Commissioning of Transformers and Reactors Transportation, Site handling & Commissioning Content • Significance of Rating plate details • Description of equipment and accessories and its role • Pre Commissioning process and various pre-commissioning tests Transformer Basics The induced voltage (V) in a transformer V = 4.44 * N * B * A * f volts Where N = Number of winding turns, B = Flux density value (Tesla) A = Core limb area (m2), f = Frequency of applied voltage(cycles/sec) V1= e1= N1 d / dt V2= e2= N2 d/ dt V1 / V2 = N1 / N2 V1/N1 =V2/N2 Mandatory information on rating plate a) Type of Plate transformer Rating details b) Number of this standard. c) Manufacturer's name, serial number & Year of manufacture. d) Number of phases. e) Rated power, voltages, currents and frequency f) Tapping range and designation with connection arrangement g) Connection and phase displacement symbol h) % impedance i) Type of cooling j) Total mass, Transportation mass Mandatory information on rating plate-continued.. Rating Plate details k) Mass and type of insulating liquid with reference to the relevant IEC standard. l) Maximum system short-circuit power or current m) Insulation levels (withstand voltages) n) Guaranteed maximum temperature rises of top liquid and windings o) Current Transformer details Rating Plate General Arrangement Layout Layout of 3 Phase 400kV Transformer Essential parts of the Transformer • Magnetic circuit- to carry mutual flux • Electric circuit- HV and LV windings • Supporting structure • OLTC & Bushings • Insulation system • Cooling system Active Part The set formed by Core, windings , Clamping Frame, Lead and Support. Current Transformer Top clamping frame HV main lead Winding Tertiary lead Lead Support Winding support assembly Bottom clamping frame HV SIDE Active Part LV main lead Tap-changer Neutral lead Top Frame Tap leads Bottom Frame LV SIDE Shunt Reactors: Shunt Reactors are used in high voltage systems to compensate capacitive generation from long lightly loaded overhead lines The shunt reactor compensates the capacitive generation on power lines to avoid non-controlled voltage rise especially on lightly loaded lines. One critical operating parameters like vibrations and noise. Shunt Reactors: Insulating Oil Used as coolant, transfers heat generated in windings and also acts as insulating medium for Transformer, Reactor, CT and CVT etc. Mineral Oil: Most popular due to low cost and easy availability, basically a fraction, based on carbon type composition petroleum Synthetic Oil: Askarels, Silicon fluids etc -Oil with special parameters like high fire resistance, high permittivity and gas absorbing characteristics Vegetable Oil: offers the benefit of complete biodegradability and it's also less flammable than mineral oils. It is extracted from plants like soy, or sunflowers, which makes it biodegradable. Bushings in POWERGRID Based on Condenser CoreOIP RIP Solid Based on Conductor Draw Rod Draw Lead Solid Stem Bushings in POWERGRID Contd… Based on Application Oil-Air OIP bushings Oil-SF6 RIP Bushings Oil to Oil RIP bushing Oil-Air Solid Bushing OLTC & Driving Mechanism Conservator Tank Other Accessories PRD OTI & WTI Buchholz Relay OSR MOG Breather Step to commissioning Contents of the Presentation Transportation & Site arrival checks Storage & Installation Vacuum drying and oil filling Pre-commissioning Testings Post-commissioning activities Transportation Mode of Transportation • By Rail • By Ship • By Road Impact Type Onboard Rail • • Impacts in longitudinal axis during shunting operations and vertical shocks due to rail joints Normally acceleration from 0.5 to 1.0 g in 2-500 Hz band is experienced, however during shunting operation acceleration up to 4.0g in 2-20 Hz band can be experienced Onboard a Ship • • • Rolling, Pitching and Yawing low frequency vibrations repeating at regular periods. Normally acceleration from 0.3 to 0.8 g in 2-30 Hz band is experienced. Impact Type Onboard a Trailer • • Impacts in longitudinal axis during braking operations and vertical and lateral shocks due to road conditions. Normally acceleration from 0.5 to 1.0 g in 3-350 Hz band is experienced. During Loading/unloading &Rigging • • Low occurrence, high magnitude