
13
15
17
19
21
23
DESCRIPTION
AIC 25K
MOUNTING Recessed
NEW/
EXIST.
REFRIGERATOR
DISPOSAL
OVEN
BEDROOMS RECEPTACLES
BEDROOM & BATH LIGHTNG
KITCHEN/DINING LIGHTING
WH
CU-1
--
DEMAND LOAD CALCULATION
LOAD
TYPE
R
R
R
R
L; M
L
R
HVAC
--
BREAKER
SIZE
20 A
20 A
30 A
20 A
20 A
20 A
20 A
30 A
--
POLES
Wire Size
A
1
1
1
1
1
1
1
2
--
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#10, 1-#10, 1-#10
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
2-#10, 1-#10, 1-#10
--
0.8
3.2
CONNECTED LOAD
A
13.0
B
9.1
TOTAL
22.1
CONNECTED AMPS
108.2
75.8
92.0 A
POLES
Wire Size
A
B
1
1
1
1
1
1
1
2
--
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#10, 1-#10, 1-#10
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
2-#10, 1-#10, 1-#10
--
0.8
3.2
CONNECTED LOAD
CONNECTED AMPS
A
13.2
109.7
B
9.1
75.8
POLES
Wire Size
A
B
1
1
1
1
1
1
1
2
--
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#10, 1-#10, 1-#10
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
2-#10, 1-#10, 1-#10
--
0.8
3.2
CONNECTED LOAD
A
13.1
B
9.1
TOTAL
22.2
CONNECTED AMPS
108.8
75.8
92.3 A
FACTOR
CONNECTE
D LOAD
DEMAND
LOAD
125%
87.31%
100%
2.1
13.4
0.2
2.6
11.7
0.2
B
A
B
1.2
1.0
3.5
1.0
1.3
1.4
0.6
0.7
0.6
0.7
1.0
1.0
0.4
3.2
0.1
0.5
Wire Size
POLES
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1
1
1
1
1
1
1
1
1
Wire Size
POLES
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1
1
1
1
1
1
1
1
1
Wire Size
POLES
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12
1
1
1
1
1
1
1
1
1
BREAKER
SIZE
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
LOAD
TYPE
R
R
R
R
L; M
R
L
L
R
NEW/
EXIST.
BREAKER
SIZE
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
LOAD
TYPE
R
R
R
R
L; M
R
L
L
R
NEW/
EXIST.
BREAKER
SIZE
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
LOAD
TYPE
R
R
R
R
L; M
R
L
L
R
NEW/
EXIST.
DESCRIPTION
CIRCUIT
DISHWASHER
RANGE
KITCHEN/DINING RECEPTACLES
BATH RECEPTACLES
BEDROOM & BATH LIGHTING
MICROWAVE
OUTDOOR LIGHTING
TENANT STORAGE LIGHTING
OUTDOOR RECEPTACLES
2
4
6
8
10
12
14
16
18
20
22
24
DESCRIPTION
CIRCUIT
DISHWASHER
RANGE
KITCHEN/DINING RECEPTACLES
BATH RECEPTACLES
BEDROOM & BATH LIGHTING
MICROWAVE
OUTDOOR LIGHTING
TENANT STORAGE LIGHTING
OUTDOOR RECEPTACLES
2
4
6
8
10
12
14
16
18
20
22
24
DESCRIPTION
CIRCUIT
DISHWASHER
RANGE
KITCHEN/DINING RECEPTACLES
BATH RECEPTACLES
BEDROOM & BATH LIGHTING
MICROWAVE
OUTDOOR LIGHTING
TENANT STORAGE LIGHTING
OUTDOOR RECEPTACLES
2
4
6
8
10
12
14
16
18
20
22
24
CONTINUOUS LOADS (C)
NON CONTINUOUS LOAD (NC)
DEMAND LOAD
DEMAND AMPS
PANEL TAG
PANEL LOCATION
VOLTAGE
PHASE
RATED AMPS
MCB
CIRCUIT
1
3
5
7
9
11
13
15
17
19
21
23
20.9
87.1 A
C
BEDROOM 140
120/240 Single
1
100 A
100 A
DESCRIPTION
WIRE 3
AIC 25K
MOUNTING Recessed
NEW/
EXIST.
REFRIGERATOR
DISPOSAL
OVEN
BEDROOMS RECEPTACLES
BEDROOM & BATH LIGHTNG
KITCHEN/DINING LIGHTING
WH
CU-2
--
DEMAND LOAD CALCULATION
LOAD
TYPE
R
R
R
R
L; M
L
R
HVAC
--
BREAKER
SIZE
20 A
20 A
30 A
20 A
20 A
20 A
20 A
30 A
--
FACTOR
CONNECTE
D LOAD
DEMAND
LOAD
125%
86.82%
100%
2.1
13.6
0.2
2.6
11.8
0.2
A
B
1.2
1.0
3.5
1.0
1.4
1.4
0.6
0.7
0.6
0.7
1.0
1.0
0.4
3.2
0.1
0.5
3985 GEORGIA ST,
SAN DIEGO, CA 92103
LIGHTING (L)
RECEPTACLES (R) - UNDER / OVER 10kVA
MOTOR LOADS (M)
KITCHEN (K)
WATER HEATER (WH)
SUB PANEL (SP)
TOTAL
22.3
92.8 A
CONTINUOUS LOADS (C)
NON CONTINUOUS LOAD (NC)
LIGHTING (L)
RECEPTACLES (R) - UNDER / OVER 10kVA
MOTOR LOADS (M)
KITCHEN (K)
WATER HEATER (WH)
SUB PANEL (SP)
DEMAND LOAD
DEMAND AMPS
PANEL TAG
PANEL LOCATION
VOLTAGE
PHASE
21.0
87.4 A
D
BEDROOM 149
120/240 Single
1
WIRE 3
RATED AMPS 100 A
MCB 100 A
CIRCUIT
1
3
5
7
9
11
13
15
17
19
21
23
DESCRIPTION
AIC 25K
MOUNTING Recessed
NEW/
EXIST.
REFRIGERATOR
DISPOSAL
OVEN
BEDROOMS RECEPTACLES
BEDROOM & BATH LIGHTNG
KITCHEN/DINING LIGHTING
WH
CU-3
--
DEMAND LOAD CALCULATION
FACTOR
LOAD
TYPE
R
R
R
R
L; M
L
R
HVAC
--
BREAKER
SIZE
20 A
20 A
30 A
20 A
20 A
20 A
20 A
30 A
--
CONNECTE
D LOAD
DEMAND
LOAD
DEMAND LOAD
DEMAND AMPS
B
1.2
1.0
3.5
1.0
1.4
1.4
0.6
0.7
0.5
0.7
1.0
1.0
0.4
3.2
0.1
0.5
MARK
DATE
DESCRIPTION
ISSUE:
PROJECT NO:
CAD FILE:
DATE:
DRAWN BY:
Sal Sham
CHECKED BY:
CONTINUOUS LOADS (C)
NON CONTINUOUS LOAD (NC)
LIGHTING (L)
RECEPTACLES (R) - UNDER / OVER 10kVA
MOTOR LOADS (M)
KITCHEN (K)
WATER HEATER (WH)
SUB PANEL (SP)
A
COPYRIGHT:
125%
86.82%
100%
2.0
13.6
0.2
2.5
11.8
0.2
SHEET TITLE:
SCHEDULES
20.9
86.9 A
DRAWING SHEET NO:
E005
MECHANICAL GENERAL NOTES
1. GENERAL
1.1 THE MECHANICAL WORK SHALL CONFORM TO APPLICABLE STATE AND LOCAL CODES AND THE REQUIREMENTS OF THE
AUTHORITIES HAVING JURISDICTION.
1.2 THE CONTRACTOR SHALL MAKE ALL NECESSARY ARRANGEMENTS AND PAY FOR ALL PERMITS, FEES, CHARGES AND
INSPECTIONS REQUIRED, AS WELL AS HAULING, RIGGING AND TRANSPORTATION CHARGES APPLICABLE TO HIS WORK.
1.3 THE PROJECT SHALL BE BID ON THE BASIS OF SPECIFIED PRODUCT(S) WHICH ESTABLISH MINIMUM QUALITY REQUIREMENTS.
WHERE MORE THAN ONE PRODUCT NAME IS INDICATED, BIDS SHALL BE BASED ON ONE OF THE NAMED PRODUCTS. ALL
MECHANICAL EQUIPMENT SHOWN ON CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE ALL LISTED AND SHALL BE PROVIDED BY
THE MECHANICAL CONTRACTOR UNLESS OTHERWISE NOTED.
A). WHERE USE OF AN ’ACCEPTABLE EQUAL' PRODUCT REQUIRES CHANGES TO THE BASE DESIGN IN ORDER TO INCORPORATE THE
PRODUCT INTO THE PROJECT, THE CONTRACTOR SHALL SUBMIT A LAYOUT SHOWING ALL CHANGES TO ARCHITECTURAL.
STRUCTURAL, ELECTRICAL, PLUMBING AND MECHANICAL REQUIREMENTS. CHANGES DUE TO USE OF ’ACCEPTABLE EQUAL’
PRODUCTS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER AND THE COST OF CHANCES SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR LAYOUT SHALL ACCOMPANY PRODUCT SUBMITTAL DATA.
SYMBOLS
4.3 ALL NECESSARY ALLOWANCES AND PROVISIONS SHALL BE MADE BY CONTRACTOR FOR BEAMS. COLUMNS OR OTHER
OBSTRUCTIONS OF THE BUILDING OR THE WORK OF OTHER CONTRACTORS. WHETHER OR NOT SAME IS INDICATED. WHERE NECESSARY
TO AVOID OBSTRUCTIONS. THE DUCTS SHALL BE TRANSFORMED, DIVIDED OFFSET, RAISED OR LOWERED WITH THE REQUIRED FREE
AREA BEING MAINTAINED IN ACCORDANCE WITH SMACNA STANDARDS.
