OPEN CIRCUIT TEST Note: Low voltage side is supplied with rated voltage while high side is left open circuited. Ioc A Vrated Poc V Eoc ɸ N1 W E1 N2 OPEN E2 HV ɸ LV POC = wattmeter reading = core loss, PCO IOC = ammeter reading = open circuit current EOC = voltmeter reading = rated voltage jXeL ReL Im V1 Rm N1 : N2 I2=0 I1=0 jXm E1 E2 Im = Ioc V1 = Eoc Rm Rm jXm Voc 2 Voc 2 = ↔ Xm = Poc Qoc Qoc = √Soc 2 − Poc 2 Soc = Voc Ioc ↔ Poc = Pco SHORT CIRCUIT TEST Note: Low voltage side is short circuited while the high voltage side is supplied with voltage adjusted so that the high voltage side will draw rated current. Isc A Psc V Esc Variable supply W ɸ N1 E1 HV ɸ E2 N2 SHORTED LV ReH jXeH N1 : N2 Im I = rated 1 V1 Rm jXm I2 = rated E1 E2 HV LV Psc = wattmeter reading = copper loss, Pcu Isc = ammeter reading during the test Esc = voltmeter reading during the test jXeH ReH I1 = Isc V1=Esc Pcu (rated) = Psc Psc Esc R eH = 2 ↔ ZeH = Isc Isc XeH = √ZeH 2 − R eH 2 ReH, XeH = equivalent resistance, reactance and impedance respectively referred to the high voltage side of the transformer. EXAMPLE: A short circuit test was performed on a 10 kVA, 2000/400 V single-phase transformer. The instruments indicated 100 V, 5 A and 100 W. determine the equivalent complex impedance of the transformer referred to the low voltage side. SOLUTION: R eH = Psc Isc 2 100 = 2 =4 5 ZeH Esc 100 = = = 20 Isc 5 XeH = √ZeH 2 − R eH 2 = √202 − 42 = 8√6 ZeL = R eH + jXeH 4 + j8√6 = = 0.16 + j0.784 Ω 2 2 a (2000/400) EXAMPLE: In an open circuit test of a 10 kVA, 2400/240 volt, 60 cycle transformer, the low side volts amperes and watts are found to be 240 volts, 0.75 A and 72 watts. The low or secondary side is short circuited when 67 volts is applied to the high side, rated current of 4.17 A flows and the power is 146 watts. Determine the equivalent impedance referred to the low side. SOLUTION: *Since only magnitude of impedance is asked, Esc 67 ZeH = = = 16.07 Isc 4.17 ZeL ZeH 16.07 = 2 = = 0.1607 Ω a (2400/240)2 Note: R m and Xm which can be calculated from the low side are too large compared to R eL and XeL EXAMPLE: A 100 kVA, 6600/330 V, 60 Hz, single phase transformer took 10 A and 436 watts at 100 V in a short circuit test on the high side. Calculate the voltage to be applied on the high voltage side on full load at 0.8 pf lagging when the secondary terminal voltage is 330 V. SOLUTION: Psc 436 R eH = 2 = 2 = 4.36 10 Isc ZeH Esc 100 = = = 10 Isc 10 XeH = √ZeH 2 − R eH 2 = √102 − 4.362 = 9 4.36Ω j9Ω I1 Vp S=100kVA E1 6600 : 330 S 100k I1 = = = 15.15 𝐴 E1 6600 VP =E1 +I1 (Ze1 ) = 6600+(15.15∠ − cos −1 0.8)(4.36 + j9) VP = 6735 V E2 = VL TRANSFORMER LOSSES Core Loss – due to hysteresis and eddy current losses in the magnetic circuit (core) of the transformer Pe = k e V1 2 V11.6 Ph = k h 0.6 f Note: Core loss of a transformer is constant at any size of load. EXAMPLE: The hysteresis and eddy-current losses in a 6.9 kV, 50 Hz transformer are 400 W and 200 W, respectively. What will be the iron loss of this transformer if it is to be connected across a 6.6 kV, 60 Hz source? SOLUTION: V11.6 Ph = k h 0.6 f 6.9k1.6 400 = k h ∗ 500.6 k h = 3.015x10−3 Pe = k e V1 2 200 = k e ∗ 6.9k 2 k e = 4.2x10−6 @ V2 = 6.6kV and f = 60 Hz, 6.6k1.6 −3 Ph = 3.015x10 ∗ = 333.936 W 0.6 60 −6 Pe = 4.2x10 ∗ 6.6k 2 = 201.285 W Piron = Ph + Pe = 333.936 + 201.285 = 535.2 𝑊 EXAMPLE: In a 400 V, 50 Hz transformer, the core loss is 2500 W. when supplied at 220 V, 25 Hz, the corresponding loss is 850 W. Calculate the eddy current loss at normal frequency and p.d. SOLUTION: Pcore V1.6 = Ph + Pe = k h 0.6 + k e V 2 f @ V1 = 400V and f = 50 Hz, 4001.6 Pcore = k h + k e 4002 0.6 50 2500 = 1392.88k h + 160000k e → eqn. 1 @ V2 = 220V and f = 25 Hz, 2201.6 Pcore = k h + k e 2202 0.6 25 850 = 811.17k h + 48400k e → eqn. 2 k h = 0.2405 ; k e = 0.01353 @ VNormal = 400V and f = 50 Hz, Peddy = k e V 2 = 0.0135 ∗ 4002 Peddy = 2165 𝑊