impact (like lifting gear failure, dropped Transformer). Shock events from 2.5 to 10.0 g in 2-20 Hz band are experienced. Impact during Transit Impact Issues Visible Damage:- Leading to on site or factory repairs Conceal Damage:- Causing out of warranty failure Damages occur because of :Acceleration Amplitude : a Change of velocity : Δv Duration: t Digital Impact Recorder TS representation on Impact Recorder • Transformer to be fitted with Electronic impact recorders (on returnable basis) at least 2 numbers for 400kV Class Transformer and 1 number for below 400kV class Transformers • Could measure the magnitude and duration of the impact in all three directions. • The acceptance criteria and limits of impact, which can be withstood by the equipment during transportation and handling in all three directions, shall not exceed“3g” for 50mSec (20Hz) or as per contractor standard, whichever is lower What to check? Check the setting of Impact Recorder Setting for range, wake & Alarm Journey Start date, end date and record duration Acceptable limit of mechanical shock is ‘ 3g for 50 ms’ on any direction Downloading and analysis of impact recorder data Impact Recorder Analysis: Shockwatch Impact Recorder Analysis: Monilog Check at site Transit Damage Healthy Locating pin and insulation Transport Modes Oil Filled Nitrogen Gas / Dry air filled When oil filling would exceed the permissible or economical maximum transport weight Customer Requirement Checks on Transformer upon arrival at site Visual external inspection. In case of any abnormality like broken glass on gauges, broken welds, Paint finish damage, same needs to be referred to manufacturer/ region/ CC Nitrogen/ Dry air pressure & dew point check or oil level check if transported in oil filled condition and compare with factory data Nitrogen pressure to be maintained minimum 0.175 kg/sq cm( 2.5 psi) during Transportation. Measurement of core insulation resistance to ground. (Min. Acceptable value : 500MΩ) Document to be referred Contract document & Technical specification for obtaining detailed scope of work Manufacturer Procedures Installation Manuals/ For guidance and uniformity across all substation in POWERGRID “Pre Commissioning Procedures and Formats for Switchyard Equipments :D-2-01-03-01-05” have been made. Activity Flowchart for commissioning Oil Filtration plant : Precaution to be taken Changing of Lubricating oil of vacuum pump Cleaning of Filter packs Flushing of whole filter machine with fresh oil Checking of vacuum obtained without load (milli bar) Silica gel breather to be provided in the tank All erection activity to be carried out with continuous purging of dry air in the main tank Internal Inspection: Should Include • Removal of any shipping blocking or temporary support. • Examination for indication of core shifting. • Tests for unintentional core or core clamp grounds. • Visual inspection of windings, leads, and connections including clamping, bracing, blocking, spacer alignment, phase barriers, oil boxes, and coil wraps. • Inspection of Dead End Tap Changer and in-tank LTCs including contact alignment. • Inspection of current transformers, including supports and wiring harness. • Checks for dirt, metal particles, moisture, or other foreign material. Internal Inspection: Findings Leakage Test through pressure Fill dry N2/ dry air till pressure of 4- 5psi (.3 kg/cm2 ) is achieved and to be kept for 24 Hrs In case pressure remain same, record dew point Proceed for evacuation if no drop in pressure is observed In case of drop in pressure, attend the leakages by applying soap water solution in all valve opening and repeat the pressure test Vacuum drop & Tightness Test Starting of evacuation on complete unit Stopping of evacuation near the pressure of 5 kPa (50 mbar) Note the Pressure as P1 in kPa after 1 hour of stopping evacuation Note the Pressure Pressure P2 in kPa after half an hour of reading pressure P1 Calculate drop in vacuum = (P2-P1) x V , V= Oil quantity Allowable Leakage of less than 150 mm Hg liters per minute ( 20 m3 Pa/min). If the leakage rate exceeds 20 m3 Pa/min or the vacuum does not hold, then the leak in the transformer system shall be located and arrested Vacuum drying and N2 