12X10
AHU
1
UNIT TAG TYPE
UNIT DESIGNATED NUMBER
AIR INTO
REGISTER/GRILLE
4.7 PROVIDE FIRE DAMPERS IN HVAC AIR DISTRIBUTION SYSTEMS THAT PENETRATE FIRE RATED ASSEMBLIES IN ACCORDANCE WITH
THE INTERNATIONAL BUILDING AND MECHANICAL CODES. FIRE DAMPERS SHALL BE TYPE B IN ALL DUCTWORK, IN ADDITION TO
SECONDARY FIRE DAMPERS FOR CEILING, WALL AND FLOOR MOUNTED AIR DEVICES.
AIR OUT OF
REGISTER/GRILLE
4.8 COORDINATE SPECIFIC FIRE RESISTIVE CONSTRUCTION REQUIREMENTS WITH THE FIRE RATED ASSEMBLIES INDICATED ON
ARCHITECTURAL DRAWINGS. THROUGH PENETRATIONS FIRESTOP SYSTEMS SHALL CONFORM TO UL LISTED FIRE RESISTANCE
DIRECTORY OR OTHER METHODS ACCEPTABLE TO LOCAL GOVERNING CODE AUTHORITIES.
4.10 PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE DETECTORS, FIRE DAMPERS. SMOKE DAMPERS,
VOLUME DAMPERS, COILS, AND OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/ OR INSPECTION. LABEL
ACCESS WITH 1/2" LETTERING.
CEILING MOUNTED
EXHAUST FAN
RECTANGULAR/SQUARE
DUCT TO ROUND DUCT SIZE
Transition
4.6 DUCTWORK SHALL BE SEALED WITH AN APPROVED DUCT MASTIC OR LIQUID SEALANT AS MANUFACTURED BY UNITED MCGILL
CORP., OR APPROVED EQUAL. DUCT SYSTEM LEAKAGE SHALL CONFORM TO SMACNA "HVAC DUCT LEAKAGE TEST MANUAL" FOR CLASS
2’ W.C. SEAL CLASS A, LEAKAGE CLASS 24 FOR RECTANGULAR DUCTS AND CLASS 12 FOR ROUND DUCTWORK.
C). WHERE ’OR EQUAL’ PRODUCTS ARE INDICATED. THE CONTRACTOR SHALL SUBMIT A LIST OF PROPOSED EQUAL SUBSTITUTE
PRODUCTS WITH THE BID. THE LIST SHALL INCLUDE ADEQUATE SUPPORTING INFORMATION AS PROOF OF EQUALITY IN ORDER TO
BE CONSIDERED ACCEPTABLE. NO LATER SUBSTITUTES WILL BE CONSIDERED.
DOUBLE LINE DUCT W/
SIZE IN INCHES
DUCT SIZE
TRANSITION
4.5 DUCTWORK SIZES SHOWN ARE NET CLEAR INSIDE DIMENSIONS. FOR INTERNALLY LINED DUCTS, FABRICATE SHEET METAL TO
ALLOW FOR THICKNESS OF INSULATION AND MAINTAIN NET CLEAR DIMENSIONS.
4.9 PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN AND EXHAUST) CONNECTED TO AIR HANDLING
UNITS, FANS AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE
POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.
EXISTING TO
NEW CONNECTION
12X8
4.4 ALL RECTANGULAR DUCTWORK ELBOWS 30 DEGREE OR GREATER SHALL BE PROVIDED WITH DOUBLE THICKNESS RADIUS TURNING
VANES.
B). SUBSTITUTIONS FOR ’ACCEPTABLE EQUAL’ PRODUCTS NOT SPECIFIED WILL BE CONSIDERED WHEN INCLUDED WITH
SUBMISSION OF THE BID AND SHALL BE SUBJECT TO ACCEPTANCE BY THE ENGINEER. PROPOSALS FOR SUBSTITUTIONS SHALL
INCLUDE, BUT NOT BE LIMITED TO: (1) ANY ADDED CREDIT OR COST. (2) PRODUCT IDENTIFICATION. (3) CODE COMPLIANCE. (4)
REFERENCED STANDARD COMPLIANCE. (5) DESCRIPTION OF ALL CHANGES INCLUDING ARCHITECTURAL, STRUCTURAL,
ELECTRICAL, PLUMBING AND MECHANICAL, REQUIRED TO INCORPORATE SUBSTITUTED PRODUCT INTO THE PROJECT. THE
OWNER/ENGINEER RESERVES THE RIGHT TO REJECT PROPOSED SUBSTITUTIONS.
NEW DUCT (1ST DIMENSION
INDICATES SIDE SHOWN, INSIDE
CLEAR DIMENSIONS)
FLEXIBLE DUCT
CONNECTOR
T
THERMOSTAT
S
SWITCH
SD
DUCT SMOKE DETECTOR
U
DOOR UNDERCUT
2’X2‘ SUPPLY DIFFUSER
MANUAL VOLUME
DAMPER
2’X2' RETURN GRILLE
BACKDRAFT DAMPER
5. INSULATION
1.4 THE CONTRACTOR SHALL VERIFY FIELD CONDITIONS FOR POINTS OF CONNECTIONS, CAPACITIES, AND LOCATIONS OF
SYSTEMS. IN ALL AREAS AFFECTED BY THE PROJECT, CUT, PATCH, REPAIR, AND/OR REPLACE ALL MATERIALS DAMAGED AS A
RESULT OF WORK. ALL REPAIRED FINISHES SHALL MATCH APPROPRIATE ADJACENT FINISHES. FILL VOIDS AROUND DUCTWORK
PENETRATING WALLS WITH FIRE STOPPING MATERIAL.
5.1 INSULATION MATERIALS SHALL BE CERTAIN-TEED OR APPROVED EQUAL INSULATION MATERIALS SHALL HAVE A FLAME SPREAD
RATING NOT MORE THAN 25 AND A SMOKE DEVELOPED RATING OF NOT MORE THAN 50. PROVIDE IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS AND AS FOLLOWS:
1.6 THE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF WORK INCLUDED IN THE PROJECT. DO
NOT SCALE THE DRAWING. THE CONTRACTOR SHALL ESTABLISH FINAL DIMENSIONS FROM FIELD MEASUREMENTS, PRIOR TO
STARTING WORK.
1.7 MECHANICAL WORK SHALL BE COORDINATED WITH THE WORK OF ALL OTHER TRADES PRIOR TO INSTALLATION, TO AVOID
CONFLICTS AND ALLOCATE SPACE REQUIREMENTS.
1.8 MATERIALS SHALL BE RATES FOR THE OPERATING TEMPERATURE AND PRESSURE OF THE HYDRONIC SYSTEM. MATERIALS
SHALL BE SUITABLE FOR THE TYPE OF FLUID IN THE HYDRONIC SYSTEM.
1.9 PROJECT PREMISES SHALL BE THOROUGHLY CLEANED AND READY FOR OCCUPANCY INCLUDING ALL FINISHES OF EQUIPMENT
PROVIDED AS PART OF THE CONTRACTOR'S WORK. PROVIDE ONE NEW SET OF CLEAN AIR FILTERS FOR ALL AIR MOVING
EQUIPMENT AT PROJECT CLOSEOUT.
1.10 THE WORD ’PROVIDE’ AS USED IN THE PROJECT SHALL BE DEFINED AS ’"FURNISH AND INSTALL"
1. SUPPLY/RETURN AIR DUCTWORK (CONCEALED): INSULATE WITH NOMINAL 1-INCH THICK TYPE 75 STANDARD DUCTWRAP WITH FSK
FACING VAPOR BARRIER. MINIMUM 3/4-INCH INSTALLED THICKNESS WITH A 5.6 R VALUE.
SUPPLY DUCT TO DROP
DOWN
2. SUPPLY/RETURN AIR DUCTWORK (INTERIOR EXPOSED WHERE INDICATED): INSULATE WITH 1-INCH THICK TYPE 200 ULTRA-LITE
ACOUSTICAL DUCT LINER WITH 100 PERCENT ADHESIVE COVERAGE AND MECHANICAL FASTENERS. MINIMUM INSTALLED R VALUE OF
3.1.
RETURN DUCT TO RISE
UP
3. SUPPLY/RETURN AIR DUCTS (CONCEALED IN ATTIC/CRAWL/ROOF CEILING SPACE): INSULATE WITH NOMINAL 3-INCH THICK TYPE 75
STANDARD DUCTWRAP WITH FSK FACING, VAPOR BARRIER. MINIMUM 2-1/4-INCH INSTALLED THICKNESS WITH 8.5 R VALUE.
RETURN DUCT TO DROP
DOWN
4. SUPPLY/RETURN/EXHAUST/OUTSIDE AIR DUCTS (OA DUCTWORK & DUCTWORK EXPOSED TO WEATHER CONDITIONS): INSULATE
DUCTWORK EXTERIOR WITH SEMI-RIGID FIBERGLASS BOARD INSULATION, TYPE 1B300, 3.0 LBS/CU. FT. DENSITY, MINIMUM 2-INCH
INSTALLED THICKNESS WITH 8.5 R VALUE. PROVIDE WEATHERPROOF FINISH AS MANUFACTURED BY FOSTERS MONOLAR 60 -95
COATINGS (MINIMUM OF 3 COATS) OR APPROVED EQUAL.
ELBOW WITH TURNING
VANES
5. PROVIDE ALL NECESSARY FOUNDATIONS, SUPPORTS, PADS AND BASES AS REQUIRED FOR MECHANICAL EQUIPMENT, PIPING, AND
DUCTWORK AS PER INTERNATIONAL BUILDING AND MECHANICAL CODES. INSTALL EQUIPMENT, PIPING, AND DUCTWORK SO AS TO BE
FREE FROM OBJECTIONABLE NOISE AND VIBRATIONS. CONTRACTOR SHALL COORDINATE WORK WITH STRUCTURAL AND
ARCHITECTURAL DRAWINGS PRIOR TO ACTUAL WORK.
SUPPLY AIR
DEVICE
RETURN OR EXHAUST AIR
DEVICE
7. ELECTRICAL WORK
2.2 MATERIALS SHALL BE RATED FOR THE OPERATING TEMPERATURE AND PRESSURE OF DOMESTIC SYSTEM. MATERIALS SHALL
BE SUITABLE FOR THE TYPE OF FLUID IN THE DOMESTIC SYSTEM.
2.3 PIPE SUPPORTS SHALL BE SELECTED AND INSTALLED IN ACCORDANCE WITH THE MSS SP-69 OR LOCAL CODES, WHICHEVER IS
MORE STRINGENT. UTILIZE TRAPEZE HANGERS FOR PARALLEL RUNS OR PIPING, OTHER THAN SPRINKLER AND WASTE PIPING.
COPPER PIPING SYSTEMS SHALL BE SUPPORTED ON COPPER OR COPPER-PLATED SUPPORTS. HANG PIPE FROM SUBSTANTIAL
BUILDING STRUCTURE. PIPING SHALL NOT BE HUNG FROM OTHER PIPING, ALL RIGID HANGERS SHALL PROVIDED A MEANS OF
VERTICAL ADJUSTMENT AFTER ERECTION. SHIELD SHALL BE PROVIDED BETWEEN HANGERS AND INSULATION.
2.4 WELDING SHALL CONFORM TO CURRENT STANDARDS AND RECOMMENDATIONS OF THE NATIONAL CERTIFIED PIPE WELDING
BUREAU, NFPA 51B, STANDARD FOR FIRE PROTECTION; AND NFPA 241,STANDARD FOR SAFEGUARDING CONSTRUCTION,
ALTERATION, AND DEMOLITION OPERATIONS.
3. EQUIPMENT
3.1 ALL MECHANICAL EQUIPMENT SHOWN ON CONTRACT DOCUMENTS SHALL BE NEW, AND SHALL BE PROVIDED BY THE
MECHANICAL CONTRACTOR UNLESS OTHERWISE NOTED.
3.2 EQUIPMENT AND PRODUCT MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS FOR INSTALLATION AND OPERATION
SHALL BE FOLLOWED IN PERFORMING MECHANICAL WORK, UNLESS OTHERWISE INDICATED OR DIRECTED. MATERIALS AND
METHODS USED IN THE WORK SHALL BE COMPATIBLE WITH BUILDING CONDITIONS AND COMPLY WITH THE BUILDING CODE
REQUIREMENTS, WHICH SHALL BE THE BASIS FOR MINIMUM PRODUCT QUALITY. ALL WORK SHALL BE PERFORMED IN A NEAT AND
WORKMANLIKE MANNER BY SKILLED WORKMEN EXPERIENCED IN THEIR TRADE. THE WORK SHALL BE SUBJECT TO THE
ACCEPTANCE OF THE OWNER OR THE DULY AUTHORIZED REPRESENTATIVE.
4. DUCTWORK
4.1 DUCTWORK SHALL BE FABRICATED OF GALVANIZED SHEET METAL WITH CONSTRUCTION AND INSTALLATION IN ACCORDANCE
WITH SMACNA STANDARDS AND SYSTEM REQUIREMENTS. SHEET METAL GAUGES SHALL CONFORM TO THE INTERNATIONAL
MECHANICAL CODE (IMC), ASHRAE STANDARDS, AND UL LISTED FIRE RESISTANCE DIRECTORY REQUIREMENTS AS APPLICABLE.
4.2 DUCT COVERINGS, DUCT LININGS, TAPES, AND CORE MATERIAL SHALL HAVE A FLAME SPREAD RATING NOT OVER 25, AND
SMOKE DEVELOPMENT NOT OVER 50.
7.1 ELECTRIC MOTORS FOR MECHANICAL EQUIPMENT SHALL BE PROVIDED UNDER THE MECHANICAL WORK UNLESS OTHERWISE
NOTED. ALL MOTORS SHALL BE NEMA STANDARD DESIGN FOR QUIET OPERATION AND SIZED TO PROPERLY OPERATE EQUIPMENT AT
RATED LOAD. MOTORS WITH BELT DRIVES SHALL BE PROVIDED WITH ADJUSTABLE PULLEYS AND SHAFTS. ELECTRICAL POWER
CONNECTIONS FOR MECHANICAL EQUIPMENT SHALL BE PROVIDED UNDER THE ELECTRICAL WORK.
7.2 MOTOR STARTERS, RELAYS, AND CONTACTORS SHALL BE FURNISHED UNDER THE MECHANICAL WORK AND INSTALLED AND
POWERED UNDER THE ELECTRICAL WORK. STARTERS, RELAYS. AND CONTACTORS SHALL BE COMPUTE WITH LUGS SIZED FOR
SPECIFIED CONDUCTORS AND INCLUDE REQUIRED ACCESSORIES (I.E. START-STOP PUSH BUTTON, PILOT LIGHTS, H.O.A. SWITCH,
AUXILIARY CONTACTS AND OVERLOAD PROTECTION), GENERAL PURPOSE NEMA TYPE 1 ENCLOSURES INDOORS, NEMA TYPE 3R
ENCLOSURES OUTDOORS. SINGLE PHASE MOTOR STARTERS SHALL BE MANUAL TYPE WITH OVERLOAD PROTECTION, UNLESS
OTHERWISE NOTED. THREE PHASE STARTERS SHALL BE MAGNETIC FULL VOLTAGE, NON-REVERSING, UNLESS OTHERWISE NOTED.
STARTERS FOR MECHANICAL SYSTEMS SHALL BE AS MANUFACTURED BY SQUARE-D, GENERAL ELECTRIC, OR CUTLER HAMMER.
STARTERS SHALL CONFORM TO NEMA STANDARDS AND NATIONAL ELECTRICAL CODE (NEC) REQUIREMENTS. STARTER CONTROL AND
INTERLOCK WIRING SHALL BE PROVIDED UNDER THE MECHANICAL WORK. ALL EQUIPMENT SHALL BE FURNISHED W/ MANUFACTURER
PROVIDED DISCONNECT SWITCH.
7.3 DUCT SMOKE DETECTORS SHALL BE INSTALLED IN ALL AIR DISTRIBUTION SYSTEMS WITH A DESIGN CAPACITY OF 2000 CFM OR
GREATER IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL CODE SECTION 606 AND NATIONAL FIRE PREVENTION CODE NFPA
72 AND 90A. DUCT SMOKE DETECTORS SHALL BE "DUAL CONTAC"’ TYPE (FOR TIE-IN TO FIRE ALARM SYSTEM AND FOR FAN SHUTDOWN). COMPLETE WITH SAMPLING TUBE, REMOTE RESET, REMOTE PILOT INDICATOR (FOR CONCEALED APPLICATIONS), UL LISTED FOR
INTENDED USE AND COMPLETELY COMPATIBLE WITH FIRE ALARM SYSTEM. DUCT SMOKE DETECTORS SHALL BE FURNISHED AND
INSTALLED UNDER THE MECHANICAL WORK AND WIRED AND POWERED UNDER THE ELECTRICAL WORK.
8 CONTROLS
8.1 PROVIDE AUTOMATIC TEMPERATURE CONTROL SYSTEM(S) FOR HVAC EQUIPMENT UNDER MECHANICAL WORK. CONTROL DEVICES
SHALL BE PROVIDED BY UNIT MANUFACTURER, UNLESS OTHERWISE NOTED. HVAC EQUIPMENT NOT PROVIDED WITH CONTROL DEVICES
SHALL BE PROVIDED WITH DEVICES AS MANUFACTURED TO MATCH BASE BUILDING CONTROLS OR APPROVED EQUAL AIR HANDLER
SHALL HAVE NIGHT SET BACK CONTROLLED BY A PROGRAMMABLE THERMOSTAT. DEVICE(S) SHALL BE FULLY COMPATIBLE AND
SUITABLE FOR INTENDED USE. CONTROL WIRING SHALL BE PROVIDED IN ACCORDANCE WITH THE NEC FOR 24-VOLT CONTROL
SYSTEM(S). WIRING SHALL BE A MINIMUM 22 AWG, COLOR CODED AND INSTALLED IN CONDUIT WHERE SUBJECT TO PHYSICAL
DAMAGE OR WHERE REQUIRED TO AVOID PLENUM SPACES. EXTEND ALL LOW VOLTAGE WIRING UNBROKEN BETWEEN EACH CONTROL
DEVICE AND EQUIPMENT TERMINAL STRIP. INSTALLATION OF CONTROL SYSTEM(S), WRING. AND DEVICES SHALL BE BY A CERTIFIED
CONTROLS CONTRACTOR WITH A MINIMUM OF FIVE (5) YEARS EXPERIENCE IN THE INSTALLATION AND SERVICING OF CONTROLS.
8.2 UNLESS OTHERWISE INDICATED, ALL THERMOSTATS SHALL BE MOUNTED IN ACCORDANCE WITH ADA REQUIREMENTS.
GRILLE TAG TYPE
AIR CFM (CUBIC FEET PER MINUTE)
SUPPLY DUCT TO RISE
UP
2. PIPING
2.1 PIPING SHOWN IS SCHEMATIC AND DOES NOT INDICATE EVERY OFFSET, ELBOW, UNION, VALVE, TRAP, ACCESS PANEL, ETC.,
THAT IS REQUIRED FOR A COMPUTE WORKING SYSTEM. PROVIDE ITEMS AND FITTINGS THAT ARE REQUIRED TO INSTALL THE
PIPING SYSTEM WITHIN THE SPACE PROVIDED AND THAT ARE REQUIRED FOR A COMPUTE SYSTEM. PIPING SHALL BE PROPERLY
SECURED IN ACCORDANCE WITH MSS STANDARD SP-69.