purging cycle • Continue Vacuum till pressure of 0.13kPa(1 Torr) is achieved and then retain it for the 72-96 hrs for 420 kV and above equipment • Break of vacuum and purge N2/ Dry air of dew point -50° or better and retain it for 48 hrs • Check for dew point • If acceptable, then proceed for oil filling Transformer HV Rated Voltage (in kV) Up to 145kV 145 kV and 246 kV Above 420 kV Application of Vacuum & holding for (before oil filling)*(in Hours) 12 HRS 24 HRS STANDING TIME After Oil circulation and before energising (in Hours) 12 HRS 48 HRS 48 HRS 120 HRS Oil Filling in Conservator Oil Filling Parameter prior be to filling in main tankto filling in Each lot Oil of the oil shall tested prior main tank at site for the following: Break Down voltage (BDV) Moisture content Tan-delta at 90°C Interfacial tension 70 kV (min.) 5 ppm (max.) 0.0025 (Max) 0.04 N/m(Min) Oil Parameter After filtration & settling prior to energisation 1 2 3 4 5 Break Down voltage (BDV) Moisture content Tan-delta at 90°C Interfacial tension *Oxidation Stability a) Acidity a) Sludge a) Tan delta at 90 °C 70 kV (min.) 5 ppm (max.) 0.005 (Max) More than 0.04 N/m 0.3 (mg KOH /g) (max.) 0.05 % (max.) 0.05 (max.) * Test results can be submitted within 45 days after commissioning Other Checks on Oil Furan Should not be traced Particle Counts As per TS Resistivity at 90 °C 6 X 10 ^12 ohm-cm (min.) Total Gas Content < 1% Pre-commissioning Tests C & Tan δ measurement on bushings & winding Variable frequency Tan delta of bushing is mandatory Frequency response analysis Voltage ratio test, Vector Group& Polarity checking Magnetization current test Magnetic Balance test( for 3-ph unit) IR measurements-PI & DAI Core Insulation Tests Winding resistance measurement Operational tests on OLTC, Cooler Banks Tests on Bushing CTs IR, Continuity, Polarity Current Ratio/ Magnetization curve Protection & alarm tests Electrical Tests and DGA Diagnostic Matrix Bushings Tap changer Windings Core Insulation equivalent circuit Conductor equivalent circuit Re1 Lf1 Lf2 Re 2 Rf X CHL High Voltage Winding CH Low Voltage Winding CL Core & Tank Ref: CIGRE Brochure No.445 Capacitance and Tan δ measurement This test provide an indication of quality and soundness of the insulation in bushing /winding Dielectric losses in the insulation are caused by: • Conductive Losses: Transport of Electrons and Ions • Polarization Losses: Through Interfacial Polarization Effects • Partial Discharges: Local discharges Measurement Set up Frequency dependency of Capacitance and Tan δ Influence of Conductivity (Polarization Effects Dominating Dielectric with Notable Conductivity Effects Dielectric Frequency Response It is used for determining moisture content and aging of press board and Paper DFR Application Areas • Power transformers • Instrument transformers • Bushings International guidelines Frequency Domain Spectroscopy • Capacitance and power factor measurements at variable frequency (1 kHz down to 0.1mHz) • • Same preparation as for capacitance and power factor Measurements Same procedure as in capacitance and power factor Measurements • Performed at relatively low voltage, typically 140 V(RMS)/ /1.4kV(RMS) Dielectric Frequency Response Response of Transformer Bushing Diagnosis methods Power frequency Capacitance(C) and Tan Acceptance value Oil Impregnated paper (OIP) Insulation Type Resin Impregnated paper (RIP) IEC-60137 < 0.7% <0.7% IEEE C57.19.01 < 0.85% <0.5% Typical New Values 0.3-0.4% 0.2-0.4% IEEE 62.1995 0.1%(Rise) 0.1%(Rise) Above values are corrected to 20° C Tan response bushing Tan delta in % 10 Faulty Bushing 1 Healthy Bushing 0,1 0,022 0,046 0,1 0,22 0,46 1 2,2 4,6 10 Frequency in Hz 20 42 60 90 220 470 1000 Capacitance response of bushing Capacitance pF 700 650 Healthy Bushing 600 550 Faulty Bushing 500 Frequency in Hertz X-Wax formation Bridging of conductive layers Frequency Response Analysis: FRA represents a systems response to a sinusoidal input at varying frequencies FRA Principle: Transformer can be modelled as a network of capacitance, resistance, self- and mutual inductances. Any alteration in these parameters, FRA response will also change accordingly IFRA – Impulse Frequency Response Analysis This uses an impulse