R1
100
FIRE
DAMPER
6. DUCT INSULATION
1.5 MECHANICAL EQUIPMENT AND PRODUCTS SHALL BE LISTED AND/OR LABELED BY AN APPROVED TESTING OR INSPECTION
AGENCY IN ACCORDANCE WITH LOCAL AND GOVERNING CODE REQUIREMENTS.
DIFFUSER TAG TYPE
AIR CFM (CUBIC FEET PER MINUTE)
3985 GEORGIA ST,
SAN DIEGO, CA 92103
D). SUBSTITUTIONS SHALL PROVIDE THE SAME GUARANTEE AS SPECIFIED FOR BASE BID PRODUCTS.
AUTOMATIC (MOTORIZED) VOLUME
DAMPER/ SMOKE DAMPER
S1
100
DUCT WITH DUCT
BRANCH
DUCT WITH ROUND DUCT
TAKE-OFF
DUCT WITH CAPPED
END
ABBREVIATIONS
AF
AFF
ACU
AHU
APD
ARCH
AIR FILTER
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AIR HANDLING UNIT
AIR PRESSURE DROP
ARCHITECTURAL
BHP
BLDG
BLW
BTUH
BRAKE HORSEPOWER
BUILDING
BELOW
BRITISH THERMAL UNIT
PER HOUR
CC
CFM
CLG
CU
CW
DB
DDC
DlA
DI
DN
DO
DO
DPS
DWG
DX
(E)
EA
EAT
EF
CUBIC FEET PER MINUTE
CEILING
CONDENSING UNIT
COLD WATER
DRY BULB
DIRECT DIGITAL CONTROL
DIAMETER
DIGITAL INPUT
DOWN
DAMPER OPERATOR
DIGITAL OUTPUT
DIFFERENTIAL PRESSURE SWITCH
DRAWING
DIRECT EXPANSION
EXISTING
EACH
ENTERING AIR TEMPERATURE
EXHAUST FAN
EQUIP
ESP
EXT
EQUIPMENT
EXTERNAL STATIC PRESSURE
EXTERNAL
NO
NOM
No.
NORMALLY OPEN
NOMINAL
NUMBER
F
FD
FL
FPM
FT
DEGREE FAHRENHEIT
FIRE DAMPER
FLOOR
FEET PER MINUTE
FEET
O.A.
OAT
OED
PD
PS
PSI
RA
RAT
REFRIG
RLA
RPM
OUTSIDE AIR
OUTSIDE AIR TEMPERATURE
OPEN END DUCT
PRESSURE DROP
PRESSURE SENSOR
POUND PER SQUARE INCH
RETURN AIR
RETURN AIR TEMPERATURE
REFRIGERANT
RUNNING LOAD AMPERE
REVOLUTION PER MINUTE
SA
SAT
SD
SF
STRUC
SUPPLY AIR
SUPPLY AIR TEMPERATURE
SMOKE DETECTOR
SUPPLY FAN
STRUCTURAL
DRAWN BY:
TD
TS
TYP
TRANSFER DUCT
TEMPERATURE SENSOR
TYPICAL
SHEET TITLE:
UNO
UNLESS NOTED OTHERWISE
W
WB
WC
WMC
WPD
WATT
WET BULB
WATER COLUMN
WIRE MESH SCREEN
WATER PRESSURE DROP
GALV
HC
HP
HW
GALVANIZED
HEATING COIL
HEAT PUMP
HOT WATER
IN
IN. WG.
KW
INCH
INCH WATER GAUGE
KILOWATT
LAT
LB
LF
LEAVING AIR TEMPERATURE
POUNDS
LINEAR FEET
MAX
MBH
MECH
MER
MIN
MOT
MAXIMUM
1000 BTUH
MECHANICAL
MECHANICAL EQUIPMENT ROOM
MINIMUM
MOTORIZED
NC
NC
NIC
NOISE CRITERIA
NORMALLY CLOSED
NOT IN CONTRACT
MARK
DATE
DESCRIPTION
ISSUE:
PROJECT NO:
CAD FILE:
DATE:
Sal Sham
CHECKED BY:
COPYRIGHT:
MECHANICAL NOTES
DRAWING SHEET NO:
M000
3' - 0"
36" MIN.
6"ø
BEDROOM
EF
1
6"ø
CLOSET
S1
6"ø
AC
1.2
BATH 8"ø
S1
100 CFM
8"ø
100 CFM
S1
100 CFM
BEDROOM
R1
300 CFM
LIVING
DINING
8"ø
R1
300 CFM
DW
AC
1.1
BATH
8"ø
S1
100 CFM
S1
S1
100 CFM
100 CFM
KITCHEN
BEDROOM
8"ø
6"ø
6"ø
6"ø
EF
1
3' - 0"
6"ø
36" MIN.
3985 GEORGIA ST,
SAN DIEGO, CA 92103
REF.
CLOSET
1ST FLOOR MECHANICAL PLAN
1/4" = 1'-0"
AIR DEVICE SCHEDULE
TYPE
SERVICE
CFM
RANGE
S1
R1
Supply Air
Return Air
100 CFM
300 CFM
MAX MAX
SP NC
0.1
0.1
30
30
TYPE
LOCATION
10" Face 3" Neck
10" Face 3" Neck
CEILING
CEILING
MODEL
NOTES
ALL-WEATHER VENT CAP
PROVIDE 3' DUCT HEIGHT
PROVIDE ROOF FLASHING
COMPATIBLE WITH EXISTING
ROOF TYPE.
UNIT NO.
LOCATION
SERVICE
COUNTS
CFM
ESP
WATTS
EF -1
CEILING
BATHROOM
6
75 CFM
0.5
50 W
DESCRIPTION
PROJECT NO:
ROOF DECK
ELECTRICAL DATA
VOLTS
PHASE
CYCLE
120
1
60
DATE
ISSUE:
STORM COLLAR
FAN SCHEDULE
MARK
CAD FILE:
ROOFING
METHOD OF CONTROL
DATE:
NOTES
DRAWN BY:
SWITCH
ROOF STRUCTURE
Sal Sham
CHECKED BY:
COPYRIGHT:
SPLIT TYPE UNIT SCHEDULE
COOLING
INDOOR
UNIT
NUMBER
SERVES
TYPE
MAX CFM
OA CFM
SHEET TITLE:
COMPRESSOR DATA
EAT °F
LAT °F
MFCR AND MODEL
TOTAL BTUH
DB
WB
DB
WB
OUTDOOR
UNIT
NUMBER
MOUNTING
COOLING
BTUH
IEER
CONDENSER FAN DATA
NOTES:
POWER SUPPLY
CIRCUIT
QTY
QTY
RLA
HP
RPM
FLA
LRA
MCA
MOCP
VOLTS
PHASE
CYCLE
UNIT
WEIGHT,
POUNDS
LRA
1)
MFCR AND MODEL
REMARKS
LOCATE ROOF PENETRATION A MINIMUM OF 10'-0"
FROM ANY OUTSIDE AIR INTAKES.
2)
PROVIDE ROOF ACCESSORIES THAT ARE COMPATIBLE
WITH EXISTING ROOFING MATERIALS.
AC-1.1
KITCHEN/DINING/BEDROOM
CASETTE
300
9000
80
67
55
54
AC-1.2
LIVING/BEDROOM
CASETTE
300
9000
80
67
55
54
CU-1
DECK
36000
21.5
35
50
240
1
60
255
EXHAUST ROOF PENETRATION DETAIL
1
3
NOT TO SCALE
GR. & 1ST LL
MECHANICAL PLANS
DRAWING SHEET NO:
M001
3' - 0"
3' - 0"
36" MIN.
36" MIN.
EF
1
S1
CLOSET
100 CFM
6"ø
TV
S1
S1
100 CFM
100 CFM
BEDROOM
EF
1
S1 CLOSET
100 CFM
8"ø
BATH
BATH8"ø
AC
2.2
LIVING
AC
2.2
6"ø
R1
R1
300 CFM
TV
S1
S1
100 CFM
LIVING
300 CFM
BEDROOM
TV
100 CFM
8"ø
6"ø
6"ø
6"ø
6"ø
TV
8"ø
8"ø
R1
300 CFM
DINING
300 CFM
BATH
AC
2.1
BATH
R1
DINING
AC
3.1
100 CFM
100 CFM
S1
100 CFMBEDROOM
8"ø
TV
36" MIN.
6"ø
3' - 0"
6"ø
S1
100 CFM
100 CFM
TV
6"ø
36" MIN.
REF.
CLOSET
S1
REF.
2ND FLOOR MECHANICAL PLAN
3RD FLOOR MECHANICAL PLAN
1/4" = 1'-0"
1/4" = 1'-0"
3985 GEORGIA ST,
SAN DIEGO, CA 92103
3' - 0"
6"ø
EF
1
6"ø
6"ø
6"ø
TV
DW
S1
BEDROOM
8"ø
EF
1
S1
6"ø
8"ø
TV
100 CFM
KITCHEN
8"ø
DW
KITCHEN
S1
ALL-WEATHER VENT CAP
MARK
DATE
DESCRIPTION
PROVIDE 3' DUCT HEIGHT
ISSUE:
STORM COLLAR
PROJECT NO:
PROVIDE ROOF FLASHING
COMPATIBLE WITH EXISTING
ROOF TYPE.
CAD FILE:
ROOF DECK
ROOFING
DATE:
DRAWN BY:
SPLIT TYPE UNIT SCHEDULE
COOLING
INDOOR
UNIT
NUMBER
SERVES
TYPE
MAX CFM
OA CFM
CHECKED BY:
ROOF STRUCTURE
COMPRESSOR DATA
EAT °F
LAT °F
MFCR AND MODEL
TOTAL BTUH
DB
WB
DB
WB
80
67
55
54
OUTDOOR
UNIT
NUMBER
MOUNTING
COOLING
BTUH
SEER
CONDENSER FAN DATA
POWER SUPPLY
CIRCUIT
QTY
QTY
RLA
HP
RPM
FLA
LRA
MCA
MOCP
VOLTS
PHASE
CYCLE
UNIT
WEIGHT,
POUNDS
MFCR AND MODEL
NOTES:
LRA
KITCHEN/DINING/BEDROOM
CASETTE
300
9000
CU-2
AC-2.2
LIVING/BEDROOM
CASETTE
300
9000
80
67
55
54
AC-3.1
KITCHEN/DINING/BEDROOM
CASETTE
300
9000
80
67
55
54
AC-3.2
LIVING/BEDROOM
CASETTE
300
9000
80
67
55
54
DECK
36000
22
10
35
50
240
1
60
255
COPYRIGHT:
SHEET TITLE:
REMARKS
1) LOCATE ROOF PENETRATION A MINIMUM OF 10'-0"
AC-2.1
Sal Sham
FROM ANY OUTSIDE AIR INTAKES.
2) PROVIDE ROOF ACCESSORIES THAT ARE COMPATIBLE
2ND & 3RD LL
MECHANICAL PLANS
WITH EXISTING ROOFING MATERIALS.
CU-3
DECK
36000
22
10
35
50
240
1
60
255
EXHAUST ROOF PENETRATION DETAIL
2
3
NOT TO SCALE
DRAWING SHEET NO:
M002
CONTRACTOR SHALL BE RESPONSIBLE FOR VISITING THE SITE AND VERIFYING ALL EXISTING FIELD
CONDITIONS PRIOR TO SUBMISSION OF BlD.
2.
CONTRACTOR IS RESPONSIBLE FOR COORDINATING WORK WITH THE WORK OF ALL OTHER TRADES AND
MAKING ANY NECESSARY MODIFICATIONS TO WORK AT NO ADDITIONAL COST, INCLUDING ALL OFFSETS.
3.
CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATION OF ANY EXISTING MINOR INTERFERENCE'S.
INCLUDING CONDUIT, HANGERS, ETC., AT NO ADDITIONAL COST.
25.
CONTRACTOR SHALL REMOVE EXISTING EQUIPMENT AND MATERIALS PERTAINING TO CONTRACT AS
SPECIFIED OR AS REQUIRED WHETHER SHOWN ON THE DRAWINGS OR NOT. TO PREPARE FOR THE NEW
WORK.
26.
4.
5.
24.
ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH LOCAL CODES. THESE CODES SHALL BE
FOLLOWED AS MINIMUM PROVIDING HIGHER GRADES OF MATERIAL AND WORKMANSHIP WHERE
REQUIRED BY THESE DOCUMENTS. PROVIDE ALL TESTS REQUIRED BY LOCAL CODES.
27.
6.
7.
8.
ALL PERMITS. FEES. LICENSES. APPROVALS AND OTHER ARRANGEMENTS FOR WORK SHALL BE OBTAINED
BY THE CONTRACTOR AT HIS OWN EXPENSE.
SUBMIT ASSEMBLED PRINTED INSTRUCTIONS FOR THE OPERATION AND MAINTENANCE OF EACH ITEM
INSTALLED ALONG WITH EQUIPMENT CUTS AND CONTROL WIRING DIAGRAMS.
SUBMIT COORDINATED SHOP DRAWINGS FOR REVIEW. THE SHOP DRAWINGS SHALL INDICATE WORK OF
OTHER TRADES AND MUST BE SUBMITTED PRIOR TO FABRICATION AND INSTALLATION.
9.
SUBMIT EQUIPMENT SPECIFICATIONS FOR REVIEW BEFORE PURCHASE.
10.
CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIAL FOR ONE YEAR AFTER COMPLETION AGAINST
ALL DEFECTS OF MATERIAL, EQUIPMENT AND WORKMANSHIP.
11.
PROVIDE COMPETENT OPERATING TECHNICIAN TO INSTRUCT THE OWNER IN THE OPERATION AND
MAINTENANCE OF THE INSTALLED EQUIPMENT.
12.
PROVIDE ACCESS PANELS FOR ALL VALVES OR ANY PIECE OF EQUIPMENT WHEN NECESSARY TO LOCATE
ABOVE NON-ACCESSIBLE CEILINGS. PROVIDE SUBMITTAL DRAWINGS FOR APPROVAL OF THE ARCHITECT.
NO EQUIPMENT SHALL BE LOCATED DIRECTLY ABOVE WALLS.
13.
PROVIDE ALL HOLES, SLEEVES AND CAULKING FOR INSTALLATION OF THIS WORK. CAULKING TO
CONFORM TO FIRE RATING OF WALLS.
14.
PIPING SHALL BE ABOVE CEILING AND CLEAR ANY EXISTING PIPING, LIGHTING FIXTURES, DUCTS, ETC.
15.
RUN NEW WASTE PIPES AS CLOSE AS POSSIBLE TO UNDERSIDE OF FLOOR SLAB AND VENT PIPING AS
CLOSE AS POSSIBLE TO SLAB ABOVE.
16.
RUN ALL PIPING OCTAGONAL & PARALLEL TO CLOSEST WALL OR PRIMARY STRUCTURAL ELEMENTS.
17.
CONTRACTOR SHALL SUBMIT SKETCH TO THE STRUCTURAL ENGINEER FOR APPROVAL, PRIOR TO MAKING
REQUIRED BEAM PENETRATIONS.
18.
PIPING SHOWN IS SCHEMATIC AND DOES NOT INDICATE EVERY OFFSET. ELBOW, UNION, VALVE, TRAP.
ACCESS PANEL. ETC., THAT IS REQUIRED FOR A COMPLETE WORKING SYSTEM. PROVIDE ITEMS AND
FITTINGS THAT ARE REQUIRED TO INSTALL THE PIPING SYSTEM WITHIN THE SPACE PROVIDED AND THAT
ARE REQUIRED FOR A COMPLETE SYSTEM. PIPING SHALL BE PROPERLY SECURED IN ACCORDANCE WITH
MSS STANDARD SP-69.
29.
ACCESS PANEL
BFP
BACKFLOW PREVENTER
C.O.P
CLEAN OUT PLUG
CW
COLD WATER
PLUMBING FIXTURES:
DW
DISHWASHER MACHINE
A.
EX.
EXISTING
HW
HOT WATER
LAV
LAVATORY
OSD
OPEN SITE DRAIN
TPV
TRAP PRIMER VALVE
TV
TEMPERING VALVE
S.A.
SHOCK ABSORBER (WATER HAMMER)
SK
SINK
V
VENT
VTR
VENT THROUGH ROOF
W
WASTE
WC
WATER CLOSET
PIPE SUPPORTS SHALL BE SELECTED AND INSTALLED IN ACCORDANCE WITH THE MSS SP-69 OR LOCAL
CODES, WHICHEVER IS MORE STRINGENT. UTILIZE TRAPEZE HANGERS FOR PARALLEL RUNS OR PIPING.
OTHER THAN SPRINKLER AND WASTE PIPING. COPPER PIPING SYSTEMS SHALL BE SUPPORTED ON
COPPER OR COPPER-PLATED SUPPORTS. HANG PIPE FROM SUBSTANTIAL BUILDING STRUCTURE, PIPING
SHALL NOT BE HUNG FROM OTHER PIPING. ALL RIGID HANGERS SHALL PROVIDE A MEANS OF VERTICAL
ADJUSTMENT AFTER ERECTION. SHIELD SHALL BE PROVIDED BETWEEN HANGERS AND INSULATION.
FURNISH AND INSTALL PLUMBING FIXTURES INDICATED. FIXTURES TO BE FIRST QUALITY,
CONNECTED,
CLEANED AND READY FOR USE. PIPING TO BE PROPERLY SECURED TO WALLS AND
STUDS.
PROVIDE TRAPS AND SUPPLIES WITH STOPS. MAKE ALL FINAL CONNECTION TO EACH FIXTURE.
HANGERS:
A.
PIPE HANGERS ON HOT PIPING TO BE ON INSIDE OF INSULATION. PROVIDE WITH SADDLES AND/OR
SHIELDS AS REQUIRED.
B.
PIPE HANGERS ON COLD PIPING TO BE ON OUTSIDE OF INSULATION. PROVIDE WITH
AND/OR
SHIELDS AS REQUIRED.
SADDLES
PROVIDE ANY AND ALL ITEMS NECESSARY TO COMPLETE THE PLUMBING SYSTEM. THE PLUMBING
DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY SHOW ALL VALVES, FITTINGS, TRAPS,
CONTROL DEVICE METHODS.
30.
INSTALL ALL ADA FIXTURES IN AN ADA COMPLIANT MANNER.
31.
INSTALL SKAL + GARD #SC-100B ON SINKS SUPPLIES AND TRAPS FOR HANDICAPPED USE.
GENERAL NOTES:
THE DRAWINGS PREPARED FOR THIS PROJECT ARE AN OUTLINE TO SHOW WHERE PIPES, DUCTS AND
APPARATUSES MUST GO IN ORDER TO HARMONIZE WITH THE BUILDING AND INSTALLATION OF THE
VARIOUS TRADES. WORK MUST BE INSTALLED IN ACCORDANCE WITH THE DRAWINGS AS MUCH AS
POSSIBLE. DRAWINGS SHALL BE CAREFULLY CHECKED DURING THE COURSE OF BIDDING AND
CONSTRUCTION. IF DISCREPANCIES, ERRORS OR OMISSIONS ARE DISCOVERED PRIOR TO OR DURING
CONSTRUCTION PHASE, NOTIFY THE ENGINEER IMMEDIATELY FOR INTERPRETATION OR CORRECTION.