voltage source, it is quick but has inherent repeatability problems and is therefore not the preferred method for general use. SFRA – Swept Frequency Response Analysis Uses a swept frequency voltage source, although slightly slower than IFRA is repeatable and the results are easily comparable between any test equipment used. Frequency Response Raw Data 1.1 -> N Raw Data 1.1 -> N 10 10,000,000 1 0.1 100,000 Impedance [Ohm] Admittance [mS] 1,000,000 0.01 10,000 0.001 1,000 0.000 10 100,000 10,000 Frequency [Hz] 1,000 100 1,000,000 100 10 10,000,000 100 Impedance 1,000 10,000 Frequency [Hz] 100,000 1,000,000 10,000,000 Admittance Phase Angle H(θ) = Tan-1 ( Vout/Vin) Raw Data 1.1 -> N -15 Raw Data -20 1.1 -> N -25 180 -30 160 -35 140 -40 120 -45 100 -50 80 -55 60 40 -60 Phase [°] Magnitude [dB] The ratio between the response signal (Vout) and the reference voltage (Vin), represented as Gain (DB’s) plotted against frequency is the required SFRA curve. -65 -70 20 0 -20 -75 -40 -80 -60 -85 -80 -90 -100 -120 -95 -140 -100 -160 10 100 1,000 10,000 Frequency [Hz] 100,000 Magnitude 1,000,000 10,000,000 10 100 1,000 10,000 Frequency [Hz] 100,000 1,000,000 Phase Difference 10,000,000 Core insulation check • • • • To ensure isolation between core-frame and tank Allows for investigating accidental grounds which results in circulating currents if there is more than one connection between the core and ground. Desire value minimum 1000M To be corelated with DGA results Insulation Resistance Measurement Purpose : To check the condition of insulation ( degree of dryness of paper insulation) and presence of any foreign contaminants in oil Absorption Coefficient: IR (60 sec)/ IR(15 sec ) Polarization Index: IR (600 sec)/ IR(60 sec ) I(t)=Ic(t)+Ia(t)+Ir Insulation Resistance Measurement For Class A insulation in reasonably dried condition DAI at 30 C should be more than 1.3. Even if insulation is dry, IR value may be low due to low resistivity of oil. Time diagrams of good and bad insulation tested Turns Ratio/ Polarity Test • The turns ratio of a transformer is the ratio of the no. of turns in a higher voltage winding to that in a lower voltage winding. • The voltage ratio of a transformer is the ratio of the rms terminal voltage of a higher voltage winding to the rms terminal voltage of a lower voltage winding. • For all practical purposes, when the transformer is on open circuit, its voltage and turns ratio may be considered to be equal. • Polarity is determined by the internal connections and is indicated on the name plate. The polarity of transformer is of interest when it is to be connected in parallel with one or more other transformers. Exciting/ Magnetising Current Test • Exciting/Magnetizing current is the current required to force a given flux thorough the core. • Normally done before DC measurements to avoid the effect of residual magnetism • Transformer under test may be demagnetized before commencement of this test. Results •between similar single phase units/phases:10% •As compared to previous tests : 25%. •The test values on the •outside legs should be within 15 % of each other, and values for the centre leg should not be more than either outside for a threephase transformers Magnetic Balance Test This test is conducted only in three phase Transformers to check imbalance in magnetic circuit V1 V2 V3 Transformer neutral to be disconnected from ground & apply 230V across one phase and measure voltage in other two windings Ensure V1 = V2+V3 Very negligible voltage induced to be investigated Winding Resistance Measurement • The transformer winding resistance is measured at site to check • Physical displacement or distortion of winding • Abnormalities due to loose connections • Broken strands or short-circuited turns • High contact resistance in tap changers • As the transformer resistance is low resistance, the measurement is done with the help of Kelvin Double Bridge/ Transformer Ohm Meter. Winding resistance at 75deg c may be calculated • R75=Rt(235+75)/(235+t) , Where Rt= Resistance measured at winding temp t The comparison of readings with other phases, duplicate transformers or previous measurements should be done and variations under field conditions should not exceed 5%.