TAKE NECESSARY MEASUREMENTS AND RESPONSIBLE FOR SAME, INCLUDING CLEARANCES FOR
EQUIPMENT THAT ARE TO BE FURNISHED. THE ARCHITECT /ENGINEER RESERVE THE RIGHT TO MAKE
MINOR LOCATION CHANGES OF PIPING AND EQUIPMENT WHERE SUCH ADJUSTMENTS ARE DEEMED
DESIRABLE FROM AN APPEARANCE OR OPERATIONAL STANDPOINT. SUCH CHANGES WILL BE
ANTICIPATED SUFFICIENTLY IN ADVANCE OR AVOID EXTRA WORK OR DELAY THE PROGRESS OF THE
PROJECT.
DISRUPTION OF ANY EXISTING SERVICE SHALL BE COORDINATED WITH THE OWNER AND SHALL BE
PERFORMED AT A TIME AND MANNER SO AS TO CAUSE THE OWNER A MINIMUM OF INCONVENIENCE.
FOR EXACT LOCATION OF PLUMBING FIXTURES, REFER TO ARCHITECTURAL PLANS AND ELEVATIONS.
EXAMINATION OF EXISTING CONDITIONS:
20.
R3 PIPE INSULATION: DOMESTIC HOT AND COLD WATER PIPING SHALL BE INSULATED WITH 1’’ THICK 4#
DENSITY, GLASS FIBER PRE-FORMED, ALL PURPOSE FLAME RETARDANT JACKET WITH BUILT-IN VAPOR
BARRIER. PROVIDE INSULATION PIPE HANGERS WHEN NECESSARY, ARMACELL, ARMAFIX IPH
32.
MATERIALS SHALL BE RATED FOR THE OPERATING TEMPERATURE AND PRESSURE OF THE HYDRONIC
SYSTEM. MATERIALS SHALL BE SUITABLE FOR THE TYPE OF FLUID IN THE HYDRONIC SYSTEM.
33.
22.
TRAP SEAL PRIMER VALVE
AP
19.
21.
GATE VALVE
MATERIALS SHALL BE RATED FOR THE OPERATING TEMPERATURE AND PRESSURE OF DOMESTIC SYSTEM.
MATERIALS SHALL BE SUITABLE FOR THE TYPE OF FLUID IN THE DOMESTIC SYSTEM.
B.
28.
PLUMBING SYMBOL LIST
PROJECT PREMISES SHALL BE THOROUGHLY CLEANED AND READY FOR OCCUPANCY INCLUDING ALL
FINISHES OF EQUIPMENT PROVIDED AS PART OF THE CONTRACTOR'S WORK.
VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE SHE AND/OR PRESENT BUILDINGS AFFECTED
BY THIS WORK SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL
ATTEND THE EXECUTION Of THE WORK BEFORE SUBMITTING PROPOSALS.
SUBMISSION OF A PROPOSAL WILL BE CONSTRUCTED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN
MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE DIFFICULTIES
ENCOUNTERED. WHICH COULD HAVE BEEN FORESEEN HAD SUCH AN EXAMINATION HAD BEEN MADE, WILL
NOT BE RECOGNIZED.
PONT OF CONNECTION OF NEW WORK TO EXISTING WORK
END OF DEMOLITION
CROSS HATCH DEMOLITION
THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE (1)
YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER AND SHALL REPAIR OR REPLACE AT NO
ADDITIONAL COST TO THE OWNER ANY PART THEREOF WHICH MAY BECOME DEFECTIVE DURING THE
PERIOD OF GUARANTEE, ORDINARY WEAR AND TEAR EXCEPTED. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR AND PAY FOR ANY DAMAGES RESULTING FROM OR CAUSED BY DEFECTS IN HIS/HER
WORK.
34.
35.
DEMOLITION KEYED NOTES
27
NEW WORK EQUIPMENT/FIXTURE TAG NUMBER
W
2
REFERENCE WATER RISER TAG NUMBER
4'' CO
7
CLEANOUT
NEW WORK KEYED NOTES
FCO
FLOOR CLEANOUT
FCO
FLOOR DRAIN
WH
1
CONNECTIONS TO EXISTING WORK:
23.
2
PLAN INSTALLATION OF NEW WORK AND CONNECTIONS TO EXISTING WORK TO INSURE MINIMUM
INTERFERENCE WITH REGULAR OPERATION OF EXISTING FACILITIES.
3985 GEORGIA ST,
SAN DIEGO, CA 92103
1.
EQUIPMENT NUMBER
NEW VENT
NEW SANITARY
PROJECT PREMISES SHALL BE THOROUGHLY CLEANED AND READY FOR OCCUPANCY INCLUDING ALL
FINISHES OF EQUIPMENT PROVIDED AS PART OF THE CONTRACTOR'S WORK AT PROJECT CLOSEOUT.
NEW GRAY WATER SANITARY
NEW HOT WATER
PIPE MATERIAL SCHEDULE
SANITARY
STORM
VENT
WATER
NEW COLD WATER
3" AND SMALLER SERVICE WT. C l. NO-HUB PIPE AND FITTINGS. 4" STORM AND LARGER SERVICE WT.
C.L HUB AND SPIGOT PIPE AND FITTINGS.
V
BLACK/GRAY WATER VALUE
3’ AND SMALLER SCH. 40 GAL PIPE AND SCREWED FITTINGS OR TYPE M COPPER PIPE AND SOLDER
DRAINAGE FITTINGS.
REMOTE MANUAL PULL STATION
4" AND LARGER SCH. 40 GAL PIPE AND SCREWED FITTINGS. PEX TYPE B
AND SOLDER FITTINGS.
DISREGARD SYMBOLS WHICH ARE NOT APPLICABLE TO THIS PROJECT
GAS
BLACK STEEL ASTM A53 SCHEDULE 40. FITTINGS, ASME B16.3, MALLEABLE IRON, 150 PSIG. JOINTS;THREADED FOR PIPE 2 INCH
AND SMALLER, WELDED FOR PIPE 2 1/2" AND LARGER
MARK
DATE
DESCRIPTION
ISSUE:
TANK LESS WATER HEATER SCHEDULE
CAD FILE:
ELECTRICAL CONNECTION
UNIT NO.
SERVED
MOUNTING
WH-1
HOT WATER
WALL
PHASE
CYCLE
1ST HOUR DELIVERY
(GPH 100F RISE)
1
60
80
GAS, MBH
WATTS VOLTS
150
1200
120
PROJECT NO:
DATE:
DRAWN BY:
Sal Sham
CHECKED BY:
COPYRIGHT:
SHEET TITLE:
PLUMBING NOTES
DRAWING SHEET NO:
P000
1/2"ø HW
1/2"ø HW
1/2"ø HW
1/2"ø CW
HOSE BIB
1/2"ø CW
D
1/2"ø CW
BEDROOM
BATH
1/2"ø HW
3/4"ø CW
CLOSET
LIVING
1/2"ø HW
1/2"ø HW
3/4"ø CW
1/2"ø HW
1/2"ø CW
3/4"ø CW
HOSE BIB
1/2"ø HW
DINING
3/4"ø CW
WH
1
WH
1
WH
1
WH
1
1/2"ø HW
3/4"ø CW
1/2"ø CW
3/4" DOWN TO GR. FLOOR
3/4" DOWN TO GR. & UP TO 2ND FLOOR
REF.
3/4" DOWN TO GR. & UP TO 3RD FLOOR
CLOSET
1/2"ø HW
HOSE BIB
3/4" DOWN TO GR. & UP TO ROOF
3/4"ø CW
GR. FLOOR WATER SUPPLY PLAN
1ST FLOOR WATER SUPPLY PLAN
1/4" = 1'-0"
1/4" = 1'-0"
1/2"ø HW
1/2"ø CW
1/2"ø HW
BEDROOM
1/2"ø HW
3/4"ø CW
BATH
1/2"ø HW
3/4"ø CW
1/2"ø CW
CLOSET
CLOSET
BEDROOM
1/2"ø HW
3/4"ø CW
1/2"ø HW
BATH
LIVING
LIVING
1/2"ø HW
1/2"ø HW
3/4"ø CW
1/2"ø HW
3/4"ø CW
1/2"ø HW
1/2"ø HW
1/2"ø HW
3/4"ø CW
3/4"ø CW
1/2"ø HW
BATH
DINING
BEDROOM
1/2"ø HW
KITCHEN
BEDROOM
1/2"ø HW
3/4"ø HW
3/4" DOWN TO 1ST FLOOR
REF.
3/4" DOWN TO 1ST FLOOR UP TO 3RD FLOOR
1/2"ø HW
CLOSET
1/2"ø HW
MARK
3/4"ø CW
1/2"ø HW
1/2"ø CW
3/4"ø CW
1/2"ø CW
DW
KITCHEN
1/2"ø CW
DW
1/2"ø HW
3/4"ø CW
BATH
3/4"ø CW
DINING
1/2"ø HW
3/4"ø CW
3/4"ø CW
1/2"ø CW
3985 GEORGIA ST,
SAN DIEGO, CA 92103
3/4"ø HW 3/4"ø HW
3/4" UP TO 1ST FLOOR
1"ø CW
KITCHEN
BEDROOM
3/4"ø CW
1" PIPE CW INPUT
3/4"ø CW
1"ø CW
DOUBLE CHECK VALVE
3/4"ø CW
3/4"ø CW
1 1/4" WATER
METER
BATH
DW
1/2"ø CW
1/2"ø HW
UTILIT
DATE
DESCRIPTION
ISSUE:
CLOSET
1/2"ø HW
REF.
3/4" UP
TO ROOF
3/4"ø HW
PROJECT NO:
CAD FILE:
3/4"ø CW
GENERAL NOTES
3/4"ø CW
3/4" DOWN TO 1ST FLOOR UP TO ROOF
3/4"ø CW
3/4"ø CW
3/4" DOWN TO 2ND FLOOR
2ND FLOOR WATER SUPPLY PLAN
3RD FLOOR WATER SUPPLY PLAN
1/4" = 1'-0"
1/4" = 1'-0"
DATE:
DRAWN BY:
Sal Sham
CHECKED BY:
COPYRIGHT:
1.
2.
3.
4.
5.
6.
7.
8.
9.
FOR DOMESTIC WATER PIPE SIZES, REFER TO DOMESTIC WATER RISER DIAGRAM.
ALL WATER LINES ARE LOCATED ABOVE THE CEILING UNLESS OTHERWISE NOTED
IF THE WATER PRESSURE EXCEEDS 80 PSI, AND EXPANSION TANK AND AN APPROVED PRESSURE REGULATOR SHALL BE INSTALLED.
THAT NON-REMOVABLE BACKFLOW PREVENTER OR BIBB-TYPE VACUUM BREAKER WILL BE INSTALLED ON ALL EXTERIOR HOSE BIBS.
ALL PLUMBING VENTS SHALL TERMINATE NOT LESS THAN 6” ABOVE THE ROOF NOR LESS THAN 1’ FROM ANY VERTICAL SURFACE. VENTS SHALL TERMINATE NOT LESS
THAN 10” FROM OR 3’ ABOVE ANY WINDOW, DOOR, OPENING, AIR INTAKE, OR VENT SHAFT NOR 3’ FROM LOT LINE.
NEW OR RECONFIGURED SHOWER STALLS SHALL BE A MINIMUM FINISHED INTERIOR OF 1,024 SQUARE INCHES, BE CAPABLE OF ENCOMPASSING A 30 INCH DIAMETER
CIRCLE. ANY DOORS SHALL SWING OUT OF THE ENCLOSURE HAVE A CLEAR OPENING OF 22 INCHES MINIMUM.
SHOWER STALLS AND BATHTUBS WITH SHOWER HEADS INSTALLED, SHALL HAVE WALLS FINISHED WITH A NONABSORBENT SURFACE FOR A MINIMUM OF 6 FEET ABOVE
THE FLOOR.
HYDRO-MASSAGE TUBS (I.E. JACUZZI TUBS) SHALL HAVE ACCESS TO THE MOTOR, BE SUPPLIED BY A GFCI PROTECTED DEDICATED CIRCUIT, AND BE LISTED BY A
RECOGNIZED TESTING AGENCY (I.E. UL). ALL METAL CABLES, FITTINGS, PIPING, OR OTHER METAL SURFACES, WITHIN 5 FEET OF THE INSIDE WALL OF THE HYDRO-MASSAGE
TUB SHALL BE PROPERLY BONDED. HYDRO-MASSAGE TUBS SHALL BE BONDED WITH A MINIMUM #8 AWG BARE COPPER WIRE AND THE BONDING SHALL BE ACCESSIBLE.
WHERE THE WATER CLOSET (OR OTHER PLUMBING FIXTURE) COMES INTO CONTACT WITH THE WALL OR FLOOR, THE JOINT SHALL BE CAULKED AND SEALED TO BE
WATERTIGHT.
SHEET TITLE:
FLOOR WATER SUPPLY
PLANS
DRAWING SHEET NO:
P001
3" SANITARY UP TO 1ST FLOOR
3"ø
1 1/2"ø
CONTINUES TO ALLEY
VENT UP TO 1ST
FLOORD
4"ø
4"ø
3" SANITARY DOWN TO GR. & UP TO 2ND FLOOR
VENT UP TO 2ND FLOOR
4"ø
1 1/2"ø
(E) 4" SANITARY LINE
3"ø
CLOSET
4"ø
1 1/2"ø
1 1/2"ø
1 1/2"ø
3"ø
BEDROOM
LIVING
1 1/2"ø
1 1/2"ø
KITCHEN
1 1/2"ø
1 1/2"ø
3" SANITARY UP TO 1ST FLOOR
1 1/2"ø
DW
1 1/2"ø
1 1/2"ø
1 1/2"ø
DINING
BATH
UTILIT
1 1/2"ø
3"ø
3"ø
BEDROOM
VENT UP TO 2ND FLOOR
3" SANITARY DOWN TO GR. & UP TO 2ND FLOOR
3"ø
3"ø
1 1/2"ø
REF.
CLOSET
GR. FLOOR POWER SANITARY PLAN
1ST FLOOR SANITARY PLAN
1/4" = 1'-0"
1/4" = 1'-0"
3"ø
3" SANITARY DOWN TO 1ST & UP TO 3RD FLOOR
3"ø
3"ø
3"ø
3" SANITARY DOWN TO 2ND FLOOR
VENT DOWN TO 2ND FLOOR
BATH
1 1/2"ø
1 1/2"ø
VENT DOWN TO 1ST & UP TO 3RD FLOOR
CLOSET
3985 GEORGIA ST,
SAN DIEGO, CA 92103
3"ø
CLOSET
BATH
1 1/2"ø
1 1/2"ø
1 1/2"ø
BEDROOM
BEDROOM
1 1/2"ø
LIVING
1 1/2"ø
LIVING
VENT AT ROOF
1 1/2"ø
DATE
DESCRIPTION
1 1/2"ø
ISSUE:
1 1/2"ø
PROJECT NO:
BEDROOM
VENT AT ROOF
KITCHEN
CAD FILE:
DATE:
1 1/2"ø
1 1/2"ø
1 1/2"ø
KITCHEN
1 1/2"ø
DW
1 1/2"ø
BEDROOM
BATH
1 1/2"ø
DW
1 1/2"ø
BATH
MARK
1 1/2"ø
1 1/2"ø
1 1/2"ø
1 1/2"ø
DINING
DINING
1 1/2"ø
DRAWN BY:
Sal Sham
CHECKED BY:
1 1/2"ø
1 1/2"ø
3"ø
VENT DOWN TO 1ST & UP TO 3RD FLOOR
3"ø
3"ø
3" SANITARY DOWN TO 1ST & UP TO 3RD FLOOR
CLOSET
VENT DOWN TO 2ND FLOOR
3" SANITARY DOWN TO 2ND FLOOR
3"ø
1 1/2"ø
1 1/2"ø
SHEET TITLE:
CLOSET
REF.
3"ø
COPYRIGHT:
REF.
FLOOR SANITARY PLANS
3"ø
2ND FLOOR SANITARY PLAN
3RD FLOOR SANITARY PLAN
1/4" = 1'-0"
1/4" = 1'-0"
DRAWING SHEET NO:
P002
1/2" HW
1/2" CW
SANITARY
VENT
VACUUM
BREAKER
RECESSED OUTLET BOX WITH
3/4" HOSE BIBB
CONNECTIONS, WATER HAMMER
ARRESTORS AND 2" DRAIN
INLET
AUTOMATIC CLOTHES
WASHER
2" STANDPIPE
DRAIN
2" TRAP
DRAIN
HOSE
1/2"ø CW
HOSE BIB
HOSE BIB
1/2"ø CW
3/4"ø CW
1/2"ø CW
1/2"ø CW
3/4" DOWN TO GR. FLOOR
3
ROOF WATER SUPPLY PLAN
1/4" = 1'-0"
2
ROOF SANITARY PLAN
1/4" = 1'-0"
3985 GEORGIA ST,
SAN DIEGO, CA 92103
1
CLOTHES WASHER DETAILS
NOT TO SCALE
GALV. WROT-IRON OR STEEL PIPE
HOT DIPPED
GALVANIZED
SEALING AND
ANCHORING
COMPOUND
WELD
MEMBRANE FLASHING AS REQUIRED
GALV. MAL. IRON (IPS) FLASHING FITTING
FRESH AIR INLET
SEAL SLEEVE WITH TIGHTLY PACKED
OAKUM AND POURED LEAD
IF COPPER; ALSO PROVIDE &
INSTALL ISOLATION FELT
4"
2'-0" ABOVE HVAC
VENT OPENING
CONCRETE
FLOOR DRAIN WITH ADJUSTABLE COLLAR / STRAINER ASSEMBLY
FLOOR LINE
CO U NTERFLASHIN G: 6L BPER SQ U ARE FO O T SH EET LEA D O R16OZ. COO PER
FINISHED FLOOR
FINISHED GRADE
SOLDER JOINT (PLMB. CONT'R)
CENTER PIPE
IN SLEEVE
MEMBRANE ANCHOR FLANCE
HOUSE TRAP W/ C.O. PLUGS
6"
ALL AROUND
MARK
ROOF FINISH
STRUCTURAL SLAB
C.O.
HOT DIPPED
GALVANIZED
STANDARD
WEIGHT
STEEL PIPE
POURED IN
PLACE
"P" TRAP
DESCRIPTION
ISSUE:
CONNECT TO COMBINED
SYSTEM
COAT EXTERIOR SURFACES
WITH TAR CONPOUND
DATE
FLA SH IN G U N DER G EN ERA L CO N ST.
PROJECT NO:
ROOF CONSTRUCTION
CAD FILE:
SANITARY FROM SYSTEM
UPPER HALF MASTIC CAULKING COMPOUND
STEEL PIPE SLEEVE
ESCUTCHEON (WHETHER OR NOT IN FIN.AREAS)
DATE:
DRAWN BY:
Sal Sham
CHECKED BY:
LOWER HALF PICKED OAKUM PACKED
GALV. WROT-IRON OR STEEL PIPE
COPYRIGHT:
SHEET TITLE:
ROOF WATER SUPPLY &
SANITARY PLANS
4
FLOOR DRAIN DETAIL
NOT TO SCALE
5
PIPE THRU FOOTING PENETRATION
NOT TO SCALE
6
SANITARY HOUSE TRAP DETAIL
NOT TO SCALE
7
VENT STACK DETAIL
NOT TO SCALE
DRAWING SHEET NO:
P003
W
øC
3/4
"
3/4
"
øC
W
"
1/2
ø
3/4
"
BATH
1/2
"
LAV
WC
1/2
"
HW
"ø
2
/
1
1/2
"
WC
1/2
"
LAV
ø H
W
øC
W
W
3/4
"
ø H
W
øC
W
3/4
"ø
CW
CW
3/4
"
HW
"ø
1/2
DOUBLE CHECK VALVE
øC
W
"ø
1/2
WC
1/2
"
øC
W
ø H
W
1"ø
CW
1"ø
1/2
"
"
1/2
BT
HW
1
11
/2"
ø
/2"
1 11 1/2
"
ø
/2"
11
1
ø
"ø
1/2
ø
SK
BATH
HW
"ø
1/2
W
øC
CW
"ø
4
/
3
1/2
"ø
CW
1/2
"ø
"ø
1/2
1
1 1/2"ø
LAV
11
/2"
"ø
1/2
11
/2"
WC
11
/2"
HW
LAV
HW
"ø
1/2
CW
"ø
2
/
1
1
ø
ø
11
/2"
WC
ø
CW
LAV
ø H
W
"ø
1/2
"
1/2
HW
"ø
2
/
1
W
ø H
BATH
CW
1
"ø
1/2
SLO
PE
1/4
"
FD
LAV
1"ø
3"ø
CW
CONTINUES TO ALLEY
HOSE BIB
LAV
1'
PER
/2"
11
ø
ø
/2"
11
WC
ø
BT
SK
"ø
1/2
11
/2"
ø
11
/2"
ø
/2"
11
ø
3"ø
PE
SLO
1'
ER
P
"
1/4
3"ø LAV
ø
/2"
11
ø
11
/2"
ø
/2"
11
WC
BT
ø
LAV
PER
1'
3"ø
ø
/2"
11
WC
/2"
11
LAV
SLO
PE
1/4
"
ø H
W
1" PIPE CW INPUT
BT
ø
WC
11
/2"
LAV
BT
W
C
"ø
3/4
HW
"ø
2
/
1/2
1
"ø
HW 1/2"ø
CW
ø
/4"
E1
P
O
SL
11
/2"
BATH
11
/2"
11
/2"
ø
LAV
3"ø
WC
W
øC
"
4
/
3/4 3
"ø
CW 1" WATER METER
øC
W
1/2
"ø
HW
ø H
W
ø H
W
W
3"ø
PER
1'
PE
SLO
3"ø
4"ø
11
/2"
ø
1'
ER
P
"
1/4
3"ø
ø
3"ø
1
4"ø
WATER SUPPLY RISER DIAGRAM
SLO
PE
1/4
"
2
PER
1'
4"ø
SANITARY RISER DIAGRAM
(E) 4" SANITARY LINE
MARK
PLUMBING FIXTURE SCHEDULE
7' - 0"
WH
1
DOMESTIC HOT WATER
CONDENSATE
DOMESTIC HOT WATER
RETURN
DOMESTIC COLD WATER
RP
1
2' - 8"
4 1/2"
1/2
"
1/2
"
3/4
"
CW
"ø
3/4
HOSE BIB
øC
W
øC
W
ø
HW
"ø
2
/
1
øC
W
LAV
1/2
"
"
3/4
HW
"ø
1/2
CW
"ø
3/4
HW
"ø
1/2
BATH
CW
"ø
2
/
1
SK
CW
"ø
3/4
ø H
W
3/4
"
3/4
"
CW
"ø
3/4
ø H
W
WC
øC
W
ø H
W
HW
1/2
"
3"ø
1'
PER
"
1/4
PE
O
ø
L
S
/2"
11
3985 GEORGIA ST,
SAN DIEGO, CA 92103
ø H
W
1/2
"
ø H
W
1/2
"
HW
"ø
1/2
CW
"ø
3/4
HW
"ø
1/2
HW
CW
3"ø
"ø
1/2
CW
"ø
4
/
3
øC
W
3/4
"
WCW
ø4"Hø
/
"
3
2
1/
ø
3"ø
1/2
"
3/4
"
SK
CW
"ø
1/2
3"ø
WC
"ø
3/4
ø H
W
1 1/2"ø
LAV
11
/2"
HOSE BIB
øC
W
CW
"ø
4
/
3
ø H
W
SK
3"ø
1/2
"
VENT AT ROOF
BT
3/4"ø CW
BATH
1/2
"
3/4"ø CW
3/4"ø CW
3/4
"
HW
"ø
1/2
ø H
W
HW
"ø
1/2
HW
ø
CW
øC
W
3/4"ø CW 3/4"ø CW
1/2
"
"ø
1/2
/2"
11
3"ø
3/4
"
3/4
"
CW
3/4"ø CW
"ø
3/4
CW
1 1/2"ø
SK
CW
"ø
3/4
"ø
1/2
1/2
"ø
øC
W
3/4
"ø
HW
3"ø
HOSE BIB
øC
W
1 1/2"ø
1/2
"
3/4"ø CW
"
3/4
3
TUB / SHOWER PLUMBING
3/4" = 1'-0"
MARK
SS
LAV
WC
BT
HB
DW
WS
F
WH-1
DESCRIPTION
SERVICE SINK
LAVATORY
WATER CLOSET
BATHTUB
HOSE BIBB
DISHWASHER
WASHER/DRYER
FRIDGE
WATER HEATER
WASTE
1 1/2"
1 1/4"
3"
1 1/2"
VENT
1 1/2"
1 1/2"
1 1/2"
1 1/2"
2"
2"
1 1/2"
1 1/2"
1/2"
MATERIAL
PVC
PVC
PVC
PVC
PVC
PVC
PVC
PVC
PVC
NOTES:
1.
PROVIDE WITH THERMOSTATIC MIXING VALVE, SET 100°F
2.
PROVIDE WITH BACKFLOW PREVENTION
3.
PROVIDE WITH INDIRECT AND INDEPENDENT HARD
PLUMBING (COPPER/PVC) TO A FLOOR DRAIN
4.
PROVIDE WITH WATER HAMMER ARRESTOR
4
WATER HEATER DETAIL
NOT TO SCALE
CW
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1"
DATE
DESCRIPTION
ISSUE:
HW
1/2"
1/2"
GAS
FLOW
NOTES
PROJECT NO:
NOTE 1
CAD FILE:
DATE:
1/2"
NOTE 1
1/2"
1/2"
NOTE 2, 4
NOTE 2, 4
DRAWN BY:
Sal Sham
CHECKED BY:
COPYRIGHT:
SHEET TITLE:
1"
NOTE 3
NOTE 3
RISER DIAGRAMS
DRAWING SHEET NO:
P004
CLOSET
CLOSET
BATH
BATH
BEDROOM
BEDROOM
LIVING
LIVING
DINING
DINING
BATH
KITCHEN
DW
DW
BATH
KITCHEN
BEDROOM
REF.
CLOSET
CLOSET
1ST FLOOR GAS PLAN
1/4" = 1'-0"
2
REF.
2ND FLOOR GAS PLAN
1/4" = 1'-0"
3985 GEORGIA ST,
SAN DIEGO, CA 92103
1
GAS
GAS
BEDROOM
CLOSET
BATH
BEDROOM
LIVING
DINING
BATH
DW
MARK
DATE
DESCRIPTION
KITCHEN
ISSUE:
BEDROOM
PROJECT NO:
CAD FILE:
GAS
DATE:
CLOSET
DRAWN BY:
REF.
Sal Sham
CHECKED BY:
COPYRIGHT:
SHEET TITLE:
3
3RD FLOOR GAS PLAN
1/4" = 1'-0"
FLOOR GAS PLANS
DRAWING SHEET NO:
P005
1"ø
1"ø
GAS
117' (167 MBH)
GAS
1"ø
2 1/2"ø
GAS EQUIPMENT SCHEDULE
GR
D
MBH EACH TOTAL
GRILL
1
102
102
WATER HEATER
4
150
600
4 BURNER RANGE
3
90
270
FIRE PIT
1
65
65
DREYER
1
65
65
1"ø
3' (102 MBH)
1 1/4"ø
QTY
97' (257 MBH)
144' (65 MBH)
6' (90 MBH)
"ø
1/2
1 1/4"ø
GAS
EQUIP #
GAS SIZING IS BASED ON A TOTAL GAS LOAD OF 1102
MBH IN STEEL PIPE AT 0.5 PSI ΔP, WITH LONGEST
RUN NOT TO EXCEED 150 FEET.
97' (347 MBH)
6' (90 MBH)
ø
1 1/2"ø
GAS
"
1/2
UTILIT
62' (887 MBH)
60' (1037 MBH)
6' (90 MBH)
2"ø
GAS
87' (437 MBH)
64' (737 MBH)
WH
GAS
WH WH
WH
21
/2"
WH
/2"
21
ø
WH
66' (587 MBH)
"
1/2
ø
WH
ø
21
/2"
UP TO ROOF
WH
2"ø
ø
2"ø
GAS
GR. FLOOR GAS PLAN
1/4" = 1'-0"
18' (1102 MBH)
21
/2"
ø
DR
21
/2"
ø
GAS PIPE INPUT
4
GAS RISER DIAGRAM
1"ø
GAS
GAS LINE
GAS SHUTOFF VALVE
90° ELBOW POINTING DOWN
MARK
DATE
DESCRIPTION
TEE
FLEX GAS HOSE AND QUICK DISCONNECT
ISSUE:
3" (MIN)
PROJECT NO:
GAS
CAD FILE:
DIRT LEG (SEDIMENT
TRAP), 2" MINIMUM
ABOVE FINISHED FLOOR
DATE:
DRAWN BY:
Sal Sham
1"ø
CHECKED BY:
GAS
COPYRIGHT:
1"ø
1
3985 GEORGIA ST,
SAN DIEGO, CA 92103
2"ø
SHEET TITLE:
DOWN TO GROUND FLOOR
GAS
FLOOR GAS PLANS
GAS
1 1/4"ø
GAS CONNECTION
NOT TO SCALE
DRAWING SHEET NO:
ROOF GAS PLAN
2
1/4" = 1'-0"
P006
Download